DEPCO POWER GENERATOR

STANDARD SPECIFICATIONS
1. ENGINE
WATER-COOLED
FOUR STROKE HEAVY DUTY HIGH PERFORMANCE INDUSTRIAL
DIESEL ENGINE.

3 PHASE 2. ENGINE FILTRATION SYSTEM


• AIR FILTER
• FUEL FILTER
60HZ 220-240V • FULL FLOW LUBO OIL FILTER

ALL FILTERS HAS REPLACEABLE ELEMENTS

DIESEL FUEL
3. COOLING SYSTEM

EFFICIENT WATER-COOLED SYSTEM WITH COMPLETE SAFETY


GUARDS, DESIGNED TO COOL THE ENGINE AT HIGH AMBIENT
TEMPERATURES (CONSULT US FOR DE-RATION FACTORS)

4. EXHAUST SYSTEM
HEAVY DUTY INDUSTRIAL EXHAUST SILENCER

5. CIRCUIT BREAKER TYPE


DELIXI MCCB 3POLE
GENERATING SET MODEL DPK-DB-32 ALTERNATOR DATA
OUTPUT RATING PRIME STANDBY MAKE LEROY SOMER
208V,3PH, 60HZ,1800RPM 29KVA 32KVA MODEL LSA 42.3 VS1
23KW 25KW NO.OF BEARINGS 1
INSULATION CLASS H
ENGINE TECHNICAL DATA WIRES 12
ENGINE MAKE BAUDOUIN INGRESS PROTECTION IP23
ENGINE MODEL 4M06G25/6 EXCITATION SYSTEM SHUNT
GOVERNING TYPE Electrical VOLTAGE ±1%
NUMBER OF CYLINDERS 4
CYLINDER ARRANGEMENT IN-LINE DIMENSION & WEIGHT
BORE AND STROKE (mm) 89 X 92 LENGTH mm 1950
DISPLACEMENT 2.3 L WIDTH mm 780
ASPIRATION NATURALLY HEIGHT mm 1050
CYCLE 4 STROKE WEIGHT*kg 760
COMPRESSION RATIO 17.5:1 FUEL TANK CAPACITY 65
COOLING SYSTEM WATER-COOLING
FREQUENCY & ENGINE SPEED 60HZ & 1800RPM CONTROL PANEL
PRIME STANDBY MAKE DEEPSEA
GROSS ENGINE POWER kW 27kW - MODEL 7320
FUEL CONSUMPTION @ 100% L/hr 6.177 - PLEASE REFER TO D300 BROCHURE FOR MORE DETAILS
FUEL CONSUMPTION @ 50% L/hr - - AN INSPIRED DESIGN D300 TO MEET YOUR NEEDS
DEPCO POWER GENERATOR
RATINGS DEFINITION STANDARD SPECIFICATIONS
PRIME POWER 8.2 ANTI-VIBERATION MOUNTING DUMPER 6. FUEL SYSTEM
DUMPER ARE AFFIXED BETWEEN THE ENGINE & ALTERNATOR
THESE RATING ARE APPLICABLE FOR SUPPLYING CONTINUOUS FEET AND THE CHASSIS, THUS ENSURING COMPLETE
ELECTRICAL POWER (AT VARIABLE LOAD) IN LIEU OF COMMERCIALLY VIBRATION ISOLATION OF ROTATING ASSEMBLY. ON GENERATING SETS UP TO 22KVA STANDBY, THE CHASSIS
PURCHASED POWER. 10% OVERLOAD POWER IS AVAILABLE FOR 1HOUR DESIGN IS INCORPORATED WITH INTEGRAL FUEL TANK WITH
IN 12HOURS CONTINUOUS OPERATION. A CAPACITY OF APPROX 5HOURS TO 8HOURS RUNNING AT
8.3 COUPLING
FULL LOAD. THE TANK IS SUPPLIED COMPLETE WITH FILL
THE ENGINE AND ALTERNATOR ARE DIRECTLY COUPLED BY CAP, BREATHER, FUEL FEED AND RETURN LINES TO THE
STANDBY POWER ENGINE AND DRAIN PLUG.
MEANS OF AN SAE FLANGE. THE ENGINE FLYWHEEL IS
THESE RATING ARE APPLICABLE FOR SUPPLYING CONTINUOUS FLEXIBLY COUPLED TO THE ALTERNATOR ROTOR.
ELECTRICAL POWER (AT VARIABLE LOAD) IN THE EVENT OF A
UTILITY POWER FAILURE. NO OVERLOAD IS PERMITTED.
8.4 SAFETY GUARDS 7. ALTERNATOR
STANDARD REFERENCE CONDITIONS THE FAN & FAN DRIVE ALONG WITH THE BATTERY 7.1 INSULATION SYSTEM
OUTPUT RATING ARE PRESENTED AT 27℃ AIR INLET TEMPERATURE, CHARGING ALTERNATOR ARE SAFETY GUARD PROTECTED FOR • THE INSULATION SYSTEM IS CLASS H
BAROMETRIC PRESSURE 100kPa, RELATIVE HUMIDITY 30%. THIS PERSONAL PROTECTION.
GENERATING SET IS DESIGNED TO OPERATE AT HIGH AMBIENT
TEMPERATURE (UP TO 52℃), HUMIDITY (UP TO 90%) AND HIGH 9. TESTS • ALL WINDINGS ARE IMPREGNATED IN EITHER A TRIPLE
ALTITUDES. DE-RATION MAY APPLY, PLEASE CONSULT US FOR DIP THERMOSETTING LIQUID, OIL AND ACID RESISTING
• THE GENERATING SET IS LOAD TEST BEFORE
SPECIFIC SITE RATINGS. POLYESTER VARNISH OR VACUUM PRESSURE IMPREGNATED
DISPATCH.
WITH A SPECIAL POLYESTER RESIN.
• ALL PROTECTIVE DEVICES CONTROL FUNCTIONS AND
AVAILABLE OPTIONS & ACCESSORIES SITE LOAD CONDITIONS ARE SIMULATED. THE GENERATOR
WE OFFER A RANGE OF OPTIONAL FEATURES AND ACCESSORIES TO AND IT'S SYSTEMS ARE CHECKED BEFORE DISPATCH.
• HEAVY COAT OF ANTITRACKING VARNISH ADDITIONAL
TAILOR OUR GENERATING SETS TO MEET YOUR POWER NEEDS.
PROTECTION AGAINST MOISTURE OR CONDENSATION
10. EQUIPMENT FINISHING
OPTIONS ALL MILD STEEL COMPONENTS ARE FULLY DEGREASED AND
• A VARIETY OF GENERATING SET CONTROL AND SYNCHRONIZING PAINTED WITH POWDER COATED PAINT TO ENSURE MAXIMUM 7.2 AUTOMATIC VOLTAGE REGULATOR (AVR)
PANELS SCUFF RESISTANCE AND DURABILITY.
• THE FULLY SEALED AUTOMATIC VOLTAGE REGULATOR
• ADDITIONAL PROTECTION ALARMS AND SHUTDOWNS
MAINTAINS THE VOLTAGE REGULATION AT ±1%.
• WATER - FUEL SEPERATOR 11. EQUIPMENT FINISHING
• WATERJACKET HEATER OPERATION & MAINTENANCE MANUAL, CIRCUIT WIRING
• BATTERY CHARGER DIAGRAMS. 7.3 MOTOR STARING (OPTIONAL)

