PRIMAIRY
LARGE SINGLE SPLIT
FIXED SPEED SERIES | COOLING ONLY
–
Johnson Controls - Hitachi Air Conditioning
Da Nang Office
Floor 9, Thanh Loi Tower, 249 Nguyen Van Linh,
Vinh Trung Ward, Thanh Khe Dist., Da Nang City
Telephone: (84.236) 3565 230
Ha Noi Office
Floor 2, Thang Long Tower, 98A Nguy Nhu Kon Tum,
Nhan Chinh Ward, Thanh Xuan Dist., Ha Noi City
Telephone: (84.24) 37 723 478 Fax: (84.24) 37 723 480
Training Center
Floor 8, Standard Factory B, Tan Thuan EPZ, Dist. 7,
Ho Chi Minh City
Email: info-vn@jci-hitachi.com
Website: hitachiaircon.vn
Hotline: 18006202
The specifications of this catalog may change without prior notice to allow Find the products Hitachi Cooling & Heating
Hitachi Cooling & Heating to incorporate the latest innovations for its customers.
The information contained in this catalog is merely informative. with the best service and conditions at your
Hitachi Cooling & Heating declines any responsibility in the broadest sense, for Hitachi Distributor.
damage, direct or indirect, arising from the use and / or interpretation of the
recommendations in this catalog.
TNZGN(M)H1-C-1903
–
06 Welcome
INDEX
16 Introducing PRIMAIRY
18 Applications
20 General Features
32 Indoor Units
40 Control Systems
44 Specification Tables
01 02
Living
Harmony
03
04
Weӏcome.
WELCOME
–
The beauty of baӏance
No matter what the weather is like outside,
when you’re indoors, you want to have
complete control over your environment.
At work or play, awake or asleep, you’re free
to create your own atmosphere; balancing
energy with calm, sound with silence and
light with shade. It’s the same for cooling
and heating.
05 06
–
– –
WELCOME
We live & breathe The future together
innovation Living Harmony puts people first. By balancing the human needs of our customers with
Since 1952, Hitachi’s Cooling & Heating an uncompromisingapproach to innovation and quality, we can continue to create the
technology has been helping make life technologies for a more comfortable and balanced world.
more harmonious for people around
the world. Today, our long heritage of Your world. We live in it together.
precision Japanese engineering ensures
that no detail is overlooked in our quest
to create Living Harmony.
07 08
Your world.
We live in it
together.
09
10
WELCOME
as shops, restaurants, cafés, creative
studios, galleries, workshops
and classrooms.
11 12
FIXED SPEED SERIES | COOLING ONLY TYPE
Striving for perfection
A set of strong beliefs and practices at Hitachi have paved the way for generations
of efficient products.PRIMAIRY represent the culmination of much collective effort,
giving the series a great advantage – and making PRIMAIRY the right way to go, for
you, your employees and your customers.
WELCOME
and quality of air in your workspace is our
role as a partner. An integral element of this
is durability.
13 14
–
Introducing
PRIMAIRY
PRIMAIRY’s aims
PRIMAIRY is an air system series made to
cope with the foremost daily needs of small
business owners and people living and working
in small to medium-sized spaces around the
world. The name ‘PRIMAIRY’ signifies the
goal of addressing the ‘Primary’ needs of
people in terms of giving them access to
cleaner, consistently modified air in
their environments.
Some features may not apply to the units sold in your country.
– –
Reliable partners Diligent
manufacturing
WELCOME
for small businesses
The need for a comfortable and quiet Stable operation of key equipment like the
environment as the basis for a small business compressor, in typical and extreme temperatures,
to thrive. Reliability, adaptability to each the inclusion of auto restart after power failure
and self-diagnosis of faults are all the result
56°C 30%
physical setting and precise control for users
are the technical priorities of PRIMAIRY. of improvement and application of research.
The careful design and continuous support in
High ambient cooling Maintains 30% refrigerant level maintenance of machines indicates how much
Strong cooling for high ambient Ensures the strong performance of the we care about ensuring comfort in your space.
temperatures, enabling delivery of refrigerant circulation components.
reliable cooling to users who require When the refrigerant volume is less than
consistent resistance to high levels of 30%, the unit automatically registers this
natural heat. System is designed for and displays the relevant fault code,
temperatures of up to 56°C. prompting users to maintain the system. – –
Design for different spaces Your need is our motivation
15 16
–
Your spaces
& PRIMAIRY
APPLICATIONS
Restaurant & Café Retail Space Small Work Space
“Running a café means noise, buzz, “I work with clothes, and the fabric “I stay late at the office along with
activity and trapped heat. Having a can heat up in summer and make my colleagues if there is a big project
correct and consistent A/C lets my things stuffy. The store is cold in to finish. Having a comfortable
customers relax and enjoy their winter. Without the system to setting is essential, and the airflow
drinks – and I can see the difference regulate things all year round, the system that management installed
in their moods.” seasons would really get to me.” is a big part of this.”
