Professional Documents
Culture Documents
"5*0/
#644:45&.4
-#3&.05&*0
%*7
'#3&.05&*0
;0/&
130'*#64
.0%#64
'*&-%#64
1&11&3-'6$)43&.05&*0
5IFJEFBMDPNCJOBUJPOPGEFDBEFTPGFYQFSJFODFBOEDVTUPNFSPSJFOUBUFEJOOPWBUJPO
1FQQFSM'VDITIBWFXPSMEXJEFBDDFTUPBMMUIFJNQPSUBOUNBSLFUTDPWFSJOHUIFSFMFWBOU
TUBOEBSETBOEJOUFSOBUJPOBMBQQSPWBMT1FQQFSM'VDITWPVDIGPSBTBGFGVUVSFXJUIDPOUJOVJUZ
JORVBMJUZBOETFSWJDF$POUJOVJUZBMTPNFBOTUIBUZPVXJMMCFBCMFUPQVSDIBTFQSPEVDUTUIBU
IBWFSFBDIFEDPOTJEFSBCMFJNQPSUBODFGPSUIFTNPPUISVOOJOHPGZPVSQMBOUPOBMPOHUFSN
CBTJT
"TBGFGVUVSFNFBOTUIBUZPVDBOSFMZPO1FQQFSM'VDITJOWFTUJOHJOJOOPWBUJWFUFDIOPMPHJFT
UPHJWFZPVUIFNPTUDPTUFGGFDUJWFTPMVUJPOTGPSZPVSUBTLT5IFDPNQBOZJTTFUUJOHUIFQBDF
GPSJOUFOTJWFBDUJWJUJFTJOEFTJHOBOESFTFBSDI
*OUIFGJFMEPG3FNPUF*0UIFSFBSF-#3FNPUF*0GPS;POFBOE%*7FNQMPZJOHUIFTBNF
FOHJOFFSJOHBT'#3FNPUF*0GPS;POF#PUIPGGFSUIFIJHIFTUQBDLJOHEFOTJUZJOUIFNBSLFU
"UUIFTBNFUJNFZPVDBODPNCJOFIJHIMZNPEVMBSEFWJDFTXJUIUIPTFPGGFSJOHNVMUJDIBOOFMT
JODPNQBDUIPVTJOHT
)VOESFETPGUIPVTBOETPGNPEVMFTBSFJOPQFSBUJPOXPSMEXJEF
5PTJNQMJGZUIFQVSDIBTJOHQSPDFTTGPSZPVXFOPXPGGFSUIFQPTTJCJMJUZUPPSEFSNPEVMFTVTJOHUIF
TIPSUNPEFMDPEFSBUIFSUIBOUIFEJHJU()(OVNCFS5IJTEPFTOPUSFTVMUJOBOZDIBOHFTUPUIF
NPEVMFUZQFUBHTTPUIFSFJTOPOFFEUPDIBOHFZPVSFTUBCMJTIFEEPDVNFOUBUJPO"MUFSOBUJWFMZZPVDBO
DPOUJOVFUPPSEFSJOUIFTBNFXBZBTZPVIBWFEPOFJOUIFQBTU
*OBEEJUJPOUP-#'#3FNPUF*0UIFSFJTBTFQBSBUFDBUBMPHGPSTJNJMBSMZQSPWFOJOVTF31*
3FNPUF1SPDFTT*OUFSGBDF
CBTFEPOPVS1PXFS3BJM4ZTUFN
Table of Contents
Remote I/O
Model Function chapter/page
LB/FB Remote I/O with Profibus DP/DPV1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0/1
Subject to reasonable changes due to technical advances. Copyright Pepperl+Fuchs Printed in Germany
Pepperl+Fuchs GmbH • 68301 Mannheim • Telephone +49 621 776 2222 • Fax +49 621 776 272222 • Internet www.pepperl-fuchs.com I
Table of Contents
Subject to reasonable changes due to technical advances. Copyright Pepperl+Fuchs Printed in Germany
Pepperl+Fuchs GmbH • 68301 Mannheim • Telephone +49 621 776 2222 • Fax +49 621 776 272222 • Internet www.pepperl-fuchs.com II
LB / FB Remote I/O with
PROFIBUS DPV1 and FDT
data base
Engineering Tool
with FDT
0/1
DCS Compatibility of Profibus DP
PLC data
Slave 1 and DPV1
DPV1 buffer The FDT concept was taken into consideration
Slave 2 during the further development of the
PROFIBUS.
The Profibus DPV1, that features some new
Slave 7
important properties, is fully compatible with the
Profibus DP. This ensures that DPV1 field sta-
data Slave 3 data
tions function with an existing Profibus DP in the
same way as an existing slave functions with a
DPV1 master. However, the user can only make
Slave 6 use of all the advantages of the DPV1 concept if
Slave 4 both master and slave have the DPV1 properties.
Slave 5 In addition to the synchronous data traffic of the
Profibus DP, the Profibus DPV1 also provides
asynchronous services that allow the exchange
of parameter and configuration data between
Fig. 2 master and slave. Whereas synchronous tele-
asynchronous datatransfer DPV1 grams belonging to one participant are always
When using the various products, the user can
of the same structure and length, the data ex-
quickly adapt to the respective operating sys-
change of the DPV1 is characterized by a fixed
tem, because, as with Microsoft WINDOWS,
buffer area into which data telegrams that are
due to the recognition effect, the configuration
important for the parameterization and configur-
software is almost self-explanatory.
ing can be inserted, when required (Fig. 2).
Therefore, by way of example, operation with
the engineering tool of the control system or
of the DCS is based on the modules shown
in Fig. 1. Here the following information is ex-
HART communication and
changed between master and slave:
Profibus DPV1
The new properties of the Profibus DPV1 also
R Type of device
make it possible to transmit HART telegrams via
R Parameters
the system bus. In this way, depending on the
R Communication settings
functions supported in the control system, exist-
R Calibration and setting data
ing field devices can be actuated with the HART
R Configuration data
protocol. Thus, this allows the same functionality
R Diagnosis functions
as that which is otherwise only provided by the
Profibus PA.
The control of the plausibilty of the parameters is
The HART signals are modulated onto the 4-20 mA
also included in this concept.
signal in the transmitter supply circuits of the
All data is managed in the master throughout
remote I/O module using the usual technique
all the planning and commissioning phases, as
(Fig. 3).
well as during operation and is also available in
the data base for the other software tools that
P+F comm. units accept all HART data. There-
are maintained by the master. Thus, the vari-
Fig. 3 fore, information specific to the devices can be
ous tools that are familiar for parameterizing the
called up via the Profibus by all HART field de-
master and slave are replaced by one common
vice manufacturers that make their HART DTM
software tool. The previously used Profibus de-
available for the FDT.
vice description file is still kept, but is now only
integrated by users who cannot use a DPV1
P+F supports both FDT 098 and FDT 1.2 while
master. The new device description file of the
most field device manufacturers offer DTMs for
DPV1 is automatically recognized by the FDT.
FDT 1.2 only.
0/2
LB / FB Remote Hardware for R In addition to the synchronous services for
the Profibus DPV1 data exchange, the software of the DPV1 pro-
tocol also provides asynchronous services for
0
It is easy for the users of the P+F remote I/O
parameterizing and configuring slaves using
to switch over to the advantages of the new
the engineering tool of the master.
Profibus DPV1. All existing I/O modules can be
kept, as it is only necessary to replace the bus R In principle, the Profibus allows changes
coupler to equip the P+F slaves with the new ONLINE. How this is done is described by
properties. the manufacturer of the PLC or DCS. DPV1
The technical data of the modules and system allows parameter settings ONLINE (measuring
components can be found in this catalogue. ranges, etc.)
R Diagnosis data is called up synchronously
LB / FB Remote Software for Profibus via the DP bus. This requires an error bit per
DPV1 module and status information on line breaks
Zone 2 Zone 1 With the aid of the FDT concept, the DTM or short circuits. The DPV1 bus provides
communication software of the P+F remote I/O is integrated into even more information, that can be called up
units
its engineering tool by the system house. This asynchronously and contains up to 64 bytes
software is matched to the firmware in the bus of information.
couplers (comm. units).
R In DP systems HART communication is only
In addition to the DTM software in the master, possible via the service bus. In the case of
the user also receives a manual and a CD ROM the DPV1 this bus does not keep a HART
with the DPV1 bus couplers. These contain protocol, as this function is accessible via the
descriptions of the properties of the remote I/O Profibus if the master supports this property
and instructions on how to use the configurati- or a secondary master is used.
on and parameterization tools.
R While, for servicing or commissioning, the DP
Although the settings are made via the master, bus couplers are already able to set outputs
the extremely useful option of using the service for manual operation via the service bus,
bus is still open. During commissioning the DPV1 couplers also provide this possibility
user can already carry out loop tests using this for inputs.
second bus while the control system is still
R Redundancy is available for P+F remote
being built up.
I/O modules in both DP and DPV1 appli-
Further possibilities provided by the service bus cations. This function is already being used
are listed below: successfully by various system houses.
R commissioning aid
R Analog inputs and outputs can be scaled
R simulations of inputs, outputs (forcing)
to suit the range of the control system. With
R fault analysis in operation
the DP bus scaling is carried out in one para-
R remote diagnosis with PC - ANYWHERE
meter for all inputs and in another parameter
via telephone modems
for all outputs. The DPV1 bus coupler allows
R software updates
the individual scaling of all inputs and outputs
via respective parameters for each channel.
Differences between P+F remote I/O with
Profibus DP and DPV1 R In the event of line faults DP bus couplers can
The most important differences between the switch outputs to zero, 0% or 100%. With
remote I/O for the Profibus DP and the DPV1 DPV1 systems any equivalent values desired
can be summarized as follows. within the measuring range can be set for
each channel.
R The only difference in the hardware for the
P+F remote I/O with Profibus DP and DPV1 R In addition to the possibility of choosing bet-
is the bus coupler. All other components ween a positive and negative logic for DPV1
remain unchanged. applications, with binary inputs it is
also possible to set ON and OFF delays.
0/3
R DP bus couplers version 3 allow the linking R Modbus is supported by suitable
of inputs and outputs within one bus station comm. units.
without the intervention of the master. This R DPV1 software for well-known DCS are
property is not provided in DPV1 systems. available after passing a system integration
R The same applies for the software tools in DP test.
systems for programming mathematical and R P+F Remote I/O operates successfully
logical functions in bus couplers. In DPV1 together with more than 20 different
bus couplers these properties are left to the well-known DCS and PLC systems.
master.
R Hundreds of thousands of modules are in
operation worldwide.
0/4
LB Remote I/O
Description
LB remote I/O stations are important signal
conditioning devices for interfacing signals from
the field to controllers or process control
systems. In potentially explosive atmospheres
in Zone 2 or Zone 22 or Div 2 the plug-in
1
modules are mounted on pre-fabricated, plastic
backplanes.
Hot swapping of the various IS I/O modules
is possible. In addition to the easy plug-in
mounting method, the other advantages of the
LB remote I/O modules are the galvanic isolation
and the amplification properties. What is more,
the conventional I/O groups for the PLC or DCS
are no longer required. Wiring is reduced to that
of a standard bus connection. The galvanic
isolation provides a safe and reliable interface
between the process and the bus. The amplifi-
cation properties and the digital transmission
ensure a high degree of measurement accuracy
that, in addition, is not influenced by variations in
the auxiliary power supply.
LEDs indicate the status of the respective
device. A green LED indicates the operating
status, while a red LED indicates a fault, e.g. an
open line or short circuit. The PLC or DCS can
call up this data via the bus.
■ 2 to 8 channels, digital
■ 1 to 4 channels, analog
■ Considerable savings in
hardware and wiring
■ Zone 2 or Div 2 mounting
possible
■ Plug-in modules for analog
and digital inputs and
outputs
■ Screw-in and plug-in cable
connections directly on the
module
■ Optional wire clamp connection
■ Safe galvanic isolation
■ LED status indication
■ Low power consumption
■ ATEX certification for EEx ia/ib
■ Proven successful with all renowned
PLCs and process controls systems
■ International approvals
1/1
Designed to be
User-Friendly
1/2
Fast- and
User-Friendly
Setup
Application redundancy
A field station features 2 redundant communica-
tion units. To be able to access both bus lines,
SE.1
SE.2
RK
SE.1
SE.2
sufficient to supply the respective backplane
with all the modules and the two communication
units. The third power supply is in the standby
mode and becomes active in the event of a
fault. A diagnostics report informs the DCS of
the fault (>V6.X).
Example Redundant substation (max. 46 slots)
Two selectors per segment using backplane LB 9022 Signal processing
Independent of the data traffic on the system
LB Remote I/O series: Software for the communication unit. However, the bus, the I/O modules constantly transmit the
Internal switches or potentiometers are not configuration of the communication unit must incoming signals into an internal bus format
needed for LB Remote I/O signal- conditioning either be loaded from the control system or via using the high integrity Manchester code. The
modules. the RS 485 service connection. In a redundant reverse is the case for outgoing signals. One task
They are either configured via the control system system this is carried out automatically. of the communication unit is to ensure the quick
or via an easy-to-use WINDOWS™ program transfer of data to the I/O modules. The internal
and the RS 485 interface in the communication Graded redundancy (see example) memory of the communication unit contains a
unit. The setting of each and every module is As each control system has its own individual complete image of the field signals at all times.
stored in a non-volatile memory in the commu- requirements, the LB Remote I/O series was As the comm unit is the only interface between
nication unit. provided with a graded redundancy concept. the LB Remote I/O and the standard bus of the
main control system, future bus developments in
Self-documentation Redundant Comm Units (BK, RK) this field can also be taken care of.
The LB remote I/O software uses the confi- Two communication units can operate in parallel
guration data to compile a full documentation so that a bumpless transition can take place in HART communication
packet. Using this property can mean a case of a fault in one of them. The LB Remote I/O range of products supports
considerable saving in time and costs. HART communication. Provided that the control
Redundant selectors (SE) system can also process the HART protocol,
Plug and play With the backplanes LB 9022 and LB 9024 both direct communication with the field devices via
As the configuration data of each I/O module communication units can access the internal the Profibus is possible. Alternatively a second-
is stored, in the event of a failure of a module, bus via redundant selectors. ary master can be used on the Profibus line.
it can easily be removed and replaced by a Depending upon the type of communication
standard module that has not been pro- Line redundancy unit, HART communication is also possible via
grammed. As soon as a new unit has been A field station features 2 redundant communica- the service bus.
plugged in, within a fraction of a second the tion units. The field bus is also redundant. The
communication unit renews the setting of the transmission lines of the master are connected Line monitor
new I/O module, and the device starts to to the active and passive communication units Almost all the LB Remote I/O modules feature
function immediately. If the wrong type of via both bus lines. In order to be able to access a line monitoring system.
module is fitted, this is recognized and does not both bus lines, the master features a VOTER for This function can be activated channel by
influence the running operation. This also applies the receiving lines. channel or it can be deactivated.
1/3
LB Remote I/O, Zone 2
Product Overview
Product features
• Mounting in Zone 2 or Zone 22 or Div 2 or
outside hazardous areas
• Analog input single channels with high
availability or 4-channel compact mode
• Digital input 2-channels with high availability
or 8-channels compact mode
• Single channel and multi-channel modules
• Can be unplugged in Zone 2 during operation
• Input- and output for all standard process
signals
• Single-channel modules with galvanic
isolation for each channel
• Multi-channel modules are galvanically
isolated betweenn input and field bus
(group isolation)
• Simulation for commissioning and service
operration (forcing)
• Plug and play service after replacement
• HART communication with PROFIBUS and
FDT or with servicebus depending on version
• Output drive selectable depending on version
• Permanent self-monitoring
• Output level adjustable depending on version
• Output with watch dog circuit for fatal errors
• Module TAG and channel TAG-depends
on version
• Same No. of modules with- and without
redundancy
• Version dependency see comm. units
• EMC to EN 61326 or NE21
General:
Power supply 24 V DC (20 … 30 V)
Degree of protection (required) IP 54 (Zone 2 or 22) IP6x (flammable dust)
Ambient temperature -20 °C ... 70°C (Ex-i 60 °C)
Control Relative humidity < 95 %, no condensation
room
CPU CPU Pollution test for plugs acc. IEC 68-2-42
(21 days with 25 ppm SO2,
at 25 °C and 75 % relative hum.)
Type of enclosure plastic, stainless steel or painted sheet steel
LB Remote LB Remote
Configuration:
Remote I/O slaves can be configured
• via Profibus using GSE files
FOL Zone 2 • via Profibus using FDT/DTM or PDM
• via Service bus using a software tool
Depending on the comm. unit there are a wide variety
FOL Zone 1 of parameters for each module to choose from.
FB Remote FB Remote
Bus Structure
1/4
LB Remote I/O, Zone 2
Product Overview
Bus structure
Number of modules (channels) per station
1 channel, high availability up to 46 (46 analog, 138 digital)
multi-channel, compact up to 23 (80 analog, 184 digital)
defined by the field bus specification
Max. number of stations per bus line
125 (Profibus), 255 (ModBus)
Number of slaves per bus segment max. 31
Repeaters between master-slave max. 3
Bus connection 9-pole Sub-D connector
FOL (fibre optic link) peripheral device required
Bus length, max. (FOL) 1000 m ( 1.5 MBaud)
Bus length, mac. (copper) 1000 m ( 187,5 kBaud)
200 m ( 1.5 MBaud)
Redundancy (optional)
2 power supplies for 24 slots
Power supply redundancy
with bumpless changeover
2 comm units per station
Line redundancy (voter)
with bumpless changeover
2 comm units per station
Application redundancy (2 CPUs)
with bumpless changeover
HART communication
Depending on the comm unit HART communication to field devices is possible via Profibus
or the service bus. The latter features an RS 485 interface for HART communication. This
can also be used with redundant systems in addition to the main bus. HART communication
with any compatible field device is possible from the control room. For this you have to use
the software provided by the manufacturer of the field device or any off-the-shelf software,
P Voter Bus e.g. CORNERSTONE, Fisher Rosemount AMS, ABB SMARTVISION, Siemens PDM, etc.
L Master In the case of control systems that support the FDT concept and use the Profibus, HART
S Redundant bus communication via the Profibus is possible using the P+F DTM. Alternatively a secondary
master can be used on the Profibus line again using an FDT compatible software package
Line redundancy (e.g. SMART VISION, Pactware, Fieldcare, Siemens PDM, Emerson AMS).
BK
BK
BK
BK
Master
P Bus Profibus DPV1
L In the case of control systems that support the FDT concept or feature the appropriate drivers
S Redundant bus and use the Profibus DPV1, configuration and setting parameters from the engineering tool of
Redund.
Master
the control system is possible via the Profibus using the P+F DTM (or Siemens PDM).
BK
BK
BK
BK
Application redundancy
ModBus
Voter Bus Suitable comm. units are available for control systems that prefer ModBus RTU.
Master
P
L Approvals
S Voter
BK
BK
BK
BK
Redund The modules have been certified by the PTB for intrinsically safe circuits (PTB 03 ATEX 2042).
Master Redundant bus Mixed installations of devices with older certificates are permitted.
A Conformity Statement from the PTB is available for mounting in Zone 2 (PTB 99 ATEX 2186)
or Zone 22.
Examples for redundant bus structures International approvals upon enquiry (Cepel, Nepsi, UL, GOST, IECEx).
1/5
LB Remote I/O
Selection Chart
Selection chart
Application Type Preferred version Page
2 channels LB 1X01 GHG 127 0000 A1X01 1/10
fully
isolated
contact
3 channels LB 1X02 GHG 127 0000 A1X02 1/11
group isolation
NAMUR 1-channel, 0-15 kHz LB 1X03 GHG 127 0000 A1X03 1/12
Initiator frequency, direction
of rotation,
10 k dosing counter
Digital input
2,2 k
7 channels LB 1X07 GHG 127 0000 A1X07 1/13
contact with NARMUR or
NAMUR voltage input
network group isolation
for LFD
Level
15 V supply
1/6
LB Remote I/O
Selection Chart
Selection chart
Application Type Preferred version Page
1 digital output
2 inputs
group isolation
LB 21XX GHG 127 0000 A21XX 1/18
1
Solenoid valve 2 channels LB 6101 GHG 127 0000 A6101 1/36
Relay output 24 V
isolated
Digital output
4 channels LB 6005 GHG 127 0000 A6005 1/37
LED
Relay output
230 V fully
isolated
Positioner
HART LB 4X02 GHG 127 0000 A4X02 1/27
750 1
I/P isolated
I/P converter
HART, 4 channels LB 4X05 GHG 127 0000 A4X05 1/28
750 1
0000 group isolation
Display
isolated
1/7
LB Remote I/O
Selection Chart
Selection chart
Application Type Preferred version Page
Strain gauge
plus LB 5102 GHG 127 0000 A5102 1/31
millivolt amplifier
20 mA/14 mV
(load 350 1,
2 mV/V)
Slide wire sensor
sensor supply
1/8
Digital input
Product Overview
Product features
• Mounting in Zone 2 or Zone 22 or Div 2
or outside hazardous areas
• Single channel high integrity or
8 channel compact modules
• Single channel and multi channel modules
can be mixed mounted
1
• any slot position
• Can be unplugged in Zone 2 during operation
(hot swap)
• inputs for NAMUR initiators, mechanical
contacts, opto-couplers and active
24 V signals
• Single- and two-channel modules:
each channel is galvanically isolated
• 8-channel modules are galvanically
isolated between input and system bus
(group isolation)
• Simulation for commissioning and
service (forcing)
• self configurating after replacement
• positive- or negative logic selectable
depending on the version
• Line monitor depending on the version
• permanently self-monitoring
• on-/off-delay depending on the version
• module TAG and channel TAG depending
on the version
• same number of modules with- and without
redundancy
• version dependancy see comm. units
• EMC to EN 61326 or NE21
Available models
LB 1X01 digital input, 2 channels, isolated
LB 1X02 digital input, 3 channels, group isolation
pulse, frequency input
LB 1X03
1 channel, isolated
LB 1007 digital input, 7 channels (group isolated)
LB 1X08 digital input, 8 channels, group isolation
10k
digital input, 15 channels 230 V
2.2k LB 1014 (group isolated)
digital input, 15 channels 24 V
Contact LB 1015 (group isolated)
Contact with
NAMUR X = 1: intrinsically safe EEx ia, X = 0: not intrinsically safe
network
for LFD
NAMUR
Initiator
Opto- Voltage
coupler input
1/9
LB 1101
Digital Input
2 Isolated Channels
Product features
• Mounting in Zone 2 or Zone 22 or Div 2 • Simulation for commission and service (forcing)
or outside hazardous areas • Self configurating after replacement
• Any slot position • Positive or negative logic selectable
• Can be unplugged in Zone 2 depending on version
during operation (hot swap) • Line monitor (LFD)
• Inputs for NAMUR initiators, • Permanent self-monitoring
mechanical contacts and opto-couplers • ON/OFF delay
• Galvanic isolation between inputs • Modul-TAG and channel-TAG
and the field bus • EMC to EN 61326 or NE21
Input:
Volt-free contacts and 2 wire
Signal type
NAMUR proximity switches
ON > 2.1 mA
Switching points
OFF < 1.2 mA
Hysteresis 0.2 mA
Line fault < 1 mA
short > 6 mA
Frequency 0 - 50 Hz (depending on DCS)
Power consumption 0.4 W
Explosion protection:
Category II (1/2) GD [EEx ia] IIC
Approval PTB 03 ATEX 2042
Uo ) 12.6 V Io ) 12.8 mA Po ) 40.1 mW
IIC Safety values (linear)
Co ) 720 nF Lo ) 2 mH
Ordering details
Category Type Order No.
Digital input, 2-channel EEx ia LB 1101 A GHG 127 0000 A1101
Digital input, 2-channel – LB 1001 A GHG 127 0000 A1001
CH 1 CH 2
10k
2.2k
+ - + -
1 2 3 4 5 6
LB Remote
LB/FB I/OI/O
Remote
1/10
LB 1102
Digital Input
3 Channels
Product features
• Mounting in Zone 2 or Zone 22 or Div 2 • Simulation for commission and service (forcing)
or outside hazardous areas • Self configurating after replacement
• Any slot position • Positive or negative logic selectable
• Can be unplugged in Zone 2
during operation (hot swap)
• Inputs for NAMUR initiators,
depending on version
• Line monitor (LFD)
• Permanent self-monitoring
1
mechanical contacts and opto-couplers • ON/OFF delay
• Galvanic isolation between the input • Modul-TAG and channel-TAG
and the field bus (group isolation) • EMC to EN 61326 or NE21
Input:
Volt-free contacts and 2 wire
Signal type
NAMUR proximity switches
on > 2.1 mA
Switching points
off < 1.2 mA
Hysteresis 0.2 mA
Line fault (LFD) < 1 mA
short > 6 mA
Frequency 0 - 50 Hz (depending on DCS)
Power consumption 0.5 W
Explosion protection:
Category II (1/2) GD [EEx ia] IIC
Approval PTB 03 ATEX 2042
Uo ) 10.5 V Io ) 35 mA Po ) 92 mW
IIC Safety values (linear)
Co ) 785 nF Lo ) 2 mH
Ordering details
Category Type Order No.
Digital input, 3-channel EEx ia LB 1102 A GHG 127 0000 A1102
Digital input, 3-channel – LB 1002 A GHG 127 0000 A1002
CH 1 CH 2 CH 3
10k
2.2k
+ + + - - -
1 2 3 4 5 6
LB/FB Remote
LB Remote I/OI/O
1/11
LB 1003 - 1103
Digital Input
Frequency, Counter, Direction of Rotation
Product features
• Frequency input, counter, direction of rotation
• any slot position
• Can be unplugged in Zone 2 or Div 2 during operation
• Inputs for contacts,
NAMUR - proximity switches and optocouplers
• Galvanic isolation between input
and system bus
• Simulation for commissioning and
service (forcing)
• plug and play service after replacement
• positive- or negative logic selectable depending on version
• Line monitor (LFD)
• permanent self-monitoring
• EMC to EN 61326 or NE21
Input:
Volt-free contacts and 2 wire
Signal type
NAMUR proximity switches
on > 2.1 mA
Switching points
off < 1.2 mA
Hysteresis 0.2 mA
Frequency 0 - 15 kHz (see below)
Processing time approx. 50 ms mode dependant
Minimum pulse duration 20 s
Line fault < 1 mA
short > 6 mA
Scanning time 6.5 ms
Power consumption approx. 0.6 W
Explosion protection:
Category II (1/2) GD [EEx ia] IIC
Approval PTB 03 ATEX 2042
Uo ) 10.5 V Io ) 23.3 mA Po ) 61.2 mW
IIC Safety values (linear)
Co ) 816 nF Lo ) 2 mH
Ordering details
Category Type Order No.
Digital input max. 15 kHz EEx ia LB 1103 A GHG 127 0000 A1103
Digital input max. 15 kHz – LB 1003 A GHG 127 0000 A1003
Digital input max. 400 Hz EEx ia LB 1103 C GHG 127 0000 C1103
CH1 Direction
10k Digital input max. 400 Hz – LB 1003 C GHG 127 0000 C1003
2.2k note:
for mechanical contacts use 400 Hz-version
Configuration parameters
TAG No.
+ - + - Line monitor
1 2 3 4 5 6
Line fault substitute value
Span, filter
Input simulation
Frequency 15 kHz without determination of direction 12 bit + 4 bit status
Frequency 15 kHz with determination of direction 12 bit + 4 bit status
Pulse counter 15 kHz without determination of direction 12 bit + 4 bit status
Pulse counter 15 kHz with determination of direction 12 bit + 4 bit status
Pulse counter 15 kHz without determination of direction 32 bit
LB Remote I/O Pulse counter 15 kHz with determination of direction 32 bit
50 Hz frequency 12 bit + 4 bit status + pulse counter 32 bit
without determination of direction (min. pulse duration 10ms)
50 Hz frequency 12 bit + 4 bit status + pulse counter 32 bit
with determination of direction (min. pulse duration 10ms)
depending on the comm. unit
1/12
LB 1007
Digital Input
7-channels, time stamping option
Product Features
• Time stamp can be activated per channel • Galvanic isolation between the input and the
(only for ComUnits LB 8108) fieldbus (group isolation)
• Mounting outside hazardous areas • Simulation for commissioning and service
• Can be unplugged during operation
(hot swap)
• Input for NAMUR initiators, mech, contacts,
(forcing)
• Self configurating after replacement
(plug and play)
1
opto-couplers and active 24 V status signals • Permanent self-monitoring
• Positive or negative logic selectable • Module-TAG and channel-TAG
• Any slot position • EMV to EN 61 326 or NE21
Input:
potential free mech. contacts or 2-wire
Signal type
proximity switches to EN/IEC 60947-5-6 or NAMUR
On > 2.1 mA
Switching points
OFF < 1.2 mA
Hysteresis 0.2 mA
Digital input (active) 24 V 5V
switches On >8V > 2.7 V
OFF <3V < 2.3 V
Minimum pulse duration 1 ms
Operating frequency 10 Hz (depending on bus cycle time)
Sample rate (7 channels) approx. 1.5 ms
Sample rate gateway approx. 6.5 ms
Time stamp resolution (slave) approx.10 ms
Line fault detection (LFD) can be deactivated (only for NAMUR)
Filter ON Delay (avoids bounce)
Connection screw plug-in connector or cage clamp
Power consumption 0.6 W
Explosion Protection:
marking omitted
Ordering information
Category Type Order No.
