You are on page 1of 19

International Journal of Air-Conditioning and Refrigeration

Vol. 26, No. 4 (2018) 1850030 (19 pages)


© World Scienti¯c Publishing Company
DOI: 10.1142/S201013251850030X

Thermal Zoning Based on Design Cooling Loads:


Methodology and Simulation Case Study
for a DOAS with Local Recirculating Units

Mridul Sarkar
by WSPC on 09/10/18. Re-use and distribution is strictly not permitted, except for Open Access articles.

Integrated Environmental Solutions India Pvt. Ltd


Pune-411021, India
mridul.sarkar@iesve.com; mridul.rns@gmail.com

Received 18 May 2018


Int. J. Air-Cond. Ref. Downloaded from www.worldscientific.com

Accepted 19 July 2018


Published 30 August 2018

A framework for creating thermal zones in a building for e®ective and e±cient heating ventilation
and air conditioning (HVAC) system design is introduced here. This method is based on simple
\sort and eliminate" schemes and requires design cooling loads of conditioned spaces obtained
from load calculation tools as primary input. The developed methodology is applied for creating
thermal zones, determining corresponding supply conditions and ascertaining sizing of a dedicated
outdoor air system (DOAS) with local recirculating units. A simulation study on a prototype-
building model shows that a DOAS coupled with zoned recirculating systems that serve distinct
thermal zones in a building (zoned model) perform comparatively better in controlling both space
temperatures and humidity without signi¯cantly compromising HVAC energy and chiller loads
than un-zoned HVAC systems serving the whole building as a single thermal block (un-zoned
model). The consistency in the performance of zoned HVAC systems is veri¯ed by applying
three di®erent simulation weather ¯les for New Delhi. Better performance along with logical
and computational simplicity makes this design procedure a good alternative to traditional
methodologies.

Keywords: Thermal zone; DOAS; weather; cooling loads; energy.

Nomenclature h : Speci¯c enthalpy (kJ/kg)


hfg : Speci¯c latent heat of vaporization (kJ/kg)
Symbols l0 : Speci¯c latent heat of vaporization at T0 ¼ 273:15 K
ADP : Apparatus dew point temperature (  C) (2501 kJ/kg)
BF : Bypass factor LL : Latent load (kW)
cpa : Speci¯c heat capacity of dry air ( 1:006 kJ/kg-K) m : Slope of RSHF (or SHF) line
cpg : Speci¯c heat capacity of dry water vapor P : Saturation vapor pressure (kPa)
( 1:86 kJ/kg-K) Pt : Ambient pressure (kPa)
cpm : Speci¯c heat capacity of moist air ( 1:023 kJ/kg-K) q : Heat load (kW)
Cplv : Di®erence of speci¯c heats of water in liquid and R : Gas constant of water vapor (0.4618 kJ/kg-K)
vapor states ( 2:326 kJ/kg-K) SL : Sensible Load (kW)
FA : Fresh air °ow rate (m 3 /s) t : Temperature (  C)

1850030-1
M. Sarkar

T : Absolute Temperature (K) modeling analyses are more focused on geometrical


V : Volume of room (m 3 Þ aspects. As per ASHRAE std. 90.1, °oor plates with
V_ : Air °ow rate (m 3 /s) unknown room partitioning layouts can be divided
into core and perimeter zones for creating early-stage
Greek symbols models.5 In recent years, researchers have introduced
many computational methodologies that can be
 : Ratio of molecular mass of water vapor and dry air (0.622)
 : Density of air (1.2 kg/m 3 )
incorporated with building simulation tools for cre-
! : Humidity ratio (kg moisture/kg DA) ating multi-zoned building models from basic archi-
tectural drawings6 or complex un-zoned models.7
These methodologies are extended for preliminary
Subscripts analyses for urban scale models, too.8 Researchers
adp-i : Supply ADP condition for space i have reported signi¯cant variations in simulation
by WSPC on 09/10/18. Re-use and distribution is strictly not permitted, except for Open Access articles.

adp-TZ : Supply ADP condition for space group/zone energy and loads with actual architectural plans and
chk-i : Resultant parameter for space i at zone supply ASHRAE 90.1 compliant zoning scheme.9
conditions
During detailed design stage, spatial complexity
d : Dew point condition
design : Design supply condition in building layouts may impose some complications
d-i : Supply dew point condition for space i for comprehensive modeling and simulation. For
Int. J. Air-Cond. Ref. Downloaded from www.worldscientific.com

d-TZ : Supply dew point condition for zone/space group simplifying thermal simulations and HVAC con-
GSHF : Grand sensible heat factor line trols, multiple spaces are combined into a single
outlet : Condenser outlet of WAHP zone based on space application and load pro¯les.10
reheat : Supply air reheat
rev-i : Revised parameter for space i
Design guidelines also suggest combining spaces into
s-i : Supply condition required for space i a single thermal zone based on thermal settings11
s-TZ : Supply condition required for thermal zone/space group and exterior exposures.5 Sources state that the
set-i : Design set point of space i general methodology for delegating spaces into ap-
set-TZ : Set point of thermal zone/space group propriate thermal zones is more subjective in nature
and depends mainly on the judgment and experience
of designers.12 The e®ect of thermal zoning on the
1. Introduction overall energy consumption of HVAC systems is also
It is estimated that by 2050 the world population will explored in a literature source.13
increase by more than 30% of the present value and Despite being comprehensive, the methodologies
reach 9.7 billion,1 which is a major concern because this for thermal zoning neither address the issues related
will create a huge burden on the available energy to HVAC design nor suggest any systematic proce-
resources. As per studies,2 30–40% of world's energy dure to link thermal zoning and HVAC system
demand is from the present building stock, which is design right from the initial stages. As per conven-
responsible for 25–35% of global CO2 emissions and tional methodology, the design air°ow rate depends
projected to increase in the coming future. Buildings on space sensible load and temperature di®erence
are multi-zoned entities that have varied and complex between supply and room set points,14,15 whereas
usage, occupancy and application patterns through- the space relative humidity (RH) depends on supply
out. That is why a single de¯nition or title cannot fully dew point temperature (DPT) and space latent
de¯ne a building. As per CBECS database, approxi- load. A distinction between these sensible and latent
mately 40% of building's energy consumption is due to loads is very important for HVAC system design
heating ventilation and air conditioning (HVAC) sys- and equipment selection.14 However, most of the
tems.3 Therefore, it is imperative that design and op- conventional software tools do not explicitly explore
eration of building HVAC systems should be e±cient or de¯ne the connection between thermal zoning
to reduce energy wastage and provide comfortable and required system supply conditions, even though
dwelling environments for occupants. thermal zoning directly a®ects the performance
Modeling multi-zoned buildings is not a new con- of HVAC systems in maintaining indoor thermal
cept. Traditionally, building simulation tools are conditions.
implemented for multi-zoned thermal models.4 Since, The present work aims towards bridging this gap
room-partitioning layout for a °oor plan is not en- by proposing a method to link thermal zoning and
tirely de¯ned during the schematic design phase, HVAC system design in buildings based on spatial

1850030-2
Thermal Zoning Based on Design Cooling Loads

cooling loads and exploring its implications on zone. In a space, the main thermal loads are divided
resulting zone conditions. The proposed zoning into sensible and latent parts. To o®set sensible
methodology is applied for designing a dedicated load, temperature of process air needs to be reduced,
outdoor air system (DOAS) with local recirculating whereas moisture condensation is required to o®set
systems. The latter part of this paper will be dedi- latent load. The ratio of the sensible to total load of
cated to a simulation case study for a prototype- a space is called the room sensible heat factor
building model located in New Delhi, India. The (RSHF),15 mathematically written by Eq. (1):
primary objective of this study is to perform a SLi
comparative assessment of HVAC systems with and RSHFi ¼ : ð1Þ
SLi þ LLi
without thermal zoning considerations with three
di®erent simulation weather ¯les of New Delhi. An air conditioning process can be plotted on a
psychrometric chart by joining the supply and space
conditions by a straight line. This line is the RSHF
by WSPC on 09/10/18. Re-use and distribution is strictly not permitted, except for Open Access articles.

