You are on page 1of 1412

Relion® 670 SERIES

Line distance protection REL670


Version 2.2 IEC
Technical manual
Document ID: 1MRK 506 370-UEN
Issued: October 2019
Revision: J
Product version: 2.2

© Copyright 2017 ABB. All rights reserved


Copyright
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third party, nor
used for any unauthorized purpose.

The software and hardware described in this document is furnished under a license and may
be used or disclosed only in accordance with the terms of such license.

This product includes software developed by the OpenSSL Project for use in the OpenSSL
Toolkit. (http://www.openssl.org/) This product includes cryptographic software written/
developed by: Eric Young (eay@cryptsoft.com) and Tim Hudson (tjh@cryptsoft.com).

Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names
mentioned in this document may be trademarks or registered trademarks of their respective
holders.

Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept or product
description and are not to be deemed as a statement of guaranteed properties. All persons
responsible for applying the equipment addressed in this manual must satisfy themselves that
each intended application is suitable and acceptable, including that any applicable safety or
other operational requirements are complied with. In particular, any risks in applications where
a system failure and/or product failure would create a risk for harm to property or persons
(including but not limited to personal injuries or death) shall be the sole responsibility of the
person or entity applying the equipment, and those so responsible are hereby requested to
ensure that all measures are taken to exclude or mitigate such risks.

This document has been carefully checked by ABB but deviations cannot be completely ruled
out. In case any errors are detected, the reader is kindly requested to notify the manufacturer.
Other than under explicit contractual commitments, in no event shall ABB be responsible or
liable for any loss or damage resulting from the use of this manual or the application of the
equipment.
Conformity
This product complies with the directive of the Council of the European Communities on the
approximation of the laws of the Member States relating to electromagnetic compatibility
(EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified
voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests
conducted by ABB in accordance with the product standard EN 60255-26 for the EMC directive,
and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive. The
product is designed in accordance with the international standards of the IEC 60255 series.
Table of contents

Table of contents

Section 1 Introduction.................................................................................................. 45
1.1 This manual................................................................................................................................. 45
1.1.1 Presumptions for Technical Data......................................................................................... 45
1.2 Intended audience......................................................................................................................45
1.3 Product documentation............................................................................................................46
1.3.1 Product documentation set...................................................................................................46
1.3.2 Document revision history..................................................................................................... 47
1.3.3 Related documents.................................................................................................................. 47
1.4 Document symbols and conventions.....................................................................................48
1.4.1 Symbols......................................................................................................................................48
1.4.2 Document conventions...........................................................................................................49
1.5 IEC 61850 edition 1 / edition 2 mapping................................................................................51

Section 2 Available functions.......................................................................................59


2.1 Main protection functions........................................................................................................59
2.2 Back-up protection functions.................................................................................................. 61
2.3 Control and monitoring functions.......................................................................................... 62
2.4 Communication...........................................................................................................................71
2.5 Basic IED functions.................................................................................................................... 74

Section 3 Analog inputs................................................................................................ 77


3.1 Introduction................................................................................................................................. 77
3.2 Function block............................................................................................................................. 77
3.3 Signals...........................................................................................................................................77
3.4 Settings........................................................................................................................................80
3.5 Monitored data...........................................................................................................................86
3.6 Operation principle.................................................................................................................... 87
3.7 Technical data.............................................................................................................................88

Section 4 Binary input and output modules...............................................................91


4.1 Binary input..................................................................................................................................91
4.1.1 Binary input debounce filter...................................................................................................91
4.1.2 Oscillation filter........................................................................................................................ 91
4.1.3 Settings...................................................................................................................................... 91
4.1.3.1 Setting parameters for binary input modules.............................................................. 91
4.1.3.2 Setting parameters for binary input/output module................................................. 92

Section 5 Local Human-Machine-Interface LHMI ......................................................93


5.1 Local HMI screen behaviour..................................................................................................... 93
5.1.1 Identification.............................................................................................................................93
5.1.2 Settings...................................................................................................................................... 93
5.2 Local HMI signals........................................................................................................................93

Line distance protection REL670 1


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

5.2.1 Identification.............................................................................................................................93
5.2.2 Function block.......................................................................................................................... 93
5.2.3 Signals........................................................................................................................................ 94
5.3 Basic part for LED indication module.................................................................................... 94
5.3.1 Identification............................................................................................................................ 94
5.3.2 Function block.......................................................................................................................... 94
5.3.3 Signals........................................................................................................................................ 95
5.3.4 Settings......................................................................................................................................95
5.4 LCD part for HMI function keys control module.................................................................. 96
5.4.1 Identification............................................................................................................................ 96
5.4.2 Function block.......................................................................................................................... 96
5.4.3 Signals........................................................................................................................................ 96
5.4.4 Settings...................................................................................................................................... 97
5.5 Operation principle....................................................................................................................98
5.5.1 Local HMI................................................................................................................................... 98
5.5.1.1 Keypad.................................................................................................................................. 99
5.5.1.2 Display................................................................................................................................. 101
5.5.1.3 LEDs.....................................................................................................................................103
5.5.2 LED configuration alternatives........................................................................................... 104
5.5.2.1 Functionality .....................................................................................................................104
5.5.2.2 Status LEDs........................................................................................................................104
5.5.2.3 Indication LEDs................................................................................................................. 105
5.5.3 Function keys...........................................................................................................................112
5.5.3.1 Functionality ......................................................................................................................112
5.5.3.2 Operation principle........................................................................................................... 112
5.5.3.3 Enabling and Disabling Authority on Function keys.................................................. 114

Section 6 Wide area measurement system.............................................................. 115


6.1 C37.118 Phasor Measurement Data Streaming Protocol Configuration PMUCONF... 115
6.1.1 Identification........................................................................................................................... 115
6.1.2 Functionality............................................................................................................................ 115
6.1.3 Operation principle................................................................................................................ 115
6.1.3.1 IEEE C37.118 Message Framework.................................................................................116
6.1.3.2 Short guidance for use of TCP........................................................................................ 117
6.1.3.3 Short guidance for use of UDP....................................................................................... 117
6.1.4 Settings.................................................................................................................................... 119
6.2 Protocol reporting via IEEE 1344 and C37.118 PMUREPORT.............................................121
6.2.1 Identification........................................................................................................................... 121
6.2.2 Functionality............................................................................................................................ 121
6.2.3 Function block.........................................................................................................................123
6.2.4 Signals.......................................................................................................................................125
6.2.5 Settings.................................................................................................................................... 129
6.2.6 Monitored data.......................................................................................................................140
6.2.7 Operation principle................................................................................................................144
6.2.7.1 Frequency reporting.........................................................................................................145
6.2.7.2 Reporting filters................................................................................................................146

2 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

6.2.7.3 Scaling Factors for ANALOGREPORT channels........................................................... 147


6.2.8 Technical data.........................................................................................................................149

Section 7 Differential protection...............................................................................151


7.1 High impedance differential protection, single phase HZPDIF ......................................151
7.1.1 Identification........................................................................................................................... 151
7.1.2 Functionality............................................................................................................................ 151
7.1.3 Function block......................................................................................................................... 151
7.1.4 Signals.......................................................................................................................................151
7.1.5 Settings.................................................................................................................................... 152
7.1.6 Monitored data....................................................................................................................... 152
7.1.7 Operation principle................................................................................................................ 152
7.1.7.1 Logic diagram....................................................................................................................154
7.1.8 Technical data......................................................................................................................... 154
7.2 Additional security logic for differential protection LDRGFC ........................................ 155
7.2.1 Identification...........................................................................................................................155
7.2.2 Functionality............................................................................................................................155
7.2.3 Function block.........................................................................................................................156
7.2.4 Signals...................................................................................................................................... 156
7.2.5 Settings.................................................................................................................................... 157
7.2.6 Monitored data....................................................................................................................... 158
7.2.7 Operation principle................................................................................................................ 158
7.2.8 Technical data......................................................................................................................... 161

Section 8 Impedance protection............................................................................... 163


8.1 Distance measuring zones, quadrilateral characteristic ZMQPDIS,
ZMQAPDIS, ZDRDIR.................................................................................................................. 163
8.1.1 Identification...........................................................................................................................163
8.1.2 Functionality............................................................................................................................163
8.1.3 Function block........................................................................................................................ 164
8.1.4 Signals...................................................................................................................................... 165
8.1.5 Settings.................................................................................................................................... 166
8.1.6 Monitored data.......................................................................................................................169
8.1.7 Operation principle................................................................................................................169
8.1.7.1 Full scheme measurement.............................................................................................. 169
8.1.7.2 Impedance characteristic................................................................................................170
8.1.7.3 Minimum operating current............................................................................................174
8.1.7.4 Measuring principles........................................................................................................ 174
8.1.7.5 Directional impedance element for quadrilateral characteristics.......................... 176
8.1.7.6 Simplified logic diagrams............................................................................................... 178
8.1.8 Technical data......................................................................................................................... 181
8.2 Phase selection, quad, fixed angle, load encroachment FDPSPDIS............................... 182
8.2.1 Identification...........................................................................................................................182
8.2.1.1 Identification..................................................................................................................... 182
8.2.2 Functionality............................................................................................................................182
8.2.3 Function block.........................................................................................................................183
8.2.4 Signals...................................................................................................................................... 183

Line distance protection REL670 3


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

8.2.5 Settings.................................................................................................................................... 184


8.2.6 Operation principle................................................................................................................ 185
8.2.6.1 Phase-to-earth fault......................................................................................................... 186
8.2.6.2 Phase-to-phase fault........................................................................................................188
8.2.6.3 Three-phase faults............................................................................................................189
8.2.6.4 Load encroachment......................................................................................................... 190
8.2.6.5 Minimum operate currents............................................................................................. 194
8.2.6.6 Simplified logic diagrams............................................................................................... 194
8.2.7 Technical data.........................................................................................................................199
8.3 Distance measuring zone, quadrilateral characteristic for series compensated
lines ZMCPDIS, ZMCAPDIS, ZDSRDIR....................................................................................199
8.3.1 Identification...........................................................................................................................199
8.3.2 Functionality........................................................................................................................... 200
8.3.3 Function block.........................................................................................................................201
8.3.4 Signals...................................................................................................................................... 201
8.3.5 Settings....................................................................................................................................203
8.3.6 Monitored data...................................................................................................................... 206
8.3.7 Operation principle................................................................................................................207
8.3.7.1 Full scheme measurement..............................................................................................207
8.3.7.2 Impedance characteristic............................................................................................... 207
8.3.7.3 Minimum operating current........................................................................................... 210
8.3.7.4 Measuring principles........................................................................................................210
8.3.7.5 Directionality for series compensation........................................................................ 213
8.3.7.6 Simplified logic diagrams............................................................................................... 214
8.3.8 Technical data......................................................................................................................... 217
8.4 Full-scheme distance measuring, Mho characteristic ZMHPDIS ................................... 218
8.4.1 Identification...........................................................................................................................218
8.4.2 Functionality............................................................................................................................218
8.4.3 Function block.........................................................................................................................219
8.4.4 Signals...................................................................................................................................... 219
8.4.5 Settings....................................................................................................................................220
8.4.6 Operation principle................................................................................................................ 222
8.4.6.1 Full scheme measurement.............................................................................................. 222
8.4.6.2 Impedance characteristic................................................................................................222
8.4.6.3 Basic operation characteristics..................................................................................... 223
8.4.6.4 Theory of operation......................................................................................................... 225
8.4.6.5 Simplified logic diagrams............................................................................................... 233
8.4.7 Technical data.........................................................................................................................236
8.5 Full-scheme distance protection, quadrilateral for earth faults ZMMPDIS,
ZMMAPDIS..................................................................................................................................237
8.5.1 Identification...........................................................................................................................237
8.5.2 Functionality............................................................................................................................237
8.5.3 Function block........................................................................................................................ 238
8.5.4 Signals...................................................................................................................................... 238
8.5.5 Settings....................................................................................................................................239
8.5.6 Operation principle................................................................................................................ 241

4 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

8.5.6.1 Full scheme measurement.............................................................................................. 241


8.5.6.2 Impedance characteristic................................................................................................241
8.5.6.3 Minimum operating current........................................................................................... 243
8.5.6.4 Measuring principles........................................................................................................243
8.5.6.5 Directionality..................................................................................................................... 245
8.5.6.6 Simplified logic diagrams............................................................................................... 247
8.5.7 Technical data.........................................................................................................................250
8.6 Directional impedance element for mho characteristic and additional distance
protection directional function for earth faults ZDMRDIR, ZDARDIR............................250
8.6.1 Identification.......................................................................................................................... 250
8.6.2 Functionality............................................................................................................................251
8.6.3 Function block.........................................................................................................................251
8.6.4 Signals.......................................................................................................................................251
8.6.5 Settings.................................................................................................................................... 252
8.6.6 Monitored data.......................................................................................................................253
8.6.7 Operation principle................................................................................................................254
8.6.7.1 Directional impedance element for mho characteristic ZDMRDIR.........................254
8.6.7.2 Additional distance protection directional function for earth faults ZDARDIR...256
8.7 Mho impedance supervision logic ZSMGAPC..................................................................... 258
8.7.1 Identification.......................................................................................................................... 258
8.7.2 Functionality........................................................................................................................... 258
8.7.3 Function block........................................................................................................................ 258
8.7.4 Signals...................................................................................................................................... 259
8.7.5 Settings....................................................................................................................................259
8.7.6 Operation principle............................................................................................................... 260
8.7.6.1 Fault inception detection............................................................................................... 260
8.8 Faulty phase identification with load encroachment FMPSPDIS....................................261
8.8.1 Identification...........................................................................................................................261
8.8.2 Functionality............................................................................................................................261
8.8.3 Function block.........................................................................................................................261
8.8.4 Signals...................................................................................................................................... 261
8.8.5 Settings.................................................................................................................................... 262
8.8.6 Operation principle................................................................................................................263
8.8.6.1 The phase selection function......................................................................................... 263
8.8.7 Technical data......................................................................................................................... 273
8.9 Distance protection zone, quadrilateral characteristic, separate settings
ZMRPDIS, ZMRAPDIS and ZDRDIR......................................................................................... 273
8.9.1 Identification...........................................................................................................................273
8.9.2 Functionality........................................................................................................................... 274
8.9.3 Function block.........................................................................................................................275
8.9.4 Signals...................................................................................................................................... 275
8.9.5 Settings.................................................................................................................................... 277
8.9.6 Operation principle................................................................................................................279
8.9.6.1 Full scheme measurement.............................................................................................. 279
8.9.6.2 Impedance characteristic............................................................................................... 280
8.9.6.3 Minimum operating current........................................................................................... 283

Line distance protection REL670 5


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

8.9.6.4 Measuring principles........................................................................................................283


8.9.6.5 Directional impedance element for quadrilateral characteristics......................... 286
8.9.6.6 Simplified logic diagrams............................................................................................... 287
8.9.7 Technical data........................................................................................................................ 290
8.10 Phase selection, quadrilateral characteristic with settable angle FRPSPDIS...............291
8.10.1 Identification...........................................................................................................................291
8.10.2 Functionality............................................................................................................................291
8.10.3 Function block........................................................................................................................ 292
8.10.4 Signals...................................................................................................................................... 292
8.10.5 Settings....................................................................................................................................293
8.10.6 Operation principle................................................................................................................294
8.10.6.1 Phase-to-earth fault.........................................................................................................295
8.10.6.2 Phase-to-phase fault........................................................................................................297
8.10.6.3 Three-phase faults........................................................................................................... 299
8.10.6.4 Load encroachment......................................................................................................... 299
8.10.6.5 Minimum operate currents.............................................................................................303
8.10.6.6 Simplified logic diagrams...............................................................................................303
8.10.7 Technical data.........................................................................................................................307
8.11 High speed distance protection ZMFPDIS..........................................................................308
8.11.1 Identification.......................................................................................................................... 308
8.11.2 Functionality........................................................................................................................... 308
8.11.3 Function block........................................................................................................................ 309
8.11.4 Signals......................................................................................................................................309
8.11.5 Settings.................................................................................................................................... 312
8.11.6 Monitored data....................................................................................................................... 317
8.11.7 Operation principle................................................................................................................ 318
8.11.7.1 Filtering...............................................................................................................................318
8.11.7.2 Distance measuring zones.............................................................................................. 319
8.11.7.3 Phase-selection element................................................................................................. 319
8.11.7.4 Directional criteria............................................................................................................ 321
8.11.7.5 Fuse failure......................................................................................................................... 321
8.11.7.6 Power swings.....................................................................................................................322
8.11.7.7 Measuring principles........................................................................................................322
8.11.7.8 Load encroachment......................................................................................................... 333
8.11.7.9 Simplified logic schemes................................................................................................ 334
8.11.7.10 Measurement.....................................................................................................................338
8.11.8 Technical data.........................................................................................................................343
8.12 High speed distance protection for series compensated lines ZMFCPDIS ................ 344
8.12.1 Identification.......................................................................................................................... 344
8.12.2 Functionality........................................................................................................................... 344
8.12.3 Function block........................................................................................................................ 345
8.12.4 Signals......................................................................................................................................346
8.12.5 Settings....................................................................................................................................348
8.12.6 Monitored data.......................................................................................................................355
8.12.7 Operation principle................................................................................................................356
8.12.7.1 Filtering.............................................................................................................................. 356

6 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

8.12.7.2 Distance measuring zones............................................................................................. 356


8.12.7.3 Phase-selection element................................................................................................. 357
8.12.7.4 Directional criteria............................................................................................................358
8.12.7.5 Transient directional element........................................................................................359
8.12.7.6 Fuse failure........................................................................................................................ 360
8.12.7.7 Power swings.................................................................................................................... 360
8.12.7.8 Measurement principles................................................................................................. 360
8.12.7.9 Load encroachment..........................................................................................................372
8.12.7.10 Simplified logic schemes.................................................................................................372
8.12.7.11 Measurement.....................................................................................................................378
8.12.8 Technical data.........................................................................................................................383
8.13 Power swing detection ZMRPSB ..........................................................................................384
8.13.1 Identification.......................................................................................................................... 384
8.13.2 Functionality........................................................................................................................... 384
8.13.3 Function block........................................................................................................................ 384
8.13.4 Signals......................................................................................................................................384
8.13.5 Settings....................................................................................................................................385
8.13.6 Operation principle................................................................................................................386
8.13.6.1 Resistive reach in forward direction.............................................................................387
8.13.6.2 Resistive reach in reverse direction..............................................................................388
8.13.6.3 Reactive reach in forward and reverse direction....................................................... 388
8.13.6.4 Basic detection logic....................................................................................................... 389
8.13.6.5 Operating and inhibit conditions..................................................................................390
8.13.7 Technical data......................................................................................................................... 391
8.14 Automatic switch onto fault logic ZCVPSOF ..................................................................... 391
8.14.1 Identification...........................................................................................................................391
8.14.2 Functionality........................................................................................................................... 392
8.14.3 Function block........................................................................................................................ 392
8.14.4 Signals...................................................................................................................................... 392
8.14.5 Settings....................................................................................................................................392
8.14.6 Monitored data.......................................................................................................................393
8.14.7 Operation principle................................................................................................................393
8.14.8 Technical data.........................................................................................................................395
8.15 Power swing logic PSLPSCH ................................................................................................. 395
8.15.1 Identification.......................................................................................................................... 395
8.15.2 Functionality........................................................................................................................... 395
8.15.3 Function block........................................................................................................................ 396
8.15.4 Signals...................................................................................................................................... 396
8.15.5 Settings.................................................................................................................................... 397
8.15.6 Operation principle................................................................................................................397
8.15.6.1 Communication and tripping logic............................................................................... 397
8.15.6.2 Blocking logic.................................................................................................................... 398
8.16 Pole slip protection PSPPPAM .............................................................................................. 399
8.16.1 Identification.......................................................................................................................... 399
8.16.2 Functionality........................................................................................................................... 399
8.16.3 Function block........................................................................................................................400

Line distance protection REL670 7


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

8.16.4 Signals..................................................................................................................................... 400


8.16.5 Settings....................................................................................................................................401
8.16.6 Monitored data.......................................................................................................................401
8.16.7 Operation principle............................................................................................................... 402
8.16.8 Technical data........................................................................................................................ 404
8.17 Out-of-step protection OOSPPAM....................................................................................... 405
8.17.1 Identification.......................................................................................................................... 405
8.17.2 Functionality...........................................................................................................................405
8.17.3 Function block........................................................................................................................405
8.17.4 Signals......................................................................................................................................406
8.17.5 Settings................................................................................................................................... 406
8.17.6 Monitored data...................................................................................................................... 407
8.17.7 Operation principle............................................................................................................... 408
8.17.7.1 Lens characteristic........................................................................................................... 410
8.17.7.2 Detecting an out-of-step condition.............................................................................. 412
8.17.7.3 Maximum slip frequency................................................................................................. 412
8.17.7.4 Taking care of the circuit breaker .................................................................................413
8.17.7.5 Design................................................................................................................................. 415
8.17.8 Technical data.........................................................................................................................416
8.18 Phase preference logic PPLPHIZ........................................................................................... 416
8.18.1 Identification...........................................................................................................................416
8.18.2 Functionality........................................................................................................................... 416
8.18.3 Function block.........................................................................................................................417
8.18.4 Signals...................................................................................................................................... 417
8.18.5 Settings.................................................................................................................................... 418
8.18.6 Operation principle................................................................................................................418
8.18.6.1 Residual current criteria.................................................................................................. 419
8.18.6.2 Phase selection................................................................................................................. 420
8.18.6.3 Preference logic.................................................................................................................421
8.18.6.4 Output.................................................................................................................................423
8.19 Phase preference logic PPL2PHIZ......................................................................................... 424
8.19.1 Identification.......................................................................................................................... 424
8.19.2 Functionality........................................................................................................................... 425
8.19.3 Function block........................................................................................................................ 425
8.19.4 Signals...................................................................................................................................... 425
8.19.5 Settings....................................................................................................................................426
8.19.6 Operation principle................................................................................................................426
8.19.6.1 Residual current criteria.................................................................................................. 427
8.19.6.2 Phase selection................................................................................................................. 428
8.19.6.3 Preference logic................................................................................................................ 429
8.19.6.4 Output.................................................................................................................................431
8.19.7 Technical data.........................................................................................................................432

Section 9 Current protection..................................................................................... 433


9.1 Instantaneous phase overcurrent protection PHPIOC .................................................... 433
9.1.1 Identification.......................................................................................................................... 433

8 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

9.1.2 Functionality........................................................................................................................... 433


9.1.3 Function block........................................................................................................................ 433
9.1.4 Signals...................................................................................................................................... 433
9.1.5 Settings....................................................................................................................................434
9.1.6 Monitored data...................................................................................................................... 434
9.1.7 Operation principle................................................................................................................435
9.1.8 Technical data.........................................................................................................................435
9.2 Directional phase overcurrent protection, four steps OC4PTOC.................................. 436
9.2.1 Identification.......................................................................................................................... 436
9.2.2 Functionality........................................................................................................................... 436
9.2.3 Function block........................................................................................................................ 437
9.2.4 Signals...................................................................................................................................... 437
9.2.5 Settings....................................................................................................................................439
9.2.6 Monitored data...................................................................................................................... 444
9.2.7 Operation principle............................................................................................................... 444
9.2.8 Technical data........................................................................................................................ 450
9.3 Instantaneous residual overcurrent protection EFPIOC ................................................. 451
9.3.1 Identification...........................................................................................................................451
9.3.2 Functionality............................................................................................................................451
9.3.3 Function block........................................................................................................................ 451
9.3.4 Signals...................................................................................................................................... 451
9.3.5 Settings....................................................................................................................................452
9.3.6 Monitored data.......................................................................................................................452
9.3.7 Operation principle................................................................................................................453
9.3.8 Technical data.........................................................................................................................453
9.4 Directional residual overcurrent protection, four steps EF4PTOC ...............................454
9.4.1 Identification.......................................................................................................................... 454
9.4.2 Functionality........................................................................................................................... 454
9.4.3 Function block........................................................................................................................ 455
9.4.4 Signals......................................................................................................................................455
9.4.5 Settings....................................................................................................................................456
9.4.6 Monitored data.......................................................................................................................462
9.4.7 Operation principle................................................................................................................462
9.4.7.1 Operating quantity within the function.......................................................................462
9.4.7.2 Internal polarizing............................................................................................................ 463
9.4.7.3 External polarizing for earth-fault function................................................................465
9.4.7.4 Directional detection for earth fault function............................................................465
9.4.7.5 Base quantities within the protection......................................................................... 465
9.4.7.6 Internal earth-fault protection structure.................................................................... 465
9.4.7.7 Four residual overcurrent steps....................................................................................466
9.4.7.8 Directional supervision element with integrated directional
comparison function....................................................................................................... 467
9.4.7.9 Second harmonic blocking element............................................................................. 469
9.4.7.10 Switch on to fault feature............................................................................................... 471
9.4.8 Technical data.........................................................................................................................473
9.5 Four step directional negative phase sequence overcurrent protection NS4PTOC . 474

Line distance protection REL670 9


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

9.5.1 Identification.......................................................................................................................... 474


9.5.2 Functionality........................................................................................................................... 474
9.5.3 Function block........................................................................................................................ 475
9.5.4 Signals...................................................................................................................................... 475
9.5.5 Settings....................................................................................................................................476
9.5.6 Monitored data...................................................................................................................... 480
9.5.7 Operation principle............................................................................................................... 480
9.5.7.1 Operating quantity within the function...................................................................... 480
9.5.7.2 Internal polarizing facility of the function................................................................... 481
9.5.7.3 External polarizing for negative sequence function..................................................481
9.5.7.4 Internal negative sequence protection structure......................................................482
9.5.7.5 Four negative sequence overcurrent stages.............................................................. 482
9.5.7.6 Directional supervision element with integrated directional comparison
function.............................................................................................................................. 483
9.5.8 Technical data........................................................................................................................ 485
9.6 Sensitive directional residual overcurrent and power protection SDEPSDE ..............486
9.6.1 Identification.......................................................................................................................... 486
9.6.2 Functionality........................................................................................................................... 486
9.6.3 Function block........................................................................................................................488
9.6.4 Signals......................................................................................................................................488
9.6.5 Settings................................................................................................................................... 489
9.6.6 Monitored data.......................................................................................................................491
9.6.7 Operation principle................................................................................................................491
9.6.7.1 Function inputs................................................................................................................. 491
9.6.8 Technical data.........................................................................................................................497
9.7 Thermal overload protection, one time constant, Celsius/Fahrenheit
LCPTTR/LFPTTR.......................................................................................................................498
9.7.1 Identification.......................................................................................................................... 498
9.7.2 Functionality........................................................................................................................... 498
9.7.3 Function block........................................................................................................................ 499
9.7.4 Signals......................................................................................................................................499
9.7.5 Settings................................................................................................................................... 500
9.7.6 Monitored data.......................................................................................................................502
9.7.7 Operation principle................................................................................................................502
9.7.8 Technical data........................................................................................................................ 505
9.8 Breaker failure protection CCRBRF...................................................................................... 505
9.8.1 Identification.......................................................................................................................... 505
9.8.2 Functionality........................................................................................................................... 505
9.8.3 Function block........................................................................................................................ 506
9.8.4 Signals......................................................................................................................................506
9.8.5 Settings....................................................................................................................................507
9.8.6 Monitored data...................................................................................................................... 508
9.8.7 Operation principle............................................................................................................... 508
9.8.8 Technical data......................................................................................................................... 513
9.9 Stub protection STBPTOC ..................................................................................................... 514
9.9.1 Identification...........................................................................................................................514

10 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

9.9.2 Functionality............................................................................................................................514
9.9.3 Function block........................................................................................................................ 514
9.9.4 Signals...................................................................................................................................... 514
9.9.5 Settings.................................................................................................................................... 515
9.9.6 Monitored data....................................................................................................................... 515
9.9.7 Operation principle................................................................................................................ 515
9.9.8 Technical data......................................................................................................................... 516
9.10 Pole discordance protection CCPDSC..................................................................................516
9.10.1 Identification...........................................................................................................................516
9.10.2 Functionality............................................................................................................................517
9.10.3 Function block.........................................................................................................................517
9.10.4 Signals.......................................................................................................................................517
9.10.5 Settings.................................................................................................................................... 518
9.10.6 Monitored data....................................................................................................................... 518
9.10.7 Operation principle................................................................................................................ 518
9.10.7.1 Pole discordance signaling from circuit breaker....................................................... 520
9.10.7.2 Unsymmetrical current detection..................................................................................521
9.10.8 Technical data......................................................................................................................... 521
9.11 Directional underpower protection GUPPDUP................................................................... 521
9.11.1 Identification........................................................................................................................... 521
9.11.2 Functionality............................................................................................................................521
9.11.3 Function block........................................................................................................................ 522
9.11.4 Signals...................................................................................................................................... 523
9.11.5 Settings.................................................................................................................................... 523
9.11.6 Monitored data.......................................................................................................................525
9.11.7 Operation principle................................................................................................................525
9.11.7.1 Low pass filtering............................................................................................................. 526
9.11.7.2 Calibration of analog inputs...........................................................................................527
9.11.8 Technical data.........................................................................................................................528
9.12 Directional overpower protection GOPPDOP ....................................................................528
9.12.1 Identification.......................................................................................................................... 528
9.12.2 Functionality........................................................................................................................... 528
9.12.3 Function block........................................................................................................................ 529
9.12.4 Signals...................................................................................................................................... 529
9.12.5 Settings....................................................................................................................................530
9.12.6 Monitored data....................................................................................................................... 531
9.12.7 Operation principle................................................................................................................ 531
9.12.7.1 Low pass filtering............................................................................................................. 533
9.12.7.2 Calibration of analog inputs...........................................................................................533
9.12.8 Technical data.........................................................................................................................534
9.13 Broken conductor check BRCPTOC ..................................................................................... 535
9.13.1 Identification...........................................................................................................................535
9.13.2 Functionality........................................................................................................................... 535
9.13.3 Function block........................................................................................................................ 535
9.13.4 Signals...................................................................................................................................... 535
9.13.5 Settings....................................................................................................................................536

Line distance protection REL670 11


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

9.13.6 Monitored data.......................................................................................................................536


9.13.7 Operation principle................................................................................................................536
9.13.8 Technical data......................................................................................................................... 537
9.14 Voltage-restrained time overcurrent protection VRPVOC...............................................538
9.14.1 Identification.......................................................................................................................... 538
9.14.2 Functionality........................................................................................................................... 538
9.14.3 Function block........................................................................................................................ 538
9.14.4 Signals...................................................................................................................................... 538
9.14.5 Settings....................................................................................................................................539
9.14.6 Monitored data...................................................................................................................... 540
9.14.7 Operation principle............................................................................................................... 540
9.14.7.1 Measured quantities........................................................................................................540
9.14.7.2 Base quantities.................................................................................................................540
9.14.7.3 Overcurrent protection...................................................................................................540
9.14.7.4 Logic diagram................................................................................................................... 542
9.14.7.5 Undervoltage protection................................................................................................ 542
9.14.8 Technical data.........................................................................................................................543

Section 10 Voltage protection.....................................................................................545


10.1 Two step undervoltage protection UV2PTUV ................................................................... 545
10.1.1 Identification.......................................................................................................................... 545
10.1.2 Functionality........................................................................................................................... 545
10.1.3 Function block........................................................................................................................ 545
10.1.4 Signals......................................................................................................................................546
10.1.5 Settings....................................................................................................................................547
10.1.6 Monitored data...................................................................................................................... 549
10.1.7 Operation principle............................................................................................................... 549
10.1.7.1 Measurement principle................................................................................................... 549
10.1.7.2 Time delay..........................................................................................................................550
10.1.7.3 Blocking.............................................................................................................................. 555
10.1.7.4 Design................................................................................................................................. 556
10.1.8 Technical data.........................................................................................................................557
10.2 Two step overvoltage protection OV2PTOV ...................................................................... 557
10.2.1 Identification...........................................................................................................................557
10.2.2 Functionality OV2PTOV.........................................................................................................557
10.2.3 Function block........................................................................................................................ 558
10.2.4 Signals...................................................................................................................................... 558
10.2.5 Settings....................................................................................................................................559
10.2.6 Monitored data....................................................................................................................... 561
10.2.7 Operation principle................................................................................................................ 561
10.2.7.1 Measurement principle....................................................................................................562
10.2.7.2 Time delay.......................................................................................................................... 562
10.2.7.3 Blocking.............................................................................................................................. 567
10.2.7.4 Design................................................................................................................................. 567
10.2.8 Technical data........................................................................................................................ 568
10.3 Two step residual overvoltage protection ROV2PTOV ....................................................569

12 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

10.3.1 Identification.......................................................................................................................... 569


10.3.2 Functionality........................................................................................................................... 569
10.3.3 Function block........................................................................................................................ 569
10.3.4 Signals...................................................................................................................................... 570
10.3.5 Settings....................................................................................................................................570
10.3.6 Monitored data....................................................................................................................... 572
10.3.7 Operation principle................................................................................................................ 572
10.3.7.1 Measurement principle....................................................................................................572
10.3.7.2 Time delay.......................................................................................................................... 572
10.3.7.3 Blocking.............................................................................................................................. 578
10.3.7.4 Design................................................................................................................................. 578
10.3.8 Technical data.........................................................................................................................579
10.4 Overexcitation protection OEXPVPH .................................................................................. 579
10.4.1 Identification...........................................................................................................................579
10.4.2 Functionality........................................................................................................................... 579
10.4.3 Function block........................................................................................................................580
10.4.4 Signals......................................................................................................................................580
10.4.5 Settings................................................................................................................................... 580
10.4.6 Monitored data....................................................................................................................... 581
10.4.7 Operation principle................................................................................................................582
10.4.7.1 Measured voltage.............................................................................................................584
10.4.7.2 Operate time of the overexcitation protection......................................................... 584
10.4.7.3 Cooling............................................................................................................................... 588
10.4.7.4 Overexcitation protection function measurands...................................................... 588
10.4.7.5 Overexcitation alarm....................................................................................................... 589
10.4.7.6 Logic diagram................................................................................................................... 589
10.4.8 Technical data........................................................................................................................ 589
10.5 Voltage differential protection VDCPTOV ......................................................................... 590
10.5.1 Identification.......................................................................................................................... 590
10.5.2 Functionality........................................................................................................................... 590
10.5.3 Function block........................................................................................................................ 590
10.5.4 Signals......................................................................................................................................590
10.5.5 Settings.................................................................................................................................... 591
10.5.6 Monitored data.......................................................................................................................592
10.5.7 Operation principle................................................................................................................592
10.5.8 Technical data.........................................................................................................................593
10.6 Loss of voltage check LOVPTUV .......................................................................................... 594
10.6.1 Identification.......................................................................................................................... 594
10.6.2 Functionality........................................................................................................................... 594
10.6.3 Function block........................................................................................................................ 594
10.6.4 Signals......................................................................................................................................594
10.6.5 Settings....................................................................................................................................595
10.6.6 Operation principle................................................................................................................595
10.6.7 Technical data........................................................................................................................ 596
10.7 Radial feeder protection PAPGAPC.......................................................................................597
10.7.1 Identification...........................................................................................................................597

Line distance protection REL670 13


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

10.7.2 Functionality........................................................................................................................... 597


10.7.3 Function block........................................................................................................................ 597
10.7.4 Signals......................................................................................................................................598
10.7.5 Settings....................................................................................................................................598
10.7.6 Monitored data...................................................................................................................... 599
10.7.7 Principle of operation........................................................................................................... 599
10.7.7.1 Faulted phase selection.................................................................................................. 599
10.7.7.2 Residual current detection.............................................................................................600
10.7.7.3 Fast fault clearance ......................................................................................................... 601
10.7.7.4 Delayed fault clearance................................................................................................... 601
10.7.7.5 Trip and autoreclose logic.............................................................................................. 602
10.7.8 Technical data........................................................................................................................ 603

Section 11 Frequency protection................................................................................ 605


11.1 Underfrequency protection SAPTUF ...................................................................................605
11.1.1 Identification.......................................................................................................................... 605
11.1.2 Functionality........................................................................................................................... 605
11.1.3 Function block........................................................................................................................ 605
11.1.4 Signals......................................................................................................................................606
11.1.5 Settings................................................................................................................................... 606
11.1.6 Operation principle................................................................................................................607
11.1.6.1 Measurement principle................................................................................................... 607
11.1.6.2 Time delay..........................................................................................................................607
11.1.6.3 Voltage dependent time delay...................................................................................... 608
11.1.6.4 Blocking..............................................................................................................................609
11.1.6.5 Design.................................................................................................................................609
11.1.7 Technical data.........................................................................................................................610
11.2 Overfrequency protection SAPTOF ..................................................................................... 610
11.2.1 Identification...........................................................................................................................610
11.2.2 Functionality........................................................................................................................... 610
11.2.3 Function block......................................................................................................................... 611
11.2.4 Signals.......................................................................................................................................611
11.2.5 Settings.................................................................................................................................... 611
11.2.6 Operation principle................................................................................................................ 612
11.2.6.1 Measurement principle.................................................................................................... 612
11.2.6.2 Time delay.......................................................................................................................... 612
11.2.6.3 Blocking.............................................................................................................................. 612
11.2.6.4 Design................................................................................................................................. 613
11.2.7 Technical data......................................................................................................................... 613
11.3 Rate-of-change of frequency protection SAPFRC ............................................................ 614
11.3.1 Identification...........................................................................................................................614
11.3.2 Functionality........................................................................................................................... 614
11.3.3 Function block........................................................................................................................ 614
11.3.4 Signals...................................................................................................................................... 614
11.3.5 Settings.................................................................................................................................... 615
11.3.6 Operation principle................................................................................................................ 615

14 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

11.3.6.1 Measurement principle....................................................................................................615


11.3.6.2 Time delay.......................................................................................................................... 616
11.3.6.3 Blocking.............................................................................................................................. 616
11.3.6.4 Design................................................................................................................................. 616
11.3.7 Technical data......................................................................................................................... 617

Section 12 Multipurpose protection........................................................................... 619


12.1 General current and voltage protection CVGAPC.............................................................. 619
12.1.1 Identification...........................................................................................................................619
12.1.2 Functionality........................................................................................................................... 619
12.1.3 Function block........................................................................................................................ 619
12.1.4 Signals......................................................................................................................................620
12.1.5 Settings.................................................................................................................................... 621
12.1.6 Monitored data.......................................................................................................................628
12.1.7 Operation principle................................................................................................................628
12.1.7.1 Measured quantities within CVGAPC........................................................................... 628
12.1.7.2 Base quantities for CVGAPC function...........................................................................631
12.1.7.3 Built-in overcurrent protection steps........................................................................... 631
12.1.7.4 Built-in undercurrent protection steps........................................................................636
12.1.7.5 Built-in overvoltage protection steps.......................................................................... 636
12.1.7.6 Built-in undervoltage protection steps........................................................................636
12.1.7.7 Logic diagram................................................................................................................... 636
12.1.8 Technical data.........................................................................................................................641

Section 13 System protection and control................................................................ 643


13.1 Multipurpose filter SMAIHPAC.............................................................................................. 643
13.1.1 Identification.......................................................................................................................... 643
13.1.2 Functionality........................................................................................................................... 643
13.1.3 Function block........................................................................................................................ 643
13.1.4 Signals......................................................................................................................................643
13.1.5 Settings................................................................................................................................... 644
13.1.6 Operation principle............................................................................................................... 644
13.1.7 Filter calculation example.................................................................................................... 647

Section 14 Secondary system supervision................................................................ 649


14.1 Current circuit supervision CCSSPVC.................................................................................. 649
14.1.1 Identification.......................................................................................................................... 649
14.1.2 Functionality........................................................................................................................... 649
14.1.3 Function block........................................................................................................................ 649
14.1.4 Signals......................................................................................................................................649
14.1.5 Settings................................................................................................................................... 650
14.1.6 Operation principle............................................................................................................... 650
14.1.7 Technical data......................................................................................................................... 651
14.2 Fuse failure supervision FUFSPVC........................................................................................ 652
14.2.1 Identification.......................................................................................................................... 652
14.2.2 Functionality........................................................................................................................... 652
14.2.3 Function block........................................................................................................................ 652

Line distance protection REL670 15


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

14.2.4 Signals...................................................................................................................................... 653


14.2.5 Settings....................................................................................................................................654
14.2.6 Monitored data.......................................................................................................................655
14.2.7 Operation principle................................................................................................................655
14.2.7.1 Zero and negative sequence detection....................................................................... 655
14.2.7.2 Delta current and delta voltage detection.................................................................. 657
14.2.7.3 Dead line detection.......................................................................................................... 659
14.2.7.4 Main logic...........................................................................................................................660
14.2.8 Technical data.........................................................................................................................663
14.3 Fuse failure supervision VDSPVC.......................................................................................... 663
14.3.1 Identification.......................................................................................................................... 663
14.3.2 Functionality........................................................................................................................... 663
14.3.3 Function block........................................................................................................................ 664
14.3.4 Signals......................................................................................................................................664
14.3.5 Settings....................................................................................................................................665
14.3.6 Monitored data...................................................................................................................... 665
14.3.7 Operation principle............................................................................................................... 666
14.3.8 Technical data.........................................................................................................................667
14.4 Voltage based delta supervision DELVSPVC...................................................................... 667
14.4.1 Identification.......................................................................................................................... 667
14.4.2 Functionality........................................................................................................................... 667
14.4.3 Function block........................................................................................................................ 668
14.4.4 Signals......................................................................................................................................668
14.4.5 Settings................................................................................................................................... 669
14.4.6 Monitored data...................................................................................................................... 669
14.4.7 Operation principle............................................................................................................... 669
14.4.7.1 Minimum signal level check............................................................................................ 670
14.4.7.2 Mode of operation........................................................................................................... 670
14.4.7.3 Instantaneous 1 cycle / 2 cycle ..................................................................................... 670
14.4.7.4 RMS/DFT based supervision.......................................................................................... 671
14.4.7.5 Angle based supervision or vector shift supervision.................................................671
14.4.8 Technical data.........................................................................................................................673
14.5 Current based delta supervision DELISPVC........................................................................ 673
14.5.1 Identification...........................................................................................................................673
14.5.2 Functionality........................................................................................................................... 673
14.5.3 Function block........................................................................................................................ 674
14.5.4 Signals...................................................................................................................................... 674
14.5.5 Settings....................................................................................................................................675
14.5.6 Monitored data.......................................................................................................................675
14.5.7 Operation principle................................................................................................................676
14.5.7.1 Minimum signal level check............................................................................................ 676
14.5.7.2 Mode of operation............................................................................................................676
14.5.7.3 Instantaneous 1 cycle / 2 cycle ......................................................................................676
14.5.7.4 RMS/DFT based supervision.......................................................................................... 677
14.5.7.5 2nd Harmonic blocking..................................................................................................... 677
14.5.7.6 3rd Harmonic based adaption........................................................................................ 678

16 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

14.5.8 Technical data.........................................................................................................................679


14.6 Delta supervision of real input DELSPVC............................................................................ 679
14.6.1 Identification.......................................................................................................................... 679
14.6.2 Functionality........................................................................................................................... 679
14.6.3 Function block........................................................................................................................ 679
14.6.4 Signals......................................................................................................................................680
14.6.5 Settings................................................................................................................................... 680
14.6.6 Operation principle............................................................................................................... 680

Section 15 Control.........................................................................................................683
15.1 Synchrocheck, energizing check, and synchronizing SESRSYN...................................... 683
15.1.1 Identification.......................................................................................................................... 683
15.1.2 Functionality........................................................................................................................... 683
15.1.3 Function block........................................................................................................................ 684
15.1.4 Signals......................................................................................................................................684
15.1.5 Settings................................................................................................................................... 686
15.1.6 Monitored data...................................................................................................................... 688
15.1.7 Operation principle............................................................................................................... 689
15.1.7.1 Basic functionality............................................................................................................689
15.1.7.2 Logic diagrams................................................................................................................. 689
15.1.8 Technical data........................................................................................................................ 698
15.2 Autorecloser for 1 phase, 2 phase and/or 3 phase operation SMBRREC .....................699
15.2.1 Identification.......................................................................................................................... 700
15.2.2 Functionality........................................................................................................................... 700
15.2.3 Function block........................................................................................................................ 700
15.2.4 Signals...................................................................................................................................... 701
15.2.5 Settings....................................................................................................................................702
15.2.6 Operation principle............................................................................................................... 704
15.2.6.1 Terminology explanation................................................................................................ 704
15.2.6.2 Status descriptions..........................................................................................................704
15.2.6.3 Description of the status transition.............................................................................705
15.2.6.4 Functional sequence description..................................................................................706
15.2.6.5 Time sequence diagrams.................................................................................................717
15.2.7 Technical data.........................................................................................................................720
15.3 Interlocking ...............................................................................................................................720
15.3.1 Functionality........................................................................................................................... 720
15.3.2 Operation principle................................................................................................................ 721
15.3.3 Logical node for interlocking SCILO .................................................................................. 723
15.3.3.1 Identification..................................................................................................................... 723
15.3.3.2 Functionality...................................................................................................................... 723
15.3.3.3 Function block................................................................................................................... 723
15.3.3.4 Signals.................................................................................................................................724
15.3.3.5 Logic diagram....................................................................................................................724
15.3.4 Interlocking for busbar earthing switch BB_ES .............................................................. 724
15.3.4.1 Identification..................................................................................................................... 724
15.3.4.2 Functionality...................................................................................................................... 725

Line distance protection REL670 17


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

15.3.4.3 Function block................................................................................................................... 725


15.3.4.4 Logic diagram....................................................................................................................725
15.3.4.5 Signals.................................................................................................................................725
15.3.5 Interlocking for bus-section breaker A1A2_BS................................................................. 726
15.3.5.1 Identification..................................................................................................................... 726
15.3.5.2 Functionality...................................................................................................................... 726
15.3.5.3 Function block................................................................................................................... 727
15.3.5.4 Logic diagram....................................................................................................................727
15.3.5.5 Signals.................................................................................................................................728
15.3.6 Interlocking for bus-section disconnector A1A2_DC ..................................................... 729
15.3.6.1 Identification..................................................................................................................... 729
15.3.6.2 Functionality......................................................................................................................730
15.3.6.3 Function block...................................................................................................................730
15.3.6.4 Logic diagram.................................................................................................................... 731
15.3.6.5 Signals................................................................................................................................. 731
15.3.7 Interlocking for bus-coupler bay ABC_BC .........................................................................732
15.3.7.1 Identification..................................................................................................................... 732
15.3.7.2 Functionality...................................................................................................................... 732
15.3.7.3 Function block................................................................................................................... 733
15.3.7.4 Logic diagram................................................................................................................... 734
15.3.7.5 Signals.................................................................................................................................736
15.3.8 Interlocking for 1 1/2 CB BH ................................................................................................ 738
15.3.8.1 Identification..................................................................................................................... 738
15.3.8.2 Functionality...................................................................................................................... 738
15.3.8.3 Function blocks.................................................................................................................740
15.3.8.4 Logic diagrams................................................................................................................. 742
15.3.8.5 Signals.................................................................................................................................745
15.3.9 Interlocking for double CB bay DB .....................................................................................749
15.3.9.1 Identification.....................................................................................................................750
15.3.9.2 Functionality......................................................................................................................750
15.3.9.3 Logic diagrams.................................................................................................................. 751
15.3.9.4 Function block...................................................................................................................754
15.3.9.5 Signals.................................................................................................................................755
15.3.10 Interlocking for line bay ABC_LINE .................................................................................... 758
15.3.10.1 Identification..................................................................................................................... 758
15.3.10.2 Functionality......................................................................................................................758
15.3.10.3 Function block...................................................................................................................760
15.3.10.4 Logic diagram....................................................................................................................761
15.3.10.5 Signals.................................................................................................................................766
15.3.11 Interlocking for transformer bay AB_TRAFO ...................................................................768
15.3.11.1 Identification..................................................................................................................... 768
15.3.11.2 Functionality......................................................................................................................768
15.3.11.3 Function block...................................................................................................................769
15.3.11.4 Logic diagram................................................................................................................... 770
15.3.11.5 Signals................................................................................................................................. 771
15.3.12 Position evaluation POS_EVAL.............................................................................................773

18 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

15.3.12.1 Identification..................................................................................................................... 773


15.3.12.2 Functionality...................................................................................................................... 773
15.3.12.3 Function block................................................................................................................... 773
15.3.12.4 Logic diagram....................................................................................................................773
15.3.12.5 Signals.................................................................................................................................774
15.4 Apparatus control.................................................................................................................... 774
15.4.1 Functionality............................................................................................................................774
15.4.2 Operation principle................................................................................................................ 775
15.4.3 Error handling......................................................................................................................... 775
15.4.4 Bay control QCBAY.................................................................................................................778
15.4.4.1 Functionality...................................................................................................................... 778
15.4.4.2 Function block................................................................................................................... 779
15.4.4.3 Signals.................................................................................................................................779
15.4.4.4 Settings...............................................................................................................................779
15.4.4.5 Operation principle.......................................................................................................... 780
15.4.5 Local/Remote switch LOCREM............................................................................................781
15.4.5.1 Function block................................................................................................................... 782
15.4.5.2 Signals.................................................................................................................................782
15.4.5.3 Settings.............................................................................................................................. 783
15.4.5.4 Operation principle.......................................................................................................... 783
15.4.6 Switch controller SCSWI....................................................................................................... 784
15.4.6.1 Functionality .....................................................................................................................784
15.4.6.2 Function block...................................................................................................................785
15.4.6.3 Signals.................................................................................................................................785
15.4.6.4 Settings...............................................................................................................................787
15.4.6.5 Operation principle.......................................................................................................... 787
15.4.7 Circuit breaker SXCBR........................................................................................................... 792
15.4.7.1 Functionality ..................................................................................................................... 793
15.4.7.2 Function block................................................................................................................... 793
15.4.7.3 Signals.................................................................................................................................793
15.4.7.4 Settings.............................................................................................................................. 794
15.4.7.5 Operation principle.......................................................................................................... 794
15.4.8 Circuit switch SXSWI..............................................................................................................797
15.4.8.1 Functionality .....................................................................................................................798
15.4.8.2 Function block...................................................................................................................798
15.4.8.3 Signals................................................................................................................................ 798
15.4.8.4 Settings.............................................................................................................................. 799
15.4.8.5 Operation principle.......................................................................................................... 799
15.4.9 Proxy for signals from switching device via GOOSE XLNPROXY ................................ 803
15.4.9.1 Functionality..................................................................................................................... 803
15.4.9.2 Function block.................................................................................................................. 803
15.4.9.3 Signals................................................................................................................................ 804
15.4.9.4 Settings..............................................................................................................................805
15.4.9.5 Operation principle..........................................................................................................805
15.4.9.6 Position supervision........................................................................................................ 805
15.4.9.7 Command response evaluation.................................................................................... 805

Line distance protection REL670 19


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

15.4.10 Bay reserve QCRSV................................................................................................................ 807


15.4.10.1 Functionality......................................................................................................................807
15.4.10.2 Function block...................................................................................................................807
15.4.10.3 Signals................................................................................................................................ 807
15.4.10.4 Settings..............................................................................................................................808
15.4.10.5 Operation principle..........................................................................................................809
15.4.11 Reservation input RESIN....................................................................................................... 810
15.4.11.1 Functionality......................................................................................................................810
15.4.11.2 Function block...................................................................................................................810
15.4.11.3 Signals................................................................................................................................. 811
15.4.11.4 Settings...............................................................................................................................812
15.4.11.5 Operation principle...........................................................................................................812
15.5 Logic rotating switch for function selection and LHMI presentation SLGAPC............813
15.5.1 Identification...........................................................................................................................813
15.5.2 Functionality............................................................................................................................813
15.5.3 Function block........................................................................................................................ 814
15.5.4 Signals...................................................................................................................................... 814
15.5.5 Settings.................................................................................................................................... 815
15.5.6 Monitored data.......................................................................................................................816
15.5.7 Operation principle................................................................................................................816
15.5.7.1 Graphical display...............................................................................................................816
15.6 Selector mini switch VSGAPC................................................................................................. 817
15.6.1 Identification........................................................................................................................... 817
15.6.2 Functionality............................................................................................................................817
15.6.3 Function block........................................................................................................................ 818
15.6.4 Signals...................................................................................................................................... 818
15.6.5 Settings.................................................................................................................................... 818
15.6.6 Operation principle................................................................................................................819
15.7 Generic communication function for Double Point indication DPGAPC.......................819
15.7.1 Identification...........................................................................................................................819
15.7.2 Functionality........................................................................................................................... 820
15.7.3 Function block........................................................................................................................ 820
15.7.4 Signals......................................................................................................................................820
15.7.5 Settings....................................................................................................................................820
15.7.6 Operation principle............................................................................................................... 820
15.8 Single point generic control 8 signals SPC8GAPC............................................................. 821
15.8.1 Identification...........................................................................................................................821
15.8.2 Functionality............................................................................................................................821
15.8.3 Function block.........................................................................................................................821
15.8.4 Signals...................................................................................................................................... 822
15.8.5 Settings.................................................................................................................................... 822
15.8.6 Operation principle................................................................................................................823
15.9 AutomationBits, command function for DNP3.0 AUTOBITS........................................... 823
15.9.1 Identification...........................................................................................................................823
15.9.2 Functionality........................................................................................................................... 823
15.9.3 Function block........................................................................................................................ 824

20 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

15.9.4 Signals...................................................................................................................................... 824


15.9.5 Settings....................................................................................................................................825
15.9.6 Operation principle................................................................................................................825
15.10 Single command, 16 signals SINGLECMD............................................................................826
15.10.1 Identification.......................................................................................................................... 826
15.10.2 Functionality........................................................................................................................... 826
15.10.3 Function block........................................................................................................................ 826
15.10.4 Signals...................................................................................................................................... 826
15.10.5 Settings.................................................................................................................................... 827
15.10.6 Operation principle................................................................................................................827

Section 16 Scheme communication............................................................................ 829


16.1 Scheme communication logic for distance or overcurrent protection ZCPSCH........ 829
16.1.1 Identification.......................................................................................................................... 829
16.1.2 Functionality........................................................................................................................... 829
16.1.3 Function block........................................................................................................................ 829
16.1.4 Signals......................................................................................................................................830
16.1.5 Settings................................................................................................................................... 830
16.1.6 Operation principle................................................................................................................ 831
16.1.6.1 Blocking scheme............................................................................................................... 831
16.1.6.2 Delta blocking scheme.................................................................................................... 832
16.1.6.3 Permissive underreaching scheme............................................................................... 832
16.1.6.4 Permissive overreaching scheme..................................................................................833
16.1.6.5 Unblocking scheme.......................................................................................................... 833
16.1.6.6 Intertrip scheme............................................................................................................... 834
16.1.6.7 Simplified logic diagram.................................................................................................834
16.1.7 Technical data.........................................................................................................................835
16.2 Phase segregated scheme communication logic for distance protection
ZC1PPSCH ................................................................................................................................. 836
16.2.1 Identification.......................................................................................................................... 836
16.2.2 Functionality........................................................................................................................... 836
16.2.3 Function block........................................................................................................................ 837
16.2.4 Signals...................................................................................................................................... 837
16.2.5 Settings....................................................................................................................................838
16.2.6 Operation principle................................................................................................................838
16.2.6.1 Blocking scheme...............................................................................................................839
16.2.6.2 Permissive underreach scheme.....................................................................................839
16.2.6.3 Permissive overreach scheme....................................................................................... 840
16.2.6.4 Unblocking scheme......................................................................................................... 840
16.2.6.5 Intertrip scheme...............................................................................................................840
16.2.6.6 Simplified logic diagram................................................................................................ 840
16.2.7 Technical data.........................................................................................................................842
16.3 Current reversal and Weak-end infeed logic for distance protection 3-phase
ZCRWPSCH ............................................................................................................................... 842
16.3.1 Identification.......................................................................................................................... 842
16.3.2 Functionality........................................................................................................................... 842
16.3.3 Function block........................................................................................................................ 843

Line distance protection REL670 21


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

16.3.4 Signals......................................................................................................................................843
16.3.5 Settings................................................................................................................................... 844
16.3.6 Operation principle............................................................................................................... 844
16.3.6.1 Current reversal logic...................................................................................................... 844
16.3.6.2 Weak-end infeed logic..................................................................................................... 845
16.3.7 Technical data........................................................................................................................ 846
16.4 Current reversal and weak-end infeed logic for phase segregated
communication ZC1WPSCH .................................................................................................. 847
16.4.1 Identification.......................................................................................................................... 847
16.4.2 Functionality........................................................................................................................... 847
16.4.3 Function block........................................................................................................................ 847
16.4.4 Signals......................................................................................................................................848
16.4.5 Settings................................................................................................................................... 849
16.4.6 Operation principle............................................................................................................... 849
16.4.6.1 Current reversal logic ..................................................................................................... 849
16.4.6.2 Weak-end infeed logic.....................................................................................................850
16.4.7 Technical data........................................................................................................................ 854
16.5 Local acceleration logic ZCLCPSCH..................................................................................... 854
16.5.1 Identification.......................................................................................................................... 854
16.5.2 Functionality........................................................................................................................... 854
16.5.3 Function block........................................................................................................................ 854
16.5.4 Signals...................................................................................................................................... 855
16.5.5 Settings....................................................................................................................................855
16.5.6 Operation principle............................................................................................................... 856
16.5.6.1 Zone extension................................................................................................................. 856
16.5.6.2 Loss-of-Load acceleration..............................................................................................856
16.6 Scheme communication logic for residual overcurrent protection ECPSCH ..............857
16.6.1 Identification...........................................................................................................................857
16.6.2 Functionality........................................................................................................................... 857
16.6.3 Function block........................................................................................................................ 858
16.6.4 Signals......................................................................................................................................858
16.6.5 Settings....................................................................................................................................859
16.6.6 Operation principle............................................................................................................... 859
16.6.6.1 Blocking scheme...............................................................................................................859
16.6.6.2 Permissive under/overreaching scheme.....................................................................860
16.6.6.3 Unblocking scheme.......................................................................................................... 861
16.6.7 Technical data.........................................................................................................................862
16.7 Current reversal and weak-end infeed logic for residual overcurrent protection
ECRWPSCH................................................................................................................................ 862
16.7.1 Identification.......................................................................................................................... 862
16.7.2 Functionality........................................................................................................................... 863
16.7.3 Function block........................................................................................................................ 863
16.7.4 Signals...................................................................................................................................... 863
16.7.5 Settings................................................................................................................................... 864
16.7.6 Operation principle............................................................................................................... 864
16.7.6.1 Directional comparison logic function........................................................................ 864

22 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

16.7.6.2 Fault current reversal logic.............................................................................................865


16.7.6.3 Weak-end infeed logic..................................................................................................... 865
16.7.7 Technical data.........................................................................................................................867
16.8 Direct transfer trip logic......................................................................................................... 867
16.8.1 Introduction............................................................................................................................ 867
16.8.2 Low active power and power factor protection LAPPGAPC......................................... 868
16.8.2.1 Identification.....................................................................................................................868
16.8.2.2 Functionality..................................................................................................................... 869
16.8.2.3 Function block.................................................................................................................. 869
16.8.2.4 Signals................................................................................................................................ 869
16.8.2.5 Settings.............................................................................................................................. 870
16.8.2.6 Monitored data..................................................................................................................871
16.8.2.7 Operation principle...........................................................................................................871
16.8.2.8 Technical data................................................................................................................... 873
16.8.3 Compensated over and undervoltage protection COUVGAPC..................................... 873
16.8.3.1 Identification..................................................................................................................... 873
16.8.3.2 Functionality...................................................................................................................... 873
16.8.3.3 Function block...................................................................................................................874
16.8.3.4 Signals................................................................................................................................ 874
16.8.3.5 Settings.............................................................................................................................. 875
16.8.3.6 Monitored data................................................................................................................. 876
16.8.3.7 Operation principle.......................................................................................................... 876
16.8.3.8 Technical data................................................................................................................... 877
16.8.4 Sudden change in current variation SCCVPTOC..............................................................878
16.8.4.1 Identification..................................................................................................................... 878
16.8.4.2 Functionality......................................................................................................................878
16.8.4.3 Function block...................................................................................................................878
16.8.4.4 Signals................................................................................................................................ 878
16.8.4.5 Settings.............................................................................................................................. 879
16.8.4.6 Operation principle.......................................................................................................... 879
16.8.4.7 Technical data...................................................................................................................880
16.8.5 Carrier receive logic LCCRPTRC.......................................................................................... 880
16.8.5.1 Identification.................................................................................................................... 880
16.8.5.2 Functionality..................................................................................................................... 880
16.8.5.3 Function block................................................................................................................... 881
16.8.5.4 Signals.................................................................................................................................881
16.8.5.5 Settings.............................................................................................................................. 881
16.8.5.6 Operation principle.......................................................................................................... 882
16.8.5.7 Technical data................................................................................................................... 882
16.8.6 Negative sequence overvoltage protection LCNSPTOV................................................ 882
16.8.6.1 Identification.....................................................................................................................882
16.8.6.2 Functionality......................................................................................................................882
16.8.6.3 Function block...................................................................................................................882
16.8.6.4 Signals................................................................................................................................ 883
16.8.6.5 Settings.............................................................................................................................. 883
16.8.6.6 Monitored data................................................................................................................. 883

Line distance protection REL670 23


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

16.8.6.7 Operation principle.......................................................................................................... 883


16.8.6.8 Technical data...................................................................................................................884
16.8.7 Zero sequence overvoltage protection LCZSPTOV........................................................ 884
16.8.7.1 Identification.....................................................................................................................884
16.8.7.2 Functionality..................................................................................................................... 884
16.8.7.3 Function block.................................................................................................................. 884
16.8.7.4 Signals................................................................................................................................ 885
16.8.7.5 Settings.............................................................................................................................. 885
16.8.7.6 Monitored data................................................................................................................. 885
16.8.7.7 Operation principle.......................................................................................................... 885
16.8.7.8 Technical data...................................................................................................................886
16.8.8 Negative sequence overcurrent protection LCNSPTOC................................................ 886
16.8.8.1 Identification.....................................................................................................................886
16.8.8.2 Functionality..................................................................................................................... 886
16.8.8.3 Function block.................................................................................................................. 886
16.8.8.4 Signals................................................................................................................................ 887
16.8.8.5 Settings.............................................................................................................................. 887
16.8.8.6 Monitored data................................................................................................................. 887
16.8.8.7 Operation principle.......................................................................................................... 887
16.8.8.8 Technical data...................................................................................................................888
16.8.9 Zero sequence overcurrent protection LCZSPTOC........................................................ 888
16.8.9.1 Identification.....................................................................................................................888
16.8.9.2 Functionality..................................................................................................................... 888
16.8.9.3 Function block.................................................................................................................. 889
16.8.9.4 Signals................................................................................................................................ 889
16.8.9.5 Settings.............................................................................................................................. 889
16.8.9.6 Monitored data.................................................................................................................889
16.8.9.7 Operation principle..........................................................................................................890
16.8.9.8 Technical data...................................................................................................................890
16.8.10 Three phase overcurrent LCP3PTOC................................................................................. 890
16.8.10.1 Identification.................................................................................................................... 890
16.8.10.2 Functionality..................................................................................................................... 890
16.8.10.3 Function block................................................................................................................... 891
16.8.10.4 Signals.................................................................................................................................891
16.8.10.5 Settings.............................................................................................................................. 892
16.8.10.6 Monitored data................................................................................................................. 892
16.8.10.7 Operation principle.......................................................................................................... 892
16.8.10.8 Technical data................................................................................................................... 892
16.8.11 Three phase undercurrent LCP3PTUC............................................................................... 893
16.8.11.1 Identification.....................................................................................................................893
16.8.11.2 Functionality......................................................................................................................893
16.8.11.3 Function block...................................................................................................................893
16.8.11.4 Signals................................................................................................................................ 894
16.8.11.5 Settings.............................................................................................................................. 894
16.8.11.6 Monitored data.................................................................................................................894
16.8.11.7 Operation principle.......................................................................................................... 895

24 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

16.8.11.8 Technical data................................................................................................................... 895

Section 17 Logic.............................................................................................................897
17.1 Tripping logic SMPPTRC ........................................................................................................ 897
17.1.1 Identification.......................................................................................................................... 897
17.1.2 Functionality........................................................................................................................... 897
17.1.3 Function block........................................................................................................................ 897
17.1.4 Signals......................................................................................................................................898
17.1.5 Settings................................................................................................................................... 899
17.1.6 Operation principle............................................................................................................... 899
17.1.6.1 Logic diagram................................................................................................................... 902
17.1.7 Technical data........................................................................................................................ 905
17.2 General start matrix block SMAGAPC.................................................................................. 905
17.2.1 Identification.......................................................................................................................... 905
17.2.2 Functionality........................................................................................................................... 905
17.2.3 Function block........................................................................................................................ 905
17.2.4 Signals......................................................................................................................................906
17.2.5 Settings................................................................................................................................... 906
17.2.6 Operation principle............................................................................................................... 906
17.3 Trip matrix logic TMAGAPC.....................................................................................................911
17.3.1 Identification........................................................................................................................... 911
17.3.2 Functionality............................................................................................................................912
17.3.3 Function block.........................................................................................................................912
17.3.4 Signals...................................................................................................................................... 912
17.3.5 Settings.................................................................................................................................... 914
17.3.6 Operation principle................................................................................................................914
17.3.7 Technical data......................................................................................................................... 915
17.4 Logic for group alarm ALMCALH...........................................................................................915
17.4.1 Identification...........................................................................................................................915
17.4.2 Functionality............................................................................................................................915
17.4.3 Function block........................................................................................................................ 916
17.4.4 Signals...................................................................................................................................... 916
17.4.5 Settings.................................................................................................................................... 917
17.4.6 Operation principle................................................................................................................ 917
17.4.7 Technical data......................................................................................................................... 917
17.5 Logic for group warning WRNCALH......................................................................................917
17.5.1 Identification........................................................................................................................... 917
17.5.2 Functionality............................................................................................................................917
17.5.3 Function block........................................................................................................................ 918
17.5.4 Signals...................................................................................................................................... 918
17.5.5 Settings.................................................................................................................................... 919
17.5.6 Operation principle................................................................................................................919
17.5.7 Technical data.........................................................................................................................919
17.6 Logic for group indication INDCALH.................................................................................... 919
17.6.1 Identification...........................................................................................................................919
17.6.2 Functionality........................................................................................................................... 919

Line distance protection REL670 25


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

17.6.3 Function block........................................................................................................................ 920


17.6.4 Signals......................................................................................................................................920
17.6.5 Settings.................................................................................................................................... 921
17.6.6 Operation principle................................................................................................................ 921
17.6.7 Technical data......................................................................................................................... 921
17.7 Basic configurable logic blocks............................................................................................. 921
17.7.1 AND function block AND....................................................................................................... 922
17.7.1.1 Function block...................................................................................................................922
17.7.1.2 Signals.................................................................................................................................923
17.7.1.3 Technical data................................................................................................................... 923
17.7.2 Controllable gate function block GATE............................................................................. 923
17.7.2.1 Function block...................................................................................................................923
17.7.2.2 Signals.................................................................................................................................923
17.7.2.3 Settings.............................................................................................................................. 924
17.7.2.4 Technical data................................................................................................................... 924
17.7.3 Inverter function block INV.................................................................................................. 924
17.7.3.1 Function block...................................................................................................................924
17.7.3.2 Signals................................................................................................................................ 924
17.7.3.3 Technical data................................................................................................................... 925
17.7.4 Loop delay function block LLD............................................................................................ 925
17.7.4.1 Function block...................................................................................................................925
17.7.4.2 Signals.................................................................................................................................925
17.7.4.3 Technical data................................................................................................................... 925
17.7.5 OR function block...................................................................................................................925
17.7.5.1 Function block...................................................................................................................926
17.7.5.2 Signals................................................................................................................................ 926
17.7.5.3 Technical data................................................................................................................... 926
17.7.6 Pulse timer function block PULSETIMER...........................................................................926
17.7.6.1 Function block................................................................................................................... 927
17.7.6.2 Signals.................................................................................................................................927
17.7.6.3 Settings.............................................................................................................................. 927
17.7.6.4 Technical data................................................................................................................... 927
17.7.7 Reset-set with memory function block RSMEMORY....................................................... 927
17.7.7.1 Function block...................................................................................................................928
17.7.7.2 Signals................................................................................................................................ 928
17.7.7.3 Settings.............................................................................................................................. 928
17.7.7.4 Technical data................................................................................................................... 928
17.7.8 Set-reset with memory function block SRMEMORY....................................................... 929
17.7.8.1 Function block...................................................................................................................929
17.7.8.2 Signals................................................................................................................................ 929
17.7.8.3 Settings.............................................................................................................................. 929
17.7.8.4 Technical data...................................................................................................................930
17.7.9 Settable timer function block TIMERSET.......................................................................... 930
17.7.9.1 Function block.................................................................................................................. 930
17.7.9.2 Signals................................................................................................................................ 930
17.7.9.3 Settings...............................................................................................................................931

26 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

17.7.9.4 Technical data....................................................................................................................931


17.7.10 Exclusive OR function block XOR........................................................................................ 931
17.7.10.1 Function block................................................................................................................... 931
17.7.10.2 Signals.................................................................................................................................932
17.7.10.3 Technical data................................................................................................................... 932
17.8 Configurable logic blocks Q/T...............................................................................................932
17.8.1 ANDQT function block...........................................................................................................933
17.8.1.1 Function block...................................................................................................................933
17.8.1.2 Signals.................................................................................................................................933
17.8.1.3 Technical data................................................................................................................... 934
17.8.2 Single point indication related signals combining function block INDCOMBSPQT.934
17.8.2.1 Function block...................................................................................................................934
17.8.2.2 Signals................................................................................................................................ 934
17.8.2.3 Technical data................................................................................................................... 935
17.8.3 Single point input signal attributes converting function block INDEXTSPQT.......... 935
17.8.3.1 Function block...................................................................................................................935
17.8.3.2 Signals................................................................................................................................ 935
17.8.3.3 Technical data................................................................................................................... 936
17.8.4 Invalid logic function block INVALIDQT............................................................................. 936
17.8.4.1 Function block...................................................................................................................936
17.8.4.2 Signals.................................................................................................................................937
17.8.4.3 Technical data................................................................................................................... 938
17.8.5 Inverter function block INVERTERQT................................................................................. 938
17.8.5.1 Function block...................................................................................................................938
17.8.5.2 Signals................................................................................................................................ 938
17.8.5.3 Technical data................................................................................................................... 938
17.8.6 ORQT function block............................................................................................................. 938
17.8.6.1 Function block...................................................................................................................939
17.8.6.2 Signals................................................................................................................................ 939
17.8.6.3 Technical data................................................................................................................... 939
17.8.7 Pulse timer function block PULSETIMERQT..................................................................... 939
17.8.7.1 Function block.................................................................................................................. 940
17.8.7.2 Signals................................................................................................................................ 940
17.8.7.3 Settings..............................................................................................................................940
17.8.7.4 Technical data...................................................................................................................940
17.8.8 Reset/Set function block RSMEMORYQT..........................................................................941
17.8.8.1 Function block................................................................................................................... 941
17.8.8.2 Signals.................................................................................................................................941
17.8.8.3 Settings.............................................................................................................................. 942
17.8.8.4 Technical data................................................................................................................... 942
17.8.9 Set/Reset function block SRMEMORYQT......................................................................... 942
17.8.9.1 Function block...................................................................................................................942
17.8.9.2 Signals................................................................................................................................ 942
17.8.9.3 Settings.............................................................................................................................. 943
17.8.9.4 Technical data................................................................................................................... 943
17.8.10 Settable timer function block TIMERSETQT.....................................................................943

Line distance protection REL670 27


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

17.8.10.1 Function block...................................................................................................................943


17.8.10.2 Signals................................................................................................................................ 944
17.8.10.3 Settings..............................................................................................................................944
17.8.10.4 Technical data...................................................................................................................944
17.8.11 Exclusive OR function block XORQT.................................................................................. 944
17.8.11.1 Function block.................................................................................................................. 945
17.8.11.2 Signals................................................................................................................................ 945
17.8.11.3 Technical data...................................................................................................................945
17.9 Extension logic package.........................................................................................................945
17.10 Fixed signals FXDSIGN............................................................................................................946
17.10.1 Identification.......................................................................................................................... 946
17.10.2 Functionality........................................................................................................................... 946
17.10.3 Function block........................................................................................................................ 946
17.10.4 Signals...................................................................................................................................... 947
17.10.5 Settings....................................................................................................................................947
17.10.6 Operation principle................................................................................................................947
17.11 Boolean 16 to Integer conversion B16I.................................................................................947
17.11.1 Identification.......................................................................................................................... 947
17.11.2 Functionality........................................................................................................................... 947
17.11.3 Function block........................................................................................................................ 948
17.11.4 Signals......................................................................................................................................948
17.11.5 Monitored data...................................................................................................................... 949
17.11.6 Settings................................................................................................................................... 949
17.11.7 Operation principle............................................................................................................... 949
17.11.8 Technical data........................................................................................................................ 950
17.12 Boolean to integer conversion with logical node representation, 16 bit BTIGAPC.... 950
17.12.1 Identification.......................................................................................................................... 950
17.12.2 Functionality........................................................................................................................... 950
17.12.3 Function block........................................................................................................................ 950
17.12.4 Signals...................................................................................................................................... 951
17.12.5 Settings.................................................................................................................................... 951
17.12.6 Monitored data....................................................................................................................... 951
17.12.7 Operation principle................................................................................................................ 951
17.12.8 Technical data.........................................................................................................................952
17.13 Integer to boolean 16 conversion IB16.................................................................................952
17.13.1 Identification.......................................................................................................................... 952
17.13.2 Functionality........................................................................................................................... 953
17.13.3 Function block........................................................................................................................ 953
17.13.4 Signals...................................................................................................................................... 953
17.13.5 Setting parameters............................................................................................................... 954
17.13.6 Operation principle............................................................................................................... 954
17.13.7 Technical data.........................................................................................................................955
17.14 Integer to Boolean 16 conversion with logic node representation ITBGAPC...............955
17.14.1 Identification.......................................................................................................................... 955
17.14.2 Functionality........................................................................................................................... 955
17.14.3 Function block........................................................................................................................ 956

28 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

17.14.4 Signals......................................................................................................................................956
17.14.5 Settings....................................................................................................................................957
17.14.6 Operation principle................................................................................................................957
17.14.7 Technical data........................................................................................................................ 958
17.15 Elapsed time integrator with limit transgression and overflow supervision
TEIGAPC..................................................................................................................................... 958
17.15.1 Identification.......................................................................................................................... 958
17.15.2 Functionality........................................................................................................................... 958
17.15.3 Function block........................................................................................................................ 959
17.15.4 Signals......................................................................................................................................959
17.15.5 Settings....................................................................................................................................959
17.15.6 Operation principle............................................................................................................... 960
17.15.6.1 Operation accuracy.......................................................................................................... 961
17.15.6.2 Memory storage................................................................................................................961
17.15.7 Technical data.........................................................................................................................961
17.16 Comparator for integer inputs INTCOMP........................................................................... 961
17.16.1 Identification...........................................................................................................................961
17.16.2 Functionality........................................................................................................................... 962
17.16.3 Function block........................................................................................................................ 962
17.16.4 Signals...................................................................................................................................... 962
17.16.5 Settings....................................................................................................................................962
17.16.6 Monitored data.......................................................................................................................963
17.16.7 Operation principle................................................................................................................963
17.16.8 Technical data........................................................................................................................ 964
17.17 Comparator for real inputs REALCOMP.............................................................................. 964
17.17.1 Identification.......................................................................................................................... 964
17.17.2 Functionality........................................................................................................................... 964
17.17.3 Function block........................................................................................................................ 964
17.17.4 Signals......................................................................................................................................964
17.17.5 Settings....................................................................................................................................965
17.17.6 Operation principle............................................................................................................... 965
17.17.7 Technical data.........................................................................................................................967

Section 18 Monitoring.................................................................................................. 969


18.1 Measurements.......................................................................................................................... 969
18.1.1 Identification.......................................................................................................................... 969
18.1.2 Functionality........................................................................................................................... 969
18.1.3 Function block........................................................................................................................ 970
18.1.4 Signals...................................................................................................................................... 972
18.1.5 Settings....................................................................................................................................975
18.1.6 Monitored data...................................................................................................................... 986
18.1.7 Operation principle............................................................................................................... 988
18.1.7.1 Measurement supervision.............................................................................................. 988
18.1.7.2 Measurements CVMMXN................................................................................................ 993
18.1.7.3 Phase current measurement CMMXU.......................................................................... 998
18.1.7.4 Phase-phase and phase-neutral voltage measurements VMMXU, VNMMXU...... 998
18.1.7.5 Voltage and current sequence measurements VMSQI, CMSQI...............................998

Line distance protection REL670 29


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

18.1.8 Technical data........................................................................................................................ 998


18.2 Gas medium supervision SSIMG......................................................................................... 1000
18.2.1 Identification........................................................................................................................ 1000
18.2.2 Functionality.........................................................................................................................1000
18.2.3 Function block......................................................................................................................1000
18.2.4 Signals.................................................................................................................................... 1001
18.2.5 Settings.................................................................................................................................. 1001
18.2.6 Monitored data.....................................................................................................................1002
18.2.7 Operation principle..............................................................................................................1002
18.2.8 Technical data...................................................................................................................... 1003
18.3 Liquid medium supervision SSIML..................................................................................... 1003
18.3.1 Identification........................................................................................................................ 1003
18.3.2 Functionality......................................................................................................................... 1003
18.3.3 Function block......................................................................................................................1004
18.3.4 Signals....................................................................................................................................1004
18.3.5 Settings................................................................................................................................. 1005
18.3.6 Monitored data.................................................................................................................... 1005
18.3.7 Operation principle............................................................................................................. 1005
18.3.8 Technical data...................................................................................................................... 1006
18.4 Breaker monitoring SSCBR.................................................................................................. 1006
18.4.1 Identification........................................................................................................................ 1006
18.4.2 Functionality......................................................................................................................... 1007
18.4.3 Function block...................................................................................................................... 1007
18.4.4 Signals.................................................................................................................................... 1007
18.4.5 Settings................................................................................................................................. 1008
18.4.6 Monitored data.................................................................................................................... 1009
18.4.7 Operation principle..............................................................................................................1010
18.4.7.1 Circuit breaker contact travel time............................................................................. 1012
18.4.7.2 Circuit breaker status.................................................................................................... 1013
18.4.7.3 Remaining life of circuit breaker..................................................................................1013
18.4.7.4 Accumulated energy.......................................................................................................1014
18.4.7.5 Circuit breaker operation cycles.................................................................................. 1015
18.4.7.6 Circuit breaker operation monitoring........................................................................ 1016
18.4.7.7 Circuit breaker spring charge monitoring................................................................. 1017
18.4.7.8 Circuit breaker gas pressure indication..................................................................... 1017
18.4.8 Technical data....................................................................................................................... 1018
18.5 Event function EVENT............................................................................................................1018
18.5.1 Identification.........................................................................................................................1018
18.5.2 Functionality..........................................................................................................................1019
18.5.3 Function block.......................................................................................................................1019
18.5.4 Signals.................................................................................................................................... 1019
18.5.5 Settings..................................................................................................................................1020
18.5.6 Operation principle..............................................................................................................1022
18.6 Disturbance report DRPRDRE.............................................................................................. 1023
18.6.1 Identification.........................................................................................................................1023
18.6.2 Functionality......................................................................................................................... 1023

30 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

18.6.3 Function block...................................................................................................................... 1024


18.6.4 Signals.................................................................................................................................... 1025
18.6.5 Settings..................................................................................................................................1026
18.6.6 Monitored data.....................................................................................................................1032
18.6.7 Operation principle..............................................................................................................1035
18.6.8 Technical data.......................................................................................................................1042
18.7 Logical signal status report BINSTATREP......................................................................... 1042
18.7.1 Identification........................................................................................................................ 1042
18.7.2 Functionality......................................................................................................................... 1042
18.7.3 Function block...................................................................................................................... 1043
18.7.4 Signals.................................................................................................................................... 1043
18.7.5 Settings................................................................................................................................. 1044
18.7.6 Operation principle............................................................................................................. 1044
18.8 Measured value expander block RANGE_XP..................................................................... 1045
18.8.1 Identification........................................................................................................................ 1045
18.8.2 Functionality......................................................................................................................... 1045
18.8.3 Function block...................................................................................................................... 1045
18.8.4 Signals....................................................................................................................................1045
18.8.5 Operation principle............................................................................................................. 1046
18.9 Fault locator LMBRFLO......................................................................................................... 1046
18.9.1 Identification........................................................................................................................ 1046
18.9.2 Functionality......................................................................................................................... 1046
18.9.3 Function block...................................................................................................................... 1047
18.9.4 Signals.................................................................................................................................... 1047
18.9.5 Settings................................................................................................................................. 1048
18.9.6 Monitored data.................................................................................................................... 1049
18.9.7 Operation principle............................................................................................................. 1049
18.9.7.1 Measuring Principle....................................................................................................... 1050
18.9.7.2 Accurate algorithm for measurement of distance to fault................................... 1050
18.9.7.3 The non-compensated impedance model.................................................................1053
18.9.7.4 IEC 60870-5-103.............................................................................................................. 1053
18.9.8 Technical data...................................................................................................................... 1054
18.10 Limit counter L4UFCNT........................................................................................................ 1054
18.10.1 Identification........................................................................................................................ 1054
18.10.2 Functionality......................................................................................................................... 1054
18.10.3 Operation principle............................................................................................................. 1054
18.10.3.1 Design...............................................................................................................................1054
18.10.3.2 Reporting......................................................................................................................... 1056
18.10.4 Function block...................................................................................................................... 1056
18.10.5 Signals....................................................................................................................................1056
18.10.6 Settings.................................................................................................................................. 1057
18.10.7 Monitored data.....................................................................................................................1057
18.10.8 Technical data.......................................................................................................................1057
18.11 Running hour-meter TEILGAPC ...........................................................................................1057
18.11.1 Identification.........................................................................................................................1057
18.11.2 Functionality......................................................................................................................... 1058

Line distance protection REL670 31


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

18.11.3 Function block...................................................................................................................... 1058


18.11.4 Signals.................................................................................................................................... 1059
18.11.5 Settings..................................................................................................................................1059
18.11.6 Operation principle..............................................................................................................1059
18.11.6.1 Operation accuracy........................................................................................................ 1061
18.11.6.2 Memory storage..............................................................................................................1061
18.11.7 Technical data....................................................................................................................... 1061
18.12 Through fault monitoring PTRSTHR .................................................................................. 1061
18.12.1 Identification.........................................................................................................................1061
18.12.2 Functionality......................................................................................................................... 1062
18.12.3 Function block...................................................................................................................... 1062
18.12.4 Signals.................................................................................................................................... 1062
18.12.5 Settings..................................................................................................................................1063
18.12.6 Monitored data.................................................................................................................... 1066
18.12.7 Operation principle..............................................................................................................1067
18.12.7.1 Transformer winding currents calculation................................................................1068
18.12.7.2 Through fault detection................................................................................................1069
18.12.7.3 Through fault duration and count of occurrence calculation............................... 1070
18.12.7.4 Through fault withstand capability calculation........................................................1071
18.12.7.5 Preparation of data for reporting............................................................................... 1072
18.12.8 Technical data.......................................................................................................................1075
18.13 Current harmonic monitoring CHMMHAI.......................................................................... 1076
18.13.1 Identification.........................................................................................................................1076
18.13.2 Functionality......................................................................................................................... 1076
18.13.3 Function block...................................................................................................................... 1076
18.13.4 Signals.................................................................................................................................... 1077
18.13.5 Settings.................................................................................................................................. 1077
18.13.6 Monitored data.....................................................................................................................1078
18.13.7 Graphical display configurable data................................................................................ 1079
18.13.8 Operation principle............................................................................................................. 1080
18.13.8.1 Total harmonic distortion (THD).................................................................................1082
18.13.8.2 Individual harmonic distortion (IHD)..........................................................................1082
18.13.8.3 Total demand distortion (TDD)................................................................................... 1083
18.13.8.4 Crest factor (CF)............................................................................................................. 1083
18.13.8.5 Blocking and alarm logic............................................................................................... 1083
18.13.9 Technical data...................................................................................................................... 1084
18.14 Voltage harmonic monitoring VHMMHAI..........................................................................1085
18.14.1 Identification........................................................................................................................ 1085
18.14.2 Functionality......................................................................................................................... 1085
18.14.3 Function block...................................................................................................................... 1086
18.14.4 Signals....................................................................................................................................1086
18.14.5 Settings..................................................................................................................................1087
18.14.6 Monitored data.................................................................................................................... 1088
18.14.7 Graphical display configurable data................................................................................ 1089
18.14.8 Operation principle............................................................................................................. 1090
18.14.8.1 Total harmonic distortion (THD).................................................................................1092

32 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

18.14.8.2 Individual harmonic distortion (IHD)..........................................................................1092


18.14.8.3 Crest factor (CF)............................................................................................................. 1093
18.14.8.4 Blocking and alarm logic............................................................................................... 1093
18.14.9 Technical data...................................................................................................................... 1094

Section 19 Metering.................................................................................................... 1095


19.1 Pulse-counter logic PCFCNT................................................................................................ 1095
19.1.1 Identification........................................................................................................................ 1095
19.1.2 Functionality......................................................................................................................... 1095
19.1.3 Function block...................................................................................................................... 1095
19.1.4 Signals.................................................................................................................................... 1095
19.1.5 Settings..................................................................................................................................1096
19.1.6 Monitored data.................................................................................................................... 1096
19.1.7 Operation principle............................................................................................................. 1096
19.1.8 Technical data...................................................................................................................... 1098
19.2 Function for energy calculation and demand handling ETPMMTR.............................. 1098
19.2.1 Identification........................................................................................................................ 1098
19.2.2 Functionality......................................................................................................................... 1099
19.2.3 Function block...................................................................................................................... 1099
19.2.4 Signals....................................................................................................................................1099
19.2.5 Settings.................................................................................................................................. 1100
19.2.6 Monitored data..................................................................................................................... 1101
19.2.7 Operation principle.............................................................................................................. 1102
19.2.8 Technical data.......................................................................................................................1104

Section 20 Ethernet..................................................................................................... 1105


20.1 Access point............................................................................................................................ 1105
20.1.1 Introduction...........................................................................................................................1105
20.1.2 Settings.................................................................................................................................. 1105
20.2 Access point diagnostics...................................................................................................... 1107
20.2.1 Functionality..........................................................................................................................1107
20.2.2 Function block.......................................................................................................................1107
20.2.3 Signals.....................................................................................................................................1107
20.2.4 Monitored data..................................................................................................................... 1108
20.3 Redundant communication.................................................................................................. 1108
20.3.1 Identification.........................................................................................................................1108
20.3.2 Functionality..........................................................................................................................1108
20.3.3 Operation principle.............................................................................................................. 1109
20.4 Merging unit.............................................................................................................................1110
20.4.1 Introduction........................................................................................................................... 1110
20.4.2 Settings...................................................................................................................................1110
20.4.3 Monitored data...................................................................................................................... 1111
20.5 Routes........................................................................................................................................1116
20.5.1 Introduction........................................................................................................................... 1116
20.5.2 Settings...................................................................................................................................1116
20.5.3 Monitored data......................................................................................................................1116

Line distance protection REL670 33


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

Section 21 Station communication............................................................................1117


21.1 Communication protocols.....................................................................................................1117
21.2 Communication protocol diagnostics................................................................................ 1117
21.3 DNP3 protocol..........................................................................................................................1118
21.4 IEC 61850-8-1 communication protocol............................................................................. 1118
21.4.1 Functionality.......................................................................................................................... 1118
21.4.2 Communication interfaces and protocols.......................................................................1119
21.4.3 Settings...................................................................................................................................1119
21.4.4 Technical data........................................................................................................................1119
21.4.5 Generic communication function for Single Point indication SPGAPC, SP16GAPC 1120
21.4.5.1 Functionality.................................................................................................................... 1120
21.4.5.2 Function block................................................................................................................. 1120
21.4.5.3 Signals................................................................................................................................1121
21.4.5.4 Settings............................................................................................................................. 1121
21.4.5.5 Monitored data................................................................................................................ 1121
21.4.5.6 Operation principle......................................................................................................... 1122
21.4.6 Generic communication function for Measured Value MVGAPC.................................1122
21.4.6.1 Functionality.....................................................................................................................1123
21.4.6.2 Function block..................................................................................................................1123
21.4.6.3 Signals............................................................................................................................... 1123
21.4.6.4 Settings............................................................................................................................. 1123
21.4.6.5 Monitored data................................................................................................................1124
21.4.6.6 Operation principle.........................................................................................................1124
21.4.7 GOOSE function block to receive a double point value GOOSEDPRCV..................... 1124
21.4.7.1 Identification....................................................................................................................1124
21.4.7.2 Functionality.................................................................................................................... 1124
21.4.7.3 Function block................................................................................................................. 1125
21.4.7.4 Signals............................................................................................................................... 1125
21.4.7.5 Settings............................................................................................................................. 1125
21.4.7.6 Operation principle ........................................................................................................ 1125
21.4.8 GOOSE function block to receive an integer value GOOSEINTRCV............................ 1126
21.4.8.1 Identification....................................................................................................................1126
21.4.8.2 Functionality.................................................................................................................... 1126
21.4.8.3 Function block..................................................................................................................1127
21.4.8.4 Signals............................................................................................................................... 1127
21.4.8.5 Settings............................................................................................................................. 1127
21.4.8.6 Operation principle ........................................................................................................ 1127
21.4.9 GOOSE function block to receive a measurand value GOOSEMVRCV....................... 1128
21.4.9.1 Identification....................................................................................................................1128
21.4.9.2 Functionality.................................................................................................................... 1128
21.4.9.3 Function block................................................................................................................. 1129
21.4.9.4 Signals............................................................................................................................... 1129
21.4.9.5 Settings.............................................................................................................................1129
21.4.9.6 Operation principle ........................................................................................................1129
21.4.10 GOOSE function block to receive a single point value GOOSESPRCV....................... 1130

34 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

21.4.10.1 Identification................................................................................................................... 1130


21.4.10.2 Functionality.................................................................................................................... 1130
21.4.10.3 Function block..................................................................................................................1131
21.4.10.4 Signals................................................................................................................................1131
21.4.10.5 Settings............................................................................................................................. 1131
21.4.10.6 Operation principle ........................................................................................................ 1131
21.4.11 Horizontal communication via GOOSE for interlocking GOOSEINTLKRCV.............. 1132
21.4.11.1 Functionality.....................................................................................................................1132
21.4.11.2 Function block..................................................................................................................1133
21.4.11.3 Signals............................................................................................................................... 1133
21.4.11.4 Settings............................................................................................................................. 1135
21.4.11.5 Operation principle.........................................................................................................1135
21.4.12 GOOSE binary receive GOOSEBINRCV.............................................................................. 1137
21.4.12.1 Function block..................................................................................................................1137
21.4.12.2 Signals............................................................................................................................... 1137
21.4.12.3 Settings.............................................................................................................................1139
21.4.12.4 Operation principle.........................................................................................................1139
21.4.13 GOOSE function block to receive a switching device GOOSEXLNRCV ..................... 1140
21.4.13.1 Identification................................................................................................................... 1140
21.4.13.2 Functionality.................................................................................................................... 1140
21.4.13.3 Function block................................................................................................................. 1140
21.4.13.4 Signals............................................................................................................................... 1141
21.4.13.5 Settings.............................................................................................................................1142
21.4.13.6 Operation principle.........................................................................................................1142
21.5 IEC/UCA 61850-9-2LE communication protocol.............................................................. 1143
21.5.1 Introduction...........................................................................................................................1143
21.5.2 Function block.......................................................................................................................1143
21.5.3 Signals.....................................................................................................................................1143
21.5.3.1 Output signals................................................................................................................. 1143
21.5.4 Settings.................................................................................................................................. 1144
21.5.5 Monitored data..................................................................................................................... 1144
21.5.6 Operation principle.............................................................................................................. 1149
21.5.6.1 Conditional blocking...................................................................................................... 1152
21.5.6.2 IEC 61850 quality expander QUALEXP........................................................................ 1156
21.5.7 Technical data....................................................................................................................... 1157
21.6 LON communication protocol..............................................................................................1157
21.6.1 Functionality.......................................................................................................................... 1157
21.6.2 Settings.................................................................................................................................. 1158
21.6.3 Operation principle.............................................................................................................. 1158
21.6.4 Technical data....................................................................................................................... 1174
21.7 SPA communication protocol...............................................................................................1175
21.7.1 Functionality.......................................................................................................................... 1175
21.7.2 Design..................................................................................................................................... 1175
21.7.3 Settings...................................................................................................................................1175
21.7.4 Operation principle.............................................................................................................. 1176
21.7.4.1 Communication ports.................................................................................................... 1183

Line distance protection REL670 35


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

21.7.5 Technical data....................................................................................................................... 1183


21.8 IEC 60870-5-103 communication protocol........................................................................1184
21.8.1 Introduction...........................................................................................................................1184
21.8.2 Measurands for IEC 60870-5-103 I103MEAS................................................................... 1184
21.8.2.1 Functionality.................................................................................................................... 1184
21.8.2.2 Identification................................................................................................................... 1184
21.8.2.3 Function block................................................................................................................. 1185
21.8.2.4 Signals............................................................................................................................... 1185
21.8.2.5 Settings.............................................................................................................................1185
21.8.3 Measurands user defined signals for IEC 60870-5-103 I103MEASUSR...................... 1186
21.8.3.1 Functionality.................................................................................................................... 1186
21.8.3.2 Identification................................................................................................................... 1186
21.8.3.3 Function block................................................................................................................. 1186
21.8.3.4 Signals............................................................................................................................... 1186
21.8.3.5 Settings............................................................................................................................. 1187
21.8.4 Function status auto-recloser for IEC 60870-5-103 I103AR......................................... 1187
21.8.4.1 Functionality.................................................................................................................... 1187
21.8.4.2 Identification................................................................................................................... 1188
21.8.4.3 Function block................................................................................................................. 1188
21.8.4.4 Signals............................................................................................................................... 1188
21.8.4.5 Settings.............................................................................................................................1188
21.8.5 Function status earth-fault for IEC 60870-5-103 I103EF.............................................. 1188
21.8.5.1 Functionality.................................................................................................................... 1188
21.8.5.2 Identification................................................................................................................... 1188
21.8.5.3 Function block................................................................................................................. 1189
21.8.5.4 Signals............................................................................................................................... 1189
21.8.5.5 Settings.............................................................................................................................1189
21.8.6 Function status fault protection for IEC 60870-5-103 I103FLTPROT........................ 1189
21.8.6.1 Functionality.................................................................................................................... 1189
21.8.6.2 Identification................................................................................................................... 1189
21.8.6.3 Function block................................................................................................................. 1190
21.8.6.4 Signals...............................................................................................................................1190
21.8.6.5 Settings............................................................................................................................. 1191
21.8.7 IED status for IEC 60870-5-103 I103IED............................................................................1191
21.8.7.1 Functionality.....................................................................................................................1191
21.8.7.2 Identification....................................................................................................................1191
21.8.7.3 Function block................................................................................................................. 1192
21.8.7.4 Signals............................................................................................................................... 1192
21.8.7.5 Settings.............................................................................................................................1192
21.8.8 Supervison status for IEC 60870-5-103 I103SUPERV.....................................................1192
21.8.8.1 Functionality.................................................................................................................... 1192
21.8.8.2 Identification....................................................................................................................1192
21.8.8.3 Function block................................................................................................................. 1193
21.8.8.4 Signals............................................................................................................................... 1193
21.8.8.5 Settings.............................................................................................................................1193
21.8.9 Status for user defined signals for IEC 60870-5-103 I103USRDEF............................. 1193

36 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

21.8.9.1 Functionality.................................................................................................................... 1193


21.8.9.2 Identification................................................................................................................... 1194
21.8.9.3 Function block................................................................................................................. 1194
21.8.9.4 Signals............................................................................................................................... 1194
21.8.9.5 Settings.............................................................................................................................1195
21.8.10 Function commands for IEC 60870-5-103 I103CMD......................................................1196
21.8.10.1 Functionality.................................................................................................................... 1196
21.8.10.2 Identification................................................................................................................... 1196
21.8.10.3 Function block................................................................................................................. 1196
21.8.10.4 Signals............................................................................................................................... 1196
21.8.10.5 Settings............................................................................................................................. 1197
21.8.11 IED commands for IEC 60870-5-103 I103IEDCMD..........................................................1197
21.8.11.1 Functionality.................................................................................................................... 1197
21.8.11.2 Identification....................................................................................................................1197
21.8.11.3 Function block................................................................................................................. 1197
21.8.11.4 Signals............................................................................................................................... 1197
21.8.11.5 Settings.............................................................................................................................1198
21.8.12 Function commands user defined for IEC 60870-5-103 I103USRCMD...................... 1198
21.8.12.1 Functionality.................................................................................................................... 1198
21.8.12.2 Identification................................................................................................................... 1198
21.8.12.3 Function block................................................................................................................. 1198
21.8.12.4 Signals............................................................................................................................... 1199
21.8.12.5 Settings.............................................................................................................................1199
21.8.13 Function commands generic for IEC 60870-5-103 I103GENCMD...............................1200
21.8.13.1 Functionality....................................................................................................................1200
21.8.13.2 Identification...................................................................................................................1200
21.8.13.3 Function block.................................................................................................................1200
21.8.13.4 Signals.............................................................................................................................. 1200
21.8.13.5 Settings.............................................................................................................................1201
21.8.14 IED commands with position and select for IEC 60870-5-103 I103POSCMD........... 1201
21.8.14.1 Functionality.................................................................................................................... 1201
21.8.14.2 Identification................................................................................................................... 1201
21.8.14.3 Function block................................................................................................................. 1201
21.8.14.4 Signals...............................................................................................................................1202
21.8.14.5 Settings............................................................................................................................ 1202
21.8.15 IED commands with position for IEC 60870-5-103 I103POSCMDV............................ 1202
21.8.15.1 Functionality.................................................................................................................... 1202
21.8.15.2 Identification................................................................................................................... 1202
21.8.15.3 Function block................................................................................................................. 1203
21.8.15.4 Signals...............................................................................................................................1203
21.8.15.5 Settings............................................................................................................................ 1203
21.8.16 Operation principle ............................................................................................................. 1203
21.8.16.1 General.............................................................................................................................. 1203
21.8.16.2 Communication ports.................................................................................................... 1212
21.8.17 Technical data....................................................................................................................... 1213
21.9 MULTICMDRCV and MULTICMDSND................................................................................... 1213

Line distance protection REL670 37


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

21.9.1 Functionality.......................................................................................................................... 1213


21.9.2 Design..................................................................................................................................... 1213
21.9.2.1 General...............................................................................................................................1213
21.9.3 Function block.......................................................................................................................1214
21.9.4 Signals.....................................................................................................................................1214
21.9.5 Settings.................................................................................................................................. 1216
21.9.6 Operation principle.............................................................................................................. 1216
21.10 Activity logging parameters ACTIVLOG............................................................................. 1216
21.10.1 Activity logging ACTIVLOG................................................................................................. 1216
21.10.2 Settings...................................................................................................................................1217

Section 22 Remote communication...........................................................................1219


22.1 Binary signal transfer............................................................................................................. 1219
22.1.1 Identification......................................................................................................................... 1219
22.1.2 Functionality.......................................................................................................................... 1219
22.1.3 Signals.....................................................................................................................................1219
22.1.4 Settings.................................................................................................................................. 1223
22.1.5 Monitored data..................................................................................................................... 1227
22.1.6 Operation principle.............................................................................................................. 1228
22.2 Transmission of local analog data via LDCM to remote end, function block
LDCMTRN called LDCMTransmit......................................................................................... 1229
22.2.1 Identification.........................................................................................................................1229
22.2.2 Function block...................................................................................................................... 1230
22.2.3 Signals.................................................................................................................................... 1230

Section 23 Security...................................................................................................... 1233


23.1 Authority check ATHCHCK.................................................................................................... 1233
23.1.1 Identification......................................................................................................................... 1233
23.1.2 Functionality..........................................................................................................................1233
23.1.3 Operation principle ............................................................................................................. 1234
23.1.3.1 Authorization with Central Account Management enabled IED............................1236
23.2 Authority management AUTHMAN..................................................................................... 1238
23.2.1 Identification.........................................................................................................................1238
23.2.2 AUTHMAN.............................................................................................................................. 1238
23.2.3 Settings.................................................................................................................................. 1238
23.3 FTP access with password FTPACCS................................................................................. 1238
23.3.1 Identification.........................................................................................................................1238
23.3.2 FTP access with TLS, FTPACCS..........................................................................................1238
23.3.3 Settings.................................................................................................................................. 1239
23.4 Authority status ATHSTAT....................................................................................................1239
23.4.1 Identification.........................................................................................................................1239
23.4.2 Functionality..........................................................................................................................1239
23.4.3 Function block.......................................................................................................................1239
23.4.4 Signals.................................................................................................................................... 1240
23.4.5 Settings..................................................................................................................................1240
23.4.6 Operation principle .............................................................................................................1240
23.5 Self supervision with internal event list INTERRSIG........................................................ 1240

38 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

23.5.1 Functionality......................................................................................................................... 1240


23.5.2 Function block...................................................................................................................... 1240
23.5.3 Signals.....................................................................................................................................1241
23.5.4 Settings.................................................................................................................................. 1241
23.5.5 Operation principle.............................................................................................................. 1241
23.5.5.1 Internal signals................................................................................................................ 1242
23.5.5.2 Supervision of analog inputs........................................................................................1245
23.5.6 Technical data.......................................................................................................................1245
23.6 ChangeLock function CHNGLCK......................................................................................... 1245
23.6.1 Functionality......................................................................................................................... 1245
23.6.2 Function block...................................................................................................................... 1245
23.6.3 Signals.................................................................................................................................... 1245
23.6.4 Operation principle .............................................................................................................1246
23.7 Denial of service DOS............................................................................................................ 1246
23.7.1 Functionality ........................................................................................................................ 1246
23.7.2 Operation principle..............................................................................................................1246

Section 24 Basic IED functions.................................................................................. 1249


24.1 Time synchronization TIMESYNCHGEN............................................................................. 1249
24.1.1 Functionality......................................................................................................................... 1249
24.1.2 Settings..................................................................................................................................1249
24.1.3 Description of SyncLostMode........................................................................................... 1255
24.1.4 Operation principle ............................................................................................................. 1256
24.1.4.1 General concepts............................................................................................................ 1256
24.1.4.2 Real-time clock (RTC) operation.................................................................................. 1258
24.1.4.3 Synchronization alternatives........................................................................................1258
24.1.4.4 Process bus IEC/UCA 61850-9-2LE synchronization............................................... 1261
24.1.4.5 Precision Time Protocol (PTP) ..................................................................................... 1261
24.1.5 Technical data....................................................................................................................... 1262
24.2 Parameter setting groups.................................................................................................... 1263
24.2.1 Functionality..........................................................................................................................1263
24.2.2 Function block.......................................................................................................................1263
24.2.3 Signals.................................................................................................................................... 1263
24.2.4 Settings..................................................................................................................................1264
24.2.5 Operation principle..............................................................................................................1264
24.3 Test mode functionality TESTMODE.................................................................................. 1265
24.3.1 Functionality......................................................................................................................... 1265
24.3.2 Function block...................................................................................................................... 1266
24.3.3 Signals.................................................................................................................................... 1266
24.3.4 Settings.................................................................................................................................. 1266
24.3.5 Operation principle ............................................................................................................. 1267
24.4 IED identifiers TERMINALID..................................................................................................1267
24.4.1 Functionality..........................................................................................................................1267
24.4.2 Settings ................................................................................................................................. 1268
24.5 Product information PRODINF............................................................................................ 1268
24.5.1 Functionality......................................................................................................................... 1268

Line distance protection REL670 39


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

24.5.2 Settings ................................................................................................................................. 1268


24.5.3 Factory defined settings.................................................................................................... 1269
24.6 Signal matrix for binary inputs SMBI..................................................................................1269
24.6.1 Functionality......................................................................................................................... 1269
24.6.2 Function block.......................................................................................................................1270
24.6.3 Signals.................................................................................................................................... 1270
24.6.4 Operation principle...............................................................................................................1271
24.7 Signal matrix for binary outputs SMBO .............................................................................1271
24.7.1 Functionality.......................................................................................................................... 1271
24.7.2 Function block....................................................................................................................... 1271
24.7.3 Signals..................................................................................................................................... 1271
24.7.4 Operation principle.............................................................................................................. 1272
24.8 Signal matrix for mA inputs SMMI.......................................................................................1272
24.8.1 Functionality.......................................................................................................................... 1272
24.8.2 Function block.......................................................................................................................1272
24.8.3 Signals.....................................................................................................................................1272
24.8.4 Operation principle.............................................................................................................. 1273
24.9 Signal matrix for analog inputs SMAI................................................................................. 1273
24.9.1 Functionality..........................................................................................................................1273
24.9.2 Function block.......................................................................................................................1273
24.9.3 Signals.................................................................................................................................... 1274
24.9.4 Settings.................................................................................................................................. 1275
24.9.5 Operation principle ............................................................................................................. 1277
24.9.5.1 Frequency values.............................................................................................................1278
24.10 Summation block 3 phase 3PHSUM.................................................................................... 1278
24.10.1 Functionality..........................................................................................................................1278
24.10.2 Function block.......................................................................................................................1279
24.10.3 Signals.................................................................................................................................... 1279
24.10.4 Settings.................................................................................................................................. 1279
24.10.5 Operation principle .............................................................................................................1280

Section 25 IED hardware............................................................................................. 1281


25.1 Overview................................................................................................................................... 1281
25.1.1 Variants of case size with local HMI display....................................................................1281
25.1.2 Case from the front and rear sides...................................................................................1282
25.2 Hardware modules.................................................................................................................1286
25.2.1 Overview................................................................................................................................ 1286
25.2.2 Numeric module (NUM).......................................................................................................1287
25.2.2.1 Introduction..................................................................................................................... 1287
25.2.2.2 Functionality....................................................................................................................1288
25.2.2.3 Technical data................................................................................................................. 1288
25.2.3 Power supply module (PSM).............................................................................................. 1289
25.2.3.1 Introduction.....................................................................................................................1289
25.2.3.2 Design............................................................................................................................... 1289
25.2.3.3 Technical data................................................................................................................. 1290
25.2.4 Local human-machine interface (Local HMI).................................................................. 1290

40 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

25.2.5 Transformer input module (TRM)..................................................................................... 1290


25.2.5.1 Introduction.....................................................................................................................1290
25.2.5.2 Design............................................................................................................................... 1290
25.2.5.3 Technical data..................................................................................................................1291
25.2.6 Analog digital conversion module (ADM)........................................................................ 1292
25.2.6.1 Introduction..................................................................................................................... 1292
25.2.6.2 Design............................................................................................................................... 1293
25.2.7 Binary input module (BIM)..................................................................................................1294
25.2.7.1 Introduction.....................................................................................................................1294
25.2.7.2 Design............................................................................................................................... 1295
25.2.7.3 Signals............................................................................................................................... 1297
25.2.7.4 Settings............................................................................................................................ 1298
25.2.7.5 Monitored data............................................................................................................... 1298
25.2.7.6 Technical data................................................................................................................. 1298
25.2.8 Binary output modules (BOM)...........................................................................................1300
25.2.8.1 Introduction.....................................................................................................................1300
25.2.8.2 Design...............................................................................................................................1300
25.2.8.3 Signals............................................................................................................................... 1301
25.2.8.4 Settings............................................................................................................................ 1302
25.2.8.5 Monitored data............................................................................................................... 1302
25.2.8.6 Technical data................................................................................................................. 1306
25.2.9 Static binary output module (SOM)................................................................................. 1306
25.2.9.1 Introduction.....................................................................................................................1306
25.2.9.2 Design............................................................................................................................... 1306
25.2.9.3 Signals.............................................................................................................................. 1309
25.2.9.4 Settings............................................................................................................................ 1309
25.2.9.5 Monitored data............................................................................................................... 1309
25.2.9.6 Technical data.................................................................................................................. 1311
25.2.10 Binary input/output module (IOM)................................................................................... 1313
25.2.10.1 Introduction......................................................................................................................1313
25.2.10.2 Design................................................................................................................................1313
25.2.10.3 Signals............................................................................................................................... 1315
25.2.10.4 Settings.............................................................................................................................1316
25.2.10.5 Monitored data................................................................................................................1316
25.2.10.6 Technical data..................................................................................................................1318
25.2.11 mA input module (MIM)...................................................................................................... 1320
25.2.11.1 Introduction..................................................................................................................... 1320
25.2.11.2 Design............................................................................................................................... 1320
25.2.11.3 Signals............................................................................................................................... 1322
25.2.11.4 Settings.............................................................................................................................1323
25.2.11.5 Monitored data............................................................................................................... 1324
25.2.11.6 Technical data..................................................................................................................1325
25.2.12 Serial and LON communication module (SLM) ..............................................................1325
25.2.12.1 Introduction..................................................................................................................... 1325
25.2.12.2 Design............................................................................................................................... 1325
25.2.12.3 Technical data................................................................................................................. 1326

Line distance protection REL670 41


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

25.2.13 Galvanic RS485 communication module......................................................................... 1327


25.2.13.1 Introduction..................................................................................................................... 1327
25.2.13.2 Design................................................................................................................................1327
25.2.13.3 Technical data................................................................................................................. 1328
25.2.14 Optical Ethernet module.....................................................................................................1328
25.2.14.1 Introduction..................................................................................................................... 1328
25.2.14.2 Functionality.................................................................................................................... 1329
25.2.14.3 Design............................................................................................................................... 1329
25.2.14.4 Technical data................................................................................................................. 1329
25.2.15 Line data communication module (LDCM)..................................................................... 1329
25.2.15.1 Introduction..................................................................................................................... 1329
25.2.15.2 Design............................................................................................................................... 1330
25.2.15.3 Technical data.................................................................................................................. 1331
25.2.16 Galvanic X.21 line data communication (X.21-LDCM).....................................................1331
25.2.16.1 Introduction......................................................................................................................1331
25.2.16.2 Design................................................................................................................................1331
25.2.16.3 Functionality.................................................................................................................... 1333
25.2.16.4 Technical data................................................................................................................. 1334
25.2.17 GPS time synchronization module (GTM)....................................................................... 1334
25.2.17.1 Introduction..................................................................................................................... 1334
25.2.17.2 Design............................................................................................................................... 1334
25.2.17.3 Monitored data................................................................................................................1335
25.2.17.4 Technical data................................................................................................................. 1335
25.2.18 GPS antenna.......................................................................................................................... 1335
25.2.18.1 Introduction..................................................................................................................... 1335
25.2.18.2 Design............................................................................................................................... 1335
25.2.18.3 Technical data..................................................................................................................1337
25.2.19 IRIG-B time synchronization module IRIG-B.................................................................... 1337
25.2.19.1 Introduction..................................................................................................................... 1337
25.2.19.2 Design................................................................................................................................1337
25.2.19.3 Encoding...........................................................................................................................1338
25.2.19.4 TimeZoneAs1344............................................................................................................ 1338
25.2.19.5 Settings.............................................................................................................................1338
25.2.19.6 Technical data................................................................................................................. 1338
25.3 Dimensions.............................................................................................................................. 1339
25.3.1 Case with protective cover.................................................................................................1339
25.3.2 Case without protective cover.......................................................................................... 1342
25.3.3 Flush mounting dimensions.............................................................................................. 1344
25.3.4 Side-by-side flush mounting dimensions....................................................................... 1344
25.3.5 Wall mounting dimensions.................................................................................................1345
25.3.6 External resistor unit for high impedance differential protection............................ 1346
25.4 Mounting alternatives........................................................................................................... 1347
25.4.1 Flush mounting.....................................................................................................................1347
25.4.1.1 Overview........................................................................................................................... 1347
25.4.1.2 Mounting procedure for flush mounting...................................................................1348
25.4.2 Wall mounting.......................................................................................................................1348

42 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

25.4.2.1 Overview...........................................................................................................................1348
25.4.2.2 Mounting procedure for wall mounting.....................................................................1349
25.4.2.3 How to reach the rear side of the IED........................................................................ 1349
25.4.3 19” panel rack mounting..................................................................................................... 1350
25.4.3.1 Overview...........................................................................................................................1350
25.4.3.2 Mounting procedure for 19” panel rack mounting................................................... 1351
25.4.4 Side-by-side 19” rack mounting.........................................................................................1352
25.4.4.1 Overview........................................................................................................................... 1352
25.4.4.2 Mounting procedure for side-by-side rack mounting............................................. 1352
25.4.4.3 IED mounted with a RHGS6 case................................................................................. 1352
25.4.5 Side-by-side flush mounting.............................................................................................. 1353
25.4.5.1 Overview........................................................................................................................... 1353
25.4.5.2 Mounting procedure for side-by-side flush mounting............................................1354
25.5 Technical data......................................................................................................................... 1354
25.5.1 Enclosure............................................................................................................................... 1354
25.5.2 Electrical safety.................................................................................................................... 1355
25.5.3 Connection system.............................................................................................................. 1355
25.5.4 Influencing factors............................................................................................................... 1356
25.5.5 Type tests according to standard.....................................................................................1357

Section 26 Labels......................................................................................................... 1359


26.1 Labels on IED........................................................................................................................... 1359

Section 27 Connection diagrams...............................................................................1361

Section 28 Inverse time characteristics................................................................... 1363


28.1 Application...............................................................................................................................1363
28.2 Principle of operation............................................................................................................ 1365
28.2.1 Mode of operation............................................................................................................... 1365
28.3 Inverse characteristics.......................................................................................................... 1370

Section 29 Glossary..................................................................................................... 1397

Line distance protection REL670 43


Technical manual
© Copyright 2017 ABB. All rights reserved
44
1MRK 506 370-UEN J Section 1
Introduction

Section 1 Introduction
1.1 This manual GUID-AB423A30-13C2-46AF-B7FE-A73BB425EB5F v19

The technical manual contains operation principle descriptions, and lists function blocks, logic
diagrams, input and output signals, setting parameters and technical data, sorted per
function. The manual can be used as a technical reference during the engineering phase,
installation and commissioning phase, and during normal service.

1.1.1 Presumptions for Technical Data GUID-1E949E38-E04D-4374-A086-912C25E9F93C v2

The technical data stated in this document are only valid under the following circumstances:

1. Main current transformers with 1 A or 2 A secondary rating are wired to the IED 1 A rated
CT inputs.
2. Main current transformer with 5 A secondary rating are wired to the IED 5 A rated CT
inputs.
3. CT and VT ratios in the IED are set in accordance with the associated main instrument
transformers. Note that for functions which measure an analogue signal which do not
have corresponding primary quantity the 1:1 ratio shall be set for the used analogue inputs
on the IED. Example of such functions are: HZPDIF, ROTIPHIZ and STTIPHIZ.
4. Parameter IBase used by the tested function is set equal to the rated CT primary current.
5. Parameter UBase used by the tested function is set equal to the rated primary phase-to-
phase voltage.
6. Parameter SBase used by the tested function is set equal to:
• √3 × IBase × UBase
7. The rated secondary quantities have the following values:
• Rated secondary phase current Ir is either 1 A or 5 A depending on selected TRM.
• Rated secondary phase-to-phase voltage Ur is within the range from 100 V to 120 V.
• Rated secondary power for three-phase system Sr = √3 × Ur × Ir
8. For operate and reset time testing, the default setting values of the function are used if
not explicitly stated otherwise.
9. During testing, signals with rated frequency have been injected if not explicitly stated
otherwise.

1.2 Intended audience GUID-C9B8127F-5748-4BEA-9E4F-CC762FE28A3A v11

This manual addresses system engineers and installation and commissioning personnel, who
use technical data during engineering, installation and commissioning, and in normal service.

The system engineer must have a thorough knowledge of protection systems, protection
equipment, protection functions and the configured functional logic in the IEDs. The
installation and commissioning personnel must have a basic knowledge in handling electronic
equipment.

Line distance protection REL670 45


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 1 1MRK 506 370-UEN J
Introduction

1.3 Product documentation

1.3.1 Product documentation set GUID-3AA69EA6-F1D8-47C6-A8E6-562F29C67172 v16

Deinstalling & disposal


Planning & purchase

Decommissioning
Commissioning

Maintenance
Engineering

Operation
Installing
Engineering manual
Installation manual

Commissioning manual
Operation manual

Application manual

Technical manual

Communication
protocol manual
Cyber security
deployment guideline
IEC07000220-4-en.vsd
IEC07000220 V4 EN-US

Figure 1: The intended use of manuals throughout the product lifecycle


The engineering manual contains instructions on how to engineer the IEDs using the various
tools available within the PCM600 software. The manual provides instructions on how to set
up a PCM600 project and insert IEDs to the project structure. The manual also recommends a
sequence for the engineering of protection and control functions, as well as communication
engineering for IEC 61850.

The installation manual contains instructions on how to install the IED. The manual provides
procedures for mechanical and electrical installation. The chapters are organized in the
chronological order in which the IED should be installed.

The commissioning manual contains instructions on how to commission the IED. The manual
can also be used by system engineers and maintenance personnel for assistance during the
testing phase. The manual provides procedures for the checking of external circuitry and
energizing the IED, parameter setting and configuration as well as verifying settings by
secondary injection. The manual describes the process of testing an IED in a substation which
is not in service. The chapters are organized in the chronological order in which the IED should
be commissioned. The relevant procedures may be followed also during the service and
maintenance activities.

The operation manual contains instructions on how to operate the IED once it has been
commissioned. The manual provides instructions for the monitoring, controlling and setting of
the IED. The manual also describes how to identify disturbances and how to view calculated
and measured power grid data to determine the cause of a fault.

46 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 1
Introduction

The application manual contains application descriptions and setting guidelines sorted per
function. The manual can be used to find out when and for what purpose a typical protection
function can be used. The manual can also provide assistance for calculating settings.

The technical manual contains operation principle descriptions, and lists function blocks, logic
diagrams, input and output signals, setting parameters and technical data, sorted per
function. The manual can be used as a technical reference during the engineering phase,
installation and commissioning phase, and during normal service.

The communication protocol manual describes the communication protocols supported by


the IED. The manual concentrates on the vendor-specific implementations.

The point list manual describes the outlook and properties of the data points specific to the
IED. The manual should be used in conjunction with the corresponding communication
protocol manual.

The cyber security deployment guideline describes the process for handling cyber security
when communicating with the IED. Certification, Authorization with role based access control,
and product engineering for cyber security related events are described and sorted by
function. The guideline can be used as a technical reference during the engineering phase,
installation and commissioning phase, and during normal service.

1.3.2 Document revision history GUID-34B323E4-1319-4D42-80CE-29B0F2D36E2C v3

Document Date Product revision History


revision
- 2017-07 2.2.0 First release for product version 2.2
A 2017-10 2.2.1 Ethernet ports with RJ45 connector added.
enhancements/updates made to ZMFPDIS and
ZMFCPDIS.
B 2017-11 2.2.1 ZMFPDIS and ZMFCPDIS - Added missing setting tables
C 2018–03 2.2.1 Document enhancements and corrections
D 2018-06 2.2.2 LDCM galvanic X.21 added. Function PTRSTHR added.
Ordering section updated.
E 2018-06 2.2.2 Technical data updated for PSM and EF4PTOC.
Corrections/enhancements made to OC4PTOC, TRPTTR,
UV2PTUV and OV2PTOV. Case dimensions updated.
F 2018–09 2.2.2 Updated KEMA test values
G 2018-11 2.2.3 Functions CHMMHAI, VHMMHAI, DELVSPVC, DELSPVC and
DELISPVC added. Updates/enhancements made to
ZMFPDIS, ZMFCPDIS, CCRBRF, REALCOMP, PTRSTHR and
FNKEYMDx. Ordering section updated.
H 2019-05 2.2.3 PTP enhancements and corrections
J 2019-10 2.2.3 SOM redesign updates

1.3.3 Related documents GUID-94E8A5CA-BE1B-45AF-81E7-5A41D34EE112 v7

Documents related to REL670 Document numbers


Application manual 1MRK 506 369-UEN
Commissioning manual 1MRK 506 371-UEN
Product guide 1MRK 506 372-BEN
Technical manual 1MRK 506 370-UEN
Type test certificate 1MRK 506 372-TEN

Line distance protection REL670 47


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 1 1MRK 506 370-UEN J
Introduction

670 series manuals Document numbers


Operation manual 1MRK 500 127-UEN
Engineering manual 1MRK 511 398-UEN
Installation manual 1MRK 514 026-UEN
Communication protocol manual, DNP3 1MRK 511 391-UUS
Communication protocol manual, IEC 60870-5-103 1MRK 511 394-UEN
Communication protocol manual, IEC 61850 Edition 1 1MRK 511 392-UEN
Communication protocol manual, IEC 61850 Edition 2 1MRK 511 393-UEN
Communication protocol manual, LON 1MRK 511 395-UEN
Communication protocol manual, SPA 1MRK 511 396-UEN
Point list manual, DNP3 1MRK 511 397-UUS
Accessories guide 1MRK 514 012-BEN
Cyber security deployment guideline 1MRK 511 399-UEN
Connection and Installation components 1MRK 513 003-BEN
Test system, COMBITEST 1MRK 512 001-BEN
Application guide, Communication set-up 1MRK 505 382-UEN

1.4 Document symbols and conventions

1.4.1 Symbols GUID-2945B229-DAB0-4F15-8A0E-B9CF0C2C7B15 v13

The electrical warning icon indicates the presence of a hazard which could
result in electrical shock.

The warning icon indicates the presence of a hazard which could result in
personal injury.

The caution hot surface icon indicates important information or warning about
the temperature of product surfaces.

Class 1 Laser product. Take adequate measures to protect the eyes and do not
view directly with optical instruments.

The caution icon indicates important information or warning related to the


concept discussed in the text. It might indicate the presence of a hazard which
could result in corruption of software or damage to equipment or property.

48 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 1
Introduction

The information icon alerts the reader of important facts and conditions.

The tip icon indicates advice on, for example, how to design your project or
how to use a certain function.

Although warning hazards are related to personal injury, it is necessary to understand that
under certain operational conditions, operation of damaged equipment may result in
degraded process performance leading to personal injury or death. It is important that the
user fully complies with all warning and cautionary notices.

1.4.2 Document conventions GUID-96DFAB1A-98FE-4B26-8E90-F7CEB14B1AB6 v8

• Abbreviations and acronyms in this manual are spelled out in the glossary. The glossary
also contains definitions of important terms.
• Push button navigation in the LHMI menu structure is presented by using the push button
icons.
For example, to navigate between the options, use and .
• HMI menu paths are presented in bold.
For example, select Main menu/Settings.
• LHMI messages are shown in Courier font.
For example, to save the changes in non-volatile memory, select Yes and press .
• Parameter names are shown in italics.
For example, the function can be enabled and disabled with the Operation setting.
• Each function block symbol shows the available input/output signal.
• the character ^ in front of an input/output signal name indicates that the signal
name may be customized using the PCM600 software.
• the character * after an input signal name indicates that the signal must be
connected to another function block in the application configuration to achieve a
valid application configuration.
• Dimensions are provided both in inches and millimeters. If it is not specifically mentioned
then the dimension is in millimeters.
• Logic diagrams describe the signal logic of the function block and are bordered by dashed
lines.
In a logic diagram, input and output signal paths are shown as lines that touch the outer
border of the diagram. Input signals are always on the left-hand side and output signals
are on the right-hand side.
Input and output signals can be configured using PCM600. They can be connected to the
inputs and outputs of other functions and to binary inputs and outputs. Examples of input
signals are BLKTR, BLOCK, and VTSZ. Examples of output signals are TRIP, START, STL1,
STL2, and STL3.
• Frames with a shaded area on the right-hand side represent setting parameters.
These parameters can only be set via the PST or LHMI. Their values are high (1) only
when the corresponding setting parameter is set to the symbolic value specified
within the frame. Example is the signal Timer tPP=On. Their logical values
correspond automatically to the selected setting value.
• Internal signals are illustrated graphically and end approximately 2 mm from the
frame edge. If an internal signal path cannot be drawn with a continuous line, the
same signal name is used where the signal should continue, see figure 2 and figure 3.
Example of the internal signal is BLK.
• Signal paths that extend beyond the logic diagram and continue in another diagram
will be approximately 2 mm from the frame edge, see figure 3 and figure 4. Examples
are STNDL1N, STNDL2N, STNDL3N, STNDL1L2, STNDL2L3, and STNDL3L1.

Line distance protection REL670 49


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 1 1MRK 506 370-UEN J
Introduction

STZMPP
OR
STCND

AND STNDL1L2
L1L2

STNDL2L3
L2L3 AND

L3L1 AND STNDL3L1

AND STNDL1N
L1N

AND STNDL2N
L2N

STNDL3N
L3N AND

OR STPE

OR
VTSZ STND
OR AND
BLOCK
BLOCFUNC BLK

99000557-2.vsd
IEC99000557-TIFF V3 EN-US

Figure 2: Logic diagram example with intermediate output signals

IEC00000488-TIFF V1 EN-US

Figure 3: Logic diagram example with intermediate input signals

50 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 1
Introduction

Timer tPP=On
STZMPP AND tPP
AND
t

BLOCFUNC
OR OR
tPE
t
AND
Timer tPE=On AND
STZMPE 15ms
BLKTR AND t
TRIP
BLK OR

STL1 AND TRL1

STL2 AND TRL2

STL3 AND TRL3

IEC09000887-3-en.vsdx

IEC09000887 V3 EN-US

Figure 4: Logic diagram example with a parameter input

Illustrations are used as an example and might show other products than the
one the manual describes. The example that is illustrated is still valid.

1.5 IEC 61850 edition 1 / edition 2 mapping GUID-C5133366-7260-4C47-A975-7DBAB3A33A96 v7

Function block names are used in ACT and PST to identify functions. Respective function block
names of Edition 1 logical nodes and Edition 2 logical nodes are shown in the table below.

Table 1: IEC 61850 edition 1 / edition 2 mapping


Function block name Edition 1 logical nodes Edition 2 logical nodes
AEGPVOC AEGGAPC AEGPVOC
AGSAL AGSAL AGSAL
SECLLN0
ALMCALH ALMCALH ALMCALH
ALTIM - ALTIM
ALTMS - ALTMS
ALTRK - ALTRK
BCZPDIF BCZPDIF BCZPDIF
BCZSPDIF BCZSPDIF BCZSPDIF
BCZTPDIF BCZTPDIF BCZTPDIF
BDCGAPC SWSGGIO BBCSWI
BDCGAPC
Table continues on next page

Line distance protection REL670 51


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 1 1MRK 506 370-UEN J
Introduction

Function block name Edition 1 logical nodes Edition 2 logical nodes


BDZSGAPC BBS6LLN0 LLN0
BDZSGAPC BDZSGAPC
BFPTRC_F01 BFPTRC BFPTRC
BFPTRC_F02 BFPTRC BFPTRC
BFPTRC_F03 BFPTRC BFPTRC
BFPTRC_F04 BFPTRC BFPTRC
BFPTRC_F05 BFPTRC BFPTRC
BFPTRC_F06 BFPTRC BFPTRC
BFPTRC_F07 BFPTRC BFPTRC
BFPTRC_F08 BFPTRC BFPTRC
BFPTRC_F09 BFPTRC BFPTRC
BFPTRC_F10 BFPTRC BFPTRC
BFPTRC_F11 BFPTRC BFPTRC
BFPTRC_F12 BFPTRC BFPTRC
BFPTRC_F13 BFPTRC BFPTRC
BFPTRC_F14 BFPTRC BFPTRC
BFPTRC_F15 BFPTRC BFPTRC
BFPTRC_F16 BFPTRC BFPTRC
BFPTRC_F17 BFPTRC BFPTRC
BFPTRC_F18 BFPTRC BFPTRC
BFPTRC_F19 BFPTRC BFPTRC
BFPTRC_F20 BFPTRC BFPTRC
BFPTRC_F21 BFPTRC BFPTRC
BFPTRC_F22 BFPTRC BFPTRC
BFPTRC_F23 BFPTRC BFPTRC
BFPTRC_F24 BFPTRC BFPTRC
BICPTRC_01 BICPTRC BICPTRC
BICPTRC_02 BICPTRC BICPTRC
BICPTRC_03 BICPTRC BICPTRC
BICPTRC_04 BICPTRC BICPTRC
BICPTRC_05 BICPTRC BICPTRC
BRCPTOC BRCPTOC BRCPTOC
BRPTOC BRPTOC BRPTOC
BTIGAPC B16IFCVI BTIGAPC
BUSPTRC_B1 BUSPTRC BUSPTRC
BBSPLLN0
BUSPTRC_B2 BUSPTRC BUSPTRC
BUSPTRC_B3 BUSPTRC BUSPTRC
BUSPTRC_B4 BUSPTRC BUSPTRC
BUSPTRC_B5 BUSPTRC BUSPTRC
BUSPTRC_B6 BUSPTRC BUSPTRC
BUSPTRC_B7 BUSPTRC BUSPTRC
BUSPTRC_B8 BUSPTRC BUSPTRC
Table continues on next page

52 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 1
Introduction

Function block name Edition 1 logical nodes Edition 2 logical nodes


BUSPTRC_B9 BUSPTRC BUSPTRC
BUSPTRC_B10 BUSPTRC BUSPTRC
BUSPTRC_B11 BUSPTRC BUSPTRC
BUSPTRC_B12 BUSPTRC BUSPTRC
BUSPTRC_B13 BUSPTRC BUSPTRC
BUSPTRC_B14 BUSPTRC BUSPTRC
BUSPTRC_B15 BUSPTRC BUSPTRC
BUSPTRC_B16 BUSPTRC BUSPTRC
BUSPTRC_B17 BUSPTRC BUSPTRC
BUSPTRC_B18 BUSPTRC BUSPTRC
BUSPTRC_B19 BUSPTRC BUSPTRC
BUSPTRC_B20 BUSPTRC BUSPTRC
BUSPTRC_B21 BUSPTRC BUSPTRC
BUSPTRC_B22 BUSPTRC BUSPTRC
BUSPTRC_B23 BUSPTRC BUSPTRC
BUSPTRC_B24 BUSPTRC BUSPTRC
BUTPTRC_B1 BUTPTRC BUTPTRC
BBTPLLN0
BUTPTRC_B2 BUTPTRC BUTPTRC
BUTPTRC_B3 BUTPTRC BUTPTRC
BUTPTRC_B4 BUTPTRC BUTPTRC
BUTPTRC_B5 BUTPTRC BUTPTRC
BUTPTRC_B6 BUTPTRC BUTPTRC
BUTPTRC_B7 BUTPTRC BUTPTRC
BUTPTRC_B8 BUTPTRC BUTPTRC
BZISGGIO BZISGGIO BZISGAPC
BZITGGIO BZITGGIO BZITGAPC
BZNPDIF_Z1 BZNPDIF BZNPDIF
BZNPDIF_Z2 BZNPDIF BZNPDIF
BZNPDIF_Z3 BZNPDIF BZNPDIF
BZNPDIF_Z4 BZNPDIF BZNPDIF
BZNPDIF_Z5 BZNPDIF BZNPDIF
BZNPDIF_Z6 BZNPDIF BZNPDIF
BZNSPDIF_A BZNSPDIF BZASGAPC
BZASPDIF
BZNSGAPC
BZNSPDIF
BZNSPDIF_B BZNSPDIF BZBSGAPC
BZBSPDIF
BZNSGAPC
BZNSPDIF
BZNTPDIF_A BZNTPDIF BZATGAPC
BZATPDIF
BZNTGAPC
BZNTPDIF
Table continues on next page

Line distance protection REL670 53


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 1 1MRK 506 370-UEN J
Introduction

Function block name Edition 1 logical nodes Edition 2 logical nodes


BZNTPDIF_B BZNTPDIF BZBTGAPC
BZBTPDIF
BZNTGAPC
BZNTPDIF
CBPGAPC CBPLLN0 CBPMMXU
CBPMMXU CBPPTRC
CBPPTRC HOLPTOV
HOLPTOV HPH1PTOV
HPH1PTOV PH3PTOC
PH3PTUC PH3PTUC
PH3PTOC RP3PDOP
RP3PDOP
CCPDSC CCRPLD CCPDSC
CCRBRF CCRBRF CCRBRF
CCRWRBRF CCRWRBRF CCRWRBRF
CCSRBRF CCSRBRF CCSRBRF
CCSSPVC CCSRDIF CCSSPVC
CMMXU CMMXU CMMXU
CMSQI CMSQI CMSQI
COUVGAPC COUVLLN0 COUVPTOV
COUVPTOV COUVPTUV
COUVPTUV
CVGAPC GF2LLN0 GF2MMXN
GF2MMXN GF2PHAR
GF2PHAR GF2PTOV
GF2PTOV GF2PTUC
GF2PTUC GF2PTUV
GF2PTUV GF2PVOC
GF2PVOC PH1PTRC
PH1PTRC
CVMMXN CVMMXN CVMMXN
D2PTOC D2LLN0 D2PTOC
D2PTOC PH1PTRC
PH1PTRC
DPGAPC DPGGIO DPGAPC
DRPRDRE DRPRDRE DRPRDRE
ECPSCH ECPSCH ECPSCH
ECRWPSCH ECRWPSCH ECRWPSCH
EF2PTOC EF2LLN0 EF2PTRC
EF2PTRC EF2RDIR
EF2RDIR GEN2PHAR
GEN2PHAR PH1PTOC
PH1PTOC
EF4PTOC EF4LLN0 EF4PTRC
EF4PTRC EF4RDIR
EF4RDIR GEN4PHAR
GEN4PHAR PH1PTOC
PH1PTOC
EFPIOC EFPIOC EFPIOC
EFRWPIOC EFRWPIOC EFRWPIOC
ETPMMTR ETPMMTR ETPMMTR
FDPSPDIS FDPSPDIS FDPSPDIS
FMPSPDIS FMPSPDIS FMPSPDIS
Table continues on next page

54 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 1
Introduction

Function block name Edition 1 logical nodes Edition 2 logical nodes


FRPSPDIS FPSRPDIS FPSRPDIS
FTAQFVR FTAQFVR FTAQFVR
FUFSPVC SDDRFUF FUFSPVC
SDDSPVC
GENPDIF GENPDIF GENGAPC
GENPDIF
GENPHAR
GENPTRC
GOPPDOP GOPPDOP GOPPDOP
PH1PTRC
GRPTTR GRPTTR GRPTTR
GSPTTR GSPTTR GSPTTR
GUPPDUP GUPPDUP GUPPDUP
PH1PTRC
HZPDIF HZPDIF HZPDIF
INDCALCH INDCALH INDCALH
ITBGAPC IB16FCVB ITBGAPC
L3CPDIF L3CPDIF L3CGAPC
L3CPDIF
L3CPHAR
L3CPTRC
L4CPDIF L4CLLN0 LLN0
L4CPDIF L4CGAPC
L4CPTRC L4CPDIF
L4CPSCH
L4CPTRC
L4UFCNT L4UFCNT L4UFCNT
L6CPDIF L6CPDIF L6CGAPC
L6CPDIF
L6CPHAR
L6CPTRC
LAPPGAPC LAPPLLN0 LAPPPDUP
LAPPPDUP LAPPPUPF
LAPPPUPF
LCCRPTRC LCCRPTRC LCCRPTRC
LCNSPTOC LCNSPTOC LCNSPTOC
LCNSPTOV LCNSPTOV LCNSPTOV
LCP3PTOC LCP3PTOC LCP3PTOC
LCP3PTUC LCP3PTUC LCP3PTUC
LCPTTR LCPTTR LCPTTR
LCZSPTOC LCZSPTOC LCZSPTOC
LCZSPTOV LCZSPTOV LCZSPTOV
LD0LLN0 LLN0 -
LDLPSCH LDLPDIF LDLPSCH
LDRGFC STSGGIO LDRGFC
LEXPDIS LEXPDIS LEXPDIS
LEXPTRC
LFPTTR LFPTTR LFPTTR
LMBRFLO LMBRFLO LMBRFLO
LOLSPTR LOLSPTR LOLSPTR
Table continues on next page

Line distance protection REL670 55


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 1 1MRK 506 370-UEN J
Introduction

Function block name Edition 1 logical nodes Edition 2 logical nodes


LOVPTUV LOVPTUV LOVPTUV
LPHD LPHD
LPTTR LPTTR LPTTR
LT3CPDIF LT3CPDIF LT3CGAPC
LT3CPDIF
LT3CPHAR
LT3CPTRC
LT6CPDIF LT6CPDIF LT6CGAPC
LT6CPDIF
LT6CPHAR
LT6CPTRC
MVGAPC MVGGIO MVGAPC
NS2PTOC NS2LLN0 NS2PTOC
NS2PTOC NS2PTRC
NS2PTRC
NS4PTOC EF4LLN0 EF4PTRC
EF4PTRC EF4RDIR
EF4RDIR PH1PTOC
GEN4PHAR
PH1PTOC
O2RWPTOV GEN2LLN0 O2RWPTOV
O2RWPTOV PH1PTRC
PH1PTRC
OC4PTOC OC4LLN0 GEN4PHAR
GEN4PHAR PH3PTOC
PH3PTOC PH3PTRC
PH3PTRC
OEXPVPH OEXPVPH OEXPVPH
OOSPPAM OOSPPAM OOSPPAM
OOSPTRC
OV2PTOV GEN2LLN0 OV2PTOV
OV2PTOV PH1PTRC
PH1PTRC
PAPGAPC PAPGAPC PAPGAPC
PCFCNT PCGGIO PCFCNT
PH4SPTOC GEN4PHAR GEN4PHAR
OCNDLLN0 PH1BPTOC
PH1BPTOC PH1PTRC
PH1PTRC
PHPIOC PHPIOC PHPIOC
PSLPSCH ZMRPSL PSLPSCH
PSPPPAM PSPPPAM PSPPPAM
PSPPTRC
QCBAY QCBAY BAY/LLN0
QCRSV QCRSV QCRSV
RCHLCCH RCHLCCH RCHLCCH
REFPDIF REFPDIF REFPDIF
ROTIPHIZ ROTIPHIZ ROTIPHIZ
ROTIPTRC
ROV2PTOV GEN2LLN0 PH1PTRC
PH1PTRC ROV2PTOV
ROV2PTOV
SAPFRC SAPFRC SAPFRC
Table continues on next page

56 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 1
Introduction

Function block name Edition 1 logical nodes Edition 2 logical nodes


SAPTOF SAPTOF SAPTOF
SAPTUF SAPTUF SAPTUF
SCCVPTOC SCCVPTOC SCCVPTOC
SCHLCCH SCHLCCH SCHLCCH
SCILO SCILO SCILO
SCSWI SCSWI SCSWI
SDEPSDE SDEPSDE SDEPSDE
SDEPTOC
SDEPTOV
SDEPTRC
SESRSYN RSY1LLN0 AUT1RSYN
AUT1RSYN MAN1RSYN
MAN1RSYN SYNRSYN
SYNRSYN
SLGAPC SLGGIO SLGAPC
SMBRREC SMBRREC SMBRREC
SMPPTRC SMPPTRC SMPPTRC
SP16GAPC SP16GGIO SP16GAPC
SPC8GAPC SPC8GGIO SPC8GAPC
SPGAPC SPGGIO SPGAPC
SSCBR SSCBR SSCBR
SSIMG SSIMG SSIMG
SSIML SSIML SSIML
PTRSTHR PTRSTHR PTRSTHR
STBPTOC STBPTOC BBPMSS
STBPTOC
STEFPHIZ STEFPHIZ STEFPHIZ
STTIPHIZ STTIPHIZ STTIPHIZ
SXCBR SXCBR SXCBR
SXSWI SXSWI SXSWI
T2WPDIF T2WPDIF T2WGAPC
T2WPDIF
T2WPHAR
T2WPTRC
T3WPDIF T3WPDIF T3WGAPC
T3WPDIF
T3WPHAR
T3WPTRC
TCLYLTC TCLYLTC TCLYLTC
TCSLTC
TCMYLTC TCMYLTC TCMYLTC
TEIGAPC TEIGGIO TEIGAPC
TEIGGIO
TEILGAPC TEILGGIO TEILGAPC
TMAGAPC TMAGGIO TMAGAPC
TPPIOC TPPIOC TPPIOC
TR1ATCC TR1ATCC TR1ATCC
TR8ATCC TR8ATCC TR8ATCC
Table continues on next page

Line distance protection REL670 57


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 1 1MRK 506 370-UEN J
Introduction

Function block name Edition 1 logical nodes Edition 2 logical nodes


TRPTTR TRPTTR TRPTTR
U2RWPTUV GEN2LLN0 PH1PTRC
PH1PTRC U2RWPTUV
U2RWPTUV
UV2PTUV GEN2LLN0 PH1PTRC
PH1PTRC UV2PTUV
UV2PTUV
VDCPTOV VDCPTOV VDCPTOV
VDSPVC VDRFUF VDSPVC
VMMXU VMMXU VMMXU
VMSQI VMSQI VMSQI
VNMMXU VNMMXU VNMMXU
VRPVOC VRLLN0 PH1PTRC
PH1PTRC PH1PTUV
PH1PTUV VRPVOC
VRPVOC
VSGAPC VSGGIO VSGAPC
WRNCALH WRNCALH WRNCALH
ZC1PPSCH ZPCPSCH ZPCPSCH
ZC1WPSCH ZPCWPSCH ZPCWPSCH
ZCLCPSCH ZCLCPLAL ZCLCPSCH
ZCPSCH ZCPSCH ZCPSCH
ZCRWPSCH ZCRWPSCH ZCRWPSCH
ZCVPSOF ZCVPSOF ZCVPSOF
ZGVPDIS ZGVLLN0 PH1PTRC
PH1PTRC ZGVPDIS
ZGVPDIS ZGVPTUV
ZGVPTUV
ZMCAPDIS ZMCAPDIS ZMCAPDIS
ZMCPDIS ZMCPDIS ZMCPDIS
ZMFCPDIS ZMFCLLN0 PSFPDIS
PSFPDIS ZMFPDIS
ZMFPDIS ZMFPTRC
ZMFPTRC ZMMMXU
ZMMMXU
ZMFPDIS ZMFLLN0 PSFPDIS
PSFPDIS PSFPDIS
ZMFPDIS ZMFPDIS
ZMFPTRC ZMFPTRC
ZMMMXU ZMMMXU
ZMHPDIS ZMHPDIS ZMHPDIS
ZMMAPDIS ZMMAPDIS ZMMAPDIS
ZMMPDIS ZMMPDIS ZMMPDIS
ZMQAPDIS ZMQAPDIS ZMQAPDIS
ZMQPDIS ZMQPDIS ZMQPDIS
ZMRAPDIS ZMRAPDIS ZMRAPDIS
ZMRPDIS ZMRPDIS ZMRPDIS
ZMRPSB ZMRPSB ZMRPSB
ZSMGAPC ZSMGAPC ZSMGAPC

58 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 2
Available functions

Section 2 Available functions


GUID-F5776DD1-BD04-4872-BB89-A0412B4B5CC3 v1

The following tables list all the functions available in the IED. Those functions
that are not exposed to the user or do not need to be configured are not
described in this manual.

2.1 Main protection functions GUID-66BAAD98-851D-4AAC-B386-B38B57718BD2 v15

Table 2: Example of quantities

2 = number of basic instances


0-3 = option quantities
3-A03 = optional function included in packages A03 (refer to ordering details)

IEC 61850 or ANSI Function description Line Distance


function name

REL670 (D42)
REL670 (A42)

REL670 (B42)
REL670 (A41)
REL670
(Customized)

Differential protection
HZPDIF 87 High impedance differential 00-03 3-A02 3-A02 3-A02
protection, single phase
LDRGFC 11REL Additional security logic for 0-1
differential protection
Impedance protection
ZMQPDIS, 21 Distance protection zone, 0-5
ZMQAPDIS quadrilateral characteristic
ZDRDIR 21D Directional impedance 0-2
quadrilateral
ZMCPDIS, 21 Distance measuring zone, 0-6
ZMCAPDIS quadrilateral characteristic for
series compensated lines
ZDSRDIR 21D Directional impedance 0-2
quadrilateral, including series
compensation
FDPSPDIS 21 Phase selection, quadrilateral 0-2
characteristic with fixed angle
ZMHPDIS 21 Full-scheme distance 0-5
protection, mho characteristic
ZMMPDIS, 21 Full-scheme distance 0-5
ZMMAPDIS protection, quadrilateral for
earth faults
ZDMRDIR 21D Directional impedance element 0-2
for mho characteristic
Table continues on next page

Line distance protection REL670 59


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 2 1MRK 506 370-UEN J
Available functions

IEC 61850 or ANSI Function description Line Distance


function name

REL670 (D42)
REL670 (A42)

REL670 (B42)
REL670 (A41)
REL670
(Customized)

ZDARDIR Additional distance protection 0-2


directional function for earth
faults
ZSMGAPC Mho impedance supervision 0-1
logic
FMPSPDIS 21 Faulty phase identification with 0-2
load enchroachment
ZMRPDIS, 21 Distance measuring zone, quad 0-5
ZMRAPDIS characteristic separate Ph-Ph
and Ph-E settings
FRPSPDIS 21 Phase selection, quadrilateral 0-2
characteristic with settable
angle
ZMFPDIS 21 High speed distance 0-2 1 1 1 1
protection, quad and mho
characteristic
ZMFCPDIS 21 High speed distance protection 0-2
for series comp. lines, quad and
mho characteristic
PPLPHIZ Phase preference logic 0-1
PPL2PHIZ Phase preference logic 0-1 1
ZMRPSB 68 Power swing detection 0-1 1 1 1 1
PSLPSCH Power swing logic 0-1 1 1 1 1
PSPPPAM 78 Poleslip/out-of-step protection 0-2 1-B24 1-B24 1-B24
OOSPPAM 78 Out-of-step protection 0-1 1 1 1
ZCVPSOF Automatic switch onto fault 1 1 1 1 1
logic, voltage and current
based

60 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 2
Available functions

2.2 Back-up protection functions GUID-A8D0852F-807F-4442-8730-E44808E194F0 v15

IEC 61850 or ANSI Function description Line Distance


function name

REL670 (D42)
REL670 (A42)

REL670 (B42)
REL670 (A41)
REL670
(Customized)

Current protection
PHPIOC 50 Instantaneous phase 0-3 1 1 1 1
overcurrent protection
OC4PTOC 51_671) Directional phase overcurrent 0-3 1 1 1 1
protection, four steps
EFPIOC 50N Instantaneous residual 0-3 1 1 1 1
overcurrent protection
EF4PTOC 51N Directional residual 0-3 1 1 1 1
67N2) overcurrent protection, four
steps
NS4PTOC 46I2 Four step directional negative 0-2 1 1 1 1
phase sequence overcurrent
protection
SDEPSDE 67N Sensitive directional residual 0-1 1 1-C16 1-C16 1-C16
overcurrent and power
protection
LCPTTR 26 Thermal overload protection, 0-2 1 1 1 1
one time constant, Celsius
LFPTTR 26 Thermal overload protection, 0-2 1 1 1 1
one time constant, Fahrenheit
CCRBRF 50BF Breaker failure protection 0-2 1 1 2 1
STBPTOC 50STB Stub protection 0-2 1 1 1B 1
1-B27
CCPDSC 52PD Pole discordance protection 0-2 1 1 2 1
GUPPDUP 37 Directional underpower 0-2 1-C39 1-C39 1-C39
protection
GOPPDOP 32 Directional overpower 0-2 1-C39 1-C39 1-C39
protection
BRCPTOC 46 Broken conductor check 1 1 1 1 1
VRPVOC 51V Voltage restrained 0-3 1 1 1 1
overcurrent protection

Voltage protection
UV2PTUV 27 Two step undervoltage 0-2 1 1 1 1
protection
OV2PTOV 59 Two step overvoltage 0-2 1 1 1 1
protection
ROV2PTOV 59N Two step residual overvoltage 0-2 1 1 1 1
protection
OEXPVPH 24 Overexcitation protection 0-1 1-D03 1-D03 1-D03
Table continues on next page

Line distance protection REL670 61


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 2 1MRK 506 370-UEN J
Available functions

IEC 61850 or ANSI Function description Line Distance


function name

REL670 (D42)
REL670 (A42)

REL670 (B42)
REL670 (A41)
REL670
(Customized)

VDCPTOV 60 Voltage differential protection 0-2 2 2 2


LOVPTUV 27 Loss of voltage check 1 1 1 1 1
PAPGAPC 27 Radial feeder protection 0-1

Frequency protection
SAPTUF 81 Underfrequency protection 0-6 1B 1B 1B 1B
3-E04 3-E04 3-E04 3-E04
SAPTOF 81 Overfrequency protection 0-6 1B 1B 1B 1B
3-E04 3-E04 3-E04 3-E04
SAPFRC 81 Rate-of-change of frequency 0-6 1B 1B 1B 1B
protection 3-E04 3-E04 3-E04 3-E04

Multipurpose protection
CVGAPC General current and voltage 0-4 1 4-F01 4-F01 4-F01
protection

General calculation
SMAIHPAC Multipurpose filter 0-6

1) 67 requires voltage
2) 67N requires voltage

2.3 Control and monitoring functions GUID-E3777F16-0B76-4157-A3BF-0B6B978863DE v19

IEC 61850 or ANSI Function Line Distance


function name description
REL670 (D42)
REL670 (A42)

REL670 (B42)
REL670 (A41)

REL670
(Customized)

Control
SESRSYN 25 Synchrocheck 0-2 1 1 2 1
, energizing
check and
synchronizin
g
SMBRREC 79 Autorecloser 0-4 1 1B 2B 1B
1-H04 2-H05 1-H04
Table continues on next page

62 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 2
Available functions

IEC 61850 or ANSI Function Line Distance


function name description

REL670 (D42)
REL670 (A42)

REL670 (B42)
REL670 (A41)
REL670
(Customized)

APC10 3 Control 0-1 1-H37 1-H37 1-H37


functionality
for a single
bay, max 10
objects (1CB),
including
interlocking
(see Table 4)
APC15 3 Control 0-1 1-H38
functionality
for a single
bay, max 15
objects
(2CB),
including
interlocking
(see Table 5)
QCBAY Bay control 1 1 1 1 1
LOCREM Handling of 1 1 1 1 1
LR-switch
positions
LOCREMCTRL LHMI control 1 1 1 1 1
of PSTO
SXCBR Circuit 6 3 3 6 3
breaker
SLGAPC Logic 15 15 15 15 15
rotating
switch for
function
selection and
LHMI
presentation
VSGAPC Selector mini 30 30 30 30 30
switch
DPGAPC Generic 32 32 32 32 32
communicati
on function
for Double
Point
indication
SPC8GAPC Single point 5 5 5 5 5
generic
control
function 8
signals
AUTOBITS Automation 3 3 3 3 3
bits,
command
function for
DNP3.0
SINGLECMD Single 8 8 8 8 8
command, 16
signals
Table continues on next page

Line distance protection REL670 63


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 2 1MRK 506 370-UEN J
Available functions

IEC 61850 or ANSI Function Line Distance


function name description

REL670 (D42)
REL670 (A42)

REL670 (B42)
REL670 (A41)
REL670
(Customized)

I103CMD Function 1 1 1 1 1
commands
for IEC
60870-5-103
I103GENCMD Function 50 50 50 50 50
commands
generic for
IEC
60870-5-103
I103POSCMD IED 50 50 50 50 50
commands
with position
and select for
IEC
60870-5-103
I103POSCMDV IED direct 50 50 50 50 50
commands
with position
for IEC
60870-5-103
I103IEDCMD IED 1 1 1 1 1
commands
for IEC
60870-5-103
I103USRCMD Function 4 4 4 4 4
commands
user defined
for IEC
60870-5-103
Secondary
system
supervision
CCSSPVC 87 Current 0-2 1 2 1
circuit
supervision
FUFSPVC Fuse failure 0-3 1 3 3 3
supervision
VDSPVC 60 Fuse failure 0-2 1-G03 1-G03 1-G03 1-G03
supervision
based on
voltage
difference
DELVSPVC 7V_78 Voltage delta 4 4 4 4 4
V supervision, 2
phase
DELISPVC 71 Current delta 4 4 4 4 4
supervision, 2
phase
DELSPVC 78 Real delta 4 4 4 4 4
supervision,
real
Logic
Table continues on next page

64 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 2
Available functions

IEC 61850 or ANSI Function Line Distance


function name description

REL670 (D42)
REL670 (A42)

REL670 (B42)
REL670 (A41)
REL670
(Customized)

SMPPTRC 94 Tripping 12 12 12 12 12
logic
SMAGAPC General start 12 12 12 12 12
matrix block
STARTCOMB Start 32 32 32 32 32
combinator
TMAGAPC Trip matrix 12 12 12 12 12
logic
ALMCALH Logic for 5 5 5 5 5
group alarm
WRNCALH Logic for 5 5 5 5 5
group
warning
INDCALH Logic for 5 5 5 5 5
group
indication
AND, GATE, INV, Basic 40-420 40-42 40-42 40-42 40-42
LLD, OR, configurable 0 0 0 0
PULSETIMER, logic blocks
RSMEMORY, (see Table 3)
SRMEMORY,
TIMERSET, XOR
ANDQT, Configurable 0-1
INDCOMBSPQT, logic blocks
INDEXTSPQT, Q/T (see
INVALIDQT, Table 6)
INVERTERQT,
ORQT,
PULSETIMERQT,
RSMEMORYQT,
SRMEMORYQT,
TIMERSETQT,
XORQT
AND, GATE, INV, Extension 0-1
LLD, OR, logic package
PULSETIMER, (see Table 7)
RSMEMORY,
SLGAPC,
SRMEMORY,
TIMERSET,
VSGAPC, XOR
FXDSIGN Fixed signal 1 1 1 1 1
function
block
B16I Boolean to 18 18 18 18 18
integer
conversion,
16 bit
Table continues on next page

Line distance protection REL670 65


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 2 1MRK 506 370-UEN J
Available functions

IEC 61850 or ANSI Function Line Distance


function name description

REL670 (D42)
REL670 (A42)

REL670 (B42)
REL670 (A41)
REL670
(Customized)

BTIGAPC Boolean to 16 16 16 16 16
integer
conversion
with logical
node
representatio
n, 16 bit
IB16 Integer to 18 18 18 18 18
Boolean 16
conversion
ITBGAPC Integer to 16 16 16 16 16
Boolean 16
conversion
with Logic
Node
representatio
n
TEIGAPC Elapsed time 12 12 12 12 12
integrator
with limit
transgressio
n and
overflow
supervision
INTCOMP Comparator 30 30 30 30 30
for integer
inputs
REALCOMP Comparator 30 30 30 30 30
for real
inputs

Table 3: Total number of instances for basic configurable logic blocks


Basic configurable logic block Total number of instances
AND 280
GATE 40
INV 420
LLD 40
OR 298
PULSETIMER 40
RSMEMORY 40
SRMEMORY 40
TIMERSET 60
XOR 40

66 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 2
Available functions

Table 4: Number of function instances in APC10


Function name Function description Total number of instances
SCILO Interlocking 10
BB_ES 3
A1A2_BS 2
A1A2_DC 3
ABC_BC 1
BH_CONN 1
BH_LINE_A 1
BH_LINE_B 1
DB_BUS_A 1
DB_BUS_B 1
DB_LINE 1
ABC_LINE 1
AB_TRAFO 1
SCSWI Switch controller 10
SXSWI Circuit switch 9
QCRSV Apparatus control 2
RESIN1 1
RESIN2 59
POS_EVAL Evaluation of position indication 10
XLNPROXY Proxy for signals from switching 12
device via GOOSE
GOOSEXLNRCV GOOSE function block to receive a 12
switching device

Table 5: Number of function instances in APC15


Function name Function description Total number of instances
SCILO Interlocking 15
BB_ES 3
A1A2_BS 2
A1A2_DC 3
ABC_BC 1
BH_CONN 1
BH_LINE_A 1
BH_LINE_B 1
DB_BUS_A 1
DB_BUS_B 1
DB_LINE 1
ABC_LINE 1
AB_TRAFO 1
SCSWI Switch controller 15
SXSWI Circuit switch 14
Table continues on next page

Line distance protection REL670 67


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 2 1MRK 506 370-UEN J
Available functions

Function name Function description Total number of instances


QCRSV Apparatus control 2
RESIN1 1
RESIN2 59
POS_EVAL Evaluation of position indication 15
XLNPROXY Proxy for signals from switching 20
device via GOOSE
GOOSEXLNRCV GOOSE function block to receive a 20
switching device

Table 6: Total number of instances for configurable logic blocks Q/T


Configurable logic blocks Q/T Total number of instances
ANDQT 120
INDCOMBSPQT 20
INDEXTSPQT 20
INVALIDQT 22
INVERTERQT 120
ORQT 120
PULSETIMERQT 40
RSMEMORYQT 40
SRMEMORYQT 40
TIMERSETQT 40
XORQT 40

Table 7: Total number of instances for extended logic package


Extended configurable logic block Total number of instances
AND 220
GATE 49
INV 220
LLD 49
OR 220
PULSETIMER 89
RSMEMORY 40
SLGAPC 74
SRMEMORY 130
TIMERSET 113
VSGAPC 120
XOR 89

68 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 2
Available functions

IEC 61850 or ANSI Function Line Distance


function name description

REL670 (D42)
REL670 (A42)

REL670 (B42)
REL670 (A41)
REL670
(Customized)

Monitoring
CVMMXN Power 6 6 6 6 6
system
measuremen
t
CMMXU Current 10 10 10 10 10
measuremen
t
VMMXU Voltage 6 6 6 6 6
measuremen
t phase-
phase
CMSQI Current 6 6 6 6 6
sequence
measuremen
t
VMSQI Voltage 6 6 6 6 6
sequence
measuremen
t
VNMMXU Voltage 6 6 6 6 6
measuremen
t phase-earth
AISVBAS General 1 1 1 1 1
service value
presentation
of analog
inputs
EVENT Event 20 20 20 20 20
function
DRPRDRE, Disturbance 1 1 1 1 1
A4RADR, report
SPGAPC Generic 96 96 96 96 96
communicati
on function
for Single
Point
indication
SP16GAPC Generic 16 16 16 16 16
communicati
on function
for Single
Point
indication 16
inputs
MVGAPC Generic 24 24 24 24 24
communicati
on function
for measured
values
BINSTATREP Logical signal 3 3 3 3 3
status report
Table continues on next page

Line distance protection REL670 69


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 2 1MRK 506 370-UEN J
Available functions

IEC 61850 or ANSI Function Line Distance


function name description

REL670 (D42)
REL670 (A42)

REL670 (B42)
REL670 (A41)
REL670
(Customized)

RANGE_XP Measured 66 66 66 66 66
value
expander
block
SSIMG 63 Insulation 21 21 21 21 21
supervision
for gas
medium
SSIML 71 Insulation 3 3 3 3 3
supervision
for liquid
medium
SSCBR Circuit 0-6 3 3 6 3
breaker
condition
monitoring
LMBRFLO Fault locator 1 1 1 1 1
I103MEAS Measurands 1 1 1 1 1
for IEC
60870-5-103
I103MEASUSR Measurands 3 3 3 3 3
user defined
signals for
IEC
60870-5-103
I103AR Function 1 1 1 1 1
status auto-
recloser for
IEC
60870-5-103
I103EF Function 1 1 1 1 1
status earth-
fault for IEC
60870-5-103
I103FLTPROT Function 1 1 1 1 1
status fault
protection
for IEC
60870-5-103
I103IED IED status for 1 1 1 1 1
IEC
60870-5-103
I103SUPERV Supervison 1 1 1 1 1
status for IEC
60870-5-103
I103USRDEF Status for 20 20 20 20 20
user defined
signals for
IEC
60870-5-103
L4UFCNT Event 30 30 30 30 30
counter with
limit
supervision
Table continues on next page

70 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 2
Available functions

IEC 61850 or ANSI Function Line Distance


function name description

REL670 (D42)
REL670 (A42)

REL670 (B42)
REL670 (A41)
REL670
(Customized)

TEILGAPC Running hour 6 6 6 6 6


meter
PTRSTHR 51TF Through fault 0-2 2-M22 2-M22 2-M22 2-M22
monitoring
CHMMHAI ITHD Current 0-3 0-3 0-3 0-3 0-3
harmonic
monitoring, 3
phase
VHMMHAI VTHD Voltage 0-3 0-3 0-3 0-3 0-3
harmonic
monitoring, 3
phase
Metering
PCFCNT Pulse-counter 16 16 16 16 16
logic
ETPMMTR Function for 6 6 6 6 6
energy
calculation
and demand
handling

2.4 Communication GUID-5F144B53-B9A7-4173-80CF-CD4C84579CB5 v17

IEC 61850 or function ANSI Function description Line Distance


name REL670 (D42)
REL670 (A42)

REL670 (B42)
REL670 (A41)

REL670
(Customized)

Station communication
ADE LON communication protocol 1 1 1 1 1
HORZCOMM Network variables via LON 1 1 1 1 1
DNPGEN DNP3.0 communication general 1 1 1 1 1
protocol
IEC 61850-8-1 IEC 61850 1 1 1 1 1
GOOSEINTLKRCV Horizontal communication via 59 59 59 59 59
GOOSE for interlocking
GOOSEBINRCV GOOSE binary receive 16 16 16 16 16
GOOSEDPRCV GOOSE function block to 64 64 64 64 64
receive a double point value
GOOSEINTRCV GOOSE function block to 32 32 32 32 32
receive an integer value
GOOSEMVRCV GOOSE function block to 60 60 60 60 60
receive a measurand value
Table continues on next page

Line distance protection REL670 71


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 2 1MRK 506 370-UEN J
Available functions

IEC 61850 or function ANSI Function description Line Distance


name

REL670 (D42)
REL670 (A42)

REL670 (B42)
REL670 (A41)
REL670
(Customized)

GOOSESPRCV GOOSE function block to 64 64 64 64 64


receive a single point value
MULTICMDRCV, Multiple command and transmit 60/10 60/10 60/10 60/10 60/10
MULTICMDSND
AGSAL Generic security application 1 1 1 1 1
component
LD0LLN0 IEC 61850 LD0 LLN0 1 1 1 1 1
SYSLLN0 IEC 61850 SYS LLN0 1 1 1 1 1
LPHD Physical device information 1 1 1 1 1
PCMACCS IED configuration protocol 1 1 1 1 1
FSTACCS Field service tool access 1 1 1 1 1
IEC 61850-9-2 Process bus 0-1 1-P30 1-P30 1-P30 1-P30
communication, 8 merging
units
ACTIVLOG Activity logging 1 1 1 1 1
ALTRK Service tracking 1 1 1 1 1
PRP IEC 62439-3 Parallel redundancy 0-1 1-P23 1-P23 1-P23 1-P23
protocol
HSR IEC 62439-3 High-availability 0-1 1-P24 1-P24 1-P24 1-P24
seamless redundancy
PMUCONF, Synchrophasor report, 8 0-1 1-P32 1-P32 1-P32 1
PMUREPORT, phasors (see Table 8)
PHASORREPORT1,
ANALOGREPORT1
BINARYREPORT1,
SMAI1 - SMAI12
3PHSUM
PMUSTATUS
PTP Precision time protocol 1 1 1 1 1
SCHLCCH Access point diagnostic for 6 6 6 6 6
non-redundant Ethernet port
RCHLCCH Access point diagnostic for 3 3 3 3 3
redundant Ethernet ports
QUALEXP IEC 61850 quality expander 96 96 96 96 96
Remote communication
BinSignRec1_1 Binary signal transfer receive 3/3/6 3/3/6 3/3/6 3/3/6 3/3/6
BinSignRec1_2
BinSignReceive2
BinSignTrans1_1 Binary signal transfer transmit 3/3/6 3/3/6 3/3/6 3/3/6 3/3/6
BinSignTrans1_2
BinSignTransm2
BinSigRec1_12M Binary signal transfer, 2Mbit 3 3 3 3 3
BinSigRec1_22M receive/transmit
BinSigTran1_12M
BinSigTran1_22M
LDCMTRN Transmission of analog data 1 1 1 1 1
from LDCM
Table continues on next page

72 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 2
Available functions

IEC 61850 or function ANSI Function description Line Distance


name

REL670 (D42)
REL670 (A42)

REL670 (B42)
REL670 (A41)
REL670
(Customized)

LDCMTRN_2M Transmission of analog data 6 6 6 6 6


from LDCM, 2Mbit
LDCMRecBinStat1 Receive binary status from 6/3/3 6/3/3 6/3/3 6/3/3 6/3/3
LDCMRecBinStat2 remote LDCM
LDCMRecBinStat3
LDCMRecBinS2_2M Receive binary status from 3 3 3 3 3
LDCM, 2Mbit
LDCMRecBinS3_2M Receive binary status from 3 3 3 3 3
remote LDCM, 2Mbit
Scheme communication
ZCPSCH 85 Scheme communication logic 0-2 1 1 1 1
with delta based blocking
scheme signal transmit
ZC1PPSCH 85 Phase segregated scheme 0-2 1-B05 1-B05 1-B05
communication logic for
distance protection
ZCRWPSCH 85 Current reversal and weak-end 0-2 1 1 1 1
infeed logic for distance
protection
ZC1WPSCH 85 Current reversal and weak-end 0-2 1-B05 1-B05 1-B05
infeed logic for phase
segregated communication
ZCLCPSCH Local acceleration logic 0-1 1 1 1 1
ECPSCH 85 Scheme communication logic 0-1 1 1 1
for residual overcurrent
protection
ECRWPSCH 85 Current reversal and weak-end 0-1 1 1 1
infeed logic for residual
overcurrent protection
DTT Direct transfer trip 0-1

Table 8: Number of function instances in Synchrophasor report, 8 phasors


Function name Function description Number of instances
PMUCONF Configuration parameters for C37.118 2011 and IEEE1344 protocol 1
PMUREPORT Protocol reporting via IEEE 1344 and C37.118 1
PHASORREPORT1 Protocol reporting of phasor data via IEEE 1344 and C37.118, phasors 1-8 1
ANALOGREPORT1 Protocol reporting of analog data via IEEE 1344 and C37.118, analogs 1-8 1
BINARYREPORT1 Protocol reporting of binary data via IEEE 1344 and C37.118, binary 1-8 1
SMAI1–SMAI12 Signal matrix for analog inputs 1
3PHSUM Summation block 3 phase 6
PMUSTATUS Diagnostics for C37.118 2011 and IEEE1344 protocol 1

Line distance protection REL670 73


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 2 1MRK 506 370-UEN J
Available functions

2.5 Basic IED functions GUID-C8F0E5D2-E305-4184-9627-F6B5864216CA v13

Table 9: Basic IED functions


IEC 61850 or function Description
name
INTERRSIG Self supervision with internal event list
TIMESYNCHGEN Time synchronization module
BININPUT, Time synchronization
SYNCHCAN,
SYNCHGPS,
SYNCHCMPPS,
SYNCHLON,
SYNCHPPH,
SYNCHPPS, SNTP,
SYNCHSPA
TIMEZONE Time synchronization
IRIG-B Time synchronization
SETGRPS Number of setting groups
ACTVGRP Parameter setting groups
TESTMODE Test mode functionality
CHNGLCK Change lock function
SMBI Signal matrix for binary inputs
SMBO Signal matrix for binary outputs
SMMI Signal matrix for mA inputs
SMAI1 - SMAI12 Signal matrix for analog inputs
3PHSUM Summation block 3 phase
ATHSTAT Authority status
ATHCHCK Authority check
AUTHMAN Authority management
FTPACCS FTP access with password
ALTMS Time master supervision
ALTIM Time management
COMSTATUS Protocol diagnostic

Table 10: Local HMI functions


IEC 61850 or function ANSI Description
name
LHMICTRL Local HMI signals
LANGUAGE Local human machine language
SCREEN Local HMI Local human machine screen behavior
FNKEYTY1–FNKEYTY5 Parameter setting function for HMI in PCM600
FNKEYMD1–
FNKEYMD5
Table continues on next page

74 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 2
Available functions

IEC 61850 or function ANSI Description


name
LEDGEN General LED indication part for LHMI
OPENCLOSE_LED LHMI LEDs for open and close keys
GRP1_LED1– Basic part for CP HW LED indication module
GRP1_LED15
GRP2_LED1–
GRP2_LED15
GRP3_LED1–
GRP3_LED15

Line distance protection REL670 75


Technical manual
© Copyright 2017 ABB. All rights reserved
76
1MRK 506 370-UEN J Section 3
Analog inputs

Section 3 Analog inputs SEMOD55010-1 v3

3.1 Introduction SEMOD55003-5 v11

Analog input channels must be configured and set properly in order to get correct
measurement results and correct protection operations. For power measuring, all directional
and differential functions, the directions of the input currents must be defined in order to
reflect the way the current transformers are installed/connected in the field ( primary and
secondary connections ). Measuring and protection algorithms in the IED use primary system
quantities. Setting values are in primary quantities as well and it is important to set the data
about the connected current and voltage transformers properly.

An AISVBAS reference PhaseAngleRef can be defined to facilitate service values reading. This
analog channel's phase angle will always be fixed to zero degrees and remaining analog
channel's phase angle information will be shown in relation to this analog input. During testing
and commissioning of the IED, the reference channel can be changed to facilitate testing and
service values reading.

The IED has the ability to receive analog values from primary equipment, that
are sampled by Merging units (MU) connected to a process bus, via the IEC
61850-9-2 LE protocol.

The availability of VT inputs depends on the ordered transformer input module


(TRM) type.

3.2 Function block SEMOD116577-1 v5

The hardware channels appear in the signal matrix tool (SMT) and in ACT when
a TRM is included in the configuration with the hardware configuration tool. In
the SMT or the ACT, they can be mapped to the desired virtual input (SMAI) of
the IED and used internally in the configuration.

3.3 Signals
PID-3920-OUTPUTSIGNALS v6

Table 11: TRM_12I Output signals


Name Type Description
STATUS BOOLEAN Analogue input module status
CH1(I) STRING Analogue current input 1
CH2(I) STRING Analogue current input 2
CH3(I) STRING Analogue current input 3
CH4(I) STRING Analogue current input 4
CH5(I) STRING Analogue current input 5
Table continues on next page

Line distance protection REL670 77


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 3 1MRK 506 370-UEN J
Analog inputs

Name Type Description


CH6(I) STRING Analogue current input 6
CH7(I) STRING Analogue current input 7
CH8(I) STRING Analogue current input 8
CH9(I) STRING Analogue current input 9
CH10(I) STRING Analogue current input 10
CH11(I) STRING Analogue current input 11
CH12(I) STRING Analogue current input 12

PID-3921-OUTPUTSIGNALS v7

Table 12: TRM_6I_6U Output signals


Name Type Description
STATUS BOOLEAN Analogue input module status
CH1(I) STRING Analogue current input 1
CH2(I) STRING Analogue current input 2
CH3(I) STRING Analogue current input 3
CH4(I) STRING Analogue current input 4
CH5(I) STRING Analogue current input 5
CH6(I) STRING Analogue current input 6
CH7(U) STRING Analogue voltage input 7
CH8(U) STRING Analogue voltage input 8
CH9(U) STRING Analogue voltage input 9
CH10(U) STRING Analogue voltage input 10
CH11(U) STRING Analogue voltage input 11
CH12(U) STRING Analogue voltage input 12

PID-3922-OUTPUTSIGNALS v6

Table 13: TRM_6I Output signals


Name Type Description
STATUS BOOLEAN Analogue input module status
CH1(I) STRING Analogue current input 1
CH2(I) STRING Analogue current input 2
CH3(I) STRING Analogue current input 3
CH4(I) STRING Analogue current input 4
CH5(I) STRING Analogue current input 5
CH6(I) STRING Analogue current input 6

PID-3923-OUTPUTSIGNALS v7

Table 14: TRM_7I_5U Output signals


Name Type Description
STATUS BOOLEAN Analogue input module status
CH1(I) STRING Analogue current input 1
CH2(I) STRING Analogue current input 2
Table continues on next page

78 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 3
Analog inputs

Name Type Description


CH3(I) STRING Analogue current input 3
CH4(I) STRING Analogue current input 4
CH5(I) STRING Analogue current input 5
CH6(I) STRING Analogue current input 6
CH7(I) STRING Analogue current input 7
CH8(U) STRING Analogue voltage input 8
CH9(U) STRING Analogue voltage input 9
CH10(U) STRING Analogue voltage input 10
CH11(U) STRING Analogue voltage input 11
CH12(U) STRING Analogue voltage input 12

PID-3924-OUTPUTSIGNALS v7

Table 15: TRM_9I_3U Output signals


Name Type Description
STATUS BOOLEAN Analogue input module status
CH1(I) STRING Analogue current input 1
CH2(I) STRING Analogue current input 2
CH3(I) STRING Analogue current input 3
CH4(I) STRING Analogue current input 4
CH5(I) STRING Analogue current input 5
CH6(I) STRING Analogue current input 6
CH7(I) STRING Analogue current input 7
CH8(I) STRING Analogue current input 8
CH9(I) STRING Analogue current input 9
CH10(U) STRING Analogue voltage input 10
CH11(U) STRING Analogue voltage input 11
CH12(U) STRING Analogue voltage input 12

PID-6598-OUTPUTSIGNALS v6

Table 16: TRM_10I_2U Output signals


Name Type Description
STATUS BOOLEAN Analogue input module status
CH1(I) STRING Analogue current input 1
CH2(I) STRING Analogue current input 2
CH3(I) STRING Analogue current input 3
CH4(I) STRING Analogue current input 4
CH5(I) STRING Analogue current input 5
CH6(I) STRING Analogue current input 6
CH7(I) STRING Analogue current input 7
CH8(I) STRING Analogue current input 8
CH9(I) STRING Analogue current input 9
Table continues on next page

Line distance protection REL670 79


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 3 1MRK 506 370-UEN J
Analog inputs

Name Type Description


CH10(I) STRING Analogue current input 10
CH11(U) STRING Analogue voltage input 11
CH12(U) STRING Analogue voltage input 12

3.4 Settings
SEMOD129840-4 v2
Dependent on ordered IED type.
PID-4153-SETTINGS v8

Table 17: AISVBAS Non group settings (basic)


Name Values (Range) Unit Step Default Description
PhaseAngleRef TRM40-Ch1 - Ch12 - - TRM40-Ch1 Reference channel
TRM41-Ch1 - Ch12 for phase angle
MU1-L1I - L4I presentation
MU1-L1U - L4U
MU2-L1I - L4I
MU2-L1U - L4U
MU3-L1I - L4I
MU3-L1U - L4U
MU4-L1I - L4I
MU4-L1U - L4U
MU5-L1I - L4I
MU5-L1U - L4U
MU6-L1I - L4I
MU6-L1U - L4U
MU7-L1I - L4I
MU7-L1U - L4U
MU8-L1I - L4I
MU8-L1U - L4U
MU9-L1I - L4I
MU9-L1U - L4U
MU10-L1I - L4I
MU10-L1U - L4U
MU11-L1I - L4I
MU11-L1U - L4U
MU12-L1I - L4I
MU12-L1U - L4U

PID-3920-SETTINGS v7

Table 18: TRM_12I Non group settings (basic)


Name Values (Range) Unit Step Default Description
CTStarPoint1 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec1 1 - 10 A 1 1 Rated CT secondary current
CTprim1 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint2 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec2 1 - 10 A 1 1 Rated CT secondary current
CTprim2 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint3 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec3 1 - 10 A 1 1 Rated CT secondary current
CTprim3 1 - 99999 A 1 3000 Rated CT primary current
Table continues on next page

80 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 3
Analog inputs

Name Values (Range) Unit Step Default Description


CTStarPoint4 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec4 1 - 10 A 1 1 Rated CT secondary current
CTprim4 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint5 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec5 1 - 10 A 1 1 Rated CT secondary current
CTprim5 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint6 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec6 1 - 10 A 1 1 Rated CT secondary current
CTprim6 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint7 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec7 1 - 10 A 1 1 Rated CT secondary current
CTprim7 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint8 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec8 1 - 10 A 1 1 Rated CT secondary current
CTprim8 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint9 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec9 1 - 10 A 1 1 Rated CT secondary current
CTprim9 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint10 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec10 1 - 10 A 1 1 Rated CT secondary current
CTprim10 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint11 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec11 1 - 10 A 1 1 Rated CT secondary current
CTprim11 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint12 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec12 1 - 10 A 1 1 Rated CT secondary current
CTprim12 1 - 99999 A 1 3000 Rated CT primary current

PID-3921-SETTINGS v7

Table 19: TRM_6I_6U Non group settings (basic)


Name Values (Range) Unit Step Default Description
CTStarPoint1 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec1 1 - 10 A 1 1 Rated CT secondary current
CTprim1 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint2 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
Table continues on next page

Line distance protection REL670 81


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 3 1MRK 506 370-UEN J
Analog inputs

Name Values (Range) Unit Step Default Description


CTsec2 1 - 10 A 1 1 Rated CT secondary current
CTprim2 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint3 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec3 1 - 10 A 1 1 Rated CT secondary current
CTprim3 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint4 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec4 1 - 10 A 1 1 Rated CT secondary current
CTprim4 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint5 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec5 1 - 10 A 1 1 Rated CT secondary current
CTprim5 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint6 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec6 1 - 10 A 1 1 Rated CT secondary current
CTprim6 1 - 99999 A 1 3000 Rated CT primary current
VTsec7 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim7 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec8 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim8 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec9 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim9 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec10 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim10 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec11 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim11 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec12 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim12 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage

PID-3922-SETTINGS v7

Table 20: TRM_6I Non group settings (basic)


Name Values (Range) Unit Step Default Description
CTStarPoint1 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec1 1 - 10 A 1 1 Rated CT secondary current
CTprim1 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint2 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec2 1 - 10 A 1 1 Rated CT secondary current
CTprim2 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint3 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec3 1 - 10 A 1 1 Rated CT secondary current
Table continues on next page

82 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 3
Analog inputs

Name Values (Range) Unit Step Default Description


CTprim3 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint4 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec4 1 - 10 A 1 1 Rated CT secondary current
CTprim4 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint5 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec5 1 - 10 A 1 1 Rated CT secondary current
CTprim5 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint6 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec6 1 - 10 A 1 1 Rated CT secondary current
CTprim6 1 - 99999 A 1 3000 Rated CT primary current

PID-3923-SETTINGS v7

Table 21: TRM_7I_5U Non group settings (basic)


Name Values (Range) Unit Step Default Description
CTStarPoint1 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec1 1 - 10 A 1 1 Rated CT secondary current
CTprim1 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint2 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec2 1 - 10 A 1 1 Rated CT secondary current
CTprim2 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint3 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec3 1 - 10 A 1 1 Rated CT secondary current
CTprim3 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint4 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec4 1 - 10 A 1 1 Rated CT secondary current
CTprim4 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint5 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec5 1 - 10 A 1 1 Rated CT secondary current
CTprim5 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint6 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec6 1 - 10 A 1 1 Rated CT secondary current
CTprim6 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint7 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec7 1 - 10 A 1 1 Rated CT secondary current
CTprim7 1 - 99999 A 1 3000 Rated CT primary current
VTsec8 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
Table continues on next page

Line distance protection REL670 83


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 3 1MRK 506 370-UEN J
Analog inputs

Name Values (Range) Unit Step Default Description


VTprim8 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec9 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim9 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec10 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim10 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec11 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim11 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec12 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim12 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage

PID-3924-SETTINGS v7

Table 22: TRM_9I_3U Non group settings (basic)


Name Values (Range) Unit Step Default Description
CTStarPoint1 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec1 1 - 10 A 1 1 Rated CT secondary current
CTprim1 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint2 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec2 1 - 10 A 1 1 Rated CT secondary current
CTprim2 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint3 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec3 1 - 10 A 1 1 Rated CT secondary current
CTprim3 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint4 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec4 1 - 10 A 1 1 Rated CT secondary current
CTprim4 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint5 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec5 1 - 10 A 1 1 Rated CT secondary current
CTprim5 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint6 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec6 1 - 10 A 1 1 Rated CT secondary current
CTprim6 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint7 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec7 1 - 10 A 1 1 Rated CT secondary current
CTprim7 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint8 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec8 1 - 10 A 1 1 Rated CT secondary current
CTprim8 1 - 99999 A 1 3000 Rated CT primary current
Table continues on next page

84 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 3
Analog inputs

Name Values (Range) Unit Step Default Description


CTStarPoint9 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec9 1 - 10 A 1 1 Rated CT secondary current
CTprim9 1 - 99999 A 1 3000 Rated CT primary current
VTsec10 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim10 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec11 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim11 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec12 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim12 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage

PID-6598-SETTINGS v6

Table 23: TRM_10I_2U Non group settings (basic)


Name Values (Range) Unit Step Default Description
CTStarPoint1 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec1 1 - 10 A 1 1 Rated CT secondary current
CTprim1 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint2 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec2 1 - 10 A 1 1 Rated CT secondary current
CTprim2 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint3 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec3 1 - 10 A 1 1 Rated CT secondary current
CTprim3 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint4 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec4 1 - 10 A 1 1 Rated CT secondary current
CTprim4 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint5 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec5 1 - 10 A 1 1 Rated CT secondary current
CTprim5 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint6 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec6 1 - 10 A 1 1 Rated CT secondary current
CTprim6 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint7 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec7 1 - 10 A 1 1 Rated CT secondary current
CTprim7 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint8 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec8 1 - 10 A 1 1 Rated CT secondary current
Table continues on next page

Line distance protection REL670 85


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 3 1MRK 506 370-UEN J
Analog inputs

Name Values (Range) Unit Step Default Description


CTprim8 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint9 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec9 1 - 10 A 1 1 Rated CT secondary current
CTprim9 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint10 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec10 1 - 10 A 1 1 Rated CT secondary current
CTprim10 1 - 99999 A 1 3000 Rated CT primary current
VTsec11 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim11 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec12 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim12 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage

3.5 Monitored data


PID-6531-MONITOREDDATA v3

Table 24: AISVBAS Monitored data


Name Type Values (Range) Unit Description
Status INTEGER 0=Ok - Service value status
1=Error
2=AngRefLow
3=Uncorrelated

PID-3920-MONITOREDDATA v6

Table 25: TRM_12I Monitored data


Name Type Values (Range) Unit Description
STATUS BOOLEAN 0=Ok - Analogue input module status
1=Error

PID-3921-MONITOREDDATA v6

Table 26: TRM_6I_6U Monitored data


Name Type Values (Range) Unit Description
STATUS BOOLEAN 0=Ok - Analogue input module status
1=Error

PID-3922-MONITOREDDATA v6

Table 27: TRM_6I Monitored data


Name Type Values (Range) Unit Description
STATUS BOOLEAN 0=Ok - Analogue input module status
1=Error

86 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 3
Analog inputs

PID-3923-MONITOREDDATA v6

Table 28: TRM_7I_5U Monitored data


Name Type Values (Range) Unit Description
STATUS BOOLEAN 0=Ok - Analogue input module status
1=Error

PID-3924-MONITOREDDATA v6

Table 29: TRM_9I_3U Monitored data


Name Type Values (Range) Unit Description
STATUS BOOLEAN 0=Ok - Analogue input module status
1=Error

PID-6598-MONITOREDDATA v6

Table 30: TRM_10I_2U Monitored data


Name Type Values (Range) Unit Description
STATUS BOOLEAN 0=Ok - Analogue input module status
1=Error

3.6 Operation principle SEMOD55028-5 v9

The direction of a measured current depends on the connection of the CT. The main CTs are
typically star connected and can be connected with the star point towards the object or away
from the object. This information must be set in the IED.

Once the CT direction settings is correctly entered the internal IED convention of the
directionality is defined as follows:

• Positive value of current or power means that the quantity has the direction into the
protected object.
• Negative value of current or power means that the quantity has the direction out from the
protected object.

For directional functions the directional conventions are defined as follows (see Figure 5)

• Forward means the direction is into the object.


• Reverse means the direction is out from the object.

Line distance protection REL670 87


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 3 1MRK 506 370-UEN J
Analog inputs

Definition of direction Definition of direction


for directional functions for directional functions
Reverse Forward Forward Reverse
Protected Object
Line, transformer, etc
e.g. P, Q, I e.g. P, Q, I
Measured quantity is Measured quantity is
positive when flowing positive when flowing
towards the object towards the object

Set parameter Set parameter


CTStarPoint CTStarPoint
Correct Setting is Correct Setting is
"ToObject" "FromObject"

en05000456.vsd
IEC05000456 V1 EN-US

Figure 5: Internal convention of the directionality in the IED


If the settings of the primary CT is correct, that is CTStarPoint set as FromObject or ToObject
according to the plant condition, then a positive quantity always flows towards the protected
object, and a Forward direction always looks towards the protected object.

The settings of the IED is performed in primary values. The ratios of the main CTs and VTs are,
therefore, basic data for the IED. The user has to set the rated secondary and primary currents
and voltages of the CTs and VTs to provide the IED with their rated ratios.

The CT and VT ratio and the name on respective channel is done under Main menu/Hardware/
Analog modules in the Parameter Settings tool or on the HMI.

3.7 Technical data SEMOD55412-1 v1

M16988-1 v11

Table 31: TRM - Energizing quantities, rated values and limits for protection transformer
Description Value
Frequency
Rated frequency fr 50/60 Hz

Operating range fr ± 10%

Current inputs
Rated current Ir 1 or 5 A

Operating range (0-100) x Ir

Thermal withstand 100 × Ir for 1 s *)


30 × Ir for 10 s
10 × Ir for 1 min
4 × Ir continuously

Dynamic withstand 250 × Ir one half wave

Burden < 20 mVA at Ir = 1 A


< 150 mVA at Ir = 5 A

*) max. 350 A for 1 s when COMBITEST test switch is included.


Voltage inputs **)
Rated voltage Ur 110 or 220 V

Operating range 0 - 340 V


Table continues on next page

88 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 3
Analog inputs

Description Value
Thermal withstand 450 V for 10 s
420 V continuously
Burden < 20 mVA at 110 V
< 80 mVA at 220 V
**) all values for individual voltage inputs
Note! All current and voltage data are specified as RMS values at rated frequency

Table 32: TRM - Energizing quantities, rated values and limits for measuring transformer
Description Value
Frequency
Rated frequency fr 50/60 Hz

Operating range fr ± 10%

Current inputs
Rated current Ir 1A 5A

Operating range (0-1.8) × Ir (0-1.6) × Ir

Thermal withstand 80 × Ir for 1 s 65 × Ir for 1 s


25 × Ir for 10 s 20 × Ir for 10 s
10 × Ir for 1 min 8 × Ir for 1 min
1.8 × Ir for 30 min 1.6 × Ir for 30 min
1.1 × Ir continuously 1.1 × Ir continuously

Burden < 200 mVA at Ir < 350 mVA at Ir

Voltage inputs *)
Rated voltage Ur 110 or 220 V

Operating range 0 - 340 V


Thermal withstand 450 V for 10 s
420 V continuously
Burden < 20 mVA at 110 V
< 80 mVA at 220 V
*) all values for individual voltage inputs
Note! All current and voltage data are specified as RMS values at rated frequency

SEMOD53376-2 v6

Table 33: CT and VT circuit connectors


Connector type Rated voltage and current Maximum conductor area
Screw compression type 250 V AC, 20 A 4 mm2 (AWG12)
2 x 2.5 mm2 (2 x AWG14)
Terminal blocks suitable for ring lug 250 V AC, 20 A 4 mm2 (AWG12)
terminals

Line distance protection REL670 89


Technical manual
© Copyright 2017 ABB. All rights reserved
90
1MRK 506 370-UEN J Section 4
Binary input and output modules

Section 4 Binary input and output modules


4.1 Binary input

4.1.1 Binary input debounce filter GUID-AE43976C-E966-484C-AF39-89B2B12F56DC v5

The debounce filter eliminates bounces and short disturbances on a binary input.

A time counter is used for filtering. The time counter is increased once in a millisecond when a
binary input is high, or decreased when a binary input is low. A new debounced binary input
signal is forwarded when the time counter reaches the set DebounceTime value and the
debounced input value is high or when the time counter reaches 0 and the debounced input
value is low. The default setting of DebounceTime is 1 ms.

The binary input ON-event gets the time stamp of the first rising edge, after which the counter
does not reach 0 again. The same happens when the signal goes down to 0 again.

4.1.2 Oscillation filter GUID-41B89E6F-50C3-44BF-9171-3CC82EB5CA15 v4

Binary input wiring can be very long in substations and there are electromagnetic fields from
for example nearby breakers. An oscillation filter is used to reduce the disturbance from the
system when a binary input starts oscillating.

An oscillation counter counts the debounced signal state changes during 1 s. If the counter
value is greater than the set value OscBlock, the input signal is blocked. The input signal is
ignored until the oscillation counter value during 1 s is below the set value OscRelease.

4.1.3 Settings
GUID-07348953-4A72-444B-A31A-030ABEA8E0C4 v1

OscBlock must always be set to a value greater than OscRelease. If this is not
done, oscillation detection will not function correctly, and the resulting
behaviour will be undefined.

4.1.3.1 Setting parameters for binary input modules


PID-3473-SETTINGS v2

Table 34: BIM Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - On Operation Off/On
On
DebounceTime 0.001 - 0.020 s 0.001 0.001 Debounce time for binary inputs
OscBlock 1 - 40 Hz 1 40 Oscillation block limit
OscRelease 1 - 30 Hz 1 30 Oscillation release limit

Line distance protection REL670 91


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 4 1MRK 506 370-UEN J
Binary input and output modules

4.1.3.2 Setting parameters for binary input/output module


PID-4050-SETTINGS v2

Table 35: IOMIN Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - On Binary input/output module in
On operation (On) or not (Off)
DebounceTime 0.001 - 0.020 s 0.001 0.001 Debounce time for binary inputs
OscBlock 1 - 40 Hz 1 40 Oscillation block limit
OscRelease 1 - 30 Hz 1 30 Oscillation release limit

92 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 5
Local Human-Machine-Interface LHMI

Section 5 Local Human-Machine-Interface


LHMI
5.1 Local HMI screen behaviour

5.1.1 Identification
GUID-84392EFF-4D3F-4A67-A6ED-34C6E98574D6 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Local HMI screen behaviour SCREEN - -

5.1.2 Settings
PID-7235-SETTINGS v1

Table 36: SCREEN Non group settings (basic)


Name Values (Range) Unit Step Default Description
DisplayTimeout 1 - 120 Min 1 10 Local HMI display timeout
ContrastLevel -100 - 100 % 10 0 Contrast level for display
DefaultScreen - 0 Default screen
EvListSrtOrder Latest on top - - Latest on top Sort order of event list
Oldest on top
AutoIndicationDRP Off - - Off Automatic indication of disturbance
On report
SubstIndSLD No - - No Substitute indication on single line
Yes diagram
InterlockIndSLD No - - No Interlock indication on single line
Yes diagram
BypassCommands No - - No Enable bypass of commands
Yes

5.2 Local HMI signals

5.2.1 Identification
GUID-03AB7AEE-87D3-4F3C-B6B9-B1EB1B538E38 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Local HMI signals LHMICTRL - -

5.2.2 Function block GUID-A8AC51E9-5BD7-4A80-9576-4816F14DD08D v2

Line distance protection REL670 93


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 5 1MRK 506 370-UEN J
Local Human-Machine-Interface LHMI

LHMICTRL
CLRLEDS HMI-ON
RED-S
YELLOW-S
YELLOW-F
CLRPULSE
LEDSCLRD

IEC09000320-1-en.vsd
IEC09000320 V1 EN-US

Figure 6: LHMICTRL function block

5.2.3 Signals
PID-3992-INPUTSIGNALS v6

Table 37: LHMICTRL Input signals


Name Type Default Description
CLRLEDS BOOLEAN 0 Input to clear the LCD-HMI LEDs

PID-3992-OUTPUTSIGNALS v6

Table 38: LHMICTRL Output signals


Name Type Description
HMI-ON BOOLEAN Backlight of the LCD display is active
RED-S BOOLEAN Red LED on the LCD-HMI is steady
YELLOW-S BOOLEAN Yellow LED on the LCD-HMI is steady
YELLOW-F BOOLEAN Yellow LED on the LCD-HMI is flashing
CLRPULSE BOOLEAN A pulse is provided when the LEDs on the LCD-HMI are
cleared
LEDSCLRD BOOLEAN Active when the LEDs on the LCD-HMI are not active

5.3 Basic part for LED indication module

5.3.1 Identification
GUID-6E36C0BC-F284-4C88-A4A8-9535D3BE8B14 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Basic part for LED indication module LEDGEN - -
Basic part for LED indication HW GRP1_LED1 - - -
module GRP1_LED15

GRP2_LED1 -
GRP2_LED15

GRP3_LED1 -
GRP3_LED15

5.3.2 Function block GUID-BDB5797F-F27E-4FEE-9FDB-1C9E2F572BB6 v3

94 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 5
Local Human-Machine-Interface LHMI

LEDGEN
BLOCK NEWIND
RESET ACK

IEC09000321-1-en.vsd
IEC09000321 V1 EN-US

Figure 7: LEDGEN function block

GRP1_LED1
^HM1L01R
^HM1L01Y
^HM1L01G
IEC09000322 V1 EN-US

Figure 8: GRP1_LED1 function block


The GRP1_LED1 function block is an example. The 15 LEDs in each of the three groups have a
similar function block.

5.3.3 Signals
PID-4114-INPUTSIGNALS v5

Table 39: LEDGEN Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Input to block the operation of the LEDs
RESET BOOLEAN 0 Input to acknowledge/reset the indication LEDs

PID-4114-OUTPUTSIGNALS v5

Table 40: LEDGEN Output signals


Name Type Description
NEWIND BOOLEAN New indication signal if any LED indication input is set
ACK BOOLEAN A pulse is provided when the LEDs are acknowledged

PID-1697-INPUTSIGNALS v18

Table 41: GRP1_LED1 Input signals


Name Type Default Description
HM1L01R BOOLEAN 0 Red indication of LED1, local HMI alarm group 1
HM1L01Y BOOLEAN 0 Yellow indication of LED1, local HMI alarm group 1
HM1L01G BOOLEAN 0 Green indication of LED1, local HMI alarm group 1

5.3.4 Settings
PID-4114-SETTINGS v6

Table 42: LEDGEN Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - On Operation Off/On
On
tRestart 0.0 - 100.0 s 0.1 0.0 Defines the disturbance length
tMax 0.1 - 100.0 s 0.1 1.0 Maximum time for the definition of a
disturbance

Line distance protection REL670 95


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 5 1MRK 506 370-UEN J
Local Human-Machine-Interface LHMI

PID-1697-SETTINGS v18

Table 43: GRP1_LED1 Non group settings (basic)


Name Values (Range) Unit Step Default Description
SequenceType Follow-S - - Follow-S Sequence type for LED 1, local HMI
Follow-F alarm group 1
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
LabelOff 0 - 18 - 1 G1L01_OFF Label string shown when LED 1, alarm
group 1 is off
LabelRed 0 - 18 - 1 G1L01_RED Label string shown when LED 1, alarm
group 1 is red
LabelYellow 0 - 18 - 1 G1L01_YELLOW Label string shown when LED 1, alarm
group 1 is yellow
LabelGreen 0 - 18 - 1 G1L01_GREEN Label string shown when LED 1, alarm
group 1 is green

5.4 LCD part for HMI function keys control module GUID-EECAE7FA-7078-472C-A429-F7607DB884EB v2

5.4.1 Identification
GUID-E6611022-5EA3-420D-ADCD-9D1E7604EFEB v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
LCD part for HMI Function Keys FNKEYMD1 - - -
Control module FNKEYMD5

5.4.2 Function block


GUID-A803A728-5CFC-4606-98E4-793E873B99D4 v3

FNKEYMD1
^LEDCTL1 ^FKEYOUT1
IEC09000327 V1 EN-US

Figure 9: FNKEYMD1 function block


Only the function block for the first button is shown above. There is a similar block for every
function key button.

5.4.3 Signals
PID-7243-INPUTSIGNALS v1

Table 44: FNKEYMD1 Input signals


Name Type Default Description
LEDCTL1 BOOLEAN 0 LED control input for function key

PID-7243-OUTPUTSIGNALS v1

Table 45: FNKEYMD1 Output signals


Name Type Description
FKEYOUT1 BOOLEAN Output controlled by function key

96 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 5
Local Human-Machine-Interface LHMI

5.4.4 Settings
PID-7243-SETTINGS v1

Table 46: FNKEYMD1 Non group settings (basic)


Name Values (Range) Unit Step Default Description
Mode Off - - Off Output operation mode
Toggle
Pulsed
PulseTime 0.001 - 60.000 s 0.001 0.200 Pulse time for output controlled by
LCDFn1
LabelOn 0 - 18 - 1 LCD_FN1_ON Label for LED on state
LabelOff 0 - 18 - 1 LCD_FN1_OFF Label for LED off state
ReqAuthority Off - - On User authorization needed for
On function key operation

PID-7236-SETTINGS v1

Table 47: FNKEYTY1 Non group settings (basic)


Name Values (Range) Unit Step Default Description
Type Off - - Off Function key type
Menu shortcut
Control
MenuShortcut - 0 Menu shortcut for function key

GUID-BCE87D54-C836-40EE-8DA7-779B767059AB v2

For setting ReqAuthority, when users are configured through local or central
account management, the default behavior of the function keys are to only
operate if a user is logged in, and the user have the required rights. This
authentication check can be configured to be bypassed per function key by
changing the ReqAuthority from ON to OFF. To be able to change this, the user
changing it have to have the Security advanced right.

MenuShortcut values are product dependent and created dynamically depending on the
product main menu.

Line distance protection REL670 97


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 5 1MRK 506 370-UEN J
Local Human-Machine-Interface LHMI

5.5 Operation principle

5.5.1 Local HMI AMU0600442 v15

IEC13000239-3-en.vsd
IEC13000239 V3 EN-US

Figure 10: Local human-machine interface


The LHMI of the IED contains the following elements

• Keypad
• Display (LCD)
• LED indicators
• Communication port for PCM600

The LHMI is used for setting, monitoring and controlling.

98 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 5
Local Human-Machine-Interface LHMI

5.5.1.1 Keypad AMU0600428 v19

The LHMI keypad contains push-buttons which are used to navigate in different views or
menus. The push-buttons are also used to acknowledge alarms, reset indications, provide help
and switch between local and remote control mode.

The keypad also contains programmable push-buttons that can be configured either as menu
shortcut or control buttons.

Line distance protection REL670 99


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 5 1MRK 506 370-UEN J
Local Human-Machine-Interface LHMI

24

1
23
2
18
3

19
4

6 20

21

7 22

8 9 10 11 12 13 14 15 16 17

IEC15000157-2-en.vsd

IEC15000157 V2 EN-US

Figure 11: LHMI keypad with object control, navigation and command push-buttons and
RJ-45 communication port

1...5 Function button


6 Close
7 Open
8 Escape
9 Left
10 Down
11 Up
12 Right
13 Key
14 Enter
15 Remote/Local
16 Uplink LED
17 Not in use
18 Multipage
19 Menu
20 Clear
21 Help

100 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 5
Local Human-Machine-Interface LHMI

22 Communication port
23 Programmable indication LEDs
24 IED status LEDs

5.5.1.2 Display GUID-55739D4F-1DA5-4112-B5C7-217AAF360EA5 v13

The LHMI includes a graphical monochrome liquid crystal display (LCD) with a resolution of 320
x 240 pixels. The character size can vary. The amount of characters and rows fitting the view
depends on the character size and the view that is shown.

The display view is divided into four basic areas.

IEC15000270-1-en.vsdx

IEC15000270 V1 EN-US

Figure 12: Display layout

1 Path
2 Content
3 Status
4 Scroll bar (appears when needed)

Line distance protection REL670 101


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 5 1MRK 506 370-UEN J
Local Human-Machine-Interface LHMI

• The path shows the current location in the menu structure. If the path is too long to be
shown, it is truncated from the beginning, and the truncation is indicated with three dots.
• The content area shows the menu content.
• The status area shows the current IED time, the user that is currently logged in and the
object identification string which is settable via the LHMI or with PCM600.
• If text, pictures or other items do not fit in the display, a vertical scroll bar appears on the
right. The text in content area is truncated from the beginning if it does not fit in the
display horizontally. Truncation is indicated with three dots.

IEC15000138-1-en.vsdx

IEC15000138 V1 EN-US

Figure 13: Truncated path


The number after : (colon sign) at the end of the function instance, for example, 1 in SMAI1:1,
indicates the number of that function instance.

The function key button panel shows on request what actions are possible with the function
buttons. Each function button has a LED indication that can be used as a feedback signal for
the function button control action. The LED is connected to the required signal with PCM600.

102 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 5
Local Human-Machine-Interface LHMI

IEC13000281-1-en.vsd
GUID-C98D972D-D1D8-4734-B419-161DBC0DC97B V1 EN-US

Figure 14: Function button panel


The indication LED panel shows on request the alarm text labels for the indication LEDs. Three
indication LED pages are available.

IEC13000240-1-en.vsd
GUID-5157100F-E8C0-4FAB-B979-FD4A971475E3 V1 EN-US

Figure 15: Indication LED panel


The function button and indication LED panels are not visible at the same time. Each panel is
shown by pressing one of the function buttons or the Multipage button. Pressing the ESC
button clears the panel from the display. Both panels have a dynamic width that depends on
the label string length.

5.5.1.3 LEDs AMU0600427 v15

The LHMI includes three status LEDs above the display: Ready, Start and Trip.

There are 15 programmable indication LEDs on the front of the LHMI. Each LED can indicate
three states with the colors: green, yellow and red. The texts related to each three-color LED
are divided into three panels.

There are 3 separate panels of LEDs available. The 15 physical three-color LEDs in one LED
group can indicate 45 different signals. Altogether, 135 signals can be indicated since there are
three LED groups. The LEDs are lit according to priority, with red being the highest and green

Line distance protection REL670 103


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 5 1MRK 506 370-UEN J
Local Human-Machine-Interface LHMI

the lowest priority. For example, if on one panel there is an indication that requires the green
LED to be lit, and on another panel there is an indication that requires the red LED to be lit, the
red LED takes priority and is lit. The LEDs can be configured with PCM600 and the operation
mode can be selected with the LHMI or PCM600.

Information panels for the indication LEDs are shown by pressing the Multipage button.
Pressing that button cycles through the three pages. A lit or un-acknowledged LED is indicated
with a highlight. Such lines can be selected by using the Up/Down arrow buttons. Pressing the
Enter key shows details about the selected LED. Pressing the ESC button exits from
information pop-ups as well as from the LED panel as such.

The Multipage button has a LED. This LED is lit whenever any LED on any panel is lit. If there are
un-acknowledged indication LEDs, then the Multipage LED blinks. To acknowledge LEDs, press
the Clear button to enter the Reset menu (refer to description of this menu for details).

There are two additional LEDs which are next to the control buttons and . These
LEDs can indicate the status of two arbitrary binary signals by configuring the
OPENCLOSE_LED function block. For instance, OPENCLOSE_LED can be connected to a circuit
breaker to indicate the breaker open/close status on the LEDs.

IEC16000076-1-en.vsd
IEC16000076 V1 EN-US

Figure 16: OPENCLOSE_LED connected to SXCBR

5.5.2 LED configuration alternatives

5.5.2.1 Functionality GUID-1A03E0EF-C10F-4797-9D9F-5CCA86CA29EB v5

The function blocks LEDGEN and GRP1_LEDx, GRP2_LEDx and GRP3_LEDx (x=1-15) controls and
supplies information about the status of the indication LEDs. The input and output signals of
the function blocks are configured with PCM600. The input signal for each LED is selected
individually using SMT or ACT. Each LED is controlled by the GRPn_LEDx (n=1-3) function block
that controls the color and the operating mode.

Each indication LED on local HMI can be set individually to operate in 6 different sequences;
two as follow type and four as latch type. Two of the latching sequence types are intended to
be used as a protection indication system, either in collecting or restarting mode, with reset
functionality. The other two are intended to be used as signalling system in collecting mode
with acknowledgment functionality.

5.5.2.2 Status LEDs GUID-4822DF9C-E343-442B-B3F1-3FA8CD8DF234 v4

There are three status LEDs above the LCD in front of the IED: green, yellow and red.

104 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 5
Local Human-Machine-Interface LHMI

The green LED has a fixed function that presents the healthy status of the IED. The yellow and
red LEDs are user configured. The yellow LED can be used to indicate that a disturbance report
is triggered (steady) or that the IED is in test mode (flashing). The red LED can be used to
indicate a trip command.

Here is a typical configuration of the status LEDs:

• Green LED: unlit > no power; blinking > startup or abnormal situation (IED is not in
service); steady > IED is in service
• Yellow LED: unlit > no attention required; blinking > IED is in Testmode (IED is not in
normal service); steady > at least one of the signals configured to turn the yellow LED on
has been active
• Red LED: unlit > no attention required; blinking > user performs a common write from
PCM600; steady > at least one of the signals configured to turn the red LED on has been
active

The yellow and red status LEDs are configured in the disturbance recorder function, DRPRDRE,
by connecting a start or trip signal from the actual function to a BxRBDR binary input function
block using the PCM600, and configuring the setting to Off, Start or Trip for that particular
signal.

5.5.2.3 Indication LEDs

Operating modes GUID-B67F1ED3-900B-4D34-8EEB-A3005999CE50 v4

Collecting mode

• LEDs that are used in the collecting mode of operation are accumulated continuously until
the unit is acknowledged manually. This mode is suitable when the LEDs are used as a
simplified alarm system. When all three inputs (red, yellow and green) are connected to
different sources of events for the same function block, collecting mode shows the
highest priority LED color that was activated since the latest acknowledgment was made.
If a number of different indications were made since the latest acknowledgment, it is not
possible to get a clear view of what triggered the latest event without looking at the
sequence of events list. A condition for getting the sequence of events is that the signals
have been engineered in the disturbance recorder.

Re-starting mode

• In the re-starting mode of operation each new start resets all previous active LEDs and
activates only those which appear during one disturbance. Only LEDs defined for re-
starting mode with the latched sequence type 6 (LatchedReset-S) will initiate a reset and a
restart at a new disturbance. A disturbance is defined to end a settable time after the
reset of the activated input signals or when the maximum time limit has elapsed. In
sequence 6, the restarting or reset mode means that upon occurrence of any new event,
all previous indications will be reset. This facilitates that only the LED indications related
to the latest event is shown.

Acknowledgment/reset GUID-E6727E8F-C28B-4295-AE21-BC5643363805 v3

• From local HMI


• The active LED indications can be acknowledged/reset manually. Manual
acknowledgment and manual reset have the same meaning and is a common signal
for all the operating sequences and LEDs. The function is positive edge triggered,
not level triggered. The acknowledgment/reset is performed via the button and
menus on the LHMI.

Line distance protection REL670 105


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 5 1MRK 506 370-UEN J
Local Human-Machine-Interface LHMI

• From function input


• The active LED indications can also be acknowledged/reset via an input, CLRLEDS, to
the function block LHMICTRL. This input can for example be configured to a binary
input operated from an external push button or a function button. The function is
positive edge triggered, not level triggered. This means that even if the button is
continuously pressed, the acknowledgment/reset only affects indications active at
the moment when the button is first pressed.

• Automatic reset
• The automatic reset can only be performed for LED indications defined for re-
starting mode with the latched sequence type 6 (LatchedReset-S). When the
automatic reset of the LEDs has been performed, still persisting indications will be
indicated with a steady light.

Operating sequence GUID-DFCA880B-308C-4334-94DF-97C7765E8C13 v5


The sequences can be of type Follow or Latched. For the Follow type, the LED follows the input
signal completely. For the Latched type, each LED latches to the corresponding input signal
until it is reset.

The figures below show the function of available sequences selectable for each LED separately.
The following 6 sequences are available:

• Sequence 1: Follow-S
• Sequence 2: Follow-F
• Sequence 3: LatchedAck-F-S
• Sequence 4: LatchedAck-S-F
• Sequence 5: LatchedColl-S
• Sequence 6: LatchedReset-S

For sequence 1 and 2, which are of the Follow type, the acknowledgment (Ack ) /reset function
is not applicable because the indication shown by the LED follows its input signal. Sequence 3
and 4, which are of the Latched type with acknowledgement, are only working in collecting
(Coll) mode. Sequence 5 is working according to Latched type and collecting mode while
Sequence 6 is working according to Latched type and re-starting (Reset) mode. The letters S
and F in the sequence names have the meaning S = Steady and F = Flash.

At the activation of the input signal to any LED, the indication on the corresponding LED
obtains a color that corresponds to the activated input, and operates according to the
selected sequence diagrams shown below.

In the sequence diagrams the different statuses of the LEDs are shown using the following
symbols:

= No indication = Steady light = Flash

G= Green Y= Yellow R= Red


IEC09000311.vsd
IEC09000311 V1 EN-US

Figure 17: Symbols used in the sequence diagrams

Sequence 1 (Follow-S) SEMOD56072-39 v4


This sequence follows the corresponding input signals all the time with a steady light. It does
not react on acknowledgment or reset. Every LED is independent of the other LEDs in its
operation.

106 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 5
Local Human-Machine-Interface LHMI

Activating
signal

LED

IEC01000228_2_en.vsd
IEC01000228 V2 EN-US

Figure 18: Operating Sequence 1 (Follow-S)


GUID-107FE952-3B4C-4C01-831A-3147E652327C v4
If inputs for two or more colors are active at the same time to the same LED, the priority color
it shows is in accordance with the color described above. An example of the operation when
two colors are activated in parallel to the same LED is shown in figure19.

Activating
signal GREEN

Activating
signal RED

LED G G R G

IEC09000312_1_en.vsd
IEC09000312 V1 EN-US

Figure 19: Operating sequence 1, two colors

Sequence 2 (Follow-F) SEMOD56072-47 v2


This sequence is the same as Sequence 1, Follow-S, but the LEDs are flashing instead of
showing steady light.

Sequence 3 LatchedAck-F-S SEMOD56072-50 v2


This sequence has a latched function and works in collecting mode. Every LED is independent
of the other LEDs in its operation. At the activation of the input signal, the indication starts
flashing. After acknowledgment the indication disappears if the signal is not present any
more. If the signal is still present after acknowledgment it gets a steady light.

Activating
signal

LED

Acknow.
en01000231.vsd
IEC01000231 V1 EN-US

Figure 20: Operating Sequence 3 LatchedAck-F-S


GUID-CC607709-5344-4C88-AA97-6395FD335E55 v5

The sequence described below is valid only if the same function block is used
for all three colour LEDs.

When an acknowledgment is performed, all indications that appear before the indication with
higher priority has been reset, will be acknowledged, independent of if the low priority
indication appeared before or after acknowledgment. In figure 21 it is shown the sequence

Line distance protection REL670 107


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 5 1MRK 506 370-UEN J
Local Human-Machine-Interface LHMI

when a signal of lower priority becomes activated after acknowledgment has been performed
on a higher priority signal. The low priority signal will be shown as acknowledged when the
high priority signal resets.

Activating
signal GREEN

Activating
signal RED

R R G
LED

Acknow
IEC09000313_1_en.vsd
IEC09000313 V1 EN-US

Figure 21: Operating Sequence 3 (LatchedAck-F-S), 2 colors involved


GUID-A652A49D-F016-472D-8D38-6D3E75DAB1DB v3
If all three signals are activated the order of priority is still maintained. Acknowledgment of
indications with higher priority will acknowledge also low priority indications, which are not
visible according to figure 22.

Activating
signal GREEN

Activating
signal YELLOW
Activating
signal RED

LED G Y R R Y

Acknow.
IEC09000314-1-en.vsd
IEC09000314 V1 EN-US

Figure 22: Operating sequence 3, three colors involved, alternative 1


GUID-071B9EB5-A1D2-49C5-9458-4D21B7E068BE v3
If an indication with higher priority appears after acknowledgment of a lower priority
indication the high priority indication will be shown as not acknowledged according to figure
23.

108 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 5
Local Human-Machine-Interface LHMI

Activating
signal GREEN

Activating
signal YELLOW
Activating
signal RED

LED G G R R Y

Acknow.
IEC09000315-1-en.vsd
IEC09000315 V1 EN-US

Figure 23: Operating sequence 3, three colors involved, alternative 2

Sequence 4 (LatchedAck-S-F) SEMOD56072-64 v1


This sequence has the same functionality as sequence 3, but steady and flashing light have
been alternated.

Sequence 5 LatchedColl-S SEMOD56072-67 v4


This sequence has a latched function and works in collecting mode. At the activation of the
input signal, the indication will light up with a steady light. The difference to sequence 3 and 4
is that indications that are still activated will not be affected by the reset that is, immediately
after the positive edge of the reset has been executed a new reading and storing of active
signals is performed. Every LED is independent of the other LEDs in its operation.

Activating
signal

LED

Reset

IEC01000235_2_en.vsd
IEC01000235 V2 EN-US

Figure 24: Operating Sequence 5 LatchedColl-S


GUID-4D52D221-F54F-4966-95B1-6ED6C536CEC9 v3
That means if an indication with higher priority has reset while an indication with lower
priority still is active at the time of reset, the LED will change color according to figure25.

Line distance protection REL670 109


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 5 1MRK 506 370-UEN J
Local Human-Machine-Interface LHMI

Activating
signal GREEN

Activating
signal RED

R G
LED

Reset
IEC09000316_1_en.vsd
IEC09000316 V1 EN-US

Figure 25: Operating sequence 5, two colors

Sequence 6 LatchedReset-S SEMOD56072-75 v4


In this mode all activated LEDs, which are set to Sequence 6 (LatchedReset-S), are
automatically reset at a new disturbance when activating any input signal for other LEDs set to
Sequence 6 LatchedReset-S. Also in this case indications that are still activated will not be
affected by manual reset, that is, immediately after the positive edge of that the manual reset
has been executed a new reading and storing of active signals is performed. LEDs set for
sequence 6 are completely independent in its operation of LEDs set for other sequences.

Timing diagram for sequence 6 SEMOD56072-86 v4


Figure 26 shows the timing diagram for two indications within one disturbance.

Disturbance
tRestart

Activating
signal 1

Activating
signal 2

LED 1

LED 2

Automatic
reset

Manual
reset
IEC01000239_2-en.vsd
IEC01000239 V2 EN-US

Figure 26: Operating sequence 6 (LatchedReset-S), two indications within same


disturbance
Figure 27 shows the timing diagram for a new indication after tRestart time has elapsed.

110 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 5
Local Human-Machine-Interface LHMI

Disturbance Disturbance

tRestart tRestart

Activating
signal 1

Activating
signal 2

LED 1

LED 2

Automatic
reset

Manual
reset
IEC01000240_2_en.vsd
IEC01000240 V2 EN-US

Figure 27: Operating sequence 6 (LatchedReset-S), two different disturbances


Figure 28 shows the timing diagram when a new indication appears after the first one has
reset but before tRestart has elapsed.

Disturbance

tRestart

Activating
signal 1

Activating
signal 2

LED 1

LED 2

Automatic
reset

Manual
reset
IEC01000241_2_en.vsd
IEC01000241 V2 EN-US

Figure 28: Operating sequence 6 (LatchedReset-S), two indications within same


disturbance but with reset of activating signal between
Figure 29 shows the timing diagram for manual reset.

Line distance protection REL670 111


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 5 1MRK 506 370-UEN J
Local Human-Machine-Interface LHMI

Disturbance

tRestart

Activating
signal 1

Activating
signal 2

LED 1

LED 2

Automatic
reset

Manual
reset
IEC01000242_2_en.vsd
IEC01000242 V2 EN-US

Figure 29: Operating sequence 6 (LatchedReset-S), manual reset

5.5.3 Function keys

5.5.3.1 Functionality GUID-BED38E9A-C90D-4B7F-AA20-42821C4F6A1C v3

Local Human-Machine-Interface (LHMI) has five function buttons, directly to the left of the
LCD, that can be configured either as menu shortcut or control buttons. Each button has an
indication LED that can be configured in the application configuration.

When used as a menu shortcut, a function button provides a fast way to navigate between
default nodes in the menu tree. When used as a control, the button can control a binary signal.

5.5.3.2 Operation principle GUID-977C3829-B19B-457E-8A4D-45317226EF22 v3

Each output on the FNKEYMD1 - FNKEYMD5 function blocks can be controlled from the LHMI
function keys. By pressing a function button on the LHMI, the output status of the actual
function block will change. These binary outputs can in turn be used to control other function
blocks, for example, switch control blocks, binary I/O outputs etc.

FNKEYMD1 - FNKEYMD5 function block also has a number of settings and parameters that
control the behavior of the function block. These settings and parameters are normally set
using the PST.

Operating sequence GUID-84CA7C61-4F83-4F86-A07F-BF9EC4E309BF v5


The operation mode is set individually for each output, either OFF, TOGGLE or PULSED.

Setting OFF

This mode always sets the outputs to a low value (0).

112 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 5
Local Human-Machine-Interface LHMI

Input value

Output value

IEC09000330-2-en.vsd

IEC09000330 V2 EN-US

Figure 30: Sequence diagram for setting OFF


Setting TOGGLE

In this mode the output toggles each time the function key has been pressed for more than
500ms. Note that the input attribute is reset each time the function block executes. The
function block execution is marked with a dotted line below.

Input value
500ms 500ms 500ms

Output value

IEC09000331_1_en.vsd

IEC09000331 V2 EN-US

Figure 31: Sequence diagram for setting TOGGLE


Setting PULSED

In this mode the output sets high (1) when the function key has been pressed for more than
500ms and remains high according to set pulse time. After this time the output will go back to
0. The input attribute is reset when the function block detects it being high and there is no
output pulse.

Note that the third positive edge on the input attribute does not cause a pulse, since the edge
was applied during pulse output. A new pulse can only begin when the output is zero; else the
trigger edge is lost.

Input value
500ms 500ms 500ms 500ms

pulse time pulse time pulse time


Output value

IEC09000332_2_en.vsd

IEC09000332 V2 EN-US

Figure 32: Sequence diagram for setting PULSED

Input function GUID-8EA4AE21-7A74-403A-84AE-D5CEF9292A63 v2


All function keys work the same way: When the LHMI is configured so that a certain function
button is of type CONTROL, then the corresponding input on this function block becomes
active, and will light the yellow function button LED when high. This functionality is active even
if the function block operation setting is set to off. It has been implemented this way for

Line distance protection REL670 113


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 5 1MRK 506 370-UEN J
Local Human-Machine-Interface LHMI

safety reasons; the idea is that the function key LEDs should always reflect the actual status of
any primary equipment monitored by these LEDs.

5.5.3.3 Enabling and Disabling Authority on Function keys GUID-27413370-00F4-477D-886F-30359C788B55 v1

When users are configured through local or central account management, the default behavior
of the function keys are to only operate if a user is logged in, and the user have the required
rights. This authentication check can be configured to be bypassed per function key by
changing the ReqAuthority from ON to OFF. To be able to change this, the user changing it
have to have the Security advanced right.

Authority can be disabled using parameter Authority. Each function key has the parameter
Authority, which can be enabled or disabled using LHMI or PCM 600. User must have Security
Advanced rights to configure the Authority parameter of the function key.

The possible values for the Authority parameter are as below:

• Enabled: Requires authentication


• Disabled: No user authentication

If there is no User Account Management or Central Account Management


configured in the IED then this parameter has no effect and the function key
can be operated without any authentication.

114 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 6
Wide area measurement system

Section 6 Wide area measurement system


6.1 C37.118 Phasor Measurement Data Streaming Protocol
Configuration PMUCONF GUID-747C6AD7-E6A1-466E-92D1-68865681F92F v1

6.1.1 Identification
GUID-1E140EA0-D198-443A-B445-47CEFD2E6134 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Configuration parameters for IEEE PMUCONF - -
1344 and C37.118 protocol

6.1.2 Functionality GUID-33694C62-A109-4D8F-9063-CEFA5D0E78BC v4

The IED supports the following IEEE synchrophasor standards:

• IEEE 1344-1995 (Both measurements and data communication)


• IEEE Std C37.118-2005 (Both measurements and data communication)
• IEEE Std C37.118.1–2011 and C37.118.1a-2014 (Measurements)
• IEEE Std C37.118.2-2011 (Data communication)

PMUCONF contains the PMU configuration parameters for both IEEE C37.118 and IEEE 1344
protocols. This means all the required settings and parameters in order to establish and define
a number of TCP and/or UDP connections with one or more PDC clients (synchrophasor client).
This includes port numbers, TCP/UDP IP addresses, and specific settings for IEEE C37.118 as
well as IEEE 1344 protocols.

6.1.3 Operation principle GUID-2608FBC4-9036-476A-942B-13452019BC11 v2

The Figure 33 demonstrates the communication configuration diagram. As can be seen, the
IED can support communication with maximum 8 TCP clients and 6 UDP client groups,
simultaneously. Every client can communicate with only one instance of the two available
PMUREPORT function block instances at a time. It means that one client cannot communicate
with both PMUREPORT:1 and PMUREPORT:2 at the same time. However, multiple clients can
communicate with the same instance of PMUREPORT function block at the same time. For TCP
clients, each client can decide to communicate with an existing instance of PMUREPORT by
knowing the corresponding PMU ID for that PMUREPORT instance. Whereas, for UDP clients,
the PMUREPORT instance for each UDP channel is defined by the user in the PMU and the client
has to know the PMU ID corresponding to that instance in order to be able to communicate.
More information is available in the sections Short guidance for the use of TCP and Short
guidance for the use of UDP.

Line distance protection REL670 115


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 506 370-UEN J
Wide area measurement system

IED
PMU ID

1344/C37.118
PMUREPORT: 1 PMUREPORT: 2 TCP Client_1
1344/C37.118
TCP Client_2
1344/C37.118
TCP Client_3
PMU ID: X
1344/C37.118
TCP IP TCP Client_4
PMU ID: Y 1344/C37.118
TCP Port TCP Client_5
1344/C37.118 TCP Client_6
1344/C37.118 TCP Client_7
1344/C37.118 TCP Client_8

PMU ID

PMUREPORT Instance: 1 or 2 1344/C37.118


UDP 1 Unicast/Multicast
UDP Client Group_1

PMUREPORT Instance: 1 or 2 1344/C37.118


UDP 2 Unicast/Multicast
UDP Client Group_2

PMUREPORT Instance: 1 or 2 1344/C37.118


UDP 3 Unicast/Multicast
UDP Client Group_3

PMUREPORT Instance: 1 or 2 1344/C37.118


UDP 4 Unicast/Multicast
UDP Client Group_4

PMUREPORT Instance: 1 or 2 1344/C37.118


UDP 5 Unicast/Multicast
UDP Client Group_5

PMUREPORT Instance: 1 or 2 1344/C37.118


UDP 6 Unicast/Multicast
UDP Client Group_6

IEC140000117-1.en.vsd
IEC140000117 V2 EN-US

Figure 33: The communication configuration (PMUCONF) structure in the IED

6.1.3.1 IEEE C37.118 Message Framework GUID-B8CC9D53-1CC5-43CC-9AF0-9B4D8CDC1922 v2

Four message types are defined in IEEE C37.118 standard: data, configuration, header, and
command frames. The first three message types are transmitted from the PMU/PDC that
serves as the data source, and the last one (command frame) is received by the PMU/PDC.

These four message types are defined in IEEE C37.118 standard as follows:

• Data messages are the measurements made by a PMU.


• Configuration is a machine-readable message describing the data types, calibration
factors, and other metadata for the data that the PMU/PDC sends.
• Header information is human readable descriptive information sent from the PMU/PDC
but provided by the user.

There is a default header file, named "ieee1344header.txt", located in the "tools" folder in the
IED. The user is allowed to access and update this text file and write it back to the IED using a
FTP client (e.g. Filezilla).

If the user-defined (updated) header file is larger than 1400 bytes, then it will be truncated to
1400 bytes in both IEEE C37.118 and IEEE1344 protocols.

Both PMU reporting instances are using the same header file (ieee1344header.txt) and this
header file is used for both IEEE C37.118 and IEEE1344 protocols.

• Commands are machine-readable codes sent to the PMU/PDC for control or


configuration.

116 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 6
Wide area measurement system

6.1.3.2 Short guidance for use of TCP GUID-700B2618-3719-4C17-A1F8-3B8F5834FE95 v3

Port 7001 is used by the SPA on TCP/IP (field service tool). If the port is used for
any other protocol, for example C37.118, the SPA on TCP/IP stops working.

The IED supports 8 concurrent TCP connections using IEEE1344 and/or C37.118 protocol. The
following parameters are used to define the TCP connection between the IED and the TCP
clients:

1. 1344TCPport– TCP port for control of IEEE 1344 data for TCP clients
2. C37.118TCPport – TCP port for control of IEEE C37.118 data for TCP clients

As can be seen, there are two separate parameters in the IED for selecting port numbers for
TCP connections; one for IEEE1344 protocol (1344TCPport) and another one for C37.118
protocol (C37.118 TCPport). Client can communicate with the IED over IEEE1344 protocol using
the selected TCP port defined in 1344TCPport, and can communicate with the IED over IEEE
C37.118 protocol using the selected TCP port number in C37.118TCPport.

All the frames (the header frame, configuration frame, command frame and data frame) are
communicated over the same TCP port. The client can request (by sending a command frame)
a configuration and/or header via the TCP channel and the requested configuration and/or
header will be sent back to the client (as Configuration frame/Header frame) over the same
TCP channel.

Once the TCP client connects to the IED, the client has to necessarily send a command frame
to start a communication. As shown in Figure 33, the IED can support 2 PMUREPORT instances
and the client has to specify the PMU ID Code in order to know which PMUREPORT data needs
to be sent out to that client. In this figure, X and Y are referring to the user-defined PMU ID
Codes for PMUREPORT instances 1 or 2, respectively. It is up to the TCP client to decide which
PMUREPORT function block shall communicate with that client. Upon successful reception of
the first command by the IED, the PMU ID will be extracted out of the command; if there is a
PMUREPORT instance configured in the IED with matching PMU ID, then the client connection
over TCP with the IED will be established and further communication will take place.
Otherwise, the connection will be terminated and the TCPCtrlCfgErrCnt is incremented in the
PMU Diagnostics on the Local HMI under Main menu/Diagnostics/Communication/PMU
diagnostics/PMUSTATUS:1

It is possible to turn off/on the TCP data communication by sending a IEEE1344 or C37.118
command frame remotely from the client to the PMU containing RTDOFF/RTDON command.

At any given point of time maximum of 8 TCP clients can be connected to the IED for
IEEE1344/C37.118 protocol. If there is an attempt made by the 9th client, the connection to the
new client will be terminated without influencing the connection of the other clients already
connected. A list of active clients can be seen on the Local HMI in the diagnostics menu under
Main menu/Diagnostics/Communication/PMU diagnostics/PMUSTATUS:1

6.1.3.3 Short guidance for use of UDP GUID-F5BCBBF7-4EED-4E79-9E86-AF046D201BB1 v3

The IED supports maximum of 6 concurrent UDP streams. They can be individually configured
to send IEEE1344 or C37.118 data frames as unicast / multicast. Note that [x] at the end of
each parameter is referring to the UDP stream number (UDP client group) and is a number
between 1 and 6. Each of the 6 UDP groups in the IED has the following settings:

1. SendDataUDP[x] – Enable / disable UDP data stream


2. ProtocolOnUDP[x] – Send IEEE1344 or C37.118 on UDP
3. PMUReportUDP[x] – Instance number of PMUREPORT function block that must send data
on this UDP stream (UDP client group[x])

Line distance protection REL670 117


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 506 370-UEN J
Wide area measurement system

4. UDPDestAddres[x] – UDP destination address for UDP client group[x] (unicast / multicast
address range)
5. UDPDestPort[x] – UDP destination port number for UDP client group[x]
6. TCPportUDPdataCtrl[x] – TCP port to control of data sent over UDP client group[x], i.e. to
receive commands and send configuration frames
7. SendCfgOnUDP[x] – Send configuration frame 2 (CFG-2) on UDP for client group[x]

It is possible to turn off/on the UDP data communication either by setting the parameter
SendDataUDP[x] to Off/On locally in the PMU or by sending a C37.118 or IEEE1344 command
frame (RTDOFF/RTDON) remotely from the client to the PMU as defined in IEEE 1344/C37.118
standard.

However, such a remote control to stop the streams from the client is only possible when the
parameter SendDataUDP[x] is set to SetByProtocol. The command RTDOFF/RTDON sent by
the client is stored in the IED, i.e. if the IED is rebooted for some reason, the state of the
stream will remain the same.

If the parameter SendDataUDP[x] is set toOn the RTDOFF/RTDON commands received from
the clients are ignored in the IED.

It is recommended not to set the parameter SendDataUDP[x] to SetByProtocol in case of a


multicast. This is because if one of the clients sends the RTDOFF command, all the clients will
stop receiving the frames.

The UDP implementation in the IED is a UDP_TCP. This means that by default, only the data
frames are sent out on UDP stream and the header frame, configuration frame and command
frame are sent over TCP. This makes the communication more reliable especially since
commands are sent over TCP which performs request/acknowledgment exchange to ensure
that no data (command in this case) is lost.

However, by setting the parameter SendCfgOnUDP[x] to On, the configuration frame 2 (CFG-2)
of IEEEC37.118 data stream is cyclically sent on the corresponding UDP stream (UDP client
group[x]) once per minute. This is useful in case of multicast UDP data stream when a lot of
PMU clients are receiving the same UDP stream from the same UDP group (UDP client
group[x]).

As shown in Figure 33, there are maximum 2 instances of PMUREPORT function blocks
available in the IED. Each UDP client group[x] can only connect to one of the PMUREPORT
instances at the same time. This is defined in the PMU by the parameter PMUReportUDP[x]
which is used to define the instance number of PMUREPORT function block that must send
data on this UDP stream (UDP client group[x]).

The data streams in the IED can be sent as unicast or as multicast. The user-defined IP address
set in the parameter UDPDestAddress[x] for each UDP stream defines if it is a Unicast or
Multicast. The address range 224.0.0.0 to 239.255.255.255 (Class D IP addresses) is treated as
multicast. Any other IP address outside this range is treated as unicast and the UDP data will
be only sent to that specific unicast IP address. In addition to UDPDestAddress[x] parameter,
UDPDestPort[x] parameter is used to define the UDP destination port number for UDP client
group[x].

In case of multicast IP, it will be the network switches and routers that take care of replicating
the packet to reach multiple receivers. Multicast mechanism uses network infrastructure
efficiently by requiring the IED to send a packet only once, even if it needs to be delivered to a
large number of receivers.

If there are more than one UDP client group defined as multicast, the user shall set different
multicast IP addresses for each UDP group.

The PMU clients receiving the UDP frames can also connect to the IED to request (command
frame) config frame 1, config frame 2, config frame 3, or header frame, and to disable/enable
real time data. This can be done by connecting to the TCP port selected in

118 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 6
Wide area measurement system

TCPportUDPdataCtrl[x] for each UDP group. This connection is done using TCP. The IED allows
4 concurrent client connections for every TCPportUDPdataCtrl[x] port (for each UDP client
group[x]).

If the client tries to connect on TCPportUDPdataCtrl[x] port using a PMU-ID other than what is
configured for that PMUREPORT instance (PMUReportUDP[x]), then that client is immediately
disconnected and the UDPCtrlCfgErrCnt is incremented in PMU Diagnostics on LHMI at Main
menu/Diagnostics/Communication/PMU diagnostics/PMUSTATUS:1

Even if the parameter SendDataUDP[x] is set to Off it is still possible for the clients to connect
on the TCP port and request the configuration frames.

6.1.4 Settings SEMOD119927-1 v2

PID-6710-SETTINGS v4

Table 48: PMUCONF Non group settings (basic)


Name Values (Range) Unit Step Default Description
1344TCPport 1024 - 65534 - 1 4711 TCP port for control of IEEE 1344 data
for TCP clients
C37.118TCPport 1024 - 65534 - 1 4712 TCP port for control of IEEE C37.118
data for TCP clients
TCPportUDPdataCtrl1 1024 - 65534 - 1 4713 TCP port for control of data sent over
UDP client group1
SendDataUDP1 Off - - Off Send data to UDP client group1
On
SetByProtocol
ProtocolOnUDP1 IEEE1344 - - C37.118 Select protocol for UDP client group1
C37.118
PMUReportUDP1 1-2 - 1 1 PMUREPORT instance used for UDP
client group1
UDPDestAddres1 0 - 16 IP 1 234.5.6.7 UDP destination address for UDP
Address client group1
UDPDestPort1 1024 - 65534 - 1 8910 UDP destination port for UDP client
group1
SendCfgOnUDP1 Off - - Off Send Config frame2 on UDP for
On group1
TCPportUDPdataCtrl2 1024 - 65534 - 1 4714 TCP port for control of data sent over
UDP client group2
SendDataUDP2 Off - - Off Send data to UDP client group2
On
SetByProtocol
ProtocolOnUDP2 IEEE1344 - - C37.118 Select protocol for UDP client group2
C37.118
PMUReportUDP2 1-2 - 1 1 PMUREPORT instance used for UDP
client group2
UDPDestAddres2 0 - 16 IP 1 234.5.6.8 UDP destination address for UDP
Address client group2
UDPDestPort2 1024 - 65534 - 1 8911 UDP destination port for UDP client
group2
SendCfgOnUDP2 Off - - Off Send Config frame2 on UDP for
On group2
TCPportUDPdataCtrl3 1024 - 65534 - 1 4715 TCP port for control of data sent over
UDP client group3
Table continues on next page

Line distance protection REL670 119


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 506 370-UEN J
Wide area measurement system

Name Values (Range) Unit Step Default Description


SendDataUDP3 Off - - Off Send data to UDP client group3
On
SetByProtocol
ProtocolOnUDP3 IEEE1344 - - C37.118 Select protocol for UDP client group3
C37.118
PMUReportUDP3 1-2 - 1 1 PMUREPORT instance used for UDP
client group3
UDPDestAddres3 0 - 16 IP 1 234.5.6.9 UDP destination address for UDP
Address client group3
UDPDestPort3 1024 - 65534 - 1 8912 UDP destination port for UDP client
group3
SendCfgOnUDP3 Off - - Off Send Config frame2 on UDP for
On group3
TCPportUDPdataCtrl4 1024 - 65534 - 1 4716 TCP port for control of data sent over
UDP client group4
SendDataUDP4 Off - - Off Send data to UDP client group4
On
SetByProtocol
ProtocolOnUDP4 IEEE1344 - - C37.118 Select protocol for UDP client group4
C37.118
PMUReportUDP4 1-2 - 1 1 PMUREPORT instance used for UDP
client group4
UDPDestAddres4 0 - 16 IP 1 234.5.6.10 UDP destination address for UDP
Address client group4
UDPDestPort4 1024 - 65534 - 1 8913 UDP destination port for UDP client
group4
SendCfgOnUDP4 Off - - Off Send Config frame2 on UDP for
On group4
TCPportUDPdataCtrl5 1024 - 65534 - 1 4717 TCP port for control of data sent over
UDP client group5
SendDataUDP5 Off - - Off Send data to UDP client group5
On
SetByProtocol
ProtocolOnUDP5 IEEE1344 - - C37.118 Select protocol for UDP client group5
C37.118
PMUReportUDP5 1-2 - 1 1 PMUREPORT instance used for UDP
client group5
UDPDestAddres5 0 - 16 IP 1 234.5.6.11 UDP destination address for UDP
Address client group5
UDPDestPort5 1024 - 65534 - 1 8914 UDP destination port for UDP client
group5
SendCfgOnUDP5 Off - - Off Send Config frame2 on UDP for
On group5
TCPportUDPdataCtrl6 1024 - 65534 - 1 4718 TCP port for control of data sent over
UDP client group6
SendDataUDP6 Off - - Off Send data to UDP client group6
On
SetByProtocol
ProtocolOnUDP6 IEEE1344 - - C37.118 Select protocol for UDP client group6
C37.118
PMUReportUDP6 1-2 - 1 1 PMUREPORT instance used for UDP
client group6
Table continues on next page

120 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 6
Wide area measurement system

Name Values (Range) Unit Step Default Description


UDPDestAddres6 0 - 16 IP 1 234.5.6.12 UDP destination address for UDP
Address client group6
UDPDestPort6 1024 - 65534 - 1 8915 UDP destination port for UDP client
group6
SendCfgOnUDP6 Off - - Off Send Config frame2 on UDP for
On group6

6.2 Protocol reporting via IEEE 1344 and C37.118


PMUREPORT GUID-0C45D2FA-1B95-4FCA-B23B-A28C2770B817 v1

6.2.1 Identification
GUID-0090956B-48F1-4E8B-9A40-90044C71DF20 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Protocol reporting via IEEE 1344 and PMUREPORT - -
C37.118

6.2.2 Functionality GUID-8DF29209-252A-4E51-9F4A-B14B669E71AB v4

The phasor measurement reporting block moves the phasor calculations into an IEEE C37.118
and/or IEEE 1344 synchrophasor frame format. The PMUREPORT block contains parameters
for PMU performance class and reporting rate, the IDCODE and Global PMU ID, format of the
data streamed through the protocol, the type of reported synchrophasors, as well as settings
for reporting analog and digital signals.

The message generated by the PMUREPORT function block is set in accordance with the IEEE
C37.118 and/or IEEE 1344 standards.

There are settings for Phasor type (positive sequence, negative sequence or zero sequence in
case of 3-phase phasor and L1, L2 or L3 in case of single phase phasor), PMU's Service class
(Protection or Measurement), Phasor representation (polar or rectangular) and the data types
for phasor data, analog data and frequency data.

Synchrophasor data can be reported to up to 8 clients over TCP and/or 6 UDP group clients for
multicast or unicast transmission of phasor data from the IED. More information regarding
synchrophasor communication structure and TCP/UDP configuration is available in section
C37.118 Phasor Measurement Data Streaming Protocol Configuration.

Multiple PMU functionality can be configured in the IED, which can stream out same or
different data at different reporting rates or different performance (service) classes. There are
2 instances of PMU functionality available in the IED. Each instance of PMU functionality
includes a set of PMU reporting function blocks tagged by the same instance number (1 or 2).
As shown in the following figures, each set of PMU reporting function blocks includes
PMUREPORT, PHASORREPORT1-4, ANALOGREPORT1-3, and BINARYREPORT1-3 function blocks.
In general, each instance of PMU functionality has 32 configurable phasor channels
(PHASORREPORT1–4 blocks), 24 analog channels (ANALOGREPORT1-3 blocks), and 28 digital
channels (24 digital-report channels in BINARYREPORT1-3 and 4 trigger-report channels in
PMUREPORT function block). Special rules shall be taken into account in PCM600 for
Application Configuration and Parameter Settings of multiple PMUREPORT blocks. These rules
are explained in the Application Manual in section PMU Report Function Blocks Connection
Rules.

Line distance protection REL670 121


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 506 370-UEN J
Wide area measurement system

Figure 34 shows both instances of the PMUREPORT function block. As seen, each PMUREPORT
instance has 4 predefined binary input signals corresponding to the Bits 03-00: Trigger Reason
defined in STAT field of the Data frame in IEEE C37.118.2 standard. These are predefined inputs
for Frequency Trigger, Rate of Change of Frequency trigger, Magnitude High and Magnitude
Low triggers.

IEC140000118-2-en.vsd
IEC140000118 V2 EN-US

Figure 34: Multiple instances of PMUREPORT function block


Figure 35 shows both instances of the PHASORREPORT function blocks. The instance number
is visible in the bottom of each function block. For each instance, there are four separate
PHASORREPORT blocks including 32 configurable phasor channels (8 phasor channels in each
PHASORREPORT block). Each phasor channel can be configured as a 3-phase (symmetrical
components positive/negative/zero) or single-phase phasor (L1/L2/L3).

IEC140000119-2-en.vsd
IEC140000119 V2 EN-US

Figure 35: Multiple instances of PHASORREPORT blocks


Figure 36 shows both instances of ANALOGREPORT function blocks. The instance number is
visible in the bottom of each function block. For each instance, there are three separate
ANALOGREPORT blocks capable of reporting up to 24 Analog signals (8 Analog signals in each
ANALOGREPORT block). These can include for example transfer of active and reactive power or
reporting the milliampere input signals to the PDC clients as defined in IEEE C37.118 data
frame format.

122 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 6
Wide area measurement system

IEC140000120-2-en.vsd
IEC140000120 V2 EN-US

Figure 36: Multiple instances of ANALOGREPORT blocks


Figure 37 shows both instances of BINARYREPORT function blocks. The instance number is
visible in the bottom of each function block. For each instance, there are three separate
BINARYREPORT blocks capable of reporting up to 24 Binary signals (8 Binary signals in each
BINARYREPORT block). These binary signals can be for example dis-connector or breaker
position indications or internal/external protection alarm signals.

