Professional Documents
Culture Documents
Electricity 101
SOUTHERN CALIFORNIA EDISON COMPANY
3
What is Electricity?
4
Movement of charges
Electron flow
Secondary energy source
Conversion from other sources of energy
Circuits
The Circuit
The path a current takes
Must be a complete loop
An incomplete circuit will not conduct electricity
5
Circuits cont.
6
Energy Units - Voltage
Note: The # of
electrons is the
same
7
Energy Units - Current
Lightning is current
flowing through air
8
Energy Units - Resistance
10
Ohm’s Law
Power = I x V = I² x R
11
Water System Analogy
Electrical Function
Water System System
The prime mover. Supplies energy to the system.
Pump Generator Converts motion to electrical energy
Restriction of the Resistance The characteristic that restricts water and current
flow.
water pipe
Amount of water This is the rate at which electrical energy is changed
Power into useful work. The quantity of water delivered.
delivered
12
(a) Series Circuits (b) Parallel Circuits
DIRECT CURRENT AND ALTERNATING CURRENT
Alternating Current
Direct Current
• Wire rotate past magnet causing a shift in direction
Electrons move in one direction • Happens many times each second
• Cycles per second = Hertz
16
AC/DC
(not the band)
Transforming ability
Phase of Electricity
Single phase AC circuit:
• Two wires connected to
electricity source
• Direction of current
changes many times per
second
3-phases of an electric system
(Wikipedia contributors, 2005)
Three phase systems:
• 3 lines with electricity from 3 circuits
• One neutral line
• 3 waveforms offset in time: 50-60 cycles/second
18
ELECRICAL CIRCUITS
12 volts
3 Ohms
4 Amps
ELECRICAL CIRCUITS
Short Circuit: In a short circuit current by-passes the load and finds
a low resistance path to ground.
In a shorted circuit
Point of resistance drops to below 0
Short
Amperage can increases to
dangerous levels.
ELECRICAL CIRCUITS
Point of open
In this circuit
current will by-pass
the switch
Point of ground
Electricity
Phase of Electricity
Star connection
Delta connection
23
© UNEP 2006
cycle time: The time it takes for the oscillation (Hz : 60 or 50 Hz)
rms = 0.707 peak value
Capacitor is like an open switch in a dc circuit once steady-state is reached
in ac circuits: The ability of the inductor to resist changes in current is measured in terms of its inductance L.
voltage and current oscillations out of phase: current to lead voltage
An electric current is not generated unless the magnetic field is moving relative to the copper wire, or the copper
wire is moving relative to the magnetic field.
So simple electric generators found in power plants contain, magnets
and copper wire that when put into motion relative to one another
create the electric current that is sent out to homes.
In this case, wind power applies a force to the blades that turns them.
The spinning blades, spin an armature that turns the copper wire
relative to the magnetic field. As long as the blades spin, electricity
will be generated!
At home, electric current
that was generated by
generators in the power
plant is used to power
electric appliances.
35
Electric Generation Basics
Generator in a Hydro
Plant
Electric Turbine
Generator
Generation - Fuel Types
Thermal Power
Coal
Nuclear
38
Generation - Renewable
Solar Geothermal
39
Energy Conversion Options for Electricity
Non-Thermal Paths
Energy Conversion Options for Electricity Thermal Paths
SCE Power Mix
42
Where do we get our Electricity?
6
TOE/person-year
a
A
a
o
ay
sh
a
.K
ic
di
i
in
ic
ad
pa
S
ss
de
w
U
fr
ex
U
In
h
an
Ja
u
or
a
R
gl
N
C
an
B
*TOE - Tons of Oil Equivalent (~40 Million Btus)
Peak Demand
Energy Cannot
be stored
Must be available
when needed
Programs to
reduce peak
demand
Peaker plants
built
46
- AC of 60 Hz produced by generator
- Resistance losses are smallest at high voltages and low currents
SCE’s Power Delivery System
Construct & Maintain Distribution
43,776 Switches
670,496 Transformers
1,448,794 Poles
94,854 Circuit Miles
317,820 Underground Structures
Plan Distribution Facilities 1,300,000 Trees
Reliability 11,873 Cap Banks
Load Growth 760,000 Street Lights
Automation
Transmission/Substation
Construct & Maintain
Operate 16,945 Circuit Breakers
904 Substations (16 manned)
4,459 Transformers
890 Transmission Circuits
13,585 Circuit Miles
4,166 Distribution Circuits
42,000 Relays
Plan Grid Facilities Protect & Test
15 UPS Sites
Reliability
Automate
4,000 Miles Communication
Load Growth Administrative Contracts
Interconnections
Circuits
Over 300 Grid Contracts
48
Transmission Substation
Transmission Power Reduced to 66 KV
Sub-Transmission
to
Distribution Station
Transformers reduce to 4, 12, or 16 kv
49
Transmission Lines
Distribution lines:
Transmission lines:
33 kV down
500 kv to 161 kV
Subtransmission lines:
55 kV to 138 kV
50
Transmission Lines
51
Distribution Devices
Distribution transformers
A device that is used to change one value of
voltage and current to another value of
voltage and current (33kV to 220 volts)
52
Environmental Protection
“The Company shall pursue the protection of endangered, threatened, and rare biological
species and their critical habitat and sensitive and unique ecosystems during all phases of
facility construction and operation and during management of Company-owned land.”
