5 Overcurrent Protection / 7SJ80

SIPROTEC Compact 7SJ80


Multifunction Protection Relay
Function overview

Protection functions
• Time-overcurrent protection
(50, 50N, 51, 51N)
• Directional time-overcurrent protection
(67, 67N)
• Sensitive dir./non-dir. ground-fault
detection (67Ns, 50Ns)
• Displacement voltage (64)
• High-impedance restricted ground fault
(87N)
• Inrush restraint
LSP2874.tif

• Undercurrent monitoring (37)


• Overload protection (49)
• Under-/overvoltage protection (27/59)
• Under-/overfrequency protection (81O/U)
• Breaker failure protection (50BF)
5
Fig. 5/56
SIPROTEC Compact 7SJ80 • Phase unbalance or negative-sequence
multifunction protection relay protection (46)
• Phase-sequence monitoring (47)
• Synch-check (25)
• Auto-reclosure (79)
Highlights • Fault locator (21FL)
Description
• Lockout (86)
Removable current and voltage terminals
The SIPROTEC Compact 7SJ80 relays provide the ideal solution for fast and Control functions/programmable logic
can be used for line/feeder protection of secure replacement of relays. • Commands for the ctrl. of CB, disconnect
high and medium voltage networks with switches (isolators/isolating switches)
Binary input thresholds and current taps
grounded, low-resistance grounded, iso- • Control through keyboard, binary
lated or a compensated neutral point. The are software settings. There is thus no need
inputs, DIGSI 4 or SCADA system
relays have all the required functions to be to ever open the relay to adapt the hardware
configuration to a specific application.
• User-defined PLC logic with CFC
applied as a backup relay to a transformer (e.g. interlocking)
differential relay. The relay provides 9 programmable func- Monitoring functions
The 7SJ80 features “flexible protection tion keys that can be used to replace push-
buttons, select switches and control switches. • Operational measured values V, I, f
functions”. 20 additional protection func-
• Energy metering values Wp, Wq
tions can be created by the user. For exam- The battery for event and fault recording • Circuit-breaker wear monitoring
ple, a rate of change of frequency function memory can be exchanged from the front • Minimum and maximum values
or a reverse power function can be created. of the relay. • Trip circuit supervision (74TC)
The relay provides circuit-breaker control, The relay is available with IEC 61850 for • Fuse failure monitor
additional primary switching devices incredible cost savings in applications (e.g. • 8 oscillographic fault records
(grounding switches, transfer switches and transfer schemes with synch-check, bus Communication interfaces
isolating switches) can also be controlled interlocking and load shedding schemes).
from the relay. Automation or PLC logic • System/service interface
functionality is also implemented in the This compact relay provides protection, – IEC 61850
relay. The integrated programmable logic control, metering and PLC logic functional- – IEC 60870-5-103
(CFC) allows the user to add own func- ity. Secure and easy to use one page matrix – PROFIBUS-DP
tions, e.g. for the automation of switch- IO programming is now a standard feature. – DNP 3.0
gear (including: interlocking, transfer and – MODBUS RTU
The housing creates a sealed dust proof
load shedding schemes). The user is also • Ethernet interface for DIGSI 4
environment for the relay internal elec-
allowed to generate user-defined messages. • USB front interface for DIGSI 4
tronics. Heat build up is dissipated through
The communication module is independ- the surface area of the steel enclosure. No Hardware
ent from the protection. It can easily be dusty or corrosive air can be circulated • 4 current transformers
exchanged or upgraded to future commu- over the electronic components. The relay • 0/3 voltage transformers
nication protocols. thus will maintain its tested insulation • 3/7 binary inputs (thresholds
characteristic standards per IEC, IEEE, configurable using software)
even if deployed in harsh environment. • 5/8 binary outputs (2 changeover/
Form C contacts)
• 1 live-status contact
• Pluggable current and voltage terminals
Siemens SIP · 2008 5/55
5 Overcurrent Protection / 7SJ80

Selection and ordering data Description Order No.


