Calibration Instruction 1 Calibration Instruction for Salwico ST400 H2S

1 Calibration Instruction for Salwico ST400


H2S

1.1 Preliminaries
This instructions applies to the following products:

Figure 1. Salwico ST400 H2S, 0-30 ppm 4-20 mA. Part no. 4462

The H2S sensor is Electrochemical and measures H2S content by means of


chemical reaction.

DANGER!
H2S – Hydrogen Sulphide – is toxic and dangerous also in rather low concentrations.

H2S is a sticky gas and smells very distinctly from rotten eggs.

Consilium Replacement article number for ST400 H2S detectors is no. 004462-S.

A new sensor is supplied without the metal housing and must be fitted in the
housing. This applies to both H2S and O2 sensors of ST400 type.

Calibration equipment
Normal measuring range is 0-30 ppm, our standard calibration bottle no.
5201005-00A contains 20 ppm of gas in air.

For SW2020 a mix-bottle is often used, with H2S 20 ppm as well as N2 99% and
C3H8 50% LEL, article no. 5201010-01A.

Test points (A) for the multi-meter as well as “SPAN” (B) and “ZERO” (C)
potentiometers are indicated below.

CAUTION!
Do not adjust the other potentiometers.

5103028_Salwico ST400 H2S_Calibration Instruction_I0_EN_2019_C 1


1 Calibration Instruction for Salwico ST400 H2S Calibration Instruction

A Test points
B SPAN potentiometer
C ZERO potentiometer

1.2 Prerequisites
1 Use the arrow keys on the control panel to
manoeuvre through the different menus.
Press the right arrow key to access the
menu tree.

2 Scroll to 4 Gas Detectors and press


Continue.

3 Scroll to the detector that should be


calibrated and press Options.

4 Scroll to 3 Disable and choose Continue.

5 You have to confirm the disablement before


you can proceed.
Press Disable to continue.

2 5103028_Salwico ST400 H2S_Calibration Instruction_I0_EN_2019_C


Calibration Instruction 1 Calibration Instruction for Salwico ST400 H2S

6 You will get a confirmation message that


the detector has been disabled.
Press Close to continue.

7 NOTE!
For the following steps in the
zero calibration instruction
proceed to the Salwico ST400
detector.

1.3 Calibrating the sensor (Zero calibration)


1 Connect the Multi-meter (set to mA) as
shown in the picture.

2 Adjust with the “ZERO” potentiometer to


4,0 mA signal output.

1.4 Calibrating the sensor (Span calibration)


Verification of detector type 0-25 ppm or 0-30 ppm
NOTE!
The ST400 for H2S is available in two types.

Type 1: 0-25 PPM. mA-signal at 20 ppm = 16.8 mA.

Type 2: 0-30 PPM. mA-signal at 20 ppm = 14.6 mA.

To verify which type is in use, make a span calibration as below and verify the
display reading in the central cabinet.

• If the readout at 14.6 mA is less than 20 PPM a calibration with 16.8 mA


set-point must be done.

5103028_Salwico ST400 H2S_Calibration Instruction_I0_EN_2019_C 3


1 Calibration Instruction for Salwico ST400 H2S Calibration Instruction

Span calibration

1 Connect the gas bottle with flowcap to the CAUTION!


sensor head. Due to the sticky
nature of the H2S as
short hoses as possible
are to be used.
2 Open the regulator valve.
3 When the reading is stabilized, adjust the If this reading cannot be
readout to 14.6 mA (or 16.8 mA) with the reached, the sensor head
“SPAN” potentiometer. should be replaced.
NOTE!
Response can be estimated to
several minutes in some cases.

1.5 Reconnecting disabled detectors


All disablements in the CGD50/500 gas detection system are presented in the
disablements list. Any enablement is made from this list.

1 Scroll to Menu » Disablements.


2 Choose the detector you just disabled and press Options.
3 Select Reconnect and press Continue.

4 5103028_Salwico ST400 H2S_Calibration Instruction_I0_EN_2019_C


Calibration Instruction 1 Calibration Instruction for Salwico ST400 H2S

5103028_Salwico ST400 H2S_Calibration Instruction_I0_EN_2019_C 5


FOR ALL THOSE MOMENTS
WHEN SAFETY MATTERS
Consilium is a producer of safety and safety-related technologies for the marine, oil and gas,
transport and building sectors. Our commitment goes beyond the products: We protect the
lives of mothers and fathers, sisters and brothers, colleagues and friends. With representation in
more than 25 countries in all time zones, we are always close to you.

www.consilium.se

You might also like