5 Overcurrent Protection / 7SJ62

SIPROTEC 4 7SJ62

Multifunction Protection Relay

Function overview

Protection functions

· Time-overcurrent protection

(definite-time/inverse-time/user-def.)

· Directional time-overcurrent protection

(definite-time/inverse-time/user-def.)

· Sensitive dir./non-dir. earth-fault

detection

· Displacement voltage

· Intermittent earth-fault protection


spe.nepfa-9922PSL

· High-impedance restricted earth fault

· Inrush restraint

· Motor protection

– Undercurrent monitoring

– Starting time supervision

– Restart inhibit 5
Fig. 5/76

SIPROTEC 7SJ62 – Locked rotor

multifunction protection relay


· Overload protection

· Temperature monitoring

· Under-/overvoltage protection

· Under-/overfrequency protection

· Breaker failure protection


Description
· Negative-sequence protection

· Phase-sequence monitoring
The SIPROTEC 4 7SJ62 relays can be used

for line protection of high and medium · Auto-reclosure

voltage networks with earthed (grounded), · Fault locator

low-resistance earthed, isolated or com- · Lockout

pensated neutral point. With regard to


Control functions/programmable logic
motor protection, the SIPROTEC 4 7SJ62

is suitable for asynchronous machines of · Commands f. ctrl of CB and of isolators

all sizes. The relay performs all functions of · Control via keyboard, binary inputs,

backup protection supplementary to trans- DIGSI 4 or SCADA system

former differential protection.


· User-defined logic with CFC

The relay provides control of the circuit- (e.g. interlocking)

breaker, further switching devices and au- Monitoring functions

tomation functions. The integrated pro-


· Operational measured values V, I, f
grammable logic (CFC) allows the user to
· Energy metering values Wp, Wq
implement their own functions, e. g. for
· Circuit-breaker wear monitoring
the automation of switchgear (interlock-
· Slave pointer
ing). The user is also allowed to generate
· Trip circuit supervision
user-defined messages.
· Fuse failure monitor
The flexible communication interfaces are
· 8 oscillographic fault records
open for modern communication architec-
Communication interfaces
tures with control systems.

· System interface

– IEC 60870-5-103/ IEC 61850

– PROFIBUS-FMS/-DP

– DNP 3.0/MODBUS RTU

· Service interface for DIGSI 4 (modem)

· Front interface for DIGSI 4

· Time synchronization via IRIG B/DCF77

Hardware

· 4 current transformers

· 3 voltage transformers

· 8/11 binary inputs

· 8/6 output relays

Siemens SIP · 2006 5/83


5 Overcurrent Protection / 7SJ62

Application

Fig. 5/77 Function diagram

The SIPROTEC 4 7SJ62 unit is a numerical Line protection Backup protection

protection relay that also performs control


The 7SJ62 units can be used for line pro- The 7SJ62can be used universally for
and monitoring functions and therefore
tection of high and medium-voltage net- backup protection.
supports the user in cost-effective power
works with earthed (grounded), low-
system management, and ensures reliable
resistance earthed, isolated or compensated Metering values

supply of electric power to the customers.


neutral point.
Extensive measured values, limit values
Local operation has been designed accord-
and metered values permit improved
ing to ergonomic criteria. A large, easy-to-
Motor protection
system management.
read display was a major design aim.
When protecting motors, the 7SJ62 relay is

suitable for asynchronous machines of all


Control

sizes.
The integrated control function permits

control of disconnect devices, earthing


Transformer protection

switches or circuit-breakers via the inte-


The relay performs all functions of backup
grated operator panel, binary inputs,
protection supplementary to transformer
DIGSI 4 or the control and protection sys-
differential protection. The inrush sup-
tem (e.g. SICAM). A full range of com-
pression effectively prevents tripping by in-
mand processing functions is provided.
rush currents.

Programmable logic
The high-impedance restricted earth-fault

The integrated logic characteristics (CFC) protection detects short-circuits and insu-

allow the user to implement their own lation faults on the transformer.

functions for automation of switchgear

(interlocking) or a substation via a graphic

user interface. The user can also generate

user-defined messages.

5/84 Siemens SIP · 2006


5 Overcurrent Protection / 7SJ62

Application

ANSI No. IEC Protection functions

50, 50N I>, I>>, IE>, IE>> Definite time-overcurrent protection (phase/neutral)

51, 51N Ip, IEp Inverse time-overcurrent protection (phase/neutral)

67, 67N Idir>, Idir>>, Ip dir Directional time-overcurrent protection (definite/inverse, phase/neutral),

IEdir>, IEdir>>, IEp dir Directional comparison protection

67Ns/50Ns IEE>, IEE>>, IEEp Directional/non-directional sensitive earth-fault detection

– Cold load pick-up (dynamic setting change)

59N/64 VE, V0> Displacement voltage, zero-sequence voltage

– IIE> Intermittent earth fault

87N High-impedance restricted earth-fault protection

50BF Breaker failure protection 5

79 Auto-reclosure

46 I2> Phase-balance current protection (negative-sequence protection)

47 V2>, phase-sequence Unbalance-voltage protection and/or phase-sequence monitoring

49 J> Thermal overload protection

48 Starting time supervision

14 Locked rotor protection

66/86 Restart inhibit

37 I< Undercurrent monitoring

38 Temperature monitoring via external device (RTD-box), e.g. bearing temperature monitoring

27, 59 V<, V> Undervoltage/overvoltage protection

81O/U f>, f< Overfrequency/underfrequency protection

21FL Fault locator

Construction

Connection techniques and

housing with many advantages

1/3-rack sizes is the available housing

width of the 7SJ62 relays, referred to a 19”

module frame system. This means that

previous models can always be replaced.

The height is a uniform 244 mm for flush-

mounting housings and 266 mm for sur-


spe.nepfa-9902PSL

face-mounting housing for all housing

widths. All cables can be connected with or

without ring lugs.

In the case of surface mounting on a panel,

the connection terminals are located above

and below in the form of screw-type termi-

nals. The communication interfaces are

located in a sloped case at the top and bot-


Fig. 5/78 Rear view with screw-type terminals
tom of the housing.

Siemens SIP · 2006 5/85


5 Overcurrent Protection / 7SJ62

Protection functions

Time-overcurrent protection

(ANSI 50, 50N, 51, 51N)

This function is based on the phase-selec-

tive measurement of the three phase cur-

rents and the earth current (four trans-

formers). Two definite-time overcurrent

protection elements (DMT) exist both for

the phases and for the earth. The current

threshold and the delay time can be set

within a wide range. In addition, inverse-

time overcurrent protection characteristics

(IDMTL) can be activated.

5 Fig. 5/79 Fig. 5/80

Definite-time overcurrent protection Inverse-time overcurrent protection

Available inverse-time characteristics

Characteristics acc. to ANSI/IEEE IEC 60255-3

Inverse · ·

Short inverse ·

Long inverse · ·

Moderately inverse ·

Very inverse · ·

Extremely inverse · ·

Reset characteristics Inrush restraint

For easier time coordination with The relay features second harmonic re-

electromechanical relays, reset characte- straint. If the second harmonic is detected

ristics according to ANSI C37.112 and during transformer energization, pickup of

IEC 60255-3 /BS 142 standards are applied. non-directional and directional normal el-

When using the reset characteristic (disk ements are blocked.

emulation), a reset process is initiated after

the fault current has disappeared. This Cold load pickup/dynamic setting change

reset process corresponds to the reverse


For directional and non-directional time-
movement of the Ferraris disk of an elec-
overcurrent protection functions the initi-
tromechanical relay (thus: disk emulation).
ation thresholds and tripping times can be

switched via binary inputs or by time con-


User-definable characteristics
trol.

Instead of the predefined time characteris-

tics according to ANSI, tripping character-

istics can be defined by the user for phase

and earth units separately. Up to 20 cur-

rent/time value pairs may be programmed.

They are set as pairs of numbers or graphi-

cally in DIGSI 4.

5/86 Siemens SIP · 2006


5 Overcurrent Protection / 7SJ62

Protection functions

Directional time-overcurrent protection

(ANSI 67, 67N)

Directional phase and earth protection are

separate functions. They operate in parallel

to the non-directional overcurrent elements.

Their pickup values and delay times can be

set separately. Definite-time and inverse-

time characteristics are offered. The tripping

characteristic can be rotated about ± 180 de-

grees.
Fig. 5/81

By means of voltage memory, Directional characteristic of

the directional
directionality can be determined reliably
time-overcurrent
even for close-in (local) faults. If the
protection
switching device closes onto a fault and the

voltage is too low to determine direction,

directionality (directional decision) is


5
made with voltage from the voltage mem-

ory. If no voltage exists in the memory,

tripping occurs according to the coordina-

tion schedule.

For earth protection, users can choose

whether the direction is to be determined

via zero-sequence system or negative-se-

quence system quantities (selectable).

Using negative-sequence variables can be

advantageous in cases where the zero volt-

age tends to be very low due to unfavorable

zero-sequence impedances.

Directional comparison protection

(cross-coupling)

It is used for selective protection of sec-


Fig. 5/82

tions fed from two sources with instanta- Directional determination

neous tripping, i.e. without the using cosine measurements

for compensated networks


disadvantage of time coordination. The di-

rectional comparison protection is suitable

if the distances between the protection sta-

tions are not significant and pilot wires are For networks with an isolated neutral, the · Each element can be set in forward,

available for signal transmission. In addi- reactive current component is evaluated; reverse, or non-directional.

tion to the directional comparison protec- for compensated networks, the active cur-
· The function can also be operated in the
tion, the directional coordinated time- rent component or residual resistive cur-
insensitive mode as an additional
overcurrent protection is used for rent is evaluated. For special network
short-circuit protection.
complete selective backup protection. If conditions, e.g. high-resistance earthed

operated in a closed-circuit connection, an networks with ohmic-capacitive earth-fault


(Sensitive) earth-fault detection

interruption of the transmission line is de- current or low-resistance earthed networks


(ANSI 50Ns, 51Ns / 50N, 51N)

tected. with ohmic-inductive current, the tripping


For high-resistance earthed networks, a
characteristics can be rotated approxi-

(Sensitive) directional earth-fault detection


sensitive input transformer is connected to
mately ± 45 degrees.

(ANSI 64, 67Ns, 67N)


a phase-balance neutral current trans-

Two modes of earth-fault direction detec-


former (also called core-balance CT).
For isolated-neutral and compensated net-
tion can be implemented: tripping or

works, the direction of power flow in the The function can also be operated in the
“signalling only mode”.

zero sequence is calculated from the zero- insensitive mode as an additional short-

It has the following functions:


sequen- ce current I0 and zero-sequence circuit protection.

voltage V0.
· TRIP via the displacement voltage VE.

· Two instantaneous elements or one

instantaneous plus one user-defined

characteristic.

Siemens SIP · 2006 5/87


5 Overcurrent Protection / 7SJ62

When the high-impedance measurement


Protection functions
principle is applied, all current transform-

ers in the protected area are connected in


Intermittent earth-fault protection
parallel and operated on one common re-

Intermittent (re-striking) faults occur due


sistor of relatively high R whose voltage is

to insulation weaknesses in cables or as a


measured (see Fig. 5/83). In the case of

result of water penetrating cable joints.


7SJ6 units, the voltage is measured by de-

Such faults either simply cease at some


tecting the current through the (external)

stage or develop into lasting short-circuits.


resistor R at the sensitive current measure-

During intermittent activity, however,


ment input IEE. The varistor V serves to

star-point resistors in networks that are


limit the voltage in the event of an internal

impedance-earthed may undergo thermal


fault. It cuts off the high momentary volt-

overloading. The normal earth-fault pro-


age spikes occurring at transformer satura-

tection cannot reliably detect and interrupt


tion. At the same time, this results in

the current pulses, some of which can be


smoothing of the voltage without any

very brief.
noteworthy reduction of the average value.

The selectivity required with intermittent


If no faults have occurred and in the event

earth faults is achieved by summating the


of external faults, the system is at equilib-

duration of the individual pulses and by


rium, and the voltage through the resistor Fig. 5/83 High-impedance restricted earth-

triggering when a (settable) summed time fault protection


5 is approximately zero. In the event of in-

is reached. The response threshold IIE>


ternal faults, an imbalance occurs which

evaluates the r.m.s. value, referred to one


leads to a voltage and a current flow
Thermal overload protection (ANSI 49)
systems period.
through the resistor R.

