CUSTOMER

ITC LIMITED
PAPERBOARDS & SPECIALTY PAPERS DIVISION
UNIT:TRIBENI , HOOGHLY DISTRICT,WEST BENGAL
PROJECT
1 X 12 MW COGENERATION POWER PLANT

OWNER’s CONSULTANT
SPB PROJECTS AND CONSULTANCY LIMITED
CHENNAI

SUPPLIER
ENMAS GB POWER SYSTEMS PROJECTS LIMITED
CHENNAI-600 018.

NAME SIGN DATE


TITLE:
PPD AVK 24/10/11

DESIGN BASIS REPORT FOR WATER TREATMENT


CHD KRG 25/10/11
SYSTEM
APPD SRS 27/10/11 DOC NO.: REV NO.

SIZE : A4 EN09-109-G-DOC-0602 0

SUBMITTED FOR APPROVAL INFORMATION REFERENCE RECORD CONSTRUCTION

http://slidepdf.com/reader/full/dbr-for-water-treatment 1/28
7/23/2019 DBR for Water Treatment

Project Description Doc. No Rev Sheet

12MW- ITC
DESIGN BASIS REPORT FOR WATER EN09-109-G-DOC- 00 2 of 28
LIMITED, TRIBENI
TREATMENT SYSTEM 0602
UNIT.

Rev Altered
Date Reason for Revision
No. Checked

http://slidepdf.com/reader/full/dbr-for-water-treatment 2/28
7/23/2019 DBR for Water Treatment

Project Description Doc. No Rev Sheet

12MW- ITC
DESIGN BASIS REPORT FOR WATER EN09-109-G-DOC- 00 3 of 28
LIMITED, TRIBENI
TREATMENT SYSTEM 0602
UNIT.

CONTENTS

SL.NO Page
DESCRIPTION
No.
1 INTRODUCTION 4
2 PROJECT INFORMATION AND DESIGN BASIS 5
2.1 SITE DATA 5
2.2 DESIGN CONDITIONS 5
2.3 POWER SUPPLY FOR ELECTRICAL SYSTEM 5
3 DESIGN BASIS 6
4.0 WATER SYSTEM DESIGN INPUTS 10
5.0 WATER SYSTEM CAPACITY – CALCULATIONS 10
6.0 WATER SYSTEM SCHEME 14
7.0 WATER TREATMENT SYSTEM DESCRIPTION 14
8.0 ELECTRICAL SYSTEM 17
9.0 CONTROL & INSTRUMENTATION SYSTEM 18
ANNEXURES
01 ANNEXURE – 01 – Raw Water Analysis Reports 19
Reports -1 ( Technical Contract document page no 09 OF 468) 19
Report -2 - Report No. W(D)/10-11/2873 dated 09.03.2011 20
Report – 3- Report No . W(D)/11-12/686 Sep 01 , 2011 23
02 ANNEXURE – 02 – Return Condensate Analysis Reports 25
Reports -1 ( Technical Contract document page no 09 OF 468) 25
Report – 3- Report No . W(D)/11-12/687 Sep 01 , 2011 26

http://slidepdf.com/reader/full/dbr-for-water-treatment 3/28
7/23/2019 DBR for Water Treatment

Project Description Doc. No Rev Sheet

12MW- ITC
DESIGN BASIS REPORT FOR WATER EN09-109-G-DOC- 00 4 of 28
LIMITED, TRIBENI
TREATMENT SYSTEM 0602
UNIT.

1. INTRODUCTION

M/s. ITC LIMITED, Paperboards & Specialty Papers Division, Unit: Tribeni (hereinafter
referred to as ITC) is developing a coal based Cogeneration Power Plant (CPP) in their existing
plant at Chandrahati, Dist. Hooghly, West Bengal. The generated power shall cater to the paper
plant needs and power plant auxiliary requirement.

This Design Basis Report (DBR) covers the details pertaining to Water Treatment system for
the above 12 MW Cogeneration Power Plant.

http://slidepdf.com/reader/full/dbr-for-water-treatment 4/28
7/23/2019 DBR for Water Treatment

Project Description Doc. No Rev Sheet

12MW- ITC
DESIGN BASIS REPORT FOR WATER EN09-109-G-DOC- 00 5 of 28
LIMITED, TRIBENI
TREATMENT SYSTEM 0602
UNIT.

2. PROJECT INFORMATION AND DESIGN BASIS

2.1 SITE DATA

i Location Chandrahati, Dist. Hooghly, West Bengal


ii Elevation above mean sea level 27m

iii Wind velocity (max) 50 m/sec (as per IS 875 Part III)

iv Seismic Data Zone –III (As per IS 1893 : 2002)


v Maximum dry bulb temperature 48°C
vi Minimum dry bulb temperature 6°C

2.2 DESIGN CONDITIONS

i Design ambient temperature for plant equipment °C 35


ii Design temperature for electrical equipment °C 50
iii Design wet bulb temperature °C 28

iv Relative Humidity - Design % 60

2.3. POWER SUPPLY FOR ELECTRICAL SYSTEM

Auxiliary & Control Voltage:

Single phase motors : 240V,50Hz,1 Phase


Three Motors : 415V, 50 Hz, 3 Phase
Control Supply for LV Starters : 110V(55-0(E)55), 50 Hz, 1 Phase
Panel lighting & space heater : 240V, 50 Hz, 1 Phase
Motor space heater : 240V, 50 Hz, 1 Phase
Supply Variations:
Voltage Variation : ±10%
Frequency Variation : ±5%
Combined variation of voltage & Frequency : 10%
System Short Circuit Current:
415V LV System : 50 KA rms for 1 second
System Grounding:
415V LV System : Solidly Earthed

http://slidepdf.com/reader/full/dbr-for-water-treatment 5/28
7/23/2019 DBR for Water Treatment

Project Description Doc. No Rev Sheet

12MW- ITC
DESIGN BASIS REPORT FOR WATER EN09-109-G-DOC- 00 6 of 28
LIMITED, TRIBENI
TREATMENT SYSTEM 0602
UNIT.

Design Margin for motor:


Motors shall have 15% margin up to and including 110kW rating and 10% margin for above
110kW rating, over and above the shaft power requirement of driven equipment at design point.

3.0 DESIGN BASIS

3.1 RAW WATER ANALYSIS (For Power Cycle Make-up Stream & Cooling tower
Make-up Stream)

The raw water analysis reports received from the OWNER is provided in the enclosed
“ANNEXURE – 01 – RAW WATER ANALYSIS REPORTS”

The raw water analysis reports (Refer Annexure-1) were studied and selected maximum values
are indicted below. The system will be designed considering these parameters.

Sl
Test parameters Unit Design parameter
No.
1. Colour Hazen 1
2. Odour Unobjectionable
3. Taste: Agreeable
4. Turbidity NTU 4.2
5. pH 7.2-7.6
6. TSS ppm 10
7. TDS ppm 474
8. Total Hardness as caco3 ppm 294
9. Total Alkalinity ppm 405
10. Colloidal Silica as SiO2 mg/l 0.2
11. Sodium as Na mg/l 37.8
12. Potasium as K mg/l 12.6
13. Ammonium as NH4 mg/l <0.01

14. Barium as Ba mg/l 0.1

http://slidepdf.com/reader/full/dbr-for-water-treatment 6/28
7/23/2019 DBR for Water Treatment

Project Description Doc. No Rev Sheet

12MW- ITC
DESIGN BASIS REPORT FOR WATER EN09-109-G-DOC- 00 7 of 28
LIMITED, TRIBENI
TREATMENT SYSTEM 0602
UNIT.

