Professional Documents
Culture Documents
INSTALLATION
3.1. Site & Environment Considerations
Usually the life expectancy of the UPS is 5 to 10 years (batteries are not included
because life expectancy of batteries depend on the type of battery, the temperat
and humidity of the environment in which it is installed, and the type of charger that
is applied to the battery). Therefore optimal life expectancy of
achieved by careful consideration of the site and environment.
(a) T h e U P S s h o u l d b e l o c a t e d i n a p l a c e w i t h a d e q u a t e v e n t i l a t i o n ( r e f e
specification of the heat dissipation of the UPS). If the UPS is installed indoors,
care must be taken in insuring the evacuation of heat from a closed room.
(b) Adequate space (at least 1M) should be allowed to open the door, unobstructed
by other objects, for operation or maintenance. Adequate space (a
s houl d be al l owed at t he t op of t he UPS, becaus e heat di ss i pat i on i s vent i l a
through the top openings.
(c) Do not put any objects on the top of the UPS that may obstruct ventilation. Do
not locate the UPS near any heat source, machinery which produce metallic dust
or powder, or any facility that will produce corrosive substances or vapor.
(d) P r o t e c t t h e U P S f r o m a c c i d e n t a l d a m a g e f r o m f i r e e x t i n g u i s h
systems. Protect the UPS from abnormal conditions with a dedicated cutoff from
the incoming power.
1
(e) It is necessary to guarantee the temperature and humidity values of the site into
which the UPS will be installed. These should be within the range allowed by the
specification. The UPS is capable of continuous normal
t e m p e r a t u r e r a n g e ℃(
o f 302℉) t o 4 0℃( 1 0 4℉) . F o r o p t i m a l p e r f o r m a n c e a n d
reliability, and to prolong UPS’s lifetime, it is rec
environment temperature below 25℃, and humidity below 80%.
(f) I f t h e U P S i s i n s t a l l e d o u t d o o r s , a v o i d d i r e c t e x p o s u r e
sunlight, wind, and rain. Avoid any exposure to sand or dust.
(g) The f loor loading capacit y should be high enough t o endure the wei ght of
UPS. The UPS is mounted on four right-angled steel angles. Insert corresponding
bolts and nut2 (dia.1/2”) into the floor for securing the UPS on the floor when it
is located in an area where earthquakes is possible, or where motion may occur,
e.g. vehicle mounted. Layout dimensions, in millimeters, are shown below.
2
(h) Wa l l s , c e i l i n g s , a n d f l o o r s n e a r t h e U P S s h o u l d b e p r e f e r a b l y c o n
non-combustible materials. A portable fire extinguisher sh
nearby in case of hazard.
(j) Access to the UPS room should be limited to a minimum number of operation
and maintenance personnel only. The doors should be kept locked and the keys
should be confined to authorized personnel only.
(k) Pe r s o n n e l w h o o p e r a t e o r m a i n t a i n t h e U P S s y s t e m s h o u l d b e p r o
normal and emergency operational procedures. Ne
trained and qualified prior to operating the equipment.
(l) Although the UPS has passed International EMC tests, it is recommended that
the UPS not be installed near any equipment that is susceptib
magnetic interference, such as computer systems, monitors, radios, etc.
(m) I t i s p r e f e r a b l e t o p l a c e t h e U P S n e a r t o t h e s o u r c e r a t h e r t h a n n e a r
load.
3
3.2. Unpacking
Carefully unpack the UPS, and then carefully locate the UPS onto the site which has
selected, with all the points in section 3.1 kept in mind.
T h e U P hSa sh a d d e t a ipl re od d u c t i o n a n d Q C t e s t i n g o f a l l t h e e l e
m e c h a n i c aclh a r a c t e r i s t i c s p r i o r t o s h i pf rmo emn tt h e f a c t o. rTyh e r e f o r e , t h e U P S
should be inproper conditionupon receipt.Once received, the UPS should be first
c h e c kvei ds u a l l y t o d i ef ta en rym pi nh ey s i c a l h da as moacgc eu r r e d d u
transportation.
- DOOR KEY
- THIS INSTRUCTION MANUAL
- BATTERY FUSE (FOR BATTERY CABINET ONLY)
- SPARE SCREWS FOR COVER PLATE
- SPARE SCREWS FOR CONNECTION TERMINALS etc.
Lastly, check to insure that the specification of the
specification of your order. The key items in the specification you must check are:
4
3.3. Cable Selection
The following tables list typical information concerning the KVA of the UPS versus
t he s i ze and r at i ng of t he cabl es. I nadequa te cabl e s iz e or ove r s i zed bre aker s
incur risk of fire or damage of insulation. Therefore, please use the following tables
to determine the input circuit breaker rating and the size of cable for input, out
and battery connections. These data are for reference; final decisions should be made
in accordance with the local electrical codes.
5
40 208/120V 3Φ 138 60 80
50 208/120V 3Φ 173 80 100
60 208/120V 3Φ 208 100 125
80 208/120V 3Φ 277 125 200
100 208/120V 3Φ 346 200 250
120 208/120V 3Φ 415 100*2 125*2
160 208/120V 3Φ 554 125*2 150*2
240 208/120V 3Φ 830 100*4 125*4
320 208/120V 3Φ 1108 150*4 200*4
6
FUSE RATING & CABLE SIZE FOR BATTERY
☆ THE BATTERY VOLTAGE IS 295 – 410V
7
3.4. Terminal Connection
☆☆☆ Three extra terminals are installed for convenience of changing the unit to
separate reserve input.
8
For single phase output UPS, the current is very much lar
terminal, therefore the terminal looks bigger than it is needed.
☆ ☆☆ Extra empty terminals are installed for convenience of changing the unit to
separate reserve input.
9
3.5. 1+1 Parallel Terminal Connection
10