The specifications of this catalog may change without prior notice to allow
Hitachi Cooling & Heating to incorporate the latest innovations for its
customers.
The information contained in this catalog is merely informative.
Find the products of Hitachi
Hitachi Cooling & Heating declines any responsibility in the broadest sense, Cooling & Heating with the best
for damage, direct or indirect, arising from the use and / or interpretation service and conditions at your
of the recommendations in this catalog. Hitachi Distributor
2304-HNSQ-3
–
Welcome The beauty of balance
No matter what the weather is like outside,
when you're indoors, you want to have complete
control over your environment. At work or play,
awake or asleep, you're free to create your own
atmosphere; balancing energy with calm, sound
with silence and light with shade. It's the same for
cooling and heating.
WELCOME
technologies for a more comfortable and
balanced world.
02
03
Helping you form
an ideal living environment
SET FREE mini is the pinnacle of indoor climate control technology.
Our versatile outdoor units, indoor units, and control devices deliver tailored solutions for every
type of living space, providing a comfortable and enjoyable living environment for all.
With SET FREE mini, we don't just gratify our customers, we transform the lives of architects,
installers, and all those involved in space design.
• Our innovative design ensures that the outdoor unit • Our outdoor unit provides unparalleled piping flexibility,
blends seamlessly into your surroundings, creating a making the design process easier and installation costs
harmonious aesthetic without any visual distractions for more affordable.
your neighbors. • Thanks to its high-static pressure design, our outdoor
• Our high-capacity outdoor unit allows for a more flexible unit is suitable for a wide range of applications in various
installation process, saving valuable space and ensuring weather and installation conditions.
that your living environment remains uncluttered and • With a diverse range of indoor units, our system can be
spacious. customized to meet the unique needs of any space.
• Our units are both energy-efficient and compact, boasting
a small body with a large capacity to maximize comfort
while minimizing space requirements.
• Our cutting-edge technology provides you with higher • Our outdoor unit features a night-shift (low-noise) mode,
efficiency, not only in cooling EER but also in heating making it ideal for residential areas where noise pollution
COP, ensuring that you can enjoy a comfortable indoor is a concern.
environment while reducing energy costs. • Our system can efficiently operate in extreme weather
• Our VRF systems are designed to provide you with greater conditions with ambient temperatures up to 52.0°C for
–
control over your indoor environment, with individual cooling operations and as low as -20.0°C for heating
controllers and a centralized controller that allow you to operations. This ensures that our units can perform
optimize the energy-saving operation of your HVAC system, consistently and reliably, no matter the weather.
keeping your energy bills under control without sacrificing
Introducing
comfort.
SET FREE mini • Our outdoor units are equipped with several DIP switches
located in the front for easier test-runs and diagnosis.
This design helps streamline the installation process and
enables quick troubleshooting to minimize downtime,
making it an ideal solution for businesses seeking
• Our slim and lightweight outdoor units make installation a
breeze, allowing installers to complete their work quickly
and efficiently.
• Our H-LINK technology provides flexible connection
options between the centralized controller, outdoor unit,
maximum operational efficiency. and indoor units, allowing for a custom configuration
tailored to your needs.
• Our outdoor unit offers four directions of piping, providing
04
flexibility and ease of installation at any site.
05
–
LINE UP OVERVIEW
990mm
800mm
–
Outdoor units 950mm
8.0HP Class/22.4KW/25.0KW/122kg
9.0HP Class/24.1KW/26.0KW/122Kg
320mm 1,100mm 390mm
10.0HP Class/28.0KW/31.5KW/147Kg
11.0HP Class/30.0KW/33.0KW/165Kg
12.0HP Class/33.5KW/37.5KW/165Kg
2.0
1.0
0.0
3.0 3.5 4.0 4.5 5.0 6.0 6.5 7.0 8.0 9.0 10.0 11.0 12.0 HP Class
The EER is tested under the following conditions when it is combined with test indoor units.
For EER: I ndoor temperature: 27°C DB/19°C WB; Outdoor temperature: 35°C DB
Pipe length: 10m; Pipe lift: 0m
(W/W)
5.0
4.20 4.19 4.14 3.99 3.96
3.90
4.0 3.64 3.63 3.62 3.62 3.71
3.41 3.47
3.0
2.0
1.0
0.0
3.0 3.5 4.0 4.5 5.0 6.0 6.5 7.0 8.0 9.0 10.0 11.0 12.0 HP Class
The COP is tested under the following conditions when it is combined with test indoor units.
For COP I ndoor temperature: 20°C DB; Outdoor temperature: 7°C DB/6°C WB
Pipe length: 10m; Pipe lift: 0m
30Pa
HIGH EXTERNAL PRESSURE OF OUTDOOR UNIT FOUR DIRECTIONS OF PIPING IN OUTDOOR UNIT
High external static pressure up to 30Pa is available in order to Front & Right Rear Bottom
avoid air short-circuit conditions. This ensures that the outdoor
unit runs with a good ventilating condition under different
conditions of installation.
30Pa
Stop valve built with 4-directional outlet piping for easier pipe installation.
The refrigerant pipes can connect the stop valves from the front and right, rear and bottom of the unit.
DESIGN FLEXIBILITY
48.0
emission and allows the system to be running stably
1st branch multi kit under high ambient conditions.
Continuous Cooling
Operation Range
-5.0
Gas pipe Liquid pipe
3 E-102SN (3.0~9.0HP)
E-162SN (10.0~12.0HP) 21.0 32.0
1 Indoor Air Inlet Temperature (°C DB)
4 2
As low as -20.0°C ambient temperature for heating operations
• As low as -15.0°C stable running
24.0
HP Class 3.0 3.5 4.0 4.5 5.0 6.0 6.5 7.0 HP Class 8.0 9.0 10.0 11.0 12.0
Model unit RAS-3.0HNSKQ RAS-3.5HNSKQ RAS-4.0HNSKQ RAS-4.5HNSKQ RAS-5.0HNSKQ RAS-6.0HNSKQ RAS-6.5HNSKQ RAS-7.0HNSKQ Model unit RAS-080HNBSTQ RAS-090HNBSTQ RAS-100HNBSTQ RAS-110HNBSTQ RAS-120HNBSTQ
Power Supply V/Ph/Hz 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 Power Supply V/Ph/Hz 380-415/3/50 380-415/3/50 380-415/3/50 380-415/3/50 380-415/3/50
Cooling kW 8.0 10.0 11.2 12.5 14.0 15.5 18.0 20.0 Cooling kW 22.4 24.1 28.0 30.0 33.5
Capacity Capacity
Heating kW 9.5 11.2 12.5 14.0 16.0 17.0 20.0 22.4 Heating kW 25.0 26.0 31.5 33.0 37.5
Cooling kW 2.00 2.56 3.02 3.61 4.30 5.15 5.46 5.85 Cooling kW 6.36 7.20 8.20 9.10 10.60
Power Input Power Input
SPECIFICATIONS
Working Cooling Stable Work at -5.0~48.0°C DB and Interval at 48.0~52.0°C DB Working Cooling Stable Work at -5.0~48.0°C DB and Interval at 48.0~52.0°C DB
Temp. Range Heating Stable Work at -15.0~24.0°C DB and Interval at -20.0~-15.0°C DB Temp. Range Heating Stable Work at -15.0~15.5°C DB and Interval at -20.0~-15.0°C
Refrigerant Control Mode Microcomputer-controlled Electronic Expansion Valve Refrigerant Control Mode Microcomputer-controlled Electronic Expansion Valve
Tubing Connection Method Flare Connection Tubing Connection Method Flare Connection
Total Liquid Pipe Total Liquid Pipe
m 30 40 40 70 70 70 120 120 m 300 300 250 250 250
Length Length
Between ODU Between ODU
m 25 25 25 60 60 60 75 75 m 80 80 100 100 100
and farthest IDU and farthest IDU
Maximum Between 1st Maximum Between 1st
Piping Length Branch Multi Kit m 20 20 20 30 30 30 30 30 Piping Length Branch Multi Kit m 40 40 40 40 40
and Farthest IDU and Farthest IDU
Between Each Between Each
Multi Kit and m 10 10 10 10 10 10 10 10 Multi Kit and m 15 15 15 15 15
Each IDU Each IDU
Notes: Notes:
1. The EER and COP are tested under the following working conditions, when the outdoor unit is connected to the special combination of indoor units. 1. The EER and COP are tested under the following working conditions, when the outdoor unit is connected to the special combination of indoor units.
Working conditions for testing EER Working conditions for testing COP Working conditions for testing EER Working conditions for testing COP
• Indoor temperature: 27.0°C DB/19.0°C WB • Indoor temperature: 20.0°C DB • Indoor temperature: 27.0°C DB/19.0°C WB • Indoor temperature: 20.0°C DB
• Outdoor temperature: 35.0°C DB • Outdoor temperature: 7.0°C DB/6.0°C WB • Outdoor temperature: 35.0°C DB • Outdoor temperature: 7.0°C DB/6.0°C WB
• Pipe length: 10.0 metre • Pipe length: 10.0 metre • Pipe length: 10.0 metre • Pipe length: 10.0 metre
• Pipe lift: 0 metre • Pipe lift: 0 metre • Pipe lift: 0 metre • Pipe lift: 0 metre
2. Noise test conditions are specified below: Noise is tested 1.5 metre above ground level and 1.0 metre away from the surface of the external service 2. Noise test conditions are specified below: Noise is tested 1.5 metre above ground level and 1.0 metre away from the surface of the external service
board on the outdoor unit. Noise parameters are tested in a semi-anechoic chamber. board on the outdoor unit. Noise parameters are tested in a semi-anechoic chamber.
3. Please consult your local distributor for indoor unit combination limitations. 3. P
lease consult your local distributor for indoor unit combination limitations.
