6 Distance Protection / 7SA513

SIPROTEC 7SA513
Distance Protection Relay for Transmission Lines
Function overview

Protection functions
• Non-switched distance protection
with 6 measurement systems
• Fault locator
• Sensitive earth-fault protection for
high-resistance earth faults in earthed
networks
• Backup overcurrent-time protection
• Overvoltage protection
• Auto-reclosure

LSP2321-afp.tif
• Teleprotection (pilot protection)
• Synchro-check
• Breaker failure protection
• Power swing blocking/tripping
• Switch-onto-fault protection
Fig. 6/81 • Weak-infeed protection
SIPROTEC 7SA513 distance protection relay 6
Features
• Tripping time 18 ms at 50 Hz
Description • Adaptive measurement algorithms
with reliable fault loop selection
The 7SA513 numerical distance protection
• Dynamically unlimited directional
relay provides selective and fast clearance
sensitivity
of faults on overhead lines and cables with
single and multiple end infeed in high and • Suitable for lines with series capacitors
extra high voltage networks with any type • Compensation for the influence of a
of meshing. The neutral point can be parallel line in case of earth faults
earthed, compensated or isolated. The • Non-volatile storage of events
main function is a fast non-switched dis-
tance protection with a polygon fault de- Monitoring functions
tection and tripping characteristic. • Self-supervision of the relay
A fault detection program with a V / I / ϕ • Measured-value supervision
characteristic is also available instead of the • Event logging
polygon fault detection characteristic. The • Fault logging
unit also incorporates all functions usually
required for line protection. It can also be • Oscillographic fault records
used as backup distance protection for all Front design
types of differential protection equipment. • User-friendly local operation
The unit can be integrated both into con-
ventional installations and into SICAM • 30 LEDs for local alarm
substation control and protection systems. • PC front port for convenient
relay setting
The serial system interface protocol used
conforms to IEC 60870-5-103. Communication interfaces
• Front interface for connecting a PC
• System interface for connecting to a
control system via IEC 60870-5-103 or
DIN 19244 protocol
Hardware
• Analog inputs:
– 5 current transformers
– 7 voltage transformers
• Binary inputs: 16/24
• Binary outputs: 22/33

Siemens SIP · 2004 6/81


6 Distance Protection / 7SA513

Application ANSI Protection functions


21 21N Distance protection
The 7SA513 numerical distance protection
relay provides selective and fast clearance FL Fault locator
of faults on overhead lines and cables with 50N 51N Directional earth-(ground)
single and multiple end infeed in high- fault overcurrent protection
voltage networks with any type of meshing.
The neutral point can be earthed, compen- 67N Directional earth-(ground)
fault overcurrent protection
sated or isolated. The main function is a
fast non-switched distance protection with 50 51 Backup overcurrent-time protection
a polygon fault detection and tripping 68 68T Power swing detection/tripping
characteristic. A fault detection program
with a V / I / ϕ characteristic is also avail- 85 21 Teleprotection for distance protection
able instead of the polygon fault detection 27WI Weak-infeed protection
characteristic. The unit also incorporates
85 67N Teleprotection for earth-fault protection
all functions usually required for line pro-
tection. It can also be used as backup over- 50HS Switch-onto-fault protection
current and distance protection for all 50BF Breaker failure protection
types of differential protection equip-
ment. The unit can be integrated both 59 Overvoltage protection
into conventional installations and into 25 Synchro-check
SICAM substation control and protection
79 Auto-reclosure
systems.
6

Fig. 6/82 Function diagram

6/82 Siemens SIP · 2004


6 Distance Protection / 7SA513

Construction

The compact 7SA513 distance protection re-


lay contains all the components required for
analog value acquisition and evaluation, the
operating and display panel, indication and
command outputs, binary input options,
serial interfaces and auxiliary voltage con-
verters. The use of a powerful 32-bit signal
processor combined with a 16-bit standard
processor permits integration of numerous
protection functions into a compact device.
Three housing versions can be supplied. The
version for panel surface mounting is fitted
with double-tier terminals accessible from
the front. The versions for panel flush
mounting or cubicle mounting have con- Fig. 6/83 Fault detection
necting elements at the rear and are available polygon for polygon
with or without a glass cover. impedance (Z<)

