You are on page 1of 49

ANSI/IEEE C57.12.

91-1979

A n American National Standard


IEEE Standard Test Code
for Dry-Type Distribution and
Power Transformers

Sponsor
Transformers Committee of the
IEEE Power Engineering Society

Approved June 16,1978


IEEE Standards Board

Secretariat
Institute of Electrical and Electronics Engineers
National Electrical Manufacturers Association

Approved November 29,1978


American National Standards Institute

Published by
The Institute of Electrical and Electronics Engineers, Inc
345 East 47th Street, New York, NY 10017
American National Standard

An American National Standard implies a consensus of those sub-


stantially concerned with its scope and provisions. An American National
Standard is intended as a guide t o aid the manufacturer, the consumer,
and the general public. The existence of an American National Standard
does not in any respect preclude anyone, whether he has approved the
standard or not, from manufacturing, marketing, purchasing, or using
products, processes, or procedures not conforming t o the standard.
American National Standards are subject to periodic review and users
are cautioned t o obtain the latest editions.
CAUTION NOTICE: This American National Standard may be
revised or withdrawn at any time. The procedures of the American
National Standards Institute require that action be taken t o reaffirm,
revise, or withdraw this standard no later than five years from the
date of publication. Purchasers of American National Standards may
receive current information on all standards by calling or writing the
American National Standards Institute.

@Copyright 1979 by

The Institute of Electrical and Electronics Engineers, Inc

N o part of this publication may be reproduced in any f o r m ,


in an electronic retrieval system o r otherwise,
without the prior written permission o f the publisher.
Foreword

(This Foreword is not a part of ANSI/IEEE C57.12.91-1979, American National Standard Test Code for Dry-Type
Distribution and Power Transformers.)

This standard with its companion standards represents a new milestone in standards for dry-type
transformers, which are becoming increasingly important with the elimination of askarel insulation
in new transformers.
Dry-type transformers have been served in the past by a variety of documents including ANSI/
IEEE C57.12.00-1973, ANSI/IEEE C57.12.90-1973, NEMA TR 27-1965 (R 1971, 1976), and
ANSI/NEMA Pub No ST 20-1972. This standard is the result of an effort encompassing the interests
of users, manufacturers, and others dedicated to produce voluntary consensus standards primarily
for dry-type transformers.
This new series of standards encompasses dry-type transformers with a high voltage of 601 V and
above and includes product standards through 34.5 kV and 7500 kVA (three phase, self-cooled).
These new standards have various and significant changes including higher BILs (for most voltages),
more stringent and meaningful short-circuit requirements, improved descriptions of usual and
unusual service conditions, and numerous other improvements. The arrangement of this new
standard should be easier and more efficient to use since its organization takes account of the
sequence in which information is normally needed. ANSI/IEEE C57.12.91-1979 includes customary
units and adds metric (SI) units in accordance with ANSI policy.
This standard was prepared by the Standards Preparation Working Group of the Dry-Type Trans-
former Subcommittee of the Transformers Committee of the Institute of Electrical and Electronics
Engineers, following which it was approved by the IEEE Dry-Type Transformer Subcommittee, the
IEEE Transformers Committee, the IEEE Standards Board, and the American National Standard
C57 Committee for Distribution and Power Transformers and Regulators. The applicable rules and
procedures of IEEE and'ANSI for the preparation and approval of voluntary consensus standards
were followed. These specify procedures for voting, review, and attempted reconciliation of dis-
senting viewpoints, a sixty day public review period, final review, and approval by the ANSI Board
of Standards Review.
This American National Standard is a voluntary consensus standard. Its use may become manda-
tory only when required by a duly constituted legal authority, or when specified in a contractual
relationship. To meet specialized needs and to allow innovation, specific changes are permissible
when mutually determined by the user and the producer, provided such changes do not violate
existing laws and are considered technically adequate for the function intended.
Suggestions for improvement of this standard will be welcome. They should be sent to:
Secretary
IEEE Standards
The Institute of Electrical and Electronics Engineers, Inc
345 East 47th Street
New York, N.Y. 10017
At the time it approved this standard, C57 had the following membership:
I. H. Koponen, Chairman C . R. Willmore, Secretary
Organization R epresen ted Name of Representative

Bonneville Power Administration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . George w.niff


Electric Light and Power Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R. R. Bast
I. 0. Berkhan
I. H. Koponen
J. P. Markey (Alt)
P. Orehek
B. F. Smith
E. A. Villasuso
Furnance Equipment Manufacturers Association. ... ................... Vacant
Institute of Electrical and Electronics Engineers ........................... S. Bennon
W. P. Burt
J. C. Dutton
D. C. Johnson (Alt)
L. W. Long
D. E. Massey
Naval Facilities Engineering Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Leonard W. Johnson
National Electrical Manufacturers Association . . . . . . . . . . . . . . . . . . . . . . . . . . . . L. C. Aicher
W. R. Courtade
J. W. Dix
J. D. Douglas
W. C. Kendall
G. W. Mayall (Alt)
W. J. McNutt
Norman M. Neagle (Alt)
R. L. Schwab
R. E. Uptegraff, J r
G. C. Wilburn (Alt)
Rural Electrification Administration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . J. C. Arnold, Jr
Tennessee Valley Authority . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L. R. Smith
Underwriters Laboratories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . W. A. Farquhar (Alt)
E. J. Huber
U S . Bureau of Reclamation ........................................ S. J . Baxter

This standard was developed by a Working Group of the Dry-Type Transformer subcommittee of
the IEEE Transformers Committee of the IEEE Power Engineering Society which had the following
membership:
J. C. Dutton, Chairman
R. Bancroft J. Lazzara
W. P. Burt W. A. Muska
H. E. Gabel J. J. Nay
0. R. Hamilton D. E. Shefka
E. J. Huber S. A. Weincek

When this standard was approved June 16, 1978, the IEEE Standards Board had the following
membership :

Joseph L. Koepfinger, Chairman Irvin N. Howell, Jr, Vice Chairman


Ivan G. Easton, Secretary

William E. Andrus Jay Forster Donald T. Michael


C. N. Berglund Ralph I. Hauser Voss A. Moore
Edward J. Cohen Loering M. Johnson William S. Morgan
Warren H. Cook Irving Kolodny Robert L. Pritchard
David B. Dobson William R. Kruesi Blair A. Rowley
R. 0. Duncan Thomas J. Martin Ralph M. Showers
Charles W. Flint John E. May B. W. Whittington
Contents
SECTION PAGE

1. Scope ................................................................. 8
2. Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3. References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4. General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.1 Test Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.2 Test Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.3 Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.4 Testsequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.5 Instrumentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5. Resistance Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.1 Importance of Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.2 Determination of Cold Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.3 Conversion of Resistance Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.4 Resistance Measurement Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
6. Polarity and Phase-Relation Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6.2 Polarity Tests - Single-phase Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6.3 ..................
Polarity and Phase-Relation Tests - Polyphase Transformers 12
7 . RatioTests ............................................................. 14
7.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
7.2 Tolerances for Ratio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
7.3 Ratio Test Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
8. No-Load Losses and Excitation Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8.1 No-Load Losses - General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8.2 Test Methods for Single-phase Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8.3 Test Methods for Three-phase Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
8.4 Excitation Current (No-Load Current) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
9 . Impedance and Load Losses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
9.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
9.2 Impedance and Load-Loss Test Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
9.3 Interlacing Impedance Voltage of a Scott-Connected Transformer . . . . . . . . . . . . . . 25
9.4 Calculation of Impedance Voltage and Load Loss from Test Data . . . . . . . . . . . . . . 25
9.5 Impedance Bridges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
10. Dielectric Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
10.1 Factory Dielectric Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
10.2 Dielectric Tests in the Field . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
10.3 Applied-Voltage Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
10.4 Induced-Voltage Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
10.5 ImpulseTests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
10.6 Impulse Tests on Transformer Neutrals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
10.7 Detection of Failure during Impulse Test ................................. 31
10.8 Insulation-Power-Factor Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
10.9 Insulation-Resistance Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
11. Temperature Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
11.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
11.2 Temperature Test Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

.
SECTION PAGE

11.3 Requirements for Temperature-Rise Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34


11.4 Determination of Average Measured Winding Temperature and
Average Winding Temperature Rise by the Hot-Resistance Method . . . . . . . . . . . . . 35
11.5 Correction Factors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
11.6 Temperature-Rise Test Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
1 2. Short-circuit Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
12.1 Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
12.2 Test Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
12.3 Test Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
12.4 TestProcedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
12.5 Proof of Satisfactorv Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
13. Audible Sound-Level Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
13.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
13.2 Instrumentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
13.3 Test Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
13.4 Microphone Positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
13.5 Sound-Level Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
13.6 Optional Frequency Analysis Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
14. Mechanical Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
14.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
14.2 Components Involved in Lifting or Moving. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
14.3 Tests of Sealed Dry-Type Transformers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
1 5. Calculated Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
15.1 Reference Temperatures for Average Winding Rises ......................... 45
15.2 TotalLosses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
15.3 Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
15.4 Voltage Regulation of a Constant-Voltage Transformer ...................... 46

FIGURES

Fig 1 Connections for the Voltmeter-Ammeter Method of Resistance Measurement. . . . . 10


Fig 2 Polarity by Inductive Kick Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Fig 3 Polarity by Alternating-Voltage Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Fig 4 Transformer Lead Markings and Voltage-PhasorDiagrams for
Three-phase Transformer Connections ................................... 13
Fig 5 Transformer Lead Markings and Voltage-PhasorDiagrams for
Six-Phase Transformer Connections ..................................... 14
Fig 6 Voltmeter Arranged t o Read the Difference between the
Two Secondary Voltages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Fig 7 Voltmeters Arranged to Read the Two Secondary Voltages . . . . . . . . . . . . . . . . . . . 15
Fig 8 Basic Circuit of Ratio Bridge .......................................... 16
Fig 9 Connections for the No-Load-LossTest of a Single-phase Transformer . . . . . . . . . . 17
Fig 1 0 Two-Wattmeter Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Fig 11 Three-Wattmeter Method with Transformer Neutral Available . . . . . . . . . . . . . . . . . 19
Fig 1 2 Three-Wattmeter Method Using Artificial Wattmeter Neutral N . . . . . . . . . . . . . . . . 19
Fig 13 Form-Factor Plot t o Reduce Excitation Current t o Sine-Wave Basis . . . . . . . . . . . . 20
Fig 1 4 Single Phase Transformer Connections for Impedance-Loss and
Impedance-Voltage Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Fig 1 5 Connections for Impedance-Loss and Impedance-Voltage Tests of an
Autotransformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

.
FIGURES PAGE
I
Fig 16 Three-phase Transformer Connections for Impedance-Loss and
Impedance-Voltage Tests Using Three-Wattmeter Method .................... 23
Fig 1 7 Three-phase Transformer Connections for Impedance-Loss and
Impedance-Voltage Tests Using Two-Wattmeter Method ..................... 23
Fig 18 General Impedance Bridge Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Fig 19 Potentiometer-Type Network Using a Phase Shifter . . . . . . . . . . . . . . . . . . . . . . . . . 26
Fig 20 Potentiometer-Type Network Using a Mutual Inductor ....................... 27
Fig 21 Two Single-phase Transformers in Opposition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Fig 22 Two Y-A Connected Transformers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Fig 23 A-A Connection for Three Single-phase Units or One Three Phase Unit . . . . . . . . . . 38

TABLES

Table 1 Measurements to be Made in Insulation Power Factor Tests . . . . . . . . . . . . . . . . . . . 32


Table 2 Empirical Factor for Various Types of Cooling ............................ 36
Table 3 Reference Temperatures for Determining Total Losses. Voltage
Regulation. and Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

Appendix Minimum Information to be Included in Certified Test Data . . . . . . . . . . . . . . . . . . 48

.
An American National Standard
IEEE Standard Test Code
for Dry-Type Distribution and
Power Transformers

1. Scope 3. References

1.1 This standard describes methods for 3.1 Various American National Standards and
performing tests specified in ANSI/IEEE Guides and other standards are listed below.
C57.12.01-1979, General Requirements for When referred to in this standard, references
Dry-Type Distribution and Power Transformers, are identified only by number and year.
and other referenced standards applicable t o (Examples: ANSI/IEEE C57.12.01-1979, IEEE
dry-type distribution and power transformers. Std 1-1969.)
It is intended for use as a basis for perform- 3.2 When the American National Standards
ance, safety, and the proper testing of dry- and Guides referred to in this standard are
type distribution and power transformers. superseded by a revision approved by the
1.2 This standard applies to all dry-type trans- American National Standards Institute, Inc, the
formers except instrument transformers, step- latest revision shall apply.
voltage and induction voltage regulators, arc ANSI/IEEE Std 100-1977, American National
furnace transformers, rectifier transformers, Standard Dictionary of Electrical and Electron-
specialty transformers, and mine transformers. ics Terms.
ANSI/IEEE C5 7.12.01-1979, American National
1.3 When this standard is used on a mandatory
Standard General Requirements for Dry-Type
basis, the words shall and must indicate man-
Distribution and Power Transformers.
datory requirements; the words should or
may refer t o matters that are recommended or ANSI/IEEE C57.12.70-1964 (R 1971), Ameri-
permissive, but not mandatory. can National Standard Terminal Markings and
Connections for Distribution and Power Trans-
NOTE: The Foreword of this voluntary consensus formers.
standard describes the circumstances in which the
standard may be used on a mandatory basis. ANSI/IEEE C5 7.12.80-1978, American National
Standard Terminology for Power and Distribu-
tion Transformers.
ANSI/IEEE C57.98-1968, American National
2. Terminology Standard Guide for Transformer Impulse Tests,
(Appendix t o C57.12.90-1968).
Standard transformer terminology available
in ANSI/IEEE C57.12.80-1978, Terminology ANSI s1.4-1971 (R 1 9 7 6 ) ~American National
for power Distribution Transformers, Standard Specification for Sound Level Meters.
shall apply. Other electrical terms are defined ANSI S1.11-1966 (R 1976), American National
in ANSI/IEEE Std 100-1977, Dictionary of Standard Specifications for Octave, Half-Octave,
Electrical and Electronics Terms. and Third-Octave Band Filter Sets.

