CONTROL IDENTIFICATION ABBREVIATION


TEMPERATURE
FIT
FLOW INDICATION
TRANSMITTER TIT INDICATION PLC
PROGRAMMABLE LOGIC
CONTROLLER
LCP LOCAL CONTROL
PANEL
TRANSMITTER
ANALYZER INDICATION LEVEL INDICATION
AIT TRANSMITTER LIT TRANSMITTER AI ANALOG INPUT DI DIGITAL INPUT

AH ALARM HIGH AL ALARM LOW AO ANALOG OUTPUT DO DIGITAL OUTPUT

ZO POSITION OPEN ZI POSITION INDICATION


FL FLOCCULANT CA CITRIC ACID

BATTERY LIMIT NOTE:


FLOCCULANT 1/2''-FL-133014321-PP-NI ZC POSITION CLOSED ZK POSITION CONTROL CS CAUSTIC SODA CO COAGULANT
FROM P-1330332A/B A. ALL VALVES ON THE P&ID DRAWINGS WILL BE PROVIDED BY
SHEET 05 OF 08 NAPIER-REID. MXA EQUIPMENT FAULT SF SPEED FEEDBACK DM DEMULSIFIER WW WASTEWATER

B. WHEN DEFINING THE PIPING BOUNDARY, 'H' REPRESENTS HQC, 'P'


CITRIC ACID 1/2''-CA-133014320-PP-NI
REPRESENTS PETROTEX (RAW PIPE MATERIALS ONLY), 'N' REPRESENTS MHS EQUPIMENT START/STOP SI SPEED INDICATION PT PHOSPHATE SL SLUDGE
FROM P-1330334A/B
NAPIER-REID.
SHEET 06 OF 08 MXL EQUIPMENT NORMAL SC
AUTO SPEED
CONTROL DN DRAIN RW RECYCLE WATER
C.MATCHING FLANGES FOR DAF TANK & SATURATION SKID HAVE BEEN
CAUSTIC SODA HAND SPEED
FROM P-1330333A/B
1/2''-CS-133014319-PP-NI PROVIDED BY NAPIER-REID. XP EMERGENCY STOP SH CONTROL SC SCUM OF OVERFLOW

SHEET 06 OF 08
YI YIELD INDICATION VH VALVE OPEN/CLOSE

COAGULANT 1/2''-CO-133014318-PP-NI
FROM P-1330331A/B
C SHEET 05 OF 08 C
DEMULSIFIER 1/2''-DM-133014317-PVDF-NI
FROM P-1330338A/B
SHEET 07 OF 08
2''-IW-133014327-AA1-NI
INDUSTRIAL WATER
3"-SW-133014006-AA2X-NI H FROM
2''-IW-133011028-HA2-NI
TREATMENT SOUR WATER
FROM P-134014A/B

MCR-0902 MCR-0902
WASH OIL
PMJ-I-1202-30-2116-D008 2''-WO-133014325-AA2X-NI
MCR-0902 FROM
2''-WO-13300042-AA1-NI
4"-WW-133014007-AA1-NI
MCR-0902
MCR-0902
MCR-0902
CONTAMINATED STORM WATER
FROM P-133027A/B/C
1/2''-PT-133014322-PP-NI
PHOSPHATE
MCR-0901 MCR-0902 MCR-0902
PMJ-I-1202-30-2116-D349 SC FROM P-1330335A/B
PH SHEET 07 OF 08
MCR-0902
MCR-0902
4''-OF-133014301-AA1-NI

DAF EFFLUENT
4''-WW-133014307-AA1-NI
TO S-1330332A/B
SHEET 03 OF 08
6''-SC-133014302-AA1-NI 4''-WW-133014304-AA1-NI
SC
FO FC 133-SC-305
B RECYCLE WATER B

2''-DN-133014305-AA1-NI
MCR-0902 MCR-0902 3''-RW-133014308-AA1-NI
TO D-1330331
FO SHEET 02 OF 08

8''-DN-133014303-AA1-NI INLET

2''-DN-133014305-AA1-NI
BAFFLE

4''-SC-133014309-AA1-NI

FO
NC
DRAIN NO

4''-SL-133014310-AA1-NI
NC
RECYCLE WATER DRAIN
FROM D-1330331
SHEET 02 OF 08
OILY SLUDGE & SCUM
TO L-133003
PMJ-I-1202-30-2116-D350

DRAIN DITCH
H AS BUILT 06/27/2018 M.C. P.P. F.L.
G FOR SUBMITTAL 04/03/2018 M.C. P.P. F.L.