7SJ80 overcurrent protection device 7SJ80oo – ooooo – oooo
Housing, binary inputs and outputs
Housing 1/6 19’’, 4 x I, 3 BI, 5 BO (2 changeover/Form C),
1 live status contact 1
Housing 1/6 19’’, 4 x I, 7 BI, 8 BO (2 changeover/Form C), see next page
1 live status contact 2
Housing 1/6 19’’, 4 x I, 3 x V, 3 BI, 5 BO (2 changeover/Form C),
1 live status contact 3
Housing 1/6 19’’, 4 x I, 3 x V, 7 BI, 8 BO (2 changeover/Form C),
1 live status contact 4

Measuring inputs, default settings


Iph = 1 A / 5 A, Ie = 1 A / 5 A 1
Iph = 1 A / 5 A, Iee (sensitive) = 0.001 to 1.6 A / 0.005 to 8 A 2

Rated auxiliary voltage


24 V / 48 V DC 1
60 V / 110 V / 125 V / 220 V DC, 115 V, 230 V AC 5
5
Unit version
Surface-mounting housing, screw-type terminal B
Flush-mounting housing, screw-type terminal E

Region-specific default and language settings


Region DE, IEC, language German (language selectable), standard front A
Region World, IEC/ANSI, language English (language selectable), standard front B
Region US, ANSI, language US-English (language selectable), US front C
Region FR, IEC/ANSI, language French (language selectable), standard front D
Region World, IEC/ANSI, language Spanish (language selectable), standard front E
Region World, IEC/ANSI, language Italian (language selectable), standard front F
Region RUS, IEC/ANSI, language Russian (language selectable), standard front G

5/56 Siemens SIP · 2008


5 Overcurrent Protection / 7SJ80

Selection and ordering data Description Order No. Order


code
7SJ80 overcurrent protection device 7SJ80oo – ooooo – oooo L 0 o
Port B (at bottom of device, rear)
No port 0
IEC 60870-5-103 or DIGSI 4/modem, electrical RS232 1 see
IEC 60870-5-103 or DIGSI 4/modem, electrical RS485 2 following
page
IEC 60870-5-103 or DIGSI 4/modem, optical 820 nm, ST connector 3
PROFIBUS-DP Slave, electrical RS485 9 L0A
PROFIBUS-DP Slave, optical, double ring, ST connector 9 L0B
MODBUS, electrical RS485 9 L0D
MODBUS, optical 820 nm, ST connector 9 L0E
DNP 3.0, electrical RS485 9 L0G
DNP 3.0, optical 820 nm, ST connector 9 L0H
IEC 60870-5-103, redundant, electrical RS485, RJ45 connector 9 L0P
IEC 61850, 100 Mbit Ethernet, electrical, double, RJ45 connector 9 L0R 5
IEC 61850, 100 Mbit Ethernet, optical, double, ST connector 9 L0S

Port A (at bottom of device, in front)


No port 0
With Ethernet interface (DIGSI, not IEC 61850), RJ45 connector 6

Measuring/fault recording
With fault recording 1
With fault recording, average values, min/max values 3

Siemens SIP · 2008 5/57


5 Overcurrent Protection / 7SJ80

Selection and ordering data Description Order No.