Sl
Test parameters Unit Design parameter
No.
15. P - Alkalinity as CaCO3 mg/l Nil
16. M - Alkalinity as CaCO3 mg/l 293
17. Bi Carbonate as CaCO3 mg/l 293
18. Carbonate as CaCO3 mg/l Nil
19. Iron as (Ferrous ) mg/l <0.1

20. Iron as (Ferric) mg/l 0.23


21. Calcium as Ca mg/l 71
22. LimE as CaO mg/l 99.4
23. Magnesium as Mg mg/l 17.3
24. Sulphate as SO4 mg/l <5
25. sulphide as S2- mg/l <0.1
26. Chloride as Cl mg/l 12

27. Nitrate as NO3 mg/l 1.8


28. Nitrate Nitrogen as N mg/l 0.41
29. Nitrite as NO2 mg/l < 0.02
30. Reactive Silica mg/l 14.3
Dissolved Phosphate as
31. mg/l < 0.003
PO4
32. Total phosphate as PO4 mg/l < 0.003
33. Copper as Cu mg/l < 0.05
34. Manganese as Mn mg/l 0.11
35. Fluoride as F mg/l 0.48
36. Nickel as Ni mg/l < 0.05
37. Mercury as Hg mg/l < 0.001
38. Cadmium as Cd mg/l < 0.01
39. Total Chromium as Cr mg/l < 0.05
40. Arsenic as As mg/1 0.008
41. Cyanide as CN mg/l < 0.05

http://slidepdf.com/reader/full/dbr-for-water-treatment 7/28
7/23/2019 DBR for Water Treatment

Project Description Doc. No Rev Sheet

12MW- ITC
DESIGN BASIS REPORT FOR WATER EN09-109-G-DOC- 00 8 of 28
LIMITED, TRIBENI
TREATMENT SYSTEM 0602
UNIT.

Sl
Test parameters Unit Design parameter
No.
42. Lead as Pb mg/l < 0.05
43. Zinc as Zn mg/l < 0.05
44. Aluminium as Al mg/l < 0.03
45. Dissolved Volatile solids mg/l 88
46. Dissolved Fixed solids mg/l 250

47. BOD mg/l < 5.0


48. COD mg/l < 5.0
49. Dissolved Oxygen mg/l 6.2
Oxygen Absorbed in 4 hrs
50. mg/l 0.1
at 37°C
51. Ammoniacal Nitrogen mg/l < 0.01
52. Ammonia as NH3 mg/l < 0.01

53. Free Carbondioxide as CO2 mg/l 0.88

3.2 PROCESS CONDENSATE WATER ANALYSIS


The process condensate water analysis reports received from the OWNER is provided in the
enclosed “ANNEXURE – 02 – PROCESS CONDENSATE RAW WATER ANALYSIS
REPORTS”

The process condensate water analysis reports were studied and selected maximum values
are indicted below. The systems will be designed considering these parameter .

Sl No. Test parameters Unit Results


1. pH ppm 7.1 - 8.95
2. TDS ppm 2.90
3. Conductivity microsiemens/cm 7
4. Hardness ppm 1
5. SiO2 ppm Nil
6. TSS ppm 12
7. Total Dissolved Phosphate Ppm 0.005

http://slidepdf.com/reader/full/dbr-for-water-treatment 8/28
7/23/2019 DBR for Water Treatment

Project Description Doc. No Rev Sheet

12MW- ITC
DESIGN BASIS REPORT FOR WATER EN09-109-G-DOC- 00 9 of 28
LIMITED, TRIBENI
TREATMENT SYSTEM 0602
UNIT.

3.3 PROPOSED WATER TREATMENT PLANT OUTPUT PARAMETERS

The following are the proposed water treatment plant output parameters

a. DM WATER QUALITY AT MB OUTLET (before pH dosing)


TREATED WATER
SL.NO DESCRIPTION UNIT QUALITY

1. Colloidal silica mg/l Nil


2. Reactive silica mg/l < 0.02
3. PH value 6.5-7.5
4. micro
Conductivity < 0.3
mho/cm

b. DM WATER QUALITY AT CONDENSATE POLISHING UNIT (CPU)


OUTLET (before pH dosing)
TREATED WATER
SL.NO DESCRIPTION UNIT QUALITY
1. PH value 6.5-7.5
2. micro
Conductivity < 0.3
mho/cm
3. Reactive Silica Mg/l < 0.02

c. TREATED COOLING TOWER MAKE UP WATER QUALITY

TREATED WATER
SL.NO DESCRIPTION UNIT QUALITY
1 pH VALUE 6.5 – 8.5
2 TOTAL HARDNESS mg/l Nil
3 GENERAL APPEARANCE Clear & Colorless

http://slidepdf.com/reader/full/dbr-for-water-treatment 9/28
7/23/2019 DBR for Water Treatment

Project Description Doc. No Rev Sheet

12MW- ITC
DESIGN BASIS REPORT FOR WATER EN09-109-G-DOC- 00 10 of 28
LIMITED, TRIBENI
TREATMENT SYSTEM 0602
UNIT.

4.0 MAKE-UP WATER SYSTEM DESIGN PROCESS INPUTS


Sl.
DESCRIPTION UNIT Data
No
4.1. AFBC Boiler capacity BMCR TPH 72
4.2. AFBC Boiler capacity TMCR TPH 66.6
4.3. Blow down (maximum) for WTP sizing per Boiler % 3
4.4. Blow down (normal) for plant operation per Boiler % 1.5
Emergency make up requirement during boiler
4.5. % 30
start up (% of AFBC boiler MCR requirement)

5.0 MAKE-UP WATER SYSTEM CAPACITY – CALCULATIONS


SL.
DESCRIPTION UNIT Data
No
5.1.0. DM WATER SYSTEM

Boiler Make up water requirement


Blow down water quantity from AFBC Boiler for DM
5.1.1. TPH 2.16
plant sizing (ref. clauses 4.1 &.4.3)
5.1.2. Blow down water quantity per day TPD 51.84
AFBC TMCR Boiler Feed water requirement (at
5.1.3. TPH 68.01
deaerator outlet)
Bleed steam for De aerator (as per HMBD – Load

5.1.4. point LC-1(Max process steam – max steam TPH 9.15


consumption – max power generation))
Process Return condensate (Considered “0” as the
5.1.5. TPH 0
CPU outlet is fed to DM Water storage tank)
Condensate from Water cooled condenser (as per
5.1.6. TPH 21.39
HMBD Load point LC-1)
5.1.7. HP Heater drain (as per HMBD Load point LC-1) TPH 7.44
AFBC Boiler Makeup water (ref. Clauses 4.1-
5.1.8. (5.1.4+5.1.5+5.1.6+5.1.7)) TPH 34.02

http://slidepdf.com/reader/full/dbr-for-water-treatment 10/28
7/23/2019 DBR for Water Treatment

Project Description Doc. No Rev Sheet

12MW- ITC
DESIGN BASIS REPORT FOR WATER EN09-109-G-DOC- 00 11 of 28
LIMITED, TRIBENI
TREATMENT SYSTEM 0602
UNIT.