Biological Resources
Endangered Species
Approximately 275 endangered
species occur within SCE’s
service territory
Raptors
Wetlands
Cultural Resources
Culture
History & Pre-history
53
SCE’s Electric System Voltage Classifications
54
ELECTRICITY DISTRIBUTION
The power supply is provided basically from main substations of 400/132 kV
which in turn supply many substations of 132/33 kV (or 132/33/11 kV) distributed geographically
throughout the region .
These 132/33 kV substations in turn provide power supply to a very large number of 33/11 kV
substations as show.
Most of these 33/11 kV substations are equipped with two transformers of 31.5 MVA each (or
2x16 MVA) as shown in Fig.3. To the 11 kV bus bars of these substations (which is divided into
two sections) several 11 kV feeders are connected using underground cables and/or overhead line
systems.
Each circuit branch is served by a draw-out circuit breaker mostly by using one of these types :
SF6 Circuit Breaker
Vacuum Circuit breaker
Minimum-Oil Circuit Breaker
Each 11 or 33 kV feeder provides the supply to large number of 11/0.433 or 33/0.433 kV
distribution transformers installed using one of the following systems:
Each 11 or 33 kV feeder provides the supply to large number of 11/0.433 or 33/0.433 kV
distribution transformers installed using one of the following systems
Each 11 or 33 kV feeder provides the supply to large number of 11/0.433 or 33/0.433 kV
distribution transformers installed using one of the following systems:
i. Pole-mounted transformers supplied directly from 11 kV overhead
lines through manually operated fused switches.
The transformer size in this system is mostly 100 up to 250 kVA.
ii. Compact type unit substations installed usually at street
pavements, in industrial, residential, and commercial areas.
These substations are provided with three compartments:
High Voltage Compartment
It is placed at one side of the substation, and has an independent access through a double-sided
door with a specially designed lock. It has the capacity to hold up to three cubicles.
Transformer Compartment
This compartment occupies the middle of the substation and designed to accommodate standard
transformers of sizes 300 up to 1500 kVA (in some cases up to 2000 kVA). The cover of this
compartment is removable to enable transformer installation on site.
Low Voltage Compartments.
The low voltage compartment is placed at the other side of the substation and it is provided with
all required protective and control devices.
To the low voltage bus bars several outgoing 0.433 kV feeders are installed. Each low voltage
feeder provides the power supply to various numbers of consumers.
A single line diagram of a typical such substation is shown in Fig.6.
The compact type unit substations has the following advantages :
a) Reduction in civil engineering work (only a small excavation is required)
b) Can be easily transported by a truck due to its small size
c) Remarkable reduction in the installation cost (all internal connections are made at the factory)
d) Minimum space requirement
e) Adaptation to any application using different standard schemes.
f) Designed for operation outdoors ( weatherproof )
g) High operation safety for both the operator and the equipment
h) Reduction in the maintenance cost as compared with open installations
i) Special sandwich construction of walls prevent quick and direct heating of equipment caused
by direct sunshine conditions.
iii. Privately owned substations installed at consumer's premises in
building basements or in conventional brick-wall rooms. Transformer
sizes used in this case vary from 100 to 1000 kVA and in accordance
with load size.
Choice of power-supply sources
The importance of maintaining a continuous supply raises the question of the use of standby-power plant.
For the main source of supply the choice is generally between a connection to the MV or the LV network of the
power-supply utility.
In practice, connection to a MV source may be necessary where the load exceeds (or is planned eventually to
exceed) a certain level - generally of the order of 250 kVA, or if the quality of service required is greater than that
normally available from a LV network.
