5 Overcurrent Protection / 7SJ62

SIPROTEC 4 7SJ62
Multifunction Protection Relay
Function overview

Protection functions
• Time-overcurrent protection
(definite-time/inverse-time/user-def.)
• Directional time-overcurrent protection
(definite-time/inverse-time/user-def.)
• Sensitive dir./non-dir. earth-fault
detection
• Displacement voltage
• Intermittent earth-fault protection
• High-impedance restricted earth fault
LSP2299-afpen.eps

• Inrush restraint
• Motor protection
– Undercurrent monitoring
– Starting time supervision
Fig. 5/76 – Restart inhibit 5
SIPROTEC 7SJ62 – Locked rotor
multifunction protection relay • Overload protection
• Temperature monitoring
• Under-/overvoltage protection
• Under-/overfrequency protection
• Breaker failure protection
Description
• Negative-sequence protection
The SIPROTEC 4 7SJ62 relays can be used • Phase-sequence monitoring
for line protection of high and medium • Auto-reclosure
voltage networks with earthed (grounded), • Fault locator
low-resistance earthed, isolated or com- • Lockout
pensated neutral point. With regard to Control functions/programmable logic
motor protection, the SIPROTEC 4 7SJ62
is suitable for asynchronous machines of • Commands f. ctrl of CB and of isolators
all sizes. The relay performs all functions of • Control via keyboard, binary inputs,
backup protection supplementary to trans- DIGSI 4 or SCADA system
former differential protection. • User-defined logic with CFC
The relay provides control of the circuit- (e.g. interlocking)
breaker, further switching devices and au- Monitoring functions
tomation functions. The integrated pro- • Operational measured values V, I, f
grammable logic (CFC) allows the user to • Energy metering values Wp, Wq
implement their own functions, e. g. for
• Circuit-breaker wear monitoring
the automation of switchgear (interlock-
ing). The user is also allowed to generate
• Slave pointer
user-defined messages. • Trip circuit supervision
• Fuse failure monitor
The flexible communication interfaces are • 8 oscillographic fault records
open for modern communication architec-
tures with control systems. Communication interfaces
• System interface
– IEC 60870-5-103/ IEC 61850
– PROFIBUS-FMS/-DP
– DNP 3.0/MODBUS RTU
• Service interface for DIGSI 4 (modem)
• Front interface for DIGSI 4
• Time synchronization via IRIG B/DCF77
Hardware
• 4 current transformers
• 3 voltage transformers
• 8/11 binary inputs
• 8/6 output relays

Siemens SIP · 2006 5/83


5 Overcurrent Protection / 7SJ62

Application

Fig. 5/77 Function diagram

The SIPROTEC 4 7SJ62 unit is a numerical Line protection Backup protection


protection relay that also performs control The 7SJ62 units can be used for line pro- The 7SJ62can be used universally for
and monitoring functions and therefore tection of high and medium-voltage net- backup protection.
supports the user in cost-effective power works with earthed (grounded), low-
system management, and ensures reliable resistance earthed, isolated or compensated Metering values
supply of electric power to the customers. neutral point.
Local operation has been designed accord- Extensive measured values, limit values
ing to ergonomic criteria. A large, easy-to- and metered values permit improved
Motor protection system management.
read display was a major design aim.
When protecting motors, the 7SJ62 relay is
Control suitable for asynchronous machines of all
sizes.
The integrated control function permits
control of disconnect devices, earthing Transformer protection
switches or circuit-breakers via the inte-
grated operator panel, binary inputs, The relay performs all functions of backup
DIGSI 4 or the control and protection sys- protection supplementary to transformer
tem (e.g. SICAM). A full range of com- differential protection. The inrush sup-
mand processing functions is provided. pression effectively prevents tripping by in-
rush currents.
Programmable logic The high-impedance restricted earth-fault
The integrated logic characteristics (CFC) protection detects short-circuits and insu-
allow the user to implement their own lation faults on the transformer.
functions for automation of switchgear
(interlocking) or a substation via a graphic
user interface. The user can also generate
user-defined messages.

5/84 Siemens SIP · 2006


5 Overcurrent Protection / 7SJ62

Application

ANSI No. IEC Protection functions

50, 50N I>, I>>, IE>, IE>> Definite time-overcurrent protection (phase/neutral)

51, 51N Ip, IEp Inverse time-overcurrent protection (phase/neutral)

67, 67N Idir>, Idir>>, Ip dir Directional time-overcurrent protection (definite/inverse, phase/neutral),
IEdir>, IEdir>>, IEp dir Directional comparison protection

67Ns/50Ns IEE>, IEE>>, IEEp Directional/non-directional sensitive earth-fault detection

– Cold load pick-up (dynamic setting change)

59N/64 VE, V0> Displacement voltage, zero-sequence voltage

– IIE> Intermittent earth fault

87N High-impedance restricted earth-fault protection

50BF Breaker failure protection 5


79 Auto-reclosure

46 I2> Phase-balance current protection (negative-sequence protection)

47 V2>, phase-sequence Unbalance-voltage protection and/or phase-sequence monitoring

49 ϑ> Thermal overload protection

48 Starting time supervision

14 Locked rotor protection

66/86 Restart inhibit

37 I< Undercurrent monitoring

38 Temperature monitoring via external device (RTD-box), e.g. bearing temperature monitoring

27, 59 V<, V> Undervoltage/overvoltage protection

81O/U f>, f< Overfrequency/underfrequency protection

21FL Fault locator

Construction

Connection techniques and


housing with many advantages
1/3-rack sizes is the available housing
width of the 7SJ62 relays, referred to a 19”
module frame system. This means that
previous models can always be replaced.
The height is a uniform 244 mm for flush-
mounting housings and 266 mm for sur-
face-mounting housing for all housing
LSP2099-afpen.eps

widths. All cables can be connected with or


without ring lugs.
In the case of surface mounting on a panel,
the connection terminals are located above
and below in the form of screw-type termi-
nals. The communication interfaces are
located in a sloped case at the top and bot-
tom of the housing. Fig. 5/78 Rear view with screw-type terminals

Siemens SIP · 2006 5/85


5 Overcurrent Protection / 7SJ62

Protection functions

Time-overcurrent protection
(ANSI 50, 50N, 51, 51N)
This function is based on the phase-selec-
tive measurement of the three phase cur-
rents and the earth current (four trans-
formers). Two definite-time overcurrent
protection elements (DMT) exist both for
the phases and for the earth. The current
threshold and the delay time can be set
within a wide range. In addition, inverse-
time overcurrent protection characteristics
(IDMTL) can be activated.

5 Fig. 5/79 Fig. 5/80


Definite-time overcurrent protection Inverse-time overcurrent protection

Available inverse-time characteristics


Characteristics acc. to ANSI/IEEE IEC 60255-3
Inverse • •
Short inverse •
Long inverse • •
Moderately inverse •
Very inverse • •
Extremely inverse • •

Reset characteristics Inrush restraint


For easier time coordination with The relay features second harmonic re-
electromechanical relays, reset characte- straint. If the second harmonic is detected
ristics according to ANSI C37.112 and during transformer energization, pickup of
IEC 60255-3 /BS 142 standards are applied. non-directional and directional normal el-
When using the reset characteristic (disk ements are blocked.
emulation), a reset process is initiated after
the fault current has disappeared. This Cold load pickup/dynamic setting change
reset process corresponds to the reverse For directional and non-directional time-
movement of the Ferraris disk of an elec- overcurrent protection functions the initi-
tromechanical relay (thus: disk emulation). ation thresholds and tripping times can be
switched via binary inputs or by time con-
User-definable characteristics trol.
Instead of the predefined time characteris-
tics according to ANSI, tripping character-
istics can be defined by the user for phase
and earth units separately. Up to 20 cur-
rent/time value pairs may be programmed.
They are set as pairs of numbers or graphi-
cally in DIGSI 4.

5/86 Siemens SIP · 2006


5 Overcurrent Protection / 7SJ62

Protection functions

Directional time-overcurrent protection


(ANSI 67, 67N)
Directional phase and earth protection are
separate functions. They operate in parallel
to the non-directional overcurrent elements.
Their pickup values and delay times can be
set separately. Definite-time and inverse-
time characteristics are offered. The tripping
characteristic can be rotated about ± 180 de-
grees.
Fig. 5/81
By means of voltage memory, Directional characteristic of
directionality can be determined reliably the directional
time-overcurrent
even for close-in (local) faults. If the protection
switching device closes onto a fault and the
voltage is too low to determine direction,
directionality (directional decision) is
made with voltage from the voltage mem- 5
ory. If no voltage exists in the memory,
tripping occurs according to the coordina-
tion schedule.
For earth protection, users can choose
whether the direction is to be determined
via zero-sequence system or negative-se-
quence system quantities (selectable).
Using negative-sequence variables can be
advantageous in cases where the zero volt-
age tends to be very low due to unfavorable
zero-sequence impedances.

Directional comparison protection


(cross-coupling)
It is used for selective protection of sec- Fig. 5/82
tions fed from two sources with instanta- Directional determination
neous tripping, i.e. without the using cosine measurements
disadvantage of time coordination. The di- for compensated networks
rectional comparison protection is suitable
if the distances between the protection sta-
tions are not significant and pilot wires are For networks with an isolated neutral, the • Each element can be set in forward,
available for signal transmission. In addi- reactive current component is evaluated; reverse, or non-directional.
tion to the directional comparison protec- for compensated networks, the active cur- • The function can also be operated in the
tion, the directional coordinated time- rent component or residual resistive cur- insensitive mode as an additional
overcurrent protection is used for rent is evaluated. For special network short-circuit protection.
complete selective backup protection. If conditions, e.g. high-resistance earthed
operated in a closed-circuit connection, an networks with ohmic-capacitive earth-fault (Sensitive) earth-fault detection
interruption of the transmission line is de- current or low-resistance earthed networks (ANSI 50Ns, 51Ns / 50N, 51N)
tected. with ohmic-inductive current, the tripping
characteristics can be rotated approxi- For high-resistance earthed networks, a
(Sensitive) directional earth-fault detection mately ± 45 degrees. sensitive input transformer is connected to
(ANSI 64, 67Ns, 67N) a phase-balance neutral current trans-
Two modes of earth-fault direction detec- former (also called core-balance CT).
For isolated-neutral and compensated net- tion can be implemented: tripping or
works, the direction of power flow in the “signalling only mode”. The function can also be operated in the
zero sequence is calculated from the zero- insensitive mode as an additional short-
sequen- ce current I0 and zero-sequence It has the following functions: circuit protection.
voltage V0. • TRIP via the displacement voltage VE.
• Two instantaneous elements or one
instantaneous plus one user-defined
characteristic.