8
ANSI/IEEE
c57.12.91-1979 IEEE STANDARD TEST CODE FOR DRY-TYPE

IEEE Std 4-1978, Standard Techniques for 4.5 Instrumentation. Although the figures in
High Voltage Testing. this standard show conventional meters,
IEEE S M 99-1970, Guide for the Preparation adequate digital-readout measuring devices are
of Test Procedures for the Thermal Evaluation considered as satisfactory alternatives.
of Insulation Systems for Electric Equipment.
3.3 Applicable Documents in Preparation’

5. Resistance Measurements
4. General
5.1 Importance of Measurements. Resistance
measurements are of fundamental importance
4.1 Test Definitions. Various types of tests for three purposes:
(“routine, ” “design, ” “other,” and “conform-
(1) For the calculation of the 1 2 R compo-
ance” tests are defined in ANSI/IEEE C57.12.
80-1978. nent of conductor losses
(2) For the calculation of winding tempera-
4.2 Test Requirements. A general summary of tures at the end of a temperature test
test requirements is included in ANSI/IEEE (3) As a base for assessing possible damage in
C57.12.01-1979, Table 7, which indicates by the field
size (500 kVA and smaller, or 500 kVA and
larger) which tests are normally considered as
1
5.2 Determination of Cold Temperature. The
“routine,” “design,” or “other.” cold temperature of the winding shall be
determined as accurately as possible when
4.3 Purpose. The purpose of this standard is measuring the cold resistance. The precautions
to provide test procedure information. Trans- gven in 5.2.1 and 5.2.2 shall be observed.
former requirements and specific test criteria 5.2.1 General. Cold-resistance measurements
are not a part of this standard but are con- shall not be made on a transformer when it is
tained in appropriate American National Stand- located in drafts or when it is located in a room
ards, such as ANSI/IEEE C57.12.01-1979, or in which the temperature is fluctuating rapidly.
in user specifications. 5.2.2 Transformer Windings. The tempera-
ture of the windings shall be recorded as the
4.4 Test Sequence. See 10.1.5.4 for sequence average readings of several thermometers or
of dielectric tests when lightning impulse or thermocouples inserted between the coils, with
switching impulse tests are specified. care used t o see that their measuring points are
NOTE: If it is desired t o minimize potential damage as nearly as possible in actual contact with the
t o the transformer during testing, the resistance, winding conductors. I t should not be assumed
polarity, phase-relation, ratio, no-load-loss and excita-
tion current, impedance, and load-loss tests and that the windings are at the same temperature
temperature-rise tests (when applicable) should precede as the surrounding air.
dielectric tests. When this sequence is used, the 5.2.2.1 The temperature of the windings
beginning tests involve voltages and currents that are
usually reduced compared t o rated values, thus tending
may be considered equal t o the ambient air
to minimize damaging effects t o the transformer. temperature provided the transformer has been
in a draft-free area for 24 hours and provided
When the following documents are completed, ap- that neither voltage nor current has been applied
proved and published, they become a part of this
listing. to it for 24 to 72 hours, depending on size.
[ 11 Distribution and Power Transformer Short- 5.3 Conversion of Resistance Measurements.
Circuit Test Guide. (To be published in the ANSI C57 Cold winding resistance measurements are
Series.)
[ 21 Requirements for Ventilated Dry-Type Distribu-
normally converted to a standard reference
tion Transformers, 1 to 500 kVA, Single-phase; and 1 5 temperature equal to rated average winding
t o 500 kVA, Three-phase; with High-Voltage 2400- temperature rise plus 2OoC. In addition, it may
34 500 Volts, C57.12.50. be necessary to convert the resistance measure-
[ 3 ] Requirements for Ventilated Dry-Type Power
Transformers, 501 kVA and Larger, Three-phase, with merits to the temperature at which the
High-Voltage 2400-34 500 Volts. C57.12.51. imDedance-loss measurements were made, The
f4 ] ReqGirements for Sealed Dry-Type Power Trans- conversions =e accomplished by the following
formers, 501 kVA and Larger, Three-phase; with High-
Voltage 2400-34 500 Volts, C57.12.52. formula:

9
ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS C57.12.91-1979

5.4.2 Voltmeter-Ammeter Method. The volt-


meter-ammeter method is sometimes more
convenient than the bridge method. It should
be employed only if the rated current of the
transformer winding is 1 ampere or more.
where Digital voltmeters and digital ammeters of
appropriate accuracy are commonly used in
Rs = resistance at desired temperature T, connection with temperature-rise determina-
Rm = measured resistance tions.
T, = desired reference temperature
5.4.2.1 Measurement is made with direct
current, and simultaneous readings of current
T, = temperature at which resistance was and voltage are taken using the connections of
measured Fig 1. The required resistance is calculated
Tk = 234.5 for copper from the readings in accordance with Ohm's
Tk = 225 for aluminum, EC law. A battery or filtered rectifier will generally
be found t o be more satisfactory as a dc source
NOTE: The value of Tk may be as high as 230 for than will a commutating machine. The latter
alloyed aluminum. may cause the voltmeter pointer to vibrate
5.4 Resistance Measurement Methods because of voltage ripple.
5.4.1 Bridge Method. Bridge methods (or
5.4.2.2 In order to minimize errors of
high-accuracy digtal instrumentation) are
observation:
generally preferred because of their accuracy
(1) The measuring instruments shall have
and convenience, since they may be employed
such ranges as will give reasonably large indica-
for the measurement of resistances up t o
tion.
10 000 C l . They should be used in cases where
(2) The polarity of the core magnetization
the rated current of the transformer winding t o
shall be kept constant during all resistance
be measured is less than 1ampere.
readings.

a
NOTE: For resistance values of 1 or more a Wheat- NOTE: A reversal in magnetization of the core can
stone bridge (or equivalent) is commonly used; for change the time constant and result in erroneous
values less than 1 0 a Kelvin bridge (or equivalent) is readings.
commonly used. Some modern resistance bridges have
capability in both ranges.

Fig 1
Connections for the Voltmeter-Ammeter Method of Resistance Measurement

10
AN SI/ IEEE
C57.12.9 1-197 9 IEEE STANDARD TEST CODE FOR DRY-TYPE

5.4.2.3 The voltmeter leads shall be in-


dependent of the current leads and shall be
connected as closely as possible t o the termi- 6. Polarity and Phase-Relation Tests
nals of the winding to be measured. This is t o
avoid including in the reading the resistances of 6.1 General. Polarity and phase-relation tests
current-carrying leads and their contacts and of are of interest primarily because of their bear-
extra lengths of leads. ing on paralleling or banking two or more
To protect the voltmeter from injury by transformers. Phase-relation tests are made t o
off-scale deflections, the voltmeter should be determine angular displacement and relative
disconnected from the circuit before the cur- phase sequence.
rent is switched on or off. To protect test
personnel from “inductive kick,” the current 6.2 Polarity Tests -. Single-phase Transformers
should be switched off by a suitably insulated 6.2.1 Polarity Tests. Polarity tests on single-
switch. phase transformers are commonly made in
If the drop of voltage is less than 1 volt, a accordance with one of the following methods:
potentiometer or millivoltmeter shall be used. (1) Inductive kick
(2) Alternating voltage
5.4.2.4 Readings shall not be taken until ( 3 ) Comparison
after the current and voltage have reached (4) Ratio bridge
steady-state values. 6.2.2 Polarity by Inductive Kick. The polar-
When measuring the cold resistance prepara- ity of transformers with leads arranged as
tory to making a heat run, the time required shown in Fig 2, A and B, may be determined
for the readings t o become constant should be at the time of making the resistance measure-
noted. The period thereby determined should ments as follows:
be allowed to elapse before taking the first (1) With direct current passing through the
reading when final winding hot-resistance high-voltage winding, connect a high-voltage
measurements are being made. direct-current voltmeter across the high-voltage
In general, the winding will exhibit a long dc winding terminals so as to get a small deflec-
time constant. To reduce the time required tion of the pointer.
for the current to reach its steady-state value, (2) Transfer the voltmeter lead connected
a noninductive external resistor should be t o H, t o XI and that connected t o H, t o X 2 .
added in series with the dc source. The resis-
tance should be large compared to the induc-
tance of the winding. It will then benecessary
to increase the source voltage t o compensate
for the voltage drop in the series resistor. The Fig 2
time will also be reduced by operating all Polarity by Inductive Kick Test
other transformer windings open circuited
during the tests.
xi-x2
5.4.2.5 Readings shall be taken with not
less than four values of current when deflect-

I_
ing instruments are used. The average of the
resistances calculated from these measurements
shall be considered to be the resistance of the
circuit.
The current used shall not exceed 15 percent
of the rated current of the winding whose
resistance is to be measured. Larger values may
cause inaccuracy by heating the winding and
X I -x2
thereby changing its temperature and resistance.
If the current is too low to be read on a
deflecting ammeter, a shunt and digital milli-
voltmeter or potentiometer shall be used. A B

11
~

ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS C57.12.91-1979

(3) Break direct-current excitation, thereby


inducing a voltage in the low-voltage winding -SOURCE-
(inductive kick) that will cause a deflection in
the voltmeter, which is interpreted in (4)
and (5) below.
(4) If the pointer swings in the opposite OHI Hz o
direction (negative), the polarity is subtractive.
(5) If the pointer swings in the same direc- xi x 2
tion as before (positive),the polarity is additive.
6.2.3 Polarity by Alternating- Voltage Test.
For transformers having a ratio of transforma-
tion of 30 t o 1 or less, the H, lead shall be con-
nected to the adjacent low-voltage lead. (In
Fig 3, this will be X,.) Any convenient value
of alternating voltage shall be applied t o the
full high-voltage winding and readings taken of
the applied voltage and the voltage between
the right-hand adjacent high-voltage and low-
voltage leads.
If the latter reading is greater than the former,
the polarity is additive.
If the latter voltage reading is less than the
former (indicating the approximate difference
in voltage between that of the high-voltage and
low-voltage windings), the polarity is subtrac-
tive.
6.2.4 Polarity by Comparison. When a trans-
former of known polarity and of the same
ratio as the unit under test is available, the
polarity can be checked by comparison, as
follows, similar to the comparison method
used for the ratio test. (See Figs 6 and 7.)
(1) Connect the high-voltage windings of
both transformers in parallel by connecting
similarly marked leads together.
(2) Connect also the low-voltage leads, X,,
of both transformers together, leaving the X,
leads free.
( 3 ) With these connections, apply a reduced
value of voltage to the high-voltage windings
and measure the voltage between the two free
leads.
A zero or negligble reading of the voltmeter
will indicate that the relative polarities of both
transformers are identical.
An alternative method of checking the
polarity is to substitute a low-rated fuse or
suitable lamps for the voltmeter.
This procedure is recommended as a precau-
tionary measure before connecting the volt-
meter.
6.2.5 Polarity by Ratio Bridge. The ratio
bridge described in Section 7 can also be used
t o test polarity.

12
ANSI/IEEE
C57.12.91-1979 IEEE STANDARD TEST CODE FOR DRY-TYPE

X, the lead that was connected t o H,, con- phase neutral is available, the phase-sequence
I
necting t o X2 the lead that was connected t o indicator leads should be transferred from H,
H,, and connecting t o X, the lead that was t o X,, from H, t o X,, from H, t o X,,respec-
connected t o H,. tively, and the direction of rotation noted. The
The transformer is again excited at a suitable tests should then be repeated by transferring
voltage (without changing the excitation con- from H, t o X,, from H, t o X4,and from H3
nections) and the indication again noted. t o X,, respectively, and noting the indication,
The phase sequence of the transformer is which should be the same as before.
correct if the indication is the same in both 6.3.3.1 The preceding method (phase-
cases. sequence test) does not disclose the angular
Six-phase secondaries, having no neutral con- displacement of the transformer.
nection, have to be connected temporarily in 6.3.3.2 The ratio bridge described in Sec-
delta (A) or wye ( Y ) for this test also. If a six- tion 7 can also be used t o test phase-sequence.

Fig 4
Transformer Lead Markings and Voltage-Phasor Diagrams for
Three-phase Transformer Connections

ANGULAR DIAGRAM FOR CHECK


ld E ASU RE M E NT
CHECK MEASUREMENTS
DISPLACEMENT

H2 x2

GROUP I
ANGULAR DELTA- DELTA CONNECTION
)I S P L ACE M E N T
0 DEGREES

Y - Y CONNECTION

HI ff3

DELTA-Y CONNECTION

GROUP 2
Af4GIJLAR
>ISPLACEMENT
30 DEGREES
Y-DELTA CONNECTION
-
TtiREE PHASE TRAP ;FORMERS WITH TAPS

$;9y2
x6 x3
ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS C57.12.9 1 - 1979

7.1.2 The ratio test shall be made at rated


7. Ratio Tests or lower voltage and rated or higher frequency.
7.1.3 In the case of three-phase transformers
when each phase is independent and accessible,
7.1 General. The turn ratio of a transformer single-phase power should preferably be used,
is the ratio of the number of turns in the high- although when convenient, three-phase power
voltage winding to that in the low-voltage may be used.
winding. 7.1.4 Transformers that have Y-diametric
7.1.1 When a transformer has taps for chang- connections but do not have the neutral of the
ing its voltage ratio, the turn ratio is based on Y brought out shall be tested for ratio with
the number of turns corresponding t o the three-phase power. Any inequality in the
normal rated voltage of the respective windings magnetizing characteristics of the three phases
to which operating and performance character- will then result in a shift of the neutral, thereby
istics are referred. causing unequal diametric voltages. When such
If the transformer has taps, the turn ratio inequality is found, the diametric connection
shall be determined for all taps as well as for should be changed t o either A or Y connection
the full winding. and the line voltages measured. If these are

Fig 5
Transformer Lead Markings and Voltage-Phasor Diagrams
for Six-Phase Transformer Connections
ANSI/IEEE
C57.12.91-1979 IEEE STANDARD TEST CODE FOR DRY-TYPE

found to be equal to each other and of proper


value (1.73 times the diametric voltages if
connected in Y), the ratio is correct.
7.2 Tolerances for Ratio. See ANSI/IEEE C57.
12.01-1979, Section 9.

7.3 Ratio Test Methods


7.3.1 Voltmeter Method. Two voltmeters
shall be used (with voltage transformers if
necessary), one t o read the voltage of the high-
voltage winding, the other that of the low-
voltage winding. The two voltmeters shall be
read simultaneously.
A second set of readings shall be taken with
the instruments interchanged, and the average
of the two sets of readings taken to compensate
for instrument errors.
Fig 6
Voltage transformer ratios should be such as
Voltmeter Arranged to Read the Difference
to yield about the same readings on the two
between the Two Secondary Voltages
voltmeters; otherwise compensation for instru-
ment errors by an interchange of instruments
will not, be satisfactory, and it will be necessary
to apply appropriate corrections to the volt-
meter readings.
Tests shall be made at not less than four
voltages in approximately 1 0 percent steps,
and the average result shall be taken as the true
value. These several values should check within
1 percent. Otherwise, the tests shall be repeated
with other voltmeters.
If appropriate corrections are applied to the
voltmeter readings, tests may be made at only
one voltage.
When several transformers of duplicate rating
are to be tested, work may be expedited by
applying the foregoing tests to only one unit
and then comparing the other units with this
one as a standard, in accordance with the (Readings are repeated after interchanging
comparison transformer method discussed voltmeters.)
in 7.3.2.
7.3.2 Comparison Method. A convenient Fig 7
method of measuring the ratio of a transformer Voltmeters Arranged t o Read the Two
is by comparison with a transformer of known Secondary Voltages
ratio.
The transformer to be tested is excited in
parallel with a transformer of the same nominal
ratio, and the two secondaries are connected
in parallel but with a voltmeter or detector in 7.3.2.1 For an alternate method the trans-
the connection between two terminals of similar former t o be tested is excited in parallel with
polarity (Fig 6). This is the more accurate a transformer of known ratio, and the volt-
method because the voltmeter or detector indi- meters are arranged t o measure the two secon-
cates the difference in voltage. dary voltages (Fig 7).

15
ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS C57.12.91-1979

Peaked voltage waves (form factor greater


TRANSFORMER
than l.ll),resulting generally from the dis-
_ _ - <UNDER TEST torted character of the excitation-current load
I
of the transformer on the test generator, give
smaller no-load losses than a sine-wave voltage.
Flat-topped waves, rarely encountered in
such tests, give larger no-load losses than a
sine-wave voltage.
Ordinary variations of temperature do not
influence no-load losses materially, and no
I I correction for temperature variation is made.
1 HZ
I
The no-load loss determination shall be based
on a sine-wave voltage, unless a different wave
form is specified for the operation of the
Fig 8 transformer.
Basic Circuit of Ratio Bridge 8.2 Test Methods for Single-phase Transform-
ers. One of the three methods given in 8.2.1
through 8.2.3 shall be used for correcting the
The voltmeters shall be interchanged and measured no-load losses to a sine-wave-voltage
the test repeated. The averages of the results basis for single-phase transformers.
are the correct voltages.
7.3.3 Ratio Bridge. A bridge using the basic 8.2.1 Average- VoZtage Voltmeter Method.
circuit of Fig 8 may be used to measure ratio. The average-voltage voltmeter method is the
most accurate method and is recommended.
7.3.3.1 When detector DET is in balance, The hysteresis loss portion of the no-load loss
the transformer ratio = R / R . is a function of the maximum flux density in
the core, independent of the wave shape of the
NOTES:
( 1 ) Measurement of ratio using circuits o f this type flux. The maximum flux density corresponds
has also (in the past) been described as “ratio by t o the average value of the voltage (not t o the
resistance potentiometer. ” rms value), and therefore, if the average value
( 2 ) More accurate results can be obtained using a
ratio bridge that provides phase-angle correction. of the test voltage is adjusted to be the same
( 3 ) The ratio bridge can also be used t o test polarity, as the average value of the desired sine wave
phase relation, and phase sequence. of voltage, and the proper frequency held,
the hysteresis loss will be the desired sine-wave
value.
NOTE: If the flux wave has more than one maximum
8. No-Load Losses and Excitation Current and one minimum value per cycle, average voltmeter
readings will not be correct, but the voltage wave then
8.1 No-Load Losses General. No-load losses
--”
is not suitable for use.
(excitation losses) are the losses of a trans-
former that is excited at rated voltage and fre-
quency, but which is not supplying load. The average-voltage voltmeter method utilizes
No-load losses include core loss, dielectric loss, an average-voltage-indicating voltmeter consist-
and loss in the windings due to exciting current. ing of a d’Arsonval voltmeter having in series
The no-load loss of a transformer consists with itself a full-wave rectifier. These instru-
principally of the iron loss in the transformer ments are generally graduated t o give the same
core and is a function of the magnitude, numerical indication as an rms voltmeter on
frequency, and wave shape of the impressed sine-wave voltage, that is, they are marked in
voltage, equivalent sine-wave rms values.
The no-load loss and current are particularly NOTE : The temperature error of an average-reading
sensitive to differences in wave shape, and voltmeter utilizing a rectifier (especially instruments
therefore, no-load-loss measurements will vary for less than 7 5 V ) is likely t o be greater than that of
rms voltmeters; therefore, the temperature characteris-
markedly with the wave shape of the test tic of such an instrument should be ascertained for
voltage. dependable results and a suitable correction applied.