LEGEND: F
E
FOR SUBMITTAL
FOR SUBMITTAL
03/16/2018
01/09/2018
M.C.
M.C.
P.P.
P.P.
F.L.
F.L.
NOTES: D FOR SUBMITTAL 12/22/2017 M.C. P.P. F.L.
1. PIPING CLASS FOR ALL WATER AND AIR PIPING IN THE WWTP IS "AA1-NI" C FOR SUBMITTAL 12/01/2017 M.C. P.P. F.L.
2. PIPING MATERIAL IN DEMULSIFIER SYSTEM IS "PVDF SCH.80". B FOR SUBMITTAL 10/17/2017 M.T. P.P. F.L.
PIPING MATERIAL IN SODIUM HYPOCHLORITE SYSTEM IS "CPVC SCH.80". A FOR SUBMITTAL 09/15/2017 M.T. P.P. F.L.
PIPING MATERIAL IN REST OF CHEMICAL SYSTEMS IS "PP, SCH.80". REV DESCRIPTION MM/DD/YYYY DESIGN CHECK APPR. NOTES
CONTINUITY ARROW
3. RESIDUAL SLUDGE WILL BE THICKENED IN SBR TANKS FIRSTLY AND THEN REVISION HISTORY
A CAN BE TRUCKED OUT AT LEAST ONCE PER WEEK. OR SETTING A A
INDIVIDUAL SLUDGE HOLDING TANK TO IMPROVE THE SBR PROCESS
PERFORMANCE. JOSE MIXED PLANT
WASTEWATER TREATMENT PACKAGE
PIPING & INSTRUMENT DIAGRAM
CUSTOMER PROJECT
PDVSA
PETROLERA
PSSA JOSE MIXED PLANT WWTP SCALE FILE. NO.: SHEET 01 OF 08
SINOVENSA OR AS NOTED DWG. NO.:
CONTRACTOR CONSULTING ENGINEER
HQC
DESIGN DATE: VERSION
THIRD ANGLE PLOT DATE : H

THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO NAPIER-REID LTD. IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. 10 ALDEN ROAD, UNIT 2, MARKHAM, ON, L3R 2S1 PHONE: (905) 475-1545 FAX: (905) 475-2021 WWW.NAPIER-REID.COM
THE DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF NAPIER-REID LTD.
8 7 6 5 4 3 2 1

TAG: D-1330331 TAG: P-1330337A/B TAG: K-1330331A/B


DAF SATURATION VESSEL DAF RECIRCULATION PUMP DAF SATURATION COMPRESSOR
DIAMETER (FT-IN) : 2-6 DESIGN CAPACITY (GPM) : 80 DESIGN CAPACITY (SCFM) : 1.3
STRAIGHT SIDE HEIGHT(FT-IN) : 6-6 HEAD (PSIG) : 78 HEAD (PSIG) : 105
DESIGN TEM. (°F) : 170 ELECTRIC POWER (HP) : 15 ELECTRIC POWER (HP) : 2
OPERATION TEM. (°F) : 80
DESIGN PRESSURE (PSIG) : 150
OPERATION PRESSURE (PSIG) : 105