SL.
DESCRIPTION UNIT Data
No
Spray water for process PRDS (as per HMBD Load
5.1.9. TPH 1.414
point LC-1)
Total Boiler Makeup Water requirement for AFBC
5.1.10. TPD 850.4
Boiler((5.1.8+5.1.9) x 24)
Net Process Condensate water available after

5.1.11. treatment from CPU Unit (after deducting MB TPD 348


regeneration water of 12TPD) (360 m3/hr-12.0 m3/d)
5.1.12. DM Water requirement m /day 502.4
DM Plant
5.1.13. No. of operating hours per day for normal DM plant hrs. 20
Required capacity of DM plant (ref. Clauses (5.1.12 / 3
5.1.14. m /hr 25.12
5.1.13)

5.1.15. No. of DM streams provided Nos. 2


5.1.16. Capacity of each stream provided m3/hr 30
Condensate Polishing Unit
Process return condensate water (50% Process 3
5.1.17. m /day 360
condensate return)
No. of operating hours per day for process return
5.1.18. hrs. 21
condensate water polishing unit (DM plant)
Process return condensate water polishing unit (DM 3
5.1.19. plant) capacity as per requirement m /hr 17.14

Process return condensate water polishing unit (DM 3


5.1.20. m /hr 21
plant) Provided (as per contract )
DM Make up Pumps cum Initial fill pumps
Emergency make up required during one Boiler start
5.1.21. m 3/hr 21.6
up (ref. Clauses 4.1 &4.5 )
Normal make up requirement of operating Boiler (reg. 3

5.1.22. Clauses 4.1 & 4.4 ) considering blowdown losses m /hr 1.08

http://slidepdf.com/reader/full/dbr-for-water-treatment 11/28
7/23/2019 DBR for Water Treatment

Project Description Doc. No Rev Sheet

12MW- ITC
DESIGN BASIS REPORT FOR WATER EN09-109-G-DOC- 00 12 of 28
LIMITED, TRIBENI
TREATMENT SYSTEM 0602
UNIT.

SL.
DESCRIPTION UNIT Data
No
Total make up requirement during Boiler start up
5.1.23. m 3/hr 22.6
(5.1.21 + 5.1.22)
Total DM make up water requirement during 3
5.1.24. m /hr 35
operation (ref. Clause 5.1.10 / 24)
Make up capacity available through De-aerator make- 3
5.1.25. m /hr 35
up pumps (1W+1S)
DM Tank
DM make up water requirement per day (ref. Clause 3
5.1.26. m /day 850.4
5.1.24)
5.1.27. DM tank storage capacity as per contract m 2 X 250
5.1.28. DM storage tank provided m 2 X 250
5.1.29. Water volume of AFBC Boiler m 70

5.1.30. Adequate DM storage capacity to cater to fill volume Yes


of one Boiler?
5.2.0. REVERSE OSMOSIS WATER SYSTEM
Degassed water input per day per stream to DM plant
3
5.2.1. considering regeneration requirement (ref. Clauses m /day 600
5.1.16)
5.2.2. No. of operating hours per day for RO plant hrs 20
5.2.3. RO plant output capacity required m /hr 30
5.2.4. RO plant outlet capacity as per contract m /hr 2X 30
5.2.5. RO plant capacity provided m /hr 2 X 30
5.3.0. SERVICE WATER SYSTEM
Building Service Water & Drinking Water
5.3.1. m3/hr 0.5
Requirement
IBD Tank Service Water Spray Requirement
5.3.2. m3/hr 1
(Intermediate)
5.3.3. Emergency application for Ash / Coal handling m3/hr 1

http://slidepdf.com/reader/full/dbr-for-water-treatment 12/28
7/23/2019 DBR for Water Treatment

Project Description Doc. No Rev Sheet

12MW- ITC
DESIGN BASIS REPORT FOR WATER EN09-109-G-DOC- 00 13 of 28
LIMITED, TRIBENI
TREATMENT SYSTEM 0602
UNIT.

SL.
DESCRIPTION UNIT Data
No
system (during start-up / non availability of waste
water)
5.3.4. Total Service Water requirement (ref.5.3.1 to 5.3.3) m3/day 60
5.3.5. Service water pump capacity (1W+1S) with margin m3/hr 5
5.4.0. Water requirement for Coal / Ash handling system

Wet scrapper conveyor water requirement (continuous


5.4.1. m3/hr 5
– 24 hours/day)
Fly ash Silo Dust Conditioner Spray Water
5.4.2. m3/hr 11
Requirement ( 4 hrs Per Day)
Coal Handling Dust Suppression System ( 8 hrs Per
5.4.3. m3/hr 8
Day)
5.4.4. Total water requirement m3/day 228

5.4.5. Available waste water from Water Balance Diagram m3/day 456
Neutralizing pit discharge pump capacity with 10%
5.4.6. m3/hr 21
margin
5.5.0. N-pit sizing
Case 1 Normal operation only reject from RO and UF
5.5.1. m3/hr 14.5
system from water balance
5.5.2. Case 2 MGF +ACF Backwash (20 min/one day) m3/regen. 29.6
5.5.3. Case 3. SAC or SBA regeneration (45 min/one day) m3/regen. 23
5.5.4. Case 4. MB regeneration (Once in 7 day for 90 min) m3/regen. 42
Out of the above the highest contributor in one hour
5.5.5. m3/hr 29.6
i.e 5.5.2, is considered for N-pit sizing
5.5.6. N-pit volume required considering 2 hrs holding time m3 60

Note :
Service cum potable water tank of 5 m3 capacity will be provided at the CHS MCC
room top. OWNER shall terminate the service water at the tank inlet. From this tank 2 x
100% service cum potable water pump will be provided. The CHS requirement will be

http://slidepdf.com/reader/full/dbr-for-water-treatment 13/28
7/23/2019 DBR for Water Treatment

Project Description Doc. No Rev Sheet

12MW- ITC
DESIGN BASIS REPORT FOR WATER EN09-109-G-DOC- 00 14 of 28
LIMITED, TRIBENI
TREATMENT SYSTEM 0602
UNIT.

met by the pumps. OWNER shall terminate the service water at the STG building Top
overhead tank. And Tank capacity for this will be 1.0 m3.

6.0. WATER SYSTEM SCHEME:


The enclosed water balance diagram drawing no EN09-109-P-PFD-0501 Rev 01 and
Process Flow Diagram drawing no. EN09-109-P-PFD-0502 Rev 01, indicate the
scheme for water system including water treatment system and cooling water system.

WATER TREATMENT SYSTEM DESCRIPTION:

The power plant water treatment system consists of the following streams,

A. Boiler DM Water Make-Up System (2 x 100% - 30m3/hr Product water each


with 20 hrs operation/day ) consisting of the following,
i. Pre Treatment System consisting of multi grade filter, activated carbon
filter and Ultra filtration unit
ii. RO and Degasser system for meeting for requirement of DM plant
iii. DM Plant consisting of Strong Acid Cation Unit (SAC), Strong Base
Anion Unit (SBA) and Mixed Bed Unit (MB)
B. Condensate Polising System (1 x 100% - 21 m3/hr) consisting of the following,
i. Plate Heat Exchanger Unit
ii. Multi Grade Filter Unit
iii. Mixed Bed Unit
C. Cooling Water Make-Up System (1 x 40m3/hr) consisting of the following,
i. Multi grade Filter
ii. Softener Unit
D. Apart from the above, a Circulating Water Treatment (CWT) System is also
provided for the cooling tower circulating water
A. Boiler DM Water Make-up System
i. Pre Treatment System

45 m3 /hr at 3.5 kg/cm2 of Clarified/ Bore well water for each stream at MGF inlet shall
be provided by OWNER at the terminal point.

