key (terminate the “initialize” function) + Set P052= 1 (select the function "Generate manufacturer setting”; when the
key is pressed, all parameters are reset to their factory setting or to the PO77-dependent value) If only those parameter values that are dependent on PO77 are required to be changed and all other parameters should remain unchanged, the following procedure is necessary «Set P051= 3 (expert mode) + Set P0S2= 2 (select “initialize” function (set MLFB) + Note PO70 and set POTO= 0 * Set PO77= 5 or 6 (select the required PO77-dependent parameter setting) # Set P052= 0 and press the
key (read in the parameter values dependent on P077) * Move the F060 error message into the "background! by pressing
+ key (MLFB is read in and the dependent parameters PO71, PO75 and PO76
are set)
* Move the F060 error message into the “foreground’ again by pressing + key
Additional parameter settings for the 12-pulse slave:
+ P05i= 3 (expert mode)
+» P688 = 1 (Peer-to-Peer protocol)
* Switch off earth short-circuit test (P354 = 0), when the unit is supplied from an unearthed supply. e.g, from
the delta winding of the 12-pulse transformer
+ For factory settings in accordance with PO77=5 or 6, binary input 1 is a source for “No external fault 1"
and binary input 2 is a source for "No external warning 1”. If this is not required, e.g. in the case of open
terminals, P575 = 1 and P588 = 1 must be set.
3.58 Siemens AG 6SETO67-SAKE5-1AAO
RecifierRegenerating Unit Operating Instructions12.98 Connection
Circuit identification:
Circuit identification should be carried out successively on the 12-pulse master and on the 12-pulse slave.
P052= 21 must be set on each unit for this purpose, and the switch-on command for the 12-pulse slave
comes from the 12-pulse master (the control word wiring ensures that the partner unit, in each case, does not
carry current or is held in the operating state r000= "~"
+ Circuit identification procedure for 12-pulse master:
Set P052= 21 on the 12-pulse master unit, switch on = circuit identification is carried out on the 12-pulse
master
n procedure for 42-pulse slave:
1 on the 12-pulse slave unit, switch on the 12-pulse master unit => circuit identification is
carried out on the 12-pulse slave
‘Note: If circuit identification is carried out with the basic settings selected (operation as a 12-pulse slave,
all control is from the 12-pulse master), the switch-on command must come from the 12-pulse master and
the power terminals of the 12-pulse master unit must be connected to the supply voltage.
Note: When the reserve setting is selected on the 12-pulse slave unit (with appropriate parameterization of
index i002 of the "Source selection parameters” P554, P5SS, .. itis also possible to issue the switch-on
command for circuit identification on the slave unit on-site via the PMU or OP1
Setting additional functions:
Ifrequired, activate the "auto restart” (via P366= 2) on the master and on the siave unit. This will be effective
in the event of failure of the electronics supply voltage provided that the Peer-to-Peer telegram failure
monitoring time has been switched off via P687.i003= 0,
3.8.6 Redundancy mode
If both rectifier/regenerating units are rated such that each separate unit is capable of carrying the full load
current, the following possibilities are available with respect to redundant operation.
+ Uninterrupted changeover of the 12-pulse master unit to stand-alone 6-pulse mode in the event of
failure of the 12-pulse slave unit during 12-pulse mode:
If the 12-pulse master is required to continue to run in “normal” stand-alone 6-pulse mode in the event of
failure of the 12-pulse slave unit without interruption, "External fault 3” must not be "wired" to the Peer-to-Peer
interface, but instead the parameterization P573.i001 (or i002) = 1 is required on the 12-pulse master. If the
master unit is also required to continue to run without an interruption in the event of failure of the Peer-to-Peer
interface cable, the Peer-to-Peer telegram failure monitoring time also has to be switched off via P687.i003=
on the master.