LEGEND:
D D

RECYCLED WATER
FROM S-1330331 3''-RW-133014308-AA1-NI
SHEET 01 OF 08
NC
C MCR-0901 MCR-0902 MCR-0902 C
NC P-1330337A

CONTINUITY ARROW

NC
MCR-0901 MCR-0902 MCR-0902 TWL
NC P-1330337B

B B
D-1330331
CONTROL IDENTIFICATION ABBREVIATION

AIT
ANALYZER INDICATION
TRANSMITTER AAL ANALYZER ALARM
LOW PLC
PROGRAMMABLE LOGIC
CONTROLLER
LCP LOCAL CONTROL
PANEL
BWL

AAH ANALYZER ALARM


HIGH MXL EQUIPMENT NORMAL AI ANALOG INPUT DI DIGITAL INPUT

NC
MXA EQUIPMENT FAULT YI YIELD INDICATION AO ANALOG OUTPUT DO DIGITAL OUTPUT

DIFFERENTIAL
MHS EQUPIMENT START/STOP XP EMERGENCY STOP AR AIR DP PRESSURE

VH VALVE OPEN/CLOSE WW WASTEWATER RW RECYCLE WATER


K-1330331A

3''-RW-133014306-AA1-NI
1/2''-AR-133014311-HX2-NI
H AS BUILT 06/27/2018 M.C. P.P. F.L.
FI-0904 G FOR SUBMITTAL 04/03/2018 M.C. P.P. F.L.
NC
F FOR SUBMITTAL 03/16/2018 M.C. P.P. F.L.
E FOR SUBMITTAL 01/09/2018 M.C. P.P. F.L.
D FOR SUBMITTAL 12/22/2017 M.C. P.P. F.L.
RECYCLED WATER
K-1330331B C FOR SUBMITTAL 12/01/2017 M.C. P.P. F.L.
TO S-1330331
SHEET 01 OF 08 B FOR SUBMITTAL 10/17/2017 M.T. P.P. F.L.
NC
A FOR SUBMITTAL 09/15/2017 M.T. P.P. F.L.
REV DESCRIPTION MM/DD/YYYY DESIGN CHECK APPR. NOTES
DRAIN
REVISION HISTORY
A A

NOTES: JOSE MIXED PLANT


1. PIPING CLASS FOR ALL WATER AND AIR PIPING IN THE WWTP IS "AA1-NI" WASTEWATER TREATMENT PACKAGE
2. PIPING MATERIAL IN DEMULSIFIER SYSTEM IS "PVDF SCH.80".
PIPING MATERIAL IN SODIUM HYPOCHLORITE SYSTEM IS "CPVC SCH.80". PIPING & INSTRUMENT DIAGRAM
PIPING MATERIAL IN REST OF CHEMICAL SYSTEMS IS "PP, SCH.80". CUSTOMER PROJECT
3. RESIDUAL SLUDGE WILL BE THICKENED IN SBR TANKS FIRSTLY AND THEN CAN
PDVSA
BE TRUCKED OUT AT LEAST ONCE PER WEEK. OR SETTING A INDIVIDUAL PSSA JOSE MIXED PLANT WWTP SCALE FILE. NO.: SHEET 02 OF 08
SLUDGE HOLDING TANK TO IMPROVE THE SBR PROCESS PERFORMANCE. PETROLERA
OR AS NOTED DWG. NO.:
SINOVENSA CONTRACTOR CONSULTING ENGINEER
HQC
DESIGN DATE: VERSION
THIRD ANGLE PLOT DATE : H

THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO NAPIER-REID LTD. IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. 10 ALDEN ROAD, UNIT 2, MARKHAM, ON, L3R 2S1 PHONE: (905) 475-1545 FAX: (905) 475-2021 WWW.NAPIER-REID.COM
THE DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF NAPIER-REID LTD.
8 7 6 5 4 3 2 1

LEGEND:

D D

INDUSTRIAL WATER
FROM 2''-IW-133011028-HA2-NI 2''-IW-133014329-AA1-NI

LCR-0908
AIR TIMER CONTROL
FROM K-1330332A/B/C 4''-AR-133014315-HX2-NI

SHEET 04 OF 08 SLUDGE
TRUCKED OUT
2.5''-RAS-133014314-AA1-NI 2.5''-WAS-133014313-AA1-NI
B.L.
NC

C C
DAF EFFLUENT
4''-WW-133014307-AA1-NI
FROM S-1330331
SHEET 01 OF 08

CONTINUITY ARROW

CONTROL IDENTIFICATION ABBREVIATION

8''-WW-133014312-AA1-NI
AIT
ANALYZER INDICATION
TRANSMITTER AAL ANALYZER ALARM
LOW PLC
PROGRAMMABLE LOGIC
CONTROLLER
LCP LOCAL CONTROL
PANEL