IEC140000121-2-en.vsd
IEC140000121 V2 EN-US

Figure 37: Multiple instances of BINARYREPORT blocks

6.2.3 Function block GUID-45150D7E-3231-4661-A8B4-17364AF25035 v2

PMUREPORT
BLOCK TIMESTAT
^FREQTRIG
^DFDTTRIG
^MAGHIGHTRIG
^MAGLOWTRIG

IEC140000102-1_en.vsd
IEC140000102 V1 EN-US

ANALOGREPORT1
^ANALOG1
^ANALOG2
^ANALOG3
^ANALOG4
^ANALOG5
^ANALOG6
^ANALOG7
^ANALOG8
IEC140000107-1_en.vsd
IEC140000107 V1 EN-US

Line distance protection REL670 123


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 506 370-UEN J
Wide area measurement system

ANALOGREPORT2
^ANALOG9
^ANALOG10
^ANALOG11
^ANALOG12
^ANALOG13
^ANALOG14
^ANALOG15
^ANALOG16
IEC140000108-1_en.vsd
IEC140000108 V1 EN-US

ANALOGREPORT3
^ANALOG17
^ANALOG18
^ANALOG19
^ANALOG20
^ANALOG21
^ANALOG22
^ANALOG23
^ANALOG24

IEC140000109-1_en.vsd
IEC140000109 V1 EN-US

BINARYREPORT1
^BINARY1
^BINARY2
^BINARY3
^BINARY4
^BINARY5
^BINARY6
^BINARY7
^BINARY8
IEC140000110-1_en.vsd
IEC140000110 V1 EN-US

BINARYREPORT2
^BINARY9
^BINARY10
^BINARY11
^BINARY12
^BINARY13
^BINARY14
^BINARY15
^BINARY16
IEC140000111-1_en.vsd
IEC140000111 V1 EN-US

BINARYREPORT3
^BINARY17
^BINARY18
^BINARY19
^BINARY20
^BINARY21
^BINARY22
^BINARY23
^BINARY24
IEC140000112-1_en.vsd
IEC140000112 V1 EN-US

PHASORREPORT1
^PHASOR1
^PHASOR2
^PHASOR3
^PHASOR4
^PHASOR5
^PHASOR6
^PHASOR7
^PHASOR8

IEC140000103-1_en.vsd
IEC140000103 V1 EN-US

124 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 6
Wide area measurement system

PHASORREPORT2
^PHASOR9
^PHASOR10
^PHASOR11
^PHASOR12
^PHASOR13
^PHASOR14
^PHASOR15
^PHASOR16

IEC140000104-1_en.vsd
IEC140000104 V1 EN-US

PHASORREPORT3
^PHASOR17
^PHASOR18
^PHASOR19
^PHASOR20
^PHASOR21
^PHASOR22
^PHASOR23
^PHASOR24

IEC140000105-1_en.vsd
IEC140000105 V1 EN-US

PHASORREPORT4
^PHASOR25
^PHASOR26
^PHASOR27
^PHASOR28
^PHASOR29
^PHASOR30
^PHASOR31
^PHASOR32

IEC140000106-1_en.vsd
IEC140000106 V1 EN-US

6.2.4 Signals SEMOD55830-1 v2

PID-6244-INPUTSIGNALS v2

Table 49: PMUREPORT Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of output signals
FREQTRIG BOOLEAN 0 Frequency trigger
DFDTTRIG BOOLEAN 0 Rate of change of frequency trigger
MAGHIGHTRIG BOOLEAN 0 Magnitude high trigger
MAGLOWTRIG BOOLEAN 0 Magnitude low trigger

PID-6244-OUTPUTSIGNALS v2

Table 50: PMUREPORT Output signals


Name Type Description
TIMESTAT BOOLEAN Time synchronization status

PID-6238-INPUTSIGNALS v2

Table 51: ANALOGREPORT1 Input signals


Name Type Default Description
ANALOG1 REAL 0.0 Analog input channel 1
ANALOG2 REAL 0.0 Analog input channel 2
ANALOG3 REAL 0.0 Analog input channel 3
Table continues on next page

Line distance protection REL670 125


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 506 370-UEN J
Wide area measurement system

Name Type Default Description


ANALOG4 REAL 0.0 Analog input channel 4
ANALOG5 REAL 0.0 Analog input channel 5
ANALOG6 REAL 0.0 Analog input channel 6
ANALOG7 REAL 0.0 Analog input channel 7
ANALOG8 REAL 0.0 Analog input channel 8

PID-6239-INPUTSIGNALS v2

Table 52: ANALOGREPORT2 Input signals


Name Type Default Description
ANALOG9 REAL 0.0 Analog input channel 9
ANALOG10 REAL 0.0 Analog input channel 10
ANALOG11 REAL 0.0 Analog input channel 11
ANALOG12 REAL 0.0 Analog input channel 12
ANALOG13 REAL 0.0 Analog input channel 13
ANALOG14 REAL 0.0 Analog input channel 14
ANALOG15 REAL 0.0 Analog input channel 15
ANALOG16 REAL 0.0 Analog input channel 16

PID-6240-INPUTSIGNALS v2

Table 53: ANALOGREPORT3 Input signals


Name Type Default Description
ANALOG17 REAL 0.0 Analog input channel 17
ANALOG18 REAL 0.0 Analog input channel 18
ANALOG19 REAL 0.0 Analog input channel 19
ANALOG20 REAL 0.0 Analog input channel 20
ANALOG21 REAL 0.0 Analog input channel 21
ANALOG22 REAL 0.0 Analog input channel 22
ANALOG23 REAL 0.0 Analog input channel 23
ANALOG24 REAL 0.0 Analog input channel 24

PID-6241-INPUTSIGNALS v3

Table 54: BINARYREPORT1 Input signals


Name Type Default Description
BINARY1 BOOLEAN 0 Binary input channel1
BINARY2 BOOLEAN 0 Binary input channel2
BINARY3 BOOLEAN 0 Binary input channel3
BINARY4 BOOLEAN 0 Binary input channel4
BINARY5 BOOLEAN 0 Binary input channel5
BINARY6 BOOLEAN 0 Binary input channel6
BINARY7 BOOLEAN 0 Binary input channel7
BINARY8 BOOLEAN 0 Binary input channel8

126 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 6
Wide area measurement system

PID-6242-INPUTSIGNALS v2

Table 55: BINARYREPORT2 Input signals


Name Type Default Description
BINARY9 BOOLEAN 0 Binary input channel 9
BINARY10 BOOLEAN 0 Binary input channel 10
BINARY11 BOOLEAN 0 Binary input channel 11
BINARY12 BOOLEAN 0 Binary input channel 12
BINARY13 BOOLEAN 0 Binary input channel 13
BINARY14 BOOLEAN 0 Binary input channel 14
BINARY15 BOOLEAN 0 Binary input channel 15
BINARY16 BOOLEAN 0 Binary input channel 16

PID-6243-INPUTSIGNALS v2

Table 56: BINARYREPORT3 Input signals


Name Type Default Description
BINARY17 BOOLEAN 0 Binary input channel 17
BINARY18 BOOLEAN 0 Binary input channel 18
BINARY19 BOOLEAN 0 Binary input channel 19
BINARY20 BOOLEAN 0 Binary input channel 20
BINARY21 BOOLEAN 0 Binary input channel 21
BINARY22 BOOLEAN 0 Binary input channel 22
BINARY23 BOOLEAN 0 Binary input channel 23
BINARY24 BOOLEAN 0 Binary input channel 24

PID-6252-INPUTSIGNALS v3

Table 57: PHASORREPORT1 Input signals


Name Type Default Description
PHASOR1 GROUP - Group signal Input for Phasor1
SIGNAL
PHASOR2 GROUP - Group signal Input for Phasor2
SIGNAL
PHASOR3 GROUP - Group signal Input for Phasor3
SIGNAL
PHASOR4 GROUP - Group signal Input for Phasor4
SIGNAL
PHASOR5 GROUP - Group signal Input for Phasor 5
SIGNAL
PHASOR6 GROUP - Group signal Input for Phasor6
SIGNAL
PHASOR7 GROUP - Group signal Input for Phasor7
SIGNAL
PHASOR8 GROUP - Group signal Input for Phasor8
SIGNAL

Line distance protection REL670 127


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 506 370-UEN J
Wide area measurement system

PID-6253-INPUTSIGNALS v2

Table 58: PHASORREPORT2 Input signals


Name Type Default Description
PHASOR9 GROUP - Group signal Input for Phasor9
SIGNAL
PHASOR10 GROUP - Group signal Input for Phasor10
SIGNAL
PHASOR11 GROUP - Group signal Input for Phasor11
SIGNAL
PHASOR12 GROUP - Group signal Input for Phasor12
SIGNAL
PHASOR13 GROUP - Group signal Input for Phasor13
SIGNAL
PHASOR14 GROUP - Group signal Input for Phasor14
SIGNAL
PHASOR15 GROUP - Group signal Input for Phasor15
SIGNAL
PHASOR16 GROUP - Group signal Input for Phasor16
SIGNAL

PID-6254-INPUTSIGNALS v2

Table 59: PHASORREPORT3 Input signals


Name Type Default Description
PHASOR17 GROUP - Group signal Input for Phasor17
SIGNAL
PHASOR18 GROUP - Group signal Input for Phasor18
SIGNAL
PHASOR19 GROUP - Group signal Input for Phasor19
SIGNAL
PHASOR20 GROUP - Group signal Input for Phasor20
SIGNAL
PHASOR21 GROUP - Group signal Input for Phasor21
SIGNAL
PHASOR22 GROUP - Group signal Input for Phasor22
SIGNAL
PHASOR23 GROUP - Group signal Input for Phasor23
SIGNAL
PHASOR24 GROUP - Group signal Input for Phasor24
SIGNAL

PID-6255-INPUTSIGNALS v2

Table 60: PHASORREPORT4 Input signals


Name Type Default Description
PHASOR25 GROUP - Group signal Input for Phasor25
SIGNAL
PHASOR26 GROUP - Group signal Input for Phasor26
SIGNAL
PHASOR27 GROUP - Group signal Input for Phasor27
SIGNAL
PHASOR28 GROUP - Group signal Input for Phasor28
SIGNAL
Table continues on next page

128 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 6
Wide area measurement system

Name Type Default Description


PHASOR29 GROUP - Group signal Input for Phasor29
SIGNAL
PHASOR30 GROUP - Group signal Input for Phasor30
SIGNAL
PHASOR31 GROUP - Group signal Input for Phasor31
SIGNAL
PHASOR32 GROUP - Group signal Input for Phasor32
SIGNAL

6.2.5 Settings SEMOD119927-1 v2

PID-6244-SETTINGS v2

Table 61: PMUREPORT Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - On Operation mode off/on
On
SvcClass P class - - P class Service class
M class
Global_PMU_ID 0 - 16 - 1 0 Global PMU Identifier (G_PMU_ID)
PMUdataStreamIDCOD 1 - 65534 - 1 1 PMU Data Stream ID Number
E (IDCODE)
PhasorFormat Rectangular - - Rectangular Select phasor format
Polar
PhasorDataType Float - - Float Select phasor datatype
Integer
FrequencyDataType Float - - Float Select frequency datatype
Integer
AnalogDataType Float - - Float Select analog data type
Integer
SendFreqInfo Off - - On Send frequency and rate of change of
On frequency information
ReportRate 10/10 fr/s - - 10/10 fr/s Phasor data report rate
(60/50Hz) (60/50Hz)
12/10 fr/s
(60/50Hz)
15/10 fr/s
(60/50Hz)
20/25 fr/s
(60/50Hz)
30/25 fr/s
(60/50Hz)
60/50 fr/s
(60/50Hz)
120/100 fr/s
(60/50Hz)
240/200 fr/s
(60/50Hz)
RptTimetag FirstSample - - MiddleSample Method of phasor timetag
MiddleSample
LastSample

Line distance protection REL670 129


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 506 370-UEN J
Wide area measurement system

PID-6238-SETTINGS v2

Table 62: ANALOGREPORT1 Non group settings (basic)


Name Values (Range) Unit Step Default Description
Analog1Range 3277.0 - - 0.1 3277.0 (+/-) Range for scaling analog 1 in
10000000000.0 integer format
Analog1UnitType Single point-on- - - RMS of analog Unit type for analog 1
wave input
RMS of analog
input
Peak of analog
input
Analog2Range 3277.0 - - 0.1 3277.0 (+/-) Range for scaling analog 2 in
10000000000.0 integer format
Analog2UnitType Single point-on- - - RMS of analog Unit type for analog 2
wave input
RMS of analog
input
Peak of analog
input
Analog3Range 3277.0 - - 0.1 3277.0 (+/-) Range for scaling analog 3 in
10000000000.0 integer format
Analog3UnitType Single point-on- - - RMS of analog Unit type for analog 3
wave input
RMS of analog
input
Peak of analog
input
Analog4Range 3277.0 - - 0.1 3277.0 (+/-) Range for scaling analog 4 in
10000000000.0 integer format
Analog4UnitType Single point-on- - - RMS of analog Unit type for analog 4
wave input
RMS of analog
input
Peak of analog
input
Analog5Range 3277.0 - - 0.1 3277.0 (+/-) Range for scaling analog 5 in
10000000000.0 integer format
Analog5UnitType Single point-on- - - RMS of analog Unit type for analog 5
wave input
RMS of analog
input
Peak of analog
input
Analog6Range 3277.0 - - 0.1 3277.0 (+/-) Range for scaling analog 6 in
10000000000.0 integer format
Analog6UnitType Single point-on- - - RMS of analog Unit type for analog 6
wave input
RMS of analog
input
Peak of analog
input
Analog7Range 3277.0 - - 0.1 3277.0 (+/-) Range for scaling analog 7 in
10000000000.0 integer format
Table continues on next page

130 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 6
Wide area measurement system

Name Values (Range) Unit Step Default Description


Analog7UnitType Single point-on- - - RMS of analog Unit type for analog 7
wave input
RMS of analog
input
Peak of analog
input
Analog8Range 3277.0 - - 0.1 3277.0 (+/-) Range for scaling analog 8 in
10000000000.0 integer format
Analog8UnitType Single point-on- - - RMS of analog Unit type for analog 8
wave input
RMS of analog
input
Peak of analog
input

PID-6239-SETTINGS v2

Table 63: ANALOGREPORT2 Non group settings (basic)


Name Values (Range) Unit Step Default Description
Analog9Range 3277.0 - - 0.1 3277.0 (+/-) Range for scaling analog 9 in
10000000000.0 integer format
Analog9UnitType Single point-on- - - RMS of analog Unit type for analog 9
wave input
RMS of analog
input
Peak of analog
input
Analog10Range 3277.0 - - 0.1 3277.0 (+/-) Range for scaling analog 10 in
10000000000.0 integer format
Analog10UnitType Single point-on- - - RMS of analog Unit type for analog 10
wave input
RMS of analog
input
Peak of analog
input
Analog11Range 3277.0 - - 0.1 3277.0 (+/-) Range for scaling analog 11 in
10000000000.0 integer format
Analog11UnitType Single point-on- - - RMS of analog Unit type for analog 11
wave input
RMS of analog
input
Peak of analog
input
Analog12Range 3277.0 - - 0.1 3277.0 (+/-) Range for scaling analog 12 in
10000000000.0 integer format
Analog12UnitType Single point-on- - - RMS of analog Unit type for analog 12
wave input
RMS of analog
input
Peak of analog
input
Analog13Range 3277.0 - - 0.1 3277.0 (+/-) Range for scaling analog 13 in
10000000000.0 integer format
Analog13UnitType Single point-on- - - RMS of analog Unit type for analog 13
wave input
RMS of analog
input
Peak of analog
input
Table continues on next page

Line distance protection REL670 131


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 506 370-UEN J
Wide area measurement system

Name Values (Range) Unit Step Default Description


Analog14Range 3277.0 - - 0.1 3277.0 (+/-) Range for scaling analog 14 in
10000000000.0 integer format
Analog14UnitType Single point-on- - - RMS of analog Unit type for analog 14
wave input
RMS of analog
input
Peak of analog
input
Analog15Range 3277.0 - - 0.1 3277.0 (+/-) Range for scaling analog 15 in
10000000000.0 integer format
Analog15UnitType Single point-on- - - RMS of analog Unit type for analog 15
wave input
RMS of analog
input
Peak of analog
input
Analog16Range 3277.0 - - 0.1 3277.0 (+/-) Range for scaling analog 16 in
10000000000.0 integer format
Analog16UnitType Single point-on- - - RMS of analog Unit type for analog 16
wave input
RMS of analog
input
Peak of analog
input

PID-6240-SETTINGS v2

Table 64: ANALOGREPORT3 Non group settings (basic)


Name Values (Range) Unit Step Default Description
Analog17Range 3277.0 - - 0.1 3277.0 (+/-) Range for scaling analog 17 in
10000000000.0 integer format
Analog17UnitType Single point-on- - - RMS of analog Unit type for analog 17
wave input
RMS of analog
input
Peak of analog
input
Analog18Range 3277.0 - - 0.1 3277.0 (+/-) Range for scaling analog 18 in
10000000000.0 integer format
Analog18UnitType Single point-on- - - RMS of analog Unit type for analog 18
wave input
RMS of analog
input
Peak of analog
input
Analog19Range 3277.0 - - 0.1 3277.0 (+/-) Range for scaling analog 19 in
10000000000.0 integer format
Analog19UnitType Single point-on- - - RMS of analog Unit type for analog 19
wave input
RMS of analog
input
Peak of analog
input
Analog20Range 3277.0 - - 0.1 3277.0 (+/-) Range for scaling analog 20 in
10000000000.0 integer format
Table continues on next page

132 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 6
Wide area measurement system

Name Values (Range) Unit Step Default Description


Analog20UnitType Single point-on- - - RMS of analog Unit type for analog 20
wave input
RMS of analog
input
Peak of analog
input
Analog21Range 3277.0 - - 0.1 3277.0 (+/-) Range for scaling analog 21 in
10000000000.0 integer format
Analog21UnitType Single point-on- - - RMS of analog Unit type for analog 21
wave input
RMS of analog
input
Peak of analog
input
Analog22Range 3277.0 - - 0.1 3277.0 (+/-) Range for scaling analog 22 in
10000000000.0 integer format
Analog22UnitType Single point-on- - - RMS of analog Unit type for analog 22
wave input
RMS of analog
input
Peak of analog
input
Analog23Range 3277.0 - - 0.1 3277.0 (+/-) Range for scaling analog 23 in
10000000000.0 integer format
Analog23UnitType Single point-on- - - RMS of analog Unit type for analog 23
wave input
RMS of analog
input
Peak of analog
input
Analog24Range 3277.0 - - 0.1 3277.0 (+/-) Range for scaling analog 24 in
10000000000.0 integer format
Analog24UnitType Single point-on- - - RMS of analog Unit type for analog 24
wave input
RMS of analog
input
Peak of analog
input

Line distance protection REL670 133


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 506 370-UEN J
Wide area measurement system

PID-6252-SETTINGS v2

Table 65: PHASORREPORT1 Non group settings (basic)


Name Values (Range) Unit Step Default Description
Phasor2 POSSEQ - - POSSEQ Group selector for Phasor2
NEGSEQ
ZEROSEQ
L1
L2
L3
Phasor3 POSSEQ - - POSSEQ Group selector for Phasor3
NEGSEQ
ZEROSEQ
L1
L2
L3
Phasor4 POSSEQ - - POSSEQ Group selector for Phasor4
NEGSEQ
ZEROSEQ
L1
L2
L3
Phasor5 POSSEQ - - POSSEQ Group selector for phasor5
NEGSEQ
ZEROSEQ
L1
L2
L3
Phasor6 POSSEQ - - POSSEQ Group selector for Phasor6
NEGSEQ
ZEROSEQ
L1
L2
L3
Phasor7 POSSEQ - - POSSEQ Group selector for Phasor7
NEGSEQ
ZEROSEQ
L1
L2
L3
Phasor8 L1 - - POSSEQ Group selector for phasor8
L2
L3
POSSEQ
NEGSEQ
ZEROSEQ
Phasor1Report Off - - On Reporting phasor 1
On
Phasor1UseFreqSrc Off - - On Include phasor 1 for automatic
On frequency source selection
Phasor2Report Off - - On Reporting phasor 2
On
Phasor2UseFreqSrc Off - - On Include phasor 2 for automatic
On frequency source selection
Phasor3Report Off - - On Reporting phasor 3
On
Phasor3UseFreqSrc Off - - On Include phasor 3 for automatic
On frequency source selection
Phasor4Report Off - - On Reporting phasor 4
On
Table continues on next page

134 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 6
Wide area measurement system

Name Values (Range) Unit Step Default Description


Phasor4UseFreqSrc Off - - On Include phasor 4 for automatic
On frequency source selection
Phasor5Report Off - - On Reporting phasor 5
On
Phasor5UseFreqSrc Off - - On Include phasor 5 for automatic
On frequency source selection
Phasor6Report Off - - On Reporting phasor 6
On
Phasor6UseFreqSrc Off - - On Include phasor 6 for automatic
On frequency source selection
Phasor7Report Off - - On Reporting phasor 7
On
Phasor7UseFreqSrc Off - - On Include phasor 7 for automatic
On frequency source selection
Phasor8Report Off - - On Reporting phasor 8
On
Phasor8UseFreqSrc Off - - On Include phasor 8 for automatic
On frequency source selection
Phasor1 POSSEQ - - POSSEQ Group Selector for Phasor1
NEGSEQ
ZEROSEQ
L1
L2
L3

PID-6253-SETTINGS v2

Table 66: PHASORREPORT2 Non group settings (basic)


Name Values (Range) Unit Step Default Description
Phasor9 POSSEQ - - POSSEQ Group selector for Phasor9
NEGSEQ
ZEROSEQ
L1
L2
L3
Phasor10 POSSEQ - - POSSEQ Group selector for Phasor10
NEGSEQ
ZEROSEQ
L1
L2
L3
Phasor11 POSSEQ - - POSSEQ Group selector for Phasor 11
NEGSEQ
ZEROSEQ
L1
L2
L3
Phasor12 POSSEQ - - POSSEQ Group selector for Phasor12
NEGSEQ
ZEROSEQ
L1
L2
L3
Table continues on next page

Line distance protection REL670 135


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 506 370-UEN J
Wide area measurement system

Name Values (Range) Unit Step Default Description


Phasor13 POSSEQ - - POSSEQ Group selector for Phasor13
NEGSEQ
ZEROSEQ
L1
L2
L3
Phasor14 POSSEQ - - POSSEQ Group selector for Phasor14
NEGSEQ
ZEROSEQ
L1
L2
L3
Phasor15 POSSEQ - - POSSEQ Group selector for Phasor15
NEGSEQ
ZEROSEQ
L1
L2
L3
Phasor16 POSSEQ - - POSSEQ Group selector for Phasor16
NEGSEQ
ZEROSEQ
L1
L2
L3
Phasor9Report Off - - On Reporting phasor 9
On
Phasor9UseFreqSrc Off - - On Include phasor 9 for automatic
On frequency source selection
Phasor10Report Off - - On Reporting phasor 10
On
Phasor10UseFreqSrc Off - - On Include phasor 10 for automatic
On frequency source selection
Phasor11Report Off - - On Reporting phasor 11
On
Phasor11UseFreqSrc Off - - On Include phasor 11 for automatic
On frequency source selection
Phasor12Report Off - - On Reporting phasor 12
On
Phasor12UseFreqSrc Off - - On Include phasor 12 for automatic
On frequency source selection
Phasor13Report Off - - On Reporting phasor 13
On
Phasor13UseFreqSrc Off - - On Include phasor 13 for automatic
On frequency source selection
Phasor14Report Off - - On Reporting phasor 14
On
Phasor14UseFreqSrc Off - - On Include phasor 14 for automatic
On frequency source selection
Phasor15Report Off - - On Reporting phasor 15
On
Phasor15UseFreqSrc Off - - On Include phasor 15 for automatic
On frequency source selection
Phasor16Report Off - - On Reporting phasor 16
On
Phasor16UseFreqSrc Off - - On Include phasor 16 for automatic
On frequency source selection

136 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 6
Wide area measurement system

PID-6254-SETTINGS v2

Table 67: PHASORREPORT3 Non group settings (basic)


Name Values (Range) Unit Step Default Description
Phasor17 POSSEQ - - POSSEQ Group selector for Phasor17
NEGSEQ
ZEROSEQ
L1
L2
L3
Phasor18 POSSEQ - - POSSEQ Group selector for Phasor18
NEGSEQ
ZEROSEQ
L1
L2
L3
Phasor19 POSSEQ - - POSSEQ Group selector for Phasor19
NEGSEQ
ZEROSEQ
L1
L2
L3
Phasor20 POSSEQ - - POSSEQ Group selector for Phasor20
NEGSEQ
ZEROSEQ
L1
L2
L3
Phasor21 POSSEQ - - POSSEQ Group selector for Phasor21
NEGSEQ
ZEROSEQ
L1
L2
L3
Phasor22 POSSEQ - - POSSEQ Group selector for Phasor22
NEGSEQ
ZEROSEQ
L1
L2
L3
Phasor23 POSSEQ - - POSSEQ Group selector for Phasor23
NEGSEQ
ZEROSEQ
L1
L2
L3
Phasor24 POSSEQ - - POSSEQ Group selector for Phasor24
NEGSEQ
ZEROSEQ
L1
L2
L3
Phasor17Report Off - - On Reporting phasor 17
On
Phasor17UseFreqSrc Off - - On Include phasor 17 for automatic
On frequency source selection
Phasor18Report Off - - On Reporting phasor 18
On
Phasor18UseFreqSrc Off - - On Include phasor 18 for automatic
On frequency source selection
Phasor19Report Off - - On Reporting phasor 19
On
Table continues on next page

Line distance protection REL670 137


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 506 370-UEN J
Wide area measurement system

Name Values (Range) Unit Step Default Description


Phasor19UseFreqSrc Off - - On Include phasor 19 for automatic
On frequency source selection
Phasor20Report Off - - On Reporting phasor 20
On
Phasor20UseFreqSrc Off - - On Include phasor 20 for automatic
On frequency source selection
Phasor21Report Off - - On Reporting phasor 21
On
Phasor21UseFreqSrc Off - - On Include phasor 21 for automatic
On frequency source selection
Phasor22Report Off - - On Reporting phasor 22
On
Phasor22UseFreqSrc Off - - On Include phasor 22 for automatic
On frequency source selection
Phasor23Report Off - - On Reporting phasor 23
On
Phasor23UseFreqSrc Off - - On Include phasor 23 for automatic
On frequency source selection
Phasor24Report Off - - On Reporting phasor 24
On
Phasor24UseFreqSrc Off - - On Include phasor 24 for automatic
On frequency source selection

PID-6255-SETTINGS v2

Table 68: PHASORREPORT4 Non group settings (basic)


Name Values (Range) Unit Step Default Description
Phasor25 POSSEQ - - POSSEQ Group selector for Phasor25
NEGSEQ
ZEROSEQ
L1
L2
L3
Phasor26 POSSEQ - - POSSEQ Group selector for Phasor26
NEGSEQ
ZEROSEQ
L1
L2
L3
Phasor27 POSSEQ - - POSSEQ Group selector for Phasor27
NEGSEQ
ZEROSEQ
L1
L2
L3
Phasor28 POSSEQ - - POSSEQ Group selector for Phasor28
NEGSEQ
ZEROSEQ
L1
L2
L3
Phasor29 POSSEQ - - POSSEQ Group selector for Phasor29
NEGSEQ
ZEROSEQ
L1
L2
L3
Table continues on next page

138 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 6
Wide area measurement system

Name Values (Range) Unit Step Default Description


Phasor30 POSSEQ - - POSSEQ Group selector for Phasor30
NEGSEQ
ZEROSEQ
L1
L2
L3
Phasor31 POSSEQ - - POSSEQ Group selector for Phasor31
NEGSEQ
ZEROSEQ
L1
L2
L3
Phasor32 POSSEQ - - POSSEQ Group selector for Phasor32
NEGSEQ
ZEROSEQ
L1
L2
L3
Phasor25Report Off - - On Reporting phasor 25
On
Phasor25UseFreqSrc Off - - On Include phasor 25 for automatic
On frequency source selection
Phasor26Report Off - - On Reporting phasor 26
On
Phasor26UseFreqSrc Off - - On Include phasor 26 for automatic
On frequency source selection
Phasor27Report Off - - On Reporting phasor 27
On
Phasor27UseFreqSrc Off - - On Include phasor 27 for automatic
On frequency source selection
Phasor28Report Off - - On Reporting phasor 28
On
Phasor28UseFreqSrc Off - - On Include phasor 28 for automatic
On frequency source selection
Phasor29Report Off - - On Reporting phasor 29
On
Phasor29UseFreqSrc Off - - On Include phasor 29 for automatic
On frequency source selection
Phasor30Report Off - - On Reporting phasor 30
On
Phasor30UseFreqSrc Off - - On Include phasor 30 for automatic
On frequency source selection
Phasor31Report Off - - On Reporting phasor 31
On
Phasor32Report Off - - On Reporting phasor 32
On
Phasor31UseFreqSrc Off - - On Include phasor 31 for automatic
On frequency source selection
Phasor32UseFreqSrc Off - - On Include phasor 32 for automatic
On frequency source selection

Line distance protection REL670 139


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 506 370-UEN J
Wide area measurement system

6.2.6 Monitored data


PID-6244-MONITOREDDATA v2

Table 69: PMUREPORT Monitored data


Name Type Values (Range) Unit Description
TIMESTAT BOOLEAN 1=Ready - Time synchronization status
0=Fail
FREQ REAL - Hz Frequency
FREQGRAD REAL - - Rate of change of frequency
FREQREFCHSEL INTEGER - - Frequency reference channel number
selected
FREQREFCHERR BOOLEAN 0=Freq ref not - Frequency reference channel error
available
1=Freq ref error
2=Freq ref
available
FREQTRIG BOOLEAN - - Frequency trigger
DFDTTRIG BOOLEAN - - Rate of change of frequency trigger
MAGHIGHTRIG BOOLEAN - - Magnitude high trigger
MAGLOWTRIG BOOLEAN - - Magnitude low trigger

PID-6238-MONITOREDDATA v2

Table 70: ANALOGREPORT1 Monitored data


Name Type Values (Range) Unit Description
ANALOG1 REAL - - Analog input channel 1
ANALOG2 REAL - - Analog input channel 2
ANALOG3 REAL - - Analog input channel 3
ANALOG4 REAL - - Analog input channel 4
ANALOG5 REAL - - Analog input channel 5
ANALOG6 REAL - - Analog input channel 6
ANALOG7 REAL - - Analog input channel 7
ANALOG8 REAL - - Analog input channel 8

PID-6239-MONITOREDDATA v2

Table 71: ANALOGREPORT2 Monitored data


Name Type Values (Range) Unit Description
ANALOG9 REAL - - Analog input channel 9
ANALOG10 REAL - - Analog input channel 10
ANALOG11 REAL - - Analog input channel 11
ANALOG12 REAL - - Analog input channel 12
ANALOG13 REAL - - Analog input channel 13
ANALOG14 REAL - - Analog input channel 14
ANALOG15 REAL - - Analog input channel 15
ANALOG16 REAL - - Analog input channel 16

140 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 6
Wide area measurement system

PID-6240-MONITOREDDATA v2

Table 72: ANALOGREPORT3 Monitored data


Name Type Values (Range) Unit Description
ANALOG17 REAL - - Analog input channel 17
ANALOG18 REAL - - Analog input channel 18
ANALOG19 REAL - - Analog input channel 19
ANALOG20 REAL - - Analog input channel 20
ANALOG21 REAL - - Analog input channel 21
ANALOG22 REAL - - Analog input channel 22
ANALOG23 REAL - - Analog input channel 23
ANALOG24 REAL - - Analog input channel 24

PID-6241-MONITOREDDATA v2

Table 73: BINARYREPORT1 Monitored data


Name Type Values (Range) Unit Description
BINARY1 BOOLEAN - - Binary input channel 1
BINARY2 BOOLEAN - - Binary input channel 2
BINARY3 BOOLEAN - - Binary input channel 3
BINARY4 BOOLEAN - - Binary input channel 4
BINARY5 BOOLEAN - - Binary input channel 5
BINARY6 BOOLEAN - - Binary input channel 6
BINARY7 BOOLEAN - - Binary input channel 7
BINARY8 BOOLEAN - - Binary input channel 8

PID-6242-MONITOREDDATA v2

Table 74: BINARYREPORT2 Monitored data


Name Type Values (Range) Unit Description
BINARY9 BOOLEAN - - Binary input channel 9
BINARY10 BOOLEAN - - Binary input channel 10
BINARY11 BOOLEAN - - Binary input channel 11
BINARY12 BOOLEAN - - Binary input channel 12
BINARY13 BOOLEAN - - Binary input channel 13
BINARY14 BOOLEAN - - Binary input channel 14
BINARY15 BOOLEAN - - Binary input channel 15
BINARY16 BOOLEAN - - Binary input channel 16

PID-6243-MONITOREDDATA v2

Table 75: BINARYREPORT3 Monitored data


Name Type Values (Range) Unit Description
BINARY17 BOOLEAN - - Binary input channel 17
BINARY18 BOOLEAN - - Binary input channel 18
BINARY19 BOOLEAN - - Binary input channel 19
BINARY20 BOOLEAN - - Binary input channel 20
Table continues on next page

Line distance protection REL670 141


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 506 370-UEN J
Wide area measurement system

Name Type Values (Range) Unit Description


BINARY21 BOOLEAN - - Binary input channel 21
BINARY22 BOOLEAN - - Binary input channel 22
BINARY23 BOOLEAN - - Binary input channel 23
BINARY24 BOOLEAN - - Binary input channel 24

PID-6252-MONITOREDDATA v3

Table 76: PHASORREPORT1 Monitored data


Name Type Values (Range) Unit Description
PHASOR1 REAL - - Phasor 1 amplitude
PHASOR1 REAL - deg Phasor 1 angle
PHASOR2 REAL - - Phasor 2 amplitude
PHASOR2 REAL - deg Phasor 2 angle
PHASOR3 REAL - - Phasor 3 amplitude
PHASOR3 REAL - deg Phasor 3 angle
PHASOR4 REAL - - Phasor 4 amplitude
PHASOR4 REAL - deg Phasor 4 angle
PHASOR5 REAL - - Phasor 5 amplitude
PHASOR5 REAL - deg Phasor 5 angle
PHASOR6 REAL - - Phasor 6 amplitude
PHASOR6 REAL - deg Phasor 6 angle
PHASOR7 REAL - - Phasor 7 amplitude
PHASOR7 REAL - deg Phasor 7 angle
PHASOR8 REAL - - Phasor 8 amplitude
PHASOR8 REAL - deg Phasor 8 angle

PID-6253-MONITOREDDATA v2

Table 77: PHASORREPORT2 Monitored data


Name Type Values (Range) Unit Description
PHASOR9 REAL - - Phasor 9 amplitude
PHASOR9 REAL - deg Phasor 9 angle
PHASOR10 REAL - - Phasor 10 amplitude
PHASOR10 REAL - deg Phasor 10 angle
PHASOR11 REAL - - Phasor 11 amplitude
PHASOR11 REAL - deg Phasor 11 angle
PHASOR12 REAL - - Phasor 12 amplitude
PHASOR12 REAL - deg Phasor 12 angle
PHASOR13 REAL - - Phasor 13 amplitude
PHASOR13 REAL - deg Phasor 13 angle
PHASOR14 REAL - - Phasor 14 amplitude
PHASOR14 REAL - deg Phasor 14 angle
PHASOR15 REAL - - Phasor 15 amplitude
Table continues on next page

142 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 6
Wide area measurement system

Name Type Values (Range) Unit Description


PHASOR15 REAL - deg Phasor 15 angle
PHASOR16 REAL - - Phasor 16 amplitude
PHASOR16 REAL - deg Phasor 16 angle

PID-6254-MONITOREDDATA v2

Table 78: PHASORREPORT3 Monitored data


Name Type Values (Range) Unit Description
PHASOR17 REAL - - Phasor 17 amplitude
PHASOR17 REAL - deg Phasor 17 angle
PHASOR18 REAL - - Phasor 18 amplitude
PHASOR18 REAL - deg Phasor 18 angle
PHASOR19 REAL - - Phasor 19 amplitude
PHASOR19 REAL - deg Phasor 19 angle
PHASOR20 REAL - - Phasor 20 amplitude
PHASOR20 REAL - deg Phasor 20 angle
PHASOR21 REAL - - Phasor 21 amplitude
PHASOR21 REAL - deg Phasor 21 angle
PHASOR22 REAL - - Phasor 22 amplitude
PHASOR22 REAL - deg Phasor 22 angle
PHASOR23 REAL - - Phasor 23 amplitude
PHASOR23 REAL - deg Phasor 23 angle
PHASOR24 REAL - - Phasor 24 amplitude
PHASOR24 REAL - deg Phasor 24 angle

PID-6255-MONITOREDDATA v2

Table 79: PHASORREPORT4 Monitored data


Name Type Values (Range) Unit Description
PHASOR25 REAL - - Phasor 25 amplitude
PHASOR25 REAL - deg Phasor 25 angle
PHASOR26 REAL - - Phasor 26 amplitude
PHASOR26 REAL - deg Phasor 26 angle
PHASOR27 REAL - - Phasor 27 amplitude
PHASOR27 REAL - deg Phasor 27 angle
PHASOR28 REAL - - Phasor 28 amplitude
PHASOR28 REAL - deg Phasor 28 angle
PHASOR29 REAL - - Phasor 29 amplitude
PHASOR29 REAL - deg Phasor 29 angle
PHASOR30 REAL - - Phasor 30 amplitude
PHASOR30 REAL - deg Phasor 30 angle
PHASOR31 REAL - - Phasor 31 amplitude
PHASOR31 REAL - deg Phasor 31 angle
PHASOR32 REAL - - Phasor 32 amplitude
PHASOR32 REAL - deg Phasor 32 angle

Line distance protection REL670 143


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 506 370-UEN J
Wide area measurement system

6.2.7 Operation principle GUID-EB2B9096-2F9D-4264-B2D2-8D9DC65697E8 v3

The Phasor Measurement Unit (PMU) features three main functional principles:

• To measure the power system related AC quantities (voltage, current) and to calculate the
phasor representation of these quantities.
• To synchronize the calculated phasors with the UTC by time-tagging, in order to make
synchrophasors (time is reference).
• To publish all phasor-related data by means of TCP/IP or UDP/IP, following the standard
IEEE C37.118 protocol.

The C37.118 standard imposes requirements on the devices and describes the communication
message structure and data. The PMU complies with all the standard requirements with a
specific attention to the Total Vector Error (TVE) requirement. The TVE is calculated using the
following equation:

2
( X r ( n ) - X r )2 + ( X i ( n ) - X i )
TVE =
X r2 + X i2
GUID-80D9B1EA-A770-4F50-9530-61644B4DEBBE V1 EN-US (Equation 1)

where,

Xr(n) and Xi(n) are the measured values

Xr and Xi are the theoretical values

In order to comply with TVE requirements, special calibration is done in the factory on the
analog input channels of the PMU, resulting in increased accuracy of the measurements. The
IEEE C37.118 standard also imposes a variety of steady state and dynamic requirements which
are fulfilled in the IED with the help of high accuracy measurements and advanced filtering
techniques.

Figure 38 shows an overview of the PMU functionality and operation. In this figure, only one
instance of PMUREPORT (PMUREPORT1) is shown. Note that connection of different signals to
the PMUREPORT, in this figure, is only an example and the actual connections and reported
signals on the IEEEC37.118/1344 can be defined by the user.

144 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 6
Wide area measurement system

U/I samples

PMUREPORT1

MU PHASOR1
PHASOR2 8 TCP
U IEEEC37.118 / 1344
TRM SMAI messages NUM
I
U 6 UDC
TRM PHASOR32
I

ANALOG1
I/P MIM SMMI ANALOG2

MEAS. ANALOG24

BINARY1
BINARY2
BIM

OR
BINARY24
PROTECTION

GPS / OP
IRIG-B FREQTRIG
UP
DFDTTRIG
OC
PPS time data MAGHIGHTRIG
MAGLOWTRIG
UV

IEC140000146-1-en.vsd

IEC140000146 V2 EN-US

Figure 38: Overview of reporting functionality (PMUREPORT)

The TRM modules are individually AC-calibrated in the factory. The calibration data is stored in
the prepared area of the TRM EEProm. The pre-processor block is extended with calibration
compensation and a new angle reference method based on timestamps. The AI3P output of
the preprocessor block is used to provide the required information for each respective
PMUREPORT phasor channel. More information about preprocessor block is available in the
section Signal matrix for analog inputs SMAI.

6.2.7.1 Frequency reporting GUID-4F3BA7C7-8C9B-4266-9F72-AFB139E9DC21 v2

By using patented algorithm the IED can track the power system frequency in quite wide range
from 9 Hz to 95 Hz. In order to do that, the three-phase voltage signal shall be connected to
the IED. Then IED can adapt its filtering algorithm in order to properly measure phasors of all
current and voltage signals connected to the IED. This feature is essential for proper operation
of the PMUREPORT function or for protection during generator start-up and shut-down
procedure.

This adaptive filtering is ensured by proper configuration and settings of all relevant pre-
processing blocks, see Signal matrix for analog inputs in the Application manual. Note that in
all preconfigured IEDs such configuration and settings are already made and the three-phase
voltage are used as master for frequency tracking. With such settings the IED will be able to
properly estimate the magnitude and the phase angle of measured current and voltage
phasors in this wide frequency range.

One of the important functions of a PMU is reporting a very accurate system frequency to the
PDC client. In the IED, each of the PMUREPORT instances is able to report an accurate
frequency. Each voltage-connected preprocessor block (SMAI block) delivers the frequency
data, derived from the analog input AC voltage values, to the respective voltage phasor

Line distance protection REL670 145


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 506 370-UEN J
Wide area measurement system

channel. Every phasor channel has a user-settable parameter (PhasorXUseFreqSrc) to be used


as a source of frequency data for reporting to the PDC client. It is very important to set this
parameter to On for the voltage-connected phasor channels. There is an automatic frequency
source selection logic to ensure an uninterrupted reporting of the system frequency to the
PDC client. In this frequency source selection logic, the following general rules are applied:

• Only the voltage phasor channels are used


• The phasor channel with a lower channel number is prioritized to the one with a higher
channel number

As a result, the first voltage phasor is always the one delivering the system frequency to the
PDC client and if, by any reason, this voltage gets disconnected then the next available voltage
phasor is automatically used as the frequency source and so on. If the first voltage phasor
comes back, since it has a higher priority compare to the currently selected phasor channel,
after 500 ms it will be automatically selected again as the frequency source. There is also an
output available on the component which shows if the reference frequency is good, error or
reference channel unavailable.

It is possible to monitor the status of the frequency reference channel (frequency source) for
the respective PMUREPORT instance on Local HMI under Test/Function status/
Communication/Station Communication/PMU Report/PMUREPORT:1/Outputs, where the
FREQREFCHSEL output shows the selected channel as the reference for frequency and
FREQREFCHERR output states if the reference frequency is good, or if there is an error or if the
reference channel is unavailable. For more information refer to the table PMUREPORT
monitored data.
PID-6244-MONITOREDDATA v2

Table 80: PMUREPORT Monitored data


Name Type Values (Range) Unit Description
TIMESTAT BOOLEAN 1=Ready - Time synchronization status
0=Fail
FREQ REAL - Hz Frequency
FREQGRAD REAL - - Rate of change of frequency
FREQREFCHSEL INTEGER - - Frequency reference channel number
selected
FREQREFCHERR BOOLEAN 0=Freq ref not - Frequency reference channel error
available
1=Freq ref error
2=Freq ref
available
FREQTRIG BOOLEAN - - Frequency trigger
DFDTTRIG BOOLEAN - - Rate of change of frequency trigger
MAGHIGHTRIG BOOLEAN - - Magnitude high trigger
MAGLOWTRIG BOOLEAN - - Magnitude low trigger

6.2.7.2 Reporting filters GUID-D39153B5-81CE-4C1F-A816-C7A4C3407048 v2

The PMUREPORT function block implements the reporting filters designed to avoid aliasing as
the reporting frequency is lower than the sample/calculation frequency. This means, the
synchrophasor and frequency data which are included in the C37.118 synchrophasor streaming
data are filtered in order to suppress aliasing effects, as the rate of the C37.118 data is slower
than the data rate for internal processing. For this purpose, there is an anti-aliasing filter
designed for each reporting rate. The correct anti-aliasing filter will be automatically selected
based on the reporting rate and the performance class (P/M) settings. The filters are designed
to attenuate all aliasing frequencies to at least -40 dB (a gain of 0.01) at M class.

146 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 6
Wide area measurement system

The synchrophasor measurement is adaptive as it follows the fundamental


frequency over a wide range despite the reporting rate.

For example, when the synchrophasor measurement follows the fundamental frequency
beyond the fixed Nyquist limits in C37.118 standard, the anti-aliasing filter stopband moves
with the measured fundamental frequency. This has to be considered in connection with
C37.118, where the passband is defined relative to a fixed nominal frequency as shown in the
equation 2.

Fs
f0 ±
2
IECEQUATION2418 V1 EN-US (Equation 2)
where,

f0 is the nominal frequency

Fs is the reporting rate

6.2.7.3 Scaling Factors for ANALOGREPORT channels GUID-0DDAF6A9-8643-4FDD-97CF-9E35EF40AF7E v2

The internal calculation of analog values in the IED is based on 32 bit floating point. Therefore,
if the user selects to report the analog data (AnalogDataType) as Integer, there will be a down-
conversion of a 32 bit floating value to a new 16 bit integer value. In such a case, in order to
optimize the resolution of the reported analog data, the user-defined analog scaling is
implemented in the IED.

The analog scaling in the IED is automatically calculated by use of the user-defined parameters
AnalogXRange for the respective analog channel X. The analog data value on the input X will
have a range between -AnalogXRange and +AnalogXRange. The resulting scale factor will be
applied to the reported analog data where applicable.

If the AnalogDataType is selected as Float, then these settings are ignored.

The analog scaling in the IED is calculated using the equation:

AnalogXRange ´ 2
S calefactor =
65535.0
offset = 0.0
65535.0 = 16 bit integer range
IECEQUATION2443 V1 EN-US

According to the IEEE C37.118.2 standard, the scale factors (conversion factor) for analog
channels are defined in configuration frame 2 (CFG-2) and configuration frame 3 (CFG-3)
frames as follows:

• CFG-2 frame: The field ANUNIT (4 bytes) specifies the conversion factor as a signed 24 bit
word for user defined scaling. Since it is a 24 bit integer, in order to support the floating
point scale factor, the scale factor itself is multiplied in 10, so that a minimum of 0.1 scale
factor can be sent over the CFG-2 frame. The resulting scale factor is rounded to the
nearest decimal value. The clients receiving the Analog scale factor over CFG-2 should
divide the received scale factor by 10 and then apply it to the corresponding analog data
value.
• CFG-3 frame: The field ANSCALE (8 bytes) specifies the conversion factor as X’ = M * X + B
where; M is magnitude scaling in 32 bit floating point (first 4 bytes) and B is the offset in
32 bit floating point (last 4 bytes).

Line distance protection REL670 147


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 506 370-UEN J
Wide area measurement system

The server uses CFG-3 scale factor to scale the analog data values. As a result, the clients which
use scale factors in CFG-3 in order to recalculate analog values, will get a better resolution than
using the scale factors in CFG-2.

The following examples show how the scale factor is calculated.

Example 1:

AnalogXRange = 3277.0
IECEQUATION2446 V1 EN-US

The scale factor is calculated as follows:

(3277.0 ´ 2.0 )
sc alefactor = = 0.1 a nd offset = 0.0
65535.0
IECEQUATION2447 V1 EN-US

The scale factor will be sent as 1 on configuration frame 2, and 0.1 on configuration frame 3.
The range of analog values that can be transmitted in this case is -0.1 to -3276.8 and +0.1 to
+3276.7.

Example 2:

AnalogXRange = 4915.5
IECEQUATION2448 V1 EN-US

The scale factor is calculated as follows:

(4915.5 ´ 2.0 )
sc alefac tor = = 0.15 a nd offse t = 0.0
65535.0
IECEQUATION2449 V1 EN-US

The scale factor will be sent as 1 on configuration frame 2, and 0.15 on configuration frame 3.
The range of analog values that can be transmitted in this case is -0.15 to -4915.5 and +0.15 to
+4915.5.

Example 3:

Analo gXRange = 10000000000


IECEQUATION2450 V1 EN-US

The scale factor is calculated as follows:

(10000000000 ´ 2.0)
sc alefac tor = = 305180.43 a nd offse t = 0.0
65535.5
IECEQUATION2451 V1 EN-US

The scale factor will be sent as 3051804 on configuration frame 2, and 305180.43 on
configuration frame 3. The range of analog values that can be transmitted in this case is
-305181 to -10000000000 and +305181 to +10000000000.

148 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 6
Wide area measurement system

6.2.8 Technical data SEMOD172233-1 v1

GUID-F0BAEBD8-E361-4D50-9737-7DF8B043D66A v4

Table 81: PMUREPORT technical data


Influencing quantity Range Accuracy
Signal frequency ± 0.1 x fr ≤ 1.0% TVE

Signal magnitude:
Voltage phasor (0.1–1.2) x Ur
Current phasor (0.5–2.0) x Ir

Phase angle ± 180°


Harmonic distortion 10% from 2nd – 50th
Interfering signal:
Magnitude 10% of fundamental signal
Minimum frequency 0.1 x fr
Maximum frequency 1000 Hz

Line distance protection REL670 149


Technical manual
© Copyright 2017 ABB. All rights reserved
150
1MRK 506 370-UEN J Section 7
Differential protection

Section 7 Differential protection


7.1 High impedance differential protection, single phase
HZPDIF IP14239-1 v4

7.1.1 Identification M14813-1 v4

IEC 61850 IEC 60617 ANSI/IEEE C37.2


Function description
identification identification device number

High impedance differential


HZPDIF Id 87
protection, single phase

SYMBOL-CC V2 EN-US

7.1.2 Functionality M13071-3 v13

High impedance differential protection, single phase (HZPDIF) functions can be used when the
involved CT cores have the same turns ratio and similar magnetizing characteristics. It utilizes
an external CT secondary current summation by wiring. Actually all CT secondary circuits which
are involved in the differential scheme are connected in parallel. External series resistor, and a
voltage dependent resistor which are both mounted externally to the IED, are also required.

The external resistor unit shall be ordered under IED accessories in the Product Guide.

HZPDIF can be used to protect tee-feeders or busbars, reactors, motors, auto-transformers,


capacitor banks and so on. One such function block is used for a high-impedance restricted
earth fault protection. Three such function blocks are used to form three-phase, phase-
segregated differential protection.

7.1.3 Function block M13737-3 v3

HZPDIF
ISI* TRIP
BLOCK ALARM
BLKTR MEASVOLT

IEC05000363-2-en.vsd
IEC05000363 V2 EN-US

Figure 39: HZPDIF function block

7.1.4 Signals IP14244-1 v2

PID-6990-INPUTSIGNALS v1

Table 82: HZPDIF Input signals


Name Type Default Description
ISI GROUP - Single phase current input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Block of trip

Line distance protection REL670 151


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 7 1MRK 506 370-UEN J
Differential protection

PID-6990-OUTPUTSIGNALS v1

Table 83: HZPDIF Output signals


Name Type Description
TRIP BOOLEAN Trip signal
ALARM BOOLEAN Alarm signal
MEASVOLT REAL Measured RMS voltage on CT secondary side

7.1.5 Settings IP14245-1 v2

PID-6990-SETTINGS v1

Table 84: HZPDIF Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
U>Alarm 5 - 500 V 1 10 Alarm voltage level in volts on CT
secondary side
tAlarm 0.000 - 60.000 s 0.001 5.000 Time delay to activate alarm
U>Trip 10 - 900 V 1 100 Operate voltage level in volts on CT
secondary side
SeriesResistor 50 - 20000 Ohm 1 250 Value of series resistor in Ohms

7.1.6 Monitored data


PID-6990-MONITOREDDATA v1

Table 85: HZPDIF Monitored data


Name Type Values (Range) Unit Description
MEASVOLT REAL - kV Measured RMS voltage on CT
secondary side

7.1.7 Operation principle IP14242-1 v2

M13075-3 v11
High impedance protection system is a simple technique which requires that all CTs, used in
the protection scheme, have relatively high knee point voltage, similar magnetizing
characteristic and the same ratio. These CTs are installed in all ends of the protected object. In
order to make a scheme all CT secondary circuits belonging to one phase are connected in
parallel. From the CT junction points a measuring branch is connected. The measuring branch
is a series connection of one variable setting resistor (or series resistor) RS with high ohmic
value and an over-current element. Thus, the high impedance differential protection responds
to the current flowing through the measuring branch. However, this current is result of a
differential voltage caused by this parallel CT connection across the measuring branch. Non-
linear resistor (that is, metrosil) is used in order to protect entire scheme from high peak
voltages which may appear during internal faults. Typical high impedance differential scheme
is shown in Figure 40. Note that only one phase is shown in this figure.

152 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 7
Differential protection

RS

3 U
I
1
I> (50) 5

2
GUID-5CEAF088-D92B-45E5-B98F-3083894A694C V1 EN-US

Figure 40: HZPDIF scheme


Where in the Figure:

1. shows one main CT secondary winding connected in parallel with all other CTs, from the
same phase, connected to this scheme.
2. shows the scheme earthing point.

It is of utmost importance to insure that only one earthing point exists in


such protection scheme.

3. shows the setting (stabilizing) resistor RS.


4. shows the over-current measuring element.

The series connection of stabilizing resistor and over-current element is


designated as measuring branch.

5. shows the non-linear resistor (that is, metrosil).


6. U is the voltage across the CT paralleling point (for example, across the measuring
branch).
7. I is the current flowing through the measuring branch.

U and I are interrelated in accordance with the following formula U=RS × I.

Due to the parallel CT connections the high impedance differential relay can only measure one
current and that is the relay operating quantity. That means that there is no any stabilizing
quantity (that is, bias) in high-impedance differential protection schemes. Therefore in order
to guaranty the stability of the differential relay during external faults the operating quantity
must not exceed the set pickup value. Thus, for external faults, even with severe saturation of
some of the current transformers, the voltage across the measuring branch shall not rise
above the relay set pickup value. To achieve that a suitable value for setting resistor RS is
selected in such a way that the saturated CT secondary winding provides a much lower
impedance path for the false differential current than the measuring branch. In case of an
external fault causing current transformer saturation, the non-saturated current transformers
drive most of the spill differential current through the secondary winding of the saturated
current transformer and not through the measuring brunch of the relay. The voltage drop

Line distance protection REL670 153


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 7 1MRK 506 370-UEN J
Differential protection

across the saturated current transformer secondary winding appears also across the
measuring brunch, however it will typically be relatively small. Therefore, the pick-up value of
the relay has to be set above this false operating voltage.

See the application manual for operating voltage and sensitivity calculation.

7.1.7.1 Logic diagram M13075-9 v5

The logic diagram shows the operation principles for the 1Ph High impedance differential
protection function HZPDIF, see Figure 41.

The function utilizes the raw samples from the single phase current input connected to it. Thus
the twenty samples per fundamental power system cycle are available to the HZPDIF function.
These current samples are first multiplied with the set value for the used stabilizing resistor in
order to get voltage waveform across the measuring branch. The voltage waveform is then
filtered in order to get its RMS value. Note that used filtering is designed in such a way that it
ensures complete removal of the DC current component which may be present in the primary
fault current. The voltage RMS value is then compared with set Alarm and Trip thresholds. Note
that the TRIP signal is intentionally delayed on drop off for 30 ms within the function. The
measured RMS voltage is available as a service value from the function. The function has block
and trip block inputs available as well.

IEC05000301 V1 EN-US

Figure 41: Logic diagram for 1Ph High impedance differential protection HZPDIF

7.1.8 Technical data IP14246-1 v1

M13081-1 v12

Table 86: HZPDIF technical data


Function Range or value Accuracy
Operate voltage (10-900) V ±1.0% of Ir at I ≤ Ir
I=U/R ±1.0% of I at I > Ir

Reset ratio >95% at (30-900) V -


Maximum continuous power U>Trip2/SeriesResistor ≤200 W -

Operate time at 0 to 10 x Ud Min. = 5 ms


Max. = 15 ms
Reset time at 10 x Ud to 0 Min. = 75 ms
Max. = 95 ms
Table continues on next page

154 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 7
Differential protection

Function Range or value Accuracy


Critical impulse time 2 ms typically at 0 to 10 x Ud -

Operate time at 0 to 2 x Ud Min. = 25 ms


Max. = 35 ms
Reset time at 2 x Ud to 0 Min. = 50 ms
Max. = 70 ms
Critical impulse time 15 ms typically at 0 to 2 x Ud -

7.2 Additional security logic for differential protection


LDRGFC GUID-0E064528-0E70-4FA1-87C7-581DADC1EB55 v2

7.2.1 Identification
GUID-3081E62B-3E96-4615-97B8-2CCA92752658 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Additional security logic for LDRGFC - 11
differential protection

7.2.2 Functionality GUID-8F918A08-E50E-4E7B-BDCA-FF0B5534B289 v3

Additional security logic for differential protection (LDRGFC) can help the security of the
protection especially when the communication system is in abnormal status or for example
when there is unspecified asymmetry in the communication link. It helps to reduce the
probability for mal-operation of the protection. LDRGFC is more sensitive than the main
protection logic to always release operation for all faults detected by the differential function.
LDRGFC consists of four sub functions:

• Phase-to-phase current variation


• Zero sequence current criterion
• Low voltage criterion
• Low current criterion

Phase-to-phase current variation takes the current samples as input and it calculates the
variation using the sampling value based algorithm. Phase-to-phase current variation function
is major one to fulfill the objectives of the startup element.

Zero sequence criterion takes the zero sequence current as input. It increases the security of
protection during the high impedance fault conditions.

Low voltage criterion takes the phase voltages and phase-to-phase voltages as inputs. It
increases the security of protection when the three-phase fault occurred on the weak end side.

Low current criterion takes the phase currents as inputs and it increases the dependability
during the switch onto fault case of unloaded line.

The differential function can be allowed to trip as no load is fed through the line and
protection is not working correctly.

Features:

Line distance protection REL670 155


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 7 1MRK 506 370-UEN J
Differential protection

• Startup element is sensitive enough to detect the abnormal status of the protected
system
• Startup element does not influence the operation speed of main protection
• Startup element would detect the evolving faults, high impedance faults and three phase
fault on weak side
• It is possible to block the each sub function of startup element
• Startup signal has a settable pulse time

7.2.3 Function block GUID-A205A0BB-C09E-42E2-B664-1863E1FF2A0A v2

LDRGFC
I3P* START
U3P* STCVL1L2
BLOCK STCVL2L3
BLKCV STCVL3L1
BLKUC STUC
BLK3I0 ST3I0
BLKUV STUV
REMSTUP

IEC14000015-1-en.vsd
IEC14000015 V1 EN-US

Figure 42: LDRGFC function block

7.2.4 Signals
PID-3558-INPUTSIGNALS v9

Table 87: LDRGFC Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKCV BOOLEAN 0 Block of ph to ph current variation criterion
BLKUC BOOLEAN 0 Block of the low current criterion
BLK3I0 BOOLEAN 0 Block of zero sequence current criterion
BLKUV BOOLEAN 0 Block of under voltage criterion
REMSTUP BOOLEAN 0 Startup signal of remote end

PID-3558-OUTPUTSIGNALS v9

Table 88: LDRGFC Output signals


Name Type Description
START BOOLEAN General startup signal
STCVL1L2 BOOLEAN Start signal for current variation criterion for phase L1L2
STCVL2L3 BOOLEAN Start signal for current variation criterion for phase L2L3
STCVL3L1 BOOLEAN Start signal for current variation criterion for phase L3L1
STUC BOOLEAN Start signal for low current criterion
ST3I0 BOOLEAN Start signal for zero sequence current criterion
STUV BOOLEAN Start signal for under voltage criterion

156 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 7
Differential protection

7.2.5 Settings
PID-3558-SETTINGS v9

Table 89: LDRGFC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
tStUpReset 0.000 - 60.000 s 0.001 7.000 Reset delay for startup signal
OperationCV Off - - On Operation current variation Off/On
On
ICV> 1 - 100 %IB 1 20 Fixed threshold for ph to ph current
variation criterion
OperationUC Off - - On Operation low current criterion
On Off/On
IUC< 1 - 100 %IB 1 5 Start value for low current operation
in % of IBase
Operation3I0 Off - - On Operation zero sequence current
On criterion Off/On
I3I0> 1 - 100 %IB 1 10 Start value for zero sequence current
criterion in % of IBase
OperationUV Off - - On Operation under voltage criterion
On Off/On
UPhN< 1 - 100 %UB 1 60 Start value for phase voltage criterion
in % of UBase
UPhPh< 1 - 100 %UB 1 60 Start value for ph to ph voltage
criterion in % of UBase

Table 90: LDRGFC Group settings (advanced)


Name Values (Range) Unit Step Default Description
tCV 0.000 - 0.005 s 0.001 0.002 Time delay for phase to phase current
variation
tUC 0.000 - 60.000 s 0.001 0.200 Time delay for low current criterion
t3I0 0.000 - 60.000 s 0.001 0.000 Time delay for zero sequence current
criterion
tUV 0.000 - 60.000 s 0.001 0.000 Time delay for low voltage criterion

Table 91: LDRGFC Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

Line distance protection REL670 157


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 7 1MRK 506 370-UEN J
Differential protection

7.2.6 Monitored data


PID-3558-MONITOREDDATA v8

Table 92: LDRGFC Monitored data


Name Type Values (Range) Unit Description
IL1 REAL - A Current RMS value for phase L1
IL2 REAL - A Current RMS value for phase L2
IL3 REAL - A Current RMS value for phase L3
3I0 REAL - A Zero sequence current value
UL1 REAL - kV Voltage RMS value for phase L1
UL2 REAL - kV Voltage RMS value for phase L2
UL3 REAL - kV Voltage RMS value for phase L3
UL12 REAL - kV Voltage RMS value for ph to ph L1L2
UL23 REAL - kV Voltage RMS value for ph to ph L2L3
UL31 REAL - kV Voltage RMS value for ph to ph L3L1

7.2.7 Operation principle GUID-60091A2A-AC10-4E04-B4B8-C190E3E07D3E v5

Additional security logic for differential protection (LDRGFC) takes the current samples,
current RMS values, phase voltage values, phase-to-phase voltage values, zero sequence
current and remote side startup signals as inputs.

Startup signal becomes activated when any one of the current variation startup signal, zero
sequence current startup signal, voltage startup signal, and current startup signal is activated.

Phase-to-phase current variation takes current samples and generates the startup signal by
comparing with the start value.

If the zero sequence current value is greater than the start value of zero sequence current then
the zero sequence current startup signal will be activated.

Voltage startup signal becomes activated when the any of phase voltage and line voltage is
less than the voltage start value and the remote startup signal has to be activated.

Current startup signal becomes activated when the current value in all phases is less than
current start value.

Phase-to-phase current variation

Phase-to-phase current variation one is main startup element. It covers most of the abnormal
status of the system. The phase-to-phase current variation fails in high impedance faults,
three-phase fault on weak side and switch onto fault on unloaded line because of low
sensitivity in these cases.

Phase-to-phase current variation takes the current samples as input and the signal is
evaluated using the sampling value based algorithm.

The phase-to-phase current variation criterion is shown below:

DiFF > 1.8DIT + DI ZD


EQUATION2255 V1 EN-US

158 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 7
Differential protection

Where:
ΔiФФ sampling value of phase-to-phase current variation

ΔIZD setting of fixed threshold, which corresponds to setting ICV>. The default value for the
setting is 0.2·IBase, where IBase is the base current.
ΔIT float threshold

It is the full-circle integral of the phase-to-phase current variation

1 2T -1
DI T = å | DiFF (t - n) |
T n =T
EQUATION2256 V1 EN-US

Where:
T count of sample values in one cycle

ΔiФФ is calculated using the below formula:

Di (k ) = [i ( k ) - i (k - N )] - [i (k - N ) - i (k - 2 N )]
= i ( k ) - 2i ( k - N ) + i (k - 2 N )
EQUATION2257 V1 EN-US

N is the number of samples in one cycle.

tCV
STCVL1L2
t
cont

I3P Current variation tCV


STCVL2L3
subfunction t
i
tCV
STCVL3L1
t

OR STCV
cont

IEC10000295-1-en.vsd
IEC10000295 V1 EN-US

Figure 43: Current variation logic diagram


tCV is the time setting for the change of current criterion. Phase current samples are included
in input signal I3P.

Zero sequence current criterion

Zero sequence criterion is mainly for detection of remote IED high resistance faults or some
gradual faults. The criterion takes the zero sequence current as input. Zero sequence current is
compared with I3I0> for the t3I0 time to generate the zero sequence current startup signal.

Line distance protection REL670 159


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 7 1MRK 506 370-UEN J
Differential protection

I3P a
a>b t3I0
I3IO> b ST3I0
AND t

BLK3I0
BLOCK OR

IEC09000778-2-en.vsd
IEC09000778 V2 EN-US

Figure 44: Zero sequence current criterion logic diagram


Here I3I0> is the setting of the maximum possible non-faulted zero sequence current for the
protected line. The default value for this setting is 0.1 · IBase where IBase is the rated current
of the CT.

t3I0 is the time setting for the zero sequence current criterion.

The zero sequence current criterion can be blocked by activating the BLK3I0 input signal.

Low voltage criterion

Low voltage criterion is mainly for detection of the three phase faults occurring on weak side
with pre fault no load condition. The low voltage criterion takes the voltage phase values,
voltage phase-to-phase values and remote startup signals as inputs. The logic for low voltage
criterion is shown below:

U3P (UPhN) a
a<b
UPhN< b
OR
U3P (UPhPh) a
a<b
UPhPh< b
tUV STUV
REMSTUP (Recived)
AND t

BLKUV
BLOCK OR

IEC09000779-2-en.vsd
IEC09000779 V2 EN-US

Figure 45: Low voltage criterion logic diagram


Voltage phase value is compared with the start value of voltage phase and voltage phase-to-
phase value is compared with the start value of voltage phase-to-phase. If any of the phase
voltage or phase-to-phase voltages is below the set voltage levels for some time duration
(tUV) then the low voltage START signal becomes activated after receiving the remote startup
signal. Low voltage criterion can be blocked by activating BLKUV input signal.

If there are more than one remote IED, all the startup signals of the remote ends are logically
OR to obtain the REMSTUP signal from the remote side as input.

Low current criterion

The current in each phase is compared to the set current level. If all currents are below setting
IUC<, the STUC output is activated after the set delay tUC.

160 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 7
Differential protection

I3P
a
a<b tUC
IUC< b STUC
AND t

BLKUC
BLOCK OR

IEC09000780-2-en.vsd
IEC09000780 V2 EN-US

Figure 46: Low current criterion logic diagram


Security logic for differential protection

The configuration for the additional security logic for differential protection is shown in Figure
47. The function will release tripping of the line differential protection up to the end of timer
tStUpReset.

Phase-phase STCV
i
current variation

Zero sequence ST3IO


I0 > tStUpReset
current criterion START Local side start-up
t
Send signal to
Low voltage
OR remote side
criterion STUV
ULOW <

Low current
criterion STUC
I0 <

REMSTUP

IEC10000296-2-en.vsd
IEC10000296 V2 EN-US

Figure 47: Additional security logic for differential protection. Logic diagram for start up
element.

7.2.8 Technical data


GUID-0BD8D3C9-620A-426C-BDB5-DAA0E4F8247F v4

Table 93: LDRGFC technical data


Function Range or value Accuracy
Operate current, zero sequence current (1-100)% of lBase ±1.0% of Ir

Operate current, low current operation (1-100)% of lBase ±1.0% of Ir

Operate voltage, phase to neutral (1-100)% of UBase ±0.5% of Ur

Operate voltage, phase to phase (1-100)% of UBase ±0.5% of Ur

Independent time delay, zero sequence (0.000-60.000) s ±0.2% or ±40 ms


current at 0 to 2 x Iset whichever is
greater
Table continues on next page

Line distance protection REL670 161


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 7 1MRK 506 370-UEN J
Differential protection

Function Range or value Accuracy


Independent time delay, low current (0.000-60.000) s ±0.2% or ± 40 ms
operation at 2 x Iset to 0 whichever is
greater
Independent time delay, low voltage (0.000-60.000) s ±0.2% or ±40 ms
operation at 2 x Uset to 0 whichever is
greater
Reset time delay for startup signal at 0 to 2 (0.000-60.000) s ±0.2% or ±40 ms
x Uset whichever is
greater

162 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Section 8 Impedance protection


8.1 Distance measuring zones, quadrilateral characteristic
ZMQPDIS, ZMQAPDIS, ZDRDIR IP14498-1 v4

8.1.1 Identification M14852-1 v6

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Distance protection zone, ZMQPDIS 21
quadrilateral characteristic (zone 1)
Z
S00346 V2 EN-US

Distance protection zone, ZMQAPDIS 21


quadrilateral characteristic (zone
2-5) Z
S00346 V2 EN-US

Directional impedance quadrilateral ZDRDIR 21D

Z<->

IEC09000167 V1 EN-US

8.1.2 Functionality M13787-3 v15

The line distance protection is an up to five (depending on product variant) zone full scheme
protection function with three fault loops for phase-to-phase faults and three fault loops for
phase-to-earth faults for each of the independent zones. Individual settings for each zone in
resistive and reactive reach gives flexibility for use as back-up protection for transformer
connected to overhead lines and cables of different types and lengths.

Distance measuring zone, quadrilateral characteristic (ZMQPDIS) together with Phase


selection with load encroachment (FDPSPDIS) has functionality for load encroachment, which
increases the possibility to detect high resistive faults on heavily loaded lines, as shown in
figure 48.

Line distance protection REL670 163


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Forward
operation

Reverse
operation

en05000034.vsd
IEC05000034 V1 EN-US

Figure 48: Typical quadrilateral distance protection zone with Phase selection with load
encroachment function FDPSPDIS activated
The independent measurement of impedance for each fault loop together with a sensitive and
reliable built-in phase selection makes the function suitable in applications with single-phase
autoreclosing.

Built-in adaptive load compensation algorithm prevents overreaching of zone 1 at load


exporting end at phase-to-earth faults on heavily loaded power lines.

The distance protection zones can operate independently of each other in directional (forward
or reverse) or non-directional mode. This makes them suitable, together with different
communication schemes, for the protection of power lines and cables in complex network
configurations, such as parallel lines, multi-terminal lines.

8.1.3 Function block IP12800-1 v2

SEMOD115983-4 v8

ZMQPDIS
I3P* TRIP
U3P* TRL1
BLOCK TRL2
VTSZ TRL3
BLKTR START
STCND STL1
DIRCND STL2
STL3
STND

IEC06000256-2-en.vsd
IEC06000256 V2 EN-US

Figure 49: ZMQPDIS function block

ZMQAPDIS
I3P* TRIP
U3P* TRL1
BLOCK TRL2
VTSZ TRL3
BLKTR START
STCND STL1
DIRCND STL2
STL3
STND

IEC09000884-1-en.vsd
IEC09000884 V1 EN-US

Figure 50: ZMQAPDIS function block (zone 2 - 5)

164 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

The two inputs I3P — Three phase group signal for current and U3P — Three
phase group signal for voltage, must be connected to non-adaptive SMAI
blocks if ANY OF THE ZONES are set for directional operation. That is, the
parameter DFTReference in used SMAI must be set to InternalDFTRef. If
adaptive SMAI block is used this might result in a wrong directional and reach
evaluation.

SEMOD54537-4 v5

ZDRDIR
I3P* STDIRCND
U3P*
IEC10000007-2-en.vsd

IEC10000007 V2 EN-US

Figure 51: ZDRDIR function block

8.1.4 Signals
PID-3651-INPUTSIGNALS v6

Table 94: ZMQPDIS Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
VTSZ BOOLEAN 0 Blocks all output by fuse failure signal
BLKTR BOOLEAN 0 Blocks all trip outputs
STCND INTEGER 0 External start condition (loop enabler)
DIRCND INTEGER 0 External directional condition

PID-3651-OUTPUTSIGNALS v6

Table 95: ZMQPDIS Output signals


Name Type Description
TRIP BOOLEAN General Trip, issued from any phase or loop
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
START BOOLEAN General Start, issued from any phase or loop
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3
STND BOOLEAN Non-directional start, issued from any phase or loop

Line distance protection REL670 165


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

PID-3650-INPUTSIGNALS v6

Table 96: ZMQAPDIS Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
VTSZ BOOLEAN 0 Blocks all output by fuse failure signal
BLKTR BOOLEAN 0 Blocks all trip outputs
STCND INTEGER 0 External start condition (loop enabler)
DIRCND INTEGER 0 External directional condition

PID-3650-OUTPUTSIGNALS v6

Table 97: ZMQAPDIS Output signals


Name Type Description
TRIP BOOLEAN General Trip, issued from any phase or loop
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
START BOOLEAN General Start, issued from any phase or loop
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3
STND BOOLEAN Non-directional start, issued from any phase or loop

PID-3545-INPUTSIGNALS v6

Table 98: ZDRDIR Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL

PID-3545-OUTPUTSIGNALS v5

Table 99: ZDRDIR Output signals


Name Type Description
STDIRCND INTEGER Binary coded directional information per measuring loop

8.1.5 Settings
GUID-62142086-79A9-46FF-A14F-BA0CDD6B6466 v1

Signals and settings for ZMQPDIS are valid for zone 1 while signals and settings
for ZMQAPDIS are valid for zone 2 - 5

166 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

PID-3651-SETTINGS v6

Table 100: ZMQPDIS Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
OperationDir Non-directional - - Forward Operation mode of directionality
Forward NonDir / Forw / Rev
Reverse
X1 0.10 - 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach
R1 0.01 - 1000.00 Ohm/p 0.01 5.00 Positive seq. resistance for zone
characteristic angle
X0 0.10 - 9000.00 Ohm/p 0.01 100.00 Zero sequence reactance reach
R0 0.01 - 3000.00 Ohm/p 0.01 15.00 Zero seq. resistance for zone
characteristic angle
RFPP 0.10 - 3000.00 Ohm/l 0.01 30.00 Fault resistance reach in ohm/loop,
Ph-Ph
RFPE 0.10 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach in ohm/loop,
Ph-E
OperationPP Off - - On Operation mode Off / On of Phase-
On Phase loops
OpModetPP Off - - On Operation mode Off / On of Zone
On timer, Ph-Ph
tPP 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-Ph
OperationPE Off - - On Operation mode Off / On of Phase-
On Earth loops
OpModetPE Off - - On Operation mode Off / On of Zone
On timer, Ph-E
tPE 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-E
IMinOpPP 10 - 1000 %IB 1 20 Minimum operate delta current for
Phase-Phase loops
IMinOpPE 10 - 1000 %IB 1 20 Minimum operate phase current for
Phase-Earth loops
IMinOpIN 5 - 1000 %IB 1 5 Minimum operate residual current for
Phase-Earth loops

Table 101: ZMQPDIS Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

PID-3650-SETTINGS v6

Table 102: ZMQAPDIS Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
OperationDir Non-directional - - Forward Operation mode of directionality
Forward NonDir / Forw / Rev
Reverse
X1 0.10 - 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach
Table continues on next page

Line distance protection REL670 167


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Name Values (Range) Unit Step Default Description


R1 0.01 - 1000.00 Ohm/p 0.01 5.00 Positive seq. resistance for zone
characteristic angle
X0 0.10 - 9000.00 Ohm/p 0.01 120.00 Zero sequence reactance reach
R0 0.01 - 3000.00 Ohm/p 0.01 15.00 Zero seq. resistance for zone
characteristic angle
RFPP 0.10 - 3000.00 Ohm/l 0.01 30.00 Fault resistance reach in ohm/loop,
Ph-Ph
RFPE 0.10 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach in ohm/loop,
Ph-E
OperationPP Off - - On Operation mode Off / On of Phase-
On Phase loops
OpModetPP Off - - On Operation mode Off / On of Zone
On timer, Ph-Ph
tPP 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-Ph
OperationPE Off - - On Operation mode Off / On of Phase-
On Earth loops
OpModetPE Off - - On Operation mode Off / On of Zone
On timer, Ph-E
tPE 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-E
IMinOpPP 10 - 1000 %IB 1 20 Minimum operate delta current for
Phase-Phase loops
IMinOpPE 10 - 1000 %IB 1 20 Minimum operate phase current for
Phase-Earth loops

Table 103: ZMQAPDIS Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

PID-3545-SETTINGS v6

Table 104: ZDRDIR Group settings (basic)


Name Values (Range) Unit Step Default Description
IMinOpPP 5 - 30 %IB 1 10 Minimum operate phase-phase
current for Phase-Phase loops
IMinOpPE 5 - 30 %IB 1 5 Minimum operate phase current for
Phase-Earth loops
ArgNegRes 90 - 175 Deg 1 115 Angle of blinder in second quadrant
for forward direction
ArgDir 5 - 45 Deg 1 15 Angle of blinder in fourth quadrant for
forward direction

Table 105: ZDRDIR Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

168 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

8.1.6 Monitored data


PID-3545-MONITOREDDATA v6

Table 106: ZDRDIR Monitored data


Name Type Values (Range) Unit Description
L1Dir INTEGER 1=Forward - Direction in phase L1
2=Reverse
0=No direction
L2Dir INTEGER 1=Forward - Direction in phase L2
2=Reverse
0=No direction
L3Dir INTEGER 1=Forward - Direction in phase L3
2=Reverse
0=No direction
L1R REAL - Ohm Resistance in phase L1
L1X REAL - Ohm Reactance in phase L1
L2R REAL - Ohm Resistance in phase L2
L2X REAL - Ohm Reactance in phase L2
L3R REAL - Ohm Resistance in phase L3
L3X REAL - Ohm Reactance in phase L3

8.1.7 Operation principle

8.1.7.1 Full scheme measurement M16923-92 v4

The execution of the different fault loops within the IED are of full scheme type, which means
that each fault loop for phase-to-earth faults and phase-to-phase faults for forward and
reverse faults are executed in parallel.

Figure 52 presents an outline of the different measuring loops for up to five, impedance-
measuring zones. There are 3 to 5 zones depending on product type and variant.

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 1

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 2

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 3

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 4

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 5

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1


Zone RV

IEC05000458-2-en.vsd
IEC05000458 V2 EN-US

Figure 52: The different measuring loops at phase-to-earth fault and phase-to-phase
fault.
The use of full scheme technique gives faster operation time compared to switched schemes
which mostly uses a start element to select correct voltages and current depending on fault
type. Each distance protection zone performs like one independent distance protection IED
with six measuring elements.

Line distance protection REL670 169


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

8.1.7.2 Impedance characteristic M16923-100 v8

The distance measuring zone includes six impedance measuring loops; three intended for
phase-to-earth faults, and three intended for phase-to-phase as well as, three-phase faults.

The distance measuring zone will essentially operate according to the non-directional
impedance characteristics presented in figure 53 and figure 54. The phase-to-earth
characteristic is illustrated with the full loop reach while the phase-to-phase characteristic
presents the per phase reach.

X (Ohm/loop)

R1+Rn

RFPE RFPE

X0-X1
Xn =
3
X1+Xn R0-R1
Rn =
3
jN jN
R (Ohm/loop)

RFPE RFPE

X1+Xn

RFPE RFPE
IEC11000427-1-en.vsd

R1+Rn
IEC11000427 V1 EN-US

Figure 53: Characteristic for phase-to-earth measuring, ohm/loop domain

170 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

X (Ohm/phase)

RFPP R1 RFPP
2 2
X 0 PE - X 1RVPE
XNRV =XX00PEPG--X31XRVPE
1RVPG
XNRV =
XNRV =
3 3
XX
X00PE
0PE
PG --1X
-X 11FWPE
XFWPE
FWPG
XNFW =
=
XNFW =
XNFW
X1 3
3 3

j j
R (Ohm/phase)

RFPP RFPP
2 2

X1

RFPP R1 RFPP
2 2
IEC11000428-1-en.vsd
IEC11000428 V1 EN-US

Figure 54: Characteristic for phase-to-phase measuring


The fault loop reach with respect to each fault type may also be presented as in Figure. Note in
particular the difference in definition regarding the (fault) resistive reach for phase-to-phase
faults and three-phase faults.

Line distance protection REL670 171


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

IL1 R1 + j X1
Phase-to-earth
UL1
element

Phase-to-earth
fault in phase L1 RFPE
(Arc + tower
resistance)

0
IN (R0-R1)/3 +
j (X0-X1)/3 )

IL1 R1 + j X1 Phase-to-phase
UL1 element L1-L2
Phase-to-phase
fault in phase RFPP
L1-L2 IL2
UL2 (Arc resistance)
R1 + j X1

IL1 R1 + j X1 0.5·RFPP Phase-to-phase


UL1 element L1-L3
Three-phase
fault
IL3
UL3
R1 + j X1 0.5·RFPP
IEC08000282-2-en.vsd
IEC08000282 V2 EN-US

Figure 55: Fault loop model


The R1 and jX1 55 represents the positive sequence impedance from the measuring point to
the fault location. The settings and RFPP are the eventual fault resistances in the faulty place.

Regarding the illustration of three-phase fault in Figure 55, there is of course fault current
flowing also in the third phase during a three-phase fault. The illustration merely reflects the
loop measurement, which is made phase-to-phase.

The zone can be set to operate in Non-directional, Forward or Reverse direction through the
setting OperationDir. The result from respective set value is illustrated in Figure. The
impedance reach is symmetric, in the sense that it conforms for forward and reverse direction.
Therefore, all reach settings apply to both directions.

172 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

X X X

R R R

Non-directional Forward Reverse

IEC05000182-2-en.vsdx

IEC05000182 V2 EN-US

Figure 56: Directional operating modes of the distance measuring zones


The zone impedance characteristic is a product of the two separate characteristics:

• The quadrilateral characteristic


• The directional characteristic

The estimated impedance needs to be inside both characteristics for the zone to start or trip.
(The non-directional start STND is an exception however. It is only dependent on the
quadrilateral characteristic.)

In the following figure, the zone with the shorter reactive reach follows the directional line
(R∙tan(15⁰)) only up to X1PP, where the quadrilateral characteristic will start to limit the reach.

X (ohm)

X1PP’

X1PP

15° R (ohm)
-X1PP RFPP/2
R· tan15°

-X1PP’
IEC19000141-1-en-us.vsdx

IEC19000141 V1 EN-US

Figure 57: Line distance protection

Line distance protection REL670 173


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

8.1.7.3 Minimum operating current M16923-127 v5

The operation of Distance measuring zones, quadrilateral characteristic (ZMQPDIS) is blocked


if the magnitude of input currents fall below certain threshold values.

The phase-to-earth loop Ln is blocked if ILn < IMinOpPE.

For zone 1 with load compensation feature the additional criterion applies, that all phase-to-
earth loops will be blocked when IN < IMinOpIN, regardless of the phase currents.

ILn is the RMS value of the current in phase Ln. IN is the RMS value of the vector sum of the
three-phase currents, that is, residual current 3I0.

The phase-to-phase loop LmLn is blocked if ILmLn < IMinOpPP.

ILmLn is the RMS value of the vector difference between phase currents Lm and Ln.

All three current limits IMinOpPE, IMinOpIN and IMinOpPP are automatically
reduced to 75% of regular set values if the zone is set to operate in reverse
direction, that is, OperationDir = Reverse.

8.1.7.4 Measuring principles M16923-4 v7

Fault loop equations use the complex values of voltage, current, and changes in the current.
Apparent impedances are calculated and compared with the set limits. The apparent
impedances at phase-to-phase faults follow equation 3 (example for a phase L1 to phase L2
fault).

UL1 – UL2
Zapp = -------------------------
I L1 – IL2
EQUATION1222 V1 EN-US (Equation 3)

Here U and I represent the corresponding voltage and current phasors in the respective phase
Ln (n = 1, 2, 3)

The earth return compensation applies in a conventional manner to phase-to-earth faults


(example for a phase L1 to earth fault) according to equation 4.

U L1
Z app =
I L1 + I N × KN
EQUATION1223 V2 EN-US (Equation 4)

Where:
are the phase voltage, phase current and residual current present to the IED
U L1
I L1
IN

KN
is defined as:

174 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Z 0 - Z1
KN =
3 × Z1
EQUATION-2105 V2 EN-US

Z 0 = R 0 + jX 0
EQUATION2106 V2 EN-US

Z 1 = R1 + jX 1
EQUATION2107 V2 EN-US

Where
R0 is setting of the resistive zero sequence reach
X0 is setting of the reactive zero sequence reach
R1 is setting of the resistive positive sequence reach
X1 is setting of the reactive positive sequence reach

Here IN is a phasor of the residual current in IED point. This results in the same reach along the
line for all types of faults.

The apparent impedance is considered as an impedance loop with resistance R and reactance
X.

The formula given in equation 4 is only valid for radial feeder application without load. When
load is considered in the case of single phase-to-earth fault, conventional distance protection
might overreach at exporting end and underreach at importing end. The IED has an adaptive
load compensation which increases the security in such applications.

Measuring elements receive current and voltage information from the A/D converter. The
check sums are calculated and compared, and the information is distributed into memory
locations. For each of the six supervised fault loops, sampled values of voltage (U), current (I),
and changes in current between samples (DI) are brought from the input memory and fed to a
recursive Fourier filter.

The filter provides two orthogonal values for each input. These values are related to the loop
impedance according to equation 5,

X Di
U = R × i + ------ × -----
w 0 Dt
EQUATION1224 V1 EN-US (Equation 5)

in complex notation, or:

X D Re ( I )
Re ( U ) = R × Re ( I ) + ------ × ------------------
w0 Dt

EQUATION354 V1 EN-US (Equation 6)

X DIm ( I )
Im ( U ) = R × Im ( I ) + ------ × -----------------
w0 Dt

EQUATION355 V1 EN-US (Equation 7)

with

Line distance protection REL670 175


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

w0 = 2 × p × f 0
EQUATION356 V1 EN-US (Equation 8)

where:
Re designates the real component of current and voltage,
Im designates the imaginary component of current and voltage and
f0 designates the rated system frequency

The algorithm calculates Rm measured resistance from the equation for the real value of the
voltage and substitutes it in the equation for the imaginary part. The equation for the Xm
measured reactance can then be solved. The final result is equal to:

Im ( U ) × DRe ( I ) – Re ( U ) × D Im ( I )
R m = ------------------------------------------------------------------------------------
DRe ( I ) × Im ( I ) – D Im ( I ) × Re ( I )
EQUATION357 V1 EN-US (Equation 9)

Re ( U ) × Im ( I ) – Im ( U ) × Re ( I )
Xm = w 0 × Dt × -------------------------------------------------------------------------------
DRe ( I ) × Im ( I ) – DIm ( I ) × Re ( I )
EQUATION358 V1 EN-US (Equation 10)

The calculated Rm and Xm values are updated each sample and compared with the set zone
reach. The adaptive tripping counter counts the number of permissive tripping results. This
effectively removes any influence of errors introduced by the capacitive voltage transformers
or by other factors.

The directional evaluations are performed simultaneously in both forward and reverse
directions, and in all six fault loops. Positive sequence voltage and a phase locked positive
sequence memory voltage are used as a reference. This ensures unlimited directional
sensitivity for faults close to the IED point.

8.1.7.5 Directional impedance element for quadrilateral characteristics M16923-139 v6

The evaluation of the directionality takes place in Directional impedance quadrilateral function
ZDRDIR. Equation 11 and equation 12 are used to classify that the fault is in forward direction
for phase-to-earth fault and phase-to-phase fault.

0.8 × U 1L1 + 0.2 × U 1L1 M


- ArgDir < arg < ArgNeg Re s
I L1
EQUATION725 V2 EN-US (Equation 11)

For the L1-L2 element, the equation in forward direction is according to.

176 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

0.8 × U 1L1 L 2 + 0.2 × U 1L1 L 2 M


- ArgDir < arg < ArgNeg Re s
I L1 L 2
EQUATION726 V2 EN-US (Equation 12)

where:
ArgDir is the setting for the lower boundary of the forward directional characteristic, by default set to
15 (= -15 degrees) and
ArgNegRes is the setting for the upper boundary of the forward directional characteristic, by default set to
115 degrees, see figure 58.
is positive sequence phase voltage in phase L1
U 1L1
is positive sequence memorized phase voltage in phase L1
U 1L1M
is phase current in phase L1
I L1
is voltage difference between phase L1 and L2 (L2 lagging L1)
U 1L1L 2
is memorized voltage difference between phase L1 and L2 (L2 lagging L1)
U 1L1L 2 M
is current difference between phase L1 and L2 (L2 lagging L1)
I L1L 2

The setting of ArgDir and ArgNegRes is by default set to 15 (= -15) and 115 degrees respectively
(as shown in figure 58). It should not be changed unless system studies have shown the
necessity.

ZDRDIR gives binary coded directional information per measuring loop on the output
STDIRCND.

STDIR= STFWL1*1+STFWL2*2+STFWL3*4+STFWL1L2*8+
+STFWL2L3*16+STFWL3L1*32+STRVL1*64+STRVL2*128+
+STRVL3*256+STRVL1L2*512+STRVL2L3*1024+STRVL3L1*2048

Line distance protection REL670 177


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

ArgNegRes

ArgDir
R

en05000722.vsd
IEC05000722 V1 EN-US

Figure 58: Setting angles for discrimination of forward and reverse fault in Directional
impedance quadrilateral function ZDRDIR

The reverse directional characteristic is equal to the forward characteristic rotated by 180
degrees.

The polarizing voltage is available as long as the positive sequence voltage exceeds 5% of the
set base voltage UBase. So the directional element can use it for all unsymmetrical faults
including close-in faults.

For close-in three-phase faults, the U1L1M memory voltage, based on the same positive
sequence voltage, ensures correct directional discrimination.

The memory voltage is used for 100 ms or until the positive sequence voltage is restored.

After 100 ms the following occurs:

• If the current is still above the set value of the minimum operating current (between 10
and 30% of the set IED rated current IBase), the condition seals in.
• If the fault has caused tripping, the trip endures.
• If the fault was detected in the reverse direction, the measuring element in the
reverse direction remains in operation.
• If the current decreases below the minimum operating value, the memory resets until the
positive sequence voltage exceeds 10% of its rated value.

8.1.7.6 Simplified logic diagrams M13841-35 v2

Distance protection zones M13841-10 v9


The design of the distance protection zones are presented for all measuring loops: phase-to-
earth as well as phase-to-phase.

Phase-to-earth related signals are designated by L1N, L2N and L3N. The phase-to-phase
signals are designated by L1L2, L2L3, and L3L1.

178 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Fulfillment of two different measuring conditions is necessary to obtain the one logical signal
for each separate measuring loop:

• Zone measuring condition, which follows the operating equations described above.
• Group functional input signal (STCND), as presented in figure 59.

Two types of function block, ZMQPDIS and ZMQAPDIS, are used in the IED. ZMQPDIS is used
for zone 1 and ZMQAPDIS for zone 2 - 5.

The STCND input signal represents a connection of six different integer values from Phase
selection with load encroachment, quadrilateral characteristic function FDPSPDIS within the
IED, which are converted within the zone measuring function into corresponding boolean
expressions for each condition separately. Input signal STCND is connected to FDPSPDIS or
FMPSPDIS function output STCNDZ.

The input signal DIRCND is used to give condition for directionality for the distance measuring
zones. The signal contains binary coded information for both forward and reverse direction.
The zone measurement function filters out the relevant signals depending on the setting of
the parameter OperationDir. It must be configured to the STDIR output on ZDRDIR function.

STZMPP
OR
STCND

AND STNDL1L2
L1L2

STNDL2L3
L2L3 AND

L3L1 AND STNDL3L1

AND STNDL1N
L1N

AND STNDL2N
L2N

STNDL3N
L3N AND

OR STPE

OR
VTSZ STND
OR AND
BLOCK
BLOCFUNC BLK

99000557-2.vsd
IEC99000557-TIFF V3 EN-US

Figure 59: Conditioning by a group functional input signal STCND, external start
condition
Composition of the phase start signals for a case, when the zone operates in a non-directional
mode, is presented in figure 60.

Line distance protection REL670 179


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

IEC00000488-TIFF V1 EN-US

Figure 60: Composition of starting signals in non-directional operating mode


Results of the directional measurement enter the logic circuits, when the zone operates in
directional (forward or reverse) mode, as shown in figure 61.

STNDL1N
AND
DIRL1N
STZMPE.
OR
STNDL2N
DIRL2N AND

STNDL3N 15 ms
OR STL1
AND AND t
DIRL3N

STNDL1L2
DIRL1L2 AND 15 ms
OR STL2
AND t
STNDL2L3
DIRL2L3 AND
15 ms
OR STL3
STNDL3L1 AND t
DIRL3L1 AND

STZMPP
OR

BLK

15 ms
OR START
AND t

IEC09000888-2-en.vsd
IEC09000888 V2 EN-US

Figure 61: Composition of start signals in directional operating mode


Tripping conditions for the distance protection zone one are symbolically presented in figure
62.

180 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Timer tPP=On
STZMPP AND tPP
AND
t

BLOCFUNC
OR OR
tPE
t
AND
Timer tPE=On AND
STZMPE 15ms
BLKTR AND t
TRIP
BLK OR

STL1 AND TRL1

STL2 AND TRL2

STL3 AND TRL3

IEC09000887-3-en.vsdx

IEC09000887 V3 EN-US

Figure 62: Tripping logic for the distance protection zone

8.1.8 Technical data IP12804-1 v1

M13842-1 v15

Table 107: ZMQPDIS Technical data


Function Range or value Accuracy
Number of zones Max 5 with selectable -
direction
Minimum operate residual (5-1000)% of IBase -
current, zone 1
Minimum operate current, (10-1000)% of IBase -
phase-to-phase and phase-to-
earth
Positive sequence reactance (0.10-3000.00) Ω/phase ±2.0% static accuracy
±2.0 degrees static angular accuracy
Positive sequence resistance (0.01-1000.00) Ω/phase Conditions:
Zero sequence reactance (0.10-9000.00) Ω/phase Voltage range: (0.1-1.1) x Ur
Current range: (0.5-30) x Ir
Angle: at 0 degrees and 85 degrees
Zero sequence resistance (0.01-3000.00) Ω/phase
Fault resistance, phase-to- (0.10-9000.00) Ω/loop
earth
Fault resistance, phase-to- (0.10-3000.00) Ω/loop
phase
Dynamic overreach <5% at 85 degrees -
measured with CVT’s
and 0.5<SIR<30
Definite time delay Ph-Ph and (0.000-60.000) s ±0.2% or ±40 ms whichever is greater
Ph-E operation
Table continues on next page

Line distance protection REL670 181


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Function Range or value Accuracy


Operate time 25 ms typically IEC 60255-121
Reset ratio 105% typically -
Reset time at 0.1 x Zreach to 2 Min. = 20 ms -
x Zreach Max. = 50 ms

8.2 Phase selection, quad, fixed angle, load encroachment


FDPSPDIS IP12400-1 v4

8.2.1 Identification

8.2.1.1 Identification M14850-1 v6

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Phase selection, quad, fixed angle, FDPSPDIS 21
load encroachment
Z<phs

SYMBOL-DD V1 EN-US

8.2.2 Functionality M13139-3 v9

The operation of transmission networks today is in many cases close to the stability limit. Due
to environmental considerations, the rate of expansion and reinforcement of the power
system is reduced, for example, difficulties to get permission to build new power lines. The
ability to accurately and reliably classify the different types of fault, so that single pole tripping
and autoreclosing can be used plays an important role in this matter. Phase selection,
quadrilateral characteristic with fixed angle (FDPSPDIS) is designed to accurately select the
proper fault loop in the distance function dependent on the fault type.

The heavy load transfer that is common in many transmission networks may make fault
resistance coverage difficult to achieve. Therefore, FDPSPDIS has a built-in algorithm for load
encroachment, which gives the possibility to enlarge the resistive setting of both the phase
selection and the measuring zones without interfering with the load.

The extensive output signals from the phase selection gives also important information about
faulty phase(s), which can be used for fault analysis.

A current-based phase selection is also included. The measuring elements continuously


measure three phase currents and the residual current and, compare them with the set values.

182 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

8.2.3 Function block M13147-3 v4

FDPSPDIS
I3P* TRIP
U3P* START
BLOCK STFWL1
DIRCND STFWL2
STFWL3
STFWPE
STRVL1
STRVL2
STRVL3
STRVPE
STNDL1
STNDL2
STNDL3
STNDPE
STFW1PH
STFW2PH
STFW3PH
STPE
STPP
STCNDZ
STCNDLE

IEC14000047-1-en.vsd
IEC10000047 V2 EN-US

Figure 63: FDPSPDIS function block

8.2.4 Signals
PID-3642-INPUTSIGNALS v7

Table 108: FDPSPDIS Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
DIRCND INTEGER 0 External directional condition

PID-3642-OUTPUTSIGNALS v7

Table 109: FDPSPDIS Output signals


Name Type Description
TRIP BOOLEAN Trip output
START BOOLEAN Start in any phase or loop
STFWL1 BOOLEAN Fault detected in phase L1 - forward direction
STFWL2 BOOLEAN Fault detected in phase L2 - forward direction
STFWL3 BOOLEAN Fault detected in phase L3 - forward direction
STFWPE BOOLEAN Earth fault detected in forward direction
STRVL1 BOOLEAN Fault detected in phase L1 - reverse direction
STRVL2 BOOLEAN Fault detected in phase L2 - reverse direction
STRVL3 BOOLEAN Fault detected in phase L3 - reverse direction
STRVPE BOOLEAN Earth fault detected in reverse direction
STNDL1 BOOLEAN Non directional start in L1
STNDL2 BOOLEAN Non directional start in L2
Table continues on next page

Line distance protection REL670 183


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Name Type Description


STNDL3 BOOLEAN Non directional start in L3
STNDPE BOOLEAN Non directional start, phase-earth
STFW1PH BOOLEAN Start in forward direction for single-phase fault
STFW2PH BOOLEAN Start in forward direction for two- phase fault
STFW3PH BOOLEAN Start in forward direction for thre-phase fault
STPE BOOLEAN Current conditions release of phase-earth measuring
elements
STPP BOOLEAN Current conditions release of phase-phase measuring
elements
STCNDZ INTEGER Start condition (Z< with LE and 3I0 E/F detection)
STCNDLE INTEGER Start condition (only LE and 3I0 E/F detection)

8.2.5 Settings
PID-3642-SETTINGS v7

Table 110: FDPSPDIS Group settings (basic)


Name Values (Range) Unit Step Default Description
INBlockPP 10 - 100 %IPh 1 40 3I0 limit for blocking phase-to-phase
measuring loops
INReleasePE 10 - 100 %IPh 1 20 3I0 limit for releasing phase-to-earth
measuring loops
RLdFw 1.00 - 3000.00 Ohm/p 0.01 80.00 Forward resistive reach within the
load impedance area
RLdRv 1.00 - 3000.00 Ohm/p 0.01 80.00 Reverse resistive reach within the load
impedance area
ArgLd 5 - 70 Deg 1 30 Load angle determining the load
impedance area
X1 0.50 - 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach
X0 0.50 - 9000.00 Ohm/p 0.01 120.00 Zero sequence reactance reach
RFFwPP 0.50 - 3000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, forward
RFRvPP 0.50 - 3000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, reverse
RFFwPE 1.00 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-E, forward
RFRvPE 1.00 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-E, reverse
IMinOpPP 5 - 500 %IB 1 10 Minimum operate delta current for
Phase-Phase loops
IMinOpPE 5 - 500 %IB 1 5 Minimum operate phase current for
Phase-Earth loops

Table 111: FDPSPDIS Group settings (advanced)


Name Values (Range) Unit Step Default Description
OperationZ< Off - - On Operation of impedance based
On measurement
OperationI> Off - - Off Operation of current based
On measurement
IPh> 10 - 2500 %IB 1 120 Start value for phase over-current
element
Table continues on next page

184 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Name Values (Range) Unit Step Default Description


IN> 10 - 2500 %IB 1 20 Start value for trip from 3I0 over-
current element
TimerPP Off - - Off Operation mode Off / On of Zone
On timer, Ph-Ph
tPP 0.000 - 60.000 s 0.001 3.000 Time delay to trip, Ph-Ph
TimerPE Off - - Off Operation mode Off / On of Zone
On timer, Ph-E
tPE 0.000 - 60.000 s 0.001 3.000 Time delay to trip, Ph-E

Table 112: FDPSPDIS Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

8.2.6 Operation principle


M13140-3 v6
The basic impedance algorithm for the operation of the phase selection measuring elements is
the same as for the distance zone measuring function. Phase selection with load
encroachment, quadrilateral characteristic FDPSPDIS includes six impedance measuring loops;
three intended for phase-to-earth faults, and three intended for phase-to-phase faults as well
as for three-phase faults.

The difference, compared to the distance zone measuring function, is in the combination of
the measuring quantities (currents and voltages) for different types of faults.

A current-based phase selection is also included. The measuring elements continuously


measure three phase currents and the residual current, and compare them with the set values.
The current signals are filtered by Fourier's recursive filter, and separate trip counter prevents
too high overreaching of the measuring elements.

The characteristic is basically non-directional, but FDPSPDIS uses information from the
directional function to discriminate whether the fault is in forward or reverse direction.

The start condition STCNDZ is essentially based on the following criteria:

1. Residual current criteria, that is, separation of faults with and without earth connection
2. Regular quadrilateral impedance characteristic or current based criteria
3. Load encroachment characteristics is always active but can be switched off by selecting a
high setting.

The current start condition STCNDLE is based on the following criteria:

1. Residual current criteria


2. No quadrilateral impedance characteristic. The impedance reach outside the load area is
theoretically infinite. The practical reach, however, will be determined by the minimum
operating current limits.
3. Load encroachment characteristic is always active, but can be switched off by selecting a
high setting.

The STCNDLE output is non-directional. The directionality is determined by the distance zones
directional function. There are outputs from FDPSPDIS that indicate whether a start is in
forward or reverse direction or non-directional, for example STFWL1, STRVL1 and STNDL1.

Line distance protection REL670 185


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

These directional indications are based on the sector boundaries of the directional function
and the impedance setting of FDPSPDIS function. Their operating characteristics are
illustrated in figure 64.

X X X

R
R R

Non-directional (ND) Forward (FW) Reverse (RV)

en08000286.vsd
IEC08000286 V1 EN-US

Figure 64: Characteristics for non-directional, forward and reverse operation of Phase
selection with load encroachment, quadrilateral characteristic FDPSPDIS
The setting of the load encroachment function may influence the total operating
characteristic, (for more information, refer to section "Load encroachment").

The input DIRCND contains binary coded information about the directional coming from the
directional function . It shall be connected to the STDIR output on ZDRDIR, directional
measuring block. This information is also transferred to the input DIRCND on the distance
measuring zones, that is, the ZMQPDIS, distance measuring block.

The code built up for the directionality is as follows:

STDIR= STFWL1*1+STFWL2*2+STFWL3*4+STFWL1L2*8+
+STFWL2L3*16+STFWL3L1*32+STRVL1*64+STRVL2*128+
+STRVL3*256+STRVL1L2*512+STRVL2L3*1024+STRVL3L1*2048

If the binary information is 1 then it will be considered that we have start in forward direction
in phase L1. If the binary code is 3 then we have start in forward direction in phase L1 and L2,
binary code 192 means start in reverse direction in phase L1 and L2A and B etc.

The STCNDZ or STCNDLE output contains, in a similar way as DIRCND, binary coded
information, in this case information about the condition for opening correct fault loop in the
distance measuring element. It shall be connected to the STCND input on the ZMQPDIS,
distance measuring block.

The code built up for release of the measuring fault loops is as follows:

STCND = L1N*1 + L2N*2 + L3N*4 + L1L2*8 + L2L3*16 + L3L1*32

8.2.6.1 Phase-to-earth fault M13140-22 v3

For a phase-to-earth fault, the measured impedance by FDPSPDIS will be according to


equation 13.

186 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Index PHS in images and equations reference settings for Phase selection with
load encroachment function FDPSPDIS.

ULn
ZPHSn =
ILn
EQUATION1255 V1 EN-US (Equation 13)

where:
n corresponds to the particular phase (n=1, 2 or 3)

The characteristic for FDPSPDIS function at phase-to-earth fault is according to figure 65. The
characteristic has a fixed angle for the resistive boundary in the first quadrant of 60°.

The resistance RN and reactance XN are the impedance in the earth-return path defined
according to equation 14 and equation 15.

R0 - R1
RN =
3
EQUATION1256 V1 EN-US (Equation 14)

X 0 - X1
XN =
3
EQUATION1257 V1 EN-US (Equation 15)

X (ohm/loop)
Kr·(X1+XN)

RFRvPE RFFwPE

X1+XN

60 deg
RFFwPE

RFRvPE R (Ohm/loop)
60 deg
X1+XN

1
Kr =
tan(60deg)

RFRvPE RFFwPE

Kr·(X1+XN)
en06000396.vsd
IEC06000396 V2 EN-US

Figure 65: Characteristic of FDPSPDIS for phase-to-earth fault (setting parameters in


italic), ohm/loop domain (directional lines are drawn as "line-dot-dot-line")

Line distance protection REL670 187


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Besides this, the 3I0 residual current must fulfil the conditions according to equation 16 and
equation 17.

3 × I0 ³ 0.5 × IMinOpPE
EQUATION2108 V1 EN-US (Equation 16)

3 × I0 ³ INReleasePE
------------------------------------ × Iphmax
100
EQUATION766 V1 EN-US (Equation 17)

where:
IMinOpPE is the minimum operation current for forward zones
INReleasePE is the setting for the minimum residual current needed to enable operation in the phase-to-
earth fault loops (in %).
Iphmax is the maximum phase current in any of three phases.

8.2.6.2 Phase-to-phase fault M13140-56 v3

For a phase-to-phase fault, the measured impedance by FDPSPDIS will be according to


equation 18.

ULm - ULn
ZPHS =
-2 × ILn
EQUATION1258 V1 EN-US (Equation 18)

ULm is the leading phase voltage, ULn the lagging phase voltage and ILn the phase current in
the lagging phase n.

The operation characteristic is shown in figure 66.

188 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

X (W / phase)
0.5·RFRvPP 0.5·RFFwPP

Kr·X1

X1
0.5·RFFwPP
60 deg

R (W / phase)
60 deg
0.5·RFRvPP
X1
1
Kr =
tan(60 deg)

Kr·X1

0.5·RFRvPP 0.5·RFFwPP
IEC09000047-2-en.vsd
IEC09000047 V2 EN-US

Figure 66: The operation characteristics for FDPSPDIS at phase-to-phase fault (setting
parameters in italic, directional lines drawn as "line-dot-dot-line"), ohm/phase
domain
In the same way as the condition for phase-to-earth fault, there are current conditions that
have to be fulfilled in order to release the phase-to-phase loop. Those are according to
equation 19 or equation 20.

3I 0 < IMinOpPE
EQUATION2109 V1 EN-US (Equation 19)

INBlockPP
3I 0 < × Iph max
100
EQUATION2110 V1 EN-US (Equation 20)

where:
IMinOpPE is the minimum operation current for earth measuring loops,
INBlockPP is 3I0 limit for blocking phase-to-phase measuring loop and
Iphmax is maximal magnitude of the phase currents.

8.2.6.3 Three-phase faults M13140-80 v4

The operation conditions for three-phase faults are the same as for phase-to-phase fault, that
is equation , equation and equation are used to release the operation of the function.

However, the reach is expanded by a factor 2/√3 (approximately 1.1547) in all directions. At the
same time the characteristic is rotated 30 degrees, counter-clockwise. The characteristic is
shown in figure 67.

Line distance protection REL670 189


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

X (ohm/phase)

4 × X1
3

90 deg

0.5·RFFwPP·K3

X1·K3 4 × RFFwPP
6

R (ohm/phase)

0.5·RFRvPP·K3
2
K3 =
3 30 deg

IEC05000671-5-en.vsd
IEC05000671 V5 EN-US

Figure 67: The characteristic of FDPSPDIS for three-phase fault (setting parameters in
italic)

8.2.6.4 Load encroachment M13140-86 v6

Each of the six measuring loops has its own load encroachment characteristic based on the
corresponding loop impedance. The load encroachment functionality is always active, but can
be switched off by selecting a high setting.

The outline of the characteristic is presented in figure 68. As illustrated, the resistive blinders
are set individually in forward and reverse direction while the angle of the sector is the same in
all four quadrants.

190 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

RLdFw
ArgLd ArgLd
R

ArgLd ArgLd
RLdRv

IEC09000042-1-en.vsd
IEC09000042 V1 EN-US

Figure 68: Characteristic of load encroachment function


The influence of load encroachment function on the operation characteristic is dependent on
the chosen operation mode of FDPSPDIS function. When output signal STCNDZ is selected, the
characteristic for FDPSPDIS (and also zone measurement depending on settings) will be
reduced by the load encroachment characteristic (see figure 69, left illustration).

When output signal STCNDLE is selected, the operation characteristic will be as the right
illustration in figure 69. The reach will in this case be limit by the minimum operation current
and the distance measuring zones.

X X

R R

STCNDZ STCNDLE

IEC10000099-1-
en.vsd
IEC10000099 V1 EN-US

Figure 69: Difference in operating characteristic depending on operation mode when


load encroachment is activated

Line distance protection REL670 191


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

When FDPSPDIS is set to operate together with a distance measuring zone the resultant
operate characteristic could look like in figure 70. The figure shows a distance measuring zone
operating in forward direction. Thus, the operating area is highlighted in black.

"Phase selection"
"quadrilateral" zone

Distance measuring zone

Load encroachment
characteristic

Directional line

en05000673.vsd
IEC05000673 V1 EN-US

Figure 70: Operating characteristic in forward direction when load encroachment is


activated
Figure 70 is valid for phase-to-earth. During a three-phase fault, or load, when the quadrilateral
phase-to-phase characteristic is subject to enlargement and rotation the operate area is
transformed according to figure 71. Notice in particular what happens with the resistive
blinders of the "phase selection" "quadrilateral" zone. Due to the 30-degree rotation, the angle
of the blinder in quadrant one is now 90 degrees instead of the original 60 degrees. The
blinder that is nominally located to quadrant four will at the same time tilt outwards and
increase the resistive reach around the R-axis. Consequently, it will be more or less necessary
to use the load encroachment characteristic in order to secure a margin to the load
impedance.

192 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

X (W / phase)
Phase selection
”Quadrilateral” zone

Distance measuring zone

R (W / phase)

IEC09000049-1-en.vsd
IEC09000049 V1 EN-US

Figure 71: Operating characteristic for FDPSPDIS in forward direction for three-phase
fault, ohm/phase domain
The result from rotation of the load characteristic at a fault between two phases is presented
in fig 72. Since the load characteristic is based on the same measurement as the quadrilateral
characteristic, it will rotate with the quadrilateral characteristic clockwise by 30 degrees when
subject to a pure phase-to-phase fault. At the same time the characteristic will "shrink",
divided by 2/√3, from the full RLdFw and RLdRv reach, which is valid at load or three-phase
fault.

Line distance protection REL670 193


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

IEC08000437.vsd

IEC08000437 V1 EN-US

Figure 72: Rotation of load characteristic for a fault between two phases
There is a gain in selectivity by using the same measurement as for the quadrilateral
characteristic since not all phase-to-phase loops will be fully affected by a fault between two
phases. It should also provide better fault resistive coverage in quadrant one. The relative loss
of fault resistive coverage in quadrant four should not be a problem even for applications on
series compensated lines.

8.2.6.5 Minimum operate currents M13140-102 v3

The operation of the Phase selection with load encroachment function (FDPSPDIS) is blocked if
the magnitude of input currents falls below certain threshold values.

The phase-to-earth loop Ln is blocked if ILn<IMinOpPE, where ILn is the RMS value of the
current in phase Ln.

The phase-to-phase loop LmLn is blocked if (2·ILn<IMinOpPP).

8.2.6.6 Simplified logic diagrams M13140-107 v7

Figure 73 presents schematically the general logic diagram for phase-selection function.

194 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

INMag Residual current 
based PhSel.
INReleasePE
STPP
PP
INBLOCKPP STPE
PE

Imin

I3P PP
PE STZPHLmn AND
PHSLmn
X
OR
U3P STZPHLm

R,X settings R
LEPHLm AND PHSLm
OR
Binary to word
LEPHLmn
OperationZ< Enable
b1 – b3
word
b4 – b6
IPELm
IL1 IRELPE
Set level

IPh> T
IRELPP STCNDZ
IN> AND 63 F
t

OperationI> Binary to word
b1 – b3
OR
STCNDLE
word
Relative current  AND b4 – b6
IPELm RELPHLmn AND
based PP release 
detection

IEC18000010-2-en.vsdx
  m = L1G, L2G, L3G
mn = L1L2, L2L3, L3L1
IEC18000010 V2 EN-US

Figure 73: General phase-selection logic diagram


Figure 74 presents schematically the creation of the phase-to-phase and phase-to-earth
operating conditions. Consider only the corresponding part of measuring and logic circuits,
when only a phase-to-earth or phase-to-phase measurement is available within the IED.

OperationZ<
AND
LDEblock

3I 0  0.5  IMinOpPE IRELPE

& 15 ms
AND t STPE
INReleasePE
3I 0   Iphmax
100 STCNDLE
Bool to AND
BLOCK integer

15 ms
3I 0  IMinOpPE 10 ms 20 ms & t STPP

OR AND t t
IRELPP
INBlockPP
3I 0   Iphmax
100

IEC09000149-3-en.vsd
IEC09000149 V3 EN-US

Figure 74: Phase-to-phase and phase-to-earth operating conditions (residual current


criteria)
A special attention is paid to correct phase selection at evolving faults. A STCNDLE output
signal is created as a combination of the load encroachment characteristic and current
criteria, refer to figure 74. This signal can be configured to STCND functional input signals of
the distance protection zone and this way influence the operation of the phase-to-phase and
phase-to-earth zone measuring elements, residual current and the load encroachment
characteristic.

Line distance protection REL670 195


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Figure 75 presents schematically the composition of non-directional phase selective signals


STNDLn. Internal signals ZMLnN and ZMLmLn (m and n change between one and three
according to the phase number) represent the fulfilled operating criteria for each separate
loop measuring element, that is, within the impedance characteristic. These signals are
released if the setting OperationZ< is set to On. Similarly, another group of internal signals
ILm and ILn represent the fulfilled phase current measurement criteria, which are released by
setting the OperationI> parameter to On.

INDL1N
INDL2N
INDL3N

15 ms
STNDPE
IRELPE OR t

LDEblockL1N
IL1 AND 15 ms
OR STNDL1
ZML1N OR t
LDEblockL2N
IL2 AND
OR
ZML2N 15 ms
LDEblockL3N STNDL2
OR t
IL3 AND
OR
ZML3N
LDEblockL1L2 15 ms
STNDL3
IL1 & IL2 AND OR t
OR
ZML1L2
LDEblockL2L3
IL2 & IL3 AND INDL1L2
OR
ZML2L3 INDL2L3
LDEblockL3L1
IL3 & IL1 AND
OR INDL3L1
ZML3L1
IRELPP 15 ms
STNDPP
OR t

IEC00000545-4-en.vsd
IEC00000545-TIFF V4 EN-US

Figure 75: Composition on non-directional phase selection signals


Composition of the directional (forward and reverse) phase selective signals is presented
schematically in figure 77 and figure 76. The directional criteria appears as a condition for the
correct phase selection in order to secure a high phase selectivity for simultaneous and
evolving faults on lines within the complex network configurations. Internal signals DFWLn and
DFWLnLm present the corresponding directional signals for measuring loops with phases Ln
and Lm. Designation FW (figure 77) represents the forward direction as well as the designation
RV (figure 76) represents the reverse direction. All directional signals are derived within the
corresponding digital signal processor.

Figure 76 presents additionally a composition of a STCNDZ output signal, which is created on


the basis of the continuation of the impedance measuring conditions and the load
encroachment characteristic. This signal can be configured to STCND functional input signals
of the distance protection zone and this way influence the operation of the phase-to-phase
and phase-to-earth zone measuring elements and their phase related starting and tripping
signals.

196 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

INDL1N
AND
DRVL1N
INDL1L2 15 ms STRVL1
AND OR t
DRVL1L2
INDL3L1
AND
DRVL3L1 15 ms
STRVPE
INDL2N OR t
AND
DRVL2N
INDL1L2 15 ms
STRVL2
AND OR t

INDL2L3 INDL1N
AND INDL2N
DRVL2L3
INDL3N Bool to STCNDZ
INDL3N INDL1L2 integer
AND INDL2L3
DRVL3N INDL3L1
INDL2L3 15 ms
STRVL3
AND OR t

INDL3L1
15 ms
AND STRVPP
OR t

IEC00000546_2_en.vsd
IEC00000546-TIFF V2 EN-US

Figure 76: Composition of phase selection signals for reverse direction

AND

INDL1N
AND 15 ms 15 ms
DFWL1N STFW1PH
AND OR t t
INDL1L2
15 ms STFWL1
AND OR t
DFWL1L2
INDL3L1
AND
AND
DFWL3L1 15 ms
STFWPE
INDL2N OR t
AND
DFWL2N
AND 15 ms
INDL1L2 STFWL2
t
AND OR
15 ms 15 ms
INDL2L3 STFW2PH
AND OR t t
AND
DFWL2L3
INDL3N
AND AND
DFWL3N 15 ms
STFWL3
t
INDL2L3
AND OR
15 ms
INDL3L1 STFW3PH
AND t
AND

15 ms
STFWPP
OR t

IEC05000201_2_en.vsd

IEC05000201 V2 EN-US

Figure 77: Composition of phase selection signals for forward direction

Line distance protection REL670 197


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Figure 78 presents the composition of output signals TRIP and START, where internal signals
STNDPP, STFWPP and STRVPP are the equivalent to internal signals STNDPE, STFWPE and
STRVPE, but for the phase-to-phase loops.

TimerPP=Off
tPP
AND AND
t
TRIP
OR OR
tPE
TimerPE=Off
t
AND AND

STNDPP

STFWPP OR
STRVPP
START
OR
STNDPE

STFWPE OR
STRVPE

IEC08000441_2_en.vsd
IEC08000441-1 V2 EN-US

Figure 78: TRIP and START signal logic

198 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

8.2.7 Technical data


M16024-1 v12

Table 113: FDPSPDIS technical data


Function Range or value Accuracy
Minimum operate current (5-500)% of IBase ±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir

Reactive reach, positive (0.50–3000.00) Ω/phase ±2.5% static accuracy


sequence ±2.0 degrees static angular accuracy
Conditions:
Resistive reach, positive (0.10–1000.00) Ω/phase Voltage range: (0.1-1.1) x Ur
sequence
Current range: (0.5-30) x Ir
Reactive reach, zero sequence (0.50–9000.00) Ω/phase Angle: at 0 degrees and 85 degrees

Resistive reach, zero sequence (0.50–3000.00) Ω/phase


Fault resistance, phase-to- (1.00–9000.00) Ω/loop
earth faults, forward and
reverse
Fault resistance, phase-to- (0.50–3000.00) Ω/loop
phase faults, forward and
reverse
Load encroachment criteria:
Load resistance, forward and (1.00–3000.00) Ω/phase
reverse (5-70) degrees
Safety load impedance angle
Reset ratio 105% typically -

8.3 Distance measuring zone, quadrilateral characteristic


for series compensated lines ZMCPDIS, ZMCAPDIS,
ZDSRDIR SEMOD168167-1 v3

8.3.1 Identification
SEMOD168165-2 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Distance measuring zone, ZMCPDIS 21
quadrilateral characteristic for series
compensated lines (zone 1) Z
S00346 V2 EN-US

Distance measuring zone, ZMCAPDIS 21


quadrilateral characteristic for series
compensated lines (zone 2-5) Z
S00346 V2 EN-US

Directional impedance quadrilateral, ZDSRDIR 21D


including series compensation
Z<->

IEC09000167 V1 EN-US

Line distance protection REL670 199


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

8.3.2 Functionality SEMOD168173-4 v11

The line distance protection is an up to five (depending on product variant) zone full scheme
protection with three fault loops for phase-to-phase faults and three fault loops for phase-to-
earth fault for each of the independent zones. Individual settings for each zone resistive and
reactive reach give flexibility for use on overhead lines and cables of different types and
lengths.

Quadrilateral characteristic is available.

Distance measuring zone, quadrilateral characteristic for series compensated lines (ZMCPDIS)
function has functionality for load encroachment which increases the possibility to detect high
resistive faults on heavily loaded lines.

Forward
operation

Reverse
operation

en05000034.vsd
IEC05000034 V1 EN-US

Figure 79: Typical quadrilateral distance protection zone with load encroachment
function activated
The independent measurement of impedance for each fault loop together with a sensitive and
reliable built in phase selection makes the function suitable in applications with single phase
auto-reclosing.

Built-in adaptive load compensation algorithm for the quadrilateral function prevents
overreaching of zone1 at load exporting end at phase to earth-faults on heavily loaded power
lines.

The distance protection zones can operate, independent of each other, in directional (forward
or reverse) or non-directional mode. This makes them suitable, together with different
communication schemes, for the protection of power lines and cables in complex network
configurations, such as parallel lines, multi-terminal lines.

200 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

8.3.3 Function block SEMOD168196-1 v2

SEMOD168198-4 v2

ZMCPDIS
I3P* TRIP
U3P* TRL1
BLOCK TRL2
VTSZ TRL3
BLKTR START
STCND STL1
DIRCND STL2
STL3
STND

IEC07000036-2-en.vsd
IEC07000036 V2 EN-US

Figure 80: ZMCPDIS function block

ZMCAPDIS
I3P* TRIP
U3P* TRL1
BLOCK TRL2
VTSZ TRL3
BLKTR START
STCND STL1
DIRCND STL2
STL3
STND

IEC09000890-1-en.vsd
IEC09000890 V1 EN-US

Figure 81: ZMCAPDIS function block


SEMOD168200-4 v2

ZDSRDIR
I3P* STFW
U3P* STRV
STDIRCND

IEC07000035-2-en.vsd
IEC07000035 V2 EN-US

Figure 82: ZDSRDIR function block

8.3.4 Signals SEMOD173074-1 v3

Input and output signals is shown for zone 1, zone 2 - 5 are equal.

PID-3639-INPUTSIGNALS v6

Table 114: ZMCPDIS Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
VTSZ BOOLEAN 0 Blocks all output by fuse failure signal
BLKTR BOOLEAN 0 Blocks all trip outputs
STCND INTEGER 0 External start condition (loop enabler)
DIRCND INTEGER 0 External directional condition

Line distance protection REL670 201


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

PID-3639-OUTPUTSIGNALS v6

Table 115: ZMCPDIS Output signals


Name Type Description
TRIP BOOLEAN General Trip, issued from any phase or loop
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
START BOOLEAN General Start, issued from any phase or loop
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3
STND BOOLEAN Non-directional start, issued from any phase or loop

PID-3637-INPUTSIGNALS v6

Table 116: ZMCAPDIS Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
VTSZ BOOLEAN 0 Blocks all output by fuse failure signal
BLKTR BOOLEAN 0 Blocks all trip outputs
STCND INTEGER 0 External start condition (loop enabler)
DIRCND INTEGER 0 External directional condition

PID-3637-OUTPUTSIGNALS v6

Table 117: ZMCAPDIS Output signals


Name Type Description
TRIP BOOLEAN General Trip, issued from any phase or loop
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
START BOOLEAN General Start, issued from any phase or loop
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3
STND BOOLEAN Non-directional start, issued from any phase or loop

202 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

PID-3547-INPUTSIGNALS v6

Table 118: ZDSRDIR Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL

PID-3547-OUTPUTSIGNALS v6

Table 119: ZDSRDIR Output signals


Name Type Description
STFW BOOLEAN Start in forward direction
STRV BOOLEAN Start in reverse direction
STDIRCND INTEGER Binary coded directional information per measuring loop

8.3.5 Settings SEMOD173077-1 v3

Settings for ZMCPDIS are valid for zone 1, while settings for ZMCAPDIS are valid
for zone 2 - 5

PID-3639-SETTINGS v6

Table 120: ZMCPDIS Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
OperationDir Non-directional - - Forward Operation mode of directionality
Forward NonDir / Forw / Rev
Reverse
OperationPP Off - - On Operation mode Off / On of Phase-
On Phase loops
X1FwPP 0.10 - 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach,
Ph-Ph, forward
R1PP 0.01 - 1000.00 Ohm/p 0.01 5.00 Positive seq. resistance for
characteristic angle, Ph-Ph
RFFwPP 0.10 - 3000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, forward
X1RvPP 0.10 - 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach,
Ph-Ph, reverse
RFRvPP 0.10 - 3000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, reverse
OpModetPP Off - - On Operation mode Off / On of Zone
On timer, Ph-Ph
tPP 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-Ph
OperationPE Off - - On Operation mode Off / On of Phase-
On Earth loops
X1FwPE 0.10 - 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach,
Ph-E, forward
R1PE 0.01 - 1000.00 Ohm/p 0.01 5.00 Positive seq. resistance for
characteristic angle, Ph-E
Table continues on next page

Line distance protection REL670 203


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Name Values (Range) Unit Step Default Description


X0PE 0.10 - 9000.00 Ohm/p 0.01 100.00 Zero sequence reactance reach, Ph-E
R0PE 0.01 - 3000.00 Ohm/p 0.01 47.00 Zero seq. resistance for zone
characteristic angle, Ph-E
RFFwPE 0.10 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-E, forward
X1RvPE 0.10 - 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach,
Ph-E, reverse
RFRvPE 0.10 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-E, reverse
OpModetPE Off - - On Operation mode Off / On of Zone
On timer, Ph-E
tPE 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-E
IMinOpPP 10 - 1000 %IB 1 20 Minimum operate delta current for
Phase-Phase loops
IMinOpPE 10 - 1000 %IB 1 20 Minimum operate phase current for
Phase-Earth loops
IMinOpIN 5 - 1000 %IB 1 5 Minimum operate residual current for
Phase-Earth loops

Table 121: ZMCPDIS Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

PID-3637-SETTINGS v6

Table 122: ZMCAPDIS Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
OperationDir Non-directional - - Forward Operation mode of directionality
Forward NonDir / Forw / Rev
Reverse
OperationPP Off - - On Operation mode Off / On of Phase-
On Phase loops
X1FwPP 0.10 - 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach,
Ph-Ph, forward
R1PP 0.01 - 1000.00 Ohm/p 0.01 5.00 Positive seq. resistance for
characteristic angle, Ph-Ph
RFFwPP 0.10 - 3000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, forward
X1RvPP 0.10 - 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach,
Ph-Ph, reverse
RFRvPP 0.10 - 3000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, reverse
OpModetPP Off - - On Operation mode Off / On of Zone
On timer, Ph-Ph
tPP 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-Ph
OperationPE Off - - On Operation mode Off / On of Phase-
On Earth loops
X1FwPE 0.10 - 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach,
Ph-E, forward
Table continues on next page

204 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Name Values (Range) Unit Step Default Description


R1PE 0.01 - 1000.00 Ohm/p 0.01 5.00 Positive seq. resistance for
characteristic angle, Ph-E
X0PE 0.10 - 9000.00 Ohm/p 0.01 100.00 Zero sequence reactance reach, Ph-E
R0PE 0.01 - 3000.00 Ohm/p 0.01 47.00 Zero seq. resistance for zone
characteristic angle, Ph-E
RFFwPE 0.10 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-E, forward
X1RvPE 0.10 - 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach,
Ph-E, reverse
RFRvPE 0.10 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-E, reverse
OpModetPE Off - - On Operation mode Off / On of Zone
On timer, Ph-E
tPE 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-E
IMinOpPP 10 - 1000 %IB 1 20 Minimum operate delta current for
Phase-Phase loops
IMinOpPE 10 - 1000 %IB 1 20 Minimum operate phase current for
Phase-Earth loops

Table 123: ZMCAPDIS Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

PID-3547-SETTINGS v6

Table 124: ZDSRDIR Group settings (basic)


Name Values (Range) Unit Step Default Description
OperationSC NoSeriesComp - - SeriesComp Special directional criteria for voltage
SeriesComp reversal
IMinOpPE 5 - 30 %IB 1 5 Minimum operate phase current for
Phase-Earth loops
IMinOpPP 5 - 30 %IB 1 10 Minimum operate phase-phase
current for Phase-Phase loops
ArgNegRes 90 - 175 Deg 1 130 Angle of blinder in second quadrant
for forward direction
ArgDir 5 - 45 Deg 1 15 Angle of blinder in fourth quadrant for
forward direction
INReleasePE 10 - 100 %IPh 1 20 3I0 limit for releasing phase-to-earth
measuring loops
INBlockPP 10 - 100 %IPh 1 40 3I0 limit for blocking phase-to-phase
measuring loops
OperationLdCh Off - - On Operation of load discrimination
On characteristic
RLdFw 1.00 - 3000.00 Ohm/p 0.01 80.00 Forward resistive reach within the
load impedance area
RLdRv 1.00 - 3000.00 Ohm/p 0.01 80.00 Reverse resistive reach within the load
impedance area
ArgLd 5 - 70 Deg 1 30 Load angle determining the load
impedance area
X1FwPP 0.50 - 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach,
Ph-Ph, forward
Table continues on next page

Line distance protection REL670 205


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Name Values (Range) Unit Step Default Description


R1PP 0.10 - 1000.00 Ohm/p 0.01 7.00 Positive seq. resistance for
characteristic angle, Ph-Ph
RFFwPP 0.50 - 3000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, forward
X1RvPP 0.50 - 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach,
Ph-Ph, reverse
RFRvPP 0.50 - 3000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, reverse
X1FwPE 0.50 - 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach,
Ph-E, forward
R1PE 0.10 - 1000.00 Ohm/p 0.01 7.00 Positive seq. resistance for
characteristic angle, Ph-E
X0FwPE 0.50 - 9000.00 Ohm/p 0.01 120.00 Zero sequence reactance reach, Ph-E,
forward
R0PE 0.50 - 3000.00 Ohm/p 0.01 20.00 Zero seq. resistance for zone
characteristic angle, Ph-E
RFFwPE 1.00 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-E, forward
X1RvPE 0.50 - 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach,
Ph-E, reverse
X0RvPE 0.50 - 9000.00 Ohm/p 0.01 120.00 Zero sequence reactance reach, Ph-E,
reverse
RFRvPE 1.00 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-E, reverse

Table 125: ZDSRDIR Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

8.3.6 Monitored data


PID-3547-MONITOREDDATA v6

Table 126: ZDSRDIR Monitored data


Name Type Values (Range) Unit Description
L1Dir INTEGER 1=Forward - Direction in phase L1
2=Reverse
0=No direction
L2Dir INTEGER 1=Forward - Direction in phase L2
2=Reverse
0=No direction
L3Dir INTEGER 1=Forward - Direction in phase L3
2=Reverse
0=No direction
L1R REAL - Ohm Resistance in phase L1
L1X REAL - Ohm Reactance in phase L1
L2R REAL - Ohm Resistance in phase L2
L2X REAL - Ohm Reactance in phase L2
L3R REAL - Ohm Resistance in phase L3
L3X REAL - Ohm Reactance in phase L3

206 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

8.3.7 Operation principle

8.3.7.1 Full scheme measurement SEMOD168177-4 v2

The execution of the different fault loops within the IED are of full scheme type, which means
that earth fault loop for phase-to-earth faults and phase-to-phase faults for forward and
reverse faults are executed in parallel.

Figure 83 presents an outline of the different measuring loops for the basic five, impedance-
measuring zones.

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 1

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 2

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 3

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 4

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 5

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1


Zone RV

IEC05000458-2-en.vsd
IEC05000458 V2 EN-US

Figure 83: The different measuring loops at phase-to-earth fault and phase-to-phase
fault
The use of full scheme technique gives faster operation time compared to switched schemes
which mostly uses a start element to select correct voltages and current depending on fault
type. Each distance protection zone performs like one independent distance protection IED
with six measuring elements.

8.3.7.2 Impedance characteristic SEMOD168177-11 v5

Distance measuring zone, quadrilateral characteristic for series compensated lines (ZMCPDIS)
include six impedance measuring loops; three intended for phase-to-earth faults, and three
intended for phase-to-phase as well as, three-phase faults.

The distance measuring zone operates according to the non-directional impedance


characteristics presented in figure 84 and figure 85. The phase-to-earth characteristic is
illustrated with the full loop reach while the phase-to-phase characteristic presents the per-
phase reach.

Line distance protection REL670 207


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

X (Ohm/loop)

R1PE+RNFw
X 0 PE - X 1FwPE
RFRvPE RFFwPE XNFw =
3
PG- -
XX00PE 1RVPG X 1RvPE
1XRVPE
XNRV XNRv
XNRV == =XXNFw ×
33 X 1FwPE
XX0 PE - X-1X
0 PG FWPE
1FWPG
XNFW==
XNFW
X1FwPE+XNFw 3 3 R0 PE - R1PE
RNFw =
jN jN 3
R (Ohm/loop)

RFRvPE RFFwPE

X1RvPE+XNRv

jN

RFRvPE RFFwPE
IEC09000625-1-en.vsd
IEC09000625 V1 EN-US

Figure 84: Characteristic for the phase-to-earth measuring loops, ohm/loop domain

X (Ohm/phase)

RFRvPP R1PP RFFwPP


2 2
X 0 PE - X 1RVPE
XNRV =XX00PE PG- -
X31XRVPE
1RVPG
XNRV ==
XNRV
33
XX
X00PE
0PE-
PG --1X
X 11FWPE
XFWPE
FWPG
XNFW===
XNFW
XNFW
3
X1FwPP 3 3

j j
jN R (Ohm/phase)

RFRvPP RFFwPP
2 2

X1RvPP

jN

RFRvPP RFFwPP
2 2
IEC09000632-1-en.vsd
IEC09000632 V1 EN-US

Figure 85: Characteristic for the phase-to-phase measuring loops

208 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

The fault loop reach with respect to each fault type may also be presented as in figure 86. Note
in particular the difference in definition regarding the (fault) resistive reach for phase-to-
phase faults and three-phase faults.

IL1 R1 + j X1
Phase-to-earth
UL1
element

Phase-to-earth
fault in phase L1 RFPE
(Arc + tower
resistance)

0
IN (R0-R1)/3 +
j (X0-X1)/3 )

IL1 R1 + j X1 Phase-to-phase
UL1 element L1-L2
Phase-to-phase
fault in phase RFPP
L1-L2 IL2
UL2 (Arc resistance)
R1 + j X1

IL1 R1 + j X1 0.5·RFPP Phase-to-phase


UL1 element L1-L3
Three-phase
fault
IL3
UL3
R1 + j X1 0.5·RFPP
IEC08000282-2-en.vsd
IEC08000282 V2 EN-US

Figure 86: Fault loop model


The R1 and jX1 in figure 86 represents the positive sequence impedance from the measuring
point to the fault location. The RFPE and RFPP is the eventual fault resistance in the fault place.

Regarding the illustration of three-phase fault in figure 86, there is of course fault current
flowing also in the third phase during a three-phase fault. The illustration merely reflects the
loop measurement, which is made phase-to-phase.

The zone may be set to operate in Non-directional, Forward or Reverse direction through the
setting OperationDir. The result from respective set value is illustrated in figure 87. It may be
convenient to once again mention that the impedance reach is symmetric, forward and reverse
direction. Therefore, all reach settings apply to both directions.

Line distance protection REL670 209


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

X X X

R R R

Non-directional Forward Reverse

IEC05000182-2-en.vsdx

IEC05000182 V2 EN-US

Figure 87: Directional operating modes of the distance measuring zone

8.3.7.3 Minimum operating current SEMOD168177-36 v2

The operation of Distance measuring zone, quadrilateral characteristic for series compensated
lines (ZMCPDIS,ZMCAPDIS) is blocked if the magnitude of input currents fall below certain
threshold values.

The phase-to-earth loop Ln is blocked if ILn < IMinOpPE.

For zone 1 with load compensation feature the additional criterion applies, that all phase-to-
earth loops will be blocked when IN < IMinOpIN, regardless of the phase currents.

ILn is the RMS value of the current in phase Ln. IN is the RMS value of the vector sum of the
three phase currents, that is, residual current 3I0.

The phase-to-phase loop LmLn is blocked if ILmLnAB (BC or CA)< IMinOpPP.

ILmLn is the RMS value of the vector difference between phase currents Lm and Ln.

All three current limits IMinOpPE, IMinOpIN and IMinOpPP are automatically
reduced to 75% of regular set values if the zone is set to operate in reverse
direction, that is, OperationDir=Reverse.

8.3.7.4 Measuring principles SEMOD168177-46 v3

Fault loop equations use the complex values of voltage, current, and changes in the current.
Apparent impedances are calculated and compared with the set limits. The calculation of the
apparent impedances at ph-ph faults follows equation 21 (example for a phase L1 to phase L2
fault).

UL1 – UL2
Zapp = -------------------------
I L1 – IL2
EQUATION1222 V1 EN-US (Equation 21)

210 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Here U and I represent the corresponding voltage and current phasors in the respective phase.

The earth return compensation applies in a conventional manner to ph-E faults (example for a
phase L1 to earth fault) according to equation 22.

U L1
Z app =
I L1 + I N × KN
EQUATION1223 V2 EN-US (Equation 22)

Where:
UL1, IL1 and IN are the phase voltage, phase current and residual current present to the IED
KN is defined as:

Z 0 - Z1
KN =
3 × Z1
EQUATION-2105 V2 EN-US

Z 0 = R 0 + jX 0
EQUATION2106 V2 EN-US

Z 1 = R1 + jX 1
EQUATION2107 V2 EN-US

Where
R0 is setting of the resistive zero sequence reach
X0 is setting of the reactive zero sequence reach
R1 is setting of the resistive positive sequence reach
X1 is setting of the reactive positive sequence reach

Here IN is a phasor of the residual current at the IED point. This results in the same reach along
the line for all types of faults.

The apparent impedance is considered as an impedance loop with resistance R and reactance
X.

The formula given in equation 22 is only valid for no loaded radial feeder applications. When
load is considered in the case of single phase-to-earth fault, conventional distance protection
might overreach at exporting end and underreach at importing end. IED has an adaptive load
compensation which increases the security in such applications.

Measuring elements receive current and voltage information from the A/D converter. The
check sums are calculated and compared, and the information is distributed into memory
locations. For each of the six supervised fault loops, sampled values of voltage (U), current (I),
and changes in current between samples (DI) are brought from the input memory and fed to a
recursive Fourier filter.

The filter provides two orthogonal values for each input. These values are related to the loop
impedance according to equation 23,

Line distance protection REL670 211


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

X Di
U = R × i + ------ × -----
w 0 Dt
EQUATION1224 V1 EN-US (Equation 23)

in complex notation, or:

X D Re ( I )
Re ( U ) = R × Re ( I ) + ------ × ------------------
w0 Dt

EQUATION354 V1 EN-US (Equation 24)

X DIm ( I )
Im ( U ) = R × Im ( I ) + ------ × -----------------
w0 Dt

EQUATION355 V1 EN-US (Equation 25)

with

w0 = 2 × p × f 0
EQUATION356 V1 EN-US (Equation 26)

where:
Re designates the real component of current and voltage,
Im designates the imaginary component of current and voltage and
f0 designates the rated system frequency

The algorithm calculates Rm measured resistance from the equation for the real value of the
voltage and substitute it in the equation for the imaginary part. The equation for the Xm
measured reactance can then be solved. The final result is equal to:

Im ( U ) × DRe ( I ) – Re ( U ) × D Im ( I )
R m = ------------------------------------------------------------------------------------
DRe ( I ) × Im ( I ) – D Im ( I ) × Re ( I )
EQUATION357 V1 EN-US (Equation 27)

Re ( U ) × Im ( I ) – Im ( U ) × Re ( I )
Xm = w 0 × Dt × -------------------------------------------------------------------------------
DRe ( I ) × Im ( I ) – DIm ( I ) × Re ( I )
EQUATION358 V1 EN-US (Equation 28)

The calculated Rm and Xm values are updated each sample and compared with the set zone
reach. The adaptive tripping counter counts the number of permissive tripping results. This
effectively removes any influence of errors introduced by the capacitive voltage transformers
or by other factors.

The directional evaluations are performed simultaneously in both forward and reverse
directions, and in all six fault loops. Positive sequence voltage and a phase locked positive
sequence memory voltage are used as a reference. This ensures unlimited directional
sensitivity for faults close to the IED point.

212 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

8.3.7.5 Directionality for series compensation SEMOD168177-97 v4

In the basic distance protection function, the control of the memory for polarizing voltage is
performed by an undervoltage control. In case of series compensated line, a voltage reversal
can occur with a relatively high voltage also when the memory must be locked. Thus, a simple
undervoltage type of voltage memory control can not be used in case of voltage reversal. In the
option for series compensated network the polarizing quantity and memory are controlled by
an impedance measurement criterion.

The polarizing voltage is a memorized positive sequence voltage. The memory is continuously
synchronized via a positive sequence filter. The memory is starting to run freely
instantaneously when a voltage change is detected in any phase. A non-directional impedance
measurement is used to detect a fault and identify the faulty phase or phases.

At a three phase fault when no positive sequence voltage remains (all three phases are
disconnected) the memory is used for direction polarization during 100 ms.

The memory predicts the phase of the positive sequence voltage with the pre-fault frequency.
This extrapolation is made with a high accuracy and it is not the accuracy of the memory that
limits the time the memory can be used. The network is at a three phase fault under way to a
new equilibrium and the post-fault condition can only be predicted accurately for a limited
time from the pre-fault condition.

In case of a three phase fault after 100 ms the phase of the memorized voltage can not be
relied upon and the directional measurement has to be blocked. The achieved direction criteria
are sealed-in when the directional measurement is blocked and kept until the impedance fault
criteria is reset (the direction is stored until the fault is cleared).

This memory control allows in the time domain unlimited correct directional measurement for
all unsymmetrical faults also at voltage reversal. Only at three phase fault within the range of
the set impedance reach of the criteria for control of the polarization voltage the memory has
to be used and the measurement is limited to 100 ms and thereafter the direction is sealed-in.
The special impedance measurement to control the polarization voltage is set separately and
has only to cover (with some margin) the impedance to fault that can cause the voltage
reversal.

The evaluation of the directionality takes place in Directional impedance quadrilateral,


including series compensation (ZDSRDIR) function. Equation 29 and equation 30 are used to
classify that the fault is in forward direction for phase-to-earth fault and phase-to-phase fault.

U 1L1M
- ArgDir < arg < ArgNeg Re s
I L1
EQUATION2004 V2 EN-US (Equation 29)

For the L1-L2 element, the equation in forward direction is according to:

Line distance protection REL670 213


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

U 1L1L 2 M
- ArgDir < arg < ArgNeg Re s
I L1L 2
EQUATION2006 V2 EN-US (Equation 30)

where:
ArgDir is the setting for the lower boundary of the forward directional characteristic, by default set to 15
(= -15 degrees) and
ArgNegRes is the setting for the upper boundary of the forward directional characteristic, by default set to
115 degrees, see Figure 88.
U1L1M is positive sequence memorized phase voltage in phase L1

IL1 is phase current in phase L1

U1L1L2M is memorized voltage difference between phase L1 and L2 (L2 lagging L1)

IL1L2 is current difference between phase L1 and L2 (L2 lagging L1)

The setting of ArgDir and ArgNegRes is by default set to 15 (= -15) and 115 degrees
respectively, see Figure 88, and it should not be changed unless system studies have shown
the necessity.

ZDSRDIR generates a binary coded signal on the output STDIR depending on the evaluation
where STFWL1N=1 adds 1, STRVL1N=1 adds 2, STFWL2N=1 adds 4.

ArgNegRes

ArgDir
R

en05000722.vsd
IEC05000722 V1 EN-US

Figure 88: Setting angles for discrimination of forward and reverse fault
The reverse directional characteristic is equal to the forward characteristic rotated by 180
degrees.

8.3.7.6 Simplified logic diagrams SEMOD168192-4 v2

214 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Distance protection zones SEMOD168192-6 v5


The design of distance protection zones are presented for all measuring loops: phase-to-earth
as well as phase-to-phase.

Phase-to-earth related signals are designated by Ln, where n represents the corresponding
phase number (L1, L2, and L3). The phase-to-phase signals are designated by LnLm, where n
and m represent the corresponding phase numbers (L1L2, L2L3, and L3L1).

Fulfillment of two different measuring conditions is necessary to obtain the one logical signal
for each separate measuring loop:

• Zone measuring condition, which follows the operating equations described above.
• Group functional input signal (STCND), as presented in figure 89.

Two types of function block, ZMCPDIS and ZMCAPDIS, are used in the IED. ZMCPDIS is used for
zone 1 and ZMCAPDIS for zone 2 - 5.

The STCND input signal represents a connection of six different integer values from the phase
selection function within the IED, which are converted within the zone measuring function into
corresponding boolean expressions for each condition separately. It is connected to Phase
selection with load enchroachment, quadrilateral characteristic (FDPSPDIS) function output
STCNDZ.

STZMPP
OR
STCND

AND STNDL1L2
L1L2

STNDL2L3
L2L3 AND

L3L1 AND STNDL3L1

AND STNDL1N
L1N

AND STNDL2N
L2N

STNDL3N
L3N AND

OR STPE

OR
VTSZ STND
OR AND
BLOCK
BLOCFUNC BLK

99000557-2.vsd
IEC99000557-TIFF V3 EN-US

Figure 89: Conditioning by a group functional input signal STCND


Composition of the phase starting signals for a case, when the zone operates in a non-
directional mode, is presented in figure 90.

Line distance protection REL670 215


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

IEC00000488-TIFF V1 EN-US

Figure 90: Composition of starting signals in non-directional operating mode


Results of the directional measurement enter the logic circuits, when the zone operates in
directional (forward or reverse) mode, as shown in figure 91.

STNDL1N
AND
DIRL1N
STZMPE.
OR
STNDL2N
DIRL2N AND

STNDL3N 15 ms
OR STL1
AND AND t
DIRL3N

STNDL1L2
DIRL1L2 AND 15 ms
OR STL2
AND t
STNDL2L3
DIRL2L3 AND
15 ms
OR STL3
STNDL3L1 AND t
DIRL3L1 AND

STZMPP
OR

BLK

15 ms
OR START
AND t

IEC09000888-2-en.vsd
IEC09000888 V2 EN-US

Figure 91: Composition of starting signals in directional operating mode


Tripping conditions for the distance protection zone one are symbolically presented in figure
92.

216 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Timer tPP=On
STZMPP AND tPP
AND
t

BLOCFUNC
OR OR
tPE
t
AND
Timer tPE=On AND
STZMPE 15ms
BLKTR AND t
TRIP
BLK OR

STL1 AND TRL1

STL2 AND TRL2

STL3 AND TRL3

IEC09000887-3-en.vsdx

IEC09000887 V3 EN-US

Figure 92: Tripping logic for the distance protection zone one

8.3.8 Technical data SEMOD173234-1 v1

SEMOD173239-2 v10

Table 127: ZMCPDIS, ZMCAPDIS Technical data


Function Range or value Accuracy
Number of zones Max 5 with selectable -
direction
Minimum operate residual (5-1000)% of IBase -
current, zone 1
Minimum operate current, Ph- (10-1000)% of IBase -
Ph and Ph-E
Positive sequence reactance (0.10-3000.00) Ω/phase ±2.0% static accuracy
±2.0 degrees static angular accuracy
Positive sequence resistance (0.10-1000.00) Ω/phase Conditions:
Zero sequence reactance (0.01-9000.00) Ω/phase Voltage range: (0.1-1.1) x Ur
Current range: (0.5-30) x Ir
Zero sequence resistance (0.01-3000.00) Ω/phase Angle: at 0 degrees and 85 degrees
Fault resistance, Ph-E (0.10-9000.00) Ω/loop
Fault resistance, Ph-Ph (0.10-3000.00) Ω/loop
Dynamic overreach <5% at 85 degrees measured -
with CCVT’s and 0.5<SIR<30
Definite time delay Ph-Ph and (0.000-60.000) s ±0.2% or ± 35 ms whichever is greater
Ph-E operation
Operate time 25 ms typically IEC 60255-121
Reset ratio 105% typically -
Reset time at 0.1 x Zreach to 2 Min. = 20 ms -
x Zreach Max. = 50 ms

Line distance protection REL670 217


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

8.4 Full-scheme distance measuring, Mho characteristic


ZMHPDIS SEMOD154227-1 v4

8.4.1 Identification
SEMOD154447-2 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE


identification identification C37.2 device
number
Full-scheme distance protection, ZMHPDIS 21
mho characteristic

Z
S00346 V2 EN-US

8.4.2 Functionality SEMOD175459-4 v12

The numerical mho line distance protection is an up to five (depending on product variant)
zone full scheme protection of short circuit and earth faults.

The zones have fully independent measuring and settings, which gives high flexibility for all
types of lines. Each zone is an individual function block available for independent configuration
in ACT.

The IED can be used up to the highest voltage levels. It is suitable for the protection of heavily
loaded lines and multi-terminal lines where the requirement for tripping is one-, two- and/or
three-pole.

The independent measurement of impedance for each fault loop together with a sensitive and
reliable phase selection makes the function suitable in applications with single phase
autoreclosing.

Built-in selectable zone timer logic is also provided in the function.

Adaptive load compensation algorithm prevents overreaching at phase-to-earth faults on


heavily loaded power lines, see Figure 93.

Load compensation algorithm prevents overreaching at phase-to-earth faults on heavily


loaded power lines, see Figure 93. This Load encroachment characteristic is taken from the
FMPSPDIS function.

218 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

jX

Operation area Operation area

Operation area

No operation area No operation area

IEC07000117-2-en.vsd
IEC07000117 V2 EN-US

Figure 93: Load encroachment influence on the offset mho characteristic


The distance protection zones can operate, independent of each other, in directional (forward
or reverse) or non-directional mode (offset). This makes them suitable, together with different
communication schemes, for the protection of power lines and cables in complex network
configurations, such as parallel lines, multi-terminal lines and so on.

The integrated control and monitoring functions offer effective solutions for operating and
monitoring all types of transmission and sub-transmission lines.

8.4.3 Function block SEMOD154705-4 v4

ZMHPDIS
I3P* TRIP
U3P* TRL1
CURR_INP* TRL2
VOLT_INP* TRL3
POL_VOLT* TRPE
BLOCK TRPP
BLKZ START
BLKZMTD STL1
BLKHSIR STL2
BLKTRIP STL3
BLKPE STPE
BLKPP STPP
EXTNST STTIMER
INTRNST
DIRCND
STCND*
LDCND

IEC06000423-2-en.vsd
IEC06000423 V3 EN-US

Figure 94: ZMHPDIS function block

8.4.4 Signals SEMOD154579-1 v2

PID-3552-INPUTSIGNALS v7

Table 128: ZMHPDIS Input signals


Name Type Default Description
I3P GROUP - Connection for current sample signals
SIGNAL
U3P GROUP - Connection for voltage sample signals
SIGNAL
CURR_INP GROUP - Connection for current signals
SIGNAL
Table continues on next page

Line distance protection REL670 219


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Name Type Default Description


VOLT_INP GROUP - Connection for voltage signals
SIGNAL
POL_VOLT GROUP - Connection for polarizing voltage
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKZ BOOLEAN 0 Block due to fuse failure
BLKZMTD BOOLEAN 0 Block signal for blocking of time domaine function
BLKHSIR BOOLEAN 0 Blocks time domain function at high SIR
BLKTRIP BOOLEAN 0 Blocks all operate output signals
BLKPE BOOLEAN 0 Blocks phase-to-earth operation
BLKPP BOOLEAN 0 Blocks phase-to-phase operation
EXTNST BOOLEAN 0 External start
INTRNST BOOLEAN 0 Internal start
DIRCND INTEGER 0 External directional condition
STCND INTEGER 0 External start condition (loop enabler)
LDCND INTEGER 0 External load condition (loop enabler)

PID-3552-OUTPUTSIGNALS v7

Table 129: ZMHPDIS Output signals


Name Type Description
TRIP BOOLEAN Trip General
TRL1 BOOLEAN Trip phase L1
TRL2 BOOLEAN Trip phase L2
TRL3 BOOLEAN Trip phase L3
TRPE BOOLEAN Trip phase-to-earth
TRPP BOOLEAN Trip phase-to-phase
START BOOLEAN Start General
STL1 BOOLEAN Start phase L1
STL2 BOOLEAN Start phase L2
STL3 BOOLEAN Start phase L3
STPE BOOLEAN Start phase-to-earth
STPP BOOLEAN Start phase-to-phase
STTIMER BOOLEAN Start timer

8.4.5 Settings SEMOD154644-1 v2

220 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

PID-3552-SETTINGS v7

Table 130: ZMHPDIS Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
DirMode Off - - Forward Direction mode
Offset
Forward
Reverse
LoadEncMode Off - - Off Load encroachment mode Off/On
On
ReachMode Overreach - - Overreach Reach mode Over/Underreach
Underreach
ZnTimerSel Timers seperated - - Timers Zone timer selection
Timers linked seperated
Internal start
Start from PhSel
External start
OpModePE Off - - On Operation mode Off / On of Phase-
On Earth loops
ZPE 0.005 - 3000.000 Ohm/p 0.001 30.000 Positive sequence impedance setting
for Phase-Earth loop
ZAngPE 10 - 90 Deg 1 85 Angle for positive sequence line
impedance for Phase-Earth loop
KN 0.00 - 3.00 - 0.01 0.80 Magnitude of earth return
compensation factor KN
KNAng -180 - 180 Deg 1 -15 Angle for earth return compensation
factor KN
ZRevPE 0.005 - 3000.000 Ohm/p 0.001 30.000 Reverse reach of the phase to earth
loop(magnitude)
tPE 0.000 - 60.000 s 0.001 0.000 Delay time for operation of phase to
earth elements
IMinOpPE 10 - 30 %IB 1 20 Minimum operation phase to earth
current
OpModePP Off - - On Operation mode Off / On of Phase-
On Phase loops
ZPP 0.005 - 3000.000 Ohm/p 0.001 30.000 Impedance setting reach for phase to
phase elements
ZAngPP 10 - 90 Deg 1 85 Angle for positive sequence line
impedance for Phase-Phase elements
ZRevPP 0.005 - 3000.000 Ohm/p 0.001 30.000 Reverse reach of the phase to phase
loop(magnitude)
tPP 0.000 - 60.000 s 0.001 0.000 Delay time for operation of phase to
phase
IMinOpPP 10 - 30 %IB 1 20 Minimum operation phase to phase
current

Line distance protection REL670 221


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Table 131: ZMHPDIS Group settings (advanced)


Name Values (Range) Unit Step Default Description
OffsetMhoDir Non-directional - - Non-directional Direction mode for offset mho
Forward
Reverse
OpModetPE Off - - On Operation mode Off / On of Zone
On timer, Ph-E
OpModetPP Off - - On Operation mode Off / On of Zone
On timer, Ph-ph

Table 132: ZMHPDIS Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

8.4.6 Operation principle SEMOD154230-1 v2

8.4.6.1 Full scheme measurement SEMOD154224-4 v3

The execution of the different fault loops within the IED are of full scheme type, which means
that each fault loop for phase-to-earth faults and phase-to-phase faults are executed in
parallel for all zones.

The use of full scheme technique gives faster operation time compared to switched schemes
which mostly uses a start element to select correct voltages and current depending on fault
type. So each distance protection zone performs like one independent distance protection
function with six measuring elements.

8.4.6.2 Impedance characteristic SEMOD154224-11 v7

The Mho distance function ZMHPDIS is present with five instances so that five separate zones
could be designed. Each instance can be selected to be either forward or reverse with positive
sequence polarized mho characteristic; alternatively self polarized offset mho characteristics
is also available. One example of the operating characteristic is shown in Figure 95 A) where
zone 5 is selected offset mho.

The directional mho characteristic of Figure 95 B) has a dynamic expansion due to the source
impedance. Instead of mho characteristic crossing origin, which is only valid where the source
impedance is zero, the crossing point is moved to the coordinates of the negative source
impedance giving an expansion of the circle of Figure 95 B).

222 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

A B
jx X

Mho, zone4

Mho, zone3 Zs=0

Mho, zone2 R

Mho, zone1

Zs=Z1

Zs=2Z1

R
Offset mho, zone5

IEC09000143-3-en.vsd

IEC09000143 V3 EN-US

Figure 95: Mho, offset mho characteristic and the source impedance influence on the mho
characteristic
The polarization quantities used for the mho circle are 100% memorized positive sequence
voltages. This will give a somewhat less dynamic expansion of the mho circle during faults
than a plain cross polarized characteristic. However, if the source impedance is high, the
dynamic expansion of the mho circle might lower the security of the function too much with
high loading and mild power swing conditions.

The mho distance element has a load encroachment function which cuts off a section of the
characteristic when enabled. The function is enabled by setting the setting parameter
LoadEnchMode to On. Enabling of the load encroachment function increases the possibility to
detect high resistive faults without interfering with the load impedance. The algorithm for the
load encroachment is located in the Faulty phase identification with load encroachment for
mho function FMPSPDIS, where also the relevant settings can be found. Information about the
load encroachment from FMPSPDIS to the zone measurement is given in binary format to the
input signal LDCND.

8.4.6.3 Basic operation characteristics SEMOD154224-21 v9

Each impedance zone can be switched On and Off by the setting parameter Operation.

Each zone can be set to Non-directional, Forward or Reverse by setting the parameter
DirMode .

The mho characteristics can be classified into - Offset or Directional. The directional mho
characteristics can be set to Offset, Forward or Reverse by the setting parameter DirMode.
The offset mho characteristic can be set to Forward or Reverse or Non-Directional by the
setting parameter OffsetMhoDir.

The operation for phase-to-earth and phase-to-phase fault can be individually switched On
and Off by the setting parameter OpModePE and OpModePP.

Line distance protection REL670 223


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

For critical applications such as for lines with high SIRs as well as CVTs, it is possible to
improve the security by setting the parameter ReachMode to Underreach. In this mode the
reach for faults close to the zone reach is reduced by 20% and the filtering is also introduced
to increase the accuracy in the measuring. If the ReachMode is set to Overreach no reduction
of the reach is introduced and no extra filtering introduced. The latter setting is recommended
for overreaching pilot zone, zone 2 or zone 3 elements and reverse zone where overreaching on
transients is not a major issue either because of less likelihood of overreach with higher
settings or the fact that these elements do not initiate tripping unconditionally.

The offset Mho characteristic can be set in Non-directional, Forward or Reverse by the setting
parameter OffsetMhoDir. When Forward or Reverse is selected a directional line is introduced.
Information about the directional line is given from the directional element and given to the
measuring element as binary coded signal to the input DIRCND.

When DirMode is set to offset and offsetMhoDir is set as Non-Directional, ZDMRDIR does not
have any effect on the measurement loop and operation of the function. When DirMode is
selected as Forward or Reverse, a directional line is introduced. Information about the
directional line is given from the directional element (ZDMRDIR) and given to the measuring
element as binary coded signal to the input DIRCND.

The zone reach for phase-to-earth fault and phase-to-phase fault is set individually in polar
coordinates.

The impedance is set by the parameters ZPE and ZPP and the corresponding arguments by the
parameters ZAngPE and ZAngPP.

Compensation for earth -return path for faults involving earth is done by setting the
parameter KN and KNAng where KN is the magnitude of the earth -return path and KNAng is
the argument of the earth-return path.

Z 0 - Z1
KN =
3 × Z1
IECEQUATION14023 V1 EN-US (Equation 31)

KNAng = arg
( Z 0 - Z1

3 × Z1
)
EQUATION1580 V1 EN-US (Equation 32)

where
Z0 is the complex zero sequence impedance of the line in Ω/phase
Z1 is the complex positive sequence impedance of the line in Ω/phase

The phase-to-earth and phase-to-phase measuring loops can be time delayed individually by
setting the parameter tPE and tPP respectively. To release the time delay, the operation mode
for the timers, OpModetPE and OpModetPP, has to be set to On. This is also the case for
instantaneous operation. In instantaneous case, the timers tPE and tPP need to be set as zero.

The operate timers triggering input depends on the parameter ZnTimerSel setting. The
parameter ZnTimerSel can be set to:

224 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

• Timers separated: Phase-to-earth and phase-to-phase timers are triggered by the


respective measuring loop start signals.
• Timers linked: Start of any of the phase-to-earth or phase-to-phase loops will trigger both
the phase-to-earth or phase-to-phase timers.
• Internal start: Phase-to-earth and phase-to-phase timers are triggered by the INTRNST
input.
• Start from PhSel: The phase-to-earth and phase-to-phase timers are triggered by the
STCND and LDCND inputs. Each of the two inputs consist binary status information related
to the six measuring loops. Hence if any of the measuring loop status is high in both two
inputs STCND and LDCND, then the timers will be triggered. In case when LoadEnchMode is
off then only STCND enables the timer.

It is not recommended to use this timer setting for the Zone instance
where LoadEnchMode is off.

• External start: Phase-to-earth and phase-to-phase timers are triggered by the EXTNST
input.

The function can be blocked in the following ways:

• activating of input BLOCK blocks the whole function


• activating of the input BLKZ (fuse failure) blocks all output signals
• activating of the input BLKZMTD blocks the delta based time domain algorithm
• activating of the input BLKHSIR blocks the instantaneous part of the algorithm for high
SIR values
• activating of the input BLKTRIP blocks all output signals
• activating the input BLKPE blocks the phase-to-earth fault loop outputs
• activating the input BLKPP blocks the phase-to-phase fault loop outputs

The activation of input signal BLKZ can be made by external fuse failure function or from the
loss of voltage check in the Mho supervision logic (ZSMGAPC). In both cases the output BLKZ
in the Mho supervision logic shall be connected to the input BLKZ in the Mho distance function
block (ZMHPDIS)

The input signal BLKZMTD is activated during some ms after fault has been detected by
ZSMGAPC to avoid unwanted operations due to transients. It shall be connected to the
BLKZMTD output signal of ZSMGAPC function.

At SIR values >10, the use of electronic CVT might cause overreach due to the built-in
resonance circuit in the CVT, which reduce the secondary voltage for a while. The input
BLKHSIR is connected to the output signal HSIR on ZSMGAPC for increasing of the filtering
and high SIR values. This is valid only when permissive underreach scheme is selected by
setting ReachMode=Underreach.

8.4.6.4 Theory of operation SEMOD154224-46 v6

The mho algorithm is based on the phase comparison of an operating phasor and a polarizing
phasor. When the operating phasor leads the reference polarizing phasor by 90 degrees or
more, the function operates and gives a trip output.

Phase-to-phase fault SEMOD154224-240 v2

Mho SEMOD154224-217 v5
The plain Mho circle has the characteristic as in Figure 96. The condition for deriving the angle
β is according to equation 33.

Line distance protection REL670 225


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

EQUATION1789 V2 EN-US (Equation 33)

where

U L1L2 is the voltage vector difference between phases L1 and L2


EQUATION1790 V2
EN-US

I L1L2 is the current vector difference between phases L1 and L2


EQUATION1791
EN-US V2

ZPP is the positive sequence impedance setting for phase-to-phase fault


Upol is the polarizing voltage

The polarized voltage consists of 100% memorized positive sequence voltage (UL1L2 for phase
L1 to L2 fault). The memorized voltage will prevent collapse of the Mho circle for close in faults.

Operation occurs if 90≤β≤270

IL1L2·X
Ucomp = UL1L2 - IL1L2 • ZPP

IL1L2 • ZPP
ß
Upol
UL1L2

IL1L2·R

en07000109.vsd
IEC07000109 V1 EN-US

Figure 96: Simplified mho characteristic and vector diagram for phase L1-to-L2 fault

Offset Mho SEMOD154224-242 v4


The characteristic for offset mho is a circle where two points on the circle are the setting
parameters ZPP and ZRevPP. The vector ZPP in the impedance plane has the settable angle
AngZPP and the angle for ZRevPP is AngZPP+180°.

The condition for operation at phase-to-phase fault is that the angle β between the two
compensated voltages Ucomp1 and Ucomp2 is greater than or equal to 90° (figure 97). The
angle will be 90° for fault location on the boundary of the circle.

The angle β for L1-to-L2 fault can be defined according to equation 34.

226 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

æ U -IL1L2 × ZPPö
b = arg ç ÷
è U-(-IL1L2 × ZRevPP) ø
EQUATION1792 V1 EN-US (Equation 34)

where

U is the UL1L2 voltage


EQUATION1800 V1 EN-US

ZRevPP is the positive sequence impedance setting for phase-to-phase fault in reverse direction

IL1L2jX

Ucomp1 = UL1L2 - IL1L2 • ZPP


IL1L2 • ZPP

U
Ucomp2 = U = IF•ZF=UL1L2
IL1L2R

- IL1L2 • Z RevPP
en07000110.vsd
IEC07000110 V1 EN-US

Figure 97: Simplified offset mho characteristic and voltage vectors for phase L1-to-L2
fault.
Operation occurs if 90≤β≤270.

Offset mho, forward direction SEMOD154224-249 v4


When forward direction has been selected for the offset mho, an extra criteria beside the one
for offset mho (90<β<270) is introduced, that is the angle φ between the voltage and the
current must lie between the blinders in second quadrant and fourth quadrant. See figure 98.
Operation occurs if 90≤β≤270 and ArgDir≤φ≤ArgNegRes.

where
ArgDir is the setting parameter for directional line in fourth quadrant in the directional
element, ZDMRDIR.
ArgNegRes is the setting parameter for directional line in second quadrant in the directional
element, ZDMRDIR.
β is calculated according to equation

The directional information is brought to the mho distance measurement from the mho
directional element as binary coded information to the input DIRCND. See Directional

Line distance protection REL670 227


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

impedance element for mho characteristic (ZDMRDIR) for information about the mho
directional element.

IL1L2jX

ZPP

UL1L2

ArgNegRes f

IL1L2
ArgDir

en07000111.vsd
IEC07000111 V1 EN-US

Figure 98: Simplified offset mho characteristic in forward direction for phase L1-to-L2
fault

Offset mho, reverse direction SEMOD154224-265 v4


The operation area for offset mho in reverse direction is according to figure 99. The operation
area in second quadrant is ArgNegRes+180°.

Operation occurs if 90≤β≤270 and 180° - ArgDir ≤φ ≤ ArgNegRes + 180°

The β is derived according to equation for the mho circle and φ is the angle between the
voltage and current.

228 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

ZPP

ArgNegRes
ϕ

IL1L2

ArgDir R

UL1L2

ZRevPP

en06000469.eps
IEC06000469 V1 EN-US

Figure 99: Operation characteristic for reverse phase L1-to-L2 fault

Phase-to-earth fault SEMOD154224-283 v2

Mho SEMOD154224-120 v5
The measuring of earth faults uses earth-return compensation applied in a conventional way.
The compensation voltage is derived by considering the influence from the earth-return path.

For an earth fault in phase L1, the compensation voltage Ucomp can be derived, as shown in
Figure 100.

Ucomp = U pol - I L1 × Z loop


EQUATION1793 V1 EN-US (Equation 35)

where
Upol is the polarizing voltage (memorized UL1 for Phase L1-to- earth
fault)
Zloop is the loop impedance, which in general terms can be expressed
as

(
Z1+ZN = Z 1 × 1 + KN )
where
Z1 is the positive sequence impedance of the line (Ohm/phase)

KN is the zero-sequence compensator factor

The angle β between the Ucomp and the polarize voltage Upol for a L1-to-earth fault is

Line distance protection REL670 229


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

(
β = arg U L1 − I L1 + 3I 0 ⋅ KN ⋅ ZPE  − arg (Upol )
  )
GUID-A9492CDF-D3B7-4DC5-8E06-6638BEE2540B V2 EN-US (Equation 36)

where
UL1 is the phase voltage in faulty phase L1

IL1 is the phase current in faulty phase L1

3I0 is the zero-sequence current in faulty phase L1

KN Z0-Z1
3 × Z1
the setting parameter for the zero sequence
compensation consisting of the magnitude KN and the
angle KNAng.
Upol is the 100% of positive sequence memorized voltage UL1

IL1·X

IL1·ZN
Ucomp

IL1 • Zloop
IL1·ZPE
Upol

f
IL1 (Ref) IL1·R

en06000472_2.vsd
IEC06000472 V2 EN-US

Figure 100: Simplified offset mho characteristic and vector diagram for phase L1-to-earth
fault
Operation occurs if 90≤β≤270.

Offset mho SEMOD154224-309 v5


The characteristic for offset mho at earth fault is a circle containing the two vectors from the
origin ZPE and ZRevPE where ZPE and ZrevPE are the setting reach for the positive sequence
impedance in forward respective reverse direction. The vector ZPE in the impedance plane has
the settable angle AngZPE and the angle for ZRevPP is AngZPE+180°.

The condition for operation at phase-to-earth fault is that the angle β between the two
compensated voltages Ucomp1 and Ucomp2 is greater or equal to 90° see figure 101. The
angle will be 90° for fault location on the boundary of the circle.

The angle β for L1-to-earth fault can be defined as

230 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

æ UL1- IL1L × ZPE ö


b = arg ç ÷
è UL1-(- IL1 × Z Re vPE ) ø
EQUATION1802 V1 EN-US (Equation 37)

is the phase L1 voltage


U L1
805 V1 EN-
EQUATION1
US

IL1L 2 • jX

U comp1 = UL1 - I L1• ZPE


IL1 • ZPE

UL1
U comp2 = UL1 - (-IL1 • ZRevPE)
IL1L2 • R

- I L1 • Z Re vPe

en 06000465.vsd
IEC06000465 V1 EN-US

Figure 101: Simplified offset mho characteristic and voltage vector for phase L1-to-earth
fault
Operation occurs if 90≤β≤270.

Offset mho, forward direction SEMOD154224-327 v3


In the same way as for phase-to-phase fault, selection of forward direction of offset mho will
introduce an extra criterion for operation. Beside the basic criteria for offset mho according to
equation and 90≤β≤270, also the criteria that the angle φ between the voltage and the current
must lie between the blinders in second and fourth quadrant. See figure 102. Operation occurs
if 90≤β≤270 and ArgDir≤φ≤ArgNegRes.

where
ArgDir is the setting parameter for directional line in fourth quadrant in the directional
element, ZDMRDIR.
ArgNegRes is the setting parameter for directional line in second quadrant in the directional
element, ZDMRDIR.
β is calculated according to equation

Line distance protection REL670 231


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

IL1 jX

UL1

ArgNegRes f

IL1 IL1·R

ArgDir

en 06000466.vsd
IEC06000466 V1 EN-US

Figure 102: Simplified characteristic for offset mho in forward direction for L1-to-earth
fault

Offset mho, reverse direction SEMOD154224-341 v4


In the same way as for offset in forward direction, the selection of offset mho in reverse
direction will introduce an extra criterion for operation compare to the normal offset mho. The
extra is that the angle between the fault voltage and the fault current shall lie between the
blinders in second and fourth quadrant. The operation area in second quadrant is limited by
the blinder defined as 180° -ArgDir and in fourth quadrant ArgNegRes+180°, see figure 103.

The conditions for operation of offset mho in reverse direction for L1-to-earth fault is
90≤β≤270 and 180°-Argdir≤φ≤ArgNegRes+180°.

The β is derived according to equation for the offset mho circle and φ is the angle between the
voltage and current.

232 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

ZPE

ArgNegRes
ϕ

IL
1
ArgDir R

UL1
ZRevPE

en06000470.eps
IEC06000470 V1 EN-US

Figure 103: Simplified characteristic for offset mho in reverse direction for L1-to-earth
fault

8.4.6.5 Simplified logic diagrams GUID-22B4A410-6F8E-4569-A354-51A1F4951F79 v3

Distance protection zones


The design of the distance protection zones are presented for all measuring loops: phase-to-
earth as well as phase-to-phase.

Phase-to-earth related signals are designated by L1N, L2N and L3N. The phase-to-phase
signals are designated by L1L2, L2L3, and L3L1.

Fulfillment of two different measuring conditions is necessary to obtain the one logical signal
for each separate measuring loop:

• Zone measuring condition, which follows the operating equations described above.
• Group functional input signal (STCND), as presented in figure 104.

The ZMHPDIS function block is used in the IED for each zone.

The STCND input signal represents a connection of six different integer values from Phase
selection with load encroachment function FMPSPDIS within the IED, which are converted
within the zone measuring function into corresponding boolean expressions for each
condition separately. Input signal STCND is connected from FMPSPDIS function output signal
STCNDPHS.

The input signal DIRCND is used to give condition for directionality for the distance measuring
zones. The signal contains binary coded information for both forward and reverse direction.
The zone measurement function filters out the relevant signals depending on the setting of

Line distance protection REL670 233


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

the parameter DirMode. Input signal DIRCND must be configured to the STDIRCND output
signal on ZDMRDIR function.

OffsetMhoDir=
Non-directional
AND AND
DirMode=Offset

STCND T
AND F

AND
LoadEnchMode=
On/Off
LDCND
T
True F
AND Release

DIRCND

OffsetMhoDir=
Forward/Reverse
AND
DirMode=
Forward/Reverse

BLKZ
BLOCK OR

IEC11000216-1-en.vsd
IEC11000216 V1 EN-US

Figure 104: Simplified logic for release start signal


When load encroachment mode is switched on (LoadEnchMode=On), start signal STCND is
also checked against LDCND signal.

Results of the directional measurement enter the logic circuits when the zone operates in
directional (forward or reverse) mode, as shown in figure 104.

Composition of the phase start signals is presented in figure 105.

234 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Release STPE
OR

AND
STL1N STL1
OR

AND
STL2N

AND
STL3N
STL2
OR
AND
STL1L2

AND
STL2L3
STL3
OR
AND
STL3L1

START
OR

STPP
OR

IEC11000217-1-en.vsd
IEC11000217 V1 EN-US

Figure 105: Composition of starting signals


Tripping conditions for the distance protection zone one are symbolically presented in figure
106.

Timer tPP=On tPP


AND t
STPP
OR
Timer tPE=On tPE
AND t
STPE

15ms
BLKTRIP AND t
TRIP

STL1 AND TRL1

AND TRL2
STL2

STL3 AND TRL3

IEC11000218-1-en.vsd
IEC11000218 V1 EN-US

Figure 106: Tripping logic for the distance protection zone


Zone timer logic for the distance protection is symbolically presented in figure 107.

Line distance protection REL670 235


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

STPE

BLOCK
TRPE
&
tON
& ³1 t
a
Internal a=b
start b STTIMER
&

Internal
a
a<b
start b
tON
³1 t && TRPP
&

STPP
ZnTimerSel
FALSE 1 timers seperated

³1 2 timers linked
internalCommonStart
3 internal start
phSelStart 4 start from phSel
externalCommonStart
5 external start

IEC12000463-3-en.vsd
IEC12000463 V2 EN-US

Figure 107: Zone timer logic

8.4.7 Technical data SEMOD173244-1 v1

SEMOD173242-2 v14

Table 133: ZMHPDIS technical data


Function Range or value Accuracy
Number of zones, Ph-E Max 5 with selectable -
direction
Minimum operate current (10–30)% of IBase -
Positive sequence impedance, (0.005–3000.000) W/phase ±2.0% static accuracy
Ph-E loop Conditions:
Voltage range: (0.1-1.1) x Ur
Positive sequence impedance (10–90) degrees
Current range: (0.5-30) x Ir
angle, Ph-E loop
Angle: 85 degrees
Reverse reach, Ph-E loop (0.005–3000.000) Ω/phase
(Magnitude)
Magnitude of earth return (0.00–3.00)
compensation factor KN
Angle for earth compensation (-180–180) degrees
factor KN
Dynamic overreach <5% at 85 degrees -
measured with CVT’s and
0.5<SIR<30
Definite time delay Ph-Ph and (0.000-60.000) s ±0.2% or ±60 ms whichever is greater
Ph-E operation
Operate time 22 ms typically IEC 60255-121
Reset ratio 105% typically -
Reset time at 0.5 x Zreach to Min. = 30 ms -
1.5 x Zreach Max. = 50 ms

236 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

8.5 Full-scheme distance protection, quadrilateral for


earth faults ZMMPDIS, ZMMAPDIS SEMOD154561-1 v2

8.5.1 Identification
SEMOD154542-2 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Fullscheme distance protection, ZMMPDIS 21
quadrilateral for earth faults (zone 1)
Z
S00346 V2 EN-US

Fullscheme distance protection, ZMMAPDIS 21


quadrilateral for earth faults (zone
2-5) Z
S00346 V2 EN-US

8.5.2 Functionality SEMOD154544-4 v7

The line distance protection is an up to five (depending on product variant) zone full scheme
protection function with three fault loops for phase-to-earth fault for each of the independent
zones. Individual settings for each zone resistive and reactive reach give flexibility for use on
overhead lines and cables of different types and lengths.

The Full-scheme distance protection, quadrilateral for earth fault functions have functionality
for load encroachment, which increases the possibility to detect high resistive faults on heavily
loaded lines , see Figure 108.

Forward
operation

Reverse
operation

en05000034.vsd
IEC05000034 V1 EN-US

Figure 108: Typical quadrilateral distance protection zone with Phase selection,
quadrilateral characteristic with settable angle function FRPSPDIS activated
The independent measurement of impedance for each fault loop together with a sensitive and
reliable built in phase selection makes the function suitable in applications with single phase
auto-reclosing.

Built-in adaptive load compensation algorithm prevents overreaching of zone1 at load


exporting end at phase to earth faults on heavily loaded power lines.

Line distance protection REL670 237


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

The distance protection zones can operate, independent of each other, in directional (forward
or reverse) or non-directional mode. This makes them suitable, together with different
communication schemes, for the protection of power lines and cables in complex network
configurations, such as parallel lines, multi-terminal lines.

8.5.3 Function block SEMOD155557-4 v2

ZMMPDIS
I3P* TRIP
U3P* TRL1
BLOCK TRL2
BLKZ TRL3
BLKTR START
STCND STL1
DIRCND STL2
STL3
STND

IEC06000454-2-en.vsd
IEC06000454 V2 EN-US

Figure 109: ZMMPDIS function block

ZMMAPDIS
I3P* TRIP
U3P* TRL1
BLOCK TRL2
BLKZ TRL3
BLKTR START
STCND STL1
DIRCND STL2
STL3
STND

IEC09000947-1-en.vsd
IEC09000947 V1 EN-US

Figure 110: ZMMAPDIS function block

8.5.4 Signals
PID-3645-INPUTSIGNALS v6

Table 134: ZMMPDIS Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKZ BOOLEAN 0 Blocks all output by fuse failure signal
BLKTR BOOLEAN 0 Blocks all trip outputs
STCND INTEGER 0 External start condition (loop enabler)
DIRCND INTEGER 0 External directional condition

PID-3645-OUTPUTSIGNALS v6

Table 135: ZMMPDIS Output signals


Name Type Description
TRIP BOOLEAN General Trip, issued from any phase or loop
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
Table continues on next page

238 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Name Type Description


TRL3 BOOLEAN Trip signal from phase L3
START BOOLEAN General Start, issued from any phase or loop
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3
STND BOOLEAN Non-directional start, issued from any phase or loop

PID-3640-INPUTSIGNALS v6

Table 136: ZMMAPDIS Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKZ BOOLEAN 0 Blocks all output by fuse failure signal
BLKTR BOOLEAN 0 Blocks all trip outputs
STCND INTEGER 0 External start condition (loop enabler)
DIRCND INTEGER 0 External directional condition

PID-3640-OUTPUTSIGNALS v6

Table 137: ZMMAPDIS Output signals


Name Type Description
TRIP BOOLEAN General Trip, issued from any phase or loop
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
START BOOLEAN General Start, issued from any phase or loop
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3
STND BOOLEAN Non-directional start, issued from any phase or loop

8.5.5 Settings
PID-3645-SETTINGS v6

Table 138: ZMMPDIS Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
OperationDir Non-directional - - Forward Operation mode of directionality
Forward NonDir / Forw / Rev
Reverse
X1 0.50 - 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach
Table continues on next page

Line distance protection REL670 239


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Name Values (Range) Unit Step Default Description


R1 0.10 - 1000.00 Ohm/p 0.01 5.00 Positive seq. resistance for zone
characteristic angle
X0 0.50 - 9000.00 Ohm/p 0.01 100.00 Zero sequence reactance reach
R0 0.50 - 3000.00 Ohm/p 0.01 15.00 Zero seq. resistance for zone
characteristic angle
RFPE 1.00 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach in ohm/loop,
Ph-E
OpModetPE Off - - On Operation mode Off / On of Zone
On timer, Ph-E
tPE 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-E
IMinOpPE 10 - 30 %IB 1 20 Minimum operate phase current for
Phase-Earth loops
IMinOpIN 5 - 30 %IB 1 5 Minimum operate residual current for
Phase-Earth loops

Table 139: ZMMPDIS Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

PID-3640-SETTINGS v6

Table 140: ZMMAPDIS Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
OperationDir Non-directional - - Forward Operation mode of directionality
Forward NonDir / Forw / Rev
Reverse
X1 0.50 - 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach
R1 0.10 - 1000.00 Ohm/p 0.01 5.00 Positive seq. resistance for zone
characteristic angle
X0 0.50 - 9000.00 Ohm/p 0.01 120.00 Zero sequence reactance reach
R0 0.50 - 3000.00 Ohm/p 0.01 15.00 Zero seq. resistance for zone
characteristic angle
RFPE 1.00 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach in ohm/loop,
Ph-E
OpModetPE Off - - On Operation mode Off / On of Zone
On timer, Ph-E
tPE 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-E
IMinOpPE 10 - 30 %IB 1 20 Minimum operate phase current for
Phase-Earth loops

Table 141: ZMMAPDIS Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

240 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

8.5.6 Operation principle

8.5.6.1 Full scheme measurement SEMOD154546-4 v2

The different fault loops within the IED are operating in parallel in the same principle as a full
scheme measurement.

Figure 111 presents an outline of the different measuring loops for the basic five, impedance-
measuring zones l.

L1-N L2-N L3-N Zone 1

L1-N L2-N L3-N Zone 2

L1-N L2-N L3-N Zone 3

L1-N L2-N L3-N Zone 4

L1-N L2-N L3-N Zone 5

en07000080.vsd
IEC07000080 V1 EN-US

Figure 111: The different measuring loops at line-earth fault and phase-phase fault.

8.5.6.2 Impedance characteristic SEMOD154546-11 v4

The distance measuring zone include three impedance measuring loops; one fault loop for
each phase.

The distance measuring zone will essentially operate according to the non-directional
impedance characteristics presented in Figure 112. The characteristic is illustrated with the full
loop reach.

Line distance protection REL670 241


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

X (Ohm/loop)

R1PE+Rn

RFPE RFPE

X0PE-X1PE
Xn =
3
X1PE+Xn R0PE-R1PE
Rn =
3
jN jN
R (Ohm/loop)

RFPE RFPE

X1PE+Xn

RFPE RFPE
en08000280-2-en.vsd

R1PE+Rn
IEC08000280 V1 EN-US

Figure 112: Characteristic for the phase-to-earth measuring loops, ohm/loop domain.
The fault loop reach may also be presented as in Figure 113.

ILn R1 + j X1
Phase-to-earth
UL1
element

Phase-to-earth
fault in phase L1 RFPE
(Arc + tower
resistance)

0
IN (R0-R1)/3 +
j (X0-X1)/3 ) en06000412.vsd
IEC06000412 V1 EN-US

Figure 113: Fault loop model


The R1 and jX1 in Figure 113 represent the positive sequence impedance from the measuring
point to the fault location. The RFPE is presented in order to “convey” the fault resistance
reach.

The zone may be set to operate in Non-directional, Forward, Off or Reverse direction through
the setting OperationDir. The result from respective set value is illustrated in Figure 114. The
impedance reach is symmetric, in the sense that it is conform for forward and reverse
direction. Therefore, all reach settings apply to both directions.

242 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

X X X

R R R

Non-directional Forward Reverse

IEC05000182-2-en.vsdx

IEC05000182 V2 EN-US

Figure 114: Directional operating modes of the distance measuring zone

8.5.6.3 Minimum operating current SEMOD154546-36 v2

The operation of the distance measuring zone is blocked if the magnitude of input currents fall
below certain threshold values.

The phase-to-earth loop Ln is blocked if ILn < IMinOpPE.

For zone 1 with load compensation feature the additional criterion applies, that all phase-to-
earth loops will be blocked when IN < IMinOpIN, regardless of the phase currents.

ILn is the RMS value of the current in phase Ln. IN is the RMS value of the vector sum of the
three phase currents, that is, residual current 3I0.

Both current limits IMinOpPE and IMinOpIN are automatically reduced to 75%
of regular set values if the zone is set to operate in reverse direction, that is,
OperationDir=Reverse.

8.5.6.4 Measuring principles SEMOD154546-46 v3

Fault loop equations use the complex values of voltage, current, and changes in the current.
Apparent impedances are calculated and compared with the set limits.

Here U and I represent the corresponding voltage and current phasors in the respective phase
Ln (n = 1, 2, 3).

The calculation of the apparant impedances at phase-to-earth fault follow equation 38

The earth return compensation applies in a conventional manner.

Line distance protection REL670 243


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

U L1
Z app =
I L1 + I N × KN
EQUATION1223 V2 EN-US (Equation 38)

Where:
UL1, IL1 and IN are the phase voltage, phase current and residual current present to the IED
KN is defined as:

Z 0 - Z1
KN =
3 × Z1
EQUATION-2105 V2 EN-US

Z 0 = R 0 + jX 0
EQUATION2106 V2 EN-US

Z 1 = R1 + jX 1
EQUATION2107 V2 EN-US

Where
R0 is setting of the resistive zero sequence reach
X0 is setting of the reactive zero sequence reach
R1 is setting of the resistive positive sequence reach
X1 is setting of the reactive positive sequence reach

Here IN is a phasor of the residual current in IED point. This results in the same reach along the
line for all types of faults.

The apparent impedance is considered as an impedance loop with resistance R and reactance
X.

The formula given in equation 38 is only valid for no loaded radial feeder applications. When
load is considered in the case of single phase-to-earth fault, conventional distance protection
might overreach at exporting end and underreach at importing end. IED has an adaptive load
compensation which increases the security in such applications.

Measuring elements receive current and voltage information from the A/D converter. The
check sums are calculated and compared, and the information is distributed into memory
locations. For each of the six supervised fault loops, sampled values of voltage (U), current (I),
and changes in current between samples (DI) are brought from the input memory and fed to a
recursive Fourier filter.

The filter provides two orthogonal values for each input. These values are related to the loop
impedance according to equation 39,

X Di
U = R × i + ------ × -----
w 0 Dt
EQUATION1224 V1 EN-US (Equation 39)

in complex notation, or:

244 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

X D Re ( I )
Re ( U ) = R × Re ( I ) + ------ × ------------------
w0 Dt

EQUATION354 V1 EN-US (Equation 40)

X DIm ( I )
Im ( U ) = R × Im ( I ) + ------ × -----------------
w0 Dt

EQUATION355 V1 EN-US (Equation 41)

with

w0 = 2 × p × f 0
EQUATION356 V1 EN-US (Equation 42)

where:
Re designates the real component of current and voltage,
Im designates the imaginary component of current and voltage and
f0 designates the rated system frequency

The algorithm calculates Rm measured resistance from the equation for the real value of the
voltage and substitute it in the equation for the imaginary part. The equation for the Xm
measured reactance can then be solved. The final result is equal to:

Im ( U ) × DRe ( I ) – Re ( U ) × D Im ( I )
R m = ------------------------------------------------------------------------------------
DRe ( I ) × Im ( I ) – D Im ( I ) × Re ( I )
EQUATION357 V1 EN-US (Equation 43)

Re ( U ) × Im ( I ) – Im ( U ) × Re ( I )
Xm = w 0 × Dt × -------------------------------------------------------------------------------
DRe ( I ) × Im ( I ) – DIm ( I ) × Re ( I )
EQUATION358 V1 EN-US (Equation 44)

The calculated Rm and Xm values are updated each sample and compared with the set zone
reach. The adaptive tripping counter counts the number of permissive tripping results. This
effectively removes any influence of errors introduced by the capacitive voltage transformers
or by other factors.

The directional evaluations are performed simultaneously in both forward and reverse
directions, and in all six fault loops. Positive sequence voltage and a phase locked positive
sequence memory voltage are used as a reference. This ensures unlimited directional
sensitivity for faults close to the IED point.

8.5.6.5 Directionality SEMOD154546-97 v3

The evaluation of the directionality takes place in the Directional impedance element for mho
characteristic ZDMRDIR function. Equation 45 is used to classify that the fault is in forward
direction for line-to-earth fault.

Line distance protection REL670 245


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

0.85 × U1L1 + 0.15 × U1L1M


- ArgDir < arg < ArgNeg Re s
I L1
EQUATION1617 V1 EN-US (Equation 45)

where:
ArgDir is the setting for the lower boundary of the forward directional characteristic, by default set to 15
(= -15 degrees) and
ArgNegRes is the setting for the upper boundary of the forward directional characteristic, by default set to
115 degrees, see figure 115.
U1L1 is positive sequence phase voltage in phase L1

U1L1M is positive sequence memorized phase voltage in phase L1

IL1 is phase current in phase L1

The setting of ArgDir and ArgNegRes is by default set to 15 (= -15) and 115 degrees respectively
(see figure 115) and it should not be changed unless system studies have shown the necessity.

ZDMRDIR gives a binary coded signal on the output STDIRCND depending on the evaluation
where STFWL1N=1 adds 1, STRVL1N=1 adds 2, STFWL2N=1 adds 4 etc.

ArgNegRes

ArgDir
R

en05000722.vsd
IEC05000722 V1 EN-US

Figure 115: Setting angles for discrimination of forward and reverse fault
The reverse directional characteristic is equal to the forward characteristic rotated by 180
degrees.

The polarizing voltage is available as long as the positive-sequence voltage exceeds 5% of the
set base voltage UBase. So the directional element can use it for all unsymmetrical faults
including close-in faults.

246 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

For close-in three-phase faults, the U1L1M memory voltage, based on the same positive
sequence voltage, ensures correct directional discrimination.

The memory voltage is used for 100 ms or until the positive sequence voltage is restored.

After 100 ms, the following occurs:

• If the current is still above the set value of the minimum operating current (between 10
and 30% of the set IED rated current IBase), the condition seals in.
• If the fault has caused tripping, the trip endures.
• If the fault was detected in the reverse direction, the measuring element in the
reverse direction remains in operation.
• If the current decreases below the minimum operating value, the memory resets until the
positive sequence voltage exceeds 10% of its rated value.

8.5.6.6 Simplified logic diagrams SEMOD154548-4 v1

Distance protection zones SEMOD154548-6 v3


The design of distance protection zone 1 is presented for all measuring phase-to-earth loops.

Phase-to-earth related signals are designated by LnE, where n represents the corresponding
phase number (L1E, L2E, and L3E).

Fulfillment of two different measuring conditions is necessary to obtain the one logical signal
for each separate measuring loop:

• Zone measuring condition, which follows the operating equations described above.
• Group functional input signal (STCND), as presented in figure 116.

The STCND input signal represents a connection of six different integer values from the phase
selection function within the IED, which are converted within the zone measuring function into
corresponding boolean expressions for each condition separately. It is connected to the Phase
selection with load enchroachment, quadrilateral characteristic (FDPSPDIS) function output
STCNDZ.

The input signal DIRCND is used to give condition for directionality for the distance measuring
zones. The signal contains binary coded information for both forward and reverse direction.
The zone measurement function filter out the relevant signals on the DIRCND input depending
on the setting of the parameter OperationDir. It shall be configured to the DIRCND output on
the Directional impedance element for mho characteristic (ZDMRDIR) function.

Line distance protection REL670 247


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

STCND

AND STNDL1N
L1N

AND STNDL2N
L2N

STNDL3N
L3N AND

OR STNDPE

OR
BLKZ STND
OR AND
BLOCK
BLK

en06000408-2.vsd
IEC06000408 V2 EN-US

Figure 116: Conditioning by a group functional input signal STCND


Composition of the phase starting signals for a case, when the zone operates in a non-
directional mode, is presented in figure 117.

STNDL1N 15 ms
AND t STL1

STNDL2N 15 ms
AND t STL2

STNDL3N 15 ms
AND t STL3

15 ms
AND t START
OR

BLK

en06000409.vsd
IEC06000409 V1 EN-US

Figure 117: Composition of starting signals in non-directional operating mode


Results of the directional measurement enter the logic circuits, when the zone operates in
directional (forward or reverse) mode, see figure 118.

248 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

STNDL1N
DIRL1N AND
OR STZMPE.
&
STNDL2N
DIRL2N AND

STNDL3N 15 ms
STL1
& t
DIRL3N AND

15 ms
STL2
& t

15 ms
STL3
& t

BLK

15 ms
OR START
& t

en07000081.vsd
IEC07000081 V1 EN-US

Figure 118: Composition of starting signals in directional operating mode


Tripping conditions for the distance protection zone one are symbolically presented in figure
119.

Timer tPE=On tPE


AND t
STZMPE
15ms
BLKTR AND t
TRIP

STL1 AND TRL1

STL2 AND TRL2

STL3 AND TRL3

en07000082.vsd
IEC07000082 V1 EN-US

Figure 119: Tripping logic for the distance protection zone one

Line distance protection REL670 249


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

8.5.7 Technical data


SEMOD173249-2 v8

Table 142: ZMMPDIS technical data


Function Range or value Accuracy
Number of zones Max 5 with selectable -
direction
Minimum operate current (10-30)% of IBase -
Positive sequence reactance (0.50-3000.00) W/phase ±2.0% static accuracy
±2.0 degrees static angular accuracy
Positive sequence resistance (0.10-1000.00) Ω/phase Conditions:
Zero sequence reactance (0.50-9000.00) Ω/phase Voltage range: (0.1-1.1) x Ur
Current range: (0.5-30) x Ir
Zero sequence resistance (0.50-3000.00) Ω/phase Angle: at 0 degrees and 85 degrees
Fault resistance, Ph-E (1.00-9000.00) W/loop
Dynamic overreach <5% at 85 degrees measured -
with CCVT’s and 0.5<SIR<30
Definite time delay Ph-Ph and (0.000-60.000) s ±0.2% or ±40 ms whichever is greater
Ph-E operation
Operate time 25 ms typically IEC 60255-121
Reset ratio 105% typically -
Reset time at 0.1 x Zreach to 2 Min. = 20 ms -
x Zreach Max. = 50 ms

8.6 Directional impedance element for mho characteristic


and additional distance protection directional function
for earth faults ZDMRDIR, ZDARDIR SEMOD154813-1 v3

8.6.1 Identification
SEMOD155886-2 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Directional impedance element for ZDMRDIR 21D
mho characteristic
Z
S00346 V2 EN-US

GUID-39299546-12A2-4D9D-86D0-A33F423944E4 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Additional distance protection ZDARDIR -
directional function for earth faults
Z
S00346 V2 EN-US

250 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

8.6.2 Functionality SEMOD154885-5 v9

The phase-to-earth impedance elements can be supervised by a phase unselective directional


function based on symmetrical components (option).

8.6.3 Function block SEMOD155551-4 v5

ZDMRDIR
I3P* DIR_CURR
U3P* DIR_VOLT
DIR_POL
STFW
STRV
STDIRCND

IEC06000422_2_en.vsd
IEC06000422 V2 EN-US

Figure 120: ZDMRDIR function block


SEMOD155560-4 v3

ZDARDIR
I3P* STFWPE
U3P* STRVPE
I3PPOL* DIREFCND
DIRCND

IEC06000425-2-en.vsd
IEC06000425 V2 EN-US

Figure 121: ZDARDIR function block

8.6.4 Signals
PID-3546-INPUTSIGNALS v7

Table 143: ZDMRDIR Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL

PID-3546-OUTPUTSIGNALS v7

Table 144: ZDMRDIR Output signals


Name Type Description
CURR GROUP SIGNAL Group signal for current signals to Mho function
VOLT GROUP SIGNAL Group signal for voltage signals to Mho function
POL GROUP SIGNAL Group signal for polarization voltage signals to Mho function
STFW BOOLEAN Start in forward direction
STRV BOOLEAN Start in reverse direction
STDIRCND INTEGER Binary coded directional information per measuring loop

Line distance protection REL670 251


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

PID-3564-INPUTSIGNALS v7

Table 145: ZDARDIR Input signals


Name Type Default Description
I3P GROUP - Current signals
SIGNAL
U3P GROUP - Voltage signals
SIGNAL
I3PPOL GROUP - Polarisation current signals
SIGNAL
DIRCND INTEGER 0 Binary coded directional signal

PID-3564-OUTPUTSIGNALS v7

Table 146: ZDARDIR Output signals


Name Type Description
STFWPE BOOLEAN Forward start signal from phase-to-ground directional
element
STRVPE BOOLEAN Reverse start signal from phase-to-ground directional
element
DIREFCND INTEGER Start direction Binary coded

8.6.5 Settings
PID-3546-SETTINGS v7

Table 147: ZDMRDIR Group settings (basic)


Name Values (Range) Unit Step Default Description
DirEvalType Impedance - - Comparator Directional evaluation mode
Comparator Impedance / Comparator
Imp/Comp
ArgNegRes 90 - 175 Deg 1 115 Angle of blinder in second quadrant
for forward direction
ArgDir 5 - 45 Deg 1 15 Angle of blinder in fourth quadrant for
forward direction
IMinOpPE 5 - 30 %IB 1 5 Minimum operate phase current for
Phase-Earth loops
IMinOpPP 5 - 30 %IB 1 10 Minimum operate phase-phase
current for Phase-Phase loops

Table 148: ZDMRDIR Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

252 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

PID-3564-SETTINGS v7

Table 149: ZDARDIR Group settings (basic)


Name Values (Range) Unit Step Default Description
PolMode -3U0 - - -3U0 Polarization quantity for opt dir
-U2 function for P-E faults
IPol
Dual
-3U0Comp
-U2comp
AngleRCA -90 - 90 Deg 1 75 Characteristic relay angle (= MTA or
base angle)
I> 5 - 200 %IB 1 5 Minimum operation current in % of
IBase
UPol> 4 - 100 %UB 1 4 Minimum polarizing voltage in % of
UBase
IPol> 5 - 100 %IB 1 10 Minimum polarizing current in % of
IBase

Table 150: ZDARDIR Group settings (advanced)


Name Values (Range) Unit Step Default Description
AngleOp 90 - 180 Deg 1 160 Operation sector angle
Kmag 0.50 - 3000.00 Ohm 0.01 40.00 Boost-factor in -U0comp and -
U2comp polarization

Table 151: ZDARDIR Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

8.6.6 Monitored data


PID-3546-MONITOREDDATA v6

Table 152: ZDMRDIR Monitored data


Name Type Values (Range) Unit Description
L1Dir INTEGER 1=Forward - Direction in phase L1
2=Reverse
0=No direction
L2Dir INTEGER 1=Forward - Direction in phase L2
2=Reverse
0=No direction
L3Dir INTEGER 1=Forward - Direction in phase L3
2=Reverse
0=No direction
L1R REAL - Ohm Resistance in phase L1
L1X REAL - Ohm Reactance in phase L1
L2R REAL - Ohm Resistance in phase L2
L2X REAL - Ohm Reactance in phase L2
L3R REAL - Ohm Resistance in phase L3
L3X REAL - Ohm Reactance in phase L3

Line distance protection REL670 253


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

8.6.7 Operation principle

8.6.7.1 Directional impedance element for mho characteristic ZDMRDIR SEMOD154817-5 v7

The evaluation of the directionality takes place in Directional impedance element for mho
characteristic (ZDMRDIR). Equation 46 and equation 47 are used to classify that the fault is in
the forward direction for phase-to-earth fault and phase-to-phase fault respectively.

0.85 × U1L1 + 0.15 × U1L1M


- ArgDir < arg < ArgNeg Re s
I L1
EQUATION1617 V1 EN-US (Equation 46)

0.85 × U1L1L 2 + 0.15 × U1L1L 2 M


- ArgDir < arg < ArgNeg Re s
I L1L 2
EQUATION1619 V1 EN-US (Equation 47)

Where:
ArgDir Setting for the lower boundary of the forward directional characteristic, by
default set to 15 (= -15 degrees)
ArgNegRes Setting for the upper boundary of the forward directional characteristic, by
default set to 115 degrees, see figure 122 for mho characteristics.
U1L1 Positive sequence phase voltage in phase L1

U1L1M Positive sequence memorized phase voltage in phase L1

IL1 Phase current in phase L1

U1L1L2 Voltage difference between phase L1 and L2 (L2 lagging L1)

U1L1L2M Memorized voltage difference between phase L1 and L2 (L2 lagging L1)

IL1L2 Current difference between phase L1 and L2 (L2 lagging L1)

The default settings for ArgDir and ArgNegRes are 15 (= -15) and 115 degrees respectively (see
figure 122) and they should not be changed unless system studies show the necessity.

If one sets DirEvalType to Comparator (which is recommended when using the mho
characteristic) then the directional lines are computed by means of a comparator-type
calculation, meaning that the directional lines are based on mho-circles (of infinite radius). The
default setting value Impedance otherwise means that the directional lines are implemented
based on an impedance calculation equivalent to the one used for the quadrilateral impedance
characteristics.

When Directional impedance element for mho characteristic (ZDMRDIR) is used


together with Fullscheme distance protection, mho characteristic (ZMHPDIS)
the following settings for parameter DirEvalType is vital:

• alternative Comparator is strongly recommended


• alternative Imp/Comp should generally not be used
• alternative Impedanceshould not be used. This altenative is intended for
use together with Distance protection zone, quadrilateral characteristic
(ZMQPDIS)

254 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

X
Zset reach point

ArgNegRes

-ArgDir R

-Zs
en06000416.vsd

IEC06000416 V1 EN-US

Figure 122: Setting angles for discrimination of forward fault


The reverse directional characteristic is equal to the forward characteristic rotated by 180
degrees.

The code built up for release of the measuring fault loops is as follows: STDIRCND = L1N*1 +
L2N*2 + L3N*4 + L1L2*8 + L2L3*16 + L3L1*32

Example: If only L1Nstart, the value is 1, if start in L1N and L3N are detected, the value is 1+4=5.

The polarizing voltage is available as long as the positive-sequence voltage exceeds 5% of the
set base voltage UBase, thus the directional element can use it for all unsymmetrical faults
including close-in faults.

For close-in three-phase faults, the U1L1M memory voltage, based on the same positive
sequence voltage, ensures correct directional discrimination.

The memory voltage is used for 100ms or until the positive sequence voltage is restored. After
100ms, the following occurs:

• If the current is still above the set value of the minimum operating current the condition
seals in.
• If the fault has caused tripping, the trip continues.
• If the fault was detected in the reverse direction, the measuring element in the
reverse direction remains in operation.
• If the current decreases below the minimum operate value, no directional indications will
be given until the positive sequence voltage exceeds 10% of its rated value.

The Directional impedance element for mho characteristic (ZDMRDIR) function has the
following output signals:

The STDIRCND output provides an integer signal that depends on the evaluation and is derived
from a binary coded signal as follows:

Line distance protection REL670 255


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

bit 11 bit 10 bit 9 bit 8 bit 7 bit 6


(2048) (1024) (512) (256) (128) (64)
STRVL3L1=1 STRVL2L3=1 STRVL1L2=1 STRVL3N=1 STRVL2N=1 STRVL1N=1
bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
(32) (16) (8) (4) (2) (1)
STFWL3L1= STFWL2L3= STFWL1L2= STFWL3N=1 STFWL2N=1 STFWL1N=1
1 1 1

The STFW output is a logical signal with value 1 or 0. It is made up as an OR-function of all the
forward starting conditions, that is, STFWL1N, STFWL2N, STFWL3N, STFWL1L2, STFWL2L3 and
STFWL3L1. The STRV output is similar to the STFW output, the only difference being that it is
made up as an OR-function of all the reverse starting conditions, that is, STRVL1N, STRVL2N,
STRVL3N, STRVL1L2, STRVL2L3 and STRVL3L1.

8.6.7.2 Additional distance protection directional function for earth faults


ZDARDIR SEMOD154933-95 v5

A Mho element needs a polarizing voltage to operate. The positive-sequence memory-


polarized elements are generally preferred. The benefits include:

• The greatest amount of expansion for improved resistive coverage. These elements
always expand back to the source.
• Memory action for all fault types. This is very important for close-in three-phase faults.
• A common polarizing reference for all six distance-measuring loops. This is important for
single-pole tripping, during a pole-open period.

There are however some situations that can cause security problems like reverse phase to
phase faults and double phase-to-earth faults during high load periods. To solve these,
additional directional element is used.

For phase-to-earth faults, directional elements using sequence components are very reliable
for directional discrimination. The directional element can be based on one of following types
of polarization:

• Zero-sequence voltage
• Negative-sequence voltage
• Zero-sequence current

These additional directional criteria are evaluated in the Additional distance protection
directional function for earth faults (ZDARDIR).

Zero-sequence voltage polarization is utilizing the phase relation between the zero-sequence
voltage and the zero-sequence current at the location of the protection. The measurement
principle is illustrated in figure 123.

256 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

- 3U 0

AngleOp
AngleRCA

3I 0

en06000417.vsd
IEC06000417 V1 EN-US

Figure 123: Principle for zero-sequence voltage polarized additional directional element
Negative-sequence voltage polarization is utilizing the phase relation between the negative-
sequence voltage and the negative-sequence current at the location of the protection.

Zero-sequence current polarization is utilizing the phase relation between the zero-sequence
current at the location of the protection and some reference zero-sequence current, for
example, the current in the neutral of a power transformer.

The principle of zero-sequence voltage polarization with zero-sequence current compensation


is described in figure 124. The same also applies for the negative-sequence function.

Z0 SA I0 I0
Z0 Line Z0 SB
Charac te ris tic
ang le
U0 U0
K*I0

U0 + K*I0
IF
en06000418.vsd
IEC06000418 V1 EN-US

Figure 124: Principle for zero sequence compensation


Note that the sequence based additional directional element cannot give per phase
information about direction to fault. This is why it is an AND-function with the normal
directional element that works on a per phase base. The enable signals are per phase and to
enable the measuring element in a specific phase, both the additional directional element and
the normal directional element, for that phase must indicate correct direction.

These polarization quantities, voltage and current, are stabilized against minimum polarizing
voltage (UPOL>) and current (IPOL>). That means if polarizing voltage is greater than UPOL>
setting, and if polarizing current is greater than IPol>, then only they are used for direction
determination.

Line distance protection REL670 257


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Normal
directional Release of distance
element measuring element
L1N, L2N, L3N L1N, L2N, L3N
AND

Additional
directional AND per
element phase

en06000419.vsd
IEC06000419 V1 EN-US

Figure 125: Earth distance element directional supervision

8.7 Mho impedance supervision logic ZSMGAPC SEMOD153841-1 v3

8.7.1 Identification
GUID-030C086A-8301-481E-BA0A-6550A9C1482E v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Mho Impedance supervision logic ZSMGAPC - -

8.7.2 Functionality SEMOD153843-5 v3

The Mho impedance supervision logic (ZSMGAPC) includes features for fault inception
detection and high SIR detection. It also includes the functionality for loss of potential logic as
well as for the pilot channel blocking scheme.

ZSMGAPC can mainly be decomposed in two different parts:

1. A fault inception detection logic


2. High SIR detection logic

8.7.3 Function block SEMOD155607-4 v4

ZSMGAPC
I3P* BLKZMTD
U3P* BLKCHST
BLOCK CHSTOP
REVSTART HSIR
BLOCKCS
CBOPEN

IEC06000426-2-en.vsd
IEC06000426 V2 EN-US

Figure 126: ZSMGAPC function block

258 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

8.7.4 Signals
PID-6718-INPUTSIGNALS v1

Table 153: ZSMGAPC Input signals


Name Type Default Description
I3P GROUP - Three phase current samples and DFT magnitude
SIGNAL
U3P GROUP - Three phase phase-neutral voltage samples and DFT
SIGNAL magnitude
BLOCK BOOLEAN 0 Block of the function
REVSTART BOOLEAN 0 Indication of reverse start
BLOCKCS BOOLEAN 0 Blocks the blocking carrier signal to remote end
CBOPEN BOOLEAN 0 Indicates that the breaker is open

PID-6718-OUTPUTSIGNALS v1

Table 154: ZSMGAPC Output signals


Name Type Description
BLKZMTD BOOLEAN Block signal for blocking of time domained mho
BLKCHST BOOLEAN Blocking signal to remote end to block overreaching zone
CHSTOP BOOLEAN Stops the blocking signal to remote end
HSIR BOOLEAN Indication of source impedance ratio above set limit

8.7.5 Settings
PID-6718-SETTINGS v1

Table 155: ZSMGAPC Group settings (basic)


Name Values (Range) Unit Step Default Description
PilotMode Off - - Off Pilot mode Off/On
On
Zreach 0.1 - 3000.0 Ohm 0.1 38.0 Line impedance
IMinOp 10 - 30 %IB 1 20 Minimum operating current for SIR
measurement

Table 156: ZSMGAPC Group settings (advanced)


Name Values (Range) Unit Step Default Description
DeltaI 0 - 200 %IB 1 10 Current change level in % of IBase for
fault inception detection
Delta3I0 0 - 200 %IB 1 10 Zero seq current change level in % of
IBase
DeltaU 0 - 100 %UB 1 5 Voltage change level in % of UBase for
fault inception detection
Delta3U0 0 - 100 %UB 1 5 Zero seq voltage change level in % of
UBase
SIRLevel 5 - 15 - 1 10 Settable level for source impedance
ratio

Line distance protection REL670 259


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Table 157: ZSMGAPC Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

8.7.6 Operation principle

8.7.6.1 Fault inception detection SEMOD153847-4 v5

The aim for the fault inception detector is to quickly detect that a fault has occurred in the
system. The fault detector detects a fault when there is a sufficient change in at least one
current and at the same time there is a sufficient change in at least one voltage. A change is
defined roughly by the difference between the present instantaneous value and the one from
one power system cycle before. The change is sufficient if it exceeds the related threshold
value. DeltaI and DeltaU for phase currents and voltages. Delta3I0 and Delta3U0 for residual
current and voltage.

If the setting PilotMode is set to On in blocking scheme and the fault inception function has
detected a system fault, a block signal BLKCHST is issued and send to remote end in order to
block the overreaching zones. Different criteria has to be fulfilled for sending the BLKCHST
signal:

1. The setting PilotMode has to be set to On


2. The breaker has to be closed, that is, the input signal CBOPEN should not be actived
3. A reverse fault should have been detected while the carrier send signal is not blocked, that
is, input signal REVSTART is activated and input signal BLOCKCS is not activated or a fault
inception is detected and input signal CSBLOCK is not activated.

If it is later detected that it was an internal fault that made the function issue the BLKCHST
signal, the function issues a CHSTOP signal to unblock the remote end. The criteria that have to
be fulfilled for this are:

1. The function has to be in pilot mode, that is, the setting PilotMode has to be set to On
2. The carrier send signal should be blocked, that is, input signal BLOCKCS is On and,
3. A reverse fault should not have been detected while the carrier send signal was not
blocked, that is, input REVSTART should not have been activated before BLOCKCS.

If loss of voltage is detected, but not a fault inception, the distance protection function is
blocked. This is also the case if a fuse failure is detected by the external fuse failure function
and activate the input FUSEFAIL. Those blocks are generated by activating the output BLKZ,
which are connected to the input BLKZ on the distance Mho function block.

During fault inception a lot of transients are developed which in turn might cause the distance
function to overreach. The Mho supervision logic (ZSMGAPC) increases the filtering during the
most transient period of the fault. This is done by activating the output BLKZMTD, which is
connected to the input BLKZMTD on mho distance function block.

High SIR detection SEMOD153847-22 v3


High SIR values increases the likelihood that CVT will introduce a prolonged and distorted
transient, increasing the risk for overreach of the distance function.

The SIR function calculates the SIR value as the source impedance divided by the setting
Zreach and activates the output signal HSIR if the calculated value for any of the six basic
shunt faults exceed the setting SIRLevel. The HSIR signal is intended to block the delta based
mho impedance function.

260 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

8.8 Faulty phase identification with load encroachment


FMPSPDIS SEMOD153819-1 v5

8.8.1 Identification
SEMOD155879-2 v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Faulty phase identification with load FMPSPDIS 21
encroachment for mho
Z
S00346 V2 EN-US

8.8.2 Functionality SEMOD153825-5 v7

The ability to accurately and reliably classify different types of fault so that single phase
tripping and autoreclosing can be used plays an important roll in today's power systems.

The phase selection function is design to accurately select the proper fault loop(s) in the
distance function dependent on the fault type.

The heavy load transfer that is common in many transmission networks may in some cases
interfere with the distance protection zone reach and cause unwanted operation. Therefore
the function has a built in algorithm for load encroachment, which gives the possibility to
enlarge the resistive setting of the measuring zones without interfering with the load.

The output signals from the phase selection function produce important information about
faulty phase(s), which can be used for fault analysis as well.

8.8.3 Function block SEMOD155615-4 v4

FMPSPDIS
I3P* STL1
U3P* STL2
BLOCK STL3
ZSTART STPE
TR3PH STCNDPHS
1POLEAR STCNDPLE
STCNDLE
START

IEC06000429-2-en.vsd
IEC06000429 V2 EN-US

Figure 127: FMPSPDIS function block

8.8.4 Signals
PID-3541-INPUTSIGNALS v9

Table 158: FMPSPDIS Input signals


Name Type Default Description
I3P GROUP - Group signal for current
SIGNAL
U3P GROUP - Group signal for voltage
SIGNAL
BLOCK BOOLEAN 0 Block of function
Table continues on next page

Line distance protection REL670 261


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Name Type Default Description


ZSTART BOOLEAN 0 Start from underimpdeance function
TR3PH BOOLEAN 0 Three phase tripping initiated
1POLEAR BOOLEAN 0 Single pole autoreclosing in progress

PID-3541-OUTPUTSIGNALS v9

Table 159: FMPSPDIS Output signals


Name Type Description
STL1 BOOLEAN Fault detected in phase L1
STL2 BOOLEAN Fault detected in phase L2
STL3 BOOLEAN Fault detected in phase L3
STPE BOOLEAN Earth fault detected
STCNDPHS INTEGER Binary coded starts from phase selection
STCNDPLE INTEGER Binary coded starts from ph sel with load encroachment
STCNDLE INTEGER Binary coded starts from load encroachment only
START BOOLEAN Indicates that something has started

8.8.5 Settings
PID-3541-SETTINGS v9

Table 160: FMPSPDIS Group settings (basic)


Name Values (Range) Unit Step Default Description
IMaxLoad 10 - 5000 %IB 1 200 Maximum load for identification of
three phase fault in % of IBase
RLd 1.00 - 3000.00 Ohm/p 0.01 80.00 Load encroachment resistive reach in
ohm/phase
ArgLd 5 - 70 Deg 1 20 Load encroachment inclination of load
angular sector

Table 161: FMPSPDIS Group settings (advanced)


Name Values (Range) Unit Step Default Description
DeltaIMinOp 5 - 100 %IB 1 10 Delta current level in % of IBase
DeltaUMinOp 5 - 100 %UB 1 20 Delta voltage level in % of UBase
U1Level 5 - 100 %UB 1 80 Pos seq voltage limit for identification
of 3-ph fault
I1LowLevel 5 - 200 %IB 1 10 Pos seq current level for identification
of 3-ph fault in % of IBase
U1MinOp 5 - 100 %UB 1 20 Minimum operate positive sequence
voltage for ph sel
U2MinOp 1 - 100 %UB 1 5 Minimum operate negative sequence
voltage for ph sel
INRelPE 10 - 100 %IB 1 20 3I0 limit for release ph-e measuring
loops in % of max phase current
INBlockPP 10 - 100 %IB 1 40 3I0 limit for blocking phase-to-phase
measuring loops in % of max phase
current

262 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Table 162: FMPSPDIS Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

8.8.6 Operation principle

8.8.6.1 The phase selection function SEMOD153832-4 v3

Faulty phase identification with load encroachment for mho (FMPSPDIS) function can be
decomposed into six different parts:

1. A high speed delta based current phase selector


2. A high speed delta based voltage phase selector
3. A symmetrical components based phase selector
4. Fault evaluation and selection logic
5. A load encroachment logic
6. A blinder logic

The total function can be blocked by activating the input BLOCK.

Delta based current and voltages SEMOD153832-14 v5


The delta based fault detection function uses adaptive technique and is based on patent
US4409636.

The aim of the delta based phase selector is to provide very fast and reliable phase selection
for releasing of tripping from the high speed Mho measuring element and is essential to
Directional Comparison Blocking scheme (DCB), which uses Power Line Carrier (PLC)
communication system along the protected line.

The current and voltage samples for each phase passes through a notch filter that filters out
the fundamental components. Under steady state load conditions or when no fault is present,
the output of the filter is zero or close to zero. When a fault occurs, currents and voltages
change resulting in sudden changes in the currents and voltages resulting in non-fundamental
waveforms being introduced on the line. At this point the notch filter produces significant
non-zero output. The filter output is processed by the delta function. The algorithm uses an
adaptive relationship between phases to determine if a fault has occurred, and determines the
faulty phases.

The current and voltage delta based phase selector gives a real output signal if the following
criterion is fulfilled (only phase L1 shown):

Max(ΔUL1,ΔUL2,ΔUL3)>DeltaUMinOp

Max(ΔIL1,ΔIL2,ΔIL3)>DeltaIMinOp

where:
ΔUL1, ΔUL2 and ΔUL3 are the voltage change between sample t and sample t-1
DeltaUMinOp and are the minimum harmonic level settings for the voltage and
DeltaIMinOp current filters to decide that a fault has occurred. A slow evolving
fault may not produce sufficient harmonics to detect the fault;
however, in such a case speed is no longer the issue and the
sequence components phase selector will operate.

Line distance protection REL670 263


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

The delta voltages ΔULn and delta current ΔILn (n index for phase order) are the voltage and
current between sample t and sample t-1.

The delta phase selector employs adaptive techniques to determine the fault type. The logic
determines the fault type by summing up all phase values and dividing by the largest value.
Both voltages and currents are filtered out and evaluated. The condition for fault type
classification for the voltages and currents can be expressed as:

FaulType =
∑ ( ∆UL1, ∆UL2, ∆UL3)
MAX ( ∆UL1, ∆UL 2, ∆UL3)
EQUATION1621 V2 EN-US (Equation 48)

FaulType =
∑ ( ∆IL1, ∆IL2, ∆IL3)
MAX ( ∆IL1, ∆IL 2, ∆IL3)
EQUATION1622 V2 EN-US (Equation 49)

The value of FaultType for different shunt faults are as follows:

Under ideal conditions: (Patent pending)


Single phase-to-earth; FaultType=1
Phase-to-phase fault FaultType=2
Three-phase fault; FaultType=3

The output signal is 1 for single phase-to-earth fault, 2 for phase-to-phase fault and 3 for
three-phase fault. At this point the filter does not know if earth was involved or not.

Typically there are induced harmonics in the non-faulted lines that will affect the result. This
method allows for a significant tolerance in the evaluation of FaultType over its entire range.

When a single phase-to-earth fault has been detected, the logic determines the largest
quantity, and asserts that phase. If phase-to-phase fault is detected, the two largest phase
quantities will be detected and asserted as outputs.

The faults detected by the delta based phase selector are coordinated in a separate block.
Different phases of faults may be detected at slightly different times due to differences in the
angles of incidence of fault on the wave shape. Therefore the output is forced to wait a certain
time by means of a timer. If the timer expires, and a fault is detected in one phase only, the
fault is deemed as phase-to-earth. This way a premature single phase-to-earth fault detection
is not released for a phase-to-phase fault. If, however, earth current is detected before the
timer expires, the phase-to-earth fault is released sooner.

If another phase picks up during the time delay, the wait time is reduced by a certain amount.
Each detection of either phase-to-earth or additional phases further reduce the initial time
delay and allow the delta phase selector output to be faster. There is no time delay if all three
phases are faulty.

The delta function is released if the input DELTAREL is activated at the same time as input
DELTABLK is not activated. Activating the DELTABLK input blocks the delta function. The
release signal has an internal pulse timer of 100 ms. When the DELTAREL signal has
disappeared the delta logic is reset. In order not to get too abrupt change, the reset is decayed
in pre-defined steps.

264 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Symmetrical component based phase selector SEMOD153832-58 v3


The symmetrical component phase selector uses preprocessed calculated sequence voltages
and currents as inputs. It also uses sampled values of the phase currents. All the symmetrical
quantities mentioned further in this section are with reference to phase L1.

The function is made up of four main parts:

A Detection of the presence of earth fault


B A phase-to-phase logic block based on U1/U2 angle relationship

C A phase-to-earth component based on patent US5390067 where the angle relationships


between U2/I0 and U2/U1 is evaluated to determine earth fault or phase- to-phase to earth
fault
D Logic for detection of three-phase fault

Presence of earth-fault detection SEMOD153832-70 v8


This detection of earth fault is performed in two levels, first by evaluation of the magnitude of
zero sequence current, and secondly by the evaluation of the zero and negative sequence
voltage. It is a complement to the earth-fault signal built-in in the Symmetrical component
based phase selector.

The complementary based zero-sequence current function evaluates the presence of earth
fault by calculating the 3I0 and comparing the result with the setting parameter INRelPE. The
output signal is used to release the earth-fault loop. It is a complement to the earth-fault
signal built-in in the sequence based phase selector. The condition for releasing the phase-to-
earth loop is as follows:

The output from this detection is used to release the earth-fault loop.

|3I0|>maxIph × INRelPE

where:
|3I0| is the magnitude of the zero sequence current 3I0

maxIph is the maximum magnitude of the phase currents


INRelPE is a setting parameter for the relation between the magnitude of 3I0 and the
maximum phase current

The earth-fault loop is also released if the evaluation of the zero sequence current by the main
sequence function meets the following conditions:

|3I0|>IBase × 0.5

|3I0|>maxIph ×INRelPE

where:
maxIph is the maximal current magnitude found in any of the three phases
INRelPE is the setting of 3I0 limit for release of phase-to-earth measuring loop in % of
IBase
IBase is the global setting of the base current (A)

In systems where the source impedance for zero sequence is high the change of zero sequence
current may not be significant and the above detection may fail. In those cases the detection

Line distance protection REL670 265


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

enters the second level, with evaluation of zero and negative sequence voltage. The release of
the earth-fault loops can then be achieved if all of the following conditions are fulfilled:

|3U0|>|U2| × 0.5

|3U0|>|U1| × 0.2

|U1|> UBase × 0.2/√(3)

and

3I0<0.1 × IBase

or

3I0<maxIph × INRelPE

where:
3U0 is the magnitude of the zero sequence voltage

U2 is the magnitude of the negative sequence voltage at the relay measuring point

k5 is design parameter
ILmax is the maximal phase current
IMinOp is the setting of minimum operate phase current in % of IBase

Phase-to-phase fault detection SEMOD153832-119 v2


The detection of phase-to-phase fault is performed by evaluation of the angle difference
between the sequence voltages U2 and U1.

IEC06000383-2-en.vsd
IEC06000383 V2 EN-US

Figure 128: Definition of fault sectors for phase-to-phase fault


The phase-to-phase loop for the faulty phases will be determined if the angle between the
sequence voltages U2 and U1 lies within the sector defined according to figure 128 and the
following conditions are fulfilled:

|U1|>U1MinOP

|U2|>U2MinOp

where:
U1MinOP and are the setting parameters for positive sequence and negative
U2MinOp sequence minimum operate voltages

266 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

The positive sequence voltage U1L1 in figure 128 above is reference.

If there is a three-phase fault, there will not be any release of the individual phase signals, even
if the general conditions for U2 and U1 are fulfilled.

Phase-to-earth and phase-to-phase-to-earth-fault detection SEMOD153832-135 v5


The detection of phase-to-earth and phase-to-phase-to-earth fault (US patent 5390067) is
based on two conditions:

1. Angle relationship between U2 and I0

2. Angle relationship between U2 and U1

The condition 1 determines faulty phase at single phase-to-earth fault by evaluating the
argument between U2 and I0.

80°

L2-E sector L3-E sector


U2L1
(Ref)

200°
L1-E sector
320°

IEC06000384_2_en.vsd
IEC06000384 V3 EN-US

Figure 129: Condition 1: Definition of faulty phase sector as angle between U2 and I0
The angle is calculated in a directional function block and gives the angle in radians as input to
the U2 and I0 function block. The input angle is released only if the fault is in forward direction.
This is done by the directional element. The fault is classified as forward direction if the angle
between U0 and I0 lies between 20 to 200 degrees, see figure 130.

Forward 20°

200° Reverse

en06000385.vsd

IEC06000385 V1 EN-US

Figure 130: Directional element used to release the measured angle between Uo and I0

Line distance protection REL670 267


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

The input radians are summarized with an offset angle and the result evaluated. If the angle is
within the boundaries for a specific sector, the phase indication for that sector will be active
see figure 129. Only one sector signal is allowed to be activated at the same time.

The sector function for condition 1 has an internal release signal which is active if the main
sequence function has classified the angle between U0 and I0 as valid. The following conditions
must be fulfilled for activating the release signals:

|U2|>U2MinOp

|3I0|> 0.05 · IBase

|3I0|>maxIph · INRelPE

where:
U2 and IN are the magnitude of the negative sequence voltage and zero-
sequence current (3I0)

U2MinOp is the setting parameter for minimum operating negative


sequence voltage
maxIph is the maximum phase current
INRelPE is the setting parameter for 3I0 limit for releasing phase-to-earth
loop

The angle difference is phase shifted by 180 degrees if the fault is in reverse direction.

The condition 2 looks at the angle relationship between the negative sequence voltage U2 and
the positive sequence voltage U1. Since this is a phase-to-phase voltage relationship, there is
no need for shifting phases if the fault is in reverse direction. A phase shift is introduced so
that the fault sectors will have the same angle boarders as for condition 1. If the calculated
angle between U2 and U1 lies within one sector, the corresponding phase for that sector will be
activated. The condition 2 is released if both the following conditions are fulfilled:

|U2|>U2MinOp

|U1|>U1MinOP

where:
|U1| and |U2| are the magnitude of the positive and negative sequence voltages.

U1MinOP and U2MinOp are the setting parameters for positive sequence and negative sequence
minimum operating voltages.

268 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

140°
L3-E sector
20°

U1L1
(Ref)
L1-E sector
L2-E sector

260° IEC06000413_2_en.vsd
IEC06000413 V2 EN-US

Figure 131: Condition 2: U2 and U1 angle relationship


If both conditions are true and there is sector match, the fault is deemed as single phase-to-
earth. If the sectors, however, do not match the fault is determined to be the complement of
the second condition, that is, a phase-to-phase-to- earth fault.

Condition 1 and Condition 2 ⇒ Fault type


L3-E L3-E L3-E
L2-E L1-E L2-L3-E

The sequence phase selector is blocked when earth is not involved or if a three-phase fault is
detected.

Three-phase fault detection SEMOD153832-174 v4


Unless it has been categorized as a single or two-phase fault, the function classifies it as a
three-phase fault if the following conditions are fulfilled:

|U1|<U1Level

and

|I1|>I1LowLevel

or

|I1|>IMaxLoad

where:
|U1| and |I1| are the positive sequence voltage and current magnitude

U1Level , are the setting of limits for positive sequence voltage and current
I1LowLevel
IMaxLoad is the setting of the maximum load current

The output signal for detection of three-phase fault is only released if not earth fault and
phase-to-phase fault in the main sequence function is detected.

The conditions for not detecting earth fault are the inverse of equation 5 to 10.

Line distance protection REL670 269


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

The condition for not detecting phase-to-phase faults is determined by three conditions. Each
of them gives condition for not detecting phase-to-phase fault. Those are:

1:
earth fault is detected
or
|3I0|> 0.05 · IBase

and
|3I0|>maxIph ·INRelPE

2:
phase-to-earth and phase-to-phase faults are not fulfilled
and
maxIph<0.1 · IBase
and
|I2|<0.1 · maxIph

3:
|3I0|>maxIph · INBlockPP

or
|I2|<maxIph · I2ILmax

where:
maxIph is the maximum of the phase currents IL1, IL2 and IL3
INRelPE is the setting parameter for 3I0 limit for release of phase-to-earth fault
loops
|I2| is the magnitude of the negative sequence current

I2ILmax is the setting parameter for the relation between negative sequence
current to the maximum phase current in percent of IBase
INBlockPP is the setting parameter for 3I0 limit for blocking phase to phase
measuring loops

Fault evaluation and selection logic SEMOD153832-307 v3


The phase selection logic has an evaluation procedure that can be simplified according to
figure 132. Only phase L1 is shown in the figure. If the internal signal 3 Phase fault is activated,
all four outputs START, STL1, STL2 and STL3 gets activated.

270 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

a a>b FaultPriority
DeltaIL1 then c=a c Adaptive release
b else c=b dependent on result
from Delta logic
DeltaUL1

Sequence based
function a<b
a
L1L2 fault
then c=b c
OR b else c=a OR
L1N fault

3 Phase fault

STL1
IL1Valid &

BLOCK

IEC06000386-2-en.vsd
IEC06000386 V2 EN-US

Figure 132: Simplified diagram for fault evaluation, phase L1

Load encroachment logic SEMOD153832-312 v3


Each of the six measuring loops has its own load (encroachment) characteristic based on the
corresponding loop impedance. The load encroachment functionality is always activated in
faulty phase identification with load encroachment for mho (FMPSPDIS) function but the
influence on the zone measurement can be switched On/Offin the respective impedance
measuring function.

The outline of the characteristic is presented in figure 133. As illustrated, the resistive reach in
forward and reverse direction and the angle of the sector is the same in all four quadrants. The
reach for the phase selector will be reduced by the load encroachment function, as shown in
figure 133.

Blinder
Blinder provides a mean to discriminate high load from a fault. The operating characteristic is
illustrated in figure 133. There are six individual measuring loops with the blinder functionality.
Three phase-to-earth loops which estimate the impedance according to

Zn = Uph / Iph

and three phase-to-phase loops according to

Zph-ph = Uph-ph / Iph-ph

The start operations from respective loop are binary coded into one word and provides an
output signal STCNDPLE.

Line distance protection REL670 271


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

X jX

Operation area Operation area

RLd
ArgLd ArgLd
R

ArgLd R
ArgLd
RLd

Operation area

No operation area No operation area

en06000414.vsd
IEC06000414 V1 EN-US

Figure 133: Influence on the characteristic by load encroachment logic

Outputs SEMOD153832-327 v7
The output of the sequence components based phase selector and the delta logic phase
selector activates the output signals STL1, STL2 and STL3. If an earth fault is detected the
signal STPE gets activated.

The phase selector also gives binary coded signals that are connected to the zone measuring
element for opening the correct measuring loop(s). This is done by the signal STCNDPHS. If
only one phase is started (L1, L2 or L3), the corresponding phase-to-earth element is enabled.
STPE is expected to be made available for two-phase and three-phase faults for the correct
output to be selected. The fault loop is indicated by one of the decimal numbers below.

The output STCNDPHS provides release information from the phase selection part only.
STCNDLE provides release information from the load encroachment part only. STCNDPLE
provides release information from the phase selection part and the load encroachment part
combined, that is, both parts have to issue a release at the same time (this signal is normally
not used in the zone measuring element). In these signals, each fault type has an associated
value, which represents the corresponding zone measuring loop to be released. The values are
presented in table 162.

0= no faulted phases
1= L1E
2= L2E
3= L3E
4= -L1L2E
5= -L2L3E
6= -L3L1E
7= -L1L2L3E
8= -L1L2
9= -L2L3
10= -L3L1
11= L1L2L3

272 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

An additional logic is applied to handle the cases when phase-to-earth outputs are to be
asserted when the earth input G is not asserted.

The output signal STCNDPLE is activated when the load encroachment is operating.

STCNDPLE is connected to the input STCND for selected quadrilateral impedance measuring
zones to be blocked. The signal must be connected to the input LDCND for selected mho
impedance measuring zones .

The load encroachment at the measuring zone must be activated to release the
blocking from the load encroachment function.

8.8.7 Technical data


SEMOD153649-2 v8

Table 163: FMPSPDIS technical data


Function Range or value Accuracy
Load encroachment criteria: (1.00–3000.00) W/phase ±2.0% static accuracy
Load resistance, forward and (5–70) degrees Conditions:
reverse Voltage range: (0.1–1.1) x Ur
Current range: (0.5–30) x Ir
Angle: at 0 degrees and 85
degrees

8.9 Distance protection zone, quadrilateral characteristic,


separate settings ZMRPDIS, ZMRAPDIS and ZDRDIR GUID-7308DB86-32CE-4615-95DC-92BEEF69E184 v1

8.9.1 Identification
GUID-420DD49A-C65B-4F04-B317-9558DCCE7A52 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Distance protection zone, ZMRPDIS 21
quadrilateral characteristic, separate
settings (zone 1) Z
S00346 V2 EN-US

Distance protection zone, ZMRAPDIS 21


quadrilateral characteristic, separate
settings (zone 2-5) Z
S00346 V2 EN-US

GUID-119120A5-8600-44C6-9C85-81136DBBE280 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Directional impedance quadrilateral ZDRDIR Z<-> 21D

Line distance protection REL670 273


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

8.9.2 Functionality GUID-014501E7-EE0D-440F-8DC8-C44B848E49D3 v3

The line distance protection is up to five zone full scheme protection with three fault loops for
phase-to-phase faults and three fault loops for phase-to-earth fault for each of the
independent zones. Individual settings for each zone in resistive and reactive reach gives
flexibility for use as back-up protection for transformer connected to overhead lines and
cables of different types and lengths.

Mho alternative quadrilateral characteristic is available.

Distance protection zone, quadrilateral characteristic (ZMRPDIS) together with Phase


selection, quadrilateral characteristic with settable angle (FRPSPDIS) has functionality for load
encroachment, which increases the possibility to detect high resistive faults on heavily loaded
lines, as shown in figure 134.

Forward
operation

Reverse
operation

en05000034.vsd
IEC05000034 V1 EN-US

Figure 134: Typical quadrilateral distance protection zone with Phase selection,
quadrilateral characteristic with settable angle function FRPSPDIS activated
The independent measurement of impedance for each fault loop together with a sensitive and
reliable built-in phase selection makes the function suitable in applications with single pole
tripping and autoreclosing.

Built-in adaptive load compensation algorithm prevents overreaching of zone 1 at load


exporting end at phase-to-earth faults on heavily loaded power lines.

The distance protection zones can operate, independent of each other, in directional (forward
or reverse) or non-directional mode. This makes them suitable, together with different
communication schemes, for the protection of power lines and cables in complex network
configurations, such as parallel lines, multi-terminal lines and so on.

274 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

8.9.3 Function block


GUID-8DF1E00C-8404-4B1C-AE2F-5702269B699A v2

ZMRPDIS
I3P* TRIP
U3P* TRL1
BLOCK TRL2
BLKZ TRL3
BLKTR START
STCND STL1
DIRCND STL2
STL3
STND

IEC08000248-1-en.vsd
IEC08000248 V1 EN-US

Figure 135: ZMRPDIS function block

ZMRAPDIS
I3P* TRIP
U3P* TRL1
BLOCK TRL2
BLKZ TRL3
BLKTR START
STCND STL1
DIRCND STL2
STL3
STND

IEC08000290_1_en.vsd
IEC08000290 V1 EN-US

Figure 136: ZMRAPDIS function block


GUID-3BB8A08A-3199-42E3-B161-B11F4FF8C65F v2

ZDRDIR
I3P* STDIRCND
U3P*
IEC10000007-2-en.vsd

IEC10000007 V2 EN-US

8.9.4 Signals
PID-3649-INPUTSIGNALS v6

Table 164: ZMRPDIS Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKZ BOOLEAN 0 Blocks all output by fuse failure signal
BLKTR BOOLEAN 0 Blocks all trip outputs
STCND INTEGER 0 External start condition (loop enabler)
DIRCND INTEGER 0 External directional condition

Line distance protection REL670 275


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

PID-3649-OUTPUTSIGNALS v6

Table 165: ZMRPDIS Output signals


Name Type Description
TRIP BOOLEAN General Trip, issued from any phase or loop
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
START BOOLEAN General Start, issued from any phase or loop
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3
STND BOOLEAN Non-directional start, issued from any phase or loop

PID-3648-INPUTSIGNALS v6

Table 166: ZMRAPDIS Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKZ BOOLEAN 0 Blocks all output by fuse failure signal
BLKTR BOOLEAN 0 Blocks all trip outputs
STCND INTEGER 0 External start condition (loop enabler)
DIRCND INTEGER 0 External directional condition

PID-3648-OUTPUTSIGNALS v6

Table 167: ZMRAPDIS Output signals


Name Type Description
TRIP BOOLEAN General Trip, issued from any phase or loop
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
START BOOLEAN General Start, issued from any phase or loop
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3
STND BOOLEAN Non-directional start, issued from any phase or loop

276 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

PID-726-INPUTSIGNALS v3

Table 168: ZDRDIR Input signals


Name Type Default Description
I3P GROUP - group connection for current abs 2
SIGNAL
U3P GROUP - group connection for voltage abs 2
SIGNAL

PID-726-OUTPUTSIGNALS v3

Table 169: ZDRDIR Output signals


Name Type Description
STDIRCND INTEGER Binary coded directional information per measuring loop

8.9.5 Settings
PID-3649-SETTINGS v6

Table 170: ZMRPDIS Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
OperationDir Non-directional - - Forward Operation mode of directionality
Forward NonDir / Forw / Rev
Reverse
X1PP 0.10 - 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach Ph-
Ph
R1PP 0.01 - 1000.00 Ohm/p 0.01 5.00 Positive seq. resistance for
characteristic angle, Ph-Ph
X1PE 0.10 - 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach Ph-
E
R1PE 0.01 - 1000.00 Ohm/p 0.01 5.00 Positive seq. resistance for
characteristic angle, Ph-E
RFPP 0.10 - 3000.00 Ohm/l 0.01 30.00 Fault resistance reach in ohm/loop,
Ph-Ph
X0PE 0.10 - 9000.00 Ohm/p 0.01 100.00 Zero sequence reactance reach, Ph-E
RFPE 0.10 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach in ohm/loop,
Ph-E
R0PE 0.01 - 3000.00 Ohm/p 0.01 15.00 Zero seq. resistance for zone
characteristic angle, Ph-E
OperationPP Off - - On Operation mode Off / On of Phase-
On Phase loops
OpModetPP Off - - On Operation mode Off / On of Zone
On timer, Ph-Ph
tPP 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-Ph
OperationPE Off - - On Operation mode Off / On of Phase-
On Earth loops
OpModetPE Off - - On Operation mode Off / On of Zone
On timer, Ph-E
tPE 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-E
Table continues on next page

Line distance protection REL670 277


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Name Values (Range) Unit Step Default Description


IMinOpPP 10 - 1000 %IB 1 20 Minimum operate delta current for
Phase-Phase loops
IMinOpPE 10 - 1000 %IB 1 20 Minimum operate phase current for
Phase-Earth loops
IMinOpIN 5 - 1000 %IB 1 5 Minimum operate residual current for
Phase-Earth loops

Table 171: ZMRPDIS Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

PID-3648-SETTINGS v6

Table 172: ZMRAPDIS Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
OperationDir Non-directional - - Forward Operation mode of directionality
Forward NonDir / Forw / Rev
Reverse
X1PP 0.10 - 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach Ph-
Ph
R1PP 0.01 - 1000.00 Ohm/p 0.01 5.00 Positive seq. resistance for
characteristic angle, Ph-Ph
X1PE 0.10 - 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach Ph-
E
R1PE 0.01 - 1000.00 Ohm/p 0.01 5.00 Positive seq. resistance for
characteristic angle, Ph-E
RFPP 0.10 - 3000.00 Ohm/l 0.01 30.00 Fault resistance reach in ohm/loop,
Ph-Ph
X0PE 0.10 - 9000.00 Ohm/p 0.01 100.00 Zero sequence reactance reach, Ph-E
RFPE 0.10 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach in ohm/loop,
Ph-E
R0PE 0.01 - 3000.00 Ohm/p 0.01 15.00 Zero seq. resistance for zone
characteristic angle, Ph-E
OperationPP Off - - On Operation mode Off / On of Phase-
On Phase loops
OpModetPP Off - - On Operation mode Off / On of Zone
On timer, Ph-Ph
tPP 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-Ph
OperationPE Off - - On Operation mode Off / On of Phase-
On Earth loops
OpModetPE Off - - On Operation mode Off / On of Zone
On timer, Ph-E
tPE 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-E
IMinOpPP 10 - 1000 %IB 1 20 Minimum operate delta current for
Phase-Phase loops
IMinOpPE 10 - 1000 %IB 1 20 Minimum operate phase current for
Phase-Earth loops

278 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Table 173: ZMRAPDIS Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

PID-3545-SETTINGS v6

Table 174: ZDRDIR Group settings (basic)


Name Values (Range) Unit Step Default Description
IMinOpPP 5 - 30 %IB 1 10 Minimum operate phase-phase
current for Phase-Phase loops
IMinOpPE 5 - 30 %IB 1 5 Minimum operate phase current for
Phase-Earth loops
ArgNegRes 90 - 175 Deg 1 115 Angle of blinder in second quadrant
for forward direction
ArgDir 5 - 45 Deg 1 15 Angle of blinder in fourth quadrant for
forward direction

Table 175: ZDRDIR Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

8.9.6 Operation principle

8.9.6.1 Full scheme measurement GUID-4519D9AD-4446-48FC-86CC-140E5299AFB7 v1

The execution of the different fault loops within the IED are of full scheme type, which means
that each fault loop for phase-to-earth faults and phase-to-phase faults for forward and
reverse faults are executed in parallel.

Figure 137 presents an outline of the different measuring loops for up to five, impedance-
measuring zones. There are 3 to 5 zones depending on product type and variant.

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 1

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 2

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 3

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 4

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 5

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1


Zone RV

IEC05000458-2-en.vsd
IEC05000458 V2 EN-US

Figure 137: The different measuring loops at phase-to-earth fault and phase-to-phase
fault.

Line distance protection REL670 279


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

The use of full scheme technique gives faster operation time compared to switched schemes
which mostly uses a start element to select correct voltages and current depending on fault
type. Each distance protection zone performs like one independent distance protection IED
with six measuring elements.

8.9.6.2 Impedance characteristic GUID-0DC94F08-9B3A-424D-9615-BD5C577344ED v1

The distance measuring zone includes six impedance measuring loops; three intended for
phase-to-earth faults, and three intended for phase-to-phase as well as, three-phase faults.

The distance measuring zone will essentially operate according to the non-directional
impedance characteristics presented in figure 138 and figure 139. The phase-to-earth
characteristic is illustrated with the full loop reach while the phase-to-phase characteristic
presents the per phase reach.

X (Ohm/loop)

R1PE+Rn

RFPE RFPE

X0PE-X1PE
Xn =
3
X1PE+Xn R0PE-R1PE
Rn =
3
jN jN
R (Ohm/loop)

RFPE RFPE

X1PE+Xn

RFPE RFPE
en08000280-2-en.vsd

R1PE+Rn
IEC08000280 V1 EN-US

Figure 138: Characteristic for phase-to-earth measuring , ohm/loop domain

280 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

X (Ohm/phase)

RFPP R1PP RFPP


2 2
X 0 PE - X 1RVPE
XNRV =XX00PEPG- -
X31XRVPE
1RVPG
XNRV =
XNRV =
3 3
XX
X00
PE
0 PE
-X
PG --1X 11FWPE
XFWPE
FWPG
XNFW =
XNFW==
XNFW
X1PP 3
3 3

j j
R (Ohm/phase)

RFPP RFPP
2 2

X1PP

RFPP R1PP RFPP


2 2
en07000062.vsd
IEC07000062 V2 EN-US

Figure 139: Characteristic for phase-to-phase measuring


The fault loop reach with respect to each fault type may also be presented as in figure 140.
Note in particular the difference in definition regarding the (fault) resistive reach for phase-to-
phase faults and three-phase faults.

Line distance protection REL670 281


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

IL1 R1 + j X1
Phase-to-earth
UL1
element

Phase-to-earth
fault in phase L1 RFPE
(Arc + tower
resistance)

0
IN (R0-R1)/3 +
j (X0-X1)/3 )

IL1 R1 + j X1 Phase-to-phase
UL1 element L1-L2
Phase-to-phase
fault in phase RFPP
L1-L2 IL2
UL2 (Arc resistance)
R1 + j X1

IL1 R1 + j X1 0.5·RFPP Phase-to-phase


UL1 element L1-L3
Three-phase
fault
IL3
UL3
R1 + j X1 0.5·RFPP
IEC08000282-2-en.vsd
IEC08000282 V2 EN-US

Figure 140: Fault loop model


The R1 and jX1 in figure 140 represents the positive sequence impedance from the measuring
point to the fault location. The settings RFPE and RFPP are the eventual fault resistances in the
faulty place.

Regarding the illustration of three-phase fault in figure 140, there is of course fault current
flowing also in the third phase during a three-phase fault. The illustration merely reflects the
loop measurement, which is made phase-to-phase.

The zone can be set to operate in Non-directional, Forward or Reverse direction through the
setting OperationDir. The result from respective set value is illustrated in figure 141. The
impedance reach is symmetric, in the sense that it conforms for forward and reverse direction.
Therefore, all reach settings apply to both directions.

282 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

X X X

R R R

Non-directional Forward Reverse

IEC05000182-2-en.vsdx

IEC05000182 V2 EN-US

Figure 141: Directional operating modes of the distance measuring zones

8.9.6.3 Minimum operating current GUID-BFD07CBE-F322-4602-A3BC-B6E8D72DB92B v1

The operation of Distance measuring zones, quadrilateral characteristic (ZMRPDIS) is blocked


if the magnitude of input currents fall below certain threshold values.

The phase-to-earth loop Ln is blocked if ILn < IMinOpPE.

For zone 1 with load compensation feature the additional criterion applies, that all phase-to-
earth loops can be blocked when IN < IMinOpIN, regardless of the phase currents.

ILn is the RMS value of the current in phase Ln. IN is the RMS value of the vector sum of the
three-phase currents, that is residual current 3I0.

The phase-to-phase loop LmLn is blocked if ILmLn< IMinOpPP.

ILmLn is the RMS value of the vector difference between phase currents Lm and Ln.

All three current limits IMinOpPE, IMinOpIN and IMinOpPP are automatically
reduced to 75% of regular set values if the zone is set to operate in reverse
direction, that is OperationDir=Reverse

8.9.6.4 Measuring principles M16923-4 v7

Fault loop equations use the complex values of voltage, current, and changes in the current.
Apparent impedances are calculated and compared with the set limits. The apparent
impedances at phase-to-phase faults follow equation 50 (example for a phase L1 to phase L2
fault).

UL1 – UL2
Zapp = -------------------------
I L1 – IL2
EQUATION1222 V1 EN-US (Equation 50)

Line distance protection REL670 283


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Here U and I represent the corresponding voltage and current phasors in the respective phase
Ln (n = 1, 2, 3)

The earth return compensation applies in a conventional manner to phase-to-earth faults


(example for a phase L1 to earth fault) according to equation 51.

U L1
Z app =
I L1 + I N × KN
EQUATION1223 V2 EN-US (Equation 51)

Where:
are the phase voltage, phase current and residual current present to the IED
U L1
I L1
IN

KN
is defined as:

Z 0 - Z1
KN =
3 × Z1
EQUATION-2105 V2 EN-US

Z 0 = R 0 + jX 0
EQUATION2106 V2 EN-US

Z 1 = R1 + jX 1
EQUATION2107 V2 EN-US

Where
R0 is setting of the resistive zero sequence reach
X0 is setting of the reactive zero sequence reach
R1 is setting of the resistive positive sequence reach
X1 is setting of the reactive positive sequence reach

Here IN is a phasor of the residual current in IED point. This results in the same reach along the
line for all types of faults.

The apparent impedance is considered as an impedance loop with resistance R and reactance
X.

The formula given in equation 51 is only valid for radial feeder application without load. When
load is considered in the case of single phase-to-earth fault, conventional distance protection
might overreach at exporting end and underreach at importing end. The IED has an adaptive
load compensation which increases the security in such applications.

Measuring elements receive current and voltage information from the A/D converter. The
check sums are calculated and compared, and the information is distributed into memory
locations. For each of the six supervised fault loops, sampled values of voltage (U), current (I),

284 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

and changes in current between samples (DI) are brought from the input memory and fed to a
recursive Fourier filter.

The filter provides two orthogonal values for each input. These values are related to the loop
impedance according to equation 52,

X Di
U = R × i + ------ × -----
w 0 Dt
EQUATION1224 V1 EN-US (Equation 52)

in complex notation, or:

X D Re ( I )
Re ( U ) = R × Re ( I ) + ------ × ------------------
w0 Dt

EQUATION354 V1 EN-US (Equation 53)

X DIm ( I )
Im ( U ) = R × Im ( I ) + ------ × -----------------
w0 Dt

EQUATION355 V1 EN-US (Equation 54)

with

w0 = 2 × p × f 0
EQUATION356 V1 EN-US (Equation 55)

where:
Re designates the real component of current and voltage,
Im designates the imaginary component of current and voltage and
f0 designates the rated system frequency

The algorithm calculates Rm measured resistance from the equation for the real value of the
voltage and substitutes it in the equation for the imaginary part. The equation for the Xm
measured reactance can then be solved. The final result is equal to:

Im ( U ) × DRe ( I ) – Re ( U ) × D Im ( I )
R m = ------------------------------------------------------------------------------------
DRe ( I ) × Im ( I ) – D Im ( I ) × Re ( I )
EQUATION357 V1 EN-US (Equation 56)

Re ( U ) × Im ( I ) – Im ( U ) × Re ( I )
Xm = w 0 × Dt × -------------------------------------------------------------------------------
DRe ( I ) × Im ( I ) – DIm ( I ) × Re ( I )
EQUATION358 V1 EN-US (Equation 57)

The calculated Rm and Xm values are updated each sample and compared with the set zone
reach. The adaptive tripping counter counts the number of permissive tripping results. This
effectively removes any influence of errors introduced by the capacitive voltage transformers
or by other factors.

The directional evaluations are performed simultaneously in both forward and reverse
directions, and in all six fault loops. Positive sequence voltage and a phase locked positive

Line distance protection REL670 285


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

sequence memory voltage are used as a reference. This ensures unlimited directional
sensitivity for faults close to the IED point.

8.9.6.5 Directional impedance element for quadrilateral characteristics M16923-139 v6

The evaluation of the directionality takes place in Directional impedance quadrilateral function
ZDRDIR. Equation 58 and equation 59 are used to classify that the fault is in forward direction
for phase-to-earth fault and phase-to-phase fault.

0.8 × U 1L1 + 0.2 × U 1L1 M


- ArgDir < arg < ArgNeg Re s
I L1
EQUATION725 V2 EN-US (Equation 58)

For the L1-L2 element, the equation in forward direction is according to.

0.8 × U 1L1 L 2 + 0.2 × U 1L1 L 2 M


- ArgDir < arg < ArgNeg Re s
I L1 L 2
EQUATION726 V2 EN-US (Equation 59)

where:
ArgDir is the setting for the lower boundary of the forward directional characteristic, by default set to
15 (= -15 degrees) and
ArgNegRes is the setting for the upper boundary of the forward directional characteristic, by default set to
115 degrees, see figure 142.
is positive sequence phase voltage in phase L1
U 1L1
is positive sequence memorized phase voltage in phase L1
U 1L1M
is phase current in phase L1
I L1
is voltage difference between phase L1 and L2 (L2 lagging L1)
U 1L1L 2
is memorized voltage difference between phase L1 and L2 (L2 lagging L1)
U 1L1L 2 M
is current difference between phase L1 and L2 (L2 lagging L1)
I L1L 2

The setting of ArgDir and ArgNegRes is by default set to 15 (= -15) and 115 degrees respectively
(as shown in figure 142). It should not be changed unless system studies have shown the
necessity.

ZDRDIR gives binary coded directional information per measuring loop on the output
STDIRCND.

STDIR= STFWL1*1+STFWL2*2+STFWL3*4+STFWL1L2*8+
+STFWL2L3*16+STFWL3L1*32+STRVL1*64+STRVL2*128+
+STRVL3*256+STRVL1L2*512+STRVL2L3*1024+STRVL3L1*2048

286 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

ArgNegRes

ArgDir
R

en05000722.vsd
IEC05000722 V1 EN-US

Figure 142: Setting angles for discrimination of forward and reverse fault in Directional
impedance quadrilateral function ZDRDIR

The reverse directional characteristic is equal to the forward characteristic rotated by 180
degrees.

The polarizing voltage is available as long as the positive sequence voltage exceeds 5% of the
set base voltage UBase. So the directional element can use it for all unsymmetrical faults
including close-in faults.

For close-in three-phase faults, the U1L1M memory voltage, based on the same positive
sequence voltage, ensures correct directional discrimination.

The memory voltage is used for 100 ms or until the positive sequence voltage is restored.

After 100 ms the following occurs:

• If the current is still above the set value of the minimum operating current (between 10
and 30% of the set IED rated current IBase), the condition seals in.
• If the fault has caused tripping, the trip endures.
• If the fault was detected in the reverse direction, the measuring element in the
reverse direction remains in operation.
• If the current decreases below the minimum operating value, the memory resets until the
positive sequence voltage exceeds 10% of its rated value.

8.9.6.6 Simplified logic diagrams M13841-35 v2

Distance protection zones GUID-CBBD5D22-7372-4C0A-B941-44A5D21EC328 v2


The design of the distance protection zones are presented for all measuring loops: phase-to-
earth as well as phase-to-phase.

Phase-to-earth related signals are designated by L1N, L2N and L3N.. The phase-to-phase
signals are designated by L1L2, L2L3, and L3L1.

Line distance protection REL670 287


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Fulfillment of two different measuring conditions is necessary to obtain the one logical signal
for each separate measuring loop:

• Zone measuring condition, which follows the operating equations described above.
• Group functional input signal (STCND), as presented in figure 59.

The STCND input signal represents a connection of six different integer values from Phase
selection with load encroachment, quadrilateral characteristic function FRPSPDIS within the
IED, which are converted within the zone measuring function into corresponding boolean
expressions for each condition separately. Input signal STCND is connected to
FRPSPDISfunction output STCNDZ.

The input signal DIRCND is used to give condition for directionality for the distance measuring
zones. The signal contains binary coded information for both forward and reverse direction.
The zone measurement function filter out the relevant signals depending on the setting of the
parameter OperationDir. It must be configured to the STDIRCND output on directional
function ZDRDIR function.

STZMPP
OR
STCND

AND STNDL1L2
L1L2

STNDL2L3
L2L3 AND

L3L1 AND STNDL3L1

AND STNDL1N
L1N

AND STNDL2N
L2N

STNDL3N
L3N AND

OR STPE

OR
VTSZ STND
OR AND
BLOCK
BLOCFUNC BLK

99000557-2.vsd
IEC99000557-TIFF V3 EN-US

Figure 143: Conditioning by a group functional input signal STCND, external start
condition
Composition of the phase start signals for a case, when the zone operates in a non-directional
mode, is presented in figure 60.

288 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

STNDL1N
OR
STNDL2N 15 ms
AND t STL1
STNDL3N
STNDL1L2 OR 15 ms
AND t STL2
STNDL2L3
15 ms
STNDL3L1 AND t STL3
OR
15 ms
AND t START
OR

BLK

IEC09000889-1-en.vsd
IEC09000889 V1 EN-US

Figure 144: Composition of starting signals in non-directional operating mode


Results of the directional measurement enter the logic circuits, when the zone operates in
directional (forward or reverse) mode, as shown in figure 61.

STNDL1N
AND
DIRL1N
STZMPE.
OR
STNDL2N
DIRL2N AND

STNDL3N 15 ms
OR STL1
AND AND t
DIRL3N

STNDL1L2
DIRL1L2 AND 15 ms
OR STL2
AND t
STNDL2L3
DIRL2L3 AND
15 ms
OR STL3
STNDL3L1 AND t
DIRL3L1 AND

STZMPP
OR

BLK

15 ms
OR START
AND t

IEC09000888-2-en.vsd
IEC09000888 V2 EN-US

Figure 145: Composition of start signals in directional operating mode


Tripping conditions for the distance protection zone one are symbolically presented in figure
62.

Line distance protection REL670 289


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Timer tPP=On
STZMPP AND tPP
AND
t

BLOCFUNC
OR OR
tPE
t
AND
Timer tPE=On AND
STZMPE 15ms
BLKTR AND t
TRIP
BLK OR

STL1 AND TRL1

STL2 AND TRL2

STL3 AND TRL3

IEC09000887-3-en.vsdx

IEC09000887 V3 EN-US

Figure 146: Tripping logic for the distance protection zone

8.9.7 Technical data


GUID-7617A215-AE7C-47CC-B189-4914F530F717 v7

Table 176: ZMRPDIS, ZMRAPDIS technical data


Function Range or value Accuracy
Number of zones Max 5 with -
selectable direction
Minimum operate residual (5-1000)% of IBase -
current, zone 1
Minimum operate current, (10-1000)% of IBase -
phase-to-phase and phase-to-
earth
Positive sequence reactance (0.10-3000.00) Ω/ ±2.0% static accuracy
phase ±2.0 degrees static angular accuracy
Conditions:
Positive sequence resistance (0.01-1000.00) Ω/ Voltage range: (0.1-1.1) x Ur
phase
Current range: (0.5-30) x Ir
Zero sequence reactance (0.10-9000.00) Ω/ Angle: at 0 degrees and 85 degrees
phase
Zero sequence resistance (0.01-3000.00) Ω/
phase
Fault resistance, phase-to- (0.10-9000.00) Ω/
earth loop
Fault resistance, phase-to- (0.10-3000.00) Ω/
phase loop
Table continues on next page

290 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Function Range or value Accuracy


Dynamic overreach <5% at 85 degrees -
measured with
CVT’s and
0.5<SIR<30
Definite time delay phase- (0.000-60.000) s ±0.2% or ±40 ms whichever is greater
phase and phase-earth
operation
Operate time 25 ms typically IEC 60255-121
Reset ratio 105% typically -
Reset time at 0.1 x Zreach to 2 Min. = 20 ms -
x Zreach Max. =50 ms

8.10 Phase selection, quadrilateral characteristic with


settable angle FRPSPDIS GUID-29E9C424-5AF7-40EE-89D9-F6BB4F0A0836 v2

8.10.1 Identification
GUID-07DB9506-656C-4E5F-A043-3DAA624313C7 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Phase selection, quadrilateral FRPSPDIS 21
characteristic with settable angle
Z<phs

SYMBOL-DD V1 EN-US

8.10.2 Functionality GUID-A15350C8-CFA9-4BD9-9DE1-5D5814290F61 v3

The ability to accurately and reliably classify the different types of fault, so that single pole
tripping and autoreclosing can be used plays an important role in today's power systems.
Phase selection, quadrilateral characteristic with settable angle FRPSPDIS is designed to
accurately select the proper fault loop in the distance function dependent on the fault type.

The heavy load transfer that is common in many transmission networks may make fault
resistance coverage difficult to achieve. Therefore, FRPSPDIS has a built-in algorithm for load
encroachment, which gives the possibility to enlarge the resistive setting of both the phase
selection and the measuring zones without interfering with the load.

The extensive output signals from the phase selection gives also important information about
faulty phase(s) which can be used for fault analysis.

A current-based phase selection is also included. The measuring elements continuously


measure three phase currents and the residual current and, compare them with the set values.

Line distance protection REL670 291


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

8.10.3 Function block GUID-4AE8EAC6-5231-4646-9215-33DBBA039B65 v2

FRPSPDIS
I3P* TRIP
U3P* START
BLOCK STFWL1
DIRCND STFWL2
STFWL3
STFWPE
STRVL1
STRVL2
STRVL3
STRVPE
STNDL1
STNDL2
STNDL3
STNDPE
STFW1PH
STFW2PH
STFW3PH
STPE
STPP
STCNDZ
STCNDLE

IEC08000430-2-en.vsd
IEC08000430 V2 EN-US

Figure 147: FRPSPDIS function block

8.10.4 Signals
PID-3643-INPUTSIGNALS v7

Table 177: FRPSPDIS Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
DIRCND INTEGER 0 External directional condition

PID-3643-OUTPUTSIGNALS v7

Table 178: FRPSPDIS Output signals


Name Type Description
TRIP BOOLEAN Trip output
START BOOLEAN Start in any phase or loop
STFWL1 BOOLEAN Fault detected in phase L1 - forward direction
STFWL2 BOOLEAN Fault detected in phase L2 - forward direction
STFWL3 BOOLEAN Fault detected in phase L3 - forward direction
STFWPE BOOLEAN Earth fault detected in forward direction
STRVL1 BOOLEAN Fault detected in phase L1 - reverse direction
STRVL2 BOOLEAN Fault detected in phase L2 - reverse direction
STRVL3 BOOLEAN Fault detected in phase L3 - reverse direction
STRVPE BOOLEAN Earth fault detected in reverse direction
STNDL1 BOOLEAN Non directional start in L1
STNDL2 BOOLEAN Non directional start in L2
Table continues on next page

292 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Name Type Description


STNDL3 BOOLEAN Non directional start in L3
STNDPE BOOLEAN Non directional start, phase-earth
STFW1PH BOOLEAN Start in forward direction for single-phase fault
STFW2PH BOOLEAN Start in forward direction for two- phase fault
STFW3PH BOOLEAN Start in forward direction for thre-phase fault
STPE BOOLEAN Current conditions release of phase-earth measuring
elements
STPP BOOLEAN Current conditions release of phase-phase measuring
elements
STCNDZ INTEGER Start condition (Z< with LE and 3I0 E/F detection)
STCNDLE INTEGER Start condition (only LE and 3I0 E/F detection)

8.10.5 Settings
PID-3643-SETTINGS v7

Table 179: FRPSPDIS Group settings (basic)


Name Values (Range) Unit Step Default Description
INBlockPP 10 - 100 %IPh 1 40 3I0 limit for blocking phase-to-phase
measuring loops
INReleasePE 10 - 100 %IPh 1 20 3I0 limit for releasing phase-to-earth
measuring loops
RLdFw 1.00 - 3000.00 Ohm/p 0.01 80.00 Forward resistive reach within the
load impedance area
RLdRv 1.00 - 3000.00 Ohm/p 0.01 80.00 Reverse resistive reach within the load
impedance area
ArgLd 5 - 70 Deg 1 30 Load angle determining the load
impedance area
X1 0.50 - 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach
R1PP 0.10 - 1000.00 Ohm/p 0.01 15.00 Positive seq. resistance for
characteristic angle, Ph-Ph
R1PE 0.10 - 1000.00 Ohm/p 0.01 1.50 Positive seq. resistance for
characteristic angle, Ph-E
X0 0.50 - 9000.00 Ohm/p 0.01 120.00 Zero sequence reactance reach
R0PE 0.50 - 3000.00 Ohm/p 0.01 5.00 Zero seq. resistance for zone
characteristic angle, Ph-E
RFFwPP 0.50 - 3000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, forward
RFRvPP 0.50 - 3000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, reverse
RFFwPE 1.00 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-E, forward
RFRvPE 1.00 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-E, reverse
IMinOpPP 5 - 500 %IB 1 10 Minimum operate delta current for
Phase-Phase loops
IMinOpPE 5 - 500 %IB 1 5 Minimum operate phase current for
Phase-Earth loops

Line distance protection REL670 293


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Table 180: FRPSPDIS Group settings (advanced)


Name Values (Range) Unit Step Default Description
TimerPP Off - - Off Operation mode Off / On of Zone
On timer, Ph-Ph
tPP 0.000 - 60.000 s 0.001 3.000 Time delay to trip, Ph-Ph
TimerPE Off - - Off Operation mode Off / On of Zone
On timer, Ph-E
tPE 0.000 - 60.000 s 0.001 3.000 Time delay to trip, Ph-E

Table 181: FRPSPDIS Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

8.10.6 Operation principle GUID-163B55DE-056F-4CB9-A401-78F9F4897903 v2

The basic impedance algorithm for the operation of the phase selection measuring elements is
the same as for the distance zone measuring function. Phase selection, quadrilateral
characteristic with settable angle (FRPSPDIS) includes six impedance measuring loops; three
intended for phase-to-earth faults, and three intended for phase-to-phase as well as for three-
phase faults.

The difference, compared to the distance zone measuring function, is in the combination of
the measuring quantities (currents and voltages) for different types of faults.

The characteristic is basically non-directional, but FRPSPDIS uses information from the
directional function ZDRDIR to discriminate whether the fault is in forward or reverse
direction.

The start condition STCNDZ is essentially based on the following criteria:

• Residual current criteria, that is, separation of faults with and without earth connection
• Regular quadrilateral impedance characteristic
• Load encroachment characteristics is always active but can be switched off by selecting a
high setting.

The current start condition STCNDLE is based on the following criteria:

• Residual current criteria


• No quadrilateral impedance characteristic. The impedance reach outside the load area is
theoretically infinite. The practical reach, however, will be determined by the minimum
operating current limits.
• Load encroachment characteristic is always active, but can be switched off by selecting a
high setting.

The STCNDLE output is non-directional. The directionality is determined by the distance zones
directional function ZDRDIR.

There are output from FRPSPDIS that indicate whether a start is in forward or reverse direction
or non-directional, for example STFWL1, STRVL1 and STNDL1.

294 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

These directional indications are based on the sector boundaries of the directional function
and the impedance setting of FRPSPDIS function. Their operating characteristics are
illustrated in figure 148.

X X X

R
R R

Non-directional (ND) Forward (FW) Reverse (RV)

en08000286.vsd
IEC08000286 V1 EN-US

Figure 148: Characteristics for non-directional, forward and reverse operation of Phase
selection, quadrilateral characteristic with settable angle (FRPSPDIS)

The setting of the load encroachment function may influence the total operating
characteristic, for more information, refer to section "Load encroachment".

The input DIRCND contains binary coded information about the directional coming from the
directional function ZDRDIR. It shall be connected to the STDIR output on ZDRDIR. This
information is also transferred to the input DIRCND on the distance measuring zones, that is,
the ZMRPDIS block.

The code built up for the directionality is as follows:

STDIR= STFWL1*1+STFWL2*2+STFWL3*4+STFWL1L2*8+
+STFWL2L3*16+STFWL3L1*32+STRVL1*64+STRVL2*128+
+STRVL3*256+STRVL1L2*512+STRVL2L3*1024+STRVL3L1*2048

If the binary information is 1 then it will be considered that we have start in forward direction
in phase L1. If the binary code is 3 then we have start in forward direction in phase L1 and L2
etc.

The STCNDZ or STCNDLE output contains, in a similar way as DIRCND, binary coded
information, in this case information about the condition for opening correct fault loop in the
distance measuring element. It shall be connected to the STCND input on the ZMRPDIS
distance measuring zones block.

The code built up for release of the measuring fault loops is as follows:

STCNDZ = L1N*1 + L2N*2 + L3N*4 + L1L2*8 + L2L3*16 + L3L1*32

8.10.6.1 Phase-to-earth fault GUID-37AF6C9C-852E-48D9-A307-A23F2BF6884A v1

For a phase-to-earth fault, the measured impedance by FRPSPDIS is according to equation 60.

Line distance protection REL670 295


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Index PHS in images and equations reference settings for Phase selection,
quadrilateral characteristic with settable angle (FRPSPDIS).

ULn
ZPHSn =
ILn
EQUATION1255 V1 EN-US (Equation 60)

where:
n corresponds to the particular phase (n=1, 2 or 3)

The characteristic for FRPSPDIS function at phase-to-earth fault is according to figure 149. The
characteristic has a settable angle for the resistive boundary in the first quadrant of 70°.

The resistance RN and reactance XN are the impedance in the earth-return path defined
according to equation 63 and equation 64.

R 0 PE - R1PE
RN =
3
EQUATION-2125 V1 EN-US (Equation 61)
R0 - R1
RN =
3
EQUATION1256 V1 EN-US (Equation 61)

X 0 - X1
XN =
3
EQUATION1257 V1 EN-US (Equation 62)

296 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

X (ohm/loop)
R1PE+RN

RFRvPE RFFwPE

X1+XN

RFFwPE

RFRvPE R (Ohm/loop)

X1+XN

RFRvPE RFFwPE

R1PE+RN
IEC09000633-1-en.vsd
IEC09000633 V1 EN-US

Figure 149: Characteristic of FRPSPDIS for phase to earth fault (directional lines are
drawn as "line-dot-dot-line")
Besides this, the 3I0 residual current must fulfil the conditions according to equation 63 and
equation 64.

3 × I0 ³ 0.5 × IMinOpPE
EQUATION2108 V1 EN-US (Equation 63)

INReleasePE- Iphmax
3 × I0 ³ ----------------------------------- ×
100
EQUATION766 V1 EN-US (Equation 64)

where:
IMinOpPE is the minimum operation current for forward zones
INReleasePE is the setting for the minimum residual current needed to enable operation in the phase-to-
earth fault loops (in %).
Iphmax is the maximum phase current in any of three phases.

8.10.6.2 Phase-to-phase fault GUID-8C41B037-72E8-42EB-A5BA-9FA20BD830DB v1

For a phase-to-phase fault, the measured impedance by FRPSPDIS is according to equation 65.

ULm - ULn
ZPHS =
-2 × ILn
EQUATION1258 V1 EN-US (Equation 65)

Line distance protection REL670 297


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

ULm is the leading phase voltage, ULn the lagging phase voltage and ILn the phase current in
the lagging phase n.

The operation characteristic is shown in figure 150.

X (ohm/phase)

0.5·FRvPP
R1PP 0.5·RFFwPP

X1
0.5·RFFwPP

R (ohm/phase)

0.5·RFRvPP
X1

R1PP
0.5·RFRvPP 0.5·RFFwPP
IEC09000634-1-en.vsd
IEC09000634 V1 EN-US

Figure 150: The operation characteristic for FRPSPDIS at phase-to-phase fault


(directional lines are drawn as "line-dot-dot-line")
In the same way as the condition for phase-to-earth fault, there are current conditions that
have to be fulfilled in order to release the phase-to-phase loop. Those are according to
equation 66 or equation 67.

3I 0 < IMinOpPE
EQUATION2109 V1 EN-US (Equation 66)

INBlockPP
3I 0 < × Iph max
100
EQUATION2110 V1 EN-US (Equation 67)

where:
IMinOpPE is the minimum operation current for forward earth measuring loops,
INBlockPP is 3I0 limit for blocking phase-to-phase measuring loop and
Iphmax is maximal magnitude of the phase currents.

298 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

8.10.6.3 Three-phase faults GUID-0CB276AE-1700-4ACB-8F90-E8E1FD670365 v1

The operation conditions for three-phase faults are the same as for phase-to-phase fault, that
is equation 65, equation 66 and equation 67 are used to release the operation of the function.

However, the reach is expanded by a factor 2/√3 (approximately 1.1547) in all directions. At the
same time the characteristic is rotated 30 degrees, counter-clockwise. The characteristic is
shown in figure 151.

X (ohm/phase)

4 × X1PP
3

0.5·RFFwPP·K3

X1·K3 30 deg 2
RFwPP ×
3

R (ohm/phase)

0.5·RFRvPP·K3

K3 = 2 / sqrt(3)
30 deg

IEC09000635-1-en.vsd
IEC09000635 V2 EN-US

Figure 151: The characteristic of FRPSPDIS for three-phase fault (set angle 70°)

8.10.6.4 Load encroachment GUID-ABD74C3B-FF0F-45B3-BF34-D7C5FEAD62D3 v1

Each of the six measuring loops has its own load encroachment characteristic based on the
corresponding loop impedance. The load encroachment functionality is always active, but can
be switched off by selecting a high setting.

The outline of the characteristic is presented in figure 153. As illustrated, the resistive blinders
are set individually in forward and reverse direction while the angle of the sector is the same in
all four quadrants.

Line distance protection REL670 299


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

RLdFw
ArgLd ArgLd
R

ArgLd ArgLd
RLdRv

IEC09000042-1-en.vsd
IEC09000042 V1 EN-US

Figure 152: Characteristic of load encroachment function


The influence of load encroachment function on the operation characteristic is dependent on
the chosen operation mode of FRPSPDIS function. When output signal STCNDZ is selected, the
characteristic for FRPSPDIS (and also zone measurement depending on settings) will be
reduced by the load encroachment characteristic, see figure 154.

When output signal STCNDI is selected, the operation characteristic will be as in figure 153.
The reach will in this case be limit by the minimum operation current and the distance
measuring zones.

X X

R R

STCNDZ STCNDLE

IEC10000099-1-
en.vsd
IEC10000099 V1 EN-US

Figure 153: Difference in operating characteristic depending on operation mode when


load encroachment is activated

300 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

When FRPSPDIS is set to operate together with a distance measuring zone the resultant
operate characteristic could look like in figure 154. The figure shows a distance measuring
zone operating in forward direction. Thus, the operating area of the zone together with the
load encroachment is highlighted in black.

"Phase selection"
"quadrilateral" zone

Distance measuring zone

Load encroachment
characteristic

Directional line

en05000673.vsd
IEC05000673 V1 EN-US

Figure 154: Operating characteristic in forward direction when load encroachment is


activated
Figure 154 is valid for phase-to-earth. During a three-phase fault, or load, when the
quadrilateral phase-to-phase characteristic is subject to enlargement and rotation the operate
area is transformed according to figure 155. Notice in particular what happens with the
resistive blinders of the "phase selection" "quadrilateral" zone. Due to the 30-degree rotation,
the angle of the blinder in quadrant one is now 100 degrees instead of the original 70 degrees
(if the angle setting is 70 degrees). The blinder that is nominally located to quadrant four will
at the same time tilt outwards and increase the resistive reach around the R-axis.
Consequently, it will be more or less necessary to use the load encroachment characteristic in
order to secure a margin to the load impedance.

Line distance protection REL670 301


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

X (W / phase)
Phase selection
”Quadrilateral” zone

Distance measuring zone

R (W / phase)

IEC09000049-1-en.vsd
IEC09000049 V1 EN-US

Figure 155: Operating characteristic for FRPSPDIS in forward direction for three-phase
fault, ohm/phase domain
The result from rotation of the load characteristic at a fault between two phases is presented
in fig 156. Since the load characteristic is based on the same measurement as the quadrilateral
characteristic, it will rotate with the quadrilateral characteristic clockwise by 30 degrees when
subject to a pure phase-to-phase fault. At the same time the characteristic will "shrink" by
2/√3, from the full RLdFw and RLdRv reach, which is valid at load or three-phase fault.