Protection functions 6
Distance protection
The main function of the 7SA513 protec-
tion relay is a non-switched distance pro-
tection. By parallel calculation and
monitoring of all six impedance loops a
high degree of sensitivity and selectivity is
achieved for all types of fault. The shortest
command time is less than one network
cycle.
The fault detection characteristic used is
the polygon impedance fault detection Z<.
The shape of the fault detection polygon
permits optimum adaptation to the load
conditions on the protected line. Starting Fig. 6/84 Characteristics of the voltage and angle-dependent overcurrent fault detection V/I/ϕ
of unfaulted loops is eliminated to prevent
the adverse influence of currents and volt-
ages in the fault free loops. Overcurrent
fault detection can be activated in parallel
to the polygon impedance fault detection.
As an option to the polygon impedance
fault detection, voltage and angle-depen-
dent overcurrent fault detection may also
be used. This V / I / ϕ characteristic uses
the phase voltages Vph-E or the line voltages
Vph-ph depending on the phase angle ϕ and
the phase current Iph according to the se-
lected mode of starting.

Fig. 6/85 Tripping characteristics


of the distance
protection

Siemens SIP · 2004 6/83


6 Distance Protection / 7SA513

Protection functions

Distance protection (continued)


The polygon tripping characteristic per-
mits separate setting of the reactance X and
the resistance R. The resistance section R
can be set separately for faults with and
without earth involvement. Earth faults are
detected by monitoring the earth current
IE, the negative-sequence current I2 and/or
the displacement voltage VE.
Five distance zones can be set forward,
reverse or non-directionally, two of them
as overreach zones for auto-reclosure and
permissible tripping schemes. For each dis-
tance zone a time stage is available for the
directional and non-directional character-
Fig. 6/86
istic (a total of 10 independent time
Polygon for power
stages). swing detection
Compensation for load current and paral-
lel lines is included.
6 Digital filtering of the measured values • Permissible overreach with overreach Weak-infeed protection
zone Z1B – echo and/or trip
makes the unit insensitive to disturbances
in the measured values. In particular the • Direction comparison with directional To prevent delayed tripping of permissible
influence of DC components, capacitive fault detection schemes during weak or zero infeed situa-
voltage transformers, series compensated tions, an echo function is provided.
• Unblocking mode with overreach zone Z1B
lines and frequency changes is reduced.
• Unblocking mode with directional fault If no fault detector picks up at one end of
Sound phase polarization and voltage detection the line, the signal received here is returned
memories provide dynamically unlimited as echo to allow accelerated tripping at the
directional sensitivity. Phase-selective • Blocking mode other end of the line.
1-pole or 3-pole tripping is possible when • Overreach zone comparison via pilot wires It is also possible to initiate tripping at the
used with 1-pole or 1 and 3-pole rapid or
delayed auto-reclosure scheme. • Reverse interlocking weak-infeed end. At the end of the line
where the fault detector does not pick up,
Following the loss of V.T. voltage inputs, The transient blocking function is provided a phase-selective 1-pole or 3-pole trip is
the distance protection can be blocked auto- with overreaching schemes to operate with issued if a corresponding drop in the
matically to prevent incorrect operation. transient or current reversals resulting from phase-earth voltage is present.
the clearance of short circuits on parallel
lines.
Fault locator Overcurrent protection as a backup func-
tion and emergency function during mea-
The fault locator calculates the fault imped- Power swing detection sured voltage failure
ance and the distance-to-fault. The result
can be displayed in ohms, kilometers or per- During network power swings, large cur- The 7SA513 protection relay includes
cent of the line length. Parallel line and load rents can occur along with small voltages. overcurrent protection. It can be used as a
current compensation are also available. Small voltages and large currents imply backup function and as an emergency
small impedances which can cause un- function in the event of a short-circuit or
wanted tripping of distance protection interruption in the voltage transformer
Tele (pilot) protection
relays. To avoid uncontrolled tripping by secondary circuit or if the circuit-breaker
for distance protection
the distance protection and to achieve con- of the voltage transformer (VT mcb) trips.
For fast selective clearance of faults up to trolled tripping in the event of loss of syn- The settings for the emergency function
100 % of the line length a signal transmis- chronism (pole slip), a power swing may differ from those of the backup pro-
sion function is available. The following detection function is available for the tection function. The overcurrent protec-
modes may be selected: 7SA513 protection relay. tion can be set as two-stage definite-time
• Permissible underreach transfer trip The following operating modes for overcurrent protection or as inverse-time
with fault detection network power swings can be set: overcurrent protection.

• Zone acceleration with Z1B • Power swing blocking to prevent the


distance protection from tripping
• Power swing tripping for controlled
tripping in the event of unstable power
swings (out-of-step protection).