AAH ANALYZER ALARM


HIGH MXL EQUIPMENT NORMAL AI ANALOG INPUT DI DIGITAL INPUT

EQUPIMENT
MXA MHF AO DO
4''-WW-133014307-NI

EQUIPMENT FAULT START/STOP ANALOG OUTPUT DIGITAL OUTPUT


FORWARD
EQUIPMENT
WASTE ACTIVATED
MHS EQUPIMENT START/STOP MHR START/STOP RAS
RETURN ACTIVATED
SLUDGE WAS SLUDGE
REVERSE

SLUDGE SI SPEED INDICATION YA YIELD ALARM


SC SCUM AR AIR
TRUCKED OUT
2.5''-RAS-133014314-AA1-NI 2.5''-WAS-133014313-AA1-NI
B NC
B.L. SC
AUTO SPEED
CONTROL YI YIELD INDICATION
CL CHLORINE WW WASTEWATER B

LCR-0909 DO DISSOLVED OXYGEN


SL SLUDGE

TIMER CONTROL
OXIDATION REDUCTION
ORP POTENTIAL RW RECYCLE WATER

1/2''-SH-133014323-CPVC-NI
SODIUM HYPO-CHLORITE
FROM P-1330340A/B
SHEET 08 OF 08

SBR EFFLUENT
8''-WW-133014312-AA1-NI 6''-TWW-133014316-AA1-NI
TO L-133002
PMJ-I-1202-30-2116-D348

H AS BUILT 06/27/2018 M.C. P.P. F.L.


G FOR SUBMITTAL 04/03/2018 M.C. P.P. F.L.
F FOR SUBMITTAL 03/16/2018 M.C. P.P. F.L.
E FOR SUBMITTAL 01/09/2018 M.C. P.P. F.L.
D FOR SUBMITTAL 12/22/2017 M.C. P.P. F.L.
C FOR SUBMITTAL 12/01/2017 M.C. P.P. F.L.
B FOR SUBMITTAL 10/17/2017 M.T. P.P. F.L.
A FOR SUBMITTAL 09/15/2017 M.T. P.P. F.L.
REV DESCRIPTION MM/DD/YYYY DESIGN CHECK APPR. NOTES
REVISION HISTORY
A A
NOTES: JOSE MIXED PLANT
1. PIPING CLASS FOR ALL WATER AND AIR PIPING IN THE WWTP IS "AA1-NI"
2. PIPING MATERIAL IN DEMULSIFIER SYSTEM IS "PVDF SCH.80". WASTEWATER TREATMENT PACKAGE
PIPING MATERIAL IN SODIUM HYPOCHLORITE SYSTEM IS "CPVC SCH.80".
PIPING MATERIAL IN REST OF CHEMICAL SYSTEMS IS "PP, SCH.80". PIPING & INSTRUMENT DIAGRAM
3. RESIDUAL SLUDGE WILL BE THICKENED IN SBR TANKS FIRSTLY AND THEN CAN CUSTOMER PROJECT
BE TRUCKED OUT AT LEAST ONCE PER WEEK. OR SETTING A INDIVIDUAL
PDVSA
PSSA JOSE MIXED PLANT WWTP SCALE FILE. NO.: SHEET 03 OF 08
SLUDGE HOLDING TANK TO IMPROVE THE SBR PROCESS PERFORMANCE.
PETROLERA
OR AS NOTED DWG. NO.:
SINOVENSA CONTRACTOR CONSULTING ENGINEER
HQC
DESIGN DATE: VERSION
THIRD ANGLE PLOT DATE : H

THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO NAPIER-REID LTD. IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. 10 ALDEN ROAD, UNIT 2, MARKHAM, ON, L3R 2S1 PHONE: (905) 475-1545 FAX: (905) 475-2021 WWW.NAPIER-REID.COM
THE DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF NAPIER-REID LTD.
8 7 6 5 4 3 2 1

