You are on page 1of 22

Cutler-Hammer Circuit Breakers and Trip Units G1-1

January 1999 Low-Voltage Power Circuit Breakers – Magnum DS


General Description

Index Page ➂ ➀ ➁
General Description –
Magnum DS . . . . . . . . . . . . . G1-1
General Description – ➃
DSII/DSLII. . . . . . . . . . . . . . . G1-7
Technical Data – Magnum DS . G1-11 ➄
Technical Data – DSII/DSLII . . G1-12

Application Data – Magnum DS
and DSII/DSLII . . . . . . . . . . . G1-16 ➆
Typical Specifications . . . . . . . G1-20
Magnum DS Breakers are power ➇
circuit breakers designed and engi-
neered specifically for use in Mag- ➈
num DS Low Voltage Switchgear
assemblies applied at nominal volt- ➉
ages of 240, 480, and 600 Vac. Six
continuous ratings – 800 amperes k
through 5000 amperes – are covered
by only two physical breaker sizes. l
Controls and indicators are function-
ally grouped on the front of the
breakers and the through-the-door
design means they are easily viewed
and accessible.
➀ Trip Flag
G
➁ Three Accessory Windows
➂ Digitrip RMS Trip Unit
➃ Contact Status Indicator (Open or
Closed)
➄ Spring Status Indicator (Charged
or Discharged)
➅ “Push Off” to Open Breaker Button
➆ “Push On” to Close Breaker Button
➇ Manual Charging Handle The breaker can be conveniently racked
in or out, stopping at the various posi-
➈ Optional Operations Counter tions with the door closed.
Integrally designed breaker steel cassette for
➉ Optional “Off” Key Lock drawout breakers provides clear indication of
connect, test, and disconnect positions.
k Padlockable Levering Device
l Color-Coded Breaker Position
Indicators
Magnum DS Breakers are 100 per-
cent rated, UL listed, and are built
and tested in an ISO 9000 certified
facility to applicable standards
including:
■ ANSI C37.13 ■ NEMA SG3
■ ANSI C37.16 ■ UL 1066
■ ANSI C37.17 ■ CSA 22.2
■ ANSI C37.50 Faceplate controls facilitate operation of
Magnum DS is also suitable for use in: the breaker, and the three accessory
mounting windows provide for easy The breaker spring charging handle is de-
■ UL 1558 Low Voltage Switchgear identification. signed with sufficient space for operation
■ UL 891 Low Voltage Switchboards even with a gloved hand.
■ CSA 22.2.31 Low Voltage
Assemblies

CAT.71.01.T.E
G1-2 Circuit Breakers and Trip Units Cutler-Hammer
Low-Voltage Power Circuit Breakers – Magnum DS January 1999

General Description

Designed for Easy Access, ➂ ➀ ➁


Inspection, and Minimal
Maintenance
The stored energy mechanism, con-
trol devices, accessories, and sec-
ondary contacts are easily accessible
by removing the front cover that is
held in place by four captive screws.
This can only be done when the
breaker is in the disconnect position
or removed from the cell. ➃

The current sensor viewing window
on the rear of the breaker allows for ➅
easy identification of the current
sensor mounted inside. ➆
The contact wear indicator elimi-
nates the need for elaborate testing

to determine if the contact assembly ➈
needs replaced.
Many minor replacement functions
involving the mechanism, control,
and/or accessories can be easily ➀ Secondary Wiring Points
G accomplished.
➉ ➁ Field Installable Accessories
k (Three Maximum)
Two-Step Stored Energy ➂ Digitrip RMS Trip Unit
Mechanism for Manually ➃ Optional Electric Charging Motor
and Electrically Operated ➄ Manual Charging Handle
Breakers ➅ Optional Operations Counter
The potential energy is stored in the ➆ Optional “Off” Key Lock
mechanism to close the breaker in ➇ Padlockable Levering Device
5 cycles or less. Sufficient energy to ➈ Breaker Position Indicator
open the breaker remains available ➉ Secondary Contacts
following the closing operation. k Arc Chute Covers
After closing, the charging spring l Primary Finger Cluster
can be recharged to provide poten- Disconnects
tial energy for reclosing following a m Current Sensor Window
fault, providing high continuity of n m l
n Rigid Frame Housing
service. This feature allows for the This rear view of a Magnum DS drawout
breaker shows the designed-in safety feature
following sequence: charge – close – of locating the secondary contacts away from
recharge – open – close – open. the primary disconnects.