The clarified/
suspended bore
solids well in
present water is passed
the water. Thisthrough
filter is aprovided
Multigrade filtera to
to keep reduce
check the
on the
suspended solids. The suspended particles in the feed water get entrapped in the filter

http://slidepdf.com/reader/full/dbr-for-water-treatment 14/28
7/23/2019 DBR for Water Treatment

Project Description Doc. No Rev Sheet

12MW- ITC
DESIGN BASIS REPORT FOR WATER EN09-109-G-DOC- 00 15 of 28
LIMITED, TRIBENI
TREATMENT SYSTEM 0602
UNIT.

media. The filter will have to be washed with effluent water for 10 to 15 mins daily.
Activated carbon provides an effective method for adsorbing a wide range of organic
Compounds and can be considered for use in the removal of organic disinfection by
products and organic precursors.
Activated carbon is used is known as granular activated carbon and is known as GAC.
Granular activated carbon is used in a vessel similar in construction to pressure sand
filter and hence referred to as activated carbon filter.
The Filtered water is then passed through the Ultra Filtration System for further
polishing.

Ultrafiltration

2x 100 % Ultra filtration unit (each stream complete with basket filter and UF module),
In addition, common Fast flush tank with necessary pumps and valves will be provided
for the UF system. The UF system shall be operated on fully automatic mode through
PLC. The UF system will be operated for 20 hours/day.
Ultra-filtration is a low-pressure membrane process for the removal of colloidal silica
and Colloidal Particles (measured in terms of Silt Density Index). The feed effluent
flows from the inside of the fibers, permeates through the membrane and is removed as
the product from the shell side.

Ultra-filtration Pre-treatment is the best pre-treatment technologies for ensuring cost


effective performance of the Reverse Osmosis System. Ultra-filtration (UF) is a unit
operation often used to remove suspended solids, colloids, traces of oil and
macromolecules from liquid streams. As pre-treatment to Reverse Osmosis System, UF
significantly increases the membrane life for the R.O membranes and reduces the
cleaning frequencies, thereby reducing operating expense for the R.O System.
The Filtered water is then passed through the RO System for further polishing

ii. RO (Reverse Osmosis) and Degasser System

The treated water collected in the UF product water storage tank will be pumped
through RO feed pumps(2W+1S) to the Micron Cartridge filters. The cartridge filters
will be followed by high pressure pumps (2W+1S) to boost the pressure of the water
and then feed into high-pressure Reverse Osmosis (RO) Permeators and Accessories.
The RO module shall be complete with micron cartridge filter, necessary dosing for de-
chlorination, anti-scalant. A bypass arrangement with a dump valve operated through
the Oxidation Reduction Potential (ORP) instrument shall be provided to safeguard the
RO membranes.
The skid shall be designed for 100% permeate flow required as per plant water balance
at minimum 70 – 75 % recovery.

The RO product water will be further passed through a degasser tower where the weak
acids and other corrosive gases will be released. Degassed water from the degasser
tower will get collected to the degassed water storage tank of 30 min holding capacity

http://slidepdf.com/reader/full/dbr-for-water-treatment 15/28
7/23/2019 DBR for Water Treatment

Project Description Doc. No Rev Sheet

12MW- ITC
DESIGN BASIS REPORT FOR WATER EN09-109-G-DOC- 00 16 of 28
LIMITED, TRIBENI
TREATMENT SYSTEM 0602
UNIT.

(30cu.m). Degassed water for make up to the auxiliary cooling water system and as feed
to the DM plant will be drawn from the degassed water tank through suitable pumps.
The RO and degasser system will be operated for 20 hours/day.
iii. DM Plant.

The treated water collected in the degassed water storage tank will be pumped to the
two DM plant streams through DM feed pumps (2W+1S). Each DM plant stream shall
consist of Stron Acid Cation (SAC) unit followed by Strong Base Anion (SBA) unit and
Mixed Bed (MB) unit. The product from MB (2 X 30m3/hr ) will be led to 2 nos of DM
storage tanks(MS - Epoxy coated), each of 250 m3 capacity. The DM water tanks shall

be provided with necessary instrumentation to maintain water level.


View glass for resin level will be provided in MB Vessels only.
Anion to cation ratio in MB shall be 2 :1 and free board shall be 120%.
Regeneration time for MB is once in 7 days.
A common pH correction dosing pumps (1W+1S) shall be located at the outlet of MB
to maintain the required pH of DM water Condensate polishing unit.
All the dosing tanks will be sized for the one day requirement. The MOC of the dosing
tank will be HDPE.

B. CONDENSATE POLISING SYSTEM

Process Condensate water will be pumped (By OWNER) to the Plate Heat Exchange
for reducing the temperature from 70 deg.C to 40 Deg.C. The condensate water
collected in the condensate return storage tank (50KL MS Epoxy coated) will be
pumped to the condensate polishing unit through CPU Feed Pump (1W+1S). The CPU
Unit shall consist of a multi grade filter (MGF) followed by a mixed bed (MB) unit. The
product from MB (1 X 21m3/hr) will led to 2 nos of common DM storage tanks.
View glass for resin level will be provided in MB Vessel.
Anion to cation ratio in MB shall be 2 : 1 and free board shall be 120%.
Regeneration time for MB is once in a days.
pH correction dosing system ( with 1W+1S pump) shall be located at the outlet of MB
to maintain the required pH of output water. The CPU plant is designed to operated for
20 hours/day.

C. COOLING TOWER MAKE-UP WATER SYSTEM:

The
watercooling
(40 m3tower
/hr atmake up watershall
3.5 kg/cm2) stream consists at
be provided of Multi-grade
a MGF and filter
a softener
(MGF) unit.
inletRaw
by
OWNER. Product water shall be stored in 75 kL MS Epoxy coated storage tank. The

http://slidepdf.com/reader/full/dbr-for-water-treatment 16/28
7/23/2019 DBR for Water Treatment

Project Description Doc. No Rev Sheet

12MW- ITC
DESIGN BASIS REPORT FOR WATER EN09-109-G-DOC- 00 17 of 28
LIMITED, TRIBENI
TREATMENT SYSTEM 0602
UNIT.

treated water shall be pumped to the cooling tower basin by Cooling Water make up
pump (1W+1S) of 40 m3/hr capacity each.

D. CIRCULATING WATER TREATMENT SYSTEM


The CWT system has the following equipments,

H2S04 dosing system (2 dosing pumps & one day tank of suitable capacity).
Non Oxidizing biocide (With dosing tank & ejector based dosing system)

Corrosion
capacity) & Scale Inhibitor dosing (2 dosing pumps & tank of suitable
Piping of UPVC material
Dosing tanks shall be Poly Ethylene semi transparent.
pH & temperature indicator (Gauge) in the Cooling water lines.
Local control panel with ON / OFF / TRIP indication and manual START /
STOP push buttons shall be provided.
One no. Side stream filter shall be provided. The capacity of side stream
filter shall be 5% of total circulating water capacity.

8.0. ELECTRICAL SYSTEM


LV MOTORS
General

Motors will conform to the latest edition of applicable IS, IEC standards. Motor duty
will be Continuous. Motors will run continuously at rated output with variation in
supply voltage ± 10% and frequency of ± 5% and combined voltage and frequency
variation of absolute sum 10%. Motors will be suitable for operation at 50°C ambient
temperature. All LV Motors will be of energy efficient type, and will have EFF2
efficiency class.
Insulation

Motor winding will be of copper and will have class F insulation but limited to class B
temperature rise.