Supplies at MV can have certain advantages:
Is not disturbed by other consumers, which could be the case at LV
Is free to choose any type of LV earthing system
Has a wider choice of economic tariffs
Can accept very large increases in load
It should be noted, however, that:
The consumer is the owner of the MV/LV substation and, in some countries, he must build and equip it at his
own expense. The power utility can, in certain circumstances, participate in the investment, at the level of the
MV line for example
A part of the connection costs can, for instance, often be recovered if a second consumer is connected to the MV
line within a certain time following the original consumer’s own connection
The consumer has access only to the LV part of the installation, access to the MV part being reserved to the
utility personnel (meter reading, operations, etc.). However, in certain countries, the MV protective circuit-
breaker (or fused load-break switch) can be operated by the consumer
The type and location of the substation are agreed between the consumer and the utility
MV circuit configuration
The main possible connection configurations are as follows
single feeder, one or several transformers
open ring, one MV incomer
open ring, 2 MV incomers
The basic configuration is a radial single-feeder architecture, with one single transformer.
In the case of using several transformers, no ring is realised unless all of the transformers are located in a same
substation. Closed-ring configuration is not taken into account.
Number and distribution of
MV/LV transformation substations
Main characteristics to consider to
determine the transformation
substations:
Surface area of building or site
Power demand, (to be compared with
standardized transformer power),
Load distribution
The preferred basic configuration
comprises one single substation.
Distribution Transformers are used in order to reduce the voltage from that of the primary distribution systems
(usually 11 kv or 13.8 kv, nowadays 20 kv is also used) to the service voltage level of the secondary distribution
network.
Transformers are rated from 5KVA up to 1000KVA and there are ratings up to 2500KVA and more.
Construction Specifications:
Core:
Is formed of cold rolled silicon sheets or. Grain oriented steel.
windings:
High tension turns are built up of electrolytic copper wires of either Circular cross sections varnish isolated or
rectangular cross section isolated by high quality sililose paper.
Low tension turns are built up of either non insulated copper foils with insulating paper in between or of
rectangular wires insulated by cylindrical paper sheets.
Tank:
The transformer tank is made of corrugated steel. The corrugated tank Surface is itself the cooling surface,
sometimes the cooling surface is Provided by radiators welded to the tank sides.Transformers with nitrogen air
bag are equipped with tanks without.oil Conservators and with welded cover plate.
Terminals:
H.V. and L.V. terminals are brought out through porcelain bushes according to the rated voltage. The insulators
are fixed to the tank cover in such a way to ensure Replacement with dismantling the transformer cover.
Cables and boxes on either H.T. or L.T. side or both can be made.
0ff load tap-changing switch:
Tap change arc installed externally for allowing voltage regulation With ±5% of the rated value in 5 equal steps
of ±2.5% each.
The Tap changer is manually operated while the current is off.
T: Time of overloading
hours per day.
EXAMPLE:
Determine the ONAN Type Transformer Capacity for a building with loading of 450 KVA for 4 hours
And the normal loading is 250 KVA.
where:
S = Lower (air entry) ventilation opening area [m²] (grid surface deducted)
S’= Upper (air exit) ventilation opening area [m²] (grid surface deducted)
P = Total dissipated power [W]
P is the sum of the power dissipated by:
The transformer (dissipation at no load and due to load)
The LV switchgear
The MV switchgear
H = Height between ventilation opening mid-points [m]
Example:
Transformer dissipation = 7,970 W
LV switchgear dissipation = 750 W
MV switchgear dissipation = 300 W
The height between ventilation opening mid-points is 1.5 m.
Calculation:
Dissipated Power P = 7,970 + 750 + 300 = 9,020 W
LV distribution networks
Medium to large-sized towns and cities have underground cable distribution systems.
MV/LV distribution substations, mutually spaced at approximately 500-600 metres, are typically equipped
with:
I. A 3-or 4-way MV switchboard, often made up of incoming and outgoing loadbreak switches forming part of
a ring main, and one or two MV circuit-breakers or combined fuse/ load-break switches for the transformer
circuits
II. One or two 1,000 kVA MV/LV transformers
III. One or two (coupled) 6-or 8-way LV 3-phase 4-wire distribution fuse boards, or moulded-case circuit-
breaker boards, control and protect outgoing 4-core distribution cables, generally referred to as
“distributors”.
The output from a transformer is connected to the LV busbars via a load-break switch, or simply through
isolating links.
Configuration of LV circuits
LV & MV Equipments Selection Technological characteristics
The technological solutions considered concern the various types of MV and LV equipment, as well as Busbar
Trunking Systems .
The choice of technological solutions is made following the choice of single-line diagram and according to
characteristics given below.
Environment, atmosphere
A notion taking account of all of the environmental constraints (average ambient temperature, altitude,
humidity, corrosion, dust, impact, etc.) and bringing together protection indexes IP and IK.
