Professional Documents
Culture Documents
P Ramachandran
A list of various types of Transformers that power engineers may come across was
listed in an earlier article. These transformers are mainly for T&D applications,
traction or industrial applications. Small and mini transformers that are used in
lighting, control circuits, electronics, toys, home appliances etc are not included.
We will see brief definitions of these transformers and relevant National Standards
available for the selection and applications of different types of transformers. Later
in this series, we will cover in detail each of these transformers. This article is in
continuation to an earlier article.
https://www.linkedin.com/pulse/a55-types-transformers-p-ramachandran
A. Based on Application or Use
Power Transformer is a static piece of apparatus with two or more windings which,
by electromagnetic induction, transforms a system of alternating voltage and
current in to another system of voltage and current, usually of different values and
at the same frequency, for transmitting the electrical power (IEC Pub 50-421-01-01)
2. Distribution Transformer
VRDT transformers (25 -3150 kVA 36 kV) are distribution transformers with an
OLTC (on-load tap-changer) on HV or LV side to regulate the LV network voltage
within limits specified by the regulating agencies. Variations of LV network voltage
is more when renewable energy power sources are connected to LV or MV grids.
These transformers must work as step up or step-down transformers due to the
power feed from renewable energy sources.
A transformer that supplies power from a station high-voltage bus to the station
auxiliaries and also to the unit auxiliaries during the generator start up and
shutdown or when the unit auxiliary transformer is not available or under both
conditions. High voltage side is connected to the HV grid and the secondary voltage
is same as the voltage of generator/auxiliary supply transformer.
These are small distribution transformers catering to the sub-station lighting and
motor loads. Sometimes the input for these transformers will be taken from the
tertiary circuit of power transformers in the station and these units will piggy ride
the main power transformer.
NGT is used for earthing the neutral of generators or three phase transformers. This
is a single-phase distribution transformer of short time rating, with the HV primary
in series with neutral grounding lead of generator or transformer and appropriate
rated resistor connected across the LV secondary winding of transformer. In this
way using small standard resistors high impedance neutral earthing is achieved
through the use of NGT.
Ground fault current will flow through them only for a short period and hence
transformers are rated for short time periods like 10 seconds. Earthing transformers
(NDT) are often provided with a secondary (low-voltage) winding to supply a local
auxiliary load, for example, the 415 V equipment within the substation
Traction Transformers are installed on the board of rolling stock. They supply
power to propulsion circuits (traction motors) and other auxiliary circuits like
lighting, air conditioning, kitchen etc. Ratings extend from few hundred kVA to 7-10
MVA. There are HV windings connected to single phase 15 or 25 kV AC and
secondary traction windings and auxiliary load windings. They are generally of high
impedance, light weight and compact with forced-oil, forced-air cooling.
Alternatives are dry type or with alternate insulating fluids (silicon oil or synthetic
ester) and high temperature insulation for winding conductors. These transformers
are of robust construction to with stand continuous shock and vibrations in service.
Furnace transformers (single phase or three phase) are used for steel melting and
metallurgical industry. They are characterised by high secondary current (up to 90
kA electrode AC or DC current for steel and 160 kA for ferro-alloys) and a wide
secondary voltage range. The secondary voltage is normally regulated by on-load
tap-changers, located in high voltage winding or in an intermediate circuit of a two
cored design (booster regulation) within the transformer tank.
DC furnace transformers are also used to melt scrap metal. Since DC current is used
for melting, transformer is installed in combination with a rectifier that feeds the
furnace.
12. Welding Transformer
In phase shifting transformers, phase relationship between input and output can be
adjusted for controlling power flow in electrical grid. e.g.to shift power flow from a
shorter (but overloaded) link to a longer path with excess capacity. A phase angle
regulating transformer, phase angle regulator (PAR, American usage), phase-
shifting transformer, phase shifter (West coast American usage), or quadrature
booster (quad booster, British usage), is a specialized form of transformer used to
control the flow of real power on three-phase electric -transmission networks.