On manually operated breakers,


closing springs are charged by hand. Increased Short Time and
For electrically operated breakers, Interrupting Ratings
springs are charged by an electric
motor but can be manually charged Magnum DS Power Circuit Breakers
if no power is available. are available with short time ratings
up to 85,000 amperes RMS symmet-
rical and interrupting ratings up to
100,000 amperes RMS symmetrical. Positioning of the secondary contact sub-
These increased ratings far exceed assembly is dedicated for installation,
ratings previously available on maintenance, and testing. Top view
power circuit breakers. shown with breaker cover removed, bot-
tom of photo is front of breaker.

CAT.71.01.T.E
Cutler-Hammer Circuit Breakers and Trip Units G1-3
January 1999 Low-Voltage Power Circuit Breakers – Magnum DS
General Description

Flexible Current Path As the circuit breaker is called upon Isolated View of Contact Opening
to open, the toe and heel simulta- Sequence
Increases Current Carrying neously touch. At that point, the cur-
Capability in Less Space rent changes its path from the main
■ Multi-finger contact structure contact to the arcing contact. As the
divides the current flow, increas- heel lifts off, any remaining current
ing the thermal carrying capability is driven to the toe. The result is
minimal arcing damage to the main
contact (heel) providing for longer
main contact life.
Upon closing, the toe absorbs most 1. Fully Closed Position
of the impact and deals with any arc- Only the main contact (heel) touches and
ing by touching down before the all current flow is through the main contact.
heel. Once again, the main contact
(heel) is protected resulting in longer
life.
Visual contact wear indicator shows
when contact replacement is necessary.
Arc Running System
■ Flexible braided current path to
the contact fingers reduces neces-
Provides Higher Interrupting
sary current carrying space and Capacity in Less Space
provides a smooth connection, ■ Heel-toe contact structure is a
eliminating bolted joints and con- 2. Simultaneous Touching of All
single contact finger design that Contacts
tact springs. This design helps performs both main and arcing The arcing contact (toe) touches down be-
increase breaker service life by
reducing localized heat buildup
contact functions by controlling fore the main contact (heel) lifts off with G
the arc direction. This design pro- current flow dividing between main (heel)
and mechanical stress inherent in

HH€€
ˆˆ
ÈÈ

FƆF
†GG
Ƈ‡
ÇÇ

and arcing (toe) contacts.

zzzz
 ,,,
yyy
vides for longer contact life.
conventional bolted joints.
■ Integral arc runner enhances the
Cross-Section of Magnum DS magnetic action of the arc chute

|{,y
{ |||
{{{
 {

z

|

Heel-Toe Contact
by drawing the arc into the chute
with increased efficiency, reduc-

{,yz|,y{{ z

|

Arc
Chute ing arcing at the toe of the con-
Moving
Arcing
tacts. This exclusive design allows
Contact Integral for higher arcing in a smaller

 z
y

,
|

(Toe) Arc Runner
Stationary space, resulting in increased inter-
Moving Main Contact
Contact rupting ratings. Alternating V Arc 3. Toe (Arcing) Contacts Touching
Fingers

{|z z,
y , |

Current Chute™ quickly divides and extin-
Moving Flow The main contact (heel) lifts off with the
Main guishes the arc. The V Arc Chute arcing contact (toe) still touching to deal
Contact Line
Conductor reaction speed protects contact with any arcing. Current flow is only

z,{
,,
zz
yy
|
,y{|
(Heel) XXXXXXX
X X

Moving
X X
XXXXXXX
Load material, extending contact life. through the arcing contact (toe).
Contact Conductor
Carrier Current
Flow
Braided XXXXXXX
Flexible X
X
X
X
Contact
Shunts XXXXXXX Sensor

Breaker
Front

Unlike conventional power breaker


designs utilizing separate arcing and
main current carrying contacts,
Magnum DS Circuit Breakers per- 4. Fully Open Position
form both functions on different Both the main (heel) and arcing (toe) con-
parts of the same contact finger. tacts are open and there is no current
flow. The arc dissipates up into the arc
Each finger has a moving main con- chute.
tact (heel) and a moving arcing con-
tact (toe). A complete movable
Arc chutes can be easily removed and in-
contact is merely the combination of
spected. The contact wear indicator on the
a number of individual fingers. main contact assembly can also be inspected.