302 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

IEC08000437.vsd

IEC08000437 V1 EN-US

Figure 156: Rotation of load characteristic for a fault between two phases
There is a gain in selectivity by using the same measurement as for the quadrilateral
characteristic since not all phase-to-phase loops will be fully affected by a fault between two
phases. It should also provide better fault resistive coverage in quadrant one. The relative loss
of fault resistive coverage in quadrant four should not be a problem even for applications on
series compensated lines.

8.10.6.5 Minimum operate currents GUID-7F780AC7-36AB-4704-843D-C1EA3F5B2D6A v1

The operation of Phase selection, quadrilateral characteristic with settable angle (FRPSPDIS) is
blocked if the magnitude of input currents falls below certain threshold values.

The phase-to-earth loop Ln is blocked if ILn<IMinOpPE, where ILn is the RMS value of the
current in phase Ln.

The phase-to-phase loop LmLn is blocked if (2·ILn<IMinOpPP).

8.10.6.6 Simplified logic diagrams GUID-95AD1A91-86F0-4854-A12B-99C504BFBC6C v1

Figure 157 presents schematically the creation of the phase-to-phase and phase-to-earth
operating conditions. Consider only the corresponding part of measuring and logic circuits,
when only a phase-to-earth or phase-to-phase measurement is available within the IED.

Line distance protection REL670 303


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

OperationZ<
AND
LDEblock

3I 0  0.5  IMinOpPE IRELPE

& 15 ms
AND t STPE
INReleasePE
3I 0   Iphmax
100 STCNDLE
Bool to AND
BLOCK integer

15 ms
3I 0  IMinOpPE 10 ms 20 ms & t STPP

OR AND t t
IRELPP
INBlockPP
3I 0   Iphmax
100

IEC09000149-3-en.vsd
IEC09000149 V3 EN-US

Figure 157: Phase-to-phase and phase-to-earth operating conditions (residual current


criteria)
A special attention is paid to correct phase selection at evolving faults. A STCNDLE output
signal is created as a combination of the load encroachment characteristic and current
criteria, refer to figure 157. This signal can be configured to STCND functional input signals of
the distance protection zone and this way influence the operation of the phase-to-phase and
phase-to-earth zone measuring elements and their phase related starting and tripping signals.

Figure 158 presents schematically the composition of non-directional phase selective signals
STNDLn. Internal signals ZMLnN and ZMLmLn (m and n change between one and three
according to the phase number) represent the fulfilled operating criteria for each separate
loop measuring element, that is within the characteristic.

INDL1N
INDL2N
INDL3N

15 ms
STNDPE
IRELPE OR t

LDEblockL1N
IL1 AND 15 ms
OR STNDL1
ZML1N OR t
LDEblockL2N
IL2 AND
OR
ZML2N 15 ms
LDEblockL3N STNDL2
OR t
IL3 AND
OR
ZML3N
LDEblockL1L2 15 ms
STNDL3
IL1 & IL2 AND OR t
OR
ZML1L2
LDEblockL2L3
IL2 & IL3 AND INDL1L2
OR
ZML2L3 INDL2L3
LDEblockL3L1
IL3 & IL1 AND
OR INDL3L1
ZML3L1
IRELPP 15 ms
STNDPP
OR t

IEC00000545-4-en.vsd
IEC00000545-TIFF V4 EN-US

Figure 158: Composition on non-directional phase selection signals

304 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Composition of the directional (forward and reverse) phase selective signals is presented
schematically in figure 159 and figure 160. The directional criteria appears as a condition for
the correct phase selection in order to secure a high phase selectivity for simultaneous and
evolving faults on lines within the complex network configurations. Internal signals DFWLn and
DFWLnLm present the corresponding directional signals for measuring loops with phases Ln
and Lm. Designation FW (figure 160) represents the forward direction as well as the
designation RV (figure 159) represents the reverse direction. All directional signals are derived
within the corresponding digital signal processor.

Figure 159 presents additionally a composition of a STCNDZ output signal, which is created on
the basis of impedance measuring conditions. This signal can be configured to STCND
functional input signals of the distance protection zone and this way influence the operation
of the phase-to-phase and phase-to-earth zone measuring elements and their phase related
starting and tripping signals.

INDL1N
AND
DRVL1N
INDL1L2 15 ms STRVL1
AND OR t
DRVL1L2
INDL3L1
AND
DRVL3L1 15 ms
STRVPE
INDL2N OR t
AND
DRVL2N
INDL1L2 15 ms
STRVL2
AND OR t

INDL2L3 INDL1N
AND INDL2N
DRVL2L3
INDL3N Bool to STCNDZ
INDL3N INDL1L2 integer
AND INDL2L3
DRVL3N INDL3L1
INDL2L3 15 ms
STRVL3
AND OR t

INDL3L1
15 ms
AND STRVPP
OR t

IEC00000546_2_en.vsd
IEC00000546-TIFF V2 EN-US

Figure 159: Composition of phase selection signals for reverse direction

Line distance protection REL670 305


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

AND

INDL1N
AND 15 ms 15 ms
DFWL1N STFW1PH
AND OR t t
INDL1L2
15 ms STFWL1
AND OR t
DFWL1L2
INDL3L1
AND
AND
DFWL3L1 15 ms
STFWPE
INDL2N OR t
AND
DFWL2N
AND 15 ms
INDL1L2 STFWL2
t
AND OR
15 ms 15 ms
INDL2L3 STFW2PH
AND OR t t
AND
DFWL2L3
INDL3N
AND AND
DFWL3N 15 ms
STFWL3
t
INDL2L3
AND OR
15 ms
INDL3L1 STFW3PH
AND t
AND

15 ms
STFWPP
OR t

IEC05000201_2_en.vsd

IEC05000201 V2 EN-US

Figure 160: Composition of phase selection signals for forward direction


Figure161 presents the composition of output signals TRIP and START, where internal signals
STNDPP, STFWPP and STRVPP are the equivalent to internal signals STNDPE, STFWPE and
STRVPE, but for the phase-to-phase loops.

306 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

TimerPP=Off
tPP
AND AND
t
TRIP
OR OR
tPE
TimerPE=Off
t
AND AND

STNDPP

STFWPP OR
STRVPP
START
OR
STNDPE

STFWPE OR
STRVPE

IEC08000441_2_en.vsd
IEC08000441-1 V2 EN-US

Figure 161: TRIP and START signal logic

8.10.7 Technical data


GUID-9E13C38A-3B6D-402B-98A6-6CDA20632CE7 v5

Table 182: FRPSPDIS technical data


Function Range or value Accuracy
Minimum operate current (5-500)% of IBase ±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir

Reactive reach, positive (0.50–3000.00) Ω/phase ±2.0% static accuracy


sequence ±2.0 degrees static angular accuracy
Conditions:
Resistive reach, positive (0.10–1000.00) Ω/phase Voltage range: (0.1-1.1) x Ur
sequence
Current range: (0.5-30) x Ir
Reactive reach, zero sequence (0.50–9000.00) Ω/phase Angle: at 0 degrees and 85 degrees

Resistive reach, zero sequence (0.50–3000.00) Ω/phase


Fault resistance, Ph-E faults, (1.00–9000.00) Ω/loop
forward and reverse
Fault resistance, Ph-Ph faults, (0.50–3000.00) Ω/loop
forward and reverse
Reset ratio 105% typically -

Line distance protection REL670 307


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

8.11 High speed distance protection ZMFPDIS GUID-CC4F7338-2281-411D-B55A-67BF03F31681 v4

8.11.1 Identification GUID-8ACD3565-C607-4399-89D2-A05657840E6D v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
High speed distance protection zone ZMFPDIS 21

Z
S00346 V2 EN-US

8.11.2 Functionality GUID-2E34AB7F-886E-499F-8984-09041A89238D v8

The High speed distance protection (ZMFPDIS) is providing sub-cycle, down towards half-
cycle, operate time for basic faults within 60% of the line length and up to around SIR 5.

The ZMFPDIS function is a six zone full scheme protection with three fault loops for phase-to-
phase faults and three fault loops for phase-to-earth faults for each of the independent zones,
which makes the function suitable in applications with single-phase autoreclosing.

In each measurement zone, ZMFPDIS function is designed with the flexibility to operate in
either quadrilateral or mho characteristic mode for separate phase-to-ground or phase-to-
phase loops.

The zones can operate independently of each other. Zones 3 to 5 in directional (forward or
reverse) or non-directional mode. Zone1 and zone2 are designed to measure in forward
direction only, while one zone (ZRV) is designed to measure in the reverse direction. This
makes them suitable, together with a communication scheme, for protection of power lines
and cables in complex network configurations, such as parallel lines, multi-terminal lines, and
so on.

A built-in adaptive load compensation algorithm prevents overreaching of the distance zones
in the load exporting end during phase-to-earth faults on heavily loaded power lines. It also
reduces underreach in the importing end.

The ZMFPDIS function block itself incorporates a phase-selection element and a directional
element, contrary to previous designs in the 600-series, where these elements were
represented with separate function-blocks.

The operation of the phase-selection element is primarily based on current change criteria (i.e.
delta quantities), with significantly increased dependability. There is also a phase selection
criterion operating in parallel which bases its operation only on voltage and current phasors.

The directional element utilizes a set of well-established quantities to provide fast and correct
directional decision during various power system operating conditions, including close-in
three-phase faults, simultaneous faults and faults with only zero-sequence in-feed.

308 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

8.11.3 Function block GUID-322E158B-C2A1-4F0D-A749-01C7942875ED v1

ZMFPDIS
I3P* TRIP
U3P* TRZ1
BLOCK TRL1Z1
VTSZ TRL2Z1
BLKZ1 TRL3Z1
BLKZ2 TRZ2
BLKZ3 TRL1Z2
BLKZ4 TRL2Z2
BLKZ5 TRL3Z2
BLKZRV TRZ3
BLKTRZ1 TRZ4
BLKTRZ2 TRZ5
BLKTRZ3 TRZRV
BLKTRZ4 START
BLKTRZ5 STZ1
BLKTRZRV STNDZ1
EXTNST STZ2
RELCNDZ1 STL1Z2
RELCNDZ2 STL2Z2
RELCNDZ3 STL3Z2
RELCNDZ4 STNDZ2
RELCNDZ5 STZ3
RELCNDZRV STNDZ3
STZ4
STNDZ4
STZ5
STNDZ5
STZRV
STL1ZRV
STL2ZRV
STL3ZRV
STNDZRV
STND
STNDL1
STNDL2
STNDL3
STNDPE
STFWL1
STFWL2
STFWL3
STFWPE
STRVL1
STRVL2
STRVL3
STRVP E
STFW1PH
STFW2PH
STFW3PH
STPE
STPP

IEC11000433-5-en.vsdx
IEC11000433 V5 EN-US

Figure 162: ZMFPDIS function block

8.11.4 Signals
PID-7162-INPUTSIGNALS v1

Table 183: ZMFPDIS Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Blocks and resets timers and outputs of entire function
VTSZ BOOLEAN 0 Blocks and resets timers and outputs of entire function
BLKZ1 BOOLEAN 0 Blocks and resets zone 1 timers and outputs
Table continues on next page

Line distance protection REL670 309


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Name Type Default Description


BLKZ2 BOOLEAN 0 Blocks and resets zone 2 timers and outputs
BLKZ3 BOOLEAN 0 Blocks and resets zone 3 timers and outputs
BLKZ4 BOOLEAN 0 Blocks and resets zone 4 timers and outputs
BLKZ5 BOOLEAN 0 Blocks and resets zone 5 timers and outputs
BLKZRV BOOLEAN 0 Blocks and resets reverse zone timers and outputs
BLKTRZ1 BOOLEAN 0 Blocks and resets zone 1 timers and trip outputs
BLKTRZ2 BOOLEAN 0 Blocks and resets zone 2 timers and trip outputs
BLKTRZ3 BOOLEAN 0 Blocks and resets zone 3 timers and trip outputs
BLKTRZ4 BOOLEAN 0 Blocks and resets zone 4 timers and trip outputs
BLKTRZ5 BOOLEAN 0 Blocks and resets zone 5 timers and trip outputs
BLKTRZRV BOOLEAN 0 Blocks and resets reverse zone timers and trip outputs
EXTNST BOOLEAN 0 External start of zone timers
RELCNDZ1 INTEGER 127 Release word for the measuring loops of zone 1
RELCNDZ2 INTEGER 127 Release word for the measuring loops of zone 2
RELCNDZ3 INTEGER 127 Release word for the measuring loops of zone 3
RELCNDZ4 INTEGER 127 Release word for the measuring loops of zone 4
RELCNDZ5 INTEGER 127 Release word for the measuring loops of zone 5
RELCNDZRV INTEGER 127 Release word for the measuring loops of zone RV

PID-7162-OUTPUTSIGNALS v1

Table 184: ZMFPDIS Output signals


Name Type Description
TRIP BOOLEAN Trip in any phase or phases from any zone or zones
TRZ1 BOOLEAN Trip in any phase or phases from zone 1 - forward direction
TRL1Z1 BOOLEAN Trip in phase L1 from zone 1 - forward direction
TRL2Z1 BOOLEAN Trip in phase L2 from zone 1 - forward direction
TRL3Z1 BOOLEAN Trip in phase L3 from zone 1 - forward direction
TRZ2 BOOLEAN Trip in any phase or phases from zone 2 - forward direction
TRL1Z2 BOOLEAN Trip in phase L1 from zone 2 - forward direction
TRL2Z2 BOOLEAN Trip in phase L2 from zone 2 - forward direction
TRL3Z2 BOOLEAN Trip in phase L3 from zone 2 - forward direction
TRZ3 BOOLEAN Trip in any phase or phases from zone 3 - zone direction
TRZ4 BOOLEAN Trip in any phase or phases from zone 4 - zone direction
TRZ5 BOOLEAN Trip in any phase or phases from zone 5 - zone direction
TRZRV BOOLEAN Trip in any phase or phases from zone RV - reverse direction
START BOOLEAN Start in any phase or phases from any zone or zones
STZ1 BOOLEAN Start in any phase or phases from zone 1 - forward direction
STNDZ1 BOOLEAN Start in any phase or phases from zone 1 - any direction
STZ2 BOOLEAN Start in any phase or phases from zone 2 - forward direction
STL1Z2 BOOLEAN Start in phase L1 from zone 2 - forward direction
STL2Z2 BOOLEAN Start in phase L2 from zone 2 - forward direction
STL3Z2 BOOLEAN Start in phase L3 from zone 2 - forward direction
Table continues on next page

310 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Name Type Description


STNDZ2 BOOLEAN Start in any phase or phases from zone 2 - any direction
STZ3 BOOLEAN Start in any phase or phases from zone 3 - zone direction
STNDZ3 BOOLEAN Start in any phase or phases from zone 3 - any direction
STZ4 BOOLEAN Start in any phase or phases from zone 4 - zone direction
STNDZ4 BOOLEAN Start in any phase or phases from zone 4 - any direction
STZ5 BOOLEAN Start in any phase or phases from zone 5 - zone direction
STNDZ5 BOOLEAN Start in any phase or phases from zone 5 - any direction
STZRV BOOLEAN Start in any phase or phases from zone RV - reverse direction
STL1ZRV BOOLEAN Start in phase L1 from zone RV - reverse direction
STL2ZRV BOOLEAN Start in phase L2 from zone RV - reverse direction
STL3ZRV BOOLEAN Start in phase L3 from zone RV - reverse direction
STNDZRV BOOLEAN Start in any phase or phases from zone RV - any direction
STND BOOLEAN Fault detected in any phase or phases - any direction
STNDL1 BOOLEAN Fault detected in phase L1 - any direction
STNDL2 BOOLEAN Fault detected in phase L2 - any direction
STNDL3 BOOLEAN Fault detected in phase L3 - any direction
STNDPE BOOLEAN Fault with earth connection detected in any phase or phases -
any direction
STFWL1 BOOLEAN Fault detected in phase L1 - forward direction
STFWL2 BOOLEAN Fault detected in phase L2 - forward direction
STFWL3 BOOLEAN Fault detected in phase L3 - forward direction
STFWPE BOOLEAN Fault with earth connection detected - forward direction
STRVL1 BOOLEAN Fault detected in phase L1 - reverse direction
STRVL2 BOOLEAN Fault detected in phase L2 - reverse direction
STRVL3 BOOLEAN Fault detected in phase L3 - reverse direction
STRVPE BOOLEAN Fault with earth connection detected - reverse direction
STFW1PH BOOLEAN Single-phase fault detected - forward direction
STFW2PH BOOLEAN Two-phase fault detected - forward direction
STFW3PH BOOLEAN Three-phase fault detected - forward direction
STPE BOOLEAN Ph-E zone measurement enabled - any direction
STPP BOOLEAN Ph-Ph zone measurement enabled - any direction

Line distance protection REL670 311


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

8.11.5 Settings
PID-7162-SETTINGS v1

Table 185: ZMFPDIS Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups
ZDbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
ZMax 0.0 - 5000.0 Ohm 0.1 1500.0 Maximum value in ohm
ZRepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband
Dead band & 5s
Cyclic
Dead band & 30s
Cyclic
Dead band & 1min
Cyclic
ZAngDbRepInt 1 - 100000 Type 1 10 Cyclic report interval (s)

Table 186: ZMFPDIS Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
RLdFw 0.01 - 5000.00 Ohm/p 0.01 60.00 Resistance determining the load
impedance area - forward
RLdRvFactor 1 - 1000 %RLdF 1 100 Resistance factor determining the
w load impedance area - reverse
XLd 0.01 - 10000.00 Ohm/p 0.01 400.00 Reactance determining the load
impedance area
ArgLd 5 - 70 Deg 1 30 Angle determining the load
impedance area
CVTType Any - - Passive type CVT selection determining filtering of
Passive type the function
None (Magnetic)
OpModePPZ1 Off - - Quadrilateral On/Off and characteristic setting for
Quadrilateral Ph-Ph loops, zone 1
Mho
MhoOffset
OpModePEZ1 Off - - Quadrilateral On/Off and characteristic setting for
Quadrilateral Ph-E loops, zone 1
Mho
MhoOffset
X1PPZ1 0.01 - 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach,
Ph-Ph, zone 1
R1PPZ1 0.00 - 1000.00 Ohm/p 0.01 5.00 Positive sequence resistive reach, Ph-
Ph, zone 1
X1PEZ1 0.01 - 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach,
Ph-E, zone 1
R1PEZ1 0.00 - 1000.00 Ohm/p 0.01 5.00 Positive sequence resistive reach, Ph-
E, zone 1
X0Z1 0.01 - 9000.00 Ohm/p 0.01 100.00 Zero sequence reactance reach, zone 1
R0Z1 0.00 - 3000.00 Ohm/p 0.01 15.00 Zero sequence resistive reach, zone 1
Table continues on next page

312 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Name Values (Range) Unit Step Default Description


RFPPZ1 0.01 - 9000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, zone 1
RFPEZ1 0.01 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-E, zone 1
tPPZ1 0.000 - 60.000 s 0.001 0.000 Time delay to trip, Phase-Phase, zone
1
tPEZ1 0.000 - 60.000 s 0.001 0.000 Time delay to trip, Phase-Earth, zone 1
IMinOpPPZ1 10 - 6000 %IB 1 10 Minimum operate Ph-Ph current for
Phase-Phase loops, zone 1
IMinOpPEZ1 5 - 6000 %IB 1 10 Minimum operate phase current for
Phase-Earth loops, zone 1
OpModePPZ2 Off - - Quadrilateral On/Off and characteristic setting for
Quadrilateral Ph-Ph loops, zone 2
Mho
MhoOffset
OpModePEZ2 Off - - Quadrilateral On/Off and characteristic setting for
Quadrilateral Ph-E loops, zone 2
Mho
MhoOffset
X1Z2 0.01 - 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach,
zone 2
R1Z2 0.00 - 1000.00 Ohm/p 0.01 5.00 Positive sequence resistive reach,
zone 2
X0Z2 0.01 - 9000.00 Ohm/p 0.01 120.00 Zero sequence reactance reach, zone 2
R0Z2 0.00 - 3000.00 Ohm/p 0.01 15.00 Zero sequence resistive reach, zone 2
RFPPZ2 0.01 - 9000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, zone 2
RFPEZ2 0.01 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-E, zone 2
tPPZ2 0.000 - 60.000 s 0.001 0.400 Time delay to trip, Phase-Phase, zone
2
tPEZ2 0.000 - 60.000 s 0.001 0.400 Time delay to trip, Phase-Earth, zone 2
IMinOpPPZ2 10 - 6000 %IB 1 10 Minimum operate Ph-Ph current for
Phase-Phase loops, zone 2
IMinOpPEZ2 5 - 6000 %IB 1 10 Minimum operate phase current for
Phase-Earth loops, zone 2
OpModePPZ3 Off - - Quadrilateral On/Off and characteristic setting for
Quadrilateral Ph-Ph loops, zone 3
Mho
MhoOffset
OpModePEZ3 Off - - Quadrilateral On/Off and characteristic setting for
Quadrilateral Ph-E loops, zone 3
Mho
MhoOffset
DirModeZ3 Non-directional - - Forward Direction of zone 3
Forward
Reverse
X1Z3 0.01 - 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach,
zone 3
R1Z3 0.00 - 1000.00 Ohm/p 0.01 5.00 Positive sequence resistive reach,
zone 3
X0Z3 0.01 - 9000.00 Ohm/p 0.01 120.00 Zero sequence reactance reach, zone 3
R0Z3 0.00 - 3000.00 Ohm/p 0.01 15.00 Zero sequence resistive reach, zone 3
RFPPZ3 0.01 - 9000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, zone 3
RFPEZ3 0.01 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-E, zone 3
Table continues on next page

Line distance protection REL670 313


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Name Values (Range) Unit Step Default Description


tPPZ3 0.000 - 60.000 s 0.001 0.800 Time delay to trip, Phase-Phase, zone
3
tPEZ3 0.000 - 60.000 s 0.001 0.800 Time delay to trip, Phase-Earth, zone 3
IMinOpPPZ3 10 - 6000 %IB 1 10 Minimum operate Ph-Ph current for
Phase-Phase loops, zone 3
IMinOpPEZ3 5 - 6000 %IB 1 10 Minimum operate phase current for
Phase-Earth loops, zone 3
OpModePPZ4 Off - - Quadrilateral On/Off and characteristic setting for
Quadrilateral Ph-Ph loops, zone 4
Mho
MhoOffset
OpModePEZ4 Off - - Quadrilateral On/Off and characteristic setting for
Quadrilateral Ph-E loops, zone 4
Mho
MhoOffset
DirModeZ4 Non-directional - - Forward Direction of zone 4
Forward
Reverse
X1Z4 0.01 - 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach,
zone 4
R1Z4 0.00 - 1000.00 Ohm/p 0.01 5.00 Positive sequence resistive reach,
zone 4
X0Z4 0.01 - 9000.00 Ohm/p 0.01 120.00 Zero sequence reactance reach, zone
4
R0Z4 0.00 - 3000.00 Ohm/p 0.01 15.00 Zero sequence resistive reach, zone 4
RFPPZ4 0.01 - 9000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, zone 4
RFPEZ4 0.01 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-E, zone 4
tPPZ4 0.000 - 60.000 s 0.001 1.200 Time delay to trip, Phase-Phase, zone
4
tPEZ4 0.000 - 60.000 s 0.001 1.200 Time delay to trip, Phase-Earth, zone 4
IMinOpPPZ4 10 - 6000 %IB 1 10 Minimum operate Ph-Ph current for
Phase-Phase loops, zone 4
IMinOpPEZ4 5 - 6000 %IB 1 10 Minimum operate phase current for
Phase-Earth loops, zone 4
OpModePPZ5 Off - - Quadrilateral On/Off and characteristic setting for
Quadrilateral Ph-Ph loops, zone 5
Mho
MhoOffset
OpModePEZ5 Off - - Quadrilateral On/Off and characteristic setting for
Quadrilateral Ph-E loops, zone 5
Mho
MhoOffset
DirModeZ5 Non-directional - - Forward Direction of zone 5
Forward
Reverse
X1Z5 0.01 - 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach,
zone 5
R1Z5 0.00 - 1000.00 Ohm/p 0.01 5.00 Positive sequence resistive reach,
zone 5
X0Z5 0.01 - 9000.00 Ohm/p 0.01 120.00 Zero sequence reactance reach, zone
5
R0Z5 0.00 - 3000.00 Ohm/p 0.01 15.00 Zero sequence resistive reach, zone 5
RFPPZ5 0.01 - 9000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, zone 5
Table continues on next page

314 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Name Values (Range) Unit Step Default Description


RFPEZ5 0.01 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-E, zone 5
tPPZ5 0.000 - 60.000 s 0.001 1.600 Time delay to trip, Phase-Phase, zone
5
tPEZ5 0.000 - 60.000 s 0.001 1.600 Time delay to trip, Phase-Earth, zone 5
IMinOpPPZ5 10 - 6000 %IB 1 10 Minimum operate Ph-Ph current for
Phase-Phase loops, zone 5
IMinOpPEZ5 5 - 6000 %IB 1 10 Minimum operate phase current for
Phase-Earth loops, zone 5
OpModePPZRV Off - - Quadrilateral On/Off and characteristic setting for
Quadrilateral Ph-Ph loops, zone RV
Mho
MhoOffset
OpModePEZRV Off - - Quadrilateral On/Off and characteristic setting for
Quadrilateral Ph-E loops, zone RV
Mho
MhoOffset
X1ZRV 0.01 - 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach,
zone RV
R1ZRV 0.00 - 1000.00 Ohm/p 0.01 5.00 Positive sequence resistive reach,
zone RV
X0ZRV 0.01 - 9000.00 Ohm/p 0.01 120.00 Zero sequence reactance reach, zone
RV
R0ZRV 0.00 - 3000.00 Ohm/p 0.01 15.00 Zero sequence resistive reach, zone
RV
RFPPZRV 0.01 - 9000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, zone RV
RFPEZRV 0.01 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-E, zone RV
tPPZRV 0.000 - 60.000 s 0.001 0.000 Time delay to trip, Phase-Phase, zone
RV
tPEZRV 0.000 - 60.000 s 0.001 0.000 Time delay to trip, Phase-Earth, zone
RV
IMinOpPPZRV 10 - 6000 %IB 1 10 Minimum operate Ph-Ph current for
Phase-Phase loops, zone RV
IMinOpPEZRV 5 - 6000 %IB 1 10 Minimum operate phase current for
Phase-Earth loops, zone RV

Table 187: ZMFPDIS Non group settings (advanced)


Name Values (Range) Unit Step Default Description
ZZeroDb 0 - 100000 m% 100 0 Magnitude zero point clamping in
0,001% of range
ZHiHiLim 0.0 - 5000.0 Ohm 0.1 800.0 High High limit in ohm
ZHiLim 0.0 - 5000.0 Ohm 0.1 150.0 High limit in ohm
ZLowLim 0.0 - 5000.0 Ohm 0.1 50.0 Low limit in ohm
ZLowLowLim 0.0 - 5000.0 Ohm 0.1 35.0 Low Low limit in ohm
ZMin 0.000 - 5000.000 Ohm 0.001 0.005 Minimum value in ohm
ZLimHys 0.000 - 100.000 % 0.001 0.500 Hysteresis value in % of range and is
common for all limits

Line distance protection REL670 315


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Table 188: ZMFPDIS Group settings (advanced)


Name Values (Range) Unit Step Default Description
RLdFwMax 0.01 - 5000.00 Ohm/p 0.01 5000.00 Maximum used resistance
determining the load impedance area,
if RLdFw is greater than RLdFwMax
then RLdFw is set to RLdFwMax
RLdFwMin 0.01 - 5000.00 Ohm/p 0.01 0.01 Minimum used resistance determining
the load impedance area, if RLdFw is
less than RLdFwMin then RLdFw is set
to RLdFwMin
ArgLdMax 5 - 70 Deg 1 70 Maximum used angle determining the
load impedance area, if ArgLd is
greater than ArgLdMax then ArgLd is
set to ArgLdMax
ArgLdMin 5 - 70 Deg 1 5 Minimum used angle determining the
load impedance area, if ArgLd is less
than ArgLdMin then ArgLd is set to
ArgLdMin
ZoneLinkStart Phase Selection - - Phase Selection Selection of start source for all
1st starting zone ZoneLinked trip delay timers
INReleasePE 5 - 400 %MaxIP 1 400 3I0 limit for releasing Phase-to-Earth
h measuring loops
TimerModeZ1 Disable all - - Enable Ph-E PhPh On/Off setting for Ph-Ph and Ph-E trip
Enable Ph-E output, zone 1
Enable PhPh
Enable Ph-E PhPh
TimerLinksZ1 LoopLink (tPP & - - LoopLink (tPP & How start of trip delay timers should
tPE) tPE) be linked for zone 1
LoopLink &
ZoneLink
No Links
TimerModeZ2 Disable all - - Enable Ph-E PhPh On/Off setting for Ph-Ph and Ph-E trip
Enable Ph-E output, zone 2
Enable PhPh
Enable Ph-E PhPh
TimerLinksZ2 LoopLink (tPP & - - LoopLink (tPP & How start of trip delay timers should
tPE) tPE) be linked for zone 2
LoopLink &
ZoneLink
No Links
TimerModeZ3 Disable all - - Enable Ph-E PhPh On/Off setting for Ph-Ph and Ph-E trip
Enable Ph-E output, zone 3
Enable PhPh
Enable Ph-E PhPh
TimerLinksZ3 LoopLink (tPP & - - LoopLink (tPP & How start of trip delay timers should
tPE) tPE) be linked for zone 3
LoopLink &
ZoneLink
No Links
TimerModeZ4 Disable all - - Enable Ph-E PhPh On/Off setting for Ph-Ph and Ph-E trip
Enable Ph-E output, zone 4
Enable PhPh
Enable Ph-E PhPh
TimerLinksZ4 LoopLink (tPP & - - LoopLink (tPP & How start of trip delay timers should
tPE) tPE) be linked for zone 4
LoopLink &
ZoneLink
No Links
Table continues on next page

316 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Name Values (Range) Unit Step Default Description


TimerModeZ5 Disable all - - Enable Ph-E PhPh On/Off setting for Ph-Ph and Ph-E trip
Enable Ph-E output, zone 5
Enable PhPh
Enable Ph-E PhPh
TimerLinksZ5 LoopLink (tPP & - - LoopLink (tPP & How start of trip delay timers should
tPE) tPE) be linked for zone 5
LoopLink &
ZoneLink
No Links
TimerModeZRV Disable all - - Enable Ph-E PhPh On/Off setting for Ph-Ph and Ph-E trip
Enable Ph-E output, zone RV
Enable PhPh
Enable Ph-E PhPh
TimerLinksZRV LoopLink (tPP & - - LoopLink (tPP & How start of trip delay timers should
tPE) tPE) be linked for zone RV
LoopLink &
ZoneLink
No Links

8.11.6 Monitored data


PID-7162-MONITOREDDATA v1

Table 189: ZMFPDIS Monitored data


Name Type Values (Range) Unit Description
L1Dir INTEGER 1=Forward - Direction in phase L1
2=Reverse
0=No direction
L2Dir INTEGER 1=Forward - Direction in phase L2
2=Reverse
0=No direction
L3Dir INTEGER 1=Forward - Direction in phase L3
2=Reverse
0=No direction
L1L2Dir INTEGER 1=Forward - Direction in loop L1L2
2=Reverse
0=No direction
L2L3Dir INTEGER 1=Forward - Direction in loop L2L3
2=Reverse
0=No direction
L3L1Dir INTEGER 1=Forward - Direction in loop L3L1
2=Reverse
0=No direction
L1R REAL - Ohm Resistance in phase L1
L1X REAL - Ohm Reactance in phase L1
L2R REAL - Ohm Resistance in phase L2
L2X REAL - Ohm Reactance in phase L2
L3R REAL - Ohm Resistance in phase L3
L3X REAL - Ohm Reactance in phase L3
L12R REAL - Ohm Resistance in phase L1-L2
L12X REAL - Ohm Reactance in phase L1-L2
L23R REAL - Ohm Resistance in phase L2-L3
L23X REAL - Ohm Reactance in phase L2-L3
Table continues on next page

Line distance protection REL670 317


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Name Type Values (Range) Unit Description


L31R REAL - Ohm Resistance in phase L3-L1
L31X REAL - Ohm Reactance in phase L3-L1
ZL1IMAG REAL - Ohm ZL1 Amplitude, magnitude of
instantaneous value
ZL1ANGIM REAL - deg ZL1 Angle, magnitude of
instantaneous value
ZL2IMAG REAL - Ohm ZL2 Amplitude, magnitude of
instantaneous value
ZL2ANGIM REAL - deg ZL2 Angle, magnitude of
instantaneous value
ZL3IMAG REAL - Ohm ZL3 Amplitude, magnitude of
instantaneous value
ZL3ANGIM REAL - deg ZL3 Angle, magnitude of
instantaneous value
ZL12IMAG REAL - Ohm ZL12 Amplitude, magnitude of
instantaneous value
ZL12ANGIM REAL - deg ZL12 Angle, magnitude of
instantaneous value
ZL23IMAG REAL - Ohm ZL23 Amplitude, magnitude of
instantaneous value
ZL23ANGIM REAL - deg ZL23 Angle, magnitude of
instantaneous value
ZL31IMAG REAL - Ohm ZL31 Amplitude, magnitude of
instantaneous value
ZL31ANGIM REAL - deg ZL31 Angle, magnitude of
instantaneous value

8.11.7 Operation principle GUID-2432C04F-62E4-4817-9900-C830306FB4B0 v3

Settings, input and output names are sometimes mentioned in the following
text without its zone suffix (i.e. BLKZx instead of BLKZ3) when the description
is equally valid for all zones.

8.11.7.1 Filtering GUID-16B5060B-101C-402A-BF25-06E70FDD7836 v2

Practically all voltage, current and impedance quantities used within the ZMFPDIS function are
derived from fundamental frequency phasors filtered by a half cycle filter.

The phasor filter is frequency adaptive in the sense that its coefficients are changed based on
the estimated power system frequency.

A half cycle filter will not be able to reject both even and odd harmonics. So, while odd
harmonics will be completely attenuated, accuracy will be affected by even harmonics. Even
harmonics will not cause the distance zones to overreach however; instead there will be a
slightly variable underreach, on average in the same order as the magnitude ratio between the
harmonic and fundamental component.

318 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

8.11.7.2 Distance measuring zones GUID-74B12BB1-FE0A-4DE4-BDBE-159A438D396B v4

The different fault loops within the IED are of full scheme type, which means that earth fault
loop for phase-to-earth faults and phase-to-phase faults for forward and reverse faults are
executed in parallel.

Figure 163 presents an outline of the different measuring loops for the six distance zones.

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 1

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 2

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 3

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 4

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 5

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1


Zone RV

IEC05000458-2-en.vsd
IEC05000458 V2 EN-US

Figure 163: The different measuring loops at phase-to-earth fault and phase-to-phase
fault
Each distance protection zone performs like one independent distance protection function
with six measuring elements.

Transients from CVTs may have a significant impact on the transient overreach of a distance
protection. At the same time these transients can be very diverse in nature from one type to
the other; in fact, more diverse than can be distinguished by the algorithm itself in the course
of a few milliseconds. So, a setting (CVTtype) is introduced in order to inform the algorithm
about the type of CVT applied and thus providing the advantage of knowing how performance
should be optimized, even during the first turbulent milliseconds of the fault period.

There are two types of CVTs from the function point of view, the passive and the active type,
which refers to the type of ferro-resonance suppression device that is employed. The active
type requires more rigorous filtering which will have a negative impact on operate times.
However, this will be evident primarily at higher source impedance ratios (SIRs), SIR 5 and
above, or close to the reach limit.

The IEC 60044-5 transient classification is of little or no use in relation to this. It is not
primarily the damping of transients that is important; it is the frequency content of the
transients that is decisive, i.e. how difficult it is to filter out the specific frequency. So, even if
two CVTs, one passive and the other active type, comply with the same transient class, the
active type requires more extensive filtering in order to avoid transient overreach.

To avoid overreach and at the same time achieve fast operate times, a supplementary circular
characteristic is implemented. A circular characteristic exists for every measuring loop and
quadrilateral/mho characteristic. There are no specific reach settings for this circular zone. It
uses the normal quadrilateral/mho zone settings to determine a reach that will be
appropriate. This implies that the circular characteristic will always have somewhat shorter
reach than the quadrilateral/mho zone.

8.11.7.3 Phase-selection element GUID-1E718907-C321-4041-B0ED-D55104B2C9B4 v6

The operation of the phase-selection element is primarily based on current change criteria (i.e.
delta quantities) with significantly increased dependability. To handle this, there is also a

Line distance protection REL670 319


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

phase selection criterion operating in parallel which bases its operation only on voltage and
current phasors.

This continuous criteria will, in the vast majority of cases, operate in parallel and carry on the
fault indication after the current change phase has ended. Only in some particularly difficult
faults on heavily loaded lines, the continuous criteria might not be sufficient, for example,
when the estimated fault impedance resides within the load area defined by the load
encroachment characteristic. In this case, the indication will be restricted to a pulse lasting for
one or two power system cycles.

The phase-selection element can, owing to the current change criteria, distinguish faults with
minimum influence from load and fault impedance. In other words, it is not restricted by a load
encroachment characteristic during the current change phase. This significantly improves
performance for remote phase-to-earth faults on heavily loaded lines. One exception, however,
are three-phase faults to which the load encroachment characteristic always has to be applied
in order to distinguish fault from load.

Phase-to-phase-earth faults (also called double earth faults) will practically always activate
phase-to-phase zone measurements. Measurement in two phase-to-earth loops at the same
time is associated with so-called simultaneous faults: two earth faults at the same time, one
each on the two circuits of a double line, or when the zero sequence current is relatively high
due to a source with low Z0/Z1 ratio. In these situations zone measurement will be released
both for the related phase-to-earth loops and the phase-to-phase loop simultaneously. On the
other hand, simultaneous faults closer to the remote bus will gradually take on the properties
of a phase-to-phase-earth fault and the function will eventually use phase-to-phase zone
measurements also here.

In cases where the fault current infeed is more or less completely of zero sequence nature (all
phase currents in phase), the measurement will be performed in the phase-to-earth loops only
for a phase-to-phase-earth fault.

AND
2-phase Fault
I3P detected by
Impedance/ current
2-phase fault
U3P PHSLy
based Phase AND
selection

PHSLxLy
AND

a
b
a>b
250%
OR
a
b a>b
50% AND OR

a
b
a<b
INMag
IL1Mag IN / Imax
IL2Mag
MAX
IL3Mag a ForcePE
b
a<b

INReleasePE

IEC17000230-1-en.vsdx

IEC17000230 V1 EN-US

Figure 164: Phase-selection logic

Figure 164 explains the release of two-phase faults (including simultaneous


faults as well as cross-country faults for high impedance earthed networks.
This is not valid for single-phase faults.

However, should it be desirable to use phase-to-earth (and only phase-to-earth) zone


measurement for phase-to-phase-earth faults, there is a setting INReleasePE that can be
lowered from its excessive default value to the level above which phase-to-earth measurement
should be activated.

320 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

8.11.7.4 Directional criteria GUID-24431EEC-5037-41CD-BC4A-7AC196F158F3 v5

Several criteria are employed when making the directional decision. The basis is provided by
comparing a positive sequence based polarizing voltage with phase currents. For extra
security, especially in making a very fast decision, this method is complemented with an
equivalent comparison where, instead of the phase current, the change in phase current is
used. Moreover, a basic negative sequence directional evaluation is taken into account as a
reliable reference during high load condition. Finally, a zero sequence directional evaluation is
used whenever there is more or less exclusive zero sequence in-feed.

The directional sectors that represent forward direction, one per measuring loop, are defined
by the following equations.

U PolL1
−15° < arg < 120°
I L1
IECEQUATION15059 V1 EN-US (Equation 68)

U PolL1L 2
−15° < arg < 120°
I L1L 2
IECEQUATION15060 V1 EN-US (Equation 69)

Where:
UPolL1 is the polarizing voltage for phase L1.

IL1 is the phase current in phase L1.

UPolL1L2 is the polarizing voltage difference between phase L1 and L2 (L2 lagging L1).

IL1L2 is the current difference between phase L1 and L2 (L2 lagging L1).

The corresponding reverse directional sectors range from 165 to -60 degrees.

Since the polarizing voltage is also used for the Mho distance characteristics, the magnitude
of the voltage is just as interesting as the phase. If there are symmetrical conditions and the
measured per phase positive sequence voltage magnitude is above 75% of the base voltage
before the fault, the pre-fault magnitude will be memorized and used as long as there is a
fault. The phase angle however will only be memorized (locked) for 75 ms at a time, not to lose
synchronism with the real system voltage.

Should the positive sequence voltage drop below 2% of the base voltage, it will be considered
invalid. In this situation, directional signals and starts from Mho elements will be sealed-in and
kept static as long as there is a fault.

For ZMFCPDIS, when option SeriesComp is chosen for OperationSC, the voltages of faulty
phases will be discarded in order not to affect the polarizing voltage with voltage reversal.

8.11.7.5 Fuse failure GUID-FA7B94D6-8BAF-4D05-8DC0-7FEBF0967D16 v3

The ZMFPDIS function has to be blocked by an additional function like the Fuse failure
supervision (FUFSPVC) or an equivalent external device. Typically, the binary input VTSZ is
used for this purpose.

A built-in supervision feature within high-speed distance protection itself, based on phase
current change, will ensure that the FUFSPVC blocking signal is received in time. Namely, an
intentional time delay will be introduced if no current magnitude change greater than 5% of
IBase has been detected for any of the three phase currents.

Line distance protection REL670 321


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

8.11.7.6 Power swings GUID-4DFED278-014F-46C2-B124-2E0809D12FC3 v2

There is need for external blocking of the ZMFPDIS function during power swings, either from
the Power Swing Blocking function (ZMRPSB) or an external device.

8.11.7.7 Measuring principles

Quadrilateral characteristic GUID-32E76D16-41ED-4CEF-B081-8413211AA783 v8


ZMFPDIS implements quadrilateral and mho characteristic in all the six zones separately. Set
OpModePEZx or OpModePPZx to Quadrilateral, to choose particular measuring loop in a zone
to work as quadrilateral distance protection.

All ZMFPDIS zones operate according to the non-directional impedance characteristics


presented in figure 166 and figure 165. The phase-to-earth characteristic is given in ohms-per-
loop domain while the phase-to-phase characteristic is given in ohms-per-phase domain.

The voltage and current phasors after the half-cycle filter are used in fault loop equations.

For phase-to-phase faults (Figure 167, lower part), the calculated impedances from the relay to
the fault Z calc  Rcalc  j  X calc follow Equation 70 (example is given for a phase L1 to phase L2
fault).

 
U L1  U L 2  I L1  I L 2  Z calc 
IECEQUATION18003 V1 EN-US (Equation 70)

Where and represents the corresponding voltage and current phasors in the respective
phase Ln (n = 1, 2, 3).

The calculated Rcalc and Xcalc are compared with the non-directional phase-to-phase
quadrilateral characteristics defined by the reactance reaches (X1PPZ1 or X1Zx, where x = 2 to 5
or RV), resistance reaches (R1PPZ1 or R1Zx, where x = 2 to 5 or RV) for the zones, as well as the
fault resistance reach setting for phase-to-phase loops (RFPPZx, where x = 1 to 5 or RV) as
shown in Figure 165. If is inside the non- directional phase-to-phase characteristic and the
phase selection algorithm enables this loop, the STNDZx output is set to TRUE.

For phase-to-earth faults (Figure 167, upper part), the earth return compensation applies
according to Equation 71 (example for a phase L1 to earth fault).

 
U L1  I L1  K N  3I 0  p  Z1  I F  RF
IECEQUATION18007 V1 EN-US (Equation 71)

Where,

p is the fault location and RF is the calculated fault resistance. p and RF are unknown and
needs to be solved.

is the zero-sequence current.

is the ground compensation factor and it is defined as:

Z 0  Z1
KN 
3  Z1
Z 0  R 0 Zx  j  X 0 Zx
Z1  R1Zx  j  X 1Zx
IECEQUATION18010 V1 EN-US

Where,

322 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

is the set complex zero sequence impedance of the line in Ω/phase.

is the set complex positive sequence impedance of the line in Ω/phase.

is the positive sequence reactance reach of the line in Ω/phase for phase-to-earth fault
for zone x (x = 1 to 5, or RV).

is the positive sequence resistive reach of the line in Ω/phase for phase-to-earth fault for
zone x (x = 1 to 5, or RV).

is the zero sequence reactance reach of the line in Ω/phase for zone x (x = 1 to 5, or RV).

is the zero sequence resistive reach of the line in Ω/phase for zone x (x = 1 to 5, or RV).

Table 190: Settings of positive and zero sequence impedances for different zones
Zones Pos. Seq. X Pos. Seq. R Zero. Seq. X Zero. Seq. R
Zone 1 X1PEZ1 R1PEZ1 X0Z1 R0Z1
Zone 2 X1Z2 R1Z2 X0Z2 R0Z2
Zone 3 X1Z3 R1Z3 X0Z3 R0Z3
Zone 4 X1Z4 R1Z4 X0Z4 R0Z4
Zone 5 X1Z5 R1Z5 X0Z5 R0Z5
Zone RV X1ZRV R1ZRV X0ZRV R0ZRV

is the fault current. It is chosen among phase, zero or negative sequence currents
automatically by the built-in adaptive load compensation algorithm.

The calculated impedances from the relay to the fault Z calc  Rcalc  j  X calc can be represented
as:
X calc  p  X 1Zx
IECEQUATION18017 V1 EN-US

Rcalc  p  R1Zx  RF
IECEQUATION18018 V1 EN-US

The calculated Rcalc and Xcalc are compared with the non-directional phase-to-earth
quadrilateral characteristics defined by the reactance reaches (X1PEZ1 or X1Zx, where x = 2 to 5
or RV), resistance reaches (R1PEZ1 or R1Zx, where x = 2 to 5 or RV) for the zones, as well as the
fault resistance reach setting for the phase-earth loops (RFPEZx, where x = 1 to 5 or RV) as
shown in Figure 166. If is inside the non-directional phase-to-earth characteristic and the
phase selection algorithm enables this loop, the STNDZx output is set to TRUE.

Zone 1 has individual positive sequence impedance settings for phase-to-phase and phase-to-
earth (X1PPZ1, R1PPZ1 and X1PEZ1, R1PEZ1). For the other zones, the positive sequence
impedance reach is common for phase-to-phase and phase-to-earth (X1Zx, R1Zx).

Line distance protection REL670 323


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

X (Ohm/phase)

RFPPZx R1Zx RFPPZx


2 2

X1Zx

R (Ohm/phase)

RFPPZx RFPPZx
2 2

X1Zx

RFPPZx R1Zx RFPPZx


2 2
IEC11000416-2-en.vsdx
IEC11000416 V2 EN-US

Figure 165: ZMFPDIS Characteristic for phase-to-phase measuring, ohm/loop domain

X (Ohm/loop)

R1Zx+RNZx

RFPEZx RFPEZx

X0Zx-X1Zx
XNZx=
3

X1Zx+XNZx R0Zx-R1Zx
RNZx=
3
φN φN
R (Ohm/loop)

RFPEZx RFPEZx

X1Zx+XNZx

RFPEZx RFPEZx

R1Zx+RNZx IEC11000415-2-en.vsdx
IEC11000415 V2 EN-US

Figure 166: ZMFPDIS Characteristic for phase-to-earth measuring, ohm/loop domain

324 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

The faulty loop in relation to the fault type can be presented as in figure 167. The main
intention with this illustration is to make clear how the fault resistive reach should be
interpreted and set. Note in particular that the setting RFPPZx always represents the total
fault resistance of the loop, regardless the fact that the fault resistance (arc) may be divided
into parts like for three-phase or phase-to-phase faults. The R1Zx + jX1Zx represent the
positive sequence impedance from the measuring point to the fault location.

IL1 R1Zx + j X1Zx


Phase-to-earth
UL1
element

Phase-to-earth
RFPEZx
fault in phase L1
(Arc + tower
resistance)

0
IN (R0Zx-R1Zx)/3 +
j (X0Zx-X1Zx)/3 )

IL1 R1Zx + j X1Zx Phase-to-phase


UL1 element L1-L2
Phase-to-phase
fault in phase RFPPZx
L1-L2 IL2
UL2 (Arc resistance)
R1Zx + j X1Zx

IL1 R1Zx + j X1Zx 0.5·RFPPZx Phase-to-phase


UL1 element L1-L3
Three-phase
fault or Phase-to-
phase-earth fault IL3
UL3
R1Zx + j X1Zx 0.5·RFPPZx
IEC11000419-3-en.vsdx
IEC11000419 V3 EN-US

Figure 167: Fault loop model


The zone impedance characteristic is a product of the two separate characteristics:

• The quadrilateral characteristic


• The directional characteristic

The estimated impedance needs to be inside both characteristics for the zone to start or trip.
(The non-directional start STND is an exception however. It is only dependent on the
quadrilateral characteristic.)

In the following figure, the zone with the shorter reactive reach follows the directional line
(R∙tan(15⁰)) only up to X1PP, where the quadrilateral characteristic will start to limit the reach.

Line distance protection REL670 325


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

X (ohm)

X1PP’

X1PP

15° R (ohm)
-X1PP RFPP/2
R· tan15°

-X1PP’
IEC19000141-1-en-us.vsdx

IEC19000141 V1 EN-US

Figure 168: Line distance protection

Mho characteristic GUID-9269239B-3A04-44CD-BE00-FD850D42836B v2


ZMFPDIS implements quadrilateral and mho characteristic in all the six zones separately. Set
OpModePEZx or OpModePPZx setting to Mho or Offset, to choose a particular measuring loop
in a zone to work as mho (or Offset Mho) distance protection.

Zones 3 to 5 can be selected to be either forward or reverse with positive sequence polarized
mho characteristic; alternatively self polarized offset mho characteristics. The operating
characteristic is in accordance to figure 169 where zone 5 is selected offset mho.

X
X

Z4
Z3
ZS=0
Z2
Z1 R
Z5 R

ZS=Z1
ZRV
ZS=2Z1

IEC15000056-1-en.vsdx

IEC15000056 V1 EN-US

Figure 169: Mho, offset mho characteristics and the source impedance influence on the
mho characteristic
The mho characteristic has a dynamic expansion due to the source impedance. Instead of
crossing the origin, as for the mho to the left of figure 169, which is only valid where the source
impedance (Zs) is zero, the crossing point is moved to the coordinates of the negative source
impedance given an expansion of the circle shown to the right of figure 169. Z1 denotes the
complex positive sequence impedance.

The magnitude of the polarizing voltage is determined completely by the positive sequence
voltage magnitude from before the fault. This will give a somewhat less dynamic expansion of

326 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

the mho circle during faults. However, if the source impedance is high, the dynamic expansion
of the mho circle might lower the security of the function too much with high loading and mild
power swing conditions.

Basic operation characteristics GUID-E6CC3CA7-72BE-40FC-A557-7BDB62F7BC1E v2


In ZMFPDIS, each zone measurement loop characteristic can be set to mho characteristic or
offset mho characteristic by setting OpModePEZx or OpModePPZx (where x is 1-5 depending
on selected zone).

ZMFPDIS fixes zone 1 and 2 in Forward mode and zone RV in Reverse mode. Zone 3-5 can be set
to Non-directional, Forward or Reverse by setting the parameter DirModeZx (where x is 3-5
depending on selected zone).

If DirModeZx (where x is 3-5 depending on selected zone) is selected as Non-directional, the


directional element will not have any effect on the measurement loop and operation of the
function. When DirModeZx (where x is 3-5 depending on selected zone) is selected as Forward
or Reverse, directional lines are introduced. Information about the directional lines is given
from the directional element. Basic Mho and offset Mho characteristics with different mode
settings are indicated in figure 170.

X X X
(a) Rset (b) (c) Rset

Xset Xset

R R R

Xset

(a)-(f)
Rset For phase-to-phase fault
Rset  R1Zx
Forward Reverse Non-directional
Xset  X 1Zx
Mho Characteristics For phase-to-earth fault
Rset  R1Zx  RNZx
Xset  X 1Zx  XNZx
(d) X
(e) X (f) X X 0 Zx  X 1Zx
XNZx 
3
R 0 Zx  R1Zx
RNZx 
Rset 3
Rset Rset

Xset Xset Xset

R R R

Xset Xset Xset

Rset Rset Rset

Forward Reverse Non-directional


Offset Mho Characteristics
(a) and (c) are for Zone 1, Zone 2 and Zone 3-5 when DirModeZ3-5 = Forward.
(b) and (d) are for ZoneRV and Zone 3-5 when DirModeZ3-5 = Reverse
(c) and (f) are for Zone 3-5 when DirModeZ3-5 = Non-Directional
IEC15000055-2-en.vsdx

IEC15000055 V2 EN-US

Figure 170: Mho and offset Mho characteristics


For each zone, the impedance is set in cartesian coordinates (resistance and reactance) which
is the same as for quadrilateral characteristic.

The ZMFPDIS function has only one set of reach setting so the reverse will be the same as for
the forward reach, meaning that the non-directional offset mho characteristic will always be
centered around the origin. In detail, for Zone 1, the resistive and reactance reaches for phase-

Line distance protection REL670 327


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

to-earth fault and phase-to-phase fault are set individually using the settings R1PPZ1, X1PPZ1,
R1PEZ1, X1PEZ1, X0Z1 and R0Z1. In Zone 2-5 and Zone RV, the same zone reach settings are
used for phase-to-earth fault and phase-to-phase (R1Zx, X1Zx, X0Zx and R0Zx, x=2-5 or RV).

Theory of operation SEMOD154224-46 v6


The mho algorithm is based on the phase comparison of an operating phasor and a polarizing
phasor. When the operating phasor leads the reference polarizing phasor by 90 degrees or
more, the function operates and gives a trip output.

Phase-to-phase fault SEMOD154224-240 v2


Mho GUID-D162893C-918A-4DDA-AAC2-0D0A814D85C1 v1
The plain Mho circle has the characteristic as in figure 171. The condition for deriving the angle
β is according to equation 72.

(
β = arg U L1L 2 − I L1L 2 ⋅ Z 1set − arg U pol ) ( )
IECEQUATION15027 V1 EN-US (Equation 72)

where

U L1L2 is the voltage vector difference between phases L1 and L2


EQUATION1790 V2
EN-US

I L1L2 is the current vector difference between phases L1 and L2


EQUATION1791
EN-US V2

is the positive sequence impedance setting for phase-to-phase fault in zone direction
Z 1set

For Zone 1,

Z 1set = R1PPZ 1 + j ⋅ X 1PPZ 1


IECEQUATION15011 V1 EN-US (Equation 73)

where
R1PPZ1 is the positive sequence resistive reach for phase-to-phase fault for zone 1
X1PPZ1 is the positive sequence reactance reach for phase-to-phase fault for zone 1

For Zone 2-5 and RV

Z 1set = R1Zx + j ⋅ X 1Zx


IECEQUATION15012 V1 EN-US (Equation 74)

where
R1Zx is the positive sequence resistive reach for zone x (x=2-5 and RV)
X1Zx is the positive sequence reactance reach for zone x (x=2-5 and RV)
is the polarizing voltage
Upol

Operation occurs if 90°≤β≤270°

328 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

IL1L2  jX

I L1L 2  Z1set
UcompUL1L2 IL1L2 Z1set

UL1L2

U pol

I L1L 2  R

IEC15000060-1-en.vsdx

IEC15000060 V1 EN-US

Figure 171: Simplified mho characteristic and vector diagram for phase L1-to-L2 fault
Offset Mho GUID-3E13E6D5-0832-4386-9677-9A40BFF42F8F v2

The characteristic for offset mho is a circle with origin as the center and magnitude of Z 1set
as the radius, where Z 1set is settable through the resistance and reactance settings.

The condition for operation at phase-to-phase fault is that the angle β between the two
compensated voltages is greater than or equal to 90° (figure 172). The angle will be 90° for
fault location on the boundary of the circle.

The angle β for L1 to L2 fault can be defined according to equation below.

 U 
L1L 2  I L1L 2  Z 1set
  arg  
 
 U L1L 2   I L1L 2  Z1set  

IECEQUATION15008 V2 EN-US (Equation 75)

Line distance protection REL670 329


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

I L1L 2  jX

U comp1  U L1L 2  I L1L 2  Z1set

I L1L 2  Z1set

U L1L 2

U comp 2  U L1L 2  ( I L1L 2  Z1set )

I L1L 2  R

I L1L 2  Z1set

IEC15000058-2-en.vsdx

IEC15000058 V2 EN-US

Figure 172: Simplified offset mho characteristic and voltage vector for phase L1 to L2
fault
Operation occurs if 90°≤β≤270 °.

Phase-to-earth fault GUID-DB8CF641-0D3F-4F7A-A628-829F3DB0AC5B


SEMOD154224-283 v2
v1
The measuring of earth faults uses earth return compensation applied in a conventional way.
The compensation voltage is derived by considering the influence from the earth return path.

Compensation for earth return path for faults involving earth is done by setting the positive
and zero sequence impedance of the line. It is known that the ground compensation factor KN
is,

Z 0set − Z 1set
KN =
3 ⋅ Z 1set
IECEQUATION15017 V1 EN-US

Z 0set = R 0Zx + j ⋅ X 0 Zx
IECEQUATION15018 V1 EN-US

For Zone 1,
Z 1set = R1PEZ 1 + j ⋅ X 1PEZ 1
IECEQUATION15019 V1 EN-US

For Zone 2-5 and RV,


Z 1set = R1Zx + j ⋅ X 1Zx
IECEQUATION15020 V1 EN-US (Equation 76)

330 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

where
is the complex zero sequence impedance of the line in Ω/phase
Z 0set
is the complex positive sequence impedance of the line in Ω/
Z 1set phase
R1PEZ1 is the positive sequence resistive reach of the line in Ω/phase
for phase-to-earth fault for zone 1
X1PEZ1 is the positive sequence reactance reach of the line in Ω/phase
for phase-to-earth fault for zone 1
R0Zx is the zero sequence resistive reach of the line in Ω/phase for
zone x (x=2-5, or RV)
X0Zx is the zero sequence reactance reach of the line in Ω/phase for
zone x (x=2-5, or RV)

For an earth fault in phase L1, the angle β between the compensation voltage and the

polarizing voltage Upol is,

β = arg [U L1 − ( I L1 + 3I 0 ⋅ K N ) ⋅ Z 1set ] − arg(U pol )


IECEQUATION15021 V1 EN-US (Equation 77)

where
is the phase voltage in faulty phase L1
UL1
is the phase current in faulty phase L1
IL1
3I0 is the zero-sequence current in faulty phase L1

is the complex positive sequence impedance of the line in Ω/


Z 1set phase for phase-to-earth fault in zone direction

is the polarizing voltage for phase L1


Upol

Line distance protection REL670 331


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

IL1•jX

UcompUL1 (IL1 3I0 KN )  Z1set


3I0KN Z1set

U L1
I L1  Z1set
U pol

IL1•R
IEC15000059-1-en.vsdx

IEC15000059 V1 EN-US

Figure 173: Simplified offset mho characteristic and vector diagram for phase L1-to-earth
fault
Operation occurs if 90°≤β≤270°.

Offset mho GUID-B1EF3931-7B86-4C7B-BCEA-3034482BA240 v3


The condition for operation of offset mho at phase-to-earth fault is that the angle β between
the two compensated voltages is equal to or greater than 90°, see figure 174. The angle will be
90° for fault location on the boundary of the circle.

   
  arg U L1  ( I L1  3I 0  K N )  Z1set  arg U L1   ( I L1  3I 0  K N )  Z1set 

IECEQUATION15022 V2 EN-US (Equation 78)

332 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

IL1• jX

U comp1  U L1  ( I L1  3I 0 K N ) Z1set


( I L1  3I 0 K N ) Z1set
U L1

U comp 2  U L1  (( I L1  3I 0 K N ) Z1set )

IL1• R

( I L1  3I 0 K N ) Z1set

IEC15000057-2-en.vsdx

IEC15000057 V2 EN-US

Figure 174: Simplified offset mho characteristic and voltage vector for phase L1-to-earth
fault
Operation occurs if 90 °≤β≤270 °.

8.11.7.8 Load encroachment GUID-6785BF05-2775-4422-8077-A663D01C6C07 v6

In some cases the measured load impedance might enter the set zone characteristic without
any fault on the protected line. This phenomenon is called load encroachment and it might
occur when an external fault is cleared and high emergency load is transferred onto the
protected line. The effect of load encroachment is illustrated on the left in figure 175. A load
impedance within the characteristic would cause an unwanted trip. The traditional way of
avoiding this situation is to set the distance zone resistive reach with a security margin to the
minimum load impedance. The drawback with this approach is that the sensitivity of the
protection to detect resistive faults is reduced.

The IED has a built in feature which shapes the characteristic according to the characteristic
shown in figure 175. The load encroachment algorithm will increase the possibility to detect
high fault resistances, especially for phase-to-earth faults at the remote line end. For example,
for a given setting of the load angle ArgLd, the resistive blinder for the zone measurement can
be set according to figure 175 affording higher fault resistance coverage without risk for
unwanted operation due to load encroachment. Separate resistive blinder settings are
available in forward and reverse direction.

Line distance protection REL670 333


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

The use of the load encroachment feature is essential for long heavily loaded lines, where there
might be a conflict between the necessary emergency load transfer and necessary sensitivity
of the distance protection. The function can also preferably be used on heavy loaded, medium
long lines. For short lines, the major concern is to get sufficient fault resistance coverage. Load
encroachment is not a major problem. .

Z1

ArgLd

[1]
RLdRv RLdFw

IEC09000248-3-en.vsdx
IEC09000248 V3 EN-US

Figure 175: Load encroachment phenomena and shaped load encroachment


characteristic
[1]

8.11.7.9 Simplified logic schemes GUID-B43F2F0B-C8A2-4CFD-A9DD-51E167A90B56 v5

PHSL1, PHSL2,...PHSL3L1 are internal binary logical signals from the Phase-selection element.
They correspond directly to the six loops of the distance zones and determine which loops
should be released to operate.

FWL1, FWL2,...FWL3L1 and RVL1, RVL2,...RVL3L1 are the internal binary signals from the
Directional element. An FW signal is activated if the criteria for a forward fault or load is
fulfilled for its particular loop. The equivalent applies to the reverse (RV) signals.

The internal input 'IN present' is activated if the residual current (3I0) exceeds 10% of the
maximum phase current magnitude and at the same time is above 5% of IBase. However, if
current transformer saturation is detected, this criterion is changed to residual voltage (3U0)
exceeding 5% of UBase/sqrt(3) instead.

[1] RLdRv=RLdRvFactor*RLdFw

334 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

FW(Ln & LmLn)

FW(Ln & LmLn)

RV(Ln & LmLn)

DirModeZ3-5
TRUE (1)
FW(Ln & LmLn) Forward
RV(Ln & LmLn) Reverse

IEC12000137-2-en.vsd
IEC12000137 V3 EN-US

Figure 176: Connection of directional signals to Zones

ZML1Zx PEZx
OR
PHSL1
AND

DIRL1Zx AND
ZML2Zx
PHSL2
AND

DIRL2Zx AND
ZML3Zx L1Zx
OR
PHSL3
AND

DIRL3Zx AND

ZML1L2Zx L2Zx
PHSL1L2 OR
AND

DIRL1L2Zx AND
ZML2L3Zx
PHSL2L3 L3Zx
AND OR
DIRL2L3Zx AND
ZML3L1Zx
PHSL3L1
AND

DIRL3L1Zx AND

L1N
PPZx
L2N OR
L3N
RELCNDZx Integer L1L2
to Bool
L2L3
NDZx
L1L3 OR

IEC12000140-2-en.vsdx
IEC12000140 V2 EN-US

Figure 177: Intermediate logic

Line distance protection REL670 335


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

TimerModeZx =
Enable PhPh or
Ph-E PhPh
PPZx AND tPPZx
OR AND
AND t
PEZx
AND tPEZx OR
OR
AND t
AND

BLOCK
VTSZ
BLKZx OR
BLKTRZx
OR TimerLinksZx
LoopLink (tPP-tPE)
ZoneLinkStart LoopLink & ZoneLink
OR
Phase Selection No Links
1st starting zone
External start FALSE (0)
LNKZ2
LNKZx
AND
OR
TimerLinksZx =
LNKZ4 LoopLink & ZoneLink
LNKZ5

EXTNST

IEC12000139-4-en.vsdx
IEC12000139 V4 EN-US

Figure 178: Logic for linking of timers

15 ms
TZx
t TRIPZx
AND

TRL1Zx
OR AND
BLOCK
VTSZ TRL2Zx
OR AND
BLKZx
TRL3Zx
AND
15 ms
L1Zx
t STL1Zx
AND
15 ms
L2Zx
t STL2Zx
AND
15 ms
t STL3Zx
AND

PPZx 15 ms
PEZx OR t STARTZx
AND

15 ms
NDZx
t STNDZx
AND

IEC12000138-2-en.vsd
IEC12000138 V2 EN-US

Figure 179: Start and trip outputs

336 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

15 ms
OR t STPE
AND

15 ms
OR t
AND

15 ms
OR t STNDL2
PHSL1L2 AND

15 ms
OR t STNDL3
AND

15 ms
OR t STPP
AND

BLOCK STARTND
OR
VTSZ OR

STPHS
STNDPE
AND

IEC12000133-3-en.vsdx
IEC12000133 V3 EN-US

Figure 180: Additional start outputs 1

PHSL1
FWL1 AND
15 ms
FWL2 AND OR t
AND

FWL3 AND 15 ms
PHSL1L2 OR t STFWL2
AND
FWL1L2 AND
PHSL2L3 15 ms
FWL2L3 AND OR t STFWL3
AND
FWL3L1 AND
OR
STFWPE
IN present AND

STFW1PH
=1
BLOCK
VTSZ OR

STFW2PH
=2

STFW3PH
=3

IEC12000134-2-en.vsd
IEC12000134 V2 EN-US

Figure 181: Additional start outputs 2

Line distance protection REL670 337


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

PHSL1
RVL1 AND
15 ms
RVL2 AND OR t
AND

RVL3 AND 15 ms
PHSL1L2 OR t STRVL2
AND
RVL1L2 AND
PHSL2L3 15 ms
RVL2L3 AND OR t STRVL3
AND
RVL3L1 AND
OR
STRVPE
IN present AND

BLOCK
VTSZ OR

IEC12000141-2-en.vsdx
IEC12000141 V2 EN-US

Figure 182: Additional start outputs 3

8.11.7.10 Measurement

Measurement supervision SEMOD54417-130 v4


The protection, control, and monitoring IEDs have functionality to measure and further
process information for currents and voltages obtained from the pre-processing blocks. The
number of processed alternate measuring quantities depends on the type of IED and built-in
options.

The information on measured quantities is available for the user at different locations:

• Locally by means of the local HMI


• Remotely using the monitoring tool within PCM600 or over the station bus
• Internally by connecting the analogue output signals to the Disturbance Report function

GUID-8568A19F-0100-4A1A-B3C3-444FD7D6F00B v1

X equals Z in the name of the below mentioned settings.

Zero point clamping GUID-4894EF16-3376-48EB-863F-9CE14487ACAB v1


Measured value below zero point clamping limit is forced to zero. This allows the noise in the
input signal to be ignored. The zero point clamping limit is a setting (XZeroDb where X equals
Z).

Continuous monitoring of the measured quantity SEMOD54417-140 v5


Users can continuously monitor the measured quantity available in the function block by
means of four defined operating thresholds, see figure 183. The monitoring has two different
modes of operating:

• Overfunction, when the measured quantity exceeds the High limit (XHiLim) or High-high
limit (XHiHiLim) pre-set values
• Underfunction, when the measured quantity decreases under the Low limit (XLowLim) or
Low-low limit (XLowLowLim) pre-set values.

338 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

X_RANGE is illustrated in figure 183.

Y = Magnitude of the Measured Quantity

X_RANGE = 3
High-high limit

X_RANGE= 1 Hysteresis
High limit

X_RANGE=0

X_RANGE=0 t

Low limit

X_RANGE=2

Low-low limit
X_RANGE=4

IEC05000657-3-en.vsdx
IEC05000657 V3 EN-US

Figure 183: Presentation of operating limits


Each analogue output has one corresponding supervision level output (X_RANGE). The output
signal is an integer in the interval 0-4 (0: Normal, 1: High limit exceeded, 3: High-high limit
exceeded, 2: below Low limit and 4: below Low-low limit).

The logical value of the functional output signals changes according to figure 183.

The user can set the hysteresis (XLimHyst), which determines the difference between the
operating and reset value at each operating point, in wide range for each measuring channel
separately. The hysteresis is common for all operating values within one channel.

Actual value of the measured quantity SEMOD54417-150 v4


The actual value of the measured quantity is available locally and remotely. The measurement
is continuous for each measured quantity separately, but the reporting of the value to the
higher levels depends on the selected reporting mode. The following basic reporting modes
are available:

• Cyclic reporting (Cyclic)


• Amplitude dead-band supervision (Dead band)
• Integral dead-band supervision (Int deadband)
• Amplitude Deadband and 5s cyclic
• Amplitude Deadband and 30s cyclic
• Amplitude Deadband and 1min cyclic

Cyclic reporting SEMOD54417-158 v3


The cyclic reporting of measured value is performed according to chosen setting (XRepTyp).
The measuring channel reports the value independent of amplitude or integral dead-band
reporting.

In addition to the normal cyclic reporting the IED also report spontaneously when measured
value passes any of the defined threshold limits.

Line distance protection REL670 339


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Y
Value Reported Value Reported
Value Reported Value Reported
(1st)

Y3 Value Reported
Y2 Y4

Y1 Y5

t (*) t (*) t (*) t (*)

t
Value 1

Value 2

Value 3

Value 4

Value 5
(*)Set value for t: XDbRepInt IEC05000500-2-en.vsdx

IEC05000500 V2 EN-US

Figure 184: Periodic reporting

Amplitude dead-band supervision SEMOD54417-163 v6


If a measuring value is changed, compared to the last reported value, and the change is larger
than the ±ΔY pre-defined limits that are set by user (XDbRepInt), then the measuring channel
reports the new value to a higher level. This limits the information flow to a minimum
necessary. Figure 185 shows an example with the amplitude dead-band supervision. The
picture is simplified: the process is not continuous but the values are evaluated with a time
interval of one execution cycle from each other.

340 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Value Reported
Y

Value Reported Value Reported


Value Reported
(1st)
Y3 Y
Y
Y2 Y
Y
Y
Y
Y1

IEC99000529-2-en.vsdx

IEC99000529 V2 EN-US

Figure 185: Amplitude dead-band supervision reporting


After the new value is reported, the ±ΔY limits for dead-band are automatically set around it.
The new value is reported only if the measured quantity changes more than defined by the ±ΔY
set limits.

Integral dead-band reporting SEMOD54417-167 v4


The measured value is reported if the time integral of all changes exceeds the pre-set limit
(XDbRepInt), figure 186, where an example of reporting with integral dead-band supervision is
shown. The picture is simplified: the process is not continuous but the values are evaluated
with a time interval of one execution cycle from each other.

The last value reported, Y1 in figure 186 serves as a basic value for further measurement. A
difference is calculated between the last reported and the newly measured value and is
multiplied by the time increment (discrete integral). The absolute values of these integral
values are added until the pre-set value is exceeded. This occurs with the value Y2 that is
reported and set as a new base for the following measurements (as well as for the values Y3,
Y4 and Y5).

The integral dead-band supervision is particularly suitable for monitoring signals with small
variations that can last for relatively long periods.

Line distance protection REL670 341


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Y A1 >=
A >= pre-set value
A2 >=
pre-set value pre-set value
Y3 A3 + A4 + A5 + A6 + A7 >=
pre-set value
Y2 A1 A2
A4 A6
Value Reported Y4 A3 A5 A7
Value
(1st) Value
A Reported Y5
Reported Value
Reported Value
Y1 Reported

t
IEC99000530-2-en.vsdx

IEC99000530 V2 EN-US

Figure 186: Reporting with integral dead-band supervision

Measurement ZMMMXU GUID-2DB6F5A4-A3C2-4BBA-8327-393B7F89EDC6 v4


The magnitude and angle of the impedance for each phase-to-earth and phase-to-phase loop
are available on local HMI, monitoring tools within PCM600 or to the station level, for example,
via IEC61850.

Phase-to-earth impedance measurement is calculated based on UL1/ IL1 , UL2 / IL2 , UL3 / IL3

and phase-to-phase impedance is calculated based on U L1 


 UL 2 / IL1  IL 2 ,
U L2 
 UL 3 / IL 2  IL 3  , U
L3 
 UL1 / IL 3  IL1  , where U LX and ILX are phase-to-earth
voltage and phase current.

When the operating current is too low, the impedance measurement can be erroneous. To
avoid such error, minimum operating current will be checked. For phase-earth currents or
phase-phase currents lower than 2% of IBase, the resistance and reactance of the impedance
are forced to 99 999 ohm, corresponding to a magnitude at 141419 (99 999*√2) ohm and an
angle at 45 degree.

342 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

8.11.8 Technical data


GUID-6C2EF52A-8166-4A23-9861-38931682AA7D v7

Table 191: ZMFPDIS, ZMFCPDIS technical data


Function Range or value Accuracy
Number of zones 3 selectable -
directions, 3 fixed
directions
Minimum operate current, Ph- (5-6000)% of IBase ±1.0% of Ir
Ph and Ph-E
Positive sequence reactance (0.01 - 3000.00) Pseudo continuous
reach, Ph-E and Ph-Ph loop ohm/p ramp:
±2.0% of set value
Positive sequence resistance (0.00 - 1000.00) Conditions:
reach, Ph-E and Ph-Ph loop ohm/p Voltage range: (0.1-1.1) x Ramp of shots:
Zero sequence reactance (0.01 - 9000.00) Ur ±2.0% of set value
reach ohm/p Current range: (0.5-30) x Conditions:
Ir IEC 60255-121 point B
Zero sequence resistive reach (0.00 - 3000.00) Angle: At 0 degrees and
ohm/p 85 degrees
Fault resistance reach, Ph-E (0.01 -9000.00) IEC 60255-121 points
and Ph-Ph ohm/l A,B,C,D,E

Dynamic overreach < 5% at 85 degrees -


measured with CVTs
and 0.5 < SIR < 30,
IEC 60255-121
Reset ratio 105% typically -
Directional blinders Forward: -15 – 120 Pseudo continuous ramp:
degrees ±2.0 degrees, IEC 60255-121
Reverse: 165 – -60
degrees
Resistance determining the (0.01 - 5000.00) Pseudo continuous Ramp of shots:
load impedance area - forward ohm/p ramp: ±5.0% of set value
±2.0% of set value Conditions:
Conditions: Tested at ArgLd = 30
Tested at ArgLd = 30 degrees
degrees
Angle determining the load 5 - 70 degrees Pseudo continuous ramp:
impedance area ±2.0 degrees
Conditions:
Tested at RLdFw = 20 ohm/p
Definite time delay to trip, Ph- (0.000-60.000) s ±0.2% of set value or ±35 ms whichever is greater
E and Ph-Ph operation
Operate time 16 ms typically, IEC -
60255-121
Reset time at 0.1 to 2 x Zreach Min. = 20 ms -
Max. = 35 ms

Line distance protection REL670 343


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

8.12 High speed distance protection for series


compensated lines ZMFCPDIS GUID-ED71CF5A-1453-4F2F-9C64-3A73C59EA948 v4

8.12.1 Identification GUID-0F03DA72-0687-4762-91CB-EC8E59B86E06 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
High speed distance protection zone ZMFCPDIS 21
(zone 1-6)
Z
S00346 V2 EN-US

8.12.2 Functionality GUID-C5C1ADD8-50A5-4485-848C-77D2222B56DC v8

High speed distance protection (ZMFCPDIS) provides sub-cycle, down towards half-cycle,
operate time for basic faults within 60% of the line length and up to around SIR 5. At the same
time, it is specifically designed for extra care during difficult conditions in high voltage
transmission networks, like faults on long heavily loaded lines and faults generating heavily
distorted signals. These faults are handled with utmost security and dependability, although
sometimes with reduced operating speed.

High speed distance protection ZMFCPDIS is fundamentally the same function as ZMFPDIS but
provides more flexibility in zone settings to suit more complex applications, such as series
compensated lines. In operation for series compensated networks, the parameters of the
directional function are altered to handle voltage reversal.

The ZMFCPDIS function is a six-zone full scheme protection with three fault loops for phase-
to-phase faults and three fault loops for phase-to-earth faults for each of the independent
zones, which makes the function suitable in applications with single-phase autoreclosing.

In each measurement zone, ZMFCPDIS function is designed with the flexibility to operate in
either quadrilateral or mho characteristic mode for separate phase-to-ground or phase-to-
phase loops.

The zones can operate independently of each other. Zones 3 to 5 in directional (forward or
reverse) or non-directional mode. Zone1 and zone2 are designed to measure in forward
direction only, while one zone (ZRV) is designed to measure in the reverse direction. This
makes them suitable, together with a communication scheme, for protection of power lines
and cables in complex network configurations, such as parallel lines, multi-terminal lines, and
so on.

A new built-in adaptive load compensation algorithm prevents overreaching of the distance
zones in the load exporting end during phase-to-earth faults on heavily loaded power lines. It
also reduces underreach in the importing end.

The ZMFCPDIS function block incorporates a phase-selection element and a directional


element, contrary to previous designs in the IED series, where these elements were
represented with separate function blocks.

The operation of the phase-selection element is primarily based on current change criteria,
with significant increased dependability. There is also a part operating with continuous
criteria that operates in parallel.

The directional element utilizes a set of well-established quantities to provide fast and correct
directional evaluation during various conditions, including close-in three-phase faults,
simultaneous faults and faults with only zero-sequence in-feed.

344 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

The ZMFCPDIS function has another transient components based directional element with
phase segregated outputs STTDFwLx and STTDRVLx (where, x = 1-3), which are intended for
permissive overreaching transfer trip (POTT) scheme. It provides directionality with high
speed, dependability and security, which is also suitable for extra high voltage and series
compensated lines where the fundamental frequency signals are distorted.

8.12.3 Function block GUID-CBB51E18-15E5-4BC5-A002-6371A6DC725A v1

ZMFCPDIS
I3P* TRIP
U3P* TRZ1
BLOCK TRL1Z1
VTSZ TRL2Z1
BLKZ1 TRL3Z1
BLKZ2 TRZ2
BLKZ3 TRL1Z2
BLKZ4 TRL2Z2
BLKZ5 TRL3Z2
BLKZRV TRZ3
BLKTRZ1 TRZ4
BLKTRZ2 TRZ5
BLKTRZ3 TRZRV
BLKTRZ4 START
BLKTRZ5 STZ1
BLKTRZRV STNDZ1
BLKTD STZ2
EXTNST STL1Z2
RELCNDZ1 STL2Z2
RELCNDZ2 STL3Z2
RELCNDZ3 STNDZ2
RELCNDZ4 STZ3
RELCNDZ5 STNDZ3
RELCNDZRV STZ4
STNDZ4
STZ5
STNDZ5
STZRV
STL1ZRV
STL2ZRV
STL3ZRV
STNDZRV
STND
STNDL1
STNDL2
STNDL3
STNDPE
STFWL1
STFWL2
STFWL3
STFWPE
STRVL1
STRVL2
STRVL3
STRVPE
STFW1PH
STFW2PH
STFW3PH
STPE
STPP
STTDFWL1
STTDFWL2
STTDFWL3
STTDRVL1
STTDRVL2
STTDRVL3
IEC11000422-5-en.vsdx
IEC11000422 V5 EN-US

Figure 187: ZMFCPDIS function block

Line distance protection REL670 345


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

8.12.4 Signals
PID-7163-INPUTSIGNALS v1

Table 192: ZMFCPDIS Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Blocks and resets timers and outputs of entire function
VTSZ BOOLEAN 0 Blocks and resets timers and outputs of entire function
BLKZ1 BOOLEAN 0 Blocks and resets zone 1 timers and outputs
BLKZ2 BOOLEAN 0 Blocks and resets zone 2 timers and outputs
BLKZ3 BOOLEAN 0 Blocks and resets zone 3 timers and outputs
BLKZ4 BOOLEAN 0 Blocks and resets zone 4 timers and outputs
BLKZ5 BOOLEAN 0 Blocks and resets zone 5 timers and outputs
BLKZRV BOOLEAN 0 Blocks and resets reverse zone timers and outputs
BLKTRZ1 BOOLEAN 0 Blocks and resets zone 1 timers and trip outputs
BLKTRZ2 BOOLEAN 0 Blocks and resets zone 2 timers and trip outputs
BLKTRZ3 BOOLEAN 0 Blocks and resets zone 3 timers and trip outputs
BLKTRZ4 BOOLEAN 0 Blocks and resets zone 4 timers and trip outputs
BLKTRZ5 BOOLEAN 0 Blocks and resets zone 5 timers and trip outputs
BLKTRZRV BOOLEAN 0 Blocks and resets reverse zone timers and trip outputs
BLKTD BOOLEAN 0 Blocks transient direction outputs
EXTNST BOOLEAN 0 External start of zone timers
RELCNDZ1 INTEGER 127 Release word for the measuring loops of zone 1
RELCNDZ2 INTEGER 127 Release word for the measuring loops of zone 2
RELCNDZ3 INTEGER 127 Release word for the measuring loops of zone 3
RELCNDZ4 INTEGER 127 Release word for the measuring loops of zone 4
RELCNDZ5 INTEGER 127 Release word for the measuring loops of zone 5
RELCNDZRV INTEGER 127 Release word for the measuring loops of zone RV

PID-7163-OUTPUTSIGNALS v1

Table 193: ZMFCPDIS Output signals


Name Type Description
TRIP BOOLEAN Trip in any phase or phases from any zone or zones
TRZ1 BOOLEAN Trip in any phase or phases from zone 1 - forward direction
TRL1Z1 BOOLEAN Trip in phase L1 from zone 1 - forward direction
TRL2Z1 BOOLEAN Trip in phase L2 from zone 1 - forward direction
TRL3Z1 BOOLEAN Trip in phase L3 from zone 1 - forward direction
TRZ2 BOOLEAN Trip in any phase or phases from zone 2 - forward direction
TRL1Z2 BOOLEAN Trip in phase L1 from zone 2 - forward direction
TRL2Z2 BOOLEAN Trip in phase L2 from zone 2 - forward direction
TRL3Z2 BOOLEAN Trip in phase L3 from zone 2 - forward direction
Table continues on next page

346 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Name Type Description


TRZ3 BOOLEAN Trip in any phase or phases from zone 3 - zone direction
TRZ4 BOOLEAN Trip in any phase or phases from zone 4 - zone direction
TRZ5 BOOLEAN Trip in any phase or phases from zone 5 - zone direction
TRZRV BOOLEAN Trip in any phase or phases from zone RV - reverse direction
START BOOLEAN Start in any phase or phases from any zone or zones
STZ1 BOOLEAN Start in any phase or phases from zone 1 - forward direction
STNDZ1 BOOLEAN Start in any phase or phases from zone 1 - any direction
STZ2 BOOLEAN Start in any phase or phases from zone 2 - forward direction
STL1Z2 BOOLEAN Start in phase L1 from zone 2 - forward direction
STL2Z2 BOOLEAN Start in phase L2 from zone 2 - forward direction
STL3Z2 BOOLEAN Start in phase L3 from zone 2 - forward direction
STNDZ2 BOOLEAN Start in any phase or phases from zone 2 - any direction
STZ3 BOOLEAN Start in any phase or phases from zone 3 - zone direction
STNDZ3 BOOLEAN Start in any phase or phases from zone 3 - any direction
STZ4 BOOLEAN Start in any phase or phases from zone 4 - zone direction
STNDZ4 BOOLEAN Start in any phase or phases from zone 4 - any direction
STZ5 BOOLEAN Start in any phase or phases from zone 5 - zone direction
STNDZ5 BOOLEAN Start in any phase or phases from zone 5 - any direction
STZRV BOOLEAN Start in any phase or phases from zone RV - reverse direction
STL1ZRV BOOLEAN Start in phase L1 from zone RV - reverse direction
STL2ZRV BOOLEAN Start in phase L2 from zone RV - reverse direction
STL3ZRV BOOLEAN Start in phase L3 from zone RV - reverse direction
STNDZRV BOOLEAN Start in any phase or phases from zone RV - any direction
STND BOOLEAN Fault detected in any phase or phases - any direction
STNDL1 BOOLEAN Fault detected in phase L1 - any direction
STNDL2 BOOLEAN Fault detected in phase L2 - any direction
STNDL3 BOOLEAN Fault detected in phase L3 - any direction
STNDPE BOOLEAN Fault with earth connection detected in any phase or phases -
any direction
STFWL1 BOOLEAN Fault detected in phase L1 - forward direction
STFWL2 BOOLEAN Fault detected in phase L2 - forward direction
STFWL3 BOOLEAN Fault detected in phase L3 - forward direction
STFWPE BOOLEAN Fault with earth connection detected - forward direction
STRVL1 BOOLEAN Fault detected in phase L1 - reverse direction
STRVL2 BOOLEAN Fault detected in phase L2 - reverse direction
STRVL3 BOOLEAN Fault detected in phase L3 - reverse direction
STRVPE BOOLEAN Fault with earth connection detected - reverse direction
STFW1PH BOOLEAN Single-phase fault detected - forward direction
STFW2PH BOOLEAN Two-phase fault detected - forward direction
STFW3PH BOOLEAN Three-phase fault detected - forward direction
STPE BOOLEAN Ph-E zone measurement enabled - any direction
STPP BOOLEAN Ph-Ph zone measurement enabled - any direction
Table continues on next page

Line distance protection REL670 347


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Name Type Description


STTDFWL1 BOOLEAN Fault detected in phase L1 by transient directional element -
forward direction
STTDFWL2 BOOLEAN Fault detected in phase L2 by transient directional element -
forward direction
STTDFWL3 BOOLEAN Fault detected in phase L3 by transient directional element -
forward direction
STTDRVL1 BOOLEAN Fault detected in phase L1 by transient directional element -
reverse direction
STTDRVL2 BOOLEAN Fault detected in phase L2 by transient directional element -
reverse direction
STTDRVL3 BOOLEAN Fault detected in phase L3 by transient directional element -
reverse direction

8.12.5 Settings
PID-7163-SETTINGS v1

Table 194: ZMFCPDIS Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups
ZDbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
ZMax 0.0 - 5000.0 Ohm 0.1 1500.0 Maximum value in ohm
ZRepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband
Dead band & 5s
Cyclic
Dead band & 30s
Cyclic
Dead band & 1min
Cyclic
ZAngDbRepInt 1 - 100000 Type 1 10 Cyclic report interval (s)

Table 195: ZMFCPDIS Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
OperationSC NoSeriesComp - - NoSeriesComp Selection of series compensation
SeriesComp operation Off / On
RLdFw 0.01 - 5000.00 Ohm/p 0.01 60.00 Resistance determining the load
impedance area - forward
RLdRvFactor 1 - 1000 %RLdF 1 100 Resistance factor determining the
w load impedance area - reverse
XLd 0.01 - 10000.00 Ohm/p 0.01 400.00 Reactance determining the load
impedance area
ArgLd 5 - 70 Deg 1 30 Angle determining the load
impedance area
CVTType Any - - Passive type CVT selection determining the
Passive type filtering of the function
None (Magnetic)
Table continues on next page

348 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Name Values (Range) Unit Step Default Description


OpModePPZ1 Off - - Quadrilateral On/Off and characteristic setting for
Quadrilateral Ph-Ph loops, zone 1
Mho
MhoOffset
OpModePEZ1 Off - - Quadrilateral On/Off and characteristic setting for
Quadrilateral Ph-E loops, zone 1
Mho
MhoOffset
X1FwPPZ1 0.01 - 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach,
Ph-Ph, zone 1, forward direction
R1FwPPZ1 0.00 - 1000.00 Ohm/p 0.01 5.00 Positive sequence resistive reach, Ph-
Ph, zone 1, forward direction
RFPPZ1 0.01 - 9000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, zone 1
X1RvPPZ1 0.01 - 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach,
Ph-Ph, zone 1, reverse direction
X1FwPEZ1 0.01 - 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach,
Ph-E, zone 1, forward direction
R1FwPEZ1 0.00 - 1000.00 Ohm/p 0.01 5.00 Positive sequence resistive reach, Ph-
E, zone 1, forward direction
X0FwPEZ1 0.01 - 9000.00 Ohm/p 0.01 100.00 Zero sequence reactance reach, Ph-E,
zone 1, forward direction
R0FwPEZ1 0.00 - 3000.00 Ohm/p 0.01 15.00 Zero sequence resistive reach, Ph-E,
zone 1, forward direction
RFPEZ1 0.01 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-E, zone 1
X1RvPEZ1 0.01 - 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach,
Ph-E, zone 1, reverse direction
tPPZ1 0.000 - 60.000 s 0.001 0.000 Time delay to trip, Phase-Phase, zone
1
tPEZ1 0.000 - 60.000 s 0.001 0.000 Time delay to trip, Phase-Earth, zone 1
IMinOpPPZ1 10 - 6000 %IB 1 10 Minimum operate Ph-Ph current for
Phase-Phase loops, zone 1
IMinOpPEZ1 5 - 6000 %IB 1 10 Minimum operate phase current for
Phase-Earth loops, zone 1
OpModePPZ2 Off - - Quadrilateral On/Off and characteristic setting for
Quadrilateral Ph-Ph loops, zone 2
Mho
MhoOffset
OpModePEZ2 Off - - Quadrilateral On/Off and characteristic setting for
Quadrilateral Ph-E loops, zone 2
Mho
MhoOffset
X1FwPPZ2 0.01 - 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach,
Ph-Ph, zone 2, forward direction
R1FwPPZ2 0.00 - 1000.00 Ohm/p 0.01 5.00 Positive sequence resistive reach, Ph-
Ph, zone 2, forward direction
RFPPZ2 0.01 - 9000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, zone 2
X1RvPPZ2 0.01 - 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach,
Ph-Ph, zone 2, reverse direction
X1FwPEZ2 0.01 - 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach,
Ph-E, zone 2, forward direction
R1FwPEZ2 0.00 - 1000.00 Ohm/p 0.01 5.00 Positive sequence resistive reach, Ph-
E, zone 2, forward direction
Table continues on next page

Line distance protection REL670 349


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Name Values (Range) Unit Step Default Description


X0FwPEZ2 0.01 - 9000.00 Ohm/p 0.01 120.00 Zero sequence reactance reach, Ph-E,
zone 2, forward direction
R0FwPEZ2 0.00 - 3000.00 Ohm/p 0.01 15.00 Zero sequence resistive reach, Ph-E,
zone 2, forward direction
RFPEZ2 0.01 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-E, zone 2
X1RvPEZ2 0.01 - 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach,
Ph-E, zone 2, reverse direction
tPPZ2 0.000 - 60.000 s 0.001 0.400 Time delay to trip, Phase-Phase, zone
2
tPEZ2 0.000 - 60.000 s 0.001 0.400 Time delay to trip, Phase-Earth, zone 2
IMinOpPPZ2 10 - 6000 %IB 1 10 Minimum operate Ph-Ph current for
Phase-Phase loops, zone 2
IMinOpPEZ2 5 - 6000 %IB 1 10 Minimum operate phase current for
Phase-Earth loops, zone 2
OpModePPZ3 Off - - Quadrilateral On/Off and characteristic setting for
Quadrilateral Ph-Ph loops, zone 3
Mho
MhoOffset
OpModePEZ3 Off - - Quadrilateral On/Off and characteristic setting for
Quadrilateral Ph-E loops, zone 3
Mho
MhoOffset
DirModeZ3 Non-directional - - Forward Direction of zone 3
Forward
Reverse
X1FwPPZ3 0.01 - 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach,
Ph-Ph, zone 3, zone direction
R1FwPPZ3 0.00 - 1000.00 Ohm/p 0.01 5.00 Positive sequence resistive reach, Ph-
Ph, zone 3, zone direction
RFFwPPZ3 0.01 - 9000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, zone 3,
zone direction
X1RvPPZ3 0.01 - 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach,
Ph-Ph, zone 3, opposite to zone dir
RFRvPPZ3 0.01 - 9000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, zone 3,
opposite to zone direction
X1FwPEZ3 0.01 - 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach,
Ph-E, zone 3, zone direction
R1FwPEZ3 0.00 - 1000.00 Ohm/p 0.01 5.00 Positive sequence resistive reach, Ph-
E, zone 3, zone direction
X0FwPEZ3 0.01 - 9000.00 Ohm/p 0.01 120.00 Zero sequence reactance reach, Ph-E,
zone 3, zone direction
R0FwPEZ3 0.00 - 3000.00 Ohm/p 0.01 15.00 Zero sequence resistive reach, Ph-E,
zone 3, zone direction
RFFwPEZ3 0.01 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-E, zone 3,
zone direction
X1RvPEZ3 0.01 - 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach,
Ph-E, zone 3, opposite to zone dir
RFRvPEZ3 0.01 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-E, zone 3,
opposite to zone direction
tPPZ3 0.000 - 60.000 s 0.001 0.800 Time delay to trip, Phase-Phase, zone
3
tPEZ3 0.000 - 60.000 s 0.001 0.800 Time delay to trip, Phase-Earth, zone 3
Table continues on next page

350 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Name Values (Range) Unit Step Default Description


IMinOpPPZ3 10 - 6000 %IB 1 10 Minimum operate Ph-Ph current for
Phase-Phase loops, zone 3
IMinOpPEZ3 5 - 6000 %IB 1 10 Minimum operate phase current for
Phase-Earth loops, zone 3
OpModePPZ4 Off - - Quadrilateral On/Off and characteristic setting for
Quadrilateral Ph-Ph loops, zone 4
Mho
MhoOffset
OpModePEZ4 Off - - Quadrilateral On/Off and characteristic setting for
Quadrilateral Ph-E loops, zone 4
Mho
MhoOffset
DirModeZ4 Non-directional - - Forward Direction of zone 4
Forward
Reverse
X1FwPPZ4 0.01 - 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach,
Ph-Ph, zone 4, zone direction
R1FwPPZ4 0.00 - 1000.00 Ohm/p 0.01 5.00 Positive sequence resistive reach, Ph-
Ph, zone 4, zone direction
RFFwPPZ4 0.01 - 9000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, zone 4,
zone direction
X1RvPPZ4 0.01 - 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach,
Ph-Ph, zone 4, opposite to zone dir
RFRvPPZ4 0.01 - 9000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, zone 4,
opposite to zone direction
X1FwPEZ4 0.01 - 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach,
Ph-E, zone 4, zone direction
R1FwPEZ4 0.00 - 1000.00 Ohm/p 0.01 5.00 Positive sequence resistive reach, Ph-
E, zone 4, zone direction
X0FwPEZ4 0.01 - 9000.00 Ohm/p 0.01 120.00 Zero sequence reactance reach, Ph-E,
zone 4, zone direction
R0FwPEZ4 0.00 - 3000.00 Ohm/p 0.01 15.00 Zero sequence resistive reach, Ph-E,
zone 4, zone direction
RFFwPEZ4 0.01 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-E, zone 4,
zone direction
X1RvPEZ4 0.01 - 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach,
Ph-E, zone 4, opposite to zone dir
RFRvPEZ4 0.01 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-E, zone 4,
opposite to zone direction
tPPZ4 0.000 - 60.000 s 0.001 1.200 Time delay to trip, Phase-Phase, zone
4
tPEZ4 0.000 - 60.000 s 0.001 1.200 Time delay to trip, Phase-Earth, zone 4
IMinOpPPZ4 10 - 6000 %IB 1 10 Minimum operate Ph-Ph current for
Phase-Phase loops, zone 4
IMinOpPEZ4 5 - 6000 %IB 1 10 Minimum operate phase current for
Phase-Earth loops, zone 4
OpModePPZ5 Off - - Quadrilateral On/Off and characteristic setting for
Quadrilateral Ph-Ph loops, zone 5
Mho
MhoOffset
OpModePEZ5 Off - - Quadrilateral On/Off and characteristic setting for
Quadrilateral Ph-E loops, zone 5
Mho
MhoOffset
Table continues on next page

Line distance protection REL670 351


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Name Values (Range) Unit Step Default Description


DirModeZ5 Non-directional - - Forward Direction of zone 5
Forward
Reverse
X1FwPPZ5 0.01 - 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach,
Ph-Ph, zone 5, zone direction
R1FwPPZ5 0.00 - 1000.00 Ohm/p 0.01 5.00 Positive sequence resistive reach, Ph-
Ph, zone 5, zone direction
RFFwPPZ5 0.01 - 9000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, zone 5,
zone direction
X1RvPPZ5 0.01 - 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach,
Ph-Ph, zone 5, opposite to zone dir
RFRvPPZ5 0.01 - 9000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, zone 5,
opposite to zone direction
X1FwPEZ5 0.01 - 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach,
Ph-E, zone 5, zone direction
R1FwPEZ5 0.00 - 1000.00 Ohm/p 0.01 5.00 Positive sequence resistive reach, Ph-
E, zone 5, zone direction
X0FwPEZ5 0.01 - 9000.00 Ohm/p 0.01 120.00 Zero sequence reactance reach, Ph-E,
zone 5, zone direction
R0FwPEZ5 0.00 - 3000.00 Ohm/p 0.01 15.00 Zero sequence resistive reach, Ph-E,
zone 5, zone direction
RFFwPEZ5 0.01 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-E, zone 5,
zone direction
X1RvPEZ5 0.01 - 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach,
Ph-E, zone 5, opposite to zone dir
RFRvPEZ5 0.01 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-E, zone 5,
opposite to zone direction
tPPZ5 0.000 - 60.000 s 0.001 1.600 Time delay to trip, Phase-Phase, zone
5
tPEZ5 0.000 - 60.000 s 0.001 1.600 Time delay to trip, Phase-Earth, zone 5
IMinOpPPZ5 10 - 6000 %IB 1 10 Minimum operate Ph-Ph current for
Phase-Phase loops, zone 5
IMinOpPEZ5 5 - 6000 %IB 1 10 Minimum operate phase current for
Phase-Earth loops, zone 5
OpModePPZRV Off - - Quadrilateral On/Off and characteristic setting for
Quadrilateral Ph-Ph loops, zone RV
Mho
MhoOffset
OpModePEZRV Off - - Quadrilateral On/Off and characteristic setting for
Quadrilateral Ph-E loops, zone RV
Mho
MhoOffset
X1FwPPZRV 0.01 - 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach,
Ph-Ph, zone RV, reverse direction
R1FwPPZRV 0.00 - 1000.00 Ohm/p 0.01 5.00 Positive sequence resistive reach, Ph-
Ph, zone RV, reverse direction
RFPPZRV 0.01 - 9000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, zone RV
X1RvPPZRV 0.01 - 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach,
Ph-Ph, zone RV, forward direction
X1FwPEZRV 0.01 - 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach,
Ph-E, zone RV, reverse direction
R1FwPEZRV 0.00 - 1000.00 Ohm/p 0.01 5.00 Positive sequence resistive reach, Ph-
E, zone RV, reverse direction
Table continues on next page

352 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Name Values (Range) Unit Step Default Description


X0FwPEZRV 0.01 - 9000.00 Ohm/p 0.01 120.00 Zero sequence reactance reach, Ph-E,
zone RV, reverse direction
R0FwPEZRV 0.00 - 3000.00 Ohm/p 0.01 15.00 Zero sequence resistive reach, Ph-E,
zone RV, reverse direction
RFPEZRV 0.01 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-E, zone RV
X1RvPEZRV 0.01 - 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach,
Ph-E, zone RV, forward direction
tPPZRV 0.000 - 60.000 s 0.001 0.000 Time delay to trip, Phase-Phase, zone
RV
tPEZRV 0.000 - 60.000 s 0.001 0.000 Time delay to trip, Phase-Earth, zone
RV
IMinOpPPZRV 10 - 6000 %IB 1 10 Minimum operate Ph-Ph current for
Phase-Phase loops, zone RV
IMinOpPEZRV 5 - 6000 %IB 1 10 Minimum operate phase current for
Phase-Earth loops, zone RV

Table 196: ZMFCPDIS Non group settings (advanced)


Name Values (Range) Unit Step Default Description
ZZeroDb 0 - 100000 m% 100 0 Magnitude zero point clamping in
0,001% of range
ZHiHiLim 0.0 - 5000.0 Ohm 0.1 800.0 High High limit in ohm
ZHiLim 0.0 - 5000.0 Ohm 0.1 150.0 High limit in ohm
ZLowLim 0.0 - 5000.0 Ohm 0.1 50.0 Low limit in ohm
ZLowLowLim 0.0 - 5000.0 Ohm 0.1 35.0 Low Low limit in ohm
ZMin 0.000 - 5000.000 Ohm 0.001 0.005 Minimum value in ohm
ZLimHys 0.000 - 100.000 % 0.001 0.500 Hysteresis value in % of range and is
common for all limits

Table 197: ZMFCPDIS Group settings (advanced)


Name Values (Range) Unit Step Default Description
RLdFwMax 0.01 - 5000.00 Ohm/p 0.01 5000.00 Maximum used resistance
determining the load impedance area,
if RLdFw is greater than RLdFwMax
then RLdFw is set to RLdFwMax
RLdFwMin 0.01 - 5000.00 Ohm/p 0.01 0.01 Minimum used resistance determining
the load impedance area, if RLdFw is
less than RLdFwMin then RLdFw is set
to RLdFwMin
ArgLdMax 5 - 70 Deg 1 70 Maximum used angle determining the
load impedance area, if ArgLd is
greater than ArgLdMax then ArgLd is
set to ArgLdMax
ArgLdMin 5 - 70 Deg 1 5 Minimum used angle determining the
load impedance area, if ArgLd is less
than ArgLdMin then ArgLd is set to
ArgLdMin
ZoneLinkStart Phase Selection - - Phase Selection Selection of start source for all
1st starting zone ZoneLinked trip delay timers
INReleasePE 5 - 400 %MaxIP 1 400 3I0 limit for releasing Phase-to-Earth
h measuring loops
Table continues on next page

Line distance protection REL670 353


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Name Values (Range) Unit Step Default Description


TimerModeZ1 Disable all - - Enable Ph-E PhPh On/Off setting for Ph-Ph and Ph-E trip
Enable Ph-E output, zone 1
Enable PhPh
Enable Ph-E PhPh
TimerLinksZ1 LoopLink (tPP & - - LoopLink (tPP & How start of trip delay timers should
tPE) tPE) be linked for zone 1
LoopLink &
ZoneLink
No Links
TimerModeZ2 Disable all - - Enable Ph-E PhPh On/Off setting for Ph-Ph and Ph-E trip
Enable Ph-E output, zone 2
Enable PhPh
Enable Ph-E PhPh
TimerLinksZ2 LoopLink (tPP & - - LoopLink (tPP & How start of trip delay timers should
tPE) tPE) be linked for zone 2
LoopLink &
ZoneLink
No Links
TimerModeZ3 Disable all - - Enable Ph-E PhPh On/Off setting for Ph-Ph and Ph-E trip
Enable Ph-E output, zone 3
Enable PhPh
Enable Ph-E PhPh
TimerLinksZ3 LoopLink (tPP & - - LoopLink (tPP & How start of trip delay timers should
tPE) tPE) be linked for zone 3
LoopLink &
ZoneLink
No Links
TimerModeZ4 Disable all - - Enable Ph-E PhPh On/Off setting for Ph-Ph and Ph-E trip
Enable Ph-E output, zone 4
Enable PhPh
Enable Ph-E PhPh
TimerLinksZ4 LoopLink (tPP & - - LoopLink (tPP & How start of trip delay timers should
tPE) tPE) be linked for zone 4
LoopLink &
ZoneLink
No Links
TimerModeZ5 Disable all - - Enable Ph-E PhPh On/Off setting for Ph-Ph and Ph-E trip
Enable Ph-E output, zone 5
Enable PhPh
Enable Ph-E PhPh
TimerLinksZ5 LoopLink (tPP & - - LoopLink (tPP & How start of trip delay timers should
tPE) tPE) be linked for zone 5
LoopLink &
ZoneLink
No Links
TimerModeZRV Disable all - - Enable Ph-E PhPh On/Off setting for Ph-Ph and Ph-E trip
Enable Ph-E output, zone RV
Enable PhPh
Enable Ph-E PhPh
TimerLinksZRV LoopLink (tPP & - - LoopLink (tPP & How start of trip delay timers should
tPE) tPE) be linked for zone RV
LoopLink &
ZoneLink
No Links

354 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

8.12.6 Monitored data


PID-7163-MONITOREDDATA v1

Table 198: ZMFCPDIS Monitored data


Name Type Values (Range) Unit Description
L1Dir INTEGER 1=Forward - Direction in phase L1
2=Reverse
0=No direction
L2Dir INTEGER 1=Forward - Direction in phase L2
2=Reverse
0=No direction
L3Dir INTEGER 1=Forward - Direction in phase L3
2=Reverse
0=No direction
L1L2Dir INTEGER 1=Forward - Direction in loop L1L2
2=Reverse
0=No direction
L2L3Dir INTEGER 1=Forward - Direction in loop L2L3
2=Reverse
0=No direction
L3L1Dir INTEGER 1=Forward - Direction in loop L3L1
2=Reverse
0=No direction
L1R REAL - Ohm Resistance in phase L1
L1X REAL - Ohm Reactance in phase L1
L2R REAL - Ohm Resistance in phase L2
L2X REAL - Ohm Reactance in phase L2
L3R REAL - Ohm Resistance in phase L3
L3X REAL - Ohm Reactance in phase L3
L12R REAL - Ohm Resistance in phase L1-L2
L12X REAL - Ohm Reactance in phase L1-L2
L23R REAL - Ohm Resistance in phase L2-L3
L23X REAL - Ohm Reactance in phase L2-L3
L31R REAL - Ohm Resistance in phase L3-L1
L31X REAL - Ohm Reactance in phase L3-L1
ZL1IMAG REAL - Ohm ZL1 Amplitude, magnitude of
instantaneous value
ZL1ANGIM REAL - deg ZL1 Angle, magnitude of
instantaneous value
ZL2IMAG REAL - Ohm ZL2 Amplitude, magnitude of
instantaneous value
ZL2ANGIM REAL - deg ZL2 Angle, magnitude of
instantaneous value
ZL3IMAG REAL - Ohm ZL3 Amplitude, magnitude of
instantaneous value
ZL3ANGIM REAL - deg ZL3 Angle, magnitude of
instantaneous value
ZL12IMAG REAL - Ohm ZL12 Amplitude, magnitude of
instantaneous value
ZL12ANGIM REAL - deg ZL12 Angle, magnitude of
instantaneous value
Table continues on next page

Line distance protection REL670 355


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Name Type Values (Range) Unit Description


ZL23IMAG REAL - Ohm ZL23 Amplitude, magnitude of
instantaneous value
ZL23ANGIM REAL - deg ZL23 Angle, magnitude of
instantaneous value
ZL31IMAG REAL - Ohm ZL31 Amplitude, magnitude of
instantaneous value
ZL31ANGIM REAL - deg ZL31 Angle, magnitude of
instantaneous value

8.12.7 Operation principle GUID-913A0692-F0A7-4B4B-83B4-AC2A96B3A989 v3

Settings, input and output names are sometimes mentioned in the following
text without its zone suffix (i.e. BLKZx instead of BLKZ3) when the description
is equally valid for all zones.

8.12.7.1 Filtering GUID-0EA39CA3-6CDA-41B0-A178-E5800868A0C5 v2

Practically all voltage, current and impedance quantities used within the ZMFCPDIS function
are derived from fundamental frequency phasors filtered by a half-cycle filter.

The phasor filter is frequency adaptive in the sense that its coefficients are changed based on
the estimated power system frequency.

A half-cycle filter will not be able to reject both even and odd harmonics. While odd harmonics
will be completely attenuated, accuracy will be affected by even harmonics. Even harmonics
will not cause the distance zones to overreach; instead there will be a slightly variable
underreach, on average in the same order as the magnitude ratio between the harmonic and
the fundamental component.

8.12.7.2 Distance measuring zones GUID-674FC410-9BA3-437E-8358-62E9B81D7B65 v3

The different fault loops within the IED are of full scheme type, which means that earth fault
loop for phase-to-earth faults and phase-to-phase faults for forward and reverse faults are
executed in parallel.

Figure 188 presents an outline of the different measuring loops for the six distance zones.

356 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 1

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 2

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 3

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 4

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 5

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1


Zone RV

IEC05000458-2-en.vsd
IEC05000458 V2 EN-US

Figure 188: The different measuring loops at phase-to-earth fault and phase-to-phase
fault
Transients from CVTs may have a significant impact on the transient overreach of a distance
protection. At the same time these transients can be very diverse in nature from one type to
the other; in fact, more diverse than can be distinguished by the algorithm itself in the course
of a few milliseconds. So, a setting is introduced in order to inform the algorithm about the
type of CVT applied and thus providing the advantage of knowing how performance should be
optimized, even during the first turbulent milliseconds of the fault period.

There are two types of CVTs from the function point of view, the passive and the active type,
which refers to the type of ferro-resonance suppression device that is employed. The active
type requires more rigorous filtering which will have a negative impact on operate times.
However, this will be evident primarily at higher source impedance ratios (SIRs), SIR 5 and
above, or close to the reach limit.

The IEC 60044-5 transient classification is of little or no use in relation to this. It is not
primarily the damping of transients that is important; it is the frequency content of the
transients that is decisive, i.e. how difficult it is to filter out the specific frequency. So, even if
two CVTs, one passive and the other active type, comply with the same transient class, the
active type requires more extensive filtering in order to avoid transient overreach.

To avoid overreach and at the same time achieve fast operate times, a supplementary circular
characteristic that includes some alternative processing is implemented. One such circular
characteristic exists for every measuring loop and quadrilateral/mho characteristic. There are
no specific reach settings for this circular zone. It uses the normal quadrilateral/mho zone
settings to determine a reach that will be appropriate. This implies that the circular
characteristic will always have somewhat shorter reach than the quadrilateral/mho zone.

8.12.7.3 Phase-selection element GUID-2BCDB96F-39EE-4C14-9856-D23A4A1B6115 v5

The operation of the phase-selection element is primarily based on current change criteria.
The current change criteria itself can however only be relied on for a short period following the
fault inception (during what we will call the current change phase). Subsequent switching in
the network may render the change in current invalid. To handle this, the phase-selection
element also operates on continuous criteria.

The phase-selection element can, owing to the current change criteria, distinguish faults with
minimum influence from load and fault impedance. In other words, it is not restricted by a load
encroachment characteristic during the current change phase. This significantly improves
performance for remote phase-to-earth faults on heavily loaded lines. One exception, however,
is three-phase faults, for which the load encroachment characteristic always has to be applied,
in order to distinguish fault from load.

Line distance protection REL670 357


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

The continuous criteria will in the vast majority of cases operate in parallel and carry on the
fault indication after the current change phase has ended. Only in some particularly difficult
faults on heavily loaded lines the continuous criteria might not be sufficient, for example,
when the estimated fault impedance resides within the load area defined by the load
encroachment characteristic. In this case, the indication will be restricted to a pulse lasting for
one or two power system cycles.

Phase-to-phase-earth faults (also called double earth faults) will practically always activate
phase-to-phase zone measurements.Measurement in two phase-to-earth loops at the same
time is associated with so-called simultaneous faults: two earth faults at the same time, one
each on the two circuits of a double line, or when the zero sequence current is relatively high
due to a source with low Z0/Z1 ratio.In these situations zone measurement will be released
both for the related phase-to-earth loops and the phase-to-phase loop simultaneously. On the
other hand, simultaneous faults closer to the remote bus will gradually take on the properties
of a phase-to-phase-earth fault and the function will eventually use phase-to-phase zone
measurements also here.

In cases where the fault current infeed is more or less completely lack of zero sequence nature
(all phase currents in phase), the measurement will be performed in the phase-to-earth loops
only for a phase-to-phase-earth fault.

However, should it be desirable to use phase-to-earth (and only phase-to-earth) zone


measurement for phase-to-phase-earth faults, there is a setting INReleasePE that can be
lowered from its excessive default value to the level above which phase-to-earth measurement
should be activated.

8.12.7.4 Directional criteria GUID-24431EEC-5037-41CD-BC4A-7AC196F158F3 v5

Several criteria are employed when making the directional decision. The basis is provided by
comparing a positive sequence based polarizing voltage with phase currents. For extra
security, especially in making a very fast decision, this method is complemented with an
equivalent comparison where, instead of the phase current, the change in phase current is
used. Moreover, a basic negative sequence directional evaluation is taken into account as a
reliable reference during high load condition. Finally, a zero sequence directional evaluation is
used whenever there is more or less exclusive zero sequence in-feed.

The directional sectors that represent forward direction, one per measuring loop, are defined
by the following equations.

U PolL1
−15° < arg < 120°
I L1
IECEQUATION15059 V1 EN-US (Equation 79)

U PolL1L 2
−15° < arg < 120°
I L1L 2
IECEQUATION15060 V1 EN-US (Equation 80)

Where:
UPolL1 is the polarizing voltage for phase L1.

IL1 is the phase current in phase L1.

UPolL1L2 is the polarizing voltage difference between phase L1 and L2 (L2 lagging L1).

IL1L2 is the current difference between phase L1 and L2 (L2 lagging L1).

The corresponding reverse directional sectors range from 165 to -60 degrees.

358 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Since the polarizing voltage is also used for the Mho distance characteristics, the magnitude
of the voltage is just as interesting as the phase. If there are symmetrical conditions and the
measured per phase positive sequence voltage magnitude is above 75% of the base voltage
before the fault, the pre-fault magnitude will be memorized and used as long as there is a
fault. The phase angle however will only be memorized (locked) for 75 ms at a time, not to lose
synchronism with the real system voltage.

Should the positive sequence voltage drop below 2% of the base voltage, it will be considered
invalid. In this situation, directional signals and starts from Mho elements will be sealed-in and
kept static as long as there is a fault.

For ZMFCPDIS, when option SeriesComp is chosen for OperationSC, the voltages of faulty
phases will be discarded in order not to affect the polarizing voltage with voltage reversal.

8.12.7.5 Transient directional element GUID-DE9C146F-CD20-4700-B6FF-B81B8DB47631 v1

The ZMFCPDIS function has another directional element with phase segregated outputs
STTDFwLx and STTDRVLx (where, x=1-3), which are intended for the permissive overreaching
transfer trip (POTT) scheme. It provides directionality with high speed, dependability and
security. It is also suitable for extra high voltage and series compensated lines where the
fundamental frequency signals are distorted. The transient directional element is based on the
changes in voltage and current signals due to a fault. The changes can be calculated by
subtracting the pre-fault voltage and current from the measured quantiles due to a fault as
shown below:

u  t   u  t   u p  t 
i  t   i  t   i p  t 
IECEQUATION18056 V1 EN-US (Equation 81)

Where,

∆u(t) and ∆i(t) are the changes in voltage and current due to the fault.

u(t) and i(t) are the measured voltage and current during the fault.

up(t) and ip(t) are the pre-fault voltage and pre-fault current.

When the power network is under stable operation, ∆u(t) and ∆i(t) are negligible. When a fault
occurs, ∆u(t) and ∆i(t) become visible due to the changes in electrical state of the power
network. According to the superposition principle, after a forward fault, ∆u(t) and ∆i(t) are
opposite in sign. While after a reverse fault, ∆u(t) and ∆i(t) are of equal sign.

By inserting a proper replica impedance ZR into the measurement path, a replica delta voltage
ΔuR(t), which is approximately proportional to ∆i(t), is obtained by ΔuR(t) = Δi(t)*ZR. The replica
impedance is optimized in the design to make the relay characteristic angle at 60 degree.
Δu(t)*ΔuR(t) is negative for a forward fault, and positive for a reverse fault.

The operating quantity can be obtained using a simple waveform integration function:

N
2
F t     u  t   u  t    dt
0
R

IECEQUATION18057 V1 EN-US (Equation 82)

Where, N is the number of samples per cycle.

Therefore, the directionality is determined according to the polarities of F(t) as below:

Forward, if F(t) is negative. i.e., F(t) < –Th–

Line distance protection REL670 359


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Reverse, if F(t) is positive. i.e., F(t) > Th+

Where, Th– and Th+ are the thresholds for negative and positive polarities of F(t).

To enable good security, the reverse detector is more sensitive compared to the forward one
by a much lower magnitude of Th+ than Th–.

Due to the transient nature, directionality decisions are required to be made after a short
duration when the phase-selection element has detected a fault. Once the decision is made, it
issues directional indications with pulses of duration at about 3-4 cycles.

The transient element has a good sensitivity for the initial fault. In certain cases, for example, a
fault with extremely high fault resistance, where Δu(t) or Δi(t) are very low and the transient
directional element is not active, the fundamental frequency component based directional
elements (see Section Directional criteria) will be available after a certain delay.

8.12.7.6 Fuse failure GUID-AB0D0D20-EF27-4475-8EC5-A3BF69FC5802 v2

The ZMFCPDIS function has to be blocked by an additional function like the Fuse failure
supervision (FUFSPVC) or an equivalent external device. Typically, the binary input VTSZ is
used for this purpose.

However, to guarantee that also very fast operation is blocked in a fuse failure situation, there
is a built-in supervision based on change in current that will delay operation before the
FUFSPVC blocking signal is received. The delay will be introduced if no (vector) magnitude
change greater than 5% of IBase has been detected in any of the phase currents.

8.12.7.7 Power swings GUID-66627E0F-33AA-4570-9C27-4217EEECC2CE v1

There is need for external blocking of the ZMFCPDIS function during power swings, either from
the Power Swing Blocking function (ZMRPSB) or an external device.

8.12.7.8 Measurement principles

Quadrilateral characteristic GUID-E1366EA0-B04E-4180-BC4C-F042CC8FA8E2 v6


ZMFCPDIS implements quadrilateral and mho characteristic in all the six zones separately. Set
OpModePEZx or OpModePPZx to Quadrilateral, to choose particular measuring loop in a zone
to work as quadrilateral distance protection.

All ZMFCPDIS zones operate according to the non-directional impedance characteristics


presented in figure 189 and figure 190. The phase-to-earth characteristic is illustrated with the
full loop reach while the phase-to-phase characteristic presents the per-phase reach.

The voltage and current phasors after the half-cycle filter are used in fault loop equations.

For phase-to-phase faults (Figure 191, lower part), the calculated impedances from the relay to
the fault Z calc  Rcalc  j  X calc follow Equation 83 (example is given for a phase L1 to phase L2
fault).

 
U L1  U L 2  I L1  I L 2  Z calc 
IECEQUATION18003 V1 EN-US (Equation 83)

Where and represents the corresponding voltage and current phasors in the respective
phase Ln (n = 1, 2, 3).

360 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

The calculated Rcalc and Xcalc are compared with the non-directional phase-to-phase
quadrilateral characteristics defined by the reactance reaches (X1FwPPZx and X1RvPPZx,
where x = 1 to 5 or RV), resistance reaches (R1FwPPZx, where x = 1 to 5 or RV) for the zones, as
well as the fault resistance reach setting for phase-to-phase loops ((RFPPZx, where x = 1, 2 or
RV), (RFFwPPZx and RFRvPPZx, where x = 3 to 5 or RV)), as shown in Figure 190. If is inside
the non-directional phase-to-phase characteristic, the STNDZx output is set to TRUE.

For phase-to-earth faults (Figure 191, upper part), the earth return compensation applies
according to Equation 84 (example for a phase L1 to earth fault).

 
U L1  I L1  K N  3I 0  p  Z1  I F  RF
IECEQUATION18007 V1 EN-US (Equation 84)

Where,

p is the fault location and RF is the calculated fault resistance. p and RF are unknown and
needs to be solved.

is the zero-sequence current.

is the ground compensation factor and it is defined as:

Z 0  Z1
KN 
3  Z1
Z 0  R0 FwPEZx  j  X 0 FwPEZx
Z1  R1FwPEZx  j  X 1FwPEZx
IECEQUATION18020 V1 EN-US

Where,

is the set complex zero sequence impedance of the line in Ω/phase.

is the set complex positive sequence impedance of the line in Ω/phase.

R1FwPEZx is the positive sequence resistive reach of the line in Ω/phase for phase-to-earth
fault in zone direction for zone x (x = 1 to 5 or RV).

X1FwPEZx is the positive sequence reactance reach of the line in Ω/phase for phase-to-earth
fault in zone direction for zone x (x = 1 to 5 or RV).

R0FwPEZx is the zero sequence resistive reach of the line in Ω/phase for phase-to-earth fault
in zone direction for zone x (x = 1 to 5 or RV).

X0FwPEZx is the zero sequence reactance reach of the line in Ω/phase for phase-to-earth fault
in zone direction for zone x (x = 1 to 5 or RV).

is the fault current. It is chosen among phase, zero or negative sequence currents
automatically by the built-in adaptive load compensation algorithm.

The calculated impedances from the relay to the fault Z calc  Rcalc  j  X calc can be represented
as:
X calc  p  X 1FwPEZx
Rcalc  p  R1FwPEZx  RF
IECEQUATION18021 V1 EN-US

The calculated Rcalc and Xcalc are compared with the non-directional phase-to-earth
quadrilateral characteristics defined by the reactance reaches (X1FwPEZx or X1RvPEZx, where
x = 1 to 5 or RV), resistance reaches (R1RwPEZx, where x = 1 to 5 or RV) for the zones, as well as

Line distance protection REL670 361


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

the fault resistance reach setting for phase-to-earth loops ((RFPEZx, where x = 1, 2 or RV),
(RFFwPEZx and RFRvPEZx, where x = 3 to 5)), as shown in Figure 189. If is inside the non-
directional phase-to-earth characteristic, the STNDZx output is set to TRUE.

X (Ohm/loop)

X0FwPEZx , X1FwPEZx
XNFwZx <
R1FwPEZx+RNFwZx 3
X1RvPEZx
XNRvZx < XNFwZx √
RFRvPEZx RFFwPEZx X1FwPEZx
R0FwPEZx , R1FwPEZx
RNFwZx <
3
X1RvPEZx
RNRvZx < RNFwZx √
X1FwPEZx
X1RvPEZx
X1FwPEZx+XNFwZx R1RvPEZx < R1FwPEZx √
X1FwPEZx

ιN ιN
R (Ohm/loop)

1) 1)
RFRvPEZx RFFwPEZx

X1RvPEZx+XNRvZx

ιN

RFRvPEZx RFFwPEZx

R1RvPEZx + RNRvZx IEC11000417-3-en.vsd

Settings RFRvPEZx and RFFwPEZx exists for Zones 3 to 5.


1)
For Zone 1, 2 and RV, setting RFPEZx is applicable for both forward and reverse direction.
IEC11000417 V3 EN-US

Figure 189: ZMFCPDIS Characteristic for phase-to-earth measuring loops, ohm/loop


domain

362 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

R1FwPPZx
X (Ohm/phase)

RFRvPPZx RFFwPPZx
2 2

X1FwPPZx

ιN
R (Ohm/phase)

1) 1)
RFRvPPZx RFFwPPZx
2 2

X1RvPPZx

ιN

RFRvPPZx RFFwPPZx
2 2
X1RvPPZx IEC11000418-3-en.vsd
R1FwPPZx √
X1FwPPZx

Settings RFRvPPZx and RFFwPPZx exist for Zones 3 to 5.


1)
For Zone 1, 2 and RV, setting RFPPZx is applicable for both forward and reverse direction.
IEC11000418 V3 EN-US

Figure 190: ZMFCPDIS Characteristic for the phase-to-phase measuring loops, ohm/
phase domain

Note that for ZMFCPDIS, the reverse zone ZRV, as well as any of zones 3-5, that
are set to DirMode=Reverse will get their operating impedances inverted
(rotated 180 degrees) internally in order to make use of the main settings,
which are the settings designated ‘Fw’. Therefore, a reverse zone will have its
Fw-settings (RFFwPPZRV, X1FwPEZ3, and so on) applied in the third quadrant,
that is, towards the busbar instead of the line.

The fault loop reach in relation to each fault type may also be presented as in figure 191. The
main intention with this illustration is to make clear how the fault resistive reach should be
interpreted. Note in particular that the setting RFPP [2] always represents the total fault
resistance of the loop, even while the fault resistance (arc) may be divided into parts like for
three-phase or phase-to-phase-to-earth faults. R1Zx and jX1Zx represent the positive sequence
impedance from the measuring point to the fault location.

[2] Represents all settings such as RFFwPPZRV, RFRvPPZ5 etc.

Line distance protection REL670 363


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

IL1 R1Zx + j X1Zx


Phase-to-earth
UL1
element

Phase-to-earth
RFPEZx
fault in phase L1
(Arc + tower
resistance)

0
IN (R0Zx-R1Zx)/3 +
j (X0Zx-X1Zx)/3 )

IL1 R1Zx + j X1Zx Phase-to-phase


UL1 element L1-L2
Phase-to-phase
fault in phase RFPPZx
L1-L2 IL2
UL2 (Arc resistance)
R1Zx + j X1Zx

IL1 R1Zx + j X1Zx 0.5·RFPPZx Phase-to-phase


UL1 element L1-L3
Three-phase
fault or Phase-to-
phase-earth fault IL3
UL3
R1Zx + j X1Zx 0.5·RFPPZx
IEC11000419-3-en.vsdx
IEC11000419 V3 EN-US

Figure 191: Fault loop model


The zone impedance characteristic is a product of the two separate characteristics:

• The quadrilateral characteristic


• The directional characteristic

The estimated impedance needs to be inside both characteristics for the zone to start or trip.
(The non-directional start STND is an exception however. It is only dependent on the
quadrilateral characteristic.)

In the following figure, the zone with the shorter reactive reach follows the directional line
(R∙tan(15⁰)) only up to X1PP, where the quadrilateral characteristic will start to limit the reach.

364 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

X (ohm)

X1PP’

X1PP

15° R (ohm)
-X1PP RFPP/2
R· tan15°

-X1PP’
IEC19000141-1-en-us.vsdx

IEC19000141 V1 EN-US

Figure 192: Line distance protection

Mho characteristic GUID-DA87F1BC-8037-4E14-96E0-03BCD98ED6F2 v1


ZMFCPDIS implements quadrilateral and mho characteristic in all the six zones separately. Set
OpModePEZx or OpModePPZx setting to Mho or Offset, to choose a particular measuring loop
in a zone to work as mho (or Offset Mho) distance protection.

Zones 3 to 5 can be selected to be either forward or reverse with positive sequence polarized
mho characteristic; alternatively self polarized offset mho characteristics. The operating
characteristic is in accordance to figure 193 where zone 5 is selected offset mho.

X
X

Z4
Z3
ZS=0
Z2
Z1 R
Z5 R

ZS=Z1
ZRV
ZS=2Z1

IEC15000056-1-en.vsdx

IEC15000056 V1 EN-US

Figure 193: Mho, offset mho characteristics and the source impedance influence on the
mho characteristic
The mho characteristic has a dynamic expansion due to the source impedance. Instead of
crossing the origin, as for the mho to the left of figure 193, which is only valid where the source
impedance (Zs) is zero, the crossing point is moved to the coordinates of the negative source
impedance given an expansion of the circle shown to the right of figure 193. Z1 denotes the
complex positive sequence impedance.

The magnitude of the polarized voltage is determined completely by the positive sequence
voltage magnitude from before the fault. This will give a somewhat less dynamic expansion of

Line distance protection REL670 365


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

the mho circle during faults. However, if the source impedance is high, the dynamic expansion
of the mho circle might lower the security of the function too much with high loading and mild
power swing conditions.

Basic operation characteristics GUID-B9D7C3D8-811A-419B-8373-712EC122EB08 v2


In ZMFCPDIS, each zone measurement loop characteristic can be set to mho characteristic or
offset mho characteristic by setting OpModePEZx or OpModePPZx (where x is 1-5 depending
on selected zone).

ZMFCPDIS fixes zone 1 and 2 in Forward mode and zone RV in Reverse mode. Zone 3-5 can be
set to Non-directional, Forward or Reverse by setting the parameter DirModeZx (where x is 3-5
depending on selected zone).

If DirModeZx (where x is 3-5 depending on selected zone) is selected as Non-directional, the


directional element will not have any effect on the measurement loop and operation of the
function. When DirModeZx (where x is 3-5 depending on selected zone) is selected as Forward
or Reverse, directional lines are introduced. Information about the directional lines is given
from the directional element. Basic Mho and offset Mho characteristics with different mode
settings are indicated in figure 194.

X X
(a) Rset
X (c)
(b) Rset

(a), (b) and (c)


For Phase-to-Phase fault
Xset Rset=R1FwPPZx; Xset=X1FwPPZx
Xset For Phase-to-earth fault
Rset=R1FwPEZx+RNFwZx
Xset=X1FwPEZx+XNFwZx
R R R X 0 PEZx  X 1 FwPEZx
XNFwZx
3
R 0PEZx  R1 FwPEZx
RNFwZx
Xset 3

Rset

Forward Reverse Non-directional

Mho Characteristics

(d), (e) and (f)


X (e) X (f) X For Phase-to-Phase fault
(d)
RsetFwZx=R1FwPPZx; XsetFwZx=X1FwPPZx
RsetFwZx RsetRvZx=R1RvPPZx; XsetFwZx=X1RvPPZx
RsetFwZx RsetFwZx
R1FwPPZx
R1RvPPZx  X 1 RvPPZx 
X 1FwPPZx
For Phase-to-Earth fault
XsetFwx XsetFwZx
XsetFwZx RsetFwZx  R1FwPEZx  RNFwZx
XsetFwZx  X 1FwPEZx  XNFwZx
R R R X 0FwPEZx  X 1FwPEZx
XNFwZx 
XsetRvZx 3
XsetRvZx XsetRvZx
R 0FwPEZx  R1FwPEZx
RNFwZx 
3
RsetRvZx RsetRvZx  R1RvPEZx  RNRvZx
RsetRvZx RsetRvZx
XsetRvZx  X 1RvPEZx  XNRvZx
R1 RvPEZx
RNRvZx  RNFwZx 
R1 FwPEZx
R1FwPEZx
Forward R1RvPEZx  X 1 RvPEZx 
Reverse Non-directional X 1FwPEZx
X 1RvPEZx
XNRvZx  XNFwZx 
X 1 FwPEZx
Offset Mho Characteristics

(a) and (c) are for Zone 1, Zone 2 and Zone 3-5 when DirModeZ3-5 = Forward
(b) and (d) are for ZoneRV and Zone 3-5 when DirModeZ3-5 = Reverse
(c) and (f) are for Zone 3-5 when DirModeZ3-5 = Non-Directional
IEC15000065‐2‐en.vsdx

IEC15000065 V2 EN-US

Figure 194: Mho and offset Mho characteristics


For each zone, the impedance is set in cartesian coordinates (resistance and reactance) which
is the same as for quadrilateral characteristic.

ZMFCPDIS function uses separate sets of reach settings in forward and reverse directions for
phase-to-earth fault and phase-to-phase fault. These settings are R1FwPPZx, X1FwPPZx,
X1RvPPZx, R1FwPEZx, X1FwPEZx, X1RvPEZx, R0FWPEZx, X0FwPPZx (x=1-5 or RV). Thus, the
center of the Non-directional offset mho circle can be arbitrarily located in the circle (figure
194).

366 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Note that the reverse ZoneRV, as well as any of zones 3-5, that are set to DirModeZx=Reverse
will get their operating impedances inverted (rotated 180 degrees) internally in order to make
use of the main settings, which are the settings designated ‘Fw’. Therefore, a reverse zone will
have its Fw-settings (R1FwPPZRV, X1FwPEZ3, and so on) applied in the third quadrant, that is,
towards the busbar instead of the line.

In Non-directional mode, for both Mho and Quad, the reach settings are equal to Forward
mode in this respect. The ‘Fw’ settings apply in the first quadrant and the ‘Rv’ settings apply in
the third quadrant.

Theory of operation SEMOD154224-46 v6


The mho algorithm is based on the phase comparison of an operating phasor and a polarizing
phasor. When the operating phasor leads the reference polarizing phasor by 90 degrees or
more, the function operates and gives a trip output.

Phase-to-phase fault GUID-46762EB9-50CA-4045-9D39-80B604C66E0F


SEMOD154224-240 v2
The plain Mho circle has the characteristic as in figure 195. The condition for deriving the angle
β is according to equation 85.

( )
β = arg U L1L 2 − I L1L 2 ⋅ Z 1set − arg U pol ( )
IECEQUATION15027 V1 EN-US (Equation 85)

where

U L1L2 is the voltage vector difference between phases L1 and L2


EQUATION1790
EN-US V2

I L1L2 is the current vector difference between phases L1 and L2


EQUATION1791
EN-US V2

is the positive sequence impedance setting for phase-to-phase fault in zone direction
Z 1set
is the polarizing voltage
Upol

Z 1set = R1FwPPZx + j ⋅ X 1FwPPZx


IECEQUATION15010 V1 EN-US (Equation 86)

where:
R1FwPPZx is the positive sequence resistive reach for phase-to-phase fault in zone direction for zone x (x=1-5
and RV)
X1FwPPZx is the positive sequence reactance reach for phase-to-phase fault in zone direction for zone x
(x=1-5 and RV)

The polarized voltage consists of 100% memorized positive sequence voltage (UL1L2 for phase
L1 to L2 fault). The memorized voltage will prevent collapse of the mho circle for close in faults.

Operation occurs if 90°≤β≤270°.

Line distance protection REL670 367


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

IL1L2  jX

I L1L 2  Z1set
UcompUL1L2 IL1L2 Z1set

UL1L2

U pol

I L1L 2  R

IEC15000060-1-en.vsdx

IEC15000060 V1 EN-US

Figure 195: Simplified mho characteristic and vector diagram for phase L1-to-L2 fault
Offset Mho GUID-2E84AD28-CA5F-4D19-B189-57354C8F7CF9 v2
The characteristic for offset mho is a circle where two points on the circle are given by the two
vectors Z 1set and Z 1RVset where Z 1set and Z 1RVset are settable through the resistance and
reactance settings in forward and reverse directions.

The condition for operation at phase-to-phase fault is that the angle β between the two
compensated voltages is greater than or equal to 90° (figure 196). The angle will be 90° for
fault location on the boundary of the circle.

The angle β for L1 to L2 fault can be defined according to equation 88.

 U 
L1L 2  I L1L 2  Z 1set
  arg  
 
 U L1L 2   I L1L 2  Z1set  

IECEQUATION15008 V2 EN-US (Equation 88)

where
is the positive sequence impedance setting for phase-to-phase
Z 1RVset fault opposite to zone direction and is defined as

Z 1RVset = R1RvPPZx + j ⋅ X 1RvPPZx


IECEQUATION15013 V1 EN-US (Equation 89)

368 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

where
X1RvPPZx is the positive sequence reactance reach for phase-to-phase
fault opposite to zone direction for zone x (x=1-5 and RV)
R1RvPPZx is the positive sequence resistive reach for phase-to-phase
fault opposite to zone direction for zone x (x=1-5 and RV) and is
internally calculated according to the equation below,

 R1FwPPZx 
R1RvPPZx = X 1RvPPZx ⋅  
 X 1FwPPZx 
IECEQUATION15014 V1 EN-US (Equation 90)

IL1L 2  jX

Ucomp1  UL1L 2  IL1L 2  Z1set

IL1L 2  Z1set

UL1L 2


Ucomp 2  UL1L 2  IL1L 2  Z1RVset 

IL1L 2  R
IL1L 2  Z1RVset

IEC16000207-1-en.vsdx

IEC16000207 V1 EN-US

Figure 196: Simplified offset mho characteristic and voltage vector for phase L1 to L2
fault
Operation occurs if 90°≤β≤270 °.

Phase-to-earth fault GUID-8A79E50E-9DC0-45DA-A3A7-DF3DBF59618C


SEMOD154224-283 v2
v1
The measuring of earth faults uses earth return compensation applied in a conventional way.
The compensation voltage is derived by considering the influence from the earth return path.

Compensation for earth return path for faults involving earth is done by setting the positive
and zero sequence impedance of the line. It is known that the ground compensation factor KN
is,

Z 0set − Z 1set
KN =
3 ⋅ Z 1set
IECEQUATION15017 V1 EN-US

Line distance protection REL670 369


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Z 0set = R 0 FwPEZx + j ⋅ X 0 FwPEZx


IECEQUATION15028 V1 EN-US

Z 1set = R1FwPEZx + j ⋅ X 1FwPEZx


IECEQUATION15029 V1 EN-US (Equation 91)

where
is the complex zero sequence impedance of the line in Ω/phase
Z 0set
is the complex positive sequence impedance of the line in Ω/
Z 1set
phase
R0FwPEZx is the zero sequence resistive reach of the line in Ω/phase for
phase-to-earth fault in zone direction for zone x (x=1-5, or RV)
X0FwPEZx is the zero sequence reactance reach of the line in Ω/phase for
phase-to-earth fault in zone direction for zone x (x=1-5, or RV)
R1FwPEZx is the positive sequence resistive reach of the line in Ω/phase
for phase-to-earth fault in zone direction for zone x (x=1-5, or
RV)
X1FwPEZx is the positive sequence reactance reach of the line in Ω/phase
for phase-to-earth fault in zone direction for zone x (x=1-5, or
RV)

For an earth fault in phase L1, the angle β between the compensation voltage and the

polarizing voltage Upol is,

β = arg [U L1 − ( I L1 + 3I 0 ⋅ K N ) ⋅ Z 1set ] − arg(U pol )


IECEQUATION15021 V1 EN-US (Equation 92)

where
is the phase voltage in faulty phase L1
UL1
is the phase current in faulty phase L1
IL1
3I0 is the zero-sequence current in faulty phase L1

is the complex positive sequence impedance of the line in Ω/


Z 1set phase for phase-to-earth fault in zone direction

is the polarizing voltage in phase L1


Upol

370 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

IL1•jX

UcompUL1 (IL1 3I0 KN )  Z1set


3I0KN Z1set

U L1
I L1  Z1set
U pol

IL1•R
IEC15000059-1-en.vsdx

IEC15000059 V1 EN-US

Figure 197: Simplified offset mho characteristic and vector diagram for phase L1-to-earth
fault
Operation occurs if 90 °≤β≤270 °.

Offset mho GUID-1CD62635-A76A-41F7-A814-8BB493F5B051 v3


The condition for operation of offset mho at phase-to-earth fault is that the angle β between
the two compensated voltages is equal to or greater than 90°, see figure "". The angle will be
90° for fault location on the boundary of the circle.

   
  arg U L1  ( I L1  3I 0  K N )  Z1set  arg U L1   ( I L1  3I 0  K N )  Z1set 

IECEQUATION15022 V2 EN-US (Equation 93)

where
is the complex positive sequence impedance of the line in Ω/
Z 1RVset phase for phase-to-earth fault opposite to zone direction and is
defined as,

Z 1RVset = R1RvPEZx + j ⋅ X 1RvPEZx


IECEQUATION15023 V1 EN-US (Equation 94)

where
X1RvPEZx is the positive sequence reactance reach for phase-to-earth
fault opposite to zone direction for zone x (x=1-5 and RV)
R1RvPEZx is the positive sequence resistive reach for phase-to-earth fault
opposite to zone direction for zone x (x=1-5 and RV) and
expressed by,

Line distance protection REL670 371


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

 R1FwPEZx 
R1RvPEZx = X 1RvPEZx ⋅  
 X 1FwPEZx 
IECEQUATION15024 V1 EN-US (Equation 95)

8.12.7.9 Load encroachment GUID-D846C3D9-4C79-40B5-9ED2-23934214AADB v7

In some cases the load impedance might enter the zone characteristic without any fault on the
protected line. The phenomenon is called load encroachment and it might occur when an
external fault is cleared and high emergency load is transferred on the protected line. The
effect of load encroachment is illustrated in the left part of figure 198. A load impedance
within the characteristic would cause an unwanted trip. The traditional way of avoiding this
situation is to set the distance zone resistive reach with a security margin to the minimum
load impedance. The drawback with this approach is that the sensitivity of the protection to
detect resistive faults is reduced.

The IED has a built-in function which shapes the characteristic according to the right part of
figure 198. The load encroachment algorithm will increase the possibility to detect high fault
resistances, especially for phase-to-earth faults at the remote line end. For example, for a
given setting of the load angle ArgLd the resistive blinder for the zone measurement can be
expanded according to the right part of the figure 198, given higher fault resistance coverage
without risk for unwanted operation due to load encroachment. This is valid in both directions.

The use of the load encroachment feature is essential for long heavily loaded lines, where there
might be a conflict between the necessary emergency load transfer and necessary sensitivity
of the distance protection. The function can also preferably be used on heavy loaded medium
long lines. For short lines, the major concern is to get sufficient fault resistance coverage. Load
encroachment is not a major problem. Nevertheless, always set RLdFw, RLdRv [3] and ArgLd
according to the expected maximum load since these settings are used internally in the
function as reference points to improve the performance of the phase selection.

Z1

ArgLd

[1]
RLdRv RLdFw

IEC09000248-3-en.vsdx
IEC09000248 V3 EN-US

Figure 198: Load encroachment phenomena

8.12.7.10 Simplified logic schemes GUID-486BDAF6-6AE2-4671-91AF-4D2F8EBE71AC v6

PHSL1, PHSL2,...PHSL3L1 are internal binary logical signals from the phase-selection element.
They correspond directly to the six loops of the distance zones and determine which loops
should be released to possibly issue a start or a trip.

[3] RLdRv=RLdRvFactor*RLdFw.

372 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

FWL1, FWL2,...FWL3L1 and RVL1, RVL2,...RVL3L1 are the internal binary signals from the
directional element. An FW signal is set true if the criteria for a forward fault or load is fulfilled
for its particular loop. The same applies to the reverse (RV) signals.

The internal input 'IN present' is true if the residual current (3I0) exceeds 7% of IBase. However,
if current transformer saturation is detected, this criterion is changed to residual voltage
(3U0) exceeding 5% of UBase/sqrt(3) instead.

FW(Ln & LmLn)

FW(Ln & LmLn)

RV(Ln & LmLn)

DirModeZ3-5
TRUE (1)
FW(Ln & LmLn) Forward
RV(Ln & LmLn) Reverse

IEC12000137-2-en.vsd
IEC12000137 V3 EN-US

Figure 199: Connection of directional signals to zones

Line distance protection REL670 373


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

ZML1Zx PEZx
OR
PHSL1
AND

DIRL1Zx AND
ZML2Zx
PHSL2
AND

DIRL2Zx AND
ZML3Zx L1Zx
OR
PHSL3
AND

DIRL3Zx AND

ZML1L2Zx L2Zx
PHSL1L2 OR
AND

DIRL1L2Zx AND
ZML2L3Zx
PHSL2L3 L3Zx
AND OR
DIRL2L3Zx AND
ZML3L1Zx
PHSL3L1
AND

DIRL3L1Zx AND

L1N
PPZx
L2N OR
L3N
RELCNDZx Integer L1L2
to Bool
L2L3
NDZx
L1L3 OR

IEC12000140-2-en.vsdx
IEC12000140 V2 EN-US

Figure 200: Intermediate logic

374 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

TimerModeZx =
Enable PhPh or
Ph-E PhPh
PPZx AND tPPZx
OR AND
AND t
PEZx
AND tPEZx OR
OR
AND t
AND

BLOCK
VTSZ
BLKZx OR
BLKTRZx
OR TimerLinksZx
LoopLink (tPP-tPE)
ZoneLinkStart LoopLink & ZoneLink
OR
Phase Selection No Links
1st starting zone
External start FALSE (0)
LNKZ2
LNKZx
AND
OR
TimerLinksZx =
LNKZ4 LoopLink & ZoneLink
LNKZ5

EXTNST

IEC12000139-4-en.vsdx
IEC12000139 V4 EN-US

Figure 201: Logic for linking of timers

15 ms
TZx
t TRIPZx
AND

TRL1Zx
OR AND
BLOCK
VTSZ TRL2Zx
OR AND
BLKZx
TRL3Zx
AND
15 ms
L1Zx
t STL1Zx
AND
15 ms
L2Zx
t STL2Zx
AND
15 ms
t STL3Zx
AND

PPZx 15 ms
PEZx OR t STARTZx
AND

15 ms
NDZx
t STNDZx
AND

IEC12000138-2-en.vsd
IEC12000138 V2 EN-US

Figure 202: Start and trip outputs

Line distance protection REL670 375


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

15 ms
OR t STPE
AND

15 ms
OR t
AND

15 ms
OR t STNDL2
PHSL1L2 AND

15 ms
OR t STNDL3
AND

15 ms
OR t STPP
AND

BLOCK STARTND
OR
VTSZ OR

STPHS
STNDPE
AND

IEC12000133-3-en.vsdx
IEC12000133 V3 EN-US

Figure 203: Additional start outputs 1

PHSL1
FWL1 AND
15 ms
FWL2 AND OR t
AND

FWL3 AND 15 ms
PHSL1L2 OR t STFWL2
AND
FWL1L2 AND
PHSL2L3 15 ms
FWL2L3 AND OR t STFWL3
AND
FWL3L1 AND
OR
STFWPE
IN present AND

STFW1PH
=1
BLOCK
VTSZ OR

STFW2PH
=2

STFW3PH
=3

IEC12000134-2-en.vsd
IEC12000134 V2 EN-US

Figure 204: Additional start outputs 2

376 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

PHSL1
RVL1 AND
15 ms
RVL2 AND OR t
AND

RVL3 AND 15 ms
PHSL1L2 OR t STRVL2
AND
RVL1L2 AND
PHSL2L3 15 ms
RVL2L3 AND OR t STRVL3
AND
RVL3L1 AND
OR
STRVPE
IN present AND

BLOCK
VTSZ OR

IEC12000141-2-en.vsdx
IEC12000141 V2 EN-US

Figure 205: Additional start outputs 3

Line distance protection REL670 377


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

TDFWL1 AND
15 ms
TDFWL2 AND OR t
AND
PHSL3
TDFWL3 AND 15 ms
PHSL1L2 OR t STTDFWL2
AND
AND
AND 15 ms
PHSL2L3 OR t STTDFWL3
AND AND
AND
PHSL3L1
AND
AND

PHSL1
TDRVL1 AND
15 ms
TDRVL2 AND OR t
AND

AND 15 ms
OR t STTDRVL2
AND
AND
AND 15 ms
PHSL2L3 OR t STTDRVL3
AND AND
AND
PHSL3L1
AND
AND

VTSZ
OR
BLOCKTD

IEC18000241-1-en.vsdx
IEC18000241 V1 EN-US

Figure 206: Transient directional element


In Figure 206, inputs TDFWLx and TDRVLx (where, x = 1-3) are the directionalities calculated
internally by the transient directional element.

8.12.7.11 Measurement

Measurement supervision SEMOD54417-130 v4


The protection, control, and monitoring IEDs have functionality to measure and further
process information for currents and voltages obtained from the pre-processing blocks. The
number of processed alternate measuring quantities depends on the type of IED and built-in
options.

The information on measured quantities is available for the user at different locations:

• Locally by means of the local HMI


• Remotely using the monitoring tool within PCM600 or over the station bus
• Internally by connecting the analogue output signals to the Disturbance Report function

378 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Zero point clamping GUID-4894EF16-3376-48EB-863F-9CE14487ACAB v1


Measured value below zero point clamping limit is forced to zero. This allows the noise in the
input signal to be ignored. The zero point clamping limit is a setting (XZeroDb where X equals
Z).

Continuous monitoring of the measured quantity SEMOD54417-140 v5


Users can continuously monitor the measured quantity available in the function block by
means of four defined operating thresholds, see figure 207. The monitoring has two different
modes of operating:

• Overfunction, when the measured quantity exceeds the High limit (XHiLim) or High-high
limit (XHiHiLim) pre-set values
• Underfunction, when the measured quantity decreases under the Low limit (XLowLim) or
Low-low limit (XLowLowLim) pre-set values.

X_RANGE is illustrated in figure 207.

Y = Magnitude of the Measured Quantity

X_RANGE = 3
High-high limit

X_RANGE= 1 Hysteresis
High limit

X_RANGE=0

X_RANGE=0 t

Low limit

X_RANGE=2

Low-low limit
X_RANGE=4

IEC05000657-3-en.vsdx
IEC05000657 V3 EN-US

Figure 207: Presentation of operating limits


Each analogue output has one corresponding supervision level output (X_RANGE). The output
signal is an integer in the interval 0-4 (0: Normal, 1: High limit exceeded, 3: High-high limit
exceeded, 2: below Low limit and 4: below Low-low limit).

The logical value of the functional output signals changes according to figure 207.

The user can set the hysteresis (XLimHyst), which determines the difference between the
operating and reset value at each operating point, in wide range for each measuring channel
separately. The hysteresis is common for all operating values within one channel.

Actual value of the measured quantity SEMOD54417-150 v4


The actual value of the measured quantity is available locally and remotely. The measurement
is continuous for each measured quantity separately, but the reporting of the value to the
higher levels depends on the selected reporting mode. The following basic reporting modes
are available:

• Cyclic reporting (Cyclic)


• Amplitude dead-band supervision (Dead band)
• Integral dead-band supervision (Int deadband)

Line distance protection REL670 379


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

• Amplitude Deadband and 5s cyclic


• Amplitude Deadband and 30s cyclic
• Amplitude Deadband and 1min cyclic

Cyclic reporting SEMOD54417-158 v3


The cyclic reporting of measured value is performed according to chosen setting (XRepTyp).
The measuring channel reports the value independent of amplitude or integral dead-band
reporting.

In addition to the normal cyclic reporting the IED also report spontaneously when measured
value passes any of the defined threshold limits.

Y
Value Reported Value Reported
Value Reported Value Reported
(1st)

Y3 Value Reported
Y2 Y4

Y1 Y5

t (*) t (*) t (*) t (*)

t
Value 1

Value 2

Value 3

Value 4

Value 5

(*)Set value for t: XDbRepInt IEC05000500-2-en.vsdx

IEC05000500 V2 EN-US

Figure 208: Periodic reporting

Amplitude dead-band supervision SEMOD54417-163 v6


If a measuring value is changed, compared to the last reported value, and the change is larger
than the ±ΔY pre-defined limits that are set by user (XDbRepInt), then the measuring channel
reports the new value to a higher level. This limits the information flow to a minimum
necessary. Figure 209 shows an example with the amplitude dead-band supervision. The
picture is simplified: the process is not continuous but the values are evaluated with a time
interval of one execution cycle from each other.

380 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Value Reported
Y

Value Reported Value Reported


Value Reported
(1st)
Y3 Y
Y
Y2 Y
Y
Y
Y
Y1

IEC99000529-2-en.vsdx

IEC99000529 V2 EN-US

Figure 209: Amplitude dead-band supervision reporting


After the new value is reported, the ±ΔY limits for dead-band are automatically set around it.
The new value is reported only if the measured quantity changes more than defined by the ±ΔY
set limits.

Integral dead-band reporting SEMOD54417-167 v4


The measured value is reported if the time integral of all changes exceeds the pre-set limit
(XDbRepInt), figure 210, where an example of reporting with integral dead-band supervision is
shown. The picture is simplified: the process is not continuous but the values are evaluated
with a time interval of one execution cycle from each other.

The last value reported, Y1 in figure 210 serves as a basic value for further measurement. A
difference is calculated between the last reported and the newly measured value and is
multiplied by the time increment (discrete integral). The absolute values of these integral
values are added until the pre-set value is exceeded. This occurs with the value Y2 that is
reported and set as a new base for the following measurements (as well as for the values Y3,
Y4 and Y5).

The integral dead-band supervision is particularly suitable for monitoring signals with small
variations that can last for relatively long periods.

Line distance protection REL670 381


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Y A1 >=
A >= pre-set value
A2 >=
pre-set value pre-set value
Y3 A3 + A4 + A5 + A6 + A7 >=
pre-set value
Y2 A1 A2
A4 A6
Value Reported Y4 A3 A5 A7
Value
(1st) Value
A Reported Y5
Reported Value
Reported Value
Y1 Reported

t
IEC99000530-2-en.vsdx

IEC99000530 V2 EN-US

Figure 210: Reporting with integral dead-band supervision

Measurement ZMMMXU GUID-2DB6F5A4-A3C2-4BBA-8327-393B7F89EDC6 v4


The magnitude and angle of the impedance for each phase-to-earth and phase-to-phase loop
are available on local HMI, monitoring tools within PCM600 or to the station level, for example,
via IEC61850.

Phase-to-earth impedance measurement is calculated based on UL1/ IL1 , UL2 / IL2 , UL3 / IL3

and phase-to-phase impedance is calculated based on U L1 


 UL 2 / IL1  IL 2 ,
U L2 
 UL 3 / IL 2  IL 3  , U
L3 
 UL1 / IL 3  IL1  , where U LX and ILX are phase-to-earth
voltage and phase current.

When the operating current is too low, the impedance measurement can be erroneous. To
avoid such error, minimum operating current will be checked. For phase-earth currents or
phase-phase currents lower than 2% of IBase, the resistance and reactance of the impedance
are forced to 99 999 ohm, corresponding to a magnitude at 141419 (99 999*√2) ohm and an
angle at 45 degree.

382 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

8.12.8 Technical data


GUID-6C2EF52A-8166-4A23-9861-38931682AA7D v7

Table 199: ZMFPDIS, ZMFCPDIS technical data


Function Range or value Accuracy
Number of zones 3 selectable -
directions, 3 fixed
directions
Minimum operate current, Ph- (5-6000)% of IBase ±1.0% of Ir
Ph and Ph-E
Positive sequence reactance (0.01 - 3000.00) Pseudo continuous
reach, Ph-E and Ph-Ph loop ohm/p ramp:
±2.0% of set value
Positive sequence resistance (0.00 - 1000.00) Conditions:
reach, Ph-E and Ph-Ph loop ohm/p Voltage range: (0.1-1.1) x Ramp of shots:
Zero sequence reactance (0.01 - 9000.00) Ur ±2.0% of set value
reach ohm/p Current range: (0.5-30) x Conditions:
Ir IEC 60255-121 point B
Zero sequence resistive reach (0.00 - 3000.00) Angle: At 0 degrees and
ohm/p 85 degrees
Fault resistance reach, Ph-E (0.01 -9000.00) IEC 60255-121 points
and Ph-Ph ohm/l A,B,C,D,E

Dynamic overreach < 5% at 85 degrees -


measured with CVTs
and 0.5 < SIR < 30,
IEC 60255-121
Reset ratio 105% typically -
Directional blinders Forward: -15 – 120 Pseudo continuous ramp:
degrees ±2.0 degrees, IEC 60255-121
Reverse: 165 – -60
degrees
Resistance determining the (0.01 - 5000.00) Pseudo continuous Ramp of shots:
load impedance area - forward ohm/p ramp: ±5.0% of set value
±2.0% of set value Conditions:
Conditions: Tested at ArgLd = 30
Tested at ArgLd = 30 degrees
degrees
Angle determining the load 5 - 70 degrees Pseudo continuous ramp:
impedance area ±2.0 degrees
Conditions:
Tested at RLdFw = 20 ohm/p
Definite time delay to trip, Ph- (0.000-60.000) s ±0.2% of set value or ±35 ms whichever is greater
E and Ph-Ph operation
Operate time 16 ms typically, IEC -
60255-121
Reset time at 0.1 to 2 x Zreach Min. = 20 ms -
Max. = 35 ms

Line distance protection REL670 383


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

8.13 Power swing detection ZMRPSB IP14499-1 v3

8.13.1 Identification
M14853-1 v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Power swing detection ZMRPSB 68

Zpsb

SYMBOL-EE V1 EN-US

8.13.2 Functionality M13873-3 v12

Power swings may occur after disconnection of heavy loads or trip of big generation plants.

Power swing detection function (ZMRPSB ) is used to detect power swings and initiate block
of all distance protection zones. Occurrence of earth-fault currents during a power swing
inhibits the ZMRPSB function, to allow fault clearance.

8.13.3 Function block M13884-3 v5

ZMRPSB
I3P* START
U3P* ZOUT
BLOCK ZIN
BLKI01
BLKI02
BLK1PH
REL1PH
BLK2PH
REL2PH
I0CHECK
TRSP
EXTERNAL

IEC06000264-2-en.vsd
IEC06000264 V2 EN-US

Figure 211: ZMRPSB function block

8.13.4 Signals
PID-3663-INPUTSIGNALS v6

Table 200: ZMRPSB Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKI01 BOOLEAN 0 Block inhibit of start output for slow swing condition
BLKI02 BOOLEAN 0 Block inhibit of start output for subsequent residual current
detection
BLK1PH BOOLEAN 0 Block one-out-of-three-phase operating mode
REL1PH BOOLEAN 0 Release one-out-of-three-phase operating mode
Table continues on next page

384 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Name Type Default Description


BLK2PH BOOLEAN 0 Block two-out-of-three-phase operating mode
REL2PH BOOLEAN 0 Release two-out-of-three-phase operating mode
I0CHECK BOOLEAN 0 Residual current (3I0) detection used to inhibit start output
TRSP BOOLEAN 0 Single-pole tripping command issued by tripping function
EXTERNAL BOOLEAN 0 Input for external detection of power swing

PID-3663-OUTPUTSIGNALS v6

Table 201: ZMRPSB Output signals


Name Type Description
START BOOLEAN Power swing detected
ZOUT BOOLEAN Measured impedance within outer impedance boundary
ZIN BOOLEAN Measured impedance within inner impedance boundary

8.13.5 Settings
PID-3663-SETTINGS v6

Table 202: ZMRPSB Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Mode On / Off
On
X1InFw 0.01 - 3000.00 Ohm/p 0.01 30.00 Inner reactive boundary, forward
R1LIn 0.01 - 1000.00 Ohm/p 0.01 30.00 Line resistance for inner characteristic
angle
R1FInFw 0.01 - 1000.00 Ohm/l 0.01 30.00 Fault resistance coverage to inner
resistive line, forward
X1InRv 0.01 - 3000.00 Ohm/p 0.01 30.00 Inner reactive boundary, reverse
R1FInRv 0.01 - 1000.00 Ohm/l 0.01 30.00 Fault resistance line to inner resistive
boundary, reverse
OperationLdCh Off - - On Operation of load discrimination
On characteristic
RLdOutFw 0.01 - 3000.00 Ohm/p 0.01 30.00 Outer resistive load boundary,
forward
ArgLd 5 - 70 Deg 1 25 Load angle determining load
impedance area
RLdOutRv 0.01 - 3000.00 Ohm/p 0.01 30.00 Outer resistive load boundary, reverse
kLdRFw 0.50 - 0.90 Mult 0.01 0.75 Multiplication factor for inner resistive
load boundary, forward
kLdRRv 0.50 - 0.90 Mult 0.01 0.75 Multiplication factor for inner resistive
load boundary, reverse
tEF 0.000 - 60.000 s 0.001 3.000 Timer for overcoming single-pole
reclosing dead time
IMinOpPE 5 - 30 %IB 1 10 Minimum operate current in % of
IBase

Line distance protection REL670 385


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Table 203: ZMRPSB Group settings (advanced)


Name Values (Range) Unit Step Default Description
tP1 0.000 - 60.000 s 0.001 0.045 Timer for detection of initial power
swing
tP2 0.000 - 60.000 s 0.001 0.015 Timer for detection of subsequent
power swings
tW 0.000 - 60.000 s 0.001 0.250 Waiting timer for activation of tP2
timer
tH 0.000 - 60.000 s 0.001 0.500 Timer for holding power swing START
output
tR1 0.000 - 60.000 s 0.001 0.300 Timer giving delay to inhibit by the
residual current
tR2 0.000 - 60.000 s 0.001 2.000 Timer giving delay to inhibit at very
slow swing

Table 204: ZMRPSB Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

8.13.6 Operation principle


M13877-4 v5
The power swing detection (ZMRPSB ) function comprises an inner and an outer quadrilateral
measurement characteristic with load encroachment, as shown in figure 212.

Its principle of operation is based on the measurement of the time it takes for a power swing
transient impedance to pass through the impedance area between the outer and the inner
characteristics. The power swings are identified by transition times longer than a transition
time set on corresponding timers. The impedance measuring principle is the same as that
used for the distance protection zones. The impedance and the characteristic passing times
are measured in all three phases separately.

One-out-of-three or two-out-of-three operating modes can be selected according to the


specific system operating conditions.

386 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

X1OutFw jX ZL R1LIn
X1InFw DFw

j
DRv
R1FInRv R1FInFw
DFw
ArgLd j

ArgLd
DRv
DFw

DFw

R
DFw
DRv

RLdInRv RLdInFw
DFw

DRv
RLdOutRv RLdOutFw

j DRv X1InRv
X1OutRv

IEC09000222_1_en.vsd
IEC09000222 V1 EN-US

Figure 212: Operating characteristic for ZMRPSB function (setting parameters in italic)
The impedance measurement within ZMRPSB function is performed by solving equation 96
and equation 97 (n = 1, 2, 3 for each corresponding phase L1, L2 and L3).

æ ULn ö
Re çç ÷÷ £ Rset
è I Ln ø
EQUATION1183 V2 EN-US (Equation 96)

æ ULn ö
Imçç ÷÷ £ Xset
è ILn ø
EQUATION1184 V2 EN-US (Equation 97)

The Rset and Xset are R and X boundaries.

8.13.6.1 Resistive reach in forward direction M13877-6 v3

To avoid load encroachment, the resistive reach is limited in forward direction by setting the
parameter RLdOutFw which is the outer resistive load boundary value while the inner resistive
boundary is calculated according to equation 98.

RLdInFw = kLdRFw·RLdOutFw
EQUATION1185 V2 EN-US (Equation 98)

where:
kLdRFw is a settable multiplication factor less than 1

Line distance protection REL670 387


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

The slope of the load encroachment inner and outer boundary is defined by setting the
parameter ArgLd.

The load encroachment in the fourth quadrant uses the same settings as in the first quadrant
(same ArgLd and RLdOutFw and calculated value RLdInFw).

The quadrilateral characteristic in the first quadrant is tilted to get a better adaptation to the
distance measuring zones. The angle is the same as the line angle and derived from the setting
of the reactive reach inner boundary X1InFw and the line resistance for the inner boundary
R1LIn. The fault resistance coverage for the inner boundary is set by the parameter R1FInFw.

From the setting parameter RLdOutFw and the calculated value RLdInFw a distance between
the inner and outer boundary, DFw, is calculated. This value is valid for R direction in first and
fourth quadrant and for X direction in first and second quadrant.

8.13.6.2 Resistive reach in reverse direction M13877-15 v3

To avoid load encroachment in reverse direction, the resistive reach is limited by setting the
parameter RLdOutRv for the outer boundary of the load encroachment zone. The distance to
the inner resistive load boundary RLdInRv is determined by using the setting parameter
kLdRRv in equation 99.

RLdInRv = kLdRRv·RLdOutRv
EQUATION1187 V2 EN-US (Equation 99)

where:
kLdRRv is a settable multiplication factor less than 1

From the setting parameter RLdOutRv and the calculated value RLdInRv, a distance between
the inner and outer boundary, DRv, is calculated. This value is valid for R direction in second
and third quadrant and for X direction in third and fourth quadrant.

The inner resistive characteristic in the second quadrant outside the load encroachment part
corresponds to the setting parameter R1FInRv for the inner boundary. The outer boundary is
internally calculated as the sum of DRv+R1FInRv.

The inner resistive characteristic in the third quadrant outside the load encroachment zone
consist of the sum of the settings R1FInRv and the line resistance R1LIn. The argument of the
tilted lines outside the load encroachment is the same as the tilted lines in the first quadrant.
The distance between the inner and outer boundary is the same as for the load encroachment
in reverse direction, that is DRv.

8.13.6.3 Reactive reach in forward and reverse direction M13877-20 v3

The inner characteristic for the reactive reach in forward direction correspond to the setting
parameter X1InFw and the outer boundary is defined as X1InFw + DFw,

where:
DFw = RLdOutFw - KLdRFw · RLdOutFw

The inner characteristic for the reactive reach in reverse direction correspond to the setting
parameter X1InRv for the inner boundary and the outer boundary is defined as X1InRv + DRv.

388 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

where:
DRv = RLdOutRv - KLdRRv · RLdOutRv

8.13.6.4 Basic detection logic M13877-24 v8

The operation of the Power swing detection ZMRPSB is only released if the magnitude of the
current is above the setting of the minimum operating current, IMinOpPE.

ZMRPSB function can operate in two operating modes:

• The 1 out of 3 operating mode is based on detection of power swing in any of the three
phases. Figure 213 presents a composition of an internal detection signal DET-L1 in this
particular phase.
• The 2 out of 3 operating mode is based on detection of power swing in at least two out of
three phases. Figure 214 presents a composition of the detection signals DET1of3 and
DET2of3.

Signals ZOUTLn (outer boundary) and ZINLn (inner boundary) in figure 213 are related to the
operation of the impedance measuring elements in each phase separately (n represents the
corresponding L1, L2 and L3). They are internal signals, calculated by ZMRPSB function.

The tP1 timer in figure 213 serve as detection of initial power swings, which are usually not as
fast as the later swings are. The tP2 timer become activated for the detection of the
consecutive swings, if the measured impedance exit the operate area and returns within the
time delay, set on the tW waiting timer. The upper part of figure 213 (internal input signal
ZOUTL1, ZINL1, AND-gates and tP-timers) are duplicated for phase L2 and L3. All tP1 and tP2
timers in the figure have the same settings.

ZOUTL1 AND
0-tP1
ZINL1 0 OR
-loop
0-tP2
-loop
AND
0
OR DET-L1
AND AND

ZOUTL2 OR
ZOUTL3

detected 0
0-tW

IEC05000113-2-en.vsd
IEC05000113 V2 EN-US

Figure 213: Detection of power swing in phase L1

Line distance protection REL670 389


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

DET-L1
DET-L2 DET1of3 - int.
>1
DET-L3

&

DET2of3 - int.
& >1

&

IEC01000057-2-en.vsd
IEC01000057-TIFF V2 EN-US

Figure 214: Detection of power swing for 1-of-3 and 2-of-3 operating mode

ZOUTL1 ZOUT
OR
ZOUTL2 ZINL1
ZIN
ZOUTL3 AND ZINL2 OR

ZINL3
tEF
TRSP
t AND

I0CHECK

10 ms
AND t
BLKI02 OR

tR1
AND t INHIBIT
OR
-loop
tR2
BLKI01 AND t
BLOCK
-loop
DET1of3 - int.
REL1PH
AND
BLK1PH
tH
DET2of3 - int. OR t
REL2PH
AND
BLK2PH OR START
AND
EXTERNAL

en05000114.vsd
IEC05000114 V1 EN-US

Figure 215: Simplified block diagram for ZMRPSB function

8.13.6.5 Operating and inhibit conditions M13877-38 v4

Figure 215 presents a simplified logic diagram for the Power swing detection function
ZMRPSB. The internal signals DET1of3 and DET2of3 relate to the detailed logic diagrams in
figure 213 and figure 214 respectively.

390 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Selection of the operating mode is possible by the proper configuration of the functional input
signals REL1PH, BLK1PH, REL2PH, and BLK2PH.

The load encroachment characteristic can be switched off by setting the parameter
OperationLdCh = Off, but notice that the DFw and DRv will still be calculated from RLdOutFw
and RLdOutRv. The characteristic will in this case be only quadrilateral.

There are four different ways to form the internal INHIBIT signal:

• Logical 1 on functional input BLOCK inhibits the output START signal instantaneously.
• The INHIBIT internal signal is activated, if the power swing has been detected and the
measured impedance remains within its operate characteristic for the time, which is
longer than the time delay set on tR2 timer. It is possible to disable this condition by
connecting the logical 1 signal to the BLKI01 functional input.
• The INHIBIT internal signal is activated after the time delay, set on tR1 timer, if an earth-
fault appears during the power swing (input IOCHECK is high) and the power swing has
been detected before the earth-fault (activation of the signal I0CHECK). It is possible to
disable this condition by connecting the logical 1 signal to the BLKI02 functional input.
• The INHIBIT logical signals becomes logical 1, if the functional input I0CHECK appears
within the time delay, set on tEF timer and the impedance has been seen within the outer
characteristic of ZMRPSB operate characteristic in all three phases. This function prevents
the operation of ZMRPSB function in cases, when the circuit breaker closes onto
persistent single-phase fault after single-phase autoreclosing dead time, if the initial
single-phase fault and single-phase opening of the circuit breaker causes the power swing
in the remaining two phases.

8.13.7 Technical data


M16036-1 v10

Table 205: ZMRPSB technical data


Function Range or value Accuracy
Reactive reach (0.10-3000.00) W/phase ±2.0% static accuracy
Conditions:
Voltage range: (0.1-1.1) x Ur
Current range: (0.5-30) x Ir
Angle: at 0 degrees and 85 degrees
Resistive reach (0.10–1000.00) W/loop
Power swing detection (0.000-60.000) s ±0.2% or ±10 ms whichever is greater
operate time
Second swing reclaim operate (0.000-60.000) s ±0.2% or ±20 ms whichever is greater
time
Minimum operate current (5-30)% of IBase ±1.0% of Ir

8.14 Automatic switch onto fault logic ZCVPSOF SEMOD153633-1 v3

8.14.1 Identification
SEMOD155890-2 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Automatic switch onto fault logic ZCVPSOF - -

Line distance protection REL670 391


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

8.14.2 Functionality SEMOD153644-5 v9

Automatic switch onto fault logic ZCVPSOF is a function that gives an instantaneous trip when
closing the breaker onto a fault. A dead-line detection check is provided to activate ZCVPSOF
when the line is de-energized.

Mho distance protections cannot operate for switch onto fault conditions when the phase
voltages are close to zero. An additional logic based on UI Level is used for this purpose.

ZCVPSOF is a complementary function to the distance protection function. It is enabled for


operation either by the closing command to the circuit breaker (normally closed auxiliary
contact of the circuit breaker) to the BC input or automatically by the dead-line detection.
Once enabled, it remains active for tSOTF duration after the enabling signal is reset. The
protection function can be enabled for tripping during the activated time by connecting the
functions included in the terminal to the ZACC input. Therefore, the start of the selected
protection functions connected to ZACC during the enabled condition results in an immediate
TRIP output from the function.

8.14.3 Function block SEMOD156265-4 v6

IEC06000459 V3 EN-US

Figure 216: ZCVPSOF function block

8.14.4 Signals SEMOD156281-1 v2

PID-3875-INPUTSIGNALS v10

Table 206: ZCVPSOF Input signals


Name Type Default Description
I3P GROUP - Current DFT
SIGNAL
U3P GROUP - Voltage DFT
SIGNAL
BLOCK BOOLEAN 0 Block of function
START_DLYD BOOLEAN 0 Start from function to be accelerated with delay by SOTF
BC BOOLEAN 0 External enabling of SOTF
ZACC BOOLEAN 0 Distance zone to be accelerated by SOTF

PID-3875-OUTPUTSIGNALS v9

Table 207: ZCVPSOF Output signals


Name Type Description
TRIP BOOLEAN Trip output

8.14.5 Settings IP15016-1 v2

392 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

PID-3875-SETTINGS v10

Table 208: ZCVPSOF Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
AutoInitMode DLD disabled - - DLD disabled Automatic switch onto fault
Voltage initialization
Current
Current & Voltage
Mode Impedance - - UILevel Mode of operation of SOTF Function
UILevel
UILvl&Imp
IPh< 1 - 100 %IB 1 20 Current level for detection of dead line
in % of IBase
UPh< 1 - 100 %UB 1 70 Voltage level for detection of dead line
in % of UBase
tDuration 0.000 - 60.000 s 0.001 0.020 Time delay for UI detection (s)
tSOTF 0.000 - 60.000 s 0.001 1.000 Drop off delay time of switch onto
fault function
tDLD 0.000 - 60.000 s 0.001 0.200 Delay time for activation of dead line
detection
tOperate 0.03 - 120.00 s 0.01 0.03 Time delay to operate of switch onto
fault function

Table 209: ZCVPSOF Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

8.14.6 Monitored data


PID-3875-MONITOREDDATA v7

Table 210: ZCVPSOF Monitored data


Name Type Values (Range) Unit Description
IL1 REAL - A Current in phase L1
IL2 REAL - A Current in phase L2
IL3 REAL - A Current in phase L3
UL1 REAL - kV Voltage in phase L1
UL2 REAL - kV Voltage in phase L2
UL3 REAL - kV Voltage in phase L3

8.14.7 Operation principle SEMOD153665-4 v8

The automatic switch onto fault logic ZCVPSOF can be activated externally (by the breaker-
closed input) or internally (automatically) with the dead-line detection using the UI level-based
logic. When the setting AutoInitMode is DLD disabled, ZCVPSOF is activated by an external
binary input BC. When the setting AutoInitMode is set to Voltage, Current or Current & Voltage
modes, ZCVPSOF is activated by the dead-line detection.

Line distance protection REL670 393


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

The activation from the dead-line detection function is released if the internal signal DeadLine
from the UILevel Detector function is activated at the same time as the inputs ZACC and
START_DLYD are not activated at least for the duration of tDLD. The internal signal DeadLine
from the UILevel Detector function is activated under any of the following conditions:

• If all three-phase currents are below the setting IPh< and the AutoInitMode setting is set
to Current
• If all three-phase voltages are below the setting UPh< and the AutoInitMode setting is set
to Voltage
• If all three-phase currents and voltages are below the settings IPh< and UPh< and the
AutoInitMode setting is set to Current & Voltage

Once the dead line drops off after energization or once BC drops off, the activated signal is
extended for the duration of tSOTF.

The internal signal SOTFUILevel is activated if the phase voltage is below the set UPh< and
the corresponding phase current is above the set IPh< for a time longer than the duration set
by tDuration.

To get the TRIP signal, one of the different operate modes must also be selected with the
Mode parameter:
• Mode = Impedance; TRIP is released if either the ZACC input (connected normally to a
nondirectional distance protection start zone) or the START_DLYD input is activated. If
START_DLD is activated, TRIP is released after a delay of tOperate.
• Mode = UILevel; TRIP is released if UILevel detector is activated
• Mode = UILvl&Imp; TRIP is released based either on the impedance-measured criteria or
UILevel detection

The ZCVPSOF function can be blocked by activating the input BLOCK.

The measured phase voltages and currents are provided as service values.

BLOCK
15ms
BC TRIP
& t

ZACC tSOTF
tDLD t
START_DLYD ≥1
& t

≥1
tOperate
t

I3P
U3P

DeadLine
IPh< UILevel tDuration
Detector t
UPh<

AutoInitMode

&
Mode = Impedance

SOTFUILevel
& ≥1
Mode = UILevel

≥1
&
Mode = UILvl&Imp

IEC07000084 V3 EN-US

Figure 217: Simplified logic diagram for Automatic switch onto fault logic

394 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

8.14.8 Technical data SEMOD173230-1 v1

M16043-1 v12

Table 211: ZCVPSOF technical data


Parameter Range or value Accuracy
Operate voltage, detection of dead line (1–100)% of ±0.5% of Ur
UBase
Operate current, detection of dead line (1–100)% of ±1.0% of Ir
IBase
Time delay to operate for the switch onto fault (0.03-120.00) s ±0.2% or ±20 ms whichever is greater
function
Time delay for UI detection (0.000-60.000) s ±0.2% or ±20 ms whichever is greater
Delay time for activation of dead line detection (0.000-60.000) s ±0.2% or ±20 ms whichever is greater
Drop-off delay time of switch onto fault function (0.000-60.000) s ±0.2% or ±30 ms whichever is greater

8.15 Power swing logic PSLPSCH SEMOD153597-1 v3

8.15.1 Identification
SEMOD175682-2 v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Power swing logic PSLPSCH - -

8.15.2 Functionality SEMOD131350-4 v4

Power Swing Logic (PSLPSCH) is a complementary function to Power Swing Detection


(ZMRPSB) function. It provides possibility for selective tripping of faults on power lines during
system oscillations (power swings or pole slips), when the distance protection function should
normally be blocked. The complete logic consists of two different parts:

• Communication and tripping part: provides selective tripping on the basis of special
distance protection zones and a scheme communication logic, which are not blocked
during the system oscillations.
• Blocking part: blocks unwanted operation of instantaneous distance protection zone 1 for
oscillations, which are initiated by faults and their clearing on the adjacent power lines
and other primary elements.

Line distance protection REL670 395


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

8.15.3 Function block SEMOD171917-4 v3

PSLPSCH
BLOCK TRIP
STZMUR STZMURPS
STZMOR BLKZMUR
STPSD BLKZMOR
STDEF CS
STZMPSD
CACC
AR1P1
CSUR
CR

IEC07000026-3-en.vsd
IEC07000026 V3 EN-US

Figure 218: PSLPSCH function block

8.15.4 Signals
PID-3664-INPUTSIGNALS v7

Table 212: PSLPSCH Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
STZMUR BOOLEAN 0 Start of the underreaching zone
STZMOR BOOLEAN 0 Start of the overreaching zone
STPSD BOOLEAN 0 Power swing detected
STDEF BOOLEAN 0 Start from Earth Fault Protection in forward or reverse
direction
STZMPSD BOOLEAN 0 Operation of Power Swing Detection external characteristic
CACC BOOLEAN 0 Overreaching ZM zone to be accelerated
AR1P1 BOOLEAN 0 Single pole auto-reclosing in progress
CSUR BOOLEAN 0 Carrier send by the underreaching power-swing zone
CR BOOLEAN 0 Carrier receive signal during power swing detection
operation

PID-3664-OUTPUTSIGNALS v7

Table 213: PSLPSCH Output signals


Name Type Description
TRIP BOOLEAN Trip through Power Swing Logic
STZMURPS BOOLEAN Start of Underreaching zone controlled by PSL to be used in
configuration
BLKZMUR BOOLEAN Block trip of underreaching impedance zone
BLKZMOR BOOLEAN Block trip of overreaching distance protection zones
CS BOOLEAN Carrier send signal controlled by the power swing

396 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

8.15.5 Settings
PID-3664-SETTINGS v6

Table 214: PSLPSCH Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
tDZ 0.000 - 60.000 s 0.001 0.050 Permitted max oper time diff between
higher and lower zone
tDZMUR 0.000 - 60.000 s 0.001 0.200 Delay for oper of underreach zone
with detected diff in oper time
tCS 0.000 - 60.000 s 0.001 0.100 Conditional timer for sending the CS
at power swings
tTrip 0.000 - 60.000 s 0.001 0.100 Conditional timer for tripping at
power swings
tBlkTr 0.000 - 60.000 s 0.001 0.300 Timer for blocking the overreaching
zones trip

8.15.6 Operation principle

8.15.6.1 Communication and tripping logic SEMOD131352-4 v2

Communication and tripping logic as used by the power swing distance protection zones is
schematically presented in figure 219.

STDEF
AR1P1 &

STPSD tCS
CS
BLOCK & t &

CSUR
BLKZMPS
tBlkTr &
tTrip t
t

CACC TRIP
>1
CR &

en06000236.vsd
IEC06000236 V1 EN-US

Figure 219: Simplified logic diagram – power swing communication and tripping logic
The complete logic remains blocked as long as there is a logical one on the BLOCK functional
input signal. Presence of the logical one on the STDEF functional input signal also blocks the
logic as long as this block is not released by the logical one on the AR1P1 functional input
signal. The functional output signal BLKZMPS remains logical one as long as the function is not
blocked externally (BLOCK is logical zero) and the earth-fault is detected on protected line
(STDEF is logical one), which is connected in three-phase mode (AR1P1 is logical zero). Timer
tBlkTr prolongs the duration of this blocking condition, if the measured impedance remains
within the operate area of the Power Swing Detection (ZMRPSB) function (STPSD input active).
The BLKZMPS can be used to block the operation of the power-swing zones.

Line distance protection REL670 397


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Logical one on functional input CSUR, which is normally connected to the TRIP functional
output of a power swing carrier sending zone, activates functional output CS, if the function is
not blocked by one of the above conditions. It also activates the TRIP functional output.

Initiation of the CS functional output is possible only, if the STPSD input has been active longer
than the time delay set on the security timer tCS.

Simultaneous presence of the functional input signals PLTR_CRD and CR (local trip condition)
also activates the TRIP functional output, if the function is not blocked by one of the above
conditions and the STPSD signal has been present longer then the time delay set on the trip
timer tTrip.

8.15.6.2 Blocking logic SEMOD131352-14 v2

Figure 220 presents the logical circuits, which control the operation of the underreaching zone
(zone 1) at power swings, caused by the faults and their clearance on the remote power lines.

&

BLKZMH
&
STZML tZL
STZMLL
BLOCK & t >1
&
STMZH tDZ
STZMPSD & t
>1
STPSD

&
-loop

en06000237.vsd
IEC06000237 V1 EN-US

Figure 220: Control of underreaching distance protection (Zone 1) at power swings


caused by the faults and their clearance on adjacent lines and other system
elements
The logic is disabled by a logical one on functional input BLOCK. It can start only if the
following conditions are simultaneously fulfilled:

• STPSD functional input signal must be a logical zero. This means, that Power swing
detection (ZMRPSB) function must not detect power swinging over the protected power
line.
• STZMPSD functional input must be a logical one. This means that the impedance must be
detected within the external boundary of ZMRPSB function.
• STZMOR functional input must be a logical one. This means that the fault must be
detected by the overreaching distance protection zone, for example zone 2.

The STZMURPS functional output, which can be used in complete terminal logic instead of a
normal distance protection zone 1, becomes active under the following conditions:

• If the STZMUR signal appears at the same time as the STZMOR or if it appears with a time
delay, which is shorter than the time delay set on timer tDZ.
• If the STZMUR signal appears after the STZMOR signal with a time delay longer than the
delay set on the tDZ timer, and remains active longer than the time delay set on the tZL
timer.

398 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

The BLKZMOR functional output signal can be used to block the operation of the higher
distance protection zone, if the fault has moved into the zone 1 operate area after tDZ time
delay.
SEMOD171935-5 v5

Table 215: PSLPSCH technical data


Function Range or value Accuracy
Permitted maximum (0.000 — 60.0000) s ±0,2% or ±15 ms whichever is greater
operating time difference
between higher and lower
zone
Delay for operation of (0.000 — 60.0000) s ±0,2% or ±15 ms whichever is greater
underreach zone with
detected difference in
operating time
Conditional timer for (0.000 — 60.0000) s ±0,2% or ±15 ms whichever is greater
sending the CS at power
swings
Conditional timer for (0.000 — 60.0000) s ±0,2% or ±15 ms whichever is greater
tripping at power swings
Timer for blocking the (0.000 — 60.0000) s ±0,2% or ±15 ms whichever is greater
overreaching zones trip

8.16 Pole slip protection PSPPPAM SEMOD156709-1 v2

8.16.1 Identification
SEMOD158949-2 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Pole slip protection PSPPPAM Ucos 78

8.16.2 Functionality
SEMOD143246-17 v7
Sudden events in an electric power system such as large changes in load, fault occurrence or
fault clearance, can cause power oscillations referred to as power swings. In a non-recoverable
situation, the power swings become so severe that the synchronism is lost, a condition
referred to as pole slipping. The main purpose of the pole slip protection (PSPPPAM) is to
detect, evaluate, and take the required action for pole slipping occurrences in the power
system.

Line distance protection REL670 399


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

8.16.3 Function block SEMOD172911-4 v3

PSPPPAM
I3P* TRIP
U3P* TRIP1
BLOCK TRIP2
BLKGEN START
BLKMOTOR ZONE1
EXTZONE1 ZONE2
GEN
MOTOR
SFREQ
SLIPZOHM
SLIPZPER
UCOS
UCOSPER

IEC10000045-1-en.vsd
IEC10000045 V1 EN-US

Figure 221: PSPPPAM function block

8.16.4 Signals
PID-3526-INPUTSIGNALS v3

Table 216: PSPPPAM Input signals


Name Type Default Description
I3P GROUP - Current group connection
SIGNAL
U3P GROUP - Voltage group connection
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKGEN BOOLEAN 0 Block operation in generating direction
BLKMOTOR BOOLEAN 0 Block operation in motor direction
EXTZONE1 BOOLEAN 0 Extension of zone1 with zone2 region

PID-3526-OUTPUTSIGNALS v3

Table 217: PSPPPAM Output signals


Name Type Description
TRIP BOOLEAN Common trip signal
TRIP1 BOOLEAN Trip1 after the N1Limit slip in zone1
TRIP2 BOOLEAN Trip2 after the N2Limit slip in zone2
START BOOLEAN Common start signal
ZONE1 BOOLEAN First slip in zone1 region
ZONE2 BOOLEAN First slip in zone2 region
GEN BOOLEAN Generator is faster than the system
MOTOR BOOLEAN Generator is slower than the system
SFREQ REAL Slip frequency
SLIPZOHM REAL Slip impedance in ohms
SLIPZPER REAL Slip impedance in percent of ZBase
UCOS REAL UCosPhi voltage
UCOSPER REAL UCosPhi voltage in percent of UBase

400 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

8.16.5 Settings
PID-3526-SETTINGS v3

Table 218: PSPPPAM Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation On / Off
On
OperationZ1 Off - - On Operation Zone1 On / Off
On
OperationZ2 Off - - On Operation Zone2 On / Off
On
ImpedanceZA 0.00 - 1000.00 % 0.01 10.00 Forward impedance in % of Zbase
ImpedanceZB 0.00 - 1000.00 % 0.01 10.00 Reverse impedance in % of Zbase
ImpedanceZC 0.00 - 1000.00 % 0.01 10.00 Impedance of zone1 limit in % of
Zbase
AnglePhi 72.00 - 90.00 Deg 0.01 85.00 Angle of the slip impedance line
StartAngle 0.0 - 180.0 Deg 0.1 110.0 Rotor angle for the start signal
TripAngle 0.0 - 180.0 Deg 0.1 90.0 Rotor angle for the trip1 and trip2
signals
N1Limit 1 - 20 - 1 1 Count limit for the trip1 signal
N2Limit 1 - 20 - 1 3 Count limit for the trip2 signal

Table 219: PSPPPAM Group settings (advanced)


Name Values (Range) Unit Step Default Description
ResetTime 0.000 - 60.000 s 0.001 5.000 Time without slip to reset all signals

Table 220: PSPPPAM Non group settings (basic)


Name Values (Range) Unit Step Default Description
MeasureMode PosSeq - - PosSeq Measuring mode (PosSeq, L1L2, L2L3,
L1L2 L3L1)
L2L3
L3L1
InvertCTcurr No - - No Invert current direction
Yes
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

8.16.6 Monitored data


PID-3526-MONITOREDDATA v3

Table 221: PSPPPAM Monitored data


Name Type Values (Range) Unit Description
SFREQ REAL - Hz Slip frequency
SLIPZOHM REAL - Ohm Slip impedance in ohms
SLIPZPER REAL - % Slip impedance in percent of ZBase
UCOS REAL - kV UCosPhi voltage
UCOSPER REAL - % UCosPhi voltage in percent of UBase

Line distance protection REL670 401


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

8.16.7 Operation principle SEMOD155755-4 v4

If the generator is faster than the power system, the rotor movement in the impedance and
voltage diagram is from right to left and generating is signaled. If the generator is slower than
the power system, the rotor movement is from left to right and motoring is signaled (the
power system drives the generator as if it were a motor).

The movements in the impedance plane can be seen in Figure 222. The transient behavior is
described by the transient EMF's EA and EB, and by X'd, XT and the transient system impedance
ZS.

Zone 1 Zone 2

EB X’d XT XS EA

IED
B A

jX

XS

Pole slip
impedance XT
d Apparent generator
movement impedance R

X’d

IEC06000437_2_en.vsd
IEC06000437 V2 EN-US

Figure 222: Movements in the impedance plain

where:
X'd = transient reactance of the generator

XT = short-circuit reactance of the step-up transformer

ZS = impedance of the power system A

The detection of rotor angle is enabled when:

402 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

• the minimum current exceeds 0.10 IN (IN is IBase parameter set under general setting).
• the maximum voltage falls below 0.92 UBase
• the voltage Ucosφ (the voltage in phase with the generator current) has an angular
velocity of 0.2...8 Hz and
• the corresponding direction is not blocked.

en07000004.vsd
IEC07000004 V1 EN-US

Figure 223: Different generator quantities as function of the angle between the
equivalent generators
An alarm is given when movement of the rotor is detected and the rotor angle exceeds the
angle set for 'WarnAngle'.

Slipping is detected when:

• a change of rotor angle of min. 50 ms is recognized


• the slip line is crossed between ZA and ZB.

When the impedance crosses the slip line between ZB and ZC it counts as being in zone 1 and
between ZC and ZA in zone 2. The entire distance ZA-ZB becomes zone 1 when signal
EXTZONE1 is high (external device detects the direction of the centre of slipping).

After the first slip, the signals ZONE1 or ZONE2 and – depending on the direction of slip -
either GEN or MOTOR are issued.

Every time pole slipping is detected, the impedance of the point where the slip line is crossed
and the instantaneous slip frequency are displayed as measurements.

Further slips are only detected, if they are in the same direction and if the rate of rotor
movement has reduced in relation to the preceding slip or the slip line is crossed in the
opposite direction outside ZA-ZB. A further slip in the opposite direction within ZA-ZB resets all
the signals and is then signalled itself as a first slip.

Line distance protection REL670 403


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

The TRIP1 tripping command and signal are generated after N1 slips in zone 1, providing the
rotor angle is less than TripAngle. The TRIP2 signal is generated after N2 slips in zone 2,
providing the rotor angle is less than TripAngle.

All signals are reset if:

• the direction of movement reverses


• the rotor angle detector resets without a slip being counted or
• no rotor relative movement was detected during the time ResetTime.

Imin > 0.10 IBase

Ucos< 0.92 UBase AND

START
AND
0.2  Slip.Freq.  8 Hz

  startAngle

ZONE1
AND
Z cross line ZC - ZB

ZONE2
AND
Z cross line ZA - ZC

Counter
a
ab
N1Limit b TRIP1
AND

  tripAngle OR
TRIP

Counter
a
ab
N2Limit b TRIP2
AND

IEC07000005.vsd

IEC07000005 V2 EN-US

Figure 224: Simplified logic diagram for pole slip protection PSPPPAM

8.16.8 Technical data SEMOD175138-1 v1

GUID-88E02516-1BFE-4075-BEEB-027484814697 v2

Table 222: PSPPPAM technical data


Function Range or value Accuracy
Impedance reach (0.00 - 1000.00)% of Zbase ±2.0% of Ur/Ir

Zone 1 and Zone 2 trip (1 - 20) -


counters

404 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

8.17 Out-of-step protection OOSPPAM GUID-667DAF85-B87B-47AA-9EAA-CD349E66F22F v3

8.17.1 Identification
GUID-BF2F1533-BA39-48F0-A55C-0B13A393F780 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Out-of-step protection OOSPPAM 78

<

8.17.2 Functionality GUID-BF2F7D4C-F579-4EBD-9AFC-7C03296BD5D4 v8

The out-of-step protection (OOSPPAM ) function in the IED can be used for both generator
protection and as well for line protection applications.

The main purpose of the OOSPPAM function is to detect, evaluate, and take the required
action during pole slipping occurrences in the power system.

The OOSPPAM function detects pole slip conditions and trips the generator as fast as
possible, after the first pole-slip if the center of oscillation is found to be in zone 1, which
normally includes the generator and its step-up power transformer. If the center of oscillation
is found to be further out in the power system, in zone 2, more than one pole-slip is usually
allowed before the generator-transformer unit is disconnected. A parameter setting is
available to take into account the circuit breaker opening time. If there are several out-of-step
relays in the power system, then the one which finds the center of oscillation in its zone 1
should operate first.

Two current channels I3P1 and I3P2 are available in OOSPPAM function to allow the direct
connection of two groups of three-phase currents; that may be needed for very powerful
generators, with stator windings split into two groups per phase, when each group is
equipped with current transformers. The protection function performs a simple summation of
the currents of the two channels I3P1 and I3P2.

8.17.3 Function block GUID-CB98C615-8A93-438D-9DF0-542F333198AC v4

OOSPPAM
I3P1* TRIP
I3P2* TRIPZ1
U3P* TRIPZ2
BLOCK START
BLKGEN GENMODE
BLKMOT MOTMODE
EXTZ1 R
X
SLIPFREQ
ROTORANG
UCOSPHI

IEC12000188-3-en.vsd
IEC12000188 V3 EN-US

Figure 225: OOSPPAM function block

Line distance protection REL670 405


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

8.17.4 Signals
PID-3539-INPUTSIGNALS v10

Table 223: OOSPPAM Input signals


Name Type Default Description
I3P1 GROUP - Group connection for three-phase current input 1
SIGNAL
I3P2 GROUP - Group connection for three-phase current input 2
SIGNAL
U3P GROUP - Group connection for three-phase voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKGEN BOOLEAN 0 Block operation in generating direction
BLKMOT BOOLEAN 0 Block operation in motor direction
EXTZ1 BOOLEAN 0 Extension of zone1 reach to zone2 settings

PID-3539-OUTPUTSIGNALS v10

Table 224: OOSPPAM Output signals


Name Type Description
TRIP BOOLEAN Common trip, issued when either zone 1 or zone 2 give trip
TRIPZ1 BOOLEAN Zone 1 trip
TRIPZ2 BOOLEAN Zone 2 trip
START BOOLEAN Set when measured impedance enters lens characteristic
GENMODE BOOLEAN Generator rotates faster than the system during pole slip
MOTMODE BOOLEAN Generator rotates slower than the system during pole slip
R REAL Real part of measured positive-sequence impedance % of
UBase/(sqrt(3)*IBase)
X REAL Imaginary part of measured positive-seq impedance % of
UBase/(sqrt(3)*IBase)
SLIPFREQ REAL Slip frequency in Hz
ROTORANG REAL Rotor angle as estimated by the out-of-step function
UCOSPHI REAL Estimated Ucos(Phi) voltage during pole slip, in V

8.17.5 Settings
PID-3539-SETTINGS v10

Table 225: OOSPPAM Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
OperationZ1 Off - - On Operation Zone1 Off / On
On
ReachZ1 1.00 - 100.00 % ZFw 0.01 50.00 Percentage part of total forward
impedance; defines Z1 reach
OperationZ2 Off - - On Operation Zone2 Off / On
On
tBreaker 0.000 - 1.000 s 0.001 0.040 Breaker opening time; use default 0s
value if it is unknown

406 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Table 226: OOSPPAM Group settings (advanced)


Name Values (Range) Unit Step Default Description
NoOfSlipsZ1 1 - 20 - 1 1 Number of pole-slips in zone 1
required to get zone 1 trip
NoOfSlipsZ2 1 - 60 - 1 3 Number of pole-slips in zone 2
required to get zone 2 trip
tReset 1.000 - 60.000 s 0.001 6.000 Time without any slip required to
completely reset function

Table 227: OOSPPAM Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups
ForwardR 0.00 - 1000.00 %ZB 0.01 1.00 Real part of total forward impedance
for Z2, in % of UBase/(sqrt(3)*IBase)
ForwardX 0.00 - 1000.00 %ZB 0.01 10.00 Imag. part of total forward impedance
for Z2, in % of UBase/(sqrt(3)*IBase)
ReverseR 0.00 - 1000.00 %ZB 0.01 1.00 Real part of source impedance behind
relay, in % of UBase/(sqrt(3)*IBase)
ReverseX 0.00 - 1000.00 %ZB 0.01 10.00 Imag. part of source impedance
behind relay, in % of UBase/
(sqrt(3)*IBase)
InvertCTCurr No - - No Invert current direction
Yes

Table 228: OOSPPAM Non group settings (advanced)


Name Values (Range) Unit Step Default Description
StartAngle 90.0 - 130.0 Deg 0.1 110.0 Angle between two rotors to get the
start signal, in deg
TripAngle 15.0 - 90.0 Deg 0.1 60.0 Maximum rotor angle to allow trip
signals, in deg

8.17.6 Monitored data


PID-3539-MONITOREDDATA v8

Table 229: OOSPPAM Monitored data


Name Type Values (Range) Unit Description
CURRENT REAL - A Magnitude of the measured positive-
sequence current, in A
VOLTAGE REAL - kV Magnitude of the measured positive-
sequence voltage, in V
R REAL - % Real part of measured positive-
sequence impedance % of UBase/
(sqrt(3)*IBase)
X REAL - % Imaginary part of measured positive-
seq impedance % of UBase/
(sqrt(3)*IBase)
Table continues on next page

Line distance protection REL670 407


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

Name Type Values (Range) Unit Description


SLIPFREQ REAL - Hz Slip frequency in Hz
ROTORANG REAL - deg Rotor angle as estimated by the out-
of-step function
UCOSPHI REAL - kV Estimated Ucos(Phi) voltage during
pole slip, in V

8.17.7 Operation principle


GUID-787EEB01-B760-4D4B-AB4E-1DCD6ABFFF5E v6

General
Under balanced and stable conditions, a generator operates with a constant rotor angle
(power angle), delivering active electrical power to the power system, which is approximately
equal to the input mechanical power on the generator axis.The currents and voltages are
constant and stable. An out-of-step condition is characterized by periodic changes in the rotor
angle, that leads to a wild flow of the synchronizing power; so there are also periodic changes
of rotational speed, currents and voltages. When displayed in the complex impedance plane,
these changes are characterized by a cyclic change in the complex load impedance Z(R, X) as
measured at the terminals of the generator, or at the location of the instrument transformers
of a power line connecting two power subsystems. This is shown in Figure 226.

1.5 ← trajectory
of Z(R, X)

to the 3rd
The 2nd pole-slip
Imaginary part (X) of Z in Ohms

1 The 1st X in Ohms


pole slip
pole slip
occurred Pre-disturbance
occurred
RE normal load
- - - - -
- - - - ----------- - - - - Z(R, X)
0.5 - ---
3 ----
---- --
Zone 2 -- - 1 ---- - 0
- - 2 -- -
-
-
---- --
-
-
^ -^ ^ ^ ^ -^ ^ ^ ^ ^ ^ ^ --
- -- ^ ^-- ^ ^ ^ --^
Zone 1 - --- -- -
-
0 - -- relay --- -
- -- -- -
- -
- - - R in Ohms
limit of reach → - - -- -- -
- -- -
-- -- -- -
lens determined - - →----- ------ 0- - - pre-disturbance Z(R, X)
- -
------
- -- - - - --- - →
-0.5 by the setting - 1 → Z(R, X) under 3-phase fault
StartAngle = 120° SE 2 → Z(R, X) when fault cleared
3 → Z when pole-slip declared

-1
-1.5 -1 -0.5 0 0.5 1 1.5
Real part (R) of Z in Ohms
IEC10000109-1-en.vsd
IEC10000109 V1 EN-US

Figure 226: Loci of the complex impedance Z(R, X) for a typical case of generator losing
step after a short circuit that was not cleared fast enough
Under typical, normal load conditions, when the protected generator supplies the active and
the reactive power to the power system, the complex impedance Z(R, X) is in the 1st quadrant,
point 0 in Figure 226. One can see that under a three-phase fault conditions, the centre of
oscillation is at the point of fault, point 1, which is logical, as all three voltages are zero or near
zero at that point. Under the fault conditions the generator accelerated and when the fault
was finally cleared, the complex impedance Z(R, X) jumped to the point 2. By that time, the
generator has already lost its step, Z(R, X) continues its way from the right-hand side to the
left-hand side, and the 1st pole-slip cannot be avoided. If the generator is not immediately
disconnected, it will continue pole-slipping — see Figure 226, where two pole-slips (two pole-
slip cycles) are shown. Under out-of-step conditions, the centre of oscillation is where the

408 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

locus of the complex impedance Z(R, X) crosses the (impedance) line connecting the points SE
(Sending End), and RE (Receiving End). The point on the SE – RE line where the trajectory of
Z(R, X) crosses the impedance line can change with time and is mainly a function of the
internal induced voltages at both ends of the equivalent two-machine system, that is, at points
SE and RE.

Measurement of the magnitude, direction and rate-of-change of load impedance relative to a


generator’s terminals provides a convenient and generally reliable means of detecting whether
machines are out-of-step and pole-slipping is taking place. Measurement of the rotor (power)
angle δ is important as well.

Rotor (power) angle δ can be thought of as the angle between the two lines, connecting point
0 in Figure 226, that is, Z(R, X) under normal load, with the points SE and RE, respectively.
These two lines are not shown in Figure 226. Normal values of the power angle, that is, under
stable, steady-state, load conditions, are from 30 to 60 electrical degrees. It can be observed
in Figure 227 that the angle reaches 180 degrees when the complex impedance Z(R, X) crosses
the impedance line SE – RE. It then changes the sign, and continues from -180 degrees to 0
degrees, and so on. Figure 227 shows the rotor (power) angle and the magnitude of Z(R, X)
against time for the case from Figure 226.

4
|Z| in Ohms
rotor (power)
3 normal angle in rad
angle
Impe dance Z in Ohm and rotor a ngle in radian ®

load
Z(R, X) unde r fa ult lies |Z|
2
on the impe dance line
or nea r (for 3-ph faults )
1
0
0
fault 500 ms
-1 fa ult
occ urrs
Unde r 3-pha s e fa ult
condition rotor a ngle 3
-2
of a pp. ±180 de gre e s
is m e a s ure d ...
2
-3 Z(R,X) cros s e d
1 1 the im pe da nce line , Z-line ,
conne cting points S E - RE
-4
0 200 400 600 800 1000 1200 1400
Time in millis econds ®

IEC10000110-2-en.vsd
IEC10000110 V2 EN-US

Figure 227: Rotor (power) angle and magnitude of the complex impedance Z(R, X) against
the time
In order to be able to fully understand the principles of OOSPPAM, a stable case, that is, a case
where the disturbance does not make a generator to go out-of-step, must be shown.

Line distance protection REL670 409


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

1
SE RE
G X [Ohm]
0.8 Z(R,X) 20 ms
fault
relay after line out
- - - RE - - -
0.6 - - --
-- ----------- - pre-fault
Imaginary part (X) of Z in Ohms →
- --- - 4 -
zone 2 - --- -
--- Z(R,X)
0.4 -- - -
- -- - --- 2 -
- -
- --- -1 5
- --- fault→
- -- -
0.2 X-line → ^ -^ ^ ^ ^ ---^ ^ 3 -- -
- -
- ^ ^ ^ ^ ^ ^ --^- ^ ^ -
- -- Z-line→ -- ^ -^ 0
-- --
- -- -- - 6
0 - -- - - -
- -
- -
- -
limit of -- - R
- -- relay lens → --- -
-- -
-0.2 reach - -- 110° ---- -
zone 1- - --- -
-- -
-
--- -
- --- --- -
-0.4 -- --- ------ --
-- ------ -
- - - - -
-0.6 SE - - -
0 → pre-fault Z(R, X)
this circle forms 3 → Z(R, X) under fault
-0.8 the right-hand side 5 → Z 20 ms after line out
edge of the lens 6 → pow er line reclosed
-1
-1 -0.5 0 0.5 1 1.5
Real part (R) of Z in Ohms → IEC10000111-1-en.vsd
IEC10000111 V1 EN-US

Figure 228: A stable case where the disturbance does not make the generator to go out-
of-step
It shall be observed that for a stable case, as shown in Figure 228, where the disturbance does
not cause the generator to lose step, the complex impedance Z(R, X) exits the lens
characteristic on the same side (point 4) it entered it (point 2), and never re-enters the lens. In
a stable case, where the protected generator remains in synchronism, the complex impedance
returns to quadrant 1, and, after the oscillations fade, it returns to the initial normal load
position (point 0), or near.

8.17.7.1 Lens characteristic GUID-F9BD3225-C87F-4FA6-A267-2248F0A4E707 v6

A precondition in order to be able to construct a suitable lens characteristic is that the power
system in which OOSPPAM is installed, is modeled as a two-machine equivalent system, or as a
single machine – infinite bus equivalent power system. Then the impedances from the position
of OOSPPAM in the direction of the normal load flow (that is from the measurement point to
the remote system) can be taken as forward. The lens characteristic, as shown in Figure226
and Figure228, is obtained so that two equal in size but differently offset Mho characteristics
are set to overlap. The resultant lens characteristic is the loci of complex impedance Z(R, X) for
which the rotor (power) angle is constant, for example 110 degrees or 120 degrees; if the rotor
(power) angle approaches this value, then there is a high risk to have an out of step condition.
The limit-of- reach circle is constructed automatically by the algorithm; it is about 10% wider
than the the circle that has the line SE-RE as diameter (that is the out-of-step characteristic
which corresponds to the rotor (power) angle of 90 degrees). Figure 229 illustrates
construction of the lens characteristic for a power system.

410 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

X
Position of the OOS
- - - RE- - -
0.6 - - --- - relay is the origin of
- - -- --- - the R - X plane
- -- - -- -
- --- Ze -- -
- Zone 2 -- -- -
0.4 X-line - - - -
Imaginary part (X) of Z in Ohms --- --
-
determined - -- Zline -- -
- - - - -
by the → ^ ^- ^ --- --
^ ^ ^- ^ -- -
0.2 setting - ^ ^ ^ ^ -
- ^ ^ ^ --- ^ -
---
ReachZ1 - -- ^ ^ ^-
--- Ztr
- -- -- - R
0 - Zone 1 -- --
- -
-- relay -
- -- 120° -- Z(R,X) -
- -- --- -
-- ← Z-line -
-0.2 - -- Zgen -- -
- -- --- -
limit-of-reach → - -- -- -
-- -- ← Lens is- the locus
circle depends on -
- -- ---- of constant
- rotor (power)
-0.4 --
the position of the - -- --- - e.g. 120°.
- - --- - -- angle,-
points SE and RE - - - - - - - - -Lens' width determined
SE
-0.6 by the setting StartAngle

-0.8 -0.6 -0.4 -0.2 0 0.2 0.4 0.6 0.8 1


Real part (R) of Z in Ohms
IEC10000112-1-en.vsd
IEC10000112 V1 EN-US

Figure 229: Construction of the lens characteristic for a power system

ReverseZ
ReverseZ(ReverseR, ReverseX)) ForwardZ(ForwardR, ForwardX)

Zgen(Rgen , Xgen) Ztr(Rtr, Xtr) Zline(Rline, Xline) Zeq(Req, Xeq)

Generator Transformer Infinite power


13.8 kV 13.8 / 220 kV system
Power line System
13.8 kV 220 kV equivalent
G d Y

SE RE

Out-Of-Step ReverseR = Rg ForwardR = Rtr + Rline + Req


REG ReverseX = Xd’ ForwardX = Xtr + Xline + Xeq
protection
OOSPPAM
All impedances must be referred to the generator voltage 13.8 kV

IEC10000113-2-en.vsd
IEC10000113 V2 EN-US

Figure 230: Example of an actual power system


To be able to automatically construct the lens characteristic for a system shown in Figure 230,
the actual power system must be modeled as a two-machine equivalent system, or as a single
machine – infinite bus equivalent system, the following information is necessary: Zgen(Rgen,
Xgen), Ztr(Rtr, Xtr), Zline(Rline, Xline), Zeq(Req, Xeq), and the setting StartAngle , for example
120 degrees. All impedances must be referred to the voltage level where the out-of-step
protection relay is placed; in the case shown in Figure 230 the relay is connected to the
terminals of the generator and, therefore, the previous quantities shall be referred to the
generator nominal voltage and nominal current. The impedances from the position of the out-
of-step protection in the direction of the normal load flow can be taken as forward.

The out-of-step relay, as in Figure 230 looks into the system and the impedances in that
direction are forward impedances:

Line distance protection REL670 411


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

• ForwardX = Xtr + Xline + Xeq (All values referred to generator voltage)


• ForwardR = Rtr + Rline + Req (All values referred to generator voltage)

The impedances that can be measured in the reverse direction are:

• ReverseX = Xd' (Generator transient reactance suitable for this protection)


• ReverseR = Rg (Relatively very small, can often be neglected)

Resistances are much smaller than reactances, but in general can not be neglected. The ratio
(ForwardX + ReverseX) / (ForwardR + ReverseR) determines the inclination of the Z-line,
connecting the point SE (Sending End) and RE (Receiving End), and is typically approximately
85 degrees. While the length of the Z-line depends on the values of ForwardX, ReverseX,
ForwardR, and ReverseR, the width of the lens is a function of the setting StartAngle .The lens
is broader for smaller values of the StartAngle , and becomes a circle for StartAngle = 90
degrees.

When the complex impedance Z(R, X) enters the lens, pole slipping is imminent, and a start
signal is issued. The angle recommended to form the lens is 110 or 120 degrees, because it is
this rotor (power) angle where problems with dynamic stability usually begin. Rotor (power)
angle 120 degrees is sometimes called “the angle of no return” because if this angle is reached
under generator power swings, the generator is most likely to lose step.

8.17.7.2 Detecting an out-of-step condition GUID-5BBAE253-3D01-4C97-A7CF-A12084FD1810 v4

An out-of-step condition is characterized by periodic changes of the rotor angle, that leads to
a wild flow of the synchronizing power; so there are also periodic changes of rotational speed,
currents and voltages. When displayed in the complex impedance plane, these changes are
characterized by a cyclic change in the complex load impedance Z(R, X) as measured at the
terminals of the generator, or at the location of the instrument transformers of a power line
connecting two power sub-systems. This was shown in Figure 226. When a synchronous
machine is out-of-step, pole-slips occur. To recognize a pole-slip, the complex impedance
Z(R,X) must traverse the lens from right to left in case of a generator and in the opposite
direction in case of a motor. Another requirement is that the travel across the lens takes no
less than a specific minimum traverse time, typically 40...60 milliseconds. The above timing is
used to discriminate a fault from an out-of-step condition. In Figure 226, some important
points on the trajectory of Z(R, X) are designated. Point 0: the pre-fault, normal load Z(R, X).
Point 1: impedance Z under a three-phase fault with low fault resistance: Z lies practically on,
or very near, the Z-line. Transition of the measured Z from point 0 to point 1 takes app. 20 ms,
due to Fourier filters. Point 2: Z immediately after the fault has been cleared. Transition of the
measured Z from point 1 to point 2 takes approximately 20 ms, due to Fourier filters. The
complex impedance then travels in the direction from the right to the left, and exits the lens on
the opposite side. When the complex impedance exits the lens on the side opposite to its
entrance, the 1st pole-slip has already occurred and more pole-slips can be expected if the
generator is not disconnected. Figure 226 shows two pole-slips. Figures like Figure 226 and
Figure 228 are always possible to draw by means of the analog output data from the pole-slip
function, and are of great help with eventual investigations of the performance of the out-of-
step function.

8.17.7.3 Maximum slip frequency GUID-1311529F-21F8-40A0-8D01-0296BD9B4F00 v5

A pole-slip may be detected if it has a slip frequency lower than a maximum value fsMax. The
specific value of fsMax depends on the setting (parameter) StartAngle (which determines the
width of the lens characteristic). A parameter in this calculation routine is the value of the
minimum traverse time, traverseTimeMin. The minimum traverse time is the minimum time
that the travel of the complex impedance Z(R, X) through the lens, from one side to the other,
must last in order to recognize that a pole-slip has occurred. The value of the internal constant
traverseTimeMin is a function of the set StartAngle.For values of StartAngle <= 110°,

412 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

traverseTimeMin = 50 ms. For values StartAngle > 110°, traverseTimeMin = 40 ms. The
expression which relates the maximum slip frequency fsMax and the traverseTimeMin is as
follows:

1000  StartAngle [°] 


fsMax [ Hz ] ≅ ⋅  1.000 - 
traverseTimeMin [ ms ]  180 [°] 
IECEQUATION2319 V1 EN-US (Equation 100)

The maximum slip frequency fsMax for traverseTimeMin = 50 ms is:

StartAngle = 90° → fsMax = 20 × 0.500 = 10.000 Hz


StartAngle = 100° → fsMax = 20 × 0.444 = 8.888 Hz
StartAngle = 110° → fsMax = 20 × 0.388 = 7.777 Hz (default 110°)

The maximum slip frequency fsMax for traverseTimeMin = 40 ms is:

StartAngle = 120° → fsMax = 25 × 0.333 = 8.333 Hz


StartAngle = 130° → fsMax = 25 × 0.277 = 6.944 Hz

The minimum value of fsMax is 6.994 Hz. When StartAngle = 110 degrees, fsMax = 7.777 Hz. This
implies, that the default StartAngle = 110 degrees covers 90% of cases as, the typical final slip
frequency is between 2 - 5Hz. In practice, however, before the slip frequency, for example 7.777
Hz, is reached, at least three pole-slips have occurred. In other words, if we consider a linear
increase of frequency from 50 Hz to 57.777 Hz, at least three pole-slips will occur (in fact:
(57.777 - 50) / 2 = 3.889). The exact instantaneous slip-frequency expressed in Hz
(corresponding to number of pole slips per second) is difficult to calculate. The easiest and
most exact method is to measure time between two successive pole slips. This means that,
the instantaneous slip-frequency is measured only after the second pole-slip, if the protected
machine is not already disconnected after the first pole-slip. The measured value of
slipsPerSecond (SLIPFREQ) is equal to the average slip-frequency of the machine between the
last two successive pole-slips.

8.17.7.4 Taking care of the circuit breaker GUID-35B49D7D-80AF-4DB0-A3C5-0CA0E54A9CA1 v4

Although out-of-step events are relatively rare, the out-of-step protection should take care of
the circuit breaker health. The electromechanical stress to which the breaker is exposed shall
be minimized. The maximum currents flowing under out-of-step conditions can be even
greater that those for a three-phase short circuit on generator terminals; see Figure 232. The
currents flowing are highest at rotor angle 180 degrees, and smallest at 0 degrees, where
relatively small currents flow. To open the circuit breaker at 180 degrees, when not only the
currents are highest, but the two internal (that is, induced) voltages at both ends are in
opposition, could be fatal for the circuit breaker. There are two methods available in order to
minimize the stress; the second method is more advanced than the first one.

The first method


The circuit breaker is only allowed to break the current when the rotor angle has become less
than the set value TripAngle, on its way to 0 electrical degrees. A recommended value for the
setting TripAngle is 90 degrees or less, for example 60 degrees. Figure 231 illustrates the case
with TripAngle = 90 degrees. The offset Mho circle represents loci of the complex impedance
Z(R, X) for which the rotor (power) angle is 90 degrees. If the circuit breaker must not open
before the rotor angle has reached 90 degrees on its way towards 0 degrees, then it is clear
that the circle delimits the R – X plane into a “no trip” and a “trip” region. For TripAngle = 90
degrees, the trip command will be issued at point 3 when the complex impedance Z(R, X) exits

Line distance protection REL670 413


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

the circle. By that time the relay logic had already ascertained the loss of step, and the general
decision to trip the generator has already been taken.

The second method


This method is more exact. If the break-time of the circuit breaker is known, (and specified as
the setting tBreaker) than it is possible to initiate a trip (break) command almost exactly
tBreaker milliseconds before the rotor (power) angle reaches 0 degrees, where the currents
are at their minimum possible values. The breaker contacts open at almost exactly 0 degrees,
as illustrated in Figure 232 for tBreaker = 0.060 s. The point in time when the breaker opening
process must be initiated is estimated by solving on-line the so called “synchronizer”
differential equation. Note that if tBreaker is left on the initial (default) value, which is zero (0),
then the alternative setting TripAngle decides when the trip command is given. If specified
tBreaker > 0, for example tBreaker = 0.040 second, then automatically, the TripAngle is ignored
and the second, more exact method applied.

X[Ohm]
0.6 trip RE - Receiving End (infinite bus)
region
loci of Z(R, X)
0.4 3
Imaginary part (X) of Z in Ohms →

no trip
region 1
here rotor here
0.2 2
angle rotor angle
is -90° no trip is +90°
rotor angle
region
= ±180°
0 no trip
relay
region R[Ohm]
inside ← Z - line connects
points SE & RE
-0.2 circle
← this circle
is loci of
outside the
the rotor
-0.4 circle is the trip
angle = 90°
region for
TripAngle <= 90° SE - Sending End (generator)

-0.6 -0.4 -0.2 0 0.2 0.4 0.6 0.8


Real part (R) of Z in Ohms →
IEC10000114-1-en.vsd
IEC10000114 V1 EN-US

Figure 231: The imaginary offset Mho circle represents loci of the impedance Z(R, X) for
which the rotor angle is 90 degrees

414 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

35
very high currents due

Current in kA, trip command to CB, rotor angle in rad →


pos. seq. current in kA
to out-of-step condition
30 trip command to CB
rotor angle in radian
← after 1st
fault cleared → pole slip
25
← 2nd

20 current increases under


fault conditions
current decreases
15
fault
occurs
10 ← min. current
trip command →
normal load current issued here
← → ← tBreaker = 60 ms
5

← rotor angle
0
angle towards 0°

-5
0 200 400 600 800 1000 1200
Time in milliseconds →
IEC10000115-1-en.vsd
IEC10000115 V1 EN-US

Figure 232: Trip initiation when the break-time of the circuit breaker is known

8.17.7.5 Design GUID-1615F014-3529-45D0-813B-153754DED1C7 v3

At every execution of the function the following is calculated: active power P, reactive power Q,
rotor angle ROTORANG, quantity UCOSPHI, the positive-sequence current CURRENT and voltage
VOLTAGE. All other quantities, that can as well be read as outputs, are only calculated if the Z(R,
X) enters the limit of reach zone, which is a circle in the complex (R – X) plane. When the
complex impedance Z(R, X) enters the limit-of-reach region, the algorithm:

• determines in which direction the impedance Z moves, that is, the direction the lens is
traversed
• measures the time taken to traverse the lens from one side to the other one

If the traverse time is more than the limit 40 or 50 ms, a pole-slip is declared. If the complex
impedance Z(R, X) exits the lens on the same side it entered, then it is a stable case and the
protected machine is still in synchronism. If a pole-slip has been detected, then it is
determined in which zone the centre of oscillation is located. If the number of actual pole-slips
exceeds the maximum number of allowed pole-slips in either of the zones, a trip command is
issued taking care of the circuit breaker safety.

Line distance protection REL670 415


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

R R
UPSRE Calculation of X X
UPSIM R and X parts
of the complex Z(R,X)
UPSMAG
positive-
IPSRE
sequence Z(R,X) NO
IPSIM
impedance within limit of Return
Z(R, X) reach?

YES UCOSPHI

Z(R,X) ROTORANG
within lens NO
Function alert
characteristic?
SLIPFREQ

YES GENMODE

Z(R,X) MOTMODE
LEFT Z(R,X) RIGHT NO
exited lens
entered lens
on the left- hand
from?
Motor losing Generator losing side?
step ? step ?
YES

Was
traverse time NO
more than
Calculation of 50 ms?
P
positive- sequence YES (pole- slip!)
active power P, Q TRIP
>= 1
reactive power Q, Number
ZONE 2 NO
rotor angle UCOSPHI
of pole- slips
ROTORANG exceeded in TRIPZ1
a zone? Open
and
ROTORANG circuit
UCOSPHI ZONE 1 TRIPZ2
breaker
safely

IEC10000116-3-en.vsd
IEC10000116 V3 EN-US

Figure 233: OOSPPAM Simplified function block

8.17.8 Technical data


SEMOD175136-2 v8

Table 230: OOSPPAM technical data


Function Range or value Accuracy
Impedance reach (0.00 - 1000.00)% of Zbase ±2.0% of Ur/(√3 ⋅ Ir)

Rotor start angle (90.0 - 130.0) degrees ±5.0 degrees


Rotor trip angle (15.0 - 90.0) degrees ±5.0 degrees
Zone 1 and Zone 2 trip (1 - 20) -
counters

8.18 Phase preference logic PPLPHIZ SEMOD151920-1 v2

8.18.1 Identification
SEMOD151937-2 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Phase preference logic PPLPHIZ - -

8.18.2 Functionality SEMOD151924-4 v5

The Phase preference logic function PPLPHIZ is intended to be used in isolated or high
impedance earthed networks where there is a requirement to operate on only one of the faulty

416 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

lines during a cross-country fault. It can be used without preference to restrain operation for
single earth faults with a delayed zero-sequence current release.

For cross-country faults, the logic selects either the leading or lagging phase-earth loop for
measurement. It initiates operation on the preferred fault based on the selected phase
preference. A number of different phase preference combinations are available for selection.

PPLPHIZ provides an additional phase selection criteria, namely under voltage criteria, suitable
for cross-country faults. In radial networks, where there is no fault current in the phase with
the external fault, current or impedance based phase selection methods become ineffective.
Hence, only voltage can be used for phase selection. The phase selection result will be the
same for all bays on a bus since the voltage is the same, which is an important condition for
operating with phase preference.

In meshed and stronger networks, it is difficult to find appropriate under-voltage or phase


selection settings. If PPLPHIZ is unable to detect both faulty phases, then it is not possible to
provide preference. The distance protection will still be released however, without preference.
The final result might be that both faulty feeders are operated. In other words, operation is
prioritized over strict adherence to preference.

8.18.3 Function block SEMOD172690-4 v4

PPLPHIZ
I3P* START
U3P* ZREL
BLOCK
RELL1N
RELL2N
RELL3N
STCND

IEC07000029-2-en.vsd
IEC07000029 V2 EN-US

Figure 234: PPLPHIZ function block

8.18.4 Signals SEMOD172700-1 v2

PID-6808-INPUTSIGNALS v2

Table 231: PPLPHIZ Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
RELL1N BOOLEAN 0 Release condition for the L1 to earth loop
RELL2N BOOLEAN 0 Release condition for the L2 to earth loop
RELL3N BOOLEAN 0 Release condition for the L3 to earth loop
STCND INTEGER 0 Integer coded external release signals

PID-6808-OUTPUTSIGNALS v2

Table 232: PPLPHIZ Output signals


Name Type Description
START BOOLEAN Indicates start for earth fault(s), regardless of direction
ZREL INTEGER Integer coded output release signal

Line distance protection REL670 417


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

8.18.5 Settings SEMOD172702-1 v2

PID-6808-SETTINGS v2

Table 233: PPLPHIZ Group settings (basic)


Name Values (Range) Unit Step Default Description
OperMode No Filter - - No Filter Operating mode (c=cyclic,a=acyclic)
NoPref
1231c
1321c
123a
132a
213a
231a
312a
321a
UPN< 0 - 100 %UB/sq 1 70 Operate value of phase undervoltage
3 in % of UBase/sqrt(3)
UPP< 0 - 100 %UB 1 50 Operate value of line to line
undervoltage (% of UBase)
3U0> 5 - 300 %UB/sq 1 20 Operate value of residual voltage in %
3 of UBase/sqrt(3)
IN> 10 - 200 %IB 1 20 Operate value of residual current (%
of IBase)
tUN 0.000 - 60.000 s 0.001 0.100 Pickup-delay for residual voltage
tOffUN 0.000 - 60.000 s 0.001 0.100 Dropoff-delay for residual voltage
tIN 0.000 - 60.000 s 0.001 0.150 Pickup-delay for residual current

Table 234: PPLPHIZ Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

8.18.6 Operation principle SEMOD151916-4 v8

PPLPHIZ is connected between the Distance protection zones ZMQPDIS and ZMQAPDIS and
Phase selection FDPSPDIS, see Figure 235. Depending on the setting, the original phase
selection will be supplemented with an additional voltage based phase selection inside
PPLPHIZ and then filtered through the phase preference logic in order to release only the
preferred phases of the distance zones.

418 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

ZMQAPDIS
FDPSPDIS
W2_CT_B_I3P I3P* TRIP
I3P* TRIP
W2_VT_B_U3P U3P* TRL1
U3P* START FALSE BLOCK TRL2
BLOCK STFWL1 PHS_L1 W2_FSD1-BLKZ VTSZ TRL3
DIRCND STFWL2 PHS_L2 FALSE BLKTR START
STFWL3 PHS_L3 STCND STL1
STFWPE
DIRCND STL2
STRVL1
STL3
STRVL2
STND
STRVL3
STRVPE
STNDL1 ZMQPDIS
STNDL2 I3P* TRIP
W2_CT_B_I3P
STNDL3 U3P* TRL1
W2_VT_B_U3P
STNDPE FALSE BLOCK TRL2
STFW1PH VTSZ TRL3
W2_FSD1-BLKZ
STFW2PH BLKTR START
FALSE
STFW3PH
STCND STL1
STPE DIRCND STL2
STPP STL3
STCNDZ STND
STCNDLE

PPLPHIZ
W2_CT_B_I3P I3P* START
W2_VT_B_U3P U3P* ZREL
FALSE BLOCK
FALSE RELL1N
FALSE RELL2N
FALSE RELL3N
STCND
IEC06000552-3-en.vsd
IEC06000552 V3 EN-US

Figure 235: Phase preference logic overview

PPLPHIZ can be divided into three main parts:

• Residual current criteria


• Phase selection
• Preference logic

8.18.6.1 Residual current criteria GUID-982F5BF4-CB45-4404-94F5-9A24B891056B v1

The fundamental start criterion for a cross-country fault is a continuous residual current (3I0)
above setting level IN>.

Transient residual currents associated with single phase fault inception are not allowed to
release the distance protection. This is taken care of by a time-on-delay tIN, which should be
set longer than the expected duration of the transient.

If a single phase fault remains for some time, it is possible to bypass the tIN time delay, since
the next fault event is expected to be a two-phase fault. The criterion for this bypass is that
the residual voltage is greater than setting level 3U0> for a time longer than setting tUN. The
time-off-delay tOffUN is used to make sure that the bypass is steady during the cross-country
fault.

The time delay for residual current start is also bypassed as soon as two low voltages are
detected during the cross-country fault (startUPP). See Figure 236.

Line distance protection REL670 419


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

startUPP

OR
tUN tOffUN
3U0 > 3U0> t t
(Non delayed IN start)
AND

tIN startIN
OR
3I0>IN> t

IEC16000018-1-en.vsdx
IEC16000018 V1 EN-US

Figure 236: Residual current criteria

8.18.6.2 Phase selection GUID-975FB3BE-A7FE-4CD8-8954-6542870DF482 v1

During a cross-country fault, the phase with an external fault typically does not carry any fault
current, which will make it difficult for a conventional phase selection function to detect the
fault. Therefore, PPLPHIZ function provides an additional phase selection based on voltage.

PPLPHIZ is designed to detect two-phase faults based on under-voltage in two phases or


between two phases.

ULx < UPN<


L1
L2 OR startU
AND
L3

3U0 > 3U0>

AND startUL1L2
OR

AND startUL2L3
OR
startUL1
OR
AND startUL3L1
ULxLy < UPP< OR
startUL2
L1L2 OR
L2L3
startUL3
L3L1 OR

IEC16000019-1-en.vsdx
IEC16000019 V1 EN-US

Figure 237: Phase selection


The voltage phase selection can be complemented with external phase selection through
inputs RELL1-3N.

Voltage phase selection is disabled in No Filter and NoPref operating modes.

420 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

startUL1
AND
startUL2
startUPP
AND OR
startUL3
AND
OperMode = No Filter
OR
AND
OperMode = NoPref

OR
RELL1N startL1
OR
OR
RELL2N startL2
OR
OR
RELL3N startL3
OR
OR
L1N
L2N
L3N
STCND Integer L1L2 zrelL1L2
to Bool
L2L3 zrelL2L3
L3L1 zrelL3L1

IEC16000105-1-en.vsdx
IEC16000105 V1 EN-US

Figure 238: Start

8.18.6.3 Preference logic GUID-A7FCCE03-C841-4BAD-98F8-EB9497D53687 v1

The different operating modes (selected with OperMode setting) determine how the internal
status is used to release the phases of the connected distance protection.

No Filter mode GUID-2D585104-E319-4B6D-82C7-3373CA7E87F7 v1


In No Filter mode, all phase starts of the phase selection will be passed through without any
preference or requirement on residual current or voltage.

No Filter mode is equivalent to connecting the phase selection directly to the distance
protection.

startL1 zrelL1

startL2 zrelL2

startL3 zrelL3

IEC16000106-1-en.vsdx
IEC16000106 V1 EN-US

Figure 239: No Filter mode

No Preference mode GUID-DA373F35-2082-4347-9A35-B34E23C03B01 v1


The ‘NoPref’ mode uses only the residual current criteria (startIN). There is no preference
provided in this mode. All three phase-to-earth loops of the distance protection may be
released when a residual current start has occurred.

Line distance protection REL670 421


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

startL1
zrelL1
AND
startL2
zrelL2
AND
startL3
zrelL3
AND

startIN

IEC16000107-1-en.vsdx
IEC16000107 V1 EN-US

Figure 240: No Preference mode

Preference modes GUID-BE61A451-E389-4136-8C0B-2C04888EEACE v1


In the preference modes (for example, ‘1231c’), the internal under-voltage phase selection
status is filtered with the selected preference scheme to achieve the desired phase preference.
Only the preferred phase-to-earth loop of the distance protection is released to operate. In
addition to the voltage phase selection, a residual current start is required.

A logic is also included to handle the special case where only one start (startL1-3) is present.

The internal under-voltage phase selection always issues a release in at least two phases, but
the inputs RELL1-3N can be activated with some time apart. If no measures are taken, the
phase activated first will pass through the preference scheme and release the distance
protection. Since it could a be non-preferred phase, a time delay of 40 ms is provided to
release if only one phase is detected, in order to wait for the second phase to be activated. If
no second phase is detected within 40 ms, the single phase is released without preference.

Additionaly, there are some cases where no release would be issued:

• All three phases are involved in the fault and a cyclic scheme is selected
• No faulty phase can be detected due to an insufficient voltage drop

In both cases, no release signals come from the phase preference scheme. For these cases, an
additional logic is provided that releases all phases if there is no output from the preference
scheme after 40 ms from the activation of the residual current start.

Hence, if there is a residual current start, it is guaranteed that the distance protection is
released in at least one phase. This is valid for all phase preference schemes.

Preference
OperMode Scheme
Sheme
startL1 prefL1
INL1 OUTL1
startL2 prefL2
INL2 OUTL2
startL3 INL3 OUTL3
prefL3

More
than
one stIN
AND
true
startIN
40 ms
stIN40ms
t

IEC16000023-1-en.vsdx
IEC16000023 V1 EN-US

Figure 241: Phase preference 1

422 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

prefL1
OR zrelL1
AND
prefL2
OR zrelL2
AND
prefL3
OR zrelL3
AND
OR

AND
stIN40ms
stIN OR

IEC16000024-1-en.vsdx
IEC16000024 V1 EN-US

Figure 242: Phase preference 2


Table 235 shows the preferred phase for each detected cross-country fault type and operating
mode (OperMode).

Table 235: Preferred phase for each cross-country fault type and operating mode
Operating mode start in L1 & L2 start in L2 & L3 start in L3 & L1
1231c L1 L2 L3
1321c L2 L3 L1
123a L1 L2 L1
132a L1 L3 L1
213a L2 L2 L1
231a L2 L2 L3
312a L1 L3 L3
321a L2 L3 L3

8.18.6.4 Output GUID-3D64237F-8D45-4CAE-8F2E-31F6741842C2 v1

All loop releasing signals are gathered in the binary coded integer output ZREL. The value of
ZREL can be calculated according to Equation 101.

ZREL L1N *1 L2N *2  L3N *4  L1L2*8  L2L3*16  L3L1*32


IECEQUATION16018 V1 EN-US (Equation 101)
For example, if only L1N is active, then the value is 1. If both start L1N and L3N are active, then
the value is 1+4=5.

The BLOCK input will only block the enabling signals for phase-to-earth loops,
phase-to-phase loops are still released. The PPLPHIZ is designed not to have
any influence on the phase-to-phase loops of the distance protection.

Line distance protection REL670 423


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

startU
AND

zrelL1
AND
zrelL2
AND L1N
zrelL3 L2N
AND L3N
Bool to ZREL
zrelL1L2 L1L2 Integer
zrelL2L3 L2L3
BLOCK zrelL3L1 L3L1

IEC16000108-1-en.vsdx
IEC16000108 V1 EN-US

Figure 243: Output


GUID-BACA37F7-E945-40BC-BF9D-A65BFC96CA91 v8

Table 236: PPLPHIZ technical data


Function Range or value Accuracy
Operate value, phase-to-phase (1 - 100)% of UBase ±0.5% of Ur
and phase-to-neutral
undervoltage
Reset ratio, undervoltage < 105% -
Operate value, residual (5 - 300)% of UBase ±0.5% of Ur at U ≤ Ur
voltage ±0.5% of U at U > Ur

Reset ratio, residual voltage > 95% -


Operate value, residual current (10 - 200)% of IBase ±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir

Reset ratio, residual current > 95% -


Independent time delay for (0.000 - 60.000) s ±0.2% or ±25 ms whichever is
residual current at 0 to 2 x Iset greater

Independent time delay for (0.000 - 60.000) s ±0.2% or ±25 ms whichever is


residual voltage at 0.8 x Uset to greater
1.2 x Uset

Independent dropoff-delay for (0.000 - 60.000) s ±0.2% or ±25 ms whichever is


residual voltage at 1.2 x Uset to greater
0.8 x Uset

Operating mode No Filter, NoPref


Cyclic: 1231c, 1321c
Acyclic: 123a, 132a, 213a, 231a, 312a, 321a

8.19 Phase preference logic PPL2PHIZ GUID-80133640-FB3E-400C-B7FF-C2BB0AD1A045 v1

8.19.1 Identification
GUID-850E4134-E912-45EC-981E-E1A2C12A91A8 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Phase preference logic PPL2PHIZ - -

424 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

8.19.2 Functionality GUID-39785DEB-E5D7-447C-977B-9E940CA8E774 v1

The Phase preference logic function (PPL2PHIZ) is used with the high speed distance
protection, quad and mho characteristic (ZMFPDIS). It is intended to be used in isolated or
high impedance earthed networks where there is a requirement to operate on only one of the
faulty lines during a cross-country fault. It can be used without preference to restrain
operation for single earth faults with a delayed zero-sequence current release.

For cross-country faults, the logic selects either the leading or lagging phase-earth loop for
measurement. It initiates operation on the preferred fault based on the selected phase
preference. A number of different phase preference combinations are available for selection.

PPL2PHIZ provides an additional phase selection criteria, namely under voltage criteria,
suitable for cross-country faults. In radial networks, where there is no fault current in the
phase with the external fault, current or impedance based phase selection methods become
ineffective. Hence, only voltage can be used for phase selection. The phase selection result will
be the same for all bays on a bus since the voltage is the same, which is an important
condition for operating with phase preference.

In meshed and stronger networks, it is difficult to find appropriate under-voltage or phase


selection settings. If PPL2PHIZ is unable to detect both faulty phases, then it is not possible to
provide preference. The distance protection will still be released however, without preference.
The final result might be that both faulty feeders are operated. In other words, operation is
prioritized over strict adherence to preference.

8.19.3 Function block GUID-8C40D1F5-FE37-422D-B9E6-BE14E6A8FED8 v1

PPL2PHIZ
I3P* START
U3P* ZREL
BLOCK
RELL1N
RELL2N
RELL3N
IEC16000016-1-en.vsdx
IEC16000016 V1 EN-US

Figure 244: PPL2PHIZ function block

8.19.4 Signals
PID-6809-INPUTSIGNALS v2

Table 237: PPL2PHIZ Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
RELL1N BOOLEAN 0 Release condition for the L1 to earth loop
RELL2N BOOLEAN 0 Release condition for the L2 to earth loop
RELL3N BOOLEAN 0 Release condition for the L3 to earth loop

Line distance protection REL670 425


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

PID-6809-OUTPUTSIGNALS v2

Table 238: PPL2PHIZ Output signals


Name Type Description
START BOOLEAN Indicates start for earth fault(s), regardless of direction
ZREL INTEGER Integer coded output release signal

8.19.5 Settings
PID-6809-SETTINGS v2

Table 239: PPL2PHIZ Group settings (basic)


Name Values (Range) Unit Step Default Description
OperMode No Filter - - No Filter Operating mode (c=cyclic,a=acyclic)
NoPref
1231c
1321c
123a
132a
213a
231a
312a
321a
UPN< 0 - 100 %UB/sq 1 70 Operate value of phase undervoltage
3 in % of UBase/sqrt(3)
UPP< 0 - 100 %UB 1 50 Operate value of line to line
undervoltage (% of UBase)
3U0> 5 - 300 %UB/sq 1 20 Operate value of residual voltage in %
3 of UBase/sqrt(3)
IN> 10 - 200 %IB 1 20 Operate value of residual current (%
of IBase)
tUN 0.000 - 60.000 s 0.001 0.100 Pickup-delay for residual voltage
tOffUN 0.000 - 60.000 s 0.001 0.100 Dropoff-delay for residual voltage
tIN 0.000 - 60.000 s 0.001 0.150 Pickup-delay for residual current

Table 240: PPL2PHIZ Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

8.19.6 Operation principle GUID-B304D0D3-1E4E-482D-975F-229467905608 v1

The PPL2PHIZ function releases the phase selection inside the distance protection, see Figure
245.

The phase selection inside the distance protection has to detect the fault
before an operation from the distance zones can be achieved, even when the
distance protection is released by PPL2PHIZ.

426 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

PPL2PHIZ ZMFPDIS
Phase
Phase selection
preference
Zone1
L1N relcndphs TRZ1
L1N bitwise enable
L2N AND
L2N
L3N Zone2
L3N Bool to ZREL bitwise
TRUE L1L2 Integer AND
enable
RELCNDZ1
TRUE L2L3
Zone3
TRUE L3L1 RELCNDZ2 bitwise
enable
AND
RELCNDZ3
Zone4
RELCNDZ4 bitwise
enable
TRZ4
AND
RELCNDZ5 Zone5
bitwise
enable
TRZ5
RELCNDZRV AND
ZoneRV
bitwise
enable
TRZRV
AND

IEC16000017-1-en.vsdx
IEC16000017 V1 EN-US

Figure 245: Phase preference logic overview


PPL2PHIZ can be divided into three main parts:

• Residual current criteria


• Phase selection
• Preference logic

8.19.6.1 Residual current criteria GUID-982F5BF4-CB45-4404-94F5-9A24B891056B v1

The fundamental start criterion for a cross-country fault is a continuous residual current (3I0)
above setting level IN>.

Transient residual currents associated with single phase fault inception are not allowed to
release the distance protection. This is taken care of by a time-on-delay tIN, which should be
set longer than the expected duration of the transient.

If a single phase fault remains for some time, it is possible to bypass the tIN time delay, since
the next fault event is expected to be a two-phase fault. The criterion for this bypass is that
the residual voltage is greater than setting level 3U0> for a time longer than setting tUN. The
time-off-delay tOffUN is used to make sure that the bypass is steady during the cross-country
fault.

The time delay for residual current start is also bypassed as soon as two low voltages are
detected during the cross-country fault (startUPP). See Figure 246.

startUPP

OR
tUN tOffUN
3U0 > 3U0> t t
(Non delayed IN start)
AND

tIN startIN
OR
3I0>IN> t

IEC16000018-1-en.vsdx
IEC16000018 V1 EN-US

Figure 246: Residual current criteria

Line distance protection REL670 427


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

8.19.6.2 Phase selection GUID-A3B9F4A9-30D1-40E5-B0A8-6BB66093C27A v1

During a cross-country fault, the phase with an external fault typically does not carry any fault
current, which will make it difficult for a conventional phase selection function to detect the
fault. Therefore, PPL2PHIZ function provides an additional phase selection based on voltage.

PPL2PHIZ is designed to detect two-phase faults based on under-voltage in two phases or


between two phases.

ULx < UPN<


L1
L2 OR startU
AND
L3

3U0 > 3U0>

AND startUL1L2
OR

AND startUL2L3
OR
startUL1
OR
AND startUL3L1
ULxLy < UPP< OR
startUL2
L1L2 OR
L2L3
startUL3
L3L1 OR

IEC16000019-1-en.vsdx
IEC16000019 V1 EN-US

Figure 247: Phase selection


The voltage phase selection can be complemented with external phase selection through
inputs RELL1-3N.

Voltage phase selection is disabled in No Filter and NoPref operating modes.

startUL1
AND
startUL2
startUPP
AND OR
startUL3
AND
OperMode = No Filter
OR
OperMode = NoPref

startL1
RELL1N OR

startL2
RELL2N OR

startL3
RELL3N OR

IEC16000020-1-en.vsdx
IEC16000020 V1 EN-US

Figure 248: Start

428 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

8.19.6.3 Preference logic GUID-A7FCCE03-C841-4BAD-98F8-EB9497D53687 v1

The different operating modes (selected with OperMode setting) determine how the internal
status is used to release the phases of the connected distance protection.

No Filter mode GUID-BB45C4A8-890F-4716-940C-53BBB47710F3 v1


In No Filter mode, all distance protection phases are released constantly, leaving it to the
phase selection inside the distance protection to decide which distance zone loops should be
allowed to operate.

TRUE zrelL1

TRUE zrelL2

TRUE zrelL3

IEC16000021-1-en.vsdx
IEC16000021 V1 EN-US

Figure 249: No Filter mode


No Filter mode is equivalent to disconnecting the PPL2PHIZ from the distance protection.

No Preference mode GUID-3D947DCA-7938-4C44-8BA6-4DA2789EDC98 v1


The ‘NoPref’ mode uses only the residual current criteria (startIN). There is no preference
provided in this mode. All three phase-to-earth loops of the distance protection releases when
a residual current start has occurred.

TRUE
zrelL1
AND
TRUE
zrelL2
AND
TRUE
zrelL3
AND

startIN

IEC16000022-1-en.vsdx
IEC16000022 V1 EN-US

Figure 250: No Preference mode

Preference modes GUID-BE61A451-E389-4136-8C0B-2C04888EEACE v1


In the preference modes (for example, ‘1231c’), the internal under-voltage phase selection
status is filtered with the selected preference scheme to achieve the desired phase preference.
Only the preferred phase-to-earth loop of the distance protection is released to operate. In
addition to the voltage phase selection, a residual current start is required.

A logic is also included to handle the special case where only one start (startL1-3) is present.

The internal under-voltage phase selection always issues a release in at least two phases, but
the inputs RELL1-3N can be activated with some time apart. If no measures are taken, the
phase activated first will pass through the preference scheme and release the distance
protection. Since it could a be non-preferred phase, a time delay of 40 ms is provided to
release if only one phase is detected, in order to wait for the second phase to be activated. If
no second phase is detected within 40 ms, the single phase is released without preference.

Additionaly, there are some cases where no release would be issued:

Line distance protection REL670 429


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

• All three phases are involved in the fault and a cyclic scheme is selected
• No faulty phase can be detected due to an insufficient voltage drop

In both cases, no release signals come from the phase preference scheme. For these cases, an
additional logic is provided that releases all phases if there is no output from the preference
scheme after 40 ms from the activation of the residual current start.

Hence, if there is a residual current start, it is guaranteed that the distance protection is
released in at least one phase. This is valid for all phase preference schemes.

Preference
OperMode Scheme
Sheme
startL1 prefL1
INL1 OUTL1
startL2 prefL2
INL2 OUTL2
startL3 INL3 OUTL3
prefL3

More
than
one stIN
AND
true
startIN
40 ms
stIN40ms
t

IEC16000023-1-en.vsdx
IEC16000023 V1 EN-US

Figure 251: Phase preference 1

prefL1
OR zrelL1
AND
prefL2
OR zrelL2
AND
prefL3
OR zrelL3
AND
OR

AND
stIN40ms
stIN OR

IEC16000024-1-en.vsdx
IEC16000024 V1 EN-US

Figure 252: Phase preference 2


Table 241 shows the preferred phase for each detected cross-country fault type and operating
mode (OperMode).

Table 241: Preferred phase for each cross-country fault type and operating mode
Operating mode start in L1 & L2 start in L2 & L3 start in L3 & L1
1231c L1 L2 L3
1321c L2 L3 L1
123a L1 L2 L1
132a L1 L3 L1
213a L2 L2 L1
Table continues on next page

430 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 8
Impedance protection

Operating mode start in L1 & L2 start in L2 & L3 start in L3 & L1


231a L2 L2 L3
312a L1 L3 L3
321a L2 L3 L3

8.19.6.4 Output GUID-FCDCF1A9-A34D-4FD7-B488-3F31A93BE231 v1

All loop releasing signals are gathered in the binary coded integer output ZREL. The value of
ZREL can be calculated according to Equation 102.

ZREL L1N *1 L2N *2  L3N *4  L1L2*8  L2L3*16  L3L1*32


IECEQUATION16018 V1 EN-US (Equation 102)
For example, if only L1N is active, then the value is 1. If both start L1N and L3N are active, then
the value is 1+4=5.

The phase-to-phase loops are always released, that is, the value of ZREL will
always be at least 8+16+32=56. For example:
If only L1N is active, then the value is 1+56=57
If start L1N and L3N are active, then the value is 1+4+56=61

The BLOCK input will only block the enabling signals for phase-to-earth loops,
phase-to-phase loops are still released. The PPL2PHIZ is designed not to have
any influence on the phase-to-phase loops of the distance protection.

startU
AND

zrelL1
AND
zrelL2
AND L1N
zrelL3 L2N
AND L3N
Bool to ZREL
TRUE L1L2 Integer
TRUE L2L3
BLOCK TRUE L3L1

IEC16000025-1-en.vsdx
IEC16000025 V1 EN-US

Figure 253: Output

Line distance protection REL670 431


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 506 370-UEN J
Impedance protection

8.19.7 Technical data


GUID-42119BFF-1756-431C-A5A1-0AB637213E96 v1

Table 242: PPL2PHIZ technical data


Function Range or value Accuracy
Operate value, phase-to-phase (1 - 100)% of UBase ±0.5% of Ur
and phase-to-neutral
undervoltage
Reset ratio, undervoltage < 105% -
Operate value, residual (5 - 300)% of UBase ±0.5% of Ur at U ≤ Ur
voltage ±0.5% of U at U > Ur

Reset ratio, residual voltage > 95% -


Operate value, residual current (10 - 200)% of IBase ±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir

Reset ratio, residual current > 95% -


Independent time delay for (0.000 - 60.000) s ±0.2% or ±25 ms whichever is
residual current at 0 to 2 x Iset greater

Independent time delay for (0.000 - 60.000) s ±0.2% or ±25 ms whichever is


residual voltage at 0.8 to 1.2 x greater
Uset

Independent dropoff-delay for (0.000 - 60.000) s ±0.2% or ±25 ms whichever is


residual voltage at 1.2 to 0.8 x greater
Uset

Operating mode No Filter, NoPref


Cyclic: 1231c, 1321c
Acyclic: 123a, 132a, 213a, 231a, 312a, 321a

432 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

Section 9 Current protection


9.1 Instantaneous phase overcurrent protection PHPIOC IP14506-1 v6

9.1.1 Identification
M14880-1 v5

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Instantaneous phase overcurrent PHPIOC 50
protection
3I>>

SYMBOL-Z V1 EN-US

9.1.2 Functionality M12910-3 v14

The instantaneous three phase overcurrent (PHPIOC) function has a low transient overreach
and short tripping time to allow use as a high set short-circuit protection function.

9.1.3 Function block M12602-3 v6

PHPIOC
I3P* TRIP
BLOCK TRL1
ENMULT TRL2
TRL3

IEC04000391-2-en.vsd
IEC04000391 V2 EN-US

Figure 254: PHPIOC function block

9.1.4 Signals IP11433-1 v2

PID-6914-INPUTSIGNALS v3

Table 243: PHPIOC Input signals


Name Type Default Description
I3P GROUP - Three phase current
SIGNAL
BLOCK BOOLEAN 0 Block of function
ENMULT BOOLEAN 0 Enable current start value multiplier

Line distance protection REL670 433


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

PID-6914-OUTPUTSIGNALS v3

Table 244: PHPIOC Output signals


Name Type Description
TRIP BOOLEAN Trip signal from any phase
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3

9.1.5 Settings IP11434-1 v2

PID-6914-SETTINGS v3

Table 245: PHPIOC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
OpMode 2 out of 3 - - 1 out of 3 Select operation mode 2-out of 3 / 1-
1 out of 3 out of 3
IP>> 5 - 2500 %IB 1 200 Operate phase current level in % of
IBase

Table 246: PHPIOC Group settings (advanced)


Name Values (Range) Unit Step Default Description
IP>>Min 5 - 2500 %IB 1 5 Minimum used operate phase current
level in % of IBase, if IP>> is less than
IP>>Min then IP>> is set to IP>>Min
IP>>Max 5 - 2500 %IB 1 2500 Maximum used operate phase current
level in % of IBase, if IP>> is greater
than IP>>Max then IP>> is set to
IP>>Max
StValMult 0.5 - 5.0 - 0.1 1.0 Multiplier for operate current level

Table 247: PHPIOC Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

9.1.6 Monitored data


PID-6914-MONITOREDDATA v3

Table 248: PHPIOC Monitored data


Name Type Values (Range) Unit Description
IL1 REAL - A Current in phase L1
IL2 REAL - A Current in phase L2
IL3 REAL - A Current in phase L3

434 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

9.1.7 Operation principle M12913-3 v8

The sampled analogue phase currents are pre-processed in a discrete Fourier filter (DFT)
block. The RMS value of each phase current is derived from the fundamental frequency
components, as well as sampled values of each phase current. These phase current values are
fed to the instantaneous phase overcurrent protection 3-phase output function PHPIOC. In a
comparator the RMS values are compared to the set operation current value of the function
(IP>>).

If a phase current is larger than the set operation current a signal from the comparator for this
phase is set to true. This signal will, without delay, activate the output signal TRLn (n=1,2,3) for
this phase and the TRIP signal that is common for all three phases.

There is an operation mode (OpMode) setting: 1 out of 3 or 2 out of 3. If the parameter is set to
1 out of 3, any phase trip signal will be activated. If the parameter is set to 2 out of 3, at least
two phase signals must be activated for trip.

There is also a possibility to activate a preset change of the set operation current (StValMult)
via a binary input (ENMULT). In some applications the operation value needs to be changed,
for example, due to transformer inrush currents.

The operation current value IP>>, is limited to be between IP>>Max and IP>>Min. The default
values of the limits are the same as the setting limits for IP>>, and the limits can only be used
for reducing the allowed range of IP>>. This feature is used when remote setting of the
operation current value is allowed, making it possible to ensure that the operation value used
is reasonable. If IP>> is set outside IP>>Max and IP>>Min, the closest of the limits to IP>> is
used by the function. If IP>>Max is smaller then IP>>Min, the limits are swapped. The principle
of the limitation is shown in Figure 255.

IP>>Max
MAX hi

u y
IP>>_used
IP>>

MIN lo
IP>>Min
IEC17000016-1-en.vsdx
IEC17000016 V1 EN-US

Figure 255: Logic for limitation of used operation current value

PHPIOC can be blocked using the binary input BLOCK.

9.1.8 Technical data IP11435-1 v1

M12336-1 v13

Table 249: PHPIOC technical data


Function Range or value Accuracy
Operate current (5-2500)% of lBase ±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir

Reset ratio > 95% at (50–2500)% of IBase -


Operate time at 0 to 2 x Iset Min. = 15 ms -
Max. = 25 ms
Reset time at 2 x Iset to 0 Min. = 15 ms -
Max. = 25 ms
Critical impulse time 10 ms typically at 0 to 2 x Iset -

Table continues on next page

Line distance protection REL670 435


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

Function Range or value Accuracy


Operate time at 0 to 10 x Iset Min. = 5 ms -
Max. = 15 ms
Reset time at 10 x Iset to 0 Min. = 25 ms -
Max. = 40 ms
Critical impulse time 2 ms typically at 0 to 10 x Iset -

Dynamic overreach < 5% at t = 100 ms -

9.2 Directional phase overcurrent protection, four steps


OC4PTOC SEMOD129998-1 v8

9.2.1 Identification
M14885-1 v6

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Directional phase overcurrent OC4PTOC 51_67
protection, four steps

TOC-REVA V2 EN-US

9.2.2 Functionality M12846-3 v17

Directional phase overcurrent protection, four steps (OC4PTOC) has an inverse or definite
time delay for each step.

All IEC and ANSI inverse time characteristics are available together with an optional user
defined time characteristic.

The directional function needs voltage as it is voltage polarized with memory. The function can
be set to be directional or non-directional independently for each of the steps.

A second harmonic blocking level can be set for the function and can be used to block each
step individually.