Bearings

In general motors’ will have anti-frictional ball bearing on both DE & NDE side. All
bearings will be 63 series wherever applicable or as per manufacturer’s standard.

http://slidepdf.com/reader/full/dbr-for-water-treatment 17/28
7/23/2019 DBR for Water Treatment

Project Description Doc. No Rev Sheet

12MW- ITC
DESIGN BASIS REPORT FOR WATER EN09-109-G-DOC- 00 18 of 28
LIMITED, TRIBENI
TREATMENT SYSTEM 0602
UNIT.

Enclosure & Cooling

The method of cooling will be TEFC for LV Motors. Degree of protection for enclosure
will be IP55 for indoor and IPW55 for outdoor installation
Temperature Detectors

LV Motors rated from 55kW onwards will be provided with PTC100 thermistor for
winding temperature detection. Thermistors leads will be wired up to the separate
terminal box.
Space Heater

LV motors rated from 55kW onwards will be provided with Anti- moisture
condensation space heaters. The Space Heater will be switched on whenever the motor
is idle. Space heater wires will be wired up to a separate terminal box.
Motor Main Terminal Box

The terminal box will be capable of withstanding maximum system fault current
(50KA) for duration of 0.25 sec. The terminal box will be suitable to rotate by 360° in 4
steps and will be mounted on top of the motor body.
Earthing Provision

Double earthing provision for motor body and main terminal boxes will be provided.

9.0. CONTROL & INSTRUMENTATION SYSTEM

Operation of the entire Water Treatment Plant is manual except for the UF/ RO Plants -
which will be automated with PLC systems and accordingly pneumatic actuated valves
will be considered at appropriate points in the UF/RO Plants. Two non-redundant
Programmable Logic Controllers (PLCs) will be used for the UF and RO Plants
automation. These PLCs will be supplied with Modbus RTU RS485 ports (Modbus
Slave to Main Plant DCS). Modbus communication is envisaged between PLC and
DCS for monitoring purpose.
For the remaining pumps, start / stop will be by manual operation. Pump trip for
avoiding dry run will be incorporated through level switches interlocked in MCC Panel.
For important Analog measurements, Transmitters will be used with in-built indication.
These analog parameters will be connected to DCS through hardwired for monitoring
purpose.
One No. raw water common header line flow measurement with Orifice and differential
pressure transmitter shall be provided.

http://slidepdf.com/reader/full/dbr-for-water-treatment 18/28
7/23/2019 DBR for Water Treatment

Project Description Doc. No Rev Sheet

12MW- ITC
DESIGN BASIS REPORT FOR WATER EN09-109-G-DOC- 00 19 of 28
LIMITED, TRIBENI
TREATMENT SYSTEM 0602
UNIT.

ANNEXURE – 01 – Raw Water Analysis Reports

RAW WATER ANALYSIS ( Technical Contract document page no 09 OF 468)

The following river water analysis as submitted by the OWNER is considered for
sizing the water treatment plant.

R.V. Briggs Report R.V. Briggs Report


W(S)/07-08/1990 W(D)/08-09/1911
Dated on Dated on
Sl No DESCRIPTION UNITS
23/02/2008 (Sample
from Deep 31/12/2008 (Sample
from Borewell No-
Tubewell No. 40) 52)
1. pH 7.6 7.2
2. TSS ppm NOT INDICATED NOT INDICATED
3. TDS ppm 474 304
4. Turbidity NTU 2 1
5. Electrical Conductivity µs/cm NOT INDICATED NOT INDICATED
6. Total Hardness ppm 294 258

7. Total Alkalinity ppm 405 288


8. Carbonate ppm NOT INDICATED NOT INDICATED
9. Chlorine ppm 12 8
10. Fluorine ppm NOT INDICATED NOT INDICATED
Biochemical Oxygen NOT INDICATED NOT INDICATED
11. ppm
Demand
Chemical Oxygen NOT INDICATED NOT INDICATED
12. ppm
Demand
13. Calcium (Ca++) ppm 79 69.9
14. Magnesium (Mg++) ppm 61.6 20.3
15. Sodium (Na+) ppm NOT INDICATED NOT INDICATED
16. Nitrates ppm 11.9 0.97
17. Sulfates ppm BDL BDL
18. Silica ppm 24.7 21
19. Iron ppm BDL 0.3
20. Zinc ppm NOT INDICATED NOT INDICATED
Note: BDL-Below Detection Limit. Minimum Detection Limit of Fe=0.1

ppm,SO 4=0.5ppm

http://slidepdf.com/reader/full/dbr-for-water-treatment 19/28
7/23/2019 DBR for Water Treatment

Project Description Doc. No Rev Sheet

12MW- ITC
DESIGN BASIS REPORT FOR WATER EN09-109-G-DOC- 00 20 of 28
LIMITED, TRIBENI
TREATMENT SYSTEM 0602
UNIT.

Report No. W(D)/10-11/2873 dated 09.03.2011 provided below,

Date : March 10,


No W(D)/10-11/2873 2011
Issued to : M/S ITC LTD
: PS. PD UNIT -
TRIBENI
: Chandahati,
Your Ref. No. Hooghly
Sample Description : Water
: Surface water tank at Pump
Collection Source House
Date of sample collection : 03.03.2011
Analysis Completed on : 09.03.2011
Method of Sampling : IS : 1622 : 1981 & IS : 3025 (Part - 1) - 1987
Mode of Sampling : Grab
A. Microbiological Test Findings :

Sl Test parameters Test Method Unit Result


No.
Sulphar Reducing IS : 13428 Anex C :
1 Bacteria /100 ml 1998 CFU Absent
2
2 Total Viable Count/ml IS : 5402-2002 CFU 1.86 x 10

B. Physical Test Findings:


1. Appearance (Before Filtration) : Clear 2.Appearance (After Filtration) : clear

C. Chemical Test Findings:

Sl Test parameters Test Method Unit Result


No.
1 a) Colour: IS:3025-1964Clause-5 Hazen 1
b) Odour: Unobjectionable
2 Taste: Agreeable
3 Turbidity APHA 20 Edn.2130B NTU 4.2
4 pH value APHA 20 Edn.4500H+B …… 7.4
5 TSS APHA 20 Edn. 2540 D mg/l <10
6 Total Dissolved Solids APHA 20 Edn.2540C mg/l 328
7 Conductivity at 25˚ C APHA 20 Edn 2510 B µs/cm 580
8 Colloidal Silica as APHA 20 Edn. 4500 - mg/l
SiO 2 SiO 2 0.2
9 APHA 20 Edn. 3500 mg/l
Sodium as Na NaB 37.8
10 Potasium as K APHA 20 Edn. 3500 KB mg/l 12.6

http://slidepdf.com/reader/full/dbr-for-water-treatment 20/28
7/23/2019 DBR for Water Treatment

Project Description Doc. No Rev Sheet

12MW- ITC
DESIGN BASIS REPORT FOR WATER EN09-109-G-DOC- 00 21 of 28
LIMITED, TRIBENI
TREATMENT SYSTEM 0602
UNIT.