Digital input, 7 channels omitted LB 1007 A GHG 127 0000 A1007
7 ch
1 3 5 7 8
2 4 6 8
7 ch
1 3 5 7 8
7 ch
+1 2 3 4 5 6 7 8 -
CH1 CH7
LB Remote I/O
1/13
LB 1108
Digital Input
8-channels
Product features
• Mounting in Zone 2 or Zone 22 or Div 2 or outside hazardous areas
• Any slot position
• Can be unplugged in Zone 2 during operation (hot swap)
• Inputs for NAMUR initiators, mechanical. contacts,
opto-couplers und active 24 V status signals
• Galvanic isolation between the input and the field bus
(group isolation)
• Simulation for commissioning and service (forcing)
• Self configurating after replacement
• Positive or negative Logic selectable depending on version
• Line monitor (LFD)
• Permanent self monitoring
• ON/OFF delay
• Modul-TAG and channel-TAG
• EMV to EN 61 326 or NE21
Eingang:
Volt-free mech. contacts or 2-wire proximity
switches acc. to DIN19 234 or NAMUR
Signal type
ON > 2.1 mA
OFF < 1.2 mA
Hysteresis 0.2 mA
Line fault (LFD) < 1 mA
short (LFD) > 6 mA
Digital input (active) 24 V 5V (non IS only)
ON > 8 V > 2.7 V
Switching points
OFF < 3 V < 2.3 V
Scanning time 6.5 ms
Power consumption 0.7 W
Explosion Protection:
Category II (1/2) GD [EEx ia] IIC
Approval PTB 03 ATEX 2042
Uo ) 15,3 V Io ) 16,1 mA Po ) 61,8 mW
IIC Safety values (linear)
Co ) 450 nF Lo ) 2 mH
Ordering details
Category Type Order No.
Digital input, 8 channel EEx ia LB 1108 A GHG 127 0000 A1108
Digital input, 8 channel – LB 1008 A GHG 127 0000 A1008
CH1 + - + - + - + - CH4
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
CH5 CH8
LB Remote I/O
1/14
LB 1014
Digital Input
15-channels, AC 95 – 230 V
Product features
• Mounting outside hazardous areas • Simulation for commissioning and service
• Can be unplugged during operation (hot swap) (forcing)
• Input for 230 V status information • Self configurating after replacement
(same phase)
• Positive or negative logic selectable
• Any slot position
(plug and play)
• Permanent self-monitoring 1
• Module-TAG and channel-TAG
• Galvanic isolation between the input • EMV to EN 61326 or NE 21
and the fieldbus (group isolation)
Input:
Signal type
Digital signals (active) AC 95 - 230 V (250 V max.)
overvoltage max. 400 V
switches ON > 90 V
OFF < 55 V
Input impedance 500 k1
Minimum pulse duration 2 periods
Step response (0 to 100 %) approx. 40 ms
Sample rate gateway approx. 6.5 ms
Line fault detection (LFD) omitted
Connection screw plug-in connector
channel 1-8 right, 9-15 left or cage clamp
Power consumption 0.6 W
Explosion Protection:
Marking omitted
Ordering Information
Category Type Order No.
Digital input, 15 channels
AC 95 - 230 V omitted LB 1014 A GHG 127 0000 A1014
L 9 10 11 12 13 14 15 16 N
R 1 2 3 4 5 6 7 8
LB Remote I/O
1/15
LB 1015
Digital Input
15-channels, DC 24 V
Product Features
• Montage outside hazardous areas • Simulation for commissioning and service
• can be unplugged during operation (hot swap) (forcing)
• Input for 24 V status information • Self configuration after replacement
• Positive or negative logic selectable (plug and play)
• Any slot position • Permanent self-monitoring
• Galvanic isolation between the input • Modul-TAG and channel-TAG
and the fieldbus (group isolation) • EMV to EN 61 326 or NE21
Input:
Signal type
Digital signals (active) DC 24 V (30 V max)
overvoltage max. 60 V
switches ON >8V
OFF <4V
Input impedance 10 k1
Minimum pulse duration 40 ms
Step response (0 to 24 V) approx. 40 ms
Sample rat gateway approx. 6.5 ms
Line fault detection (LFD) omitted
Connection screw plug-in connector
channel 1-8 right, 9-15 left or cage clamp
Power consumption 0.6 W
Explosion Protection:
Marking omitted
Ordering Information
Category Type Order No.
Digital input, 15 channels
DC 24 V omitted LB 1015 A GHG 127 0000 A1015
L 9 10 11 12 13 14 15 16 -
R 1 2 3 4 5 6 7 8
LB Remote I/O
1/16
Digital Output
Product Overview
Product features
• Mounting in Zone 2 or Zone 22 or Div 2
or outside hazardous areas
• Single channel high integrity or
8 channel compact modules
• Single channel and multi channel modules
1
can be mixed mounted
• Any slot position
• Can be unplugged in Zone 2 during operation
(hot swap)
• Output for intrinsically safe solenoid valves,
sounders and LEDs, relays for Ex-d solenoid
valves
• Modules are galvanically isolated per channel
or group isolated between output and system
bus
• Short circuit protected
• Simulation for commissioning and
service (forcing)
• Self configurating after replacement
• Positive- or negative logic selectable
depending on the version
• Line monitor depending on the version
• permanent self-monitoring
• ON/OFF-delay depending on the version
• Selectable output fault level depending
on the version
• Output with watch dog circuit for fatal errors
• Module-TAG and channel TAG depending
on the version
• Same number of modules with- and without
redundancy
• version dependancy see communits
• EMC to EN 61326 or NE21
Available modules
LB 2XZZ Digital output, 2 feed-back inputs
LB 6101 Relay output, 2 channels 24 V, isolated
LB 6005 Relay output, 4 channels 230 V, isolated
LB 6006 Relay output, 8 channels 24 V, isolated
LB 6X08 Digital output, 8 channels, group isolation
LB 6X10-6X15 Digital output, 4 channels, group isolation
Solenoid Sounder
valve
1/17
LB 2101 - 2113
Digital Output
with Position Feed Back
Product features
• Mounting in Zone 2 or Zone 22 or Div 2 • Line monitor (LFD)
or outside hazardous areas depending on version
• Output for intrinsic safety solenoid valves • Permanently self-monitoring
• Output for sounders and LEDs (without LFD) • Output with watch circuit for fatal errors
• Positive- or negative logic selectable • EMC to EN 61326 or NE21
Input:
Volt-free mech. contacts or 2-wire proximity
switches acc. to DIN19234 or NAMUR
Signal type
on > 2.1 mA
off < 1.2 mA
Hysteresis 0.2 mA
Line fault (LFD) < 1 mA
short > 6 mA
Output:
with line monitor (LFD) short circuit protected (see below)
Watch dog Output OFF 0.5 s after serious fault
Power consumption 0.52 W - 1.8 W depending on version
Explosion protection:
Category II (1/2) GD [EEx ia] IIC
Approval PTB 03 ATEX 2042
sensor circuit Uo ) 14 V, Io ) 16 mA, Po ) 55 mW
IIC Safety values (linear)
output circuit see table Co ) 418 nF, Lo ) 5 mH
Ordering details
Uout Ra/1 Limit/mA LFD/1 Uo/V IO/mA PO/mW CO/nF LO/mH Type Order No.
22.0 315 50 20...2000 24.9 91 558 79 1 LB 2101 A GHG 127 0000 A2101
24.0 210 75 1) 110...1200 27.8 183 1270 227 1) 1.9 1) LB 2102 A GHG 127 0000 A2102
24.0 360 50 70...2000 27.8 91.5 636 69 0.4 LB 2103 A GHG 127 0000 A2103
22.0 220 50 220...1300 24.2 145 872 92 0.27 LB 2104 A GHG 127 0000 A2104
22.0 220 50 2) 220...1300 24.2 145 872 92 0.27 LB 2104 C GHG 127 0000 C2104
22.8 290 50 150...2000 25.2 108 681 74 0.5 LB 2105 A GHG 127 0000 A2105
25.3 329 – 25...3500 27.8 108 751 81 0.19 LB 2112 A GHG 127 0000 A2112
25.3 329 – 2) 25...3500 27.8 108 751 81 0.19 LB 2112 C GHG 127 0000 C2112
26.7 509 – 40...7000 28.7 68 485 69 0.4 LB 2113 A GHG 127 0000 A2113
26.7 509 – 2) 40...7000 28.7 68 485 69 0.4 LB 2113 C GHG 127 0000 C2113
OUT
24.0 210 75 110...1200 – – – – – LB 2002 A GHG 127 0000 A2002
24.0 210 75 2) 110...1200 – – – – – LB 2002 C GHG 127 0000 C2002
1) 2)
only group II B output without line monitoring LFD no longer required since the test pulse
can be deactivated via software for modules delivered after March 07.
+1 –4 1 4
CH1 CH2 note: models 2106, 2107, 2108 have been dicontinued.
10k
2,2k
+ + + - - -
1 2 3 4 5 6
Ra
UOUT
LB Remote I/O
1/18
LB 2101 - 2103 - 2112 - 2113
Digital Output
with Shut Down Input
Product features
• Mounting in Zone 2 or Zone 22 or Div 2 • 2 digital inputs (valve position)
or outside hazardous areas • Line monitor (LFD)
• Output for intrinsic safety solenoid valves depending on the version
• Output for sounders and LEDs (without LFD)
• Positive- or negative logic selectable
• Permanently self-monitoring
• Output with watch dog circuit for fatal errors
• EMC to EN 61326 or NE21
1
• Shut down input independent of the bus
Input:
Volt-free mech. contacts or 2-wire proximity
switches acc. to DIN19234 or NAMUR
Signal type
on > 2.1 mA
off < 1.2 mA
Hysteresis 0.2 mA
Line fault (LFD) < 1 mA
short > 6 mA
Output:
with line monitor (LFD) short circuit protected (see below)
Watch dog Output OFF 0.5 s after serious fault
Power consumption 0.52 W - 1.8 W depending on version
Explosion protection:
Category II (1/2) GD [EEx ia] IIC
Approval PTB 03 ATEX 2042
sensor circuit Uo ) 14 V, Io ) 16 mA, Po ) 55 mW
IIC Safety values (linear)
output circuit see table Co ) 418 nF, Lo ) 5 mH
Ordering details
Uout Ra/1 Limit/mA LFD/1 Uo/V IO/mA PO/mW CO/nF LO/mH Type Order No.
22.0 315 50 20...2000 24.9 91 558 79 1 LB 2101 E GHG 127 0000 E2101
24.0 360 50 70...2000 27.8 91.5 636 69 0.4 LB 2103 E GHG 127 0000 E2103
24.0 360 502) 70...2000 27.8 91.5 636 69 0.4 LB 2103 G GHG 127 0000 G21032)
22.8 290 50 150...2000 25.2 108 681 74 0.5 LB 2105 E GHG 127 0000 E2105
25.3 329 – 25...3500 27.8 108 751 81 0.19 LB 2112 E GHG 127 0000 E2112
26.7 509 – 40...7000 28.7 68 485 69 0.4 LB 2113 E GHG 127 0000 E2113
2)
output without line monitoring LFD no longer required since the test pulse can be deactivated
via software for modules delivered after March 07.
OUT
+1 –4 1 4
CH1 CH2
10k
2,2k
+ + + - - -
1 2 3 4 5 6
LB Remote I/O
1/19
Transmitter Power Supply
Analog Input, HART
Product Overview
Product features
• Mounting in Zone 2 or Zone 22 or Div 2
or outside hazardous areas
• Single channel high integrity or
4 channel compact modules
• Single channel- and multi-channel modules
can be mixed mounted
• Any slot position
• Can be unplugged in Zone 2 during operation
(hot swap)
• Input for pressure, differential pressure, flow,
level and other 2-/4-wire transmitters
• Resolution 12 bit for 0-20 mA
• Single channel modules are galvanically
isolated between channels
• 4-channel modules are galvanically
isolated between input and system bus
(group isolation)
• Simulation for commissioning and
service (forcing)
• Self configurating after replacement
• HART communication on Profibus via FDT or
on servicebus (depends on version)
• Line monitor (LFD)
• permanently self-monitoring
• Module-TAG and channel-TAG
depending on version
• Same number of modules with- and without
redundancy
• Version dependancy see comm. units
• EMC to EN 61326 or NE21
Available modules
LB 3101 Analog input, 14.5 V
LB 3X02 Analog input, HART, 16 V
LB 3103 Analog input, HART, 15 V
LB 3X05 Analog input, HART, 4 chan., group isolation
Flow Level
Powered Hand-held
field devices configurator
1/20
LB 3101
Analog Input,
Transmitter Power Supply
Product features
• Mounted in Zone 2 or Zone 22 or Div 2 • Galvanic isolation between the input
or outside hazardous areas and the field bus
• Any slot position • Simulation for commissioning and service
• Can be unplugged in Zone 2 or 22
during operation (hot swap)
(forcing)
• Self configurating after replacement
• Line monitor (LFD)
1
• Power supply for 2-wire transmitters
• Input isolator for separately powered devices • Permanently self monitoring
• Module-TAG and channel-TAG
• EMC to EN 61326 or NE21
Input:
Field device power supply 14.5 V (20 mA)
Input range 4 - 20 mA (0 - 26 mA)
Input impedance (terminal 5-6) 15 1
Internal impedance (terminal 2-5) 315 1
Linearity < 0.1 %
Temperature drift < 0.1 % / 10 K
min. 1 mA
Line monitor
max. 22 mA programmable
Conversion time ) 50 msec
Power consumption 1.2 W
Explosion protection:
Category II (1/2) GD [EEx ia] IIC
Approval PTB 03 ATEX 2042
Uo ) 23.8 V Io ) 89.5 mA Po ) 534 mW
IIC Safety values (linear)
Co ) 87 nF Lo ) 0.5 mH
IIC Safety values Uo ) 0.7 V Io ) 3 mA Po ) 2 mW
(trapeze R i = 8.28 k) for input 5-6 Co ) 53 F Lo ) 50 mH Ci ) 1.65 nF
Ordering details
Category Type Order No.
Transmitter power supply Ex-i LB 3101 A GHG 127 0000 A3101
+
-
+
4 -20 mA
-
+
4 - 20 mA
1 2 3 4 5 6
LBLocal
Remote
BusI/O
1/21
LB 3102
HART
Analog Input
Transmitter Power Supply
Product features
• Mounted in Zone 2 or Zone 22 or Div 2 • Galvanic isolation between the input
or outside hazardous areas and the field bus
• Any slot position • Simulation for commissioning and service
• Can be unplugged in Zone 2 or 22 (forcing)
during operation (hot swap) • Self configurating after replacement
• Power supply for 2-wire transmitters (HART) • Line monitor (LFD)
• Input isolator for separately powered • Permanently self monitoring
devices (HART) • Module-TAG and channel-TAG
• EMC to EN 61326 or NE21
Input:
Field device power supply 16.5 V (20 mA) incl. 250 1
Input range 4 - 20 mA (0 - 26 mA) HART
Input impedance 15 1 (5 - 6) 236 1 (1- 6 HART)
Internal impedance (2-5) 315 1
Linearity < 0.1 %
Temperature drift < 0.1 % / 10 K
min. 1 mA
Line monitor
max. 22 mA programmable
Conversion time ) 50 msec.
Power consumption 1.2 W
Explosion protection:
Category II (1/2) GD [EEx ia] IIC
Approval PTB 03 ATEX 2042
Uo ) 27 V Io ) 92 mA Po ) 619 mW
IIC Safety values (linear)
Co ) 73 nF Lo ) 0.4 mH
IIC Safety values Uo ) 0.7 V Io ) 3 mA Po ) 2 mW
(trapeze R i = 8.28 k) for input 5-6 Co ) 53 F Lo ) 50 mH Ci ) 1.65 nF
IIC Safety values Uo ) 8.2 V Io ) 56 mA Po ) 310 mW
(trapeze R i = 447 1) for input 1-6 Co ) 1.1 F Lo ) 1 mH Ci ) 1.65 nF
Ordering details
Category Type Order No.
HART-analog input/transmitter power supply EEx ia LB 3102 A GHG 127 0000 A3102
HART-analog input/transmitter power supply – LB 3002 A GHG 127 0000 A3002
1+ HART -6
HART
LB Remote I/O
1/22
LB 3103
HART
Analog Input
Transmitter Power Supply
Product features
• Mounted in Zone 2 or Zone 22 or Div 2 • Galvanic isolation between the input
or outside hazardous areas and the field bus
• Any slot position • Simulation for commissioning and service
• Can be unplugged in Zone 2 or 22
during operation (hot swap)
(forcing)
• Self configurating after replacement
• Line monitor (LFD)
1
• Power supply for 2-wire transmitters (HART)
• Input isolator for separately powered • Permanently self monitoring
devices (HART) • Module-TAG and channel-TAG
• EMC to EN 61326 or NE21
Input:
Field device power supply 15 V (20 mA) incl. 250 1
Input range 4 - 20 mA (0 - 26 mA) HART
Input impedance 15 1 (5 - 6) 236 1 (1 - 6 HART)
Internal impedance (2-5) 315 1
Linearity < 0.1 %
Temperature drift < 0.1 % / 10 K
min. 1 mA
Line monitor
max. 22 mA programmable
Conversion time ) 50 msec.
Power consumption 1.2 W
Explosion protection:
Category II (1/2) GD [EEx ia] IIC
Approval PTB 03 ATEX 2042
Uo ) 24.9 V Io ) 77 mA Po ) 478 mW
IIC Safety values (linear)
Co ) 83 nF Lo ) 0.5 mH
IIC Safety values Uo ) 0.7 V Io ) 3 mA Po ) 2 mW
(trapeze R i = 8.28 k) for input 5-6 Co ) 53 F Lo ) 50 mH Ci ) 1.65 nF
IIC Safety values Uo ) 8.2 V Io ) 56 mA Po ) 310 mW
(trapeze R i = 447 1) for input 1-6 Co ) 1.1 F Lo ) 1 mH Ci ) 1.65 nF
Ordering details
Category Type Order No.
HART-analog input Ex-i LB 3103 A GHG 127 0000 A3103
1+ HART -6
HART
LB Remote I/O
1/23
LB 3104 - LB 3105
HART Transmitter Power Supply,
Analog Input,
4 Channels
Product features
• Mounting in Zone 2 or Zone 22 or Div 2 • Simulation for commissiong and service
or outside hazardous areas (forcing)
• Any slot position • Self configurating after replacement
• Can be unplugged in Zone 2 during operation • Line monitor (LFD)
• Power supply for 2 wire converters (HART) • Permanently self-monitoring
• Input isolator for powered devices • Module-TAG and channel-TAG
• HART via fieldbus or hand-held configurator • EMC to EN 61326 or NE21
• Galvanic isolation between the input and the
field bus (group isolation)
Input:
Power supply 15 V (20 mA) incl. 250 1
Input impedance 15 1 (stat.)
Input range 0/4 - 20 mA (0 ... 26 mA)
Linearity 0.1 %
Temperature drift 0.1 % / 10 K
min. 1 mA
Line monitor
max. 22 mA programmable
Scanning time 6.5 ms
Memory update time 80 ms (4 channels) 130 ms during HART
Power consumption 3W
Explosion protection:
Category II (1/2) GD [EEx ia] IIC
Approval PTB 03 ATEX 2042
Uo ) 28 V Io ) 90 mA Po ) 626 mW
IIC Safety values (linear)
Co ) 69 nF Lo ) 0.4 mH
IIC Safety values (trapeze R i = 7.1 k) Uo ) 0.7 V Io ) 2.3 mA Po ) 2 mW
for inputs 3-4, 7-8, 11-12, 15-16 Co ) 53 F Lo ) 50 mH Ci ) 1.2 nF
Ordering details
Category Type Order No.
Analog input, 4 chan. EEx ia LB 3104 A GHG 127 0000 A3104
HART analog input, 4 chan. EEx ia LB 3105 A GHG 127 0000 A3105
HART analog input, 4 chan. – LB 3005 A GHG 127 0000 A3005
Notes:
Supply circuits: 1-2, 5-6, 9-10, 13-14
active inputs: 3-4, 7-8, 11-12, 15-16 no HART
CH1 + - + - + - + - CH2
1 2 3 4 5 6 7 8
CH3 CH4
9 10 11 12 13 14 15 16
LB REMOTE I/O
1/24
Analog Output, HART
Product Overview
Product features
• Mounting in Zone 2 or Zone 22 or Div 2
or outside hazardous areas
• Single channel high integrity or
4 channel compact modules
• Single channel- and multi-channel modules
can be mixed mounted
1
• Any slot position
• Can be unplugged in Zone 2 during operation
hot swap
• Output for positioner, I/P converters, displays,
valves
• Resolution 12 bit for 0-20 mA
• Single channel modules are galvanically
isolated between channels
• 4-channel modules are galvanically isolated
between outputs and system bus
• Simulation for commissioning and service
(forcing)
• Self configurating after replacement
• HART communication via Profibus with FDT
or via service bus (depending on the version)
• Line monitor (LFD)
• Permanently self-monitoring
• Selectable output drive in case of fault
(depending on the version)
• Output with watchdog circuit for fatal errors
• Short circuit protected
• Module-TAG and channel-TAG
depending on the version
• Same number of modules with- and without
redundancy
• Version dependancy see comm. units
• EMC to EN 61326 or NE21
Available modules
LB 4101 Analog output, 750 1
LB 4X02 Analog output, HART, 750 1
LB 4X05 Analog output, HART, 4 chan., group isolation
Valve Positioner
I/P 0000
I/P converter Display
Hand-held
configurator
1/25
LB 4101
Analog Output
Product features
• Mounted in Zone 2 or Zone 22 or Div 2 • Galvanic isolation between the output
or outside hazardous areas and the field bus
• Any slot position • Simulation for commissioning and service
• Can be unplugged in Zone 2 or Zone 22 (forcing)
during operation (hot swap) • Self configurating after replacement
• Output isolator for 4-20 mA, indicators, • Line monitor (LFD)
positioners, I/P converters • Permanently self-monitoring
• Module-TAG and channel-TAG
• EMC to EN 61326 or NE21
Output:
Max. load 750 1
Output current 0/4 - 20 mA (short circuit protected)
Imin/max 0/25 mA (1 mA for LFD)
Linearity < 0.1 %
Temperature drift < 0.1 % / 10 K
Conversion time ) 50 msec.
Line monitor > 850 1 ... 4 k1
Watch dog output OFF 0.5 s after serious fault
Power consumption 0.8 W
Explosion protection:
Category II (1/2) GD [EEx ia] IIC
Approval PTB 03 ATEX 2042
Uo ) 27.3 V Io ) 87 mA Po ) 595 mW
IIC Safety values (linear)
Co ) 72 nF Lo ) 0.4 mH
Ordering details
Category Type Order No.
Analog output EEx ia LB 4101 A GHG 127 0000 A4101
0000
LB Remote I/O
1/26
LB 4102
HART
Analog Output
Product features
• Mounted in Zone 2 or Zone 22 or Div 2 • Simulation for commissioning and service
or outside hazardous areas (forcing)
• Any slot position • Self configurating after replacement
• Can be unplugged in Zone 2 or Zone 22
during operation (hot swap)
• Line monitor (LFD)
• Permanently self-monitoring
• Module-TAG and channel-TAG
1
• Output isolator for 4-20 mA, indicators,
positioners, I/P converters • EMC to EN 61326 or NE21
• Galvanic isolation between the output • Optional bus independant shut down
and the field bus
Output:
Max. load 750 1
Output current 0/4 - 20 mA (short circuit protected)
Imin/max 0/25 mA (1 mA for LFD)
Linearity < 0.1 %
Conversion time ) 50 msec.
Temperature drift < 0.1 % / 10 K
Line monitor > 850 1 ... 4 k1
Watch dog output OFF 0.5 s after serious fault
Power consumption 0.8 W
Explosion protection:
Category II (1/2) GD [EEx ia] IIC
0000 Approval PTB 03 ATEX 2042
Uo ) 27.3 V Io ) 87 mA Po ) 595 mW
IIC Safety values (linear)
Co ) 72 nF Lo ) 0.4 mH
HART
Ordering details
Category Type Order No.
HART analog output EEx ia LB 4102 A GHG 127 0000 A4102
HART analog output – LB 4002 A GHG 127 0000 A4002
HART analog out, shut-down input EEx ia LB 4102 C GHG 127 0000 C4102
LB Remote
LB/FB I/OI/O
Remote
0000
HART
LB Remote
LB/FB I/OI/O
Remote
regular version
1/27
LB 4104 - LB 4105
HART Analog Output
4 Channels
Product features
• Zone 2 or Zone 22 or Div 2 • Galvanic isolation between input and field bus
or non-hazardous area mounted (group isolation)
• Any slot position • Simulation for commissiong and service (forcing)
• Can be unplugged in Zone 2 during operation • Self configurating after replacement
• Output isolator for indicators, displays, • Line monitor (LFD) – version dependent
IP converters, positioners, valves • Permanently self-monitoring
• HART option via fieldbus or hand-held • Module-TAG and channel-TAG
configurator • Optional bus independent shut-down input
• EMC to EN 61326 or NE21
Output:
Max. load 750 1
Output current 4 - 20 mA (0 ... 25 mA) short protected
Linearity 0.1 %
Temperature drift 0.1 % / 10 K
Line monitor min. 1 mA (version dependent)
Threshold > 850 1
Watch dog circuit output OFF 0.5 s after serious faults
Scanning time 6.5 ms
58 ms (4 channels)
0000 Memory update time
110 ms (during HART communications)
Power consumption 3W
Explosion protection:
I/P Category II (1/2) GD [EEx ia] IIC
Approval PTB 03 ATEX 2042
Uo ) 27.3 V Io ) 93 mA Po ) 635 mW
IIC Safety values (linear)
Co ) 74 nF Lo ) 0.4 mH
+ – + – + – + –
1 2 3 4 5 6 7 8 Ordering details
CH1 CH4
Category Type Order No.
Analog output, 4-chan. EEx ia LB 4104 A GHG 127 0000 A4104
HART analog output, 4-channel EEx ia LB 4105 A GHG 127 0000 A4105
HART analog output, 4-channel – LB 4005 A GHG 127 0000 A4005
HART analog out, 4-chan. shut-down input EEx ia LB 4105 C GHG 127 0000 C4105
LB REMOTE HART analog out, 4-channel
with line monitor EEx ia LB 4105 D GHG 127 0000 D4105
shut down input option HART analog out, 4-channel
with line monitor – LB 4005 D GHG 127 0000 D4005
0000
I/P
+ – + – + – + –
1 2 3 4 5 6 7 8
CH1 CH4
LB REMOTE
regular version
1/28
RTD Transmitter,
Thermocouple Transmitter,
Voltage Converter
Product Overview
Product features
• Mounting in Zone 2 or Zone 22 or Div 2
or outside hazardous areas
• Single channel high integrity or
4 channel compact modules
• Single channel- and mult-channel modules
can be mixed
1
• Any slot position
• Can be unplugged in Zone 2 during operation
(hot swap)
• Input for RTD, thermocouples and DC-voltage
• Resolution 16 bit for the whole range
(lower depending on the span)
• Single channel modules are galvanically
isolated between channels
• 4-channel modules are galvanically isolated
between input and system bus
(group isolation)
• Simulation for commissioning and service
(forcing)
• Self configurating after replacement
• Line monitor (LFD)
• Permanently self-monitoring
• Module TAG and channel TAG depending
on the version
• Same number of modules with- and without
redundancy
• Version dependancy see comm. units
• EMC to EN 61326 or NE21
Available modules
LB 5X01 RTD transmitter
LB 5X02 thermocouple transmitter (mV)
LB 5X04 RTD transmitter 4 channels
LB 5X05 thermocouple transmitter (mV) 4 channels
CJC
LB 5X06 voltage converter (10 V)
Thermocouple Thermocouple
summator circuit
Thermocouple RTD
differential measurement 4-wire circuit
RTD RTD
3-wire circuit 2-wire circuit
1/29
LB 5101
RTD Transmitter
Product features
• Mounting in Zone 2 or Zone 22 or Div 2 • Simulation for commissioning and service
or outside hazardous areas (forcing)
• Any slot position • Self configurating after replacement
• Can be unplugged in Zone 2 • Line monitor (LFD)
during operation (hot swap) • Permanently self-monitoring
• Input for 2-, 3-, 4-wire RTD (temperature) • Module-TAG and channel-TAG
• Galvanic isolation between the input • EMC to EN 61326 or NE21
and the field bus
Input:
Range 10 - 400 1 (500 1 incl. wiring)
Smallest span 20 1 für 0.1 % accuracy
Wire resistance 50 1 max. each wire
Pt100 line fault (LFD) > 1 k1
short < 10 1
Linearity < 0.025 % (widest span)
Temperature drift < 0.025 %/10 K (widest span)
Sensor current 200 +A
< 20 ms without LFD
Conversion time
< 125 ms with LFD
Power consumption 0.45 W
Explosion protection:
Category II (1/2) GD [EEx ia] IIC
Approval PTB 03 ATEX 2042
Uo ) 2.7 V Io ) 43 mA Po ) 93 mW
IIC Safety values (trapeze Ri = 330 1)
Co ) 3 nF Lo ) 10 mH Ci ) 1.25 nF
Ordering details
Category Type Order No.