16
ANSI/IEEE
C5 7.12.91-19 79 IEEE STANDARD TEST CODE FOR DRY-TYPE

t I
SOURCE G?

T VOLTAGE
TRANS FORM ER

SOURCE

I I I I

NOTE: F = frequency meter; AV = average-voltage


voltmeter.

Fig 9
Connections for the No-Load-Loss Test of a
Single-phase Transformer: A - Without
Instrument Transformers. B - - With Instrument
Transformers

Figure 9A shows the necessary equipment use safe. When such multipliers are used, they
and connections when no instrument trans- shall be calibrated with the instruments.
formers are needed; Fig 9B when they are Low-power-factor wattmeters shall be used
needed, which is the general case. As indicated to obtain accurate results.
in Fig 9A, the voltmeters should be connected Either the high- or the low-voltage winding
nearest t o the load, the ammeter nearest to the of the transformer under test may be used, but
supply, and the wattmeter between the two it is generally more convenient t o make this
with its voltage coil on the load side of the test using the low-voltage winding. In any case,
current coil. the full winding (not merely a portion of the
Large transformers are not suitable for use as winding) should be used if possible. If for some
instrument transformers, since they introduce unusual reason only a portion of a winding is
losses as voltage transformers, and large ratio excited, this portion shall be not less than 25
and phase errors as current transformers. percent of the winding.
Transformers used for measuring no-load Adjust the frequency t o the desired value as
losses shall be instrument transformers. indicated by the frequency meter, and the
Resistance multipliers may be used in series voltage t o the desired value by the average-
with the voltage coil of instruments instead of voltage voltmeter. Record the simultaneous
voltage transformers if desired, provided values of frequency, rms voltage, watts, average-
suitable precautions are taken to make their voltage voltmeter readings, and amperes. Then

17
ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS C5 7.12.9 1-19 79

disconnect the transformer under test and read instrument is graduated in volts and calibrated
the losses on the wattmeter, which represent on a sine wave of voltage.
the losses of the connected instruments (and The principle of this instrument is based on a
voltage transformer if used), and which is t o be comparison of the losses in its reference core
subtracted from the earlier wattmeter reading when excited from a circuit having a sine wave,
to obtain the no-load loss of the transformer with its losses when excited from the source of
under test. excitation for the transformer under test. If
The correct no-load loss of the transformer these losses are unlike for the same rms voltage,
shall be determined from the measured value it is obvious that the wave form of the proposed
by means of the following equation: test voltage deviates from a sine wave. By
adjusting the value of the test voltage until the
loss in the core is the same as when excited
Pl + kP2 from a circuit having a sine-wave voltage of the
desired value, the measurement of the no-load
loss of the transformer under test is placed on a
where sine-wave basis.
The circuit is arranged as in Fig 9A or 9B, the
P = no-load loss (watts) at voltage Ea iron-loss voltmeter replacing the average-voltage
corrected to a sine-wave basis voltmeter. The voltage of the circuit is then
Pm = no-load loss measured in test adjusted by any convenient means until the
iron-loss voltmeter indicates the desired test
P, = per-unit hysteresis loss, referred to Pm
voltage. Then, the losses of the transformer
P, = per-unit eddy-current loss, referred to under test, like the losses of the core in the
pm iron-loss voltmeter, correspond substantially t o
a sine-wave voltage of the indicated magnitude
k =
(%), and frequency.
It is necessary t o verify that the core material
E, = test voltage measured by rms voltage of the iron-loss voltmeter is representative of
Ea = test voltage measured by average- the core material of the transformers to be
voltage voltmeter tested.
If a voltage transformer is used, its rating
The actual per-unit values of hysteresis and should be large enough so that the burden of
eddy current losses should be used, if available. the iron-loss voltmeter does not materially
change its ratio or phase angle or wave shape.
NOTE: If actual values are not available, it is sug-
gested that these two loss components be assumed 8.2.3 Standard Core Method. The standard
equal in value, assigning each a value of 0.5 per unit. core is a miniature representative sample of the
transformers to be tested. Its no-load loss is
The eddy-current loss in the core varies with accurately determined previously with a sine
the square of the rms value of the excitation wave of applied voltage over a wide range of
voltage and is substantially independent of the flux density on each of the several taps of its
voltage wave shape. When the test voltage is winding; the flux density in any transformer
held at rated voltage with the average-voltage under test can thus be closely approximated.
voltmeter, the actual rms value of the test The sample core is usually supplied from a
voltage may not be the rated value, and the voltage transformer that is connected in
eddy-current loss in the test will be related t o multiple with the transformer under test; the
the correct eddy-current loss at rated voltage losses of the sample and of the transformer are
by the equations. determined at the rated voltage of the trans-
8.2.2 Iron-Loss Voltmeter Method. The iron- former.
loss voltmeter is essentially a wattmeter The ratio between the loss of the sample with
measuring the excitation loss in a small self- a sine wave of applied voltage of the same
contained laminated core of silicon steel. The effective value (read from a curve) and the loss
excitation winding of this core is in series with with the actual test voltage applied constitute
the stationary coil of the wattmeter. The the necessary multiplier for the measured
ANSI/IEEE
C5 7.12.9 1-1979 IEEE STANDARD TEST CODE FOR DRY-TYPE

q
-
1 I

W
0
iiz
TOTAL LOSS
TOTAL LOSS
PI - p2

I I J

Fig 10
Two-Wattmeter Method Fig 11
Three-Wattmeter Method with Transformer
Neutral Available
excitation loss of the transformer under test
to correct it to a sine-wave basis. This method
ordinarily is not suitable for field work.
It is necessary t o verify that the core material
of the standard core is representative of the
core material of the transformer t o be tested.
If a voltage transformer is used, its rating
should be large enough so that the burden of
the standard core does not materially change TOTAL LOSS
P, + P2 + P3
its ratio or phase angle or wave shape.
8.3 Test Methods for Three-phase Trans-
formers. The methods described for single- Fig 12
phase transformers also apply to three-phase Three-Wattmeter Method Using Artificial
transformers with the additions and modifica- Wattmeter Neutral N
tions given in 8.3.1 through 8.3.4.
8.3.1 In measuring the core loss of three-
phase transformers with two wattmeters connected from one line to the three-phase
(Fig lo), three entirely separate sets of readings neutral, when available (Fig 11). The three
shall be taken by using each of the three lines readings are added t o obtain the no-load loss.
in succession as the common line. The average 8.3.3 If the three-phase neutral is not avail-
value of the three sets of readings shall be able, an artificial neutral may be derived
recorded as the true no-load loss. (Fig 12). If voltage transformers are neces-
8.3.2 In using the two-wattmeter method, s a r y , an open A-connection should be used to
great care should be exercised in reading the supply the Y -connected wattmeters.
wattmeters accurately. Because of the low 8.3.4 The impedance bridge method may be
power factor, the reading of one wattmeter will used as an alternate to the wattmeter method
be negative and must be subtracted from the for the measurement of no-load losses provided
other. The two readings may be of the same that the applied excitation voltage is sufficiently
general order of magnitude, so that slight close to a sine wave. Each major harmonic
inaccuracies in their values may lead to large should not exceed 0.5 percent of the funda-
percentage errors in their small difference. mental unless acceptable corrections are applied
Under such difficult conditions greater ac- to the measurement.
curacy may be obtained by the alternative The impedance bridge method is advantageous
procedure given in 8.3.2.1. for low-power-factor measurements where
8.3.2.1 Measurements may be made with special wattmeters and techniques are ordinarily
three wattmeters, each voltage circuit being required.

19
ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS C57.12.91-1979

8.3.4.1 Impedance Bridge Networks. While


many configurations of impedance bridge net-
works are possible, the choice of a particular
network shall be determined by the measure-
ment problem at hand and the testing facilities
available. See 9.5.
8.4 Excitation Current (No-Load Current). The
excitation current of a transformer is the
current that maintains the magnetic flux excita-
tion in the core of the transformer.
NOTE: It is usually expressed per unit o r in percent
of the rated current of the winding in which it is FS FI
measured.
NOTE: I , , I2 = exciting currents at form factors
8.4.1 Excitation Current Test. Circuit con- F1, F 2 .
nections for the measurement of excitation
current shall be the same as those for the Fig 13
measurement of the excitation loss. The Form-Factor Plot to Reduce Excitation
different methods of measurement, based on Current t o Sine-Wave Basis (Is,F , )
the instruments used, shall be as given in 8.4.2
through 8.4.4. This is the most accurate method of measure-
8.4.2 R M S Voltmeter and Ammeter. Mea- ment when waves of sufficiently different form
surements of excitation current are ordinarily factor are available to provide effective ex-
made with rms voltmeters and ammeters. trapolation (Fig 13).
This method of measurement is reasonably Excitation current is measured with an rms
accurate only when the applied voltage is ammeter at two or more applied voltages
practically of sine-wave form. having different form factors but held at the
In cases where the voltage wave shape departs same value with an average-voltage voltmeter,
appreciably from a sine wave, as when a trans- such as is used for the reduction of excitation
former is large in rating compared with the loss t o a sine-wave basis.
generator used for test, the excitation current
will be lower in value than that obtained with Form factors may be varied conveniently by
a sine wave of applied voltage. The value so changing the excitation of the generator field
obtained shall be corrected to a sine-wave basis. or by inserting an impedance in the test circuit.
8.4.3 Average- Voltage Voltmeter and RMS Form factors may be determined by taking
Ammeter. When an average-voltage voltmeter simultaneous voltage readings with rms and
average-voltage voltmeters; their values will be
and an rms ammeter are used, the measured
indicated by the ratio of the rms reading t o the
rms value of excitation current will generally
be higher than that obtained with a sine wave average-voltage voltmeter reading.
of voltage when the voltage wave shape departs The excitation current ( I s ) corresponding to
appreciably from a sine wave. sine-wave voltage shall be determined from the
When the value obtained by this method is foregoing data by the following equation:
within the guaranteed limits, no correction is
required.
The measurement of the excitation current
shall, when necessary, be corrected to a sine-
wave basis by one of the methods given where I , and I , are the rms currents corre-
in 8.4.3.1 and 8.4.3.2. sponding, respectively, to the form factors
8.4.3.1 Form-Factor Method. This method F , and F , .
is based on the fact that a substantially straight 8.4.3.2 Crest-Ammeter Method. In the
line relation exists between the rms value of crest-ammeter method, use is made of an
the excitation current and the form factor of average-voltage voltmeter (the same instrument
the applied-voltage wave over a wide range of used for the reduction of excitation loss to a
form factors. sine-wave basis) and a crest ammeter for read-

20
ANSI/IEEE
C57.12.91-1979 IEEE STANDARD TEST CODE FOR DRY-TYPE

ing the instantaneous maximum value of the in the test made according t o 8.4.3 do not differ
corresponding currents. by more than 10 percent, the excitation cur-
Simultaneous readings are taken on these rent on a sine-wave basis shall be taken as the
two instruments at 100 percent, 86.6 percent, average of the values obtained by the tests
and 50 percent voltage. These data determine described in 8.4.2 and 8.4.3.
approximately the fundamental, third, and
fifth harmonics of the excitation current.
The excitation current (Is)corresponding t o 9. Impedance and Load Losses
sine-wave voltage shall be determined from the
foregoing data by the following equation: 9.1 General. Load losses are those losses in
a transformer that are incident t o the carrying
of the load.
NOTE: Load losses include Z2R loss in the windings
due t o load current; stray loss due to stray fluxes in
in which I , , I,, and I , are the instantaneous the windings, core clamps, magnetic shields, enclosure
or tank walls, etc, and also to circulating currents, if
maximum values of excitation current corre- any, in parallel windings.
sponding to excitation voltages of 100 percent,
88.6 percent, and 50 percent of rated voltage. 9.1.1 Impedance Voltage. The impedance
This method applies not only t o single-phase voltage comprises an effective resistive com-
transformers but, in a slightly modified form, ponent corresponding to the load losses, and a
also to those three-phase transformers that reactive component corresponding t o the
are free from large third-harmonic voltages, leakage-flux linkages of the windings.
that is, in practice, the transformers having It is not practical to measure these compo-
one or more A-windings or those having a nents separately, but after the total impedance
three-legged, three-phase core. loss and total impedance voltage are measured,
Readings are obtained as indicated in the the components may be separated by calculation.
preceding paragraphs, but now the line current The voltage required t o circulate the rated
consists of only the fundamental and the fifth- current under short-circuit conditions when
harmonic components of the required ampere- connected on the rated voltage tap is the
turn excitation. impedance voltage, and the watt loss measured
Since only two important components are is the load loss.
present, only two readings are necessary (II at The impedance voltage generally falls between
100 percent excitation voltage and I, at 86.6 3 percent and 15 percent of the rated voltage
percent voltage), and the excitation current of the excited winding, and this fact may be
( I s )corresponding t o sine-wave voltages may be used as a guide in planning for the voltage
determined by the following equation: suppl9 for the impedance test.
NOTE: The “load loss” is sometimes referred to as
Is = 4 0 . 2 5 1 ; + 0.3381: the “impedance loss.”

