Professional Documents
Culture Documents
2017
Foreword
This report has been prepared by the Nearly Zero-Energy Buildings Research Group of the
Institute of Civil Engineering and Architecture of Tallinn University of Technology within the
framework of the project ‘Study on the cost-effective minimum energy efficiency
requirements for buildings’.
The work was ordered and financed by the Ministry of Economic Affairs and
Communications and the KredEx Fund.
Reference:
Arumägi, E., Simson, R., Kuusk, K., Kalamees, T., Kurnitski, J. (2017). Analysis of cost-
optimal minimum energy efficiency requirements for buildings. Tallinn University of
Technology.
Non-exclusive licence for the use of personal copyrights: KredEx Fund, Ministry of
Economic Affairs and Communications
Summary
In the scope of this study, calculations of cost-optimal energy efficiency levels for new and
significantly renovated buildings were performed. According to the Directive on the Energy
Performance of Buildings, cost-optimal calculations are to be performed every five years,
and the first time these calculations were due to be performed was in 2012 (the
calculations for Estonia were completed in 2011). Cost-optimal is the level of energy
efficiency at which the total cost of the life cycle is minimised, taking into account the costs
of construction, energy and maintenance. According to the methodology, a calculation of
the life cycle is performed using the net present value method for a period of 30 years for
residential buildings and for a period of 20 years for non-residential buildings. Cost-
optimisation calculations are performed as the investor’s financial calculation and a
macroeconomic calculation. The financial calculation takes into account appreciation of all
taxes, money and energy costs. The macroeconomic calculation is performed without the
value added tax but including the cost of CO2 emissions. Calculations are performed at
various interest rates to assess sensitivity.
Macroeconomic calculations were performed in Estonia for the first time, and their results in
most cases overlapped with the results of financial calculations. Only in the case of the
smaller residential buildings did the macroeconomic calculations demonstrate a somewhat
lower cost-optimal energy performance indicator. There was no difference with regard to
other buildings. The results of the financial calculations for new buildings are summarised
in the following table. Compared to 2011, cost-optimal energy performance indicators have
improved significantly, reaching either very close to nearly zero-energy level or even
surpassing it (energy performance class A). According to the results, the nearly zero-
energy requirement for terraced and office buildings has become cost-optimal, while that
for the apartment blocks is only one unit away. The cost-optimal value of 200 m² small
residential buildings remained furthest away (7 units) from the level of the near-zero energy
building. In the case of the 100 m² small residential buildings, it is essential to consider that
the nearly zero-energy requirement of 100 kWh/(m²·a) applies to all small residential
buildings of up to 120 m². This is why the cost-optimal energy efficiency margin is justified,
because achieving energy efficiency in smaller buildings is more expensive.
Cost-optimal energy performance indicators and additional costs for new buildings. The
cost-optimal energy performance indicators and nearly zero-energy requirements for 2011
are included for comparison.
Based on the results for major renovations of small residential buildings, apartment
buildings and office buildings, the cost-optimal energy efficiency level has improved by one
energy performance class. Therefore, the minimum energy efficiency requirement for major
renovations should be reduced by one class to class C.
Given the significant difference between the current minimum requirements for new
buildings (class C) and the cost-optimal energy efficiency levels (approximately class A),
implementation of the cost-optimal requirements in two stages is justified. With a
preparatory period of one year, it is possible to make a transition to class B by 31
December 2018 and to class A by 31 December 2019. It is possible to make a transition to
class C in the case of major renovations by 31 December 2018 with a one-year preparatory
period as well.
Table of contents
Summary ................................................................................. 3
1 Introduction ..................................................................................................................... 7
1.1 Objective .................................................................................................................. 7
1.2 Description of the study ............................................................................................ 7
2 Methodology used for the analysis ................................................................................... 8
2.1 Energy calculations ................................................................................................... 8
2.2 Cost-effectiveness calculations .................................................................................. 8
2.2.1 Costs of structural solutions and openings ..................................................................... 11
3 Cost-effectiveness of new buildings ................................................................................ 15
3.1 Small residential buildings....................................................................................... 15
3.1.1 Detached residential building (100 m²) .................................................................... 15
3.1.2 Results of cost-effectiveness calculations ................................................................ 17
3.1.3 Detached residential building (200 m²) .................................................................... 20
3.1.4 Results of cost-effectiveness calculations ................................................................ 23
3.1.5 Terraced building ...................................................................................................... 26
3.1.6 Results of cost-effectiveness calculations ................................................................ 28
3.2 Apartment buildings ............................................................................................... 31
3.2.1 Description of the building ....................................................................................... 31
3.2.2 Results of cost-effectiveness calculations ................................................................ 33
3.3 Office buildings ....................................................................................................... 36
3.3.1 Description of the analysed building ........................................................................ 36
3.3.2 Description of the analysed measures ............................................................................ 39
3.3.3 Results of cost-effectiveness calculations ................................................................ 41
4 Cost-effectiveness of renovated buildings ....................................................................... 45
4.1 Small residential buildings....................................................................................... 45
4.1.1 Description of the buildings...................................................................................... 45
4.1.2 Description of renovation measures ........................................................................ 45
4.1.3 Results of cost-effectiveness calculations ................................................................ 47
4.2 Apartment buildings ............................................................................................... 48
4.2.1 Description of the buildings...................................................................................... 48
4.2.2 Description of renovation measures ........................................................................ 71
4.2.3 Results of cost-effectiveness calculations ....................................................................... 71
4.3 Office buildings ....................................................................................................... 73
4.3.1 Description of the buildings...................................................................................... 73
4.3.2 Description of renovation measures ........................................................................ 74
4.3.3 Results of cost-effectiveness calculations ....................................................................... 75
References ............................................................................ 76
Annexes ................................................................................. 77
Annex 1. Simulation results for a small residential building (100 m²). .................................... 77
Annex 2. Simulation results for a small residential building (200 m²). .................................... 81
Annex 3. Simulation results for a terraced building. ................................................................ 88
Annex 4. Simulation results for an office building.................................................................... 92
Annex 5. Annex III to Regulation EU 244 (pursuant to EU Directive 2010/31/EU) .................. 96
1 Introduction
1.1 Objective
The aim of the study is to assess the cost-optimal minimum energy efficiency of new buildings,
taking into account the energy use of the building and the additional costs associated with
achieving the nearly zero-energy level. The energy efficiency requirements applicable at the
time of conducting the study were as follows:
The results of the cost-effectiveness calculations are presented as a ratio between the change
in the net present value of the building’s expenses and the energy performance indicator.
2 Methodology used for the analysis
The energy demand of a building was calculated according to the methodology for calculating
the energy efficiency of buildings, using dynamic energy simulation software IDA Indoor
Climate and Energy 4.7.1 (IDA-ICE) from the company EQUA Simulations AB. The software
used for calculations meets all the software requirements in the regulation on minimum energy
performance requirements. The results obtained from the dynamic simulations were used to
assess the energy savings potential of different energy efficiency measures and to calculate
the energy consumption of buildings with different structural solutions.
The unit prices required for calculating the additional cost of various structural solutions
affecting the energy use of buildings were obtained from construction companies by the
building type. The budget officers provided unit costs per square metre for various structural
solutions and openings, which also included the costs of material and installation. The costs of
solar panels were estimated. The costs of structures, openings and technical systems were
calculated by the following companies: Merko AS, Timbeco AS, YIT AS, Matek AS, HEVAC
OÜ, Energiamaja OÜ and Kliimaseade OÜ. All calculated costs included VAT.
