You are on page 1of 8

PROTECTION OF LARGE INDUCTION MOTORS

By Jos Luis Azucena, P. Eng. Introduction The protection scheme of motors varies considerably from one motor to another because the different motor size, type or application. To be cost effective, motor protection is usually based upon motor size and/or importance. Motor protection is required to detect abnormal operating conditions and internal fault conditions. Abnormal operating conditions include unbalanced voltages, undervoltage, overvoltage, single phasing, and incorrect phase sequence. Internal fault conditions include insulation failures and mechanical failures. Should currents higher than normal circulates through the motor some damage will occur if these currents are not interrupted on time. Short circuit currents in either motor feeders or motor windings are unwanted situations that must be isolated to avoid further damage to the motor and to the system. Motor load currents, available short circuit currents, motor thermal capacity, and protection relay are tabulated in time current curves to evaluate the coordination of the protection devices.
Induction Motor Hazards Induction motor hazards originate from different sources and can be classified as follows: 1. From Motor/Motor Feeder Insulation failure (in feeder or winding) Mechanical failures (loose parts, bearing failure) 2. From Load/Environment Overload/underload Jamming High inertia High ambient temperature/blocked ventilation 3. From Energy Supplier Overvoltage Undervoltage Open phase Phase reversal Out-of-step after system disturbance

Protection of Large Induction Motors 1-877-955-8131

www.magnaelectric.com 1

Motor Characteristics Involved in Protection Motor Thermal Damage Curve The motor thermal capacity is defined by the Thermal Damage Curves. Time in Seconds

Overload Thermal Limit

Accelerating Thermal Limit

Permissible Locked Rotor Time

Starting Current Curves 0.9 V Motor Load Current Asymmetrical Current Current 1.0 V

Thermal Damage Curves The Overload Thermal Limit curve, the Accelerating Thermal Limit curve and the Permissible Locked Rotor Time blend together to define the Motor Thermal Damage Curves. These thermal limits are relatively indeterminate zones that for practical purposes are usually represented as curves. The Motor Thermal Damage Curve defines the maximum loading for any given time period, this curve defines the maximum circulating current and the time that this current can circulate. The Thermal Damage Curve should be obtained from the motor manufacturer. For large motors two thermal damage curves are supplied, one for starting the motor (cold motor) and another for running the motor (hot motor). Full Load Current

Protection of Large Induction Motors 1-877-955-8131

www.magnaelectric.com 2

The full load current of the motor (FLC) is the maximum continuous current that can circulate during the duty cycle of the motor without producing thermal damage. The initial motor current levels are significantly above the FLC; multiples of two to seven are the most common. Motor Protection Relays Motor overcurrent protection relays operate following a time current curve (TCC). When the relay overload pickup level is reached, the TCC will come into effect, and a tripping signal will be issued if the time determined by the TCC is exceeded. Thermal relays are used as back-up motor protection, these relays use remote temperature detectors (RTD) to measure stator temperature. The curve of operation of O/C relays and thermal relays should be set to follow the motor thermal damage curve

Time in Seconds Motor Thermal Damage Curve Thermal Relay

Overcurrent Relay

Instantaneous Relay

Motor Starting Curve

Current of Motor

Motor Protection Using Overcurrent and Thermal Relays

Protection of Large Induction Motors 1-877-955-8131

www.magnaelectric.com 3

Also, overload (O/L) motor protection relays must allow the motor to start and run under all normal operation conditions. The curve of operation of motor protection relays must be halfway between the Load Current Curve and the Motor Thermal Damage Curve. The starting currents of high inertia loads can be very close to the Overload Thermal Limit Curve. Then two sets of O/L curves should be applied one for motor starting (O.L Starting Curve), and a second one for motor running (O/L Running Curve). The overlap of the O/L Running Curve with the motor starting curve is acceptable for high inertia motors. The motor Starting Curve shall not exceed the Cold Motor Thermal Damage Curve, and the motor Running Curve shall not exceed the Hot Motor Thermal Damage Curve Digital relays are suited to the Cold Motor Thermal Damage Curves for motor starting, and Hot Motor Thermal Damage Curves for motor running. O/L Running Curve Hot Motor Thermal Damage Curve O/L Starting Curve Cold Motor Thermal Damage Curve

Time in Seconds

Motor Starting FLC Motor Running

Current of Motor

Cold and Hot Thermal Damage Curves Short Circuit Currents and Power Fuses in Motor Protection Short circuit currents in the motor and/or motor feeder can be detected using over-current relays. Back-up fuses must be used when the short circuit current available at starter terminals exceeds the ampacity of its contacts. The TCC of the power fuses must be coordinated with the TCC of the O/C relay.

Protection of Large Induction Motors 1-877-955-8131

www.magnaelectric.com 4

Power Fuses Power fuses are used when the starter contacts do not have the capacity to open the short circuit current available at starter terminals. Power fuses with high interrupting current capacity are used for short circuit protection. The power fuse does not protect the motor from overloads; the motor protection relay of the motor starter is the one that protects the motor from overloads, as previously described.