CAT.71.01.T.E
G1-4 Circuit Breakers and Trip Units Cutler-Hammer
Low-Voltage Power Circuit Breakers – Magnum DS January 1999

General Description

Rigid Frame Housing Built-in Safety Features ■ Connect. Both main and second-
ary contacts are connected and
The Magnum DS Breaker utilizes a Provide Optimum Operator the breaker is ready for normal
rigid frame housing – an ANSI Safety and System Security operation.
power breaker exclusive. This
■ Improved C-loop current path ■ Test. Main disconnects are disen-
housing provides the strength and
design provides dramatic gaged, secondary contacts are
stability required in the mounting of
improvements in both safety and engaged. All functions of the
the current path and operating
efficiency. Higher current ratings breaker and trip unit can be tested
mechanism.
increase the blow-on forces on in this position.
■ Increased Uptime. Because the the contact surfaces, allowing the ■ Disconnect. A storage position in
current path is isolated and insu- proper downstream protective the compartment but the breaker
lated inside a two-piece inter- device to open, isolating the fault is open and disconnected.
connected housing, any potential and increasing uptime.
damage that may occur during Positive on is indicated on the
arc interruption between the

Quality and Reliability
breaker faceplate. This unique
poles or outside of the breaker is interlocking feature prevents the Cutler-Hammer performs consistent
minimized. levering door from being opened endurance and reliability tests on
■ Increased Breaker Life. By provid- if the contacts are welded, pro- Magnum DS Breakers.
ing rigid support for the operating tecting personnel from exposure
■ Mini-Life Tests. A breaker is ran-
mechanism and the contact struc- to live primary contacts.
domly selected from the produc-
ture, mechanical stress is Making current release prevents
■ tion line daily, and tested for an
reduced, increasing reliability. the breaker from closing in on average of 50 mechanical opera-
■ Design Reliability. The housing a fault exceeding 15 times the tions to assure performance as
reduces the number of frame nominal current. required.
G parts in comparison with conven- ■ Keyed sensor plug insures error- ■ Maxi-Life Tests. MTBF testing
tional ANSI power breakers, pro- free installation of the sensor in continuously tests Magnum DS
viding increased reliability. the field. Breakers until they fail. This iden-
■ Rigid Frame. The engineered ther- ■ Deadfront faceplate isolates the tifies potential performance
moset composite resin provides operator from the primary voltage issues with the breaker and
excellent structural properties, when the breaker is energized. provides statistical analysis for
dielectric strength, and arc track further improvement.
resistance helping to provide the ■ Anti-pump prevents any attempts
higher interrupting and short time to reclose the breaker on a short
(withstand) ratings in a smaller circuit fault if the close signal
size. (mechanical or electrical) is
maintained.
■ Interlocked levering door cannot
be opened until the contacts are
in the open condition.
■ Three position indicators on the
faceplate for drawout mounting.
Specific colors identify the
breaker position.

CAT.71.01.T.E
Cutler-Hammer Circuit Breakers and Trip Units G1-5
January 1999 Low-Voltage Power Circuit Breakers – Magnum DS
Accessories

A Common Family of Acces- Factory Installed or


sories for Both Frame Sizes Available as UL Listed
Magnum DS accessories fit all frame Field Installable Kits
sizes.
Through-the-Window Electrical
Magnum DS through-the-window Accessories
accessories are installed near the
right front of the breaker. The unique
windows in the breaker cover enable
accessories to be quickly identified
by name and rating.
Accessories are plug-in, providing
for easy mounting and wiring to
save both installation time and cost.
This feature facilitates accessory
changes and replacements by user ■ Shunt Trip – Provides remote con-
personnel, eliminating the need to trolled circuit breaker opening
use factory trained personnel or out- when energized by a voltage
Through-the-window electrical accesso-
side service companies. input. ries are identically sized, yet keyed for
■ Spring Release – Remotely closes error-free mounting.
Modular accessories are keyed for
fast error-free mounting in the field. the breaker when its coil is ener-
For example, the spring release can gized by a voltage input.
only be mounted in the center cavity. ■ Undervoltage Release (UVR) –
Trips the breaker remotely when G
an existing voltage signal is lost
or drops below an established
threshold.