First of all, simulation models were developed to assess the impact of individual components
of the building envelope on the energy consumption of the building. In the initial energy
simulations, only one component was changed and the result was compared to the energy
consumption of the original building. The variable of the individual modifiable components was
the thermal transmittance of the relevant component. In addition to the thermal transmittance,
the effect of the building’s air permeability was also assessed. The values of thermal
transmittance and air leakage of different structural solutions used in simulation models were
as follows:
thermal transmittance U of the external wall [W/(m²·K)]: 0.16, 0.14, 0.12, 0.10;
thermal transmittance U of the roofing deck [W/(m²·K)]: 0.12, 0.10, 0.08;
thermal transmittance U of the floor [W/(m²·K)]: 0.18, 0.14, 0.10;
thermal transmittance U of the windows [W/(m²·K)]: 1.1, 0.9, 0.7;
number of air leaks q50 [m³/h·m²]: 6.0, 3.0, 1.5, 1.0.
In addition to assessing the impact of the individual components on the building’s energy
consumption, the calculation of the energy efficiency indicator was performed for all
combinations by combining various values of thermal conductivity and air leakage of structural
solutions.
The cost-effectiveness of different structural solutions was estimated using the net present
value method:
where:
τ means the calculation period;
CG(τ) means total cost (referred to starting year τ0) over the calculation period;
Ci means initial investment costs for measure or set of measures j;
Ca,i (j) means annual cost during year i for measure or set of measures j;
Rd(i) means discount factor for year i.
The cost effectiveness of the additional costs related to structural solutions and renewable
energy solutions that were needed to meet the requirements of the nearly zero-energy building
was assessed in these calculations:
The discount was calculated using the calculated interest rate and a relative price increase
during the calculation period. Depending on the uses of the buildings, the cost-effectiveness
calculation period was chosen to be 30 years (for residential buildings) or 20 years (for non-
residential buildings). The discount was based on the real interest rate of 2.5 %, which
corresponds to the rate of return of 3.5 % when inflation is 1 %. The real escalation of energy
prices for the calculation period was taken at 1 % per annum.
The initial purchase price of energy carriers was calculated at the following prices (including
VAT):
electricity purchase 0.113 EUR/kWh;
electricity sale 0.035 EUR/kWh (re-sale price of electricity from PV panels back to the
network);
district heating 0.060 EUR/kWh;
gas 0.048 EUR/kWh;
pellet 0.045 EUR/kWh.
Financial calculations were based on the additional investment needed to achieve the nearly
zero-energy levels. When calculating the additional cost of the measure/package, the prices
payable by the customer, including all applicable taxes, VAT and support were taken into
account in the financial calculations. The calculations did not take into account the potential
support that may apply to the introduction of various technologies related to the production of
renewable energy.
The cost of building components was calculated by totalling the different expense types and by
applying a discount rate to them using the discount factor.
The criterion of profitability is that the net revenue generated and discounted during the
economic life of the investment should be greater than the initial investment.
The calculations are based on the prognosis of the long-term CO2 price variation in the
Delegated Regulation (EU) No 244/2012 of the European Commission (see Table 2).
Carbon price evolution 2020 2025 2030 2035 2040 2045 2050
Reference 16.5 20 36 50 52 51 50
(frag. action, ref. fossil f.
prices)
Effect. Techn. 25 38 60 64 78 115 190
(glob. action, low fossil f.
prices)
Effect. Techn. 25 34 51 53 64 92 147
(frag. action, ref. fossil f.
prices)
Source: Annex 7.10 in the document http://eur-
lex.europa.eu/LexUriServ/LexUriServ.do?uri=SEC:2011:0288:FIN:EN:PDF
Calculations of the amounts of CO2 emissions required for macroeconomic calculations are
based on the CO2 specific emission rates provided in the report ‘Study on the cost-effective
minimum energy efficiency requirements for buildings. Weighting factors for energy carriers’.
The CO2 specific emission factors for the main energy carriers calculated in the report ‘Study
on the cost-effective minimum energy efficiency requirements for buildings. Weighting factors
for energy carriers’ are given in Table 3.
Table 3. CO2 specific emission factors for the main energy carriers
CO specific
2
Electricity 1150
District heating 193
Efficient district heating 39
Extremely efficient district 39
heating
Gas 202
2.2.1 Costs of structural solutions and openings
The costs of the structural solutions for private residential buildings and apartment blocks
based on the bids received from builders are shown in the graphs in Figure 1 to Figure 8.
Cost, (EUR/m²)
Min. wool
PIR
Min. wool
PIR
Supplier 1
Supplier 2
Figure 1. The dependence of the structure’s estimated cost on thermal transmittance (U):
Timber frame walls.
EPS λ=0.040
EPS λ=0.040
EPS λ=0.033
EPS λ=0.033
PIR
Supplier 1
Supplier 2
Figure 2. The dependence of the structure’s estimated cost on thermal transmittance (U):
Concrete block walls with rendering.
Min. wool λ=0.040
EPS λ=0.040
Cost, (EUR/m²)
EPS λ=0.040
EPS λ=0.033
EPS λ=0.033
PIR
PIR
Supplier 1
Supplier 2
Figure 3. The dependence of the structure’s estimated cost on thermal transmittance (U):
Reinforced concrete walls.
Cost, (EUR/m²)
Cost, (EUR/m²)
Min. wool
Cellulose fibre wool
PIR
Min. wool
Cellulose fibre wool
PIR
Supplier 1
Supplier 2
Figure 4. The dependence of the structure’s estimated cost on thermal transmittance (U):
Timber frame roofs.
Min. wool
Min. wool
Cost, (EUR/m²)
EPS λ=0.040
EPS λ=0.040
EPS λ=0.033
EPS λ=0.033
PIR
PIR
Supplier 1
Supplier 2
Thermal transmittance U,
(W/m²·K)
Figure 5. The dependence of the structure’s estimated cost on thermal transmittance (U):
Reinforced concrete roofs.
EPS λ=0.040
Cost, (EUR/m²)
EPS λ=0.040
EPS λ=0.033
EPS λ=0.033
Supplier 1
Supplier 2
Thermal transmittance U,
(W/m²·K)
Figure 6. The dependence of the structure’s estimated cost on thermal transmittance (U):
Reinforced concrete floor above ambient air.
EPS λ=0.040
EPS λ=0.040
Cost, (EUR/m²)
EPS λ=0.033
PIR
PIR
Supplier 1
Supplier 2
Thermal transmittance
U, (W/m²·K)
Figure 7. The dependence of the structure’s estimated cost on thermal transmittance (U):
Reinforced concrete floor at ground level.
Cost, (EUR/m²)
Openable wood-aluminium
Unopenable wood-aluminium
Openable wooden
Unopenable wooden
Openable plastic
)
Supplier 1
Supplier 2
Figure 8. The dependence of the estimated cost of windows on thermal transmittance (U).
3 Cost-effectiveness of new buildings
The simulations and calculations for assessing the cost-effectiveness of technical
solutions are based on the selected sample buildings.