436 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

9.2.3 Function block M12609-3 v8

OC4PTOC
I3P* TRIP
U3P* TR1
BLOCK TR2
BLKTR TR3
BLKST1 TR4
BLKST2 TRL1
BLKST3 TRL2
BLKST4 TRL3
ENMULT1 TR1L1
ENMULT2 TR1L2
ENMULT3 TR1L3
ENMULT4 TR2L1
TR2L2
TR2L3
TR3L1
TR3L2
TR3L3
TR4L1
TR4L2
TR4L3
START
ST1
ST2
ST3
ST4
STL1
STL2
STL3
ST1L1
ST1L2
ST1L3
ST2L1
ST2L2
ST2L3
ST3L1
ST3L2
ST3L3
ST4L1
ST4L2
ST4L3
ST2NDHRM
DIRL1
DIRL2
DIRL3
STDI RCND
IEC06000187-4-en.vsdx
IEC06000187 V4 EN-US

Figure 256: OC4PTOC function block

9.2.4 Signals
PID-6973-INPUTSIGNALS v3

Table 250: OC4PTOC Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Block of trip
BLKST1 BOOLEAN 0 Block of Step1
BLKST2 BOOLEAN 0 Block of Step2
BLKST3 BOOLEAN 0 Block of Step3
BLKST4 BOOLEAN 0 Block of Step4
Table continues on next page

Line distance protection REL670 437


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

Name Type Default Description


ENMULT1 BOOLEAN 0 When activated, the current multiplier is in use for step1
ENMULT2 BOOLEAN 0 When activated, the current multiplier is in use for step2
ENMULT3 BOOLEAN 0 When activated, the current multiplier is in use for step3
ENMULT4 BOOLEAN 0 When activated, the current multiplier is in use for step4

PID-6973-OUTPUTSIGNALS v3

Table 251: OC4PTOC Output signals


Name Type Description
TRIP BOOLEAN Trip
TR1 BOOLEAN Common trip signal from step1
TR2 BOOLEAN Common trip signal from step2
TR3 BOOLEAN Common trip signal from step3
TR4 BOOLEAN Common trip signal from step4
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
TR1L1 BOOLEAN Trip signal from step1 phase L1
TR1L2 BOOLEAN Trip signal from step1 phase L2
TR1L3 BOOLEAN Trip signal from step1 phase L3
TR2L1 BOOLEAN Trip signal from step2 phase L1
TR2L2 BOOLEAN Trip signal from step2 phase L2
TR2L3 BOOLEAN Trip signal from step2 phase L3
TR3L1 BOOLEAN Trip signal from step3 phase L1
TR3L2 BOOLEAN Trip signal from step3 phase L2
TR3L3 BOOLEAN Trip signal from step3 phase L3
TR4L1 BOOLEAN Trip signal from step4 phase L1
TR4L2 BOOLEAN Trip signal from step4 phase L2
TR4L3 BOOLEAN Trip signal from step4 phase L3
START BOOLEAN General start signal
ST1 BOOLEAN Common start signal from step1
ST2 BOOLEAN Common start signal from step2
ST3 BOOLEAN Common start signal from step3
ST4 BOOLEAN Common start signal from step4
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3
ST1L1 BOOLEAN Start signal from step1 phase L1
ST1L2 BOOLEAN Start signal from step1 phase L2
ST1L3 BOOLEAN Start signal from step1 phase L3
ST2L1 BOOLEAN Start signal from step2 phase L1
ST2L2 BOOLEAN Start signal from step2 phase L2
ST2L3 BOOLEAN Start signal from step2 phase L3
Table continues on next page

438 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

Name Type Description


ST3L1 BOOLEAN Start signal from step3 phase L1
ST3L2 BOOLEAN Start signal from step3 phase L2
ST3L3 BOOLEAN Start signal from step3 phase L3
ST4L1 BOOLEAN Start signal from step4 phase L1
ST4L2 BOOLEAN Start signal from step4 phase L2
ST4L3 BOOLEAN Start signal from step4 phase L3
ST2NDHRM BOOLEAN Second harmonic detected
DIRL1 INTEGER Direction for phase1
DIRL2 INTEGER Direction for phase2
DIRL3 INTEGER Direction for phase3
STDIRCND INTEGER Binary coded start and directional information

9.2.5 Settings
PID-6973-SETTINGS v3

Table 252: OC4PTOC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
AngleRCA 40 - 65 Deg 1 55 Relay characteristic angle (RCA)
AngleROA 40 - 89 Deg 1 80 Relay operation angle (ROA)
StartPhSel 1 out of 3 - - 1 out of 3 Number of phases required for op (1
2 out of 3 of 3, 2 of 3, 3 of 3)
3 out of 3
DirMode1 Off - - Non-directional Directional mode of step 1 (off, nodir,
Non-directional forward, reverse)
Forward
Reverse
Characterist1 ANSI Ext. inv. - - ANSI Def. Time Selection of time delay curve type for
ANSI Very inv. step 1
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
I1> 5 - 2500 %IB 1 1000 Operating phase current level for step
1 in % of IBase
t1 0.000 - 60.000 s 0.001 0.000 Def time delay or add time delay for
inverse char of step 1
k1 0.05 - 999.00 - 0.01 0.05 Time multiplier for the inverse time
delay for step 1
Table continues on next page

Line distance protection REL670 439


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

Name Values (Range) Unit Step Default Description


IMin1 1 - 10000 %IB 1 100 Minimum operate current for step1 in
% of IBase
t1Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse
curves for step 1
I1Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for current operate level for
step 1
DirMode2 Off - - Non-directional Directional mode of step 2 (off, nodir,
Non-directional forward, reverse)
Forward
Reverse
Characterist2 ANSI Ext. inv. - - ANSI Def. Time Selection of time delay curve type for
ANSI Very inv. step 2
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
I2> 5 - 2500 %IB 1 500 Operating phase current level for step
2 in % of IBase
t2 0.000 - 60.000 s 0.001 0.400 Def time delay or add time delay for
inverse char of step 2
k2 0.05 - 999.00 - 0.01 0.05 Time multiplier for the inverse time
delay for step 2
IMin2 1 - 10000 %IB 1 50 Minimum operate current for step2 in
% of IBase
t2Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse
curves for step 2
I2Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for current operate level for
step 2
DirMode3 Off - - Non-directional Directional mode of step 3 (off, nodir,
Non-directional forward, reverse)
Forward
Reverse
Table continues on next page

440 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

Name Values (Range) Unit Step Default Description


Characterist3 ANSI Ext. inv. - - ANSI Def. Time Selection of time delay curve type for
ANSI Very inv. step 3
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
I3> 5 - 2500 %IB 1 250 Operating phase current level for step
3 in % of IBase
t3 0.000 - 60.000 s 0.001 0.800 Def time delay or add time delay for
inverse char of step 3
k3 0.05 - 999.00 - 0.01 0.05 Time multiplier for the inverse time
delay for step 3
IMin3 1 - 10000 %IB 1 33 Minimum operate current for step3 in
% of IBase
t3Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse
curves for step 3
I3Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for current operate level for
step 3
DirMode4 Off - - Non-directional Directional mode of step 4 (off, nodir,
Non-directional forward, reverse)
Forward
Reverse
Characterist4 ANSI Ext. inv. - - ANSI Def. Time Selection of time delay curve type for
ANSI Very inv. step 4
ANSI Norm. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
I4> 5 - 2500 %IB 1 175 Operating phase current level for step
4 in % of IBase
t4 0.000 - 60.000 s 0.001 2.000 Def time delay or add time delay for
inverse char of step 4
k4 0.05 - 999.00 - 0.01 0.05 Time multiplier for the inverse time
delay for step 4
Table continues on next page

Line distance protection REL670 441


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

Name Values (Range) Unit Step Default Description


IMin4 1 - 10000 %IB 1 17 Minimum operate current for step4 in
% of IBase
t4Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse
curves for step 4
I4Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for current operate level for
step 4

Table 253: OC4PTOC Group settings (advanced)


Name Values (Range) Unit Step Default Description
IMinOpPhSel 1 - 100 %IB 1 7 Minimum current for phase selection
in % of IBase
2ndHarmStab 5 - 100 % 1 20 Operate level of 2nd harmonic curr in
% of fundamental curr
I1>Min 5 - 2500 %IB 1 5 Minimum used operating phase
current level for step 1 in % of IBase, if
I1> is less than I1>Min then I1> is set to
I1>Min
I1>Max 5 - 2500 %IB 1 2500 Maximum used operating phase
current level for step 1 in % of IBase, if
I1> is greater than I1>Max then I1> is
set to I1>Max
ResetTypeCrv1 Instantaneous - - Instantaneous Selection of reset curve type for step 1
IEC Reset
ANSI reset
tReset1 0.000 - 60.000 s 0.001 0.020 Constant reset time for step 1
tPCrv1 0.005 - 3.000 - 0.001 1.000 Parameter P for customer
programmable curve for step 1
tACrv1 0.005 - 200.000 - 0.001 13.500 Parameter A for customer
programmable curve for step 1
tBCrv1 0.00 - 20.00 - 0.01 0.00 Parameter B for customer
programmable curve for step 1
tCCrv1 0.1 - 10.0 - 0.1 1.0 Parameter C for customer
programmable curve for step 1
tPRCrv1 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer
programmable curve for step 1
tTRCrv1 0.005 - 100.000 - 0.001 13.500 Parameter TR for customer
programmable curve for step 1
tCRCrv1 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer
programmable curve for step 1
HarmBlock1 Off - - Off Enable block of step 1 from harmonic
On restrain
I2>Min 5 - 2500 %IB 1 5 Minimum used operating phase
current level for step 2 in % of IBase, if
I2> is less than I2>Min then I2> is set
to I2>Min
I2>Max 5 - 2500 %IB 1 2500 Maximum used operating phase
current level for step 2 in % of IBase, if
I2> is greater than I2>Max then I2> is
set to I2>Max
ResetTypeCrv2 Instantaneous - - Instantaneous Selection of reset curve type for step 2
IEC Reset
ANSI reset
tReset2 0.000 - 60.000 s 0.001 0.020 Constant reset time for step 2
Table continues on next page

442 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

Name Values (Range) Unit Step Default Description


tPCrv2 0.005 - 3.000 - 0.001 1.000 Parameter P for customer
programmable curve for step 2
tACrv2 0.005 - 200.000 - 0.001 13.500 Parameter A for customer
programmable curve for step 2
tBCrv2 0.00 - 20.00 - 0.01 0.00 Parameter B for customer
programmable curve for step 2
tCCrv2 0.1 - 10.0 - 0.1 1.0 Parameter C for customer
programmable curve for step 2
tPRCrv2 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer
programmable curve for step 2
tTRCrv2 0.005 - 100.000 - 0.001 13.500 Parameter TR for customer
programmable curve for step 2
tCRCrv2 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer
programmable curve for step 2
HarmBlock2 Off - - Off Enable block of step 2 from harmonic
On restrain
I3>Min 5 - 2500 %IB 1 5 Minimum used operating phase
current level for step 3 in % of IBase, if
I3> is less than I3>Min then I3> is set
to I3>Min
I3>Max 5 - 2500 %IB 1 2500 Maximum used operating phase
current level for step 3 in % of IBase, if
I3> is greater than I3>Max then I3> is
set to I3>Max
ResetTypeCrv3 Instantaneous - - Instantaneous Selection of reset curve type for step 3
IEC Reset
ANSI reset
tReset3 0.000 - 60.000 s 0.001 0.020 Constant reset time for step 3
tPCrv3 0.005 - 3.000 - 0.001 1.000 Parameter P for customer
programmable curve for step 3
tACrv3 0.005 - 200.000 - 0.001 13.500 Parameter A for customer
programmable curve for step 3
tBCrv3 0.00 - 20.00 - 0.01 0.00 Parameter B for customer
programmable curve for step 3
tCCrv3 0.1 - 10.0 - 0.1 1.0 Parameter C for customer
programmable curve for step 3
tPRCrv3 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer
programmable curve for step 3
tTRCrv3 0.005 - 100.000 - 0.001 13.500 Parameter TR for customer
programmable curve for step 3
tCRCrv3 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer
programmable curve for step 3
HarmBlock3 Off - - Off Enable block of step 3 from harmonic
On restrain
I4>Min 5 - 2500 %IB 1 5 Minimum used operating phase
current level for step 4 in % of IBase, if
I4> is less than I4>Min then I4> is set
to I4>Min
I4>Max 5 - 2500 %IB 1 2500 Maximum used operating phase
current level for step 4 in % of IBase, if
I4> is greater than I4>Max then I4> is
set to I4>Max
ResetTypeCrv4 Instantaneous - - Instantaneous Selection of reset curve type for step
IEC Reset 4
ANSI reset
Table continues on next page

Line distance protection REL670 443


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

Name Values (Range) Unit Step Default Description


tReset4 0.000 - 60.000 s 0.001 0.020 Constant reset time for step 4
tPCrv4 0.005 - 3.000 - 0.001 1.000 Parameter P for customer
programmable curve for step 4
tACrv4 0.005 - 200.000 - 0.001 13.500 Parameter A for customer
programmable curve for step 4
tBCrv4 0.00 - 20.00 - 0.01 0.00 Parameter B for customer
programmable curve for step 4
tCCrv4 0.1 - 10.0 - 0.1 1.0 Parameter C for customer
programmable curve for step 4
tPRCrv4 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer
programmable curve for step 4
tTRCrv4 0.005 - 100.000 - 0.001 13.500 Parameter TR for customer
programmable curve for step 4
tCRCrv4 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer
programmable curve for step 4
HarmBlock4 Off - - Off Enable block of step 4 from harmonic
On restrain

Table 254: OC4PTOC Non group settings (basic)


Name Values (Range) Unit Step Default Description
MeasType DFT - - DFT Selection between DFT and RMS
RMS measurement
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

9.2.6 Monitored data


PID-6973-MONITOREDDATA v3

Table 255: OC4PTOC Monitored data


Name Type Values (Range) Unit Description
DIRL1 INTEGER 1=Forward - Direction for phase1
2=Reverse
0=No direction
DIRL2 INTEGER 1=Forward - Direction for phase2
2=Reverse
0=No direction
DIRL3 INTEGER 1=Forward - Direction for phase3
2=Reverse
0=No direction
IL1 REAL - A Current in phase L1
IL2 REAL - A Current in phase L2
IL3 REAL - A Current in phase L3

9.2.7 Operation principle M12883-3 v10

Directional phase overcurrent protection, four steps OC4PTOC is divided into four different
sub-functions. For each step x , where x is step 1, 2, 3 and 4, an operation mode is set by
DirModex: Off/Non-directional/Forward/Reverse.

444 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

The protection design can be divided into four parts:

• The direction element


• The harmonic restraint blocking function
• The four step overcurrent function
• The mode selection

If VT inputs are not available or not connected, setting parameter DirModex


shall be left to default value, Non-directional.

4 step overcurrent
Direction dirPh1Flt element faultState
faultState
Element One element for each
dirPh2Flt step
I3P dirPh3Flt START

U3P

TRIP

Harmonic harmRestrBlock
Restraint
Element

enableDir
Mode Selection
enableStep1-4
DirectionalMode1-4

IEC05000740-3-en.vsdx

IEC05000740 V3 EN-US

Figure 257: Functional overview of OC4PTOC


M12883-16 v11
A common setting for all steps, StartPhSel, is used to specify the number of phase currents to
be high to enable operation. These settings can be chosen: 1 out of 3, 2 out of 3 or 3 out of 3.

Using a parameter setting MeasType within the general settings for the function OC4PTOC, it
is possible to select the type of the measurement used for all overcurrent stages. Either
discrete Fourier filter (DFT) or true RMS filter (RMS) can be selected.

If the DFT option is selected, only the RMS value of the fundamental frequency component of
each phase current is derived. The influence of the DC current component and higher harmonic
current components are almost completely suppressed. If the RMS option is selected, then the
true RMS value is used. The true RMS value includes the contribution from the current DC
component as well as from the higher current harmonic in addition to the fundamental
frequency component.

In a comparator, the DFT or RMS values are compared to the set operation current value of the
function (I1>, I2>, I3> or I4>) for each phase current. If a phase current is larger than the set
operation current, outputs START, STx, STL1, STL2 and STL3 are activated without delay.
Output signals STL1, STL2 and STL3 are common for all steps. This means that the lowest set
step will initiate the activation. The START signal is common for all three phases and all steps.
It shall be noted that the selection of measured value (DFT or RMS) do not influence the
operation of directional part of OC4PTOC.

Line distance protection REL670 445


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

Service values for individually measured phase currents are available on the local HMI for
OC4PTOC function, which simplifies testing, commissioning and in service operational
checking of the function.

A harmonic restrain of the function can be chosen. A set 2nd harmonic current in relation to
the fundamental current is used.

The function can be directional.The direction of a fault is given as the current angle in relation
to the voltage angle. The fault current and fault voltage for the directional function are
dependent on the fault type. The selection of the measured value (DFT or RMS) does not
influence the operation of the directional part of OC4PTOC. To enable directional
measurement at close-in faults, causing a low measured voltage, the polarization voltage is a
combination of the apparent voltage (85%) and a memory voltage (15%). The following
combinations are used.

Phase-phase short circuit:

U refL1L 2 = U L1 - U L 2 I dirL1L 2 = I L1 - I L 2
EQUATION1449 V1 EN-US (Equation 103)

U refL 2 L 3 = U L 2 - U L 3 I dirL 2 L 3 = I L 2 - I L 3
EQUATION1450 V1 EN-US (Equation 104)

U refL 3 L1 = U L 3 - U L1 I dirL 3 L1 = I L 3 - I L1
EQUATION1451 V1 EN-US (Equation 105)

Phase-earth short circuit:

U refL1 = U L1 I dirL1 = I L1
EQUATION1452 V1 EN-US (Equation 106)

U refL 2 = U L 2 I dirL 2 = I L 2
EQUATION1453 V1 EN-US (Equation 107)

U refL 3 = U L 3 I dirL 3 = I L 3
EQUATION1454 V1 EN-US (Equation 108)

The polarizing voltage is available as long as the positive-sequence voltage exceeds 5% of the
set base voltage UBase. So the directional element can be used for all unsymmetrical faults
including close-in faults.

For close-in three-phase faults, the U1L1M memory voltage, based on the same positive
sequence voltage, ensures correct directional discrimination.

The memory voltage is used for 100 ms or until the positive sequence voltage is restored.

After 100 ms, the following occurs:

• If the current is still above the set value of the minimum operating current (7% of the set
terminal rated current IBase), the condition seals in.

446 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

• If the fault has caused tripping, the trip endures.


• If the fault was detected in the reverse direction, the measuring element in the
reverse direction remains in operation.
• If the current decreases below the minimum operating value, the memory resets until the
positive sequence voltage exceeds 10% of its rated value.

The directional setting is given as a characteristic angle AngleRCA for the function and an
angle window ROADir.

Reverse

Uref

RCA
ROA

ROA Forward

Idir

en05000745.vsd
IEC05000745 V1 EN-US

Figure 258: Directional characteristic of the phase overcurrent protection


The default value of AngleRCA is –55°. The parameter AngleROA gives the angular distance
from AngleRCA to define the directional borders.

A minimum current for the directional phase start current signal can be set. IMinOpPhSel is the
start level for the directional evaluation of IL1, IL2 and IL3. The directional signals release the
overcurrent measurement in the respective phases if their current amplitudes are higher than
the start level (IMinOpPhSel) and the direction of the current is according to the set direction
of the step.

If no blocking signals are active, the start signal will start the timer of the steps. The time
characteristic for each step can be chosen as definite time delay or an inverse time delay
characteristic. A wide range of standardized inverse time delay characteristics is available. It is
also possible to create a tailor made time characteristic.

The possibilities for inverse time characteristics are described in section "Inverse
characteristics".

Line distance protection REL670 447


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

Characteristx=DefTime
|IOP| AND
tx TRx
a OR
a>b
Ix> b

AND
STx

txmin
BLKSTx AND
BLOCK
Inverse

Characteristx=Inverse

DirModex=Off OR STAGEx_DIR_Int
DirModex=Non-directional
DirModex=Forward
AND OR
FORWARD_Int
DirModex=Reverse

AND
REVERSE_Int

IEC12000008.vsd
IEC12000008.vsd

IEC12000008 V2 EN-US

Figure 259: Simplified logic diagram for OC4PTOC

I3P
DFWDLx

U3P DFWDLxx

DREVLx
Directional
Element
AngleRCA DREVLxx FORWARD_int

Directional
AngleROA Release REVERSE_int
Block

STLx

Greater
IMinOpPhSel Comparator
x‐ means three phases 1,2 and 3
xx – means phase to phase 12,23,31

IEC15000266-2-en.vsdx
IEC15000266 V2 EN-US

Figure 260: OC4 directional release block diagram


Different types of reset time can be selected as described in section "Inverse characteristics".

There is a possibility to activate a preset change (IxMult x= 1, 2, 3 or 4) of the set operation


current via a binary input ENMULTx (enable multiplier). In some applications the operation
value needs to be changed, for example due to changed network switching state.

448 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

The operation current value Ix>, is limited to be between Ix>Max and Ix>Min. The default values
of the limits are the same as the setting limits for Ix>, and the limits can only be used for
reducing the allowed range of Ix>. This feature is used when remote setting of the operation
current value is allowed, making it possible to ensure that the operation value used is
reasonable. If Ix> is set outside Ix>Max and Ix>Min, the closest of the limits to Ix> is used by
the function. If Ix>Max is smaller then Ix>Min, the limits are swapped. The principle of the
limitation is shown in Figure 261.

Ix>Max
MAX hi

u y
Ix>_used
Ix>

MIN lo
Ix>Min

IEC17000018-1-en.vsdx
IEC17000018 V1 EN-US

Figure 261: Logic for limitation of used operation current value

The STDIRCND output provides an integer signal that depends on the start and directional
evaluation and is derived from a binary coded signal as described in Table 256.

Table 256: Code description for STDIRCND output signal


STDIRCND Description
bit 0 (1) General start
bit 1 (2) Direction detected in forward
bit 2 (4) Direction detected in reverse
bit 3 (8) Start in phase L1
bit 4 (16) Forward direction detected in phase L1
bit 5 (32) Reverse direction detected in phase L1
bit 6 (64) Start in phase L2
bit 7 (128) Forward direction detected in phase L2
bit 8 (256) Reverse direction detected in phase L2
bit 9 (512) Start in phase L3
bit 10 (1024) Forward direction detected in phase L3
bit 11 (2048) Reverse direction detected in phase L3

All four steps in OC4PTOC can be blocked from the binary input BLOCK. The binary input
BLKSTx (x=1, 2, 3 or 4) blocks the operation of the respective step.

The start signals from the function can be blocked by the binary input BLKST.The trip signals
from the function can be blocked by the binary input BLKTR.
GUID-E3980B2D-EEDA-4BF1-A07D-E7B721130554 v6
A harmonic restrain of the directional phase overcurrent protection function OC4PTOC can be
chosen. If the ratio of the 2nd harmonic component in relation to the fundamental frequency
component in a phase current exceeds the preset level defined by the parameter 2ndHarmStab
setting, any of the four overcurrent stages can be selectively blocked by the parameter
HarmBlockx setting. When the 2nd harmonic restraint feature is active, the OC4PTOC function
output signal ST2NDHRM will be set to the logical value one.

Line distance protection REL670 449


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

BLOCK

a
a>b
0.07*IBase b

a
a>b
b
Extract second AND
IOP
harmonic current a
a>b
component b

2ndH_BLOCK_Int
Extract
fundamental
current component
X
2ndHarmStab

IEC13000014-2-en.vsd
IEC13000014 V2 EN-US

Figure 262: Second harmonic blocking

When DirModex is set to Forward/Reverse and Ix> is set at its minimum value,
that is, 5.0% of IBase, the operation from the respective overcurrent step takes
place at 20.0% of IBase. This is done to avoid unintentional maloperations
during unbalanced loading conditions that might appear in power systems and
the unbalanced loading condition might lead to a neutral current in the range
of 10.0% to 15.0% of IBase.

9.2.8 Technical data


M12342-1 v21

Table 257: OC4PTOC technical data


Function Range or value Accuracy
Operate current, step 1-4 (5-2500)% of lBase ±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir

Reset ratio > 95% at (50–2500)% of -


lBase
Minimum operate current, step 1-4 (1-10000)% of lBase ±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir

Relay characteristic angle (RCA) (40.0–65.0) degrees ±2.0 degrees


Relay operating angle (ROA) (40.0–89.0) degrees ±2.0 degrees
Second harmonic blocking (5–100)% of fundamental ±2.0% of Ir

Independent time delay at 0 to 2 x Iset, step (0.000-60.000) s ±0.2% or ±35 ms whichever is


1-4 greater

Minimum operate time for inverse curves , (0.000-60.000) s ±0.2% or ±35 ms whichever is
step 1-4 greater
Inverse time characteristics, see 16 curve types See table 1150, table 1151 and
table 1150, table 1151 and table 1152 table 1152
Operate time, start non-directional at 0 to Min. = 15 ms -
2 x Iset
Max. = 30 ms
Reset time, start non-directional at 2 x Iset Min. = 15 ms -
to 0
Max. = 30 ms
Operate time, start non-directional at 0 to Min. = 5 ms -
10 x Iset Max. = 20 ms

Table continues on next page

450 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

Function Range or value Accuracy


Reset time, start non-directional at 10 x Iset Min. = 20 ms -
to 0 Max. = 35 ms

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Impulse margin time 15 ms typically -


Operate frequency, directional overcurrent 38-83 Hz -
Operate frequency, non-directional 10-90 Hz -
overcurrent

9.3 Instantaneous residual overcurrent protection EFPIOC IP14508-1 v3

9.3.1 Identification
M14887-1 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Instantaneous residual overcurrent EFPIOC 50N
protection
IN>>

IEF V1 EN-US

9.3.2 Functionality M12701-3 v16

The Instantaneous residual overcurrent protection (EFPIOC) has a low transient overreach and
short tripping times to allow the use for instantaneous earth-fault protection, with the reach
limited to less than the typical eighty percent of the line at minimum source impedance.
EFPIOC is configured to measure the residual current from the three-phase current inputs and
can be configured to measure the current from a separate current input.

9.3.3 Function block M12614-3 v6

EFPIOC
I3P* TRIP
BLOCK
BLKAR
ENMULT

IEC06000269-3-en.vsdx
IEC06000269 V3 EN-US

Figure 263: EFPIOC function block

9.3.4 Signals IP11448-1 v2

Line distance protection REL670 451


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

PID-6915-INPUTSIGNALS v4

Table 258: EFPIOC Input signals


Name Type Default Description
I3P GROUP - Three phase currents
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKAR BOOLEAN 0 Block input for auto reclose
ENMULT BOOLEAN 0 Enable current multiplier

PID-6915-OUTPUTSIGNALS v4

Table 259: EFPIOC Output signals


Name Type Description
TRIP BOOLEAN Trip signal

9.3.5 Settings IP11449-1 v2

PID-6915-SETTINGS v4

Table 260: EFPIOC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
IN>> 5 - 2500 %IB 1 200 Operate residual current level in % of
IBase

Table 261: EFPIOC Group settings (advanced)


Name Values (Range) Unit Step Default Description
IN>>Min 5 - 2500 %IB 1 5 Minimum used operate residual
current level in % of IBase, if IN>> is
less than IN>>Min then IN>> is set to
IN>>Min
IN>>Max 5 - 2500 %IB 1 2500 Maximum used operate residual
current level in % of IBase, if IN>> is
greater than IN>>Max then IN>> is set
to IN>>Max
StValMult 0.5 - 5.0 - 0.1 1.0 Multiplier for operate current level

Table 262: EFPIOC Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

9.3.6 Monitored data


PID-6915-MONITOREDDATA v4

Table 263: EFPIOC Monitored data


Name Type Values (Range) Unit Description
IN REAL - A Residual current

452 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

9.3.7 Operation principle M12704-3 v8

The sampled analog residual currents are pre-processed in a discrete Fourier filter (DFT) block.
From the fundamental frequency components of the residual current, as well as from the
sample values the equivalent RMS value is derived. This current value is fed to the
Instantaneous residual overcurrent protection (EFPIOC). In a comparator the RMS value is
compared to the set operation current value of the function (IN>>).

If the residual current is larger than the set operation current a signal from the comparator is
set to true. This signal will, without delay, activate the output signal TRIP.

There is also a possibility to activate a preset change of the set operation current via a binary
input (enable multiplier ENMULT). In some applications the operation value needs to be
changed, for example, due to transformer inrush currents.

The operation current value IN>>, is limited to be between IN>>Max and IN>>Min. The default
values of the limits are the same as the setting limits for IN>>, and the limits can only be used
for reducing the allowed range of IN>>. This feature is used when remote setting of the
operation current value is allowed, making it possible to ensure that the operation value used
is reasonable. If IN>> is set outside IN>>Max and IN>>Min, the closest of the limits to IN>> is
used by the function. If IN>>Max is smaller then IN>>Min, the limits are swapped. The principle
of the limitation is shown in Figure 264.

IN>>Max
MAX hi

u y
IN>>_used
IN>>

MIN lo
IN>>Min

IEC17000015-1-en.vsdx
IEC17000015 V1 EN-US

Figure 264: Logic for limitation of used operation current value

EFPIOC function can be blocked from the binary input BLOCK. The trip signals from the
function can be blocked from the binary input BLKAR, that can be activated during single pole
trip and autoreclosing sequences.

9.3.8 Technical data IP11450-1 v1

M12340-2 v9

Table 264: EFPIOC technical data


Function Range or value Accuracy
Operate current (5-2500)% of lBase ±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir

Reset ratio > 95% at (50–2500)% of lBase -


Operate time at 0 to 2 x Iset Min. = 15 ms -
Max. = 25 ms
Reset time at 2 x Iset to 0 Min. = 15 ms -
Max. = 25 ms
Critical impulse time 10 ms typically at 0 to 2 x Iset -

Operate time at 0 to 10 x Min. = 5 ms -


Iset Max. = 15 ms

Table continues on next page

Line distance protection REL670 453


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

Function Range or value Accuracy


Reset time at 10 x Iset to 0 Min. = 25 ms -
Max. = 35 ms
Critical impulse time 2 ms typically at 0 to 10 x Iset -

Dynamic overreach < 5% at t = 100 ms -

9.4 Directional residual overcurrent protection, four steps


EF4PTOC IP14509-1 v8

9.4.1 Identification
M14881-1 v6

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Directional residual overcurrent EF4PTOC 51N_67N
4(IN>)
protection, four steps
4
alt
4
TEF-REVA V2 EN-US

9.4.2 Functionality M13667-3 v19

Directional residual overcurrent protection, four steps (EF4PTOC) can be used as main
protection for phase-to-earth faults. It can also be used to provide a system back-up, for
example, in the case of the primary protection being out of service due to communication or
voltage transformer circuit failure.

EF4PTOC has an inverse or definite time delay independent for each step.

All IEC and ANSI time-delayed characteristics are available together with an optional user-
defined characteristic.

EF4PTOC can be set to be directional or non-directional independently for each step.

IDir, UPol and IPol can be independently selected to be either zero sequence or negative
sequence.

A second harmonic blocking can be set individually for each step.

Directional operation can be combined together with the corresponding communication logic
in permissive or blocking teleprotection scheme. The current reversal and weak-end infeed
functionality are available as well.

The residual current can be calculated by summing the three-phase currents or taking the
input from the neutral CT.

454 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

9.4.3 Function block M12619-3 v8

EF4PTOC
I3P* TRIP
U3P* TRIN1
I3PPOL* TRIN2
I3PDIR* TRIN3
BLOCK TRIN4
BLKTR TRSOTF
BLKST1 START
BLKST2 STIN1
BLKST3 STIN2
BLKST4 STIN3
ENMULT1 STIN4
ENMULT2 STSOTF
ENMULT3 STFW
ENMULT4 STRV
CBPOS 2NDHARMD
CLOSECB
OPENCB
IEC06000424-5-en.vsdx
IEC06000424 V5 EN-US

Figure 265: EF4PTOC function block

9.4.4 Signals IP11453-1 v2

PID-6967-INPUTSIGNALS v3

Table 265: EF4PTOC Input signals


Name Type Default Description
I3P GROUP - Group connection for operate current
SIGNAL
U3P GROUP - Group connection for polarizing voltage
SIGNAL
I3PPOL GROUP - Group connection for polarizing current
SIGNAL
I3PDIR GROUP - Group connection for directional current
SIGNAL
BLOCK BOOLEAN 0 General block
BLKTR BOOLEAN 0 Block of trip
BLKST1 BOOLEAN 0 Block of step 1 (Start and trip)
BLKST2 BOOLEAN 0 Block of step 2 (Start and trip)
BLKST3 BOOLEAN 0 Block of step 3 (Start and trip)
BLKST4 BOOLEAN 0 Block of step 4 (Start and trip)
ENMULT1 BOOLEAN 0 When activated, the current multiplier is in use for step1
ENMULT2 BOOLEAN 0 When activated, the current multiplier is in use for step2
ENMULT3 BOOLEAN 0 When activated, the current multiplier is in use for step3
ENMULT4 BOOLEAN 0 When activated, the current multiplier is in use for step4
CBPOS BOOLEAN 0 Breaker position
CLOSECB BOOLEAN 0 Breaker close command
OPENCB BOOLEAN 0 Breaker open command

Line distance protection REL670 455


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

PID-6967-OUTPUTSIGNALS v3

Table 266: EF4PTOC Output signals


Name Type Description
TRIP BOOLEAN General trip signal
TRIN1 BOOLEAN Trip signal from step 1
TRIN2 BOOLEAN Trip signal from step 2
TRIN3 BOOLEAN Trip signal from step 3
TRIN4 BOOLEAN Trip signal from step 4
TRSOTF BOOLEAN Trip signal from earth fault switch onto fault function
START BOOLEAN General start signal
STIN1 BOOLEAN Start signal step 1
STIN2 BOOLEAN Start signal step 2
STIN3 BOOLEAN Start signal step 3
STIN4 BOOLEAN Start signal step 4
STSOTF BOOLEAN Start signal from earth fault switch onto fault function
STFW BOOLEAN Start signal forward direction
STRV BOOLEAN Start signal reverse direction
2NDHARMD BOOLEAN 2nd harmonic block signal

9.4.5 Settings IP11454-1 v2

PID-6967-SETTINGS v3

Table 267: EF4PTOC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
EnDir Disable - - Enable Enabling the Directional calculation
Enable
AngleRCA -180 - 180 Deg 1 65 Relay Characteristic Angle (RCA)
polMethod Voltage - - Voltage Type of polarization
Current
Dual
UPolMin 1 - 100 %UB 1 1 Minimum voltage level for polarization
in % of UBase
IPolMin 2 - 100 %IB 1 5 Minimum current level for polarization
in % of IBase
RNPol 0.50 - 1000.00 Ohm 0.01 5.00 Real part of source impedance used
for current polarisation
XNPol 0.50 - 3000.00 Ohm 0.01 40.00 Imaginary part of source imp. used for
current polarisation
IN>Dir 1 - 100 %IB 1 10 Residual current level in % of IBase for
Direction release
2ndHarmStab 5 - 100 % 1 20 Operate level of 2nd harmonic curr in
% of fundamental curr
BlkParTransf Off - - Off Enable blocking at energizing of
On parallel transformers
Table continues on next page

456 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

Name Values (Range) Unit Step Default Description


UseStartValue IN1> - - IN4> Current level blk at parallel transf
IN2> (step1, 2, 3 or 4)
IN3>
IN4>
SOTF Off - - Off SOTF operation mode (Off/SOTF/
SOTF Undertime/SOTF&Undertime)
UnderTime
SOTF&UnderTime
ActivationSOTF Open - - Open Select signal to activate SOTF: CB-
Closed Open/ -Closed/ -Close cmd
CloseCommand
StepForSOTF Step 2 - - Step 2 Select start from step 2 or 3 to start
Step 3 SOTF
HarmBlkSOTF Off - - Off Enable harmonic restrain function in
On SOTF
tSOTF 0.000 - 60.000 s 0.001 0.200 Time delay for SOTF
t4U 0.000 - 60.000 s 0.001 1.000 Switch-onto-fault active time
ActUnderTime CB position - - CB position Select signal to activate under time
CB command (CB Pos / CB Command)
tUnderTime 0.000 - 60.000 s 0.001 0.300 Time delay for under time
DirMode1 Off - - Non-directional Directional mode of step 1 (Off, Non-
Non-directional dir, Forward, Reverse)
Forward
Reverse
Characterist1 ANSI Ext. inv. - - ANSI Def. Time Time delay characteristic for step 1
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
IN1> 1 - 2500 %IB 1 100 Residual current operate level for step
1 in % of IBase
t1 0.000 - 60.000 s 0.001 0.000 Def time delay or add time delay for
inverse char of step 1
k1 0.05 - 999.00 - 0.01 0.05 Time multiplier for the step 1 selected
time characteristic
IMin1 1.00 - 10000.00 %IB 1.00 100.00 Minimum operate residual current for
step 1 in % of IBase
t1Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse
time characteristic step 1
IN1Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for the residual current
setting value for step 1
HarmBlock1 Off - - On Enable block of step 1 from harmonic
On restrain
Table continues on next page

Line distance protection REL670 457


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

Name Values (Range) Unit Step Default Description


DirMode2 Off - - Non-directional Directional mode of step 2 (Off, Non-
Non-directional dir, Forward, Reverse)
Forward
Reverse
Characterist2 ANSI Ext. inv. - - ANSI Def. Time Time delay characteristic for step 2
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
IN2> 1 - 2500 %IB 1 50 Residual current operate level for step
2 in % of IBase
t2 0.000 - 60.000 s 0.001 0.400 Def time delay or add time delay for
inverse char of step 2
k2 0.05 - 999.00 - 0.01 0.05 Time multiplier for the step 2 selected
time characteristic
IMin2 1.00 - 10000.00 %IB 1.00 50 Minimum operate residual current for
step 2 in % of IBase
t2Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse
time characteristic step 2
IN2Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for the residual current
setting value for step 2
HarmBlock2 Off - - On Enable block of step 2 from harmonic
On restrain
DirMode3 Off - - Non-directional Directional mode of step 3 (Off, Non-
Non-directional dir, Forward, Reverse)
Forward
Reverse
Characterist3 ANSI Ext. inv. - - ANSI Def. Time Time delay characteristic for step 3
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
IN3> 1 - 2500 %IB 1 33 Residual current operate level for step
3 in % of IBase
Table continues on next page

458 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

Name Values (Range) Unit Step Default Description


t3 0.000 - 60.000 s 0.001 0.800 Def time delay or add time delay for
inverse char of step 3
k3 0.05 - 999.00 - 0.01 0.05 Time multiplier for the step 3 selected
time characteristic
IMin3 1.00 - 10000.00 %IB 1.00 33 Minimum operate residual current for
step 3 in % of IBase
t3Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse
time characteristic step 3
IN3Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for the residual current
setting value for step 3
HarmBlock3 Off - - On Enable block of step 3 from harmonic
On restrain
DirMode4 Off - - Non-directional Directional mode of step 4 (Off, Non-
Non-directional dir, Forward, Reverse)
Forward
Reverse
Characterist4 ANSI Ext. inv. - - ANSI Def. Time Time delay characteristic for step 4
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
IN4> 1 - 2500 %IB 1 17 Residual current operate level for step
4 in % of IBase
t4 0.000 - 60.000 s 0.001 1.200 Def time delay or add time delay for
inverse char of step 4
k4 0.05 - 999.00 - 0.01 0.05 Time multiplier for the step 4 selected
time characteristic
IMin4 1.00 - 10000.00 %IB 1.00 17 Minimum operate residual current for
step 4 in % of IBase
t4Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse
time characteristic step 4
IN4Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for the residual current
setting value for step 4
HarmBlock4 Off - - On Enable block of step 4 from harmonic
On restrain

Line distance protection REL670 459


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

Table 268: EF4PTOC Group settings (advanced)


Name Values (Range) Unit Step Default Description
IN1>Min 1 - 2500 %IB 1 1 Minimum used operate residual
current level for step 1 in % of IBase, if
IN1> is less than IN1>Min then IN1> is
set to IN1>Min
IN1>Max 1 - 2500 %IB 1 2500 Maximum used operate residual
current level for step 1 in % of IBase, if
IN1> is greater than IN1>Max then IN1>
is set to IN1>Max
ResetTypeCrv1 Instantaneous - - Instantaneous Reset curve type for step1
IEC Reset (Instantaneous / IEC / ANSI)
ANSI reset
tReset1 0.000 - 60.000 s 0.001 0.020 Reset time delay for step 1
tPCrv1 0.005 - 3.000 - 0.001 1.000 Param P for customized inverse trip
time curve for step 1
tACrv1 0.005 - 200.000 - 0.001 13.500 Param A for customized inverse trip
time curve for step 1
tBCrv1 0.00 - 20.00 - 0.01 0.00 Param B for customized inverse trip
time curve for step 1
tCCrv1 0.1 - 10.0 - 0.1 1.0 Param C for customized inverse trip
time curve for step 1
tPRCrv1 0.005 - 3.000 - 0.001 0.500 Param PR for customized inverse reset
time curve for step 1
tTRCrv1 0.005 - 100.000 - 0.001 13.500 Param TR for customized inverse reset
time curve for step 1
tCRCrv1 0.1 - 10.0 - 0.1 1.0 Param CR for customized inverse
reset time curve for step 1
IN2>Min 1 - 2500 %IB 1 1 Minimum used operate residual
current level for step 2 in % of IBase, if
IN2> is less than IN2>Min then IN2> is
set to IN2>Min
IN2>Max 1 - 2500 %IB 1 2500 Maximum used operate residual
current level for step 2 in % of IBase, if
IN2> is greater than IN2>Max then
IN2> is set to IN2>Max
ResetTypeCrv2 Instantaneous - - Instantaneous Reset curve type for step2
IEC Reset (Instantaneous / IEC / ANSI)
ANSI reset
tReset2 0.000 - 60.000 s 0.001 0.020 Reset time delay for step 2
tPCrv2 0.005 - 3.000 - 0.001 1.000 Param P for customized inverse trip
time curve for step 2
tACrv2 0.005 - 200.000 - 0.001 13.500 Param A for customized inverse trip
time curve for step 2
tBCrv2 0.00 - 20.00 - 0.01 0.00 Param B for customized inverse trip
time curve for step 2
tCCrv2 0.1 - 10.0 - 0.1 1.0 Param C for customized inverse trip
time curve for step 2
tPRCrv2 0.005 - 3.000 - 0.001 0.500 Param PR for customized inverse reset
time curve for step 2
tTRCrv2 0.005 - 100.000 - 0.001 13.500 Param TR for customized inverse reset
time curve for step 2
tCRCrv2 0.1 - 10.0 - 0.1 1.0 Param CR for customized inverse
reset time curve for step 2
Table continues on next page

460 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

Name Values (Range) Unit Step Default Description


IN3>Min 1 - 2500 %IB 1 1 Minimum used operate residual
current level for step 3 in % of IBase, if
IN3> is less than IN3>Min then IN3> is
set to IN3>Min
IN3>Max 1 - 2500 %IB 1 2500 Maximum used operate residual
current level for step 3 in % of IBase, if
IN3> is greater than IN3>Max then
IN3> is set to IN3>Max
ResetTypeCrv3 Instantaneous - - Instantaneous Reset curve type for step3
IEC Reset (Instantaneous / IEC / ANSI)
ANSI reset
tReset3 0.000 - 60.000 s 0.001 0.020 Reset time delay for step 3
tPCrv3 0.005 - 3.000 - 0.001 1.000 Param P for customized inverse trip
time curve for step 3
tACrv3 0.005 - 200.000 - 0.001 13.500 Param A for customized inverse trip
time curve for step 3
tBCrv3 0.00 - 20.00 - 0.01 0.00 Param B for customized inverse trip
time curve for step 3
tCCrv3 0.1 - 10.0 - 0.1 1.0 Param C for customized inverse trip
time curve for step 3
tPRCrv3 0.005 - 3.000 - 0.001 0.500 Param PR for customized inverse reset
time curve for step 3
tTRCrv3 0.005 - 100.000 - 0.001 13.500 Param TR for customized inverse reset
time curve for step 3
tCRCrv3 0.1 - 10.0 - 0.1 1.0 Param CR for customized inverse
reset time curve for step 3
IN4>Min 1 - 2500 %IB 1 1 Minimum used operate residual
current level for step 4 in % of IBase, if
IN4> is less than IN4>Min then IN4> is
set to IN4>Min
IN4>Max 1 - 2500 %IB 1 2500 Maximum used operate residual
current level for step 4 in % of IBase, if
IN4> is greater than IN4>Max then
IN4> is set to IN4>Max
ResetTypeCrv4 Instantaneous - - Instantaneous Reset curve type for step4
IEC Reset (Instantaneous / IEC / ANSI)
ANSI reset
tReset4 0.000 - 60.000 s 0.001 0.020 Reset time delay for step 4
tPCrv4 0.005 - 3.000 - 0.001 1.000 Param P for customized inverse trip
time curve for step 4
tACrv4 0.005 - 200.000 - 0.001 13.500 Param A for customized inverse trip
time curve for step 4
tBCrv4 0.00 - 20.00 - 0.01 0.00 Param B for customized inverse trip
time curve for step 4
tCCrv4 0.1 - 10.0 - 0.1 1.0 Param C for customized inverse trip
time curve for step 4
tPRCrv4 0.005 - 3.000 - 0.001 0.500 Param PR for customized inverse reset
time curve for step 4
tTRCrv4 0.005 - 100.000 - 0.001 13.500 Param TR for customized inverse reset
time curve for step 4
tCRCrv4 0.1 - 10.0 - 0.1 1.0 Param CR for customized inverse
reset time curve for step 4

Line distance protection REL670 461


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

Table 269: EF4PTOC Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups
SeqTypeIDir Zero seq - - Zero seq Choice of measurand for directional
Neg seq current
SeqTypeIPol Zero seq - - Zero seq Choice of measurand for polarizing
Neg seq current
SeqTypeUPol Zero seq - - Zero seq Choice of measurand for polarizing
Neg seq voltage

9.4.6 Monitored data


PID-6967-MONITOREDDATA v3

Table 270: EF4PTOC Monitored data


Name Type Values (Range) Unit Description
IOp REAL - A Operating current level
UPol REAL - kV Polarizing voltage level
IPol REAL - A Polarizing current level
UPOLIANG REAL - deg Polarizing angle between voltage and
current
IPOLIANG REAL - deg Polarizing current angle

9.4.7 Operation principle IP12992-1 v2

M13941-51 v7
This function has the following four analog inputs on its function block in the configuration
tool:

1. I3P, input used for the operating quantity. Supplies the zero-sequence magnitude
measuring functionality.
2. U3P, input used for the voltage polarizing quantity. Supplies either the zero or the
negative sequence voltage to the directional functionality
3. I3PPOL, input used for the current polarizing quantity. Provides polarizing current to the
directional functionality. This current is normally taken from the grounding of a power
transformer.
4. I3PDIR, input used for directional detection. Supplies either the zero or the negative
sequence current to the directional functionality.

These inputs are connected from the corresponding pre-processing function blocks in the
configuration tool in PCM600.

9.4.7.1 Operating quantity within the function M13941-58 v9

The function always uses residual current (3I0) for its operating quantity. The residual current
can be:

1. directly measured (when a dedicated CT input of the IED is connected in PCM600 to the
fourth analog input of the pre-processing block connected to EF4PTOC function input
I3P). This dedicated IED CT input can be, for example, connected to:

462 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

• parallel connection of current instrument transformers in all three phases (Holm-


Green connection).
• one single core balance current instrument transformer (cable CT).
• one single current instrument transformer located between power system star point
and earth (current transformer located in the star point of a star connected
transformer winding).
• one single current instrument transformer located between two parts of a protected
object (current transformer located between two star points of double star shunt
capacitor bank).
2. calculated from three-phase current input within the IED (when the fourth analog input of
the pre-processing block, connected to EF4PTOC function Analog Input I3P, is not
connected to a dedicated CT input of the IED in PCM600). In such a case, the pre-
processing block will calculate 3I0 from the first three inputs into the pre-processing block
by using the following formula (will take 3I0 from SMAI AI3P and will be connected to
I3PDIR and I3P inputs.

If the zero sequence current is selected,

Iop = 3I0 = IL1 + IL2 + IL3


EQUATION1874 V2 EN-US (Equation 109)

where:
IL1, IL2 and IL3 are fundamental frequency phasors of three individual phase currents.

The residual current is pre-processed by a discrete Fourier filter. Thus the phasor of the
fundamental frequency component of the residual current is derived. The phasor magnitude is
used within the EF4PTOC protection to compare it with the set operation current value of the
four steps (IN1>, IN2>, IN3> or IN4>).

If the residual current is larger than the set operation current and the step is used in non-
directional mode a signal from the comparator for this step is set to true. This signal will,
without delay, activate the output signal STINx (x=step 1-4) for this step and a common START
signal.

9.4.7.2 Internal polarizing M13941-82 v11

A polarizing quantity is used within the protection in order to determine the direction to the
earth fault (forward/reverse).

The function can be set to use voltage polarizing, current polarizing or dual polarizing.

Voltage polarizing
When voltage polarizing is selected, the protection will use the residual voltage -3U0 as the
polarizing quantity U3P.

This voltage can be:

1. directly measured (when a dedicated VT input of the IED is connected in PCM600 to the
fourth analog input of the pre-processing block connected to EF4PTOC function input
U3P). This dedicated IED VT input shall be then connected to the open delta winding of a
three-phase main VT.
2. calculated from three-phase voltage input within the IED (when the fourth analog input of
the pre-processing block, connected to EF4PTOC analog function input U3P, is NOT
connected to a dedicated VT input of the IED in PCM600). In such a case, the pre-

Line distance protection REL670 463


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

processing block will calculate -3U0 from the first three inputs into the pre-processing
block by using the following formula:

UPol = -3U 0 = -(UL1 + UL2 + UL3)


EQUATION1875 V2 EN-US (Equation 111)

where:
UL1, UL2 and UL3 are fundamental frequency phasors of three individual phase voltages.

In order to use this, all three phase-to-earth voltages must be connected to three
IED VT inputs.

The residual voltage is pre-processed by a discrete fourier filter. Thus, the phasor of the
fundamental frequency component of the residual voltage is derived.

This phasor is used together with the phasor of the operating directional current, in order to
determine the direction to the earth fault (Forward/Reverse). In order to enable voltage
polarizing the magnitude of polarizing voltage shall be bigger than a minimum level defined by
setting parameter UPolMin.

It shall be noted that residual voltage (-3U0) or negative sequence voltage (-3U2) is used to
determine the location of the earth fault. This ensures the required inversion of the polarizing
voltage within the earth-fault function.

Current polarizing
When current polarizing is selected, the function will use an external residual current (3I0) as
the polarizing quantity IPol. This current can be:

1. directly measured (when a dedicated CT input of the IED is connected in PCM600 to the
fourth analog input of the pre-processing block, connected to EF4PTOC function input
I3PPOL). This dedicated IED CT input is then typically connected to one single current
transformer located between power system star point and earth (current transformer
located in the star point of a star connected transformer winding).
• For some special line protection applications, this dedicated IED CT input can be
connected to a parallel connection of current transformers in all three phases (Holm-
Green connection).
2. calculated from three phase current input within the IED (when the fourth analog input
into the pre-processing block, connected to EF4PTOC function analog input I3PPOL, is
NOT connected to a dedicated CT input of the IED in PCM600). In such case, the pre-
processing block will calculate 3I0 from the first three inputs into the pre-processing block
by using the following formula:

IPol = 3I0 = IL1 + IL2 + IL3


EQUATION2018 V2 EN-US (Equation 113)

where:
IL1, IL2 and IL3 are fundamental frequency phasors of three individual phase currents.

The residual current is pre-processed by a discrete fourier filter. Thus the phasor of the
fundamental frequency component of the polarizing current is derived. This phasor is then

464 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

multiplied with the pre-set equivalent zero-sequence source impedance in order to calculate
the equivalent polarizing voltage UIPol in accordance with the following formula:

UIPol = Z 0s × IPol = (RNPol + j × XNPol) × IPol


EQUATION1877 V2 EN-US (Equation 114)

which will be then used, together with the phasor of the operating current, in order to
determine the direction to the earth fault (forward/reverse).

In order to enable current polarizing, the magnitude of the polarizing current shall be bigger
than a minimum level defined by setting parameter IPolMin.

Dual polarizing
When dual polarizing is selected, the function will use the vectorial sum of the voltage based
and current based polarizing in accordance with the following formula:

UTotPol=UPol  UIPol=UPol  Z 0s  IPol  UPol   RNPol  jXNPol   Ipol


IECEQUATION2408 V2 EN-US (Equation 115)

UPol and IPol can be either zero sequence component or negative sequence component
depending upon the user selection.

Then the phasor of the total polarizing voltage UTotPol will be used, together with the phasor
of the operating current, to determine the direction of the earth fault (forward/reverse).

9.4.7.3 External polarizing for earth-fault function M13941-144 v6

The individual steps within the protection can be set as non-directional. When this setting is
selected, it is possible via the function binary input BLKSTx to provide external directional
control (that is, torque control) by, for example, using one of the following functions if
available in the IED:

1. Distance protection directional function.


2. Negative sequence polarized general current and voltage multi purpose protection
function.

9.4.7.4 Directional detection for earth fault function GUID-FC382DD3-E2C8-455E-8CD5-1DE1793DD178 v6

Zero sequence components will be used for detecting directionality for the earth fault
function. In some cases, zero sequence quantities might detect directionality incorrectly. In
such a scenario, negative sequence quantities will be used. The user can select either zero
sequence components or negative sequence components for detecting directionality with the
parameter SeqTypeIPol. I3PDIR input is always connected to the same source as I3P input.

9.4.7.5 Base quantities within the protection M13941-152 v6

The base quantities are entered as global settings for all functions in the IED. Base current
(IBase) shall be entered as rated phase current of the protected object in primary amperes.
Base voltage (UBase) shall be entered as rated phase-to-phase voltage of the protected object
in primary kV.

9.4.7.6 Internal earth-fault protection structure M13941-157 v5

The protection is internally divided into the following parts:

Line distance protection REL670 465


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

1. Four residual overcurrent steps.


2. Directional supervision element for residual overcurrent steps with integrated directional
comparison step for communication based earth-fault protection schemes (permissive or
blocking).
3. Second harmonic blocking element with additional feature for sealed-in blocking during
switching of parallel transformers.
4. Switch on to fault feature with integrated Under-Time logic for detection of breaker
problems during breaker opening or closing sequence.

9.4.7.7 Four residual overcurrent steps M13941-166 v8

Each overcurrent step uses operating quantity Iop (residual current) as the measuring
quantity. Each of the four residual overcurrent steps has the following built-in facilities:

• Directional mode can be set to Off/Non-directional/Forward/Reverse. By this parameter


setting the directional mode of the step is selected.
• Residual current start value.
• Type of operating characteristic (inverse or definite time). By this parameter setting it is
possible to select inverse or definite time delay for the earth-fault protection. Most of the
standard IEC and ANSI inverse characteristics are available. For the complete list of
available inverse curves, please refer to section "Inverse characteristics".
• Type of reset characteristic (Instantaneous / IEC Reset / ANSI Reset). By this parameter
setting it is possible to select the reset characteristic of the step. For the complete list of
available reset curves, please refer to section "Inverse characteristics".
• Time delay related settings. By these parameter settings the properties like definite time
delay, minimum operating time for inverse curves, reset time delay and parameters to
define user programmable inverse curve are defined.
• Supervision by second harmonic blocking feature (On/Off). By this parameter setting it is
possible to prevent operation of the step if the second harmonic content in the residual
current exceeds the preset level.
• Multiplier for scaling of the set residual current pickup value by external binary signal. By
this parameter setting it is possible to increase residual current pickup value when
function binary input ENMULTx has logical value 1.
• The operation current value INx>, is limited to be between INx>Max and INx>Min. The
default values of the limits are the same as the setting limits for INx>, and the limits can
only be used for reducing the allowed range of INx>. This feature is used when remote
setting of the operation current value is allowed, making it possible to ensure that the
operation value used is reasonable. If INx> is set outside INx>Max and INx>Min, the closest
of the limits to INx> is used by the function. If INx>Max is smaller then INx>Min, the limits
are swapped. The principle of the limitation is shown in Figure 266.

INx>Max
MAX hi

u y
INx>_used
INx>

MIN lo
INx>Min
IEC17000017-1-en.vsdx
IEC17000017 V1 EN-US

Figure 266: Logic for limitation of used operation current value

Simplified logic diagram for one residual overcurrent step is shown in Figure 267.

466 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

BLKTR
EMULTX

IMinx Characteristx=DefTime
X T b
a>b
F a
tx TRINx
AND AND
|IOP|
a OR t
a>b
b

STINx
INxMult AND
X T
INx> F
AND Inverse
BLKSTx
AND
BLOCK Characteristx=Inverse

txmin
2ndHarm_BLOCK_Int
OR t
HarmRestrainx=Off

DirModex=Off OR STEPx_DIR_Int
DirModex=Non-directional
DirModex=Forward
AND OR
FORWARD_Int
DirModex=Reverse

AND
REVERSE_Int

IEC10000008.vsd

IEC10000008 V5 EN-US

Figure 267: Simplified logic diagram for residual overcurrent step x, where x = step 1, 2, 3 or 4
The protection can be completely blocked from the binary input BLOCK. Output signals for
respective step, and STINx and TRINx, can be blocked from the binary input BLKSTx. The trip
signals from the function can be blocked from the binary input BLKTR.

9.4.7.8 Directional supervision element with integrated directional comparison


function M13941-179 v11

At least one of the four residual overcurrent steps shall be set as directional in
order to enable execution of the directional supervision element and the
integrated directional comparison function.

The protection has an integrated directional feature. As the operating quantity current Iop is
always used, the polarizing method is determined by the parameter setting polMethod. The
polarizing quantity will be selected by the function in one of the following three ways:

1. When polMethod = Voltage, UPol will be used as polarizing quantity.


2. When polMethod = Current, IPol will be used as polarizing quantity.
3. When polMethod = Dual, UPol + IPol · ZNPol will be used as polarizing quantity.

The operating and polarizing quantity are then used inside the directional element, as shown
in Figure 268, in order to determine the direction of the earth fault.

Line distance protection REL670 467


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

Operating area

STRV
0.6 * IN>DIR
Characteristic for reverse
release of measuring steps
-RCA -85 deg
Characteristic
for STRV 40% of
IN>DIR RCA +85 deg

RCA
65° Upol = -3U 0

-RCA +85 deg

RCA -85 deg


Characteristic for forward
release of measuring steps
IN>DIR

STFW

I op = 3I0

Operating area
Characteristic
for STFW IEC11000243-1-en.ai
IEC11000243 V1 EN-US

Figure 268: Operating characteristic for earth-fault directional element using the zero
sequence components
The relevant setting parameters for the directional supervision element are:

• The directional element will be internally enabled to operate as soon as Iop is bigger than
40% of IN>Dir and the directional condition is fulfilled in the set direction.
• The relay characteristic angle AngleRCA, which defines the position of forward and reverse
areas in the operating characteristic.

The directional comparison will set the output binary signals:

1. STFW=1 when operating quantity magnitude Iop x cos(φ - AngleRCA) is bigger than
setting parameter IN>Dir and directional supervision element detects fault in forward
direction.
2. STRV=1 when operating quantity magnitude Iop x cos(φ - AngleRCA) is bigger than 60% of
setting parameter IN>Dir and directional supervision element detects fault in reverse
direction.

These signals shall be used for communication based earth-fault teleprotection


communication schemes (permissive or blocking).

Simplified logic diagram for directional supervision element with integrated directional
comparison step is shown in Figure 269:

468 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

| IopDir |
a
a>b STRV
b AND
REVERSE_Int
0.6
X
a
a>b STFW
IN>Dir b AND
FORWARD_Int

X
0.4

FWD
AND FORWARD_Int
AngleRCA
polMethod=Voltage
OR

Characteristic
UPolMin

Directional
polMethod=Dual UPol IPolMin
T
I3PDIR
polMethod=Current 0.0 F
OR
UTotPol
IPol AND REVERSE_Int
T RVS
0.0 F

UIPol STAGE1_DIR_Int
RNPol Complex X T STAGE2_DIR_Int
XNPol Number 0.0 F STAGE3_DIR_Int OR
STAGE4_DIR_Int
BLOCK AND

IEC07000067-6-en.vsdx

IEC07000067 V6 EN-US

Figure 269: Simplified logic diagram for directional supervision element with integrated directional
comparison step

9.4.7.9 Second harmonic blocking element M13941-200 v8

A harmonic restrain can be chosen for each step by a parameter setting HarmBlockx. If the
ratio of the 2nd harmonic component in relation to the fundamental frequency component in
the residual current exceeds the preset level (defined by parameter 2ndHarmStab), output
signal 2NDHARMD is set to logical value one and the harmonic restraining feature to the
function block will be applicable.

Blocking from the 2nd harmonic element activates if all of three criteria are satisfied:

1. The fundamental frequency component of the current > 1% of IBase


2. The second harmonic component > 1% of IBase
3. The ratio of the 2nd harmonic component in relation to the fundamental frequency
component in the residual current exceeds the preset level defined by the parameter
2ndHarmStab setting

In addition to the basic functionality explained above, the 2nd harmonic blocking can be set in
such way to seal-in until residual current disappears. This feature might be required to
stabilize EF4PTOC during switching of parallel transformers in the station. In case of parallel
transformers there is a risk of sympathetic inrush current. If one of the transformers is in
operation, and the parallel transformer is switched in, the asymmetric inrush current of the
switched-in transformer will cause partial saturation of the transformer already in service. This
is called transferred saturation. The 2nd harmonic of the inrush currents of the two

Line distance protection REL670 469


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

transformers is in phase opposition. The summation of the two currents thus gives a small 2nd
harmonic current. The residual fundamental current is however significant. The inrush current
of the transformer in service before the parallel transformer energizing, is a little delayed
compared to the first transformer. Therefore, we have high 2nd harmonic current component
initially. After a short period this current is however small and the normal 2nd harmonic
blocking resets. If the BlkParTransf function is activated, the 2nd harmonic restrain signal is
latched as long as the residual current measured by the relay is larger than a selected step
current level by using setting UseStartValue.

This feature has been called Block for Parallel Transformers. This 2nd harmonic seal-in feature
is activated when all of the following three conditions are simultaneously fulfilled:

1. Feature is enabled by entering setting parameter BlkParTransf = On.


2. Basic 2nd harmonic restraint feature has been active for at least 70ms.
3. Residual current magnitude is higher than the set start value for one of the four residual
overcurrent stages. By a parameter setting UseStartValue it is possible to select which
one of the four start values that will be used (IN1> or IN2> or IN3> or IN4>).

Once Block for Parallel Transformers is activated, the basic 2nd harmonic blocking signal is
sealed-in until the residual current magnitude falls below a value defined by parameter setting
UseStartValue (see condition 3 above).

Simplified logic diagram for 2nd harmonic blocking feature is shown in Figure 270.

470 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

BLOCK

a
a>b
0.07*IBase b

a
a>b
b
Extract second AND
IOP
harmonic current a
a>b
component b

Extract
fundamental
current component
X
2ndHarmStab

q-1

t=70ms OR
t AND OR 2ndH_BLOCK_Int

BlkParTransf=On

a
a>b
b
UseStartValue
IN1>
IN2>
IN3>
IN4>

q-1 = unit delay


IEC13000015-4-en.vsdx

IEC13000015 V4 EN-US

Figure 270: Simplified logic diagram for 2nd harmonic blocking feature and Block for Parallel
Transformers feature

9.4.7.10 Switch on to fault feature M13941-211 v5

Integrated in the four step residual overcurrent protection are the switch on to fault logic
(SOTF) and the under-time logic. The setting parameter SOTF is set to activate SOTF, the
under-time logic or both. When the circuit breaker is closing there is a risk to close it onto a
permanent fault, for example during an autoreclosing sequence. The SOTF logic will enable
fast fault clearance during such situations. The time during which SOTF and under-time logics
will be active after activation is defined by the setting parameter t4U.

The SOTF logic uses the start signal from step 2 or step 3 for its operation, selected by setting
parameter StepForSOTF. The setting parameter ActivationSOTF can be set for activation of CB
position open change, CB position closed change or CB close command. In case of a residual
current start from step 2 or 3 (dependent on setting) the function will give a trip after a set
delay tSOTF. This delay is normally set to a short time (default 200 ms).

The under-time logic acts as a circuit breaker pole-discordance protection, but it is only active
immediately after breaker switching. The under-time logic can only be used in solidly or low
impedance grounded systems.

The under-time logic always uses the start signal from the step 4. The under-time logic will
normally be set to operate for a lower current level than the SOTF function. The under-time

Line distance protection REL670 471


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

logic can also be blocked by the 2nd harmonic restraint feature. This enables high sensitivity
even if power transformer inrush currents can occur at breaker closing. This logic is typically
used to detect asymmetry of CB poles immediately after switching of the circuit breaker. The
under-time logic is activated either from change in circuit breaker position or from circuit
breaker close and open command pulses. This selection is done by setting parameter
ActUnderTime. In case of a start from step 4 this logic will give a trip after a set delay
tUnderTime. This delay is normally set to a relatively short time (default 300 ms).

SOTF

200 ms
Open
t
t4U
200 ms
Closed
t ActivationSOTF

tSOTF
Close command AND
AND t
STIN2

StepForSOTF
STIN3

SOTF
BLOCK
OFF
SOTF
UNDERTIME TRIP
UnderTime

tUnderTime
SOTF or
2nd Harmonic AND
HarmResSOFT t UnderTime

OR

Open
Close OR

t4U

Close command ActUnderTime


AND

STIN4

IEC06000643-6-en.vsdx

IEC06000643 V6 EN-US

Figure 271: Simplified logic diagram for SOTF and under-time features
M13941-3 v6
Simplified logic diagram for the complete EF4PTOC function is shown in Figure 272:

472 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

signal to communication scheme


Directional Check
Element

4 step over current


INPol Direction
operatingCurrent element
Element
3U0 One element for each
earthFaultDirection step
3I0
angleValid
I3PDIR
DirMode
enableDir

harmRestrBlock
3I0 Harmonic
Restraint 1
Element TRIP


start step 2, 3 and 4

Blocking at parallel
transformers
SwitchOnToFault
TRSOTF

CB
DirMode pos
or cmd
enableDir
Mode
Selection enableStep1-4

DirectionalMode1-4

IEC06000376-4-en.vsdx
IEC06000376 V4 EN-US

Figure 272: Functional overview of EF4PTOC

9.4.8 Technical data IP11455-1 v1

M15223-1 v18

Table 271: EF4PTOC technical data


Function Range or value Accuracy
Operate current, step 1-4 (1-2500)% of IBase ±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir

Reset ratio > 95% at (10-2500)% of -


IBase
Relay characteristic angle (-180 to 180) degrees ±2.0 degrees
(RCA)
Operate current for directional release (1–100)% of IBase For RCA ±60 degrees:
±2.5% of Ir at I ≤ Ir
±2.5% of I at I > Ir

Independent time delay at 0 to 2 x Iset, (0.000-60.000) s ±0.2% or ±35 ms whichever is


step 1-4 greater

Minimum operate time for inverse curves, (0.000 - 60.000) s ±0.2% or ±35 ms whichever is
step 1-4 greater
Inverse time characteristics, see Table 16 curve types See Table 1150, Table 1151 and
1150, Table 1151 and Table 1152 Table 1152
Second harmonic blocking (5–100)% of fundamental ±2.0% of Ir

Minimum polarizing voltage (1–100)% of UBase ±0.5% of Ur

Minimum polarizing current (2-100)% of IBase ±1.0% of Ir

Real part of source Z used for current (0.50-1000.00) W/phase -


polarization
Table continues on next page

Line distance protection REL670 473


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

Function Range or value Accuracy


Imaginary part of source Z used for (0.50–3000.00) W/phase -
current polarization
*Operate time, start non-directional at 0 Min. = 15 ms -
to 2 x Iset Max. = 30 ms

*Reset time, start non-directional at 2 x Min. = 15 ms -


Iset to 0 Max. = 30 ms

*Operate time, start non-directional at 0 Min. = 5 ms -


to 10 x Iset Max. = 20 ms

*Reset time, start non-directional at 10 x Min. = 20 ms -


Iset to 0 Max. = 35 ms

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Impulse margin time 15 ms typically -


*Note: Operate time and reset time are only valid if harmonic blocking is turned off for a step.

9.5 Four step directional negative phase sequence


overcurrent protection NS4PTOC GUID-E8CF8AA2-AF54-4FD1-A379-3E55DCA2FA3A v1

9.5.1 Identification
GUID-E1720ADA-7F80-4F2C-82A1-EF2C9EF6A4B4 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Four step negative sequence NS4PTOC 46I2
overcurrent protection I2
4
alt
4
IEC10000053 V1 EN-US

9.5.2 Functionality GUID-485E9D36-0032-4559-9204-101539A32F47 v6

Four step directional negative phase sequence overcurrent protection (NS4PTOC) has an
inverse or definite time delay independent for each step separately.

All IEC and ANSI time delayed characteristics are available together with an optional user
defined characteristic.

The directional function is voltage polarized.

NS4PTOC can be set directional or non-directional independently for each of the steps.

NS4PTOC can be used as main protection for unsymmetrical fault; phase-phase short circuits,
phase-phase-earth short circuits and single phase earth faults.

NS4PTOC can also be used to provide a system backup for example, in the case of the primary
protection being out of service due to communication or voltage transformer circuit failure.

Directional operation can be combined together with corresponding communication logic in


permissive or blocking teleprotection scheme. The same logic as for directional zero sequence
current can be used. Current reversal and weak-end infeed functionality are available.

474 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

9.5.3 Function block GUID-8EDB8B12-0D86-4F6B-A1FB-F5D0C72AA545 v2

NS4PTOC
I3P* TRIP
I3PDIR* TR1
U3P* TR2
BLOCK TR3
BLKTR TR4
BLKST1 START
BLKST2 ST1
BLKST3 ST2
BLKST4 ST3
ENMULT1 ST4
ENMULT2 STFW
ENMULT3 STRV
ENMULT4

IEC10000054-2-en.vsd
IEC10000054 V2 EN-US

Figure 273: NS4PTOC function block

9.5.4 Signals
PID-4151-INPUTSIGNALS v4

Table 272: NS4PTOC Input signals


Name Type Default Description
I3P GROUP - Group connection for operate current
SIGNAL
I3PDIR GROUP - Group connection for directional current
SIGNAL
U3P GROUP - Group connection for polarizing voltage
SIGNAL
BLOCK BOOLEAN 0 General block
BLKTR BOOLEAN 0 Block of trip
BLKST1 BOOLEAN 0 Block of step 1 (Start and trip)
BLKST2 BOOLEAN 0 Block of step 2 (Start and trip)
BLKST3 BOOLEAN 0 Block of step 3 (Start and trip)
BLKST4 BOOLEAN 0 Block of step 4 (Start and trip)
ENMULT1 BOOLEAN 0 When activated, the current multiplier is in use for step1
ENMULT2 BOOLEAN 0 When activated, the current multiplier is in use for step2
ENMULT3 BOOLEAN 0 When activated, the current multiplier is in use for step3
ENMULT4 BOOLEAN 0 When activated, the current multiplier is in use for step4

PID-4151-OUTPUTSIGNALS v4

Table 273: NS4PTOC Output signals


Name Type Description
TRIP BOOLEAN General trip signal
TR1 BOOLEAN Trip signal from step 1
TR2 BOOLEAN Trip signal from step 2
TR3 BOOLEAN Trip signal from step 3
TR4 BOOLEAN Trip signal from step 4
START BOOLEAN General start signal
ST1 BOOLEAN Start signal step 1
Table continues on next page

Line distance protection REL670 475


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

Name Type Description


ST2 BOOLEAN Start signal step 2
ST3 BOOLEAN Start signal step 3
ST4 BOOLEAN Start signal step 4
STFW BOOLEAN Forward directional start signal
STRV BOOLEAN Reverse directional start signal

9.5.5 Settings
PID-4151-SETTINGS v4

Table 274: NS4PTOC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
EnDir Disable - - Enable Enabling the Directional calculation
Enable
AngleRCA -180 - 180 Deg 1 65 Relay characteristic angle (RCA)
UPolMin 1 - 100 %UB 1 5 Minimum voltage level for polarization
in % of UBase
I2>Dir 1 - 100 %IB 1 10 Residual current level in % of IBase for
Direction release
DirMode1 Off - - Non-directional Directional mode of step 1 (off, nodir,
Non-directional forward, reverse)
Forward
Reverse
Characterist1 ANSI Ext. inv. - - ANSI Def. Time Time delay characteristic for step 1
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
I2-1> 1 - 2500 %IB 1 100 Negative sequence current op level for
step 1 in % of IBase
t1 0.000 - 60.000 s 0.001 0.000 Time delay of step 1 when definite
time char. is selected
k1 0.05 - 999.00 - 0.01 0.05 Time multiplier for the step 1 selected
time characteristic
IMin1 1.00 - 10000.00 %IB 1.00 100.00 Minimum current for step 1
t1Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse
time characteristic step 1
I1Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for scaling the current
setting value for step 1
Table continues on next page

476 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

Name Values (Range) Unit Step Default Description


DirMode2 Off - - Non-directional Directional mode of step 2 (off, nodir,
Non-directional forward, reverse)
Forward
Reverse
Characterist2 ANSI Ext. inv. - - ANSI Def. Time Time delay characteristic for step 2
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
I2-2> 1 - 2500 %IB 1 50 Negative sequence current op level for
step 2 in % of IBase
t2 0.000 - 60.000 s 0.001 0.400 Time delay of step 2 when definite
time char. is selected
k2 0.05 - 999.00 - 0.01 0.05 Time multiplier for the step 2 selected
time characteristic
IMin2 1.00 - 10000.00 %IB 1.00 50 Minimum current for step 2
t2Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse
time characteristic step 2
I2Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for scaling the current
setting value for step 2
DirMode3 Off - - Non-directional Directional mode of step 3 (off, nodir,
Non-directional forward, reverse)
Forward
Reverse
Characterist3 ANSI Ext. inv. - - ANSI Def. Time Time delay characteristic for step 3
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
I2-3> 1 - 2500 %IB 1 33 Negative sequence current op level for
step 3 in % of IBase
t3 0.000 - 60.000 s 0.001 0.800 Time delay of step 3 when definite
time char. is selected
Table continues on next page

Line distance protection REL670 477


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

Name Values (Range) Unit Step Default Description


k3 0.05 - 999.00 - 0.01 0.05 Time multiplier for the step 3 selected
time characteristic
IMin3 1.00 - 10000.00 %IB 1.00 33 Minimum current for step 3
t3Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse
time characteristic step 3
I3Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for scaling the current
setting value for step 3
DirMode4 Off - - Non-directional Directional mode of step 4 (off, nodir,
Non-directional forward, reverse)
Forward
Reverse
Characterist4 ANSI Ext. inv. - - ANSI Def. Time Time delay characteristic for step 4
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
I2-4> 1 - 2500 %IB 1 17 Negative sequence current op level for
step 4 in % of IBase
t4 0.000 - 60.000 s 0.001 1.200 Time delay of step 4 when definite
time char. is selected
k4 0.05 - 999.00 - 0.01 0.05 Time multiplier for the step 4 selected
time characteristic
IMin4 1.00 - 10000.00 %IB 1.00 17 Minimum current for step 4
t4Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse
time characteristic step 4
I4Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for scaling the current
setting value for step 4

Table 275: NS4PTOC Group settings (advanced)


Name Values (Range) Unit Step Default Description
ResetTypeCrv1 Instantaneous - - Instantaneous Reset curve type for step1
IEC Reset (Instantaneous / IEC / ANSI)
ANSI reset
tReset1 0.000 - 60.000 s 0.001 0.020 Reset time delay for step 1
tPCrv1 0.005 - 3.000 - 0.001 1.000 Param P for customized inverse trip
time curve for step 1
tACrv1 0.005 - 200.000 - 0.001 13.500 Param A for customized inverse trip
time curve for step 1
tBCrv1 0.00 - 20.00 - 0.01 0.00 Param B for customized inverse trip
time curve for step 1
Table continues on next page

478 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

Name Values (Range) Unit Step Default Description


tCCrv1 0.1 - 10.0 - 0.1 1.0 Param C for customized inverse trip
time curve for step 1
tPRCrv1 0.005 - 3.000 - 0.001 0.500 Param PR for customized inverse reset
time curve for step 1
tTRCrv1 0.005 - 100.000 - 0.001 13.500 Param TR for customized inverse reset
time curve for step
tCRCrv1 0.1 - 10.0 - 0.1 1.0 Param CR for customized inverse
reset time curve for step 1
ResetTypeCrv2 Instantaneous - - Instantaneous Reset curve type for step2
IEC Reset (Instantaneous / IEC / ANSI)
ANSI reset
tReset2 0.000 - 60.000 s 0.001 0.020 Reset time delay for step 2
tPCrv2 0.005 - 3.000 - 0.001 1.000 Param P for customized inverse trip
time curve for step 2
tACrv2 0.005 - 200.000 - 0.001 13.500 Param A for customized inverse trip
time curve for step 2
tBCrv2 0.00 - 20.00 - 0.01 0.00 Param B for customized inverse trip
time curve for step 2
tCCrv2 0.1 - 10.0 - 0.1 1.0 Param C for customized inverse trip
time curve for step 2
tPRCrv2 0.005 - 3.000 - 0.001 0.500 Param PR for customized inverse reset
time curve for step 2
tTRCrv2 0.005 - 100.000 - 0.001 13.500 Param TR for customized inverse reset
time curve for step 2
tCRCrv2 0.1 - 10.0 - 0.1 1.0 Param C for customized inverse reset
time curve for step 2
ResetTypeCrv3 Instantaneous - - Instantaneous Reset curve type for step3
IEC Reset (Instantaneous / IEC / ANSI)
ANSI reset
tReset3 0.000 - 60.000 s 0.001 0.020 Reset time delay for step 3
tPCrv3 0.005 - 3.000 - 0.001 1.000 Param P for customized inverse trip
time curve for step 3
tACrv3 0.005 - 200.000 - 0.001 13.500 Param A for customized inverse trip
time curve for step 3
tBCrv3 0.00 - 20.00 - 0.01 0.00 Param B for customized inverse trip
time curve for step 3
tCCrv3 0.1 - 10.0 - 0.1 1.0 Param C for customized inverse trip
time curve for step 3
tPRCrv3 0.005 - 3.000 - 0.001 0.500 Param PR for customized inverse reset
time curve for step 3
tTRCrv3 0.005 - 100.000 - 0.001 13.500 Param TR for customized inverse reset
time curve for step 3
tCRCrv3 0.1 - 10.0 - 0.1 1.0 Param CR for customized inverse
reset time curve for step 3
ResetTypeCrv4 Instantaneous - - Instantaneous Reset curve type for step4
IEC Reset (Instantaneous / IEC / ANSI)
ANSI reset
tReset4 0.000 - 60.000 s 0.001 0.020 Reset time delay for step 4
tPCrv4 0.005 - 3.000 - 0.001 1.000 Param P for customized inverse trip
time curve for step 4
tACrv4 0.005 - 200.000 - 0.001 13.500 Param A for customized inverse trip
time curve for step 4
Table continues on next page

Line distance protection REL670 479


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

Name Values (Range) Unit Step Default Description


tBCrv4 0.00 - 20.00 - 0.01 0.00 Param B for customized inverse trip
time curve for step 4
tCCrv4 0.1 - 10.0 - 0.1 1.0 Param C for customized inverse trip
time curve for step 4
tPRCrv4 0.005 - 3.000 - 0.001 0.500 Param PR for customized inverse reset
time curve for step 4
tTRCrv4 0.005 - 100.000 - 0.001 13.500 Param TR for customized inverse reset
time curve for step 4
tCRCrv4 0.1 - 10.0 - 0.1 1.0 Param CR for customized inverse
reset time curve for step 4

Table 276: NS4PTOC Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

9.5.6 Monitored data


PID-4151-MONITOREDDATA v4

Table 277: NS4PTOC Monitored data


Name Type Values (Range) Unit Description
IOp REAL - A Operating current level
UPol REAL - kV Polarizing voltage level
UPOLIANG REAL - deg Polarizing angle between voltage and
current

9.5.7 Operation principle GUID-8923EC0B-A5BA-431B-9699-EB67E2637560 v3

Four step negative sequence overcurrent protection NS4PTOC function has the following
three “Analog Inputs” on its function block in the configuration tool:

1. I3P, input used for “Operating Quantity”.


2. U3P, input used for “Polarizing Quantity”.
3. I3PDIR, input used for "Directional finding"

These inputs are connected from the corresponding pre-processing function blocks in the
Configuration Tool within PCM600.

9.5.7.1 Operating quantity within the function GUID-8F0A5BDE-AC98-4188-9085-42A8DF00C476 v3

Four step negative sequence overcurrent protection NS4PTOC function always uses negative
sequence current (I2) for its operating quantity. The negative sequence current is calculated
from three-phase current input within the IED. The pre-processing block calculates I2 from the
first three inputs into the pre-processing block by using the following formula:

1
I2 =
3
(
× IL1 + a × IL 2 + a × IL 3
2
)
EQUATION2266 V2 EN-US (Equation 116)

480 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

where:
IL1, IL2 and IL3 are fundamental frequency phasors of three individual phase currents.
a is so called operator which gives a phase shift of 120 deg, that is, a = 1∠120
deg

a2 similarly gives a phase shift of 240 deg, that is, a2 = 1∠240 deg

The phasor magnitude is used within the NS4PTOC protection to compare it with the set
operation current value of the four steps (I1>, I2>, I3> or I4>). If the negative sequence current
is larger than the set operation current and the step is used in non-directional mode a signal
from the comparator for this step is set to true. This signal, without delay, activates the
output signal STx (x=1 - 4) for this step and a common START signal.

9.5.7.2 Internal polarizing facility of the function GUID-B00FE98B-F269-4F1B-AC03-68250798851B v3

A polarizing quantity is used within the protection to determine the direction to the fault
(Forward/Reverse).

Four step negative sequence overcurrent protection NS4PTOC function uses the voltage
polarizing method.

NS4PTOC uses the negative sequence voltage -U2 as polarizing quantity U3P. This voltage is
calculated from three phase voltage input within the IED. The pre-processing block calculates -
U2 from the first three inputs into the pre-processing block by using the following formula:

1
UPol = -U 2 = - × (UL1 + a 2 × UL 2 + a × UL3 )
3
EQUATION2267 V2 EN-US

where:
UL1, UL2 and UL3 are fundamental frequency phasors of three individual phase voltages.

To use this all three phase-to-earth voltages must be connected to three IED VT
inputs.

This phasor is used together with the phasor of the operating current, in order to determine
the direction to the fault (Forward/Reverse).To enable voltage polarizing the magnitude of
polarizing voltage must be bigger than a minimum level defined by setting UpolMin.

Note that –U2 is used to determine the location of the fault. This ensures the required
inversion of the polarizing voltage within the function.

9.5.7.3 External polarizing for negative sequence function GUID-21930E81-1B40-4BA4-B1D8-3B365327AEF6 v1

The individual steps within the protection can be set as non-directional. When this setting is
selected it is then possible via function binary input BLKSTx (where x indicates the relevant
step within the protection) to provide external directional control (that is, torque control) by
for example using one of the following functions if available in the IED:

Line distance protection REL670 481


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

• Distance protection directional function


• Negative sequence polarized general current and voltage multi purpose protection
function

9.5.7.4 Internal negative sequence protection structure GUID-A6B9B3F1-A1FE-4653-A8AF-61FCCF19CE95 v1

The protection is internally divided into the following parts:

• Four negative sequence overcurrent steps


• Directional supervision element for negative sequence overcurrent steps with integrated
directional comparison step for communication based negative sequence protection
schemes (permissive or blocking)

Each part is described separately in the following sections.

9.5.7.5 Four negative sequence overcurrent stages GUID-D8ACB136-2BA6-4ADA-A096-5C38BD12DB72 v2

Each overcurrent stage uses Operating Quantity I2 (negative sequence current) as measuring
quantity. Every of the four overcurrent stage has the following built-in facilities:

• Operating mode (Off/ Non-directional /Forward / Reverse). By this parameter setting the
operating mode of the stage is selected. Note that the directional decision (Forward/
Reverse) is not made within the overcurrent stage itself. The direction of the fault is
determined in common “Directional Supervision Element” described in the next
paragraph.
• Negative sequence current pickup value.
• Type of operating characteristic (Inverse or Definite Time). By this parameter setting it is
possible to select Inverse or definite time delay for negative sequence overcurrent
function. Most of the standard IEC and ANSI inverse characteristics are available. For the
complete list of available inverse curves, refer to Chapter "Inverse characteristics"
• Type of reset characteristic (Instantaneous / IEC Reset /ANSI reset).By this parameter
setting it is possible to select the reset characteristic of the stage. For the complete list of
available reset curves, refer to Chapter "Inverse characteristics"
• Time delay related settings. By these parameter settings the properties like definite time
delay, minimum operating time for inverse curves, reset time delay and parameters to
define user programmable inverse curve are defined.
• Multiplier for scaling of the set negative sequence current pickup value by external binary
signal. By this parameter setting it is possible to increase negative sequence current
pickup value when function binary input ENMULTx has logical value 1.

Simplified logic diagram for one negative sequence overcurrent stage is shown in the
following figure:

482 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

BLKTR

Characteristx=DefTime AND
TRx
|IOP| AND
tx
a OR
a>b
ENMULTx b

STx
IxMult AND
X T
Ix> F
txmin
BLKSTx AND
BLOCK
Inverse

Characteristx=Inverse

DirModex=Off OR STAGEx_DIR_Int
DirModex=Non-directional
DirModex=Forward
AND OR
FORWARD_Int
DirModex=Reverse

AND
REVERSE_Int

IEC09000683.vsd
IEC09000683 V3 EN-US

Figure 274: Simplified logic diagram for negative sequence overcurrent stage x , where x=1, 2, 3 or 4
NS4PTOC can be completely blocked from the binary input BLOCK. The start signals from
NS4PTOC for each stage can be blocked from the binary input BLKSTx. The trip signals from
NS4PTOC can be blocked from the binary input BLKTR.

9.5.7.6 Directional supervision element with integrated directional comparison


function GUID-F54E21F7-7C99-41D6-BEC6-2D6EC6D2B2A3 v3

At least one of the four negative sequence overcurrent steps must be set as
directional in order to enable execution of the directional supervision element
and the integrated directional comparison function.

The operating and polarizing quantity are then used inside the directional element, as shown
in figure 275, to determine the direction of the fault.

Line distance protection REL670 483


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

Reverse
Area

AngleRCA Upol=-U2

Forward
Area
Iop = I2

IEC10000031-1-en.vsd
IEC10000031 V1 EN-US

Figure 275: Operating characteristic for fault directional element

Two relevant setting parameters for directional supervision element are:

• Directional element is internally enable to operate as soon as Iop is bigger than 40% of
I>Dir and the directional condition is fulfilled in set direction.
• Relay characteristic angle AngleRCA which defines the position of forward and reverse
areas in the operating characteristic.

Directional comparison step, built-in within directional supervision element, set NS4PTOC
output binary signals:

1. STFW=1 when tip of I2 phasor (operating quantity magnitude) is in forward area, see fig
275 (Operating quantity magnitude is bigger than setting I>Dir)
2. STRV=1 when tip of I2 phasor (operating quantity magnitude) is in the reverse area, see fig
275. (Operating quantity magnitude is bigger than 60% of setting I>Dir)

These signals must be used for communication based fault teleprotection communication
schemes (permissive or blocking).

Simplified logic diagram for directional supervision element with integrated directional
comparison step is shown in figure 276:

484 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

|Iop|
a a>
STRV
b b REVERSE_Int
AND
0.6
X
a a>
STFW
I>Dir b b FORWARD_Int
AND

X
0.4

FWD
AND FORWARD_Int
AngleRCA

C h a r a c e ri s ti c
D i r e c ti o n a l
UPolMin

IPolMin

t
Iop

UPol
AND REVERSE_Int
RVS

STAGE1_DIR_Int
STAGE2_DIR_Int
STAGE3_DIR_Int OR
STAGE4_DIR_Int
BLOCK AND

IEC07000067-4.vsd

IEC07000067-4 V2 EN-US

Figure 276: Simplified logic diagram for directional supervision element with integrated directional
comparison step

9.5.8 Technical data GUID-10E9194D-3AE9-4D0F-867E-473E6F4BF443 v1

GUID-E83AD807-8FE0-4244-A50E-86B9AF92469E v6

Table 278: NS4PTOC technical data


Function Range or value Accuracy
Operate current, step 1 - 4 (1-2500)% of lBase ±1.0% of Ir at I £ Ir
±1.0% of I at I > Ir

Reset ratio > 95% at (10-2500)% of -


IBase
Independent time delay at 0 to 2 x Iset, (0.000-60.000) s ±0.2% or ±35 ms whichever is
step 1 - 4 greater

Minimum operate time for inverse (0.000 - 60.000) s ±0.2% or ±35 ms whichever is
curves, step 1 - 4 greater
Inverse time characteristics, see table 16 curve types See table 1150, table 1151 and table
1150, table 1151 and table 1152 1152
Minimum operate current, step 1 - 4 (1.00 - 10000.00)% of IBase ±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir

Relay characteristic angle (RCA) (-180 to 180) degrees ±2.0 degrees


Table continues on next page

Line distance protection REL670 485


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

Function Range or value Accuracy


Operate current for directional release (1–100)% of IBase For RCA ±60 degrees:
±2.5% of Ir at I ≤ Ir
±2.5% of I at I > Ir

Minimum polarizing voltage (1–100)% of UBase ±0.5% of Ur

Real part of negative sequence source (0.50-1000.00) W/phase -


impedance used for current
polarization
Imaginary part of negative sequence (0.50–3000.00) W/phase -
source impedance used for current
polarization
Operate time, start non-directional at Min. = 15 ms -
0 to 2 x Iset Max. = 30 ms

Reset time, start non-directional at 2 x Min. = 15 ms -


Iset to 0 Max. = 30 ms

Operate time, start non-directional at Min. = 5 ms -


0 to 10 x Iset Max. = 20 ms

Reset time, start non-directional at 10 Min. = 20 ms -


x Iset to 0 Max. = 35 ms

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Impulse margin time 15 ms typically -


Transient overreach <10% at τ = 100 ms -

9.6 Sensitive directional residual overcurrent and power


protection SDEPSDE SEMOD171436-1 v4

9.6.1 Identification
SEMOD172025-2 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Sensitive directional residual over SDEPSDE - 67N
current and power protection

9.6.2 Functionality SEMOD171959-4 v12

In networks with high impedance earthing, the phase-to-earth fault current is significantly
smaller than the short circuit currents. Another difficulty for earth fault protection is that the
magnitude of the phase-to-earth fault current is almost independent of the fault location in
the network.

Directional residual current can be used to detect and give selective trip of phase-to-earth
faults in high impedance earthed networks. The protection uses the residual current
component 3I0 · cos φ, where φ is the angle between the residual current and the residual
voltage (-3U0), compensated with a characteristic angle. Alternatively, the function can be set
to strict 3I0 level with a check of angle φ.

Directional residual power can also be used to detect and give selective trip of phase-to-earth
faults in high impedance earthed networks. The protection uses the residual power

486 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

component 3I0 · 3U0 · cos φ, where φ is the angle between the residual current and the
reference residual voltage, compensated with a characteristic angle.

A normal non-directional residual current function can also be used with definite or inverse
time delay.

A backup neutral point voltage function is also available for non-directional residual
overvoltage protection.

In an isolated network, that is, the network is only coupled to earth via the capacitances
between the phase conductors and earth, the residual current always has -90º phase shift
compared to the residual voltage (3U0). The characteristic angle is chosen to -90º in such a
network.

In resistance earthed networks or in Petersen coil earthed, with a parallel resistor, the active
residual current component (in phase with the residual voltage) should be used for the earth
fault detection. In such networks, the characteristic angle is chosen to 0º.

As the amplitude of the residual current is independent of the fault location, the selectivity of
the earth fault protection is achieved by time selectivity.

When should the sensitive directional residual overcurrent protection be used and when
should the sensitive directional residual power protection be used? Consider the following:

• Sensitive directional residual overcurrent protection gives possibility for better sensitivity.
The setting possibilities of this function are down to 0.25 % of IBase, 1 A or 5 A. This
sensitivity is in most cases sufficient in high impedance network applications, if the
measuring CT ratio is not too high.
• Sensitive directional residual power protection gives possibility to use inverse time
characteristics. This is applicable in large high impedance earthed networks, with large
capacitive earth fault currents. In such networks, the active fault current would be small
and by using sensitive directional residual power protection, the operating quantity is
elevated. Therefore, better possibility to detect earth faults. In addition, in low impedance
earthed networks, the inverse time characteristic gives better time-selectivity in case of
high zero-resistive fault currents.

Phase
currents
IN

Phase-
ground
voltages
UN

IEC13000013-1-en.vsd
IEC13000013 V1 EN-US

Figure 277: Connection of SDEPSDE to analog preprocessing function block

Overcurrent functionality uses true 3I0, i.e. sum of GRPxL1, GRPxL2 and GRPxL3. For 3I0 to be
calculated, connection is needed to all three phase inputs.

Line distance protection REL670 487


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

Directional and power functionality uses IN and UN. If a connection is made to GRPxN this
signal is used, else if connection is made to all inputs GRPxL1, GRPxL2 and GRPxL3 the
internally calculated sum of these inputs (3I0 and 3U0) will be used.

9.6.3 Function block SEMOD172780-4 v6

SDEPSDE
I3P* TRIP
U3P* TRDIRIN
BLOCK TRNDIN
BLKTR TRUN
BLKTRDIR START
BLKNDN STDIRIN
BLKUN STNDIN
STUN
STFW
STRV
STDIR
UNREL

IEC07000032-2-en.vsd
IEC07000032 V2 EN-US

Figure 278: SDEPSDE function block

9.6.4 Signals
PID-3892-INPUTSIGNALS v7

Table 279: SDEPSDE Input signals


Name Type Default Description
I3P GROUP - Group signal for current
SIGNAL
U3P GROUP - Group signal for voltage
SIGNAL
BLOCK BOOLEAN 0 Blocks all the outputs of the function
BLKTR BOOLEAN 0 Blocks the trip outputs of the function
BLKTRDIR BOOLEAN 0 Blocks the directional operate outputs of the function
BLKNDN BOOLEAN 0 Blocks the Non directional current residual outputs
BLKUN BOOLEAN 0 Blocks the Non directional voltage residual outputs

PID-3892-OUTPUTSIGNALS v7

Table 280: SDEPSDE Output signals


Name Type Description
TRIP BOOLEAN General trip of the function
TRDIRIN BOOLEAN Trip of the directional residual over current function
TRNDIN BOOLEAN Trip of non directional residual over current
TRUN BOOLEAN Trip of non directional residual over voltage
START BOOLEAN General start of the function
STDIRIN BOOLEAN Start of the directional residual over current function
STNDIN BOOLEAN Start of non directional residual over current
STUN BOOLEAN Start of non directional residual over voltage
STFW BOOLEAN Start of directional function for a fault in forward direction
Table continues on next page

488 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

Name Type Description


STRV BOOLEAN Start of directional function for a fault in reverse direction
STDIR INTEGER Direction of fault. A general signal common to all three mode
of residual over current protection
UNREL BOOLEAN Residual voltage release of operation of all directional modes

9.6.5 Settings
PID-3892-SETTINGS v7

Table 281: SDEPSDE Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
OpMode 3I0Cosfi - - 3I0Cosfi Selection of operation mode for
3I03U0Cosfi protection
3I0 and fi
DirMode Forward - - Forward Direction of operation forward or
Reverse reverse
RCADir -179 - 180 Deg 1 -90 Relay characteristic angle RCA, in deg
RCAComp -10.0 - 10.0 Deg 0.1 0.0 Relay characteristic angle
compensation
ROADir 0 - 90 Deg 1 90 Relay open angle ROA used as release
in phase mode, in deg
INCosPhi> 0.25 - 200.00 %IB 0.01 1.00 Set level for 3I0cosFi, directional res
over current in % of IBase
SN> 0.25 - 200.00 %SB 0.01 10.00 Set level for 3I03U0cosFi, starting inv
time count in % of SBase
INDir> 0.25 - 200.00 %IB 0.01 5.00 Set level for directional residual over
current prot in % of IBase
tDef 0.000 - 60.000 s 0.001 0.100 Definite time delay directional
residual overcurrent, in sec
SRef 0.03 - 200.00 %SB 0.01 10.00 Reference value of res power for
inverse time count in % of SBase
kSN 0.00 - 2.00 - 0.01 0.10 Time multiplier setting for directional
residual power mode
OpINNonDir> Off - - Off Operation of non-directional residual
On overcurrent protection
INNonDir> 1.00 - 400.00 %IB 0.01 10.00 Set level for non directional residual
over current in % of IBase
tINNonDir 0.000 - 60.000 s 0.001 1.000 Time delay for non-directional residual
over current, in sec
Table continues on next page

Line distance protection REL670 489


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

Name Values (Range) Unit Step Default Description


TimeChar ANSI Ext. inv. - - IEC Norm. inv. Operation curve selection for IDMT
ANSI Very inv. operation
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
tMin 0.000 - 60.000 s 0.001 0.040 Minimum operate time for IEC IDMT
curves, in sec
kIN 0.05 - 2.00 - 0.01 1.00 IDMT time mult for non-dir res over
current protection
OpUN> Off - - Off Operation of non-directional residual
On overvoltage protection
UN> 1.00 - 200.00 %UB 0.01 20.00 Set level for non-directional residual
over voltage in % of UBase
tUN 0.000 - 60.000 s 0.001 0.100 Time delay for non-directional residual
over voltage, in sec
INRel> 0.25 - 200.00 %IB 0.01 1.00 Residual release current for all
directional modes in % of IBase
UNRel> 1.00 - 300.00 %UB 0.01 3.00 Residual release voltage for all
direction modes in % of UBase

Table 282: SDEPSDE Group settings (advanced)


Name Values (Range) Unit Step Default Description
tReset 0.000 - 60.000 s 0.001 0.040 Time delay used for reset of definite
timers, in sec
tPCrv 0.005 - 3.000 - 0.001 1.000 Setting P for customer programmable
curve
tACrv 0.005 - 200.000 - 0.001 13.500 Setting A for customer programmable
curve
tBCrv 0.00 - 20.00 - 0.01 0.00 Setting B for customer programmable
curve
tCCrv 0.1 - 10.0 - 0.1 1.0 Setting C for customer programmable
curve
ResetTypeCrv Immediate - - IEC Reset Reset mode when current drops off.
IEC Reset
ANSI reset
tPRCrv 0.005 - 3.000 - 0.001 0.500 Setting PR for customer
programmable curve
tTRCrv 0.005 - 100.000 - 0.001 13.500 Setting TR for customer
programmable curve
tCRCrv 0.1 - 10.0 - 0.1 1.0 Setting CR for customer
programmable curve

490 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

Table 283: SDEPSDE Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Global base selection for function
groups

Table 284: SDEPSDE Non group settings (advanced)


Name Values (Range) Unit Step Default Description
RotResU 0 deg - - 180 deg Setting for rotating polarizing
180 deg quantity if necessary

9.6.6 Monitored data


PID-3892-MONITOREDDATA v6

Table 285: SDEPSDE Monitored data


Name Type Values (Range) Unit Description
INCOSPHI REAL - A Magnitude of residual current along
the polarizing quantity 3I0cos(Fi-RCA)
IN REAL - A Measured magnitude of the residual
current 3I0
UN REAL - kV Measured magnitude of the residual
voltage 3U0
SN REAL - MVA Measured magnitude of residual
power 3I03U0cos(Fi-RCA)
ANG FI-RCA REAL - deg Angle between 3U0 and 3I0 minus RCA
(Fi-RCA)

9.6.7 Operation principle

9.6.7.1 Function inputs SEMOD171963-4 v5

The function is using phasors of the residual current and voltage. Group signals I3P and U3P
containing phasors of residual current and voltage which are taken from pre-processor blocks.

The sensitive directional earth fault protection has the following sub-functions included:

Directional residual current protection measuring 3I0·cos φ


SEMOD171963-8 v7
φ is defined as the angle between the residual current 3I0 and the reference voltage (|
φ=ang(3I0)-ang(Uref)|). The reference voltage (Uref) is the polarizing quantity which is used for
directionality and is defined as Uref = -3U0 e—jRCADir, that is -3U0 inversely rotated by the set
characteristic angle RCADir. RCADir is normally set equal to 0 in a high impedance earthed
network with a neutral point resistor as the active current component is appearing out on the
faulted feeder only. RCADir is set equal to -90° in an isolated network as all currents are mainly
capacitive. The function operates when 3I0·cos φ gets larger than the set value.

Line distance protection REL670 491


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

RCADir = 0o,ROADir = 90o

3I0

j = ang(3I0 ) - ang(3Uref )
-3U0 = Uref
3I0 × cosj

IEC06000648-4-en.vsd
IEC06000648 V4 EN-US

Figure 279: RCADir set to 0°

Uref
RCADir = −90 , ROADir = 90

3I0

3I0 ⋅ cos ϕ

ϕ = ang (3I0 ) − ang (Uref )

−3U0

IEC06000649_3_en.vsd
IEC06000649 V3 EN-US

Figure 280: RCADir set to -90°


For trip, the operating quantity 3I0 cos φ, the residual current 3I0, and the residual voltage 3U0
must be larger than the set levels : INCosPhi>, INRel> and UNRel>. Refer to the simplified
logical diagram in Figure 284.

Trip from this function can be blocked from the binary input BLKTRDIR.

When the function picks up, binary output signals START and STDIRIN are activated. If the
output signals START and STDIRIN remain active for the set delay tDef the binary output
signals TRIP and TRDIRIN get activated. The trip from this sub-function has definite time delay.

ROADir is Relay Operating Angle. ROADir is identifying a window around the reference
direction in order to detect directionality. Figure 281 shows the restrictions made by the
ROADir.

492 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

RCADir = 0o

3I0
Operate area

j
-3U0 = Uref
3I0 × cos j

ROADir

IEC06000650_2_en.vsd
IEC06000650 V2 EN-US

Figure 281: Characteristic with ROADir restriction


The function indicates forward/reverse direction to the fault. Reverse direction is defined as
3I0·cos (φ + 180°) ≥ the set value.

It is also possible to tilt the characteristic to compensate for current transformer angle error
with a setting RCAComp as shown in the Figure 282:

Line distance protection REL670 493


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

RCADir = 0º

Operate area

-3U0 =Uref

Instrument
transformer
angle error 
RCAcomp
Characteristic after
angle compensation

3I0 (prim) 3I0 (to prot)

IEC06000651-3-en.vsd

IEC06000651 V3 EN-US

Figure 282: Explanation of RCAComp

Directional residual power protection measuring 3I0 · 3U0 · cos φ


SEMOD171963-32 v6
φ is defined as the angle between the residual current 3I0 and the reference voltage (Uref = -3U0
e-jRCA) compensated with the set characteristic angle RCADir (|φ=ang(3I0)—ang(Uref)|). The
function operates when 3I0 · 3U0 · cos φ gets larger than the set value SN>. Refer to the
simplified logical diagram in Figure 284.

For trip, the residual power 3I0 · 3U0 · cos φ, the residual current 3I0 and the release voltage
3U0, shall be larger than the set levels (SN>, INRel> and UNRel>).

Trip from this function can be blocked from the binary input BLKTRDIR.

When the function picks up, binary output signals START and STDIRIN are activated. If the
output signals START and STDIRIN remain active for the set delay tDef or after the inverse time
delay (setting kSN) the binary output signals TRIP and TRDIRIN get activated.

The function shall indicate forward/reverse direction to the fault. Reverse direction is defined
as 3I0 · 3U0·cos (φ + 180°) ³ the set value.

This variant has the possibility of choice between definite time delay and inverse time delay.

The inverse time delay is defined as:

kSN × (3I0 × 3U 0 × cos j(reference))


t inv =
3I0 × 3U 0 × cos j(measured)
EQUATION1942 V2 EN-US (Equation 117)

494 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

Directional residual current protection measuring 3I0 and φ


SEMOD171963-48 v4
The function will operate if the residual current is larger than the set value and the angle |φ =
ang(3I0)-ang(Uref)| is within the sector RCADir ± ROADir

RCADir = 0º

ROADir = 80º

Operate area

3I0

-3U0

IEC06000652-3-en.vsd
IEC06000652 V3 EN-US

Figure 283: Example of characteristic


For trip, Residual current 3I0 shall be larger than both INRel> and INDir>, and residual voltage
3U0 shall be larger than the UNRel>. In addition, the angle φ shall be in the set area defined by
ROADir and RCADir. Refer to the simplified logical diagram in Figure 284.

Trip from this function can be blocked from the binary input BLKTRDIR.

When the function picks up, binary output signals START and STDIRIN are activated. If the
output signals START and STDIRIN remain active for the set delay tDef the binary output
signals TRIP and TRDIRIN get activated.

The function indicates forward/reverse direction to the fault. Reverse direction is defined as φ
is within the angle sector: RCADir + 180° ± ROADir

This variant has definite time delay.

Directional functions SEMOD171963-60 v4


For all the directional functions there are directional start signals STFW: fault in the forward
direction, and STRV: fault in the reverse direction. Even if the directional function is set to
operate for faults in the forward direction, a fault in the reverse direction will give the start
signal STRV. Also if the directional function is set to operate for faults in the reverse direction,
a fault in the forward direction will give the start signal STFW.

Non-directional earth fault current protection SEMOD171963-63 v6


This function will measure the residual current without checking the phase angle. The function
will be used to detect cross-country faults. This function can serve as alternative or backup to
distance protection with phase preference logic. To assure selectivity the distance protection
can block the non-directional earth fault current function via the input BLKNDN.

The non-directional function is using the calculated residual current, derived as sum of the
phase currents. This will give a better ability to detect cross-country faults with high residual

Line distance protection REL670 495


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

current, also when dedicated core balance CT for the sensitive earth fault protection will
saturate.

This variant has the possibility of choice between definite time delay and inverse time delay
(TimeChar parameter). The inverse time delay shall be according to IEC 60255-3.

For trip, the residual current 3I0 shall be larger than the set level (INNonDir>).

Trip from this function can be blocked from the binary input BLKNDN.

When the function picks up, binary output signal STNDIN is activated. If the output signal
STNDIN remains active for the set delay tINNonDir or after the inverse time delay the binary
output signals TRIP and TRNDIN get activated.

Residual overvoltage release and protection SEMOD171963-72 v8


All the directional functions shall be released when the residual voltage gets higher than a set
level UNRel>.

In addition, there is also a separate non-directional residual over voltage protection, with its
own definite time delay tUN and set level UN>.

For trip, the residual voltage 3U0 shall be larger than the set level (UN>).

Trip from this function can be blocked from the binary input BLKUN.

When the function picks up, binary output signal STUN is activated. If the output signal STUN
is active for the set delay tUNNonDir, the binary output signals TRIP and TRUN get activated. A
simplified logical diagram of the total function is shown in Figure 284.

496 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

OpINNonDir> = On
STNDIN
&
INNonDir>
t
TRNDIN
TimeChar IN
OpUN> = On
STUN
&
UN>
tUN TRUN
t

OpMode = 3I0Cosfi
INRel>

UNRel> & &


tDef
INCosPhi> t

OpMode = 3I0 and fi


& ³ STDIRIN
INDir> &
1

tDef ³ TRDIRIN
t 1
OpMode = 3I03U0Cosfi
& &
SN>
t
³ S
1 N
STFW
RCADir Direction &
Detection
RCAComp Logic STRV
&
ROADir

DirMode = Forward

DirMode = Reverse
IEC06000653.vsd

IEC06000653 V4 EN-US

Figure 284: Simplified logical diagram of the sensitive earth fault current protection

9.6.8 Technical data SEMOD173352-1 v1

SEMOD173350-2 v16

Table 286: SDEPSDE technical data


Function Range or value Accuracy
Operate level for 3I0·cosj directional (0.25-200.00)% of IBase ±1.0% of Ir at I £ Ir
residual overcurrent ±1.0% of I at I > Ir

Operate level for ·3I0·3U0 cosj directional (0.25-200.00)% of SBase ±1.0% of Sr at S £ Sr


residual power ±1.0% of S at S > Sr

Operate level for 3I0 and j residual (0.25-200.00)% of IBase ±1.0% of Ir at £ Ir


overcurrent ±1.0% of I at I > Ir

Operate level for non-directional (1.00-400.00)% of IBase ±1.0% of Ir at I £ Ir


overcurrent ±1.0% of I at I > Ir

Operate level for non-directional residual (1.00-200.00)% of UBase ±0.5% of Ur at U £ Ur


overvoltage ±0.5% of U at U > Ur

Table continues on next page

Line distance protection REL670 497


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

Function Range or value Accuracy


Residual release current for all directional (0.25-200.00)% of IBase ±1.0% of Ir at I £ Ir
modes ±1.0% of I at I > Ir

Residual release voltage for all directional (1.00-300.00)% of UBase ±0.5% of Ur at U £ Ur


modes ±0.5% of U at U > Ur

Operate time for non-directional residual Min. = 40 ms


overcurrent at 0 to 2 x Iset
Max. = 65 ms
Reset time for non-directional residual Min. = 40 ms
overcurrent at 2 x Iset to 0
Max. = 65 ms
Operate time for directional residual Min. = 110 ms
overcurrent at 0 to 2 x Iset
Max. = 160 ms
Reset time for directional residual Min. = 20 ms
overcurrent at 2 x Iset to 0
Max. = 60 ms
Independent time delay for non- (0.000 – 60.000) s ±0.2% or ± 75 ms whichever is
directional residual overvoltage at 0.8 x greater
Uset to 1.2 x Uset

Independent time delay for non- (0.000 – 60.000) s ±0.2% or ± 75 ms whichever is


directional residual overcurrent at 0 to 2 x greater
Iset

Independent time delay for directional (0.000 – 60.000) s ±0.2% or ± 170 ms whichever is
residual overcurrent at 0 to 2 x Iset greater

Inverse characteristics, see table 1153, 16 curve types See Table 1153, Table 1154 and Table
Table 1154 and Table 1155 1155
Relay characteristic angle (RCADir) (-179 to 180) degrees ±2.0 degrees
Relay operate angle (ROADir) (0 to 90) degrees ±2.0 degrees

9.7 Thermal overload protection, one time constant,


Celsius/Fahrenheit LCPTTR/LFPTTR IP14512-1 v7

9.7.1 Identification
M17106-1 v7

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Thermal overload protection, one LCPTTR 26
time constant, Celsius

Thermal overload protection, one LFPTTR 26


time constant, Fahrenheit

9.7.2 Functionality M12020-4 v14

The increasing utilization of the power system closer to the thermal limits has generated a
need of a thermal overload protection for power lines.

498 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

A thermal overload will often not be detected by other protection functions and the
introduction of the thermal overload protection can allow the protected circuit to operate
closer to the thermal limits.

The three-phase current measuring protection has an I2t characteristic with settable time
constant and a thermal memory. The temperature is displayed in either Celsius or Fahrenheit,
depending on whether the function used is Thermal overload protection (LCPTTR) (Celsius) or
(LFPTTR) (Fahrenheit).

An alarm level gives early warning to allow operators to take action well before the line is
tripped.

Estimated time to trip before operation, and estimated time to reclose after operation are
presented.

9.7.3 Function block M12627-3 v8

LCPTTR
I3P* TRIP
BLOCK START
BLKTR ALARM
ENMULT LOCKOUT
AMBTEMP
SENSFLT
RESET

IEC13000199-1-en.vsd
IEC13000199 V1 EN-US
LFPTTR
I3P* TRIP
BLOCK START
BLKTR ALARM
ENMULT LOCKOUT
AMBTEMP
SENSFLT
RESET

IEC13000301-1-en.vsd
IEC13000301 V1 EN-US

Figure 285: LCPTTR/LFPTTR function bloc

9.7.4 Signals
PID-3908-INPUTSIGNALS v7

Table 287: LCPTTR Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Block of trip
ENMULT BOOLEAN 0 Current multiplyer used when THOL is for two or more lines
AMBTEMP REAL 0 Ambient temperature from external temperature sensor
SENSFLT BOOLEAN 0 Validity status of ambient temperature sensor
RESET BOOLEAN 0 Reset of internal thermal load counter

Line distance protection REL670 499


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

PID-3909-INPUTSIGNALS v9

Table 288: LFPTTR Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Block of trip
ENMULT BOOLEAN 0 Current multiplyer used when THOL is for two or more lines
AMBTEMP REAL 0 Ambient temperature from external temperature sensor
SENSFLT BOOLEAN 0 Validity status of ambient temperature sensor
RESET BOOLEAN 0 Reset of internal thermal load counter

PID-3908-OUTPUTSIGNALS v7

Table 289: LCPTTR Output signals


Name Type Description
TRIP BOOLEAN Trip
START BOOLEAN Start Signal
ALARM BOOLEAN Alarm signal
LOCKOUT BOOLEAN Lockout signal

PID-3909-OUTPUTSIGNALS v8

Table 290: LFPTTR Output signals


Name Type Description
TRIP BOOLEAN Trip
START BOOLEAN Start Signal
ALARM BOOLEAN Alarm signal
LOCKOUT BOOLEAN Lockout signal

9.7.5 Settings
PID-3908-SETTINGS v7

Table 291: LCPTTR Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
TRef 0 - 300 Deg C 1 90 End temperature rise above ambient
of the line when loaded with IRef
IRef 0 - 400 %IB 1 100 The load current (in % of IBase)
leading to TRef temperature
IMult 1-5 - 1 1 Current multiplier when function is
used for two or more lines
Tau 1 - 1000 Min 1 45 Time constant of the line in minutes.
AlarmTemp 0 - 200 Deg C 1 80 Temperature level for start (alarm)
TripTemp 0 - 300 Deg C 1 90 Temperature level for trip
Table continues on next page

500 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

Name Values (Range) Unit Step Default Description


ReclTemp 0 - 300 Deg C 1 75 Temperature for reset of lockout after
trip
tPulse 0.05 - 0.30 s 0.01 0.10 Operate pulse length. Minimum one
execution cycle
AmbiSens Off - - Off External temperature sensor available
On
DefaultAmbTemp -50 - 100 Deg C 1 20 Ambient temperature used when
AmbiSens is set to Off.
DefaultTemp -50 - 300 Deg C 1 50 Temperature raise above ambient
temperature at startup

Table 292: LCPTTR Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

PID-3909-SETTINGS v8

Table 293: LFPTTR Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
TRef 0 - 600 Deg F 1 160 End temperature rise above ambient
of the line when loaded with IRef
IRef 0 - 400 %IB 1 100 The load current (in % of IBase)
leading to TRef temperature
IMult 1-5 - 1 1 Current multiplier when function is
used for two or more lines
Tau 1 - 1000 Min 1 45 Time constant of the line in minutes.
AlarmTemp 0 - 400 Deg F 1 175 Temperature level for start (alarm)
TripTemp 0 - 600 Deg F 1 195 Temperature level for trip
ReclTemp 0 - 600 Deg F 1 170 Temperature for reset of lockout after
trip
tPulse 0.05 - 0.30 s 0.01 0.10 Operate pulse length. Minimum one
execution cycle
AmbiSens Off - - Off External temperature sensor available
On
DefaultAmbTemp -50 - 250 Deg F 1 60 Ambient temperature used when
AmbiSens is set to Off.
DefaultTemp -50 - 600 Deg F 1 100 Temperature raise above ambient
temperature at startup

Table 294: LFPTTR Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

Line distance protection REL670 501


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

9.7.6 Monitored data


PID-3908-MONITOREDDATA v7

Table 295: LCPTTR Monitored data


Name Type Values (Range) Unit Description
TTRIP INTEGER - - Estimated time to trip (in min)
TENRECL REAL - - Estimated time to reset of lockout (in
min)
TEMP REAL - deg Calculated temperature of the device
TEMPAMB REAL - deg Ambient temperature used in the
calculations
TERMLOAD REAL - - Temperature relative to operate
temperature

PID-3909-MONITOREDDATA v7

Table 296: LFPTTR Monitored data


Name Type Values (Range) Unit Description
TTRIP INTEGER - - Estimated time to trip (in min)
TENRECL REAL - - Estimated time to reset of lockout (in
min)
TEMP REAL - Temperatur Calculated temperature of the device
e
Fahrenheit
TEMPAMB REAL - Temperatur Ambient temperature used in the
e calculations
Fahrenheit
TERMLOAD REAL - - Temperature relative to operate
temperature

9.7.7 Operation principle M12018-3 v11

The sampled analog phase currents are pre-processed and for each phase current the RMS
value is derived. These phase current values are fed to the thermal overload protection, one
time constant LCPTTR/LFPTTR function. The temperature is displayed either in Celsius or
Fahrenheit, depending on whether LCPTTR/LFPTTR function is selected.

From the largest of the three-phase currents a final temperature is calculated according to the
expression:

2
æ I ö
Q final =ç ÷÷ × Tref
ç I ref
è ø
EQUATION1167 V1 EN-US (Equation 118)

where:
I is the largest phase current,
Iref is a given reference current and

Tref is steady state temperature rise corresponding to Iref

502 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

The ambient temperature is added to the calculated final temperature. If this temperature is
larger than the set operate temperature level, TripTemp, a START output signal is activated.

The actual temperature at the actual execution cycle is calculated as:

æ Dt
ö
Qn = Qn -1 + ( Q final - Q n-1 ) × ç1 - e t ÷
-

è ø
EQUATION1168 V1 EN-US (Equation 119)

where:
Qn is the calculated present temperature,

Qn-1 is the calculated temperature at the previous time step,

Qfinal is the calculated final temperature with the actual current,

Dt is the time step between calculation of the actual temperature and


t is the set thermal time constant for the protected device (line or cable)

The actual temperature of the protected component (line or cable) is calculated by adding the
ambient temperature to the calculated temperature, as shown above. The ambient
temperature can be taken from a separate sensor or can be given a constant value. The
calculated component temperature is available as a real figure signal, TEMP.

When the component temperature reaches the set alarm level AlarmTemp the output signal
ALARM is set. When the component temperature reaches the set trip level TripTemp the
output signal TRIP is set.

There is also a calculation of the present time to operate with the present current. This
calculation is only performed if the final temperature is calculated to be above the operation
temperature:

æQ - Qoperate ö
toperate = -t × ln ç final
ç Q final - Q n ÷÷
è ø
EQUATION1169 V1 EN-US (Equation 120)

The calculated time to trip is available as a real figure signal, TTRIP.

After a trip, caused by the thermal overload protection, there can be a lockout to reconnect the
tripped circuit. The output lockout signal LOCKOUT is activated when the device temperature
is above the set lockout release temperature setting ReclTemp.

The time to lockout release is calculated by the following cooling time calculation. The thermal
content of the function can be reset with input RESET.

æQ - Qlockout _ release ö
tlockout _ release = -t × ln ç final ÷÷
ç Q final - Q n
è ø
EQUATION1170 V1 EN-US (Equation 121)

In the above equation, the final temperature is equal to the set or measured ambient
temperature. The calculated time to reset of lockout is available as a real figure signal,
TENRECL. This signal is enabled when the LOCKOUT output is activated.

Line distance protection REL670 503


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

In some applications the measured current can involve a number of parallel lines. This is often
used where one bay connects several parallel cables. By setting the parameter IMult to the
number of parallel lines (cables) the actual current on one line is used in the protection
algorithm by dividing the measured current by the total number of cables. To activate this
option the input ENMULT must be activated.

The protection has a reset input: RESET. By activating this input the calculated temperature is
reset to its default initial value. This is useful during testing when secondary injected current
has given a calculated “false” temperature level.

START
Final Temp > Trip Temp

TEMP
Calculation of actual
temperature

AMBTEMP ALARM
Actual Temp > Alarm Temp

I3P

Calculation of final
temperature
ENMULT
TRIP

Actual Temp > Trip Temp


SENSFLT

LOCKOUT
Lockout logic

Actual Temp < Recl Temp


BLOCK

TTRIP
Calculation of time to trip
BLKTR

TENRECL
Calculation of time to reset
of lockout

IEC09000637-2-en.vsd
IEC09000637 V2 EN-US

Figure 286: Functional overview of LCPTTR/LFPTTR

504 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

9.7.8 Technical data


M12352-1 v15

Table 297: LCPTTR/LFPTTR technical data


Function Range or value Accuracy
Reference current (2-400)% of IBase ±1.0% of Ir

Reference temperature (0-300)°C, (0 - 600)°F ±1.0°C, ±2.0°F


Operate time: Time constant t = (1–1000) IEC 60255-149, ±5.0% or ±200
minutes ms whichever is greater
 
 I , Ip
2 2 
t < σ ln  
 2 TTrip , TAmb 2 
I , T √ I ref

 ref 
EQUATION13000039 V3 EN-US (Equation 122)

TTrip= set operate temperature


TAmb = ambient temperature
Tref = temperature rise above ambient at Iref
Iref = reference load current
I = actual measured current
Ip = load current before overload occurs

Alarm temperature (0-200)°C, (0-400)°F ±2.0°C, ±4.0°F


Operate temperature (0-300)°C, (0-600)°F ±2.0°C, ±4.0°F
Reset level temperature (0-300)°C, (0-600)°F ±2.0°C, ±4.0°F

9.8 Breaker failure protection CCRBRF IP14514-1 v6

9.8.1 Identification
M14878-1 v5

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Breaker failure protection, 3-phase CCRBRF 50BF
activation and output
3I>BF

SYMBOL-U V1 EN-US

9.8.2 Functionality M11550-6 v18

Breaker failure protection (CCRBRF) ensures a fast backup tripping of the surrounding
breakers in case the own breaker fails to open. CCRBRF measurement criterion can be current
based, CB position based or an adaptive combination of these two conditions.

A current based check with extremely short reset time is used as check criterion to achieve
high security against inadvertent operation.

CB position check criteria can be used where the fault current through the breaker is small.

CCRBRF provides three different options to select how t1 and t2 timers are run:

Line distance protection REL670 505


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

1. By external start signals which is internally latched


2. Follow external start signal only
3. Follow external start signal and the selected FunctionMode

CCRBRF can be single- or three- phase initiated to allow its use with single phase tripping
applications. For the three-phase application of the CCRBRF the current criteria can be set to
operate only if “2 elements operates out of three phases and neutral” for example; two phases
or one phase plus the residual current start. This gives a higher security to the backup trip
command.

The CCRBRF function can be programmed to give a single- or three- phase retrip to its own
breaker to avoid unnecessary tripping of surrounding breakers at an incorrect initiation due to
mistakes during testing.

9.8.3 Function block M11944-3 v8

CCRBRF
I3P* TRBU
BLOCK TRBU2
START TRRET
STL1 TRRETL1
STL2 TRRETL2
STL3 TRRETL3
CBCLDL1 CBALARM
CBCLDL2 STALARM
CBCLDL3
CBFLT

IEC18001006-1-en.vsd
IEC18001006 V1 EN-US

Figure 287: CCRBRF function block

9.8.4 Signals
PID-7233-INPUTSIGNALS v1

Table 298: CCRBRF Input signals


Name Type Default Description
I3P GROUP - Three phase group signal for current inputs
SIGNAL
BLOCK BOOLEAN 0 Block of function
START BOOLEAN 0 Three phase start for breaker failure protection function
STL1 BOOLEAN 0 Start signal for phase L1
STL2 BOOLEAN 0 Start signal for phase L2
STL3 BOOLEAN 0 Start signal for phase L3
CBCLDL1 BOOLEAN 0 Circuit breaker closed in phase L1
CBCLDL2 BOOLEAN 0 Circuit breaker closed in phase L2
CBCLDL3 BOOLEAN 0 Circuit breaker closed in phase L3
CBFLT BOOLEAN 0 CB faulty, unable to trip. Backup trip instantaneously

506 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

PID-7233-OUTPUTSIGNALS v1

Table 299: CCRBRF Output signals


Name Type Description
TRBU BOOLEAN Backup trip by breaker failure protection function
TRBU2 BOOLEAN Second backup trip by breaker failure protection function
TRRET BOOLEAN Retrip by breaker failure protection function
TRRETL1 BOOLEAN Retrip by breaker failure protection function phase L1
TRRETL2 BOOLEAN Retrip by breaker failure protection function phase L2
TRRETL3 BOOLEAN Retrip by breaker failure protection function phase L3
CBALARM BOOLEAN Alarm for faulty circuit breaker
STALARM BOOLEAN External start signal timed out, when by setting StartMode
the external start signal is followed (i.e. when is NOT Latched)

9.8.5 Settings
PID-7233-SETTINGS v1

Table 300: CCRBRF Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

Table 301: CCRBRF Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
FunctionMode Current - - Current Selection of measurement principle:
CB Pos Current / CB Position / Current or CB
Current or CB Pos Position
StartMode LatchedStart - - LatchedStart Select how t1 and t2 timers are run: By
FollowStart external start signals which is
FollowStart&Mod internally latched / Follow the external
e start signal only / Follow external
start signal and selected
FunctionMode
tStartTimeout 0.5 - 600.0 s 0.1 1.0 Time delay after which the external
start signal will be ignored, when by
setting StartMode the external start
signal is followed (i.e. when is NOT
Latched)
BuTripMode 2 out of 4 - - 1 out of 3 Select backup trip mode when t2
1 out of 3 timer expires and current
1 out of 4 measurement is used: 2 elements
operate out of three phases and
neutral / 1 element operates out of
three phases / 1 element operates out
of three phases and neutral
RetripMode Off - - Off Select retrip mode when t1 timer
UseFunctionMode expires: Off / use FunctionMode to
Always check / always without any check
IPh> 5 - 200 %IB 1 10 Operate phase current level in % of
IBase
Table continues on next page

Line distance protection REL670 507


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

Name Values (Range) Unit Step Default Description


IN> 2 - 200 %IB 1 10 Operate residual current level in % of
IBase
t1 0.000 - 60.000 s 0.001 0.000 Time delay of retrip
t2 0.000 - 60.000 s 0.001 0.150 Time delay of backup trip
t2MPh 0.000 - 60.000 s 0.001 0.150 Time delay of backup trip at multi-
phase start. It can be used to speed
up backup trip command for multi-
phase faults on OHLs
tPulse 0.010 - 60.000 s 0.001 0.200 Minimum trip pulse duration

Table 302: CCRBRF Group settings (advanced)


Name Values (Range) Unit Step Default Description
I>BlkCBPos 5 - 200 %IB 1 20 I> in % of IBase to block operation
based on CB Position when
FunctionMode=Current or CB Pos
t3 0.000 - 60.000 s 0.001 0.030 Additional time delay which is added
to t2. It can be used as a second
backup trip
tCBAlarm 0.000 - 60.000 s 0.001 5.000 Time delay for alarm when faulty
circuit breaker indicated

9.8.6 Monitored data


PID-7233-MONITOREDDATA v1

Table 303: CCRBRF Monitored data


Name Type Values (Range) Unit Description
IL1 REAL - A Measured current in phase L1
IL2 REAL - A Measured current in phase L2
IL3 REAL - A Measured current in phase L3
IN REAL - A Measured residual current

9.8.7 Operation principle M16914-3 v11

Breaker failure protection CCRBRF is initiated from the protection trip command, either from
protection functions within the IED or from external protection devices.

To this function the three-phase current input and/or change to: the breaker normally open
auxiliary contact (i.e. "52a" or "closed") shall be connected. On OHL feeders where single pole
auto-reclosing is used, auxiliary contact from each CB pole shall be connected separately

The input START signal (i.e. initiate signal) can be phase selective or common (for all three
phases). Phase selective start signals enable single pole retrip functionality. This means that a
second attempt to open the same breaker can be done phase-selective. The retrip attempt is
made after a set time delay t1. For transmission lines, single pole trip and auto-reclosing is
often used. The retrip function can be phase selective if it is initiated from the phase selective
line protection.

The retrip function can be done with or without FunctionMode check. With this check, the
retrip is only performed if the circuit breaker is still seen as closed when t1 timer has elapsed.

508 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

The START signal will also start the backup trip timer. The function detects the successful
breaker opening, either by detection of low current through RMS evaluation and a special
adapted current algorithm or by monitoring the circuit breaker status using normally open
auxiliary contact from the breaker. The special algorithm enables a very fast detection of
successful breaker opening, which is, fast resetting of the current measurement. If the
function has not detected breaker opening before the backup timer has run-out its time a
backup trip is initiated.

Further the following possibilities are available:

• Three phase (i.e. common) start/initiation via input START or individual start/initiation
per phase by using phase segregated inputs STLx.
• The minimum length of the retrip pulse, the backup trip pulse and the second backup trip
pulse are settable. This pulse duration is defined by a parameter setting tPulse. The retrip
pulse, the backup trip pulse and the second backup trip pulse will however sustain as long
as there is an indication of closed breaker.
• If the current detection is used it is possible to use three different options: 1 out of 3
where it is sufficient to detect failure to open (high current) in one pole, 1 out of 4 where it
is sufficient to detect failure to open (high current) in one pole or high residual current
and 2 out of 4 where at least two currents (phase current and/or residual current) shall be
high for breaker failure detection.
• The current detection level for the residual current can be set different from the setting of
phase current detection.
• It is possible to have different backup time delays for single-phase faults and for multi-
phase faults.
• It is possible to have instantaneous backup trip function if the circuit breaker is incapable
to clear faults, for example, at low gas pressure. This will happen when input signal CBFLT
has logical value one and timer tCBAlarm has expired. This situation will be indicated via
output signal CBALARM.

The selection of measurement criterion is done with setting parameter FunctionMode, to


determine if the breaker has opened or not:

• Option1 - Current: Compares the measured phase current magnitude to setting


IPh>(operate phase current level in % of IBase), and the measured residual current
magnitude to setting IN> (Operate residual current level in % of IBase). Criterion is active
(i.e. breaker did not open yet) if the measured current magnitudes are higher than the set
values.

• Option 2 - CB Pos: This criterion is active (i.e. breaker did not open yet in phase Lx) if the
binary input CBCLDLx has logical value one. Thus function simply follows the status of CB
pole normally open auxiliary contact (i.e. "52a" or "closed") which shall be connected to
this input.

• Option 3 - Current or CB Pos: It uses a combination of Current or CB Pos criteria. Note that
Current criterion will be then always used, while the CB Pos criterion will be only enabled
and used if current is smaller than set value I>BlkCBPos at the moment when external
START signal has been received. It is recommended to set value for I>BlkCBPos higher
than the set value for IPh>.

By the setting StartMode it is possible to select how t1 and t2 timers are run and consequently
how output commands are given from the function:

• Option 1 - LatchedStart: “By external start signals which is internally latched”.


When function is once started by external START signal, the timers t1 and t2 will always
elapse and then measurement criterion defined by parameter FunctionMode will be
always checked in order to verify if the appropriate command shall be given out from the
function. Timers cannot be stopped by removing the external START signal. Function can
be started again only when all of the following three timers t1, t2 and fixed timer of 150 ms

Line distance protection REL670 509


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

in function internal design has expired and the measurement criterion defined by
parameter FunctionMode has been deactivated, see Figure 288.

• Option 2 - FollowStart: “Follow the external start signal only”.


The timers t1 and t2 will run while external START signal is present. If they elapse then
measurement criterion defined by parameter FunctionMode will be checked in order to
verify if the appropriate command shall be given out from the function. Timers can be
always stopped by resetting the external START signal, see Figure 289.

• Option 3- FollowStart&Mode: “Follow external start signal and selected FunctionMode”.


The timers t1 and t2 will run while external START signal is present and in the same time
the measurement criterion defined by parameter FunctionMode is active. If they elapse
then the appropriate command will be given out from the function. Timers can be stopped
by resetting the external START signal or if the measurement criterion de-activates, see
Figure 290.

When one of the two “follow modes” is used, there is a settable timer tStartTimeout which will
block the external START input signal when it times-out. This will automatically also reset the
t1 and t2 timers and consequently prevent any backup trip command. At the same time the
STALARM output from the function will have logical value one. To reset this signal external
START signal shall be removed. This is done in order to prevent unwanted operation of the
breaker failure function for cases where a permanent START signal is given by mistake (e.g.
due to a fault in the station battery system). Note that any backup trip command will inhibit
running of tStartTimeout timer.

The BLOCK signal overrides any StartMode condition and resets START signal, running of t1
and t2 timers and all function outputs.

30ms t1 30ms
START OR TRRET
S Q t AND

t2 30ms
OR TRBU
t AND

Current Check
CB Position Check OR

150ms
AND
t
NOT

IEC18001002-1-en.vsdx

IEC18001002 V1 EN-US

Figure 288: Simplified overall logic for LatchedStart

510 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

t1
START OR TRRET
t AND

Current Check
CB Position Check OR

t2
TRBU
t AND
OR

IEC18001003-1-en.vsdx
IEC18001003 V1 EN-US

Figure 289: Simplified overall logic for FollowStart

START t1 TRRET
AND t

Current Check
CB Position Check OR t2 TRBU
t

IEC18001004-1-en.vsdx
IEC18001004 V1 EN-US

Figure 290: Simplified overall logic for FollowStart&Mode


The BuTripMode setting defines how many measurement elements must operate, when
current criterion is used, to determine if the CB is opened or not:

• 2 elements operate out of three phases and neutral


• 1 element operates out of three phases
• 1 element operates out of three phases and neutral

Note that it is possible to set several timers for the backup trip as described below:

1. Timer t2 is used when function is started in one phase only (i.e. for single-phase to ground
fault on an OHL (Over Head Lines) when single-pole auto-reclosing is used).
2. Timer t2MPh is used when function is started in at least two phases. This will allow to have
shorter backup trip times for a multi-phase fault on an OHL Note that for a protected
object which are always tripped three-phase (e.g. transformers, generators, reactors,
cables, etc.) this timer shall always be set to the same value as t2 timer.
3. Timer t3 can be used to give a second backup trip command. It can be used in stations
having small DC battery which is not capable to trip all surrounding breakers at once. Note
that t3 timer will only start when t2 timer expires.

The RetripMode defines how retrip feature will behave:

• Off: The retrip command to the own circuit breaker is permanently disabled.
• UseFunctionMode: Retrip command to the own circuit breaker is given only if
measurement criterion defined by setting parameter FunctionMode is still active when set
timer t1 expires (e.g. if FunctionMode=Current and current magnitude is higher than set
value IPh> when t1 expires, the retrip command will be issued).
• Always: Retrip command to the own circuit breaker is given always when set timer t1
expires without any further checks.

Line distance protection REL670 511


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

The simplified logic for the function is given in the following figures.

StartMode

LatchedStart

FollowStart
1 FollowStart&Mode OR

START 30ms
int startL1
STL1 OR AND S Q
BLOCK
NOT

int reset
OR R
NOT

TRBU
NOT int startAlarmL1

tStartTimeout
AND t NOT
AND AND int startAlarmL2 STALARM
From other OR
phases int startAlarmL3

IEC18001005-1-en.vsdx

IEC18001005 V1 EN-US

Figure 291: Start logic for all three Function Modes of operation

IL1
a
a>b NOT
IPh> b

FunctionMode
Current
CB Pos OR AND int reset
OR
1
Current or CB Pos 150 ms
int startL1
t
OR AND
t1
t
t2
t OR
t2MPh
t

AND

CBCLDL1
NOT

IEC18001007-1-en.vsdx

IEC18001007 V1 EN-US

Figure 292: Reset logic in latched mode

StartMode
LatchedStart
FollowStart
1 FollowStart&Mode OR AND

int retrip
currPh1Check
CB Position Check OR 30ms
AND t1 OR AND
int startL1 t OR

t1
t

RetripMode
Off tPulse
TRRETL1
UseFunctionMode AND OR
1
Always

TRRETL2 TRRET
TRRETL3
OR

tPulse From other


AND phases

IEC18001008-1-en.vsdx

IEC18001008 V1 EN-US

Figure 293: Simplified retrip logic

512 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

StartMode
LatchedStart

1 FollowStart
FollowStart&Mode OR AND

currCheck
CB Position Check OR
backupTripL1
t2
AND t 30ms
OR AND
OR OR
int startL1

t2MPh tPulse TRBU


int startL2 From backupTripL2 OR
2 of 3 OR
int startL3 t other backupTripL3
phases

t3
t TRBU2
OR
AND
tPulse

CBFLT tCBAlarm CBALARM


t
IEC18001009-1-en.vsdx

IEC18001009 V1 EN-US

Figure 294: Simplified backup trip logic

9.8.8 Technical data IP10269-1 v1

M12353-1 v15

Table 304: CCRBRF technical data


Function Range or value Accuracy
Operate phase current (5-200)% of lBase ±1.0% of Ir at I £ Ir
±1.0% of I at I > Ir

Reset ratio, phase current > 95% -


Operate residual current (2-200)% of lBase ±1.0% of Ir at I £ Ir
±1.0% of I at I > Ir

Reset ratio, residual current > 95% -


Phase current level for blocking of contact (5-200)% of lBase ±1.0% of Ir at I £ Ir
function ±1.0% of I at I > Ir

Reset ratio > 95% -


Operate time for current detection 10 ms typically -
Reset time for current detection 10 ms maximum * -
Time delay for retrip at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±15 ms whichever is
greater
Time delay for backup trip at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±15 ms whichever is
greater
Time delay for backup trip at multi-phase start (0.000-60.000) s ±0.2% or ±20 ms whichever is
at 0 to 2 x Iset greater

Additional time delay for a second backup trip (0.000-60.000) s ±0.2% or ±20 ms whichever is
at 0 to 2 x Iset greater

Time delay for alarm for faulty circuit breaker (0.000-60.000) s ±0.2% or ±15 ms whichever is
greater
Minimum trip pulse duration (0.010-60.000) s ±0.2% or ±5 ms whichever is
greater
* Valid for product version 2.2.3 or later

Line distance protection REL670 513


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

9.9 Stub protection STBPTOC IP14515-1 v3

9.9.1 Identification
M17108-1 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Stub protection STBPTOC 50STB

3I>STUB

SYMBOL-T V1 EN-US

9.9.2 Functionality M12902-3 v10

When a power line is taken out of service for maintenance and the line disconnector is opened
in multi-breaker arrangements the voltage transformers will mostly be outside on the
disconnected part. The primary line distance protection will thus not be able to operate and
must be blocked.

The stub protection (STBPTOC) covers the zone between the current transformers and the
open disconnector. The three-phase instantaneous overcurrent function is released from a
normally open, NO (b) auxiliary contact on the line disconnector.

9.9.3 Function block M12524-3 v5

STBPTOC
I3P* TRIP
BLOCK START
BLKTR
RELEASE

IEC05000678-2-en.vsd
IEC05000678 V2 EN-US

Figure 295: STBPTOC function block

9.9.4 Signals
PID-6931-INPUTSIGNALS v1

Table 305: STBPTOC Input signals


Name Type Default Description
I3P GROUP - Three phase currents
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Block of trip
RELEASE BOOLEAN 0 Release of stub protection

PID-6931-OUTPUTSIGNALS v1

Table 306: STBPTOC Output signals


Name Type Description
TRIP BOOLEAN General trip
START BOOLEAN General start

514 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

9.9.5 Settings
PID-6931-SETTINGS v1

Table 307: STBPTOC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
ReleaseMode Release - - Release Release of stub protection
Continuous
I> 5 - 2500 %IB 1 200 Operate current level in % of IBase

Table 308: STBPTOC Group settings (advanced)


Name Values (Range) Unit Step Default Description
tDelay 0.000 - 60.000 s 0.001 0.000 Time delay

Table 309: STBPTOC Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

9.9.6 Monitored data


PID-3462-MONITOREDDATA v5

Table 310: STBPTOC Monitored data


Name Type Values (Range) Unit Description
IL1 REAL - A Current in phase L1
IL2 REAL - A Current in phase L2
IL3 REAL - A Current in phase L3

9.9.7 Operation principle M12905-3 v5

The sampled analog phase currents are pre-processed in a discrete Fourier filter (DFT) block.
From the fundamental frequency components of each phase current the RMS value of each
phase current is derived. These phase current values are fed to a comparator in the stub
protection function STBPTOC. In a comparator the RMS values are compared to the set
operating current value of the function I>.

If a phase current is larger than the set operating current the signal from the comparator for
this phase is activated. This signal will, in combination with the release signal from line
disconnection (RELEASE input), activate the timer for the TRIP signal. If the fault current
remains during the timer delay t, the TRIP output signal is activated. The function can be
blocked by activation of the BLOCK input.

Line distance protection REL670 515


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

STUB PROTECTION FUNCTION

BLOCK

TRIP
STIL1 AND

STIL2 OR

STIL3

RELEASE

en05000731.vsd
IEC05000731 V1 EN-US

Figure 296: Simplified logic diagram for Stub protection

9.9.8 Technical data


M12350-1 v12

Table 311: STBPTOC technical data


Function Range or value Accuracy
Operating current (5-2500)% of IBase ±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir

Reset ratio > 95% at (50-2500)% of IBase -


Independent time delay at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±30 ms whichever is
greater
Operate time, start at 0 to 2 x Iset Min. = 10 ms -
Max. = 20 ms
Reset time, start at 2 x Iset to 0 Min. = 10 ms -
Max. = 20 ms
Critical impulse time 10 ms typically at 0 to 2 x Iset -

Impulse margin time 15 ms typically -

9.10 Pole discordance protection CCPDSC IP14516-1 v5

9.10.1 Identification
M14888-1 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Pole discordance protection CCPDSC 52PD

PD

SYMBOL-S V1 EN-US

516 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

9.10.2 Functionality M13269-3 v15

An open phase can cause negative and zero sequence currents which cause thermal stress on
rotating machines and can cause unwanted operation of zero sequence or negative sequence
current functions.

Normally the own breaker is tripped to correct such a situation. If the situation persists the
surrounding breakers should be tripped to clear the unsymmetrical load situation.

The Pole discordance protection function (CCPDSC) operates based on information from
auxiliary contacts of the circuit breaker for the three phases with additional criteria from
unsymmetrical phase currents when required.

9.10.3 Function block M17149-3 v6

CCPDSC
I3P* TRIP
BLOCK START
BLKDBYAR
CLOSECMD
OPENCMD
EXTPDIND
POLE1OPN
POLE1CL
POLE2OPN
POLE2CL
POLE3OPN
POLE3CL

IEC13000305-1-en.vsd
IEC13000305 V1 EN-US

Figure 297: CCPDSC function block

9.10.4 Signals
PID-3525-INPUTSIGNALS v8

Table 312: CCPDSC Input signals


Name Type Default Description
I3P GROUP - Three phase currents
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKDBYAR BOOLEAN 0 Block of function at CB single phase auto re-closing cycle
CLOSECMD BOOLEAN 0 Close order to CB
OPENCMD BOOLEAN 0 Open order to CB
EXTPDIND BOOLEAN 0 Pole discordance signal from CB logic
POLE1OPN BOOLEAN 1 Pole one opened indication from CB
POLE1CL BOOLEAN 0 Pole one closed indication from CB
POLE2OPN BOOLEAN 1 Pole two opened indication from CB
POLE2CL BOOLEAN 0 Pole two closed indication from CB
POLE3OPN BOOLEAN 1 Pole three opened indication from CB
POLE3CL BOOLEAN 0 Pole three closed indication from CB

Line distance protection REL670 517


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

PID-3525-OUTPUTSIGNALS v8

Table 313: CCPDSC Output signals


Name Type Description
TRIP BOOLEAN Trip signal to CB
START BOOLEAN Trip condition TRUE, waiting for time delay

9.10.5 Settings
PID-3525-SETTINGS v8

Table 314: CCPDSC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
tTrip 0.000 - 60.000 s 0.001 0.300 Time delay between trip condition and
trip signal
ContSel Off - - Off Contact function selection
PD signal from CB
Pole pos aux cont.
CurrSel Off - - Off Current function selection
CB oper monitor
Continuous
monitor
CurrUnsymLevel 0 - 100 % 1 80 Unsym magn of lowest phase current
compared to the highest.
CurrRelLevel 0 - 100 %IB 1 10 Current magnitude for release of the
function in % of IBase

Table 315: CCPDSC Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

9.10.6 Monitored data


PID-3525-MONITOREDDATA v6

Table 316: CCPDSC Monitored data


Name Type Values (Range) Unit Description
IMin REAL - A Lowest phase current
IMax REAL - A Highest phase current

9.10.7 Operation principle


M13273-3 v6
The detection of pole discordance can be made in two different ways. If the contact based
function is used an external logic can be made by connecting the auxiliary contacts of the
circuit breaker so that a pole discordance is indicated, see figure 298.

518 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

circuit breaker

Pole discordance signal from circuit breaker

en05000287.vsd

IEC05000287 V2 EN-US

Figure 298: Pole discordance external detection logic


This binary signal is connected to a binary input of the IED. The appearance of this signal will
start a timer that will give a trip signal after the set time delay.

There is also a possibility to connect all phase selective auxiliary contacts (phase contact open
and phase contact closed) to binary inputs of the IED, see figure 299.

C.B.

poleOneClosed from C.B.

poleTwoClosed from C.B.

poleThreeClosed from C.B.

+
poleOneOpened from C.B.

poleTwoOpened from C.B.

poleThreeOpened from C.B.

en05000288.vsd
IEC05000288 V1 EN-US

Figure 299: Pole discordance signals for internal logic


In this case the logic is realized within the function. If the inputs are indicating pole
discordance the trip timer is started. This timer will give a trip signal after the set delay.

Pole discordance can also be detected by means of phase selective current measurement. The
sampled analog phase currents are pre-processed in a discrete Fourier filter (DFT) block. From
the fundamental frequency components of each phase current the RMS value of each phase
current is derived. The smallest and the largest phase current are derived. If the smallest phase
current is lower than the setting CurrUnsymLevel times the largest phase current the settable
trip timer (tTrip) is started. The tTrip timer gives a trip signal after the set delay. The TRIP
signal is a pulse 150 ms long. The current based pole discordance function can be set to be
active either continuously or only directly in connection to breaker open or close command.

The function also has a binary input that can be configured from the autoreclosing function, so
that the pole discordance function can be blocked during sequences with a single pole open if
single pole autoreclosing is used.
M13946-3 v7
The simplified block diagram of the current and contact based Pole discordance protection
function CCPDSC is shown in figure 300.

Line distance protection REL670 519


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

BLOCK
OR
BLKDBYAR

PolPosAuxCont

AND
POLE1OPN
POLE1CL
POLE2OPN
Discordance
POLE2CL
detection
POLE3OPN
POLE3CL t 150 ms
t TRIP
AND
OR

PD Signal from CB
AND
EXTPDIND

CLOSECMD t+200 ms
OR
OPENCMD

AND

Unsymmetry current
detection

en05000747.vsd
IEC05000747 V1 EN-US

Figure 300: Simplified block diagram of pole discordance function CCPDSC - contact and
current based
CCPDSC is blocked if:

• The IED is in TEST mode and CCPDSC has been blocked from the local HMI
• The input signal BLOCK is high
• The input signal BLKDBYAR is high

The BLOCK signal is a general purpose blocking signal of the pole discordance protection. It
can be connected to a binary input in the IED in order to receive a block command from
external devices or can be software connected to other internal functions in the IED itself in
order to receive a block command from internal functions. Through OR gate it can be
connected to both binary inputs and internal function outputs.

The BLKDBYAR signal blocks the pole discordance operation when a single phase
autoreclosing cycle is in progress. It can be connected to the output signal 1PT1 on
SMBRRECfunction block. If the autoreclosing function is an external device, then BLKDBYAR
has to be connected to a binary input in the IED and this binary input is connected to a
signalization “1phase autoreclosing in progress” from the external autoreclosing device.

If the pole discordance protection is enabled, then two different criteria can generate a trip
signal TRIP:

• Pole discordance signaling from the circuit breaker.


• Unsymmetrical current detection.

9.10.7.1 Pole discordance signaling from circuit breaker M13946-18 v4

If one or two poles of the circuit breaker have failed to open or to close the pole discordance
status, then the function input EXTPDIND is activated from the pole discordance signal
derived from the circuit breaker auxiliary contacts (one NO contact for each phase connected
in parallel, and in series with one NC contact for each phase connected in parallel) and, after a
settable time interval tTrip (0-60 s), a 150 ms trip pulse command TRIP is generated by the
Polediscordance function.

520 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

9.10.7.2 Unsymmetrical current detection M13946-21 v4

Unsymmetrical current indicated if:

• any phase current is lower than CurrUnsymLevel of the highest current in the three
phases.
• the highest phase current is greater than CurrRelLevel of IBase.

If these conditions are true, an unsymmetrical condition is detected and the internal signal
INPS is turned high. This detection is enabled to generate a trip after a set time delay tTrip if
the detection occurs in the next 200 ms after the circuit breaker has received a command to
open trip or close and if the unbalance persists. The 200 ms limitation is for avoiding
unwanted operation during unsymmetrical load conditions.

The pole discordance protection is informed that a trip or close command has been given to
the circuit breaker through the inputs CLOSECMD (for closing command information) and
OPENCMD (for opening command information). These inputs can be connected to terminal
binary inputs if the information are generated from the field (that is from auxiliary contacts of
the close and open push buttons) or may be software connected to the outputs of other
integrated functions (that is close command from a control function or a general trip from
integrated protections).

9.10.8 Technical data


M13279-1 v10

Table 317: CCPDSC technical data


Function Range or value Accuracy
Operate current (0–100)% of IBase ±1.0% of Ir

Independent time delay (0.000-60.000) s ±0.2% or ± 30 ms whichever is greater


between trip condition and
trip signal

9.11 Directional underpower protection GUPPDUP SEMOD156693-1 v4

9.11.1 Identification
SEMOD158941-2 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Directional underpower protection GUPPDUP 37
P<
2
SYMBOL-LL V2 EN-US

9.11.2 Functionality SEMOD155787-4 v6

The task of a generator in a power plant is to convert mechanical energy available as a torque
on a rotating shaft to electric energy.

Sometimes, the mechanical power from a prime mover may decrease so much that it does not
cover bearing losses and ventilation losses. Then, the synchronous generator becomes a

Line distance protection REL670 521


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

synchronous motor and starts to take electric power from the rest of the power system. This
operating state, where individual synchronous machines operate as motors, implies no risk for
the machine itself. If the generator under consideration is very large and if it consumes lots of
electric power, it may be desirable to disconnect it to ease the task for the rest of the power
system.

Often, the motoring condition may imply that the turbine is in a very dangerous state. The task
of the low forward power protection is to protect the turbine and not to protect the generator
itself.

Figure 301 illustrates the low forward power and reverse power protection with underpower
and overpower functions respectively. The underpower IED gives a higher margin and should
provide better dependability. On the other hand, the risk for unwanted operation immediately
after synchronization may be higher. One should set the underpower IED to trip if the active
power from the generator is less than about 2%. One should set the overpower IED to trip if
the power flow from the network to the generator is higher than 1% depending on the type of
turbine.

When IED with a metering class input CTs is used pickup can be set to more sensitive value
(e.g.0,5% or even to 0,2%).

Underpower IED Overpower IED

Operate
Q Q
Operate
Line Line

Margin Margin
P P

Operating point Operating point


without without
turbine torque turbine torque

IEC06000315-2-en.vsd
IEC06000315 V2 EN-US

Figure 301: Protection with underpower IED and overpower IED

9.11.3 Function block SEMOD172623-4 v4

GUPPDUP
I3P* TRIP
U3P* TRIP1
BLOCK TRIP2
BLOCK1 START
BLOCK2 START1
START2
P
PPERCENT
Q
QPERCENT

IEC07000027-2-en.vsd
IEC07000027 V2 EN-US

Figure 302: GUPPDUP function block

522 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

9.11.4 Signals
PID-3709-INPUTSIGNALS v6

Table 318: GUPPDUP Input signals


Name Type Default Description
I3P GROUP - Current group connection
SIGNAL
U3P GROUP - Voltage group connection
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLOCK1 BOOLEAN 0 Block of stage 1
BLOCK2 BOOLEAN 0 Block of stage 2

PID-3709-OUTPUTSIGNALS v6

Table 319: GUPPDUP Output signals


Name Type Description
TRIP BOOLEAN Common trip signal
TRIP1 BOOLEAN Trip of stage 1
TRIP2 BOOLEAN Trip of stage 2
START BOOLEAN Common start
START1 BOOLEAN Start of stage 1
START2 BOOLEAN Start of stage 2
P REAL Active Power in MW
PPERCENT REAL Active power in % of SBase
Q REAL Reactive power in MVAr
QPERCENT REAL Reactive power in % of SBase

9.11.5 Settings
PID-3709-SETTINGS v6

Table 320: GUPPDUP Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
OpMode1 Off - - UnderPower Operation mode for stage 1 Off / On
UnderPower
Power1 0.0 - 500.0 %SB 0.1 1.0 Stage 1 underpower setting in Angle1
direction in % of SBase
Angle1 -180.0 - 180.0 Deg 0.1 0.0 Characteristic angle for max power
senistivity stage 1
TripDelay1 0.01 - 6000.00 s 0.01 1.00 Trip delay for stage 1
DropDelay1 0.01 - 6000.00 s 0.01 0.06 Drop-off delay for stage 1
OpMode2 Off - - UnderPower Operation mode for stage 2 Off / On
UnderPower
Power2 0.0 - 500.0 %SB 0.1 1.0 Power setting for stage 2 in % of
SBase
Table continues on next page

Line distance protection REL670 523


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

Name Values (Range) Unit Step Default Description


Angle2 -180.0 - 180.0 Deg 0.1 0.0 Characteristic angle for max power
senistivity stage 2
TripDelay2 0.01 - 6000.00 s 0.01 1.00 Trip delay for stage 2
DropDelay2 0.01 - 6000.00 s 0.01 0.06 Drop-off delay for stage 2

Table 321: GUPPDUP Group settings (advanced)


Name Values (Range) Unit Step Default Description
k 0.000 - 0.999 - 0.001 0.000 Low pass filter coefficient for power
measurement, P and Q
Hysteresis1 0.2 - 5.0 %SB 0.1 0.5 Absolute hysteresis of stage 1 in %
SBase
Hysteresis2 0.2 - 5.0 %SB 0.1 0.5 Absolute hysteresis of stage 2 in %
SBase
IAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
current error at 5% of Ir
IAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
current error at 30% of Ir
IAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
current error at 100% of Ir
UAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
voltage error at 5% of Ur
UAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
voltage error at 30% of Ur
UAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
voltage error at 100% of Ur
IAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Corr of error betw current and voltage
angles at 5% of Ir
IAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Corr of error betw current and voltage
angles at 30% of Ir
IAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Corr of error betw current and voltage
angles at 100% of Ir

Table 322: GUPPDUP Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups
Mode L1, L2, L3 - - Pos Seq Selection of measured current and
Arone voltage
Pos Seq
L1L2
L2L3
L3L1
L1
L2
L3

524 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

9.11.6 Monitored data


PID-3709-MONITOREDDATA v5

Table 323: GUPPDUP Monitored data


Name Type Values (Range) Unit Description
P REAL - MW Active Power in MW
PPERCENT REAL - % Active power in % of SBase
Q REAL - MVAr Reactive power in MVAr
QPERCENT REAL - % Reactive power in % of SBase

9.11.7 Operation principle


SEMOD172136-4 v4
A simplified scheme showing the principle of the power protection function is shown in
figure 303. The function has two stages with individual settings.

Chosen current
phasors P

Complex Derivation of S(angle)


S(angle) < t TRIP1
power S(composant)
Chosen voltage Power1
calculation in Char angle
phasors Q
START1

S(angle) < t TRIP2


Power2
START2

P = POWRE

Q = POWIM

IEC09000018-2-en.vsd
IEC09000018 V2 EN-US

Figure 303: Simplified logic diagram of the power protection function


The function will use voltage and current phasors calculated in the pre-processing blocks. The
apparent complex power is calculated according to chosen formula as shown in table 324.

Table 324: Complex power calculation


Set value: Mode Formula used for complex power calculation
L1, L2, L3
S = U L1 × I L1* + U L 2 × I L 2* + U L 3 × I L 3*
EQUATION1697 V1 EN-US (Equation 123)
Arone
S = U L1L 2 × I L1* - U L 2 L 3 × I L 3*
EQUATION1698 V1 EN-US (Equation 124)
PosSeq
S = 3 × U PosSeq × I PosSeq*
EQUATION1699 V1 EN-US (Equation 125)
Table continues on next page

Line distance protection REL670 525


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

Set value: Mode Formula used for complex power calculation


L1L2
S = U L1L 2 × ( I L1* - I L 2* )
EQUATION1700 V1 EN-US (Equation 126)
L2L3
S = U L 2 L 3 × ( I L 2* - I L 3* )
EQUATION1701 V1 EN-US (Equation 127)
L3L1
S = U L 3 L1 × ( I L 3* - I L1* )
EQUATION1702 V1 EN-US (Equation 128)
L1
S = 3 × U L1 × I L1*
EQUATION1703 V1 EN-US (Equation 129)
L2
S = 3 × U L 2 × I L 2*
EQUATION1704 V1 EN-US (Equation 130)
L3
S = 3 × U L 3 × I L 3*
EQUATION1705 V1 EN-US (Equation 131)

The active and reactive power is available from the function and can be used for monitoring
and fault recording.

The component of the complex power S = P + jQ in the direction Angle1(2) is calculated. If this
angle is 0° the active power component P is calculated. If this angle is 90° the reactive power
component Q is calculated.

The calculated power component is compared to the power pick up setting Power1(2). For
directional underpower protection, a start signal START1(2) is activated if the calculated power
component is smaller than the pick up value. For directional overpower protection, a start
signal START1(2) is activated if the calculated power component is larger than the pick up
value. After a set time delay TripDelay1(2) a trip TRIP1(2) signal is activated if the start signal is
still active. At activation of any of the two stages a common signal START will be activated. At
trip from any of the two stages also a common signal TRIP will be activated.

To avoid instability there is a settable hysteresis in the power function. The absolute
hysteresis of the stage1(2) is Hysteresis1(2) = abs (Power1(2) + drop-power1(2)). For generator
low forward power protection the power setting is very low, normally down to 0.02 p.u. of
rated generator power. The hysteresis should therefore be set to a smaller value. The drop-
power value of stage1 can be calculated with the Power1(2), Hysteresis1(2): drop-power1(2) =
Power1(2) + Hysteresis1(2)

For small power1 values the hysteresis1 may not be too big, because the drop-power1(2) would
be too small. In such cases, the hysteresis1 greater than (0.5 · Power1(2)) is corrected to the
minimal value.

If the measured power drops under the drop-power1(2) value, the function will reset after a set
time DropDelay1(2). The reset means that the start signal will drop out and that the timer of
the stage will reset.

9.11.7.1 Low pass filtering SEMOD172136-39 v3

In order to minimize the influence of the noise signal on the measurement it is possible to
introduce the recursive, low pass filtering of the measured values for S (P, Q). This will make
slower measurement response to the step changes in the measured quantity. Filtering is
performed in accordance with the following recursive formula:

526 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

S = k × SOld + (1 - k ) × SCalculated
EQUATION1959 V1 EN-US (Equation 132)

Where
S is a new measured value to be used for the protection function
Sold is the measured value given from the function in previous execution cycle

SCalculated is the new calculated value in the present execution cycle

k is settable parameter by the end user which influence the filter properties
TD

Default value for parameter k is 0.00. With this value the new calculated value is immediately
given out without any filtering (that is without any additional delay). When k is set to value
bigger than 0, the filtering is enabled. A typical value for k=0.92 in case of slow operating
functions.

9.11.7.2 Calibration of analog inputs SEMOD172136-57 v3

Measured currents and voltages used in the Power function can be calibrated to get class 0.5
measuring accuracy. This is achieved by amplitude and angle compensation at 5, 30 and 100%
of rated current and voltage. The compensation below 5% and above 100% is constant and
linear in between, see example in figure 304.

IEC05000652 V2 EN-US

Figure 304: Calibration curves


The first current and voltage phase in the group signals will be used as reference and the
amplitude and angle compensation will be used for related input signals.

Line distance protection REL670 527


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

Analog outputs (Monitored data) from the function can be used for service values or in the
disturbance report. The active power is provided as MW value: P, or in percent of base power:
PPERCENT. The reactive power is provided as Mvar value: Q, or in percent of base power:
QPERCENT.

9.11.8 Technical data SEMOD175153-1 v1

SEMOD175152-2 v11

Table 325: GUPPDUP technical data


Function Range or value Accuracy
Power level (0.0–500.0)% of SBase ±1.0% of Sr at S ≤ Sr
for Step 1 and Step 2 ±1.0% of S at S > Sr
where

S r = 1.732 × U r × I r

Characteristic angle (-180.0–180.0) degrees ±2.0 degrees


for Step 1 and Step 2
Independent time delay to operate for (0.01-6000.00) s ±0.2% or ±40 ms whichever is
Step 1 and Step 2 at 2 x Sr to 0.5 x Sr and greater
k=0.000

9.12 Directional overpower protection GOPPDOP SEMOD172360-1 v4

9.12.1 Identification
SEMOD176574-2 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Directional overpower protection GOPPDOP 32
P>
2
DOCUMENT172362-IMG158942
V2 EN-US

9.12.2 Functionality SEMOD172356-4 v5

The task of a generator in a power plant is to convert mechanical energy available as a torque
on a rotating shaft to electric energy.

Sometimes, the mechanical power from a prime mover may decrease so much that it does not
cover bearing losses and ventilation losses. Then, the synchronous generator becomes a
synchronous motor and starts to take electric power from the rest of the power system. This
operating state, where individual synchronous machines operate as motors, implies no risk for
the machine itself. If the generator under consideration is very large and if it consumes lots of
electric power, it may be desirable to disconnect it to ease the task for the rest of the power
system.

Often, the motoring condition may imply that the turbine is in a very dangerous state. The task
of the reverse power protection is to protect the turbine and not to protect the generator
itself.

Figure 305 illustrates the low forward power and reverse power protection with underpower
and overpower functions respectively. The underpower IED gives a higher margin and should

528 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

provide better dependability. On the other hand, the risk for unwanted operation immediately
after synchronization may be higher. One should set the underpower IED to trip if the active
power from the generator is less than about 2%. One should set the overpower IED to trip if
the power flow from the network to the generator is higher than 1%.

When IED with a metering class input CTs is used pickup can be set to more sensitive value
(e.g.0,5% or even to 0,2%).

Underpower IED Overpower IED

Operate
Q Q
Operate
Line Line

Margin Margin
P P

Operating point Operating point


without without
turbine torque turbine torque

IEC06000315-2-en.vsd
IEC06000315 V2 EN-US

Figure 305: Reverse power protection with underpower IED and overpower IED

9.12.3 Function block SEMOD172667-4 v4

GOPPDOP
I3P* TRIP
U3P* TRIP1
BLOCK TRIP2
BLOCK1 START
BLOCK2 START1
START2
P
PPERCENT
Q
QPERCENT

IEC07000028-2-en.vsd
IEC07000028 V2 EN-US

Figure 306: GOPPDOP function block

9.12.4 Signals
PID-3710-INPUTSIGNALS v7

Table 326: GOPPDOP Input signals


Name Type Default Description
I3P GROUP - Current group connection
SIGNAL
U3P GROUP - Voltage group connection
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLOCK1 BOOLEAN 0 Block of stage 1
BLOCK2 BOOLEAN 0 Block of stage 2

Line distance protection REL670 529


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

PID-3710-OUTPUTSIGNALS v7

Table 327: GOPPDOP Output signals


Name Type Description
TRIP BOOLEAN Common trip signal
TRIP1 BOOLEAN Trip of stage 1
TRIP2 BOOLEAN Trip of stage 2
START BOOLEAN Common start
START1 BOOLEAN Start of stage 1
START2 BOOLEAN Start of stage 2
P REAL Active power P in MW
PPERCENT REAL Active power P in % of SBase
Q REAL Reactive power Q in MVAr
QPERCENT REAL Reactive power Q in % of SBase

9.12.5 Settings
PID-3710-SETTINGS v7

Table 328: GOPPDOP Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
OpMode1 Off - - OverPower Operation mode for stage 1 Off / On
OverPower
Power1 0.0 - 500.0 %SB 0.1 120.0 Stage 1 overpower setting in Angle1
direction in % of SBase
Angle1 -180.0 - 180.0 Deg 0.1 0.0 Characteristic angle for max power
senistivity stage 1
TripDelay1 0.01 - 6000.00 s 0.01 1.00 Trip delay for stage 1
DropDelay1 0.01 - 6000.00 s 0.01 0.06 Drop-off delay for stage 1
OpMode2 Off - - OverPower Operation mode for stage 2 Off / On
OverPower
Power2 0.0 - 500.0 %SB 0.1 120.0 Stage 2 overpower setting in Angle2
direction in % of SBase
Angle2 -180.0 - 180.0 Deg 0.1 0.0 Characteristic angle for max power
senistivity stage 2
TripDelay2 0.01 - 6000.00 s 0.01 1.00 Trip delay for stage 2
DropDelay2 0.01 - 6000.00 s 0.01 0.06 Drop-off delay for stage 2

Table 329: GOPPDOP Group settings (advanced)


Name Values (Range) Unit Step Default Description
k 0.000 - 0.999 - 0.001 0.000 Low pass filter coefficient for power
measurement, P and Q
Hysteresis1 0.2 - 5.0 %SB 0.1 0.5 Absolute hysteresis of stage 1 in % of
SBase
Hysteresis2 0.2 - 5.0 %SB 0.1 0.5 Absolute hysteresis of stage 2 in % of
SBase
Table continues on next page

530 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

Name Values (Range) Unit Step Default Description


IAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
current error at 5% of Ir
IAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
current error at 30% of Ir
IAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
current error at 100% of Ir
UAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
voltage error at 5% of Ur
UAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
voltage error at 30% of Ur
UAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
voltage error at 100% of Ur
IAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Corr of error betw current and voltage
angles at 5% of Ir
IAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Corr of error betw current and voltage
angles at 30% of Ir
IAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Corr of error betw current and voltage
angles at 100% of Ir

Table 330: GOPPDOP Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups
Mode L1, L2, L3 - - Pos Seq Selection of measured current and
Arone voltage
Pos Seq
L1L2
L2L3
L3L1
L1
L2
L3

9.12.6 Monitored data


PID-3710-MONITOREDDATA v6

Table 331: GOPPDOP Monitored data


Name Type Values (Range) Unit Description
P REAL - MW Active power P in MW
PPERCENT REAL - % Active power P in % of SBase
Q REAL - MVAr Reactive power Q in MVAr
QPERCENT REAL - % Reactive power Q in % of SBase

9.12.7 Operation principle


SEMOD172154-4 v3
A simplified scheme showing the principle of the power protection function is shown in
figure 307. The function has two stages with individual settings.

Line distance protection REL670 531


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

Chosen current
phasors P

Complex Derivation of S(angle)


S(angle) > t TRIP1
power S(composant)
Chosen voltage Power1
calculation in Char angle
phasors Q
START1

S(angle) > t TRIP2


Power2
START2

P = POWRE

Q = POWIM

IEC06000567-2-en.vsd
IEC06000567 V2 EN-US

Figure 307: Simplified logic diagram of the power protection function


The function will use voltage and current phasors calculated in the pre-processing blocks. The
apparent complex power is calculated according to chosen formula as shown in table 332.

Table 332: Complex power calculation


Set value: Mode Formula used for complex power calculation
L1, L2, L3
S = U L1 × I L1* + U L 2 × I L 2* + U L 3 × I L 3*
EQUATION1697 V1 EN-US (Equation 133)
Arone
S = U L1L 2 × I L1* - U L 2 L 3 × I L 3*
EQUATION1698 V1 EN-US (Equation 134)
PosSeq
S = 3 × U PosSeq × I PosSeq*
EQUATION1699 V1 EN-US (Equation 135)
L1L2
S = U L1L 2 × ( I L1* - I L 2* )
EQUATION1700 V1 EN-US (Equation 136)
L2L3
S = U L 2 L 3 × ( I L 2* - I L 3* )
EQUATION1701 V1 EN-US (Equation 137)
L3L1
S = U L 3 L1 × ( I L 3* - I L1* )
EQUATION1702 V1 EN-US (Equation 138)
L1
S = 3 × U L1 × I L1*
EQUATION1703 V1 EN-US (Equation 139)
L2
S = 3 × U L 2 × I L 2*
EQUATION1704 V1 EN-US (Equation 140)
L3
S = 3 × U L 3 × I L 3*
EQUATION1705 V1 EN-US (Equation 141)

532 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

The active and reactive power is available from the function and can be used for monitoring
and fault recording.

The component of the complex power S = P + jQ in the direction Angle1(2) is calculated. If this
angle is 0° the active power component P is calculated. If this angle is 90° the reactive power
component Q is calculated.

The calculated power component is compared to the power pick up setting Power1(2). A start
signal START1(2) is activated if the calculated power component is larger than the pick up
value. After a set time delay TripDelay1(2) a trip TRIP1(2) signal is activated if the start signal is
still active. At activation of any of the two stages a common signal START will be activated. At
trip from any of the two stages also a common signal TRIP will be activated.

To avoid instability there is a settable hysteresis in the power function. The absolute
hysteresis of the stage1(2) is Hysteresis1(2) = abs (Power1(2) – drop-power1(2)). For generator
reverse power protection the power setting is very low, normally down to 0.02 p.u. of rated
generator power. The hysteresis should therefore be set to a smaller value. The drop-power
value of stage1 can be calculated with the Power1(2), Hysteresis1(2): drop-power1(2) =
Power1(2) – Hysteresis1(2)

For small power1 values the hysteresis1 may not be too big, because the drop-power1(2) would
be too small. In such cases, the hysteresis1 greater than (0.5 · Power1(2)) is corrected to the
minimal value.

If the measured power drops under the drop-power1(2) value the function will reset after a set
time DropDelay1(2). The reset means that the start signal will drop out ant that the timer of
the stage will reset.

9.12.7.1 Low pass filtering SEMOD172154-37 v4

In order to minimize the influence of the noise signal on the measurement it is possible to
introduce the recursive, low pass filtering of the measured values for S (P, Q). This will make
slower measurement response to the step changes in the measured quantity. Filtering is
performed in accordance with the following recursive formula:

S = k × SOld + (1 - k ) × SCalculated
EQUATION1959 V1 EN-US (Equation 142)

Where
S is a new measured value to be used for the protection function
Sold is the measured value given from the function in previous execution cycle

SCalculated is the new calculated value in the present execution cycle

k is settable parameter by the end user which influence the filter properties

Default value for parameter k is 0.00. With this value the new calculated value is immediately
given out without any filtering (that is, without any additional delay). When k is set to value
bigger than 0, the filtering is enabled. A typical value for k = 0.92 in case of slow operating
functions.

9.12.7.2 Calibration of analog inputs SEMOD172154-55 v2

Measured currents and voltages used in the Power function can be calibrated to get class 0.5
measuring accuracy. This is achieved by amplitude and angle compensation at 5, 30 and 100%

Line distance protection REL670 533


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

of rated current and voltage. The compensation below 5% and above 100% is constant and
linear in between, see example in figure 308.

IEC05000652 V2 EN-US

Figure 308: Calibration curves


The first current and voltage phase in the group signals will be used as reference and the
amplitude and angle compensation will be used for related input signals.

Analog outputs from the function can be used for service values or in the disturbance report.
The active power is provided as MW value: P, or in percent of base power: PPERCENT. The
reactive power is provided as Mvar value: Q, or in percent of base power: QPERCENT.

9.12.8 Technical data SEMOD175160-1 v1

SEMOD175159-2 v9

Table 333: GOPPDOP technical data


Function Range or value Accuracy
Power level (0.0–500.0)% of SBase ±1.0% of Sr at S ≤ Sr
for Step 1 and Step 2 ±1.0% of S at S > Sr

Characteristic angle (-180.0–180.0) degrees ±2.0 degrees


for Step 1 and Step 2
Operate time, start at 0.5 x Sr to 2 x Sr and Min. =10 ms
k=0.000
Max. = 25 ms
Reset time, start at 2 x Sr to 0.5 x Sr and Min. = 35 ms
k=0.000
Max. = 55 ms
Independent time delay to operate for (0.01-6000.00) s ±0.2% or ±40 ms whichever is
Step 1 and Step 2 at 0.5 x Sr to 2 x Sr and greater
k=0.000

534 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

9.13 Broken conductor check BRCPTOC SEMOD171761-1 v3

9.13.1 Identification
SEMOD172362-2 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Broken conductor check BRCPTOC - 46

9.13.2 Functionality SEMOD171805-5 v6

Conventional protection functions cannot detect the broken conductor condition. Broken
conductor check BRCPTOC function, consisting of continuous phase selective current
unsymmetrical check on the line where the IED is connected, gives an alarm or trip at detecting
broken conductors.

9.13.3 Function block SEMOD171906-11 v4

BRCPTOC
I3P* TRIP
BLOCK START
BLKTR

IEC07000034-2-en.vsd
IEC07000034 V2 EN-US

Figure 309: BRCPTOC function block

9.13.4 Signals
PID-3479-INPUTSIGNALS v6

Table 334: BRCPTOC Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Block of trip

PID-3479-OUTPUTSIGNALS v7

Table 335: BRCPTOC Output signals


Name Type Description
TRIP BOOLEAN Operate signal of the protection logic
START BOOLEAN Start signal of the protection logic

Line distance protection REL670 535


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

9.13.5 Settings
PID-3479-SETTINGS v7

Table 336: BRCPTOC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
Iub> 50 - 90 %IM 1 50 Highest and lowest phase currents
difference in % of highest phase
current
IP> 5 - 100 %IB 1 20 Minimum phase current for operation
of Iub> in % of IBase
tOper 0.000 - 60.000 s 0.001 5.000 Operate time delay

Table 337: BRCPTOC Group settings (advanced)


Name Values (Range) Unit Step Default Description
tReset 0.010 - 60.000 s 0.001 0.100 Time delay in reset

Table 338: BRCPTOC Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

9.13.6 Monitored data


PID-3479-MONITOREDDATA v6

Table 339: BRCPTOC Monitored data


Name Type Values (Range) Unit Description
IUNBAL REAL - - Measured unbalance of phase
currents

9.13.7 Operation principle SEMOD171791-5 v5

Broken conductor check (BRCPTOC) detects a broken conductor condition by detecting the
asymmetry between currents in the three phases. The current-measuring elements
continuously measure the three-phase currents.

The current asymmetry signal output START is set on if:

• The difference in currents between the phase with the lowest current and the phase with
the highest current is greater than set percentage Iub> of the highest phase current
• The highest phase current is greater than the minimum setting value IP>.
• The lowest phase current is below 50% of the minimum setting value IP>

The third condition is included to avoid problems in systems involving parallel lines. If a
conductor breaks in one phase on one line, the parallel line will experience an increase in
current in the same phase. This might result in the first two conditions being satisfied. If the
unsymmetrical detection lasts for a period longer than the set time tOper the TRIP output is
activated.

536 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

The simplified logic diagram of the broken conductor check function is shown in figure 310

BRCPTOC is disabled (blocked) if:

• The IED is in TEST status and the function has been blocked from the local HMI test menu
(BlockBRC=Yes).
• The input signal BLOCK is high.

The BLOCK input can be connected to a binary input of the IED in order to receive a block
command from external devices, or can be software connected to other internal functions of
the IED itself to receive a block command from internal functions.

The output trip signal TRIP is a three-phase trip. It can be used to command a trip to the circuit
breaker or for alarm purpose only.

TEST

TEST-ACTIVE
and
Block BRCPTOC=Yes
START

Function Enable
BLOCK or
tOper
TRIP
and t
Unsymmetrical
Current Detection
STI

IL1<50%IP>

IL2<50%IP> or

IL3<50%IP>

IEC09000158-3-en.vsd
IEC09000158 V3 EN-US

Figure 310: Simplified logic diagram for Broken conductor check BRCPTOC

9.13.8 Technical data SEMOD171939-1 v1

SEMOD175200-2 v7

Table 340: BRCPTOC technical data


Function Range or value Accuracy
Minimum phase current for operation (5–100)% of IBase ±1.0% of Ir

Unbalance current operation (50–90)% of maximum current ±1.0% of Ir

Independent operate time delay (0.000-60.000) s ±0.2% or ±45 ms whichever is


greater
Independent reset time delay (0.010-60.000) s ±0.2% or ±30 ms whichever is
greater
Start time at current change from Ir to Min. = 25 ms -
0 Max. = 35 ms

Reset time at current change from 0 to Min. = 5 ms -


Ir Max. = 20 ms

Line distance protection REL670 537


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

9.14 Voltage-restrained time overcurrent protection


VRPVOC GUID-613620B1-4092-4FB6-901D-6810CDD5C615 v4

9.14.1 Identification GUID-7835D582-3FF4-4587-81CE-3B40D543E287 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Voltage-restrained time overcurrent VRPVOC I>/U< 51V
protection

9.14.2 Functionality GUID-935E1CE8-601F-40E2-8D22-2FF68420FADF v6

Voltage-restrained time overcurrent protection (VRPVOC) function can be used as generator


backup protection against short-circuits.

The overcurrent protection feature has a settable current level that can be used either with
definite time or inverse time characteristic. Additionally, it can be voltage controlled/
restrained.

One undervoltage step with definite time characteristic is also available within the function in
order to provide functionality for overcurrent protection with undervoltage seal-in.

9.14.3 Function block GUID-6B4EB1A4-2226-4397-A6FD-14F9DD02B12E v4

VRPVOC
I3P* TRIP
U3P* TROC
BLOCK TRUV
BLKOC START
BLKUV STOC
STUV

IEC12000184-1-en.vsd
IEC12000184 V1 EN-US

Figure 311: VRPVOC function block

9.14.4 Signals
PID-3858-INPUTSIGNALS v7

Table 341: VRPVOC Input signals


Name Type Default Description
I3P GROUP - Three phase group signal for current inputs
SIGNAL
U3P GROUP - Three phase group signal for voltage inputs
SIGNAL
BLOCK BOOLEAN 0 Block of function both stages
BLKOC BOOLEAN 0 Block of voltage restraint overcurrent stage (ANSI 51V)
BLKUV BOOLEAN 0 Block of under voltage function

538 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

PID-3858-OUTPUTSIGNALS v8

Table 342: VRPVOC Output signals


Name Type Description
TRIP BOOLEAN General trip signal
TROC BOOLEAN Trip signal from voltage restrained overcurrent stage
TRUV BOOLEAN Trip signal from undervoltage function
START BOOLEAN General start signal
STOC BOOLEAN Start signal from voltage restrained overcurrent stage
STUV BOOLEAN Start signal from undervoltage function

9.14.5 Settings
PID-3858-SETTINGS v7

Table 343: VRPVOC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
StartCurr 2.0 - 5000.0 %IB 1.0 120.0 Start current level in % of IBase
Characterist ANSI Ext. inv. - - IEC Norm. inv. Time delay curve type for 51V Voltage
ANSI Very inv. restrained overcurrent
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
tDef_OC 0.00 - 6000.00 s 0.01 0.50 Definite time delay for Over Current
k 0.05 - 999.00 - 0.01 1.00 Time multiplier for Inverse Definite
Minimum Time curves
tMin 0.00 - 60.00 s 0.01 0.05 Minimum operate time for Inverse
Definite Minimum Time curve
Operation_UV Off - - Off Operation of under-voltage stage
On (ANSI 27) Off / On
StartVolt 2.0 - 100.0 %UB 0.1 50.0 Voltage for start of under-voltage
stage in % of UBase
tDef_UV 0.00 - 6000.00 s 0.01 1.00 Definite time time delay when used
for Under-Voltage
EnBlkLowV Off - - Off Enable internal low voltage level
On blocking for Under-Voltage
BlkLowVolt 0.0 - 5.0 %UB 0.1 3.0 Internal low voltage level for blocking
of UV in % of UBase

Line distance protection REL670 539


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

Table 344: VRPVOC Group settings (advanced)


Name Values (Range) Unit Step Default Description
VDepMode Step - - Slope Voltage dependent mode OC (step,
Slope slope)
VDepFact 5.0 - 100.0 % 0.1 25.0 Start current level in % of pickup when
U< 25% of UBase
UHighLimit 30.0 - 100.0 %UB 0.1 100.0 Voltage high limit setting in % of
UBase

Table 345: VRPVOC Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

9.14.6 Monitored data


PID-3858-MONITOREDDATA v6

Table 346: VRPVOC Monitored data


Name Type Values (Range) Unit Description
IMAX REAL - A Maximum phase current magnitude
UUMIN REAL - kV Minimum ph-to-ph voltage magnitude

9.14.7 Operation principle

9.14.7.1 Measured quantities GUID-0D511C03-3750-4F61-9555-69DAD96CDC21 v5

The voltage-restrained time overcurrent protection VRPVOC function is always connected to


three-phase current and three-phase voltage input in the configuration tool (ACT), but it will
always measure the maximum of the three-phase currents and the minimum of the three
phase-to-phase voltages. If frequency tracking mode for preprocessing blocks is used, then
the function operates properly in wide frequency range (e.g. 10-90 Hz).

9.14.7.2 Base quantities GUID-08944177-73CF-4FB4-818E-3B7AC4F625EE v4

GlobalBaseSel defines the particular Global Base Values Group where the base quantities of
the function are set. In that Global Base Values Group:

IBase shall be entered as rated phase current of the protected object in primary amperes.

UBase shall be entered as rated phase-to-phase voltage of the protected object in primary kV.

9.14.7.3 Overcurrent protection GUID-7BB29872-EBC1-4628-AFB5-7A15E2EC41A8 v2

The overcurrent step simply compares the magnitude of the measured current quantity with
the set start level. The overcurrent step starts if the magnitude of the measured current
quantity is higher than the set level.

Voltage restraint/control feature GUID-E7C59BAD-47A1-46C2-8929-7E589548045C v3


The overcurrent protection operation is made dependent of a measured voltage quantity. This
means that the start level of the overcurrent step is not constant but decreases with the

540 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

decrease in magnitude of the measured voltage quantity. This feature affects the start current
value of both definite time and inverse time IDMT overcurrent protection; in particular the
overcurrent with IDMT curve operates faster during low voltage conditions. Two different
types of dependencies are available:

• Voltage restrained overcurrent (when setting parameter VDepMode = Slope); the start
level of the overcurrent stage changes according to the Figure 312. The voltage restrained
characteristic is defined by the two points: (0.25*UBase ; VDepFact *StartCurr/100*IBase)
and (UHighLimit/100*UBase; StartCurr/100*IBase). In the first point the factor 0.25 that
multiply UBase cannot be changed.

Start level of the current

StartCurr

VDepFact * StartCurr

0,25 UHighLimit
UBase
IEC10000123-2-en.vsd
IEC10000123 V2 EN-US

Figure 312: Example for start level of the current variation as function of measured
voltage magnitude in Slope mode of operation

• Voltage controlled overcurrent (when setting parameter VDepMode = Step); the start level
of the overcurrent stage changes according to the Figure 313.

Start level of the current

StartCurr

VDepFact * StartCurr

UHighLimit UBase

IEC10000124-2-en.vsd
IEC10000124 V2 EN-US

Figure 313: Example for start level of the current variation as function of measured
voltage magnitude in Step mode of operation

Line distance protection REL670 541


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 506 370-UEN J
Current protection

9.14.7.4 Logic diagram GUID-0A1565A4-74E1-4171-968B-50529AABF192 v2

DEF time
selected
TROC
OR

MaxPhCurr
a STOC
a>b
b

StartCurr
X Inverse

Inverse
Voltage time
control or selected
restraint
feature

MinPh-PhVoltage

IEC10000214-1-en.vsd

IEC10000214 V1 EN-US

Figure 314: Simplified internal logic diagram for overcurrent function

DEF time
selected TRUV

MinPh-phVoltage a
b>a
b STUV
AND
StartVolt

Operation_UV=On

BLKUV

IEC10000213-1-en.vsd

IEC10000213 V1 EN-US

Figure 315: Simplified internal logic diagram for undervoltage function

9.14.7.5 Undervoltage protection GUID-96171DC7-9F8E-47B4-BE0D-E1B9EE214612 v5

The undervoltage step simply compares the magnitude of the lowest measured phase-phase
voltage quantity with the set start level. The undervoltage step starts if the magnitude of the
measured voltage quantity is lower than the set level.

The start signal starts a definite time delay. If the value of the start signal is logical TRUE for
longer than the set time delay, the undervoltage step sets its trip signal to logical TRUE.

This undervoltage functionality together with additional ACT logic can be used to provide
functionality for overcurrent protection with undervoltage seal-in.

542 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 9
Current protection

9.14.8 Technical data


GUID-7EA9731A-8D56-4689-9072-D72D9CDFD795 v8

Table 347: VRPVOC technical data


Function Range or value Accuracy
Start overcurrent (2.0 - 5000.0)% of IBase ±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir

Reset ratio, overcurrent > 95% -


Operate time, start overcurrent at 0 to 2 x Min. = 15 ms -
Iset
Max. = 30 ms
Reset time, start overcurrent at 2 x Iset to Min. = 15 ms -
0
Max. = 30 ms
Operate time, start overcurrent at 0 to 10 Min. = 5 ms -
x Iset Max. = 20 ms

Reset time, start overcurrent at 10 x Iset to Min. = 20 ms -


0 Max. = 35 ms

Independent time delay to operate at 0 to (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is


2 x Iset greater

Inverse time characteristics, 13 curve types See tables 1150 and 1151
see tables 1150 and 1151
Minimum operate time for inverse time (0.00 - 60.00) s ±0.2% or ±35 ms whichever is
characteristics greater
High voltage limit, voltage dependent (30.0 - 100.0)% of UBase ±1.0% of Ur
operation
Start undervoltage (2.0 - 100.0)% of UBase ±0.5% of Ur

Reset ratio, undervoltage < 105% -


Operate time start undervoltage at 2 x Min. = 15 ms -
Uset to 0
Max. = 30 ms
Reset time start undervoltage at 0 to 2 x Min. = 15 ms -
Uset
Max. = 30 ms
Independent time delay to operate, (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is
undervoltage at 2 x Uset to 0 greater

Internal low voltage blocking (0.0 - 5.0)% of UBase ±0.25% of Ur

Overcurrent: -
Critical impulse time 10 ms typically at 0 to 2 x Iset
Impulse margin time 15 ms typically
Undervoltage: -
Critical impulse time 10ms typically at 2 x Uset to 0
Impulse margin time 15 ms typically

Line distance protection REL670 543


Technical manual
© Copyright 2017 ABB. All rights reserved
544
1MRK 506 370-UEN J Section 10
Voltage protection

Section 10 Voltage protection


10.1 Two step undervoltage protection UV2PTUV IP14544-1 v3

10.1.1 Identification
M16876-1 v7

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Two step undervoltage protection UV2PTUV 27

3U<

V2 EN-US
SYMBOL-R-2U-GREATER-THAN

10.1.2 Functionality M13789-3 v12

Undervoltages can occur in the power system during faults or abnormal conditions. The two-
step undervoltage protection function (UV2PTUV) can be used to open circuit breakers to
prepare for system restoration at power outages or as a long-time delayed back-up to the
primary protection.

UV2PTUV has two voltage steps, each with inverse or definite time delay.

It has a high reset ratio to allow settings close to the system service voltage.

10.1.3 Function block M13794-3 v6

UV2PTUV
U3P* TRIP
BLOCK TR1
BLKTR1 TR1L1
BLKST1 TR1L2
BLKTR2 TR1L3
BLKST2 TR2
TR2L1
TR2L2
TR2L3
START
ST1
ST1L1
ST1L2
ST1L3
ST2
ST2L1
ST2L2
ST2L3

IEC06000276-2-en.vsd
IEC06000276 V2 EN-US

Figure 316: UV2PTUV function block

Line distance protection REL670 545


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 506 370-UEN J
Voltage protection

10.1.4 Signals
PID-3586-INPUTSIGNALS v7

Table 348: UV2PTUV Input signals


Name Type Default Description
U3P GROUP - Three phase voltages
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR1 BOOLEAN 0 Block of operate signal, step 1
BLKST1 BOOLEAN 0 Block of step 1
BLKTR2 BOOLEAN 0 Block of operate signal, step 2
BLKST2 BOOLEAN 0 Block of step 2

PID-3586-OUTPUTSIGNALS v7

Table 349: UV2PTUV Output signals


Name Type Description
TRIP BOOLEAN Trip
TR1 BOOLEAN Common trip signal from step1
TR1L1 BOOLEAN Trip signal from step1 phase L1
TR1L2 BOOLEAN Trip signal from step1 phase L2
TR1L3 BOOLEAN Trip signal from step1 phase L3
TR2 BOOLEAN Common trip signal from step2
TR2L1 BOOLEAN Trip signal from step2 phase L1
TR2L2 BOOLEAN Trip signal from step2 phase L2
TR2L3 BOOLEAN Trip signal from step2 phase L3
START BOOLEAN General start signal
ST1 BOOLEAN Common start signal from step1
ST1L1 BOOLEAN Start signal from step1 phase L1
ST1L2 BOOLEAN Start signal from step1 phase L2
ST1L3 BOOLEAN Start signal from step1 phase L3
ST2 BOOLEAN Common start signal from step2
ST2L1 BOOLEAN Start signal from step2 phase L1
ST2L2 BOOLEAN Start signal from step2 phase L2
ST2L3 BOOLEAN Start signal from step2 phase L3

546 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 10
Voltage protection

10.1.5 Settings
PID-3586-SETTINGS v7

Table 350: UV2PTUV Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
OperationStep1 Off - - On Enable execution of step 1
On
Characterist1 Definite time - - Definite time Selection of time delay curve type for
Inverse curve A step 1
Inverse curve B
Prog. inv. curve
OpMode1 1 out of 3 - - 1 out of 3 Number of phases required for op (1
2 out of 3 of 3, 2 of 3, 3 of 3) from step 1
3 out of 3
U1< 1.0 - 100.0 %UB 0.1 70.0 Voltage setting/start val (DT & IDMT)
in % of UBase, step 1
t1 0.00 - 6000.00 s 0.01 5.00 Definitive time delay of step 1
t1Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse
curves for step 1
k1 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time
delay for step 1
IntBlkSel1 Off - - Off Internal (low level) blocking mode,
Block of trip step 1
Block all
IntBlkStVal1 1 - 50 %UB 1 20 Voltage setting for internal blocking in
% of UBase, step 1
tBlkUV1 0.000 - 60.000 s 0.001 0.000 Time delay of internal (low level)
blocking for step 1
HystAbs1 0.0 - 50.0 %UB 0.1 0.5 Absolute hysteresis in % of UBase,
step 1
OperationStep2 Off - - On Enable execution of step 2
On
Characterist2 Definite time - - Definite time Selection of time delay curve type for
Inverse curve A step 2
Inverse curve B
Prog. inv. curve
OpMode2 1 out of 3 - - 1 out of 3 Number of phases required for op (1
2 out of 3 of 3, 2 of 3, 3 of 3) from step 2
3 out of 3
U2< 1.0 - 100.0 %UB 0.1 50.0 Voltage setting/start val (DT & IDMT)
in % of UBase, step 2
t2 0.000 - 60.000 s 0.001 5.000 Definitive time delay of step 2
t2Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse
curves for step 2
k2 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time
delay for step 2
IntBlkSel2 Off - - Off Internal (low level) blocking mode,
Block of trip step 2
Block all
Table continues on next page

Line distance protection REL670 547


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 506 370-UEN J
Voltage protection

Name Values (Range) Unit Step Default Description


IntBlkStVal2 1 - 50 %UB 1 20 Voltage setting for internal blocking in
% of UBase, step 2
tBlkUV2 0.000 - 60.000 s 0.001 0.000 Time delay of internal (low level)
blocking for step 2
HystAbs2 0.0 - 50.0 %UB 0.1 0.5 Absolute hysteresis in % of UBase,
step 2

Table 351: UV2PTUV Group settings (advanced)


Name Values (Range) Unit Step Default Description
tReset1 0.000 - 60.000 s 0.001 0.025 Reset time delay used in IEC Definite
Time curve step 1
ResetTypeCrv1 Instantaneous - - Instantaneous Selection of used IDMT reset curve
Frozen timer type for step 1
Linearly
decreased
tIReset1 0.000 - 60.000 s 0.001 0.025 Time delay in IDMT reset (s), step 1
ACrv1 0.005 - 200.000 - 0.001 1.000 Parameter A for customer
programmable curve for step 1
BCrv1 0.50 - 100.00 - 0.01 1.00 Parameter B for customer
programmable curve for step 1
CCrv1 0.0 - 1.0 - 0.1 0.0 Parameter C for customer
programmable curve for step 1
DCrv1 0.000 - 60.000 - 0.001 0.000 Parameter D for customer
programmable curve for step 1
PCrv1 0.000 - 3.000 - 0.001 1.000 Parameter P for customer
programmable curve for step 1
CrvSat1 0 - 100 % 1 0 Tuning param for prog. under voltage
IDMT curve, step 1
tReset2 0.000 - 60.000 s 0.001 0.025 Reset time delay used in IEC Definite
Time curve step 2
ResetTypeCrv2 Instantaneous - - Instantaneous Selection of used IDMT reset curve
Frozen timer type for step 2
Linearly
decreased
tIReset2 0.000 - 60.000 s 0.001 0.025 Time delay in IDMT reset (s), step 2
ACrv2 0.005 - 200.000 - 0.001 1.000 Parameter A for customer
programmable curve for step 2
BCrv2 0.50 - 100.00 - 0.01 1.00 Parameter B for customer
programmable curve for step 2
CCrv2 0.0 - 1.0 - 0.1 0.0 Parameter C for customer
programmable curve for step 2
DCrv2 0.000 - 60.000 - 0.001 0.000 Parameter D for customer
programmable curve for step 2
PCrv2 0.000 - 3.000 - 0.001 1.000 Parameter P for customer
programmable curve for step 2
CrvSat2 0 - 100 % 1 0 Tuning param for prog. under voltage
IDMT curve, step 2

548 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 10
Voltage protection

Table 352: UV2PTUV Non group settings (basic)


Name Values (Range) Unit Step Default Description
ConnType PhN DFT - - PhN DFT Group selector for connection type
PhPh RMS
PhN RMS
PhPh DFT
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

10.1.6 Monitored data


PID-3586-MONITOREDDATA v6

Table 353: UV2PTUV Monitored data


Name Type Values (Range) Unit Description
UL1 REAL - kV Voltage in phase L1
UL2 REAL - kV Voltage in phase L2
UL3 REAL - kV Voltage in phase L3

10.1.7 Operation principle M15326-3 v9

Two-step undervoltage protection (UV2PTUV) is used to detect low power system voltage. If
one, two or three phase voltages decrease below the set value, a corresponding START signal
is generated. The parameters OpMode1 and OpMode2 influence the requirements to activate
the START outputs: the measured voltages 1 out of 3, 2 out of 3, or 3 out of 3 have to be lower
than the corresponding set point to issue the corresponding START signal.

UV2PTUV has two voltage-measuring steps with separate time delays. If the voltage remains
below the set value for the chosen time delay, the corresponding trip signal is issued. To avoid
an unwanted trip due to the disconnection of the related high-voltage equipment, a voltage-
controlled blocking of the function is available: if the voltage is lower than the set blocking
level, the function is blocked and no START or TRIP signal is generated. The time delay
characteristic is individually chosen for each step and can be either definite time delay or
inverse time delay.

To avoid oscillations of the output START signal, a hysteresis has been included.

10.1.7.1 Measurement principle M15326-6 v7

Depending on the value of the ConnType parameter, UV2PTUV can be set to measure phase-
to-earth fundamental value, phase-to-phase fundamental value, phase-to-earth true RMS value
or phase-to-phase true RMS value, and compares it against the set values, U1< and U2<. The
voltage-related settings are made in percentage of the base voltage which is set in kV phase-
to-phase voltage. This means operation for phase-to-earth voltage under:

UBase(kV )
U (%) ·
3
EQUATION1429 V3 EN-US (Equation 143)

and operation for phase-to-phase voltage under:

Line distance protection REL670 549


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 506 370-UEN J
Voltage protection

U < (%) × UBase(kV)


EQUATION1990 V1 EN-US (Equation 144)

When the phase-to-earth voltage measurement is selected, the function


automatically introduces division of the base value by the square root of three.

10.1.7.2 Time delay M15326-10 v12

The time delay for the two steps can be either definite time delay (DT) or inverse time delay
(IDMT). For the inverse time delay three different modes are available:

• inverse curve A
• inverse curve B
• customer programmable inverse curve

The type A curve is described as:

k
t=
æ Un < -U ö
ç ÷
è Un < ø
EQUATION1431 V2 EN-US (Equation 145)

where:
Un< Set value for step 1 and step 2
U Measured voltage

The type B curve is described as:

k × 480
t= 2.0
+ 0.055
æ Un < - U ö
ç 32 × - 0.5 ÷
è Un < ø
EQUATION1432 V2 EN-US (Equation 146)

The customer programmable curve can be created as:

é ù
ê ú
ê k×A ú
t=ê pú
+D
ê æ Un < - U ö ú
êçB × -C÷ ú
ëè Un < ø û
EQUATION1433 V2 EN-US (Equation 147)

When the denominator in the expression is equal to zero the time delay will be infinity. There
will be an undesired discontinuity. Therefore a tuning parameter CrvSatn is set to compensate
for this phenomenon. In the voltage interval Un< down to Un< · (1.0 – CrvSatn/100) the used

550 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 10
Voltage protection

voltage will be: Un< · (1.0 – CrvSatn/100). If the programmable curve is used this parameter
must be calculated so that:

CrvSatn
B× -C > 0
100
EQUATION1435 V1 EN-US (Equation 148)

The lowest voltage is always used for the inverse time delay integration. The details of the
different inverse time characteristics are shown in section "Inverse characteristics".

Voltage

UL1
UL2
UL3

IDMT Voltage

Time

IEC12000186-1-en.vsd

IEC12000186 V1 EN-US

Figure 317: Voltage used for the inverse time characteristic integration
Trip signal issuing requires that the undervoltage condition continues for at least the user set
time delay. This time delay is set by the parameter t1 and t2 for definite time mode (DT) and by
some special voltage level dependent time curves for the inverse time mode (IDMT). If the start
condition, with respect to the measured voltage, ceases during the delay time, and is not
fulfilled again within a user-defined reset time (tReset1 and tReset2 for the definite time and
tIReset1 and tIReset2 pickup for the inverse time) the corresponding start output is reset.
After leaving the hysteresis area, the start condition must be fulfilled again and it is not
sufficient for the signal to only return back to the hysteresis area. For the undervoltage
function the IDMT reset time is constant and does not depend on the voltage fluctuations
during the drop-off period. However, there are three ways to reset the timer: the timer is reset
instantaneously, the timer value is frozen during the reset time, or the timer value is linearly
decreased during the reset time. See figure 318 and figure 319.

Line distance protection REL670 551


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 506 370-UEN J
Voltage protection

tIReset1
Voltage Measured
START Voltage
HystAbs1
TRIP

U1<

Time

START

TRIP

Time
Integrator Frozen Timer

Time
Linearly
Instantaneous
decreased IEC05000010-5-en.vsdx

IEC05000010 V5 EN-US

Figure 318: Voltage profile not causing a reset of the START signal for step 1, and inverse time delay at
different reset types

552 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 10
Voltage protection

tIReset1
Voltage
START
START
HystAbs1 Measured Voltage
TRIP

U1<

Time

START t

TRIP

Time
Integrator Frozen Timer

Time
Instantaneous Linearly decreased
IEC05000011-en-4.vsdx

IEC05000011 V4 EN-US

Figure 319: Voltage profile causing a reset of the START signal for step 1, and inverse time delay at
different reset types
Definite timer delay

When definite time delay is selected the function will operate as shown in figure 320. Detailed
information about individual stage reset/operation behavior is shown in figure 321 and figure
322 respectively. Note that by setting tResetn = 0.0s, instantaneous reset of the definite time
delayed stage is ensured.

Line distance protection REL670 553


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 506 370-UEN J
Voltage protection

ST1

U t1
a tReset1
TR1
t
a<b t
U1< R
b
AND

IEC09000785-3-en.vsd
IEC09000785 V3 EN-US

Figure 320: Logic diagram for step 1, DT operation

U1<

ST1

TR1

tReset1

t1

IEC10000039-3-en.vsd
IEC10000039 V3 EN-US

Figure 321: Example for Definite Time Delay stage1 reset

U1<

ST1

TR1

tReset1

t1

IEC10000040-3-en.vsd
IEC10000040 V3 EN-US

Figure 322: Example for Definite Time Delay stage1 operation

554 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 10
Voltage protection

10.1.7.3 Blocking M15326-20 v8

It is possible to block Two step undervoltage protection UV2PTUV partially or completely, by


binary input signals or by parameter settings, where:

BLOCK: blocks all outputs


BLKTR1: blocks all trip outputs of step 1
BLKST1: blocks all start and trip outputs related to step 1
BLKTR2: blocks all trip outputs of step 2
BLKST2: blocks all start and trip outputs related to step 2

If the measured voltage level decreases below the setting of IntBlkStVal1, either the trip output
of step 1, or both the trip and the START outputs of step 1, are blocked. The characteristic of
the blocking is set by the IntBlkSel1 parameter. This internal blocking can also be set to Off
resulting in no voltage based blocking. Corresponding settings and functionality are valid also
for step 2.

In case of disconnection of the high voltage component the measured voltage will get very
low. The event will START both the under voltage function and the blocking function, as seen in
figure 323. The delay of the blocking function must be set less than the time delay of under
voltage function.

U Disconnection

Normal voltage

U1<

U2<

tBlkUV1 <
t1,t1Min
IntBlkStVal1
tBlkUV2 <
t2,t2Min
IntBlkStVal2

Time

Block step 1

Block step 2
en05000466.vsd
IEC05000466 V1 EN-US

Figure 323: Blocking function

Line distance protection REL670 555


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 506 370-UEN J
Voltage protection

10.1.7.4 Design M15326-35 v9

The voltage measuring elements continuously measure the three phase-to-neutral voltages or
the three phase-to-phase voltages. Recursive fourier filters or true RMS filters of input voltage
signals are used. The voltages are individually compared to the set value, and the lowest
voltage is used for the inverse time characteristic integration. A special logic is included to
achieve the 1 out of 3, 2 out of 3 and 3 out of 3 criteria to fulfill the START condition. The design
of Two step undervoltage protection UV2PTUV is schematically shown in Figure 324.

UL1 Comparator ST1L1


UL1 < U1< Voltage Phase Phase 1
Selector
OpMode1 ST1L2
UL2 Comparator Phase 2
1 out of 3
UL2 < U1< 2 out of 3 ST1L3
3 out of 3 Phase 3 Start t1
UL3 Comparator t1Reset
UL3 < U1< IntBlkStVal1 &
OR ST1
Trip
Output
START Logic TR1L1

Step 1 TR1L2
Time integrator TRIP
MinVoltSelector tIReset1
ResetTypeCrv1 TR1L3

TR1
OR

Comparator ST2L1
UL1 < U2< Voltage Phase Phase 1
Selector
OpMode2 ST2L2
Comparator Phase 2
UL2 < U2< 1 out of 3
2 out of 3 Start t2 ST2L3
3 out of 3 Phase 3 t2Reset
Comparator IntBlkStVal2 &
UL3 < U2< Trip ST2
Output OR
Logic
START TR2L1

Step 2
TR2L2
Time integrator TRIP
MinVoltSelector tIReset2
ResetTypeCrv2 TR2L3

TR2
OR
START
OR

TRIP
OR

IEC05000834-2-en.vsd
IEC05000834 V2 EN-US

Figure 324: Schematic design of Two step undervoltage protection UV2PTUV

556 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 10
Voltage protection

10.1.8 Technical data IP13001-1 v1

M13290-1 v15

Table 354: UV2PTUV technical data


Function Range or value Accuracy
Operate voltage, low and high step (1.0–100.0)% of UBase ±0.5% of Ur

Absolute hysteresis (0.0–50.0)% of UBase ±0.5% of Ur

Internal blocking level, step 1 and step (1–50)% of UBase ±0.5% of Ur


2
Inverse time characteristics for step 1 - See table 1159
and step 2, see table 1159
Definite time delay, step 1 at 1.2 x Uset (0.00-6000.00) s ±0.2% or ±40ms whichever is
to 0 greater

Definite time delay, step 2 at 1.2 x Uset (0.000-60.000) s ±0.2% or ±40ms whichever is
to 0 greater

Minimum operate time, inverse (0.000–60.000) s ±0.5% or ±40ms whichever is


characteristics greater
Operate time, start at 2 x Uset to 0 Min. = 15 ms -
Max. = 30 ms
Reset time, start at 0 to 2 x Uset Min. = 15 ms -
Max. = 30 ms
Operate time, start at 1.2 x Uset to 0 Min. = 5 ms -
Max. = 25 ms
Reset time, start at 0 to 1.2 x Uset Min. = 15 ms -
Max. = 35 ms
Critical impulse time 5 ms typically at 1.2 x Uset to -
0
Impulse margin time 15 ms typically -

10.2 Two step overvoltage protection OV2PTOV IP14545-1 v3

10.2.1 Identification
M17002-1 v8

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Two step overvoltage protection OV2PTOV 59

3U>

SYMBOL-C-2U-SMALLER-THAN V2 EN-US

10.2.2 Functionality OV2PTOV M13798-3 v16

Overvoltages may occur in the power system during abnormal conditions such as sudden
power loss, tap changer regulating failures, and open line ends on long lines.

Two step overvoltage protection (OV2PTOV) function can be used to detect open line ends,
normally then combined with a directional reactive over-power function to supervise the

Line distance protection REL670 557


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 506 370-UEN J
Voltage protection

system voltage. When triggered, the function will cause an alarm, switch in reactors, or switch
out capacitor banks.

OV2PTOV has two voltage steps, each of them with inverse or definite time delayed.

OV2PTOV has a high reset ratio to allow settings close to system service voltage.

10.2.3 Function block M13803-3 v6

OV2PTOV
U3P* TRIP
BLOCK TR1
BLKTR1 TR1L1
BLKST1 TR1L2
BLKTR2 TR1L3
BLKST2 TR2
TR2L1
TR2L2
TR2L3
START
ST1
ST1L1
ST1L2
ST1L3
ST2
ST2L1
ST2L2
ST2L3

IEC06000277-2-en.vsd
IEC06000277 V2 EN-US

Figure 325: OV2PTOV function block

10.2.4 Signals
PID-3535-INPUTSIGNALS v7

Table 355: OV2PTOV Input signals


Name Type Default Description
U3P GROUP - Group signal for three phase voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR1 BOOLEAN 0 Block of operate signal, step 1
BLKST1 BOOLEAN 0 Block of step 1
BLKTR2 BOOLEAN 0 Block of operate signal, step 2
BLKST2 BOOLEAN 0 Block of step 2

PID-3535-OUTPUTSIGNALS v7

Table 356: OV2PTOV Output signals


Name Type Description
TRIP BOOLEAN Trip
TR1 BOOLEAN Common trip signal from step1
TR1L1 BOOLEAN Trip signal from step1 phase L1
TR1L2 BOOLEAN Trip signal from step1 phase L2
TR1L3 BOOLEAN Trip signal from step1 phase L3
TR2 BOOLEAN Common trip signal from step2
TR2L1 BOOLEAN Trip signal from step2 phase L1
Table continues on next page

558 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 10
Voltage protection

Name Type Description


TR2L2 BOOLEAN Trip signal from step2 phase L2
TR2L3 BOOLEAN Trip signal from step2 phase L3
START BOOLEAN General start signal
ST1 BOOLEAN Common start signal from step1
ST1L1 BOOLEAN Start signal from step1 phase L1
ST1L2 BOOLEAN Start signal from step1 phase L2
ST1L3 BOOLEAN Start signal from step1 phase L3
ST2 BOOLEAN Common start signal from step2
ST2L1 BOOLEAN Start signal from step2 phase L1
ST2L2 BOOLEAN Start signal from step2 phase L2
ST2L3 BOOLEAN Start signal from step2 phase L3

10.2.5 Settings
PID-3535-SETTINGS v7

Table 357: OV2PTOV Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
OperationStep1 Off - - On Enable execution of step 1
On
Characterist1 Definite time - - Definite time Selection of time delay curve type for
Inverse curve A step 1
Inverse curve B
Inverse curve C
Prog. inv. curve
OpMode1 1 out of 3 - - 1 out of 3 Number of phases required for op (1
2 out of 3 of 3, 2 of 3, 3 of 3) from step 1
3 out of 3
U1> 1.0 - 200.0 %UB 0.1 120.0 Voltage setting/start val (DT & IDMT)
in % of UBase, step 1
t1 0.00 - 6000.00 s 0.01 5.00 Definitive time delay of step 1
t1Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse
curves for step 1
k1 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time
delay for step 1
HystAbs1 0.0 - 50.0 %UB 0.1 0.5 Absolute hysteresis in % of UBase,
step 1
OperationStep2 Off - - On Enable execution of step 2
On
Characterist2 Definite time - - Definite time Selection of time delay curve type for
Inverse curve A step 2
Inverse curve B
Inverse curve C
Prog. inv. curve
OpMode2 1 out of 3 - - 1 out of 3 Number of phases required for op (1
2 out of 3 of 3, 2 of 3, 3 of 3) from step 2
3 out of 3
U2> 1.0 - 200.0 %UB 0.1 150.0 Voltage setting/start val (DT & IDMT)
in % of UBase, step 2
Table continues on next page

Line distance protection REL670 559


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 506 370-UEN J
Voltage protection

Name Values (Range) Unit Step Default Description


t2 0.000 - 60.000 s 0.001 5.000 Definitive time delay of step 2
t2Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse
curves for step 2
k2 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time
delay for step 2
HystAbs2 0.0 - 50.0 %UB 0.1 0.5 Absolute hysteresis in % of UBase,
step 2

Table 358: OV2PTOV Group settings (advanced)


Name Values (Range) Unit Step Default Description
tReset1 0.000 - 60.000 s 0.001 0.025 Reset time delay used in IEC Definite
Time curve step 1
ResetTypeCrv1 Instantaneous - - Instantaneous Selection of used IDMT reset curve
Frozen timer type for step 1
Linearly
decreased
tIReset1 0.000 - 60.000 s 0.001 0.025 Time delay in IDMT reset (s), step 1
ACrv1 0.005 - 200.000 - 0.001 1.000 Parameter A for customer
programmable curve for step 1
BCrv1 0.50 - 100.00 - 0.01 1.00 Parameter B for customer
programmable curve for step 1
CCrv1 0.0 - 1.0 - 0.1 0.0 Parameter C for customer
programmable curve for step 1
DCrv1 0.000 - 60.000 - 0.001 0.000 Parameter D for customer
programmable curve for step 1
PCrv1 0.000 - 3.000 - 0.001 1.000 Parameter P for customer
programmable curve for step 1
CrvSat1 0 - 100 % 1 0 Tuning param for prog. over voltage
IDMT curve, step 1
tReset2 0.000 - 60.000 s 0.001 0.025 Reset time delay used in IEC Definite
Time curve step 2
ResetTypeCrv2 Instantaneous - - Instantaneous Selection of used IDMT reset curve
Frozen timer type for step 2
Linearly
decreased
tIReset2 0.000 - 60.000 s 0.001 0.025 Time delay in IDMT reset (s), step 2
ACrv2 0.005 - 200.000 - 0.001 1.000 Parameter A for customer
programmable curve for step 2
BCrv2 0.50 - 100.00 - 0.01 1.00 Parameter B for customer
programmable curve for step 2
CCrv2 0.0 - 1.0 - 0.1 0.0 Parameter C for customer
programmable curve for step 2
DCrv2 0.000 - 60.000 - 0.001 0.000 Parameter D for customer
programmable curve for step 2
PCrv2 0.000 - 3.000 - 0.001 1.000 Parameter P for customer
programmable curve for step 2
CrvSat2 0 - 100 % 1 0 Tuning param for prog. over voltage
IDMT curve, step 2

560 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 10
Voltage protection

Table 359: OV2PTOV Non group settings (basic)


Name Values (Range) Unit Step Default Description
ConnType PhN DFT - - PhN DFT Group selector for connection type
PhPh DFT
PhN RMS
PhPh RMS
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

10.2.6 Monitored data


PID-3535-MONITOREDDATA v6

Table 360: OV2PTOV Monitored data


Name Type Values (Range) Unit Description
UL1 REAL - kV Voltage in phase L1
UL2 REAL - kV Voltage in phase L2
UL3 REAL - kV Voltage in phase L3

10.2.7 Operation principle M15330-3 v11

Two step overvoltage protection OV2PTOV is used to detect high power system voltage.
OV2PTOV has two steps with separate time delays. If one-, two- or three-phase voltages
increase above the set value, a corresponding START signal is issued. OV2PTOV can be set to
START/TRIP, based on 1 out of 3, 2 out of 3 or 3 out of 3 of the measured voltages, being above
the set point. If the voltage remains above the set value for a time period corresponding to the
chosen time delay, the corresponding trip signal is issued.

The time delay characteristic is individually chosen for the two steps, and can be either
definite time or inverse time delayed.

The voltage related settings are made in percent of the global set base voltage UBase, which is
set in kV, phase-to-phase.

OV2PTOV can be set to measure phase-to-earth fundamental value, phase-to-phase


fundamental value, phase-to-earth RMS value or phase-to-phase RMS value. The choice of
measuring is done by the parameter ConnType.

The setting of the analog inputs are given as primary phase-to-earth or phase-to-phase
voltage. OV2PTOV will operate if the voltage gets higher than the set percentage of the set
base voltage UBase. This means operation for phase-to-earth voltage over:

U > (%) × UBase( kV )


3
EQUATION1434 V1 EN-US (Equation 149)

and operation for phase-to-phase voltage over:

U > (%) × UBase(kV)


EQUATION1993 V1 EN-US (Equation 150)

Line distance protection REL670 561


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 506 370-UEN J
Voltage protection

When phase-to-earth voltage measurement is selected the function


automatically introduces division of the base value by the square root of three.

10.2.7.1 Measurement principle M15330-6 v6

All the three voltages are measured continuously, and compared with the set values, U1> for
Step 1 and U2> for Step 2. The parameters OpMode1 and OpMode2 influence the requirements
to activate the START outputs. Either 1 out of 3, 2 out of 3 or 3 out of 3 measured voltages have
to be higher than the corresponding set point to issue the corresponding START signal.

To avoid oscillations of the output START signal, a hysteresis is included.

10.2.7.2 Time delay M15330-10 v11

The time delay for the two steps can be either definite time delay (DT) or inverse time delay
(IDMT). For the inverse time delay four different modes are available:

• inverse curve A
• inverse curve B
• inverse curve C
• customer programmable inverse curve

The type A curve is described as:

k
t=
æ U - Un > ö
ç ÷
è Un > ø
IECEQUATION2422 V1 EN-US (Equation 151)

where:
Un> Set value for step 1 and step 2
U Measured voltage

The type B curve is described as:

k  480
t 2.0
 0.035
 U  Un  
 32   0.5 
 Un  

IECEQUATION2423 V2 EN-US (Equation 152)

The type C curve is described as:

k × 480
t= 3.0
+ 0.035
æ U - Un > ö
ç 32 × - 0.5 ÷
è U n > ø
IECEQUATION2425 V1 EN-US (Equation 153)

562 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 10
Voltage protection

The customer programmable curve is defined by the below equation, where A, B, C, D, k and p
are settings:

k×A
t= p
+D
æ U -Un > ö
çB× -C÷
è Un > ø
EQUATION1439 V2 EN-US (Equation 154)

When the denominator in the expression is equal to zero the time delay will be infinity. There
will be an undesired discontinuity. Therefore, a tuning parameter CrvSatn is set to compensate
for this phenomenon. In the voltage interval Un> up to Un> · (1.0 + CrvSatn/100) the used
voltage will be: Un> · (1.0 + CrvSatn/100). If the programmable curve is used this parameter
must be calculated so that:

CrvSatn
B× -C > 0
100
EQUATION1435 V1 EN-US (Equation 155)

The highest phase (or phase-to-phase) voltage is always used for the inverse time delay
integration, see figure 326. The details of the different inverse time characteristics are shown
in section "Inverse characteristics".

Voltage
IDMT Voltage

UL1
UL2
UL3

Time

IEC05000016-2-en.vsd
IEC05000016 V2 EN-US

Figure 326: Voltage used for the inverse time characteristic integration
Operation of the trip signal requires that the overvoltage condition continues for at least the
user set time delay. This time delay is set by the parameter t1 and t2 for definite time mode
(DT) and by selected voltage level dependent time curves for the inverse time mode (IDMT). If
the START condition, with respect to the measured voltage ceases during the delay time, and
is not fulfilled again within a user defined reset time (tReset1 and tReset2 for the definite time
and tIReset1 and tIReset2 for the inverse time) the corresponding START output is reset, after
that the defined reset time has elapsed. Here it should be noted that after leaving the
hysteresis area, the START condition must be fulfilled again and it is not sufficient for the
signal to only return back to the hysteresis area. The hysteresis value for each step is settable
HystAbsn (where n means either 1 or 2 respectively) to allow a high and accurate reset of the
function. For OV2PTOV the IDMT reset time is constant and does not depend on the voltage
fluctuations during the drop-off period. However, there are three ways to reset the timer:

Line distance protection REL670 563


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 506 370-UEN J
Voltage protection

either the timer is reset instantaneously, or the timer value is frozen during the reset time, or
the timer value is linearly decreased during the reset time.

tIReset1
Voltage
START
TRIP

U1>

HystAbs1 Measured
Voltage

Time

START t

TRIP

Time
Integrator Linearly decreased
Frozen Timer
t

Instantaneous Time
IEC09000055‐3‐en.vsdx

IEC09000055 V3 EN-US

Figure 327: Voltage profile not causing a reset of the START signal for step 1, and inverse time delay at
different reset types

564 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 10
Voltage protection

tIReset1
Voltage
START TRIP
START HystAbs1

U1>
Measured
Voltage

Time

START t

TRIP

Time
Integrator Frozen Timer

Time
Linearly
Instantaneous decreased
IEC05000020‐4‐en.vsdx

IEC05000020 V4 EN-US

Figure 328: Voltage profile causing a reset of the START signal for step 1, and inverse time delay at
different reset types
Definite time delay

When definite time delay is selected, the function will operate as shown in figure 329. Detailed
information about individual stage reset/operation behavior is shown in figure 330 and figure
331 respectively. Note that by setting tResetn = 0.0s (where n means either 1 or 2 respectively),
instantaneous reset of the definite time delayed stage is ensured.

Line distance protection REL670 565


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 506 370-UEN J
Voltage protection

ST1

U tReset1 t1
a
a>b t t
TR1
U1>
b AND
OFF ON
Delay Delay

IEC10000100-2-en.vsd
IEC10000100 V2 EN-US

Figure 329: Logic diagram for step 1, definite time delay, DT operation

U1>

START

TRIP

tReset1

t1

IEC10000037-2-en.vsd
IEC10000037 V2 EN-US

Figure 330: Example for step 1, Definite Time Delay stage 1 reset

U1>

START

TRIP

tReset1

t1

IEC10000038-2-en.vsd
IEC10000038 V2 EN-US

Figure 331: Example for Definite Time Delay stage 1 operation

566 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 10
Voltage protection

10.2.7.3 Blocking M15330-20 v8

It is possible to block Two step overvoltage protection OV2PTOV partially or completely, by


binary input signals where:

BLOCK: blocks all outputs


BLKTR1: blocks all trip outputs of step 1
BLKST1: blocks all start and trip outputs related to step 1
BLKTR2: blocks all trip outputs of step 2
BLKST2: blocks all start and trip outputs related to step 2

10.2.7.4 Design M15330-34 v8

The voltage measuring elements continuously measure the three phase-to-earth voltages or
the three phase-to-phase voltages. Recursive Fourier filters or true RMS filters of input voltage
signals are used. The phase voltages are individually compared to the set value, and the
highest voltage is used for the inverse time characteristic integration. A special logic is
included to achieve the 1 out of 3, 2 out of 3 or 3 out of 3 criteria to fulfill the START condition.
The design of Two step overvoltage protection (OV2PTOV) is schematically described in
figure 332.

Line distance protection REL670 567


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 506 370-UEN J
Voltage protection

UL1 Comparator ST1L1


UL1 > U1> Phase 1
Voltage Phase
Selector ST1L2
UL2 Comparator OpMode1 Phase 2
UL2 > U1> 1 out of 3
Start ST1L3
2 out of 3
3 out of 3 Phase 3 t1
UL3 Comparator t1Reset
UL3 > U1> & ST1
OR
Trip
START Output TR1L1
Logic

Time integrator Step 1 TR1L2


TRIP
MaxVoltSelect tIreset1
ResetTypeCrv1 TR1L3

OR TR1

Comparator ST2L1
UL1 > U2> Phase 1
Voltage Phase
Selector ST2L2
Comparator OpMode2 Phase 2
UL2 > U2> 1 out of 3
Start ST2L3
2 out of 3
Phase 3 t2
3 out of 3
Comparator t2Reset
UL3 > U2> & ST2
OR
Trip
START Output TR2L1
Logic

Time integrator Step 2 TR2L2


MaxVoltSelect tIreset2 TRIP
ResetTypeCrv2 TR2L3

TR2
OR

START
OR

TRIP
OR

IEC05000013-2-en.vsd

IEC05000013-WMF V2 EN-US

Figure 332: Schematic design of Two step overvoltage protection OV2PTOV

10.2.8 Technical data IP13013-1 v1

M13304-1 v14

Table 361: OV2PTOV technical data


Function Range or value Accuracy
Operate voltage, step 1 and 2 (1.0-200.0)% of UBase ±0.5% of Ur at U ≤ Ur
±0.5% of U at U > Ur

Absolute hysteresis (0.0–50.0)% of UBase ±0.5% of Ur at U ≤ Ur


±0.5% of U at U > Ur

Inverse time characteristics for steps 1 - See table 1158


and 2, see table 1158
Definite time delay, low step (step 1) at (0.00 - 6000.00) s ±0.2% or ±45 ms whichever is
0 to 1.2 x Uset greater

Definite time delay, high step (step 2) at (0.000-60.000) s ±0.2% or ±45 ms whichever is
0 to 1.2 x Uset greater

Table continues on next page

568 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 10
Voltage protection

Function Range or value Accuracy


Minimum operate time, Inverse (0.000-60.000) s ±0.2% or ±45 ms whichever is
characteristics greater
Operate time, start at 0 to 2 x Uset Min. = 15 ms -
Max. = 30 ms
Reset time, start at 2 x Uset to 0 Min. = 15 ms -
Max. = 30 ms
Operate time, start at 0 to 1.2 x Uset Min. = 20 ms -
Max. = 35 ms
Reset time, start at 1.2 x Uset to 0 Min. = 5 ms -
Max. = 25 ms
Critical impulse time 10 ms typically at 0 to 2 x -
Uset

Impulse margin time 15 ms typically -

10.3 Two step residual overvoltage protection ROV2PTOV IP14546-1 v4

10.3.1 Identification
SEMOD54295-2 v6

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Two step residual overvoltage ROV2PTOV 59N
protection
2(U0>)

IEC15000108 V1 EN-US

10.3.2 Functionality M13808-3 v11

Residual voltages may occur in the power system during earth faults.

Two step residual overvoltage protection (ROV2PTOV) function calculates the residual voltage
from the three-phase voltage input transformers or measures it from a single voltage input
transformer fed from an open delta or neutral point voltage transformer.

ROV2PTOV has two voltage steps, each with inverse or definite time delay.

A reset delay ensures operation for intermittent earth faults.

10.3.3 Function block M13812-3 v6

ROV2PTOV
U3P* TRIP
BLOCK TR1
BLKTR1 TR2
BLKST1 START
BLKTR2 ST1
BLKST2 ST2

IEC06000278-2-en.vsd
IEC06000278 V2 EN-US

Figure 333: ROV2PTOV function block

Line distance protection REL670 569


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 506 370-UEN J
Voltage protection

10.3.4 Signals
PID-3531-INPUTSIGNALS v5

Table 362: ROV2PTOV Input signals


Name Type Default Description
U3P GROUP - Three phase voltages
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR1 BOOLEAN 0 Block of operate signal, step 1
BLKST1 BOOLEAN 0 Block of step 1
BLKTR2 BOOLEAN 0 Block of operate signal, step 2
BLKST2 BOOLEAN 0 Block of step 2

PID-3531-OUTPUTSIGNALS v5

Table 363: ROV2PTOV Output signals


Name Type Description
TRIP BOOLEAN Trip
TR1 BOOLEAN Common trip signal from step1
TR2 BOOLEAN Common trip signal from step2
START BOOLEAN General start signal
ST1 BOOLEAN Common start signal from step1
ST2 BOOLEAN Common start signal from step2

10.3.5 Settings
PID-3531-SETTINGS v5

Table 364: ROV2PTOV Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
OperationStep1 Off - - On Enable execution of step 1
On
Characterist1 Definite time - - Definite time Selection of time delay curve type for
Inverse curve A step 1
Inverse curve B
Inverse curve C
Prog. inv. curve
U1> 1.0 - 200.0 %UB 0.1 30.0 Voltage setting/start val (DT & IDMT),
step 1 in % of UBase
t1 0.00 - 6000.00 s 0.01 5.00 Definitive time delay of step 1
t1Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse
curves for step 1
k1 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time
delay for step 1
HystAbs1 0.0 - 50.0 %UB 0.1 0.5 Absolute hysteresis in % of UBase,
step 1
OperationStep2 Off - - On Enable execution of step 2
On
Table continues on next page

570 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 10
Voltage protection

Name Values (Range) Unit Step Default Description


Characterist2 Definite time - - Definite time Selection of time delay curve type for
Inverse curve A step 2
Inverse curve B
Inverse curve C
Prog. inv. curve
U2> 1.0 - 100.0 %UB 0.1 45.0 Voltage setting/start val (DT & IDMT),
step 2 in % of UBase
t2 0.000 - 60.000 s 0.001 5.000 Definitive time delay of step 2
t2Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse
curves for step 2
k2 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time
delay for step 2
HystAbs2 0.0 - 50.0 %UB 0.1 0.5 Absolute hysteresis in % of UBase,
step 2

Table 365: ROV2PTOV Group settings (advanced)


Name Values (Range) Unit Step Default Description
tReset1 0.000 - 60.000 s 0.001 0.025 Reset time delay used in IEC Definite
Time curve step 1
ResetTypeCrv1 Instantaneous - - Instantaneous Selection of used IDMT reset curve
Frozen timer type for step 1
Linearly
decreased
tIReset1 0.000 - 60.000 s 0.001 0.025 Time delay in IDMT reset (s), step 1
ACrv1 0.005 - 200.000 - 0.001 1.000 Parameter A for customer
programmable curve for step 1
BCrv1 0.50 - 100.00 - 0.01 1.00 Parameter B for customer
programmable curve for step 1
CCrv1 0.0 - 1.0 - 0.1 0.0 Parameter C for customer
programmable curve for step 1
DCrv1 0.000 - 60.000 - 0.001 0.000 Parameter D for customer
programmable curve for step 1
PCrv1 0.000 - 3.000 - 0.001 1.000 Parameter P for customer
programmable curve for step 1
CrvSat1 0 - 100 % 1 0 Tuning param for prog. over voltage
IDMT curve, step 1
tReset2 0.000 - 60.000 s 0.001 0.025 Time delay in DT reset (s), step 2
ResetTypeCrv2 Instantaneous - - Instantaneous Selection of used IDMT reset curve
Frozen timer type for step 2
Linearly
decreased
tIReset2 0.000 - 60.000 s 0.001 0.025 Time delay in IDMT reset (s), step 2
ACrv2 0.005 - 200.000 - 0.001 1.000 Parameter A for customer
programmable curve for step 2
BCrv2 0.50 - 100.00 - 0.01 1.00 Parameter B for customer
programmable curve for step 2
CCrv2 0.0 - 1.0 - 0.1 0.0 Parameter C for customer
programmable curve for step 2
Table continues on next page

Line distance protection REL670 571


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 506 370-UEN J
Voltage protection

Name Values (Range) Unit Step Default Description


DCrv2 0.000 - 60.000 - 0.001 0.000 Parameter D for customer
programmable curve for step 2
PCrv2 0.000 - 3.000 - 0.001 1.000 Parameter P for customer
programmable curve for step 2
CrvSat2 0 - 100 % 1 0 Tuning param for prog. over voltage
IDMT curve, step 2

Table 366: ROV2PTOV Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

10.3.6 Monitored data


PID-3531-MONITOREDDATA v4

Table 367: ROV2PTOV Monitored data


Name Type Values (Range) Unit Description
ULevel REAL - kV Magnitude of measured voltage

10.3.7 Operation principle M15331-3 v8

Two step residual overvoltage protection ROV2PTOV is used to detect a high residual voltage.
The residual voltage can be measured directly from a voltage transformer in the neutral of a
power transformer or from a three-phase voltage transformer, where the secondary windings
are connected in an open delta. Another possibility is to measure the three phase-to-earth
voltages, and calculate the corresponding residual voltage internally in the IED. ROV2PTOV has
two steps with separate time delays. If the residual voltage remains above the set value for a
time period corresponding to the chosen time delay, the corresponding TRIP signal is issued.

The time delay characteristic is individually chosen for the two steps and can be either definite
time delay or inverse time delay.

The voltage-related settings are made in percent of the base voltage, which is set in kV, phase-
phase. The set UBase value is divided by sqrt(3) before the set value is calculated.

10.3.7.1 Measurement principle M15331-6 v6

The residual voltage is measured continuously, and compared with the set values, U1> and
U2>.

To avoid oscillations of the output START signal, a settable hysteresis has been included.

10.3.7.2 Time delay M15331-10 v11

The time delay for the two steps can be either definite time delay (DT) or inverse time delay
(IDMT). For the inverse time delay four different modes are available:

572 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 10
Voltage protection

• inverse curve A
• inverse curve B
• inverse curve C
• customer programmable inverse curve

The type A curve is described as:

k
t=
æ U - Un > ö
ç ÷
è Un > ø
IECEQUATION2422 V1 EN-US (Equation 156)

where:
Un> Set value for step 1 and step 2
U Measured voltage

The type B curve is described as:

k  480
t 2.0
 0.035
 U  Un  
 32   0.5 
 U n  

IECEQUATION2423 V2 EN-US (Equation 157)

The type C curve is described as:

k × 480
t= 3.0
+ 0.035
æ U - Un > ö
ç 32 × - 0.5 ÷
è U> ø
IECEQUATION2421 V1 EN-US (Equation 158)

The customer programmable curve can be created as:

k×A
t= p
+D
æ U -Un > ö
çB× -C÷
è Un > ø
EQUATION1439 V2 EN-US (Equation 159)

When the denominator in the expression is equal to zero, the time delay will be infinite. There
will be an undesired discontinuity. Therefore a tuning parameter CrvSatn is set to compensate
for this phenomenon. In the voltage interval Un> up to Un> · (1.0 + CrvSatn/100) the used
voltage will be: Un> · (1.0 + CrvSatn/100). If the programmable curve is used this parameter
must be calculated so that:

CrvSatn
B× -C > 0
100
EQUATION1440 V1 EN-US (Equation 160)

Line distance protection REL670 573


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 506 370-UEN J
Voltage protection

The details of the different inverse time characteristics are shown in section "Inverse
characteristics".

TRIP signal issuing requires that the residual overvoltage condition continues for at least the
user set time delay. This time delay is set by the parameter t1 and t2 for definite time mode
(DT) and by some special voltage level dependent time curves for the inverse time mode
(IDMT).

If the START condition, with respect to the measured voltage ceases during the delay time, and
is not fulfilled again within a user defined reset time (tReset1 and tReset2 for the definite time
and tIReset1 and tIReset2 for the inverse time) the corresponding START output is reset, after
the defined reset time has elapsed.

Here it should be noted that after leaving the hysteresis area, the START condition must be
fulfilled again and it is not sufficient for the signal to only return back to the hysteresis area.
Also, notice that for the overvoltage function, IDMT reset time is constant and does not
depend on the voltage fluctuations during the drop-off period.

There are three ways to reset the timer: the timer is reset instantaneously, the timer value is
frozen during the reset time, or the timer value is linearly decreased during the reset time. See
figure 334 and figure 335.

574 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 10
Voltage protection

tIReset1
Voltage
START
TRIP

U1>

HystAbs1 Measured
Voltage

Time

START t

TRIP

Time
Integrator Linearly decreased
Frozen Timer
t

Instantaneous Time
IEC09000055‐3‐en.vsdx

IEC09000055 V3 EN-US

Figure 334: Voltage profile not causing a reset of the START signal for step 1, and inverse time delay

Line distance protection REL670 575


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 506 370-UEN J
Voltage protection

tIReset1
Voltage
START TRIP
START HystAbs1

U1>
Measured
Voltage

Time

START t

TRIP

Time
Integrator Frozen Timer

Time
Linearly
Instantaneous decreased
IEC05000020‐4‐en.vsdx

IEC05000020 V4 EN-US

Figure 335: Voltage profile causing a reset of the START signal for step 1, and inverse time delay
Definite time delay

When definite time delay is selected, the function will operate as shown in figure 336. Detailed
information about individual stage reset/operation behavior is shown in figure 337 and figure
338 respectively. Note that by setting tResetn = 0.0s, instantaneous reset of the definite time
delayed stage is ensured.

576 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 10
Voltage protection

ST1

U tReset1 t1
a
a>b t t
TR1
U1>
b AND
OFF ON
Delay Delay

IEC10000100-2-en.vsd
IEC10000100 V2 EN-US

Figure 336: Logic diagram for step 1, Definite time delay, DT operation

U1<

ST1

TR1

tReset1

t1

IEC10000039-3-en.vsd
IEC10000039 V3 EN-US

Figure 337: Example for Definite Time Delay stage 1 reset

U1<

ST1

TR1

tReset1

t1

IEC10000040-3-en.vsd
IEC10000040 V3 EN-US

Figure 338: Example for Definite Time Delay stage 1 operation

Line distance protection REL670 577


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 506 370-UEN J
Voltage protection

10.3.7.3 Blocking M15331-18 v7

It is possible to block two step residual overvoltage protection ROV2PTOV partially or


completely by binary input signals where:

BLOCK: blocks all outputs


BLKTR1: blocks all trip outputs of step 1
BLKST1: blocks all start and trip outputs related to step 1
BLKTR2: blocks all trip outputs of step 2
BLKST2: blocks all start and trip inputs related to step 2

10.3.7.4 Design M15331-32 v7

The voltage measuring elements continuously measure the residual voltage. Recursive Fourier
filters filter the input voltage signal for the rated frequency. The residual voltage is compared
to the set value, and is also used for the inverse time characteristic integration. The design of
the function is schematically described in figure 339.

UN Comparator Phase 1 ST1


UN > U1>
Start TR1
START t1
tReset1
&
Trip
Time integrator Output
tIReset1 TRIP
Logic
ResetTypeCrv1
Step 1

ST2
Comparator Phase 1
UN > U2> TR2
Start
t2
START tReset2
& START
Trip OR
Time integrator Output
TRIP Logic
tIReset2
ResetTypeCrv2 TRIP
Step 2 OR

IEC05000748_2_en.vsd
IEC05000748 V2 EN-US

Figure 339: Schematic design of Two step residual overvoltage protection ROV2PTOV

578 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 10
Voltage protection

10.3.8 Technical data


M13317-2 v14

Table 368: ROV2PTOV technical data


Function Range or value Accuracy
Operate voltage, step 1 - step 2 (1.0-200.0)% of UBase ± 0.5% of Ur at U ≤ Ur
± 0.5% of U at U > Ur

Absolute hysteresis (0.0–50.0)% of UBase ± 0.5% of Ur at U ≤ Ur


± 0.5% of U at U > Ur

Inverse time characteristics for low - See table 1160


and high step, see table 1160
Definite time delay low step (step 1) at (0.00–6000.00) s ± 0.2% or ± 45 ms whichever is
0 to 1.2 x Uset greater

Definite time delay high step (step 2) (0.000–60.000) s ± 0.2% or ± 45 ms whichever is


at 0 to 1.2 x Uset greater

Minimum operate time (0.000-60.000) s ± 0.2% or ± 45 ms whichever is


greater
Operate time, start at 0 to 2 x Uset Min. = 15 ms -
Max. = 30 ms
Reset time, start at 2 x Uset to 0 Min. = 15 ms -
Max. = 30 ms
Operate time, start at 0 to 1.2 x Uset Min. = 20 ms -
Max. = 35 ms
Reset time, start at 1.2 x Uset to 0 Min. = 5 ms -
Max. = 25 ms
Critical impulse time 10 ms typically at 0 to 2 x Uset -

Impulse margin time 15 ms typically -

10.4 Overexcitation protection OEXPVPH IP14547-1 v3

10.4.1 Identification
M14867-1 v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Overexcitation protection OEXPVPH 24

U/f >

SYMBOL-Q V1 EN-US

10.4.2 Functionality M13319-3 v9

When the laminated core of a power transformer or generator is subjected to a magnetic flux
density beyond its design limits, stray flux will flow into non-laminated components that are
not designed to carry flux. This will cause eddy currents to flow. These eddy currents can cause
excessive heating and severe damage to insulation and adjacent parts in a relatively short
time. The function has settable inverse operating curves and independent alarm stages.

Line distance protection REL670 579


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 506 370-UEN J
Voltage protection

10.4.3 Function block M13326-3 v5

OEXPVPH
I3P* TRIP
U3P* START
BLOCK ALARM
RESET

IEC05000329-2-en.vsd
IEC05000329 V3 EN-US

Figure 340: OEXPVPH function block

10.4.4 Signals
PID-3514-INPUTSIGNALS v6

Table 369: OEXPVPH Input signals


Name Type Default Description
I3P GROUP - Current connection
SIGNAL
U3P GROUP - Voltage connection
SIGNAL
BLOCK BOOLEAN 0 Block of function
RESET BOOLEAN 0 Reset operation

PID-3514-OUTPUTSIGNALS v6

Table 370: OEXPVPH Output signals


Name Type Description
TRIP BOOLEAN Trip from overexcitation function
START BOOLEAN Overexcitation above set operate level (instantaneous)
ALARM BOOLEAN Overexcitation above set alarm level (delayed)

10.4.5 Settings
PID-3514-SETTINGS v6

Table 371: OEXPVPH Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
V/Hz> 100.0 - 180.0 %UB/f 0.1 110.0 Operate level of V/Hz at no load and
rated freq in % of (UBase/frated)
V/Hz>> 100.0 - 200.0 %UB/f 0.1 140.0 High level of V/Hz above which tMin is
used, in % of (UBase/frated)
XLeak 0.000 - 200.000 Ohm 0.001 0.000 Winding leakage reactance in primary
ohms
TrPulse 0.000 - 60.000 s 0.001 0.100 Length of the pulse for trip signal (in
sec)
tMin 0.000 - 60.000 s 0.001 7.000 Minimum trip delay for V/Hz inverse
curve, in sec
tMax 0.00 - 9000.00 s 0.01 1800.00 Maximum trip delay for V/Hz inverse
curve, in sec
Table continues on next page

580 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 10
Voltage protection

Name Values (Range) Unit Step Default Description


tCooling 0.10 - 9000.00 s 0.01 1200.00 Transformer magnetic core cooling
time constant, in sec
CurveType IEEE - - IEEE Inverse time curve selection, IEEE/
Tailor made Tailor made
kForIEEE 1 - 60 - 1 1 Time multiplier for IEEE inverse type
curve
AlarmLevel 50.0 - 120.0 % 0.1 100.0 Alarm operate level as % of operate
level
tAlarm 0.00 - 9000.00 s 0.01 5.00 Alarm time delay, in sec

Table 372: OEXPVPH Group settings (advanced)


Name Values (Range) Unit Step Default Description
t1Tailor 0.00 - 9000.00 s 0.01 7200.00 Time delay t1 (longest) for tailor made
curve, in sec
t2Tailor 0.00 - 9000.00 s 0.01 3600.00 Time delay t2 for tailor made curve, in
sec
t3Tailor 0.00 - 9000.00 s 0.01 1800.00 Time delay t3 for tailor made curve, in
sec
t4Tailor 0.00 - 9000.00 s 0.01 900.00 Time delay t4 for tailor made curve, in
sec
t5Tailor 0.00 - 9000.00 s 0.01 450.00 Time delay t5 for tailor made curve, in
sec
t6Tailor 0.00 - 9000.00 s 0.01 225.00 Time delay t6 (shortest) for tailor
made curve, in sec

Table 373: OEXPVPH Non group settings (basic)


Name Values (Range) Unit Step Default Description
MeasuredU PosSeq - - L1L2 Selection of measured voltage
L1L2
L2L3
L3L1
MeasuredI L1L2 - - L1L2 Selection of measured current
L2L3
L3L1
PosSeq
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

10.4.6 Monitored data


PID-3514-MONITOREDDATA v5

Table 374: OEXPVPH Monitored data


Name Type Values (Range) Unit Description
TMTOTRIP REAL - s Calculated time to trip for
overexcitation, in sec
VPERHZ REAL - V/Hz Voltage to frequency ratio in per-unit
THERMSTA REAL - % Overexcitation thermal status in % of
trip level

Line distance protection REL670 581


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 506 370-UEN J
Voltage protection

10.4.7 Operation principle


M5854-3 v8
The importance of Overexcitation protection (OEXPVPH) function is growing as the power
transformers as well as other power system elements today operate near their designated
limits most of the time.

Modern design transformers are more sensitive to overexcitation than earlier types. This is a
result of the more efficient designs and designs which rely on the improvement in the
uniformity of the excitation level of modern systems. If an emergency that causes
overexcitation does occur, transformers may be damaged unless corrective action is taken.
Transformer manufacturers recommend an overexcitation protection as a part of the
transformer protection system.

Overexcitation results from excessive applied voltage, possibly in combination with below-
normal frequency. Such conditions may occur when a transformer unit is loaded, but are more
likely to arise when the transformer is unloaded, or when loss of load occurs. Transformers
directly connected to generators are in particular danger to experience overexcitation
conditions. It follows from the fundamental transformer equation, see equation 161, that the
peak flux density Bmax is directly proportional to induced voltage E, and inversely proportional
to frequency f and turns n.

E = 4.44 × f × n × Bmax× A
EQUATION898 V2 EN-US (Equation 161)

The relative excitation M is therefore according to equation 162.

E f
M ( p.u.) =
( Ur ) ( fr )
IECEQUATION2296 V1 EN-US (Equation 162)

Disproportional variations in quantities E and f may give rise to core overfluxing. If the core
flux density Bmax increases to a point above saturation level (typically 1.9 Tesla), the flux will
no longer be contained within the core, but will extend into other (non-laminated) parts of the
power transformer and give rise to eddy current circulations.

Overexcitation will result in:

• overheating of the non-laminated metal parts


• a large increase in magnetizing currents
• an increase in core and winding temperature
• an increase in transformer vibration and noise

Protection against overexcitation is based on calculation of the relative volt per hertz (V/Hz)
ratio. Protection initiates a reduction of excitation, and if this fails, or if this is not possible,
the TRIP signal will disconnect the transformer from the source after a delay ranging from
seconds to minutes, typically 5-10 seconds.

Overexcitation protection may be of particular concern on directly connected generator unit


transformers. Directly connected generator-transformers are subjected to a wide range of
frequencies during the acceleration and deceleration of the turbine. In such cases, OEXPVPH
(24) may trip the field breaker during a start-up of a machine, by means of the overexcitation
ALARM signal. If this is not possible, the power transformer can be disconnected from the
source, after a delay, by the TRIP signal.

The IEC 60076 - 1 standard requires that transformers operate continuously at not more than
10% above rated voltage at no load, and rated frequency. At no load, the ratio of the actual

582 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 10
Voltage protection

generator terminal voltage to the actual frequency should not exceed 1.1 times the ratio of
transformer rated voltage to the rated frequency on a sustained basis, see equation 163.

E
---- £ 1.1 × Ur
------
f fr
EQUATION900 V1 EN-US (Equation 163)

or equivalently, with 1.1 · Ur = V/Hz> according to equation 164.

E V Hz >
£
f fr
IECEQUATION2297 V2 EN-US (Equation 164)

where:
V/Hz> is the maximum continuously allowed voltage at no load, and rated frequency.

V/Hz> is a setting parameter. The setting range is 100% to 180%. If the user does not know
exactly what to set, then the default value for V/Hz> = 110 % given by the IEC 60076-1 standard
shall be used.

In OEXPVPH, the relative excitation M is expressed according to equation 165.

E f
M ( p.u.) =
Ur fr
IECEQUATION2299 V1 EN-US (Equation 165)

It is clear from the above formula that, for an unloaded power transformer, M = 1 for any E and
f, where the ratio E/f is equal to Ur/fr. A power transformer is not overexcited as long as the
relative excitation is M ≤ V/Hz>, V/Hz> expressed in % of Ur/fr.

The overexcitation protection algorithm is fed with an input voltage U which is in general not
the induced voltage E from the fundamental transformer equation. For no load condition,
these two voltages are the same, but for a loaded power transformer the internally induced
voltage E may be lower or higher than the voltage U which is measured and fed to OEXPVPH ,
depending on the direction of the power flow through the power transformer, the power
transformer side where OEXPVPH is applied, and the power transformer leakage reactance of
the winding. It is important to specify in the application configuration on which side of the
power transformer OEXPVPH is placed.

As an example, at a transformer with a 15% short circuit impedance Xsc, the full load, 0.8
power factor, 105% voltage on the load side, the actual flux level in the transformer core, will
not be significantly different from that at the 110% voltage, no load, rated frequency, provided
that the short circuit impedance X can be equally divided between the primary and the
secondary winding: Xleak = Xleak1 = Xleak2 = Xsc / 2 = 0.075 pu.

OEXPVPH calculates the internal induced voltage E if Xleak (meaning the leakage reactance of
the winding where OEXPVPH is connected) is known to the user. The assumption taken for
two-winding power transformers that Xleak = Xsc / 2 is unfortunately most often not true. For
a two-winding power transformer the leakage reactances of the two windings depend on how
the windings are located on the core with respect to each other. In the case of three-winding
power transformers the situation is still more complex. If a user has the knowledge on the
leakage reactance, then it should applied. If a user has no idea about it, Xleak can be set to

Line distance protection REL670 583


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 506 370-UEN J
Voltage protection

Xc/2. OEXPVPH protection will then take the given measured voltage U, as the induced voltage
E.

It is assumed that overexcitation is a symmetrical phenomenon, caused by events such as loss-


of-load, etc. A high phase-to-earth voltage does not mean overexcitation. For example, in an
unearthed power system, a single phase-to-earth fault means high voltages of the “healthy”
two phases-to-earth, but no overexcitation on any winding. The phase-to-phase voltages will
remain essentially unchanged. The important voltage is the voltage between the two ends of
each winding.

10.4.7.1 Measured voltage M5854-39 v8

If one phase-to-phase voltage is available from the side where overexcitation protection is
applied, then Overexcitation protection OEXPVPH shall be set to measure this voltage,
MeasuredU. The particular voltage which is used determines the two currents that must be
used. This must be chosen with the setting MeasuredI.

It is extremely important that MeasuredU and MeasuredI are set to same value.

If, for example, voltage UL1L2 is fed to OEXPVPH, then currents IL1, and IL2 must be applied.
From these two input currents, current IL1L2 = IL1 - IL2 is calculated internally by the OEXPVPH
algorithm. The phase-to-phase voltage must be higher than 70% of the rated value, otherwise
the protection algorithm exits without calculating the excitation. ERROR output is set to 1, and
the displayed value of relative excitation V/Hz shows 0.000.

If three phase-to-earth voltages are available from the side where overexcitation is connected,
then OEXPVPH shall be set to measure positive sequence voltage and current. In this case the
positive sequence voltage and the positive sequence current are used by OEXPVPH. A check is
made if the positive sequence voltage is higher than 70% of rated phase-to-earth voltage,
when below this value, OEXPVPH exits immediately, and no excitation is calculated. ERROR
output is set to 1, and the displayed value of relative excitation V/Hz shows 0.000.

• OEXPVPH can be connected to any power transformer side, independent from the power
flow.
• The side with a possible load tap changer must not be used.

10.4.7.2 Operate time of the overexcitation protection M5854-52 v8

The operate time of OEXPVPH is a function of the relative overexcitation.

Basically there are two different delay laws available to choose between:

• the so called IEEE law, and


• a tailor-made law.

The so called IEEE law approximates a square law and has been chosen based on analysis of
the various transformers’ overexcitation capability characteristics. They can match the
transformer core capability well.

The square law is according to equation 166.

584 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 10
Voltage protection

0.18 × k 0.18 × k
top = 2
= 2
æ M ö overexcitation
ç V Hz> - 1 ÷
è ø
IECEQUATION2298 V2 EN-US (Equation 166)

where:
M the relative excitation
V/Hz> is maximum continuously allowed voltage at no load, and rated frequency, in pu and
k is time multiplier for inverse time functions, see figure 342.
Parameter k (“time multiplier setting”) selects one delay curve from the family of curves.

The relative excitation M is calculated using equation167

æ Umeasured ö
ç ÷ Umeasured frated

fmeasured ø
M = ×
æ UBase ö UBase fmeasured
ç ÷
è frated ø
IECEQUATION2404 V1 EN-US (Equation 167)

An analog overexcitation relay would have to evaluate the following integral expression, which
means to look for the instant of time t = top according to equation 168.

top

ò (M (t) - V Hz > ) dt ³ 0.18 × k


2

IECEQUATION2300 V1 EN-US (Equation 168)

A digital, numerical relay will instead look for the lowest j (that is, j = n) where it becomes true
that:

n
2
Dt × å ( M(j) – V/Hz> ) ³ 0.18 × k
j=k
EQUATION906 V1 EN-US (Equation 169)

where:
Dt is the time interval between two successive executions of OEXPVPH and
M(j) - V/Hz> is the relative excitation at (time j) in excess of the normal (rated) excitation which is given as
Ur/fr.

As long as M > V/Hz> (that is, overexcitation condition), the above sum can only be larger with
time, and if the overexcitation persists, the protected transformer will be tripped at j = n.

Inverse delays as per figure 342, can be modified (limited) by two special definite delay
settings, namely tMax and tMin, see figure 341.

Line distance protection REL670 585


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 506 370-UEN J
Voltage protection

delay in s

tMax

under - inverse delay law


excitation

overexcitation
tMin
0 Mmax - V/Hz> Overexcitation M-V/Hz>

M=V/Hz> Mmax Excitation M

V/Hz> Emax E (only if f = fr = const)

99001067.vsd
IEC99001067 V1 EN-US

Figure 341: Restrictions imposed on inverse delays by tMax and tMin


A definite maximum time, tMax, can be used to limit the operate time at low degrees of
overexcitation. Inverse delays longer than tMax will not be allowed. In case the inverse delay is
longer than tMax, OEXPVPH trips after tMax seconds.

A definite minimum time, tMin, can be used to limit the operate time at high degrees of
overexcitation. In case the inverse delay is shorter than tMin, OEXPVPH function trips after
tMin seconds. The inverse delay law is not valid for values exceeding Mmax. The delay will be
tMin, irrespective of the overexcitation level, when values exceed Mmax (that is, M>V/Hz>).

586 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 10
Voltage protection

Time (s) IEEE OVEREXCITATION CURVES

1000

100

k = 60

k = 20

k = 10
10 k=9
k=8
k=7
k=6
k=5
k=4
k=3

k=2

k=1
1
1 2 3 4 5 10 20 30 40

OVEREXCITATION IN % (M-Emaxcont)*100)

en01000373.vsd
IEC01000373 V1 EN-US

Figure 342: Delays inversely proportional to the square of the overexcitation


The critical value of excitation M is determined indirectly via OEXPVPH setting V/Hz>>. V/Hz>>
can be thought of as a no-load voltage at rated frequency, where the inverse law should be
replaced by a short definite delay, tMin. If, for example, V/Hz>> = 140 %, then M is according to
equation 170.

(V Hz>> ) / f
M= = 1.40
Ur/fr
IECEQUATION2286 V1 EN-US (Equation 170)

The Tailor-Made law allows a user to design an arbitrary delay characteristic. In this case the
interval between M = V/Hz>, and M = Mmax is automatically divided into five equal
subintervals, with six delays. (settings t1, t2, t3, t4, t5 and t6) as shown in figure 343. These
times should be set so that t1 => t2 => t3 => t4 => t5 => t6.

The lower V/Hz limit is always the set value V/Hz> in %.

The upper V/Hz limit for the Tailor-Made characteristic is always the greater value among the
following two values in %:

• 1.10 x V/Hz>
• V/Hz>>

Line distance protection REL670 587


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 506 370-UEN J
Voltage protection

The reason is to prevent the loss of accuracy of the Tailor-Made characteristic when small set
value for V/Hz>> is used.

delay in s

tMax

under- tMin
excitation Overexcitation M-Emaxcont
0 Mmax - Emaxcont Excitation M

Emaxcont Mmax
99001068.vsd
IEC99001068 V1 EN-US

Figure 343: An example of a Tailor-Made delay characteristic


Delays between two consecutive points, for example t3 and t4, are obtained by linear
interpolation.

Should it happen that tMax be lower than, for example, delays t1, and t2, the actual delay would
be tMax. Above Mmax, the delay can only be tMin.

10.4.7.3 Cooling M5854-92 v6

Overexcitation protection OEXPVPH is basically a thermal protection; therefore a cooling


process has been introduced. Exponential cooling process is applied. Parameter Setting tool is
an OEXPVPH setting, with a default time constant tCooling of 20 minutes. This means that if
the voltage and frequency return to their previous normal values (no more overexcitation), the
normal temperature is assumed to be reached not before approximately 5 times tCooling
minutes. If an overexcitation condition would return before that, the time to trip will be
shorter than it would be otherwise.

10.4.7.4 Overexcitation protection function measurands M5854-95 v8

A monitored data value, TMTOTRIP, is available on the local HMI and in PCM600. This value is
an estimation of the remaining time to trip (in seconds), if the overexcitation remained on the
level it had when the estimation was done. This information can be useful during small or
moderate overexcitation situations.

If the overexcitation is so low that the valid delay is tMax, then the estimation of the remaining
time to trip is done against tMax.

The relative excitation M, shown on the local HMI and in PCM600 has a monitored data value
VPERHZ and is calculated from the expression:

E f
M ( p.u.) =
Ur fr
IECEQUATION2299 V1 EN-US (Equation 171)

If VPERHZ value is less than setting V/Hz> (in %), the power transformer is underexcited. If
VPERHZ is equal to V/Hz> (in %), the excitation is exactly equal to the power transformer
continuous capability. If VPERHZ is higher than V/Hz>, the protected power transformer is
overexcited. For example, if VPERHZ = 1.100, while V/Hz> = 110 %, then the power transformer
is exactly on its maximum continuous excitation limit.

588 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 10
Voltage protection

The monitored data value THERMSTA shows the thermal status of the protected power
transformer iron core. THERMSTA gives the thermal status in % of the trip value which
corresponds to 100%. THERMSTA should reach 100% at the same time, as TMTOTRIP reaches
0 seconds. If the protected power transformer is then for some reason not switched off,
THERMSTA shall go over 100%.

If the delay as per IEEE law, or Tailor-made Law, is limited by tMax, and/or tMin, then the
Thermal status will generally not reach 100% at the same time, when tTRIP reaches 0 seconds.
For example, if, at low degrees of overexcitation, the very long delay is limited by tMax, then
the OEXPVPH TRIP output signal will be set to 1 before the Thermal status reaches 100%.

10.4.7.5 Overexcitation alarm M5854-123 v6

A separate step, AlarmLevel, is provided for alarming purpose. It is normally set 2% lower than
(V/Hz>) and has a definite time delay, tAlarm. This will give the operator an early warning.

10.4.7.6 Logic diagram M13333-9 v4

BLOCK
AlarmLevel
tAlarm ALARM
&
t

M>V/Hz>
TRIP
&
V/Hz>
U3P Calculation
Ei k
M
of internal M=
I3P induced (Ei / f) IEEE law &
voltage Ei (Ur / fr) tMax ³1
M t
Tailor-made law
M>V/Hz>>
tMin
Xleak
t
V/Hz>>

M = relative V/Hz as service value


IEC05000162-3-en.vsd
IEC05000162 V3 EN-US

Figure 344: A simplified logic diagram of the Overexcitation protection OEXPVPH


Simplification of the diagram is in the way the IEEE and Tailor-made delays are calculated. The
cooling process is not shown. It is not shown that voltage and frequency are separately
checked against their respective limit values.

10.4.8 Technical data


M13338-2 v11

Table 375: OEXPVPH technical data


Function Range or value Accuracy
Operate value, start (100–180)% of (UBase/frated) ±0.5% of U

Operate value, alarm (50–120)% of start level ±0.5% of Ur at U ≤ Ur


±0.5% of U at U > Ur

Operate value, high level (100–200)% of (UBase/frated) ±0.5% of U

Table continues on next page

Line distance protection REL670 589


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 506 370-UEN J
Voltage protection

Function Range or value Accuracy


Curve type IEEE or customer defined ±5.0 % or ±45 ms, whichever is
greater
(0.18 × k )
IEEE : t =
( M - 1) 2

EQUATION1319 V1 EN-US (Equation 172)

where M = (E/f)/(Ur/fr)
Minimum time delay for inverse (0.000–60.000) s ±1.0% or ±45 ms, whichever is
function greater
Maximum time delay for inverse (0.00–9000.00) s ±1.0% or ±45 ms, whichever is
function greater
Alarm time delay (0.00–9000.00) ±1.0% or ±45 ms, whichever is
greater

10.5 Voltage differential protection VDCPTOV SEMOD153860-1 v2

10.5.1 Identification
SEMOD167723-2 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Voltage differential protection VDCPTOV - 60

10.5.2 Functionality SEMOD153862-5 v7

A voltage differential monitoring function is available. It compares the voltages from two three
phase sets of voltage transformers and has one sensitive alarm step and one trip step.

10.5.3 Function block SEMOD159374-4 v2

VDCPTOV
U3P1* TRIP
U3P2* START
BLOCK ALARM
U1LOW
U2LOW
UL1DIFF
UL2DIFF
UL3DIFF

IEC06000528-2-en.vsd
IEC06000528 V2 EN-US

Figure 345: VDCPTOV function block

10.5.4 Signals
PID-3591-INPUTSIGNALS v6

Table 376: VDCPTOV Input signals


Name Type Default Description
U3P1 GROUP - Bus voltage
SIGNAL
U3P2 GROUP - Capacitor voltage
SIGNAL
BLOCK BOOLEAN 0 Block of function

590 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 10
Voltage protection

PID-3591-OUTPUTSIGNALS v6

Table 377: VDCPTOV Output signals


Name Type Description
TRIP BOOLEAN Voltage differential protection operated
START BOOLEAN Start of voltage differential protection
ALARM BOOLEAN Voltage differential protection alarm
U1LOW BOOLEAN Loss of U1 voltage
U2LOW BOOLEAN Loss of U2 voltage
UL1DIFF REAL Differential Voltage phase L1
UL2DIFF REAL Differential Voltage phase L2
UL3DIFF REAL Differential Voltage phase L3

10.5.5 Settings
PID-3591-SETTINGS v6

Table 378: VDCPTOV Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
BlkDiffAtULow No - - Yes Block operation at low voltage
Yes
UDTrip 2.0 - 100.0 %UB 0.1 5.0 Operate level, in % of UBase
tTrip 0.000 - 60.000 s 0.001 1.000 Time delay for voltage differential
operate, in seconds
tReset 0.000 - 60.000 s 0.001 0.000 Time delay for voltage differential
reset, in seconds
UDAlarm 2.0 - 100.0 %UB 0.1 2.0 Alarm level, in % of UBase
tAlarm 0.000 - 60.000 s 0.001 2.000 Time delay for voltage differential
alarm, in seconds
U1Low 1.0 - 100.0 %UB 0.1 70.0 Input 1 undervoltage level, in % of
UBase
U2Low 1.0 - 100.0 %UB 0.1 70.0 Input 2 undervoltage level, in % of
UBase
tBlock 0.000 - 60.000 s 0.001 0.000 Reset time for undervoltage block

Table 379: VDCPTOV Group settings (advanced)


Name Values (Range) Unit Step Default Description
RFL1 0.000 - 3.000 - 0.001 1.000 Ratio compensation factor phase L1
U2L1*RFL1=U1L1
RFL2 0.000 - 3.000 - 0.001 1.000 Ratio compensation factor phase L2
U2L2*RFL2=U1L2
RFL3 0.000 - 3.000 - 0.001 1.000 Ratio compensation factor phase L3
U2L3*RFL3=U1L3

Table 380: VDCPTOV Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

Line distance protection REL670 591


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 506 370-UEN J
Voltage protection

10.5.6 Monitored data


PID-3591-MONITOREDDATA v6

Table 381: VDCPTOV Monitored data


Name Type Values (Range) Unit Description
UL1DIFF REAL - kV Differential Voltage phase L1
UL2DIFF REAL - kV Differential Voltage phase L2
UL3DIFF REAL - kV Differential Voltage phase L3

10.5.7 Operation principle SEMOD153866-61 v4

The Voltage differential protection function VDCPTOV (60) is based on comparison of the
amplitudes of the two voltages connected in each phase. Possible differences between the
ratios of the two Voltage/Capacitive voltage transformers can be compensated for with a
ratio correction factors RFLx. The voltage difference is evaluated and if it exceeds the alarm
level UDAlarm or trip level UDATrip signals for alarm (ALARM output) or trip (TRIP output) is
given after definite time delay tAlarm respectively tTrip. The two three phase voltage supplies
are also supervised with undervoltage settings U1Low and U2Low. The outputs for loss of
voltage U1LOW resp U2LOW will be activated. The U1 voltage is supervised for loss of
individual phases whereas the U2 voltage is supervised for loss of all three phases.

Loss of all U1 or all U2 voltages will block the differential measurement. This blocking can be
switched off with setting BlkDiffAtULow = No.

VDCPTOV function can be blocked from an external condition with the binary BLOCK input. It
can, for example, be activated from Fuse failure supervision function FUFSPVC.

To allow easy commissioning the measured differential voltage is available as service value.
This allows simple setting of the ratio correction factor to achieve full balance in normal
service.

The principle logic diagram is shown in figure 346.

592 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 10
Voltage protection

UDTripL1>
AND

UDTripL2> O tReset tTrip


AND
R t t
AND TRIP

UDTripL3>
AND
AND START

UDAlarmL1>
AND

UDAlarmL2> O tAlarm
AND
R t AND ALARM

UDAlarmL3>
AND

U1<L1
tAlarm
U1<L2 AND t U1LOW
AND

U1<L3 AND

OR
BlkDiffAtULow

U2<L1
t1
U2<L2 AND t U2LOW
AND

U2<L3

BLOCK

en06000382-2.vsd
IEC06000382 V3 EN-US

Figure 346: Principle logic for Voltage differential function VDCPTOV

10.5.8 Technical data


SEMOD166919-2 v7

Table 382: VDCPTOV technical data


Function Range or value Accuracy
Voltage difference for alarm and trip (2.0–100.0) % of UBase ±0.5% of Ur

Under voltage level (1.0–100.0) % of UBase ±0.5% of Ur

Independent time delay for voltage (0.000–60.000)s ±0.2% or ±40 ms whichever is


differential alarm at 0.8 x UDAlarm to 1.2 x greater
UDAlarm
Independent time delay for voltage (0.000–60.000)s ±0.2% or ±40 ms whichever is
differential trip at 0.8 x UDTrip to 1.2 x greater
UDTrip
Independent time delay for voltage (0.000–60.000)s ±0.2% or ±40 ms whichever is
differential reset at 1.2 x UDTrip to 0.8 x greater
UDTrip

Line distance protection REL670 593


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 506 370-UEN J
Voltage protection

10.6 Loss of voltage check LOVPTUV SEMOD171453-1 v3

10.6.1 Identification
SEMOD171954-2 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Loss of voltage check LOVPTUV - 27

10.6.2 Functionality SEMOD171457-5 v8

Loss of voltage check (LOVPTUV ) is suitable for use in networks with an automatic system
restoration function. LOVPTUV issues a three-pole trip command to the circuit breaker, if all
three phase voltages fall below the set value for a time longer than the set time and the circuit
breaker remains closed.

