7/1/2013

- This sheet can be used to calculate wire distances for any 24Vdc (or FWR) Notification Appliance Circuit
(NAC) as well as audio circuits if you know the device loads and panel specs.
- Distances will be worst case (end loaded). Longer distances may be achieved if other calculations are
done for evenly distributed devices on the NAC.
- If using Edwards signaling devices, you can use the Load NAC( ) sheets to calculate circuit loads, which
can then be entered below for NAC( ) operating currents.
- The Load SpkrStrb sheet is for speaker loading (used with audio panels). The strobe currents from that
sheet will have to be assigned to one or more of the 24V NACs.

Load factors: Source voltages: Wire resistances (ohms/ft)*:


EBPS( )A = 0.59 EBPS( )A = 19.1 12AWG = 0.00198
E-FSC302 = 0.25 E-FSC( ) = 20.4 14AWG = 0.00314
E-FSC502 =0 .40 E-FSA( ) = 20.4 16AWG = 0.00499
E-FSC1004 = 0.20 18AWG = 0.00795
E-FSA64 = 0.20 *Resistances are typical. Use wire
E-FSA250 = 0.24 manufacturer's actual specs if known for
most accurate results.

Enter values in yellow boxes.


Refer to above load factors and source voltages for Edwards panels.

Choose panel being used:


NAC 3 & 4 not
Enter 1 for EBPS
available on 3 & 5
Enter 2 for E-FSC
zone conventional or
Enter 3 for E-FSA
E-FSA64.
Enter 4 for Other

Wire Distances for 24Vdc (or FWR) Notification Appliance Circuits


NAC1 NAC2 NAC3 NAC4
Enter total operating current (amps)
Enter load factor x 0 0 0 (Enter 0 if unknown)
Load voltage drop = 0 0 0 0
Enter source voltage 0 0 0
Load voltage drop
- 0 0 0 0
Minimum voltage
= 0 0 0 0
Enter min. device operating voltage
-
Voltage drop
= 0 0 0 0
Total operating current
/ 0 0 0 0
Maximum resistance=
Enter wire resistance (ohms/ft)
/
Maximum wire length (ft)
= (Single wire)
/ 2 2 2 2
Maximum cable length (ft) = (Pair of wires)
Speaker circuit distance is based on allowable dB (signal) loss. So rather than the
calculation resulting in a wire distance, you enter the distance you want to go for the
given wire size and load, and the calculation will give you the dB loss.

Typical audio amplifier voltage is 25 or 70Vrms, but may be different depending on


amplifier used (must check amplifier's spec).

Audio Wiring Distance dBA Change vs Audio Voltage


Enter audio voltage (Vrms) Enter speaker voltage
Enter wire guage Enter amplifier voltage
Enter wire resistance (ohms/ft) dB loss 0.0 (See note 6)
Enter speaker load (in watts) (See note 6)
Enter distance (in feet)
dB loss 0.0
(See note 4)

dBA Change vs Distance dBA Change vs Wattage


Enter dBA rating at starting distance Enter starting dBA
Enter starting distance (10 ft typical) Enter starting wattage
Enter new distance (in feet) Enter new wattage
New dBA 0.0 New dBA 0.0
(See note 5) (See note 5)

