Professional Documents
Culture Documents
91-1979
Sponsor
Transformers Committee of the
IEEE Power Engineering Society
Secretariat
Institute of Electrical and Electronics Engineers
National Electrical Manufacturers Association
Published by
The Institute of Electrical and Electronics Engineers, Inc
345 East 47th Street, New York, NY 10017
American National Standard
@Copyright 1979 by
(This Foreword is not a part of ANSI/IEEE C57.12.91-1979, American National Standard Test Code for Dry-Type
Distribution and Power Transformers.)
This standard with its companion standards represents a new milestone in standards for dry-type
transformers, which are becoming increasingly important with the elimination of askarel insulation
in new transformers.
Dry-type transformers have been served in the past by a variety of documents including ANSI/
IEEE C57.12.00-1973, ANSI/IEEE C57.12.90-1973, NEMA TR 27-1965 (R 1971, 1976), and
ANSI/NEMA Pub No ST 20-1972. This standard is the result of an effort encompassing the interests
of users, manufacturers, and others dedicated to produce voluntary consensus standards primarily
for dry-type transformers.
This new series of standards encompasses dry-type transformers with a high voltage of 601 V and
above and includes product standards through 34.5 kV and 7500 kVA (three phase, self-cooled).
These new standards have various and significant changes including higher BILs (for most voltages),
more stringent and meaningful short-circuit requirements, improved descriptions of usual and
unusual service conditions, and numerous other improvements. The arrangement of this new
standard should be easier and more efficient to use since its organization takes account of the
sequence in which information is normally needed. ANSI/IEEE C57.12.91-1979 includes customary
units and adds metric (SI) units in accordance with ANSI policy.
This standard was prepared by the Standards Preparation Working Group of the Dry-Type Trans-
former Subcommittee of the Transformers Committee of the Institute of Electrical and Electronics
Engineers, following which it was approved by the IEEE Dry-Type Transformer Subcommittee, the
IEEE Transformers Committee, the IEEE Standards Board, and the American National Standard
C57 Committee for Distribution and Power Transformers and Regulators. The applicable rules and
procedures of IEEE and'ANSI for the preparation and approval of voluntary consensus standards
were followed. These specify procedures for voting, review, and attempted reconciliation of dis-
senting viewpoints, a sixty day public review period, final review, and approval by the ANSI Board
of Standards Review.
This American National Standard is a voluntary consensus standard. Its use may become manda-
tory only when required by a duly constituted legal authority, or when specified in a contractual
relationship. To meet specialized needs and to allow innovation, specific changes are permissible
when mutually determined by the user and the producer, provided such changes do not violate
existing laws and are considered technically adequate for the function intended.
Suggestions for improvement of this standard will be welcome. They should be sent to:
Secretary
IEEE Standards
The Institute of Electrical and Electronics Engineers, Inc
345 East 47th Street
New York, N.Y. 10017
At the time it approved this standard, C57 had the following membership:
I. H. Koponen, Chairman C . R. Willmore, Secretary
Organization R epresen ted Name of Representative
This standard was developed by a Working Group of the Dry-Type Transformer subcommittee of
the IEEE Transformers Committee of the IEEE Power Engineering Society which had the following
membership:
J. C. Dutton, Chairman
R. Bancroft J. Lazzara
W. P. Burt W. A. Muska
H. E. Gabel J. J. Nay
0. R. Hamilton D. E. Shefka
E. J. Huber S. A. Weincek
When this standard was approved June 16, 1978, the IEEE Standards Board had the following
membership :
1. Scope ................................................................. 8
2. Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3. References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4. General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.1 Test Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.2 Test Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.3 Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.4 Testsequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.5 Instrumentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5. Resistance Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.1 Importance of Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.2 Determination of Cold Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.3 Conversion of Resistance Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.4 Resistance Measurement Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
6. Polarity and Phase-Relation Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6.2 Polarity Tests - Single-phase Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6.3 ..................
Polarity and Phase-Relation Tests - Polyphase Transformers 12
7 . RatioTests ............................................................. 14
7.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
7.2 Tolerances for Ratio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
7.3 Ratio Test Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
8. No-Load Losses and Excitation Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8.1 No-Load Losses - General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8.2 Test Methods for Single-phase Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8.3 Test Methods for Three-phase Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
8.4 Excitation Current (No-Load Current) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
9 . Impedance and Load Losses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
9.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
9.2 Impedance and Load-Loss Test Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
9.3 Interlacing Impedance Voltage of a Scott-Connected Transformer . . . . . . . . . . . . . . 25
9.4 Calculation of Impedance Voltage and Load Loss from Test Data . . . . . . . . . . . . . . 25
9.5 Impedance Bridges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
10. Dielectric Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
10.1 Factory Dielectric Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
10.2 Dielectric Tests in the Field . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
10.3 Applied-Voltage Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
10.4 Induced-Voltage Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
10.5 ImpulseTests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
10.6 Impulse Tests on Transformer Neutrals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
10.7 Detection of Failure during Impulse Test ................................. 31
10.8 Insulation-Power-Factor Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
10.9 Insulation-Resistance Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
11. Temperature Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
11.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
11.2 Temperature Test Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
.
SECTION PAGE
FIGURES
.
FIGURES PAGE
I
Fig 16 Three-phase Transformer Connections for Impedance-Loss and
Impedance-Voltage Tests Using Three-Wattmeter Method .................... 23
Fig 1 7 Three-phase Transformer Connections for Impedance-Loss and
Impedance-Voltage Tests Using Two-Wattmeter Method ..................... 23
Fig 18 General Impedance Bridge Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Fig 19 Potentiometer-Type Network Using a Phase Shifter . . . . . . . . . . . . . . . . . . . . . . . . . 26
Fig 20 Potentiometer-Type Network Using a Mutual Inductor ....................... 27
Fig 21 Two Single-phase Transformers in Opposition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Fig 22 Two Y-A Connected Transformers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Fig 23 A-A Connection for Three Single-phase Units or One Three Phase Unit . . . . . . . . . . 38
TABLES
.
An American National Standard
IEEE Standard Test Code
for Dry-Type Distribution and
Power Transformers
1. Scope 3. References
1.1 This standard describes methods for 3.1 Various American National Standards and
performing tests specified in ANSI/IEEE Guides and other standards are listed below.
C57.12.01-1979, General Requirements for When referred to in this standard, references
Dry-Type Distribution and Power Transformers, are identified only by number and year.
and other referenced standards applicable t o (Examples: ANSI/IEEE C57.12.01-1979, IEEE
dry-type distribution and power transformers. Std 1-1969.)
It is intended for use as a basis for perform- 3.2 When the American National Standards
ance, safety, and the proper testing of dry- and Guides referred to in this standard are
type distribution and power transformers. superseded by a revision approved by the
1.2 This standard applies to all dry-type trans- American National Standards Institute, Inc, the
formers except instrument transformers, step- latest revision shall apply.
voltage and induction voltage regulators, arc ANSI/IEEE Std 100-1977, American National
furnace transformers, rectifier transformers, Standard Dictionary of Electrical and Electron-
specialty transformers, and mine transformers. ics Terms.
ANSI/IEEE C5 7.12.01-1979, American National
1.3 When this standard is used on a mandatory
Standard General Requirements for Dry-Type
basis, the words shall and must indicate man-
Distribution and Power Transformers.
datory requirements; the words should or
may refer t o matters that are recommended or ANSI/IEEE C57.12.70-1964 (R 1971), Ameri-
permissive, but not mandatory. can National Standard Terminal Markings and
Connections for Distribution and Power Trans-
NOTE: The Foreword of this voluntary consensus formers.
standard describes the circumstances in which the
standard may be used on a mandatory basis. ANSI/IEEE C5 7.12.80-1978, American National
Standard Terminology for Power and Distribu-
tion Transformers.
ANSI/IEEE C57.98-1968, American National
2. Terminology Standard Guide for Transformer Impulse Tests,
(Appendix t o C57.12.90-1968).
Standard transformer terminology available
in ANSI/IEEE C57.12.80-1978, Terminology ANSI s1.4-1971 (R 1 9 7 6 ) ~American National
for power Distribution Transformers, Standard Specification for Sound Level Meters.
shall apply. Other electrical terms are defined ANSI S1.11-1966 (R 1976), American National
in ANSI/IEEE Std 100-1977, Dictionary of Standard Specifications for Octave, Half-Octave,
Electrical and Electronics Terms. and Third-Octave Band Filter Sets.
8
ANSI/IEEE
c57.12.91-1979 IEEE STANDARD TEST CODE FOR DRY-TYPE
IEEE Std 4-1978, Standard Techniques for 4.5 Instrumentation. Although the figures in
High Voltage Testing. this standard show conventional meters,
IEEE S M 99-1970, Guide for the Preparation adequate digital-readout measuring devices are
of Test Procedures for the Thermal Evaluation considered as satisfactory alternatives.
of Insulation Systems for Electric Equipment.
3.3 Applicable Documents in Preparation’
5. Resistance Measurements
4. General
5.1 Importance of Measurements. Resistance
measurements are of fundamental importance
4.1 Test Definitions. Various types of tests for three purposes:
(“routine, ” “design, ” “other,” and “conform-
(1) For the calculation of the 1 2 R compo-
ance” tests are defined in ANSI/IEEE C57.12.