2. Air Conditioning of Thermal Zones line and its slope is given by


 
Primary goal of any air conditioning system is to cpm 1  RSHFi !  !s-i
maintain indoor conditions that are comfortable and mi ¼ ¼ set-i : ð2Þ
hfg RSHFi tset-i  ts-i
thermally acceptable for occupants. For this, it is
Int. J. Air-Cond. Ref. Downloaded from www.worldscientific.com

important to identify the key thermodynamic If either the humidity or supply temperature is
factors a®ecting the conditions inside a space. a±xed, the above equation allows calculation of
Available literature source presents the general other supply parameters. The minimum limit on the
methodology for conditioning a single space based apparatus condition depends on the type and char-
on its sensible and latent loads.15 However, in acteristics of the heat exchanger (coil), refrigerant
practical applications, a system is utilized for con- supply temperature from main cooling plant and
ditioning a whole zone comprising various spaces thermal properties of the supplied refrigerant °uid.
that may have di®erent applications. Hence, it is generally assumed as such for HVAC
A thermal zone is a single space or a group of system design. The required supply °ow rate for
spaces that have similar thermal load character- conditioning a space is determined by Eq. (3) as
istics, such that a HVAC system may control and SLi
maintain approximate levels of prescribed condi- V_i ¼ : ð3Þ
  cpm  ðtset-i  ts-i Þ
tions inside. In a building, there are di®erent types
of spaces that have varied load variation and oper- Equations (4a) and (4b) give the corresponding
ational patterns. Identifying these spaces and speci¯c enthalpy of the supply air and return air for
grouping them into clusters based on similar cooling each space, as
load characteristics will allow meeting space-condi-
hset-i ¼ cpa  tset-i þ !set-i  ð2501 þ cpg  tset-i Þ ;
tioning requirements with limited number of ther-
mal equipment. ð4aÞ
In the present work, two terms namely \sample hs-i ¼ cpa  ts-i þ !s-i  ð2501 þ cpg  ts-i Þ : ð4bÞ
space group" and \thermal zone" are used fre-
quently. A sample space group is de¯ned as a set of When individual spaces form a thermal zone, the
spaces that are sorted out after satisfying certain overall sensible heat factor (SHF) is given by the
conditions and is under assessment for further divi- weighted average of constituting space RSHF as
sion into multiple clusters called thermal zones. X
k
Hence, all the equations shown in the later sections V_i  ðhset-i  hs-i Þ  RSHFi
are equally applicable for any sample space group or i¼1
SHFTZ ¼ ; kn
thermal zone. X
k
V_i  ðhset-i  hs-i Þ
i¼1

2.1. Methodology ð5Þ


In this section, the general design methodology for where `k' is the number of spaces considered in a
conditioning a single space is extended to a thermal zone (or sample space group) and `n' is the total

1850030-3
M. Sarkar

number of conditioned spaces in the building, whose deviation (SDTZ Þ17 as


corresponding systems are served by a common vffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
" #
u X
cooling plant and same supplied refrigerant °uid. u k V_rev-i  ðhseti  hs-TZ Þ
u
The overall zone set point is given by volume- u
u k i¼1  ðRSHFi  SHFTZ Þ 2
weighted average of space set points as SDTZ ¼ u uk  1 
t X k
Xk
V_rev-i  ðhset-i  hs-TZ Þ
Vi  tset-i
i¼1
i¼1
tset-TZ ¼ ; ð6Þ ð12Þ
Xk
Vi
and relative standard deviation (RSD) in % is
i¼1
given by
X
k
Vi  !set-i SDTZ
by WSPC on 09/10/18. Re-use and distribution is strictly not permitted, except for Open Access articles.

i¼1 RSD ¼  100% : ð13Þ


!set-TZ ¼ : ð7Þ SHFTZ
X
k
Vi The nature of load variation in a zone is expressed
i¼1
mathematically by the skewness coe±cient (SC).
The absolute humidity set point of a space is also
Int. J. Air-Cond. Ref. Downloaded from www.worldscientific.com

It is given by Eq. (14) as


written in terms of its RH set point as " #
  RHset-i  Pset-i Xk V_rev-i  ðhset-i  hs-TZ Þ
!set-i ¼ : ð8Þ
Pt  RHset-i  Pset-i  ðRSHFi  SHFTZ Þ 3
i¼1
The saturation vapor pressure at room set point SC ¼ : ð14Þ
Xk
temperature (Pset-i Þ is given by Eq. (9) as16 ðSDTZ Þ 3  ½V_rev-i  ðhset-i  hs-TZ Þ
"   Cplv  # i¼1
Tset-i  R
Pset-i ¼ PT0  In statistics, skewness is the measure of asymmetry
T0
in data distribution of a sample group. In the pres-
   
l0 þ Cplv  T0 1 1 ent context, the concerned data is space-cooling
 exp   : load. Positive skewness implies that the overall
R T0 Tset-i
group SHF lies near the minimum RSHF value.
ð9Þ
Contrary to this, negative skewness implies that the
Here, T0 is the reference temperature of 273.15 K SHF lies in closer proximity to the maximum RSHF
and saturation vapor pressure at T0 (PT 0 Þ is value in the group. Zero skewness implies a sym-
0.611 kPa. Similar to Eq. (1), the slope of zone SHF metric distribution of cooling loads across the con-
line is given by stituent spaces.
  In this paper, maximum permissible variations of
cpm 1  SHFTZ !  !s-TZ
mTZ ¼ ¼ set-TZ : ð10Þ  0:5  C and  5% in design temperature and RH
hfg SHFTZ tset-TZ  ts-TZ set points, respectively, are assumed for the spaces
The revised supply °ow rate of a space in terms of in a valid thermal zone. For the prescribed throt-
zone supply temperature for a constituting space of tling limits, a conservative RSD limit of 5% is con-
the zone is given by sidered here.
SLi
V_rev-i ¼ ; i 2 TZ : ð11Þ
  cpm  ðtset-i  ts-TZ Þ 2.2. Sample space group creation
(`sort' scheme)
It should be noted that supplying air at the deter-
mined zone supply conditions might not o®set all of An air conditioning system serving a particular
the thermal loads inside every space in the zone. thermal zone is sized based on the peak zone cooling
However, with proper thermal zoning, these varia- load or the block load, which is sum of all the cooling
tions can be kept within acceptable limits. The net loads of constituent spaces at a speci¯c time. Since,
variation between zone SHF and RSHF of consti- the variations of thermal loads are dynamic in na-
tuting spaces is given by the weighted standard ture, occurrence of the peak zone load and peak