Taking into account the additional investment to improve the structures and the heat
energy savings this achieves, energy efficiency indicators which whose costs were still
cost-effective were identified. The results of the financial calculations are shown in
Figures 12 to 41. Each point on the graph represents one combination of structural
solutions and the energy efficiency thus achieved. All points below the baseline relate to
combinations that are cost-effective. The points above the baseline relate to combinations
for which the original investment to improve energy efficiency exceeds the amount of
energy savings.
Parameter Value
Heated area (m²) 101
Base area of the building (m²) 167
Floors above the ground 1
Floors below the ground -
Height (m) 6.7
Length (m) 14.2
Width (m) 9.6
Closed net area (m²) 101.1
Capacity (m³) 400
Common area (m²)
Dwelling area (m²) 79.1
Total dwelling rooms 4
3.1.2 Results of cost-effectiveness calculations
Figures 11 to 13 reflect the results of cost-effectiveness calculations for a residential
building with different combinations of structural solutions and heat sources and real
interest rates of 2.0 %, 2.5 % and 3.0 %.
EPI, kWh/(m² a)
Figure 11. Energy performance indicator (EPI) of a detached residential building (100 m²)
and change in the net present value (NPV) for different combinations of structural
solutions and heat sources. Real interest rate 2.0 %.
ΔNPV, EUR/m²
EPI, kWh/(m² a)
Figure 12. Energy performance indicator (EPI) of a detached residential building (100 m²)
and change in the net present value (NPV) for different combinations of structural
solutions and heat sources. Real interest rate 2.5 %.
ΔNPV, EUR/m²
EPI, kWh/(m² a)
Based on the definition of a nearly zero-energy building given in the Directive on Energy
Performance of Buildings, local production of renewable energy is required to reach the
nearly zero-energy level. Local generation of renewable energy is added below to the
architecturally and technically appropriate combinations. Electricity generation with solar
panels was considered as a solution for local production of renewable energy.
In the case of a smaller residential building, the cost-optimal range of energy performance
indicators without local production of renewable energy is between 123 and 131
kWh/(m²a), and the additional investment is in the range between 7.4 and 16.9 EUR/m².
EPI, kWh/(m² a)
Figure 14. Energy performance indicator (EPI) of a detached residential building (100 m²)
and change in the net present value (NPV) for different combinations of structural
solutions and heat sources with local renewable energy production (PV panels with a
nominal power of 2.8 kW). Real interest rate 2.0 %.
ΔNPV, EUR/m²
EPI, kWh/(m² a)
Figure 15. Energy performance indicator (EPI) of a detached residential building (100 m²)
and change in the net present value (NPV) for different combinations of structural
solutions and heat sources with local renewable energy production (PV panels with a
nominal power of 2.8 kW). Real interest rate 2.5 %.
ΔNPV, EUR/m²
EPI, kWh/(m² a)
Figure 16. Energy performance indicator (EPI) of a detached residential building (100 m²)
and change in the net present value (NPV) for different combinations of structural
solutions and heat sources with local renewable energy production (PV panels with a
nominal power of 2.8 kW). Real interest rate 3.0 %.
According to the current requirements, the limit value of the nearly zero-energy level for a
residential building is the EPI of 50 kWh/(m²a). The results of the calculations show that
the cost-optimal levels of energy performance indicators for selected buildings exceed the
current nearly zero-energy limit value.
With local renewable energy production, the cost-optimal range of energy performance
indicators for a detached residential building (100 m²) is from 77 to 83 kWh/(m²a), and the
additional investment is between 51.0 and 58.3 EUR/m².
The calculation results of the macroeconomic total expenditure are presented in Figure 17.
ΔNPV, EUR/m²
EPI, kWh/(m² a)
At the macroeconomic level, the cost-optimal range of energy performance indicators for
a detached residential building (100 m²) with a geothermal pump and generation of local
renewable energy is 60 to 70 kWh(m² a); in the case of a gas boiler, the figure is between
115 and 119 kWh(m² a).
Figure 19. Second floor plan of a detached residential building (200 m²).
Figure 20. Views of a detached residential building (200 m²)
Parameter Value
Heated area (m²) 206
Base area of the building (m²) 179
Floors above the ground 2
Floors below the ground -
Height (m) 7
Length (m) 19.9
Width (m) 12.8
Closed net area (m²) 190.3
Capacity (m³) 1252
Common area (m²)
Dwelling area (m²) 160.8
Total dwelling rooms 4
3.1.4 Results of cost-effectiveness calculations
Calculations for a larger residential building were performed in a similar way to the
calculations for a small residential building. Figures 21 to 23 reflect the results of cost-
effectiveness calculations for residential buildings in different combinations of structural
solutions and heat sources at the real interest rates of 2.0 %, 2.5 % and 3.0 %.
EPI, kWh/(m² a)
Figure 21. Energy performance indicator (EPI) of a detached residential building (200 m²) and
change in the net present value (∆NPV) for different combinations of structural solutions and
heat sources. Real interest rate 2.0 %.
ΔNPV, EUR/m²
EPI, kWh/(m² a)
Figure 22. Energy performance indicator (EPI) of a detached residential building (200 m²) and
change in the net present value (NPV) for different combinations of structural solutions and
heat sources. Real interest rate 2.5 %.
ΔNPV, EUR/m²
EPI, kWh/(m² a)
Figure 23. Energy performance indicator (EPI) of a detached residential building (200 m²) and
change in the net present value (NPV) for different combinations of structural solutions and
heat sources. Real interest rate 3.0 %.
In the case of a detached residential building (200 m²), the cost-optimal range of energy
performance indicators without local production of renewable energy is between 137 and 141
kWh/(m²a), and the additional investment is in the range between 13.6 and 17.1 EUR/m².
EPI, kWh/(m² a)
Figure 24. Energy performance indicator (EPI) of a detached residential building (200 m²) and
change in the net present value (NPV) for different combinations of structural solutions and
heat sources with local renewable energy production (PV panels with a nominal power of 4.0
kW). Real interest rate 2.0 %.
ΔNPV, EUR/m²
EPI, kWh/(m² a)
Figure 25. Energy performance indicator (EPI) of a detached residential building (200 m²) and
change in the net present value (NPV) for different combinations of structural solutions and
heat sources with local renewable energy production (PV panels with a nominal power of 4.0
kW). Real interest rate 2.5 %.
ΔNPV, EUR/m²
EPI, kWh/(m² a)
Figure 26. Energy performance indicator (EPI) of a detached residential building (200 m²)
and change in the net present value (NPV) for different combinations of structural
solutions and heat sources with local renewable energy production (PV panels with a
nominal power of 4.0 kW). Real interest rate 3.0 %.
With local renewable energy production, the cost-optimal range of energy performance
indicators for a detached residential building (200 m²) is from 87 to 91 kWh/(m²a), and the
additional investment is between 63.2 and 66.7 EUR/m².
ΔNPV, EUR/m²
EPI, kWh/(m² a)
Figure 27. Results of cost-effectiveness calculations for a detached residential building (200
m²) at the macroeconomic level. Real interest rate 2.5 %.
At the macroeconomic level, the cost-optimal range of energy performance indicators for a
detached residential building (200 m²) with a geothermal pump and generation of local
renewable energy is 55 to 65 kWh(m² a), with an air-water heat pump and generation of local
renewable energy it is 85 to 90 kWh(m² a); in the case of a gas boiler and generation of local
renewable energy, the figure is between 115 and 119 kWh(m² a).
