Professional Documents
Culture Documents
1
2016 年 2 月 Technical Acoustics Feb., 2016
Abstract: Rapid urban development in China has created many environmental noise issues. Six large cooling towers
were located at 15 m away from a residential building and the measured noise level at the noise receiver had exceeded
the national environmental standard by 25 dB(A). Traditional noise control measures by erecting acoustic barrier was
not effective while acoustic enclosure with silencers might affect the cooling performance of the cooling towers. The
challenge of this project is not only the high demand on noise attenuation but also the minimization of pressure drop
and elimination of air ventilation short circuit problem. The authors provided a total solution to the noise and air circu-
lation problems. Acoustic enclosure with 3 m and 1.8 m long silencers for air intake and discharge was designed and
built to reduce the noise level at the NSR from 75 dB(A) to 49 dB(A). The system and product designs to improve the
acoustic and aerodynamic performance are worth for discussion.
Key words: cooling tower noise; silencer; acoustic enclosure; acoustic barrier
ing to ISO 9613-2, the barrier attenuation should not from the cooling tower plant. By doing so, the orienta-
be taken to be greater than 20 dB. Moreover, the noise tion of discharge openings would be changed to face
sources in this project were not point sources, the equ- directly to the residential building around the plant. It
ation presented in the ISO 9613-2 and other simple was predicted that the noise level at the NSR would be
prediction models, such as Z. Maekawa model, was increased from 75 dB(A) to 80 dB(A). Accordingly,
not applicable. Estimation of the noise reduction by the new design would require to attenuate the noise
installation of barrier would be far more difficult in level by 30 dB(A).
this case. The formula to predict the noise levels at NSR is:
Furthermore, the erected barrier had increased Lp2 = Lp1 + A + D + IL + 3
the hot air short-circuit problem as illustrated in Fig.2. where
Lp2 is the sound pressure level at 1 m in front of
the building façade of NSR, in decibel, dB;
Lp1 is the sound pressure level in front of the air
opening, in decibel, dB;
A is the distance attenuation of sound, in deci-
bel, dB;
D is the directivity factor, in decibel, dB;
IL is the insertion loss of silencer, in decibel, dB;
The 3 dB factor is correction factor of façade ref-
lection.
Fig.2 Picture showing the Air Circulation Path in Existing Cooling It is remarked that there were 6 cooling towers
Tower Plant
and the noise would emit from the air intake, air dis-
charge and tower casing. This is a multisource cooling
2 TOTAL SOLUTION tower plant and predictions shall be conducted for
each source and path. The resultant noise levels shall
After a series of feasibility study, the design of be calculated at each NSR around the plant.
using acoustic enclosure and silencers was identified It has been mentioned that elbow plenums would
to be the best solution to solve the noise problem. be installed on top of the discharge silencers to reduce
However the challenge of this design was to fulfill the hot air short-circuit and inefficient heat dissipation
both the hot air short-circuit problem and the ultimate problem, the distance between the discharge outlets
noise reduction requirement, which is minimum 25 and intake air opening would still be too close. To
dB(A). Installation of silencers would induce air flow overcome this problem, the height of the intake open-
resistance which is the pressure drop of the silencers. ing was increased. The picture showing the air circula-
To minimize the effect on the cooling load of the cool- tion paths after installation of the silencers with air
ing towers, the pressure drop induced by installation plenums is shown in Fig.3.
of the silencers shall not be over 50 Pa.