1850030-4
Thermal Zoning Based on Design Cooling Loads

space loads may not coincide with each other. This criterion can be applied as the second level of
Hence, creation of sample space groups requires a scrutiny.
scrutiny of constituting space application and load . Those spaces whose peak cooling load occurs in
characteristics. the same season (months in which cooling is
To be sorted into a sample group, respective dominant) can be included into a group. This is
spaces in a building should satisfy certain assess- the third level of assessment. As per ASHRAE std.
ment criteria. Technical spaces and other areas with 169,18 summer or cooling season extends from
special air conditioning requirements (e.g., kitchens, April to September and October to March in
natatoriums, etc.) or that are required to be zoned northern and southern hemisphere, respectively.
separately from other comfort-conditioned spaces . The ¯nal criteria is to check the time of the peak
should be exempted from application of these cri- load occurrence of individual spaces. Spaces whose
teria. Four di®erent assessment levels are identi¯ed peak load occurs within a maximum spread of 3 h
by WSPC on 09/10/18. Re-use and distribution is strictly not permitted, except for Open Access articles.

here as listed below: with respect to each other can be included to-
gether in a group. This criterion allows sorting
. All spaces whose design thermostat and RH set
only spaces that do not have considerable varia-
points do not di®er more than prescribed maxi-
tion in space load characteristics.
mum limits can be sorted into a group. Recom-
mendation of 4  C as the maximum di®erence in These criteria are the main features of the `sorting'
Int. J. Air-Cond. Ref. Downloaded from www.worldscientific.com

thermostat set points11 and a maximum di®erence scheme. Figure 1 summarizes the sorting criteria
of 10% in RH set points are acceptable for spaces applied for creating sample space groups.
in a sample group. It should be noted that in this
work, satisfactory space RH range is shown to be
achievable entirely by thermal zoning and no 2.3. Sample space group to thermal zone
separate RH controlling intervention or controls translation (`eliminate' scheme)
are assumed to be present in the primary air The three parameters required for creating thermal
conditioning unit. zones from sample space groups are given by
. As per ASHRAE std. 90.1 Appendix G5, spaces Eqs. (12)–(14). The weighted standard deviation
whose weekly operation schedules do not di®er by provides an indication whether a single HVAC unit
more than 40 equivalent full-load hours (EFLH) can maintain thermal conditions inside the constit-
can be grouped together in a single HVAC zone. uent spaces of a group. If relative standard deviation

Fig. 1. Criteria for sorting scheme to create sample space groups.

1850030-5
M. Sarkar

exceeds the permissible limit, it implies that the 3. Air System Consideration
design load characteristics between spaces in the
A DOAS splits ventilation loads from primary air
considered group lack su±cient coherence and cor-
conditioning unit. Separate treatment of outdoor air
responding skewness coe±cient is checked. If skew-
by DOAS unit not only reduces the size of main
ness > 0, the contribution from the space with
supply duct and supply unit, but also improves in-
highest RSHF value is least towards the overall
group SHF and converse is true when skewness < 0. door air quality (IAQ) by decoupling dehumidi¯ca-
Consequently, the current group is modi¯ed by tion and sensible loads of outdoor air. Ideally, a
eliminating a single space with extreme RSHF value DOAS should be designed to handle entire space
based on the skewness coe±cient and equations are latent load along with some portion of sensible
reapplied. This procedure is iterated until the re- load.19–21 However, limitations on allowable outdoor
quired level of RSD is achieved. The whole proce- air°ow rates and minimum supply DPTs act as de-
terring factors in achieving this objective entirely.
by WSPC on 09/10/18. Re-use and distribution is strictly not permitted, except for Open Access articles.

dure is repeated for the new space group composed


of the eliminated spaces, until every space in the Treated fresh air through a DOAS unit is either
sample group is accounted and placed into a thermal supplied directly to the space or to main air-recir-
zone or forms a thermal zone by itself. If thermal culating unit, the former being more e±cient.22,23
load in a particular space varies considerably from Treatment of outdoor air in a DOAS unit can be
Int. J. Air-Cond. Ref. Downloaded from www.worldscientific.com

the remaining spaces in the group, it forms a ther- done by integrating many ancillary components like
mal zone by itself after iterations. Figure 2 shows the heat recovery devices, active desiccant wheels, heat
°owchart depicting the eliminate scheme. pipe coupled dehumidi¯er systems, etc. In the

Fig. 2. Flowchart depicting eliminate scheme for creating thermal zones from a sample space groups.

1850030-6
Thermal Zoning Based on Design Cooling Loads

present work, a wrap-around heat pipe (WAHP) l0 þ Cplv T0


based dehumidi¯er system is considered as the main ¼ :
R
outdoor tempering unit supplying ventilation air
directly to the spaces. Many researchers have The sensible and latent loads met by DOAS unit
investigated the application of WAHP in HVAC depend on the ventilation rate (FA) for each of the
systems and studied its implications on the overall spaces and given by
system performance.24,25 SLiDOAS ¼   FAi  cpm ðtset-i  ts-iDOAS Þ ; ð18Þ
In a WAHP enhanced dehumidi¯er system, the
supply dry bulb and DPT of air are controlled by LLiDOAS ¼   FAi  hfg ð!set-i  !s-iDOAS Þ : ð19Þ
modulating condenser and dehumidi¯er coil outlet If the loads mitigated by DOAS unit are greater
temperatures, respectively. A WAHP precools in- than the space loads, the design supply temperature
coming air through its evaporator, thereby reducing and humidity ratio of the DOAS unit need to be
by WSPC on 09/10/18. Re-use and distribution is strictly not permitted, except for Open Access articles.

its dew point depression (DPD) before passing it increased. The remaining loads to be met by local
through the dehumidi¯er coil. Due to this, air exits recirculating units are given by
the coil at almost saturated condition. Hence,
without loss of generality, the supply DPT is SLiAHU ¼ SLi  SLiDOAS ; ð20Þ
approximated by the coil exit temperature. The LLiAHU ¼ LLi  LLiDOAS : ð21Þ
Int. J. Air-Cond. Ref. Downloaded from www.worldscientific.com