For protecting cables and transformers,


The current transformers must be of the
Phase-balance current protection (ANSI 46) an overload protection with an integrated
same type and must at least offer a separate
(Negative-sequence protection) pre-warning element for temperature and
core for the high-impedance restricted
current can be applied. The temperature is
In line protection, the two-element phase-
earth-fault protection. They must in par-
calculated using a thermal homogeneous-
balance current/negative-sequence protec-
ticular have the same transformation ratio
body model (according to IEC 60255-8),
tion permits detection on the high side of
and an approximately identical knee-point
which takes account both of the energy en-
high-resistance phase-to-phase faults and
voltage. They should also demonstrate only
tering the equipment and the energy losses.
phase-to-earth faults that are on the low
minimal measuring errors.
The calculated temperature is constantly ad-
side of a transformer (e.g. with the switch
justed accordingly. Thus, account is taken of
group Dy 5). This provides backup protec-
Auto-reclosure (ANSI 79)
the previous load and the load fluctuations.
tion for high-resistance faults beyond the
Multiple reclosures can be defined by the
transformer.
For thermal protection of motors (especially
user and lockout will occur if a fault is
the stator) a further time constant can be set
present after the last reclosure. The follow-
Breaker failure protection (ANSI 50BF)
so that the thermal ratios can be detected
ing functions are possible:
If a faulted portion of the electrical circuit correctly while the motor is rotating and

is not disconnected upon issuance of a trip · 3-pole ARC for all types of faults when it is stopped. The ambient tempera-

command, another command can be initi- ture or the temperature of the coolant can
· Separate settings for phase and earth faults
ated using the breaker failure protection be detected serially via an external tempera-

· Multiple ARC, one rapid auto-reclosure ture monitoring box (resistance-tempera-


which operates the circuit-breaker, e.g. of
(RAR) and up to nine delayed
an upstream (higher-level) protection re- ture detector box, also called RTD- box).

auto-reclosures (DAR)
lay. Breaker failure is detected if, after a The thermal replica of the overload function

trip command, current is still flowing in is automatically adapted to the ambient


· Starting of the ARC depends on the trip

the faulted circuit. As an option, it is possi- conditions. If there is no RTD-box it is as-


command selection (e.g. 46, 50, 51, 67)

ble to make use of the circuit-breaker posi- sumed that the ambient temperatures are
· Blocking option of the ARC via binary
tion indication. constant.
inputs

High-impedance restricted earth-fault pro- · ARC can be initiated externally or via CFC Settable dropout delay times

tection (ANSI 87N)


· The directional and non-directional ele- If the devices are used in parallel with elec-

The high-impedance measurement princi- ments can either be blocked or operated tromechanical relays in networks with inter-

ple is an uncomplicated and sensitive non-delayed depending on the auto- mittent faults, the long dropout times of the

method for detecting earth faults, espe- reclosure cycle electromechanical devices (several hundred

cially on transformers. It can also be ap- milliseconds) can lead to problems in terms
· Dynamic setting change of the directional
plied to motors, generators and reactors of time grading. Clean time grading is only
and non-directional elements can be acti-
when these are operated on an earthed net- possible if the dropout time is approxi-
vated depending on the ready AR
work. mately the same. This is why the parameter

of dropout times can be defined for certain

functions such as time-overcurrent protec-

tion, earth short-circuit and phase-balance

current protection.

5/88 Siemens SIP · 2006


5 Overcurrent Protection / 7SJ62

Protection functions

Motor protection

Restart inhibit (ANSI 66/86)

If a motor is started up too many times in

succession, the rotor can be subject to ther-

mal overload, especially the upper edges of

the bars. The rotor temperature is calcu-

lated from the stator current. The reclosing

lockout only permits start-up of the motor

if the rotor has sufficient thermal reserves

for a complete start-up (see Fig. 5/84).

Emergency start-up

This function disables the reclosing lock-

out via a binary input by storing the state

of the thermal replica as long as the binary

input is active. It is also possible to reset


5
the thermal replica to zero.
Fig. 5/84

Temperature monitoring (ANSI 38)

Up to two temperature monitoring boxes


If the trip time is rated according to the Undervoltage protection (ANSI 27)

with a total of 12 measuring sensors can be


above formula, even a prolonged start-up
The two-element undervoltage protection
used for temperature monitoring and de-
and reduced voltage (and reduced start-up
provides protection against dangerous
tection by the protection relay. The ther-
current) will be evaluated correctly. The
voltage drops (especially for electric ma-
mal status of motors, generators and
tripping time is inverse (current depend-
chines). Applications include the isolation
transformers can be monitored with this
ent).
of generators or motors from the network
device. Additionally, the temperature of

A binary signal is set by a speed sensor to to avoid undesired operating states and a
the bearings of rotating machines are mon-

detect a blocked rotor. An instantaneous possible loss of stability. Proper operating


itored for limit value violation. The tem-

tripping is effected. conditions of electrical machines are best


peratures are being measured with the help
evaluated with the positive-sequence quan-
of temperature detectors at various loca-
Phase-balance current protection (ANSI 46) tities. The protection function is active
tions of the device to be protected. This
(Negative-sequence protection) over a wide frequency range (45 to 55, 55
data is transmitted to the protection relay
1)
to 65 Hz) . Even when falling below this
via one or two temperature monitoring The negative-sequence / phase-balance
frequency range the function continues to
boxes (see “Accessories”, page 5/113). current protection detects a phase failure
work, however, with a greater tolerance
or load unbalance due to network asym-
band.
Starting time supervision (ANSI 48/14)
metry and protects the rotor from imper-

Starting time supervision protects the mo- missible temperature rise. The function can operate either with the

tor against long unwanted start-ups that positive phase-sequence system voltage

Undercurrent monitoring (ANSI 37) (default) or with the phase-to-phase volt-


might occur in the event of excessive load

torque or excessive voltage drops within ages, and can be monitored with a current
With this function, a sudden drop in cur-

the motor, or if the rotor is locked. Rotor criterion. Three-phase and single-phase
rent, which can occur due to a reduced

temperature is calculated from measured connections are possible.


motor load, is detected. This may be due to

stator current. The tripping time is calcu- shaft breakage, no-load operation of
Frequency protection (ANSI 81O/U)
lated according to the following equation: pumps or fan failure.

Frequency protection can be used for over-


for I > IMOTOR START
Voltage protection frequency and underfrequency protection.
2

æ IA ö Electric machines and parts of the system


t=ç ÷ ×T Overvoltage protection (ANSI 59)
A
è I ø are protected from unwanted speed devia-

The two-element overvoltage protection


I = Actual current flowing
tions. Unwanted frequency changes in the

detects unwanted network and machine


network can be detected and the load can
IMOTOR START = Pickup current to detect a motor
overvoltage conditions. The function can
start be removed at a specified frequency set-

operate either with phase-to-phase voltage


ting.
t = Tripping time
(default) or with the negative phase-se-
IA = Rated motor starting current
quence system voltage. Three-phase and
TA = Tripping time at rated motor
single-phase connections are possible.
starting current

1) The 45 to 55, 55 to 65 Hz range is available

for fN = 50/60 Hz.

Siemens SIP · 2006 5/89


5 Overcurrent Protection / 7SJ62

Customized functions (ANSI 32, 51V, 55, etc.)


Protection functions/Functions

Additional functions, which are not time

Frequency protection can be used over a critical, can be implemented via the CFC

wide frequency range (45 to 55, 55 to using measured values. Typical functions
1)
65 Hz) . There are four elements include reverse power, voltage controlled

(selectable as overfrequency or overcurrent, phase angle detection, and

underfrequency) and each element can be zero-sequence voltage detection.

delayed separately. Blocking of the fre-

quency protection can be performed if us- Commissioning

ing a binary input or by using an


Commissioning could hardly be easier and
undervoltage element.
is fully supported by DIGSI 4. The status of

the binary inputs can be read individually


Fault locator (ANSI 21FL)
and the state of the binary outputs can be

The fault locator specifies the distance to a set individually. The operation of switch-

fault location in kilometers or miles or the ing elements (circuit-breakers, disconnect

reactance of a second fault operation. devices) can be checked using the switch-

ing functions of the bay controller. The an-

Circuit-breaker wear monitoring alog measured values are represented as

wide-ranging operational measured values.


5 Methods for determining circuit-breaker
To prevent transmission of information to
contact wear or the remaining service life
the control center during maintenance, the
of a circuit-breaker (CB) allow CB mainte- Fig. 5/85 CB switching cycle diagram

bay controller communications can be dis-


nance intervals to be aligned to their actual
abled to prevent unnecessary data from be-
degree of wear. The benefit lies in reduced
Automation / user-defined logic
ing transmitted. During commissioning, all
maintenance costs.
indications with test marking for test pur-
With integrated logic, the user can set, via a
There is no mathematically exact method poses can be connected to a control and
graphic interface (CFC), specific functions
of calculating the wear or the remaining protection system.
for the automation of switchgear or substa-
service life of circuit-breakers that takes
tion. Functions are activated via function
into account the arc-chamber's physical Test operation
keys, binary input or via communication
conditions when the CB opens. This is why
During commissioning, all indications can interface.
various methods of determining CB wear
be passed to an automatic control system
have evolved which reflect the different op-
Switching authority
for test purposes.
erator philosophies. To do justice to these,
Switching authority is determined accord-
the devices offer several methods:
Control and automatic functions
ing to parameters, communication or by
· I
key-operated switch (when available).
Control
x
· S I , with x = 1... 3 If a source is set to “LOCAL”, only local
In addition to the protection functions, the
switching operations are possible. The fol-
The devices additionally offer a new SIPROTEC 4 units also support all control
lowing sequence of switching authority is
method for determining the remaining ser- and monitoring functions that are required
laid down: “LOCAL”; DIGSI PC program,
vice life: for operating medium-voltage or high-
“REMOTE”.
· Two-point method voltage substations.

The CB manufacturers double-logarithmic The main application is reliable control of


Command processing

switching cycle diagram (see Fig. 5/85) and switching and other processes. All the functionality of command process-
the breaking current at the time of contact
ing is offered. This includes the processing
The status of primary equipment or auxil-
opening serve as the basis for this method.
of single and double commands with or
iary devices can be obtained from auxiliary
After CB opening, the two-point method
without feedback, sophisticated monitor-
contacts and communicated to the 7SJ62
calculates the number of still possible
ing of the control hardware and software,
via binary inputs. Therefore it is possible to
switching cycles. To this end, the two
checking of the external process, control
detect and indicate both the OPEN and
points P1 and P2 only have to be set on the
actions using functions such as runtime
CLOSED position or a fault or intermedi-
device. These are specified in the CB's tech-
monitoring and automatic command ter-
ate circuit-breaker or auxiliary contact po-
nical data.
mination after output. Here are some typi-
sition.
cal applications:
All of these methods are phase-selective
The switchgear or circuit-breaker can be
and a limit value can be set in order to ob-
· Single and double commands using 1,
controlled via:
tain an alarm if the actual value falls below
1 plus 1 common or 2 trip contacts
or exceeds the limit value during determi- – integrated operator panel

– binary inputs · User-definable bay interlocks


nation of the remaining service life.

