You are on page 1of 5

NA2XSEY 3,6/6 kV Contact

NA2XSEY 3,6/6 kV 3x120 mm2 Local Sales


ventas.peru@nexans.com

Nexans Ref.: P00013596­3

Power distribution in medium voltage.

DESCRIPTION
Application

Power distribution in medium voltage. As transformer feeders in substations. In power
plants,  industrial  and  operation  installations,  in  residential  areas  and  mining
installations, in dry or wet locations.

Construction

1. Conductor: Compact stranded 1350 aluminium, class 2.
STANDARDS
2. Inner semi­conductor: Extruded.
International IEC 60228;
3. Insulation: Cross linked polyethylene XLPE­TR (Tree retardant).. IEC 60332­1­2; IEC 60502­2;
IEC 60811­401; IEC 60811­402;
4. External semi­conductor: Extruded strippable.
IEC 60811­409; IEC 60811­501;
These last three components extruded CV (continuous vulcanization) triple extrusion in IEC 60811­502; IEC 60811­504;
dry cure process. IEC 60811­505; IEC 60811­506;
IEC 60811­507; IEC 60811­508;
5. Individual screen: Copper tapes. IEC 60811­509

6. Filler: Compound polyvinyl chloride PVC. National ICEA S­93­639; NTP­
IEC 60228; NTP­IEC 60502­2;
7. Outer sheath: Compound polyvinyl chloride PVC. UL 2556

Main characteristics

Excellent properties against heat aging. Resistance to abrasion, moisture and sunlight.
Adequate resistance to greases and oils. Flame retardant.

Cross section:

70 mm2, 95 mm2 and 120 mm2.

Marking:

INDECO S.A. NA2XSEY 3,6/6 kV ­ Nb. Cores x Section ­ Year ­ Sequential length.

Packing:

Non returnable wooden reels.

Colour:

Lead free Conductor exibility Rated Voltage Uo/U U.V resistance Flame retardant Oil resistance Maximum operating


Yes Class 2 IEC 60228 (Um) UL 2556 - Sunlight IEC 60332-1-2; FT1 ICEA S-93-639 temperature
3.6 / 6 (7.2) kV Resistance 90 °C

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 1/21/22 www.nexans.pe Page 1 / 5
NA2XSEY 3,6/6 kV Contact
NA2XSEY 3,6/6 kV 3x120 mm2 Local Sales
ventas.peru@nexans.com

Insulation: Natural.

Outer sheath: Red.

National standards

NTP-IEC 60228: Conductors of insulated cables.

NTP-IEC 60502-2: Power  cables  with  extruded  insulation  and  their  accessories  for
rated voltages from 6 kV up to 30 kV.

International standards

IEC 60228: Conductors of insulated cables.

IEC 60502-2: Power cables with extruded insulation and their accessories for rated


voltages from 6 kV up to 30 kV.

IEC 60332-1-2: Test for vertical ame propagation for a single insulated wire or cable ­


Procedure for 1 kW pre­mixed ame.

UL 2556: Wire and Cable Test Methods. Section 9.3: FT1 (Vertical­Specimen) Flame


Test.

IEC 60811-401: Thermal ageing methods. Ageing in an air oven.

IEC 60811-402: Water absorption tests.

IEC 60811-409: Loss of mass test for thermoplastic insulations and sheaths.

IEC 60811-501: Test for determining the mechanical properties.

IEC 60811-502: Shrinkage test for insulations.

IEC 60811-504: Bending test at low temperature for insulation and sheaths.

IEC 60811-505: Elongation at low temperature for insulations and sheaths.

IEC 60811-506: Impact test at low temperature for insulations and sheaths.

IEC 60811-507: Hot set test for cross­linked materials.

IEC 60811-508: Pressure test at high temperature for insulation and sheaths.

IEC 60811-509: Test for resistance of insulations and sheaths to cracking.

Lead free Conductor exibility Rated Voltage Uo/U U.V resistance Flame retardant Oil resistance Maximum operating


Yes Class 2 IEC 60228 (Um) UL 2556 - Sunlight IEC 60332-1-2; FT1 ICEA S-93-639 temperature
3.6 / 6 (7.2) kV Resistance 90 °C

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 1/21/22 www.nexans.pe Page 2 / 5
NA2XSEY 3,6/6 kV Contact
NA2XSEY 3,6/6 kV 3x120 mm2 Local Sales
ventas.peru@nexans.com

ICEA S-93-639: 5­46  kV  Shielded  Power  Cable  for  Use  in  the  Transmission  and
Distribution of Electric Energy. Section 9.4.2: Oil Immersion Test.