80-1978. nent of conductor losses
(2) For the calculation of winding tempera-
4.2 Test Requirements. A general summary of tures at the end of a temperature test
test requirements is included in ANSI/IEEE (3) As a base for assessing possible damage in
C57.12.01-1979, Table 7, which indicates by the field
size (500 kVA and smaller, or 500 kVA and
larger) which tests are normally considered as
1
5.2 Determination of Cold Temperature. The
“routine,” “design,” or “other.” cold temperature of the winding shall be
determined as accurately as possible when
4.3 Purpose. The purpose of this standard is measuring the cold resistance. The precautions
to provide test procedure information. Trans- gven in 5.2.1 and 5.2.2 shall be observed.
former requirements and specific test criteria 5.2.1 General. Cold-resistance measurements
are not a part of this standard but are con- shall not be made on a transformer when it is
tained in appropriate American National Stand- located in drafts or when it is located in a room
ards, such as ANSI/IEEE C57.12.01-1979, or in which the temperature is fluctuating rapidly.
in user specifications. 5.2.2 Transformer Windings. The tempera-
ture of the windings shall be recorded as the
4.4 Test Sequence. See 10.1.5.4 for sequence average readings of several thermometers or
of dielectric tests when lightning impulse or thermocouples inserted between the coils, with
switching impulse tests are specified. care used t o see that their measuring points are
NOTE: If it is desired t o minimize potential damage as nearly as possible in actual contact with the
t o the transformer during testing, the resistance, winding conductors. I t should not be assumed
polarity, phase-relation, ratio, no-load-loss and excita-
tion current, impedance, and load-loss tests and that the windings are at the same temperature
temperature-rise tests (when applicable) should precede as the surrounding air.
dielectric tests. When this sequence is used, the 5.2.2.1 The temperature of the windings
beginning tests involve voltages and currents that are
usually reduced compared t o rated values, thus tending
may be considered equal t o the ambient air
to minimize damaging effects t o the transformer. temperature provided the transformer has been
in a draft-free area for 24 hours and provided
When the following documents are completed, ap- that neither voltage nor current has been applied
proved and published, they become a part of this
listing. to it for 24 to 72 hours, depending on size.
[ 11 Distribution and Power Transformer Short- 5.3 Conversion of Resistance Measurements.
Circuit Test Guide. (To be published in the ANSI C57 Cold winding resistance measurements are
Series.)
[ 21 Requirements for Ventilated Dry-Type Distribu-
normally converted to a standard reference
tion Transformers, 1 to 500 kVA, Single-phase; and 1 5 temperature equal to rated average winding
t o 500 kVA, Three-phase; with High-Voltage 2400- temperature rise plus 2OoC. In addition, it may
34 500 Volts, C57.12.50. be necessary to convert the resistance measure-
[ 3 ] Requirements for Ventilated Dry-Type Power
Transformers, 501 kVA and Larger, Three-phase, with merits to the temperature at which the
High-Voltage 2400-34 500 Volts. C57.12.51. imDedance-loss measurements were made, The
f4 ] ReqGirements for Sealed Dry-Type Power Trans- conversions =e accomplished by the following
formers, 501 kVA and Larger, Three-phase; with High-
Voltage 2400-34 500 Volts, C57.12.52. formula:
9
ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS C57.12.91-1979
a
NOTE: For resistance values of 1 or more a Wheat- NOTE: A reversal in magnetization of the core can
stone bridge (or equivalent) is commonly used; for change the time constant and result in erroneous
values less than 1 0 a Kelvin bridge (or equivalent) is readings.
commonly used. Some modern resistance bridges have
capability in both ranges.
Fig 1
Connections for the Voltmeter-Ammeter Method of Resistance Measurement
10
AN SI/ IEEE
C57.12.9 1-197 9 IEEE STANDARD TEST CODE FOR DRY-TYPE
I_
ing instruments are used. The average of the
resistances calculated from these measurements
shall be considered to be the resistance of the
circuit.
The current used shall not exceed 15 percent
of the rated current of the winding whose
resistance is to be measured. Larger values may
cause inaccuracy by heating the winding and
X I -x2
thereby changing its temperature and resistance.
If the current is too low to be read on a
deflecting ammeter, a shunt and digital milli-
voltmeter or potentiometer shall be used. A B
11
~
ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS C57.12.91-1979
12
ANSI/IEEE
C57.12.91-1979 IEEE STANDARD TEST CODE FOR DRY-TYPE
X, the lead that was connected t o H,, con- phase neutral is available, the phase-sequence
I
necting t o X2 the lead that was connected t o indicator leads should be transferred from H,
H,, and connecting t o X, the lead that was t o X,, from H, t o X,, from H, t o X,,respec-
connected t o H,. tively, and the direction of rotation noted. The
The transformer is again excited at a suitable tests should then be repeated by transferring
voltage (without changing the excitation con- from H, t o X,, from H, t o X4,and from H3
nections) and the indication again noted. t o X,, respectively, and noting the indication,
The phase sequence of the transformer is which should be the same as before.
correct if the indication is the same in both 6.3.3.1 The preceding method (phase-
cases. sequence test) does not disclose the angular
Six-phase secondaries, having no neutral con- displacement of the transformer.
nection, have to be connected temporarily in 6.3.3.2 The ratio bridge described in Sec-
delta (A) or wye ( Y ) for this test also. If a six- tion 7 can also be used t o test phase-sequence.
Fig 4
Transformer Lead Markings and Voltage-Phasor Diagrams for
Three-phase Transformer Connections
H2 x2
GROUP I
ANGULAR DELTA- DELTA CONNECTION
)I S P L ACE M E N T
0 DEGREES
Y - Y CONNECTION
HI ff3
DELTA-Y CONNECTION
GROUP 2
Af4GIJLAR
>ISPLACEMENT
30 DEGREES
Y-DELTA CONNECTION
-
TtiREE PHASE TRAP ;FORMERS WITH TAPS
$;9y2
x6 x3
ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS C57.12.9 1 - 1979
Fig 5
Transformer Lead Markings and Voltage-Phasor Diagrams
for Six-Phase Transformer Connections
ANSI/IEEE
C57.12.91-1979 IEEE STANDARD TEST CODE FOR DRY-TYPE
15
ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS C57.12.91-1979
16
ANSI/IEEE
C5 7.12.91-19 79 IEEE STANDARD TEST CODE FOR DRY-TYPE
t I
SOURCE G?
T VOLTAGE
TRANS FORM ER
SOURCE
I I I I
Fig 9
Connections for the No-Load-Loss Test of a
Single-phase Transformer: A - Without
Instrument Transformers. B - - With Instrument
Transformers
Figure 9A shows the necessary equipment use safe. When such multipliers are used, they
and connections when no instrument trans- shall be calibrated with the instruments.
formers are needed; Fig 9B when they are Low-power-factor wattmeters shall be used
needed, which is the general case. As indicated to obtain accurate results.
in Fig 9A, the voltmeters should be connected Either the high- or the low-voltage winding
nearest t o the load, the ammeter nearest to the of the transformer under test may be used, but
supply, and the wattmeter between the two it is generally more convenient t o make this
with its voltage coil on the load side of the test using the low-voltage winding. In any case,
current coil. the full winding (not merely a portion of the
Large transformers are not suitable for use as winding) should be used if possible. If for some
instrument transformers, since they introduce unusual reason only a portion of a winding is
losses as voltage transformers, and large ratio excited, this portion shall be not less than 25
and phase errors as current transformers. percent of the winding.
Transformers used for measuring no-load Adjust the frequency t o the desired value as
losses shall be instrument transformers. indicated by the frequency meter, and the
Resistance multipliers may be used in series voltage t o the desired value by the average-
with the voltage coil of instruments instead of voltage voltmeter. Record the simultaneous
voltage transformers if desired, provided values of frequency, rms voltage, watts, average-
suitable precautions are taken to make their voltage voltmeter readings, and amperes. Then
17
ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS C5 7.12.9 1-19 79
disconnect the transformer under test and read instrument is graduated in volts and calibrated
the losses on the wattmeter, which represent on a sine wave of voltage.
the losses of the connected instruments (and The principle of this instrument is based on a
voltage transformer if used), and which is t o be comparison of the losses in its reference core
subtracted from the earlier wattmeter reading when excited from a circuit having a sine wave,
to obtain the no-load loss of the transformer with its losses when excited from the source of
under test. excitation for the transformer under test. If
The correct no-load loss of the transformer these losses are unlike for the same rms voltage,
shall be determined from the measured value it is obvious that the wave form of the proposed
by means of the following equation: test voltage deviates from a sine wave. By
adjusting the value of the test voltage until the
loss in the core is the same as when excited
Pl + kP2 from a circuit having a sine-wave voltage of the
desired value, the measurement of the no-load
loss of the transformer under test is placed on a
where sine-wave basis.