condenser outlet temperature is maintained via


electrically operated solenoid valves that can control The RSHF of any space due the loads o®set by a
the °ow of refrigerant through heat pipe tubes based local recirculating unit is given by
on the required condenser outlet temperature.26 SLiAHU
RSHFiAHU ¼ : ð22Þ
SLiAHU þ LLiAHU
4. Thermal Zoning for DOAS with Local and slope of this line:
Recirculating Systems  
cpm 1  RSHFiAHU
4.1. Optimum supply conditions miAHU ¼ : ð23Þ
hfg RSHFiAHU
at design loads
On a psychrometric chart, the line connecting coil
The supply temperature from DOAS unit is as-
entering and leaving conditions is called as grand
sumed the same as condenser outlet temperature of
sensible heat factor (GSHF)15 line. Since, DOAS
WAHP system. Hence:
unit separately treats and supplies ventilation air
ts-iDOAS ¼ toutlet : ð15Þ directly to the spaces, entering conditions of air to
the recirculating AHU coil is the same as return air
The supply DPT of DOAS unit is an assumed design
condition (or space set point). The slope of this line
value. Hence:
is given by
td-iDOAS ¼ DPTdesign : ð16Þ !set-i  !s-iGSHF
miGSHF ¼ : ð24Þ
Supply humidity ratio corresponding to the supply tset-i  ts-iGSHF
DPT27 of the DOAS unit can be determined by At minimum design ADP of recirculating coil, the
applying Eq. (17): supply temperature of recirculating unit for each

x
!s-iDOAS ¼ !s-TZDOAS ¼  ; ð17Þ space is given in terms of coil bypass factor (BF) as:
1x
ts-iGSHF ¼ ð1  BFÞ  ADPmin-design þ BF  tset-i :
where
    ð25Þ
P T0 1 1
x¼ exp  and supply humidity ratio:
Pt T0 td-iDOAS þ T0

!s-iGSHF ¼ ð1  BFÞ  !ADPmin-design þ BF  !set-i :
 f þ A  ðtd-iDOAS þ 2  T0 Þg ;
ð26Þ
 
Cplv Putting Eqs. (25) and (26) into Eq. (24), the mini-
A¼  ;
2R mum slope of design GSHF line for each space is

1850030-7
M. Sarkar

determined and compared with the slope of space T0 solve for Tadp , successive roots are determined
RSHF line given by Eq. (23). If the slope of design iteratively until convergence is achieved. The suc-
GHSF line is greater than or equal to the slope of cessive root for Eq. (30) is determined by
RSHF line, the required supply condition of recir-
culating unit can be controlled by modulating gðTadpj Þ
Tadpjþ1 ¼ Tadpj  : ð31Þ
refrigerant °ow through the coil. However, if RSHF g 0 ðTadpj Þ
line is steeper than GSHF line, minimum design
ADP of the coil is not su±cient to meet remaining The design DPT of the space can be considered
space latent load and additional provisions like re- as the initial guess (Tadp0 Þ for obtaining successive
heat or bypass control are required to meet the solutions. DPT can be determined in terms of hu-
loads. Based on this comparison, the sample space midity ratio27 by Eq. (32) as
group are sorted into two sub-groups and corre- ð  kT0 Þ
td ¼
by WSPC on 09/10/18. Re-use and distribution is strictly not permitted, except for Open Access articles.

sponding thermal zoning methodologies are applied.


2A
pffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
4.1.1. Procedure a ð  kT0 Þ 2 þ 4AðAT 02 þ T0 Þ
þ  T0 : ð32Þ
In this case: 2A
miAHU  miGSHF : ð27Þ After determining the supply ADP by numerical
Int. J. Air-Cond. Ref. Downloaded from www.worldscientific.com

iteration, required supply temperature and humidi-


The RSHF line intersects the saturation curve at a
ty ratio are obtained by
temperature higher than or equal to the lowest de-
sign ADP of AHU coil. Slope of the RSHF line given ts-iAHU ¼ ð1  BFÞ  tadp-iAHU þ BF  tset-i ; ð33Þ
by Eq. (23) can be written as !s-iAHU ¼ ð1  BFÞ  !adp-iAHU þ BF  !set-i ; ð34Þ
 
cpm 1  RSHFiAHU
miAHU ¼ where
hfg RSHFiAHU
!set-i  !adp-iAHU tadp-iAHU ¼ Tadp-iAHU  T0 :
¼ : ð28Þ
Tset-i  Tadp-iAHU The required supply °ow rate by the AHU is
In Eq. (28), both the supply ADP and humidity given by
ratio are unknown. The ADP (in Kelvin) can be SLiAHU
V_iAHU ¼ : ð35Þ
expressed in terms of humidity ratio through a   cpm  ðtset-i  ts-iAHU Þ
quadratic equation 27 as per Eq. (29):
The SHF of the sample space group served by AHU
A  ðTadp-iAHU Þ 2 þ ð  kT0 Þ  Tadp-iAHU and corresponding slope of SHF line are obtained by
 ðAT 02 þ T0 Þ ¼ 0 ; ð29Þ applying Eqs. (5) and (10), respectively. Supply
ADP temperature (in Kelvin) of the AHU serving an
where entire zone is determined by numerically solving
  Eq. (36) below:
Cplv
A¼  ;
2R A  ðTadp-TZAHU Þ 2 þ ð  kT0 Þ  Tadp-TZAHU
   
Pt !adp-iAHU  ðAT 02 þ T0 Þ ¼ 0 ð36Þ
k ¼ ln þ ln ;
P T0  þ !adp-iAHU
where
l0 þ Cplv T0
¼ : !adp-TZAHU ¼ !set-TZ  mTZAHU
R
 ðTset-TZ  Tadp-TZAHU Þ : ð37Þ
One cannot solve Eq. (29) explicitly by applying
conventional method and hence, it should be solved
Similar to the methodology applied for individual
numerically. To solve this, Newton–Raphson method
space, ADP of the coil supplying to space group is
can be applied. The general form of Eq. (29) is
determined by applying Newton–Raphson method.
gðTadp Þ ¼ A  ðTadp Þ 2 þ ð  kT0 Þ  Tadp The initial guess in this case is the prescribed
DPT of the space group determined by substituting
ðAT 02 þ T0 Þ : ð30Þ corresponding parameters in Eqs. (7) and (32).

1850030-8
Thermal Zoning Based on Design Cooling Loads

The required supply temperature and humidity The set points used in Eqs. (42) and (43) are
ratio of sample space sub-group are determined by obtained from Eqs. (6) to (7). Equation (11) is ap-
replacing corresponding parameters in Eqs. (33) plied in a similar way as before to determine revised
and (34), respectively. The revised space °ow rate supply °ow rate for each space in the space group
required for each space in the group is obtained by and elimination scheme is applied to create thermal
applying Eq. (11) and required thermal zones are zones. Equation (38) applied before for procedure a
created by applying the elimination scheme shown gives the resultant humidity ratio of any space in a
before. Equation (43) below gives the resultant hu- thermal zone.
midity ratio of any space in the zone: Section 4.1 concludes the general zoning meth-
LLiDOAS þ LLiAHU odology of a DOAS with local recirculating units for
!i-chk ¼ common ventilation and primary supply, respec-
  hfg  ðFAi þ V_i-rev Þ
AHU
tively. Based on the design space load character-
ð!s-TZDOAS  FAi þ !s-TZAHU  V_i-revAHU Þ
by WSPC on 09/10/18. Re-use and distribution is strictly not permitted, except for Open Access articles.