17 18
–
General
Features
GENERAL FEATURES
PRIMAIRY responds sensitively to air temperature and maintains
it at the desired level, using just the right amount of energy.
19 20
–
COMFORT & RELIABILITY
EXPANSION INTERFACE
GENERAL FEATURES
A multi-speed fan helps satisfy various Units are automatically returned to previous
airflow requirements. operation conditions after a power outage,
Connect for simplified operation.
Signal
lines QUIET OPERATION
Connect
Units have a quiet mode that reduces the fan speed
and the frequency of the compressor, resulting in a
low operation noise, keeping your family and
neighbors content.
ERROR SELF-DIAGNOSIS FUNCTION Outdoor control board
Cassette unit
The error code is clearly displayed on the
diagnostic panel of the outdoor unit for
quick troubleshooting and maintenance.
flashes, various faults are represented. It can be used to check outdoor running parameters.
Floor Ceiling Convertible unit
21 22
–
EFFICIENCY
EFFICIENCY RATIO
GENERAL FEATURES
2.0 2.0 2.0
High cooling performance within a wide
1.0 1.0 1.0 ambient temperature range.
Powerful cooling performance at standard and low ambient temperatures: conditions. System is designed for cooling at -15°C.
High efficiency attributed to high performance twin rotary compressor.
Twin rotors balances out centrifugal load resulting from rotation. Reduce compressor vibration, lower noise level, and HIGH EFFICIENCY FIN
HIGH EFFICIENCY HEAT EXCHANGER
increase reliability.
23 24
–
RELIABILITY
GENERAL FEATURES
An encompassing metal box design ensures full - Fan motor overheating protection Ensures the compressor will operate in the
product safety. - Compressor overheating protection safety range, and prevent the damage caused
by refrigerant leakage.
Comments:
Comments: only applicable for model above 3.0HP.
25 26
–
RELIABILITY
A hydrophilic aluminum fin enhances heat exchanging performance by increasing water mobility
on fin surface and preventing water droplets from forming blockage between fins. The blue coating
enhances protection from corrosion resulting from environmental and microbiological factors,
increasing reliability and ensuring performance.
GENERAL FEATURES
The indoor unit will stop operation automatically and show
an error code when the refrigerant charging amount is lower
than 30%, which can avoid the compressor being damaged
by high temperature due to refrigerant leakage.
The coating prevents water droplets collecting on the fins and causing blockages.
27 28
–
DESIGN
FLEXIBILITY
340mm
1,410mm
Dimension (W×H×D) Dimension (W×H×D) Long piping and large height difference
GENERAL FEATURES
715×482×240mm 810×585×280mm Up to 50m piping run and 30m height applications can
HP Class HP Class be covered, high flexibility in installation configuration.
1.0-1.5 2.0
Outdoor unit above the indoor unit.
Liquid pipe
Gas pipe
Diameter (Gas) Inch 1/2 1/2 1/2 5/8 3/4 3/4 3/4
Max Length m 15 15 20 30 30 50 50
Max Height m 7.5 7.5 15 15 20 30 30
29 30
– –
LINE-UP OVERVIEW
Ducted unit • • •
• • •
Cassette unit • • •
• •
Air moves within your interior spaces, making living and working
more comfortable. The balanced design of the indoor units is key • •
to making them unobtrusive, reliable and ultra-efficient. The Indoor
unit’s flexibility solves users' difficulties in conditioning their spaces, Floor Ceiling • •
Convertible unit
creating a comfortable environment for people to focus on their
work or their business.
•
INDOOR UNITS
• •
–
FREEDOM OF CHOICE
Which unit or units should you choose?
There may be more than one good option, but you
should take a little time to find the one that works
best for you. Within the category of PRIMAIRY, there
are three main units: Ducted, Cassette, and Floor
Ceiling Convertible.
31 32
CASSETTE
– COMFORT
4-Way
HCRA31NEWH HCWA21NEWH
(Standard) (Optional)
Cassette units are especially suited to narrow ceiling cavities or high ceilings.
They fit to a standard ceiling grid and can be easily incorporated between
light panels and other overhead fixtures.
INDOOR UNITS
Louver opens up to: 90º
DESIGN FLEXIBILITY
SLEEP UP/DOWN
RESET
33 34
DUCTED
– COMFORT
DESIGN FLEXIBILITY
INDOOR UNITS
to ensure a uniform gust of air around a complex space. A system can be set up in a
short time and will run reliably into the future.