RTD transmitter EEx ia LB 5101 A GHG 127 0000 A5101
RTD transmitter – LB 5001 A GHG 127 0000 A5001
slide
wire
2 wire
3 wire
4 wire
1 2 3 4 5 6
mV
LB
FB Remote I/O
Remote I/O
1/30
LB 5102
Thermocouple
Transmitter, mV
Product features
• Mounting in Zone 2 or Zone 22 or Div 2 • Simulation for commissioning and service
or outside hazardous areas (forcing)
• Any slot position • Self configurating after replacement
• Can be unplugged in Zone 2
during operation (hot swap)
• Input for thermocouples or mV
• Line monitor (LFD)
• Permanently self-monitoring
• Module-TAG and channel-TAG
1
• Galvanic isolation between the input • EMC to EN 61326 or NE21
and the field bus
Input:
U, B, E, T, K, S, R, L, J, N, Pallaplat
Range
-75 mV .... + 75 mV
Compensation internal (at connector) or external
CJC Pt100 sensor current 200 +A
< 20 ms without LFD
Conversion time for external CJC
< 80 ms with LFD
< 120 ms without LFD
Conversion time for internal CJC
< 240 ms with LFD
Linearity < 0.1 % (at 5 mV span), 0.01 % (0-50 mV)
Temperature drift < 0.1 % / 10 K, 0,025 % (widest span)
Line fault (LFD) > 1 k1
Power consumption 0.45 W
Explosion protection:
Category II (1/2) GD [EEx ia] IIC
Approval PTB 03 ATEX 2042
Uo ) 1.8 V Io ) 43 mA Po ) 67 mW
IIC Safety values (trapeze Ri = 330 1)
Co ) 8.7 nF Lo ) 10 mH Ci ) 103 nF
Ordering details
Category Type Order No.
Thermocouple transmitter, mV EEx ia LB 5102 A GHG 127 0000 A5102
Thermocouple transmitter, mV – LB 5002 A GHG 127 0000 A5002
RTD
CJC
+ -
1 2 3 4 5 6
mV
LB
FB Remote I/O
Remote I/O
1/31
LB 5104
Pt100, Ni100, Slide Wire Sensors
4 Channels
Product features
• Mounting in Zone 2 or Zone 22 or Div 2 • Group isolation
or outside hazardous areas • Simulation for commissioning and service
• Any slot position (forcing)
• Can be unplugged in Zone 2 • Self configurating after replacement
during operation (hot swap) • Line monitor (LFD)
• 2-, 3-, 4-wire Pt100, Pt1000 (RTD) • Permanently self-monitoring
or slide wire sensors • Module-TAG and channel-TAG
• Galvanic isolation between the input • EMC to EN 61326 or NE21
and the bus
Input:
Pt100 range (-200 ... + 850 °C) 18 - 390 1 (500 1 incl. line)
Pt200 (37-780 1), Pt500 (92-1952 1)
Pt1000 (185-3905 1)
RTD Range
Ni100 (69-270 1), Ni500 (345-1350 1)
Ni1000 (690-2700 1)
Slide wire sensors 0 - 10000 1
Smallest span for 0.1 % 50 1 (or 1/10 of full scale)
Sensor current < 0.22 mA
Wire resistance < 50 1 each wire
Line break/short circuit programmable
Line break detection (Pt100) > 1 k1
Line short detection (Pt100) < 10 1
Non linearity 0.025 % of max. span
Temperature drift 0.025 % of max. span / 10 K
Scan time 6.5 ms
< 500 ms (4 channels)
Conversion time
< 1 s (for 4 x 3 wire Pt100)
Busy after download 5-15 s
Connection screw plug-in or wire clamp connectors
Power consumption 0.6 W
Explosion protection:
Category II (1/2) GD [EEx ia] IIC
Approval PTB 03 ATEX 2042
Uo ) 6.8 V Io ) 70 mA Po ) 118 mW
IIC Safety values (trapeze Ri = 103 1)
Co ) 1 F Lo ) 5 mH
Ordering details
2 wire
Category Type Order No.
Slide wire
RTD, slide wire transmitter, 4 channel Ex-i LB 5104 A GHG 127 0000 A5104
or RTD, slide wire transmitter, 4 channel – LB 5004 A GHG 127 0000 A5004
3 wire
Temperature 2 wire
3 wire
4 wire
CH1 CH2
1 2 3 4 5 6 7 8
+
9 10 11 12 13 14 15 16
CH3 CH4
LB Remote I/O
1/32
LB 5105
Thermocouples, mV
4 Channels
Product features
• Mounting in Zone 2 or Zone 22 or Div 2 • Simulation for commissioning and service
or outside hazardous areas (forcing)
• Any slot position • Self configurating after replacement
• Can be unplugged in Zone 2
during operation (hot swap)
• Thermocouples or mV signals
• Line monitor (LFD)
• Permanently self-monitoring
• Module-TAG and channel-TAG
1
• Galvanic isolation between the input • EMC to EN 61326 or NE21
and the bus and between channels
Input:
Thermocouples Type U, B, E, T, K, S, R, L, J, N, Pallaplat.
Measuring range -65 mV ... +75 mV
Smallest span for 0.1 % 5 mV
Compensation internal (built-in) or external (e.g. thermostat)
Line fault detection (LFD) > 1 k1
Non linearity 0.01 % (0-50 mV) or 0.025 % (of max. span)
Temperature drift 0.02 % / 10 K (0-50 mV)
Cycle time (com unit) 6.5 ms
< 200 ms (4 channels) without LFD
Conversion time
< 350 ms (4 channels) with LFD
Connection screw plug-in or wire clamp connectors
Test voltage 1.5 kV input - input
1.5 kV input - bus and power
Power consumption approx. 1 W
Explosion protection:
Category II (1/2) GD [EEx ia] IIC
Approval PTB 03 ATEX 2042
Uo ) 1 V Io ) 71 mA Po ) 62 mW
IIC Safety values (trapeze Ri = 500 1)
Co ) 33 F Lo ) 5 mH
Ordering details
Category Type Order No.
Thermocouple transmitter, 4 channel EExia LB 5105 A GHG 127 0000 A5105
Thermocouple transmitter – LB 5005 A GHG 127 0000 A5005
CH1 CH2
1 2 5 6
+ +
9 10 13 14
CH3 CJC
VST CH4
FIELD BUS
1/33
LB 5106
Voltage Converter
Product features
• Mounting in Zone 2 or Zone 22 or Div 2 • Simulation for commissioning and service
or outside hazardous areas (forcing)
• Any slot position • Self configurating after replacement
• Can be unplugged in Zone 2 • Permanently self-monitoring
during operation (hot swap) • Module-TAG and channel-TAG
• Input for voltage signals • EMC to EN 61326 or NE21
• Galvanic isolation between the input
and the field bus
Input:
Range 0 .... +10 V
Smallest span for 0.1 % 500 mV
Input impedance 100 k1
Line fault detection (LFD) None
Linearity < typ. 0,1 %
Temperature drift < 0.1 % / 10 K
Conversion time 100 ms
Power consumption < 0.45 W
Explosion protection:
Category II (1/2) GD [EEx ia] IIC
Approval PTB 03 ATEX 2042
Uo ) 0.9 V Io ) 0.2 mA Po ) 0.2 mW
IIC Safety values (linear)
Co ) 53 F Lo ) 100 mH Ci ) 52 nF
Ordering details
Category Type Order No.
Voltage converter EEx ia LB 5106 A GHG 127 0000 A5106
Voltage converter – LB 5006 A GHG 127 0000 A5006
+ -
1 2 3 4 5 6
LB Remote I/O
1/34
Digital Output
Product Overview
Product features
• Mounting in Zone 2 or Zone 22 or Div 2 or
outside hazardous areas
• Single channel high integrity or
8 channel with compact modules
• Single channel- and mult-channel modules
can be mixed
1
• Any slot position
• Can be unplugged in Zone 2 during operation
(hot swap)
• Output for intrinsically safe solenoid valves,
sounders, and LEDs, relays for Ex-d solenoid
valves
• Modules are galvanically isolated between
channels or galvanically isolated between
input and system bus (group isolation)
• Simulation for commissioning and service
(forcing)
• Self configurating after replacement
• Positive or negative logic selectable
depending on the version
• Line monitor (LFD) depending on the version
• Permanently self-monitoring
• ON/OFF delay depending on the version
• Output level selectable on fault condition
depending on the version
• Output with watch dog circuit for fatal errors
• Module TAG and channel TAG depending on
the version
• Same number of modules with and without
redundancy
• Version dependancy see comm. units
• EMC to EN 61326 or NE21
Available modules
LB 2XZZ digital output, 2 feed-back inputs
LB 6101 relay output, 2 channels 24V, isolated
LB 6005 relay output, 4 channels 230V, isolated
LB 6006 relay output, 8 channels 24V, isolated
LB 6X08 digital output, 8 channels, group isolation
LB 6X10-6X15 digital output, 4 channels, group isolation
Solenoid Sounder
valve
1/35
LB 6101
Relay Output
2 Channels
Product features
• Mounting in Zone 2 or Zone 22 or Div 2 • Galvanic isolation between outputs and
or outside hazardous areas the field bus
• Any slot position • Simulation for commissiong and service
• Can be unplugged in Zone 2 during operation (forcing)
conditional hot swap see instructions • Self configurating after replacement
• Relay output for Ex-d valves, trip points, • Permanently self-monitoring
indicators, general purpose switching • output watch dog
functions • Module-TAG and channel-TAG
• EMC to EN 61326 or NE21
Output:
Relay rating
Voltage rating (nominal) 24 V DC/AC (30 Vmax.)
Current rating 1 A DC/AC (resistive load)
Switch power Pmax. 30 W/VA
Electrical lifetime 0.5 Mio. cycles
Min. switching capability > 1 V, > 1 mA
Contact material AgPd gold plated
Watch dog output OFF 0.5 s after serious fault
Response time < 20 ms (depending on bus cycle time)
Power consumption 0.65 W
Explosion Protection:
Category II 3 GD EEx nA CII T4
Approval PTB 99 ATEX 2186
Ordering details
Category Type Order No.
Relay output, 2-channel – LB 6101 A GHG 127 0000 A6101
Relay output, 2-channels,
230 V, 1A (ohmic load) – LB 6101 H GHG 127 0000 H6101
HE HE
1 2 3 4 5 6
CH1 CH2
FIELD BUS
1/36
LB 6005
Relay Output
4 Channels
Product features
• Mounting in Zone 2 or Zone 22 or Div 2 • Positive- or negative logic selectable
or outside hazardous areas • Permanently self-monitoring
• Output with relay-contacts for LEDs, • ON/OFF delay
annunciators or valves
• Any slot position
• Galvanic isolation between outputs
•
•
Module TAG and channel-TAG
EMC to EN 61326 or NE21 1
• Simulation for commissiong and service
(forcing)
• Self configurating after replacement
Output:
30 V DC, 1 A, 30 W (resistive load)
Relay contact/channel
230 V AC, 1 A, 250 VA (resistive load)
Contact material AgPd gold plated
Electrical lifetime 0,1 Mio. cycles
Min. switching capability > 1 V, > 1 mA
Response time approx. 20 ms (depending on bus cycle time)
Scanning time 6.5 ms
Relay off 0.5 sec.
Watch dog circuit
after serious faults
Power consumption 1.2 W
Explosion Protection:
Category II 3 GD EEx nA CII T4
Approval PTB 99 ATEX 2186
Ordering details
Category Type Order No.
Relay 230 V AC, 4-channels – LB 6005 A GHG 127 0000 A6005
HE HE
CH1 1 2 3 4 5 6 7 8 CH2
CH3 9 1011 121314 15 16 CH4
FIELD BUS
1/37
LB 6006
Relay Output
8 Channels
Product features
• Mounting in Zone 2 or Zone 22 or Div 2 • Positive- or negative logic selectable
or outside hazardous areas • Permanently self-monitoring
• Output with relay-contacts for LEDs, • ON/OFF delay
annunciators or valves • Module TAG and channel-TAG
• Any slot position • EMC to EN 61326 or NE21
• Galvanic isolation between outputs
• Simulation for commissiong and service
(forcing)
• Self configurating after replacement
Output:
Relay contact/channel 24 V AC/DC, 1 A, 30 W, 30 VA (resistive load)
Contact material AgPd gold plated
Electrical lifetime 0.5 Mio. cycles
Min. switching capability > 1 V, > 1 mA
Response time approx. 20 ms (depending on bus cycle time)
Scanning time 6.5 ms
Relay OFF 0.5 Sec.
Watch dog circuit
after serious faults
screw plug in or
Connection
wire clamp
Power consumption 1.6 W
Explosion Protection:
Category II 3 GD EEx nA CII T4
Approval PTB 99 ATEX 2186
Ordering details
Category Type Order No.
Relay 24 V AC/DC, 8-chan. – LB 6006 A GHG 127 0000 A6006
HE HE
CH1 1 2 3 4 5 6 7 8 CH4
CH5 9 1011 121314 15 16 CH8
FIELD BUS
1/38
LB 6108
Digital Output
8 Channels, Low Power
Product features
• Mounting in Zone 2 or Zone 22 or Div 2 • Self configurating after replacement
or outside hazardous areas • Positive- or negative logic selectable
• Any slot position • Line monitor (LFD)
• Active 20 V output to switch LEDs, indicators,
or low power solenoid valves
• Can be unplugged in Zone 2 during operation
•
•
•
Permanently self-monitoring
ON/OFF delay
shut down input
1
• Galvanic isolation between the output and the • Module TAG and channel-TAG
field bus (group isolation) • EMC to EN 61326 or NE21
• Simulation for commissiong and service
(forcing)
Output:
Digital output (active/short protected) 20 V, 8 mA per channel
21.6 V/5.2 mA (model C6108)
Scanning time 6.5 ms
LFD test current 0.33 mA
output volt-free 0.5 sec.
Watch dog circuit
after serious faults
Power consumption 2.2 W
Explosion protection:
Category II (2) GD [EEx ib] IIC
approval PTB 03 ATEX 2042
IIC safety values (rectangular) model A6108 Uo ) 28 V Io ) 13.5 mA Po ) 376 mW
Co ) 76 nF Lo ) 0.5 mH
IIC safety values (rectangular) model C6108 Uo ) 30 V Io ) 13.5 mA Po ) 404 mW
Co ) 62 nF Lo ) 0.5 mH
Ordering details
Category Type Order No.
Digital output, 8-channels EEx ib LB 6108 A GHG 127 0000 A6108
Digital output, 8-channels – LB 6008 A GHG 127 0000 A6008
Digital output, 8-chan., 21.6 V EEx ib LB 6108 C GHG 127 0000 C6108
CH1 1 2 3 4 5 6 7 8 CH4
CH5 9 1011 121314 15 16 CH8
+ + + + –
FIELD BUS
1/39
LB 6110 - LB 6115
Digital Output
4-channels, IS power
Product features
• Mounting in Zone 2 or Zone 22 or Div 2 • Self configuration after replacement
or outside hazardous areas (plug and play)
• Output for intrinsically safe solenoid valves, • Permanently self monitoring
for sounders and LEDs • ON/OFF delay
• Positive or negative logic selectable • optional Shut down input independent
• any slot position of the bus
• galvanic isolation between outputs • Output with watch dog circuit for fatal errors
and BUS (group isolation) • Module-TAG and channel-TAG
• Simulation für commissioning and service • EMV to EN 61 326 or NE21
(forcing)
Power Supply:
External Power 24 V DC, 9 W via Booster connection on
Backplanes LB 9022, 9023, ..25, ..26, ..27, ..29
Slave can be fully fitted even in combination
with other modules.
Output:
Drive capability see ordering details
Line monitor (2ms test pulse) every 2,5 a (LFD can bei deactivated)
LFD reaction time 10 s (worst case) 10 s (worst case)
Output response time > 10 ms (depending on the master)
Scan rate 6,5 ms
Watch dog Output OFF 0.5 s
after serious fault.
Connection screw plug-in
or wire clamp connectors
Power consumption 0.6 W
Explosion protection:
Category II (2/1) GD [EEx ia/ib] IIC
Approval PTB 03 ATEX 2042
CH1 1 2 3 4 5 6 7 8 CH4
Safety values see ordering details
+ - + - + - + -
FIELD BUS
regular
regular version
version
1/40
Gateway or ComUnit Properties
Selection Guide
The following table is intended to assist you in finding the best gateway or ComUnit for your
application.
Gateways LB 8103 or FB 8203 only support single width modules. All other gateways support
single channel high integrity modules as well as dual width multi channel modules. LB 8103 or FB
8203 are available mainly as replacements. Gateways LB 8106, FB 8206 are mainly used when the
DCS prefers to configure the slaves on the basis of the GSE file only. This is possible with any
1
system which supports Profibus.
Profibus systems which offer more can make use of the superior properties of the UniCOM gateways
LB 8109 or FB 8209 (e.g. FDT or Siemens (PDM)). These are compatible with LB 8105 or FB 8205
gateways offering additional CiR functionality independent of the process control system or PLC
(ONLINE configuration). LB 8105 or FB 8205 are mostly used in connection with ABB systems.
Gateways LB 8107 and FB 8207 are reserved for MODBUS applications.
Gateways LB 8108 are mainly used in connection with NON intrinsically safe applications, where a
large number of digital inputs have to be processed.
Hardware Zone 2 GHG 127 0xxx H 8103 H 8105 H 8106 H 8107 H 8108 H 8109
Hardware Zone 1 GHG 127 0xxx H 8203 H 8205 H 8206 H 8207 H 8209
Properties/Firmware Version 4.X 6.X 6.X 7.X 8.X 9.X
Configuration software or DTM for FDT098 4/5/6 6 6
Configuration software or DTM for FDT1.2 7 ❍ ❍ 7 7
Configuration tool acts as Profibus Simulator PACTware EasyCom PACTware PACTware
Servicebus required
Servicebus useable ● ● ❍ ● ❍ ●
HART via Servicebus ❍ ❍ ❍ ❍ ❍
HART via Profibus ● ● ● ● ●
HART secondary variables synchronous data ❍ ❍ ❍ ❍ ❍
GSD/GSE file CGV40710 CGV61710 CGV61711 CGV61712 CGV61710
Profibus DP ● ● ● ● ●
Profibus DPV1 ● ● ● ● ●
Modbus ●
Redundancy ❍ ● ● ❍ ❍ ●
HCiR (system dependent ONLINE configuration) ● ● ● ● ● ●
CiR (system independent ONLINE configuration) ●
Time stamping (in cooperation with master) ●
1x01, 1x02, 1x03 ● ● ● ● ● ●
1x08 ● ● ● ● ●
1x07, 1x14, 1x15 ❍ ❍ ❍ ● ❍
2xxx, 2xxx (SIL) ● ● ● ● ● ●
3x01, 3x02, 3x03 ● ● ● ● ● ●
3x04, 3x05 ● ● ● ● ●
4x01, 4x02,4x02 (SIL) ● ● ● ● ● ●
4x04, 4x05,4x05 (SIL) ● ● ● ● ●
4x05 (LFD) ❍ ❍ ❍ ❍ ● ❍
5x01, 5x02 ● ● ● ● ● ●
5x04, 5x05 ● ● ● ● ●
5x06 ● ● ● ● ● ●
6x01 ● ● ● ● ● ●
6x04, 6x05, 6x06, 6x08, 6x08 (SIL) ● ● ● ● ●
6x10, 6x11, 6x12, 6x13, 6x14, 6x15 ● ● ● ● ●
6x10-6x14, 6x15 (SIL) ● ● ● ● ●
Analog chan. (max. depends on configuration) 48 80 80 80 80 24-80
Digital chan. (max. depends on configuration) 144 184 184 184 184 96-184
1/41
LB 8101 - LB 8104
Communication
Interface
only for replacements
Product features
• Mounting in Zone 2 or Div 2 or outside • non volatile memory for configurating and
hazardous areas parameter settings
• Can be unplugged in Zone 2 during operation • LED diagnostic indication
(hot swap) • HART communication on Profibus or service
• bumpless transition in redundant systems bus depending on the version
• self configurating in a redundant system • EMC to EN 61326 and NE21
(plug and play as from version V4.X)
Technical data
Profibus DP, DPV1, MODBUS RTU, Modicon,
Fieldbus connection
others upon enquiry
Profibus 1500 kBaud
Transferrate
ModBus 38,4 kBaud
Power consumption 2W
defined by the field bus standard
Max. number of slaves per busline
255 (ModBus), 125 (Profibus)
Number of slaves per bus segment max. 31
Repeaters between Master-Slave max. 3
depending on the comm unit version
Number of channels per substation
48-80 analog max., 144-184 digital max.
9-pole bus connector to RS485 standards
Connections via Backplane
power via power supply modules
FOL (fibre optic link) additional hardware required
maximum bus extension (FOL) 1000 m (1.5 MBaud)
1000 m (187.5 kBaud)
maximum bus extension (copper)
200 m (1.5 MBaud)
Address setting via configuration software
Profibus DPV1 to standard (address 126 ex works)
Redundant comm unit automatic as from version V4.X
Servicebus address max. 119
Explosion protection:
Category II 3G EEx nA II T4
Approval PTB 99 ATEX 2186
Ordering details
ComUnits for 48 analog/144 digital channels
HART via Servicebus Type Order No.
+P +P Redundant comm units can also be configured for non redundant systems.
Comm units can be converted from Profibus DP to ModBus or vice versa.
Comm units Type LB 8101 and LB 8102 are replaced by LB 8109 and LB 8107.
The order number in front of the code letter „A“ indicates the Firmware and the
LB Remote I/O LB Remote I/O corresponding configuration software. „X“ == reserves space for the version number.
HART Communication is possible via the servicebus using the appropriate software
of reknowned manufacturers.
1/42
LB 8103 - LB 8105
Communication
Interface
Product features
Various communication modules are available Existing comm units therefore have to be fitted
depending on the application. with the appropriate firmware when newly
Comm units are downwards compatible if kept developed I/O modules are to be employed.
within one series. Firmware Updates are
possible within such a series. Thus comm units
using Firmware 3.09 can be updated to 3.22.
The CDROM supplied with deliveries contains a
README file which lists the supported I/O
modules and properties for each firmware version.
1
In the same way versions 4.14 can be updated Please also ensure compatibilty for the
to 4.30. configuration software. CDROM versions 3.X are
Updates offer advantages if the master also meant for comm unit versions 3.X only etc.
supports the new properties. Therefore CEAG Profibus applications require a GSE-file
strives to implement integration tests with the (GSE = English GSD) also to be found on the
master prior to new releases. CDROM unless you are using a DPV1 master.
Different comm units can operate on the same Profibus DPV1 applications employing the FDT
bus as long as the conditions are observed concept transfer field device properties to the
which are detailed in the manuals. However, in master during the installation of the DTM (Device
a redundant slave you must only use comm Type Manager). Other system manufacturers
units with identical versions. make use of software drivers e.g. Siemens
Comm units always have to relate to the PDM V5.2.
connected I/O modules.
Ordering details
ComUnits for 48 analog/144 digital channels
HART via Profibus Type Order No.
Profibus (any master) or LB 8103 H 04XX GHG 127 04XX H8103
Profibus DPV1 compatible master only for replacement
Redundancy and HCIR master dependant
Redundant comm units can also be configured for non redundant systems.
The order number in front of the code letter „H“ indicates the Firmware and the corresponding
configuration software. „X“ = reserves space for the version number.
Different ComUnits can be used on the same bus. Only use identical ComUnits within a redundant
slave.
Factory setting: redundant system to be converted to single operation via mouseclick.
ComUnits / gateways LB 8103 are superseded by LB 8105 or LB 8109.
HART Communication on Profibus is possible even for systems which do not support this feature
themselves. In that case a class 2 master is used.
1/43
LB 8106
EasyCom Com Unit with Standard
GSE-Parameterization
Product features
• DCS configuration via GSE parameters (plug and play)
• automatic data exchange (Standard Profibus)
• supports 1-8 channel I/O modules (multi channel)
• mounted in Zone 2 or outside hazardous areas
• can be unplugged in Zone 2 during operation (hot swap)
• ON/OFF delay for digital inputs (Filter, pulse extension)
• self configurating in a redundant system (plug and play)
• drives outputs to a defined position in case of failure
• non volatile memory for configuration and parameter settings
• LED diagnostic indication
• HART communication on Profibus
• optional servicebus for extended diagnostics and commissioning (forcing)
• EMC to EN 61326 and NE21
Technical data:
Fieldbus connection Profibus DP, DPV1
others upon enquiry
HART communication to PNO Standard
Transferrate Profibus up to 1500 kBaud
Power consumption 2W
Max. number of slaves per busline defined by fieldbus specification
125 (Profibus), 119 (Servicebus)
Number of slaves per bus segment max. 31 (RS485 Standard)
Repeaters between Master-Slave max. 3
Number of channels per substation depending on the modules
max. 80 analog, 184 digital
Backplane Connections 9-pole bus connector to RS485 Standard
power via power supply modules
FOL (fibre optic link) additional hardware required
maximum bus extension (FOL) 1000 m (1.5 MBaud)
maximum bus extension (copper) 1000 m (187.5 kBaud)
200 m (1.5 MBaud)
Address setting via P+F configuration software or
DP Master-Set Slave Address
Profibus address standard compliant (ex works addr. 126)
Redundant comm unit address automatic
Servicebus address max. 119
Explosion protection:
Category II 3 G EEx nA II T4
Approval PTB 99 ATEX 2186
Different comm units can be used on the same bus. Only use identical comm units within
LB Remote I/O LB Remote I/O a redundant slave.
Factory setting: single system to be converted to redundant operation via mouseclick.
1/44
LB 8107
Com Unit for Standard
MODBUS RTU
Product features
• MODBUS communication
• supports 1-8 channel I/O modules (multi channel)
• mounted in Zone 2 or outside hazardous areas
•
•
•
can be unplugged in Zone 2 during operation (hot swap)
ON/OFF delay for digital inputs (Filter, pulse extension)
self configurating in a redundant system (plug and play)
1
• drives outputs to a defined position in case of failure
• non volatile memory for configuration and parameter settings
• LED diagnostic indication
• HART communication on MODBUS
• optional servicebus for extended diagnostics and commissioning (forcing)
• EMC to EN 61326 and NE21
Technical data:
Fieldbus connection MODBUS
others upon enquiry
HART communication via MODBUS
Transferrate MODBUS 38.4 kBaud
Power consumption 2W
Max. number of slaves per busline defined by fieldbus specification
247 (MODBUS), 119 (Servicebus)
Number of slaves per bus segment max. 31 (RS485 Standard)
Repeaters between Master-Slave max. 3
Number of channels per substation depending on the modules
max. 80 analog, 184 digital
Backplane Connections 9-pole bus connector to RS485 Standard
power via power supply modules
FOL (fibre optic link) additional hardware required
maximum bus extension (FOL) 1200 m (38.4 kBaud)
maximum bus extension (copper) 1200 m (38.4 kBaud)
Address setting via P+F configuration software
MODBUS address standard compliant (ex works addr. 125)
Redundant comm unit address automatic
Servicebus address max. 119
Explosion protection:
Category II 3 G EEx nA II T4
Approval PTB 99 ATEX 2186
Ordering details
Primary comm unit Redundant comm unit ComUnits for 80 analog/184 digital channels
with Standard MODBUS Parameterization
Fieldbus Redundant bus
Service bus Service bus Model Order No.
local connection
MODBUS (any Master) LB 8107 H07XX GHG 127 07XX H 8107
Note:
LB Remote I/O LB Remote I/O Redundancy and HART require an integration test with the master system.
1/45
LB 8108
ComUnit for Profibus DP/DPV1
with time stamp option
Product Features
• Configuration from the DCS or PLC using GSE parameters (plug and play)
• fast track to data exchange (standard Profibus)
• supports 1-15 channel I/O modules (multi channel)
• mounted in Zone 2 or Zone 22 or Div 2 or outside hazardous areas
• can be unplugged in Zone 2 during operation (hot swap)
• ON/OFF delay for digital inputs (Filter, pulse extension)
• self configuration in a redundant system (plug and play)
• drives outputs to a defined position in case of failure
• non volatile memory for configuration and parameter settings
• LED diagnostic indication
• HART communication on Profibus
• optional servicebus for extended diagnostics and commissioning (forcing)
• EMC to EN 61326 and NE21
Technical data:
Fieldbus connection Profibus DP, DPV1
HART communication to PNO Standard
Transferrate Profibus up to 1500 kBaud
Power consumption 2W
Max. number of slaves per busline defined by fieldbus specification
125 (Profibus), 119 (Service bus)
Number of time stamps 200 using digital input LB 1007 (7-channels)
Time stamp resolution 10 ms (depending on master)
Number of slaves per bus segment max. 31 (RS485 Standard)
Repeaters between Master-Slave max. 3
Number of channels per substation depending on the configuration
max. 80 analog, 184 digital
Backplane Connections 9-pole Bus connector to RS485 Standard
power via power supply modules
FOL (fibre optic link) additional hardware required
maximum bus extension (FOL) 1000 m (1.5 MBaud)
maximum bus extension (copper) 1000 m (187.5 kBaud)
200 m 1.5 MBaud)
Address setting via configuration software or DP master
Profibus address standard compliant (ex works addr 126)
Redundant comm unit address automatic
Servicebus address max. 119
Explosion protection:
Category II 3 G EEx nA II T4
EC Conformity Declaration PTB 99 ATEX 2186
LB Remote I/O LB Remote I/O HART Communication on Profibus is possible e.g. for ABB systems or Siemens PDM or
Emerson AMS or E&H FieldCare or PACTware. Secondary HART variables can be mapped
to the Profibus data exchange at request.
Different comm units can be used on the same bus. Only use identical comm units within a
redundant slave.
Block diagram of redundant comm units Factory setting: redundant system to be converted to single operation via mouseclick.