Siemens SIP · 2006 5/87


5 Overcurrent Protection / 7SJ62

Protection functions When the high-impedance measurement


principle is applied, all current transform-
Intermittent earth-fault protection ers in the protected area are connected in
parallel and operated on one common re-
Intermittent (re-striking) faults occur due sistor of relatively high R whose voltage is
to insulation weaknesses in cables or as a measured (see Fig. 5/83). In the case of
result of water penetrating cable joints. 7SJ6 units, the voltage is measured by de-
Such faults either simply cease at some tecting the current through the (external)
stage or develop into lasting short-circuits. resistor R at the sensitive current measure-
During intermittent activity, however, ment input IEE. The varistor V serves to
star-point resistors in networks that are limit the voltage in the event of an internal
impedance-earthed may undergo thermal fault. It cuts off the high momentary volt-
overloading. The normal earth-fault pro- age spikes occurring at transformer satura-
tection cannot reliably detect and interrupt tion. At the same time, this results in
the current pulses, some of which can be smoothing of the voltage without any
very brief. noteworthy reduction of the average value.
The selectivity required with intermittent If no faults have occurred and in the event
earth faults is achieved by summating the of external faults, the system is at equilib-
duration of the individual pulses and by rium, and the voltage through the resistor Fig. 5/83 High-impedance restricted earth-
5 triggering when a (settable) summed time is approximately zero. In the event of in- fault protection
is reached. The response threshold IIE> ternal faults, an imbalance occurs which
evaluates the r.m.s. value, referred to one leads to a voltage and a current flow
systems period. Thermal overload protection (ANSI 49)
through the resistor R.
For protecting cables and transformers,
Phase-balance current protection (ANSI 46) The current transformers must be of the an overload protection with an integrated
(Negative-sequence protection) same type and must at least offer a separate pre-warning element for temperature and
core for the high-impedance restricted current can be applied. The temperature is
In line protection, the two-element phase- earth-fault protection. They must in par-
balance current/negative-sequence protec- calculated using a thermal homogeneous-
ticular have the same transformation ratio body model (according to IEC 60255-8),
tion permits detection on the high side of and an approximately identical knee-point
high-resistance phase-to-phase faults and which takes account both of the energy en-
voltage. They should also demonstrate only tering the equipment and the energy losses.
phase-to-earth faults that are on the low minimal measuring errors.
side of a transformer (e.g. with the switch The calculated temperature is constantly ad-
group Dy 5). This provides backup protec- justed accordingly. Thus, account is taken of
Auto-reclosure (ANSI 79) the previous load and the load fluctuations.
tion for high-resistance faults beyond the
transformer. Multiple reclosures can be defined by the
For thermal protection of motors (especially
user and lockout will occur if a fault is
the stator) a further time constant can be set
Breaker failure protection (ANSI 50BF) present after the last reclosure. The follow-
so that the thermal ratios can be detected
ing functions are possible:
If a faulted portion of the electrical circuit correctly while the motor is rotating and
is not disconnected upon issuance of a trip • 3-pole ARC for all types of faults when it is stopped. The ambient tempera-
command, another command can be initi- • Separate settings for phase and earth faults ture or the temperature of the coolant can
ated using the breaker failure protection be detected serially via an external tempera-
which operates the circuit-breaker, e.g. of • Multiple ARC, one rapid auto-reclosure ture monitoring box (resistance-tempera-
an upstream (higher-level) protection re- (RAR) and up to nine delayed ture detector box, also called RTD- box).
lay. Breaker failure is detected if, after a auto-reclosures (DAR) The thermal replica of the overload function
trip command, current is still flowing in • Starting of the ARC depends on the trip is automatically adapted to the ambient
the faulted circuit. As an option, it is possi- command selection (e.g. 46, 50, 51, 67) conditions. If there is no RTD-box it is as-
ble to make use of the circuit-breaker posi- sumed that the ambient temperatures are
• Blocking option of the ARC via binary constant.
tion indication.
inputs
High-impedance restricted earth-fault pro- • ARC can be initiated externally or via CFC Settable dropout delay times
tection (ANSI 87N) • The directional and non-directional ele- If the devices are used in parallel with elec-
The high-impedance measurement princi- ments can either be blocked or operated tromechanical relays in networks with inter-
ple is an uncomplicated and sensitive non-delayed depending on the auto- mittent faults, the long dropout times of the
method for detecting earth faults, espe- reclosure cycle electromechanical devices (several hundred
cially on transformers. It can also be ap- milliseconds) can lead to problems in terms
• Dynamic setting change of the directional of time grading. Clean time grading is only
plied to motors, generators and reactors
and non-directional elements can be acti- possible if the dropout time is approxi-
when these are operated on an earthed net-
vated depending on the ready AR mately the same. This is why the parameter
work.
of dropout times can be defined for certain
functions such as time-overcurrent protec-
tion, earth short-circuit and phase-balance
current protection.

5/88 Siemens SIP · 2006


5 Overcurrent Protection / 7SJ62

Protection functions

n Motor protection
Restart inhibit (ANSI 66/86)
If a motor is started up too many times in
succession, the rotor can be subject to ther-
mal overload, especially the upper edges of
the bars. The rotor temperature is calcu-
lated from the stator current. The reclosing
lockout only permits start-up of the motor
if the rotor has sufficient thermal reserves
for a complete start-up (see Fig. 5/84).

Emergency start-up
This function disables the reclosing lock-
out via a binary input by storing the state
of the thermal replica as long as the binary
input is active. It is also possible to reset 5
the thermal replica to zero.
Fig. 5/84
Temperature monitoring (ANSI 38)
Up to two temperature monitoring boxes If the trip time is rated according to the Undervoltage protection (ANSI 27)
with a total of 12 measuring sensors can be above formula, even a prolonged start-up
used for temperature monitoring and de- The two-element undervoltage protection
and reduced voltage (and reduced start-up provides protection against dangerous
tection by the protection relay. The ther- current) will be evaluated correctly. The
mal status of motors, generators and voltage drops (especially for electric ma-
tripping time is inverse (current depend- chines). Applications include the isolation
transformers can be monitored with this ent).
device. Additionally, the temperature of of generators or motors from the network
the bearings of rotating machines are mon- A binary signal is set by a speed sensor to to avoid undesired operating states and a
itored for limit value violation. The tem- detect a blocked rotor. An instantaneous possible loss of stability. Proper operating
peratures are being measured with the help tripping is effected. conditions of electrical machines are best
of temperature detectors at various loca- evaluated with the positive-sequence quan-
tions of the device to be protected. This Phase-balance current protection (ANSI 46) tities. The protection function is active
data is transmitted to the protection relay (Negative-sequence protection) over a wide frequency range (45 to 55, 55
via one or two temperature monitoring to 65 Hz)1). Even when falling below this
The negative-sequence / phase-balance
boxes (see “Accessories”, page 5/113). frequency range the function continues to
current protection detects a phase failure
work, however, with a greater tolerance
or load unbalance due to network asym-
Starting time supervision (ANSI 48/14) band.
metry and protects the rotor from imper-
Starting time supervision protects the mo- missible temperature rise. The function can operate either with the
tor against long unwanted start-ups that positive phase-sequence system voltage
might occur in the event of excessive load Undercurrent monitoring (ANSI 37) (default) or with the phase-to-phase volt-
torque or excessive voltage drops within With this function, a sudden drop in cur- ages, and can be monitored with a current
the motor, or if the rotor is locked. Rotor rent, which can occur due to a reduced criterion. Three-phase and single-phase
temperature is calculated from measured motor load, is detected. This may be due to connections are possible.
stator current. The tripping time is calcu- shaft breakage, no-load operation of
lated according to the following equation: pumps or fan failure. Frequency protection (ANSI 81O/U)
Frequency protection can be used for over-
for I > IMOTOR START
2
n Voltage protection frequency and underfrequency protection.
t =  A  ⋅ TA
I Electric machines and parts of the system
Overvoltage protection (ANSI 59)
 I  are protected from unwanted speed devia-
I = Actual current flowing
The two-element overvoltage protection tions. Unwanted frequency changes in the
detects unwanted network and machine network can be detected and the load can
IMOTOR START = Pickup current to detect a motor
start overvoltage conditions. The function can be removed at a specified frequency set-
t = Tripping time
operate either with phase-to-phase voltage ting.
(default) or with the negative phase-se-
IA = Rated motor starting current
quence system voltage. Three-phase and
TA = Tripping time at rated motor
single-phase connections are possible.
starting current

1) The 45 to 55, 55 to 65 Hz range is available


for fN = 50/60 Hz.

Siemens SIP · 2006 5/89


5 Overcurrent Protection / 7SJ62

Customized functions (ANSI 32, 51V, 55, etc.)


Protection functions/Functions
Additional functions, which are not time
Frequency protection can be used over a critical, can be implemented via the CFC
wide frequency range (45 to 55, 55 to using measured values. Typical functions
65 Hz)1). There are four elements include reverse power, voltage controlled
(selectable as overfrequency or overcurrent, phase angle detection, and
underfrequency) and each element can be zero-sequence voltage detection.
delayed separately. Blocking of the fre-
quency protection can be performed if us- Commissioning
ing a binary input or by using an Commissioning could hardly be easier and
undervoltage element. is fully supported by DIGSI 4. The status of
the binary inputs can be read individually
Fault locator (ANSI 21FL) and the state of the binary outputs can be
The fault locator specifies the distance to a set individually. The operation of switch-
fault location in kilometers or miles or the ing elements (circuit-breakers, disconnect
reactance of a second fault operation. devices) can be checked using the switch-
ing functions of the bay controller. The an-
Circuit-breaker wear monitoring alog measured values are represented as
5 Methods for determining circuit-breaker wide-ranging operational measured values.
contact wear or the remaining service life To prevent transmission of information to
of a circuit-breaker (CB) allow CB mainte- the control center during maintenance, the Fig. 5/85 CB switching cycle diagram
nance intervals to be aligned to their actual bay controller communications can be dis-
degree of wear. The benefit lies in reduced abled to prevent unnecessary data from be-
ing transmitted. During commissioning, all Automation / user-defined logic
maintenance costs.
indications with test marking for test pur- With integrated logic, the user can set, via a
There is no mathematically exact method poses can be connected to a control and graphic interface (CFC), specific functions
of calculating the wear or the remaining protection system. for the automation of switchgear or substa-
service life of circuit-breakers that takes tion. Functions are activated via function
into account the arc-chamber's physical Test operation keys, binary input or via communication
conditions when the CB opens. This is why interface.
During commissioning, all indications can
various methods of determining CB wear
be passed to an automatic control system
have evolved which reflect the different op- Switching authority
for test purposes.
erator philosophies. To do justice to these,
Switching authority is determined accord-
the devices offer several methods:
n Control and automatic functions ing to parameters, communication or by
• I key-operated switch (when available).
Control
• Σ I x, with x = 1... 3 If a source is set to “LOCAL”, only local
In addition to the protection functions, the switching operations are possible. The fol-
The devices additionally offer a new SIPROTEC 4 units also support all control lowing sequence of switching authority is
method for determining the remaining ser- and monitoring functions that are required laid down: “LOCAL”; DIGSI PC program,
vice life: for operating medium-voltage or high- “REMOTE”.
• Two-point method voltage substations.
The CB manufacturers double-logarithmic The main application is reliable control of Command processing
switching cycle diagram (see Fig. 5/85) and switching and other processes. All the functionality of command process-
the breaking current at the time of contact ing is offered. This includes the processing
opening serve as the basis for this method. The status of primary equipment or auxil-
iary devices can be obtained from auxiliary of single and double commands with or
After CB opening, the two-point method without feedback, sophisticated monitor-
calculates the number of still possible contacts and communicated to the 7SJ62
via binary inputs. Therefore it is possible to ing of the control hardware and software,
switching cycles. To this end, the two checking of the external process, control
points P1 and P2 only have to be set on the detect and indicate both the OPEN and
CLOSED position or a fault or intermedi- actions using functions such as runtime
device. These are specified in the CB's tech- monitoring and automatic command ter-
nical data. ate circuit-breaker or auxiliary contact po-
sition. mination after output. Here are some typi-
All of these methods are phase-selective cal applications:
and a limit value can be set in order to ob- The switchgear or circuit-breaker can be
controlled via: • Single and double commands using 1,
tain an alarm if the actual value falls below 1 plus 1 common or 2 trip contacts
or exceeds the limit value during determi- – integrated operator panel
nation of the remaining service life. – binary inputs • User-definable bay interlocks
– substation control and protection system
• Operating sequences combining several
– DIGSI 4
switching operations such as control of
circuit-breakers, disconnectors and
earthing switches
1) The 45 to 55, 55 to 65 Hz range is
available for fN= 50/60 Hz

5/90 Siemens SIP · 2006


5 Overcurrent Protection / 7SJ62

Functions Measured values


The r.m.s. values are calculated from the
• Triggering of switching operations, indi- acquired current and voltage along with
cations or alarm by combination with the power factor, frequency, active and
existing information reactive power. The following functions
are available for measured value process-
Assignment of feedback to command ing:
The positions of the circuit-breaker or • Currents IL1, IL2, IL3, IE, IEE (67Ns)
switching devices and transformer taps are
• Voltages VL1, VL2, VL3, VL1L2, VL2L3, VL3L1
acquired by feedback. These indication in-
puts are logically assigned to the corre- • Symmetrical components
sponding command outputs. The unit can I1, I2, 3I0; V1, V2, V0
therefore distinguish whether the indica- • Power Watts, Vars, VA/P, Q, S
tion change is a consequence of switching (P, Q: total and phase selective)
operation or whether it is a spontaneous
change of state. • Power factor (cos ϕ),
(total and phase selective)
Chatter disable • Frequency
• Energy ± kWh, ± kVarh, forward and 5

LSP2077f.eps
Chatter disable feature evaluates whether,
in a configured period of time, the number reverse power flow
of status changes of indication input ex-
• Mean as well as minimum and maximum
ceeds a specified figure. If exceeded, the in-
current and voltage values
dication input is blocked for a certain
period, so that the event list will not record • Operating hours counter
excessive operations. • Mean operating temperature of overload
function
Indication filtering and delay
• Limit value monitoring
Binary indications can be filtered or de- Limit values are monitored using pro-
layed. grammable logic in the CFC. Commands Fig. 5/86
Filtering serves to suppress brief changes in can be derived from this limit value indi- NXAIR panel (air-insulated)
potential at the indication input. The indi- cation.
cation is passed on only if the indication • Zero suppression
voltage is still present after a set period of In a certain range of very low measured
time. In the event of indication delay, there values, the value is set to zero to suppress
is a wait for a preset time. The information interference.
is passed on only if the indication voltage is
still present after this time. Metered values

Indication derivation For internal metering, the unit can calcu-


late an energy metered value from the
A further indication (or a command) can measured current and voltage values. If an
be derived from an existing indication. external meter with a metering pulse out-
Group indications can also be formed. The put is available, the SIPROTEC 4 unit can
volume of information to the system inter- obtain and process metering pulses via an
face can thus be reduced and restricted to indication input.
the most important signals.
The metered values can be displayed and
Switchgear cubicles for passed on to a control center as an accu-
high/medium voltage mulation with reset. A distinction is made
between forward, reverse, active and reac-
All units are designed specifically to meet
tive energy.
the requirements of high/medium-voltage
applications.
In general, no separate measuring instru-
ments (e.g., for current, voltage, frequency,
…) or additional control components are
necessary.