The selected building has two floors. The building is divided into six sections with separate
entrances. It has a rectangular base plan with some protruding parts on the façade. External
walls of the building are made of wall elements on a wooden frame, and these are covered
with plasterboard on the inside. Partition walls between the sections of the building are made
of wall elements on a wooden frame, with the internal walls made of plasterboard on a metal
frame. The details of the building are given in Table 6, with the plans shown in Figure 28 and
the views in Figure 29.
Parameter Value
Building footprint (m²) 643.4
Floors above the ground 2
Floors below the ground -
Height (m) 6.6
Length (m) 53.2
Width (m) 22.9
Net enclosed area (m²) 676.8
Heated area (m²) 565.8
Capacity (m³) 2180
Common area (m²) 16
Dwelling area (m²) 676.8
Total dwelling rooms 6
Figure 28. Plans of the first and second floors of the terraced building.
The results of cost-effectiveness calculations for the terraced building are provided in
Figures 30 to 35.
Air-water SP
Ground source heat pump
ΔNPV, EUR/m²
Gas boiler
EPI, kWh/(m² a)
Figure 30. Energy performance indicator (EPI) of a terraced building and change in the net
present value (NPV) for different combinations of structural solutions and heat sources. Real
interest rate 2.0 %.
ΔNPV, EUR/m²
EPI, kWh/(m² a)
Figure 31. Energy performance indicator (EPI) of a terraced building and change in the net
present value (NPV) for different combinations of structural solutions and heat sources. Real
interest rate 2.5 %.
ΔNPV, EUR/m²
EPI, kWh/(m² a)
Figure 32. Energy performance indicator (EPI) of a terraced building and change in the net
present value (NPV) for different combinations of structural solutions and heat sources.
Real interest rate 3.0 %.
In the case of a terraced building, the cost-optimal range of energy performance indicators
without local production of renewable energy is between 84 and 86 kWh/(m²a), and the
additional investment is in the range between 22.7 and 31.4 EUR/m².
EPI, kWh/(m² a)
Figure 33. Energy performance indicator (EPI) of a terraced building and change in the net
present value (NPV) for different combinations of structural solutions and heat sources with
local renewable energy production (PV panels with a nominal power of 4.5 kW). Real interest
rate 2.0 %.
ΔNPV, EUR/m²
EPI, kWh/(m² a)
Figure 34. Energy performance indicator (EPI) of a terraced building and change in the net
present value (NPV) for different combinations of structural solutions and heat sources with
local renewable energy production (PV panels with a nominal power of 4.5 kW). Real interest
rate 2.5 %.
ΔNPV, EUR/m²
EPI, kWh/(m² a)
Figure 35. Energy performance indicator (EPI) of a terraced building and change in the net
present value (NPV) for different combinations of structural solutions and heat sources
with local renewable energy production (PV panels with a nominal power of 4.5 kW). Real
interest rate 3.0 %.
With local renewable energy production, the cost-optimal range of energy performance
indicators for a terraced building is from 71 to 73 kWh/(m²a), and the additional investment is
between 35.9 and 44.6 EUR/m².
3.2 Apartment buildings
Parameter Value
Heated area (m²) 6373
Base area of the building (m²) 1618
Floors above the ground 5
Floors below the ground 1
Height (m) 17.8
Length (m) 54.3
Width (m) 35.7
Closed net area (m²) 6373
Capacity (m³) 25900
Common area (m²) 2009.2
Dwelling area (m²) 3713.8
Total dwelling rooms 51
EPI, kWh/(m² a)
Figure 38. Energy performance indicator (EPI) of an apartment block and change in the net
present value (NPV) for different combinations of structural solutions. Real interest rate
2.0 %.
ΔNPV, EUR/m²
EPI, kWh/(m² a)
Figure 39. Energy performance indicator (EPI) of an apartment block and change in the net
present value (NPV) for different combinations of structural solutions. Real interest rate
2.5 %.
ΔNPV, EUR/m²
EPI, kWh/(m² a)
Figure 40. Energy performance indicator (EPI) of an apartment block and change in the net
present value (NPV) for different combinations of structural solutions. Real interest rate
3.0 %.
Without local renewable energy production, the cost-optimal range of energy performance
indicators for an apartment block is approximately from 115 to 117 kWh/(m²a), and the
additional investment is between 6.2 and 9.6 EUR/m².
ΔNPV, EUR/m²
EPI, kWh/(m² a)
Figure 41. Energy performance indicator (EPI) of an apartment block and change in the net
present value (NPV) for different combinations of structural solutions with local renewable
energy production (PV panels with a nominal power of 53 kW). Real interest rate 2.0 %.
ΔNPV, EUR/m²
EPI, kWh/(m² a)
Figure 42. Energy performance indicator (EPI) of an apartment block and change in the net
present value (NPV) for different combinations of structural solutions with local renewable
energy production (PV panels with a nominal power of 53 kW). Real interest rate 2.5 %.
ΔNPV, EUR/m²
EPI, kWh/(m² a)
Figure 43. Energy performance indicator (EPI) of an apartment block and change in the net
present value (NPV) for different combinations of structural solutions with local renewable
energy production (PV panels with a nominal power of 53 kW). Real interest rate 3.0 %.
According to the current requirements, the limit value of the nearly zero-energy level for a
section of an apartment block is an EPI of 100 kWh/(m²a). The results of the calculations
show that the cost-optimal levels of energy performance indicators exceed the current nearly
zero-energy limit value.
With local renewable energy production, the cost-optimal range of energy performance
indicators for an apartment block is from 101 to 103 kWh/(m²a), and the additional investment
is between 22.9 and 26.3 EUR/m².
The calculation results of the macroeconomic total expenditure for an apartment block are
presented in Figure 44.
ΔNPV, EUR/m²
EPI, kWh/(m² a)
Figure 46. Standard floor plans of an office building with zones. These plans were used to
compile a simulation model of energy calculations. First floor plan (top left); plan of the floors
2 to 5 (top right); sixth floor plan (bottom).
The general details of the building are given in Table 8, with the details of structures shown in
Table 9. The 3D simulation model of the building is shown in Figure 47.
Parameter Value
Heated area of the building, Aheated, 4191.2
m²
Gross floor area of the building, 5820.0
Agross, m²
Number of floors, - 6
Proportion of windows in the façade, 55.1
%
Ratio of the building envelope to the
heated area 1.23
Aenv/Aheated, -
Specific heat loss, ∑H/Aheated, 0.49
W/(K·m²)
Source of heat supply for
heating and for warming up of district heating
domestic water and ventilation
air
Heating elements steel panel radiators
Cold source compressor-cold machine
Room equipment for cooling active cooling pads
Ventilation systems mechanical SP-VT in
office rooms and the
parking area; VT system
in toilets
Ventilation heat recovery rotor heat exchanger
Figure 47. South view (left) and north view (right) of the building’s simulation model.
3.3.2 Description of the analysed measures
The analysis of an office building was focused on the façade design of the building, efficient
technical systems and local renewable energy options. The volumetric solution in the project
design for the studied building and its energy supply mode formed the basis of the analysis.