6.5HP,7HP
* Indicates that there are pipe adapters in the outdoor unit, which are used to adjust the gas pipe between the outdoor unit and the first branch.
Thus the φ19.05 diameter pipe is converted to φ22.2 diameter pipe in the model.
** Indicates that there is a pipe adapter in the model, which is used to adjust the gas pipe length between the outdoor unit and the first branch. Thus
the φ19.05 diameter pipe is converted to a φ25.4 diameter pipe.
12
13
–
VRF INDOOR UNITS We offers a variety of indoor units in
its line-up to achieve comfortable air
conditioning that flexibly addresses
various applications and shapes of
16 SOLUTIONS TO BE MEMORIZED space. By raising the "quality" of the
16 WIDE RANGE OF LINE-UP air, we believe that the "quality" of time
17 GENTLECOOL customers spend there will also be
17 CROWDSENSE enhanced.
26 DUCTED
28 HIGH ESP TYPE [RPIH-HNAUN1Q] (AC MOTOR TYPE)
MEDIUM ESP TYPE [RPIM-HNAUN1Q] (AC MOTOR TYPE)
15
29 LOW ESP TYPE [RPIL-HNAUN1Q] (AC MOTOR TYPE)
COMPACT TYPE [RPIZ-HNDTS1Q] (DC MOTOR TYPE)
30 COMPACT TYPE [RPIZ-HNATN1Q] (AC MOTOR TYPE)
56 VENTILATIONS
14
15
– –
SOLUTIONS TO BE MEMORIZED SOLUTIONS TO BE MEMORIZED
WIDE RANGE OF LINE-UP TEMPERATURE MANAGEMENT FOR SUPERIOR COMFORT
DUCTED
HIGH ESP TYPE MEDIUM ESP TYPE LOW ESP TYPE COMPACT TYPE GENTLECOOL
(AC MOTOR TYPE) (AC MOTOR TYPE) (AC MOTOR TYPE) (DC MOTOR TYPE)
RPIH-HNAUN1Q RPIM-HNAUN1Q RPIL-HNAUN1Q RPIZ-HNDTS1Q RCI-FSRP RCIM-FSRE RCD-FSR RCS-FSR RPK-FSRM RPC-FSR
(all panels) PC-ARFG1
RCI-FSKDN1Q
∙ Cooling Capacity: ∙ Cooling Capacity: ∙ Cooling Capacity: ∙ Cooling Capacity: Set your comfortable temperature not only for “Room” but also for “Air” in cooling operation. To make your room reach to the desired
8.4-16.0kW ESP: High ESP 2.2-7.1kW ESP: Medium 2.2-16.0kW 2.2-7.1kW Fan air flow rate
(90/120/180Pa) ESP (50/80Pa for 0.8-2.5HP ESP: Low ESP (30Pa for up to 6 taps (DC motor
temperature faster, the discharged air from the indoor unit can be sometimes much cooler, causing discomfort at the beginning of
class) 0.8-2.5HP class, 60Pa for model only) operation. Now, you can choose “discharge air temperature = your own comfort level”, as you like, by our Advanced color wire remote
3.0-6.0HP class) ESP: 10/30Pa
controller PC-ARFG1. You can be in comfort and avoid cold draft from the moment when cooling operation starts, while the room gently
cools down.
CASSETTE
4-WAY CASSETTE TYPE (DC MOTOR TYPE) 4-WAY CASSETTE TYPE 4-WAY CASSETTE TYPE
RCI-FSRP (DC MOTOR TYPE) + TWIN-SENSE 4-way Panel
RCI-FSKDN1Q RCI-FSRP+ P-AP160NAE2
RCI-FSKDN1Q+ P-AP160NAE2
Color variation (RCI-FSRP) + OPT-EZJ01 GentleCool: OFF GentleCool: LOW GentleCool: MED GentleCool: HIGH
∙ N
eutral White, Black, Gray and Beige options ∙ Economic yet efficient ∙ Adaptive comfort for real
∙R
easonable offering to meet your comfort and operation solution for your life by multiple advanced
CROWDSENSE
SOLUTIONS TO BE MEMORIZED
commercial indoor space comfort settings
Silent-IconicTM 4-WAY CASSETTE COMPACT TYPE 2-WAY CASSETTE TYPE 1-WAY CASSETTE TYPE Adjusting capacity by predicting room temperature changes due to
P-GP160NAP, P-GP160NAPU (DC MOTOR TYPE) (DC MOTOR TYPE) (DC MOTOR TYPE) an increase or decrease in human activity
+ RCI-FSRP RCIM-FSRE RCD-FSR RCS-FSR
The motion and radiant temperature sensors detect changes in the number of people in RCI-FSRP RCI-FSKDN1Q
+ + PC-ARFG1
the area and changes in the heat source and predict changes in room temperature. This P-AP160NAE2 P-AP160NAE2
+
CROWDSENSE feature activated by “Predictive crowd adjustment mode" adjusts the air OPT-EZJ01
Number of tim e
people Predict room temperature
room Target set temperature changes. Reduce power in
increase
Predictive temperature advance as the number of
control po w e r people increases to prevent 16
the room temperature from
∙ C
an be installed in floor rising too high
tim e
cavities and walls 17
–
SOLUTIONS TO BE MEMORIZED
TEMPERATURE MANAGEMENT FOR SUPERIOR COMFORT
FEETWARM
RCI-FSRP RCI-FSKDN1Q
+ + PC-ARFG1
P-AP160NAE2 P-AP160NAE2
INTELLIGENT COMFORT WITH OPTIONAL SENSOR +
OPT-EZJ01
Airflow heat control raises the temperature in the foot area
Activated by [FeetWarm heat air control] in 25
comfort setting, in the heating operation, Start-up motion
SOLUTIONS TO BE MEMORIZED
motion" to "Temperature unevenness suppression
temperature of your foot area in the room can be quickly warmed up. motion", which is to circulates the air flow more
*1 Under this "FEETWARM" feature, the gap of closed louver is a bit wider than the gap in operation-off. effectively in order to suppress the temperature
*2 In the case of underflow, the air may hit your body directly, possibly causing you to feel cold a bit.
swing swing
unevenness in the foot area. swing
Zoom IN Zoom IN
4-way cassette operates in Auto-Swing mode by
letting 3 louvers open, while closing only one s
remaining louver.
To do so, 4-way cassette can suction the lower swing swing
swing
cold temperature more efficiently, and, help warm
air circulate inside the room.
Alternately repeat
every 3 minutes
Image:
Effect of temperature unevenness suppression motion (temperature distribution around the foot area)
Image:
20 minutes after
Effect of start-up motion (temperature distribution near the foot area 30 minutes after starting the heating function) [Image based on calculation results]
Start-up Motion temperature unevenness suppression motion
Conventional control New control [FEETWARM" feature (Start-up motion)] [Measurement condition Based on
Hitachi research]
See simulation result under the
following conditions above.
Unit capacity: 80 type, room size:
"height 3.2m, length 6.3m, width
6.3m", indoor initial temperature:
7 °C, outdoor temperature: 7 °C,
indoor airflow temperature: 30 °C
About 2°C rise for 0-5 minutes, Gradually rise from
Foot area 30 °C to 40 °C after 5 minutes, Multi-
is warmed function remote control setting:
up more Airflow heat control "effective / long".
18
quickly! (Note) The effect varies depending on
the size of the room and the load.
Average temperature 30 cm above the floor = 15.4 ° C Average temperature 30 cm above the floor = 17.9 °C 4-Way Cassette Type Feetwarm evenly! 19
– –
SOLUTIONS TO BE MEMORIZED SOLUTIONS TO BE MEMORIZED
TEMPERATURE MANAGEMENT FOR SUPERIOR COMFORT FOR YOUR SMARTER OPERATION
Conditioning the air by horizontal airflow only so that Conditioning the air by Auto-Swing airflow so that
people won't get hit by the direct air blow people can feel the direct cold air
Floor
Horizontal airflow Auto swing 0.8m
Image: during cooling Image: during cooling
swing
SOLUTIONS TO BE MEMORIZED
and activates auto-save.
Detect people Detect people
FLOORSENSE COOL
RCI-FSRP RCI-FSKDN1Q
Detects the temperature near the floor to reduce overcooling + + PC-ARFG1
P-AP160NAE2 P-AP160NAE2
+
OPT-EZJ01
When the room has undergone prolonged cooling, the radiant temperature near the floor
is detected and the air flow is automatically reduced, thus reducing the air conditioning
capacity and preventing overcooling. *1 SETBACK MODE FOR HOTEL APPLICATION
*1 When a group of people return to the room or the room temperature rises due to sunlight, the cooling operation returns to normal. Off set the temperature when the space is not occupied RCI-FSRP RCIM-FSRE RCD-FSR RCS-FSR RPC-FSR
*2 Air flow contact varies depending on the capacity of the indoor unit and the height of the ceiling. reducing the power consumption (all panels) PC-ARFG1
RCI-FSKDN1Q
If the air conditioning unit
is used for a long time, the Detects the temperature
near the floor
Adjusted to reduce overcooling
after detection
Room card A Room card B Room card C Room card D
room gets cold OUT IN OUT IN
move
A Returning to set
30.0°C
temperature when
C room key inserted
27.0°C
STEP1 STEP2 B D
23.0°C
The radiant temperature sensor detects The airflow direction is changed
the temperature near the floor surface that to horizontal flow to reduce direct
20
is lower than the set temperature. air contact.*2 In addition, the air Room card Room card Room card
conditioning capacity is also preserved. in out out 21
02
–
INDOOR AIR QUALITY
Optional accessory filter
Live and work in harmony
ViroSense Z2 filter
Model: F-160L-ZV
ViroSense Z2 filter can help reduce the risk of secondar sollution and
Hitachi IAQ accessory Line-up infection in a room. We have confirmed the proven effect that can
ViroSense Z2 filter inhabits certain viruses attached to the air conditioner's filter already
01 ViroSense S filter 02 ViroSense Z2 filter 03 AQtiv-Ion Kit before.and in 2022, we have confirmed that it can inihibit the SARS-
Optional upgrade Optional upgrade CoV-2 as well under the laboratory test.