Different categories:
Standard: no particular environmental constraints
Enhanced: severe environment, several environmental parameters generate important constraints for the
installed equipment
Specific: atypical environment, requiring special enhancements
Service Index
The service index (IS) is a value that allows us to characterize an LV switchboard according to user requirements
in terms of operation, maintenance, and scalability.
The different index values are indicated in the following table
There are a limited number of relevant service indices
The types of electrical connections of functional units can be denoted by a three letters code:
The first letter denotes the type of electrical connection of the main incoming circuit,
The second letter denotes the type of electrical connection of the main outgoing circuit,
The third letter denotes the type of electrical connection of the auxiliary circuits.
The following letters are used:
F for fixed connections,
D for disconnectable connections,
W for withdrawable connections.
SWITCHBOARDS AND SWITCHGEAR
A switchboard is a large, free-standing assembly of switches and fuses (and/or circuit breakers), which
normally provides switching and overcurrent protection to a number of circuits connected to a single electric
source. Metering and other instrumentation are also often included.
A switchboard may be represented in a single-line diagram, as shown in Fig. 26.23. This equipment serves to
distribute, with adequate protection, bulk power into smaller “packages.” Thus, in a hydraulic analogy, the
main buswork of the switchboard is equivalent to a main water supply header, the switches to on/off valves,
the fuses to flow-limiting devices, and the feeders to subpiping connected to the main header.
Modern switchboards (Figs. 26.24 to 26.27) are all deadfront; that is, they have all circuit breakers, switches,
fuses, and live parts completely enclosed in a metal structure. The operator controls all devices by means of
pushbuttons and insulated handles on the front panel.
Circuit breakers equipped with bayonet-type contacts, each mounted in a movable drawer (like the drawers of
a standard letter file) in a switchboard, are described as the drawout type. This drawout arrangement
facilitates emergency replacements, inspection, and repairs and is illustrated in Fig. 26.26.
No clear distinction is made between the terms switchboard and switchgear, although the terms suggest a
sense of scale. Generally, low voltage switchboards with large circuit breakers and all high-voltage equipment
(above 600 V) are referred to as switchgear.
When molded-case circuit breakers are utilized in a switchboard, it is often referred to as a building-type
switchboard.
Recommended minimum space requirements for various types of switchgear are shown in Fig. 26.28.
Working space around all types of electrical equipment must meet the requirements of NEC Article 110.
Main metal-clad switchgear for commercial, industrial, and public buildings is almost invariably located in a
basement and housed in a separate well-ventilated electrical switchgear room. Smaller subdistribution
switchboards require no special room.
A wire screen enclosure to prevent tampering or vandalism plus a large “DANGER— HIGH VOLTAGE” sign are
usually adequate. The architect must provide adequate exits, hallways, and/or hatches for the installation and
removal of all equipment. Specifications for switchgear should state the maximum overall dimensions of sections
that will be transported and installed in one piece.
When switchgear is to be installed outdoors, one of three methods is employed: build a small structure to enclose
normal indoor gear, utilize weatherproof outdoor gear, or utilize switchgear that is built into its own exterior
enclosing structure, as seen in Fig. 26.27. These housings are equipped with heating and lighting and often prove
to be the most economical choice.
UNIT SUBSTATIONS (TRANSFORMER LOAD CENTERS)
An assembly, comprising a primary voltage switch and- fuse or circuit breaker, a step-down transformer, meters,
controls, buswork, and secondary (low-voltage) switchgear, is known as a unit substation or a load-center
substation. Its function is to accept an incoming high-voltage power supply, transform the high voltage to a
voltage that can be utilized in the facility, and distribute the low-voltage power through associated low-voltage
(secondary) switchgear. A dimensional physical sketch of a typical unit substation, along with its electrical
singleline diagram, is shown in Fig. 26.29. Equipment is available for indoor or outdoor installation.
If installed indoors, the location of a unit substation is governed by the type of transformer utilized, as explained
in the discussion on indoor transformer installations. For this reason, almost all indoor unit substations utilize
dry-type (airfilled) transformers. A basement location is most often selected, with ventilation requirements as
detailed previously.