Distance Conversions
Miles Kilometers
Kilometers 0 Miles 0

Yards Meters
Meters 0 Yards 0

Feet Meters
Meters 0 Feet 0

Inches Centimeters
Centimeters 0 Inches 0

Notes:
1) For fire alarm applications you should be at least 15dBA above ambient noise levels, or 5dBA above the
maximum noise level having a duration of at least 60 seconds, or 75dBA, whichever is greatest.
2) Speaker circuit cable must be a minimum of 18 gauge twisted pair. Shielded cable may be necessary in
areas of high electrical noise.
3) "T" tapping of NAC (Notification Appliance Circuit) wiring is NOT permitted.
4) Speaker circuit wiring should not exceed -1dBA loss. In some cases, a spec may not allow more than a
-.5dBA loss.
5) dBA calculations are based on the distances being directly in front of the signaling device under ideal
conditions. Room acoustics and angles off center can affect actual dB readings.
6) If using a speaker with a higher voltage rating than the amplifier, you must de-rate speaker output by
amount shown. Example: If 70V speaker is rated at 90dBA, then is connected to an amplifier that outputs
25V, speaker dB will be less by the amount shown. You cannot connect a speaker to an amplifier with a
higher voltage rating.
3) "T" tapping of NAC (Notification Appliance Circuit) wiring is NOT permitted.
4) Speaker circuit wiring should not exceed -1dBA loss. In some cases, a spec may not allow more than a
-.5dBA loss.
5) dBA calculations are based on the distances being directly in front of the signaling device under ideal
conditions. Room acoustics and angles off center can affect actual dB readings.
6) If using a speaker with a higher voltage rating than the amplifier, you must de-rate speaker output by
amount shown. Example: If 70V speaker is rated at 90dBA, then is connected to an amplifier that outputs
25V, speaker dB will be less by the amount shown. You cannot connect a speaker to an amplifier with a
higher voltage rating.
FWR Current Totals (from Load NAC1) = 0 amps
dc Current Totals (from Load NAC1) = 0 amps

FWR Current Totals (from Load NAC2) = 0 amps


dc Current Totals (from Load NAC2) = 0 amps

FWR Current Totals (from Load NAC3) = 0 amps


dc Current Totals (from Load NAC3) = 0 amps

FWR Current Totals (from Load NAC4) = 0 amps


dc Current Totals (from Load NAC4) = 0 amps

FWR Current Totals (from Load SpkrStrb) = 0 amps


dc Current Totals (from Load SpkrStrb) = 0 amps

Total FWR Current = 0 amps


Total dc Current = 0 amps

For E-FSA and E-FSC panels, use FWR currents.


For EBPS( )A, use dc currents.
Be sure not to exceed panel's NAC rating:
E-FSC = 2.0A per ckt.
E-FSA = 2.5A per ckt.
EBPS( )A = 3.0A per ckt.

Minimum operating voltage for regulated devices, such as


Edwards Genesis series, is 16 volts.
If using a mix of devices with different minimum ratings on
same circuit, must use highest rating.

Enter wire resistance values from above if actual


specs for wire used is unknown.

Distance from panel to last device for class B, or


from panel to last device and back for class A.
Wattage Totals (from Load SpkrStrb) = 0 watts

If using a speaker with higher voltage rating than amplifier.


7/19/2011 v6a Updated 116DEGEX 24Vfwr cu
8/10/2011 v6b Added w.p. Genesis speaker str
5/2/2012 v7 draft Changed dB calc to allow diff. a
7/1/2013 v7 draft Added w.p. Genesis horn strobe
7/1/2013 v7 Released
4/24/2014 v7a draft Added low freq. Genesis
6/24/2014 v8 Released
Added 5553 haz loc speaker
EX 24Vfwr current
sis speaker strobes
to allow diff. audio voltages
sis horn strobes

enesis

oc speaker
4/24/2014

NAC1
Notes:
1) Enter quantities below per circuit in yellow boxes. Totals will appear to the right.
2) Be sure total does not exceed panel's NAC rating.
3) For FWR power supplies, such as E-FS(C)(A) panels, use the FWR currents.
4) For dc power supplies, such as the EBPS6(10)A, use the dc currents. Total FWR Current Load = 0 amps
5) Currents are worst case (U.L. nameplate) values. Total dc Current Load = 0 amps
6) This page does not list all the available fire alarm signals. Refer to catalog for additional
choices.