The circuit is arranged as in Fig 9A or 9B, the
P = no-load loss (watts) at voltage Ea iron-loss voltmeter replacing the average-voltage
corrected to a sine-wave basis voltmeter. The voltage of the circuit is then
Pm = no-load loss measured in test adjusted by any convenient means until the
iron-loss voltmeter indicates the desired test
P, = per-unit hysteresis loss, referred to Pm
voltage. Then, the losses of the transformer
P, = per-unit eddy-current loss, referred to under test, like the losses of the core in the
pm iron-loss voltmeter, correspond substantially t o
a sine-wave voltage of the indicated magnitude
k =
(%), and frequency.
It is necessary t o verify that the core material
E, = test voltage measured by rms voltage of the iron-loss voltmeter is representative of
Ea = test voltage measured by average- the core material of the transformers to be
voltage voltmeter tested.
If a voltage transformer is used, its rating
The actual per-unit values of hysteresis and should be large enough so that the burden of
eddy current losses should be used, if available. the iron-loss voltmeter does not materially
change its ratio or phase angle or wave shape.
NOTE: If actual values are not available, it is sug-
gested that these two loss components be assumed 8.2.3 Standard Core Method. The standard
equal in value, assigning each a value of 0.5 per unit. core is a miniature representative sample of the
transformers to be tested. Its no-load loss is
The eddy-current loss in the core varies with accurately determined previously with a sine
the square of the rms value of the excitation wave of applied voltage over a wide range of
voltage and is substantially independent of the flux density on each of the several taps of its
voltage wave shape. When the test voltage is winding; the flux density in any transformer
held at rated voltage with the average-voltage under test can thus be closely approximated.
voltmeter, the actual rms value of the test The sample core is usually supplied from a
voltage may not be the rated value, and the voltage transformer that is connected in
eddy-current loss in the test will be related t o multiple with the transformer under test; the
the correct eddy-current loss at rated voltage losses of the sample and of the transformer are
by the equations. determined at the rated voltage of the trans-
8.2.2 Iron-Loss Voltmeter Method. The iron- former.
loss voltmeter is essentially a wattmeter The ratio between the loss of the sample with
measuring the excitation loss in a small self- a sine wave of applied voltage of the same
contained laminated core of silicon steel. The effective value (read from a curve) and the loss
excitation winding of this core is in series with with the actual test voltage applied constitute
the stationary coil of the wattmeter. The the necessary multiplier for the measured
ANSI/IEEE
C5 7.12.9 1-1979 IEEE STANDARD TEST CODE FOR DRY-TYPE
q
-
1 I
W
0
iiz
TOTAL LOSS
TOTAL LOSS
PI - p2
I I J
Fig 10
Two-Wattmeter Method Fig 11
Three-Wattmeter Method with Transformer
Neutral Available
excitation loss of the transformer under test
to correct it to a sine-wave basis. This method
ordinarily is not suitable for field work.
It is necessary t o verify that the core material
of the standard core is representative of the
core material of the transformer t o be tested.
If a voltage transformer is used, its rating
should be large enough so that the burden of
the standard core does not materially change TOTAL LOSS
P, + P2 + P3
its ratio or phase angle or wave shape.
8.3 Test Methods for Three-phase Trans-
formers. The methods described for single- Fig 12
phase transformers also apply to three-phase Three-Wattmeter Method Using Artificial
transformers with the additions and modifica- Wattmeter Neutral N
tions given in 8.3.1 through 8.3.4.
8.3.1 In measuring the core loss of three-
phase transformers with two wattmeters connected from one line to the three-phase
(Fig lo), three entirely separate sets of readings neutral, when available (Fig 11). The three
shall be taken by using each of the three lines readings are added t o obtain the no-load loss.
in succession as the common line. The average 8.3.3 If the three-phase neutral is not avail-
value of the three sets of readings shall be able, an artificial neutral may be derived
recorded as the true no-load loss. (Fig 12). If voltage transformers are neces-
8.3.2 In using the two-wattmeter method, s a r y , an open A-connection should be used to
great care should be exercised in reading the supply the Y -connected wattmeters.
wattmeters accurately. Because of the low 8.3.4 The impedance bridge method may be
power factor, the reading of one wattmeter will used as an alternate to the wattmeter method
be negative and must be subtracted from the for the measurement of no-load losses provided
other. The two readings may be of the same that the applied excitation voltage is sufficiently
general order of magnitude, so that slight close to a sine wave. Each major harmonic
inaccuracies in their values may lead to large should not exceed 0.5 percent of the funda-
percentage errors in their small difference. mental unless acceptable corrections are applied
Under such difficult conditions greater ac- to the measurement.
curacy may be obtained by the alternative The impedance bridge method is advantageous
procedure given in 8.3.2.1. for low-power-factor measurements where
8.3.2.1 Measurements may be made with special wattmeters and techniques are ordinarily
three wattmeters, each voltage circuit being required.
19
ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS C57.12.91-1979
20
ANSI/IEEE
C57.12.91-1979 IEEE STANDARD TEST CODE FOR DRY-TYPE
ing the instantaneous maximum value of the in the test made according t o 8.4.3 do not differ
corresponding currents. by more than 10 percent, the excitation cur-
Simultaneous readings are taken on these rent on a sine-wave basis shall be taken as the
two instruments at 100 percent, 86.6 percent, average of the values obtained by the tests
and 50 percent voltage. These data determine described in 8.4.2 and 8.4.3.
approximately the fundamental, third, and
fifth harmonics of the excitation current.
The excitation current (Is)corresponding t o 9. Impedance and Load Losses
sine-wave voltage shall be determined from the
foregoing data by the following equation: 9.1 General. Load losses are those losses in
a transformer that are incident t o the carrying
of the load.
NOTE: Load losses include Z2R loss in the windings
due t o load current; stray loss due to stray fluxes in
in which I , , I,, and I , are the instantaneous the windings, core clamps, magnetic shields, enclosure
or tank walls, etc, and also to circulating currents, if
maximum values of excitation current corre- any, in parallel windings.
sponding to excitation voltages of 100 percent,
88.6 percent, and 50 percent of rated voltage. 9.1.1 Impedance Voltage. The impedance
This method applies not only t o single-phase voltage comprises an effective resistive com-
transformers but, in a slightly modified form, ponent corresponding to the load losses, and a
also to those three-phase transformers that reactive component corresponding t o the
are free from large third-harmonic voltages, leakage-flux linkages of the windings.
that is, in practice, the transformers having It is not practical to measure these compo-
one or more A-windings or those having a nents separately, but after the total impedance
three-legged, three-phase core. loss and total impedance voltage are measured,
Readings are obtained as indicated in the the components may be separated by calculation.
preceding paragraphs, but now the line current The voltage required t o circulate the rated
consists of only the fundamental and the fifth- current under short-circuit conditions when
harmonic components of the required ampere- connected on the rated voltage tap is the
turn excitation. impedance voltage, and the watt loss measured
Since only two important components are is the load loss.
present, only two readings are necessary (II at The impedance voltage generally falls between
100 percent excitation voltage and I, at 86.6 3 percent and 15 percent of the rated voltage
percent voltage), and the excitation current of the excited winding, and this fact may be
( I s )corresponding t o sine-wave voltages may be used as a guide in planning for the voltage
determined by the following equation: suppl9 for the impedance test.
NOTE: The “load loss” is sometimes referred to as
Is = 4 0 . 2 5 1 ; + 0.3381: the “impedance loss.”
21
ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS C57.12.91-1979
a cross section equal to, or greater than, the It is sufficient t o measure and adjust the
corresponding transformer leads. They should current in the excited winding only because
be as short as possible and should be kept the current in the short-circuited winding will
away from magnetic masses. Contacts should be the correct value (except for a negligible
be clean and tight. excitation-current error) when the current in
NOTE: The accuracy of impedance-voltage measure- the excited winding is correct. To introduce
ments is improved by using short-circuiting connec- measuring equipment in series with the short-
tions with a resistance that is low relative t o the circuited winding t o measure its current may
resistance of the winding being short-circuited.
introduce a greater error into the impedance
(3) These precautions are of importance in data owing to the losses and voltage drop of
avoiding extraneous impedance voltage and that equipment.
losses that might otherwise be introduced into 9.2.3 Impedance Test of Autotransformer
the measurements. (1) An autotransformer may be tested for
9.2.2 Impedance Test of Single-phase Trans- impedance with its internal connections un-
former. One of the two windings of the trans- changed. The test is made by short-circuiting
former (either the high-voltage winding or the its input (or output) terminals and applying
low-voltage winding) is short-circuited, and voltage t o the other terminals t o cause its
voltage at rated frequency is applied t o the appropriate rated line current to flow, the
other winding and adjusted t o circulate rated external connections being as in Fig 15.
currents in the windings (Fig 14). (2) The series and common windings of the
With the current and frequency adjusted t o autotransformer may be treated as separate
the rated values as nearly as possible, simulta- windings, one being short-circuited, the other
neous readings should be taken on the ammeter, excited, for the impedance test.
voltmeter, wattmeter, and frequency meter. When this procedure is followed, the current
The transformer under test should then be held must be the rated current of the exciting
disconnected and tare readings taken on the winding, which may or may not be the same as
wattmeter, representing the losses of the mea- the line current indicated in preceding para-
suring equipment, similar to the procedure in graphs.
the no-load-loss test. With the foregoing precaution followed, the
impedance watts and volt-amperes will be the
same by either method (1) or (2).