First SIEMENS Gas-Insulated
Medium-Voltage Switchgear (April 1982)
Kulmbach / Germany
8DA10
16 panels
24 kV / 16 kA (3s) / 1250 A
Switchgear Type 8DJ
Typical Application Examples
SafeLink CB
Compact Ring Main Unit for Secondary Distribution
© ABB Group
Safe-series product evolution
SafeLink CB
Well proven technology – years of experience – global references
36 kV
24 kV
12 kV
1985 2011
© ABB Group
Applicable IEC standards
SafeLink CB
© ABB Group
Unit Overall View/Picture
SafeLink CB
© ABB Group
General Information
SafeLink CB
© ABB Group
Configurations
SafeLink CB
Available in non-extensible
V
configurations of CVC and
extensible configurations of
+CVC+, +V+ and +C+ where
C- Cable/Ring switch module with test
point facility
(3 positions ON-OFF-EARTH)
C C
V-Vacuum circuit breaker module for
relay transformer protection
(with manually operated
disconnector)
© ABB Group
RMU in Network
SafeLink CB
© ABB Group
Technical Data
SafeLink CB C Module V Module
Switch Vacuum Circuit Earthing Switch
Disconnector Earthing Switch Breaker /Disconnector
Rated Voltage kV 12 12 12 12
Power frequency withstand voltage kV 38 38 38 38
- across disconnector kV 45 45 45 45
Lightning impulse withstand voltage kV 95 95 95 95
- across disconnector kV 110 110 110 110
Rated normal current1) A 630 630 630 630
Breaking capacities
- active load breaking current A 630 - - -
- closed loop breaking current A 630 - - -
- cable charging breaking current A 25 - 25 (Class C2) -
- line charging breaking current A 1 - 10 (Class C2) -
- earth fault breaking current A 75 - - -
- earth fault cable and line charging A 43.5 - - -
- short circuit breaking current kA - - 21 -
Making capacity kA 52.5 52.5 52.5 see2)
Short time current (3-sec) kA 21 21 21 21
Mechanical Operations nos M1 M0 M1+3000 M0
1)Suitablederating shall be applied for ambient temperatures greater than 40 deg
2)Disconnector is manually opearated, earthing operation is through VI. Hence no making capacity assigned
© ABB Group
Switchgear Dimensions1 ‘CVC’ (in mm)
SafeLink CB
1210
960
1540
1320
Bushing
C-C
100 mm
826
Side View Front View
Height: 1540 mm, Width: 960 mm, Depth 1210 mm
© ABB Group
Switchgear Dimensions2 ‘CVC’ (in mm)
SafeLink CB.
1830
Bushing
C-C
105 mm
2020
Front Door
Back View Open View
© ABB Group
Switchgear Dimensions ‘+CVC+’ (in mm)
SafeLink CB.
© ABB Group
Switchgear Dimensions ‘+V+’ (in mm)
SafeLink CB.
© ABB Group
Switchgear Dimensions ‘+C+’ (in mm)
SafeLink CB.
© ABB Group
Switchgear Dimensions in coupled condition (in mm)
SafeLink CB.
1995
Front View
© ABB Group
Switchgear Compartments
SafeLink CB
Breaker
Mechanisms
Switch
Pressure relief
Cable Connection
Cable Compartment
© ABB Group
Front Mimic
SafeLink CB
Logical user interface
Clear display of all functions with
appropriate usage of colours for ON-OFF-
EARTH functions and indication
Mimics – independent of language
Padlock for switch and disconnector
© ABB Group
Description of functions
SafeLink CB
1. Manometer
2. Relay
3. Fault Indicator 11
8 4. VPIS for Ring Switch RHS
1 5. Ring Switch RHS
10
6. Cable Box for Ring Switch RHS
7. Test Point Box for Ring Switch RHS
2 8. Operating Handle
9. T-Off Cable Box (For BKR)
3 4 10. Protection CT mounted on BKR Bushing
11. Lifting Hooks for Switch Gear
12. Tank Earthing
13. End Cover Box (Extensible bushing)
13
5 9
6
12
7
© ABB Group
Why SafeLink CB?
Cost efficiency
High standardized volumes
Space saving
Minimal maintenance
Easy installation
SYSTEM INSPECTION
Each electric wiring system is inspected at least twice by the local inspection authorities: once after raceways
(roughing) have been installed and before the wiring and closing-in of walls, and once after the entire job is
complete.
The purpose of these inspections is to determine whether the design, material, and installation techniques meet
the national and local code requirements. Quality of installation is the responsibility of the contractor.
The designer, however, must be familiar with installation work and the equipment’s physical characteristics in
order to properly design an electrical system that will not present the contractor with unwarranted difficulties.
The designer must understand and be aware of equipment substitutions by a contractor, who, having submitted
a bid on the basis of plans and specifications, should be required to supply the specified equipment.
Commissioning of electrical systems to the Owner’s Project Requirements is recommended.
Presence of L.V back-up generators
The electrical power supply supplied by a back-up generator is produced by an alternator, driven by a thermal
engine.
No power can be produced until the generator has reached its rated speed. This type of device is therefore not
suitable for an uninterrupted power supply.
According to the generator’s capacity to supply power to all or only part of the installation, there is either total or
partial redundancy.
