Professional Documents
Culture Documents
P. O. BOX 1234
ANYWHERE, USA 12345
Serial: 17-111-0
Location: COMPANY
Reviewed By:
TECHNICAL MANAGER, LEVEL III
CHEMICALS CORP
P. O. BOX 1234
ANYWHERE, USA 12345
Serial: 17-111-0
Location: COMPANY
Reviewed By:
TECHNICAL MANAGER, LEVEL III
TABLE OF CONTENTS
Calibration Procedures
SUMMARY OF INSPECTION
An eddy current tube inspection was performed as part of a preventive maintenance program
with the following results.
RESTRICTED 1 0.33
RECOMMENDATIONS
The tubes in this machine were tested for normal wear patterns using accepted test methods for
eddy current inspections. The possibility does exist that tubes could contain abnormal wear
patterns, defects and/or leaks not detectable by normal eddy current test methods.
The following suggested repair actions are based on accepted industry standards. After
removing sample tubes to confirm the inspection results, a determination of corrective action
should be made by the repair agency and end user. Only these parties have knowledge of the
critical applications and long-term use of the equipment. If plugging is selected over
replacement, both efficiency and capacity should be considered.
HEAT EXCHANGER:
Tubes marked for Excessive Dents showed indications of stress or wear, or were located in the
bundle where further damage is a concern. We recommend these tubes be isolated from the system
at this time. Tubes marked for Nominal Dents require no corrective time.
We recommend tubes indicating OD Pits of 60% or more be isolated from the system. Tubes
indicating OD Pits of less than 60% require no corrective action at the present time.
However, the damage mechanism and growth rate are unknown. This damage should be monitored
for growth.
Tubes marked as Previously Plugged, had been plugged prior to this inspection.
Tubes marked as Restricted contained defects, or foreign material which prevented the probe
from passing. The condition of these tubes at and beyond the obstruction remains unknown.
SUMMARY:
If you should have any questions concerning this report, or if we may be of further
assistance, please feel free to call upon us.
DATA SHEET
LOCATION: COMPANY
05/15/2000 05/16/2000
62.0
58.9 OD PIT 40% - 59%
55.8 05/15/2000
52.7 PREVIOUSLY PLUGGED
49.6
05/15/2000
46.5
Number of Defects
CALIBRATION PAGE
DIFF
ABS
ABS DIFF
HEAT EXCHANGER SECTION
S/N 17-111-0
DIFF
ABS
ABS DIFF
NO SIGNIFICANT DEFECTS
HEAT EXCHANGER SECTION
S/N 17-111-0
DIFF
ABS
ABS DIFF
S/N 17-111-0
DIFF
ABS
ABS DIFF
S/N 17-111-0
DIFF
ABS
ABS DIFF
DENT, NOMINAL
HEAT EXCHANGER SECTION
S/N 17-111-0
DIFF
ABS
ABS DIFF
S/N 17-111-0
DIFF
ABS
ABS DIFF
S/N 17-111-0
DIFF
ABS
ABS DIFF
DENT, NOMINAL
HEAT EXCHANGER SECTION
S/N 17-111-0
DIFF
ABS
ABS DIFF
DENT, EXCESSIVE
HEAT EXCHANGER SECTION
S/N 17-111-0
DIFF
ABS
ABS DIFF
A strip chart recording of each calibration reference standard used for the
inspection has been included in this report. Each artificial discontinuity
has been identified on the strip chart recording.
EXPLANATION OF ABBREVIATIONS
B .............. Bay
S .............. Support