Fig 14 The impedance voltage measured across the
Single-phase Transformer Connections for series winding will correspond t o that between
Impedance-Loss and Impedance-Voltage the high-voltage terminals of the autotrans-
Tests former, while the impedance voltage measured
22
ANSI/IEEE
C5 7.1 2.91-1979 IEEE STANDARD TEST CODE FOR DRY-TYPE
POWER
SOURCE
b T
VOLTS C A N
BE READ:
A N , E N , CN -
OR
A B , B C , CA
C
CCI
N&.C -/ TRANS FORM ER
UNDER TEST
(FOR ANY A O R Y
COMBINATION)
VT
Fig 16
Three-phase Transformer Connections for Impedance-Loss and
Impedance-Voltage Tests Using Three-Wattmeter Method
23
ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS C57.12.91-1979
24
ANSI/IEEE
C57.12.91-1979 IEEE STANDARD TEST CODE FOR DRY-TYPE
where Z12, Z 2 3 , and Z31 are the measured Per-unit values of the resistance, reactance, and
impedance values between pairs of windings, as impedance voltages are obtained by dividing
indicated, all expressed on the same kVA base. Er, E,, and E, by the rated voltage. Percentage
These equations involve complex numbers, values are obtained by multiplying per-unit
but they may be used for the resistance (in- values by 100.
phase) component or reactance (quadrature) The 12R losses of the two windings are calcu-
component of the impedance voltage or of lated from the ohmic resistance measurements
impedance volt-amperes. (corrected to the temperature at which the
The treatment of the individual impedance impedance test was made) and the currents
losses for temperature correction, etc, is the that were used in the impedance measurement.
same as for two-winding single-phase trans- The 12R losses subtracted from the load-loss
formers. watts give the stray losses of the transformer
The total loss for a three-winding trans- at the temperature at which the load-loss test
former is approximately the sum of the losses was made.
in the three windings as determined for the The 12R component of the load loss increases
load conditions of the windings. with the temperature, and the stray-loss com-
9.3 Interlacing Impedance Voltage of a Scott- ponent diminishes with the temperature; there-
Connected Transformer. The interlacing im- fore, when it is desired t o convert the imped-
pedance voltage of Scott-connected trans- ance losses from one temperature t o another,
formers is the single-phase voltage applied the two components of the impedance loss are
from the midtap of the main transformer converted separately. Thus,
winding t o both ends connected together, the
voltage being sufficient t o circulate in the
supply lines a current equal t o the rated three-
phase line current. The current in each half of
the winding is 50 percent of this value.
The percent interlacing impedance is the
measured voltage expressed as a percentage of
the teaser voltage.
The percent resistance is the measured watts
expressed as a percentage of the rated kVA of resistance loss at temperature T
the teaser winding. stray loss a t temperature T
9.4 Calculation of Impedance Voltage and calculated resistance loss at tempera-
Load Loss from Test Data ture Tm
9.4.1 Impedance Voltage. Resistive and re- calculated stray loss at temperature
active components of the impedance voltage
Tm
are determined by the use of the following
equations: 234.5 for copper
p, 225 for aluminum
Er = -
I
NOTE: 225 applies for pure or EC aluminum. Tk may
be as high as 230 for alloyed aluminum.
E, = dEi - E:
9.5 Impedance Bridges
where 9.5.1 Impedance Bridge Method. The im-
pedance bridge method may be used as an
E, = resistance voltage, in-phase component alternate t o the wattmeter-voltmeter-ammeter
E, = reactance voltage, quadrature com- method for the measurement of impedance and
ponent impedance losses.
The impedance bridge method is advantageous
E , = impedance voltage
for low-power-factor measurements where
P, = watts measured in impedance test special wattmeters and techniques are ordi-
I = current in amperes in excited winding narily required.
25
ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS (257.12.91-1979
TRANSFORMER
UNDER TEST
Fig 18
General Impedance Bridge Network
TO POWER
L
SOURCE I TRANSFORMER
90' PHASE UNDER TEST
SHIFTER
A
VT
Fig 19
Potentiometer-Type Network Using a Phase Shifter
26
ANSI/IEEE
C57.12.91-1979 IEEE STANDARD TEST CODE FOR DRY-TYPE
‘0POWFR
SOURCE
I
f I
A I
\;;ANSFORMER
UNDER TEST
%
CT - MUTUAL
4 1
Fig 20
Potentiometer-Type Network Using a Mutual Inductor
phasor sum of the voltage drops B and C are 10.1.2 Test Voltages. Unless otherwise spec-
compared with the voltage drop A. For op- ified, the dielectric test voltages shall be mea-
eration at a fixed frequency (normally 60 Hz), sured or applied, or both, in accordance with
the constants of the circuit can be arranged so IEEE Std 4-1978, Standard Techniques for
that the balance position of potentiometer B High Voltage Testing.
is directly proportional to the loss in the trans- 10.1.3 Transformers. Transformers shall be
former under test for low power factors. assembled prior to making dielectric tests,
The configuration of a direct-reading-type including sheet metal enclosures and any termi-
potentiometer network for measuring loss is nal compartments involved, except in those
usually determined by the voltage or current instances where the transformer is furnished to
to be held during test. For no-load loss, where the user without sheet metal enclosures or
voltage is the reference parameter, the in-phase terminal compartments.
and quadrature voltage drops required for 10.1.4 Temperature. The temperature of
balance are advantageously derived from the the transformer during dielectric testing shall
voltage portion of the test circuit. For imped- be between 10°C and 40°C.
ance loss, where load current is the reference 10.1.5 Conditions. The dielectric tests spec-
parameter, these voltage drops are advanta- ified in 10.1.5.1 through 10.1.5.3 shall be
geously derived from the current portion of the performed in accordance with the require-
test circuit. ments in ANSI/IEEE C57.12.01-1979.
Additional information on these and other 10.1.5.1 Low-Frequency Dielectric Tests.
impedance networks of the potentiometer type Tests shall be performed in accordance with
is included in references. Table 3 and Section 5.10 of ANSI/IEEE C57.
9.5.2.2 Three-phase Bridge Measurements. 12.01-1979.
Loss measurements on three-phase transformers NOTES :
are made by connecting the bridge network to (1) I; the following test descriptions, the word
each phase in turn and calculating the total loss “phase refers to the “line terminal” of a winding and
from the three single-phase measurements. This not t o the entire phase of a winding, recognizing the
construction of windings with “graded insulation.”
is analogous to the three-wattmeter method of (2) The low-frequency tests are described in func-
measuring losses using a single wattmeter. tional and geometric terms. The accomplishment of
these low-frequency tests is achieved by the “applied-
voltage” and “induced-voltage” tests described in 10.3
and 10.4, or combinations thereof.
10. Dielectric Tests
10.1.5.2 Low-Frequency Tests-Exceptions.
10.1 Factory Dielectric Tests (1) Subject to the limitation that thevoltage-
10.1.1 Purpose. The purpose of dielectric to-ground test must be performed as specified
tests in the factory is to demonstrate that the in 10.1.5.1 on the line terminals of the winding
transformer has been designed and constructed with the lowest ratio of test voltage to minimum
to withstand the imposition of voltages associ- turns, then test levels may otherwise be reduced
ated with the specified insulation levels. such that none of the tests required in 10.1.5.1
27
ANSIIIEEE
DISTRZBUTION AND POWER TRANSFORMERS C57.12.91-1979
28
ANSI/IEEE
C5 7.12.91 -1979 IEEE STANDARD TEST CODE FOR DRY-TYPE
29
ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS C57.12.91-1979
10.5.1.2 When specified, the results of im- full-wave value given in the tables in these
pulse tests shall be reported on the “Trans- standards. When reports require oscillograms,
former Impulse Test Report” form illustrated those of the first reduced-full-wave voltage and
in ANSI/IEEE C57.98-1968. current, the last two chopped waves, and the
10.5.2 Wave to be Used for Impulse Tests. last full wave of voltage and current shall
A 1.2 X 50 microsecond wave shall be used represent a record of the successful application
for full-wave and reduced full-wave tests. of the impulse test t o the transformer.