– substation control and protection system


· Operating sequences combining several
– DIGSI 4
switching operations such as control of

circuit-breakers, disconnectors and

earthing switches
1) The 45 to 55, 55 to 65 Hz range is

available for fN= 50/60 Hz

5/90 Siemens SIP · 2006


5 Overcurrent Protection / 7SJ62

Measured values
Functions

The r.m.s. values are calculated from the

· Triggering of switching operations, indi- acquired current and voltage along with

cations or alarm by combination with the power factor, frequency, active and

existing information reactive power. The following functions

are available for measured value process-

Assignment of feedback to command ing:

The positions of the circuit-breaker or · Currents IL1, IL2, IL3, IE, IEE (67Ns)

switching devices and transformer taps are


· Voltages VL1, VL2, VL3, VL1L2, VL2L3, VL3L1
acquired by feedback. These indication in-

puts are logically assigned to the corre- · Symmetrical components

sponding command outputs. The unit can I1, I2, 3I0; V1, V2, V0

therefore distinguish whether the indica-


· Power Watts, Vars, VA/P, Q, S
tion change is a consequence of switching
(P, Q: total and phase selective)
operation or whether it is a spontaneous
· Power factor (cos j),
change of state.
(total and phase selective)

Chatter disable · Frequency

spe.f7702PSL
Chatter disable feature evaluates whether, · Energy ± kWh, ± kVarh, forward and

in a configured period of time, the number reverse power flow

of status changes of indication input ex-


· Mean as well as minimum and maximum
ceeds a specified figure. If exceeded, the in-
current and voltage values
dication input is blocked for a certain

period, so that the event list will not record · Operating hours counter

excessive operations.
· Mean operating temperature of overload

function
Indication filtering and delay

· Limit value monitoring


Binary indications can be filtered or de-
Limit values are monitored using pro-
layed.
grammable logic in the CFC. Commands
Fig. 5/86

Filtering serves to suppress brief changes in can be derived from this limit value indi-
NXAIR panel (air-insulated)

potential at the indication input. The indi- cation.

cation is passed on only if the indication


· Zero suppression
voltage is still present after a set period of
In a certain range of very low measured
time. In the event of indication delay, there
values, the value is set to zero to suppress
is a wait for a preset time. The information
interference.
is passed on only if the indication voltage is

still present after this time. Metered values

For internal metering, the unit can calcu-


Indication derivation

late an energy metered value from the


A further indication (or a command) can
measured current and voltage values. If an
be derived from an existing indication.
external meter with a metering pulse out-
Group indications can also be formed. The
put is available, the SIPROTEC 4 unit can
volume of information to the system inter-
obtain and process metering pulses via an
face can thus be reduced and restricted to
indication input.
the most important signals.

The metered values can be displayed and

Switchgear cubicles for passed on to a control center as an accu-

high/medium voltage mulation with reset. A distinction is made

between forward, reverse, active and reac-


All units are designed specifically to meet
tive energy.
the requirements of high/medium-voltage

applications.

In general, no separate measuring instru-

ments (e.g., for current, voltage, frequency,

…) or additional control components are

necessary.

Siemens SIP · 2006 5/91


5 Overcurrent Protection / 7SJ62

System interface protocols (retrofittable)


Communication

IEC 61850 protocol

In terms of communication, the units offer


As of mid-2004, the Ethernet-based
substantial flexibility in the context of con-
IEC 61850 protocol is the worldwide stan-
nection to industrial and power automa-
dard for protection and control systems
tion standards. Communication can be
used by power supply corporations.
extended or added on thanks to modules
Siemens is the first manufacturer to sup-
for retrofitting on which the common pro-
port this standard. By means of this proto-
tocols run. Therefore, also in the future it
col, information can also be exchanged
will be possible to optimally integrate units
directly between bay units so as to set up
into the changing communication infra-
simple masterless systems for bay and sys-
structure, for example in Ethernet net-
tem interlocking. Access to the units via
works (which will also be used increasingly
the Ethernet bus will also be possible with
in the power supply sector in the years to
DIGSI.
come).

IEC 60870-5-103 protocol


Fig. 5/87
Serial front interface

The IEC 60870-5-103 protocol is an inter- IEC 60870-5-103: Radial fiber-optic connection

There is a serial RS232 interface on the


national standard for the transmission of

5 front of all the units. All of the unit’s func-


protective data and fault recordings. All
tions can be set on a PC by means of the
messages from the unit and also control
DIGSI 4 protection operation program.
commands can be transferred by means of
Commissioning tools and fault analysis are
published, Siemens-specific extensions to
also built into the program and are avail-
the protocol.
able through this interface.

PROFIBUS-FMS
1)
Rear-mounted interfaces

PROFIBUS-FMS is an internationally stan-


A number of communication modules
dardized communication system
suitable for various applications can be fit-
(EN 50170) for efficient performance of
ted in the rear of the flush-mounting hous-
communication tasks in the bay area.
ing. In the flush-mounting housing, the
SIPROTEC 4 units use a profile specially
modules can be easily replaced by the user.
optimized for protection and control re-
The interface modules support the follow-
quirements. DIGSI can also work on the
ing applications:
basis of PROFIBUS-FMS. The units are

linked to a SICAM automation system.


· Time synchronization interface

All units feature a permanently integrated


PROFIBUS-DP protocol
electrical time synchronization interface.

It can be used to feed timing telegrams in PROFIBUS-DP is the most widespread

IRIG-B or DCF77 format into the units protocol in industrial automation. Via
Fig. 5/88
via time synchronization receivers. PROFIBUS-DP, SIPROTEC units make
PROFIBUS: Fiber-optic double ring circuit
· System interface their information available to a SIMATIC

Communication with a central control controller or, in the control direction, re-

system takes place through this interface. ceive commands from a central SIMATIC.

Radial or ring type station bus topologies Measured values can also be transferred.

can be configured depending on the cho-

sen interface. Furthermore, the units can MODBUS RTU protocol

exchange data through this interface via


This uncomplicated, serial protocol is
Ethernet and IEC 61850 protocol and can
mainly used in industry and by power sup-
also be operated by DIGSI.
ply corporations, and is supported by a
· Service interface
number of unit manufacturers. SIPROTEC
The service interface was conceived for re-
units function as MODBUS slaves, making
mote access to a number of protection
their information available to a master or
units via DIGSI. On all units, it can be an
receiving information from it. A time-
electrical RS232/RS485 or an optical inter-
stamped event list is available.
face. For special applications, a maximum

of two temperature monitoring boxes

(RTD-box) can be connected to this inter-

face as an alternative.

Fig. 5/89

Bus structure for station bus with Ethernet and


1) For units in panel surface-mounting housings
IEC 61850, fiber-optic ring

please refer to note on page 5/112.

5/92 Siemens SIP · 2006


5 Overcurrent Protection / 7SJ62

Communication

DNP 3.0 protocol

Power supply corporations use the serial

DNP 3.0 (Distributed Network Protocol)

for the station and network control levels.

SIPROTEC units function as DNP slaves,

supplying their information to a master

system or receiving information from it.

System solutions for protection and station

control

Together with the SICAM power automa-

tion system, SIPROTEC 4 can be used with

PROFIBUS-FMS. Over the low-cost elec-

trical RS485 bus, or interference-free via

the optical double ring, the units exchange

information with the control system.

5
Units featuring IEC 60870-5-103 interfaces

can be connected to SICAM in parallel via

the RS485 bus or radially by fiber-optic

link. Through this interface, the system is

open for the connection of units of other

manufacturers (see Fig. 5/87).


Fig. 5/90

Because of the standardized interfaces, System solution/communication

SIPROTEC units can also be integrated

into systems of other manufacturers or in

SIMATIC. Electrical RS485 or optical in-

terfaces are available. The optimum physi-

cal data transfer medium can be chosen

thanks to opto-electrical converters. Thus,

the RS485 bus allows low-cost wiring in

the cubicles and an interference-free opti-

cal connection to the master can be estab-

lished.
fit.0182PSL

For IEC 61850, an interoperable system so-

lution is offered with SICAM PAS. Via the

100 Mbits/s Ethernet bus, the units are Fig. 5/91

linked with PAS electrically or optically to Optical Ethernet communication module

the station PC. The interface is standard- for IEC 61850 with integrated Ethernet-switch

ized, thus also enabling direct connection

of units of other manufacturers to the

Ethernet bus. With IEC 61850, however,

the units can also be used in other manu-

facturers’ systems (see Fig. 5/89).

Siemens SIP · 2006 5/93


5 Overcurrent Protection / 7SJ62

Typical connections

Connection of current

and voltage transformers

Standard connection

For earthed networks, the earth current is

obtained from the phase currents by the

residual current circuit.

Fig. 5/92

Residual current

circuit without direc-

tional element

Fig. 5/93

Sensitive earth-

current detection

without directional

element

Fig. 5/94

Residual current

circuit with direc-

tional element

5/94 Siemens SIP · 2006


5 Overcurrent Protection / 7SJ62

Typical connections

Connection for compensated networks

The figure shows the connection of two

phase-to-earth voltages and the VE voltage

of the open delta winding and a phase-

balance neutral current transformer for the

earth current. This connection maintains

maximum precision for directional earth-

fault detection and must be used in com-

pensated networks.

Fig. 5/95 shows sensitive directional

earth-fault detection.

Fig. 5/95

Sensitive directional

earth-fault detection

with directional

element for phases


5

Fig. 5/96

Sensitive directional

earth-fault detection

Connection for isolated-neutral

or compensated networks only

If directional earth-fault protection is not

used, the connection can be made with

only two phase current transformers. Di-

rectional phase short-circuit protection

can be achieved by using only two primary

transformers.

Fig. 5/97

Isolated-neutral or

compensated

networks

Siemens SIP · 2006 5/95


5 Overcurrent Protection / 7SJ62

Typical applications

Overview of connection types

Type of network Function Current connection Voltage connection

(Low-resistance) earthed network Time-overcurrent protection Residual circuit, with 3 phase-current -

phase/earth non-directional transformers required, phase-balance

neutral current transformer possible

(Low-resistance) earthed networks Sensitive earth-fault protection Phase-balance neutral current -

transformers required

Isolated or compensated networks Time-overcurrent protection Residual circuit, with 3 or 2 phase -

phases non-directional current transformers possible

(Low-resistance) earthed networks Time-overcurrent protection Residual circuit, with 3 phase-current Phase-to-earth connection or

phases directional transformers possible phase-to-phase connection

Isolated or compensated networks Time-overcurrent protection Residual circuit, with 3 or 2 phase- Phase-to-earth connection or

phases directional current transformers possible phase-to-phase connection

(Low-resistance) earthed networks Time-overcurrent protection Residual circuit, with 3 phase-current Phase-to-earth connection required

earth directional transformers required, phase-balance

neutral current transformers possible


5
Isolated networks Sensitive earth-fault Residual circuit, if earth current 3 times phase-to-earth connection or

protection > 0.05 IN on secondary side, other- phase-to-earth connection with open

wise phase-balance neutral current delta winding

transformers required

Compensated networks Sensitive earth-fault protection Phase-balance neutral current Phase-to-earth connection with open

cos j measurement transformers required delta winding required

Connection of circuit-breaker

Undervoltage releases

Undervoltage releases are used for auto-

matic tripping of high-voltage motors.

Example:

DC supply voltage of control system fails

and manual electric tripping is no longer

possible.

Automatic tripping takes place when volt-

age across the coil drops below the trip

limit. In Fig. 5/98, tripping occurs due to

failure of DC supply voltage, by automatic

opening of the live status contact upon

failure of the protection unit or by

short-circuiting the trip coil in event of

network fault.

Fig. 5/98 Undervoltage release with make contact (50, 51)

5/96 Siemens SIP · 2006


5 Overcurrent Protection / 7SJ62

Typical applications

In Fig. 5/99 tripping is by failure of auxil-

iary voltage and by interruption of tripping

circuit in the event of network failure.

Upon failure of the protection unit, the

tripping circuit is also interrupted, since

contact held by internal logic drops back

into open position.

Trip circuit supervision (ANSI 74TC)

One or two binary inputs can be used for

monitoring the circuit-breaker trip coil in-

cluding its incoming cables. An alarm sig-

nal occurs whenever the circuit is

interrupted.

Lockout (ANSI 86)

All binary outputs can be stored like LEDs 5


Fig. 5/99 Undervoltage trip with locking contact (trip signal 50 is inverted)

and reset using the LED reset key. The

lockout state is also stored in the event of

supply voltage failure. Reclosure can only

occur after the lockout state is reset.

