You are on page 1of 7

General Performance Data

Prime Power 250KVA/200KW Brand Cummins


Engine
Stand by Power 275KVA/220KW Model 6LTAA8.9-G2

Frequency/Speed 50Hz/1500rpm Control module Deepsea 6120

Rated Power Factor(cosφ) 0.8 Rated Current 361A

Standard Voltage 230V/400V Capacity of Breaker 400A

Phases 3 Starting Voltage DC24V

Fuel consumption Standards followed

Rated output Fuel consumption rate ISO9001 ISO14001

100%Standby 1 9 9 g/KW.h 5 8 L/h ISO8528 ISO12100

100%Prime 1 9 7 g/KW.h 5 3 L/h ISO13849 EN12601

75%Prime 1 9 7 g/KW.h 3 9 L/h GB12786 GB/T2820

50%Prime 2 0 1 g/KW.h 2 7 L/h IEC60034 IEC60204

25%Prime 2 2 0 g/KW.h 1 5 L/h CE RETIE

Dimensions and Weights

Type Open Silent

Length(mm) 2570 3600

Width(mm) 1000 1200

Height(mm) 1765 1980

Weight(kg) 2000 2700

Base fuel tank volume (L) 420 420


Engine specification

Basic parameter Air induction system

Manufacturer dongfeng Cummins Maximum allowable intake air restriction

Model 6LTAA8.9-G2 ---with clean filter element 3.7kPa

No. of cylinder 6 ---with dirty filter element 6.2kPa

Type 4 cycle, Vertical In-line Intake Air alarm temperature 82℃

Prime Power 220kw /295HP Exhaust system

Standby Power 240kw /322HP Max. allowable back pressure 10kPa

Turbocharged and Air


Induction system Standard exhaust pipe diameter 75mm
to Air Aftercooled

Governor Electronic speed

Bore x Stroke 114x145mm Cooling system

Displacement 8.9L Coolant capacity

Compression ratio 16.6:1 ---Engine only 11.1L

Oil Capacity(Total) 27.6L ---Total system 34 L

Coolant Capacity(Engine only) 11.1L ---With heat exchanger 22.9L

Cranking Motor Voltage DC24V Standard thermostat(modulating) range 82-95 ℃

Fuel System Minimum cap pressure 103kPa

North Oil P7100 inline Max. allowable top tank temerature


Type Injection system 104/100 ℃
pump for stand by/prime power
Min. Allowable flow of fuel to
58 L/h
fuel pump

Lubrication system Electric system

Oil Pressure Min. recommended battery capacity (24V)

---Idle speed 103kPa ---10℃(50°F) & above- 0°F CCA 750

---Rated speed 276-414kPa --- 0℃(32°F) to 10℃(50°F)- 0°F CCA 750

Max. allowable oil temperature 121℃ ---18℃(0°F) to 0℃(32°F)- 0°F CCA 750

Offset sump oil capacity: low/high N /A Max. allowable resistance of Starting circuit 0.002ohm

Total system capacity 27.6L Starter(heave,Anode) DC24V

Battery recharge system, negative ground 70ampere

Alternator specification Leroysomer: TAL-A46-D/200KW


Phases 3 Coating Vacuum impregnation

Poles 4 Insulation class H

Power factor(cosφ) 0.8 Protection IP23

Winding connection Star Excitation system SHUNT

Winding pitch 2/3 Bearing Single Bearing

Voltage regulator type AVR Coupling Flexible disc


Control system Introduction

Deepsea 6120 Auto start & auto mains


Key Features:
failure control panel
Deepsea 6120 is an auto mains failure controller for single ● Auto start/stop, load transfer and alarming
generator, it can monitor and protect the generator of generator
working all the time. it has a LCD display which clearly ● Remote start on or off load
shows the status of the engine. this controller include ● With hierarchical loading function
seven inputs and six outputs. This controller can also be ● Multiple start/stop cycles can be preset
programmed using the front panel or by using DSE ● 3 phase generator and mains voltage monitoring.
configuration Suite PC software ● Generator/load power detection(kW, kVA, kVAr PF)
● Overload protection (kW)