Ducted unit
For example: (Top view)
60Pa: 120Pa:
Air outlet 1
Ducted unit
(Top view)
Wall
Air outlet 2
Air outlet
Cement
Compact design
Height: 190mm
This compact design minimizes the space between the cement (1.0~2.0HP class)
and dropped ceiling, allowing a higher space within the room. Dropped ceiling
35 36
FLOOR CEILING
CONVERTIBLE
– COMFORT
230mm
Air Outlet
After a straightforward installation the unit blends into your interior. installation can adapt to many different
The fresh air intake, fan housing and other features have all been room layouts, business types or living spaces. Air Outlet
INDOOR UNITS
680mm
designed for discretion, comfort and control. Air Inlet
Air Inlet
230mm
37 38
–
Controllers
CONTROL SYSTEMS
39 40
– –
REMOTE CONTROLLER WIRED CONTROLLER
The remote control is practical and intuitive in design, with a You can keep an eye on exactly what your system is doing
HCRA31NEWH HCWA21NEWH
Operation mode
Heating mode Dry mode
Cooling mode Fan mode
SIGNAL EMITTING WINDOW
Auto mode
/TRANSMISSION SIGN
CONTROL SYSTEMS
DISPLAY
WEEKLY TIMER
41 42
–
Specifications
SPECIFICATIONS
43 44
SPECIFICATIONS
–
SPECIFICATIONS
Net/Gross weight kg 19/25 19/25 20/27 28/35 30/39 33/42 33/42
Panel Dimension (WxHxD) mm 650×30×650 650×30×650 650×30×650 950×37×950 950×37×950 950×37×950 950×37×950
Packing(WxHxD) mm 730×130×730 730×130×730 730×130×730 1,025×120×1,015 1,025×120×1,015 1,025×120×1,015 1025×120×1,015
Net/Gross weight kg 2.4/ 5 2.4/ 5 2.4/ 5 6.5/9.5 6.5/9.5 6.5/9.5 6.5/9.5
Drainage water pipe diameter mm IDΦ21 IDΦ21 IDΦ21 IDΦ32 IDΦ32 IDΦ32 IDΦ32
Controller Remote controller Remote controller Remote controller Remote controller Remote controller Remote controller Remote controller
Operation temperature °C 16~30 16~30 16~30 16~30 16~30 16~30 16~30
Qty’per 20’ /40’ /40'HQ(Indoor unit) Set 147/315/384 147/315/384 147/315/384 72/144/168 72/144/168 60/120/144 60/120/144
Compressor Type ROTARY ROTARY ROTARY ROTARY ROTARY ROTARY ROTARY
Rated current(RLA) A 4.1 4.1 7.2 11.4 5.9 7.8 9.2
Refrigerant oil type/ml VG74 /350 VG74 /350 ATMOS-RB68EP/600 α68HES-H/570 α68HES-H/2,600 α68HES-H/1,600 α68HES-H/1,600
Outdoor fan Qty 1 1 1 1 1 2 2
motor
Input W 25 25 41 118 160 74/74 145/145
Speed r/min 850 850 910 880/830/540 880/740/660 900/800/700 700/600/500
Outdoor noise level (sound pressure) dB(A) 55 55 54 56 62 55 58
Throttle type Throttle Valve Throttle Valve Throttle Valve Throttle Valve Capillary Capillary Capillary
Outdoor unit Dimension(WxHxD) mm 715×482×240 715×482×240 810×585×280 860×665×310 885×795×366 950×1,050×340 950×1,386×340
Packing(WxHxD) mm 830×530×315 830×530×315 940×640×420 990×730×450 1,050×890×500 1,110×1,200×460 1,110×1,530×460
Net/Gross weight kg 28/30 28/30 42/45 51/56 67/71 96/103 106/116
Refrigerant type/Quantity Type R410A R410A R410A R410A R410A R410A R410A
Charged volume kg 0.85 0.85 1.30 1.58 2.60 2.40 3.10
Refrigerant piping Liquid side/ Gas side mm(inch) Φ6.35/Φ12.7(1/4"/1/2") Φ6.35/Φ12.7(1/4"/1/2") Φ6.35/Φ12.7(1/4"/1/2") Φ9.52/Φ15.88(3/8"/5/8") Φ9.52/Φ19(3/8"/3/4") Φ9.52/Φ19.05(3/8"/3/4") Φ9.52/Φ19.05(3/8"/3/4")
Max. pipe length m 15 15 20 30 30 50 50
Max. difference in level m 7.5 7.5 15 15 20 30 30