TAG: K-1330332A/B/C
SBR BLOWER
DESIGN CAPACITY (SCFM) : 307
DIFFERENTIAL HEAD (PSIG) : 9.35
ELECTRIC POWER (HP) : 25

D D
LEGEND:

TIMER CONTROL

MCR-0901 MCR-0902

C C
AIR
4''-AR-133014315-HX2-NI
TO S-1330332A
SHEET 03 OF 08

CONTINUITY ARROW

TIMER CONTROL

MCR-0901 MCR-0902

NOTES:
1. PIPING CLASS FOR ALL WATER AND AIR PIPING IN THE WWTP IS "AA1-NI"
2. PIPING MATERIAL IN DEMULSIFIER SYSTEM IS "PVDF SCH.80".
PIPING MATERIAL IN SODIUM HYPOCHLORITE SYSTEM IS "CPVC SCH.80".
PIPING MATERIAL IN REST OF CHEMICAL SYSTEMS IS "PP, SCH.80".
B 3. RESIDUAL SLUDGE WILL BE THICKENED IN SBR TANKS FIRSTLY AND THEN CAN
B
TIMER CONTROL BE TRUCKED OUT AT LEAST ONCE PER WEEK. OR SETTING A INDIVIDUAL
SLUDGE HOLDING TANK TO IMPROVE THE SBR PROCESS PERFORMANCE.

MCR-0901 MCR-0902

AIR
4''-AR-133014315-HX2-NI H AS BUILT 06/27/2018 M.C. P.P. F.L.
TO S-1330332B
G FOR SUBMITTAL 04/03/2018 M.C. P.P. F.L.
SHEET 03 OF 08
F FOR SUBMITTAL 03/16/2018 M.C. P.P. F.L.
E FOR SUBMITTAL 01/09/2018 M.C. P.P. F.L.
D FOR SUBMITTAL 12/22/2017 M.C. P.P. F.L.
C FOR SUBMITTAL 12/01/2017 M.C. P.P. F.L.
B FOR SUBMITTAL 10/17/2017 M.T. P.P. F.L.
A FOR SUBMITTAL 09/15/2017 M.T. P.P. F.L.
REV DESCRIPTION MM/DD/YYYY DESIGN CHECK APPR. NOTES
REVISION HISTORY
A A

JOSE MIXED PLANT


WASTEWATER TREATMENT PACKAGE
PIPING & INSTRUMENT DIAGRAM
CUSTOMER PROJECT

PDVSA
PSSA JOSE MIXED PLANT WWTP SCALE FILE. NO.: SHEET 04 OF 08
PETROLERA
OR AS NOTED DWG. NO.:
SINOVENSA CONTRACTOR CONSULTING ENGINEER
HQC
DESIGN DATE: VERSION
THIRD ANGLE PLOT DATE : H

THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO NAPIER-REID LTD. IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. 10 ALDEN ROAD, UNIT 2, MARKHAM, ON, L3R 2S1 PHONE: (905) 475-1545 FAX: (905) 475-2021 WWW.NAPIER-REID.COM
THE DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF NAPIER-REID LTD.
8 7 6 5 4 3 2 1

D LEGEND D

INDUSTRIAL WATER MCR-0902


2''-IW-133014328-AA1-NI CONTINUITY ARROW
FROM DISTRIBUTION 50 PSI
PMJ-I-1202-30-2116-D303

MCR-0901 MCR-0902 MCR-0902


LCR-0901
COAGULANT
1/2''-CO-133014318-PP-AI TO S-1330333
SHEET 01 OF 08
NC

50 PSI

NC

C C

NC

NC NC NC NC

COFFERDAM

CONTROL IDENTIFICATION ABBREVIATION

MHS EQUPIMENT START/STOP MXL EQUIPMENT NORMAL


PLC
PROGRAMMABLE LOGIC
CONTROLLER
LCP LOCAL CONTROL
PANEL

MXA EQUIPMENT FAULT SR SPEED SETPOINT


AI ANALOG INPUT DI DIGITAL INPUT

MCR-0902
AO ANALOG OUTPUT DO DIGITAL OUTPUT

FL FLOCCULANT CO COAGULANT

B INDUSTRIAL WATER B
FROM DISTRIBUTION
2''-IW-133014328-AA1-NI
IW INDUSTRIAL WATER
MCR-0901 MCR-0902 MCR-0902
PMJ-I-1202-30-2116-D303 50 PSI
LCR-0902