Waves of positive polarity shall be used for 10.5.3 Connections for Impulse Tests. In
dry-type transformers. general the tests shall be applied to each termi-
The time to crest on the front from virtual nal, one a t a time.
time zero to actual crest shall not exceed 10.5.3.1 Grounding. One terminal of the
2.5 ps except for windings of large impulse winding under test shall be grounded directly
capacitance (low-voltage, high-kVA and some or through a low resistance if current measure-
high-voltage, high-kVA windings). ments are t o be made. (For exceptions see the
To demonstrate that the large capacitance of following paragraph.) The terminals of windings
the winding causes the long front, the impulse that are not being tested may be grounded
generator series resistance may be reduced, directly or through a resistor in order to limit
which should cause superimposed oscillations. the voltage induced in these windings. It is
Only the inherent generator and lead induc- desirable that the voltages on terminals that
tances should be in the circuit. are not being tested should not exceed 80 per-
For convenience in measurement, the time t o cent of the full-wave voltage for their insula-
crest may be considered as 1.67 times the tion level.
actual time between points on the front of All grounds shall be direct, except as de-
the wave at 30 and 90 percent of the crest scribed in the preceding paragraph and at
value. neutral terminals, which may be grounded
The time on the tail to the point of halfcrest through the same neutral grounding impedance
voltage of the applied wave shall be not less as is t o be used in service. If such neutral
than 40 ps from the virtual time zero, unless grounding impedance is unavailable, the neutral
the winding is of low inductance. This is within shall be directly grounded.
the minus 20 percent tolerance provided for 10.5.3.2 Series/MuEtiple Connections. Only
a 1.2 X 50 ps wave. the series connection of a series or multiple
The virtual time zero can be determined by connection shall be tested, unless tests on both
locating points on the front of the wave at connections are specified. The connection of
which the voltage is, respectively, 30 and the other windings (whether series or parallel)
90 percent of the crest value and then drawing shall be made at the choice of the manufacturer.
a straight line through these points. The inter- 10.5.3.3 Delta and Wye Connections. Un-
section of this line with the zero voltage line less otherwise specified, tests shall be made
is the virtual time zero. on the A-connection. When so specified, tests
When there are high-frequency oscillations shall be made on the Y-connection, or both the
on the crest of the wave, the crest value shall A- and Yconnections.
be determined from a smooth wave sketched 10.5.3.4 Tap Connections. Tap connec-
through the oscillations. If the period of these tions shall be made with minimum effective
oscillations is 2 ps or more, the actual crest turns in the winding under test. The choice of
value shall be used. tap connections of windings not being tested
If there are oscillations on the front of the shall be made by the manufacturer.
waves, the 30 and 90 percent points shall be 10.5.3.5 Protective Devices. When protec-
determined from the average, smooth-wave tive devices are permanently connected as an
front sketched in through the oscillations. integral part of series transformer windings or
The magnitude of the oscillations preferably of other portions of windings, these devices
should not exceed 10 percent of the applied shall be connected during test. The operation
voltage. of these devices usually will cause differences
All impulses applied to a transformer should between the reduced-full-wave and the full-wave
be recorded by a cathode-ray oscillograph if oscillograms. That these differences are caused
their crest voltage exceeds 40 percent of the by the operation of the protective devices may
ANSI/IEEE
C57.12.91-1979 IEEE STANDARD TEST CODE FOR DRY-TYPE
be demonstrated by making two or more amplitude equal t o the BIL of the neutral. The
reduced-full-wave tests at different voltage winding being tested shall be on the maximum-
values t o show the trend in their operation. voltage connection.
Further evidence that the differences are due
to the operation of the protective devices may 10.7 Detection of Failure during Impulse Test.
be obtained, in some cases, by making addi- Because of the nature of impulse test failures,
tional tests with the protective devices shorted one of the most important matters is the detec-
out. tion of such failures, There are a number of
10.5.3.6 Low-Impedance Windings. In some indications of insulation failure.
cases the inductance of the winding is so low 10.7.1 Ground-Current Oscillograms. Unless
that the desired voltage magnitude and dura- otherwise specified, ground-current oscillograms
tion to the 50 percent point on the tail of the shall be the standard method of failure detec-
wave cannot be obtained with available equip- tion, where applicable. Both ground-current
ment. In some cases the terminals of such oscillograms and voltage oscillograms may be
windings having the same insulation class at used for failure detection.
both ends may be tied together for the test. In this method of failure detection, the im-
Because of the difference in insulation level at pulse current in the grounded end of the
the two terminals of the winding, it is some- winding tested is measured by means of a
times impossible t o tie the terminals together cathode-ray oscillograph connected across a
for the impulse test. Low-inductance windings suitable shunt inserted between the normally
may also be tested by inserting a resistor of not grounded end of the winding and ground. Any
more than 500 52 in the grounded end of the differences in the wave shape between the
winding. In all such cases shorter waves may be reduced full wave and final full wave detected
used. by superimposing the two current oscillograms
may be indications of failure or deviations due
10.6 Impulse Tests on Transformer Neutrals. t o noninjurious causes. They should be fully
When specified, impulse tests on the neutral investigated and explained by a new reduced-
of a transformer may be applied by the methods wave and full-wave test. Examples are opera-
given in 10.6.1 and 10.6.2. The choice of the tion of protective devices, core saturation, or
method of testing the neutral shall be made conditions in the test circuit external to the
by the manufacturer. transformer. In air- or gas-insulated apparatus
NOTE: The standard neutral insulation specified in partial discharges (corona) may produce
ANSI/IEEE C57.12.01-1979, provides for grounded high-frequency oscillations on the wave. This
Y operation, and the neutral is designed for an applied- is not an indication of failure and should be
voltage test. If specified, the neutral shall be insulated
for a higher insulation level. taken into account in interpreting the traces.
10.7.1.1 The ground-current method of de-
10.6.1 The test on the neutral, or neutral tection is not applicable for use with chopped-
and regulating winding, is induced by the appli- wave tests.
cation of an impulse t o any line terminal with
the neutral grounded through a suitable imped- 10.7.2 Other Methods of Failure Detection
ance so that the required full-wave test voltage 10.7.2.1 Voltage Oscillograms, Any unex-
is obtained from the neutral terminal t o ground. plained differences between the reduced full
One reduced and two full waves shall be ap- wave and the final full wave detected by super-
plied t o the line end of a winding with a crest imposing the two voltage oscillograms, or any
voltage equal t o or less than the full-wave level such differences observed by comparing the
of the line end. The other windings may be chopped waves to each other and t o the full
short-circuited for this test. The winding being wave up to the time of flashover, are indica-
tested shall be on the maximum voltage con- tions of failure. Deviations may be caused by
nection. The voltage oscillograms shall be taken conditions in the test circuit external to the
at the neutral. When this method of test is transformer or by protective devices and should
used, the test on the neutral shall precede the be fully investigated. In air- or gas-insulated
test on the line terminal. apparatus partial discharges (corona) may
10.6.2 One reduced and two full waves are produce high-frequency oscillations on the
applied directly to the winding neutral with an wave. This is not an indication of failure and
31
ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS C57.12.91-1979
should be taken into account in interpreting curacy of measurement should be within f 0.25
the traces. percent insulation power factor, and the mea-
10.7.2.2 Failure of Gap to Flashover. In surement should be made at or near a frequency
making the chopped-wave test, failure of the of 60 Hz.
chopping gap, or any external part, to flash- 10.8.3 Voltage to be Applied. The voltage
over, although the voltage oscillogram shows a t o be applied for measuring insulation power
chopped wave, is a definite indication of a factor shall not exceed operating voltage to
flashover either within the transformer or in ground for any part of the winding or 1000 V,
the test circuit. whichever is lower.
10.7.2.3 Noise. Unusual noise within the 10.8.4 Procedure. Insulation power-factor
transformer at the instant of applying the tests shall be made from windings t o ground
impulse is an indication of trouble. Such noise and between windings, as shown in Table 1.
should be investigated.
NOTE: While the real significance that can be at-
10.8 Insulation-Power-Factor Tests. Insulation tached to the insulation power factor of dry-type
transformers is still a matter of opinion, experience has
power factor is the ratio of the power dissipated shown that insulation power factor is helpful in assess-
in the insulation in watts to the product of ing t h e probable condition of t h e insulation when good
the effective voltage and current in volt- judgment is used.
amperes when tested under a sinusoidal voltage In interpreting the results of insulation-power-factor
test values, the comparative values of tests taken at
and prescribed conditions. periodic intervals are useful in identifying potential
The methods described herein are applicable problems rather than an absolute value of insulation
power factor.
to dry-type distribution and power transformers A factory insulation-power-factor test will be of
of present-day design. value for comparison with field insulation power
10.8.1 Preparation for Tests. The test speci- factor measurements to assess the probable condi-
men shall have: tion of the insulation. It has not been feasible to
establish standard insulation power factor values for
(1) All windings short-circuited dry-type transformers because experience has indi-
(2) All terminals in place cated that little or n o relation exists between insulation
power factor and t h e ability of t h e transformer t o with-
(3) Temperature of transformer near the stand t h e prescribed dielectric tests.
reference temperature of 20°C
Where the temperature is other than 20°C, 10.9 Insulation-Resistance Tests. Insulation-re-
the results should be corrected t o 2OoC. sistance tests are made to determine the in-
sulation resistance from individual windings t o
NOTE: Typical temperature correction-factor data for ground, or between individual windings. The
dry-type transformers are not presently available.
insulation resistance in such tests is commonly
10.8.2 Instrumentation. Insulation power fac- measured in megohms but may be calculated
tor may be measured by special bridge circuits from measurements of applied voltage and
or by the volt-ampere-watt method. The ac- leakage current.
Table 1
Measurements to be Made in Insulation Power Factor Tests
*The Term guard signifies one or more conducting elements arranged and connected o n an electrical instrument or
measuring circuit so as to divert unwanted currents from the measuring means.
$Permanently connected windings, such as autotransformers, shall be considered as one winding.