Siemens SIP · 2006 5/91


5 Overcurrent Protection / 7SJ62

System interface protocols (retrofittable)


Communication
IEC 61850 protocol
In terms of communication, the units offer As of mid-2004, the Ethernet-based
substantial flexibility in the context of con- IEC 61850 protocol is the worldwide stan-
nection to industrial and power automa- dard for protection and control systems
tion standards. Communication can be used by power supply corporations.
extended or added on thanks to modules Siemens is the first manufacturer to sup-
for retrofitting on which the common pro- port this standard. By means of this proto-
tocols run. Therefore, also in the future it col, information can also be exchanged
will be possible to optimally integrate units directly between bay units so as to set up
into the changing communication infra- simple masterless systems for bay and sys-
structure, for example in Ethernet net- tem interlocking. Access to the units via
works (which will also be used increasingly the Ethernet bus will also be possible with
in the power supply sector in the years to DIGSI.
come).
IEC 60870-5-103 protocol
Serial front interface Fig. 5/87
The IEC 60870-5-103 protocol is an inter- IEC 60870-5-103: Radial fiber-optic connection
There is a serial RS232 interface on the national standard for the transmission of
5 front of all the units. All of the unit’s func- protective data and fault recordings. All
tions can be set on a PC by means of the messages from the unit and also control
DIGSI 4 protection operation program. commands can be transferred by means of
Commissioning tools and fault analysis are published, Siemens-specific extensions to
also built into the program and are avail- the protocol.
able through this interface.
PROFIBUS-FMS
Rear-mounted interfaces1)
PROFIBUS-FMS is an internationally stan-
A number of communication modules dardized communication system
suitable for various applications can be fit- (EN 50170) for efficient performance of
ted in the rear of the flush-mounting hous- communication tasks in the bay area.
ing. In the flush-mounting housing, the SIPROTEC 4 units use a profile specially
modules can be easily replaced by the user. optimized for protection and control re-
The interface modules support the follow- quirements. DIGSI can also work on the
ing applications: basis of PROFIBUS-FMS. The units are
• Time synchronization interface linked to a SICAM automation system.
All units feature a permanently integrated
electrical time synchronization interface. PROFIBUS-DP protocol
It can be used to feed timing telegrams in PROFIBUS-DP is the most widespread
IRIG-B or DCF77 format into the units protocol in industrial automation. Via
via time synchronization receivers. Fig. 5/88
PROFIBUS-DP, SIPROTEC units make
PROFIBUS: Fiber-optic double ring circuit
• System interface their information available to a SIMATIC
Communication with a central control controller or, in the control direction, re-
system takes place through this interface. ceive commands from a central SIMATIC.
Radial or ring type station bus topologies Measured values can also be transferred.
can be configured depending on the cho-
sen interface. Furthermore, the units can MODBUS RTU protocol
exchange data through this interface via This uncomplicated, serial protocol is
Ethernet and IEC 61850 protocol and can mainly used in industry and by power sup-
also be operated by DIGSI. ply corporations, and is supported by a
• Service interface number of unit manufacturers. SIPROTEC
The service interface was conceived for re- units function as MODBUS slaves, making
mote access to a number of protection their information available to a master or
units via DIGSI. On all units, it can be an receiving information from it. A time-
electrical RS232/RS485 or an optical inter- stamped event list is available.
face. For special applications, a maximum
of two temperature monitoring boxes
(RTD-box) can be connected to this inter-
face as an alternative.

Fig. 5/89
Bus structure for station bus with Ethernet and
1) For units in panel surface-mounting housings IEC 61850, fiber-optic ring
please refer to note on page 5/112.

5/92 Siemens SIP · 2006


5 Overcurrent Protection / 7SJ62

Communication

DNP 3.0 protocol


Power supply corporations use the serial
DNP 3.0 (Distributed Network Protocol)
for the station and network control levels.
SIPROTEC units function as DNP slaves,
supplying their information to a master
system or receiving information from it.

System solutions for protection and station


control
Together with the SICAM power automa-
tion system, SIPROTEC 4 can be used with
PROFIBUS-FMS. Over the low-cost elec-
trical RS485 bus, or interference-free via
the optical double ring, the units exchange
information with the control system.
5
Units featuring IEC 60870-5-103 interfaces
can be connected to SICAM in parallel via
the RS485 bus or radially by fiber-optic
link. Through this interface, the system is
open for the connection of units of other
manufacturers (see Fig. 5/87).
Fig. 5/90
Because of the standardized interfaces, System solution/communication
SIPROTEC units can also be integrated
into systems of other manufacturers or in
SIMATIC. Electrical RS485 or optical in-
terfaces are available. The optimum physi-
cal data transfer medium can be chosen
thanks to opto-electrical converters. Thus,
the RS485 bus allows low-cost wiring in
the cubicles and an interference-free opti-
cal connection to the master can be estab-
lished.
LSP2810.tif

For IEC 61850, an interoperable system so-


lution is offered with SICAM PAS. Via the
100 Mbits/s Ethernet bus, the units are Fig. 5/91
linked with PAS electrically or optically to Optical Ethernet communication module
the station PC. The interface is standard- for IEC 61850 with integrated Ethernet-switch
ized, thus also enabling direct connection
of units of other manufacturers to the
Ethernet bus. With IEC 61850, however,
the units can also be used in other manu-
facturers’ systems (see Fig. 5/89).

Siemens SIP · 2006 5/93


5 Overcurrent Protection / 7SJ62

Typical connections

n Connection of current
and voltage transformers
Standard connection
For earthed networks, the earth current is
obtained from the phase currents by the
residual current circuit.

Fig. 5/92
Residual current
circuit without direc-
tional element
5

Fig. 5/93
Sensitive earth-
current detection
without directional
element

Fig. 5/94
Residual current
circuit with direc-
tional element

5/94 Siemens SIP · 2006


5 Overcurrent Protection / 7SJ62

Typical connections

Connection for compensated networks


The figure shows the connection of two
phase-to-earth voltages and the VE voltage
of the open delta winding and a phase-
balance neutral current transformer for the
earth current. This connection maintains
maximum precision for directional earth-
fault detection and must be used in com-
pensated networks.
Fig. 5/95 shows sensitive directional
earth-fault detection.

Fig. 5/95
Sensitive directional
earth-fault detection
with directional
element for phases
5

Fig. 5/96
Sensitive directional
earth-fault detection

Connection for isolated-neutral


or compensated networks only
If directional earth-fault protection is not
used, the connection can be made with
only two phase current transformers. Di-
rectional phase short-circuit protection
can be achieved by using only two primary
transformers.

Fig. 5/97
Isolated-neutral or
compensated
networks

Siemens SIP · 2006 5/95


5 Overcurrent Protection / 7SJ62

Typical applications

Overview of connection types


Type of network Function Current connection Voltage connection
(Low-resistance) earthed network Time-overcurrent protection Residual circuit, with 3 phase-current -
phase/earth non-directional transformers required, phase-balance
neutral current transformer possible
(Low-resistance) earthed networks Sensitive earth-fault protection Phase-balance neutral current -
transformers required
Isolated or compensated networks Time-overcurrent protection Residual circuit, with 3 or 2 phase -
phases non-directional current transformers possible
(Low-resistance) earthed networks Time-overcurrent protection Residual circuit, with 3 phase-current Phase-to-earth connection or
phases directional transformers possible phase-to-phase connection
Isolated or compensated networks Time-overcurrent protection Residual circuit, with 3 or 2 phase- Phase-to-earth connection or
phases directional current transformers possible phase-to-phase connection
(Low-resistance) earthed networks Time-overcurrent protection Residual circuit, with 3 phase-current Phase-to-earth connection required
earth directional transformers required, phase-balance
5 neutral current transformers possible
Isolated networks Sensitive earth-fault Residual circuit, if earth current 3 times phase-to-earth connection or
protection > 0.05 IN on secondary side, other- phase-to-earth connection with open
wise phase-balance neutral current delta winding
transformers required
Compensated networks Sensitive earth-fault protection Phase-balance neutral current Phase-to-earth connection with open
cos ϕ measurement transformers required delta winding required

n Connection of circuit-breaker
Undervoltage releases
Undervoltage releases are used for auto-
matic tripping of high-voltage motors.
Example:
DC supply voltage of control system fails
and manual electric tripping is no longer
possible.
Automatic tripping takes place when volt-
age across the coil drops below the trip
limit. In Fig. 5/98, tripping occurs due to
failure of DC supply voltage, by automatic
opening of the live status contact upon
failure of the protection unit or by
short-circuiting the trip coil in event of
network fault.
Fig. 5/98 Undervoltage release with make contact (50, 51)

5/96 Siemens SIP · 2006


5 Overcurrent Protection / 7SJ62

Typical applications

In Fig. 5/99 tripping is by failure of auxil-


iary voltage and by interruption of tripping
circuit in the event of network failure.
Upon failure of the protection unit, the
tripping circuit is also interrupted, since
contact held by internal logic drops back
into open position.

Trip circuit supervision (ANSI 74TC)


One or two binary inputs can be used for
monitoring the circuit-breaker trip coil in-
cluding its incoming cables. An alarm sig-
nal occurs whenever the circuit is
interrupted.

Lockout (ANSI 86)


All binary outputs can be stored like LEDs Fig. 5/99 Undervoltage trip with locking contact (trip signal 50 is inverted)
5
and reset using the LED reset key. The
lockout state is also stored in the event of
supply voltage failure. Reclosure can only
occur after the lockout state is reset.