The operation of LOVPTUV is supervised by the fuse failure supervision FUFSPVC.

10.6.3 Function block SEMOD171785-4 v4

LOVPTUV
U3P* TRIP
BLOCK START
CBOPEN
VTSU

IEC07000039-2-en.vsd
IEC07000039 V2 EN-US

Figure 347: LOVPTUV function block

10.6.4 Signals
PID-3519-INPUTSIGNALS v6

Table 383: LOVPTUV Input signals


Name Type Default Description
U3P GROUP - Voltage connection
SIGNAL
BLOCK BOOLEAN 0 Block the all outputs
CBOPEN BOOLEAN 0 Circuit breaker open
VTSU BOOLEAN 0 Block from voltage circuit supervision

PID-3519-OUTPUTSIGNALS v6

Table 384: LOVPTUV Output signals


Name Type Description
TRIP BOOLEAN Trip signal
START BOOLEAN Start signal

594 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 10
Voltage protection

10.6.5 Settings
PID-3519-SETTINGS v6

Table 385: LOVPTUV Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
UPE 1 - 100 %UB 1 70 Operate voltage in % of base voltage
UBase
tTrip 0.000 - 60.000 s 0.001 7.000 Operate time delay

Table 386: LOVPTUV Group settings (advanced)


Name Values (Range) Unit Step Default Description
tPulse 0.050 - 60.000 s 0.001 0.150 Duration of TRIP pulse
tBlock 0.000 - 60.000 s 0.001 5.000 Time delay to block when all 3ph
voltages are not low
tRestore 0.000 - 60.000 s 0.001 3.000 Time delay for enable the function
after restoration

Table 387: LOVPTUV Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

10.6.6 Operation principle SEMOD171765-4 v6

The operation of Loss of voltage check LOVPTUV is based on line voltage measurement.
LOVPTUV is provided with a logic, which automatically recognizes if the line was restored for
at least tRestore before starting the tTrip timer. All three phases are required to be low before
the output TRIP is activated. The START output signal indicates start.

Additionally, LOVPTUV is automatically blocked if only one or two phase voltages have been
detected low for more than tBlock.

LOVPTUV operates again only if the line has been restored to full voltage for at least tRestore.
Operation of the function is also inhibited by fuse failure and open circuit breaker information
signals, by their connection to dedicated inputs of the function block.

Due to undervoltage conditions being continuous the trip pulse is limited to a length set by
setting tPulse.

The operation of LOVPTUV is supervised by the fuse-failure function (BLKU input) and the
information about the open position (CBOPEN) of the associated circuit breaker.

The BLOCK input can be connected to a binary input of the IED in order to receive a block
command from external devices or can be software connected to other internal functions of
the IED itself in order to receive a block command from internal functions. LOVPTUV is also
blocked when the IED is in TEST status and the function has been blocked from the HMI test
menu. (Blocked=Yes).

Line distance protection REL670 595


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 506 370-UEN J
Voltage protection

TEST

TEST-ACTIVE
&
Blocked = Yes

START
BLOCK >1
Function Enable tTrip tPulse TRIP
STUL1N & t

STUL2N &
only 1 or 2 phases are low for
Latched at least 10 s (not three)
STUL3N Enable
&

tBlock
>1 t

CBOPEN Reset Enable


>1
&
VTSU
tRestore
>1 Set Enable
t
>1
Line restored for
at least 3 s

IEC07000089_2_en.vsd

IEC07000089 V2 EN-US

Figure 348: Simplified diagram of Loss of voltage check LOVPTUV

10.6.7 Technical data


SEMOD175210-2 v6

Table 388: LOVPTUV technical data


Function Range or value Accuracy
Operate voltage (1–100)% of UBase ±0.5% of Ur

Pulse timer when (0.050–60.000) s ±0.2% or ±15 ms whichever is greater


disconnecting all three phases
Time delay for enabling the (0.000–60.000) s ±0.2% or ±35 ms whichever is greater
functions after restoration
Operate time delay when (0.000–60.000) s ±0.2% or ±35 ms whichever is greater
disconnecting all three phases
Time delay to block when all (0.000–60.000) s ±0.2% or ±35 ms whichever is greater
three phase voltages are not
low

596 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 10
Voltage protection

10.7 Radial feeder protection PAPGAPC GUID-831891A3-B5AB-4532-8901-311C541F0ABB v1

10.7.1 Identification GUID-1B7B3DC5-DD7B-4017-928D-0C41768E94D9 v1

Function description IEC 61850 identification IEC 60617 identification ANSI/IEEE C37.2 device
number
Radial feeder protection PAPGAPC U< 27

10.7.2 Functionality GUID-82856D0B-5C5E-499A-9A62-CC511E4F047A v3

The radial feeder protection (PAPGAPC) function is used to provide protection of radial
feeders having passive loads or weak end in-feed sources. It is possible to achieve fast
tripping using communication system with remote end or delayed tripping not requiring
communication or upon communication system failure. For fast tripping, scheme
communication is required. Delayed tripping does not require scheme communication.

The PAPGAPC function performs phase selection using measured voltages. Each phase voltage
is compared to the opposite phase-phase voltage. A phase is deemed to have a fault if its
phase voltage drops below a settable percentage of the opposite phase-phase voltage. The
phase - phase voltages include memory. This memory function has a settable time constant.

The voltage-based phase selection is used for both fast and delayed tripping. To achieve fast
tripping, scheme communication is required. Delayed tripping does not require scheme
communication. It is possible to permit delayed tripping only upon failure of the
communications channel by blocking the delayed tripping logic with a communications
channel healthy input signal.

On receipt of the communications signal, phase selective outputs for fast tripping are set
based on the phase(s) in which the phase selection function has operated.

For delayed tripping, single pole and three pole delays are separately and independently
settable. Furthermore, it is possible to enable or disable single pole and three pole delayed
tripping. For single phase faults, it is possible to include a residual current check in the
tripping logic. Three pole tripping is always selected for phase selection on more than one
phase. Three pole tripping will also occur if the residual current exceeds the set level during
fuse failure for a time longer than the three pole trip delay time.

10.7.3 Function block GUID-017455D7-C7F7-42F1-9CAA-53D785A1F4E7 v1

PAPGAPC
I3P* TRIP
U3P* TRIN
BLOCK TRL1
BLKTR TRL2
BLKST TRL3
BLKDLFLT ARST
FUSEFAIL ARST3PH
COMOK ARSTL1
CR ARSTL2
CBCLD ARSTL3
POLEDISC

IEC14000004-1-en.vsd
IEC14000004 V1 EN-US

Figure 349: PAPGAPC function block

Line distance protection REL670 597


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 506 370-UEN J
Voltage protection

10.7.4 Signals GUID-AE032A57-2479-443A-89B8-4F107AE012FA v1

PID-4140-INPUTSIGNALS v9

Table 389: PAPGAPC Input signals


Name Type Default Description
I3P GROUP - Group parameter for current signals
SIGNAL
U3P GROUP - Group parameter for voltage signals
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Block trip
BLKST BOOLEAN 0 Block Start
BLKDLFLT BOOLEAN 0 Blocks the delayed fault clear functionality
FUSEFAIL BOOLEAN 0 Block from fuse failure function
COMOK BOOLEAN 0 Telecommunication link healthy
CR BOOLEAN 0 Received communication signal
CBCLD BOOLEAN 0 Circuit breaker is closed
POLEDISC BOOLEAN 0 The position of CB poles differs (pole discordance)

PID-4140-OUTPUTSIGNALS v9

Table 390: PAPGAPC Output signals


Name Type Description
TRIP BOOLEAN General trip
TRIN BOOLEAN Trip caused by residual current detection
TRL1 BOOLEAN Trip phase L1
TRL2 BOOLEAN Trip phase L2
TRL3 BOOLEAN Trip phase L3
ARST BOOLEAN Start signal to the autorecloser function
ARST3PH BOOLEAN Three phase reclosing to be performed
ARSTL1 BOOLEAN Autoreclosing start phase L1
ARSTL2 BOOLEAN Autoreclosing start phase L2
ARSTL3 BOOLEAN Autoreclosing start phase L3

10.7.5 Settings GUID-841D8428-5335-484B-9ED8-89ED86A33E03 v1

PID-4140-SETTINGS v9

Table 391: PAPGAPC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
UPhSel< 30 - 100 % 1 60 Faulted phase voltage in % of
quadrilateral phase-phase voltage
divided by sqrt (3)
Tau 1 - 60 sec 1 5 Time constant for reference voltage
FastOperation Off - - Off Enable fast fault clearing function
On
Table continues on next page

598 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 10
Voltage protection

Name Values (Range) Unit Step Default Description


t3Ph 0.000 - 60.000 s 0.001 1.000 Time delay for three phase operation
IN> 10 - 150 %IB 1 50 Residual current detection level in %
of IBase
ResCurrCheck Off - - Off Enable residual current check for
On delayed operation at single-phase
faults
Del1PhOp 3Ph - - 3Ph Enable delayed operation for single
1Ph phase faults
t1Ph 0.000 - 60.000 s 0.001 1.000 Time delay for single phase operation
Del3PhOp Off - - Off Enable delayed 3-phase operation
On
ResCurrOper Off - - Off Enabling signal for residual current
On operation
tResCurr 0.000 - 60.000 s 0.001 0.200 Time delay for residual current
indication

Table 392: PAPGAPC Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

10.7.6 Monitored data


PID-4140-MONITOREDDATA v8

Table 393: PAPGAPC Monitored data


Name Type Values (Range) Unit Description
UL1 REAL - kV Voltage DFT amplitude in Phase1
UL2 REAL - kV Voltage DFT amplitude in Phase2
UL3 REAL - kV Voltage DFT amplitude in Phase3
IN REAL - A Residual current DFT amplitude

10.7.7 Principle of operation GUID-C8CBC104-7CCD-46CD-A01C-5FEDDC0F55AF v1

10.7.7.1 Faulted phase selection GUID-5FE347E6-8A02-4B87-B515-3CEB25232AFA v1

The faulted phase selection is based on voltage measurement. Each phase voltage magnitude
(rms) is compared with the quadrature phase – phase voltage, which is obtained by passing
full wave rectified signal through an exponential filter.

The filter updates the output if the output magnitude is lower than input voltage. However,
when the input voltage is lower than output magnitude, the output decreases with a settable
time constant of Tau. The desired filter response is depicted in Figure350.

Line distance protection REL670 599


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 506 370-UEN J
Voltage protection

Time constant=Tau Output from


filter
Rectified
input signal

en01000140.vsd
IEC14000006 V2 EN-US

Figure 350: Desired filter response


Phase Lx is deemed to have faulted if the phase Lx voltage is lower than filtered quadrature
phase – phase voltage times UPhSel< set value. The phase selection for remaining phases can
be performed in the similar way. The logic diagram for faulted phase selection is shown in
Figure 351.

Z-1

U3P* ABS
MAX

-t ×
EXP
×
Tau ÷

× a PHSLx
a<b
3 ÷ × b

UPhSel<

IEC14000007-1-en.vsd
IEC14000007 V1 EN-US

Figure 351: Simplified logic diagram for faulted phase selection

10.7.7.2 Residual current detection GUID-98B7BF77-6658-4603-BD3F-19A419551BC7 v1

PAPGAPC (27) detects the presence of residual current if the residual current exceeds the set
IN> value and lasts for a period of 600 ms.

The output TRIN is high after a set time of tResCurr if the setting ResCurrOper is enabled.

The output TRIN is blocked by enabling either of BLOCK or BLKTR inputs.

I3P* 600 ms
a STIN
a>b t
b
IN> tResCurr
t
TRIN
ResCurrOper &

BLOCK
BLKTR _1
>

IEC14000008-1-en.vsd
IEC14000008 V1 EN-US

Figure 352: Simplified logic diagram for residual current detection

600 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 10
Voltage protection

10.7.7.3 Fast fault clearance GUID-B1E84A31-7733-4CB8-AB8C-51B723B8335D v2

Operation at the remote end of the line with passive loads or weak sources is obtained as
follows. The fault clearing at remote end is initiated by CR signal received from the other end
of the feeder. Fast fault clearing can be enabled by the FastOperation setting. The function is
enabled for 650 ms upon receiving the carrier signal from the other end. It generates the start
signal STLx depending on the status of the faulty phase(s). The presence of FUSEFAIL inhibits
the operation of fault clearance on faulty phase(s) and the corresponding logic diagram is
depicted in Figure 353. The fast fault clearance operation is blocked upon failure of the
communication channel input COMOK.

650 ms
CR
&

FUSEFAIL

COMOK
& & STL 1
FastOperation

PHSL1

& STL2
PHSL2

& STL 3
PHSL3

IEC14000009-2-en.vsd

IEC14000009 V2 EN-US

Figure 353: Simplified logic diagram for fast fault clearance

10.7.7.4 Delayed fault clearance GUID-40D30808-EA85-431D-AA7F-E9F5529DDD3B v2

Delayed fault clearance does not require scheme communication. It is possible to permit
delayed tripping upon the failure of the communication channel input COMOK.

It is possible to select delayed single- and three pole tripping by choosing the appropriate
settings Del1PhOp and Del3PhOp. Furthermore, time delays for single- and three pole tripping
can independently be set by t1Ph and t3Ph.

For single phase faults, ResCurrCheck is included in the tripping logic. It is also possible to
select either single- or three pole tripping for single phase faults occurring in the system.
Three pole tripping is always selected for phase selection of more than one phase.

In case of a fuse failure condition, that is FUSEFAIL is high, single- and three pole tripping are
inhibited, however, three pole tripping occurs if the residual current exceeds the set level
during fuse failure for a time longer than the three pole trip delay time of t3Ph.

The inputs BLKDLFLT and COMOK inhibit the delayed operation for faulty phase(s).

Start signal STLx is enabled as soon as the fault is detected in any phase(s).

Line distance protection REL670 601


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 506 370-UEN J
Voltage protection

COMOK
&
FastOperation
BLKDLFLT &

FUSEFAIL

STIN
≥1 &
ResCurrCheck

Del1PhOp
t1Ph
STL1
PHSL1 & t &
≥1
t1Ph
STL2
PHSL2 & t &
≥1
t1Ph STL3
PHSL3 & t &
≥1

≥1 &

&
Del3PhOp

t3Ph
≥2 & ≥1 t

&

IEC14000010-2-en.vsd

IEC14000010 V2 EN-US

Figure 354: Simplified logic diagram for delayed fault clearance

10.7.7.5 Trip and autoreclose logic GUID-FBEFA5C3-6313-4D3F-8C85-E67C1689D110 v1

The start signals for each phase are generated from both the fast fault clearance and delayed
fault clearance. Upon receiving the start signal STLx in phase(s), the corresponding phase trip
signal TRLx is issued. A general trip signal, TRIP is also generated.

The single or three phase operation of autorecloser depends on the status of CBCLD and the
existence of pole discrepancy, indicated by the input POLEDISC. If conditions for reclosing are
fulfilled, a start signal ARSTLx is issued for the faulty phase(s).

A general start signal, ARST is also generated. If more than one phase seems to be detected
faulty, three phase autoreclosing signal ARST3PH is issued.

The binary input BLOCK can be used to block the function. The activation of the BLOCK input
deactivates all outputs.

Start output signals ARSTLx, ARST and ARST3PH are blocked by enabling BLKST input and the
activation of the BLKTR input deactivates all trip outputs.

602 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 10
Voltage protection

STL1
TRL1
&

STL2
TRL2
&

STL3
TRL3
&

≥1 TRIP
&

BLOCK
BLKTR ≥1

BLKST ≥1

& ARSTL1
&

& ARSTL2
&

& ARSTL3
&
POLEDISC
100 ms
CBCLD &
t ≥1
≥1 ARST
&

≥1 ARST3PH
&

IEC14000011-2-en.vsd

IEC14000011 V2 EN-US

Figure 355: Simplified logic diagram for trip and autoreclose logic

10.7.8 Technical data GUID-C172D5EB-51E8-4FC9-B2E7-EF976872FD7E v6

Table 394: PAPGAPC technical data


Function Range or value Accuracy
Residual current detection (10 - 150)% of IBase ±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir
Reset ratio >95% at (50 - 150)% of IBase -
Operate time, residual current Min. = 15 ms -
detection at 0 to 2 x Iset
Max. = 30 ms
Independent time delay to (0.000 - 60.000) s ±0.2% or ±40 ms whichever is
operate, residual current greater
detection at 0 to 2 x Iset

Voltage based phase selection (30 - 100)% of UBase ±1.0% of Ur

Reset ratio <115% -


Operate time, voltage-based Min. = 15 ms -
phase selection at 1.2 x Uset to 0.8
Max. = 30 ms
x Uset

Independent time delay to (0.000 – 60.000) s ±0.2% or ±40 ms whichever is


operate, voltage-based phase greater
selection at 1.2 x Uset to 0.8 x Uset

Line distance protection REL670 603


Technical manual
© Copyright 2017 ABB. All rights reserved
604
1MRK 506 370-UEN J Section 11
Frequency protection

Section 11 Frequency protection


11.1 Underfrequency protection SAPTUF IP15746-1 v3

11.1.1 Identification
M14865-1 v5

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Underfrequency protection SAPTUF 81

f<

SYMBOL-P V1 EN-US

11.1.2 Functionality M13349-3 v13

Underfrequency occurs as a result of a lack of generation in the network.

Underfrequency protection (SAPTUF) measures frequency with high accuracy, and is used for
load shedding systems, remedial action schemes, gas turbine startup and so on. Separate
definite time delays are provided for operate and restore.

SAPTUF is provided with undervoltage blocking.

The operation is based on positive sequence voltage measurement and requires two phase-
phase or three phase-neutral voltages to be connected. For information about how to connect
analog inputs, refer to Application manual/IED application/Analog inputs/Setting
guidelines.

11.1.3 Function block M13352-3 v6

SAPTUF
U3P* TRIP
BLOCK START
BLKTRIP RESTORE
BLKREST BLKDMAGN
FREQ

IEC06000279_2_en.vsd
IEC06000279 V2 EN-US

Figure 356: SAPTUF function block

Line distance protection REL670 605


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 506 370-UEN J
Frequency protection

11.1.4 Signals
PID-6752-INPUTSIGNALS v2

Table 395: SAPTUF Input signals


Name Type Default Description
U3P GROUP - Three phase group signal for voltage inputs
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTRIP BOOLEAN 0 Blocking operate output
BLKREST BOOLEAN 0 Blocking restore output

PID-6752-OUTPUTSIGNALS v2

Table 396: SAPTUF Output signals


Name Type Description
TRIP BOOLEAN General trip signal
START BOOLEAN General start signal
RESTORE BOOLEAN Restore signal for load restoring purposes
BLKDMAGN BOOLEAN Blocking indication due to low amplitude
FREQ REAL Measured frequency

11.1.5 Settings
PID-6752-SETTINGS v2

Table 397: SAPTUF Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
StartFrequency 35.00 - 75.00 Hz 0.01 48.80 Frequency set value
IntBlockLevel 0.0 - 100.0 %UB 1.0 50.0 Internal blocking level in % of UBase
tDelay 0.000 - 60.000 s 0.001 0.200 Operate time delay
tReset 0.000 - 60.000 s 0.001 0.000 Time delay for reset
tRestore 0.000 - 60.000 s 0.001 0.000 Restore time delay
RestoreFreq 45.00 - 65.00 Hz 0.01 49.90 Restore frequency value
TimerMode Definite timer - - Definite timer Setting for choosing timer mode
Volt based timer
UNom 50.0 - 150.0 %UB 1.0 100.0 Nominal voltage for voltage based
timer in % of UBase
UMin 50.0 - 150.0 %UB 1.0 90.0 Lower operation limit for voltage
based timer in % of UBase
Exponent 0.0 - 5.0 - 0.1 1.0 For calculation of the curve form for
voltage based timer
tMax 0.010 - 60.000 s 0.001 1.000 Maximum time operation limit for
voltage based timer
tMin 0.010 - 60.000 s 0.001 1.000 Minimum time operation limit for
voltage based timer

606 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 11
Frequency protection

Table 398: SAPTUF Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

11.1.6 Operation principle M13354-3 v9

Underfrequency protection SAPTUF is used to detect low power system frequency. SAPTUF
can either have a definite time delay or a voltage magnitude dependent time delay. If the
voltage magnitude dependent time delay is applied, the time delay will be longer if the voltage
is higher, and the delay will be shorter if the voltage is lower. If the frequency remains below
the set value for a time period corresponding to the chosen time delay, the corresponding trip
signal is issued. To avoid an unwanted trip due to uncertain frequency measurement at low
voltage magnitude, a voltage controlled blocking of the function is available, that is, if the
voltage is lower than the set blocking voltage IntBlockLevel, the function is blocked and no
START or TRIP signal is issued.

11.1.6.1 Measurement principle M13354-6 v8

The fundamental frequency of the measured input voltage is measured continuously, and
compared with the set value, StartFrequency. The frequency function is dependent on the
voltage magnitude. If the voltage magnitude decreases below the setting IntBlockLevel,
SAPTUF gets blocked, and the output BLKDMAGN is issued. All voltage settings are made in
percent of the setting UBase, which should be set as a phase-phase voltage in kV.

To avoid oscillations of the output START signal, a hysteresis has been included.

11.1.6.2 Time delay M13354-10 v9

The time delay for underfrequency protection SAPTUF can be either a settable definite time
delay or a voltage magnitude dependent time delay, where the time delay depends on the
voltage level; a high voltage level gives a longer time delay and a low voltage level causes a
short time delay. For the definite time delay, the setting tDelay sets the time delay.

For the voltage dependent time delay the measured voltage level and the settings UNom,
UMin, Exponent, tMax and tMin set the time delay according to figure 357 and equation . The
setting TimerMode is used to decide what type of time delay to apply.

Trip signal issuing requires that the underfrequency condition continues for at least the user
set time delay tDelay. If the START condition, with respect to the measured frequency ceases
during this user set delay time, and is not fulfilled again within a user defined reset time,
tReset, the START output is reset, after that the defined reset time has elapsed. Here it should
be noted that after leaving the hysteresis area, the START condition must be fulfilled again and
it is not sufficient for the signal to only return back to the hysteresis area.

The total time delay consists of the set value for time delay plus the minimum
operate time of the start function (80-90 ms).

On the RESTORE output of SAPTUF a 100ms pulse is issued, after a time delay corresponding
to the setting of tRestore, when the measured frequency returns to the level corresponding to
the setting RestoreFreq, after an issue of the TRIP output signal. If tRestore is se to 0.000 s
the restore functionality is disabled, and no output will be given.

Line distance protection REL670 607


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 506 370-UEN J
Frequency protection

11.1.6.3 Voltage dependent time delay M13354-19 v5

Since the fundamental frequency in a power system is the same all over the system, except
some deviations during power oscillations, another criterion is needed to decide, where to
take actions, based on low frequency. In many applications the voltage level is very suitable,
and in most cases is load shedding preferable in areas with low voltage. Therefore, a voltage
dependent time delay has been introduced, to make sure that load shedding, or other actions,
take place at the right location. At constant voltage, U, the voltage dependent time delay is
calculated according to equation 173. At non-constant voltage, the actual time delay is
integrated in a similar way as for the inverse time characteristic for the undervoltage and
overvoltage functions.

Exponent
é U - UMin ù
t=ê × ( tMax - tMin ) + tMin
ë UNom - UMin úû
EQUATION1182 V1 EN-US (Equation 173)

where:
t is the voltage dependent time delay (at constant voltage),
U is the measured voltage
Exponent is a setting,
UMin, UNom are voltage settings corresponding to
tMax, tMin are time settings.

The inverse time characteristics are shown in figure 357, for:

UMin = 90%
UNom = 100%
tMax = 1.0 s
tMin = 0.0 s
Exponent = 0, 1, 2, 3 and 4

1
0
1
Exponenent
TimeDlyOperate [s]

2
3
0.5 4

0
90 95 100

U [% of UBase]
en05000075.vsd
IEC05000075 V1 EN-US

Figure 357: Voltage dependent inverse time characteristics for underfrequency


protection SAPTUF. The time delay to operate is plotted as a function of the
measured voltage, for the Exponent = 0, 1, 2, 3, 4 respectively.

608 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 11
Frequency protection

11.1.6.4 Blocking M13354-50 v7

It is possible to block underfrequency protection SAPTUF partially or completely, by binary


input signals or by parameter settings, where:

BLOCK: blocks the START, TRIP and


RESTORE outputs
BLKTRIP: blocks the TRIP output
BLKREST: blocks the RESTORE output

If the measured voltage level decreases below the setting of IntBlockLevel, both the START and
the TRIP outputs are blocked.

11.1.6.5 Design M13354-63 v10

The frequency measuring element continuously measures the frequency of the positive
sequence voltage and compares it to the setting StartFrequency. The frequency signal is
filtered to avoid transients due to switchings and faults. The time integrator can operate
either due to a definite delay time or to the special voltage dependent delay time. When the
frequency has returned back to the setting of RestoreFreq, the RESTORE output is issued after
the time delay tRestore. The design of underfrequency protection SAPTUF is schematically
described in figure 358.

BLKDMAGN

BLOCK

block START
OR

U < IntBlockLevel

Start
&
start Trip
Voltage
output
Definite timer
logic TRIP
or
Voltage based timer
Frequency
f < StartFrequency
tReset trip
tDelay RESTORE
AND

BLKTRIP

f > RestoreFreq tRestore


restore
AND
BLKREST

IEC16000041-1-en.vsdx
IEC16000041 V1 EN-US

Figure 358: Simplified logic diagram for SAPTUF

Line distance protection REL670 609


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 506 370-UEN J
Frequency protection

11.1.7 Technical data


M13360-1 v15

Table 399: SAPTUF technical data


Function Range or value Accuracy
Operate value, start function, at symmetrical (35.00-75.00) Hz ±2.0 mHz
three phase voltage
Operate time, start at fset + 0.02 Hz to fset - 0.02 Min. = 80 ms
Hz fn = 50 Hz
Max. = 95 ms
-
Min. = 65 ms
fn = 60 Hz
Max. = 80 ms
Reset time, start at fset - 0.02 Hz to fset + 0.02 Hz Min. = 15 ms
-
Max. = 30 ms
Operate time, definite time function at fset + (0.000-60.000)s ±0.2% or ±100 ms
0.02 Hz to fset - 0.02 Hz whichever is greater

Reset time, definite time function at fset - 0.02 (0.000-60.000)s ±0.2% or ±120 ms
Hz to fset + 0.02 Hz whichever is greater

Voltage dependent time delay Settings: ±1.0% or ±100 ms


UNom=(50-150)% of Ubase whichever is greater
UMin=(50-150)% of Ubase
Exponent=0.0-5.0
tMax=(0.010–60.000)s
tMin=(0.010–60.000)s

Exponent
é U - UMin ù
t=ê × ( tMax - tMin ) + tMin
ë UNom - UMin úû
EQUATION1182 V1 EN-US (Equation 174)
U=Umeasured

11.2 Overfrequency protection SAPTOF IP15747-1 v3

11.2.1 Identification
M14866-1 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Overfrequency protection SAPTOF 81

f>

SYMBOL-O V1 EN-US

11.2.2 Functionality M14953-3 v12

Overfrequency protection function (SAPTOF) is applicable in all situations, where reliable


detection of high fundamental power system frequency is needed.

Overfrequency occurs because of sudden load drops or shunt faults in the power network.
Close to the generating plant, generator governor problems can also cause over frequency.

610 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 11
Frequency protection

SAPTOF measures frequency with high accuracy, and is used mainly for generation shedding
and remedial action schemes. It is also used as a frequency stage initiating load restoring. A
definite time delay is provided for operate.

SAPTOF is provided with an undervoltage blocking.

The operation is based on positive sequence voltage measurement and requires two phase-
phase or three phase-neutral voltages to be connected. For information about how to connect
analog inputs, refer to Application manual/IED application/Analog inputs/Setting
guidelines.

11.2.3 Function block M14956-3 v5

SAPTOF
U3P* TRIP
BLOCK START
BLKTRIP BLKDMAGN
FREQ

IEC06000280_2_en.vsd
IEC06000280 V2 EN-US

Figure 359: SAPTOF function block

11.2.4 Signals
PID-6751-INPUTSIGNALS v2

Table 400: SAPTOF Input signals


Name Type Default Description
U3P GROUP - Three phase group signal for voltage inputs
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTRIP BOOLEAN 0 Blocking operate output

PID-6751-OUTPUTSIGNALS v2

Table 401: SAPTOF Output signals


Name Type Description
TRIP BOOLEAN General trip signal
START BOOLEAN General start signal
BLKDMAGN BOOLEAN Blocking indication due to low amplitude
FREQ REAL Measured frequency

11.2.5 Settings
PID-6751-SETTINGS v2

Table 402: SAPTOF Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
StartFrequency 35.00 - 90.00 Hz 0.01 51.20 Frequency set value
IntBlockLevel 0.0 - 100.0 %UB 1.0 50.0 Internal blocking level in % of UBase
tDelay 0.000 - 60.000 s 0.001 0.000 Operate time delay
tReset 0.000 - 60.000 s 0.001 0.000 Time delay for reset

Line distance protection REL670 611


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 506 370-UEN J
Frequency protection

Table 403: SAPTOF Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

11.2.6 Operation principle M14958-3 v7

Overfrequency protection SAPTOF is used to detect high power system frequency. SAPTOF
has a settable definite time delay. If the frequency remains above the set value for a time
period corresponding to the chosen time delay, the corresponding TRIP signal is issued. To
avoid an unwanted TRIP due to uncertain frequency measurement at low voltage magnitude, a
voltage controlled blocking of the function is available, that is, if the voltage is lower than the
set blocking voltage IntBlockLevel, the function is blocked and no START or TRIP signal is
issued.

11.2.6.1 Measurement principle M14958-6 v9

The fundamental frequency of the positive sequence voltage is measured continuously, and
compared with the set value, StartFrequency. Overfrequency protection SAPTOF is dependent
on the voltage magnitude. If the voltage magnitude decreases below the setting IntBlockLevel,
SAPTOF is blocked and the output BLKDMAGN is issued. All voltage settings are made in
percent of the UBase, which should be set as a phase-phase voltage in kV. To avoid oscillations
of the output START signal, a hysteresis has been included.

11.2.6.2 Time delay M14958-9 v8

The time delay for Overfrequency protection SAPTOF is a settable definite time delay,
specified by the setting tDelay.

TRIP signal issuing requires that the overfrequency condition continues for at least the user
set time delay, tDelay. If the START condition, with respect to the measured frequency ceases
during this user set delay time, and is not fulfilled again within a user defined reset time,
tReset, the START output is reset, after that the defined reset time has elapsed. It is to be
noted that after leaving the hysteresis area, the START condition must be fulfilled again and it
is not sufficient for the signal to only return back to the hysteresis area.

The total time delay consists of the set value for time delay plus minimum
operate time of the start function (80 - 90 ms).

11.2.6.3 Blocking M14958-13 v7

It is possible to block overfrequency protection SAPTOF partially or completely, by binary input


signals or by parameter settings, where:

BLOCK: blocks the START and TRIP


outputs
BLKTRIP: blocks the TRIP output

If the measured voltage level decreases below the setting of IntBlockLevel, both the START and
the TRIP outputs are blocked.

612 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 11
Frequency protection

11.2.6.4 Design M14958-24 v9

The frequency measuring element continuously measures the frequency of the positive
sequence voltage and compares it to the setting StartFrequency. The frequency signal is
filtered to avoid transients due to switchings and faults in the power system. The time
integrator operates due to a definite delay time. The design of overfrequency protection
SAPTOF is schematically described in figure 360.

BLKDMAGN

BLOCK

block START
OR

U < IntBlockLevel

Start
&
start Trip
Voltage
output
logic TRIP
Definite timer
Frequency
f > StartFrequency tReset
trip
tDelay

AND

BLKTRIP

IEC16000042-1-en.vsdx
IEC16000042 V1 EN-US

Figure 360: Simplified logic diagram for SAPTOF

11.2.7 Technical data


M14964-1 v12

Table 404: SAPTOF technical data


Function Range or value Accuracy
Operate value, start function at (35.00-90.00) Hz ±2.0 mHz
symmetrical three-phase voltage
Operate time, start at fset -0.02 Hz to fset Min. = 80 ms -
fn = 50Hz
+0.02 Hz Max. = 95 ms
Min. = 65 ms
fn = 60 Hz
Max. = 80 ms
Reset time, start at fset +0.02 Hz to fset Min. = 15 ms -
-0.02 Hz Max. = 30 ms

Operate time, definite time function at (0.000-60.000)s ±0.2% ±100 ms


fset -0.02 Hz to fset +0.02 Hz whichever is
greater
Reset time, definite time function at fset (0.000-60.000)s ±0.2% ±120 ms,
+0.02 Hz to fset -0.02 Hz whichever is
greater

Line distance protection REL670 613


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 506 370-UEN J
Frequency protection

11.3 Rate-of-change of frequency protection SAPFRC IP15748-1 v4

11.3.1 Identification
M14868-1 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Rate-of-change of frequency SAPFRC 81
protection
df/dt >
<

SYMBOL-N V1 EN-US

11.3.2 Functionality M14965-3 v14

The rate-of-change of frequency protection function (SAPFRC) gives an early indication of a


main disturbance in the system. SAPFRC measures frequency with high accuracy, and can be
used for generation shedding, load shedding and remedial action schemes. SAPFRC can
discriminate between a positive or negative change of frequency. A definite time delay is
provided for operate.

SAPFRC is provided with an undervoltage blocking. The operation is based on positive


sequence voltage measurement and requires two phase-phase or three phase-neutral voltages
to be connected. For information about how to connect analog inputs, refer to Application
manual/IED application/Analog inputs/Setting guidelines.

11.3.3 Function block M14968-3 v6

SAPFRC
U3P* TRIP
BLOCK START
BLKTRIP RESTORE
BLKREST BLKDMAGN

IEC06000281-2-en.vsd
IEC06000281 V2 EN-US

Figure 361: SAPFRC function block

11.3.4 Signals
PID-6754-INPUTSIGNALS v2

Table 405: SAPFRC Input signals


Name Type Default Description
U3P GROUP - Three phase group signal for voltage inputs
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTRIP BOOLEAN 0 Blocking operate output
BLKREST BOOLEAN 0 Blocking restore output

614 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 11
Frequency protection

PID-6754-OUTPUTSIGNALS v2

Table 406: SAPFRC Output signals


Name Type Description
TRIP BOOLEAN Trip signal
START BOOLEAN Start signal
RESTORE BOOLEAN Restore signal for load restoring purposes
BLKDMAGN BOOLEAN Blocking indication due to low amplitude

11.3.5 Settings
PID-6754-SETTINGS v2

Table 407: SAPFRC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
StartFreqGrad -10.00 - 10.00 Hz/s 0.01 0.50 Frequency gradient start value, the
sign defines direction
IntBlockLevel 0.0 - 100.0 %UB 1.0 50.0 Internal blocking level in % of UBase
tDelay 0.000 - 60.000 s 0.001 0.200 Operate time delay
RestoreFreq 45.00 - 65.00 Hz 0.01 49.90 Restore frequency value
tRestore 0.000 - 60.000 s 0.001 0.000 Restore time delay
tReset 0.000 - 60.000 s 0.001 0.000 Time delay for reset

Table 408: SAPFRC Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

11.3.6 Operation principle M14970-3 v9

Rate-of-change frequency protection SAPFRC is used to detect fast power system frequency
changes at an early stage. SAPFRC has a settable definite time delay. If the rate-of-change of
frequency remains below the set value, for negative rate-of-change, for a time period equal to
the chosen time delay, the TRIP signal is issued. If the rate-of-change of frequency remains
above the set value, for positive rate-of-change, for a time period equal to the chosen time
delay, the TRIP signal is issued. To avoid an unwanted trip due to uncertain frequency
measurement at low voltage magnitude a voltage controlled blocking of the function is
available, that is, if the voltage is lower than the set blocking voltage IntBlockLevel the function
is blocked and no START or TRIP signal is issued. If the frequency recovers, after a frequency
decrease, a restore signal is issued.

11.3.6.1 Measurement principle M14970-6 v8

The rate-of-change of the fundamental frequency of the selected voltage is measured


continuously, and compared with the set value, StartFreqGrad. Rate-of-change frequency
protection SAPFRC is also dependent on the voltage magnitude. If the voltage magnitude
decreases below the setting IntBlockLevel, SAPFRC is blocked, and the output BLKDMAGN is
issued. The sign of the setting StartFreqGrad, controls if SAPFRC reacts on a positive or on a
negative change in frequency. If SAPFRC is used for decreasing frequency that is, the setting

Line distance protection REL670 615


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 506 370-UEN J
Frequency protection

StartFreqGrad has been given a negative value, and a trip signal has been issued, then a 100
ms pulse is issued on the RESTORE output, when the frequency recovers to a value higher than
the setting RestoreFreq. A positive setting of StartFreqGrad, sets SAPFRC to START and TRIP
for frequency increases.

To avoid oscillations of the output START signal, a hysteresis has been included.

11.3.6.2 Time delay M14970-10 v7

Rate-of-change frequency protection SAPFRC has a settable definite time delay, tDelay.

Trip signal issuing requires that the rate-of-change of frequency condition continues for at
least the user set time delay, tDelay. If the START condition, with respect to the measured
frequency ceases during the delay time, and is not fulfilled again within a user defined reset
time, tReset, the START output is reset, after that the defined reset time has elapsed. Here it
should be noted that after leaving the hysteresis area, the START condition must be fulfilled
again and it is not sufficient for the signal to only return back into the hysteresis area.

The RESTORE output of SAPFRC is set, after a time delay equal to the setting of tDelay, when
the measured frequency has returned to the level corresponding to RestoreFreq, after an issue
of the TRIP output signal. If tRestore is set to 0.000 s the restore functionality is disabled, and
no output will be given. The restore functionality is only active for lowering frequency
conditions and the restore sequence is disabled if a new negative frequency gradient is
detected during the restore period, defined by the settings RestoreFreq and tRestore.

11.3.6.3 Blocking M14970-23 v6

Rate-of-change frequency protection (SAPFRC) can be partially or totally blocked, by binary


input signals or by parameter settings, where:

BLOCK: blocks the START and TRIP outputs


BLKTRIP: blocks the TRIP output
BLKREST: blocks the RESTORE output

If the measured voltage level decreases below the setting of IntBlockLevel, both the START and
the TRIP outputs are blocked.

11.3.6.4 Design M14970-34 v7

Rate-of-change frequency protection (SAPFRC) measuring element continuously measures the


frequency of the selected voltage and compares it to the setting StartFreqGrad. The frequency
signal is filtered to avoid transients due to power system switchings and faults. The time
integrator operates with a definite delay time. When the frequency has returned back to the
setting of RestoreFreq, the RESTORE output is issued after the time delay tRestore, if the TRIP
signal has earlier been issued. The sign of the setting StartFreqGrad is essential, and controls
if the function is used for raising or lowering frequency conditions. The design of SAPFRC is
schematically described in figure 362.

616 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 11
Frequency protection

BLKDMAGN

BLOCK
block
OR
Voltage
U < IntBlockLevel

START

Start
Rate-of-change
&
of Frequency start
If Trip
[StartFreqGrad<0 output
AND logic
Definite timer
df/dt < StartFreqGrad]
start TRIP
OR
tReset
[StartFreqGrad>0
AND
tDelay
df/dt > StartFreqGrad]
Then
START trip
AND
BLKTRIP
RESTORE

Frequency restore
f > RestoreFreq
> tRestore
AND
BLKREST

IEC16000040-1-en.vsdx
IEC16000040 V1 EN-US

Figure 362: Simplified logic diagram for SAPFRC

11.3.7 Technical data


M14976-1 v10

Table 409: SAPFRC Technical data


Function Range or value Accuracy
Operate value, start function (-10.00-10.00) Hz/s ±10.0 mHz/s
Operate value, restore enable frequency (45.00-65.00) Hz ±2.0 mHz
Definite restore time delay (0.000-60.000) s ±0.2% or ±100 ms whichever is
greater
Definite time delay for frequency gradient (0.000-60.000) s ±0.2% or ±120 ms whichever is
trip greater
Definite reset time delay (0.000-60.000) s ±0.2% or ±250 ms whichever is
greater

Line distance protection REL670 617


Technical manual
© Copyright 2017 ABB. All rights reserved
618
1MRK 506 370-UEN J Section 12
Multipurpose protection

Section 12 Multipurpose protection


12.1 General current and voltage protection CVGAPC IP14552-1 v2

12.1.1 Identification
M14886-2 v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
General current and voltage CVGAPC 2(I>/U<) -
protection

12.1.2 Functionality
M13083-11 v9
The General current and voltage protection (CVGAPC) can be utilized as a negative sequence
current protection detecting unsymmetrical conditions such as open phase or unsymmetrical
faults.

CVGAPC can also be used to improve phase selection for high resistive earth faults, outside
the distance protection reach, for the transmission line. Three functions are used, which
measures the neutral current and each of the three phase voltages. This will give an
independence from load currents and this phase selection will be used in conjunction with the
detection of the earth fault from the directional earth fault protection function.

12.1.3 Function block M13748-3 v3

CVGAPC
I3P* TRIP
U3P* TROC1
BLOCK TROC2
BLKOC1 TRUC1
BLKOC1TR TRUC2
ENMLTOC1 TROV1
BLKOC2 TROV2
BLKOC2TR TRUV1
ENMLTOC2 TRUV2
BLKUC1 START
BLKUC1TR STOC1
BLKUC2 STOC2
BLKUC2TR STUC1
BLKOV1 STUC2
BLKOV1TR STOV1
BLKOV2 STOV2
BLKOV2TR STUV1
BLKUV1 STUV2
BLKUV1TR BLK2ND
BLKUV2 DIROC1
BLKUV2TR DIROC2
UDIRLOW
CURRENT
ICOSFI
VOLTAGE
UIANGLE

IEC05000372-2-en.vsd
IEC05000372 V2 EN-US

Figure 363: CVGAPC function block

Line distance protection REL670 619


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 12 1MRK 506 370-UEN J
Multipurpose protection

12.1.4 Signals
PID-3857-INPUTSIGNALS v8

Table 410: CVGAPC Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKOC1 BOOLEAN 0 Block of over current function OC1
BLKOC1TR BOOLEAN 0 Block of trip for over current function OC1
ENMLTOC1 BOOLEAN 0 When activated, the current multiplier is in use for OC1
BLKOC2 BOOLEAN 0 Block of over current function OC2
BLKOC2TR BOOLEAN 0 Block of trip for over current function OC2
ENMLTOC2 BOOLEAN 0 When activated, the current multiplier is in use for OC2
BLKUC1 BOOLEAN 0 Block of under current function UC1
BLKUC1TR BOOLEAN 0 Block of trip for under current function UC1
BLKUC2 BOOLEAN 0 Block of under current function UC2
BLKUC2TR BOOLEAN 0 Block of trip for under current function UC2
BLKOV1 BOOLEAN 0 Block of over voltage function OV1
BLKOV1TR BOOLEAN 0 Block of trip for over voltage function OV1
BLKOV2 BOOLEAN 0 Block of over voltage function OV2
BLKOV2TR BOOLEAN 0 Block of trip for over voltage function OV2
BLKUV1 BOOLEAN 0 Block of under voltage function UV1
BLKUV1TR BOOLEAN 0 Block of trip for under voltage function UV1
BLKUV2 BOOLEAN 0 Block of under voltage function UV2
BLKUV2TR BOOLEAN 0 Block of trip for under voltage function UV2

PID-3857-OUTPUTSIGNALS v8

Table 411: CVGAPC Output signals


Name Type Description
TRIP BOOLEAN General trip signal
TROC1 BOOLEAN Trip signal from overcurrent function OC1
TROC2 BOOLEAN Trip signal from overcurrent function OC2
TRUC1 BOOLEAN Trip signal from undercurrent function UC1
TRUC2 BOOLEAN Trip signal from undercurrent function UC2
TROV1 BOOLEAN Trip signal from overvoltage function OV1
TROV2 BOOLEAN Trip signal from overvoltage function OV2
TRUV1 BOOLEAN Trip signal from undervoltage function UV1
TRUV2 BOOLEAN Trip signal from undervoltage function UV2
START BOOLEAN General start signal
STOC1 BOOLEAN Start signal from overcurrent function OC1
STOC2 BOOLEAN Start signal from overcurrent function OC2
Table continues on next page

620 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 12
Multipurpose protection

Name Type Description


STUC1 BOOLEAN Start signal from undercurrent function UC1
STUC2 BOOLEAN Start signal from undercurrent function UC2
STOV1 BOOLEAN Start signal from overvoltage function OV1
STOV2 BOOLEAN Start signal from overvoltage function OV2
STUV1 BOOLEAN Start signal from undervoltage function UV1
STUV2 BOOLEAN Start signal from undervoltage function UV2
BLK2ND BOOLEAN Block from second harmonic detection
DIROC1 INTEGER Directional mode of OC1 (nondir, forward,reverse)
DIROC2 INTEGER Directional mode of OC2 (nondir, forward,reverse)
UDIRLOW BOOLEAN Low voltage for directional polarization
CURRENT REAL Measured current value
ICOSFI REAL Measured current multiplied with cos (Phi)
VOLTAGE REAL Measured voltage value
UIANGLE REAL Angle between voltage and current

12.1.5 Settings
PID-3857-SETTINGS v9

Table 412: CVGAPC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
CurrentInput phase1 - - MaxPh Select current signal which will be
phase2 measured inside function
phase3
PosSeq
NegSeq
3*ZeroSeq
MaxPh
MinPh
UnbalancePh
phase1-phase2
phase2-phase3
phase3-phase1
MaxPh-Ph
MinPh-Ph
UnbalancePh-Ph
VoltageInput phase1 - - MaxPh Select voltage signal which will be
phase2 measured inside function
phase3
PosSeq
-NegSeq
-3*ZeroSeq
MaxPh
MinPh
UnbalancePh
phase1-phase2
phase2-phase3
phase3-phase1
MaxPh-Ph
MinPh-Ph
UnbalancePh-Ph
OperHarmRestr Off - - Off Operation of 2nd harmonic restrain
On Off / On
Table continues on next page

Line distance protection REL670 621


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 12 1MRK 506 370-UEN J
Multipurpose protection

Name Values (Range) Unit Step Default Description


l_2nd/l_fund 10.0 - 50.0 % 1.0 20.0 Ratio of second to fundamental
current harmonic in %
BlkLevel2nd 10 - 5000 %IB 1 5000 Harm analyse disabled above this
current level in % of fundamental
current
EnRestrainCurr Off - - Off Enable current restrain function On /
On Off
RestrCurrInput PosSeq - - PosSeq Select current signal which will be
NegSeq used for curr restrain
3*ZeroSeq
Max
RestrCurrCoeff 0.00 - 5.00 - 0.01 0.00 Restraining current coefficient
RCADir -180 - 180 Deg 1 -75 Relay Characteristic Angle
ROADir 1 - 90 Deg 1 75 Relay Operate Angle
LowVolt_VM 0.0 - 5.0 %UB 0.1 0.5 Below this level in % of UBase setting
ActLowVolt takes over
Operation_OC1 Off - - Off Operation OC1 Off / On
On
StartCurr_OC1 2.0 - 5000.0 %IB 1.0 120.0 Operate current level for OC1 in % of
IBase
CurveType_OC1 ANSI Ext. inv. - - ANSI Def. Time Selection of time delay curve type for
ANSI Very inv. OC1
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Programmable
RI type
RD type
tDef_OC1 0.00 - 6000.00 s 0.01 0.50 Independent (definite) time delay of
OC1
k_OC1 0.05 - 999.00 - 0.01 0.30 Time multiplier for the dependent
time delay for OC1
IMin1 1 - 10000 %IB 1 100 Minimum operate current for step1 in
% of IBase
tMin_OC1 0.00 - 6000.00 s 0.01 0.05 Minimum operate time for IEC IDMT
curves for OC1
VCntrlMode_OC1 Voltage control - - Off Control mode for voltage controlled
Off OC1 function
VDepMode_OC1 Step - - Step Voltage dependent mode OC1 (step,
Slope slope)
VDepFact_OC1 0.02 - 5.00 - 0.01 1.00 Multiplying factor for I pickup when
OC1 is U dependent
ULowLimit_OC1 1.0 - 200.0 %UB 0.1 50.0 Voltage low limit setting OC1 in % of
UBase
UHighLimit_OC1 1.0 - 200.0 %UB 0.1 100.0 Voltage high limit setting OC1 in % of
UBase
Table continues on next page

622 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 12
Multipurpose protection

Name Values (Range) Unit Step Default Description


HarmRestr_OC1 Off - - Off Enable block of OC1 by 2nd harmonic
On restrain
DirMode_OC1 Non-directional - - Non-directional Directional mode of OC1 (nondir,
Forward forward, reverse)
Reverse
DirPrinc_OC1 I&U - - I&U Measuring on IandU or IcosPhiandU
IcosPhi&U for OC1
ActLowVolt1_VM Non-directional - - Non-directional Low voltage level action for Dir_OC1
Block (Nodir, Blk, Mem)
Memory
Operation_OC2 Off - - Off Operation OC2 Off / On
On
StartCurr_OC2 2.0 - 5000.0 %IB 1.0 120.0 Operate current level for OC2 in % of
IBase
CurveType_OC2 ANSI Ext. inv. - - ANSI Def. Time Selection of time delay curve type for
ANSI Very inv. OC2
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Programmable
RI type
RD type
tDef_OC2 0.00 - 6000.00 s 0.01 0.50 Independent (definite) time delay of
OC2
k_OC2 0.05 - 999.00 - 0.01 0.30 Time multiplier for the dependent
time delay for OC2
IMin2 1 - 10000 %IB 1 50 Minimum operate current for step2 in
% of IBase
tMin_OC2 0.00 - 6000.00 s 0.01 0.05 Minimum operate time for IEC IDMT
curves for OC2
VCntrlMode_OC2 Voltage control - - Off Control mode for voltage controlled
Off OC2 function
VDepMode_OC2 Step - - Step Voltage dependent mode OC2 (step,
Slope slope)
VDepFact_OC2 0.02 - 5.00 - 0.01 1.00 Multiplying factor for I pickup when
OC2 is U dependent
ULowLimit_OC2 1.0 - 200.0 %UB 0.1 50.0 Voltage low limit setting OC2 in % of
UBase
UHighLimit_OC2 1.0 - 200.0 %UB 0.1 100.0 Voltage high limit setting OC2 in % of
UBase
HarmRestr_OC2 Off - - Off Enable block of OC2 by 2nd harmonic
On restrain
DirMode_OC2 Non-directional - - Non-directional Directional mode of OC2 (nondir,
Forward forward, reverse)
Reverse
DirPrinc_OC2 I&U - - I&U Measuring on IandU or IcosPhiandU
IcosPhi&U for OC2
Table continues on next page

Line distance protection REL670 623


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 12 1MRK 506 370-UEN J
Multipurpose protection

Name Values (Range) Unit Step Default Description


ActLowVolt2_VM Non-directional - - Non-directional Low voltage level action for Dir_OC2
Block (Nodir, Blk, Mem)
Memory
Operation_UC1 Off - - Off Operation UC1 Off / On
On
EnBlkLowI_UC1 Off - - Off Enable internal low current level
On blocking for UC1
BlkLowCurr_UC1 0 - 150 %IB 1 20 Internal low current blocking level for
UC1 in % of IBase
StartCurr_UC1 2.0 - 150.0 %IB 1.0 70.0 Operate undercurrent level for UC1 in
% of IBase
tDef_UC1 0.00 - 6000.00 s 0.01 0.50 Independent (definite) time delay of
UC1
tResetDef_UC1 0.00 - 6000.00 s 0.01 0.00 Reset time delay used in IEC Definite
Time curve UC1
HarmRestr_UC1 Off - - Off Enable block of UC1 by 2nd harmonic
On restrain
Operation_UC2 Off - - Off Operation UC2 Off / On
On
EnBlkLowI_UC2 Off - - Off Enable internal low current level
On blocking for UC2
BlkLowCurr_UC2 0 - 150 %IB 1 20 Internal low current blocking level for
UC2 in % of IBase
StartCurr_UC2 2.0 - 150.0 %IB 1.0 70.0 Operate undercurrent level for UC2 in
% of IBase
tDef_UC2 0.00 - 6000.00 s 0.01 0.50 Independent (definite) time delay of
UC2
HarmRestr_UC2 Off - - Off Enable block of UC2 by 2nd harmonic
On restrain
Operation_OV1 Off - - Off Operation OV1 Off / On
On
StartVolt_OV1 2.0 - 200.0 %UB 0.1 150.0 Operate voltage level for OV1 in % of
UBase
CurveType_OV1 Definite time - - Definite time Selection of time delay curve type for
Inverse curve A OV1
Inverse curve B
Inverse curve C
Prog. inv. curve
tDef_OV1 0.00 - 6000.00 s 0.01 1.00 Operate time delay in sec for definite
time use of OV1
tMin_OV1 0.00 - 6000.00 s 0.01 0.05 Minimum operate time for IDMT
curves for OV1
k_OV1 0.05 - 999.00 - 0.01 0.30 Time multiplier for the dependent
time delay for OV1
Operation_OV2 Off - - Off Operation OV2 Off / On
On
StartVolt_OV2 2.0 - 200.0 %UB 0.1 150.0 Operate voltage level for OV2 in % of
UBase
CurveType_OV2 Definite time - - Definite time Selection of time delay curve type for
Inverse curve A OV2
Inverse curve B
Inverse curve C
Prog. inv. curve
Table continues on next page

624 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 12
Multipurpose protection

Name Values (Range) Unit Step Default Description


tDef_OV2 0.00 - 6000.00 s 0.01 1.00 Operate time delay in sec for definite
time use of OV2
tMin_OV2 0.00 - 6000.00 s 0.01 0.05 Minimum operate time for IDMT
curves for OV2
k_OV2 0.05 - 999.00 - 0.01 0.30 Time multiplier for the dependent
time delay for OV2
Operation_UV1 Off - - Off Operation UV1 Off / On
On
StartVolt_UV1 2.0 - 150.0 %UB 0.1 50.0 Operate undervoltage level for UV1 in
% of UBase
CurveType_UV1 Definite time - - Definite time Selection of time delay curve type for
Inverse curve A UV1
Inverse curve B
Prog. inv. curve
tDef_UV1 0.00 - 6000.00 s 0.01 1.00 Operate time delay in sec for definite
time use of UV1
tMin_UV1 0.00 - 6000.00 s 0.01 0.05 Minimum operate time for IDMT
curves for UV1
k_UV1 0.05 - 999.00 - 0.01 0.30 Time multiplier for the dependent
time delay for UV1
EnBlkLowV_UV1 Off - - On Enable internal low voltage level
On blocking for UV1
BlkLowVolt_UV1 0.0 - 5.0 %UB 0.1 0.5 Internal low voltage blocking level for
UV1 in % of UBase
Operation_UV2 Off - - Off Operation UV2 Off / On
On
StartVolt_UV2 2.0 - 150.0 %UB 0.1 50.0 Operate undervoltage level for UV2 in
% of UBase
CurveType_UV2 Definite time - - Definite time Selection of time delay curve type for
Inverse curve A UV2
Inverse curve B
Prog. inv. curve
tDef_UV2 0.00 - 6000.00 s 0.01 1.00 Operate time delay in sec for definite
time use of UV2
tMin_UV2 0.00 - 6000.00 s 0.01 0.05 Minimum operate time for IDMT
curves for UV2
k_UV2 0.05 - 999.00 - 0.01 0.30 Time multiplier for the dependent
time delay for UV2
EnBlkLowV_UV2 Off - - On Enable internal low voltage level
On blocking for UV2
BlkLowVolt_UV2 0.0 - 5.0 %UB 0.1 0.5 Internal low voltage blocking level for
UV2 in % of UBase

Table 413: CVGAPC Group settings (advanced)


Name Values (Range) Unit Step Default Description
CurrMult_OC1 1.0 - 10.0 - 0.1 2.0 Multiplier for scaling the current
setting value for OC1
ResCrvType_OC1 Instantaneous - - Instantaneous Selection of reset curve type for OC1
IEC Reset
ANSI reset
tResetDef_OC1 0.00 - 6000.00 s 0.01 0.00 Reset time delay used in IEC Definite
Time curve OC1
Table continues on next page

Line distance protection REL670 625


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 12 1MRK 506 370-UEN J
Multipurpose protection

Name Values (Range) Unit Step Default Description


P_OC1 0.001 - 10.000 - 0.001 0.020 Parameter P for customer
programmable curve for OC1
A_OC1 0.000 - 999.000 - 0.001 0.140 Parameter A for customer
programmable curve for OC1
B_OC1 0.000 - 99.000 - 0.001 0.000 Parameter B for customer
programmable curve for OC1
C_OC1 0.000 - 1.000 - 0.001 1.000 Parameter C for customer
programmable curve for OC1
PR_OC1 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer
programmable curve for OC1
TR_OC1 0.005 - 600.000 - 0.001 13.500 Parameter TR for customer
programmable curve for OC1
CR_OC1 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer
programmable curve for OC1
CurrMult_OC2 1.0 - 10.0 - 0.1 2.0 Multiplier for scaling the current
setting value for OC2
ResCrvType_OC2 Instantaneous - - Instantaneous Selection of reset curve type for OC2
IEC Reset
ANSI reset
tResetDef_OC2 0.00 - 6000.00 s 0.01 0.00 Reset time delay used in IEC Definite
Time curve OC2
P_OC2 0.001 - 10.000 - 0.001 0.020 Parameter P for customer
programmable curve for OC2
A_OC2 0.000 - 999.000 - 0.001 0.140 Parameter A for customer
programmable curve for OC2
B_OC2 0.000 - 99.000 - 0.001 0.000 Parameter B for customer
programmable curve for OC2
C_OC2 0.000 - 1.000 - 0.001 1.000 Parameter C for customer
programmable curve for OC2
PR_OC2 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer
programmable curve for OC2
TR_OC2 0.005 - 600.000 - 0.001 13.500 Parameter TR for customer
programmable curve for OC2
CR_OC2 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer
programmable curve for OC2
tResetDef_UC2 0.00 - 6000.00 s 0.01 0.00 Reset time delay used in IEC Definite
Time curve UC2
ResCrvType_OV1 Instantaneous - - Instantaneous Selection of reset curve type for OV1
Frozen timer
Linearly
decreased
tResetDef_OV1 0.00 - 6000.00 s 0.01 0.00 Reset time delay in sec for definite
time use of OV1
tResetIDMT_OV1 0.00 - 6000.00 s 0.01 0.00 Reset time delay in sec for IDMT
curves for OV1
A_OV1 0.005 - 999.000 - 0.001 0.140 Parameter A for customer
programmable curve for OV1
B_OV1 0.500 - 99.000 - 0.001 1.000 Parameter B for customer
programmable curve for OV1
C_OV1 0.000 - 1.000 - 0.001 1.000 Parameter C for customer
programmable curve for OV1
D_OV1 0.000 - 10.000 - 0.001 0.000 Parameter D for customer
programmable curve for OV1
Table continues on next page

626 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 12
Multipurpose protection

Name Values (Range) Unit Step Default Description


P_OV1 0.001 - 10.000 - 0.001 0.020 Parameter P for customer
programmable curve for OV1
ResCrvType_OV2 Instantaneous - - Instantaneous Selection of reset curve type for OV2
Frozen timer
Linearly
decreased
tResetDef_OV2 0.00 - 6000.00 s 0.01 0.00 Reset time delay in sec for definite
time use of OV2
tResetIDMT_OV2 0.00 - 6000.00 s 0.01 0.00 Reset time delay in sec for IDMT
curves for OV2
A_OV2 0.005 - 999.000 - 0.001 0.140 Parameter A for customer
programmable curve for OV2
B_OV2 0.500 - 99.000 - 0.001 1.000 Parameter B for customer
programmable curve for OV2
C_OV2 0.000 - 1.000 - 0.001 1.000 Parameter C for customer
programmable curve for OV2
D_OV2 0.000 - 10.000 - 0.001 0.000 Parameter D for customer
programmable curve for OV2
P_OV2 0.001 - 10.000 - 0.001 0.020 Parameter P for customer
programmable curve for OV2
ResCrvType_UV1 Instantaneous - - Instantaneous Selection of reset curve type for UV1
Frozen timer
Linearly
decreased
tResetDef_UV1 0.00 - 6000.00 s 0.01 0.00 Reset time delay in sec for definite
time use of UV1
tResetIDMT_UV1 0.00 - 6000.00 s 0.01 0.00 Reset time delay in sec for IDMT
curves for UV1
A_UV1 0.005 - 999.000 - 0.001 0.140 Parameter A for customer
programmable curve for UV1
B_UV1 0.500 - 99.000 - 0.001 1.000 Parameter B for customer
programmable curve for UV1
C_UV1 0.000 - 1.000 - 0.001 1.000 Parameter C for customer
programmable curve for UV1
D_UV1 0.000 - 10.000 - 0.001 0.000 Parameter D for customer
programmable curve for UV1
P_UV1 0.001 - 10.000 - 0.001 0.020 Parameter P for customer
programmable curve for UV1
ResCrvType_UV2 Instantaneous - - Instantaneous Selection of reset curve type for UV2
Frozen timer
Linearly
decreased
tResetDef_UV2 0.00 - 6000.00 s 0.01 0.00 Reset time delay in sec for definite
time use of UV2
tResetIDMT_UV2 0.00 - 6000.00 s 0.01 0.00 Reset time delay in sec for IDMT
curves for UV2
A_UV2 0.005 - 999.000 - 0.001 0.140 Parameter A for customer
programmable curve for UV2
B_UV2 0.500 - 99.000 - 0.001 1.000 Parameter B for customer
programmable curve for UV2
Table continues on next page

Line distance protection REL670 627


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 12 1MRK 506 370-UEN J
Multipurpose protection

Name Values (Range) Unit Step Default Description


C_UV2 0.000 - 1.000 - 0.001 1.000 Parameter C for customer
programmable curve for UV2
D_UV2 0.000 - 10.000 - 0.001 0.000 Parameter D for customer
programmable curve for UV2
P_UV2 0.001 - 10.000 - 0.001 0.020 Parameter P for customer
programmable curve for UV2

Table 414: CVGAPC Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

12.1.6 Monitored data


PID-3857-MONITOREDDATA v7

Table 415: CVGAPC Monitored data


Name Type Values (Range) Unit Description
DIROC1 INTEGER 1=Forward - Directional mode of OC1 (nondir,
0=Non- forward,reverse)
directional
2=Reverse
DIROC2 INTEGER 1=Forward - Directional mode of OC2 (nondir,
0=Non- forward,reverse)
directional
2=Reverse
CURRENT REAL - A Measured current value
ICOSFI REAL - A Measured current multiplied with cos
(Phi)
VOLTAGE REAL - kV Measured voltage value
UIANGLE REAL - deg Angle between voltage and current

12.1.7 Operation principle

12.1.7.1 Measured quantities within CVGAPC M13751-3 v4

General current and voltage protection (CVGAPC) function is always connected to three-phase
current and three-phase voltage input in the configuration tool, but it will always measure only
one current and one voltage quantity selected by the end user in the setting tool.

The user can select a current input, by a setting parameter CurrentInput, to measure one of
the current quantities shown in table 416.

628 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 12
Multipurpose protection

Table 416: Current selection for CVGAPC function


Set value for the
parameter Comment
CurrentInput
1 Phase1 CVGAPC function will measure the phase L1 current phasor
2 Phase2 CVGAPC function will measure the phase L2 current phasor
3 Phase3 CVGAPC function will measure the phase L3 current phasor
4 PosSeq CVGAPC function will measure internally calculated positive sequence current
phasor
5 NegSeq CVGAPC function will measure internally calculated negative sequence current
phasor
6 3ZeroSeq CVGAPC function will measure internally calculated zero sequence current phasor
multiplied by factor 3
7 MaxPh CVGAPC function will measure current phasor of the phase with maximum
magnitude
8 MinPh CVGAPC function will measure current phasor of the phase with minimum
magnitude
9 UnbalancePh CVGAPC function will measure magnitude of unbalance current, which is
internally calculated as the algebraic magnitude difference between the current
phasor of the phase with maximum magnitude and current phasor of the phase
with minimum magnitude. Phase angle will be set to 0° all the time
10 Phase1-Phase2 CVGAPC function will measure the current phasor internally calculated as the
vector difference between the phase L1 current phasor and phase L2 current
phasor (IL1-IL2)

11 Phase2-Phase3 CVGAPC function will measure the current phasor internally calculated as the
vector difference between the phase L2 current phasor and phase L3 current
phasor (IL2-IL3)

12 Phase3-Phase1 CVGAPC function will measure the current phasor internally calculated as the
vector difference between the phase L3 current phasor and phase L1 current
phasor ( IL3-IL1)

13 MaxPh-Ph CVGAPC function will measure ph-ph current phasor with the maximum
magnitude
14 MinPh-Ph CVGAPC function will measure ph-ph current phasor with the minimum
magnitude
15 UnbalancePh-Ph CVGAPC function will measure magnitude of unbalance current, which is
internally calculated as the algebraic magnitude difference between the ph-ph
current phasor with maximum magnitude and ph-ph current phasor with
minimum magnitude. Phase angle will be set to 0° all the time

The user can select a voltage input, by a setting parameter VoltageInput, to measure one of
the voltage quantities shown in table 417:

Table 417: Voltage selection for CVGAPC function


Set value for the
parameter Comment
VoltageInput
1 Phase1 CVGAPC function will measure the phase L1 voltage phasor
2 Phase2 CVGAPC function will measure the phase L2 voltage phasor
3 Phase3 CVGAPC function will measure the phase L3 voltage phasor
4 PosSeq CVGAPC function will measure internally calculated positive sequence voltage
phasor
Table continues on next page

Line distance protection REL670 629


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 12 1MRK 506 370-UEN J
Multipurpose protection

Set value for the


parameter Comment
VoltageInput
5 -NegSeq CVGAPC function will measure internally calculated negative sequence voltage
phasor. This voltage phasor will be intentionally rotated for 180° in order to
enable easier settings for the directional feature when used.
6 -3ZeroSeq CVGAPC function will measure internally calculated zero sequence voltage phasor
multiplied by factor 3. This voltage phasor will be intentionally rotated for 180° in
order to enable easier settings for the directional feature when used.
7 MaxPh CVGAPC function will measure voltage phasor of the phase with maximum
magnitude
8 MinPh CVGAPC function will measure voltage phasor of the phase with minimum
magnitude
9 UnbalancePh CVGAPC function will measure magnitude of unbalance voltage, which is
internally calculated as the algebraic magnitude difference between the voltage
phasor of the phase with maximum magnitude and voltage phasor of the phase
with minimum magnitude. Phase angle will be set to 0° all the time
10 Phase1-Phase2 CVGAPC function will measure the voltage phasor internally calculated as the
vector difference between the phase L1 voltage phasor and phase L2 voltage
phasor (UL1-UL2)

11 Phase2-Phase3 CVGAPC function will measure the voltage phasor internally calculated as the
vector difference between the phase L2 voltage phasor and phase L3 voltage
phasor (UL2-UL3)

12 Phase3-Phase1 CVGAPC function will measure the voltage phasor internally calculated as the
vector difference between the phase L3 voltage phasor and phase L1 voltage
phasor ( UL3-UL1)

13 MaxPh-Ph CVGAPC function will measure ph-ph voltage phasor with the maximum
magnitude
14 MinPh-Ph CVGAPC function will measure ph-ph voltage phasor with the minimum
magnitude
15 UnbalancePh-Ph CVGAPC function will measure magnitude of unbalance voltage, which is
internally calculated as the algebraic magnitude difference between the ph-ph
voltage phasor with maximum magnitude and ph-ph voltage phasor with
minimum magnitude. Phase angle will be set to 0° all the time

Note that the voltage selection from table 417 is always applicable regardless the actual
external VT connections. The three-phase VT inputs can be connected to IED as either three
phase-to-earth voltages, UL1, UL2 and UL3, , and or three phase-to-phase voltages UL1L2, UL2L3
and UL3L1, , and . This information about actual VT connection is entered as a setting
parameter for the pre-processing block, which will then be taken care automatically.

The user can select one of the current quantities shown in table 418 for built-in current
restraint feature:

Table 418: Restraint current selection for CVGAPC function


Set value for the
parameter RestrCurr Comment
1 PosSeq CVGAPC function will measure internally calculated positive sequence current
phasor
2 NegSeq CVGAPC function will measure internally calculated negative sequence current
phasor
3 3ZeroSeq CVGAPC function will measure internally calculated zero sequence current phasor
multiplied by factor 3
4 MaxPh CVGAPC function will measure current phasor of the phase with maximum
magnitude

630 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 12
Multipurpose protection

12.1.7.2 Base quantities for CVGAPC function SEMOD53443-112 v4

The parameter settings for the base quantities, which represent the base (100%) for pickup
levels of all measuring stages shall be entered as setting parameters for every CVGAPC
function.

Base current shall be entered as:

1. rated phase current of the protected object in primary amperes, when the measured
Current Quantity is selected from 1 to 9, as shown in table "".
2. rated phase current of the protected object in primary amperes multiplied by √3 (1.732 x
Iphase), when the measured Current Quantity is selected from 10 to 15, as shown in table
"".

Base voltage shall be entered as:

1. rated phase-to-earth voltage of the protected object in primary kV, when the measured
Voltage Quantity is selected from 1 to 9, as shown in table "".
2. rated phase-to-phase voltage of the protected object in primary kV, when the measured
Voltage Quantity is selected from 10 to 15, as shown in table "".

12.1.7.3 Built-in overcurrent protection steps M13751-136 v3

Two overcurrent protection steps are available. They are absolutely identical and therefore
only one will be explained here.

Overcurrent step simply compares the magnitude of the measured current quantity (see
table 416) with the set pickup level. Non-directional overcurrent step will pickup if the
magnitude of the measured current quantity is bigger than this set level. However depending
on other enabled built-in features this overcurrent pickup might not cause the overcurrent
step start signal. Start signal will only come if all of the enabled built-in features in the
overcurrent step are fulfilled at the same time.

Second harmonic feature M13751-254 v3


The overcurrent protection step can be restrained by a second harmonic component in the
measured current quantity (see table 416). However it shall be noted that this feature is not
applicable when one of the following measured currents is selected:

• PosSeq (positive sequence current)


• NegSeq (negative sequence current)
• UnbalancePh (unbalance phase current)
• UnbalancePh-Ph (unbalance phase-phase current)

This feature will prevent overcurrent step start if the second-to-first harmonic ratio in the
measured current exceeds the set level.

Directional feature M13751-263 v5


The overcurrent protection step operation can be made dependent on the relevant phase
angle between measured current phasor (see table 416) and measured voltage phasor (see
table 417). In protection terminology it means that the General currrent and voltage protection
(CVGAPC) function can be made directional by enabling this built-in feature. In that case
overcurrent protection step will only operate if the current flow is in accordance with the set
direction (Forward, which means towards the protected object, or Reverse, which means from
the protected object). For this feature it is of the outmost importance to understand that the
measured voltage phasor (see table 417) and measured current phasor (see table 416) will be
used for directional decision. Therefore it is the sole responsibility of the end user to select the
appropriate current and voltage signals in order to get a proper directional decision. CVGAPC

Line distance protection REL670 631


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 12 1MRK 506 370-UEN J
Multipurpose protection

function will NOT do this automatically. It will simply use the current and voltage phasors
selected by the end user to check for the directional criteria.

Table 419 gives an overview of the typical choices (but not the only possible ones) for these
two quantities from traditional directional relays.

Table 419: Typical current and voltage choices for directional feature
Set value for the Set value for the
parameter parameter Comment
CurrentInput VoltageInput
PosSeq PosSeq Directional positive sequence overcurrent function is obtained.
Typical setting for RCADir is from 45° to 90° depending on the
power system voltage level (X/R ratio)
NegSeq -NegSeq Directional negative sequence overcurrent function is obtained.
Typical setting for RCADir is from 45° to 90° depending on the
power system voltage level (X/R ratio)
3ZeroSeq -3ZeroSeq Directional zero sequence overcurrent function is obtained.
Typical setting for RCADir is from 0° to 90° depending on the
power system earthing (that is, solidly earthed, earthed via
resistor)
Phase1 Phase2-Phase3 Directional overcurrent function for the first phase is obtained.
Typical setting for RCADir is +30° or +45°
Phase2 Phase3-Phase1 Directional overcurrent function for the second phase is
obtained. Typical setting for RCADir is +30° or +45°
Phase3 Phase1-Phase2 Directional overcurrent function for the third phase is obtained.
Typical setting for RCADir is +30° or +45°

Unbalance current or voltage measurement shall not be used when the directional feature is
enabled.

Two types of directional measurement principles are available, I & U and IcosPhi&U. The first
principle, referred to as "I & U" in the parameter setting tool, checks that:

• the magnitude of the measured current is bigger than the set pick-up level
• the phasor of the measured current is within the operating region (defined by the relay
operate angle, ROADir parameter setting; see figure 364).

632 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 12
Multipurpose protection

U=-3U0
RCADir

Ipickup ROADir I=3Io

Operate region
MTA line
IEC05000252-2-en.vsd

IEC05000252 V2 EN-US

Figure 364: I & U directional operating principle for CVGAPC function

where:
RCADir is 75°
ROADir is 50°

The second principle, referred to as "IcosPhi&U" in the parameter setting tool, checks that:

• that the product I·cos(Φ) is bigger than the set pick-up level, where Φ is angle between the
current phasor and the mta line
• that the phasor of the measured current is within the operating region (defined by the
I·cos(Φ) straight line and the relay operate angle, ROADir parameter setting; see
figure 364).

U=-3U0

Ipickup ROADir  I=3Io

Operate region
MTA line
IEC05000253-2-en.vsdx

IEC05000253 V2 EN-US

Figure 365: CVGAPC, IcosPhi&U directional operating principle

where:
RCADir is 75°
ROADir is 50°

Line distance protection REL670 633


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 12 1MRK 506 370-UEN J
Multipurpose protection

Note that it is possible to decide by a parameter setting how the directional feature shall
behave when the magnitude of the measured voltage phasor falls below the pre-set value.
User can select one of the following three options:

• Non-directional (operation allowed for low magnitude of the reference voltage)


• Block (operation prevented for low magnitude of the reference voltage)
• Memory (memory voltage shall be used to determine direction of the current)

It shall also be noted that the memory duration is limited in the algorithm to 100 ms. After that
time the current direction will be locked to the one determined during memory time and it will
re-set only if the current fails below set pickup level or voltage goes above set voltage memory
limit.

Voltage restraint/control feature M13751-326 v4


The overcurrent protection step operation can be made dependent of a measured voltage
quantity (see table 417). Practically then the pickup level of the overcurrent step is not
constant but instead decreases with the decrease in the magnitude of the measured voltage
quantity. Two different types of dependencies are available:

• Voltage restraint overcurrent (when setting parameter VDepMode_OC1=Slope)

OC1 Stage Pickup Level

StartCurr_OC1

VDepFact_OC1 * StartCurr_OC1

ULowLimit_OC1 UHighLimit_OC1
Selected Voltage
Magnitude
en05000324.vsd
IEC05000324 V1 EN-US

Figure 366: Example for OC1 step current pickup level variation as function of measured
voltage magnitude in Slope mode of operation

• Voltage controlled overcurrent (when setting parameter VDepMode_OC1=Step)

634 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 12
Multipurpose protection

OC1 Stage Pickup Level

StartCurr_OC1

VDepFact_OC1 * StartCurr_OC1

UHighLimit_OC1 Selected Voltage Magnitude

en05000323.vsd
IEC05000323 V1 EN-US

Figure 367: Example for OC1 step current pickup level variation as function of measured
voltage magnitude in Step mode of operation
This feature will simply change the set overcurrent pickup level in accordance with magnitude
variations of the measured voltage. It shall be noted that this feature will as well affect the
pickup current value for calculation of operate times for IDMT curves (overcurrent with IDMT
curve will operate faster during low voltage conditions).

Current restraint feature M13751-338 v3


The overcurrent protection step operation can be made dependent of a restraining current
quantity (see table 418). Practically then the pickup level of the overcurrent step is not
constant but instead increases with the increase in the magnitude of the restraining current.

IMeasured
ea ain
ar str
e Ire
at ff*
per e
O Co
estr
I>R
IsetHigh

IsetLow

atan(RestrCoeff)

Restraint
en05000255.vsd
IEC05000255 V1 EN-US

Figure 368: Current pickup variation with restraint current magnitude


This feature will simply prevent overcurrent step to start if the magnitude of the measured
current quantity is smaller than the set percentage of the restrain current magnitude. However
this feature will not affect the pickup current value for calculation of operate times for IDMT
curves. This means that the IDMT curve operate time will not be influenced by the restrain
current magnitude.

Line distance protection REL670 635


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 12 1MRK 506 370-UEN J
Multipurpose protection

When set, the start signal will start definite time delay or inverse (IDMT) time delay in
accordance with the end user setting. If the start signal has value one for longer time than the
set time delay, the overcurrent step will set its trip signal to one. Reset of the start and trip
signal can be instantaneous or time delay in accordance with the end user setting.

12.1.7.4 Built-in undercurrent protection steps M13751-231 v2

Two undercurrent protection steps are available. They are absolutely identical and therefore
only one will be explained here. Undercurrent step simply compares the magnitude of the
measured current quantity (see table 416) with the set pickup level. The undercurrent step will
pickup and set its start signal to one if the magnitude of the measured current quantity is
smaller than this set level. The start signal will start definite time delay with set time delay. If
the start signal has value one for longer time than the set time delay the undercurrent step will
set its trip signal to one. Reset of the start and trip signal can be instantaneous or time delay
in accordance with the setting.

12.1.7.5 Built-in overvoltage protection steps M13751-234 v3

Two overvoltage protection steps are available. They are absolutely identical and therefore
only one will be explained here.

Overvoltage step simply compares the magnitude of the measured voltage quantity (see
table 417) with the set pickup level. The overvoltage step will pickup if the magnitude of the
measured voltage quantity is bigger than this set level.

The start signal will start definite time delay or inverse (IDMT) time delay in accordance with
the end user setting. If the start signal has value one for longer time than the set time delay,
the overvoltage step will set its trip signal to one. Reset of the start and trip signal can be
instantaneous or time delay in accordance with the end user setting.

12.1.7.6 Built-in undervoltage protection steps M13751-239 v3

Two undervoltage protection steps are available. They are absolutely identical and therefore
only one will be explained here.

Undervoltage step simply compares the magnitude of the measured voltage quantity (see
table 417) with the set pickup level. The undervoltage step will pickup if the magnitude of the
measured voltage quantity is smaller than this set level.

The start signal will start definite time delay or inverse (IDMT) time delay in accordance with
the end user setting. If the start signal has value one for longer time than the set time delay,
the undervoltage step will set its trip signal to one. Reset of the start and trip signal can be
instantaneous or time delay in accordance with the end user setting.

12.1.7.7 Logic diagram M13085-3 v7

The simplified internal logics, for CVGAPC function are shown in the following figures.

The following currents and voltages are inputs to the multipurpose protection function. They
must all be expressed in true power system (primary) Amperes and kilovolts.

1. Instantaneous values (samples) of currents & voltages from one three-phase current and
one three-phase voltage input.
2. Fundamental frequency phasors from one three-phase current and one three-phase
voltage input calculated by the pre-processing modules.
3. Sequence currents & voltages from one three-phase current and one three-phase voltage
input calculated by the pre-processing modules.

636 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 12
Multipurpose protection

The multipurpose protection function:

1. Selects one current from the three-phase input system (see table 416) for internally
measured current.
2. Selects one voltage from the three-phase input system (see table 417) for internally
measured voltage.
3. Selects one current from the three-phase input system (see table 418) for internally
measured restraint current.

Line distance protection REL670 637


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 12 1MRK 506 370-UEN J
Multipurpose protection

CURRENT

UC1
TRUC1
2nd Harmonic
Selected current restraint
STUC2
UC2
nd
TRUC2
2 Harmonic
restraint

STOC1
OC1 TROC1

2nd Harmonic BLK2ND


restraint ³1
Selected restraint current
Current restraint
DIROC1
Directionality
Voltage control /
restraint

STOC2
OC2 TROC2

2nd Harmonic
restraint
Current restraint ³1
UDIRLOW

Directionality DIROC2

Voltage control /
restraint

STOV1
OV1 TROV1

STOV2
OV2 TROV2

STUV1
Selected voltage
UV1 TRUV1

STUV2
UV2 TRUV2

VOLTAGE

en05000170.vsd
IEC05000170 V1 EN-US

Figure 369: CVGAPC function main logic diagram for built-in protection elements
Logic in figure 369 can be summarized as follows:

638 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 12
Multipurpose protection

1. The selected currents and voltage are given to built-in protection elements. Each
protection element and step makes independent decision about status of its START and
TRIP output signals.
2. More detailed internal logic for every protection element is given in the following four
figures.
3. Common START and TRIP signals from all built-in protection elements & steps (internal OR
logic) are available from multipurpose function as well.

a
a>b AND
BlkLevel2nd b

Enable
second Second harmonic
harmonic check DEF time BLKTRO C1 TROC1
selected DEF AND
OR
a
a>b
b
OC1=On STOC1
AND
StartCurr_OC1 BLKOC1
X
Inverse

Voltage Directionali ty DIR_OK Inverse


control or time
check selected
restrai nt
feature

Selected v oltage
Curren t
Restrai nt
Feature
Selected restrain current Imea sure d > k Irestra int

IEC05000831-2-en.vsdx

IEC05000831 V2 EN-US

Figure 370: Simplified internal logic diagram for built-in first overcurrent step that is, OC1 (step OC2 has
the same internal logic)

Bin input: BLKUC1TR

Selected current a TRUC1


b>a
DEF AND
b
StartCurr_UC1
AND

Operation_UC1=On
STUC1

Bin input: BLKUC1

en05000750.vsd

IEC05000750 V1 EN-US

Figure 371: Simplified internal logic diagram for built-in first undercurrent step that is, UC1 (step UC2
has the same internal logic)

Line distance protection REL670 639


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 12 1MRK 506 370-UEN J
Multipurpose protection

DEF time BLKTROV1


selected DEF TROV1
AND
OR
Selected voltage a
a>b
b STOV1
StartVolt_OV1
AND

Inverse
Operation_OV1=On
Inverse time
BLKOV1 selected

en05000751.vsd

IEC05000751 V1 EN-US

Figure 372: Simplified internal logic diagram for built-in first overvoltage step OV1 (step OV2 has the
same internal logic)

DEF time BLKTRUV


selected DEF 1 TRUV1
AND
OR
Selected voltage a
b>a
b STUV1
AND
StartVolt_UV1

Inverse
Operation_UV1=On
Inverse time
BLKUV1 selected

en05000752.vsd

IEC05000752 V1 EN-US

Figure 373: Simplified internal logic diagram for built-in first undervoltage step UV1 (step UV2 has the
same internal logic)

640 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 12
Multipurpose protection

12.1.8 Technical data


M13095-2 v11

Table 420: CVGAPC technical data


Function Range or value Accuracy
Measuring current input phase1, phase2, phase3, PosSeq, - -
NegSeq, -3*ZeroSeq, MaxPh,
MinPh, UnbalancePh, phase1-
phase2, phase2-phase3, phase3-
phase1, MaxPh-Ph, MinPh-Ph,
UnbalancePh-Ph
Measuring voltage input phase1, phase2, phase3, PosSeq, - -
NegSeq, -3*ZeroSeq, MaxPh,
MinPh, UnbalancePh, phase1-
phase2, phase2-phase3, phase3-
phase1, MaxPh-Ph, MinPh-Ph,
UnbalancePh-Ph
Start overcurrent, step 1 - 2 (2 - 5000)% of IBase ±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir

Start undercurrent, step 1 - 2 (2 - 150)% of IBase ±1.0% of Ir at I ≤ Ir


±1.0% of I at I > Ir

Independent time delay, overcurrent (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is


at 0 to 2 x Iset, step 1 - 2 greater

Independent time delay, undercurrent (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is


at 2 x Iset to 0, step 1 - 2 greater

Overcurrent (non-directional):
Start time at 0 to 2 x Iset Min. = 15 ms -
Max. = 30 ms
Reset time at 2 x Iset to 0 Min. = 15 ms -
Max. = 30 ms
Start time at 0 to 10 x Iset Min. = 5 ms -
Max. = 20 ms
Reset time at 10 x Iset to 0 Min. = 20 ms -
Max. = 35 ms
Undercurrent:
Start time at 2 x Iset to 0 Min. = 15 ms -
Max. = 30 ms
Reset time at 0 to 2 x Iset Min. = 15 ms -
Max. = 30 ms
Overcurrent:
Inverse time characteristics, see table 16 curve types See table 1150, 1151 and table
1150, 1151 and table 1152 1152
Overcurrent:
Minimum operate time for inverse (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is
curves, step 1 - 2 greater
Voltage level where voltage memory (0.0 - 5.0)% of UBase ±0.5% of Ur
takes over
Start overvoltage, step 1 - 2 (2.0 - 200.0)% of UBase ±0.5% of Ur at U ≤ Ur
±0.5% of U at U > Ur

Start undervoltage, step 1 - 2 (2.0 - 150.0)% of UBase ±0.5% of Ur at U ≤ Ur


±0.5% of U at U > Ur

Independent time delay, overvoltage (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is


at 0.8 x Uset to 1.2 x Uset, step 1 - 2 greater

Table continues on next page

Line distance protection REL670 641


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 12 1MRK 506 370-UEN J
Multipurpose protection

Function Range or value Accuracy


Independent time delay, undervoltage (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is
at 1.2 x Uset to 0.8 x Uset, step 1 - 2 greater

Overvoltage:
Start time at 0.8 x Uset to 1.2 x Uset Min. = 15 ms -
Max. = 30 ms
Reset time at 1.2 x Uset to 0.8 x Uset Min. = 15 ms -
Max. = 30 ms
Undervoltage:
Start time at 1.2 x Uset to 0.8 x Uset Min. = 15 ms -
Max. = 30 ms
Reset time at 1.2 x Uset to 0.8 x Uset Min. = 15 ms -
Max. = 30 ms
Overvoltage:
Inverse time characteristics, see table 4 curve types See table 1158
1158
Undervoltage:
Inverse time characteristics, see table 3 curve types See table 1159
1159
High and low voltage limit, voltage (1.0 - 200.0)% of UBase ±1.0% of Ur at U ≤ Ur
dependent operation, step 1 - 2 ±1.0% of U at U > Ur

Directional function Settable: NonDir, forward and -


reverse
Relay characteristic angle (-180 to +180) degrees ±2.0 degrees
Relay operate angle (1 to 90) degrees ±2.0 degrees
Reset ratio, overcurrent > 95% -
Reset ratio, undercurrent < 105% -
Reset ratio, overvoltage > 95% -
Reset ratio, undervoltage < 105% -
Operate frequency 10-90 Hz -
Overcurrent:
Critical impulse time 10 ms typically at 0 to 2 x Iset -

Impulse margin time 15 ms typically -


Undercurrent:
Critical impulse time 10 ms typically at 2 x Iset to 0 -

Impulse margin time 15 ms typically -


Overvoltage:
Critical impulse time 10 ms typically at 0.8 x Uset to 1.2 x -
Uset

Impulse margin time 15 ms typically -


Undervoltage:
Critical impulse time 10 ms typically at 1.2 x Uset to 0.8 x -
Uset

Impulse margin time 15 ms typically -

642 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 13
System protection and control

Section 13 System protection and control


13.1 Multipurpose filter SMAIHPAC GUID-6B541154-D56B-452F-B143-4C2A1B2D3A1F v1

13.1.1 Identification GUID-8224B870-3DAA-44BF-B790-6600F2AD7C5D v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Multipurpose filter SMAIHPAC - -

13.1.2 Functionality GUID-EB0B11C3-FF79-4B8D-A335-649623E832F9 v3

The multi-purpose filter function block (SMAIHPAC) is arranged as a three-phase filter. It has
very much the same user interface (e.g. inputs and outputs) as the standard pre-processing
function block SMAI. However the main difference is that it can be used to extract any
frequency component from the input signal. Thus it can, for example, be used to build sub-
synchronous resonance protection for synchronous generator.

13.1.3 Function block GUID-FA590757-0DB1-4605-9DE2-20FA8304795F v1

SMAIHPAC
BLOCK AI3P
G3P* AI1
AI2
AI3
AI4

IEC13000180-1-en.vsd
IEC13000180 V1 EN-US

13.1.4 Signals GUID-DF7C833A-9AB9-40CA-867B-950AC1F662B5 v1

PID-6733-INPUTSIGNALS v1

Table 421: SMAIHPAC Input signals


Name Type Default Description
G3P GROUP - Analog input group from SMAI
SIGNAL
BLOCK BOOLEAN 0 Block of function

PID-6733-OUTPUTSIGNALS v1

Table 422: SMAIHPAC Output signals


Name Type Description
AI3P GROUP SIGNAL Analog input 3-phase group
AI1 GROUP SIGNAL Analog input 1
AI2 GROUP SIGNAL Analog input 2
AI3 GROUP SIGNAL Analog input 3
AI4 GROUP SIGNAL Analog input 4

Line distance protection REL670 643


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 13 1MRK 506 370-UEN J
System protection and control

13.1.5 Settings GUID-5EA398AD-66E2-4240-8918-4332995CED11 v1

PID-6733-SETTINGS v1

Table 423: SMAIHPAC Non group settings (basic)


Name Values (Range) Unit Step Default Description
ConnectionType Ph - Ph - - Ph - N Analogue input connection type
Ph - N
SetFrequency 2.0 - 500.0 Hz 0.1 50.0 Desired frequency to be extracted by
the filter
FreqBandWidth 0.0 - 60.0 Hz 0.1 0.0 Extra added frequency band around
the set frequency
FilterLength 0.1 s - - 1.0 s Approximate length of the filtering
0.2 s window in seconds
0.5 s
1.0 s
2.0 s
4.0 s
OverLap 0 - 95 % 5 20 Filtering window overlap between two
calculations in percent

13.1.6 Operation principle GUID-262C1783-3A0A-46B6-99FC-1202AE8E7519 v2

For all four analogue input signals into this filter (i.e. three phases and the residual quantity)
the input samples from the TRM module which are coming at rate of 20 samples per
fundamental system cycle are first stored. When enough samples are available in the internal
memory, the phasor values at set frequency defined by the setting parameter SetFrequency
are calculated. The following values are internally available for each of the calculated phasors:

• Magnitude
• Phase angle
• Exact frequency of the extracted signal

Note that the special filtering algorithm is used to extract these phasors. This algorithm is
different from the standard one-cycle Digital Fourier Filter typically used by the numerical
IEDs. This filter provides extremely good accuracy of measurement and excellent noise
rejection, but at the same time it has much slower response time. It is capable to extract
phasor (i.e. magnitude, phase angle and actual frequency) of any signal (e.g. 37,2Hz) present in
the waveforms of the connected CTs and/or VTs. The magnitude and the phase angle of this
phasor are calculated with very high precision. For example the magnitude and phase angle of
the phasor can be estimated even if it has magnitude of one per mille (i.e. 1‰ ) in comparison
to the dominating signal (e.g. the fundamental frequency component). Several instances of
this function block are provided. These instances are fully synchronized between each-other in
respect of phase angle calculation. Thus if two multi-purpose filters are used for some
application, one for current and the second one for the voltage signals, the power values (i.e. P
& Q) at the set frequency can be calculated from them by the over-/under-power function or
CVMMXN measurement function block.

In addition to these phasors the following quantities are internally calculated as well:

• Phasors for the individual phases as well as phase-to-phase phasors


• True RMS value of the input signal over all samples available in the memory
• Positive sequence phasor
• Negative sequence phasor
• Zero sequence phasor
• etc.

644 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 13
System protection and control

In order to properly calculate phase-to-phase phasors from the individual phase phasors or
vice versa, the setting parameters ConnectionType is provided. It defines what quantities (i.e.
individual phases or phase-to-phase quantities) are physically connected to the IED analogue
inputs by wiring. Then the IED knows which one of them are the measured quantities and the
other one is then internally calculated. This setting is only important for the VT inputs, because
the CTs are typically star connected all the time.

Thus when this filter is used in conjunction with multi-purpose protection function or
overcurrent function or over-voltage function or over-power function many different
protection applications can be arranged. For example the following protection, monitoring or
measurement features can be realized:

• Sub-synchronous resonance protection for turbo generators


• Sub-synchronous protection for wind turbines/wind farms
• Detection of sub-synchronous oscillation between HVDC links and synchronous
generators
• Super-synchronous protection
• Detection of presence of the geo-magnetic induced currents
• Overcurrent or overvoltage protection at specific frequency harmonic, sub-harmonic,
inter-harmonic etc.
• Presence of special railway frequencies (e.g. 16.7Hz or 25Hz) in the three-phase power
system
• Sensitive reverse power protection
• Stator or rotor earth fault protection for special injection frequencies (e.g. 25Hz)
• etc.

The filter output can also be connected to the measurement function blocks such as CVMMXN
(Measurements), CMMXU (Phase current measurement), VMMXU (Phase-phase voltage
measurement), etc.

The filter has as well additional capability to report the exact frequency of the extracted signal.
Thus the user can check the actual frequency of some phenomenon in the power system (e.g.
frequency of the sub-synchronous currents) and compare it with expected value obtained
previously by either calculation or simulation. For the whole three-phase filter group the
frequency of the signal connected to the first input (i.e. phase L1) is reported. This value can be
then used either by over-/under-frequency protections or reported to the built-in HMI or any
other external client via the measurement blocks such is the CVMMXN.

How many samples in the memory are used for the phasor calculation depends on the setting
parameter FilterLength. Table 424 gives overview of the used number of samples for phasor
calculation by the filter. Note that the used number of samples is always a power of number
two.

Table 424: Length of the filtering window


Value for parameter Used No of samples for Corresponding length of Corresponding length of
FilterLength calculation (fixed, the input waveform in the input waveform in
independent from rated miliseconds for 50Hz miliseconds for 60Hz
frequency) power system power system
0.1 s 128 = 27 128 ms 107 ms

0.2 s 256 = 28 256 ms 213 ms

0.5 s 512 = 29 512 ms 427 ms

1.0 s 1024 = 210 1024 ms 853 ms

2.0 s 2048 = 211 2048 ms 1707 ms

4.0 s 4096 = 212 4096 ms 3413 ms

Line distance protection REL670 645


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 13 1MRK 506 370-UEN J
System protection and control

Note that the selected value for the parameter FilterLength automatically defines certain filter
properties as described below:

First in order to secure proper filter operation the selected length of the filter shall always be
longer than three complete periods of the signal which shall be extracted. Actually the best
results are obtained if at least five complete periods are available within the filtering window.
Thus, this filter feature will limit which filter lengths can be used to extract low frequency
signals. For example if 16,7 Hz signal shall be extracted the minimum filter length in
milliseconds shall be:

1000
3× = 180ms
16.7
EQUATION000028 V1 EN-US (Equation 175)

Thus based on the data from Table 424 the minimum acceptable value for this parameter
would be “FilterLength = 0.2 s” but more accurate results will be obtained by using
“FilterLength = 0.5 s”

Second feature which is determined by the selected value for parameter FilterLength is the
capability of the filter to separate the desired signal from the other disturbing signals which
may have similar frequency value. Note that the filter output will be the phasor with the
highest magnitude within certain “pass frequency band” around the SetFrequency. Table 425
defines the natural size of this pass frequency band for the filter, depending on the selected
value for parameter FilterLength.

Table 425: Pass frequency band due to FilterLength


Value for parameter FilterLength For 50Hz power system For 60Hz power system
0.1 s ±22.5 Hz ±27.0 Hz
0.2 s ±11.5 Hz ±14.0 Hz
0.5 s ±6.0 Hz ±7.2 Hz
1.0 s ±3.0 Hz ±3.6 Hz
2.0 s ±1.5 Hz ±1.8 Hz
4.0 s ±0.8 Hz ±1.0 Hz

Thus the longer length of the filter the better capability it has to reject the disturbing signals
close to the required frequency component and any other noise present in the input signal
waveform. For example if 46 Hz signal wants to be extracted in 50Hz power system, then from
Table 425 it can be concluded that “FilterLength=1,0 s” shall be selected as a minimum value.
However if frequency deviation of the fundamental frequency signal in the power system are
taken into account it may be advisable to select “FilterLength=2,0 s” for such application.

Note that in case when no clear magnitude peak exist in the set pass frequency band the filter
will return zero values for the phasor magnitude and angle while the signal frequency will have
value minus one. Finally the set value for parameter FilterLength also defines the response
time of the filter after a step change of the measured signal. The filter will correctly estimate
the new signal magnitude once 75% of the filter length has been filed with the new signal value
(i.e. after the change).

If for any reason this natural frequency band shall be extended (e.g. to get accurate but wider
filter) it is possible to increase the pass band by entering the value different from zero for
parameter FreqBandWidth. In such case the total filter pass band can be defined as:

± (value given in Table 425 + one-half of the set FreqBandWidth value)

Example if in 60Hz system the selected values are “FilterLength =1.0 s” and “FreqBandWidth =
5.0” the total filter pass band will be ±(3.6+5.0/2)= ± 6.1 Hz.

646 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 13
System protection and control

It shall be noted that the phasor calculation is relatively computation demanding (required
certain amount of the CPU processing time). In order to control the CPU usage for this filter,
the setting parameter OverLap is used. This setting parameter defines how often the new
phasor value is calculated during time period defined by the set value for the parameter
FilterLength (see Table 424). The following list gives some examples how this parameter
influence the calculation rate for the extracted phasor:

• when OverLap=0% the new phasor value is calculated only once per FilterLength
• when OverLap=50% the new phasor value is calculated two times per FilterLength
• when OverLap=75% the new phasor value is calculated four times per FilterLength
• when OverLap=90% the new phasor value is calculated ten times per FilterLength

13.1.7 Filter calculation example GUID-F5828B0A-CED3-483E-B5B1-F389C3C2AEFB v3

In the following Figure an example from an installation of this filter on a large, 50 Hz turbo
generator with a rating in excess of 1000 MVA is presented. In this installation filter is used to
measure the stator sub-synchronous resonance currents. For this particular installation the
following settings were used for the filter:

• SetFrequency= 31.0 Hz
• FilterLength= 1.0 s
• OverLap = 75%
• FreqBandWidth= 0.0 Hz

IEC13000178-2-en.vsd
IEC13000178 V3 EN-US

Figure 374: Example of filter calculation


The data shown in the Figure comes from the comtrade file captured by the IED. The following
traces are presented in this Figure.

a) Waveforms of the stator three-phase currents given in primary kA.

b) RMS value of the sub-synchronous resonance current extracted by the filter in primary
amperes.

Line distance protection REL670 647


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 13 1MRK 506 370-UEN J
System protection and control

c) Frequency of the extracted sub-synchronous resonance current provided by the filter in Hz.

Note the very narrow scale on the y-axle for b) and c). Such small scale as well indicates with
which precision and consistency the filter calculates the phasor magnitude and frequency of
the extracted stator sub-synchronous current component.

The following can be observed in the Figure:

• The stator total RMS current value is around 33 kA primary.


• The measured magnitude of the sub-synchronous current is around 173 A primary (that is,
0.5% of the fundamental 50 Hz component).
• The frequency of this sub-synchronous current component is 31.24 Hz.

With above given settings the sub-synchronous current magnitude and frequency are
calculated approximately four times per second (that is, correct value is four times per 1024
ms).

648 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 14
Secondary system supervision

Section 14 Secondary system supervision


14.1 Current circuit supervision CCSSPVC IP14555-1 v5

14.1.1 Identification
M14870-1 v5

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Current circuit supervision CCSSPVC - 87

14.1.2 Functionality M12444-3 v10

Open or short circuited current transformer cores can cause unwanted operation of many
protection functions such as differential, earth-fault current and negative-sequence current
functions.

Current circuit supervision (CCSSPVC) compares the residual current from a three phase set of
current transformer cores with the neutral point current on a separate input taken from
another set of cores on the current transformer.

A detection of a difference indicates a fault in the circuit and is used as alarm or to block
protection functions expected to give inadvertent tripping.

14.1.3 Function block M12436-3 v9

CCSSPVC
I3P* FAIL
IREF* ALARM
BLOCK
IEC13000304-1-en.vsd
IEC13000304 V1 EN-US

Figure 375: CCSSPVC function block

Signal ISIREF must be connected in the configuration.

14.1.4 Signals
PID-6806-INPUTSIGNALS v2

Table 426: CCSSPVC Input signals


Name Type Default Description
I3P GROUP - Group signal for three phase current input
SIGNAL
IREF GROUP - Residual reference current input
SIGNAL
BLOCK BOOLEAN 0 Block of function

Line distance protection REL670 649


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 506 370-UEN J
Secondary system supervision

PID-6806-OUTPUTSIGNALS v2

Table 427: CCSSPVC Output signals


Name Type Description
FAIL BOOLEAN Detection of current circuit failure
ALARM BOOLEAN Alarm for current circuit failure

14.1.5 Settings
PID-6806-SETTINGS v2

Table 428: CCSSPVC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
IMinOp 10 - 200 %IB 1 20 Minimum operate current differential
level in % of IBase

Table 429: CCSSPVC Group settings (advanced)


Name Values (Range) Unit Step Default Description
Ip>Block 20 - 500 %IB 1 150 Block of the function at high phase
current, in % of IBase

Table 430: CCSSPVC Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

14.1.6 Operation principle M12396-5 v10

Current circuit supervision CCSSPVC compares the absolute value of the vectorial sum of the
three phase currents |ΣIphase| and the absolute value of the residual current |Iref| from
another current transformer set, see figure 376.

The FAIL output will be set to high when the following criteria are fulfilled:

• The numerical value of the difference |ΣIphase| – |Iref| is higher than 80% of the numerical
value of the sum |ΣIphase| + |Iref|.
• The numerical value of the current |ΣIphase| – |Iref| is equal to or higher than the set
operate value IMinOp.
• No phase current has exceeded Ip>Block during the last 10 ms.
• CCSSPVC is enabled by setting Operation = On.

The FAIL output remains activated 100 ms after the AND-gate resets when being activated for
more than 20 ms. If the FAIL lasts for more than 150 ms an ALARM will be issued. In this case
the FAIL and ALARM will remain activated 1 s after the AND-gate resets. This prevents
unwanted resetting of the blocking function when phase current supervision element(s)
operate, for example, during a fault.

650 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 14
Secondary system supervision

IL1 IL1 I>1.054 * IMinOp


IL2 IL2 +
IL3 IL3  -
+ +
I ref Iref + x -
0,8
I>IP>Block
10 ms AND
OR FAIL
OR t

40 ms 100 ms

170 ms 3000 ms ALARM


OPERATION
BLOCK

IEC05000463-3-en.vsd
IEC05000463 V3 EN-US

Figure 376: Simplified logic diagram for Current circuit supervision CCSSPVC
The operate characteristic is percentage restrained, which is shown in Figure 377.

| åI phase | - | I ref |

Slope = 1

Operation
Slope = 0.8
area
I MinOp

| åI phase | + | I ref |
99000068.vsd
IEC99000068 V1 EN-US

Figure 377: Operate characteristics

Due to the formulas for the axis compared, |SIphase | - |I ref | and |S I phase | + |
I ref | respectively, the slope can not be above 1.

14.1.7 Technical data


M12358-1 v10

Table 431: CCSSPVCtechnical data


Function Range or value Accuracy
Operate current (10-200)% of IBase ±10.0% of Ir at I ≤ Ir
±10.0% of I at I > Ir

Reset ratio, Operate current >90%


Block current (20-500)% of IBase ±5.0% of Ir at I ≤ Ir
±5.0% of I at I > Ir

Reset ratio, Block current >90% at (50-500)% of IBase

Line distance protection REL670 651


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 506 370-UEN J
Secondary system supervision

14.2 Fuse failure supervision FUFSPVC IP14556-1 v3

14.2.1 Identification
M14869-1 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Fuse failure supervision FUFSPVC - -

14.2.2 Functionality SEMOD113820-4 v12

The aim of the fuse failure supervision function (FUFSPVC) is to block voltage measuring
functions at failures in the secondary circuits between the voltage transformer and the IED in
order to avoid inadvertent operations that otherwise might occur.

The fuse failure supervision function basically has three different detection methods, negative
sequence and zero sequence based detection and an additional delta voltage and delta current
detection.

The negative sequence detection algorithm is recommended for IEDs used in isolated or high-
impedance earthed networks. It is based on the negative-sequence quantities.

The zero sequence detection is recommended for IEDs used in directly or low impedance
earthed networks. It is based on the zero sequence measuring quantities.

The selection of different operation modes is possible by a setting parameter in order to take
into account the particular earthing of the network.

A criterion based on delta current and delta voltage measurements can be added to the fuse
failure supervision function in order to detect a three phase fuse failure, which in practice is
more associated with voltage transformer switching during station operations.

14.2.3 Function block M13678-3 v9

FUFSPVC
I3P* BLKZ
U3P* BLKU
BLOCK 3PH
CBCLOSED DLD1PH
MCBOP DLD3PH
DISCPOS STDI
BLKTRIP STDIL1
STDIL2
STDIL3
STDU
STDUL1
STDUL2
STDUL3

IEC14000065-1-en.vsd
IEC14000065 V1 EN-US

Figure 378: FUFSPVC function block

652 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 14
Secondary system supervision

14.2.4 Signals
PID-3492-INPUTSIGNALS v9

Table 432: FUFSPVC Input signals


Name Type Default Description
I3P GROUP - Current connection
SIGNAL
U3P GROUP - Voltage connection
SIGNAL
BLOCK BOOLEAN 0 Block of function
CBCLOSED BOOLEAN 0 Active when circuit breaker is closed
MCBOP BOOLEAN 0 Active when external MCB opens protected voltage circuit
DISCPOS BOOLEAN 0 Active when line disconnector is open
BLKTRIP BOOLEAN 0 Blocks operation of function when active

PID-3492-OUTPUTSIGNALS v9

Table 433: FUFSPVC Output signals


Name Type Description
BLKZ BOOLEAN Start of current and voltage controlled function
BLKU BOOLEAN General start of function
3PH BOOLEAN Three-phase start of function
DLD1PH BOOLEAN Dead line condition in at least one phase
DLD3PH BOOLEAN Dead line condition in all three phases
STDI BOOLEAN Common start signal of sudden change in current
STDIL1 BOOLEAN Start signal of sudden change in current, phase L1
STDIL2 BOOLEAN Start signal of sudden change in current, phase L2
STDIL3 BOOLEAN Start signal of sudden change in current, phase L3
STDU BOOLEAN Common start signal of sudden change in voltage
STDUL1 BOOLEAN Start signal of sudden change in voltage, phase L1
STDUL2 BOOLEAN Start signal of sudden change in voltage, phase L2
STDUL3 BOOLEAN Start signal of sudden change in voltage, phase L3

Line distance protection REL670 653


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 506 370-UEN J
Secondary system supervision

14.2.5 Settings
PID-3492-SETTINGS v9

Table 434: FUFSPVC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
OpMode Off - - UZsIZs Operating mode selection
UNsINs
UZsIZs
UZsIZs OR
UNsINs
UZsIZs AND
UNsINs
OptimZsNs
3U0> 1 - 100 %UB 1 30 Operate level of residual overvoltage
element in % of UBase
3I0< 1 - 100 %IB 1 10 Operate level of residual undercurrent
element in % of IBase
3U2> 1 - 100 %UB 1 30 Operate level of neg seq overvoltage
element in % of UBase
3I2< 1 - 100 %IB 1 10 Operate level of neg seq undercurrent
element in % of IBase
OpDUDI Off - - Off Operation of change based function
On Off/On
DU> 1 - 100 %UB 1 60 Operate level of change in phase
voltage in % of UBase
DI< 1 - 100 %IB 1 15 Operate level of change in phase
current in % of IBase
UPh> 1 - 100 %UB 1 70 Operate level of phase voltage in % of
UBase
IPh> 1 - 100 %IB 1 10 Operate level of phase current in % of
IBase
SealIn Off - - On Seal in functionality Off/On
On
USealln< 1 - 100 %UB 1 70 Operate level of seal-in phase voltage
in % of UBase
IDLD< 1 - 100 %IB 1 5 Operate level for open phase current
detection in % of IBase
UDLD< 1 - 100 %UB 1 60 Operate level for open phase voltage
detection in % of UBase

Table 435: FUFSPVC Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

654 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 14
Secondary system supervision

14.2.6 Monitored data


PID-3492-MONITOREDDATA v8

Table 436: FUFSPVC Monitored data


Name Type Values (Range) Unit Description
3I0 REAL - A Magnitude of zero sequence current
3I2 REAL - A Magnitude of negative sequence
current
3U0 REAL - kV Magnitude of zero sequence voltage
3U2 REAL - kV Magnitude of negative sequence
voltage

14.2.7 Operation principle

14.2.7.1 Zero and negative sequence detection M13677-3 v5

The zero and negative sequence function continuously measures the currents and voltages in
all three phases and calculates, see figure 379:

• the zero-sequence voltage 3U0


• the zero-sequence current 3I0
• the negative sequence current 3I2
• the negative sequence voltage 3U2

The measured signals are compared with their respective set values 3U0> and 3I0<, 3U2> and
3I2<.

The function enable the internal signal FuseFailDetZeroSeq if the measured zero-sequence
voltage is higher than the set value 3U0> and the measured zero-sequence current is below the
set value 3I0<.

The function enable the internal signal FuseFailDetNegSeq if the measured negative sequence
voltage is higher than the set value 3U2> and the measured negative sequence current is below
the set value 3I2<.

A drop out delay of 100 ms for the measured zero-sequence and negative sequence current will
prevent a false fuse failure detection at un-equal breaker opening at the two line ends.

Line distance protection REL670 655


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 506 370-UEN J
Secondary system supervision

Sequence Detection
3I0< CurrZeroSeq
IL1
Zero 3I0
sequence
filter 100 ms CurrNegSeq
a
IL2 a>b t
b
Negative 3I2
sequence
IL3 filter FuseFailDetZeroSeq
AND
100 ms
a
a>b t
3I2< b
FuseFailDetNegSeq
AND
3U0>
VoltZeroSeq
UL1
Zero
sequence a 3U0
a>b
b
filter
UL2 VoltNegSeq

Negative
sequence a 3U2
a>b
UL3 filter b

3U2>

IEC10000036-2-en.vsd
IEC10000036 V2 EN-US

Figure 379: Simplified logic diagram for sequence detection part


The calculated values 3U0, 3I0, 3I2 and 3U2 are available as service values on local HMI and
monitoring tool in PCM600.

Input and output signals M13677-19 v6


The output signals 3PH, BLKU and BLKZ as well as the signals DLD1PH and DLD3PH from dead
line detections are blocked if any of the following conditions occur:

• The input BLOCK is activated


• The input BLKTRIP is activated and the internal signal FuseFailStarted is not present
• The operation mode selector OpMode is set to Off
• The IED is in TEST status (TEST-ACTIVE is high) and the function has been blocked from
the HMI (BlockFUSE=Yes)

The input BLOCK signal is a general purpose blocking signal of the fuse failure supervision
function. It can be connected to a binary input of the IED in order to receive a block command
from external devices or can be software connected to other internal functions of the IED itself
in order to receive a block command from internal functions. Through OR gate it can be
connected to both binary inputs and internal function outputs.

The input BLKTRIP is intended to be connected to the trip output from any of the protection
functions included in the IED. When activated for more than 20 ms, the operation of the fuse
failure is blocked; a fixed drop-out timer prolongs the block for 100 ms. The aim is to increase
the security against unwanted operations during the opening of the breaker, which might
cause unbalance conditions for which the fuse failure might operate.

The output signal BLKZ will also be blocked if the internal dead line detection is activated. The
dead line detection signal has a 200 ms drop-out time delay.

The input signal MCBOP is supposed to be connected via a terminal binary input to the N.C.
auxiliary contact of the miniature circuit breaker protecting the VT secondary circuit. The
MCBOP signal sets the output signals BLKU and BLKZ in order to block all the voltage related
functions when the MCB is open independent of the setting of OpMode selector. The
additional drop-out timer of 150 ms prolongs the presence of MCBOP signal to prevent the
unwanted operation of voltage dependent function due to non simultaneous closing of the
main contacts of the miniature circuit breaker.

656 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 14
Secondary system supervision

The input signal DISCPOS is supposed to be connected via a terminal binary input to the N.C.
auxiliary contact of the line disconnector. The DISCPOS signal sets the output signal BLKU in
order to block the voltage related functions when the line disconnector is open. The
impedance protection function is not affected by the position of the line disconnector since
there will be no line currents that can cause malfunction of the distance protection. If
DISCPOS=0 it signifies that the line is connected to the system and when the DISCPOS=1 it
signifies that the line is disconnected from the system and the block signal BLKU is generated.

The output BLKU can be used for blocking the voltage related measuring functions
(undervoltage protection, energizing check and so on) except for the impedance protection.

The function output BLKZ shall be used for blocking the impedance protection function.

14.2.7.2 Delta current and delta voltage detection M13685-3 v7

A simplified diagram for the functionality is found in figure 380. The calculation of the changes
of currents and voltages is based on a sample analysis algorithm. The calculated delta
quantities are compared with their respective set values DI< and DU>. The algorithm detects a
fuse failure if a sufficient change in voltage without a sufficient change in current is detected
in each phase separately. The following quantities are calculated in all three phases:

• The change in voltage DU


• The change in current DI

The internal FuseFailDetDUDI signal is activated if the following conditions are fulfilled:

• The magnitude of the phase-ground voltage has been above UPh> for more than 1.5 cycles
(i.e. 30 ms in a 50 Hz system)
• The magnitudes of DU in three phases are higher than the corresponding setting DU>
• The magnitudes of DI in three phases are below the setting DI<

In addition to the above conditions, at least one of the following conditions shall be fulfilled in
order to activate the internal FuseFailDetDUDI signal:

• The magnitude of the phase currents in three phases are higher than the setting IPh>
• The circuit breaker is closed (CBCLOSED = True)

The first criterion means that detection of failure in three phases together with high current
for the three phases will set the output. The measured phase current is used to reduce the risk
of false fuse failure detection. If the current on the protected line is low, a voltage drop in the
system (not caused by fuse failure) may be followed by current change lower than the setting
DI<, and therefore a false fuse failure might occur.

The second criterion requires that the delta condition shall be fulfilled at the same time as
circuit breaker is closed. If CBCLOSED input is connected to FALSE , then only the first criterion
can enable the delta function.If the DUDI detections of three phases set the internal signal
FuseFailDetDUDI at the level high, then the signal FuseFailDetDUDI will remain high as long as
the voltages of three phases are lower then the setting Uph>.

In addition to fuse failure detection, two internal signals DeltaU and DeltaI are also generated
by the delta current and delta voltage DUDI detection algorithm. The internal signals DelatU
and DeltaI are activated when a sudden change of voltage, or respectively current, is detected.
The detection of the sudden change is based on a sample analysis algorithm. In particular
DelatU is activated if at least three consecutive voltage samples are higher then the setting
DU>. In a similar way DelatI is activated if at least three consecutive current samples are higher
then the setting DI<. When DeltaU or DeltaI are active, the output signals STDUL1, STDUL2,
STDUL3 and respectively STDIL1, STDIL2, STDIL3, based on a sudden change of voltage or
current detection, are activated with a 20 ms time off delay. The common start output signals

Line distance protection REL670 657


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 506 370-UEN J
Secondary system supervision

STDU or STDI are activated with a 60 ms time off delay, if any sudden change of voltage or
current is detected.

The delta function (except the sudden change of voltage and current detection)
is deactivated by setting the parameter OpDUDI to Off.

DUDI Detection
DUDI detection Phase 1
DeltaIL1
IL1
IL2
IL3 DI detection based on sample analysis OR

DI<

UL1

DU detection based on sample analysis


AND
DU>
1.5 cycle 20 ms DeltaUL1
a
a>b t t
UPh> b

IL1 DeltaIL2
IL2 DUDI detection Phase 2
DeltaUL2
IL3
UL2 Same logic as for phase 1

IL1 DeltaIL3
DUDI detection Phase 3
IL2
DeltaUL3
IL3
UL3 Same logic as for phase 1

UL1
a
a<b
b

IL1
a
a>b
IPh> b AND

OR AND
CBCLOSED AND OR

UL2
a
a<b
b

IL2
a
a>b
b AND

OR AND
AND OR

UL3
a
a<b
b

IL3
a
a>b
b AND

OR AND
AND OR FuseFailDetDUDI
AND

IEC12000166-3-en.vsd

IEC12000166 V3 EN-US

Figure 380: Simplified logic diagram for the DU/DI detection part

658 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 14
Secondary system supervision

intBlock
STDI
AND

20 ms
DeltaIL1 STDIL1
t AND
OR
20 ms
DeltaIL2
t STDIL2
AND
20 ms
DeltaIL3
t
STDIL3
AND

STDU
AND

20 ms
DeltaUL1 STDUL1
t AND
OR
20 ms
DeltaUL2
t STDUL2
AND
20 ms
DeltaUL3
t
STDUL3
AND

IEC12000165-1-en.vsd
IEC12000165 V1 EN-US

Figure 381: Internal signals DeltaU or DeltaI and the corresponding output signals

14.2.7.3 Dead line detection M13679-44 v4

A simplified diagram for the functionality is found in figure 382. A dead phase condition is
indicated if both the voltage and the current in one phase is below their respective setting
values UDLD< and IDLD<. If at least one phase is considered to be dead the output DLD1PH
and the internal signal DeadLineDet1Ph is activated. If all three phases are considered to be
dead the output DLD3PH is activated

Line distance protection REL670 659


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 506 370-UEN J
Secondary system supervision

Dead Line Detection


IL1
a
a<b AllCurrLow
b
AND
IL2
a
a<b
b

IL3
a
a<b
b

IDLD<
DeadLineDet1Ph
UL1
a AND
a<b
b OR DLD1PH
AND
UL2
a AND
a<b
b
AND DLD3PH
UL3 AND
a AND
a<b
b

UDLD<

intBlock

IEC10000035-1-en.vsd
IEC10000035 V2 EN-US

Figure 382: Simplified logic diagram for Dead Line detection part

14.2.7.4 Main logic GUID-D474A49E-D3A8-438C-B7E4-E527FEC2F335 v6

A simplified diagram for the functionality is found in figure 383. The fuse failure supervision
function (FUFSPVC) can be switched on or off by the setting parameter Operation to On or
Off.

For increased flexibility and adaptation to system requirements an operation mode selector,
OpMode, has been introduced to make it possible to select different operating modes for the
negative and zero sequence based algorithms. The different operation modes are:

• Off. The negative and zero sequence function is switched off.


• UNsINs. Negative sequence is selected.
• UZsIZs. Zero sequence is selected.
• UZsIZs OR UNsINs. Both negative and zero sequence are activated and work in parallel
(OR-condition for operation).
• UZsIZs AND UNsINs. Both negative and zero sequence are activated and work in series
(AND-condition for operation).
• OptimZsNs. Optimum of negative and zero sequence current (the function that has the
highest magnitude of measured negative and zero sequence current will be activated).

The delta function can be activated by setting the parameter OpDUDI to On. When selected it
operates in parallel with the sequence based algorithms.

As soon as any fuse failure situation is detected, signals FuseFailDetZeroSeq,


FuseFailDetNegSeq or FuseFailDetDUDI, and the specific functionality is released, the function
will activate the output signal BLKU. The output signal BLKZ will be activated as well if the
internal dead phase detection, DeadLineDet1Ph, is not activated at the same time. The output
BLKU can be used for blocking voltage related measuring functions (under voltage protection,
energizing check, and so on). The output BLKZ shall be used to block the impedance
protection functions.

If the fuse failure situation is present for more than 5 seconds and the setting parameter
SealIn is set to On it will be sealed in as long as at least one phase voltages is below the set

660 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 14
Secondary system supervision

value USealIn<. This will keep the BLKU and BLKZ signals activated as long as any phase
voltage is below the set value USealIn<. If all three phase voltages drop below the set value
USealIn< and the setting parameter SealIn is set to On the output signal 3PH will also be
activated. The signals 3PH, BLKU and BLKZ will now be active as long as any phase voltage is
below the set value USealIn<.

If SealIn is set to On the fuse failure condition lasting more then 5 seconds is stored in the non-
volatile memory in the IED. At start-up of the IED (due to auxiliary power interruption or re-
start due to configuration change) it uses the stored value in its non-volatile memory and re-
establishes the conditions that were present before the shut down. All phase voltages must be
restored above USealIn< before fuse failure is de-activated and resets the signals BLKU, BLKZ
and 3PH.

The output signal BLKU will also be active if all phase voltages have been above the setting
USealIn< for more than 60 seconds, the zero or negative sequence voltage has been above the
set value 3U0> and 3U2> for more than 5 seconds, all phase currents are below the setting
IDLD< (criteria for open phase detection) and the circuit breaker is closed (input CBCLOSED is
activated).

If a MCB is used then the input signal MCBOP is to be connected via a binary input to the N.C.
auxiliary contact of the miniature circuit breaker protecting the VT secondary circuit. The
MCBOP signal sets the output signals BLKU and BLKZ in order to block all the voltage related
functions when the MCB is open independent of the setting of OpMode or OpDUDI. An
additional drop-out timer of 150 ms prolongs the presence of MCBOP signal to prevent the
unwanted operation of voltage dependent function due to non simultaneous closing of the
main contacts of the miniature circuit breaker.

The input signal DISCPOS is supposed to be connected via a terminal binary input to the N.C.
auxiliary contact of the line disconnector. The DISCPOS signal sets the output signal BLKU in
order to block the voltage related functions when the line disconnector is open. The
impedance protection function does not have to be affected since there will be no line currents
that can cause malfunction of the distance protection.

Line distance protection REL670 661


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 506 370-UEN J
Secondary system supervision

Fuse failure detection


Main logic
TEST

TEST ACTIVE
AND
BlocFuse = Yes

BLOCK intBlock
OR
BLKTRIP 20 ms 100 ms
AND t t
FusefailStarted

All UL < USealIn<


OR
AND
3PH
AND
SealIn = On AND

AND
Any UL < UsealIn<

FuseFailDetDUDI
AND 5s
OpDUDI = On
OR t
FuseFailDetZeroSeq
AND

AND

FuseFailDetNegSeq
AND

UNsINs OR
UZsIZs OR
UZsIZs OR UNsINs
OpMode
UZsIZs AND UNsINs
OptimZsNs
OR
CurrZeroSeq
a AND
CurrNegSeq a>b
b

AND

DeadLineDet1Ph 200 ms
AND BLKZ
t OR AND
150 ms
MCBOP t

AND BLKU
60 s
t OR OR
All UL > UsealIn<
AND

VoltZeroSeq 5s
VoltNegSeq OR t

AllCurrLow
CBCLOSED

DISCPOS IEC10000033-2-en.vsd

IEC10000033 V2 EN-US

Figure 383: Simplified logic diagram for fuse failure supervision function, Main logic

662 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 14
Secondary system supervision

14.2.8 Technical data


M16069-1 v12

Table 437: FUFSPVCtechnical data


Function Range or value Accuracy
Operate voltage, zero sequence (1-100)% of UBase ±0.5% of Ur

Operate current, zero sequence (1–100)% of IBase ±0.5% of Ir

Operate voltage, negative sequence (1-100)% of UBase ±0.5% of Ur

Operate current, negative sequence (1–100)% of IBase ±0.5% of Ir

Operate voltage change level (1-100)% of UBase ±10.0% of Ur

Operate current change level (1–100)% of IBase ±10.0% of Ir

Operate phase voltage (1-100)% of UBase ±0.5% of Ur

Operate phase current (1–100)% of IBase ±0.5% of Ir

Operate phase dead line voltage (1-100)% of UBase ±0.5% of Ur

Operate phase dead line current (1–100)% of IBase ±0.5% of Ir

Operate time, start, 1 ph, at 1 x Ur to 0 Min. = 10 ms -


Max. = 25 ms
Reset time, start, 1 ph, at 0 to 1 x Ur Min. = 15 ms -
Max. = 30 ms

14.3 Fuse failure supervision VDSPVC GUID-9C5BA1A7-DF2F-49D4-A13A-C6B483DDFCDC v2

14.3.1 Identification GUID-109434B0-23E5-4053-9E6E-418530A07F9C v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Fuse failure supervision VDSPVC VTS 60

14.3.2 Functionality GUID-6AF2219A-264F-4971-8D03-3B8A9D0CB284 v5

Different protection functions within the protection IED operates on the basis of measured
voltage at the relay point. Some example of protection functions are:

• Distance protection function.


• Undervoltage function.
• Energisation function and voltage check for the weak infeed logic.

These functions can operate unintentionally, if a fault occurs in the secondary circuits between
voltage instrument transformers and the IED. These unintentional operations can be
prevented by fuse failure supervision (VDSPVC).

VDSPVC is designed to detect fuse failures or faults in voltage measurement circuit, based on
phase wise comparison of voltages of main and pilot fused circuits. VDSPVC blocking output
can be configured to block functions that need to be blocked in case of faults in the voltage
circuit.

Line distance protection REL670 663


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 506 370-UEN J
Secondary system supervision

14.3.3 Function block GUID-0C4A6C94-E0D7-4E36-AB49-D74A5E330D36 v2

VDSPVC
U3P1* MAINFUF
U3P2* PILOTFUF
BLOCK U1L1FAIL
U1L2FAIL
U1L3FAIL
U2L1FAIL
U2L2FAIL
U2L3FAIL

IEC14000048-1-en.vsd
IEC12000142 V2 EN-US

Figure 384: VDSPVC function block

14.3.4 Signals
PID-3485-INPUTSIGNALS v8

Table 438: VDSPVC Input signals


Name Type Default Description
U3P1 GROUP - Main fuse voltage
SIGNAL
U3P2 GROUP - Pilot fuse voltage
SIGNAL
BLOCK BOOLEAN 0 Block of function

PID-3485-OUTPUTSIGNALS v8

Table 439: VDSPVC Output signals


Name Type Description
MAINFUF BOOLEAN Block of main fuse failure
PILOTFUF BOOLEAN Alarm of pilot fuse failure
U1L1FAIL BOOLEAN Fuse failure of Main fuse group phase L1
U1L2FAIL BOOLEAN Fuse failure of Main fuse group phase L2
U1L3FAIL BOOLEAN Fuse failure of Main fuse group phase L3
U2L1FAIL BOOLEAN Fuse failure of Pilot fuse group phase L1
U2L2FAIL BOOLEAN Fuse failure of Pilot fuse group phase L2
U2L3FAIL BOOLEAN Fuse failure of Pilot fuse group phase L3

664 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 14
Secondary system supervision

14.3.5 Settings
PID-3485-SETTINGS v8

Table 440: VDSPVC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Mode Off / On
On
Ud>MainBlock 10.0 - 80.0 %UB 0.1 20.0 Blocking picked up voltage level in %
of UBase when main fuse fails
Ud>PilotAlarm 10.0 - 80.0 %UB 0.1 30.0 Alarm picked up voltage level in % of
UBase when pilot fuse fails
SealIn Off - - On Seal in functionality Off/On
On
USealIn 0.0 - 100.0 %UB 0.1 70.0 Operate level of seal-in voltage in % of
UBase

Table 441: VDSPVC Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

Table 442: VDSPVC Non group settings (advanced)


Name Values (Range) Unit Step Default Description
ConTypeMain Ph-N - - Ph-N Selection of connection type for main
Ph-Ph fuse group
ConTypePilot Ph-N - - Ph-N Selection of connection type for pilot
Ph-Ph fuse group

14.3.6 Monitored data


PID-3485-MONITOREDDATA v7

Table 443: VDSPVC Monitored data


Name Type Values (Range) Unit Description
UL1DIF_A REAL - kV Differential voltage phase L1 for alarm
functionality
UL2DIF_A REAL - kV Differential voltage phase L2 for alarm
functionality
UL3DIF_A REAL - kV Differential voltage phase L3 for alarm
functionality
UL1DIF_B REAL - kV Differential voltage phase L1 for block
functionality
UL2DIF_B REAL - kV Differential voltage phase L2 for block
functionality
UL3DIF_B REAL - kV Differential voltage phase L3 for block
functionality

Line distance protection REL670 665


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 506 370-UEN J
Secondary system supervision

14.3.7 Operation principle GUID-06BC0CC0-8A4F-4D84-A0B1-506E433F72F3 v4

VDSPVC requires six voltage inputs, which are the three phase voltages on main and pilot fuse
groups. The initial voltage difference between the two groups is theoretical zero in the healthy
condition. Any subsequent voltage difference will be due to a fuse failure.

If the main fuse voltage becomes smaller than the pilot fuse voltage (vMainL1 < vPilotL1 or
vMainL2 < vPilotL2 or vMainL3 < vPilotL3) and the voltage difference exceeds the operation
level (Ud>MainBlock), a blocking signal will be initiated to indicate the main fuse failure and
block the voltage-dependent functions. In addition, the function also indicates the phase in
which the voltage reduction has occurred.

If the pilot fuse voltage becomes smaller than the main fuse voltage (vPilotL1 < vMainL1 or
vPilotL2 < vMainL2 or vPilotL3 < vMainL3) and the voltage difference exceeds the operation
level (Ud>PilotAlarm), an alarm signal will be initiated to indicate the pilot fuse failure and also
the faulty phase where the voltage reduction occurred.

When SealIn is set to On and the fuse failure has last for more than 5 seconds, the blocked
protection functions will remain blocked until normal voltage conditions are restored above
the USealIn setting. Fuse failure outputs are deactivated when normal voltage conditions are
restored.

5s
a
a<b AND OR t
USealIn b

SealIn=0

vPilotL1
+
vMainL1 -
å MAX a U1L1FAIL
OR
a>b AND
Ud>MainBlock b MAINFAIL
OR
0

MIN ABS a
a>b AND U2L1FAIL
Ud> PilotAlarm b
BLOCK
OR PILOTFAIL

vPilotL2 U1L2FAIL
vMainL2 Phase L2, same as Phase L1 U2L2FAIL

vPilotL3 U1L3FAIL
vMainL3 Phase L3, same as Phase L1 U2L3FAIL

IEC12000144-1-en.vsd
IEC12000144 V1 EN-US

Figure 385: Simplified logic diagram VDSPVC

666 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 14
Secondary system supervision

14.3.8 Technical data


GUID-E2EA8017-BB4B-48B0-BEDA-E71FEE353774 v5

Table 444: VDSPVC technical data


Function Range or value Accuracy
Operate value, block of main fuse failure (10.0-80.0)% of UBase ±0.5% of Ur
Reset ratio <110%
Operate time, block of main fuse failure at 1 x Ur Min. = 5 ms –
to 0
Max. = 15 ms
Reset time, block of main fuse failure at 0 to 1 x Min. = 15 ms –
Ur
Max. = 30 ms
Operate value, alarm for pilot fuse failure (10.0-80.0)% of UBase ±0.5% of Ur
Reset ratio <110% –
Operate time, alarm for pilot fuse failure at 1 x Ur Min. = 5 ms –
to 0
Max. = 15 ms
Reset time, alarm for pilot fuse failure at 0 to 1 x Min. = 15 ms –
Ur
Max. = 30 ms

14.4 Voltage based delta supervision DELVSPVC GUID-579ED249-B8C9-4755-9E80-28E2BA8E5377 v2

14.4.1 Identification
GUID-C7108931-DECA-4397-BCAF-8BFF3B57B4EF v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Voltage based delta supervision DELVSPVC – 7V_78V

14.4.2 Functionality GUID-6188C4C1-E1D5-421A-B496-96676287EBB2 v2

Delta supervision function is used to quickly detect (sudden) changes in the network. This can,
for example, be used to detect faults in the power system networks and islanding in grid
networks. Voltage based delta supervision (DELVSPVC) is needed at the grid interconnection
point.

Line distance protection REL670 667


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 506 370-UEN J
Secondary system supervision

14.4.3 Function block GUID-06FEC7EF-B37E-4D42-99DA-868453E6FDBF v2

DELVSPVC
U3P* START
BLOCK STARTL1
STARTL2
STARTL3
STRISE
STRISEL1
STRISEL2
STRISEL3
STLOW
STLOWL1
STLOWL2
STLOWL3
DELMAGL1
DELMAGL2
DELMAGL3

IEC18000007‐1‐en.vsdx
IEC18000007 V1 EN-US

Figure 386: DELVSPVC function block

14.4.4 Signals
PID-7097-INPUTSIGNALS v1

Table 445: DELVSPVC Input signals


Name Type Default Description
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function

PID-7097-OUTPUTSIGNALS v1

Table 446: DELVSPVC Output signals


Name Type Description
START BOOLEAN General start of function
STARTL1 BOOLEAN Start of L1
STARTL2 BOOLEAN Start of L2
STARTL3 BOOLEAN Start of L3
STRISE BOOLEAN Common rise signal when input has increased
STRISEL1 BOOLEAN L1/L12 delta value increased
STRISEL2 BOOLEAN L2/L23 delta value increased
STRISEL3 BOOLEAN L3/L31 delta value increased
STLOW BOOLEAN Common low signal when input has decreased
STLOWL1 BOOLEAN L1/L12 delta value decreased
STLOWL2 BOOLEAN L2/L23 delta value decreased
STLOWL3 BOOLEAN L3/L31 delta value decreased
DELMAGL1 REAL Delta magnitude of L1 / L12
DELMAGL2 REAL Delta magnitude of L2 / L23
DELMAGL3 REAL Delta magnitude of L3 / L31

668 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 14
Secondary system supervision

14.4.5 Settings
PID-7097-SETTINGS v1

Table 447: DELVSPVC Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups
OpMode Instantaneous 1 - - DFT mag Operation mode
cycle
Instantaneous 2
cycle
RMS
DFT mag
DFT Angle (Vector
shift)
MeasMode Phase to phase - - Phase to ground Measurement type: Phase to ground /
Phase to ground Phase to phase

Table 448: DELVSPVC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
UMin 1.0 - 50.0 %UB 0.1 5.0 Minimum start value of voltage for
release of delta function
DeltaT 1 - 10 cycle 1 2 Number of old power cycles for delta
calculation
DelU> 2.0 - 500.0 %UB 0.1 40.0 Magnitude start level for magnitude,
RMS and sample based delta
comparison
DelUAng> 2.0 - 40.0 Deg 1.0 8.0 Start level for angle based delta
detection
tHold 0.10 - 60.00 s 0.01 0.10 Hold time for start signal

14.4.6 Monitored data


PID-7097-MONITOREDDATA v1

Table 449: DELVSPVC Monitored data


Name Type Values (Range) Unit Description
UL1 REAL - kV RMS magnitude of L1 /L12
UL2 REAL - kV RMS magnitude of L2 /L23
UL3 REAL - kV RMS magnitude of L3 /L31

14.4.7 Operation principle GUID-7F65AD13-1F0E-402A-8B9C-3B1D6ED0D2BB v2

The delta supervision function is a phase segregated function. Following are the features of
DELVSPVC:

• Check of the minimum signal level


• Five different modes of operation
• Frequency stabilization for angle shift

Line distance protection REL670 669


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 506 370-UEN J
Secondary system supervision

The general design of DELVSPVC is shown in Figure 387:

opMode = Instantaneous 1 cycle/2 cycle


Sample delta  STARTSAMPLE
U3P calculation
opMode = DFTAngle
Frequency 
estimation and  Frequency stabilization STARTANGLE
angle shift based on 2 cycle old 
calculation frequency
1 START
AND

Signal pre‐processing
 
  fundamental DFT
opMode= RMS/DFTMag
  harmonic extraction
 
Magnitude based  STARTMAG
delta calculation DELMAGLx

MinValueCheck AND

BLOCK   
IEC18000008-1-en.vsdx

IEC18000008 V1 EN-US

Figure 387: Simplified logic diagram for voltage based delta supervision DELVSPVC

14.4.7.1 Minimum signal level check GUID-FE5377C8-E4CF-43D3-B1EC-C886E76377A6 v2

The setting Umin is used to check and release the signals for the delta supervision. The delta
detection is blocked for 2 cycles by Umin comparator for angle shift mode.

14.4.7.2 Mode of operation GUID-B4EDA716-DB28-422A-88E3-F41D5D7BB6A4 v2

DELVSPVC can be selected for phase-to-ground or phase-to-phase measurements using the


MeasMode setting. If the setting is selected as phase-to-phase, then outputs with L1 will
represent L12 phase-to-phase quantities. Following are the modes of operations for the
OpMode setting:
• Instantaneous 1 cycle
• Instantaneous 2 cycle
• True RMS
• DFT mag
• Vector Shift

These modes of operation are explained in following sections.

14.4.7.3 Instantaneous 1 cycle / 2 cycle GUID-BAF266E2-A0A0-4848-9DFB-776C197B4A7F v1

This method uses the instantaneous sample for delta detection. The logic of this scheme is
given in Figure 388. The instantaneous difference between the present sample and the one
cycle (or two cycle) old sample is used for the delta detection. The change (delta) is verified for
three continuous samples in order to release the start signal. Once the start signal is set, any
subsequent change in sample values within 60 ms will not be detected. The DELU> setting will
be set in % of UB. The sample based delta is selectable for one cycle/two cycle operation,
based on the OpMode setting.

670 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 14
Secondary system supervision

Old value buffer 
Voltage sample input
  1  cycle / 
   2 cycle

‐ Abs
60ms
>
StartSampleDelta
AND t

DelU>
q‐1

q‐1

IEC17000199-2-en.vsdx

IEC17000199 V2 EN-US

Figure 388: Simplified logic diagram for sample based delta detection

14.4.7.4 RMS/DFT based supervision GUID-B299BE6C-AD89-4DFE-AFFC-E3DD252A260A v2

This mode uses the RMS or DFT magnitude value of the voltage signal for the delta detection.
The logic of this scheme is given in Figure 389. Difference between the present value and the
old value is used for the delta detection. The old value is chosen based on the setting DeltaT,
which is defined as the number of old power cycles.

The function has an execution cycle time of 3 ms. For a DeltaT setting of 3, the
old value is 60 ms. Therefore, accuracy of the old cycle data depends upon the
execution cycle.

The output of the comarator is ascertained for half a cycle before releasing a STARTMAG
signal. In DELVSPVC, the DelU> setting is set in % of UB. RMS based delta will have poor
accuracy if the signal contains harmonics and other frequency components. DFT Mag based
delta will operate better in these conditions.

Additional information for the STARTRISE and STARTLOW outputs of the delta are also
available in this mode. The STARTRISE and STARTLOW outputs will be sealed by the start
signal. These outputs explains the reason for the STARTMAG signal.

Seal‐in  STARTLOW
logic

0.1
>

RMS input / Seal‐in  STARTRISE


> logic
DFT mag Delay defined by  ‐0.1
DeltaT
0. 3 cycle
‐ Abs
> t
DelU>

IEC17000200-2-en.vdsx

IEC17000200 V2 EN-US

Figure 389: Simplified logic diagram for RMS/DFT based delta detection

14.4.7.5 Angle based supervision or vector shift supervision GUID-26960EA3-233A-4B76-8C11-245334012C76 v2

The Vector shift selection in the OpMode setting is used to set the DELVSPVC function to
operate. A change in magnitude will not have any impact on this supervision. Angle shift is
measured based on the half cycle time (HCTime) as shown in Figure 390. The figure shows a
waveform shift of 40 degree in the voltage waveform. There are two half cycle time which is
affected by this angle shift namely, HCTime(k-1) and HCTime(k). A cumulative difference of
two HCTime difference is calculated to get an accurate estimate of the angle shift. This angle
shift is compared with DelUang> setting to release the STARTANGLE signal.

Line distance protection REL670 671


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 506 370-UEN J
Secondary system supervision

The logic for this mode is given in Figure 391. The DelUAng> setting will be set in absolute
degrees.

Voltage

Angle shift= [{Hctime(k) ‐ Hctime(k‐2)} + {Hctime(k‐1) ‐ Hctime(k‐3)}]

Angle shift

HC time (k‐3) HC time (k‐2) HC time (k‐1) HC time (k)


Time

IEC17000210-1-en.vsdx

IEC17000210 V1 EN-US

Figure 390: Angle shift


Angle measurement is affected by system parameters such as frequency, load or generation.
Hence, a stabilization of the angle is also present in this mode of operation. The measured
frequency is compared with the 2 cycles old value. If the change is greater than 0.2 Hz, the
STARTANGLE signal is blocked. The output will release Angle shift mode when the measured
frequency difference is continuously less than 0.2 Hz for 2 cycles. The general logic is
presented in Figure 391. In this mode STLOW, STRISE, STLOWLx and STRISELx outputs will not
be used and set as FALSE.

ULx Angle shift 
calculation
0.5 cycle
Abs Delta Angle
> t

DelUang> STARTANGLE
Frequency difference of last 2 cycles AND
> AND
0.2 Hz

IEC18000902-1-en.vsdx

IEC18000902 V1 EN-US

Figure 391: Simplified logic diagram for angle based delta detection

672 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 14
Secondary system supervision

14.4.8 Technical data


GUID-DAECF9F5-1D0B-43FC-AD29-8F96E05DD0DA v3

Table 450: DELVSPVC technical data


Function Range or value Accuracy
Minimum Voltage (5.0 - 50.0)% of UBase ±0.5% of Ur at U ≤ Ur
DelU> (2.0 - 500.0)% of UBase Instantaneous 1 cycle & Instantaneous
2 cycle mode:±20% of Ur at U ≤ Ur
±20% of U at U > UrRMS & DFT Mag
mode:±10% of Ur at U ≤ Ur±10% of U
at U > Ur
DelUAng> (2.0 - 40.0) degrees ±2.0 degrees
Operate time for Instantaneous 1 cycle & Instantaneous
changeat Ur to (Ur + 2 x 2 cycle mode - <20msRMS & DFT Mag
DelU>)at Ur to (Ur + 5 x mode - <30ms
DelU>)
Operate time for jump Vector shift mode - <60ms
from Zero degrees to
'AngStVal' + 2 degrees

14.5 Current based delta supervision DELISPVC GUID-4F012876-FA0A-4A97-9E23-387974304CED v2

14.5.1 Identification
GUID-0B735A27-6A7D-40E1-B981-91B689608495 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Current based delta supervision DELISPVC – 7I < >

14.5.2 Functionality GUID-30A00AE0-8D3A-4CE8-9379-8D1A0A6078E3 v2

Delta supervision function is used to quickly detect (sudden) changes in the network. This can,
for example, be used to detect disturbances in the power system network. Current based delta
supervision (DELISPVC) provides selectivity between load change and the fault.

Present power system has many power electronic devices or FACTS devices, which injects a
large number of harmonics into the system. The function has additional features of 2nd
harmonic blocking and 3rd harmonic start level adaption. The 2nd harmonic blocking secures
the operation during the transformer charging, when high inrush currents are supplied into
the system.

Line distance protection REL670 673


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 506 370-UEN J
Secondary system supervision

14.5.3 Function block GUID-D1467592-DD2D-488F-94CA-66BD0FA57A8D v2

DELISPVC
I3P* START
BLOCK STARTL1
STARTL2
STARTL3
STRISE
STRISEL1
STRISEL2
STRISEL3
STLOW
STLOWL1
STLOWL2
STLOWL3
ADAPTVAL
HARM2BLK
DELMAGL1
DELMAGL2
DELMAGL3
IEC18000005-1-en.vsdx
IEC18000005 V1 EN-US

Figure 392: DELISPVC function block

14.5.4 Signals
PID-7098-INPUTSIGNALS v1

Table 451: DELISPVC Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
BLOCK BOOLEAN 0 Block of function

PID-7098-OUTPUTSIGNALS v1

Table 452: DELISPVC Output signals


Name Type Description
START BOOLEAN General start of function
STARTL1 BOOLEAN Start of L1
STARTL2 BOOLEAN Start of L2
STARTL3 BOOLEAN Start of L3
STRISE BOOLEAN Common rise signal when input has increased
STRISEL1 BOOLEAN L1/L12 delta value increased
STRISEL2 BOOLEAN L2/L23 delta value increased
STRISEL3 BOOLEAN L3/L31 delta value increased
STLOW BOOLEAN Common low signal when input has decreased
STLOWL1 BOOLEAN L1/L12 delta value decreased
STLOWL2 BOOLEAN L2/L23 delta value decreased
STLOWL3 BOOLEAN L3/L31 delta value decreased
ADAPTVAL BOOLEAN Delta start level changed by 3rd harmonic
HARM2BLK BOOLEAN 2nd harmonic blocking active
DELMAGL1 REAL Delta magnitude of L1 / L12
DELMAGL2 REAL Delta magnitude of L2 / L23
DELMAGL3 REAL Delta magnitude of L3 / L31

674 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 14
Secondary system supervision

14.5.5 Settings
PID-7098-SETTINGS v1

Table 453: DELISPVC Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups
OpMode Instantaneous 1 - - DFT mag Operation mode
cycle
Instantaneous 2
cycle
RMS
DFT mag
MeasMode Phase to phase - - Phase to ground Measurement type: Phase to ground /
Phase to ground Phase to phase

Table 454: DELISPVC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
IMin 1.0 - 50.0 %IB 0.1 10.0 Minimum current start value for
release of delta function
DeltaT 1 - 10 cycle 1 2 Number of old power cycles for delta
calculation
DelI> 2.0 - 500.0 %IB 0.1 40.0 Magnitude start level for magnitude,
RMS and sample based delta
comparison
tHold 0.10 - 60.00 s 0.01 0.10 Hold time for start signal
EnaHarm2Blk Off - - Off Enable 2nd harmonic blocking
On
HarmBlkLevel 5.0 - 100.0 % 0.1 15.0 Harmonic blocking level for 2nd
harmonic in % of fundamental
EnStValAdap Off - - Off Enable set level setting adaption
On based on 3rd harmonic
Harm3Level 5.0 - 100.0 % 0.1 15.0 3rd Harmonic level in % of
fundamental for enabling adaptive
start value
StValGrad -90.00 - 500.00 % 0.10 -10.00 Gradient for adapting magnitude set
level during 3rd harmonic in % of DelI>

14.5.6 Monitored data


PID-7098-MONITOREDDATA v1

Table 455: DELISPVC Monitored data


Name Type Values (Range) Unit Description
IL1 REAL - A RMS magnitude of L1 /L12
IL2 REAL - A RMS magnitude of L2 /L23
IL3 REAL - A RMS magnitude of L3 /L31

Line distance protection REL670 675


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 506 370-UEN J
Secondary system supervision

14.5.7 Operation principle GUID-27E7C6C8-83B1-4CA6-9B4E-38FDED3FD360 v2

The delta supervision function is a phase segregated function. Following are the features of
DELISPVC:

• Check of the minimum signal level


• Four different modes of operation
• 2nd harmonic blocking of delta function
• 3rd harmonic based adaption of starting value

The general design of DELISPVC is shown in Figure 393:

opMode = Instantaneous 1 cycle/2 cycle


I3P Sample delta  STARTSAMPLE
calculation
1 AND START

Signal pre‐processing
 
  fundamental DFT
opMode= RMS/DFTMag
  harmonic extraction
 
Magnitude based  STARTMAG
delta calculation DELMAGLx
DFTMagToComp
rd
3 harmonic based 
  ADAPTVAL
adaption nd HARM2BLK
2  harmonic 
blocking
AND
MinValueCheck

BLOCK   
IEC18000006-1-en.vsdx

IEC18000006 V1 EN-US

Figure 393: Simplified logic diagram for current based delta supervision DELISPVC

14.5.7.1 Minimum signal level check GUID-5E5503ED-1A61-4927-86F0-6ABDC7E2AA2B v2

The setting Imin is used to check and release the signals for the delta supervision. This setting
can be used to obtain selectivity between load current and fault current.

14.5.7.2 Mode of operation GUID-2B87BAB6-A0D4-4A3D-8116-88F1598C1AC6 v2

DELISPVC can be selected for phase-to-ground or phase-to-phase measurements using the


MeasMode setting. If the setting is selected as phase-to-phase, then outputs with L1 will
represent L12 phase-to-phase quantities and so on. Following are the modes of operations for
the OpMode setting:

• Instantaneous 1 cycle
• Instantaneous 2 cycle
• True RMS
• DFT mag

These modes of operation are explained in following sections.

14.5.7.3 Instantaneous 1 cycle / 2 cycle GUID-4FD743D6-DB93-4C76-819D-E81C562B762A v2

This method uses the buffer of instantaneous sample for delta detection. The logic of this
scheme is given in Figure 394. The instantaneous difference between the present sample and
the one cycle (or two cycle) old sample is used for the delta detection. The change (vectorial
delta) is verified for three continuous samples in order to release the start signal. This delta
calculation is affected by angle or magnitude or both changes in the signal in the last one
cycle/two cycle. It is also known as vectorial delta scheme. Once the start signal is set, any
subsequent change in sample values within 60 ms will not be detected. The DelI> setting will

676 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 14
Secondary system supervision

be set in % of IB. The sample based delta is selectable for one cycle/two cycle operation, based
on the OpMode setting.

Old value buffer 
Current Samples   1  cycle / 
   2 cycle


60ms
Abs
> AND
StartSampleDelta
t

DelI>
q‐1

q‐1

IEC17000191-2-en.vsdx

IEC17000191 V2 EN-US

Figure 394: Simplified logic diagram for sample based delta detection

14.5.7.4 RMS/DFT based supervision GUID-427A82EF-1BB6-45C5-BAEB-2DF50A9D99BD v2

This mode uses the RMS or DFT magnitude value of the current signal for the delta detection.
The logic of this scheme is given in Figure 395. Difference between the present value and the
old value is used for the delta detection. The old value is chosen based on the setting DeltaT,
which is defined as the number of old power cycles.

The function has an execution cycle of 3 ms. For a DeltaT setting of 3, the old
value is 60 ms. Therefore, accuracy of the old cycle data depends upon the
execution cycle.

The output of the comparator is ascertained for half a cycle before releasing a STARTMAG
signal. In DELISPVC, the DelI> setting is set in % of IB.

Additional information for the STARTRISE and STARTLOW outputs of the delta are also
available in this mode. The STARTRISE and STARTLOW outputs will be sealed by the start
signal. These outputs explains the reason for the STARTMAG signal.

Seal‐in  STARTLOW
logic

0.1
>

Seal‐in  STARTRISE
> logic
RMS Input Delay defined by  ‐0.1
DeltaT
0. 5 cycle
‐ Abs STARTMAG
> t
DelI>

IEC17000192-2-en.vsdx

IEC17000192 V2 EN-US

Figure 395: Simplified logic diagram for RMS based delta detection

14.5.7.5 2nd Harmonic blocking GUID-BE749AFA-992C-44A6-8C12-12BA4D1AA674 v2

Presence of the harmonics is another reason for maloperation of the delta based protection.
The 2nd harmonic blocking is an additional security feature in this function. It can be enabled
by the EnaHarm2Blk setting. If the ratio of 2nd harmonic frequency signal magnitude to the
fundamental frequency magnitude is greater than the set level harmBlkLev, then this feature
will block the start signal of the delta protection. The logic for this functionality is shown in
Figure 396. The tON of 1.25 cycle is added to ensure a reliable harmonic blocking. The tOFF of 2
cycles is added to block the operation during any sudden increase in the current load.

Line distance protection REL670 677


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 506 370-UEN J
Secondary system supervision

EnaHarm2Blk
2 cycles
t HARM2BLK
DFTInput‐2ndHarm AND
< 1.25 cycle
t
DFTInput ‐ fundamental
X
HarmBlkLev
IEC17000194-2-en.vsdx

IEC17000194 V2 EN-US

Figure 396: Simplified logic diagram for 2nd harmonic blocking logic

14.5.7.6 3rd Harmonic based adaption GUID-02A00917-EAB6-47F9-8375-643F76AA0D2B v2

Present days power system network has high amount of the 3rd harmonics presence due to
heavy power electronic devices. In such case, many networks modify the settings based on the
3rd harmonic present in the system. Delta supervision can be adapted based on the 3rd
harmonic present in the signal. When OpMode is set to DFTMag and EnStValAdap is set to is
Enable, then the setting DelI> will change based on the StValGrad setting if the third harmonic
is greater than the set level defined by the Harm3Level setting. The logic for this functionality
is shown in Figure 397.

 DelI  New  DelI 1  StValGrad 

DeltaMode = DFTMag

EnStValAdap = Enable/Disable
2 cycle
t ADAPTSTLEV
rd
DFTInput ‐ 3  Harmonics AND
< 1.25 cycle
DFTInput ‐ fundamental t
X
Harm3Lev
StValGrad X T DeltaMagToComp
F
DelI>

IEC17000195-2-en.vsdx
IEC17000195 V2 EN-US

Figure 397: Simplified logic diagram for 3rd harmonic restrain of MagStVal setting
Since this mode is adaptably changing the setting, the tOFF time is mandatory to ensure the
reliable operation during any sudden change.

678 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 14
Secondary system supervision

14.5.8 Technical data


GUID-ED3FE722-1F29-4340-94E9-6C907C4474F2 v3

Table 456: DELISPVC technical data


Function Range or value Accuracy
Minimum current (5.0 - 50.0)% of IBase ±1.0% of Ir at I ≤ Ir±1.0% of I at I > Ir
DelI> (10.0 - 500.0)% of IBase Instantaneous 1 cycle &
Instantaneous 2 cycle mode:±20% of
Ir at I ≤ Ir±20% of I at I > IrRMS & DFT
Mag mode:±10% of Ir at I ≤ Ir±10%
of I at I > Ir
Second harmonic blocking (5.0 - 100.0)% of fundamental ±2.0% of Ir
Third harmonic (5.0 - 100.0)% of fundamental ±2.0% of Ir
restraining
Operate time for Instantaneous 1 cycle &
changeat Ir to (Ir + 2 x Instantaneous 2 cycle mode - <20ms
DelI>)at Ir to (Ir + 5 x RMS & DFT Mag mode - <30ms
DelI>)

14.6 Delta supervision of real input DELSPVC GUID-470F7470-F3D1-46BC-B0EA-CD180FBA0AB2 v1

14.6.1 Identification
GUID-66CFBA71-B3A4-489F-B7F4-F1909B75E1DD v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Delta supervision of real input DELSPVC – –

14.6.2 Functionality GUID-8FAD2CCF-091F-4CDB-8ABF-1BDC874A8403 v2

Delta supervision functions are used to quickly detect (sudden) changes in the power system.
Real input delta supervision (DELSPVC) function is a general delta function. It is used to detect
the change measured qualities over a settable time period, such as:

• Power
• Reactive power
• Temperature
• Frequency
• Power factor

14.6.3 Function block GUID-1472A816-E653-4828-8F03-4B26B93E7EF9 v1

DELSPVC
BLOCK START
INPUT STRISE
STLOW
DELREAL
IEC17000202-1-en.vsdx
IEC17000202 V1 EN-US

Figure 398: DELSPVC function block

Line distance protection REL670 679


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 506 370-UEN J
Secondary system supervision

14.6.4 Signals
PID-7096-INPUTSIGNALS v1

Table 457: DELSPVC Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
INPUT REAL 0 Real Input

PID-7096-OUTPUTSIGNALS v1

Table 458: DELSPVC Output signals


Name Type Description
START BOOLEAN Start of function
STRISE BOOLEAN Rise signal when input has increased
STLOW BOOLEAN Low signal when input has decreased
DELREAL REAL Delta value of real input

14.6.5 Settings
PID-7096-SETTINGS v1

Table 459: DELSPVC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
MinStVal 0.1 - 99999.9 - 0.1 1.0 Minimum start value for release of
delta function
DeltaT 6 - 100 cycle 1 10 Number of old execution cycle for
delta calculation
DelSt> 0.1 - 9999999.9 - 0.1 10.0 Delta start level for real input
tHold 0.10 - 60.00 s 0.01 0.10 Hold time for start signal

14.6.6 Operation principle GUID-CA9B38EB-26E4-4286-8517-C5ECDA730236 v1

Delta supervision of real input DELSPVC is a general delta function with the following features:

• Check of the minimum signal level


• Detect an increase or decrease of the measured value

The general design of DELSPVC is shown in Figure 399.

680 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 14
Secondary system supervision

Seal‐in  STARTLOW
Logic

>
0.1
Seal‐in  STARTRISE
Logic
REALIN Delay defined by  >
‐0.1
DeltaT
0. 5 cycle
‐ Abs
> t
DelStLevel
tHold
& t
>
MinStVal

IEC17000203-1-en.vsdx
IEC17000203 V1 EN-US

Figure 399: Simplified logic diagram for DELSPVC


The setting MinStVal is used to check and release the signals for the delta supervision. In its
initial condition, during the first time a real value signal is detected (ascertained by the
MinStVal comparator), the delta detection is blocked for operation for the next 11 cycles. These
11 cycles are used to block any unwanted operation during the initialization of the function.

The outputs STARTRISE and STARTLOW are released based on the difference (respectively
above and below) from the old value at the instant when the START signal is released.

Line distance protection REL670 681


Technical manual
© Copyright 2017 ABB. All rights reserved
682
1MRK 506 370-UEN J Section 15
Control

Section 15 Control
15.1 Synchrocheck, energizing check, and synchronizing
SESRSYN IP14558-1 v4

15.1.1 Identification
M14889-1 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Synchrocheck, energizing check, and SESRSYN 25
synchronizing
sc/vc

SYMBOL-M V1 EN-US

15.1.2 Functionality M12480-3 v16

The Synchronizing function allows closing of asynchronous networks at the correct moment
including the breaker closing time, which improves the network stability.

Synchrocheck, energizing check, and synchronizing (SESRSYN) function checks that the
voltages on both sides of the circuit breaker are in synchronism, or with at least one side dead
to ensure that closing can be done safely.

SESRSYN function includes a built-in voltage selection scheme for double bus and 1½ breaker
or ring busbar arrangements.

Manual closing as well as automatic reclosing can be checked by the function and can have
different settings.

For systems, which can run asynchronously, a synchronizing feature is also provided. The main
purpose of the synchronizing feature is to provide controlled closing of circuit breakers when
two asynchronous systems are in phase and can be connected. The synchronizing feature
evaluates voltage difference, phase angle difference, slip frequency and frequency rate of
change before issuing a controlled closing of the circuit breaker. Breaker closing time is a
setting.

Line distance protection REL670 683


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

15.1.3 Function block M12431-3 v7

SESRSYN
U3PBB1* SYNOK
U3PBB2* AUTOSYOK
U3PLN1* AUTOENOK
U3PLN2* MANSYOK
BLOCK MANENOK
BLKSYNCH TSTSYNOK
BLKSC TSTAUTSY
BLKENERG TSTMANSY
B1QOPEN TSTENOK
B1QCLD USELFAIL
B2QOPEN B1SEL
B2QCLD B2SEL
LN1QOPEN LN1SEL
LN1QCLD LN2SEL
LN2QOPEN SYNPROGR
LN2QCLD SYNFAIL
UB1OK UOKSYN
UB1FF UDIFFSYN
UB2OK FRDIFSYN
UB2FF FRDIFFOK
ULN1OK FRDERIVA
ULN1FF UOKSC
ULN2OK UDIFFSC
ULN2FF FRDIFFA
STARTSYN PHDIFFA
TSTSYNCH FRDIFFM
TSTSC PHDIFFM
TSTENERG INADVCLS
AENMODE UDIFFME
MENMODE FRDIFFME
PHDIFFME
UBUS
ULINE
MODEAEN
MODEMEN

IEC10000046-1-en.vsd
IEC10000046 V1 EN-US

Figure 400: SESRSYN function block

15.1.4 Signals
PID-6724-INPUTSIGNALS v1

Table 460: SESRSYN Input signals


Name Type Default Description
U3PBB1 GROUP - Group signal for phase to earth voltage input L1, busbar 1
SIGNAL
U3PBB2 GROUP - Group signal for phase to earth voltage input L1, busbar 2
SIGNAL
U3PLN1 GROUP - Group signal for phase to earth voltage input L1, line 1
SIGNAL
U3PLN2 GROUP - Group signal for phase to earth voltage input L1, line 2
SIGNAL
BLOCK BOOLEAN 0 General block
BLKSYNCH BOOLEAN 0 Block synchronizing
BLKSC BOOLEAN 0 Block synchro check
BLKENERG BOOLEAN 0 Block energizing check
B1QOPEN BOOLEAN 0 Open status for CB or disconnector connected to bus1
B1QCLD BOOLEAN 0 Close status for CB or disconnector connected to bus1
B2QOPEN BOOLEAN 0 Open status for CB or disconnector connected to bus2
B2QCLD BOOLEAN 0 Close status for CB or disconnector connected to bus2
Table continues on next page

684 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

Name Type Default Description


LN1QOPEN BOOLEAN 0 Open status for CB or disconnector connected to line1
LN1QCLD BOOLEAN 0 Close status for CB or disconnector connected to line1
LN2QOPEN BOOLEAN 0 Open status for CB or disconnector connected to line2
LN2QCLD BOOLEAN 0 Close status for CB or disconnector connected to line2
UB1OK BOOLEAN 0 Bus1 voltage transformer OK
UB1FF BOOLEAN 0 Bus1 voltage transformer fuse failure
UB2OK BOOLEAN 0 Bus2 voltage transformer OK
UB2FF BOOLEAN 0 Bus2 voltage transformer fuse failure
ULN1OK BOOLEAN 0 Line1 voltage transformer OK
ULN1FF BOOLEAN 0 Line1 voltage transformer fuse failure
ULN2OK BOOLEAN 0 Line2 voltage transformer OK
ULN2FF BOOLEAN 0 Line2 voltage transformer fuse failure
STARTSYN BOOLEAN 0 Start synchronizing
TSTSYNCH BOOLEAN 0 Set synchronizing in test mode
TSTSC BOOLEAN 0 Set synchro check in test mode
TSTENERG BOOLEAN 0 Set energizing check in test mode
AENMODE INTEGER 0 Input for setting of automatic energizing mode
MENMODE INTEGER 0 Input for setting of manual energizing mode

PID-6724-OUTPUTSIGNALS v1

Table 461: SESRSYN Output signals


Name Type Description
SYNOK BOOLEAN Synchronizing OK output
AUTOSYOK BOOLEAN Auto synchro check OK
AUTOENOK BOOLEAN Automatic energizing check OK
MANSYOK BOOLEAN Manual synchro check OK
MANENOK BOOLEAN Manual energizing check OK
TSTSYNOK BOOLEAN Synchronizing OK test output
TSTAUTSY BOOLEAN Auto synchro check OK test output
TSTMANSY BOOLEAN Manual synchro check OK test output
TSTENOK BOOLEAN Energizing check OK test output
USELFAIL BOOLEAN Selected voltage transformer fuse failed
B1SEL BOOLEAN Bus1 selected
B2SEL BOOLEAN Bus2 selected
LN1SEL BOOLEAN Line1 selected
LN2SEL BOOLEAN Line2 selected
SYNPROGR BOOLEAN Synchronizing in progress
SYNFAIL BOOLEAN Synchronizing failed
UOKSYN BOOLEAN Voltage amplitudes for synchronizing above set limits
UDIFFSYN BOOLEAN Voltage difference out of limit for synchronizing
FRDIFSYN BOOLEAN Frequency difference out of limit for synchronizing
FRDIFFOK BOOLEAN Frequency difference in band for synchronizing
Table continues on next page

Line distance protection REL670 685


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

Name Type Description


FRDERIVA BOOLEAN Frequency derivative out of limit for synchronizing
UOKSC BOOLEAN Voltage amplitudes above set limits
UDIFFSC BOOLEAN Voltage difference out of limit
FRDIFFA BOOLEAN Frequency difference out of limit for Auto operation
PHDIFFA BOOLEAN Phase angle difference out of limit for Auto operation
FRDIFFM BOOLEAN Frequency difference out of limit for Manual operation
PHDIFFM BOOLEAN Phase angle difference out of limit for Manual Operation
INADVCLS BOOLEAN Inadvertent circuit breaker closing
UDIFFME REAL Calculated difference of voltage in p.u of set voltage base
value
FRDIFFME REAL Calculated difference of frequency
PHDIFFME REAL Calculated difference of phase angle
UBUS REAL Bus voltage
ULINE REAL Line voltage
MODEAEN INTEGER Selected mode for automatic energizing
MODEMEN INTEGER Selected mode for manual energizing

15.1.5 Settings
PID-6724-SETTINGS v2

Table 462: SESRSYN Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
OperationSynch Off - - Off Operation for synchronizing function
On Off/On
UHighBusSynch 50.0 - 120.0 %UBB 1.0 80.0 Voltage high limit bus for
synchronizing in % of UBaseBus
UHighLineSynch 50.0 - 120.0 %UBL 1.0 80.0 Voltage high limit line for
synchronizing in % of UBaseLine
UDiffSynch 0.02 - 0.50 pu 0.01 0.10 Voltage difference limit for
synchronizing in p.u of set voltage
base value
FreqDiffMin 0.003 - 0.250 Hz 0.001 0.010 Minimum frequency difference limit
for synchronizing
FreqDiffMax 0.050 - 1.000 Hz 0.001 0.200 Maximum frequency difference limit
for synchronizing
CloseAngleMax 15.0 - 30.0 Deg 1.0 15.0 Maximum closing angle between bus
and line for synchronizing
FreqRateChange 0.000 - 0.500 Hz/s 0.001 0.300 Maximum allowed frequency rate of
change
tBreaker 0.000 - 1.000 s 0.001 0.080 Closing time of the breaker
tClosePulse 0.050 - 60.000 s 0.001 0.200 Breaker closing pulse duration
tMaxSynch 0.00 - 6000.00 s 0.01 600.00 Resets synch if no close has been
made before set time
tMinSynch 0.000 - 60.000 s 0.001 2.000 Minimum time to accept
synchronizing conditions
Table continues on next page

686 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

Name Values (Range) Unit Step Default Description


OperationSC Off - - On Operation for synchronism check
On function Off/On
UHighBusSC 50.0 - 120.0 %UBB 1.0 80.0 Voltage high limit bus for
synchrocheck in % of UBaseBus
UHighLineSC 50.0 - 120.0 %UBL 1.0 80.0 Voltage high limit line for
synchrocheck in % of UBaseLine
UDiffSC 0.02 - 0.50 pu 0.01 0.15 Voltage difference limit for
synchrocheck in p.u of set voltage
base value
FreqDiffA 0.003 - 1.000 Hz 0.001 0.010 Frequency difference limit between
bus and line Auto
FreqDiffM 0.003 - 1.000 Hz 0.001 0.010 Frequency difference limit between
bus and line Manual
PhaseDiffA 5.0 - 90.0 Deg 1.0 25.0 Phase angle difference limit between
bus and line Auto
PhaseDiffM 5.0 - 90.0 Deg 1.0 25.0 Phase angle difference limit between
bus and line Manual
tSCA 0.000 - 60.000 s 0.001 0.100 Time delay output for synchrocheck
Auto
tSCM 0.000 - 60.000 s 0.001 0.100 Time delay output for synchrocheck
Manual
AutoEnerg Off - - DLLB Automatic energizing check mode
DLLB
DBLL
Both
ManEnerg Off - - Both Manual energizing check mode
DLLB
DBLL
Both
ManEnergDBDL Off - - Off Manual dead bus, dead line energizing
On
UHighBusEnerg 50.0 - 120.0 %UBB 1.0 80.0 Voltage high limit bus for energizing
check in % of UBaseBus
UHighLineEnerg 50.0 - 120.0 %UBL 1.0 80.0 Voltage high limit line for energizing
check in % of UBaseLine
ULowBusEnerg 10.0 - 80.0 %UBB 1.0 40.0 Voltage low limit bus for energizing
check in % of UBaseBus
ULowLineEnerg 10.0 - 80.0 %UBL 1.0 40.0 Voltage low limit line for energizing
check in % of UBaseLine
UMaxEnerg 50.0 - 180.0 %UB 1.0 115.0 Maximum voltage for energizing in %
of UBase, Line and/or Bus
tAutoEnerg 0.000 - 60.000 s 0.001 0.100 Time delay for automatic energizing
check
tManEnerg 0.000 - 60.000 s 0.001 0.100 Time delay for manual energizing
check

Line distance protection REL670 687


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

Table 463: SESRSYN Non group settings (basic)


Name Values (Range) Unit Step Default Description
SelPhaseBus1 Phase L1 - - Phase L1 Select phase for busbar1
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
GblBaseSelBus 1 - 12 - 1 1 Selection of one of the Global Base
Value groups, Bus
GblBaseSelLine 1 - 12 - 1 1 Selection of one of the Global Base
Value groups, Line
SelPhaseBus2 Phase L1 - - Phase L1 Select phase for busbar2
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
SelPhaseLine1 Phase L1 - - Phase L1 Select phase for line1
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
SelPhaseLine2 Phase L1 - - Phase L1 Select phase for line2
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
CBConfig No voltage sel. - - No voltage sel. Select CB configuration
Double bus
1 1/2 bus CB
1 1/2 bus alt. CB
Tie CB

Table 464: SESRSYN Non group settings (advanced)


Name Values (Range) Unit Step Default Description
PhaseShift -180 - 180 Deg 1 0 Additional phase angle for selected
line voltage

15.1.6 Monitored data


PID-6724-MONITOREDDATA v1

Table 465: SESRSYN Monitored data


Name Type Values (Range) Unit Description
UDIFFME REAL - - Calculated difference of voltage in p.u
of set voltage base value
FRDIFFME REAL - Hz Calculated difference of frequency
PHDIFFME REAL - deg Calculated difference of phase angle
UBUS REAL - kV Bus voltage
ULINE REAL - kV Line voltage

688 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

15.1.7 Operation principle

15.1.7.1 Basic functionality M14832-3 v8

The synchrocheck feature measures the conditions across the circuit breaker and compares
them to set limits. The output for closing operation is given when all measured quantities are
simultaneously within their set limits.

The energizing check feature measures the bus and line voltages and compares them to both
high and low threshold detectors. The output is given only when the actual measured
quantities match the set conditions.

The synchronizing feature measures the conditions across the circuit breaker, and also
determines the angle change occurring during the closing delay of the circuit breaker, from the
measured slip frequency. The output is given only when all measured conditions are
simultaneously within their set limits. The closing of the output is timed to give closure at the
optimal time including the time needed for the circuit breaker and the closing circuit
operation.

The voltage difference, frequency difference and phase angle difference values are measured
in the IED centrally and are available for the SESRSYN function for evaluation. By setting the
phases used for SESRSYN, with the settings SelPhaseBus1, SelPhaseBus2, SelPhaseLine1 and
SelPhaseLine2, a compensation is made automatically for the voltage amplitude difference
and the phase angle difference caused if different setting values are selected for both sides of
the breaker. If needed, an additional phase angle adjustment can be done for selected line
voltage with the PhaseShift setting.

For double bus single circuit breaker and 1½ circuit breaker arrangements, the SESRSYN
function blocks have the capability to make the necessary voltage selection. For double bus
single circuit breaker arrangements, selection of the correct voltage is made using auxiliary
contacts of the bus disconnectors. For 1½ circuit breaker arrangements, correct voltage
selection is made using auxiliary contacts of the bus disconnectors as well as the circuit
breakers.

The internal logic for each function block as well as, the input and outputs, and the setting
parameters with default setting and setting ranges is described in this document. For
application related information, please refer to the application manual.

15.1.7.2 Logic diagrams IP14739-1 v1

M14833-3 v5
The logic diagrams that follow illustrate the main principles of the SESRSYN function
components such as Synchrocheck, Synchronizing, Energizing check and Voltage selection,
and are intended to simplify the understanding of the function.

Synchrocheck M14834-3 v15


When the function is set to OperationSC = On, the measuring will start.

The function will compare the bus and line voltage values with the set values for UHighBusSC
and UHighLineSC.

If both sides are higher than the set values, the measured values are compared with the set
values for acceptable frequency, phase angle and voltage difference: FreqDiffA, FreqDiffM,
PhaseDiffA, PhaseDiffM and UDiffSC. If additional phase angle adjustment is done with the
PhaseShift setting, the adjustment factor is deducted from the line voltage before the
comparison of the phase angle values.

The frequency on both sides of the circuit breaker is also measured. The frequencies must not
deviate from the rated frequency more than ±5Hz. The frequency difference between the bus
frequency and the line frequency is measured and may not exceed the set value FreqDiff.

Line distance protection REL670 689


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

Two sets of settings for frequency difference and phase angle difference are available and
used for the manual closing and autoreclose functions respectively, as required.

The inputs BLOCK and BLKSC are available for total block of the complete SESRSYN function
and selective block of the Synchrocheck function respectively. Input TSTSC will allow testing of
the function where the fulfilled conditions are connected to a separate test output.

The outputs MANSYOK and AUTOSYOK are activated when the actual measured conditions
match the set conditions for the respective output. The output signal can be delayed
independently for MANSYOK and AUTOSYOK conditions.

A number of outputs are available as information about fulfilled checking conditions. UOKSC
shows that the voltages are high, UDIFFSC, FRDIFFA, FRDIFFM, PHDIFFA, PHDIFFM shows
when the voltage difference, frequency difference and phase angle difference are out of limits.

Output INADVCLS, inadvertent circuit breaker closing, indicates that the circuit breaker has
been closed at wrong phase angle by mistake. The output is activated, if the voltage
conditions are fulfilled at the same time the phase angle difference between bus and line is
suddenly changed from being larger than 60 degrees to smaller than 5 degrees.

Note! Similar logic for Manual Synchrocheck.

OperationSC = On
AND TSTAUTSY
AND

invalidSelection AND
OR AUTOSYOK
AND
0-60 s
AND t
tSCA

UDiffSC 50 ms
AND t
UHighBusSC
UOKSC
AND
UHighLineSC
UDIFFSC
1

1
FRDIFFA
FreqDiffA

1
PHDIFFA
PhaseDiffA

UDIFFME
voltageDifferenceValue
FRDIFFME
frequencyDifferenceValue
PHDIFFME
phaseAngleDifferenceValue

32 ms 100 ms
AND t INADVCLS
PhDiff > 60° AND

PhDiff < 5°

IEC07000114-6-en.vsdx

IEC07000114 V6 EN-US

Figure 401: Simplified logic diagram for the auto synchrocheck function

Synchronizing SEMOD171603-4 v12


When the function is set to OperationSynch = On the measuring will be performed.

690 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

The function will compare the values for the bus and line voltage with the set values for
UHighBusSynch and UHighLineSynch, which is a supervision that the voltages are both live.
Also the voltage difference is checked to be smaller than the set value for UDiffSynch, which is
a p.u value of set voltage base values. If both sides are higher than the set values and the
voltage difference between bus and line is acceptable, the measured values are compared with
the set values for acceptable frequency FreqDiffMax and FreqDiffMin, rate of change of
frequency FreqRateChange and phase angle CloseAngleMax.

The measured frequencies between the settings for the maximum and minimum frequency will
initiate the measuring and the evaluation of the angle change to allow operation to be sent at
the right moment including the set tBreaker time. The calculation of the operation pulse sent
in advance is using the measured SlipFrequency and the set tBreaker time. To prevent
incorrect closing pulses, a maximum closing angle between bus and line is set with
CloseAngleMax. Table 466 below shows the maximum settable value for tBreaker when
CloseAngleMax is set to 15 or 30 degrees, at different allowed slip frequencies for
synchronizing. To minimize the moment stress when synchronizing near a power station, a
narrower limit for CloseAngleMax needs to be used.

Table 466: Dependencies between tBreaker and SlipFrequency with different CloseAngleMax values
tBreaker [s] (max settable value) tBreaker [s] (max settable value) SlipFrequency [Hz]
with CloseAngleMax = 15 degrees with CloseAngleMax = 30 degrees (BusFrequency - LineFrequency)
[default value] [max value]
0.040 0.080 1.000
0.050 0.100 0.800
0.080 0.160 0.500
0.200 0.400 0.200
0.400 0.810 0.100
1.000 0.080
0.800 0.050
1.000 0.040

At operation the SYNOK output will be activated with a pulse tClosePulse and the function
resets. The function will also reset if the synchronizing conditions are not fulfilled within the
set tMaxSynch time. This prevents that the function is, by mistake, maintained in operation for
a long time, waiting for conditions to be fulfilled.

The inputs BLOCK and BLKSYNCH are available for total block of the complete SESRSYN
function and block of the Synchronizing function respectively. TSTSYNCH will allow testing of
the function where the fulfilled conditions are connected to a separate output.

Line distance protection REL670 691


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

OperationSynch=On

TSTSYNCH

STARTSYN

invalidSelection
SYNPROGR
AND
BLOCK AND
S
BLKSYNCH OR
R

UDiffSynch
50 ms SYNOK
AND
UHighBusSynch AND t

UHighLineSynch OR

FreqDiffMax TSTSYNOK
AND
FreqDiffMin

tClosePulse
FreqRateChange
AND

fBus&fLine ± 5Hz
tMaxSynch
CloseAngleMax AND
SYNFAIL

PhaseDiff=Close pulse in advance

FreqDiff
Close pulse
in advance
tBreaker

=IEC06000636=5=en=Original.vsd
IEC06000636 V5 EN-US

Figure 402: Simplified logic diagram for the synchronizing function

Energizing check M14835-3 v12


Voltage values are measured in the IED and are available for evaluation by the Energizing check
function.

The function measures voltages on the busbar and the line to verify whether they are live or
dead. This is done by comparing with the set values UHighBusEnerg and ULowBusEnerg for
bus energizing and UHighLineEnerg and ULowLineEnerg for line energizing.

The frequency on both sides of the circuit breaker is also measured. The frequencies must not
deviate from the rated frequency more than +/-5Hz.

The Energizing direction can be selected individually for the Manual and the Automatic
functions respectively. When the conditions are met the outputs AUTOENOK and MANENOK
respectively will be activated if the fuse supervision conditions are fulfilled. The output signal
can be delayed independently for MANENOK and AUTOENOK conditions. The Energizing
direction can also be selected by an integer input AENMODE respective MENMODE, which for
example, can be connected to a Binary to Integer function block (B16I). Integers supplied shall
be 1=Off, 2=DLLB, 3=DBLL and 4= Both. Not connected input will mean that the setting is done
from Parameter Setting tool. The active position can be read on outputs MODEAEN resp
MODEMEN. The modes are 0=OFF, 1=DLLB, 2=DBLL and 3=Both.

The inputs BLOCK and BLKENERG are available for total block of the complete SESRSYN
function respective block of the Energizing check function. TSTENERG will allow testing of the
function where the fulfilled conditions are connected to a separate test output.

692 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

manEnergOpenBays
MANENOK
OR

TSTENERG

BLKENERG
OR
BLOCK

selectedFuseOK

UHighBusEnerg
DLLB tManEnerg
AND
OR t
AND
OR
ULowLineEnerg AND

ManEnerg BOTH

ULowBusEnerg
DBLL
AND

UHighLineEnerg

TSTENOK
ManEnergDBDL AND AND

UMaxEnerg
fBus and fLine ±5 Hz

IEC14000031-1-en.vsd
IEC14000031 V1 EN-US

Figure 403: Manual energizing

TSTENERG

BLKENERG
OR
BLOCK

selectedFuseOK

UHighBusEnerg
DLLB 50ms tAutoEnerg
AND
OR t t
AND OR
AUTOENOK
ULowLineEnerg AND
BOTH
AutoEnerg
ULowBusEnerg
DBLL
AND

UHighLineEnerg

TSTENOK
UMaxEnerg AND

fBus and fLine ±5 Hz

IEC14000030-2-en.vsdx
IEC14000030 V2 EN-US

Figure 404: Automatic energizing

Line distance protection REL670 693


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

BLKENERG
BLOCK OR manEnergOpenBays
AND

ManEnerg

1½ bus CB
CBConfig AND

B1QOPEN
LN1QOPEN AND
OR
B1QCLD
B2QOPEN
AND

LN2QOPEN

1½ bus alt. CB AND OR


AND
OR

B2QCLD
AND

Tie CB
AND
AND
OR

AND

IEC14000032-1-en.vsd
IEC14000032 V1 EN-US

Figure 405: Open bays

Fuse failure supervision M14837-3 v11


External fuse failure signals or signals from a tripped fuse switch/MCB are connected to binary
inputs that are configured to the inputs of SESRSYN function in the IED. Alternatively, the
internal signals from fuse failure supervision can be used when available. There are two
alternative connection possibilities. Inputs labelled OK must be connected if the available
contact indicates that the voltage circuit is healthy. Inputs labelled FF must be connected if
the available contact indicates that the voltage circuit is faulty.

The UB1OK/UB2OK and UB1FF/UB2FF inputs are related to the busbar voltage and the
ULN1OK/ULN2OK and ULN1FF/ULN2FF inputs are related to the line voltage. Configure them
to the binary input or function outputs that indicate the status of the external fuse failure of
the busbar and line voltages. In the event of a fuse failure, the energizing check function is
blocked. The synchronizing and the synchrocheck function requires full voltage on both sides,
thus no blocking at fuse failure is needed.

Voltage selection M14836-3 v9


The voltage selection module including supervision of included voltage transformers for the
different arrangements is a basic part of the SESRSYN function and determines the voltages
fed to the Synchronizing, Synchrocheck and Energizing check functions. This includes the
selection of the appropriate Line and Bus voltages and MCB supervision.

The voltage selection type to be used is set with the parameter CBConfig.

If No voltage sel. is set the voltages used will be U-Line1 and U-Bus1. This setting is also used in
the case when external voltage selection is provided. Fuse failure supervision for the used
inputs must also be connected.

The voltage selection function, selected voltages, and fuse conditions are used for the
Synchronizing, Synchrocheck and Energizing check inputs.

694 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

For the disconnector positions it is advisable to use (NO) a and (NC) b type contacts to supply
Disconnector Open and Closed positions but, it is also possible to use an inverter for one of
the positions.

If breaker or disconnector positions not are available for deciding if energizing is allowed, it is
considered to be allowed to manually energize. This is only allowed for manual energizing in
1½ breaker and Tie breaker arrangements. Manual energization of a completely open diameter
in 1 1/2 CB switchgear is allowed by internal logic.

Voltage selection for a single circuit breaker with double busbars M14838-3 v9
The setting CBConfig selected for Double Bus activates the voltage selection for single CB and
double busbars. This function uses the binary input from the disconnectors auxiliary contacts
B1QOPEN-B1QCLD for Bus 1, and B2QOPEN-B2QCLD for Bus 2 to select between bus 1 and bus
2 voltages. If the disconnector connected to bus 1 is closed and the disconnector connected to
bus 2 is opened the bus 1 voltage is used. All other combinations use the bus 2 voltage. The
outputs B1SEL and B2SEL respectively indicate the selected Bus voltage.

The function checks the fuse-failure signals for bus 1, bus 2 and line voltage transformers.
Inputs UB1OK-UB1FF supervise the MCB for Bus 1 and UB2OK-UB2FF supervises the MCB for
Bus 2. ULN1OK and ULN1FF supervises the MCB for the Line voltage transformer. The inputs
fail (FF) or healthy (OK) can alternatively be used dependent on the available signal. If a VT
failure is detected in the selected voltage source an output signal USELFAIL is set. This output
signal is true if the selected bus or line voltages have a VT failure. This output as well as the
function can be blocked with the input signal BLOCK. The function logic diagram is shown in
figure 406.

B1QOPEN
B1SEL
B1QCLD AND

B2QOPEN B2SEL
AND
1
B2QCLD
invalidSelection
AND

bus1Voltage busVoltage

bus2Voltage

UB1OK AND
UB1FF OR
OR selectedFuseOK
AND
UB2OK AND
UB2FF OR USELFAIL
AND

ULN1OK
ULN1FF OR

BLOCK

en05000779-2.vsd
IEC05000779 V2 EN-US

Figure 406: Logic diagram for the voltage selection function of a single circuit breaker with double
busbars

Line distance protection REL670 695


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

Voltage selection for a 1 1/2 circuit breaker arrangement M14839-3 v8


Note that with 1½ breaker schemes three Synchrocheck functions must be used for the
complete diameter. Below, the scheme for one Bus breaker and the Tie breaker is described.

With the setting parameter CBConfig the selection of actual CB location in the 1 1/2 circuit
breaker switchgear is done. The settings are: 1 1/2 Bus CB, 1 1/2 alt. Bus CB or Tie CB.

This voltage selection function uses the binary inputs from the disconnectors and circuit
breakers auxiliary contacts to select the right voltage for the SESRSYN function. For the bus
circuit breaker one side of the circuit breaker is connected to the busbar and the other side is
connected either to line 1, line 2 or the other busbar depending on the best selection of voltage
circuit.

Inputs LN1QOPEN-LN1QCLD, B1QOPEN-B1QCLD, B2QOPEN-B2QCLD, LN2QOPEN-LN2QCLD are


inputs for the position of the Line disconnectors respectively the Bus and Tie breakers. The
outputs LN1SEL, LN2SEL and B2SEL will give indication of the selected Line voltage as a
reference to the fixed Bus 1 voltage, which indicates B1SEL.

The fuse supervision is connected to ULN1OK-ULN1FF, ULN2OK-ULN2FF and with alternative


Healthy or Failing fuse signals depending on what is available from each fuse (MCB).

The tie circuit breaker is connected either to bus 1 or line 1 voltage on one side and the other
side is connected either to bus 2 or line 2 voltage. Four different output combinations are
possible, bus to bus, bus to line, line to bus and line to line.

• The line 1 voltage is selected if the line 1 disconnector is closed.


• The bus 1 voltage is selected if the line 1 disconnector is open and the bus 1 circuit breaker
is closed.
• The line 2 voltage is selected if the line 2 disconnector is closed.
• The bus 2 voltage is selected if the line 2 disconnector is open and the bus 2 circuit breaker
is closed.

The function also checks the fuse-failure signals for bus 1, bus 2, line 1 and line 2. If a VT failure
is detected in the selected voltage an output signal USELFAIL is set. This output signal is true
if the selected bus or line voltages have a MCB trip. This output as well as the function can be
blocked with the input signal BLOCK. The function block diagram for the voltage selection of a
bus circuit breaker is shown in figure 407 and for the tie circuit breaker in figure 408.

696 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

LN1QOPEN
AND
LN1SEL
LN1QCLD

B1QOPEN
LN2SEL
B1QCLD AND AND
B2SEL
OR
LN2QOPEN
AND invalidSelection
LN2QCLD AND
AND
B2QOPEN
B2QCLD AND

line1Voltage lineVoltage

line2Voltage

bus2Voltage

UB1OK
UB1FF OR

OR selectedFuseOK
UB2OK AND
AND
UB2FF OR

USELFAIL
ULN1OK AND
AND
ULN1FF OR

ULN2OK
AND
ULN2FF OR

BLOCK

en05000780-2.vsd
IEC05000780 V2 EN-US

Figure 407: Simplified logic diagram for the voltage selection function for a bus circuit breaker in a 1 1/2
breaker arrangement

Line distance protection REL670 697


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

LN1QOPEN
AND
LN1SEL
LN1QCLD
B1SEL
1

B1QOPEN AND
AND
B1QCLD AND

line1Voltage busVoltage

bus1Voltage
LN2QOPEN
LN2SEL
LN2QCLD AND
B2SEL
1
invalidSelection
OR
B2QOPEN AND
AND
B2QCLD AND

line2Voltage lineVoltage

bus2Voltage

UB1OK AND
UB1FF OR

OR selectedFuseOK
UB2OK AND
AND
UB2FF OR

USELFAIL
ULN1OK AND
AND
ULN1FF OR

ULN2OK
AND
ULN2FF OR

BLOCK

en05000781-2.vsd
IEC05000781 V2 EN-US

Figure 408: Simplified logic diagram for the voltage selection function for the tie circuit breaker in 1 1/2
breaker arrangement.

15.1.8 Technical data


M12359-1 v15

Table 467: SESRSYN technical data


Function Range or value Accuracy
Phase shift, jline - jbus (-180 to 180) degrees -

Voltage high limit for synchronizing and (50.0-120.0)% of UBase ±0.5% of Ur at U ≤ Ur


synchrocheck ±0.5% of U at U > Ur

Reset ratio, synchrocheck > 95% -


Frequency difference limit between bus (0.003-1.000) Hz ±2.5 mHz
and line for synchrocheck
Table continues on next page

698 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

Function Range or value Accuracy


Phase angle difference limit between bus (5.0-90.0) degrees ±2.0 degrees
and line for synchrocheck
Voltage difference limit between bus and (0.02-0.5) p.u ±0.5% of Ur
line for synchronizing and synchrocheck
Time delay output for synchrocheck when (0.000-60.000) s ±0.2% or ±35 ms whichever is
angle difference between bus and line greater
jumps from “PhaseDiff” + 2 degrees to
“PhaseDiff” - 2 degrees
Frequency difference minimum limit for (0.003-0.250) Hz ±2.5 mHz
synchronizing
Frequency difference maximum limit for (0.050-1.000) Hz ±2.5 mHz
synchronizing
Maximum allowed frequency rate of (0.000-0.500) Hz/s ±10.0 mHz/s
change
Maximum closing angle between bus and (15-30) degrees ±2.0 degrees
line for synchronizing
Breaker closing pulse duration (0.050-1.000) s ±0.2% or ±15 ms whichever is
greater
tMaxSynch, which resets synchronizing (0.000-6000.00) s ±0.2% or ±35 ms whichever is
function if no close has been made before greater
set time
Minimum time to accept synchronizing (0.000-60.000) s ±0.2% or ±35 ms whichever is
conditions greater
Voltage high limit for energizing check (50.0-120.0)% of UBase ±0.5% of Ur at U ≤ Ur
±0.5% of U at U > Ur

Reset ratio, voltage high limit > 95% -


Voltage low limit for energizing check (10.0-80.0)% of UBase ±0.5% of Ur

Reset ratio, voltage low limit < 105% -


Maximum voltage for energizing (50.0-180.0)% of UBase ±0.5% of Ur at U ≤ Ur
±0.5% of U at U > Ur

Time delay for energizing check when (0.000-60.000) s ±0.2% or ±100 ms whichever is
voltage jumps from 0 to 90% of Urated greater
Operate time for synchrocheck function Min. = 15 ms –
when angle difference between bus and Max. = 30 ms
line jumps from “PhaseDiff” + 2 degrees to
“PhaseDiff” - 2 degrees
Operate time for energizing function Min. = 70 ms –
when voltage jumps from 0 to 90% of Max. = 90 ms
Urated

15.2 Autorecloser for 1 phase, 2 phase and/or 3 phase


operation SMBRREC IP14559-1 v6

Line distance protection REL670 699


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

15.2.1 Identification
M14890-1 v7

Function Description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Autorecloser for 1 phase, 2 phase and/or 3 SMBRREC 79
phase
5(0 -->1)
IEC15000204 V1 EN-US

15.2.2 Functionality M12390-3 v17

The auto recloser (SMBRREC) function provides:

• high-speed and/or delayed auto reclosing


• single and/or three phase auto reclosing
• support for single or multi-breaker applications.

The auto recloser can be used for delayed busbar restoration.

Up to five reclosing shots can be performed. The first shot can be single-, two-, and /or three-
phase depending on the type of the fault and the selected auto reclosing mode.

Several auto reclosing functions can be provided for multi-breaker arrangements. A priority
circuit allows one circuit breaker to reclose first and the second will only close if the fault
proved to be transient.

Each auto reclosing function can be configured to co-operate with the synchrocheck function.

15.2.3 Function block M12633-3 v6

SMBRREC
ON BLOCKED
OFF SETON
BLKON READY
BLKOFF ACTIVE
RESET SUCCL
INHIBIT UNSUCCL
START INPROGR
STARTHS 1PT1
TRSOTF 2PT1
SKIPHS 3PT1
ZONESTEP 3PT2
TR2P 3PT3
TR3P 3PT4
THOLHOLD 3PT5
CBREADY PERMIT1P
CBCLOSED PREP3P
PLCLOST CLOSECB
SYNC WFMASTER
WAIT COUNT1P
RSTCOUNT COUNT2P
MODEINT COUNT3P1
COUNT3P2
COUNT3P3
COUNT3P4
COUNT3P5
COUNTAR
MODE
ABORTED
SYNCFAIL
INHIBOUT
IEC06000189-3-en.vsd
IEC06000189 V3 EN-US

Figure 409: SMBRREC function block

700 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

15.2.4 Signals
PID-6796-INPUTSIGNALS v2

Table 468: SMBRREC Input signals


Name Type Default Description
ON BOOLEAN 0 Switch AR On (at ExternalCtrl = On)
OFF BOOLEAN 0 Switch AR Off (at ExternalCtrl = On)
BLKON BOOLEAN 0 Set AR in blocked state
BLKOFF BOOLEAN 0 Release AR from blocked state
RESET BOOLEAN 0 Reset AR to initial conditions
INHIBIT BOOLEAN 0 Interrupt and inhibit reclosing sequence
START BOOLEAN 0 Start reclosing sequence
STARTHS BOOLEAN 0 Start high-speed reclosing without synchrocheck
TRSOTF BOOLEAN 0 Continue to shots 2-5 at a trip from switch-on-to-fault
SKIPHS BOOLEAN 0 Skip high speed shot and continue with delayed shots
ZONESTEP BOOLEAN 0 Coordinate local AR with down stream devices
TR2P BOOLEAN 0 Two phase trip occurred
TR3P BOOLEAN 0 Three phase trip occurred
THOLHOLD BOOLEAN 0 Hold AR in wait state
CBREADY BOOLEAN 0 Circuit breaker is ready
CBCLOSED BOOLEAN 0 Circuit breaker status
PLCLOST BOOLEAN 0 Power line carrier or other form of permissive signal is lost
SYNC BOOLEAN 0 Synchrocheck conditions are fulfilled
WAIT BOOLEAN 0 Wait for master
RSTCOUNT BOOLEAN 0 Reset counters
MODEINT INTEGER 0 Integer input used to set reclosing mode (alternative to
setting)

PID-6796-OUTPUTSIGNALS v2

Table 469: SMBRREC Output signals


Name Type Description
BLOCKED BOOLEAN AR is blocked
SETON BOOLEAN AR is operative
READY BOOLEAN AR is ready for a new sequence
ACTIVE BOOLEAN Reclosing sequence in progress
SUCCL BOOLEAN Reclosing is successful
UNSUCCL BOOLEAN Reclosing is unsuccessful
INPROGR BOOLEAN Reclosing in progress, inactive during reclaim time
1PT1 BOOLEAN Single-phase reclosing is in progress for shot 1
2PT1 BOOLEAN Two-phase reclosing is in progress for shot 1
3PT1 BOOLEAN Three-phase reclosing is in progress for shot 1
3PT2 BOOLEAN Three-phase reclosing is in progress for shot 2
3PT3 BOOLEAN Three-phase reclosing is in progress for shot 3
3PT4 BOOLEAN Three-phase reclosing is in progress for shot 4
Table continues on next page

Line distance protection REL670 701


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

Name Type Description


3PT5 BOOLEAN Three-phase reclosing is in progress for shot 5
PERMIT1P BOOLEAN Single-phase trip is permitted
PREP3P BOOLEAN Three-phase trip is prepared
CLOSECB BOOLEAN Close command for circuit breaker
WFMASTER BOOLEAN Wait signal to slave issued by master for sequential reclosing
COUNT1P INTEGER Number of single-phase reclosing shots
COUNT2P INTEGER Number of two-phase reclosing shots
COUNT3P1 INTEGER Number of three-phase shot 1 reclosings
COUNT3P2 INTEGER Number of three-phase shot 2 reclosings
COUNT3P3 INTEGER Number of three-phase shot 3 reclosings
COUNT3P4 INTEGER Number of three-phase shot 4 reclosings
COUNT3P5 INTEGER Number of three-phase shot 5 reclosings
COUNTAR INTEGER Number of total reclosing shots
MODE INTEGER Integer output for reclosing mode
ABORTED BOOLEAN General abort
SYNCFAIL BOOLEAN AR sequence is aborted by synchrocheck conditions not
fulfilled
INHIBOUT BOOLEAN AR sequence is aborted via INHIBIT input

15.2.5 Settings
PID-6796-SETTINGS v2

Table 470: SMBRREC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
ExternalCtrl Off - - Off To be set On if AR is to be used with
On external control
ARMode 3 phase - - 1/2/3ph AR mode selection
1/2/3ph
1/2ph
1ph+1*2ph
1/2ph+1*3ph
1ph+1*2/3ph
t1 1Ph 0.000 - 120.000 s 0.001 1.000 Dead time for shot 1, single-phase
reclosing
t1 3Ph 0.000 - 120.000 s 0.001 6.000 Dead time for shot 1, delayed three-
phase reclosing with synchrocheck
conditions
t1 3PhHS 0.000 - 120.000 s 0.001 0.400 Dead time for shot 1, high speed
three-phase reclosing
tReclaim 0.00 - 6000.00 s 0.01 60.00 Reclaim time
tSync 0.00 - 6000.00 s 0.01 30.00 Maximum wait time for fulfilled
synchrocheck conditions
tLongStartInh 0.000 - 60.000 s 0.001 0.200 Maximum allowed start pulse duration
tPulse 0.000 - 60.000 s 0.001 0.200 Circuit breaker closing pulse duration
Table continues on next page

702 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

Name Values (Range) Unit Step Default Description


tCBClosedMin 0.00 - 6000.00 s 0.01 5.00 Minimum time that circuit breaker
must be closed before new sequence
is allowed
tUnsucCl 0.00 - 6000.00 s 0.01 30.00 Maximun wait time for circuit breaker
closing before indicating unsuccessful
Priority None - - None Priority selection between adjacent
Low terminals
High
tWaitForMaster 0.00 - 6000.00 s 0.01 60.00 Maximum wait time for release from
master
LongStartInhib Off - - On To be set ON if AR is to be used with
On maximum allowed start pulse
duration check

Table 471: SMBRREC Group settings (advanced)


Name Values (Range) Unit Step Default Description
NoOfShots 1 - - 1 Max number of reclosing shots
2
3
4
5
StartByCBOpen Off - - Off To be set ON if AR is to be started by
On circuit breaker open position
CBReadyType CO - - CO Circuit breaker ready signal type
OCO
t1 2Ph 0.000 - 120.000 s 0.001 1.000 Dead time for shot 1, two-phase
reclosing
t2 3Ph 0.00 - 6000.00 s 0.01 30.00 Dead time for shot 2, three-phase
reclosing
t3 3Ph 0.00 - 6000.00 s 0.01 30.00 Dead time for shot 3, three-phase
reclosing
t4 3Ph 0.00 - 6000.00 s 0.01 30.00 Dead time for shot 4, three-phase
reclosing
t5 3Ph 0.00 - 6000.00 s 0.01 30.00 Dead time for shot 5, three-phase
reclosing
Extended t1 Off - - Off Extend dead time at loss of
On permissive channel
tExtended t1 0.000 - 60.000 s 0.001 0.500 Extend three-phase dead time
duration
tInhibit 0.000 - 60.000 s 0.001 5.000 Reset time for reclosing inhibit
CutPulse Off - - Off Shorten circuit breaker closing pulse
On at a new start
Follow CB Off - - Off Advance to next shot if circuit breaker
On has been closed during dead time
AutoContinue Off - - Off Continue with next reclosing shot if
On circuit breaker did not close
tAutoContWait 0.000 - 60.000 s 0.001 2.000 Wait time after close command before
proceeding to next shot
UnsucClByCBChk NoCBCheck - - NoCBCheck Unsuccessful closing signal obtained
CB check by checking circuit breaker position
BlockByUnsucCl Off - - Off Block AR at unsuccessful reclosing
On
Table continues on next page

Line distance protection REL670 703


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

Name Values (Range) Unit Step Default Description


ZoneSeqCoord Off - - Off Coordination of down stream devices
On to local protection unit’s AR
tSuccessful 0.000 - 60.000 s 0.001 1.000 Delay time before indicating
successful reclosing
tSlaveDeadTime 0.100 - 60.000 s 0.001 0.400 Wait time for the slave to close when
WAIT input has reset

15.2.6 Operation principle

15.2.6.1 Terminology explanation GUID-EA0760DF-8F0B-4146-8A42-3F20E75E1053 v1

Before describing the auto reclosing function it is first necessary to define the following
terminology:

• a shot is an attempt from the function to close a circuit breaker


• multi-shot is where more than one shot is attempted
• dead time is the time between a start of the function and the attempt to close the circuit
breaker
• reclaim time is the time from the circuit breaker closing command till the reset of the
function, should the auto reclosing attempt be successful and no new start is received
• high-speed shot is generally used for an application where the dead time is less than 1
second and synchrocheck is not required
• delayed auto reclosing is generally regarded as an application where the dead time is
greater than 1 second and where typically synchrocheck is required
• sequence is the auto reclosing cycle beginning with start and ending with successful,
unsuccessful or aborted reclosing as a result
• status is the state which the auto reclosing function have reached in the sequence

15.2.6.2 Status descriptions GUID-AFC069D6-ADA5-4D97-9699-8C9F058458EB v1

The auto reclosing function can be in one of the following five statuses:

“Inactive” GUID-BF80C969-FCBE-4CAB-BF71-9590A2DB433C v1
The auto recloser is in “inactive” status when the following conditions are fulfilled:

• the auto recloser is set to On and


• either the circuit breaker is not closed
• or the circuit breaker is not ready

The function will not react on any start from protection trips while in “inactive” status and
no automatic reclosing is possible.

“Ready” GUID-04F154EC-E236-40A4-A3E0-7624A2F6B132 v1
The function is in “ready” status when the following conditions are fulfilled:

• the circuit breaker is ready


• the circuit breaker must have been closed for more that the set time in setting:
tCBClosedMin
• the function is not in “blocked” status
• the function is not in “in progress” status

Only in “ready” status a start of the auto reclosing sequence is possible.

704 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

“In progress” GUID-24F8890F-A8FA-4A6F-B9E8-08BDB17B9A0D v1


The function is in “in progress” status when the following condition is fulfilled:

• the auto reclosing sequence is started

Start can be initiated by either protection trip command or circuit breaker position change.
The second starting alternative is only possible when enabled by a setting.

In “in progress” status the dead time starts and the status ceases when the dead time expires.
Then circuit breaker close command is given and the function changes its state into the
"reclaim time" status.

“Reclaim time” GUID-D838C380-C74B-498C-82D6-3364E2F6BA22 v1


The auto recloser is in “reclaim time” status while the following conditions are fulfilled:

• the reclaim time has not yet expired


• the status is not interrupted by either a new start signal or a block signal

A new start signal during “reclaim time” status forces the function to proceed to next shot and
change state into “in progress” status, as long as the last shot is not reached.

“Blocked” GUID-9C38B1BE-3772-49AE-B4B3-391CE15D5CD2 v1
The function is in “blocked” status when an external blocking signal exists. No auto reclosing is
possible in “blocked” status. Only an external signal for cancellation of the blocking can cancel
this status.

15.2.6.3 Description of the status transition GUID-C12DF571-AC0D-4A04-9B9E-D53E15A24331 v1

From Table 472 below it is possible to see which status transitions are possible. When the auto
recloser is for instance in “inactive” status only two transition are possible:

• transition to “ready” status when the circuit breaker is ready and closed
• transition to “blocked” status by external blocking

The empty cells in the table indicate that no such transition is possible.

Line distance protection REL670 705


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

Table 472: Status transition matrix


To → inactive ready in progress reclaim time blocked
From ↓ (dead time)
inactive activate activate BLKON
CBCLOSED and
CBREADY
ready deactivate activate START activate BLKON
CBCLOSED or or activate
CBREADY or STARTHS
activate INHIBIT
or RESET
in progress activate INHIBIT when activate BLKON
(dead time) or RESET CBCLOSED
issued
reclaim time activate RESET activate START activate BLKON
or INHIBIT and the last
shot has not
been reached
yet
blocked deactivate activate
CBCLOSED or BLKOFF and
CBREADY and CBCLOSED and
activate CBREADY
BLKOFF

15.2.6.4 Functional sequence description GUID-C73A160D-330B-4627-B8F0-A31C9B3F7417 v1

To comprehend this chapter better it is essential to first read chapters “Status


descriptions“ and “Description of the status transition” carefully.

The logic for most of the explained inputs, outputs, settings and internal signals, described in
this chapter, is shown in Figure 415. Other figures mentioned are in some way connected or
cooperate with Figure 415.

Before going into details in the following chapters, the short functional/feature summary is
given below.

The auto reclosing function is multi-shot capable and suitable for both high-speed and
delayed auto reclosing. The function can be set to perform a single-shot, two-shot, three-shot,
four-shot or five-shot reclosing sequence. Dead times for all shots can be set independently.

An auto recloser sequence can be initiated by:

• protection operation
• circuit breaker operation (when enabled by setting StartByCBOpen=On)

At the end of the dead time, provided that other conditions are fulfilled, a circuit breaker close
command signal is given. The other conditions to be fulfilled are:

• input signal SYNC is true, which typically indicates that power systems on the two sides of
the circuit breaker are in synchronism
• and that input signal CBREADY is true, typically indicating that circuit breaker springs are
charged.

If a circuit breaker close command is given successfully at the end of the dead time, a reclaim
time starts. If the circuit breaker does not trip again within reclaim time, the auto recloser
indicates a successful reclosing and resets into "ready" status. If the protection trips again
during the reclaim time, the sequence advances to the next shot. If all reclosing attempts have

706 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

been made and the circuit breaker does not remain closed, the auto recloser indicates an
unsuccessful reclosing. Each time a breaker close command is given, a shot counter is
incremented by one.

Operation Off and On GUID-D868C9CF-CDB1-48AA-8B31-60C447FBD1D3 v1


The auto recloser can be switched Off or On with a setting or by external control inputs. With
the setting Operation = On, the auto recloser is activated and with the setting Operation = Off
it is deactivated. With the settings Operation = On and ExternalCtrl = On, the activation and
deactivation is made by signal pulses to the ON and OFF inputs, for example, from a control
system or by a control switch.

If the input conditions CBCLOSED and CBREADY, from the circuit breaker, are not fulfilled
while switching the auto recloser on, the auto recloser changes into “inactive” status and the
output SETON is activated (high). The auto recloser is not ready for auto reclosing. If, however,
the circuit breaker is closed and ready when switching the auto recloser on, the output READY
is activated and the function is prepared to start the auto reclosing cycle. The circuit breaker
must have been closed for at least the set value for setting tCBClosedMin before a start is
accepted. The logic for Off or On operation is shown in Figure 410.

Operation
AND OR S SETON
ExternalCtrl

R
ON AND

OR
OFF AND

StartByCBOpen
START AND

STARTHS AND
100ms OR
AND OR initiate
100ms
AND
TRSOTF
startThermal AND
CBReady
120ms
CBREADY OR S
t AND start
AND
AND
tCBClosedMin R
CBCLOSED
t

cbClosed AND
count0 AND READY
inhibit
OR
INHIBIT

IEC16000153-1-en.vsdx
IEC16000153 V1 EN-US

Figure 410: Simplified logic for Operation Off/On and starting

Mode selection GUID-25A24DC8-80C8-4C42-A084-D25712049F06 v1


The auto reclosing mode is selected with the setting ARMode. As an alternative to the setting,
the mode can be selected by connecting an integer, for example from function block B16I, to
the MODEINT input. The six possible modes are described in Table 473 below with their
corresponding MODEINT integer value.

Line distance protection REL670 707


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

When a valid integer is connected to the input MODEINT the selected setting ARMode will be
invalid and the MODEINT input value will be used instead. The selected mode is reported as an
integer on the MODE output.

Please note that tripping mode of the IED is defined in Trip Logic function block SMPPTRC. For
example for two-phase faults either 2ph or 3ph tripping and consequent auto reclosing can be
selected

Table 473: Type of reclosing shots at different settings of “ARMode” or integer inputs to "MODEINT"
MODEINT (Integer) ARMode Type of fault 1st shot 2nd - 5th shot
1ph 3ph 3ph
1 3ph 2ph 3ph 3ph
3ph 3ph 3ph
1ph 1ph 3ph
2 1/2/3ph 2ph 2ph 3ph
3ph 3ph 3ph
1ph 1ph 3ph
3 1/2ph 2ph 2ph 3ph
3ph - -
1ph 1ph 3ph
4 1ph+1x2ph 2ph 2ph -
3ph - -
1ph 1ph 3ph
5 1/2ph+1x3ph 2ph 2ph 3ph
3ph 3ph –
1ph 1ph 3ph
6 1ph+1x2/3ph 2ph 2ph -
3ph 3ph -

Auto reclosing shots GUID-817797BE-FAFC-4BC7-B288-F19416459DCE v1


A maximum of five auto reclosing shots can be selected with the setting NoOfShots. Every
shot has its own dead time setting.

The first shot differs from the other shots by the possibility to extend its dead time and to
utilize up to four different time settings for it.

For the first shot, there are separate settings for single-, two- and three-phase dead times, t1
1Ph, t1 2Ph and t1 3Ph. If only the START input signal is applied, and an auto-reclosing program
with single-phase reclosing is selected, the auto reclosing dead time t1 1Ph will be used. If one
of the TR2P or TR3P inputs is activated in in parallel with the START input, the auto reclosing
dead time for either two-phase or three-phase auto reclosing is used.

There is also a separate time setting facility for three-phase high-speed auto reclosing, t1
3PhHS. This high-speed auto reclosing is activated by the STARTHS input and is used when
auto reclosing is done without the requirement of synchrocheck conditions to be fulfilled. The
high-speed dead time shall be set shorter than normal first shot three-phase dead time. Note
that if high-speed three-phase shot is not successful the auto reclosing sequence will continue
with shot two.

A time extension delay, tExtended t1, can be added to the dead time delay for the first shot. It
is intended to come into use if the communication channel for permissive line protection is
lost. In a case like this there can be a significant time difference in fault clearance at the two

708 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

line ends, where a longer auto reclosing dead time can be useful. This time extension is
controlled by the setting Extended t1 and the PLCLOST input. The logic for control of extended
dead time is shown in Figure411 and Figure 415. Time extension delay is not possible to add to
the three-phase high-speed auto reclosing dead time, t1 3PhHS.

Extended t1

AND extendTime
PLCLOST
OR
initiate AND
AND
start

IEC16000155-1-en.vsdx
IEC16000155 V1 EN-US

Figure 411: Control of extended dead time


Shots 2 to 5 are all three-phase shots and have only one corresponding time setting each, t2
3Ph, t3 3Ph, t4 3Ph and t5 3Ph.

Starting auto reclosing GUID-7794EA6E-7D73-46BD-A623-65DED8E45D05 v1


When a start is applied to the auto function, it status will change from “ready” status to “in
progress” status. When the dead time has expired, the close command is issued and the
reclaim time is started and the “in progress” status will change to “reclaim time” status.

The usual way to start a reclosing sequence, is to start it when a selective line protection
tripping has occurred, by applying a signal to the START input. If the auto reclosing mode with
only three-phase reclosing is selected, activation of the START input will start the three-phase
dead timer. When alternatively the START input signal is applied, and an auto reclosing mode
with single-phase reclosing is selected, the auto reclosing dead time for single-phase is used.
However if one of the TR2P or TR3P inputs is activated in connection with the START input, the
auto reclosing dead time for two-phase or three-phase auto reclosing is used. The STARTHS
input (start high-speed reclosing) can also be used to start a separate, high-speed three-phase
dead time in which case the synchrocheck condition will be bypassed.

To start a new auto reclosing cycle, a number of conditions of input signals need to be fulfilled.
The inputs are:

• CBREADY: circuit breaker is ready for a reclosing cycle, for example, charged operating
gear.
• CBCLOSED: to ensure that the circuit breaker was closed when the line fault occurred and
start was applied. The CBCLOSED condition must be present for more that the settable
time tCBClosedMin.
• no BLKON or INHIBIT signal is present.

When the start has been accepted, the internal signals “start” and “initiate” are set. The
internal signal “start” is latched and the internal signal “initiate” follows the length of the
signal on the START input. The latched signal “start” can be interrupted by a signal to the
INHIBIT input.

The simplified logic is shown in Figure 410.

The auto recloser is normally started by selective tripping. It is either a zone 1 or


communication aided trip, or a general trip. If the general trip is used the auto recloser must
be blocked, via the INHIBIT input, from all back-up tripping. The breaker failure function must
always be connected to inhibit the auto recloser. START makes a first shot with synchrocheck
conditions to be fulfilled, STARTHS makes its first shot without any fulfilled synchrocheck
conditions. The TRSOTF “trip by switch onto fault” input starts shots 2 to 5. It may be
connected to the “switch onto fault” output of line protection if multi-shot auto reclosing is
used.

Line distance protection REL670 709


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

In normal circumstances, the auto recloser is started with a protection trip command which
resets quickly due to fault clearing. In case the start signal lasts for a too long time, the user
can set a maximum start pulse duration tLongStartInh. This start pulse duration time is
controlled by setting LongStartInhib. When the start pulse duration signal is longer than the
set maximum start pulse duration, the auto reclosing sequence will be interrupted in the same
way as if the INHIBIT input was set to true. The logic for the control of long start pulse
duration is shown in Figure 412.

LongStartInhib

start
AND
tLongStartInh
initiate
t
longStartInhibit
OR

Extended t1 AND

t13PhExtTimeout

IEC16000154-1-en.vsdx
IEC16000154 V1 EN-US

Figure 412: Control of long start pulse duration


If the user wants to start the auto recloser from circuit breaker open position instead of the
protection trip signals, this starting mode is selected by enabling a setting StartByCBOpen.
Typically, a circuit breaker auxiliary contact of type normally open (NO) shall be connected to
the CBCLOSED and START inputs. Then the circuit breaker status change from closed to open
will generate an auto reclosing start pulse of limited length (100ms) subject to the usual auto
recloser checks. The auto reclosing sequence continues then as usual. Signals from manual
tripping and other functions, which shall prevent auto reclosing, need to be connected to the
INHIBIT input. The logic for start from circuit breaker open position is shown in Figure 410.

The function can also be set to proceed to the next reclosing shot (if selected) even if the
external start signal is not received but the breaker is still not closed. The user can set a
required time delay for the auto recloser to proceed without a new start with setting
tAutoContWait. Also the synchrocheck conditions not fulfilled will also make the auto recloser
to proceed to next shot. This automatic proceeding of shots is controlled by setting
AutoContinue and is shown in figure 413.

tAutoContWait
t
AND
commandCloseCB
AND S
R
OR
AND
OR
cbClosed AND autoInitiate
synchroCheckOK

AutoContinue

IEC16000156-1-en.vsdx
IEC16000156 V1 EN-US

Figure 413: Automatic proceeding of shots

Blocking, resetting and inhibiting auto reclosing GUID-82719FE0-02E4-48FB-9685-2146480F3653 v1


The BLKON input is used to block the auto recloser for example, when certain special service
conditions arise. The auto recloser can also be blocked by an unsuccessful reclosing attempt.

710 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

This is controlled by the setting BlockByUnsucCl. When the auto recloser is blocked it
immediately resets to its initial conditions and the ACTIVE output is unactivated. The
BLOCKED output indicates that the auto recloser is blocked. To unblock the auto recloser the
BLKOFF input must be activated.

The RESET input is used to reset the auto recloser to its initial conditions. When initial starting
conditions are fulfilled again, after a reset, the auto recloser is ready for a new reclosing
sequence.

If the INHIBIT input is activated it is reported on the INHIBOUT output. To ensure reliable
interruption and temporary blocking of the auto recloser a reset time delay tInhibit is used.
The auto recloser will be blocked the time set in tInhibit after the deactivation of the INHIBIT
input. The following internal inhibit signals are also affected by the setting tInhibit:

• inhibitWaitForMaster: after expiration of the tWaitForMaster time for the WAIT input to
reset, the reclosing cycle of the slave is inhibited.
• longStartInhibit: if start pulse duration is longer than the tLongStartInh time, the
reclosing cycle is inhibited.

The ABORTED output indicates that the auto recloser is inhibited while it was in one of
following internal states:

• inProgress: auto recloser is started and dead time is in progress.


• reclaimTimeStarted: the circuit breaker closing command has started the reclaim timer.
• wait: an auto recloser, acting as slave, is waiting for a release from the master to proceed
with its own reclosing sequence.

The SYNCFAIL output indicates that the auto recloser is inhibited because the synchrocheck or
energizing check condition has not been fulfilled within the set time interval, tSync. The
ABORTED output will also be activated.

The behavior of the functionality described above is described in Table 474 and Table 475
below.

Table 474: BLKON, BLKOFF, RESET, INHIBIT and SYNC behavior when the function is in "ready" status

Output → READY ACTIVE BLOCKED INHIBOUT ABORTED SYNCFAIL


Input ↓
None of below True False False False False False
inputs
activated
BLKON pulse False False True False False False
BLKOFF pulse True False False False False False
RESET pulse False False False False False False
INHIBIT pulse False False False True False False
SYNC True False False False False False

Table 475: BLKON, BLKOFF, RESET, INHIBIT and SYNC behavior when the function is in "in progress" status

Output → READY ACTIVE BLOCKED INHIBOUT ABORTED SYNCFAIL


Input ↓
None of below False True False False False False
inputs
activated
BLKON pulse False False True False False False
Table continues on next page

Line distance protection REL670 711


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

BLKOFF pulse True False False False False False


RESET pulse False False False False False False
INHIBIT pulse False False False True True False
No SYNC False False False False True True

Auto reclosing sequence GUID-78AAE7CD-702E-407B-94D2-6A70BAFC8E70 v1


When the function has started and the dead time has elapsed during the auto reclosing
sequence, certain conditions must be fulfilled before the circuit breaker closing command is
issued. In three-phase reclosing, a synchrocheck and/or energizing check can be used. It is
possible to use a synchrocheck function in the same physical device or an external one. The
synchrocheck release signal shall be connected to the auto reclosing SYNC input. If reclosing
without synchrocheck is preferred the SYNC input can be set to TRUE (set high) permanently.
The synchrocheck release signal is not checked for single-phase or two-phase auto reclosing.
When a three-phase high-speed reclosing started by STARTHS input, synchronization is not
checked either, and the state of the SYNC input is disregarded. The SYNC input shall be true
within a set time interval, tSync. If it is not, the auto reclosing is interrupted and the SYNCFAIL
and ABORTED outputs are activated.

By choosing CBReadyType = CO (circuit breaker ready for a Close-Open sequence) the


readiness of the circuit breaker is also checked before issuing the circuit breaker closing
command. If the circuit breaker has a readiness contact of type CBReadyType = OCO (circuit
breaker ready for an Open-Close-Open sequence) this condition may not be fulfilled during the
dead time and at the moment of auto reclosure. The Open-Close-Open condition was however
checked at the start of the auto reclosing cycle and it is then likely that the circuit breaker is
prepared for a Close-Open sequence.

The reclaim timer, tReclaim, is started each time a circuit breaker closing command is given. If
no start occurs within this time, the auto recloser will reset. A new start received in “reclaim
time” status will move the auto recloser to “in progress” status and next shot as long as the
final shot is not reached. The auto recloser will reset and enter “inactive” status if a new start
is given during the final reclaim time. This will also happen if the circuit breaker has not been
closed within set time interval tUnsucCl after each circuit breaker close command. The latter
case is controlled by setting UnsucClByCBChk. The auto reclosing sequence is considered
unsuccessful for both above cases and the UNSUCCL output is activated.

If the circuit breaker closing command is given and the circuit breaker is closed within the set
time interval tUnsucCl, the SUCCL output is activated after the set time interval tSuccessful.
The logic for successful and unsuccessful reclosing indication is shown in Figure 414.

712 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

initiate
reclaimTimeStarted AND

OR
AND UNSUCCL
OR tUnsucCl S
AND t unsuccessful
cbClosed
AND
UnsucClByCBChk
count0
OR R

tUnsucCl tSuccessful
AND SUCCL
commandCloseCB t AND S t

R
OR

IEC16000157-1-en.vsdx
IEC16000157 V1 EN-US

Figure 414: Successful/Unsuccessful


Figure 415 shows the logic for most parts of an auto reclosing sequence. Figure 415 should be
read together with the other logic diagrams to get the whole picture.

Line distance protection REL670 713


Technical manual
© Copyright 2017 ABB. All rights reserved
ZoneSeqCoord

714
ZONESTEP AND
Control

MODEINT MODE
Section 15

start ARMode
initiate inProgress

IEC16000158 V1 EN-US
TR2P and INPROGR
TR3P NoOfShots 1PT1
startThermal OR 2PT1
selection 3PT1
Dead time
reclaimTimeStarted 3PT2
tExtended t1 tExtended t1 is 3PT3
extendTime added to t1 1Ph inhibitThermalStart 3PT4
t
or t1 2ph or t1 3Ph 3PT5
SKIPHS Skips high-speed shot (t1 3PhHS) and PREP3P
continues with delayed shot (t1 3Ph) AND tReclaim PERMIT1P
AND t 1
t1 1Ph OR
t1 2Ph OR
Dead t1 3PhHS AND
t13PhExtTimeout
time inhibit
t1 3PH OR OR
settings t2 3PH synchroCheckOK
t3 3PH OR BlockByUnsucCl
t4 3PH AND
t5 3PH unsuccessful AND ACTIVE
1
t OR OR
AND S

Figure 415: Auto reclosing sequence


tSlaveDeadTime AND
slaveDeadTime sets every dead timer R
t BLOCKED

sequence. The outputs are:


to tSlaveDeadTime

tSync
SYNC AND t SYNCFAIL
inProgress AND
reclaimTimeStarted OR
CBReadyType wait AND ABORTED
CB OR
AND
readiness
AND inhibitWaitForMaster tInhibit
CBReady check t
OR
longStartInhibit count0
OR Counter COUNT1P
inhibitThermalStart COUNT2P
CutPulse inProgress COUNT3P1
AND Set COUNT3P2
OR COUNT3P3
OR COUNT3P4
AND
AND COUNT3P5
Reset COUNTAR

© Copyright 2017 ABB. All rights reserved


tPulse
Follow CB CLOSECB
OR
AND AND
cbClosed
50ms commandCloseCB

RSTCOUNT
RESET

BLKON
BLKOFF
INHIBIT INHIBOUT

IEC16000158-1-en.vsdx

A number of outputs from the function keeps track of the actual state in the auto reclosing

Technical manual
Line distance protection REL670
1MRK 506 370-UEN J
1MRK 506 370-UEN J Section 15
Control

• INPROGR: any dead time is in progress


• 1PT1, 2PT1, 3PT1, 3PT2, 3PT3, 3PT4 and 3PT5: dead time is in progress for respective shot
and fault type
• ACTIVE: during dead time + reclaim time
• COUNTAR: total number of auto reclosing shots
• COUNT1P, COUNT2P, COUNT3P1, COUNT3P2, COUNT3P3, COUNT3P4 and COUNT3P5:
number of circuit breaker close commands made for respective shot
• STATUS: reports, only through the IEC 61850 protocol, the actual status of the function.

The possible statuses are described in Table 476 below. Their mapping to output signals and
their corresponding IEC 61850 integer value is also given in the table. Mapping from
IEC 61850 Ed2 standard is also shown for the AutoRecSt data object.

Table 476: Auto reclosing status reported by IEC 61850 in priority order
Data object AutoRecSt Description for mapped Mapped output signals / Description in IEC61850
value signals Comments Ed2
1 Ready READY Ready
2 In Progress INPROGR In Progress
3 Successful SUCCL Successful
4 Waiting for trip
5 Trip issued by protection
6 Fault disappeared
7 Wait to complete CLOSECB Wait to complete
8 Circuit breaker closed
9 Cycle unsuccessful UNSUCCL
10
-1 Aborted by synchrocheck SYNCFAIL
fail
11 Aborted ABORTED Aborted
-2 Set On, Not Ready SETON = 1, READY = 0,
ACTIVE = 0, SUCCL = 0,
UNSUCC = 0, INPROG = 0
-3 Set Off, Not Ready SETON = 0
-99 Others Means that auto recloser
is in transitional state,
that should not be visible
in steady state situation

There are several counters within the function. One for each shot and type of fault and one
overall counter for total number of circuit breaker closing commands. All counters can be reset
to zero using either the HMI command or the RSTCOUNT input or by an IEC 61850 command.

The circuit breaker closing command, CLOSECB output is a pulse with settable duration by
setting tPulse. For circuit breakers without anti-pumping function, close pulse cutting can be
used. This is controlled by the setting CutPulse. In case of a new auto recloser start pulse, the
breaker closing command pulse is cut (interrupted). The minimum duration of the closing
pulse is always 50ms.

The prepare three-phase trip, PREP3P output is usually connected to the trip function
SMPPTRC to force the coming trip to be three-phase. If the auto recloser cannot make a single-
phase or two-phase reclosing, the start from the trip function should be three-phase.

Line distance protection REL670 715


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

The permit single-phase trip, PERMIT1P output is the inverse of the PREP3P output. It can be
connected to a binary output relay for connection to external protection or trip relays. In case
of a total loss of auxiliary power, the output relay drops and does not allow single-phase trip.

The setting Follow CB can be used to prevent close command to be issued when dead time has
expired and circuit breaker is already closed (e.g. by manual close command). If a new start is
received after the dead time expiration the auto recloser will advance to next shot.

If input SKIPHS is activated, and simultaneously STARTHS input is initiated then actually
normal three-phase shot one with dead time "t1 3Ph" will be started.

The ZONESTEP input is used when coordination between local auto reclosers and down
stream auto reclosers is needed. If function is in "ready" status and this input is activated the
auto recloser increases its actual shot number by one and enters directly the “reclaim time”
status for shot one. If a start is received during the reclaim time, the function will proceed with
the next shot (e.g. starting dead time for shot two). Every new pulse on the ZONESTEP input
will further increase the shot number. Note that ZONESTEP input will have such effect only if
local start signal was not activated, as shown in Figure 415. The setting NoOfShots limits of
course the maximum number of available shots. This functionality is controlled by the setting
ZoneSeqCoord.

By activating the THOLHOLD input the auto recloser is set on hold. It can be connected to a
thermal overload protection trip signal which resets only when the thermal content has fallen
to an acceptable level, for example, 70%. As long as the signal is high, indicating that the line is
hot, the auto reclosing is halted. When the signal resets, a reclosing cycle will continue. This
may cause a considerable delay between start of the auto recloser and the breaker closing
command. An external logic limiting this time and activating the INHIBIT input can be used.
The THOLHOLD input can also be used to set the auto recloser on hold, for longer or shorter
time periods, for other purposes if for some reason the auto recloser needs to be halted. The
logic for thermal protection hold is shown in Figure 416.

start inhibitThermalStart
THOLHOLD AND AND S

q-1 20ms
startThermal
AND

inhibit OR

IEC16000159-1-en.vsdx
IEC16000159 V1 EN-US

Figure 416: Thermal protection hold


The auto recloser is set as master or slave in multi-breaker arrangements with sequential
reclosing with the setting Priority. The auto recloser for the first circuit breaker, e.g. near the
busbar, is set as master (when Priority=High) and the auto recloser for the second circuit
breaker is set as slave (when Priority=Low). While the master is in progress, it issues the
WFMASTER output. After an unsuccessful reclosing the WFMASTER output is also maintained
by the UNSUCCL output.

When activating the WAIT input, in the auto recloser set as slave, every dead timer is changed
to the value of setting tSlaveDeadTime and holds back the auto reclosing operation. When the
WAIT input is reset at the time of a successful reclosing of the first circuit breaker, the slave is
released to continue the reclosing sequence after the set tSlaveDeadTime. The reason for
shortening the time, for the normal dead timers with the value of tSlaveDeadTime, is to give
the slave permission to react almost immediately when the WAIT input resets. The mimimum
settable time for tSlaveDeadTime is 0.1sec because both master and slave should not send the
breaker closing command at the same time. The slave should take the duration of the breaker
closing time of the master into consideration before sending the breaker closing command. A
setting tWaitForMaster sets a maximum wait time for the WAIT input to reset. If the wait time

716 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

expires, the reclosing cycle of the slave is inhibited. The maximum wait time, tWaitForMaster
for the second circuit breaker is set longer than the auto reclosing dead time plus a margin for
synchrocheck conditions to be fulfilled for the first circuit breaker. Typical setting is 2sec. In
single circuit breaker applications, the setting Priority is set to None. The logic for master-
slave is shown in Figure 417.

Master:
High (Master)
Priority
WFMASTER
inProgress AND

unsuccessful OR

Slave:
Low (Slave)
Priority
inhibitWaitForMaster
AND
start tWaitForMaster
AND t
WAIT
wait

AND slaveDeadTime
AND S
inhibit
commandCloseCB R
OR
reclaimTimeStarted

IEC16000160-1-en.vsdx
IEC16000160 V1 EN-US

Figure 417: Master-Slave


If reclosing of the first circuit breaker is unsuccessful, the UNSUCCL output connected to the
INHIBIT input of the slave unit interrupts the reclosing sequence of the latter. The signals can
be cross-connected to allow simple changing of the priority by just setting the High and the
Low priorities without changing the configuration. The CBCLOSED inputs from each circuit
breaker are important in multi-breaker arrangements to ensure that the circuit breaker was
closed at the beginning of the sequence. If the High priority breaker was not closed its auto
reclosing sequence will not start and the low priority breaker will just continue its auto
reclosing sequence in accordance with its normal settings.

15.2.6.5 Time sequence diagrams M12458-10 v5

Some examples of the timing of internal and external signals at typical transient and
permanent faults are shown below in Figure 418 to 421.

Line distance protection REL670 717


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

Fault
CBCLOSED
Closed Open Closed
CBREADY

START
SYNC
tReclaim
READY

INPROGR

1PT1

ACTIVE

CLOSECB t1 1Ph tPulse

PREP3P

SUCCL

Time

IEC04000196-4-en.vsd

IEC04000196 V4 EN-US

Figure 418: Transient single-phase fault, single-phase reclosing

Fault
CBCLOSED Open
Closed Open C C
CBREADY

START

TR3P
SYNC

READY

INPROGR

3PT1 t1 3Ph

3PT2 t2 3Ph

ACTIVE tReclaim

CLOSECB tPulse tPulse

PREP3P

UNSUCCL
Time

IEC04000197-3-en.vsd

IEC04000197 V3 EN-US

Figure 419: Permanent fault, three-phase trip, two-shot reclosing

718 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

Fault
CBCLOSED
CBREADY

START

TR3P

SYNC

READY

INPROGR

1PT1

3PT1

3PT2
CLOSECB t1 1Ph

PREP3P

UNSUCCL tReclaim
IEC04000198-3-en.vsd
IEC04000198 V3 EN-US

Figure 420: Permanent single-phase fault, single-phase trip, single-shot reclosing,


ARMode=1/2/3ph

Fault
CBCLOSED
CBREADY

START

TR3P

SYNC

READY

INPROGR

1PT1

3PT1

3PT2
t2 3Ph
CLOSECB t1 1Ph

PREP3P

UNSUCCL tReclaim

IEC04000199-3-en.vsd
IEC04000199 V3 EN-US

Figure 421: Permanent single-phase fault, single-phase trip, two-shot reclosing,


ARMode=1ph + 1*2ph

Line distance protection REL670 719


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

15.2.7 Technical data


M12379-1 v13

Table 477: SMBRREC technical data


Function Range or value Accuracy
Dead time:
shot 1 “t1 1Ph” (0.000-120.000) s ±0.2% or ±35 ms
shot 1 “t1 2Ph” whichever is greater
shot 1 “t1 3Ph “
shot 1 “t1 3PhHS”
Dead time: (0.00-6000.00) s ±0.2% or ±35 ms
shot 2 “t2 3Ph” whichever is greater
shot 3 “t3 3Ph”
shot 4 “t4 3Ph”
shot 5 “t5 3Ph”
Extend three-phase dead time duration “tExtended t1” (0.000-60.000) s ±0.2% or ±35 ms
whichever is greater
Minimum time that circuit breaker must be closed before (0.00-6000.00) s ±0.2% or ±35 ms
new sequence is allowed “tCBClosedMin” whichever is greater
Wait time for the slave to close when WAIT input has (0.100-60.000) s ±0.2% or ±35 ms
reset “tSlaveDeadTime” whichever is greater
Maximum allowed start pulse duration “tLongStartInh” (0.000-60.000) s ±0.2% or ±15 ms
whichever is greater
Circuit breaker closing pulse duration “tPulse” (0.000-60.000) s ±0.2% or ±15 ms
whichever is greater
Reclaim time ”tReclaim” (0.00-6000.00) s ±0.2% or ±15 ms
whichever is greater
Maximum wait time for release from master (0.00-6000.00) s ±0.2% or ±15 ms
“tWaitForMaster” whichever is greater
Reset time for reclosing inhibit “tInhibit” (0.000-60.000) s ±0.2% or ±45 ms
whichever is greater
Wait time after close command before proceeding to (0.000-60.000) s ±0.2% or ±45 ms
next shot “tAutoContWait” whichever is greater
Maximum wait time for fulfilled synchrocheck conditions (0.00-6000.00) s ±0.2% or ±45 ms
“tSync” whichever is greater
Delay time before indicating successful reclosing (0.000-60.000) s ±0.2% or ±50 ms
“tSuccessful” whichever is greater
Maximum wait time for circuit breaker closing before (0.00-6000.00) s ±0.2% or ±45 ms
indicating unsuccessful “tUnsucCl” whichever is greater

15.3 Interlocking IP15572-1 v2

15.3.1 Functionality M15106-3 v7

The interlocking functionality blocks the possibility to operate high-voltage switching devices,
for instance when a disconnector is under load, in order to prevent material damage and/or
accidental human injury.

Each control IED has interlocking functions for different switchyard arrangements, each
handling the interlocking of one bay. The interlocking functionality in each IED is not
dependent on any central function. For the station-wide interlocking, the IEDs communicate
via the station bus or by using hard wired binary inputs/outputs.

720 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

The interlocking conditions depend on the circuit configuration and status of the system at
any given time.

15.3.2 Operation principle M13528-4 v7

The interlocking function consists of software modules located in each control IED. The
function is distributed and not dependent on any central function. Communication between
modules in different bays is performed via the station bus.

The reservation function (see section "Functionality") is used to ensure that HV apparatuses
that might affect the interlock are blocked during the time gap, which arises between position
updates. This can be done by means of the communication system, reserving all HV
apparatuses that might influence the interlocking condition of the intended operation. The
reservation is maintained until the operation is performed.

After the selection and reservation of an apparatus, the function has complete data on the
status of all apparatuses in the switchyard that are affected by the selection. Other operators
cannot interfere with the reserved apparatus or the status of switching devices that may
affect it.

The open or closed positions of the HV apparatuses are inputs to software modules
distributed in the control IEDs. Each module contains the interlocking logic for a bay. The
interlocking logic in a module is different, depending on the bay function and the switchyard
arrangements, that is, double-breaker or 1 1/2 breaker bays have different modules. Specific
interlocking conditions and connections between standard interlocking modules are
performed with an engineering tool. Bay-level interlocking signals can include the following
kind of information:

• Positions of HV apparatuses (sometimes per phase)


• Valid positions (if evaluated in the control module)
• External release (to add special conditions for release)
• Line voltage (to block operation of line earthing switch)
• Output signals to release the HV apparatus

The interlocking module is connected to the surrounding functions within a bay as shown in
figure 422.

Apparatus control
Interlocking
modules
modules in
SCILO SCSWI
other bays SXSWI

Apparatus control
modules
Interlocking SCILO SCSWI SXCBR
module

Apparatus control
modules
en04000526.vsd SCILO SCSWI SXSWI

IEC04000526 V1 EN-US

Figure 422: Interlocking module on bay level


Bays communicate via the station bus and can convey information regarding the following:

Line distance protection REL670 721


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

• Unearthed busbars
• Busbars connected together
• Other bays connected to a busbar
• Received data from other bays is valid

Figure 423 illustrates the data exchange principle.

Station bus

Bay 1 Bay n Bus coupler

Disc QB1 and QB2 closed Disc QB1 and QB2 closed WA1 unearthed
WA1 unearthed
WA1 and WA2 interconn

...
WA1 not earthed WA1 not earthed
WA2 not earthed WA2 not earthed WA1 and WA2 interconn
WA1 and WA2 interconn WA1 and WA2 interconn in other bay

..
WA1

WA2
QB1 QB2 QB1 QB2 QB1 QB2 QC1 QC2

QA1 QA1 QA1

QB9 QB9

en05000494.vsd
IEC05000494 V1 EN-US

Figure 423: Data exchange between interlocking modules


When invalid data such as intermediate position, loss of a control IED, or input board error are
used as conditions for the interlocking condition in a bay, a release for execution of the
function will not be given.

On the local HMI an override function exists, which can be used to bypass the interlocking
function in cases where not all the data required for the condition is valid.

For all interlocking modules these general rules apply:

• The interlocking conditions for opening or closing of disconnectors and earthing switches
are always identical.
• Earthing switches on the line feeder end, for example, rapid earthing switches, are
normally interlocked only with reference to the conditions in the bay where they are
located, not with reference to switches on the other side of the line. So a line voltage
indication may be included into line interlocking modules. If there is no line voltage
supervision within the bay, then the appropriate inputs must be set to no voltage, and the
operator must consider this when operating.
• Earthing switches can only be operated on isolated sections for example, without load/
voltage. Circuit breaker contacts cannot be used to isolate a section, that is, the status of
the circuit breaker is irrelevant as far as the earthing switch operation is concerned.
• Disconnectors cannot break power current or connect different voltage systems.
Disconnectors in series with a circuit breaker can only be operated if the circuit breaker is
open, or if the disconnectors operate in parallel with other closed connections. Other
disconnectors can be operated if one side is completely isolated, or if the disconnectors
operate in parallel to other closed connections, or if they are earthed on both sides.
• Circuit breaker closing is only interlocked against running disconnectors in its bay or
additionally in a transformer bay against the disconnectors and earthing switch on the
other side of the transformer, if there is no disconnector between CB and transformer.
• Circuit breaker opening is only interlocked in a bus-coupler bay, if a bus bar transfer is in
progress.

722 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

To make the implementation of the interlocking function easier, a number of standardized and
tested software interlocking modules containing logic for the interlocking conditions are
available:

• Line for double and transfer busbars, ABC_LINE


• Bus for double and transfer busbars, ABC_BC
• Transformer bay for double busbars, AB_TRAFO
• Bus-section breaker for double busbars, A1A2_BS
• Bus-section disconnector for double busbars, A1A2_DC
• Busbar earthing switch, BB_ES
• Double CB Bay, DB_BUS_A, DB_LINE, DB_BUS_B
• 1 1/2-CB diameter, BH_LINE_A, BH_CONN, BH_LINE_B

The interlocking conditions can be altered, to meet the customer specific requirements, by
adding configurable logic by means of the graphical configuration tool PCM600. The inputs
Qx_EXy on the interlocking modules are used to add these specific conditions.

The input signals EXDU_xx shall be set to true if there is no transmission error at the transfer
of information from other bays. Required signals with designations ending in TR are intended
for transfer to other bays.

15.3.3 Logical node for interlocking SCILO IP14138-1 v2

15.3.3.1 Identification
GUID-3EC5D7F1-FDA0-4F0E-9391-08D357689E0C v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Logical node for interlocking SCILO - 3

15.3.3.2 Functionality M15048-3 v6

The Logical node for interlocking SCILO function is used to enable a switching operation if the
interlocking conditions permit. SCILO function itself does not provide any interlocking
functionality. The interlocking conditions are generated in separate function blocks containing
the interlocking logic.

15.3.3.3 Function block M15049-3 v6

SCILO
POSOPEN EN_OPEN
POSCLOSE EN_CLOSE
OPEN_EN
CLOSE_EN

IEC05000359-2-en.vsd
IEC05000359 V2 EN-US

Figure 424: SCILO function block

Line distance protection REL670 723


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

15.3.3.4 Signals
PID-3487-INPUTSIGNALS v7

Table 478: SCILO Input signals


Name Type Default Description
POSOPEN BOOLEAN 0 Open position of switch device
POSCLOSE BOOLEAN 0 Closed position of switch device
OPEN_EN BOOLEAN 0 Open operation from interlocking logic is enabled
CLOSE_EN BOOLEAN 0 Close operation from interlocking logic is enabled

PID-3487-OUTPUTSIGNALS v7

Table 479: SCILO Output signals


Name Type Description
EN_OPEN BOOLEAN Open operation at closed or interm. or bad pos. is enabled
EN_CLOSE BOOLEAN Close operation at open or interm. or bad pos. is enabled

15.3.3.5 Logic diagram M15086-3 v6

The function contains logic to enable the open and close commands respectively if the
interlocking conditions are fulfilled. That means also, if the switch has a defined end position
for example, open, then the appropriate enable signal (in this case EN_OPEN) is false. The
enable signals EN_OPEN and EN_CLOSE can be true at the same time only in the intermediate
and bad position state and if they are enabled by the interlocking function. The position inputs
come from the logical nodes Circuit breaker/Circuit switch (SXCBR/SXSWI) and the enable
signals come from the interlocking logic. The outputs are connected to the logical node Switch
controller (SCSWI). One instance per switching device is needed.

POSOPEN SCILO
POSCLOSE =1 1
EN_OPEN
&
>1
&

OPEN_EN
CLOSE_EN & EN_CLOSE
>1
&
en04000525.vsd

IEC04000525 V1 EN-US

Figure 425: SCILO function logic diagram

15.3.4 Interlocking for busbar earthing switch BB_ES IP14164-1 v4

15.3.4.1 Identification
GUID-F3CBAFDC-3723-429F-9183-45229A6F0A12 v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Interlocking for busbar earthing BB_ES - 3
switch

724 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

15.3.4.2 Functionality M15015-3 v7

The interlocking for busbar earthing switch (BB_ES) function is used for one busbar earthing
switch on any busbar parts according to figure 426.

QC

en04000504.vsd
IEC04000504 V1 EN-US

Figure 426: Switchyard layout BB_ES

15.3.4.3 Function block M15069-3 v6

BB_ES
QC_OP QCREL
QC_CL QCITL
BB_DC_OP BBESOPTR
VP_BB_DC BBESCLTR
EXDU_BB

IEC05000347-2-en.vsd
IEC05000347 V2 EN-US

Figure 427: BB_ES function block

15.3.4.4 Logic diagram M15103-3 v4

BB_ES
VP_BB_DC QCREL
BB_DC_OP QCITL
EXDU_BB & 1

QC_OP BBESOPTR
QC_CL BBESCLTR
en04000546.vsd

IEC04000546 V1 EN-US

15.3.4.5 Signals
PID-3494-INPUTSIGNALS v10

Table 480: BB_ES Input signals


Name Type Default Description
QC_OP BOOLEAN 0 Busbar earthing switch QC is in open position
QC_CL BOOLEAN 0 Busbar earthing switch QC is in closed position
BB_DC_OP BOOLEAN 0 All disconnectors on this busbar part are open
VP_BB_DC BOOLEAN 0 Status for all disconnectors on this busbar part are valid
EXDU_BB BOOLEAN 0 No transm error from bays with disc on this busbar part

Line distance protection REL670 725


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

PID-3494-OUTPUTSIGNALS v10

Table 481: BB_ES Output signals


Name Type Description
QCREL BOOLEAN Switching of QC is allowed
QCITL BOOLEAN Switching of QC is forbidden
BBESOPTR BOOLEAN QC on this busbar part is in open position
BBESCLTR BOOLEAN QC on this busbar part is in closed position

15.3.5 Interlocking for bus-section breaker A1A2_BS IP14154-1 v2

15.3.5.1 Identification
GUID-29EF1F25-E10A-4C82-A6B7-FA246D9C6CD2 v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Interlocking for bus-section breaker A1A2_BS - 3

15.3.5.2 Functionality M15110-3 v7

The interlocking for bus-section breaker (A1A2_BS) function is used for one bus-section circuit
breaker between section 1 and 2 according to figure 428. The function can be used for
different busbars, which includes a bus-section circuit breaker.

WA1 (A1) WA2 (A2)

QC1 QB1 QB2 QC2

QA1

QC3 QC4

en04000516.vsd
A1A2_BS
IEC04000516 V1 EN-US

Figure 428: Switchyard layout A1A2_BS

726 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

15.3.5.3 Function block M13535-3 v6

A1A2_BS
QA1_OP QA1OPREL
QA1_CL QA1OPITL
QB1_OP QA1CLREL
QB1_CL QA1CLITL
QB2_OP QB1REL
QB2_CL QB1ITL
QC3_OP QB2REL
QC3_CL QB2ITL
QC4_OP QC3REL
QC4_CL QC3ITL
S1QC1_OP QC4REL
S1QC1_CL QC4ITL
S2QC2_OP S1S2OPTR
S2QC2_CL S1S2CLTR
BBTR_OP QB1OPTR
VP_BBTR QB1CLTR
EXDU_12 QB2OPTR
EXDU_ES QB2CLTR
QA1O_EX1 VPS1S2TR
QA1O_EX2 VPQB1TR
QA1O_EX3 VPQB2TR
QB1_EX1
QB1_EX2
QB2_EX1
QB2_EX2

IEC05000348-2-en.vsd
IEC05000348 V2 EN-US

Figure 429: A1A2_BS function block

15.3.5.4 Logic diagram M15098-3 v4

A1A2_BS
QA1_OP
QA1_CL =1 VPQA1
QB1_OP
QB1_CL =1 VPQB1
QB2_OP
QB2_CL =1 VPQB2
QC3_OP
QC3_CL =1 VPQC3
QC4_OP
QC4_CL =1 VPQC4
S1QC1_OP
S1QC1_CL =1 VPS1QC1
S2QC2_OP
S2QC2_CL =1 VPS2QC2
VPQB1
QB1_OP QA1OPREL
& >1
QA1O_EX1 QA1OPITL
1
VPQB2
QB2_OP
&
QA1O_EX2
VP_BBTR
BBTR_OP
&
EXDU_12
QA1O_EX3

VPQB1 QA1CLREL
VPQB2 & QA1CLITL
1
VPQA1
VPQC3 QB1REL
& >1
VPQC4 QB1ITL
1
VPS1QC1
QA1_OP
QC3_OP
QC4_OP
S1QC1_OP
EXDU_ES
QB1_EX1

VPQC3
VPS1QC1
&
QC3_CL
S1QC1_CL
EXDU_ES
QB1_EX2

en04000542.vsd

IEC04000542 V1 EN-US

Line distance protection REL670 727


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

VPQA1
VPQC3 QB2REL
VPQC4 & >1
QB2ITL
VPS2QC2 1
QA1_OP
QC3_OP
QC4_OP
S2QC2_OP
EXDU_ES
QB2_EX1
VPQC4
VPS2QC2
&
QC4_CL
S2QC2_CL
EXDU_ES
QB2_EX2

VPQB1 QC3REL
VPQB2 QC3ITL
QB1_OP & 1
QC4REL
QB2_OP
QC4ITL
1

QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR

QB2_OP QB2OPTR
QB2_CL QB2CLTR
VPQB2 VPQB2TR
QB1_OP S1S2OPTR
QB2_OP >1 S1S2CLTR
QA1_OP 1
VPQB1
VPS1S2TR
VPQB2 &
VPQA1
en04000543.vsd

IEC04000543 V1 EN-US

15.3.5.5 Signals
PID-3498-INPUTSIGNALS v9

Table 482: A1A2_BS Input signals


Name Type Default Description
QA1_OP BOOLEAN 0 QA1 is in open position
QA1_CL BOOLEAN 0 QA1 is in closed position
QB1_OP BOOLEAN 0 QB1 is in open position
QB1_CL BOOLEAN 0 QB1 is in closed position
QB2_OP BOOLEAN 0 QB2 is in open position
QB2_CL BOOLEAN 0 QB2 is in closed position
QC3_OP BOOLEAN 0 QC3 is in open position
QC3_CL BOOLEAN 0 QC3 is in closed position
QC4_OP BOOLEAN 0 QC4 is in open position
QC4_CL BOOLEAN 0 QC4 is in closed position
S1QC1_OP BOOLEAN 0 QC1 on bus section 1 is in open position
S1QC1_CL BOOLEAN 0 QC1 on bus section 1 is in closed position
S2QC2_OP BOOLEAN 0 QC2 on bus section 2 is in open position
S2QC2_CL BOOLEAN 0 QC2 on bus section 2 is in closed position
BBTR_OP BOOLEAN 0 No busbar transfer is in progress
VP_BBTR BOOLEAN 0 Status are valid for app. involved in the busbar transfer
EXDU_12 BOOLEAN 0 No transm error from any bay connected to busbar 1 and 2
EXDU_ES BOOLEAN 0 No transm error from bays containing earth. sw. QC1 or QC2
QA1O_EX1 BOOLEAN 0 External open condition for apparatus QA1
QA1O_EX2 BOOLEAN 0 External open condition for apparatus QA1
Table continues on next page

728 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

Name Type Default Description


QA1O_EX3 BOOLEAN 0 External open condition for apparatus QA1
QB1_EX1 BOOLEAN 0 External condition for apparatus QB1
QB1_EX2 BOOLEAN 0 External condition for apparatus QB1
QB2_EX1 BOOLEAN 0 External condition for apparatus QB2
QB2_EX2 BOOLEAN 0 External condition for apparatus QB2

PID-3498-OUTPUTSIGNALS v9

Table 483: A1A2_BS Output signals


Name Type Description
QA1OPREL BOOLEAN Opening of QA1 is allowed
QA1OPITL BOOLEAN Opening of QA1 is forbidden
QA1CLREL BOOLEAN Closing of QA1 is allowed
QA1CLITL BOOLEAN Closing of QA1 is forbidden
QB1REL BOOLEAN Switching of QB1 is allowed
QB1ITL BOOLEAN Switching of QB1 is forbidden
QB2REL BOOLEAN Switching of QB2 is allowed
QB2ITL BOOLEAN Switching of QB2 is forbidden
QC3REL BOOLEAN Switching of QC3 is allowed
QC3ITL BOOLEAN Switching of QC3 is forbidden
QC4REL BOOLEAN Switching of QC4 is allowed
QC4ITL BOOLEAN Switching of QC4 is forbidden
S1S2OPTR BOOLEAN No bus section connection between bus section 1 and 2
S1S2CLTR BOOLEAN Bus coupler connection between bus section 1 and 2 exists
QB1OPTR BOOLEAN QB1 is in open position
QB1CLTR BOOLEAN QB1 is in closed position
QB2OPTR BOOLEAN QB2 is in open position
QB2CLTR BOOLEAN QB2 is in closed position
VPS1S2TR BOOLEAN Status of the app. between bus section 1 and 2 are valid
VPQB1TR BOOLEAN Switch status of QB1 is valid (open or closed)
VPQB2TR BOOLEAN Switch status of QB2 is valid (open or closed)

15.3.6 Interlocking for bus-section disconnector A1A2_DC IP14159-1 v2

15.3.6.1 Identification
GUID-0A0229EB-5ECD-405C-B706-6A54CBBDB49D v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Interlocking for bus-section A1A2_DC - 3
disconnector

Line distance protection REL670 729


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

15.3.6.2 Functionality M13544-3 v7

The interlocking for bus-section disconnector (A1A2_DC) function is used for one bus-section
disconnector between section 1 and 2 according to figure 430. A1A2_DC function can be used
for different busbars, which includes a bus-section disconnector.

QB
WA1 (A1) WA2 (A2)

QC1 QC2

A1A2_DC en04000492.vsd

IEC04000492 V1 EN-US

Figure 430: Switchyard layout A1A2_DC

15.3.6.3 Function block M13541-3 v6

A1A2_DC
QB_OP QBOPREL
QB_CL QBOPITL
S1QC1_OP QBCLREL
S1QC1_CL QBCLITL
S2QC2_OP DCOPTR
S2QC2_CL DCCLTR
S1DC_OP VPDCTR
S2DC_OP
VPS1_DC
VPS2_DC
EXDU_ES
EXDU_BB
QBCL_EX1
QBCL_EX2
QBOP_EX1
QBOP_EX2
QBOP_EX3

IEC05000349-2-en.vsd
IEC05000349 V2 EN-US

Figure 431: A1A2_DC function block

730 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

15.3.6.4 Logic diagram M15099-3 v5

A1A2_DC
QB_OP
VPQB VPDCTR
QB_CL =1
DCOPTR
DCCLTR
S1QC1_OP
VPS1QC1
S1QC1_CL =1
S2QC2_OP
VPS2QC2
S2QC2_CL =1
VPS1QC1
VPS2QC2
VPS1_DC & >1 QBOPREL
S1QC1_OP QBOPITL
1
S2QC2_OP
S1DC_OP
EXDU_ES

EXDU_BB
QBOP_EX1

VPS1QC1
VPS2QC2
VPS2_DC &
S1QC1_OP
S2QC2_OP
S2DC_OP
EXDU_ES

EXDU_BB
QBOP_EX2

VPS1QC1
VPS2QC2
S1QC1_CL &
S2QC2_CL
EXDU_ES
QBOP_EX3

en04000544.vsd

IEC04000544 V1 EN-US

IEC04000545 V1 EN-US

15.3.6.5 Signals
PID-3499-INPUTSIGNALS v10

Table 484: A1A2_DC Input signals


Name Type Default Description
QB_OP BOOLEAN 0 QB is in open position
QB_CL BOOLEAN 0 QB is in closed position
S1QC1_OP BOOLEAN 0 QC1 on bus section 1 is in open position
S1QC1_CL BOOLEAN 0 QC1 on bus section 1 is in closed position
S2QC2_OP BOOLEAN 0 QC2 on bus section 2 is in open position
S2QC2_CL BOOLEAN 0 QC2 on bus section 2 is in closed position
S1DC_OP BOOLEAN 0 All disconnectors on bus section 1 are in open position
Table continues on next page

Line distance protection REL670 731


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

Name Type Default Description


S2DC_OP BOOLEAN 0 All disconnectors on bus section 2 are in open position
VPS1_DC BOOLEAN 0 Switch status of disconnectors on bus section 1 are valid
VPS2_DC BOOLEAN 0 Switch status of disconnectors on bus section 2 are valid
EXDU_ES BOOLEAN 0 No transm error from bays containing earth. sw. QC1 or QC2
EXDU_BB BOOLEAN 0 No transm error from bays with disc conn to section 1 and 2
QBCL_EX1 BOOLEAN 0 External close condition for section disconnector QB
QBCL_EX2 BOOLEAN 0 External close condition for section disconnector QB
QBOP_EX1 BOOLEAN 0 External open condition for section disconnector QB
QBOP_EX2 BOOLEAN 0 External open condition for section disconnector QB
QBOP_EX3 BOOLEAN 0 External open condition for section disconnector QB

PID-3499-OUTPUTSIGNALS v10

Table 485: A1A2_DC Output signals


Name Type Description
QBOPREL BOOLEAN Opening of QB is allowed
QBOPITL BOOLEAN Opening of QB is forbidden
QBCLREL BOOLEAN Closing of QB is allowed
QBCLITL BOOLEAN Closing of QB is forbidden
DCOPTR BOOLEAN The bus section disconnector is in open position
DCCLTR BOOLEAN The bus section disconnector is in closed position
VPDCTR BOOLEAN Switch status of QB is valid (open or closed)

15.3.7 Interlocking for bus-coupler bay ABC_BC IP14144-1 v2

15.3.7.1 Identification
GUID-8149EE0A-E2A4-431C-9D07-D1A0BD296743 v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Interlocking for bus-coupler bay ABC_BC - 3

15.3.7.2 Functionality M13555-3 v8

The interlocking for bus-coupler bay (ABC_BC) function is used for a bus-coupler bay
connected to a double busbar arrangement according to figure 432. The function can also be
used for a single busbar arrangement with transfer busbar or double busbar arrangement
without transfer busbar.