32
ANSI/IEEE
C57.12.91-1979 IEEE STANDARD TEST CODE FOR DRY-TYPE
Insulation-resistance tests shall be made when winding involved (or 1 0 0 0 V for a solidly p o u n d e d
wye winding), a relief gap may be employed to protect
specified. the insulation.
The insulation resistance of electrical appara-
tus is of doubtful significance as compared 10.9.4 Procedure
with the dielectric strength. It is subject t o (1) Insulation-resistance tests shall be made
wide variation with design, temperature, dry- with all circuits of equal voltage above ground
ness, and cleanliness of the parts. When the connected together. Circuits or groups of cir-
insulation resistance falls below prescribed cuits of different voltages above ground shall
values, it can, in most cases of good design and be tested separately; for example, high voltage
where no defect exists, be brought up t o the t o low voltage and ground, low voltage t o high
required standard by cleaning and drying the voltage and ground.
apparatus. The insulation resistance, therefore, (2) Voltage should be increased in incre-
may afford a useful indication as to whether ments (usually 1 to 5 kV), holding each step
the apparatus is in suitable condition for appli- for 1 min.
cation of the dielectric test. (3) The test should be discontinued im-
mediately in the event the current begins t o
NOTES : increase without stabilizing.
( 1 ) The significance of values of insulation-resistance
tests generally requires some interpretation, depending
on the design and the dryness and cleanlidess of the
insulation involved. If a user decides to make insula- 11. Temperature Tests
tion-resistance tests, it is recommended that insulation-
resistance values be measured periodically (during
maintenance shutdown) and that these periodic values 11.1 General. Transformers shall be tested
be plotted. Substantial variation in the plotted values of under a loading condition that will give losses
insulation resistance should be investigated for cause.
(2) Insulation resistances may vary with applied as near as possible t o those obtained when the
voltage, and any comparison must be made with transformer is operating connected for its
measurements at the same voltage. nameplate rating. In some cases temperature
testing requires a slight overexcitation.
10.9.1 Preparation for Test The resultant increase in total loss has a
(1) Windings in their normal insulation negligible effect on the kilovolt-ampere output.
environment It is therefore not considered in the tempera-
(2) All windings short-circuited ture rise test methods described herein.
(3) All bushings or terminals in place Conditions under which temperature limits
(4) Transformer temperature approximately apply are stated in ANSI/IEEE C57.12.01-
2oOc. 1979. Transformers shall be tested on the tap
10.9.2 Instrumentation. Insulation resistance connection giving the highest winding tempera-
may be measured using either: ture rise.
(1) A variable-voltage dc power supply with
means to measure voltage and current (generally 11.2 Temperature Test Methods
in microamperes o r milliamperes) 11.2.1 Simulated Loading
(2) A megohmeter 11.2.1.1 Loading-Back (Opposition) Meth-
od for Self-Cooled and Forced-Cooled Trans-
NOTE: Megohmeters are commonly available with formers, Ventilated Dry Type. The loading-back
nominal voltages of 500, 1000, and 2500 V. DC ap- (opposition) method requires a greater amount
plied test equipment is available at higher voltages.
of testing facilities and auxiliary equipment,
10.9.3 Voltage t o be Applied. The dc voltage and also energy consumption. Because of these
applied for measuring insulation resistance to requirements, the loading-back method becomes
ground shall not exceed a value equal to the increasingly difficult to perform as the size
rms low-frequency applied voltage allowed of the transformer increases.
in 10.3. 11.2.1.2 Short-circuit Method for Venti-
NOTES:
lated Dry-Type Self-Cooled Transformers Only
(1) Partial discharges should not be present during (Separate Load-Loss and Excitation Test). If
insulation-resistance tests, since they can damage a the test equipment cannot produce rated cur-
transformer and may also result in erroneous values of rent, the short-circuit method necessitates an
I insulation resistance.
( 2 ) When measurements are t o be made using dc
voltages exceeding the rms operating voltage of the
accurate predetermination of excitation losses
and conductor losses, including stray losses, at
33
ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS C5 7.12.91 -1979
operating temperature. It has the advantage of restricted cooling, or any other suitable
permitting a direct measurement of the wattage method.
and current being held during the temperature 11.3.2 Temperature Measurements. The ulti-
rise test. This method requires fewer testing mate temperature rise is considered to be
facilities and a smaller amount of energy con- reached when the temperature rise becomes
sumption. It is particularly suitable for the constant, that is, when the temperature rise
larger size transformers and is equally satis- does not vary more than 2°C during a consecu-
factory for small transformers. tive 3 h period.
11.2.1.3 Impedance kVA Method. This is Use of thermocouples is the preferred method
a method for testing a single three-phase trans- of measuring surface temperatures. Thermo-
former or three single-phase transformers hav- couples shall be placed in intimate contact
ing delta windings or able t o be connected t o with the surface being measured, attached to
two delta windings. One delta winding must be maintain firm contact, and thermally insulated
open so that the impedance kVA can be from the surrounding medium.
supplied. For the purpose of determining where
11.2.2 Actual Loading. The actual loading constant temperature conditions have been
method is the most accurate of all methods, achieved, the sensing thermocouples shall be
but its energy requirements are excessive for applied to the surfaces as specified in the
large transformers. following :
Transformers of small output may be tested (1) Ventilated dry-types: Top center of core
under actual load conditions by loading them top yoke and innermost low-voltage lead of
on a rheostat, bank of lamps, or water box or middle phase (34 units) or an inner low-voltage
by similar loading methods. of a 14 unit
11.2.3 Test Method Application (2) Sealed dry or nonventilated types: Center
11.2.3.1 The loading-back method is a of top cover surface and center of one sidewall
basic method for testing sealed or ventilated surface
dry-type transformers and may be used when When the temperature rise has become con-
more than one unit is available for test. stant, the test voltage and current should be
11.2.3.2 The separate load-loss and excita- removed and the fans, if used, shut off. Im-
tion-loss test method may be used on all self- mediately thereafter the coil thermometers
cooled, ventilated dry-type transformers. and any other temperature-indicating devices
11.2.3.3 The load-loss test plus an addi- should be read continually in rotation until the
tive factor may be used for all ventilated temperature begins to fall. If any of the ther-
dry-type transformers when empirical data mometer temperatures are higher than those
are available establishing the proper value of observed during the run, the highest tempera-
the additive factor. ture should be recorded as the final thermome-
11.2.3.4 When it is not feasible t o make ter temperature.
a loading-back temperature test on a sealed or The temperature rise of the windings shall be
nonventilated dry-type transformer, a combina- determined by the resistance method, or by
tion of tests involving a total-loss heat-run thermometer when so specified.
test, a current heat-run test, and an excitation When measured, the temperature rise of metal
heat-run test may be used to calculate the parts (other than the winding conductor) in
temperature rise of the windings. contact with, or adjacent to, insulation, and of
11.3 Requirements for Temperature-Rise Tests other metal parts, shall be determined by
11.3.1 General. Transformers shall be com- therinocouples or by thermometer.
pletely assembled with all panels in place. Provision shall be made to measure the surface
If the transformers are equipped with thermal temperature of iron or alloy parts surrounding
indicators, bushing-type current transformers, or adjacent t o the outlet leads or terminals
and so forth, such devices shall be assembled carrying large currents. Readings shall be taken
with the transformer. at intervals or immediately after shutdown.
The temperature-rise test shall be made in a The determination of the temperature rise
room which is as free from drafts as practicable. of metal parts within the case, other than
It is permissible t o shorten the time required winding conductors, is a design test and shall
for the test by the use of initial overloads, be made when so specified unless a record of
34
ANSI/IEEE
C57.12.91-1979 IEEE STANDARD TEST CODE FOR DRY-TYPE
35
ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS C57.12.91-1979
36
ANSI/IEEE
C5 7.12.91-1979 IEEE STANDARD TEST CODE FOR DRY-TYPE
RATED FREQUENCY
EXC ITAT ION SOU RC E
li
r----
--+P--l
I '
I
SOURCE FOR
IMPEDANCE LOSS
I r"l
Fig 21
Two Single-phase Transformers in Opposition I I
37
ANSI/IEEE
C57.12.91-1979
DISTRIBUTION AND POWER TRANSFORMERS
L------l
Fig 23
A-A Connection for Three Single-phase
Units or One Three-phase Unit
11.6.4 Short-circuit Test: (Separate) Load- 11.6.5 Load-Loss Test Plus Additive Factor.
Loss and Excitation Tests. Temperature tests The total winding rise Tt of a single ventilated
on individual ventilated dry-type units may be dry-type transformer may be calculated by
made by utilizing the rises obtained in two applying an additive factor AT, t o the rise
separate tests, one with load-loss alone and one T,, as outlined in the next paragraph.
with excitation loss alone, and calculating The additive factor ATe is an empirically
winding rises using the following formula: determined temperature difference between
the winding temperature rise obtained by
loading-back test (in accordance with 11.6.1
or 11.6.2) and the winding temperature rise
measured with the load loss only (in accor-
where dance with 11.6.3). It must be established by
test data on units of similar construction.