Fig. 5/100 Trip circuit supervision with 2 binary inputs

Fig. 5/101 Trip circuit supervision with 1 binary input

Siemens SIP · 2006 5/97


5 Overcurrent Protection / 7SJ62

Technical data

General unit data Binary outputs/command outputs

Measuring circuits Type 7SJ621 7SJ622

System frequency 50 / 60 Hz (settable) Command/indication relay 8 6

Current transformer Contacts per command/ 1 NO / form A

indication relay (Two contacts changeable to NC/form


Rated current Inom 1 or 5 A (settable)
B, via jumpers)
Option: sensitive earth-fault CT IEE < 1.6 A
Live status contact 1 NO / NC (jumper) / form A/B
Power consumption
Switching capacity
at Inom = 1 A Approx. 0.05 VA per phase
Make 1000 W / VA
at Inom = 5 A Approx. 0.3 VA per phase

for sensitive earth-fault CT at 1 A Approx. 0.05 VA Break 30 W / VA / 40 W resistive /

25 W at L/R £ 50 ms
Overload capability

Thermal (effective) 100 x Inom for 1 s Switching voltage £ 250 V DC

30 x Inom for 10 s
Permissible current 5 A continuous,
4 x Inom continuous
30 A for 0.5 s making current,
Dynamic (impulse current) 250 x Inom (half cycle)
2000 switching cycles

Overload capability if equipped with

sensitive earth-fault CT
5
Electrical tests
Thermal (effective) 300 A for 1 s

100 A for 10 s Specification

15 A continuous
Standards IEC 60255
Dynamic (impulse current) 750 A (half cycle)
ANSI C37.90, C37.90.1, C37.90.2,

Voltage transformer UL508

Rated voltage Vnom 100 V to 225 V Insulation tests

Power consumption at Vnom = 100 V < 0.3 VA per phase Standards IEC 60255-5; ANSI/IEEE C37.90.0

Overload capability in voltage path Voltage test (100 % test) 2.5 kV (r.m.s. value), 50/60 Hz

(phase-neutral voltage) all circuits except for auxiliary

Thermal (effective) 230 V continuous voltage and RS485/RS232 and

time synchronization
Auxiliary voltage

Auxiliary voltage 3.5 kV DC


Rated auxiliary DC 24/48 V 60/125 V 110/250 V

voltage Vaux AC 115/230 V Communication ports 500 V AC

and time synchronization


Permissible tolerance DC 19–58 V 48–150 V 88–300 V

AC 92-138 V 184–265 V Impulse voltage test (type test) 5 kV (peak value); 1.2/50 µs; 0.5 J

all circuits, except communication 3 positive and 3 negative impulses


Ripple voltage, £ 12 %
ports and time synchronization, at intervals of 5 s
peak-to-peak
class III
Power consumption
EMC tests for interference immunity; type tests
Quiescent Approx. 3–4 W

Energized Approx. 7–9 W Standards IEC 60255-6; IEC 60255-22

(product standard)
Backup time during ³ 50 ms at V ³ 110 V DC
EN 50082-2 (generic specification)
loss/short circuit of ³ 20 ms at V ³ 24 V DC
DIN 57435 Part 303
auxiliary voltage ³ 200 ms at 115 V/230 V AC

High-frequency test 2.5 kV (peak value); 1 MHz; t =15 ms;


Binary inputs/indication inputs

IEC 60255-22-1, class III 400 surges per s; test duration 2 s


Type 7SJ621 7SJ622
and VDE 0435 Part 303, class III

Number 8 11
Electrostatic discharge 8 kV contact discharge;

Voltage range 24–250 V DC IEC 60255-22-2 class IV 15 kV air gap discharge;

and EN 61000-4-2, class IV both polarities; 150 pF; Ri = 330 W


Pickup threshold modifiable by plug-in jumpers

Irradiation with radio-frequency 10 V/m; 27 to 500 MHz


Pickup threshold 19 V DC 88 V DC
field, non-modulated
For rated control voltage 24/48/60/ 110/125/
IEC 60255-22-3 (Report) class III
110/125 V 220/250 V DC
Irradiation with radio-frequency 10 V/m, 80 to 1000 MHz;
Response time/drop-out Approx. 3.5
field, amplitude-modulated AM 80 %; 1 kHz
time
IEC 61000-4-3; class III

Power consumption 1.8 mA (independent of operating voltage)


Irradiation with radio-frequency 10 V/m, 900 MHz; repetition
energized
field, pulse-modulated rate 200 Hz, on duration 50 %

IEC 61000-4-3/ENV 50204; class III

Fast transient interference/burst 4 kV; 5/50 ns; 5 kHz;

IEC 60255-22-4 and IEC 61000-4-4, burst length = 15 ms;

class IV repetition rate 300 ms; both polarities;

Ri = 50 W; test duration 1 min

5/98 Siemens SIP · 2006


5 Overcurrent Protection / 7SJ62

Technical data

High-energy surge voltages During transportation

(Surge)
Standards IEC 60255-21 and IEC 60068-2
IEC 61000-4-5; class III
Vibration Sinusoidal
Auxiliary voltage From circuit to circuit: 2 kV; 12 W; 9 µF
IEC 60255-21-1, class 2 5 to 8 Hz: ± 7.5 mm amplitude;
across contacts: 1 kV; 2 W ;18 µF
IEC 60068-2-6 8 to 150 Hz; 2 g acceleration,
Binary inputs/outputs From circuit to circuit: 2 kV; 42 W; 0.5 µF
frequency sweep 1 octave/min
across contacts: 1 kV; 42 W; 0.5 µF
20 cycles in 3 perpendicular axes

Line-conducted HF, 10 V; 150 kHz to 80 MHz;


Shock Semi-sinusoidal
amplitude-modulated AM 80 %; 1 kHz
IEC 60255-21-2, Class 1 Acceleration 15 g, duration 11 ms
IEC 61000-4-6, class III
IEC 60068-2-27 3 shocks in both directions of 3 axes

Power frequency magnetic field 30 A/m; 50 Hz, continuous


Continuous shock Semi-sinusoidal
IEC 61000-4-8, class IV 300 A/m; 50 Hz, 3 s
IEC 60255-21-2, class 1 Acceleration 10 g, duration 16 ms
IEC 60255-6 0.5 mT, 50 Hz
IEC 60068-2-29 1000 shocks in both directions

Oscillatory surge withstand 2.5 to 3 kV (peak value), 1 to 1.5 MHz of 3 axes

capability damped wave; 50 surges per s;

ANSI/IEEE C37.90.1 duration 2 s, Ri = 150 to 200 W


Climatic stress tests
Fast transient surge withstand 4 to 5 kV; 10/150 ns; 50 surges per s
Temperatures
capability ANSI/IEEE C37.90.1 both polarities; duration 2 s, Ri = 80 W
5
Type-tested acc. to IEC 60068-2-1 -25 °C to +85 °C /-13 °F to +185 °F
Radiated electromagnetic 35 V/m; 25 to 1000 MHz;
and -2, test Bd, for 16 h
interference amplitude and pulse-modulated

ANSI/IEEE C37.90.2 Temporarily permissible operating -20 °C to +70 °C /-4 °F to -158 °F

temperature, tested for 96 h


Damped wave 2.5 kV (peak value, polarity

IEC 60694 / IEC 61000-4-12 alternating) Recommended permanent operat- -5 °C to +55 °C /+25 °F to +131 °F

100 kHz, 1 MHz, 10 and 50 MHz, ing temperature acc. to IEC 60255-6

Ri = 200 W (Legibility of display may be im-

paired above +55 °C /+131 °F)


EMC tests for interference emission; type tests

– Limiting temperature during -25 °C to +55 °C /-13 °F to +131 °F


Standard EN 50081-* (generic specification)
permanent storage

Conducted interferences 150 kHz to 30 MHz – Limiting temperature during -25 °C to +70 °C /-13 °F to +158 °F

only auxiliary voltage IEC/CISPR Limit class B transport

22
Humidity

Radio interference field strength 30 to 1000 MHz


Permissible humidity Annual average 75 % relative humid-
IEC/CISPR 11 Limit class B
It is recommended to arrange the ity; on 56 days a year up to 95 % rela-

Units with a detached operator units in such a way that they are not tive humidity; condensation not

panel must be installed in a metal exposed to direct sunlight or permissible!

cubicle to maintain limit class B pronounced temperature changes

that could cause condensation.

Unit design
Mechanical stress tests

Housing 7XP20
Vibration, shock stress and seismic vibration

Dimensions See dimension drawings, part 16


During operation

Weight
Standards IEC 60255-21 and IEC 60068-2
Surface-mounting housing 4.5 kg
Vibration Sinusoidal
Flush-mounting housing 4.0 kg
IEC 60255-21-1, class 2 10 to 60 Hz; +/- 0.075 mm amplitude;
Degree of protection
IEC 60068-2-6 60 to 150 Hz; 1 g acceleration
acc. to EN 60529
frequency sweep 1 octave/min
Surface-mounting housing IP 51
20 cycles in 3 perpendicular axes
Flush-mounting housing Front: IP 51, rear: IP 20;
Shock Semi-sinusoidal
Operator safety IP 2x with cover
IEC 60255-21-2, class 1 Acceleration 5 g, duration 11 ms;

IEC 60068-2-27 3 shocks in both directions of 3 axes

Seismic vibration Sinusoidal

IEC 60255-21-3, class 1 1 to 8 Hz: ± 3.5 mm amplitude

IEC 60068-3-3 (horizontal axis)

1 to 8 Hz: ± 1.5 mm amplitude

(vertical axis)

8 to 35 Hz: 1 g acceleration

(horizontal axis)

8 to 35 Hz: 0.5 g acceleration

(vertical axis)

Frequency sweep 1 octave/min

1 cycle in 3 perpendicular axes

Siemens SIP · 2006 5/99


5 Overcurrent Protection / 7SJ62

Technical data

Serial interfaces Ethernet, electrical

Operating interface (front of unit)


Connection Two RJ45 connectors

Connection Non-isolated, RS232; front panel, For flush-mounting housing/ mounting location "B"

9-pin subminiature connector surface-mounting housing with

detached operator panel


Transmission rate min. 4800 baud, max. 38400 baud

Distance Max. 20 m / 65.6 ft


Service/modem interface (rear of unit)

Test voltage 500 V AC against earth


Isolated interface for data transfer Port C: DIGSI 4/modem/RTD-box

Ethernet, optical
Transmission rate Setting as supplied 38400 baud

min. 4800 baud, max. 38400 baud


Connection Intergr. ST connector for FO connec-

RS232/RS485 tion

For flush-mounting housing/ Mounting location "B"

Connection surface-mounting housing with

For flush-mounting housing/ 9-pin subminiature connector, detached operator panel

surface-mounting housing with mounting location “C” Optical wavelength 1300 nmm

detached operator panel Distance 1.5 km/0.9 miles

For surface-mounting housing At the bottom part of the housing:


PROFIBUS-FMS/DP
with two-tier terminal at the shielded data cable

5 top/bottom part Isolated interface for data transfer Port B

to a control center
Distance RS232 15 m /49.2 ft

Transmission rate Up to 1.5 Mbaud


Distance RS485 Max. 1 km/3300 ft

RS485
Test voltage 500 V AC against earth

System interface (rear of unit) Connection

For flush-mounting housing/ 9-pin subminiature connector,


IEC 60870-5-103 protocol
surface-mounting housing with mounting location “B”
Isolated interface for data transfer Port B detached operator panel

to a control center For surface-mounting housing At the bottom part of the housing:

with two-tier terminal on the shielded data cable


Transmission rate Setting as supplied: 9600 baud,
top/bottom part
min. 9600 baud, max. 19200 baud

Distance 1000 m/3300 ft £ 93.75 kbaud;


RS232/RS485
500 m/1500 ft £ 187.5 kbaud;

200 m/600 ft £ 1.5 Mbaud


Connection
100 m/300 ft £ 12 Mbaud
For flush-mounting housing/ Mounting location “B”

surface-mounting housing with Test voltage 500 V AC against earth

detached operator panel


Fiber optic
For surface-mounting housing At the bottom part of the housing:

with two-tier terminal on the shielded data cable Connection fiber-optic cable Integr. ST connector for FO connec-

top/bottom part tion

Distance RS232 Max. 15 m/49 ft For flush-mounting housing/ Mounting location “B”

surface-mounting housing with


Distance RS485 Max. 1 km/3300 ft
detached operator panel
Test voltage 500 V AC against earth
For surface-mounting housing At the bottom part of the housing
Fiber optic
with two-tier terminal on the Important: Please refer to footnotes
1) 2)
top/bottom part and on page 5/112
Connection fiber-optic cable Integrated ST connector for fi-

ber-optic connection Optical wavelength 820 nm

For flush-mounting housing/ Mounting location “B” Permissible path attenuation Max. 8 dB, for glass fiber 62.5/125 µm

surface-mounting housing with


Distance 500 kB/s 1.6 km/0.99 miles
detached operator panel
1500 kB/s 530 m/0.33 miles