Fig. 5/100 Trip circuit supervision with 2 binary inputs

Fig. 5/101 Trip circuit supervision with 1 binary input

Siemens SIP · 2006 5/97


5 Overcurrent Protection / 7SJ62

Technical data

General unit data Binary outputs/command outputs


Measuring circuits Type 7SJ621 7SJ622
System frequency 50 / 60 Hz (settable) Command/indication relay 8 6
Current transformer Contacts per command/ 1 NO / form A
Rated current Inom 1 or 5 A (settable) indication relay (Two contacts changeable to NC/form
B, via jumpers)
Option: sensitive earth-fault CT IEE < 1.6 A
Live status contact 1 NO / NC (jumper) / form A/B
Power consumption
at Inom = 1 A Approx. 0.05 VA per phase Switching capacity
at Inom = 5 A Approx. 0.3 VA per phase Make 1000 W / VA
for sensitive earth-fault CT at 1 A Approx. 0.05 VA Break 30 W / VA / 40 W resistive /
Overload capability 25 W at L/R ≤ 50 ms
Thermal (effective) 100 x Inom for 1 s Switching voltage ≤ 250 V DC
30 x Inom for 10 s Permissible current 5 A continuous,
4 x Inom continuous 30 A for 0.5 s making current,
Dynamic (impulse current) 250 x Inom (half cycle) 2000 switching cycles
Overload capability if equipped with
5 sensitive earth-fault CT
Thermal (effective) 300 A for 1 s Electrical tests
100 A for 10 s Specification
15 A continuous
Standards IEC 60255
Dynamic (impulse current) 750 A (half cycle)
ANSI C37.90, C37.90.1, C37.90.2,
Voltage transformer UL508
Rated voltage Vnom 100 V to 225 V Insulation tests
Power consumption at Vnom = 100 V < 0.3 VA per phase Standards IEC 60255-5; ANSI/IEEE C37.90.0
Overload capability in voltage path Voltage test (100 % test) 2.5 kV (r.m.s. value), 50/60 Hz
(phase-neutral voltage) all circuits except for auxiliary
Thermal (effective) 230 V continuous voltage and RS485/RS232 and
Auxiliary voltage time synchronization
Rated auxiliary DC 24/48 V 60/125 V 110/250 V Auxiliary voltage 3.5 kV DC
voltage Vaux AC 115/230 V Communication ports 500 V AC
Permissible tolerance DC 19–58 V 48–150 V 88–300 V and time synchronization
AC 92-138 V 184–265 V Impulse voltage test (type test) 5 kV (peak value); 1.2/50 µs; 0.5 J
Ripple voltage, ≤ 12 % all circuits, except communication 3 positive and 3 negative impulses
peak-to-peak ports and time synchronization, at intervals of 5 s
class III
Power consumption
Quiescent Approx. 3–4 W EMC tests for interference immunity; type tests
Energized Approx. 7–9 W Standards IEC 60255-6; IEC 60255-22
Backup time during ≥ 50 ms at V ≥ 110 V DC (product standard)
loss/short circuit of ≥ 20 ms at V ≥ 24 V DC EN 50082-2 (generic specification)
auxiliary voltage ≥ 200 ms at 115 V/230 V AC DIN 57435 Part 303
Binary inputs/indication inputs High-frequency test 2.5 kV (peak value); 1 MHz; τ =15 ms;
IEC 60255-22-1, class III 400 surges per s; test duration 2 s
Type 7SJ621 7SJ622 and VDE 0435 Part 303, class III
Number 8 11 Electrostatic discharge 8 kV contact discharge;
Voltage range 24–250 V DC IEC 60255-22-2 class IV 15 kV air gap discharge;
Pickup threshold modifiable by plug-in jumpers and EN 61000-4-2, class IV both polarities; 150 pF; Ri = 330 Ω

Pickup threshold 19 V DC 88 V DC Irradiation with radio-frequency 10 V/m; 27 to 500 MHz


field, non-modulated
For rated control voltage 24/48/60/ 110/125/ IEC 60255-22-3 (Report) class III
110/125 V 220/250 V DC
Irradiation with radio-frequency 10 V/m, 80 to 1000 MHz;
Response time/drop-out Approx. 3.5 field, amplitude-modulated AM 80 %; 1 kHz
time IEC 61000-4-3; class III
Power consumption 1.8 mA (independent of operating voltage) Irradiation with radio-frequency 10 V/m, 900 MHz; repetition
energized field, pulse-modulated rate 200 Hz, on duration 50 %
IEC 61000-4-3/ENV 50204; class III
Fast transient interference/burst 4 kV; 5/50 ns; 5 kHz;
IEC 60255-22-4 and IEC 61000-4-4, burst length = 15 ms;
class IV repetition rate 300 ms; both polarities;
Ri = 50 Ω; test duration 1 min

5/98 Siemens SIP · 2006


5 Overcurrent Protection / 7SJ62

Technical data

High-energy surge voltages During transportation


(Surge) Standards IEC 60255-21 and IEC 60068-2
IEC 61000-4-5; class III
Auxiliary voltage From circuit to circuit: 2 kV; 12 Ω; 9 µF Vibration Sinusoidal
across contacts: 1 kV; 2 Ω ;18 µF IEC 60255-21-1, class 2 5 to 8 Hz: ± 7.5 mm amplitude;
IEC 60068-2-6 8 to 150 Hz; 2 g acceleration,
Binary inputs/outputs From circuit to circuit: 2 kV; 42 Ω; 0.5 µF frequency sweep 1 octave/min
across contacts: 1 kV; 42 Ω; 0.5 µF 20 cycles in 3 perpendicular axes
Line-conducted HF, 10 V; 150 kHz to 80 MHz; Shock Semi-sinusoidal
amplitude-modulated AM 80 %; 1 kHz IEC 60255-21-2, Class 1 Acceleration 15 g, duration 11 ms
IEC 61000-4-6, class III IEC 60068-2-27 3 shocks in both directions of 3 axes
Power frequency magnetic field 30 A/m; 50 Hz, continuous Continuous shock Semi-sinusoidal
IEC 61000-4-8, class IV 300 A/m; 50 Hz, 3 s IEC 60255-21-2, class 1 Acceleration 10 g, duration 16 ms
IEC 60255-6 0.5 mT, 50 Hz IEC 60068-2-29 1000 shocks in both directions
Oscillatory surge withstand 2.5 to 3 kV (peak value), 1 to 1.5 MHz of 3 axes
capability damped wave; 50 surges per s;
ANSI/IEEE C37.90.1 duration 2 s, Ri = 150 to 200 Ω
Climatic stress tests
Fast transient surge withstand 4 to 5 kV; 10/150 ns; 50 surges per s
capability ANSI/IEEE C37.90.1 both polarities; duration 2 s, Ri = 80 Ω Temperatures
Type-tested acc. to IEC 60068-2-1 -25 °C to +85 °C /-13 °F to +185 °F
5
Radiated electromagnetic 35 V/m; 25 to 1000 MHz;
interference amplitude and pulse-modulated and -2, test Bd, for 16 h
ANSI/IEEE C37.90.2 Temporarily permissible operating -20 °C to +70 °C /-4 °F to -158 °F
Damped wave 2.5 kV (peak value, polarity temperature, tested for 96 h
IEC 60694 / IEC 61000-4-12 alternating) Recommended permanent operat- -5 °C to +55 °C /+25 °F to +131 °F
100 kHz, 1 MHz, 10 and 50 MHz, ing temperature acc. to IEC 60255-6
Ri = 200 Ω (Legibility of display may be im-
EMC tests for interference emission; type tests paired above +55 °C /+131 °F)
– Limiting temperature during -25 °C to +55 °C /-13 °F to +131 °F
Standard EN 50081-* (generic specification) permanent storage
Conducted interferences 150 kHz to 30 MHz – Limiting temperature during -25 °C to +70 °C /-13 °F to +158 °F
only auxiliary voltage IEC/CISPR Limit class B transport
22 Humidity
Radio interference field strength 30 to 1000 MHz Permissible humidity Annual average 75 % relative humid-
IEC/CISPR 11 Limit class B It is recommended to arrange the ity; on 56 days a year up to 95 % rela-
Units with a detached operator units in such a way that they are not tive humidity; condensation not
panel must be installed in a metal exposed to direct sunlight or permissible!
cubicle to maintain limit class B pronounced temperature changes
that could cause condensation.

Mechanical stress tests Unit design

Vibration, shock stress and seismic vibration Housing 7XP20

During operation Dimensions See dimension drawings, part 16

Standards IEC 60255-21 and IEC 60068-2 Weight


Surface-mounting housing 4.5 kg
Vibration Sinusoidal Flush-mounting housing 4.0 kg
IEC 60255-21-1, class 2 10 to 60 Hz; +/- 0.075 mm amplitude;
IEC 60068-2-6 60 to 150 Hz; 1 g acceleration Degree of protection
frequency sweep 1 octave/min acc. to EN 60529
20 cycles in 3 perpendicular axes Surface-mounting housing IP 51
Flush-mounting housing Front: IP 51, rear: IP 20;
Shock Semi-sinusoidal Operator safety IP 2x with cover
IEC 60255-21-2, class 1 Acceleration 5 g, duration 11 ms;
IEC 60068-2-27 3 shocks in both directions of 3 axes
Seismic vibration Sinusoidal
IEC 60255-21-3, class 1 1 to 8 Hz: ± 3.5 mm amplitude
IEC 60068-3-3 (horizontal axis)
1 to 8 Hz: ± 1.5 mm amplitude
(vertical axis)
8 to 35 Hz: 1 g acceleration
(horizontal axis)
8 to 35 Hz: 0.5 g acceleration
(vertical axis)
Frequency sweep 1 octave/min
1 cycle in 3 perpendicular axes

Siemens SIP · 2006 5/99


5 Overcurrent Protection / 7SJ62

Technical data

Serial interfaces Ethernet, electrical


Operating interface (front of unit) Connection Two RJ45 connectors
Connection Non-isolated, RS232; front panel, For flush-mounting housing/ mounting location "B"
9-pin subminiature connector surface-mounting housing with
detached operator panel
Transmission rate min. 4800 baud, max. 38400 baud
Distance Max. 20 m / 65.6 ft
Service/modem interface (rear of unit)
Test voltage 500 V AC against earth
Isolated interface for data transfer Port C: DIGSI 4/modem/RTD-box
Ethernet, optical
Transmission rate Setting as supplied 38400 baud
min. 4800 baud, max. 38400 baud Connection Intergr. ST connector for FO connec-
RS232/RS485 tion
For flush-mounting housing/ Mounting location "B"
Connection surface-mounting housing with
For flush-mounting housing/ 9-pin subminiature connector, detached operator panel
surface-mounting housing with mounting location “C” Optical wavelength 1300 nmm
detached operator panel Distance 1.5 km/0.9 miles
For surface-mounting housing At the bottom part of the housing:
PROFIBUS-FMS/DP
with two-tier terminal at the shielded data cable
5 top/bottom part Isolated interface for data transfer Port B
Distance RS232 15 m /49.2 ft to a control center
Distance RS485 Max. 1 km/3300 ft Transmission rate Up to 1.5 Mbaud
Test voltage 500 V AC against earth RS485
System interface (rear of unit) Connection
IEC 60870-5-103 protocol For flush-mounting housing/ 9-pin subminiature connector,
surface-mounting housing with mounting location “B”
Isolated interface for data transfer Port B detached operator panel
to a control center For surface-mounting housing At the bottom part of the housing:
Transmission rate Setting as supplied: 9600 baud, with two-tier terminal on the shielded data cable
min. 9600 baud, max. 19200 baud top/bottom part
Distance 1000 m/3300 ft ≤ 93.75 kbaud;
RS232/RS485
500 m/1500 ft ≤ 187.5 kbaud;
Connection 200 m/600 ft ≤ 1.5 Mbaud
For flush-mounting housing/ Mounting location “B” 100 m/300 ft ≤ 12 Mbaud
surface-mounting housing with Test voltage 500 V AC against earth
detached operator panel Fiber optic
For surface-mounting housing At the bottom part of the housing:
with two-tier terminal on the shielded data cable Connection fiber-optic cable Integr. ST connector for FO connec-
top/bottom part tion
Distance RS232 Max. 15 m/49 ft For flush-mounting housing/ Mounting location “B”
Distance RS485 Max. 1 km/3300 ft surface-mounting housing with
detached operator panel
Test voltage 500 V AC against earth
For surface-mounting housing At the bottom part of the housing
Fiber optic with two-tier terminal on the Important: Please refer to footnotes
1)
top/bottom part and 2) on page 5/112
Connection fiber-optic cable Integrated ST connector for fi-
ber-optic connection Optical wavelength 820 nm
For flush-mounting housing/ Mounting location “B” Permissible path attenuation Max. 8 dB, for glass fiber 62.5/125 µm
surface-mounting housing with Distance 500 kB/s 1.6 km/0.99 miles
detached operator panel 1500 kB/s 530 m/0.33 miles
For surface-mounting housing At the bottom part of the housing MODBUS RTU, ASCII, DNP 3.0
with two-tier terminal on the
top/bottom part Isolated interface for data transfer Port B
to a control center
Optical wavelength 820 nm
Permissible path attenuation Max. 8 dB, for glass fiber 62.5/125 µm Transmission rate Up to 19200 baud
Distance Max. 1.5 km/0.9 miles RS485
IEC 61850 protocol Connection
Isolated interface for data transfer: Port B, 100 Base T acc. to IEEE802.3 For flush-mounting housing/ 9-pin subminiature connector,
- to a control center surface-mounting housing with mounting location “B”
- with DIGSI detached operator panel
- between SIPROTEC 4 relays For surface-mounting housing At bottom part of the housing:
with two-tier terminal at the shielded data cable
Transmission rate 100 Mbit top/bottom part
Test voltage 500 V AC against earth