732 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

WA1 (A)
WA2 (B)
WA7 (C)
QB1 QB2 QB20 QB7
QC1

QA1

QC2

en04000514.vsd
IEC04000514 V1 EN-US

Figure 432: Switchyard layout ABC_BC

15.3.7.3 Function block M13552-3 v6

ABC_BC
QA1_OP QA1OPREL
QA1_CL QA1OPITL
QB1_OP QA1CLREL
QB1_CL QA1CLITL
QB2_OP QB1REL
QB2_CL QB1ITL
QB7_OP QB2REL
QB7_CL QB2ITL
QB20_OP QB7REL
QB20_CL QB7ITL
QC1_OP QB20REL
QC1_CL QB20ITL
QC2_OP QC1REL
QC2_CL QC1ITL
QC11_OP QC2REL
QC11_CL QC2ITL
QC21_OP QB1OPTR
QC21_CL QB1CLTR
QC71_OP QB220OTR
QC71_CL QB220CTR
BBTR_OP QB7OPTR
BC_12_CL QB7CLTR
VP_BBTR QB12OPTR
VP_BC_12 QB12CLTR
EXDU_ES BC12OPTR
EXDU_12 BC12CLTR
EXDU_BC BC17OPTR
QA1O_EX1 BC17CLTR
QA1O_EX2 BC27OPTR
QA1O_EX3 BC27CLTR
QB1_EX1 VPQB1TR
QB1_EX2 VQB220TR
QB1_EX3 VPQB7TR
QB2_EX1 VPQB12TR
QB2_EX2 VPBC12TR
QB2_EX3 VPBC17TR
QB20_EX1 VPBC27TR
QB20_EX2
QB7_EX1
QB7_EX2

IEC05000350-2-en.vsd
IEC05000350 V2 EN-US

Figure 433: ABC_BC function block

Line distance protection REL670 733


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

15.3.7.4 Logic diagram M15095-3 v4

ABC_BC
QA1_OP
QA1_CL =1 VPQA1
QB1_OP
QB1_CL =1 VPQB1
QB20_OP
QB20_CL =1 VPQB20
QB7_OP
QB7_CL =1 VPQB7
QB2_OP
QB2_CL =1 VPQB2
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QC11_OP
QC11_CL =1 VPQC11
QC21_OP
QC21_CL =1 VPQC21
QC71_OP
QC71_CL =1 VPQC71
VPQB1
QB1_OP QA1OPREL
& >1 QA1OPITL
QA1O_EX1 1
VPQB20
QB20_OP &
QA1O_EX2
VP_BBTR
BBTR_OP &
EXDU_12
QA1O_EX3
VPQB1 QA1CLREL
VPQB2 QA1CLITL
VPQB7 & 1
VPQB20
en04000533.vsd

IEC04000533 V1 EN-US

VPQA1
VPQB2 QB1REL
& >1
VPQC1 QB1ITL
VPQC2 1
VPQC11
QA1_OP
QB2_OP
QC1_OP
QC2_OP
QC11_OP
EXDU_ES
QB1_EX1
VPQB2
VP_BC_12
&
QB2_CL
BC_12_CL
EXDU_BC
QB1_EX2
VPQC1
VPQC11
&
QC1_CL
QC11_CL
EXDU_ES
QB1_EX3

en04000534.vsd

IEC04000534 V1 EN-US

734 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

VPQA1
VPQB1 QB2REL
& >1
VPQC1 QB2ITL
VPQC2 1
VPQC21
QA1_OP
QB1_OP
QC1_OP
QC2_OP
QC21_OP
EXDU_ES
QB2_EX1
VPQB1
VP_BC_12
&
QB1_CL
BC_12_CL
EXDU_BC
QB2_EX2
VPQC1
VPQC21
&
QC1_CL
QC21_CL
EXDU_ES
QB2_EX3

en04000535.vsd

IEC04000535 V1 EN-US

VPQA1
VPQB20 QB7REL
& >1
VPQC1 QB7ITL
VPQC2 1
VPQC71
QA1_OP
QB20_OP
QC1_OP
QC2_OP
QC71_OP
EXDU_ES
QB7_EX1
VPQC2
VPQC71
&
QC2_CL
QC71_CL
EXDU_ES
QB7_EX2
VPQA1
VPQB7 QB20REL
& >1
VPQC1 QB20ITL
VPQC2 1
VPQC21
QA1_OP
QB7_OP
QC1_OP
QC2_OP
QC21_OP
EXDU_ES
QB20_EX1
VPQC2
VPQC21
&
QC2_CL
QC21_CL
EXDU_ES
QB20_EX2

en04000536.vsd

IEC04000536 V1 EN-US

Line distance protection REL670 735


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

VPQB1 QC1REL
VPQB20 QC1ITL
& 1
VPQB7
QC2REL
VPQB2
QB1_OP QC2ITL
1
QB20_OP
QB7_OP
QB2_OP
QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
QB20_OP QB220OTR
QB2_OP & QB220CTR
VPQB20 1
VQB220TR
VPQB2 &
QB7_OP QB7OPTR
QB7_CL QB7CLTR
VPQB7 VPQB7TR
QB1_OP QB12OPTR
QB2_OP >1 QB12CLTR
VPQB1 1
VPQB12TR
VPQB2 &
QA1_OP BC12OPTR
QB1_OP >1 BC12CLTR
QB20_OP 1
VPQA1
VPBC12TR
VPQB1 &
VPQB20
QA1_OP BC17OPTR
QB1_OP >1 BC17CLTR
QB7_OP 1
VPQA1
VPBC17TR
VPQB1 &
VPQB7
QA1_OP BC27OPTR
QB2_OP >1 BC27CLTR
QB7_OP 1
VPQA1
VPBC27TR
VPQB2 &
VPQB7
en04000537.vsd

IEC04000537 V1 EN-US

15.3.7.5 Signals
PID-3500-INPUTSIGNALS v9

Table 486: ABC_BC Input signals


Name Type Default Description
QA1_OP BOOLEAN 0 QA1 is in open position
QA1_CL BOOLEAN 0 QA1 is in closed position
QB1_OP BOOLEAN 0 QB1 is in open position
QB1_CL BOOLEAN 0 QB1 is in closed position
QB2_OP BOOLEAN 0 QB2 is in open position
QB2_CL BOOLEAN 0 QB2 is in closed position
QB7_OP BOOLEAN 0 QB7 is in open position
QB7_CL BOOLEAN 0 QB7 is in closed position
QB20_OP BOOLEAN 0 QB20 is in open position
QB20_CL BOOLEAN 0 QB20 is in closed position
QC1_OP BOOLEAN 0 QC1 is in open position
QC1_CL BOOLEAN 0 QC1 is in closed position
QC2_OP BOOLEAN 0 QC2 is in open position
QC2_CL BOOLEAN 0 QC2 is in closed position
QC11_OP BOOLEAN 0 Earthing switch QC11 on busbar WA1 is in open position
QC11_CL BOOLEAN 0 Earthing switch QC11 on busbar WA1 is in closed position
QC21_OP BOOLEAN 0 Earthing switch QC21 on busbar WA2 is in open position
QC21_CL BOOLEAN 0 Earthing switch QC21 on busbar WA2 is in closed position
QC71_OP BOOLEAN 0 Earthing switch QC71 on busbar WA7 is in open position
Table continues on next page

736 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

Name Type Default Description


QC71_CL BOOLEAN 0 Earthing switch QC71 on busbar WA7 is in closed position
BBTR_OP BOOLEAN 0 No busbar transfer is in progress
BC_12_CL BOOLEAN 0 A bus coupler connection exists between busbar WA1 and
WA2
VP_BBTR BOOLEAN 0 Status are valid for app. involved in the busbar transfer
VP_BC_12 BOOLEAN 0 Status of the bus coupler app. between WA1 and WA2 are
valid
EXDU_ES BOOLEAN 0 No transm error from any bay containing earthing switches
EXDU_12 BOOLEAN 0 No transm error from any bay connected to WA1/WA2
busbars
EXDU_BC BOOLEAN 0 No transmission error from any other bus coupler bay
QA1O_EX1 BOOLEAN 0 External open condition for apparatus QA1
QA1O_EX2 BOOLEAN 0 External open condition for apparatus QA1
QA1O_EX3 BOOLEAN 0 External open condition for apparatus QA1
QB1_EX1 BOOLEAN 0 External condition for apparatus QB1
QB1_EX2 BOOLEAN 0 External condition for apparatus QB1
QB1_EX3 BOOLEAN 0 External condition for apparatus QB1
QB2_EX1 BOOLEAN 0 External condition for apparatus QB2
QB2_EX2 BOOLEAN 0 External condition for apparatus QB2
QB2_EX3 BOOLEAN 0 External condition for apparatus QB2
QB20_EX1 BOOLEAN 0 External condition for apparatus QB20
QB20_EX2 BOOLEAN 0 External condition for apparatus QB20
QB7_EX1 BOOLEAN 0 External condition for apparatus QB7
QB7_EX2 BOOLEAN 0 External condition for apparatus QB7

PID-3500-OUTPUTSIGNALS v9

Table 487: ABC_BC Output signals


Name Type Description
QA1OPREL BOOLEAN Opening of QA1 is allowed
QA1OPITL BOOLEAN Opening of QA1 is forbidden
QA1CLREL BOOLEAN Closing of QA1 is allowed
QA1CLITL BOOLEAN Closing of QA1 is forbidden
QB1REL BOOLEAN Switching of QB1 is allowed
QB1ITL BOOLEAN Switching of QB1 is forbidden
QB2REL BOOLEAN Switching of QB2 is allowed
QB2ITL BOOLEAN Switching of QB2 is forbidden
QB7REL BOOLEAN Switching of QB7 is allowed
QB7ITL BOOLEAN Switching of QB7 is forbidden
QB20REL BOOLEAN Switching of QB20 is allowed
QB20ITL BOOLEAN Switching of QB20 is forbidden
QC1REL BOOLEAN Switching of QC1 is allowed
QC1ITL BOOLEAN Switching of QC1 is forbidden
QC2REL BOOLEAN Switching of QC2 is allowed
Table continues on next page

Line distance protection REL670 737


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

Name Type Description


QC2ITL BOOLEAN Switching of QC2 is forbidden
QB1OPTR BOOLEAN QB1 is in open position
QB1CLTR BOOLEAN QB1 is in closed position
QB220OTR BOOLEAN QB2 and QB20 are in open position
QB220CTR BOOLEAN QB2 or QB20 or both are not in open position
QB7OPTR BOOLEAN QB7 is in open position
QB7CLTR BOOLEAN QB7 is in closed position
QB12OPTR BOOLEAN QB1 or QB2 or both are in open position
QB12CLTR BOOLEAN QB1 and QB2 are not in open position
BC12OPTR BOOLEAN No connection via the own bus coupler between WA1 and WA2
BC12CLTR BOOLEAN Conn. exists via the own bus coupler between WA1 and WA2
BC17OPTR BOOLEAN No connection via the own bus coupler between WA1 and WA7
BC17CLTR BOOLEAN Conn. exists via the own bus coupler between WA1 and WA7
BC27OPTR BOOLEAN No connection via the own bus coupler between WA2 and
WA7
BC27CLTR BOOLEAN Conn. exists via the own bus coupler between WA2 and WA7
VPQB1TR BOOLEAN Switch status of QB1 is valid (open or closed)
VQB220TR BOOLEAN Switch status of QB2 and QB20 are valid (open or closed)
VPQB7TR BOOLEAN Switch status of QB7 is valid (open or closed)
VPQB12TR BOOLEAN Switch status of QB1 and QB2 are valid (open or closed)
VPBC12TR BOOLEAN Status of the bus coupler app. between WA1 and WA2 are
valid
VPBC17TR BOOLEAN Status of the bus coupler app. between WA1 and WA7 are
valid
VPBC27TR BOOLEAN Status of the bus coupler app. between WA2 and WA7 are
valid

15.3.8 Interlocking for 1 1/2 CB BH IP14173-1 v3

15.3.8.1 Identification
GUID-03F1A3BB-4A1E-49E8-88C6-10B3876F64DA v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Interlocking for 1 1/2 breaker BH_CONN - 3
diameter
Interlocking for 1 1/2 breaker BH_LINE_A - 3
diameter
Interlocking for 1 1/2 breaker BH_LINE_B - 3
diameter

15.3.8.2 Functionality M13570-3 v6

The interlocking for 1 1/2 breaker diameter (BH_CONN, BH_LINE_A, BH_LINE_B) functions are
used for lines connected to a 1 1/2 breaker diameter according to figure 434.

738 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

WA1 (A)
WA2 (B)
QB1 QB2
QC1 QC1

QA1 QA1

QC2 QC2

QB6 QB6

QC3 QC3
BH_LINE_A BH_LINE_B

QB61 QA1 QB62

QB9 QB9
QC1 QC2
QC9 QC9

BH_CONN
en04000513.vsd

IEC04000513 V1 EN-US

Figure 434: Switchyard layout 1 1/2 breaker


M13570-7 v4
Three types of interlocking modules per diameter are defined. BH_LINE_A and BH_LINE_B are
the connections from a line to a busbar. BH_CONN is the connection between the two lines of
the diameter in the 1 1/2 breaker switchyard layout.

Line distance protection REL670 739


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

15.3.8.3 Function blocks IP14412-1 v1

M13574-3 v6

BH_LINE_A
QA1_OP QA1CLREL
QA1_CL QA1CLITL
QB6_OP QB6REL
QB6_CL QB6ITL
QB1_OP QB1REL
QB1_CL QB1ITL
QC1_OP QC1REL
QC1_CL QC1ITL
QC2_OP QC2REL
QC2_CL QC2ITL
QC3_OP QC3REL
QC3_CL QC3ITL
QB9_OP QB9REL
QB9_CL QB9ITL
QC9_OP QC9REL
QC9_CL QC9ITL
CQA1_OP QB1OPTR
CQA1_CL QB1CLTR
CQB61_OP VPQB1TR
CQB61_CL
CQC1_OP
CQC1_CL
CQC2_OP
CQC2_CL
QC11_OP
QC11_CL
VOLT_OFF
VOLT_ON
EXDU_ES
QB6_EX1
QB6_EX2
QB1_EX1
QB1_EX2
QB9_EX1
QB9_EX2
QB9_EX3
QB9_EX4
QB9_EX5
QB9_EX6
QB9_EX7

IEC05000352-2-en.vsd
IEC05000352 V2 EN-US

Figure 435: BH_LINE_A function block

740 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

M13578-3 v6

BH_LINE_B
QA1_OP QA1CLREL
QA1_CL QA1CLITL
QB6_OP QB6REL
QB6_CL QB6ITL
QB2_OP QB2REL
QB2_CL QB2ITL
QC1_OP QC1REL
QC1_CL QC1ITL
QC2_OP QC2REL
QC2_CL QC2ITL
QC3_OP QC3REL
QC3_CL QC3ITL
QB9_OP QB9REL
QB9_CL QB9ITL
QC9_OP QC9REL
QC9_CL QC9ITL
CQA1_OP QB2OPTR
CQA1_CL QB2CLTR
CQB62_OP VPQB2TR
CQB62_CL
CQC1_OP
CQC1_CL
CQC2_OP
CQC2_CL
QC21_OP
QC21_CL
VOLT_OFF
VOLT_ON
EXDU_ES
QB6_EX1
QB6_EX2
QB2_EX1
QB2_EX2
QB9_EX1
QB9_EX2
QB9_EX3
QB9_EX4
QB9_EX5
QB9_EX6
QB9_EX7

IEC05000353-2-en.vsd
IEC05000353 V2 EN-US

Figure 436: BH_LINE_B function block


M13582-3 v6

BH_CONN
QA1_OP QA1CLREL
QA1_CL QA1CLITL
QB61_OP QB61REL
QB61_CL QB61ITL
QB62_OP QB62REL
QB62_CL QB62ITL
QC1_OP QC1REL
QC1_CL QC1ITL
QC2_OP QC2REL
QC2_CL QC2ITL
1QC3_OP
1QC3_CL
2QC3_OP
2QC3_CL
QB61_EX1
QB61_EX2
QB62_EX1
QB62_EX2

IEC05000351-2-en.vsd
IEC05000351 V2 EN-US

Figure 437: BH_CONN function block

Line distance protection REL670 741


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

15.3.8.4 Logic diagrams IP14413-1 v1

M13577-1 v5

BH_CONN
QA1_OP
QA1_CL =1 VPQA1
QB61_OP
QB61_CL =1 VPQB61
QB62_OP
QB62_CL =1 VPQB62
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
1QC3_OP
1QC3_CL =1 VP1QC3
2QC3_OP
2QC3_CL =1 VP2QC3
VPQB61 QA1CLREL
VPQB62 & QA1CLITL
1
VPQA1
VPQC1 QB61REL
& >1
VPQC2 QB61ITL
1
VP1QC3
QA1_OP
QC1_OP
QC2_OP
1QC3_OP
QB61_EX1
VPQC1
VP1QC3
&
QC1_CL
1QC3_CL
QB61_EX2
VPQA1
VPQC1 QB62REL
& >1
VPQC2 QB62ITL
1
VP2QC3
QA1_OP
QC1_OP
QC2_OP
2QC3_OP
QB62_EX1
VPQC2
VP2QC3
&
QC2_CL
2QC3_CL
QB62_EX2
VPQB61 QC1REL
VPQB62 QC1ITL
& 1
QB61_OP QC2REL
QB62_OP QC2ITL
1
en04000560.vsd

IEC04000560 V1 EN-US

742 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

BH_LINE_A
QA1_OP
QA1_CL =1 VPQA1
QB1_OP
QB1_CL =1 VPQB1
QB6_OP
QB6_CL =1 VPQB6
QC9_OP
QC9_CL =1 VPQC9
QB9_OP
QB9_CL =1 VPQB9
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QC3_OP
QC3_CL =1 VPQC3
CQA1_OP
CQA1_CL =1 VPCQA1
CQC1_OP
CQC1_CL =1 VPCQC1
CQC2_OP
CQC2_CL =1 VPCQC2
CQB61_OP
CQB61_CL =1 VPCQB61
QC11_OP
QC11_CL =1 VPQC11
VOLT_OFF
VOLT_ON =1 VPVOLT
VPQB1 QA1CLREL
VPQB6 QA1CLITL
& 1
VPQB9
VPQA1
VPQC1 QB6REL
VPQC2 & >1
QB6ITL
1
VPQC3
QA1_OP
QC1_OP
QC2_OP
QC3_OP
QB6_EX1
VPQC2
VPQC3
&
QC2_CL
QC3_CL
QB6_EX2
en04000554.vsd

IEC04000554 V1 EN-US

VPQA1
VPQC1 QB1REL
VPQC2 & >1
QB1ITL
1
VPQC11
QA1_OP
QC1_OP
QC2_OP
QC11_OP
EXDU_ES
QB1_EX1

VPQC1
VPQC11
&
QC1_CL
QC11_CL
EXDU_ES
QB1_EX2

VPQB1 QC1REL
VPQB6 QC1ITL
QB1_OP & 1
QC2REL
QB6_OP QC2ITL
VPQB6 1
VPQB9 QC3REL
VPCQB61 &
QC3ITL
1
QB6_OP
QB9_OP
CQB61_OP
VPQA1 QB9REL
VPQB6 QB9ITL
VPQC9 & >1 1

VPQC1
VPQC2
VPQC3
VPCQA1
VPCQB61
VPCQC1
VPCQC2
QB9_EX1
QB6_OP
QB9_EX2
>1
QA1_OP
QC1_OP
QC2_OP &
QB9_EX3

en04000555.vsd

IEC04000555 V1 EN-US

Line distance protection REL670 743


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

CQB61_OP
QB9_EX4
>1 & >1
CQA1_OP
CQC1_OP
CQC2_OP &
QB9_EX5
QC9_OP
QC3_OP
QB9_EX6
VPQC9
VPQC3
&
QC9_CL
QC3_CL
QB9_EX7
VPQB9 QC9REL
VPVOLT QC9ITL
QB9_OP & 1

VOLT_OFF
QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
en04000556.vsd

IEC04000556 V1 EN-US

BH_LINE_B
QA1_OP
QA1_CL =1 VPQA1
QB2_OP
QB2_CL =1 VPQB2
QB6_OP
QB6_CL =1 VPQB6
QC9_OP
QC9_CL =1 VPQC9
QB9_OP
QB9_CL =1 VPQB9
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QC3_OP
QC3_CL =1 VPQC3
CQA1_OP
CQA1_CL =1 VPCQA1
CQC1_OP
CQC1_CL =1 VPCQC1
CQC2_OP
CQC2_CL =1 VPCQC2
CQB62_OP
CQB62_CL =1 VPCQB62
QC21_OP
QC21_CL =1 VPQC21
VOLT_OFF
VOLT_ON =1 VPVOLT
VPQB2 QA1CLREL
VPQB6 QA1CLITL
& 1
VPQB9
VPQA1
VPQC1 QB6REL
VPQC2 & >1
QB6ITL
1
VPQC3
QA1_OP
QC1_OP
QC2_OP
QC3_OP
QB6_EX1
VPQC2
VPQC3
&
QC2_CL
QC3_CL
QB6_EX2
en04000557.vsd

IEC04000557 V1 EN-US

744 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

VPQA1
VPQC1 QB2REL
VPQC2 & >1
QB2ITL
1
VPQC21
QA1_OP
QC1_OP
QC2_OP
QC21_OP
EXDU_ES
QB2_EX1

VPQC1
VPQC21
&
QC1_CL
QC21_CL
EXDU_ES
QB2_EX2

VPQB2 QC1REL
VPQB6 QC1ITL
QB2_OP & 1
QC2REL
QB6_OP QC2ITL
VPQB6 1
VPQB9 QC3REL
VPCQB62 &
QC3ITL
1
QB6_OP
QB9_OP
CQB62_OP
VPQA1 QB9REL
VPQB6 QB9ITL
VPQC9 & >1 1

VPQC1
VPQC2
VPQC3
VPCQA1
VPCQB62
VPCQC1
VPCQC2
QB9_EX1
QB6_OP
QB9_EX2
>1
QA1_OP
QC1_OP
QC2_OP &
QB9_EX3

en04000558.vsd

IEC04000558 V1 EN-US

CQB62_OP
QB9_EX4
>1 & >1
CQA1_OP
CQC1_OP
CQC2_OP &
QB9_EX5
QC9_OP
QC3_OP
QB9_EX6
VPQC9
VPQC3
&
QC9_CL
QC3_CL
QB9_EX7
VPQB9 QC9REL
VPVOLT QC9ITL
QB9_OP & 1

VOLT_OFF
QB2_OP QB2OPTR
QB2_CL QB2CLTR
VPQB2 VPQB2TR
en04000559.vsd

IEC04000559 V1 EN-US

15.3.8.5 Signals
PID-3593-INPUTSIGNALS v9

Table 488: BH_LINE_A Input signals


Name Type Default Description
QA1_OP BOOLEAN 0 QA1 is in open position
QA1_CL BOOLEAN 0 QA1 is in closed position
QB6_OP BOOLEAN 0 QB6 is in open position
QB6_CL BOOLEAN 0 QB6 is in close position
QB1_OP BOOLEAN 0 QB1 is in open position
Table continues on next page

Line distance protection REL670 745


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

Name Type Default Description


QB1_CL BOOLEAN 0 QB1 is in closed position
QC1_OP BOOLEAN 0 QC1 is in open position
QC1_CL BOOLEAN 0 QC1 is in closed position
QC2_OP BOOLEAN 0 QC2 is in open position
QC2_CL BOOLEAN 0 QC2 is in closed position
QC3_OP BOOLEAN 0 QC3 is in open position
QC3_CL BOOLEAN 0 QC3 is in closed position
QB9_OP BOOLEAN 0 QB9 is in open position
QB9_CL BOOLEAN 0 QB9 is in closed position
QC9_OP BOOLEAN 0 QC9 is in open position
QC9_CL BOOLEAN 0 QC9 is in closed position
CQA1_OP BOOLEAN 0 QA1 in module BH_CONN is in open position
CQA1_CL BOOLEAN 0 QA1 in module BH_CONN is in closed position
CQB61_OP BOOLEAN 0 QB61 in module BH_CONN is in open position
CQB61_CL BOOLEAN 0 QB61 in module BH_CONN is in closed position
CQC1_OP BOOLEAN 0 QC1 in module BH_CONN is in open position
CQC1_CL BOOLEAN 0 QC1 in module BH_CONN is in closed position
CQC2_OP BOOLEAN 0 QC2 in module BH_CONN is in open position
CQC2_CL BOOLEAN 0 QC2 in module BH_CONN is in closed position
QC11_OP BOOLEAN 0 Earthing switch QC11 on busbar WA1 is in open position
QC11_CL BOOLEAN 0 Earthing switch QC11 on busbar WA1 is in closed position
VOLT_OFF BOOLEAN 0 There is no voltage on line and not VT (fuse) failure
VOLT_ON BOOLEAN 0 There is voltage on the line or there is a VT (fuse) failure
EXDU_ES BOOLEAN 0 No transm error from bay containing earthing switch QC11
QB6_EX1 BOOLEAN 0 External condition for apparatus QB6
QB6_EX2 BOOLEAN 0 External condition for apparatus QB6
QB1_EX1 BOOLEAN 0 External condition for apparatus QB1
QB1_EX2 BOOLEAN 0 External condition for apparatus QB1
QB9_EX1 BOOLEAN 0 External condition for apparatus QB9
QB9_EX2 BOOLEAN 0 External condition for apparatus QB9
QB9_EX3 BOOLEAN 0 External condition for apparatus QB9
QB9_EX4 BOOLEAN 0 External condition for apparatus QB9
QB9_EX5 BOOLEAN 0 External condition for apparatus QB9
QB9_EX6 BOOLEAN 0 External condition for apparatus QB9
QB9_EX7 BOOLEAN 0 External condition for apparatus QB9

PID-3593-OUTPUTSIGNALS v9

Table 489: BH_LINE_A Output signals


Name Type Description
QA1CLREL BOOLEAN Closing of QA1 is allowed
QA1CLITL BOOLEAN Closing of QA1 is forbidden
QB6REL BOOLEAN Switching of QB6 is allowed
Table continues on next page

746 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

Name Type Description


QB6ITL BOOLEAN Switching of QB6 is forbidden
QB1REL BOOLEAN Switching of QB1 is allowed
QB1ITL BOOLEAN Switching of QB1 is forbidden
QC1REL BOOLEAN Switching of QC1 is allowed
QC1ITL BOOLEAN Switching of QC1 is forbidden
QC2REL BOOLEAN Switching of QC2 is allowed
QC2ITL BOOLEAN Switching of QC2 is forbidden
QC3REL BOOLEAN Switching of QC3 is allowed
QC3ITL BOOLEAN Switching of QC3 is forbidden
QB9REL BOOLEAN Switching of QB9 is allowed
QB9ITL BOOLEAN Switching of QB9 is forbidden
QC9REL BOOLEAN Switching of QC9 is allowed
QC9ITL BOOLEAN Switching of QC9 is forbidden
QB1OPTR BOOLEAN QB1 is in open position
QB1CLTR BOOLEAN QB1 is in closed position
VPQB1TR BOOLEAN Switch status of QB1 is valid (open or closed)

PID-3594-INPUTSIGNALS v9

Table 490: BH_LINE_B Input signals


Name Type Default Description
QA1_OP BOOLEAN 0 QA1 is in open position
QA1_CL BOOLEAN 0 QA1 is in closed position
QB6_OP BOOLEAN 0 QB6 is in open position
QB6_CL BOOLEAN 0 QB6 is in close position
QB2_OP BOOLEAN 0 QB2 is in open position
QB2_CL BOOLEAN 0 QB2 is in closed position
QC1_OP BOOLEAN 0 QC1 is in open position
QC1_CL BOOLEAN 0 QC1 is in closed position
QC2_OP BOOLEAN 0 QC2 is in open position
QC2_CL BOOLEAN 0 QC2 is in closed position
QC3_OP BOOLEAN 0 QC3 is in open position
QC3_CL BOOLEAN 0 QC3 is in closed position
QB9_OP BOOLEAN 0 QB9 is in open position
QB9_CL BOOLEAN 0 QB9 is in closed position
QC9_OP BOOLEAN 0 QC9 is in open position
QC9_CL BOOLEAN 0 QC9 is in closed position
CQA1_OP BOOLEAN 0 QA1 in module BH_CONN is in open position
CQA1_CL BOOLEAN 0 QA1 in module BH_CONN is in closed position
CQB62_OP BOOLEAN 0 QB62 in module BH_CONN is in open position
CQB62_CL BOOLEAN 0 QB62 in module BH_CONN is in closed position
CQC1_OP BOOLEAN 0 QC1 in module BH_CONN is in open position
CQC1_CL BOOLEAN 0 QC1 in module BH_CONN is in closed position
Table continues on next page

Line distance protection REL670 747


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

Name Type Default Description


CQC2_OP BOOLEAN 0 QC2 in module BH_CONN is in open position
CQC2_CL BOOLEAN 0 QC2 in module BH_CONN is in closed position
QC21_OP BOOLEAN 0 Earthing switch QC21 on busbar WA2 is in open position
QC21_CL BOOLEAN 0 Earthing switch QC21 on busbar WA2 is in closed position
VOLT_OFF BOOLEAN 0 There is no voltage on line and not VT (fuse) failure
VOLT_ON BOOLEAN 0 There is voltage on the line or there is a VT (fuse) failure
EXDU_ES BOOLEAN 0 No transm error from bay containing earthing switch QC21
QB6_EX1 BOOLEAN 0 External condition for apparatus QB6
QB6_EX2 BOOLEAN 0 External condition for apparatus QB6
QB2_EX1 BOOLEAN 0 External condition for apparatus QB2
QB2_EX2 BOOLEAN 0 External condition for apparatus QB2
QB9_EX1 BOOLEAN 0 External condition for apparatus QB9
QB9_EX2 BOOLEAN 0 External condition for apparatus QB9
QB9_EX3 BOOLEAN 0 External condition for apparatus QB9
QB9_EX4 BOOLEAN 0 External condition for apparatus QB9
QB9_EX5 BOOLEAN 0 External condition for apparatus QB9
QB9_EX6 BOOLEAN 0 External condition for apparatus QB9
QB9_EX7 BOOLEAN 0 External condition for apparatus QB9

PID-3594-OUTPUTSIGNALS v9

Table 491: BH_LINE_B Output signals


Name Type Description
QA1CLREL BOOLEAN Closing of QA1 is allowed
QA1CLITL BOOLEAN Closing of QA1 is forbidden
QB6REL BOOLEAN Switching of QB6 is allowed
QB6ITL BOOLEAN Switching of QB6 is forbidden
QB2REL BOOLEAN Switching of QB2 is allowed
QB2ITL BOOLEAN Switching of QB2 is forbidden
QC1REL BOOLEAN Switching of QC1 is allowed
QC1ITL BOOLEAN Switching of QC1 is forbidden
QC2REL BOOLEAN Switching of QC2 is allowed
QC2ITL BOOLEAN Switching of QC2 is forbidden
QC3REL BOOLEAN Switching of QC3 is allowed
QC3ITL BOOLEAN Switching of QC3 is forbidden
QB9REL BOOLEAN Switching of QB9 is allowed
QB9ITL BOOLEAN Switching of QB9 is forbidden
QC9REL BOOLEAN Switching of QC9 is allowed
QC9ITL BOOLEAN Switching of QC9 is forbidden
QB2OPTR BOOLEAN QB2 is in open position
QB2CLTR BOOLEAN QB2 is in closed position
VPQB2TR BOOLEAN Switch status of QB2 is valid (open or closed)

748 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

PID-3501-INPUTSIGNALS v9

Table 492: BH_CONN Input signals


Name Type Default Description
QA1_OP BOOLEAN 0 QA1 is in open position
QA1_CL BOOLEAN 0 QA1 is in closed position
QB61_OP BOOLEAN 0 QB61 is in open position
QB61_CL BOOLEAN 0 QB61 is in closed position
QB62_OP BOOLEAN 0 QB62 is in open position
QB62_CL BOOLEAN 0 QB62 is in closed position
QC1_OP BOOLEAN 0 QC1 is in open position
QC1_CL BOOLEAN 0 QC1 is in closed position
QC2_OP BOOLEAN 0 QC2 is in open position
QC2_CL BOOLEAN 0 QC2 is in closed position
1QC3_OP BOOLEAN 0 QC3 on line 1 is in open position
1QC3_CL BOOLEAN 0 QC3 on line 1 is in closed position
2QC3_OP BOOLEAN 0 QC3 on line 2 is in open position
2QC3_CL BOOLEAN 0 QC3 on line 2 is in closed position
QB61_EX1 BOOLEAN 0 External condition for apparatus QB61
QB61_EX2 BOOLEAN 0 External condition for apparatus QB61
QB62_EX1 BOOLEAN 0 External condition for apparatus QB62
QB62_EX2 BOOLEAN 0 External condition for apparatus QB62

PID-3501-OUTPUTSIGNALS v9

Table 493: BH_CONN Output signals


Name Type Description
QA1CLREL BOOLEAN Closing of QA1 is allowed
QA1CLITL BOOLEAN Closing of QA1 is forbidden
QB61REL BOOLEAN Switching of QB61 is allowed
QB61ITL BOOLEAN Switching of QB61 is forbidden
QB62REL BOOLEAN Switching of QB62 is allowed
QB62ITL BOOLEAN Switching of QB62 is forbidden
QC1REL BOOLEAN Switching of QC1 is allowed
QC1ITL BOOLEAN Switching of QC1 is forbidden
QC2REL BOOLEAN Switching of QC2 is allowed
QC2ITL BOOLEAN Switching of QC2 is forbidden

15.3.9 Interlocking for double CB bay DB IP14167-1 v2

Line distance protection REL670 749


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

15.3.9.1 Identification
GUID-D6D10255-2818-44E4-A44E-DF623161C486 v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Interlocking for double CB bay DB_BUS_A - 3
Interlocking for double CB bay DB_BUS_B - 3
Interlocking for double CB bay DB_LINE - 3

15.3.9.2 Functionality M13585-3 v10

The interlocking for a double busbar double circuit breaker bay including DB_BUS_A,
DB_BUS_B and DB_LINE functions are used for a line connected to a double busbar
arrangement according to figure 438.

WA1 (A)
WA2 (B)
QB1 QB2
QC1 QC4

QA1 QA2

DB_BUS_A DB_BUS_B
QC2 QC5

QB61 QB62

QC3

QB9
DB_LINE

QC9

en04000518.vsd
IEC04000518 V1 EN-US

Figure 438: Switchyard layout double circuit breaker

750 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

15.3.9.3 Logic diagrams IP14633-1 v1

M15105-1 v4

DB_BUS_A
QA1_OP
QA1_CL =1 VPQA1
QB61_OP
QB61_CL =1 VPQB61
QB1_OP
QB1_CL =1 VPQB1
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QC3_OP
QC3_CL =1 VPQC3
QC11_OP
QC11_CL =1 VPQC11
VPQB61 QA1CLREL
VPQB1 & QA1CLITL
1
VPQA1
VPQC1 QB61REL
& >1
VPQC2 QB61ITL
1
VPQC3
QA1_OP
QC1_OP
QC2_OP
QC3_OP
QB61_EX1
VPQC2
VPQC3
&
QC2_CL
QC3_CL
QB61_EX2
VPQA1
VPQC1 QB1REL
& >1
VPQC2 QB1ITL
1
VPQC11
QA1_OP
QC1_OP
QC2_OP
QC11_OP
EXDU_ES
QB1_EX1

VPQC1
VPQC11
&
QC1_CL
QC11_CL
EXDU_ES
QB1_EX2

en04000547.vsd

IEC04000547 V1 EN-US

VPQB61 QC1REL
VPQB1 QC1ITL
& 1
QB61_OP QC2REL
QB1_OP QC2ITL
1
QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
en04000548.vsd

IEC04000548 V1 EN-US

Line distance protection REL670 751


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

DB_BUS_B
QA2_OP
QA2_CL =1 VPQA2
QB62_OP
QB62_CL =1 VPQB62
QB2_OP
QB2_CL =1 VPQB2
QC4_OP
QC4_CL =1 VPQC4
QC5_OP
QC5_CL =1 VPQC5
QC3_OP
QC3_CL =1 VPQC3
QC21_OP
QC21_CL =1 VPQC21
VPQB62 QA2CLREL
VPQB2 & QA2CLITL
1
VPQA2
VPQC4 QB62REL
& >1
VPQC5 QB62ITL
1
VPQC3
QA2_OP
QC4_OP
QC5_OP
QC3_OP
QB62_EX1
VPQC5
VPQC3
&
QC5_CL
QC3_CL
QB62_EX2
VPQA2
VPQC4 QB2REL
& >1
VPQC5 QB2ITL
1
VPQC21
QA2_OP
QC4_OP
QC5_OP
QC21_OP
EXDU_ES
QB2_EX1

VPQC4
VPQC21
&
QC4_CL
QC21_CL
EXDU_ES
QB2_EX2

en04000552.vsd

IEC04000552 V1 EN-US

VPQB62 QC4REL
VPQB2 QC4ITL
& 1
QB62_OP QC5REL
QB2_OP QC5ITL
1
QB2_OP QB2OPTR
QB2_CL QB2CLTR
VPQB2 VPQB2TR
en04000553.vsd

IEC04000553 V1 EN-US

752 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

DB_LINE
QA1_OP
QA1_CL =1 VPQA1
QA2_OP
QA2_CL =1 VPQA2
QB61_OP
QB61_CL =1 VPQB61
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QB62_OP
QB62_CL =1 VPQB62
QC4_OP
QC4_CL =1 VPQC4
QC5_OP
QC5_CL =1 VPQC5
QB9_OP
QB9_CL =1 VPQB9
QC3_OP
QC3_CL =1 VPQC3
QC9_OP
QC9_CL =1 VPQC9
VOLT_OFF
VOLT_ON =1 VPVOLT
VPQA1
VPQA2 QB9REL
VPQC1 & >1
QB9ITL
1
VPQC2
VPQC3
VPQC4
VPQC5
VPQC9
QA1_OP
QA2_OP
QC1_OP
QC2_OP
QC3_OP
QC4_OP
QC5_OP
QC9_OP
QB9_EX1

& en04000549.vsd

IEC04000549 V1 EN-US

VPQA1
VPQC1
VPQC2 & >1
VPQC3
VPQC9
VPQB62
QA1_OP
QC1_OP
QC2_OP
QC3_OP
QC9_OP
QB62_OP
QB9_EX2
VPQA2
VPQB61
&
VPQC3
VPQC4
VPQC5
VPQC9
QA2_OP
QB61_OP
QC3_OP
QC4_OP
QC5_OP
QC9_OP
QB9_EX3
VPQC3
VPQC9
&
VPQB61
VPQB62
QC3_OP
QC9_OP
QB61_OP
QB62_OP
QB9_EX4
VPQC3
VPQC9
&
QC3_CL
QC9_CL
QB9_EX5
en04000550.vsd

IEC04000550 V1 EN-US

Line distance protection REL670 753


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

VPQB61
VPQB62 QC3REL
VPQB9 &
QC3ITL
1
QB61_OP
QB62_OP
QB9_OP
VPQB9
VPVOLT QC9REL
QB9_OP &
QC9ITL
1
VOLT_OFF
en04000551.vsd

IEC04000551 V1 EN-US

15.3.9.4 Function block IP14391-1 v1

M13591-3 v6

DB_BUS_A
QA1_OP QA1CLREL
QA1_CL QA1CLITL
QB1_OP QB61REL
QB1_CL QB61ITL
QB61_OP QB1REL
QB61_CL QB1ITL
QC1_OP QC1REL
QC1_CL QC1ITL
QC2_OP QC2REL
QC2_CL QC2ITL
QC3_OP QB1OPTR
QC3_CL QB1CLTR
QC11_OP VPQB1TR
QC11_CL
EXDU_ES
QB61_EX1
QB61_EX2
QB1_EX1
QB1_EX2

IEC05000354-2-en.vsd
IEC05000354 V2 EN-US

Figure 439: DB_BUS_A function block


M15107-3 v6

DB_LINE
QA1_OP QB9REL
QA1_CL QB9ITL
QA2_OP QC3REL
QA2_CL QC3ITL
QB61_OP QC9REL
QB61_CL QC9ITL
QC1_OP
QC1_CL
QC2_OP
QC2_CL
QB62_OP
QB62_CL
QC4_OP
QC4_CL
QC5_OP
QC5_CL
QB9_OP
QB9_CL
QC3_OP
QC3_CL
QC9_OP
QC9_CL
VOLT_OFF
VOLT_ON
QB9_EX1
QB9_EX2
QB9_EX3
QB9_EX4
QB9_EX5

IEC05000356-2-en.vsd
IEC05000356 V2 EN-US

Figure 440: DB_LINE function block

754 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

M13596-3 v6

DB_BUS_B
QA2_OP QA2CLREL
QA2_CL QA2CLITL
QB2_OP QB62REL
QB2_CL QB62ITL
QB62_OP QB2REL
QB62_CL QB2ITL
QC4_OP QC4REL
QC4_CL QC4ITL
QC5_OP QC5REL
QC5_CL QC5ITL
QC3_OP QB2OPTR
QC3_CL QB2CLTR
QC21_OP VPQB2TR
QC21_CL
EXDU_ES
QB62_EX1
QB62_EX2
QB2_EX1
QB2_EX2

IEC05000355-2-en.vsd
IEC05000355 V2 EN-US

Figure 441: DB_BUS_B function block

15.3.9.5 Signals
PID-3598-INPUTSIGNALS v9

Table 494: DB_BUS_A Input signals


Name Type Default Description
QA1_OP BOOLEAN 0 QA1 is in open position
QA1_CL BOOLEAN 0 QA1 is in closed position
QB1_OP BOOLEAN 0 QB1 is in open position
QB1_CL BOOLEAN 0 QB1 is in closed position
QB61_OP BOOLEAN 0 QB61 is in open position
QB61_CL BOOLEAN 0 QB61 is in closed position
QC1_OP BOOLEAN 0 QC1 is in open position
QC1_CL BOOLEAN 0 QC1 is in closed position
QC2_OP BOOLEAN 0 QC2 is in open position
QC2_CL BOOLEAN 0 QC2 is in closed position
QC3_OP BOOLEAN 0 QC3 is in open position
QC3_CL BOOLEAN 0 QC3 is in closed position
QC11_OP BOOLEAN 0 Earthing switch QC11 on busbar WA1 is in open position
QC11_CL BOOLEAN 0 Earthing switch QC11 on busbar WA1 is in closed position
EXDU_ES BOOLEAN 0 No transm error from bay containing earthing switch QC11
QB61_EX1 BOOLEAN 0 External condition for apparatus QB61
QB61_EX2 BOOLEAN 0 External condition for apparatus QB61
QB1_EX1 BOOLEAN 0 External condition for apparatus QB1
QB1_EX2 BOOLEAN 0 External condition for apparatus QB1

Line distance protection REL670 755


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

PID-3598-OUTPUTSIGNALS v9

Table 495: DB_BUS_A Output signals


Name Type Description
QA1CLREL BOOLEAN Closing of QA1 is allowed
QA1CLITL BOOLEAN Closing of QA1 is forbidden
QB61REL BOOLEAN Switching of QB61 is allowed
QB61ITL BOOLEAN Switching of QB61 is forbidden
QB1REL BOOLEAN Switching of QB1 is allowed
QB1ITL BOOLEAN Switching of QB1 is forbidden
QC1REL BOOLEAN Switching of QC1 is allowed
QC1ITL BOOLEAN Switching of QC1 is forbidden
QC2REL BOOLEAN Switching of QC2 is allowed
QC2ITL BOOLEAN Switching of QC2 is forbidden
QB1OPTR BOOLEAN QB1 is in open position
QB1CLTR BOOLEAN QB1 is in closed position
VPQB1TR BOOLEAN Switch status of QB1 is valid (open or closed)

PID-3601-INPUTSIGNALS v9

Table 496: DB_BUS_B Input signals


Name Type Default Description
QA2_OP BOOLEAN 0 QA2 is in open position
QA2_CL BOOLEAN 0 QA2 is in closed position
QB2_OP BOOLEAN 0 QB2 is in open position
QB2_CL BOOLEAN 0 QB2 is in closed position
QB62_OP BOOLEAN 0 QB62 is in open position
QB62_CL BOOLEAN 0 QB62 is in closed position
QC4_OP BOOLEAN 0 QC4 is in open position
QC4_CL BOOLEAN 0 QC4 is in closed position
QC5_OP BOOLEAN 0 QC5 is in open position
QC5_CL BOOLEAN 0 QC5 is in closed position
QC3_OP BOOLEAN 0 QC3 is in open position
QC3_CL BOOLEAN 0 QC3 is in closed position
QC21_OP BOOLEAN 0 Earthing switch QC21 on busbar WA2 is in open position
QC21_CL BOOLEAN 0 Earthing switch QC21 on busbar WA2 is in closed position
EXDU_ES BOOLEAN 0 No transm error from bay containing earthing switch QC21
QB62_EX1 BOOLEAN 0 External condition for apparatus QB62
QB62_EX2 BOOLEAN 0 External condition for apparatus QB62
QB2_EX1 BOOLEAN 0 External condition for apparatus QB2
QB2_EX2 BOOLEAN 0 External condition for apparatus QB2

756 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

PID-3601-OUTPUTSIGNALS v9

Table 497: DB_BUS_B Output signals


Name Type Description
QA2CLREL BOOLEAN Closing of QA2 is allowed
QA2CLITL BOOLEAN Closing of QA2 is forbidden
QB62REL BOOLEAN Switching of QB62 is allowed
QB62ITL BOOLEAN Switching of QB62 is forbidden
QB2REL BOOLEAN Switching of QB2 is allowed
QB2ITL BOOLEAN Switching of QB2 is forbidden
QC4REL BOOLEAN Switching of QC4 is allowed
QC4ITL BOOLEAN Switching of QC4 is forbidden
QC5REL BOOLEAN Switching of QC5 is allowed
QC5ITL BOOLEAN Switching of QC5 is forbidden
QB2OPTR BOOLEAN QB2 is in open position
QB2CLTR BOOLEAN QB2 is in closed position
VPQB2TR BOOLEAN Switch status of QB2 is valid (open or closed)

PID-3508-INPUTSIGNALS v10

Table 498: DB_LINE Input signals


Name Type Default Description
QA1_OP BOOLEAN 0 QA1 is in open position
QA1_CL BOOLEAN 0 QA1 is in closed position
QA2_OP BOOLEAN 0 QA2 is in open position
QA2_CL BOOLEAN 0 QA2 is in closed position
QB61_OP BOOLEAN 0 QB61 is in open position
QB61_CL BOOLEAN 0 QB61 is in closed position
QC1_OP BOOLEAN 0 QC1 is in open position
QC1_CL BOOLEAN 0 QC1 is in closed position
QC2_OP BOOLEAN 0 QC2 is in open position
QC2_CL BOOLEAN 0 QC2 is in closed position
QB62_OP BOOLEAN 0 QB62 is in open position
QB62_CL BOOLEAN 0 QB62 is in closed position
QC4_OP BOOLEAN 0 QC4 is in open position
QC4_CL BOOLEAN 0 QC4 is in closed position
QC5_OP BOOLEAN 0 QC5 is in open position
QC5_CL BOOLEAN 0 QC5 is in closed position
QB9_OP BOOLEAN 0 QB9 is in open position
QB9_CL BOOLEAN 0 QB9 is in closed position
QC3_OP BOOLEAN 0 QC3 is in open position
QC3_CL BOOLEAN 0 QC3 is in closed position
QC9_OP BOOLEAN 0 QC9 is in open position
QC9_CL BOOLEAN 0 QC9 is in closed position
VOLT_OFF BOOLEAN 0 There is no voltage on the line and not VT (fuse) failure
Table continues on next page

Line distance protection REL670 757


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

Name Type Default Description


VOLT_ON BOOLEAN 0 There is voltage on the line or there is a VT (fuse) failure
QB9_EX1 BOOLEAN 0 External condition for apparatus QB9
QB9_EX2 BOOLEAN 0 External condition for apparatus QB9
QB9_EX3 BOOLEAN 0 External condition for apparatus QB9
QB9_EX4 BOOLEAN 0 External condition for apparatus QB9
QB9_EX5 BOOLEAN 0 External condition for apparatus QB9

PID-3508-OUTPUTSIGNALS v10

Table 499: DB_LINE Output signals


Name Type Description
QB9REL BOOLEAN Switching of QB9 is allowed
QB9ITL BOOLEAN Switching of QB9 is forbidden
QC3REL BOOLEAN Switching of QC3 is allowed
QC3ITL BOOLEAN Switching of QC3 is forbidden
QC9REL BOOLEAN Switching of QC9 is allowed
QC9ITL BOOLEAN Switching of QC9 is forbidden

15.3.10 Interlocking for line bay ABC_LINE IP14139-1 v2

15.3.10.1 Identification
GUID-BEA26EA4-F402-4385-9238-1361E862D987 v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Interlocking for line bay ABC_LINE - 3

15.3.10.2 Functionality M13561-3 v8

The interlocking for line bay (ABC_LINE) function is used for a line connected to a double
busbar arrangement with a transfer busbar according to figure 442. The function can also be
used for a double busbar arrangement without transfer busbar or a single busbar
arrangement with/without transfer busbar.

758 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

WA1 (A)
WA2 (B)
WA7 (C)
QB1 QB2 QB7
QC1

QA1

QC2

QB9
QC9

en04000478.vsd
IEC04000478 V1 EN-US

Figure 442: Switchyard layout ABC_LINE

Line distance protection REL670 759


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

15.3.10.3 Function block M15108-3 v6

ABC_LINE
QA1_OP QA1CLREL
QA1_CL QA1CLITL
QB9_OP QB9REL
QB9_CL QB9ITL
QB1_OP QB1REL
QB1_CL QB1ITL
QB2_OP QB2REL
QB2_CL QB2ITL
QB7_OP QB7REL
QB7_CL QB7ITL
QC1_OP QC1REL
QC1_CL QC1ITL
QC2_OP QC2REL
QC2_CL QC2ITL
QC9_OP QC9REL
QC9_CL QC9ITL
QC11_OP QB1OPTR
QC11_CL QB1CLTR
QC21_OP QB2OPTR
QC21_CL QB2CLTR
QC71_OP QB7OPTR
QC71_CL QB7CLTR
BB7_D_OP QB12OPTR
BC_12_CL QB12CLTR
BC_17_OP VPQB1TR
BC_17_CL VPQB2TR
BC_27_OP VPQB7TR
BC_27_CL VPQB12TR
VOLT_OFF
VOLT_ON
VP_BB7_D
VP_BC_12
VP_BC_17
VP_BC_27
EXDU_ES
EXDU_BPB
EXDU_BC
QB9_EX1
QB9_EX2
QB1_EX1
QB1_EX2
QB1_EX3
QB2_EX1
QB2_EX2
QB2_EX3
QB7_EX1
QB7_EX2
QB7_EX3
QB7_EX4

IEC05000357-2-en.vsd
IEC05000357 V2 EN-US

Figure 443: ABC_LINE function block

760 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

15.3.10.4 Logic diagram M15089-3 v5

ABC_LINE
QA1_OP
QA1_CL =1 VPQA1
QB9_OP
QB9_CL =1 VPQB9
QA1CLREL
QB1_OP
QB1_CL =1 VPQB1 QA1CLITL
& 1
QB2_OP
QB2_CL =1 VPQB2
QB7_OP
QB7_CL =1 VPQB7
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QC9_OP
QC9_CL =1 VPQC9
QC11_OP
QC11_CL =1 VPQC11
QC21_OP
QC21_CL =1 VPQC21
QC71_OP
QC71_CL =1 VPQC71
VOLT_OFF
VOLT_ON =1 VPVOLT
VPQA1
VPQC1 QB9REL
VPQC2 & >1
QB9ITL
1
VPQC9
QA1_OP
QC1_OP
QC2_OP
QC9_OP
QB9_EX1
VPQC2
VPQC9
&
QC2_CL
QC9_CL
QB9_EX2

en04000527.vsd
IEC04000527 V1 EN-US

Line distance protection REL670 761


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

VPQA1 QB1REL
& ³1
VPQB2
VPQC1 1 QB1ITL
VPQC2
VPQC11
QA1_OP
QB2_OP
QC1_OP
QC2_OP
QC11_OP
EXDU_ES

QB1_EX1

VPQB2 &
VP_BC_12
QB2_CL
BC_12_CL
EXDU_BC

QB1_EX2

VPQC1 &
VPQC11
QC1_CL
QC11_CL
EXDU_ES

QB1EX3

en04000528.vsd

IEC04000528 V1 EN-US

762 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

VPQA1 QB2REL
& ³1
VPQB1
VPQC1 1 QB2ITL
VPQC2
VPQC21
QA1_OP
QB1_OP
QC1_OP
QC2_OP
QC21_OP
EXDU_ES

QB2_EX1

VPQB1 &
VP_BC_12
QB1_CL
BC_12_CL
EXDU_BC

QB2_EX2

VPQC1 &
VPQC21
QC1_CL
QC21_CL
EXDU_ES

QB2_EX3

en04000529.vsd

IEC04000529 V1 EN-US

Line distance protection REL670 763


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

VPQC9 QB7REL
& >1
VPQC71
VP_BB7_D 1 QB7ITL
VP_BC_17
VP_BC_27
QC9_OP
QC71_OP
EXDU_ES

BB7_D_OP
EXDU_BPB

BC_17_OP
BC_27_OP
EXDU_BC
QB7_EX1

VPQA1
VPQB1
VPQC9
&
VPQB9
VPQC71
VP_BB7_D
VP_BC_17
QA1_CL
QB1_CL
QC9_OP
QB9_CL
QC71_OP
EXDU_ES

BB7_D_OP
EXDU_BPB
BC_17_CL

EXDU_BC

QB7_EX2

IEC04000530 V1 EN-US

764 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

VPQA1
VPQB2
& >1
VPQC9
VPQB9
VPQC71
VP_BB7_D
VP_BC_27
QA1_CL
QB2_CL
QC9_OP
QB9_CL
QC71_OP
EXDU_ES

BB7_D_OP
EXDU_BPB
BC_27_CL
EXDU_BC
QB7_EX3
VPQC9
VPQC71
&
QC9_CL
QC71_CL
EXDU_ES
QB7_EX4
VPQB1 QC1REL
VPQB2 QC1ITL
VPQB9 & 1
QC2REL
QB1_OP
QB2_OP QC2ITL
1
QB9_OP
VPQB7
VPQB9 QC9REL
VPVOLT &
QC9ITL
QB7_OP 1
QB9_OP
VOLT_OFF
en04000531.vsd
IEC04000531 V1 EN-US

Line distance protection REL670 765


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
QB2_OP QB2OPTR
QB2_CL QB2CLTR
VPQB2 VPQB2TR
QB7_OP QB7OPTR
QB7_CL QB7CLTR
VPQB7 VPQB7TR
QB1_OP QB12OPTR
QB2_OP >1 QB12CLTR
VPQB1 1
VPQB12TR
VPQB2 &
en04000532.vsd
IEC04000532 V1 EN-US

15.3.10.5 Signals
PID-3509-INPUTSIGNALS v10

Table 500: ABC_LINE Input signals


Name Type Default Description
QA1_OP BOOLEAN 0 QA1 is in open position
QA1_CL BOOLEAN 0 QA1 is in closed position
QB9_OP BOOLEAN 0 QB9 is in open position
QB9_CL BOOLEAN 0 QB9 is in closed position
QB1_OP BOOLEAN 0 QB1 is in open position
QB1_CL BOOLEAN 0 QB1 is in closed position
QB2_OP BOOLEAN 0 QB2 is in open position
QB2_CL BOOLEAN 0 QB2 is in closed position
QB7_OP BOOLEAN 0 QB7 is in open position
QB7_CL BOOLEAN 0 QB7 is in closed position
QC1_OP BOOLEAN 0 QC1 is in open position
QC1_CL BOOLEAN 0 QC1 is in closed position
QC2_OP BOOLEAN 0 QC2 is in open position
QC2_CL BOOLEAN 0 QC2 is in closed position
QC9_OP BOOLEAN 0 QC9 is in open position
QC9_CL BOOLEAN 0 QC9 is in closed position
QC11_OP BOOLEAN 0 Earthing switch QC11 on busbar WA1 is in open position
QC11_CL BOOLEAN 0 Earthing switch QC11 on busbar WA1 is in closed position
QC21_OP BOOLEAN 0 Earthing switch QC21 on busbar WA2 is in open position
QC21_CL BOOLEAN 0 Earthing switch QC21 on busbar WA2 is in closed position
QC71_OP BOOLEAN 0 Earthing switch QC71 on busbar WA7 is in open position
QC71_CL BOOLEAN 0 Earthing switch QC71 on busbar WA7 is in closed position
BB7_D_OP BOOLEAN 0 Disconnectors on busbar WA7 except in the own bay are open
BC_12_CL BOOLEAN 0 A bus coupler connection exists between busbar WA1 and
WA2
Table continues on next page

766 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

Name Type Default Description


BC_17_OP BOOLEAN 0 No bus coupler connection exists between busbar WA1 and
WA7
BC_17_CL BOOLEAN 0 A bus coupler connection exists between busbar WA1 and
WA7
BC_27_OP BOOLEAN 0 No bus coupler connection exists between busbar WA2 and
WA7
BC_27_CL BOOLEAN 0 A bus coupler connection exists between busbar WA2 and
WA7
VOLT_OFF BOOLEAN 0 There is no voltage on the line and not VT (fuse) failure
VOLT_ON BOOLEAN 0 There is voltage on the line or there is a VT (fuse) failure
VP_BB7_D BOOLEAN 0 Switch status of the disconnectors on busbar WA7 are valid
VP_BC_12 BOOLEAN 0 Status of the bus coupler app. between WA1 and WA2 are
valid
VP_BC_17 BOOLEAN 0 Status of the bus coupler app. between WA1 and WA7 are
valid
VP_BC_27 BOOLEAN 0 Status of the bus coupler app. between WA2 and WA7 are
valid
EXDU_ES BOOLEAN 0 No transm error from any bay containing earthing switches
EXDU_BPB BOOLEAN 0 No transm error from any bay with disconnectors on WA7
EXDU_BC BOOLEAN 0 No transmission error from any bus coupler bay
QB9_EX1 BOOLEAN 0 External condition for apparatus QB9
QB9_EX2 BOOLEAN 0 External condition for apparatus QB9
QB1_EX1 BOOLEAN 0 External condition for apparatus QB1
QB1_EX2 BOOLEAN 0 External condition for apparatus QB1
QB1_EX3 BOOLEAN 0 External condition for apparatus QB1
QB2_EX1 BOOLEAN 0 External condition for apparatus QB2
QB2_EX2 BOOLEAN 0 External condition for apparatus QB2
QB2_EX3 BOOLEAN 0 External condition for apparatus QB2
QB7_EX1 BOOLEAN 0 External condition for apparatus QB7
QB7_EX2 BOOLEAN 0 External condition for apparatus QB7
QB7_EX3 BOOLEAN 0 External condition for apparatus QB7
QB7_EX4 BOOLEAN 0 External condition for apparatus QB7

PID-3509-OUTPUTSIGNALS v10

Table 501: ABC_LINE Output signals


Name Type Description
QA1CLREL BOOLEAN Closing of QA1 is allowed
QA1CLITL BOOLEAN Closing of QA1 is forbidden
QB9REL BOOLEAN Switching of QB9 is allowed
QB9ITL BOOLEAN Switching of QB9 is forbidden
QB1REL BOOLEAN Switching of QB1 is allowed
QB1ITL BOOLEAN Switching of QB1 is forbidden
QB2REL BOOLEAN Switching of QB2 is allowed
QB2ITL BOOLEAN Switching of QB2 is forbidden
QB7REL BOOLEAN Switching of QB7 is allowed
Table continues on next page

Line distance protection REL670 767


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

Name Type Description


QB7ITL BOOLEAN Switching of QB7 is forbidden
QC1REL BOOLEAN Switching of QC1 is allowed
QC1ITL BOOLEAN Switching of QC1 is forbidden
QC2REL BOOLEAN Switching of QC2 is allowed
QC2ITL BOOLEAN Switching of QC2 is forbidden
QC9REL BOOLEAN Switching of QC9 is allowed
QC9ITL BOOLEAN Switching of QC9 is forbidden
QB1OPTR BOOLEAN QB1 is in open position
QB1CLTR BOOLEAN QB1 is in closed position
QB2OPTR BOOLEAN QB2 is in open position
QB2CLTR BOOLEAN QB2 is in closed position
QB7OPTR BOOLEAN QB7 is in open position
QB7CLTR BOOLEAN QB7 is in closed position
QB12OPTR BOOLEAN QB1 or QB2 or both are in open position
QB12CLTR BOOLEAN QB1 and QB2 are not in open position
VPQB1TR BOOLEAN Switch status of QB1 is valid (open or closed)
VPQB2TR BOOLEAN Switch status of QB2 is valid (open or closed)
VPQB7TR BOOLEAN Switch status of QB7 is valid (open or closed)
VPQB12TR BOOLEAN Switch status of QB1 and QB2 are valid (open or closed)

15.3.11 Interlocking for transformer bay AB_TRAFO IP14149-1 v2

15.3.11.1 Identification
GUID-AD839CAA-531B-43BC-B508-39AED3D0A97D v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Interlocking for transformer bay AB_TRAFO - 3

15.3.11.2 Functionality M13567-3 v7

The interlocking for transformer bay (AB_TRAFO) function is used for a transformer bay
connected to a double busbar arrangement according to figure 444. The function is used when
there is no disconnector between circuit breaker and transformer. Otherwise, the interlocking
for line bay (ABC_LINE) function can be used. This function can also be used in single busbar
arrangements.

768 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

WA1 (A)
WA2 (B)
QB1 QB2
QC1

QA1
AB_TRAFO
QC2

QC3

QA2
QA2 and QC4 are not
QC4 used in this interlocking

QB3 QB4

en04000515.vsd
IEC04000515 V1 EN-US

Figure 444: Switchyard layout AB_TRAFO

15.3.11.3 Function block M13565-3 v6

AB_TRAFO
QA1_OP QA1CLREL
QA1_CL QA1CLITL
QB1_OP QB1REL
QB1_CL QB1ITL
QB2_OP QB2REL
QB2_CL QB2ITL
QC1_OP QC1REL
QC1_CL QC1ITL
QC2_OP QC2REL
QC2_CL QC2ITL
QB3_OP QB1OPTR
QB3_CL QB1CLTR
QB4_OP QB2OPTR
QB4_CL QB2CLTR
QC3_OP QB12OPTR
QC3_CL QB12CLTR
QC11_OP VPQB1TR
QC11_CL VPQB2TR
QC21_OP VPQB12TR
QC21_CL
BC_12_CL
VP_BC_12
EXDU_ES
EXDU_BC
QA1_EX1
QA1_EX2
QA1_EX3
QB1_EX1
QB1_EX2
QB1_EX3
QB2_EX1
QB2_EX2
QB2_EX3

IEC05000358-2-en.vsd
IEC05000358 V2 EN-US

Figure 445: AB_TRAFO function block

Line distance protection REL670 769


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

15.3.11.4 Logic diagram M15097-3 v4

AB_TRAFO
QA1_OP
QA1_CL =1 VPQA1
QB1_OP
QB1_CL =1 VPQB1
QB2_OP
QB2_CL =1 VPQB2
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QB3_OP
QB3_CL =1 VPQB3
QB4_OP
QB4_CL =1 VPQB4
QC3_OP
QC3_CL =1 VPQC3
QC11_OP
QC11_CL =1 VPQC11
QC21_OP
QC21_CL =1 VPQC21
VPQB1 QA1CLREL
VPQB2 QA1CLITL
VPQC1 & 1

VPQC2
VPQB3
VPQB4
VPQC3
QA1_EX2
QC3_OP
QA1_EX3
QC1_CL >1
QC2_CL
QC3_CL &
QA1_EX1

en04000538.vsd

IEC04000538 V1 EN-US

VPQA1
VPQB2 QB1REL
& >1
VPQC1 QB1ITL
VPQC2 1
VPQC3
VPQC11
QA1_OP
QB2_OP
QC1_OP
QC2_OP
QC3_OP
QC11_OP
EXDU_ES
QB1_EX1
VPQB2
VPQC3
&
VP_BC_12
QB2_CL
QC3_OP
BC_12_CL
EXDU_BC
QB1_EX2
VPQC1
VPQC2
&
VPQC3
VPQC11
QC1_CL
QC2_CL
QC3_CL
QC11_CL
EXDU_ES
QB1_EX3

en04000539.vsd

IEC04000539 V1 EN-US

770 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

VPQA1
VPQB1 QB2REL
& >1
VPQC1 QB2ITL
VPQC2 1
VPQC3
VPQC21
QA1_OP
QB1_OP
QC1_OP
QC2_OP
QC3_OP
QC21_OP
EXDU_ES
QB2_EX1
VPQB1
VPQC3
&
VP_BC_12
QB1_CL
QC3_OP
BC_12_CL
EXDU_BC
QB2_EX2
VPQC1
VPQC2
&
VPQC3
VPQC21
QC1_CL
QC2_CL
QC3_CL
QC21_CL
EXDU_ES
QB2_EX3

en04000540.vsd

IEC04000540 V1 EN-US

VPQB1 QC1REL
VPQB2 QC1ITL
& 1
VPQB3
QC2REL
VPQB4
QB1_OP QC2ITL
1
QB2_OP
QB3_OP
QB4_OP
QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
QB2_OP QB2OPTR
QB2_CL QB2CLTR
VPQB2 VPQB2TR
QB1_OP QB12OPTR
QB2_OP >1 QB12CLTR
VPQB1 1
VPQB12TR
VPQB2 &
en04000541.vsd

IEC04000541 V1 EN-US

15.3.11.5 Signals
PID-3510-INPUTSIGNALS v10

Table 502: AB_TRAFO Input signals


Name Type Default Description
QA1_OP BOOLEAN 0 QA1 is in open position
QA1_CL BOOLEAN 0 QA1 is in closed position
QB1_OP BOOLEAN 0 QB1 is in open position
QB1_CL BOOLEAN 0 QB1 is in closed position
QB2_OP BOOLEAN 0 QB2 is in open position
QB2_CL BOOLEAN 0 QB2 is in closed position
QC1_OP BOOLEAN 0 QC1 is in open position
QC1_CL BOOLEAN 0 QC1 is in closed position
QC2_OP BOOLEAN 0 QC2 is in open position
QC2_CL BOOLEAN 0 QC2 is in closed position
QB3_OP BOOLEAN 0 QB3 is in open position
Table continues on next page

Line distance protection REL670 771


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

Name Type Default Description


QB3_CL BOOLEAN 0 QB3 is in closed position
QB4_OP BOOLEAN 0 QB4 is in open position
QB4_CL BOOLEAN 0 QB4 is in closed position
QC3_OP BOOLEAN 0 QC3 is in open position
QC3_CL BOOLEAN 0 QC3 is in closed position
QC11_OP BOOLEAN 0 QC11 on busbar WA1 is in open position
QC11_CL BOOLEAN 0 QC11 on busbar WA1 is in closed position
QC21_OP BOOLEAN 0 QC21 on busbar WA2 is in open position
QC21_CL BOOLEAN 0 QC21 on busbar WA2 is in closed position
BC_12_CL BOOLEAN 0 A bus coupler connection exists between busbar WA1 and
WA2
VP_BC_12 BOOLEAN 0 Status of the bus coupler app. between WA1 and WA2 are
valid
EXDU_ES BOOLEAN 0 No transm error from any bay containing earthing switches
EXDU_BC BOOLEAN 0 No transmission error from any bus coupler bay
QA1_EX1 BOOLEAN 0 External condition for apparatus QA1
QA1_EX2 BOOLEAN 0 External condition for apparatus QA1
QA1_EX3 BOOLEAN 0 External condition for apparatus QA1
QB1_EX1 BOOLEAN 0 External condition for apparatus QB1
QB1_EX2 BOOLEAN 0 External condition for apparatus QB1
QB1_EX3 BOOLEAN 0 External condition for apparatus QB1
QB2_EX1 BOOLEAN 0 External condition for apparatus QB2
QB2_EX2 BOOLEAN 0 External condition for apparatus QB2
QB2_EX3 BOOLEAN 0 External condition for apparatus QB2

PID-3510-OUTPUTSIGNALS v10

Table 503: AB_TRAFO Output signals


Name Type Description
QA1CLREL BOOLEAN Closing of QA1 is allowed
QA1CLITL BOOLEAN Closing of QA1 is forbidden
QB1REL BOOLEAN Switching of QB1 is allowed
QB1ITL BOOLEAN Switching of QB1 is forbidden
QB2REL BOOLEAN Switching of QB2 is allowed
QB2ITL BOOLEAN Switching of QB2 is forbidden
QC1REL BOOLEAN Switching of QC1 is allowed
QC1ITL BOOLEAN Switching of QC1 is forbidden
QC2REL BOOLEAN Switching of QC2 is allowed
QC2ITL BOOLEAN Switching of QC2 is forbidden
QB1OPTR BOOLEAN QB1 is in open position
QB1CLTR BOOLEAN QB1 is in closed position
QB2OPTR BOOLEAN QB2 is in open position
QB2CLTR BOOLEAN QB2 is in closed position
QB12OPTR BOOLEAN QB1 or QB2 or both are in open position
Table continues on next page

772 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

Name Type Description


QB12CLTR BOOLEAN QB1 and QB2 are not in open position
VPQB1TR BOOLEAN Switch status of QB1 is valid (open or closed)
VPQB2TR BOOLEAN Switch status of QB2 is valid (open or closed)
VPQB12TR BOOLEAN Switch status of QB1 and QB2 are valid (open or closed)

15.3.12 Position evaluation POS_EVAL GUID-F20A8939-E91E-44F6-920C-083E5D3FCDFD v2

15.3.12.1 Identification
GUID-3C4B9379-C861-406C-9295-0309014D548E v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Position evaluation POS_EVAL - -

15.3.12.2 Functionality GUID-C3D07B40-FF01-45C5-A083-EED5643A5FCC v4

Position evaluation (POS_EVAL) function converts the input position data signal POSITION,
consisting of value, time and signal status, to binary signals OPENPOS or CLOSEPOS.

The output signals are used by other functions in the interlocking scheme.

15.3.12.3 Function block GUID-B5EF4A28-9C9F-4558-8CD6-453FB480314B v2

POS_EVAL
POSITION OPENPOS
CLOSEPOS

IEC09000079_1_en.vsd
IEC09000079 V1 EN-US

Figure 446: POS_EVAL function block

15.3.12.4 Logic diagram GUID-F0EF8D38-031B-4A8E-BD7D-60314F5DCD59 v2

POS_EVAL
Position including quality POSITION OPENPOS
Open/close position of
CLOSEPOS switch device

IEC08000469-1-en.vsd
IEC08000469-1-EN V1 EN-US

Only the value, open/close, and status is used in this function. Time information is not used.

Input position (Value) Signal quality Output OPENPOS Output CLOSEPOS


0 (Breaker intermediate) Good 0 0
1 (Breaker open) Good 1 0
2 (Breaker closed) Good 0 1
3 (Breaker faulty) Good 0 0
Any Invalid 0 0
Any Oscillatory 0 0

Line distance protection REL670 773


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

15.3.12.5 Signals
PID-3555-INPUTSIGNALS v6

Table 504: POS_EVAL Input signals


Name Type Default Description
POSITION INTEGER 0 Position status including quality

PID-3555-OUTPUTSIGNALS v6

Table 505: POS_EVAL Output signals


Name Type Description
OPENPOS BOOLEAN Open position
CLOSEPOS BOOLEAN Close position

15.4 Apparatus control IP14560-1 v3

15.4.1 Functionality M13444-3 v15

The apparatus control functions are used for control and supervision of circuit breakers,
disconnectors and earthing switches within a bay. Permission to operate is given after
evaluation of conditions from other functions such as interlocking, synchrocheck, operator
place selection and external or internal blockings.

The complete apparatus control function is not included in this product, and
the information below is included for understanding of the principle for the use
of QCBAY, LOCREM, and LOCREMCTRL.

Apparatus control features:

• Select-Execute principle to give high reliability


• Selection function to prevent simultaneous operation
• Selection and supervision of operator place
• Command supervision
• Block/deblock of operation
• Block/deblock of updating of position indications
• Substitution of position and quality indications
• Overriding of interlocking functions
• Overriding of synchrocheck
• Operation counter
• Suppression of mid position

Two types of command models can be used:

• Direct with normal security


• SBO (Select-Before-Operate) with enhanced security

Normal security means that only the command is evaluated and the resulting position is not
supervised. Enhanced security means that the command is evaluated with an additional
supervision of the status value of the control object. The command sequence with enhanced
security is always terminated by a CommandTermination service primitive and an AddCause
telling if the command was successful or if something went wrong.

Control operation can be performed from the local HMI with authority control if so defined.

774 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

15.4.2 Operation principle M13423-4 v9

A bay can handle, for example a power line, a transformer, a reactor, or a capacitor bank. The
different primary apparatuses within the bay can be controlled via the apparatus control
functions directly by the operator or indirectly by automatic sequences.

Because a primary apparatus can be allocated to many functions within a Substation


Automation system, the object-oriented approach with a function block that handles the
interaction and status of each process object ensures consistency in the process information
used by higher-level control functions.

Primary apparatuses such as breakers and disconnectors are controlled and supervised by one
function block (SCSWI) each. Because the number and type of signals used for the control of a
breaker or a disconnector are almost the same, the same function block type is used to handle
these two types of apparatuses.

The SCSWI function block is connected either to an SXCBR function block (for circuit breakers)
or to an SXSWI function block (for disconnectors and earthing switches). The physical process
in the switchyard is connected to these two function blocks via binary inputs and outputs.

Four types of function blocks are available to cover most of the control and supervision within
the bay. These function blocks are interconnected to form a control function reflecting the
switchyard configuration. The total number used depends on the switchyard configuration.
These types are:

• Bay control QCBAY


• Switch controller SCSWI
• Circuit breaker SXCBR
• Circuit switch SXSWI

The functions Local Remote (LOCREM) and Local Remote Control (LOCREMCTRL), to handle
the local/remote switch. The functions Bay reserve (QCRSV) and Reservation input (RESIN), for
the reservation function, also belong to the apparatus control function.

The principles of operation, function blocks, input and output signals and setting parameters
for all these functions are described below.

15.4.3 Error handling GUID-6C31D291-74E8-46A3-8FC2-D3959C2458A5 v7

Depending on the error that occurs during the command sequence the error signal will be set
with a value. Table 506 describes the cause values given on local HMI. The translation to
AddCause values specified in IEC 61850-8-1 is shown in Table 507. For IEC 61850-8-1 edition 2
only addcauses defined in the standard are used, for edition 1 also a number of vendor specific
causes are used. The values are available in the command response to commands from IE
C61850-8-1 clients. An output L_CAUSE on the function block for Switch controller (SCSWI),
Circuit breaker (SXCBR) and Circuit switch (SXSWI) indicates the value of the cause during the
latest command if the function specific command evaluation has been started. The causes
that are not always reflected on the output L_CAUSE, with description of the typical reason are
listed in table 508.

Table 506: Values for "cause" signal


Cause Name Description Supported
number
0 None Control action successfully executed X
1 Not-supported Given for Cancel request with Direct Control in Ready state X
2 Blocked-by-switching- Not successful since one of the downstream Loc switches X
hierarchy like in CSWI has the value TRUE
Table continues on next page

Line distance protection REL670 775


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

Cause Name Description Supported


number
3 Select-failed Cancelled due to an unsuccessful selection (select service) X
4 Invalid-position Control action is aborted due to invalid switch position (Pos X
in XCBR or XSWI)
5 Position-reached Switch is already in the intended position (Pos in XCBR or X
XSWI)
6 Parameter-change-in- Control action is blocked due to running parameter change X
execution
7 Step-limit Control action is blocked, because tap changer has reached X
the limit (EndPosR or EndPosL in YLTC)
8 Blocked-by-Mode Control action is blocked, because the LN (CSWI or XCBR/ X
XSWI) is in a mode (Mod) which doesn’t allow any switching
9 Blocked-by-process Control action is blocked due to some external event at X
process level that prevents a successful operation, for
example blocking indication (EEHealth in XCBR or XSWI)
10 Blocked-by- Control action is blocked due to interlocking of switching X
interlocking devices (in CILO attribute EnaOpn.stVal=”FALSE” or
EnaCls.stVal=”FALSE”
11 Blocked-by- Control action with synchrocheck is aborted due to exceed X
synchrocheck of time limit and missing synchronism condition
12 Command-already-in- Control, select or cancel service is rejected, because control X
execution action is already running
13 Blocked-by-health Control action is blocked due to some internal event that X
prevents a successful operation (Health)
14 1-of-n-control Control action is blocked because another control action in X
a domain (for example, substation) is already running (in
any XCBR or XSWI of that domain, the DPC.stSeld=”TRUE”)
15 Abortion-by-cancel Control action is aborted due to cancel service X
16 Time-limit-over Control action is terminated due to exceed of some time X
limit
17 Abortion-by-trip Control action is aborted due to a trip (PTRC with X
ACT.general=”TRUE”)
18 Object-not-selected Control action is rejected, because control object was not X
selected
19 Object-already- Select action is not executed because the addressed object X
selected is already selected
20 No-access-authority Control action is blocked due to lack of access authority X
21 Ended-with- Control action executed but the end position has overshoot
overshoot
22 Abortion-due-to- Control action is aborted due to deviation between the
deviation command value and the measured value
23 Abortion-by- Control action is aborted due to the loss of connection with
communication-loss the client that issued the control
24 Blocked-by-command Control action is blocked due to the data attribute X
CmdBlk.stVal is TRUE
26 Inconsistent- The parameters between successive control services are X
parameters not consistent, for example the ctlNum of Select and
Operate service are different
27 Locked-by-other- Another client has already reserved the object X
client
-22 Wrong-Ctl-model Command from client uses wrong control model X
-23 Blocked-by-command Blocked by command X
Table continues on next page

776 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

Cause Name Description Supported


number
-24 Blocked-for-open- Blocked for Open command X
cmd
-25 Blocked-for-close- Blocked for Close Command X
cmd
-30 Long-operation-time Operation time too long X
-31 Switch-not-start- Switch did not start moving X
moving
-32 Persistent- Switch stopped in intermediate state X
intermediate-state
-33 Switch-returned-to- Switch returned to the initial position X
init-pos
-34 Switch-in-bad-state Switch is in a bad position state X
-35 Not-expected-final- Switch did not reach the expected final position X
position

Table 507: Translation of cause values for IEC 61850 edition 2 and edition 1
Internal Cause AddCause in IEC 61850-8-1 Name
Number
Ed 2 Ed 1
0 25 0 None
1 1 1 Not-supported
2 2 2 Blocked-by-switching-hierarchy
3 3 3 Select-failed
4 4 4 Invalid-position
5 5 5 Position-reached
6 6 6 Parameter-change-in-execution
7 7 7 Step-limit
8 8 8 Blocked-by-Mode
9 9 9 Blocked-by-process
10 10 10 Blocked-by-interlocking
11 11 11 Blocked-by-synchrocheck
12 12 12 Command-already-in-execution
13 13 13 Blocked-by-health
14 14 14 1-of-n-control
15 15 1 Abortion-by-cancel
16 16 16 Time-limit-over
17 17 17 Abortion-by-trip
18 18 18 Object-not-selected
19 19 3 Object-already-selected
20 20 3 No-access-authority
24 24 -23 Blocked-by-command
26 26 6 Inconsistent-parameters
27 27 12 Locked-by-other-client
-22 0 -22 Wrong-Ctl-model
Table continues on next page

Line distance protection REL670 777


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

Internal Cause AddCause in IEC 61850-8-1 Name


Number
Ed 2 Ed 1
-23 24 -23 Blocked-by-command
-24 9 -24 Blocked-for-open-cmd
-25 9 -25 Blocked-for-close-cmd
-30 16 -30 Long-operation-time
-31 16 -31 Switch-not-start-moving
-32 4 -32 Persistent-intermediate-state
-33 22 -33 Switch-returned-to-init-pos
-34 4 -34 Switch-in-bad-state
-35 22 -35 Not-expected-final-position

Table 508: Cause values not reflected on the output L_CAUSE


Cause number Cause description Conditions
3 Select-failed Canceled due to an unsuccessful selection
(select service)
8 Blocked-by-Mode Control action is blocked because the LN
(CSWI) is in a mode (Mod) which doesn’t allow
any switching or does not match the mode of
the command.
12 Command-already-in-execution Control, select or cancel service is rejected
because control action is already running.
13 Blocked-by-health Control action is blocked due to some internal
event that prevents a successful operation
(Health).
16 Time-limit-over Control action is terminated due to exceed of
some time limit.
18 Object-not-selected Control action is rejected because control
object was not selected.
19 Object-already-selected Select action is not executed because the
addressed object is already selected.
20 No-access-authority Control action is blocked due to lack of access
authority.
26 Inconsistent-parameters The parameters between successive control
services are not consistent, for example the
ctlNum of Select and Operate service are
different.
27 Locked-by-other-client Another client has already reserved the object.

15.4.4 Bay control QCBAY IP15597-1 v2

15.4.4.1 Functionality M13447-3 v8

The Bay control (QCBAY) function is used together with Local remote and local remote control
functions to handle the selection of the operator place per bay. QCBAY also provides blocking
functions that can be distributed to different apparatuses within the bay.

778 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

15.4.4.2 Function block M13469-3 v4

QCBAY
LR_OFF PSTO
LR_LOC UPD_BLKD
LR_REM CMD_BLKD
LR_VALID LOC
BL_UPD STA
BL_CMD REM
IEC10000048-3-en.vsdx
IEC10000048 V3 EN-US

Figure 447: QCBAY function block

15.4.4.3 Signals
PID-4086-INPUTSIGNALS v8

Table 509: QCBAY Input signals


Name Type Default Description
LR_OFF BOOLEAN 0 External Local/Remote switch is in Off position
LR_LOC BOOLEAN 0 External Local/Remote switch is in Local position
LR_REM BOOLEAN 0 External Local/Remote switch is in Remote position
LR_VALID BOOLEAN 0 Data representing the L/R switch position is valid
BL_UPD BOOLEAN 0 Steady signal to block the position updates
BL_CMD BOOLEAN 0 Steady signal to block the command

PID-4086-OUTPUTSIGNALS v8

Table 510: QCBAY Output signals


Name Type Description
PSTO INTEGER Value for the operator place allocation
UPD_BLKD BOOLEAN Update of position is blocked
CMD_BLKD BOOLEAN Function is blocked for commands
LOC BOOLEAN Local operation allowed
STA BOOLEAN Station operation allowed
REM BOOLEAN Remote operation allowed

15.4.4.4 Settings
PID-4086-SETTINGS v8

Table 511: QCBAY Non group settings (basic)


Name Values (Range) Unit Step Default Description
AllPSTOValid Priority - - Priority Override Priority of originators,
No priority commands from both local, station
and remote are allowed
RemoteIncStation No - - No Both Station and Remote control are
Yes allowed but not Local when local
remote switch is in remote

Line distance protection REL670 779


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

15.4.4.5 Operation principle


M13446-4 v8
The function sends information about the Permitted Source To Operate (PSTO) and blocking
conditions to other functions within the bay for example, switch control functions and voltage
control functions. The functionality of the Bay control (QCBAY) function is mainly described by
the LLN0 node in the IEC 61850-8-1 edition 2 standard, applied to one bay. In IEC 61850 edition
1 the functionality is not described by the LLN0 node or any other node, therefore the Bay
control function is represented as a vendor specific node in edition 1.

Local panel switch M13446-7 v8


The local panel switch is a switch that defines the operator place selection. The switch
connected to this function can have three positions (remote/local/off). The positions are here
defined so that remote means that operation is allowed from station and/or remote level and
local means that operation is allowed from the IED level. The local/remote switch is also on the
control/protection IED itself, which means that the position of the switch and its validity
information are connected internally, not via I/O boards. When the switch is mounted
separately from the IED the signals are connected to the function via I/O boards.

When the local panel switch (or LHMI selection, depending on the set source to select this) is in
Off position, all commands from remote and local level will be ignored. If the position for the
local/remote switch is not valid the PSTO output will always be set to faulty state (3), which
means no possibility to operate.

To adapt the signals from the local HMI or from an external local/remote switch, the function
blocks LOCREM and LOCREMCTRL are needed and connected to QCBAY.

Permitted Source To Operate (PSTO) M13446-16 v10


The actual state of the operator place is presented by the value of the Permitted Source To
Operate, PSTO signal. The PSTO value is evaluated from the local/remote switch position
according to Table 512. In addition, there are two settings and one command that affect the
value of the PSTO signal.

If the setting AllPSTOValid is set to No Priority and the LR-switch position is in Local or Remote
state, the PSTO output is set to 5 (all), that is, it is permitted to operate from local, station and
remote level without any priority. When the external panel switch is in Off position, the PSTO
output shows the actual state of the switch that is, 0. In this case, it is not possible to control
anything. The LocSta command value is forced to FALSE if AllPSTOValid is set to No priority.

If the setting RemoteIncStation is set to Yes and the LR-switch position is in Remote state, the
PSTO output is set to 2 (Station or Remote), that is, it is permitted to operate from both
station and remote level without any priority.

If the LR-switch position is in Remote state, and AllPSTOValid is set to Priority and
RemoteIncStation is set to No, the switching between station and remote level control is done
through the command LocSta. The command is accessible only through the IEC 61850 Edition
2 protocol.

780 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

Table 512: PSTO values for different Local panel switch positions
Local panel AllPSTOValid RemoteInc LocSta.CtlV PSTO LED Possible
switch (setting) Station al value indications on locations that
positions (setting) (command) LHMI shall be able
to operate
0 = Off - - - 0 Remote and Not possible
Local Off to operate
1 = Local Priority - - 1 Remote Off, Local Panel
Local On
1 = Local No priority - - 5 Remote and Local,
Local On Station or
Remote level
without any
priority
2 = Remote Priority No TRUE 6 Remote On, Station level
Local Off
2 = Remote Priority No FALSE 7 Remote On, Remote level
Local Off
2 = Remote Priority Yes - 2 Remote On, Station or
Local Off Remote level
2 = Remote No priority - - 5 Remote and Local,
Local On Station or
Remote level
without any
priority
3 = Faulty - - - 3 Remote and Not possible
Local to operate
Flashing

Blockings M13446-50 v6
The blocking states for position indications and commands are intended to provide the
possibility for the user to make common blockings for the functions configured within a
complete bay.

The blocking facilities provided by the bay control function are the following:

• Blocking of position indications, BL_UPD. This input will block all inputs related to
apparatus positions for all configured functions within the bay.
• Blocking of commands, BL_CMD. This input will block all commands for all configured
functions within the bay.

The switching of the Local/Remote switch requires at least system operator level. The
password will be requested at an attempt to operate if authority levels have been defined in
the IED, otherwise the default authority level can handle the control without LogOn. The users
and passwords are defined with the IED Users tool in PCM600.

15.4.5 Local/Remote switch LOCREM IP16319-1 v3

M17086-3 v11
The signals from the local HMI or from an external local/remote switch are connected via the
function blocks local remote (LOCREM) and local remote control (LOCREMCTRL) to the Bay
control (QCBAY) function block. The parameter ControlMode in function block LOCREM is set
to choose if the switch signals are coming from the local HMI or from an external hardware
switch connected via binary inputs.

Line distance protection REL670 781


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

15.4.5.1 Function block M17088-3 v4

LOCREM
CTRLOFF OFF
LOCCTRL LOCAL
REMCTRL REMOTE
LHMICTRL VALID
IEC05000360-3-en.vsdx
IEC05000360 V3 EN-US

Figure 448: LOCREM function block

LOCREMCTRL
^PSTO1 HMICTR1
^PSTO2 HMICTR2
^PSTO3 HMICTR3
^PSTO4 HMICTR4
^PSTO5 HMICTR5
^PSTO6 HMICTR6
^PSTO7 HMICTR7
^PSTO8 HMICTR8
^PSTO9 HMICTR9
^PSTO10 HMICTR10
^PSTO11 HMICTR11
^PSTO12 HMICTR12
IEC05000361-3-en.vsdx
IEC05000361 V3 EN-US

Figure 449: LOCREMCTRL function block

15.4.5.2 Signals
PID-3944-INPUTSIGNALS v7

Table 513: LOCREM Input signals


Name Type Default Description
CTRLOFF BOOLEAN 0 Disable control
LOCCTRL BOOLEAN 0 Local in control
REMCTRL BOOLEAN 0 Remote in control
LHMICTRL INTEGER 0 LHMI control

PID-3944-OUTPUTSIGNALS v7

Table 514: LOCREM Output signals


Name Type Description
OFF BOOLEAN Control is disabled
LOCAL BOOLEAN Local control is activated
REMOTE BOOLEAN Remote control is activated
VALID BOOLEAN Outputs are valid

PID-3943-INPUTSIGNALS v6

Table 515: LOCREMCTRL Input signals


Name Type Default Description
PSTO1 INTEGER 0 PSTO input channel 1
PSTO2 INTEGER 0 PSTO input channel 2
PSTO3 INTEGER 0 PSTO input channel 3
PSTO4 INTEGER 0 PSTO input channel 4
PSTO5 INTEGER 0 PSTO input channel 5
Table continues on next page

782 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

Name Type Default Description


PSTO6 INTEGER 0 PSTO input channel 6
PSTO7 INTEGER 0 PSTO input channel 7
PSTO8 INTEGER 0 PSTO input channel 8
PSTO9 INTEGER 0 PSTO input channel 9
PSTO10 INTEGER 0 PSTO input channel 10
PSTO11 INTEGER 0 PSTO input channel 11
PSTO12 INTEGER 0 PSTO input channel 12

PID-3943-OUTPUTSIGNALS v6

Table 516: LOCREMCTRL Output signals


Name Type Description
HMICTR1 INTEGER Bitmask output 1 to local remote LHMI input
HMICTR2 INTEGER Bitmask output 2 to local remote LHMI input
HMICTR3 INTEGER Bitmask output 3 to local remote LHMI input
HMICTR4 INTEGER Bitmask output 4 to local remote LHMI input
HMICTR5 INTEGER Bitmask output 5 to local remote LHMI input
HMICTR6 INTEGER Bitmask output 6 to local remote LHMI input
HMICTR7 INTEGER Bitmask output 7 to local remote LHMI input
HMICTR8 INTEGER Bitmask output 8 to local remote LHMI input
HMICTR9 INTEGER Bitmask output 9 to local remote LHMI input
HMICTR10 INTEGER Bitmask output 10 to local remote LHMI input
HMICTR11 INTEGER Bitmask output 11 to local remote LHMI input
HMICTR12 INTEGER Bitmask output 12 to local remote LHMI input

15.4.5.3 Settings
PID-3944-SETTINGS v7

Table 517: LOCREM Non group settings (basic)


Name Values (Range) Unit Step Default Description
ControlMode Internal LR-switch - - Internal LR- Control mode for internal/external LR-
External LR- switch switch
switch

PID-3943-SETTINGS v2

15.4.5.4 Operation principle M17087-3 v9

The function block Local remote (LOCREM) handles the signals coming from the local/remote
switch. The connections are seen in Figure 450, where the inputs on function block LOCREM
are connected to binary inputs if an external switch is used. When the local HMI is used, the
inputs are not used. The switching between external and local HMI source is done through the
parameter ControlMode. The outputs from the LOCREM function block control the output
PSTO (Permitted Source To Operate) on Bay control (QCBAY).

Line distance protection REL670 783


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

LOCREM QCBAY
CTRLOFF OFF LR_ OFF PSTO
LOCCTRL LOCAL LR_ LOC UPD_ BLKD
REMCTRL REMOTE LR_ REM CMD_ BLKD
LHMICTRL VALID LR_ VALID LOC
BL_ UPD STA
BL_ CMD REM

LOCREM QCBAY
CTRLOFF OFF LR_ OFF PSTO
LOCCTRL LOCAL LR_ LOC UPD_ BLKD
REMCTRL REMOTE LR_ REM CMD_ BLKD
LHMICTRL VALID LR_ VALID LOC
BL_ UPD STA
BL_ CMD REM

LOCREMCTRL
PSTO1 HMICTR1
PSTO2 HMICTR2
PSTO3 HMICTR3
PSTO4 HMICTR4
PSTO5 HMICTR5
PSTO6 HMICTR6
PSTO7 HMICTR7
PSTO8 HMICTR8
PSTO9 HMICTR9
PSTO 10 HMICTR 10
PSTO 11 HMICTR 11
PSTO 12 HMICTR 12

IEC10000052-1-en.vsd
IEC10000052 V2 EN-US

Figure 450: Configuration for the local/remote handling for a local HMI with two bays and
two screen pages
If the IED contains control functions for several bays, the local/remote position can be
different for the included bays. When the local HMI is used the position of the local/remote
switch can be different depending on which single line diagram screen page that is presented
on the local HMI. The function block Local remote control (LOCREMCTRL) controls the
presentation of the LEDs for the local/remote position to applicable bay and screen page.

The switching of the local/remote switch requires at least system operator level. The
password will be requested at an attempt to operate if authority levels have been defined in
the IED. Otherwise the default authority level, SuperUser, can handle the control without
LogOn. The users and passwords are defined with the IED Users tool in PCM600.

15.4.6 Switch controller SCSWI IP15603-1 v2

15.4.6.1 Functionality M13486-3 v10

The Switch controller (SCSWI) initializes and supervises all functions to properly select and
operate switching primary apparatuses. The Switch controller may handle and operate on one
multi-phase device or up to three one-phase devices.

784 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

15.4.6.2 Function block M13482-3 v5

SCSWI
BLOCK EXE_OP
PSTO EXE_CL
L_SEL SEL_OP
L_OPEN SEL_CL
L_CLOSE SELECTED
AU_OPEN RES_RQ
AU_CLOSE START_SY
BL_CMD CANC_SY
RES_GRT POSITION
RES_EXT OPENP OS
SY_INPRO CLOSEPOS
SYNC_OK POLEDISC
EN_OPEN CMD_BLK
EN_CLOSE L_CAUSE
XPOSL1* POS_INTR
XPOSL2* XEXINF
XPOSL3*
IEC05000337-6-en.vsdx
IEC05000337 V6 EN-US

Figure 451: SCSWI function block

15.4.6.3 Signals
PID-6798-INPUTSIGNALS v4

Table 518: SCSWI Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
PSTO INTEGER 2 Operator place selection
L_SEL BOOLEAN 0 Select signal from local panel
L_OPEN BOOLEAN 0 Open signal from local panel
L_CLOSE BOOLEAN 0 Close signal from local panel
AU_OPEN BOOLEAN 0 Open signal from local automation function
AU_CLOSE BOOLEAN 0 Close signal from local automation function
BL_CMD BOOLEAN 0 Steady signal for block of the command
RES_GRT BOOLEAN 0 Positive acknowledge that all reservations are made
RES_EXT BOOLEAN 0 Reservation is made externally
SY_INPRO BOOLEAN 0 Synchronizing function in progress
SYNC_OK BOOLEAN 0 Closing is permitted at set to true by the synchrocheck
EN_OPEN BOOLEAN 0 Enables open operation
EN_CLOSE BOOLEAN 0 Enables close operation
XPOSL1 GROUP - Group signal from XCBR/XSWI per phase
SIGNAL
XPOSL2 GROUP - Group signal from XCBR/XSWI per phase
SIGNAL
XPOSL3 GROUP - Group signal from XCBR/XSWI per phase
SIGNAL

Line distance protection REL670 785


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

PID-6798-OUTPUTSIGNALS v4

Table 519: SCSWI Output signals


Name Type Description
EXE_OP BOOLEAN Execute command for open direction
EXE_CL BOOLEAN Execute command for close direction
SEL_OP BOOLEAN Selected for open command
SEL_CL BOOLEAN Selected for close command
SELECTED BOOLEAN Select conditions are fulfilled
RES_RQ BOOLEAN Request signal to the reservation function
START_SY BOOLEAN Starts the external synchronizing function
CANC_SY BOOLEAN Cancels the external synchronizing function, started through
START_SY
POSITION INTEGER Position indication
OPENPOS BOOLEAN Open position indication
CLOSEPOS BOOLEAN Closed position indication
POLEDISC BOOLEAN The positions for poles L1-L3 are not equal after a set time
CMD_BLK BOOLEAN Commands are blocked
L_CAUSE INTEGER Latest value of the error indication during command
POS_INTR BOOLEAN Stopped in intermediate position
XEXINF GROUP SIGNAL Execution information to XCBR, XSWI & XLNPROXY

GUID-7DABB496-EABE-48A4-8078-7ED5D6D4FE14 v2

AU_OPEN and AU_CLOSE are used to issue automated commands as e.g. for
load shedding for opening respectively closing to the SCSWI function. They
work without regard to how the operator place selector, PSTO, is set. In order
to have effect on the outputs EXE_OP and EXE_CL, the corresponding enable
input, EN_OPEN respectively EN_CLOSE must be set, and that no interlocking is
active.

L_SEL, L_OPEN and L_CLOSE are used for local command sequence connected
to binary inputs. In order to have effect, the operator place selector, PSTO,
must be set to local or to remote with no priority. If the control model used is
Select before operate, Also the corresponding enable input must be set, and no
interlocking is active. The L_SEL input must be set before L_OPEN or L_CLOSE
is operated, if the control model is Select before operate.

If one multi-phase XCBR/XSWI or two single-phase XCBR/XSWI are used for a


two- or three-phase system, two or more of the inputs XPOSL1, XPOSL2 and
XPOSL3 are connected to the same source.

786 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

15.4.6.4 Settings
PID-6798-SETTINGS v4

Table 520: SCSWI Non group settings (basic)


Name Values (Range) Unit Step Default Description
CtlModel Dir Norm - - SBO Enh Specifies control model type
SBO Enh
PosDependent Always permitted - - Always Permission to operate depending on
Not perm at permitted the position
00/11
tSelect 0.00 - 600.00 s 0.01 30.00 Maximum time between select and
execute signals
tResResponse 0.000 - 60.000 s 0.001 5.000 Allowed time from reservation request
to reservation granted
tSynchrocheck 0.00 - 600.00 s 0.01 10.00 Allowed time for synchrocheck to fulfil
close conditions
tSynchronizing 0.00 - 600.00 s 0.01 0.00 Supervision time to get the signal
synchronizing in progress
tExecutionFB 0.00 - 600.00 s 0.01 30.00 Maximum time from command
execution to termination
tPoleDiscord 0.000 - 60.000 s 0.001 2.000 Allowed time to have discrepancy
between the poles
SuppressMidPos Off - - On Mid-position is suppressed during
On time tIntermediate; tIntermediate is
set on each connected XCBR/XSWI
function individually
InterlockChk Sel & Op phase - - Sel & Op phase Selection if interlock check should be
Op phase done in select phase

15.4.6.5 Operation principle


M13484-4 v4
The Switch controller (SCSWI) is provided with verification checks for the select - execute
sequence, that is, checks the conditions prior each step of the operation are fulfilled. The
involved functions for these condition verifications are interlocking, reservation, blockings and
synchrocheck.

Control handling M13484-6 v7


.
Two types of control models can be used. The two control models are "direct with normal
security" and "SBO (Select-Before-Operate) with enhanced security". The parameter CtlModel
defines which one of the two control models is used. The control model "direct with normal
security" does not require a select whereas, the "SBO with enhanced security" command model
requires a select before execution. The command sequence for a command with control mode
SBO with enhanced security is shown in figure 452, with control mode direct with normal
security is shown in figure 453.

Line distance protection REL670 787


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

Reservation SXCBR /
Client SCSWI
logic SXSWI
select

SEL_CL = TRUE

RES_RQ = TRUE
tReservation
Response

tSelect
RES_GRT = TRUE
SELECTED = TRUE
selectAck/AddCause = 0

requestedPosition = 10

opRcvd = TRUE
EXE_CL

opOK = TRUE, tOpOk


operateAck/AddCause = 0
operateAck/AddCause = 0
tExecutionFB

POSITION = 00, timeStamp


POSITION = 00, timeStamp
POSITION = 10, timeStamp
cmdTermination/AddCause = 0

POSITION = 10, timeStamp


cmdTermination/AddCause = 0
SELECTED = FALSE
SEL_CL = FALSE

RES_RQ = FALSE

RES_GRT = FALSE

IEC15000416-2-EN.vsdx

IEC15000416 V2 EN-US

Figure 452: Example of command sequence for a successful close command when the
control model SBO with enhanced security is used

Reservation SwitchCtrl Switch


client
core core core

requestedPosition = 10

opRcvd = TRUE

RES_RQ
tReservation
Response

RES_GRT = TRUE
EXE_CL

opOK = TRUE, tOpOk

operateAck/AddCause = 0 operateAck/AddCause = 0

POSITION = 00, timeStamp POSITION = 00, timeStamp

POSITION = 10, timeStamp


cmdTermination/
POSITION = 10, timeStamp AddCause = 0

RES_RQ = FALSE

RES_GRT = FALSE

IEC15000417-1-en.vsdx

IEC15000417 V1 EN-US

Figure 453: Example of command sequence for a successful close command when the
control model direct with normal security is used
Normal security means that only the command is evaluated and the resulting position is not
supervised. Enhanced security means that the command sequence is supervised in three
steps, the selection, command evaluation and the supervision of position. Each step ends up
with a pulsed signal to indicate that the respective step in the command sequence is finished.
If an error occurs in one of the steps in the command sequence, the sequence is terminated.
The last error (L_CAUSE) can be read from the function block and used for example at
commissioning.

788 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

There is no relation between the command direction and the actual position.
For example, if the switch is in closed position it is possible to execute a close
command.

Before an execution command, an evaluation of the position is done. If the parameter


PosDependent is true and the position is in intermediate state or in bad state no execution
command is sent. If the parameter is false the execution command is sent independent of the
position value.

Evaluation of position M13484-14 v5


The position output from the switches (SXCBR or SXSWI) is connected to the switch controller
SCSWI. The XPOSL1, XPOSL2 and XPOSL3 input signals receive the position, time stamps and
quality attributes of the position which is used for further evaluation.

In the case when there are two or more one-phase switches connected to the switch control
function, the switch control will "merge" the position of the switches to the resulting multi-
phase position. In the case when the position differ between the one-phase switches,
following principles will be applied:

All switches in open position: switch control position = open


All switches in closed position: switch control position = closed
At least one switch in open position and the switch control position = intermediate
other(s) in closed position:
Any switch in intermediate position: switch control position = intermediate
Any switch in bad state: switch control position = bad state

The time stamp of the output multi-phase position from switch control will have the time
stamp of the last changed phase when it reaches the end position. When it goes to
intermediate position or bad state, it will get the time stamp of the first changed phase.

In addition, there is also the possibility that one of the one-phase switches will change
position at any time due to a trip. Such situation is here called pole discordance and is
supervised by this function. In case of a pole discordance situation, that is, the positions of the
one-phase switches are not equal for a time longer than the setting tPoleDiscord, an error
signal POLEDISC will be set.

In the supervision phase, the switch controller function evaluates the "cause" values from the
switch modules circuit breaker (SXCBR)/circuit switch (SXSWI). At error the "cause" value with
highest priority is shown.

Blocking principles M13484-37 v5


The blocking signals are normally coming from the bay control function (QCBAY) and via the
IEC 61850 communication from the operator place.

The different blocking possibilities are:

• Block/deblock of command. It is used to block command for operation of position.


• Blocking of function, BLOCK. If the BLOCK signal is set, it means that the function is
active, but no outputs are generated, no reporting, control commands are rejected and
functional and configuration data is visible.

The different block conditions will only affect the operation of this function,
that is, no blocking signals will be "forwarded" to other functions. The above
blocking outputs are stored in a non-volatile memory.

Line distance protection REL670 789


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

Dependence on operator place GUID-AB327F15-AF44-4ACC-8FA5-2A52AE4AE090 v4


For the commands from a communication protocol, such as IEC 61850-8-1, and through the
inputs L_SEL, L_OPEN and L_CLOSE, the operator place is evaluated, and only the commands
from enabled operator places are accepted, see Table 512. Commands through the inputs
L_SEL, L_OPEN and L_CLOSE are always from the local operator place. For commands through
the inputs AU_OPEN and AU_CLOSE, the operator place is not evaluated. If the operator place is
set to Off, the commands through the inputs AU_OPEN and AU_CLOSE are not accepted.

Interaction with synchrocheck and synchronizing functions M13484-47 v5


The Switch controller (SCSWI) works in conjunction with the synchrocheck and the
synchronizing function (SESRSYN). It is assumed that the synchrocheck function is
continuously in operation and gives the result to SCSWI. The result from the synchrocheck
function is evaluated during the close execution. If the operator performs an override of the
synchrocheck, the evaluation of the synchrocheck state is omitted. When there is a positive
confirmation from the synchrocheck function, SCSWI will send the close signal EXE_CL to the
switch function Circuit breaker (SXCBR).

When there is no positive confirmation from the synchrocheck function, SCSWI will send a
start signal START_SY to the synchronizing function, which will send the closing command to
SXCBR when the synchronizing conditions are fulfilled, see Figure 454. If no synchronizing
function is included, the timer for supervision of the "synchronizing in progress signal" is set
to 0, which means no start of the synchronizing function. SCSWI will then set the attribute
"blocked-by-synchrocheck" in the "cause" signal. See also the time diagram in Figure 458.

SCSWI SXCBR
EXE_CL
OR CLOSE

SYNC_OK
START_SY
CANC_SY
SY_INPRO
SESRSYN

CLOSECB
Synchro Synchronizing
check function

IEC09000209-2-en.vsd
IEC09000209 V2 EN-US

Figure 454: Example of interaction between SCSWI, SESRSYN (synchrocheck and


synchronizing function) and SXCBR function

Time diagrams M13484-51 v7


The Switch controller (SCSWI) function has timers for evaluating different time supervision
conditions. These timers are explained here.

The timer tSelect is used for supervising the time between the select and the execute
command signal, that is, the time the operator has to perform the command execution after
the selection of the object to operate.

790 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

select
execute command
tSelect
timer t1 t1>tSelect, then long-
operation-time in 'cause'
is set

en05000092.vsd
IEC05000092 V1 EN-US

Figure 455: tSelect

The Long-operation-time cause is only given on the output L_CAUSE. It is not


sent on protocols since the selection has already received a positive response,
and no operation has been issued. If an operation is issued after the time out,
the negative response is Object-not-selected.

The parameter tResResponse is used to set the maximum allowed time to make the
reservation, that is, the time between reservation request and the feedback reservation
granted from all bays involved in the reservation function.

select

reservation request RES_RQ

reservation granted RES_GRT


t1>tResResponse, then 1-
tResResponse
of-n-control in 'cause' is
timer t1
set
IEC05000093-2-en.vsd
IEC05000093 V2 EN-US

Figure 456: tResResponse


The timer tExecutionFB supervises the time between the execute command and the command
termination, see Figure 457.

Line distance protection REL670 791


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

execute command

position L1 open

close

position L2 open

close

position L3 open

close

cmd termination L1

cmd termination L2

cmd termination L3

cmd termination *

position open

close

t1>tExecutionFB, then
tExecutionFB timer long-operation-time in
t1 'cause' is set

* The cmd termination will be delayed one execution sample . APCtExecutionFB=IEC0


5000094=2=en=Original
.vsd
IEC05000094 V2 EN-US

Figure 457: tExecutionFB


The parameter tSynchrocheck is used to define the maximum allowed time between the
execute command and the input SYNC_OK to become true. If SYNC_OK=true at the time the
execute command signal is received, the timer "tSynchrocheck" will not start. The start signal
for the synchronizing is obtained if the synchrocheck conditions are not fulfilled.

The parameter tSynchronizing is used to define the maximum allowed time between the start
signal for synchronizing and the confirmation that synchronizing is in progress.

execute command

SYNC_OK

tSynchrocheck
t1
START_SY

SY_INPRO

tSynchronizing t2>tSynchronizing, then


t2 blocked-by-synchrocheck in
'cause' is set

en05000095.vsd
IEC05000095 V1 EN-US

Figure 458: tSynchroCheck and tSynchronizing

15.4.7 Circuit breaker SXCBR IP15614-1 v3

792 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

15.4.7.1 Functionality M13489-3 v6

The purpose of Circuit breaker (SXCBR) is to provide the actual status of positions and to
perform the control operations, that is, pass all the commands to primary apparatuses in the
form of circuit breakers via binary output boards and to supervise the switching operation and
position.

15.4.7.2 Function block M13500-3 v5

SXCBR
BLOCK XPOS
LR_SWI EXE_OP
OPEN EXE_CL
CLOSE SUBSTED
BL_OPEN OP_BLKD
BL_CLOSE CL_BLKD
BL_UPD UPD_BLKD
POSOP EN POSITION
POSCLOSE OPENP OS
CBOPCAP CLOSEPOS
TR_OPEN TR_POS
TR_CLOSE CNT_VAL
RS_CNT L_CAUSE
EEH_WARN EEHEALTH
EEH_ALM CBOPCAP
XIN
IEC05000338-6-en.vsdx
IEC05000338 V6 EN-US

Figure 459: SXCBR function block

15.4.7.3 Signals
PID-6799-INPUTSIGNALS v3

Table 521: SXCBR Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
LR_SWI BOOLEAN 0 Local/Remote switch indication from switchyard
OPEN BOOLEAN 0 Pulsed signal used to immediately open the switch
CLOSE BOOLEAN 0 Pulsed signal used to immediately close the switch
BL_OPEN BOOLEAN 0 Signal to block the open command
BL_CLOSE BOOLEAN 0 Signal to block the close command
BL_UPD BOOLEAN 0 Steady signal for block of the position updating
POSOPEN BOOLEAN 0 Signal for open position of apparatus from I/O
POSCLOSE BOOLEAN 0 Signal for close position of apparatus from I/O
CBOPCAP INTEGER 3 Breaker operating capability 1 = None, 2 = O, 3 = CO, 4 = OCO,
5 = COCO, 6+ = More
TR_OPEN BOOLEAN 0 Signal for open position of truck from I/O
TR_CLOSE BOOLEAN 0 Signal for close position of truck from I/O
RS_CNT BOOLEAN 0 Resets the operation counter
EEH_WARN BOOLEAN 0 Warning from external equipment
EEH_ALM BOOLEAN 0 Alarm from external equipment
XIN GROUP - Execution information from CSWI
SIGNAL

Line distance protection REL670 793


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

PID-6799-OUTPUTSIGNALS v3

Table 522: SXCBR Output signals


Name Type Description
XPOS GROUP SIGNAL Group connection to CSWI for XCBR and XSWI
EXE_OP BOOLEAN Executes the command for open direction
EXE_CL BOOLEAN Executes the command for close direction
SUBSTED BOOLEAN Indication that the position is substituted
OP_BLKD BOOLEAN Indication that the function is blocked for open commands
CL_BLKD BOOLEAN Indication that the function is blocked for close commands
UPD_BLKD BOOLEAN Update of position indication is blocked
POSITION INTEGER Apparatus position indication
OPENPOS BOOLEAN Apparatus open position
CLOSEPOS BOOLEAN Apparatus closed position
TR_POS INTEGER Truck position indication
CNT_VAL INTEGER Operation counter value
L_CAUSE INTEGER Latest value of the error indication during command
EEHEALTH INTEGER External equipment health. 1=No warning or alarm,
2=Warning, 3=Alarm
CBOPCAP INTEGER Breaker operating capability 1 = None, 2 = O, 3 = CO, 4 = OCO,
5 = COCO, 6+ = More

15.4.7.4 Settings
PID-6799-SETTINGS v3

Table 523: SXCBR Non group settings (basic)


Name Values (Range) Unit Step Default Description
tStartMove 0.000 - 60.000 s 0.001 0.100 Supervision time for the apparatus to
move after a command
tIntermediate 0.000 - 60.000 s 0.001 0.150 Allowed time for intermediate
position
AdaptivePulse Not adaptive - - Not adaptive Output resets when a new correct end
Adaptive position is reached
tOpenPulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for open
command
tClosePulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for close
command
InitialCount 0 - 20000 - 1 0 Initial number of operations (Initial
count value)

15.4.7.5 Operation principle


M13487-4 v8
The circuit breaker function (SXCBR) is used by other functions such as, for example, switch
controller, protection functions, autorecloser function or an IEC 61850 client residing in
another IED or the operator place. This switch function executes commands, evaluates block
conditions and evaluates different time supervision conditions. Only if all conditions indicate a
switch operation to be allowed, the function performs the execution command. In case of
erroneous conditions, the function indicates an appropriate "cause" value, see Table 506.

794 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

SXCBR has an operation counter for closing and opening commands. The counter value can be
read remotely from the operator place. The value is reset from local HMI, a binary input or
remotely from the operator place by configuring a signal from the Single Point Generic Control
8 signals (SPC8GAPC) for example. The health of the external equipment, the switch, can be
monitored according to IEC 61850-8-1. The operation counter functionality and the external
equipment health supervision are independent sub-functions of the circuit breaker function.

Local/Remote switch M13487-7 v4


One binary input signal LR_SWI is included in SXCBR to indicate the local/remote switch
position from switchyard provided via the I/O board. If this signal is set to TRUE it means that
change of position is allowed only from switchyard level. If the signal is set to FALSE it means
that command from IED or higher level is permitted. When the signal is set to TRUE all
commands (for change of position) are rejected, even trip commands from protection
functions are rejected. The functionality of the local/remote switch is described in Figure 460.

Local= Operation at
UE switch yard level
TR

From I/O switchLR


FAL
SE
Remote= Operation at
IED or higher level

en05000096.vsd
IEC05000096 V1 EN-US

Figure 460: Local/Remote switch

Blocking principles M13487-12 v6


SXCBR includes several blocking principles. The basic principle for all blocking signals is that
they will affect commands from all other clients for example, switch controller, protection
functions and autoreclosure.

The blocking possibilities are:

• Block/deblock for open command. It is used to block operation for the open command.
• Block/deblock for close command. It is used to block operation for the close command.
• Update block/deblock of positions. It is used to block the updating of position values.
Other signals related to the position will be reset.
• Blocking of function, BLOCK. If BLOCK signal is set, it means that the function is active,
but no outputs are generated, no reporting, control commands are rejected and
functional and configuration data is visible.

The above blocking outputs are stored in a non-volatile memory.

Substitution M13487-22 v5
The substitution part in SXCBR is used for manual set of the position and quality of the switch.
The typical use of substitution is that an operator enters a manual value because that the real
process value is erroneous for some reason. SXCBR will then use the manually entered value
instead of the value for positions determined by the process.

It is always possible to make a substitution, independently of the position


indication and the status information of the I/O board. When substitution is
enabled, the other signals related to the position follow the substituted
position. The substituted values are stored in a non-volatile memory. If the
function is blocked or blocked for update when the substitution is released, the
position value is kept the same as the last substitution value, but the quality is
changed to "questionable, old data", indicating that the value is old and not
reliable.

Line distance protection REL670 795


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

When the position of the SXCBR is substituted, its IEC 61850-8-1 data object is
marked as “substituted", in addition to the substituted quality, but the position
quality of the connected SCSWI is not dependent on the substitution indication
in the quality, so it does not show that it is derived from a substituted value.

Time diagrams M13487-28 v5


There are two timers for supervising of the execute phase, tStartMove and tIntermediate.
tStartMove supervises that the primary device starts moving after the execute output pulse is
sent. tIntermediate defines the maximum allowed time for intermediate position. Figure 461
explains these two timers during the execute phase.

EXE_CL AdaptivePulse = TRUE


Close pulse duration

OPENPOS

CLOSEPOS

if t1 > tStartMove then


tStartMove timer "switch-not-start-moving"
t1 attribute in 'cause' is set
tStartMove

if t2 > tIntermediate then


tIntermediate timer "persisting-intermediate-state"
t2 attribute in 'cause' is set
tIntermediate

en05000097.vsd

IEC05000097 V1 EN-US

Figure 461: The timers tStartMove and tIntermediate


The timers tOpenPulse and tClosePulse are the length of the execute output pulses to be sent
to the primary equipment. Note that the output pulses for open and close command can have
different pulse lengths. The pulses can also be set to be adaptive with the configuration
parameter AdaptivePulse. Figure 462 shows the principle of the execute output pulse. The
AdaptivePulse parameter will have effect on both execute output pulses.

OPENPOS

CLOSEPOS

AdaptivePulse=FALSE
EXE_CL
tClosePulse

AdaptivePulse=TRUE
EXE_CL
tClosePulse
en05000098.vsd
IEC05000098 V1 EN-US

Figure 462: Execute output pulse

796 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

If the pulse is set to be adaptive, it is not possible for the pulse to exceed tOpenPulse or
tClosePulse.

The execute output pulses are reset when:

• the new expected final position is reached and the configuration parameter AdaptivePulse
is set to true
• the timer tOpenPulse or tClosePulse has elapsed
• an error occurs due to the switch does not start moving, that is, tStartMove has elapsed.

If the breaker reaches the final position before the execution pulse time has
elapsed, and AdaptivePulse is not true, the function waits for the end of the
execution pulse before telling the activating function that the command is
completed.

There is one exception to the first item above: if the primary device is in open position and an
open command is executed or if the primary device is in closed position and a close command
is executed. In these cases, with the additional condition that the configuration parameter
AdaptivePulse is true, the execute output pulse is always activated and resets when
tStartMove has elapsed. If the configuration parameter AdaptivePulse is set to false, the
execution output remains active until the pulse duration timer has elapsed.

If the start position indicates bad state (OPENPOS=1 and CLOSEPOS =1) when
a command is executed, the execute output pulse resets only when timer
tOpenPulse or tClosePulse has elapsed.

An example of when a primary device is open and an open command is executed is shown in
Figure 463 .

OPENPOS

CLOSEPOS

EXE_OP AdaptivePulse=FALSE

tOpenPulse

EXE_OP AdaptivePulse=TRUE

tOpenPulse

tStartMove timer

en05000099.vsd
IEC05000099 V1 EN-US

Figure 463: Open command with open position indication

15.4.8 Circuit switch SXSWI IP15620-1 v2

Line distance protection REL670 797


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

15.4.8.1 Functionality M16492-3 v6

The purpose of Circuit switch (SXSWI) function is to provide the actual status of positions and
to perform the control operations, that is, pass all the commands to primary apparatuses in
the form of disconnectors or earthing switches via binary output boards and to supervise the
switching operation and position.

15.4.8.2 Function block M13504-3 v5

SXSWI
BLOCK XPOS
LR_SWI EXE_OP
OPEN EXE_CL
CLOSE SUBSTED
BL_OPEN OP_BLKD
BL_CLOSE CL_BLKD
BL_UPD UPD_BLKD
POSOP EN POSITION
POSCLOSE OPENP OS
SWOPCAP CLOSEPOS
RS_CNT CNT_VAL
EEH_WARN L_CAUSE
EEH_ALM EEHEALTH
XIN SWOPCAP

IEC05000339-5-en.vsdx
IEC05000339 V5 EN-US

Figure 464: SXSWI function block

15.4.8.3 Signals
PID-6800-INPUTSIGNALS v4

Table 524: SXSWI Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
LR_SWI BOOLEAN 0 Local/Remote switch indication from switchyard
OPEN BOOLEAN 0 Pulsed signal used to immediately open the switch
CLOSE BOOLEAN 0 Pulsed signal used to immediately close the switch
BL_OPEN BOOLEAN 0 Signal to block the open command
BL_CLOSE BOOLEAN 0 Signal to block the close command
BL_UPD BOOLEAN 0 Steady signal for block of the position updating
POSOPEN BOOLEAN 0 Signal for open position of apparatus from I/O
POSCLOSE BOOLEAN 0 Signal for close position of apparatus from I/O
SWOPCAP INTEGER 4 Switch operating capability 1 = None, 2 = O, 3 = C, 4 = O and C
RS_CNT BOOLEAN 0 Resets the operation counter
EEH_WARN BOOLEAN 0 Warning from external equipment
EEH_ALM BOOLEAN 0 Alarm from external equipment
XIN GROUP - Execution information from CSWI
SIGNAL

798 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

PID-6800-OUTPUTSIGNALS v4

Table 525: SXSWI Output signals


Name Type Description
XPOS GROUP SIGNAL Group connection to CSWI for XCBR and XSWI
EXE_OP BOOLEAN Executes the command for open direction
EXE_CL BOOLEAN Executes the command for close direction
SUBSTED BOOLEAN Indication that the position is substituted
OP_BLKD BOOLEAN Indication that the function is blocked for open commands
CL_BLKD BOOLEAN Indication that the function is blocked for close commands
UPD_BLKD BOOLEAN Update of position indication is blocked
POSITION INTEGER Apparatus position indication
OPENPOS BOOLEAN Apparatus open position
CLOSEPOS BOOLEAN Apparatus closed position
CNT_VAL INTEGER Operation counter value
L_CAUSE INTEGER Latest value of the error indication during command
EEHEALTH INTEGER External equipment health. 1=No warning or alarm,
2=Warning, 3=Alarm
SWOPCAP INTEGER Switch operating capability 1 = None, 2 = O, 3 = C, 4 = O and C

15.4.8.4 Settings
PID-6800-SETTINGS v4

Table 526: SXSWI Non group settings (basic)


Name Values (Range) Unit Step Default Description
tStartMove 0.000 - 60.000 s 0.001 3.000 Supervision time for the apparatus to
move after a command
tIntermediate 0.000 - 60.000 s 0.001 15.000 Allowed time for intermediate
position
AdaptivePulse Not adaptive - - Not adaptive Output resets when a new correct end
Adaptive position is reached
tOpenPulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for open
command
tClosePulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for close
command
SwitchType Load Break - - Disconnector 1=LoadBreak,2=Disconnector,3=Earth
Disconnector Sw,4=HighSpeedEarthSw
Earthing Switch
HS Earthing
Switch
InitialCount 0 - 20000 - 1 0 Initial number of operations (Initial
count value)

15.4.8.5 Operation principle


M16494-3 v8
The users of the Circuit switch (SXSWI) are other functions such as for example, switch
controller, protection functions, autorecloser function, or a 61850 client residing in another IED
or the operator place. SXSWI executes commands, evaluates block conditions and evaluates
different time supervision conditions. Only if all conditions indicate a switch operation to be

Line distance protection REL670 799


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

allowed, SXSWI performs the execution command. In case of erroneous conditions, the
function indicates an appropriate "cause" value, see Table 506.

SXSWI has an operation counter for closing and opening commands. The counter value can be
read remotely from the operator place. The value is reset from a binary input or remotely from
the operator place by configuring a signal from the Single Point Generic Control 8 signals
(SPC8GAPC), for example.

Also, the health of the external equipment, the switch, can be monitored according to IEC
61850-8-1.

Local/Remote switch M16494-6 v4


One binary input signal LR_SWI is included in SXSWI to indicate the local/remote switch
position from switchyard provided via the I/O board. If this signal is set to TRUE it means that
change of position is allowed only from switchyard level. If the signal is set to FALSE it means
that command from IED or higher level is permitted. When the signal is set to TRUE all
commands (for change of position) from internal IED clients are rejected, even trip commands
from protection functions are rejected. The functionality of the local/remote switch is
described in Figure 465.

Local= Operation at
UE switch yard level
TR

From I/O switchLR


FAL
SE
Remote= Operation at
IED or higher level

en05000096.vsd
IEC05000096 V1 EN-US

Figure 465: Local/Remote switch

Blocking principles M16494-11 v6


SXSWI includes several blocking principles. The basic principle for all blocking signals is that
they will affect commands from all other clients for example, switch controller, protection
functions and autorecloser.

The blocking possibilities are:

• Block/deblock for open command. It is used to block operation for open command.
• Block/deblock for close command. It is used to block operation for close command.
• Update block/deblock of positions. It is used to block the updating of position values.
Other signals related to the position will be reset.
• Blocking of function, BLOCK. If BLOCK signal is set, it means that the function is active,
but no outputs are generated, no reporting, control commands are rejected and
functional and configuration data is visible.

The above blocking outputs are stored in a non-volatile memory.

Substitution M16494-21 v7
The substitution part in SXSWI is used for manual set of the position and quality of the switch.
The typical use of substitution is that an operator enters a manual value because the real
process value is erroneous of some reason. SXSWI will then use the manually entered value
instead of the value for positions determined by the process.

800 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

It is always possible to make a substitution, independently of the position


indication and the status information of the I/O board. When substitution is
enabled, the other signals related to the position follow the substituted
position. The substituted values are stored in a non-volatile memory. If the
function is blocked or blocked for update when the substitution is released, the
position value is kept the same as the last substitution value, but the quality is
changed to "questionable, old data", indicating that the value is old and not
reliable.

When the position of the SXSWI is substituted, its IEC 61850-8-1 data object is
marked as “substituted", in addition to the substituted quality, but the position
quality of the connected SCSWI is not dependent on the substitution indication
in the quality, so it does not show that it is derived from a substituted value.

Time diagrams M16494-26 v6


There are two timers for supervising of the execute phase, tStartMove and tIntermediate.
tStartMove supervises that the primary device starts moving after the execute output pulse is
sent. tIntermediate defines the maximum allowed time for intermediate position. Figure 466
explains these two timers during the execute phase.

EXE_CL AdaptivePulse = TRUE


Close pulse duration

OPENPOS

CLOSEPOS

if t1 > tStartMove then


tStartMove timer "switch-not-start-moving"
t1 attribute in 'cause' is set
tStartMove

if t2 > tIntermediate then


tIntermediate timer "persisting-intermediate-state"
t2 attribute in 'cause' is set
tIntermediate

en05000097.vsd

IEC05000097 V1 EN-US

Figure 466: The timers tStartMove and tIntermediate


The timers tOpenPulse and tClosePulse are the length of the execute output pulses to be sent
to the primary equipment. Note that the output pulses for open and close command can have
different pulse lengths. The pulses can also be set to be adaptive with the configuration
parameter AdaptivePulse. Figure 467 shows the principle of the execute output pulse. The
AdaptivePulse parameter will have effect on both execute output pulses.

Line distance protection REL670 801


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

OPENPOS

CLOSEPOS

AdaptivePulse=FALSE
EXE_CL
tClosePulse

AdaptivePulse=TRUE
EXE_CL
tClosePulse
en05000098.vsd
IEC05000098 V1 EN-US

Figure 467: Execute output pulse


If the pulse is set to be adaptive, it is not possible for the pulse to exceed tOpenPulse or
tClosePulse.

The execute output pulses are reset when:

• the new expected final position is reached and the configuration parameter AdaptivePulse
is set to true
• the timer tOpenPulse or tClosePulse has elapsed
• an error occurs due to the switch does not start moving, that is, tStartMove has elapsed.

If the controlled primary device reaches the final position before the execution
pulse time has elapsed, and AdaptivePulse is not true, the function waits for
the end of the execution pulse before telling the activating function that the
command is completed.

There is one exception from the first item above. If the primary device is in open position and
an open command is executed or if the primary device is in close position and a close
command is executed. In these cases, with the additional condition that the configuration
parameter AdaptivePulse is true, the execute output pulse is always activated and resets when
tStartMove has elapsed. If the configuration parameter AdaptivePulse is set to false the
execution output remains active until the pulse duration timer has elapsed.

If the start position indicates bad state (OPENPOS=1 and CLOSEPOS =1) when
a command is executed the execute output pulse resets only when timer
tOpenPulse or tClosePulse has elapsed.

An example when a primary device is open and an open command is executed is shown in
Figure 468.

802 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

OPENPOS

CLOSEPOS

EXE_OP AdaptivePulse=FALSE

tOpenPulse

EXE_OP AdaptivePulse=TRUE

tOpenPulse

tStartMove timer

en05000099.vsd
IEC05000099 V1 EN-US

Figure 468: Open command with open position indication

15.4.9 Proxy for signals from switching device via GOOSE XLNPROXY

15.4.9.1 Functionality GUID-11F9CA1C-8E20-489B-822B-34DACC59553A v1

The proxy for signals from switching device via GOOSE (XLNPROXY) gives an internal
representation of the position status and control response for a switch modelled in a breaker
IED. This representation is identical to that of an SXCBR or SXSWI function.

15.4.9.2 Function block GUID-408513CD-A87E-45E8-8E44-24E153947F02 v1

XLNPROXY
BEH* XPOS
BEH_VALID* SELECTED
LOC* OP_BLKD
LOC_VALID* CL_BLKD
BLKOPN* OPENPOS
BLKOPN_V* CLOSEPOS
BLKCLS* CNT_VAL
BLKCLS_V* L_CAUSE
POSVAL* EEHEALTH
POSVAL_V* OPCAP
OPCNT*
OP_CNT_V*
BLK
BLK_VAL
STSELD
STSELD_V
OPRCVD
OPRCVD_V
OPOK
OPOK_VAL
EEHEALTH
EEH_VAL
OPCAP
OPCAP_V
COMMVALID
XIN

IEC16000043-1-en.vsdx
IEC16000043 V1 EN-US

Figure 469: XLNPROXY function block

Line distance protection REL670 803


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

15.4.9.3 Signals
PID-6712-INPUTSIGNALS v3

Table 527: XLNPROXY Input signals


Name Type Default Description
BEH INTEGER -1 Behaviour
BEH_VLD BOOLEAN 0 Valid data on BEH input
LOC BOOLEAN 0 Local control behaviour
LOC_VLD BOOLEAN 0 Valid data on LOC input
BLKOPN BOOLEAN 0 Block opening
BLKOPN_VLD BOOLEAN 0 Valid data on BLKOPN input
BLKCLS BOOLEAN 0 Block closing
BLKCLS_VLD BOOLEAN 0 Valid data on BLKCLS input
POSVAL INTEGER 0 Switch position, Pos.stVal
POSVAL_VLD BOOLEAN 0 Valid data on POSVAL input
OPCNT INTEGER -1 Operation counter
OPCNT_VLD BOOLEAN 0 Valid data on OPCNT input
BLK BOOLEAN 0 Dynamic blocking of function described by the LN
BLK_VLD BOOLEAN 0 Valid data on BLK input
STSELD BOOLEAN 0 The controllable data is in the status "selected”
STSELD_VLD BOOLEAN 0 Valid data on STSELD input
OPRCVD BOOLEAN 0 Operate command for a controllable data object received
OPRCVD_VLD BOOLEAN 0 Valid data on OPRCVD input
OPOK BOOLEAN 0 Operate command for a controllable data object accepted
OPOK_VLD BOOLEAN 0 Valid data on OPOK input
EEHEALTH INTEGER -1 External equipment health
EEHEALTH_VLD BOOLEAN 0 Valid data on EEHEALTH input
OPCAP INTEGER -1 Operating capability
OPCAP_VLD BOOLEAN 0 Valid data on OPCAP input
COMMVALID BOOLEAN 0 Communication valid
XIN GROUP - Execution information from CSWI
SIGNAL

PID-6712-OUTPUTSIGNALS v3

Table 528: XLNPROXY Output signals


Name Type Description
XPOS GROUP SIGNAL Group connection to CSWI
SELECTED BOOLEAN Select conditions are fulfilled
OP_BLKD BOOLEAN Indication that the function is blocked for open commands
CL_BLKD BOOLEAN Indication that the function is blocked for close commands
OPENPOS BOOLEAN Apparatus open position
CLOSEPOS BOOLEAN Apparatus closed position
CNT_VAL INTEGER Operation counter value
Table continues on next page

804 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

Name Type Description


L_CAUSE INTEGER Latest value of the error indication during command
EEHEALTH INTEGER External equipment health. 1=No warning or alarm,
2=Warning, 3=Alarm
OPCAP INTEGER Switch / breaker operating capability

15.4.9.4 Settings
PID-6712-SETTINGS v3

Table 529: XLNPROXY Non group settings (basic)


Name Values (Range) Unit Step Default Description
SwitchType Circuit Breaker - - Circuit Breaker 0 = CB, 1 = Load Break, 2 =
Load Break Disconnector, 3 = Earthing Switch, 4 =
Disconnector High Speed Earthing Switch
Earthing Switch
HS Earth Switch
tStartMove 0.000 - 60.000 s 0.001 0.100 Supervision time for the apparatus to
move after a command
tIntermediate 0.000 - 60.000 s 0.001 0.150 Allowed time for intermediate
position

GUID-A4CCC681-D4D8-4534-905D-1D8AD40E923B v1

The default values of the inputs BEH, OPCNT, EEHEALTH and OPCAP are set to
-1 to denote that they are not connected.

15.4.9.5 Operation principle GUID-D2679E0E-ABB5-46F0-AD9C-F6E8E8099534 v1

The proxy for signals from switching device via GOOSE (XLNPROXY) is intended to be used
when the switch (XCBR/XSWI) is modelled and controlled in a breaker IED or similar unit on the
process bus. XLNPROXY packages the signals from the GOOSE receive function, normally
GOOSEXLNRCV, into the same format as used from SXCBR and SXSWI to SCSWI. It makes a
similar evaluation of the command response as SXCBR and SXSWI when a command is issued
from the connected SCSWI.

15.4.9.6 Position supervision GUID-95C72346-A577-4F0A-8584-8E1593B9B947 v1

XLNPROXY has two outputs for position indication: OPENPOS and CLOSEPOS. Position is a
double point indication and the OPENPOS and CLOSEPOS are binary outputs intended to be
used for condition logics to protection and control functions

Normally, the position outputs, OPENPOS and CLOSEPOS, follow the value of the input
POSVAL. However, if the POSVAL_V input is FALSE, the communication is lost (COMMVALID =
FALSE), or the quality of the position received is bad, the OPENPOS and CLOSEPOS are both
set to FALSE.

15.4.9.7 Command response evaluation GUID-A2CDC1AE-A6F5-478B-B6E5-3442C54212D8 v1

The command evaluation is triggered through the group input XIN that is connected to the
SCSWI function controlling the switch.

Line distance protection REL670 805


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

If an operation is initiated by the SCSWI, the XLNPROXY function checks if the switch is
blocked for the operation direction and that the position moves to the desired position within
the two time limits tStartMove and tIntermediate. The default values for tStartMove and
tIntermediate are for a breaker. The typical values for a disconnector are:

• tStartMove = 3s
• tIntermediate = 15s

In most cases, tStartMove and tIntermediate can be set to the same values as
in the source XCBR or XSWI function. However, if the time limits are set very
close to the actual movement times of the apparatus, compensation may be
needed for the communication delays and differences in cycle time of the
XLNPROXY function and the source function. The compensation should be in
the range of 0 - 5ms.

When the switch has started moving, it issues a response to the SCSWI function that the
operation has started. If it does not start moving within tStartMove, the command is deemed
as failed, and a cause is raised on the L_CAUSE output and sent to the SCSWI. The different
causes it can identify are listed in order of priority in table 1. The detection of the different
ways of blocking is done while waiting for movement of the switch, but the cause is not given
until the tStartMove has elapsed.

Table 530: Possible cause values from XLNPROXY


Cause No Cause Description Conditions
8 Blocked-by-Mode The BEH input is 5.
2 Blocked-by-switching- The LOC input indicates that only local commands
hierarchy are allowed for the breaker IED function.
-24 Blocked-for-open-cmd The BLKOPN is active indicating that the switch is
blocked for open commands.
-25 Blocked-for-close-cmd The BLKCLS is active indicating that the switch is
blocked for close commands.
9 Blocked-by-process If the Blk input is connected and active indicating
that the switch is dynamically blocked. Or if the
OPCAP input is connected, it indicates that the
operation capability of the switch is not enough to
perform the command.
5 Position-reached Switch is already in the intended position.
-31 Switch-not-start-moving Switch did not start moving within tStartMove.
-32 Persistent-intermediate-state The switch stopped in intermediate state for longer
than tIntermediate.
-33 Switch-returned-to-init-pos Switch returned to the initial position.
-34 Switch-in-bad-state Switch is in a bad position.
-35 Not-expected-final-position Switch did not reach the expected final position.

The L_CAUSE output keeps its output value until a new command sequence has been started.

If the quality of the position or the communication becomes bad, the command evaluation
replaces the uncertain position value with intermediate position. Thus, as long as the quality is
bad, all commands will result in the cause Persistant-intermediate-state, -32.

If the switch in the merging unit has the behaviour set to Test or Test blocked, when the
IED has the behaviour On or Blocked, all data from the switch is regarded as invalid. Thus, any
command will fail with the cause PersistantiIntermediate-state, -32, and if selection is used for

806 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

the switch, all attempts to select the connected SCSWI will fail with the cause Select-failed, 3,
from the SCSWI.

It is possible to speed up the command response for when the command has been started by
the switch in the breaker IED by connecting the inputs OPOK and OPOK_VAL. Then the
blocking check is only done until OPOK is activated and confirmation of that the command has
been started is given to the SCSWI function.

If the inputs STSELD and STSELD_V are connected, the switch in the breaker IED is assumed to
use selection. Then the SCSWI will wait for a selected indication, STSELD input of XLNPROXY,
before accepting selection, this information is transferred to the SCSWI function from the
XLNPROXY through the group connection XPOS. If STSELD is not activated within tSelect of
the SCSWI function, the selection is deemed failed and it gives a negative selection
acknowledgement to the command issuer with the cause Select-failed. Further, if the
communication is lost, or the data received is deemed invalid, the selection will also fail with
cause Select-failed from the SCSWI.

15.4.10 Bay reserve QCRSV IP15629-1 v2

15.4.10.1 Functionality M13506-3 v5

The purpose of the reservation (QCRSV) function is primarily to transfer interlocking


information between IEDs in a safe way and to prevent double operation in a bay, switchyard
part, or complete substation.

15.4.10.2 Function block M13509-3 v3

QCRSV
EXCH_IN RES_GRT1
RES_RQ1 RES_GRT2
RES_RQ2 RES_GRT3
RES_RQ3 RES_GRT4
RES_RQ4 RES_GRT5
RES_RQ5 RES_GRT6
RES_RQ6 RES_GRT7
RES_RQ7 RES_GRT8
RES_RQ8 RES_BAYS
BLOCK ACK_TO_B
OVERRIDE RESERVED
RES_DATA EXCH_OUT
IEC05000340-3-en.vsdx
IEC05000340 V3 EN-US

Figure 470: QCRSV function block

15.4.10.3 Signals
PID-3561-INPUTSIGNALS v7

Table 531: QCRSV Input signals


Name Type Default Description
EXCH_IN INTEGER 0 Used for exchange signals between different BayRes blocks
RES_RQ1 BOOLEAN 0 Signal for app. 1 that requests to do a reservation
RES_RQ2 BOOLEAN 0 Signal for app. 2 that requests to do a reservation
RES_RQ3 BOOLEAN 0 Signal for app. 3 that requests to do a reservation
RES_RQ4 BOOLEAN 0 Signal for app. 4 that requests to do a reservation
RES_RQ5 BOOLEAN 0 Signal for app. 5 that requests to do a reservation
Table continues on next page

Line distance protection REL670 807


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

Name Type Default Description


RES_RQ6 BOOLEAN 0 Signal for app. 6 that requests to do a reservation
RES_RQ7 BOOLEAN 0 Signal for app. 7 that requests to do a reservation
RES_RQ8 BOOLEAN 0 Signal for app. 8 that requests to do a reservation
BLOCK BOOLEAN 0 Reservation is not possible and the output signals are reset
OVERRIDE BOOLEAN 0 Signal to override the reservation
RES_DATA INTEGER 0 Reservation data coming from function block ResIn

PID-3561-OUTPUTSIGNALS v7

Table 532: QCRSV Output signals


Name Type Description
RES_GRT1 BOOLEAN Reservation is made and the app. 1 is allowed to operate
RES_GRT2 BOOLEAN Reservation is made and the app. 2 is allowed to operate
RES_GRT3 BOOLEAN Reservation is made and the app. 3 is allowed to operate
RES_GRT4 BOOLEAN Reservation is made and the app. 4 is allowed to operate
RES_GRT5 BOOLEAN Reservation is made and the app. 5 is allowed to operate
RES_GRT6 BOOLEAN Reservation is made and the app. 6 is allowed to operate
RES_GRT7 BOOLEAN Reservation is made and the app. 7 is allowed to operate
RES_GRT8 BOOLEAN Reservation is made and the app. 8 is allowed to operate
RES_BAYS BOOLEAN Request for reservation of other bays
ACK_TO_B BOOLEAN Acknowledge to other bays that this bay is reserved
RESERVED BOOLEAN Indicates that the bay is reserved
EXCH_OUT INTEGER Used for exchange signals between different BayRes blocks

15.4.10.4 Settings
PID-3561-SETTINGS v7

Table 533: QCRSV Non group settings (basic)


Name Values (Range) Unit Step Default Description
tCancelRes 0.000 - 60.000 s 0.001 10.000 Supervision time for canceling the
reservation
ParamRequest1 Other bays res. - - Only own bay res. Reservation of the own bay only, at
Only own bay res. selection of apparatus 1
ParamRequest2 Other bays res. - - Only own bay res. Reservation of the own bay only, at
Only own bay res. selection of apparatus 2
ParamRequest3 Other bays res. - - Only own bay res. Reservation of the own bay only, at
Only own bay res. selection of apparatus 3
ParamRequest4 Other bays res. - - Only own bay res. Reservation of the own bay only, at
Only own bay res. selection of apparatus 4
ParamRequest5 Other bays res. - - Only own bay res. Reservation of the own bay only, at
Only own bay res. selection of apparatus 5
ParamRequest6 Other bays res. - - Only own bay res. Reservation of the own bay only, at
Only own bay res. selection of apparatus 6
ParamRequest7 Other bays res. - - Only own bay res. Reservation of the own bay only, at
Only own bay res. selection of apparatus 7
ParamRequest8 Other bays res. - - Only own bay res. Reservation of the own bay only, at
Only own bay res. selection of apparatus 8

808 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

15.4.10.5 Operation principle


M13505-4 v3
The Bay reserve (QCRSV) function handles the reservation. QCRSV function starts to operate in
two ways. It starts when there is a request for reservation of the own bay or if there is a
request for reservation from another bay. It is only possible to reserve the function if it is not
currently reserved. The signal that can reserve the own bay is the input signal RES_RQx (x=1-8)
coming from switch controller (SCWI). The signals for request from another bay are the
outputs RE_RQ_B and V_RE_RQ from function block RESIN. These signals are included in signal
EXCH_OUT from RESIN and are connected to RES_DATA in QCRSV.

The parameters ParamRequestx (x=1-8) are chosen at reservation of the own bay only (TRUE)
or other bays (FALSE). To reserve the own bay only means that no reservation request
RES_BAYS is created.

Reservation request of own bay M13505-7 v2


If the reservation request comes from the own bay, the function QCRSV has to know which
apparatus the request comes from. This information is available with the input signal RES_RQx
and parameter ParamRequestx (where x=1-8 is the number of the requesting apparatus). In
order to decide if a reservation request of the current bay can be permitted QCRSV has to
know whether the own bay already is reserved by itself or another bay. This information is
available in the output signal RESERVED.

If the RESERVED output is not set, the selection is made with the output RES_GRTx (where
x=1-8 is the number of the requesting apparatus), which is connected to switch controller
SCSWI. If the bay already is reserved the command sequence will be reset and the SCSWI will
set the attribute "1-of-n-control" in the "cause" signal.

Reservation of other bays M13505-11 v2


When the function QCRSV receives a request from an apparatus in the own bay that requires
other bays to be reserved as well, it checks if it already is reserved. If not, it will send a request
to the other bays that are predefined (to be reserved) and wait for their response
(acknowledge). The request of reserving other bays is done by activating the output
RES_BAYS.

When it receives acknowledge from the bays via the input RES_DATA, it sets the output
RES_GRTx (where x=1-8 is the number of the requesting apparatus). If not acknowledgement
from all bays is received within a certain time defined in SCSWI (tResResponse), the SCSWI will
reset the reservation and set the attribute "1-of-n-control" in the "cause" signal.

Reservation request from another bay M13505-15 v2


When another bay requests for reservation, the input BAY_RES in corresponding function block
RESIN is activated. The signal for reservation request is grouped into the output signal
EXCH_OUT in RESIN, which is connected to input RES_DATA in QCRSV. If the bay is not
reserved, the bay will be reserved and the acknowledgment from output ACK_T_B is sent back
to the requested bay. If the bay already is reserved the reservation is kept and no
acknowledgment is sent.

Blocking and overriding of reservation M13505-18 v4


If QCRSV function is blocked (input BLOCK is set to true) the reservation is blocked. That is, no
reservation can be made from the own bay or any other bay. This can be set, for example, via a
binary input from an external device to prevent operations from another operator place at the
same time.

The reservation function can also be overridden in the own bay with the OVERRIDE input
signal, that is, reserving the own bay without waiting for the external acknowledge.

Bay with more than eight apparatuses M13505-22 v6


If only one instance of QCRSV is used for a bay that is, use of up to eight apparatuses, the
input EXCH_IN must be set to zero.

Line distance protection REL670 809


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

If there are more than eight apparatuses in the bay, there has to be one additional QCRSV. The
two QCRSV functions have to communicate and this is done through the input EXCH_IN and
EXCH_OUT according to Figure 471. If more than one QCRSV are used, the execution order is
very important. The execution order must be in the way that the first QCRSV has a lower
number than the next one.

QCRSV
EXCH_IN RES_GRT1
RES_RQ1 RES_GRT2
RES_RQ2 RES_GRT3
RES_RQ3 RES_GRT4
RES_RQ4 RES_GRT5
RES_RQ5 RES_GRT6
RES_RQ6 RES_GRT7
RES_RQ7 RES_GRT8
RES_RQ8 RES_BAYS
BLOCK ACK_TO_B
OVERRIDE RESERVED
RES_DATA EXCH_OUT

QCRSV
EXCH_IN RES_GRT1
RES_RQ1 RES_GRT2
RES_BAYS
RES_RQ2 RES_GRT3 1
RES_RQ3 RES_GRT4
RES_RQ4 RES_GRT5
RES_RQ5 RES_GRT6 ACK_TO_B
RES_RQ6 RES_GRT7 1
RES_RQ7 RES_GRT8
RES_RQ8 RES_BAYS

1
BLOCK ACK_TO_B RESERVED
OVERRIDE RESERVED
RES_DATA EXCH_OUT

IEC05000088-3-en.vsdx
IEC05000088 V3 EN-US

Figure 471: Connection of two QCRSV function blocks

15.4.11 Reservation input RESIN IP15650-1 v2

15.4.11.1 Functionality M16501-3 v5

The Reservation input (RESIN) function receives the reservation information from other bays.
The number of instances is the same as the number of involved bays (up to 60 instances are
available).

15.4.11.2 Function block M13512-3 v3

RESIN1
BAY_ACK ACK_F_B
BAY_VAL ANY_ACK
BAY_RES VALID_TX
RE_RQ_B
V_RE_RQ
EXCH_OUT

IEC05000341-2-en.vsd
IEC05000341 V2 EN-US

Figure 472: RESIN1 function block

810 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

RESIN2
EXCH_IN ACK_F_B
BAY_ACK ANY_ACK
BAY_VAL VALID_TX
BAY_RES RE_RQ_B
V_RE_RQ
EXCH_OUT
IEC09000807_1_en.vsd
IEC09000807 V1 EN-US

Figure 473: RESIN2 function block

15.4.11.3 Signals
PID-3629-INPUTSIGNALS v7

Table 534: RESIN1 Input signals


Name Type Default Description
BAY_ACK BOOLEAN 0 Another bay has acknow. the reservation req. from this bay
BAY_VAL BOOLEAN 0 The reserv. and acknow. signals from another bay are valid
BAY_RES BOOLEAN 0 Request from other bay to reserve this bay

PID-3629-OUTPUTSIGNALS v7

Table 535: RESIN1 Output signals


Name Type Description
ACK_F_B BOOLEAN All other bays have acknow. the reserv. req. from this bay
ANY_ACK BOOLEAN Any other bay has acknow. the reserv. req. from this bay
VALID_TX BOOLEAN The reserv. and acknow. signals from other bays are valid
RE_RQ_B BOOLEAN Request from other bay to reserve this bay
V_RE_RQ BOOLEAN Check if the request of reserving this bay is valid
EXCH_OUT INTEGER Used for exchange signals between different ResIn blocks

PID-3630-INPUTSIGNALS v7

Table 536: RESIN2 Input signals


Name Type Default Description
EXCH_IN INTEGER 5 Used for exchange signals between different ResIn blocks
BAY_ACK BOOLEAN 0 Another bay has acknow. the reservation req. from this bay
BAY_VAL BOOLEAN 0 The reserv. and acknow. signals from another bay are valid
BAY_RES BOOLEAN 0 Request from other bay to reserve this bay

PID-3630-OUTPUTSIGNALS v7

Table 537: RESIN2 Output signals


Name Type Description
ACK_F_B BOOLEAN All other bays have acknow. the reserv. req. from this bay
ANY_ACK BOOLEAN Any other bay has acknow. the reserv. req. from this bay
VALID_TX BOOLEAN The reserv. and acknow. signals from other bays are valid
RE_RQ_B BOOLEAN Request from other bay to reserve this bay
V_RE_RQ BOOLEAN Check if the request of reserving this bay is valid
EXCH_OUT INTEGER Used for exchange signals between different ResIn blocks

Line distance protection REL670 811


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

15.4.11.4 Settings
PID-3629-SETTINGS v7

Table 538: RESIN1 Non group settings (basic)


Name Values (Range) Unit Step Default Description
FutureUse Bay in use - - Bay in use The bay for this ResIn block is for
Bay future use future use

PID-3630-SETTINGS v7

Table 539: RESIN2 Non group settings (basic)


Name Values (Range) Unit Step Default Description
FutureUse Bay in use - - Bay in use The bay for this ResIn block is for
Bay future use future use

15.4.11.5 Operation principle M16503-3 v6

The reservation input (RESIN) function is based purely on Boolean logic conditions. The logic
diagram in Figure 474 shows how the output signals are created. The inputs of the function
block are connected to a receive function block representing signals transferred over the
station bus from another bay.

EXCH_IN INT

BIN

ACK_F_B
&
FutureUse
³1

ANY_ACK
BAY_ACK ³1

VALID_TX
&

BAY_VAL ³1

RE_RQ_B
³1

BAY_RES &
V _RE_RQ
³1

BIN
EXCH_OUT
INT

en05000089.vsd
IEC05000089 V1 EN-US

Figure 474: Logic diagram for RESIN


Figure 475 describes the principle of the data exchange between all RESIN modules in the
current bay. There is one RESIN function block per "other bay" used in the reservation

812 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

mechanism. The output signal EXCH_OUT in the last RESIN functions are connected to the
module bay reserve (QCRSV) that handles the reservation function in the own bay.

RESIN
BAY_ACK ACK_F_B
Bay 1 BAY_VAL ANY_ACK
BAY_RES VALID_TX
RE_RQ_B
V_RE_RQ
EXCH_OUT

RESIN
EXCH_IN ACK_F_B
BAY_ACK ANY_ACK
Bay 2 BAY_VAL VALID_TX
BAY_RES RE_RQ_B
V_RE_RQ
EXCH_OUT

RESIN
EXCH_IN ACK_F_B
BAY_ACK ANY_ACK
Bay n BAY_VAL VALID_TX
BAY_RES RE_RQ_B QCRSV
V_RE_RQ
EXCH_OUT RES_DATA

en05000090.vsd
IEC05000090 V2 EN-US

Figure 475: Diagram of the chaining principle for RESIN

15.5 Logic rotating switch for function selection and LHMI


presentation SLGAPC SEMOD114936-1 v5

15.5.1 Identification
SEMOD167845-2 v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Logic rotating switch for function SLGAPC - -
selection and LHMI presentation

15.5.2 Functionality SEMOD114908-4 v11

The logic rotating switch for function selection and LHMI presentation (SLGAPC) (or the
selector switch function block) is used to get an enhanced selector switch functionality
compared to the one provided by a hardware selector switch. Hardware selector switches are
used extensively by utilities, in order to have different functions operating on pre-set values.
Hardware switches are however sources for maintenance issues, lower system reliability and
an extended purchase portfolio. The selector switch function eliminates all these problems.

Line distance protection REL670 813


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

15.5.3 Function block SEMOD114954-4 v6

SLGAPC
BLOCK ^P01
PSTO ^P02
UP ^P03
DOWN ^P04
^P05
^P06
^P07
^P08
^P09
^P10
^P11
^P12
^P13
^P14
^P15
^P16
^P17
^P18
^P19
^P20
^P21
^P22
^P23
^P24
^P25
^P26
^P27
^P28
^P29
^P30
^P31
^P32
SWPOSN

IEC14000005-1-en.vsd
IEC14000005 V1 EN-US

Figure 476: SLGAPC function block

15.5.4 Signals
PID-6641-INPUTSIGNALS v3

Table 540: SLGAPC Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
PSTO INTEGER 0 Operator place selection
UP BOOLEAN 0 Binary "UP" command
DOWN BOOLEAN 0 Binary "DOWN" command

PID-6641-OUTPUTSIGNALS v3

Table 541: SLGAPC Output signals


Name Type Description
P01 BOOLEAN Selector switch position 1
P02 BOOLEAN Selector switch position 2
P03 BOOLEAN Selector switch position 3
P04 BOOLEAN Selector switch position 4
P05 BOOLEAN Selector switch position 5
P06 BOOLEAN Selector switch position 6
P07 BOOLEAN Selector switch position 7
Table continues on next page

814 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

Name Type Description


P08 BOOLEAN Selector switch position 8
P09 BOOLEAN Selector switch position 9
P10 BOOLEAN Selector switch position 10
P11 BOOLEAN Selector switch position 11
P12 BOOLEAN Selector switch position 12
P13 BOOLEAN Selector switch position 13
P14 BOOLEAN Selector switch position 14
P15 BOOLEAN Selector switch position 15
P16 BOOLEAN Selector switch position 16
P17 BOOLEAN Selector switch position 17
P18 BOOLEAN Selector switch position 18
P19 BOOLEAN Selector switch position 19
P20 BOOLEAN Selector switch position 20
P21 BOOLEAN Selector switch position 21
P22 BOOLEAN Selector switch position 22
P23 BOOLEAN Selector switch position 23
P24 BOOLEAN Selector switch position 24
P25 BOOLEAN Selector switch position 25
P26 BOOLEAN Selector switch position 26
P27 BOOLEAN Selector switch position 27
P28 BOOLEAN Selector switch position 28
P29 BOOLEAN Selector switch position 29
P30 BOOLEAN Selector switch position 30
P31 BOOLEAN Selector switch position 31
P32 BOOLEAN Selector switch position 32
SWPOSN INTEGER Switch position (integer)

15.5.5 Settings
PID-6641-SETTINGS v3

Table 542: SLGAPC Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
NrPos 2 - 32 - 1 32 Number of positions in the switch
OutType Pulsed - - Steady Output type, steady or pulse
Steady
tPulse 0.000 - 60.000 s 0.001 0.200 Operate pulse duration, in [s]
tDelay 0.000 - s 0.010 0.000 Time delay on the output, in [s]
60000.000
StopAtExtremes Disabled - - Disabled Stop when min or max position is
Enabled reached

Line distance protection REL670 815


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

15.5.6 Monitored data


PID-6641-MONITOREDDATA v3

Table 543: SLGAPC Monitored data


Name Type Values (Range) Unit Description
SWPOSN INTEGER - - Switch position (integer)

15.5.7 Operation principle


SEMOD114931-4 v8
The logic rotating switch for function selection and LHMI presentation (SLGAPC) function has
two operating inputs – UP and DOWN. When a signal is received on the UP input, the function
will activate the output next to the present activated output, in ascending order (for example
if the present activated output is P03 and one activates the UP input then the output P04 will
be activated). When a signal is received on the DOWN input, the function will activate the
output next to the present activated output, in descending order (for example if the present
activated output is P03 and one activates the DOWN input then the output P02 will be
activated). Depending on the output settings the output signals can be steady or pulsed. In
case of steady signals, the output will be active till the time it receives next operation of UP/
DOWN inputs. Also, depending on the settings one can have a time delay between activation of
the UP or DOWN input signals and the output activation.

Besides the inputs visible in the application configuration in the Application Configuration
Tool, there are other possibilities that will allow an user to set the desired position directly
(without activating the intermediate positions), either locally or remotely, using a “select
before execute” dialog. One can block the function operation, by activating the BLOCK input.
In this case, the present position will be kept and further operation will be blocked. The
operator place (local or remote) is specified through the PSTO input. If any operation is
allowed the signal INTONE from the Fixed signal function block can be connected. SLGAPC
function block has also an integer value output, that generates the actual position number.
The positions and the block names are fully settable by the user. These names will appear in
the menu, so the user can see the position names instead of a number.

15.5.7.1 Graphical display SEMOD114931-35 v4

There are two possibilities for SLGAPC

• if it is used just for the monitoring, the switches will be listed with their actual position
names, as defined by the user (max. 13 characters).
• if it is used for control, the switches will be listed with their actual positions, but only the
first three letters of the name will be used.

In both cases, the switch full name will be shown, but the user has to redefine it when building
the Graphical Display Editor, under the "Caption". If used for the control, the following
sequence of commands will ensure:

816 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

From the graphical display:

Control
Control Sing le Line Diagram
Measurements Comma nds
Events
Disturb ance r eco rds
Settings
Diagno stics
Test
Chang e to the "Switche s" pag e Reset
of the SLD by left-righ t arrows. Authori zation
Sele ct switch by up-down Lan guage
arro ws

../Control/SLD/Switch
O I ../Control/SLD/Switch

SMBRREC control SMBRREC control


WFM Sele ct switch. Pre ss the
WFM
I or O key. A dialo g b ox
Pilo t se tup app ears.
Pilo t se tup
OFF OFF

Damage control
P: Disc N: Disc Fe
DAL
The pos will not b e mod ified
(outputs will not b e activa ted) unt il OK Cancel
you press the Enter button for O.K.

../Control/SLD/Switch

SMBRREC control
WFM

Pilo t se tup
OFF

Damage control
DFW

IEC06000421-3-en.vsdx
IEC06000421 V3 EN-US

Figure 477: Example 2 on handling the switch from the local HMI.
From the single line diagram on local HMI.

15.6 Selector mini switch VSGAPC SEMOD158754-1 v3

15.6.1 Identification
SEMOD167850-2 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Selector mini switch VSGAPC - 43

15.6.2 Functionality SEMOD158756-5 v10

The Selector mini switch (VSGAPC) function block is a multipurpose function used for a variety
of applications, as a general purpose switch.

Line distance protection REL670 817


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

VSGAPC can be controlled from the menu, from a symbol on the single line diagram (SLD) on
the local HMI or from Binary inputs.

15.6.3 Function block SEMOD158768-4 v3

VSGAPC
BLOCK BLOCKED
PSTO POSITION
IPOS1 POS1
IPOS2 POS2
CMDPOS12
CMDPOS21

IEC14000066-1-en.vsd
IEC14000066 V1 EN-US

Figure 478: VSGAPC function block

15.6.4 Signals
PID-6504-INPUTSIGNALS v6

Table 544: VSGAPC Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
PSTO INTEGER 0 Operator place selection
IPOS1 BOOLEAN 0 Position 1 indicating input
IPOS2 BOOLEAN 0 Position 2 indicating input

PID-6504-OUTPUTSIGNALS v6

Table 545: VSGAPC Output signals


Name Type Description
BLOCKED BOOLEAN The function is active but the functionality is blocked
POSITION INTEGER Position indication, integer
POS1 BOOLEAN Position 1 indication, logical signal
POS2 BOOLEAN Position 2 indication, logical signal
CMDPOS12 BOOLEAN Execute command from position 1 to position 2
CMDPOS21 BOOLEAN Execute command from position 2 to position 1

15.6.5 Settings
PID-6504-SETTINGS v6

Table 546: VSGAPC Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
CtlModel Dir Norm - - Dir Norm Specifies the type for control model
SBO Enh according to IEC 61850
Mode Steady - - Pulsed Operation mode
Pulsed
tSelect 0.000 - 60.000 s 0.001 30.000 Max time between select and execute
signals
tPulse 0.000 - 60.000 s 0.001 0.200 Command pulse lenght

818 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

15.6.6 Operation principle SEMOD158762-4 v7

Selector mini switch (VSGAPC) function can be used for double purpose, in the same way as
switch controller (SCSWI) functions are used:

• for indication on the single line diagram (SLD). Position is received through the IPOS1 and
IPOS2 inputs and distributed in the configuration through the POS1 and POS2 outputs, or
to IEC 61850 through reporting, or GOOSE.
• for commands that are received via the local HMI or IEC 61850 and distributed in the
configuration through outputs CMDPOS12 and CMDPOS21.
The output CMDPOS12 is set when the function receives a CLOSE command from the local
HMI when the SLD is displayed and the object is chosen.
The output CMDPOS21 is set when the function receives an OPEN command from the local
HMI when the SLD is displayed and the object is chosen.

It is important for indication in the SLD that a symbol is associated with a


controllable object, otherwise the symbol won't be displayed on the screen. A
symbol is created and configured in GDE tool in PCM600.

The PSTO input is connected to the Local remote switch to have a selection of operators place,
operation from local HMI (Local) or through IEC 61850 (Remote). An INTONE connection from
Fixed signal function block (FXDSIGN) will allow operation from local HMI.

As it can be seen, both indications and commands are done in double-bit representation,
where a combination of signals on both inputs/outputs generate the desired result.

The following table shows the relationship between IPOS1/IPOS2 inputs and the name of the
string that is shown on the SLD. The value of the strings are set in PST.

IPOS1 IPOS2 Name of displayed string Default string value


0 0 PosUndefined P00
1 0 Position1 P01
0 1 Position2 P10
1 1 PosBadState P11

15.7 Generic communication function for Double Point


indication DPGAPC SEMOD55384-1 v4

15.7.1 Identification
GUID-E16EA78F-6DF9-4B37-A92D-5C09827E2297 v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Generic communication function for DPGAPC - -
Double Point indication

Line distance protection REL670 819


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

15.7.2 Functionality SEMOD55850-5 v7

Generic communication function for Double Point indication (DPGAPC) function block is used
to send double point position indications to other systems, equipment or functions in the
substation through IEC 61850-8-1 or other communication protocols. It is especially intended
to be used in the interlocking station-wide logics.

15.7.3 Function block SEMOD54710-4 v5

IEC13000081 V1 EN-US

Figure 479: DPGAPC function block

15.7.4 Signals SEMOD55883-1 v2

PID-4139-INPUTSIGNALS v12

Table 547: DPGAPC Input signals


Name Type Default Description
OPEN BOOLEAN 0 Open indication
CLOSE BOOLEAN 0 Close indication
VALID BOOLEAN 0 Valid indication

PID-4139-OUTPUTSIGNALS v11

Table 548: DPGAPC Output signals


Name Type Description
POSITION INTEGER Double point indication

15.7.5 Settings ABBD8E283863 v4

The function does not have any parameters available in the local HMI or PCM600.

15.7.6 Operation principle SEMOD55861-5 v7

When receiving the input signals, DPGAPC sends the signals over IEC 61850-8-1 to the systems,
equipment or functions that requests and thus subscribes on these signals. To be able to get
the signals into other systems, equipment or functions, one must use other tools, described in
the Engineering manual, and define which function block in which systems, equipment or
functions should receive this information.

More specifically, DPGAPC function reports a combined double point position indication
output POSITION, by evaluating the value and the timestamp attributes of the inputs OPEN
and CLOSE, together with the logical input signal VALID.

When the input signal VALID is active, the values of the OPEN and CLOSE inputs determine the
two-bit integer value of the output POSITION. The timestamp of the output POSITION will have
the latest updated timestamp of the inputs OPEN and CLOSE.

820 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

When the input signal VALID is inactive, DPGAPC function forces the position to intermediated
state.

When the value of the input signal VALID changes, the timestamp of the output POSITION will
be updated as the time when DPGAPC function detects the change.

Refer to Table 549 for the description of the input-output relationship in terms of the value
and the quality attributes.

Table 549: Description of the input-output relationship


POSITION
VALID OPEN CLOSE
Value Description
0 - - 0 Intermediate
1 0 0 0 Intermediate
1 1 0 1 Open
1 0 1 2 Closed
1 1 1 3 Bad State

15.8 Single point generic control 8 signals SPC8GAPC SEMOD176448-1 v3

15.8.1 Identification
SEMOD176456-2 v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Single point generic control 8 signals SPC8GAPC - -

15.8.2 Functionality SEMOD176462-4 v11

The Single point generic control 8 signals (SPC8GAPC) function block is a collection of 8 single
point commands that can be used for direct commands for example reset of LEDs or putting
IED in "ChangeLock" state from remote. In this way, simple commands can be sent directly to
the IED outputs, without confirmation. Confirmation (status) of the result of the commands is
supposed to be achieved by other means, such as binary inputs and SPGAPC function blocks.
The commands can be pulsed or steady with a settable pulse time.

15.8.3 Function block SEMOD176479-4 v5

SPC8GAPC
BLOCK ^OUT1
PSTO ^OUT2
^OUT3
^OUT4
^OUT5
^OUT6
^OUT7
^OUT8

IEC07000143-3-en.vsd
IEC07000143 V3 EN-US

Figure 480: SPC8GAPC function block

Line distance protection REL670 821


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

15.8.4 Signals
PID-3575-INPUTSIGNALS v8

Table 550: SPC8GAPC Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Blocks the function operation
PSTO INTEGER 1 Operator place selection

PID-3575-OUTPUTSIGNALS v8

Table 551: SPC8GAPC Output signals


Name Type Description
OUT1 BOOLEAN Command output 1
OUT2 BOOLEAN Command output 2
OUT3 BOOLEAN Command output 3
OUT4 BOOLEAN Command output 4
OUT5 BOOLEAN Command output 5
OUT6 BOOLEAN Command output 6
OUT7 BOOLEAN Command output 7
OUT8 BOOLEAN Command output 8

15.8.5 Settings
PID-3575-SETTINGS v8

Table 552: SPC8GAPC Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
PulseMode1 Pulsed - - Pulsed Setting for pulsed/latched mode for
Latched output 1
tPulse1 0.01 - 6000.00 s 0.01 0.10 Pulse time output 1
PulseMode2 Pulsed - - Pulsed Setting for pulsed/latched mode for
Latched output 2
tPulse2 0.01 - 6000.00 s 0.01 0.10 Pulse time output 2
PulseMode3 Pulsed - - Pulsed Setting for pulsed/latched mode for
Latched output 3
tPulse3 0.01 - 6000.00 s 0.01 0.10 Pulse time output 3
PulseMode4 Pulsed - - Pulsed Setting for pulsed/latched mode for
Latched output 4
tPulse4 0.01 - 6000.00 s 0.01 0.10 Pulse time output 4
PulseMode5 Pulsed - - Pulsed Setting for pulsed/latched mode for
Latched output 5
tPulse5 0.01 - 6000.00 s 0.01 0.10 Pulse time output 5
PulseMode6 Pulsed - - Pulsed Setting for pulsed/latched mode for
Latched output 6
tPulse6 0.01 - 6000.00 s 0.01 0.10 Pulse time output 6
PulseMode7 Pulsed - - Pulsed Setting for pulsed/latched mode for
Latched output 7
Table continues on next page

822 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

Name Values (Range) Unit Step Default Description


tPulse7 0.01 - 6000.00 s 0.01 0.10 Pulse time output 7
PulseMode8 Pulsed - - Pulsed Setting for pulsed/latched mode for
Latched output 8
tPulse8 0.01 - 6000.00 s 0.01 0.10 Pulse time output 8

15.8.6 Operation principle SEMOD176471-4 v7

The PSTO input selects the operator place (LOCAL, REMOTE or ALL). One of the eight outputs
is activated based on the command sent from the operator place selected. The settings
Latchedx and tPulsex (where x is the respective output) will determine if the signal will be
pulsed (and how long the pulse is) or latched (steady). BLOCK will block the operation of the
function – in case a command is sent, no output will be activated.

PSTO is the universal operator place selector for all control functions. Although,
PSTO can be configured to use LOCAL or ALL operator places, only REMOTE
operator place is used in SPC8GAPC function.

15.9 AutomationBits, command function for DNP3.0


AUTOBITS SEMOD158589-1 v3

15.9.1 Identification
GUID-C3BB63F5-F0E7-4B00-AF0F-917ECF87B016 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
AutomationBits, command function
AUTOBITS - -
for DNP3

15.9.2 Functionality SEMOD158591-5 v8

Automation bits function for DNP3 (AUTOBITS) is used within PCM600 to get into the
configuration of the commands coming through the DNP3 protocol. The AUTOBITS function
plays the same role as functions GOOSEBINRCV (for IEC 61850) and MULTICMDRCV (for LON).

Line distance protection REL670 823


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

15.9.3 Function block SEMOD158603-4 v3

AUTOBITS
BLOCK ^CMDBIT1
PSTO ^CMDBIT2
^CMDBIT3
^CMDBIT4
^CMDBIT5
^CMDBIT6
^CMDBIT7
^CMDBIT8
^CMDBIT9
^CMDBIT10
^CMDBIT11
^CMDBIT12
^CMDBIT13
^CMDBIT14
^CMDBIT15
^CMDBIT16
^CMDBIT17
^CMDBIT18
^CMDBIT19
^CMDBIT20
^CMDBIT21
^CMDBIT22
^CMDBIT23
^CMDBIT24
^CMDBIT25
^CMDBIT26
^CMDBIT27
^CMDBIT28
^CMDBIT29
^CMDBIT30
^CMDBIT31
^CMDBIT32

IEC09000925-1-en.vsd
IEC09000925 V1 EN-US

Figure 481: AUTOBITS function block

15.9.4 Signals
PID-3776-INPUTSIGNALS v6

Table 553: AUTOBITS Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
PSTO INTEGER 0 Operator place selection

PID-3776-OUTPUTSIGNALS v6

Table 554: AUTOBITS Output signals


Name Type Description
CMDBIT1 BOOLEAN Command out bit 1
CMDBIT2 BOOLEAN Command out bit 2
CMDBIT3 BOOLEAN Command out bit 3
CMDBIT4 BOOLEAN Command out bit 4
CMDBIT5 BOOLEAN Command out bit 5
CMDBIT6 BOOLEAN Command out bit 6
CMDBIT7 BOOLEAN Command out bit 7
CMDBIT8 BOOLEAN Command out bit 8
CMDBIT9 BOOLEAN Command out bit 9
CMDBIT10 BOOLEAN Command out bit 10
Table continues on next page

824 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

Name Type Description


CMDBIT11 BOOLEAN Command out bit 11
CMDBIT12 BOOLEAN Command out bit 12
CMDBIT13 BOOLEAN Command out bit 13
CMDBIT14 BOOLEAN Command out bit 14
CMDBIT15 BOOLEAN Command out bit 15
CMDBIT16 BOOLEAN Command out bit 16
CMDBIT17 BOOLEAN Command out bit 17
CMDBIT18 BOOLEAN Command out bit 18
CMDBIT19 BOOLEAN Command out bit 19
CMDBIT20 BOOLEAN Command out bit 20
CMDBIT21 BOOLEAN Command out bit 21
CMDBIT22 BOOLEAN Command out bit 22
CMDBIT23 BOOLEAN Command out bit 23
CMDBIT24 BOOLEAN Command out bit 24
CMDBIT25 BOOLEAN Command out bit 25
CMDBIT26 BOOLEAN Command out bit 26
CMDBIT27 BOOLEAN Command out bit 27
CMDBIT28 BOOLEAN Command out bit 28
CMDBIT29 BOOLEAN Command out bit 29
CMDBIT30 BOOLEAN Command out bit 30
CMDBIT31 BOOLEAN Command out bit 31
CMDBIT32 BOOLEAN Command out bit 32

15.9.5 Settings
PID-3776-SETTINGS v6

Table 555: AUTOBITS Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On

15.9.6 Operation principle SEMOD158597-4 v5

AutomationBits function (AUTOBITS) has 32 individual outputs which each can be mapped as a
Binary Output point in DNP3. The output is operated by a "Object 12" in DNP3. This object
contains parameters for control-code, count, on-time and off-time. To operate an AUTOBITS
output point, send a control-code of latch-On, latch-Off, pulse-On, pulse-Off, Trip or Close. The
remaining parameters will be regarded were appropriate. ex: pulse-On, on-time=100, off-
time=300, count=5 would give 5 positive 100 ms pulses, 300 ms apart.

There is a BLOCK input signal, which will disable the operation of the function, in the same way
the setting Operation: On/Off does. That means that, upon activation of the BLOCK input, all
32 CMDBITxx outputs will be set to 0. The BLOCK acts like an overriding, the function still
receives data from the DNP3 master. Upon deactivation of BLOCK, all the 32 CMDBITxx
outputs will be set by the DNP3 master again, momentarily. For AUTOBITS , the PSTO input

Line distance protection REL670 825


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 506 370-UEN J
Control

determines the operator place. The command can be written to the block while in “Remote”. If
PSTO is in “Local” then no change is applied to the outputs.

15.10 Single command, 16 signals SINGLECMD SEMOD119849-1 v2

15.10.1 Identification
GUID-2217CCC2-5581-407F-A4BC-266CD6808984 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Single command, 16 signals SINGLECMD - -

15.10.2 Functionality M12446-6 v5

The IEDs can receive commands either from a substation automation system or from the local
HMI. The command function block has outputs that can be used, for example, to control high
voltage apparatuses or for other user defined functionality.

15.10.3 Function block SEMOD116040-4 v2

SINGLECMD
BLOCK ^OUT1
^OUT2
^OUT3
^OUT4
^OUT5
^OUT6
^OUT7
^OUT8
^OUT9
^OUT10
^OUT11
^OUT12
^OUT13
^OUT14
^OUT15
^OUT16

IEC05000698-2-en.vsd
IEC05000698 V3 EN-US

Figure 482: SINGLECMD function block

15.10.4 Signals
PID-6189-INPUTSIGNALS v7

Table 556: SINGLECMD Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block single command function

826 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 15
Control

PID-6189-OUTPUTSIGNALS v7

Table 557: SINGLECMD Output signals


Name Type Description
OUT1 BOOLEAN Single command output 1
OUT2 BOOLEAN Single command output 2
OUT3 BOOLEAN Single command output 3
OUT4 BOOLEAN Single command output 4
OUT5 BOOLEAN Single command output 5
OUT6 BOOLEAN Single command output 6
OUT7 BOOLEAN Single command output 7
OUT8 BOOLEAN Single command output 8
OUT9 BOOLEAN Single command output 9
OUT10 BOOLEAN Single command output 10
OUT11 BOOLEAN Single command output 11
OUT12 BOOLEAN Single command output 12
OUT13 BOOLEAN Single command output 13
OUT14 BOOLEAN Single command output 14
OUT15 BOOLEAN Single command output 15
OUT16 BOOLEAN Single command output 16

15.10.5 Settings
PID-6189-SETTINGS v7

Table 558: SINGLECMD Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
Steady
Pulsed

15.10.6 Operation principle M12447-3 v3

Single command, 16 signals (SINGLECMD) function has 16 binary output signals. The outputs
can be individually controlled from a substation automation system or from the local HMI.
Each output signal can be given a name with a maximum of 13 characters in PCM600.

The output signals can be of the types Off, Steady, or Pulse. This configuration setting is done
via the local HMI or PCM600 and is common for the whole function block. The length of the
output pulses are 100 ms. In steady mode, SINGLECMD function has a memory to remember
the output values at power interruption of the IED. Also a BLOCK input is available used to
block the updating of the outputs.

The output signals, OUT1 to OUT16, are available for configuration to built-in functions or via
the configuration logic circuits to the binary outputs of the IED.

Line distance protection REL670 827


Technical manual
© Copyright 2017 ABB. All rights reserved
828
1MRK 506 370-UEN J Section 16
Scheme communication

Section 16 Scheme communication


16.1 Scheme communication logic for distance or
overcurrent protection ZCPSCH IP15749-1 v3

16.1.1 Identification
M14854-1 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Scheme communication logic for ZCPSCH - 85
distance or overcurrent protection

16.1.2 Functionality M13860-3 v11

To achieve instantaneous fault clearance for all line faults, scheme communication logic is
provided. All types of communication schemes for permissive underreaching, permissive
overreaching, blocking, delta based blocking, unblocking and intertrip are available.

The built-in communication module (LDCM) can be used for scheme communication signaling
when included.

16.1.3 Function block M13866-3 v7

ZCPSCH
I3P* TRIP
U3P* CS
BLOCK CHSTOP
BLKTR CRL
BLKCS LCG
CSBLK
CACC
CSOR
CSUR
CR
CRG
CBOPEN

IEC09000004

IEC09000004 V4 EN-US

Figure 483: ZCPSCH function block

Line distance protection REL670 829


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 506 370-UEN J
Scheme communication

16.1.4 Signals
PID-3766-INPUTSIGNALS v7

Table 559: ZCPSCH Input signals


Name Type Default Description
I3P GROUP - Current group connection
SIGNAL
U3P GROUP - Voltage group connection
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Signal for block of trip output from communication logic
BLKCS BOOLEAN 0 Block of carrier send in permissive OR and blocking schemes
CSBLK BOOLEAN 0 Reverse directed distance protection zone signal
CACC BOOLEAN 0 Permissive distance protection zone signal
CSOR BOOLEAN 0 Overreaching distance protection zone signal
CSUR BOOLEAN 0 Underreaching distance protection zone signal
CR BOOLEAN 0 Carrier Signal Received
CRG BOOLEAN 0 Carrier guard signal received
CBOPEN BOOLEAN 0 Indicates that the breaker is open

PID-3766-OUTPUTSIGNALS v5

Table 560: ZCPSCH Output signals


Name Type Description
TRIP BOOLEAN Trip output
CS BOOLEAN Carrier Send signal
CHSTOP BOOLEAN Stops the blocking signal to remote end
CRL BOOLEAN Carrier signal received or missing carrier guard signal
LCG BOOLEAN Loss of carrier guard signal

16.1.5 Settings
PID-3766-SETTINGS v7

Table 561: ZCPSCH Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
SchemeType Intertrip - - Permissive UR Scheme type
Permissive UR
Permissive OR
Blocking
DeltaBlocking
tCoord 0.000 - 60.000 s 0.001 0.035 Co-ordination time for blocking
communication scheme
tSendMin 0.000 - 60.000 s 0.001 0.100 Minimum duration of a carrier send
signal

830 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 16
Scheme communication

Table 562: ZCPSCH Group settings (advanced)


Name Values (Range) Unit Step Default Description
Unblock Off - - Off Operation mode of unblocking logic
NoRestart
Restart
DeltaI 0 - 200 %IB 1 10 Current change level in % of IBase for
fault inception detection
DeltaU 0 - 100 %UB 1 5 Voltage change level in % of UB for
fault inception detection
Delta3I0 0 - 200 %IB 1 10 Zero seq current change level in % of
IBase
Delta3U0 0 - 100 %UB 1 5 Zero seq voltage change level in % of
UBase
tSecurity 0.000 - 60.000 s 0.001 0.035 Security timer for loss of carrier guard
detection

Table 563: ZCPSCH Non group settings (advanced)


Name Values (Range) Unit Step Default Description
GlobalBaseSelector 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

16.1.6 Operation principle


M13893-3 v5
Depending on whether a reverse or forward directed impedance zone is used to issue the send
signal, the communication schemes are divided into blocking and permissive schemes,
respectively.

A permissive scheme is inherently faster and has better security against false tripping than a
blocking scheme. On the other hand, a permissive scheme depends on a received signal for a
fast trip, so its dependability is lower than that of a blocking scheme.

16.1.6.1 Blocking scheme M13893-6 v7

The principle of operation for a blocking scheme is that an overreaching zone is allowed to trip
instantaneously after the settable co-ordination time tCoord has elapsed, when no signal is
received from the remote IED.

The received signal, which shall be connected to CR, is used to block the zone to be accelerated
to clear the fault instantaneously (after time tCoord). The forward overreaching zone to be
accelerated is connected to the input CACC, see figure 484.

In case of external faults, the blocking signal (CR) must be received before the settable timer
tCoord elapses to prevent a false trip, see figure 484.

The function can be totally blocked by activating the input BLOCK. Tripping can be blocked by
activating the input BLKTR. Signal send can be blocked by activating the input BLKCS.

tCoord
CACC
t TRIP
CR AND

en05000512.vsd
IEC05000512 V1 EN-US

Figure 484: Basic logic for trip signal in blocking scheme

Line distance protection REL670 831


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 506 370-UEN J
Scheme communication

Channels for communication in each direction must be available.

16.1.6.2 Delta blocking scheme GUID-22E3BFAC-82E9-4434-B761-AD63BCFC68D5 v2

In order to avoid delays due to carrier coordination times, the initiation of sending of blocking
signal to remote end is done by a fault inception detection element based on delta quantities
of currents and voltages. The delta based fault detection is very fast and if the channel is fast
there is no need for delaying the operation of the remote distance element. The received
blocking signal arrives well before the distance element has started. If the fault is in forward
direction the sending is immediately stopped by a forward directed distance, directional
current or directional earth fault element.

The fault inception detection element detects instantaneous changes in any phase currents or
zero sequence current in combination with a change in the corresponding phase voltage or
zero sequence voltage. The criterion for the fault inception detection is if the change of any
phase voltage and current exceeds the settings DeltaU and DeltaI respectively, or if the change
of zero sequence voltage and zero sequence current exceeds the settings Delta3U0,Delta3I0
respectively. The schemeType is selected as DeltaBlocking.

If the fault inception function has detected a system fault, a block signal CS will be issued and
sent to remote end in order to block the overreaching zones. Different criteria has to be
fulfilled for sending the CS signal:

1. The breaker has to be in closed condition, that is, the input signal CBOPEN is deactivated.
2. A fault inception should have been detected while the carrier send signal is not blocked,
that is, the input signal BLKCS is not activated.

If it is later detected that it was an internal fault that made the function issue the CS signal,
the function will issue a CHSTOP signal to unblock the remote end.

The received signal, which is connected to the CR input, is not used to accelerate the release of
the overreaching zone to clear the fault instantaneously. The overreaching zone to be
accelerated is connected to the input CACC, see Figure 485.

In case of external faults, the blocking signal (CR) must be received before the settable timer
tCoord elapses, to prevent a false trip, see Figure 485.

The function can be totally blocked by activating the input BLOCK, block of trip by activating
the input BLKTR, block of carrier send by activating the input BLKCS.

tCoord
CACC
t TRIP
CR AND

en05000512.vsd
IEC05000512 V1 EN-US

Figure 485: Basic logic for trip signal in delta blocking scheme
Channels for communication in each direction must be available.

16.1.6.3 Permissive underreaching scheme M13893-13 v6

In a permissive underreaching scheme, a forward directed underreaching measuring element


(normally zone1) sends a permissive signal CS to the remote end if a fault is detected.in
forward direction. The received signal CR is used to allow an overreaching zone to trip after the
tCoord timer has elapsed. The tCoord in permissive underreaching schemes is normally set to
zero.

The logic for trip signal in permissive scheme is shown in figure 486.

832 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 16
Scheme communication

tCoord
CACC
t TRIP
CR AND

en05000513.vsd
IEC05000513 V1 EN-US

Figure 486: Logic for trip signal in permissive scheme


The function can be totally blocked by activating the input BLOCK. Tripping can be blocked by
activating the input BLKTR. Signal send can be blocked by activating the input BLKCS.

16.1.6.4 Permissive overreaching scheme M13893-22 v6

In a permissive overreaching scheme, a forward directed overreaching measuring element


(normally zone2) sends a permissive signal CS to the remote end if a fault is detected in
forward direction. The received signal CR is used to allow an overreaching zone to trip after the
settable tCoord timer has elapsed. The tCoord in permissive overreaching schemes is normally
set to zero.

The logic for trip signal in permissive scheme is shown in figure 486.

tCoord
CACC
t TRIP
CR AND

en05000513.vsd
IEC05000513 V1 EN-US

Figure 487: Logic for trip signal in permissive scheme


The function can be totally blocked by activating the input BLOCK. Tripping can be blocked by
activating the input BLKTR. Signal send can be blocked by activating the input BLKCS.e.

16.1.6.5 Unblocking scheme M13893-31 v8

In unblocking scheme, the lower dependability of a permissive scheme is overcome by using


the loss of guard signal from the communication equipment to locally create a receive signal. It
is common or suitable to use the function when older, less reliable power-line carrier (PLC)
communication is used.

The unblocking function uses a guard signal CRG, which must always be present, even when no
CR signal is received. The absence of the CRG signal for a time longer than the setting
tSecurity time is used as a CR signal, see figure 488. This enables a permissive scheme to
operate when the line fault blocks the signal transmission. The CRG signal is only used in
unblocking schemes.

The received signal created by the unblocking function is reset 150 ms after the security timer
has elapsed. When that occurs an output signal LCG is activated for signalling purpose. The
unblocking function is reset 200 ms after that the guard signal is present again.

Line distance protection REL670 833


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 506 370-UEN J
Scheme communication

CR
tSecurity CRL
t OR

CRG
200 ms 150 ms
t OR t AND
AND
LCG

IEC05000746-2-en.vsd
IEC05000746 V2 EN-US

Figure 488: Guard signal logic with unblocking scheme and with setting Unblock = Restart

CR
CRL
tSecurity OR
CRG t

IEC11000253-2-en.vsd
IEC11000253 V2 EN-US

Figure 489: Guard signal logic with unblocking scheme and with setting Unblock =
NoRestart
The unblocking function can be set in three operation modes (setting Unblock):

Off The unblocking function is out of operation


No restart Communication failure shorter than tSecurity will be ignored
If CRG disappears a CRL signal will be transferred to the trip logic
There will not be any information in case of communication failure (LCG)
Restart Communication failure shorter than tSecurity will be ignored
It sends a defined (150 ms) CRL after the disappearance of the CRG signal
The function will activate LCG output in case of communication failure
If the communication failure comes and goes (<200 ms) there will not be
recurrent signalling

16.1.6.6 Intertrip scheme M13893-36 v5

In the direct intertrip scheme, the send signal CS is sent from an underreaching zone that is
tripping the line.

The received signal CR is directly transferred to a trip for tripping without local criteria. The
signal is further processed in the tripping logic.

In case of single-pole tripping in multi-phase systems, a phase selection is performed.

16.1.6.7 Simplified logic diagram M13893-40 v4

The simplified logic diagram for the complete logic is shown in figure 490.

834 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 16
Scheme communication

Unblock =Off

CR

Unblock =
OR CRL
NoRestart AND
CRL
Unblock =
tSecurit
Restart
y
CRG 1 t AND

200 ms 150 ms LCG


AND
t OR AND t

SchemeType =
Intertrip

CSUR
tSendMi
n AND
OR

BLOCK AND
CSBLK OR
CRL

Schemetype =
Permissive UR AND CS
OR

tCoord
AND 25 ms
OR
t TRIP
CACC t

Schemetype =
Permissive OR

CSOR OR AND

AND
tSendMin
OR
AND
SchemeType =
Blocking

BLKCS

AND

IEC05000515-2-en.vsd
IEC05000515 V2 EN-US

Figure 490: Scheme communication logic for distance or overcurrent protection,


simplified logic diagram

16.1.7 Technical data


M16038-1 v14

Table 564: ZCPSCH technical data


Function Range or value Accuracy
Scheme type Off -
Intertrip
Permissive UR
Permissive OR
Blocking
DeltaBlocking
Operate voltage, Delta U (0–100)% of UBase ±5.0% of ΔU
Operate current, Delta I (0–200)% of IBase ±5.0% of ΔI
Table continues on next page

Line distance protection REL670 835


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 506 370-UEN J
Scheme communication

Function Range or value Accuracy


Operate zero sequence voltage, (0–100)% of UBase ±10.0% of Δ3U0
Delta 3U0
Operate zero sequence current, (0–200)% of IBase ±10.0% of Δ3I0
Delta 3I0
Co-ordination time for blocking (0.000-60.000) s ±0.2% or ±15 ms whichever is
communication scheme greater
Minimum duration of a carrier (0.000-60.000) s ±0.2% or ±45 ms whichever is
send signal greater
Security timer for loss of guard (0.000-60.000) s ±0.2% or ±15 ms whichever is
signal detection greater
Operation mode of unblocking Off -
logic NoRestart
Restart

16.2 Phase segregated scheme communication logic for


distance protection ZC1PPSCH SEMOD141690-1 v2

16.2.1 Identification
SEMOD141699-2 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Phase segregated Scheme ZC1PPSCH - 85
communication logic for distance
protection

16.2.2 Functionality SEMOD141686-4 v3

Communication between line ends is used to achieve fault clearance for all faults on a power
line. All possible types of communication schemes for example, permissive underreach,
permissive overreach and blocking schemes are available. To manage problems with
simultaneous faults on parallel power lines phase segregated communication is needed. This
will then replace the standard Scheme communication logic for distance or Overcurrent
protection (ZCPSCH) on important lines where three communication channels (in each
subsystem) are available for the distance protection communication.

The main purpose of the Phase segregated scheme communication logic for distance
protection (ZC1PPSCH) function is to supplement the distance protection function such that:

• fast clearance of faults is also achieved at the line end for which the faults are on the part
of the line not covered by its underreaching zone.
• correct phase selection can be maintained to support single-pole tripping for faults
occurring anywhere on the entire length of a double circuit line.

To accomplish this, three separate communication channels, that is, one per phase, each
capable of transmitting a signal in each direction is required.

ZC1PPSCH can be completed with the current reversal and WEI logic for phase segregated
communication, when found necessary in Blocking and Permissive overreaching schemes.

836 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 16
Scheme communication

16.2.3 Function block SEMOD155566-4 v2

ZC1PPSCH
BLOCK TRIP
BLKTR TRL1
BLKTRL1 TRL2
BLKTRL2 TRL3
BLKTRL3 CSL1
CACCL1 CSL2
CACCL2 CSL3
CACCL3 CSMPH
CSURL1 CRLL1
CSURL2 CRLL2
CSURL3 CRLL3
CSORL1
CSORL2
CSORL3
CSBLKL1
CSBLKL2
CSBLKL3
BLKCSL1
BLKCSL2
BLKCSL3
CRL1
CRL2
CRL3
CRMPH

IEC06000427-2-en.vsd
IEC06000427 V2 EN-US

Figure 491: ZC1PPSCH function block

16.2.4 Signals
PID-3523-INPUTSIGNALS v5

Table 565: ZC1PPSCH Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Common signal for block of trip output from communication
logic in all phases
BLKTRL1 BOOLEAN 0 Signal for block of trip output from communication logic in
Phase L1
BLKTRL2 BOOLEAN 0 Signal for block of trip output from communication logic in
Phase L2
BLKTRL3 BOOLEAN 0 Signal for block of trip output from communication logic in
Phase L3
CACCL1 BOOLEAN 0 Accelerated Distance protection zone start in Phase L1
CACCL2 BOOLEAN 0 Accelerated Distance protection zone signal in Phase L2
CACCL3 BOOLEAN 0 Accelerated Distance protection zone signal in Phase L3
CSURL1 BOOLEAN 0 Underreaching distance protection zone signal in Phase L1
CSURL2 BOOLEAN 0 Underreaching distance protection zone signal in Phase L2
CSURL3 BOOLEAN 0 Underreaching distance protection zone signal in Phase L3
CSORL1 BOOLEAN 0 Overreaching distance protection zone signal in Phase L1
CSORL2 BOOLEAN 0 Overreaching distance protection zone signal in Phase L2
CSORL3 BOOLEAN 0 Overreaching distance protection zone signal in Phase L3
CSBLKL1 BOOLEAN 0 Reverse directed distance protection zone signal in Phase L1
CSBLKL2 BOOLEAN 0 Reverse directed distance protection zone signal in Phase L2
CSBLKL3 BOOLEAN 0 Reverse directed distance protection zone signal in Phase L3
BLKCSL1 BOOLEAN 0 Block of carrier send in POR and Blocking schemes in Phase L1
Table continues on next page

Line distance protection REL670 837


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 506 370-UEN J
Scheme communication

Name Type Default Description


BLKCSL2 BOOLEAN 0 Block of carrier send in POR and Blocking schemes in Phase
L2
BLKCSL3 BOOLEAN 0 Block of carrier send in POR and Blocking schemes in Phase
L3
CRL1 BOOLEAN 0 Carrier signal received in Phase L1
CRL2 BOOLEAN 0 Carrier signal received in Phase L2
CRL3 BOOLEAN 0 Carrier signal received in Phase L3
CRMPH BOOLEAN 0 Carrier Signal received for multiphase fault

PID-3523-OUTPUTSIGNALS v6

Table 566: ZC1PPSCH Output signals


Name Type Description
TRIP BOOLEAN Common trip output in any of the phase
TRL1 BOOLEAN Trip output in Phase L1
TRL2 BOOLEAN Trip output in Phase L2
TRL3 BOOLEAN Trip output in Phase L3
CSL1 BOOLEAN Carrier Send in phase L1
CSL2 BOOLEAN Carrier Send in phase L2
CSL3 BOOLEAN Carrier Send in phase L3
CSMPH BOOLEAN carrier Send for multi phase fault
CRLL1 BOOLEAN Carrier signal received in Phase L1
CRLL2 BOOLEAN Carrier signal received in Phase L2
CRLL3 BOOLEAN Carrier signal received in Phase L3

16.2.5 Settings
PID-3523-SETTINGS v5

Table 567: ZC1PPSCH Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation On / Off
On
Scheme Type Off - - Permissive UR Scheme type
Intertrip
Permissive UR
Permissive OR
Blocking
tCoord 0.000 - 60.000 s 0.001 0.000 Trip coordinate time
tSendMin 0.000 - 60.000 s 0.001 0.100 Minimum duration of Carrier Send
signal

16.2.6 Operation principle


SEMOD141705-4 v2
Depending on whether a reverse or forward directed impedance zone is used to issue the send
signal, the communication schemes are divided into Blocking and Permissive schemes,
respectively.

838 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 16
Scheme communication

A permissive scheme is inherently faster and has better security against false tripping than a
blocking scheme. On the other hand, a permissive scheme depends on a received signal for a
fast trip, so its dependability is lower than that of a blocking scheme.

The Phase segregated scheme communication logic for distance protection (ZC1PPSCH)
function is a logical function built-up from logical elements. It is a supplementary function to
the distance protection, requiring for its operation inputs from the distance protection and
the communication equipment.

The type of communication-aided scheme to be used can be selected by way of the settings.

The ability to select which distance protection zone is assigned to which input of ZC1PPSCH
makes this logic able to support practically any scheme communication requirements
regardless of their basic operating principle. The outputs to initiate tripping and sending of
the teleprotection signal are given in accordance with the type of communication-aided
scheme selected and the zone(s) and phase(s) of the distance protection which have operated.

When power line carrier communication channels are used for permissive schemes
communication, unblocking logic which uses the loss of guard signal as a receive criteria is
provided. This logic compensates for the lack of dependability due to the transmission of the
command signal over the faulted line.

16.2.6.1 Blocking scheme SEMOD141705-12 v2

The principle of operation for a blocking scheme is that an overreaching zone is allowed to trip
instantaneously after the settable co-ordination time tCoord has elapsed, when no signal is
received from the remote IED. The received signal (sent by a reverse looking element in the
remote IED), which shall be connected to CRLx, is used to not release the zone to be
accelerated to clear the fault instantaneously (after time tCoord). The overreaching zone to be
accelerated is connected to the input CACCLx, see figure 492. In case of external faults, the
blocking signal (CRLx) must be received before the settable timer tCoord elapses, to prevent
an unneccesary trip, see figure 492.

ZC1PPSCH can be totally blocked by activating the input BLOCK, block of trip is achieved by
activating the input BLKTRLx, Block of carrier send is done by activating the input BLKCSLx.

tCoord 25 ms
CACCLx
t t TRLx
CRLx AND

IEC06000310_2_en.vsd
IEC06000310 V2 EN-US

Figure 492: Basic logic for trip carrier in one phase of a blocking scheme

16.2.6.2 Permissive underreach scheme SEMOD141705-18 v1

In a permissive underreach scheme, a forward directed underreach measuring element


(normally zone1) sends a permissive signal CSLx to the remote end if a fault is detected in
forward direction. The received signal CRLx is used to allow an overreaching zone (connected
to CACCLx) to trip after the tCoord timer has elapsed. The tCoord is in permissive underreach
schemes normally set to zero. The logic for trip carrier in permissive scheme is shown in
figure 493. Three channels for communication in each direction must be available.

Line distance protection REL670 839


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 506 370-UEN J
Scheme communication

tCoord 25 ms
CACCLx t t TRLx
CRLx AND

IEC07000088_2_en.vsd
IEC07000088 V2 EN-US

Figure 493: Basic logic for trip carrier in one phase of a permissive underreach scheme

16.2.6.3 Permissive overreach scheme SEMOD141705-26 v1

In a permissive overreach scheme, a forward directed overreach measuring element (normally


zone2) sends a permissive signal CSLx to the remote end if a fault is detected in forward
direction. The received signal CRLx is used to allow an overreaching zone to trip after the
settable tCoord timer has elapsed. The tCoord is in permissive overreach schemes normally
set to zero. The logic for trip carrier is the same as for permissive underreach, see figure 492.

The permissive overreach scheme has the same blocking possibilities as mentioned for
blocking scheme above. The blocking inputs are activated from the current reversal logic when
this function is included.

Three channels for communication in each direction must be available.

16.2.6.4 Unblocking scheme SEMOD141705-31 v2

In an unblocking scheme, the lower dependability in permissive scheme is overcome by using


the loss of guard signal from the communication equipment to locally create a carrier receive
signal. It is common or suitable to use the function when older, less reliable, power-line carrier
(PLC) communication is used. As phase segregated communication schemes uses phases
individually and the PLC is typically connected single-phase or phase-to-phase it is not
possible to evaluate which of the phases to release and the unblocking scheme has thus not
been supported.

16.2.6.5 Intertrip scheme SEMOD141705-34 v1

In the direct intertrip scheme, the carrier send signal CS is sent from an underreaching zone
that is tripping the line.

The received signal per phase is directly transferred to the trip function block for tripping
without local criteria. The signal is not further processed in the phase segregated
communication logic. In case of single-pole tripping the phase selection and logic for tripping
the three phases is performed in the trip function block.

16.2.6.6 Simplified logic diagram SEMOD141705-38 v2

The simplified logic diagram for one phase is shown in figure 494.

840 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 16
Scheme communication

SchemeType =
Intertrip

CSURLx

tSendMin AND
OR

BLOCK
AND
CSBLKLx OR
CRLx

Scheme Type =
Permissive UR AND CSLx
OR

tCoord
25 ms
AND t TRLx
OR t
CACCLx

Scheme Type =
Permissive OR

CSORLx OR AND

AND

tSendMin
OR

AND
Scheme Type =
Blocking
BLKCSx

AND

CSL1
CSL2 AND

CSL2
OR CSMPH
CSL3 AND

CSL3
CSL1 AND

CSL1
CSL2 GENERAL
OR
CSL3

IEC06000311_2_en.vsd
IEC06000311 V2 EN-US

Figure 494: Simplified logic diagram for one phase

Line distance protection REL670 841


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 506 370-UEN J
Scheme communication

16.2.7 Technical data


SEMOD166936-2 v7

Table 568: ZC1PPSCH technical data


Function Range or value Accuracy
Scheme type Intertrip -
Permissive UR
Permissive OR
Blocking
Co-ordination time for blocking (0.000-60.000) s ±0.2% or ±15 ms whichever is
communication scheme greater
Minimum duration of a carrier (0.000-60.000) s ±0.2% or ±15 ms whichever is
send signal greater

16.3 Current reversal and Weak-end infeed logic for


distance protection 3-phase ZCRWPSCH IP15751-1 v4

16.3.1 Identification
M15073-1 v5

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Current reversal and weak-end ZCRWPSCH - 85
infeed logic for distance protection
3-phase

16.3.2 Functionality M13896-3 v15

The ZCRWPSCH function provides the current reversal and weak end infeed logic functions
that supplement the standard scheme communication logic. It is not suitable for standalone
use as it requires inputs from the distance protection functions and the scheme
communications function included within the terminal.

On detection of a current reversal, the current reversal logic provides an output to block the
sending of the teleprotection signal to the remote end, and to block the permissive tripping at
the local end. This blocking condition is maintained long enough to ensure that no unwanted
operation will occur as a result of the current reversal.

On verification of a weak end infeed condition, the weak end infeed logic provides an output
for sending the received teleprotection signal back to the remote sending end and other
output(s) for local tripping. For terminals equipped for single- and two-pole tripping, outputs
for the faulted phase(s) are provided. Undervoltage detectors are used to detect the faulted
phase(s).

842 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 16
Scheme communication

16.3.3 Function block SEMOD53507-9 v6

ZCRWPSCH
U3P* IRVL
BLOCK TRWEI
IRVBLK TRWEIL1
IRV TRWEIL2
WEIBLK1 TRWEIL3
WEIBLK2 ECHO
VTSZ
CBOPEN
CRL

IEC06000287-2-en.vsd
IEC06000287 V2 EN-US

Figure 495: ZCRWPSCH function block

16.3.4 Signals
PID-3521-INPUTSIGNALS v8

Table 569: ZCRWPSCH Input signals


Name Type Default Description
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
IRVBLK BOOLEAN 0 Block of current reversal function
IRV BOOLEAN 0 Activation of current reversal logic
WEIBLK1 BOOLEAN 0 Block of WEI logic
WEIBLK2 BOOLEAN 0 Block of WEI logic due to operation of other protections
VTSZ BOOLEAN 0 Block of trip from WEI logic through fuse-failure function
CBOPEN BOOLEAN 0 Block of trip from WEI logic by an open breaker
CRL BOOLEAN 0 POR Carrier receive for WEI logic

PID-3521-OUTPUTSIGNALS v8

Table 570: ZCRWPSCH Output signals


Name Type Description
IRVL BOOLEAN Operation of current reversal logic
TRWEI BOOLEAN Trip signal from weak end infeed logic
TRWEIL1 BOOLEAN Trip signal from weak end infeed logic in phase L1
TRWEIL2 BOOLEAN Trip signal from weak end infeed logic in phase L2
TRWEIL3 BOOLEAN Trip signal from weak end infeed logic in phase L3
ECHO BOOLEAN Carrier send by WEI logic

Line distance protection REL670 843


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 506 370-UEN J
Scheme communication

16.3.5 Settings
PID-3521-SETTINGS v8

Table 571: ZCRWPSCH Group settings (basic)


Name Values (Range) Unit Step Default Description
CurrRev Off - - Off Operating mode of Current Reversal
On Logic
tPickUpRev 0.000 - 60.000 s 0.001 0.020 Pickup time for current reversal logic
tDelayRev 0.000 - 60.000 s 0.001 0.060 Time Delay to prevent Carrier send
and local trip
WEI Off - - Off Operating mode of WEI logic
Echo
Echo & Trip
tPickUpWEI 0.000 - 60.000 s 0.001 0.010 Coordination time for the WEI logic
UPP< 10 - 90 %UB 1 70 Phase to Phase voltage for detection
of fault condition
UPN< 10 - 90 %UB 1 70 Phase to Neutral voltage for detection
of fault condition

Table 572: ZCRWPSCH Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

16.3.6 Operation principle

16.3.6.1 Current reversal logic M16679-3 v9

The current reversal logic can be enabled by setting the parameter CurrRev = On. The current
reversal logic uses a reverse zone connected to the input IRV to recognize the fault on the
parallel line in any of the phases.When the reverse zone has been activated (even if only for a
short time), it prevents sending of a communication signal and tripping through the scheme
communication logic after a settable time tPickUpRev. The prevention will last for tPickUpRev
+ 10 ms + tDelayRev after the IREV reset. This makes it possible for the receive signal to reset
before the carrier-aided trip signal is activated due to the current reversal by the forward
directed zone. The logic diagram for current reversal is shown in Figure 496.

BLOCK

IRVBLK
tDelayRev
tPickUpRev 10 ms tPickUpRev IRVL
IRV AND t
t t t

CurrRev = On

IEC05000122-4-en.vsd
IEC05000122 V4 EN-US

Figure 496: Simplified logic diagram for current reversal


By connecting the output signal IRVL to input BLKCS in the ZCPSCH function, the sending of
the signal CS from the overreaching zone connected to CSOR in ZCPSCH will be blocked. By

844 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 16
Scheme communication

connecting IRVL to input BLKTR in the ZCPSCH function, the TRIP output from the ZCPSCH
function will be blocked.

The function has an internal 10 ms drop-off timer which will secure that the current reversal
logic will be activated for short input signals even if the pick-up timer is set to zero.

16.3.6.2 Weak-end infeed logic M16679-8 v12

The weak-end infeed logic (WEI) function sends back (echoes) the received signal under the
condition that no fault has been detected on the weak-end by different fault detection
elements (distance protection in forward or reverse direction).

The WEI function returns the received signal, shown in Figure 497, when:

• The setting parameter WEI is set to either Echo or Echo & Trip.
• No active signal is present on the input BLOCK.
• The functional input CRL is active for a time longer than the tPickUpWei setting. This input
is usually connected to the CRL output on the scheme communication logic ZCPSCH.
• The WEI function is not blocked by the active signal connected to the WEIBLK1 functional
input or to the VTSZ functional input. The later is usually configured to the VTSZ
functional output of the fuse-failure function.
• No active signal has been present for at least 200 ms on the WEIBLK2 functional input. An
OR combination of all fault detection functions (not undervoltage) as present within the
IED is usually used for this purpose.
• The weak-end infeed logic also echoes the received permissive signal when local breaker
opens.

BLOCK
VTSZ
WEIBLK1 OR

tPickUpWEI
CRL AND 50 ms 200 ms
t AND
OR t t
ECHO
200 ms AND
WEIBLK2
t

AND

OR
1500 ms
CBOPEN
t

WEI = Echo

IEC05000123-3-en.vsd
IEC05000123 V3 EN-US

Figure 497: Simplified logic diagram for weak-end infeed logic — Echo
When an echo function is used in both IEDs (should generally be avoided), a spurious signal can
be looped round by the echo logics. To avoid a continuous lock-up of the system, the duration
of the echoed signal is limited to 200 ms.

An undervoltage criteria is used as an additional tripping criteria, when the tripping of the
local breaker is selected, setting WEI = Echo&Trip. With this setting the Echo and Trip are
working in parallel as in logic shown in Figure 498.

Line distance protection REL670 845


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 506 370-UEN J
Scheme communication

BLOCK
VTSZ
WEIBLK1 OR
tPickUpWEI
CRL AND 50 ms 200 ms
t AND ECHO
OR t t AND
200 ms
WEIBLK2
t

AND

1500 ms
OR
CBOPEN
t
AND

U3P*
UL1<UPN<
UL2 < UPN<
UL3 < UPN<
UPN< 100 ms
OR
AND t
TRWEI
OR

15 ms
TRWEIL1
U3P*
AND t
UL1L2 <UPP< OR
UL2L3 < UPP<
UL3L1 < UPP<
15 ms
UPP< TRWEIL2
AND t
OR

15 ms
OR TRWEIL3
AND t

WEI = Echo & Trip

IEC00000551-TIFF V4 EN-US IEC00000551-TIFF.vsd

Figure 498: Simplified logic diagram for weak-end infeed logic — Echo&Trip

16.3.7 Technical data


M16039-1 v16

Table 573: ZCRWPSCH technical data


Function Range or value Accuracy
Detection level phase-to- (10-90)% of UBase ±0.5% of Ur
neutral voltage
Detection level phase-to- (10-90)% of UBase ±0.5% of Ur
phase voltage
Operate time for current (0.000-60.000) s ±0.2% or ±15 ms whichever is
reversal logic greater
Delay time for current reversal (0.000-60.000) s ±0.2% or ±15 ms whichever is
greater
Coordination time for weak- (0.000-60.000) s ±0.2% or ±15 ms whichever is
end infeed logic greater

846 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 16
Scheme communication

16.4 Current reversal and weak-end infeed logic for phase


segregated communication ZC1WPSCH SEMOD155635-1 v2

16.4.1 Identification
SEMOD156467-2 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Current reversal and weak-end ZC1WPSCH - 85
infeed logic for phase segregated
communication

16.4.2 Functionality SEMOD156473-5 v3

Current reversal and weak-end infeed logic for phase segregated communication (ZC1WPSCH)
function is used to prevent unwanted operations due to current reversal when using
permissive overreach protection schemes in application with parallel lines where the overreach
from the two ends overlaps on the parallel line.

The weak-end infeed logic is used in cases where the apparent power behind the protection
can be too low to activate the distance protection function. When activated, received carrier
signal together with local undervoltage criteria and no reverse zone operation gives an
instantaneous trip. The received signal is also echoed back to accelerate the sending end.

16.4.3 Function block SEMOD157994-5 v2

ZC1WPSCH
U3P* TRPWEI
BLOCK TRPWEIL1
BLKZ TRPWEIL2
CBOPEN TRPWEIL3
CRL1 IRVOP
CRL2 IRVOPL1
CRL3 IRVOPL2
IRVL1 IRVOPL3
IRVL2 ECHO
IRVL3 ECHOL1
IRVBLKL1 ECHOL2
IRVBLKL2 ECHOL3
IRVBLKL3
WEIBLK
WEIBLKL1
WEIBLKL2
WEIBLKL3
WEIBLKOP
WEIBLKO1
WEIBLKO2
WEIBLKO3

IEC06000477-2-en.vsd
IEC06000477 V2 EN-US

Figure 499: ZC1WPSCH function block

Line distance protection REL670 847


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 506 370-UEN J
Scheme communication

16.4.4 Signals
PID-3524-INPUTSIGNALS v9

Table 574: ZC1WPSCH Input signals


Name Type Default Description
U3P GROUP - Voltage
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKZ BOOLEAN 0 Block of trip from WEI logic by the fuse-failure function
CBOPEN BOOLEAN 0 Block of trip from WEI logic by an open breaker
CRL1 BOOLEAN 0 Carrier receive for WEI logic in Phase L1
CRL2 BOOLEAN 0 Carrier receive for WEI logic in Phase L2
CRL3 BOOLEAN 0 Carrier receive for WEI logic in Phase L3
IRVL1 BOOLEAN 0 Activation of current reversal logic in Phase L1
IRVL2 BOOLEAN 0 Activation of current reversal logic in Phase L2
IRVL3 BOOLEAN 0 Activation of current reversal logic in phase L3
IRVBLKL1 BOOLEAN 0 Block of current reversal function in Phase L1
IRVBLKL2 BOOLEAN 0 Block of current reversal function in Phase L2
IRVBLKL3 BOOLEAN 0 Block of current reversal function in Phase L3
WEIBLK BOOLEAN 0 Block of WEI logic
WEIBLKL1 BOOLEAN 0 Block of WEI logic in Phase L1
WEIBLKL2 BOOLEAN 0 Block of WEI logic in Phase L2
WEIBLKL3 BOOLEAN 0 Block of WEI logic in Phase L3
WEIBLKOP BOOLEAN 0 Block of WEI logic due to operation of other protection
WEIBLKO1 BOOLEAN 0 Block of WEI logic in Phase L1 due to operation of other
protection
WEIBLKO2 BOOLEAN 0 Block of WEI logic in Phase L2 due to operation of other
protections
WEIBLKO3 BOOLEAN 0 Block of WEI logic in Phase L3 due to operation of other
protections

PID-3524-OUTPUTSIGNALS v9

Table 575: ZC1WPSCH Output signals


Name Type Description
TRPWEI BOOLEAN Trip of WEI logic
TRPWEIL1 BOOLEAN Trip of WEI logic in Phase L1
TRPWEIL2 BOOLEAN Trip of WEI logic in Phase L2
TRPWEIL3 BOOLEAN Trip of WEI logic in Phase L3
IRVOP BOOLEAN Operation of current reversal logic
IRVOPL1 BOOLEAN Operation of current reversal logic in Phase L1
IRVOPL2 BOOLEAN Operation of current reversal logic in Phase L2
IRVOPL3 BOOLEAN Operation of current reversal logic in Phase L3
ECHO BOOLEAN Carrier Send by WEI logic
ECHOL1 BOOLEAN Carrier Send by WEI logic in Phase L1
ECHOL2 BOOLEAN Carrier Send by WEI logic in Phase L2
ECHOL3 BOOLEAN Carrier Send by WEI logic in Phase L3

848 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 16
Scheme communication

16.4.5 Settings
PID-3524-SETTINGS v8

Table 576: ZC1WPSCH Group settings (basic)


Name Values (Range) Unit Step Default Description
OperCurrRev Off - - Off Operating mode of Current Reversal
On Logic
tPickUpRev 0.000 - 60.000 s 0.001 0.020 Pickup time for current reversal logic
tDelayRev 0.000 - 60.000 s 0.001 0.060 Time Delay to prevent Carrier send
and local trip
OperationWEI Off - - Off Operating mode of WEI logic
Echo
Echo & Trip
UPE< 10 - 90 %UB 1 70 Phase to Earth voltage for detection
of fault condition
UPP< 10 - 90 %UB 1 70 Phase to Phase voltage for detection
of fault condition
tPickUpWEI 0.000 - 60.000 s 0.001 0.010 Coordination time for the WEI logic

Table 577: ZC1WPSCH Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

16.4.6 Operation principle

16.4.6.1 Current reversal logic SEMOD156478-5 v4

The current reversal logic can be enabled by setting the parameter OperCurrRev = On. The
current reversal logic uses a reverse zone connected to the input IRVLx to recognize the fault
on the parallel line in any of the phases. When the reverse zone has been activated (even if only
for a short time), it prevents sending of a communication signal and tripping through the
scheme communication logic after a settable time tPickUpRev. The prevention will last for
tPickUpRev + 10 ms + tDelayRev after the IRVLx reset. This makes it possible for the receive
signal to reset before the trip signal is activated due to the current reversal by the forward
directed zone. The logic diagram for current reversal is shown in Figure 500.

BLOCK

IRVBLKLx
tDelayRev
tPickUpRev 10 ms tPickUpRev IRVOPLx
IRVLx & t
t t t

operCurrRev=On

IEC06000474-3-en.vsd
IEC06000474 V3 EN-US

Figure 500: Simplified logic diagram for current reversal


By connecting the IRVOPLx signal to input BLKCSLx in the ZC1PPSCH function, the sending
carrier send signal CSLx in ZC1PPSCH is blocked. By connecting the IRVOPLx signal to input
BLKTRLx in ZC1PPSCH, the TRIPLx output in ZC1PPSCH is blocked.

Line distance protection REL670 849


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 506 370-UEN J
Scheme communication

The Current reversal and weak-end infeed logic for phase segregated communication
(ZC1WPSCH) function has an internal 10 ms drop-off timer which secure that the current
reversal logic will be activated for short input signals even if the pickup timer is set to zero.

16.4.6.2 Weak-end infeed logic GUID-CBFC8E60-748A-49F6-AF73-563E7CFC0653 v4

The WEI function sends back (echoes) the received carrier signal under the condition that no
fault has been detected at the weak end by different fault detection elements (distance
protection in forward and reverse direction).

BLOCK
BLKZ
WEIBLKLx 1 ECHOLx-contd
&
tPickUpWEI
CRLx & 50 ms 200 ms
t &
1 t t
ECHOLx
200 ms &
WEIBLKOx
t

&

1
1500 ms
CBOPEN
t

OperationWEI=Echo

IEC07000085-3-en.vsd
IEC07000085 V3 EN-US

Figure 501: Simplified logic for weak-end infeed logic — Echo


The WEI function returns the received carrier signal, shown in Figure 501, when:

• No active signal present on the input BLOCK.


• The input CRLx is active. This input is usually connected to the CRLx output on the scheme
communication logic for distance or Overcurrent protection (ZCPSCH).
• The WEI function is not blocked by the active signal connected to the WEIBLKLx input or to
the BLKZ input. The latter is usually configured to the STGEN output of the fuse-failure
function.
• No active signal has been present for at least 200 ms on the WEIBLKOx input. An OR
combination of all fault detection functions (not undervoltage) as present within the IED
is usually used for this purpose.
• The weak-end infeed logic also echoes the received permissive signal when local breaker
opens, CBOPEN prior to faults appeared at the end of line.

When an echo function is used in both the IEDs on the protected line (should generally be
avoided), a spurious signal can be looped round by the echo logics. To avoid a continuous lock-
up of the system, the duration of the echoed signal is limited to 200 ms.

An undervoltage criteria is used as an additional tripping criteria when the tripping of the local
breaker is selected. Setting OperationWEI = Echo &Trip together with the WEI function and
ECHOLx, trip signal TRPWEIx has been issued by the echo and trip logic which is described in
Figure 502.

850 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 16
Scheme communication

ECHOLx- contd

CBOPEN

U3P*
100 ms
=1
& t
Undervoltage TRPWEI
detection =1
UPE<

15 ms
UPP< TRPWEI1
& t

OperationWEI= Echo & Trip

15 ms
TRPWEI2
& t

15 ms
TRPWEI3
& t

IEC13000278-1-en.vsd
IEC13000278 V1 EN-US

Figure 502: Simplified logic diagram for weak-end infeed logic – Echo & Trip

It is strongly recommended to not connect any start signals from impedance


protection or directional overcurrent protection functions to WEIBLK and
WEIBLKOP inputs in ZC1WPSCH function to block the echo signal, if local
protection functions operate for faults at the weak end.

Start signals can be connected to WEIBLKLx and WEIBLKOx via OR gate to achieve the blocking
of echo signal in case if the faults are detected by local protection functions and thereby,
avoiding the operation from the remote end. By this, 3-pole operation can be accomplished in
addition to 1-pole and 2-pole operations by ZC1WPSCH function. Also, if a 3-pole operation
needs to be achieved by a separate protection function, current reversal and weak-end infeed
logic for distance protection 3-phase ZCRWPSCH function can be used. Figure 503 and Figure
504 shows the connection of start signals from ZMFCPDIS function to WEIBLKLx and
WEIBLKOx in ACT configuration to block echo signal.

Line distance protection REL670 851


Technical manual
© Copyright 2017 ABB. All rights reserved
852
Section 16
Scheme communication

IEC18000012 V1 EN-US
IEC18000012-1-en.vsdx

© Copyright 2017 ABB. All rights reserved


Figure 503: Blocking of echo signal using WEIBLKLx input of ZC1WPSCH
Project Responsible department Technical reference Document kind Doc. designation
Test123234 ABB Ltd. Graphical Application Co... AA1J1Q01A2
Replacing Created by Title Document id.
REL670
Test123234.Substation.Voltage Level.Bay Approved by Rev. Rel. date Lan
1/1
Rev. Modification Rel. date Created ... Based on 0 3/2/2018 en

Technical manual
Line distance protection REL670
1MRK 506 370-UEN J
Technical manual
1MRK 506 370-UEN J

IEC18000013 V1 EN-US

Line distance protection REL670


IEC18000013-1-en.vsdx

© Copyright 2017 ABB. All rights reserved


Figure 504: Blocking of echo signal using WEIBLKOx input of ZC1WPSCH
Project Responsible department Technical reference Document kind Doc. designation
Test123234 ABB Ltd. Graphical Application Co... AA1J1Q01A2
Replacing Created by Title Document id.
REL670
Test123234.Substation.Voltage Level.Bay Approved by Rev. Rel. date Lan
1/1
Rev. Modification Rel. date Created ... Based on 0 3/2/2018 en

853
Scheme communication
Section 16
Section 16 1MRK 506 370-UEN J
Scheme communication

16.4.7 Technical data


SEMOD166938-2 v6

Table 578: ZC1WPSCH technical data


Function Range or value Accuracy
Detection level phase to (10-90)% of UBase ±0.5% of Ur
neutral voltage
Detection level phase to (10-90)% of UBase ±0.5% of Ur
phase voltage
Reset ratio <105% at (20-90)% of UBase -
Operate time for current (0.000-60.000) s ±0.2% or ±15 ms whichever is
reversal greater
Delay time for current reversal (0.000-60.000) s ±0.2% or ±15 ms whichever is
greater
Coordination time for weak- (0.000-60.000) s ±0.2% or ±15 ms whichever is
end infeed logic greater

16.5 Local acceleration logic ZCLCPSCH SEMOD52894-1 v4

16.5.1 Identification
M14860-1 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Local acceleration logic ZCLCPSCH - -

16.5.2 Functionality M13823-3 v7

To achieve fast clearing of faults on the whole line, when no communication channel is
available, local acceleration logic (ZCLCPSCH) can be used. This logic enables fast fault
clearing and re-closing during certain conditions, but naturally, it can not fully replace a
communication channel.

The logic can be controlled either by the autorecloser (zone extension) or by the loss-of-load
current (loss-of-load acceleration).

16.5.3 Function block M13816-3 v4

ZCLCPSCH
I3P* TRZE
BLOCK TRLL
ARREADY
NDST
EXACC
BC
LLACC

IEC13000307-1-en.vsd
IEC13000307 V1 EN-US

Figure 505: ZCLCPSCH function block

854 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 16
Scheme communication

16.5.4 Signals
PID-3511-INPUTSIGNALS v6

Table 579: ZCLCPSCH Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
BLOCK BOOLEAN 0 Block of function
ARREADY BOOLEAN 0 Autoreclosure ready, releases function used for fast trip
NDST BOOLEAN 0 Non directional criteria used to prevent instantaneous trip
EXACC BOOLEAN 0 Connected to function used for tripping at zone extension
BC BOOLEAN 0 Breaker Close
LLACC BOOLEAN 0 Connected to function used for tripping at loss of load

PID-3511-OUTPUTSIGNALS v6

Table 580: ZCLCPSCH Output signals


Name Type Description
TRZE BOOLEAN Trip by zone extension
TRLL BOOLEAN Trip by loss of load

16.5.5 Settings
PID-3511-SETTINGS v7

Table 581: ZCLCPSCH Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
LoadCurr 1 - 100 %IB 1 10 Load current before disturbance in %
of IBase
LossOfLoad Off - - Off Enable/Disable operation of Loss of
On load.
ZoneExtension Off - - Off Enable/Disable operation of Zone
On extension
MinCurr 1 - 100 %IB 1 5 Lev taken as curr loss due to remote
CB trip in % of IBase
tLowCurr 0.000 - 60.000 s 0.001 0.200 Time delay on pick-up for MINCURR
value
tLoadOn 0.000 - 60.000 s 0.001 0.000 Time delay on pick-up for load current
release
tLoadOff 0.000 - 60.000 s 0.001 0.300 Time delay on drop off for load
current release

Table 582: ZCLCPSCH Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

Line distance protection REL670 855


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 506 370-UEN J
Scheme communication

16.5.6 Operation principle

16.5.6.1 Zone extension M13819-3 v3

When the auto-recloser controls the function, a signal auto-recloser ready (ZCLCARREADY)
allows an overreaching zone (ZCLC-EXACC) to trip instantaneously, see figure 506.

The ZCLC-ARREADY functional input should be configured to READY output of auto-reclosing


function.

The overreaching zone is connected to the input EXACC.

IEC05000157 V1 EN-US

Figure 506: Simplified logic diagram for local acceleration logic


The function provides instantaneous trip (TRZE) if the ARREADY and EXACC inputs are set.
After that, the autorecloser initiates the close command and remains in the reclaim state and
therefore ARREADY signal will be low. This will block the TRZE output. If a non-direction start is
picked up after reclosing, the TRZE is blocked and therefore the fault clearance is as per the
step-time distance protection.

In case of a fault on the adjacent line within the overreaching zone range, an unwanted
autoreclosing cycle will occur due to the zone extension functionality.

On the other hand, if the fault is a persistent line fault on the line section and not covered by
instantaneous zone (normally zone 1), then a trip after reclosing will be with the step-time
distance function (which is time delayed) and only the first trip (before reclosing) will be
"instantaneous" .

The function will be blocked if the input BLOCK is activated (common with loss-of-load
acceleration).

16.5.6.2 Loss-of-Load acceleration M13819-9 v6

The local acceleration logic uses the loss-of-load condition to accelerate the trip for faults that
were not detected in an instantaneous zone (normally zone 1). If there is a fault in the range of
over reaching zone but still in the same line section, then the distance protection in the remote
operates in the instantaneous zone and the remote breaker opens in all three phases. Due to
this, the load current in the healthy phases will be discontinued, however, the current
continues to flow in the fault phases. Hence, this scenario is used to detect that the fault is
inside the line section and then LLACC is released for TRLL.

When the "acceleration" is controlled by a loss-of-load, the overreaching zone used for
"acceleration" connected to input LLACC is not allowed to trip "instantaneously" during normal
non-fault system conditions. When all three-phase currents have been above the set value
MinCurr for more than setting tLowCurr, an overreaching zone will be allowed to trip
"instantaneously" during a fault condition when one or two of the phase currents will become

856 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 16
Scheme communication

low due to a three-phase trip at the opposite IED, see figure 507. The current measurement is
performed internally and the internal STILL signal becomes logical one under the described
conditions. The load current in a healthy phase is in this way used to indicate the tripping at
the opposite IED. Note that this function will not operate in case of three-phase faults,
because none of the phase currents will be low when the opposite IED is tripped.

BLOCK

BC OR

I_PHL1
a overPhase1
a>b
LoadCurr b

tLoadOn tLoadOff
a
a > b overPhase2 AND t t
b

a
a>b
b overPhase3

tLoadOn
AND TRLL
AND t
OR

a
a < b underPhase1
MinCurr b

tLowCurr
I_PHL2
a AND t
a < b underPhase2 OR
b

I_PHL3
a
a<b
b underPhase3

LLACC

IEC05000158-2-en.vsdx
IEC05000158 V2 EN-US

Figure 507: Loss-of-load acceleration - simplified logic diagram


Breaker closing signals can if decided be connected to block the function during normal
closing.
M13819-14 v2

16.6 Scheme communication logic for residual overcurrent


protection ECPSCH IP14711-1 v2

16.6.1 Identification
M14882-1 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Scheme communication logic for ECPSCH - 85
residual overcurrent protection

16.6.2 Functionality M13918-4 v11

To achieve fast fault clearance of earth faults on the part of the line not covered by the
instantaneous step of the residual overcurrent protection, the directional residual overcurrent
protection can be supported with a logic that uses communication channels.

In the directional scheme, information of the fault current direction must be transmitted to
the other line end. With directional comparison, a short operate time of the protection
including a channel transmission time, can be achieved. This short operate time enables rapid
autoreclosing function after the fault clearance.

The communication logic module for directional residual current protection enables blocking
as well as permissive under/overreaching, and unblocking schemes. The logic can also be

Line distance protection REL670 857


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 506 370-UEN J
Scheme communication

supported by additional logic for weak-end infeed and current reversal, included in Current
reversal and weak-end infeed logic for residual overcurrent protection (ECRWPSCH) function.

16.6.3 Function block M13924-3 v5

ECPSCH
BLOCK TRIP
BLKTR CS
BLKCS CRL
CSBLK LCG
CACC
CSOR
CSUR
CR
CRG

IEC06000288-2-en.vsd
IEC06000288 V2 EN-US

Figure 508: ECPSCH function block

16.6.4 Signals
PID-3581-INPUTSIGNALS v7

Table 583: ECPSCH Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Signal for blocking trip due to communication logic
BLKCS BOOLEAN 0 Signal for blocking CS in Overreach and Blocking schemes
CSBLK BOOLEAN 0 Reverse residual overcurrent signal for Carrier Send
CACC BOOLEAN 0 Signal to be used for tripping by Communication Scheme
CSOR BOOLEAN 0 Overreaching residual overcurrent signal for Carrier Send
CSUR BOOLEAN 0 Underreaching residual overcurrent signal for Carrier Send
CR BOOLEAN 0 Carrier Receive for Communication Scheme Logic
CRG BOOLEAN 0 Carrier guard signal received

PID-3581-OUTPUTSIGNALS v6

Table 584: ECPSCH Output signals


Name Type Description
TRIP BOOLEAN Trip signal by communication scheme logic
CS BOOLEAN Carrier Send by Communication Scheme Logic
CRL BOOLEAN Carrier Receive from Communication Scheme Logic
LCG BOOLEAN loss of carrier guard signal

858 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 16
Scheme communication

16.6.5 Settings
PID-3581-SETTINGS v6

Table 585: ECPSCH Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
SchemeType Off - - Permissive UR Scheme type, Mode of Operation
Intertrip
Permissive UR
Permissive OR
Blocking
tCoord 0.000 - 60.000 s 0.001 0.035 Communication scheme coordination
time
tSendMin 0.000 - 60.000 s 0.001 0.100 Minimum duration of a carrier send
signal

Table 586: ECPSCH Group settings (advanced)


Name Values (Range) Unit Step Default Description
Unblock Off - - Off Operation mode of unblocking logic
NoRestart
Restart
tSecurity 0.000 - 60.000 s 0.001 0.035 Security timer for loss of carrier guard
detection

16.6.6 Operation principle


M13922-4 v5
The four step directional residual overcurrent protection EF4PTOC is configured to give input
information, that is directional fault detection signals, to the ECPSCH logic:

• Input signal CACC is used for tripping of the communication scheme, normally the start
signal of a forward overreaching step of STFW.
• Input signal CSBLK is used for sending block signal in the blocking communication
scheme, normally the start signal of a reverse overreaching step of STRV.
• Input signal CSUR is used for sending permissive signal in the underreaching permissive
communication scheme, normally the start signal of a forward underreaching step of
STINn, where n corresponds to the underreaching step.
• Input signal CSOR is used for sending permissive signal in the overreaching permissive
communication scheme, normally the start signal of a forward overreaching step of STINn,
where n corresponds to the overreaching step.

In addition to this a signal from the autoreclosing function should be configured to the BLKCS
input for blocking of the function at a single phase reclosing cycle.

16.6.6.1 Blocking scheme M13922-9 v5

In the blocking scheme a signal is sent to the other line end if the directional element detects
an earth fault in the reverse direction. When the forward directional element operates, it trips
after a short time delay if no blocking signal is received from the opposite line end. The time
delay, normally 30 – 40 ms, depends on the communication transmission time and a chosen
safety margin.

Line distance protection REL670 859


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 506 370-UEN J
Scheme communication

One advantage of the blocking scheme is that only one channel (carrier frequency) is needed if
the ratio of source impedances at both end is approximately equal for zero and positive
sequence source impedances, the channel can be shared with the impedance measuring
system, if that system also works in the blocking mode. The communication signal is
transmitted on a healthy line and no signal attenuation will occur due to the fault.

Blocking schemes are particular favorable for three-terminal applications if there is no zero-
sequence outfeed from the tapping. The blocking scheme is immune to current reversals
because the received signal is maintained long enough to avoid unwanted operation due to
current reversal. There is never any need for weak-end infeed logic, because the strong end
trips for an internal fault when no blocking signal is received from the weak end. The fault
clearing time is however generally longer for a blocking scheme than for a permissive scheme.

If the fault is on the line, the forward direction measuring element operates. If no blocking
signal comes from the other line end via the CR binary input (received signal) the TRIP output
is activated after the tCoord set time delay.

IEC05000448 V1 EN-US

Figure 509: Simplified logic diagram for blocking scheme

16.6.6.2 Permissive under/overreaching scheme M13922-17 v6

In the permissive scheme the forward directed earth-fault measuring element sends a
permissive signal to the other end, if an earth fault is detected in the forward direction. The
directional element at the other line end must wait for a permissive signal before activating a
trip signal. Independent channels must be available for the communication in each direction.

An impedance measuring IED, which works in the same type of permissive mode, with one
channel in each direction, can share the channels with the communication scheme for residual
overcurrent protection. If the impedance measuring IED works in the permissive overreaching
mode, common channels can be used in single line applications. In case of double lines
connected to a common bus at both ends, use common channels only if the ratio Z1S/Z0S
(positive through zero-sequence source impedance) is about equal at both ends. If the ratio is
different, the impedance measuring and the directional earth-fault current system of the
healthy line may detect a fault in different directions, which could result in unwanted tripping.

Common channels cannot be used when the weak-end infeed function is used in the distance
or earth-fault protection.

In case of an internal earth-fault, the forward directed measuring element operates and sends
a permissive signal to the remote end via the CS output (sent signal). Local tripping is
permitted when the forward direction measuring element operates and a permissive signal is
received via the CR binary input (received signal).

860 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 16
Scheme communication

The permissive scheme can be of either underreaching or overreaching type. In the


underreaching alternative, an underreaching directional residual overcurrent measurement
element will be used as sending criterion of the permissive input signal CSUR.

In the overreaching alternative, an overreaching directional residual overcurrent measurement


element will be used as sending criterion of the permissive input signal CSOR. Also the
underreaching input signal CSUR can initiate sending.

BLOCK
CRL
CR AND
25 ms

t TRIP
0 - 60 s

CACC AND AND t


50 ms
tCoord
t

AND

BLKCS OR CS
AND
Overreach
CSOR AND 25 ms

CSUR OR t

IEC05000280.vsd

IEC05000280 V4 EN-US

16.6.6.3 Unblocking scheme M13922-45 v6

In unblocking scheme, the lower dependability in permissive scheme is overcome by using the
loss of guard signal from the communication equipment to locally create a receive signal. It is
common or suitable to use the function when older, less reliable, power line carrier (PLC)
communication is used.

The unblocking function uses a guard signal CRG, which must always be present, even when no
CR signal is received. The absence of the CRG signal for a time longer than the setting
tSecurity time is used as a CR signal, see figure 510. This also enables a permissive scheme to
operate when the line fault blocks the signal transmission.

The received signal created by the unblocking function is reset 150 ms after the security timer
has elapsed. When that occurs an output signal LCG is activated for signaling purpose. The
unblocking function is reset 200 ms after that the guard signal is present again.

Line distance protection REL670 861


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 506 370-UEN J
Scheme communication

CR
tSecurity CRL
t OR

CRG
200 ms 150 ms
t OR t AND
AND
LCG

IEC05000746-2-en.vsd
IEC05000746 V2 EN-US

Figure 510: Guard signal logic with unblocking scheme


The unblocking function can be set in three operation modes (setting Unblock):

Off: The unblocking function is out of operation


No restart: Communication failure shorter than tSecurity will be ignored
If CRG disappears, a CRL signal will be transferred to the trip logic
There will not be any information in case of communication failure (LCG)
Restart Communication failure shorter than tSecurity will be ignored
It sends a defined (150 ms) CRL after the disappearance of the CRG signal
The function will activate LCG output in case of communication failure
If the communication failure comes and goes (<200 ms) there will not be
recurrent signaling

16.6.7 Technical data


M16049-1 v10

Table 587: ECPSCH technical data


Function Range or value Accuracy
Scheme type Permissive Underreaching -
Permissive Overreaching
Blocking
Communication scheme (0.000-60.000) s ±0.2% or ±20 ms whichever is greater
coordination time

16.7 Current reversal and weak-end infeed logic for residual


overcurrent protection ECRWPSCH IP14365-1 v4

16.7.1 Identification
M14883-1 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Current reversal and weak-end ECRWPSCH - 85
infeed logic for residual overcurrent
protection

862 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 16
Scheme communication

16.7.2 Functionality
M13928-3 v8
The Current reversal and weak-end infeed logic for residual overcurrent protection
(ECRWPSCH) is a supplement to Scheme communication logic for residual overcurrent
protection ECPSCH.

To achieve fast fault clearing for all earth faults on the line, the directional earth fault
protection function can be supported with logic that uses tele-protection channels.

This is why the IEDs have available additions to the scheme communication logic.
M13928-6 v2
If parallel lines are connected to common busbars at both terminals, overreaching permissive
communication schemes can trip unselectively due to fault current reversal. This unwanted
tripping affects the healthy line when a fault is cleared on the other line. This lack of security
can result in a total loss of interconnection between the two buses. To avoid this type of
disturbance, a fault current reversal logic (transient blocking logic) can be used.
M13928-8 v5
Permissive communication schemes for residual overcurrent protection can basically operate
only when the protection in the remote IED can detect the fault. The detection requires a
sufficient minimum residual fault current, out from this IED. The fault current can be too low
due to an opened breaker or high-positive and/or zero-sequence source impedance behind
this IED. To overcome these conditions, weak-end infeed (WEI) echo logic is used. The weak-
end infeed echo is limited to 200 ms to avoid channel lockup.

16.7.3 Function block M13930-3 v6

ECRWPSCH
U3P* IRVL
BLOCK TRWEI
IRVBLK ECHO
IRV
WEIBLK1
WEIBLK2
VTSZ
CBOPEN
CRL

IEC06000289-3-en.vsd
IEC06000289 V3 EN-US

Figure 511: ECRWPSCH function block

16.7.4 Signals
PID-3522-INPUTSIGNALS v9

Table 588: ECRWPSCH Input signals


Name Type Default Description
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
IRVBLK BOOLEAN 0 Block of current reversal function
IRV BOOLEAN 0 Activation of current reversal logic
WEIBLK1 BOOLEAN 0 Block of WEI Logic
WEIBLK2 BOOLEAN 0 Block of WEI logic due to operation of other protections
VTSZ BOOLEAN 0 Block of trip from WEI logic through fuse-failure function
CBOPEN BOOLEAN 0 Block of trip from WEI logic by an open breaker
CRL BOOLEAN 0 POR Carrier receive for WEI logic

Line distance protection REL670 863


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 506 370-UEN J
Scheme communication

PID-3522-OUTPUTSIGNALS v8

Table 589: ECRWPSCH Output signals


Name Type Description
IRVL BOOLEAN Operation of current reversal logic
TRWEI BOOLEAN Trip signal from weak end infeed logic
ECHO BOOLEAN Permissive signal transmitted as echo signal or in case of
weak end infeed

16.7.5 Settings
PID-3522-SETTINGS v9

Table 590: ECRWPSCH Group settings (basic)


Name Values (Range) Unit Step Default Description
CurrRev Off - - Off Operating mode of Current Reversal
On Logic
tPickUpRev 0.000 - 60.000 s 0.001 0.020 Pickup time for current reversal logic
tDelayRev 0.000 - 60.000 s 0.001 0.060 Time Delay to prevent Carrier send
and local trip
WEI Off - - Off Operating mode of WEI logic
Echo
Echo & Trip
tPickUpWEI 0.000 - 60.000 s 0.001 0.000 Coordination time for the WEI logic
3U0> 5 - 70 %UB 1 25 Neutral voltage setting for fault
conditions measurement

Table 591: ECRWPSCH Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

16.7.6 Operation principle

16.7.6.1 Directional comparison logic function M13929-4 v6

The directional comparison function contains logic for blocking overreaching and permissive
overreaching schemes.

The circuits for the permissive overreaching scheme contain logic for current reversal and
weak-end infeed functions. These functions are not required for the blocking overreaching
scheme.

Use the independent or inverse time functions in the directional earth fault protection module
to get backup tripping in case the communication equipment malfunctions and prevents
operation of the directional comparison logic.

Connect the necessary signal from the autorecloser for blocking of the directional comparison
scheme, during a single-phase autoreclosing cycle, to the BLOCK input of the directional
comparison module.

864 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 16
Scheme communication

16.7.6.2 Fault current reversal logic M13929-11 v8

The fault current reversal logic uses a reverse directed element, connected to the input signal
IRV, which recognizes that the fault is in reverse direction. When the reverse direction element
is activated the output signal IRVL is activated which is shown in Figure 512. The logic is now
ready to handle a current reversal without tripping. The output signal IRVL will be connected to
the block input on the permissive overreaching scheme.

When the fault current is reversed on the healthy line, IRV is deactivated and IRVBLK is
activated. The tDelayRev timer delays the reset of the output signal. The signal blocks
operation of the overreach permissive scheme for residual current and thus prevents
unwanted operation caused by fault current reversal.

BLOCK

IRVBLK
tDelayRev
tPickUpRev 10 ms tPickUpRev AND t
IRVL
IRV
t t t

CurrRev = On

IEC09000031-4-en.vsd
IEC09000031 V4 EN-US

Figure 512: Simplified logic diagram for current reversal

16.7.6.3 Weak-end infeed logic M13929-24 v10

The weak-end infeed function can be set to send only an echo signal (WEI=Echo) or an echo
signal and a trip signal (WEI=Echo & Trip). The corresponding logic diagrams are depicted in
Figure 513 and Figure 514.

The weak-end infeed logic uses normally a reverse and a forward direction element, connected
to WEIBLK2 via an OR-gate. If neither the forward nor the reverse directional measuring
element is activated during the last 200 ms, the weak-end infeed logic echoes back the
received permissive signal as shown in Figure 513 and Figure 514. The weak-end infeed logic
also echoes the received permissive signal when CBOPEN is high (local breaker opens) prior to
faults appeared at the end of line.

If the forward or the reverse directional measuring element is activated during the last 200 ms,
the fault current is sufficient for the IED to detect the fault with the earth fault function that is
in operation.

Line distance protection REL670 865


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 506 370-UEN J
Scheme communication

CR
BLOCK AND

VTSZ
OR

tPickUpWEI
WEIBLK1
t AND 50 ms 200 ms
AND
OR t t ECHO
200 ms AND
CRL t

WEIBLK2

AND
1500 ms
CBOPEN OR
t

WEI = Echo

IEC09000032-6-en.vsd

IEC09000032 V6 EN-US

Figure 513: Simplified logic diagram for weak-end infeed logic - Echo
With the WEI= Echo & Trip setting, the logic sends an echo according to the diagram above.
Further, it activates the TRWEI signal to trip the breaker if the echo conditions are fulfilled and
the neutral point voltage is above the set operate value for 3U0>.

The voltage signal that is used to calculate the zero sequence voltage is set in the earth fault
function which is in operation.

BLOCK

VTSZ
OR

tPickUpWEI
WEIBLK1 t AND 50 ms 200 ms
AND
OR t t ECHO
200 ms AND
t
CRL

AND
WEIBLK2 1500 ms
OR
t

CBOPEN

AND
ST3U0
15 ms TRWEI
a>b AND
3U0> t

WEI = Echo&Trip

IEC09000020-6-en.vsd

IEC09000020 V6 EN-US

Figure 514: Simplified logic diagram for weak-end infeed logic - Echo & Trip
The weak-end infeed echo sent to the strong line end has a maximum duration of 200 ms.
When this time period has elapsed, the conditions that enable the echo signal to be sent are
set to zero for a time period of 50 ms. This avoids ringing action if the weak-end echo is
selected for both line ends.

866 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 16
Scheme communication

16.7.7 Technical data


M16051-2 v11

Table 592: ECRWPSCH technical data


Function Range or value Accuracy
Operate mode of WEI logic Off -
Echo
Echo & Trip
Operate voltage 3U0 for WEI (5-70)% of UBase ±0.5% of Ur
trip
Operate time for current (0.000-60.000) s ±0.2% or ±30 ms whichever is greater
reversal logic
Delay time for current reversal (0.000-60.000) s ±0.2% or ±30 ms whichever is greater
Coordination time for weak- (0.000–60.000) s ±0.2% or ±30 ms whichever is greater
end infeed logic

16.8 Direct transfer trip logic GUID-F6AE5927-D93F-4CAD-A6C6-445720C806D8 v1

16.8.1 Introduction GUID-40B4D8B0-2B57-4E0B-BC85-CB611E8EFBFE v1

Direct transfer trip (DTT) logic is used together with Line distance protection function or other
type of line protection. One typical example for use of transfer trip is given below. When Line
distance protection function is extended to cover power lines feeding the transformer directly
and there is a fault in transformer differential area, the transformer differential protection
operates faster than line protection. A trip command is sent to the remote end of the line. On
remote end, before sending a trip command to the circuit breaker, the certainty of a fault
condition is ensured by checking local criterion in DTT logic.

CR CS TRIP
TRIP
DTT IDIFF>

Xsource VT1

~ CT1
Line
CT2 CT3
Source Power Load
Transformer

en03000120.vsd
IEC03000120 V1 EN-US

Figure 515: Direct transfer trip


On receiving the CR signal from remote end, Direct transfer trip logic needs to check
additional local criterion, before sending the trip signal to circuit breaker.

DTT logic can be handled in the following separate application functions:

1. Low active power and power factor protection LAPPGAPC


2. Sudden change in current variation SCCVPTOC
3. Compensated over and undervoltage protection COUVGAPC
4. Carrier receive logic LCCRPTRC
5. Zero sequence overvoltage protection LCZSPTOV
6. Negative sequence overvoltage protection LCNSPTOV
7. Zero sequence overcurrent protection LCZSPTOC

Line distance protection REL670 867


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 506 370-UEN J
Scheme communication

8. Negative sequence overcurrent protection LCNSPTOC


9. Three-phase overcurrent LCP3PTOC
10. Three-phase undercurrent LCP3PTUC

A composite scheme of these functions must be configured in PCM600 configuration tool, to


make a complete DTT scheme as shown in Figure 516. The different individual local criteria
functions can also be used as direct tripping protections, normally with a time delay.

CR1

CR2

Impedance protection
Low impedance protection

Breaker Failure Backup trip of breaker failure


protection

Three phase overcurrent

CarrierReceiveLogic

LCCRPTRC
Three phase undercurrent
U3P
CR1

CB Trip output
CR2
Zero sequence overcurrent
protection

LocalCheck
Analog input

Negative sequence overcurrent


protection OR

Zero sequence overvoltage


protection
I3P

Negative sequence overvoltage


protection

Compensated over and


undervoltage protection

Low active power and power


factor protection

Sudden change in current


variation

IEC09000773-1-en.vsd
IEC09000773 V1 EN-US

Figure 516: Direct transfer trip scheme

16.8.2 Low active power and power factor protection LAPPGAPC GUID-585236C8-583C-4415-9820-A1DD038EA995 v1

16.8.2.1 Identification
GUID-6F3FADD8-8974-4874-8A43-642C1D540D3E v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Low active power and power factor LAPPGAPC - 37_55
protection

868 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 16
Scheme communication

16.8.2.2 Functionality GUID-25A2A94F-09FE-4552-89F8-CF22632A7A0D v2

Low active power and power factor protection (LAPPGAPC) function measures power flow. It
can be used for protection and monitoring of:

• phase wise low active power


• phase wise low power factor
• phase wise reactive power and apparent power as service values

Following features are available:

• Definite time stage for low active power protection


• Definite time stage for low power factor protection
• Individual enabling of Low active power and Low power factor functions
• Low active power trip with 2 selection modes '1 out of 3' and '2 out of 3'
• Phase wise calculated values of apparent power, reactive power, active power and power
factor are available as service values
• Insensitive to small variations in voltage and current

16.8.2.3 Function block GUID-CB3033A2-D2AD-42CE-AAAE-1918A8A2861C v1

LAPPGAPC
I3P* TRLAP
U3P* TRLPF
BLOCK TRLPFL1
BLKTR TRLPFL2
TRLPFL3
STLAP
STLPF
STLAPL1
STLAPL2
STLAPL3
STLPFL1
STLPFL2
STLPFL3

IEC09000763-1-en.vsd
IEC09000763 V1 EN-US

Figure 517: LAPPGAPC function block

16.8.2.4 Signals
PID-3520-INPUTSIGNALS v6

Table 593: LAPPGAPC Input signals


Name Type Default Description
I3P GROUP - Three phase group signal for current
SIGNAL
U3P GROUP - Three phase group signal for voltage
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Block all trip signals of the funtction

Line distance protection REL670 869


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 506 370-UEN J
Scheme communication

PID-3520-OUTPUTSIGNALS v6

Table 594: LAPPGAPC Output signals


Name Type Description
TRLAP BOOLEAN Trip low active power
TRLPF BOOLEAN Trip low power factor
TRLPFL1 BOOLEAN Trip low power factor phase 1
TRLPFL2 BOOLEAN Trip low power factor phase 2
TRLPFL3 BOOLEAN Trip low power factor phase 3
STLAP BOOLEAN Start low active power
STLPF BOOLEAN Start low power factor
STLAPL1 BOOLEAN Start low active power phase 1
STLAPL2 BOOLEAN Start low active power phase 2
STLAPL3 BOOLEAN Start low active power phase 3
STLPFL1 BOOLEAN Start low power factor phase 1
STLPFL2 BOOLEAN Start low power factor phase 2
STLPFL3 BOOLEAN Start low power factor phase 3

16.8.2.5 Settings
PID-3520-SETTINGS v6

Table 595: LAPPGAPC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
OperationLAP Off - - Off Operation low active power Off/On
On
OpMode 2 out of 3 - - 2 out of 3 Trip mode low active power 2out of 3
1 out of 3 or 1 out of 3
LAP< 2.0 - 100.0 %SB 0.1 5.0 3 Phase start value for low active
power in % of SBase
tOpLAP 0.000 - 60.000 s 0.001 0.010 Time delay to operate for low active
power
OperationLPF Off - - Off Operation low power factor Off/On
On
LPF< 0.00 - 1.00 - 0.01 0.40 Start value for low power factor
tOpLPF 0.000 - 60.000 s 0.001 0.010 Time delay to operate for low power
factor

Table 596: LAPPGAPC Group settings (advanced)


Name Values (Range) Unit Step Default Description
UGenZeroDb 0.0 - 100.0 %UB 0.1 30.0 Zero point Clamping in % of UBase
IGenZeroDb 0.0 - 100.0 %IB 0.1 3.0 Zero point clamping in % of IBase

Table 597: LAPPGAPC Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

870 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 16
Scheme communication

16.8.2.6 Monitored data


PID-3520-MONITOREDDATA v6

Table 598: LAPPGAPC Monitored data


Name Type Values (Range) Unit Description
SL1 REAL - MVA Apparent power for phase 1
SL2 REAL - MVA Apparent power for phase 2
SL3 REAL - MVA Apparent power for phase 3
PL1 REAL - MW Active power for phase 1
PL2 REAL - MW Active power for phase 2
PL3 REAL - MW Active power for phase 3
QL1 REAL - MVAr Reactive power for phase 1
QL2 REAL - MVAr Reactive power for phase 2
QL3 REAL - MVAr Reactive power for phase 3
PFL1 REAL - - Power factor phase 1
PFL2 REAL - - Power factor phase 2
PFL3 REAL - - Power factor phase 3

16.8.2.7 Operation principle GUID-FF753775-9D02-4CC6-AD0C-7ED1693F6372 v2

Low active power and low power factor protection (LAPPGAPC) calculates power and power
factor from voltage and current values. Trip signal must be set independently for low active
power and low power factor condition after definite time delay.

Active power calculation

LAPPGAPC calculates single phase complex power of L1, L2 and L3 loop by following equations.
From this complex apparent power, the real and imaginary parts can be respective active and
reactive power values of respective phases. All the apparent power values given out of the
function are absolute values. The active power is the real part of the calculated apparent
power.

S L1 = U L1 × I L1
EQUATION2243 V1 EN-US (Equation 176)

S L2 = U L2 × IL2
EQUATION2244 V1 EN-US (Equation 177)

S L3 = U L3 × I L3
EQUATION2245 V1 EN-US (Equation 178)

Power factor calculation

Power factor is a ratio of active power to apparent power. The function calculates power
factor from the calculated values of active power and apparent power of L1, L2 and L3 loop by
following equation:

PL1
pf L1 =
S L1
EQUATION2246 V1 EN-US (Equation 179)

Line distance protection REL670 871


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 506 370-UEN J
Scheme communication

PL 2
pf L 2 =
SL2
EQUATION2247 V1 EN-US (Equation 180)

PL 3
pf L 3 =
SL3
EQUATION2248 V1 EN-US (Equation 181)

Active power trip mode

The low active power functionality has a trip mode setting. According to this setting, trip is
activated if the low active power is detected in one out of three phases or two out of three
phases respectively. These two modes are user settable through setting OpMode.

Zero clamping filtering

The function will do zero clamping to disable the calculation if the current and voltage values
of a particular phase are less than 30% of UBase for voltage and 3% of IBase for current value.

Calculation

The active power setting value used for detection of under power must be given as a three-
phase value. The design starts to calculate internally the per phase value from this setting and
detect phase wise under power condition individually. The power factor start value is common
for all the three phases.

Phase wise analog values apparent power, active power, reactive power and power factor are
available as service values.

STLAPLx

P < LAP<
I3P TRLAP
t
Calculation P and
pf
U3P

STLPFLx

pf < pf<
TRLPFLx
t

IEC10000011-1-en.vsd
IEC10000011 V1 EN-US

Figure 518: Logic diagram of Low active power and low power factor protection
(LAPPGAPC)

872 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 16
Scheme communication

16.8.2.8 Technical data


GUID-B5714FAE-A87D-4C2D-A167-6CB3522CE1D5 v5

Table 599: LAPPGAPC technical data


Function Range or value Accuracy
Operate value, low active power (2.0-100.0)% of SBase ±1.0% of Sr

Reset ratio, low active power <105% -


Operate value, low power factor 0.00-1.00 ±0.02
Independent time delay to operate for (0.000-60.000) s ±0.2% or ±40 ms whichever is
low active power at 1.2 x Pset to 0.8 x greater
Pset

Independent time delay to operate for (0.000-60.000) s ±0.2% or ±40 ms whichever is


low power factor at 1.2 x PFset to 0.8 x greater
PFset

Critical impulse time, low active power 10 ms typically at 1.2 x Pset to 0.8 -
x Pset

Impulse margin time, low active power 10 ms typically -

16.8.3 Compensated over and undervoltage protection COUVGAPC GUID-41C1AD2A-3E57-40A9-9039-F159A3CE3DF8 v1

16.8.3.1 Identification
GUID-F5F76C4D-DD25-4695-9FF1-6B45C696CC5E v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Compensated over and undervoltage COUVGAPC - 59_27
protection

16.8.3.2 Functionality GUID-229EB419-0903-46FA-9192-BBB35725C841 v2

Compensated over and undervoltage protection (COUVGAPC) function calculates the remote
end voltage of the transmission line utilizing local measured voltage, current and with the help
of transmission line parameters, that is, line resistance, reactance, capacitance and local shunt
reactor. For protection of long transmission line for in zone faults, COUVGAPCcan be
incorporated with local criteria within direct transfer trip logic to ensure tripping of the line
only under abnormal conditions.

Line distance protection REL670 873


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 506 370-UEN J
Scheme communication

16.8.3.3 Function block GUID-7A5D719C-3C29-43A8-B213-9FDABB4B05E6 v1

COUVGAPC
I3P* TRUV
U3P* TROV
BLOCK TRUVL1
BLKTR TRUVL2
SWIPOS TRUVL3
TROVL1
TROVL2
TROVL3
STUV
STOV
STUVL1
STUVL2
STUVL3
STOVL1
STOVL2
STOVL3

IEC09000764-1-en.vsd
IEC09000764 V1 EN-US

Figure 519: COUVGAPC function block

16.8.3.4 Signals
PID-3480-INPUTSIGNALS v8

Table 600: COUVGAPC Input signals


Name Type Default Description
I3P GROUP - Group signal for current inputs
SIGNAL
U3P GROUP - Group signal for voltage inputs
SIGNAL
BLOCK BOOLEAN 0 Block of the function
BLKTR BOOLEAN 0 Blocks all operate outputs
SWIPOS BOOLEAN 1 Local shunt reactor connected or not

PID-3480-OUTPUTSIGNALS v8

Table 601: COUVGAPC Output signals


Name Type Description
TRUV BOOLEAN Common trip signal for compensated under voltage
TROV BOOLEAN Common trip signal for compensated over voltage
TRUVL1 BOOLEAN Trip signal for compensated under voltage of phase 1
TRUVL2 BOOLEAN Trip signal for compensated under voltage of phase 2
TRUVL3 BOOLEAN Trip signal for compensated under voltage of phase 3
TROVL1 BOOLEAN Trip signal for compensated over voltage of phase 1
TROVL2 BOOLEAN Trip signal for compensated over voltage of phase 2
TROVL3 BOOLEAN Trip signal for compensated over voltage of phase 3
STUV BOOLEAN Common start signal for compensated under voltage
STOV BOOLEAN Common start signal for compensated over voltage
STUVL1 BOOLEAN Start signal for compensated under voltage of phase 1
STUVL2 BOOLEAN Start signal for compensated under voltage of phase 2
STUVL3 BOOLEAN Start signal for compensated under voltage of phase 3
Table continues on next page

874 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 16
Scheme communication

Name Type Description


STOVL1 BOOLEAN Start signal for compensated over voltage of phase 1
STOVL2 BOOLEAN Start signal for compensated over voltage of phase 2
STOVL3 BOOLEAN Start signal for compensated over voltage of phase 3

16.8.3.5 Settings
PID-3480-SETTINGS v8

Table 602: COUVGAPC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
OperationUV Off - - On Operation compensated under
On voltage Off/On
U< 1 - 100 %UB 1 70 Compensated under voltage level in %
of UBase
tUV 0.000 - 60.000 s 0.001 1.000 Time delay to trip under voltage
OperationOV Off - - On Operation compensated over voltage
On Off/On
U> 1 - 200 %UB 1 120 Compensated over voltage level in %
of UBase
tOV 0.000 - 60.000 s 0.001 5.000 Time delay to trip over voltage

Table 603: COUVGAPC Group settings (advanced)


Name Values (Range) Unit Step Default Description
HystAbs 0.0 - 50.0 %UB 0.1 0.5 Hysteresis absolute for compensated
over/under voltage in % of UBase

Table 604: COUVGAPC Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups
R1 0.01 - 3000.00 Ohm 0.01 5.00 Positive sequence resistance per
phase for the line in ohm
X1 0.01 - 3000.00 Ohm 0.01 40.00 Positive sequence reactance per
phase for the line in ohm
Xc 1.00 - 10000.00 Ohm 0.01 1000.00 Half of equivalent capacitive
reactance per phase in ohm
EnShuntReactor Off - - On Enable setting if shunt reactor
On connected in line
Xsh 1.00 - 10000.00 Ohm 0.01 1500.00 Per phase reactance of local Shunt
Reactor in ohm

Line distance protection REL670 875


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 506 370-UEN J
Scheme communication

16.8.3.6 Monitored data


PID-3480-MONITOREDDATA v8

Table 605: COUVGAPC Monitored data


Name Type Values (Range) Unit Description
CMPUL1 REAL - kV Compensated voltage of phase 1
CMPUL2 REAL - kV Compensated voltage of phase 2
CMPUL3 REAL - kV Compensated voltage of phase 3

16.8.3.7 Operation principle GUID-F0E1BCC7-2010-4B48-9A6F-9A2D92107AD8 v2

Compensated over and undervoltage protection (COUVGAPC) function is phase segregated


and mainly used for local criteria check in Direct transfer trip. The principle is to utilize local
measured voltage and current to calculate the voltage at the remote end of the line.

The main measured inputs to COUVGAPC are three-phase voltage and current signals.
COUVGAPCuses line resistance, reactance and line charging capacitance to calculate the
remote end voltage. It also takes the input for local shunt reactor, connected at the line side of
the line breaker, reactance value. The calculated voltage is referred to as compensated voltage.

STOV

TROV
Over voltage

U3P STOVLx
comparator
I3P TRIPOVLx
t
Compensated
SWIPOS voltage calculation STUVLx
EnShuntReactor &
TRIPUVLx
Under voltage t
TRUV
comparator
STUV

IEC09000782-1-en.vsd
IEC09000782 V1 EN-US

Figure 520: Logic diagram of Compensated over and undervoltage protection


(COUVGAPC)
The formula used for calculation of compensated voltage is as follows:

Uremote = Ulocal – (Ilocal – j x Ulocal/Xsr + j x Ulocal/Xcp) x Zsetting

Where:
Uremote calculated voltage at the opposite side of line

Ulocal measured local voltage

Ilocal measured local current

Xsr reactance of local line connected shunt reactor, if applicable

Xcp half of equivalent reactance of line distributed capacitor

Above calculated compensated voltage is compared to preset over and under voltage levels
set as percentage of base voltage UBase. If the calculated voltage exceeds setting in any

876 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 16
Scheme communication

phase, COUVGAPC generates start and trip signals for that phase and common start and trip
signals. Independent enabling for overvoltage and undervoltage are available with definite
time delay. If shunt reactor is not present in the system, COUVGAPC does not include any
effect of shunt reactor while calculating the compensated voltage. This shunt reactor
calculation is enabled when both input SWIPOS is 1 and setting parameter EnShuntReactor is
On. Run time change in EnShuntReactor setting parameter restarts the IED and SWIPOS input
signal is used to enable/disable the shunt reactor calculations.

