ASHRAE STANDARD
Designation and
Safety Classification of
Refrigerants
Approved by the ASHRAE Standards Committee on January 23, 2010; by the ASHRAE Board of Directors on
January 27, 2010; and by the American National Standards Institute on February 24, 2010.
This standard is under continuous maintenance by a Standing Standard Project Committee (SSPC) for which
the Standards Committee has established a documented program for regular publication of addenda or revi-
sions, including procedures for timely, documented, consensus action on requests for change to any part of
the standard. The change submittal form, instructions, and deadlines may be obtained in electronic form from
the ASHRAE Web site, http://www.ashrae.org, or in paper form from the Manager of Standards. The latest edi-
tion of an ASHRAE Standard may be purchased from ASHRAE Customer Service, 1791 Tullie Circle, NE,
Atlanta, GA 30329-2305. E-mail: orders@ashrae.org. Fax: 404-321-5478. Telephone: 404-636-8400 (world-
wide), or toll free 1-800-527-4723 (for orders in US and Canada).
© Copyright 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
ISSN 1041-2336
SPECIAL NOTE
This American National Standard (ANS) is a national voluntary consensus standard developed under the auspices of the American
Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE). Consensus is defined by the American National Standards
Institute (ANSI), of which ASHRAE is a member and which has approved this standard as an ANS, as “substantial agreement reached by
directly and materially affected interest categories. This signifies the concurrence of more than a simple majority, but not necessarily unanimity.
Consensus requires that all views and objections be considered, and that an effort be made toward their resolution.” Compliance with this
standard is voluntary until and unless a legal jurisdiction makes compliance mandatory through legislation.
ASHRAE obtains consensus through participation of its national and international members, associated societies, and public review.
ASHRAE Standards are prepared by a Project Committee appointed specifically for the purpose of writing the Standard. The Project
Committee Chair and Vice-Chair must be members of ASHRAE; while other committee members may or may not be ASHRAE members, all
must be technically qualified in the subject area of the Standard. Every effort is made to balance the concerned interests on all Project
Committees.
The Manager of Standards of ASHRAE should be contacted for:
a. interpretation of the contents of this Standard,
b. participation in the next review of the Standard,
c. offering constructive criticism for improving the Standard, or
d. permission to reprint portions of the Standard.
DISCLAIMER
ASHRAE uses its best efforts to promulgate Standards and Guidelines for the benefit of the public in light of available information and
accepted industry practices. However, ASHRAE does not guarantee, certify, or assure the safety or performance of any products, components,
or systems tested, installed, or operated in accordance with ASHRAE’s Standards or Guidelines or that any tests conducted under its
Standards or Guidelines will be nonhazardous or free from risk.
(This foreword is not part of this standard. It is tions as specified in Section 6.1.5. Blends shall be
merely informative and does not contain assigned a flammability classification based on
requirements necessary for conformance to the their WCF and WCFF, as determined from a frac-
standard. It has not been processed according tionation analysis (see Section B2 in Normative
to the ANSI requirements for a standard and Appendix B). A fractionation analysis for flamma-
may contain material that has not been subject bility is not required if the components of the blend
to public review or a consensus process. are all in one class; the blend shall be assigned the
Unresolved objectors on informative material that same class (see Table 3).
are not offered the right to appeal at ASHRAE
Burning velocity measurements shall be
or ANSI.)
conducted according to a credible method. The
method shall be in agreement with established
FOREWORD
methods of determining burning velocity by
This addendum adds an optional 2L subclass to demonstrating measurement results of 6.7 ± 0.7 cm/
the existing Class 2 flammability classification, s burning velocity for R-32 and 23.0 ± 2.3 cm/s for
signifying class 2 refrigerants with a burning velocity R-152a, or by presenting other evidence supporting
less than or equal to 10 cm/s. the accuracy of the method. One acceptable method
is the vertical tube method as detailed by Jabbour
Note: In this addendum, changes to the current (2004) and summarized by Jabbour and Clodic
standard are indicated in the text by underlining (for (2004). Measurements shall be conducted starting
additions) and strikethrough (for deletions) unless
from the LFL to at least 125% of the stoichiometric
the instructions specifically mention some other
concentration. Measurements shall be done with
means of indicating the changes.