5/100 Siemens SIP · 2006


5 Overcurrent Protection / 7SJ62

Technical data

Fiber-optic Trip characteristics


IEC Normal inverse, very inverse,
Connection fiber-optic cable Integrated ST connector for fiber-optic extremely inverse, long inverse
connection ANSI Inverse, short inverse, long inverse
For flush-mounting housing/ Mounting location “B” moderately inverse, very inverse,
surface-mounting housing with extremely inverse, definite inverse
detached operator panel
User-defined characteristic Defined by a maximum of 20 value
For surface-mounting housing At the bottom part of the housing pairs of current and time delay
with two-tier terminal at the Important: Please refer to footnotes
top/bottom part 1)
and 2) on page 5/112 Dropout setting
Without disk emulation Approx. 1.05 · setting value Ip for
Optical wavelength 820 nm Ip/Inom ≥ 0.3, corresponds to approx.
Permissible path attenuation Max 8 dB. for glass fiber 62.5/125 µm 0.95 · pickup threshold
Distance Max. 1.5 km/0.9 miles With disk emulation Approx. 0.90 · setting value Ip

Time synchronization DCF77/IRIG-B signal (Format IRIG-B000) Tolerances


Pickup/dropout thresholds Ip, IEp 2 % of setting value or 50 mA1)
Connection 9-pin subminiature connector Pickup time for 2 ≤ I/Ip ≤ 20 5 % of reference (calculated) value
(SUB-D) + 2 % current tolerance, respectively
(terminal with surface-mounting 30 ms
housing) Dropout ratio for 0.05 ≤ I/Ip 5 % of reference (calculated) value 5
Voltage levels 5 V, 12 V or 24 V (optional) ≤ 0.9 + 2 % current tolerance, respectively
30 ms
Direction detection
Functions
For phase faults
Definite-time overcurrent protection, directional/non-directional
(ANSI 50, 50N, 67, 67N) Polarization With cross-polarized voltages;
Operating mode non-directional 3-phase (standard) or 2-phase With voltage memory for measure-
phase protection (ANSI 50) (L1 and L3) ment voltages that are too low
Setting ranges Forward range Vref,rot ± 86°
Rotation of reference voltage Vref,rot - 180° to 180° (in steps of 1°)
1)
Pickup phase elements I>, I>> 0.5 to 175 A or ∞ (in steps of 0.01 A)
Pickup earth elements IE>, IE>> 0.25 to 175 A or ∞1) (in steps of 0.01 A) Direction sensitivity For one and two-phase faults unlim-
ited;
Delay times T 0 to 60 s or ∞ (in steps of 0.01 s) For three-phase faults dynamically
Dropout delay time TDO 0 to 60 s (in steps of 0.01 s) unlimited;
Times Steady-state approx. 7 V
Pickup times (without inrush phase-to-phase
restraint, with inrush restraint For earth faults
+ 10 ms)
Non-directional Directional Polarization With zero-sequence quantities 3V0, 3I0
With twice the setting value Approx. 30 ms 45 ms or with negative-sequence quantities
With five times the setting value Approx. 20 ms 40 ms 3V2, 3I2
Dropout times Approx. 40 ms Forward range Vref,rot ± 86°
Rotation of reference voltage Vref,rot - 180° to 180° (in steps of 1°)
Dropout ratio Approx. 0.95 for
I/Inom ≥ 0.3 Direction sensitivity
Zero-sequence quantities 3V0, 3I0 VE ≈ 2.5 V displacement voltage,
Tolerances measured;
Pickup 2 % of setting value or 50 mA1) 3V0 ≈ 5 V displacement voltage,
Delay times T, TDO 1 % or 10 ms calculated
Inverse-time overcurrent protection, directional/non-directional Negative -sequence quantities 3V2 ≈ 5 V negative-sequence voltage;
(ANSI 51, 51N, 67, 67N) 3V2, 3I2 3I2 ≈ 225 mA negative-sequence cur-
Operating mode non-directional 3-phase (standard) or 2-phase rent1)
phase protection (ANSI 51) (L1 and L3) Tolerances (phase angle error under
Setting ranges reference conditions)
Pickup phase element IP 0.5 to 20 A or ∞ 1) (in steps of 0.01 A) For phase and earth faults ± 3 ° electrical
Pickup earth element IEP 0.25 to 20 A or ∞ 1) (in steps of 0.01 A) Inrush blocking
Time multiplier T 0.05 to 3.2 s or ∞ (in steps of 0.01 s) Influenced functions Time-overcurrent elements, I>, IE>,
(IEC characteristics) Ip, IEp (directional, non-directional)
Time multiplier D 0.05 to 15 s or ∞ (in steps of 0.01 s)
(ANSI characteristics) Lower function limit 1.25 A 1)
Upper function limit (setting range) 1.5 to 125 A 1) (in steps of 0.01 A)
Setting range I2f /I 10 to 45 % (in steps of 1 %)
Crossblock (IL1, IL2, IL3) ON/OFF

1) At Inom = 1 A, all limits divided by 5.

Siemens SIP · 2006 5/101


5 Overcurrent Protection / 7SJ62

Technical data

Dynamic setting change Earth-fault pickup for all types of earth faults
Controllable function Directional and non-directional Inverse-time characteristic (ANSI 51Ns)
pickup, tripping time User-defined characteristic Defined by a maximum of 20 pairs of
Start criteria Current criteria, current and delay time values
CB position via aux. contacts, Logarithmic inverse I
binary input, t = TIEEpmax − TIEEp ⋅ ln
auto-reclosure ready I EEp

Time control 3 timers Setting ranges


Pickup threshold IEEp
Current criteria Current threshold
For sensitive input 0.001 A to 1.4 A (in steps of 0.001 A)
(reset on dropping below threshold;
For normal input 0.25 to 20 A1) (in steps of 0.01 A)
monitoring with timer)
User defined
(Sensitive) earth-fault detection (ANSI 64, 50 Ns, 51Ns, 67Ns) Time multiplier T 0.1 to 4 s or ∞ (in steps of 0.01 s)
Displacement voltage starting for all types of earth fault (ANSI 64) Logarithmic inverse
Time multiplier TIEEp mul 0.05 to 15 s or ∞ (in steps of 0.01 s)
Setting ranges Delay time TIEEp 0.1 to 4 s or ∞ (in steps of 0.01 s)
Pickup threshold VE> (measured) 1.8 to 170 V (in steps of 0.1 V) Min time delay TIEEpmin 0 to 32 s (in steps of 0.01 s)
Pickup threshold 3V0> (calcu- 10 to 225 V (in steps of 0.1 V) Max. time delay TIEEpmax 0 to 32 s (in steps of 0.01 s)
lated)
5 Delay time TDelay pickup 0.04 to 320 s or ∞ (in steps of 0.01 s) Times
Additional trip delay TVDELAY 0.1 to 40000 s or ∞ (in steps of 0.01 s) Pickup times Approx. 60 ms (non-directional)
Approx 80 ms (directional)
Times
Pickup time Approx. 60 ms Pickup threshold Approx. 1.1 · IEEp
Dropout ratio 0.95 or (pickup value -0.6 V) Dropout ratio Approx. 1.05 · IEEp
Tolerances Tolerances
Pickup threshold VE (measured) 3 % of setting value or 0.3 V Pickup threshold IEEp 2 % of setting value or 1 mA
Pickup threshold 3V0 (calculated) 3 % of setting value or 3 V Delay times in linear range 7 % of reference value for 2 ≤ I/IEEp
Delay times 1 % of setting value or 10 ms ≤ 20 + 2 % current tolerance, or 70 ms
Phase detection for earth fault in an unearthed system Direction detection for all types of earth-faults (ANSI 67Ns)
Direction measurement IE and VE measured or
Measuring principle Voltage measurement (phase-to-earth) 3I0 and 3V0 calculated
Setting ranges Measuring principle Active/reactive power measurement
Vph min (earth-fault phase) 10 to 100 V (in steps of 1 V)
Setting ranges
Vph max (unfaulted phases) 10 to 100 V (in steps of 1 V) Measuring enable IRelease direct.
Measuring tolerance 3 % of setting value, or 1 V For sensitive input 0.001 to 1.2 A (in steps of 0.001 A)
acc. to DIN 57435 part 303 For normal input 0.25 to 150 A1) (in steps of 0.01 A)
Earth-fault pickup for all types of earth faults Measuring method cos ϕ and sin ϕ
Direction phasor ϕCorrection - 45 ° to + 45 ° (in steps of 0.1 °)
Definite-time characteristic (ANSI 50Ns) Dropout delay TReset delay 1 to 60 s (in steps of 1 s)
Setting ranges Angle correction for cable CT
Pickup threshold IEE>, IEE>> Angle correction F1, F2 0 ° to 5 ° (in steps of 0.1 °)
For sensitive input 0.001 to 1.5 A (in steps of 0.001 A) Current value I1, I2
For normal input 0.25 to 175 A1) (in steps of 0.01 A) For sensitive input 0.001 to 1.5 A (in steps of 0.001 A)
Delay times T for IEE>, IEE>> 0 to 320 s or ∞ (in steps of 0.01 s) For normal input 0.25 to 175 A1) (in steps of 0.01 A)
Dropout delay time TDO 0 to 60 s (in steps of 0.01 s) Tolerances
Times Pickup measuring enable 2 % of the setting value or 1 mA
Pickup times Approx. 60 ms (non-directional) Angle tolerance 3°
Approx. 80 ms (directional Note: Due to the high sensitivity the linear range of the measuring input IN
Dropout ratio Approx. 0.95 with integrated sensitive input transformer is from 0.001 A to 1.6 A. For cur-
Tolerances rents greater than 1.6 A, correct directionality can no longer be guaranteed.
Pickup threshold IEE>, IEE>> 2 % of setting value or 1 mA
Delay times 1 % of setting value or 20 ms

1) For Inom = 1 A, all limits divided by 5.