+ Reconnection of the 12-pulse slave unit during operation of the master:
If (12-pulse) operation of a 12-pulse slave unit is required to be reinstated following an interruption of the
Peer-to-Peer interface cable without error message and during (stand-alone 6-pulse) operation of the master
unit, the Peer-to-Peer telegram failure monitoring time also has to be switched off via P687.i003= 0 on the 12-
pulse slave unit,
+ Changeover of the 12-pulse slave unit to stand-alone 6-pulse mode in the event of failure of the 12-
pulse master unit:
In the event of failure of the master unit during 12-pulse mode, it is possible for the 12-pulse slave unit to
change over to stand-alone 6-pulse mode almost without interruption, because all external control commands
that are wired to the terminals of the master unit (e.g. ON command) are also carried to the terminals of the
12-pulse slave unit. Externally implemented logic must ensure that in the event of failure of the master unit,
the 12-pulse slave is switched from the basic to the reserve setting. The 12-pulse slave must be
parameterized appropriately in the reserve setting to facilitate stand-alone 6-pulse mode with external control
‘The Peer-to-Peer telegram failure monitoring time also has to be switched off via P687 i003 0 in this case.
Siemens AG_6SE7087-SAKES-1AAQ 3.59
RectfierRegenerating Unit Operating InstructionsConnection 12.08
Note
With the parameterization P687.i003=0 AND 681 i001 = 599, in the event of telegram failure, bits 3 and 6
of the first SST2 Peer-to-Peer receive data (\.e. the controlistatus word for 12-pulse mode sent from the
partner unit) are set to 0.
3.8.7 RS485 interface cable for the Peer-to-Peer link on SST2
‘The RS485 interface cable required for the serial Peer-to-Peer link on SST2 is in the form of a four-wire
connection.
A screened 4-core cable must be connected at the screw terminals of the 5-pole plug of terminal block -X117 on
‘submodule A2 (C98043-A1690). Submodule A2 is fitted to the CUR A10 electronics module (see Section 9.6).
‘The 4-core cable is not included in the scope of delivery.
12-pulse master 12-pulse slave
A2 A2
M
xn7, xt7
Figure 342 Connecting cable for Peer-to-Peer" communication on SST2 (between the terminals of the A2 submodule (C86042-A 1090)
3-80 Siemens AG 6SETO67-SAKE5-1AAO
RecifierRegenerating Unit Operating Instructions12.98 StartUp
4 Start-Up
41 Introduction and handling start-up
WARNING
Despite disconnecting the power terminals from the supply, voltage may still be
present on terminal X19 due to the external fan supply.
4A Handling the start-up instructions
NOTE.
# Section 4.2 First start-up:
First start-up of the rectifieriregenerating unit
# Section 4.3 Startup aids
Index-type reference for start-up and use of the rectifier/regenerating unit, which only has to be used if
actually required!
* Section 4.4 Funetion diagrams:
Graphical overview of the setpoint channel, open-loopiclosed-loop control, analog inputs/outputs, and the
rectiferiregenerating unit data sets
4A General explanation of the terminology and functions of the rectifieriregenerating unit
Abbreviations:
+ Abbreviations used: Refer to Section 15 "information, notes ”
rol Pf feriregener
+ "Function block diagrams: Open and closed-loop control": see Section 4.4
‘+ Application: Power supply of the variable-voltage DC link of SIMOVERT converters of the
@SEET0 series
Mode variants:
a) The line voltage in the regenerative branch is stepped up by an (auto) transformer to prevent
having to reduce the DC link voltage in regenerating mode
b) Permanent reduction of the DC link voltage by phase angle control in rectifier mode in order
to always be able to feed power back into the system
P18 Reduced DC link voltage setpoint (e.g. = 80 %)
P571= 0001 Permanent selection of reduced voltage
©) Reduction ofthe link voltage for regenerative mode only by means of open-loop control to be
able to exploit the line voltage fully in rectifier mode and not have to use an autotransformer
for feeding power back into the system. This type of power feedback is not intended for
dynamic operation, but only for setpoint-controlled operation in conjunction with external
‘open-loop control
P18 Reduced DC link voltage setpoint (e.g. = 80 %)
P571 = 1004 Selection of reduction via terminal X101-12
P613 = 1001 Output "DC Link voltage reduced” message to signaling relay X104-17/18
Pa19 Hysteresis "Link voltage reduced” message
Siemens AG 6SE7087-SAKES-1AA0 44
RectfierRegenerating Unit Operating Instructions