HECPS Generator
circuit-breakers
Table of contents
Hitachi Energy is a leader in the design and manufacturing The generator circuit-breaker system HECPS is one integrated
of generator circuit-breakers (GCBs) since 1954 with more than solution which provides all functions required by pumped stor-
Standards and quality Further tests such as temperature rise, extended mechanical
endurance, low temperature, high temperature, sound level,
8,000 deliveries in over 100 countries. We offer the widest and age power plants (PSPP) in one system and from a single
The generator circuit-breaker system type HECPS fulfils degree of protection and reaction force tests were carried out
most modern portfolio of GCBs in SF6 and vacuum technology manufacturer and is available with the following ratings:
the requirements of all relevant standards, i.e. IEEE C37.013, with all the related components within the system to verify the
with a range of short-circuit current ratings from 50 kA to • Up to 130 kA rated system-source short-circuit current
IEC/ IEEE 62271-37-013, IEC 62271-1, IEC 62271-102, liability and compliance with the requirements of the relevant
300 kA and nominal currents from 3,150 A to over 50,000 A • Up to 25.3 kV rated voltage
IEC 61869-2, IEC 61869-3, IEC 60358, IEC 60099-4, standards.
to meet the demand of all types of power plants around • Up to 17,500 A rated normal current at 50 Hz/ 60 Hz
IEC 62271-300, IEC 60480 and IEC 60529. The HECS system
the globe. • Full 180° out-of-phase current switching capability
is tested according to the standard that were valid at the time Routine and factory acceptance tests
of testing. Prior to dispatch, the generator circuit-breaker system is sub-
GCBs protect the important assets in power plants such as The interrupting chamber of HECPS is fully type tested
jected to an extensive test program defined in accordance with
generators and transformers by clearing potential harmful according to IEEE C37.013 and designed to meet the
The production of generator circuit-breakers in Switzerland is the standards IEC/ IEEE 62271-37-013:2015 and
short-circuit faults in tens of milliseconds preventing severe requirements of IEC/ IEEE 62271-37-013.
continuously endeavored to improve its quality systems and is IEC 62271-102:2018, including:
damages and possibly lengthy plant downtime.
awarded by Bureau Veritas for management system with the • Power frequency withstand voltage tests on major insulation
certificate for ISO 9001:2015, ISO 14001:2015 and components and insulation of enclosures (HV tests)
ISO 45001:2018. • Electrical resistance of current path across circuit-breaker
and the disconnecting switch
• Mechanical timing test on generator circuit-breaker
Tests • Mechanical test on other components
• Tests on auxiliary and control circuits
Type tests
• Tightness test
The generator circuit-breaker type HECPS has been designed
• Design and visual checks
to meet the requirements of IEC/ IEEE 62271-37-013 and in
some respects, its performance even exceeds the minimum
requirements of this standard. The interrupting capability of the
HECPS generator circuit-breaker system was fully type tested
01 HECPS Generator circuit-breaker power plant structure
by the High-Power Laboratory of KEMA/ Netherlands in
accordance to the standard IEEE C37.013.
6 | H E C P S G E N E R AT O R C I R C U I T- B R E A K E R U N I Q U E S O LU T I O N F O R P U M P E D S TO R AG E P O W E R P L A N T S H E C P S G E N E R AT O R C I R C U I T- B R E A K E R U N I Q U E S O LU T I O N F O R P U M P E D S TO R AG E P O W E R P L A N T S | 7
General
factory where we will complete all the to earth and across circuit-breakers/ switch contacts kV peak 125 (150) 125 (150) 125 (150)
test procedures and issue the relevant across isolating distance of disconnector kV peak 145 (165) 145 (165) 145 (165)
SIMPLIFIED AND EFFICIENT test protocols. If customers are not able Circuit-breaker
LIFETIME MANAGEMENT to join us in the factory, through our
Remote Factory Acceptance Test (RFAT) Rated peak withstand current kA peak 300 360 360
HECPS is fully integrated with Hitachi they can witness the testing of their GCB Rated short-time withstand current kA, 3s 100 130 130
Energy GCB digital monitoring system in our factory without actually leaving Rated short-circuit making current kA peak 300 360 360
GMS600, the state-of-the-art monitoring their office living a real-time customer Rated short-circuit breaking current kA rms 100 130 130
system that enables simplified and effi- event experience. Rated operating sequence CO-30min-CO
cient lifetime management in order to Opening time ms 34 ± 5 34 ± 5 34 ± 5
optimize the use of the GCB in power
Rated interrupting time ms 68 68 68
plants. GMS600-A offers the possibility
Mechanical endurance life CO 20000 20000 20000
to perform a direct contact erosion mea-
surement with high accuracy without Disconnector
taking the GCB out of service, thus
Rated peak withstand current kA peak 300 360 360
increasing the availability of the OUTSTANDING RELIABILITY
Rated short-time current kA, 3s 100 130 130
power plant.