6/84 Siemens SIP · 2004


6 Distance Protection / 7SA513

Protection functions High-resistance earth-fault protection Overvoltage protection


in an earthed network
Switch-onto-fault protection On very long EHV lines that carry no or
In earthed networks where high-resistance light loads, impermissible overvoltages can
Instantaneous tripping is required when earth faults can occur, the fault detection occur due to the Ferranti effect. For protec-
energizing a faulty line. Initiation of the bi- of the distance protection may not be sen- tion against these overvoltages the 7SA513
nary input “Manual Close” will, depending sitive enough. The 7SA513 protection relay line protection relay contains a two stage
on the setting, result in instantaneous trip- has protection functions for high- overvoltage protection. Compounding can
ping in Z1, Z1B or with fault detection. resistance earth faults of this nature. Only be set for the V> stage that calculates the
On definite, large current faults, the high one of these functions can be active at one voltages at the remote end of the line.
current instantaneous stage can initiate very time: Tripping can be performed at the local cir-
fast 3-pole tripping even if the binary input cuit-breaker or at the remote end of the line
• Directional or non-directional earth-fault by transmission of an intertripping signal.
“Manual Close” is not initiated. protection with definite-time overcurrent
characteristic Breaker failure protection
Auto-reclosure
• Directional or non-directional earth-fault The 7SA513 relay incorporates a single-
The 7SA513 relay is equipped with auto- protection with inverse-time overcurrent
reclosure (AR). The range of functions in- stage breaker failure protection function to
characteristic
cludes: detect failure of tripping command
• Directional or non-directional earth-fault execution, for example due to a defective
• 3-pole RAR/DAR1) for all types of faults protection with voltage-dependent char- circuit-breaker. The current detection logic
acteristic (V0 inverse characteristic). is phase-selective and can therefore also be
• 1-pole RAR for 1-phase faults, no
used in single-pole tripping schemes. If the
reclosing for multi-phase faults To implement a directional comparison
scheme, the directional earth-fault func-
fault current has not been interrupted after 6
• 1-pole RAR for 1-phase and 2-phase faults a set time delay has elapsed, the busbar trip
tion can be supplemented with a signal
without earth, no reclose for multi-phase command is generated.
transmission logic.
faults
• 1-pole RAR for 1-phase and 3-pole Earth-fault direction detection is performed Parameter set switchover
RAR/DAR for multi-phase faults with residual current and residual voltage.
It is possible to switch between four differ-
In addition or as an alternative to the resid-
• 1-pole RAR for 1-phase and 2-phase faults ual voltage, the star point current (IY) of an
ent parameter sets via the binary inputs,
without earth and 3-pole RAR/DAR for the integrated operating panel or the serial
earthed transformer may be used for polar-
other faults operating interface. In this way it is possi-
ization of the directional earth-fault func-
ble to adapt the protection relay settings if
• Multiple-shot DAR tion. A phase selector permits single-pole
the network configuration has been chang-
tripping by the earth-fault protection in the
• Interaction with an external device for ed by switching actions.
event of single-phase earth-faults in con-
auto-reclosure via binary inputs and
junction with 1-pole auto-reclosing. Parameter set switchover is also possible
outputs
via the compatible IEC 60870-5-103
• Control of the integrated AR function by Synchro-check system interface protocol.
external protection
When connecting two network sections by
• AR blocking for faults on the cable por- control command or following a 3-pole
tion of mixed cable/overhead lines auto-reclosure, it must be ensured that the
• Interaction with an internal or external two network sections are synchronized. For
synchro-check this purpose, a synchro-check function is
provided. After verification of network syn-
• Monitoring of the circuit-breaker auxil- chronism, the function enables the CLOSE
iary contacts.
command. Alternatively, reclosure can be
enabled after checking that the busbar or
line is not carrying a voltage (dead line or
dead bus).

1) RAR – Rapid auto-reclosure


DAR – Delayed auto-reclosure
AR – Auto-reclosure.

Siemens SIP · 2004 6/85


6 Distance Protection / 7SA513

Communication

Serial interfaces
The relay is equipped with two serial
interfaces.
The operating interface on the front
panel is suitable for connecting a Win-
dows-capable PC. The DIGSI
operating and analysis software allows easy
setting, fault recording evaluation and
commissioning. The system interface is
an 820 nm fiber-optic interface for linking
to the SICAM substation control and pro-
tection system or a protection master unit
(protocol) according to IEC 60870-5-103.
The operator with DIGSI can also be con-
nected to the system interface.