Internal Accessories
■ Auxiliary Switch – Provides the
capability to remotely indicate if
the breaker is open or closed. Up
to six normally open and six nor-
mally closed auxiliary contacts
are available for customer use.
The auxiliary switch is an internal acces-
■ Overcurrent Trip Switch (Bell sory that provides remote electrical indi-
Alarm) – A set of normally open cation if the breaker is open or closed.

The accessory cavity design, unique to


and normally closed contacts that
ANSI power breakers, is accessible in the indicate when a breaker trips.
front of the breaker. Up to three accesso- ■ Electrical Operator – A universal
ries can be easily installed and wired in
the field. type electric motor, internally
mounted in the circuit breaker,
that charges the closing springs
automatically, facilitating remote
or local closing.

An electric motor automatically charges


the closing springs. In absence of control
power, the springs can be manually
charged.

CAT.71.01.T.E
G1-6 Circuit Breakers and Trip Units Cutler-Hammer
Low-Voltage Power Circuit Breakers – Magnum DS January 1999

Trip Units

Programmable Trip Units


■ Digitrip RMS 1150 provides pro-
grammability for more sophisti-
cated distribution systems
– Increased protection and coor-
dination capabilities.
– Systems monitoring informa-
tion including power factor,
voltage, current, harmonic dis-
tortion values, and waveform
capture with a three-line, (eight
characters per line) LED display.
Magnum DS modular design allows cus- – Two programmable contacts for
tomers to mount accessories in the field. customer use.
– Time stamping of trip events for
Electronic Trip Units improved troubleshooting and
Cutler-Hammer introduced the first diagnostics.
microprocessor-based trip unit and
– Accuracy of 1% on current and
has advanced the technology into a
voltage values and 2% on
new family of UL and CSA listed
energy and power.
Digitrip RMS Electronic and Pro-
grammable Trip Units designed and – Systems diagnostic informa-
G engineered exclusively for Magnum tion.
DS Breakers.
– IMPACC/PowerNet
■ Digitrip RMS 520 enables the user communications.
as many as nine phase and
For additional information on trip
ground current protection set-
units see section G3
tings for maximum flexibility in
trip-curve shaping and multi-unit
coordination, and adds ground
current protection settings.
■ Digitrip RMS 520M adds phase,
neutral, and ground current
metering with a four-character
LCD display window.

CAT.71.01.T.E
Cutler-Hammer Circuit Breakers and Trip Units G1-7
January 1999 Low-Voltage Power Circuit Breakers – DSII
General Description

Two-Step Stored Energy Closing


Mechanism — Spring charging (1)
and spring release to close breaker
(2) are independent operations, and
always give positive control of the
instant of closing.
Motor Operated Stored-Energy
Closing Mechanisms are supplied
on electrically operated breakers.
Standard control voltages are 48,
125 and 250 dc, and 120 and 240 ac.
Remote Closing and Tripping can be
accomplished with manually oper-
DS II with 910
ated breakers by charging the clos-
ing mechanism manually, then
closing and tripping it remotely
Type DSII Low-Voltage through electric spring release and
Power Circuit Breakers shunt trip coils; available as optional
attachments.
Type DSII Low-Voltage Power
Circuit Breakers provide: Digitrip RMS Integral Microproces-
sor-Based Breaker Overcurrent Trip
■ 100% rated, fully selective Systems — Provides maximum reli-
protection. ability, true RMS sensing as stan-
■ Integral microprocessor-based
breaker tripping systems.
dard, excellent repeatability, and
requires minimum maintenance. No
Two-Step Stored-Energy Closing G
external control source is required. Two-step stored energy closing
■ Two-step stored-energy breaker
closing. gives operator positive control of
Change in Trip Rating — The over-
closing after spring mechanism is
and many other features for coordi- current trip pickup range is estab-
charged. Breaker can’t close while
nated, safe, convenient, trouble-free lished by a combination of trip unit
still being charged. Operation is
and economical control and pro- rating plugs and the rating of the
optional—full manual, full electric,
tection of low-voltage distribution current sensors on the breaker.
or manual charge and electric close.
systems. Interphase Barriers on breakers pro-
On manual breakers, the spring
Maximum Ratings vide maximum insulation security.
mechanism is manually charged by
The barriers are easily removable for
600 Vac one downward stroke of the lever
breaker inspection.
5000 amperes continuous without pumping, and released by
200,000 amperes short circuit Provision for Padlocking — All the mechanical “push-to-close”
capacity breakers include provision for pad- release button. On electrically oper-
locking open to prevent electrical ated breakers, the mechanism is
Type DSII Circuit Breaker or manual closing. This padlocking normally charged and released elec-
also secures the breaker in the con- trically, but can be charged manually
Features nected, test or disconnected position by pumping the charging lever 10 to
Protection During Levering Opera- by preventing levering. 12 times and released mechanically.
tion — When levering the breaker
Ease of Inspection and Maintenance An interlock discharges the closing
between the connected, test and dis-
— Type DSII breakers are designed springs as the breaker is removed
connected positions, the operator is
for maximum accessibility and the from the compartment. The system
protected by a steel barrier (face-
utmost ease of inspection and is patterned after 5 kV and 15 kV
plate) from contact with live parts.
maintenance. Metal-Clad switchgear.