Type of purchase Now fitted as standard
Model: F-160L-ZV Model: JK-LAZQ
4
additional noise reduction solutions
∙ Lasts up to 6 years (15000h)
∙ Lasts up to 4 years (10000h)
∙ Generates negative ions and emits through
∙ Lasts up to 5 years (12500h) ∙ Quick & easy to install/change from existing
AC airflow, which binds to pollutants and
filters
∙ Anti-virus (>99% inhibition) odors, sending them harmlessly to the floor
Key Features ∙ Anti-virus (>99.7% inhibition): better than
∙ Anti-bacteria (>99% inhibition) ∙ Plug & play; converts your ducted IDU into
Ion filter
an air-purifying IDU SARS-CoV-2 Virus Inhibition Bacteria removal Life span of Quick anti-virus
∙ Anti-mold (100% growth stop) ∙ Anti SARS-CoV-2 (>99.9% inhibition)
∙ Up to 96.85% capturing of Influenza virus Inhibition by by over 99.7% by over 99% up to 4 years transformation
01
∙ Anti-bacteria (>99% inhibition)
∙ Up to 74.90% removal of Formaldehyde over 99.9% The efficiency of Efficiency of With regular Your existing 4-way
The efficiency of the ViroSense Z2 ViroSense Z2 filter maintenance and cassette panel can be
the ViroSense filter against certain against Certain types cleaning of the filter, quickly aadapted for the
Z2 filter against viruses has been of Bacterial has been the filter can have a anti-virus version, once
Standard-equipped filter SARS-CoV-2 been confirmed with confirmed too with life span of you change your existing
ViroSense S filter confirmed with inhibition rate up
to more than 99.7%.
inhibition rate up to
more than 99%.
up to 4 years. filter to the ViroSense Z2
filter. The same, usual
inhibition rate up to
We have renewed our standard air filter for some of our Hitachi VRF indoor units with an leading-edge ion-technology, more than 99.9%. attachment!
and, now it has THREE benefits for you & more assures indoor environment.
Our STANDARD Air Filter with Ion Purification feature, ViroSense S filter, will catch & reduce them, then help create the cleaner indoor
22
(Standard P-AP160NAE2
P-AP160NAE2 P-AP160NA3 P-AP160KA3 P-GP160NAP P-GP160NAPU P-GP160KAP 23
P-AP90DNA/P-AP160DNA P-AP36CNA/P-AP56CNA/P-AP80CNA RPC-1.5FSR~6.0FSR Equipped) + OPT-EZJ01
Note: for the additional filter purchase, it is treated as "service part". Please consult your distributors.
03
–
INDOOR AIR QUALITY AQTIV-ION KIT DEACTIVATION PERFORMANCE
Live and work in harmony SARS-CoV-2 Escherichia coli Influenza virus Staphylococcus aureus PM2.5 Formaldehyde Ammonia
Various pathogenic factors Breeding of bacteria, mold Formaldehyde, ammonia, Second-hand smoking and ust and mites from fabrics,
D for AQtiv-Ion Kit to be fixed to. suspended-ceiling
including bacteria and certain and damage to household benzene and a variety of volatile kitchen oil fume. such as beddings and pet
viruses caused by insufficient items, allergies caused by high organic compounds released by dander might cause allergies.
ventilation. humidity in wet season. decoration materials.
Pollen and
other allergens
Pollutants safely decompose
Inhibit and eliminate
Bacteria & Certain Viruses
COMPATIBLE INDOOR UNITS WITH AQTIV-ION KIT
HIGH ESP (AC) MEIDIUM ESP (AC) LOW ESP (AC) COMPACT (AC) COMPACT (DC)
AQtiv-Ion Kit The free Negative Formaldehyde Smog
RPIH-**HNAUN1Q RPIM-**HNAUN1Q RPIL-**HNAUN1Q RPIZ-**HNATN1Q RPIZ-**HNDTS1Q
releases high- electrons oxygen ions are
Mold Virus
speed electrons collide with O2 created, ready
into the room. molecules. to capture and
Benzene, ketone Ammonia and
inhibits the air and other other odors 24
impurities. Bacteria volatile organic
compounds
(*) For RPI-8.0/10.0FSNQH, please fix the AQtiv-Ion Kit to the indoor unit air-outlet. 25
–
DUCTED
Model
HIGH ESP TYPE (AC MOTOR TYPE) MEDIUM ESP TYPE (AC MOTOR TYPE) LOW ESP TYPE (AC MOTOR TYPE) RPIM-HNAUN1Q
RPIH-HNAUN1Q RPIZ-HNDTS1Q RPIZ-HNATN1Q
RPIL-HNAUN1Q
[RPIH-HNAUN1Q] [RPIM-HNAUN1Q] [RPIL-HNAUN1Q]
∙ High ESP (90/120/180Pa) ∙ Medium ESP (50/80Pa for 0.8-2.5HP class) ∙ Low ESP (30Pa for 0.8-2.5HP class, 60Pa for 3.0-6.0HP class) Temperature Setting Rate 1.0°C 1.0°C 1.0°C 1.0°C
∙ Space saving design thanks to a height of only 300mm ∙ Space saving design thanks to a height of only 270mm ∙ Space saving design thanks to a height of only 270mm (0.8-
∙ Compatible with AQtiv-Ion Kit (Optional accessory) ∙ Compatible with AQtiv-Ion Kit (Optional accessory) 2.5HP class) or 350mm (3.0-6.0HP class) Indoor Fan Speed 3 taps 3 taps 6 taps 3 taps
IDU Category Cooling (kW) 2.2 2.8 3.6 4.0 4.3 5.0 5.6 6.3 7.1 8.0 8.4 9.0 11.2 14.0 14.2 16.0
DUCTED
Automatic Fan Operation
Motion Sensor - - - -
PC-RLH11 PC-RLH11 PC-RLH11 PC-RLH11
Receiver Kit for wireless remote controller
PC-ALHZ1 PC-ALHZ1 PC-ALHZ1 PC-ALHZ1
DUPI-131Q
Drain-up mechanism availability DUPI-361Q (*3) (*3)
DUPI-361Q
OPTIONAL KW-PP5Q KW-PP5Q
ACCESSORY KW-PP7/
Air filter KW-PP9/10Q KW-PP6Q KW-PP6Q
8/9/10Q
KW-PP12Q KW-PP12Q
AQtiv-Ion Kit
(*1) This function is utilized to prevent cold discharged air at start-up of heating operation,
after defrosting operation, etc.
AQtiv-Ion Kit
Leads to the better Indoor Air Quality
(*2) Advanced wired remote controller PC-ARF1 needs to be connected.
(*3) Included as standard equipment. Features
∙Up to 96.85% capture of viruses and bacteria
(*4) Please consult your distributor.
∙Down to PM0.3 micro particle removal
∙Pollutant removal
∙Active oxygen generation
26
∙Inactivation of SARS-CoV-2 by more than 99.9%
27
–
DUCTED
HIGH ESP TYPE (HIGH EXTERNAL STATIC PRESSURE TYPE) LOW ESP TYPE (LOW EXTERNAL STATIC PRESSURE TYPE)
(AC MOTOR TYPE) [RPIH-HNAUN1Q] (AC MOTOR TYPE) [RPIL-HNAUN1Q]
Maximum
900mm
Maximum
900mm
COMPACT TYPE
(DC MOTOR TYPE) [RPIZ-HNDTS1Q]
DUCTED
FEATURES AND BENEFITS
1) Ideal for installation over the closet or windows thanks to the up to the compactness with 192mm height
2) Drain-pump with 900mm lift as standard optional part
3) Quiet operation level (as low as 22.5dB(A))
MEDIUM ESP TYPE (MEDIUM EXTERNAL STATIC PRESSURE TYPE) 4) Fan air flow rate up to 6 taps (DC motor model only)
Maximum
900mm
28
29
– –
DUCTED Success
that sparks
COMPACT TYPE
(AC MOTOR TYPE) [RPIZ-HNDTN1Q]
Information
Labs Tower Cyprus
FEATURES AND BENEFITS FFOTI PITTA 4, CYPRUS, 1065
https://labstower.cy/
1)Ideal for installation over the closet or windows thanks to the up to the compactness with 192mm height
2) Drain-pump with 900mm lift as standard optional part General Information
Year of installation : 2022
3) Quiet operation level (as low as 20dB(A))
Project type : Retrofit
4) Fan air flow rate up to 6 taps (DC motor model only) Vertical application: Commercial multi-tenant building
DUCTED
30
31
–
CASSETTE
CASSETTE
Dirty Filter Notice Availability
Sensor Condition Check
Model Display (*2) - -
Check Menu
MAINTENANCE
Indoor/Outdoor PCB Check
Alarm History Display
Colored Decoration Panel availability (*6) - - (*6) (*6)
General Information
Year of installation : 2022
Project type : Retrofit
Tomohiko Sato
Hitachi, Ltd. Product Design Department, Senior Designer
The designer graduated from University
in the United Kingdom and soon after,
he joined a London based design studio,
working across a wide variety of disciplines The air-outlet port
including furniture, interior and the public with occupied
CASSETTE
realm. Currently, he dedicates himself to air
presence suppression
conditioning design, working as a Senior
Designer in the Hitachi product design Blind shaped
department in Hitachi, Ltd.
air-inlet port
34
35
–
CASSETTE
Silent-IconicTM
570 mm
White Black
P-GP160NAP P-GP160KAP
Standard
(H×W×D) 40×950×950(mm) 570 mm
(H×W×D) 40×950×950(mm) (H×W×D) 40×950×950(mm) (H×W×D) 52×950×950(mm)
Silent-IconicTM
(H×W×D) 52×950×950(mm)
RCI-FSRP
RCI-FSRP RCI-FSRP RCI-FSRP
RCI-FSKDN1Q
Twin-Sense Cassette
37
Adaptive comfort for real life
The compact 600×600mm footprint fits a standard ceiling grid, allowing it to be easily
incorporated between lighting panels, being ideal for the small place installation!
