W H I T E PA P E R
07 The advantages of
digital switchgear
—
Making the switch to
digital switchgear
From industrial manufacturing and processing Besides control function, smart devices can also
facilities to data center server farms and support collect a wealth of data related to the operational
systems like lighting and air conditioning, almost condition of circuit breakers, motors or feeders.
every aspect of the modern world requires a However, there are various reasons that still lead
constant, reliable source of electric power. many operators to choose traditional, simpler
switchgear devices.
As a foundational piece of electrical equipment,
switchgear plays a key role in delivering First, there is a perception that smart devices
dependable energy. Switchgear is used to have higher complexity and lower reliability. Plant
distribute electricity safely and effectively operators are sometimes worried that alarms
from the high voltage of 6 to 36 kV coming from would be issued too early or without a real need,
power plants and utility networks to low voltage creating a low level of trust. To avoid unnecessary
distribution networks that are in the range of alarms, time must be spent programming the
up to 690V. smart device to operate appropriately.
—
The hidden cost of traditional
switchgear technology
A traditional switchgear can be of conventional But preventative maintenance means more than
design or be one that uses smart devices but not just giving switchgear its annual check-up. It
all the data they provide. There are many hidden means identifying small symptoms and acting
costs of traditional switchgear that can add up before it becomes a more serious problem, which
over the life of the switchgear. These costs can may require further data.
include:
For example, a temperature increase can indicate
• The initial cost of device implementation and bad electrical joints due to loose connections,
correct parameter value-setting, which can be which leads to higher resistance in the
time-consuming due to a lack of necessary conducting circuit. If undetected, this can lead
information. to a dangerous situation such as arcing or fire.
• Coordination between the engineering and Even preventative yearly maintenance can miss
commissioning team, which is often needed to this critical moment. The ability to monitor and
reconcile information used to inform design respond to a small increase in temperature can
versus on-site, real-world load and rating make all the difference in avoiding catastrophe.
changes.
• Switchgear testing, including manual Another thing to keep in mind is that switchgear
operational data collection and report creation, has an average life of 30 years. While conventional
which can require costly and time-consuming switchgear may be great for your CapEx, this can
coordination with the buyer, operator and lead to a situation where your switchgear is
manufacturer. engineered and built in accordance with your
• Operational costs, including regular visual known requirements at the time of purchase,
inspection, function checks and further not the needs of your business in 10 or 20 years in
maintenance that is sometimes conducted the future. If you consider new machinery that is
on a preventative basis rather than on a brought in, an added extension to the building,
need basis. or a larger motor replacing a smaller motor in the
manufacturing process, you can see how easy the
Due to its complexity and always-on nature, power demand on the electrical assembly could
it can be difficult and expensive to keep up increase, which can decrease the life expectancy
with switchgear maintenance. For example, of devices or put them at risk of failure.
the manufacturer may recommend inspection
and maintenance every two years, while plant While switchgear can be extended by adding
shutdown can be scheduled for intervals of five a new breaker in a spare space inside of the
years, creating conflict in planning. Without the assembly or by adding a new section or panel, it
ability to know what is happening with devices, can be difficult for operators to calculate if there
operators are forced to conduct reactive is sufficient electrical and thermal capacity in the
maintenance, maintain a collection of expensive switchgear to add new components or if there is
spare parts and keep a trained maintenance team a need for more capable switchgear altogether.
available in the case of device failure. Despite By using manual calculations instead of real data,
being more expensive and disruptive, reactive operators risk making the wrong decision or
maintenance is still far more common than delaying the right decision until it's too late.
preventative maintenance, which could
keep the switchgear running in top condition
and minimize downtime.
6 M A K I N G T H E S W I T C H T O D I G I TA L S W I T C H G E A R
—
Unlocking your data
Your electrical infrastructure is already capable However, if accessed and incorporated into a
of producing more data than you may realize. single system, this data could be used to identify
For example, protection relays not only operate the right threshold settings and help drive
the breaker under normal conditions, but also trip cost-effective predictive switchgear maintenance
the breaker when critical situations are detected based on actual condition information, which is
in the electrical network. While those relays count far preferable to waiting for a costly failure to
the operation and trip cycles, they can also be occur.
used to estimate contact wear and other breaker
condition data. Of course, if it were that simple, you’d already
be doing it. To access this data, it can often
Meanwhile, motor controllers used in everything take specialized knowledge to set up and
from industrial operations to HVAC systems program smart devices, fieldbus and Ethernet
could collect not just operation and trip data, but communication inside of the electrical assembly.
motor load conditions that can help the operator Process and electrical control teams often
detect problems in motors or attached machines. don’t know or understand the need for condition
However, the data your devices create is only as monitoring, thus they configure and read only the
useful as your ability to collect and access it. data they need to keep their costs to a minimum.