FWR mA dc mA
Horns & Horn Strobes FWR mA Total dc mA Total
Genesis wall mount horn only
EG1(*)-HD
Enter quantities for each dBA setting
0 Temporal Horn Count
0 Ok
high dBA 51 0 26 0
low dBA 37 0 19 0

Genesis low freqency horn only (for sleeping areas)


G4LF(**)-H 215 0 166 0

Genesis wall mount horn strobes


EG1(*)-HDVM
Enter quantities for each candela & dB setting
0 Temporal Horn / Strobe Count
0 Ok
15 cd, high dBA 176 0 129 0
30 cd, high dBA 230 0 167 0
75 cd, high dBA 397 0 281 0
110 cd, high dBA 443 0 337 0
15 cd, low dBA 162 0 122 0
30 cd, low dBA 216 0 160 0
75 cd, low dBA 383 0 274 0
110 cd, low dBA 429 0 330 0

Genesis low freqency horn strobe (for sleeping areas)


G4LF(**)-HVM
Enter quantities for each candela setting
0 Temporal Horn / Strobe Count
0 Ok
15 cd 308 0 219 0
30 cd 362 0 266 0
75 cd 510 0 381 0
110 cd 579 0 437 0

Genesis ceiling low candela horn strobes


EGC(*)-HDVM
Enter quantities for each candela setting
0 Temporal Horn / Strobe Count
0 Ok
15 cd 189 0 147 0
30 cd 253 0 190 0
75 cd 417 0 316 0
95 cd 451 0 372 0

Genesis ceiling high candela horn strobes


EGC(*)-HDVMH
Enter quantities for each candela setting
0 Temporal Horn / Strobe Count
0 Ok
95 cd 432 0 330 0
115 cd 518 0 392 0
150 cd 643 0 502 0
177 cd 693 0 565 0

Strobes
Genesis wall strobes
EG1(*)-VM
Enter quantities for each candela setting
0 Strobe Count
0 Ok
15 cd 125 0 103 0
30 cd 179 0 141 0
75 cd 346 0 255 0
110 cd 392 0 311 0

Genesis low candela ceiling strobes


EGC(*)-VM
Enter quantities for each candela setting
0 Strobe Count
0 Ok
15 cd 131 0 109 0
30 cd 194 0 151 0
75 cd 379 0 281 0
95 cd 437 0 318 0

Genesis high candela ceiling strobes


EGC(*)-VMH
Enter quantities for each candela setting
0 Strobe Count
0 Ok
95 cd 432 0 330 0
115 cd 518 0 392 0
150 cd 643 0 502 0
177 cd 693 0 565 0

Weatherproof Horn (Strobes)


Genesis low candela w.p. horn strobes
WG4**-HVMC
Enter quantities for each candela setting
0 Horn Strobe Count
0 Ok
15 cd 218 0 127 0
29 cd 239 0 168 0
70 cd 393 0 297 0
87 cd 422 0 351 0
Genesis high candela w.p. horn strobes
WG4**-HVMHC
Enter quantities for each candela setting
0 Horn Strobe Count
0 Ok
102 cd 447 0 342 0
123 cd 502 0 408 0
147 cd 614 0 517 0
161 cd 679 0 526 0

Integrity weatherproof horn


2447TH-* 82 0 35 0

Integrity 4 wire weatherproof worn wtrobe


2452THS-15/75-* 210 0 150 0
2452THS-110-* 420 0 329 0

Weatherproof strobe
CS405-7A-T* 210 0 150 0
CS405-8A-T* 420 0 329 0

Explosionproof
Horn
889D-AW 160 0 160 0
Strobe
116DEGEX-FJ 683 0 505 0

FWR mA dc mA
Other (not included above) FWR mA Total dc mA Total

Qty Part Number


0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0

Totals = 0 0
NAC2
Notes:
1) Enter quantities below per circuit in yellow boxes. Totals will appear to the right.
2) Be sure total does not exceed panel's NAC rating.
3) For FWR power supplies, such as E-FS(C)(A) panels, use the FWR currents.
4) For dc power supplies, such as the EBPS6(10)A, use the dc currents. Total FWR Current Load = 0 amps
5) Currents are worst case (U.L. nameplate) values.
6) This page does not list all the available fire alarm signals. Refer to catalog for additional
Total dc Current Load = 0 amps
choices.