istics, speci¯c procedures shown above can be aptly


þ :
ðFAi þ V_i-rev Þ
AHU
applied and optimum supply conditions and air°ow
rates for each thermal zone can be determined
ð38Þ
accordingly. Subsequently, cooling coil capacities
4.1.2. Procedure b required for each thermal zone is determined by
Int. J. Air-Cond. Ref. Downloaded from www.worldscientific.com

considering these supply conditions and design zone


This procedure is applicable when condition given air°ow rates, which is followed by sizing of the
by Eq. (27) is not valid and cooling plant. The proceeding section discusses the
miAHU > miGSHF : ð39Þ basic controlling methodology for the zoned HVAC
systems considered in this work.
In this case, the ADP of recirculating AHU serving
individual spaces of an entire thermal zone is con-
sidered equal to the minimum design (min-design) 4.2. Consideration at part loads
coil ADP: At part load conditions, variations in space cooling
tadp-iAHU ¼ tadp-TZAHU ¼ ADPmin-design : ð40Þ loads require air conditioning systems to respond in
appropriate manner to maintain comfortable con-
The corresponding humidity ratio at this saturation ditions. Dehumidi¯cation performance of HVAC
temperature is determined by substituting the systems vary with the variations in space cooling
minimum design coil ADP into Eq. (17). The supply loads. Temperature reset strategy can control the
humidity ratio for each space is given by Eq. (34). HVAC supply temperatures in response to the space
The required supply temperature for each space will cooling loads. However, this may lead to reduced
be higher than the AHU coil outlet temperature and dehumidi¯cation and higher indoor humidity levels.
given in terms of the slope of space RSHF line as In this regard, a constant air volume system (CAV)
!set-i  !s-iAHU that allows modulation of supply temperature, while
ts-iAHU ¼ tset-i  ; ð41Þ
miAHU maintaining constant air°ow rate, introduces
where slope of RSHF line is given by Eq. (28). The greater challenge in controlling dehumidi¯cation at
required supply °ow rate for each space is deter- part load conditions.28
mined by applying Eq. (35). The SHF of the sample Literature study suggests that a variable air
space group served by AHU and corresponding slope volume system (VAV) supplying at a speci¯c design
of SHF line are obtained by applying Eqs. (5) temperature can maintain both space temperature
and (10), respectively. The supply humidity ratio for and humidity levels within acceptable limits by
the space group is given as varying supply air°ow rates and operating terminal
reheat coils, whenever needed.29 Figure 3 depicts
!s-TZAHU ¼ ð1  BFÞ  !adp-TZAHU
ð42Þ typical RH contours of a zone served by a VAV
þBF  !set-TZ system at part load conditions. This system supplies
and required zone supply temperature: air at a constant DPT determined at design sensible
!set-TZ  !s-TZAHU and latent loads and prescribed space set point
ts-TZAHU ¼ tset-TZ  : ð43Þ (in this case 50% RH and 24  C). Here, space air°ow
mTZAHU rates are modulated to maintain the required

1850030-9
M. Sarkar
by WSPC on 09/10/18. Re-use and distribution is strictly not permitted, except for Open Access articles.
Int. J. Air-Cond. Ref. Downloaded from www.worldscientific.com

Fig. 3. Zone RH variation at part loads for VAV systems supplying air at design conditions.

temperature set point (24  C). The ¯gure shows that thermal zoning on operational characteristics of a
over a wide range of variations in sensible and latent DOAS with local VAV recirculating units. Varia-
loads, space RH levels stay between 40% and 60% tions in space temperature and RH are the two basic
during air conditioning periods. This is the optimum criteria considered for the performance of zoned
indoor RH range as per literature recom- HVAC system in the simulation case study. The
mendation for healthy and comfortable dwelling acceptable range of thermal conditions inside a zone
environments.30 is ascertained by the maximum and minimum limits
Extending the argument from a single space to a on the design thermostat and RH set points based
multi-space zone, the same design strategy ensures on the space application and comfort criteria for
similar levels of space RH, when compounding with occupancy.
a DOAS for better dehumidi¯cation performance at
part loads. Hence, under the purview of this system
con¯guration and operational strategy, the thermal 5. Simulation Case Study
zoning scheme corresponding to design cooling loads This section presents an energy performance study
as per Sec. 4.1 remains valid even at part load con- of a prototype building located in New Delhi, India.
ditions. Figure 4 depicts the basic building geometry and
This design scheme predicates the controlling constituent spaces. Space typology and corre-
methodology for the zoned HVAC systems consid- sponding thermal data considered for the model are
ered here. The air°ow modulation is achieved by the summarized in Table 1. The basic energy modeling
VAV boxes for maintaining the space temperature input parameters are listed in Table 2 and opera-
between the minimum and maximum design set tional pro¯les of each space type are shown in Fig. 5.
points. Air°ow is supplied to each thermal zone at
corresponding ¯xed supply temperatures through-
out the conditioning period. Despite active RH 5.1. Load estimation
controllers in primary air systems not being con- Both internal and external sources a®ect the cooling
sidered, appropriate thermal zoning ensures com- loads of a space. Lighting, equipment, occupants,
paratively better RH control of thermal zone due to conduction, in¯ltration, solar transmission and
similar load varying characteristics of constituent delayed release of stored heat through thermal mass
spaces. The simulation case study in the proceeding are the main sources of sensible heat gain, whereas
section applies this strategy for analyzing e®ect of moisture transfer from occupants, equipment and

1850030-10
Thermal Zoning Based on Design Cooling Loads
by WSPC on 09/10/18. Re-use and distribution is strictly not permitted, except for Open Access articles.
Int. J. Air-Cond. Ref. Downloaded from www.worldscientific.com

Fig. 4. Geometry of BEM.

Table 1. Space input summary.

HVAC Occupancy Lighting Receptacle Ventilation

Occupied Occupied
Space type max. (  C) min. (  C) RH (%) Weekly EFLH m 2 /person W/m 2 W/m 2 lps/m 2

Corridor 25  0.5 20  0.5 45  10 126 — 5 0 0.3


Classroom 24  0.5 22  0.5 50  10 78 5 15 10.8 1.1
Dining 24  0.5 22  0.5 50  10 126 5 10 9 1.7
Lobby 24  0.5 22  0.5 50  10 126 3.3 14 2.7 1.1
Meeting room 24  0.5 22  0.5 50  10 49 5 14 5.4 0.8
O±ce 24  0.5 22  0.5 50  10 78 20 12 10.8 0.4
Retail 24  0.5 22  0.5 50  10 126 6.7 18 2.7 1.2
Stairs — — — — — 6 — —
Toilet — — — — — 10 — —

in¯ltration are the main sources of latent heat gain. the location from ASHRAE database are set into the
Contrary to internal loads that vary based on ap- program as main weather input and heat calculation
plication trends, external loads depend on the is done by applying ASHRAE heat balance meth-
weather conditions. Due to this, space sensible and od.32 Another way for load calculation is through
latent loads vary both diurnally and seasonally. dynamic simulation pathway. In this method, con-
IES-VE is the energy simulation and load esti- ditioned spaces are linked with a virtual HVAC
mation tool applied in the present work. VE is a system (called as main system) and weather data is
whole-building simulation tool based on ¯rst prin- accessed from a simulation weather ¯le. Running
ciple for mathematically modeling dynamic heat dynamic simulations with this setting enables the
transfer and advanced HVAC system control.31 program to determine sensible and latent loads via
There are two methods for estimating cooling loads heat balance method at realistic hourly outdoor
in IES-VE. The ¯rst method is the conventional way conditions. In the present work, simulation pathway
of load calculation by ASHRAE-LOADS module. is applied for determining space-cooling loads that
For this method, standard design DBT and WBT of are required for thermal zoning and system sizing.