6 Fig. 6/87
Telecontrol of protection equipment with a PC via modem, telephone channel and star coupler

6/86 Siemens SIP · 2004


6 Distance Protection / 7SA513

Technical data

General unit data Command contacts


Analog inputs Number of relays per input/output 2 (marshallable)
Rated current IN 1 or 5 A module with 2 NO contacts each

Rated voltage VN 80 to 125 V AC Switching power


Make 1000 W / VA
Rated frequency fN 50 or 60 Hz Break 30 W / VA
Thermal overload capacity Switching voltage 250 V AC/DC
In V.T. circuits, continuous 140 V AC
permissible current
In C.T. circuits, continuous 4 x IN
Continuous 5A
for 1 s 100 x IN
0.5 s 30 A
Maximum dynamic overload 250 x IN
LEDs
Power consumption
Ready = green 1
Voltage inputs Approx. 0.5 VA
Current inputs at IN = 1 A Approx. 0.1 VA Faulty = red 1
at IN = 5 A Approx. 0.5 VA Converter healthy = green 4
Power supply (via integrated converter) Marshallable displays per 8
Rated auxiliary voltage Vaux 48, 60 V DC input/output module = red
(working range) 110, 125 V DC
220, 250 V DC
Serial interfaces
Permissible tolerance of the –20 to + 15 %
rated auxiliary voltage Vaux Operating interface On the front, not isolated, suitable

Max. ripple at VauxN ≤ 12 %


for connecting a personal computer 6
Baud rate 1200 to 19200 baud
Power consumption
System interface Isolated, suitable for linking
Quiescent Approx. 15 W
to a central unit
Energized Approx. 40 W
Baud rate 1200 to 19200 baud
Max. bridging time during ≥ 50 ms at Vaux ≥ 110 V
auxiliary voltage failure Fiber-optic connection Integrated FSMA connector
for FO connection with ceramic
Input/output modules connector
Quantity 2 or 3 Optical wavelength 820 nm
Binary inputs Permissible line attenuation Up to 8 dB per glass fiber 62.5/125
Distance µm
Number per input/output module 8 (marshallable)
Up to 2 km
Voltage range, 24, 60 V DC
Unit design
can be set with jumpers 110, 125 V DC
220, 250 V DC Housing, dimensions 7XP20, see dimension drawings,
part 16
Current consumption Approx. 3 mA
Degree of protection to EN 60529
Alarm contacts
Housing IP 51
Number of relays per input/output 9 standard relays or Terminals IP 21
module each with 1 changeover 6 standards relays and
Insulation tests (IEC 60255-5, DIN VDE 0435, Part 303)
contact 1 Reed relay;
all relays can be marshalled Voltage test (100 % test), all circuits 2 kV (RMS value), 50 Hz
except for auxiliary voltage
Switching capacity of the standard 20 W / VA
relays make/break Voltage test (100 % test), 2.8 kV DC
only auxiliary voltage
Permissible current for standard 1A Surge voltage test (type test), 5 kV (peak value), 1.2/50 µs, 0.5 J,
relays, continuous all circuits, class III 3 positive and 3 negative surges
at intervals of 5 s
Switching voltage for standard relays 250 V AC / DC
EMC tests for noise immunity; type tests
Switching power of the Reed relays 15 W / VA
make/break Standards:
IEC 60255-22 (product standard) /
Permissible current for Reed relays, 0.3 A
EN 50082-2 (generic standard) /
continuous
DIN VDE 0435, Part 303
Switching voltage for Reed relays 220 V AC / DC
High-frequency test 2.5 kV (peak value), 1 MHz,
Permissible load circuit capacitance Max. 5 nF IEC 60255-22-1, class III and τ = 15 µs, 400 pulses per s,
for Reed relays DIN VDE 0435 Part 303, class III test duration 2 s
Electrostatic discharge 4 kV/6 kV contact discharge,
IEC 60255-22-2, class III and 8 kV air discharge, both polarities,
EN 61000-4-2, class III 150 pF, Ri =330 Ω
Irradiation with high-frequency 10 V/m, 27 to 500 MHz
field, unmodulated