ACCESSORIES 12. QUALITY STANDARDS • AN OVERLOAD CAPACITY EQUIVALENT TO 300% OF THE


• GENUINE SPARE PARTS THE EUQIPMENT MEETS THE FOLLOWING FULL LOAD IMPEDANCE AT ZERO POWER FACTOR CAN BE
• AUXILIARY FUEL TANKS STANDARDS:BS4999, BS5000, BS5514, IEC60034, SUSTAINED FOR 10 SECONDS, WHEN AREP (AUXILIARY
VDE0530 AND ISO8528 WINDING)OPTION IS FITTED.
• MANUAL & AUTOMATIC TRANSFER SWITCHS

13. WARRANTY
ASSEMBLED AND DISTRIBUTED BY ALL OF THE GENERATING SETS ARE COVERED UNDER A 8. MOUNTING ARRANGMENT
WARRANTY POLICY FOR A PERIOD OF 12MONTHS OR 1 YEAR 8.1 CHASSIS
(WHICHEVER COMES EARLIER) OF THE EQUIPMENT IS IN
LINE WITH MANUFACTURERS WARRANTY TERMS AND THE COMPLETE GENERATING SET IS MOUNTED AS A WHOLE
CONDITIONS. ON A HEAVY DUTY FABRICATED STEEL CHASSIS.
FUJIAN DEPCO POWER GENERATION CO.,LTD