1850030-11
M. Sarkar

Table 2. Input parameters for energy model.

Parameter Details

Location: New Delhi, India


Geometry: G þ 1, Mixed-use type, Total °oor area ¼ 4545 m 2
Envelope details:
External wall Insulated cavity wall sandwiched with plaster boards, U-value ¼ 0:705 W/m 2 -K
Roof Concrete deck with insulation entirely above deck and weatherproof membrane,
U-value ¼ 0:362 W/m 2 -K
Glazing Double pane window with air cavity, U-value ¼ 6:801 W/m 2 -K and SHGC ¼ 0:25.
Roof light Roof light without curb, U-value ¼ 7:72 W/m 2 -K and SHGC ¼ 0:36.
Base In¯ltration rate 0.362 lps/m 2 -facade
System control:
Primary system VAV AHU with terminal reheat coils
by WSPC on 09/10/18. Re-use and distribution is strictly not permitted, except for Open Access articles.

Primary system control Flow modulation based on zone temperature. Terminal air dampers and VFD fan for °ow
modulation. Terminal reheat coils for space temperature control when required. Start-up
period for pre-occupancy operation is 2 h. Temperature setback during unoccupied hours.
Cooling plant Chilled-water system. Higher side speci¯cations as per section G3.1.3 Appendix G, ASHRAE std.
90.1-2007 5 .
Int. J. Air-Cond. Ref. Downloaded from www.worldscientific.com

Simulation speci¯cs:
Simulation time period Summer season (April 1st to September 30th).
Simulation time-step 10 min.
Weather ¯les (1) IND New.Delhi.421820 IWEC.epw (IWEC weather data)
(2) IND New.Delhi.421820 ISHRAE.epw (ISHRAE weather data)
(3) New Delhi WA 2016.fwt (Weather Analytics historical weather data for 2016)

Simulation tool IES-VE (2015)

Fig. 5. Operating pro¯les of various space types considered in the model.

1850030-12
Thermal Zoning Based on Design Cooling Loads

5.2. Weather data the sorting criteria from Sec. 2.2, di®erent space
groups are created. From each space group, thermal
In this article, three simulation weather ¯les of
zones are generated by applying the procedure
New Delhi from di®erent sources are utilized for
proposed for DOAS with recirculating AHU. Fol-
load calculations and dynamic simulations. The ¯rst
lowing assumptions are made for the HVAC systems
two simulation weather ¯les are created, compiled
in this study:
by International Weather for Energy Calculation
(IWEC) and Indian Society of Heating, Refrigerat- . Refrigerant for cooling dehumidi¯cation process is
ing and Air-Conditioning Engineers (ISHRAE), and chilled water.
available as EnergyPlus weather data source.33 The . Design supply DPT of 12  C and condenser outlet
third weather ¯le incorporates historical data for temperature of 18  C are considered for the DOAS
year 2016 from Weather Analytics (WA) database34 sub-system.
and extracted as an .fwt ¯le through cloud-based . Coil BF of 0.1 is considered for all the recirculat-
by WSPC on 09/10/18. Re-use and distribution is strictly not permitted, except for Open Access articles.

building analytics service called IES-SCAN.35 The ing AHU.


variation of temperature and humidity data from . A minimum limit of 11  C is considered for the
the simulation weather ¯les are shown in Fig. 6. supply ADP of recirculating AHU serving thermal
From the data plot, it is observed that the extreme zones.
monthly DBT during summer season is relatively
Int. J. Air-Cond. Ref. Downloaded from www.worldscientific.com

higher in WA-2016 weather ¯le. However, IWEC


and ISHRAE weather ¯les show higher monthly 5.4. Dynamic simulations
median of humidity ratio during summer season Detailed HVAC networks with corresponding air-
than the WA-2016 weather ¯le. side and plant-side controllers are compiled in
APACHE-HVAC module of IES-VE. The HVAC
control-network and simulation weather ¯le should
5.3. Thermal zoning be linked together at APACHE-SIM interface for
Occurrence of peak cooling loads inside spaces may modeling dynamic interactions between building
vary with the weather data considered. By applying HVAC systems and outdoor climate of the location.

Fig. 6. Monthly variation of temperature and humidity data from simulation weather.

1850030-13
M. Sarkar

Table 3. Simulation test scenarios.

Scenario # Zoning Ventilation Linked weather ¯le Design supply Temp

1 Zoned DOAS (WAHP dehumidi¯er system) IND New.Delhi.421820 ISHRAE. As per zoning method
epw
1a, 1b, 1c, 1d Un-zoned Untreated direct mechanical ventilation IND New.Delhi.421820 ISHRAE. 11, 12, 13 and 14  C
epw
1e, 1f, 1g, 1h Un-zoned DOAS (WAHP dehumidi¯er system) IND New.Delhi.421820 ISHRAE. 11, 12, 13 and 14  C
epw
2 Zoned DOAS (WAHP dehumidi¯er system) IND New.Delhi.421820 IWEC.epw As per zoning method
2a, 2b, 2c, 2d Un-zoned Untreated direct mechanical ventilation IND New.Delhi.421820 IWEC.epw 11, 12, 13 and 14  C
2e, 2f, 2g, 2h Un-zoned DOAS (WAHP dehumidi¯er system) IND New.Delhi.421820 IWEC.epw 11, 12, 13 and 14  C
3 Zoned DOAS (WAHP dehumidi¯er system) New Delhi WA 2016.fwt As per zoning method
3a, 3b, 3c, 3d Un-zoned Untreated direct mechanical ventilation New Delhi WA 2016.fwt 11, 12, 13 and 14  C
by WSPC on 09/10/18. Re-use and distribution is strictly not permitted, except for Open Access articles.