9.1.2 Impedance kVA. Impedance kVA is


8.4.4 Average Method. When the voltage the kVA measured in the primary, with the
wave shape is not too distorted, the following secondary short-circuited and with sufficient
simplified method may be used. This method is voltage applied t o the primary t o cause rated
based on the fact that the value of excitation current t o flow in the windings.
current obtained is too low when an rms
voltmeter is used (see 8.4.2) and too high when 9.2 Impedance and Load-Loss Test Procedures
an average-voltage voltmeter is used (see 8.4.3). 9.2.1 Preparation
The procedure is as follows: (1) The temperature of the windings shall be
(1) Determine the excitation current as taken immediately before and after the im-
in 8.4.2. pedance measurements in a manner similar t o
(2) Determine the excitation current as that described in 5.2. The average shall be
in 8.4.3, reading also the rms voltage. taken as the true temperature.
(3) If the reading of rms voltage and the (2) Conductors used for short-circuiting low-
average-voltage voltmeter reading of voltage voltage highcurrent transformers should have

21
ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS C57.12.91-1979

a cross section equal to, or greater than, the It is sufficient t o measure and adjust the
corresponding transformer leads. They should current in the excited winding only because
be as short as possible and should be kept the current in the short-circuited winding will
away from magnetic masses. Contacts should be the correct value (except for a negligible
be clean and tight. excitation-current error) when the current in
NOTE: The accuracy of impedance-voltage measure- the excited winding is correct. To introduce
ments is improved by using short-circuiting connec- measuring equipment in series with the short-
tions with a resistance that is low relative t o the circuited winding t o measure its current may
resistance of the winding being short-circuited.
introduce a greater error into the impedance
(3) These precautions are of importance in data owing to the losses and voltage drop of
avoiding extraneous impedance voltage and that equipment.
losses that might otherwise be introduced into 9.2.3 Impedance Test of Autotransformer
the measurements. (1) An autotransformer may be tested for
9.2.2 Impedance Test of Single-phase Trans- impedance with its internal connections un-
former. One of the two windings of the trans- changed. The test is made by short-circuiting
former (either the high-voltage winding or the its input (or output) terminals and applying
low-voltage winding) is short-circuited, and voltage t o the other terminals t o cause its
voltage at rated frequency is applied t o the appropriate rated line current to flow, the
other winding and adjusted t o circulate rated external connections being as in Fig 15.
currents in the windings (Fig 14). (2) The series and common windings of the
With the current and frequency adjusted t o autotransformer may be treated as separate
the rated values as nearly as possible, simulta- windings, one being short-circuited, the other
neous readings should be taken on the ammeter, excited, for the impedance test.
voltmeter, wattmeter, and frequency meter. When this procedure is followed, the current
The transformer under test should then be held must be the rated current of the exciting
disconnected and tare readings taken on the winding, which may or may not be the same as
wattmeter, representing the losses of the mea- the line current indicated in preceding para-
suring equipment, similar to the procedure in graphs.
the no-load-loss test. With the foregoing precaution followed, the
impedance watts and volt-amperes will be the
same by either method (1) or (2).
Fig 14 The impedance voltage measured across the
Single-phase Transformer Connections for series winding will correspond t o that between
Impedance-Loss and Impedance-Voltage the high-voltage terminals of the autotrans-
Tests former, while the impedance voltage measured

(Instrument transformers t o be added when Fig 15


necessary .) Connections for Impedance-Loss and
Impedance-Voltage Tests of an
Autotransformer

22
ANSI/IEEE
C5 7.1 2.91-1979 IEEE STANDARD TEST CODE FOR DRY-TYPE

POWER
SOURCE
b T
VOLTS C A N
BE READ:
A N , E N , CN -
OR
A B , B C , CA
C
CCI
N&.C -/ TRANS FORM ER
UNDER TEST
(FOR ANY A O R Y
COMBINATION)

VT

Fig 16
Three-phase Transformer Connections for Impedance-Loss and
Impedance-Voltage Tests Using Three-Wattmeter Method

across the common winding will correspond t o ( 2 ) Two-Wattmeter Connection (Alternate).


that between the low-voltage terminals of the See Fig 17.
autotransformer.
9.2.4 Impedance Test of Three-phase Trans-
former with Three-phase Voltage. All three
terminals of either the high-voltage winding or
the low-voltage winding are short-circuited
together, and balanced three-phase voltages of
rated frequency and suitable magnitude are
applied t o the terminals of the other winding
to force the rated currents t o circulate (Fig 16
or Fig 17).
The procedure is similar t o that described for
single-phase units except that all connections
and measurements are three phase instead of
A
single phase.
9.2.4.1 Measurement Connections. Watt-
meter readings may be taken as described for
the no-load-loss test in 8.3. Fig 17
If the three line currents cannot be balanced, Three-phase Transformer Connections for
their average r m s values should correspond t o Impedance-Loss and Impedance-Voltage
the desired value. Tests Using Two-Wattmeter Method
(1) Three-Wattmeter Connection (Preferred). (Instrument transformers t o be added
See Fig 16. when necessary .)

23
ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS C57.12.91-1979

9.2.5 Impedance Test of Three-phase Trans- Measured impedance volts


former with Single-phase Voltage. To test the
impedance of a three-phase unit with single-
phase voltage, the winding t o which voltage is
t o be applied must be connected in A and a
comer of the A opened t o apply the single- where P and E are the individual readings of
phase voltage. The other winding must be measured impedance loss and voltage, respec-
either connected in A (in which case no short- tively, as indicated by subscripts.
circuiting is necessary), or if it is in Y, its The stray-loss component of the impedance
terminals must be short-circuited t o its neutral. watts shall be obtained by subtracting from the
The procedure is otherwise like a single-phase latter 12R losses of the transformer. Let R l be
impedance test. the resistance measured between two high-
The voltage obtained in this manner is three voltage terminals and R, that between two
times the impedance voltage of one phase of low-voltage terminals, and let I, and I, be the
the transformer, and this fact must be con- respective rated line currents. Then, the total
sidered in converting the values into percent 12R loss of all three phases will be
or per-unit quantities. Use the following
formula: Total 12R = 1.5(<R1 + I;R,) watts

Percent impedance volts = This formula applies equally well to Y- or A-


connected windings.
measured impedance volts Temperature correction shall be made as
loo 3 X rated voltage of excited in 5.3.
windings in A
9.2.6 Impedance Test of a Three-Winding
This method of test does not duplicate the Transformer. In a three-winding transformer,
three-phase impedance condition very exactly which may be either single phase or three
and tends t o give higher losses by introducing phase, two winding impedance measurements
irrelevant zero-phase-sequence losses (usually are made with each pair of windings (which
losses in the tank or enclosure) into the mea- means three different impedance measurements)
surement. This effect is more pronounced for following the same procedure as for two-winding
core-type transformers. Therefore, it is not transformers.
suitable for the higher reactance transformers. If the kVA capacities of the different windings
are not alike, the current held for the impedance
9.2.5.1 An alternative single-phase test is
test should correspond t o the capacity of the
applicable regardless of whether windings are
lower rated winding of the pair of windings
connected A, wye, zigzag, or any combination
under test. However, all of these data when
of these. The neutral terminals, if any, are not
converted into percentage form should be based
used, and it is not necessary t o open a comer
on the same output kVA, preferably that of the
of the A .
primary winding.
The three line leads of one winding are short-
The individual equivalent impedance charac-
circuited, and single-phase voltage at rated
teristics of the separate windings may be
frequency is applied to two terminals of the
determined with the following expressions:
other winding and adjusted to circulate rated
line current.
Three successive readings are taken on the 2, =
'12 - z23 z31

three pairs of leads, as for example: H, and 2


H,, H, and H3, H3 and H I . Then:

Measured impedance watts

'31 - 212 + z23


Z3 =
2

24
ANSI/IEEE
C57.12.91-1979 IEEE STANDARD TEST CODE FOR DRY-TYPE

where Z12, Z 2 3 , and Z31 are the measured Per-unit values of the resistance, reactance, and
impedance values between pairs of windings, as impedance voltages are obtained by dividing
indicated, all expressed on the same kVA base. Er, E,, and E, by the rated voltage. Percentage
These equations involve complex numbers, values are obtained by multiplying per-unit
but they may be used for the resistance (in- values by 100.
phase) component or reactance (quadrature) The 12R losses of the two windings are calcu-
component of the impedance voltage or of lated from the ohmic resistance measurements
impedance volt-amperes. (corrected to the temperature at which the
The treatment of the individual impedance impedance test was made) and the currents
losses for temperature correction, etc, is the that were used in the impedance measurement.
same as for two-winding single-phase trans- The 12R losses subtracted from the load-loss
formers. watts give the stray losses of the transformer
The total loss for a three-winding trans- at the temperature at which the load-loss test
former is approximately the sum of the losses was made.
in the three windings as determined for the The 12R component of the load loss increases
load conditions of the windings. with the temperature, and the stray-loss com-
9.3 Interlacing Impedance Voltage of a Scott- ponent diminishes with the temperature; there-
Connected Transformer. The interlacing im- fore, when it is desired t o convert the imped-
pedance voltage of Scott-connected trans- ance losses from one temperature t o another,
formers is the single-phase voltage applied the two components of the impedance loss are
from the midtap of the main transformer converted separately. Thus,
winding t o both ends connected together, the
voltage being sufficient t o circulate in the
supply lines a current equal t o the rated three-
phase line current. The current in each half of
the winding is 50 percent of this value.
The percent interlacing impedance is the
measured voltage expressed as a percentage of
the teaser voltage.
The percent resistance is the measured watts
expressed as a percentage of the rated kVA of resistance loss at temperature T
the teaser winding. stray loss a t temperature T
9.4 Calculation of Impedance Voltage and calculated resistance loss at tempera-
Load Loss from Test Data ture Tm
9.4.1 Impedance Voltage. Resistive and re- calculated stray loss at temperature
active components of the impedance voltage
Tm
are determined by the use of the following
equations: 234.5 for copper
p, 225 for aluminum
Er = -
I
NOTE: 225 applies for pure or EC aluminum. Tk may
be as high as 230 for alloyed aluminum.
E, = dEi - E:
9.5 Impedance Bridges
where 9.5.1 Impedance Bridge Method. The im-
pedance bridge method may be used as an
E, = resistance voltage, in-phase component alternate t o the wattmeter-voltmeter-ammeter
E, = reactance voltage, quadrature com- method for the measurement of impedance and
ponent impedance losses.
The impedance bridge method is advantageous
E , = impedance voltage
for low-power-factor measurements where
P, = watts measured in impedance test special wattmeters and techniques are ordi-
I = current in amperes in excited winding narily required.

25
ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS (257.12.91-1979

TRANSFORMER
UNDER TEST

Fig 18
General Impedance Bridge Network

TO POWER
L
SOURCE I TRANSFORMER
90' PHASE UNDER TEST
SHIFTER

A
VT

Fig 19
Potentiometer-Type Network Using a Phase Shifter

9.5.1.1 Impedance Bridge Networks. While 9.5.2.1 Potentiometer-Type Networks. A


many configurations of impedance bridge net- convenient form of the impedance bridge for
works are possible, the choice of a particular transformer testing is a double ac potentiometer-
network is determined by the measurement type network using a phase shifter (Fig 19).
problem at hand and the testing facilities The two potentiometers A and B are either
available. See 9.5.2. connected directly or through a potential
9.5.2 Impedance Bridge Networks for Mea- (voltage) transformer (VT) t o the terminals of
surement of Losses. The general form of the the transformer under test. The phasor sum of
impedance bridge is an electrical network so the voltage drops A and B, which are in quadra-
arranged that a voltage proportional to the ture, are then compared with the voltage drop
current through the transformer under test C across the secondary of the current trans-
can be compared with a reference voltage that former CT. The constants of this network can
is a function of the applied test voltage Et be arranged so that the balance position of
(Fig 18). The voltage comparison is made by potentiometer A is directly proportional t o the
adjusting one or more of the bridge arms Z , , loss in the transformer under test. This net-
Z 2 , and Z 3 , until the voltages across 2, and Z 3 work can be connected in place of the usual
are exactly equal in magnitude and phase. dynamometer-type wattmeter and is readily
Voltage balance is indicated by a null reading adaptable to automatic testing.
of the detector DET. The impedance char- Another configuration of the double po-
acteristics of the transformer under test can tentiometer-type network employs a mutual
then be calculated from the values of Z,, Z2, inductor to obtain a quadrature voltage drop
and Z 3 . required for balance (Fig 20). In this case the

26
ANSI/IEEE
C57.12.91-1979 IEEE STANDARD TEST CODE FOR DRY-TYPE

‘0POWFR
SOURCE
I
f I
A I
\;;ANSFORMER
UNDER TEST

%
CT - MUTUAL

4 1

Fig 20
Potentiometer-Type Network Using a Mutual Inductor

phasor sum of the voltage drops B and C are 10.1.2 Test Voltages. Unless otherwise spec-
compared with the voltage drop A. For op- ified, the dielectric test voltages shall be mea-
eration at a fixed frequency (normally 60 Hz), sured or applied, or both, in accordance with
the constants of the circuit can be arranged so IEEE Std 4-1978, Standard Techniques for
that the balance position of potentiometer B High Voltage Testing.
is directly proportional to the loss in the trans- 10.1.3 Transformers. Transformers shall be
former under test for low power factors. assembled prior to making dielectric tests,
The configuration of a direct-reading-type including sheet metal enclosures and any termi-
potentiometer network for measuring loss is nal compartments involved, except in those
usually determined by the voltage or current instances where the transformer is furnished to
to be held during test. For no-load loss, where the user without sheet metal enclosures or
voltage is the reference parameter, the in-phase terminal compartments.
and quadrature voltage drops required for 10.1.4 Temperature. The temperature of
balance are advantageously derived from the the transformer during dielectric testing shall
voltage portion of the test circuit. For imped- be between 10°C and 40°C.
ance loss, where load current is the reference 10.1.5 Conditions. The dielectric tests spec-
parameter, these voltage drops are advanta- ified in 10.1.5.1 through 10.1.5.3 shall be
geously derived from the current portion of the performed in accordance with the require-
test circuit. ments in ANSI/IEEE C57.12.01-1979.
Additional information on these and other 10.1.5.1 Low-Frequency Dielectric Tests.
impedance networks of the potentiometer type Tests shall be performed in accordance with
is included in references. Table 3 and Section 5.10 of ANSI/IEEE C57.
9.5.2.2 Three-phase Bridge Measurements. 12.01-1979.
Loss measurements on three-phase transformers NOTES :
are made by connecting the bridge network to (1) I; the following test descriptions, the word
each phase in turn and calculating the total loss “phase refers to the “line terminal” of a winding and
from the three single-phase measurements. This not t o the entire phase of a winding, recognizing the
construction of windings with “graded insulation.”
is analogous to the three-wattmeter method of (2) The low-frequency tests are described in func-
measuring losses using a single wattmeter. tional and geometric terms. The accomplishment of
these low-frequency tests is achieved by the “applied-
voltage” and “induced-voltage” tests described in 10.3
and 10.4, or combinations thereof.
10. Dielectric Tests
10.1.5.2 Low-Frequency Tests-Exceptions.
10.1 Factory Dielectric Tests (1) Subject to the limitation that thevoltage-
10.1.1 Purpose. The purpose of dielectric to-ground test must be performed as specified
tests in the factory is to demonstrate that the in 10.1.5.1 on the line terminals of the winding
transformer has been designed and constructed with the lowest ratio of test voltage to minimum
to withstand the imposition of voltages associ- turns, then test levels may otherwise be reduced
ated with the specified insulation levels. such that none of the tests required in 10.1.5.1

27
ANSIIIEEE
DISTRZBUTION AND POWER TRANSFORMERS C57.12.91-1979

need be exceeded in order to meet the require- 10.3 Applied-Voltage Tests


ments of the others, or such that no winding 10.3.1 For transformers designed for delta
need be tested above its specified level in order connection or designed so that either terminal
to meet the test requirements of another of a single-phase winding can be used as the
winding. line terminal, the applied-voltage test shall be
(2) Autotransformers with grounded neutrals made by applying between each winding and
cannot always be tested a t the assigned low- all other windings connected t o ground, a
frequency test levels because the insulation low-frequency voltage from an external source,
levels may not be in proportion t o the turns in accordance with ANSI/IEEE C57.12.01-
ratio of the windings. In that case, the winding 1979, Table 3.
with the lowest ratio of low-frequency test 10.3.2 Permanently Y-connected windings
voltage t o minimum turns will determine the shall receive an applied-voltage test in accor-
induced voltages on all windings. The other dance with ANSI/IEEE C57.12.01-1979, 5.10.
winding will be tested at maximum turns unless 2.1 and Table 3, column 3, when the neutral is
maximum turns will produce a voltage in the solidly grounded; o r in accordance with 5.10.
other winding in excess of the required test 2.2 and Table 3, column 4, when the neutral is
level. This situation is possible on autotrans- ungrounded.
formers with a wide tapchanger range in one 10.3.3 A normal power frequency such as
winding. 60 Hz shall be used and the duration of the test
10.1.5.3 Impulse Tests. When specified, im- shall be 1minute.
pulse tests shall be performed in accordance The winding being tested shall have all its
with ANSI/IEEE C57.12.01-1979: parts joined together and connected t o the
10.1.5.4 Test Sequence. The sequence of line terminal of the testing transformer.
tests shall be impulse tests (when required) All other terminals and parts (including core
followed by the low-frequency voltage tests. and enclosure or tank) shall be connected t o
ground and t o the grounded terminal of the
10.2 Dielectric Tests in the Field. It is recog- testing transformer.
nized that dielectric tests impose a severe stress The ground connections between the appa-
on the insulation and, if applied frequently, ratus being tested and the testing transformer
will hasten breakdown or may cause break- shall be a substantial metallic circuit. All con-
down; the stress imposed, of course, will be nections shall make good mechanical joints
more severe the higher the value of the applied without forming sharp comers or points.
voltage. Hence, practice in this matter has Small bare wire may be used in connecting
varied widely among operating companies, and the respective taps and line terminals together,
the advisability of periodic testing may be but care must be taken t o keep the wire on
questionable. the high-voltage side well away from the
Field dielectric tests may be warranted by ground.
special circumstances. However, periodic di- No appreciable resistance should be placed
electric tests are not recommended because of between the testing transformer and the one
the severe stress imposed on the insulation. under test. It is permissible, however, to use
Where low-frequency applied-voltage and reactive coils at or near the terminals of the
induced-voltage tests for acceptance are con- testing transformer.
ducted in the field, the test voltages shall not A relief gap set at a voltage 10 percent or
exceed 75 percent of factory test values. When more in excess of the specified test voltage
field tests are made on a periodic basis, it is may be connected during the applied-voltage
recommended that the test voltages be limited test.
t o 65 percent of factory test values. 10.3.4 The voltage should be started at one-
Duration of the tests shall be the same as quarter or less of the full value and be brought
that specified in 10.3 and 10.4. up gradually to full value in not more than 15 s.
After being held for the time specified, it
More information will be found in new publications
should be reduced gradually (in not more
now in preparation. See 3.3, footnote 1, [ 2 ] , [ 3 ] than 5 s) to onequarter of the maximum
and [ 4 ] . value o r less, and the circuit opened.