Sl Test parameters Test Method Unit Result


No.
11 Ammonium as NH 4 APHA 20 Edn. 4500 mg/l
NH 3 F <0.01
12 Barium as Ba IS : 13428 : Annex F mg/l <0.1
13 P - Alkalinity as IS:3025(Part-23)-1986 mg/l
CaCO 3 Nil
14 M - Alkalinity as IS:3025(Part-23)-1986 mg/l
CaCO 3 293
15 Bi Carbonate as IS:3025(Part-23)-1987 mg/l

16 CaCO 3 as CaCO
Carbonate 3 IS:3025(Part-23)-1987 mg/l 293
Nil
17 Iron as (Ferrous ) APHA 20 Edn.3500FeB mg/l <0.1
18 Iron as (Ferric) APHA 20 Edn.3500FeB mg/l 0.23
19 Calcium as Ca APHA 20 Edn.3500CaB mg/l 56
20 Lima as CaO APHA 20 Edn.3500CaB mg/l 78
21 Magnesium as Mg APHA20Edn.3500MgB mg/l 17
22 Sulphate as SO 4 IS:3025(Part-24)-1986 mg/l <5
-
23 sulphide as S APHA20Edn.3500MgB mg/l <0.1
24 Chloride as Cl APHA 20 Edn.4500ClB mg/l 10
25 Nitrate as NO 3 APHA20Edn.4500NO3 mg/l 1.8
26 Nitrate Nitrogen as N APHA20Edn.4500NO3D mg/l 0.41
27 Nitrite as NO 2 APHA20Edn.4500- mg/l
NO 2B <0.02
28 Total Hardness as APHA 20 Edn.2340C mg/l
CaCO 3 212
29 Reactive Silica APHA 20 Edn.4500 mg/l
SiO 2C 12.1
30 Dissolved Phosphate APHA 20 Edn.4500 - PD mg/l
as PO 4 <0.003
31 Total phosphate as APHA 20 Edn.4500 - PD mg/l
PO4 <0.003
32 Copper as Cu APHA 20 Edn.3111B mg/l <0.05
33 Manganese as Mn APHA 20 Edn.3111B mg/l 0.08
34 Fluoride as F APHA 20 Edn.4500FD mg/l 0.48
35 Nickel as Ni APHA 20 Edn. 3111 B mg/l <0.05
36 Mercury as Hg APHA 20 Edn.3112B mg/l <0.001
37 Cadmium as Cd APHA 20 Edn. 3111 B mg/l <0.01
38 Total Chromium as Cr APHA 20 Edn. 3111 B mg/l <0.05
39 Arsenic as As APHA 20 Edn.3114C mg/1 0.008
Cyanide as CN APHA 20 Edn.4500CN- mg/l
40 F <0.05
41 Lead as Pb APHA 20 Edn.3111B mg/l <0.05
42 Zinc as Zn APHA 20 Edn.3111B mg/l <0.05
43 Aluminium as Al APHA 20 Edn.3111D mg/l <0.03

http://slidepdf.com/reader/full/dbr-for-water-treatment 21/28
7/23/2019 DBR for Water Treatment

Project Description Doc. No Rev Sheet

12MW- ITC
DESIGN BASIS REPORT FOR WATER EN09-109-G-DOC- 00 22 of 28
LIMITED, TRIBENI
TREATMENT SYSTEM 0602
UNIT.

Sl Test parameters Test Method Unit Result


No.
Dissolved Volatile mg/l
44 solids APHA 20 Edn.2540E 78
45 Dissolved Fixed solids APHA 20 Edn.2540E mg/l 250
BOD IS : 3025 (Part - 44) - mg/l
46 1993 <5.0
47 COD APHA 20EDn 5220 B mg/l <5.0
48 Dissolved Oxygen IS : 3025 (Part - 38) mg/l 6.2
Oxygen Absorbed in 4
49 IS : 3025 - 1964 (cl-51) mg/l 0.1
hrs at 37°C Nitrogen
Ammoniacal APHA 20 Edn. 4500 mg/l
50 NH,F <0.01
Ammonia as NH 3 APHA 20 Edn. 4500 mg/l
51 NH,F <0.01
Free Carbondioxide as APHA 20 Edn.4500 -
52 mg/l 3.08
CO 2 CO 2C
Note :
Minimum Detection Limit of Cu - 0.05mg/1, Phenolic Compounds - 0.001mg/1,Iron - 0.1mg/l
Hg - 0.001mg/1, Cd - 0.01mg/1,Se - 0.01mg/1,CN - 0.05mg/1,Zn - 0.05mg/l, BOD - 5.0mg/l,COD
- 5.0mg/l
Al - 0.03mg/1,Boron - 1.0mg/1.Pb - 0.05mg/1,TSS - 10mg/l, Ba - 0.5mg/l,SO 4- 5mg/l,PO 4 -0.03
mg/l
Ni - 0.05mg/l,

D) If any wide variation in water analysis is observed during contract execution stage

resulting in addition / enhancement of any equipment the same shall be at additional cost.

Provision to add Ultra-Filtration in future to be made before RO. Same should be shown

in layout & P&ID. In case of requirement of UF due to colloidal silica more than 0.2mg/l

in raw water, supplier will provide on mutually agreed price, Necessary flanges & blinds

to be included.

http://slidepdf.com/reader/full/dbr-for-water-treatment 22/28
7/23/2019 DBR for Water Treatment

Project Description Doc. No Rev Sheet

12MW- ITC
DESIGN BASIS REPORT FOR WATER EN09-109-G-DOC- 00 23 of 28
LIMITED, TRIBENI
TREATMENT SYSTEM 0602
UNIT.

SAMPLE DRAWN BY US :
No. W(D)/11-12/686 Date : September 01, 2011 Page 1 of 2
Issued to : M/S I.T.C. LTD.
: P.S.P.D., Unit Tribeni, Chandrahati, Hooghly.
Your Ref. No. : Letter dtd. 19.08.2011
Sample Description : Water
Collection Source : Fresh Water from Surface Pump House.
Sample Collected on : 19.08.2011
Analysis Completed on : 29.08.2011
: IS : 1622 : 1981 & IS : 3025 (Part -
Method of Sampling 1) - 1987
Mode of Sampling : Grab
A. Microbiological Test Findings :
Sl Test parameters Test Method Unit Results
No.
1 Coliform APHA 20 Edn. 9222 B
Organism/100ml CFU 58
2 E. coli/100ml APHA 20 Edn.9222 D CFU Absent
3 TVC IS:5402:2002 CFU 730
4 Sulphate Reducing IS:13428:1998 Annex - 6
Bacteria Absent

B. Physical Test Findings:


1. Appearance when analysed : Clear. 2.Appearance After Filtration : Clear.
C. Chemical Test Findings:
Sl Test parameters Test Method Unit Results
No.
1 Colour: IS:3025-1964Clause-5 Hazen 1
2 Smell : Unobjectionable
3 TSS APHA 20 Edn. 2540 D mg/l <10
4 Turbidity APHA 20 Edn.2130B NTU 2.8
5 pH value at 25º C APHA 20 Edn.4500H+B …… 7.4
6 Conductivity at 25˚ C APHA 20 Edn 2510 B µs/cm 590
7 APHA 20 Edn. 4500 - mg/l
Colloidal Silica as SiO 2 SiO 2C < 0.1
8 Total Dissolved Solids APHA 20 Edn.2540C mg/l 318
9 Volatile Solids at 550˚C APHA 20 Edn.2540E mg/l 88
10 APHA 20 Edn. 3500 mg/l
Sodium as Na NaB 25.1
11 Potasium as K APHA 20 Edn. 3500 KB mg/l 2.1
12 P - Alkalinity as CaCO 3 IS:3025(Part-23)-1986 mg/l Nil
13 M - Alkalinity as IS:3025(Part-23)-1986 mg/l
CaCO 3 289
14 Silica as SiO 2 APHA 20 mg/l
Edn.4500SiO2C 14.3
15 Iron as Fe (Ferric) APHA 20 Edn.3500FeB mg/l <0.1
16 Calcium as Ca APHA 20 Edn.3500CaB mg/l 71

http://slidepdf.com/reader/full/dbr-for-water-treatment 23/28
7/23/2019 DBR for Water Treatment

Project Description Doc. No Rev Sheet

12MW- ITC
DESIGN BASIS REPORT FOR WATER EN09-109-G-DOC- 00 24 of 28
LIMITED, TRIBENI
TREATMENT SYSTEM 0602
UNIT.