Operating time s 2 2 2
Based on the modern, robust and
streamlined design of the HECS-platform Earthing switch
with more than 2000 installed breakers
Rated peak withstand current kA peak 300 360 360
worldwide, HECPS is built around well
proven components that ensure its Rated short-time current kA, 1s 100 130 130
Circuit-breaker module
Generator circuit-breaker
system and modules The generator circuit-breaker module is the one containing
the SF6 circuit-breaker. It consists of a three-phase system
in single-phase enclosures, supplied fully assembled on a
common frame with operating mechanisms and capacitors.
8 8 83 Earthing 8switches
8 8 8 8 1
1 7 7 7 2 7
7 7 7 2 7
4 Starting switch for SFC connection
3 3 6 9 6 3 6 3 Surge3 capacitor 6 9
6 3
7 Current transformers
2 7
2 7 04 Typical single line diagram of HECPS generator circuit-breaker module
8 Voltage transformers
The single line diagram of the five phase disconnector Arrangement of the braking switch module
05 Disconnector in open position and phase reversal module is depicted in the figure 06. The braking switch module is connected to the generator main 07 Braking switch module
Monitoring system
The overlapping time is typically measured using the dynamic The presented innovative solution offers the possibility to per-
contact resistance measurement (DRM) technique, which evalu- form a direct contact erosion measurement with high accuracy
ates the contact resistance during an operation of the GCB. The and does not need the GCB to be taken out of service, thus in-
measument consists in injecting a DC current in one phase of creasing the availability of the power plant. This enables new
the GCB and requires the GCB to be taken out of service and service concepts to be implemented, promoting the transition
isolated from the rest of the power plant. from the traditional reactive maintenance work to an optimized
maintenance planning based on residual lifetime prediction and
The innovative method to measure the contact overlapping time supported by faster response, higher flexibility and simplified in-
is based on a concept which transmits high-frequency signals spections and overhauls.
across the GCB (see figure 09(b)). A test signal is generated by
The GMS600 (see figure 09(a)) is a novel monitoring system for sample per second. This raw temperature data is processed by the phase module and is fed into the conductor via the capaci- The possibility to accurately measure the erosion of the GCB
GCBs that has been specifically developed to support power a temperature evaluation module every minute, and a warning tive voltage divider on the transformer side. The signal is then contacts is of special importance in applications which involve
plant operators and maintenance engineers for a proactive and or alarm is generated in case the temperature deviation of the received through a second capacitive voltage divider on the a high number of switching operations such as in pumped stor-
cost-effective maintenance program, while improving diagnostic three sensors per phase exceeds the set limit or the tempera- generator side. The amplitude of the received test signal varies age power plants. The use of a monitoring system to support
capability through the recorded data and threshold levels. ture reaches the maximum tolerated level. All information is depending on the position of the GCB, i.e., closed, main the maximization of the usage of equipment plays a key role in
displayed to the GCB operator locally by local human machine contacts open, or arcing contacts open. Evaluation of this optimizing system performance and reducing operating costs.
Built on the well-proven technology, it offers unique features interface as well as remotely by webserver and web client appli- amplitude variation allows to calculate the overlapping time of
such as SF6 gas monitoring and trending (GMS600-G), cation. Data can be transmitted over the power plant network the two contact systems.
temperature monitoring of primary conductors (GMS600-T) by the modern communication protocols IEC 61850 and
and ablation monitoring (GMS600-A). In addition, it is also able DNP3.
to provide operating mechanism supervision. GMS600 can be
integrated in new GCBs or retrofitted into existing GCB A recent advance in monitoring system led to the launch of the
applications. global first online contacts erosion monitoring system for GCBs.
AMPLITUDE (a.u.)
1 2
Predominantly during opening operations, some material is ab-
The monitoring system provides precise indication of the GCB’s lated from the GCB arcing contact system resulting in reduced 3 4 5
remaining time-to- preventive maintenance based on cumulative overlapping times, i.e. the time elapsed between the opening of
current interruptions, total number of mechanical operations the main and the arcing contacts during switching operations.
and time from last overhaul. The wear on arcing contacts of GCBs can be better monitored 6
2 Power supply and communication interface 6 Time at which the main contact system is closed
Analog signals
3 Receiving capacitive voltage divider 7 Time at which the arching contact system is closed
MODBUS
(RS-485)
09(b) GMS600 concept diagram and test signal of closing operation
IEC 61850
SF6
Temperature
LAN Drive/ position
signals
Our footprint
Pumped storage power plant references
Hitachi Energy is
market leader in
pumped storage
applications.
18 | H E C P S G E N E R AT O R C I R C U I T- B R E A K E R U N I Q U E S O LU T I O N F O R P U M P E D S TO R AG E P O W E R P L A N T S H E C P S G E N E R AT O R C I R C U I T- B R E A K E R U N I Q U E S O LU T I O N F O R P U M P E D S TO R AG E P O W E R P L A N T S | 19