ETHPCB/AW-QT/F/02/02

s
Confirmation on RoutineTests Circuit Breaker

Client : ELECTRICA
Contractor : SIEMENS S.R.L. ROMANIA

Technical Data

Circuit-breaker type : 3AP1FG

Factory Serial number : 2019/26134

Rated Voltage : 145kV

Rated Frequency : 50 Hz

Rated current : 3150A

Rated Short-Circuit Breaking Current : 40.0 kA

Rated Range Of Ambient Temperature : - 35deg..+ 45 dec C

Nominal SF6 pressure(guage) at 20 deg-C : 6.0 bar

Rated Operating Sequences : O-0.3sec-CO-3min-CO

Date of testing : 06.08.2019

1.
General

Compliance with the current editions of the below mentioned specifications has been checked by routine testing in our test laboratory: IEC
Publ. 62271-1, IEC Publ. 62271-100

Test pressures are declared as guage pressures.

Stamp Sign by Testing Engineer

___________________________
ETHPCB/AW-QT/F/02/02

Breaker Sr. No. : 2019/26134 Circuit-breaker type : 145kV

2. Operating times of the device

All operating tests required by the standards have been carried out successfully. The operating times below have been
measured at rated conditions .

Designation Minimum Maximum Actual Value


value value C O1 O2 CO OCO

tC 55.0 72.0 63.6 --- --- --- ---

dtC 0.0 3.0 0.4 --- --- --- ---

to 25.0 33.0 --- 31.0 30.5 --- ---

dtO 0.0 2.0 --- 0.8 0.4 --- ---

tCO <=40 --- --- --- 35.6 ---

dtO(CO) <=300 --- --- --- 229.4

tcNO 29.0 45.0 40.8 --- --- --- ---

tcNC 50.0 66.0 61.3 --- --- --- ---

tcWi 31.0 47.0 39.6 --- --- --- ---

toNO 25.0 45.0 --- 41.1 41.5 --- ---

toNC 25.0 40.0 --- 30.9 30.5 --- ---

toWi 19.0 35.0 --- 24.9 23.1 --- ---

All values ms

Explanation Explanation.

tC (mSec) Closing time tCNC (mSec) Aux. switch break contact, close

dtC (mSec) Closing time difference tCNO (mSec) Aux. switch make contact, close

tO (mSec) Opening time tCWi (mSec) Aux. switch wipe contact, close

dtO (mSec) Opening time difference tONC (mSec) Aux. switch break contact, open

tCO (mSec) Close-Open time tONO (mSec) Aux. switch make contact, open

dtO(CO) (mSec) Time difference 2nd Opening OCO tOWi (mSec) Aux. switch wipe contact, open

Stamp Sign by Testing Engineer

___________________________
ETHPCB/AW-QT/F/02/02

Breaker Sr. No. : 2019/26134 Circuit-breaker type :145kV

3 Operations carried out

220 DC Volts
Rated Voltage (Un) :

Quantity Switching operation Trip voltage

5 CLOSE ( C ) 0.85 x 220 DC Volts

5 OPEN (O) 0.7 x 220 DC Volts

5 CLOSE ( C ) 1.1 x 220 DC Volts

5 OPEN (O) 1.1 x 220 DC Volts

5 Close Open ( CO ) Un 220 DC Volts

5 0-0.3s-CO Un 220 DC Volts

4. Charging time of closing Spring

Rated Voltage : 230 AC Volts

Parameter Maximum. Value Actual Value

<=15 5.05
Spring Charging Time (Sec.)

All values in Sec

5. Measurements of Coil Resistance

Rated voltage Actual Value


Coil (V DC) (Ohm)

Closing Coil 220 DC Volts 214.8

212.0
Tripping Coils
220 DC Volts
212.3

Stamp Sign by Testing Engineer

___________________________
ETHPCB/AW-QT/F/02/02

Breaker Sr. No. : 2019/26134 Circuit-breaker type : 145kV

6. Measurement of the resistance of the main circuit (Micro Ohms )


Voltage drop between connecting flanges, measured at 100 A (DC).

Maximum. Value Pole A Pole B Pole C


52.0 (μΩ) 39.50 38.69 39.45
All values μΩ

7. SF6 gas pressure monitoring (Bar)

Nominal values and tolerances correspond to 20°C. Actual values measured at actual ambient temperature and
normalized to 20°C.

Maximum
Name of contact Nom. val. Actual Value Direction
Value.

5.0 5.2 5.2 fall


Loss of SF6

4.8 5.0 5.0 fall


General lockout SF6

8. Voltage withstand tests on control and auxiliary circuits

All connections of control panel : 2.0kV, 50Hz.

9. Power frequency voltage withstand tests on the main circuit

The specified power frequency voltage withstands tests, was carried out successfully.as per IEC 62271-100

275kV For 1minute, 50Hz on Complete Breaker

10. Tests and Inspections

The folowing tests were performed during the routine test in accordance with IEC 62271-100

Inspection of the wiring Rating Plate.

Gas tightness Circuit Check of anti condensation heaters

Anti-pumping device Earthing terminals of the circuit-breaker.

Stamp Sign by Testing Engineer

___________________________