1/46
LB 8109
UniCOM ComUnit for Profibus DP/DPV1
with ONLINE Configuration (CiR)
Product Features
• ONLINE DCS configuration (with or without redundancy)
• fast track to data exchange (using universal setting)
• supports 1-8 channel I/O modules (multi channel)
•
•
•
mounted in Zone 2 or outside hazardous areas
can be unplugged in Zone 2 during operation (hot swap)
ON/OFF delay for digital inpuls (Filter, pulse extension)
1
• self configuration in a redundant system (plug and play)
• drives outputs to a defined position in case of failure
• non volatile memory for configuration and parameter settings
• LED diagnostic indication
• HART communication on Profibus
• optional servicebus for extended diagnostics and commissioning (forcing)
• EMC to EN 61326 and NE21
Technical Data:
Fieldbus connection Profibus DP, DPV, other upon enquiry
HART communication to PNO Standard
Transferrate Profibus up to 1500 kBaud
Power consumption 2W
Max. number of slaves per busline defined by fieldbus specification
125 (Profibus), 119 (Servicebus)
Number of channels (120 Byte In/out) combined configuration possible, otherwise
with standard configuration 80 analog, 184 digital (single+multi channel)
with universal 2l20 setting 48 analog, 184 binär (single+digital multi chan.)
with universal 4l40 setting 60 analog, 120 binär (single+multi channel)
Number of slaves per bus segment max. 31 (RS485 Standard)
Repeaters between Master-Slave max. 3
Number of channels per substation depending on the configuration
max. 80 analog, 184 digital
Backplane Connections 9-pole bus connector to RS485 Standard
power via power supply modules
FOL (fibre optic link) additional hardware required
maximum bus extension (FOL) 1000 m (1.5 MBaud)
maximum bus extension (copper) 1000 m (187.5 kBaud)
200 m (1.5 MBaud)
Address setting via configuration software or
Profibus address standard compliant (ex works addr. 126)
Redundant comm unit address automatic
Servicebus address max. 119
Explosion protection:
Category II 3 G EEx nA II T4
Primary comm unit Redundant comm unit EC Conformity Declaration PTB 99 ATEX 2186
A universal setting allows you to configure a running system without the obligatory Profibus restart
even in non redundant systems (CiR functinality).
LB Remote I/O LB Remote I/O
HART Communication on Profibus is possible e.g. for ABB systems or Siemens PDM or
Emerson AMS or E&H FieldCare or PACTware. Secondary HART variables can be mapped
to the Profibus data exchange at request.
Different comm units can be used on the same bus. Only use identical comm units within a
Block diagram of redundant comm units
redundant slave.
Factory setting: redundant system to be converted to single operation via mouseclick.
1/47
LB 9006
24 V DC Power Supply
Product features
• Mounting in Zone 2 or Div 2 or outside hazardous areas
• Can be plugged in during operation in Zone 2 for servicing (observe conditions)
• Supplies 12 I/O modules and a comm unit
• Galvanic isolation to line
• EMC to EN 61326 or NE21
• Redundant supply of the comm. interface and I/O-modules possible
• Green Power-On LED
Technical data:
Power supply
DC voltage 24 V DC, 18 ... 30 V
Internal fuse 3.15 A mtg
Start up current 34 A (20 ms)
Power consumption max. 29 W
Power consumption of a
substation with 22 slots max. 58 W (2 power supplies)
substation with 46 slots max. 116 W (4 power supplies)
When fitted with predominantly digital
inputs the power consumption is markedly
lower. See manual for details.
screw terminals at the right end of the
Power supply
backplane (max. 1.5 mm2)
can be fed from 2 separate power lines.
3 power supplies can be connected in parallel.
Redundancy
No adverse effect on the substation if one of
the 3 power supplies fails. (high integrity)
only with base unit LB 9022 and
Application
extension unit LB 9024
Explosion protection:
Category II 3 G D EEx nA II T3
Approval PTB 99 ATEX 2186
Ordering details
Function Type Order No.
24 V DC power supply LB 9006 A GHG 127 0000 A9006
input output
24 V 12 V 5 V
+ - + + -
1/48
LB 9104
24 V DC Power Supply
only for LB 9101, LB 9121
Product features
• Mounting in Zone 2 or outside hazardous areas
• Can be plugged-in during operation for service in Zone 2 (observe conditions)
• Supplies 8 I/O modules and a communication unit
•
•
•
Galvanic isolation in the I/O modules and in the communication unit
EMC to EN 61326 or NE21
Redundant supply of comm. units
1
through 2 power supplies in the first 2 segments
• Green Power-On LED
Technical data:
Power supply
DC voltage 24 V DC, 20 ... 30 V
Internal fuse 3.15 A mtg
Start up current 15 A (20 ms)
Power consumption max. 12 W
Power consumption of a
substation with 24 E/A max. 32 W (3 power supplies)
substation with 48 E/A max. 62 W (6 power supplies)
When fitted with predominantly digital inputs,
the power consumption is markedly lower/
see manual for details
Screw terminals on the left and right-hand
Power supply
end piece of the backplane (max. 1.5 mm2)
redundant supply of comm units
through 2 power supplies
Redundancy in the first 2 segments.
substation power redundancy only with LB 9006
and backplanes LB 9022 and LB 9024
preferably with LB 9101 and LB 9103.
In rare cases useable with base unit
Application
LB 9022 and extension unit
LB 9024
Additional function
Segmentation Substations are subdivided into 1 to 6 segments
thus achieving a high availability
Should one power supply fail, max. 8 modules
will be affected.
Selector The power supply module houses the
selector for the data transfer to 8 modules
each. Should one module fail, no other
slots will be affected. At the same time,
the selector ensures that the modules
are self configurating and that no
setting-up is required when replacing a
module.
Explosion protection:
Category II 3 G D EEx nA II
Approval PTB 99 ATEX 2186
input output
24 V 12 V 5 V Ordering details
+ - + + -
Function Type Order No.
24 V DC power Supply LB 9104 A GHG 127 0000 A9104
1/49
LB 9X01 - 9X99
Backplane, Segments,
Accessories
Unit structure
max. 6 backplane segments LB 9101 in a row
ComUnits LB 9104
LB 8101 to 8109 power supply
1
Single channel -
2
multi channel can be mounted
in any order 3 5 7
6
4
1 Primary bus
2 Redundant bus
3 Service bus
4 supply terminals (24 V DC)
5 LB 9102 left end segment
6 LB 9101 backplane segment
7 LB 9103 right end segment
ComUnits LB 9006
LB 8103 to 8109 power supply
5 6 7 8 9
1
2
3
10
4
11
12
13
1 Primary bus
2 Redundancy bus
3 Service bus
4 connection to extension unit LB 9024
5 comm unit
6 Redundant comm. unit
7, 8, 9 Power supply (1 of 3 Redundancy)
11, 12 Supply terminals (24 V DC)
10 shut down input with booster connection
for LB 6x1x above
13 Backplane LB 9022 for 22 single resp.
11 double modules
1/50
Accessories
Ordering details
8
7 Type Ex-i Order No.
6 Connector 6-pole
5
4
3
Note: hood cover can only be used with screw connectors.
LB 9007 Screw terminals connector, green, 6-pole
LB 9008 Cover for connector green, 6-pole
GHG 127 0000 A 9007
GHG 127 0000 A 9008
1
2
1 LB 9011 Cold junction module with hood, green GHG 127 0000 A 9011
LB 9012 screw connector with voltage divider GHG 127 0000 A 9012
1 2 3 4 and hood for 10 V inputs
LB 9107 Screw terminals connector blue, 6-pole X GHG 127 0000 A 9107
LB 9009 Wire clamp connector green, 6-pole GHG 127 0000 A 9009
LB 9107 Wire clamp connector blue, 6-pole X CGS 127 0000 P 9107
LB 9108 Cover for connector blue, 6-pole X GHG 127 0000 A 9108
6 LB 9111 Cold junction module with hood, blue, 6-pole X GHG 127 0000 A 9111
Connector 8-pole
LB 9120 Cover for connector blue, 8-pole X GHG 127 0000 A 9120
5 LB 9013 Screw terminals connector green, 8-pole GHG 127 0000 A 9013
LB 9113 Screw terminals connector blue, 8-pole X GHG 127 0000 A 9113
1 Wire clamp connector LB 9014 Screw terminals connector green, 2 x 8-pole GHG 127 0000 A 9014
2 Screw connector with label 1-8 and 9-16
3 Front screw connector LB 9124 Screw terminals connector blue, 2 x 8-pole X GHG 127 0000 A 9124
4 Label (included in the delivery) with label 1-8 and 9-16
5 Hood cover – only for (2) LB 9015 Wire clamp connector green, 8-pole GHG 127 0000 A 9015
6 Coding strip LB 9115 Wire clamp connector blue, 8-pole X GHG 127 0000 A 9115
LB 9016 Wire clamp connector green, 2 x 8-pole GHG 127 0000 A 9016
plugs are labled 1-6 or 1-8
with label 1-8 and 9-16
or 9-16
LB 9116 Wire clamp connector blue, 2 x 8-pole X GHG 127 0000 A 9116
coding strip only when necessary (uncoded ex with label 1-8 and 9-16
works)
LB 9018 Front screw connector 1-8, green GHG 127 0000 A 9018
LB 9118 Front screw connector 1-8, blue X GHG 127 0000 A 9118
LB 9019 Front screw connector 1-8 and 9-16, green GHG 127 0000 A 9019
LB 9119 Front screw connector 1-8 and 9-16, blue GHG 127 0000 A 9119
LB 9020 Coding strip for coding the male GHG 127 0000 A 9020
connector (100 pcs.)
Backplane
LB 9101 Backplane-Segment for 8 I/O GHG 127 0000 A 9101*
LB 9102 left end segment GHG 127 0000 A 9102*
LB 9103 right end segment GHG 127 0000 A 9103*
LB 9121 Backplane for Redundant comm. unit
LB 9101, LB 9102, LB 9103 and 6 I/O GHG 127 0000 A 9121*
not for new installations LB 9153 Extension cable for 2 rows, 1 m with GHG 127 0000 A 9153*
left and right end segments
LB 9022 base unit for 22 single or GHG 127 0000 A 9022
11 double modules or their combination
incl. end segments
LB 9024 extension unit for 22 single or 12 douple GHG 127 0000 A 9024
modules or their combination incl.
end segments and extension cable
LB 9023 base unit with 8 slots incl. end segments GHG 127 0000 A 9023
LB 9023 base unit with 8 slots LB 9025 extension backplane with 8 slots
incl. end segments GHG 127 0000 A 9025
LB 9026 base unit with 16 slots incl. end segments GHG 127 0000 A 9026
LB 9027 extension backplane with 16 slots
incl. end segments GHG 127 0000 A 9027
1/51
Accessories
Ordering details
Type Ex-i Order No.
Bus connectors
SUB D connector (left cable entry) with GHG 127 0000 A 9110
switchable bus termination resistor
SUB D connector ERNI (left cable entry) GHG 210 9233 P 0003
SUB D bus termination ERNI (left cable entry) GHG 210 9233 P 0004
Bus connector with SUB D connector Phoenix (left cable entry) with GHG 127 0000 A 9001
2 cable entries switchable bus termination resistor
GHG 127 0000 A 9001 SUB D connector Phoenix (vertical cable entry) GHG 127 0000 A 9002
with switchable bus termination resistor
SUB D connector Siemens (left cable entry) GHG 127 0000 A 9003
with switchable bus termination resistor
and bus monitor socket
Servicebus RS232-RS485 converter
this requires upon enquiry
converter-servicebus connection GHG 127 0000 P 9281
LB 9109 DIN A4 label for TAG No. GHG 127 0000 A 9109
Software
CD-ROM with DTM configuration software for GHG 127 0000 H 0401
NAMUR replacement network for FDT098 incl. documentation for LB/FB Remote I/O
mech. contacts in combination V4X + V5X + V6X + FDT1.2 DTM for all com units
with digital inputs (LFD) incl. licence for 1 project
GHG 139 0011 C 0000
when required, order comm unit factory update after
return of devices per item plus shipment or GHG 127 0000 H XXXX
On-site Update by a service engineer GHG 127 0000 H YYYY
or on site commissioning assistance
or factory acceptance test alternatives upon enquiry
1/52
Engineering Aids
Substation Setup with Backplanes
LB 9022 and LB 9024
Backplanes accept LB Remote I/O modules All the module slots have equal priorities. So
which act as interfaces between signals in the devices of any function can be mounted next to
NETZ 1
Base Unit
BASISEINHEIT hazardous area and the safe area. any other devices. Marshalling can be arranged
The base unit Backplane LB 9022 will take up via software.
275 mm
to 22 single width modules or 11 double width
devices or any combination of the same.
Intrinsically safe I/O devices can be mounted
next to NON IS modules as long as the spacing
1
LB 9023 base backplane (8 slots, 275 mm) It is ready to accommodate redundant comm between exposed parts of the front connectors
units. exceeds the required 50mm. This can be
The extension Backplane LB 9024 can take achieved by using hooded front connectors (see
another 24 single width modules or 12 double accessories in the catalogue).
width devices or any combination of the same. Modules as well as power supplies may be hot
Additional backplanes offer options as shown. swapped. This also applies to Zone 2 mounted
NETZ
Extension Unit
ERWEITERUNGSEINHEIT
equipment (see operating instructions)
Two slots are provided for comm units to the left
275 mm hand side of the backplane. The leftmost comm
unit is connected to the topmost bus connector
LB 9025 extension (8 slots, 275 mm)
X4. The right hand redundant comm units is
linked to the lower bus connector X5.
BUSKOPPLER
KOPPLER
NETZ 1
NETZ 2
NETZ 3
Redundancy Unit
REDUNDANZEINHEIT
440 mm
LB 9029 redundancy unit (12 slots, not extendable, 440 mm)
REDUNDANZ-
BUSKOPPLER
KOPPLER
NETZ 1
NETZ 2
NETZ 3
Base Unit
BASISEINHEIT
605 mm
LB 9022 base backplane (22 slots, 605 mm) Sectional view
Backplane with guide rails
NETZ 1
NETZ 2
NETZ 3
605 mm
LB 9024 extension backplane (24 slots, 605 mm)
1/53
Engineering Aids
Substation Setup with Backplanes
LB 9101, LB 9102, LB 9103, LB 9121
NET Z
NET Z
NET Z
24 V
For new installations see overleaf
base unit LB 9022 and
24 V
extension unit LB 9024.
KOPPLER
NETZ
24 V
LB 9103 (not for new installations)
Right end segment with terminals for 24VDC
Example of a redundant substation 165
LB 9121 (not for new installations)
55 55 Segment for redundant slaves incl. left end
segment with sub-D connectors for the system
bus, the redundant bus, and the servicebus as
well as terminals for the 24VDC power supply.
119
Compatibility
Substations with backplane segments LB9101-
LB 9121 can be fitted with any kind of I/O
module. Must use power supplies LB9104 only.
left end segment right end segment Existing installations can be fitted with multi
LB 9102 LB 9103 channel modules as long as the comm unit
supports them (see LB 8103).
Dimensions (in mm) Base unit LB 9022 and extension unit
The middle segment LB 9101 is used 3 times to form a base unit or LB 9024 are only suitable to accept I/O
an extension unit. The total size is 605 mm each for the base and modules, power supplies, and comm units in
extension units plus 6 mm on the left and right for fixing terminals. new housings.
The new housings can be recognized by their
pressure pads which enable you to remove the
modules without having to employ any tools
(see fig.).
pressure pads
The modules can also be mounted on
backplane segments LB 9101 -LB 9121
Note therefore:
Modules with pressure pad – any Backplane
Modules without pad – LB 9101-LB 9121 only
1/54
Engineering Aids
Accessories
Plugs
Sensors and actuators are adapted via front
end screw plug-in connectors.
screw plug-in hooded screw
plug-in Wire clamp connections on request.
connector
connector screw plug-in By using hooded plugs intrinsically safe and
connector non IS modules can be mounted next to
each other.
Cabinets
LB Remote I/O products can be mounted in
standard cabinets. 384 I/O modules can be
fitted depending on cabinet size. A combination
with PLC components in the same cabinet is
also possible
Modul
single-coding Cabinets 800 x 400 x 2000
horizontal mounting
8 rows or 4 bus substations
736 digital I/O or 320 analog I/O
vertical mounting
3 rows or 4 + 1 bus substations
824 digital I/O or 360 analog I/O
Modules
Cabinets 800 x 600 x 2000
front and rear access
horizontal mounting
2 x 8 rows each 3 bus substations
2x736 digital I/O or 2x320 analog I/O
vertical mounting
2 x 3 rows each 9 bus substations
2x824 digital I/O or 2x360 analog I/O
Dimensions in mm
1/55
LB Remote I/O in Zone 2
ATEX Directive 94/9/EC
Certified to IEC 60 079-15
1/56
FB Remote I/O
Description
FB Remote I/O stations are used as signal
conditioning units between field devices
and control systems. The devices are
mounted in well designed IP66 field
enclosures in Zone 1. The various I/O
modules may be plugged in or removed
from a live circuit. The modules are
encapsulated for rough environmental 2
conditions. The flame proof housings allow
them to be hot swapped in Zone 1.
FB Remote I/O modules offer advantages
in that they are galvanically isolated, they
can boost and amplify signals, and are
easily mounted as plug-in units. Since
they are galvanically isolated they do not
require equipotential earth connections
normally encountered with safety barriers.
Changes in the power supply voltage do
not affect the excellent device performance
due to the properties of the built-in
amplifier circuits. Furthermore they render
system I/O cards superfluous. Wiring
between them and the system is reduced
to a single bus.
Light emitting diodes (LEDs) indicate the
device status. A green LED shows the
operating condition and a red LED signals
alarm conditions e.g. line faults and
interruptions. This information can be
accessed from the DCS and PLC via a
standard bus.
■ 2- to 8 channels digital
■ 1- bis 4 channels analogue
■ Considerable savings in
hardware and wiring
■ Zone 1 mounting possible
■ Plug-in modules for analogue
or digital I/O
■ Screw plug-in
field connectors
■ Wire clamp terminals optional
■ Safe galvanic isolation
■ Status LEDs
■ Low power consumption
■ Similar electronic and identical
Ex-i features as LB Remote I/O
■ EEx ia/ib approved acc. to ATEX
■ Suitable for all well-known
PLC and DCS
■ International approvals
2/1
Designed to be
User-Friendly
Substation ➀
Substations can be connected to process
control systems (DCS) and programmable logic
controllers (PLC) via standard busses. They
open the gate to all major system manufacturers
and can be mounted in zone 1 hazardous areas.
Mounting
The prewired Ex-e IP66 enclosure contains
a mechanically compact and robust backplane
system. The various IS input/output modules
plug into the frame. Proven Ex-d connectors with
self cleaning contacts allow modules to be
removed in the hazardous area during operation
(hot swap).
The backplane ➁
The modular concept allows you to flange
enclosures together to arrive at the desired size.
Each housing contains Ex-e terminals for power
and communication. These are safely covered
separately and touch protected.
The modules
The compact size of the modules using the
proven LB Remote I/O electronics lead to a
high packing density. Snap in mounting utilising
the most advanced plastics technology
allows the FB Remote I/O modules to be plugged
in firmly without the need for fixing screws.
The field connection is made by a coded Phoenix
mini combicon connector on the top of the module.
The system is so designed that any of the
modules can be slotted into any position on
the backplane so that IS terminations are made
to suit the wiring and not the other way around.
Up to 24 I/O modules ➂ plus a power supply
module can be fitted in an enclosure. Depending
upon the module type, either one, two, or eight
channels can be utilised.
A wide range of interface modules are available
for all applications including HART compatible
devices.
Communications module
The communications module is the link between
the intrinsically safe I/O modules and the control
system. The unit can handle up to 48 I/O
modules and is available in various bus formats.
The unit is located on the left hand side of the
first backplane segment.
2/2
Fast and User-friendly
Commissioning
Line redundancy
PROFIBUS IS field equipment A field station features 2 redundant communica-
DP, DPV1 tion units. The field bus is also redundant. The
MODBUS
transmission lines of the master are connected
to the active and passive communication units
1 23 24 via both bus lines. In order to be able to access
24 V DC
supply
both bus lines, the master features a VOTER for
memory
I/O I/O I/O
Example:
the receiving lines.
Application redundancy 2
A field station features 2 redundant communica-
Bus Bus Bus Bus Bus
substation
with 2 x 1-24 tion units. To be able to access both bus lines,
I/O modules the master features 2 redundant interfaces. Both
FB Remote I/O communication units are active on both external
busses. Only one communication unit is active
on the internal bus and can define outputs.
PROFIBUS IS field equipment Redundant Power Supplies
DP, DPV1
Redundant comm units are powered via power
MODBUS
supplies positioned in the base unit and the
redundancy units.
1 24 Example: The extension unit features 2 power supplies.
24 V DC 24 V DC Substation with
supply supply
In case of a failure the second power supply
2 x 1-24 I/O modules
redundant ensures continued operation. A diagnostic flag
memory memory
I/O I/O communication unit is sent to the DCS system.
and redundant power Signal processing
Bus Bus Bus Bus Bus Bus supply The FB Remote I/O series interface units have a
unique way of handling signals to and from the field.
The FB Remote I/O modules convert incoming
FBFBRemote
Remote I/O
I/O
field signals to an internal FB Remote I/O format.
This also works in reverse for outgoing signals.
FB Remote I/O series: software If the wrong type of module is fitted, this is One function of the communications module is to
The FB Remote I/O interface modules have no recognized and does not influence the running supervise a rapid data exchange between all of
internal or external switches or adjustments. operation. This also applies for the communica- the I/O modules and itself. At any time, an internal
The configuration can be done either by the tion unit. However, the configuration of the memory within the communications module,
control system or by an easy to use WINDOWS communication unit must either be loaded from holds all the field signal data. The second function
program and the RS485 interface in the comm the control system or via the RS 485 service of the memory within thecommunications module,
unit. These can also be configured in the control connection. In a redundant system this is carried is to allow the control system’s fieldbus to access
room and transported to be plugged in in the field. out automatically. and exchange information.
The setup data for every module is stored in a Graded redundancy As the memory is the only interface between the
non volatile memory located within the commu- As every control system has its own individual FB Remote I/O and the control system fieldbus,
nications module. requirements, the FB Remote I/O series has a future fieldbus developments in this area can be
Self generating documentation modular approach to redundancy. accommodated easily.
The FB Remote I/O series software uses the Due to the FB Remote I/O series hardware HART communication
configuration data to generate a full system design, the power supply and the FB Remote I/ The FB Remote I/O range of products supports
documentation package. Considerable time and O are not regarded as being susceptible to HART communication. Provided that the control
cost savings can be realised by utilising this major system failure. The critical areas of system can also process the HART protocol,
feature. concern are the control system fieldbus and the direct communication with the field devices via
Plug and play service communications module. the Profibus is possible. Alternatively a second-
The I/O setup data for every module is stored in The FB Remote I/O series can overcome these ary master can be used on the Profibus line.
non volatile memory. Should a fault develop concerns by offering a solution. Depending upon the type of communication
within a module, it can easily be removed and Redundant communication module unit, HART communication is also possible via
replaced by a standard unprogrammed I/O Two FB Remote I/O series communications the service bus.
module. modules can, if required, be placed in parallel to Line fault detection
As soon as the new unit is inserted, the give a high level of system redundancy. Almost all FB Remote I/O series I/O modules
communication module instantly updates Redundant selectors have a sophisticated Line Fault Detection
the new I/O module and within a fraction Both communication units can access the System. This feature can be enabled or disabled
of a second the device is back in operation. internal bus via redundant selectors. for each channel individually.
2/3
FB Remote I/O, Zone 1
Product Overview
Product features
• Zone 1 or zone 2 mounted
• Suitable for rough ambient conditions
(encapsulated)
• Single channel with high availability or
4 channels with compact mode
• Digital 2 channels with high availability or
8 channels with compact mode
• Single channel- and multi-channel modules
can be mixed mounted
• Any slot position
• Can be unplugged in Zone 1 during operation
• Input and output for all standard process
signals
• Alternatively connection to flame proof field
devices
• Single channel modules are galvanically
isolated between each channel
• Multi channel modules are galvanically
isolated between field signals and system bus
(group isolation)
• Simulation for commissioning and service
operation (forcing)
• Plug- and play service after replacement
• HART communication Profibus via FDT
or via service bus (depending on version)
• Line monitor (LFD)
• Permanent self-monitoring
• Selectable output drive in case of fault
(depending on version)
• Output with watch dog circuit
for serious faults
• Module TAG and channel TAG
depending on version
• Same Nos. of modules with- and without
redundancy
• EMC to EN 61326 or NE21
Input:
24 V DC (20 … 30 V)
Power supply
230 V AC (50 ... 60 Hz) or 110 V AC
Control 3 x 2 x 2.5 mm2 (mains)
room
CPU CPU Connection terminals 1 x 2 x 2.5 mm2 (PROFIBUS)
1 x 2 x 2.5 mm2 (Servicebus)
Backplane plug contact material CuZn 39P63 galv. 6 mAg
Ex-i-plug contact material E-Cu 57F37 galv. Cu/Ag5
LB Remote LB Remote 6 x M20 (mains and bus cables)
Cable entries per enclosure
24 entries Ex-i (cables 3 - 9 mm)
with 24 slots
24 blind plugs
Degree of protection IP 66
FOL Zone 2
Ex-marking according the directive 94/9/EG II 2 (1) G EEx dem [ia] IIC T4 resp. T6
EG-Certificate of Conformity PTB 97 ATEX 1075
Ambient temperature (outside enclosure) – 20 °C ... 40 °C (T6), – 20 °C ... 55 °C (T4)
Relative humidity < 95 %
FOL Zone 1 Environmental test Nb acc. DIN IEC68 part 2-14
Humidity Cb acc. DIN IEC68 part 2-56
FB Remote FB Remote acc. IEC68-2-42
Pollution and gas test for plugs (21 days in 25 ppm SO2,
at 25 °C und 75 % rel. humidity)
plastic, stainless steel also available
Type of enclosure with flanged terminal box
(see accessories)
544 x 271 x 252 (24 slots)
800 x 1000 x 300 (48 slots)
Dimensions (L x W x D)
Example for bus structures 1200 x 1000 x 500 up to 1800 x 1600 x 500
(see accessories)
2/4
FB Remote I/O, Zone 1
Product Overview
Product features
FB Remote I/O Modules FB 1201 - FB 9215
Reponse time between module and
6.5 ms
communication interface
Between input and master see documentation
Ex-marking acc. The directive 94/9/EC II 2 (1) G EEx d [ia/ib] IIC
EC-Certificate of Conformity PTB 97 ATEX 1074U
Approval of intrinsically
safe circuits of the modules
resp. EC Certificate of Conformity
PTB 03 ATEX 2042 2
Ambient conditions see housing
ATEX approved for housing
Housing surface temperatures up to 55 °C
(station completely fitted)
EMC to EN 61326 or NE21
IS connectors screw and cage clamp connectors
Bus structure
Number of modules (channels)
per station 1 channel, high integrity, up to 48 (48 analog, 144 digital)
multichannel, compact up to 24 (96 analog, 192 digital)
determined by fieldbus specification
Max. number of stations per bus line
125 (Profibus), 255 (Modbus)
Number of slaves per bus segment max. 31
Repeater between master and slave max. 3
increased safety (NO IS isolating
Bus connection
module for bus line required)
FOL (optical fibre link) peripheral device necessary
max. bus lenght (FOL) 1000 m (1.5 MBaud)
max. bus lenght (copper) 1000 m (187.5 kBaud)
200 m (1.5 MBaud)
Redundancy (optional)
2 power supplies for 24 slots
Power supply redundancy
with bumpless changeover
2 comm. units per station
Line redundancy (voter)
with bumpless changeover
2 comm. units per station
Application redundancy (2 CPUs)
with bumpless changeover
P Voter Bus
L Master HART communication
S Redundant bus Depending on the comm. unit HART communication to field devices is possible via Profibus or the
service bus. The latter features an RS 485 interface for HART communication. This can also be
Line redundancy
BK
BK
BK
BK
used with redundant systems in addition to the main bus. HART communication with any compat-
ible field device is possible from the control room. For this you have to use the software provided
Master by the manufacturer of the field device or any off-the-shelf software, e.g. CORNERSTONE, Fisher
P Bus Rosemount AMS, ABB SMARTVISION, Siemens PDM, etc.
L In the case of control systems that support the FDT concept and use the Profibus, HART commu-
S Redundant bus nication via the Profibus is possible using the P+F DTM. Alternatively a secondary master can be
Redund.
Master
used on the Profibus line again using an FDT compatible software package (e.g. SMART VISION,
BK
BK
BK
BK
BK
BK
BK
Redund
Master Redundant bus Suitable ComUnits are available for control systems that prefer ModBus RTU.
Approvals
Examples for redundant bus structures
The plug-in modules contain the same electronics as the Zone 2 devices. Therefore IS circuits refer
to the PTB certificate for the intrinsically safe circuits PTB 03 ATEX 2042. Certification for the
modules according to the EC-Directive 94/9/EC PTB 97 ATEX 1074 U. Certification for the housing
PTB 97 ATEX 1075 International approvals upon enquiry.