FLOCCULANT NOTES:
1/2''-FL-133014321-PP-NI
TO S-1330333 1. PIPING CLASS FOR ALL WATER AND AIR PIPING IN THE WWTP IS "AA1-NI"
SHEET 01 OF 08 2. PIPING MATERIAL IN DEMULSIFIER SYSTEM IS "PVDF SCH.80".
NC PIPING MATERIAL IN SODIUM HYPOCHLORITE SYSTEM IS "CPVC SCH.80".
50 PSI PIPING MATERIAL IN REST OF CHEMICAL SYSTEMS IS "PP, SCH.80".
3. RESIDUAL SLUDGE WILL BE THICKENED IN SBR TANKS FIRSTLY AND THEN
NC CAN BE TRUCKED OUT AT LEAST ONCE PER WEEK. OR SETTING A INDIVIDUAL
SLUDGE HOLDING TANK TO IMPROVE THE SBR PROCESS PERFORMANCE.

LCR-0902

H AS BUILT 06/27/2018 M.C. P.P. F.L.


G FOR SUBMITTAL 04/03/2018 M.C. P.P. F.L.
F FOR SUBMITTAL 03/16/2018 M.C. P.P. F.L.
NC E FOR SUBMITTAL 01/09/2018 M.C. P.P. F.L.
D FOR SUBMITTAL 12/22/2017 M.C. P.P. F.L.
C FOR SUBMITTAL 12/01/2017 M.C. P.P. F.L.
NC NC NC NC B FOR SUBMITTAL 10/17/2017 M.T. P.P. F.L.
A FOR SUBMITTAL 09/15/2017 M.T. P.P. F.L.
REV DESCRIPTION MM/DD/YYYY DESIGN CHECK APPR. NOTES
REVISION HISTORY
A COFFERDAM A

JOSE MIXED PLANT


WASTEWATER TREATMENT PACKAGE
PIPING & INSTRUMENT DIAGRAM
CUSTOMER PROJECT

PDVSA
PSSA JOSE MIXED PLANT WWTP SCALE FILE. NO.: SHEET 05 OF 08
PETROLERA
OR AS NOTED DWG. NO.:
SINOVENSA CONTRACTOR CONSULTING ENGINEER
HQC
DESIGN DATE: VERSION
THIRD ANGLE PLOT DATE : H

THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO NAPIER-REID LTD. IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. 10 ALDEN ROAD, UNIT 2, MARKHAM, ON, L3R 2S1 PHONE: (905) 475-1545 FAX: (905) 475-2021 WWW.NAPIER-REID.COM
THE DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF NAPIER-REID LTD.
8 7 6 5 4 3 2 1

