1MRS752358-MUM CMCU3

Issued: 10/1997 Supervision Function of the Energizing


Version: F/21.8.2003
Current Input Circuit
Data subject to change without notice

Contents

1. Introduction...................................................................................................2

1.1 Application ...............................................................................................2


1.2 Input description ......................................................................................2
1.3 Output description...................................................................................2
2. Description of operation ............................................................................ 3

2.1 Configuration ...........................................................................................3


2.2 Measuring mode......................................................................................3
2.3 Operation criteria.....................................................................................3
2.4 Test mode ...............................................................................................4
2.5 Registers.................................................................................................4
2.6 Resetting .................................................................................................5
3. Parameters and events ............................................................................... 6

3.1 General....................................................................................................6
3.2 Control settings .......................................................................................7
3.3 Measurement values ...............................................................................7
3.3.1 Input data .......................................................................................7
3.3.2 Output data ....................................................................................7
3.3.3 Recorded data 1 ............................................................................8
3.3.4 Recorded data 2 ............................................................................8
3.3.5 Recorded data 3 ............................................................................8
3.3.6 Events ............................................................................................8
4. Technical data .............................................................................................. 9
CMCU3 Substation Automation

1. Introduction

1.1 Application

This document specifies the function of the phase current supervision function block
CMCU3 used in products based on the RED 500 Platform.

Figure 1. Function block symbol of CMCU3

1.2 Input description

Name Type Description


IL1 Analogue signal (SINT) Input for measuring phase current IL1
IL2 Analogue signal (SINT) Input for measuring phase current IL2
IL3 Analogue signal (SINT) Input for measuring phase current IL3

1.3 Output description

Name Type Description


ALARM Digital signal Alarm signal output
(BOOL, active high)
ERR Digital signal Signal for indicating a configuration
(BOOL, active high) error

2
Substation Automation CMCU3

2. Description of operation

2.1 Configuration

The function block measures phase currents by means of conventional current


transformers or Rogowski coils. The measuring devices and signal types for analogue
channels are selected and configured in a special dialogue box of the Relay
Configuration Tool.

When the analogue channels have been selected and configured in the dialogue box,
the inputs and outputs of the function block can be configured on a graphical
worksheet of the configuration tool. The phase currents IL1, IL2 and IL3 are connected
to the corresponding IL1, IL2 and IL3 inputs of the function block and, in the same
way, the digital outputs of the function block are connected to the output signals.

CMCU3 can be used with two or three current measurement channels. If only two
channels are available, the remaining third analogue channel input shall be left
unconnected. If this is the case, CMCU3 will adapt the setting "Current select"
automatically according to the connected inputs. Changing this setting will not be
possible unless all three inputs are connected.

2.2 Measuring mode

The function block operates on the numerically calculated fundamental frequency


component of the phase currents.

2.3 Operation criteria

The supervision function block CMCU3 detects interruptions in energizing circuits. The
user can select three-phase or two-phase operation with the parameter “Current
select”. The function block can also be set out of use by means of the parameter
“Operation mode”.

The function block supervises the energizing circuits by comparing the measured phase
currents. If one or two phase currents exceed the setting “High limit”, while the
measured phase current in the remaining one or two phases is below the setting “Low
limit”, the output ALARM is activated after the settable alarm delay.

The function block is disabled if all input currents are below the setting “Low limit”.

The ALARM output will reset automatically when the fault disappears.

3
CMCU3 Substation Automation

Figure 2. Basic block diagram of the CMCU3 function block

2.4 Test mode

The user can activate the ALARM output of the function block with the control
parameter “Test ALARM” either locally via the MMI or externally via the serial
communication.

2.5 Registers

The function block records the phase current values required for later fault analysis at
the moment of the supervision alarm, i.e. when the set operate time delay (parameter
“Alarm delay”) has elapsed.

4
Substation Automation CMCU3

2.6 Resetting

The user does not need to acknowledge the ALARM output signal but it resets
automatically when the fault disappears.

The operation indicators and recorded data can be reset as follows:

Operation Recorded
indicators data
1)
General parameter F001V011 X
1)
General parameter F001V013 X X
1)
Push-button C X
1)
Push-buttons C + E (5 s) X X
1)
Affects all function blocks.

5
CMCU3 Substation Automation

3. Parameters and events

3.1 General

• Each function block has a specific channel number for serial communication
parameters and events. The channel for CMCU3 is 181.

