INTRODUCTION
1,600
WHILE the increasing trend in the number of
datacenters continues unflaggingly, the increasing
(hundred million kWh/year)
Power consumption volume
50%
60 High-efficiency decrease commercialization efforts in setting up the
power-supply CoolCenter50 project, which has set a target of
40 equipment
Heat-conduction reducing total datacenter power consumption by up to
simulation
20 High-efficiency 50% over five years. At present, we are speeding up
Achievements of
air-conditioner Harmonious Green plan development of the energy-saving technologies to meet
0 this target.
Present Equipment-environment Optimization
improvement (after 5 years) In regard to main IT products, priority areas for
UPS: uninterruptible power supply IT: information technology power reduction and a technology roadmap were
established as the Harmonious Green plan, and product
Fig. 2—Breakdown of Power Consumption of a Datacenter and
development is instigated by the research and
Power-consumption Reduction Model.
As for a datacenter, power consumption of IT equipment does
development sector as a whole in the manner described
not exceed about half of total power consumption, so it is also in the following.
necessary to boost efficiency of the whole center, including As for facilities, air-conditioning efficiency of
equipment such as UPS, transformers, and air-conditioners. server rooms is being optimized, and, for example,
Hitachi is pursuing energy saving for improving the equipment energy-saving technology for air-conditioning and
environment as well as IT equipment. power-supply equipment and technology for
Strengthening development of
environmentally friendly products Energy saving for an entire datacenter
230%
Air-conditioning
Current diagnosis
40°C
Input-air side→ capacity deficiency
30°C
Input-air temperature to
177%
Input-air side→ 20°C
all racks
exceeds 35°C.
Capacity utilization of
218%
all air-conditioning equipment
Input-air side→ exceeds 100%.
288% 255% 224%
Proposal for improvement
94%
units added 40°C No problems
Environment Consulting Service.
30°C Input-air temperature to
all racks is 35°C By means of simulation, temperature
94%
77%
20°C
or less. distribution in server room, airflow
Capacity utilization of
all air-conditioning distribution, and air-conditioning
87%
88%
equipment is utilization rate are calculated, and
100% or lower.
96% 74% 93% air-conditioning efficiency can be
optimized.
optimizing control of air-conditioning units en masse example, it then determines whether or not the cooling
(in response to load on IT equipment) are being performance of an air-conditioning facility is sufficient
developed. and whether local “hot spots” are occurring.
Applying these energy-saving technologies and
optimizing the power consumption of an entire Improvement
datacenter are expected to cut power consumption by In the next step, based on the results of the diagnosis
50% (at most) over five years in comparison to present- step, a plan for improving air-conditioning efficiency
day consumption. As for datacenters within Hitachi, by reviewing locations of equipment, devices, and
these energy-saving technologies are already being wiring and by eliminating hot spots is set up, and
applied, and while the results of these applications are measures and policies for energy saving by properly
being verified, foundation of new datacenters — based setting the number of operating air conditioners are
on these results — is going ahead. proposed. An example of such an improvement plan
Such know-how gained within Hitachi is bundled for deficiency in air-conditioning performance is
together as solutions, and our approach for datacenter shown in Fig. 4.
power saving is systemized in five steps, namely,
“diagnosis,” “improvement,” “operation and Optimization
management,” “optimization,” and “construction,” and Although the improvement step mainly aims at
each step is presented as a “construction and efficiently using existing equipment, in the
improvement solution” targeting customers’ optimization step, replacement with Hitachi’s energy-
datacenters. Each of these solutions is described in saving equipment is recommended. That is to say,
the following sections. while engineers with full knowledge of the features of
each piece of equipment are collaborating, the power
Diagnosis consumption of the entire datacenter is optimized. By
As for the diagnosis step, power efficiency of a applying virtualization technology in regard to IT
datacenter (including IT equipment, power-supply equipment, Hitachi will, for example, continue to
equipment, and air-conditioning systems) is diagnosed develop optimization solutions through power-saving
in total. In particular, regarding server rooms, a operation and reduction of server number by server
consulting service for air-conditioning environments integration.
is being provided. This service uses a three-
dimensional airflow and heat-transfer simulator, Operation and Management
calculates temperature distribution, airflow distribution, Hitachi is providing solutions that visualize
and air-conditioner operation ratio. From that data, for temperature and humidity of individual server racks
Hitachi Review Vol. 57 (2008), No. 5 229
Utilization-resource optimization
Virtualization
Cooling