CASSETTE
GENTLECOOL FEETWARM
>16.0°C
2) Top-class silent operation IDU Capacity HP(Class) 0.8 1 1.5 2 2.5
(standard feature) To make your room (with radiant temperature sensor)
As quiet as gentle breeze
reach to the desired temperature optimization of IDU air flow direction
Sound pressure level (dB(A)) 24.5 24.5 27.5 31 35
faster, the discharged air from the during heating mode by to make
*Air flow rate: Lo
indoor unit can be sometimes much sure that leg zone is consistently 20dB(A) 30dB(A) 40dB(A)
cooler, causing discomfort at the heated CLOCK MIDNIGHT LIBRARY
beginning of operation.
37
–
CASSETTE
Horizontal Blow
25°
60°
louver opens up to
CASSETTE
2) The height of the space for 3) Suitable for high ceiling space 2) Quiet operation 3) Suitable for high ceiling space
installing the unit can be Standard drain-pump with 850mm lift
Standard drain-pump with 850mm lift New design in fan inlet and fan resulted in the low
fine-tuned
* Air flow rate: Hi2 sound pressure
* 2.0-6.0 FSR
IDU cooling capacity (kW) 2.2 2.8 4.0 5.6 7.1 8.0
panel
(Cooling)
Up to
(Cooling)
Up to
5.3m
down
4.6m
down
corner pocket
38
39
–
CONCEALED & EXPOSED
FEATURES COMPARISON
KEY INFORMATION
WALL MOUNTED FLOOR/CEILING CEILING FLOOR
TYPE CONVERTIBLE SUSPENDED CONCEALED
TYPE TYPE TYPE
Model
IDU Category Cooling (kW) 2.2 2.8 3.6 4.0 4.3 5.0 5.6 6.3 7.1 8.0 8.4 9.0 11.2 14.0 14.2 16.0 Daylight Saving Time
(*1) This function is utilized to prevent cold discharged air at start-up of heating operation, after defrosting operation, etc.
(*2) Advanced wired remote controller PC-ARF1 needs to be connected.
(*3) 5 steps only in the operation of Cooling or Dry.
(*4) Please consult your distributor for the availability.
(*5) Basic Receiver kit (PC-RLH11) is equipped with the unit in package as standard optional part with Wireless Remote Controller (PC-LH7QE).
40
41
–
CONCEALED & EXPOSED
4) Easy maintenance.
Front flat panel keeps the unit from dust and facilitates maintenance work.
The front grille hinges open easily—no tools are needed to gain quick access to the filter.
The filter can be removed and cleaned as required.
43
–
CONCEALED & EXPOSED
1) Adapts to both floor and ceiling 1) Wide Detection area of motion sensor (SOR-NEP)
⟦CEILING USE⟧ ⟦FLOOR USE⟧ (Optional part) to achieve better energy-saving
Supplies air to a wide area. High ceiling use capability. Smaller footprint: Only 230mm in depth. Suitable for installation
beneath a window thanks to the 680mm height.
Ceiling
Height
2.7m
1.8m 7m
Ceiling Type
3) New design in fan inlet and fan resulted 4) Suitable for high ceiling space
in the low sound pressure
Cooling capacity (kW) 4.0 8.0 11.2 14.0 IDU Capacity HP(Class) 1.5-3.0 4.0-6.0
(Option)
drain
600
mm
(Cooling)
Up to
5.6m
down
44
* Air flow rate: Hi2
* 4.0-6.0 FSR 45
– –
CONCEALED & EXPOSED GENERAL DATA & ACCESSORIES
FLOOR CONCEALED TYPE HIGH ESP TYPE (HIGH EXTERNAL STATIC PRESSURE TYPE)
(AC MOTOR TYPE) [RPIH-HNAUN1Q]
(AC MOTOR TYPE) [RPFI-FSNQ]
Model RPIH-3.0HNAUN1Q RPIH-3.3HNAUN1Q RPIH-4.0HNAUN1Q RPIH-5.0HNAUN1Q RPIH-6.0HNAUN1Q
Basic PC-RLH11
Receiver Kit
Advanced PC-ALHZ1
620mm
Condensate Drain Pump Kit DUPI-361Q
3.0-4.0 (HP class) KW-PP9Q
Air filter
5.0-6.0 (HP class) KW-PP10Q
AQtiv-Ion Kit JK-LZAQ
900-1,170mm
Air Inlet NOTES:
1. The cooling capacities above show the maximum capacities when the outdoor 2. The sound pressure level is based on following conditions. 1.4 metre Beneath the unit.
and indoor temperature are under the following conditions. With Discharge Duct (2.0 metre) and Return Duct (1.0 metre).
Voltage of the power source for the indoor fan motor is 220V.
Cooling Operation Conditions Heating Operation Conditions (In case of the power source of 240V, the sound pressure level increases by about 1~2dB(A).)
Indoor Air Inlet Temperature: 27.0ᵒC DB Indoor Air Inlet Temperature: 20.0ᵒC DB
202mm The above data was measured in an anechoic chamber so that reflected sound should be taken
Basic PC-RLH11
Receiver Kit
Advanced PC-ALHZ1
Condensate
0.8-2.5 (HP class) DUPI-131Q
Drain Pump Kit
0.8-1.5 (HP class) KW-PP7Q
Air filter
1.8-2.5 (HP class) KW-PP8Q
AQtiv-Ion Kit JK-LZAQ
NOTES:
1. The cooling capacities above show the maximum capacities when the outdoor 2. The sound pressure level is based on following conditions. 1.4 metre Beneath the unit.
and indoor temperature are under the following conditions. With Discharge Duct (2.0 metre) and Return Duct (1.0 metre).
Voltage of the power source for the indoor fan motor is 220V.
Cooling Operation Conditions Heating Operation Conditions (In case of the power source of 240V, the sound pressure level increases by about 1~2dB(A).)
Indoor Air Inlet Temperature: 27.0ᵒC DB Indoor Air Inlet Temperature: 20.0ᵒC DB The above data was measured in an anechoic chamber so that reflected sound should be taken
19.0ᵒC WB Outdoor Air Inlet Temperature: 7.0ᵒC DB into consideration in the field.
Outdoor Air Inlet Temperature: 35.0ᵒC DB 6.0ᵒC WB
Piping Length:7.5 metre Piping Length:7.5 metre 3. The data for external pressure (*3) indicates "Standard Pressure Setting values when a filter is 46
Piping Lift:0 metre Piping Lift:0 metre not used.
47
–
GENERAL DATA & ACCESSORIES
LOW ESP TYPE (LOW EXTERNAL STATIC PRESSURE TYPE) COMPACT TYPE
(AC MOTOR TYPE) [RPIL-HNAUN1Q] (DC MOTOR TYPE) [RPIZ-HNDTS1Q]
Model RPIL-0.8HNAUN1Q RPIL-1.0HNAUN1Q RPIL-1.3HNAUN1Q RPIL-1.5HNAUN1Q RPIL-1.8HNAUN1Q RPIL-2.0HNAUN1Q RPIL-2.3HNAUN1Q Model RPIZ- RPIZ-
0.8HNDTS1Q 1.0HNDTS1Q
RPIZ-
1.3HNDTS1Q
RPIZ-
1.5HNDTS1Q
RPIZ-
1.8HNDTS1Q
RPIZ-
2.0HNDTS1Q
RPIZ-
2.3HNDTS1Q
RPIZ-
2.5HNDTS1Q
Indoor Unit Power Supply AC 1Φ, [220-240V/50Hz] Indoor Unit Power Supply AC 1Φ, [220-240V/50Hz] [220V/60Hz]
Cooling kW 2.2 2.8 3.6 4.3 5.0 5.6 6.3 Cooling kW 2.2 2.8 3.6 4.0 5.0 5.6 6.3 7.1
Nominal Capacity Nominal Capacity
Heating kW 2.8 3.3 4.2 4.9 5.6 6.5 7.5 Heating kW 2.5 3.2 4.0 4.5 5.6 6.3 7.1 8.0
Sound Pressure Sound Pressure 33/31/28/ 33/31/28/ 33/31/28/ 31/30/28/ 36/33.5/31/ 36/33.5/31/ 37/36/33/ 37/36/33/
(Hi/Me/Lo) dB(A) 28/25/22 28/25/22 34/32/30 34/32/30 34/32/29 34/32/29 36.5/30.5/25 (6 taps) dB(A)
Level Level 25/23.5/22.5 25/23.5/22.5 25/23.5/22.5 25/22/20 28/24.5/22.5 28/24.5/22.5 30/28/25 30/28/25
Outer Dimension (H×W×D) mm 270×725×720 270×725×720 270×725×720 270×725×720 270×975×720 270×975×720 270×975×720 Outer Dimension H×W×D mm 192×700×447 192×700×447 192×700×447 192×910×447 192×1,180×447 192×1,180×447 192×1,180×447 192×1,180×447
Net Weight kg 24 24 25 25 31 31 32 Net Weight kg 17 17 17 20 24 24 24 24
Refrigerant R410A R410A R410A R410A R410A R410A R410A Refrigerant R410A R410A R410A R410A R410A R410A R410A R410A
Indoor Fan Indoor Fan 8.5/8/7/ 8.5/8/7/ 8.5/8/7/ 10/9/8/ 14.5/13.2/11.8/ 14.5/13.2/11.8/ 16.5/15/13/ 16.5/15/13/
(Hi/Me/Lo) m3/min 9/8/7 9/8/7 13/11/9 13/11/9 15/14/12 15/14/12 21/14/11 (6 taps) m3/min
Basic PC-RLH11
Receiver Kit
Advanced PC-ALHZ1
Condensate Drain Pump Kit - (included as standard equipment)
0.8-1.3 (HP Class) KW-PP12Q
Air filter 1.5 (HP Class) KW-PP5Q
1.8-2.5 (HP Class) KW-PP6Q
AQtiv-Ion Kit JK-LZAQ
NOTES:
1. The cooling capacities above show the maximum capacities when the outdoor 2. The sound pressure level is based on following conditions. 1.4 metre Beneath the unit.
and indoor temperature are under the following conditions. With Discharge Duct (2.0 metre) and Return Duct (1.0 metre).