FWR mA dc mA
Horns & Horn Strobes FWR mA Total dc mA Total
Genesis wall mount horn only
EG1(*)-HD
Enter quantities for each dBA setting
0 Temporal Horn Count
0 Ok
high dBA 51 0 26 0
low dBA 37 0 19 0

Genesis low frequency horn only (for sleeping areas)


G4LF(**)-H 215 0 166 0

Genesis wall mount horn strobes


EG1(*)-HDVM
Enter quantities for each candela & dB setting
0 Temporal Horn / Strobe Count
0 Ok
15 cd, high dBA 176 0 129 0
30 cd, high dBA 230 0 167 0
75 cd, high dBA 397 0 281 0
110 cd, high dBA 443 0 337 0
15 cd, low dBA 162 0 122 0
30 cd, low dBA 216 0 160 0
75 cd, low dBA 383 0 274 0
110 cd, low dBA 429 0 330 0

Genesis low frequency horn strobes (for sleeping areas)


G4LF(**)-HVM
Enter quantities for each candela & dB setting
0 Temporal Horn / Strobe Count
0 Ok
15 cd 308 0 219 0
30 cd 362 0 266 0
75 cd 510 0 381 0
110 cd 579 0 437 0

Genesis ceiling low candela horn strobes


EGC(*)-HDVM
Enter quantities for each candela setting
0 Temporal Horn / Strobe Count
0 Ok
15 cd 189 0 147 0
30 cd 253 0 190 0
75 cd 417 0 316 0
95 cd 451 0 372 0

Genesis ceiling high candela horn strobes


EGC(*)-HDVMH
Enter quantities for each candela setting
0 Temporal Horn / Strobe Count
0 Ok
95 cd 432 0 330 0
115 cd 518 0 392 0
150 cd 643 0 502 0
177 cd 693 0 565 0

Strobes
Genesis wall strobes
EG1(*)-VM
Enter quantities for each candela setting
0 Strobe Count
0 Ok
15 cd 125 0 103 0
30 cd 179 0 141 0
75 cd 346 0 255 0
110 cd 392 0 311 0

Genesis low candela ceiling strobes


EGC(*)-VM
Enter quantities for each candela setting
0 Strobe Count
0 Ok
15 cd 131 0 109 0
30 cd 194 0 151 0
75 cd 379 0 281 0
95 cd 437 0 318 0

Genesis high candela ceiling strobes


EGC(*)-VMH
Enter quantities for each candela setting
0 Strobe Count
0 Ok
95 cd 432 0 330 0
115 cd 518 0 392 0
150 cd 643 0 502 0
177 cd 693 0 565 0

Weatherproof Horn (Strobes)


Genesis low candela w.p. horn strobes
WG4**-HVMC
Enter quantities for each candela setting
0 Horn Strobe Count
0 Ok
15 cd 218 0 127 0
29 cd 239 0 168 0
70 cd 393 0 297 0
87 cd 422 0 351 0
Genesis high candela w.p. horn strobes
WG4**-HVMHC
Enter quantities for each candela setting
0 Horn Strobe Count
0 Ok
102 cd 447 0 342 0
123 cd 502 0 408 0
147 cd 614 0 517 0
161 cd 679 0 526 0

Weatherproof Horn
2447TH-* 82 0 35 0

Weatherproof Horn Strobe


2452THS-15/75-* 210 0 150 0
2452THS-110-* 420 0 329 0

Weatherproof Strobe
CS405-7A-T* 210 0 150 0
CS405-8A-T* 420 0 329 0

Explosionproof
Horn
889D-AW 160 0 160 0
Strobe
116DEGEX-FJ 683 0 505 0

FWR mA dc mA
Other (not included above) FWR mA Total dc mA Total

Qty Part Number


0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0

Totals = 0 0
NAC3*
Notes:
1) Enter quantities below per circuit in yellow boxes. Totals will appear to the right.
2) Be sure total does not exceed panel's NAC rating.
3) For FWR power supplies, such as E-FS(C)(A) panels, use the FWR currents.
4) For dc power supplies, such as the EBPS6(10)A, use the dc currents. Total FWR Current Load = 0 amps
5) Currents are worst case (U.L. nameplate) values. Total dc Current Load = 0 amps
6) This page does not list all the available fire alarm signals. Refer to catalog for additional
choices.
7) NAC3 not available on E-FSC302, E-FSC502 or E-FSA64 panels.*