Calculations

• All resistance and reactance considered in compensated voltage calculation are primary
side values.
• Calculation of shunt reactor reactance in ohms from given MVAr rating:

2
UN
X sr =
QN
EQUATION2249 V1 EN-US (Equation 182)

Where:
UN line to line voltage

QN is total three phase MVAr of shunt reactor


• If total line capacitance (Ctotal) is known then half line capacitive reactance:

2
X cp =
wCtotal
EQUATION2250 V1 EN-US (Equation 183)

and if total line capacitive reactance XcTotal is known:

X cp = 2 X cTotal
EQUATION2251 V1 EN-US (Equation 184)

Compensated voltage for all three phases is available as service values.

16.8.3.8 Technical data


GUID-D9EADF1B-5FC7-4FDB-BF38-95BDBC4D7C3D v5

Table 606: COUVGAPC technical data


Function Range or value Accuracy
Operate value, undervoltage (1-100)% of UBase ±0,5% of Ur

Absolute hysteresis (0.00–50.0)% of UBase ±0.5% of Ur at U ≤ Ur


±0.5% of U at U > Ur

Critical impulse time, undervoltage 10 ms typically at 1.2 x Uset to 0.8 x -


Uset

Impulse margin time, undervoltage 15 ms typically -


Operate value, overvoltage (1-200)% of UBase ±0.5% of Ur at U≤Ur
± 0.5% of U at U>Ur

Critical impulse time, overvoltage 10 ms typically at 0.8 x Uset to 1.2 x -


Uset

Table continues on next page

Line distance protection REL670 877


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 506 370-UEN J
Scheme communication

Function Range or value Accuracy


Impulse margin time, overvoltage 15 ms typically -
Independent time delay for (0.000-60.000) s ±0.2% or ±40 ms whichever is
undervoltage functionality at 1.2 x greater
Uset to 0.8 x Uset

Independent time delay for (0.000-60.000) s ±0.2% or ±40 ms whichever is


overvoltage functionality at 0.8 x greater
Uset to 1.2 x Uset

16.8.4 Sudden change in current variation SCCVPTOC GUID-61E9C823-5313-4682-93CB-2BA6AC0A0640 v1

16.8.4.1 Identification
GUID-3B6E6472-8153-4D8F-874B-DF68891296C8 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Sudden change in current variation SCCVPTOC - 51

16.8.4.2 Functionality GUID-413851A9-5EB7-4C48-8F5D-E30E470EFFAF v2

Sudden change in current variation (SCCVPTOC) function is a fast way of finding any
abnormality in line currents. When there is a fault in the system, the current changes faster
than the voltage. SCCVPTOC finds abnormal condition based on phase-to-phase current
variation. The main application is as a local criterion to increase security when transfer trips
are used.

16.8.4.3 Function block GUID-98592177-56F1-400E-AE03-02D33C12B94E v1

SCCVPTOC
I3P* TRIP
BLOCK START
BLKTR

IEC09000765-1-en.vsd
IEC09000765 V1 EN-US

Figure 521: SCCVPTOC function block

16.8.4.4 Signals
PID-3585-INPUTSIGNALS v5

Table 607: SCCVPTOC Input signals


Name Type Default Description
I3P GROUP - Three phase to phase current samples group
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Block trip signals

878 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 16
Scheme communication

PID-3585-OUTPUTSIGNALS v6

Table 608: SCCVPTOC Output signals


Name Type Description
TRIP BOOLEAN Common trip signal
START BOOLEAN Common start signal

16.8.4.5 Settings
PID-3585-SETTINGS v6

Table 609: SCCVPTOC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
I> 5 - 100 %IB 1 20 Fixed threshold setting in % of IBase
tHold 0.000 - 60.000 s 0.001 0.500 Hold time for operate signals

Table 610: SCCVPTOC Group settings (advanced)


Name Values (Range) Unit Step Default Description
tDelay 0.000 - 0.005 s 0.001 0.002 Time delay for start and trip signals

Table 611: SCCVPTOC Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

16.8.4.6 Operation principle GUID-53346F67-4CF8-4E74-83AD-5DF32DECAA0A v2

Sudden change in current variation (SCCVPTOC) function calculates the variation in phase-to-
phase current and gives the START output when this variation crosses the sum of start level
and float threshold for a time of tDelay. The variation is calculated for all the three phase-to-
phase currents.

The variation in the current is calculated using the following equation:

Di = i ( t ) - 2 × i ( t - T ) + i ( t - 2T )
EQUATION2252 V1 EN-US

Where:
i(t) Amplitude of the current at the present instant
i(t-T) Amplitude of the current at the instant exactly one cycle time before
i(t-2T) Amplitude of the current at the instant exactly two cycle time before

Criteria:

Di > i (1.8 × DIT + I >)


EQUATION2253 V1 EN-US (Equation 185)

Line distance protection REL670 879


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 506 370-UEN J
Scheme communication

I>: start level

It is the full-circle integral of the phase-to-phase current variation

1 2T -1
DIT = å Di ( t - n )
T n =T
EQUATION2254 V1 EN-US (Equation 186)

T: the count of the sampling value in one cycle

If the above criteria becomes true for a time of tDelay, then respective START output is
activated provided the BLOCK input is false, and the respective TRIP outputs is activated for
the time of tHold provided the BLKTR and BLOCK input is false.

16.8.4.7 Technical data


GUID-4BF21D95-4517-424E-BC23-6156EA0E253C v4

Table 612: SCCVPTOC technical data


Function Range or value Accuracy
Operate value, overcurrent (5-100)% of IBase ±2.0% of Ir

Hold time for operate signal at 0 to (0.000-60.000) s ±0.2% or ±15 ms whichever is


2 x Iset greater

16.8.5 Carrier receive logic LCCRPTRC GUID-13BF45AF-B04C-4C6D-B59D-79A51241C449 v1

16.8.5.1 Identification
GUID-D420E532-37DC-442F-B847-8F73EE8527A7 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Carrier receive logic LCCRPTRC - 94

16.8.5.2 Functionality GUID-79AB9B9E-9200-44D7-B4EE-57C9E7BB74A9 v2

In Direct transfer trip (DTT) scheme, the received CR signal gives the trip to the circuit breaker
after checking certain local criteria functions in order to increase the security of the overall
tripping functionality. Carrier receive logic (LCCRPTRC) function gives final trip output of the
DTT scheme.

Features:

• Carrier redundancy to ensure security in DTT scheme


• Blocking function output on CR Channel Error
• Phase wise trip outputs

880 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 16
Scheme communication

16.8.5.3 Function block GUID-B90E2B88-8C17-4B9C-8BC0-E3194559A4D1 v1

LCCRPTRC
BLOCK TRIP
LOCTR TRL1
LOCTRL1 TRL2
LOCTRL2 TRL3
LOCTRL3
CHERR1
CHERR2
CR1
CR2

IEC09000766-1-en.vsd
IEC09000766 V1 EN-US

Figure 522: LCCRPTRC function block

16.8.5.4 Signals
PID-3481-INPUTSIGNALS v6

Table 613: LCCRPTRC Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
LOCTR BOOLEAN 0 Local common trip signal coming from DTT
LOCTRL1 BOOLEAN 0 Local trip signal for phase 1 coming from DTT
LOCTRL2 BOOLEAN 0 Local trip signal for phase 2 coming from DTT
LOCTRL3 BOOLEAN 0 Local trip signal for phase 3 coming from DTT
CHERR1 BOOLEAN 0 Channel error indication flag for carrier receive 1
CHERR2 BOOLEAN 0 Channel error indication flag for carrier receive 2
CR1 BOOLEAN 0 Carrier receive 1
CR2 BOOLEAN 0 Carrier receive 2

PID-3481-OUTPUTSIGNALS v6

Table 614: LCCRPTRC Output signals


Name Type Description
TRIP BOOLEAN Common trip
TRL1 BOOLEAN Trip phase 1
TRL2 BOOLEAN Trip phase 2
TRL3 BOOLEAN Trip phase 3

16.8.5.5 Settings
PID-3481-SETTINGS v5

Table 615: LCCRPTRC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
ChMode 2 Out Of 2 - - 2 Out Of 2 Setting to select 1/2 or 2/2 mode
1 Out Of 2
tOperate 0.000 - 60.000 s 0.001 0.100 Time delay to operate

Line distance protection REL670 881


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 506 370-UEN J
Scheme communication

16.8.5.6 Operation principle GUID-203F41ED-D08B-41E1-AF54-DFFBECCE1F06 v2

The functionality of the Carrier receive logic (LCCRPTRC) is to release the TRIP signal for DTT
scheme based on the LOCTRL1, LOCTRL2, LOCTRL3, and LOCTR signals coming from local
criterion, and the Carrier receive signals CR1 and CR2. There are two modes of operation 1 out
of 2 and 2 out of 2. In the case of the 1 out of 2 mode if any one of the carrier signal is received
then the trip signals will be released, and in 2 out of 2 mode both the CRs should be high to
release trip signal. If any one of the channel error signals is high in 2 out of 2 mode, then logic
automatically switches to 1 out of 2 mode after a time delay of 200 ms. After switching to 1/2
mode under channel error condition and if channel error gets cleared the mode will switch
back only after a time delay of 200 ms.

If the input channel error signal is high then the respective carrier receive signal will be
blocked.

The complete function can be blocked by setting the BLOCK input high.

16.8.5.7 Technical data


GUID-C99E063D-B377-40D5-8481-9F46D4166AED v3

Table 616: LCCRPTRC technical data


Function Range or value Accuracy
Operation mode 1 Out Of 2 -
2 Out Of 2
Independent time delay (0.000-60.000) s ±0.2% or ±35 ms whichever is
greater

16.8.6 Negative sequence overvoltage protection LCNSPTOV GUID-F15A69BA-58B1-4F3E-AE12-11FF71B96021 v1

16.8.6.1 Identification
GUID-C0F8D64B-FBCD-4115-9A5A-23B252CB7E45 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Negative sequence overvoltage LCNSPTOV - 47
protection

16.8.6.2 Functionality GUID-C5CBB6A2-780D-4008-98E3-455A404D32CB v2

Negative sequence components are present in all types of fault condition. Negative sequence
voltage and current get high values during unsymmetrical faults.

16.8.6.3 Function block GUID-F0F40881-AF96-45C4-8157-7EE6DE60C23A v1

LCNSPTOV
U3P* TRIP
BLOCK START
BLKTR

IEC09000767-1-en.vsd
IEC09000767 V1 EN-US

Figure 523: LCNSPTOV Function block

882 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 16
Scheme communication

16.8.6.4 Signals
PID-3618-INPUTSIGNALS v6

Table 617: LCNSPTOV Input signals


Name Type Default Description
U3P GROUP - Three phase group signal for voltage inputs
SIGNAL
BLOCK BOOLEAN 0 Block overall function
BLKTR BOOLEAN 0 Block trip output

PID-3618-OUTPUTSIGNALS v6

Table 618: LCNSPTOV Output signals


Name Type Description
TRIP BOOLEAN Trip signal for negative sequence over voltage
START BOOLEAN Start signal for negative sequence over voltage

16.8.6.5 Settings
PID-3618-SETTINGS v6

Table 619: LCNSPTOV Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
U2> 1 - 200 %UB 1 10 Negative sequence over voltage start
value in % of UBase
tU2 0.000 - 120.000 s 0.001 2.000 Time delay to operate

Table 620: LCNSPTOV Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

16.8.6.6 Monitored data


PID-3618-MONITOREDDATA v6

Table 621: LCNSPTOV Monitored data


Name Type Values (Range) Unit Description
U2 REAL - kV Neagative sequence voltage value

16.8.6.7 Operation principle GUID-ADD0FC96-B81F-458D-AEA3-94C374128FB0 v2

Negative sequence over voltage protection (LCNSPTOV) is a definite time stage comparator
function. The negative sequence input voltage from the SMAI block is connected as input to
the function through a group connection U3P in PCM600. This voltage is compared against the
preset value and a start signal will be set high if the input negative sequence voltage is greater
than the preset value U2>. Trip signal will be set high after a time delay setting of tU2. There is

Line distance protection REL670 883


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 506 370-UEN J
Scheme communication

a BLOCK input which will block the complete function. BLKTR will block the trip output. The
negative sequence voltage is also available as service value output U2.

16.8.6.8 Technical data


GUID-122A206E-27D2-4D15-AD5A-86B68F1ED559 v5

Table 622: LCNSPTOV technical data


Function Range or value Accuracy
Operate value, negative sequence (1-200)% of UBase ±0.5% of Ur at U≤Ur
overvoltage ±0.5% of U at U>Ur

Reset ratio, negative sequence >95% at (10–200)% of UBase -


overvoltage
Operate time, start at 0 to 2 x Uset Min. = 15 ms -
Max. = 30 ms
Reset time, start at 2 x Uset to 0 Min. = 15 ms -
Max. = 30 ms
Critical impulse time, negative 10 ms typically at 0 to 2 x Uset -
sequence overvoltage
Impulse margin time, negative 15 ms typically -
sequence overvoltage
Independent time delay to operate at (0.000-120.000) s ±0.2% or ±40 ms whichever is
0 to 1.2 x Uset greater

16.8.7 Zero sequence overvoltage protection LCZSPTOV GUID-5179ADF5-7A85-4B95-972F-F55566B46709 v1

16.8.7.1 Identification
GUID-0D2A007F-167A-4534-A41B-22C107FEAC46 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Zero sequence overvoltage LCZSPTOV - 59N
protection

16.8.7.2 Functionality GUID-4CF3EC6A-D286-4808-929B-C9302418E4ED v2

Zero sequence components are present in all abnormal conditions involving earth. They can
reach considerably high values during earth faults.

16.8.7.3 Function block GUID-7764289A-A859-4C02-A9A1-B8F963F65138 v1

LCZSPTOV
U3P* TRIP
BLOCK START
BLKTR

IEC09000768-1-en.vsd
IEC09000768 V1 EN-US

Figure 524: LCZSPTOV function block

884 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 16
Scheme communication

16.8.7.4 Signals
PID-3631-INPUTSIGNALS v6

Table 623: LCZSPTOV Input signals


Name Type Default Description
U3P GROUP - Three phase group signal for voltage inputs
SIGNAL
BLOCK BOOLEAN 0 Block overall function
BLKTR BOOLEAN 0 Block TRIP output

PID-3631-OUTPUTSIGNALS v6

Table 624: LCZSPTOV Output signals


Name Type Description
TRIP BOOLEAN TRIP signal for zero sequence over voltage protection
START BOOLEAN Start signal for zero sequence over voltage protection

16.8.7.5 Settings
PID-3631-SETTINGS v6

Table 625: LCZSPTOV Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
3U0> 1 - 200 %UB 1 10 Zero sequence voltage start value in %
of UBase
t3U0 0.000 - 120.000 s 0.001 2.000 Time delay to operate

Table 626: LCZSPTOV Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

16.8.7.6 Monitored data


PID-3631-MONITOREDDATA v6

Table 627: LCZSPTOV Monitored data


Name Type Values (Range) Unit Description
3U0 REAL - kV Zero sequence voltage value

16.8.7.7 Operation principle GUID-901A8A6C-A68B-47CB-9C41-BB0E0BDF7EF8 v2

Zero sequence over voltage protection (LCZSPTOV) is a definite time stage comparator
function. The zero sequence input voltage from the SMAI block is connected as input to the
function through a group connection U3P in PCM600. This voltage is compared against the
preset value and a start signal will be set high if the input zero sequence voltage is greater
than the preset value 3U0>. Trip signal will be set high after a time delay setting of t3U0.

Line distance protection REL670 885


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 506 370-UEN J
Scheme communication

BLOCK input will block the complete function. BLKTR will block the trip output. The zero
sequence voltage will be available as service value output as 3U0.

16.8.7.8 Technical data


GUID-7A8E7F49-F079-42A0-8685-20288FAD5982 v5

Table 628: LCZSPTOV technical data


Function Range or value Accuracy
Operate value, zero sequence (1-200)% of UBase ±0.5% of Ur at U ≤ Ur
overvoltage ±0.5% of U at U > Ur

Reset ratio, zero sequence >95% at (10–200)% of UBase -


overvoltage
Operate time, start at 0 to 2 x Uset Min. = 15 ms -
Max. = 30 ms
Reset time, start at 2 x Uset to 0 Min. = 15 ms -
Max. = 30 ms
Critical impulse time, zero sequence 10 ms typically at 0 to 2 x Uset -
overvoltage
Impulse margin time, zero sequence 15 ms typically -
overvoltage
Independent time delay to operate at (0.000-120.000) s ±0.2% or ±40 ms whichever is
0 to 1.2 x Uset greater

16.8.8 Negative sequence overcurrent protection LCNSPTOC GUID-0593B07A-4F76-4F92-92E9-EB30FC836ABE v1

16.8.8.1 Identification
GUID-EDC20AC7-540D-43DE-8ABF-7A463E115950 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Negative sequence overcurrent LCNSPTOC - 46
protection

16.8.8.2 Functionality GUID-C4F99554-88BC-4F11-9EFE-91BCA6ED1261 v2

Negative sequence components are present in all types of fault condition. They can reach
considerably high values during abnormal operation.

16.8.8.3 Function block GUID-199CCB09-A4D0-4147-9BBD-5D1ADF85CA2F v1

LCNSPTOC
I3P* TRIP
BLOCK START
BLKTR

IEC09000769-1-en.vsd
IEC09000769 V1 EN-US

Figure 525: LCNSPTOC Function block

886 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 16
Scheme communication

16.8.8.4 Signals
PID-3617-INPUTSIGNALS v5

Table 629: LCNSPTOC Input signals


Name Type Default Description
I3P GROUP - Three phase group signal for current inputs
SIGNAL
BLOCK BOOLEAN 0 Block overall function
BLKTR BOOLEAN 0 Block trip signal

PID-3617-OUTPUTSIGNALS v6

Table 630: LCNSPTOC Output signals


Name Type Description
TRIP BOOLEAN Trip signal negative sequence over current protection
START BOOLEAN Start signal for negative sequence over current protection

16.8.8.5 Settings
PID-3617-SETTINGS v6

Table 631: LCNSPTOC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
I2> 3 - 2500 %IB 1 100 Negative sequence over current start
value in % of IBase
tI2 0.000 - 60.000 s 0.001 0.000 Time delay to operate

Table 632: LCNSPTOC Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

16.8.8.6 Monitored data


PID-3617-MONITOREDDATA v5

Table 633: LCNSPTOC Monitored data


Name Type Values (Range) Unit Description
I2 REAL - A Neagative sequence current value

16.8.8.7 Operation principle GUID-C7D22C1D-2441-4C7B-938B-E7B47559D3C5 v2

Negative sequence overcurrent protection (LCNSPTOC) is a definite time stage comparator


function. The negative sequence input current from the SMAI block is connected as input to
the function through a group connection I3P in PCM600. This current is compared against the
preset value and a start signal will be set high if the input negative sequence current is greater
than the preset value I2>. Trip signal will be set high after a time delay setting of tI2. BLOCK

Line distance protection REL670 887


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 506 370-UEN J
Scheme communication

input will block the complete function. BLKTR will block the trip output. The negative sequence
current is available as service value output I2.

16.8.8.8 Technical data


GUID-0E964441-43DE-43B6-B454-485FBBF66B5C v5

Table 634: LCNSPTOC technical data


Function Range or value Accuracy
Operate value, negative sequence (3 - 2500)% of IBase ±1.0% of Ir at I ≤ Ir
overcurrent ±1.0% of I at I > Ir

Reset ratio, negative sequence >95% at (50–2500)% of IBase -


overcurrent
Operate time, start at 0 to 2 x Iset Min. = 15 ms -
Max. = 25 ms
Reset time, start at 2 x Iset to 0 Min. = 15 ms -
Max. = 25 ms
Operate time, start at 0 to 10 x Iset Min. = 10 ms -
Max. = 20 ms
Reset time, start at 10 x Iset to 0 Min. = 20 ms -
Max. = 35 ms
Critical impulse time, negative sequence 10 ms typically at 0 to 2 x Iset -
overcurrent 2 ms typically at 0 to 10 x Iset

Impulse margin time, negative sequence 15 ms typically -


overcurrent
Independent time delay at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±35 ms, whichever is
greater
Transient overreach, start function <10% at τ = 100 ms -

16.8.9 Zero sequence overcurrent protection LCZSPTOC GUID-6F355F11-2863-4E05-A72C-FB4D6A1A6C0F v1

16.8.9.1 Identification
GUID-581BA9F0-7886-4E46-84B6-37E8B6962934 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Zero sequence overcurrent LCZSPTOC - 51N
protection

16.8.9.2 Functionality GUID-F0C38DA1-2F39-46DE-AFFE-F919E6CF4A57 v2

Zero sequence components are present in all abnormal conditions involving earth. They have a
considerably high value during earth faults.

888 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 16
Scheme communication

16.8.9.3 Function block GUID-2EBCFED9-1980-4B9C-A27B-BFB07B279B5C v1

LCZSPTOC
I3P* TRIP
BLOCK START
BLKTR

IEC09000770-1-en.vsd
IEC09000770 V1 EN-US

Figure 526: LCZSPTOC Function block

16.8.9.4 Signals
PID-3632-INPUTSIGNALS v5

Table 635: LCZSPTOC Input signals


Name Type Default Description
I3P GROUP - Three phase group signal for current inputs
SIGNAL
BLOCK BOOLEAN 0 Block overall function
BLKTR BOOLEAN 0 Block trip output

PID-3632-OUTPUTSIGNALS v6

Table 636: LCZSPTOC Output signals


Name Type Description
TRIP BOOLEAN Trip signal for zero sequence over current protection
START BOOLEAN Start signal for zero sequence over current protection

16.8.9.5 Settings
PID-3632-SETTINGS v6

Table 637: LCZSPTOC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
3I0> 3 - 2500 %IB 1 100 Zero sequence over current start value
in % of IBase
t3I0 0.000 - 60.000 s 0.001 0.000 Time delay to operate

Table 638: LCZSPTOC Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

16.8.9.6 Monitored data


PID-3632-MONITOREDDATA v5

Table 639: LCZSPTOC Monitored data


Name Type Values (Range) Unit Description
3I0 REAL - A Zero sequence current value

Line distance protection REL670 889


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 506 370-UEN J
Scheme communication

16.8.9.7 Operation principle GUID-AAB75539-3C71-4B32-97DA-4D1D349B25E5 v2

Zero sequence overcurrent protection (LCZSPTOC) is a definite time stage comparator


function. The zero sequence input current from the SMAI block is connected as input to the
function through a group connection I3P in PCM600. This current is compared against the
preset value and a start signal will be set high if the input zero sequence current is greater
than the preset value 3I0>. Trip signal will be set high after a time delay setting of t3I0. BLOCK
input will block the complete function. BLKTR will block the trip output. The zero sequence
current is available as service value output 3I0.

16.8.9.8 Technical data


GUID-9F739808-04CA-4988-ABBC-1A444297FDB5 v5

Table 640: LCZSPTOC technical data


Function Range or value Accuracy
Operate value, zero sequence (3-2500)% of IBase ±1.0% of Ir at I≤Ir
overcurrent ±1.0% of I at I>Ir

Reset ratio, zero sequence overcurrent >95% at (50–2500)% of IBase -


Operate time, start at 0 to 2 x Iset Min. = 15 ms -
Max. = 30 ms
Reset time, start at 2 x Iset to 0 Min. = 15 ms -
Max. = 30 ms
Operate time, start at 0 to 10 x Iset Min. = 10 ms -
Max. = 20 ms
Reset time, start at 10 x Iset to 0 Min. = 20 ms -
Max. = 35 ms
Critical impulse time, zero sequence 10 ms typically at 0 to 2 x Iset -
overcurrent 2 ms typically at 0 to 10 x Iset

Impulse margin time, zero sequence 15 ms typically -


overcurrent
Independent time delay at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±35 ms whichever is
greater

16.8.10 Three phase overcurrent LCP3PTOC GUID-510F1FCE-39ED-4B44-89D0-338B085DD8C3 v1

16.8.10.1 Identification
GUID-5FBC4309-C8FB-4CDF-A4D6-84E3A89C81B7 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Three phase overcurrent LCP3PTOC - 51

16.8.10.2 Functionality GUID-AC4FF35E-5D86-421E-82C7-93F600E9F453 v2

Three phase overcurrent (LCP3PTOC) is designed for overcurrent conditions.

Features:

890 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 16
Scheme communication

• Phase wise start and trip signals


• Overcurrent protection
• Phase wise RMS current is available as service values
• Single definite time stage trip function.

16.8.10.3 Function block GUID-CBFCC6B5-F239-4AE1-BDCC-0D192127579D v1

LCP3PTOC
I3P* TRIP
BLOCK TRL1
BLKTR TRL2
TRL3
START
STL1
STL2
STL3

IEC09000771-1-en.vsd
IEC09000771 V1 EN-US

Figure 527: LCP3PTOC Function block

16.8.10.4 Signals
PID-3672-INPUTSIGNALS v5

Table 641: LCP3PTOC Input signals


Name Type Default Description
I3P GROUP - Three phase group signal for current inputs
SIGNAL
BLOCK BOOLEAN 0 Block all binary outputs by resetting timers
BLKTR BOOLEAN 0 Block trip of the function

PID-3672-OUTPUTSIGNALS v6

Table 642: LCP3PTOC Output signals


Name Type Description
TRIP BOOLEAN Common trip signal
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
START BOOLEAN Common start signal
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3

Line distance protection REL670 891


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 506 370-UEN J
Scheme communication

16.8.10.5 Settings
PID-3672-SETTINGS v6

Table 643: LCP3PTOC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation On / Off
On
IOC> 5 - 2500 %IB 1 1000 Start value for 3 phase over current in
% of IBase
tOC 0.000 - 60.000 s 0.001 0.020 Time delay to operate

Table 644: LCP3PTOC Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

16.8.10.6 Monitored data


PID-3672-MONITOREDDATA v6

Table 645: LCP3PTOC Monitored data


Name Type Values (Range) Unit Description
IL1 REAL - A Current RMS value for phase L1
IL2 REAL - A Current RMS value for phase L2
IL3 REAL - A Current RMS value for phase L3

16.8.10.7 Operation principle GUID-ED4F48A8-91AF-4123-94DA-C50E957931DC v2

Three phase overcurrent (LCP3PTOC) is used for detecting over current conditions. LCP3PTOC
starts when the current exceeds the set limit IOC>. It operates with definite time (DT)
characteristics, that is, the function operates after a predefined time tOC and resets when the
fault current disappears. The function contains a blocking functionality. It is possible to block
the function output, timer or the function itself, if desired.

16.8.10.8 Technical data


GUID-C4ACE306-2A54-483D-B247-A479D48CBF5F v5

Table 646: LCP3PTOC technical data


Function Range or value Accuracy
Operate value, overcurrent (5-2500)% of IBase ±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir

Reset ratio, overcurrent > 95% at (50-2500)% of -


IBase
Start time at 0 to 2 x Iset Min. = 10 ms -
Max. = 25 ms
Reset time at 2 x Iset to 0 Min. = 20 ms -
Max. = 35 ms
Table continues on next page

892 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 16
Scheme communication

Function Range or value Accuracy


Critical impulse time, overcurrent 3 ms typically at 0 to 2 x Iset -
1 ms typically at 0 to 10 x Iset

Impulse margin time, overcurrent 10 ms typically -


Independent time delay to operate at 0 to (0.000-60.000) s ±0.2% or ±30 ms whichever is
2 x Iset greater

16.8.11 Three phase undercurrent LCP3PTUC GUID-E8EAE24D-4B69-43DC-BCFC-C4AC63AA66AB v1

16.8.11.1 Identification
GUID-51A4DEE2-C549-483B-9BDD-8F79AD4CFE23 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Three phase undercurrent LCP3PTUC - 37

16.8.11.2 Functionality GUID-E8EA5CE8-ED7A-4FA3-9DAC-83227D53387F v3

Three phase undercurrent function (LCP3PTUC) is designed for detecting loss of load
conditions.

Features:

• Phase wise start and trip signals


• Phase wise RMS current is available as service values
• Single definite time stage trip function

16.8.11.3 Function block GUID-432A180E-CBB4-4928-A898-0748C34D3527 v1

LCP3PTUC
I3P* TRIP
BLOCK TRL1
BLKTR TRL2
TRL3
START
STL1
STL2
STL3

IEC09000772-1-en.vsd
IEC09000772 V1 EN-US

Figure 528: LCP3PTUC Function block

Line distance protection REL670 893


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 506 370-UEN J
Scheme communication

16.8.11.4 Signals
PID-3673-INPUTSIGNALS v5

Table 647: LCP3PTUC Input signals


Name Type Default Description
I3P GROUP - Three phase group signal for current inputs
SIGNAL
BLOCK BOOLEAN 0 Block all binary outputs by resetting timers
BLKTR BOOLEAN 0 Block trip of the function

PID-3673-OUTPUTSIGNALS v6

Table 648: LCP3PTUC Output signals


Name Type Description
TRIP BOOLEAN Common trip signal
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
START BOOLEAN Common start signal
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3

16.8.11.5 Settings
PID-3673-SETTINGS v6

Table 649: LCP3PTUC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation On / Off
On
IUC< 1.00 - 100.00 %IB 0.01 50.00 Start value for 3 phase under current
in % of IBase
tUC 0.000 - 60.000 s 0.001 0.000 Time delay to operate

Table 650: LCP3PTUC Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

16.8.11.6 Monitored data


PID-3673-MONITOREDDATA v6

Table 651: LCP3PTUC Monitored data


Name Type Values (Range) Unit Description
IL1 REAL - A Current RMS value for phase L1
IL2 REAL - A Current RMS value for phase L2
IL3 REAL - A Current RMS value for phase L3

894 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 16
Scheme communication

16.8.11.7 Operation principle GUID-B13D3F9D-358E-4E6C-BD72-A44B00B27BC0 v2

Three phase undercurrent (LCP3PTUC) is used for detecting sudden load loss which is
considered as fault condition. LCP3PTUC starts when the current is less than the set limit
IUC<. It operates with definite time (DT) characteristics, that is, the function operates after a
predefined time tUC and resets when the load current restores. The function contains a
blocking functionality. It is possible to block the function output, timer or the function itself, if
desired.

16.8.11.8 Technical data


GUID-CE2C6F0A-DF49-4AAF-80F0-9CDCBB08E755 v5

Table 652: LCP3PTUC technical data


Function Range or value Accuracy
Operate value, undercurrent (1.00-100.00)% of IBase ±1.0% of Ir

Reset ratio, undercurrent < 105% at (50.00-100.00)% -


of IBase
Start time at 2 x Iset to 0 Min. = 15 ms -
Max. = 30 ms
Reset time at 0 to 2 x Iset Min. = 10 ms -
Max. = 25 ms
Critical impulse time, undercurrent 10 ms typically at 2 x Iset to 0 -

Impulse margin time, undercurrent 10 ms typically -


Independent time delay to operate at 2 x (0.000-60.000) s ±0.2% or ±45 ms whichever is
Iset to 0 greater

Line distance protection REL670 895


Technical manual
© Copyright 2017 ABB. All rights reserved
896
1MRK 506 370-UEN J Section 17
Logic

Section 17 Logic
17.1 Tripping logic SMPPTRC IP14576-1 v4

17.1.1 Identification
SEMOD56226-2 v7

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Tripping logic SMPPTRC 94

1 -> 0
IEC15000314 V1 EN-US

17.1.2 Functionality M12275-3 v14

A function block for protection tripping and general start indication is always provided as a
basic function for each circuit breaker. It provides a settable pulse prolongation time to ensure
a trip pulse of sufficient length, as well as all functionality necessary for correct co-operation
with autoreclosing functions.

The trip function block includes a settable latch function for the trip signal and circuit breaker
lockout.

The trip function can collect start and directional signals from different application functions.
The aggregated start and directional signals are mapped to the IEC 61850 logical node data
model.

17.1.3 Function block M12638-3 v7

SMPPTRC
BLOCK TRIP
BLKLKOUT TRL1
TRIN TRL2
TRINL1 TRL3
TRINL2 TR1P
TRINL3 TR2P
PSL1 TR3P
PSL2 CLLKOU T
PSL3 START
1PTRZ STL1
1PTREF STL2
P3PTR STL3
SETLKOUT STN
RSTLKOUT FW
STDI R REV
IEC05000707-4-en.vsdx
IEC05000707 V4 EN-US

Figure 529: SMPPTRC function block

Line distance protection REL670 897


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

17.1.4 Signals
GUID-2918ECA6-4D98-493F-A33C-2D33DE64AE3B v1

Table 653: SMPPTRC Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
BLKLKOUT BOOLEAN 0 Blocks circuit breaker lockout output (CLLKOUT)
TRIN BOOLEAN 0 Trip all phases
TRINL1 BOOLEAN 0 Trip phase L1
TRINL2 BOOLEAN 0 Trip phase L2
TRINL3 BOOLEAN 0 Trip phase L3
PSL1 BOOLEAN 0 Functional input for phase selection in phase L1
PSL2 BOOLEAN 0 Functional input for phase selection in phase L2
PSL3 BOOLEAN 0 Functional input for phase selection in phase L3
1PTRZ BOOLEAN 0 Input for phase selective carrier aided trip
1PTREF BOOLEAN 0 Input for phase selective earth fault trip
P3PTR BOOLEAN 0 Prepare all tripping to be three-phase
SETLKOUT BOOLEAN 0 Input for setting the circuit breaker lockout function
RSTLKOUT BOOLEAN 0 Input for resetting the circuit breaker lockout function
STDIR INTEGER 0 General start direction input

GUID-D6B3DFE3-F7DF-4602-B57E-764DC9EB0D4A v1

Table 654: SMPPTRC Output signals


Name Type Description
TRIP BOOLEAN General trip output signal
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
TR1P BOOLEAN Trip single-pole
TR2P BOOLEAN Trip two-pole
TR3P BOOLEAN Trip three-pole
CLLKOUT BOOLEAN Circuit breaker lockout output (set until reset)
START BOOLEAN General start signal
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3
STN BOOLEAN Start signal from neutral
FW BOOLEAN General forward signal
REV BOOLEAN General reverse signal

898 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

17.1.5 Settings
GUID-6D6424B9-B676-4D9B-949A-33C74BDC5711 v1

Table 655: SMPPTRC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
Program 3 phase - - 1ph/3ph Three ph; single or three ph; single,
1ph/3ph two or three ph trip
1ph/2ph/3ph
tTripMin 0.000 - 60.000 s 0.001 0.150 Minimum duration of trip output
signal
tWaitForPHS 0.020 - 0.500 s 0.001 0.050 Secure 3-pole trip when phase
selection failed

Table 656: SMPPTRC Group settings (advanced)


Name Values (Range) Unit Step Default Description
TripLockout Off - - Off Latch TRIP output when SETLKOUT
On input is activated
AutoLock Off - - Off Activate CLLKOUT output when TRIP
On output is activated
tEvolvingFault 0.000 - 60.000 s 0.001 2.000 Secure 3-pole tripping at evolving
faults

17.1.6 Operation principle M12255-3 v12

The duration of the trip output signal is settable (tTripMin). The pulse length should be long
enough to secure the opening of the circuit breaker.

There is a single input (TRIN) through which all trip output signals from the protection
functions within the IED or from external protection functions via one or more of the IEDs'
binary inputs are routed. It has a single three-phase trip output (TRIP) to connect to one or
more of the IEDs' binary outputs, as well as to other functions within the IED requiring this
signal.

Line distance protection REL670 899


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

Simplified logic where setting


Program = 3 phase
BLKLKOUT

Final Tripping Circuits


3 phase BLKLKOUT TRIP
TRIP
BLOCK TRL1
BLOCK TRIPALL TRIPALL TRL1
TRIN TRL2
TRIN TRIPL1 TRL2
TRINL1 TRL3
TRINL1 TRIPL2 TRL3
TRINL2
TRINL2 TRIPL3 TR1P
TRINL3
TRINL3 SETLKOUT TR2P
1PTRZ TR3P
1PTRZ RSTLKOUT TR3P
1PTREF CLLKOUT
1PTREF CLLKOUT

SETLKOUT
RSTLKOUT

Simplified logic where setting


Program = 1ph/3ph
BLKLKOUT
Final Tripping Circuits
BLOCK
TRIP
BLKLKOUT TRIP
1ph/3ph TRL1
TRIPALL TRL1
Phase Segregated TRL2
BLOCK TRIPL1 TRIPL1 TRL2
TRIN TRL3
TRIN L1TRIP L1TRIP TRIPL2 TRIPL2 TRL3
TRINL1 TR1P
TRINL1 L2TRIP L2TRIP TRIPL3 TRIPL3 TR1P
TRINL2
TRINL2 L3TRIP L3TRIP SETLKOUT TR2P
TRINL3 TR3P
TRINL3 P3PTR RSTLKOUT TR3P
PSL1 CLLKOUT
PSL1 CLLKOUT
PSL2
PSL2
PSL3
PSL3
1PTRZ
1PTRZ
1PTREF
1PTREF

P3PTR
SETLKOUT
RSTLKOUT

Simplified logic where setting


Program = 1ph/2ph/3ph
BLKLKOUT
Final Tripping Circuits
BLOCK
TRIP
BLKLKOUT TRIP
1ph/2ph/3ph TRL1
TRIPALL TRL1
Phase Segregated BLOCK TRIPL1 TRL2
TRIPL1 TRL2
TRIN TRL3
TRIN L1TRIP L1TRIP TRIPL2 TRIPL2 TRL3
TRINL1 TR1P
TRINL1 L2TRIP L2TRIP TRIPL3 TRIPL3 TR1P
TRINL2 TR2P
TRINL2 L3TRIP L3TRIP SETLKOUT TR2P
TRINL3 P3PTR TR3P
TRINL3 RSTLKOUT TR3P
PSL1 CLLKOUT
PSL1 CLLKOUT
PSL2
PSL2
PSL3
PSL3
1PTRZ
1PTRZ
1PTREF
1PTREF

P3PTR
SETLKOUT
RSTLKOUT

IEC10000266=2=en=Original.vsdx

IEC10000266 V2 EN-US

Figure 530: Simplified logic diagrams with different program modes


SMPPTRC function has separate inputs (TRINL1, TRINL2, TRINL3) which are used for single-
phase and two-phase tripping from the functions which offer phase segregated trip outputs.

The inputs 1PTRZ and 1PTREF enable single- phase and two-phase tripping for those functions
which do not have their own phase selection capability (i.e. which have just a single trip
output). An example of such a protection function is the residual overcurrent protection. The
SMPPTRC function has two inputs for these functions, one for impedance tripping (1PTRZ
used for carrier-aided tripping commands from the scheme communication logic), and one for
earth fault tripping (1PTREF used for tripping from a residual overcurrent protection). External
phase selection for these two trip signals shall be provided via inputs PSL1, PSL2 and PSL3.

900 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

A timer tWaitForPHS, secures a three-phase trip command for these two trip signals in the
absence of the external phase selection signals.

The SMPPTRC function has three trip outputs TRL1, TRL2, TRL3 (besides the three-phase trip
output TRIP), one per phase, to connect to one or more of the IEDs’ binary outputs, as well as
to other functions within the IED requiring these signals. These three output signals shall be
used as trip signals for individual circuit breaker poles. These signals are important for
cooperation with the autorecloser SMBRREC function.

The SMPPTRC function is equipped with logic which secures correct operation for evolving
faults as well as for reclosing on to persistent faults. A binary input P3PTR is provided which
will force all tripping to be three-phase. This input is required in order to cooperate with the
SMBRREC function.

In multi-breaker arrangements, one SMPPTRC function block is used for each circuit breaker.

The lockout function


A tripped circuit breaker can be locked out and prevented from closing by the output close
lockout (CLLKOUT). The reset lockout (RSTLKOUT) is the input for deactivating and resetting
the output close lockout CLLKOUT.

CLLKOUT can be set by an external trip signal from another protection function via the input
SETLKOUT or internally via a three-phase trip with the setting AutoLock = On. If CLLKOUT is
set by an external trip signal from another protection function and setting TripLockout = On,
all trip outputs are set true.

The BLKLKOUT input blocks the circuit breaker lockout output CLLKOUT.

Directional data
Merged directional data from application functions can be provided to the trip function
(SMPPTRC) via the start matrix function (SMAGAPC) connected to the STDIR input.

The directional input signal STDIR is a coded integer signal which may contain up to 14
individual Boolean signals; see Figure 535:

STDIRX=[b0, b1, b2, b3, b4, b5, b6, b7, b8, b9, b10, b11, b12, b13, b14]
b0= START (start)
b1= FW (forward)
b2= REV (reverse)
b3= STL1 (start L1)
b4= FWL1 (forward L1)
b5= REVL1 (reverse L1)
b6= STL2 (start L2)
b7= FWL2 (forward L2)
b8= REVL2 (reverse L2)
b9= STL3 (start L3)
b10= FWL3 (forward L3)
b11= REVL3 (reverse L3)
b12= STN (start N)
b13= FWN (forward N)
b14= REVN (reverse N)

Line distance protection REL670 901


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

The indications for general start START and phase-wise starts STL1, STL2 and STL3, and
neutral STN and general directional forward FW and reverse REV are all available as outputs on
the trip function.

All start and directional outputs are mapped to the IEC 61850 logical node data model of the
trip function. The time stamping is updated each time an operate or start signal is changed:

• The common DIR output (general) is mapped as:

dirGeneral
0 unknown
1 forward
2 backward (reverse)
3 both
• The phase wise directional outputs (DIRL1, DIRL2, DIRL3 and DIRN) are mapped as:

dirPhsA, dirPhsB, dirPhsC, dirNeut


0 unknown
1 forward
2 backward (reverse)

17.1.6.1 Logic diagram M12258-7 v6

tTripMin
BLOCK TRIPALL
OR
AND t

TRINL1
TRINL2
TRINL3
TRIN OR
1PTREF
1PTRZ

IEC05000517=4=en=Original..vsdx
IEC05000517 V4 EN-US

Figure 531: Three-phase front logic — simplified logic diagram

902 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

TRIN
TRINL1
L1TRIP
OR
PSL1
AND

TRINL2
L2TRIP
OR
PSL2
AND

TRINL3
L3TRIP
OR
PSL3
AND

-LOOP

OR OR
OR

AND
AND

OR
tWaitForPHS
-LOOP t

OR

1PTREF AND
AND

1PTRZ OR

IEC10000056=4=en=Original.vsdx

IEC10000056 V4 EN-US

Figure 532: Phase segregated front logic

tTripMin
BLOCK
OR TRIPL1
L1TRIP AND t OR

tEvolvingFault

t TRIP
AND

L2TRIP
L3TRIP
OR
P3PTR

IEC17000065-2-en.vsdx

IEC17000065 V2 EN-US

Figure 533: Simplified additional logic per phase, Program = 1ph/3ph or 1ph/2ph/3ph

Line distance protection REL670 903


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

BLKLKOUT

TRIPL1
TRL1
OR

TRIPL2
TRL2
OR

TRIPL3
TRL3
OR

TRIP
TRIPALL OR
OR
-LOOP

OR
AND
TR3P
AND

10 ms To ensure that the


AND fault is single phase TR1P
t

OR 5 ms To ensure that the


fault is two phase TR2P
t

AND

AND

AND OR
OR

-LOOP
AND

-LOOP
AND
AutoLock
CLKLKOUT
OR AND
SETLKOUT OR AND
3ms
RSTLKOUT t

AND
TripLockout

-LOOP

IEC17000066=1=en=Original.vsdx

IEC17000066 V1 EN-US

Figure 534: Final tripping circuits

Directional logic
IntToBits
STDIR START START
in b0
FW STL1
b1
REV STL2
b2
STL1 STL3
b3
FWL1 STN
b4
REVL1
b5
STL2
b6
FWL2 FW
b7
REVL2 BitsToInt
b8 dirGeneral (61850 Standard)
STL3
b9 0 = unknown
FWL3 b0 out
b10 DIR 1 = forward
REVL3 b1 2 = backward (reverse)
b11
STN 3 = both
b12
FWN REV
b13
REVN
b14
b15

BitsToInt dirPhsA (61850 Standard)


0 = unknown
AND b0 out DIRL1
b0 = START 1 = forward
b1 2 = backward (reverse)
b1 = FW
b2 = REV
b3 = STL1 XOR
b4 = FWL1
b5 = REVL1
b6 = STL2 AND
b7 = FWL2
b8 = REVL2
b9 = STL3 BitsToInt dirPhsB (61850 Standard)
b10 = FWL3
0 = unknown
b11 = REVL3 AND b0 out DIRL2
1 = forward
b12 = STN b1 2 = backward (reverse)
b13 = FWN
b14 = REVN
b15 = N/A XOR

AND

BitsToInt dirPhsC (61850 Standard)


0 = unknown
AND b0 out DIRL3
1 = forward
b1 2 = backward (reverse)

XOR

AND

BitsToInt dirNeut (61850 Standard)


0 = unknown
AND b0 out DIRN
1 = forward
b1 2 = backward (reverse)

XOR

AND

IEC16000179-2-en.vsdx

IEC16000179 V2 EN-US

Figure 535: The directional logic

904 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

17.1.7 Technical data


M12380-1 v14

Table 657: SMPPTRC technical data


Function Range or value Accuracy
Trip action 3-ph, 1/3-ph, 1/2/3-ph -
Minimum trip pulse length (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
3-pole trip delay (0.020-0.500) s ±0.2% or ±15 ms whichever is greater
Evolving fault delay (0.000-60.000) s ±0.2% or ±15 ms whichever is greater

17.2 General start matrix block SMAGAPC

17.2.1 Identification GUID-C6D3DE50-03D2-4F27-82FF-623E81D019F4 v1

Function Description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Generat start matrix block SMAGAPC - -

17.2.2 Functionality GUID-BA516165-96DE-4CD9-979B-29457C7653C0 v3

The Start Matrix (SMAGAPC) merges start and directional output signals from different
application functions and creates a common start and directional output signal (STDIR) to be
connected to the Trip function, see Figure 536.

The purpose of this functionality is to provide general start and directional information for the
IEC 61850 trip logic data model SMPPTRC.

17.2.3 Function block GUID-99B1DF71-F7C4-4954-8688-BC709C3C2A16 v1

SMAGAPC
BLOCK STDIR
STDIR1
STDIR2
STDIR3
STDIR4
STDIR5
STDIR6
STDIR7
STDIR8
STDIR9
STDIR10
STDIR11
STDIR12
STDIR13
STDIR14
STDIR15
STDIR16

IEC16000165-1-en.vsdx
IEC16000165 V1 EN-US

Figure 536: SMAGAPC function block

Line distance protection REL670 905


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

17.2.4 Signals
PID-6906-INPUTSIGNALS v2

Table 658: SMAGAPC Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
STDIR1 INTEGER 0 Start direction input 1
STDIR2 INTEGER 0 Start direction input 2
STDIR3 INTEGER 0 Start direction input 3
STDIR4 INTEGER 0 Start direction input 4
STDIR5 INTEGER 0 Start direction input 5
STDIR6 INTEGER 0 Start direction input 6
STDIR7 INTEGER 0 Start direction input 7
STDIR8 INTEGER 0 Start direction input 8
STDIR9 INTEGER 0 Start direction input 9
STDIR10 INTEGER 0 Start direction input 10
STDIR11 INTEGER 0 Start direction input 11
STDIR12 INTEGER 0 Start direction input 12
STDIR13 INTEGER 0 Start direction input 13
STDIR14 INTEGER 0 Start direction input 14
STDIR15 INTEGER 0 Start direction input 15
STDIR16 INTEGER 0 Start direction input 16

PID-6906-OUTPUTSIGNALS v2

Table 659: SMAGAPC Output signals


Name Type Description
STDIR INTEGER Common start direction output

17.2.5 Settings
PID-6906-SETTINGS v2

Table 660: SMAGAPC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On

17.2.6 Operation principle GUID-02403756-5715-4D6B-9308-540D72979BD0 v3

Start matrix
The Start Matrix function requires that a protection function delivers the directional output
signals in a fixed order to Start Matrix.

A directional input signal STDIRX of the Start Matrix is of type word. Each input contains 14
individual Boolean signals, which are positioned as, see Figure 538.

906 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

STDIRX=[b0, b1, b2, b3, b4, b5, b6, b7, b8, b9, b10, b11, b12, b13, b14]
b0= START (start)
b1= FW (forward)
b2= REV (reverse)
b3= STL1 (startL1)
b4= FWL1 (forwardL1)
b5= REVL1 (reverseL1)
b6= STL2 (startL2)
b7= FWL2 (forwardL2)
b8= REVL2 (reverseL2)
b9= STL3 (startL3)
b10= FWL3 (forwardL3)
b11= REVL3 (reverseL3)
b12= STN (startN)
b13= FWN (forwardN)
b14= REVN (reverseN)

The StartMatrix function contains two function: the START criteria and the DIRECTION criteria,
see Figure 537.

The START criteria is to ensure that a forward and reverse signal shall come together with a
start signal to pass through the block. This is done individually for each protection function
connected to the StartMatrix via the STDIRX inputs, see Figure 538.

All STDIROUT signals are then connected via an OR gate, see Figure 537.

The DIRECTION criteria allow either forward or reverse (phase-wise forward FWLx or forward
neutral FWN or phase-wise reverse REVLx or reverse neutral REVN) to pass through to the
general STDIR output. If both forward and reverse are active phase-wise (e.g. REVLx=FWLx =
True) or at neutral (e.g. FWN = REVN = True) at the same time, none will be shown, see Figure
539.

Line distance protection REL670 907


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

SMAGAPC
(StartMatrix)

START Criteria
STDIR1
STDIRX STDIROUT

START Criteria
STDIR2
STDIRX STDIROUT

START Criteria
STDIR3
STDIRX STDIROUT
DIRECTION Criteria
STDIR
≥1 STDIRIN STDIR
START Criteria
STDIR4
STDIRX STDIROUT

START Criteria
STDIR5
STDIRX STDIROUT

START Criteria
STDIR6
STDIRX STDIROUT

START Criteria
STDIR7
STDIRX STDIROUT

START Criteria
STDIR8
STDIRX STDIROUT

START Criteria
STDIR9
STDIRX STDIROUT

START Criteria
STDIR10
STDIRX STDIROUT

START Criteria
STDIR11
STDIRX STDIROUT

START Criteria
STDIR12
STDIRX STDIROUT

START Criteria
STDIR13
STDIRX STDIROUT

START Criteria
STDIR14
STDIRX STDIROUT

START Criteria
STDIR15
STDIRX STDIROUT

START Criteria
STDIR16
STDIRX STDIROUT

IEC16000161-2-en.vsdx

IEC16000161 V2 EN-US

Figure 537: The StartMatrix function

908 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

START Criteria

START (in)
STL1 (in)
STL2 (in) ≥1 START (out)
STL3 (in)
IntToBits STN (in) BitsToint
STDIRX STDIROUT
in b0 START (in) STL1 (out) START (out) b0 out
b1 FW (in) STL2 (out) FW (out) b1
b2 REV (in) STL3 (out) REV (out) b2
b3 STL1 (in) STN (out) STL1 (out) b3
b4 FWL1 (in) FWL1 (out) b4
b5 REVL1 (in) REVL1 (out) b5
&
b6 STL2 (in) FW (in) STL2 (out) b6
b7 FWL2 (in) FWL2 (out) b7
≥1 FW (out)
b8 REVL2 (in) REVL2 (out) b8
b9 STL3 (in) STL3 (out) b9
b10 FWL3 (in) FWL3 (out) b10
b11 REVL3 (in) & REVL3 (out) b11
REV (in)
b12 STN (in) STN (out) b12
b13 FWN (in) ≥1 REV (out) FWN (out) b13
b14 REVN (in) REVN (out) b14
b15 N/A FALSE b15

& FWL1 (out)


FWL1 (in)

& REVL1 (out)


REVL1 (in)

& FWL2 (out)


FWL2 (in)

& REVL2 (out)


REVL2 (in)

& FWL3 (out)


FWL3 (in)

& REVL3 (out)


REVL3 (in)

& FWN (out)


FWN (in)

& REVN (out)


REVN (in)

IEC16000162-2-en.vsdx

IEC16000162 V2 EN-US

Figure 538: The START Criteria function

DIRECTION Criteria

START (in) START (out)


IntToBits STL1 (in) STL1 (out) BitsToint
STDIRIN STL2 (in) STL2 (out) STDIR
in b0 START (in) START (out) b0 out
STL3 (in) STL3 (out)
b1 FW (in) FW (out) b1
STN (in) STN (out)
b2 REV (in) REV (out) b2
b3 STL1 (in) STL1 (out) b3
FW (in)
b4 FWL1 (in) FWL1 (out) b4
b5 REVL1 (in) REVL1 (out) b5
≥1 FW (out)
b6 STL2 (in) STL2 (out) b6
b7 FWL2 (in) FWL2 (out) b7
b8 REVL2 (in) REVL2 (out) b8
b9 STL3 (in) STL3 (out) b9
REV (in)
b10 FWL3 (in) FWL3 (out) b10
b11 REVL3 (in) REVL3 (out) b11
≥1 REV (out)
b12 STN (in) STN (out) b12
b13 FWN (in) FWN (out) b13
b14 REVN (in) REVN (out) b14
b15 N/A FALSE b15
& FWL1 (out)

FWL1 (in)
=1
REVL1 (in)

& REVL1 (out)

& FWL2 (out)

FWL2 (in)
=1
REVL2 (in)

& REVL2 (out)

& FWL3 (out)

FWL3 (in)
=1
REVL3 (in)

& REVL3 (out)

& FWN (out)

FWN (in)
=1
REVN (in)

& REVN (out)

IEC16000163-2-en.vsdx

IEC16000163 V2 EN-US

Figure 539: The DIRECTION Criteria function

STARTCOMB
To make it possible to provide the directional information from a protection function, a
STARTCOMB block is used in between the application function and the Start Matrix function.

The STARTCOMB function has one block input and 14 Boolean inputs that convert the 14
Boolean inputs into a WORD output STDIR, see Figure 540.

Line distance protection REL670 909


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

STDIRX=[b0, b1, b2, b3, b4, b5, b6, b7, b8, b9, b10, b11, b12, b13, b14]
b0= START (start)
b1= FW (forward)
b2= REV (reverse)
b3= STL1 (startL1)
b4= FWL1 (forwardL1)
b5= REVL1 (reverseL1)
b6= STL2 (startL2)
b7= FWL2 (forwardL2)
b8= REVL2 (reverseL2)
b9= STL3 (startL3)
b10= FWL3 (forwardL3)
b11= REVL3 (reverseL3)
b12= STN (startN)
b13= FWN (forwardN)
b14= REVN (reverseN)

STARTCOMB
BLOCK STDI R
START
FW
REV
STL1
FWL1
REVL1
STL2
FWL2
REVL2
STL3
FWL3
REVL3
STN
FWN
REVN
IEC16000166-2-en.vsdx
IEC16000166 V2 EN-US

Figure 540: STARTCOMB

Protection functions
Some protection functions are provided with start and directional outputs, for example:

• Protection 1: General START, FW and REV


• Protection 2: Phase-wise STLx, FWLx and REVLx (where x = 1, 2 and 3)
• Protection 3: STN, FWN and REVN
• Protection 4: STDIR

Connection example
In Figure 541 below is an example how to connect start and directional signals from protection
functions via STARTCOMB and SMAGAPC to SMPPTRC.

910 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

SMAGAPC
STARTCOMB BLOCK STDIR
PROTECTION 1 BLOCK STDIR STDIR1
START START STDIR2
FW FW STDIR3
REV REV STDIR4
STL1 STDIR5
FWL1 STDIR6 SMPPTRC
REVL1 STDIR7 BLOCK TRIP
STL2 STDIR8 BLKLKOUT TRL1
FWL2 STDIR9 TRIN TRL2
REVL2 STDIR10 TRINL1 TRL3
STL3 STDIR11 TRINL2 TR1P
FWL3 STDIR12 TRINL3 TR2P
REVL3 STDIR13 PSL1 TR3P
STN STDIR14 PSL2 CLLKOUT
FWN STDIR15 PSL3 START
REVN STDIR16 1PTRZ STL1
1PTREF STL2
P3PTR STL3
STARTCOMB SETLKOUT STN
BLOCK STDIR RSTLKOUT FW
START STDIR REV
FW
PROTECTION 2 REV
STL1 STL1
FWL1 FWL1
REVL1 REVL1
STL2 STL2
FWL2 FWL2
REVL2 REVL2
STL3 STL3
FWL3 FWL3
REVL3 REVL3
STN
FWN
REVN

STARTCOMB
BLOCK STDIR
START
FW
REV
STL1
FWL1
REVL1
STL2
FWL2
REVL2
STL3
PROTECTION 4
FWL3
-
PROTECTION 3 REVL3
STDIR
STN STN
-
FWN FWN
-
REVN REVN
IEC16000164-2-en.vsdx
IEC16000164 V2 EN-US

Figure 541: Connection example of protection functions using STARTCOMB, SMAGAPC to


SMPPTRC

17.3 Trip matrix logic TMAGAPC IP15121-1 v4

17.3.1 Identification
SEMOD167882-2 v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Trip matrix logic TMAGAPC - -

Line distance protection REL670 911


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

17.3.2 Functionality M15321-3 v13

The trip matrix logic (TMAGAPC) function is used to route trip signals and other logical output
signals to different output contacts on the IED.

The trip matrix logic function has 3 output signals and these outputs can be connected to
physical tripping outputs according to the specific application needs for settable pulse or
steady output.

17.3.3 Function block SEMOD54400-4 v6

TMAGAPC
BLOCK OUTPUT1
BLK1 OUTPUT2
BLK2 OUTPUT3
BLK3
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16
INPUT17
INPUT18
INPUT19
INPUT20
INPUT21
INPUT22
INPUT23
INPUT24
INPUT25
INPUT26
INPUT27
INPUT28
INPUT29
INPUT30
INPUT31
INPUT32

IEC13000197-1-en.vsd
IEC13000197 V1 EN-US

Figure 542: TMAGAPC function block

17.3.4 Signals
PID-6513-INPUTSIGNALS v4

Table 661: TMAGAPC Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
BLK1 BOOLEAN 0 Block of output 1
BLK2 BOOLEAN 0 Block of output 2
BLK3 BOOLEAN 0 Block of output 3
INPUT1 BOOLEAN 0 Binary input 1
INPUT2 BOOLEAN 0 Binary input 2
INPUT3 BOOLEAN 0 Binary input 3
Table continues on next page

912 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

Name Type Default Description


INPUT4 BOOLEAN 0 Binary input 4
INPUT5 BOOLEAN 0 Binary input 5
INPUT6 BOOLEAN 0 Binary input 6
INPUT7 BOOLEAN 0 Binary input 7
INPUT8 BOOLEAN 0 Binary input 8
INPUT9 BOOLEAN 0 Binary input 9
INPUT10 BOOLEAN 0 Binary input 10
INPUT11 BOOLEAN 0 Binary input 11
INPUT12 BOOLEAN 0 Binary input 12
INPUT13 BOOLEAN 0 Binary input 13
INPUT14 BOOLEAN 0 Binary input 14
INPUT15 BOOLEAN 0 Binary input 15
INPUT16 BOOLEAN 0 Binary input 16
INPUT17 BOOLEAN 0 Binary input 17
INPUT18 BOOLEAN 0 Binary input 18
INPUT19 BOOLEAN 0 Binary input 19
INPUT20 BOOLEAN 0 Binary input 20
INPUT21 BOOLEAN 0 Binary input 21
INPUT22 BOOLEAN 0 Binary input 22
INPUT23 BOOLEAN 0 Binary input 23
INPUT24 BOOLEAN 0 Binary input 24
INPUT25 BOOLEAN 0 Binary input 25
INPUT26 BOOLEAN 0 Binary input 26
INPUT27 BOOLEAN 0 Binary input 27
INPUT28 BOOLEAN 0 Binary input 28
INPUT29 BOOLEAN 0 Binary input 29
INPUT30 BOOLEAN 0 Binary input 30
INPUT31 BOOLEAN 0 Binary input 31
INPUT32 BOOLEAN 0 Binary input 32

PID-6513-OUTPUTSIGNALS v4

Table 662: TMAGAPC Output signals


Name Type Description
OUTPUT1 BOOLEAN OR function betweeen inputs 1 to 16
OUTPUT2 BOOLEAN OR function between inputs 17 to 32
OUTPUT3 BOOLEAN OR function between inputs 1 to 32

Line distance protection REL670 913


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

17.3.5 Settings
PID-6513-SETTINGS v4

Table 663: TMAGAPC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
PulseTime 0.050 - 60.000 s 0.001 0.150 Output pulse time
OnDelay 0.000 - 60.000 s 0.001 0.000 Output on delay time
OffDelay 0.000 - 60.000 s 0.001 0.000 Output off delay time
ModeOutput1 Steady - - Steady Mode for output ,1 steady or pulsed
Pulsed
ModeOutput2 Steady - - Steady Mode for output 2, steady or pulsed
Pulsed
ModeOutput3 Steady - - Steady Mode for output 3, steady or pulsed
Pulsed

17.3.6 Operation principle SEMOD52537-5 v8

The trip matrix logic (TMAGAPC) block is provided with 32 input signals and 3 output signals.
The function block incorporates internal logic OR gates in order to provide grouping of
connected input signals to the three output signals from the function block.

Internal built-in OR logic is made in accordance with the following three rules:

1. when any one of first 16 inputs signals (INPUT1 to INPUT16) has logical value 1 the first
output signal (OUTPUT1) will get logical value 1.
2. when any one of second 16 inputs signals (INPUT17 to INPUT32) has logical value 1 the
second output signal (OUTPUT2) will get logical value 1.
3. when any one of all 32 input signals (INPUT1 to INPUT32) has logical value 1 the third
output signal (OUTPUT3) will get logical value 1.

By use of the settings ModeOutput1, ModeOutput2, ModeOutput3, PulseTime, OnDelay and


OffDelay the behavior of each output can be customized. The OnDelay is always active and will
delay the input to output transition by the set time. The ModeOutput for respective output
decides whether the output shall be steady with an drop-off delay as set by OffDelay or if it
shall give a pulse with duration set by PulseTime. Note that for pulsed operation and that the
inputs are connected in an OR-function, a new pulse will only be given on the output if all
related inputs are reset and then one is activated again. For steady operation the OffDelay will
start when all related inputs have reset. Detailed logical diagram is shown in figure 543

914 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

PulseTime

t
&
ModeOutput1=Pulsed
INPUT 1
OUTPUT 1
Ondelay Offdelay
&
³1
³1 t t
INPUT 16

PulseTime

t
&
ModeOutput2=Pulsed

INPUT 17
OUTPUT 2
Ondelay Offdelay
&
³1
³1 t t
INPUT 32

PulseTime
t
&

ModeOutput3=Pulsed

OUTPUT 3
Ondelay Offdelay
&
³1
³1 t t

IEC09000612-3-en.vsd
IEC09000612 V3 EN-US

Figure 543: Trip matrix internal logic


Output signals from TMAGAPC are typically connected to other logic blocks or directly to
output contacts in the IED. When used for direct tripping of the circuit breaker(s) the pulse
time shall be set to at least 0.150 seconds in order to obtain satisfactory minimum duration of
the trip pulse to the circuit breaker trip coils.

17.3.7 Technical data


GUID-3AB1EE95-51BF-4CC4-99BD-F4ECDAACB75A v3

Table 664: Number of TMAGAPC instances


Function Quantity with cycle time
3 ms 8 ms 100 ms
TMAGAPC 6 6 -

17.4 Logic for group alarm ALMCALH GUID-64EA392C-950F-486C-8D96-6E7736B592BF v1

17.4.1 Identification GUID-64EA392C-950F-486C-8D96-6E7736B592BF v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Logic for group alarm ALMCALH - -

17.4.2 Functionality GUID-16E60E27-F7A8-416D-8648-8174AAC49BB5 v4

The group alarm logic function (ALMCALH) is used to route several alarm signals to a common
indication, LED and/or contact, in the IED.

Line distance protection REL670 915


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

17.4.3 Function block GUID-EA192656-71DD-4D44-A1D5-96B1B4937971 v1

ALMCALH
BLOCK ALARM
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16

IEC13000181-1-en.vsd
IEC13000181 V1 EN-US

17.4.4 Signals
PID-6510-INPUTSIGNALS v5

Table 665: ALMCALH Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
INPUT1 BOOLEAN 0 Binary input 1
INPUT2 BOOLEAN 0 Binary input 2
INPUT3 BOOLEAN 0 Binary input 3
INPUT4 BOOLEAN 0 Binary input 4
INPUT5 BOOLEAN 0 Binary input 5
INPUT6 BOOLEAN 0 Binary input 6
INPUT7 BOOLEAN 0 Binary input 7
INPUT8 BOOLEAN 0 Binary input 8
INPUT9 BOOLEAN 0 Binary input 9
INPUT10 BOOLEAN 0 Binary input 10
INPUT11 BOOLEAN 0 Binary input 11
INPUT12 BOOLEAN 0 Binary input 12
INPUT13 BOOLEAN 0 Binary input 13
INPUT14 BOOLEAN 0 Binary input 14
INPUT15 BOOLEAN 0 Binary input 15
INPUT16 BOOLEAN 0 Binary input 16

PID-6510-OUTPUTSIGNALS v5

Table 666: ALMCALH Output signals


Name Type Description
ALARM BOOLEAN OR function betweeen inputs 1 to 16

916 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

17.4.5 Settings
PID-6510-SETTINGS v5

Table 667: ALMCALH Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On

17.4.6 Operation principle GUID-0405BB7B-7EF7-4546-92CD-F703AA0DD9F4 v2

The logic for group alarm ALMCALH block is provided with 16 input signals and one ALARM
output signal. The function block incorporates internal logic OR gate in order to provide
grouping of connected input signals to the output ALARM signal from the function block.

When any one of 16 input signals (INPUT1 to INPUT16) has logical value 1, the ALARM output
signal will get logical value 1.

The function has a drop-off delay of 200 ms when all inputs are reset to provide a steady
signal.

Input 1
200 ms
ALARM
³1 t
Input 16

IEC13000191-1-en.vsd
IEC13000191 V1 EN-US

Figure 544: Group alarm logic

17.4.7 Technical data


GUID-A05AF26F-DC98-4E62-B96B-E75D19F20767 v2

Table 668: Number of ALMCALH instances


Function Quantity with cycle time
3 ms 8 ms 100 ms
ALMCALH - - 5

17.5 Logic for group warning WRNCALH

17.5.1 Identification GUID-3EBD3D5B-F506-4557-88D7-DFC0BD21C690 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Logic for group warning WRNCALH - -

17.5.2 Functionality GUID-F7D9A012-3AD4-4D86-BE97-DF2A99BE5383 v4

The group warning logic function (WRNCALH) is used to route several warning signals to a
common indication, LED and/or contact, in the IED.

Line distance protection REL670 917


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

17.5.3 Function block GUID-C909E4FB-3F7A-47F7-8988-36B159E2C7B2 v1

WRNCALH
BLOCK WARNING
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16

IEC13000182-1-en.vsd
IEC13000182 V1 EN-US

17.5.4 Signals
PID-4127-INPUTSIGNALS v3

Table 669: WRNCALH Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
INPUT1 BOOLEAN 0 Binary input 1
INPUT2 BOOLEAN 0 Binary input 2
INPUT3 BOOLEAN 0 Binary input 3
INPUT4 BOOLEAN 0 Binary input 4
INPUT5 BOOLEAN 0 Binary input 5
INPUT6 BOOLEAN 0 Binary input 6
INPUT7 BOOLEAN 0 Binary input 7
INPUT8 BOOLEAN 0 Binary input 8
INPUT9 BOOLEAN 0 Binary input 9
INPUT10 BOOLEAN 0 Binary input 10
INPUT11 BOOLEAN 0 Binary input 11
INPUT12 BOOLEAN 0 Binary input 12
INPUT13 BOOLEAN 0 Binary input 13
INPUT14 BOOLEAN 0 Binary input 14
INPUT15 BOOLEAN 0 Binary input 15
INPUT16 BOOLEAN 0 Binary input 16

PID-4127-OUTPUTSIGNALS v3

Table 670: WRNCALH Output signals


Name Type Description
WARNING BOOLEAN OR function betweeen inputs 1 to 16

918 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

17.5.5 Settings
PID-4127-SETTINGS v3

Table 671: WRNCALH Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On

17.5.6 Operation principle GUID-71C65C20-7B6C-499F-BFCD-E418AA55F7EC v2

The logic for group warning WRNCALH block is provided with 16 input signals and 1 WARNING
output signal. The function block incorporates internal logic OR gate in order to provide
grouping of connected input signals to the output WARNING signal from the function block.

When any one of 16 input signals (INPUT1 to INPUT16) has logical value 1, the WARNING output
signal will get logical value 1.

The function has a drop-off delay of 200 ms when all inputs are reset to provide a steady
signal.

INPUT1
200 ms
WARNING
³1 t
INPUT16

IEC13000192-1-en.vsd
IEC13000192 V1 EN-US

17.5.7 Technical data


GUID-70B7357D-F467-4CF5-9F73-641A82D334F5 v2

Table 672: Number of WRNCALH instances


Function Quantity with cycle time
3 ms 8 ms 100 ms
WRNCALH - - 5

17.6 Logic for group indication INDCALH

17.6.1 Identification GUID-3B5D4371-420D-4249-B6A4-5A168920D635 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Logic for group indication INDCALH - -

17.6.2 Functionality GUID-D8D1A4EE-A87F-46C6-8529-277FC1ADA9B0 v4

The group indication logic function (INDCALH) is used to route several indication signals to a
common indication, LED and/or contact, in the IED.

Line distance protection REL670 919


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

17.6.3 Function block GUID-9D89E183-449A-4016-AB83-E57C8DDBA843 v1

INDCALH
BLOCK IND
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16

IEC13000183-1-en.vsd
IEC13000183 V1 EN-US

17.6.4 Signals
PID-4128-INPUTSIGNALS v4

Table 673: INDCALH Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
INPUT1 BOOLEAN 0 Binary input 1
INPUT2 BOOLEAN 0 Binary input 2
INPUT3 BOOLEAN 0 Binary input 3
INPUT4 BOOLEAN 0 Binary input 4
INPUT5 BOOLEAN 0 Binary input 5
INPUT6 BOOLEAN 0 Binary input 6
INPUT7 BOOLEAN 0 Binary input 7
INPUT8 BOOLEAN 0 Binary input 8
INPUT9 BOOLEAN 0 Binary input 9
INPUT10 BOOLEAN 0 Binary input 10
INPUT11 BOOLEAN 0 Binary input 11
INPUT12 BOOLEAN 0 Binary input 12
INPUT13 BOOLEAN 0 Binary input 13
INPUT14 BOOLEAN 0 Binary input 14
INPUT15 BOOLEAN 0 Binary input 15
INPUT16 BOOLEAN 0 Binary input 16

PID-4128-OUTPUTSIGNALS v4

Table 674: INDCALH Output signals


Name Type Description
IND BOOLEAN OR function betweeen inputs 1 to 16

920 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

17.6.5 Settings
PID-4128-SETTINGS v4

Table 675: INDCALH Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On

17.6.6 Operation principle GUID-72B1B4E8-BC6C-4AF7-8B41-058241B944F8 v2

The logic for group indication INDCALH block is provided with 16 input signals and 1 IND
output signal. The function block incorporates internal logic OR gate in order to provide
grouping of connected input signals to the output IND signal from the function block.

When any one of 16 input signals (INPUT1 to INPUT16) has logical value 1, the IND output signal
will get logical value 1.

The function has a drop-off delay of 200 ms when all inputs are reset to provide a steady
signal.

INPUT1
200 ms
IND
³1 t
INPUT16

IEC13000193-1-en.vsd
IEC13000193 V1 EN-US

17.6.7 Technical data


GUID-EAA43288-01A5-49CF-BF5B-9ABF6DC27D85 v2

Table 676: Number of INDCALH instances


Function Quantity with cycle time
3 ms 8 ms 100 ms
INDCALH - 5 -

17.7 Basic configurable logic blocks M11396-4 v18

The basic configurable logic blocks do not propagate the time stamp and quality of signals
(have no suffix QT at the end of their function name). A number of logic blocks and timers are
always available as basic for the user to adapt the configuration to the specific application
needs. The list below shows a summary of the function blocks and their features.

These logic blocks are also available as part of an extension logic package.

• AND function block. The AND function is used to form general combinatory expressions
with boolean variables. The AND function block has up to four inputs and two outputs.
One of the outputs is inverted.

• GATE function block is used for whether or not a signal should be able to pass from the
input to the output.

Line distance protection REL670 921


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

• INVERTER function block that inverts the input signal to the output.

• LLD function block. Loop delay used to delay the output signal one execution cycle.

• OR function block. The OR function is used to form general combinatory expressions with
boolean variables. The OR function block has up to six inputs and two outputs. One of the
outputs is inverted.

• PULSETIMER function block can be used, for example, for pulse extensions or limiting of
operation of outputs, settable pulse time.

• RSMEMORY function block is a flip-flop that can reset or set an output from two inputs
respectively. Each block has two outputs where one is inverted. The memory setting
controls if, after a power interruption, the flip-flop resets or returns to the state it had
before the power interruption. RESET input has priority.

• SRMEMORY function block is a flip-flop that can set or reset an output from two inputs
respectively. Each block has two outputs where one is inverted. The memory setting
controls if, after a power interruption, the flip-flop resets or returns to the state it had
before the power interruption. The SET input has priority.

• TIMERSET function has pick-up and drop-out delayed outputs related to the input signal.
The timer has a settable time delay.

• XOR is used to generate combinatory expressions with boolean variables. XOR has two
inputs and two outputs. One of the outputs is inverted. The output signal OUT is 1 if the
input signals are different and 0 if they are the same.

17.7.1 AND function block AND IP11013-1 v2

M11453-3 v4
The AND function is used to form general combinatory expressions with boolean variables. The
AND function block has up to four inputs and two outputs. One of the outputs is inverted.

17.7.1.1 Function block


M11452-3 v2

AND
INPUT1 OUT
INPUT2 NOUT
INPUT3
INPUT4

IEC14000071-1-en.vsd
IEC14000071 V1 EN-US

Figure 545: AND function block

922 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

17.7.1.2 Signals
PID-3437-INPUTSIGNALS v7

Table 677: AND Input signals


Name Type Default Description
INPUT1 BOOLEAN 1 Input signal 1
INPUT2 BOOLEAN 1 Input signal 2
INPUT3 BOOLEAN 1 Input signal 3
INPUT4 BOOLEAN 1 Input signal 4

PID-3437-OUTPUTSIGNALS v7

Table 678: AND Output signals


Name Type Description
OUT BOOLEAN Output signal
NOUT BOOLEAN Inverted output signal

17.7.1.3 Technical data


GUID-D1179280-1D99-4A66-91AC-B7343DBA9F23 v3

Table 679: Number of AND instances


Logic block Quantity with cycle time
3 ms 8 ms 100 ms
AND 60 60 160

17.7.2 Controllable gate function block GATE IP11021-1 v2

M11489-3 v2
The Controllable gate function block (GATE) is used for controlling if a signal should be able to
pass from the input to the output or not depending on a setting.

17.7.2.1 Function block


M11490-3 v2

GATE
INPUT OUT

IEC04000410-2-en.vsd
IEC04000410 V2 EN-US

Figure 546: GATE function block

17.7.2.2 Signals
PID-3801-INPUTSIGNALS v6

Table 680: GATE Input signals


Name Type Default Description
INPUT BOOLEAN 0 Input to gate

Line distance protection REL670 923


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

PID-3801-OUTPUTSIGNALS v5

Table 681: GATE Output signals


Name Type Description
OUT BOOLEAN Output from gate

17.7.2.3 Settings
PID-3801-SETTINGS v6

Table 682: GATE Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On

17.7.2.4 Technical data


GUID-45DF373F-DC39-4E1B-B45B-6B454E8E0E50 v3

Table 683: Number of GATE instances


Logic block Quantity with cycle time
3 ms 8 ms 100 ms
GATE 10 10 20

17.7.3 Inverter function block INV IP11011-1 v2

17.7.3.1 Function block


M11445-3 v1

INV
INPUT OUT

IEC04000404_2_en.vsd
IEC04000404 V2 EN-US

Figure 547: INV function block

17.7.3.2 Signals
PID-3803-INPUTSIGNALS v5

Table 684: INV Input signals


Name Type Default Description
INPUT BOOLEAN 0 Input

PID-3803-OUTPUTSIGNALS v4

Table 685: INV Output signals


Name Type Description
OUT BOOLEAN Output

924 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

17.7.3.3 Technical data


GUID-0EC4192A-EF03-47C0-AEC1-09B68B411A98 v3

Table 686: Number of INV instances


Logic block Quantity with cycle time
3 ms 8 ms 100 ms
INV 90 90 240

17.7.4 Loop delay function block LLD GUID-05D959B5-A55B-437C-8E8F-831A4A357E24 v2

GUID-64B24094-010D-4B8F-8B7B-DDD49499AAE5 v3
The Logic loop delay function block (LLD) function is used to delay the output signal one
execution cycle, that is, the cycle time of the function blocks used.

17.7.4.1 Function block


GUID-EE44CFDF-C8F7-4870-BD1C-98D9CD91FD97 v4

LLD
INPUT OUT

IEC15000144.vsd
IEC15000144 V1 EN-US

Figure 548: LLD function block

17.7.4.2 Signals
PID-3805-INPUTSIGNALS v5

Table 687: LLD Input signals


Name Type Default Description
INPUT BOOLEAN 0 Input signal

PID-3805-OUTPUTSIGNALS v5

Table 688: LLD Output signals


Name Type Description
OUT BOOLEAN Output signal delayed one execution cycle

17.7.4.3 Technical data


GUID-B2E6F510-8766-4381-9618-CE02ED71FFB6 v2

Table 689: Number of LLD instances


Logic block Quantity with cycle time
3 ms 8 ms 100 ms
LLD 10 10 20

17.7.5 OR function block IP11012-1 v3

M11449-3 v2
The OR function is used to form general combinatory expressions with boolean variables. The
OR function block has up to six inputs and two outputs. One of the outputs is inverted.

Line distance protection REL670 925


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

17.7.5.1 Function block


M11448-3 v1

OR
INPUT1 OUT
INPUT2 NOUT
INPUT3
INPUT4
INPUT5
INPUT6

IEC04000405_2_en.vsd
IEC04000405 V2 EN-US

Figure 549: OR function block

17.7.5.2 Signals
PID-3806-INPUTSIGNALS v5

Table 690: OR Input signals


Name Type Default Description
INPUT1 BOOLEAN 0 Input 1 to OR gate
INPUT2 BOOLEAN 0 Input 2 to OR gate
INPUT3 BOOLEAN 0 Input 3 to OR gate
INPUT4 BOOLEAN 0 Input 4 to OR gate
INPUT5 BOOLEAN 0 Input 5 to OR gate
INPUT6 BOOLEAN 0 Input 6 to OR gate

PID-3806-OUTPUTSIGNALS v5

Table 691: OR Output signals


Name Type Description
OUT BOOLEAN Output from OR gate
NOUT BOOLEAN Inverted output from OR gate

17.7.5.3 Technical data


GUID-35A795D7-A6BD-4669-A023-43C497DBFB01 v4

Table 692: Number of OR instances


Logic block Quantity with cycle time
3 ms 8 ms 100 ms
OR 78 60 160

17.7.6 Pulse timer function block PULSETIMER IP11016-1 v2

M11466-3 v3
The pulse (PULSETIMER) function can be used, for example, for pulse extensions or limiting the
operation time of outputs. The PULSETIMER has a settable length. When the input is 1, the
output will be 1 for the time set by the time delay parameter t. Then it returns to 0.

926 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

17.7.6.1 Function block


M11465-3 v4

PULSETIMER
INPUT OUT

IEC04000407-3-en.vsd
IEC04000407 V3 EN-US

Figure 550: PULSETIMER function block

17.7.6.2 Signals
PID-6985-INPUTSIGNALS v1

Table 693: PULSETIMER Input signals


Name Type Default Description
INPUT BOOLEAN 0 Input to pulse timer

PID-6985-OUTPUTSIGNALS v1

Table 694: PULSETIMER Output signals


Name Type Description
OUT BOOLEAN Output from pulse timer

17.7.6.3 Settings
PID-6985-SETTINGS v1

Table 695: PULSETIMER Non group settings (basic)


Name Values (Range) Unit Step Default Description
t 0.000 - s 0.001 0.010 Time delay of function
90000.000

17.7.6.4 Technical data


GUID-E05E5FB1-23E7-4816-84F2-1FBFFDFF2B43 v2

Table 696: Number of PULSETIMER instances


Logic block Quantity with cycle time Range or Value Accuracy
3 ms 8 ms 100 ms
PULSETIMER 10 10 20 (0.000–90000.000) s ±0.5% ±10 ms

17.7.7 Reset-set with memory function block RSMEMORY GUID-9C93669F-078B-49EA-85B8-C4BB6A434734 v1

GUID-4C804DEA-3C83-4C20-82C6-BAD03BD48242 v4
The Reset-set with memory function block (RSMEMORY) is a flip-flop with memory that can
reset or set an output from two inputs respectively. Each RSMEMORY function block has two
outputs, where one is inverted. The memory setting controls if, after a power interruption, the
flip-flop resets or returns to the state it had before the power interruption. For a Reset-Set
flip-flop, RESET input has higher priority over SET input.

Line distance protection REL670 927


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

Table 697: Truth table for RSMEMORY function block


RESET SET OUT NOUT
0 0 Last Inverted last
value value
0 1 1 0
1 0 0 1
1 1 0 1

17.7.7.1 Function block


GUID-50D5A4C0-59BF-44DE-86AC-47640ACD35A7 v3

RSMEMORY
SET OUT
RESET NOUT

IEC09000294-1-en.vsd
IEC09000294 V1 EN-US

Figure 551: RSMEMORY function block

17.7.7.2 Signals
PID-3811-INPUTSIGNALS v5

Table 698: RSMEMORY Input signals


Name Type Default Description
SET BOOLEAN 0 Input signal to set
RESET BOOLEAN 0 Input signal to reset

PID-3811-OUTPUTSIGNALS v5

Table 699: RSMEMORY Output signals


Name Type Description
OUT BOOLEAN Output signal
NOUT BOOLEAN Inverted output signal

17.7.7.3 Settings
PID-3811-SETTINGS v5

Table 700: RSMEMORY Group settings (basic)


Name Values (Range) Unit Step Default Description
Memory Off - - On Operating mode of the memory
On function

17.7.7.4 Technical data


GUID-BE6FD540-E96E-4F15-B2A2-12FFAE6C51DB v2

Table 701: Number of RSMEMORY instances


Logic block Quantity with cycle time
3 ms 8 ms 100 ms
RSMEMORY 10 10 20

928 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

17.7.8 Set-reset with memory function block SRMEMORY IP11020-1 v2

M11485-3 v4
The Set-reset with memory function block (SRMEMORY) is a flip-flop with memory that can set
or reset an output from two inputs respectively. Each SRMEMORY function block has two
outputs, where one is inverted. The memory setting controls if, after a power interruption, the
flip-flop resets or returns to the state it had before the power interruption. The input SET has
priority.

Table 702: Truth table for SRMEMORY function block


SET RESET OUT NOUT
0 0 Last Inverted
value last value
0 1 0 1
1 0 1 0
1 1 1 0

17.7.8.1 Function block


M11484-3 v2

SRMEMORY
SET OUT
RESET NOUT

IEC04000408_2_en.vsd
IEC04000408 V2 EN-US

Figure 552: SRMEMORY function block

17.7.8.2 Signals
PID-3813-INPUTSIGNALS v5

Table 703: SRMEMORY Input signals


Name Type Default Description
SET BOOLEAN 0 Input signal to set
RESET BOOLEAN 0 Input signal to reset

PID-3813-OUTPUTSIGNALS v5

Table 704: SRMEMORY Output signals


Name Type Description
OUT BOOLEAN Output signal
NOUT BOOLEAN Inverted output signal

17.7.8.3 Settings
PID-3813-SETTINGS v5

Table 705: SRMEMORY Group settings (basic)


Name Values (Range) Unit Step Default Description
Memory Off - - On Operating mode of the memory
On function

Line distance protection REL670 929


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

17.7.8.4 Technical data


GUID-7A0F4327-CA83-4FB0-AB28-7C5F17AE6354 v2

Table 706: Number of SRMEMORY instances


Logic block Quantity with cycle time
3 ms 8 ms 100 ms
SRMEMORY 10 10 20

17.7.9 Settable timer function block TIMERSET IP11022-1 v2

M11494-3 v3
The Settable timer function block (TIMERSET) timer has two outputs for the delay of the input
signal at drop-out and at pick-up. The timer has a settable time delay. It also has an Operation
setting On and Off that controls the operation of the timer.

Input
tdelay
On

Off
tdelay

t
IEC08000289-2-en.vsd

IEC08000289 V2 EN-US

Figure 553: TIMERSET status diagram

17.7.9.1 Function block


M11495-3 v3

TIMERSET
INPUT ON
OFF

IEC04000411-2-en.vsd
IEC04000411 V2 EN-US

Figure 554: TIMERSET function block

17.7.9.2 Signals
PID-6976-INPUTSIGNALS v1

Table 707: TIMERSET Input signals


Name Type Default Description
INPUT BOOLEAN 0 Input to timer

930 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

PID-6976-OUTPUTSIGNALS v1

Table 708: TIMERSET Output signals


Name Type Description
ON BOOLEAN Output from timer, pick-up delayed
OFF BOOLEAN Output from timer, drop-out delayed

17.7.9.3 Settings
PID-6976-SETTINGS v1

Table 709: TIMERSET Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
t 0.000 - s 0.001 0.000 Delay for settable timer n
90000.000

17.7.9.4 Technical data


GUID-C6C98FE0-F559-45EE-B853-464516775417 v3

Table 710: Number of TIMERSET instances


Logic block Quantity with cycle time Range or Value Accuracy
3 ms 8 ms 100 ms
TIMERSET 15 15 30 (0.000–90000.000) s ±0.5% ±10 ms

17.7.10 Exclusive OR function block XOR IP11018-1 v2

M11477-3 v4
The exclusive OR function (XOR) is used to generate combinatory expressions with boolean
variables. XOR has two inputs and two outputs. One of the outputs is inverted. The output
signal OUT is 1 if the input signals are different and 0 if they are the same.

Table 711: Truth table for XOR function block


INPUT1 INPUT2 OUT NOUT
0 0 0 1
0 1 1 0
1 0 1 0
1 1 0 1

17.7.10.1 Function block


M11476-3 v1

XOR
INPUT1 OUT
INPUT2 NOUT

IEC04000409-2-en.vsd
IEC04000409 V2 EN-US

Figure 555: XOR function block

Line distance protection REL670 931


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

17.7.10.2 Signals
PID-3817-INPUTSIGNALS v2

Table 712: XOR Input signals


Name Type Default Description
INPUT1 BOOLEAN 0 Input 1 to XOR gate
INPUT2 BOOLEAN 0 Input 2 to XOR gate

PID-3817-OUTPUTSIGNALS v2

Table 713: XOR Output signals


Name Type Description
OUT BOOLEAN Output from XOR gate
NOUT BOOLEAN Inverted output from XOR gate

17.7.10.3 Technical data


GUID-0B07F78C-10BD-4070-AFF0-6EE36454AA03 v2

Table 714: Number of XOR instances


Logic block Quantity with cycle time
3 ms 8 ms 100 ms
XOR 10 10 20

17.8 Configurable logic blocks Q/T GUID-0CA6511A-E8BD-416E-9B59-5C6BD98C60B7 v5

The configurable logic blocks QT propagate the time stamp and the quality of the input
signals (have suffix QT at the end of their function name).

The function blocks assist the user to adapt the IEDs' configuration to the specific application
needs. The list below shows a summary of the function blocks and their features.

• ANDQT AND function block. The function also propagates the time stamp and the quality
of input signals. Each block has four inputs and two outputs where one is inverted.

• INDCOMBSPQT combines single input signals to group signal. Single position input is
copied to value part of SP_OUT output. TIME input is copied to time part of SP_OUT
output. Quality input bits are copied to the corresponding quality part of SP_OUT output.

• INDEXTSPQT extracts individual signals from a group signal input. The value part of single
position input is copied to SI_OUT output. The time part of single position input is copied
to TIME output. The quality bits in the common part and the indication part of inputs
signal are copied to the corresponding quality output.

• INVALIDQT function which sets quality invalid of outputs according to a "valid" input.
Inputs are copied to outputs. If input VALID is 0, or if its quality invalid bit is set, all
outputs invalid quality bit will be set to invalid. The time stamp of an output will be set to
the latest time stamp of INPUT and VALID inputs.

• INVERTERQT function block that inverts the input signal and propagates the time stamp
and the quality of the input signal.

932 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

• ORQT OR function block that also propagates the time stamp and the quality of the input
signals. Each block has six inputs and two outputs where one is inverted.

• PULSETIMERQT Pulse timer function block can be used, for example, for pulse extensions
or limiting of operation of outputs. The function also propagates the time stamp and the
quality of the input signal.

• RSMEMORYQT function block is a flip-flop that can reset or set an output from two inputs
respectively. Each block has two outputs where one is inverted. The memory setting
controls if the block after a power interruption should return to the state before the
interruption, or be reset. The function also propagates the time stamp and the quality of
the input signal.

• SRMEMORYQT function block is a flip-flop that can set or reset an output from two inputs
respectively. Each block has two outputs where one is inverted. The memory setting
controls if the block after a power interruption should return to the state before the
interruption, or be reset. The function also propagates the time stamp and the quality of
the input signal.

• TIMERSETQT function has pick-up and drop-out delayed outputs related to the input
signal. The timer has a settable time delay. The function also propagates the time stamp
and the quality of the input signal.

• XORQT XOR function block. The function also propagates the time stamp and the quality
of the input signals. Each block has two outputs where one is inverted.

17.8.1 ANDQT function block GUID-E3023D85-FDCC-4A5F-99B4-64DA7B4AC5BB v5

The ANDQT function is used to form general combinatory expressions with boolean variables.
The ANDQT function block has four inputs and two outputs.

17.8.1.1 Function block GUID-4CEE3C76-A39D-4C33-AD55-88C570210F2B v2

ANDQT
INPUT1 OUT
INPUT2 NOUT
INPUT3
INPUT4

IEC09000297-1-en.vsd
IEC09000297 V1 EN-US

Figure 556: ANDQT function block

17.8.1.2 Signals GUID-4543C4C9-FAE2-4328-8DE2-4A5756A020E9 v1

PID-3800-INPUTSIGNALS v6

Table 715: ANDQT Input signals


Name Type Default Description
INPUT1 BOOLEAN 1 Input signal 1
INPUT2 BOOLEAN 1 Input signal 2
INPUT3 BOOLEAN 1 Input signal 3
INPUT4 BOOLEAN 1 Input signal 4

Line distance protection REL670 933


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

PID-3800-OUTPUTSIGNALS v6

Table 716: ANDQT Output signals


Name Type Description
OUT BOOLEAN Output signal
NOUT BOOLEAN Inverted output signal

17.8.1.3 Technical data


GUID-23D4121A-4C9A-4072-BBE3-6DB076EDAB79 v1

Table 717: Number of ANDQT instances


Logic block Quantity with cycle time
3 ms 8 ms 100 ms
ANDQT - 20 100

17.8.2 Single point indication related signals combining function


block INDCOMBSPQT GUID-13C9325D-D3A0-480F-9F3B-738A13E0ECF8 v3

GUID-EEBD65A5-394C-4ECD-BF6F-D556B610FC57 v3
The value of single point input (SP_IN) is copied to the value part of the SP_OUT output. The
TIME input is copied to the time part of the SP_OUT output. State input bits are copied to the
corresponding state part of the SP_OUT output. If the state or value on the SP_OUT output
changes, the Event bit in the state part is toggled.

INDCOMBSPQT can propagate the quality, the value and the time stamps of the signals via IEC
61850.

17.8.2.1 Function block GUID-55B49FC7-8239-4891-BE16-29296A8F40BE v1

INDCOMBSPQT
SP_IN* SP_OUT
TIME*
BLOCKED*
SUBST*
INVALID*
TEST*

IEC15000146.vsd
IEC15000146 V1 EN-US

Figure 557: INDCOMBSPQT function block

17.8.2.2 Signals GUID-4543C4C9-FAE2-4328-8DE2-4A5756A020E9 v1

PID-3792-INPUTSIGNALS v2

Table 718: INDCOMBSPQT Input signals


Name Type Default Description
SP_IN BOOLEAN 0 Single point indication
TIME GROUP 0 Timestamp
SIGNAL
BLOCKED BOOLEAN 0 Blocked for update
SUBST BOOLEAN 0 Substitued
INVALID BOOLEAN 0 Invalid value
TEST BOOLEAN 0 Testmode

934 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

PID-3792-OUTPUTSIGNALS v2

Table 719: INDCOMBSPQT Output signals


Name Type Description
SP_OUT BOOLEAN Single point indication

17.8.2.3 Technical data


GUID-27DF23C0-A0B2-4BB0-80B5-FC7B7F7FE448 v1

Table 720: Number of INDCOMBSPQT instances


Logic block Quantity with cycle time
3 ms 8 ms 100 ms
INDCOMBSPQT - 10 10

17.8.3 Single point input signal attributes converting function block


INDEXTSPQT GUID-9C3D6C45-6B3A-466C-86A1-3DBCD4809B33 v1

GUID-9B700C69-4DAE-434A-BCE6-CE2D1139680A v3
The value part of the single point input signal SI_IN is copied to SI_OUT output. The time part
of single point input is copied to the TIME output. The state bits in the common part and the
indication part of the input signal are copied to the corresponding state output.

INDEXTSPQT can propagate the quality, the value and the time stamps of the signals via IEC
61850.

17.8.3.1 Function block GUID-04AA5209-B919-4161-A585-336CE9618A89 v2

INDEXTSPQT
SI_IN* SI_OUT
TIME
BLOCKED
SUBST
INVALID
TEST

IEC14000067-1-en.vsd
IEC14000067 V1 EN-US

Figure 558: INDEXTSPQT function block

17.8.3.2 Signals GUID-4543C4C9-FAE2-4328-8DE2-4A5756A020E9 v1

PID-3821-INPUTSIGNALS v2

Table 721: INDEXTSPQT Input signals


Name Type Default Description
SI_IN BOOLEAN 0 Single indication

Line distance protection REL670 935


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

PID-3821-OUTPUTSIGNALS v2

Table 722: INDEXTSPQT Output signals


Name Type Description
SI_OUT BOOLEAN Single indication
TIME GROUP SIGNAL Timestamp of input
BLOCKED BOOLEAN Blocked for update
SUBST BOOLEAN Substituted
INVALID BOOLEAN Invalid value
TEST BOOLEAN Testmode

17.8.3.3 Technical data


GUID-C1E61AE5-22CF-4198-97CF-8C8043EE96D2 v1

Table 723: Number of INDEXTSPQT instances


Logic block Quantity with cycle time
3 ms 8 ms 100 ms
INDEXTSPQT - 10 10

17.8.4 Invalid logic function block INVALIDQT GUID-66C6DCEE-1F0E-4EB8-9ADB-97F8B41E53DF v4

Component which sets quality invalid of outputs according to a "valid" input.

The values of the input signals INPUTx (where 1<x<16) are copied to the outputs OUTPUTx
(where 1<x<16). If the input VALID is 0 or if its quality bit is set invalid, all outputs OUTPUTx
(where 1<x<16) quality bit will be set to invalid. The time stamp of any output OUTPUTx (where
1<x<16) will be set to the latest time stamp of any input and the input VALID.

INVALIDQT can propagate the quality, the value and the time stamps of the signals via IEC
61850.

17.8.4.1 Function block GUID-0BD84306-0965-4702-8D5C-9570A70168EA v1

INVALIDQT
INPUT1 OUTPUT1
INPUT2 OUTPUT2
INPUT3 OUTPUT3
INPUT4 OUTPUT4
INPUT5 OUTPUT5
INPUT6 OUTPUT6
INPUT7 OUTPUT7
INPUT8 OUTPUT8
INPUT9 OUTPUT9
INPUT10 OUTPUT10
INPUT11 OUTPUT11
INPUT12 OUTPUT12
INPUT13 OUTPUT13
INPUT14 OUTPUT14
INPUT15 OUTPUT15
INPUT16 OUTPUT16
VALID

iec08000169.vsd
IEC08000169 V1 EN-US

Figure 559: INVALIDQT function block

936 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

17.8.4.2 Signals GUID-4543C4C9-FAE2-4328-8DE2-4A5756A020E9 v1

PID-3822-INPUTSIGNALS v5

Table 724: INVALIDQT Input signals


Name Type Default Description
INPUT1 BOOLEAN 0 Indication input 1
INPUT2 BOOLEAN 0 Indication input 2
INPUT3 BOOLEAN 0 Indication input 3
INPUT4 BOOLEAN 0 Indication input 4
INPUT5 BOOLEAN 0 Indication input 5
INPUT6 BOOLEAN 0 Indication input 6
INPUT7 BOOLEAN 0 Indication input 7
INPUT8 BOOLEAN 0 Indication input 8
INPUT9 BOOLEAN 0 Indication input 9
INPUT10 BOOLEAN 0 Indication input 10
INPUT11 BOOLEAN 0 Indication input 11
INPUT12 BOOLEAN 0 Indication input 12
INPUT13 BOOLEAN 0 Indication input 13
INPUT14 BOOLEAN 0 Indication input 14
INPUT15 BOOLEAN 0 Indication input 15
INPUT16 BOOLEAN 0 Indication input 16
VALID BOOLEAN 1 Inputs are valid or not

PID-3822-OUTPUTSIGNALS v5

Table 725: INVALIDQT Output signals


Name Type Description
OUTPUT1 BOOLEAN Indication output 1
OUTPUT2 BOOLEAN Indication output 2
OUTPUT3 BOOLEAN Indication output 3
OUTPUT4 BOOLEAN Indication output 4
OUTPUT5 BOOLEAN Indication output 5
OUTPUT6 BOOLEAN Indication output 6
OUTPUT7 BOOLEAN Indication output 7
OUTPUT8 BOOLEAN Indication output 8
OUTPUT9 BOOLEAN Indication output 9
OUTPUT10 BOOLEAN Indication output 10
OUTPUT11 BOOLEAN Indication output 11
OUTPUT12 BOOLEAN Indication output 12
OUTPUT13 BOOLEAN Indication output 13
OUTPUT14 BOOLEAN Indication output 14
OUTPUT15 BOOLEAN Indication output 15
OUTPUT16 BOOLEAN Indication output 16

Line distance protection REL670 937


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

17.8.4.3 Technical data


GUID-77FEBE9B-0882-4E85-8B1A-7671807BFC02 v2

Table 726: Number of INVALIDQT instances


Logic block Quantity with cycle time
3 ms 8 ms 100 ms
INVALIDQT 10 6 6

17.8.5 Inverter function block INVERTERQT GUID-502064E0-FE2F-43C0-AA40-79D058FC3E1C v4

The INVERTERQT function block inverts one binary input signal to the output. It can propagate
the quality, value and the time stamps of the signals via IEC 61850.

17.8.5.1 Function block GUID-06C5C594-E00B-4FD5-8B0F-4ED05DB348B6 v2

INVERTERQT
INPUT OUT

IEC09000299-1-en.vsd
IEC09000299 V1 EN-US

Figure 560: INVERTERQT function block

17.8.5.2 Signals GUID-4543C4C9-FAE2-4328-8DE2-4A5756A020E9 v1

PID-3804-INPUTSIGNALS v5

Table 727: INVERTERQT Input signals


Name Type Default Description
INPUT BOOLEAN 0 Input signal

PID-3804-OUTPUTSIGNALS v5

Table 728: INVERTERQT Output signals


Name Type Description
OUT BOOLEAN Output signal

17.8.5.3 Technical data


GUID-F25B94C6-9CC9-48A0-A7A3-47627D2B56E2 v1

Table 729: Number of INVERTERQT instances


Logic block Quantity with cycle time
3 ms 8 ms 100 ms
INVERTERQT - 20 100

17.8.6 ORQT function block GUID-F8F8D591-F895-4BCB-ADBD-5F95E7B70FEB v2

GUID-F8AECD9C-83FC-4025-9AB5-809D88122277 v4
The ORQT function block (ORQT) is used to form general combinatory expressions OR with
boolean variables. ORQT function block has up to six inputs and two outputs. One of the

938 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

outputs is inverted. It can propagate the quality, value and the timestamps of the signals via
IEC 61850.

17.8.6.1 Function block GUID-BCDFD5F0-4F30-4012-BA49-2E5C2115912E v2

ORQT
INPUT1 OUT
INPUT2 NOUT
INPUT3
INPUT4
INPUT5
INPUT6

IEC09000298-1-en.vsd
IEC09000298 V1 EN-US

Figure 561: ORQT function block

17.8.6.2 Signals GUID-4543C4C9-FAE2-4328-8DE2-4A5756A020E9 v1

PID-3807-INPUTSIGNALS v5

Table 730: ORQT Input signals


Name Type Default Description
INPUT1 BOOLEAN 0 Input signal 1
INPUT2 BOOLEAN 0 Input signal 2
INPUT3 BOOLEAN 0 Input signal 3
INPUT4 BOOLEAN 0 Input signal 4
INPUT5 BOOLEAN 0 Input signal 5
INPUT6 BOOLEAN 0 Input signal 6

PID-3807-OUTPUTSIGNALS v5

Table 731: ORQT Output signals


Name Type Description
OUT BOOLEAN Output signal
NOUT BOOLEAN Inverted output signal

17.8.6.3 Technical data


GUID-88B27B3C-26D2-47AF-9878-CC19018171B1 v1

Table 732: Number of ORQT instances


Logic block Quantity with cycle time
3 ms 8 ms 100 ms
ORQT - 20 100

17.8.7 Pulse timer function block PULSETIMERQT GUID-5CB71BD1-58A0-4A06-9207-6DAE389B5288 v2

GUID-D930E5A7-C564-4464-B97F-C72B4801C917 v4
The pulse timer function block (PULSETIMERQT) can be used, for example, for pulse extensions
or for limiting the operation time of the outputs. PULSETIMERQT has a settable output pulse
length.

Line distance protection REL670 939


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

When the input goes to 1, the output will be 1 for the time set by the time delay parameter t.
Then it returns to 0.

When the output changes value, the time stamp of the output signal is updated.

The supported “quality” state bits are propagated from the input to the output at each
execution cycle. A change of these bits will not lead to an updated time stamp on the output.

PULSETIMERQT can propagate the quality, value and the time stamps of the signals via IEC
61850.

17.8.7.1 Function block GUID-C0490ECF-5C4E-4F17-B628-482694C590D2 v1

PULSETIMERQT
INPUT OUT

IEC15000145.vsd
IEC15000145 V1 EN-US

Figure 562: PULSETIMERQT function block

17.8.7.2 Signals GUID-4543C4C9-FAE2-4328-8DE2-4A5756A020E9 v1

PID-3810-INPUTSIGNALS v5

Table 733: PULSETIMERQT Input signals


Name Type Default Description
INPUT BOOLEAN 0 Input signal

PID-3810-OUTPUTSIGNALS v5

Table 734: PULSETIMERQT Output signals


Name Type Description
OUT BOOLEAN Output signal

17.8.7.3 Settings
PID-3810-SETTINGS v5

Table 735: PULSETIMERQT Non group settings (basic)


Name Values (Range) Unit Step Default Description
t 0.000 - s 0.001 0.010 Pulse time length
90000.000

17.8.7.4 Technical data


GUID-61263951-53A8-4113-82B5-3DB3BF0D9449 v1

Table 736: Number of PULSETIMERQT instances


Logic block Quantity with cycle time Range or Value Accuracy
3 ms 8 ms 100 ms
PULSETIMERQT - 10 30 (0.000–90000.000) s ±0.5% ±10 ms

940 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

17.8.8 Reset/Set function block RSMEMORYQT GUID-095B2670-610E-47AE-A5D3-F3E7C0A56B65 v2

GUID-32A1B759-2ED8-45B3-8385-762167626CE2 v5
The Reset-set function (RSMEMORYQT) is a flip-flop with memory that can reset or set an
output from two inputs respectively. Each RSMEMORYQT function block has two outputs,
where one is inverted. The memory setting controls if, after a power interruption, the flip-flop
resets or returns to the state it had before the power interruption. For a Reset-Set flip-flop,
the RESET input has higher priority than the SET input.

RSMEMORYQT can propagate the quality, the value and the time stamps of the signals via IEC
61850.

Table 737: Truth table for RSMEMORYQT function block


RESET SET OUT NOUT
0 0 Last Inverted last
value value
0 1 1 0
1 0 0 1
1 1 0 1

17.8.8.1 Function block GUID-BDBFD8BA-9253-4277-96D8-0FF7EE93B56E v1

RSMEMORYQT
SET OUT
RESET NOUT

IEC14000069-1-en.vsd
IEC14000069 V1 EN-US

Figure 563: RSMEMORYQT function block

17.8.8.2 Signals GUID-4543C4C9-FAE2-4328-8DE2-4A5756A020E9 v1

PID-3812-INPUTSIGNALS v5

Table 738: RSMEMORYQT Input signals


Name Type Default Description
SET BOOLEAN 0 Input signal to set
RESET BOOLEAN 0 Input signal to reset

PID-3812-OUTPUTSIGNALS v5

Table 739: RSMEMORYQT Output signals


Name Type Description
OUT BOOLEAN Output signal
NOUT BOOLEAN Inverted output signal

Line distance protection REL670 941


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

17.8.8.3 Settings
PID-3812-SETTINGS v5

Table 740: RSMEMORYQT Group settings (basic)


Name Values (Range) Unit Step Default Description
Memory Off - - On Operating mode of the memory
On function

17.8.8.4 Technical data


GUID-94C803B4-6C5A-4072-AB5C-20DDE98C9A70 v1

Table 741: Number of RSMEMORYQT instances


Logic block Quantity with cycle time
3 ms 8 ms 100 ms
RSMEMORYQT - 10 30

17.8.9 Set/Reset function block SRMEMORYQT GUID-D910BA2D-07FA-44C5-A820-E0413AD7FD91 v2

GUID-39060D4B-9AA7-4505-9487-88B2CBC534F0 v5
The Set-reset function (SRMEMORYQT) is a flip-flop with memory that can set or reset an
output from two inputs respectively. Each SRMEMORYQT function block has two outputs,
where one is inverted. The memory setting controls if, after a power interruption, the flip-flop
resets or returns to the state it had before the power interruption. The SET input has priority.

SRMEMORYQT can propagate the quality, the value and the time stamps of the signals via IEC
61850.

Table 742: Truth table for SRMEMORYQT function block


SET RESET OUT NOUT
0 0 Last Inverted
value last value
0 1 0 1
1 0 1 0
1 1 1 0

If Memory parameter is On, the output result is stored in semi-retained memory.

17.8.9.1 Function block GUID-8B04BA86-9685-4E73-9C04-3AE74752CDBF v1

SRMEMORYQT
SET OUT
RESET NOUT

IEC14000070-1-en.vsd
IEC14000070 V1 EN-US

Figure 564: SRMEMORYQT function block

17.8.9.2 Signals GUID-4543C4C9-FAE2-4328-8DE2-4A5756A020E9 v1

942 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

PID-3814-INPUTSIGNALS v5

Table 743: SRMEMORYQT Input signals


Name Type Default Description
SET BOOLEAN 0 Input signal to set
RESET BOOLEAN 0 Input signal to reset

PID-3814-OUTPUTSIGNALS v5

Table 744: SRMEMORYQT Output signals


Name Type Description
OUT BOOLEAN Output signal
NOUT BOOLEAN Inverted output signal

17.8.9.3 Settings
PID-3814-SETTINGS v5

Table 745: SRMEMORYQT Group settings (basic)


Name Values (Range) Unit Step Default Description
Memory Off - - On Operating mode of the memory
On function

17.8.9.4 Technical data


GUID-341562FB-6149-495B-8A63-200DF16A5590 v1

Table 746: Number of SRMEMORYQT instances


Logic block Quantity with cycle time
3 ms 8 ms 100 ms
SRMEMORYQT - 10 30

17.8.10 Settable timer function block TIMERSETQT GUID-582D9F19-9974-40D6-95EB-7BAD72910748 v2

GUID-3830BCA7-4876-481E-B5AC-2104675232E7 v5
The Settable timer function block (TIMERSETQT) has two outputs for delay of the input signal
at pick-up and drop-out. The timer has a settable time delay (t). It also has an Operation
setting On/Off that controls the operation of the timer.

When the output changes value, the timestamp of the output signal is updated. The supported
“quality” state bits are propagated from the input to the output at each execution cycle. A
change of these bits will not lead to an updated timestamp on the output.

TIMERSETQT can propagate the quality, value and the timestamps of the signals via IEC 61850.

17.8.10.1 Function block GUID-13589BAE-38AE-46A1-8E9F-94BCD1CBCBF1 v1

TIMERSETQT
INPUT ON
OFF

IEC14000068-1-en.vsd
IEC14000068 V1 EN-US

Figure 565: TIMERSETQT function

Line distance protection REL670 943


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

17.8.10.2 Signals GUID-4543C4C9-FAE2-4328-8DE2-4A5756A020E9 v1

PID-3816-INPUTSIGNALS v5

Table 747: TIMERSETQT Input signals


Name Type Default Description
INPUT BOOLEAN 0 Input signal

PID-3816-OUTPUTSIGNALS v5

Table 748: TIMERSETQT Output signals


Name Type Description
ON BOOLEAN Output signal, pick-up delayed
OFF BOOLEAN Output signal, drop-out delayed

17.8.10.3 Settings
PID-3816-SETTINGS v5

Table 749: TIMERSETQT Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
t 0.000 - s 0.001 0.000 Delay for settable timer n
90000.000

17.8.10.4 Technical data


GUID-B6231B97-05ED-40E8-B735-1E1A50FDB85F v1

Table 750: Number of TIMERSETQT instances


Logic block Quantity with cycle time Range or Value Accuracy
3 ms 8 ms 100 ms
TIMERSETQT - 10 30 (0.000–90000.000) s ±0.5% ±10 ms

17.8.11 Exclusive OR function block XORQT GUID-76ADACC1-A273-4100-BE62-99BCDABFEB7A v2

GUID-62986D87-1690-499E-B8D3-1F51D2DA191E v4
The exclusive OR function (XORQT) function is used to generate combinatory expressions with
boolean variables. XORQT function has two inputs and two outputs. One of the outputs is
inverted. The output signal OUT is 1 if the input signals are different and 0 if they are equal.

Table 751: Truth table for XORQT function block


INPUT1 INPUT2 OUT NOUT
0 0 0 1
0 1 1 0
1 0 1 0
1 1 0 1

944 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

XORQT can propagate the quality, value and time stamps of the signals via IEC 61850.

17.8.11.1 Function block GUID-A685524C-DF12-4BA8-A29C-A027CEAC75E5 v2

XORQT
INPUT1 OUT
INPUT2 NOUT

IEC09000300-1-en.vsd
IEC09000300 V1 EN-US

Figure 566: XORQT function block

17.8.11.2 Signals GUID-4543C4C9-FAE2-4328-8DE2-4A5756A020E9 v1

PID-3818-INPUTSIGNALS v5

Table 752: XORQT Input signals


Name Type Default Description
INPUT1 BOOLEAN 0 Input signal 1
INPUT2 BOOLEAN 0 Input signal 2

PID-3818-OUTPUTSIGNALS v5

Table 753: XORQT Output signals


Name Type Description
OUT BOOLEAN Output signal
NOUT BOOLEAN Inverted output signal

17.8.11.3 Technical data


GUID-1C381E02-6B9E-44DC-828F-8B3EA7EDAA54 v1

Table 754: Number of XORQT instances


Logic block Quantity with cycle time
3 ms 8 ms 100 ms
XORQT - 10 30

17.9 Extension logic package IP11362-1 v2

When extra configurable logic blocks are required, an additional package can be ordered.
GUID-19810098-1820-4765-8F0B-7D585FFC0C78 v8

Table 755: Number of instances in the extension logic package


Logic block Quantity with cycle time
3 ms 8 ms 100 ms
SLGAPC 10 10 54
VSGAPC 10 10 100
AND 80 40 100
OR 80 40 100
PULSETIMER 20 20 49
Table continues on next page

Line distance protection REL670 945


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

Logic block Quantity with cycle time


3 ms 8 ms 100 ms
GATE — — 49
TIMERSET 34 30 49
XOR 10 10 69
LLD — — 49
SRMEMORY 10 10 110
INV 80 40 100
RSMEMORY 10 10 20

17.10 Fixed signals FXDSIGN

17.10.1 Identification
SEMOD167904-2 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Fixed signals FXDSIGN - -

17.10.2 Functionality M15322-3 v15

The Fixed signals function (FXDSIGN) has nine pre-set (fixed) signals that can be used in the
configuration of an IED, either for forcing the unused inputs in other function blocks to a
certain level/value, or for creating certain logic. Boolean, integer, floating point, string types of
signals are available.

One FXDSIGN function block is included in all IEDs.

17.10.3 Function block SEMOD54909-4 v4

FXDSIGN
OFF
ON
INTZERO
INTONE
INTALONE
REALZERO
STRNULL
ZEROSMPL
GRP_OFF

IEC05000445-3-en.vsd
IEC05000445 V3 EN-US

Figure 567: FXDSIGN function block

946 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

17.10.4 Signals
PID-6191-OUTPUTSIGNALS v6

Table 756: FXDSIGN Output signals


Name Type Description
OFF BOOLEAN Boolean signal fixed off
ON BOOLEAN Boolean signal fixed on
INTZERO INTEGER Integer signal fixed zero
INTONE INTEGER Integer signal fixed one
INTALONE INTEGER Integer signal fixed all ones
REALZERO REAL Real signal fixed zero
STRNULL STRING String signal with no characters
ZEROSMPL GROUP SIGNAL Channel id for zero sample
GRP_OFF GROUP SIGNAL Group signal fixed off

17.10.5 Settings
PID-1325-SETTINGS v12
The function does not have any settings available in Local HMI or Protection and Control IED
Manager (PCM600).

17.10.6 Operation principle SEMOD54827-5 v6

There are nine outputs from FXDSIGN function block:

• OFF is a boolean signal, fixed to OFF (boolean 0) value


• ON is a boolean signal, fixed to ON (boolean 1) value
• INTZERO is an integer number, fixed to integer value 0
• INTONE is an integer number, fixed to integer value 1
• INTALONE is an integer value FFFF (hex)
• REALZERO is a floating point real number, fixed to 0.0 value
• STRNULL is a string, fixed to an empty string (null) value
• ZEROSMPL is a channel index, fixed to 0 value
• GRP_OFF is a group signal, fixed to 0 value

17.11 Boolean 16 to Integer conversion B16I SEMOD175715-1 v1

17.11.1 Identification
SEMOD175721-2 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Boolean 16 to integer conversion B16I - -

17.11.2 Functionality SEMOD175725-4 v5

Boolean to integer conversion, 16 bit (B16I) is used to transform a set of 16 boolean (logical)
signals into an integer.

Line distance protection REL670 947


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

17.11.3 Function block SEMOD175798-5 v4

B16I
BLOCK OUT
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
IN9
IN10
IN11
IN12
IN13
IN14
IN15
IN16

IEC07000128-2-en.vsd
IEC07000128 V2 EN-US

Figure 568: B16I function block

17.11.4 Signals
PID-3606-INPUTSIGNALS v4

Table 757: B16I Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
IN1 BOOLEAN 0 Input 1
IN2 BOOLEAN 0 Input 2
IN3 BOOLEAN 0 Input 3
IN4 BOOLEAN 0 Input 4
IN5 BOOLEAN 0 Input 5
IN6 BOOLEAN 0 Input 6
IN7 BOOLEAN 0 Input 7
IN8 BOOLEAN 0 Input 8
IN9 BOOLEAN 0 Input 9
IN10 BOOLEAN 0 Input 10
IN11 BOOLEAN 0 Input 11
IN12 BOOLEAN 0 Input 12
IN13 BOOLEAN 0 Input 13
IN14 BOOLEAN 0 Input 14
IN15 BOOLEAN 0 Input 15
IN16 BOOLEAN 0 Input 16

PID-3606-OUTPUTSIGNALS v3

Table 758: B16I Output signals


Name Type Description
OUT INTEGER Output value

948 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

17.11.5 Monitored data


PID-3606-MONITOREDDATA v4

Table 759: B16I Monitored data


Name Type Values (Range) Unit Description
OUT INTEGER - - Output value

17.11.6 Settings ABBD8E283673 v4

The function does not have any parameters available in the local HMI or PCM600.

17.11.7 Operation principle SEMOD175737-4 v5

The Boolean 16 to integer conversion function (B16I) will transfer a combination of up to 16


binary inputs INx, where 1≤x≤16, to an integer. Each INx represents a value according to the
table below from 0 to 32768. This follows the general formula: INx = 2x-1 where 1≤x≤16. The sum
of all the values on the activated INx will be available on the output OUT as a sum of the integer
values of all the inputs INx that are activated. OUT is an integer. When all INx (where 1≤x≤16)
are activated, that is = Boolean 1, it corresponds to that integer 65535 is available on the
output OUT. The B16I function is designed for receiving up to 16 booleans input locally. If the
BLOCK input is activated, it will freeze the output at the last value.

Values of each of the different OUTx from function block B16I for 1≤x≤16.

The sum of the value on each INx corresponds to the integer presented on the output OUT on
the function block B16I

Name of input Type Default Description Value when Value when


activated deactivated
IN1 BOOLEAN 0 Input 1 1 0
IN2 BOOLEAN 0 Input 2 2 0
IN3 BOOLEAN 0 Input 3 4 0
IN4 BOOLEAN 0 Input 4 8 0
IN5 BOOLEAN 0 Input 5 16 0
IN6 BOOLEAN 0 Input 6 32 0
IN7 BOOLEAN 0 Input 7 64 0
IN8 BOOLEAN 0 Input 8 128 0
IN9 BOOLEAN 0 Input 9 256 0
IN10 BOOLEAN 0 Input 10 512 0
IN11 BOOLEAN 0 Input 11 1024 0
IN12 BOOLEAN 0 Input 12 2048 0
IN13 BOOLEAN 0 Input 13 4096 0
IN14 BOOLEAN 0 Input 14 8192 0
IN15 BOOLEAN 0 Input 15 16384 0
IN16 BOOLEAN 0 Input 16 32768 0

The sum of the numbers in column “Value when activated” when all INx (where 1≤x≤16) are
active that is=1; is 65535. 65535 is the highest boolean value that can be converted to an
integer by the B16I function block.

Line distance protection REL670 949


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

17.11.8 Technical data


GUID-65A2876A-F779-41C4-ACD7-7662D1E7F1F2 v3

Table 760: Number of B16I instances


Function Quantity with cycle time
3 ms 8 ms 100 ms
B16I 6 4 8

17.12 Boolean to integer conversion with logical node


representation, 16 bit BTIGAPC SEMOD175753-1 v4

17.12.1 Identification
SEMOD175757-2 v5

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Boolean to integer conversion with BTIGAPC - -
logical node representation, 16 bit

17.12.2 Functionality SEMOD175781-4 v8

Boolean to integer conversion with logical node representation, 16 bit (BTIGAPC) is used to
transform a set of 16 boolean (logical) signals into an integer. The block input will freeze the
output at the last value.

17.12.3 Function block SEMOD175801-5 v4

BTIGAPC
BLOCK OUT
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
IN9
IN10
IN11
IN12
IN13
IN14
IN15
IN16

IEC13000303-1-en.vsd
IEC13000303 V1 EN-US

Figure 569: BTIGAPC function block

950 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

17.12.4 Signals
PID-6944-INPUTSIGNALS v2

Table 761: BTIGAPC Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
IN1 BOOLEAN 0 Input 1
IN2 BOOLEAN 0 Input 2
IN3 BOOLEAN 0 Input 3
IN4 BOOLEAN 0 Input 4
IN5 BOOLEAN 0 Input 5
IN6 BOOLEAN 0 Input 6
IN7 BOOLEAN 0 Input 7
IN8 BOOLEAN 0 Input 8
IN9 BOOLEAN 0 Input 9
IN10 BOOLEAN 0 Input 10
IN11 BOOLEAN 0 Input 11
IN12 BOOLEAN 0 Input 12
IN13 BOOLEAN 0 Input 13
IN14 BOOLEAN 0 Input 14
IN15 BOOLEAN 0 Input 15
IN16 BOOLEAN 0 Input 16

PID-6944-OUTPUTSIGNALS v2

Table 762: BTIGAPC Output signals


Name Type Description
OUT INTEGER Output value

17.12.5 Settings ABBD8E283673 v4

The function does not have any parameters available in the local HMI or PCM600.

17.12.6 Monitored data


PID-6944-MONITOREDDATA v2

Table 763: BTIGAPC Monitored data


Name Type Values (Range) Unit Description
OUT INTEGER - - Output value

17.12.7 Operation principle SEMOD158425-4 v6

The Boolean 16 to integer conversion with logic node representation function (BTIGAPC) will
transfer a combination of up to 16 binary inputs INx, where 1≤x≤16, to an integer. Each INx
represents a value according to the table below from 0 to 32768. This follows the general
formula: INx = 2x-1 where 1≤x≤16. The sum of all the values on the activated INx will be available

Line distance protection REL670 951


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

on the output OUT as a sum of the integer values of all the inputs INx that are activated. OUT
is an integer. When all INx (where 1≤x≤16) are activated, that is = Boolean 1, it corresponds to
that integer 65535 is available on the output OUT. If the BLOCK input is activated, it will freeze
the logical outputs at the last value.

Values of each of the different OUTx from function block BTIGAPC for 1≤x≤16.

The sum of the value on each INx corresponds to the integer presented on the output OUT on
the function block BTIGAPC.

Name of input Type Default Description Value when Value when


activated deactivated
IN1 BOOLEAN 0 Input 1 1 0
IN2 BOOLEAN 0 Input 2 2 0
IN3 BOOLEAN 0 Input 3 4 0
IN4 BOOLEAN 0 Input 4 8 0
IN5 BOOLEAN 0 Input 5 16 0
IN6 BOOLEAN 0 Input 6 32 0
IN7 BOOLEAN 0 Input 7 64 0
IN8 BOOLEAN 0 Input 8 128 0
IN9 BOOLEAN 0 Input 9 256 0
IN10 BOOLEAN 0 Input 10 512 0
IN11 BOOLEAN 0 Input 11 1024 0
IN12 BOOLEAN 0 Input 12 2048 0
IN13 BOOLEAN 0 Input 13 4096 0
IN14 BOOLEAN 0 Input 14 8192 0
IN15 BOOLEAN 0 Input 15 16384 0
IN16 BOOLEAN 0 Input 16 32768 0

The sum of the numbers in column “Value when activated” when all INx (where 1≤x≤16) are
active that is=1; is 65535. 65535 is the highest boolean value that can be converted to an
integer by the BTIGAPC function block.

17.12.8 Technical data


GUID-3820F464-D296-4CAD-8491-F3F997359D79 v2

Table 764: Number of BTIGAPC instances


Function Quantity with cycle time
3 ms 8 ms 100 ms
BTIGAPC 4 4 8

17.13 Integer to boolean 16 conversion IB16

17.13.1 Identification
SEMOD167941-2 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Integer to boolean 16 conversion IB16 - -

952 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

17.13.2 Functionality SEMOD158373-5 v6

Integer to boolean 16 conversion function (IB16) is used to transform an integer into a set of 16
boolean (logical) signals.

17.13.3 Function block SEMOD158389-4 v4

IB16
BLOCK OUT1
INP OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
OUT9
OUT10
OUT11
OUT12
OUT13
OUT14
OUT15
OUT16

IEC06000501-3-en.vsdx

IEC06000501 V3 EN-US

Figure 570: IB16 function block

17.13.4 Signals
PID-6938-INPUTSIGNALS v1

Table 765: IB16 Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
INP INTEGER 0 Integer Input

PID-6938-OUTPUTSIGNALS v1

Table 766: IB16 Output signals


Name Type Description
OUT1 BOOLEAN Output 1
OUT2 BOOLEAN Output 2
OUT3 BOOLEAN Output 3
OUT4 BOOLEAN Output 4
OUT5 BOOLEAN Output 5
OUT6 BOOLEAN Output 6
OUT7 BOOLEAN Output 7
OUT8 BOOLEAN Output 8
OUT9 BOOLEAN Output 9
OUT10 BOOLEAN Output 10
OUT11 BOOLEAN Output 11
OUT12 BOOLEAN Output 12
Table continues on next page

Line distance protection REL670 953


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

Name Type Description


OUT13 BOOLEAN Output 13
OUT14 BOOLEAN Output 14
OUT15 BOOLEAN Output 15
OUT16 BOOLEAN Output 16

17.13.5 Setting parameters ABBD8E242451 v4

The function does not have any parameters available in local HMI or Protection and Control IED
Manager (PCM600)

17.13.6 Operation principle SEMOD158385-4 v4

With integer 15 on the input INP the OUT1 = OUT2 = OUT3= OUT4 =1 and the remaining OUTx =
0 for (5≤x≤16).

OUTx represents a value when activated. The value of each of the OUTx is in accordance with
the table IB16_1. When not activated the OUTx has the value 0.

In the above example when integer 15 is on the input INP the OUT1 has a value =1, OUT2 has a
value =2, OUT3 has a value =4 and OUT4 has a value =8. The sum of these OUTx is equal to 1 + 2
+ 4 + 8 = 15.

This follows the general formulae: The sum of the values of all OUTx = 2x-1 where 1≤x≤16 will be
equal to the integer value on the input INP.

The Integer to Boolean 16 conversion function (IB16) will transfer an integer with a value
between 0 to 65535 connected to the input INP to a combination of activated outputs OUTx
where 1≤x≤16. The sum of the values of all OUTx will then be equal to the integer on input INP.
The values of the different OUTx are according to the table below. When an OUTx is not
activated, its value is 0.

When all OUTx where 1≤x≤16 are activated that is = Boolean 1 it corresponds to that integer
65535 is connected to input INP. The IB16 function is designed for receiving the integer input
locally. If the BLOCK input is activated, it will freeze the logical outputs at the last value.

Values of each of the different OUTx from function block IB16 for 1≤x≤16.

The sum of the value on each INx corresponds to the integer presented on the output OUT on
the function block IB16.

Name of OUTx Type Description Value when Value when


activated deactivated
OUT1 BOOLEAN Output 1 1 0
OUT2 BOOLEAN Output 2 2 0
OUT3 BOOLEAN Output 3 4 0
OUT4 BOOLEAN Output 4 8 0
OUT5 BOOLEAN Output 5 16 0
OUT6 BOOLEAN Output 6 32 0
OUT7 BOOLEAN Output 7 64 0
OUT8 BOOLEAN Output 8 128 0
OUT9 BOOLEAN Output 9 256 0
Table continues on next page

954 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

Name of OUTx Type Description Value when Value when


activated deactivated
OUT10 BOOLEAN Output 10 512 0
OUT11 BOOLEAN Output 11 1024 0
OUT12 BOOLEAN Output 12 2048 0
OUT13 BOOLEAN Output 13 4096 0
OUT14 BOOLEAN Output 14 8192 0
OUT15 BOOLEAN Output 15 16384 0
OUT16 BOOLEAN Output 16 32768 0

The sum of the numbers in column “Value when activated” when all OUTx (where x = 1 to 16)
are active that is=1; is 65535. 65535 is the highest integer that can be converted by the IB16
function block.

17.13.7 Technical data


GUID-B45901F4-B163-4696-8220-7F8CAC84D793 v2

Table 767: Number of IB16 instances


Function Quantity with cycle time
3 ms 8 ms 100 ms
IB16 6 4 8

17.14 Integer to Boolean 16 conversion with logic node


representation ITBGAPC SEMOD158419-1 v3

17.14.1 Identification
SEMOD167944-2 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Integer to boolean 16 conversion ITBGAPC - -
with logic node representation

17.14.2 Functionality SEMOD158421-5 v9

Integer to boolean conversion with logic node representation function (ITBGAPC) is used to
transform an integer which is transmitted over IEC 61850 and received by the function to 16
boolean (logic) output signals.

ITBGAPC function can only receive remote values over IEC 61850 when the R/L (Remote/Local)
push button on the front HMI indicates that the control mode for the operator is in position R
(Remote i.e. the LED adjacent to R is lit), and the corresponding signal is connected to the
input PSTO ITBGAPC function block. The input BLOCK will freeze the output at the last received
value and blocks new integer values to be received and converted to binary coded outputs.

Line distance protection REL670 955


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

17.14.3 Function block SEMOD158435-4 v4

ITBGAPC
BLOCK OUT1
PSTO OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
OUT9
OUT10
OUT11
OUT12
OUT13
OUT14
OUT15
OUT16

IEC14000012-1-en.vsd
IEC14000012 V1 EN-US

Figure 571: ITBGAPC function block

17.14.4 Signals
PID-3627-INPUTSIGNALS v7

Table 768: ITBGAPC Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
PSTO INTEGER 1 Operator place selection

PID-3627-OUTPUTSIGNALS v7

Table 769: ITBGAPC Output signals


Name Type Description
OUT1 BOOLEAN Output 1
OUT2 BOOLEAN Output 2
OUT3 BOOLEAN Output 3
OUT4 BOOLEAN Output 4
OUT5 BOOLEAN Output 5
OUT6 BOOLEAN Output 6
OUT7 BOOLEAN Output 7
OUT8 BOOLEAN Output 8
OUT9 BOOLEAN Output 9
OUT10 BOOLEAN Output 10
OUT11 BOOLEAN Output 11
OUT12 BOOLEAN Output 12
OUT13 BOOLEAN Output 13
OUT14 BOOLEAN Output 14
OUT15 BOOLEAN Output 15
OUT16 BOOLEAN Output 16

956 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

17.14.5 Settings
GUID-F573CA16-4821-4203-970A-F7D01AF5E63B v1
This function does not have any setting parameters.

17.14.6 Operation principle SEMOD176587-4 v6

An example is used to explain the principle of operation: With integer 15 sent to and received
by the ITBGAPC function on the IEC 61850 the OUTx changes from 0 to 1 on each of the OUT1;
OUT2 OUT3 and OUT4. All other OUTx (5≤x≤16) remains 0. The boolean interpretation of this is
represented by the assigned values of each of the outputs OUT1 = 1; and OUT2 = 2; and OUT3=
4; and OUT4 = 8. The sum of these OUTx (1≤x≤4) is equal to the integer 15 received via the IEC
61850 network. The remaining OUTx = 0 for (5≤x≤16).

OUTx represents a value when activated. The value of each of the OUTx is in accordance with
the Table 770. When not activated the OUTx has the value 0.

The value of each OUTx for 1≤x≤16 (1≤x≤16) follows the general formulae: OUTx = 2x-1 The sum
of the values of all activated OUTx = 2x-1 where 1≤x≤16 will be equal to the integer value
received over IEC 61850 to the ITBGAPC_1 function block.

The Integer to Boolean 16 conversion with logic node representation function (ITBGAPC) will
transfer an integer with a value between 0 to 65535 communicated via IEC 61850 and
connected to the ITBGAPC function block to a combination of activated outputs OUTx where
1≤x≤16. The values represented by the different OUTx are according to Table 770. When an
OUTx is not activated, its value is 0.

The ITBGAPC function is designed for receiving the integer input from a station computer - for
example, over IEC 61850. If the BLOCK input is activated, it will freeze the logical outputs at the
last value.

Table 770: Outputs and their values when activated


Name of OUTx Type Description Value when Value when
activated deactivated
OUT1 BOOLEAN Output 1 1 0
OUT2 BOOLEAN Output 2 2 0
OUT3 BOOLEAN Output 3 4 0
OUT4 BOOLEAN Output 4 8 0
OUT5 BOOLEAN Output 5 16 0
OUT6 BOOLEAN Output 6 32 0
OUT7 BOOLEAN Output 7 64 0
OUT8 BOOLEAN Output 8 128 0
OUT9 BOOLEAN Output 9 256 0
OUT10 BOOLEAN Output 10 512 0
OUT11 BOOLEAN Output 11 1024 0
OUT12 BOOLEAN Output 12 2048 0
OUT13 BOOLEAN Output 13 4096 0
OUT14 BOOLEAN Output 14 8192 0
OUT15 BOOLEAN Output 15 16384 0
OUT16 BOOLEAN Output 16 32768 0

Line distance protection REL670 957


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

The sum of the numbers in column “Value when activated” when all OUTx (1≤x≤16) are active
equals 65535. This is the highest integer that can be converted to boolean by the ITBGAPC
function block.

The operator position input (PSTO) determines the operator place. The integer number that is
communicated to the ITBGAPC can only be written to the block while the PSTO is in position
“Remote”. If PSTO is in position ”Off” or ”Local”, then no changes are applied to the outputs.

17.14.7 Technical data


GUID-A339BBA3-8FD0-429D-BB49-809EAC4D53B0 v2

Table 771: Number of ITBGAPC instances


Function Quantity with cycle time
3 ms 8 ms 100 ms
ITBGAPC 4 4 8

17.15 Elapsed time integrator with limit transgression and


overflow supervision TEIGAPC

17.15.1 Identification GUID-1913E066-37D1-4689-9178-5B3C8B029815 v3

Function Description IEC 61850 IEC 60617 ANSI/IEEE C37.2 device


identificatio identificatio number
n n
Elapsed time integrator TEIGAPC - -

17.15.2 Functionality GUID-390D7433-0C1C-48B4-9A90-71AA148C3C35 v3

Elapsed Time Integrator (TEIGAPC) function is a function that accumulates the elapsed time
when a given binary signal has been high, see also Figure 572.

BLOCK
RESET
IN Time Integration ACCTIME
with Retain

q-1

a
OVERFLOW
AND
a>b
999 999 s b

a
WARNING
AND
a>b
tWarning b

a
ALARM
AND
a>b
tAlarm b

q-1 = unit delay IEC13000290-2-en.vsd

IEC13000290 V2 EN-US

Figure 572: TEIGAPC logics


The main features of TEIGAPC

958 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

• Applicable to long time integration up to 999 999.9 seconds


• Supervision of overflow
• Possibility to define a warning and an alarm with the resolution of 10 milliseconds
• Retain the integration value
• Possibilities for blocking and reset of the total integrated time
• Report of the integrated time

17.15.3 Function block GUID-6D50A060-7751-405B-AEC1-FAE942EBDA64 v2

TEIGAPC
BLOCK WARNING
IN ALARM
RESET OVERFLOW
ACCTIME

IEC14000014-1-en.vsd
IEC14000014 V1 EN-US

Figure 573: TEIGAPC function block

17.15.4 Signals
PID-6836-INPUTSIGNALS v2

Table 772: TEIGAPC Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Freeze the integration and block the other outputs
IN BOOLEAN 0 The input signal that is used to measure the elapsed time,
when its value is high
RESET BOOLEAN 0 Reset the integration time

PID-6836-OUTPUTSIGNALS v2

Table 773: TEIGAPC Output signals


Name Type Description
WARNING BOOLEAN Indicator of the integrated time has reached the warning limit
ALARM BOOLEAN Indicator of the integrated time has reached the alarm limit
OVERFLOW BOOLEAN Indicator of the integrated time has reached the overflow
limit
ACCTIME REAL Integrated elapsed time in seconds

17.15.5 Settings
PID-6836-SETTINGS v2

Table 774: TEIGAPC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
tWarning 1.00 - 999999.00 s 0.01 600.00 Time limit for warning supervision
tAlarm 1.00 - 999999.00 s 0.01 1200.00 Time limit for alarm supervision

Line distance protection REL670 959


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

17.15.6 Operation principle GUID-04CC8365-DCDE-4DC7-BEF0-6EF8382305DD v3

The elapsed time integrator (TEIGAPC) provides

• time integration, accumulating the elapsed time when a given binary signal has been high
• blocking and reset of the total integrated time
• supervision of limit transgression and overflow, the overflow limit is fixed to 999999.9
seconds
• retaining of the integrated value

Figure 574 describes the simplified logic of the function where the block “Time
Integration“ covers the logics for the first two items listed above while the block
“Transgression Supervision Plus Retain“ contains the logics for the last two.

Loop Delay

tWarning
OVERFLOW
tAlarm
Transgression Supervision WARNING
Plus Retain
ALARM

BLOCK
RESET ACCTIME
Time Integration
IN

Loop Delay

IEC12000195-4-en.vsd

IEC12000195 V4 EN-US

Figure 574: TEIGAPC Simplified logic


TEIGAPC main functionalities

• integration of the elapsed time when IN has been high


• applicable to long time integration (≤999 999.9 seconds)
• output ACCTIME presents integrated value in seconds
• integrated value is retained in nonvolatile memory
• any retained value with a warning/alarm/overflow is used as initiation value for the
integration following by a restart
• RESET: Reset of the integration value. Consequently all other outputs are also reset
• unconditionally on the input IN value
• reset the value of the nonvolatile memory to zero
• BLOCK: Freeze the integration and block/reset the other outputs
• unconditionally on the signal value
• BLOCK request overrides RESET request
• Monitor and report the conditions of limit transgression
• overflow if output ACCTIME >999999.9 seconds
• alarm if ACCTIME > tAlarm
• warning if ACCTIME > tWarning

960 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

The ACCTIME output represents the integrated time in seconds while tOverflow, tAlarm and
tWarning are the time limit parameters in seconds.

tAlarm and tWarning are user settable limits. They are also independent, that is, there is no
check if tAlarm > tWarning.

tAlarm and tWarning are possible to be defined with a resolution of 10 ms, depending on the
level of the defined values for the parameters.

The limit for the overflow supervision is fixed at 999999.9 seconds. The outputs freeze if an
overflow occurs.

17.15.6.1 Operation accuracy GUID-E0772193-9F6E-43DA-B642-2923565E5D4C v3

The accuracy of TEIGAPC depends on essentially three factors

• function cycle time


• the pulse length
• the number of pulses, that is, the number of rising and falling flank pairs

In principle, a shorter function cycle time, longer integrated time length or more pulses may
lead to reduced accuracy.

17.15.6.2 Memory storage GUID-6FDD6590-30F9-4CC1-AC9D-945544AB8688 v3

The value of the integrated elapsed time is retained in a non-volatile memory.

17.15.7 Technical data


GUID-B258726E-1129-47C9-94F9-BE634A2085FA v4

Table 775: TEIGAPC Technical data


Function Cycle time (ms) Range or value Accuracy
Elapsed time integration 3 0 ~ 999999.9 s ±0.2% or ±20 ms whichever
is greater
8 0 ~ 999999.9 s ±0.2% or ±100 ms
whichever is greater
100 0 ~ 999999.9 s ±0.2% or ±250 ms
whichever is greater

Table 776: Number of TEIGAPC instances


Function Quantity with cycle time
3 ms 8 ms 100 ms
TEIGAPC 4 4 4

17.16 Comparator for integer inputs INTCOMP

17.16.1 Identification GUID-5992B0F2-FC1B-4838-9BAB-2D2542BB264D v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Comparison of integer values INTCOMP Int<=>

Line distance protection REL670 961


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

17.16.2 Functionality GUID-A93564FA-0017-4939-A9C1-095DA0FD9832 v1

The function gives the possibility to monitor the level of integer values in the system relative
to each other or to a fixed value. It is a basic arithmetic function that can be used for
monitoring, supervision, interlocking and other logics.

17.16.3 Function block GUID-EB28F45B-B1D0-452F-98B4-F96D7FA34069 v1

INTCOMP
INPUT INEQUAL
REF INHIGH
INLOW

IEC15000052-1-en.vsdx
IEC15000052 V1 EN-US

17.16.4 Signals
PID-6928-INPUTSIGNALS v2

Table 777: INTCOMP Input signals


Name Type Default Description
INPUT INTEGER 0 Input value to be compared with reference value
REF INTEGER 0 Reference value to be compared with input value

PID-6928-OUTPUTSIGNALS v2

Table 778: INTCOMP Output signals


Name Type Description
INEQUAL BOOLEAN Input value is equal to the reference value
INHIGH BOOLEAN Input value is higher than the reference value
INLOW BOOLEAN Input value is lower than the reference value

17.16.5 Settings
PID-6928-SETTINGS v2

Table 779: INTCOMP Group settings (basic)


Name Values (Range) Unit Step Default Description
EnaAbs Signed - - Signed Selection for absolute or signed
Absolute comparison
RefSource Set Value - - Set Value Selection for reference value either
Input REF input or setting
SetValue -2000000000 - - 1 100 Set value for reference
2000000000

962 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

17.16.6 Monitored data


PID-6928-MONITOREDDATA v1

Table 780: INTCOMP Monitored data


Name Type Values (Range) Unit Description
INEQUAL BOOLEAN - - Input value is equal to the reference
value
INHIGH BOOLEAN - - Input value is higher than the
reference value
INLOW BOOLEAN - - Input value is lower than the reference
value

17.16.7 Operation principle GUID-E9C1B863-ACA7-45C0-91F1-A51FE38755FE v2

The comparison can be done in two ways,

• Between 2 inputs, INPUT and REF


• Between INPUT and the value set by the user SetValue.

The selection of reference value for comparison can be done through setting RefSource. If
RefSource is selected as Input REF then the reference value for comparison is taken from
second input signal (REF). If RefSource is selected as Set Value then the reference value for
comparison is taken from setting (SetValue).

The comparison can be done either between absolute values or signed values and it depends
on the setting EnaAbs. If EnaAbs is selected as Absolute then both input and reference value is
converted into absolute values and comparison is done. If EnaAbs is selected as Signed then
the comparison is done without any conversion.

The function has three state outputs high, low and equal to condition. It will check the
following condition and give corresponding outputs.

• If the input is above the reference value then INHIGH is set HIGH
• If the input is below the reference value then INLOW is set HIGH
• If the input is equal to reference value then INEQUAL is set HIGH

EnaAbs
INPUT ABS T a
F
INHIGH
a>b
b

a INEQUAL
a=b
b
RefSource

REF ABS T
T
SetValue
F a INLOW
F a<b
b

IEC15000129-3-en.vsdx
IEC15000129 V4 EN-US

Figure 575: Function logic diagram for INTCOMP

Line distance protection REL670 963


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

17.16.8 Technical data GUID-CEA332FF-838D-42B7-AEFC-C1E87809825E v3

Table 781: Number of INTCOMP instances


Function Quantity with cycle time
3 ms 8 ms 100 ms
INTCOMP 10 10 10

17.17 Comparator for real inputs REALCOMP

17.17.1 Identification GUID-0D68E846-5A15-4C2C-91A2-F81A74034E81 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Comparator for real inputs REALCOMP Real<=>

17.17.2 Functionality GUID-E17A88D7-D095-4F36-9CD5-64EBFD2A1DEA v1

The function gives the possibility to monitor the level of real value signals in the system
relative to each other or to a fixed value. It is a basic arithmetic function that can be used for
monitoring, supervision, interlocking and other logics.

17.17.3 Function block GUID-8752DF2A-D131-4461-80C6-C52F9980D228 v1

REALCOMP
INPUT INEQUAL
REF INHIGH
INLOW

IEC15000053-1-en.vsdx
IEC15000053 V1 EN-US

17.17.4 Signals
PID-7248-INPUTSIGNALS v1

Table 782: REALCOMP Input signals


Name Type Default Description
INPUT REAL 0.000 Input value to be compared with reference value
REF REAL 0.000 Reference value to be compared with input value

PID-7248-OUTPUTSIGNALS v1

Table 783: REALCOMP Output signals


Name Type Description
INEQUAL BOOLEAN Input value is equal to the reference value
INHIGH BOOLEAN Input value is higher than the reference value
INLOW BOOLEAN Input value is lower than the reference value

964 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

17.17.5 Settings
PID-7248-SETTINGS v1

Table 784: REALCOMP Group settings (basic)


Name Values (Range) Unit Step Default Description
EnaAbs Signed - - Signed Selection for absolute or signed
Absolute comparison
RefSource Set Value - - Set Value Selection for reference value either
Input REF input or setting
SetValue -999.999 - - 0.001 0.001 Set value for reference
999.999
SetValPrefix milli - - unit Multiplication factor for SetValue
unit
kilo
Mega
Giga
EqualBandHigh 0.10 - 50.00 % 0.01 0.50 Equal band high limit in % of
reference value
EqualBandLow 0.10 - 50.00 % 0.01 0.50 Equal band low limit in % of reference
value

17.17.6 Operation principle GUID-3FA699A8-D076-4E5E-BCB8-C6B7907573D1 v2

The comparison can be done in two ways,

1. Between 2 inputs, INPUT and REF


2. Between INPUT and the SetValue setting

The selection of reference value for comparison can be done through setting RefSource. If
RefSource is selected as Input REF then the reference value for comparison is taken from
second input signal (REF). If RefSource is selected as Set Value then the reference value for
comparison is taken from setting (SetValue).

Generally the inputs to the function are in SI units, but when the comparison is to be done with
respect to set level, then the user can set a value in any unit out of Milli to Giga range in setting
SetValue. The unit can be separately set with setting RefPrefix. Internally the function handles
the reference value for comparator as SetValue*RefPrefix.

Additionally the comparison can be done either between absolute values or signed values and
it depends on the setting EnaAbs. If EnaAbs is selected as Absolute then both input and
reference value is converted into absolute values and then comparison is done. If EnaAbs is
selected as Signed then the comparison is done without absolute conversion.

Line distance protection REL670 965


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 506 370-UEN J
Logic

EnaAbs
INPUT
ABS T
F
High
Comparator
EqualBandHigh INHIGH

RefSource XOR INEQUAL

REF ABS T
T
F Low
SetValue F comparator
INLOW
SetValPrefix

EqualBandLow

IEC15000130-2-en.vsdx
IEC15000130 V2 EN-US

Figure 576: Logic diagram for REALCOMP


This function has two settings EqualBandHigh and EqualBandLow to provide margins from
reference value for equal to condition. When the INPUT value is within high and low band,
output INEQUAL will get set.

In order to avoid oscillations at boundary conditions of equal band low limit and high limit,
hysteresis has been provided. If the INPUT is above the equal high level margin including
hysteresis, then INHIGH will set. Similarly if the INPUT is below the equal low level margin
including hysteresis, then INLOW will set.

INEQUAL Reset / INHIGH Set INEQUAL Set / INHIGH Reset

EqualBandHigh

Internal
Equal Band REF or SetValue Hysteresis for
equal band

EqualBandLow

INEQUAL Reset / INLOW Set INEQUAL Set / INLOW Reset


IEC15000261-1-en.vsdx

IEC15000261 V1 EN-US

Figure 577: Operation principle of REALCOMP

When EnaAbs is set as absolute comparison and SetValue is set less than 0.2%
of the set unit then INLOW output will never pickups. During the above
mentioned condition, due to marginal value for avoiding oscillations of
function outputs, the INLOW output will never set.

966 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 17
Logic

17.17.7 Technical data


GUID-62792FCB-B436-4034-9A08-C9FF918FF547 v1
REALCOMP function can compare the values from milli value level to giga value level and the
maximum expectable accuracy level from the function is 10 µ.
GUID-3FDD7677-1D86-42AD-A545-B66081C49B47 v4

Table 785: Number of REALCOMP instances


Function Quantity with cycle time
3 ms 8 ms 100 ms
REALCOMP 10 10 10

Line distance protection REL670 967


Technical manual
© Copyright 2017 ABB. All rights reserved
968
1MRK 506 370-UEN J Section 18
Monitoring

Section 18 Monitoring
18.1 Measurements IP14593-1 v3

18.1.1 Identification
SEMOD56123-2 v8

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Power system measurements CVMMXN -
P, Q, S, I, U, f

SYMBOL-RR V1 EN-US

Phase current measurement CMMXU -

SYMBOL-SS V1 EN-US

Phase-phase voltage measurement VMMXU -

SYMBOL-UU V1 EN-US

Current sequence component CMSQI -


measurement
I1, I2, I0

SYMBOL-VV V1 EN-US

Voltage sequence component VMSQI -


measurement
U1, U2, U0

SYMBOL-TT V1 EN-US

Phase-neutral voltage measurement VNMMXU -

SYMBOL-UU V1 EN-US

18.1.2 Functionality SEMOD54488-4 v12

Measurement functions are used for power system measurement, supervision and reporting
to the local HMI, monitoring tool within PCM600 or to station level for example, via IEC 61850.
The possibility to continuously monitor measured values of active power, reactive power,
currents, voltages, frequency, power factor etc. is vital for efficient production, transmission
and distribution of electrical energy. It provides to the system operator fast and easy overview
of the present status of the power system. Additionally, it can be used during testing and
commissioning of protection and control IEDs in order to verify proper operation and
connection of instrument transformers (CTs and VTs). During normal service by periodic
comparison of the measured value from the IED with other independent meters the proper
operation of the IED analog measurement chain can be verified. Finally, it can be used to verify
proper direction orientation for distance or directional overcurrent protection function.

Line distance protection REL670 969


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

The available measured values from an IED are depending on the actual
hardware (TRM) and the logic configuration made in PCM600.

All measured values can be supervised with four settable limits that is, low-low limit, low limit,
high limit and high-high limit. A zero clamping reduction is also supported, that is, the
measured value below a settable limit is forced to zero which reduces the impact of noise in
the inputs.

Dead-band supervision can be used to report measured signal value to station level when
change in measured value is above set threshold limit or time integral of all changes since the
last time value updating exceeds the threshold limit. Measure value can also be based on
periodic reporting.

Main menu/Measurement/Monitoring/Service values/CVMMXN

The measurement function, CVMMXN, provides the following power system quantities:

• P, Q and S: three phase active, reactive and apparent power


• PF: power factor
• U: phase-to-phase voltage amplitude
• I: phase current amplitude
• F: power system frequency

,
The measuring functions CMMXU, VMMXU and VNMMXU provide physical quantities:

• I: phase currents (amplitude and angle) (CMMXU)


• U: voltages (phase-to-earth and phase-to-phase voltage, amplitude and angle) (VMMXU,
VNMMXU)

The CVMMXN function calculates three-phase power quantities by using fundamental


frequency phasors (DFT values) of the measured current and voltage signals. The measured
power quantities are available either, as instantaneously calculated quantities or, averaged
values over a period of time (low pass filtered) depending on the selected settings.

It is possible to calibrate the measuring function above to get better then class 0.5
presentation. This is accomplished by angle and amplitude compensation at 5, 30 and 100% of
rated current and at 100% of rated voltage.

The power system quantities provided, depends on the actual hardware, (TRM)
and the logic configuration made in PCM600.

The measuring functions CMSQI and VMSQI provide sequence component quantities:

• I: sequence currents (positive, zero, negative sequence, amplitude and angle)


• U: sequence voltages (positive, zero and negative sequence, amplitude and angle).

18.1.3 Function block SEMOD130334-4 v7

The available function blocks of an IED are depending on the actual hardware (TRM) and the
logic configuration made in PCM600.

970 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

CVMMXN
I3P* S
U3P* S_RANGE
P_INST
P
P_RANGE
Q_INST
Q
Q_RANGE
PF
PF_RANGE
ILAG
ILEAD
U
U_RANGE
I
I_RANGE
F
F_RANGE

IEC10000016-1-en.vsd
IEC10000016 V1 EN-US

Figure 578: CVMMXN function block

CMMXU
I3P* IL1
IL1RANG
IL1ANGL
IL2
IL2RANG
IL2ANGL
IL3
IL3RANG
IL3ANGL

IEC05000699-2-en.vsd
IEC05000699 V2 EN-US

Figure 579: CMMXU function block

VMMXU
U3P* UL12
UL12RANG
UL12ANGL
UL23
UL23RANG
UL23ANGL
UL31
UL31RANG
UL31ANGL

IEC05000701-2-en.vsd
IEC05000701 V2 EN-US

Figure 580: VMMXU function block

CMSQI
I3P* 3I0
3I0RANG
3I0ANGL
I1
I1RANG
I1ANGL
I2
I2RANG
I2ANGL

IEC05000703-2-en.vsd
IEC05000703 V2 EN-US

Figure 581: CMSQI function block

Line distance protection REL670 971


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

VMSQI
U3P* 3U0
3U0RANG
3U0ANGL
U1
U1RANG
U1ANGL
U2
U2RANG
U2ANGL

IEC05000704-2-en.vsd
IEC05000704 V2 EN-US

Figure 582: VMSQI function block

VNMMXU
U3P* UL1
UL1RANG
UL1ANGL
UL2
UL2RANG
UL2ANGL
UL3
UL3RANG
UL3ANGL

IEC09000850-1-en.vsd
IEC09000850 V1 EN-US

Figure 583: VNMMXU function block

18.1.4 Signals
PID-6713-INPUTSIGNALS v3

Table 786: CVMMXN Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL

PID-6713-OUTPUTSIGNALS v3

Table 787: CVMMXN Output signals


Name Type Description
S REAL Apparent Power magnitude of deadband value
S_RANGE INTEGER Apparent Power range
P_INST REAL Active Power
P REAL Active Power magnitude of deadband value
P_RANGE INTEGER Active Power range
Q_INST REAL Reactive Power
Q REAL Reactive Power magnitude of deadband value
Q_RANGE INTEGER Reactive Power range
PF REAL Power Factor magnitude of deadband value
PF_RANGE INTEGER Power Factor range
ILAG BOOLEAN Current is lagging voltage
ILEAD BOOLEAN Current is leading voltage
U REAL Calculated voltage magnitude of deadband value
U_RANGE INTEGER Calculated voltage range
Table continues on next page

972 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

Name Type Description


I REAL Calculated current magnitude of deadband value
I_RANGE INTEGER Calculated current range
F REAL System frequency magnitude of deadband value
F_RANGE INTEGER System frequency range

PID-6735-INPUTSIGNALS v3

Table 788: CMMXU Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL

PID-6735-OUTPUTSIGNALS v3

Table 789: CMMXU Output signals


Name Type Description
IL1 REAL IL1 Amplitude, magnitude of reported value
IL1RANG INTEGER IL1 Amplitude range
IL1ANGL REAL IL1 Angle, magnitude of reported value
IL2 REAL IL2 Amplitude, magnitude of reported value
IL2RANG INTEGER IL2 Amplitude range
IL2ANGL REAL IL2 Angle, magnitude of reported value
IL3 REAL IL3 Amplitude, magnitude of reported value
IL3RANG INTEGER IL3 Amplitude range
IL3ANGL REAL IL3 Angle, magnitude of reported value

PID-6738-INPUTSIGNALS v2

Table 790: VMMXU Input signals


Name Type Default Description
U3P GROUP - Group signal for voltage input
SIGNAL

PID-6738-OUTPUTSIGNALS v2

Table 791: VMMXU Output signals


Name Type Description
UL12 REAL UL12 Amplitude, magnitude of reported value
UL12RANG INTEGER UL12 Amplitude range
UL12ANGL REAL UL12 Angle, magnitude of reported value
UL23 REAL UL23 Amplitude, magnitude of reported value
UL23RANG INTEGER UL23 Amplitude range
UL23ANGL REAL UL23 Angle, magnitude of reported value
UL31 REAL UL31 Amplitude, magnitude of reported value
UL31RANG INTEGER UL31 Amplitude range
UL31ANGL REAL UL31 Angle, magnitude of reported value

Line distance protection REL670 973


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

PID-6736-INPUTSIGNALS v3

Table 792: CMSQI Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL

PID-6736-OUTPUTSIGNALS v3

Table 793: CMSQI Output signals


Name Type Description
3I0 REAL 3I0 Amplitude, magnitude of reported value
3I0RANG INTEGER 3I0 Amplitude range
3I0ANGL REAL 3I0 Angle, magnitude of reported value
I1 REAL I1 Amplitude, magnitude of reported value
I1RANG INTEGER I1 Amplitude range
I1ANGL REAL I1 Angle, magnitude of reported value
I2 REAL I2 Amplitude, magnitude of reported value
I2RANG INTEGER I2 Amplitude range
I2ANGL REAL I2 Angle, magnitude of reported value

PID-6739-INPUTSIGNALS v2

Table 794: VMSQI Input signals


Name Type Default Description
U3P GROUP - Group signal for voltage input
SIGNAL

PID-6739-OUTPUTSIGNALS v2

Table 795: VMSQI Output signals


Name Type Description
3U0 REAL 3U0 Amplitude, magnitude of reported value
3U0RANG INTEGER 3U0 Amplitude range
3U0ANGL REAL 3U0 Angle, magnitude of reported value
U1 REAL U1 Amplitude, magnitude of reported value
U1RANG INTEGER U1 Amplitude range
U1ANGL REAL U1 Angle, magnitude of reported value
U2 REAL U2 Amplitude, magnitude of reported value
U2RANG INTEGER U2 Amplitude range
U2ANGL REAL U2 Angle, magnitude of reported value

PID-6737-INPUTSIGNALS v2

Table 796: VNMMXU Input signals


Name Type Default Description
U3P GROUP - Group signal for voltage input
SIGNAL

974 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

PID-6737-OUTPUTSIGNALS v2

Table 797: VNMMXU Output signals


Name Type Description
UL1 REAL UL1 Amplitude, magnitude of reported value
UL1RANG INTEGER UL1 Amplitude range
UL1ANGL REAL UL1 Angle, magnitude of reported value
UL2 REAL UL2 Amplitude, magnitude of reported value
UL2RANG INTEGER UL2 Amplitude range
UL2ANGL REAL UL2 Angle, magnitude of reported value
UL3 REAL UL3 Amplitude, magnitude of reported value
UL3RANG INTEGER UL3 Amplitude range
UL3ANGL REAL UL3 Angle, magnitude of reported value

18.1.5 Settings SEMOD130322-4 v7

The available setting parameters of the measurement function (MMXU, MSQI) are depending
on the actual hardware (TRM) and the logic configuration made in PCM600.

These six functions are not handled as a group, so parameter settings are only available in the
first setting group.

The following terms are used in the Unit and Description columns:

• UBase (UB): Base voltage in primary kV. This voltage is used as reference for voltage
setting. It can be suitable to set this parameter to the rated primary voltage supervised
object.
• IBase (IB): Base current in primary A. This current is used as reference for current setting.
It can be suitable to set this parameter to the rated primary current of the supervised
object.
• SBase (SB): Base setting for power values in MVA.

PID-6713-SETTINGS v3

Table 798: CVMMXN Non group settings (basic)


Name Values (Range) Unit Step Default Description
SLowLim 0.0 - 2000.0 %SB 0.1 80.0 Low limit in % of SBase
SLowLowLim 0.0 - 2000.0 %SB 0.1 60.0 Low Low limit in % of SBase
SMin 0.0 - 2000.0 %SB 0.1 50.0 Minimum value in % of SBase
SMax 0.0 - 2000.0 %SB 0.1 200.0 Maximum value in % of SBase
SRepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
PMin -2000.0 - 2000.0 %SB 0.1 -200.0 Minimum value in % of SBase
PMax -2000.0 - 2000.0 %SB 0.1 200.0 Maximum value in % of SBase
Table continues on next page

Line distance protection REL670 975


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

Name Values (Range) Unit Step Default Description


PRepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
QMin -2000.0 - 2000.0 %SB 0.1 -200.0 Minimum value in % of SBase
QMax -2000.0 - 2000.0 %SB 0.1 200.0 Maximum value in % of SBase
QRepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
PFMin -1.000 - 1.000 - 0.001 -1.000 Minimum value
PFMax -1.000 - 1.000 - 0.001 1.000 Maximum value
PFRepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
UMin 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
UMax 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
URepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
IMin 0.0 - 500.0 %IB 0.1 5.0 Minimum value in % of IBase
IMax 0.0 - 500.0 %IB 0.1 200.0 Maximum value in % of IBase
IRepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
FrMin 0.000 - 100.000 Hz 0.001 0.000 Minimum value
FrMax 0.000 - 100.000 Hz 0.001 70.000 Maximum value
FrRepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
Operation Off - - Off Operation Off / On
On
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups
Table continues on next page

976 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

Name Values (Range) Unit Step Default Description


Mode L1, L2, L3 - - L1, L2, L3 Selection of measured current and
Arone voltage
Pos Seq
L1L2
L2L3
L3L1
L1
L2
L3
PowAmpFact 0.000 - 6.000 - 0.001 1.000 Amplitude factor to scale power
calculations
PowAngComp -180.0 - 180.0 Deg 0.1 0.0 Angle compensation for phase shift
between measured I & U
k 0.000 - 1.000 - 0.001 0.000 Low pass filter coefficient for power
measurement, U and I

Table 799: CVMMXN Non group settings (advanced)


Name Values (Range) Unit Step Default Description
SDbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
SZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
SHiHiLim 0.0 - 2000.0 %SB 0.1 150.0 High High limit in % of SBase
SHiLim 0.0 - 2000.0 %SB 0.1 120.0 High limit in % of SBase
SLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
PDbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
PZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
PHiHiLim -2000.0 - 2000.0 %SB 0.1 150.0 High High limit in % of SBase
PHiLim -2000.0 - 2000.0 %SB 0.1 120.0 High limit in % of SBase
PLowLim -2000.0 - 2000.0 %SB 0.1 -120.0 Low limit in % of SBase
PLowLowLim -2000.0 - 2000.0 %SB 0.1 -150.0 Low Low limit in % of SBase
PLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
QDbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
QZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
QHiHiLim -2000.0 - 2000.0 %SB 0.1 150.0 High High limit in % of SBase
QHiLim -2000.0 - 2000.0 %SB 0.1 120.0 High limit in % of SBase
QLowLim -2000.0 - 2000.0 %SB 0.1 -120.0 Low limit in % of SBase
QLowLowLim -2000.0 - 2000.0 %SB 0.1 -150.0 Low Low limit in % of SBase
QLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
PFDbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
PFZeroDb 0 - 100000 m% 100 500 Magnitude zero point clamping in
0,001% of range
Table continues on next page

Line distance protection REL670 977


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

Name Values (Range) Unit Step Default Description


PFHiHiLim -1.000 - 1.000 - 0.001 1.000 High High limit (physical value)
PFHiLim -1.000 - 1.000 - 0.001 0.800 High limit (physical value)
PFLowLim -1.000 - 1.000 - 0.001 -0.800 Low limit (physical value)
PFLowLowLim -1.000 - 1.000 - 0.001 -1.000 Low Low limit (physical value)
PFLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
UDbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
UZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
UHiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
UHiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
ULowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
ULowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
ULimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
IDbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
IZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
IHiHiLim 0.0 - 500.0 %IB 0.1 150.0 High High limit in % of IBase
IHiLim 0.0 - 500.0 %IB 0.1 120.0 High limit in % of IBase
ILowLim 0.0 - 500.0 %IB 0.1 80.0 Low limit in % of IBase
ILowLowLim 0.0 - 500.0 %IB 0.1 60.0 Low Low limit in % of IBase
ILimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
FrDbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
FrZeroDb 0 - 100000 m% 10 100 Magnitude zero point clamping in
0,001% of range
FrHiHiLim 0.000 - 100.000 Hz 0.001 65.000 High High limit (physical value)
FrHiLim 0.000 - 100.000 Hz 0.001 63.000 High limit (physical value)
FrLowLim 0.000 - 100.000 Hz 0.001 47.000 Low limit (physical value)
FrLowLowLim 0.000 - 100.000 Hz 0.001 45.000 Low Low limit (physical value)
FrLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
UGenZeroDb 1 - 100 %UB 1 5 Zero point clamping in % of UBase
IGenZeroDb 1 - 100 %IB 1 5 Zero point clamping in % of IBase
UAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage
at 5% of Ur
UAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage
at 30% of Ur
UAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage
at 100% of Ur
IAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current
at 5% of Ir
IAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current
at 30% of Ir
Table continues on next page

978 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

Name Values (Range) Unit Step Default Description


IAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current
at 100% of Ir
IAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 5% of
Ir
IAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 30% of
Ir
IAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 100%
of Ir

PID-6735-SETTINGS v3

Table 800: CMMXU Non group settings (basic)


Name Values (Range) Unit Step Default Description
IL1DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
Operation Off - - Off Operation Mode On / Off
On
IL1Min 0.0 - 500.0 %IB 0.1 50.0 Minimum value in % of IBase
IL1Max 0.0 - 500.0 %IB 0.1 200.0 Maximum value in % of IBase
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups
IL1RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
IL1AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
IL2DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
IL2Min 0.0 - 500.0 %IB 0.1 50.0 Minimum value in % of IBase
IL2Max 0.0 - 500.0 %IB 0.1 200.0 Maximum value in % of IBase
IL2RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
IL2AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
IL3DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
IL3Min 0.0 - 500.0 %IB 0.1 50.0 Minimum value in % of IBase
IL3Max 0.0 - 500.0 %IB 0.1 200.0 Maximum value in % of IBase
IL3RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
IL3AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)

Line distance protection REL670 979


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

Table 801: CMMXU Non group settings (advanced)


Name Values (Range) Unit Step Default Description
IL1ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
IL1HiHiLim 0.0 - 500.0 %IB 0.1 150.0 High High limit in % of IBase
IL1HiLim 0.0 - 500.0 %IB 0.1 120.0 High limit in % of IBase
IAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current
at 5% of Ir
IAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current
at 30% of Ir
IL1LowLim 0.0 - 500.0 %IB 0.1 80.0 Low limit in % of IBase
IL1LowLowLim 0.0 - 500.0 %IB 0.1 60.0 Low Low limit in % of IBase
IAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current
at 100% of Ir
IAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 5% of
Ir
IAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 30% of
Ir
IAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 100%
of Ir
IL1LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
IL2ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
IL2HiHiLim 0.0 - 500.0 %IB 0.1 150.0 High High limit in % of IBase
IL2HiLim 0.0 - 500.0 %IB 0.1 120.0 High limit in % of IBase
IL2LowLim 0.0 - 500.0 %IB 0.1 80.0 Low limit in % of IBase
IL2LowLowLim 0.0 - 500.0 %IB 0.1 60.0 Low Low limit in % of IBase
IL2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
IL3ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
IL3HiHiLim 0.0 - 500.0 %IB 0.1 150.0 High High limit in % of IBase
IL3HiLim 0.0 - 500.0 %IB 0.1 120.0 High limit in % of IBase
IL3LowLim 0.0 - 500.0 %IB 0.1 80.0 Low limit in % of IBase
IL3LowLowLim 0.0 - 500.0 %IB 0.1 60.0 Low Low limit in % of IBase
IL3LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits

PID-6738-SETTINGS v2

Table 802: VMMXU Non group settings (basic)


Name Values (Range) Unit Step Default Description
UL12DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
Operation Off - - Off Operation Mode On / Off
On
UL12ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
UL12Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
Table continues on next page

980 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

Name Values (Range) Unit Step Default Description


UL12Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
UL12RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups
UL12AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
UL23DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
UL23ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
UL23Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
UL23Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
UL23RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
UL23AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
UL31DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
UL31ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
UL31Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
UL31Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
UL31RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
UL31AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)

Table 803: VMMXU Non group settings (advanced)


Name Values (Range) Unit Step Default Description
UL12HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
UL12HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
UL12LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
UL12LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
UAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage
at 100% of Ur
UL12LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
UL23HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
UL23HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
UL23LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
Table continues on next page

Line distance protection REL670 981


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

Name Values (Range) Unit Step Default Description


UL23LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
UL23LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
UL31HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
UL31HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
UL31LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
UL31LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
UL31LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits

PID-6736-SETTINGS v3

Table 804: CMSQI Non group settings (basic)


Name Values (Range) Unit Step Default Description
3I0DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
3I0ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
3I0Min 0.0 - 500.0 %IB 0.1 50.0 Minimum value in % of IBase
3I0Max 0.0 - 500.0 %IB 0.1 200.0 Maximum value in % of IBase
3I0RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups
3I0LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
3I0AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
Operation Off - - Off Operation Mode On / Off
On
I1DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
I1ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
I1Min 0.0 - 500.0 %IB 0.1 50.0 Minimum value in % of IBase
I1Max 0.0 - 500.0 %IB 0.1 200.0 Maximum value in % of IBase
I1RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
I1AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
I2DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
I2ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
I2Min 0.0 - 500.0 %IB 0.1 50.0 Minimum value in % of IBase
Table continues on next page

982 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

Name Values (Range) Unit Step Default Description


I2Max 0.0 - 500.0 %IB 0.1 200.0 Maximum value in % of IBase
I2RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
I2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
I2AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)

Table 805: CMSQI Non group settings (advanced)


Name Values (Range) Unit Step Default Description
3I0HiHiLim 0.0 - 500.0 %IB 0.1 150.0 High High limit in % of IBase
3I0HiLim 0.0 - 500.0 %IB 0.1 120.0 High limit in % of IBase
3I0LowLim 0.0 - 500.0 %IB 0.1 80.0 Low limit in % of IBase
3I0LowLowLim 0.0 - 500.0 %IB 0.1 60.0 Low Low limit in % of IBase
I1HiHiLim 0.0 - 500.0 %IB 0.1 150.0 High High limit in % of IBase
I1HiLim 0.0 - 500.0 %IB 0.1 120.0 High limit in % of IBase
I1LowLim 0.0 - 500.0 %IB 0.1 80.0 Low limit in % of IBase
I1LowLowLim 0.0 - 500.0 %IB 0.1 60.0 Low Low limit in % of IBase
I1LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
I2HiHiLim 0.0 - 500.0 %IB 0.1 150.0 High High limit in % of IBase
I2HiLim 0.0 - 500.0 %IB 0.1 120.0 High limit in % of IBase
I2LowLim 0.0 - 500.0 %IB 0.1 80.0 Low limit in % of IBase
I2LowLowLim 0.0 - 500.0 %IB 0.1 60.0 Low Low limit in % of IBase

PID-6739-SETTINGS v2

Table 806: VMSQI Non group settings (basic)


Name Values (Range) Unit Step Default Description
3U0DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
3U0ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
3U0Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
3U0Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups
3U0RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
3U0LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
3U0AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
Table continues on next page

Line distance protection REL670 983


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Mode On / Off
On
U1DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
U1ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
U1Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
U1Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
U1RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
U1LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
U1AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
U2DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
U2ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
U2Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
U2Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
U2RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
U2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
U2AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
UAmpPreComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to pre-calibrate
voltage at 5% of Ur
UAmpPreComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to pre-calibrate
voltage at 30% of Ur
UAmpPreComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to pre-calibrate
voltage at 100% of Ur

Table 807: VMSQI Non group settings (advanced)


Name Values (Range) Unit Step Default Description
3U0HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
3U0HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
3U0LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
3U0LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
U1HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
U1HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
U1LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
U1LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
Table continues on next page

984 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

Name Values (Range) Unit Step Default Description


U2HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
U2HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
U2LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
U2LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase

PID-6737-SETTINGS v2

Table 808: VNMMXU Non group settings (basic)


Name Values (Range) Unit Step Default Description
UL1DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
Operation Off - - Off Operation Mode On / Off
On
UL1ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
UL1Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
UL1Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups
UL1RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
UL1LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
UL1AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
UL2DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
UL2ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
UL2Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
UL2Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
UL2RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
UL2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
UL2AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
UL3DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
UL3ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
UL3Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
UL3Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
Table continues on next page

Line distance protection REL670 985


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

Name Values (Range) Unit Step Default Description


UL3RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
UL3LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
UL3AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)

Table 809: VNMMXU Non group settings (advanced)


Name Values (Range) Unit Step Default Description
UL1HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
UL1HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
UL1LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
UL1LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
UAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage
at 100% of Ur
UL2HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
UL2HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
UL2LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
UL2LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
UL3HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
UL3HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
UL3LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
UL3LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase

18.1.6 Monitored data


PID-6713-MONITOREDDATA v3

Table 810: CVMMXN Monitored data


Name Type Values (Range) Unit Description
S REAL - MVA Apparent Power magnitude of
deadband value
P REAL - MW Active Power magnitude of deadband
value
Q REAL - MVAr Reactive Power magnitude of
deadband value
PF REAL - - Power Factor magnitude of deadband
value
U REAL - kV Calculated voltage magnitude of
deadband value
I REAL - A Calculated current magnitude of
deadband value
F REAL - Hz System frequency magnitude of
deadband value

986 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

PID-6735-MONITOREDDATA v3

Table 811: CMMXU Monitored data


Name Type Values (Range) Unit Description
IL1 REAL - A IL1 Amplitude, magnitude of reported
value
IL1ANGL REAL - deg IL1 Angle, magnitude of reported value
IL2 REAL - A IL2 Amplitude, magnitude of reported
value
IL2ANGL REAL - deg IL2 Angle, magnitude of reported
value
IL3 REAL - A IL3 Amplitude, magnitude of reported
value
IL3ANGL REAL - deg IL3 Angle, magnitude of reported
value

PID-6738-MONITOREDDATA v2

Table 812: VMMXU Monitored data


Name Type Values (Range) Unit Description
UL12 REAL - kV UL12 Amplitude, magnitude of
reported value
UL12ANGL REAL - deg UL12 Angle, magnitude of reported
value
UL23 REAL - kV UL23 Amplitude, magnitude of
reported value
UL23ANGL REAL - deg UL23 Angle, magnitude of reported
value
UL31 REAL - kV UL31 Amplitude, magnitude of
reported value
UL31ANGL REAL - deg UL31 Angle, magnitude of reported
value

PID-6736-MONITOREDDATA v3

Table 813: CMSQI Monitored data


Name Type Values (Range) Unit Description
3I0 REAL - A 3I0 Amplitude, magnitude of reported
value
3I0ANGL REAL - deg 3I0 Angle, magnitude of reported
value
I1 REAL - A I1 Amplitude, magnitude of reported
value
I1ANGL REAL - deg I1 Angle, magnitude of reported value
I2 REAL - A I2 Amplitude, magnitude of reported
value
I2ANGL REAL - deg I2 Angle, magnitude of reported value

Line distance protection REL670 987


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

PID-6739-MONITOREDDATA v2

Table 814: VMSQI Monitored data


Name Type Values (Range) Unit Description
3U0 REAL - kV 3U0 Amplitude, magnitude of
reported value
3U0ANGL REAL - deg 3U0 Angle, magnitude of reported
value
U1 REAL - kV U1 Amplitude, magnitude of reported
value
U1ANGL REAL - deg U1 Angle, magnitude of reported value
U2 REAL - kV U2 Amplitude, magnitude of reported
value
U2ANGL REAL - deg U2 Angle, magnitude of reported value

PID-6737-MONITOREDDATA v2

Table 815: VNMMXU Monitored data


Name Type Values (Range) Unit Description
UL1 REAL - kV UL1 Amplitude, magnitude of reported
value
UL1ANGL REAL - deg UL1 Angle, magnitude of reported
value
UL2 REAL - kV UL2 Amplitude, magnitude of
reported value
UL2ANGL REAL - deg UL2 Angle, magnitude of reported
value
UL3 REAL - kV UL3 Amplitude, magnitude of
reported value
UL3ANGL REAL - deg UL3 Angle, magnitude of reported
value

18.1.7 Operation principle

18.1.7.1 Measurement supervision SEMOD54417-130 v4

The protection, control, and monitoring IEDs have functionality to measure and further
process information for currents and voltages obtained from the pre-processing blocks. The
number of processed alternate measuring quantities depends on the type of IED and built-in
options.

The information on measured quantities is available for the user at different locations:

• Locally by means of the local HMI


• Remotely using the monitoring tool within PCM600 or over the station bus
• Internally by connecting the analogue output signals to the Disturbance Report function

Phase angle reference SEMOD54417-303 v5


All phase angles are presented in relation to a defined reference channel. The General setting
parameter PhaseAngleRef defines the reference, see section "Analog inputs".

988 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

Zero point clamping SEMOD54417-137 v4


Measured value below zero point clamping limit is forced to zero. This allows the noise in the
input signal to be ignored. The zero point clamping limit is a general setting (XZeroDb where X
equals S, P, Q, PF, U, I, F, IL1-3, UL1-3, UL12-31, I1, I2, 3I0, U1, U2 or 3U0). Observe that this
measurement supervision zero point clamping might be overridden by the zero point clamping
used for the measurement values within CVMMXN.

Continuous monitoring of the measured quantity SEMOD54417-140 v5


Users can continuously monitor the measured quantity available in the function block by
means of four defined operating thresholds, see figure 584. The monitoring has two different
modes of operating:

• Overfunction, when the measured quantity exceeds the High limit (XHiLim) or High-high
limit (XHiHiLim) pre-set values
• Underfunction, when the measured quantity decreases under the Low limit (XLowLim) or
Low-low limit (XLowLowLim) pre-set values.

X_RANGE is illustrated in figure 584.

Y = Magnitude of the Measured Quantity

X_RANGE = 3
High-high limit

X_RANGE= 1 Hysteresis
High limit

X_RANGE=0

X_RANGE=0 t

Low limit

X_RANGE=2

Low-low limit
X_RANGE=4

IEC05000657-3-en.vsdx
IEC05000657 V3 EN-US

Figure 584: Presentation of operating limits


Each analogue output has one corresponding supervision level output (X_RANGE). The output
signal is an integer in the interval 0-4 (0: Normal, 1: High limit exceeded, 3: High-high limit
exceeded, 2: below Low limit and 4: below Low-low limit).

The logical value of the functional output signals changes according to figure 584.

The user can set the hysteresis (XLimHyst), which determines the difference between the
operating and reset value at each operating point, in wide range for each measuring channel
separately. The hysteresis is common for all operating values within one channel.

Actual value of the measured quantity SEMOD54417-150 v4


The actual value of the measured quantity is available locally and remotely. The measurement
is continuous for each measured quantity separately, but the reporting of the value to the
higher levels depends on the selected reporting mode. The following basic reporting modes
are available:

• Cyclic reporting (Cyclic)


• Amplitude dead-band supervision (Dead band)
• Integral dead-band supervision (Int deadband)

Line distance protection REL670 989


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

• Amplitude Deadband and 5s cyclic


• Amplitude Deadband and 30s cyclic
• Amplitude Deadband and 1min cyclic

Cyclic reporting SEMOD54417-158 v3


The cyclic reporting of measured value is performed according to chosen setting (XRepTyp).
The measuring channel reports the value independent of amplitude or integral dead-band
reporting.

In addition to the normal cyclic reporting the IED also report spontaneously when measured
value passes any of the defined threshold limits.

Y
Value Reported Value Reported
Value Reported Value Reported
(1st)

Y3 Value Reported
Y2 Y4

Y1 Y5

t (*) t (*) t (*) t (*)

t
Value 1

Value 2

Value 3

Value 4

Value 5

(*)Set value for t: XDbRepInt IEC05000500-2-en.vsdx

IEC05000500 V2 EN-US

Figure 585: Periodic reporting

Amplitude dead-band supervision SEMOD54417-163 v6


If a measuring value is changed, compared to the last reported value, and the change is larger
than the ±ΔY pre-defined limits that are set by user (XDbRepInt), then the measuring channel
reports the new value to a higher level. This limits the information flow to a minimum
necessary. Figure 586 shows an example with the amplitude dead-band supervision. The
picture is simplified: the process is not continuous but the values are evaluated with a time
interval of one execution cycle from each other.

990 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

Value Reported
Y

Value Reported Value Reported


Value Reported
(1st)
Y3 Y
Y
Y2 Y
Y
Y
Y
Y1

IEC99000529-2-en.vsdx

IEC99000529 V2 EN-US

Figure 586: Amplitude dead-band supervision reporting


After the new value is reported, the ±ΔY limits for dead-band are automatically set around it.
The new value is reported only if the measured quantity changes more than defined by the ±ΔY
set limits.

Integral dead-band reporting SEMOD54417-167 v4


The measured value is reported if the time integral of all changes exceeds the pre-set limit
(XDbRepInt), figure 587, where an example of reporting with integral dead-band supervision is
shown. The picture is simplified: the process is not continuous but the values are evaluated
with a time interval of one execution cycle from each other.

The last value reported, Y1 in figure 587 serves as a basic value for further measurement. A
difference is calculated between the last reported and the newly measured value and is
multiplied by the time increment (discrete integral). The absolute values of these integral
values are added until the pre-set value is exceeded. This occurs with the value Y2 that is
reported and set as a new base for the following measurements (as well as for the values Y3,
Y4 and Y5).

The integral dead-band supervision is particularly suitable for monitoring signals with small
variations that can last for relatively long periods.

Line distance protection REL670 991


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

Y A1 >=
A >= pre-set value
A2 >=
pre-set value pre-set value
Y3 A3 + A4 + A5 + A6 + A7 >=
pre-set value
Y2 A1 A2
A4 A6
Value Reported Y4 A3 A5 A7
Value
(1st) Value
A Reported Y5
Reported Value
Reported Value
Y1 Reported

t
IEC99000530-2-en.vsdx

IEC99000530 V2 EN-US

Figure 587: Reporting with integral dead-band supervision

Amplitude deadband and xx cyclic (xx: 5 sec, 30 sec, 1 min) GUID-297D6481-EDFA-4A38-BC9D-29538491254D v1


In this mode of operation, the reporting interval will be cyclic like in reporting type cyclic. This
cyclic time has three options: 5sec, 30 sec and 1 min.

Additionally, if a measuring value has changed from the last reported value, and the change is
larger than ±ΔY predefined limits that are set by user (XDbRepInt), then the measuring channel
reports the new value to a higher level immediately irrespective of cyclic trigger. See Figure
588 for example.

992 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

Value

Y1...Y7 : Cyclic reported values, depending upon time Δt.


Y’ and Y” : Deadband reported value, change is greater than setting

Value
Reported

Y5
Y6

Y’ -ΔY

+ΔY
Y1 Y7
Y2 Y4 Y”

Y3

Δt Δt Δt Δt Δt Δt

Time
IEC16000109-1-en.vsdx
IEC16000109 V1 EN-US

Figure 588: Example of value reporting in mode dead band and xx cyclic (xx : 5 sec , 30
sec, 1 min)

18.1.7.2 Measurements CVMMXN SEMOD54417-172 v3

Mode of operation SEMOD54417-174 v7


The measurement function must be connected to three-phase current and three-phase voltage
input in the configuration tool (group signals), but it is capable to measure and calculate
above mentioned quantities in nine different ways depending on the available VT inputs
connected to the IED. The end user can freely select by a parameter setting, which one of the
nine available measuring modes shall be used within the function. Available options are
summarized in the following table:

Line distance protection REL670 993


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

Set value Formula used for complex, Formula used for voltage Comment
for three-phase power calculation and current magnitude
parameter calculation
“Mode”
1 L1, L2, L3 Used when three phase-to-
* * *
S = U L1 × I L1 + U L 2 × I L 2 + U L 3 × I L 3 U = ( U L1 + U L 2 + U L 3 ) / 3 earth voltages are available
EQUATION1385 V1 EN-US (Equation 187) I = ( I L1 + I L 2 + I L 3 ) / 3

EQUATION1386 V1 EN-US (Equation 188)


2 Arone Used when two phase-to-
S = U L1 L 2 × I L*1 - U L 2 L 3 × I L* 3 U = ( U L1 L 2 + U L 2 L 3 ) / 2 phase voltages are
available
(Equation 189)
EQUATION1387 V1 EN-US
I = ( I L1 + I L 3 ) / 2
EQUATION1388 V1 EN-US (Equation 190)
3 PosSeq Used when only
S = 3 × U PosSeq × I PosSeq
*
U = 3 × U PosSeq symmetrical three phase
power shall be measured
(Equation 191)
EQUATION1389 V1 EN-US
I = I PosSeq
EQUATION1390 V1 EN-US (Equation 192)
4 L1L2 Used when only UL1L2
S = U L1 L 2 × ( I L*1 - I L* 2 ) U = U L1 L 2 phase-to-phase voltage is
available
(Equation 193)
I = ( I L1 + I L 2 ) / 2
EQUATION1391 V1 EN-US

EQUATION1392 V1 EN-US (Equation 194)


5 L2L3 Used when only UL2L3
S = U L 2 L 3 × ( I L* 2 - I L* 3 ) U = U L2 L3 phase-to-phase voltage is
available
(Equation 195)
I = ( I L2 + I L3 ) / 2
EQUATION1393 V1 EN-US

EQUATION1394 V1 EN-US (Equation 196)


6 L3L1 Used when only UL3L1
S = U L 3 L1 × ( I L* 3 - I L*1 ) U = U L 3 L1 phase-to-phase voltage is
available
(Equation 197)
I = ( I L 3 + I L1 ) / 2
EQUATION1395 V1 EN-US

EQUATION1396 V1 EN-US (Equation 198)


7 L1 Used when only UL1 phase-
S = 3 × U L1 × I L*1 U = 3 × U L1 to-earth voltage is
available
(Equation 199)
I = I L1
EQUATION1397 V1 EN-US

EQUATION1398 V1 EN-US (Equation 200)


8 L2 Used when only UL2 phase-
S = 3 × U L 2 × I L* 2 U = 3 × U L2 to-earth voltage is
available
(Equation 201)
I = IL2
EQUATION1399 V1 EN-US

EQUATION1400 V1 EN-US (Equation 202)


9 L3 Used when only UL3 phase-
S = 3 × U L 3 × I L* 3 U = 3 × U L3 to-earth voltage is
available
(Equation 203)
I = I L3
EQUATION1401 V1 EN-US

EQUATION1402 V1 EN-US (Equation 204)


* means complex conjugated value

994 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

It shall be noted that only in the first two operating modes that is, 1 & 2 the measurement
function calculates the three-phase power accurately. In other operating modes that is, from 3
to 9 it calculates the three-phase power under assumption that the power system is fully
symmetrical. Once the complex apparent power is calculated then the P, Q, S, & PF are
calculated in accordance with the following formulas:

P = Re( S )
EQUATION1403 V1 EN-US (Equation 205)

Q = Im( S )
EQUATION1404 V1 EN-US (Equation 206)

S = S = P2 + Q2
EQUATION1405 V1 EN-US (Equation 207)

PF = cosj = P
S
EQUATION1406 V1 EN-US (Equation 208)

Additionally to the power factor value, the two binary output signals from the function are
provided which indicates the angular relationship between the current and voltage phasors.
Binary output signal ILAG is set TRUE when current phasor is lagging behind voltage phasor.
Binary output signal ILEAD is set TRUE when current phasor is leading the voltage phasor.

Each analogue output has a corresponding supervision level output (X_RANGE). The output
signal is an integer in the interval 0-4, see section "Measurement supervision".

Calibration of analog inputs SEMOD54417-293 v5


Measured currents and voltages used in the CVMMXN function can be calibrated to get 0.5
class measuring accuracy. This is achieved by amplitude and angle compensation at 5, 30 and
100% of rated current and voltage. The compensation below 5% and above 100% is constant
and linear in between, see example in figure 589.

Line distance protection REL670 995


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

IEC05000652 V2 EN-US

Figure 589: Calibration curves


The first current and voltage phase signal, in the group signals will be used as reference. The
amplitude and angle compensation will be used for other related input signals.

Low pass filtering SEMOD54417-233 v4


In order to minimize the influence of the noise signal on the measurement it is possible to
introduce the recursive, low pass filtering of the measured values for P, Q, S, U, I and power
factor. This will make slower measurement response to the step changes in the measured
quantity. Filtering is performed in accordance with the following recursive formula:

X = k × X Old + (1 - k ) × X Calculated
EQUATION1407 V1 EN-US (Equation 209)

where:
X is a new measured value (that is P, Q, S, U, I or PF) to be given out from the function
XOld is the measured value given from the measurement function in previous execution cycle

XCalculated is the new calculated value in the present execution cycle

k is settable parameter by the end user which influence the filter properties

Default value for parameter k is 0.00. With this value the new calculated value is immediately
given out without any filtering (that is, without any additional delay). When k is set to value
bigger than 0, the filtering is enabled. Appropriate value of k shall be determined separately
for every application. Some typical value for k =0.14.

Zero point clamping SEMOD54417-250 v5


In order to avoid erroneous measurements when either current or voltage signal is not
present, it is possible for the end user to set the amplitudeIGenZeroDb level for current and
voltage measurement UGenZeroDb is forced to zero. When either current or voltage

996 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

measurement is forced to zero automatically the measured values for power (P, Q and S) and
power factor are forced to zero as well. Since the measurement supervision functionality,
included in CVMMXN, is using these values the zero clamping will influence the subsequent
supervision (observe the possibility to do zero point clamping within measurement
supervision, see section "Measurement supervision").

Compensation facility SEMOD54417-253 v5


In order to compensate for small amplitude and angular errors in the complete measurement
chain (CT error, VT error, IED input transformer errors and so on.) it is possible to perform on
site calibration of the power measurement. This is achieved by setting the complex constant
which is then internally used within the function to multiply the calculated complex apparent
power S. This constant is set as amplitude (setting parameter PowAmpFact, default value
1.000) and angle (setting parameter PowAngComp, default value 0.0 degrees). Default values
for these two parameters are done in such way that they do not influence internally calculated
value (complex constant has default value 1). In this way calibration, for specific operating
range (for example, around rated power) can be done at site. However, to perform this
calibration it is necessary to have an external power meter with high accuracy class available.

Directionality SEMOD54417-256 v7
If CT earthing parameter is set as described in section "Analog inputs", active and reactive
power will be always measured towards the protected object. This is shown in the following
figure 590.

Busbar

IED

P Q

Protected
Object
IEC09000038-1-en.vsd
IEC09000038-1-EN V1 EN-US

Figure 590: Internal IED directionality convention for P & Q measurements


Practically, it means that active and reactive power will have positive values when they flow
from the busbar towards the protected object and they will have negative values when they
flow from the protected object towards the busbar.

In some application, for example, when power is measured on the secondary side of the power
transformer it might be desirable, from the end client point of view, to have actually opposite
directional convention for active and reactive power measurements. This can be easily
achieved by setting parameter PowAngComp to value of 180.0 degrees. With such setting the

Line distance protection REL670 997


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

active and reactive power will have positive values when they flow from the protected object
towards the busbar.

Frequency SEMOD54417-261 v2
Frequency is actually not calculated within measurement block. It is simply obtained from the
pre-processing block and then just given out from the measurement block as an output.

18.1.7.3 Phase current measurement CMMXU SEMOD54417-264 v7

The Phase current measurement (CMMXU) function must be connected to three-phase current
input in the configuration tool to be operable. Currents handled in the function can be
calibrated to get better then 0.5 class measuring accuracy for internal use, on the outputs and
IEC 61850. This is achieved by amplitude and angle compensation at 5, 30 and 100% of rated
current. The compensation below 5% and above 100% is constant and linear in between, see
figure 589.

Phase currents (amplitude and angle) are available on the outputs and each amplitude output
has a corresponding supervision level output (ILx_RANG). The supervision output signal is an
integer in the interval 0-4, see section "Measurement supervision".

18.1.7.4 Phase-phase and phase-neutral voltage measurements VMMXU, VNMMXU SEMOD54417-268 v6

The voltage function must be connected to three-phase voltage input in the configuration tool
to be operable. Voltages are handled in the same way as currents when it comes to class 0.5
calibrations, see above.

The voltages (phase-to-earth or phase-to-phase voltage, amplitude and angle) are available on
the outputs and each amplitude output has a corresponding supervision level output
(ULxy_RANG). The supervision output signal is an integer in the interval 0-4, see
section "Measurement supervision".

18.1.7.5 Voltage and current sequence measurements VMSQI, CMSQI SEMOD54417-299 v6

The measurement functions must be connected to three-phase current (CMSQI) or voltage


(VMSQI) input in the configuration tool to be operable. No outputs, other than X_RANG, are
calculated within the measuring blocks and it is not possible to calibrate the signals. Input
signals are obtained from the pre-processing block and transferred to corresponding output.

Positive, negative and three times zero sequence quantities are available on the outputs
(voltage and current, amplitude and angle). Each amplitude output has a corresponding
supervision level output (X_RANGE). The output signal is an integer in the interval 0-4, see
section "Measurement supervision".

18.1.8 Technical data


M12386-1 v16

Table 816: Power system measurement CVMMXN technical data


Function Range or value Accuracy
Frequency (0.95-1.05) x fr ±2.0 mHz

Voltage (10 to 300) V ±0.3% of U at U≤ 50 V


±0.2% of U at U> 50 V
Current (0.1-4.0) x Ir ±0.8% of I at 0.1 x Ir< I < 0.2 x Ir
± 0.5% of I at 0.2 x Ir< I < 0.5 x Ir
±0.2% of I at 0.5 x Ir< I < 4.0 x Ir

Table continues on next page

998 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

Function Range or value Accuracy


Active power, P (10 to 300) V ±0.5% of Sr at S ≤0.5 x Sr
(0.1-4.0) x Ir ±0.5% of S at S > 0.5 x Sr

(100 to 220) V ±0.2% of P


(0.5-2.0) x Ir
cos φ> 0.7
Reactive power, Q (10 to 300) V ±0.5% of Sr at S ≤0.5 x Sr
(0.1-4.0) x Ir ±0.5% of S at S > 0.5 x Sr

(100 to 220) V ±0.2% of Q


(0.5-2.0) x Ir
cos φ< 0.7
Apparent power, S (10 to 300) V ±0.5% of Sr at S ≤0.5 x Sr
(0.1-4.0) x Ir ±0.5% of S at S >0.5 x Sr

(100 to 220) V ±0.2% of S


(0.5-2.0) x Ir

Power factor, cos (φ) (10 to 300) V <0.02


(0.1-4.0) x Ir

(100 to 220) V <0.01


(0.5-2.0) x Ir

GUID-5E04B3F9-E1B7-4974-9C0B-DE9CD4A2408F v6

Table 817: CMMXU technical data


Function Range or value Accuracy
Current at symmetrical load (0.1-4.0) × Ir ±0.3% of Ir at I ≤ 0.5 × Ir
±0.3% of I at I > 0.5 × Ir

Phase angle at symmetrical (0.1-4.0) × Ir ±1.0 degrees at 0.1 × Ir < I ≤ 0.5 × Ir


load ±0.5 degrees at 0.5 × Ir < I ≤ 4.0 × Ir

GUID-374C2AF0-D647-4159-8D3A-71190FE3CFE0 v5

Table 818: VMMXU technical data


Function Range or value Accuracy
Voltage (10 to 300) V ±0.5% of U at U ≤ 50 V
±0.2% of U at U > 50 V
Phase angle (10 to 300) V ±0.5 degrees at U ≤ 50 V
±0.2 degrees at U > 50 V

GUID-9B8A7FA5-9C98-4CBD-A162-7112869CF030 v5

Table 819: CMSQI technical data


Function Range or value Accuracy
Current positive sequence, I1 (0.1–4.0) × Ir ±0.3% of Ir at I ≤ 0.5 × Ir
Three phase settings ±0.3% of I at I > 0.5 × Ir

Current zero sequence, 3I0 (0.1–1.0) × Ir ±0.3% of Ir at I ≤ 0.5 × Ir


Three phase settings ±0.3% of I at I > 0.5 × Ir

Current negative sequence, I2 (0.1–1.0) × Ir ±0.3% of Ir at I ≤ 0.5 × Ir


Three phase settings ±0.3% of I at I > 0.5 × Ir

Phase angle (0.1–4.0) × Ir ±1.0 degrees at 0.1 × Ir < I ≤ 0.5 × Ir


±0.5 degrees at 0.5 × Ir < I ≤ 4.0 × Ir

Line distance protection REL670 999


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

GUID-47094054-A828-459B-BE6A-D7FA1B317DA7 v6

Table 820: VMSQItechnical data


Function Range or value Accuracy
Voltage positive sequence, U1 (10 to 300) V ±0.5% of U at U ≤ 50 V
±0.2% of U at U > 50 V
Voltage zero sequence, 3U0 (10 to 300) V ±0.5% of U at U ≤ 50 V
±0.2% of U at U > 50 V
Voltage negative sequence, U2 (10 to 300) V ±0.5% of U at U ≤ 50 V
±0.2% of U at U > 50 V
Phase angle (10 to 300) V ±0.5 degrees at U ≤ 50 V
±0.2 degrees at U > 50 V

GUID-ED634B6D-9918-464F-B6A4-51B78129B819 v6

Table 821: VNMMXU technical data


Function Range or value Accuracy
Voltage (5 to 175) V ±0.5% of U at U ≤ 50 V
±0.2% of U at U > 50 V
Phase angle (5 to 175) V ±0.5 degrees at U ≤ 50 V
±0.2 degrees at U > 50 V

18.2 Gas medium supervision SSIMG GUID-358AD8F8-AE06-4AEA-9969-46E5299D5B4B v3

18.2.1 Identification
GUID-AD96C26E-C3E5-4B21-9ED6-12E540954AC3 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Insulation gas monitoring function SSIMG - 63

18.2.2 Functionality GUID-0692CD0D-F33E-4370-AC91-B216CAAAFC28 v6

Insulation supervision for gas medium (SSIMG) is used for monitoring the circuit breaker
condition. Binary information based on the gas pressure in the circuit breaker is used as input
signals to the function. In addition, the function generates alarms based on received
information.

18.2.3 Function block


GUID-94B75A6D-973D-4F1F-8643-F2128AD31CC4 v3

SSIMG
BLOCK LOCKOUT
BLKALM PRESLO
SENPRES TEMPLO
SENTEMP ALARM
SENPRESALM PRESALM
SENPRESLO TEMPALM
SETPLO PRESSURE
SETTLO TEMP
RESETLO
IEC09000129-2-en.vsdx
IEC09000129 V2 EN-US

Figure 591: SSIMG function block

1000 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

18.2.4 Signals
GUID-89749F71-CAEB-4A57-A1F0-148CCF68E97E v2

PID-6950-INPUTSIGNALS v6

Table 822: SSIMG Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
BLKALM BOOLEAN 0 Block all the alarms
SENPRES REAL 0.0 Pressure input from CB
SENTEMP REAL 0.0 Temperature of the insulation medium from CB
SENPRESALM BOOLEAN 0 Pressure alarm signal
SENPRESLO BOOLEAN 0 Pressure lockout signal
SETPLO BOOLEAN 0 Set pressure lockout
SETTLO BOOLEAN 0 Set temperature lockout
RESETLO BOOLEAN 0 Reset pressure and temperature lockout

PID-6950-OUTPUTSIGNALS v6

Table 823: SSIMG Output signals


Name Type Description
LOCKOUT BOOLEAN Pressure below lockout level or temperature above lockout
level
PRESLO BOOLEAN Pressure below lockout level
TEMPLO BOOLEAN Temperature above lockout level
ALARM BOOLEAN Pressure below alarm level or temperature above alarm level
PRESALM BOOLEAN Pressure below alarm level
TEMPALM BOOLEAN Temperature above alarm level
PRESSURE REAL Pressure service value
TEMP REAL Temperature of the insulation medium

18.2.5 Settings
PID-6950-SETTINGS v6

Table 824: SSIMG Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
PresAlmLimit 1.00 - 100.00 - 0.01 5.00 Alarm setting for pressure
PresLOLimit 1.00 - 100.00 - 0.01 3.00 Pressure lockout setting
TempAlarmLimit -40.00 - 200.00 - 0.01 30.00 Temperature alarm level setting of the
medium
TempLOLimit -40.00 - 200.00 - 0.01 30.00 Temperature lockout level of the
medium
tPressureAlarm 0.000 - 60.000 s 0.001 0.000 Time delay for pressure alarm
tPressureLO 0.000 - 60.000 s 0.001 0.000 Time delay for pressure lockout
indication
tTempAlarm 0.000 - 60.000 s 0.001 0.000 Time delay for temperature alarm
Table continues on next page

Line distance protection REL670 1001


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

Name Values (Range) Unit Step Default Description


tTempLockOut 0.000 - 60.000 s 0.001 0.000 Time delay for temperture lockout
tResetPresAlm 0.000 - 60.000 s 0.001 0.000 Reset time delay for pressure alarm
tResetPresLO 0.000 - 60.000 s 0.001 0.000 Reset time delay for pressure lockout
tResetTempLO 0.000 - 60.000 s 0.001 0.000 Reset time delay for temperture
lockout
tResetTempAlm 0.000 - 60.000 s 0.001 0.000 Reset time delay for temperture alarm

18.2.6 Monitored data


PID-6950-MONITOREDDATA v5

Table 825: SSIMG Monitored data


Name Type Values (Range) Unit Description
PRESSURE REAL - - Pressure service value
TEMP REAL - deg Temperature of the insulation
medium

18.2.7 Operation principle GUID-359458EA-FFAA-4A44-A8E8-9469CA069C80 v7

Gas medium supervision SSIMG is used to monitor the gas pressure in the circuit breaker.
Binary inputs of gas density SENPRESALM, SENPRESLO, and gas pressure signal SENPRES, are
taken into account to initiate the alarm PRESALM and the lockout PRESLO. When SENPRES is
less than PresAlmLimit or binary signal from CB SENPRESALM is high, the gas pressure alarm
PRESALM will be initiated. Similarly, if pressure input SENPRES is less than PresLOLimit or
binary signal from CB SENPRESLO is high, PRESLO will be initiated.

There may be sudden change in pressure of the gas for a very small time, for which the
function need not to initiate any alarm. To avoid the intermittent alarm, two time delays
tPressureAlarm or tPressureLO have been included. If the pressure goes below the settings for
more than these time delays, the corresponding alarm PRESALM or lockout PRESLO will be
initiated. The SETPLO binary input is used for setting the gas pressure lockout PRESLO. The
PRESLO output retains the last value until it is reset by using the binary input RESETLO. The
binary input BLKALM can be used to block the alarms, and the BLOCK input can block both
alarm and the lockout indications.

Temperature of the medium is available from the input signal of temperature. The signal is
monitored to detect high temperature.

When temperature input SENTEMP is above TempAlarmLimit, temperature alarm TEMPALM


will be initiated. Similarly, if temperature input SENTEMP is above TempLOLimit, temperature
lockout TEMPLO will be initiated.

There may be sudden change in temperature of the medium for a very small time, for which the
function need not to initiate any alarm. To avoid the intermittent alarm, two time delays
tTempAlarm or tTempLockOut have been included. If the temperature goes above the settings
for more than these time delays, the corresponding alarm TEMPALM or lockout TEMPLO will be
initiated. The SETTLO binary input is used for setting the temperature lockout TEMPLO. The
TEMPLO output retains the last value until it is reset by using the binary input RESETLO. The
binary input BLKALM can be used to block the alarms, and the BLOCK input can block both
alarm and the lockout indications.

The output ALARM goes high if the pressure alarm condition or the temperature alarm
condition exists inside the circuit breaker. The output ALARM can be blocked by activating
BLOCK or BLKALM inputs.

1002 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

The output LOCKOUT goes high if the pressure lockout condition or the temperature lockout
condition exists inside the circuit breaker and it resets by using the binary input RESETLO. The
output LOCKOUT can be blocked by activating BLOCK input.

18.2.8 Technical data


GUID-F034B396-6600-49EF-B0A5-8ED96766A6A0 v8

Table 826: SSIMG Technical data


Function Range or value Accuracy
Pressure alarm level 1.00-100.00 ±10.0% of set value
Pressure lockout level 1.00-100.00 ±10.0% of set value
Temperature alarm level -40.00-200.00 ±2.5% of set value
Temperature lockout level -40.00-200.00 ±2.5% of set value
Time delay for pressure alarm (0.000-60.000) s ±0.2% or ±250ms whichever is
greater
Reset time delay for pressure (0.000-60.000) s ±0.2% or ±250ms whichever is
alarm greater
Time delay for pressure lockout (0.000-60.000) s ±0.2% or ±250ms whichever is
greater
Time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is
greater
Reset time delay for temperature (0.000-60.000) s ±0.2% or ±250ms whichever is
alarm greater
Time delay for temperature (0.000-60.000) s ±0.2% or ±250ms whichever is
lockout greater

18.3 Liquid medium supervision SSIML GUID-37669E94-4830-4C96-8A67-09600F847F23 v3

18.3.1 Identification
GUID-4CE96EF6-42C6-4F2E-A190-D288ABF766F6 v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Insulation liquid monitoring function SSIML - 71

18.3.2 Functionality GUID-3B1A665F-60A5-4343-85F4-AD9C066CBE8D v7

Insulation supervision for liquid medium (SSIML) is used for monitoring the oil insulated device
condition. For example, transformers, shunt reactors, and so on. Binary information based on
the oil level in the oil insulated devices are used as input signals to the function. In addition,
the function generates alarms based on the received information.

Line distance protection REL670 1003


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

18.3.3 Function block GUID-AC82A86C-495D-4CBD-9BF9-3CC760591AA9 v3

SSIML
BLOCK LOCKOUT
BLKALM LVLLO
SENLEVEL TEMPLO
SENTEMP ALARM
SENLVLALM LVLALM
SENLVLLO TEMPALM
SETLLO LEVEL
SETTLO TEMP
RESETLO
IEC09000128-2-en.vsdx
IEC09000128 V2 EN-US

Figure 592: SSIML function block

18.3.4 Signals
GUID-0C378BB3-2104-417F-94B5-16EFC55151FE v2

PID-6951-INPUTSIGNALS v7

Table 827: SSIML Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
BLKALM BOOLEAN 0 Block all the alarms
SENLEVEL REAL 0.0 Level input from CB
SENTEMP REAL 0.0 Temperature of the insulation medium from CB
SENLVLALM BOOLEAN 0 Level alarm signal
SENLVLLO BOOLEAN 0 Level lockout signal
SETLLO BOOLEAN 0 Set level lockout
SETTLO BOOLEAN 0 Set temperature lockout
RESETLO BOOLEAN 0 Reset level and temperature lockout

PID-6951-OUTPUTSIGNALS v7

Table 828: SSIML Output signals


Name Type Description
LOCKOUT BOOLEAN Level below lockout level or temperature above lockout level
LVLLO BOOLEAN Level below lockout level
TEMPLO BOOLEAN Temperature above lockout level
ALARM BOOLEAN Level below alarm level or temperature above alarm level
LVLALM BOOLEAN Level below alarm level
TEMPALM BOOLEAN Temperature above alarm level
LEVEL REAL Level service value
TEMP REAL Temperature of the insulation medium

1004 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

18.3.5 Settings
PID-6951-SETTINGS v7

Table 829: SSIML Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
LevelAlmLimit 1.00 - 100.00 - 0.01 5.00 Alarm setting for level
LevelLOLimit 1.00 - 100.00 - 0.01 3.00 Level lockout setting
TempAlarmLimit -40.00 - 200.00 - 0.01 30.00 Temperature alarm level setting of the
medium
TempLOLimit -40.00 - 200.00 - 0.01 30.00 Temperature lockout level of the
medium
tLevelAlarm 0.000 - 60.000 s 0.001 0.000 Time delay for level alarm
tLevelLockOut 0.000 - 60.000 s 0.001 0.000 Time delay for level lockout indication
tTempAlarm 0.000 - 60.000 s 0.001 0.000 Time delay for temperature alarm
tTempLockOut 0.000 - 60.000 s 0.001 0.000 Time delay for temperture lockout
tResetLevelAlm 0.000 - 60.000 s 0.001 0.000 Reset time delay for level alarm
tResetLevelLO 0.000 - 60.000 s 0.001 0.000 Reset time delay for level lockout
tResetTempLO 0.000 - 60.000 s 0.001 0.000 Reset time delay for temperture
lockout
tResetTempAlm 0.000 - 60.000 s 0.001 0.000 Reset time delay for temperture alarm

18.3.6 Monitored data


PID-6951-MONITOREDDATA v5

Table 830: SSIML Monitored data


Name Type Values (Range) Unit Description
LEVEL REAL - - Level service value
TEMP REAL - deg Temperature of the insulation
medium

18.3.7 Operation principle GUID-F4340B59-90D0-4EA7-9FD8-F21D425C884A v8

Liquid medium supervision SSIML is used to monitor the oil level in the oil insulated devices.
Binary inputs of oil level SENLVLALM, SENLVLLO and oil level signal SENLEVEL are taken into
account to initiate the alarm LVLALM and the lockout LVLLO. When SENLEVEL is less than
LevelAlmLimit or binary signal from oil insulated device SENLVLALM is high, the oil level
indication alarm LVLALM will be initiated. Similarly, if oil level input SENLEVEL is less than
LevelLOLimit or binary signal from oil insulated device SENLVLLO is high, the oil level
indication lockout LVLLO will be initiated.

There may be sudden change in oil level for a very small time, for which the function need not
to initiate any alarm. To avoid the intermittent alarm, two time delays tLevelAlarm or
tLevelLockOut have been included. If the oil level goes below the settings for more than these
time delays, the corresponding alarm LVLALM or lockout LVLLO will be initiated. The SETLLO
binary input is used for setting the liquid level lockout LVLLO. The LVLLO output retains the
last value until it is reset by using the binary input RESETLO. The binary input BLKALM can be
used for blocking the alarms, and the BLOCK input can block both alarms and the lockout
indication.

Line distance protection REL670 1005


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

Temperature of the medium is available from the input signal of temperature. The signal is
monitored to detect high temperature.

When temperature input SENTEMP is above TempAlarmLimit, temperature alarm TEMPALM


will be initiated. Similarly, if temperature input SENTEMP is above TempLOLimit, temperature
lockout TEMPLO will be initiated.

There may be sudden change in temperature of the medium for a very small time, for which the
function need not to initiate any alarm. To avoid the intermittent alarm, two time delays
tTempAlarm or tTempLockOuthave been included. If the temperature goes above the settings
for more than these time delays, the corresponding alarm TEMPALM or lockout TEMPLO will be
initiated. The SETTLO binary input is used for setting the temperature lockout TEMPLO. The
TEMPLO output retains the last value until it is reset by using the binary input RESETLO. The
binary input BLKALM can be used for blocking the alarms, and the BLOCK input can block both
alarm and the lockout indications.

The output ALARM goes high if the level alarm condition or the temperature alarm condition
exists in the oil insulated devices. The output ALARM can be blocked by activating BLOCK or
BLKALM inputs.

The output LOCKOUT goes high if the pressure lockout condition or the temperature lockout
condition exists in the oil insulated devices and it resets by using the binary input RESETLO.
The output LOCKOUT can be blocked by activating BLOCK input.

18.3.8 Technical data


GUID-83B0F607-D898-403A-94FD-7FE8D45C73FF v8

Table 831: SSIMLTechnical data


Function Range or value Accuracy
Oil alarm level 1.00-100.00 ±10.0% of set value
Oil lockout level 1.00-100.00 ±10.0% of set value
Temperature alarm level -40.00-200.00 ±2.5% of set value
Temperature lockout level -40.00-200.00 ±2.5% of set value
Time delay for oil alarm (0.000-60.000) s ±0.2% or ±250ms whichever is
greater
Reset time delay for oil alarm (0.000-60.000) s ±0.2% or ±250ms whichever is
greater
Time delay for oil lockout (0.000-60.000) s ±0.2% or ±250ms whichever is
greater
Time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is
greater
Reset time delay for temperature (0.000-60.000) s ±0.2% or ±250ms whichever is
alarm greater
Time delay for temperature (0.000-60.000) s ±0.2% or ±250ms whichever is
lockout greater

18.4 Breaker monitoring SSCBR

18.4.1 Identification GUID-0FC081B2-0BC8-4EB8-9529-B941E51F18EE v7

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Breaker monitoring SSCBR - -

1006 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

18.4.2 Functionality GUID-E1FD74C3-B9B6-4E11-AA1B-7E7F822FB4DD v13

The circuit breaker condition monitoring function (SSCBR) is used to monitor different
parameters of the breaker condition. The breaker requires maintenance when the number of
operations reaches a predefined value. For a proper functioning of the circuit breaker, it is
essential to monitor the circuit breaker operation, spring charge indication or breaker wear,
travel time, number of operation cycles and estimate the accumulated energy during arcing
periods.

18.4.3 Function block GUID-B002ED61-5092-4E9E-AEB6-E4A4310BDAF2 v11

SSCBR
I3P* OPENPOS
BLOCK CLOSEPOS
BLKALM INVDPOS
TRIND TRCMD
POSOPEN TRVTOPAL
POSCLOSE TRVTCLAL
PRESALM OPERALM
PRESLO OPERLO
SPRCHRST CBLIFEAL
SPRCHRD MONALM
RSTCBWR IPOWALPH
RSTTRVT IPOWLOPH
RSTIPOW SPCHALM
RSTSPCHT GPRESALM
GPRESLO

IEC13000231-2-en.vsd
IEC13000231 V2 EN-US

Figure 593: SSCBR function block

18.4.4 Signals
PID-3267-INPUTSIGNALS v10

Table 832: SSCBR Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
BLOCK BOOLEAN 0 Block all the alarm and lockout indication
BLKALM BOOLEAN 0 Block all the alarms
TRIND BOOLEAN 0 Trip command from trip circuit
POSOPEN BOOLEAN 0 Signal for open position of apparatus from I/O
POSCLOSE BOOLEAN 0 Signal for close position of apparatus from I/O
PRESALM BOOLEAN 0 Pressure alarm indication from CB
PRESLO BOOLEAN 0 Pressure lockout indication from CB
SPRCHRST BOOLEAN 0 CB spring charging started indication signal
SPRCHRD BOOLEAN 0 CB spring charged indication signal
RSTCBWR BOOLEAN 0 Reset of CB remaining life and operation counter
RSTTRVT BOOLEAN 0 Reset of CB closing and opening travel times
RSTIPOW BOOLEAN 0 Reset of accumulated I^CurrExponent
RSTSPCHT BOOLEAN 0 Reset of CB spring charging time

Line distance protection REL670 1007


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

PID-3267-OUTPUTSIGNALS v10

Table 833: SSCBR Output signals


Name Type Description
OPENPOS BOOLEAN CB is in open position
CLOSEPOS BOOLEAN CB is in closed position
INVDPOS BOOLEAN CB is in Invalid Position
TRCMD BOOLEAN Open command issued to CB
TRVTOPAL BOOLEAN CB open travel time exceeded set value
TRVTCLAL BOOLEAN CB close travel time exceeded set value
OPERALM BOOLEAN Number of CB operations exceeds alarm limit
OPERLO BOOLEAN Number of CB operations exceeds lockout limit
CBLIFEAL BOOLEAN Remaining life of CB reduced to Life alarm level
MONALM BOOLEAN CB 'not operated for long time' alarm
IPOWALPH BOOLEAN Accum I^CurrExponent integr over CB open travel time
exceeds alarm limit
IPOWLOPH BOOLEAN Accum I^CurrExponent integr over CB open travel time
exceeds lockout limit
SPCHALM BOOLEAN Spring charging time has crossed the set value
GPRESALM BOOLEAN Pressure below alarm level
GPRESLO BOOLEAN Pressure below lockout level

18.4.5 Settings
PID-3267-SETTINGS v10

Table 834: SSCBR Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups
PhSel Phase L1 - - Phase L1 Phase selection
Phase L2
Phase L3
RatedOperCurr 100.00 - 5000.00 A 0.01 1000.00 Rated operating current of the
breaker
OperNoRated 1 - 99999 - 1 10000 Number of operations possible at
rated current
RatedFltCurr 500.00 - 99999.99 A 0.01 5000.00 Rated fault current of the breaker
OperNoFault 1 - 10000 - 1 1000 Number of operations possible at
rated fault current
tTrOpenAlm 0.000 - 0.200 s 0.001 0.040 Alarm level for open travel time
tTrCloseAlm 0.000 - 0.200 s 0.001 0.040 Alarm level for close travel time
OperAlmLevel 0 - 9999 - 1 200 Alarm level for number of operations
OperLOLevel 0 - 9999 - 1 300 Lockout level for number of
operations
AccSelCal Aux Contact - - Trip Signal Accumulated energy calculation
Trip Signal selection
Table continues on next page

1008 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

Name Values (Range) Unit Step Default Description


CurrExponent 0.50 - 3.00 - 0.01 2.00 Current exponent value used for
energy calculation
AccStopCurr 5.00 - 100.00 %IB 0.01 10.00 RMS current level below which energy
accumulation stops
AlmAccCurrPwr 0.00 - 20000.00 - 0.01 2500.00 Alarm level for accumulated
I^CurrExponent integrated over CB
open travel time
LOAccCurrPwr 0.00 - 20000.00 - 0.01 2500.00 Lockout level for accumulated
I^CurrExponent integrated over CB
open travel time
SpChAlmTime 0.00 - 60.00 s 0.01 1.00 Alarm level for spring charging time
InitCBRemLife 1 - 99999 - 1 10000 Initial value for remaining life
estimates
InactiveAlDays 0 - 9999 Day 1 2000 Alarm level for inactive days counter

Table 835: SSCBR Non group settings (advanced)


Name Values (Range) Unit Step Default Description
OpenTimeCorr -0.100 - 0.100 s 0.001 0.010 Correction for open travel time
CloseTimeCorr -0.100 - 0.100 s 0.001 0.010 Correction for close travel time
DirCoef -3.00 - -0.50 - 0.01 -1.50 Directional coefficient for CB life
calculation
CBLifeAlmLevel 1 - 99999 - 1 5000 Alarm level for CB remaining life
ContTrCorr -0.010 - 0.010 s 0.001 0.005 Correction for time difference in
auxiliary and main contacts open time
OperTimeDelay 0.000 - 0.200 s 0.001 0.020 Time delay between change of status
of trip output and start of main
contact separation
tDGasPresAlm 0.00 - 60.00 s 0.01 0.10 Time delay for gas pressure alarm
tDGasPresLO 0.00 - 60.00 s 0.01 0.10 Time delay for gas pressure lockout
InitCounterVal 0 - 9999 - 1 0 Initial value for number of operations
InitAccCurrPwr 0.00 - 9999.99 - 0.01 0.00 Initial value for accum I^CurrExponent
integr over CB open travel time value
InitInactDays 0 - 9999 Day 1 0 Initial value for inactive days
InactiveAlHrs 0 - 23 Hour 1 0 Alarm time for inactive days counter in
hours

18.4.6 Monitored data


PID-3267-MONITOREDDATA v7

Table 836: SSCBR Monitored data


Name Type Values (Range) Unit Description
TTRVOP REAL - ms Travel time of the CB during opening
operation
TTRVCL REAL - ms Travel time of the CB during closing
operation
NOOPER INTEGER - - Number of CB operation cycle
CBLIFEPH INTEGER - - CB Remaining life of respective phase
Table continues on next page

Line distance protection REL670 1009


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

Name Type Values (Range) Unit Description


INADAYS INTEGER - - The number of days CB has been
inactive
IPOWPH REAL - - Accumulated I^CurrExponent
integrated over CB open travel time
SPCHT REAL - s The charging time of the CB spring

18.4.7 Operation principle GUID-3902D69C-1858-40DD-AD63-C33C381697BA v12

The breaker monitoring function includes metering and monitoring subfunctions. The
subfunctions can be enabled and disabled with the Operation setting. The corresponding
parameter values are On and Off.

The operation of the subfunctions is described by the module diagram as shown in figure 594.
All the modules in the diagram are explained in subsequent sections.

1010 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

I3P-ILRMSPH
POSCLOSE TTRVOP
POSOPEN CB Contact Travel TTRVCL
BLOCK Time TRVTOPAL
BLKALM TRVTCLAL
RSTTRVT

OPENPOS

CB Status CLOSEPOS
INVDPOS

CBLIFEAL
Remaining Life of CB
CBLIFEPH
RSTCBWR

TRCMD

Accumulated IPOWALPH
energy
I3P-IL IPOWLOPH
TRIND
IPOWPH
RSTIPOW

CB Operation OPERALM
Cycles NOOPER

CB Operation MONALM
Monitoring INADAYS

SPCHALM
SPRCHRST CB Spring Charge SPCHT
SPRCHRD Monitoring
RSTSPCHT

CB Gas Pressure GPRESALM


PRESALM Indication GPRESLO
PRESLO
IEC12000624-3-en.vsd
IEC12000624 V3 EN-US

Figure 594: Functional module diagram of breaker monitoring

Line distance protection REL670 1011


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

18.4.7.1 Circuit breaker contact travel time GUID-3AF0EE8D-AA8E-4F83-9916-61B5D0D6B05B v13

The circuit breaker contact travel time sub function calculates the breaker contact travel time
for opening and closing operations. The operation of the breaker contact travel time
measurement is described in figure595.

POSCLOSE TTRVOP
Contact travel
POSOPEN time TTRVCL
calculation
RSTTRVT

TRVTOPAL
Alarm limit
BLOCK check TRVTCLAL
BLKALM
IEC12000615-2-en.vsd
IEC12000615 V2 EN-US

Figure 595: Functional module diagram for circuit breaker contact travel time

Contact travel time calculation


The contact travel time of the breaker is calculated from the time between the state of change
of auxiliary contacts. The opening travel time is measured between the opening of the
POSCLOSE and closing of the POSOPEN auxiliary contacts. Similarly, the closing travel time is
measured between the opening of the POSOPEN and closing of the POSCLOSE auxiliary
contacts. A compensation factor has been added to consider the time difference between
auxiliary contact operation and the actual physical opening of the breaker main contact.

Main Contact
1

0
POSCLOSE

POSOPEN
1

t1 tOpen t2 t3 tClose t4

tTravelOpen = tOpen + t1 + t2 tTravelClose = tClose + t3 + t4


IEC12000616_2_en.vsd

IEC12000616 V2 EN-US

Figure 596: Travel time calculation


There is a time difference t1 between the start of the main contact opening and the opening of
the POSCLOSE auxiliary contact. Similarly, there is a time difference t2 between the time when
the POSOPEN auxiliary contact opens and the main contact is completely open. Therefore, a
correction factor needs to be added to get the actual opening time. This factor is added with
the OpenTimeCorr (t1+t2) setting. The closing time is calculated by adding the value set with
the CloseTimeCorr (t3+t4) setting to the measured closing time.

The last measured opening travel time (TTRVOP) and the closing travel time (TTRVCL) are given
as service values.

The values can be reset using the Clear menu on the LHMI or by activation the input RSTCBWR.

1012 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

Alarm limit check


When the measured opening travel time is longer than the value set in the tTrOpenAlm setting,
the TRVTOPAL output is activated. Similarly, when the measured closing travel time is longer
than the value set in the tTrCloseAlm setting, the TRVTCLAL output is activated.

It is also possible to block the TRVTCLAL and TRVTOPAL alarm signals by activating the BLKALM
input.

18.4.7.2 Circuit breaker status GUID-390A1250-B258-4023-9A7D-0D7E19E13A6C v12

The circuit breaker status subfunction monitors the position of the circuit breaker, that is,
whether the breaker is in the open, closed or error position. The operation is described in
figure 597.

Phase current
I3P-ILRMSPH
check

OPENPOS
Contact
POSCLOSE position CLOSEPOS
indicator
POSOPEN INVDPOS

IEC12000613-3-en.vsd
IEC12000613 V3 EN-US

Figure 597: Functional module diagram for monitoring circuit breaker status

Phase current check


The module compares the phase current I3P-ILRMSPH to the AccStopCurr setting. If the
current in the selected phase exceeds the set level, it is reported to the contact position
indicator module as closed circuit breaker.

Contact position indicator


The circuit breaker status is open when the auxiliary input contact POSCLOSE is low, the
POSOPEN input is high and the phase current is less than the setting AccStopCurr value. The
circuit breaker is closed when the POSOPEN input is low and the POSCLOSE input is high. The
breaker is in the error state if both auxiliary contacts have the same value or if the auxiliary
input contact POSCLOSE is low and the POSOPEN input is high but the current is above the
setting AccStopCurr.

The status of the breaker is indicated with the binary outputs OPENPOS, CLOSEPOS and
INVDPOS for open, closed and error position respectively.

18.4.7.3 Remaining life of circuit breaker GUID-C347406A-2B6F-42BD-B70B-51489AB51EAE v13

The Remaining life of circuit breaker subfunction is used to give an indication on the wear and
tear of the circuit breaker. Every time the breaker operates, the life of the circuit breaker
reduces due to wear. The breaker wear depends on the interrupted current. The remaining life
of the breaker is estimated from the circuit breaker trip curve provided by the manufacturer.
The remaining life is decreased by at least one when the circuit breaker is opened. The
operation of the remaining life of circuit breaker subfunction is described in figure 598.

Line distance protection REL670 1013


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

I3P-ILRMSPH
CB remaining CBLIFEPH
POSCLOSE life estimation

RSTCBWR

Alarm limit
BLOCK CBLIFEAL
Check
BLKALM

IEC12000620-3-en.vsd
IEC12000620 V3 EN-US

Figure 598: Functional module diagram for estimating the life of the circuit breaker

Circuit breaker remaining life estimation


If the interrupted current is less than the rated operating current set using the RatedOperCurr
setting, the remaining operations of the breaker are reduced by one operation. If the
interrupted current is more than the rated fault current set using the RatedFltCurr setting, the
remaining operations of the circuit breaker are reduced by the set OperNoRated divided by the
set OperNoFault value. If the tripping current is between these two values, the remaining life
of the circuit breaker is calculated based on the maintenance curve equation given by the
manufacturer. The OperNoRated parameter sets the number of operations the breaker can
perform at the rated current. The OperNoFault parameter sets the number of operations the
breaker can perform at the rated fault current.

Alarm limit check


When the remaining life of a circuit breaker phase drops below the CBLifeAlmLevel setting, the
life alarm CBLIFEAL is activated.

It is possible to deactivate the CBLIFEAL alarm signal by activating the binary input BLKALM.

The old circuit breaker operation counter value can be used by adding the value to the
InitCBRemLife parameter. The value can be reset using the Clear menu from LHMI or by
activating the input RSTCBWR.

18.4.7.4 Accumulated energy GUID-0163FF0F-6E18-4CDC-87AA-578304E0872E v12

The Accumulated energy subfunction calculates the accumulated energy (Iyt) based on current
samples, where the setting CurrExponent (y) ranges from 0.5 to 3.0. The operation is
described in figure 599.

The TRCMD output is enabled when either of the trip indications from the trip coil circuit TRIND
is high or the breaker status is OPENPOS.

I3P-IL
TRCMD
I3P-ILRMSPH Accumulated
POSCLOSE energy
calculation IPOWPH
TRIND

LRSTIPOW

IPOWALPH
Alarm limit
BLOCK Check IPOWLOPH
BLKALM

IEC12000619-3-en.vsd
IEC12000619 V3 EN-US

Figure 599: Functional module diagram for estimating accumulated energy

1014 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

Accumulated energy calculation


Accumulated energy can be calculated either with TRIND or POSCLOSE by selecting the
AccSelCal parameter value accordingly.

The calculation is initiated with the POSCLOSE or TRIND input events. It ends when the RMS
current is lower than the AccStopCurr setting.

The ContTrCorr setting is used to determine the accumulated energy in relation to the time
the main contact opens. If the setting is positive, the calculation of energy starts after the
auxiliary contact has opened and the delay equal to the value of the ContTrCorr setting has
passed. When the setting is negative, the calculation starts in advance by the correction time
in relation to when the auxiliary contact opened.

Main Contact Main Contact


close close

open open
POSCLOSE 1 POSCLOSE 1

0 0

Energy Energy
Accumulation Accumulation
starts starts

ContTrCorr ContTrCorr
(Negative) (Positive)
IEC12000618_1_en.vsd
IEC12000618 V1 EN-US

Figure 600: Significance of correction factor setting


Accumulated energy can also be calculated by using the change of state of the trip output.
TRIND is used to get the instance of the trip output and the time delay between the trip
initiation and the opening of the main contact is introduced by the setting OperTimeDelay.

The accumulated energy output IPOWPH is provided as a service value. The value can be reset
by enabling RSTIPOW through LHMI or by activating the input RSTIPOW.

Alarm limit check


The IPOWALPH alarm is activated when the accumulated energy exceeds the set value
AlmAccCurrPwr.

IPOWLOPH is activated when the accumulated energy exceeds the limit of the LOAccCurrPwr
setting.

The IPOWALPH and IPOWLOPH outputs can be blocked by activating the binary input BLKALM.

18.4.7.5 Circuit breaker operation cycles GUID-D3481D26-2E42-455E-8DB2-91538421F3B1 v10

The circuit breaker operation cycles subfunction counts the number of closing-opening
sequences of the breaker. The operation counter value is updated after each closing-opening
sequence. The operation is described in figure601.

Line distance protection REL670 1015


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

POSCLOSE
Operation
POSOPEN NOOPER
counter
RSTCBWR

OPERALM
Alarm limit
BLOCK
Check
OPERLO
BLKALM
IEC12000617 V2 EN-US

Figure 601: Functional module diagram for circuit breaker operation cycles

Operation counter
The operation counter counts the number of operations based on the state of change of the
auxiliary contact inputs POSCLOSE and POSOPEN.

The number of operations NOOPER is given as a service value. The old circuit breaker
operation counter value can be used by adding the value to the InitCounterVal parameter and
can be reset by Clear CB wear in the Clear menu on the LHMI or activating the input RSTCBWR.

Alarm limit check


OPERALM is generated when the number of operations exceeds the set value of the
OperAlmLevel threshold setting.

If the number of operations increases and exceeds the limit value set with the OperLOLevel
setting, the OPERLO output is activated.

The binary outputs OPERALM and OPERALO are deactivated when the BLKALM input is activated.

18.4.7.6 Circuit breaker operation monitoring GUID-6DAE4C6B-BD66-49CD-817D-08E4EBF47DE0 v9

The circuit breaker operation monitoring subfunction indicates the inactive days of the circuit
breaker and gives an alarm when the number of days exceed the set level. The operation of the
circuit breaker operation monitoring is shown in figure 602.

POSCLOSE
Inactive timer INADAYS
POSOPEN

Alarm limit MONALM


BLOCK
Check
BLKALM
IEC12000614 V2 EN-US

Figure 602: Functional module diagram for circuit breaker operation monitoring

Inactive timer
The Inactive timer module calculates the number of days the circuit breaker has remained in
the same open or closed state. The value is calculated by monitoring the states of the POSOPEN
and POSCLOSE auxiliary contacts.

The number of inactive days INADAYS is available as a service value. The initial number of
inactive days is set using the InitInactDays parameter.

1016 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

Alarm limit check


MONALM is initiated when the number of inactive days and hours exceed the limit value defined
by the InactiveAlDays and InactivAlHrs setting. The alarm signal MONALM can be blocked by
activating the binary input BLKALM.

18.4.7.7 Circuit breaker spring charge monitoring GUID-F850A940-7890-4C37-8B31-6C7D5B30E582 v12

The circuit breaker spring charge monitoring subfunction calculates the spring charging time.
The operation is described in figure 603.

SPRCHRST
Spring charging
SPRCHRD time SPCHT
measurement
RSTSPCHT

Alarm limit
BLOCK SPCHALM
Check
BLKALM
IEC12000621 V2 EN-US

Figure 603: Functional module diagram for circuit breaker spring charge indication

Spring charging time measurement


Spring charging time calculation will be initiated as soon as the circuit breaker is closed and
charging motor starts (NO contact of the device is connected to SPRCHRST) to store the energy
in the close spring. An indicator provided in the circuit breaker is displayed when the spring is
completely charged. This status is taken through NO contact and then connected to SPRCHRD.

The binary input SPRCHRST indicates the start of circuit breaker spring charging time.
SPRCHRD indicates that the circuit breaker spring is charged. The spring charging time is
calculated from the difference of these two signal timings. Spring charging indication is
described in figure 603.

The last measured spring charging time SPCHT is provided as a service value. The spring
charging time SPCHT can be reset on the LHMI or by activating the input RSTSPCHT.

Alarm limit check


If the time taken by the spring to charge is more than the value set with the SpChAlmTime
setting, the subfunction generates the SPCHALM alarm.

It is possible to block the SPCHALM alarm signal by activating the BLKALM binary input.

18.4.7.8 Circuit breaker gas pressure indication GUID-9D070D52-B499-4D45-9195-60181819184E v10

The circuit breaker gas pressure indication subfunction monitors the gas pressure inside the
arc chamber. The operation is described in figure 604.

Line distance protection REL670 1017


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

PRESALM
tDGasPresAlm
BLOCK AND t GPRESALM

BLKALM

tDGasPresLO
PRESLO AND t GPRESLO
IEC12000622 V3 EN-US

Figure 604: Functional module diagram for circuit breaker gas pressure indication
When the PRESALM binary input is activated, the GPRESALM output is activated after a time
delay set with the tDGasPresAlm setting. The GPRESALM alarm can be blocked by activating the
BLKALM input.

If the pressure drops further to a very low level, the PRESLO binary input goes high, activating
the lockout alarm GPRESLO after a time delay set with the tDGasPresLO setting. The GPRESLO
alarm can be blocked by activating the BLKALM input.

The binary input BLOCK can be used to block the function. The activation of the BLOCK input
deactivates all outputs and resets internal timers. The alarm signals from the function can be
blocked by activating the binary input BLKALM.

18.4.8 Technical data


GUID-B6799420-D726-460E-B02F-C7D4F1937432 v9

Table 837: SSCBR Technical data


Function Range or value Accuracy
Alarm level for open and close (0 – 200) ms ±3 ms
travel time
Alarm level for number of (0 – 9999) -
operations
Independent time delay for spring (0.00 – 60.00) s ±0.2% or ±30 ms whichever is
charging time alarm greater
Independent time delay for gas (0.00 – 60.00) s ±0.2% or ±30 ms whichever is
pressure alarm greater
Independent time delay for gas (0.00 – 60.00) s ±0.2% or ±30 ms whichever is
pressure lockout greater
CB Contact Travel Time, opening ±3 ms
and closing
Remaining Life of CB ±2 operations
Accumulated Energy ±1.0% or ±0.5 whichever is greater

18.5 Event function EVENT SEMOD120002-1 v2

18.5.1 Identification
SEMOD167950-2 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Event function EVENT -
S00946 V1 EN-US

1018 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

18.5.2 Functionality M12805-6 v11

When using a Substation Automation system with LON or SPA communication, time-tagged
events can be sent at change or cyclically from the IED to the station level. These events are
created from any available signal in the IED that is connected to the Event function (EVENT).
The EVENT function block is used for LON and SPA communication.

Analog, integer and double indication values are also transferred through the EVENT function.

18.5.3 Function block SEMOD116030-4 v2

EVENT
BLOCK
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9
^INPUT10
^INPUT11
^INPUT12
^INPUT13
^INPUT14
^INPUT15
^INPUT16

IEC05000697-2-en.vsd
IEC05000697 V2 EN-US

Figure 605: EVENT function block

18.5.4 Signals IP11335-1 v2

PID-4145-INPUTSIGNALS v6

Table 838: EVENT Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
INPUT1 GROUP 0 Input 1
SIGNAL
INPUT2 GROUP 0 Input 2
SIGNAL
INPUT3 GROUP 0 Input 3
SIGNAL
INPUT4 GROUP 0 Input 4
SIGNAL
INPUT5 GROUP 0 Input 5
SIGNAL
INPUT6 GROUP 0 Input 6
SIGNAL
INPUT7 GROUP 0 Input 7
SIGNAL
INPUT8 GROUP 0 Input 8
SIGNAL
INPUT9 GROUP 0 Input 9
SIGNAL
Table continues on next page

Line distance protection REL670 1019


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

Name Type Default Description


INPUT10 GROUP 0 Input 10
SIGNAL
INPUT11 GROUP 0 Input 11
SIGNAL
INPUT12 GROUP 0 Input 12
SIGNAL
INPUT13 GROUP 0 Input 13
SIGNAL
INPUT14 GROUP 0 Input 14
SIGNAL
INPUT15 GROUP 0 Input 15
SIGNAL
INPUT16 GROUP 0 Input 16
SIGNAL

18.5.5 Settings IP11336-1 v2

PID-4145-SETTINGS v6

Table 839: EVENT Non group settings (basic)


Name Values (Range) Unit Step Default Description
SPAChannelMask Off - - Off SPA channel mask
Channel 1-8
Channel 9-16
Channel 1-16
LONChannelMask Off - - Off LON channel mask
Channel 1-8
Channel 9-16
Channel 1-16
EventMask1 NoEvents - - AutoDetect Reporting criteria for input 1
OnSet
OnReset
OnChange
AutoDetect
EventMask2 NoEvents - - AutoDetect Reporting criteria for input 2
OnSet
OnReset
OnChange
AutoDetect
EventMask3 NoEvents - - AutoDetect Reporting criteria for input 3
OnSet
OnReset
OnChange
AutoDetect
EventMask4 NoEvents - - AutoDetect Reporting criteria for input 4
OnSet
OnReset
OnChange
AutoDetect
EventMask5 NoEvents - - AutoDetect Reporting criteria for input 5
OnSet
OnReset
OnChange
AutoDetect
Table continues on next page

1020 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

Name Values (Range) Unit Step Default Description


EventMask6 NoEvents - - AutoDetect Reporting criteria for input 6
OnSet
OnReset
OnChange
AutoDetect
EventMask7 NoEvents - - AutoDetect Reporting criteria for input 7
OnSet
OnReset
OnChange
AutoDetect
EventMask8 NoEvents - - AutoDetect Reporting criteria for input 8
OnSet
OnReset
OnChange
AutoDetect
EventMask9 NoEvents - - AutoDetect Reporting criteria for input 9
OnSet
OnReset
OnChange
AutoDetect
EventMask10 NoEvents - - AutoDetect Reporting criteria for input 10
OnSet
OnReset
OnChange
AutoDetect
EventMask11 NoEvents - - AutoDetect Reporting criteria for input 11
OnSet
OnReset
OnChange
AutoDetect
EventMask12 NoEvents - - AutoDetect Reporting criteria for input 12
OnSet
OnReset
OnChange
AutoDetect
EventMask13 NoEvents - - AutoDetect Reporting criteria for input 13
OnSet
OnReset
OnChange
AutoDetect
EventMask14 NoEvents - - AutoDetect Reporting criteria for input 14
OnSet
OnReset
OnChange
AutoDetect
EventMask15 NoEvents - - AutoDetect Reporting criteria for input 15
OnSet
OnReset
OnChange
AutoDetect
EventMask16 NoEvents - - AutoDetect Reporting criteria for input 16
OnSet
OnReset
OnChange
AutoDetect
MinRepIntVal1 0 - 3600 s 1 2 Minimum reporting interval input 1
MinRepIntVal2 0 - 3600 s 1 2 Minimum reporting interval input 2
MinRepIntVal3 0 - 3600 s 1 2 Minimum reporting interval input 3
MinRepIntVal4 0 - 3600 s 1 2 Minimum reporting interval input 4
Table continues on next page

Line distance protection REL670 1021


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

Name Values (Range) Unit Step Default Description


MinRepIntVal5 0 - 3600 s 1 2 Minimum reporting interval input 5
MinRepIntVal6 0 - 3600 s 1 2 Minimum reporting interval input 6
MinRepIntVal7 0 - 3600 s 1 2 Minimum reporting interval input 7
MinRepIntVal8 0 - 3600 s 1 2 Minimum reporting interval input 8
MinRepIntVal9 0 - 3600 s 1 2 Minimum reporting interval input 9
MinRepIntVal10 0 - 3600 s 1 2 Minimum reporting interval input 10
MinRepIntVal11 0 - 3600 s 1 2 Minimum reporting interval input 11
MinRepIntVal12 0 - 3600 s 1 2 Minimum reporting interval input 12
MinRepIntVal13 0 - 3600 s 1 2 Minimum reporting interval input 13
MinRepIntVal14 0 - 3600 s 1 2 Minimum reporting interval input 14
MinRepIntVal15 0 - 3600 s 1 2 Minimum reporting interval input 15
MinRepIntVal16 0 - 3600 s 1 2 Minimum reporting interval input 16

18.5.6 Operation principle M12807-6 v6

The main purpose of the Event function (EVENT) is to generate events when the state or value
of any of the connected input signals is in a state, or is undergoing a state transition, for which
event generation is enabled.

Each EVENT function has 16 inputs INPUT1 - INPUT16. Each input can be given a name from the
Application Configuration tool. The inputs are normally used to create single events, but are
also intended for double indication events. For double indications, only the first eight inputs,
1–8, must be used. Inputs 9–16 can be used for other types of events in the same EVENT block.

The EVENT function also has an input BLOCK to block the generation of events.

Events that are sent from the IED can originate from both internal logical signals and binary
input channels. The internal signals are time-tagged in the main processing module, while the
binary input channels are time-tagged directly on the input module. Time-tagging of the
events that are originated from internal logical signals have a resolution corresponding to the
execution cycle-time of the source application. Time-tagging of the events that are originated
from binary input signals have a resolution of 1 ms.

The outputs from the EVENT function are formed by the reading of status, events and alarms
by the station level on every single input. The user-defined name for each input is intended to
be used by the station level.

All events according to the event mask are stored in a buffer, which contains up to 1000
events. If new events appear before the oldest event in the buffer is read, the oldest event is
overwritten and an overflow alarm appears.

Events are produced according to set event masks. The event masks are treated commonly for
both the LON and SPA communication. An EventMask can be set individually for each input
channel. These settings are available:

• NoEvents
• OnSet
• OnReset
• OnChange
• AutoDetect

1022 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

It is possible to define which part of the EVENT function generates the events. This can be
performed individually for communication types SPAChannelMask and LONChannelMask. For
each communication type these settings are available:

• Off
• Channel 1-8
• Channel 9-16
• Channel 1-16

For LON communication, events are normally sent to station level at change. It is also possible
to set a time for cyclic sending of the events individually for each input channel.

To protect the SA system from signals with a high change rate that can easily saturate the
EVENT function or the communication subsystems behind it, a quota limiter is implemented. If
an input creates events at a rate that completely consume the granted quota then further
events from the channel will be blocked. This block will be removed when the input calms down
and the accumulated quota reach 66% of the maximum burst quota. The maximum burst
quota per input channel is 45 events per second.

18.6 Disturbance report DRPRDRE IP14584-1 v2

18.6.1 Identification
M16055-1 v9

Function description IEC 61850 identification IEC 60617 ANSI/IEEE C37.2


identification device number
Disturbance report DRPRDRE - -
Disturbance report A1RADR - A4RADR - -
Disturbance report B1RBDR - B22RBDR - -

18.6.2 Functionality M12153-3 v14

Complete and reliable information about disturbances in the primary and/or in the secondary
system together with continuous event-logging is accomplished by the disturbance report
functionality.

Disturbance report (DRPRDRE), always included in the IED, acquires sampled data of all
selected analog input and binary signals connected to the function block with a maximum of
40 analog and 352 binary signals.

The Disturbance report functionality is a common name for several functions:

• Event list
• Indications
• Event recorder
• Trip value recorder
• Disturbance recorder
• Fault locator
• Settings information

The Disturbance report function is characterized by great flexibility regarding configuration,


starting conditions, recording times, and large storage capacity.

Line distance protection REL670 1023


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

A disturbance is defined as an activation of an input to the AnRADR or BnRBDR function blocks,


which are set to trigger the disturbance recorder. All connected signals from start of pre-fault
time to the end of post-fault time will be included in the recording. Disturbance record will
have visible settings from all function instances that are configured in the application
configuration tool.

Every disturbance report recording is saved in the IED in the standard Comtrade format as a
reader file HDR, a configuration file CFG, and a data file DAT. The same applies to all events,
which are continuously saved in a ring-buffer. The local HMI is used to get information about
the recordings. The disturbance report files can be uploaded to PCM600 for further analysis
using the disturbance handling tool.

18.6.3 Function block IP806-1 v1

M12510-3 v3

DRPRDRE
DRPOFF
RECSTART
RECMADE
CLEARED
MEMUSED

IEC05000406-3-en.vsd
IEC05000406 V3 EN-US

Figure 606: DRPRDRE function block


SEMOD54843-4 v3

A4RADR
^INPUT31
^INPUT32
^INPUT33
^INPUT34
^INPUT35
^INPUT36
^INPUT37
^INPUT38
^INPUT39
^INPUT40

IEC05000431-3-en.vsd
IEC05000431 V3 EN-US

Figure 607: A4RADR function block, derived analog inputs


SEMOD54845-4 v6

B1RBDR
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9
^INPUT10
^INPUT11
^INPUT12
^INPUT13
^INPUT14
^INPUT15
^INPUT16

IEC05000432-3-en.vsd
IEC05000432 V3 EN-US

Figure 608: B1RBDR function block, binary inputs, example for B1RBDR - B22RBDR

1024 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

18.6.4 Signals
PID-3949-OUTPUTSIGNALS v2

Table 840: DRPRDRE Output signals


Name Type Description
DRPOFF BOOLEAN Disturbance report function turned off
RECSTART BOOLEAN Disturbance recording started
RECMADE BOOLEAN Disturbance recording made
CLEARED BOOLEAN All disturbances in the disturbance report cleared
MEMUSED BOOLEAN More than 80% of memory used

GUID-D025D5D9-A0F3-4A00-891A-63AD5F609A77
PID-4017-INPUTSIGNALS v6
v3

Table 841: A4RADR Input signals


Name Type Default Description
INPUT31 REAL 0 Analog channel 31
INPUT32 REAL 0 Analog channel 32
INPUT33 REAL 0 Analog channel 33
INPUT34 REAL 0 Analog channel 34
INPUT35 REAL 0 Analog channel 35
INPUT36 REAL 0 Analog channel 36
INPUT37 REAL 0 Analog channel 37
INPUT38 REAL 0 Analog channel 38
INPUT39 REAL 0 Analog channel 39
INPUT40 REAL 0 Analog channel 40

PID-3798-INPUTSIGNALS v6

Table 842: B1RBDR Input signals


Name Type Default Description
INPUT1 BOOLEAN 0 Binary channel 1
INPUT2 BOOLEAN 0 Binary channel 2
INPUT3 BOOLEAN 0 Binary channel 3
INPUT4 BOOLEAN 0 Binary channel 4
INPUT5 BOOLEAN 0 Binary channel 5
INPUT6 BOOLEAN 0 Binary channel 6
INPUT7 BOOLEAN 0 Binary channel 7
INPUT8 BOOLEAN 0 Binary channel 8
INPUT9 BOOLEAN 0 Binary channel 9
INPUT10 BOOLEAN 0 Binary channel 10
INPUT11 BOOLEAN 0 Binary channel 11
INPUT12 BOOLEAN 0 Binary channel 12
INPUT13 BOOLEAN 0 Binary channel 13
INPUT14 BOOLEAN 0 Binary channel 14
INPUT15 BOOLEAN 0 Binary channel 15
INPUT16 BOOLEAN 0 Binary channel 16

Line distance protection REL670 1025


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

GUID-D3A8067F-80F8-4174-BD2D-4C43F4B99020 v3
B2RBDR to B22RBDR functions have the same input signal specifications as B1RBDR but with
different numbering:

• B2RBDR: INPUT17 to INPUT32 (binary channels 17 to 32)


• B3RBDR: INPUT33 to INPUT48 (binary channels 33 to 48)
• B4RBDR: INPUT49 to INPUT64 (binary channels 49 to 64)
• B5RBDR: INPUT65 to INPUT80 (binary channels 65 to 80)
• B6RBDR: INPUT81 to INPUT96 (binary channels 81 to 96)
• B7RBDR: INPUT97 to INPUT112 (binary channels 97 to 112)
• B8RBDR: INPUT113 to INPUT128 (binary channels 113 to 128)
• B9RBDR: INPUT129 to INPUT144 (binary channels 129 to 144)
• B10RBDR: INPUT145 to INPUT160 (binary channels 145 to 160)
• B11RBDR: INPUT161 to INPUT176 (binary channels 161 to 176)
• B12RBDR: INPUT177 to INPUT192 (binary channels 177 to 192)
• B13RBDR: INPUT193 to INPUT208 (binary channels 193 to 208)
• B14RBDR: INPUT209 to INPUT224 (binary channels 209 to 224)
• B15RBDR: INPUT225 to INPUT240 (binary channels 225 to 240)
• B16RBDR: INPUT241 to INPUT256 (binary channels 241 to 256)
• B17RBDR: INPUT257 to INPUT272 (binary channels 257 to 272)
• B18RBDR: INPUT273 to INPUT288 (binary channels 273 to 288)
• B19RBDR: INPUT289 to INPUT304 (binary channels 289 to 304)
• B20RBDR: INPUT305 to INPUT320 (binary channels 305 to 320)
• B21RBDR: INPUT321 to INPUT336 (binary channels 321 to 336)
• B22RBDR: INPUT337 to INPUT352 (binary channels 337 to 352)

18.6.5 Settings
PID-7068-SETTINGS v1

Table 843: DRPRDRE Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
PreFaultRecT 0.05 - 9.90 s 0.01 0.10 Pre-fault recording time
PostFaultRecT 0.1 - 10.0 s 0.1 0.5 Post-fault recording time
TimeLimit 0.5 - 10.0 s 0.1 1.0 Fault recording time limit
PostRetrig Off - - Off Post-fault retrig enabled (On) or not
On (Off)
MaxNoStoreRec 10 - 100 - 1 100 Maximum number of stored
disturbances
ZeroAngleRef 1 - 30 Ch 1 1 Trip value recorder, phasor reference
channel
OpModeTest Off - - Off Operation mode during test mode
On
SetInfoInDRep Disable - - Enable Enable Disturbance report settings
Enable functionality

GUID-E05EEC82-CB90-4E73-B9C9-4C16FD95FCBF v1
A2RADR to A4RADR functions have the same Non group settings (basic) as A1RADR but with
different numbering:

• A2RADR: Operation11 to Operation20


• A3RADR: Operation21 to Operation30
• A4RADR: Operation31 to Operation40

1026 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

A2RADR to A4RADR functions have the same Non group settings (advanced) as A1RADR but
with different numbering (examples given in brackets):

• A2RADR: 11 to 20 (NomValue11, nominal value for analog channel 11)


• A3RADR: 21 to 30 (NomValue21, nominal value for analog channel 21)
• A4RADR: 31 to 40 (NomValue31, nominal value for analog channel 31)

PID-3798-SETTINGS v6

Table 844: B1RBDR Non group settings (basic)


Name Values (Range) Unit Step Default Description
TrigDR01 Off - - Off Trigger operation On/Off
On
SetLED01 Off - - Off Set LED on HMI for binary channel 1
Start
Trip
Start and Trip
TrigDR02 Off - - Off Trigger operation On/Off
On
SetLED02 Off - - Off Set LED on HMI for binary channel 2
Start
Trip
Start and Trip
TrigDR03 Off - - Off Trigger operation On/Off
On
SetLED03 Off - - Off Set LED on HMI for binary channel 3
Start
Trip
Start and Trip
TrigDR04 Off - - Off Trigger operation On/Off
On
SetLED04 Off - - Off Set LED on HMI for binary channel 4
Start
Trip
Start and Trip
TrigDR05 Off - - Off Trigger operation On/Off
On
SetLED05 Off - - Off Set LED on HMI for binary channel 5
Start
Trip
Start and Trip
TrigDR06 Off - - Off Trigger operation On/Off
On
SetLED06 Off - - Off Set LED on HMI for binary channel 6
Start
Trip
Start and Trip
TrigDR07 Off - - Off Trigger operation On/Off
On
SetLED07 Off - - Off Set LED on HMI for binary channel 7
Start
Trip
Start and Trip
TrigDR08 Off - - Off Trigger operation On/Off
On
SetLED08 Off - - Off Set LED on HMI for binary channel 8
Start
Trip
Start and Trip
Table continues on next page

Line distance protection REL670 1027


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

Name Values (Range) Unit Step Default Description


TrigDR09 Off - - Off Trigger operation On/Off
On
SetLED09 Off - - Off Set LED on HMI for binary channel 9
Start
Trip
Start and Trip
TrigDR10 Off - - Off Trigger operation On/Off
On
SetLED10 Off - - Off Set LED on HMI for binary channel 10
Start
Trip
Start and Trip
TrigDR11 Off - - Off Trigger operation On/Off
On
SetLED11 Off - - Off Set LED on HMI for binary channel 11
Start
Trip
Start and Trip
TrigDR12 Off - - Off Trigger operation On/Off
On
SetLED12 Off - - Off Set LED on HMI for binary channel 12
Start
Trip
Start and Trip
TrigDR13 Off - - Off Trigger operation On/Off
On
SetLED13 Off - - Off Set LED on HMI for binary channel 13
Start
Trip
Start and Trip
TrigDR14 Off - - Off Trigger operation On/Off
On
SetLED14 Off - - Off Set LED on HMI for binary channel 14
Start
Trip
Start and Trip
TrigDR15 Off - - Off Trigger operation On/Off
On
SetLED15 Off - - Off Set LED on HMI for binary channel 15
Start
Trip
Start and Trip
TrigDR16 Off - - Off Trigger operation On/Off
On
SetLED16 Off - - Off Set LED on HMI for binary channel 16
Start
Trip
Start and Trip
FunType1 0 - 255 - 1 0 Function type for binary channel 1 (IEC
-60870-5-103)
InfNo1 0 - 255 - 1 0 Information number for binary
channel 1 (IEC -60870-5-103)
FunType2 0 - 255 - 1 0 Function type for binary channel 2 (IEC
-60870-5-103)
InfNo2 0 - 255 - 1 0 Information number for binary
channel 2 (IEC -60870-5-103)
Table continues on next page

1028 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

Name Values (Range) Unit Step Default Description


FunType3 0 - 255 - 1 0 Function type for binary channel 3 (IEC
-60870-5-103)
InfNo3 0 - 255 - 1 0 Information number for binary
channel 3 (IEC -60870-5-103)
FunType4 0 - 255 - 1 0 Function type for binary channel 4
(IEC -60870-5-103)
InfNo4 0 - 255 - 1 0 Information number for binary
channel 4 (IEC -60870-5-103)
FunType5 0 - 255 - 1 0 Function type for binary channel 5 (IEC
-60870-5-103)
InfNo5 0 - 255 - 1 0 Information number for binary
channel 5 (IEC -60870-5-103)
FunType6 0 - 255 - 1 0 Function type for binary channel 6
(IEC -60870-5-103)
InfNo6 0 - 255 - 1 0 Information number for binary
channel 6 (IEC -60870-5-103)
FunType7 0 - 255 - 1 0 Function type for binary channel 7 (IEC
-60870-5-103)
InfNo7 0 - 255 - 1 0 Information number for binary
channel 7 (IEC -60870-5-103)
FunType8 0 - 255 - 1 0 Function type for binary channel 8
(IEC -60870-5-103)
InfNo8 0 - 255 - 1 0 Information number for binary
channel 8 (IEC -60870-5-103)
FunType9 0 - 255 - 1 0 Function type for binary channel 9
(IEC -60870-5-103)
InfNo9 0 - 255 - 1 0 Information number for binary
channel 9 (IEC -60870-5-103)
FunType10 0 - 255 - 1 0 Function type for binary channel 10
(IEC -60870-5-103)
InfNo10 0 - 255 - 1 0 Information number for binary
channel 10 (IEC -60870-5-103)
FunType11 0 - 255 - 1 0 Function type for binary channel 11
(IEC -60870-5-103)
InfNo11 0 - 255 - 1 0 Information number for binary
channel 11 (IEC -60870-5-103)
FunType12 0 - 255 - 1 0 Function type for binary channel 12
(IEC -60870-5-103)
InfNo12 0 - 255 - 1 0 Information number for binary
channel 12 (IEC -60870-5-103)
FunType13 0 - 255 - 1 0 Function type for binary channel 13
(IEC -60870-5-103)
InfNo13 0 - 255 - 1 0 Information number for binary
channel 13 (IEC -60870-5-103)
FunType14 0 - 255 - 1 0 Function type for binary channel 14
(IEC -60870-5-103)
InfNo14 0 - 255 - 1 0 Information number for binary
channel 14 (IEC -60870-5-103)
FunType15 0 - 255 - 1 0 Function type for binary channel 15
(IEC -60870-5-103)
Table continues on next page

Line distance protection REL670 1029


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

Name Values (Range) Unit Step Default Description


InfNo15 0 - 255 - 1 0 Information number for binary
channel 15 (IEC -60870-5-103)
FunType16 0 - 255 - 1 0 Function type for binary channel 16
(IEC -60870-5-103)
InfNo16 0 - 255 - 1 0 Information number for binary
channel 16 (IEC -60870-5-103)

Table 845: B1RBDR Non group settings (advanced)


Name Values (Range) Unit Step Default Description
TrigLevel01 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 1
IndicationMa01 Hide - - Show Indication mask for binary channel 1
Show
TrigLevel02 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 2
IndicationMa02 Hide - - Show Indication mask for binary channel 2
Show
TrigLevel03 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 3
IndicationMa03 Hide - - Show Indication mask for binary channel 3
Show
TrigLevel04 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 4
IndicationMa04 Hide - - Show Indication mask for binary channel 4
Show
TrigLevel05 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 5
IndicationMa05 Hide - - Show Indication mask for binary channel 5
Show
TrigLevel06 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 6
IndicationMa06 Hide - - Show Indication mask for binary channel 6
Show
TrigLevel07 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 7
IndicationMa07 Hide - - Show Indication mask for binary channel 7
Show
TrigLevel08 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 8
IndicationMa08 Hide - - Show Indication mask for binary channel 8
Show
TrigLevel09 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 9
IndicationMa09 Hide - - Show Indication mask for binary channel 9
Show
TrigLevel10 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 10
IndicationMa10 Hide - - Show Indication mask for binary channel 10
Show
TrigLevel11 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 11
Table continues on next page

1030 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

Name Values (Range) Unit Step Default Description


IndicationMa11 Hide - - Show Indication mask for binary channel 11
Show
TrigLevel12 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 12
IndicationMa12 Hide - - Show Indication mask for binary channel 12
Show
TrigLevel13 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 13
IndicationMa13 Hide - - Show Indication mask for binary channel 13
Show
TrigLevel14 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 14
IndicationMa14 Hide - - Show Indication mask for binary channel 14
Show
TrigLevel15 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 15
IndicationMa15 Hide - - Show Indication mask for binary channel 15
Show
TrigLevel16 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 16
IndicationMa16 Hide - - Show Indication mask for binary channel 16
Show

GUID-8702C5B9-05A3-4E61-8952-C66483FFDFE2 v4
B2RBDR to B22RBDR functions have the same Non group settings (basic) as B1RBDR but with
different numbering (examples given in brackets):

• B2RBDR: 17 to 32 (SetLED17, set LED on HMI for binary channel 17)


• B3RBDR: 33 to 48 (SetLED33, set LED on HMI for binary channel 33)
• B4RBDR: 49 to 64 (SetLED49, set LED on HMI for binary channel 49)
• B5RBDR: 65 to 80 (SetLED65, set LED on HMI for binary channel 65)
• B6RBDR: 81 to 96 (SetLED81, set LED on HMI for binary channel 81)
• B7RBDR: 97 to 112 (SetLED97, set LED on HMI for binary channel 97)
• B8RBDR: 113 to 128 (SetLED113, set LED on HMI for binary channel 113)
• B9RBDR: 129 to 144 (SetLED129, set LED on HMI for binary channel 129)
• B10RBDR: 145 to 160 (SetLED145, set LED on HMI for binary channel 145)
• B11RBDR: 161 to 176 (SetLED161, set LED on HMI for binary channel 161)
• B12RBDR: 177 to 192 (SetLED177, set LED on HMI for binary channel 177)
• B13RBDR: 193 to 208 (SetLED193, set LED on HMI for binary channel 193)
• B14RBDR: 209 to 224 (SetLED209, set LED on HMI for binary channel 209)
• B15RBDR: 225 to 240 (SetLED225, set LED on HMI for binary channel 225)
• B16RBDR: 241 to 256 (SetLED241, set LED on HMI for binary channel 241)
• B17RBDR: 257 to 272 (SetLED257, set LED on HMI for binary channel 257)
• B18RBDR: 273 to 288 (SetLED273, set LED on HMI for binary channel 273)
• B19RBDR: 289 to 304 (SetLED289, set LED on HMI for binary channel 289)
• B20RBDR: 305 to 320 (SetLED305, set LED on HMI for binary channel 305)
• B21RBDR: 321 to 336 (SetLED321, set LED on HMI for binary channel 321)
• B22RBDR: 337 to 352 (SetLED337, set LED on HMI for binary channel 337)

B2RBDR to B22RBDR functions have the same Non group settings (advanced) as B1RBDR but
with different numbering (examples given in brackets):

• B2RBDR: 17 to 32 (IndicationMa17, indication mask for binary channel 17)


• B3RBDR: 33 to 48 (IndicationMa33, indication mask for binary channel 33)
• B4RBDR: 49 to 64 (IndicationMa49, indication mask for binary channel 49)

Line distance protection REL670 1031


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

• B5RBDR: 65 to 80 (IndicationMa65, indication mask for binary channel 65)


• B6RBDR: 81 to 96 (IndicationMa81, indication mask for binary channel 81)
• B7RBDR: 97 to 112 (IndicationMa97, indication mask for binary channel 97)
• B8RBDR: 113 to 128 (IndicationMa113, indication mask for binary channel 113)
• B9RBDR: 129 to 144 (IndicationMa129, indication mask for binary channel 129)
• B10RBDR: 145 to 160 (IndicationMa145, indication mask for binary channel 145)
• B11RBDR: 161 to 176 (IndicationMa161, indication mask for binary channel 161)
• B12RBDR: 177 to 192 (IndicationMa177, indication mask for binary channel 177)
• B13RBDR: 193 to 208 (IndicationMa193, indication mask for binary channel 193)
• B14RBDR: 209 to 224 (IndicationMa209, indication mask for binary channel 209)
• B15RBDR: 225 to 240 (IndicationMa225, indication mask for binary channel 225)
• B16RBDR: 241 to 256 (IndicationMa241, indication mask for binary channel 241)
• B17RBDR: 257 to 272 (IndicationMa257, indication mask for binary channel 257)
• B18RBDR: 273 to 288 (IndicationMa273, indication mask for binary channel 273)
• B19RBDR: 289 to 304 (IndicationMa289, indication mask for binary channel 289)
• B20RBDR: 305 to 320 (IndicationMa305, indication mask for binary channel 305)
• B21RBDR: 321 to 336 (IndicationMa321, indication mask for binary channel 321)
• B22RBDR: 337 to 352 (IndicationMa337, indication mask for binary channel 337)

18.6.6 Monitored data


PID-3949-MONITOREDDATA v2

Table 846: DRPRDRE Monitored data


Name Type Values (Range) Unit Description
MemoryUsed INTEGER - % Memory usage (0-100%)
UnTrigStatCh1 BOOLEAN - - Under level trig for analog channel 1
activated
OvTrigStatCh1 BOOLEAN - - Over level trig for analog channel 1
activated
UnTrigStatCh2 BOOLEAN - - Under level trig for analog channel 2
activated
OvTrigStatCh2 BOOLEAN - - Over level trig for analog channel 2
activated
UnTrigStatCh3 BOOLEAN - - Under level trig for analog channel 3
activated
OvTrigStatCh3 BOOLEAN - - Over level trig for analog channel 3
activated
UnTrigStatCh4 BOOLEAN - - Under level trig for analog channel 4
activated
OvTrigStatCh4 BOOLEAN - - Over level trig for analog channel 4
activated
UnTrigStatCh5 BOOLEAN - - Under level trig for analog channel 5
activated
OvTrigStatCh5 BOOLEAN - - Over level trig for analog channel 5
activated
UnTrigStatCh6 BOOLEAN - - Under level trig for analog channel 6
activated
OvTrigStatCh6 BOOLEAN - - Over level trig for analog channel 6
activated
UnTrigStatCh7 BOOLEAN - - Under level trig for analog channel 7
activated
OvTrigStatCh7 BOOLEAN - - Over level trig for analog channel 7
activated
Table continues on next page

1032 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

Name Type Values (Range) Unit Description


UnTrigStatCh8 BOOLEAN - - Under level trig for analog channel 8
activated
OvTrigStatCh8 BOOLEAN - - Over level trig for analog channel 8
activated
UnTrigStatCh9 BOOLEAN - - Under level trig for analog channel 9
activated
OvTrigStatCh9 BOOLEAN - - Over level trig for analog channel 9
activated
UnTrigStatCh10 BOOLEAN - - Under level trig for analog channel 10
activated
OvTrigStatCh10 BOOLEAN - - Over level trig for analog channel 10
activated
UnTrigStatCh11 BOOLEAN - - Under level trig for analog channel 11
activated
OvTrigStatCh11 BOOLEAN - - Over level trig for analog channel 11
activated
UnTrigStatCh12 BOOLEAN - - Under level trig for analog channel 12
activated
OvTrigStatCh12 BOOLEAN - - Over level trig for analog channel 12
activated
UnTrigStatCh13 BOOLEAN - - Under level trig for analog channel 13
activated
OvTrigStatCh13 BOOLEAN - - Over level trig for analog channel 13
activated
UnTrigStatCh14 BOOLEAN - - Under level trig for analog channel 14
activated
OvTrigStatCh14 BOOLEAN - - Over level trig for analog channel 14
activated
UnTrigStatCh15 BOOLEAN - - Under level trig for analog channel 15
activated
OvTrigStatCh15 BOOLEAN - - Over level trig for analog channel 15
activated
UnTrigStatCh16 BOOLEAN - - Under level trig for analog channel 16
activated
OvTrigStatCh16 BOOLEAN - - Over level trig for analog channel 16
activated
UnTrigStatCh17 BOOLEAN - - Under level trig for analog channel 17
activated
OvTrigStatCh17 BOOLEAN - - Over level trig for analog channel 17
activated
UnTrigStatCh18 BOOLEAN - - Under level trig for analog channel 18
activated
OvTrigStatCh18 BOOLEAN - - Over level trig for analog channel 18
activated
UnTrigStatCh19 BOOLEAN - - Under level trig for analog channel 19
activated
OvTrigStatCh19 BOOLEAN - - Over level trig for analog channel 19
activated
UnTrigStatCh20 BOOLEAN - - Under level trig for analog channel 20
activated
OvTrigStatCh20 BOOLEAN - - Over level trig for analog channel 20
activated
Table continues on next page

Line distance protection REL670 1033


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

Name Type Values (Range) Unit Description


UnTrigStatCh21 BOOLEAN - - Under level trig for analog channel 21
activated
OvTrigStatCh21 BOOLEAN - - Over level trig for analog channel 21
activated
UnTrigStatCh22 BOOLEAN - - Under level trig for analog channel 22
activated
OvTrigStatCh22 BOOLEAN - - Over level trig for analog channel 22
activated
UnTrigStatCh23 BOOLEAN - - Under level trig for analog channel 23
activated
OvTrigStatCh23 BOOLEAN - - Over level trig for analog channel 23
activated
UnTrigStatCh24 BOOLEAN - - Under level trig for analog channel 24
activated
OvTrigStatCh24 BOOLEAN - - Over level trig for analog channel 24
activated
UnTrigStatCh25 BOOLEAN - - Under level trig for analog channel 25
activated
OvTrigStatCh25 BOOLEAN - - Over level trig for analog channel 25
activated
UnTrigStatCh26 BOOLEAN - - Under level trig for analog channel 26
activated
OvTrigStatCh26 BOOLEAN - - Over level trig for analog channel 26
activated
UnTrigStatCh27 BOOLEAN - - Under level trig for analog channel 27
activated
OvTrigStatCh27 BOOLEAN - - Over level trig for analog channel 27
activated
UnTrigStatCh28 BOOLEAN - - Under level trig for analog channel 28
activated
OvTrigStatCh28 BOOLEAN - - Over level trig for analog channel 28
activated
UnTrigStatCh29 BOOLEAN - - Under level trig for analog channel 29
activated
OvTrigStatCh29 BOOLEAN - - Over level trig for analog channel 29
activated
UnTrigStatCh30 BOOLEAN - - Under level trig for analog channel 30
activated
OvTrigStatCh30 BOOLEAN - - Over level trig for analog channel 30
activated
UnTrigStatCh31 BOOLEAN - - Under level trig for analog channel 31
activated
OvTrigStatCh31 BOOLEAN - - Over level trig for analog channel 31
activated
UnTrigStatCh32 BOOLEAN - - Under level trig for analog channel 32
activated
OvTrigStatCh32 BOOLEAN - - Over level trig for analog channel 32
activated
UnTrigStatCh33 BOOLEAN - - Under level trig for analog channel 33
activated
OvTrigStatCh33 BOOLEAN - - Over level trig for analog channel 33
activated
Table continues on next page

1034 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

Name Type Values (Range) Unit Description


UnTrigStatCh34 BOOLEAN - - Under level trig for analog channel 34
activated
OvTrigStatCh34 BOOLEAN - - Over level trig for analog channel 34
activated
UnTrigStatCh35 BOOLEAN - - Under level trig for analog channel 35
activated
OvTrigStatCh35 BOOLEAN - - Over level trig for analog channel 35
activated
UnTrigStatCh36 BOOLEAN - - Under level trig for analog channel 36
activated
OvTrigStatCh36 BOOLEAN - - Over level trig for analog channel 36
activated
UnTrigStatCh37 BOOLEAN - - Under level trig for analog channel 37
activated
OvTrigStatCh37 BOOLEAN - - Over level trig for analog channel 37
activated
UnTrigStatCh38 BOOLEAN - - Under level trig for analog channel 38
activated
OvTrigStatCh38 BOOLEAN - - Over level trig for analog channel 38
activated
UnTrigStatCh39 BOOLEAN - - Under level trig for analog channel 39
activated
OvTrigStatCh39 BOOLEAN - - Over level trig for analog channel 39
activated
UnTrigStatCh40 BOOLEAN - - Under level trig for analog channel 40
activated
OvTrigStatCh40 BOOLEAN - - Over level trig for analog channel 40
activated
FaultNumber INTEGER - - Disturbance fault number

18.6.7 Operation principle


M12155-6 v13
Disturbance report DRPRDRE is a common name for several functions to supply the operator,
analysis engineer, and so on, with sufficient information about events in the system.