= total winding rise with full load cur- The total winding rise Tt is given by
Tt
rent in the winding and normal excita-
tion on the core Tt = Tc + ATe
T , = high-voltage or low-voltage winding 11.6.6 Compromise Test Procedure for Sealed
rise measured immediately following or Nonventilated Dry-Type Transformers
the load-loss heat run with full load 11.6.6.1 General Procedure. Conduct an
current flowing in one winding and excitation 1-un until external top surface and
the other winding short-circuited side surfaces of the tank or enclosure stabilize
T, = high-voltage or low-voltage winding rise from a temperature-rise standpoint. Terminate
measured immediately following the the heat run and measure the high-voltage and
heat run with normal excitation on low-voltage winding temperature rises using the
the core procedure described in 11.4. Also measure and
38
ANSI/IEEE
C5 7.12.91-1979 IEEE STANDARD TEST CODE FOR DRY-TYPE
record the average temperature rise over T, = Twm - Tsr, = high-voltage or low-
ambient for the tank o r enclosure surface. voltage winding temperature over
Make a current run maintaining rated current enclosure surface temperature during
in the windings until the surface temperatures current heat run
of the tank or enclosure are again constant. Tst = average enclosure surface temperature
Terminate the current run and determine the during total-loss heat run
winding tempefature rises as described in 11.4.
Also measure and record the average tempera- Tsrt = average enclosure surface temperature
ture rise over ambient for the tank or enclosure rise during total-loss heat run
surface. = Tst - Ta
Then circulate the necessary current in the Twr = high-voltage or low-voltage average
transformer windings to generate a loss equal winding rise by resistance over
to the load loss plus the excitation loss, and ambient temperature
maintain this load until the tank or enclosure = Tsrt + Te + Tc
surfaces are again constant in temperature rise.
Winding rise measurements are not required
for this total-loss run.
From the excitation and current run the
high-voltage winding rise and the low-voltage 12. Short-circuit Tests
winding rise over average surface temperature
is determined, and these values are then added 12.1 Scope. This test code applies t o dry-
t o the average surface temperature rise over type distribution and power transformers
ambient for the total-loss run. The sum of 1 kVA and above. Within the scope, three
these values represents the average winding categories shall be recognized :
temperature rise over ambient for the trans-
I former windings. Single-phase Three-phase
Category (kVA) (kVA)
11.6.6.2 Nomenclature and Equations I 1-500 15-500
I1 501-1667 501-5000
Ta = ambient temperature I11 1668-10000 5001-30000
Tse = average enclosure surface temperature NOTES:
during excitation heat run (1) For autotransformers the category shall be
determined by the equivalent two-winding kVA (as
Tsre average enclosure surface temperature
= defined in ANSI/IEEE C57.12.80-1978).
rise during excitation heat run ( 2 ) All kVA ratings are minimum nameplate kVA
for the principal windings.
= Tse - Ta
Twre = high-voltage or low-voltage winding The code defines a procedure by which the
temperature rise over ambient during mechanical capability of a transformer t o with-
excitation heat run stand short-circuit stresses may be demon-
strated. The prescribed tests are not designed
Te = Twre - Tsre = high-voltage or low- to verify thermal performance. Conformance
voltage winding temperature rise to short-circuit thermal requirements shall be
over enclosure surface temperature by calculation in accordance with ANSI/IEEE
during excitation heat run C57.12.01-1979.
Tsc = average enclosure surface temperature The short-circuit test procedure described
during current heat run herein is for the purpose of establishing that
Tsrc = average enclosure surface temperature the performance of the transformer under test
rise during current heat run meets specification requirements. Tests may
be conducted at manufacturer’s facilities, test
= Tsc - Ta
laboratories, or in the field, but it must be
Twm = high-voltage or low-voltage winding recognized that complete equipment is not
temperature rise over ambient during usually available in the field for conducting
current heat run tests and verifying results.
39
ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS C57.12.91-1979
40
ANSI/IEEE
C57.12.91-1979 IEEE STANDARD TEST CODE FOR DRY-TYPE
41
ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS C57.12.91-1979
12.5 Proof of Satisfactory Performance. The applicable American National Standard product
transfomer under test shall be judged t o have standards.
performed satisfactorily if the visual inspec- 12.5.4 Waveshape of Terminal Voltage and
tion (12.5.1), dielectric tests (12.5.2), and Current. No abrupt changes shall occur in the
temperature test (12.5.3) criteria have been terminal voltage or short-circuit current wave-
satisfactorily met. Recommended terminal shapes during any test.
measurements that may be made during the 12.5.5 Impedance. Impedance measured on
course of the tests but are not required t o be a per-phase basis after the test series shall
made unless specified, are listed in 12.5.4 not differ from that measured before the test
through 12.5.7. If the terminal measurements series by more than the values specified below:
are made and the requirements of 12.5.4 Category I: The allowable variation shall
through 12.5.7 have been met following all be a function of the transformer impedance
tests, it is probable that the transformer has (2,) as follows:
sustained no mechanical damage during the test
2, (per unit) Percentage Variation
series. A composite evaluation of the degree t o
which all criteria of 12.5.4 through 12.5.7 0.0299 or less 22.5 - 500 (2,)
have been met may indicate the need for a 0.0300 or more 7.5
greater or lesser degree of visual inspection t o
confirm satisfactory performance. The evidence Categories I1 or 111: 5 percent allowable for
may be sufficient to permit a judgment of noncircular concentric coils; 2 percent allow-
satisfactory performance t o be made without able variation for circular coils.
complete dielectric tests. A decision to waive The measuring equipment must have the
all or parts of the visual inspection or dielectric demonstrated capability of giving reproducible
test criteria must be based on discussions and readings within an accuracy of f 0.2 percent.
negotiation by all parties involved in specifica- 12.5.6 Low- Voltage Impulse (LVI) Tests.
tion and performance of short-circuit tests. Comparison of oscilloscope traces of LVI cur-
12.5.1 Visual Inspection. Visual inspection rents taken before and after each short-circuit
of the core and coils shall give no indication test shall show no significant change in wave
that there has been any change in mechanical shape. Acceptable conditions and conditions
condition that will impair the function of the requiring further investigation are defined
transformer. The extent of the visual inspec- in 12.5.6.1 and 12.5.6.2.
tion shall be established on the basis of com- 12.5.6.1 Acceptable Conditions
bined evidence obtained from the terminal (1) No LVI trace change occurs during the
measurements described in 12.5.4 through complete test series
12.5.7. If the terminal measurements give no (2) Small changes or amplitude of phase
indication of change in condition, external angle occur following one of the short-circuit
inspection of the core and coils removed from tests, but no further changes occur on subse-
the enclosure or tank may suffice. Any evidence quent tests
of change in condition from more than one of (3) Small changes of amplitude or phase
the terminal measurements would warrant angle occur following one of the short-circuit
disassembly of the windings from the core for tests, but the trace returns t o its original shape
a more detailed inspection. on subsequent tests
12.5.2 Dielectric Tests. The transformer shall 12.5.6.2 Conditions Requiring Further In-
withstand standard applied-voltage and induced- vest igat ion
voltage tests at the full specification level in (1) Large LVI trace changes occur during
accordance with ANSI/IEEE C57.12.01-1979, the course of the test series
or applicable American National Standard (2) Small changes of amplitude or phase
product standards. When impulse tests have angle occur after the first full-amplitude short-
been made prior t o the short-circuit tests, the circuit test, and these changes continue t o grow
impulse tests shall be repeated if specified. with each subsequent test
12.5.3 Temperature Test. The transformer (3) LVI equipment and test procedures3
shall meet the specified average winding tem-
perature rise by resistance values in accor- 3LVI equipment and test procedures will be described
in a new publication now in preparation. See 3.3,
dance with ANSI/IEEE C57.12.01-1979, or footnote 1 , [ 11.