—
The advantages of digital
switchgear
—
Digital switchgear use cases
Digital medium-voltage (MV) and low-voltage (LV) Moreover, collecting and monitoring data
switchgear solutions not only distribute energy of other components in an MV switchgear
safely and reliably but also have the capabilities assembly such as earthing switches,
to monitor the condition of devices and other disconnectors, and the correct lock position of
electrical equipment included in the switchgear. doors, provides further insights into the electrical
These devices are connected through Ethernet- and mechanical status of the assembly without
based digital communication, including the the need to be present in the switch room, thus
widely used IEC 61850 for medium-voltage enhancing overall safety for the operation and
devices and Modbus TCP or OPC UA for all maintenance teams.
devices. Those communication protocols are
commonly found today in industrial Internet With MV and LV switchgear section or panel
of Things (IoT) platforms. condition monitoring, temperature and humidity
data can be collected from both the switch room
Intelligent electronic devices (IED) such as ABB’s and from inside the switchgear. This provides
Relion® relays or ABB’s low-voltage circuit breaker insight into the operating conditions and
Emax 2 with Ekip control and protection unit not potential impact on the switchgear over its
only perform control and protection functions lifetime. Monitoring your critical electrical
but optionally include a feature for circuit breaker connections 24/7 eliminates the need for manual
condition monitoring that provides an operator maintenance tasks and ensures data is
with data that can be analyzed and used for continuously recorded and analyzed.
scheduling circuit breaker maintenance or
function testing, while a runtime counter enables In MV switchgear, monitoring insulation and
scheduling of time-based maintenance for the partial discharge occurrences provide even
connected motor or transformer. more information.
—
03 Inside view of a MV IED protection and monitoring relay
switchgear section
Temperature monitoring
Circuit breaker
Truck monitoring
LV switchgear is largely used to distribute With digital switchgear, module data can be
energy to hundreds of loads such as motors or provided by smart devices such as a power meter
sub-distribution panels. Located in various areas and motor controller to monitor module
of a building or plant, it is often exposed to insertions and temperatures so you can better
temperature and humidity changes. While understand conditions, calculate the correct
switchgear is designed to accommodate a certain maintenance cycles, and minimize maintenance
level of heat caused by heat losses inside the efforts by working only on those modules in need,
switchgear, an extension during its lifetime will avoiding entire switchgear shutdowns.
further increase the heat level. Traditionally, an
operator must make calculations to determine Smart LV motor controllers are another group of
the possibility of adding loads to avoid exceeding devices that are often underutilized compared
the thermal and electrical capacity of switchgear. to their digital capabilities. While their primary
However, digital switchgear can provide current function is motor control and protection, they are
and historical data as the basis for operators and capable of collecting additional valuable data,
planners when making the right decisions for such as:
extension planning.
• Motor current levels and imbalances
LV switchgear also consists of various types • Thermal loading levels
of modules, feeding motors or external loads. • Operating and insertion counter data
This is another area where maintenance, • Condition monitoring data
although regularly required, is sometimes • Temperature, humidity and other data using
overlooked. Removable modules use specially additional sensors
designed contact systems for power connections
that are designed to withstand a number of Finally, motor current levels and imbalances can
operations (as per IEC 61439 minimum 200 clearly indicate issues with the motor or the
operations). These contact systems require connected machine. With this data, you can go
maintenance like greasing, which is traditionally beyond switchgear monitoring to enable the
— conducted in maintenance cycles that may not monitoring of your complete power train.
04
align with the actual maintenance needs of the
Inside view of a LV
switchgear assembly component.
Circuit Temperature
breaker monitoring
monitoring
Switchgear load
level, power loss
monitoring
—
Condition monitoring on a
digitized switchgear
Enthernet network
IEC 61850
Medium- Protection Air Molded Power Variable Softstarter Motor Low-voltage Other device
voltage relay and circuit case meter speed starter temperature integration
temperature circuit breaker circuit drive sensors
and partial breaker breaker
discharge monitoring
sensors
C O N D I T I O N M O N I TO R I N G O N A D I G I T I Z E D S W I TC H G E A R 11
—
Whether using the simple app from a smartphone
—
06 Example of
an ABB Ability™
CMES dashboard
or tablet or working with a more powerful An interactive user dashboard
workstation, a Condition monitoring solution
allows you to prevent failures, predict conditions
provides an immediate, real-time
and manage energy consumption so you can summary overview of the health
reduce maintenance and operational costs.
index of all switchgear, as well as
Installed as an integral part of the switchgear sections and devices, on a plant-
assembly at the time of manufacturing, the
solution monitors the complete lifetime of a
wide, substation, or switchgear
switchgear from factory acceptance testing basis.