The functions included in the disturbance report are:

• Event list (EL)


• Indications (IND)
• Event recorder (ER)
• Trip value recorder (TVR)
• Disturbance recorder (DR)
• Fault locator (FL)
• Settings information

Figure 609 shows the relations between Disturbance Report, included functions and function
blocks. Event list (EL), Event recorder (ER) and Indications (IND) uses information from the
binary input function blocks (BxRBDR).Trip value recorder (TVR) uses analog information from
the analog input function blocks (AxRADR) which is used by FL after estimation by TVR.
Disturbance recorder DRPRDRE acquires information from both AxRADR and BxRBDR.

Line distance protection REL670 1035


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

AxRADR Disturbance Report

DRPRDRE FL
Analog signals
Trip value rec Fault locator

BxRBDR Disturbance
recorder

Binary signals

Event list

Event recorder

Indications

IEC09000336-3-en.vsdx

IEC09000336 V3 EN-US

Figure 609: Disturbance report functions and related function blocks


The whole disturbance report can contain information for a number of recordings, each with
the data coming from all the parts mentioned above. The event list function is working
continuously, independent of disturbance triggering, recording time, and so on. Settings
information function contains all the visible settings, parameter information of components
configured in ACT, runtime status and IEC61850 behavior that is added to the disturbance
record header file. These settings information is recorded in XML format and then grouped for
each function instance in the HDR file. The function, setting names and Enum values are same
as in the HMI and can be translated to the selected HMI language. All setting values are
updated along with the units. If the setting values are related to the global base value, then the
setting value is scaled and updated with corresponding global base unit. All information in the
disturbance report is stored in non-volatile flash memories. This implies that no information is
lost in case of loss of auxiliary power. Each report will get an identification number in the
interval from 0-999.

Disturbance report

Record no. N Record no. N+1 Record no. N+100

General dist.
Trip Event Disturbance
Information & Setting Indications Fault locator Event list
values recordings recording
infotrmation

IEC05000125-2-en.vsdx
IEC05000125 V2 EN-US

Figure 610: Disturbance report structure


Up to 100 disturbance reports can be stored. If a new disturbance is to be recorded when the
memory is full, the oldest disturbance report is overwritten by the new one. The total
recording capacity for the disturbance recorder is depending of sampling frequency, number
of analog and binary channels and recording time and settings information (refer Figure 612

1036 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

for the recording times definition). Figure 611 shows the number of recordings versus the total
recording time tested for a typical configuration. In a 50 Hz system, it is possible to record 100
disturbance recordings where the average recording time for each disturbance recording file
is 3.4 seconds with 40 analog and 96 binary signals in each recording. The memory limit does
not affect the rest of the disturbance recordings report (Event list (EL), Event recordings (ER),
Indications (IND) and Trip value recordings (TVR)).

Number of recordings
100
3,4 s

80 3,4 s 20 analog
96 binary
40 analog
96 binary
60 6,3 s
6,3 s

6,3 s 50 Hz
40
60 Hz
Total recording time

250 300 350 400 s

en05000488.vsd
IEC05000488 V1 EN-US

Figure 611: Example of number of recordings versus the total recording time

The maximum number of recordings depend on each recordings total


recording time. Long recording time will reduce the number of recordings to
less than 100.

The IED flash disk should NOT be used to store any user files. This might cause
disturbance recordings to be deleted due to lack of disk space.

Disturbance information M12155-175 v4


Date and time of the disturbance, the indications, events, fault location and the trip values are
available on the local HMI. To acquire a complete disturbance report the user must use a PC
and - either the PCM600 Disturbance handling tool - or a FTP or MMS (over 61850) client. The
PC can be connected to the IED front, rear or remotely via the station bus (Ethernet ports).

Indications (IND) M12155-87 v5


Indications is a list of signals that were activated during the total recording time of the
disturbance (not time-tagged).

Event recorder (ER) M12155-89 v6


The event recorder may contain a list of up to 150 time-tagged events, which have occurred
during the disturbance. The information is available via the local HMI or PCM600.

Line distance protection REL670 1037


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

Event list (EL) M12155-177 v7


The event list may contain a list of totally 1000 time-tagged events. The list information is
continuously updated when selected binary signals change state. The oldest data is
overwritten. The logged signals may be presented via the local HMI or PCM600.

Trip value recorder (TVR) M12155-91 v5


The recorded trip values include phasors of selected analog signals before the fault and during
the fault.

Disturbance recorder (DR) M12155-97 v5


Disturbance recorder records analog and binary signal data before, during and after the fault.

Settings information GUID-892F72ED-CC6C-469B-90CA-73E9E1181187 v2


For each disturbance recording, the setting values of the configured components are read
twice; once during the trigger of disturbance record and again during post processing of the
disturbance record.

During post processing of the disturbance record, the header file is updated with a section
called Settings . Settings has complete setting values of the configured components that are
read during the trigger time. The setting values, runtime status and the behavior of each
component are compared between the trigger and the post processing time. If there are any
differences, then it will be added in the header file under section Changed_settings.

In the HDR file, section tag Settings has an attribute tag called function which includes
parameters that are grouped based on the function instance. The function tag has content
called name which is the function name provided together with the user-defined name in
brackets similar to the HMI. Status content will indicate the runtime status of the function and
beh content will indicate the IEC61850 behavior of the components, if supported. Non runtime
components will not have status and beh tag contents.

Parameters of the function are listed as a child tag Set with contents name, value and unit:

• name — parameter name same as HMI


• value — actual parameter value
• unit — parameter unit

The changed_settings attribute tag is similar to the settings section. It contains functions
which have changes in parameter value or runtime status or IEC61850 behavior when
compared with trigger and post-processing settings values.

Fault locator (FL) M12155-186 v4


The fault location function calculates the distance to fault.

Time tagging M12155-194 v1


The IED has a built-in real-time calendar and clock. This function is used for all time tagging
within the disturbance report

Recording times M12155-99 v5


Disturbance report DRPRDRE records information about a disturbance during a settable time
frame. The recording times are valid for the whole disturbance report. Disturbance recorder
(DR), event recorder (ER) and indication function register disturbance data and events during
tRecording, the total recording time.

The total recording time, tRecording, of a recorded disturbance is:

tRecording = PreFaultrecT + tFault + PostFaultrecT or PreFaultrecT + TimeLimit, depending on


which criterion stops the current disturbance recording

1038 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

Trig point
TimeLimit

PreFaultRecT PostFaultRecT

1 2 3

en05000487.vsd
IEC05000487 V1 EN-US

Figure 612: The recording times definition

PreFaultRecT, 1 Pre-fault or pre-trigger recording time. The time before the fault including the operate time
of the trigger. Use the setting PreFaultRecT to set this time.
tFault, 2 Fault time of the recording. The fault time cannot be set. It continues as long as any valid
trigger condition, binary or analog, persists (unless limited by TimeLimit the limit time).
PostFaultRecT, 3 Post fault recording time. The time the disturbance recording continues after all activated
triggers are reset. Use the setting PostFaultRecT to set this time.
TimeLimit Limit time. The maximum allowed recording time after the disturbance recording was
triggered. The limit time is used to eliminate the consequences of a trigger that does not
reset within a reasonable time interval. It limits the maximum recording time of a recording
and prevents subsequent overwriting of already stored disturbances. Use the setting
TimeLimit to set this time.

Analog signals M12155-160 v9


Up to 40 analog signals can be selected for recording by the Disturbance recorder and
triggering of the Disturbance report function. Out of these 40, 30 are reserved for external
analog signals from analog input modules (TRM) and line data communication module (LDCM)
via preprocessing function blocks (SMAI) and summation block (3PHSUM). The last 10 channels
may be connected to internally calculated analog signals available as function block output
signals (mA input signals, phase differential currents, bias currents and so on).

Line distance protection REL670 1039


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

SMAI A1RADR
Block AI3P A2RADR
^GRP2L1 AI1 INPUT1 A3RADR
External
analogue ^GRP2L2 AI2 INPUT2
signals ^GRP2L3 AI3 INPUT3
^GRP2N AI4 INPUT4
Type AIN INPUT5
INPUT6
...

A4RADR

INPUT31
INPUT32
INPUT33
Internal analogue signals INPUT34
INPUT35
INPUT36

...

INPUT40

IEC10000029-1-en.vsd
IEC10000029 V1 EN-US

Figure 613: Analog input function blocks


The external input signals will be acquired, filtered and skewed and (after configuration)
available as an input signal on the AxRADR function block via the SMAI function block. The
information is saved at the Disturbance report base sampling rate (1000 or 1200 Hz). Internally
calculated signals are updated according to the cycle time of the specific function. If a function
is running at lower speed than the base sampling rate, Disturbance recorder will use the latest
updated sample until a new updated sample is available.

If the IED is preconfigured the only tool needed for analog configuration of the Disturbance
report is the Signal Matrix Tool (SMT, external signal configuration). In case of modification of
a preconfigured IED or general internal configuration the Application Configuration tool within
PCM600 is used.

The preprocessor function block (SMAI) calculates the residual quantities in cases where only
the three phases are connected (AI4-input not used). SMAI makes the information available as
a group signal output, phase outputs and calculated residual output (AIN-output). In situations
where AI4-input is used as an input signal the corresponding information is available on the
non-calculated output (AI4) on the SMAI function block. Connect the signals to the AxRADR
accordingly.

For each of the analog signals, Operation = On means that it is recorded by the disturbance
recorder. The trigger is independent of the setting of Operation, and triggers even if operation
is set to Off. Both undervoltage and overvoltage can be used as trigger conditions. The same
applies for the current signals.

If Operation = Off, no waveform (samples) will be recorded and reported in graph. However,
Trip value, pre-fault and fault value will be recorded and reported. The input channel can still be
used to trig the disturbance recorder.

If Operation = On, waveform (samples) will also be recorded and reported in graph.

The analog signals are presented only in the disturbance recording, but they affect the entire
disturbance report when being used as triggers.

1040 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

Binary signals M12155-162 v10


Up to 352 binary signals can be selected to be handled by disturbance report. The signals can
be selected from internal logical and binary input signals. A binary signal is selected to be
recorded when:

• the corresponding function block is included in the configuration


• the signal is connected to the input of the function block

Each of the 352 signals can be selected as a trigger of the disturbance report (Operation = On).
A binary signal can be selected to activate the red LED on the local HMI (SetLED = On).

The selected signals are presented in the event recorder, event list and the disturbance
recording. But they affect the whole disturbance report when they are used as triggers. The
indications are also selected from these 352 signals with local HMI IndicationMask = Show/
Hide.

Trigger signals M12155-164 v3


The trigger conditions affect the entire disturbance report, except the event list, which runs
continuously. As soon as at least one trigger condition is fulfilled, a complete disturbance
report is recorded. On the other hand, if no trigger condition is fulfilled, there is no
disturbance report, no indications, and so on. This implies the importance of choosing the
right signals as trigger conditions.

A trigger can be of type:

• Manual trigger
• Binary-signal trigger
• Analog-signal trigger (over/under function)

Manual trigger M12155-167 v5


A disturbance report can be manually triggered from the local HMI, PCM600 or via station bus
(IEC 61850). When the trigger is activated, the manual trigger signal is generated. This feature
is especially useful for testing. Refer to the operator's manual for procedure.

Binary-signal trigger M12155-169 v4


Any binary signal state (logic one or a logic zero) can be selected to generate a trigger
(Triglevel = Trig on 0/Trig on 1). When a binary signal is selected to generate a trigger from a
logic zero, the selected signal will not be listed in the indications list of the disturbance report.

Analog-signal trigger M12155-171 v6


All analog signals are available for trigger purposes, no matter if they are recorded in the
disturbance recorder or not. The settings are OverTrigOp, UnderTrigOp, OverTrigLe and
UnderTrigLe.

The check of the trigger condition is based on peak-to-peak values. When this is found, the
absolute average value of these two peak values is calculated. If the average value is above the
threshold level for an overvoltage or overcurrent trigger, this trigger is indicated with a greater
than (>) sign with the user-defined name.

If the average value is below the set threshold level for an undervoltage or undercurrent
trigger, this trigger is indicated with a less than (<) sign with its name. The procedure is
separately performed for each channel.

This method of checking the analog start conditions gives a function which is insensitive to DC
offset in the signal. The operate time for this start is typically in the range of one cycle, 20 ms
for a 50 Hz network.

All under/over trig signal information is available on the local HMI and PCM600.

Line distance protection REL670 1041


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

18.6.8 Technical data


M12760-1 v11

Table 847: DRPRDRE technical data


Function Range or value Accuracy
Pre-fault time (0.05–9.90) s -
Post-fault time (0.1–10.0) s -
Limit time (0.5–10.0) s -
Maximum number of recordings 100, first in - first out -
Time tagging resolution 1 ms See table 1053
Maximum number of analog inputs 30 + 10 (external + internally -
derived)
Maximum number of binary inputs 352 -
Maximum number of phasors in the Trip Value 30 -
recorder per recording
Maximum number of indications in a disturbance 352 -
report
Maximum number of events in the Event recording 150 -
per recording
Maximum number of events in the Event list 1000, first in - first out -
Maximum total recording time (3.4 s recording 340 seconds (100 recordings) -
time and maximum number of channels, typical at 50 Hz, 280 seconds (80
value) recordings) at 60 Hz
Sampling rate 1 kHz at 50 Hz -
1.2 kHz at 60 Hz
Recording bandwidth (5-300) Hz -

18.7 Logical signal status report BINSTATREP GUID-E7A2DB38-DD96-4296-B3D5-EB7FBE77CE07 v2

18.7.1 Identification GUID-E0247779-27A2-4E6C-A6DD-D4C31516CA5C v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Logical signal status report BINSTATREP - -

18.7.2 Functionality GUID-A72E490D-01F7-4874-B010-8BDE38391D88 v3

The Logical signal status report (BINSTATREP) function makes it possible for a SPA master to
poll signals from various other functions.

1042 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

18.7.3 Function block GUID-BA0A5BC3-493B-4FE3-B4A9-14F60A88A22F v2

BINSTATREP
BLOCK OUTPUT1
^INPUT1 OUTPUT2
^INPUT2 OUTPUT3
^INPUT3 OUTPUT4
^INPUT4 OUTPUT5
^INPUT5 OUTPUT6
^INPUT6 OUTPUT7
^INPUT7 OUTPUT8
^INPUT8 OUTPUT9
^INPUT9 OUTPUT10
^INPUT10 OUTPUT11
^INPUT11 OUTPUT12
^INPUT12 OUTPUT13
^INPUT13 OUTPUT14
^INPUT14 OUTPUT15
^INPUT15 OUTPUT16
^INPUT16

IEC09000730-1-en.vsd
IEC09000730 V1 EN-US

Figure 614: BINSTATREP function block

18.7.4 Signals
PID-4144-INPUTSIGNALS v6

Table 848: BINSTATREP Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
INPUT1 BOOLEAN 0 Single status report input 1
INPUT2 BOOLEAN 0 Single status report input 2
INPUT3 BOOLEAN 0 Single status report input 3
INPUT4 BOOLEAN 0 Single status report input 4
INPUT5 BOOLEAN 0 Single status report input 5
INPUT6 BOOLEAN 0 Single status report input 6
INPUT7 BOOLEAN 0 Single status report input 7
INPUT8 BOOLEAN 0 Single status report input 8
INPUT9 BOOLEAN 0 Single status report input 9
INPUT10 BOOLEAN 0 Single status report input 10
INPUT11 BOOLEAN 0 Single status report input 11
INPUT12 BOOLEAN 0 Single status report input 12
INPUT13 BOOLEAN 0 Single status report input 13
INPUT14 BOOLEAN 0 Single status report input 14
INPUT15 BOOLEAN 0 Single status report input 15
INPUT16 BOOLEAN 0 Single status report input 16

Line distance protection REL670 1043


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

PID-4144-OUTPUTSIGNALS v6

Table 849: BINSTATREP Output signals


Name Type Description
OUTPUT1 BOOLEAN Logical status report output 1
OUTPUT2 BOOLEAN Logical status report output 2
OUTPUT3 BOOLEAN Logical status report output 3
OUTPUT4 BOOLEAN Logical status report output 4
OUTPUT5 BOOLEAN Logical status report output 5
OUTPUT6 BOOLEAN Logical status report output 6
OUTPUT7 BOOLEAN Logical status report output 7
OUTPUT8 BOOLEAN Logical status report output 8
OUTPUT9 BOOLEAN Logical status report output 9
OUTPUT10 BOOLEAN Logical status report output 10
OUTPUT11 BOOLEAN Logical status report output 11
OUTPUT12 BOOLEAN Logical status report output 12
OUTPUT13 BOOLEAN Logical status report output 13
OUTPUT14 BOOLEAN Logical status report output 14
OUTPUT15 BOOLEAN Logical status report output 15
OUTPUT16 BOOLEAN Logical status report output 16

18.7.5 Settings
PID-4144-SETTINGS v6

Table 850: BINSTATREP Non group settings (basic)


Name Values (Range) Unit Step Default Description
t 0.0 - 60.0 s 0.1 10.0 Time delay of function

18.7.6 Operation principle GUID-537921CA-82B9-4A02-BAD1-67E3AC61AE96 v3

The Logical signal status report (BINSTATREP) function has 16 inputs and 16 outputs. The
output status follows the inputs and can be read from the local HMI or via SPA communication.

When an input is set, the respective output is set for a user defined time. If the input signal
remains set for a longer period, the output will remain set until the input signal resets.

INPUTn

OUTPUTn
t t

IEC09000732-1-en.vsd
IEC09000732 V1 EN-US

Figure 615: BINSTATREP logical diagram

1044 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

18.8 Measured value expander block RANGE_XP SEMOD52451-1 v2

18.8.1 Identification
SEMOD113212-2 v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Measured value expander block RANGE_XP - -

18.8.2 Functionality SEMOD52450-4 v8

The current and voltage measurements functions (CVMMXN, CMMXU, VMMXU and VNMMXU),
current and voltage sequence measurement functions (CMSQI and VMSQI) and IEC 61850
generic communication I/O functions (MVGAPC) are provided with measurement supervision
functionality. All measured values can be supervised with four settable limits: low-low limit,
low limit, high limit and high-high limit. The measure value expander block (RANGE_XP) has
been introduced to enable translating the integer output signal from the measuring functions
to 5 binary signals: below low-low limit, below low limit, normal, above high limit or above
high-high limit. The output signals can be used as conditions in the configurable logic or for
alarming purpose.

18.8.3 Function block SEMOD54336-4 v3

RANGE_XP
RANGE* HIGHHIGH
HIGH
NORMAL
LOW
LOWLOW

IEC05000346-2-en.vsd
IEC05000346 V2 EN-US

Figure 616: RANGE_XP function block

18.8.4 Signals SEMOD53803-1 v2

PID-3819-INPUTSIGNALS v5

Table 851: RANGE_XP Input signals


Name Type Default Description
RANGE INTEGER 0 Measured value range

PID-3819-OUTPUTSIGNALS v5

Table 852: RANGE_XP Output signals


Name Type Description
HIGHHIGH BOOLEAN Measured value is above high-high limit
HIGH BOOLEAN Measured value is between high and high-high limit
NORMAL BOOLEAN Measured value is between high and low limit
LOW BOOLEAN Measured value is between low and low-low limit
LOWLOW BOOLEAN Measured value is below low-low limit

Line distance protection REL670 1045


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

18.8.5 Operation principle SEMOD52462-4 v6

The input signal must be connected to a range output of a measuring function block
(CVMMXN, CMMXU, VMMXU, VNMMXU, CMSQI, VMSQ or MVGAPC). The function block converts
the input integer value to five binary output signals according to table 853.

Table 853: Input integer value converted to binary output signals


Measured supervised below low- between low‐ between low between above high-high limit
value is: low limit low and low and high limit high-high
Output: limit and high limit
LOWLOW High
LOW High
NORMAL High
HIGH High
HIGHHIGH High

18.9 Fault locator LMBRFLO IP14592-1 v2

18.9.1 Identification
M14892-1 v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Fault locator LMBRFLO - -

18.9.2 Functionality M13970-3 v13

The accurate fault locator is an essential component to minimize the outages after a
persistent fault and/or to pin-point a weak spot on the line.

The fault locator is an impedance measuring function giving the distance to the fault in km,
miles or % of line length. The main advantage is the high accuracy achieved by compensating
for load current and for the mutual zero-sequence effect on double circuit lines.

The compensation includes setting of the remote and local sources and calculation of the
distribution of fault currents from each side. This distribution of fault current, together with
recorded load (pre-fault) currents, is used to exactly calculate the fault position. The fault can
be recalculated with new source data at the actual fault to further increase the accuracy.

Especially on heavily loaded long lines, where the source voltage angles can be up to 35-40
degrees apart, the accuracy can be still maintained with the advanced compensation included
in fault locator.

1046 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

18.9.3 Function block M16684-3 v7

LMBRFLO
PHSELL1* CALCMADE
PHSELL2* FLT_X
PHSELL3* BCD_80
CALCDIST* BCD_40
BCD_20
BCD_10
BCD_8
BCD_4
BCD_2
BCD_1

IEC05000679-4-en.vsd

IEC05000679 V4 EN-US

Figure 617: LMBRFLO function block

18.9.4 Signals
PID-3906-INPUTSIGNALS v1

Table 854: LMBRFLO Input signals


Name Type Default Description
PHSELL1 BOOLEAN 0 Phase selecton L1
PHSELL2 BOOLEAN 0 Phase selecton L2
PHSELL3 BOOLEAN 0 Phase selecton L3
CALCDIST BOOLEAN 0 Do calculate fault distance (release)

PID-3906-OUTPUTSIGNALS v1

Table 855: LMBRFLO Output signals


Name Type Description
CALCMADE BOOLEAN Fault calculation made
FLT_X REAL Reactive distance to fault
BCD_80 BOOLEAN Distance in binary coded data, bit represents 80%
BCD_40 BOOLEAN Distance in binary coded data, bit represents 40%
BCD_20 BOOLEAN Distance in binary coded data, bit represents 20%
BCD_10 BOOLEAN Distance in binary coded data, bit represents 10%
BCD_8 BOOLEAN Distance in binary coded data, bit represents 8%
BCD_4 BOOLEAN Distance in binary coded data, bit represents 4%
BCD_2 BOOLEAN Distance in binary coded data, bit represents 2%
BCD_1 BOOLEAN Distance in binary coded data, bit represents 1%

Line distance protection REL670 1047


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

18.9.5 Settings
PID-3906-SETTINGS v2

Table 856: LMBRFLO Group settings (basic)


Name Values (Range) Unit Step Default Description
R1A 0.001 - 1500.000 Ohm/p 0.001 2.000 Source resistance A (near end)
X1A 0.001 - 1500.000 Ohm/p 0.001 12.000 Source reactance A (near end)
R1B 0.001 - 1500.000 Ohm/p 0.001 2.000 Source resistance B (far end)
X1B 0.001 - 1500.000 Ohm/p 0.001 12.000 Source reactance B (far end)
R1L 0.001 - 1500.000 Ohm/p 0.001 2.000 Positive sequence line resistance
X1L 0.001 - 1500.000 Ohm/p 0.001 12.500 Positive sequence line reactance
R0L 0.001 - 1500.000 Ohm/p 0.001 8.750 Zero sequence line resistance
X0L 0.001 - 1500.000 Ohm/p 0.001 50.000 Zero sequence line reactance
R0M 0.000 - 1500.000 Ohm/p 0.001 0.000 Zero sequence mutual resistance
X0M 0.000 - 1500.000 Ohm/p 0.001 0.000 Zero sequence mutual reactance
LineLengthUnit kilometer - - kilometer Line length unit
miles
LineLength 0.0 - 10000.0 - 0.1 40.0 Length of line

Table 857: LMBRFLO Non group settings (basic)


Name Values (Range) Unit Step Default Description
DrepChNoIL1 1 - 30 Ch 1 1 Recorder input number recording
phase current, IL1
DrepChNoIL2 1 - 30 Ch 1 2 Recorder input number recording
phase current, IL2
DrepChNoIL3 1 - 30 Ch 1 3 Recorder input number recording
phase current, IL3
DrepChNoIN 0 - 30 Ch 1 4 Recorder input number recording
residual current, IN
DrepChNoIP 0 - 30 Ch 1 0 Recorder input number recording 3I0
on parallel line
DrepChNoUL1 1 - 30 Ch 1 5 Recorder input number recording
phase voltage, UL1
DrepChNoUL2 1 - 30 Ch 1 6 Recorder input number recording
phase voltage, UL2
DrepChNoUL3 1 - 30 Ch 1 7 Recorder input number recording
phase voltage, UL3
UL1Gain 0.000 - 10.000 - 0.001 1.000 Scale factor for fine tuning of voltage
magnitude L1
UL2Gain 0.000 - 10.000 - 0.001 1.000 Scale factor for fine tuning of voltage
magnitude L2
UL3Gain 0.000 - 10.000 - 0.001 1.000 Scale factor for fine tuning of voltage
magnitude L3

1048 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

18.9.6 Monitored data


PID-3906-MONITOREDDATA v1

Table 858: LMBRFLO Monitored data


Name Type Values (Range) Unit Description
FLT_REL REAL - - Distance to fault, relative
FLT_DIST REAL - - Distance to fault in line length unit
FLT_X REAL - Ohm Reactive distance to fault
FLT_R REAL - Ohm Resistive distance to fault
FLT_LOOP INTEGER 1=L1-N - Fault loop
2=L2-N
3=L3-N
4=L1-L2
5=L2-L3
6=L3-L1
7=Others

18.9.7 Operation principle


M14982-4 v7
The Fault locator (LMBRFLO) in the IED is an essential complement to other monitoring
functions, since it measures and indicates the distance to the fault with high accuracy.

When calculating distance to fault, pre-fault and fault phasors of currents and voltages are
selected from the Trip value recorder data, thus the analog signals used by the fault locator
must be among those connected to the disturbance report function. The analog configuration
(channel selection) is performed using the parameter setting tool within PCM600.

The calculation algorithm considers the effect of load currents, double-end infeed and
additional fault resistance.

R0L+jX0L
R1L+jX1L

R1A+jX1A R1B+jX1B
Z0m=Z0m+jX0m

R0L+jX0L
R1L+jX1L
DRPRDRE
LMBRFLO

IEC05000045_2_en.vsd
IEC05000045 V2 EN-US

Figure 618: Simplified network configuration with network data, required for settings of
the fault location-measuring function
If source impedance in the near and far end of the protected line have changed in a significant
manner relative to the set values at fault location calculation time (due to exceptional
switching state in the immediate network, power generation out of order, and so on), new
values can be entered via the local HMI and a recalculation of the distance to the fault can be
ordered using the algorithm described below. It’s also possible to change fault loop. In this
way, a more accurate location of the fault can be achieved.

The function indicates the distance to the fault as a percentage of the line length, in kilometers
or miles according to the setting LineLengthUnit. The fault location is stored as a part of the

Line distance protection REL670 1049


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

disturbance report information (ER, DR, IND, TVR and FL) and managed via the local HMI or
PCM600.

18.9.7.1 Measuring Principle M14983-4 v2

For transmission lines with voltage sources at both line ends, the effect of double-end infeed
and additional fault resistance must be considered when calculating the distance to the fault
from the currents and voltages at one line end. If this is not done, the accuracy of the
calculated figure will vary with the load flow and the amount of additional fault resistance.

The calculation algorithm used in the fault locator in compensates for the effect of double-end
infeed, additional fault resistance and load current.

M14983-5 v1

18.9.7.2 Accurate algorithm for measurement of distance to fault M14983-7 v5

Figure 619 shows a single-line diagram of a single transmission line, that is fed from both ends
with source impedances ZA and ZB. Assume that the fault occurs at a distance F from IED A on
a line with the length L and impedance ZL. The fault resistance is defined as RF. A single-line
model is used for better clarification of the algorithm.

A B
ZA IA pZL IB (1-p).ZL ZB

IF

UA RF

xx01000171.vsd
IEC01000171 V1 EN-US

Figure 619: Fault on transmission line fed from both ends


From figure 619 it is evident that:

U A = I A × p × Z L + IF × R F
EQUATION95 V1 EN-US (Equation 210)

Where:
IA is the line current after the fault, that is, pre-fault current plus current change due to the fault,

IF is the fault current and

p is a relative distance to the fault

The fault current is expressed in measurable quantities by:

1050 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

IF A
IF = --------
DA
EQUATION96 V1 EN-US (Equation 211)

Where:
IFA is the change in current at the point of measurement, IED A and

DA is a fault current-distribution factor, that is, the ratio between the fault current at line end A and the
total fault current.

For a single line, the value is equal to:

( 1 – p ) × Z L + ZB
DA = -----------------------------------------
Z A + Z L + ZB
EQUATION97 V1 EN-US (Equation 212)

Thus, the general fault location equation for a single line is:

I FA
U A = I A × p × Z L + -------- × R F
DA
EQUATION98 V1 EN-US (Equation 213)

Table 859: Expressions for UA, IA and IFA for different types of faults

Fault type: UA IA IFA


L1-N UL1A IL1A + KN x INA 3
--- ´ D ( I L 1 A – I 0A )
2
EQUATION110 V1 EN-US

L2-N UL2A IL2A + KN x INA


3
--- ´ D ( I L2A – I 0A )
2
EQUATION111 V1 EN-US

L3-N UL3A IL3A + KN x INA


3
--- ´ D ( I L3A – I0A )
2
EQUATION112 V1 EN-US

L1-L2-L3, L1-L2,L1-L2- UL1A-UL2A IL1A - IL2A


DIL 1 L 2 A
N
EQUATION113 V1 EN-US

L2-L3, L2-L3-N UL2A-UL3A IL2A - IL3A DIL2L3A


EQUATION114 V1 EN-US

L3-L1, L3-L1-N UL3A-UL1A IL3A - IL1A


DIL3L1A
EQUATION115 V1 EN-US

The KN complex quantity for zero-sequence compensation for the single line is equal to:

Z0L – Z 1L
K N = ------------------------
3 × Z1L
EQUATION99 V1 EN-US (Equation 214)

DI is the change in current, that is the current after the fault minus the current before the fault.

In the following, the positive sequence impedance for ZA, ZB and ZL is inserted into the
equations, because this is the value used in the algorithm.

Line distance protection REL670 1051


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

For double lines, the fault equation is:

I FA
U A = I A × p × Z 1L + -------- × RF + I 0P × Z 0M
DA
EQUATION100 V1 EN-US (Equation 215)

Where:
I0P is a zero sequence current of the parallel line,

Z0M is a mutual zero sequence impedance and

DA is the distribution factor of the parallel line, which is:

( 1 – p ) × ( ZA + ZA L + ZB ) + Z B
DA = ----------------------------------------------------------------------------
-
2 × ZA + Z L + 2 × Z B
EQUATION101 V1 EN-US (Equation 216)

The KN compensation factor for the double line becomes:

Z0L – Z 1L Z 0M I 0P
K N = ----------------------- - × -------
- + ----------------
3 × Z1L 3 × Z1L I 0A
EQUATION102 V1 EN-US (Equation 217)

From these equations it can be seen, that, if Z0m = 0, then the general fault location equation
for a single line is obtained. Only the distribution factor differs in these two cases.

Because the DA distribution factor according to equation 213 or 215 is a function of p, the
general equation 215 can be written in the form:

2
p – p × K1 + K2 – K3 × RF = 0
EQUATION103 V1 EN-US (Equation 218)

Where:

UA ZB
K 1 = ---------------
- + --------------------------
-+1
I A × ZL Z L + ZA DD

EQUATION104 V1 EN-US (Equation 219)

UA ZB
K2 = --------------- × æè --------------------------- + 1öø
IA × Z L Z L + Z A DD

EQUATION105 V1 EN-US (Equation 220)

I F A æ Z A + ZB
- × --------------------------- + 1ö
K 3 = ---------------
I A × Z L è Z 1 + ZA DD ø
EQUATION106 V1 EN-US (Equation 221)

and:

1052 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

• ZADD = ZA + ZB for parallel lines.


• IA, IFA and UA are given in the above table.
• KN is calculated automatically according to equation 217.
• ZA, ZB, ZL, Z0L and Z0M are setting parameters.

For a single line, Z0M = 0 and ZADD = 0. Thus, equation 218 applies to both single and parallel
lines.

Equation 218 can be divided into real and imaginary parts:

2
p – p × Re ( K 1 ) + Re ( K 2 ) – R F × Re ( K 3 ) = 0
EQUATION107 V1 EN-US (Equation 222)

– p × Im × ( K1 ) + Im × ( K 2 ) – R F × Im × ( K3 ) = 0
EQUATION108 V1 EN-US (Equation 223)

If the imaginary part of K3 is not zero, RF can be solved according to equation 223, and then
inserted to equation 222. According to equation 222, the relative distance to the fault is solved
as the root of a quadratic equation.

Equation 222 gives two different values for the relative distance to the fault as a solution. A
simplified load compensated algorithm, which gives an unequivocal figure for the relative
distance to the fault, is used to establish the value that should be selected.

If the load compensated algorithms according to the above do not give a reliable solution, a
less accurate, non-compensated impedance model is used to calculate the relative distance to
the fault.

18.9.7.3 The non-compensated impedance model M14983-121 v3

In the non-compensated impedance model, IA line current is used instead of IFA fault current:

U A = p × Z 1 L × IA + R F × IA
EQUATION109 V1 EN-US (Equation 224)

Where:
IA is according to table 859.

The accuracy of the distance-to-fault calculation, using the non-compensated impedance


model, is influenced by the pre-fault load current. So, this method is only used if the load
compensated models do not function.

18.9.7.4 IEC 60870-5-103 M14983-135 v2

The communication protocol IEC 60870-5-103 may be used to poll fault location information
from the IED to a master (that is station HSI). There are two outputs that must be connected
to appropriate inputs on the function block I103StatFltDis, FLTDISTX gives distance to fault
(reactance, according the standard) and CALCMADE gives a pulse (100 ms) when a result is
obtainable on FLTDISTX output.

Line distance protection REL670 1053


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

18.9.8 Technical data


M14987-1 v6

Table 860: LMBRFLO technical data


Function Value or range Accuracy
Reactive and resistive reach (0.001-1500.000) Ω/phase ±2.0% static accuracy
Conditions:
Voltage range: (0.1-1.1) x Ur
Current range: (0.5-30) x Ir

Phase selection According to input signals -


Maximum number of fault 100 -
locations

18.10 Limit counter L4UFCNT GUID-22E141DB-38B3-462C-B031-73F7466DD135 v1

18.10.1 Identification
GUID-F3FB7B33-B189-4819-A1F0-8AC7762E9B7E v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Limit counter L4UFCNT -

18.10.2 Functionality GUID-13157EAB-1686-4D2E-85DF-EC89768F3572 v6

The Limit counter (L4UFCNT) provides a settable counter with four independent limits where
the number of positive and/or negative flanks on the input signal are counted against the
setting values for limits. The output for each limit is activated when the counted value reaches
that limit.

Overflow indication is included for each up-counter.

18.10.3 Operation principle


GUID-4D58423F-329C-4553-9FAF-E55A368849A5 v2
Limit counter (L4UFCNT) counts the number of positive and/or negative flanks on the binary
input signal depending on the function settings. L4UFCNT also checks if the accumulated
value is equal or greater than any of its four settable limits. The four limit outputs will be
activated relatively on reach of each limit and remain activated until the reset of the function.
Moreover, the content of L4UFCNT is stored in flash memory and will not be lost at an auxiliary
power interruption.

18.10.3.1 Design GUID-B643C994-D0BA-4BE9-BACB-ADEA0197CAE4 v1

Figure 620 illustrates the general logic diagram of the function.

1054 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

BLOCK

INPUT
Operation
Counter
RESET
VALUE
Overflow
CountType Detection OVERFLOW

OnMaxValue

Limit LIMIT1 … 4
MaxValue Check

CounterLimit1...4

Error ERROR
Detection
InitialValue

IEC12000625_1_en.vsd
IEC12000625 V1 EN-US

Figure 620: Logic diagram


The counter can be initialized to count from a settable non-zero value after reset of the
function. The function has also a maximum counted value check. The three possibilities after
reaching the maximum counted value are:

• Stops counting and activates a steady overflow indication for the next count
• Rolls over to zero and activates a steady overflow indication for the next count
• Rolls over to zero and activates a pulsed overflow indication for the next count

The pulsed overflow output lasts up to the first count after rolling over to zero, as illustrated in
figure 621.

Overflow indication

Actual value ... Max value -1® Max value ® Max value +1 ® Max value +2 ® Max value +3 ...

Counted value ... Max value -1 ® Max value ® 0 ® 1 ® 2 ...

IEC12000626_1_en.vsd
IEC12000626 V1 EN-US

Figure 621: Overflow indication when OnMaxValue is set to rollover pulsed


The Error output is activated as an indicator of setting the counter limits and/or initial value
setting(s) greater than the maximum value. The counter stops counting the input and all the
outputs except the error output remains at zero state. The error condition remains until the
correct settings for counter limits and/or initial value setting(s) are applied.

The function can be blocked through a block input. During the block time, input is not counted
and outputs remain in their previous states. However, the counter can be initialized after reset
of the function. In this case the outputs remain in their initial states until the release of the
block input.

Line distance protection REL670 1055


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

18.10.3.2 Reporting GUID-7DF874A7-F7DA-48DD-8760-5E4CF05FD870 v2

The content of the counter can be read on the local HMI.

Reset of the counter can be performed from the local HMI or via a binary input.

Reading of content and resetting of the function can also be performed remotely, for example
from a IEC 61850 client. The value can also be presented as a measurement on the local HMI
graphical display.

18.10.4 Function block GUID-C90E7375-F3CC-414A-93FC-9AC4A9156FFC v1

L4UFCNT
BLOCK ERROR
INPUT OVERFLOW
RESET LIMIT1
LIMIT2
LIMIT3
LIMIT4
VALUE

IEC12000029-1-en.vsd
IEC12000029 V1 EN-US

Figure 622: L4UFCNT function block

18.10.5 Signals
PID-6966-INPUTSIGNALS v2

Table 861: L4UFCNT Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
INPUT BOOLEAN 0 Input for counter
RESET BOOLEAN 0 Reset of function

PID-6966-OUTPUTSIGNALS v2

Table 862: L4UFCNT Output signals


Name Type Description
ERROR BOOLEAN Error indication on counter limit and/or initial value settings
OVERFLOW BOOLEAN Overflow indication on count of greater than MaxValue
LIMIT1 BOOLEAN Counted value is larger than or equal to CounterLimit1
LIMIT2 BOOLEAN Counted value is larger than or equal to CounterLimit2
LIMIT3 BOOLEAN Counted value is larger than or equal to CounterLimit3
LIMIT4 BOOLEAN Counted value is larger than or equal to CounterLimit4
VALUE INTEGER Counted value

1056 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

18.10.6 Settings
PID-6966-SETTINGS v2

Table 863: L4UFCNT Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
CountType Positive edge - - Positive edge Select counting on positive and/or
Negative edge negative flanks
Both edges
CounterLimit1 1 - 65535 - 1 100 Value of the first limit
CounterLimit2 1 - 65535 - 1 200 Value of the second limit
CounterLimit3 1 - 65535 - 1 300 Value of the third limit
CounterLimit4 1 - 65535 - 1 400 Value of the fourth limit
MaxValue 1 - 65535 - 1 500 Maximum count value
OnMaxValue Stop - - Stop Select if counter stops or rolls over
Rollover Steady after reaching maxValue with steady
Rollover Pulsed or pulsed overflow flag
InitialValue 0 - 65535 - 1 0 Initial count value after reset of the
function

18.10.7 Monitored data


PID-6966-MONITOREDDATA v2

Table 864: L4UFCNT Monitored data


Name Type Values (Range) Unit Description
VALUE INTEGER - - Counted value

18.10.8 Technical data


GUID-C43B8654-60FE-4E20-8328-754C238F4AD0 v3

Table 865: L4UFCNT technical data


Function Range or value Accuracy
Counter value 0-65535 -
Max. count up speed 30 pulses/s (50% duty cycle) -

18.11 Running hour-meter TEILGAPC

18.11.1 Identification GUID-3F9EF4FA-74FA-4D1D-88A0-E948B722B64F v1

Function Description IEC 61850 IEC 60617 ANSI/IEEE C37.2 device


identification identification number
Running hour-meter TEILGAPC - -

Line distance protection REL670 1057


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

18.11.2 Functionality GUID-464FB24F-B367-446C-963A-A14841943B87 v2

The Running hour-meter (TEILGAPC) function is a function that accumulates the elapsed time
when a given binary signal has been high, see also figure 623.

BLOCK
RESET
IN Time Accumulation ACC_HOUR
ADDTIME with Retain
ACC_DAY
tAddToTime

q-1

OVERFLOW
a
&
a>b
99 999.9 h b

WARNING
a
&
a>b
tWarning b

ALARM
a
&
a>b
tAlarm b

q-1 = unit delay IEC15000321-1-en.vsd

IEC15000321 V1 EN-US

Figure 623: TEILGAPC logics


The main features of TEILGAPC are:

• Applicable to very long time accumulation (≤ 99999.9 hours)


• Supervision of limit transgression conditions and rollover/overflow
• Possibility to define a warning and alarm with the resolution of 0.1 hours
• Retain any saved accumulation value at a restart
• Possibilities for blocking and reset
• Possibility for manual addition of accumulated time
• Reporting of the accumulated time

18.11.3 Function block GUID-D0E9688B-C9D9-44B7-BD95-81132CCA5E4F v1

TEILGAPC
BLOCK ALARM
IN WARNING
ADDTIME OVERFLOW
RESET ACC_HOUR
ACC_DAY

IEC15000323.vsdx

IEC15000323 V1 EN-US

Figure 624: TEILGAPC function block

1058 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

18.11.4 Signals
PID-6998-INPUTSIGNALS v1

Table 866: TEILGAPC Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Freeze the accumulation and block the outputs
IN BOOLEAN 0 The input signal that is used to measure the elapsed time,
when its value is high
ADDTIME BOOLEAN 0 Add time to the accumulation
RESET BOOLEAN 0 Reset accumulated time

PID-6998-OUTPUTSIGNALS v1

Table 867: TEILGAPC Output signals


Name Type Description
ALARM BOOLEAN Indicator that accumulated time has reached alarm limit
WARNING BOOLEAN Indicator that accumulated time has reached warning limit
OVERFLOW BOOLEAN Indicator that accumulated time has reached overflow limit
ACC_HOUR REAL Accumulated time in hours
ACC_DAY REAL Accumulated time in days

18.11.5 Settings
PID-6998-SETTINGS v1

Table 868: TEILGAPC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
tAlarm 1.0 - 99999.9 Hour 0.1 90000.0 Time limit for alarm supervision
tWarning 1.0 - 99999.9 Hour 0.1 50000.0 Time limit for warning supervision
tAddToTime 0.0 - 99999.9 Hour 0.1 0.0 Time to add to the accumulation

18.11.6 Operation principle GUID-C7F91D4E-5942-4006-B7C8-4F499E7DC49D v3

Figure 625 describes the simplified logic of the function.

Line distance protection REL670 1059


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

Loop Delay

tWarning
OVERFLOW
tAlarm
Transgression Supervision WARNING
Plus Retain
ALARM

BLOCK
RESET ACC_HOUR
Time Accumulation
IN
ADDTIME ACC_DAY

tAddToTime

Loop Delay

IEC15000322.vsd

IEC15000322 V1 EN-US

Figure 625: TEILGAPC Simplified logic


TEILGAPC main functionalities

• IN: Accumulation of the elapsed time when input IN is high


• applicable to very long time accumulation (≤99999.9 hours)
• output ACC_HOUR presents accumulated value in hours and ACC_DAY presents
accumulated value in days
• accumulated value is retained in a non-volatile memory
• any retained value is used as initiation value for the integration following by a restart
• RESET: Reset of the accumulated value. Consequently all other outputs are also reset
• independent of the input IN value
• reset the value of the nonvolatile memory to zero.
Note that the nonvolatile memory will not reset to zero if the input IN is high during
the reset.
• reset can be made by activation of input RESET or from LHMI or with IEC 61850
command
• ADDTIME: Manually add time to the currently accumulated time
• the amount of time to be added is defined by a setting tAddToTime
• time is added through activation of input ADDTIME or from LHMI or with IEC 61850
command
• BLOCK: Freeze the accumulation and block/reset the other outputs
• independent of the input IN value
• BLOCK request overrides RESETrequest
• Monitor and report the conditions of limit transgression
• overflow if output ACC_HOUR > 99 999.9 hours
• alarm if output ACC_HOUR > tAlarm
• warning if output ACC_HOUR > tWarning

The ACC_HOURoutput represents the accumulated time in hours and the ACC_DAY output
represents the accumulated time in days.

tAlarm and tWarning are user settable time limit parameters in hours. They are also
independent of each other, that is, there is no check if tAlarm > tWarning.

1060 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

tAddToTime is a user settable time parameter in hours.

tAlarm, tWarning and tAddToTime are possible to be defined with a resolution of 0.1 hours (6
minutes).

The limit for the overflow supervision is fixed at 99999.9 hours. The outputs will reset and the
accumulated time will reset and start from zero if an overflow occurs.

18.11.6.1 Operation accuracy GUID-B6FBEFD7-17C8-41C6-B5D5-32E1205E6752 v1

The accuracy of TEILGAPC depends on essentially two factors

• the pulse length


• the number of pulses, that is, the number of rising and falling flank pairs

In principle, more pulses may lead to reduced accuracy.

18.11.6.2 Memory storage GUID-B49698FF-0AB2-4792-A7CB-5534313B6CA0 v2

The value of the accumulated time is retained in a non-volatile memory,

• at every falling edge of the input IN


• at every even 6 minutes, after a rising edge of the input IN
• after a manual addition of time

Consequently in case of a power failure, there is a risk of losing the difference in time between
actual time and last time stored in the non-volatile memory.

18.11.7 Technical data


GUID-F5E124E3-0B85-41AC-9830-A2362FD289F2 v1

Table 869: TEILGAPC Technical data


Function Range or value Accuracy
Time limit for alarm supervision, (0 - 99999.9) hours ±0.1% of set value
tAlarm
Time limit for warning supervision, (0 - 99999.9) hours ±0.1% of set value
tWarning
Time limit for overflow supervision Fixed to 99999.9 hours ±0.1%

18.12 Through fault monitoring PTRSTHR GUID-7AE60CB5-3CD5-4FE2-8D54-664AA78DD2DE v1

18.12.1 Identification
GUID-B62A30E5-C1F3-4E1F-B351-4F4CC60BA53F v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Through fault monitoring PTRSTHR - 51TF

Line distance protection REL670 1061


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

18.12.2 Functionality GUID-D5A0DC68-B3FD-4EBE-A5ED-68BE7DA20245 v1

The through fault monitoring function PTRSTHR is used to monitor the mechanical stress on a
transformer and place it against its designed withstand capability. During through faults, the
fault-current magnitude is higher as the allowed overload current range. At low fault current
magnitudes which are below the overload capability of the transformer, mechanical effects are
considered less important unless the frequency of fault occurrence is high. Since through fault
current magnitudes are typically closer to the extreme design capabilities of the transformer,
mechanical effects are more significant than thermal effects.

For other power system objects, for example, an over-head line, this function can be used to
make a log of all START and/or TRIP operations of the protection IED.

18.12.3 Function block GUID-EB4C73B5-6A8E-4F4F-AC37-390CD1A0AD2A v1

PTRSTHR
I3PW1* ALARM
I3PW2* W1L1ALM
I3PW3* W1L2ALM
U3P* W1L3ALM
BLOCK W2L1ALM
ACCFREEZE W2L2ALM
EXTTRIG W2L3ALM
INHIBIT W3L1ALM
RSTTFCNT W3L2ALM
RSTCMLI2T W3L3ALM
TAPOLTC1 MTFWRN
TAPOLTC2 I2TALM
CMLI2TALM
REPMADE

IEC18000072-1-en.vsdx
IEC18000072 V1 EN-US

Figure 626: PTRSTHR function block

18.12.4 Signals
PID-7144-INPUTSIGNALS v1

Table 870: PTRSTHR Input signals


Name Type Default Description
I3PW1 GROUP - Group signal for winding 1 currents
SIGNAL
I3PW2 GROUP - Group signal for winding 2 currents
SIGNAL
I3PW3 GROUP - Group signal for winding 3 currents
SIGNAL
U3P GROUP - Group signal for three phase voltage
SIGNAL
BLOCK BOOLEAN 0 Block of the function
ACCFREEZE BOOLEAN 0 Block accumulation values from incrementing
EXTTRIG BOOLEAN 0 External trigger to force fault (I^2)t calculation
INHIBIT BOOLEAN 0 Inhibit fault calculation, e.g. when transformer is energized
RSTTFCNT BOOLEAN 0 Reset all counters to initial value for all windings and phases
RSTCMLI2T BOOLEAN 0 Reset cumulated (I^2)t value to initial value for all windings
and phases
TAPOLTC1 INTEGER 1 Present tap position reading on OLTC 1
TAPOLTC2 INTEGER 1 Present tap position reading on OLTC 2

1062 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

PID-7144-OUTPUTSIGNALS v1

Table 871: PTRSTHR Output signals


Name Type Description
ALARM BOOLEAN General fault detection alarm
W1L1ALM BOOLEAN Fault detection alarm of winding 1, phase L1
W1L2ALM BOOLEAN Fault detection alarm of winding 1, phase L2
W1L3ALM BOOLEAN Fault detection alarm of winding 1, phase L3
W2L1ALM BOOLEAN Fault detection alarm of winding 2, phase L1
W2L2ALM BOOLEAN Fault detection alarm of winding 2, phase L2
W2L3ALM BOOLEAN Fault detection alarm of winding 2, phase L3
W3L1ALM BOOLEAN Fault detection alarm of winding 3, phase L1
W3L2ALM BOOLEAN Fault detection alarm of winding 3, phase L2
W3L3ALM BOOLEAN Fault detection alarm of winding 3, phase L3
MTFWRN BOOLEAN Multiple faults detected in short time
I2TALM BOOLEAN General fault (I^2)t alarm for an event
CMLI2TALM BOOLEAN General cumulative fault (I^2)t alarm
REPMADE BOOLEAN Report is ready for file transfer

18.12.5 Settings
PID-7144-SETTINGS v1

Table 872: PTRSTHR Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSelW1 1 - 12 - 1 1 Selection of one of the Global Base
Value groups, winding 1
GlobalBaseSelW2 1 - 12 - 1 1 Selection of one of the Global Base
Value groups, winding 2
GlobalBaseSelW3 1 - 12 - 1 1 Selection of one of the Global Base
Value groups, winding 3

Table 873: PTRSTHR Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
W1I> 50 - 1000 %IB 1 350 Current start value for fault detection
in % of IBase of winding 1
W2I> 50 - 1000 %IB 1 350 Current start value for fault detection
in % of IBase of winding 2
W3I> 50 - 1000 %IB 1 350 Current start value for fault detection
in % of IBase of winding 3
tMin 0.00 - 10.00 s 0.01 0.05 Minimum duration of fault to start any
calculation
MaxI2tW1 1.000 - (kA)²s 0.001 60.000 (I^2)t threshold limit for alarm of
360000.000 individual fault event in winding 1 per
phase
MaxI2tW2 1.000 - (kA)²s 0.001 200.000 (I^2)t threshold limit for alarm of
360000.000 individual fault event in winding 2 per
phase
Table continues on next page

Line distance protection REL670 1063


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

Name Values (Range) Unit Step Default Description


MaxI2tW3 1.000 - (kA)²s 0.001 40.000 (I^2)t threshold limit for alarm of
360000.000 individual fault event in winding 3 per
phase
MaxI2tCmlW1 1.000 - (kA)²s 0.001 600.000 Cumulative (I^2)t threshold limit for
1000000.000 alarm of all fault events in winding 1
per phase
MaxI2tCmlW2 1.000 - (kA)²s 0.001 2000.000 Cumulative (I^2)t threshold limit for
1000000.000 alarm of all fault events in winding 2
per phase
MaxI2tCmlW3 1.000 - (kA)²s 0.001 400.000 Cumulative (I^2)t threshold limit for
1000000.000 alarm of all fault events in winding 3
per phase
tMultiThroFlt 1 - 86400 s 1 3600 Time window to detect multiple faults
tPulse 0.1 - 10.0 s 0.1 0.2 Pulse duration for alarm signals

Table 874: PTRSTHR Non group settings (advanced)


Name Values (Range) Unit Step Default Description
InitTFCnt 0 - 1000 - 1 0 Initial value of overall fault counter
InitTFCntW1L1 0 - 1000 - 1 0 Initial value of fault counter of winding
1 phase L1
InitTFCntW1L2 0 - 1000 - 1 0 Initial value of fault counter of winding
1 phase L2
InitTFCntW1L3 0 - 1000 - 1 0 Initial value of fault counter of winding
1 phase L3
InitTFCntW2L1 0 - 1000 - 1 0 Initial value of fault counter of winding
2 phase L1
InitTFCntW2L2 0 - 1000 - 1 0 Initial value of fault counter of winding
2 phase L2
InitTFCntW2L3 0 - 1000 - 1 0 Initial value of fault counter of winding
2 phase L3
InitTFCntW3L1 0 - 1000 - 1 0 Initial value of fault counter of winding
3 phase L1
InitTFCntW3L2 0 - 1000 - 1 0 Initial value of fault counter of winding
3 phase L2
InitTFCntW3L3 0 - 1000 - 1 0 Initial value of fault counter of winding
3 phase L3
InitCmlI2tW1L1 0.000 - (kA)²s 0.001 0.000 Initial value of cumulative (I^2)t value
1000000.000 of winding 1 phase L1
InitCmlI2tW1L2 0.000 - (kA)²s 0.001 0.000 Initial value of cumulative (I^2)t value
1000000.000 of winding 1 phase L2
InitCmlI2tW1L3 0.000 - (kA)²s 0.001 0.000 Initial value of cumulative (I^2)t value
1000000.000 of winding 1 phase L3
InitCmlI2tW2L1 0.000 - (kA)²s 0.001 0.000 Initial value of cumulative (I^2)t value
1000000.000 of winding 2 phase L1
InitCmlI2tW2L2 0.000 - (kA)²s 0.001 0.000 Initial value of cumulative (I^2)t value
1000000.000 of winding 2 phase L2
InitCmlI2tW2L3 0.000 - (kA)²s 0.001 0.000 Initial value of cumulative (I^2)t value
1000000.000 of winding 2 phase L3
Table continues on next page

1064 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

Name Values (Range) Unit Step Default Description


InitCmlI2tW3L1 0.000 - (kA)²s 0.001 0.000 Initial value of cumulative (I^2)t value
1000000.000 of winding 3 phase L1
InitCmlI2tW3L2 0.000 - (kA)²s 0.001 0.000 Initial value of cumulative (I^2)t value
1000000.000 of winding 3 phase L2
InitCmlI2tW3L3 0.000 - (kA)²s 0.001 0.000 Initial value of cumulative (I^2)t value
1000000.000 of winding 3 phase L3

Table 875: PTRSTHR Group settings (advanced)


Name Values (Range) Unit Step Default Description
NoOfWindings Two winding - - Two winding Number of transformer windings
Three winding
ConnTypeW1 WYE (Y) - - WYE (Y) Connection type of winding 1
Delta (D)
ConnTypeW2 WYE (Y) - - WYE (Y) Connection type of winding 2
Delta (D)
ConnTypeW3 WYE (Y) - - Delta (D) Connection type of winding 3
Delta (D)
ZSCurrCor Off - - Off Enable or disable the zero sequence
On current correction for a single delta
winding
ClockNumberW2 0 [0 deg] - - 0 [0 deg] Phase displacement between W2 &
1 [30 deg lag] W1, hour notation
2 [60 deg lag]
3 [90 deg lag]
4 [120 deg lag]
5 [150 deg lag]
6 [180 deg]
7 [150 deg lead]
8 [120 deg lead]
9 [90 deg lead]
10 [60 deg lead]
11 [30 deg lead]
ClockNumberW3 0 [0 deg] - - 5 [150 deg lag] Phase displacement between W3 &
1 [30 deg lag] W1, hour notation
2 [60 deg lag]
3 [90 deg lag]
4 [120 deg lag]
5 [150 deg lag]
6 [180 deg]
7 [150 deg lead]
8 [120 deg lead]
9 [90 deg lead]
10 [60 deg lead]
11 [30 deg lead]
OLTCWinding Not in use - - Not in use Transformer winding where OLTC1,
W1 OLTC2 is located
W2
W3
W1, W2
W1, W3
W2, W1
W2, W3
W3, W1
W3, W2
RatedTapOLTC1 1 - 100 - 1 6 OLTC1 rated voltage tap position
designation
HighTapOLTC1 1 - 100 - 1 11 OLTC1 number of tap position at
maximum voltage
Table continues on next page

Line distance protection REL670 1065


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

Name Values (Range) Unit Step Default Description


LowTapOLTC1 1 - 100 - 1 1 OLTC1 number of tap position at
minimum voltage
StepSizeOLTC1 0.01 - 30.00 % 0.01 1.00 Voltage change per OLTC1 step in
percent of rated voltage
RatedTapOLTC2 1 - 100 - 1 6 OLTC1 rated voltage tap position
designation
HighTapOLTC2 1 - 100 - 1 11 OLTC2 number of tap position at
maximum voltage
LowTapOLTC2 1 - 100 - 1 1 OLTC2 number of tap position at
minimum voltage
StepSizeOLTC2 0.01 - 30.00 % 0.01 1.00 Voltage change per OLTC2 step in
percent of rated voltage

18.12.6 Monitored data


PID-7144-MONITOREDDATA v1

Table 876: PTRSTHR Monitored data


Name Type Values (Range) Unit Description
TFDUR REAL - s Last fault duration
TFCNT INTEGER - - Overall number of faults detected
since last reset
W1IP REAL - A Maximum peak current of winding 1
among all phases of the last event
W2IP REAL - A Maximum peak current of winding 2
among all phases of the last event
W3IP REAL - A Maximum peak current of winding 3
among all phases of the last event
W1IRMS REAL - A Maximum RMS current of winding 1
among all phases of the last event
W2IRMS REAL - A Maximum RMS current of winding 2
among all phases of the last event
W3IRMS REAL - A Maximum RMS current of winding 3
among all phases of the last event
I2TP REAL - % Maximum through fault (I^2)t in % of
set limit among all windings and
phases of last event
W1CMLIP REAL - A Maximum cumulative peak current of
winding 1 among all phases
W2CMLIP REAL - A Maximum cumulative peak current of
winding 2 among all phases
W3CMLIP REAL - A Maximum cumulative peak current of
winding 3 among all phases
CMLI2TP REAL - % Maximum cumulative through
fault(I^2)t in % of set limit among all
windings and phases
L1URMS REAL - kV Measured RMS voltage, phase L1
L2URMS REAL - kV Measured RMS voltage, phase L2
L3URMS REAL - kV Measured RMS voltage, phase L3
W1L1MIRMS REAL - A Measured RMS current of winding 1,
phase L1
Table continues on next page

1066 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

Name Type Values (Range) Unit Description


W1L2MIRMS REAL - A Measured RMS current of winding 1,
phase L2
W1L3MIRMS REAL - A Measured RMS current of winding 1,
phase L3
W2L1MIRMS REAL - A Measured RMS current of winding 2,
phase L1
W2L2MIRMS REAL - A Measured RMS current of winding 2,
phase L2
W2L3MIRMS REAL - A Measured RMS current of winding 2,
phase L3
W3L1MIRMS REAL - A Measured RMS current of winding 3,
phase L1
W3L2MIRMS REAL - A Measured RMS current of winding 3,
phase L2
W3L3MIRMS REAL - A Measured RMS current of winding 3,
phase L3

18.12.7 Operation principle GUID-55C86B69-66D5-4BB9-9C11-049BD7199F78 v1

The PTRSTHR function monitors the transformer during through fault and predicts the
degradation of its withstand capability. It detects the fault when the measured RMS current is
above the set threshold current limit. When the fault is detected, it calculates the I2t value for
the through fault duration with the calculated winding current. This calculation is triggered for
all individual events of through fault, winding-wise and in all phases. The function compares
the calculated I2t for each fault event with the set limit of I2t and an alarm is raised when the
limit is exceeded.

Similarly, the cumulative effect of through faults with the accumulated I2t is calculated
throughout the transformer lifetime. This cumulative I2t is compared with the set limit of ΣI2t
and an alarm is raised when the limit is exceeded.

Additionally, the function monitors the time between subsequent through faults against the
set time. If this time is shorter than the set time, then the multi-through faults in short time
detection warning is raised.

The function also reports the below monitoring parameters of each winding and phases:

• The maximum peak current during the fault


• The maximum RMS current during the fault
• The maximum peak current during all through fault duration
• Percentage degradation of transformer withstand capability with respect to the
calculated I2t
• Total percentage degradation of transformer withstand capability with respect to the
calculated ΣI2t
• Difference between subsequent through fault I2t values
• Number of through faults detected

This function can be used for both 2-winding and 3-winding transformer configurations with
maximum two on-line load tap changers. It calculates all required parameters for each through
faults and produces an individual report per event.

Line distance protection REL670 1067


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

18.12.7.1 Transformer winding currents calculation GUID-F0DD5908-B7A0-4DB3-9096-8392C2A2FE04 v1

Generally, line currents are measured by current transformers at the transformer terminals.
However, the winding current should be calculated and used to estimate the degradation of
withstand capability due to through faults. Winding currents calculation from line currents
depend upon the transformer connection type and the phase displacement between winding
currents. Therefore, winding current calculation is required to protect the transformer within
its capacity. On the other hand, CT measurements done at the windings do not require any
further derivations of the winding current.

Consider the Dy11 transformer configuration shown in Figure 627, where ia, ib and ic are delta
winding side line currents and iA, iB and iC are star winding side line currents.

ia iA

ic iB
ibc
ib iC
IEC18000073-1-en.vsdx
IEC18000073 V1 EN-US

Figure 627: Transformer configuration Dy11


In this example, both line currents and winding currents (phase) are equal in the star winding
side. The delta winding currents iac, ibc and ica are derived from the line currents ia, ib and ic.
Line currents at the delta side do not have zero sequence currents, which are present at the
star winding side in case of earth faults. In order to calculate the transformer through fault
withstand capability, these delta side winding currents are required to be calculated from the
measured currents. To perform this calculation, the number of windings is selected by the
NoOfWindings setting and the transformer winding configuration is selected by the
ConnTypeWx (where, x = winding number 1, 2 or 3) setting.

The winding current calculation requires voltage ratio information, which is dynamically
calculated from the present OLTC tap position. The tap position inputs TAPOLTC1 and
TAPOLTC2 can be driven from the tap changer supervision function (YLTC). The
RatedVoltageWx (where, x = winding number 1, 2 or 3) settings and settings corresponding to
OLTC1 and OLTC2 are required to calculate the voltage ratio. The placement of OLTC1 and
OLTC2 are selected using the OLTCWinding setting.

Table 877: Corresponding settings for OLTC parameters


Parameter Setting
Rated tap position RatedTapOLTC#1)
Minimum voltage tap position HighTapOLTC#
Maximum voltage tap position LowTapOLTC#
Step size StepSizeOLTC#

1) # = OLTC number 1 or 2

Phase displacement between the windings decides the direction of circulating zero sequence
current. The clock position of the phase displacement between winding 1 and winding 2 is set
using the ClockNumberW2 setting. Similarly, the clock position between winding 1 and winding
3 is set using the ClockNumberW3 setting.

1068 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

The zero sequence current correction can be enabled or disabled by selecting the ZSCurrCor
setting. If the ZSCurrCor setting is selected as On, then the zero sequence current which
circulates internally in the delta winding is estimated from the available winding currents and
used for further calculations. If the ZSCurrCor setting is selected as Off, then the zero
sequence current is considered as zero. The utility can select the ZSCurrCor setting as Off
when:

• All the windings are in WYE (Y) configuration


• Transformer has two or more windings in the delta configuration
• Winding current transformers are used (In this case, the ConnTypeWx settings should be
set as WYE)

The function internally calculates the winding RMS current and peak current from the
measured current samples and used for further calculations.

18.12.7.2 Through fault detection GUID-6F61907D-3B6C-45F7-A99F-128414DE34AD v1

Through faults are detected if the measured RMS current in any phase among all windings is
above the set limit. The user can set the limit with reference to the IEEE standard (3.5 times
Irated) or according to the transformer manufacturer specification. The settings for the
through fault detection threshold (W1I>, W2I> and W3I>) are given winding-wise.

In addition to the limit check, through fault detection is verified against the INHIBIT binary
input. The INHIBIT input can be connected, for example, from the transformer differential
protection TxWPDIF function which blocks the through fault detection in case of an internal
fault. Similarly, the function can be blocked during transformer energization inrush by
connecting the second harmonic blocking to the INHIBIT input.

If both conditions are through, then the persistence of the signal is checked for set minimum
time tMin value. Through fault is declared only when the signal persists for the minimum
duration and BLOCK or INHIBIT input are not high. The function resets the through fault
detection alarm output when the measured current goes below the set limit including
hysteresis limits.

The through fault detection alarm outputs, WxLyALM (x = winding number 1 to 3 and y = phase
L1, L2 or L3) are given for all windings phase-wise. Additionally, the function has a general
alarm to indicate through fault detection. Once the through fault detection alarm has raised,
the function starts to calculate the I2t.

Besides this, the binary input EXTTRIG is used to trigger the through fault withstand capability
calculations.

W1L1ALM

tMin
W1L1IRMS
OR t CalculationStart
OR
W1I>

tMin

EXTTRIG

IEC18000074-1-en.vsdx
IEC18000074 V1 EN-US

Figure 628: Through fault detection logic


In order to avoid the I2t calculation during any unwanted conditions, either the BLOCK or
INHIBIT inputs should be activated. Below cases describes the interoperability between
BLOCK, INHIBIT and I2t calculation:

Line distance protection REL670 1069


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

• If BLOCK or INHIBIT input is activated first and a fault is detected, then that particular
fault is discarded.
• If BLOCK or INHIBIT input is activated first and deactivated before confirming the
detected fault, then that particular fault is considered.
• If BLOCK or INHIBIT input is activated after the fault confirmation, then that particular
fault is not discarded.

18.12.7.3 Through fault duration and count of occurrence calculation GUID-362E172E-D08B-4939-AFE5-810F90FB4CB4 v1

The through fault withstand capacity is decided based on the fault current magnitude and
duration of the fault. The fault duration is calculated from the instant the measured RMS
current crosses the set threshold current limit to the through fault detection reset. The TFDUR
output gives the duration of through fault in seconds. The through fault detection alarm is
picked up after confirming the fault with a time delay of tMin. If the fault is not confirmed,
then the TFDUR output will not be updated.

Additionally, the function measures the time between transformers subsequent through fault
events. When this time difference is smaller than the tMultiThroFlt setting, then the function
issues a warning signal MTFWRN. The transformer manufacturer may indicate the maximum
number of through fault per time period in order to set the tMultiThroFlt setting.

The function counts the number of through faults for all windings and phases whenever a
through fault is detected. Also, the overall transformer through fault count is incremented by
one if any winding phase detects the fault. The fault count increment occurs after each fault
has been cleared.

The through fault counts can be reset to the default value by activating either the RSTTFCNT
binary input or the command input. The default values for each individual winding phase and
the overall transformer is set through the InitCmlTFCnt and InitTFCntWxLy parameters
respectively.

The binary input ACCFREEZE can be activated to stop incrementing through fault counters. In
order to control the function during the test mode, connect the PTRSTHR function block with
the TESTMODE function block, as shown in Figure 629.

PTRSTHR
I3PW1* ALARM
I3PW2* W1L1ALM
I3PW3* W1L2ALM
TESTMODE U3P* W1L3ALM
IED_TEST TEST BLOCK W2L1ALM
IED_TEST ACCFREEZE W2L2ALM
BLOCK EXTTRIG W2L3ALM
NOEVENT INHIBIT W3L1ALM
INPUT RSTTFCNT W3L2ALM
SETTING RSTCMLI2T W3L3ALM
IEC61850 TAPOLTC1 MTFWRN
TAPOLTC2 I2TALM
CMLI2TALM
REPMADE

IEC18000075-1-en.vsdx
IEC18000075 V1 EN-US

Figure 629: ACT configuration for test mode connection

1070 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

18.12.7.4 Through fault withstand capability calculation GUID-6F0B19EF-434C-47F2-9783-50EFB5762ED7 v1

The transformer is subjected to electrical and mechanical stress when a fault current flows
through it, which is more than the transformer overload current. In general, stress reduces the
transformer life and it becomes even worse when stress occurs due to through faults. Stress
can cause insulation damages, conductor displacement and overall it weakens the windings
and collapses their structure. Therefore, stress reduces the transformer withstand capability
throughout its lifetime. Degradation of the transformer withstand capability can be predicted
using the equation:

IECEQUATION18022 V1 EN-US (Equation 225)

Where,

I = Short circuit current

t = Duration of fault

k = Constant

Once the function detects a through fault based on the measured RMS current, it starts to
calculate I2t. The I2t calculation is based on the fault current instantaneous sample value and
the duration of the fault. If the fault is confirmed after the minimum time delay, then the I2t
calculation will be carried-out until the fault is cleared. If the fault is cleared before minimum
time delay, then the calculated I2t is discarded. This calculation is done for all windings and
phases individually and repeats for all individual faults.

The calculated I2t value is used to check whether the transformer is within its withstand
capability or not. This is monitored with respect to the maximum withstand capability set
limit. The I2t limits can be set winding-wise using MaxI2tW1, MaxI2tW2 and MaxI2tW3 settings
and this limit is applicable for all phases of the respective winding. If the calculated I2t value of
any winding crosses the corresponding set limit, then a general alarm I2TALM is raised. Once
the I2TALM alarm is raised, it resets after the set time tPulse.

Transformer through faults produces physical forces that cause insulation compression,
insulation wear, and friction-induced displacement in the winding. These effects are
cumulative and should be considered throughout the transformer lifetime. The damage
intensity from through faults depends on the current magnitude, fault duration, and the total
number of fault occurrences. Therefore, the function accumulates the calculated I2t value over
all through faults for winding and phase-wise.

The calculated cumulative ƩI2t values are used to check whether the transformer is within its
withstand capability or not. This is monitored with respect to the maximum cumulative
withstand capability set limit. The ƩI2t limits can be set winding-wise using MaxI2tCmlW1,
MaxI2tCmlW2 and MaxI2tCmlW3 settings and this limit is applicable for all phases of the
respective winding. If the calculated ƩI2t values of any winding cross the corresponding set
limit, then a general alarm CMLI2TALM is raised. Once the CMLI2TALM alarm is raised, it resets
only if the cumulative I2t values are reset to value below the set limit. In order to reset the ƩI2t
values to default, activate either the RSTCMLI2T binary input or the command input. Default
values for each individual winding phase is set using InitCmlI2tWxLy parameters.

Line distance protection REL670 1071


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

WxL1zRMS tMin
a ≥ b t Time  TFDUR
OR
WxI> accumulation
1 T WxLzTFCNT
tMin Ʃ 
0 F
EXTTRIG

RSTTFCNT

InitTFCntWxLz  T
F

WxLzISAMPLES 2 q‐1
a
T WxLzI2T
Ʃ 
SAMPLINGRATE F

0.0 T 0.0
F q‐1
I2TALM
a ≥ b
MaxI2tWx

÷  WxLzI2TP

100.0 WxLzCI2T
RSTTFCNT Ʃ 

InitTFCntWxLz  T
F

q‐1 CMLI2TALM
a ≥ b
MaxCmlI2tWx

÷  WxLzCI2TP

100.0

IEC18000076-1-en.vsdx

x – winding 1, 2 and 3
z – Phase L1, L2 and L3

IEC18000076 V1 EN-US

Figure 630: Through fault withstand capability calculation


Both I2t and ƩI2t values are limited to 3.6 e12 and the maximum fault duration for I2t calculation
is limited to 1 min. Additionally, the function performs a plausibility check on the measured
current samples prior to the calculation, which limits the maximum sample value as ±1e6 A.

18.12.7.5 Preparation of data for reporting GUID-75426B18-64EE-44A7-8EB4-21B8D8378CAD v1

The function monitors the following parameters which are related to through fault for all
windings and phases:

• Fault peak current


• Cumulative maximum peak fault current
• Fault RMS current
• Delta value of I2t between two subsequent through faults

The peak and RMS current are measured during the interval of through fault
period.

Additionally, the function gives the percentage degradation of withstand capability for
individual through faults and all faults as a cumulative effect.

The percentage degradation of withstand capability for the individual through fault event is
calculated as:

I 2 teventwise
Event-wise % degradation of withstand capability= 100
MaxI 2tWx
IECEQUATION18023 V1 EN-US (Equation 226)

Where,

1072 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

I2teventwise = Calculated I2t for an event of through fault

MaxI2Wx = xth winding maximum allowable withstand capability degradation during through
fault.

The total percentage degradation of withstand capability for the transformer is calculated as:

 I 2t
Total % degradation of withstand capability  100
MaxI 2tCmlWx
IECEQUATION18024 V1 EN-US (Equation 227)

Where,

ΣI2t = Calculated ΣI2t over all through faults

MaxI2tCmlWx = xth winding maximum allowable withstand capability degradation over all
through faults.

The function provides general outputs from all windings and phases, which is displayed in the
local HMI and monitoring tool apart from the through fault monitoring report. The general
data are calculated as the maximum value out of all available data. The maximum fault peak
current, maximum cumulative fault peak current, and maximum fault RMS current outputs are
derived for each winding as the maximum of respective winding all phase values. The event
wise % degradation and total % degradation of withstand capability outputs are derived as
the maximum value of all winding and phase values. In the through fault monitoring report, the
data is divided into two parts; general and winding wise for maximum 3 windings.

The function provides service values of measured current RMS values for each phase of all
windings. Also, it displays the measured RMS phase-to-earth voltage values for any one of the
windings (which is connected to the function block). The instantaneous RMS voltage values are
captured at one and a half power cycle delayed from the point of detected fault or the fault
detection reset, whichever is earlier. In order to indicate the report is ready for file transfer, the
function provides a binary output REPMADE, see Figure 631. The outputs given as ‘general
data’ and ‘winding wise for all phases’ in the through fault monitoring report are shown in
Table 878.

Table 878: Through fault monitoring report outputs


General data Winding wise for all phases
• Test mode status • Cumulative maximum peak • Number of faults
• Fault duration in current W1 • Event wise maximum peak current
seconds • Cumulative maximum peak • Event wise RMS current
• Overall number of current W2 • Event wise I2t
faults • Cumulative maximum peak • Event wise I2t in % of set limit
• Event wise maximum current W3 • Delta I2t compared to prior fault
peak current W1 • Cumulative I2t in % of set • Cumulative maximum peak current
• Event wise maximum limit • Cumulative I2t
peak current W2 • Event wise RMS voltage L1 • Cumulative I2t in % of set limit
• Event wise maximum (The winding is based on
peak current W3 the input connection to
• Event wise RMS U3P)
current W1 • Event wise RMS voltage L2
• Event wise RMS (The winding is based on
current W2 the input connection to
• Event wise RMS U3P)
current W3 • Event wise RMS voltage L3
• Event wise I2t in % of (The winding is based on
set limit the input connection to
U3P)
• Multiple faults warning

Line distance protection REL670 1073


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

The winding-wise data shows the fault phase values as calculated but other healthy phases will
show zero except peak and RMS values as calculated.

If two-winding configuration is used, then only winding 1 and winding 2 information are shown
in the report (winding 3 information will be hidden in the report). However, the general
information shows all windings data and it will show winding 3 data as zero in the case of two-
winding configuration.

U3P

I3PWx
TAPOLTC1
TAPOLTC2
NoOfWindings

ConnTypeWx

ZSCurrCor ALARM
Winding current  WxLzALM
ClockNumberW2
calculation MTFWRN
ClockNumberW3 I2TALM
OLTCWinding CMLI2TALM
REPMADE
RatedTapOLTCy
WxLzMIRMS
HighTapOLTCy WxIP
LowTapOLTCy WxIRMS
I2TP
StepSizeOLTCy
WxCIP
CI2TP
Fault I2t  TFTIME
EXTTRIG
calculation TFCNT
INHIBIT
WxLzTFCNT
WxI> WxLzIP
Through fault  WxLzIRMS Through fault 
tMin
detection WxLzI2T report 
BLOCK
WxLzI2TP
tPulse
WxLzDI2T
tMultiThroFlt WxLzCIP
WxLzCI2T
WxLzCI2TP
TFDUR
LzURMS
MaxI2tWx

MaxI2tCmlWx

InitCI2TWxLz

InitTFCntWxLz
RSTTFCNT
RSTCMLI2T

IEC18000077-1-en.vsdx
x – Winding 1, 2 and  3
z – Phase L1, L2 and  L3
IEC18000077 V1 EN-US

Figure 631: Simplified logic diagram for through fault monitoring PTRSTHR
Through fault reports can be viewed using the local HMI. As shown in Figure 632, the list of
saved through fault reports those are grouped based on the instance can be found on the local
HMI under Main menu/Measurements/Through fault reports.

IEC18000096-1-en.vsdx
IEC18000096 V1 EN-US

Figure 632: List of saved through fault reports


The local HMI mapped inputs can be displayed by entering each through fault report, see
Figure 633.

1074 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

IEC18000097-1-en.vsdx
IEC18000097 V1 EN-US

Figure 633: Report for one event


The through fault monitoring report can also be viewed in PCM600, using the through fault
monitoring tool, see Figure 634.

IEC18000098-1-en.vsdx
IEC18000098 V1 EN-US

Figure 634: Through fault monitoring tool

18.12.8 Technical data


GUID-3763D0D6-AD44-4C9B-91E4-050C0B63C7EA v1

Table 879: PTRSTHR technical data


Function Range or value Accuracy
Operate current (50-1000)% of IBase ±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir

Reset ratio > 95% at (50-1000)% of IBase –

Line distance protection REL670 1075


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

18.13 Current harmonic monitoring CHMMHAI GUID-692151F8-812B-4B32-AE86-E7A4E4B0101B v1

18.13.1 Identification
GUID-C7863D78-34DB-42E5-90FE-6483EDAAF319 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Current harmonic monitoring CHMMHAI ITHD ITHD

18.13.2 Functionality GUID-CD97D6CF-7343-416B-82D3-8352FFF9D73E v1

Current harmonic monitoring function CHMMHAI is used to monitor the current part of the
power quality of a system. It calculates the total harmonic distortion (THD) with respect to
fundamental signal amplitude, and the total demand distortion (TDD) with respect to
maximum demand load current. These indices indicate the current signal quality factor.

Additionally, the function is used to calculate the numerical multiple of rated frequency
harmonics amplitude and harmonic distortion upto the 5th order. It helps the user to know the
predominant harmonic frequencies order and their amplitudes present in the system. The
function also calculates the crest factor to indicate the effectiveness of the signal. All
calculations in the harmonic monitoring function are based on IEEE 1459 and IEEE 519
standards.

The current harmonic function monitors the harmonic distortion and demand distortion
values constantly. Whenever these value crosses their set limit levels, a warning signal will be
initiated. If the warning signal persists continuously for the set time, an alarm signal will be
generated.

18.13.3 Function block GUID-5165010F-A903-4D0F-8DE2-7AE03D80C94E v1

CHMMHAI
I3P* THDALM
BLOCK TDDALM
BLKALM 2NDHDALM
BLKWRN 3RDHDALM
4THHDALM
5THHDALM
THDWRN
TDDWRN
2NDHDWRN
3RDHDWRN
4THHDWRN
5THHDWRN
DCAMPL1
DCAMPL2
DCAMPL3
DCAMPN

IEC18000001‐1‐en.vsdx
IEC18000001 V1 EN-US

Figure 635: CHMMHAI function block

1076 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

18.13.4 Signals
PID-7121-INPUTSIGNALS v1

Table 880: CHMMHAI Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKALM BOOLEAN 0 Block alarm signals
BLKWRN BOOLEAN 0 Block warning signals

PID-7121-OUTPUTSIGNALS v1

Table 881: CHMMHAI Output signals


Name Type Description
THDALM BOOLEAN General alarm signal for total harmonic distortion
TDDALM BOOLEAN General alarm signal for total demand distortion
2NDHDALM BOOLEAN 2nd order harmonic distortion alarm signal (Max of 3 phase)
3RDHDALM BOOLEAN 3rd order harmonic distortion alarm signal (Max of 3 phase)
4THHDALM BOOLEAN 4th order harmonic distortion alarm signal (Max of 3 phase)
5THHDALM BOOLEAN 5th order harmonic distortion alarm signal (Max of 3 phase)
THDWRN BOOLEAN General warning signal for total harmonic distortion
TDDWRN BOOLEAN General warning signal for total demand distortion
2NDHDWRN BOOLEAN 2nd order harmonic distortion warning signal (Max of 3
phase)
3RDHDWRN BOOLEAN 3rd order harmonic distortion warning signal (Max of 3
phase)
4THHDWRN BOOLEAN 4th order harmonic distortion warning signal (Max of 3
phase)
5THHDWRN BOOLEAN 5th order harmonic distortion warning signal (Max of 3
phase)
DCAMPL1 REAL DC Component value of phase L1
DCAMPL2 REAL DC Component value of phase L2
DCAMPL3 REAL DC Component value of phase L3
DCAMPN REAL DC Component value of neutral

18.13.5 Settings
PID-7121-SETTINGS v1

Table 882: CHMMHAI Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

Line distance protection REL670 1077


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

Table 883: CHMMHAI Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
MaxLoadCurr 10.0 - 200.0 %IB 0.1 100.0 Maximum demand load current at PCC
for total demand distortion
calculation
WrnLimitTHD 2.5 - 100.0 % 0.1 5.0 Warning limit for percentage total
harmonic distortion value
tDelayAlmTHD 0.0 - 600.0 s 1.0 300.0 Time delay to alarm after warning for
total harmonic distortion
WrnLimitTDD 2.5 - 100.0 % 0.1 5.0 Warning limit for percentage total
demand distortion value
tDelayAlmTDD 0.0 - 600.0 s 1.0 300.0 Time delay to alarm after warning for
total demand distortion
WrnLimit2ndHD 2.5 - 100.0 % 0.1 3.5 Warning limit for percentage 2nd
order harmonic distortion value
tDelayAlm2ndHD 0.0 - 600.0 s 1.0 300.0 Time delay to alarm after warning for
2nd order harmonic distortion
WrnLimit3rdHD 2.5 - 100.0 % 0.1 3.0 Warning limit for percentage 3rd order
harmonic distortion value
tDelayAlm3rdHD 0.0 - 600.0 s 1.0 300.0 Time delay to alarm after warning for
3rd order harmonic distortion
WrnLimit4thHD 2.5 - 100.0 % 0.1 2.5 Warning limit for percentage 4th
order harmonic distortion value
tDelayAlm4thHD 0.0 - 600.0 s 1.0 300.0 Time delay to alarm after warning for
4th order harmonic distortion
WrnLimit5thHD 2.5 - 100.0 % 0.1 2.5 Warning limit for percentage 5th
order harmonic distortion value
tDelayAlm5thHD 0.0 - 600.0 s 1.0 300.0 Time delay to alarm after warning for
5th order harmonic distortion

18.13.6 Monitored data


PID-7121-MONITOREDDATA v1

Table 884: CHMMHAI Monitored data


Name Type Values (Range) Unit Description
THDL1 REAL - % Total harmonic distortion of phase L1
THDL2 REAL - % Total harmonic distortion of phase L2
THDL3 REAL - % Total harmonic distortion of phase L3
THDN REAL - % Total harmonic distortion of neutral
TDDL1 REAL - % Total demand distortion value of
phase L1
TDDL2 REAL - % Total demand distortion value of
phase L2
TDDL3 REAL - % Total demand distortion value of
phase L3
TDDN REAL - % Total demand distortion value of
neutral
2NDHD REAL - % 2nd order harmonic distortion (Max of
3 phase)
Table continues on next page

1078 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

Name Type Values (Range) Unit Description


3RDHD REAL - % 3rd order harmonic distortion (Max of
3 phase)
4THHD REAL - % 4th order harmonic distortion (Max of
3 phase)
5THHD REAL - % 5th order harmonic distortion (Max of
3 phase)
CFL1 REAL - - Crest factor of phase L1
CFL2 REAL - - Crest factor of phase L2
CFL3 REAL - - Crest factor of phase L3
CFN REAL - - Crest factor of neutral
TRMSL1 REAL - A True RMS value of phase L1
TRMSL2 REAL - A True RMS value of phase L2
TRMSL3 REAL - A True RMS value of phase L3
TRMSN REAL - A True RMS value of neutral
MEASFREQ REAL - Hz Measured frequency
FUNDL1 REAL - A Fundamental amplitude of phase L1
FUNDL2 REAL - A Fundamental amplitude of phase L2
FUNDL3 REAL - A Fundamental amplitude of phase L3
FUNDN REAL - A Fundamental amplitude of neutral
HAAMPL1 REAL - A Harmonic RMS value of phase L1
HAAMPL2 REAL - A Harmonic RMS value of phase L2
HAAMPL3 REAL - A Harmonic RMS value of phase L3
HAAMPN REAL - A Harmonic RMS value of neutral
DCAMPL1 REAL - A DC Component value of phase L1
DCAMPL2 REAL - A DC Component value of phase L2
DCAMPL3 REAL - A DC Component value of phase L3
DCAMPN REAL - A DC Component value of neutral
HA2NDAMP REAL - A 2nd order Harmonic RMS value (Max
of 3 phase)
HA3RDAMP REAL - A 3rd order Harmonic RMS value (Max of
3 phase)
HA4THAMP REAL - A 4th order Harmonic RMS value (Max of
3 phase)
HA5THAMP REAL - A 5th order Harmonic RMS value (Max of
3 phase)

18.13.7 Graphical display configurable data


GUID-F669DFF5-D999-4D6A-8BC7-4A0EA5870178 v1

Table 885: CHMMHAI Graphical display configurable data


Name Description
2NDHD 2nd order harmonic distortion
3RDHD 3rd order harmonic distortion
4THHD 4th order harmonic distortion
5THHD 5th order harmonic distortion
Table continues on next page

Line distance protection REL670 1079


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

Name Description
HAAMPL1 Harmonic RMS value of phase L1
HAAMPL2 Harmonic RMS value of phase L2
HAAMPL3 Harmonic RMS value of phase L3
HAAMPN Harmonic RMS value of neutral
MEASFREQ Measured frequency
TDDL1 Total demand distortion value of phase L1
TDDL2 Total demand distortion value of phase L2
TDDL3 Total demand distortion value of phase L3
TDDN Total demand distortion value of neutral
THDL1 Total harmonic distortion of phase L1
THDL2 Total harmonic distortion of phase L2
THDL3 Total harmonic distortion of phase L3
THDN Total harmonic distortion of neutral
TRMSL1 True RMS value of phase L1
TRMSL2 True RMS value of phase L2
TRMSL3 True RMS value of phase L3
TRMSN True RMS value of neutral
FUNDL1 Fundamental amplitude of phase L1
FUNDL2 Fundamental amplitude of phase L2
FUNDL3 Fundamental amplitude of phase L3
FUNDN Fundamental amplitude of neutral

18.13.8 Operation principle GUID-C9E8E0EA-DED7-40F3-9520-2276398881DF v1

The current harmonic monitoring function calculates the following power quality indices based
on the current input signal:

• Total Harmonic Distortion (THD) in percentage of fundamental component


• Individual Harmonic Distortion (IHD) in percentage of fundamental component
• Total Demand Distortion (TDD) in percentage of maximum load demand current
• Crest Factor (CF)

The harmonic function calculates fundamental signal magnitude and specific harmonic values
from 2nd to 5th orders of the given signal using FFT filter.

The main functionality of the harmonic monitoring function is to find the total harmonic
distortion (THD) for current signals. If the distorted voltage and current waveforms consist of
only harmonics, a measurement time interval kT (T = Cycle Time) enables the correct
measurement of RMS value. If the monitored waveform contains an interharmonic, then the
measurement time interval kT should be designed according to the minimum frequency signal
measurement. The time interval, which is required for an accurate measurement of RMS values
and power, is the least common multiple of the periods of the fundamental component and
the interharmonic component (i.e., kT = mTi ; Ti =1 / fi , where ‘fi’ is the interharmonic
frequency and ‘k’, ‘m’ are integer numbers). When the measurement time interval kT does not
include an integer number of periods Ti (i.e., kT ≠ mTi), the RMS value of the interharmonic is
inaccurate. This error is also reflected in the measurement accuracy of the total RMS value. If
at least one of the interharmonics of order h is an irrational number, then the observed
waveform is not periodic, commonly known as Nearly Periodic. In such a case, the
measurement time interval kT should be infinitely large in order to have a correct

1080 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

measurement of the RMS value or power. The larger the measurement time kT, the lesser the
significance of errors caused by interharmonics.

Figure 636 shows the envelopes of the maximum errors made when the RMS value of an
interharmonic is measured in function of the number of cycle’s m. For example, if m = 20, the
RMS value of the interharmonic will be measured with a maximum error of ± 0.2%. For the
accurate measurement of true RMS value and harmonic components amplitude, FFT filter
design is used for harmonic monitoring functionality.

2
1.6
1.2
MAXIMUM ERROR (%)

0.8
0.4
0
‐0.4
‐0.8
‐1.2
‐1.6
‐2
0 20 40 60 80 100 120
NUMBER OF CYCLES m
IEC17000205-1-en.vsdx
IEC17000205 V1 EN-US

Figure 636: Percent maximum error of RMS measurement versus number of cycles
Individual harmonic distortion is calculated only for 2nd to 5th harmonic orders. For simplicity,
maximum harmonic amplitude out of all phases is considered for monitoring and the same
value is considered for harmonic distortion calculation, warning and alarm conditions. Phase
wise harmonic values are available in the IEC 61850 data model. The overview diagram of
harmonic monitoring function is shown in Figure 637.

A FFT filter is used to calculate complex amplitude and frequency for the rated frequency, and
its harmonic components up to 5th order include DC component. The filter length is fixed to 1
second, which is 1024 samples at 1 kHz sampling for calculation in each execution of the FFT
filter. This gives an increased resolution on true RMS calculation upto interharmonic level.

The function calculates THD, IHD, TDD and CF using the derived quantities of the given signal.
The FFT filter tries to find the fundamental frequency in a frequency search range of ± 5 Hz
from the system rated frequency. If the fundamental frequency is not able to identify from the
measured signal, then it will not do any calculation.

In many cases, the traditional instrument transformers which are only designed
to have a high accuracy at rated frequency, are used for harmonic
measurements. This questions accuracy of the harmonic measurements and
the reliability of any compliance assessment. In this function, the measurement
accuracy level of instrument transformers are not considered.

The following sections describe how each power quality indices are calculated.

Line distance protection REL670 1081


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

18.13.8.1 Total harmonic distortion (THD) GUID-49B95C3B-76CB-4F99-AA63-720FD3A7C619 v1

The overall deviation of a distorted wave from its fundamental can be estimated using total
harmonic distortion (THD).

The total harmonic distortion of the current is as follows:

 2 
IH   I 
%THDI      1  *100
I1   I1  
 
IECEQUATION17019 V1 EN-US (Equation 228)

Where,
= Current true RMS value

= Current fundamental DFT magnitude

= Current harmonic magnitude (including interharmonics)

Harmonic RMS  HRMS
Calculation
FFT Filter
I3P (Input from SMAI) MEASFREQ
I3P FREQ
THDx
TRMS Total Harmonic 
Distortion 
FUND Calculation #HD
FundDFT
Harm2nd
Harm3rd
th
Harm4 THDALM
Individual 
th Harmonic 
Harm5 #HDALM
Distortion 
Calculation THDWRN
Blocking , Alarm 
and Warning 
#HDWRN
logic TDDALM
TDDWRN
Peak
DCComp
Total Demand 
Distortion 
Calculation
MaxLoadCurr
TDDx

Crest Factor  CFx
PEAK Calculation
DCAMPx

BLOCK

WrnLimit#HD

WrnLimitTHD
tDelayAlm#HD  Harmonic RMS Values HAAMPx
tDelayAlmTHD Individual Harmonic   HA#AMP
RMS Values
WrnLimitTDD
Fundamental  FUNDx
tDelayAlmTDD Values
BLKALM True RMS  TRMSx
Values
BLKWARN

x  –  Phase outputs L1 , L2, L3 and N
nd rd th  th
#  –  Harmonic order (2 , 3 , 4 and 5 )
IEC18000002-1-en.vsdx

IEC18000002 V1 EN-US

Figure 637: Simplified logic diagram for current harmonic monitoring CHMMHAI

18.13.8.2 Individual harmonic distortion (IHD) GUID-2B5D203F-9722-4F5F-A2E9-0743D6197A95 v1

The individual harmonic distortion is defined as the percentage of harmonics for order h with
respect to the fundamental frequency.

The individual harmonic distortion of the current for order h is as follows:

1082 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

Ih
% IHDI h  *100
I1
IECEQUATION17020 V1 EN-US (Equation 229)
Where, Ih = Current harmonic magnitude for the order h

Additionally, it calculates the maximum individual harmonic distortion value as the maximum
of all phase signals harmonic distortion. The individual harmonic distortion is used further in
warning and alarm logic.

18.13.8.3 Total demand distortion (TDD) GUID-753B43A5-133E-4F55-B610-7E9FFC34A03D v1

According to IEEE 519-1992 standard, the total effect of distortion in the current waveform at
the Point of Common Coupling PCC is measured by the index called total demand distortion
(TDD), as a percentage of the maximum demand current at the PCC. In other words, it is
defined as the ratio of the root-mean-square of the harmonic content, to the root-mean-
square of the maximum demand load current at the PCC. It is expressed as the percentage of
maximum demand load current.

I 
%TDD   H  *100
 IL 
IECEQUATION17050 V1 EN-US (Equation 230)

Where,

= 2 2 = Current harmonic magnitude


1

= Maximum demand load current

When the PCC is considered at the service entrance or utility metering point, the IEEE-519
standard recommends that the maximum demand load current (IL) be calculated as the
average current of the maximum demand for the preceding 12 months.

18.13.8.4 Crest factor (CF) GUID-C9ED45F0-F780-4E32-B117-7F6B11710D5C v1

Crest factor is the ratio between value of the peak current and its RMS value.

The crest factor of current is as follows:

I Peak
CFI 
I RMS
IECEQUATION17051 V1 EN-US (Equation 231)

Where,
= Current peak amplitude

= Current true RMS

18.13.8.5 Blocking and alarm logic GUID-800D9E0F-F89D-4FCD-BEBA-F2C83F28409F v1

It is possible to set warning limits for each individual harmonic order. If the calculated
individual harmonic distortion exceeds beyond the warning limit, an individual harmonic
warning will be raised. Also, the user can set the time delay to alarm for the individual

Line distance protection REL670 1083


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

harmonic distortion value. If the IHD value sustains above the warning limit for the set time, an
alarm signal will be raised.

Similarly, total harmonic distortion and total demand distortion have separate settings for
warning limit and alarm time delay. Once the THD or TDD value exceeds beyond set warning
limit, a separate warning signal will be raised. If the warning signal sustains above the time set
at alarm time delay setting, an individual alarm signal will be raised.

The phase-wise alarm and warning signals with respect to total harmonic distortion is
provided through IEC 61850 communication protocol (general alarm and general warning are
also provided). Warning and alarm based on individual harmonic distortion are activated for
specific harmonic order outputs of alarm and warning. To avoid oscillations of warning signals
at boundary conditions, a hysteresis has been included.

When the BLOCK input is activated, all binary outputs will be forced to reset. Also, the alarm
outputs and warning outputs can be separately blocked by activating the BLKALM and
BLKWRN inputs, respectively.

BLOCK
BLKWARN
BLKALM

Total Harmonic 
Distortion
a
a > b AND
THDWRN
b

WrnLimitTHD tOff
t AND
THDALM

tDelayAlmTHD

Individual Harmonic 
Distortion 
(Max of phase wise 
a
a > b AND
#HDWRN
harmonic distortion) b

WrnLimit#HD tOff
#HDALM
t AND

tDelayAlmIHD #

Total Demand 
Distortion 
a
a > b AND
TDDWRN
b

WrnLimitTDD tOff
t AND
TDDALM

tDelayAlmTDD

IEC17000207-1-en.vsdx
IEC17000207 V1 EN-US

Figure 638: Simplified logic diagram for warning and alarm

18.13.9 Technical data


GUID-09EC65AC-C60B-4256-A601-FE2CC90D26EC v1

Table 886: CHMMHAI (50/60 Hz) technical data


Function Range or value Accuracy
Fundamental Harmonic
Frequency (0.95 - 1.05) X fr 2nd order to 5th order (0.1 - 0.5) X Ir ± 2 mHz
True RMS (0.1 to 1) X Ir None ± 0.5%
1 X Ir 2nd order to 5th order (0.1 - 0.5) X Ir ± 2%
Table continues on next page

1084 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

Function Range or value Accuracy


Fundamental Harmonic
Fundamental (0.1 to 1) X Ir None ± 0.5%
1 X Ir 2nd order to 5th order (0.1 - 0.5) X Ir ± 0.5%
Crest Factor (0.1 to 1) X Ir None ± 2%
Harmonic (0.1 to 1) X Ir 2nd order to 5th order (0.1 - 0.5) X Ir ± 5%
Amplitude
Total Demand (0.1 to 1) X Ir 2nd order to 5th order (0.1 - 0.5) X Ir ± 6%
Distortion (TDD)
Total Harmonic (0.1 to 1) X Ir 2nd order to 5th order (0.1 - 0.5) X Ir ± 6%
Distortion (ITHD)

18.14 Voltage harmonic monitoring VHMMHAI GUID-B2F24353-AAEA-4520-BB1C-5FD5FFCFC67B v1

18.14.1 Identification
GUID-BF90E93F-C0F4-43F7-BDD5-F3C289B5535B v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Voltage harmonic monitoring VHMMHAI UTHD VTHD

18.14.2 Functionality GUID-868ED1BB-A921-45DE-94C4-0CF23ECD9ADA v1

Voltage harmonic monitoring function VHMMHAI is used to monitor the voltage part of the
power quality of a system. It calculates the total harmonic distortion (THD) with respect to the
fundamental signal amplitude which indicates the voltage signal quality factor.

Additionally, the function is used to calculate the numerical multiple of rated frequency
harmonics amplitude and harmonic distortion upto the 5th order. It helps the user to know the
predominant harmonic frequencies order and their amplitudes present in the system. The
function also calculates the crest factor to indicate the effectiveness of the signal. All
calculations in the harmonic monitoring function are based on IEEE 1459 and IEEE 519
standards.

The voltage harmonic function monitors the harmonic distortion value constantly. Whenever
these value crosses their set limit levels, a warning signal will be initiated. If the warning signal
persists continuously for the set time, an alarm signal will be generated.

Line distance protection REL670 1085


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

18.14.3 Function block GUID-60BEA940-7577-471C-A7E3-64D1E65CA824 v1

VHMMHAI
U3P* THDALM
BLOCK 2NDHDALM
BLKALM 3RDHDALM
BLKWRN 4THHDALM
5THHDALM
THDWRN
2NDHDWRN
3RDHDWRN
4THHDWRN
5THHDWRN
DCAMPL1
DCAMPL2
DCAMPL3
DCAMPN
DCAMPL1L2
DCAMPL2L3
DCAMPL3L1

IEC18000003-1-en.vsdx
IEC18000003 V1 EN-US

Figure 639: VHMMHAI function block

18.14.4 Signals
PID-7123-INPUTSIGNALS v1

Table 887: VHMMHAI Input signals


Name Type Default Description
U3P GROUP - Group signal for voltagee input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKALM BOOLEAN 0 Block alarm signals
BLKWRN BOOLEAN 0 Block warning signals

PID-7123-OUTPUTSIGNALS v1

Table 888: VHMMHAI Output signals


Name Type Description
THDALM BOOLEAN General alarm signal for total harmonic distortion
2NDHDALM BOOLEAN 2nd order harmonic distortion alarm signal (Max of 3 phase)
3RDHDALM BOOLEAN 3rd order harmonic distortion alarm signal (Max of 3 phase)
4THHDALM BOOLEAN 4th order harmonic distortion alarm signal (Max of 3 phase)
5THHDALM BOOLEAN 5th order harmonic distortion alarm signal (Max of 3 phase)
THDWRN BOOLEAN General warning signal for total harmonic distortion
2NDHDWRN BOOLEAN 2nd order harmonic distortion warning signal (Max of 3
phase)
3RDHDWRN BOOLEAN 3rd order harmonic distortion warning signal (Max of 3
phase)
4THHDWRN BOOLEAN 4th order harmonic distortion warning signal (Max of 3
phase)
5THHDWRN BOOLEAN 5th order harmonic distortion warning signal (Max of 3
phase)
DCAMPL1 REAL DC Component value of phase L1
DCAMPL2 REAL DC Component value of phase L2
Table continues on next page

1086 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

Name Type Description


DCAMPL3 REAL DC Component value of phase L3
DCAMPN REAL DC Component value of neutral
DCAMPL1L2 REAL DC Component value of phase to phase L1L2
DCAMPL2L3 REAL DC Component value of phase to phase L2L3
DCAMPL3L1 REAL DC Component value of phase to phase L3L1

18.14.5 Settings
PID-7123-SETTINGS v1

Table 889: VHMMHAI Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

Table 890: VHMMHAI Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
WrnLimitTHD 2.5 - 100.0 % 0.1 5.0 Warning limit for percentage total
harmonic distortion value
tDelayAlmTHD 0.0 - 600.0 s 1.0 300.0 Time delay to alarm after warning for
total harmonic distortion
WrnLimit2ndHD 2.5 - 100.0 % 0.1 3.5 Warning limit for percentage 2nd
order harmonic distortion value
tDelayAlm2ndHD 0.0 - 600.0 s 1.0 300.0 Time delay to alarm after warning for
2nd order harmonic distortion
WrnLimit3rdHD 2.5 - 100.0 % 0.1 3.0 Warning limit for percentage 3rd order
harmonic distortion value
tDelayAlm3rdHD 0.0 - 600.0 s 1.0 300.0 Time delay to alarm after warning for
3rd order harmonic distortion
WrnLimit4thHD 2.5 - 100.0 % 0.1 2.5 Warning limit for percentage 4th
order harmonic distortion value
tDelayAlm4thHD 0.0 - 600.0 s 1.0 300.0 Time delay to alarm after warning for
4th order harmonic distortion
WrnLimit5thHD 2.5 - 100.0 % 0.1 2.5 Warning limit for percentage 5th
order harmonic distortion value
tDelayAlm5thHD 0.0 - 600.0 s 1.0 300.0 Time delay to alarm after warning for
5th order harmonic distortion

Line distance protection REL670 1087


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

18.14.6 Monitored data


PID-7123-MONITOREDDATA v1

Table 891: VHMMHAI Monitored data


Name Type Values (Range) Unit Description
THDL1 REAL - % Total harmonic distortion of phase L1
THDL2 REAL - % Total harmonic distortion of phase L2
THDL3 REAL - % Total harmonic distortion of phase L3
THDN REAL - % Total harmonic distortion of neutral
THDL1L2 REAL - % Total harmonic distortion of phase to
phase L1L2
THDL2L3 REAL - % Total harmonic distortion of phase to
phase L2L3
THDL3L1 REAL - % Total harmonic distortion of phase to
phase L3L1
2NDHD REAL - % 2nd order harmonic distortion (Max of
3 phase)
3RDHD REAL - % 3rd order harmonic distortion (Max of
3 phase)
4THHD REAL - % 4th order harmonic distortion (Max of
3 phase)
5THHD REAL - % 5th order harmonic distortion (Max of
3 phase)
CFL1 REAL - - Crest factor of phase L1
CFL2 REAL - - Crest factor of phase L2
CFL3 REAL - - Crest factor of phase L3
CFN REAL - - Crest factor of neutral
CFL1L2 REAL - - Crest factor of phase to phase L1L2
CFL2L3 REAL - - Crest factor of phase to phase L2L3
CFL3L1 REAL - - Crest factor of phase to phase L3L1
TRMSL1 REAL - kV True RMS value of phase L1
TRMSL2 REAL - kV True RMS value of phase L2
TRMSL3 REAL - kV True RMS value of phase L3
TRMSN REAL - kV True RMS value of neutral
TRMSL1L2 REAL - kV True RMS value of phase to phase L1L2
TRMSL2L3 REAL - kV True RMS value of phase to phase
L2L3
TRMSL3L1 REAL - kV True RMS value of phase to phase L3L1
MEASFREQ REAL - Hz Measured frequency
FUNDL1 REAL - kV Fundamental amplitude of phase L1
FUNDL2 REAL - kV Fundamental amplitude of phase L2
FUNDL3 REAL - kV Fundamental amplitude of phase L3
FUNDN REAL - kV Fundamental amplitude of neutral
FUNDL1L2 REAL - kV Fundamental amplitude of phase to
phase L1L2
FUNDL2L3 REAL - kV Fundamental amplitude of phase to
phase L2L3
Table continues on next page

1088 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

Name Type Values (Range) Unit Description


FUNDL3L1 REAL - kV Fundamental amplitude of phase to
phase L3L1
HAAMPL1 REAL - kV Harmonic RMS value of phase L1
HAAMPL2 REAL - kV Harmonic RMS value of phase L2
HAAMPL3 REAL - kV Harmonic RMS value of phase L3
HAAMPN REAL - kV Harmonic RMS value of neutral
HAAMPL1L2 REAL - kV Harmonic RMS value of phase to
phase L1L2
HAAMPL2L3 REAL - kV Harmonic RMS value of phase to
phase L2L3
HAAMPL3L1 REAL - kV Harmonic RMS value of phase to
phase L3L1
DCAMPL1 REAL - kV DC Component value of phase L1
DCAMPL2 REAL - kV DC Component value of phase L2
DCAMPL3 REAL - kV DC Component value of phase L3
DCAMPN REAL - kV DC Component value of neutral
DCAMPL1L2 REAL - kV DC Component value of phase to
phase L1L2
DCAMPL2L3 REAL - kV DC Component value of phase to
phase L2L3
DCAMPL3L1 REAL - kV DC Component value of phase to
phase L3L1
HA2NDAMP REAL - kV 2nd order Harmonic RMS value (Max
of 3 phase)
HA3RDAMP REAL - kV 3rd order Harmonic RMS value (Max of
3 phase)
HA4THAMP REAL - kV 4th order Harmonic RMS value (Max of
3 phase)
HA5THAMP REAL - kV 5th order Harmonic RMS value (Max of
3 phase)

18.14.7 Graphical display configurable data


GUID-4C6C76EC-9E19-4A78-B2F5-6B6FEC6DF165 v1

Table 892: VHMMHAI Graphical display configurable data


Name Description
2NDHD 2nd order harmonic distortion
3RDHD 3rd order harmonic distortion
4THHD 4th order harmonic distortion
5THHD 5th order harmonic distortion
HAAMPL1 Harmonic RMS value of phase L1
HAAMPL2 Harmonic RMS value of phase L2
HAAMPL3 Harmonic RMS value of phase L3
HAAMPN Harmonic RMS value of neutral
HAAMPL1L2 Harmonic RMS value of phase to phase L1L2
HAAMPL2L3 Harmonic RMS value of phase to phase L2L3
Table continues on next page

Line distance protection REL670 1089


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

Name Description
HAAMPL3L1 Harmonic RMS value of phase to phase L3L1
MEASFREQ Measured frequency
THDL1 Total harmonic distortion of phase L1
THDL2 Total harmonic distortion of phase L2
THDL3 Total harmonic distortion of phase L3
THDN Total harmonic distortion of neutral
THDL1L2 Total harmonic distortion of phase to phase L1L2
THDL2L3 Total harmonic distortion of phase to phase L2L3
THDL3L1 Total harmonic distortion of phase to phase L3L1
TRMSL1 True RMS value of phase L1
TRMSL2 True RMS value of phase L2
TRMSL3 True RMS value of phase L3
TRMSN True RMS value of neutral
TRMSL1L2 True RMS value of phase to phase L1L2
TRMSL2L3 True RMS value of phase to phase L2L3
TRMSL3L1 True RMS value of phase to phase L3L1
FUNDL1 Fundamental amplitude of phase L1
FUNDL2 Fundamental amplitude of phase L2
FUNDL3 Fundamental amplitude of phase L3
FUNDN Fundamental amplitude of neutral
FUNDL1L2 Fundamental amplitude of phase to phase L1L2
FUNDL2L3 Fundamental amplitude of phase to phase L2L3
FUNDL3L1 Fundamental amplitude of phase to phase L3L1

18.14.8 Operation principle GUID-2799ED97-DBA6-447A-BCFA-C4AF0BE6964E v1

The voltage harmonic monitoring function calculates the following power quality indices
based on the voltage input signal:

• Total Harmonic Distortion (THD) in percentage of fundamental component


• Individual Harmonic Distortion (IHD) in percentage of fundamental component
• Crest Factor (CF)

The harmonic function calculates fundamental signal magnitude and specific harmonic values
from 2nd to 5th orders of the given signal using a FFT filter.

The main functionality of the harmonic monitoring function is to find the total harmonic
distortion (THD) for voltage signals. If the distorted voltage and current waveforms consist of
only harmonics, a measurement time interval kT (T = Cycle Time) enables the correct
measurement of RMS value. If the monitored waveform contains an interharmonic, then the
measurement time interval kT should be designed according to the minimum frequency signal
measurement. The time interval, which is required for an accurate measurement of RMS values
and power, is the least common multiple of the periods of the fundamental component and
the interharmonic component (i.e., kT = mTi ; Ti =1 / fi , where ‘fi’ is the interharmonic
frequency and ‘k’, ‘m’ are integer numbers). When the measurement time interval kT does not
include an integer number of periods Ti (i.e., kT ≠ mTi), the RMS value of the interharmonic is
inaccurate. This error is also reflected in the measurement accuracy of the total RMS value. If
at least one of the interharmonics of order h is an irrational number, then the observed

1090 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

waveform is not periodic, commonly known as Nearly Periodic. In such a case, the
measurement time interval kT should be infinitely large in order to have a correct
measurement of the RMS value or power. The larger the measurement time kT, the lesser the
significance of errors caused by interharmonics.

Figure 640 shows the envelopes of the maximum errors made when the RMS value of an
interharmonic is measured in function of the number of cycle’s m. For example, if m = 20, the
RMS value of the interharmonic will be measured with a maximum error of ± 0.2%. For the
accurate measurement of true RMS value and harmonic components amplitude, FFT filter
design is used for harmonic monitoring functionality.

2
1.6
1.2
MAXIMUM ERROR (%)

0.8
0.4
0
‐0.4
‐0.8
‐1.2
‐1.6
‐2
0 20 40 60 80 100 120
NUMBER OF CYCLES m
IEC17000205-1-en.vsdx
IEC17000205 V1 EN-US

Figure 640: Percent maximum error of RMS measurement versus number of cycles
Individual harmonic distortion is calculated only for 2nd to 5th harmonic orders. For simplicity,
maximum harmonic amplitude out of all phases is considered for monitoring and the same
value is considered for harmonic distortion calculation, warning and alarm conditions. Phase
wise harmonic values are available in the IEC 61850 data model. The overview diagram of
harmonic monitoring function is shown in Figure 641.

A FFT filter is used to calculate complex amplitude and frequency for the rated frequency, and
its harmonic components up to 5th order includes DC component. The filter length is fixed to 1
second, which is 1024 samples at 1 kHz sampling for calculation in each execution of the FFT
filter. This gives an increased resolution on true RMS calculation upto interharmonic level.

The function calculates THD, IHD and CF using the derived quantities of the given signal. The
FFT filter tries to find the fundamental frequency in a frequency search range of ± 5 Hz from
the system rated frequency. If the fundamental frequency is not able to identify from the
measured signal, then it will not do any calculation.

In many cases, the traditional instrument transformers which are only designed
to have a high accuracy at rated frequency, are used for harmonic
measurements. This questions accuracy of the harmonic measurements and
the reliability of any compliance assessment. In this function, the measurement
accuracy level of instrument transformers are not considered.

The following sections describe how each power quality indices are calculated.

Line distance protection REL670 1091


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

18.14.8.1 Total harmonic distortion (THD) GUID-037ED9E1-8E21-455B-9DA0-F7914A97B3D7 v1

The overall deviation of a distorted wave from its fundamental can be estimated using total
harmonic distortion (THD).

The total harmonic distortion of the voltage is as follows:

 2 
VH   V 
%THDV      1  *100
V1   V1  
 
IECEQUATION17058 V1 EN-US (Equation 232)

Where,
= Voltage true RMS value

= Voltage fundamental DFT magnitude

= Voltage harmonic magnitude (including interharmonics)

FFT Filter MEASFREQ
V3P ( Input from SMAI)
V3P FREQ
THDx
TRMS Total Harmonic 
THDxx
Distortion 
FUND Calculation #HD
FundDFT
nd
Harm2
Harm3rd
Harm4th THDALM
Individual 
Harm5th Harmonic 
Distortion 
#HDALM
Calculation THDWRN
Blocking,  Alarm 
and Warning  #HDWRN
logic

Peak
DCComp

CFx
Crest Factor 
PEAK Calculation CFxx
DCAMPx
DCAMPxx

BLOCK

WrnLimit#HD
HAAMPx
  Harmonic RMS Values
WrnLimitTHD HAAMPxx
tDelayAlmIHD# Individual Harmonic   HA #AMP
RMS Values
tDelayAlmTHD FUNDx
Fundamental 
Values FUNDxx
BLKALM TRMSx
True RMS 
BLKWARN Values TRMSxx

x  –  Phase outputs (L1 , L2 , L 3 andN)


xx  –  Phase to Phase Outputs (L1L2, L2L3 and L3L1)
#  –  Harmonic order (2nd , 3rd , 4th and 5th ) IEC18000004-1-en.vsdx

IEC18000004 V1 EN-US

Figure 641: Simplified logic diagram for voltage harmonic monitoring VHMMHAI

18.14.8.2 Individual harmonic distortion (IHD) GUID-8DFC8603-2C3B-402F-9774-93D9E166938B v2

The individual harmonic distortion is defined as the percentage of harmonics for order h with
respect to the fundamental frequency.

The individual harmonic distortion of the voltage for order h is as follows:

1092 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 18
Monitoring

Vh
% IHDV h  *100
V1
IECEQUATION17059 V1 EN-US (Equation 233)
Where, Vh = Voltage harmonic magnitude for the order h

Additionally, it calculates the maximum individual harmonic distortion value as the maximum
of three phase signals harmonic distortion.Additionally, it calculates the maximum individual
harmonic distortion value as the maximum of two phase signals harmonic distortion. The
individual harmonic distortion is used further in warning and alarm logic.

18.14.8.3 Crest factor (CF) GUID-11E60216-E7DB-42DB-872C-8B1E53D7D30A v1

Crest factor is the ratio between value of the peak voltage and its RMS value.

The crest factor of voltage is as follows:


VPeak
CFV 
VRMS
IECEQUATION17060 V1 EN-US (Equation 234)

Where,
= Voltage peak amplitude

= Voltage true RMS

18.14.8.4 Blocking and alarm logic GUID-56FFB124-6F86-41FA-B34F-61C7D4CD5720 v1

It is possible to set warning limits for each individual harmonic order. If the calculated
individual harmonic distortion exceeds beyond the warning limit, an individual harmonic
warning will be raised. Also, the user can set the time delay to alarm for the individual
harmonic distortion value. If the IHD value sustains above the warning limit for the set time, an
alarm signal will be raised.

Similarly, total harmonic distortion has separate settings for warning limit and alarm time
delay. Once the THD value exceeds beyond set warning limit, a separate warning signal will be
raised. If the warning signal sustains above the time set at alarm time delay setting, an
individual alarm signal will be raised.

The phase-wise alarm and warning signals with respect to total harmonic distortion is
provided through IEC 61850 communication protocol (general alarm and general warning are
also provided). In case of phase-to-phase measurement, once the THD exceeded the limits,
both phase warning and alarm signals will be activated. Warning and alarm based on individual
harmonic distortion are activated for specific harmonic order outputs of alarm and warning.
To avoid oscillations of warning signals at boundary conditions, a hysteresis has been
included.

When the BLOCK input is activated, all binary outputs will be forced to reset. Also, the alarm
outputs and warning outputs can be separately blocked by activating the BLKALM and
BLKWRN inputs, respectively.

Line distance protection REL670 1093


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 506 370-UEN J
Monitoring

BLOCK
BLKWARN
BLKALM

Total Harmonic 
Distortion
a
a > b AND
THDWRN
b

WarnLimitTHD tOff
t AND
THDALM

tDelayAlmTHD

Individual Harmonic 
Distortion 
a #HDWRN
(Max of phase wise  a > b AND
harmonic distortion) b

WarnLimitIHD# tOff
#HDALM
t AND

tDelayAlmIHD #

IEC17000207-1-en.vsdx
IEC17000211 V1 EN-US

Figure 642: Simplified logic diagram for warning and alarm

18.14.9 Technical data


GUID-2068BBA0-9026-48D0-9DEB-301BCB3C600C v1

Table 893: VHMMHAI (50/60 Hz) technical data


Function Range or value Accuracy
Fundamental Harmonic
Frequency (0.95 - 1.05) X fr 2nd order to 5th order (0.1 - 0.5) X V ± 2 mHz
True RMS (10 to 150) V None ± 0.5%
(10 to 150) V 2nd order to 5th order (0.1 - 0.5) X V ± 2%
Fundamental (10 to 150) V None ± 0.5%
(10 to 150) V 2nd order to 5th order (0.1 - 0.5) X V ± 0.5%
Crest Factor (10 to 150) V None ± 2%
Harmonic (10 to 150) V 2nd order to 5th order (0.1 - 0.5) X V ± 4%
Amplitude
Total Harmonic (10 to 150) V 2nd order to 5th order (0.1 - 0.5) X V ± 4%
Distortion
(VTHD)

1094 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 19
Metering

Section 19 Metering
19.1 Pulse-counter logic PCFCNT IP14600-1 v3

19.1.1 Identification
M14879-1 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Pulse-counter logic PCFCNT -

S00947 V1 EN-US

19.1.2 Functionality M13394-3 v7

Pulse-counter logic (PCFCNT) function counts externally generated binary pulses, for instance
pulses coming from an external energy meter, for calculation of energy consumption values.
The pulses are captured by the binary input module and then read by the PCFCNT function. A
scaled service value is available over the station bus. The special Binary input module with
enhanced pulse counting capabilities must be ordered to achieve this functionality.

19.1.3 Function block M13400-3 v5

PCFCNT
BLOCK INVALID
READ_VAL RESTART
BI_PULSE* BLOCKED
RS_CNT NEW_VAL
SCAL_VAL

IEC14000043-1-en.vsd
IEC09000335 V3 EN-US

Figure 643: PCFCNT function block

19.1.4 Signals
PID-6509-INPUTSIGNALS v4

Table 894: PCFCNT Input signals


Name Type Default Description
BI_PULSE BOOLEAN 0 Connect binary input channel for metering
BLOCK BOOLEAN 0 Block of function
READ_VAL BOOLEAN 0 Initiates an additional pulse counter reading
RS_CNT BOOLEAN 0 Resets pulse counter value

Line distance protection REL670 1095


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 19 1MRK 506 370-UEN J
Metering

PID-6509-OUTPUTSIGNALS v4

Table 895: PCFCNT Output signals


Name Type Description
INVALID BOOLEAN The pulse counter value is invalid
RESTART BOOLEAN The reported value does not comprise a complete integration
cycle
BLOCKED BOOLEAN The pulse counter function is blocked
NEW_VAL BOOLEAN A new pulse counter value is generated
SCAL_VAL REAL Scaled value with time and status information

19.1.5 Settings
PID-6509-SETTINGS v4

Table 896: PCFCNT Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
EventMask NoEvents - - NoEvents Report mask for analog events from
ReportEvents pulse counter
CountCriteria Off - - RisingEdge Pulse counter criteria
RisingEdge
Falling edge
OnChange
Scale 1.000 - - 0.001 1.000 Scaling value for SCAL_VAL output to
90000.000 unit per counted value
Quantity Count - - Count Measured quantity for SCAL_VAL
ActivePower output
ApparentPower
ReactivePower
ActiveEnergy
ApparentEnergy
ReactiveEnergy
tReporting 0 - 3600 s 1 60 Cycle time for reporting of counter
value

19.1.6 Monitored data


PID-6509-MONITOREDDATA v4

Table 897: PCFCNT Monitored data


Name Type Values (Range) Unit Description
SCAL_VAL REAL - - Scaled value with time and status
information

19.1.7 Operation principle IP14087-1 v2

M13397-3 v5
The registration of pulses is done for positive transitions (0->1) on one of the 16 binary input
channels located on the Binary Input Module (BIM). Pulse counter values are sent to the station
HMI with predefined cyclicity without reset.

The reporting time period can be set in the range from 1 second to 60 minutes and is
synchronized with absolute system time. Interrogation of additional pulse counter values can

1096 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 19
Metering

be done with a command (intermediate reading) for a single counter. All active counters can
also be read by the LON General Interrogation command (GI) or IEC 61850.

Pulse-counter logic (PCFCNT) function in the IED supports unidirectional incremental counters.
That means only positive values are possible. The counter uses a 32 bit format, that is, the
reported value is a 32-bit, signed integer with a range 0...+2147483647. The counter is reset at
initialization of the IED.

The reported value to station HMI over the station bus contains Identity, Scaled Value (pulse
count x scale), Time, and Pulse Counter Quality. The Pulse Counter Quality consists of:

• Invalid (board hardware error or configuration error)


• Wrapped around
• Blocked
• Adjusted

The transmission of the counter value by SPA can be done as a service value, that is, the value
frozen in the last integration cycle is read by the station HMI from the database. PCFCNT
updates the value in the database when an integration cycle is finished and activates the
NEW_VAL signal in the function block. This signal can be connected to an Event function block,
be time tagged, and transmitted to the station HMI. This time corresponds to the time when
the value was frozen by the function.

The pulse-counter logic function requires a binary input card, BIMp, that is
specially adapted to the pulse-counter logic function.

M13399-3 v9
Figure 644 shows the pulse-counter logic function block with connections of the inputs and
outputs.

SingleCmdFunc PulseCounter EVENT


OUTx BLOCK
INVALID INPUT1
SingleCmdFunc Pulse RESTART INPUT2
OUTx INPUT OUT READ_VAL
Pulse length >1s BLOCKED INPUT3
I/O-module NEW_VAL INPUT4
BI_PULSE
”Reset counter” RS_CNT
NAME
SCAL_VAL IEC EVENT

SMS settings Database


1.Operation = Off/On Pulse counter value:
2.tReporting = 0s...60min 0...2147483647
3.Event Mask = No Events/Report Events
4.Scale = 1-90000
en05000744.vsd
IEC05000744 V1 EN-US

Figure 644: Overview of the pulse-counter logic function


The BLOCK and READ_VAL inputs can be connected to Single Command logics, which are
intended to be controlled either from the station HMI or/and the local HMI. As long as the
BLOCK signal is set, the pulse counter is blocked. The signal connected to READ_VAL performs
one additional reading per positive flank. The signal must be a pulse with a length >1 second.

The BI_PULSE input is connected to the used input of the function block for the Binary Input
Module (BIM).

The RS_CNT input is used for resetting the counter.

Line distance protection REL670 1097


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 19 1MRK 506 370-UEN J
Metering

Each pulse-counter logic function block has four binary output signals that can be connected
to an Event function block for event recording: INVALID, RESTART, BLOCKED and NEW_VAL.
The SCAL_VAL signal can be connected to the IEC Event function block.

The INVALID signal is a steady signal and is set if the Binary Input Module, where the pulse
counter input is located, fails or has wrong configuration.

The RESTART signal is a steady signal and is set when the reported value does not comprise a
complete integration cycle. That is, in the first message after IED start-up, in the first message
after deblocking, and after the counter has wrapped around during last integration cycle.

The BLOCKED signal is a steady signal and is set when the counter is blocked. There are two
reasons why the counter is blocked:

• The BLOCK input is set, or


• The Binary Input Module, where the counter input is situated, is inoperative.

The NEW_VAL signal is a pulse signal. The signal is set if the counter value was updated since
last report.

Note, the pulse is short, one cycle.

The SCAL_VAL signal consists of scaled value (according to parameter Scale), time and status
information.

19.1.8 Technical data IP14092-1 v1

M13404-2 v5

Table 898: PCFCNT technical data


Function Setting range Accuracy
Input frequency See Binary Input Module (BIM) -
Cycle time for report of (1–3600) s -
counter value

19.2 Function for energy calculation and demand handling


ETPMMTR SEMOD153638-1 v2

19.2.1 Identification
SEMOD175537-2 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Function for energy calculation and ETPMMTR W_Varh -
demand handling

1098 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 19
Metering

19.2.2 Functionality GUID-6898E29B-DA70-421C-837C-1BBED8C63A7A v3

Power system measurement (CVMMXN) can be used to measure active as well as reactive
power values. Function for energy calculation and demand handling (ETPMMTR) uses
measured active and reactive power as input and calculates the accumulated active and
reactive energy pulses, in forward and reverse direction. Energy values can be read or
generated as pulses. Maximum demand power values are also calculated by the function. This
function includes zero point clamping to remove noise from the input signal. As output of this
function: periodic energy calculations, integration of energy values, calculation of energy
pulses, alarm signals for limit violation of energy values and maximum power demand, can be
found.

The values of active and reactive energies are calculated from the input power values by
integrating them over a selected time tEnergy. The integration of active and reactive energy
values will happen in both forward and reverse directions. These energy values are available as
output signals and also as pulse outputs. Integration of energy values can be controlled by
inputs (STARTACC and STOPACC) and EnaAcc setting and it can be reset to initial values with
RSTACC input.

The maximum demand for active and reactive powers are calculated for the set time interval
tEnergy and these values are updated every minute through output channels. The active and
reactive maximum power demand values are calculated for both forward and reverse direction
and these values can be reset with RSTDMD input.

19.2.3 Function block SEMOD175502-4 v5

ETPMMTR
P* ACCINPRG
Q* EAFPULSE
STARTACC EARPULSE
STOPACC ERFPULSE
RSTACC ERRPULSE
RSTDMD EAFALM
EARALM
ERFALM
ERRALM
EAFACC
EARACC
ERFACC
ERRACC
MAXPAFD
MAXPARD
MAXPRFD
MAXPRRD

IEC14000019-1-en.vsd
IEC14000019 V1 EN-US

Figure 645: ETPMMTR function block

19.2.4 Signals
PID-6872-INPUTSIGNALS v3

Table 899: ETPMMTR Input signals


Name Type Default Description
P REAL 0 Measured active power
Q REAL 0 Measured reactive power
STARTACC BOOLEAN 0 Start to accumulate energy values
STOPACC BOOLEAN 0 Stop to accumulate energy values.
RSTACC BOOLEAN 0 Reset of accumulated enery reading
RSTDMD BOOLEAN 0 Reset of maximum demand reading

Line distance protection REL670 1099


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 19 1MRK 506 370-UEN J
Metering

PID-6872-OUTPUTSIGNALS v3

Table 900: ETPMMTR Output signals


Name Type Description
ACCINPRG BOOLEAN Accumulation of energy values in progress
EAFPULSE BOOLEAN Accumulated forward active energy pulse
EARPULSE BOOLEAN Accumulated reverse active energy pulse
ERFPULSE BOOLEAN Accumulated forward reactive energy pulse
ERRPULSE BOOLEAN Accumulated reverse reactive energy pulse
EAFALM BOOLEAN Alarm for active forward energy exceed limit in set interval
EARALM BOOLEAN Alarm for active reverse energy exceed limit in set interval
ERFALM BOOLEAN Alarm for reactive forward energy exceed limit in set interval
ERRALM BOOLEAN Alarm for reactive reverse energy exceed limit in set interval
EAFACC REAL Accumulated forward active energy value
EARACC REAL Accumulated reverse active energy value
ERFACC REAL Accumulated forward reactive energy value
ERRACC REAL Accumulated reverse reactive energy value
MAXPAFD REAL Maximum forward active power demand value for set interval
MAXPARD REAL Maximum reverse active power demand value for set interval
MAXPRFD REAL Maximum forward reactive power demand value for set
interval
MAXPRRD REAL Maximum reverse reactive power demand value for set
interval

19.2.5 Settings
PID-6872-SETTINGS v3

Table 901: ETPMMTR Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
EnaAcc Off - - Off Activate the accumulation of energy
On values
tEnergy 1 Minute - - 1 Minute Time interval for energy calculation
5 Minutes
10 Minutes
15 Minutes
30 Minutes
60 Minutes
180 Minutes
tEnergyOnPls 0.100 - 60.000 s 0.001 1.000 Energy accumulated pulse ON time in
secs
tEnergyOffPls 0.100 - 60.000 s 0.001 0.500 Energy accumulated pulse OFF time in
secs
EAFAccPlsQty 0.001 - 10000.000 MWh 0.001 100.000 Pulse quantity for active forward
accumulated energy value
EARAccPlsQty 0.001 - 10000.000 MWh 0.001 100.000 Pulse quantity for active reverse
accumulated energy value
ERFAccPlsQty 0.001 - 10000.000 MVArh 0.001 100.000 Pulse quantity for reactive forward
accumulated energy value
ERRAccPlsQty 0.001 - 10000.000 MVArh 0.001 100.000 Pulse quantity for reactive reverse
accumulated energy value

1100 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 19
Metering

Table 902: ETPMMTR Non group settings (advanced)


Name Values (Range) Unit Step Default Description
EALim 0.001 - MWh 0.001 1000000.000 Active energy limit
10000000000.00
0
ERLim 0.001 - MVArh 0.001 1000.000 Reactive energy limit
10000000000.00
0
EnZeroClamp Off - - On Enable of zero point clamping
On detection function
LevZeroClampP 0.001 - 10000.000 MW 0.001 10.000 Zero point clamping level at active
Power
LevZeroClampQ 0.001 - 10000.000 MVAr 0.001 10.000 Zero point clamping level at reactive
Power
DirEnergyAct Forward - - Forward Direction of active energy flow
Reverse Forward/Reverse
DirEnergyReac Forward - - Forward Direction of reactive energy flow
Reverse Forward/Reverse
EAFPrestVal 0.000 - MWh 0.001 0.000 Preset Initial value for forward active
100000000.000 energy
EARPrestVal 0.000 - MWh 0.001 0.000 Preset Initial value for reverse active
100000000.000 energy
ERFPresetVal 0.000 - MVArh 0.001 0.000 Preset Initial value for forward
100000000.000 reactive energy
ERRPresetVal 0.000 - MVArh 0.001 0.000 Preset Initial value for reverse reactive
100000000.000 energy

19.2.6 Monitored data


PID-6872-MONITOREDDATA v3

Table 903: ETPMMTR Monitored data


Name Type Values (Range) Unit Description
EAFACC REAL - MWh Accumulated forward active energy
value
EARACC REAL - MWh Accumulated reverse active energy
value
ERFACC REAL - MVArh Accumulated forward reactive energy
value
ERRACC REAL - MVArh Accumulated reverse reactive energy
value
MAXPAFD REAL - MW Maximum forward active power
demand value for set interval
MAXPARD REAL - MW Maximum reverse active power
demand value for set interval
MAXPRFD REAL - MVAr Maximum forward reactive power
demand value for set interval
MAXPRRD REAL - MVAr Maximum reverse reactive power
demand value for set interval

Line distance protection REL670 1101


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 19 1MRK 506 370-UEN J
Metering

19.2.7 Operation principle GUID-4A46757C-EC5D-4BCE-9D09-C8152B062CE1 v3

The instantaneous output values of active and reactive power from the Measurements
function CVMMXN are used and integrated over a selected time tEnergy to measure the
integrated energy. Figure 646 shows the overall functionality of the energy calculation and
demand handling function ETPMMTR.

MAXPAFD
RSTDMD
MAXPARD
MAXPRFD
P
MAXPRRD
Zero Clamping Maximum Power
EAFALM
Detection Demand Calculation
Q EARALM
ERFALM
ERRALM

ACCINPRG
EAFPULSE
EARPULSE
ERFPULSE
Energy Accumulation ERRPULSE
STARTACC
Calculation EAFACC
EARACC
STOPACC
ERFACC
ERRACC
RSTACC

IEC13000185-2-en.vsd
IEC13000185 V2 EN-US

Figure 646: ETPMMTR Functional overview logical diagram


The integration of energy values is enabled by the setting EnaAcc and controlled by the
STARTACC and STOPACC inputs. If the integration is in progress, the output ACCINPRG is high.
Otherwise, it is low. Figure 647 shows the logic of the ACCINPRG output. ACCINPRG is active
when the STARTACC input is active and the EnaAcc setting is enabled. When the RSTACC input
is in the active state, the output ACCINPRG is low even if the integration of energy is enabled.
ACCINPRG is deactivated by activating the STOPACC input.

STOPACC

FALSE
STARTACC T
³1
& F ACCINPRG
EnaAcc &

q-1

RSTACC

q-1 = unit delay IEC13000186-4-en.vsd


IEC13000186 V4 EN-US

Figure 647: ACCINPRG Logic diagram


The accumulated energy values (in MWh and MVArh) are available as service values and also as
pulsed output depending on the ExxAccPlsQty setting, which can be connected to a pulse
counter. Accumulated energy outputs are available for forward as well as reverse direction.
The accumulated energy values can be reset to initial accumulated energy values (ExxPrestVal)
from the local HMI reset menu or with the input signal RSTACC. Figure 648 shows the logic for
integration of energy in active forward direction. Similarly, the integration of energy in active
reverse, reactive forward and reactive reverse is done.

1102 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 19
Metering

RSTACC

EAFPrestVal

ACCINPRG

P* (ACTIVE FORWARD)
X
 T
T EAFACC
60.0
F
F

&

q-1

1000 GWh T
-1 F
q 0.0

a
a>b
b
-1
q = unit delay
IEC13000187-5-en.vsdx
IEC13000187 V5 EN-US

Figure 648: Logic for integration of active forward energy


The energy pulses generated by using internally calculated accumulated energy values and
energy per pulse (ExxAccPlsQty) setting. The accumulated energy values are divided by the
energy-per-pulse value to get the number of pulses. The number of pulses can be reset to zero
by activating RSTACC input or by using the local HMI reset menu. The pulse on and off time
duration is set by the settings tEnergyOnPls and tEnergyOffPls. Figure 649 shows the logic for
pulse output generation for the integrated energy in the active forward direction. Similarly, the
pulse generation for integrated energy in the active reverse, reactive forward and reactive
reverse is done.

tEnergyOffPls
EAFACC

a Counter q-1
a>b CU
1000 GWh b CV
Rst
tOff
t
R I q-1

0
÷ X
 R I T
EAFPULSE
a TP
a>b F
b
EAFAccPlsQty ÷ 0
Counter
CU
CV
RSTACC
Rst

q-1

tEnergyOnPls

q-1 = unit delay


IEC13000188-5-en.vsdx
IEC13000188 V5 EN-US

Figure 649: Logic for pulse generation of integrated active forward energy
The maximum demand values for active and reactive power are calculated for the set time
interval tEnergy. The maximum values are updated every minute and stored in a register

Line distance protection REL670 1103


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 19 1MRK 506 370-UEN J
Metering

available over communication and from outputs MAXPAFD, MAXPARD, MAXPRFD and MAXPRRD for
the active and reactive power forward and reverse direction. When the RSTDMD input is active
from the local HMI reset menu, these outputs are reset to zero. The energy alarm is activated
once the periodic energy value crosses the energy limit ExLim. Figure 650 shows the logic of
alarm for active forward energy exceeds limit and Maximum forward active power demand
value. Similarly, the maximum power calculation and energy alarm outputs in the active
reverse, reactive forward and reactive reverse is implemented.

P (ACTIVE FORWARD)
Average Power
X a EAFALM
tEnergy Calculation a>b
b

EALim

RSTMAXD

0.0 T MAXPAFD
MAX F

q-1
q-1 = unit delay
IEC13000189-4-en.vsd
IEC13000189 V4 EN-US

Figure 650: Logic for maximum power demand calculation and energy alarm

19.2.8 Technical data


SEMOD153707-2 v5

Table 904: ETPMMTR technical data


Function Range or value Accuracy
Energy metering kWh Export/Import, kvarh Input from MMXU. No extra error at steady
Export/Import load

1104 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 20
Ethernet

Section 20 Ethernet
20.1 Access point

20.1.1 Introduction GUID-6E5D2696-A8EE-43E7-A94B-69C3D0612127 v2

An access point is an Ethernet communication interface for single or redundant station


communication. Each access point is allocated with one physical Ethernet port, two physical
Ethernet ports are allocated if redundant communication is activated for the access point.

Device 1 Device 1

AP1 AP2 AP3 AP1 AP2 AP3


SFP_301 SFP_302 SFP_303 SFP_301 SFP_302 SFP_303

IEC16000092-1-en.vsdx
IEC16000092 V1 EN-US

Figure 651: Access points, non redundant (left) and redundant communication (right)

20.1.2 Settings
PID-6775-SETTINGS v4

Table 905: AP_1 Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation on/off of the access point
On
Redundancy None - - None Ethernet redundancy mode
PRP-0
PRP-1
HSR
IPAddress 0 - 18 IP 1 192.168.1.10 IP address of the access point
Address
SubnetMask 0 - 18 IP 1 255.255.255.0 Subnet mask of the access point
Address
Description 1 - 18 - 1 Station bus User editable access point description
[1-18 char]
PTP Off - - Off Precision time protocol
On
Slave only
PCM600Access Off - - On PCM600 access
On
FTP Off - - On FTP and FTPS access
On
MMS Off - - On IEC61850-8-1 MMS
On
GOOSE Off - - On IEC61850-8-1 GOOSE
On
DNP3 Off - - On DNP3 slave
On
Table continues on next page

Line distance protection REL670 1105


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 20 1MRK 506 370-UEN J
Ethernet

Name Values (Range) Unit Step Default Description


SNTPServer Off - - On SNTP server
On
FSTAccess Off - - On Field Service Tool access
On
C37.118TCP Off - - On IEEE 1344 and C37.118 TCP server
On
C37.118UDP1 Off - - On IEEE 1344 and C37.118 UDP stream and
On the TCP control server
C37.118UDP2 Off - - On IEEE 1344 and C37.118 UDP stream and
On the TCP control server
C37.118UDP3 Off - - On IEEE 1344 and C37.118 UDP stream and
On the TCP control server
C37.118UDP4 Off - - On IEEE 1344 and C37.118 UDP stream and
On the TCP control server
C37.118UDP5 Off - - On IEEE 1344 and C37.118 UDP stream and
On the TCP control server
C37.118UDP6 Off - - On IEEE 1344 and C37.118 UDP stream and
On the TCP control server
DefaultGateway 0 - 18 IP 1 0.0.0.0 Default gateway IP address
Address

PID-6637-SETTINGS v3

Table 906: AP_FRONT Non group settings (basic)


Name Values (Range) Unit Step Default Description
IPAddress 0 - 18 IP 1 10.1.150.3 IP address of the access point
Address
SubnetMask 0 - 18 IP 1 255.255.255.0 Subnet mask of the access point
Address
Description 1 - 18 - 1 FrontPort User editable access point description
[1-18 char]
PCM600Access Off - - On PCM600 access
On
FTP Off - - On FTP and FTPS access
On
MMS Off - - On IEC61850-8-1 MMS
On
GOOSE Off - - On IEC61850-8-1 GOOSE
On
DNP3 Off - - On DNP3 slave
On
SNTPServer Off - - On SNTP Server
On
FSTAccess Off - - On Field Service Tool access
On
C37.118TCP Off - - On IEEE 1344 and C37.118 TCP server
On
C37.118UDP1 Off - - On IEEE 1344 and C37.118 UDP stream and
On the TCP control server
C37.118UDP2 Off - - On IEEE 1344 and C37.118 UDP stream and
On the TCP control server
Table continues on next page

1106 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 20
Ethernet

Name Values (Range) Unit Step Default Description


C37.118UDP3 Off - - On IEEE 1344 and C37.118 UDP stream and
On the TCP control server
C37.118UDP4 Off - - On IEEE 1344 and C37.118 UDP stream and
On the TCP control server
C37.118UDP5 Off - - On IEEE 1344 and C37.118 UDP stream and
On the TCP control server
C37.118UDP6 Off - - On IEEE 1344 and C37.118 UDP stream and
On the TCP control server
DefaultGateway 0 - 18 IP 1 0.0.0.0 Default gateway IP address
Address

20.2 Access point diagnostics

20.2.1 Functionality GUID-20F64A6D-AA8C-47D7-AA7D-4810996B2FF2 v2

The access point diagnostics function blocks (RCHLCCH, SCHLCCH and FRONTSTATUS)
supervise communication. SCHLCCH is used for communication over the rear Ethernet ports,
RCHLCCH is used for redundant communications over the rear Ethernet ports and
FRONTSTATUS is used for communication over the front port. All access point function blocks
include output signal for denial of service.

20.2.2 Function block GUID-727BF536-1D60-4060-A674-5D73F252CCB7 v2

SCHLCCH
LINKUP
DOSALARM

IEC16000044-1-en.vsdx
IEC16000044 V1 EN-US

Figure 652: SCHLCCH Function block

RCHLCCH
REDLINKA
REDLINKB
DOSALARM

IEC16000045-1-en.vsdx
IEC16000045 V1 EN-US

Figure 653: RCHLCCH Function block

20.2.3 Signals
PID-6818-OUTPUTSIGNALS v2

Table 907: SCHLCCH Output signals


Name Type Description
LINKUP BOOLEAN Access point link status
DOSALARM BOOLEAN Denial of service alarm

Line distance protection REL670 1107


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 20 1MRK 506 370-UEN J
Ethernet

PID-6819-OUTPUTSIGNALS v2

Table 908: RCHLCCH Output signals


Name Type Description
REDLINKA BOOLEAN Channel A redundancy status
REDLINKB BOOLEAN Channel B redundancy status
DOSALARM BOOLEAN Denial of service alarm (A + B)

20.2.4 Monitored data


PID-6818-MONITOREDDATA v2

Table 909: SCHLCCH Monitored data


Name Type Values (Range) Unit Description
GatewayConfig INTEGER 0=Ok - Gateway configuration status
1=Error
-1=Off
2=Invalid

PID-6819-MONITOREDDATA v2

Table 910: RCHLCCH Monitored data


Name Type Values (Range) Unit Description
GatewayConfig INTEGER 0=Ok - Gateway configuration status
1=Error
-1=Off
2=Invalid

20.3 Redundant communication

20.3.1 Identification
GUID-B7AE0374-0336-42B8-90AF-3AE1C79A4116 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
IEC 62439-3 Parallel redundancy PRP - -
protocol
IEC 62439-3 High-availability HSR - -
seamless redundancy
Access point diagnostic for RCHLCCH - -
redundant Ethernet ports

20.3.2 Functionality GUID-494FACF7-4BE0-4B9F-A18F-47CD1E92C0F9 v1

PRP IEC 62439-3 redundant communication


Redundant communication according to IEC 62439-3 PRP-0 and IEC 62439-3 PRP-1 parallel
redundancy protocol (PRP) is available as an option when ordering IEDs. PRP according to IEC
62439-3 uses two optical Ethernet ports.

1108 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 20
Ethernet

IEC 62439-3 High-availabillity Seamless Redundancy (HSR)


Redundant station bus communication according to IEC 62439-3 Edition 1 and IEC 62439-3
Edition 2 High-availability seamless redundancy (HSR) is available as an option when ordering
IEDs. Redundant station bus communication according to 62439-3 uses two optical Ethernet
ports.

20.3.3 Operation principle GUID-73DB23CD-A924-4B89-8AAB-1E79D44DE429 v1

PRP IEC 62439-3 redundant communication


The communication is performed in parallel, that is the same data package is transmitted on
both channels simultaneously. The received package identity from one channel is compared
with data package identity from the other channel, if they are the same, the last package is
discarded.

The RCHLCCH function block supervise the redundant communication on the two channels. If
no data package has been received on one (or both) channels within the last 10 s, the output
LinkAUp and/or LinkBUp is set to 0 which indicates an error.

Device 1 Device 2

AP1 AP1
PhyPortA PhyPortB PhyPortA PhyPortB

Switch A Switch B

PhyPortA PhyPortB PhyPortA PhyPortB


AP1 AP1

Device 3 Device 4

IEC09000758-4-en.vsd
IEC09000758 V4 EN-US

Figure 654: Redundant station bus

IEC 62439-3 High-availabillity Seamless Redundancy (HSR)


HSR applies the principle of parallel operation to a single ring.

For each message sent, the node sends two frames, one through each port. Both the frames
circulate in opposite directions over the ring. Every node forwards the frames it receives from
one port to another to reach the next node. When the originating sender node receives the
frame it sent, the sender node discards the frame to avoid loops

Line distance protection REL670 1109


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 20 1MRK 506 370-UEN J
Ethernet

The RCHLCCH function block supervise the redundant communication on the two channels. If
no data package has been received on one (or both) channels within the last 10 s, the output
LinkAUp and/or LinkBUp is set to 0 which indicates an error.

If IEEE1588 (PTP) is used an accuracy of 1 µs can be guaranteed for up to 15 devices in one


HSR-ring.

Device 1 Device 2

AP1 AP1
PhyPortA PhyPortB PhyPortA PhyPortB

PhyPortB PhyPortA PhyPortB PhyPortA


AP1 AP1

Device 3 Device 4

IEC16000038-1-en.vsdx
IEC16000038 V1 EN-US

Figure 655: HSR ring

20.4 Merging unit

20.4.1 Introduction GUID-E630C16F-EDB8-40AE-A8A2-94189982D15F v1

The IEC/UCA 61850-9-2LE process bus communication protocol enables an IED to


communicate with devices providing measured values in digital format, commonly known as
Merging Units (MU). The rear access points are used for the communication.

The merging units (MU) are called so because they can gather analog values from one or more
measuring transformers, sample the data and send the data over process bus to other clients
(or subscribers) in the system. Some merging units are able to get data from classical
measuring transformers, others from non-conventional measuring transducers and yet others
can pick up data from both types.

20.4.2 Settings
PID-6770-SETTINGS v2

Table 911: MU1 Non group settings (basic)


Name Values (Range) Unit Step Default Description
SampleValueID 0 - 34 - 1 ABB_MU0101 Sample Value ID (SVID) for the
merging unit [0-34 char]
APConnection None - - None Access point connection for the
AP1 merging unit
AP2
AP3
AP4

1110 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 20
Ethernet

PID-6850-SETTINGS v3

Table 912: MU1_HW Non group settings (basic)


Name Values (Range) Unit Step Default Description
CTStarPoint1 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTStarPoint2 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTStarPoint3 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTStarPoint4 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite

20.4.3 Monitored data


PID-6850-MONITOREDDATA v3

Table 913: MU1_HW Monitored data


Name Type Values (Range) Unit Description
MUDATA BOOLEAN 0=Ok - Fatal error, data not received,
1=Error transmission errors, time-sync issues
or inconsistent sample rate
SYNCH BOOLEAN 0=Ok - High when IED clock is not within
1=Error configured accuracy or time domain
SMPLLOST BOOLEAN 1=Yes - Fatal error or recovery state after fatal
0=No error. High if any subscribed channel
has bad quality or TEST while IED not
in test mode.
MUSYNCH BOOLEAN 0=Ok - MU not synced or MU clock not synced
1=Error to same clock as IED
TESTMODE BOOLEAN 1=Yes - Quality of one or more subscribed
0=No analogue channels is TEST
SIMMODE BOOLEAN 1=Yes - MU delivers simulated data accepted
0=No by IED
BadReference BOOLEAN 1=Yes - BadReference indication output for I1
0=No
Derived BOOLEAN 1=Yes - Derived indication output for I1
0=No
Failure BOOLEAN 1=Yes - Failure indication output for I1
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for I1
0=No
Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for I1
0=No
OldData BOOLEAN 1=Yes - OldData indication output for I1
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for
0=No I1
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for I1
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for I1
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for I1
0=No
Table continues on next page

Line distance protection REL670 1111


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 20 1MRK 506 370-UEN J
Ethernet

Name Type Values (Range) Unit Description


Source BOOLEAN 0=Process - Source indication output for I1
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for I1
0=No
Validity INTEGER 0=Good - Validity indication output I1
2=Reserved
1=Invalid
3=Questionable
BadReference BOOLEAN 1=Yes - BadReference indication output for I2
0=No
Derived BOOLEAN 1=Yes - Derived indication output for I2
0=No
Failure BOOLEAN 1=Yes - Failure indication output for I2
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for I2
0=No
Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for I2
0=No
OldData BOOLEAN 1=Yes - OldData indication output for I2
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for
0=No I2
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for I2
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for I2
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for I2
0=No
Source BOOLEAN 0=Process - Source indication output for I2
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for I2
0=No
Validity INTEGER 0=Good - Validity indication output I2
2=Reserved
1=Invalid
3=Questionable
BadReference BOOLEAN 1=Yes - BadReference indication output for I3
0=No
Derived BOOLEAN 1=Yes - Derived indication output for I3
0=No
Failure BOOLEAN 1=Yes - Failure indication output for I3
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for I3
0=No
Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for I3
0=No
OldData BOOLEAN 1=Yes - OldData indication output for I3
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for
0=No I3
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for I3
0=No
Table continues on next page

1112 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 20
Ethernet

Name Type Values (Range) Unit Description


OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for I3
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for I3
0=No
Source BOOLEAN 0=Process - Source indication output for I3
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for I3
0=No
Validity INTEGER 0=Good - Validity indication output I3
2=Reserved
1=Invalid
3=Questionable
BadReference BOOLEAN 1=Yes - BadReference indication output for I4
0=No
Derived BOOLEAN 1=Yes - Derived indication output for I4
0=No
Failure BOOLEAN 1=Yes - Failure indication output for I4
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for I4
0=No
Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for I4
0=No
OldData BOOLEAN 1=Yes - OldData indication output for I4
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for
0=No I4
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for I4
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for I4
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for I4
0=No
Source BOOLEAN 0=Process - Source indication output for I4
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for I4
0=No
Validity INTEGER 0=Good - Validity indication output I4
2=Reserved
1=Invalid
3=Questionable
BadReference BOOLEAN 1=Yes - BadReference indication output for U1
0=No
Derived BOOLEAN 1=Yes - Derived indication output for U1
0=No
Failure BOOLEAN 1=Yes - Failure indication output for U1
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for U1
0=No
Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for U1
0=No
OldData BOOLEAN 1=Yes - OldData indication output for U1
0=No
Table continues on next page

Line distance protection REL670 1113


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 20 1MRK 506 370-UEN J
Ethernet

Name Type Values (Range) Unit Description


OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for
0=No U1
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for U1
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for U1
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for U1
0=No
Source BOOLEAN 0=Process - Source indication output for U1
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for U1
0=No
Validity INTEGER 0=Good - Validity indication output U1
2=Reserved
1=Invalid
3=Questionable
BadReference BOOLEAN 1=Yes - BadReference indication output for U2
0=No
Derived BOOLEAN 1=Yes - Derived indication output for U2
0=No
Failure BOOLEAN 1=Yes - Failure indication output for U2
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for U2
0=No
Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for U2
0=No
OldData BOOLEAN 1=Yes - OldData indication output for U2
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for
0=No U2
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for U2
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for U2
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for U2
0=No
Source BOOLEAN 0=Process - Source indication output for U2
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for U2
0=No
Validity INTEGER 0=Good - Validity indication output U2
2=Reserved
1=Invalid
3=Questionable
BadReference BOOLEAN 1=Yes - BadReference indication output for U3
0=No
Derived BOOLEAN 1=Yes - Derived indication output for U3
0=No
Failure BOOLEAN 1=Yes - Failure indication output for U3
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for U3
0=No
Table continues on next page

1114 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 20
Ethernet

Name Type Values (Range) Unit Description


Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for U3
0=No
OldData BOOLEAN 1=Yes - OldData indication output for U3
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for
0=No U3
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for U3
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for U3
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for U3
0=No
Source BOOLEAN 0=Process - Source indication output for U3
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for U3
0=No
Validity INTEGER 0=Good - Validity indication output U3
2=Reserved
1=Invalid
3=Questionable
BadReference BOOLEAN 1=Yes - BadReference indication output for
0=No U4
Derived BOOLEAN 1=Yes - Derived indication output for U4
0=No
Failure BOOLEAN 1=Yes - Failure indication output for U4
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for U4
0=No
Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for U4
0=No
OldData BOOLEAN 1=Yes - OldData indication output for U4
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for
0=No U4
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for U4
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for U4
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for U4
0=No
Source BOOLEAN 0=Process - Source indication output for U4
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for U4
0=No
Validity INTEGER 0=Good - Validity indication output U4
2=Reserved
1=Invalid
3=Questionable

Line distance protection REL670 1115


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 20 1MRK 506 370-UEN J
Ethernet

20.5 Routes

20.5.1 Introduction GUID-95F9C7BA-92F8-489F-AD0A-047410B5E66F v1

A route is a specified path for data to travel between the source device in a subnetwork to the
destination device in a different subnetwork. A route consists of a destination address and the
address of the gateway to be used when sending data to the destination device, see Figure
656.

Default gateway

Gateway

Source Destination
IEC16000095-1-en.vsdx
IEC16000095 V1 EN-US

Figure 656: Route from source to destination through gateway

20.5.2 Settings
PID-6761-SETTINGS v2

Table 914: ROUTE_1 Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation on/off of the route
On
IPAddress 0 - 18 IP 1 0.0.0.0 IP address of the gateway
Address
DestIPAddress 0 - 18 IP 1 0.0.0.0 Destination IP address
Address
DestSubnetMask 0 - 18 IP 1 255.255.255.255 Destination IP subnet mask
Address
Name 1 - 18 - 1 Route1 User configurable name of the route
[1-18 char]

20.5.3 Monitored data


PID-6761-MONITOREDDATA v2

Table 915: ROUTE_1 Monitored data


Name Type Values (Range) Unit Description
RouteConfig INTEGER 0=Ok - Route configuration status
1=Error
-1=Off

1116 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 21
Station communication

Section 21 Station communication


21.1 Communication protocols M14815-3 v14

Each IED is provided with several communication interfaces enabling it to connect to one or
many substation level systems or equipment, either on the Substation Automation (SA) bus or
Substation Monitoring (SM) bus.

Available communication protocols are:

• IEC 61850-8-1 communication protocol


• IEC/UCA 61850-9-2LE communication protocol
• LON communication protocol
• SPA communication protocol
• IEC 60870-5-103 communication protocol
• C37.118 communication protocol

Several protocols can be combined in the same IED.

21.2 Communication protocol diagnostics GUID-6BC4671F-6D06-4BBD-B1FF-2F03FF16A856 v1

Status of the protocols can be viewed in the LHMI under Main menu/Diagnostics/IED status/
Protocol diagnostics. The diagnostic values are:

Diagnostic value Description


Off Protocol is turned off
Error An error has occured, refer to event list for more
information
Warning Configuration inconsistency. Unable to locate data
point.
Ready Protocol is ready

Line distance protection REL670 1117


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 21 1MRK 506 370-UEN J
Station communication

IEC15000400-1-en.vsd
IEC15000400 V1 EN-US

Figure 657: Protocol diagnostic screen in LHMI

21.3 DNP3 protocol GUID-54A54716-23BD-4E7C-8245-DE2B4C75E8DC v1

DNP3 (Distributed Network Protocol) is a set of communications protocols used to


communicate data between components in process automation systems. For a detailed
description of the DNP3 protocol, see the DNP3 Communication protocol manual.

21.4 IEC 61850-8-1 communication protocol IP14616-1 v2

21.4.1 Functionality M14787-3 v16

IEC 61850 Ed.1 or Ed.2 can be chosen by a setting in PCM600. The IED is equipped with up to
six (order dependent) optical Ethernet rear ports for IEC 61850-8-1 station bus
communication.The IEC 61850-8-1 communication is also possible from the electrical Ethernet
front port. IEC 61850-8-1 protocol allows intelligent electrical devices (IEDs) from different
vendors to exchange information and simplifies system engineering. IED-to-IED
communication using GOOSE and client-server communication over MMS are supported.
Disturbance recording file (COMTRADE) uploading can be done over MMS or FTP.

The front port is only intended for PCM600 communication, maintenance,


training and test purposes due to risk of interference during normal operation.

1118 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 21
Station communication

21.4.2 Communication interfaces and protocols GUID-35C845D3-574A-40D1-AEF1-9E0D330E31DE v9

Table 916: Supported station communication interfaces and protocols


Protocol Ethernet Serial
100BASE-FX (ST connector) Glass fiber (ST connector) EIA-485
IEC 61850–8–1 ● - -
DNP3 ● ● ●
IEC 60870-5-103 - ● ●
● = Supported

When double Ethernet ports are activated, make sure that all ports are
connected to different subnets. For example: port 1 has IP address
198.168.101.10 with subnet mask 255.255.255.0, and port 2 has IP address
198.168.102.10 with subnet mask 255.255.255.0.

21.4.3 Settings
PID-6702-SETTINGS v3

Table 917: IEC61850-8-1 Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
GOOSEPortEd1 AP_FRONT - - AP_1 Selection of GOOSE port (only for
AP_1 IEC61850 Ed1)
AP_2
AP_3
AP_4
AP_5
AP_6
ProtocolEdition Ed 1 - - Ed 1 Protocol Edition
Ed 2
RemModControl Off - - Off Remote Mode Control
Maintenance
All levels
AllowSimulation No - - No Allow simulated GOOSE values or
Yes simulated sampled measurand values
RemSetControlEd2 Disabled - - Disabled Changing settings over 61850 enabled
Enabled (only for IEC61850 Ed2)
ResvTmsEd2 1 - 3600 s 1 60 Reservation time (only for IEC61850
Ed2)

21.4.4 Technical data IP14434-1 v1

M15031-1 v9

Table 918: Communication protocols


Function Value
Protocol IEC 61850-8-1
Communication speed for the IEDs 100BASE-FX
Protocol IEC 60870–5–103
Table continues on next page

Line distance protection REL670 1119


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 21 1MRK 506 370-UEN J
Station communication

Function Value
Communication speed for the IEDs 9600 or 19200 Bd
Protocol DNP3.0
Communication speed for the IEDs 300–115200 Bd
Protocol TCP/IP, Ethernet
Communication speed for the IEDs 100 Mbit/s
Protocol LON
Communication speed for the IEDs 1.25 Mbit/s
Protocol SPA
Communication speed for the IEDs 300–38400 Bd

21.4.5 Generic communication function for Single Point indication


SPGAPC, SP16GAPC SEMOD55999-1 v4

21.4.5.1 Functionality SEMOD55713-5 v8

Generic communication function for Single Point indication (SPGAPC) is used to send one
single logical signal to other systems or equipment in the substation.

21.4.5.2 Function block SEMOD54714-4 v4

SPGAPC
BLOCK
^IN

IEC14000021-1-en.vsd
IEC14000021 V1 EN-US

Figure 658: SPGAPC function block

SP16GAPC
BLOCK
^IN1
^IN2
^IN3
^IN4
^IN5
^IN6
^IN7
^IN8
^IN9
^IN10
^IN11
^IN12
^IN13
^IN14
^IN15
^IN16

IEC14000020-1-en.vsd
IEC14000020 V1 EN-US

Figure 659: SP16GAPC function block

1120 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 21
Station communication

21.4.5.3 Signals SEMOD55830-1 v2

PID-3780-INPUTSIGNALS v6

Table 919: SPGAPC Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
IN BOOLEAN 0 Input status

PID-3781-INPUTSIGNALS v6

Table 920: SP16GAPC Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
IN1 BOOLEAN 0 Input 1 status
IN2 BOOLEAN 0 Input 2 status
IN3 BOOLEAN 0 Input 3 status
IN4 BOOLEAN 0 Input 4 status
IN5 BOOLEAN 0 Input 5 status
IN6 BOOLEAN 0 Input 6 status
IN7 BOOLEAN 0 Input 7 status
IN8 BOOLEAN 0 Input 8 status
IN9 BOOLEAN 0 Input 9 status
IN10 BOOLEAN 0 Input 10 status
IN11 BOOLEAN 0 Input 11 status
IN12 BOOLEAN 0 Input 12 status
IN13 BOOLEAN 0 Input 13 status
IN14 BOOLEAN 0 Input 14 status
IN15 BOOLEAN 0 Input 15 status
IN16 BOOLEAN 0 Input 16 status

21.4.5.4 Settings ABBD8E283673 v4

The function does not have any parameters available in the local HMI or PCM600.

21.4.5.5 Monitored data


PID-3780-MONITOREDDATA v3

Table 921: SPGAPC Monitored data


Name Type Values (Range) Unit Description
OUT GROUP - - Output status
SIGNAL

Line distance protection REL670 1121


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 21 1MRK 506 370-UEN J
Station communication

PID-3781-MONITOREDDATA v3

Table 922: SP16GAPC Monitored data


Name Type Values (Range) Unit Description
OUT1 GROUP - - Output 1 status
SIGNAL
OUT2 GROUP - - Output 2 status
SIGNAL
OUT3 GROUP - - Output 3 status
SIGNAL
OUT4 GROUP - - Output 4 status
SIGNAL
OUT5 GROUP - - Output 5 status
SIGNAL
OUT6 GROUP - - Output 6 status
SIGNAL
OUT7 GROUP - - Output 7 status
SIGNAL
OUT8 GROUP - - Output 8 status
SIGNAL
OUT9 GROUP - - Output 9 status
SIGNAL
OUT10 GROUP - - Output 10 status
SIGNAL
OUT11 GROUP - - Output 11 status
SIGNAL
OUT12 GROUP - - Output 12 status
SIGNAL
OUT13 GROUP - - Output 13 status
SIGNAL
OUT14 GROUP - - Output 14 status
SIGNAL
OUT15 GROUP - - Output 15 status
SIGNAL
OUT16 GROUP - - Output 16 status
SIGNAL
OUTOR GROUP - - Output status logic OR gate for input
SIGNAL 1 to 16

21.4.5.6 Operation principle SEMOD55725-5 v8

Upon receiving a signal at its input, Generic communication function for Single Point
indication (SPGAPC) function sends the signal over IEC 61850-8-1 to the equipment or system
that requests this signal. Additional configuration is needed with PCM600 or IET600 to get the
IEC 61850-8-1 communication established. For more information, refer to the Engineering
manual.

21.4.6 Generic communication function for Measured Value MVGAPC SEMOD55402-1 v3

1122 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 21
Station communication

21.4.6.1 Functionality SEMOD55872-5 v10

Generic communication function for measured values (MVGAPC) function is used to send the
instantaneous value of an analog signal to other systems or equipment in the substation. It
can also be used inside the same IED, to attach a RANGE aspect to an analog value and to
permit measurement supervision on that value.

21.4.6.2 Function block SEMOD54712-4 v4

MVGAPC
BLOCK ^VALUE
^IN RANGE

IEC14000022-1-en.vsd
IEC14000022 V1 EN-US

Figure 660: MVGAPC function block

21.4.6.3 Signals SEMOD55948-1 v2

PID-6753-INPUTSIGNALS v1

Table 923: MVGAPC Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
IN REAL 0 Analog input value

PID-6753-OUTPUTSIGNALS v1

Table 924: MVGAPC Output signals


Name Type Description
VALUE REAL Magnitude of deadband value
RANGE INTEGER Range

21.4.6.4 Settings SEMOD55954-1 v2

PID-6753-SETTINGS v1

Table 925: MVGAPC Non group settings (basic)


Name Values (Range) Unit Step Default Description
BasePrefix micro - - unit Base prefix (multiplication factor)
milli
unit
kilo
Mega
Giga
Tera
MV db 1 - 100000 Type 1 10000 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
MV zeroDb 0 - 100000 m% 500 1000 Zero point clamping in 0,001% of
range
MV hhLim -5000.00 - xBase 0.01 900.00 High High limit multiplied with the
5000.00 base prefix (multiplication factor)
MV hLim -5000.00 - xBase 0.01 800.00 High limit multiplied with the base
5000.00 prefix (multiplication factor)
Table continues on next page

Line distance protection REL670 1123


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 21 1MRK 506 370-UEN J
Station communication

Name Values (Range) Unit Step Default Description


MV lLim -5000.00 - xBase 0.01 -800.00 Low limit multiplied with the base
5000.00 prefix (multiplication factor)
MV llLim -5000.00 - xBase 0.01 -900.00 Low Low limit multiplied with the
5000.00 base prefix (multiplication factor)
MV min -5000.00 - xBase 0.01 -1000.00 Minimum value multiplied with the
5000.00 base prefix (multiplication factor)
MV max -5000.00 - xBase 0.01 1000.00 Maximum value multiplied with the
5000.00 base prefix (multiplication factor)
MV dbType Cyclic - - Deadband Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
MV limHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range
(common for all limits)

21.4.6.5 Monitored data


PID-6753-MONITOREDDATA v1

Table 926: MVGAPC Monitored data


Name Type Values (Range) Unit Description
VALUE REAL - - Magnitude of deadband value
RANGE INTEGER 1=High - Range
2=Low
3=High-High
4=Low-Low
0=Normal

21.4.6.6 Operation principle SEMOD55936-5 v7

Upon receiving an analog signal at its input, Generic communication function for Measured
Value (MVGAPC) will give the instantaneous value of the signal and the range, as output values.
Additional configuration is needed with PCM600 or IET600 to get the IEC 61850-8-1
communication established. For more information see the Engineering manual.

21.4.7 GOOSE function block to receive a double point value


GOOSEDPRCV

21.4.7.1 Identification
GUID-8C11DB9A-7844-4E1F-A6BB-D97ECE350FC1 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
GOOSE function block to receive a GOOSEDPRCV - -
double point value

21.4.7.2 Functionality GUID-1D2DBC22-4F04-4809-B34E-8939D442C185 v3

GOOSEDPRCV is used to receive a double point value using IEC 61850 protocol via GOOSE.

1124 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 21
Station communication

21.4.7.3 Function block GUID-ED277880-FB5D-4630-872F-9F343D449FFE v1

GOOSEDPRCV
BLOCK ^DPOUT
^SRCDPOUT DATAVALID
COMMVALID
TEST

IEC10000249-2-en.vsdx
IEC10000249 V2 EN-US

Figure 661: GOOSEDPRCV function block

21.4.7.4 Signals
GUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1

Except for the BLOCK input, the rest of the inputs of this GOOSE function block
are used for GOOSE connections. These connections are visible and possible to
make only if Easy GOOSE engineering is enabled. For instructions on how to
enable Easy GOOSE engineering in PCM600, refer to the Engineering Manual.

PID-6828-INPUTSIGNALS v3

Table 927: GOOSEDPRCV Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
SRCDPOUT INTEGER 0 Source to double point output

PID-6828-OUTPUTSIGNALS v3

Table 928: GOOSEDPRCV Output signals


Name Type Description
DPOUT INTEGER Double point output
DATAVALID BOOLEAN Data valid for double point output
COMMVALID BOOLEAN Communication valid for double point output
TEST BOOLEAN Test output

21.4.7.5 Settings
PID-6828-SETTINGS v3

Table 929: GOOSEDPRCV Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On

21.4.7.6 Operation principle GUID-82A1C8A2-827A-40EF-8E58-F573E29E468E v4

The DATAVALID output will be HIGH if the incoming message is with valid data.

The COMMVALID output will become LOW when the sending IED is under total failure
condition and the GOOSE transmission from the sending IED does not happen.

The TEST output will go HIGH if the sending IED is in test mode.

Line distance protection REL670 1125


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 21 1MRK 506 370-UEN J
Station communication

Data Value Data Valid Comm Valid Test


Incoming data with q=Normal Updated 1 1 0
Incoming data with q=oldData 0 0 1 0
Incoming data with q=Invalid 0 0 1 0
Incoming data with q=test 0 0 1 1
Incoming data with q=test+oldData 0 0 1 1

Receiver in block 0 0 1 0
Receiver in block and communication 0 0 0 0
error
Receiver in test mode and incoming Updated 1 1 0
data with q= Normal
Receiver in test mode and incoming Updated 1 1 1
data with q= Test
Communication Error 0 0 0 0

The input of this GOOSE block must be linked either in SMT by means of a cross
or in ACT by means of a GOOSE connection (if easy GOOSE engineering is
enabled) to receive the double point values.

The implementation for IEC 61850 quality data handling is restricted to a


simple level. If quality data validity is GOOD then the DATAVALID output will be
HIGH. If quality data validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE
or OLD DATA then the DATAVALID output will be LOW.

21.4.8 GOOSE function block to receive an integer value


GOOSEINTRCV

21.4.8.1 Identification
GUID-93A1E81B-1DE8-483A-BB3B-DB771EE66DC1 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
GOOSE function block to receive an GOOSEINTRCV - -
integer value

21.4.8.2 Functionality GUID-27B1ED7A-C8E8-499E-89C1-C656FB0337F8 v3

GOOSEINTRCV is used to receive an integer value using IEC 61850 protocol via GOOSE.

1126 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 21
Station communication

21.4.8.3 Function block GUID-56F0C9F7-98F3-4091-B071-53CA5074DC8F v1

GOOSEINTRCV
BLOCK ^INTOUT
^SRCINTOUT DATAVALID
COMMVALID
TEST
IEC10000250-2-en.vsd
IEC10000250 V2 EN-US

Figure 662: GOOSEINTRCV function block

21.4.8.4 Signals
GUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1

Except for the BLOCK input, the rest of the inputs of this GOOSE function block
are used for GOOSE connections. These connections are visible and possible to
make only if Easy GOOSE engineering is enabled. For instructions on how to
enable Easy GOOSE engineering in PCM600, refer to the Engineering Manual.

PID-6829-INPUTSIGNALS v3

Table 930: GOOSEINTRCV Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
SRCINTOUT INTEGER 0 Source to integer output

PID-6829-OUTPUTSIGNALS v3

Table 931: GOOSEINTRCV Output signals


Name Type Description
INTOUT INTEGER Integer output
DATAVALID BOOLEAN Data valid for integer output
COMMVALID BOOLEAN Communication valid for integer output
TEST BOOLEAN Test output

21.4.8.5 Settings
PID-6829-SETTINGS v3

Table 932: GOOSEINTRCV Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On

21.4.8.6 Operation principle GUID-5BBDF772-3B3E-4F7C-ABE9-18CE3C1A2E2D v4

The DATAVALID output will be HIGH if the incoming message is with valid data.

The COMMVALID output will become LOW when the sending IED is under total failure
condition and the GOOSE transmission from the sending IED does not happen.

The TEST output will go HIGH if the sending IED is in test mode.

Line distance protection REL670 1127


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 21 1MRK 506 370-UEN J
Station communication

Data Value Data Valid Comm Valid Test


Incoming data with q=Normal Updated 1 1 0
Incoming data with q=oldData Freeze 0 1 0
Incoming data with q=Invalid Freeze 0 1 0
Incoming data with q=test Freeze 0 1 1
Incoming data with q=test+oldData Freeze 0 1 1

Receiver in block Freeze 0 1 0


Receiver in block and communication error Freeze 0 0 0
Receiver in test mode and incoming data Updated 1 1 0
with q= Normal
Receiver in test mode and incoming data Updated 1 1 1
with q= Test
Communication Error Freeze 0 0 0

The input of this GOOSE block must be linked either in SMT by means of a cross
or in ACT by means of a GOOSE connection (if easy GOOSE engineering is
enabled) to receive the integer values.

The implementation for IEC 61850 quality data handling is restricted to a


simple level. If quality data validity is GOOD then the DATAVALID output will be
HIGH. If quality data validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE
or OLD DATA then the DATAVALID output will be LOW.

21.4.9 GOOSE function block to receive a measurand value


GOOSEMVRCV

21.4.9.1 Identification
GUID-B1FFBE08-C823-4A58-9FE0-A9A20DA6BB44 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
GOOSE function block to receive a GOOSEMVRCV - -
measurand value

21.4.9.2 Functionality GUID-759CB016-2B4D-4D98-82E1-592044983D53 v3

GOOSEMVRCV is used to receive measured value using IEC 61850 protocol via GOOSE.

1128 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 21
Station communication

21.4.9.3 Function block GUID-A0B333CC-AEF4-40EA-B152-364648AB78D3 v1

GOOSEMVRCV
BLOCK ^MVOUT
^SRCMVOUT DATAVALID
COMMVALID
TEST
IEC10000251-2-en.vsd
IEC10000251 V2 EN-US

Figure 663: GOOSEMVRCV function block

21.4.9.4 Signals
GUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1

Except for the BLOCK input, the rest of the inputs of this GOOSE function block
are used for GOOSE connections. These connections are visible and possible to
make only if Easy GOOSE engineering is enabled. For instructions on how to
enable Easy GOOSE engineering in PCM600, refer to the Engineering Manual.

PID-6830-INPUTSIGNALS v3

Table 933: GOOSEMVRCV Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
SRCMVOUT REAL 0 Source to measurand value output

PID-6830-OUTPUTSIGNALS v3

Table 934: GOOSEMVRCV Output signals


Name Type Description
MVOUT REAL Measurand value output
DATAVALID BOOLEAN Data valid for measurand value output
COMMVALID BOOLEAN Communication valid for measurand value output
TEST BOOLEAN Test output

21.4.9.5 Settings
PID-6830-SETTINGS v3

Table 935: GOOSEMVRCV Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On

21.4.9.6 Operation principle GUID-7B24A6D3-2E5F-4961-A0A6-86436373809E v5

The DATAVALID output will be HIGH if the incoming message is with valid data.

The COMMVALID output will become LOW when the sending IED is under total failure
condition and the GOOSE transmission from the sending IED does not happen.

The TEST output will go HIGH if the sending IED is in test mode.

Line distance protection REL670 1129


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 21 1MRK 506 370-UEN J
Station communication

Data Value Data Valid Comm Valid Test


Incoming data with q=Normal Updated 1 1 0
Incoming data with q=oldData Freeze 0 1 0
Incoming data with q=Invalid Freeze 0 1 0
Incoming data with q=test Freeze 0 1 1
Incoming data with q=test+oldData Freeze 0 1 1

Receiver in block Freeze 0 1 0


Receiver in block and communication error Freeze 0 0 0
Receiver in test mode and incoming data Updated 1 1 0
with q= Normal
Receiver in test mode and incoming data Updated 1 1 1
with q= Test
Communication Error Freeze 0 0 0

The input of this GOOSE block must be linked either in SMT by means of a cross
or in ACT by means of a GOOSE connection (in case easy GOOSE engineering is
enabled) to receive the measured value.

The implementation for IEC 61850 quality data handling is restricted to a


simple level. If quality data validity is GOOD then the DATAVALID output will be
HIGH. If quality data validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE
or OLD DATA then the DATAVALID output will be LOW.

21.4.10 GOOSE function block to receive a single point value


GOOSESPRCV

21.4.10.1 Identification
GUID-F2B30A70-842E-435E-8FAB-B1E58B9C0164 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
GOOSE function block to receive a GOOSESPRCV - -
single point value

21.4.10.2 Functionality GUID-0C99A106-C131-45D3-9B81-6B188E35EB34 v3

GOOSESPRCV is used to receive a single point value using IEC 61850 protocol via GOOSE.

1130 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 21
Station communication

21.4.10.3 Function block GUID-A414F31A-323F-4684-BADA-46F9C5E2B0E8 v1

GOOSESPRCV
BLOCK ^SPOUT
^SRCSPOUT DATAVALID
COMMVALID
TEST
IEC10000248-2-en.vsd
IEC10000248 V2 EN-US

Figure 664: GOOSESPRCV function block

21.4.10.4 Signals
GUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1

Except for the BLOCK input, the rest of the inputs of this GOOSE function block
are used for GOOSE connections. These connections are visible and possible to
make only if Easy GOOSE engineering is enabled. For instructions on how to
enable Easy GOOSE engineering in PCM600, refer to the Engineering Manual.

PID-6832-INPUTSIGNALS v3

Table 936: GOOSESPRCV Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
SRCSPOUT BOOLEAN 0 Source to single point output

PID-6832-OUTPUTSIGNALS v3

Table 937: GOOSESPRCV Output signals


Name Type Description
SPOUT BOOLEAN Single point output
DATAVALID BOOLEAN Data valid for single point output
COMMVALID BOOLEAN Communication valid for single point output
TEST BOOLEAN Test output

21.4.10.5 Settings
PID-6832-SETTINGS v3

Table 938: GOOSESPRCV Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On

21.4.10.6 Operation principle GUID-0E25A3FB-41BD-4EFE-9CA0-1262B9CD14CD v4

The DATAVALID output will be HIGH if the incoming message is with valid data.

The COMMVALID output will become LOW when the sending IED is under total failure
condition and the GOOSE transmission from the sending IED does not happen.

The TEST output will go HIGH if the sending IED is in test mode.

Line distance protection REL670 1131


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 21 1MRK 506 370-UEN J
Station communication

Data Value Data Valid Comm Valid Test


Incoming data with q=Normal Updated 1 1 0
Incoming data with q=oldData 0 0 1 0
Incoming data with q=Invalid 0 0 1 0
Incoming data with q=test 0 0 1 1
Incoming data with q=test+oldData 0 0 1 1

Receiver in block 0 0 1 0
Receiver in block and communication 0 0 0 0
error
Receiver in test mode and incoming Updated 1 1 0
data with q= Normal
Receiver in test mode and incoming Updated 1 1 1
data with q= Test
Communication Error 0 0 0 0

The input of this GOOSE block must be linked either in SMT by means of a cross
or in ACT by means of a GOOSE connection (if easy GOOSE engineering is
enabled) to receive the binary single point values.

The implementation for IEC 61850 quality data handling is restricted to a


simple level. If quality data validity is GOOD then the DATAVALID output will be
HIGH. If quality data validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE
or OLD DATA then the DATAVALID output will be LOW.

21.4.11 Horizontal communication via GOOSE for interlocking


GOOSEINTLKRCV SEMOD173197-1 v2

21.4.11.1 Functionality GUID-92ECE152-892C-4214-95DE-B92718689434 v2

GOOSE communication can be used for exchanging information between IEDs via the IEC
61850-8-1 station communication bus. This is typically used for sending apparatus position
indications for interlocking or reservation signals for 1-of-n control. GOOSE can also be used to
exchange any boolean, integer, double point and analog measured values between IEDs.

1132 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 21
Station communication

21.4.11.2 Function block SEMOD173210-4 v5

GOOSEINTLKRCV
BLOCK ^RESREQ
^SRCRESREQ ^RESGRANT
^SRCRESGR ^APP1_OP
^SRCAPP1 ^APP1_CL
^SRCAPP2 APP1VAL
^SRCAPP3 ^APP2_OP
^SRCAPP4 ^APP2_CL
^SRCAPP5 APP2VAL
^SRCAPP6 ^APP3_OP
^SRCAPP7 ^APP3_CL
^SRCAPP8 APP3VAL
^SRCAPP9 ^APP4_OP
^SRCAPP10 ^APP4_CL
^SRCAPP11 APP4VAL
^SRCAPP12 ^APP5_OP
^SRCAPP13 ^APP5_CL
^SRCAPP14 APP5VAL
^SRCAPP15 ^APP6_OP
^APP6_CL
APP6VAL
^APP7_OP
^APP7_CL
APP7VAL
^APP8_OP
^APP8_CL
APP8VAL
^APP9_OP
^APP9_CL
APP9VAL
^APP10_OP
^APP10_CL
APP10VAL
^APP11_OP
^APP11_CL
APP11VAL
^APP12_OP
^APP12_CL
APP12VAL
^APP13_OP
^APP13_CL
APP13VAL
^APP14_OP
^APP14_CL
APP14VAL
^APP15_OP
^APP15_CL
APP15VAL
COMMVALID
TEST
IEC07000048-4-en.vsd
IEC07000048 V4 EN-US

Figure 665: GOOSEINTLKRCV function block

21.4.11.3 Signals SEMOD173205-1 v2

GUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1

Except for the BLOCK input, the rest of the inputs of this GOOSE function block
are used for GOOSE connections. These connections are visible and possible to
make only if Easy GOOSE engineering is enabled. For instructions on how to
enable Easy GOOSE engineering in PCM600, refer to the Engineering Manual.

PID-6831-INPUTSIGNALS v3

Table 939: GOOSEINTLKRCV Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of output signals
SRCRESREQ BOOLEAN 0 Source to reservation request
SRCRESGR BOOLEAN 0 Source to reservation granted
Table continues on next page

Line distance protection REL670 1133


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 21 1MRK 506 370-UEN J
Station communication

Name Type Default Description


SRCAPP1 INTEGER 0 Source to apparatus 1 position
SRCAPP2 INTEGER 0 Source to apparatus 2 position
SRCAPP3 INTEGER 0 Source to apparatus 3 position
SRCAPP4 INTEGER 0 Source to apparatus 4 position
SRCAPP5 INTEGER 0 Source to apparatus 5 position
SRCAPP6 INTEGER 0 Source to apparatus 6 position
SRCAPP7 INTEGER 0 Source to apparatus 7 position
SRCAPP8 INTEGER 0 Source to apparatus 8 position
SRCAPP9 INTEGER 0 Source to apparatus 9 position
SRCAPP10 INTEGER 0 Source to apparatus 10 position
SRCAPP11 INTEGER 0 Source to apparatus 11 position
SRCAPP12 INTEGER 0 Source to apparatus 12 position
SRCAPP13 INTEGER 0 Source to apparatus 13 position
SRCAPP14 INTEGER 0 Source to apparatus 14 position
SRCAPP15 INTEGER 0 Source to apparatus 15 position

PID-6831-OUTPUTSIGNALS v3

Table 940: GOOSEINTLKRCV Output signals


Name Type Description
RESREQ BOOLEAN Reservation request
RESGRANT BOOLEAN Reservation granted
APP1_OP BOOLEAN Apparatus 1 position is open
APP1_CL BOOLEAN Apparatus 1 position is closed
APP1VAL BOOLEAN Apparatus 1 position is valid
APP2_OP BOOLEAN Apparatus 2 position is open
APP2_CL BOOLEAN Apparatus 2 position is closed
APP2VAL BOOLEAN Apparatus 2 position is valid
APP3_OP BOOLEAN Apparatus 3 position is open
APP3_CL BOOLEAN Apparatus 3 position is closed
APP3VAL BOOLEAN Apparatus 3 position is valid
APP4_OP BOOLEAN Apparatus 4 position is open
APP4_CL BOOLEAN Apparatus 4 position is closed
APP4VAL BOOLEAN Apparatus 4 position is valid
APP5_OP BOOLEAN Apparatus 5 position is open
APP5_CL BOOLEAN Apparatus 5 position is closed
APP5VAL BOOLEAN Apparatus 5 position is valid
APP6_OP BOOLEAN Apparatus 6 position is open
APP6_CL BOOLEAN Apparatus 6 position is closed
APP6VAL BOOLEAN Apparatus 6 position is valid
APP7_OP BOOLEAN Apparatus 7 position is open
APP7_CL BOOLEAN Apparatus 7 position is closed
APP7VAL BOOLEAN Apparatus 7 position is valid
Table continues on next page

1134 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 21
Station communication

Name Type Description


APP8_OP BOOLEAN Apparatus 8 position is open
APP8_CL BOOLEAN Apparatus 8 position is closed
APP8VAL BOOLEAN Apparatus 8 position is valid
APP9_OP BOOLEAN Apparatus 9 position is open
APP9_CL BOOLEAN Apparatus 9 position is closed
APP9VAL BOOLEAN Apparatus 9 position is valid
APP10_OP BOOLEAN Apparatus 10 position is open
APP10_CL BOOLEAN Apparatus 10 position is closed
APP10VAL BOOLEAN Apparatus 10 position is valid
APP11_OP BOOLEAN Apparatus 11 position is open
APP11_CL BOOLEAN Apparatus 11 position is closed
APP11VAL BOOLEAN Apparatus 11 position is valid
APP12_OP BOOLEAN Apparatus 12 position is open
APP12_CL BOOLEAN Apparatus 12 position is closed
APP12VAL BOOLEAN Apparatus 12 position is valid
APP13_OP BOOLEAN Apparatus 13 position is open
APP13_CL BOOLEAN Apparatus 13 position is closed
APP13VAL BOOLEAN Apparatus 13 position is valid
APP14_OP BOOLEAN Apparatus 14 position is open
APP14_CL BOOLEAN Apparatus 14 position is closed
APP14VAL BOOLEAN Apparatus 14 position is valid
APP15_OP BOOLEAN Apparatus 15 position is open
APP15_CL BOOLEAN Apparatus 15 position is closed
APP15VAL BOOLEAN Apparatus 15 position is valid
COMMVALID BOOLEAN Communication Valid
TEST BOOLEAN Test Output

21.4.11.4 Settings SEMOD173168-1 v2

PID-6831-SETTINGS v3

Table 941: GOOSEINTLKRCV Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On

21.4.11.5 Operation principle GUID-7275CFBA-F1FE-496A-A9A1-724139DB2081 v1

The APPxVAL output will be HIGH if the incoming message is with valid data.

The COMMVALID output will become LOW when the sending IED is under total failure
condition and the GOOSE transmission from the sending IED does not happen.

The TEST output will go HIGH if the sending IED is in test mode.

Line distance protection REL670 1135


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 21 1MRK 506 370-UEN J
Station communication

Data Value Data Valid Comm Valid Test


Incoming data with q=Normal Updated 1 1 0
Incoming data with q=oldData 0 0 1 0
Incoming data with q=Invalid 0 0 1 0
Incoming data with q=test 0 0 1 1
Incoming data with q=test+oldData 0 0 1 1

Receiver in block 0 0 1 0
Receiver in block and communication 0 0 0 0
error
Receiver in test mode and incoming Updated 1 1 0
data with q= Normal
Receiver in test mode and incoming Updated 1 1 1
data with q= Test
Communication Error 0 0 0 0

At least one of the inputs of this GOOSE block must be linked either in SMT by
means of a cross or in ACT by means of a GOOSE connection (if easy GOOSE
engineering is enabled) to receive any data. Only those outputs whose source
input is linked/connected will be updated.

The implementation for IEC 61850 quality data handling is restricted to a


simple level. If quality data validity is GOOD then the APPxVAL output will be
HIGH. If quality data validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE
or OLD DATA then the APPxVAL output will be LOW.

1136 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 21
Station communication

21.4.12 GOOSE binary receive GOOSEBINRCV SEMOD173158-1 v3

21.4.12.1 Function block SEMOD173175-4 v2

GOOSEBINRCV
BLOCK ^OUT1
^SRCOUT1 DVALID1
^SRCOUT2 ^OUT2
^SRCOUT3 DVALID2
^SRCOUT4 ^OUT3
^SRCOUT5 DVALID3
^SRCOUT6 ^OUT4
^SRCOUT7 DVALID4
^SRCOUT8 ^OUT5
^SRCOUT9 DVALID5
^SRCOUT10 ^OUT6
^SRCOUT11 DVALID6
^SRCOUT12 ^OUT7
^SRCOUT13 DVALID7
^SRCOUT14 ^OUT8
^SRCOUT15 DVALID8
^SRCOUT16 ^OUT9
DVALID9
^OUT10
DVALID10
^OUT11
DVALID11
^OUT12
DVALID12
^OUT13
DVALID13
^OUT14
DVALID14
^OUT15
DVALID15
^OUT16
DVALID16
COMMVALID
TEST

IEC07000047-4-en.vsd
IEC07000047 V4 EN-US

Figure 666: GOOSEBINRCV function block

21.4.12.2 Signals SEMOD173166-1 v2

GUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1

Except for the BLOCK input, the rest of the inputs of this GOOSE function block
are used for GOOSE connections. These connections are visible and possible to
make only if Easy GOOSE engineering is enabled. For instructions on how to
enable Easy GOOSE engineering in PCM600, refer to the Engineering Manual.

PID-6827-INPUTSIGNALS v3

Table 942: GOOSEBINRCV Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of output signals
SRCOUT1 BOOLEAN 0 Source to binary output 1
SRCOUT2 BOOLEAN 0 Source to binary output 2
SRCOUT3 BOOLEAN 0 Source to binary output 3
SRCOUT4 BOOLEAN 0 Source to binary output 4
SRCOUT5 BOOLEAN 0 Source to binary output 5
SRCOUT6 BOOLEAN 0 Source to binary output 6
SRCOUT7 BOOLEAN 0 Source to binary output 7
Table continues on next page

Line distance protection REL670 1137


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 21 1MRK 506 370-UEN J
Station communication

Name Type Default Description


SRCOUT8 BOOLEAN 0 Source to binary output 8
SRCOUT9 BOOLEAN 0 Source to binary output 9
SRCOUT10 BOOLEAN 0 Source to binary output 10
SRCOUT11 BOOLEAN 0 Source to binary output 11
SRCOUT12 BOOLEAN 0 Source to binary output 12
SRCOUT13 BOOLEAN 0 Source to binary output 13
SRCOUT14 BOOLEAN 0 Source to binary output 14
SRCOUT15 BOOLEAN 0 Source to binary output 15
SRCOUT16 BOOLEAN 0 Source to binary output 16

PID-6827-OUTPUTSIGNALS v3

Table 943: GOOSEBINRCV Output signals


Name Type Description
OUT1 BOOLEAN Binary output 1
DVALID1 BOOLEAN Valid data on binary output 1
OUT2 BOOLEAN Binary output 2
DVALID2 BOOLEAN Valid data on binary output 2
OUT3 BOOLEAN Binary output 3
DVALID3 BOOLEAN Valid data on binary output 3
OUT4 BOOLEAN Binary output 4
DVALID4 BOOLEAN Valid data on binary output 4
OUT5 BOOLEAN Binary output 5
DVALID5 BOOLEAN Valid data on binary output 5
OUT6 BOOLEAN Binary output 6
DVALID6 BOOLEAN Valid data on binary output 6
OUT7 BOOLEAN Binary output 7
DVALID7 BOOLEAN Valid data on binary output 7
OUT8 BOOLEAN Binary output 8
DVALID8 BOOLEAN Valid data on binary output 8
OUT9 BOOLEAN Binary output 9
DVALID9 BOOLEAN Valid data on binary output 9
OUT10 BOOLEAN Binary output 10
DVALID10 BOOLEAN Valid data on binary output 10
OUT11 BOOLEAN Binary output 11
DVALID11 BOOLEAN Valid data on binary output 11
OUT12 BOOLEAN Binary output 12
DVALID12 BOOLEAN Valid data on binary output 12
OUT13 BOOLEAN Binary output 13
DVALID13 BOOLEAN Valid data on binary output 13
OUT14 BOOLEAN Binary output 14
DVALID14 BOOLEAN Valid data on binary output 14
OUT15 BOOLEAN Binary output 15
Table continues on next page

1138 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 21
Station communication

Name Type Description


DVALID15 BOOLEAN Valid data on binary output 15
OUT16 BOOLEAN Binary output 16
DVALID16 BOOLEAN Valid data on binary output 16
COMMVALID BOOLEAN Communication Valid
TEST BOOLEAN Test Output

21.4.12.3 Settings SEMOD173168-1 v2

PID-6827-SETTINGS v3

Table 944: GOOSEBINRCV Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On

21.4.12.4 Operation principle GUID-950F2501-9183-43C0-A193-7D15124F6CCE v2

The DVALIDx output will be HIGH if the incoming message is with valid data.

The COMMVALID output will become LOW when the sending IED is under total failure
condition and the GOOSE transmission from the sending IED does not happen.

The TEST output will go HIGH if the sending IED is in test mode.

Data Value Data Valid Comm Valid Test


Incoming data with q=Normal Updated 1 1 0
Incoming data with q=oldData 1 0 1 0
Incoming data with q=Invalid 0 0 1 0
Incoming data with q=test 0 0 1 1
Incoming data with q=test+oldData 0 0 1 1

Receiver in block 0 0 1 0
Receiver in block and communication 0 0 0 0
error
Receiver in test mode and incoming Updated 1 1 0
data with q= Normal
Receiver in test mode and incoming Updated 1 1 1
data with q= Test
Communication Error 0 0 0 0

At least one of the inputs of this GOOSE block must be linked either in SMT by
means of a cross or in ACT by means of a GOOSE connection (if easy GOOSE
engineering is enabled) to receive any data. Only those outputs whose source
input is linked/connected will be updated.

Line distance protection REL670 1139


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 21 1MRK 506 370-UEN J
Station communication

The implementation for IEC 61850 quality data handling is restricted to a


simple level. If quality data validity is GOOD then the DVALIDx output will be
HIGH. If quality data validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE
or OLD DATA then the DVALIDx output will be LOW.

21.4.13 GOOSE function block to receive a switching device


GOOSEXLNRCV

21.4.13.1 Identification
GUID-4B23D0CF-F298-4BBC-B833-1B8CC98D1604 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
GOOSE function block to receive a GOOSEXLNRCV - -
switching device

21.4.13.2 Functionality GUID-5AC7DE11-CB95-4565-A8AE-FB23D59FD717 v1

The GOOSE XLN Receive component is used to collect information from another device’s
XCBR/XSWI logical node sent over process bus via GOOSE. The GOOSE XLN Receive
component includes 12 different outputs (and their respective channel valid bits) with defined
names to ease the 61850 mapping of the GOOSE signals in the configuration process.

21.4.13.3 Function block GUID-690FD935-5344-4D6F-AB94-F9FD5FD35B23 v1

GOOSEXLNRCV
BLOCK ^BEH
^SRCBEH BEH_VALID
^SRCLOC ^LOC
^SRCBLKOPN LOC_VALID
^SRCBLKCLS ^BLKOPN
^SRCPOS BLKOPN_VALID
^SRCOPCNT ^BLKCLS
^SRCBLK BLKCLS_VALID
^SRCSTSELD ^POSVAL
^SRCOPRCVD POSVAL_VALID
^SRCOPOK ^OPCNT
^SRCEEHLT OPCNT_VALID
^SRCOPCAP ^BLK
BLK_VALID
^STSELD
STSELD_VALID
^OPRCVD
OPRCVD_VALID
^OPOK
OPOK_VALID
^EEHEALTH
EEHEALTH_VALID
^OPCAP
OPCAP_VALID
COMMVALID
TEST
IEC16000036-1-en.vsdx
IEC16000036 V1 EN-US

Figure 667: GOOSEXLNRCV function block

1140 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 21
Station communication

21.4.13.4 Signals
GUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1

Except for the BLOCK input, the rest of the inputs of this GOOSE function block
are used for GOOSE connections. These connections are visible and possible to
make only if Easy GOOSE engineering is enabled. For instructions on how to
enable Easy GOOSE engineering in PCM600, refer to the Engineering Manual.

PID-6643-INPUTSIGNALS v3

Table 945: GOOSEXLNRCV Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of output signals
SRCBEH INTEGER 0 Source to behaviour output
SRCLOC BOOLEAN 0 Source to local control behaviour output
SRCBLKOPN BOOLEAN 0 Source to block opening
SRCBLKCLS BOOLEAN 0 Source to block closing
SRCPOS INTEGER 0 Source to switch position
SRCOPCNT INTEGER 0 Source to operation counter
SRCBLK BOOLEAN 0 Source to dynamic blocking of function described by the LN
SRCSTSELD BOOLEAN 0 Source to the controllable data is in the status "selected”
SRCOPRCVD BOOLEAN 0 Source to operate command for a controllable data object
received
SRCOPOK BOOLEAN 0 Source to operate command for a controllable data object
accepted
SRCEEHLT INTEGER 0 Source to external equipment health
SRCOPCAP INTEGER 0 Source to operating capability

PID-6643-OUTPUTSIGNALS v3

Table 946: GOOSEXLNRCV Output signals


Name Type Description
BEH INTEGER Behaviour
BEH_VLD BOOLEAN Valid data on Beh output
LOC BOOLEAN Local control behaviour
LOC_VLD BOOLEAN Valid data on Loc output
BLKOPN BOOLEAN Block opening
BLKOPN_VLD BOOLEAN Valid data on BlkOpn output
BLKCLS BOOLEAN Block closing
BLKCLS_VLD BOOLEAN Valid data on BlkCls output
POSVAL INTEGER Switch position
POSVAL_VLD BOOLEAN Valid data on PosVal output
OPCNT INTEGER Operation counter
OPCNT_VLD BOOLEAN Valid data on OpCnt output
BLK BOOLEAN Dynamic blocking of function described by the LN
BLK_VLD BOOLEAN Valid data on Blk output
STSELD BOOLEAN The controllable data is in the status "selected”
Table continues on next page

Line distance protection REL670 1141


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 21 1MRK 506 370-UEN J
Station communication

Name Type Description


STSELD_VLD BOOLEAN Valid data on stSeld output
OPRCVD BOOLEAN Operate command for a controllable data object received
OPRCVD_VLD BOOLEAN Valid data on opRcvd output
OPOK BOOLEAN Operate command for a controllable data object accepted
OPOK_VLD BOOLEAN Valid data on opOk output
EEHEALTH INTEGER External equipment health
EEHEALTH_VLD BOOLEAN Valid data on EEHealth output
OPCAP INTEGER Operating capability
OPCAP_VLD BOOLEAN Valid data on OpCap output
COMMVALID BOOLEAN Communication valid
TEST BOOLEAN Test output

21.4.13.5 Settings
PID-6643-SETTINGS v3

Table 947: GOOSEXLNRCV Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On

21.4.13.6 Operation principle GUID-903B5E3F-DC92-4D0A-B4D5-59DD01F36458 v1

The xxx_VALID outputs will be HIGH if the incoming message is with valid data.

The COMMVALID output will become LOW when the sending IED is under total failure
condition and the GOOSE transmission from the sending IED does not happen.

The TEST output will go HIGH if the sending IED is in test mode.

At least one of the inputs of this GOOSE block must be linked either in SMT by
means of a cross or in ACT by means of a GOOSE connection (if easy GOOSE
engineering is enabled) to receive any data. Only those outputs whose source
input is linked/connected will be updated.

The implementation for IEC 61850 quality data handling is restricted to a


simple level. If quality data validity is GOOD then the xxx_VALID output will be
HIGH. If quality data validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE
or OLD DATA then the xxx_VALID output will be LOW.

1142 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 21
Station communication

21.5 IEC/UCA 61850-9-2LE communication protocol GUID-6814F62B-8D99-4679-A11E-68048D1AC424 v2

21.5.1 Introduction GUID-FE2AC08A-2E04-4E73-8CA4-905522B1026A v2

The IEC/UCA 61850-9-2LE process bus communication protocol enables an IED to


communicate with devices providing measured values in digital format, commonly known as
Merging Units (MU). The rear access points are used for the communication.

21.5.2 Function block GUID-2581F3AD-7487-4C80-BDF3-9C6EC9F2E43C v3

The function blocks are not represented in the configuration tool. The signals
appear only in the SMT tool when merging units (MU) are included in the
configuration with the Ethernet configuration tool. In the SMT tool they can be
mapped to the desired virtual input (SMAI) of the IED and used internally in the
configuration.

21.5.3 Signals

21.5.3.1 Output signals SEMOD166622-1 v1

GUID-942C81AD-22D9-438F-95FA-1972BA2BE2E5 v1
The output signals are the same for all MUs so only the table for MU1_HW is included in this
manual.
PID-6850-OUTPUTSIGNALS v3

Table 948: MU1_HW Output signals


Name Type Description
I1 STRING Analogue input I1
I2 STRING Analogue input I2
I3 STRING Analogue input I3
I4 STRING Analogue input I4
U1 STRING Analogue input U1
U2 STRING Analogue input U2
U3 STRING Analogue input U3
U4 STRING Analogue input U4
MUDATA BOOLEAN Fatal error, data not received, transmission errors, time-sync
issues or inconsistent sample rate
SYNCH BOOLEAN High when IED clock is not within configured accuracy or time
domain
SMPLLOST BOOLEAN Fatal error or recovery state after fatal error. High if any
subscribed channel has bad quality or TEST while IED not in
test mode.
MUSYNCH BOOLEAN MU not synced or MU clock not synced to same clock as IED
TESTMODE BOOLEAN Quality of one or more subscribed analogue channels is TEST
SIMMODE BOOLEAN MU delivers simulated data accepted by IED
I1QUALITY INTEGER Binary coded quality information for I1
I2QUALITY INTEGER Binary coded quality information for I2
I3QUALITY INTEGER Binary coded quality information for I3
Table continues on next page

Line distance protection REL670 1143


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 21 1MRK 506 370-UEN J
Station communication

Name Type Description


I4QUALITY INTEGER Binary coded quality information for I4
U1QUALITY INTEGER Binary coded quality information for U1
U2QUALITY INTEGER Binary coded quality information for U2
U3QUALITY INTEGER Binary coded quality information for U3
U4QUALITY INTEGER Binary coded quality information for U4

21.5.4 Settings SEMOD166625-1 v2

PID-6850-SETTINGS v3

Table 949: MU1_HW Non group settings (basic)


Name Values (Range) Unit Step Default Description
CTStarPoint1 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTStarPoint2 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTStarPoint3 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTStarPoint4 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite

21.5.5 Monitored data


PID-6850-MONITOREDDATA v3

Table 950: MU1_HW Monitored data


Name Type Values (Range) Unit Description
MUDATA BOOLEAN 0=Ok - Fatal error, data not received,
1=Error transmission errors, time-sync issues
or inconsistent sample rate
SYNCH BOOLEAN 0=Ok - High when IED clock is not within
1=Error configured accuracy or time domain
SMPLLOST BOOLEAN 1=Yes - Fatal error or recovery state after fatal
0=No error. High if any subscribed channel
has bad quality or TEST while IED not
in test mode.
MUSYNCH BOOLEAN 0=Ok - MU not synced or MU clock not synced
1=Error to same clock as IED
TESTMODE BOOLEAN 1=Yes - Quality of one or more subscribed
0=No analogue channels is TEST
SIMMODE BOOLEAN 1=Yes - MU delivers simulated data accepted
0=No by IED
BadReference BOOLEAN 1=Yes - BadReference indication output for I1
0=No
Derived BOOLEAN 1=Yes - Derived indication output for I1
0=No
Failure BOOLEAN 1=Yes - Failure indication output for I1
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for I1
0=No
Table continues on next page

1144 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 21
Station communication

Name Type Values (Range) Unit Description


Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for I1
0=No
OldData BOOLEAN 1=Yes - OldData indication output for I1
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for
0=No I1
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for I1
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for I1
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for I1
0=No
Source BOOLEAN 0=Process - Source indication output for I1
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for I1
0=No
Validity INTEGER 0=Good - Validity indication output I1
2=Reserved
1=Invalid
3=Questionable
BadReference BOOLEAN 1=Yes - BadReference indication output for I2
0=No
Derived BOOLEAN 1=Yes - Derived indication output for I2
0=No
Failure BOOLEAN 1=Yes - Failure indication output for I2
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for I2
0=No
Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for I2
0=No
OldData BOOLEAN 1=Yes - OldData indication output for I2
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for
0=No I2
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for I2
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for I2
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for I2
0=No
Source BOOLEAN 0=Process - Source indication output for I2
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for I2
0=No
Validity INTEGER 0=Good - Validity indication output I2
2=Reserved
1=Invalid
3=Questionable
BadReference BOOLEAN 1=Yes - BadReference indication output for I3
0=No
Derived BOOLEAN 1=Yes - Derived indication output for I3
0=No
Table continues on next page

Line distance protection REL670 1145


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 21 1MRK 506 370-UEN J
Station communication

Name Type Values (Range) Unit Description


Failure BOOLEAN 1=Yes - Failure indication output for I3
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for I3
0=No
Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for I3
0=No
OldData BOOLEAN 1=Yes - OldData indication output for I3
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for
0=No I3
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for I3
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for I3
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for I3
0=No
Source BOOLEAN 0=Process - Source indication output for I3
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for I3
0=No
Validity INTEGER 0=Good - Validity indication output I3
2=Reserved
1=Invalid
3=Questionable
BadReference BOOLEAN 1=Yes - BadReference indication output for I4
0=No
Derived BOOLEAN 1=Yes - Derived indication output for I4
0=No
Failure BOOLEAN 1=Yes - Failure indication output for I4
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for I4
0=No
Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for I4
0=No
OldData BOOLEAN 1=Yes - OldData indication output for I4
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for
0=No I4
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for I4
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for I4
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for I4
0=No
Source BOOLEAN 0=Process - Source indication output for I4
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for I4
0=No
Validity INTEGER 0=Good - Validity indication output I4
2=Reserved
1=Invalid
3=Questionable
Table continues on next page

1146 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 21
Station communication

Name Type Values (Range) Unit Description


BadReference BOOLEAN 1=Yes - BadReference indication output for U1
0=No
Derived BOOLEAN 1=Yes - Derived indication output for U1
0=No
Failure BOOLEAN 1=Yes - Failure indication output for U1
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for U1
0=No
Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for U1
0=No
OldData BOOLEAN 1=Yes - OldData indication output for U1
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for
0=No U1
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for U1
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for U1
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for U1
0=No
Source BOOLEAN 0=Process - Source indication output for U1
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for U1
0=No
Validity INTEGER 0=Good - Validity indication output U1
2=Reserved
1=Invalid
3=Questionable
BadReference BOOLEAN 1=Yes - BadReference indication output for U2
0=No
Derived BOOLEAN 1=Yes - Derived indication output for U2
0=No
Failure BOOLEAN 1=Yes - Failure indication output for U2
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for U2
0=No
Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for U2
0=No
OldData BOOLEAN 1=Yes - OldData indication output for U2
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for
0=No U2
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for U2
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for U2
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for U2
0=No
Source BOOLEAN 0=Process - Source indication output for U2
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for U2
0=No
Table continues on next page

Line distance protection REL670 1147


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 21 1MRK 506 370-UEN J
Station communication

Name Type Values (Range) Unit Description


Validity INTEGER 0=Good - Validity indication output U2
2=Reserved
1=Invalid
3=Questionable
BadReference BOOLEAN 1=Yes - BadReference indication output for U3
0=No
Derived BOOLEAN 1=Yes - Derived indication output for U3
0=No
Failure BOOLEAN 1=Yes - Failure indication output for U3
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for U3
0=No
Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for U3
0=No
OldData BOOLEAN 1=Yes - OldData indication output for U3
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for
0=No U3
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for U3
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for U3
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for U3
0=No
Source BOOLEAN 0=Process - Source indication output for U3
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for U3
0=No
Validity INTEGER 0=Good - Validity indication output U3
2=Reserved
1=Invalid
3=Questionable
BadReference BOOLEAN 1=Yes - BadReference indication output for
0=No U4
Derived BOOLEAN 1=Yes - Derived indication output for U4
0=No
Failure BOOLEAN 1=Yes - Failure indication output for U4
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for U4
0=No
Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for U4
0=No
OldData BOOLEAN 1=Yes - OldData indication output for U4
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for
0=No U4
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for U4
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for U4
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for U4
0=No
Table continues on next page

1148 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 21
Station communication

Name Type Values (Range) Unit Description


Source BOOLEAN 0=Process - Source indication output for U4
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for U4
0=No
Validity INTEGER 0=Good - Validity indication output U4
2=Reserved
1=Invalid
3=Questionable

21.5.6 Operation principle GUID-A1D31CDA-1FE2-4BC0-A472-1B35E73CA1F2 v6

The merging units (MUs) are situated close to the primary equipment, like circuit breakers,
isolators, etc. The MUs have the capability to gather measured values from measuring
transformers, non-conventional transducers or both. The gathered data are then transmitted
to subscribers over the process bus, utilizing the IEC/UCA 61850-9-2LE protocol.

The IED communicates with the MUs over the process bus via the rear access points. For the
user, the MU appears in the IED as a normal analogue input module and is engineered in the
very same way.

Line distance protection REL670 1149


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 21 1MRK 506 370-UEN J
Station communication

IED

Application

Station Wide
Preprocessing blocks Preprocessing blocks GPS Clock
SMAI SMAI

MU1 MU2
Splitter
Electrical-to-
Optical Converter

1PPS
TRM module
Access Point
110 V 1A 1A

IEC/UCA 61850-9-2LE

Ethernet Switch

IEC/UCA 61850-9-2LE

IEC/UCA 61850-9-2LE

Merging 1PPS Merging 1PPS


Unit Unit

Combi Combi
CT CT
Sensor Sensor

Conventional VT
IEC080000723enOriginal.vsd

IEC08000072 V3 EN-US

Figure 668: Example of signal path for sampled analogue values from MU and
conventional CT/VT
The function has the following alarm signals:

• MUDATA:
• Ok[0] indicates that the merging unit samples are received from the merging unit
and are accepted.
• ERROR[1] indicates that the merging unit samples are generated by internal
substitution.
• SYNCH:
• OK[0] indicates
• when SyncLostMode = Block, and the time quality of the hardware is within
the set value [SyncAccLevel=1us, 4us or Unspecified]
• when SyncLostMode = BlockOnLostUTC, the time quality of the hardware is
within the set value [SyncAccLevel=1us, 4us or Unspecified] [AND] IED

1150 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 21
Station communication

receives global common time[UTC] from any of the FineSyncSource like IRIG-
B, PTP or GPS.
• when SyncLostMode = NoBlock
• ERROR[1] indicates
• when SyncLostMode = Block, and the time quality of the hardware is not
within the set value [SyncAccLevel=1us, 4us or Unspecified]
• when SyncLostMode = BlockonLostUTC, the time quality of the hardware is
not within the set value [SyncAccLevel=1us, 4us or Unspecified] [OR] IED
doesn't receive global common time[UTC] from any of the FineSyncSource
like IRIG-B, PTP or GPS.

• SMPLLOST:
• NO[0] indicates that the merging unit samples are received from the merging unit
and are accepted
• YES[1] indicates
• when merging unit data are generated by internal substitution
• when one/more channel's Quality is not good
• when merging unit is in Testmode/detailed quality=Test, IED is not in test
mode

• MUSYNCH:
• OK[0] indicates
• when SyncLostMode = Block/BlockOnLostUTC, the time quality of the
hardware is within the set value [SyncAccLevel=1us, 4us or Unspecified] [AND]
merging unit is time synchronized [smpSynch flag in datastream is not equal
to 0] [AND] the hardware time matches the time in the datastream within 10
ms.
• when SyncLostMode = NoBlock, the merging unit samples are received
• ERROR[1] indicates
• when SyncLostMode = Block/BlockOnLostUTC, the time quality of the
hardware is not within the set value [SyncAccLevel=1us, 4us or Unspecified]
[OR] merging unit is not time synchronized [smpSynch flag in datastream is
equal to 0] [OR] the hardware time is out of 10 ms from the time in the
datastream.
• when SyncLostMode = NoBlock, the merging unit samples are not received

• TESTMODE:
• NO[0] indicates that No merging unit analog channels are in testmode
• YES[1] indicates that one/more subscribed channels are in testmode
• SIMMODE:
• NO[0] indicates that normal data is received and are accepted
• YES[1] indicates that the received datastream is tagged as simulated and are
accepted

Internal substitution can happen during the following conditions:

1. Transient block after receive error (sample loss)


2. Transient block after Simulated/Real Sample value stream transition
3. Transient block after recovery from substitution
4. No data from merging unit
5. Bad data from merging unit
6. Merging unit report lost sync[smpSynch=0] and SyncLostMode = Block/BlockOnLostUTC

Line distance protection REL670 1151


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 21 1MRK 506 370-UEN J
Station communication

7. IED time quality of hardware is not good [not within set value SyncAccLevel] and
SyncLostMode = Block/BlockOnLostUTC
8. Merging unit channel reported with quality other than good
9. Merging unit channel/channels is/are in testmode and the IED is not in testmode

During Internal substitution, the functions connected to that particular merging unit will be
blocked and the merging unit channel's analog values will be forced to 0 with quality as Invalid,
Substituted, Failure.

Timeout

TSYNCERR Indicates that there is some timeout on any configured time source or the time
quality is worse than specified in SynchAccLevel. The timeout is individually specified per time
source (PPS, IRIG-B, SNTP etc.) See section "Time synchronization TIMESYNCHGEN"

21.5.6.1 Conditional blocking GUID-D129543D-82BE-4F8A-9333-4C3470693F98 v1

Introduction GUID-9D9A73FA-505E-4936-BB55-E7D86AB8023B v1
Conditional blocking is a concept in the 670 series which improves resilience against errors in
network communication, time synchronization, and hardware. This is important for digital
substations where analogue data (some or even all) is sourced from the IEC61850 9-2 MUs
(merging units).

Conditional blocking functionality GUID-C12A5162-7F49-4FF0-98AA-BA362BC48070 v1


The overall idea with conditional blocking is to avoid blocking of the parts of an IED which can
safely continue the operation in presence of certain error conditions (listed below).

To make conditional blocking work as intended, there are configuration rules that need to be
followed. If an incorrect configuration is deployed, the IED functionality may be blocked
inadvertently, thereby reducing the availability of protection functions. An incorrect
configuration also increases the sensitivity to single point failures.

With a proper configuration, on the other hand, only functions directly affected by an error will
be blocked, while other functions will continue to operate.

Implementation GUID-D9880430-E6D6-42EE-B315-7E9279BEC913 v1
In Figure 669, two functions are shown, F1 and F2, where F1 takes data only from MU1, while F2
takes data from both MU1 and MU2.

3Ph Group
MU1 SMAI F1

3Ph Group
MU2 SMAI F2
IEC18001012-1-en.vsdx
IEC18001012 V1 EN-US

Figure 669: Implementation schematic


When F1 and F2 start-up, each function analyzes the analogue data which is driving it. This
information is used to determine how the function should be blocked during error conditions
separately.

1152 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 21
Station communication

Function F1 is independent of MU2, if MU2 is lost, this will not affect F1. It will execute its
algorithms as long as data from MU1 is available. Note that F1 will operate even with poor time
synchronization. This is possible because F1 only depends on data from a single MU.

Function F2 on the other hand, depends on the correct information and time synchronized
data being available from both MU1 and MU2. If any of the MUs fail, or if any of them indicates
the loss of time synchronization, F2 will be blocked.

Examples of error conditions GUID-AFB2C078-59A8-4DFD-AD6C-B458695E4FA5 v1


This section contains examples of error conditions that can trigger function blocking.

• Time synchronization is not available/correctly configured in the IED

• Time synchronization quality is poor

• Analogue MU data indicates bad time quality in the MU

• Analogue MU data indicates data error in the MU

• Analogue MU data is unavailable (for example, if a connection to an IEC 9-2 MU is lost)

• Hardware errors (for example, network switches and fibers, station clock failures etc.)

Depending on how the IED is configured, these kinds of errors will have a bigger or smaller
impact on how much of the IED functionality that is blocked.

Incorrect configuration GUID-7857CC4E-A7DF-4B85-BF4E-9470A02903E5 v1


As an example, consider an instance of OC4PTOC, which has four steps of functionality. In
Figure 670, it is configured with two 3-phase groups, one for current and one for voltage. The
analogue data comes from two different MUs.

IEC18001013-1-en.vsdx
IEC18001013 V1 EN-US

Figure 670: Incorrect configuration

Line distance protection REL670 1153


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 21 1MRK 506 370-UEN J
Station communication

Assume, that the user has configured one step in the OC4PTOC as non-directional, and
another step as directional. Because the analogue data comes from two different MUs, the
user should understand that the data from both MUs must be available and both must indicate
that they are time synchronized, for the directional step to operate.

Due to the way conditional blocking works, if one or both of the MUs indicate poor time
synchronization, then the entire function will be blocked. Unfortunately, in this example, this
will also block the non-directional over-current step, although it would be perfectly capable of
operating without time synchronization.

This shows the incorrect configuration from a conditional blocking perspective.

Correct configuration GUID-AA803422-5774-4BDE-B84E-2FCF465EE4D0 v1


In Figure 671, the configuration is changed so the user have two instances of the function,
where the non-directional over-current instance uses only currents from one MU, while the
directional over-current instance uses current and voltage from both the MUs.

IEC18001014-1-en.vsdx

IEC18001014 V1 EN-US

Figure 671: Correct configuration


If the time synchronization is lost, or if there is an error in the voltage modules of the MU, or if
the voltage MU is lost altogether, the non-directional instance will still be operative.

This is an example of how the user needs to configure the IED to ensure conditional blocking
works as intended.

Another way to avoid conditional blocking is to take currents as well as voltages from the
same MU. Thus, the usage of multiple SMAIs in itself is not a trigger of conditional blocking,
but the usage of multiple MUs can be. This also implies that hardware-wise, one should try to
not divide a 3-phase group of currents and voltages over multiple MUs, when this is possible
(this is really a consideration for the substation hardware setup).

Functions with multiple internal steps GUID-D067CD74-43CD-480E-9A50-4F978A8DF5D8 v1


The following functions have internal steps/functions, which also can be configured
incorrectly similar to the above description.

NS4PTOC, OC4PTOC, EF4PTOC

• Each step can be set differently with respect to directionality

1154 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 21
Station communication

SDEPSDE

• Directional overcurrent, non-directional residual overcurrent, and residual overvoltage

VRPVOC

• Voltage restrained overcurrent, undervoltage

LDRGFC

• Current variation, undercurrent, residual overcurrent, and undervoltage

CVGAPC

• Each step can be set differently with respect to directionality: Overcurrent1, Overcurrent2,
Undercurrent1, Undercurrent2, Overvoltage1, Overvoltage2, Undervoltage1, Undervoltage2

Time synchronization GUID-5DD58144-76EA-4019-A8EA-354E263810FB v1


A correct configuration also has to consider how the time synchronization is set up.

To begin with, a suitable station clock must be available. ABB recommends that PTP is used as
a time synchronization protocol.

Further, it is recommended that at least two station clocks are connected to the substation
network. This is to avoid the single point of failure. If one clock encounters an error, or loses its
connection to the network, the other clock will seamlessly take over the time synchronization
task, and thus avoid blocking due to lost time synchronization.

It is also required that PTP is active on all ports that send or receive sampled data on all
devices, to secure that the system time is common for all devices.

Synchronization via PTP GUID-F7D9C58F-CB87-4D2A-BC64-2B34D41557A4 v1


While synchronizing a station via PTP (IEC61850-9-3), the time propagates from the clock
through the system to each IED.

This means that during a transition, for example, when a clock regains time from the GPS
system after drifting for some time, there can be different times in different parts of a
substation.

Refer the following figure for a simple system:

Line distance protection REL670 1155


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 21 1MRK 506 370-UEN J
Station communication

GMC

MU2

REX 670

MU1 MU3

SAM600 - TS CT VT
IEC18001015-1-en.vsdx

IEC18001015 V1 EN-US

Figure 672: Synchronization via PTP

If the station clock is out of order for some time and then regains good synch from, for
example, the satellite system, the correct time will reach MU2 and the 670 first. Then, it will
propagate to MU1 and MU3 through the boundary clock in the 670. This means, that for a short
duration, MU1 and MU2 will both appear to be synchronized, but they will in practice have
different times. If the protection is not blocked during this condition, user will get a false trip.

To fix this problem, the synch-lost signal from the merging units is prolonged for 16 seconds in
the 670. The synch-lost signal is used for conditional blocking of protections which use data
from the TRM of the IED in combination with a merging unit. The maximum time frame
specified by IEC61850-9-3 to propagate the time and resynchronize is 16 seconds.

The same time frame applies for the internal synchronization of the 670. In the scenario where
PTP is used in combination with 9-2, the synch-lost signal is also prolonged with 16 seconds.
Again, this delay is needed to ensure that the correct time has propagated to all units before
blocked functions are released for operation.

21.5.6.2 IEC 61850 quality expander QUALEXP GUID-9C5DC78E-041B-422B-9668-320E62B847A2 v1

The quality expander component is used to display the detailed quality of an IEC/UCA
61850-9-2LE analog channel. The component expands the channel quality output of a Merging
Unit analog channel received in the IED as per the IEC 61850-7-3 standard. This component can
be used during the ACT monitoring to get the particular channel quality of the Merging Unit.

The expanded quality bits are visible on the outputs as per IEC 61850-7-3 standard. When
written to IED, the configuration will show the expanded form of the respective MU channel
quality information during the online monitoring in the ACT.

1156 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 21
Station communication

The validity status of the quality as described in IEC 61850-7-3 is expanded to Good, Invalid,
Reserved and Questionable (QUEST) outputs.

The detailed quality as described in IEC 61850-7-3 is expanded to Overflow, Out of Range
(OUTRANGE), Bad reference (BADREF), Oscillatory (OSC), Failure, old data, inconsistent
(INCONS) and inaccurate (INACC) outputs.

The source status of the quality as described in IEC 61850-7-3 is expanded to Process and
Substituted (SUBST) outputs.

The other quality statuses (Test, Operator Blocked (OPBLKD) and Derived) are shown as they
are.

The derived quality is the extension to IEC 61850-7-3. If the derived bit is set to 1, it indicates
that there is no physical sensor within the system to determine the value, but the value is
derived from a combination of values from other physical sensors. Typically, I4 or U4 are
derived if they are calculated as the sum of the three phase quantities.

The configured MU channel quality as described in IEC 61850-7-3 is available on LHMI. This can
be viewed under Main Menu/Diagnostics/Merging units/MUX:XXXX/XX Quality.

IEC16000074-1-en.vsdx
IEC16000074 V1 EN-US

Figure 673: Configured MU channel quality in LHMI

21.5.7 Technical data SEMOD172233-1 v1

SEMOD172236-2 v3

Table 951: IEC/UCA 61850-9-2LE communication protocol


Functions Value
Protocol IEC/UCA 61850-9-2LE
Communication speed for the IEDs 100BASE-FX

21.6 LON communication protocol IP14420-1 v1

21.6.1 Functionality M11924-3 v6

An optical network can be used within the substation automation system. This enables
communication with the IED through the LON bus from the operator’s workplace, from the
control center and also from other terminals.

LON communication protocol is specified in LonTalkProtocol Specification Version 3 from


Echelon Corporation and is designed for communication in control networks. These networks
are characterized by high speed for data transfer, short messages (few bytes), peer-to-peer

Line distance protection REL670 1157


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 21 1MRK 506 370-UEN J
Station communication

communication, multiple communication media, low maintenance, multivendor equipment,


and low support costs. LonTalk supports the needs of applications that cover a range of
requirements. The protocol follows the reference model for open system interconnection (OSI)
designed by the International Standardization Organization (ISO).

In this document the most common addresses for commands and events are available. For
other addresses, refer to section Related documents.

It is assumed that the reader is familiar with LON communication protocol in general.

21.6.2 Settings IP14441-1 v2

PID-593-SETTINGS v11

Table 952: HORZCOMM Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation
On

PID-4147-SETTINGS v7

Table 953: ADE Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation
On
TimerClass Slow - - Slow Timer class
Normal
Fast
TimeDomain Local without DST - - Local with DST Time domain
Local with DST

21.6.3 Operation principle IP14439-1 v2

M15083-3 v3
The speed of the network depends on the medium and transceiver design. With protection and
control devices, fiber optic media is used, which enables the use of the maximum speed of 1.25
Mbits/s. The protocol is a peer-to-peer protocol where all the devices connected to the
network can communicate with each other. The own subnet and node number are identifying
the nodes (max. 255 subnets, 127 nodes per one subnet).

The LON bus links the different parts of the protection and control system. The measured
values, status information, and event information are spontaneously sent to the higher-level
devices. The higher-level devices can read and write memorized values, setting values, and
other parameter data when required. The LON bus also enables the bay level devices to
communicate with each other to deliver, for example, interlocking information among the
terminals without the need of a bus master.

The LonTalk protocol supports two types of application layer objects: network variables and
explicit messages. Network variables are used to deliver short messages, such as measuring
values, status information, and interlocking/blocking signals. Explicit messages are used to
transfer longer pieces of information, such as events and explicit read and write messages to
access device data.

The benefits achieved from using the LON bus in protection and control systems include direct
communication among all terminals in the system and support for multi-master
implementations. The LON bus also has an open concept, so that the terminals can
communicate with external devices using the same standard of network variables.

1158 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 21
Station communication

Introduction of LON protocol M15083-8 v2


For more information, refer to LON bus, LonWorks Network in Protection and Control, User’s
manual and Technical description.

LON protocol M15083-11 v1

Configuration of LON M15083-13 v3


LON network tool (LNT) is a multi-purpose tool for LonWorks network configuration. All the
functions required for setting up and configuring a LonWorks network, is easily accessible on a
single tool program.

Activate LON Communication M15083-16 v3


Activate LON communication in the Parameter Setting tool under Main Menu/Configuration/
Communication/Station communication/ LON/HORZCOMM:1, where Operation must be set
to ON.

Add LON Device Types LNT M15083-19 v3


A new device is added to LON Network Tool from the Device menu or by installing the device
from the ABB LON Device Types package for LNT 505 using SLDT package version 1p2 r04.

LON net address M15083-22 v3


To establish a LON connection, the IED has to be given a unique net address. The net address
consists of a subnet and node number. This is accomplished with the LON Network Tool by
creating one device for each IED.

Vertical communication M15083-25 v1


Vertical communication describes communication between the monitoring devices and
protection and control IEDs. This communication includes sending of changed process data to
monitoring devices as events and transfer of commands, parameter data and disturbance
recorder files. This communication is implemented using explicit messages.

Events and indications M15083-28 v3


Events are sent to the monitoring devices using explicit messages (message code 44H) with
unacknowledged transport service of the LonTalk protocol. When a signal is changed in the
IED, one message with the value, quality and time is transmitted from terminal.

Binary events M15083-31 v6


Binary events are generated in Event function blocks EVENT:1 to EVENT:20 in the IEDs. The
EVENT function blocks have predefined LON addresses. Table 954 shows the LON addresses
to the first input on the EVENT function blocks. Addresses to the other inputs on the EVENT
function block are consecutive after the first input. For example, input 15 on EVENT:17 function
block has the address 1280 + 14 (15-1) = 1294.

For double indications, only the first eight inputs 1–8 must be used. Inputs 9–16 can be used
for other types of events at the same EVENT block.

Three EVENT function blocks EVENT:1 to EVENT:3 running with a fast loop time (3 ms) are
available as basic in the IEDs.. The remaining EVENT function blocks EVENT:4 to EVENT:9 run
with a loop time of 8 ms and EVENT:10 to EVENT:20 run with a loop time of 100 ms. The EVENT
blocks are used to send binary signals, integers, real time values like analogue data from
measuring functions and mA input modules as well as pulse counter signals.

16 pulse counter value function blocks PCFCNT:1 to PCFCNT:16, and 24 mA input service values
function blocks SMMI1_In1 to 6 – SMMI4_In1 to 6 are available in the IEDs.

The first LON address in every EVENT function block is found in table 954. The formula for
calculating the LON address is:

LON Address = (EVBlkNr-1)×16 + signalNr +1023

For instance, the first pin at Event block number 2 has the address: (2-1)×16 +1 +1023 = 1040

Line distance protection REL670 1159


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 21 1MRK 506 370-UEN J
Station communication

Table 954: LON adresses for EVENT functions


Function block First LON address in
function block
EVENT:1 1024
EVENT:2 1040
EVENT:3 1056
EVENT:4 1072
EVENT:5 1088
EVENT:6 1104
EVENT:7 1120
EVENT:8 1136
EVENT:9 1152
EVENT:10 1168
EVENT:11 1184
EVENT:12 1200
EVENT:13 1216
EVENT:14 1232
EVENT:15 1248
EVENT:16 1264
EVENT:17 1280
EVENT:18 1296
EVENT:19 1312
EVENT:20 1328

Event masks M15083-78 v4


Event mask for each input can be set individually from Parameter Setting Tool (PST) under:
Settings/IED settings/ Monitoring / Event Function or via parameter setting tool (PST) as
follows:

• No events
• OnSet, at pick-up of the signal
• OnReset, at drop-out of the signal
• OnChange, at both pick-up and drop-out of the signal
• AutoDetect, the EVENT function makes the reporting decision (reporting criteria for
integers has no semantic, prefer to be set by the user)

Single indication M15083-123 v3


Directly connected binary IO signal via binary input function block (SMBI) is always reported on
change, no changed detection is done in the EVENT function block. Other Boolean signals, for
example a start or a trip signal from a protection function is event masked in the EVENT
function block.

Double indications M15083-126 v3


Double indications can only be reported for the first 8 inputs on an EVENT function block.

• 00 generates an intermediate event with the read status 0


• 01 generates an open event with the read status 1
• 10 generates a close event with the read status 2
• 11 generates an undefined event with the read status 3

Analog value M15083-135 v4

1160 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 21
Station communication

All analog values are reported cyclic. The reporting interval is taken from the connected
function if there is a limit supervised signal. Otherwise it is taken from the EVENT function
block.

Command handling M15083-80 v4


Commands are transferred using transparent SPA-bus messages. The transparent SPA-bus
message is an explicit LON message which contains an ASCII character message following the
coding rules of the SPA-bus protocol. The message is sent using explicit messages with
message code 41H and using acknowledged transport service.

Both the SPA-bus command messages (R or W) and the reply messages (D, A or N) are sent
using the same message code. It is mandatory that one device sends out only one SPA-bus
message at a time to one node and waits for the reply before sending the next message.

For commands from the operator workplace to the IED for apparatus control, that is the
function blocks type SCSWI 1 to 30, SXCBR 1 to 18 and SXSWI 1 to 24, the SPA addresses are
according to table 955.
SEMOD116913-2 v2

Table 955: SPA addresses for commands from the operator workplace to the IED for apparatus control
Name Function SPA Description
block address
BL_CMD SCSWI01 1 I 5115 SPA parameters for block
command
BL_CMD SCSWI02 1 I 5139 SPA parameters for block
command
BL_CMD SCSWI02 1 I 5161 SPA parameters for block
command
BL_CMD SCSWI04 1 I 5186 SPA parameters for block
command
BL_CMD SCSWI05 1 I 5210 SPA parameters for block
command
BL_CMD SCSWI06 1 I 5234 SPA parameters for block
command
BL_CMD SCSWI07 1 I 5258 SPA parameters for block
command
BL_CMD SCSWI08 1 I 5283 SPA parameters for block
command
BL_CMD SCSWI09 1 I 5307 SPA parameters for block
command
BL_CMD SCSWI10 1 I 5331 SPA parameters for block
command
BL_CMD SCSWI11 1 I 5355 SPA parameters for block
command
BL_CMD SCSWI12 1 I 5379 SPA parameters for block
command
BL_CMD SCSWI13 1 I 5403 SPA parameters for block
command
BL_CMD SCSWI14 1 I 5427 SPA parameters for block
command
BL_CMD SCSWI15 1 I 5451 SPA parameters for block
command
BL_CMD SCSWI16 1 I 5475 SPA parameters for block
command
BL_CMD SCSWI17 1 I 5499 SPA parameters for block
command
Table continues on next page

Line distance protection REL670 1161


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 21 1MRK 506 370-UEN J
Station communication

Name Function SPA Description


block address
BL_CMD SCSWI18 1 I 5523 SPA parameters for block
command
BL_CMD SCSWI19 1 I 5545 SPA parameters for block
command
BL_CMD SCSWI20 1 I 5571 SPA parameters for block
command
BL_CMD SCSWI21 1 I 5594 SPA parameters for block
command
BL_CMD SCSWI22 1 I 5619 SPA parameters for block
command
BL_CMD SCSWI23 1 I 5643 SPA parameters for block
command
BL_CMD SCSWI24 1 I 5667 SPA parameters for block
command
BL_CMD SCSWI25 1 I 5691 SPA parameters for block
command
BL_CMD SCSWI26 1 I 5715 SPA parameters for block
command
BL_CMD SCSWI27 1 I 5739 SPA parameters for block
command
BL_CMD SCSWI28 1 I 5763 SPA parameters for block
command
BL_CMD SCSWI29 1 I 5787 SPA parameters for block
command
BL_CMD SCSWI30 1 I 5811 SPA parameters for block
command
BL_CMD SCSWI31 1 I 5835 SPA parameters for block
command
BL_CMD SCSWI32 1 I 5859 SPA parameters for block
command
CANCEL SCSWI01 1 I 5107 SPA parameters for cancel
command
CANCEL SCSWI02 1 I 5131 SPA parameters for cancel
command
CANCEL SCSWI03 1 I 5153 SPA parameters for cancel
command
CANCEL SCSWI04 1 I 5178 SPA parameters for cancel
command
CANCEL SCSWI05 1 I 5202 SPA parameters for cancel
command
CANCEL SCSWI06 1 I 5226 SPA parameters for cancel
command
CANCEL SCSWI07 1 I 5250 SPA parameters for cancel
command
CANCEL SCSWI08 1 I 5275 SPA parameters for cancel
command
CANCEL SCSWI09 1 I 5299 SPA parameters for cancel
command
CANCEL SCSWI10 1 I 5323 SPA parameters for cancel
command
CANCEL SCSWI11 1 I 5347 SPA parameters for cancel
command
Table continues on next page

1162 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 21
Station communication

Name Function SPA Description


block address
CANCEL SCSWI12 1 I 5371 SPA parameters for cancel
command
CANCEL SCSWI13 1 I 5395 SPA parameters for cancel
command
CANCEL SCSWI14 1 I 5419 SPA parameters for cancel
command
CANCEL SCSWI15 1 I 5443 SPA parameters for cancel
command
CANCEL SCSWI16 1 I 5467 SPA parameters for cancel
command
CANCEL SCSWI17 1 I 5491 SPA parameters for cancel
command
CANCEL SCSWI18 1 I 5515 SPA parameters for cancel
command
CANCEL SCSWI19 1 I 5537 SPA parameters for cancel
command
CANCEL SCSWI20 1 I 5563 SPA parameters for cancel
command
CANCEL SCSWI21 1 I 5586 SPA parameters for cancel
command
CANCEL SCSWI22 1 I 5611 SPA parameters for cancel
command
CANCEL SCSWI23 1 I 5635 SPA parameters for cancel
command
CANCEL SCSWI24 1 I 5659 SPA parameters for cancel
command
CANCEL SCSWI25 1 I 5683 SPA parameters for cancel
command
CANCEL SCSWI26 1 I 5707 SPA parameters for cancel
command
CANCEL SCSWI27 1 I 5731 SPA parameters for cancel
command
CANCEL SCSWI28 1 I 5755 SPA parameters for cancel
command
CANCEL SCSWI29 1 I 5779 SPA parameters for cancel
command
CANCEL SCSWI30 1 I 5803 SPA parameters for cancel
command
CANCEL SCSWI31 1 I 5827 SPA parameters for cancel
command
CANCEL SCSWI32 1 I 5851 SPA parameters for cancel
command
SELECTOpen=00, SCSWI01 1 I 5105 SPA parameters for select
SELECTClose=01, (Open/Close) command
SELOpen+ILO=10, Note: Send select command
SELClose+ILO=11, before operate command
SELOpen+SCO=20,
SELClose+SCO=21,
SELOpen+ILO+SCO=30,
SELClose+ILO+SCO=31
SELECTOpen=00, SCSWI02 1 I 5129 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
Table continues on next page

Line distance protection REL670 1163


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 21 1MRK 506 370-UEN J
Station communication

Name Function SPA Description


block address
SELECTOpen=00, SCSWI03 1 I 5151 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI04 1 I 5176 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI05 1 I 5200 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI06 1 I 5224 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI07 1 I 5248 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI08 1 I 5273 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI09 1 I 5297 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI10 1 I 5321 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI11 1 I 5345 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI12 1 I 5369 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI13 1 I 5393 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI14 1 I 5417 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI15 1 I 5441 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI16 1 I 5465 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI17 1 I 5489 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI18 1 I 5513 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI19 1 I 5535 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI20 1 I 5561 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI21 1 I 5584 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI22 1 I 5609 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI23 1 I 5633 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI24 1 I 5657 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI25 1 I 5681 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI26 1 I 5705 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI27 1 I 5729 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI28 1 I 5753 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
Table continues on next page

1164 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 21
Station communication

Name Function SPA Description


block address
SELECTOpen=00, SCSWI29 1 I 5777 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI30 1 I 5801 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI31 1 I 5825 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI32 1 I 5849 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI01 1 I 5106 SPA parameters for operate
ExcClose=01, (Open/Close) command
ExcOpen+ILO=10, Note: Send select command
ExcClose+ILO=11, before operate command
ExcOpen+SCO=20,
ExcClose+SCO=21,
ExcOpen+ILO+SCO=30,
ExcClose+ILO+SCO=31
ExcOpen=00, SCSWI02 1 I 5130 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI02 1 I 5152 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI04 1 I 5177 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI05 1 I 5201 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI06 1 I 5225 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI07 1 I 5249 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI08 1 I 5274 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI09 1 I 5298 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI10 1 I 5322 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI11 1 I 5346 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI12 1 I 5370 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI13 1 I 5394 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI14 1 I 5418 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI15 1 I 5442 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI16 1 I 5466 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI17 1 I 5490 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI18 1 I 5514 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI19 1 I 5536 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
Table continues on next page

Line distance protection REL670 1165


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 21 1MRK 506 370-UEN J
Station communication

Name Function SPA Description


block address
ExcOpen=00, SCSWI20 1 I 5562 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI21 1 I 5585 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI22 1 I 5610 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI23 1 I 5634 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI24 1 I 5658 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI25 1 I 5682 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI26 1 I 5706 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI27 1 I 5730 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI28 1 I 5754 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI29 1 I 5778 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI30 1 I 5802 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI31 1 I 5826 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI32 1 I 5850 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
Sub Value SXCBR01 2 I 7854 SPA parameter for position to
be substituted
Note: Send the value before
Enable
Sub Value SXCBR02 2 I 7866 SPA parameter for position to
be substituted
Sub Value SXCBR03 2 I 7884 SPA parameter for position to
be substituted
Sub Value SXCBR04 2 I 7904 SPA parameter for position to
be substituted
Sub Value SXCBR05 2 I 7923 SPA parameter for position to
be substituted
Sub Value SXCBR06 2 I 7942 SPA parameter for position to
be substituted
Sub Value SXCBR07 2 I 7961 SPA parameter for position to
be substituted
Sub Value SXCBR08 2 I 7980 SPA parameter for position to
be substituted
Sub Value SXCBR09 3I7 SPA parameter for position to
be substituted
Sub Value SXCBR10 3 I 26 SPA parameter for position to
be substituted
Sub Value SXCBR11 3 I 45 SPA parameter for position to
be substituted
Sub Value SXCBR12 3 I 56 SPA parameter for position to
be substituted
Table continues on next page

1166 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 21
Station communication

Name Function SPA Description


block address
Sub Value SXCBR13 3 I 74 SPA parameter for position to
be substituted
Sub Value SXCBR14 3 I 94 SPA parameter for position to
be substituted
Sub Value SXCBR15 3 I 120 SPA parameter for position to
be substituted
Sub Value SXCBR16 3 I 133 SPA parameter for position to
be substituted
Sub Value SXCBR17 3 I 158 SPA parameter for position to
be substituted
Sub Value SXCBR18 3 I 179 SPA parameter for position to
be substituted
Sub Value SXSWI01 3 I 196 SPA parameter for position to
be substituted
Sub Value SXSWI02 3 I 216 SPA parameter for position to
be substituted
Sub Value SXSWI03 3 I 235 SPA parameter for position to
be substituted
Sub Value SXSWI04 3 I 254 SPA parameter for position to
be substituted
Sub Value SXSWI05 3 I 272 SPA parameter for position to
be substituted
Sub Value SXSWI06 3 I 292 SPA parameter for position to
be substituted
Sub Value SXSWI07 3 I 310 SPA parameter for position to
be substituted
Sub Value SXSWI08 3 I 330 SPA parameter for position to
be substituted
Sub Value SXSWI09 3 I 348 SPA parameter for position to
be substituted
Sub Value SXSWI10 3 I 359 SPA parameter for position to
be substituted
Sub Value SXSWI11 3 I 378 SPA parameter for position to
be substituted
Sub Value SXSWI12 3 I 397 SPA parameter for position to
be substituted
Sub Value SXSWI13 3 I 416 SPA parameter for position to
be substituted
Sub Value SXSWI14 3 I 435 SPA parameter for position to
be substituted
Sub Value SXSWI15 3 I 454 SPA parameter for position to
be substituted
Sub Value SXSWI16 3 I 473 SPA parameter for position to
be substituted
Sub Value SXSWI17 3 I 492 SPA parameter for position to
be substituted
Sub Value SXSWI18 3 I 511 SPA parameter for position to
be substituted
Sub Value SXSWI19 3 I 530 SPA parameter for position to
be substituted
Sub Value SXSWI20 3 I 549 SPA parameter for position to
be substituted
Table continues on next page

Line distance protection REL670 1167


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 21 1MRK 506 370-UEN J
Station communication

Name Function SPA Description


block address
Sub Value SXSWI21 3 I 568 SPA parameter for position to
be substituted
Sub Value SXSWI22 3 I 587 SPA parameter for position to
be substituted
Sub Value SXSWI23 3 I 606 SPA parameter for position to
be substituted
Sub Value SXSWI24 3 I 625 SPA parameter for position to
be substituted
Sub Value SXSWI25 3 I 644 SPA parameter for position to
be substituted
Sub Value SXSWI26 3 I 663 SPA parameter for position to
be substituted
Sub Value SXSWI27 3 I 682 SPA parameter for position to
be substituted
Sub Value SXSWI28 3 I 701 SPA parameter for position to
be substituted
Sub Enable SXCBR01 2 I 7855 SPA parameter for substitute
enable command
Note: Send the Value before
Enable
Sub Enable SXCBR02 2 I 7865 SPA parameter for substitute
enable command
Sub Enable SXCBR03 2 I 7885 SPA parameter for substitute
enable command
Sub Enable SXCBR04 2 I 7903 SPA parameter for substitute
enable command
Sub Enable SXCBR05 2 I 7924 SPA parameter for substitute
enable command
Sub Enable SXCBR06 2 I 7941 SPA parameter for substitute
enable command
Sub Enable SXCBR07 2 I 7962 SPA parameter for substitute
enable command
Sub Enable SXCBR08 2 I 7979 SPA parameter for substitute
enable command
Sub Enable SXCBR09 3I8 SPA parameter for substitute
enable command
Sub Enable SXCBR10 3 I 25 SPA parameter for substitute
enable command
Sub Enable SXCBR11 3 I 46 SPA parameter for substitute
enable command
Sub Enable SXCBR12 3 I 55 SPA parameter for substitute
enable command
Sub Enable SXCBR13 3 I 75 SPA parameter for substitute
enable command
Sub Enable SXCBR14 3 I 93 SPA parameter for substitute
enable command
Sub Enable SXCBR15 3 I 121 SPA parameter for substitute
enable command
Sub Enable SXCBR16 3 I 132 SPA parameter for substitute
enable command
Sub Enable SXCBR17 3 I 159 SPA parameter for substitute
enable command
Table continues on next page

1168 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 21
Station communication

Name Function SPA Description


block address
Sub Enable SXCBR18 3 I 178 SPA parameter for substitute
enable command
Sub Enable SXSWI01 3 I 197 SPA parameter for substitute
enable command
Sub Enable SXSWI02 3 I 215 SPA parameter for substitute
enable command
Sub Enable SXSWI03 3 I 234 SPA parameter for substitute
enable command
Sub Enable SXSWI04 3 I 252 SPA parameter for substitute
enable command
Sub Enable SXSWI05 3 I 271 SPA parameter for substitute
enable command
Sub Enable SXSWI06 3 I 290 SPA parameter for substitute
enable command
Sub Enable SXSWI07 3 I 309 SPA parameter for substitute
enable command
Sub Enable SXSWI08 3 I 328 SPA parameter for substitute
enable command
Sub Enable SXSWI09 3 I 347 SPA parameter for substitute
enable command
Sub Enable SXSWI10 3 I 360 SPA parameter for substitute
enable command
Sub Enable SXSWI11 3I 379 SPA parameter for substitute
enable command
Sub Enable SXSWI12 3 I 398 SPA parameter for substitute
enable command
Sub Enable SXSWI13 3 I 417 SPA parameter for substitute
enable command
Sub Enable SXSWI14 3 I 436 SPA parameter for substitute
enable command
Sub Enable SXSWI15 3 I 455 SPA parameter for substitute
enable command
Sub Enable SXSWI16 3 I 474 SPA parameter for substitute
enable command
Sub Enable SXSWI17 3 I 493 SPA parameter for substitute
enable command
Sub Enable SXSWI18 3 I 512 SPA parameter for substitute
enable command
Sub Enable SXSWI19 3 I 531 SPA parameter for substitute
enable command
Sub Enable SXSWI20 3 I 550 SPA parameter for substitute
enable command
Sub Enable SXSWI21 3 I 569 SPA parameter for substitute
enable command
Sub Enable SXSWI22 3 I 588 SPA parameter for substitute
enable command
Sub Enable SXSWI23 3 I 607 SPA parameter for substitute
enable command
Sub Enable SXSWI24 3 I 626 SPA parameter for substitute
enable command
Sub Enable SXSWI25 3 I 645 SPA parameter for substitute
enable command
Table continues on next page

Line distance protection REL670 1169


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 21 1MRK 506 370-UEN J
Station communication

Name Function SPA Description


block address
Sub Enable SXSWI26 3 I 664 SPA parameter for substitute
enable command
Sub Enable SXSWI27 3 I 683 SPA parameter for substitute
enable command
Sub Enable SXSWI28 3 I 702 SPA parameter for substitute
enable command
Update Block SXCBR01 2 I 7853 SPA parameter for update block
command
Update Block SXCBR02 2 I 7864 SPA parameter for update block
command
Update Block SXCBR03 2 I 7883 SPA parameter for update block
command
Update Block SXCBR04 2 I 7905 SPA parameter for update block
command
Update Block SXCBR05 2 I 7922 SPA parameter for update block
command
Update Block SXCBR06 2 I 7943 SPA parameter for update block
command
Update Block SXCBR07 2 I 7960 SPA parameter for update block
command
Update Block SXCBR08 2 I 7981 SPA parameter for update block
command
Update Block SXCBR09 3I6 SPA parameter for update block
command
Update Block SXCBR10 3 I 27 SPA parameter for update block
command
Update Block SXCBR11 3 I 44 SPA parameter for update block
command
Update Block SXCBR12 3 I 57 SPA parameter for update block
command
Update Block SXCBR13 3 I 73 SPA parameter for update block
command
Update Block SXCBR14 3 I 92 SPA parameter for update block
command
Update Block SXCBR15 3 I 122 SPA parameter for update block
command
Update Block SXCBR16 3 I 131 SPA parameter for update block
command
Update Block SXCBR17 3 I 160 SPA parameter for update block
command
Update Block SXCBR18 3 I 177 SPA parameter for update block
command
Update Block SXSWI01 3 I 198 SPA parameter for update block
command
Update Block SXSWI02 3 I 214 SPA parameter for update block
command
Update Block SXSWI03 3 I 236 SPA parameter for update block
command
Update Block SXSWI04 3 I 253 SPA parameter for update block
command
Update Block SXSWI05 3 I 273 SPA parameter for update block
command
Table continues on next page

1170 Line distance protection REL670


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 506 370-UEN J Section 21
Station communication

Name Function SPA Description


block address
Update Block SXSWI06 3 I 291 SPA parameter for update block
command
Update Block SXSWI07 3 I 311 SPA parameter for update bloc

You might also like