42
ANSI/IEEE
C5 7.12.91-1979 IEEE STANDARD TEST CODE FOR DRY-TYPE
12.5.7 Excitation Current. Excitation cur- Type E, Class I1 performance, or their equal.
rent measured after the test series shall not 13.2.3 Discrete frequency measurements shall
increase above that measured before the test be made when specified o r when test conditions
series by more than 5 percent for stacked- necessitate (See 13.6.1, note.) Instrumentation
type cores. For transformers with wound-core is not presently standardized; however, typical
construction, the increase shall not exceed analyzer bandwidth characteristics deemed
25 percent. The measuring equipment must suitable are one-tenth octave; 1, 3, or 10 per-
have demonstrated capability of giving cent of the selected frequency; or 3, 10, or
reproducible readings with an accuracy of k 0.5 50 Hz.
percent. 13.2.4 A suitable wind screen may be used
12.5.8 Other Diagnostic Measurements. Other where the air velocity due to winds, prevailing
diagnostic measurements may be made during drafts, or microphone locations in the proximity
the course of the tests t o evaluate whether of fans causes the readings to be in error. Suit-
there have been any sudden or progressive able corrections, if necessary, shall be made
changes in the mechanical condition of the for readings with wind screens to ensure that
transformer. Such results may be useful t o the the wind noise effects only are negated.
understanding of the response t o short-circuit
13.3 Test Conditions
forces, but they shall not form part of the
13.3.1 Measurements shall be performed in
proof criteria.
an environment having an ambient level at least
13. Audible Sound-Level Measurements 5 dB, but preferably 10 dB or more, below the
combined level of transformer and ambient
13.1 General. The audible sound generated for the frequency band in which measurements
internally by a transformer is composed of are being made.
discrete tones whose frequencies are even The ambient level shall be established by
multiples of the transformer excitation fre- averaging measurements performed immediately
quency. The audible sound generated by preceding and immediately following the trans-
auxiliary cooling equipment, such as fans, has former tests for at least four microphone loca-
a more broadly and evenly distributed fre- tions spaced equally around the transformer.
quency composition. For an average ambient level 5 dB or more below
The A-weighted measurement characteristic the combined level of transformer and ambient,
best relates how a remote young listener (with the correction shall be applied as follows.
normal hearing) hears the complex transformer-
generated sound and shall be used t o determine
the average sound-level performance of the Difference Correction
transformer. between Average Applied t o Average
For some purposes a frequency distribution Level of Combined Level of Combined
of a transformer’s sound is desirable, and Transformer and Transformer and
when specified, it shall be measured in fre- Ambient and Ambient to Obtain
quency bands (either octave or one-third Average Level Average Level of
octave) or as discrete frequencies, as specified. of Ambient Transformer
13.2 Instrumentation (dB) (dB)
13.2.1 Sound-level measurements shall be 5 -1.6
made with instrumentation that meets the 6 -1.3
requirements of ANSI S1.4-1971 (R 1976), 7 -1.0
Specification for Sound Level Meters, for Type 8 -0.8
2 meters. 9 -0.6
13.2.2 Octave-band or one-third-octave-band 10 -0.4
frequency measurements shall be made, when Over 10 -0.0
specified, with instrumentation that meets
the requirements of ANSI S1.4-1971, for Type
2 meters together with those of ANSI S1.11- Ambient corrections shall be governed by
1966 (R 1976), Specifications for Octave, Half- average level measurements with identical fre-
Octave, and Third-Octave Band Filter Sets, for quency bandwidths for the combined trans-
43
ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS C57.12.91-1979
former and ambient and the ambient alone. straight line perpendicular t o the reference
Where ambient conditions do not comply sound-producing surface at each microphone lo-
with the above, suitable corrections may be cation point. The microphone shall be spaced 1
feasible with steady ambient conditions. The f t (0.30 m) from the reference sound-producing
details and method of making such ambient surface, except that when fans are in operation
corrections shall be determined by those the microphone shall be spaced 6 f t (1.83 m)
responsible for the design and application of from any portion of the transformer coolers
the transformer. cooled by forced air.
Where the difference is less than 5 dB and it 13.4.3 For transformers having an overall
is only desired t o know a level the transformer tank or enclosure height of less than 8 ft
does not exceed, a correction of -1.6 dB may (2.4 m), measurements shall be made at half-
be used. height. For transformers having an overall tank
13.3.2 The transformer shall be located so or enclosure height of 8 f t (2.4 m) or more,
that no acoustically reflecting surface is within measurements shall be made at one-third and
10 ft (3.0 m) of the transformer, other than two-thirds height.
the floor or ground. 13.5 Sound-Level Measurements
13.3.3 The transformer shall be connected 13.5.1 Sound levels shall be measured in con-
for and energized at rated voltage and fre- formance with 13.2.1,13.3,and 13.4 using the
quency at no load, and tests shall be made for sound-level-meter A-weighting characteristic.
the various ratings (AA, AA/FA, AFA, etc)
13.5.2 The average A-weighted sound level is
with fans operating, if appropriate, for the defined as the arithmetic mean of the respec-
rating being tested. tive A-weighted sound-level measurements taken
at each microphone location defined in this
13.4 Microphone Positions section.
13.4.1 The reference sound-producing sur- 13.5.3 When specified, measurements shall
face of a transformer is a vertical surface that also be taken using the sound-level-meter C-
follows the contour of a taut string stretched weighting characteristic.
around the periphery of the transformer or 13.5.4 If ambient conditions necessitate, the
integral enclosure. This contour is to include sound level may be measured using discrete-
coolers, switch compartments, terminal cham- frequency components. (See 13.6.1, note,
bers, etc, but excludes bushings and minor and 13.6.4.)
extensions such as valves, gages, thermometers,
conduit terminal boxes, and projections at or 13.6 Optional Frequency Analysis Measure-
above cover height. ments
In consideration of safety and consistency of 13.6.1 When specified, frequency analyses
measurement, the reference sound-producing shall be made in accordance with 13.2, 13.3,
surface near unenclosed live parts of field- and 13.4 for either octave, one-third-octave,
assembled items such as switches, switchgear, or discrete-frequency measurements. Either the
and terminal compartments or wall-mounted A-weighting, the C-weighting, or the flat re-
bushings, etc, shall be moved outward from the sponse meter characteristic may be used. The
taut string contour such as to be consistent weighting characteristic used shall be reported
with safe worker clearances for the voltage with the data.
class of the live parts termination involved.
NOTE : For a discrete-frequency application, see
13.4.2 The first microphone location point R. T. Hemmes and D. C. Graham, Measurement of Self-
shall coincide with the nameplate. Addit,ional Cooled Transformer Sound Levels in Relatively High
points shall be located at 3 f t (0.91 m) inter- Ambients, ZEEE Transactions on Power Apparatus and
vals, proceeding clockwise in a horizontal Systems, vol PAS-89, Sept/Oct 1970, pp 1657-1662.
direction, as viewed from above, along the
reference sound-producing surface defined 13.6.2 Octave-band or one-third-octave-band
in 13.4.1. frequency analysis measurements shall cover
There shall be no fewer than four microphone the interval of midband frequencies from 63
location points, which may result in intervals through 4000 Hz, inclusive. Discrete-frequency-
of less than 3 ft (0.91 m) for small trans- analysis measurements shall cover the fun-
formers. The microphone shall be located on a damental through the seventh harmonic
44
ANSI/IEEE
C57.12.91-1979 IEEE STANDARD TEST CODE FOR DRY-TYPE
reg = d ( r + p ) 2 + (x -a)' -1
15.3 Efficiency. The efficiency of a trans-
former is the ratio of its useful power output where
to its total power input:
p = power factor of load
output - input - losses q = + dl -p2
Efficiency = 7 -
input input
r =resistance factor of transformer
46
ANSI/IEEE
C57.12.91-1979 IEEE STANDARD TEST CODE FOR DRY-TYPE
47
ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS C57.12.91-1979
Appendix
(?is Appendix is not a part o f ANSI/IEEE C57.12.91-1979, American National Standard Test Code for Dry-Qpe
hstribution and Power Transformers.)
.
..
IEEE Standards of Special Interest
t o the Power Engineer
IEEE Title
Std
85-1973 Test Procedure for Airborne Sound Measurements on Rotating Electric Ma-
chinery
259-1974 Test Procedure for Evaluation of Systems of Insulation for Specialty Trans-
formers
266-1969 Test Procedure for Evaluation of Insulation Systems for Electronics Power
Transformers (Reaff 1975)
346-1973 Definitions in Power Operations Terminology Including Terms for Reporting
and Analyzing Outages of Electrical Transmission and Distribution Facilities
and Interruptions to Customer Service
430-1976 Procedures for the Measurement of Radio Noise from Overhead Power Lines
454-1973 Recommended Practice for the Detection and Measurement of Partial Dis-
charges (Corona) During Dielectric Tests
ANSI C2 National Electrical Safety Code, 1977 edition
ANSI/IEEE
C37.91-1972 Guide for Protection Relay Applications t o Power Transformers
C37.95-1973 Guide for Protective Relaying of Utility Consumer Interconnections
C57.12.00-1980 Standard General Requirements for Liquid Immersed Distribution, Power
and Regulating Transformers (Revision of ANSI/IEEE C57.12.00-1973)
C57.12.01-1979 Standard General Requirements for Dry-Type Distribution and Power Trans-
formers
C57.12.80-1978 Terminology for Power and Distribution Transformers
C57.12.90-1973 Test Code for Distribution, Power and Regulating Transformers
C57.12.90a-1978 Distribution and Power Transformer Short-circuit Test Code (Revision of
ANSI/IEEE C57.12.90a-1974)
C57.12.91-1979 Standard for Dry-Type Transformers
C57.13-1978 Standard Requirements for Instrument Transformers (Revision of ANSI
C57.13-1968)
C57 -98-1968 Guide for Transformer Impulse Tests (Appendix to C57.12.90-1973)
C57.100-1974 Test Procedure for Thermal Evaluation of Oil-Immersed Distribution Trans-
formers
C57.104-1978 Guide for the Detection and Determination of Generated Gases in Oil Im-
mersed Transformers and their Relation to the Serviceability of the Equip-
men t
C57.105-1978 Guide for Application of Transformer Connections in Three-phase Distri-
bution Systems
C57.106-1 977 Guide for Acceptance and Maintenance of Insulating Oil in Equipment
(Revision of IEEE Std 64-1969)