A back-up generator functions generally disconnected from the network. A source switching system is therefore
necessary.
The generator can function permanently or intermittently. Its back-up time depends on the quantity of available
fuel.
The main characteristics to consider for implementing LV back-up generator:
1. Sensitivity of loads to power interruption,
2. Availability of the public distribution network,
3. Other constraints (e.g.: generators compulsory in hospitals or high-vise buildings)
The presence of generators can be decided to reduce the energy bill or due to the opportunity for co-generation.
The presence of a back-up generator is essential if the loads cannot be shed for an indefinite duration (long
interruption only acceptable) or if the utility network availability is low.
Determining the number of back-up generator units is in line with the same criteria as determining the number
of transformers, as well as taking account of economic and availability considerations (redundancy, start-up
reliability, maintenance facility).
Emergency Generators
Emergency generators are used to provide critical loads with power supply in the case of mains
failure (operating theaters & intensive care units in hospitals, computer buildings, etc…).
Emergency generators are usually driven by diesel engines, and connected to the load in the
following way :
a) When the generator is of the same size as the power supply transformer.
b) When the generator is of a smaller size as compared with the power supply transformer
Presence of an Uninterruptible Power Supply (UPS)
The electrical power from a UPS is supplied from a storage unit:
batteries or inertia wheel. This system allows us to avoid any power
failure. The back-up time of the system is limited: from several
minutes to several hours.
The simultaneous presence of a back-up generator and a UPS unit is
used for permanently supply loads for which no failure is acceptable.
The back-up
time of the battery or the inertia wheel must be compatible with the
maximum time for the generator to start up and be brought on-line.
A UPS unit is also used for supply power to loads that are sensitive to
disturbances (generating a “clean” voltage that is independent of the
network).
Main characteristics to be considered for implementing a UPS:
Sensitivity of loads to power interruptions,
Sensitivity of loads to disturbances.
The presence of a UPS unit is essential if and only if no failure is
acceptable.
Uninterruptible Power Supply ( UPS )
The basic version of the UPS consists of a rectifier, inverter, and batteries.
During normal operation, the inverter supplies the critical load and ensures that the amplitude
and frequency of the output voltage are stable and precisely controlled.
The inverter receives its power from mains via the rectifire which, at all times, float charges the
batteries.
In the event of an interruption in the power supply, the batteries takes over the task of supplying
power to the inverter.
When the mains power has been restored, the rectifier resumes input power to the inverter and
automatically recharges the battery
UNINTERRUPTIBLE POWER SUPPLY
As explained previously, power-conditioning equipment can supply clean utility power; it cannot, however,
supply any power during a utility outage.
That eventuality is addressed by providing an alternate supply of power. Facilities with desktop computers,
servers, and other data-processing equipment cannot tolerate power outages in excess of about 8 to 50
milliseconds (ms) without serious risk of data loss, and all the negative ramifications of such a loss.
An uninterruptible power supply (UPS) is an arrangement of normal and backup power supplies that transfer
a facility’s critical load from the normal to the backup supply in so short a time that no computer malfunction
results. This transfer time varies somewhat among different schemes and manufacturers but is always less
than 8.3 ms, which is the minimum period of power outage that computers must tolerate without disturbance
to meet the computer industry’s manufacturing guidelines. This time period is double the maximum transfer
time required by IEEE Standard 446, Recommended Practice for Emergency and Standby Power Systems for
Industrial and Commercial Applications, of ¼ cycle at 60 Hz, or 4.16 ms. Thus, all computer systems fed
from a UPS that meets this standard have a safety factor of at least 2 with respect to transfer time.
The period of time after transfer that the equipment will run on the standby source depends upon system
design. In most cases it is 5 to 10 minutes, which is usually enough time to permit an orderly manual or
automatic shutdown. Where shutdown is not a viable alternative, as with computer-controlled manufacturing
processes or critical server equipment, the standby power system can readily be designed to supply power
indefinitely.
The selection of a UPS system for a facility is a complex process beyond the scope of this book. The material
that follows is intended to provide sufficient familiarity with these systems to permit preliminary selection and
planning.
Schematic Diagram of a Typical UPS Installation
Case (1) : Mains Available ( Normal Operation )
Industry:
assembly lines
engine rooms on ships
critical auxiliaries in
thermal power stations…
Infrastructures:
port and railway installations
runway lighting systems
control systems on military sites…
REACTIVE POWER PRINCIBLES
All inductive (i.e. electromagnetic) machines and devices that operate on AC systems convert electrical energy
from the power system generators into mechanical work and heat. This energy is measured by kWh meters, and
is referred to as “active” or “wattful” energy. In order to perform this conversion, magnetic fields have to be
established in the machines, and these fields are associated with another form of energy to be supplied from the
power system, known as “reactive” or “wattless” energy.