Siemens SIP · 2004 6/87


6 Distance Protection / 7SA513

Technical data

IEC 60255-22-3 (report), class III Functions


Irradiation with high-frequency 10 V/m, 80 to 1000 MHz, Distance protection
field, amplitude-modulated 80 %, 1 kHz, AM Setting ranges
ENV 50140, class III Earth-fault detection 0.1 to 1 (in steps of 0.01)
Irradiation with high-frequency 10 V/m, 900 MHz, repetition rate Earth current IE / IN
field, pulse-modulated 2000 Hz, ED 50 % Displacement voltage
ENV 5014/ENV 50204, class III VE > (= 3 x V0, 2 to 100 V (in steps of 1 V)
Fast transients, bursts 2 kV, 5/50 ns, 5 kHz, burst length = earthed networks)
IEC 60255-22-4 and 15 ms, repetition rate 300 ms, both VE > (= 3 x V0, 10 to 100 V (in steps of 1 V)
EN 61000-4-4, class III polarities, Ri = 50 Ω, test duration 1 unearthed networks)
min Impedance start (Z<)
Line-conducted high frequency, 10 V, 150 kHz to 80 MHz, 80 %, Characteristic Polygon
amplitude-modulated 1 kHz, AM Range forward X+ 0.1 to 200 Ω1) (in steps of 0.01 Ω)
ENV 50141, class III Range backward X– 0.1 to 200 Ω1) (in steps of 0.01 Ω)
Resistance R 0.1 to 200 Ω1) (in steps of 0.01 Ω)
Magnetic field 30 A/m, continuous, 300 A/m for 3 s, Limit angle between
with power frequency 50 Hz load and short-circuit range 30 to 80 ° (in steps of 0.1 °)
EN 61000-4-8, class IV Minimum current Iph> / IN 0.1 to 4 (in steps of 0.01)
EMC tests for interference emission; type tests Overcurrent Iph>> / IN 1 to 20 (in steps of 0.01)
Standards: Voltage and angle-dependent
EN 50081-2 (generic standard) overcurrent start (V/I /ϕ)
Phase-to-earth voltage
Conducted interference voltages, 150 kHz to 30 MHz
6 only
Vph-E (I>) in steps of 20 to 70 V (in steps of 1 V)
Phase-to-earth voltage
auxiliary voltage, CISPR 11,
Vph-E (I>>) 20 to 70 V (in steps of 1 V)
EN 55011, limit value A and
Phase-to-phase voltage
DIN VDE 0875, Part 11, limit value
Vph-ph (I>) 40 to 130 V (in steps of 1 V)
A
Phase-to-phase voltage
Radio interference field strength 30 to 1000 MHz Vph-ph (I>>) 40 to 130 V (in steps of 1 V)
CISPR 11, EN 55011, limit value A Minimum current
and DIN VDE 0875, Part 11, limit Iph> / IN 0.1 to 1 (in steps of 0.01)
value A Overcurrent Iph>> / IN 0.25 to 4 (in steps of 0.01)
Limit angle between
load and short-circuit
Climatic stress test range ϕ 30 to 60 ° or 90 to 120 °
Permissible ambient temperature Distance measurement
During operation –5 to + 55 °C Characteristic Polygon
During storage –25 to + 55 °C
Distance zones 5, 2 of these as overreach zones and
During transport –25 to + 70 °C
all can be set forward, backward or
Humidity stress Average annual relative humidity non-directional
≤ 75 %, on 30 days per year up to
Range X 0.05 to 130 Ω (in steps of 0.01 Ω)
95 % relative humidity, condensation
not permissible Resistance R
For phase-to-phase fault 0.05 to 65 Ω (in steps of 0.01 Ω)
For phase-to-earth fault 0.05 to 130 Ω (in steps of 0.01 Ω)
Mechanical stress test Time stages 7 for multi-phase faults
IEC 60255-21-1, IEC 60068-2 3 for single-phase faults
Permissible mechanical stress Ranges 0 to 32 s or deactivated
During operation 10 to 60 Hz, 0.035 mm amplitude (in steps of 0.01 s)
60 to 500 Hz, 0.5 g acceleration Earth impedance matching
During transport 5 to 8 Hz, 7.5 mm amplitude X E RE –7 to 7 (in steps of 0.01)
8 to 500 Hz, 2 g acceleration ,
X L RL
Parallel line matching
X M RM –7 to 7 (in steps of 0.01)
,
X L RL
Load current compensation –
Direction detection for all types of With sound phase polarization
faults and voltage memory dynamically
Directional sensitivity unlimited
Times
Shortest command time Approx. 18 ms at fN = 50 Hz
Shortest command time Approx. 16.5 ms at fN = 60 Hz
Reset time
After TRIP command Approx. 25 ms
1) Impedance settings refer to IN = 1 A; After reset without Approx. 30 ms
at IN = 5 A these values must be divided by 5. TRIP command