3e, 3f, 3g, 3h Un-zoned DOAS (WAHP dehumidi¯er system) New Delhi WA 2016.fwt 11, 12, 13 and 14  C

Table 3 shows the HVAC system variants for this to determine optimum supply conditions and °ow
case study. Three basic types of air systems are rates of zoned HVAC systems. Figure 8(b) shows
Int. J. Air-Cond. Ref. Downloaded from www.worldscientific.com

considered for the comparative study: the hierarchical levels in the model for thermal
zoning process.
. DOAS with multiple VAV recirculating AHU
serving corresponding thermal zones.
. DOAS with a single VAV recirculating AHU
serving all the conditioned spaces by con-
sidering entire building as a single thermal block
(un-zoned systems). Design supply temperatures:
11, 12, 13 and 14  C.
. A conventional VAV recirculating AHU with di-
rect mechanical ventilation serving all the condi-
tioned spaces by considering entire building as a
single thermal block. Design supply temperatures:
11, 12, 13 and 14  C.
Figure 7 shows the schematics of these system
con¯gurations. In a test scenario, an air system (a)
network is linked with one simulation weather ¯le
at a time and simulation is ran for an entire
summer season i.e., from April to September
months. The result parameters considered for as-
sessment are:
. HVAC energy utilization intensity (EUI–
kWh/m2).
. Total chiller load (kWh/m2).
. Temperature unmet hours: Number of occupied (b)
hours when space temperatures are either
> 24:5  C (occupied maximum þ 0:5  C) or
< 21:5  C (occupied minimum – 0.5  C).
. RH unmet hours: Number of occupied hours when
(c)
space RH are either > 60% or < 40%.
Fig. 7. Schematics of HVAC system con¯gurations considered
Figure 8(a) shows the general layout of the simula- for simulation case study (a) DOAS with multiple VAV AHUs
tion work°ow adapted in this case study. The sort (zoned); (b) DOAS with a single VAV AHU (un-zoned) and (c) A
and eliminate schemes for thermal zoning is applied single VAV AHU with untreated direct ventilation (un-zoned).

1850030-14
Thermal Zoning Based on Design Cooling Loads
by WSPC on 09/10/18. Re-use and distribution is strictly not permitted, except for Open Access articles.
Int. J. Air-Cond. Ref. Downloaded from www.worldscientific.com

(a)

(b)
Fig. 8. General outline of simulation case study: (a) IES-VE application work°ow and (b) Hierarchical levels considered for thermal
zoning.

5.5. Results and discussion in unmet hours between various cases are reduced to
150 and 25, respectively, on a pro-rata basis.
Before assessing the performance of the considered
Figure 9(a) shows the temperature unmet hours
options, quantitative validation of the simulation is
¯rst con¯rmed. As per performance rating method for all the considered cases. The plot provides satis-
(PRM) from ASHRAE 90.1 Standard appendix G5, factory evidence, that the control settings and sys-
the temperature unmet hours in a validated building tem sizing methodology in of all the simulation cases
energy model (BEM) should not be greater than 300 are conformal with the basic validation criteria of
and di®erence in unmet hours between two consid- ASHRAE standard 90.1. This is valid for the system
ered models (baseline and proposed models) should types that are sized by considering a speci¯c tem-
not exceed 50. Since, only the summer season is perature di®erence between room set points and de-
considered as the simulation period in this study, the sign supply temperatures, as well as that are sized by
permissible temperature unmet hours and di®erence the thermal zoning methodology presented in Sec. 2.

1850030-15
M. Sarkar
by WSPC on 09/10/18. Re-use and distribution is strictly not permitted, except for Open Access articles.

(a)
Int. J. Air-Cond. Ref. Downloaded from www.worldscientific.com

(b)
Fig. 9. (a) Temperature unmet hours for simulation scenarios and (b) simulation energy summary for the considered scenarios.

Figure 9(b) summarizes the energy consumption corresponding simulation weather sets only vary
from various end sources considered in the model. between 5–6% and 7–9%, respectively. These per-
Energy consumption due to chillers, reheat coils, centages are subjected to change with variations in
distribution fans, chilled water distribution pump model inputs and outdoor air°ow rates supplied to
and heat rejection loop comprises the net energy the building. Nevertheless, similar types of systems
consumption due to HVAC. Energy consumed by with di®erent zoning considerations should not only
lighting and miscellaneous equipment are considered consider energy consumption but also system capa-
the same and contributes 28–30% of overall energy bility to maintain indoor environmental quality as a
consumption in all the simulation scenarios. As the primary factor for qualitative assessment.
supply temperature reduces, both chiller and reheat Figure 10 depicts the scatter plots of total chiller
energy increases, whereas distribution fan energy loads and RH unmet hours against HVAC EUIs for
decreases and vice-versa. The ¯gure shows that all the considered scenarios. Each scatter plot depicts
DOAS based VAV systems perform relatively better the performance of nine basic system con¯gurations
than conventional VAV systems with direct venti- that are sized and simulated with a speci¯c simula-
lation. Separately treating fresh air through a tion weather ¯le. The data points are clustered into
DOAS sub-system equipped with a WAHP en- three di®erent groups for qualitative characteristic
hanced dehumidi¯er module reduces the coil loads of assessment by applying K-means clustering meth-
the primary recirculating units. Despite this, the odology based on Euclidian distance metric. Similar
di®erences in total energy and HVAC energy con- to temperature unmet hours, a permissible RH
sumptions between the best and worst cases in unmet hour limit of 0–150 is considered here.

1850030-16
Thermal Zoning Based on Design Cooling Loads
by WSPC on 09/10/18. Re-use and distribution is strictly not permitted, except for Open Access articles.

Fig. 10. Scatter plots of total chiller loads and RH unmet hours versus HVAC EUIs for simulation scenarios.
Int. J. Air-Cond. Ref. Downloaded from www.worldscientific.com

The maximum percentage di®erences in HVAC This simulation case study provides su±cient
EUI and total chiller loads between zoned recircu- evidence that the thermal zoning methodology in-
lating AHU and the best performing un-zoned recir- troduced in the present work is an e®ective design
culating AHU are less than 4% and 3%, respectively, strategy, which is not only e±cient but provides
in all the considered simulation scenarios. Since, good control over the space conditions without any
DOAS supplies ventilation air at the same condition, detrimental e®ects on energy performance.
the di®erences in HVAC EUI and total chiller loads
are primarily due to di®erences in supply conditions
and design air°ow rates. Un-zoned recirculating sys- 6. Conclusions
tem considers the whole building as a single thermal A thermal zoning methodology based on design
block and supplies conditioned air at the same tem- space cooling load is presented in this paper. This
perature regardless of its thermal load character- method followed \sort and eliminate" schemes for
istics. On the other hand, zoned recirculating systems ¯rst creating sample space groups and then forming
consider load characteristics to optimize design sup- multiple clusters of spaces served by respective
ply conditions for each thermal zone. In addition, the HVAC systems. The optimized design supply con-
moisture controlling capability of zoned recirculating ditions for the served zones are also determined
systems with DOAS is consistently better than other through the thermal zoning framework that pri-
systems. The zoned recirculating system con¯gura- marily depends on the type of HVAC system and
tion shows its worst performance with WA-2016 weather data considered for load calculations. The
simulation weather ¯le, where approximately 98% of present methodology is applied for sizing and de-
occupied hours stay within the mandated RH limits signing a DOAS with local recirculating system.
(40–60%). This performance is substantially better A simulation case study is done by applying three
than the other considered system con¯gurations. The di®erent simulation weather ¯les of New Delhi to a
clustering methodology applied here places the per- prototype-building model. Results showed that a
formance points of this system con¯guration into DOAS with zoned recirculating systems consistently
`better performing' clusters across all the simulation keep more than 98% of occupied hours within the
scenario sets. The results clearly shows that a DOAS design temperature and RH limits, without in-
with zoned recirculating systems perform better in creasing the overall HAVC energy and chiller loads
maintaining indoor environmental conditions than beyond 4% and 3% from the best performing cases,
un-zoned systems without signi¯cantly compromis- respectively. This substantiates its superior quali-
ing the energy consumption and total equipment tative performance characteristics. The methodolo-
cooling loads. gy presented here for creating thermal zones is