28
ANSI/IEEE
C5 7.12.91 -1979 IEEE STANDARD TEST CODE FOR DRY-TYPE

10.4 Induced-Voltage Tests circuiting one phase at a time of the high-


10.4.1 The induced-voltage test for trans- voltage winding and exciting the remaining two
formers that receive the full standard applied- phases t o achieve twice-rated turn-to-turn
voltage test shall be made by applying between voltage in the excited windings. Three tests,
the terminals of one winding a voltage as one for each phase, are required.
specified in 5.10.3.2 of ANSI/IEEE C57.12.01-
NOTE: This alternate method will result in approxi-
1979. mately 15 percent excess voltage between line
10.4.2 The induced-voltage test shall be ap- terminals.
plied for 7200 cycles or 60 s - whichever is
shorter. 10.4.7 When the induced test on a winding
results in a voltage between terminals of other
10.4.3 As this test applies greater than rated windings in excess of the low-frequency test
voltage per turn to the transformer, the fre- voltage specified in these standards, the other
quency of the applied voltage must be high winding may be sectionalized and grounded.
enough t o limit the flux density in the core to Additional induced tests shall then be made to
that permitted by 4.1.6(2) of ANSI/IEEE give the required test voltage between terminals
C57.12.01-1979. The minimum test frequency of windings that were sectionalized.
to meet this condition is:
10.5 Impulse Tests
NOTE: See ANSI/IEEE C57.98-1968, Guide for
Test frequency = Et X rated frequency Transformer Impulse Tests (Appendix to C57.12.90-
1.1 X Er
1968), for information on impulse testing techniques,
interpretation of oscillograms, and failure detection
where Et is the induced test voltage across the criteria.
winding and E r is the rated voltage across the 10.5.1 General. When specified, impulse tests
winding. shall be performed. When required, the impulse
10.4.4 The voltage should be started at one- test shall precede the low-frequency applied-
quarter or less of the full value and be brought and induced-voltage tests. Impulse tests consist
up gradually to full val,ue in not more than of applying, in the following order, one reduced
15 s. After being held for the time specified full wave, two chopped waves, and one full
in 10.4.2, it should be reduced gradually (in wave. Applicable values are listed in ANSI/IEEE
not more than 5 s) t o % of the maximum value C57.12.01-1979 or in applicable product stan-
or less, and the circuit opened. dards.
(1) Reduced full-wave test: For this test
10.4.5 In the case of transformers having the applied voltage wave shall have a crest
one end of the high-voltage winding grounded, value of between 50 and 70 percent of the
the other windings should be grounded during required full-wave value.
the induced-voltage test. This ground on each
winding may be made at a selected point of (2) Chopped-wave test: For this test the
the winding itself or of the winding of a set-up applied voltage wave shall be chopped by a
suitable air gap. It shall have a crest value and
transformer, which is used to supply the
voltage, or which is connected for the purpose time to flashover in accordance with 10.5.1.
of furnishing the ground. The gap shall be located as close as possible t o
the terminals, and the impedance shall be
10.4.6 Three-phase Y-connected transformers limited to that of the necessary leads to the
with standard (reduced) neutral insulation shall gap.
have the neutral grounded during the induced- ( 3 ) Full-wave test: For this test the voltage
voltage test and shall be tested with three- wave shall have a crest value in accordance
phase induced voltage. with 10.5.1, and no flashover of insulated parts
10.4.6.1 Three-phase Y-connected trans- or test gap shall occur.
formers with nonreduced neutral insulation
may be tested with the neutral either grounded 10.5.1.1 The time interval between appli-
or ungrounded. cation of the last chopped wave and the final
10.4.6.2 An alternate method of making full wave shall be minimized to avoid recovery
the induced-voltage test may be used with of insulation strength if a failure occurs prior
single-phase excitation. This is done by short- to the final full wave.

29
ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS C57.12.91-1979

10.5.1.2 When specified, the results of im- full-wave value given in the tables in these
pulse tests shall be reported on the “Trans- standards. When reports require oscillograms,
former Impulse Test Report” form illustrated those of the first reduced-full-wave voltage and
in ANSI/IEEE C57.98-1968. current, the last two chopped waves, and the
10.5.2 Wave to be Used for Impulse Tests. last full wave of voltage and current shall
A 1.2 X 50 microsecond wave shall be used represent a record of the successful application
for full-wave and reduced full-wave tests. of the impulse test t o the transformer.
Waves of positive polarity shall be used for 10.5.3 Connections for Impulse Tests. In
dry-type transformers. general the tests shall be applied to each termi-
The time to crest on the front from virtual nal, one a t a time.
time zero to actual crest shall not exceed 10.5.3.1 Grounding. One terminal of the
2.5 ps except for windings of large impulse winding under test shall be grounded directly
capacitance (low-voltage, high-kVA and some or through a low resistance if current measure-
high-voltage, high-kVA windings). ments are t o be made. (For exceptions see the
To demonstrate that the large capacitance of following paragraph.) The terminals of windings
the winding causes the long front, the impulse that are not being tested may be grounded
generator series resistance may be reduced, directly or through a resistor in order to limit
which should cause superimposed oscillations. the voltage induced in these windings. It is
Only the inherent generator and lead induc- desirable that the voltages on terminals that
tances should be in the circuit. are not being tested should not exceed 80 per-
For convenience in measurement, the time t o cent of the full-wave voltage for their insula-
crest may be considered as 1.67 times the tion level.
actual time between points on the front of All grounds shall be direct, except as de-
the wave at 30 and 90 percent of the crest scribed in the preceding paragraph and at
value. neutral terminals, which may be grounded
The time on the tail to the point of halfcrest through the same neutral grounding impedance
voltage of the applied wave shall be not less as is t o be used in service. If such neutral
than 40 ps from the virtual time zero, unless grounding impedance is unavailable, the neutral
the winding is of low inductance. This is within shall be directly grounded.
the minus 20 percent tolerance provided for 10.5.3.2 Series/MuEtiple Connections. Only
a 1.2 X 50 ps wave. the series connection of a series or multiple
The virtual time zero can be determined by connection shall be tested, unless tests on both
locating points on the front of the wave at connections are specified. The connection of
which the voltage is, respectively, 30 and the other windings (whether series or parallel)
90 percent of the crest value and then drawing shall be made at the choice of the manufacturer.
a straight line through these points. The inter- 10.5.3.3 Delta and Wye Connections. Un-
section of this line with the zero voltage line less otherwise specified, tests shall be made
is the virtual time zero. on the A-connection. When so specified, tests
When there are high-frequency oscillations shall be made on the Y-connection, or both the
on the crest of the wave, the crest value shall A- and Yconnections.
be determined from a smooth wave sketched 10.5.3.4 Tap Connections. Tap connec-
through the oscillations. If the period of these tions shall be made with minimum effective
oscillations is 2 ps or more, the actual crest turns in the winding under test. The choice of
value shall be used. tap connections of windings not being tested
If there are oscillations on the front of the shall be made by the manufacturer.
waves, the 30 and 90 percent points shall be 10.5.3.5 Protective Devices. When protec-
determined from the average, smooth-wave tive devices are permanently connected as an
front sketched in through the oscillations. integral part of series transformer windings or
The magnitude of the oscillations preferably of other portions of windings, these devices
should not exceed 10 percent of the applied shall be connected during test. The operation
voltage. of these devices usually will cause differences
All impulses applied to a transformer should between the reduced-full-wave and the full-wave
be recorded by a cathode-ray oscillograph if oscillograms. That these differences are caused
their crest voltage exceeds 40 percent of the by the operation of the protective devices may
ANSI/IEEE
C57.12.91-1979 IEEE STANDARD TEST CODE FOR DRY-TYPE

be demonstrated by making two or more amplitude equal t o the BIL of the neutral. The
reduced-full-wave tests at different voltage winding being tested shall be on the maximum-
values t o show the trend in their operation. voltage connection.
Further evidence that the differences are due
to the operation of the protective devices may 10.7 Detection of Failure during Impulse Test.
be obtained, in some cases, by making addi- Because of the nature of impulse test failures,
tional tests with the protective devices shorted one of the most important matters is the detec-
out. tion of such failures, There are a number of
10.5.3.6 Low-Impedance Windings. In some indications of insulation failure.
cases the inductance of the winding is so low 10.7.1 Ground-Current Oscillograms. Unless
that the desired voltage magnitude and dura- otherwise specified, ground-current oscillograms
tion to the 50 percent point on the tail of the shall be the standard method of failure detec-
wave cannot be obtained with available equip- tion, where applicable. Both ground-current
ment. In some cases the terminals of such oscillograms and voltage oscillograms may be
windings having the same insulation class at used for failure detection.
both ends may be tied together for the test. In this method of failure detection, the im-
Because of the difference in insulation level at pulse current in the grounded end of the
the two terminals of the winding, it is some- winding tested is measured by means of a
times impossible t o tie the terminals together cathode-ray oscillograph connected across a
for the impulse test. Low-inductance windings suitable shunt inserted between the normally
may also be tested by inserting a resistor of not grounded end of the winding and ground. Any
more than 500 52 in the grounded end of the differences in the wave shape between the
winding. In all such cases shorter waves may be reduced full wave and final full wave detected
used. by superimposing the two current oscillograms
may be indications of failure or deviations due
10.6 Impulse Tests on Transformer Neutrals. t o noninjurious causes. They should be fully
When specified, impulse tests on the neutral investigated and explained by a new reduced-
of a transformer may be applied by the methods wave and full-wave test. Examples are opera-
given in 10.6.1 and 10.6.2. The choice of the tion of protective devices, core saturation, or
method of testing the neutral shall be made conditions in the test circuit external to the
by the manufacturer. transformer. In air- or gas-insulated apparatus
NOTE: The standard neutral insulation specified in partial discharges (corona) may produce
ANSI/IEEE C57.12.01-1979, provides for grounded high-frequency oscillations on the wave. This
Y operation, and the neutral is designed for an applied- is not an indication of failure and should be
voltage test. If specified, the neutral shall be insulated
for a higher insulation level. taken into account in interpreting the traces.
10.7.1.1 The ground-current method of de-
10.6.1 The test on the neutral, or neutral tection is not applicable for use with chopped-
and regulating winding, is induced by the appli- wave tests.
cation of an impulse t o any line terminal with
the neutral grounded through a suitable imped- 10.7.2 Other Methods of Failure Detection
ance so that the required full-wave test voltage 10.7.2.1 Voltage Oscillograms, Any unex-
is obtained from the neutral terminal t o ground. plained differences between the reduced full
One reduced and two full waves shall be ap- wave and the final full wave detected by super-
plied t o the line end of a winding with a crest imposing the two voltage oscillograms, or any
voltage equal t o or less than the full-wave level such differences observed by comparing the
of the line end. The other windings may be chopped waves to each other and t o the full
short-circuited for this test. The winding being wave up to the time of flashover, are indica-
tested shall be on the maximum voltage con- tions of failure. Deviations may be caused by
nection. The voltage oscillograms shall be taken conditions in the test circuit external to the
at the neutral. When this method of test is transformer or by protective devices and should
used, the test on the neutral shall precede the be fully investigated. In air- or gas-insulated
test on the line terminal. apparatus partial discharges (corona) may
10.6.2 One reduced and two full waves are produce high-frequency oscillations on the
applied directly to the winding neutral with an wave. This is not an indication of failure and

31
ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS C57.12.91-1979

should be taken into account in interpreting curacy of measurement should be within f 0.25
the traces. percent insulation power factor, and the mea-
10.7.2.2 Failure of Gap to Flashover. In surement should be made at or near a frequency
making the chopped-wave test, failure of the of 60 Hz.
chopping gap, or any external part, to flash- 10.8.3 Voltage to be Applied. The voltage
over, although the voltage oscillogram shows a t o be applied for measuring insulation power
chopped wave, is a definite indication of a factor shall not exceed operating voltage to
flashover either within the transformer or in ground for any part of the winding or 1000 V,
the test circuit. whichever is lower.
10.7.2.3 Noise. Unusual noise within the 10.8.4 Procedure. Insulation power-factor
transformer at the instant of applying the tests shall be made from windings t o ground
impulse is an indication of trouble. Such noise and between windings, as shown in Table 1.
should be investigated.
NOTE: While the real significance that can be at-
10.8 Insulation-Power-Factor Tests. Insulation tached to the insulation power factor of dry-type
transformers is still a matter of opinion, experience has
power factor is the ratio of the power dissipated shown that insulation power factor is helpful in assess-
in the insulation in watts to the product of ing t h e probable condition of t h e insulation when good
the effective voltage and current in volt- judgment is used.
amperes when tested under a sinusoidal voltage In interpreting the results of insulation-power-factor
test values, the comparative values of tests taken at
and prescribed conditions. periodic intervals are useful in identifying potential
The methods described herein are applicable problems rather than an absolute value of insulation
power factor.
to dry-type distribution and power transformers A factory insulation-power-factor test will be of
of present-day design. value for comparison with field insulation power
10.8.1 Preparation for Tests. The test speci- factor measurements to assess the probable condi-
men shall have: tion of the insulation. It has not been feasible to
establish standard insulation power factor values for
(1) All windings short-circuited dry-type transformers because experience has indi-
(2) All terminals in place cated that little or n o relation exists between insulation
power factor and t h e ability of t h e transformer t o with-
(3) Temperature of transformer near the stand t h e prescribed dielectric tests.
reference temperature of 20°C
Where the temperature is other than 20°C, 10.9 Insulation-Resistance Tests. Insulation-re-
the results should be corrected t o 2OoC. sistance tests are made to determine the in-
sulation resistance from individual windings t o
NOTE: Typical temperature correction-factor data for ground, or between individual windings. The
dry-type transformers are not presently available.
insulation resistance in such tests is commonly
10.8.2 Instrumentation. Insulation power fac- measured in megohms but may be calculated
tor may be measured by special bridge circuits from measurements of applied voltage and
or by the volt-ampere-watt method. The ac- leakage current.

Table 1
Measurements to be Made in Insulation Power Factor Tests

Method I : Method 11:


Test without Guard Circuit* Test with Guard Circuit*

Two-winding transformers? Two-winding transformerst


High to low and ground High to low and ground
Low t o high and ground High to ground, guard on low
High and low to ground Low to high and ground
Low to ground, guard on high

*The Term guard signifies one or more conducting elements arranged and connected o n an electrical instrument or
measuring circuit so as to divert unwanted currents from the measuring means.
$Permanently connected windings, such as autotransformers, shall be considered as one winding.