increments of at most 10% of the stoichiometric
concentration and each measurement shall be
Addendum ak to 34-2007 repeated at least 2 times. The burning velocity is the
maximum value obtained from a least-squares fit to
3. DEFINITION OF TERMS the measured data. The gas mixture shall be made
by any method that produces a blend of air/ refrig-
burning velocity (Su): the maximum velocity (cm/ erant that is accurate to ±0.1% in the test chamber.
s) at which a laminar flame propagates in a normal Dry air (less than 0.00015 grams of water vapor per
direction relative to the unburned gas ahead of it. gram of dry air) containing 21.0 ± 0.1% O2 shall be
flame propagation (for determining flammability used as the oxidant. The flammable gas shall have a
according to Appendix B): any combustion that minimum purity of 99.5% by weight. Note: Meth-
moves upward and outward from the point of igni- ods that have been used include: (a) pressurized
tion as defined in Section B1.8 in Normative mixture made by using partial pressure, or (b) quan-
Appendix B. titative flow methods like volumetric flow meters
and mass flow controllers fixing the ratio of air and
propagation velocity of flame: the velocity at which refrigerant.
the flame propagates in the test space.
6.1.3 Flammability Classification. Refrigerants References:
shall be assigned to one of three classes – 1, 2, or 3,
Jabbour, T., (2004) Flammable Refrigerant Classi-
and one optional subclass – 2L – based on lower
fication Based on the Burning Velocity. PhD
flammability limit testing, heat of combustion, and
Thesis, Ecole des Mines: Paris, France.
the optional burning velocity measurement. Flam-
mability testsTests shall be conducted in accor- Jabbour, T. and Clodic, D.F., (2004) Burning
dance with ASTM E6812 using a spark ignition velocity and refrigerant flammability classifi-
source. Testing of all halocarbon refrigerants shall cation. ASHRAE Trans., Vol. 110, part 2.
be in accordance with the Annex of ASTM E681.
6.1.3.2.1 Subclass 2L (optional)
Single-compound refrigerants shall be assigned a
single flammability classification. Refrigerant Refrigerants that meet the following additional
blends shall be assigned flammability classifica- condition:
1. Have a maximum burning velocity of ≤10 cm/s 9.7.2 Burning Velocity Information
when tested at 23 °C and 101.3 kPa. (optional). Applications seeking an assignment
6.1.4 Matrix Diagram of Safety Group Classi-
of 2L shall include the following:
fication System. The toxicity and flammability
classifications described in Sections 6.1.1, 6.1.2, a. a full description of the test method employed
and 6.1.3 yield six separate safety group classifica- b. results of standards testing with the specified
tions (A1, A2, A3, B1, B2, and B3) and two sub- test approach to ensure agreement with
classes (A2L and B2L) for refrigerants. These accepted values:
classifications are represented by the matrix shown
in Figure 1. • burning velocity for R-32 (acceptable range
is 6.7±0.7 cm/s) and burning velocity for
6.1.5 Safety Classification of Refrigerants R-152a (acceptable range is 23.0±2.3 cm/
(add A2L and B2L classifications to Figure 1 as s),
shown) • or other evidence supporting the accuracy
of the method against accepted burning
Safety group
velocity values for other class 2 refriger-
Higher ants above and below 10 cm/s
A3 B3
Flammability
c. duplicate test results from the LFL to at least
A2 B2 125% of the stoichiometric concentration
Lower
Flammability
A2L* B2L*
No flame
A1 B1
Propagation
*A2L and B2L are lower flammability refrigerants with a maximum burning velocity
of ≤ 10 cm/s