1850030-17
M. Sarkar

computationally simple and established on basic Int. Build. Perform. Sim. Assn., Hyderabad, India,
mathematical formulations making it more intui- Dec. 7–9, 2015, pp. 1853–1860.
tive than the conventional way, which is more 10. BEMBOOK (2017), Thermal Zoning Determina-
subjective and depends on discretion and experi- tion, http://bembook.ibpsa.us/index.php?title=
ence of designer. Thermal Zoning Determination.
11. ISO 13790-2008, Energy performance of buildings —
calculation of energy use for space heating and
cooling, International Organization for Standardi-
Acknowledgments zation, Geneva, Switzerland, 2008.
The author acknowledges no con°ict of interest. 12. COMNET (2017), Thermal Blocks, HVAC Zones
This research did not receive any speci¯c grant from and Space Functions, https://comnet.org/22-ther-
funding agencies in the public, commercial, or not- mal-blocks-hvac-zones-and-space-functions.
for-pro¯t sectors. The author acknowledges full 13. C. De Souza and S. Alsaadani, Thermal zoning in
by WSPC on 09/10/18. Re-use and distribution is strictly not permitted, except for Open Access articles.

speculative o±ce buildings: Discussing the connec-


support given by IES during the course of this work.
tion between space layout and inside temperature
control, First Building Simulation and Optimazation
Conference, Loughborough, UK, 10–11 Sept., 2012,
References
pp. 417–424.
1. United Nations Department of Economic and Social 14. Chapter 28 — Nonresidential Cooling and Heating
Int. J. Air-Cond. Ref. Downloaded from www.worldscientific.com

A®airs: Population Division, World Population Load Calculations, ASHRAE Handbook — Funda-
Prospects — The 2015 Revision. New York, USA, mentals, American Society of Heating, Refrigeration
2015. and Air Conditioning Engineers, Inc., GA, U.S.A.,
2. United Nations Development Programme, Promot- 1997.
ing Energy E±ciency in buildings: Lessons Learned 15. Chapter 8 — Applied Psychrometrics, Part 1 Load
from International Experience, New York, USA, Estimating, Carrier System Design Handbook, Car-
2010. rier Corporations, Syracuse, New York, USA, 1960,
3. U.S. Energy Information Administration, Commer- pp. 115–151.
cial Buildings Energy Consumption Survey: Energy 16. M. Sarkar, Theoretical comparison of cooling loads
Usage Summary, Washington DC, USA, 2012. of an air handling unit in blow-through and draw-
4. S. Royer, S. Thil, T. Talbert and M. Polit, A pro- through con¯gurations, Energy Build. 64 (2013)
cedure for modeling buildings and their thermal 239–248.
zones using co-simulation and system identi¯cation, 17. Mathematics stack exchange, Standard deviation
Energy Build. 78 (2014) 231–237. of weighted-mean, https://math.stackexchange.
5. ANSI/ASHRAE Standard 90.1-2007, Energy stan- com/questions/320441/standard-deviation-of-the-
dard for buildings except low-rise residential build- weighted-mean.
ings. American Society of Heating, Refrigeration 18. ANSI/ASHRAE Standard 169-2013, Climatic Data
and Air Conditioning Engineers, Inc., GA, U.S.A., for Building Design Standards, American Society of
2007. Heating, Refrigeration and Air Conditioning Engi-
6. N. Jones, C. McCrone, B. Walter and K. Pratt, neers, Inc., GA, U.S.A., 2013.
Automated translation and thermal zoning of digital 19. S. Mumma, Designing dedicated outdoor air system,
building model for energy analysis, Proc. 13th Int. ASHRAE J. 43 (2001) 28–31.
Build. Perform. Sim. Assn. Conf., Chambery, 20. M. Larranaga, M. Beruvides, H. Holder, E.
France, 2013, pp. 202–209. Karunasena and D. Straus, DOAS and humidity
7. T. Dogan and C. Reinhart, Autozoner an algorithm control, ASHRAE J. 50 (2008) 34–40.
for automatic thermal zoning of buildings with un- 21. H. Crowther and Y. Ma, Design considerations for
known interior space de¯nitions, J. Build. Perform. dedicated OA systems, ASHRAE J. 58 (2016) 30–42.
Sim. 9 (2015) 176–189. 22. S. Mumma, Terminal equipment with DOAS: Series
8. T. Dogan, C. Reinhart and P. Michaltaos, Auto- vs. parallel, Engin. Syst. 25(5) (2008) 86–89.
mated multi-zone building energy model generation 23. S. Deng, L. Lau and J. Jeong, Do all DOAS con¯g-
for schematic design and urban massing studies, Int. urations provide the same bene¯ts? ASHRAE J. 56
Build. Perform. Sim. Ass. (IBPSA) e-Sim Conf., (2014) 52–57.
2014, Ottawa, Canada, Jan., 2014. 24. H. Chaudhary, B. Hughes and S. Ghani, A review of
9. T. Dogan, C. Reinhart and E. Saratsis, The optimiza- heat pipe systems for heat recovery and renewable
tion potential of °oor-plan typologies in early design energy applications, Renew. Sustain. Energy Rev. 16
energy modeling, Proceedings of BS2015: 14th Con. (2012) 2249–2259.

1850030-18
Thermal Zoning Based on Design Cooling Loads

25. L. Zhang and W. Lee, Evaluating the use heat pipe for 31. VE for engineers, https://www.iesve.com/software/
dedicated ventilation of o±ce buildings in Hong Kong, ve-for-engineers.
Energy Convers. Manage. 52 (2011) 1983–1989. 32. J. Spitler, Load Calculations Application Manual,
26. D. John, Wrap-around heat pipes in humid climates, American Society of Heating, Refrigeration and Air
ASHRAE J. 58 (2016) 28–38. Conditioning Engineers, Inc., GA, U.S.A., 2009.
27. M. Sarkar, A new theoretical formulation of dew 33. Weather Data — New Delhi, https://energyplus.
point temperatures applicable for comfort air-cool- net/weather-region/asia wmo region 2/IND%20%
ing systems, Energy Build. 86 (2015) 243–256. 20.
28. J. Murphy, Dehumidi¯cation performance of HVAC 34. Weather data from Weather Analytics, https://
systems, ASHRAE J. 44 (2002) 23–31. www.iesve.com/support/weather¯les/weather-ana-
29. J. Murphy, Using VAV to limit humidity at part lytics.
load, ASHRAE J. 52 (2010) 18–22. 35. IES SCAN: Interrogating metered data to optimize
30. E. M. Sterling, A. Arundel and T. D. Sterling, Cri- energy e±ciency in real buildings, https://scan.
by WSPC on 09/10/18. Re-use and distribution is strictly not permitted, except for Open Access articles.

teria for human exposure to humidity in occupied iesve.com/unauthenticated/home.


buildings, ASHRAE Trans. 91 (1985) 611–622.
Int. J. Air-Cond. Ref. Downloaded from www.worldscientific.com

1850030-19

You might also like