Professional Documents
Culture Documents
Power distribution in medium voltage.
DESCRIPTION
Application
Power distribution in medium voltage. As transformer feeders in substations. In power
plants, industrial and operation installations, in residential areas and mining
installations, in dry or wet locations.
Construction
1. Conductor: Compact stranded 1350 aluminium, class 2.
STANDARDS
2. Inner semiconductor: Extruded.
International IEC 60228;
3. Insulation: Cross linked polyethylene XLPETR (Tree retardant).. IEC 6033212; IEC 605022;
IEC 60811401; IEC 60811402;
4. External semiconductor: Extruded strippable.
IEC 60811409; IEC 60811501;
These last three components extruded CV (continuous vulcanization) triple extrusion in IEC 60811502; IEC 60811504;
dry cure process. IEC 60811505; IEC 60811506;
IEC 60811507; IEC 60811508;
5. Individual screen: Copper tapes. IEC 60811509
6. Filler: Compound polyvinyl chloride PVC. National ICEA S93639; NTP
IEC 60228; NTPIEC 605022;
7. Outer sheath: Compound polyvinyl chloride PVC. UL 2556
Main characteristics
Excellent properties against heat aging. Resistance to abrasion, moisture and sunlight.
Adequate resistance to greases and oils. Flame retardant.
Cross section:
70 mm2, 95 mm2 and 120 mm2.
Marking:
INDECO S.A. NA2XSEY 3,6/6 kV Nb. Cores x Section Year Sequential length.
Packing:
Non returnable wooden reels.
Colour:
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 1/21/22 www.nexans.pe Page 1 / 5
NA2XSEY 3,6/6 kV Contact
NA2XSEY 3,6/6 kV 3x120 mm2 Local Sales
ventas.peru@nexans.com
Insulation: Natural.
Outer sheath: Red.
National standards
NTP-IEC 60502-2: Power cables with extruded insulation and their accessories for
rated voltages from 6 kV up to 30 kV.
International standards
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 1/21/22 www.nexans.pe Page 2 / 5
NA2XSEY 3,6/6 kV Contact
NA2XSEY 3,6/6 kV 3x120 mm2 Local Sales
ventas.peru@nexans.com
ICEA S-93-639: 546 kV Shielded Power Cable for Use in the Transmission and
Distribution of Electric Energy. Section 9.4.2: Oil Immersion Test.
CHARACTERISTICS
Construction characteristics
Conductor material Aluminum Alloy 1350
Material of the inner semiconductor Extruded
Insulating material XLPETR
Material of the external semiconductor Extruded strippable
Individual screen Copper tapes helically applied
Outer sheath PVC
Sheath colour Red
Lead free Yes
Conductor exibility Class 2 IEC 60228
Conductor shape Compact stranded
Dimensional characteristics
Number of cores 3
Conductor crosssection 120 mm²
Conductor diameter 12.8 mm
Diameter over insulation 18.5 mm
Diameter over screen 20.2 mm
Diameter over Sheath 49.9 mm
Approximate weight 3317 kg/km
Screen thickness 100 µm
Total number of wires 19
Electrical characteristics
Max. DC resistance of the conductor at 20°C 0.253 Ohm/km
Rated Voltage Uo/U (Um) 3.6 / 6 (7.2) kV
Dielectric strength core to screen DC, min. 12.5 kV
Time of application Dielectric strength core to screen DC 5 min.
Voltage for partial discharge test 6.3 kV
Maximal partial discharge test 10 pC
Impulse voltage 60 kV
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 1/21/22 www.nexans.pe Page 3 / 5
NA2XSEY 3,6/6 kV Contact
NA2XSEY 3,6/6 kV 3x120 mm2 Local Sales
ventas.peru@nexans.com
Electrical characteristics
Nominal capacitance 486.0 pF/m
A.C. Conductor resist. at 90 °C trefoil formation 0.3254 Ohm/km
Phase reactance 60 Hz trefoil formation 0.1055 Ohm/km
Perm. current rating buried 20°C trefoil formation 232 A
Perm. current rating in air 30°C trefoil formation 273 A
Usage characteristics
U.V resistance UL 2556 Sunlight Resistance
Flame retardant IEC 6033212; FT1
Oil resistance ICEA S93639
Maximum operating temperature 90 °C
Overload maximum core temperature 130 °C
Shortcircuit max. conductor temperature 250 °C
R=Dxf
R:Bending radius when installed (mm)
D:Diameter over sheath (mm)
f: Multiplicative factor; given the following table:
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 1/21/22 www.nexans.pe Page 4 / 5
NA2XSEY 3,6/6 kV Contact
NA2XSEY 3,6/6 kV 3x120 mm2 Local Sales
ventas.peru@nexans.com
Maximum conductor temperature: 90°C.
Ambient air temperature: 30°C.
Ground temperature: 20°C.
Depth of laying: 0,8 m.
Thermal resistivity of soil: 1,5 K.m/W.
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 1/21/22 www.nexans.pe Page 5 / 5