32
ANSI/IEEE
C57.12.91-1979 IEEE STANDARD TEST CODE FOR DRY-TYPE

Insulation-resistance tests shall be made when winding involved (or 1 0 0 0 V for a solidly p o u n d e d
wye winding), a relief gap may be employed to protect
specified. the insulation.
The insulation resistance of electrical appara-
tus is of doubtful significance as compared 10.9.4 Procedure
with the dielectric strength. It is subject t o (1) Insulation-resistance tests shall be made
wide variation with design, temperature, dry- with all circuits of equal voltage above ground
ness, and cleanliness of the parts. When the connected together. Circuits or groups of cir-
insulation resistance falls below prescribed cuits of different voltages above ground shall
values, it can, in most cases of good design and be tested separately; for example, high voltage
where no defect exists, be brought up t o the t o low voltage and ground, low voltage t o high
required standard by cleaning and drying the voltage and ground.
apparatus. The insulation resistance, therefore, (2) Voltage should be increased in incre-
may afford a useful indication as to whether ments (usually 1 to 5 kV), holding each step
the apparatus is in suitable condition for appli- for 1 min.
cation of the dielectric test. (3) The test should be discontinued im-
mediately in the event the current begins t o
NOTES : increase without stabilizing.
( 1 ) The significance of values of insulation-resistance
tests generally requires some interpretation, depending
on the design and the dryness and cleanlidess of the
insulation involved. If a user decides to make insula- 11. Temperature Tests
tion-resistance tests, it is recommended that insulation-
resistance values be measured periodically (during
maintenance shutdown) and that these periodic values 11.1 General. Transformers shall be tested
be plotted. Substantial variation in the plotted values of under a loading condition that will give losses
insulation resistance should be investigated for cause.
(2) Insulation resistances may vary with applied as near as possible t o those obtained when the
voltage, and any comparison must be made with transformer is operating connected for its
measurements at the same voltage. nameplate rating. In some cases temperature
testing requires a slight overexcitation.
10.9.1 Preparation for Test The resultant increase in total loss has a
(1) Windings in their normal insulation negligible effect on the kilovolt-ampere output.
environment It is therefore not considered in the tempera-
(2) All windings short-circuited ture rise test methods described herein.
(3) All bushings or terminals in place Conditions under which temperature limits
(4) Transformer temperature approximately apply are stated in ANSI/IEEE C57.12.01-
2oOc. 1979. Transformers shall be tested on the tap
10.9.2 Instrumentation. Insulation resistance connection giving the highest winding tempera-
may be measured using either: ture rise.
(1) A variable-voltage dc power supply with
means to measure voltage and current (generally 11.2 Temperature Test Methods
in microamperes o r milliamperes) 11.2.1 Simulated Loading
(2) A megohmeter 11.2.1.1 Loading-Back (Opposition) Meth-
od for Self-Cooled and Forced-Cooled Trans-
NOTE: Megohmeters are commonly available with formers, Ventilated Dry Type. The loading-back
nominal voltages of 500, 1000, and 2500 V. DC ap- (opposition) method requires a greater amount
plied test equipment is available at higher voltages.
of testing facilities and auxiliary equipment,
10.9.3 Voltage t o be Applied. The dc voltage and also energy consumption. Because of these
applied for measuring insulation resistance to requirements, the loading-back method becomes
ground shall not exceed a value equal to the increasingly difficult to perform as the size
rms low-frequency applied voltage allowed of the transformer increases.
in 10.3. 11.2.1.2 Short-circuit Method for Venti-
NOTES:
lated Dry-Type Self-Cooled Transformers Only
(1) Partial discharges should not be present during (Separate Load-Loss and Excitation Test). If
insulation-resistance tests, since they can damage a the test equipment cannot produce rated cur-
transformer and may also result in erroneous values of rent, the short-circuit method necessitates an
I insulation resistance.
( 2 ) When measurements are t o be made using dc
voltages exceeding the rms operating voltage of the
accurate predetermination of excitation losses
and conductor losses, including stray losses, at

33
ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS C5 7.12.91 -1979

operating temperature. It has the advantage of restricted cooling, or any other suitable
permitting a direct measurement of the wattage method.
and current being held during the temperature 11.3.2 Temperature Measurements. The ulti-
rise test. This method requires fewer testing mate temperature rise is considered to be
facilities and a smaller amount of energy con- reached when the temperature rise becomes
sumption. It is particularly suitable for the constant, that is, when the temperature rise
larger size transformers and is equally satis- does not vary more than 2°C during a consecu-
factory for small transformers. tive 3 h period.
11.2.1.3 Impedance kVA Method. This is Use of thermocouples is the preferred method
a method for testing a single three-phase trans- of measuring surface temperatures. Thermo-
former or three single-phase transformers hav- couples shall be placed in intimate contact
ing delta windings or able t o be connected t o with the surface being measured, attached to
two delta windings. One delta winding must be maintain firm contact, and thermally insulated
open so that the impedance kVA can be from the surrounding medium.
supplied. For the purpose of determining where
11.2.2 Actual Loading. The actual loading constant temperature conditions have been
method is the most accurate of all methods, achieved, the sensing thermocouples shall be
but its energy requirements are excessive for applied to the surfaces as specified in the
large transformers. following :
Transformers of small output may be tested (1) Ventilated dry-types: Top center of core
under actual load conditions by loading them top yoke and innermost low-voltage lead of
on a rheostat, bank of lamps, or water box or middle phase (34 units) or an inner low-voltage
by similar loading methods. of a 14 unit
11.2.3 Test Method Application (2) Sealed dry or nonventilated types: Center
11.2.3.1 The loading-back method is a of top cover surface and center of one sidewall
basic method for testing sealed or ventilated surface
dry-type transformers and may be used when When the temperature rise has become con-
more than one unit is available for test. stant, the test voltage and current should be
11.2.3.2 The separate load-loss and excita- removed and the fans, if used, shut off. Im-
tion-loss test method may be used on all self- mediately thereafter the coil thermometers
cooled, ventilated dry-type transformers. and any other temperature-indicating devices
11.2.3.3 The load-loss test plus an addi- should be read continually in rotation until the
tive factor may be used for all ventilated temperature begins to fall. If any of the ther-
dry-type transformers when empirical data mometer temperatures are higher than those
are available establishing the proper value of observed during the run, the highest tempera-
the additive factor. ture should be recorded as the final thermome-
11.2.3.4 When it is not feasible t o make ter temperature.
a loading-back temperature test on a sealed or The temperature rise of the windings shall be
nonventilated dry-type transformer, a combina- determined by the resistance method, or by
tion of tests involving a total-loss heat-run thermometer when so specified.
test, a current heat-run test, and an excitation When measured, the temperature rise of metal
heat-run test may be used to calculate the parts (other than the winding conductor) in
temperature rise of the windings. contact with, or adjacent to, insulation, and of
11.3 Requirements for Temperature-Rise Tests other metal parts, shall be determined by
11.3.1 General. Transformers shall be com- therinocouples or by thermometer.
pletely assembled with all panels in place. Provision shall be made to measure the surface
If the transformers are equipped with thermal temperature of iron or alloy parts surrounding
indicators, bushing-type current transformers, or adjacent t o the outlet leads or terminals
and so forth, such devices shall be assembled carrying large currents. Readings shall be taken
with the transformer. at intervals or immediately after shutdown.
The temperature-rise test shall be made in a The determination of the temperature rise
room which is as free from drafts as practicable. of metal parts within the case, other than
It is permissible t o shorten the time required winding conductors, is a design test and shall
for the test by the use of initial overloads, be made when so specified unless a record of

34
ANSI/IEEE
C57.12.91-1979 IEEE STANDARD TEST CODE FOR DRY-TYPE

this test made on a duplicate, or essentially


duplicate, unit can be furnished. Comparisons
with other transformers having metal parts of
similar design and arrangement, but not neces-
sarily having the same rating, will be adequate
in many cases.
When temperature-rise tests by thermometer The average winding temperature rise may be
are required, place at least one alcohol ther- determined by the following equation:
mometer in each high- and low-voltage group
of coils. If the respective coil groups consist
of several coils, several thermometers should
be placed in each group.
It is important that the coil thermometers where
be properly placed in the air ducts in such a
manner as to indicate the winding temperature T = temperature ("C) corresponding to hot
and yet not restrict the ventilation. This may resistance R
be accomplished by means of grooved sticks of To = temperature ("C) corresponding to
insulating material slightly larger than the cold resistance Ro
thermometer bulbs.
When the thermometers are used, the bulbs Tr = average temperature rise ("C)
shall be covered by pads cemented t o the T, = ambient temperature ("C) correspond-
equipment or by grooved sticks. ing to hot resistance R
11.3.3 Ambient Temperature. The ambient
temperature shall be taken as that of the sur- Ro = cold resistance determined in accor-
rounding air, which should not be less than dance with the rules in this standard
10°C or more than 40°C. R = hot resistance
The ambient temperature shall be the average Tk = 234.5 for copper
of the readings from at least three thermo-
couples, or thermometers, spaced uniformly Tk = 225foraluminum
around the transformers under test. They NOTE: T k may be as high as 230 for alloyed aluminum.
should be located about one-half the height of
the transformer, and at a distance of 3 to 6 f t
(0.91 t o 1.83 m) from the transformer. They The induction time for the measuring current
should be protected from drafts and abnormal to become stable should be noted during the
heating. cold-resistance measurements in order t o
To reduce t o a minimum the errors due to ensure that sufficient time elapses for the
time lag between the temperature of the trans- induction effect to disappear before hot-
formers and the variations in the ambient resistance readings are taken.
temperature, the thermocouples, or thermom- When transferring leads from one winding t o
eters, shall be placed in suitable containers another, maintain the same relative polarity
which shall have such proportions as will with regard to the measuring leads and the
require not less than 2 hours for the indicated transformer terminals.
temperature within the container to change Record the elapsed time between the instant
6.3"C if suddenly placed in air that has a of shutdown and each hot-resistance measure-
temperature 10°C higher, or lower, than the ment.
previous steady-state indicated temperature 11.4.1 Correction Back to Shutdown, Cool-
within the container. ing Curve Method. Take a series of at least
four, preferably more, readings on one phase
11.4 Determination of Average Measured of each winding and record the time after
Winding Temperature and Average Winding shutdown for each reading.
Temperature Rise by the Hot-Resistance The readings should be time spaced to en-
Method. The average measured temperature sure accurate extrapolation back t o shutdown.
of a winding may be determined by either The overall reading time should exceed 4
of the following equations: min and may extend considerably beyond.

35
ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS C57.12.91-1979

The first reading on each winding should be where


taken as quickly as possible after shutdown,
but not before the measuring current has Tc = corrected winding rise ("C)
become stable, and must be taken within 4 Tm = measured winding rise ("C)
min.
Plot the resistance time data on suitable W = required total loss
coordinate paper and extrapolate the curve w = total loss during temperature tests
back to instant shutdown.
n = 0.80 for ventilated and 0.70 for sealed
The resistance time curve obtained on one
phase of the primary winding, or of the secon- This method may be used as long as the
dary winding, and so forth, may be used to required values of no-load loss, load loss, or
determine the correction back t o shutdown for total loss do not differ by more than 20 per-
the other phases of the primary or secondary cent from their corresponding values during
windings, and so forth, provided the first test.
reading on each of the other windings has been 11.5.3 Correction of Observed Temperature
taken within 4 min after shutdown. Rise for Variation in Altitude. When tests are
If necessary, the temperature test may be made at an altitude not exceeding 3300 f t
resumed so that the first readings on any group
(1000 m) above sea level, no altitude correc-
of windings may be completed within the
tion shall be applied t o the temperature rise.
required 4 min. See also 5.4.2.4.
When a transformer that is tested at an alti-
11.5 Correction Factors tude of 3300 f t (1000 m) or less is t o be oper-
11.5.1 Correction for Ambient Air Tem- ated at an altitude in excess of 3300 f t (1000 m),
perature. When the ambient air temperature is it shall be assumed that the observed tempera-
other than 3OoC, a correction shall be applied ture rise will increase in accordance with the
t o the temperature rise of the winding by multi- following equation :
plying it by the correction factor C, which is
given by the ratio Increase in temperature rise for ventilated dry-
pe transformers at Altitude A ( f t ) =

Observed rise X (" ~ 3 ~ o oF )

where where F is an empirical factor given in Table 2.


The observed rise in the equation is the wind-
Ta = ambient air temperature ing rise over the ambient temperature.
Tk = 234.5 for copper
11.6 Temperature Rise Test Procedures
Tk = 225 for aluminum 11.6.1 Temperature Rise of Single-phase
NOTE: Tk may be as high as 230 for alloyed aluminum. Transfomers the
Duplicate single-phase transformers may be
11.5.2 Correction to be Applied When
Temperature Test Must be Corrected for a Table 2
Difference in Total Loss. If the load losses Empirical Factor for
under test differ from their true values, a cor- Various Types of Cooling
rection for the winding rise is required.
This correction may be calculated provided
Empirical
the loading frequency does not differ from the Type of Cooling factor F
rated frequency by more than 10 percent.
The corrected winding rise may be calculated For dry-type, selfcooled (AA) 0.005
using For dry-type with auxiliary forced-
air cooling (AAIFA) 0.006*
For dry-type forced-air cooled (AFA) 0.010
*Applies t o forced-cooled rating only.

36
ANSI/IEEE
C5 7.12.91-1979 IEEE STANDARD TEST CODE FOR DRY-TYPE

RATED FREQUENCY
EXC ITAT ION SOU RC E

li
r----
--+P--l

I '
I

SOURCE FOR
IMPEDANCE LOSS

I r"l
Fig 21
Two Single-phase Transformers in Opposition I I

tested in the loading-back method by con- LOADING SOURCE


necting both high-voltage windings in parallel
and both low-voltage windings in parallel and Fig 22
by applying rated excitation voltage at rated Two Y-A Connected Transformers
frequency to one set of parallel windings
(Fig 21).
The circulated current should preferably
Circulate load current by opening the con- (but not necessarily) be at rated frequency.
nections of either pair of windings at one point The correction to be applied when the circu-
and impress a voltage across the break just lating current is not at rated value is given
sufficient t o circulate rated current through the in 11.5.2.
windings : Run until equilibrium conditions are at-
(1) This current should preferably (but not tained. Then shut down, measure the winding
necessarily) be at rated frequency. resistance, and calculate the average winding
(2) The correction to be applied when the rises over the ambient temperature as described
circulating current is not at rated value is given in 11.4.
in 11.5.2. 11.6.3 Temperature-Rise Tests of Three-
Run until equilibrium conditions are attained. Phase Transformers or Three Single-phase
Then shut down, measure the winding resis- Transformers by the Impedance k VA Method.
tance, and calculate the average winding rises A single three-phase transformer may be
over the ambient temperature, as described tested by itself, as shown in Fig 23, if both the
in 11.4. high- and low-voltage windings can be con-
11.6.2 Temperature-Rise Test of Three-phase nected in delta. Rated three-phase voltage at
Transformers by the Loading-Back Method. rated frequency shall be applied t o one of the
Duplicate three-phase transformers may be deltas. A corner of either delta connection
tested by the loading-back method by connect- shall be opened, and a voltage from an auxiliary
ing both the high-voltage and low-voltage single-phase source shall be impressed across the
windings in parallel (Fig 22). break. This voltage shall be just sufficient t o
It is desirable to connect similarly marked circulate rated current through the windings.
leads together rather than attempt t o connect The circulated current should preferably be at
windings in parallel by symmetry alone. rated frequency.
Rated excitation voltage at rated frequency Since this method of loading sometimes intro-
shall be applied t o one set of windings. duces extraneous zero-phase-sequence losses,
Circulate rated current by joining either the circulated current shall be adjusted t o yield
set of windings through an auxiliary source of the true impedance losses of the transformer
three-phase loading voltage (Fig 22). (the sum of all three phases).