CAT.71.01.T.E
G1-8 Circuit Breakers and Trip Units Cutler-Hammer
Low-Voltage Power Circuit Breakers – DSII January 1999

General Decription

Arc Chute Levering Mechanism Release of the stored energy is


There are three basic means of The worm gear levering mechanism accomplished by manually depress-
extinguishing an arc: lengthening is self-contained on the breaker ing a bar on the front of the breaker
the arc path; cooling by gas blast or drawout element and engages slots or electrically energizing a releasing
contraction; deionizing or physically in the breaker compartment. A solenoid.
removing the conduction particles removable crank is used to lever Contacts
from the arc path. It was the discov- the breaker between the Connected-
All air circuit breakers have solid
ery by Westinghouse of this last Test-Disconnected and Removed
block, silver tungsten, inlaid main
method which made the first large positions.
contacts. This construction ensures
power air circuit breaker possible.
Mechanical interlocking is arranged lasting current-carrying ability,
The De-ion® principle is incorpo- so that levering cannot be accom- which is not seriously impaired even
rated in all of these circuit breakers. plished unless the breaker is in the after repeated fault interruptions or
This makes possible faster arc opened position. repeated momentary overload.
extinction for given contact travel;
Stored-Energy Mechanism The main contacts are of the butt
ensures positive interruption and
A cam-type closing mechanism type and are composed of a multi-
minimum contact burning.
closes the breaker. It receives its plicity of fingers to give many points
energy from a spring which can be of contact without alignment being
charged by a manual handle on the critical.
front of the breaker or by a universal
electric motor.

G Arcing Contact Stationary Arcing Interphase Secondary


Spring Contacts Barriers Disconnecting
Contacts

Molded Base

Moving
Arcing
Stationary Main Contact
Contact Fingers

Moving Contact
Assembly
Insulating
Link

Levering Device Arm


(Connected Position)

Main Disconnecting
Insulating Link
Contacts
Lock Nut Sensors

DSII Breaker Pole Unit DSII Breaker Rear View

CAT.71.01.T.E
Cutler-Hammer Circuit Breakers and Trip Units G1-9
January 1999 Low-Voltage Power Circuit Breakers – DSII
General Description