6/88 Siemens SIP · 2004


6 Distance Protection / 7SA513

Technical data

Distance protection (continued) Overcurrent-time protection


Tolerances Characteristic Definite-time overcurrent protection,
Measuring tolerances to inverse-time overcurrent protection
DIN VDE 0435, part 303 (for Applications As backup protection function, as
sinusoidal measured quantities) emergency function with automatic
For impedance start ∆X ≤ 5 % for 30 ° ≤ ϕ ≤ 90 °
sc activation following measured voltage
X
∆R ≤ 10 % for 0 ° ≤ ϕ ≤ 60 ° failure or voltage transformer mcb trip
sc
R Setting range of definite-time
For distance measurement ∆X ≤ 5 % for 30 ° ≤ ϕ ≤ 90 ° overcurrent protection
sc
X
High set Phase Iph>>/IN 0.1 to 9.99 (in steps of 0.01)
∆R ≤ 5 % for 0 ° ≤ ϕ ≤ 60 °
sc Earth IE>>/IN 0.1 to 4 (in steps of 0.01)
R
Overcurrent Phase Iph>/IN 0.1 to 9.99 (in steps of 0.01)
For amplitude measurement ±5% Earth IE>>/IN 0.1 to 4 (in steps of 0.01)
Timer accuracy ± 1 % of setting value or 10 ms
Instantaneous high-current switch-onto-fault protection
High current start Isc> / IN 1 to 25 Times tI>, tIE>, tI>> 0 to 32 s (in steps of 0.01 s)
or deactivated
Shortest command time Approx. 11 ms Shortest command time Approx. 30 ms
Fault locator Setting range of inverse-time
Output of the distance to fault In Ω secondary, Ω primary, km, % overcurrent protection
Start of calculation Trip, pickup reset, binary input High set Phase Iph>> / IN 0.1 to 9.99 (in steps of 0.01)
Setting reactance per unit in 0.01 to 5 Ω/km (DT) Earth IE>>/ IN 0.1 to 4 (in steps of 0.01) 6
steps of 0.01 Ω/km Overcurrent Phase IPh / IN 0.1 to 4 (in steps of 0.01)
(IDMT) Earth IEP / IN 0.1 to 4 (in steps of 0.01)
Parallel line compensation Can be set as an option
Time multiplier tp 0.05 to 32
Load current compensation Can be set as an option
Pickup threshold 1.1 x Ip
Measuring tolerances
Characteristic according to Normal inverse, very inverse,
to DIN VDE 0435, part 303 ≤ 2.5 % line length
IEC 60255-4, Section 3.5.2 extremely inverse
(for sinusoidal measured quantities) at 30 ° ≤ ϕsc ≤ 90 ° and Vsc / VN ≥ 0.1
or BS 142
Teleprotection for distance protection
Measuring tolerance according to
Modes DIN VDE 0435, part 303
Permissible underreach schemes PUTT transfer trip with fault detector
Pickup level DT ≤±5%
Zone acceleration with Z1B
IDMT Pickup at 1.05 <I/IP< 1.15
Permissible overreach methods POTT, directional comparison:
Unblocking with fault detection
Time delay DT 1 % of setting value or 10 ms
Unblocking with Z1B
≤ 5 % ± 15 ms for 2 ≤ I/IP ≤ 20 and
Blocking
IDMT 1 s ≤ tp ≤ 20 s
Overreach zone comparison –
via pilot wire Earth-fault protection for high-resistance earth faults in earthed networks
Reverse interlocking – Directional earth-fault definite-time protection with non-directional
backup protection
Power swing blocking/tripping (for impedance start Z<)
Pickup with earth current IE>/ IN 0.1 to 4 (in steps of 0.01)
Principle of power swing protection Measurement of the rate of change of
Displacement voltage 0.1 to 10 V (in steps of 1 V)
the impedance vector
VE > (= 3 x V0)
Modes Power swing blocking
Direction detection With IE and VE and IY
Power swing tripping
Teleprotection method Direction comparison
Difference power swing 0.1 to 50 Ω (in steps of 0.01 Ω)
Times
and fault detector polygon
Shortest command time Approx. 30 ms
Rate of change dR/dT 0 to 200 Ω/s (in steps of 1 Ω/s) Current reversal time Approx. 30 ms
Operating time 0.01 to 32 s or until (in steps of 0.01 Trip delay 0 to 32 s or deactivated
s) the end of power swing (in steps of 0.01 s)
Time tolerance ≤ 1 % of setting value or 10 ms
Weak-infeed protection with overreach and blocking schemes:
active during signal reception without fault detection Directional earth IDMTL protection
Characteristics according to Normal inverse, very inverse,
Mode Echo function and/or trip IEC 60255-4, Section 3.5.2 extremely inverse
or BS 142
Pickup value IE> / IN 0.1 to 4 (in steps of 0.01)
Time multiplier tIE> 0 to 32 s (in steps of 0.01)
Tolerances
Current pickup level Pickup at 1.05 < I/IEP < 1.15
Operating times ≤ 5 % for 2 ≤ (I/IE>) ≤ 20 and
1 s ≤ tIE ≤ 20 s