Voltage of the power source for the indoor fan motor is 220V.
Cooling Operation Conditions Heating Operation Conditions (In case of the power source of 240V, the sound pressure level increases by about 1~2dB(A).)
Indoor Air Inlet Temperature: 27.0ᵒC DB Indoor Air Inlet Temperature: 20.0ᵒC DB The above data was measured in an anechoic chamber so that reflected sound should be taken 48
19.0ᵒC WB Outdoor Air Inlet Temperature: 7.0ᵒC DB into consideration in the field.
Outdoor Air Inlet Temperature: 35.0ᵒC DB 6.0ᵒC WB
Piping Length:7.5 metre Piping Length:7.5 metre 3. The data for external pressure (*3) indicates "Standard Pressure Setting values when a filter is 49
Piping Lift:0 metre Piping Lift:0 metre not used.
4. When the model of RAS-7.0~12HNBRMQ outdoor unit is connected to the compact ducted type
indoor units (RPIZ), if only one indoor unit is in cooling operation,and the capacity is less than
2.8kW, the minimum outdoor temperature is 5.0°C DB.
–
GENERAL DATA & ACCESSORIES
NOTES:
1. The
cooling and heating capacities above show the maximum capacities when the outdoor and indoor temperature are under the following conditions.
Cooling Operation Conditions Heating Operation Conditions
Indoor Air Inlet Temperature: 27.0ᵒC DB Indoor Air Inlet Temperature: 20.0ᵒC DB
19.0ᵒC WB Outdoor Air Inlet Temperature: 7.0ᵒC DB
Outdoor Air Inlet Temperature: 35.0ᵒC DB 6.0ᵒC WB
Piping Length:7.5 metre Piping Length:7.5 metre
Piping Lift:0 metre Piping Lift:0 metre
Indoor Unit Power Supply AC 1Φ, [220-240V/50Hz] [220V/60Hz] Indoor Unit Power Supply AC 1Φ, [230V/50Hz] [220-240V/50Hz] [220V/60Hz]
Nominal Cooling kW 2.8 4.0 5.6 6.3 7.1 8.0 11.2 14.0 16.0 Nominal Cooling kW 2.2 2.8 4.0 5.6 7.1
Capacity Heating kW 3.2 4.8 6.3 7.1 8.5 9.0 12.5 16.0 18.0 Capacity Heating kW 2.5 3.2 4.8 6.3 8.5
Sound Pressure Sound Pressure
(Hi2/Hi/Me/Lo) dB(A) 33/30/28/27 35/31/30/27 37/32/30/27 42/36/32/28 42/36/32/28 42/36/32/28 48/43/39/33 48/45/40/35 48/46/41/37 (Hi2/Hi/Me/Lo) dB(A) 36/33/29/24.5 38/34/30/24.5 41/37/33/27.5 45/39/35/31 47/43/39/35
Level Level
Outer Dimension (H×W×D) mm 238×840×840 238×840×840 238×840×840 238x840x840 238×840×840 288×840×840 288×840×840 288×840×840 288×840×840 Outer Dimension (H×W×D) mm 285×570×570 285×570×570 285×570×570 285×570×570 285×570×570
Net Weight kg 20 21 21 22 22 26 26 26 26 Net Weight kg 16 16 16 17 17
Refrigerant R410A R410A R410A R410A R410A R410A R410A R410A R410A Refrigerant R410A R410A R410A R410A R410A
Indoor Fan Indoor Fan
(Hi2/Hi/Me/Lo) m3/min 15/13/11/9 21/17/14/11 22/17/14/11 27/23/18/14 27/23/18/14 27/23/18/14 37/31/24/20 37/33/26/21 37/35/28/22 (Hi2/Hi/Me/Lo) m3/min 11/9.5/8/6 12/10/8.5/6 13/11/9.5/7 15/12/10/8 16/14/12/10
Air Flow Rate Air Flow Rate
Connections Flare-Nut Connection (with flare Nuts) Connections Flare-Nut Connection (with Flare Nuts)
Refrigerant Liquid Line mm Φ6.35 Φ6.35 Φ6.35 φ9.52 Φ9.52 Φ9.52 Φ9.52 Φ9.52 Φ9.52 Refrigerant Liquid Line mm Φ6.35 Φ6.35 Φ6.35 Φ6.35 Φ9.52
Piping Diameter Gas Line mm Φ12.7 Φ12.7 Φ12.7 φ15.88 Φ15.88 Φ15.88 Φ15.88 Φ15.88 Φ15.88 Piping Diameter Gas Line mm Φ12.7 Φ12.7 Φ12.7 Φ12.7 Φ15.88
Condensate Drain VP25 VP25 VP25 VP25 VP25 VP25 VP25 VP25 VP25 Condensate Drain VP25 VP25 VP25 VP25 VP25
Approximate Packing Volume m3 0.21 0.21 0.21 0.21 0.21 0.25 0.25 0.25 0.25 Approximate Packing Volume m3 0.13 0.13 0.13 0.13 0.13
- (Standard) Condensate Drain Pump Kit - (Standard) Decoration panel P-AP56NAM Motion Sensor SOR-NEC
Decoration Panel
Twin-Sense panel P-AP160NAE2 + OPT-EZJ01 Duct Adapter PD-75A Decoration panel Condensate Drain Pump Kit - (Standard)
Advanced P-AP56NAMR
Basic HR4A10NEWQ ViroSense Z2 filter F-160L-ZV with Receiver kit Duct Adapter PD-75C
Receiver Kit Receiver kit Advanced PC-ALHC1
Advanced PC-ALH3 ViroSense S filter - (Standard)
NOTE: NOTES:
1. T
he cooling and heating capacities above show the maximum capacities when the outdoor and indoor temperature are under the following conditions. 1. The cooling and heating capacities above show the maximum capacities when the outdoor and indoor temperature are under the following conditions.
Cooling Operation Conditions Heating Operation Conditions Cooling Operation Conditions Heating Operation Conditions
Indoor Air Inlet Temperature: 27.0ᵒC DB (80.0ᵒF DB) Indoor Air Inlet Temperature: 20.0ᵒC DB (68.0ᵒF DB) Indoor Air Inlet Temperature: 27.0ᵒC DB Indoor Air Inlet Temperature: 20.0ᵒC DB
19.0ᵒC WB (66.2ᵒF WB) Outdoor Air Inlet Temperature: 7.0ᵒC DB (45.0ᵒF DB) 19.0ᵒC WB Outdoor Air Inlet Temperature: 7.0ᵒC DB
Outdoor Air Inlet Temperature: 35.0ᵒC DB (95.0ᵒF DB) 6.0ᵒC WB (43.0ᵒF WB) Outdoor Air Inlet Temperature: 35.0ᵒC DB 6.0ᵒC WB
Piping Length: 7.5 metre Piping Length: 7.5 metre Piping Length:7.5 metre Piping Length:7.5 metre 50
Piping Lift: 0 metre Piping Lift: 0 metre Piping Lift:0 metre Piping Lift:0 metre
2. The sound pressure level is based on following conditions. 1.5 metre Beneath the unit. 51
2. The
sound pressure level is based on following conditions. 1.5 metre Beneath the unit.
T
he data in the table above was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field. The data in the table above was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
–
GENERAL DATA & ACCESSORIES
Indoor Unit Power Supply AC 1Φ, [220-240V/50Hz] [220V/60Hz] Model RPK-2.5FSRM RPK-3.0FSRM RPK-4.0FSRM
Nominal Cooling kW 2.2 2.8 4.0 5.6 7.1 8.0 11.2 14.0 16.0 Indoor Unit Power Supply AC 1Φ, [220-240V/50Hz] [220V/60Hz]
Capacity Heating kW 2.5 3.2 4.8 6.3 8.5 9.0 12.5 16.0 18.0 Cooling kW 7.1 8.0 11.2
Nominal Capacity
Sound Pressure Heating kW 8.5 9.0 12.5
(Hi2/Hi/Me/Lo) dB(A) 30/29/28/27 31/29/28/27 37/34/31/30 39/36/33/30 42/39/36/33 45/42/38/33 43/40/37/34 47/44/41/35 48/45/42/39
Level Sound Pressure
(Hi2/Hi/Me/Lo) dB(A) 45/42/38/35 47/44/40/35 51/48/44/39
Outer Dimension (H×W×D) mm 298×860×630 298×860×630 298×860×630 298×860×630 298×860×630 298×860×630 298×1,420×630 298×1,420×630 298×1,420×630 Level
Net Weight kg 23 23 25 25 25 25 39 39 39 Color White
Refrigerant R410A R410A R410A R410A R410A R410A R410A R410A R410A Outer Dimension (H×W×D) mm 300×1,100×260 300×1,100×260 300×1,100×260
Indoor Fan 16.5/14.5/ 18.5/16.5/ 21/18.5/ 37/32.5/ Net Weight kg 15 15 15
(Hi2/Hi/Me/Lo) m3/min 10/9/7.5/6.5 11/9.5/8.5/7 15/13/11.5/10 30/26.5/23/20 35/31/27/21
NOTES: NOTES:
1. The cooling and heating capacities above show the maximum capacities when the outdoor and indoor
STRAINER KIT
1. T
he cooling and heating capacities above show the maximum capacities when the outdoor and indoor temperature are under the following conditions. Strainer Kit Refrigerant Pipe
Cooling Operation Conditions Heating Operation Conditions temperature are under the following conditions.
