The contractor shall refer to Electrical Method of Measurement ITEM 17 page 47 of 49 ,and find below the electrical
specification for Security system (ALS ) . The system to be coordinate with all trades and find below the electrical specification
for Security system (ALS ) . The system to be coordinate with all trades.
Airlock system
2 Door interlock for access controlled systems:
Interlock device that prevents more than one door being open at any time, thus creating an airlock between the inner and outer
environments.
A door interlock system requires the user to pass through two doors in sequence to enter the premises. The doors are monitored
to ensure that they cannot both be open at the same time.
The system follows the sequence:
1. Request to open a door.
2. Confirm that the other door is Closed.
3. Accept the door open request - Energise the Lock Out relay.
Features
Switchable for fail safe and fail secure locks.
Can be used as a standalone device.
Multiple units can be connected together for scenarios where more than 2 doors need to be interlocked
Includes plastic casing.
Simple to wire up.