2/5
FB Remote I/O
Selection Chart
Selection chart
Application Type Preferred version Page
2 channels FB 1X01 GHG 127 0000 B1X01 2/10
fully
isolated
Contact
3 channels FB 1X02 GHG 127 0000 B1X02 2/11
group isolation
NAMUR 1-channel, 0-15 kHz FB 1X03 GHG 127 0000 B1X03 2/12
Initiator frequency, direction
of rotation
10 k Dosing counter
Digital input
2.2 k
8 channels FB 1X08 GHG 127 0000 B1X08 2/13
Contact with NAMUR or
NAMUR voltage input
network group isolation
for LFD
Opto-
coupler
Signal voltage
level supply 15 V
galvanically 2/63
isolated
intrinsically safe
circuits X = 2 intrinsically safe
X = 3 increased saftey
2/6
FB Remote I/O
Selection Chart
Selection chart
Application Type Preferred version Page
positioner
HART FB 4X02 GHG 127 0000 B4X02 2/30
750 1
I/P isolated
I/P converter
HART, 4 channels FB 4205 GHG 127 0000 B4205 2/31
750 1
0000 group isolation
Display
2/7
FB Remote I/O
Selection Chart
Selection chart
Application Type Preferred version Page
strain gauge
plus FB 5202 GHG 127 0000 B5202 2/36
millivolt amplifier
20 mA/14 mV
(load 350 1,
2 mV/V)
slide wire sensor
sensor supply
2/8
Digital Input
Product Overview
Product features
• Zone 1 or Zone 2 mounted
• Suitable for rough ambient conditions (potted)
• Single channel high integrity or
8 channel compact modules
• Single channel- and mult-channel modules
can be mixed mounted
• Any slot position
• Can be unplugged in Zone 1 during operation
(hot swop) 2
• Inputs for NAMUR initiators, mechanical
contacts, opto-couplers and active
24 V signals
• Alternatively connection to flame proof
field devices
• 1-2 channel modules are galvanically isolated
between channels
• 8 channel modules are galvanically isolated
between input and system bus (group
isolation)
• Simulation for commissiong and service
operation (forcing)
• Self configurating after replacement
• Positive or negative logic selectable
(depending on version)
• Line monitor (LFD) depending on version
• Permanently self monitoring
• ON/OFF delay depending on the version
• Module TAG and channel TAG
depending on version
• Same Nos. of modules with- and without
redundancy
• EMC to EN 61326 or NE21
Available models
FB 1X01 Digital input, 2 channels, isolated
FB 1X02 Digital input, 3 channels, group isolation
Pulse-, frequency input,
FB 1X03
1 chanal, isolated
FB 1X08 Digital input, 8 channels, group isolation
10k
2.2k X = 2 intrinsically safe EExia, X = 3 increased safety
Contact
Contact with
NAMUR
network
for LFD
NAMUR
Initiator
Opto- Voltage
coupler input
2/9
FB 1201
Digital Input
2 Isolated Channels
Product features
• Mounting in Zone 1 or Zone 2 hazardous • Simulation for commissioning and service
areas (forcing)
• Any slot position • Self configurating after replacement
• Can be unplugged in Zone 1 during operation • Positive or negative logic selectable depending
(hot swap) on version
• Inputs for NAMUR initiators, mechanical • Line monitor (LFD)
contacts and opto-couplers • Permanently self-monitoring
• Galvanic isolation between inputs and the • ON/OFF delay
field bus • Module-TAG and channel-TAG
• EMC to EN 61326 or NE21
Input:
Volt-free contacts and 2 wire
Signal type
NAMUR proximity switches
on > 2.1 mA
Switching points
off < 1.2 mA
Hysteresis 0.2 mA
Line fault (LFD) < 1 mA
short > 6 mA
Frequency 0 - 50 Hz (depending on DCS)
Power consumption 0.4 W
Explosion protection:
Category II 2 (1/2) GD EEx d [ia/ib] IIC
Approval PTB 97 ATEX 1074 U
Uo ) 12.6 V Io ) 12.8 mA Po ) 40.1 mW
IIC Safety values (linear)
Co ) 720 nF Lo ) 2 mH
Ordering details
Type Order No.
Digital input, 2 channels, Ex-i FB 1201 B GHG 127 0000 B1201
CH 1 CH 2
10k
2.2k
+ - + -
1 2 3 4 5 6
FB Remote
LB/FB I/OI/O
Remote
2/10
FB 1202
Digital Input
3 Channels
Product features
• Mounting in Zone 1 or Zone 2 hazardous • Simulation for commissioning and service
areas (forcing)
• Any slot position • Self configurating after replacement
• Can be unplugged in Zone 1 during operation • Positive or negative logic selectable depending
(hot swap) on version
• Inputs for NAMUR initiators, mechanical • Line monitor (LFD)
contacts and opto-couplers • Permanently self-monitoring
• Galvanic isolation between the input and the
field bus (group isolation)
• ON/OFF delay
• Module-TAG and channel-TAG
2
• EMC to EN 61326 or NE21
Input:
Volt-free contacts and 2 wire
Signal type
NAMUR proximity switches
on > 2.1 mA
Switching points
off < 1.2 mA
Hysteresis 0.2 mA
Line fault (LFD) < 1 mA
short > 6 mA
Frequency 0 - 50 Hz (depending on DCS)
Power consumption 0.5 W
Explosion protection:
Category II 2 (1/2) GD EEx d [ia/ib] IIC
Approval PTB 97 ATEX 1074 U
Uo ) 10.5 V Io ) 35 mA Po ) 92 mW
IIC Safety values (linear)
Co ) 785 nF Lo ) 2 mH
Ordering details
Type Order No.
Digital input, 3 channels, Ex-i FB 1202 B GHG 127 0000 B1202
CH 1 CH 2 CH 3
10k
2.2k
+ + + - - -
1 2 3 4 5 6
FB Remote
LB/FB I/OI/O
Remote
2/11
FB 1203
Digital Input
Counter, Frequency, Direction of Rotation
Product features
• Frequency, counter, direction of rotation
• Any slot position
• Can be unplugged in Zone 1 during operation
• Inputs for mech. contacts, NAMUR proximity switches
and optocouplers
• Galvanic isolation between the input and the system bus
• Simulation for commissiong and service (forcing)
• Plug- and play service after replacement
• Positive- or negative logic selectable depending on version
• Line monitor (LFD)
• Permanent self-monitoring
• EMC to EN 61326 or NE21
Input:
Volt-free contacts and 2 wire
Signal type
NAMUR proximity switches
on > 2.1 mA
Switching points
off < 1.2 mA
Hysteresis 0.2 mA
Frequency 0 - 15 kHz (see below)
Processing time approx. 50 ms mode dependant
Minimum pulse duration 20 +s
Line fault (LFD) < 1 mA
short > 6 mA
screw terminals or
Connection
cage clamp connectors
Power consumption approx. 0.6 W
Explosion protection:
Category II 2 (1/2) GD EEx d [ia/ib] IIC
Approval PTB 97 ATEX 1074 U
Uo ) 10.5 V Io ) 23.3 mA Po ) 61.2 mW
IIC Safety values (linear)
Co ) 816 nF Lo ) 2 mH
Ordering details
Type Order No.
Frequency in, counter, direction of rotation, FB 1203 B GHG 127 0000 B1203
Digital input max. 400 Hz, Ex-i FB 1203 C GHG 127 0000 C1203
Note
CH1 Direction for mech. contacts use 400 Hz version
10k
2.2k
Configuration parameters
TAG No.
Line monitor
Line fault substitute value
+ – + – Span, filter
Input simulation
1 2 3 4 5 6 Frequency 15 kHz without determination of direction 12 bit + 4 bit status
Frequency 15 kHz with determination of direction 12 bit + 4 bit status
Pulse counter 15 kHz without determination of direction 12 bit + 4 bit status
Pulse counter 15 kHz with determination of direction 12 bit + 4 bit status
Pulse counter 15 kHz without determination of direction 32 bit
Pulse counter 15 kHz with determination of direction 32 bit
50 Hz frequency 12 bit + 4 bit status + pulse counter 32 bit without dtermination of direction
(min. pulse duration 10 ms)
FB Remote I/O
50 Hz frequency 12 bit + 4 bit status + pulse counter 32 bit with dtermination of direction
(min. pulse duration 10 ms)
2/12
FB 1208
Digital Input
8 Channels
Product features
• Zone 1 or Zone 2 mounted • Simulation for commissiong and service
• Any slot position (forcing)
• Can be unplugged during operation • Self configurating after replacement
(hot swap) • Positive- or negative logic selectable
• Inputs for contacts, NAMUR-proximity • Line monitor (LFD)
switches and optocouplers and active • Permanently self-monitoring
switch-signals 24 V • Switch delay on/off
• Galvanic isolation between the input and
the field bus (group isolation)
• Module TAG and channel-TAG
• EMC to EN 61326 or NE21 2
Input:
Volt-free contacts and 2 wire
Signal type
NAMUR proximity switches
on > 2.1 mA
Switching points off < 1.2 mA
1.65 mA +/– 0.25 mA
Hysteresis 0.2 mA
Line fault (LFD) < 1 mA
short > 6 mA
Scanning time 6.5 ms
Power consumption 0.7 W
Explosion protection:
Category II 2 (1/2) GD EEx d [ia/ib] IIC
Approval PTB 97 ATEX 1074 U
Uo ) 15.3 V Io ) 16.1 mA Po ) 61.8 mW
IIC Safety values (linear)
Co ) 450 nF Lo ) 2 mH
Ordering details
Type Order No.
Digital input, 8 channels, Ex-i FB 1208 B GHG 127 0000 B1208
CH1 + - + - + - + - CH4
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
CH5 CH8
LB FB
Remote
Remote I/O
I/O
2/13
FB 1301
Digital Input
2 Channels, Ex-e
Product features
• Inputs for contacts, • Galvanic isolation between the inputs as
NAMUR - proximity switches well as the input and the field bus
and optocouplers • EMC to EN 61326 or NE21
• Zone 1 mounted • Line monitor
• Any slot position
• Can be unplugged during operation (hot swap)
• Access to Exe connections when
voltfree
Input:
Volt-free contacts and 2 wire
Signal type
NAMUR proximity switches
on > 2.1 mA
Switching points
off < 1.2 mA
Hysteresis 0.2 mA
Line fault (LFD) < 1 mA
short > 6 mA
Frequency 0 - 50 Hz (depending on DCS)
Scanning time approx. 6.5 ms
Connection 2 m cable tails to Ex-e terminals
Power consumption 0.4 W
Explosion protection:
Category II 2 GD EEx d IIC
Approval PTB 97 ATEX 1074 U
Ordering details
Type Order No.
Digital input, 2 channels, Ex-e, 200 cm wire ends FB 1301 B-200 GHG 127 0003 B1301
CH 1 CH 2
10k
2.2k
+ - + -
1 2 3 4 5 6
FB Remote
LB/FB RemoteI/O
I/O
2/14
FB 1302
Digital Input
3 Channels, Ex-e
Product features
• Can be unplugged during operation • Simulation for service and commissioning
(hot swap) in Zone 1 (forcing)
• Access to Ex-e connections possible • Self-configurating during hot swap
when voltfree (plug and play)
• Inputs for mech. contacts, NAMUR-proximity • Positive or negative logic selectable
switches and optocouplers • Line monitor (LFD)
• 3 channels • Continuously self-monitoring
• Galvanic isolation (group) between inputs
and BUS
• EMC to EN 61326 or NE21
2
Input:
Volt-free mech. contacts and 2 wire
Signal type
proximity switches DIN 19234 or NAMUR
on > 2.1 mA
Switching points
off < 1.2 mA
Hysteresis 0.2 mA
Line fault (LFD) < 1 mA
short > 6 mA
Frequency 50 Hz (depending on DCS bus cycle)
Cycle time (com unit) 6.5 ms
Connection 2 m cable tails to Ex-e terminals
Power consumption 0.5 W
Explosion protection:
Category II 2 GD EEx d IIC
Approval PTB 97 ATEX 1074 U
Ordering details
Type Order No.
Digital input, 3 channels,
Ex-e, 200 cm cable tails FB 1302 BS200 GHG 127 0000 B1302
Digital input, 3 channels,
Ex-e, 80 cm wire ends FB 1302 B-080 GHG 127 0001 B1302
Digital input, 3 channels, Ex-e,
150 cm wire ends FB 1302 B-150 GHG 127 0002 B1302
Digital input, 3 channels,
Ex-e, 200 cm wire ends FB 1302 B-200 GHG 127 0003 B1302
CH 1 CH 2 CH 3
2.2k
+ + + - - -
1 2 3 4 5 6
FBFIELD BUS
Remote I/O
2/15
FB 1303
Counter, Frequency, Direction of Rotation
1 Channel, Ex-e
Product features
• Frequency in, counter, direction of rotation • Inputs for contacts, NAMUR - proximity
• Zone 1 mounted switches and optocouplers
• any slot position • Galvanic isolation between the input
• Can be unplugged during operation (hot swap) and the field bus
• Access to Ex-e connections possible • EMC to EN 61326 or NE21
when voltfree • Line monitor
Input:
Volt-free contacts and 2 wire
Signal type
NAMUR proximity switches
on > 2.1 mA
Switching points
off < 1.2 mA
Hysteresis 0.2 mA
Frequency 0 - 15 kHz (see below)
Processing time approx. 50 ms mode dependent
Minimum puls duration 20 +s
Line fault (LFD) < 1 mA
short > 6 mA
Scanning time approx. 6.5 ms
Connection 2 m cable tails to Ex-e terminals
Power consumption 0.6 W
Explosion protection:
Category II 2 GD EEx d IIC
Approval PTB 97 ATEX 1074 U
Ordering details
Type Order No.
Counter, frequency, direction of rotation,
NAMUR Ex-e, 200 cm, cable tail FB 1303 BS200 GHG 127 0000 B1303
Counter, frequency, direction of rotation,
NAMUR Ex-e, 200 cm, wire ends FB 1303 B-200 GHG 127 0000 B1303
Configuration parameters
2/16
FB 1308
Digital Input
8 Channels, Ex-e
Product features
• Zone 1 or zone 2 mounted • Self configurating after replacement
• Any slot position • Positive- or negative logic selectable
• Voltfree Exe loops can be unplugged during • Line monitor (LFD)
operation (hot swap) • Permanently self-monitoring
• Inputs for contacts, mech. contacts, and • ON/OFF delay
optocouplers and active switch-signals 24 V • Module TAG and channel-TAG
• Galvanic isolation between the input and the • EMC to EN 61326 or NE21
field bus (group isolation)
• Simulation for commissiong and service 2
(forcing)
Input:
Volt-free contacts and 2 wire
Signal type
NAMUR proximity switches
on > 2.1 mA
Switching points off < 1.2 mA
1.65 mA +/– 0.25 mA
Hysteresis 0.2 mA
Line fault (LFD) < 1 mA
short > 6 mA
Digital signals (active) 24 V 5.0 V
on > 8 V > 2.7 V
Switching points
off < 3 V < 2.3 V
Scanning time 6.5 ms
Connection 2 m cable tails to Ex-e terminals
Power consumption 0.7 W
Explosion protection:
Category II 2 GD EEx d IIC
Approval PTB 97 ATEX 1074 U
Ordering details
Type Order No.
Digital input, 8 channels,
Ex-e, cable tails FB 1308 BS200 GHG 127 0000 B1308
Digital input, 8 channels,
Ex-e, 80 cm wire ends FB 1308 B-080 GHG 127 0001 B1308
Digital input, 8 channels,
Ex-e, 150 cm wire ends FB 1308 B-150 GHG 127 0002 B1308
Digital input, 8 channels,
Ex-e, 200 cm wire ends FB 1308 B-200 GHG 127 0003 B1308
CH1 + - + - + - + - CH4
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
CH5 CH8
LB FB
Remote
Remote I/O
I/O
2/17
Digital Output
Product Overview
Product features
• Zone 1 or zone 2 mounted
• Suitable for rough ambient conditions (potted)
• Single channel high integrity or
8 channel compact modules
• Single channel- and mult-channel modules
can be mixed mounted
• Any slot position
• Can be unplugged in Zone 1 during operation
(hot swap)
• Output for intrinsically safe solenoid valves,
sounders and LED, relay for Exd solenoid
valve
• Alternatively connection to flame proof
field devices
• Modules are galvanically isolated between
channels or between ouput and system bus
(group isolation)
• Simulation for commissioning and service
operation (forcing)
• Self configurating after replacement
• Positive or negative logic selectable (depends
on version)
• Line monitor (LFD) depends on version
• Permanently self-monitoring
• ON/OFF delay (depends on version)
• Selectable output fault level (depends on
version)
• Short circuit protected
• Output with watch dog circuit for fatal errors
• Module TAG and channel TAG depending on
the version
• Same Nos. of modules with- and without
redundancy
• Version dependancy see comm. units
• EMC to EN 61326 or NE21
Available modules
FB 2XZZ Digital output, 2 feed-back inputs
FB 6301 Relay output, 2 channels 24 V, isolated
FB 6305 Relay output, 4 channels 230 V, isolated
FB 6306 Relay output, 8 channels 24 V, isolated
FB 6X08 Digital output, 8 channels, group isolation
FB 6210-6215 Digital output, 4 channels, group isolation
X = 2 intrinsically safe
X = 3 increased safety
ZZ = depending on the valve
Solenoid Sounder
2/18
FB 2201 - 2213
Digital Output
with Position Feed Back
Product features
• Zone 1 or Zone 2 mounted • Line monitor (LFD)
• Output for intrinsic safety solenoid valves depends on version
• Output for sounders and LED • Permanently self-monitoring
(only without LFD) • Output with watch dog circuit for fatal errors
• Positive- or negative logic selectable • EMC to EN 61326 or NE21
depending on version
Input:
Volt-free mech. contacts or 2-wire proximity
2
Signal type
2-wire-initiators EN/IEC 60947-5-6 / NAMUR
on > 2.1 mA
Switching points
off < 1.2 mA
Hysteresis 0.2 mA
Line fault (LFD) < 1 mA
short > 6 mA
Output:
with line monitor (LFD) short circuit protected (see below)
Watch dog Output OFF 0.5 s after serious fault
Power consumption 0.52 W - 1.8 W depending on version
Explosion protection:
Category II 2 (1/2) GD EEx d [ia] IIC
Approval PTB 97 ATEX 1047 U
sensor circuit Uo ) 14 V, ISC ) 16 mA, Po ) 55 mW
IIC Safety values (linear) Co ) 418 nF, Lo ) 5 mH
output circuit see table
Ordering details
Uout/V Ra/1 Limit/mA LFD/1 Uo/V IO/mA PO/mW CO/nF LO/mH Type Order No.
22.0 315 50 20...2000 24.9 91 558 79 1 FB 2201 B GHG 127 0000 B2201
24.0 210 75 1) 110...1200 27.8 183 1270 227 1) 1.9 1) FB 2202 B GHG 127 0000 B2202
24.0 360 50 70...2000 27.8 91.5 636 69 0.4 FB 2203 B GHG 127 0000 B2203
22.0 220 50 220...1300 24.2 145 872 92 0.27 FB 2204 B GHG 127 0000 B2204
22.0 220 50 2) 220...1300 24.2 145 872 92 0.27 FB 2204 D GHG 127 0000 D2204
22.8 290 50 150...2000 25.2 108 681 74 0.5 FB 2205 B GHG 127 0000 B2205
25.3 329 – 25...3500 27.8 108 751 81 0.19 FB 2212 B GHG 127 0000 B2212
25.3 329 – 2) 25...3500 27.8 108 751 81 0.19 FB 2212 D GHG 127 0000 D2212
26.7 509 – 40...7000 28.7 68 485 69 0.4 FB 2213 B GHG 127 0000 B2213
OUT
26.7 509 – 2) 40...7000 28.7 68 485 69 0.4 FB 2213 D GHG 127 0000 D2213
1)
only group II B
2)
output without LFD no longer required since the test pulse can be deactivated via software
+1 –4 1 4 for modules delivered after March 07.
CH1 CH2
10k
2,2k
+ + + - - -
1 2 3 4 5 6
Ra
UOUT
FB
LBRemote I/O
Remote I/O
2/19
FB 2201 - 2203 - 2212 - 2213
Digital Output
with Shut-down Input
Product features
• Zone 1 or Zone 2 mounted • 2 digital inputs (valve position)
• Output for intrinsic safety solenoid valves • Line monitor (LFD)
• Output for sounders and LED depends on version
(only without LFD) • Permanently self-monitoring
• Positive- or negative logic selectable • Output with watch dog circuit for fatal errors
depending on version • EMC to EN 61326 or NE21
• Shut down input independent of the bus
Input:
Volt-free mech. contacts or 2-wire proximity
Signal type
2-wire initiators DIN 19324 resp. NAMUR
on > 2.1 mA
Switching points
off < 1.2 mA
Hysteresis 0.2 mA
Line fault (LFD) < 1 mA
short > 6 mA
Output:
with line monitor (LFD) short circuit protected (see below)
Watch dog Output OFF 0.5 s after serious fault
Power consumption 0.52 W - 1.8 W depending on version
Explosion protection:
Category II (1/2) GD EEx d [ia] IIC
Approval PTB 97 ATEX 1074 U
sensor circuit Uo ) 14 V, Io ) 16 mA, Po ) 55 mW
IIC Safety values (linear) Co ) 418 nF, Lo ) 5 mH
output circuit see table
Ordering details
Uout/V Ra/1 Limit/mA LFD/1 Uo/V IO/mA PO/mW CO/nF LO/mH Type Order No.
22.0 315 50 20...2000 24.9 91 558 79 1 FB 2201 E GHG 127 0000 E2201
24.0 360 50 70...2000 27.8 91.5 636 69 0.4 FB 2203 E GHG 127 0000 E2203
24.0 360 502) 70...2000 27.8 91.5 636 69 0.4 FB 2203 G GHG 127 0000 G2203
22.8 290 50 150...2000 25.2 108 681 74 0.5 FB 2205 E GHG 127 0000 E2205
25.3 329 – 25...3500 27.8 108 751 81 0.19 FB 2212 E GHG 127 0000 E2212
26.7 509 – 40...7000 28.7 68 485 69 0.4 FB 2213 E GHG 127 0000 E2213
2)
output without LFD no longer required since the test pulse can be deactivated via software
for modules delivered after March 07.
OUT
+1 —4 1 4
CH1 CH2
10k
2,2k
+ + + - - -
1 2 3 4 5 6
FB
LB Remote I/O
Remote I/O
2/20
Transmitter Power Supply,
Analog Input, HART
Product Overview
Product features
• Zone 1 or Zone 2 mounted
• Suitable for rough ambient conditions (potted)
• Single channel with high integrity or
4 channel compact mode
• Single channel- and multi-channel modules
can be mixed mounted
• Any slot position
• Can be unplugged in Zone 1 during operation
(hot swap) 2
• Input for pressure, differential pressure, flow,
level and other 2-/4-wire transmitters
• Resolution 12 bit for 0-20 mA
• Alternatively connection to flame proof
field devices
• Single channel modules are galvanically
isolated between channels
• 4 channel modules are galvanically
isolated between input and system bus
(group isolation)
• Simulation for commissioning and service
(forcing)
• Self configurating after replacement
• HART communication on Profibus via FDT
or on servicebus (depends on version)
• Line monitor (LFD)
• Permanently self-monitoring
• Module TAG and channel TAG depending on
version
• Same Nos. of modules with and without
redundancy
• Version dependancy see comm. units
• EMC to EN 61326 or NE21
Available modules
FB 3201 Analog input, 14.5 V
FB 3X02 Analog input, HART, 16 V
FB 3203 Analog input, HART, 15 V
FB 3205 Analog input, HART, 4 chan., group isolation
Flow Level
Powered Hand-held
field devices configurator
2/21
FB 3201
Analog Input
Transmitter Power Supply
Product features
• Power supply for 2- and 3-wire • Intrinsically safe approval
4 - 20 mA transmitters • Line monitor
• Galvanic isolation • Zone 1 mounted
• EMC to EN 61326 or NE21 • Can be unplugged during operation (hot swap)
Input:
Field device power supply 14.5 V (20 mA)
Input range 4 - 20 mA (0 - 26 mA)
Input impedance (terminals 5-6) 15 1
Internal impedance (terminal 2-5) 315 1
Linearity < 0.1 %
Temperature drift < 0.1 % / 10 K
min. 1 mA
Line monitor
max. 22 mA, programmable
Conversion time ) 50 msec
Power consumption 1.2 W
Explosion protection:
Category II 2 (1/2) GD EEx d [ia/ib] IIC
Approval PTB 97 ATEX 1074 U
Uo ) 23.8 V Io ) 89.5 mA Po ) 534 mW
IIC Safety values (linear)
Co ) 87 nF Lo ) 0.5 mH
IIC Safety values Uo ) 0.7 V Io ) 3 mA Po ) 2 mW
(trapeze R i = 8.28 k1) for input 5-6 Co ) 53 F Lo ) 50 mH Ci ) 1.65 nF
Ordering details
Type Order No.
Transmitter power supply, Ex-i FB 3201 B GHG 127 0000 B3201
+
-
+
4 -20 mA
-
+
4 - 20 mA
1 2 3 4 5 6
FBLocal
Remote
Bus I/O
2/22
FB 3202
HART
Analog Input
Transmitter Power Supply
Product features
• Power supply for 2- and 3-wire • Intrinsically safe approval
4 - 20 mA transmitters • Line monitor
• HART compatible • Zone 1 mounted
• HART communicationn via fieldbus or • Can be unplugged during operation
local RS 485 interface (see conduit) (hot swap)
• Galvanic isolation • Input isolator with HART communication
• EMC to EN 61326 or NE21 for seperately powered field devices
2
Input:
Field device power supply 16,5 V (20 mA) incl. 250 1
Input range 4 - 20 mA (0 - 26 mA) HART
Input impedance 15 1 (at 5 - 6) 236 1 (at 1 - 6 HART)
Internal impedance (terminal 2-5) 315 1
Linearity < 0.1 %
Temperature drift < 0.1 % / 10 K
min. 1 mA
Line monitor
max. 22 mA, programmable
Conversion time ) 50 msec
Power consumption 1.2 W
Explosion protection:
Category II 2 (1/2) GD EEx d [ia/ib] IIC
Approval PTB 97 ATEX 1074 U
Uo ) 27 V Io ) 92 mA Po ) 619 mW
IIC Safety values (linear)
Co ) 73 nF Lo ) 0.4 mH
IIC Safety values Uo ) 0.7 V Io ) 3 mA Po ) 2 mW
(trapeze R i = 8.28 k1) for input 5-6 Co ) 53 F Lo ) 50 mH Ci ) 1.65 nF
IIC Safety values Uo ) 8.2 V Io ) 56 mA Po ) 310 mW
(trapeze R i = 447 1) for input 1-6 Co ) 1.1 F Lo ) 1 mH Ci ) 1.65 nF
Ordering details
Type Order No.
HART analog input, Ex-i FB 3202 B GHG 127 0000 B3202
1+ HART -6
HART
FB Remote I/O
2/23
FB 3203
HART
Analog Input
Transmitter Power Supply
Product features
• Power supply for 2- and 3-wire • Intrinsically safe approval
4 - 20 mA transmitters • Line monitor
• HART compatible • Zone 1 mounted
• HART communicationn via fieldbus or • Can be unplugged during operation
local RS 485 interface (see ComUnit) (hot swap)
• Galvanic isolation • Input isolator with HART communication
• EMC to EN 61326 or NE21 for seperately powered field devices
Input:
Field device power supply 15 V (20 mA) incl. 250 1
Input range 4 - 20 mA (0 - 26 mA) HART
Input impedance 15 1 (at 5 - 6) 236 1 (at 1 - 6 HART)
Internal impedance (terminal 2-5) 315 1
Linearity < 0.1 %
Temperature drift < 0.1 % / 10 K
min. 1 mA
Line monitor
max. 22 mA, programmable
Conversion time ) 50 msec
Power consumption 1.2 W
Explosion protection:
Category II 2 (1/2) GD EEx d [ia/ib] IIC
Approval PTB 97 ATEX 1074 U
Uo ) 24.9 V Io ) 77 mA Po ) 478 mW
IIC Safety values (linear)
Co ) 83 nF Lo ) 0.5 mH
IIC Safety values Uo ) 0.7 V Io ) 3 mA Po ) 2 mW
(trapeze R i = 8.28 k1) for input 5-6 Co ) 53 F Lo ) 50 mH Ci ) 1.65 nF
IIC Safety values Uo ) 8.2 V Io ) 56 mA Po ) 310 mW
(trapeze R i = 447 1) for input 1-6 Co ) 1.1 F Lo ) 1 mH Ci ) 1.65 nF
Ordering details
Type Order No.
HART analog input, Ex-i FB 3203 B GHG 127 0000 B3203
1+ HART -6
HART
FB Remote I/O
2/24
FB 3204 - FB 3205
Analog Input
HART Transmitter Power Supply,
4 Channels
Product features
• Zone 1 or Zone 2 mounted • Simulation for commissiong and service
• Any slot position (forcing)
• Can be unplugged in Zone 1 during operation • Self configurating after replacement
• Power supply for 2 wire converters • Line monitor (LFD)
• Input isolator for powered devices • Permanently self-monitoring
• HART communication via fieldbus • Module TAG and channel-TAG
• Galvanic isolation between input and BUS • EMC to EN 61326 or NE21
(group isolation)
2
Input:
Power supply 15 V (20 mA)
Input impedance 15 1 (stat.) no HART
Input range 0/4 - 20 mA (0 ... 26 mA)
Linearity 0.1 %
Temperature drift 0.1 % / 10 K
min. 1 mA
Line monitor
max. 22 mA programmable
Scanning time 6.5 ms
80 ms (4 channels)
Memory update time
130 ms during HART
Power consumption 3W
Explosion protection:
Category II 2 (1/2) GD EEx d [ia/ib] IIC
Approval PTB 97 ATEX 1074 U
Uo ) 28 V Io ) 90 mA Po ) 626 mW
IIC Safety values (linear)
Co ) 69 nF Lo ) 0.4 mH
IIC Safety values (trapeze R i = 7.1 k1) Uo ) 0.7 V Io ) 2.3 mA Po ) 2 mW
for inputs 3-4, 7-8, 11-12, 15-16 Co ) 53 F Lo ) 50 mH Ci ) 1.2 nF
Ordering details
Type Order No.