The main noise sources of a typical cooling
tower are fan noise, water sparkling noise and motor
noise. Noise would radiate from the intake side, dis-
charge side and breakout through tower casing. The
noise contributions from each path and the corres-
ponding frequency spectra shall be measured at the
beginning of design stage. The noise level at 1 m in
front of the intake opening was 91 dB(A) while that at
2 m above the discharge opening was 86 dB(A). Fig.3 Picture showing the Air Circulation Path in the Cooling Tower
Plant according to the New Design
To reduce the hot air short-circuit problem, the
discharge air shall be diverted away from the centre Acoustic panels were used to build the air dis-
space over the plant room. It was proposed to install charge elbow plenums and air intake plenums. The
an elbow plenum on top of the discharge silencer to inner face of the acoustic panels was sound absorptive
divert the hot air to discharge horizontally and away which acted as lined ducts to further reduce the noise
第1期 IU King Kwong, et al:Acoustic barrier – not a total solution for reducing cooling towers’ noise 65
splitters should be reduced or the splitters should be splitter nose and tail will affect the aerodynamic per-
separated longitudinally and placed along the duct formance as well as the acoustic performance. Fur-
with an off-set, see Fig.5. thermore, the quality of sound absorption material and
how it is installed in the splitters will lead to devia-
tions from the predicted acoustic performance. Labor-
atory test is the most accurate method to validate the
performance of silencers.
To achieve the design requirement of acoustics
and aerodynamics of the silencers, Supreme Acoustics
has been performing a lot of product designs and la-
boratory tests in accordance with the testing standard
ASTM E477 and ISO 7235. Fig.7 shows the laborato-
Fig.5 Insertion Loss Di vs Frequency f and Pressure Loss Coefficient ζ ry test facilities which are the silencer test rig in
for Different Splitter Configurations
length of 50 m connected into the reverberation room
From Fig.5, both of the methods would increase for diffuse field sound pressure measurements.
the pressure loss, but the off-set method can only pro- The sound absorptive material in the splitters is a
vide an additional attenuation of less than 6 dB while major acoustic component of a silencer. Measurement
the pressure loss coefficient ζ was almost doubled. of specific airflow resistance is useful during product
After a series of estimation and consideration, the development and for quality control to ensure the con-
method of reducing the width of silencer airway was sistency of acoustic performance of the silencers dur-
chosen to increase the sound attenuation at high fre- ing manufacture.
quencies. The induced pressure loss shall be reduced Supreme Acoustics has been conducting many
by designing the splitters into streamline shape. airflow resistance tests for the sound absorptive mate-
In the final design, a 3 m long intake silencer rials according to ISO 9053:1991 to ensure the quali-
with 47% airway open area and 1.8 m long discharge ties of the silencers and for research purpose. Fig.8
silencer with 33% airway open area at each discharge shows the testing instrument.
opening were chosen. According to the flow rate of
cooling towers, the air face velocities at intake and
discharge silencers would be 3.9 m/s and 3.3 m/s, the
pressure loss induced by NAP Silentflo silencers at
these face velocities were tested to be 17 Pa and 26 Pa
respectively.
4 Laboratory Test
Although the silencer performance can be pre- Fig.7 Silencer Test Rig and Reverberation Room in Supreme Acous-
dicted by simple estimation formulae, the design of tics Testing Centre
第1期 IU King Kwong, et al:Acoustic barrier – not a total solution for reducing cooling towers’ noise 67
Reference
隔声屏障-不能治理冷却塔噪声
姚景光,杨香灏,冯雪珍
(盈达声学科研有限公司;盈达环科声学科研(深圳)有限公司)
摘要:现时中国大陆城市急速发展,做成大量环境噪声问题。某室外空调机房配备了六台冷却塔,与附近最近的居
民楼距离只有 15 m,测得的噪声比国标的规定高出了 25 dB(A)。传统的噪声治理是利用隔声屏障去阻挡冷却塔的噪
声,可是效果不显着,而使用隔声罩与消声器则可能会影响冷却塔运作。此项工程最大的挑战除了要做到高消声效
果外,还要解决消声器的压降与进出风短路问题。作者提供了一个整体的降噪治理和解决进出风短路的方案,最终
把居民楼的噪声由 75 dB(A)降至 49 dB(A)。此系统和产品设计非常值得讨论。
关键词:冷却塔噪声;消声器;隔声罩;隔音屏障
中图分类号:TB533 文献标识码:A 文章编号:1000-3630(2016)-01-0063-05
DOI 编码:10.16300/j.cnki.1000-3630.2016.01.014