UL 2556: Wire and Cable Test Methods. Section 4.2.8.5: Carbon­Arc and Xenon­Arc


Tests­ Sunlight resistance.

CHARACTERISTICS
Construction characteristics
Conductor material Aluminum Alloy 1350
Material of the inner semi­conductor Extruded
Insulating material XLPE­TR
Material of the external semi­conductor Extruded strippable
Individual screen Copper tapes helically applied
Outer sheath PVC
Sheath colour Red
Lead free Yes
Conductor exibility Class 2 IEC 60228
Conductor shape Compact stranded
Dimensional characteristics
Number of cores 3
Conductor cross­section 120 mm²
Conductor diameter 12.8 mm
Diameter over insulation 18.5 mm
Diameter over screen 20.2 mm
Diameter over Sheath 49.9 mm
Approximate weight 3317 kg/km
Screen thickness 100 µm
Total number of wires 19
Electrical characteristics
Max. DC resistance of the conductor at 20°C 0.253 Ohm/km
Rated Voltage Uo/U (Um) 3.6 / 6 (7.2) kV
Dielectric strength core to screen DC, min. 12.5 kV
Time of application Dielectric strength core to screen DC 5 min.
Voltage for partial discharge test 6.3 kV
Maximal partial discharge test 10 pC
Impulse voltage 60 kV

Lead free Conductor exibility Rated Voltage Uo/U U.V resistance Flame retardant Oil resistance Maximum operating


Yes Class 2 IEC 60228 (Um) UL 2556 - Sunlight IEC 60332-1-2; FT1 ICEA S-93-639 temperature
3.6 / 6 (7.2) kV Resistance 90 °C

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 1/21/22 www.nexans.pe Page 3 / 5
NA2XSEY 3,6/6 kV Contact
NA2XSEY 3,6/6 kV 3x120 mm2 Local Sales
ventas.peru@nexans.com

Electrical characteristics
Nominal capacitance 486.0 pF/m
A.C. Conductor resist. at 90 °C ­ trefoil formation 0.3254 Ohm/km
Phase reactance 60 Hz ­ trefoil formation 0.1055 Ohm/km
Perm. current rating buried 20°C ­ trefoil formation 232 A
Perm. current rating in air 30°C ­ trefoil formation 273 A
Usage characteristics
U.V resistance UL 2556 ­ Sunlight Resistance
Flame retardant IEC 60332­1­2; FT1
Oil resistance ICEA S­93­639
Maximum operating temperature 90 °C
Overload maximum core temperature 130 °C
Short­circuit max. conductor temperature 250 °C

BENDING RADIUS INSTALLED IN M.V

R=Dxf
R:Bending radius when installed (mm)

D:Diameter over sheath (mm)

f: Multiplicative factor; given the following table:

BENDING RADIUS FACTOR MV

Lead free Conductor exibility Rated Voltage Uo/U U.V resistance Flame retardant Oil resistance Maximum operating


Yes Class 2 IEC 60228 (Um) UL 2556 - Sunlight IEC 60332-1-2; FT1 ICEA S-93-639 temperature
3.6 / 6 (7.2) kV Resistance 90 °C

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 1/21/22 www.nexans.pe Page 4 / 5
NA2XSEY 3,6/6 kV Contact
NA2XSEY 3,6/6 kV 3x120 mm2 Local Sales
ventas.peru@nexans.com

CALCULATION OF CURRENT CONDITION MULTI-CORE M.V.

CALCULATION OF CURRENT CONDITION BASED ON NTP-IEC 60502-2 Annex B

Maximum conductor temperature: 90°C.
Ambient air temperature: 30°C.
Ground temperature: 20°C.
Depth of laying: 0,8 m.
Thermal resistivity of soil: 1,5 K.m/W.

Lead free Conductor exibility Rated Voltage Uo/U U.V resistance Flame retardant Oil resistance Maximum operating


Yes Class 2 IEC 60228 (Um) UL 2556 - Sunlight IEC 60332-1-2; FT1 ICEA S-93-639 temperature
3.6 / 6 (7.2) kV Resistance 90 °C

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 1/21/22 www.nexans.pe Page 5 / 5