LEGEND

D D

MCR-0902

MCR-0901 MCR-0902 MCR-0902


50 PSI

LCR-0903 MCR-0902
CITRIC ACID
TO S-1330333
1/2''-CA-133014320-PP-NI
SHEET 01 OF 08

50 PSI
C C
NC

CONTINUITY ARROW

NC NC NC NC

COFFERDAM

MCR-0902
B B

MCR-0901 MCR-0902 MCR-0902


50 PSI

LCR-0904 MCR-0902
CAUSTIC SODA NOTES:
TO S-1330333 1. PIPING CLASS FOR ALL WATER AND AIR PIPING IN THE WWTP IS "AA1-NI"
1/2''-CS-133014319-PP-NI
SHEET 01 OF 08 2. PIPING MATERIAL IN DEMULSIFIER SYSTEM IS "PVDF SCH.80".
PIPING MATERIAL IN SODIUM HYPOCHLORITE SYSTEM IS "CPVC SCH.80". PIPING
MATERIAL IN REST OF CHEMICAL SYSTEMS IS "PP, SCH.80".
50 PSI 3. RESIDUAL SLUDGE WILL BE THICKENED IN SBR TANKS FIRSTLY AND THEN CAN BE
TRUCKED OUT AT LEAST ONCE PER WEEK. OR SETTING A INDIVIDUAL SLUDGE
HOLDING TANK TO IMPROVE THE SBR PROCESS PERFORMANCE.
NC
H AS BUILT 06/27/2018 M.C. P.P. F.L.
G FOR SUBMITTAL 04/03/2018 M.C. P.P. F.L.
F FOR SUBMITTAL 03/16/2018 M.C. P.P. F.L.
E FOR SUBMITTAL 01/09/2018 M.C. P.P. F.L.
D FOR SUBMITTAL 12/22/2017 M.C. P.P. F.L.
C FOR SUBMITTAL 12/01/2017 M.C. P.P. F.L.
B FOR SUBMITTAL 10/17/2017 M.T. P.P. F.L.
A FOR SUBMITTAL 09/15/2017 M.T. P.P. F.L.
REV DESCRIPTION MM/DD/YYYY DESIGN CHECK APPR. NOTES
NC NC NC NC REVISION HISTORY
A A
COFFERDAM JOSE MIXED PLANT
WASTEWATER TREATMENT PACKAGE
PIPING & INSTRUMENT DIAGRAM
CUSTOMER PROJECT

PDVSA
PSSA JOSE MIXED PLANT WWTP SCALE FILE. NO.: SHEET 06 OF 08
PETROLERA
OR AS NOTED DWG. NO.:
SINOVENSA CONTRACTOR CONSULTING ENGINEER
HQC
DESIGN DATE: VERSION
THIRD ANGLE PLOT DATE : H

THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO NAPIER-REID LTD. IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. 10 ALDEN ROAD, UNIT 2, MARKHAM, ON, L3R 2S1 PHONE: (905) 475-1545 FAX: (905) 475-2021 WWW.NAPIER-REID.COM
THE DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF NAPIER-REID LTD.
8 7 6 5 4 3 2 1

LEGEND

D D

MCR-0902

INDUSTRIAL WATER
1''-SW-133014327-AA1-NI MCR-0901 MCR-0902 MCR-0902
FROM DISTRIBUTION 50 PSI
PMJ-I-1202-30-2116-D303

PHOSPHATE
1/2''-PT-133014322-PP-NI
TO ME-1330332
SHEET 01 OF 08
NC

50 PSI

NC

C LCR-0905
C

CONTINUITY ARROW
NC

NC NC NC NC

COFFERDAM

MCR-0902
B B

MCR-0901 MCR-0902 MCR-0902


50 PSI

NOTES:
1. PIPING CLASS FOR ALL WATER AND AIR PIPING IN THE WWTP IS "AA1-NI"
2. PIPING MATERIAL IN DEMULSIFIER SYSTEM IS "PVDF SCH.80".
DEMULSIFIER PIPING MATERIAL IN SODIUM HYPOCHLORITE SYSTEM IS "CPVC SCH.80".
TO ME-1330331 PIPING MATERIAL IN REST OF CHEMICAL SYSTEMS IS "PP, SCH.80".
1/2''-DM-133014317-PVDF-NI
LCR-0906 SHEET 01 OF 08 3. RESIDUAL SLUDGE WILL BE THICKENED IN SBR TANKS FIRSTLY AND THEN
CAN BE TRUCKED OUT AT LEAST ONCE PER WEEK. OR SETTING A
50 PSI INDIVIDUAL SLUDGE HOLDING TANK TO IMPROVE THE SBR PROCESS
PERFORMANCE.

NC

H AS BUILT 06/27/2018 M.C. P.P. F.L.