For surface-mounting housing At the bottom part of the housing


MODBUS RTU, ASCII, DNP 3.0

with two-tier terminal on the


Isolated interface for data transfer Port B
top/bottom part
to a control center
Optical wavelength 820 nm

Transmission rate Up to 19200 baud


Permissible path attenuation Max. 8 dB, for glass fiber 62.5/125 µm

RS485
Distance Max. 1.5 km/0.9 miles

IEC 61850 protocol


Connection

For flush-mounting housing/ 9-pin subminiature connector,


Isolated interface for data transfer: Port B, 100 Base T acc. to IEEE802.3
surface-mounting housing with mounting location “B”
- to a control center
detached operator panel
- with DIGSI
For surface-mounting housing At bottom part of the housing:
- between SIPROTEC 4 relays
with two-tier terminal at the shielded data cable
Transmission rate 100 Mbit
top/bottom part

Test voltage 500 V AC against earth

5/100 Siemens SIP · 2006


5 Overcurrent Protection / 7SJ62

Technical data

Fiber-optic Trip characteristics

IEC Normal inverse, very inverse,


Connection fiber-optic cable Integrated ST connector for fiber-optic
extremely inverse, long inverse
connection
ANSI Inverse, short inverse, long inverse
For flush-mounting housing/ Mounting location “B”
moderately inverse, very inverse,
surface-mounting housing with
extremely inverse, definite inverse
detached operator panel
User-defined characteristic Defined by a maximum of 20 value
For surface-mounting housing At the bottom part of the housing
pairs of current and time delay
with two-tier terminal at the Important: Please refer to footnotes
1) 2)
Dropout setting
top/bottom part and on page 5/112
Without disk emulation Approx. 1.05 · setting value Ip for
Optical wavelength 820 nm
Ip/Inom ³ 0.3, corresponds to approx.

Permissible path attenuation Max 8 dB. for glass fiber 62.5/125 µm 0.95 · pickup threshold

With disk emulation Approx. 0.90 · setting value Ip


Distance Max. 1.5 km/0.9 miles

Tolerances
Time synchronization DCF77/IRIG-B signal (Format IRIG-B000)
1)
Pickup/dropout thresholds Ip, IEp 2 % of setting value or 50 mA
Connection 9-pin subminiature connector
Pickup time for 2 £ I/Ip £ 20 5 % of reference (calculated) value
(SUB-D)
+ 2 % current tolerance, respectively
(terminal with surface-mounting
30 ms
housing)
Dropout ratio for 0.05 £ I/Ip 5 % of reference (calculated) value
5
Voltage levels 5 V, 12 V or 24 V (optional) £ 0.9 + 2 % current tolerance, respectively

30 ms

Direction detection
Functions

For phase faults


Definite-time overcurrent protection, directional/non-directional

(ANSI 50, 50N, 67, 67N) Polarization With cross-polarized voltages;

With voltage memory for measure-


Operating mode non-directional 3-phase (standard) or 2-phase
ment voltages that are too low
phase protection (ANSI 50) (L1 and L3)

Forward range Vref,rot ± 86°


Setting ranges
Rotation of reference voltage Vref,rot - 180° to 180° (in steps of 1°)
1)
Pickup phase elements I>, I>> 0.5 to 175 A or ¥ (in steps of 0.01 A)
1)
Direction sensitivity For one and two-phase faults unlim-
Pickup earth elements IE>, IE>> 0.25 to 175 A or ¥ (in steps of 0.01 A)
ited;
Delay times T 0 to 60 s or ¥ (in steps of 0.01 s)
For three-phase faults dynamically
Dropout delay time TDO 0 to 60 s (in steps of 0.01 s)
unlimited;

Times Steady-state approx. 7 V

Pickup times (without inrush phase-to-phase

restraint, with inrush restraint


For earth faults
+ 10 ms)

Polarization With zero-sequence quantities 3V0, 3I0


Non-directional Directional
or with negative-sequence quantities
With twice the setting value Approx. 30 ms 45 ms
3V2, 3I2
With five times the setting value Approx. 20 ms 40 ms

Forward range Vref,rot ± 86°


Dropout times Approx. 40 ms
Rotation of reference voltage Vref,rot - 180° to 180° (in steps of 1°)
Dropout ratio Approx. 0.95 for
Direction sensitivity
I/Inom ³ 0.3
Zero-sequence quantities 3V0, 3I0 VE » 2.5 V displacement voltage,
Tolerances
measured;
1)
Pickup 2 % of setting value or 50 mA
3V0 » 5 V displacement voltage,
Delay times T, TDO 1 % or 10 ms
calculated

Inverse-time overcurrent protection, directional/non-directional Negative -sequence quantities 3V2 » 5 V negative-sequence voltage;

(ANSI 51, 51N, 67, 67N) 3V2, 3I2 3I2 » 225 mA negative-sequence cur-
1)
rent
Operating mode non-directional 3-phase (standard) or 2-phase

phase protection (ANSI 51) (L1 and L3) Tolerances (phase angle error under

reference conditions)
Setting ranges
1) For phase and earth faults ± 3 ° electrical
Pickup phase element IP 0.5 to 20 A or ¥ (in steps of 0.01 A)
1)
Pickup earth element IEP 0.25 to 20 A or ¥ (in steps of 0.01 A) Inrush blocking

Time multiplier T 0.05 to 3.2 s or ¥ (in steps of 0.01 s)


Influenced functions Time-overcurrent elements, I>, IE>,
(IEC characteristics)
Ip, IEp (directional, non-directional)
Time multiplier D 0.05 to 15 s or ¥ (in steps of 0.01 s)
1)
Lower function limit 1.25 A
(ANSI characteristics)
1)
Upper function limit (setting range) 1.5 to 125 A (in steps of 0.01 A)

Setting range I2f /I 10 to 45 % (in steps of 1 %)

Crossblock (IL1, IL2, IL3) ON/OFF

1) At Inom = 1 A, all limits divided by 5.

Siemens SIP · 2006 5/101


5 Overcurrent Protection / 7SJ62

Technical data

Dynamic setting change Earth-fault pickup for all types of earth faults

Controllable function Directional and non-directional Inverse-time characteristic (ANSI 51Ns)

pickup, tripping time


User-defined characteristic Defined by a maximum of 20 pairs of

Start criteria Current criteria, current and delay time values

CB position via aux. contacts,


Logarithmic inverse I
binary input, t = T - TIEEp × ln
IEEpmax

I
EEp
auto-reclosure ready

Time control 3 timers Setting ranges

Pickup threshold IEEp


Current criteria Current threshold
For sensitive input 0.001 A to 1.4 A (in steps of 0.001 A)
(reset on dropping below threshold; 1)
For normal input 0.25 to 20 A (in steps of 0.01 A)
monitoring with timer)
User defined

(Sensitive) earth-fault detection (ANSI 64, 50 Ns, 51Ns, 67Ns) Time multiplier T 0.1 to 4 s or ¥ (in steps of 0.01 s)

Logarithmic inverse
Displacement voltage starting for all types of earth fault (ANSI 64)

Time multiplier TIEEp mul 0.05 to 15 s or ¥ (in steps of 0.01 s)


Setting ranges
Delay time TIEEp 0.1 to 4 s or ¥ (in steps of 0.01 s)
Pickup threshold VE> (measured) 1.8 to 170 V (in steps of 0.1 V)
Min time delay TIEEpmin 0 to 32 s (in steps of 0.01 s)
Pickup threshold 3V0> (calcu- 10 to 225 V (in steps of 0.1 V)
Max. time delay TIEEpmax 0 to 32 s (in steps of 0.01 s)
lated)
5 Delay time TDelay pickup 0.04 to 320 s or ¥ (in steps of 0.01 s)
Times

Pickup times Approx. 60 ms (non-directional)


Additional trip delay TVDELAY 0.1 to 40000 s or ¥ (in steps of 0.01 s)
Approx 80 ms (directional)
Times
Pickup threshold Approx. 1.1 · IEEp
Pickup time Approx. 60 ms

Dropout ratio Approx. 1.05 · IEEp


Dropout ratio 0.95 or (pickup value -0.6 V)

Tolerances
Tolerances
Pickup threshold IEEp 2 % of setting value or 1 mA
Pickup threshold VE (measured) 3 % of setting value or 0.3 V
Delay times in linear range 7 % of reference value for 2 £ I/IEEp
Pickup threshold 3V0 (calculated) 3 % of setting value or 3 V
£ 20 + 2 % current tolerance, or 70 ms
Delay times 1 % of setting value or 10 ms

Direction detection for all types of earth-faults (ANSI 67Ns)


Phase detection for earth fault in an unearthed system

Direction measurement IE and VE measured or


Measuring principle Voltage measurement (phase-to-earth)
3I0 and 3V0 calculated

Setting ranges
Measuring principle Active/reactive power measurement
Vph min (earth-fault phase) 10 to 100 V (in steps of 1 V)

Setting ranges
Vph max (unfaulted phases) 10 to 100 V (in steps of 1 V)
Measuring enable IRelease direct.

Measuring tolerance 3 % of setting value, or 1 V For sensitive input 0.001 to 1.2 A (in steps of 0.001 A)
1)
acc. to DIN 57435 part 303 For normal input 0.25 to 150 A (in steps of 0.01 A)

Measuring method cos j and sin j


Earth-fault pickup for all types of earth faults

Direction phasor jCorrection - 45 ° to + 45 ° (in steps of 0.1 °)


Definite-time characteristic (ANSI 50Ns)
Dropout delay TReset delay 1 to 60 s (in steps of 1 s)

Setting ranges Angle correction for cable CT

Pickup threshold IEE>, IEE>> Angle correction F1, F2 0 ° to 5 ° (in steps of 0.1 °)

For sensitive input 0.001 to 1.5 A (in steps of 0.001 A) Current value I1, I2
1)
For normal input 0.25 to 175 A (in steps of 0.01 A) For sensitive input 0.001 to 1.5 A (in steps of 0.001 A)
1)
Delay times T for IEE>, IEE>> 0 to 320 s or ¥ (in steps of 0.01 s) For normal input 0.25 to 175 A (in steps of 0.01 A)

Dropout delay time TDO 0 to 60 s (in steps of 0.01 s)


Tolerances

Times Pickup measuring enable 2 % of the setting value or 1 mA

Pickup times Approx. 60 ms (non-directional) Angle tolerance 3 °

Approx. 80 ms (directional
Note: Due to the high sensitivity the linear range of the measuring input IN

Dropout ratio Approx. 0.95 with integrated sensitive input transformer is from 0.001 A to 1.6 A. For cur-

rents greater than 1.6 A, correct directionality can no longer be guaranteed.


Tolerances

Pickup threshold IEE>, IEE>> 2 % of setting value or 1 mA

Delay times 1 % of setting value or 20 ms

1) For Inom = 1 A, all limits divided by 5.