Indoor Air Inlet Temperature: 27.0ᵒC DB Indoor Air Inlet Temperature: 20.0ᵒC DB Cooling Operation Conditions Heating Operation Conditions
19.0ᵒC WB Outdoor Air Inlet Temperature: 7.0ᵒC DB Indoor Air Inlet Temperature: 27.0ᵒC DB Indoor Air Inlet Temperature: 20.0ᵒC DB
Outdoor Air Inlet Temperature: 35.0ᵒC DB 6.0ᵒC WB 19.0ᵒC WB Outdoor Air Inlet Temperature: 7.0ᵒC DB
Piping Length:7.5 metre Piping Length:7.5 metre Outdoor Air Inlet Temperature: 35.0ᵒC DB 6.0ᵒC WB
solid foreign filter
Piping Lift:0 metre Piping Lift:0 metre Piping Length: 7.5 metre Piping Length: 7.5 metre
substances
Piping Lift: 0 metre Piping Lift: 0 metre
2. The
sound pressure level is based on following conditions. 1.5 metre Beneath the unit.
2. The sound pressure level is based on following conditions. A strainer kit ensures that solid foreign substances, like small particles
Model RPFC-1.8FSNQ RPFC-2.0FSNQ RPFC-2.3FSNQ RPFC-2.5FSNQ RPFC-3.0FSNQ RPFC-3.3FSNQ RPFC-4.0FSNQ RPFC-5.0FSNQ Model RPFI-1.0FSNQ RPFI-1.5FSNQ RPFI-2.0FSNQ RPFI-2.5FSNQ
Indoor Unit Power Supply AC 1Φ, [220-240V/50Hz] [220V/60Hz] Indoor Unit Power Supply AC 1Φ, [220-240V/50Hz]
Nominal Cooling kW 5.0 5.6 6.3 7.1 8.4 9.0 11.2 14.2 Nominal Cooling kW 2.8 4.3 5.6 7.1
Capacity Heating kW 5.6 6.5 7.5 8.5 9.6 10.0 13.0 16.3 Capacity Heating kW 3.3 4.9 6.5 8.5
Sound Pressure Ceiling Mode dB(A) 39/35/30 39/35/30 45/41/37 45/41/37 43/39/34 45/40/36 51/46/40 50/46/42 Sound Pressure
(Hi/Me/Lo) dB(A) 37/34/31 40/38/35 42/38/36 45/43/40
Level Floor Mode dB(A) 43/38/35 43/38/35 48/44/40 48/44/40 46/41/37 48/43/39 54/49/43 55/50/46 Level
Outer Dimension (H×W×D) mm 230×990×680 230×990×680 230×990×680 230×990×680 230×1,285×680 230×1,285×680 230×1,285×680 230×1,580×680 Outer Dimension (H×W×D) mm 620×900×202 620×900×202 620×1,170×202 620×1,170×202
Net Weight kg 31 31 32 32 39 40 41 47 Net Weight kg 25 26 34 34
Refrigerant R410A R410A R410A R410A R410A R410A R410A R410A Refrigerant R410A R410A R410A R410A
Indoor Fan Indoor Fan
NOTES: NOTES:
1. T
he cooling and heating capacities above show the maximum capacities when the outdoor and indoor temperature are under the following conditions. 1. The cooling and heating capacities above show the maximum capacities when the outdoor and indoor temperature are under the following conditions.
Cooling Operation Conditions Heating Operation Conditions Cooling Operation Conditions Heating Operation Conditions
Indoor Air Inlet Temperature: 27.0ᵒC DB Indoor Air Inlet Temperature: 20.0ᵒC DB Indoor Air Inlet Temperature: 27.0ᵒC DB Indoor Air Inlet Temperature: 20.0ᵒC DB
19.0ᵒC WB Outdoor Air Inlet Temperature: 7.0ᵒC DB 19.0ᵒC WB Outdoor Air Inlet Temperature: 7.0ᵒC DB
Outdoor Air Inlet Temperature: 35.0ᵒC DB 6.0ᵒC WB Outdoor Air Inlet Temperature: 35.0ᵒC DB 6.0ᵒC WB
Piping Length: 7.5 metre Piping Length: 7.5 metre Piping Length: 7.5 metre Piping Length: 7.5 metre
Piping Lift: 0 metre Piping Lift: 0 metre Piping Lift: 0 metre Piping Lift: 0 metre
2. The
sound pressure level is based on following conditions. 2. The sound pressure level is based on following conditions.
1.0 metre Beneath the unit. 1.0 metre from the unit.
1.0 metre from Discharge grille. 1.0 metre from floor level.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field. Voltage of the power source for the indoor fan motor is 220V.
When bottom air inlet is adopted, sound pressure will increase according to factors such as installation mode and the room structure. The above data was measured in an anechoic chamber.
NOTES:
1. T
he cooling and heating capacities above show the maximum capacities when the outdoor and indoor temperature are under the following conditions.
Cooling Operation Conditions Heating Operation Conditions
Indoor Air Inlet Temperature: 27.0ᵒC DB Indoor Air Inlet Temperature: 20.0ᵒC DB
19.0ᵒC WB Outdoor Air Inlet Temperature: 7.0ᵒC DB
Outdoor Air Inlet Temperature: 35.0ᵒC DB 6.0ᵒC WB
Piping Length: 7.5 metre Piping Length: 7.5 metre
Piping Lift: 0 metre Piping Lift: 0 metre
2. The
sound pressure level is based on following conditions. 54
1.0 metre Beneath the unit.
1.0 metre from Discharge grille.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field. 55
When bottom air inlet is adopted, sound pressure will increase according to factors such as installation mode and the room structure.
–
VENTILATIONS
RENEW AIR
Today, the average person spends more than 75% of their day indoors; at home, at work, in the gym, shopping or socializing. Many of these
environments are effectively sealed and fresh air isn't easily available
Without proper ventilation, CO2 levels rise, pollutants circulate and potentially harmful bacterias build-up, impacting on the wellbeing, comfort
and productivity of occupants.
Make these spaces as healthy and comfortable as possible by providing fresh air with our premium air renewal systems for commercial buildings
OUR LINE-UP
Fan Air Flow Rate (m3/h) 150 200 210 230 300 400 500 550 650 700 800 1,000 1,080 1,250 1,500 1,680 2,000 2,100 2,500 3,000 4,000 5,000 6,000
VENTILATIONS
Sound Pressure
(Hi/Me/Lo) dB(A) 32/30/25 36/34/28 39/37/30 40/38/31 40/38/35 40/38/34 43/42/34 42/40/37
Level
Outer
(H×W×D) mm 220×962×735 220×962×735 220×1,112×735 220×1,112×735 388×1,119×884 388×1,119×884 388×1,119×884 430×1,250×1,135
Dimension
Net Weight kg 38 40 46 52 61 69 69 95
Air Flow Rate (Hi/Me/Lo) m3/h 200/200/150 300/300/210 400/400/230 500/500/400 650/650/550 800/800/650 1,000/1,000/700 1,250/1,250/800
External Static
(Hi/Me/Lo) Pa 100/70/40 120/90/50 120/90/50 120/90/50 130/100/90 130/100/90 165/120/60 100/50/30
Pressure
Power Input (Hi/Me/Lo) W 120/110/75 165/155/120 210/200/130 330/310/230 2×(188/173/142) 2×(207/188/165) 2×(250/228/205) 2×(308/266/237)
Current (Hi/Me/Lo) A 0.6/0.5/0.4 0.8/0.7/0.6 1.0/1.0/0.7 1.6/1.5/1.1 1.72/1.58/1.31 2.04/1.93/1.73 2.35/2.09/1.92 3.03/2.45/2.18
320×250
Connection Duct Diameter mm Φ144 Φ144 Φ144 Φ194 Φ242 Φ242 Φ242
+320×250
Approximate Packing Volume m3 0.37 0.37 0.43 0.49 0.94 1.15 1.15 1.25
Enthalpy Summer % 57 57 55 56 55 53
Efficiency Winter % 68 68 72 72 63 61
Sound Pressure Level dB(A) 50 51 53 54 57 58
Outer
(H×W×D) mm 536×1,500×1,300 536×1,500×1,400 640×1,700×1,500 640×1,750×1,600 1,655×1,400×850 1,730×1,700×850
Dimension
Net Weight kg 144 155 180 220 225 260
Air Flow Rate m3/h 1,500 2,000 2,500 3,000 4,000 5,000
External Static Pressure Pa 165 160 180 200 220 240
Power Input W 2×440 2×810 2×925 2×1080 2×1,470 2×1,980
Current A 2.84 3.08 4.19 5.23 5.57 7.51
400×320 400×320 500×350 500×350 400×320 500×350
Connection Duct Diameter mm
+400×320 +400×320 +500×350 +500×350 +590×320 +700×320
Approximate Packing Volume m3 1.82 1.95 2.63 2.93 3.01 3.75 56
NOTE: 57
Please confirm the model name for "wires remote controller" compatible with Total Heat Exchanger to your local distributor.