Siemens SIP · 2004 6/89


6 Distance Protection / 7SA513

Technical data

Auto-reclosure Breaker failure protection


Number of auto-reclosures Up to 10 Setting ranges
Program Only 1-pole Current start IBF/IN 0.1 to 4 (in steps of 0.01)
Only 3-pole Delay time 0.05 to 1 s (in steps of 0.01 s)
1 or 3-pole Shortest reset time Approx. 10 ms
Action times for RAR and DAR cycle 0.01 to 320 s (in steps of 0.01 s) Time tolerance ≤ 1 % of setting value or 10 ms
Dead times in the RAR cycle 0.01 to 320 s (in steps of 0.01 s) Measuring tolerance according to ±5%
Dead times in DAR cycles 0.01 to 1800 s (in steps of 0.01 s) DIN VDE 0435, part 303
(for sinusoidal measured quantities)
Reclaim times 0.5 to 320 s (in steps of 0.01 s)
Fault recording
CLOSE command duration 0.01 to 32 s (in steps of 0.01 s)
Measured quantities iph1, iph2, iph3, iE, Vph1, Vph2, Vph3, VE
Synchro-check
Start signal for fault recording Trip, start, binary input, operator
Modes for connection panel, PC
Line dead/busbar dead V1< / V2<
Line dead/busbar live V1< / V2> Memory management Dynamic ring buffer
Line live/busbar dead V1> / V2< Maximum number of recordings
Synchronism V1> / V2> available at one time 8
Permissible voltage 1 to 50 V (in steps of 1 V) Sampling interval 20 samples per network cycle
difference ∆V Maximum storage time
Permissible frequence 0.01 to 1 Hz (in steps of 0.01 Hz) (sum of all recordings)
6 difference ∆f At 50 Hz 10 s
Permissible angle difference ∆ϕ 1 to 60 ° (in steps of 1 °) At 60 Hz 8.3 s

Overvoltage protection Pre-trigger time 0.05 to 0.5 s (in steps of 0.01 s)

Function Post-fault time 0.05 to 0.5 s (in steps of 0.01 s)


Voltage measurement, local Maximum time for one recording 0.3 to 5 s (in steps of 0.01 s)
Voltage calculation, for the
opposite end (compounding)
Additional functions
Voltage selection 3 x phase-to-earth voltages or
3 x phase-to-phase voltages Operational measured values:
Currents Iph1, Iph2, Iph3
Pickup of the V>> level By ANDing the phase-selective start Voltages Vph1-ph2, Vph2-ph3, Vph3-ph1,
signals or by ORing the phase-selec- Vph1, Vph2, Vph3
tive start signals Power P/Q
Setting ranges Frequency f
Voltage threshold V>/ VN 1 to 1.9 (in steps of 0.01) Effective range 0 to 240 % x IN
Reset ratio Vres / V> 0.5 to 0.99 (in steps of 0.01) 0 to 120 % x VN
Voltage threshold V>>/VN 1 to 1.9 (in steps of 0.01) 0 to 120 % x PN
Reset ratio Vres / V>> 0.5 to 0.99 (in steps of 0.01) 96 to 104 % x fN
Times Tolerance ≤ 2 % of the rated value
tdelay> 0 to 32 s
tdelay>> with
circuit-breaker closed 0 to 32 s (in steps of 0.01 s) CE conformity
tdelay>> with The product meets the stipulations of the guideline of the Council of the
circuit-breaker open 0 to 32 s (in steps of 0.01 s) European Communities for harmonization of the legal requirements of
Command time Approx. 45 ms the member states on electromagnetic compatibility (EMC guide-line
Measuring tolerance according ±5% 89/336/EEC).
to DIN VDE 0435, part 303 The product conforms with the international standard of the IEC 60255
(for sinusoidal measured quantities) series and the German national standard DIN VDE 57 435, Part 303.
The unit has been developed and manufactured for use in industrial
areas in accordance with the EMC standard. The unit has not been
designed for use in living quarters as defined in standard EN 50081.
This conformity is the result of a test that was performed by Siemens AG
in accordance with article 10 of the guideline and the EN 50081-2 and EN
50082-2 basic specifications.