5/102 Siemens SIP · 2006


5 Overcurrent Protection / 7SJ62

Technical data

High-impedance restricted earth-fault protection (ANSI 87N) / single-phase Thermal overload protection (ANSI 49)

overcurrent protection
Setting ranges

Setting ranges
Factor k 0.1 to 4 (in steps of 0.01)
Pickup thresholds I>, I>>
Time constant 1 to 999.9 min (in steps of 0.1 min)
For sensitive input 0.003 to 1.5 A or ¥ (in steps of 0.001 A)
1)
For normal input 0.25 to 175 A or ¥ (in steps of 0.01 A) Warning overtemperature 50 to 100 % with reference

Delay times TI>, TI>> 0 to 60 s or ¥ (in steps of 0.01 s) Qalarm/Qtrip to the tripping overtemperature

(in steps of 1 %)
Times

Pickup times Current warning stage Ialarm 0.5 to 20 A (in steps of 0.01 A)

Minimum Approx. 20 ms
Extension factor when stopped 1 to 10 with reference to the time con-
Typical Approx. 30 ms
kt factor stant with the machine running
Dropout times Approx. 30 ms
(in steps of 0.1)

Dropout ratio Approx. 0.95 for I/Inom ³ 0.5


Rated overtemperature (for Inom) 40 to 200 °C (in steps of 1 °C)

Tolerances
2 2
Tripping characteristic
Pickup thresholds 3 % of setting value or (I /k ×I
nom ) - (I pre / k × I nom )
For (I/k · Inom) £ 8 t = t th × ln
2
1 % rated current at Inom = 1 or 5 A;
(I / k ×I
nom ) -1
5 % of setting value or

3 % rated current at Inom = 0.1 A t = Tripping time

Delay times 1 % of setting value or 10 ms tth = Temperature rise time constant 5


I = Load current
Intermittent earth-fault protection
Ipre = Preload current
Setting ranges
k = Setting factor acc. to VDE 0435

Pickup threshold Part 3011 and IEC 60255-8


1)
For IE IIE> 0.25 to 175 A (in steps of 0.01 A) Inom = Rated (nominal) current of the
1)
For 3I0 IIE> 0.25 to 175 A (in steps of 0.01 A) protection relay

For IEE IIE> 0.005 to 1.5 A (in steps of 0.001 A)


Dropout ratios

Pickup prolon- TV 0 to 10 s (in steps of 0.01 s) Q/QTrip Drops out with QAlarm

gation time Q/QAlarm Approx. 0.99

I/IAlarm Approx. 0.97


Earth-fault accu- Tsum 0 to 100 s (in steps of 0.01 s)

mulation time Tolerances

With reference to k · Inom Class 5 acc. to IEC 60255-8


Reset time for Tres 1 to 600 s (in steps of 1 s)
With reference to tripping time 5 % +/- 2 s acc. to IEC 60255-8
accumulation

Auto-reclosure (ANSI 79)


Number of pickups for 2 to 10 (in steps of 1)

intermittent earth fault


Number of reclosures 0 to 9

Times Shot 1 to 4 individually adjustable

Pickup times
Program for phase fault
Current = 1.25 · pickup value Approx. 30 ms
Start-up by Time-overcurrent elements (dir.,
Current ³ 2 · pickup value Approx. 22 ms
non-dir.), negative sequence, binary

Dropout time Approx. 22 ms input

Tolerances Program for earth fault


1)
Pickup threshold IIE> 3 % of setting value, or 50 mA Start-up by Time-overcurrent elements

(dir., non-dir.), sensitive earth-fault


Times TV, Tsum, Tres 1 % of setting value or 10 ms
protection, binary input

Blocking of ARC Pickup of protection functions,

three-phase fault detected by a protec-

tive element, binary input,

last TRIP command after the reclosing

cycle is complete (unsuccessful

reclosing),

TRIP command by the breaker failure

protection (50BF),

opening the CB without ARC initiation,

external CLOSE command

1) For Inom = 1 A, all limits divided by 5.

Siemens SIP · 2006 5/103


5 Overcurrent Protection / 7SJ62

Technical data

Auto-reclosure (cont'd) Negative-sequence current detection (ANSI 46)

Setting ranges Definite-time characteristic (ANSI 46-1 and 46-2)

Dead time 0.01 to 320 s (in steps of 0.01 s)


Setting ranges
(separate for phase and earth
Pickup current I2>, I2>> 0.5 to 15 A or ¥ (in steps of 0.01 A)
and individual for shots 1 to 4)
Delay times 0 to 60 s or ¥ (in steps of 0.01 s)

Blocking duration for manual- 0.5 s to 320 s or 0 (in steps of 0.01 s) Dropout delay time TDO 0 to 60 s (in steps of 0.01 s)

CLOSE detection 1)
Functional limit All phase currents £ 20 A
Blocking duration after 0.5 s to 320 s (in steps of 0.01 s)
Times
reclosure
Pickup times Approx. 35 ms
Blocking duration after 0.01 to 320 s (in steps of 0.01 s)
Dropout times Approx. 35 ms
dynamic blocking
Dropout ratio Approx. 0.95 for I2 /Inom > 0.3
Start-signal monitoring time 0.01 to 320 s or ¥ (in steps of 0.01 s)
Tolerances
Circuit-breaker supervision 0.1 to 320 s (in steps of 0.01 s) 1)
Pickup thresholds 3 % of the setting value or 50 mA
time
Delay times 1 % or 10 ms

Max. delay of dead-time start 0 to 1800 s or ¥ (in steps of 0.1 s)


Inverse-time characteristic (ANSI 46-TOC)

Maximum dead time extension 0.5 to 320 s or ¥(in steps of 0.01 s)


Setting ranges
1)
Action time 0.01 to 320 s or ¥ (in steps of 0.01 s) Pickup current 0.5 to 10 A (in steps of 0.01 A)
5 Time multiplier T 0.05 to 3.2 s or ¥ (in steps of 0.01 s)
The delay times of the following protection function can be altered individ-
(IEC characteristics)
ually by the ARC for shots 1 to 4
Time multiplier D 0.5 to 15 s or ¥ (in steps of 0.01 s)
(setting value T = T, non-delayed T = 0, blocking T = ¥):
(ANSI characteristics)
I>>, I>, Ip, Idir>>, Idir>, Ipdir
1)
IE>>, IE>, IEp, IEdir>>, IEdir>, IEdir Functional limit All phase currents £ 20 A

Additional functions Lockout (final trip), Trip characteristics

delay of dead-time start via binary input IEC Normal inverse, very inverse, extremely

(monitored), inverse

dead-time extension via binary input ANSI Inverse, moderately inverse, very in-

(monitored), verse, extremely inverse

co-ordination with other protection


Pickup threshold Approx. 1.1 · I2p setting value
relays,
Dropout
circuit-breaker monitoring,
IEC and ANSI Approx. 1.05 · I2p setting value,
evaluation of the CB contacts
(without disk emulation) which is approx. 0.95 · pickup threshold
Breaker failure protection (ANSI 50 BF)
ANSI with disk emulation Approx. 0.90 · I2p setting value

Setting ranges
Tolerances
1)
Pickup threshold CB I> 0.2 to 5 A (in steps of 0.01 A) 1)
Pickup threshold 3 % of the setting value or 50 mA

Delay time 0.06 to 60 s or ¥ (in steps of 0.01 s) Time for 2 £ M £ 20 5 % of setpoint (calculated)

+2 % current tolerance, at least 30 ms


Times

Pickup times Starting time monitoring for motors (ANSI 48)

with internal start is contained in the delay time


Setting ranges
start via control is contained in the delay time 1)
Motor starting current ISTARTUP 2.5 to 80 A (in steps of 0.01)
with external start is contained in the delay time 1)
Pickup threshold IMOTOR START 2 to 50 A (in steps of 0.01)
Dropout times Approx. 25 ms
Permissible starting 1 to 180 s (in steps of 0.1 s)

Tolerances time TSTARTUP


1)
Pickup value 2 % of setting value (50 mA) Permissible blocked rotor 0.5 to 120 s or ¥ (in steps of 0.1 s)
time TLOCKED-ROTOR
Delay time 1 % or 20 ms

Tripping time characteristic


2

æ I STARTUP ö
For I > IMOTOR START t = ç ÷ × TSTARTUP
è I ø

ISTARTUP = Rated motor starting

current

I = Actual current flowing

TSTARTUP = Tripping time for rated

motor starting current

t = Tripping time in seconds

Dropout ratio IMOTOR START Approx. 0.95

Tolerances
1)
Pickup threshold 2 % of setting value or 50 mA

Delay time 5 % or 30 ms

1) At Inom = 1 A, all limits divided by 5.

5/104 Siemens SIP · 2006


5 Overcurrent Protection / 7SJ62

Technical data

Restart inhibit for motors (ANSI 66) Undervoltage protection (ANSI 27)

Setting ranges Operating modes/measuring

quantities
Motor starting current relative 1.1 to 10 (in steps of 0.1)

to rated motor current 3-phase Positive-sequence component or

IMOTOR START/IMotor Nom smallest of the phase-to-phase voltages


1)
Rated motor current IMotor Nom 1 to 6 A (in steps of 0.01 A) 1-phase Single-phase phase-earth or

Max. permissible starting time 3 to 320 s (in steps of 1 s) phase-phase voltage

TStart Max
Setting ranges
Equilibrium time TEqual 0 min to 320 min (in steps of 0.1 min)
Pickup thresholds V<, V<<
Minimum inhibit time 0.2 min to 120 min (in steps of 0.1 min)
3-phase, phase-earth connec- 10 to 210 V (in steps of 1 V)
TMIN. INHIBIT TIME
tion
Max. permissible number of 1 to 4 (in steps of 1)
3-phase, phase-phase connec- 10 to 120 V (in steps of 1 V)
warm starts
tion
Difference between cold and 1 to 2 (in steps of 1)
1-phase connection 10 to 120 V (in steps of 1 V)
warm starts
Dropout ratio r 1.01 to 3 (in steps of 0.01)
Extension k-factor for cooling 0.2 to 100 (in steps of 0.1)
Delay times T 0 to 100 s or ¥ (in steps of 0.01 s)
simulations of rotor at zero speed
1)
Current Criteria "Bkr Closed 0.2 to 5 A (in steps of 0.01 A)
kt at STOP
IMIN"
Extension factor for cooling time 0.2 to 100 (in steps of 0.1)
5
constant with motor running Dropout threshold r ·V<(<) Max. 130 V for phase-phase voltages

kt RUNNING Max. 225 V phase-earth voltages

Restarting limit Times


n -1
c Pickup times V<, V<<, V1<, V1<< Approx. 50 ms
Q restart = Q rot max perm ×
n Dropout times As pickup times
c

Tolerances
Qrestart = Temperature limit below
Pickup thresholds 3 % of setting value or 1 V
which restarting is possi-
Times 1 % of setting value or 10 ms
ble

Qrot max perm = Maximum permissible Overvoltage protection (ANSI 59)

rotor overtemperature
Operating modes/measuring
(= 100 % in operational
quantities
measured value
3-phase Negative-sequence component or
Qrot/Qrot trip)
largest of the phase-to-phase voltages
nc = Number of permissible
1-phase Single-phase phase-earth or
start-ups from cold state
phase-phase voltage
Undercurrent monitoring (ANSI 37)
Setting ranges
Signal from the operational Predefined with programmable logic
Pickup thresholds V>, V>>
measured values
3-phase, phase-earth connec- 40 to 260 V (in steps of 1 V)

Temperature monitoring box (ANSI 38) tion, largest phase-phase

voltage
Temperature detectors
3-phase, phase-phase connec- 40 to 150 V (in steps of 1 V)

Connectable boxes 1 or 2 tion, largest phase-phase

Number of temperature Max. 6 voltage

detectors per box 3-phase, negative-sequence 2 to 150 V (in steps of 1 V)

Type of measuring Pt 100 W or Ni 100 W or Ni 120 W voltage

Mounting identification “Oil” or “Environment” or “Stator” or 1-phase connection 40 to 150 V (in steps of 1 V)

“Bearing” or “Other”
Dropout ratio r 0.9 to 0.99 (in steps of 0.01)

Thresholds for indications Delay times T 0 to 100 s or ¥ (in steps of 0.01 s)

For each measuring detector


Times
Stage 1 -50 °C to 250 °C (in steps of 1 °C)
Pickup times V>, V>> Approx. 50 ms
-58 °F to 482 °F (in steps of 1 °F)
Pickup times V2>, V2>> Approx. 60 ms
or ¥ (no indication)
Dropout times As pickup times
Stage 2 -50 °C to 250 °C (in steps of 1 °C)
Tolerances
-58 °F to 482 °F (in steps of 1 °F)
Pickup thresholds 3 % of setting value or 1 V
or ¥ (no indication)
Times 1 % of setting value or 10 ms

1) At Inom = 1 A, all limits divided by 5.