– New generation:
CONTROLLERS simple and smart!
Everyone deserves comfort, but comfort does not mean the same
to everyone. That’s why control is key. Our controllers offer best-
in-class simplicity. Using our praised central stations, building
60 CENTRALIZED CONTROLLERS
60 Line up overview
62
64 Central Station EX
65 Central Station EZ
CONTROLLERS
65 Central Station mini
66 INDIVIDUAL CONTROLLERS
66 Line up overview
68
70 Advanced Color Wired Remote Controller
72 Eco–Compact Controller
74 Wired remote controller
75 Advanced wireless remote controller
75 Wireless remote controller
75 Receiver kit
76 ACCESSORIES
59
–
CENTRALIZED CONTROLLERS
Control each indoor unit, one specific zone or even
multiple systems from one place! Small to large systems & fixed or cloud-based
CENTRAL STATION EX CENTRAL STATION EZ CENTRAL STATION MINI
CENTRALIZED CONTROLLERS
Control Function Filter sign reset
Outdoor unit capacity control - - △ (*4)
Outdoor unit noise control - - -
Main 5 functions (*5)
Individual controller lock
Alarm status & code
Monitor
Filter sign
Function
Air inlet temperature of indoor unit - -
(HC-IoTGW) CENTRAL STATION EX (PSC-A128EX3) Air inlet temperature of outdoor unit - -
∙ Remote access via smartphone app or web. ∙ Control capacity: max 2,560 indoor units (+15x Frostwash status - - -
∙ Unlimited number of systems, zones and users. Extension Adapter PSC-AD128EX3). Weekly -
∙ Intuitive scheduling function. ∙ With energy calculation software (PSC-AS01EXC), Setting times per day 16 16 10 10
Schedule
∙ Troubleshooting with access to error history and alerts. determine each tenant's energy usage. Function
Special day setting 5 5 - -
∙ Filter sign display to quickly overview daily ∙ Easy monitoring with simplified interface. Holiday setting - - -
maintenance needs. ∙ Best option for middle-large size buildings. Annual/Summer/Winter schedule Future Version - -
∙ Ideal for all types of applications. ∙ Remote access! Operate Central Station EX from your Alarm history (records number) Unlimited 10,000 100 100
∙ Compact and optimized 170x250mm body screens ∙ Compact and optimized 120x140mm body screens (*1) One Extension Adapter (PSC-AD128EX3) enable CENTRAL STATION EX to control additional 160 RC groups /128 groups / 160 IDUs / 64 ODUs, and up to 15 adapters can connect
to one Central Station EX.
fitting in even small walls. fitting in even small walls. (*2) No restriction on the number of H-LINK.
(*3) Individual Feature Control in Each Remote Controller is not available.
∙ Easy monitoring with simplified interface. ∙ Easy monitoring with simplified interface. (*4) Applicable only with Schedule function or external signal input. You cannot set it up directly from monitoring panel.
(*5) Main 5 functions meaning: 1) Run/Stop 2) Operation mode 3) Temperature setting 4) Fan speed 5) Louver control.
∙ Best option for middle size buildings. ∙ Best option for small size buildings. (*6) Ability to connect unlimited number of "HC-IoTGW" in one project and control all AC units via one single screen on Web or Mobile Phone.
(*7) Unlimited creation of zones, across multiple "HC-IoTGW" units within the same project.
(*8) Visualization of outdoor unit energy consumption. 60
(*9) 4G available through optional 4G module; 4G module package comes with global SIM and pre-paid global data plan.
(*10) OTA: Over-the-air firmware update, provides always up-to-date firmware and latest functionalities.
(*11) Mini , EZ : Accumulated operation time ( min ) , Accumulated thermo - ON ( min ). 61
EX : A
ccumulated operation time ( min ) , Accumulated thermo - ON time ( min ) , Average air intake temperature of indoor unit , Average air intake temperature of outdoor unit , Average setting
temperature , Average RC sensor temperature.
–
CENTRALIZED CONTROLLERS
[Gateway]
✓ Intuitive simplicity
200mm
For stand-alone airCloud Pro is designed to make your job easier.
Functions
• Access via smartphone app or web • On/Off • Mode • Set temperature
IoT connection • Air intake temperature • RC sensor temperature (*3)
• Unlimited number of gateways
(cloud-based) • Air intake temperature of outdoor unit
• Unlimited number of locations Monitor Function
• Unlimited number of users • Fan Speed • Louver • RC prohibition
CENTRALIZED CONTROLLERS
Schedule function
• Per indoor unit remote control group • Operation mode • Setting temperature
• Louver • Fan speed
Simplify your job Save more energy
• On/Off • Mode • Set temperature
Control function • Fan speed • Louver • RC lock * “All Groups Run/Stop” command signal exception function for selected groups is available by The pilot app makes managing Monitor energy consumption
• Filter sign reset “Exception of Run/Stop Operation.” function. your VRF systems easy. and optimize usage.
*1 Confirm compatibility of your VRF installation with your Hitachi Cooling & Heating representative. *2 Functions not available as of September 2019, coming soon. 63
*3 4G module available as a side accessory.
–
CENTRALIZED CONTROLLERS
CENTRAL STATION EX FOR LARGE-SCALE BUILDINGS (PSC-A128EX3) CENTRAL STATION EZ FOR MEDIUM-SCALE BUILDINGS (PSC-A64GT)
CENTRALIZED CONTROLLERS
Display control Touch Panel
Functions
All together
Each area
Each of the following settings is available in 3
different [annual] [summer][winter] categories:
Energy saving:
• Run/Stop
CENTRAL STATION MINI FOR SMALL-SCALE BUILDINGS (PSC-A32MN)
Operation → Weekly schedule
Each block • RC prohibition
unit → Up to 16 actions can be set per day
Each group
Each indoor unit → Exception day setting: 5 different types
• Temperature shift
(For Cool/Dry mode: +1.0°C~+9.0°C (+1.0°F~+18.0°F))
22 52.7
Capacity
→ Holiday setting (For Heat mode: -1.0°C~-9.0°C (-1.0°F~-18.0°F))
On/Off RC group 32
• Mode shift
Mode Schedule Setting items in schedule is as below: ( Mode shifted to Fan when in Cool/Dry mode, Group 32
Set temperature function • On/Off and shifted to Stop in Heat mode) Block 4 Patterns (2/4/8/16)
Fan speed • Operation mode • Capacity control on outdoor units 120mm Indoor Unit 160
Louver • Setting temperature • Lower noise control for outdoor units
Control Outdoor Unit 64
RC prohibition • Louver
function External input
Filter sign reset • Fan speed Building Scale Small
/ output Control/Monitor
Function selection for indoor units (*1) • RC operation prohibition → Controlled items:
Function selection for outdoor units (*2) • Capacity control for outdoor units
Capacity control for outdoor units (*2) • Lower noise control for outdoor units
• Run/Stop
• Mode (Cool/Heat)
140mm
Lateral view (mm) Specifications
Lower noise control for outdoor units (*2) Alarm history: 10,000 records → Monitored items:
Rated Power Supply 1-, AC 100-240V, 50/60Hz
On/Off History External In/Output history: 1,000 records • Run/Stop
Pulse input history: 6 months • Mode (Cool/Heat) Electrical Power Consumption 20W (Max.)
Mode With easy control via an 5.0 inch color touch
Set temperature Up to 2 years worth of data history can be • Alarm state Communication Unit Units of Adopting for H-LINK
Air intake temperature displayed for the following: panel, its detailed control functionalities Communication Line Non-polar 2-wire
RC sensor temperature (*3) • Accumulated operation time (min.) Others: Communication Speed 9,600bps
Monitor Air intake temperature of outdoor unit • Accumulated thermo-ON time (min.) • Power consumption signal input such as weekly scheduling, operation
Management Wiring Length 1,000m (Total Length)
function Fan Speed • Average air intake temp temperature of • Emergency stop
report hours tracking, help you save energy. Up Display 5.0-inch Wide Color LCD (Full Dot)
Louver indoor unit
visualization
RC prohibition • Average air intake temperature of outdoor (*1) Some indoor units may not fully support all functions. to 32 remote-controlled groups and up to Display Control Touch Panel
Thermo-ON information unit (*2) Available for applicable outdoor units only.
Filter sign/Auto cleaning fault • Average setting temperature 160 indoor units can be connected to the
Alarm status/Alarm codes • Average RC sensor temperature
(*3) Whether this is shown on the screen depends
on the remote controller settings. Central Station mini. Functions
• Run/Stop/Abnormality • Setting Temperature
• RC Operation Prohibited Setting
Monitor Function • Accumulated Operating Time
• Operation Mode • Setting Fan Speed
Remote access. Example: school
• Setting Louver • Filter Sign • Alarm Code"
• Run/Stop* • Fan Speed
• Operation Mode • Louver
You can now operate Central Station EX from your laptop PC or touch panel PC. Control Function • Temperature Setting
Install our software and you can connect from anywhere, using our VPN network. • RC Operation Prohibited
• Filter Reset Signal
* “All Groups Run/Stop” command signal exception function for selected groups is
Staff room available by “Exception of Run/Stop Operation.” function.
64
LAN
EX
65
–
INDIVIDUAL CONTROLLERS From basic to advanced controls
ADVANCED-COLOR ECO-COMPACT WIRED REMOTE ADVANCED WIRELESS WIRELESS REMOTE
CONTROLLER CONTROLLER CONTROLLER REMOTE CONTROLLER CONTROLLER
INDIVIDUAL CONTROLLERS
&simplified),FR, ES,PT
Ready-to-tap controllers
∙ NFC chip embedded in the controller
INDIVIDUAL CONTROLLERS
∙ Time saving setting process
∙ Reduced need of documentation support
Specify settings for one room, save them, then apply these settings to other similar rooms in one tap. Particularly useful for multiple zones with
similar needs! Hotel guestrooms, office meeting rooms, condominium units, etc.