Time

Motor Thermal Damage Curve

Motor Protection Relay

Power Fuse

Current Differential Relays Short circuit currents within the motor can be detected using differential relays. The best differential protection in terms of sensitivity, speed, and security is to pass the conductors of the windings throughout the window of a current transformer (CT), and then an overcurrent relay is installed at CT secondary terminals. The following example illustrates the application of differential relays when the system is grounded through a neutral grounding resistor: Neutral grounding resistors (NGR) = 300 ohms Line to line voltage 4160 volts (then line to ground voltage is 2400 volts) Differential Relay to protect 95 % of the winding Then the relay should pick up at 5 % of line to ground voltage: 2400 volts x .05 = 120 volts 120 volts / 300 = 0.4 amperes Then an overcurrent relay detecting 0.4 amperes primary current will be protecting 95 % of the windings of the motor. Ground Fault Protection Ground fault protection using one overcurrent relay and one ZSCT (Zero Sequence CT), can be obtained whenever the conductors of the three phases of the motor are passed throughout the window of the ZSCT, and an O/C relay is connected to ZSCT terminals. Typical relay sensitivity is 5 Amperes primary current (when the relay can not read 5 Amperes then 10 Amperes is used).

Protection of Large Induction Motors 1-877-955-8131

www.magnaelectric.com 5

Load Characteristics Involved in Protection Load characteristics define the time that the starting current is applied and the motor running currents that circulate during normal operation, these values are called Acceleration Time and Full Load Running Current. Using those values, a Load Current Curve can be drawn for any given motor and motor loading. In a motor protection relay the Acceleration Time Set Point is used to protect the equipment driven by the motor. This feature measures the maximum allowable time between a motor start and the normal motor running speed. This set point should not overwrite the value of locked rotor current or the thermal relay curve. This set point can be obtained from statistics of the operation of the equipment. Increase or decrease of acceleration times or running current values may give indication of loading induced faults. Loading induced faults are underload, overload, jamming, and high inertia. Underload Underload appears as a reduction in the average running current and means that the motor is running unloaded. Under current relays can detect a current lower than normal and issue an alarm signal, the relay setting could be 105 % of the motor no-load current. Overload Overload produces high currents that must be stopped before the motor is overheated. Overcurrent relays are used for this matter; the overcurrent relay following its own TCC will trip the contactor when an overload condition remains in the system for a certain amount of time. Jamming Jamming means a sudden speed reduction when the motor is operating at normal speed. Under this condition locked rotor currents will circulate when the motor tries to accelerate to get back to running speed, and the motor must be isolated before the Permissible Locked Rotor Time is exceeded. Definite time overcurrent relays can properly protect the motor; usual tripping setting is 2.5 x FLC with a time delay of 5 seconds. Digital relays can distinguish starting currents from running currents, therefore these relays do not operate during motor starting. These relays will start to operate only after motor running currents have been detected High Inertia High Inertia means that the motor can not accelerate to running speed. During this condition lock rotor currents will circulate through the motor. The motor protection relay must trip before the Permissible Locked Rotor Time is reached. Definite time O/C relays can properly protect the motor against locked rotor currents, but the following conditions apply: The pick up value of the setting of the overcurrent tripping should be no more than the 95% of the starting current, and The time delay should be greater than the load acceleration time at 95% of nominal voltage.

Protection of Large Induction Motors 1-877-955-8131

www.magnaelectric.com 6

System Characteristics Involved in Protection The power system should be operating at nominal values of voltage and frequency.

Abnormal system operation conditions are unbalanced voltages, underfrequency, overfrequency, overvoltage and undervoltage. Abnormal system operation conditions may produce unwanted overcurrents that will damage the motor; the most common problem is unbalanced voltages. Unbalance Voltages Operation of polyphase induction motors on unbalanced voltages produces negative sequence currents much larger than the unbalance of the voltages. These negative sequence currents cause overheating and reduction in output torque. The equivalent circuit of an induction motor with a phase open-circuited is the positive and negative sequence networks connected in series, and the magnitude of the positive and negative sequence currents is the same. Under single-phase conditions excessive heating can occur in the stator only if the current in one or more phases exceeds the nominal current value. Under these conditions the motor protection relay should trip the motor starter because a real fault has been detected, typical values are 40 % of full load current following in only two phases, and the time to trip depends on the thermal capacity of the motor and usually is 10 seconds. The ratio of positive sequence impedance to negative sequence impedance at normal speed is approximately equal to the ratio of the starting current (Is) to the normal full load running current (Iflc). Then, in a motor with an Is/Iflc ratio of 5 the negative sequence current for an unbalance of 2 % of the phase voltage will be 10 % of the positive sequence current. Typical values to alarm are between 5 to 10 % of unbalance in the line current. Typical values to trip are between 10 to 20 % of unbalance in the line current.

Overvoltage and Undervoltage NEMA MG1-1987 quotes a limit of 10 % of rated voltage. These values are not to protect the insulation; but to avoid overheating produced by the circulating currents. Overvoltage relays do not protect against high surge-voltages. The supply network must be fitted with surge-suppression devices or voltage limiters if such conditions may arise. System low voltages result in failure to start, high running currents, or loss of speed and eventually pull out from the system. High running currents will reduce the motor thermal overload times. Inverse time undervoltage relays can be used. Undervoltage relays trip the motor starter before the motor pulls out from the system.

Reclosing and Jogging

Protection of Large Induction Motors 1-877-955-8131

www.magnaelectric.com 7

Reclosing and jogging protection in big non-reversal induction motors is achieved using timers that allowed minimum time between starts, backspin time, and maximum number of starters per hour.

Summary The information required to analyzing the settings of protection relays for large induction motors was described. The three factors that define motor protection scheme are: Characteristics of the electrical motor Characteristics of the load Characteristics of the power system The measurement of operational currents provides information about the load. The characteristics of the load include average starting current, average acceleration time and running current. An analysis of voltage variations provides information about the power system itself. Time current curves for each motor-load are required to provide tabulated, graphical representation of the coordination of the motor protection devices in conjunction motor load, and motor thermal damage curves.

Protection of Large Induction Motors 1-877-955-8131

www.magnaelectric.com 8

You might also like