The following parameters were examined with regard to the façade design:
the insulation thickness of the external wall and roofing deck;
window transparency, size and number of insulated glass units;
static and dynamic solar shielding. The following parameters were analysed for the
technical systems;
heat exchanger temperature ratio (ηT) and specific power (SFP) of ventilation units;
power of the building’s cooling system (kW) depending on the façade solutions;
specific power (W/m²) and control of the lighting system.
The thickness of the insulating material for the external wall was changed by 30 mm
increments and the roofing deck was changed by 50 mm increments. Unit pricing for the
boundary structures was calculated based on the data in Table 10, taking into account the
cost of materials and installation.
Table 10. Insulation thickness, thermal conductivity and cost of the boundary structures.
In addition to the triple sun protection glazing in the project design, windows with clear
glazing, both triple and quadruple, were also analysed. The thermal conductivity of the
aluminium window frame was 1.0 W/(m²·K) for each solution. Table 11 describes all window
options and their costs.
The building is designed with a rotor heat recovery ventilation unit that has the specific power
(SFP) of 1.82 kW/(m3/s) and the heat recovery temperature ratio ηT of 73.9 %. In order to
reduce the energy use of ventilation, an alternative solution was analysed that uses ventilation
units 1-2 times larger than conventional units [SFP = 1.57 kW/(m3/s); heat recovery
temperature ratio ηT = 76.1 %].
For the production of local renewable electricity, the installation of PV panels was analysed on
the roofs of buildings that have approximately 620 m² of spare roof space. The technical data
and cost of the selected PV panel are given in Table 13, while its output was simulated in the
IDA-ICE calculation programme. The maximum surface area of PV panels is 328.1 m² (205
pcs). Three systems of different sizes were studied:
1) PV panels with an area of 70.4 m² (44 pcs) and a total output of 11 kW (micro producer)
2) PV panels with an area of 211.2 m² (132 pcs) and a total output of 33 kW (small
producer)
3) PV panels with an area of 328.1 m² (205 pcs) and a total output of 51.25 kW (small
producer)
The pricing of a PV panel includes the cost of an inverter (approximately 15 % of the final
price), installation and material costs (30 %).
Table 13. Technical data, optimal installation and cost of the PV panel.
Parameter Value
Nominal power, W 250
Efficiency factor, % 15.9
Surface area of the PV panel, m² 1.60
Width of the PV panel, m 0.986
Angle of inclination, ° 45
Angle to the south direction, ° 24
Simulated productivity per PV panel, kWh/a 261
Cost of the PV panel (without VAT), EUR 149.50
System cost (without VAT), EUR/W 1.14*
System cost (without VAT), EUR/W 1.20**
System cost (without VAT), EUR/W 1.22***
* - system’s total power under 11 kW (44 pcs);
** - system’s total power under 33 kW (132 pcs);
*** - system’s total power over 33 kW.
Figure 49 shows the results of a cost-effectiveness analysis that illustrate the energy
performance indicators of the analysed options, the change in net present value and the
amount of additional investment in comparison to the original solution.
nZEB with dynamic sun shading Minimum
requirement
nZEB
Low-energy building I
EUR/m²
ΔNPV,
Low-energy building II
Figure 49. Energy performance indicator of the studied options, change in the net present
value and additional investment in relation to the original solution for an office building.
Achieving the level of 112.6 kWh/(m²∙a) of a low-energy building only requires an additional
investment of 0.1 %.
The additional investment required to achieve the energy efficiency level of a nearly zero-
energy building is 1.6 % of the cost of the original solution (22.9 EUR/m²). The ΔNPV for this
option is approximately -40 EUR/m² (savings) compared to the reference solution, therefore
the achieved level of the nearly zero-energy building can be called the cost-optimal level, and
the cost-optimal energy consumption range is between 90 and 95 kWh/(m²∙a). Figures 50 to
53 provide cost-effectiveness calculations for all analysed options at the real interest rates of
2.0 %, 2.5 % and 3.0 %.
Dynamic shading
ΔNPV, EUR/m²
EUR/m²
EUR/m²
ΔNPV,
ΔNPV,
EPI, kWh/(m² a)
Figure 50. Results of cost-effectiveness calculations for an office building. Real interest rate
2.0 %.
ΔNPV, EUR/m²
EPI, kWh/(m² a)
Figure 51. Results of cost-effectiveness calculations for an office building. Real interest rate
2.5 %.
ΔNPV, EUR/m²
EPI, kWh/(m² a)
Figure 52. Results of cost-effectiveness calculations for an office building. Real interest rate
3.0 %.
ΔNPV, EUR/m²
EPI, kWh/(m² a)
a newer, small residential building that only requires renovation of the technical building
systems;
an older, small residential building that also requires renovation of the building
envelope.
Newer building (renovation of the technical building Older building (renovation of the structures and
systems only) technical building systems)
The note ‘50/100’ for the insulation layer thickness of the external wall and roofing deck refers
to a situation where 50 mm of additional insulation has been used for a newer sample building
and 100 mm of additional insulation has been used for an older building in order to equalise
the thermal transmittance of the structures in post-renovation conditions.
When evaluating the cost of the measures, the cost estimates provided by general contracting
companies in the field of construction were used, which were compared with the unit prices
based on EKE Nora unit prices.
EPI, kWh/(m² a)
Figure 54. Results of cost-effectiveness calculations for a newer small residential sample
building.
ΔNPV, EUR/m²
EPI, kWh/(m² a)
Figure 55. Results of cost-effectiveness calculations for an older small residential sample
building.
The cost-optimal range for the reconstruction of a newer building only requiring the renovation
of technical systems is the energy performance indicator between 240 and 260 kWh/(m²a).
The cost-optimal range for the reconstruction of an older building also requiring the renovation
of the building envelope is the energy performance indicator between 250 and
260 kWh/(m²a). Reconstruction of technical systems only is not a case of major renovation,
therefore the minimum energy efficiency requirement for a major renovation should be set on
the basis of the buildings that require renovation of the building envelope. The current
minimum energy efficiency requirement for a major renovation of small residential buildings is
210 kWh/(m²a). When laying down the new requirements, the energy efficiency requirement
for a major renovation should be increased by one energy performance class, that is, the
energy efficiency requirement for a major renovation could be equal to the minimum energy
efficiency requirement of 160 kWh/(m²a) that applies to the new small residential buildings.
This is because the cost-effective range for the reconstruction of small residential buildings is
quite large and the changes in the total cost are relatively small up to the energy performance
value of 150 kWh/(m²a).
Proportion
million m²
Large block
Other
Reinforced concrete – large panel
Brick
Wood
Details of the technical characteristics of the existing situation with the sample buildings are
given in Table 16 and in Figure 57.
Smaller Larger
Bearing structure Brick Reinforced concrete
Number of floors 4 5
Net floor area, m² 1383 3519
Heated area, m² 1154 2968
Number of apartments
Thermal conductivity of the 32 60
Building envelope, W/(m²·K)
External wall 1.0 0.9
Roof 1.1 0.8
Windows 2.0 2.0
Surface area of the building
envelope, m²
External wall 760 1410
Roof 320 610
Windows 260 520
Figure 57. Photos illustrating the sample apartment blocks.
The calculations for the costs of measures were based on the budgets for reconstruction work of
the apartment buildings that have applied for a renovation grant from the government. The costs of
measures only include the energy saving works. The cost of electricity, water, sewerage and other
works is not included and would increase the cost of the package by approximately 20 %.