Siemens SIP · 2006 5/105


5 Overcurrent Protection / 7SJ62

Technical data

Frequency protection (ANSI 81) Additional functions

Number of frequency elements 4 Operational measured values

Setting ranges Currents In A (kA) primary, in A secondary or in % Inom

Pickup thresholds for fnom = 50 Hz 45.5 to 54.5 Hz (in steps of 0.01 Hz) IL1, IL2, IL3

Pickup thresholds for fnom = 60 Hz 55.5 to 64.5 Hz (in steps of 0.01 Hz) Positive-sequence component I1

Delay times 0 to 100 s or ¥ (in steps of 0.01 s) Negative-sequence component I2

Undervoltage blocking, with 10 to 150 V (in steps of 1 V) IE or 3I0

positive-sequence voltage V1
Range 10 to 200 % Inom
2)
Times Tolerance 1 % of measured value or 0.5 % Inom

Pickup times Approx. 150 ms


Phase-to-earth voltages In kV primary, in V secondary or in % Vnom
Dropout times Approx. 150 ms
VL1-E, VL2-E, VL3-E

Dropout Phase-to-phase voltages

Df = pickup value - dropout value Approx. 20 mHz VL1-L2, VL2-L3, VL3-L1, VE or V0

Ratio undervoltage blocking Approx. 1.05 Positive-sequence component V1

Negative-sequence component V2
Tolerances

Pickup thresholds Range 10 to 120 % Vnom


2)
Frequency 10 mHz Tolerance 1 % of measured value or 0.5 % of Vnom

Undervoltage blocking 3 % of setting value or 1 V


5 S, apparent power In kVAr (MVAr or GVAr) primary and
Delay times 3 % of the setting value or 10 ms
in % of Snom

Fault locator (ANSI 21FL)


Range 0 to 120 % Snom
2)
Output of the fault distance In W secondary, Tolerance 1 % of Snom

in km / mile of line length for V/Vnom and I/Inom = 50 to 120 %

Starting signal Trip command, dropout of a protec- P, active Power With sign, total and phase-segregated in

tion element, via binary input kW (MW or GW) primary and in % Snom

Setting ranges Range 0 to 120 % Snom


1) 2)
Reactance (secondary) 0.001 to 1.9 W/km (in steps of 0.0001) Tolerance 2 % of Snom
1)
0.001 to 3 W/mile (in steps of 0.0001) for V/Vnom and I/Inom = 50 to 120 %

and ½cos j½ = 0.707 to 1 with


Tolerances
Snom = 3 ×V × I nom
Measurement tolerance acc. to 2.5 % fault location, or 0.025 W nom

VDE 0435, Part 303 for sinusoi- (without intermediate infeed) for Q, reactive power With sign, total and phase-segregated

dal measurement quantities 30 ° £ jK £ 90 ° and VK/Vnom ³ 0.1 in kVAr (MVAr or GVAr)primary and

and IK/Inom ³ 1 in % Snom

Range 0 to 120 % Snom


2)
Tolerance 2 % of Snom

for V/Vnom and I/Inom = 50 to 120 %

and ½sin j½ = 0.707 to 1 with

Snom = 3 ×V × I nom
nom

cos j, power factor (p.f.) Total and phase segregated

Range - 1 to + 1
2)
Tolerance 3 % for ½cos j½ ³ 0.707

Frequency f In Hz

Range fnom ± 5 Hz
2)
Tolerance 20 mHz

Temperature overload protection In %

Q/QTrip

Range 0 to 400 %
2)
Tolerance 5 % class accuracy per IEC 60255-8

Temperature restart inhibit In %

QL/QL Trip

Range 0 to 400 %
2)
Tolerance 5 % class accuracy per IEC 60255-8

Restart threshold QRestart/QL Trip In %

Reclose time TReclose In min

Currents of sensitive ground fault In A (kA) primary and in mA second-

detection (total, real, and reactive ary

current) IEE, IEE real, IEE reactive

Range 0 mA to 1600 mA
2)
Tolerance 2 % of measured value or 1 mA

RTD-box See section "Temperature monitoring

box"
1) At Inom = 1 A, all limits multiplied with 5.

2) At rated frequency.

5/106 Siemens SIP · 2006


5 Overcurrent Protection / 7SJ62

Technical data

Long-term averages Time stamping

Time window 5, 15, 30 or 60 minuets Resolution for event log (opera- 1 ms

tional annunciations)
Frequency of updates Adjustable

Resolution for trip log (fault 1 ms


Long-term averages
annunciations)
of currents IL1dmd, IL2dmd, IL3dmd, I1dmd in A (kA)

of real power Pdmd in W (kW, MW) Maximum time deviation (internal 0.01 %

of reactive power Qdmd in VAr (kVAr, MVAr) clock)

of apparent power Sdmd in VAr (kVAr, MVAr)


Battery Lithium battery 3 V/1 Ah,

Max. / Min. report type CR 1/2 AA, message "Battery

Fault" for insufficient battery charge


Report of measured values With date and time

Oscillographic fault recording


Reset, automatic Time of day adjustable (in minutes,

0 to 1439 min) Maximum 8 fault records saved,

Time frame and starting time adjust- memory maintained by buffer bat-

able (in days, 1 to 365 days, and ¥) tery in case of loss of power supply

Reset, manual Using binary input, Recording time Total 5 s

using keypad, Pre-trigger and post-fault recording

via communication and memory time adjustable


5
Min./Max. values for current IL1, IL2, IL3, Sampling rate for 50 Hz 1 sample/1.25 ms (16 sam/cyc)

I1 (positive-sequence component) Sampling rate for 60 Hz 1 sample/1.04 ms (16 sam/cyc)

Min./Max. values for voltages VL1-E, VL2-E, VL3-E Energy/power

V1 (positive-sequence component)
Meter values for power in kWh (MWh or GWh) and kVARh
VL1-L2, VL2-L3, VL3-L1
Wp, Wq (real and reactive power (MVARh or GVARh)

Min./Max. values for power S, P, Q, cos j, frequency demand)

1)
Min./Max. values for overload pro- Q/QTrip Tolerance £ 5 % for I > 0.5 Inom, V > 0.5 Vnom

tection and ½cos j½ (p.f.) ³ 0.707

Min./Max. values for mean values IL1dmd, IL2dmd, IL3dmd Statistics

I1 (positive-sequence component);
Saved number of trips Up to 9 digits
Sdmd, Pdmd, Qdmd
Number of automatic reclosing Up to 9 digits
Local measured values monitoring
commands (segregated according
st nd
Current asymmetry Imax/Imin > balance factor, to 1 and ³ 2 cycle)

for I>Ibalance limit


Circuit-breaker wear

Voltage asymmetry Vmax/Vmin > balance factor, x


Methods · SI with x = 1 .. 3
for V>Vlim
· 2-point method (remaining service

Current sum |iL1 + iL2 + iL3 + kiE × iE| > limit value, life)

with
Operation Phase-selective accumulation of mea-

I CT PRIM / I CT SEC sured values on TRIP command, up to


earth earth
k =
iE

CT PRIM / CT SEC 8 digits, phase-selective limit values,

monitoring indication
Current phase sequence Clockwise (ABC) / counter-clockwise
Operating hours counter
(ACB)

Display range Up to 7 digits


Voltage phase sequence Clockwise (ABC) / counter-clockwise

(ACB) Criterion Overshoot of an adjustable current

threshold (BkrClosed IMIN)


Limit value monitoring Predefined limit values, user-defined

expansions via CFC Trip circuit monitoring

Fault recording
With one or two binary inputs

Recording of indications of the last Commissioning aids

8 power system faults


Phase rotation field check,

Recording of indications of the last operational measured values,

3 power system ground faults circuit-breaker / switching device

test,

creation of a test measurement re-

port

1) At rated frequency.

Siemens SIP · 2006 5/107


5 Overcurrent Protection / 7SJ62

Technical data

Clock

Time synchronization DCF77/IRIG-B signal (telegram for-

mat IRIG-B000),

binary input,

communication

Setting group switchover of the function parameters

Number of available setting groups 4 (parameter group A, B, C and D)

Switchover performed Via keypad, DIGSI, system (SCADA)

interface or binary input

Control

Number of switching units Depends on the binary inputs and

outputs

Interlocking Programmable

Circuit-breaker signals Feedback, close, open, intermediate

position

5 Control commands Single command / double command

1, 1 plus 1 common or 2 trip contacts

Programmable controller CFC logic, graphic input tool

Local control Control via menu,

assignment of a function key

Remote control Via communication interfaces,

using a substation automation and

control system

(e.g. SICAM),

DIGSI 4 (e.g. via modem)

CE conformity

This product is in conformity with the Directives of the European Commu-

nities on the harmonization of the laws of the Member States relating to

electromagnetic compatibility (EMC Council Directive 89/336/EEC) and

electrical equipment designed for use within certain voltage limits (Council

Directive 73/23/EEC).

This unit conforms to the international standard IEC 60255, and the Ger-

man standard DIN 57435/Part 303 (corresponding to VDE 0435/Part 303).

Further applicable standards: ANSI/IEEE C37.90.0 and C37.90.1.

The unit conforms to the international standard IEC 60255, and the Ger-

man standard DIN 57435/Part 303 (corresponding to VDE 0435/Part 303).

This conformity is the result of a test that was performed by Siemens AG in

accordance with Article 10 of the Council Directive complying with the

generic standards EN 50081-2 and EN 50082-2 for the EMC Directive and

standard EN 60255-6 for the “low-voltage Directive”.

5/108 Siemens SIP · 2006


5 Overcurrent Protection / 7SJ62

Selection and ordering data Description Order No.

7SJ62 multifunction protection relay 7SJ62 – –

Housing, binary inputs (BI) and outputs (BO)

Housing 1/3 19"; 8 BI, 8 BO, 1 live status contact 1

Housing 1/3 19"; 11 BI, 6 BO, 1 live status contact 2

see

Measuring inputs (3 x V, 4 x I) next


1) 1)
Iph = 1 A , Ie = 1 A (min. = 0.05 A) page

Position 15 only with A, C, E, G 1

1)
Iph = 1 A , Ie = sensitive (min. = 0.001 A)

Position 15 only with B, D, F, H 2

1) 1)
Iph = 5 A , Ie = 5 A (min. = 0.25 A)

Position 15 only with A, C, E, G 5

1)
Iph = 5 A , Ie = sensitive (min. = 0.001 A)

Position 15 only with B, D, F, H 6

1) 1)
Iph = 5 A , Ie = 1 A (min. = 0.05 A)

Position 15 only with A, C, E, G 7

Rated auxiliary voltage (power supply, indication voltage)

3)
24 to 48 V DC, threshold binary input 19 DC 2 5
2) 3)
60 to 125 V DC , threshold binary input 19 DC 4

2) 4) 3)
110 to 250 V DC , 115 to 230 V AC, threshold binary input 88 V DC 5

Unit version

For panel surface mounting, two-tier terminal top/bottom B

For panel flush mounting, plug-in terminal, (2/3 pin connector) D

For panel flush mounting, screw-type terminal (direct connection/ring-type cable lugs) E

Region-specific default settings/function versions and language settings

Region DE, 50 Hz, IEC, language: German, selectable A

Region World, 50/60 Hz, IEC/ANSI, language: English (GB), selectable B

Region US, 60 Hz, ANSI, language: English (US), selectable C

Region FR, 50/60 Hz, IEC/ANSI, language: French, selectable D

Region World, 50/60 Hz, IEC/ANSI, language: Spanish, selectable E

System interface (Port B): Refer to page 5/112

No system interface 0

Protocols see page 5/112

Service interface (Port C)

No interface at rear side 0

DIGSI 4/modem, electrical RS232 1

5)
DIGSI 4/modem/RTD-box , electrical RS485 2

5)6)
DIGSI 4/modem/RTD-box , optical 820 nm wave length, ST connector 3

Measuring/fault recording

Fault recording 1

Slave pointer, mean values, min/max values, fault recording 3

1) Rated current can be selected by means of

jumpers.

2) Transition between the two auxiliary

voltage ranges can be selected by

means of jumpers.

3) The binary input thresholds can be

selected per binary input by means of

jumpers.

4) 230 V AC, starting from device version

…/EE.

5) Temperature monitoring box

7XV5662- AD10, refer to “Accessories”.

6) When using the temperature monitoring

box at an optical interface, the additional

RS485 fiber-optic converter

7XV5650-0 A00 is required.

Siemens SIP · 2006 5/109


5 Overcurrent Protection / 7SJ62

Selection and ordering data Description Order No.