37
ANSI/IEEE
C57.12.91-1979
DISTRIBUTION AND POWER TRANSFORMERS

L------l

Fig 23
A-A Connection for Three Single-phase
Units or One Three-phase Unit

11.6.4 Short-circuit Test: (Separate) Load- 11.6.5 Load-Loss Test Plus Additive Factor.
Loss and Excitation Tests. Temperature tests The total winding rise Tt of a single ventilated
on individual ventilated dry-type units may be dry-type transformer may be calculated by
made by utilizing the rises obtained in two applying an additive factor AT, t o the rise
separate tests, one with load-loss alone and one T,, as outlined in the next paragraph.
with excitation loss alone, and calculating The additive factor ATe is an empirically
winding rises using the following formula: determined temperature difference between
the winding temperature rise obtained by
loading-back test (in accordance with 11.6.1
or 11.6.2) and the winding temperature rise
measured with the load loss only (in accor-
where dance with 11.6.3). It must be established by
test data on units of similar construction.
= total winding rise with full load cur- The total winding rise Tt is given by
Tt
rent in the winding and normal excita-
tion on the core Tt = Tc + ATe
T , = high-voltage or low-voltage winding 11.6.6 Compromise Test Procedure for Sealed
rise measured immediately following or Nonventilated Dry-Type Transformers
the load-loss heat run with full load 11.6.6.1 General Procedure. Conduct an
current flowing in one winding and excitation 1-un until external top surface and
the other winding short-circuited side surfaces of the tank or enclosure stabilize
T, = high-voltage or low-voltage winding rise from a temperature-rise standpoint. Terminate
measured immediately following the the heat run and measure the high-voltage and
heat run with normal excitation on low-voltage winding temperature rises using the
the core procedure described in 11.4. Also measure and

38
ANSI/IEEE
C5 7.12.91-1979 IEEE STANDARD TEST CODE FOR DRY-TYPE

record the average temperature rise over T, = Twm - Tsr, = high-voltage or low-
ambient for the tank o r enclosure surface. voltage winding temperature over
Make a current run maintaining rated current enclosure surface temperature during
in the windings until the surface temperatures current heat run
of the tank or enclosure are again constant. Tst = average enclosure surface temperature
Terminate the current run and determine the during total-loss heat run
winding tempefature rises as described in 11.4.
Also measure and record the average tempera- Tsrt = average enclosure surface temperature
ture rise over ambient for the tank or enclosure rise during total-loss heat run
surface. = Tst - Ta
Then circulate the necessary current in the Twr = high-voltage or low-voltage average
transformer windings to generate a loss equal winding rise by resistance over
to the load loss plus the excitation loss, and ambient temperature
maintain this load until the tank or enclosure = Tsrt + Te + Tc
surfaces are again constant in temperature rise.
Winding rise measurements are not required
for this total-loss run.
From the excitation and current run the
high-voltage winding rise and the low-voltage 12. Short-circuit Tests
winding rise over average surface temperature
is determined, and these values are then added 12.1 Scope. This test code applies t o dry-
t o the average surface temperature rise over type distribution and power transformers
ambient for the total-loss run. The sum of 1 kVA and above. Within the scope, three
these values represents the average winding categories shall be recognized :
temperature rise over ambient for the trans-
I former windings. Single-phase Three-phase
Category (kVA) (kVA)
11.6.6.2 Nomenclature and Equations I 1-500 15-500
I1 501-1667 501-5000
Ta = ambient temperature I11 1668-10000 5001-30000
Tse = average enclosure surface temperature NOTES:
during excitation heat run (1) For autotransformers the category shall be
determined by the equivalent two-winding kVA (as
Tsre average enclosure surface temperature
= defined in ANSI/IEEE C57.12.80-1978).
rise during excitation heat run ( 2 ) All kVA ratings are minimum nameplate kVA
for the principal windings.
= Tse - Ta
Twre = high-voltage or low-voltage winding The code defines a procedure by which the
temperature rise over ambient during mechanical capability of a transformer t o with-
excitation heat run stand short-circuit stresses may be demon-
strated. The prescribed tests are not designed
Te = Twre - Tsre = high-voltage or low- to verify thermal performance. Conformance
voltage winding temperature rise to short-circuit thermal requirements shall be
over enclosure surface temperature by calculation in accordance with ANSI/IEEE
during excitation heat run C57.12.01-1979.
Tsc = average enclosure surface temperature The short-circuit test procedure described
during current heat run herein is for the purpose of establishing that
Tsrc = average enclosure surface temperature the performance of the transformer under test
rise during current heat run meets specification requirements. Tests may
be conducted at manufacturer’s facilities, test
= Tsc - Ta
laboratories, or in the field, but it must be
Twm = high-voltage or low-voltage winding recognized that complete equipment is not
temperature rise over ambient during usually available in the field for conducting
current heat run tests and verifying results.

39
ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS C57.12.91-1979

12.2 Test Connections 12.2.2 Multiwinding Transformers, Including


12.2.1 Two-Winding Transformers and Auto- Autotransformers
transformers without Tertiary Windings 12.2.2.1 Fault Location and Type. The
fault types and terminals t o which they are to
12.2.1.1 Fault Location. The short circuit,
be applied must be determined individually for
may be applied on the transformer primary or
each particular transformer. The maximum
secondary terminals as dictated by the available
fault current for each winding shall be deter-
voltage source, but the secondary fault is
mined from calculations for the fault types
preferred since it most closely represents the
specified in ANSI/IEEE C57.12.01-1979, Sec-
system fault condition. The short circuit shall
tion 7, considering various fault types, fault
be applied by means of suitable low-resistance
locations, and applicable system data. During
connectors.
testing, each winding shall be subjected t o its
In order of preference, the tests may be
maximum calculated fault current on at least
conducted by either of the following:
one test. In general, a given fault type and loca-
(1) Closing a breaker at the faulted termi-
tion will not produce the maximum fault cur-
nal to apply a short circuit to the previously
rent in more than one winding; so it will be
energized transformer necessary t o make tests with several different
(2) Closing a breaker at the source terminal connections in order to evaluate fully the
to apply energy t o the previously shortcircuited capability of all windings.
transformer.
In order by preference, the tests may be
12.2.1.2 Fault Type. The type of fault t o conducted by either of the following:
be applied will be dependent on the available (1) Closing a breaker at the faulted terminal
energy source. Any of the following may be to apply a short circuit t o the previously
used (given in order of preference for three- energized transformer
phase transformers): (2) Closing a breaker at the source terminal
(1) Three-phase source: three-phase short- to apply energy to the previously short-circuited
circuit. transformer
(2) T h r e e - p h a s e source: single phase-to- 12.2.2.2 Tap Connection for Tests. When
ground short circuit. the transformer is provided with taps in any
(3) Single-phase source: simulated three- winding, at least one test satisfying the asym-
phase short circuit. (For Y-connected windings, metrical current requirement shall be made on
apply source or fault between one line termi- the tap connection that calculations predict will
nal and the other two connected together. For produce the most severe mechanical stresses.
deltaconnected windings, apply source or fault Extremes of the tap range, all taps out or all
between two line terminals with no connection taps in, normally produce the most severe
to the other line terminal. Must be repeated for stresses; so tests on these connections are
each of three phases). recommended. Tests on other taps, or connec-
(4) Single-phase source: single-phase short tions in the case of dual-voltage windings, may
circuit on one phase at a time. (Applies t o all be made if required t o ensure design adequacy.
single-phase transformers.) 12.3 Test Requirements
12.2.1.3 Tap Connection for Test. When 12.3.1 Symmetrical Current Requirement -
the transformer is provided with taps in any Two-Winding Transformers. For two-winding
winding, at least one test satisfying the asym- transformers, the required value of symmetrical
metrical current requirement shall be made on winding current for any test shall be deter-
the tap connection that calculations predict mined from the equations in ANSI/IEEE
will produce the most severe mechanical C57.12.01-1979.
stresses. Extremes of the tap range, all taps out
or all taps in, normally produce the most NOTE: The symmetrical current magnitude shall not
exceed the values listed in ANSI/IEEE C57.12.01-1979,
severe stresses; so tests on these connections Section 7. For category I, calculate I,, using trans-
are recommended. Tests on other taps, or con- former impedance only. For categories I1 and 111, cal-
nections in the case of dual-voltage windings, culate I,, using transformer plus system impedance.
See ANSI/IEEE C57.12.01-1979, 7.3.2(2) for addi-
may be made if required t o ensure design tional clarifying information on the determination of
adequacy. 2,.

40
ANSI/IEEE
C57.12.91-1979 IEEE STANDARD TEST CODE FOR DRY-TYPE

12.3.2 Symmetrical Current Requirement - nitudes shall be measured on the transformer


Multiwinding Transfonners and Autotrans- terminals connected t o the energy source. The
formers. For multiwinding transformers and symmetrical peak current shall be established
autotransformers, the required peak value of as one-half of the peak-to-peak envelope of the
symmetrical current in each winding shall be current wave, measured at the midpoint of the
determined by calculation based on applicable second cycle of test current. If the transformer
system conditions and fault types. winding connected t o the energy source is
12.3.3 Asymmetrical Current Requirement. Y-connected, the first-cycle peak asymmetrical
The required firstcycle peak for asymmetrical current in each phase of the winding shall be
winding current tests shall be calculated in measured directly from the oscillogram of
accordance with the equations in ANSI/IEEE terminal currents. If the transformer winding
C57.12.01-1979. connected t o the energy source is Aconnected,
12.3.4 Number of Tests. Each phase of the the first-cycle peak asymmetrical current can
transformer shall be subjected t o a total of six not be determined directly from terminal
tests satisfying the symmetrical current require- measurements at the source terminals. The
ment specified in 12.3.1 and 12.3.2. Two of following alternatives exist:
these tests on each phase shall also satisfy the (1) Measure firstcycle peak asymmetrical
asymmetrical current requirements specified current on oscillograms at the faulted termi-
in 12.3.3. nals, if the faulted winding is Yconnected.
12.4 Test Procedure Convert to source winding current by inverse
12.4.1 Fault Application. To produce the turns ratio
fully asymmetrical current wave specified in (2) If all windings are A-connected, connect
12.3, a synchronous switch shall be used t o metering accuracy current transformers (CTs)
control the timing of fault application. having suitable current ratios inside the delta
12.4.2 Calibration Tests. Calibration tests t o of the source winding and measure firstcycle
establish required source voltage or switch peak asymmetrical current from oscillograms
closing times should be made at voltage levels obtained from these CTs
not greater than 50 percent of the value that (3) If all windings are A-connected, deter-
would produce the specified symmetrical short- mine only symmetrical currents on the external
circuit current. For field testing, calibration lines and time-fault application for the instant
tests should be made at reduced voltage levels, that would produce peak asymmetrical current
if possible. Tests with voltage equal t o or in the required phase winding. (Close breaker
greater than that required to produce 95 per- at a time close to voltage zero for the given
cent of the specified symmetrical short-circuit phase winding, with appropriate timing adjust-
current may be counted toward fulfillment of ment t o account for the R / X ratio of the test
the required number of tests. system plus transformer.)
12.4.3 Terminal Voltage Limits. If tests are 12.4.6 Tolerances on Required Currents. The
to be made by applying the short circuit t o the measured currents, symmetrical or asymmetri-
energized transformer, the no-load source cal, in the tested phase or phases shall not be
voltage shall not exceed 110 percent of the less than 95 percent of the required current.
rated tap voltage unless otherwise approved The required current shall take into account
by the manufacturer. the measured impedance variation resulting
Throughout the course of any test, the voltage from the test, if any, and any significant varia-
at the transformer source terminals shall be tion among the individual per-phase impedances
maintained within a range of 95 to 105 percent inherent in the transformer design.
of that necessary t o produce the required sym-
metrical short-circuit current as determined NOTE: If test equipment parameters cause difficulty
in 12.3.1. in achieving in a single test the prescribed value of the
12.4.4 Temperature Limits. For dry-type first-cycle asymmetrical peak current, without sub-
transformers, the ambient air temperature at jecting the transformer to a higher value of symmetri-
cal short-circuit current than is required, the relationship
the start of the test shall be between 0°C and of these current values may be adjusted by changing
4OoC. the angle at which the synchronous switch is closed to
control the timing of the fault application to obtain
12.4.5 Current Measurements. Current mag- the correct values within the tolerance limits.

41
ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS C57.12.91-1979

12.5 Proof of Satisfactory Performance. The applicable American National Standard product
transfomer under test shall be judged t o have standards.
performed satisfactorily if the visual inspec- 12.5.4 Waveshape of Terminal Voltage and
tion (12.5.1), dielectric tests (12.5.2), and Current. No abrupt changes shall occur in the
temperature test (12.5.3) criteria have been terminal voltage or short-circuit current wave-
satisfactorily met. Recommended terminal shapes during any test.
measurements that may be made during the 12.5.5 Impedance. Impedance measured on
course of the tests but are not required t o be a per-phase basis after the test series shall
made unless specified, are listed in 12.5.4 not differ from that measured before the test
through 12.5.7. If the terminal measurements series by more than the values specified below:
are made and the requirements of 12.5.4 Category I: The allowable variation shall
through 12.5.7 have been met following all be a function of the transformer impedance
tests, it is probable that the transformer has (2,) as follows:
sustained no mechanical damage during the test
2, (per unit) Percentage Variation
series. A composite evaluation of the degree t o
which all criteria of 12.5.4 through 12.5.7 0.0299 or less 22.5 - 500 (2,)
have been met may indicate the need for a 0.0300 or more 7.5
greater or lesser degree of visual inspection t o
confirm satisfactory performance. The evidence Categories I1 or 111: 5 percent allowable for
may be sufficient to permit a judgment of noncircular concentric coils; 2 percent allow-
satisfactory performance t o be made without able variation for circular coils.
complete dielectric tests. A decision to waive The measuring equipment must have the
all or parts of the visual inspection or dielectric demonstrated capability of giving reproducible
test criteria must be based on discussions and readings within an accuracy of f 0.2 percent.
negotiation by all parties involved in specifica- 12.5.6 Low- Voltage Impulse (LVI) Tests.
tion and performance of short-circuit tests. Comparison of oscilloscope traces of LVI cur-
12.5.1 Visual Inspection. Visual inspection rents taken before and after each short-circuit
of the core and coils shall give no indication test shall show no significant change in wave
that there has been any change in mechanical shape. Acceptable conditions and conditions
condition that will impair the function of the requiring further investigation are defined
transformer. The extent of the visual inspec- in 12.5.6.1 and 12.5.6.2.
tion shall be established on the basis of com- 12.5.6.1 Acceptable Conditions
bined evidence obtained from the terminal (1) No LVI trace change occurs during the
measurements described in 12.5.4 through complete test series
12.5.7. If the terminal measurements give no (2) Small changes or amplitude of phase
indication of change in condition, external angle occur following one of the short-circuit
inspection of the core and coils removed from tests, but no further changes occur on subse-
the enclosure or tank may suffice. Any evidence quent tests
of change in condition from more than one of (3) Small changes of amplitude or phase
the terminal measurements would warrant angle occur following one of the short-circuit
disassembly of the windings from the core for tests, but the trace returns t o its original shape
a more detailed inspection. on subsequent tests
12.5.2 Dielectric Tests. The transformer shall 12.5.6.2 Conditions Requiring Further In-
withstand standard applied-voltage and induced- vest igat ion
voltage tests at the full specification level in (1) Large LVI trace changes occur during
accordance with ANSI/IEEE C57.12.01-1979, the course of the test series
or applicable American National Standard (2) Small changes of amplitude or phase
product standards. When impulse tests have angle occur after the first full-amplitude short-
been made prior t o the short-circuit tests, the circuit test, and these changes continue t o grow
impulse tests shall be repeated if specified. with each subsequent test
12.5.3 Temperature Test. The transformer (3) LVI equipment and test procedures3
shall meet the specified average winding tem-
perature rise by resistance values in accor- 3LVI equipment and test procedures will be described
in a new publication now in preparation. See 3.3,
dance with ANSI/IEEE C57.12.01-1979, or footnote 1 , [ 11.