6/90 Siemens SIP · 2004


6 Distance Protection / 7SA513

Selection and ordering data Description Order No.


7SA513 distance protection relay, version V3 7SA513o-¨¨A2o- 0C¨¨
Rated current for 50/60 Hz AC
1A 1
5A 5

Rated auxiliary voltage


48 to 60 V DC 2
110 to 125 V DC 4
220 to 250 V DC 5

Unit design
For panel surface mounting B
For panel flush mounting or cubicle flush mounting C
For panel flush mounting or cubicle flush mounting without glass cover E

Input/output modules (EAH) 1)


2 EAH: 18 SR, 4 CR, 16 BI 0
3 EAH: 27 SR, 6 CR, 24 BI 1
2 EAH: 12 SR, 2 RR, 4 CR, 16 BI 2
3 EAH: 18 SR, 3 RR, 6 CR, 24 BI 3

Options A 6
Without auto-reclosure, without synchro-check E
With auto-reclosure 1/3-pole, without synchro-check G
With auto-reclosure 1/3-pole, with synchro-check H

Options B
Without earth-fault backup protection for earthed networks 0
With earth-fault backup protection for earthed networks 1

1) SR Signal/Alarm relay, switching power 20 W, 1 A


RR Reed relay, switching power 15 W, 0.3 A
CR Command relay, switching power 1000 W, 5 A
BI Binary input, voltage range 24 to 250 V DC settable.

Siemens SIP · 2004 6/91


6 Distance Protection / 7SA513

Accessories Description Order No.


DIGSI 4
Software for configuration and operation of Siemens protection units
running under MS Windows (version Windows 95 and higher)
device templates, Comtrade Viewer, electronic manual included
as well as “Getting started” manual on paper, connecting cables (copper)
Basis
Full version with license for 10 computers, on CD-ROM
(authorization by serial number) 7XS5400-0AA00
Demo
Demo version on CD-ROM 7XS5401-0AA00
Professional
Complete version:
DIGSI 4 Basis and additionally SIGRA (fault record analysis),
CFC Editor (logic editor), Display Editor (editor for default
and control displays) and DIGSI 4 Remote (remote operation) 7XS5402-0AA00

SIGRA
(generally contained in DIGSI Professional, but can be ordered additionally)
Software for graphic visualization, analysis and evaluation of fault records.
Can also be used for fault records of devices of other manufacturers
(Comtrade format). Running under MS Windows 95/98/ME/NT/2000/XP Professional.
6 Incl. templates, electronic manual with license for 10 PCs.
Authorization by serial number. On CD-ROM. 7XS5410-0AA00

Connecting cable
Cable between PC/notebook (9-pin connector) and protection unit (25-pin connector) 7XV5100-2
or
Cable between PC/notebook (9-pin connector) and protection unit (9-pin connector) 7XV5100-4
Adaptor 9-/25-pin for 7XV5100-4 cable for protec. unit w. 25-pin connector
(cable 7XV5100-4 and adaptor contained in DIGSI 4) 7XV5100-8H

Manual for 7SA513


English C53000-G1176-C103

6/92 Siemens SIP · 2004


6 Distance Protection / 7SA513

Connection diagram

Binary inputs, signal relays, command


relays and LEDs can be freely marshalled.
1) IEP – Earth current of the parallel line or
IY – Neutral point current.
2) For 7SA513*–**** . Not available
2
3
3) For 7SA513*–**** . Reed relay
2 Fig. 6/88 Connection diagram for the 7SA513 distance protection relay for transmission lines,
3 version DD, with 2 input/output modules (for 7SA513 with 3 input/output modules see Fig. 6/89)

Siemens SIP · 2004 6/93


6 Distance Protection / 7SA513

Connection diagram

Fig. 6/89 (To be read together with Fig. 6/88)


Input/output module EAH2 in the 7SA513 distance protection relay
for transmission lines with 3 input/output modules, version DD

Binary inputs, signal relays, command


relays and LEDs can be freely marshalled.
1) For 7SA513*–**** . Not available
2
3
2) For 7SA513*–**** . Reed relay
2
3

6/94 Siemens SIP · 2004


6 Distance Protection / 7SA513

Dimension drawings in mm / inch

Dimension drawings for SIPROTEC 3


1/1 x 19" housing

Front view Side view 6

Fig. 16/33
1/1 x 19" housing
for panel flush mounting/cubicle mounting

Fig. 16/34
1/1 x 19" housing for panel surface mounting

Siemens SIP · 2004 6/95