The reason for this is that inductive circuit cyclically absorbs energy from the system (during the build-up of the
magnetic fields) and re-injects that energy into the system (during the collapse of the magnetic fields) twice in
every power-frequency cycle.
An exactly similar phenomenon occurs with shunt capacitive elements in a power system, such as cable
capacitance or banks of power capacitors, etc. In this case, energy is stored electrostatically. The cyclic charging
and discharging of capacitive circuit reacts on the generators of the system in the same manner as that described
above for inductive circuit, but the current flow to and from capacitive circuit in exact phase opposition to that of
the inductive circuit. This feature is the basis on which power factor correction schemes depend.
It should be noted that while this “wattless” current (more accurately, the “wattless” component of a load current)
does not draw power from the system, it does cause power losses in transmission and distribution systems by
heating the conductors. In practical power systems, “wattless” components of load currents are invariably
inductive, while the impedances of transmission and distribution systems are predominantly inductively reactive.
The combination of inductive current passing through an inductive reactance produces the worst possible
conditions of voltage drop (i.e. in direct phase opposition to the system voltage).
For these reasons (transmission power losses and voltage drop), the power-supply authorities reduce the amount
of “wattless” (inductive) current as much as possible.
“Wattless” (capacitive) currents have the reverse effect on voltage
levels and produce voltage-rises in power systems.
The power (kW) associated with “active” energy is usually
represented by the letter P.
The reactive power (kvar) is represented by Q. Inductively-reactive
power is conventionally positive (+ Q) while capacitively-reactive
power is shown as a negative quantity (- Q).
The apparent power S (kVA) is a combination of P and Q (see Fig.
L1). Sub-clause 1.3 shows the relationship between P, Q, and S.
The results of applying the above equations are given in a charts and tables and could be used to
determine the amount of kVAR that should be installed to improve the power factor to the
required value.
Table for Finding the K – factor K = ( tanØ1 - tanØ2 )
Although the use of this method improves distribution system performance, it does not provide an
optimum solution as it considers each group of loads independently of all other loads connected to the
same distribution feeder.
Advantages of Reactive Power Compensation:
There are many benefits to be gained from the application of shunt capacitors to distribution circuit,
some of these benefits are :-
1. Voltage Drop Reduction
2. Increasing the Apparent Power Capacity
3.Reduction in Line & Cable Losses
4. Reduction in Transformer Losses
Theoretical principles
An inductive load having a low power factor requires the generators and transmission/distribution systems to
pass reactive current (lagging the system voltage by 90 degrees) with associated power losses and exaggerated
voltage drops, as noted in sub-clause 1.1.
If a bank of shunt capacitors is added to the load, its (capacitive) reactive current will take the same path
through the power system as that of the load reactive current. Since, as pointed out in sub-clause 1.1, this
capacitive current Ic (which leads the system voltage by 90 degrees) is in direct phase opposition to the load
reactive current (IL), the two components flowing through the same path will cancel each other, such that if
the capacitor bank is sufficiently large and Ic = IL there will be no reactive current flow in the system upstream
of the capacitors.
This is indicated in Figure L8 (a) and (b) which show the flow of the reactive components of current
only. In this figure:
R represents the active-power elements of the load
L represents the (inductive) reactive-power elements of the load
C represents the (capacitive) reactive-power elements of the power-factor correction equipment (i.e.
capacitors).
It will be seen from diagram (b) of Figure L9, that the capacitor bank C appears
to be supplying all the reactive current of the load. For this reason, capacitors are sometimes referred to as
“generators of lagging vars”.
In diagram (c) of Figure L9, the active-power current component has been added,
and shows that the (fully-compensated) load appears to the power system as having a power factor of 1.
In general, it is not economical to fully compensate an installation.
Figure L9 uses the power diagram discussed in sub-clause 1.3 (see Fig. L3) to illustrate the principle of
compensation by reducing a large reactive power Q to a smaller value Q’ by means of a bank of capacitors having
a reactive power Qc. In doing so, the magnitude of the apparent power S is seen to reduce to S’.
Example:
A motor consumes 100 kW at a power factor of 0.75 (i.e. tan ϕ = 0.88). To improve the power factor to 0.93 (i.e.
tan ϕ = 0.4), the reactive power of the capacitor bank must be : Qc = 100 (0.88 - 0.4) = 48 kvar
The selected level of compensation and the calculation of rating for the capacitor bank depend on the particular
installation. The factors requiring attention are explained in a general way in clause 5, and in clauses 6 and 7 for
transformers and motors.