EPI, kWh/(m² a)
Figure 58. Results of cost-effectiveness calculations for a smaller sample apartment block.
ΔNPV, EUR/m²
EPI, kWh/(m² a)
Figure 59. Results of cost-effectiveness calculations for a larger sample apartment block.
For a smaller apartment block, the cost-optimal energy consumption range is between 130 and
160 kWh/(m²a). For a larger apartment block, it is between 110 and 130 kWh/(m²a). Taking into
account the largely varying sizes and technical conditions of the existing apartment blocks, the cost-
optimal energy efficiency requirement for a major renovation would be equal to the 150 kWh/(m²a)
minimum energy efficiency requirement for new apartment buildings.
The results of the macroeconomic total cost calculations are shown in Figures 60 and 61.
ΔNPV, EUR/m²
EPI, kWh/(m² a)
Figure 60. Results of macroeconomic cost-effectiveness calculations for a smaller apartment block.
ΔNPV, EUR/m²
EPI, kWh/(m² a)
Figure 61. Results of macroeconomic cost-effectiveness calculations for a larger apartment block.
The macroeconomic cost-optimal calculations also support the equalisation of the energy efficiency
requirement for a major renovation with the current minimum energy efficiency requirement of
150 kWh/(m²a) for new apartment blocks.
All calculations were performed on both building samples. The final results were the weighted
average values of the two buildings’ surface areas.
The building envelopes and air circulation of the existing buildings were characterised by the
following main indicators:
Thermal transmittance of U ≈ 1.1
external walls W/(m²·K)
Thermal transmittance of U ≈ 1.0
roofs W/(m²·K)
Thermal transmittance of U ≈ 1.8
windows W/(m²·K)
EPI, kWh/(m² a)
The cost-optimal energy efficiency requirement for a major renovation is 160 kWh/(m²a) and is
equal to the minimum requirements for energy efficiency of new office buildings.
References
Directive 2010/31/EU of the European Parliament and the Council of 19 May 2010 on the energy
performance of buildings (EPBD).
Regulation No 55 of the Minister for Economic Affairs and Infrastructure of 3 June 2015 on minimum
energy performance requirements for buildings.
Regulation No 58 of the Minister for Economic Affairs and Infrastructure of 5 June 2015 on the
methods for calculating the energy performance of buildings.
Annexes
ANNEX
III
Reporting template that Member States may use for reporting to the Commission
pursuant to Article 5(2) of Directive 2010/31/EU and Article 6 of this Regulation
1. REFERENCE BUILDINGS
The building types used as the basis for the analysis of building stock energy efficiency
improvement in ‘ENMAK: Estonia’s long-term energy management development plan 2030+’
were used as reference buildings for existing buildings.
When selecting the reference buildings, the existing building stock was taken into account, and
the most common types of buildings were used in simulation calculations.
In these simulation calculations, the following variables were set at different levels:
This report sets out in detail the source data and results of energy simulations and cost-optimal
calculations for small residential buildings, apartment blocks and offices. A more detailed
description of the cost-effectiveness calculations is provided in Annex 1 ‘Cost optimal and
nZEB energy performance levels for buildings’.
Table 1. Reference building for existing buildings (major renovation)
For existing Building Ratio of Floor area, Descriptio Description Average Component
buildings geometry1 window m², as used n of the of the energy level
area over in the building2 average performanc requirement
the building Building building e kWh/m² a s (typical
envelope Code technology3 (prior to value)
and investment)
windows
with no
solar access
1. Single family buildings and subcategories Component
Older small External level
External wall: Windows: Heated Bearing 520 requirements
residential wall:
142 m² 22 m² area: structure – have not been
buildings U = 0.54
(14 % of 165 m² wood
W/(m²K) defined. The
Attic ceiling
façade Roof: regulation on
138 m²
area) U = 0.48 minimum
Floor at W/(m²K) energy
ground level: Windows: performance
138 m² U = 2.8 requirements
W/(m²K) sets out
Number of general
Heating
floors: 1 requirements
system:
for building
stove
envelopes,
heating
technical
External
Newer External wall: Windows: Heated Bearing 310 systems and
wall:
small 206 m² 50 m² area: structure – heating
U = 0.25
residential (20 % of 182 m² small block systems.
Attic ceiling W/(m²K)
buildings façade Roof:
237 m²
area) U = 0.16
Floor at W/(m²K)
ground level: Windows:
237 m² U-
1.8
Number of W/(m²K)
floors: 2
Heating
system: gas
boiler
2. Apartment blocks and multifamily buildings and subcategories
External
Smaller External wall: Windows: Heated Bearing 242
wall:
apartment 760 m² 260 m² area: structure –
U = 1.0
blocks (34 % of 1154 m² brick
W/(m²K)
Attic ceiling
façade Roof:
320 m²
area) U = 1.1
Floor at W/(m²K)
ground level: Windows:
320 m² U = 2.0
W/(m²K)
1
S/V (surface to volume), orientation, area of N/W/S/E façade.
2
Construction material, typical air tightness (qualitative), use pattern (if appropriate), age (if appropriate).
3
Technical building systems, thermal transmittance of building elements, windows – area, thermal transmittance (U-
value), shading, passive systems, etc.
Number of
Heating
floors: 4
system:
district
heating
External
Larger External wall: Windows: Heated bearing 202
wall:
apartment 1410 m² 520 m² area: structure –
U = 0.9
blocks (37 % of 2968 m² assembled
Attic ceiling W/(m²K)
façade reinforced
610 m² Roof:
area) concrete
U = 0.8
Floor at W/(m²K)
ground level: Windows:
610 m² U = 2.0
W/(m²K)
Number of Heating
floors: 5 system:
district
heating
External wall:
3. Office 310
U = 1.1
buildings
W/(m²K)
and Roof:
subcategori U = 1.0
es W/(m²K)
Windows:
U = 1.8
W/(m²K)
Heating
system:
district
heating
5. Other
non-
residential
building
categories
terraced buildings;
apartment buildings;
office buildings.
The factors taken into consideration when selecting the reference buildings included the
number of floors, the net area, and the window to façade area ratio. The aim was to select
buildings that the architects considered to be characteristic of newly planned buildings. On
the basis of the selected buildings, calculation models were developed to simulate energy
consumption.
In these simulation calculations, the following variables were set at different levels:
Descriptions of the calculation models can be found in Table 1. The area covered by the
models is presented in the form of the heated area, since energy consumption is presented in
relation to the heated area. The heated area is deemed to be the net area for which the indoor
climate is conditioned.
4
S/V, area of N/W/S/E façade. Please note: the orientation of the building can constitute an energy efficiency measure in
itself in the case of new buildings.
subcategories 1493 m² envelopes,
technical
Floor at ground systems and
level: heating
1364 m² systems.
Floor at ground
level:
1056 m²
4. Other non-
residential
building
categories
Table 3. Basic reporting table for energy performance relevant data
Location Tallinn, 59.35 N and 24.8 E Name of the city with indication of latitude and longitude
Degree-days are
calculated for the
whole year. The
number of degree-
days depends on the
location of the
building and the HDD
Climate conditions bivalent (heating To be evaluated according to EN ISO 15927-6, specifying the
Heating degree-days
temperature. Estonia degree-day) period of calculation
is divided into six
regions. For
instance, the number
of degree-days in a
standard year in the
Tallinn region at the
bivalent temperature
17 °C is 4220.