Analog input, 4 chan., Ex-i FB 3204 B GHG 127 0000 B3204
HART analog input, 4 chan., Ex-i FB 3205 B GHG 127 0000 B3205
Notes:
Supply circuits: 1-2, 5-6, 9-10, 13-14
active inputs: 3-4, 7-8, 11-12, 15-16, no HART
CH1 + - + - + - + - CH2
1 2 3 4 5 6 7 8
CH3 CH4
9 10 11 12 13 14 15 16
LB
FB REMOTE I/O
Remote I/O
2/25
FB 3302
HART
Input Isolator, Ex-e
Transmitter Power Supply
Product features
• Input isolator for 2-wire transmitters • HART communication via field bus or
• Zone 1 mounted service bus
• Any slot position • Galvanic isolation between input
• Can be unplugged during operation and the BUS
(hot swap) • EMV acc. to EN 61326 and NE21
• Access to Ex-e connections possible • Line monitor
when voltfree
Input:
Field device power supply 16.5 V (20 mA) incl. 250 1
Input range 4 - 20 mA (0 - 26 mA)
Input impedance 236 1 (1-6), 15 1 (5-6)
Linearity < 0.1 %
Temperature drift < 0.1 % / 10 K
min. 1 mA
Line monitor
max. 22 mA, programmable
Scanning time approx. 6.5 ms
Conversion time approx. 50 ms
Processing time approx. 50 ms
Connection 2 m cable tails to Ex-e terminals
Power consumption 1.2 W
Explosion protection:
Category II 2 GD EEx d IIC
Approval PTB 97 ATEX 1074 U
Ordering details
Type Order No.
HART supply, input isolator,
Ex-e, cable tails FB 3302 BS200 GHG 127 0000 B3302
HART supply, input isolator,
Ex-e, 80 cm wire ends FB 3302 B-080 GHG 127 0001 B3302
HART supply, input isolator,
Ex-e, 150 cm wire ends FB 3302 B-150 GHG 127 0002 B3302
HART supply, input isolator,
Ex-e, 200 cm wire ends FB 3302 B-200 GHG 127 0003 B3302
+ + - -
1 2 5 6
FB Remote I/O
2/26
FB 3305
HART Transmitter Power Supply
Input Isolator, 4 Channels, Ex-e
Product features
• Mounted in Zone 1 or Zone 2 • Simulation for commissioning and service
• Any slot position (forcing)
• Can be unplugged when Ex-e circuits are • Self configurating after replacement
volt free • Line monitor (LFD)
• Power supply for 2-wire transmitters • Permanently self-monitoring
• Input isolator for separately powered devices • Module-TAG and channel-TAG
• Galvanic isolation between the inputs and • EMC to EN 61326 or NE21
the field bus (group isolation)
2
Input:
15 V (20 mA)
Transmitter supply
offering HART communications
Input range 4 - 20 mA (0 - 20 mA)
Input impedance 15 1 (stat), non HART
Current limit approx. 26 mA
Linearity 0.1 %
Temperature drift 0.1 % / 10 K
min. 1 mA
Line monitor
max. 22 mA selectable
80 ms or 130 ms
Memory update period for 4 channels
during HART communications
Connection 2 m cable tails to Ex-e terminals
Power consumption 3W
Explosion protection:
Category II 2 GD EEx d IIC
Approval PTB 97 ATEX 1074 U
Ordering details
Type Order No.
HART Transm. supply, inp. 4 chan.,
Ex-e, 200 cm cable tail FB 3305 BS200 GHG 127 0000 B3305
HART Transm. supply, inp. 4 chan.,
Ex-e, 80 cm wire ends FB 3305 B-080 GHG 127 0001 B3305
HART Transm. supply, inp. 4 chan.,
Ex-e, 150 cm wire ends FB 3305 B-150 GHG 127 0002 B3305
HART Transm. supply, inp. 4 chan.,
Ex-e, 200 cm wire ends FB 3305 B-200 GHG 127 0003 B3305
Notes:
Supply circuits: 1-2, 5-6, 9-10, 13-14
Active inputs: 3-4, 7-8, 11-12, 15-16 no HART
CH1 + - + - + - + - CH2
1 2 3 4 5 6 7 8
CH3 CH4
9 10 11 12 13 14 15 16
LB
FB REMOTE I/O
Remote I/O
2/27
Analog Output, HART
Product Overview
Product features
• Zone 1 or Zone 2 mounted
• Suitable for rough ambient conditions (potted)
• Single channel with high integrity or
4 channel compact modules
• Single channel- and mult-channel modules
can be mixed mounted
• Any slot position
• Can be unplugged in Zone 1 during operation
(hot swap)
• Output for positioner, I/P-converter, display,
valves
• Resolution 12 bit for 0-20 mA
• Alternatively connection to flame proof
field devices
• Single channel modules are galvanically
isolated between channels
• 4-channel modules are galvanically isolated
between output and bus (group isolation)
• Simulation for commissioning and service
(forcing)
• Self configurating after replacement
• HART communication via Profibus with FDT or
via Service bus (depends on version)
• Line monitor (LFD)
• Permanently self-monitoring
• Selectable output drive in case of faults
(depends on version)
• Short circuit protected
• Output with watch dog circuit for fatal errors
• Module TAG and channel TAG depends on
version
• Same Nos. of modules with- and without
redundancy
• Version dependancy see comm. units
• EMC to EN 61326 or NE21
Available modules
FB 4201 Analog output, 750 1
FB 4X02 Analog output, HART, 750 1
FB 4205 Analog output, HART, 4 chan., group isolation
Valve Positioner
I/P 0000
I/P converter Display
Hand-held
configurator
2/28
FB 4201
Analog Output
Product features
• Output isolator for 4 - 20 mA, • Intrinsically safe approval
• Indicators, positioners, • Line monitor
I/P converters • Zone 1 mounted
• Galvanic isolation • Can be unplugged during operation
• EMC to EN 61326 or NE21 (hot swap)
Output:
Max. load 750 1
2
Output current 4 - 20 mA (short circuit protected)
Imin/max 0/25 mA (1 mA for LFD)
Linearity < 0.1 %
Temperature drift < 0.1 % / 10 K
Line monitor > 850 1 ... 4 k1
Conversion time ) 50 msec
Watch dog Output OFF 0.5 s after serious fault
Power consumption 0.8 W
Explosion protection:
Category II 2 (1/2) GD EEx d [ia/ib] IIC
Approval PTB 97 ATEX 1074 U
Uo ) 27.3 V Io ) 87 mA Po ) 595 mW
IIC Safety values (linear)
Co ) 72 nF Lo ) 0.4 mH
Ordering details
Type Order No.
Analog output, Ex-i FB 4201 B GHG 127 0000 B4201
0000
FB Remote I/O
2/29
FB 4202
HART
Analog Output
Product features
• Output isolator for 4 - 20 mA, • Intrinsically safe approval
indicators, positioners, I/P converters • Line monitor
• HART compatible • Zone 1 mounted
• HART communication via fieldbus or • Can be unplugged during operation
local RS 485 interface (hot swap)
• Galvanic isolation • Optional bus independent shut down
• EMC to EN 61326 or NE21
Output:
Max. load 750 1
Output current 0/4 - 20 mA (short circuit protected)
Imin/max 0/25 mA (1 mA for LFD)
Linearity < 0.1 %
Temperature drift < 0.1 % / 10 K
Line monitor > 850 1 ... 4 k1
Conversion time ) 50 msec
Watch dog Output OFF 0.5 s after serious fault
Power consumption 0.8 W
Explosion protection:
Category EEx d [ia/ib] IIC
Approval PTB 97 ATEX 1074 U
0000 Uo ) 27.3 V Io ) 87 mA Po ) 595 mW
IIC Safety values (linear)
Co ) 72 nF Lo ) 0.4 mH
HART
Ordering details
Type Order No.
HART analog output, Ex-i FB 4202 B GHG 127 0000 B4202
HART analog output, Ex-i, shut-down input FB 4202 C GHG 127 0000 C4202
FB Remote
LB/FB I/OI/O
Remote
0000
HART
FB Remote
LB/FB I/O
Remote I/O
regular version
2/30
FB 4204 - FB 4205
HART Analog Output,
4 Channels
Product features
• Zone 1 or Zone 2 mounted • Simulation for commissiong and service
• Any slot position (forcing)
• Can be unplugged in Zone 1 during operation • Self configurating after replacement
• Output isolator for indicators, Display, • Line monitor (LFD) – version dependent
IP converter • Permanently self-monitoring
• HART communication via fieldbus • Module TAG and channel-TAG
• Galvanic isolation between input and bus • Optional bus independent shut down input
(group isolation) • EMC to EN 61326 or NE21
2
Input:
Max. load 750 1
Output current 4-20 mA (0 ... 25 mA short protected)
Linearity 0.1 %
Temperature drift 0.1 % / 10 K
Line monitor (LFD) min. 1 mA (version dependent)
Threshold > 850 1
output OFF 0.5 s
Watch dog circuit
after serious faults
Scanning time 6.5 ms
58 ms (4 channels)
0000 Memory update time
110 ms during HART
Power consumption 3W
Explosion protection:
I/P Category II 2 (1/2) GD EEx d [ia/ib] IIC
Approval PTB 97 ATEX 1074 U
Uo ) 27.3 V Io ) 93 mA Po ) 635 mW
IIC Safety values (linear)
Co ) 74 nF Lo ) 0.4 mH
+ – + – + – + –
1 2 3 4 5 6 7 8
CH1 CH4 Ordering details
Type Order No.
Analog output, 4 chan., Ex-i FB 4204 B GHG 127 0000 B4204
HART analog output, 4 chan., Ex-i FB 4205 B GHG 127 0000 B4205
HART analog out, 4 chan., Ex-i, shut-down input FB 4205 C GHG 127 0000 C4205
LBRemote
FB REMOTEI/O HART analog out, 4 chan., Ex-i, with LFD FB 4205 D GHG 127 0000 D4205
0000
I/P
+ — + — + — + —
1 2 3 4 5 6 7 8
CH1 CH4
LBRemote
FB REMOTEI/O
regular version
2/31
FB 4302
HART
Analog Output, Ex-e
Product features
• Output isolator for 4 - 20 mA, • Line monitor
indicators, positioners, I/P converters • Zone 1 mounted
• Galvanic isolation • Can be unplugged during operation
• EMC to EN 61326 or NE21 (hot swap)
• HART compatible • Ex-e terminal accessible when voltfree
• HART communicationn via fieldbus or • Optional bus independent shut down
local RS 485 interface
Output:
Max. load 750 1
Output current 0/4 - 20 mA (short circuit protected)
Imin/max 0/25 mA (1 mA for LFD)
Linearity < 0.1 %
Temperature drift < 0.1 % / 10 K
Line monitor > 850 1 ... 4 k1
Watch dog Output OFF 0.5 s after serious fault
Connection 2 m cable tail to Ex-e terminals
Conversion time ) 50 msec
Power consumption 1W
Explosion protection:
Category II 2 GD EEx d IIC
Approval PTB 97 ATEX 1074 U
0000
FB Remote I/O
0000
HART
FB Remote
LB/FB RemoteI/O
I/O
regular version
2/32
FB 4305
HART Output Isolator,
4 Channels, Ex-e
Product features
• Mounted in Zone 1 or Zone 2 • Simulation for commissioning and service
• Any slot position (forcing)
• Can be unplugged when Ex-e circuits are • Self configurating after replacement
volt free • Permanently self-monitoring
• Output isolator for proportional valves, • Line monitor (LFD)
displays or IP converters • Module-TAG and channel-TAG
• HART option via fieldbus • Optional bus independent shut down input
• Galvanic isolation between outputs and bus • EMC to EN 61326 or NE21
2
Output:
Load 750 1 (at 22 mA)
Output range 0/4 - 20 mA (short protected)
Current limit Approx. 25 mA
Linearity 0.1 %
Temperature drift 0.1 % / 10 K
Line monitor (LFD) min. 1 mA (version dependent)
Watch dog circuit Output OFF 0.5 s after serious fault
58 ms or 110 ms
Memory update period for 4 channels
during HART communications
Connection 2 m cable tails to Ex-e terminals
0000 Power consumption 3W
Explosion protection:
Category II 2 GD EEx d IIC
I/P Approval PTB 97 ATEX 1074 U
Ordering details
+ – + – + – + –
Type Order No.
1 2 3 4 5 6 7 8
CH1 CH4 HART output isolator, 4 chan,
Ex-e, 200 cm cable tail FB 4305 BS200 GHG 127 0000 B4305
HART output isolator, 4 chan,
Ex-e, 80 cm wire ends FB 4305 B-080 GHG 127 0001 B4305
HART output isolator, 4 chan,
Ex-e, 150 cm wire ends FB 4305 B-150 GHG 127 0002 B4305
LBRemote
FB REMOTEI/O HART output isolator, 4 chan,
Ex-e, 200 cm wire ends FB 4305 B-200 GHG 127 0003 B4305
shut down input option HART output isolator, 4 chan,
Ex-e, 200 cm wire ends, shut down input FB 4305 C-200 GHG 127 0003 C4305
HART analog out, 4 chan,
Ex-e, with LFD, 200 cm wire ends FB 4305 D-200 GHG 127 0003 D4305
0000
I/P
+ — + — + — + —
1 2 3 4 5 6 7 8
CH1 CH4
LBRemote
FB REMOTEI/O
regular version
2/33
RTD Transmitter
Thermocouple Transmitter, Voltage Converter
Product Overview
Product features
• Zone 1 or Zone 2 mounted
• Suitable for rough ambient conditions (potted)
• Single channel high integrity or
4 channel compact modules
• Single channel- and mult-channel modules
can be mixed mounted
• Can be unplugged in Zone 1 during operation
(hot swap)
• Input for RTD, thermocouples and DC-voltage
• Resolution 16 bit for the whole range (lower
depending on the span)
• Single channel modules are galvanically
isolated between channels
• 4 channel modules are galvanically
isolated between input and system bus
(group isolation)
• Simulation for commissioning and service
(forcing)
• Self configurating after replacement
• Line monitor (LFD)
• Permanently self-monitoring
• Module TAG and channel TAG
depending on version
• Same Nos. of modules with- and without
redundancy
• Version dependancy see comm. units
• EMC to EN 61326 or NE21
Available modules
FB 5201 RTD transmitter
FB 5202 thermocouple transmitter (mV)
FB 5204 RTD transmitter 4 channels
FB 5205 thermocouple transmitter (mV) 4 channels
CJC
FB 5206 voltage converter (10 V)
Thermocouple Thermocouple
summator circuit
Thermocouple RTD
differential measurement 4-wire circuit
RTD RTD
3-wire circuit 2-wire circuit
2/34
FB 5201
RTD Transmitter
Product features
• Mounted in Zone 1 or Zone 2 hazardous areas • Simulation for commissioning and service
• Any slot position (forcing)
• Can be unplugged in Zone 1 during operation • Self configurating after replacement
(hot swap) • Line monitor (LFD)
• Input for 2-, 3-, 4-wire RTD (temperature) • Permanently self-monitoring
• Galvanic isolation between the input and • Module-TAG and channel-TAG
the field bus • EMC to EN 61326 or NE21
2
Input:
Range 10 - 400 1 (500 1 incl. wire resistance)
Smallest span 20 1 for 0.1 % accuracy
Wire resistance 50 1 max. each wire
Pt100 line fault (LFD) > 1 k1
short < 10 1
Linearity < 0.025 % (widest span)
Temperature drift < 0.025 % / 10 K (widest span)
Sensor current 200 +A
< 20 ms without LFD
Conversion time
< 125 ms with LFD
Power consumption 0.45 W
Explosion protection:
Category II 2 (1/2) GD EEx d [ia/ib] IIC
Approval PTB 97 ATEX 1074 U
Uo ) 2.7 V Io ) 43 mA Po ) 93 mW
IIC Safety values (trapeze R i = 330 1)
Co ) 3 +F Lo ) 10 mH Ci ) 1.25 nF
Ordering details
Type Order No.
RTD transmitter, Ex-i FB 5201 B GHG 127 0000 B5201
slide
wire
2 wire
3 wire
4 wire
1 2 3 4 5 6
mV
FB Remote I/O
2/35
FB 5202
Thermocouple
Transmitter
Product features
• Mounted in Zone 1 or Zone 2 hazardous areas • Simulation for commissioning and service
• Any slot position (forcing)
• Can be unplugged in Zone 1 during operation • Self configurating after replacement
(hot swap) • Line monitor (LFD)
• Input for thermocouples or mV • Permanently self-monitoring
• Galvanic isolation between the input and • Module-TAG and channel-TAG
the field bus • EMC to EN 61326 or NE21
Input:
U, B, E, T, K, S, R, L, J, N, Pallaplat
Range
-75 mV .... + 75 mV
Compensation internal (at connector) or external
CJC Pt100 sensor current 200 +A
< 20 ms without LFD
Conversion time for external CJC
< 80 ms with LFD
< 120 ms without LFD
Conversion time for internal CJC
< 240 ms with LFD
Linearity < 0.1 % (at 5 mV span), 0.01 % (0-50 mV)
Temperature drift < 0.1 % / 10 K, 0,025 % (widest span)
Line fault (LFD) > 1 k1
Power consumption 0.45 W
Explosion protection:
Category II 2 (1/2) GD EEx d [ia/ib] IIC
Approval PTB 97 ATEX 1074 U
Uo ) 1.8 V Io ) 43 mA Po ) 67 mW
IIC Safety values (trapeze Ri = 330 1)
Co ) 8.7 +F Lo ) 10 mH Ci ) 103 nF
Ordering details
Category Type Order No.
Thermocouple transmitter, mV Ex-i FB 5202 B GHG 127 0000 B5202
RTD
CJC
+ -
1 2 3 4 5 6
mV
FB Remote I/O
2/36
FB 5204
Pt100, Ni100, Slide Wire Sensors
4 Channels
Product features
• Mounting in Zone 1 or Zone 2 • Simulation for commissioning and service
• Any slot position (forcing)
• Can be unplugged in Zone 1 • Self configurating after replacement
during operation (hot swap) • Line monitor (LFD)
• 2-, 3-, 4-Ltr. Pt100, Pt1000 (RTD) • Permanently self-monitoring
or slide wire sensors • Module-TAG and channel-TAG
• Galvanic isolation between inputs • EMC to EN 61326 or NE21
and the bus (group isolation)
2
Input:
Pt100 range (-200 ... + 850 °C) 18 - 390 1 (500 1 incl. line)
Pt200 (37-780 1), Pt500 (92-1952 1)
Pt1000 (185-3905 1)
RTD Range
Ni100 (69-270 1), Ni500 (345-1350 1)
Ni1000 (690-2700 1)
Slide wire sensors 0 - 10,000 1
Smallest span for 0.1 % 50 1 (or 1/10 of full scale)
Sensor current < 0.22 mA
Wire resistance < 50 1 each wire
Line break/short circuit programmable
Line break detection (Pt100) > 1 k1
Line short detection (Pt100) < 10 1
Non linearity 0.025 % of max. span
Temperature drift 0.025 % of max. span / 10 K
Scan time 6.5 ms
< 500 ms (4 channels)
Conversion time
< 1 s (for 4 x 3 wire Pt100)
Busy after download 5-15 s
Connection screw plug-in or wire clamp connectors
Power consumption 0.6 W
Explosion protection:
Category II 2 (1/2) GD EEx d [ia/ib] IIC
Approval PTB 97 ATEX 1074 U
Uo ) 6.8 V Io ) 70 mA Po ) 118 mW
II C Safety values (trapeze R = 103 1)
Co ) 1 +F Lo ) 5 mH
Ordering details
2 wire
Category Type Order No.
Slide wire
RTD, slide wire transmitter, 4 channel Ex-i FB 5204 B GHG 127 0000 B5204
or
3 wire
Temperature 2 wire
3 wire
4 wire
CH1 CH2
1 2 3 4 5 6 7 8
+
9 10 11 12 13 14 15 16
CH3 CH4
LB
FBRemote
RemoteI/O
I/O
2/37
FB 5205
Thermocouples, mV
4 Channels
Product features
• Mounting in Zone 1 or Zone 2 • Simulation for commissioning and service
• Any slot position (forcing)
• Can be unplugged in Zone 1 • Self configurating after replacement
during operation (hot swap) • Line monitor (LFD)
• Thermocouples or mV signals • Permanently self-monitoring
• Galvanic isolation between the inputs • Module-TAG and channel-TAG
and the bus and between channels • EMC to EN 61326 or NE21
Input:
Thermocouples Type U, B, E, T, K, S, R, L, J, N, Pallaplat.
Measuring range -65 mV ... +75 mV
Smallest span for 0.1 % 5 mV
Compensation internal (built-in) or external (e.g. thermostat)
Line fault detection (LFD) > 1 k1
Non linearity 0.01 % (0-50 mV) or 0.025 % (max. span)
Temperature drift 0.02 % / 10 K (0-50 mV)
Cycle time (com unit) 6.5 ms
< 200 ms (4 channels) without LFD
Conversion time
< 350 ms (4 channels) with LFD
Connection screw plug-in or wire clamp connectors
1.5 kV input - input
Test voltage
1.5 kV input - bus and power
Power consumption approx. 1 W
Explosion protection:
Category II 2 (1/2) GD EEx d [ia/ib] IIC
Approval PTB 97 ATEX 1074 U
Uo ) 1 V Io ) 71 mA Po ) 62 mW
IIC Safety values (trapeze Ri = 500 1)
Co ) 33 +F Lo ) 5 mH
Ordering details
Category Type Order No.
Thermocouple transmitter, 4 channels EExia FB 5205 B GHG 127 0000 B5205
CH1 CH2
1 2 5 6
+ +
9 10 13 14
CH3 VST
CJC CH4
FIELD
FB BUS
Remote I/O
2/38
FB 5206
Voltage Converter
Product features
• Mounting in Zone 1 or Zone 2 • Simulation for commissioning and service
hazardous areas (forcing)
• Any slot position • Self configurating after replacement
• Can be unplugged in Zone 1 • Permanently self-monitoring
during operation (hot swap) • Module-TAG and channel-TAG
• Input for voltage signals • EMC to EN 61326 or NE21
• Galvanic isolation between the input
and the field bus
2
Input:
Range 0 V to +10 V
Smallest span for 0,1 % 500 mV
Input impedance 100 k1
Line fault detection (LFD) None
Linearity < typ. 0.1 %
Temperature drift < 0.1 % / 10 K
Conversion time 100 ms
Power consumption < 0.45 W
Explosion protection:
Category II 2 (1/2) GD EEx d [ia/ib] IIC
Approval PTB 97 ATEX 1074 U
Uo ) 0.9 V Io ) 0.2 mA Po ) 0.2 mW
IIC Safety values (linear)
Co ) 53 +F Lo ) 100 mH Ci ) 52 nF
Ordering details
Type Order No.
Voltage converter Ex-i FB 5206 B GHG 127 0000 B5206
+ -
1 2 3 4 5 6
LB Remote
FB Remote I/O
I/O
2/39
Digital Output
Product Overview
Product features
• Zone 1 or Zone 2 mounted
• Suitable for rough ambient conditions (potted)
• Single channel high integrity or
8 channel compact modules
• Single channel- and mult-channel modules
can be mixed mounted
• Any slot position
• Can be unplugged in Zone 1 during operation
(hot swap)
• Output for intrinsically safe solenoid valves,
sounders, and LEDs, relays for Ex-d solenoid
valves
• Alternatively connection to flame proof
field devices
• Modules are galvanically isolated between
each channel or galvanically isolated between
input and system bus (group isolation)
• Simulation for commissioning and service
(forcing)
• Self configurating after replacement
• Positive or negative logic selectable
depending on the version
• Line monitor (LFD) depending on the version
• Permanently self-monitoring
• ON/OFF delay depending on version
• Output level selectable on fault condition
depending on the version
• Output with watch dog circuit for fatal errors
• Module TAG and channel TAG depending on
version
• Same Nos. of modules with- and without
redundancy
• Version dependancy see comm. units
• EMC to EN 61326 or NE21
Available modules
FB 2XZZ digital output, 2 feed back inputs
FB 6301 relay output, 2 channels 24V, isolated
FB 6305 relay output, 4 channels 230V, isolated
FB 6306 relay output, 8 channels 24V, isolated
FB 6X08 digital output, 8 channels, group isolation
FB 6210-6215 digital output, 4 channels, group isolation
Solenoid Sounder
2/40
FB 6208
Digital Output
8 Channels, Low Power
Product features
• Zone 1 or Zone 2 mounted • Self configurating after replacement
• Any slot position • Positive- or negative logic selectable
• Active 20 V output to switch LEDs, indicators, • Line monitor (LFD)
or low power solenoid valves • Permanently self-monitoring
• Can be unplugged in Zone 1 during operation • ON/OFF delay
• Galvanical isolation between input and • Shut down input
system bus (group isolation) • Module TAG and channel TAG
• Simulation for commissioning and service
(forcing)
• EMC to EN 61326 or NE21
2
Output:
20 V, 8 mA per channel
Digital output (active/short protected)
21.6 V, 5.2 mA (model C6208)
Scanning time 6.5 ms
LFD test current 0.33 mA
output volt-free 0.5 sec.
Watch dog circuit
after serious faults
Power consumption 2.2 W
Explosion protection:
Category II 2 (2) GD EEx d [ib] IIC
Approval PTB 97 ATEX 1074 U
Uo ) 28 V Io ) 13.5 mA Po ) 376 mW
IIC Safety values (rectangular) model B6208
Co ) 76 nF Lo ) 0.5 mH
Uo ) 30 V Io ) 13.5 mA Po ) 404 mW
IIC Safety values (rectangular) model C6208
Co ) 62 nF Lo ) 0.5 mH
Ordering details
Type Order No.
Digital output, 8-chan., Ex-i FB 6208 B GHG 127 0000 B6208
Digital output, 8-chan., 21.6 V, Ex-i FB 6208 C GHG 127 0000 C6208
CH1 1 2 3 4 5 6 7 8 CH4
CH5 9 10 11 12 13 14 15 16 CH8
+ + + + —
FIELD
FB BUS
Remote I/O
2/41
FB 6210 - FB 6215
Digital Output
4-channels, IS power
Product features
• Mounting in Zone 1 oder Zone 2 • Self configurating after replacement
• Output for intrinsically safe solenoid valves, (plug and play)
for sounders and LEDs • Permanently self monitoring
• Positive or negative logic selectable • ON/OFF delay
• any slot position • optional Shut down input independant of the bus
• galvanic isolation between outputs and BUS • Output with watch dog circuit for fatal errors
(group isolation) • Module-TAG and channel-TAG
• Simulation for commissioning and service • EMC to EN 61326 or NE21
(forcing)
Power Supply:
24 V DC, 9 W
External Power via Booster Ex-e module front end connection.
Slave can be fully fitted even in combination
with other modules.
Output:
Drive capability see ordering details
Line monitor (2 ms test pulse) every 2.5 s (LFD can be deactivated)
LFD reaction time 10 s (worst case)
Output response time > 10 ms (depending on the master)
Scan rate 6.5 ms
Output OFF 0.5 s
Watch dog
after serious fault
screw plug-in or wire clamp connectors
Connection for IS circuits, wire ends
for Ex-e booster
Power consumption 0.6 W
U Ra
Ordering details
limit Po Co Lo Type Order No.
U/V Ra/1 mA LFD/1 Uo/V Io/mA mW nF mH
24 V
24.5 370 55 90 ... 12000 27.8 90,4 629 81 0.2 FB 6210B GHG 127 0000 B6210
boost FIELD BUS
24.5 320 60 110 ... 12000 27.8 107 744 81 0.2 FB 6211B GHG 127 0000 B6211
shut downregular
input option 17.0 185 70 95 ... 8000 19.8 142 705 117 0.5 FB 6212B GHG 127 0000 B6212
version
23.0 290 60 110 ... 10000 26 110 714 96 0.2 FB 6213B GHG 127 0000 B6213
23.0 355 55 90 ... 10000 26 88.7 578 96 0.2 FB 6214B GHG 127 0000 B6214
16.2 78 80 100 ... 8500 18.9 286 1350 150 0.17 FB 6215B FB 6215B
24 V
boost FIELD BUS
2/42
FB 6301
Relay Output
2 Channels, Ex-e
Product features
• Zone 1 mounted • Switches 24 V or 230 V power circuits and
• Any slot position Exd solenoid valves
• Can be unplugged during operation • Output watch dog circuit
(hot swap) • Galvanic isolation between the output and
• Access to Ex-e connections possible the BUS as well as between outputs
when voltfree • EMC to EN 61326 or NE21
2
Output:
Relay rating
Voltage rating (nominal) 24 V DC, 24 V AC (30 V max.)
Current rating 1 A, AC/DC (resistive load)
Switch power 30 VA, 30 W
Electrical lifetime 0.5 Mio. cycles
Min. switching capability > 1 V, > 1 mA
Contact material AgPd gold plated
Watch dog Output OFF 0.5 s after serious fault
Response time approx. 20 ms (depending on bus cycle time)
Scanning time approx. 6.5 ms
Connection 2 m cable tail to Ex-e terminals
Power consumption 0.65 W
Explosion protection:
Category II 2 GD EEx d IIC
Approval PTB 97 ATEX 1074 U
Ordering details
Type Order No.
Relay output, 2-chan., Ex-e, 200 cm cable tail FB 6301 BS200 GHG 127 0000 B6301
Relay output, 2-chan., Ex-e, 80 cm wire ends FB 6301 B-080 GHG 127 0001 B6301
Relay output, 2-chan., Ex-e, 150 cm wire ends FB 6301 B-150 GHG 127 0002 B6301
Relay output, 2-chan., Ex-e, 200 cm wire ends FB 6301 B-200 GHG 127 0003 B6301
Relay output, 2-chan., Ex-e, 200 cm cable tail
230 V, 1A (ohmic load) FB 6301 HS200 GHG 127 0000 H6301
Relay output, 2-chan., Ex-e, 200 cm wire ends
230 V, 1A (ohmic load) FB 6301 H-200 GHG 127 0003 H6301
pwr pwr
1 2 3 4 5 6
CH1 CH2
FIELD
FB BUS
Remote I/O
2/43
FB 6305
Relay Output
4 Channels
Product features
• Output with relay-contacts for LEDs, • Simulation for commissioning and
annunciators or valves service (forcing)
• Zone 1 or Zone 2 mounted • Self configurating after replacement
• Any slot position • Positive- or negative logic selectable
• Can be unplugged when Ex-e circuits • Permanently self-monitoring
are voltfree • ON/OFF delay
• Galvanical isolation between outputs • Module TAG and channel-TAG
and system bus • EMC to EN 61326 or NE21
Output:
30 V DC, 1 A, 30 W (resistive load)
Relay contact/channel
230 V AC, 1 A, 230 VA (resistive load)
Contact material AgPd gold plated
Electrical lifetime 0.1 Mio. cycles
min. switching capability > 1 V, > 1 mA
Response time approx. 20 ms (depending on bus cycle time)
Scanning time 6.5 ms
Relay off 0.5 sec.