Note: Before starting a compensation project, a number of precautions should be observed. In
particular, oversizing of motors should be avoided, as well as the noloadnrunning of motors. In this latter
condition, the reactive energy consumed by a motor results in a very low power factor (≈ 0.17); this is because
the kW taken by the motor (when it is unloaded) are very small.
By using what equipment?
Compensation at LV
At low voltage, compensation is provided by:
b Fixed-value capacitor
b Equipment providing automatic regulation, or banks which allow continuous adjustment according to
requirements, as loading of the installation changes
Note: When the installed reactive power of compensation exceeds 800 kvar, and the
load is continuous and stable, it is often found to be economically advantageous to install capacitor banks at the
medium voltage level.
Control Methods
The amount of capacitors connected should be controlled in accordance with load variations as to
keep the power factor and voltage within the design limits.
To achieve this, capacitor banks are provided with manual or automatic switching facilities.
Time Switches
This method is the simplest and the cheapest and the best in the cases where the load kVAR cycle
can be predicted.
A timer is set to switch the capacitor bank at times dictated by the kVAR needs. It is normal to fit
a device to prevent switching in at weekends and during holidays.
Disadvantages :-
1. Problems arise if holiday periods are irregular.
2. The switches does not respond to unexpected load variations.
Time Switches with Voltage Over-ride
This method was developed to overcome the disadvantage of the simple time switch.
A voltage sensing relay ( energized by the timer ) is used to switch the bank only if the voltage
condition require it.
Voltage-Sensitive Control
In this method a voltage sensing relay is used to switch the capacitor bank in response to
system voltage changes. The disadvantage of this method is that the capacitor bank has other
important functions beside voltage control.
kVAR Sensitive Control
In this method a reactive power relay is used to perform switching of capacitors in accordance
with load kVAR variations.
This method is widely used but it is quite expensive.
Cos Ø Sensitive Control
This method is used in special cases where a well-defined power factor conditions occurs
regularly.
Fixed capacitors (see Fig. L10) Automatic capacitor banks (see Fig. L11)
This arrangement employs one or more capacitor(s) to This kind of equipment provides automatic control of
form a constant level of compensation, maintaining the
compensation. Control may be: power factor within close limits around a selected level.
b Manual: by circuit-breaker or load-break switch Such equipment is applied at
b Semi-automatic: by contactor points in an installation where the active-power and/or
b Direct connection to an appliance and switched with it reactive-power variations are
These capacitors are applied: relatively large, for example:
b At the terminals of inductive devices (motors and b At the busbars of a general power distribution board
transformers) b At the terminals of a heavily-loaded feeder cable
b At busbars supplying numerous small motors and
inductive appliance for which
individual compensation would be too costly
b In cases where the level of load is reasonably constant
Electricity
PF Correction:
Capacitors
• Act as reactive power
generators
• Reduce reactive power
• Reduce total power generated
by the utilities
244
© UNEP 2006
The principles of, and reasons, for using automatic compensation
A bank of capacitors is divided into a number of sections, each of which is controlled by a contactor. Closure of
a contactor switches its section into parallel operation with other sections already in service. The size of the
bank can therefore be increased or decreased in steps, by the closure and opening of the controlling contactors.
A control relay monitors the power factor of the controlled circuit(s) and is arranged to close and open
appropriate contactors to maintain a reasonably constant system power factor (within the tolerance imposed by
the size of each step of compensation). The current transformer for the monitoring relay must evidently be
placed on one phase of the incoming cable which supplies the circuit(s) being controlled, as shown in Figure
L12.
A Varset Fast capacitor bank is an automatic power factor correction equipment including static contactors
(thyristors) instead of usual contactors. Static correction is particularly suitable for a certain number of
installations using equipment with fast cycle and/or sensitive to transient surges.
The advantages of static contactors are :
o Immediate response to all power factor fluctuation (response time 2 s or 40 ms according to regulator option)
o Unlimited number of operations
o Elimination of transient phenomena on the network on capacitor switching
o Fully silent operation
By closely matching compensation to that required by the load, the possibility of producing overvoltages at
times of low load will be avoided, thereby preventing an overvoltage condition, and possible damage to
appliances and equipment.
Overvoltages due to excessive reactive compensation depend partly on the value of
source impedance.
In the case of certain (common) types of tariff, an
examination of several bills covering the most heavily-
loaded period of the year allows determination of the
kvar level of compensation required to avoid kvarh
(reactiveenergy) charges.
The pay-back period of a bank of power-factor-correction
capacitors and associated equipment is generally about
18 months
The choice between a fixed or automatically
regulated bank of capacitors
Commonly-applied rules