(FAT) through commissioning and operational
life on site. No programming knowledge shall be required to
set up the solution. Moreover to increase usability
While traditional process control and supervisory and speedup troubleshooting, the Condition
control and data acquisition systems (SCADA) monitoring solution shall offer a ‘Knowledge
only read the necessary data points required for Base’ guiding you through every alarm or event
control functions, a Condition Monitoring providing a detailed description of the issues,
solution reads every data point provided by possible reasons, and suggested actions for
devices and sensors in the switchgear. remedy.
12 M A K I N G T H E S W I T C H T O D I G I TA L S W I T C H G E A R
—
Digitalization and condition
monitoring benefits
Flexibility
• Digital switchgear can be easily adapted and
customized as requirements change, such as
when loads are added to the switchgear
• Add sensors or smart devices to upgrade
conventional feeders or motor starters without
interventions on power parts like circuit
breakers, cables or busbars
• Upgrade software to utilize new functionality
without changing the equipment physically
• Support virtual factory acceptance testing,
commissioning support, remote service and
troubleshooting through digital services
and tools
Customize
• Add switchgear panel, devices or functions all
at once or incrementally
• Easily combine fixed, plug-in or withdrawable
switchgear technology
D I G I TA L I Z AT I O N A N D C O N D I T I O N M O N I TO R I N G B E N E F I T S 13
Optimize
—
• Shift from planned maintenance to By using a digital switchgear
condition-based and predictive maintenance
• Reduce cost impact of unexpected shutdowns with
solution from ABB, you get
faster fault analysis the visibility and knowledge
• Plan ahead with condition reports and maintenance
date calculation
necessary to make data-driven
• Improve energy management using energy maintenance decisions so you
consumption data available from each connected
motor or load
can identify and solve minor
• Prioritize investment and optimization steps issues before they become a
by identifying less efficient equipment
• Achieve continuous operation by avoiding
major problem. In doing so,
unplanned outages while optimizing operating you can help increase uptime,
costs and reach savings of up to 30 percent
decrease maintenance costs
Economize and spend more time focused
• Replace only specific components instead of entire
devices based on individual condition situations
on high-value tasks instead of
• Upgrading devices can cost up to 30 percent less manual monitoring and data
than full replacement of a switchgear at later
stages
collection.
• Reduce infrastructure requirements as Ethernet-
powered infrastructure are less expensive to
purchase, install and maintain compared to
Learn more about ABB Ability™
hardwired connections CMES.
• PLC-free design further reduces infrastructure
investment by up to 20 percent
14 M A K I N G T H E S W I T C H T O D I G I TA L S W I T C H G E A R
—
To the Edge and beyond
Digitalization and the adoption of the Industrial An Edge device is relatively inexpensive to install
Internet of Things (IIoT) in electrical systems and operate while still providing a suitable level of
requires careful analysis. Keep in mind that data on-site calculation power and data storage,
collected from electrical systems reflect site making it an effective solution whether used
operational and maintenance conditions. Any solely on-premise or connected to the cloud.
analysis that takes place on-premise is limited to
what it gets from that premise, while situations Many users of digital switchgear adopt Edge
and experiences from other sites are not computing as a crucial part of their hybrid data
considered. architecture thanks to its ability to vastly reduce
latency, reduce the need for data centers and cut
While this may be sufficient for your operation down on costly bandwidth requirements. And
and maintenance planning today, it may not with connectivity to ABB Ability™ cloud-based
be in the future. So, should all the data be sent solutions, you can extend predictive capabilities
to a larger data center for further analytics, that help you understand probabilities of failure
machine learning and the application of artificial across multiple sites and switchgear, enabling
intelligence? Not necessarily. Here, Edge you to further reduce operational costs while
computing plays a critical role. Instead of being making your switchgear capable for the future
transmitted to a far-off data center, your data can needs of Industry 4.0.
be processed in real-time on a local computer,
server or even the device that collects it.
—
ABB Ability™ gives the best of Learn more about ABB
both worlds. Because ABB Ability Electrification and
solution are also installed on ABB Ability™.
Edge devices, you have the option
to connect to on-site systems or
cloud-based solutions for
maintenance management.