Ambient temperature Cooling °C -15~+43 -15~+43 -15~+43 -15~+43 -15~+43 -15~+43 -15~+43
Qty’per 20’ /40’ /40'HQ(Outdoor unit) Set 204/412/520 204/412/520 102/204/272 90/186/186 44/92/96 26/53/106 26/53/53
45 46
SPECIFICATIONS
–
SPECIFICATIONS
Packing(WxHxD) mm 1,070×236×580 1,070×236×580 1,070×236×580 1,170×340×870 1,550×410×940 1,550×410×940 1,550×410×940
Net/Gross weight kg 19/25 19/25 19/25 30/35 54/62 54/62 54/62
Drainage water pipe diameter mm ODΦ32 ODΦ32 ODΦ32 ODΦ32 ODΦ32 ODΦ32 ODΦ32
Controller Wired controller Wired controller Wired controller Wired controller Wired controller Wired controller Wired controller
Operation temperature °C 16~30 16~30 16~30 16~30 16~30 16~30 16~30
Qty’per 20’ /40’ /40'HQ(Indoor unit) Set 200/440/484 200/440/484 200/440/484 84/182/182 35/75/90 35/75/90 35/75/90
Compressor Type ROTARY ROTARY ROTARY ROTARY ROTARY ROTARY ROTARY
Rated current(RLA) A 4.1 4.1 7.2 11.4 5.9 7.8 9.2
Refrigerant oil type/ml VG74 /350 VG74 /350 ATMOS-RB68EP/600 α68HES-H/570 α68HES-H/2,600 α68HES-H/1,600 α68HES-H/1,600
Outdoor fan motor Qty 1 1 1 1 1 2 2
Input W 25 25 41 118 160 74/74 145/145
Speed r/min 850 850 910 880/830/540 880/740/660 900/800/700 700/600/500
Outdoor noise level (sound pressure) dB(A) 55 55 54 56 62 55 58
Throttle type Throttle Valve Throttle Valve Throttle Valve Throttle Valve Capillary Capillary Capillary
Outdoor unit Dimension(WxHxD) mm 715×482×240 715×482×240 810×585×280 860×665×310 885×795×366 950×1,050×340 950×1,386×340
Packing(WxHxD) mm 830×530×315 830×530×315 940×640×420 990×730×450 1,050×890×500 1,110×1,200×460 1,110×1,530×460
Net/Gross weight kg 28/30 28/30 42/45 51/56 67/71 96/103 106/116
Refrigerant type/Quantity Type R410A R410A R410A R410A R410A R410A R410A
Charged volume kg 0.85 0.85 1.30 1.58 2.60 2.40 3.10
Refrigerant piping Liquid side/ Gas side mm(inch) Φ6.35/Φ12.7(1/4"/1/2") Φ6.35/Φ12.7(1/4"/1/2") Φ6.35/Φ12.7(1/4"/1/2") Φ9.52/Φ15.88(3/8"/5/8") Φ9.52/Φ19.05(3/8"/3/4") Φ9.52(3/8")/Φ19.05(3/4") Φ9.52(3/8")/Φ19.05(3/4")
Max. pipe length m 15 15 20 30 30 50 50
Max. difference in level m 7.5 7.5 15 15 20 30 30
Ambient temperature Cooling °C -15~+43 -15~+43 -15~+43 -15~+43 -15~+43 -15~+43 -15~+43
Qty’per 20’ /40’ /40'HQ(Outdoor unit) Set 204/412/520 204/412/520 102/204/272 90/186/186 44/92/96 26/53/106 26/53/53
47 48
SPECIFICATIONS
–
Indoor air flow Rated(Hi/Med/Lo) m3/h 800/700/600 1,400/1,100/900 1,700/1,650/1,500 2,000/1,800/1,600 2,000/1,800/1,600
Indoor noise level (Sound pressure)(Hi/Med/Lo) dB(A) 41/38/36 52/50/46 57/54/52 53/52/50 53/52/50
SPECIFICATIONS
Packing (WxHxD) mm 1,100×350×820 1,100×350×820 1,400×350×820 1,690×350×820 1,690×350×820
Controller Remote controller Remote controller Remote controller Remote controller Remote controller
Qty’per 20’ /40’ /40'HQ(Indoor unit) Set 84/168/196 84/168/196 66/132/154 42/84/98 42/84/98
Throttle type Throttle Valve Throttle Valve Throttle Valve Capillary Capillary
Refrigerant piping Liquid side/ Gas side mm(inch) Φ6.35/Φ12.7(1/4'/1/2') Φ9.52/Φ15.88(3/8'/5/8') Φ9.52/Φ19(3/8"/3/4") Φ9.52/Φ19.05(3/8"/3/4") Φ9.52/Φ19.05(3/8"/3/4")
Qty’per 20’ /40’ /40'HQ (Outdoor unit) Set 102/204/272 90/186/186 44/92/96 26/53/106 26/53/53
49 50