5/102 Siemens SIP · 2006


5 Overcurrent Protection / 7SJ62

Technical data

High-impedance restricted earth-fault protection (ANSI 87N) / single-phase Thermal overload protection (ANSI 49)
overcurrent protection Setting ranges
Setting ranges Factor k 0.1 to 4 (in steps of 0.01)
Pickup thresholds I>, I>>
For sensitive input 0.003 to 1.5 A or ∞ (in steps of 0.001 A) Time constant 1 to 999.9 min (in steps of 0.1 min)
For normal input 0.25 to 175 A1) or ∞ (in steps of 0.01 A) Warning overtemperature 50 to 100 % with reference
Delay times TI>, TI>> 0 to 60 s or ∞ (in steps of 0.01 s) Θalarm/Θtrip to the tripping overtemperature
Times (in steps of 1 %)
Pickup times Current warning stage Ialarm 0.5 to 20 A (in steps of 0.01 A)
Minimum Approx. 20 ms
Extension factor when stopped 1 to 10 with reference to the time con-
Typical Approx. 30 ms
kτ factor stant with the machine running
Dropout times Approx. 30 ms
(in steps of 0.1)
Dropout ratio Approx. 0.95 for I/Inom ≥ 0.5
Rated overtemperature (for Inom) 40 to 200 °C (in steps of 1 °C)
Tolerances
(I / k ⋅ I nom ) − (I pre / k ⋅ I nom )
2 2
Tripping characteristic
Pickup thresholds 3 % of setting value or t = τ th ⋅ ln
For (I/k · Inom) ≤ 8
(I / k ⋅ I nom ) − 1
2
1 % rated current at Inom = 1 or 5 A;
5 % of setting value or
3 % rated current at Inom = 0.1 A t =
Tripping time
Delay times 1 % of setting value or 10 ms τth =
Temperature rise time constant 5
Intermittent earth-fault protection I =
Load current
Ipre =
Preload current
Setting ranges k =
Setting factor acc. to VDE 0435
Pickup threshold Part 3011 and IEC 60255-8
For IE IIE> 0.25 to 175 A1) (in steps of 0.01 A) Inom = Rated (nominal) current of the
For 3I0 IIE> 0.25 to 175 A1) (in steps of 0.01 A) protection relay
For IEE IIE> 0.005 to 1.5 A (in steps of 0.001 A) Dropout ratios
Pickup prolon- TV 0 to 10 s (in steps of 0.01 s) Θ/ΘTrip Drops out with ΘAlarm
gation time Θ/ΘAlarm Approx. 0.99
Earth-fault accu- Tsum 0 to 100 s (in steps of 0.01 s) I/IAlarm Approx. 0.97
mulation time Tolerances
Reset time for Tres 1 to 600 s (in steps of 1 s) With reference to k · Inom Class 5 acc. to IEC 60255-8
accumulation With reference to tripping time 5 % +/- 2 s acc. to IEC 60255-8
Number of pickups for 2 to 10 (in steps of 1) Auto-reclosure (ANSI 79)
intermittent earth fault Number of reclosures 0 to 9
Times Shot 1 to 4 individually adjustable
Pickup times Program for phase fault
Current = 1.25 · pickup value Approx. 30 ms Start-up by Time-overcurrent elements (dir.,
Current ≥ 2 · pickup value Approx. 22 ms non-dir.), negative sequence, binary
Dropout time Approx. 22 ms input
Tolerances Program for earth fault
Pickup threshold IIE> 3 % of setting value, or 50 mA 1) Start-up by Time-overcurrent elements
(dir., non-dir.), sensitive earth-fault
Times TV, Tsum, Tres 1 % of setting value or 10 ms
protection, binary input
Blocking of ARC Pickup of protection functions,
three-phase fault detected by a protec-
tive element, binary input,
last TRIP command after the reclosing
cycle is complete (unsuccessful
reclosing),
TRIP command by the breaker failure
protection (50BF),
opening the CB without ARC initiation,
external CLOSE command

1) For Inom = 1 A, all limits divided by 5.

Siemens SIP · 2006 5/103


5 Overcurrent Protection / 7SJ62

Technical data

Auto-reclosure (cont'd) Negative-sequence current detection (ANSI 46)


Setting ranges Definite-time characteristic (ANSI 46-1 and 46-2)
Dead time 0.01 to 320 s (in steps of 0.01 s) Setting ranges
(separate for phase and earth Pickup current I2>, I2>> 0.5 to 15 A or ∞ (in steps of 0.01 A)
and individual for shots 1 to 4) Delay times 0 to 60 s or ∞ (in steps of 0.01 s)
Blocking duration for manual- 0.5 s to 320 s or 0 (in steps of 0.01 s) Dropout delay time TDO 0 to 60 s (in steps of 0.01 s)
CLOSE detection Functional limit All phase currents ≤ 20 A1)
Blocking duration after 0.5 s to 320 s (in steps of 0.01 s)
reclosure Times
Blocking duration after 0.01 to 320 s (in steps of 0.01 s) Pickup times Approx. 35 ms
dynamic blocking Dropout times Approx. 35 ms
Dropout ratio Approx. 0.95 for I2 /Inom > 0.3
Start-signal monitoring time 0.01 to 320 s or ∞ (in steps of 0.01 s)
Tolerances
Circuit-breaker supervision 0.1 to 320 s (in steps of 0.01 s) Pickup thresholds 3 % of the setting value or 50 mA1)
time Delay times 1 % or 10 ms
Max. delay of dead-time start 0 to 1800 s or ∞ (in steps of 0.1 s) Inverse-time characteristic (ANSI 46-TOC)
Maximum dead time extension 0.5 to 320 s or ∞(in steps of 0.01 s) Setting ranges
Action time 0.01 to 320 s or ∞ (in steps of 0.01 s) Pickup current 0.5 to 10 A 1) (in steps of 0.01 A)
5 The delay times of the following protection function can be altered individ- Time multiplier T 0.05 to 3.2 s or ∞ (in steps of 0.01 s)
ually by the ARC for shots 1 to 4 (IEC characteristics)
(setting value T = T, non-delayed T = 0, blocking T = ∞): Time multiplier D 0.5 to 15 s or ∞ (in steps of 0.01 s)
I>>, I>, Ip, Idir>>, Idir>, Ipdir (ANSI characteristics)
IE>>, IE>, IEp, IEdir>>, IEdir>, IEdir Functional limit All phase currents ≤ 20 A 1)
Additional functions Lockout (final trip), Trip characteristics
delay of dead-time start via binary input IEC Normal inverse, very inverse, extremely
(monitored), inverse
dead-time extension via binary input ANSI Inverse, moderately inverse, very in-
(monitored), verse, extremely inverse
co-ordination with other protection Pickup threshold Approx. 1.1 · I2p setting value
relays,
circuit-breaker monitoring, Dropout
evaluation of the CB contacts IEC and ANSI Approx. 1.05 · I2p setting value,
(without disk emulation) which is approx. 0.95 · pickup threshold
Breaker failure protection (ANSI 50 BF) ANSI with disk emulation Approx. 0.90 · I2p setting value
Setting ranges Tolerances
Pickup threshold CB I> 0.2 to 5 A1) (in steps of 0.01 A) Pickup threshold 3 % of the setting value or 50 mA1)
Delay time 0.06 to 60 s or ∞ (in steps of 0.01 s) Time for 2 ≤ M ≤ 20 5 % of setpoint (calculated)
Times +2 % current tolerance, at least 30 ms
Pickup times Starting time monitoring for motors (ANSI 48)
with internal start is contained in the delay time Setting ranges
start via control is contained in the delay time Motor starting current ISTARTUP 2.5 to 80 A1) (in steps of 0.01)
with external start is contained in the delay time Pickup threshold IMOTOR START 2 to 50 A1) (in steps of 0.01)
Dropout times Approx. 25 ms Permissible starting 1 to 180 s (in steps of 0.1 s)
Tolerances time TSTARTUP
Pickup value 2 % of setting value (50 mA)1) Permissible blocked rotor 0.5 to 120 s or ∞ (in steps of 0.1 s)
Delay time 1 % or 20 ms time TLOCKED-ROTOR
Tripping time characteristic 2

t =  STARTUP  ⋅ TSTARTUP
I
For I > IMOTOR START
 I 

ISTARTUP = Rated motor starting


current
I = Actual current flowing
TSTARTUP = Tripping time for rated
motor starting current
t = Tripping time in seconds
Dropout ratio IMOTOR START Approx. 0.95
Tolerances
Pickup threshold 2 % of setting value or 50 mA1)
Delay time 5 % or 30 ms

1) At Inom = 1 A, all limits divided by 5.

5/104 Siemens SIP · 2006


5 Overcurrent Protection / 7SJ62

Technical data

Restart inhibit for motors (ANSI 66) Undervoltage protection (ANSI 27)
Setting ranges Operating modes/measuring
Motor starting current relative 1.1 to 10 (in steps of 0.1) quantities
to rated motor current 3-phase Positive-sequence component or
IMOTOR START/IMotor Nom smallest of the phase-to-phase voltages
Rated motor current IMotor Nom 1 to 6 A1) (in steps of 0.01 A) 1-phase Single-phase phase-earth or
Max. permissible starting time 3 to 320 s (in steps of 1 s) phase-phase voltage
TStart Max Setting ranges
Equilibrium time TEqual 0 min to 320 min (in steps of 0.1 min) Pickup thresholds V<, V<<
Minimum inhibit time 0.2 min to 120 min (in steps of 0.1 min) 3-phase, phase-earth connec- 10 to 210 V (in steps of 1 V)
TMIN. INHIBIT TIME tion
Max. permissible number of 1 to 4 (in steps of 1) 3-phase, phase-phase connec- 10 to 120 V (in steps of 1 V)
warm starts tion
Difference between cold and 1 to 2 (in steps of 1) 1-phase connection 10 to 120 V (in steps of 1 V)
warm starts
Extension k-factor for cooling 0.2 to 100 (in steps of 0.1) Dropout ratio r 1.01 to 3 (in steps of 0.01)
simulations of rotor at zero speed Delay times T 0 to 100 s or ∞ (in steps of 0.01 s)
kτ at STOP Current Criteria "Bkr Closed 0.2 to 5 A1) (in steps of 0.01 A)
Extension factor for cooling time 0.2 to 100 (in steps of 0.1) IMIN"
constant with motor running Dropout threshold r ·V<(<) Max. 130 V for phase-phase voltages
5
kτ RUNNING Max. 225 V phase-earth voltages
Restarting limit Times
nc − 1
Θ restart = Θ rot max perm ⋅ Pickup times V<, V<<, V1<, V1<< Approx. 50 ms
nc Dropout times As pickup times
Tolerances
Θrestart = Temperature limit below
Pickup thresholds 3 % of setting value or 1 V
which restarting is possi-
Times 1 % of setting value or 10 ms
ble
Θrot max perm = Maximum permissible Overvoltage protection (ANSI 59)
rotor overtemperature Operating modes/measuring
(= 100 % in operational quantities
measured value
Θrot/Θrot trip) 3-phase Negative-sequence component or
nc = Number of permissible largest of the phase-to-phase voltages
start-ups from cold state 1-phase Single-phase phase-earth or
phase-phase voltage
Undercurrent monitoring (ANSI 37)
Setting ranges
Signal from the operational Predefined with programmable logic Pickup thresholds V>, V>>
measured values 3-phase, phase-earth connec- 40 to 260 V (in steps of 1 V)
Temperature monitoring box (ANSI 38) tion, largest phase-phase
voltage
Temperature detectors
3-phase, phase-phase connec- 40 to 150 V (in steps of 1 V)
Connectable boxes 1 or 2 tion, largest phase-phase
Number of temperature Max. 6 voltage
detectors per box 3-phase, negative-sequence 2 to 150 V (in steps of 1 V)
Type of measuring Pt 100 Ω or Ni 100 Ω or Ni 120 Ω voltage
Mounting identification “Oil” or “Environment” or “Stator” or 1-phase connection 40 to 150 V (in steps of 1 V)
“Bearing” or “Other”
Dropout ratio r 0.9 to 0.99 (in steps of 0.01)
Thresholds for indications Delay times T 0 to 100 s or ∞ (in steps of 0.01 s)
For each measuring detector
Times
Stage 1 -50 °C to 250 °C (in steps of 1 °C)
Pickup times V>, V>> Approx. 50 ms
-58 °F to 482 °F (in steps of 1 °F)
Pickup times V2>, V2>> Approx. 60 ms
or ∞ (no indication)
Dropout times As pickup times
Stage 2 -50 °C to 250 °C (in steps of 1 °C)
-58 °F to 482 °F (in steps of 1 °F) Tolerances
or ∞ (no indication) Pickup thresholds 3 % of setting value or 1 V
Times 1 % of setting value or 10 ms

1) At Inom = 1 A, all limits divided by 5.