STEP1 STEP2
Read the settings from one device Hold the mobile device over each product and
and save settings. write settings of STEP1.
1. Activate the NFC function on 2.Open the airCloud Tap app 3. Edit the desired settings on 4.Tap again your equipment to
the AC equipment. and tap the AC equipment with your phone. apply the new settings.
your phone to read the current
settings.
68
69
–
INDIVIDUAL CONTROLLERS
NEW
• Modern and subtle colors advanced comfort settings OK Select Back OK Select Back OK Select Back
help customizing the air to GentleCool limits the temperature AutoBoost automatically activates AC Scheduling is easier than ever,
their occupants' specific of conditioned air, preventing cold for 30 minutes every time the AC is thanks to flexible features such as
drafts for optimal comfort. turned on, helping the room reach the holiday calendar.
needs.
the desired temperature faster.
INDIVIDUAL CONTROLLERS
1 Room name Outer dimensions (H×W×D)
2 Set temperature 120×120×16.5mm (thinnest part)
1 12
3 Operation mode
The latest VRF features
120×120×21.5mm (thickest part)
2
4 Indoor unit ON/OFF light
Installation Menu FrostWash Setting 01-01 Function Menu
5 Indoor unit ON/OFF Fan Speed at Cooling Thermo-OFF 1 2 3 4 Simple Timer
2
6 Navigation buttons Capacity Fan Speed at Heating Thermo-OFF
Start Frost Wash
Start
Auto
Main the
RCS FrostWash
Clearning
cannot Now?
beStart/Disable
detected. Operation Schedule
3 9 10 11 Indoor Unit Address Change Press OK Wash
Frost to set this as Main RCS.
Intervals OK Power Saving Setting
7 Back button Power Supply Powered by indoor unit, 15VDC±10% Indv. Indv. Indv. Indv.
Address Check Operation Frost
YesWash Available
CancelTiming Night Quiet Operation
OK
4 8 OK button 180g (approx.) Address Initialization Frost Wash History Power Sav./Night Quiet Schedule
Adjust air direction & louver angle.
8 Installation Indoor, on the wall or switch box
9 Fan speed OK Enter Back OK Confirm Back Back OK Enter Back
7 Connection capacity Up to 16 indoor units (with the same wired remote controller)
5 6 10 Louver direction When two wired Advanced Controller units are connected to the same indoor
Fan speed at thermo-off Activate, schedule and check Individual 4-way cassette louvers Schedule Night Quiet mode
▲ Display reduces air circulation when the history of indoor units’ optimizes air flow direction to each to minimize the outdoor unit’s
11 Access to menu unit, the maximum brightness of each controller will be halved
cooling or heating is not FrostWashTM function. corner layout. operation noise so you and your
12 Filter cleaning reminder
*H is the height of the unit from the front, without the effective. neighbors get a better night’s sleep.
protrusion at the bottom.
Simultaneous control for up to 16 IDU with transition wiring Ideal for indoor units with motion sensor features
Active intelligent comfort features connected to your indoor unit’s motion sensor and/or radiant sensor*: choice of direct/indirect air flow, FeetWarm
Primary RC Secondary RC H-LINK
NEW, FloorSense Cool NEW and the exclusive Crowd-Sense NEW to prevent heat peak from rapid crowd arrival. 70
Remote Control Cable
71
–
INDIVIDUAL CONTROLLERS
NEW
Functional spaces
The Peak-Cut feature enables users to save even Include GentleCool, which controls the
more energy during peak consumption periods. discharged air temperature for a smooth
cooling down and prevents cold drafts.
INDIVIDUAL CONTROLLERS
Low Med High
1 Set Temperature Outer dimensions (H×W×D)
1 2 Operation mode 90mm×90mm×15.5mm(thinnest part)
11 Weekly scheduling automatically turns the indoor AutoBoost activates for 30 minutes every time the AC is turned
3 Run indicator 90mm×90mm×18.5mm(thickest part) unit on/off at set times, great for classrooms, retail on, helping the room reach the desired temperature faster
4 On/Off button businesses or other premises with regular opening with a powerful automatic mode, which is ideal for meeting
5 Operation mode button hours. rooms and other areas requiring fast temperature reach.
6 Fan speed button Capacity
2
10
7 Menu buttons Power Supply Powered by indoor unit, 15VDC±10%
3 9 8 Directional key 100g (approx.)
Installation Indoor, on the wall or switch box
9 Fan speed
10 Louver direction
Connection capacity Up to 16 indoor units (with the same wired remote controller)
Supports easy Special features
4 5 6 7 8
11 Current time maintenance For residential users: For hotels:
set the Sleep mode timer NEW interlock the Eco-Compact Controller
A filter symbol appears when it’s time
to gradually change the room with your hotel key card receiver and
to clean the filter.In the event of an temperature for a better night's activate setback temperature while
error, the error code and the related sleep. The unit will turn off guest is away.
automatically after a set time.
indoor unit number is clearly displayed
1 2
Possibility of 2 Wired Controller Connection Up to 16 IDU connection
3 Embedded IR receiver
4
For use with the Wireless
Remote Controller. Ideal
2 RC control for indoor units without
is available ........
embedded IR receiver
(ex: ducted units)
Simultaneous control for up to 16 IDU with transition wiring
1 Alarm Icon
H-LINK
2 Indoor Unit No.(Refrigerant system) Wireless Remote Controller
Primary RC Secondary RC (sold separately)
3 Indoor Unit No.(Refrigerant system) 72
Remote Control Cable
Over the closet In dropped ceiling, over window
4 Alarm Code When IR receiver receives the commands, the buzzer sounds. 73
*Compatible HCRB10NEWQand PC-LH7QE/PC-LH7QE1 wireless controllers
–
INDIVIDUAL CONTROLLERS
INDIVIDUAL CONTROLLERS
RECEIVER KIT FOR WIRELESS REMOTE CONTROLLER
Model
Model
Specifications
Operation example
Outer dimensions (H×W×D)
∙Cooling operation: ∙Heating operation:
(mm) 68.0×240.0×154.0
Compressor is ON by closing terminals 2 Compressor is ON by closing terminals 1
and 3 of CN3. and 2 of CN3.
3P CONNECTOR CABLE BMS ADAPTER FOR BACNET® Functions
Compressor is OFF by opening terminals Compressor is OFF by opening terminals
(PCC-1A) 2 and 3 of CN3. 1 and 2 of CN3. ( HC-A64BNP1) Corresponding ANSI/ASHRAE Standard 135-2004 • Run Stop (State)
BACnet® Standard BACnet® • Operation Mode (State)
• Run Stop (Setting) • Fan Speed Level (State)
FOR CONNECTION TO REMOTE ON/OFF *One set contains five 3P connector cables. CONTROL UP TO 64 INDOOR UNITS • Operation Mode (Setting) • Indoor Temperature (State)
Control Item at • Fan Speed Level (Setting) Monitoring Item at • Prohibiting RC Operation (State)
DEVICE/RECEIPT OF OUTPUT SIGNAL *PCC-1A can connect to external signal input-output terminal both in outdoor unit and indoor unit.
Upper System • Indoor Temperature (Setting) Upper System • Filter Signal
• Indoor Air Intake Temperature
System configuration example
• RC Operation lock (Setting)
• Filter Sign Reset • Alarm Signal
«PCC-1A» 3
2
1
System configuration example
Thermostat
3 CN3 H-LINK
2 Remote control cable
1 BACnet ®
Temperature
increase Field-supplied
Remote ON/OFF device
Indoor unit PCB Fire
Lighting alarm Lift Ventilation
H-LINK Centralized
controller
Remote control cable
(mm) 50.0×50.0×15.0
BACnet ®
ACCESSORIES
HC-A64BNP1
H-LINK
«THM-R2A»
Remote sensor cord
3x
in different places.
1 2 3 • Some indoor units of each
respective system are close
Flexible wiring Can connect to one another.
No adapter
routes: with various types of
is needed! H-LINK SOLUTION
more
no restrictions & Hitachi air conditioning
products, including VRF Simple connection
Where two indoor units
time-saving of each respective system
and mini splits, to terminal blocks. are close together: you
benefits! at installation.
for centralized controls.
can connect two
refrigerant systems via
the indoor units.
Wiring distance is
CENTRAL CONTROL
reduced substantially.
ROOM AREA 1 AREA 2
H-LINK SOLUTION
Connect the farthest
Indoor unit refrigerant system
directly to central station
either to outdoor units
or indoor units.
The central station
can make the central link
between the different
refrigerant systems.
CENTRAL CONTROL
2 2 2 2 2 AREA 1 ROOM AREA 2
RC Group RC Group RC Group RC Group RC Group
1
CS-NET
3 3
Group Group
(4) • Each refrigerant
4 system in separate
Block areas.
1 CS-NET/Central station
• Indoor units are
Hitachi original centralized controller. closer from one
2 RC Group (Remote Controller System Group) group to another.
tands for a number of indoor units (up to 16 units) connected using "same remote controller" wiring.
S H-LINK SOLUTION
In this group, connected indoor units are all controlled in the same way. entralized control can
C
be achieved by connecting
3 Group the refrigerant systems
via the closer indoor units.
Stands for the multiple "RC groups" that are registered in the centralized controller network setting.
Wiring can be indoors
4 Block only.
CENTRAL CONTROL
78
Stands for the multiple "groups" that are registered in the centralized controller network setting. ROOM AREA 1 AREA 2 AREA 3 AREA 4
79