FWR mA dc mA
Horns & Horn Strobes FWR mA Total dc mA Total
Genesis wall mount horn only
EG1(*)-HD
Enter quantities for each dBA setting
0 Temporal Horn Count
0 Ok
high dBA 51 0 26 0
low dBA 37 0 19 0

Genesis low freqency horn only (for sleeping areas)


G4LF(**)-H 215 0 166 0

Genesis wall mount horn strobes


EG1(*)-HDVM
Enter quantities for each candela & dB setting
0 Temporal Horn / Strobe Count
0 Ok
15 cd, high dBA 176 0 129 0
30 cd, high dBA 230 0 167 0
75 cd, high dBA 397 0 281 0
110 cd, high dBA 443 0 337 0
15 cd, low dBA 162 0 122 0
30 cd, low dBA 216 0 160 0
75 cd, low dBA 383 0 274 0
110 cd, low dBA 429 0 330 0

Genesis low freqency horn strobe (for sleeping areas)


G4LF(**)-HVM
Enter quantities for each candela setting
0 Temporal Horn / Strobe Count
0 Ok
15 cd 308 0 219 0
30 cd 362 0 266 0
75 cd 510 0 381 0
110 cd 579 0 437 0

Genesis ceiling low candela horn strobes


EGC(*)-HDVM
Enter quantities for each candela setting
0 Temporal Horn / Strobe Count
0 Ok
15 cd 189 0 147 0
30 cd 253 0 190 0
75 cd 417 0 316 0
95 cd 451 0 372 0

Genesis ceiling high candela horn strobes


EGC(*)-HDVMH
Enter quantities for each candela setting
0 Temporal Horn / Strobe Count
0 Ok
95 cd 432 0 330 0
115 cd 518 0 392 0
150 cd 643 0 502 0
177 cd 693 0 565 0

Strobes
Genesis wall strobes
EG1(*)-VM
Enter quantities for each candela setting
0 Strobe Count
0 Ok
15 cd 125 0 103 0
30 cd 179 0 141 0
75 cd 346 0 255 0
110 cd 392 0 311 0

Genesis low candela ceiling strobes


EGC(*)-VM
Enter quantities for each candela setting
0 Strobe Count
0 Ok
15 cd 131 0 109 0
30 cd 194 0 151 0
75 cd 379 0 281 0
95 cd 437 0 318 0

Genesis high candela ceiling strobes


EGC(*)-VMH
Enter quantities for each candela setting
0 Strobe Count
0 Ok
95 cd 432 0 330 0
115 cd 518 0 392 0
150 cd 643 0 502 0
177 cd 693 0 565 0

Weatherproof Horn (Strobes)


Genesis low candela w.p. horn strobes
WG4**-HVMC
Enter quantities for each candela setting
0 Horn Strobe Count
0 Ok
15 cd 218 0 127 0
29 cd 239 0 168 0
70 cd 393 0 297 0
87 cd 422 0 351 0
Genesis high candela w.p. horn strobes
WG4**-HVMHC
Enter quantities for each candela setting
0 Horn Strobe Count
0 Ok
102 cd 447 0 342 0
123 cd 502 0 408 0
147 cd 614 0 517 0
161 cd 679 0 526 0

Weatherproof Horn
2447TH-* 82 0 35 0

Weatherproof Horn Strobe


2452THS-15/75-* 210 0 150 0
2452THS-110-* 420 0 329 0

Weatherproof Strobe
CS405-7A-T* 210 0 150 0
CS405-8A-T* 420 0 329 0

Explosionproof
Horn
889D-AW 160 0 160 0
Strobe
116DEGEX-FJ 683 0 505 0

FWR mA dc mA
Other (not included above) FWR mA Total dc mA Total

Qty Part Number


0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0

Totals = 0 0
NAC4*
Notes:
1) Enter quantities below per circuit in yellow boxes. Totals will appear to the right.
2) Be sure total does not exceed panel's NAC rating.
3) For FWR power supplies, such as E-FS(C)(A) panels, use the FWR currents.
4) For dc power supplies, such as the EBPS6(10)A, use the dc currents. Total FWR Current Load = 0 amps
5) Currents are worst case (U.L. nameplate) values.
6) This page does not list all the available fire alarm signals. Refer to catalog for additional
Total dc Current Load = 0 amps
choices.
7) NAC4 not available on E-FSC302, E-FSC502 or E-FSA64 panels.*

