ION 6200 RMD Retrofit Instructions

For further information, contact your The ION 6200 Remote Modular Display (RMD) is supplied separately as an addi-
Power Measurement representative
or Technical Services at one of the
tion to an existing ION 6200 TRAN meter.
following locations:

World Wide Web DANGER: Installation and maintenance of ION meters and meter options should only be
www.pwrm.com performed by qualified personnel that have appropriate training and experience with high
voltage/current devices. In the ION 6200 Install and Basic Setup Instructions, refer to
E-Mail Installation Considerations, and the Danger, Warning, and Limitation of Liability notices.
support@pwrm.com

Worldwide Headquarters
POWER MEASUREMENT LTD.
Location & Mounting
2195 Keating Cross Road The RMD should be mounted in a dry location free from dirt and corrosive vapors.
Saanichton, BC Once installed, no cleaning of the device is necessary. (When the RMD unit is
Canada V8M 2A5 mounted flush to a panel, then the front side meets type 4, 4x and 5 according to
Tel: 1-250-652-7101 NEMA standards 1-10-1979 and 5-25-1988).
Fax: 1-250-652-0411
RMD Dimensions
Europe
POWER MEASUREMENT EUROPE
110 mm 25 mm 86 mm
Bayreuther Str. 6 (4.30”) (.99”) (3.37”)

D-91301 Forchheim
Germany
Tel: 49-9191-7005-25
Fax: 49-9191-7005-20 86 mm
110 mm (3.37”)
(4.30”)
Asia & Pacific
POWER MEASUREMENT AUSTRALIA
Suite 1B, 5 Mumford Place
Balcatta
Western Australia 6021
Tel: 61-89-345-3866
Fax: 61-89-345-3899 Mounting the RMD in a DIN or ANSI Cutout
The RMD can be mounted in either a standard ANSI 4” or DIN 96 cutout.
© 2001 Power Measurement Ltd.
All rights reserved
Printed in Canada ANSI 4” DIN 96
Revision Date: Oct. 29, 2001
70050-0146-00 3 3/8” screws fit in corners;
holes not required
3/16” diameter
4” diameter

screw &
washer

3 3/8”

mounting
surface 92 mm x 92 mm

70050-0146-00 1/3
Mounting the RMD on a Flat Panel Oct. 29, 2001

To mount the RMD in an ANSI or DIN cutout:


1. Fit the RMD into the cutout.
2. Insert each screw in a drilled hole near the corners of the mounting surface (no
drilled holes required in a DIN 96 cutout).
3. Thread each screw in its corresponding metal insert located on the four corners
of the RMD backside.
4. With a #2 Phillips screwdriver, tighten the screws to 1.35Nm or 1 ft • Lbf
(maximum).

Mounting the RMD on a Flat Panel


With only 5 small holes, the RMD can be mounted on a flat panel. The hole pattern
required to mount the RMD to a flat panel is shown on the diagram below. This
diagram shows the hole pattern in actual size, and can be used as a template for
drilling the holes.

85.7 mm
(3 3/8”)

42.9 mm
(1 11/16”)

42.9 mm
(1 11/16”)

85.7 mm
(3 3/8”)

Min. 15.9 mm diameter 4.8 - 6.4 mm diameter


(5/8”) (3/16” - 1/4”)

2/3 70050-0146-00
Oct. 29, 2001 Connecting the Remote Modular Display

Connecting the Remote Modular Display


The RMD connects to the TRAN with a 26 gauge 6 conductor RJ11-type cable. The
cable connects between the RJ11 socket on the backside of the RMD, and the RJ11
socket on the side of the TRAN.

CAUTION: Only use the supplied cable to connect the remote display unit.

RJ11 port on the RMD

RJ11 connector

RJ11 port on the TRAN

RJ11 connector

To connect the RMD and the TRAN meter:


1. Slide the RJ11 connector into the RJ11 port at the back of the RMD (the RJ11
connector locking tab faces outwards).
2. Thread the free end of the cable through the recessed channel.

Cable Path

3. Take the free end of the cable and slide its RJ11 connector into the RJ11 port on
the side of the TRAN (the RJ11 connector locking tab faces outwards).

70050-0146-00 3/3