• The data direction of the parameters defines the use of each parameter as follows:
Data direction Description
R, R/M Read only
W Write only
R/W Read and write

• The different event mask parameters (see section “Control settings”) affect the
visibility of events on the MMI or on serial communication (LON or SPA) as
follows:
Event mask 1 (FxxxV101/102) SPA / MMI (LON)
Event mask 2 (FxxxV103/104) LON
Event mask 3 (FxxxV105/106) LON
Event mask 4 (FxxxV107/108) LON

For example, if only the events E3, E4 and E5 are to be seen on the MMI of the
relay terminal, the event mask value 56 (8 + 16 + 32) is written to the “Event mask
1” parameter (FxxxV101).
In case a function block includes more than 32 events, there are two parameters
instead of e.g. the “Event mask 1” parameter: the parameter “Event mask 1A”
(FxxxV101) covers the events 0...31 and “Event mask 1B”(FxxxV102) the events
32...63.

6
Substation Automation CMCU3

3.2 Control settings

Parameter Code Values Unit Default Data Explanation


direction
Operation mode V1 0 or 1 1) - 1 R/W Switching between the modes "In use"
and "Not in use"

Current select. V2 1...4 2) - 1 R/W Selection of phase currents to be


supervised

High limit V3 10...20 % In 12 R/W High limit for phase current supervision

Low limit V4 2...8 % In 6 R/W Low limit for phase current supervision

Alarm delay V5 3...60 s 15 R/W Operate time delay

Test ALARM V31 0 or 1 3) - 0 R/W Testing of alarm output

Event mask 1 V101 0...3 - 3 R/W Event mask 1 for event transmission
(E0 ... E1)

Event mask 2 V103 0...3 - 3 R/W Event mask 2 for event transmission
(E0 ... E1)

Event mask 3 V105 0...3 - 3 R/W Event mask 3 for event transmission
(E0 ... E1)

Event mask 4 V107 0...3 - 3 R/W Event mask 4 for event transmission
(E0 ... E1)
1)
Operation mode 0 = Not in use; 1 = In use
2)
Current selection 1 = L1 & L2 & L3; 2 = L1 & L2; 3 = L1 & L3; 4 = L2 & L3
3)
Test alarm 0 = Do not activate; 1 = Activate

3.3 Measurement values

3.3.1 Input data

Parameter Code Values Unit Default Data Explanation


direction
Current IL1 I1 0.00...60.00 x In 0.00 R/M Phase current IL1

Current IL2 I2 0.00...60.00 x In 0.00 R/M Phase current IL2

Current IL3 I3 0.00...60.00 x In 0.00 R/M Phase current IL3

3.3.2 Output data

Parameter Code Values Unit Default Data Explanation


direction
Output ALARM O1 0 or 1 1) - 0 R/M Status of alarm signal
1)
Alarm activation 0 = Not active; 1 = Active

7
CMCU3 Substation Automation

3.3.3 Recorded data 1

Parameter Code Values Unit Default Data Explanation


direction
Date V201 YYYY-MM-DD - - R/M Recording date

Time V202 hh:mm:ss.000 - - R/M Recording time

Current IL1 V203 0.00...60.00 x In 0.00 R/M Value of current IL1

Current IL2 V204 0.00...60.00 x In 0.00 R/M Value of current IL2

Current IL3 V205 0.00...60.00 x In 0.00 R/M Value of current IL3

3.3.4 Recorded data 2

Parameter Code Values Unit Default Data Explanation


direction
Date V301 YYYY-MM-DD - - R/M Recording date

Time V302 hh:mm:ss.000 - - R/M Recording time

Current IL1 V303 0.00...60.00 x In 0.00 R/M Value of current IL1

Current IL2 V304 0.00...60.00 x In 0.00 R/M Value of current IL2

Current IL3 V305 0.00...60.00 x In 0.00 R/M Value of current IL3

3.3.5 Recorded data 3

Parameter Code Values Unit Default Data Explanation


direction
Date V401 YYYY-MM-DD - - R/M Recording date

Time V402 hh:mm:ss.000 - - R/M Recording time

Current IL1 V403 0.00...60.00 x In 0.00 R/M Value of current IL1

Current IL2 V404 0.00...60.00 x In 0.00 R/M Value of current IL2

Current IL3 V405 0.00...60.00 x In 0.00 R/M Value of current IL3

3.3.6 Events

Code Weighting Default mask Event reason Event state


coefficient
E0 1 1 Current input circuit alarm Off

E1 2 1 Current input circuit alarm On

8
Substation Automation CMCU3

4. Technical data
Operation accuracies Depends on the frequency of the current measured:

f/f n = 0.95...1.05: ± 2.5 % of set value or ± 0.01 x In

Configuration data Task execution interval (Relay Configuration Tool): 100 ms


at the rated frequency f n = 50 Hz

Technical revision history


Technical revision Change
B -

C Control settings: Operate mode → Operation mode