17 Magnesium as Mg APHA20Edn.3500MgB mg/l 17.3


18 Sulphate as SO 4 IS:3025(Part-24)-1986 mg/l <5
19 Chloride as Cl APHA 20 Edn.4500ClB mg/l 12
20 Nitrate as NO 3 APHA20Edn.4500NO3D mg/l 1.2
21 Nitrite as NO 2 APHA20Edn.4500- mg/l
NO 2B <0.02
22 Total Hardness as APHA 20 Edn.2340C mg/l
CaCO 3 249
23 Copper as Cu APHA 20 Edn.3111B mg/l <0.05
24 Manganese as Mn APHA 20 Edn.3111B mg/l 0.11

25
26 Fluoride
Phenolic as F
Compounds APHA
APHA 20
20 Edn.4500FD
Edn.5530C mg/l
mg/l 0.36
<0.001
27 Mercury as Hg APHA 20 Edn.3112B mg/l <0.001
28 Cadmium as Cd APHA 20 Edn. 3111 B mg/l <0.01
29 Selenium as Se APHA 20 Edn.3111B mg/l <0.01
30 Arsenic as As APHA 20 Edn.3114C mg/l < 0.001
31 Cyanide as CN APHA 20 Edn.4500CN- mg/l
F <0.05
32 Lead as Pb APHA 20 Edn.3111B mg/l <0.05
33 Zinc as Zn APHA 20 Edn.3111B mg/l < 0.05
34 Aluminium as Al APHA 20 Edn.3111D mg/l <0.03
35 Boron as B APHA 20 Edn 3500 -BC mg/l <1.0
36 Barium as Ba IS : 13428 : Annex F mg/l <0.1
37 APHA 20 Edn.4500 -
Free Carbondioxide mg/l 0.88
CO 2C
38 Carbonate as CaCO 3 IS:3025(Part-23)-1986 mg/l Nil
39 biCarbonate as CaCO 3 IS:3025(Part-23)-1986 mg/l 289
-
40 Sulphide as S APHA20Edn.4500 S B mg/l <0.1
41 Sulphide as H2S APHA20Edn.4500 S B mg/l < 0.1
42 Ammoniacal Nitrogen APHA 20 Edn. 4500 mg/l
NH 3 F <0.01
43 Ammonia as NH 3 APHA 20 Edn. 4500 mg/l
NH 3 F <0.01
44 BOD IS : 3025 (Part - 44) - mg/l
1993 <5.0
45 COD APHA 20EDn 5220 B mg/l <5.0
46 Dissolved Oxygen IS : 3025 (Part - 38) mg/l 6.2
47 Total Chromium as Cr APHA 20 Edn. 3111 B mg/l <0.05
48 Nickel as Ni APHA 20 Edn. 3111 B mg/l <0.05
49 Lima as CaO APHA 20 Edn.3500CaB mg/l 99.4
50 Iron as Fe(Ferrous ) APHA 20 Edn.3500FeB mg/l <0.1
51 APHA 20 mg/l
Nitrate Nitrogen as N Edn.4500NO3D 0.271
52 Total Dissolved
Phosphate as Po 4 < 0.003

http://slidepdf.com/reader/full/dbr-for-water-treatment 24/28
7/23/2019 DBR for Water Treatment

Project Description Doc. No Rev Sheet

12MW- ITC
DESIGN BASIS REPORT FOR WATER EN09-109-G-DOC- 00 25 of 28
LIMITED, TRIBENI
TREATMENT SYSTEM 0602
UNIT.

53 Total Fixed Solids APHA 20 Edn.2540E mg/l 230


54 Oxygen absorbed (Tide's
test) Nil
Note :
Minimum Detection Limit of TSS - 10mg/l,Colloidal Silica - 0.1mg/l, Iron - 0.1mg/l,Sulphate -
5.0mg/l,Nitrate - 0.02mg/l,Cu - 0.05mg/l
Phenolic Compounds - 0.001mg/l, Mercury - 0.01mg/l,Cd - 0.01mg/l,Se - 0.01mg/l,Chromium
Hexavalent - 0.01mg/l, As - 0.001mg/l,
CN - 0.05mg/l,Lead - 0.05mg/l,Al - 0.03mg/l,Zinc - 0.05mg/l,B - 1.0mg/l,Ba - 0.1mg/l,Sulphate as S -
0.1mg/l, H2S - 0.1mg/l,
Ammonical Nitrogen - 0.01mg/l,Ammonia - 0.01mg/l,BOD - 5.0mg/l,COD - 5.0mg/l,Cr - 0.05mg/l,Ni
- 0.05mg/l,Iron(Ferrous) - 0.1mg/l,
& Total Dissolved Phosphate - 0.003mg/l.

ANNEXURE – 02 – Return Condensate Analysis Reports

CONDENSATE WATER ANALYSIS ( as per Contract Annexure page no 12 OF 468 )

TEST REPORT of CONDENSATE WATER as per ITC email dated 14.03.2011


Date : 12.03.2011 & Time 9=00 am
PM1 PM3 PM4
pH 8.56 8.95 8.78
TDS ppm 2.7 2.4 2.2
Conductivity 4.5 3.5 3.3
microsiemens/cm
Hardness ppm Nil Nil Nil
SiO2 ppm Nil Nil Nil

TSS of Composite of PM1,PM3 & PM4 =>11 ppm

Date : 12.03.2011 & Time 10=45 am


PM1 PM3 PM4
pH 8.45 8.90 8.76
TDS ppm 2.8 2.4 2.3
Conductivity 4.2 3.4 3.2
microsiemens/cm
Hardness ppm Nil Nil Nil
SiO2 ppm Nil Nil Nil

http://slidepdf.com/reader/full/dbr-for-water-treatment 25/28
7/23/2019 DBR for Water Treatment

Project Description Doc. No Rev Sheet

12MW- ITC
DESIGN BASIS REPORT FOR WATER EN09-109-G-DOC- 00 26 of 28
LIMITED, TRIBENI
TREATMENT SYSTEM 0602
UNIT.

TSS of Composite of PM1,PM3 & PM4 =>12 ppm

If any wide variation in water analysis is observed during contract execution stage resulting in

addition / enhancement of any equipment the same shall be at additional cost.