7SJ62 multifunction protection relay 7SJ62 – –

Designation ANSI No. Description

Basic version Control

50/51 Time-overcurrent protection

I>, I>>, Ip, reverse interlocking

50N/51N Earth-fault protection

IE>, IE>>, IEp

50N/51N Insensitive earth-fault protection via


1)
IEE function: IEE>, IEE>>, IEEp

49 Overload protection (with 2 time constants)

46 Phase balance current protection

(negative-sequence protection)

37 Undercurrent monitoring

47 Phase sequence

59N/64 Displacement voltage

50BF Breaker failure protection

74TC Trip circuit supervision

4 setting groups, cold-load pickup

Inrush blocking

5 86 Lockout

V, f 27/59 Under-/overvoltage

81 O/U Under-/overfrequency F E

IEF V, f 27/59 Under-/overvoltage

81 O/U Under-/overfrequency

Intermittent earth fault P E

Dir 67/67N Direction determination for overcurrent, phases and earth F C

Dir V, f 67/67N Direction determination for overcurrent, phases and earth

27/59 Under-/overvoltage

81O/U Under-/overfrequency F G

Dir IEF 67/67N Direction determination for overcurrent, phases and earth

Intermittent earth fault P C

Directional Dir 67/67N Direction determination for overcurrent, phases and earth

earth-fault 67Ns Directional sensitive earth-fault detection

detection 87N High-impedance restricted earth fault


2)
F D

Directional Dir IEF 67/67N Direction determination for overcurrent, phases and earth

earth-fault 67Ns Directional sensitive earth-fault detection

detection 87N High-impedance restricted earth fault

Intermittent earth fault


2)
P D

Directional 67Ns Directional sensitive earth-fault detection,

earth-fault 87N High-impedance restricted earth fault

detection
2)
F B

Directional Motor V, f 67Ns Directional sensitive earth-fault detection,

earth-fault 87N High-impedance restricted earth fault

detection 48/14 Starting time supervision, locked rotor

66/86 Restart inhibit

27/59 Under-/overvoltage
2)
81O/U Under-/overfrequency H F

Directional Motor V, f 67/67N Direction determination for overcurrent, phases and earth

earth-fault Dir 67Ns Directional sensitive earth-fault detection

detection 87N High-impedance restricted earth fault

48/14 Starting time supervision, locked rotor

Basic version included 66/86 Restart inhibit

27/59 Under-/overvoltage
V, f = Voltage, frequency protection
2)
81O/U Under-/overfrequency H H
Dir = Directional overcurrent protection

IEF = Intermittent earth fault

1) Only with insensitive earth-current

transformer when position 7 = 1, 5, 7.

2) For isolated/compensated networks


Continued on
only with sensitive earth-current
next page
transformer when position 7 = 2, 6.

5/110 Siemens SIP · 2006


5 Overcurrent Protection / 7SJ62

Selection and ordering data Description Order No. Order

code

7SJ62 multifunction protection relay 7SJ62 – –

Designation ANSI No. Description

Basic version Control

50/51 Time-overcurrent protection

I>, I>>, Ip, reverse interlocking

50N/51N Earth-fault protection

IE>, IE>>, IEp

50N/51N Insensitive earth-fault protection via


1)
IEE function: IEE>, IEE>>, IEEp

49 Overload protection (with 2 time constants)

46 Phase balance current protection

(negative-sequence protection)

37 Undercurrent monitoring

47 Phase sequence

59N/64 Displacement voltage

50BF Breaker failure protection

74TC Trip circuit supervision

4 setting groups, cold-load pickup

Inrush blocking 5
86 Lockout

Directional Motor V, f 67/67N Direction determination for

earth-fault Dir overcurrent, phases and earth

detection 67Ns Directional sensitive earth-fault detection

87N High-impedance restricted earth fault

48/14 Starting time supervision, locked rotor

66/86 Restart inhibit

27/59 Under-/overvoltage
2)
81O/U Under-/overfrequency R H

Motor V, f 67/67N Direction determination for overcurrent,

Dir phases and earth

48/14 Starting time supervision, locked rotor

66/86 Reclosing lockout

27/59 Under/overvoltage

81 O/U Under/overfrequency H G

ARC, fault locator Without 0

79 With auto-reclosure 1

21 FL With fault locator 2

79, 21 FL With auto-reclosure, with fault locator 3

ATEX100 Certification

For protection of explosion-protected motors (increased-safety type of protection “e”) Z X 9 9

Basic version included

V, f = Voltage, frequency protection

Dir = Directional overcurrent protection

IEF = Intermittent earth fault

1) Only with insensitive earth-current

transformer when position 7 = 1, 5, 7.

2) For isolated/compensated networks

only with sensitive earth-current

transformer when position 7 = 2, 6.

Siemens SIP · 2006 5/111


5 Overcurrent Protection / 7SJ62

Order number for system port B Description Order No. Order

code

7SJ62 multifunction protection relay 7SJ62 – – –

System interface (on rear of unit, Port B)

No system interface 0

IEC 60870-5-103 protocol, RS232 1

IEC 60870-5-103 protocol, RS485 2

IEC 60870-5-103 protocol, 820 nm fiber, ST connector 3

PROFIBUS-FMS Slave, RS485 4

1
PROFIBUS-FMS Slave, 820 nm wavelength, single ring, ST connector ) 5

1
PROFIBUS-FMS Slave, 820 nm wavelength, double ring, ST connector ) 6

PROFIBUS-DP Slave, RS485 9 L 0 A

1
PROFIBUS-DP Slave, 820 nm wavelength, double ring, ST connector ) 9 L 0 B

MODBUS, RS485 9 L 0 D

2
MODBUS, 820 nm wavelength, ST connector ) 9 L 0 E

5
DNP 3.0, RS485 9 L 0 G

2
DNP 3.0, 820 nm wavelength, ST connector ) 9 L 0 H

IEC 61850, 100 Mbit Ethernet, electrical, double, RJ45 connector (EN 100) 9 L 0 R

2)
IEC 61850, 100 Mbit Ethernet, optical, double, ST connector (EN 100) 9 L 0 S

1) Not with position 9 = “B”; if 9 = “B”, please order 7SJ6 unit with RS485 port and separate fiber-optic converters.

For single ring, please order converter 6GK1502-2CB10, not available with position 9 = “B”.

For double ring, please order converter 6GK1502-3CB10, not available with position 9 = “B”.

The converter requires a 24 V AC power supply (e.g. power supply 7XV5810-0BA00)

2) Not available with position 9 = “B”

Sample order Position Order No. + Order code

7SJ6225-5EC91-3FC1+L0G

6 I/O’s: 11 BI/6 BO, 1 live status contact 2

7 Current transformer: 5 A 5

8 Power supply: 110 to 250 V DC, 115 V AC to 230 V AC 5

9 Unit version: Flush-mounting housing, screw-type terminals E

10 Region: US, English language (US); 60 Hz, ANSI C

11 Communication: System interface: DNP 3.0, RS485 9 L 0G

12 Communication: DIGSI 4, electric RS232 1

13 Measuring/fault recording: Extended measuring and fault records 3

14/15 Protection function package: Basic version plus directional TOC F C

16 With auto-reclosure 1

5/112 Siemens SIP · 2006


5 Overcurrent Protection / 7SJ62

Accessories
Description Order No.

DIGSI 4

Software for configuration and operation of Siemens protection units

running under MS Windows 2000/XP Professional Edition

Basis Full version with license for 10 computers, on CD-ROM

(authorization by serial number) 7XS5400-0AA00

Professional DIGSI 4 Basis and additionally SIGRA (fault record analysis),

CFC Editor (logic editor), Display Editor (editor for default

and control displays) and DIGSI 4 Remote (remote operation) 7XS5402-0AA00

Professional + IEC 61850

Complete version:

DIGSI 4 Basis and additionally SIGRA (fault record analysis),

CFC Editor (logic editor), Display Editor (editor for default

and control displays) and DIGSI 4 Remote (remote operation)

+ IEC 61850 system configurator 7XS5403-0AA00

IEC 61850 System configurator

Software for configuration of stations with IEC 61850 communication under

DIGSI, running under MS Windows 2000 or XP Professional Edition


5
Optional package for DIGSI 4 Basis or Professional

License for 10 PCs. Authorization by serial number. On CD-ROM 7XS5460-0AA00

SIGRA 4

Software for graphic visualization, analysis and evaluation of fault records.

Can also be used for fault records of devices of other manufacturers (Comtrade

format). Running under MS Windows 2000 or XP Professional Edition.

(generally contained in DIGSI Professional, but can be ordered additionally)

Authorization by serial number. On CD-ROM. 7XS5410-0AA00

Temperature monitoring box

24 to 60 V AC/DC 7XV5662-2AD10

90 to 240 V AC/DC 7XV5662-5AD10

Varistor/Voltage arrester

Voltage arrester for high-impedance REF protection

125 Vrms; 600 A; 1S/S 256 C53207-A401-D76-1

240 Vrms; 600 A; 1S/S 1088 C53207-A401-D77-1

Connecting cable

Cable between PC/notebook (9-pin con.) and protection unit (9-pin connector)

(contained in DIGSI 4, but can be ordered additionally) 7XV5100-4

Cable between temperature monitoring box and SIPROTEC 4 unit

- length 5 m /16.4 ft 7XV5103-7AA05

- length 25 m /82 ft 7XV5103-7AA25

- length 50 m /164 ft 7XV5103-7AA50

Manual for 7SJ62/63/64,

English C53000-G1140-C147-6

French C53000-G1177-C147-2

Spanish C53000-G1178-C147-2

Catalog SIP 3.1 Spanish E50001-K4403-A111-A1-7800

Siemens SIP · 2006 5/113


5 Overcurrent Protection / 7SJ62

Accessories Description Order No. Size of package Supplier

spe.pfa-9822PSL
Terminal safety cover

Voltage/current terminal 18-pole/12-pole C73334-A1-C31-1 1 Siemens

Voltage/current terminal 12-pole/8-pole C73334-A1-C32-1 1 Siemens

Connector 2-pin C73334-A1-C35-1 1 Siemens


Mounting rail
Connector 3-pin C73334-A1-C36-1 1 Siemens

2 1)
Crimp connector CI2 0.5 to 1 mm 0-827039-1 4000 AMP

taped on reel
spe.pfa-1902PSL
spe.pfa-0902PSL

2 1)
Crimp connector CI2 0.5 to 1 mm 0-827396-1 1 AMP

2 1)
Crimp connector: Type III+ 0.75 to 1.5 mm 0-163084-2 1 AMP
1)
2
AMP
Crimp connector: Type III+ 0.75 to 1.5 mm 0-163083-7 4000
2-pin 3-pin
taped on reel
connector connector

1)
Crimping tool for Type III+ 0-539635-1 1 AMP
1)
and matching female 0-539668-2 1 AMP
1)
Crimping tool for CI2 1 AMP
spe.pfa-3902PSL

0-734372-1
spe.pfa-2902PSL

1)
and matching female 1-734387-1 1 AMP
5
Short-circuit links

for current terminals C73334-A1-C33-1 1 Siemens

for other terminals C73334-A1-C34-1 1 Siemens


Short-circuit links Short-circuit links

for current termi- for other terminals


Mounting rail for 19" rack C73165-A63-D200-1 1 Siemens
nals

1) Your local Siemens representative

can inform you on local suppliers.

5/114 Siemens SIP · 2006


5 Overcurrent Protection / 7SJ62

Connection diagram

Fig. 5/102 7SJ621 connection diagram

*) For pinout of communication ports see part 16 of this catalog.

For the allocation of the terminals of the panel surface mounting version

refer to the manual (http://www.siprotec.com).

Siemens SIP · 2006 5/115


5 Overcurrent Protection / 7SJ62

Connection diagram

Fig. 5/103 7SJ622 connection diagram

*) For pinout of communication ports see part 16 of this catalog.

For the allocation of the terminals of the panel surface mounting version

refer to the manual (http://www.siprotec.com).

5/116 Siemens SIP · 2006


5 Overcurrent Protection / 7SJ62

Dimension drawings in mm / inch

Dimension drawings for SIPROTEC 4

1/3 x 19" housing (7XP20)

Side view Rear view 1 Rear view 2 Panel cutout

7SA610, 7SD61, 7SJ64 7SJ61, 7SJ62, 7UT612,

7UM611

Fig. 16/22

Housing for panel flush mounting/

cubicle mounting (1/3 x 19")

Front view Side view

Fig. 16/23

1/3 x 19” surface-mounting housing

Siemens SIP · 2006 5/117