When calculating
with a simulation
programme, the
‘Estonian Test
Reference Year’ is
used as external
climate data
CDD
Cooling degree-days Not used in Estonia (cooling
degree-day)
Orientation Azimuth angle of the south façade (deviation from the South
see Annexes 1 °
direction of the ‘south’ oriented façade).
and 2
Small residential
Average thermal gain from occupants buildings: 2 W/m²
Apartment blocks: 3
Offices: 5
Latent heat
sources Small residential
buildings: 8
Total electric power of the complete lighting system of the
Specific electric power of the lighting system Apartment blocks: 8 W/m² conditioned rooms (all lamps + control equipment of the
lighting system)
Offices: 12
* In residential
buildings, lighting
utilisation is 0.1
Small residential
Specific electric power of electric equipment buildings: 2.4 W/m²
Apartment blocks: 3
Offices: 12
Small residential
buildings: New - 0.14 Weighted U-value of all walls: U_wall =
Average U-value of walls Existing - 0.25 / 0.54 (U_wall_1 · A_wall_1 + U_wall_2 · A_wall_2 + … +
Apartment blocks: U_wall_n
New - 0.17 · A_wall_n) / (A_wall_1 + A_wall_2 + … + A_wall_n); where
Existing - 0.8 / 1.1 U_wall_i = U-value of wall type i; A_wall_i = total surface area
of wall type i
Offices: New - 0.17
Existing - 1.0
Small residential
Building buildings: New - 0.09
elements Existing - 0.16 / 0.48
Small residential
Average U-value of foundation buildings: 0.09 W/m²K Similar to walls.
Apartment blocks:
0.14
Offices: 0.14
Small
residential
buildings:
New - 0.8
W/m²K
Average U-value of windows Existing - 2.1
Apartment Similar to walls; it should take into account the thermal bridge
due to the frame and dividers (according to EN ISO 10077-1)
blocks: New -
1.1
Existing - 2.0
Offices:
New -
1.1
Existing - 1.6
Total length Additional m
conductivities of
Average linear thermal bridges are
thermal added to simulation
Thermal bridges transmittance calculations in
accordance with W/mK
the regulation on
the methods for
calculating the
energy
performance of
buildings1
Not defined in the
External walls J/m²K
calculation method
Not defined in the
Thermal capacity per unit Internal walls J/m²K
calculation method To be evaluated according to EN ISO 13786
area
Not defined in the
Slabs J/m²K
calculation method
Not included in cost-optimal
Type of shading systems E.g. sun blind, roll-up shutter, curtain
calculations
Small
residential
buildings:
New - 1.0
Existing - 6.0 / 15
Infiltration rate (air changes per hour) m /(hm²)
3
E.g. calculated for a pressure difference inside/outside of 50 Pa
Apartment
blocks: New -
1.5
Existing - 4.4
Offices:
New -
1.5
Existing - 6.0
Small residential
Air flow rate buildings: 0.42 l/(cm²)
Apartment blocks:
Ventilation system 0.5
Building systems
Offices: 2.0
Underfloor
Distribution % Evaluated in accordance with EN 15316-1, EN 15316-2-1,
heating 90 %
EN 15316-4-1, EN 15316-4-2, EN 15232, EN 14825 and
Radiators 97 %
EN 14511 standards
Emission Not defined in the %
calculation method
Compressor - 3.5
Absorption cooling -
Efficiency of cooling system 0.7 Evaluated in accordance with EN 14825, EN 15243,
EN 14511 and EN 15232 standards
Depends on the
temperature of the
Distribution cooling water flow %
0.2-0.6
Emission Not defined in the %
calculation method
Small residential
Wint buildings: ≥ 21 °C
er
Apartment blocks: ≥
Temperature setpoint 21 Indoor operative temperature
Offices: ≥ 21
Building setpoints
and schedules Small residential
Sum buildings: ≤ 27 °C
mer
Apartment blocks: ≤
27
Offices: ≤ 25
Wint Not defined in the % Indoor relative humidity, if applicable: ‘Humidity has only a
er calculation method small effect on thermal sensation and perceived air quality in the
Humidity setpoint rooms of sedentary occupancy’ (EN 15251)
Sum Not defined in the %
mer calculation method
Occupancy In accordance with Table 2 in
Operation schedules and Section 6 of Regulation No 63 of
controls Lighting the Minister for Economic Provide comments or references (EN or national standards, etc.)
Appliances Affairs and Communications of on the schedules used for the calculation
Ventilation 8 October 2012 on the methods
Heating system for calculating the energy
Cooling system performance of buildings1. The
table provides detailed usage data
for lighting in residential buildings,
appliances in residential buildings,
people in residential buildings, and
for offices, buildings used for
educational purposes and pre-school
care establishments.
Energy building (Thermal) energy contribution 1) … Not included in cost- kWh/a E.g. solar greenhouse, natural ventilation, day lighting
need/use of main passive strategies 2) … optimal calculations kWh/a
implemented 3) … kWh/a
Energy consumption kWh/a
Energy need for heating using different
calculation variants is Heat to be delivered to or extracted from a conditioned space to
given in Table 5 maintain the intended temperature conditions during a given
Energy consumption kWh/a period of time
Energy need for cooling using different
calculation variants is
given in Table 5
Heat to be delivered to the needed amount of domestic hot water
Energy
consumption using to raise its temperature from the cold network temperature to the
Energy need for DHW kWh/a prefixed delivery temperature at the delivery point
different calculation
variants is given in
Table 5
Latent heat in the water vapour to be delivered to or extracted
Not included in cost-
Other energy need (humidification, from a conditioned space by a technical building system to
optimal calculations kWh/a
dehumidification) maintain a specified minimum or maximum humidity within the
space (if applicable)
Energy Electrical energy input to the ventilation system for air transport
consumption using and heat recovery (not including the energy input for preheating
Energy use for ventilation kWh/a
different calculation the air) and energy input to the humidification systems to satisfy
variants is given in the need for humidification
Table 5
Energy
consumption using
Energy use for internal lighting kWh/a
different calculation
variants is given in
Electrical energy input to the lighting system and
Table 5
other appliances/systems
Energy
Other energy use (appliances, external lighting, consumption using
kWh/a
auxiliary systems, etc.) different calculation
variants is given in
Table 5
Energy
consumption using
kWh/a
Thermal energy from renewable sources different calculation
Energy generation (e.g. thermal solar collectors) variants is given in Energy from renewable sources (that are not depleted by
directly in or near Table 5 extraction, such as solar energy, wind, water power, renewed
the building biomass) or co-generation
Energy
Electrical energy generated in the building and used on- consumption using kWh/a
site different calculation
variants is given in
Table 5
Not included in the
Electrical energy generated in the building and cost-optimal kWh/a
exported to the market
calculation model
Energy
Electricity consumption using kWh/a
different calculation
variants is given in
Table 5
Energy, expressed per energy carrier, supplied to the technical
Energy building systems through the system boundary, to satisfy the
Delivered energy consumption using
Fossil fuel kWh/a uses taken into account (heating, cooling, ventilation, domestic
different calculation hot water, lighting, appliances, etc.)