FWR mA dc mA
Horns & Horn Strobes FWR mA Total dc mA Total
Genesis wall mount horn only
EG1(*)-HD
Enter quantities for each dBA setting
0 Temporal Horn Count
0 Ok
high dBA 51 0 26 0
low dBA 37 0 19 0

Genesis low freqency horn only (for sleeping areas)


G4LF(**)-H 215 0 166 0

Genesis wall mount horn strobes


EG1(*)-HDVM
Enter quantities for each candela & dB setting
0 Temporal Horn / Strobe Count
0 Ok
15 cd, high dBA 176 0 129 0
30 cd, high dBA 230 0 167 0
75 cd, high dBA 397 0 281 0
110 cd, high dBA 443 0 337 0
15 cd, low dBA 162 0 122 0
30 cd, low dBA 216 0 160 0
75 cd, low dBA 383 0 274 0
110 cd, low dBA 429 0 330 0

Genesis low freqency horn strobe (for sleeping areas)


G4LF(**)-HVM
Enter quantities for each candela setting
0 Temporal Horn / Strobe Count
0 Ok
15 cd 308 0 219 0
30 cd 362 0 266 0
75 cd 510 0 381 0
110 cd 579 0 437 0

Genesis ceiling low candela horn strobes


EGC(*)-HDVM
Enter quantities for each candela setting
0 Temporal Horn / Strobe Count
0 Ok
15 cd 189 0 147 0
30 cd 253 0 190 0
75 cd 417 0 316 0
95 cd 451 0 372 0

Genesis ceiling high candela horn strobes


EGC(*)-HDVMH
Enter quantities for each candela setting
0 Temporal Horn / Strobe Count
0 Ok
95 cd 432 0 330 0
115 cd 518 0 392 0
150 cd 643 0 502 0
177 cd 693 0 565 0

Strobes
Genesis wall strobes
EG1(*)-VM
Enter quantities for each candela setting
0 Strobe Count
0 Ok
15 cd 125 0 103 0
30 cd 179 0 141 0
75 cd 346 0 255 0
110 cd 392 0 311 0

Genesis low candela ceiling strobes


EGC(*)-VM
Enter quantities for each candela setting
0 Strobe Count
0 Ok
15 cd 131 0 109 0
30 cd 194 0 151 0
75 cd 379 0 281 0
95 cd 437 0 318 0

Genesis high candela ceiling strobes


EGC(*)-VMH
Enter quantities for each candela setting
0 Strobe Count
0 Ok
95 cd 432 0 330 0
115 cd 518 0 392 0
150 cd 643 0 502 0
177 cd 693 0 565 0

Weatherproof Horn (Strobes)


Genesis low candela w.p. horn strobes
WG4**-HVMC
Enter quantities for each candela setting
0 Horn Strobe Count
0 Ok
15 cd 218 0 127 0
29 cd 239 0 168 0
70 cd 393 0 297 0
87 cd 422 0 351 0
Genesis high candela w.p. horn strobes
WG4**-HVMHC
Enter quantities for each candela setting
0 Horn Strobe Count
0 Ok
102 cd 447 0 342 0
123 cd 502 0 408 0
147 cd 614 0 517 0
161 cd 679 0 526 0