7SJ80 overcurrent protection device 7SJ80oo – ooooo – oooo
Designation ANSI No. Description
Basic version 50/51 Time-overcurrent protection phase I>, I>>, I>>>, Ip
50N/51N Time-overcurrent protection ground IE>, IE>>, IE>>>, IEp
50N(s)/51N(s)1) Sensitive ground fault protection IEE>, IEE>>, IEEp
87N 2) High impedance REF
49 Overload protection
74TC Trip circuit supervision
50BF Circuit-breaker failure protection
46 Negative-sequence protection
37 Undercurrent monitoring
86 Lockout
Parameter changeover
Monitoring functions
Control of circuit-breaker
Flexible protection functions (current parameters)
3)
Inrush restraint F A
Basic version + directional sensitive ground fault, voltage and frequency protection
5 n 67N Directional overcurrent protection ground
IE>, IE>>, IEp
1)
67N(s) Directional sensitive ground fault protection
IEE>, IEE>>, IEEp
64/59N Displacement voltage
27/59 Under-/overvoltage
81U/O Under-/overfrequency, f<, f>
47 Phase rotation
32/55/81R Flexible protection functions (current and voltage
parameters): Protective function for voltage, power,
power factor, frequency change F B 4)
Basic version + directional phase & ground overcurrent, directional sensitive ground fault,
voltage and frequency protection
n 67 Directional overcurrent protection phase
I>, I>>, Ip
67N Directional overcurrent protection ground
IE>, IE>>, IEp
67N(s) 1) Directional sensitive ground fault protection
IEE>, IEE>>, IEEp
64/59N Displacement voltage
27/59 Under-/overvoltage
81U/O Under-/overfrequency, f<, f>
47 Phase rotation
32/55/81R Flexible protection functions (current and voltage
parameters): Protective function for voltage, power,
power factor, frequency change F C 4)
Basic version + directional phase overcurrent, voltage and frequency protection + synch-check
n 67 Directional overcurrent protection phase
I>, I>>, Ip
27/59 Under-/overvoltage
81U/O Under-/overfrequency, f<, f>
47 Phase rotation
25 Synch-check
32/55/81R Flexible protection functions (current and voltage
parameters): Protective function for voltage, power,
power factor, frequency change F Q 4)
Auto-reclosure, fault locator
Without 0
n Basic version included 79 With auto-reclosure 1
21FL With fault locator 2
1) Depending on the ground current input 79/21FL With auto-reclosure, with fault locator 3
the function will be either sensitive (Iee)
or non-sensitive (Ie).
2) 87N (REF) only with sensitive ground
current input (position 7 = 2).
3) Only if position 6 = 1 or 2.
4) Only if position 6 = 3 or 4.

5/58 Siemens SIP · 2008


5 Overcurrent Protection / 7SJ80

Sample order Position Order No. + Order code


7SJ8041-5EC96-3FC1+L0G

6 I/O’s: 7 BI/8 BO, 1 live status contact 4


7 Current transformer: Iph = 1 A / 5 A, Ie = 1 A / 5 A 1
8 Power supply: 60 to 250 V DC, 115 V AC to 230 V AC 5
9 Unit version: Flush-mounting housing, screw-type terminals E
10 Region: US, English language (US); 60 Hz, ANSI C
11 Communication: System interface: DNP 3.0, RS485 9 L 0G
12 Communication: Ethernet interface (DIGSI, not IEC 61850) 6
13 Measuring/fault recording: Extended measuring and fault records 3
14/15 Protection function package: Basic version plus directional TOC FC
16 With auto-reclosure 1

5
Accessories Description Order No.

DIGSI 4
Software for configuration and operation of Siemens protection units
running under MS Windows 2000/XP Professional Edition/Vista.

Basis Full version with license for 10 computers, on CD-ROM


(authorization by serial number) 7XS5400-0AA00
Professional DIGSI 4 Basis and additionally SIGRA (fault record analysis),
CFC Editor (logic editor), Display Editor (editor for default
and control displays) and DIGSI 4 Remote (remote operation) 7XS5402-0AA00
Professional + IEC 61850
Complete version:
DIGSI 4 Basis and additionally SIGRA (fault record analysis),
CFC Editor (logic editor), Display Editor (editor for default
and control displays) and DIGSI 4 Remote (remote operation)
+ IEC 61850 system configurator 7XS5403-0AA00

IEC 61850 System configurator


Software for configuration of stations with IEC 61850 communication under
DIGSI, running under MS Windows 2000/XP Professional Edition/Vista.
Optional package for DIGSI 4 Professional
License for 10 PCs. Authorization by serial number. On CD-ROM 7XS5460-0AA00

SIGRA 4
Software for graphic visualization, analysis and evaluation of fault records.
Can also be used for fault records of devices of other manufacturers (Comtrade format).
Running under MS Windows 2000/XP Professional Edition/Vista
(generally contained in DIGSI Professional, but can be ordered additionally).
Authorization by serial number. On CD-ROM. 7XS5410-0AA00

Varistor/Voltage Arrester
Voltage arrester for high-impedance REF protection
125 Vrms; 600 A; 1S/S 256 C53207-A401-D76-1
240 Vrms; 600 A; 1S/S 1088 C53207-A401-D77-1

Manual for 7SJ80


English E50417-G1140-C343-A1
German E50417-G1100-C343-A1

Mounting rail for 19" rack C73165-A63-C200-4

Siemens SIP · 2008 5/59