Energy consumption variants is given in
Table 5
Energy
Other (biomass, district consumption using
kWh/a
heating/cooling, etc.) different calculation
variants is given in
Table 5
Energy
consumption using
Primary energy kWh/a Energy that has not been subjected to any conversion or
different calculation
transformation process
variants is given in
Table 5
4. Selecting variants/measures/packages
86
energy sources
87
Office Current Nearly zero-energy level
building
practices
Small residential buildings Existing requirement for a major Energy performance class C
renovation
Older/newer Energy performance class D
Measures based on - -
renewable energy sources
88
U-value of roof, W/m²K 0.12 0.12
U-value of floor at
ground level, W/m²K
Measures based on - -
renewable energy sources
3. Calculation of the primary energy demand of the measures
Energy performance calculations are carried out in accordance with Regulation No 55 of the
Minister for Economic Affairs and Infrastructure on minimum energy performance
requirements1 and with Regulation No 58 of the Minister for Economic Affairs and
Infrastructure on the methods for calculating the energy performance of buildings.1
The primary energy demand of a building is expressed using the energy performance indicator. This
figure shows the gross energy needs per square metre of heated area per year, multiplied by
weighting factors. The unit in which the energy performance indicator is measured is kWh/m²a.
Current building 59.1 - 3.1 26.3 6.3 25 Electricity: 34.4; 154 (gas boiler) -
practices Gas: 85.4
79 (air-
Cost-optimal level 16.6 - 3.1 12.5 6.3 25 Electricity: 63.5 water heat 75
pump + PV
PV output: 24.0 panels)
90
Current building 96.3 - 3.2 26.3 6.3 25 Electricity: 34.5; 192 (gas -
practices Gas: 122.6 boiler)
87 (air-
Cost-optimal level 21.5 3.2 12.5 6.3 25 Electricity: 43.5 water heat 105
pump + PV
panels)
Apartment buildings
Current building 26.1 - 3.2 30.0 6.3 29.5 Electricity: 39.1 127 -
practices
District heating:
56.1
Cost-optimal level 13.6 - 3.2 30.0 6.3 29.5 Electricity: 39.1 103 24
District heating:
43.6
91
Office
Energy consumption, kWh/m²a
Measure/package/ Delivered energy Primary energy Reduction in
variant Heating Cooling Ventilation Domestic Fans, Lighting, specified by source, demand, kWh/m²a demand for
(as described in exhaust air hot water pumps appliances kWh/m²a (district (district heating) primary energy
Table 4) heating heating and compared to the
radiators) reference building,
kWh/m²a
Current building 25.8 3.0 9.5 5.8 13.8 37.9 Electricity: 55.7 149 -
practices
District heating: 41.1
Cost-optimal level 32.0 3.0 10.2 5.8 12.9 22.3 Electricity: 37.8 93 56
District heating:
48.0
92
Table 5.2. Energy demand calculation output table (existing buildings)
93
6.0
Existing 150 - electric 25 6.5 25.5 Electricity: 207 103
requirement for heater 38
a major
renovation Heating + hot
Energy water (pellet):
performance 175
class D
6.0
Energy 30 - electric 10 6.5 25.5 Electricity: 156 154
performance heater 38
class C
Heating + hot
water
(geothermal
heat): 40
Apartment buildings
Measure/package Net energy use, kWh/m²a Delivered energy Primary energy Reduction in
/variant specified by demand, kWh/m²a demand for
(as Heating Cooling Ventilatio Domestic Fans, Lighting, source, kWh/m²a primary energy
described in n exhaust hot water pumps appliances (gas boiler and compared to the
Table 4) air heat underfloor reference
heating) building,
kWh/m²a
94
Energy 45 - 5.0 30 5.0 29.5 Electricity: 148 94
performance electric 40
class C heater
Heating + hot water
(district heating): 70
Office
Measure/package Energy consumption, kWh/m²a Reduction in demand
/variant (as Delivered energy Primary energy for primary energy
described in Heating Cooling Ventilation Domestic Fans, pumps Lighting, specified by source demand, kWh/m²a compared to the
Table 4) exhaust air hot water appliances reference building,
heat kWh/m²a
Existing 65 35 7.5 6 10 37.6 Electricity: 59 177 133
requirement for a
major renovation Heating + hot water
Energy (district heating): 71
performance
class D
95
4. Calculation of total cost
New buildings
The economic calculations included construction cost calculations and discounted energy cost
calculations for 30 years in the case of residential buildings and 20 years in the case of non-
residential buildings. The cost of construction was calculated only for construction work and
components linked to improving energy performance.
Labour costs, materials, overhead expenses, part of the project-management costs, design costs and
VAT were included in the construction costs relating to energy performance.
The discount was calculated using the calculated interest rate and a relative price increase during
the calculation period. Depending on the uses of the buildings, the cost-effectiveness calculation
period was chosen to be 30 years (for residential buildings) or 20 years (for non-residential
buildings). The discount was based on the real interest rate of 2.5 %, which corresponds to the rate
of return of 3.5 % when inflation is 1 %. The real escalation of energy prices for the calculation
period was taken at 1 % per annum.
Financial calculations were based on the additional investment needed to achieve the nearly zero-
energy levels. When calculating the additional cost of the measure/package, the prices payable by
the customer, including all applicable taxes, VAT and support were taken into account in the
financial calculations. The calculations did not take into account the potential support that may
apply to the introduction of various technologies related to the production of renewable energy.
The cost of building components was calculated by totalling the different expense
types, and a discount rate was applied to them using the discount factor.
The criterion of profitability is that the net revenue generated and discounted during
the economic life of the investment should be greater than the initial investment.
Existing buildings
The economic calculations included construction cost calculations and discounted energy cost
calculations for 20 years. All renovation work costs were included in the calculation of construction
costs. For example, costs of additional roof insulation were added to the costs of roofing
installation.
The energy prices used, including value added tax, were as follows:
96
• Electricity EUR 0.11/kWh
• Natural gas EUR 0.05/kWh
• Pellet EUR 0.045/kWh
• District heating EUR 0.06/kWh
Justification of the gap: In the case of small residential buildings, the cost-optimal level
depends on the heat source used. Since energy carriers are weighted differently, there is no
direct correlation between delivered energy and primary energy use, and so the cost-optimal
level established through primary energy can change.
Plan to reduce the non-justifiable gap: Class B requirements will start applying in 2018, and
class A – or nearly zero-energy requirements – will be in force as of 31 December 2019, which
means 80 for small residential buildings and 100 for apartment blocks and office buildings. As
a result, the differences between cost-optimal and nearly zero-energy will be -8 % in small
residential buildings, -3 % in apartment blocks and 8 % in office buildings.
Justification of the gap: When laying down the new requirements, the energy efficiency
requirement for a major renovation should be increased by one energy performance class, i.e.
the energy efficiency requirement for a major renovation could be equal to the minimum
energy efficiency requirement of 160 kWh/(m²a) that applies to new small residential
97
buildings. This is because the cost-effective range for the reconstruction of small residential
buildings is quite large and the changes in the total cost are relatively small up to the energy
performance value of 150 kWh/(m²a).
Plan to reduce the non-justifiable gap: the transition to the class C requirements will take place
in 2018. As a result, the differences will disappear.
98