Siemens SIP · 2006 5/105


5 Overcurrent Protection / 7SJ62

Technical data

Frequency protection (ANSI 81) Additional functions


Number of frequency elements 4 Operational measured values
Setting ranges Currents InA(kA)primary, inAsecondaryorin%Inom
Pickup thresholds for fnom = 50 Hz 45.5 to 54.5 Hz (in steps of 0.01 Hz) IL1, IL2, IL3
Pickup thresholds for fnom = 60 Hz 55.5 to 64.5 Hz (in steps of 0.01 Hz) Positive-sequence component I1
Delay times 0 to 100 s or ∞ (in steps of 0.01 s) Negative-sequence component I2
Undervoltage blocking, with 10 to 150 V (in steps of 1 V) IE or 3I0
positive-sequence voltage V1 Range 10 to 200 % Inom
Times Tolerance2) 1 % of measured value or 0.5 % Inom
Pickup times Approx. 150 ms Phase-to-earth voltages In kV primary, in V secondary or in % Vnom
Dropout times Approx. 150 ms VL1-E, VL2-E, VL3-E
Dropout Phase-to-phase voltages
∆f = pickup value - dropout value Approx. 20 mHz VL1-L2, VL2-L3, VL3-L1, VE or V0
Ratio undervoltage blocking Approx. 1.05 Positive-sequence component V1
Tolerances Negative-sequence component V2
Pickup thresholds Range 10 to 120 % Vnom
Frequency 10 mHz Tolerance2) 1 % of measured value or 0.5 % of Vnom
Undervoltage blocking 3 % of setting value or 1 V
5 Delay times 3 % of the setting value or 10 ms
S, apparent power In kVAr (MVAr or GVAr) primary and
in % of Snom
Fault locator (ANSI 21FL) Range 0 to 120 % Snom
Output of the fault distance In Ω secondary, Tolerance2) 1 % of Snom
in km / mile of line length for V/Vnom and I/Inom = 50 to 120 %
Starting signal Trip command, dropout of a protec- P, active Power With sign, total and phase-segregated in
tion element, via binary input kW (MW or GW) primary and in % Snom
Setting ranges Range 0 to 120 % Snom
Reactance (secondary) 0.001 to 1.9 Ω/km1) (in steps of 0.0001) Tolerance2) 2 % of Snom
0.001 to 3 Ω/mile1) (in steps of 0.0001) for V/Vnom and I/Inom = 50 to 120 %
Tolerances and cos ϕ = 0.707 to 1 with
Measurement tolerance acc. to 2.5 % fault location, or 0.025 Ω Snom = 3 ⋅ Vnom ⋅ I nom
VDE 0435, Part 303 for sinusoi- (without intermediate infeed) for Q, reactive power With sign, total and phase-segregated
dal measurement quantities 30 ° ≤ ϕK ≤ 90 ° and VK/Vnom ≥ 0.1 in kVAr (MVAr or GVAr)primary and
and IK/Inom ≥ 1 in % Snom
Range 0 to 120 % Snom
Tolerance2) 2 % of Snom
for V/Vnom and I/Inom = 50 to 120 %
and sin ϕ = 0.707 to 1 with
Snom = 3 ⋅ Vnom ⋅ I nom
cos ϕ, power factor (p.f.) Total and phase segregated
Range - 1 to + 1
Tolerance2) 3 % for cos ϕ ≥ 0.707
Frequency f In Hz
Range fnom ± 5 Hz
Tolerance2) 20 mHz
Temperature overload protection In %
Θ/ΘTrip
Range 0 to 400 %
Tolerance2) 5 % class accuracy per IEC 60255-8
Temperature restart inhibit In %
ΘL/ΘL Trip
Range 0 to 400 %
Tolerance2) 5 % class accuracy per IEC 60255-8
Restart threshold ΘRestart/ΘL Trip In %
Reclose time TReclose In min
Currents of sensitive ground fault In A (kA) primary and in mA second-
detection (total, real, and reactive ary
current) IEE, IEE real, IEE reactive
Range 0 mA to 1600 mA
Tolerance2) 2 % of measured value or 1 mA
RTD-box See section "Temperature monitoring
box"
1) At Inom = 1 A, all limits multiplied with 5.
2) At rated frequency.

5/106 Siemens SIP · 2006


5 Overcurrent Protection / 7SJ62

Technical data

Long-term averages Time stamping


Time window 5, 15, 30 or 60 minuets Resolution for event log (opera- 1 ms
Frequency of updates Adjustable tional annunciations)

Long-term averages Resolution for trip log (fault 1 ms


of currents IL1dmd, IL2dmd, IL3dmd, I1dmd in A (kA) annunciations)
of real power Pdmd in W (kW, MW) Maximum time deviation (internal 0.01 %
of reactive power Qdmd in VAr (kVAr, MVAr) clock)
of apparent power Sdmd in VAr (kVAr, MVAr) Battery Lithium battery 3 V/1 Ah,
Max. / Min. report type CR 1/2 AA, message "Battery
Report of measured values With date and time Fault" for insufficient battery charge

Reset, automatic Time of day adjustable (in minutes, Oscillographic fault recording
0 to 1439 min) Maximum 8 fault records saved,
Time frame and starting time adjust- memory maintained by buffer bat-
able (in days, 1 to 365 days, and ∞) tery in case of loss of power supply
Reset, manual Using binary input, Recording time Total 5 s
using keypad, Pre-trigger and post-fault recording
via communication and memory time adjustable
Min./Max. values for current IL1, IL2, IL3, Sampling rate for 50 Hz 1 sample/1.25 ms (16 sam/cyc)
5
I1 (positive-sequence component) Sampling rate for 60 Hz 1 sample/1.04 ms (16 sam/cyc)
Min./Max. values for voltages VL1-E, VL2-E, VL3-E Energy/power
V1 (positive-sequence component) Meter values for power in kWh (MWh or GWh) and kVARh
VL1-L2, VL2-L3, VL3-L1 Wp, Wq (real and reactive power (MVARh or GVARh)
Min./Max. values for power S, P, Q, cos ϕ, frequency demand)
Min./Max. values for overload pro- Θ/ΘTrip Tolerance1) ≤ 5 % for I > 0.5 Inom, V > 0.5 Vnom
tection and cos ϕ (p.f.) ≥ 0.707
Min./Max. values for mean values IL1dmd, IL2dmd, IL3dmd Statistics
I1 (positive-sequence component); Saved number of trips Up to 9 digits
Sdmd, Pdmd, Qdmd
Number of automatic reclosing Up to 9 digits
Local measured values monitoring commands (segregated according
Current asymmetry Imax/Imin > balance factor, to 1st and ≥ 2nd cycle)
for I>Ibalance limit Circuit-breaker wear
Voltage asymmetry Vmax/Vmin > balance factor, Methods • ΣIx with x = 1 .. 3
for V>Vlim • 2-point method (remaining service
Current sum |iL1 + iL2 + iL3 + kiE ⋅ iE| > limit value, life)
with Operation Phase-selective accumulation of mea-
I CT PRIM / I earth CT SEC sured values on TRIP command, up to
k iE = earth
CT PRIM / CT SEC 8 digits, phase-selective limit values,
monitoring indication
Current phase sequence Clockwise (ABC) / counter-clockwise
(ACB) Operating hours counter
Voltage phase sequence Clockwise (ABC) / counter-clockwise Display range Up to 7 digits
(ACB) Criterion Overshoot of an adjustable current
Limit value monitoring Predefined limit values, user-defined threshold (BkrClosed IMIN)
expansions via CFC Trip circuit monitoring
Fault recording With one or two binary inputs
Recording of indications of the last Commissioning aids
8 power system faults
Phase rotation field check,
Recording of indications of the last operational measured values,
3 power system ground faults circuit-breaker / switching device
test,
creation of a test measurement re-
port

1) At rated frequency.

Siemens SIP · 2006 5/107


5 Overcurrent Protection / 7SJ62

Technical data

Clock
Time synchronization DCF77/IRIG-B signal (telegram for-
mat IRIG-B000),
binary input,
communication
Setting group switchover of the function parameters
Number of available setting groups 4 (parameter group A, B, C and D)
Switchover performed Via keypad, DIGSI, system (SCADA)
interface or binary input
Control
Number of switching units Depends on the binary inputs and
outputs
Interlocking Programmable
Circuit-breaker signals Feedback, close, open, intermediate
position
5 Control commands Single command / double command
1, 1 plus 1 common or 2 trip contacts
Programmable controller CFC logic, graphic input tool
Local control Control via menu,
assignment of a function key
Remote control Via communication interfaces,
using a substation automation and
control system
(e.g. SICAM),
DIGSI 4 (e.g. via modem)

CE conformity
This product is in conformity with the Directives of the European Commu-
nities on the harmonization of the laws of the Member States relating to
electromagnetic compatibility (EMC Council Directive 89/336/EEC) and
electrical equipment designed for use within certain voltage limits (Council
Directive 73/23/EEC).
This unit conforms to the international standard IEC 60255, and the Ger-
man standard DIN 57435/Part 303 (corresponding to VDE 0435/Part 303).
Further applicable standards: ANSI/IEEE C37.90.0 and C37.90.1.
The unit conforms to the international standard IEC 60255, and the Ger-
man standard DIN 57435/Part 303 (corresponding to VDE 0435/Part 303).
This conformity is the result of a test that was performed by Siemens AG in
accordance with Article 10 of the Council Directive complying with the
generic standards EN 50081-2 and EN 50082-2 for the EMC Directive and
standard EN 60255-6 for the “low-voltage Directive”.

5/108 Siemens SIP · 2006


5 Overcurrent Protection / 7SJ62

Selection and ordering data Description Order No.


7SJ62 multifunction protection relay 7SJ62¨o – ¨¨¨¨¨ – ¨¨¨¨
Housing, binary inputs (BI) and outputs (BO)
Housing 1/3 19"; 8 BI, 8 BO, 1 live status contact 1
Housing 1/3 19"; 11 BI, 6 BO, 1 live status contact 2
see
Measuring inputs (3 x V, 4 x I) next
Iph = 1 A1), Ie = 1 A1) (min. = 0.05 A) page
Position 15 only with A, C, E, G 1
Iph = 1 A1), Ie = sensitive (min. = 0.001 A)
Position 15 only with B, D, F, H 2
Iph = 5 A1), Ie = 5 A1) (min. = 0.25 A)
Position 15 only with A, C, E, G 5
Iph = 5 A1), Ie = sensitive (min. = 0.001 A)
Position 15 only with B, D, F, H 6
Iph = 5 A1), Ie = 1 A1) (min. = 0.05 A)
Position 15 only with A, C, E, G 7

Rated auxiliary voltage (power supply, indication voltage)


24 to 48 V DC, threshold binary input 19 DC3) 2 5
60 to 125 V DC2), threshold binary input 19 DC3) 4
110 to 250 V DC2), 115 to 230 V4) AC, threshold binary input 88 V DC3) 5

Unit version
For panel surface mounting, two-tier terminal top/bottom B
For panel flush mounting, plug-in terminal, (2/3 pin connector) D
For panel flush mounting, screw-type terminal (direct connection/ring-type cable lugs) E

Region-specific default settings/function versions and language settings


Region DE, 50 Hz, IEC, language: German, selectable A
Region World, 50/60 Hz, IEC/ANSI, language: English (GB), selectable B
Region US, 60 Hz, ANSI, language: English (US), selectable C
Region FR, 50/60 Hz, IEC/ANSI, language: French, selectable D
Region World, 50/60 Hz, IEC/ANSI, language: Spanish, selectable E

System interface (Port B): Refer to page 5/112


No system interface 0
Protocols see page 5/112

Service interface (Port C)


No interface at rear side 0
DIGSI 4/modem, electrical RS232 1
DIGSI 4/modem/RTD-box5), electrical RS485 2
DIGSI 4/modem/RTD-box5)6), optical 820 nm wave length, ST connector 3

Measuring/fault recording
Fault recording 1
Slave pointer, mean values, min/max values, fault recording 3

1) Rated current can be selected by means of


jumpers.
2) Transition between the two auxiliary
voltage ranges can be selected by
means of jumpers.
3) The binary input thresholds can be
selected per binary input by means of
jumpers.
4) 230 V AC, starting from device version
…/EE.
5) Temperature monitoring box
o
7XV5662- AD10, refer to “Accessories”.
6) When using the temperature monitoring
box at an optical interface, the additional
RS485 fiber-optic converter
o
7XV5650-0 A00 is required.

Siemens SIP · 2006 5/109


5 Overcurrent Protection / 7SJ62

Selection and ordering data Description Order No.