Watch dog circuit
after serious faults
2 m cable tail to
Connection
Ex-e terminals
Power consumption 1.2 W
Explosion protection:
Category II 2 GD EEx d IIC
Approval PTB 97 ATEX 1074 U
Ordering details
Type Order No.
Relay 230 V AC, 4-chan, Exe, 200 cm cable tail FB 6305 BS200 GHG 127 0000 B6305
Relay 230 V AC, 4-chan, Exe, 80 cm wire ends FB 6305 B-080 GHG 127 0001 B6305
Relay 230 V AC, 4-chan, Exe, 150 cm wire ends FB 6305 B-150 GHG 127 0002 B6305
Relay 230 V AC, 4-chan, Exe, 200 cm wire ends FB 6305 B-200 GHG 127 0003 B6305
pwr pwr
CH1 1 2 3 4 5 6 7 8 CH2
CH3 9 10 11 12 13 14 15 16 CH4
FB Remote
FIELD BUS I/O
2/44
FB 6306
Relay Output
8 Channels
Product features
• Output with relay-contacts for LEDs, • Self configurating after replacement
annunciators or valves • Positive- or negative logic selectable
• Zone 1 or Zone 2 mounted • Permanently self-monitoring
• Any slot position • ON/OFF delay
• Can be unplugged when Ex-e circuits are • Module TAG and channel TAG
voltfree • EMC to EN 61326 or NE21
• Galvanic isolation between outputs and BUS
• Simulation for commissioning and service
(forcing) 2
Output:
Relay contact/channel 24 V AC/DC, 1 A, 30 W, 30 VA (resistive load)
Contact material AgPd gold plated
Electrical lifetime 0,5 Mio. cycles
min. switching capability > 1 V, > 1 mA
Response time approx. 20 ms (depending on bus cycle time)
Scanning time 6.5 ms
Relay off 0.5 sec.
Watch dog circuit
after serious faults
2 m cable tail to
Connection
Ex-e terminals
Power consumption 1.6 W
Explosion protection:
Category II 2 GD EEx d IIC
Approval PTB 97 ATEX 1074 U
Ordering details
Typ Order No.
Relay 24 V AC/DC, 8-chan.,
Ex-e, 200 cm cable tail FB 6306 BS200 GHG 127 0000 B6306
Relay 24 V AC/DC, 8-chan.,
Ex-e, 80 cm wire ends FB 6306 B-080 GHG 127 0001 B6306
Relay 24 V AC/DC, 8-chan.,
Ex-e, 150 cm wire ends FB 6306 B-150 GHG 127 0002 B6306
Relay 24 V AC/DC, 8-chan.,
Ex-e, 200 cm wire ends FB 6306 B-200 GHG 127 0003 B6306
pwr pwr
CH1 1 2 3 4 5 6 7 8 CH4
CH5 9 10 11 12 13 14 15 16 CH8
FB Remote
FIELD BUSI/O
2/45
FB 6308
Digital Output
8 Channels
Product features
• Output with active 20 V signal for low • Self configurating after replacement
power loads e.g. Input of control stations • Positive- or negative logic selectable
• Zone 1 or Zone 2 mounted • Permanently self-monitoring
• Any slot position • ON/OFF delay
• Can be unplugged when Ex-e circuits • Shut down input
are voltfree • Module TAG and channel TAG
• Galvanic isolation between input and • EMC to EN 61326 or NE21
BUS (group isolation)
• Simulation for commissioning and
service (forcing)
Output:
20 V, 8 mA per channel
Digital output (active/short protected)
21.6 V, 5.2 mA model C6308
Scanning time 6.5 ms
LFD test current 0.33 mA
output volt-free 0.5 sec.
Watch dog circuit
after a fatal error
2 m cable tail to
Connection
Ex-e terminals
Power consumption 2.2 W
Explosion protection:
Category II 2 GD EEx d IIC
Approval PTB 97 ATEX 1074 U
Ordering details
Type Order No.
Digital output, 8-chan., 20 V DC, Ex-e
200 cm cable tails FB 6308 BS200 GHG 127 0000 B6308
Digital output, 8-chan., 21.6 V DC, Ex-e
200 cm cable tails FB 6308 CS200 GHG 127 0000 C6308
Digital output, 8-chan., 20 V DC, Ex-e,
200 cm wire ends FB 6308 B-200 GHG 127 0003 B6308
CH1 1 2 3 4 5 6 7 8 CH4
CH5 9 10 11 12 13 14 15 16 CH8
+ + + + —
FIELD
FB BUS
Remote I/O
2/46
Gateway or ComUnit Properties
Selection Guide
The following table is intended to assist you in finding the best gateway or ComUnit for your
application.
Gateways LB 8103 or FB 8203 only support single width modules. All other gateways support
single channel high integrity modules as well as dual width multi channel modules. LB 8103 or
FB 8203 are available mainly as replacements. Gateways LB 8106, FB 8206 are mainly used when
the DCS prefers to configure the slaves on the basis of the GSE file only. This is possible with any
system which supports Profibus.
Profibus systems which offer more can make use of the superior properties of the UniCOM
gateways LB 8109 or FB 8209 (e.g. FDT or Siemens (PDM)). These are compatible with LB 8105 or
2
FB 8205 gateways offering additional CiR functionality independent of the process control system
or PLC (ONLINE configuration). LB 8105 or FB 8205 are mostly used in connection with ABB
systems.
Gateways LB 8107 and FB 8207 are reserved for MODBUS applications.
Gateways LB 8108 are mainly used in connection with NON intrinsically safe applications, where a
large number of digital inputs have to be processed.
Hardware Zone 2 GHG 127 0xxx H 8103 H 8105 H 8106 H 8107 H 8108 H 8109
Hardware Zone 1 GHG 127 0xxx H 8203 H 8205 H 8206 H 8207 H 8209
Properties/Firmware Version 4.X 6.X 6.X 7.X 8.X 9.X
Configuration software or DTM for FDT098 4/5/6 6 6
Configuration software or DTM for FDT1.2 7 ❍ ❍ 7 7
Configuration tool acts as Profibus Simulator PACTware EasyCom PACTware PACTware
Servicebus required
Servicebus useable ● ● ❍ ● ❍ ●
HART via Servicebus ❍ ❍ ❍ ❍ ❍
HART via Profibus ● ● ● ● ●
HART secondary variables synchronous data ❍ ❍ ❍ ❍ ❍
GSD/GSE file CGV40710 CGV61710 CGV61711 CGV61712 CGV61710
Profibus DP ● ● ● ● ●
Profibus DPV1 ● ● ● ● ●
Modbus ●
Redundancy ❍ ● ● ❍ ❍ ●
HCIR (system dependent ONLINE configuration) ● ● ● ● ● ●
CiR (system independent ONLINE configuration) ●
Time stamping (in cooperation with master) ●
1x01, 1x02, 1x03 ● ● ● ● ● ●
1x08 ● ● ● ● ●
1x07, 1x14, 1x15 ❍ ❍ ❍ ● ❍
2xxx, 2xxx (SIL) ● ● ● ● ● ●
3x01, 3x02, 3x03 ● ● ● ● ● ●
3x04, 3x05 ● ● ● ● ●
4x01, 4x02, 4x02 (SIL) ● ● ● ● ● ●
4x04, 4x05, 4x05 (SIL) ● ● ● ● ●
4x05 (LFD) ❍ ❍ ❍ ❍ ● ❍
5x01, 5x02 ● ● ● ● ● ●
5x04, 5x05 ● ● ● ● ●
5x06 ● ● ● ● ● ●
6x01 ● ● ● ● ● ●
6x04, 6x05, 6x06, 6x08, 6x08 (SIL) ● ● ● ● ●
6x10, 6x11, 6x12, 6x13, 6x14, 6x15 ● ● ● ● ●
6x10-6x14, 6x15 (SIL) ● ● ● ● ●
Analog chan. (max. depends on configuration) 48 80 80 80 80 24-80
Digital chan. (max. depends on configuration) 144 184 184 184 184 96-184
2/47
FB 8201 - FB 8204
Communication Interface
only for replacements
Product features
• Mounting in Zone 1 or Zone 2 • LED diagnostic indication
• Can be unplugged in Zone 1 during operation • HART communication on Profibus or
• Bumpless transition in redundant systems service bus depending on the version
• Self configurating in a redundant system • EMC to EN 61326 and NE21
(plug and play as from version V4.X)
• Non volatile memory for configuration and
parameter settings
Technical data
Profibus DP, DPV1, MODBUS RTU, Modicon
Fieldbus connection
other upon inquiry
Profibus 1500 kBaud
Transferrate
Modbus 38.4 kBaud
Power consumption 2W
defind by the field bus standard
Max. number of slaves per busline
255 (Modbus), 125 (Profibus)
Number of slaves per bus segment max. 31 (RS 485 Norm)
Repeaters between Master-Slave max. 3
depending on the comm unit version
Number of channels per substation
48-80 analog max., 144-192 digital max.
Ex-e bus terminals to RS485 standard
Connections via Backplane
power via power supply modules
FOL (fibre optic link) additional hardware required
Maximum bus extension (FOL) 1000 m (1.5 MBaud)
1000 m (187.5 kBaud)
Maximum bus extension (copper)
200 m (1.5 MBaud)
Address setting via configuration software
Profibus DPV1 to standard (address 126 ex works)
Redundant comm unit automatic as from version V4.X
Servicebus address 119 max. as of version V4.X
Explosion protection:
Category II 2 (1)GD EEx d [ia] IIC
Certificate of conformity PTB97 ATEX 1074U
Ordering details
Com Units for 48 analog / 144 digital channels
HART via Servicebus Type Order No.
Primary comm unit Redundant comm unit
Profibus (any Master) FB 8203 B03XX GHG 127 0309 B8203
Feldbus Redundant bus Redundancy Master dependant
Service bus Service bus MODBUS (RTU, Modicon) FB 8204 B03XX GHG 127 0309 B8204
local connection Redundancy Master dependant
2/48
FB 8203 - FB 8205
Communication Interface
Product features
Various communication modules are available Existing comm units therefore have to be fitted
depending on the application. with the appropriate firmware when newly
Comm. units are downwards compatible if kept developed I/O modules are to be employed.
within one series. Firmware Updates are The CDROM supplied with deliveries contains a
possible within such a series. Thus comm units README file which lists the supported I/O
using Firmware 3.09 can be updated to 3.22. modules and properties for each firmware
In the same way versions 4.14 can be updated version.
to 4.30.
Updates offer advantages if the master also
Please also ensure compatibilty for the
configuration software. CDROM versions 3.X
2
supports the new properties. Therefore P+F are meant for comm. unit versions 3.X only etc.
strives to implement integration tests with the Profibus applications require a GSE-file
master prior to new releases. (GSE = English GSD) also to be found on the
Different comm. units can operate on the same CDROM unless you are using a DPV1 master.
bus as long as the conditions are observed Profibus DPV1 applications employing the
which are detailed in the manuals. However, in a FDT concept transfer field device properties
redundant slave you must only use comm. units to the master during the installation of the
with identical versions. DTM (Device Type Manager). Other system
Comm. units always have to relate to the manufacturers make use of software drivers
connected I/O modules e.g. Siemens PDM V5.2
Ordering details
Com Unit for 48 analog / 144 digital channels
HART via Profibus Type Order No.
Profibus (any master) or FB 8203 H04XX GHG 127 04XX H8203
Profibus DPV1 compatible masters
Redundancy and HCIR master dependant only for replacement
Redundant comm. units can also be configured for non redundant systems.
The order number in front of the code letter „H “ indicates the Firmware and the
corresponding configuration software. „X “ = reserves space for the version number.
HART Communication on Profibus is possible even for systems which do not support
this feature themselves. In that case a class 2 master is used.
The following HART software is available ABB Smartvision, M&M Software, E&H Fieldcare, Emerson
AMS, Siemens PDM, PACTware etc. Secondary HART variables can be mapped to the Profibus
data exchange at request.
2/49
FB 8206
EasyCom Unit with Standard
GSE-Parameterization
Product features
• DCS configuration via GSE parameters • drives outputs to a defined position in case
(plug and play) of failure
• automatic data exchange (Standard Profibus) • non volatile memory for configuration and
• supports 1-8 channel I/O modules parameter settings
(multi channel) • LED diagnostic indication
• mounted in Zone 1 or Zone 2 • HART communication on Profibus
• can be unplugged in Zone 1 during operation • optional servicebus for extended diagnostics
(hot swap) and commissioning (forcing)
• ON/OFF delay for digital inputs (Filter, pulse • EMC to EN 61326 and NE21
extension)
• self configurating in a redundant system
(plug and play)
Technical data:
Profibus DP, DPV1
Fieldbus connection
others upon enquiry
HART communication to PNO standard
Transferrate Profibus up to 1500 kBaud
Power consumption 2W
defined by fieldbus specification
Max. number of slaves per busline
125 (Profibus), 119 (Servicebus)
Number of slaves per bus segment max. 31 (RS485 Standard)
Repeaters between Master-Slave max. 3
depending on the modules
Number of channels per substation
max. 80 analog, 192 digital
Ex-e bus terminals to RS485 Standard
Backplane Connections
power via power supply modules
FOL (fibre optic link) additional hardware required
Maximum bus extension (FOL) 1000 m (1.5 MBaud)
1000 m (187.5 kBaud)
Maximum bus extension (copper)
200 m (1.5 MBaud)
Address setting via configuration software or
DP Master-Set Slave Address
Profibus address standard compliant (ex works addr. 126)
Redundant comm unit address automatic
Servicebus address max. 119
Explosion protection:
Category II 2 (1) GD EEx d [ia] IIC
Approval PTB 97 ATEX 1074 U
Different comm units can be used on the same bus. Only use identical comm units within
a redundant slave.
FB Remote I/O FB Remote I/O
Factory setting: single system to be converted to redundant operation via mouseclick.
2/50
FB 8207
Com Unit for Standard
MODBUS RTU
Product features
• MODBUS communication • non volatile memory for configuration and
• supports 1-8 channel I/O modules parameter settings
(multi channel) • LED diagnostic indication
• mounted in Zone 1 or Zone 2 • HART communication on MODBUS
• can be unplugged in Zone 1 during operation • optional servicebus for extended diagnostics
(hot swap) and commissioning (forcing)
• ON/OFF delay for digital inputs (Filter, pulse • EMC to EN 61326 and NE21
extension)
• self configurating in a redundant system
2
(plug and play)
• drives outputs to a defined position in case
of failure
Technical data:
MODBUS
Fieldbus connection
others upon enquiry
HART communication via MODBUS
Transferrate MODBUS 38.4 kBaud
Power consumption 2W
defined by fieldbus specification
Max. number of slaves per busline
247 (MODBUS), 119 (Servicebus)
Number of slaves per bus segment max. 31 (RS485 Standard)
Repeaters between Master-Slave max. 3
depending on the modules
Number of channels per substation
max. 80 analog, 192 digital
Ex-e bus terminals to RS485 Standard
Backplane Connections
power via power supply modules
FOL (fibre optic link) additional hardware required
Maximum bus extension (FOL) 1200 m (38.4 kBaud)
Maximum bus extension (copper) 1200 m (38.4 kBaud)
Address setting via configuration software
MODBUS address standard compliant (ex works addr. 126)
Redundant comm unit address automatic
Servicebus address max. 119
Explosion protection:
Category II 2 (1) GD EEx d [ia] IIC T4
EC-Type Examination Certificate PTB 97 ATEX 1074 U
Ordering details
Primary comm unit Redundant comm unit
Comm Unit for 80 analog/184 digital channels
Feldbus Redundant bus with Standard MODBUS Parameterization Model Order No.
Service bus Service bus
local connection Modbus (any Master) FB 8207 H07XX GHG 127 07XX H 8207
memory memory Different comm units can be used on the same bus. Only use identical comm units within
a redundant slave.
µP µP Factory setting: redundant system to be converted to single operation via mouseclick.
Note:
Redundancy and HART require an integration test with the master system.
FB Remote I/O FB Remote I/O
2/51
FB 8209
UniCOM ComUnit for Profibus DP/DPV1
with ONLINE Configuration (CiR)
Product features
• ONLINE DCS configuration • self configurating in a redundant system
(with or without redundancy) (plug and play)
• fast track to data exchange • drives outputs to a defined position in case
(using universal setting) of failure
• supports 1-8 channel I/O modules • non volatile memory for configuration and
(multi channel) parameter settings
• Mounted in Zone 1 or Zone 2 • LED diagnostic indication
• can be unplugged in Zone 1 during operation • HART communication on Profibus
(hot swap) • optional servicebus for extended diagnostics
• ON/OFF delay for digital inputs and commissioning (forcing)
(Filter, pulse extension) • EMC to EN 61 326 and NE21
Technical Data:
Fieldbus connection Profibus DP, DPV1, others upon enquiry
HART communication to PNO Standard
Transferrate Profibus up to 1500 kBaud
Power consumption 2W
defined by fieldbus specification
Max. number of slaves per busline
125 (Profibus), 119 (Servicebus)
Number of channels (120 Byte In/Out) combined configuration possible, otherwise
with standard configuration 80 analog, 192 digital (single+multi channel)
with universal 2I2O setting 48 analog, 192 digital (single+multi channel)
with universal 4I4O setting 60 analog, 120 digital (single+multi channel)
Number of slaves per bus segment max. 31 (RS485 Standard)
Repeaters between Master-Slave max. 3
depending on the configuration
Number of channels per substation
max. 80 analog, 192 digital
Ex-e bus terminals to RS485 Standard
Backplane Connections
power via supply modules
FOL (fibre optic link) additional hardware required
maximum bus extension (FOL) 1000 m (1.5 MBaud)
1000 m (187.5 kBaud)
maximum bus extension (copper)
200 m (1.5 MBaud)
Address setting via configuration software or DP master
Profibus address standard compliant (ex works addr. 126)
Redundant comm unit address automatic
Servicebus address max. 119
Explosion protection:
Category II 2 (1) GD EEx d [ia] IIC T4
EC Type Examination Certificate PTB 97 ATEX 1074 U
Primary comm unit Redundant comm unit
Different comm units can be used on the same bus. Only use identical comm units
within a redundant slave.
Factory setting: redundant system to be converted to single operation via mouseclick.
Block diagram of redundant comm units
2/52
FB 9204 - FB 9216
Power Supply
Product features
• Supplies 24 I/O slots and a com. interface
• Galvanically isolated at 230 V AC resp. 110 V AC.
At 24 V DC with common ground.
Galvanic isolation in the I/O modules and comm. interface
• EMC to EN 61326 or NE21
• EEx d certified
• Use two power supplies for redundancy
• Green Power-On LED
• Zone 1 mounted
2
• Can be plugged-in during operation (hot swap)
Technical data:
Power supply
DC voltage 24 V DC 20...30 V
230 V AC + 10/- 15 % isolated
AC voltage
110 V (100-132 V) isolated
Internal fuse 3.15 A mtg bzw. 1 AT
Start up current 15 A (20 ms)
Power consumption 35 W (24 V)
30 VA (230 V), 60 VA (110 V)
When fitted with predominantly digital
inputs, the power consumption is markedly
lower. See manual for details.
Explosion protection:
Category II 2 GD EEx d IIC
Approval PTB 97 ATEX 1074 U
Ordering details
Type Power Type Order No.
Power supply 24 V DC FB 9204 B GHG 127 0000 B9204*
Power supply 230 V AC FB 9215 B GHG 127 0000 B9215
Power supply 110 V AC FB 9216 B GHG 127 0000 B9216
input 12 V 5 V
+ + -
2/53
FB 9205
230 V Power Supply
replaced by FB 9205 C
Product features
• Supplies 24 V DC
• Suitable for the supply of FOL, field products
(analysers level meters etc.)
• Zone 1 mounted
• EEx d certified
• Can be plugged-in during operation (hot swap)
• Galvanic isolation between the input and the output
• EMC to EN 61326 or NE21
Technical data:
Power supply
AC voltage 230 V AC + 10/- 10 %
Power consumption 15 VA
Output (unregulated) for 230 V AC
Voltage 22 V DC 26 V DC
Current 300 mA 100 mA
Power consumption 7W
Explosion protection:
Category II 2 GD EEx d IIC
Approval PTB 97 ATEX 1074 U
Ordering details
Function Type Order No.
Power supply 230 V AC/24 V DC FB 9205 B GHG 127 0000 B9205*
24 V 0 V
1 2 12 5
2/54
FB 9206
24 V DC Power Supply
Product features
• Zone 1 or Zone 2 mounted
• can be unplugged in Zone 1 during operation
• Supplies 24 I/O slots and a com. interface
• Galvanic isolation to line
• EMC to EN 61326 or NE21
• Redundant supply of the comm. interface
and I/O modules possible
• Green Power-On LED 2
Technical data:
Power supply
DC voltage 24 V DC 20...30 V
Internal fuse 3.15 AT
Start up current 5 A (20 ms)
Power consumption max. 47 W
When fitted with predominantly digital inputs
the power consumption is markedly lower.
See manual for details.
wire clamp terminals at the left end of
Power supply
the backplane (max. 2.5 or 4 mm2)
2 power supplies can be fed from
2 separate power lines.
Redundancy
No adverse effect on the substation
if one power supply fails (high integrity).
Explosion protection:
Category II 2 GD EEx d IIC
Approval PTB 97 ATEX 1074 U
Ordering details
Function Type Order No.
Power supply 24 V DC FB 9206 B GHG 127 0000 B9206
24 V 12 V 5 V
+ - + + -
2/55
FB 9293, FB 9294, FB 9295
Bus Termination Modules
Product features
• Bus termination resistors
• to be plugged into backplane next to the comm. unit
• Can be replaced during operation in Zone 1
if the bus operation will not be disturbed
• Galvanic isolation from the mains
• EMC to EN 61326 or NE21
Technical data:
Bus termination absolutely necessary for each last station
of a busline for field enclosures and cabinets
from version V2 onwards (2002)
Explosion protection:
Category II 2 GD EEx d IIC
Approval PTB 97 ATEX 1074 U
Ordering details
Function Type Order No.
Service bus termination FB 9293 B GHG 127 0000 B9293
Bus termination FB 9294 B GHG 127 0000 B9294
Bus- and service bus termination FB 9295 B GHG 127 0000 B9295
2/56
Engineering Aids/Accessories
LB / FB Remote I/O
Control room with PLC or DCS The wiring of the bus and mains cables should
be engineered to allow for later expansions. The
bus need not be switched off to do so if junction
boxes are provided in strategic positions.
Important stations can be built up redundantly.
Technical details are to be taken from the
PLC
DCS
respective catalogues and the manual.
2
FOL FOL
Larger distances can be bridged with
the optical fibre link
max. 48 slots, substation 1
LB Remote I/O
48 slots, substation 31
2/57
Engineering Aids/Accessories
FB Remote I/O
Examples of decentralized field units
(metallized plastic enclosures with empty
terminal box flanged-on at the bottom).
Prewired marshalling terminals upon enquiry.
Has been replaced by non metallized version.
FB Remote I/O
Decentralized field unit (plastic enclosure)
Terminal BOX flanged at the bottom
for screen rail
2/59
Field Enclosures
Zone 1
FB Remote I/O
Available cabinet dimensions Descripiton
Type A: 1800 x 1600 x 500
Type B: 1600 x 1200 x 500 Bus substations are available in different
standard designs with an EC declaration of
Type C: 1200 x 1000 x 500 conformity.
metric cabinet dimensions 1800 x 1600 x 500
cabinet dimensions 800 x 1000 x 300
Besides, we offer engineered solutions. Some
examples are given below. The cabinets are
available in stainless steel with IP 54 protection.
EG-Certificate of Conformity
PTB 97 ATEX 1075
Example
Decentralized field unit (sheet steel
enclosure)
Cabinet for 5 redundant substations,
4 substations with 24 slots,
1 substation with 48 slots
Legend:
1) Flameproof mains circuit breakers (24 V DC)
2) Busstations
3) Redundancy units
4) Option marshalling terminals
5) Option screen rails
FB Remote I/O
Decentralized field unit (plastic enclosure)
Field unit FB 9226
GHG 127 0000 B9226 with:
1 socket for communication interface FB 820X
1 socket for power supply FB 92XX
10 sockets for I/O modules
Cable glands (plastic)
2 x M20 for power supply
2 x M20 for bus cable
1 x M20 for service bus cable
Available cabinet dimensions 24x M16 for 24 I/O cables
544 x 271 x 252 24 x M16 blanking plugs
metric Terminals for mains connection and bus VBG4
protected.
Note:
– Enclosure must be mounted horizontally
(see photo).
– Modules must be transported in
original packing.
If boxes must be transported with modules fitted
please do so with enclosures lying down.
2/60
Accessories
Ordering details
8
7 Type Ex-i Order No.
6
5 Connector 6-pole
4 Note: Hood cover can only be used with screw fixing
3 connectors. Connectors with cover require field
2 enclosures to be at least 300 mm deep
1 2 3
1
4
LB 9107 Screw terminals connector, blue, 6-pole
LB 9107 Wire clamp connector blue, 6-pole
X
X
GHG 127 0000 A 9107
CGS 127 0000 P 9107 2
LB 9117 Front connector, screw fixing, blue, 6-pole X GHG 127 0000 A 9117
LB 9108 Cover for connector blue, 6-pole X GHG 127 0000 A 9108
LB 9112 Cold junction compensation module blue, 6-pole X GHG 127 0000 A 9112
6 Connector 8-pole
LB 9120 Cover for connector blue, 8-pole X GHG 127 0000 A 9120
LB 9113 Screw terminals connector blue, 8-pole X GHG 127 0000 A 9113
LB 9124 Screw terminals connector blue, 2 x 8-pole X GHG 127 0000 A 9124
5 with label 1-8 and 9-16
LB 9115 Wire clamp connector blue, 8-pole X GHG 127 0000 A 9115
1 Wire clamp connector LB 9116 Wire clamp connector blue, 2 x 8-pol. X GHG 127 0000 A 9116
2 Screw terminals connector with label 1-8 and 9-16
3 Front srew connector LB 9118 Front screw connector 1-8, blue X GHG 127 0000 A 9118
4 Label (included in the delivery) LB 9119 Front screw connector 1-8, and 9-16, blue X GHG 127 0000 A 9119
5 Hood cover – only for (2)* LB 9020 Coding strip for coding GHG 127 0000 A 9020
6 Coding strip the male connector (100 pcs.)
* observe depth of enclosure
Bus connection
plugs are labeld 1-6 or 1-8
or 9-16 Note: The bus is connected in protection category
Coding strip only when necessary (uncoded ex increased safety. So RS 485 standards are fully
works) applicable. There is no need for an Ex-i bus-converter.
Service-bus interface-converter RS232-RS485 upon enquiry
COMBICON Needed in case of service
Connector only for mobile use of service-bus or in lab
Converter/service-bus-connection CGS 127 0000 P 9281
Adapter-cable for service-bus connection (Ex-e) CGS 127 0000 C 9258
2/61
Accessories
Ordering details
Type Ex-i Order No.
Software
CD-ROM with DTM configuration software for GHG 127 0000 H 0401
FDT098 incl. documentation for LB/FB Remote I/O
V4X + V5X + V6X + FDT 1.2 DTM for all ComUnits
incl. licence for 1 project
when required, order comm unit factory update after
return of devices per item plus shipment or upon enquiry
On-site Update by a service engineer
or on site commissioning assistance
or factory acceptance test
2/62
Engineering Aids/Accessories
Ordering details
Type Ex-i Order No.