42
ANSI/IEEE
C5 7.12.91-1979 IEEE STANDARD TEST CODE FOR DRY-TYPE

12.5.7 Excitation Current. Excitation cur- Type E, Class I1 performance, or their equal.
rent measured after the test series shall not 13.2.3 Discrete frequency measurements shall
increase above that measured before the test be made when specified o r when test conditions
series by more than 5 percent for stacked- necessitate (See 13.6.1, note.) Instrumentation
type cores. For transformers with wound-core is not presently standardized; however, typical
construction, the increase shall not exceed analyzer bandwidth characteristics deemed
25 percent. The measuring equipment must suitable are one-tenth octave; 1, 3, or 10 per-
have demonstrated capability of giving cent of the selected frequency; or 3, 10, or
reproducible readings with an accuracy of k 0.5 50 Hz.
percent. 13.2.4 A suitable wind screen may be used
12.5.8 Other Diagnostic Measurements. Other where the air velocity due to winds, prevailing
diagnostic measurements may be made during drafts, or microphone locations in the proximity
the course of the tests t o evaluate whether of fans causes the readings to be in error. Suit-
there have been any sudden or progressive able corrections, if necessary, shall be made
changes in the mechanical condition of the for readings with wind screens to ensure that
transformer. Such results may be useful t o the the wind noise effects only are negated.
understanding of the response t o short-circuit
13.3 Test Conditions
forces, but they shall not form part of the
13.3.1 Measurements shall be performed in
proof criteria.
an environment having an ambient level at least
13. Audible Sound-Level Measurements 5 dB, but preferably 10 dB or more, below the
combined level of transformer and ambient
13.1 General. The audible sound generated for the frequency band in which measurements
internally by a transformer is composed of are being made.
discrete tones whose frequencies are even The ambient level shall be established by
multiples of the transformer excitation fre- averaging measurements performed immediately
quency. The audible sound generated by preceding and immediately following the trans-
auxiliary cooling equipment, such as fans, has former tests for at least four microphone loca-
a more broadly and evenly distributed fre- tions spaced equally around the transformer.
quency composition. For an average ambient level 5 dB or more below
The A-weighted measurement characteristic the combined level of transformer and ambient,
best relates how a remote young listener (with the correction shall be applied as follows.
normal hearing) hears the complex transformer-
generated sound and shall be used t o determine
the average sound-level performance of the Difference Correction
transformer. between Average Applied t o Average
For some purposes a frequency distribution Level of Combined Level of Combined
of a transformer’s sound is desirable, and Transformer and Transformer and
when specified, it shall be measured in fre- Ambient and Ambient to Obtain
quency bands (either octave or one-third Average Level Average Level of
octave) or as discrete frequencies, as specified. of Ambient Transformer
13.2 Instrumentation (dB) (dB)
13.2.1 Sound-level measurements shall be 5 -1.6
made with instrumentation that meets the 6 -1.3
requirements of ANSI S1.4-1971 (R 1976), 7 -1.0
Specification for Sound Level Meters, for Type 8 -0.8
2 meters. 9 -0.6
13.2.2 Octave-band or one-third-octave-band 10 -0.4
frequency measurements shall be made, when Over 10 -0.0
specified, with instrumentation that meets
the requirements of ANSI S1.4-1971, for Type
2 meters together with those of ANSI S1.11- Ambient corrections shall be governed by
1966 (R 1976), Specifications for Octave, Half- average level measurements with identical fre-
Octave, and Third-Octave Band Filter Sets, for quency bandwidths for the combined trans-

43
ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS C57.12.91-1979

former and ambient and the ambient alone. straight line perpendicular t o the reference
Where ambient conditions do not comply sound-producing surface at each microphone lo-
with the above, suitable corrections may be cation point. The microphone shall be spaced 1
feasible with steady ambient conditions. The f t (0.30 m) from the reference sound-producing
details and method of making such ambient surface, except that when fans are in operation
corrections shall be determined by those the microphone shall be spaced 6 f t (1.83 m)
responsible for the design and application of from any portion of the transformer coolers
the transformer. cooled by forced air.
Where the difference is less than 5 dB and it 13.4.3 For transformers having an overall
is only desired t o know a level the transformer tank or enclosure height of less than 8 ft
does not exceed, a correction of -1.6 dB may (2.4 m), measurements shall be made at half-
be used. height. For transformers having an overall tank
13.3.2 The transformer shall be located so or enclosure height of 8 f t (2.4 m) or more,
that no acoustically reflecting surface is within measurements shall be made at one-third and
10 ft (3.0 m) of the transformer, other than two-thirds height.
the floor or ground. 13.5 Sound-Level Measurements
13.3.3 The transformer shall be connected 13.5.1 Sound levels shall be measured in con-
for and energized at rated voltage and fre- formance with 13.2.1,13.3,and 13.4 using the
quency at no load, and tests shall be made for sound-level-meter A-weighting characteristic.
the various ratings (AA, AA/FA, AFA, etc)
13.5.2 The average A-weighted sound level is
with fans operating, if appropriate, for the defined as the arithmetic mean of the respec-
rating being tested. tive A-weighted sound-level measurements taken
at each microphone location defined in this
13.4 Microphone Positions section.
13.4.1 The reference sound-producing sur- 13.5.3 When specified, measurements shall
face of a transformer is a vertical surface that also be taken using the sound-level-meter C-
follows the contour of a taut string stretched weighting characteristic.
around the periphery of the transformer or 13.5.4 If ambient conditions necessitate, the
integral enclosure. This contour is to include sound level may be measured using discrete-
coolers, switch compartments, terminal cham- frequency components. (See 13.6.1, note,
bers, etc, but excludes bushings and minor and 13.6.4.)
extensions such as valves, gages, thermometers,
conduit terminal boxes, and projections at or 13.6 Optional Frequency Analysis Measure-
above cover height. ments
In consideration of safety and consistency of 13.6.1 When specified, frequency analyses
measurement, the reference sound-producing shall be made in accordance with 13.2, 13.3,
surface near unenclosed live parts of field- and 13.4 for either octave, one-third-octave,
assembled items such as switches, switchgear, or discrete-frequency measurements. Either the
and terminal compartments or wall-mounted A-weighting, the C-weighting, or the flat re-
bushings, etc, shall be moved outward from the sponse meter characteristic may be used. The
taut string contour such as to be consistent weighting characteristic used shall be reported
with safe worker clearances for the voltage with the data.
class of the live parts termination involved.
NOTE : For a discrete-frequency application, see
13.4.2 The first microphone location point R. T. Hemmes and D. C. Graham, Measurement of Self-
shall coincide with the nameplate. Addit,ional Cooled Transformer Sound Levels in Relatively High
points shall be located at 3 f t (0.91 m) inter- Ambients, ZEEE Transactions on Power Apparatus and
vals, proceeding clockwise in a horizontal Systems, vol PAS-89, Sept/Oct 1970, pp 1657-1662.
direction, as viewed from above, along the
reference sound-producing surface defined 13.6.2 Octave-band or one-third-octave-band
in 13.4.1. frequency analysis measurements shall cover
There shall be no fewer than four microphone the interval of midband frequencies from 63
location points, which may result in intervals through 4000 Hz, inclusive. Discrete-frequency-
of less than 3 ft (0.91 m) for small trans- analysis measurements shall cover the fun-
formers. The microphone shall be located on a damental through the seventh harmonic

44
ANSI/IEEE
C57.12.91-1979 IEEE STANDARD TEST CODE FOR DRY-TYPE

component (fundamental component is twice 14.2 Components Involved in Lifting or


the excitation frequency). Moving
13.6.3 The average level for each frequency 14.2.1 Design tests of components involved
band measured shall be determined by taking in the lifting or moving of transformers shall be
the power average of the individual readings conducted on typical components to verify
about the transformer: thus that the designs conform t o the safety factors
specified in American National Standard dry-
type transformer product standards?

NOTE: Such tests are normally performed on com-


ponents only (arranged t o simulate normal application
conditions) in mechanical testing machines rather than
on complete transformers.
where
14.2.2 Tests of components such as lifting
Lx = average level for the X frequency band lugs shall be made with the test specimen ar-
ranged so that the angle of the lifting cable
Lj = level in the X frequency band at the
with respect t o vertical will be the maximum
ith measurement point angle allowed in applicable standards.
n = total number of measurement points 14.2.3 Tests of components such as pulling
eyes or lugs for rolling or skidding shall be
If the components are with A weighting, the made in two directions:
average is then with A weighting. (1) In a direction parallel to the long axis of
13.6.4 If the average sound level, dB (A) as the transformer
defined in 13.5.2, is t o be determined from the (2) In a direction perpendicular t o the long
individual A -weighted frequency-band measure- axis of the transformer
ments at each microphone position, then an 14.2.4 Tests of jacking facilities shall be
A-weighted sound level shall be calculated for made under conditions simulating typical
each microphone position from the band mea- applications.
surements, as follows:
14.3 Tests of Sealed Dry-Type Transformers
14.3.1 Leak Test. A leak test shall be per-
formed as a routine test to verify the adequacy
of sealing the transformer.
14.3.2 Tank Pressure Tests. Design tests shall
be made at 125 percent of maximum operating
pressure t o demonstrate that sealed dry-type
where tank designs will withstand their maximum
allowable operating pressure. This test pressure
LA = calculated A-weighted sound level
shall not produce a permanent deformation.
Lj = band level with A weighting for the
jth band
n = total number of bands 15. Calculated Data
Finally, the average sound level, dB (A), shall 15.1 Reference Temperatures for Average
be determined as the arithmetic mean of the Winding Rises. The reference temperature for
values of LA for all the microphone locations. determining total losses, voltage regulation, and
efficiency shall be as shown in Table 3.
14. Mechanical Tests 15.2 Total Losses. Total losses are the sum of
the no-load losses and the load losses.
14.1 General. Routine or design mechanical
tests or analyses specified in ANSI/IEEE
C57.12.01-1979 or applicable American Na- 4 M ~ r edetailed information will be found in new publi-
tional Standard product standards shall be con- cations now in preparation. See 3.3, footnote 1 , [ 2 ] ,
ducted as described in this section. [ 3 l , and [ 4 l .
ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS C57.12.91-1979

Table 3 15.4.4 Voltage Regulation Computation -


Reference Temperatures for Determining Two-Winding Transformers. When specified,
Total Losses, Voltage Regulation, the voltage regulation shall be computed as
and Efficiency in 15.4.4.1through 15.4.4.3.
~~~~~~~ ~ ~~
15.4.4.1 Exact Formulas for Calculation
Average of Regulation. Exact formulas for the calcula-
winding temperature Reference tion of regulation are:
rise by resistance temperature
("C) ("C) (1) When the load is lagging:
80 100
115 135 reg = d ( r + p l 2 + (X + q ) 2 -1
150 170
(2) When the load is leading:

reg = d ( r + p ) 2 + (x -a)' -1
15.3 Efficiency. The efficiency of a trans-
former is the ratio of its useful power output where
to its total power input:
p = power factor of load
output - input - losses q = + dl -p2
Efficiency = 7 -
input input
r =resistance factor of transformer

= I - - losses - impedance loss (kW)


input rated kVA
x = reactance factor of transformer
= 1 - losses = + d m .
output + losses impedance kVA
z = impedancefactor =
When specified, . efficiency shall be calculated rated kVA
on the basis of the reference temperature for
The quantities p , q, x , and r are on a per-unit
the average winding temperature rise of the
basis; so the result must be multipled by 100
transformer.
to get the regulation in percent.
15.4.4.2 General Expression for Calcula-
tion of Transformer Regulation. A general
15.4 Voltage Regulation of a Constant- expression for the calculation of transformer
Voltage Transformer regulation that permits calculations t o any
15.4.1 General. The voltage regulation of a degree of precision justified by the supporting
constant-voltage transformer is defined in data is:
ANSI/IEEE C57.12.80-1978. The regulation
may be expressed in percent (or per unit) on
the basis of the rated secondary voltage at full
load.
15.4.2 Reference Temperature. When speci- 21 33
-a6 +-a7
fied, voltage regulation calculations shall be - 16 16
based on the reference temperature of 15.1.
15.4.3 Impedance Wattage and Impedance where reg is the regulation on a per-unit basis
Voltage. The tests for impedance wattage and and a equals a quantity depending on the angle
impedance voltage for use in the computation and magnitude of the transformer impedance,
of voltage regulation may be measured at any the power factor of the load, and the number
convenient temperature and corrected using of windings in the transformer.
the correction factors applying to the type of The quantity a for the calculation of the per-
conductor material in the windings (see 5.3 unit regulation of a two-winding transformer is
and 9.4). determined as follows:

46
ANSI/IEEE
C57.12.91-1979 IEEE STANDARD TEST CODE FOR DRY-TYPE

z2 15.4.4.3 Three-phase to Two-Phase Trans-


I a = zcos($+8) +-
2 formers. For the calculation of the regulation
for three-phase to two-phase transformation,
where proceed as follows:
(1) For the per-unit regulation of main
r = resistance factor phase, use the impedance of the main trans-
former for substitution in the formula selected
-- impedance loss (kW) for use.
rated kVA (2) For the per-unit regulation of the teaser
z = impedance factor phase, use the sum of the impedance of the
teaser transformer plus the interlacing imped-
- impedance kVA
- ance of the main transformer for substitution
rated kVA
in the formula selected for use.
x = reactance factor (3) To determine the interlacing impedance,
= + 4 2 2 - r2 connect the two ends of the three-phase winding
of the main transformer together and impress
$ = impedance angle of transformer im- between this common connection and the
pedance 50 percent tap a voltage sufficient to pass
r three-phase line current in the supply lines.
cos $ = -
z (4) The voltage thus determined is the inter-
= power factor of load cos 8 lacing impedance voltage and is to be put on a
p
per-unit basis by reference to the rated voltage
8 = phase angle of load current - posi- of the teaser transformer on the 86.6 percent
tive for leading current, negative for tap.
lagging current

47
ANSI/IEEE
DISTRIBUTION AND POWER TRANSFORMERS C57.12.91-1979

Appendix

(?is Appendix is not a part o f ANSI/IEEE C57.12.91-1979, American National Standard Test Code for Dry-Qpe
hstribution and Power Transformers.)

Minimum Information to be Included in Certified Test Data

Al. Order Data (3) Impedance


(1)Purchaser (4)Temperature rise
(2)Purchaser's order number (5) Applied-voltagetest
(3) Manufacturer's requisition number (6j Induced-voltage test
(4) Date of test (7)Impulse test data in accordance with
ANSI/IEEE C57.98-1968,American National
A2. RatingData Standard Guide for Transformer Impulse Tests
(1) Cooling class (Appendix to C57.12.90-1968)(when specified)
(2)Number of phases (8) Sound-level tests (when specified)
(3) Frequency
(4)Insulation medium A4. Calculated Data
(5)Temperature rise (1) Correction of resistances and losses to
(6)Polarity standard temperature basis
(7)Winding ratings (volts, kVA) (2) Regulation (if specified)
A3. Test Data (by individual serial number) A5. Certification Statement and Approval
(1) Winding resistances NOTE: All reported data should be corrected to
(2) Losses: no-load, load, total standard temperatures.

.
..
IEEE Standards of Special Interest
t o the Power Engineer
IEEE Title
Std
85-1973 Test Procedure for Airborne Sound Measurements on Rotating Electric Ma-
chinery
259-1974 Test Procedure for Evaluation of Systems of Insulation for Specialty Trans-
formers
266-1969 Test Procedure for Evaluation of Insulation Systems for Electronics Power
Transformers (Reaff 1975)
346-1973 Definitions in Power Operations Terminology Including Terms for Reporting
and Analyzing Outages of Electrical Transmission and Distribution Facilities
and Interruptions to Customer Service
430-1976 Procedures for the Measurement of Radio Noise from Overhead Power Lines
454-1973 Recommended Practice for the Detection and Measurement of Partial Dis-
charges (Corona) During Dielectric Tests
ANSI C2 National Electrical Safety Code, 1977 edition

ANSI/IEEE
C37.91-1972 Guide for Protection Relay Applications t o Power Transformers
C37.95-1973 Guide for Protective Relaying of Utility Consumer Interconnections
C57.12.00-1980 Standard General Requirements for Liquid Immersed Distribution, Power
and Regulating Transformers (Revision of ANSI/IEEE C57.12.00-1973)
C57.12.01-1979 Standard General Requirements for Dry-Type Distribution and Power Trans-
formers
C57.12.80-1978 Terminology for Power and Distribution Transformers
C57.12.90-1973 Test Code for Distribution, Power and Regulating Transformers
C57.12.90a-1978 Distribution and Power Transformer Short-circuit Test Code (Revision of
ANSI/IEEE C57.12.90a-1974)
C57.12.91-1979 Standard for Dry-Type Transformers
C57.13-1978 Standard Requirements for Instrument Transformers (Revision of ANSI
C57.13-1968)
C57 -98-1968 Guide for Transformer Impulse Tests (Appendix to C57.12.90-1973)
C57.100-1974 Test Procedure for Thermal Evaluation of Oil-Immersed Distribution Trans-
formers
C57.104-1978 Guide for the Detection and Determination of Generated Gases in Oil Im-
mersed Transformers and their Relation to the Serviceability of the Equip-
men t
C57.105-1978 Guide for Application of Transformer Connections in Three-phase Distri-
bution Systems
C57.106-1 977 Guide for Acceptance and Maintenance of Insulating Oil in Equipment
(Revision of IEEE Std 64-1969)

For a free catalog of IEEE Standards write the


Institute of Electrical and Electronics Engineers, Inc
345 East 47th Street, New York, N.Y. 10017, U.S.A.

You might also like