7SJ62 multifunction protection relay 7SJ62 ¨o – ¨¨¨¨¨ – ¨¨¨¨
Designation ANSI No. Description
Basic version Control
50/51 Time-overcurrent protection
I>, I>>, Ip, reverse interlocking
50N/51N Earth-fault protection
IE>, IE>>, IEp
50N/51N Insensitive earth-fault protection via
IEE function: IEE>, IEE>>, IEEp1)
49 Overload protection (with 2 time constants)
46 Phase balance current protection
(negative-sequence protection)
37 Undercurrent monitoring
47 Phase sequence
59N/64 Displacement voltage
50BF Breaker failure protection
74TC Trip circuit supervision
4 setting groups, cold-load pickup
Inrush blocking
5 86 Lockout
n V, f 27/59 Under-/overvoltage
81 O/U Under-/overfrequency F E
n IEF V, f 27/59 Under-/overvoltage
81 O/U Under-/overfrequency
Intermittent earth fault P E
n Dir 67/67N Direction determination for overcurrent, phases and earth F C
n Dir V, f 67/67N Direction determination for overcurrent, phases and earth
27/59 Under-/overvoltage
81O/U Under-/overfrequency F G
n Dir IEF 67/67N Direction determination for overcurrent, phases and earth
Intermittent earth fault P C
Directional Dir 67/67N Direction determination for overcurrent, phases and earth
earth-fault 67Ns Directional sensitive earth-fault detection
detection 87N High-impedance restricted earth fault
n F D 2)
Directional Dir IEF 67/67N Direction determination for overcurrent, phases and earth
earth-fault 67Ns Directional sensitive earth-fault detection
detection 87N High-impedance restricted earth fault
n Intermittent earth fault
P D 2)
Directional 67Ns Directional sensitive earth-fault detection,
earth-fault 87N High-impedance restricted earth fault
detection
n F B 2)
Directional Motor V, f 67Ns Directional sensitive earth-fault detection,
earth-fault 87N High-impedance restricted earth fault
detection 48/14 Starting time supervision, locked rotor
n 66/86 Restart inhibit
27/59 Under-/overvoltage
2)
81O/U Under-/overfrequency H F
Directional Motor V, f 67/67N Direction determination for overcurrent, phases and earth
earth-fault Dir 67Ns Directional sensitive earth-fault detection
detection 87N High-impedance restricted earth fault
n 48/14 Starting time supervision, locked rotor
n Basic version included 66/86 Restart inhibit
V, f = Voltage, frequency protection 27/59 Under-/overvoltage
2)
Dir = Directional overcurrent protection 81O/U Under-/overfrequency HH
IEF = Intermittent earth fault
1) Only with insensitive earth-current
transformer when position 7 = 1, 5, 7.
2) For isolated/compensated networks
only with sensitive earth-current Continued on
transformer when position 7 = 2, 6. next page

5/110 Siemens SIP · 2006


5 Overcurrent Protection / 7SJ62

Selection and ordering data Description Order No. Order


code
7SJ62 multifunction protection relay 7SJ62¨o – ¨¨¨¨¨ – ¨¨¨¨ ¨¨¨¨
Designation ANSI No. Description
Basic version Control
50/51 Time-overcurrent protection
I>, I>>, Ip, reverse interlocking
50N/51N Earth-fault protection
IE>, IE>>, IEp
50N/51N Insensitive earth-fault protection via
IEE function: IEE>, IEE>>, IEEp1)
49 Overload protection (with 2 time constants)
46 Phase balance current protection
(negative-sequence protection)
37 Undercurrent monitoring
47 Phase sequence
59N/64 Displacement voltage
50BF Breaker failure protection
74TC Trip circuit supervision
4 setting groups, cold-load pickup
Inrush blocking 5
86 Lockout
Directional Motor V, f 67/67N Direction determination for
earth-fault Dir overcurrent, phases and earth
detection 67Ns Directional sensitive earth-fault detection
n 87N High-impedance restricted earth fault
48/14 Starting time supervision, locked rotor
66/86 Restart inhibit
27/59 Under-/overvoltage
81O/U Under-/overfrequency R H 2)
n Motor V, f 67/67N Direction determination for overcurrent,
Dir phases and earth
48/14 Starting time supervision, locked rotor
66/86 Reclosing lockout
27/59 Under/overvoltage
81 O/U Under/overfrequency H G
ARC, fault locator Without 0
79 With auto-reclosure 1
21 FL With fault locator 2
79, 21 FL With auto-reclosure, with fault locator 3
ATEX100 Certification
For protection of explosion-protected motors (increased-safety type of protection “e”) Z X 9 9

n Basic version included


V, f = Voltage, frequency protection
Dir = Directional overcurrent protection
IEF = Intermittent earth fault
1) Only with insensitive earth-current
transformer when position 7 = 1, 5, 7.
2) For isolated/compensated networks
only with sensitive earth-current
transformer when position 7 = 2, 6.

Siemens SIP · 2006 5/111


5 Overcurrent Protection / 7SJ62

Order number for system port B Description Order No. Order


code
7SJ62 multifunction protection relay 7SJ62 ¨o – ¨¨¨¨¨ – ¨¨¨¨–¨¨¨
System interface (on rear of unit, Port B)
No system interface 0
IEC 60870-5-103 protocol, RS232 1
IEC 60870-5-103 protocol, RS485 2
IEC 60870-5-103 protocol, 820 nm fiber, ST connector 3
PROFIBUS-FMS Slave, RS485 4
PROFIBUS-FMS Slave, 820 nm wavelength, single ring, ST connector 1) 5
1
PROFIBUS-FMS Slave, 820 nm wavelength, double ring, ST connector ) 6
PROFIBUS-DP Slave, RS485 9 L 0 A
1
PROFIBUS-DP Slave, 820 nm wavelength, double ring, ST connector ) 9 L 0B
MODBUS, RS485 9 L 0D
2
MODBUS, 820 nm wavelength, ST connector ) 9 L 0 E
5 DNP 3.0, RS485 9 L 0G
2
DNP 3.0, 820 nm wavelength, ST connector ) 9 L 0H
IEC 61850, 100 Mbit Ethernet, electrical, double, RJ45 connector (EN 100) 9 L 0R
2)
IEC 61850, 100 Mbit Ethernet, optical, double, ST connector (EN 100) 9 L 0 S
1) Not with position 9 = “B”; if 9 = “B”, please order 7SJ6 unit with RS485 port and separate fiber-optic converters.
For single ring, please order converter 6GK1502-2CB10, not available with position 9 = “B”.
For double ring, please order converter 6GK1502-3CB10, not available with position 9 = “B”.
The converter requires a 24 V AC power supply (e.g. power supply 7XV5810-0BA00)
2) Not available with position 9 = “B”

Sample order Position Order No. + Order code


7SJ6225-5EC91-3FC1+L0G

6 I/O’s: 11 BI/6 BO, 1 live status contact 2


7 Current transformer: 5 A 5
8 Power supply: 110 to 250 V DC, 115 V AC to 230 V AC 5
9 Unit version: Flush-mounting housing, screw-type terminals E
10 Region: US, English language (US); 60 Hz, ANSI C
11 Communication: System interface: DNP 3.0, RS485 9 L 0G
12 Communication: DIGSI 4, electric RS232 1
13 Measuring/fault recording: Extended measuring and fault records 3
14/15 Protection function package: Basic version plus directional TOC FC
16 With auto-reclosure 1

5/112 Siemens SIP · 2006


5 Overcurrent Protection / 7SJ62

Accessories Description Order No.

DIGSI 4
Software for configuration and operation of Siemens protection units
running under MS Windows 2000/XP Professional Edition
Basis Full version with license for 10 computers, on CD-ROM
(authorization by serial number) 7XS5400-0AA00
Professional DIGSI 4 Basis and additionally SIGRA (fault record analysis),
CFC Editor (logic editor), Display Editor (editor for default
and control displays) and DIGSI 4 Remote (remote operation) 7XS5402-0AA00
Professional + IEC 61850
Complete version:
DIGSI 4 Basis and additionally SIGRA (fault record analysis),
CFC Editor (logic editor), Display Editor (editor for default
and control displays) and DIGSI 4 Remote (remote operation)
+ IEC 61850 system configurator 7XS5403-0AA00

IEC 61850 System configurator


Software for configuration of stations with IEC 61850 communication under
DIGSI, running under MS Windows 2000 or XP Professional Edition
Optional package for DIGSI 4 Basis or Professional
5
License for 10 PCs. Authorization by serial number. On CD-ROM 7XS5460-0AA00

SIGRA 4
Software for graphic visualization, analysis and evaluation of fault records.
Can also be used for fault records of devices of other manufacturers (Comtrade
format). Running under MS Windows 2000 or XP Professional Edition.
(generally contained in DIGSI Professional, but can be ordered additionally)
Authorization by serial number. On CD-ROM. 7XS5410-0AA00

Temperature monitoring box


24 to 60 V AC/DC 7XV5662-2AD10
90 to 240 V AC/DC 7XV5662-5AD10

Varistor/Voltage arrester
Voltage arrester for high-impedance REF protection
125 Vrms; 600 A; 1S/S 256 C53207-A401-D76-1
240 Vrms; 600 A; 1S/S 1088 C53207-A401-D77-1

Connecting cable
Cable between PC/notebook (9-pin con.) and protection unit (9-pin connector)
(contained in DIGSI 4, but can be ordered additionally) 7XV5100-4
Cable between temperature monitoring box and SIPROTEC 4 unit
- length 5 m /16.4 ft 7XV5103-7AA05
- length 25 m /82 ft 7XV5103-7AA25
- length 50 m /164 ft 7XV5103-7AA50

Manual for 7SJ62/63/64,


English C53000-G1140-C147-6
French C53000-G1177-C147-2
Spanish C53000-G1178-C147-2

Catalog SIP 3.1 Spanish E50001-K4403-A111-A1-7800

Siemens SIP · 2006 5/113


5 Overcurrent Protection / 7SJ62

Accessories Description Order No. Size of package Supplier

LSP2289-afp.eps
Terminal safety cover
Voltage/current terminal 18-pole/12-pole C73334-A1-C31-1 1 Siemens
Voltage/current terminal 12-pole/8-pole C73334-A1-C32-1 1 Siemens
Connector 2-pin C73334-A1-C35-1 1 Siemens
Mounting rail
Connector 3-pin C73334-A1-C36-1 1 Siemens
1)
Crimp connector CI2 0.5 to 1 mm2 0-827039-1 4000 AMP
taped on reel
LSP2091-afp.eps
LSP2090-afp.eps

2 1)
Crimp connector CI2 0.5 to 1 mm 0-827396-1 1 AMP
2 1)
Crimp connector: Type III+ 0.75 to 1.5 mm 0-163084-2 1 AMP
1)
Crimp connector: Type III+ 0.75 to 1.5 mm
2
0-163083-7 4000 AMP
2-pin 3-pin
connector connector taped on reel

Crimping tool for Type III+ 0-539635-1 1 AMP 1)


1)
and matching female 0-539668-2 1 AMP
1)
Crimping tool for CI2 0-734372-1 1 AMP
LSP2093-afp.eps

LSP2092-afp.eps

1)
and matching female 1-734387-1 1 AMP
5
Short-circuit links
for current terminals C73334-A1-C33-1 1 Siemens
for other terminals C73334-A1-C34-1 1 Siemens
Short-circuit links Short-circuit links
for current termi- for other terminals Mounting rail for 19" rack C73165-A63-D200-1 1 Siemens
nals

1) Your local Siemens representative


can inform you on local suppliers.

5/114 Siemens SIP · 2006


5 Overcurrent Protection / 7SJ62

Connection diagram

Fig. 5/102 7SJ621 connection diagram

*) For pinout of communication ports see part 16 of this catalog.


For the allocation of the terminals of the panel surface mounting version
refer to the manual (http://www.siprotec.com).

Siemens SIP · 2006 5/115


5 Overcurrent Protection / 7SJ62

Connection diagram

Fig. 5/103 7SJ622 connection diagram

*) For pinout of communication ports see part 16 of this catalog.


For the allocation of the terminals of the panel surface mounting version
refer to the manual (http://www.siprotec.com).

5/116 Siemens SIP · 2006


5 Overcurrent Protection / 7SJ62

Dimension drawings in mm / inch

Dimension drawings for SIPROTEC 4


1/3 x 19" housing (7XP20)

Side view Rear view 1 Rear view 2 Panel cutout


7SA610, 7SD61, 7SJ64 7SJ61, 7SJ62, 7UT612,
7UM611
Fig. 16/22
Housing for panel flush mounting/
cubicle mounting (1/3 x 19")

Front view Side view

Fig. 16/23
1/3 x 19” surface-mounting housing

Siemens SIP · 2006 5/117