Extension cables
Extension cables for plastic enclosures
GHG 127 0000 D 92XX
for redundancy unit-basic unit (2.1 m) CGS 227 0096 P 8000
for redundancy unit-expansion (2.1 m)
for basic unit-expansion (2.1 m)
CGS 227 0096 P 9000
CGS 227 0097 P 0000 2
for comm. interface to redundant comm. interface (2.1 m) CGS 127 0000 P 9283
(Extension cables are included in the
delivery of FB 9225, 9248, 9249)
Extension cables for plastic enclosures with
built-on terminal box E 92XX resp. G 92XX
for redundancy unit-basic unit (1.6 m) CGS 227 0096 P 5000
for redundancy unit-expansion (1.9 m) CGS 227 0096 P 6000
for basic unit-expansion (2.2 m) CGS 227 0096 P 7000
for comm. interface to redundant comm. interface (2.1 m) CGS 127 0000 P 9284
(Extension cables are included in the
delivery of FB 9225, 9248, 9249)
Bus cable
Comm. cable in metres for PROFIBUS or MODBUS CGS 127 0000 P 9290
for underground laying in Zone 1 (6XV1830-3AH10)
Comm. cable in metres for PROFIBUS or MODBUS CGS 127 0000 P 9291
for cable trays in Zone 1 (6XV1830-OEH10)
Termination resistor Comm. cable in metres for PROFIBUS or MODBUS CGS 127 0000 P 9292
in a non-hazardous area (6XV1830-OAH10)
Line filter
Single flame proof EMC line filter (if needed) GHG 411 8100 R 0015
in IP 66 enclosure
Double flame proof EMC line filter (if needed) GHG 411 8200 R 0015
in IP 66 enclosure
Services
Project engineering on inquiry
Factory settings on inquiry
CAD documentation on inquiry
Project management on inquiry
Computer aided functional test on inquiry
Factory acceptance test (FAT, GAMP) on inquiry
Installation certificates acc. to ATEX
2/63
2/64
Fibre Optic Link in Zone 1
for Profibus DP/DPV1
3/1
Fibre Optic Link in Zone 1
for Profibus DP/DPV1
Profibus DP / DPV1 / PA
Control Room
100MBd Ethernet
Back of Panel
DP DP DP
FOL FOL
redundant line topology FOL
point to point
FOL FOL FOL
ZONE 2 DP
1-8 channel
plug-in modules
for Zone 1
3/2
Fibre Optic Link in Zone 1
for Profibus DP/DPV1
Control Room
3
100MBd Ethernet
Back of Panel
DP DP
FOL FOL
FOL redundant star topology
ring topology
FOL FOL
DP ZONE 2
FOL up to
ZONE 1
3000 m
between
FOL up to
devices in the
3000 m
ring
RS485
200 m
• actuators • positioners
• converters • drives
• motors • field devices
• valves • Ex-e, Ex-d
• controllers Ex-e • Ex-m, Ex-p
• Remote I/O
3/3
Fibre Optic Link in Zone 1
for Profibus DP/DPV1
Technical data
Fieldbus PROFIBUS DP-V0, DP-V1, DP-V2 and
FMS, (PA via external DP/PA LINK)
transmission rate 9.6; 19.2; 45.45; 93.75; 187.5;
500 kbit/s; 1.5; 3; 6; 12 Mbit/s
(automatic setting)
Signal processing time (any in/output) < 6.5 Bit times
Input /Output signal RS 485 level
network expansion – cable length depending on baudrate 200 m to 1000 m
Bus termination can be activated using a switch
alarm contact (low protective voltage) max DC 60 V, AC 24 V, 1A (Ex-e)
GRP enclosure test output “optical input” Ex-e terminals
Profibus Ex-e terminals
Cage clamp terminals max. 1.5 mm2
cable glands M20 2 x power, 2 x FOL
2 x RS 485 Bus, 1 x diagnostic contact
Optical interface (2 optical ports)
wave length 860 nm
launchable optical power in 50/125 62.5/125 HCS200/230
Multimode Fibre (MM) 50/125 –15 dBm –13 dBm – 10 dBm
optical input power min. –28 dBm, max. –3 dBm
cascading unlimited
network expansion – cable length
DIN-rail module* Multimode Fibre (MM) 50/125 µm 3000 m, 13 dB link budget at
860 nm; A = 3 dB/km, 3 dB Reserve
Multimode Fibre (MM) 62.5/125 µm 3000 m, 15 dB link budget at
860 nm; A =3.5dB/km, 3 dB Reserve
Multimode Fibre HCS (MM) 200/230 µm 1000 m, 18 dB link budget at
860 nm; A = 8 dB/km, 3 dB Reserve
Power supply galv. isolated
operating voltage 18 ... 32 VDC, typ. 24 VDC
operating current max. 200 mA
power consumption 4.8 W
Redundancy HIPER-Ring (ring structure)
Redundancy function redundant 24 V supply
display power supply voltage monitoring
Stainles steel enclosure
LED red/green (system) and Bitrate
LED red/yellow (CH 1) monitors the electric channel
FOL Profibus Coupler LED red/yellow (CH 2, CH 3) monitors the optical channels
Repeater Permissible Ambient Temperatures
for safe area or Zone 2 Operating temperature – 20 ºC to + 60 ºC
mounting Storage/Transport temperature – 40 ºC to + 80 ºC
Relative humidity < 75 %, max. < 95 %, no condensation
OZD Profi 12M G12 Construction Module GRP Stainless steel
(two optical ports)
Dimensions (WxHxD) mm 156x125x75 165x194x138 230x219x108
Order No.
GHG 127 0000 A 9300 Weight app. 1.5 kg app. 2.4 kg app. 3.7 kg
Ingress Protection to EN 60529 – IP 66 IP66
details upon enquiry. EMC-noise immunity EN 61000-4-2/3/4/5/6, EN 55022, NE 21
Explosion Protection PTB 07 ATEX 2021 U (Module)
FOL BFOC/2.5 intrinsically safe
EC-type examination PTB 04 ATEX 1030 (Module inside housing)
* Note: DIN rail module Protection category II 2(1) G EEx me IIC T4
must be certified II 2(1) D IP66 T130 °C
together with the housing
Ordering details
FOL Cable FOL Profibus Repeater Type Order No. GHG
Fibre optic cables can be laid by the user given
DIN-rail module, DC 24 V FOL 7250 B059 127 3200 B 0059
he has suitable tools.
GRP enclosure, DC 24 V FOL 7250 B159 127 3200 B 0159
The cable glands are fitted with a split seal so
stainless steel enclosure, DC 24 V FOL 7250 B259 127 3200 B 0259
that the fibre cables can be inserted with the
GRP lid with LED viewing glass
connectors already fitted. This ensures that IP66
Hot Swap eXLink plug 129 0100 A 0010
protection is maintained.
upon enquiry
3/4
Foundation Fieldbus
Modular I/O
/
Foundation Fieldbus
Modular I/O
LB and FB Remote I/O are important signal conditioning devices
for interfacing sensors and signals from legacy field devices to the
Foundation Fieldbus Host of controllers or process control systems. For
the first time there is now a modular concept to adapt digital and analog
signals to the Foundation Fieldbus. The plug-in modules are mounted on
pre-fabricated plastic backplanes for installation in potentially explosive
atmospheres in Zone 2 or Zone 22 for LB or Zone 1 and Zone 21 for FB.
The various IS I/O modules can be plugged in or removed during
operation without the need for a hot work permit. Other advantages
include the galvanic isolation and the amplification properties.
What is more, the wiring is reduced to that of a standard bus
connection. The galvanic isolation provides a safe and reliable interface
between the process and the bus. The amplification properties and
4
the digital transmission ensure a high degree of measurement accuracy
which is not influenced by variations in the auxiliary power supply.
0 LEDs indicate the status of the respective device. A green LED indicates
the operating status, while a red LED indicates a fault, e.g. an open line or
short circuit. The PLC or DCS can call upon this data via the bus.
4/1
Foundation Fieldbus
Modular I/O
1 Foundation Fieldbus
Modular I/O brings
analog and digital
signals to the Bus
Basics
Foundation Fieldbus is the power house of mo-
dern process instrumentation. Compared with
legacy I/0 instrumentation using point-to-point
DIN rail devices or Eurocards the bus offers
considerable savings and technical improve-
ments. This holds particularly true where Asset
Management is employed to obtain information
for advance maintenance or to avoid unneces-
sary service activities.
Fieldbus Remote I/O offers a modular concept
to adapt intrinsically safe inputs and outputs
from sensors and actuators to the bus.
It accepts NAMUR type signals or switches and
can drive power valves or relays for increased
safety controls as well as acoustic alarms or
alarm indicators. It supplies 4-20mA transmitters
and takes in 20mA from separately powered
field devices or temperature inputs. It also
drives I/P converters, proportional valves and
positioners.
It loads the bus with just 10mA since it comes
with its own power supply. This makes it inde-
pendent from the power available on the trunk
1 Architecture of a typical plant using Foundation FArchitectuieldbus Remote I/O line.
System based on experience FF Remote I/O for Foundation Fieldbus FF Inputs and Outputs – digital or analog
Pepperl+Fuchs have made a considerable By adding a Foundation Fieldbus ComUnit or In contrast to dedicated digital input devices the
contribution to Fieldbus technology over the gateway we have created a new FF Remote I/O modular I/O approach allows you to combine
past ten years. Now we have reached yet to support all non foundation fieldbus signals. analog and digital I/O in the same device. It
another milestone. It makes use of the established reliable hardware supports NAMUR or switch type inputs as well
While many different components were needed and employs standard FF multi function blocks as solenoid outputs, temperature signals or
in the past to build a complete system, P+F are to offer a modular fieldbus Remote I/O for the supply circuits for two- or four-wire transmitters,
now offering a total concept founded on stability very first time. proportional valves and positioners. These often
and experience. In addition to temperature Also the bus speed of 31.25 kBd is exploited do not have a Foundation Fieldbus connection
multiple inputs and discrete digital I/O boxes more efficiently whilst reducing cost compared themselves.
driving low power valves there is now a with discrete field devices which are on offer to The modular approach arrives at a very com-
Foundation Fieldbus Modular I/O which addsall fulfil similar tasks. pact solution offering up to 40 digital inputs or
the functionalities required for process outputs or 20 analog I/O or any combination of
instrumentation in an ideal combination. analog and digital I/O. The data sheet of the FF
gateway or ComUnit lists the useable modules.
All dual width cards are supported. The data
sheets of the modules can be found in chapters
1+2 of the catalog.
Modules can be added within this framework
whenever required. This allows for a modular
expansion with modules on demand. Changes
are conducted ONLINE without disrupting nor-
mal operation. Housings in glass fibre reinforced
polyester (GRP) or stainless steel also offer
space for Fieldbarriers and valve banks.
4/2
Foundation Fieldbus
Modular I/O
DD / EDDL
The integration of the FF Remote I/O into
suitable host DCS systems is accomplished
by the well established DD technology (device
description) and CFF (configuration file) files.
Foundation Fieldbus thus arrives at an easy to
use configuration tool which is part of the DCS
environment just like any other FF device.
4/3
Foundation Fieldbus
Modular I/O
HART Communikation
Intelligent field devices which make use of the
HART protocol can be connected to suitable
analog input and output modules (models
3X05, 4X05). The field devices then become
accessible via the service bus using appropriate
communication software (e.g. PACTware).
There is also a HART communication DTM for
other FDT containers to interface with our HART
enabled gateway. The DTM is included in the
standard setup. HART field devices are then
engineered in the same way as they are with
standard gateways and ComUnits.
4/4
LB 8110
ComUnit for Zone 2 FF Modular I/O
supports 20 Al / AO or 40 DI / DO
Product Features
• configured via the DCS
• fast route to communications
• supports multichannel I/O module (8-channel digital, 4-channel analog)
• mounted in Div. 2 or Zone 2 or outside hazardous areas
• modules can be exchanged in Zone 2 with power on (hot swap)
• HART communication via service bus
• outputs drive to safe state in case of failures
• configuration and parameters stored in non volatile memory (FF-standard)
• LED diagnostics complement FF diagnostics
• EMC to EN 61326 or NE21
Technical Data:
Fieldbus connection Foundation Fieldbus H1 to IEC 1158-2
4
Transferrate MBP 31.25
Power consumption 2W
Power supply DC24 V local supply
defined by the Fieldbus specification
Max. number of FF devices per line 31 depending on the desired reaction time
(recommended maximum 1-2 Modular I/O)
depending on the chosen configuration
Number of channels per Modular I/O 20 analog, 40 digital max.
directly connected to the trunk or via
Connection spur protector
uses its own power supply
Power trunk load of 10mA as required
by the standard
sum of all trunk and spur lines must not
Maximum bus extension exceed 1900 m (31.25 kBaud)
max. spur length 120 m depending on the number of field devices
Adress setting via DCS configuration software
Fieldbus address assigned automatically by the DCS
ordering details
ComUnit for FF Modular I/O model order no.
Foundation Fieldbus (Zone 2) LB 8110 Hxxyy LB 8110 Hxxyy
(any Host)
Block Diagram
xx = device revision, yy = DD (device description revision)
4/5
FB 8210
ComUnit for Zone 1 FF Modular I/O
supports 20 Al / AO or 40 DI / DO
Product Features
• configured via the DCS
• fast route to communications
• supports multichannel I/O module (8-channel digital, 4-channel analog)
• mounted in Zone 1 or Zone 2
• modules can be exchanged in Zone 1 with power on (hot swap)
• HART communication via service bus
• outputs drive to safe state in case of failures
• configuration and parameters stored in non volatile memory (FF-standard)
• LED diagnostics complement FF diagnostics
• EMC to EN 61326 or NE21
Technical Data:
Fieldbus connection Foundation Fieldbus H1 to IEC1158-2
Transfer rate MBP 31.25
Power consumption 2W
Power supply DC24 V or AC230 V local supply
defined by the Fieldbus specification
Max. number of FF devices per line 31 depending on the desired reaction time
(recommended maximum 1-2 Modular I/O)
depending on the chosen configuration
Number of channels per Modular I/O 20 analog, 40 digital max.
directly connected to the trunk or via
Connection Ex-e spur protector using Ex-e terminals
uses its own power supply.
Power trunk load of 10mA as required
by the standard
sum of all trunk and spur lines must not
Maximum bus extension exceed 1900 m (31.25 kBaud)
max. spur length 120 m depending on the number of field devices
Adress setting via DCS configuration software
Fieldbus adress assigned automatically by the DCS
ordering details
ComUnit for FF Modular I/O model order no.
Foundation Fieldbus (Zone 1) FB 8210 Hxxyy FB 8210 Hxxyy
(beliebiger Host)
Block diagram
xx = device revision, yy = DD (device description revision)
4/6
Accessories
LB Modular I/O Backplanes can be mounted in any enclosure outside hazardous areas as long as
the minimum IP20 protection category is reached.
129
In hazardous areas ATEX or UL approved housings must be used providing a minimum protection
as follows: IP54 for Zone 2, IP66 for Zone 22 and IP54 in DIV2
FB Modular I/O may only be mounted in hazardous areas in suitably approved enclosures:
275 IP54 for Zone 1, IP66 for Zone 22, IP54 for DIV 2.
LB 9035 Backplane, empty On the left some examples are shown depicting factory standards.
for FF Modular I/O Other options are available upon enquiry e.g. fitted with valve banks or fuses. Deliveries ex works
Zone 2, Zone 22, DIV 2 always fulfil the heat dissipation requirements demanded by explosion protection regulations.
For front connectors and other accessories see the corresponding chapters under LB Remote I/O
or FB Remote I/O.
Only use double width modules.
4
LB 9035 fitted with modules
FF Modular I/O Ordering details order number
Zone 2, Zone 22, DIV 2 Zone 2, Zone 22, DIV 2
LB 9035 FF Modular I/O Backplane for 5 modules (without modules) LB 9035A
Zone 1, Zone 21
FB 9251 FF Modular I/O GRP enclosure for 5 modules FB 9251 B
(without modules)
Zone 1, Zone 21
FB 9252 FF Modular I/O GRP enclosure for 5 modules FB 9252 B
with space for a max. number of 2 field barriers and flanged box.
FB 9251 fitted with modules
(without modules)
for FF Modular I/O
Zone 1, Zone 21
Software
CD-ROM with DD and CFF files for system integration
including documentation for Foundation
Fieldbus LB/FB Modular I/O
Supplied with every ComUnit or Gateway
212 544
X 520
X 247
271
4/7
4/8
Multi Purpose Terminal
Common Data
maximum voltage 400 V
maximum current 6.3 A
permissible wire diammeter 0.8 ... 2.5 mm2
–40 °C ... +70 °C up to 1.6 A
5/1
Multi Functional Terminal
Model MFT – F
Fuse Terminal
Product features
module • Zone 1 mounting
• Hot swap without hot work permit
• Suitable for devices in categories Ex-i, Ex-d, Ex-e, Ex-p, Ex-m, Ex-n
• Many applications: fuses for Ex-d valves, lamps, indicators, sounders, supply circuits
Technical data:
Nominal voltage 250 V
Nominal current 0.032 ... 6.3 A
Switch rating 35 A
Charakteristic T (slow)
Dimensions 80 x 93 x 17.5 mm (D x H x W)
Weight approx. 115 g
Ambient temperature –20 °C ... +55 °C (–40 °C ... +70 °C up to 1.6 A)
Explosion protection category EEx de IIC
EC type examination certificate PTB 07 ATEX 1004 U
Ordering details
base 1 fuse Order No. 1 fuse + Order No.
1 jumper
1 x 0.032 A MFT-F.32 1 x 0.032 A MFT-F.32.L
1 x 0.050 A MFT-F.50 1 x 0.050 A MFT-F.50.L
1 x 0.063 A MFT-F.63 1 x 0.063 A MFT-F.63.L
1 x 0.080 A MFT-F.80 1 x 0.080 A MFT-F.80.L
1 x 0.100 A MFT-F.100 1 x 0.100 A MFT-F.100.L
1 x 0.125 A MFT-F.125 1 x 0.125 A MFT-F.125.L
1 x 0.160 A MFT-F.160 1 x 0.160 A MFT-F.160.L
1 x 0.200 A MFT-F.200 1 x 0.200 A MFT-F.200.L
1 x 0.250 A MFT-F.250 1 x 0.250 A MFT-F.250.L
1 x 0.315 A MFT-F.315 1 x 0.315 A MFT-F.315.L
1 x 0.400 A MFT-F.400 1 x 0.400 A MFT-F.400.L
1 x 0.500 A MFT-F.500 1 x 0.500 A MFT-F.500.L
1 x 0.630 A MFT-F.630 1 x 0.630 A MFT-F.630.L
1 x 0.800 A MFT-F.800 1 x 0.800 A MFT-F.800.L
1 x 1.000 A MFT-F.1000 1 x 1.000 A MFT-F.1000.L
1 x 1.250 A MFT-F.1250 1 x 1.250 A MFT-F.1250.L
1 x 1.600 A MFT-F.1600 1 x 1.600 A MFT-F.1600.L
1 x 2.000 A MFT-F.2000 1 x 2.000 A MFT-F.2000.L
1 x 2.500 A MFT-F.2500 1 x 2.500 A MFT-F.2500.L
1 x 3.150 A MFT-F.3150 1 x 3.150 A MFT-F.3150.L
1 x 4.000 A MFT-F.4000 1 x 4.000 A MFT-F.4000.L
4
1 x 5.000 A MFT-F.5000 1 x 5.000 A MFT-F.5000.L
1 x 6.300 A MFT-F.6300 1 x 6.300 A MFT-F.6300.L
MFT – F.xxxx Accessoires: Accessoires:
2 pole base MFT-BASE.2P 4-pole base MFT-BASE.4P
4 3 1 (L)
2 identical fuses (max. 2 x 3.15 A) Order No.
MFT – F.xxxx.L
Note: modules will be supplied without base unit.
Please order seperately.
1 2
5/2
Multi Functional Terminal
Model MFT – D
Diode Terminal
Product features
module • Zone 1 mounting
• Hot swap without hot work permit
• Suitable for devices in categories Ex-i, Ex-d, Ex-e, Ex-p, Ex-m, Ex-n
• Many applications: diode seperation for supply circuits
Technical data:
Diode 1 A, 250 V
Dimensions 80 x 93 x 17.5 mm (D x H x W)
Weight approx. 115 g
Ambient temperature –20 °C ... +55 °C (–40 °C ... +70 °C up to 1.6 A)
Explosion protection category EEx de IIC
EC type examination certificate PTB 07 ATEX 1004 U
Ordering details
Model Order No.
1 x diode
Accessories: 2 pole base
MFT-D.1000
MFT-BASE.2P
5
base
2 x diode MFT-2D.1000
Accessories: 4 pole base MFT-BASE.4P
4 4 3
1 1 2
5/3
Multi Functional Terminal
Model MFT – R
Resistor Terminal
Product features
module • Zone 1 mounting
• Hot swap without hot work permit
• Suitable for devices in categories Ex-i, Ex-d, Ex-e, Ex-p, Ex-m, Ex-n
• Many applications: current limitation, valve bypass, loop series, loop parallel resistor,
end of line resistor
Technical data:
Resistor values 1 1 ... 22 M1 0.5 W
Dimensions 80 x 93 x 17.5 mm (D x H x W)
Weight approx. 115 g
Ambient temperature –20 °C ... +55 °C (–40 °C ... +70 °C up to 1.6 A)
Explosion protection category EEx de IIC
EC type examination certificate PTB 07 ATEX 1004 U
Ordering details
Resistor Order No.
1 x 1 R 00 MFT.-R.1001
1x 1R5 MFT.-R.1501
base 1 x 2 R 21 MFT.-R.2211
1 x 3 R 32 MFT.-R.3321
1 x 4 R 75 MFT.-R.4751
1 x 6 R 81 MFT.-R.6811
1 x 10 R 0 MFT.-R.1002
1 x 15 R 0 MFT.-R.1502
1 x 22 R 1 MFT.-R.2212
1 x 33 R 2 MFT.-R.3322
1 x 47 R 5 MFT.-R.4572
1 x 68 R 1 MFT.-R.6812
1 x 100 R MFT.-R.1003
1 x 150 R MFT.-R.1503
1 x 221 R MFT.-R.2213
1 x 332 R MFT.-R.3323
1 x 475 R MFT.-R.4753
1 x 681 R MFT.-R.6813
1x 1K0 MFT.-R.1004
1 x 1 K 50 MFT.-R.1504
1 x 2 K 21 MFT.-R.2214
1 x 3 K 32 MFT.-R.3324
1 x 4 K 75 MFT.-R.4754
1 x 6 K 81 MFT.-R.6814
1 x 10 K MFT.-R.1005
1 x 15 K MFT.-R.1505
1 x 22 K 1 MFT.-R.2215
1 x 33 K 2 MFT.-R.3325
1 x 47 K 5 MFT.-R.4755
1 x 68 K 1 MFT.-R.6815
4 1 x 100 K MFT.-R.1006
1 x 150 K MFT.-R.1506
1 x 221 K MFT.-R.2216
1 x 332 K MFT.-R.3326
1 x 475 K MFT.-R.4756
1 x 681 K MFT.-R.6816
1x 1M MFT.-R.1007
1 x 1 M 50 MFT.-R.1507
1 x 2 M 21 MFT.-R.2217
1 x 3 M 32 MFT.-R.3327
1 x 4 M 75 MFT.-R.4757
1 x 6 M 81 MFT.-R.6817
1 x 10 M MFT.-R.1008
1 x 22 M 1 MFT.-R.2218
5/4
Multi Functional Terminal
Model MFT – 2R, MFT – 2L
Dual Resistor Terminal
Product features
module • Zone 1 mounting
• Hot swap without hot work permit
• Suitable for devices in categories Ex-i, Ex-d, Ex-e, Ex-p, Ex-m, Ex-n
• Many applications: current limitation, valve bypass, loop series, loop parallel resistor,
end of line resistor
Technical data:
Resistor values 1 1 ... 22 M1 0.5 W
Dimensions 80 x 93 x 17.5 mm (D x H x W)
Weight approx. 115 g
Ambient temperature –20 °C ... +55 °C (–40 °C ... +70 °C up to 1.6 A)
Explosion protection category EEx de IIC
EC type examination certificate PTB 07 ATEX 1004 U
Ordering details
2 Resistors Order No.
2 x 1 R 00
2x 1R5
2 x 2 R 21
MFT-2R.1001
MFT-2R.1501
MFT-2R.2211
5
base
2 x 3 R 32 MFT-2R.3321
2 x 4 R 75 MFT-2R.4751
2 x 6 R 81 MFT-2R.6811
2 x 10 R 0 MFT-2R.1002
2 x 15 R 0 MFT-2R.1502
2 x 22 R 1 MFT-2R.2212
2 x 33 R 2 MFT-2R.3322
2 x 47 R 5 MFT-2R.4572
2 x 68 R 1 MFT-2R.6812
2 x 100 R MFT-2R.1003
2 x 150 R MFT-2R.1503
2 x 221 R MFT-2R.2213
2 x 332 R MFT-2R.3323
2 x 475 R MFT-2R.4753
2 x 681 R MFT-2R.6813
2x 1K0 MFT-2R.1004
2 x 1 K 50 MFT-2R.1504
2 x 2 K 21 MFT-2R.2214
2 x 3 K 32 MFT-2R.3324
2 x 4 K 75 MFT-2R.4754
2 x 6 K 81 MFT-2R.6814
2 x 10 K MFT-2R.1005
2 x 15 K MFT-2R.1505
2 x 22 K 1 MFT-2R.2215
2 x 33 K 2 MFT-2R.3325
2 x 47 K 5 MFT-2R.4755
2 x 68 K 1 MFT-2R.6815
4 3 2 x 100 K MFT-2R.1006
2 x 150 K MFT-2R.1506
2 x 221 K MFT-2R.2216
2 x 332 K MFT-2R.3326
2 x 475 K MFT-2R.4756
2 x 681 K MFT-2R.6816
2x 1M MFT-2R.1007
2 x 1 M 50 MFT-2R.1507
2 x 2 M 21 MFT-2R.2217
2 x 3 M 32 MFT-2R.3327
2 x 4 M 75 MFT-2R.4757
2 x 6 M 81 MFT-2R.6817
2 x 10 M MFT-2R.1008
2 x 22 M 1 MFT-2R.2218
2 x jumper MFT-2L.1600
5/5
Multi Functional Terminal
Model MFT – FT
Termination for Foundation Fieldbus / Profibus PA
Zone 1, Zone 2, mounted
Product features
module • mounted in Zone 1 or Zone 2
• Hot swap without hot work permit
• Suitable for devices in categories Ex-i, Ex-d, Ex-e, Ex-p, Ex-m, Ex-n
• End of line terminator
Techncal Data:
Fieldbus Foundation Fieldbus / Profibus PA
IEC 1158-2 (MBP)
Dimensions 80 x 93 x 17.5 mm (D x H x W)
Weight approx. 115 g
Ambient temperature –20 °C ... +55 °C (–40 °C ... +70 °C up to 1.6 A)
Explosion protection category EEx de IIC
EC type examination certificate PTB 07 ATEX 1004 U
base
Ordering details
Bus termination for
Foundation Fieldbus / Profibus PA Order No.
MFT – FT bus termination MFT-FT.0001
Accessories: 4 pole base MFT-BASE.4P
4 3
1 2
5/6
Multi Functional Terminal
Model MFT – RNO/RNC
Relay Module
Product features
module • Mounted in Zone 1
• removable without hot work permit
• connects to devices in protection categories Ex-d, Ex-e, Ex-p, Ex-m
Technical data:
Contact material silver alloy
Contact resistance at 6 V, 1 A 100 m1
Switching capability (ohmic load):
power rating 6 A, 250 V AC
max. power rationg 1500 VA
Switch voltage 400 V AC 45...65 Hz, 300 V DC
max. current 6 A AC
Ordering details
Function Order No.
1 normally open contact MFT-RNO.0006
1 normally closed contact MFT-RNC.0006
Accessories: 4 pole base MFT-BASE.4P
4 3
+1 2
5/7
Multi Functional Terminal
Model MFT – TRI with Solid State Relay (TRIAC)
Model MFT – T with Solid State Relay (MOS)
Product features
module • Mounted in Zone 1
• removable without hot work permit
• connects to devices in protection categories Ex-d, Ex-e, Ex-p, Ex-m
Technical data:
MFT-TRI with Solid State Relay (TRIAC)
Drive voltage DC 20...28 V (e.g. from FB 6x08)
Drive current approx. 7.9 mA at 20 V, approx. 11.5 mA at 28 V
Switching capability:
Switching voltage 75...250 V AC 45...65 Hz
Minimum current 0.02 A
ON/OFF switching on zero crossing
Leakage current in OFF state 1.5 mA at 200 V
Voltage Drop in ON state 1.6 V
Response time max. 1/2 cycle of the sine wave +1 ms
OFF delay max. 1/2 cycle of the sine wave +1 ms
Built-in fuse for output loads:
Nominal value T 630 mA (slow)
Fuse switching capability 35 A
base
MFT-T with Solid State Relay (MOS)
Drive voltage DC 20...28 V (e.g. from FB 6x08)
Drive current approx. 7.9 mA at 20 V, approx. 11.5 mA at 28 V
Switching capability:
Switch voltage 0...30 V DC
Minimum current 0.001 A
Leakage current in OFF state 0.01 mA
Voltage Drop in ON state 0.3 V
Max. switching frequency 0.5/sec
Response time max. 2 ms
OFF delay max. 0.4 ms
Built-in fuse for output loads:
Nominal value T 2.0 A (slow)
Fuse switching capability 35 A
Properties
Insulation Resistance min. 1000 1 at 500 V DC
Test voltage 2500 V AC between drive and load circuits
Ambient temperature –20 °C ... +55 °C (-40 °C...+70 °C up to1.6A)
Explosion protection category EEx de IIC
EC type examination certificate PTB 07 ATEX 1004 U
Ordering details
Function Order No.
MFT - TRI solid state relay (TRIAC) MFT-TRI.630
MFT - T solid state relay (MOS) MFT-T.2000
Accessories: 4 pole base MFT-BASE.4P
5/8
5
5/9
5/10
proCess automation –
protecting your process
For over a half century, Pepperl+Fuchs has been continually providing new concepts for the world of process automation. Our
company sets standards in quality and innovative technology. We develop, produce and distribute electronic interface modu-
les, Human-Machine Interfaces and hazardous location protection equipment on a global scale, meeting the most demanding
needs of industry. Resulting from our world-wide presence and our high flexibility in production and customer service, we
are able to individually offer complete solutions – wherever and whenever you need us. We are the recognized experts in our
technologies – Pepperl+Fuchs has earned a strong reputation by supplying the world’s largest process industry companies
with the broadest line of proven components for a diverse range of applications.
6
5 1
3
7
2
1 Worldwide/German Headquarters
Pepperl+Fuchs GmbH
Mannheim · Germany
Tel. +49 621 776 2222 8
E-Mail: pa-info@de.pepperl-fuchs.com
www.pepperl-fuchs.com
Subject to reasonable modifications due to technical advances • Copyright PEPPERL+FUCHS • Printed in Germany • Part. No. 195317 11/07 02