①Emergency stop button ● Load current monitoring and protection


● Engine speed protection
⑤ ②Power switch
● Engine pre-heat
③Power indicator
● Engine start idle & stop idle
④Operation buttons
● Battery voltage monitoring
④ ③② ① ⑤LCD display ● Start under the low battery
● 4 active outputs
⑥ ⑦ ⑧
● 4 digital inputs and 3 analogue inputs.
● 6 Custom digital input
● 6 outputs(4 configurable on magnetic pick-up,
6 configurable on Canbus version)
● DSE2130,DSE2157,DSE2548 expansion module
can be connected
● Support 0-10V or 4-20mA oil pressure sensor
⑨ ⑩

⑥Voltage and frequency trimmer ⑨MCB


⑦Governor ⑩Relay
⑧Charger

Main features: Protection:

● Multi language display ● Two sets of protection parameters can be preset


● Mains failure self starting ● Normal alarm, electrical trip and shutdown alarm can be
● The running time of the engine can be recorded to set to effectively monitor the engine speed,oil pressure,
facilitate the maintenance and repair of the unit water temperature and oil level, as well as the frequency,
● User-friendly set-up and button layout voltage, current and power of the alternator, for
● LCD display can display multiple parameters at the complete engine/alternator protection
same time ● Low Oil Pressure
● Support EFI engine ● High water Temperature
● IP65 rating (with optional gasket) ● High voltage and low voltage
● PC and front panel configuration ● Overspeed
● 100 event records ● Emergency stop
● Data recording and trend analysis ● Fail to start
AOSIF Soundproof Canopy Introduction:

Silent Type:

● The vertical angle structure makes the appearance The drainage outlets are all connected to the outside
beautiful for easy operation

● High quality coating powder, chemical surface


treatment & ● The sufficient air in & out design ensure long-term
100-120um coating thickness greatly improving the and
anti- stable operation of the unit
corrosion and anti rust level

● Isolation net is designed for air inlet, exhaust outlet


and
● carbon hinge & door lock are beautiful and anti-rust
muffler outlet to prevent objects from entering the
unit

● High density foam used inside effectively reduces


● 1.8mm cold rolled plate used makes the body more
noise
solid

● The built-in base fuel tank with fuel filler set on the
● The bottom forklift and loading port design enables
shell
easy
facilitates refueling
loading and unloading

● 180° revolvable and disassemble door for easy ●Emergency stop button mounted on the canopy
maintenance. exterior for urgency.
Decomposition diagram introduction of AOSIF Typical Canopy

Standard supply scope:

① Engine
⑧ ② AC Alternator
③ Cooling Radiator
④ Auto Start Control Panel
⑨ ⑤ Main Ciruit Breaker
⑥ Built in Shock Pad
⑦ High Strength Frame
⑩ ⑧ Exhaust silencer
⑨ Bellow
⑩ Starting battery

Optional supply scope:


Genset Engine Alternator Control system

● Tool box ● Fuel heater ● Temp. detector for ● ATS


● Base fuel tank ● Fuel and water winding and bearing ● Synchronization
● External daily fuel tank separator ● PMG System
● Trailer ● Antirust, mildew and ● Adjustable earth relay
salt fog treatment
● Anti condensation
heater

Breaker Fuel system Lub-oil system Cooling system

● ABB ● Low fuel level alarm ● Lub oil heater ● Elec.coolant Heater
● Schneider ● Auto Fuel Pump ● Temp.-sensor
● T Vlave ● Oil drain Pump
● AOSIF Engineering provides a full line of brand new and high quality products.

● Each unit passes strictly loading test in factory before shipment.

● Quality Warranty is provided strictly in accordance with warranty terms.

● Three level service guarantee: Aosif dealers, Service outlets of engine/alternator

manufacturers, Aosif service team.

严格按保修条款提供免费保修服务

XIAMEN AOSIF ENGINEERING LTD.


Marketing Center: Unit 1001,No.1 of Cheng Yi North Street,Software Park Phase III ,Xiamen ,China;
Factory: No.1088 Tangbian, Changtai Economic Development Zone, Zhangzhou,Fujian,China.
Website: www.aosif.com

You may get more information from our official account.


Specifications are subject to change without notice.

You might also like