G FOR SUBMITTAL 04/03/2018 M.C. P.P. F.L.
F FOR SUBMITTAL 03/16/2018 M.C. P.P. F.L.
E FOR SUBMITTAL 01/09/2018 M.C. P.P. F.L.
D FOR SUBMITTAL 12/22/2017 M.C. P.P. F.L.
C FOR SUBMITTAL 12/01/2017 M.C. P.P. F.L.
B FOR SUBMITTAL 10/17/2017 M.T. P.P. F.L.
A FOR SUBMITTAL 09/15/2017 M.T. P.P. F.L.
NC NC NC NC
REV DESCRIPTION MM/DD/YYYY DESIGN CHECK APPR. NOTES
REVISION HISTORY
A A
COFFERDAM
JOSE MIXED PLANT
WASTEWATER TREATMENT PACKAGE
PIPING & INSTRUMENT DIAGRAM
CUSTOMER PROJECT

PDVSA
PSSA JOSE MIXED PLANT WWTP SCALE FILE. NO.: SHEET 07 OF 08
PETROLERA
OR AS NOTED DWG. NO.:
SINOVENSA CONTRACTOR CONSULTING ENGINEER
HQC
DESIGN DATE: VERSION
THIRD ANGLE PLOT DATE : H

THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO NAPIER-REID LTD. IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. 10 ALDEN ROAD, UNIT 2, MARKHAM, ON, L3R 2S1 PHONE: (905) 475-1545 FAX: (905) 475-2021 WWW.NAPIER-REID.COM
THE DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF NAPIER-REID LTD.
8 7 6 5 4 3 2 1

LEGEND

D D

C C
MCR-0902

MCR-0901 MCR-0902
50 PSI
CONTINUITY ARROW

LCR-0907 SODIUM HYPOCHLORITE


1/2''-SH-133014323-CPVC-NI
TO TK-1330334
SHEET 03 OF 08

50 PSI

NC

B NC NC NC NC
B

COFFERDAM

NOTES:
1. PIPING CLASS FOR ALL WATER AND AIR PIPING IN THE WWTP IS "AA1-NI"
2. PIPING MATERIAL IN DEMULSIFIER SYSTEM IS "PVDF SCH.80".
PIPING MATERIAL IN SODIUM HYPOCHLORITE SYSTEM IS "CPVC SCH.80".
PIPING MATERIAL IN REST OF CHEMICAL SYSTEMS IS "PP, SCH.80".
3. RESIDUAL SLUDGE WILL BE THICKENED IN SBR TANKS FIRSTLY AND THEN
CAN BE TRUCKED OUT AT LEAST ONCE PER WEEK. OR SETTING A
INDIVIDUAL SLUDGE HOLDING TANK TO IMPROVE THE SBR PROCESS
PERFORMANCE.

H AS BUILT 06/27/2018 M.C. P.P. F.L.


G FOR SUBMITTAL 04/03/2018 M.C. P.P. F.L.
F FOR SUBMITTAL 03/16/2018 M.C. P.P. F.L.
E FOR SUBMITTAL 01/09/2018 M.C. P.P. F.L.
D FOR SUBMITTAL 12/22/2017 M.C. P.P. F.L.
C FOR SUBMITTAL 12/01/2017 M.C. P.P. F.L.
B FOR SUBMITTAL 10/17/2017 M.T. P.P. F.L.
A FOR SUBMITTAL 09/15/2017 M.T. P.P. F.L.
REV DESCRIPTION MM/DD/YYYY DESIGN CHECK APPR. NOTES
REVISION HISTORY
A A

JOSE MIXED PLANT


WASTEWATER TREATMENT PACKAGE
PIPING & INSTRUMENT DIAGRAM
CUSTOMER PROJECT

PDVSA
PSSA JOSE MIXED PLANT WWTP SCALE FILE. NO.: SHEET 08 OF 08
PETROLERA
OR AS NOTED DWG. NO.:
SINOVENSA CONTRACTOR CONSULTING ENGINEER
HQC
DESIGN DATE: VERSION
THIRD ANGLE PLOT DATE : H

THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO NAPIER-REID LTD. IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. 10 ALDEN ROAD, UNIT 2, MARKHAM, ON, L3R 2S1 PHONE: (905) 475-1545 FAX: (905) 475-2021 WWW.NAPIER-REID.COM
THE DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF NAPIER-REID LTD.