Weatherproof Horn
2447TH-* 82 0 35 0

Weatherproof Horn Strobe


2452THS-15/75-* 210 0 150 0
2452THS-110-* 420 0 329 0

Weatherproof Strobe
CS405-7A-T* 210 0 150 0
CS405-8A-T* 420 0 329 0

Explosionproof
Horn
889D-AW 160 0 160 0
Strobe
116DEGEX-FJ 683 0 505 0

FWR mA dc mA
Other (not included above) FWR mA Total dc mA Total

Qty Part Number


0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0

Totals = 0 0
6/24/2014

Speaker Strobes
Notes:
1) Enter quantities below per circuit in yellow boxes. Totals will appear to the right.
2) Be sure total does not exceed panel's NAC (or amplifer) rating.
3) For FWR power supplies, such as E-FS(C)(A) panels, use the FWR currents.
4) For dc power supplies, such as the EBPS6(10)A, use the dc currents. Total FWR Current Load = 0 amps
5) Currents are worst case (U.L. nameplate) values. Total dc Current Load = 0 amps
6) This page does not list all the available fire alarm signals. Refer to catalog for additional
choices. Total Wattage = 0 watts

FWR mA dc mA Speaker
Indoor Speakers & Speaker Strobes FWR mA Total dc mA Total Wattage

Genesis wall mount speakers


EG4(*)-S(*)
Enter quantities for each wattage setting
0 Speaker Count
0 Ok
1/4 watt 0
1/2 watt 0
1 watt 0
2 watt 0

Genesis wall mount speaker strobes


EG4(*)-S(*)VM
Enter quantities for each wattage and candela setting
0 Speaker Count
0 Ok
1/4 watt 0
1/2 watt 0
1 watt 0
2 watt 0
0 Strobe Count
0 Ok
15 cd 120 0 96 0
30 cd 169 0 130 0
75 cd 329 0 239 0
110 cd 375 0 294 0

Genesis ceiling speakers


EGC(*)-S(*)
Enter quantities for each wattage setting
0 Speaker Count
0 Ok
1/4 watt 0
1/2 watt 0
1 watt 0
2 watt 0

Genesis low candela ceiling speaker strobes


EGC(*)-S(*)VM
Enter quantities for each wattage and candela setting
0 Speaker Count
0 Ok
1/4 watt 0
1/2 watt 0
1 watt 0
2 watt 0
0 Strobe Count
0 Ok
15 cd 131 0 109 0
30 cd 194 0 151 0
75 cd 379 0 281 0
95 cd 437 0 318 0

Genesis high candela ceiling speaker strobes


EGC(*)-S(*)VMH
Enter quantities for each wattage and candela setting
0 Speaker Count
0 Ok
1/4 watt 0
1/2 watt 0
1 watt 0
2 watt 0
0 Strobe Count
0 Ok
95 cd 432 0 330 0
115 cd 518 0 392 0
150 cd 643 0 502 0
177 cd 693 0 565 0

Weatherproof Speaker(Strobes)

Genesis weatherproof speaker only


WG4**-S
Enter quantities for each wattage
0 Speaker Count
0 Ok
1/4 watt 0
1/2 watt 0
1 watt 0
2 watt 0

Genesis low candela weatherproof speaker strobe


WG4**-SVMC
Enter quantities for each wattage and candela
0 Speaker Count
0 Ok
1/4 watt 0
1/2 watt 0
1 watt 0
2 watt 0
0 Strobe Count
0 Ok
15 cd 120 0 106 0
29 cd 178 0 144 0
70 cd 347 0 167 0
87 cd 386 0 319 0
Genesis high candela weatherproof speaker strobe
Enter quantities for each wattage and candela setting
WG4**-SVMHC
0 Speaker Count
0 Ok
1/4 watt 0
1/2 watt 0
1 watt 0
2 watt 0
0 Strobe Count
0 Ok
102 cd 412 0 324 0
123 cd 487 0 390 0
147 cd 607 0 494 0
161 cd 646 0 495 0

Double reentrant (projection) speaker


5552-15-R(W)
0 Speaker Count
0 Ok
1 watt 0
2 watt 0
4 watt 0
8 watt 0
15 watt 0

Hazardous Location

Hazardous location (Division 2) speaker


5553-25/70-R(G)
0 Speaker Count
0 Ok
1 watt 0
2 watt 0
4 watt 0
8 watt 0
15 watt 0

Others (not included above)


Strobe Currents
Speaker FWR mA dc mA Speaker
Qty Part Number Wattage FWR mA Total dc mA Total Wattage
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0

Totals = 0 0 0