SAMPLE DRAWN BY US :
No. W(D)/11-12/687 Date : September 01, 2011 Page 1 of 2
Issued to : M/S I.T.C. LTD.
: P.S.P.D., Unit Tribeni, Chandrahati, Hooghly.
Your Ref. No. : Letter dtd. 19.08.2011
Sample Description : Water
Collection Source : Condensed Water at Paper Machine.
Sample Collected on : 19.08.2011
Analysis Completed on : 29.08.2011
: IS : 1622 : 1981 & IS : 3025 (Part -
Method of Sampling 1) - 1987
Mode of Sampling : Grab
A. Microbiological Test Findings :
Sl Test parameters Test Method Unit Results
No.
1 Coliform APHA 20 Edn. 9222 B
Organism/100ml CFU <1
2 E. coli/100ml APHA 20 Edn.9222 D CFU Absent
3 TVC IS:5402:2002 CFU 2
4 Sulphate Reducing IS:13428:1998 Annex - 6
Bacteria Absent
B. Physical Test Findings:
1. Appearance when analysed : Clear. 2.Appearance After Filtration : Clear.
C. Chemical Test Findings:
Sl Test parameters Test Method Unit Results

No.
1 Colour: IS:3025-1964Clause-5 Hazen 1
2 Smell : Unobjectionable
3 TSS APHA 20 Edn. 2540 D mg/l <10
4 Turbidity APHA 20 Edn.2130B NTU <1
5 pH value at 25º C APHA 20 Edn.4500H+B …… 7.1
6 Conductivity at 25˚ C APHA 20 Edn 2510 B µs/cm 7
7 APHA 20 Edn. 4500 - mg/l
Colloidal Silica as SiO 2 SiO 2C < 0.1
8 Total Dissolved Solids APHA 20 Edn.2540C mg/l 4
9 Volatile Solids at 550˚C APHA 20 Edn.2540E mg/l <4
10 APHA 20 Edn. 3500 mg/l
Sodium as Na NaB <1
11 Potasium as K APHA 20 Edn. 3500 KB mg/l <1

http://slidepdf.com/reader/full/dbr-for-water-treatment 26/28
7/23/2019 DBR for Water Treatment

Project Description Doc. No Rev Sheet

12MW- ITC
DESIGN BASIS REPORT FOR WATER EN09-109-G-DOC- 00 27 of 28
LIMITED, TRIBENI
TREATMENT SYSTEM 0602
UNIT.

12 P - Alkalinity as CaCO 3 IS:3025(Part-23)-1986 mg/l <2


13 M - Alkalinity as IS:3025(Part-23)-1986 mg/l
CaCO 3 <2
14 Silica as SiO 2 APHA 20 mg/l
Edn.4500SiO2C 1.1
15 Iron as Fe (Ferric) APHA 20 Edn.3500FeB mg/l <0.1
16 Calcium as Ca APHA 20 Edn.3500CaB mg/l <1
17 Magnesium as Mg APHA20Edn.3500MgB mg/l <1
18 Sulphate as SO 4 IS:3025(Part-24)-1986 mg/l <5
19 Chloride as Cl APHA 20 Edn.4500ClB mg/l <2

20
21 Nitrate as NO
Nitrite as NO 3 APHA20Edn.4500NO3D
APHA20Edn.4500- mg/l
mg/l < 0.1
2
NO 2B <0.02
22 Total Hardness as APHA 20 Edn.2340C mg/l
CaCO 3 1
23 Copper as Cu APHA 20 Edn.3111B mg/l <0.05
24 Manganese as Mn APHA 20 Edn.3111B mg/l < 0.05
25 Fluoride as F APHA 20 Edn.4500FD mg/l < 0.1
26 Phenolic Compounds APHA 20 Edn.5530C mg/l <0.001
27 Mercury as Hg APHA 20 Edn.3112B mg/l <0.001
28 Cadmium as Cd APHA 20 Edn. 3111 B mg/l <0.01
29 Selenium as Se APHA 20 Edn.3111B mg/l <0.01
30 Arsenic as As APHA 20 Edn.3114C mg/l < 0.001
31 Cyanide as CN APHA 20 Edn.4500CN- mg/l
F <0.05
32 Lead as Pb APHA 20 Edn.3111B mg/l <0.05
33 Zinc as Zn APHA 20 Edn.3111B mg/l < 0.05
34 Aluminium as Al APHA 20 Edn.3111D mg/l <0.03
35 Boron as B APHA 20 Edn 3500 -BC mg/l <1.0
36 Barium as Ba IS : 13428 : Annex F mg/l <0.1
37 APHA 20 Edn.4500 -
Free Carbondioxide mg/l 0.88
CO 2C
38 Carbonate as CaCO 3 IS:3025(Part-23)-1986 mg/l 1.0
39 biCarbonate as CaCO 3 IS:3025(Part-23)-1986 mg/l 1.0
-
40 Sulphide as S APHA20Edn.4500 S B mg/l <0.1
41 Sulphide as H2S APHA20Edn.4500 S B mg/l < 0.1
42 Ammoniacal Nitrogen APHA 20 Edn. 4500 mg/l
NH 3 F <0.01
43 Ammonia as NH 3 APHA 20 Edn. 4500 mg/l
NH 3 F <0.01
44 BOD IS : 3025 (Part - 44) - mg/l
1993 <5.0
45 COD APHA 20EDn 5220 B mg/l <5.0
46 Dissolved Oxygen IS : 3025 (Part - 38) mg/l 5.9
47 Total Chromium as Cr APHA 20 Edn. 3111 B mg/l <0.05

http://slidepdf.com/reader/full/dbr-for-water-treatment 27/28
7/23/2019 DBR for Water Treatment

Project Description Doc. No Rev Sheet

12MW- ITC
DESIGN BASIS REPORT FOR WATER EN09-109-G-DOC- 00 28 of 28
LIMITED, TRIBENI
TREATMENT SYSTEM 0602
UNIT.

48 Nickel as Ni APHA 20 Edn. 3111 B mg/l <0.05


49 Lima as CaO APHA 20 Edn.3500CaB mg/l 0.56
50 Iron as Fe(Ferrous ) APHA 20 Edn.3500FeB mg/l <0.1
51 APHA 20 mg/l
Nitrate Nitrogen as N Edn.4500NO3D < 0.1
52 Total Dissolved
Phosphate as Po 4 < 0.003
53 Total Fixed Solids APHA 20 Edn.2540E mg/l <4
54 Oxygen absorbed (Tide's
test) Nil

Note :
Minimum Detection Limit of TSS - 10mg/l,Colloidal Silica - 0.1mg/l, Iron - 0.1mg/l,Sulphate -
5.0mg/l,Nitrate - 0.02mg/l,Cu - 0.05mg/l
Phenolic Compounds - 0.001mg/l, Mercury - 0.01mg/l,Cd - 0.01mg/l,Se - 0.01mg/l,Chromium
Hexavalent - 0.01mg/l, As - 0.001mg/l,
CN - 0.05mg/l,Lead - 0.05mg/l,Al - 0.03mg/l,Zinc - 0.05mg/l,B - 1.0mg/l,Ba - 0.1mg/l,Sulphate as S -
0.1mg/l, H2S - 0.1mg/l,
Ammonical Nitrogen - 0.01mg/l,Ammonia - 0.01mg/l,BOD - 5.0mg/l,COD - 5.0mg/l,Cr - 0.05mg/l,Ni
- 0.05mg/l,Iron(Ferrous) - 0.1mg/l,
Total Dissolved Phosphate - 0.003mg/l,Volatile Solids - 4.0mg/l,Na - 1.0mg/l,K - 1.0mg/l,p-Alkalinity
- 2.0mg/l,m-Alkalinity - 2.0mg/l,

Ca - 1.0mg/l,Mg
0.1mg/l&Total - 1.0mg/l,Cl
Fixed - 2.0mg/l,Nitrate - 0.1mg/l,Nitrite - 0.02mg/l,Nitrate Nitogen -
Solids - 4mg/l.