DSLII-620 Front View


DSLII-620 Rear View

Type DSLII Limiter Type currents beyond the breaker rating, identifying the blown fuse and (2)
up to a maximum of 200,000 picks up a solenoid which raises the
Air Circuit Breakers amperes symmetrical. Thus, on breaker trip bar, holding the breaker
Application overloads and faults within the mechanically trip-free.
Type DSLII breakers are coordinated breaker interrupting rating, the
The DSLII-632 and DSLII-840 combi-
combinations of Type DSII breakers breaker protects the limiters; on
and series connected current limit- higher fault currents exceeding the
nations with separately mounted
limiters operate on the same princi-
G
ers. They are intended for applica- breaker rating, the limiters protect
ple except that the solenoid operates
tions requiring the overload the breaker.
a micro-switch which trips the
protection and switching functions Protection Against Single Phasing breaker electrically through a shunt
of air circuit breakers on systems trip coil.
Loads are protected against single
whose available fault currents
phase operation by interlock arrange- Safety Features
exceed the interrupting rating of the
ments which trip the circuit breaker
breakers alone, and/or the withstand The integral fuses on Types DSLII-
whenever any one limiter blows. The
ratings of “downstream” circuit 308, DSLII-516, and DSLII-620 break-
breaker cannot be reclosed on a live
components. ers are inaccessible until the breaker
source until there are three unblown
is completely withdrawn from its
Sizes and Arrangements limiters in the circuit.
compartment, thereby assuring
Types DSLII-308 (800 ampere), On the Types DSLII-308, DSLII-516, complete isolation.
DSLII-516 (1600 ampere), and DSLII- and DSLII-620 breakers, the prima-
620 (2000 ampere) frame breakers Likewise, the Types DSLII-632 and
ries of small auxiliary transformers
include the limiters integrally DSLII-840 fuses are inaccessible
are connected in parallel with the
mounted on the drawout breaker until the separate fuse truck is
limiters. The voltage between the
elements in series with the upper completely withdrawn and the fuses
ends of an unblown limiter is zero,
terminals. isolated. The fuse truck is key inter-
but when any limiter blows, the
locked with the breaker to prevent
Current limiters used in Types DSLII- associated transformer is energized
withdrawal or insertion unless the
632 and DSLII-840 combinations are and (1) operates an indicator
breaker is locked open.
mounted on separate drawout
trucks in an additional equal size Table 1 – Interrupting Ratings of Type DSLII Breakers
compartment. Type DSLII-308 DSLII-516 DSLII-620 DSLII-632 DSLII-840

Scope of Fault Interruption Frame Size, Amperes 800 1600 2000 3200 4000

With properly selected and coordi- Maximum Interrupting Rating, 200,000 200,000 200,000 200,000 200,000
RMS Symmetrical Ampere,
nated limiters, it is expected that the System Voltage 600 or Below
breaker itself will clear overloads
and faults within its interrupting
rating, leaving the limiters intact
and undamaged. The limiters will
provide fast interruption of fault

CAT.71.01.T.E
G1-10 Circuit Breakers and Trip Units
Cutler-Hammer
Low-Voltage Power Circuit Breakers – DSII January 1999

Accessories/Trip Units

Optional Breaker (f) Electric Lockout (optional on equipment. The primary function of
manual breakers). In order to the Digitrip electronic trip unit is to
Attachments and Accessories close the breaker after manually provide circuit protection. This is
(a) Shunt trip on manually operated charging the closing mechanism, achieved by analyzing the secondary
breakers, for any standard con- it is necessary to operate an elec- current signals received from the
trol voltage. trical pushbutton on the breaker circuit breaker current sensors and
faceplate. This pushbutton is initiating trip signals to the circuit
(b) Auxiliary contacts on manually or wired-out to the secondary con- breaker trip unit when pre-set cur-
electrically operated breakers. tacts so it may be wired in series rent levels and time delay settings
Maximum of 5 normally open with any required external inter- are exceeded. By sampling the cur-
and 5 normally closed contacts locking. The mechanical “push- rent waveform at various points on
are available on any breaker, to-close” bar is made inoperative the wave and calculating true RMS
manually or electrically oper- when the breaker is in the con- current, the Digitrip is able to reduce
ated. The contact rating is 10 nected position. nuisance tripping events due to non-
amperes. sinusoidal wave shapes.
(g) Electric close release on manu-
(c) Compartment position switch, ally operated breakers, for any Electronic trip units are applied to
6 or 12 contact, actuated by standard control voltage. Breaker distribution systems when high
movement of drawout breaker can be closed by remote control standards of protection and coordi-
between the connected and test switch or pushbutton after the nation are called for. In addition,
positions. Most common uses closing spring is manually electronic trip units can provide fur-
are for disconnecting remote charged. ther enhanced features such as
control circuits of electrically alarming, diagnostics, system moni-
operated breaker, and for bypass- (h) Operation counter.
toring and communications.
ing “b” interlocking auxiliary
(i) Latch check switch.
contacts, when breaker is with- Cutler-Hammer RMS sensing trip
G drawn to test position. units for power breakers fall into two
Electronic Trip Units main categories:
(d) Undervoltage trip (ac and dc
available). Acts to trip the breaker Cutler-Hammer offers the most com- ■ Front adjustable trip units: Digitrip
when the voltage on its solenoid prehensive range of electronic trip RMS 510, 610, 810, 910
coil is insufficient to restrain a units in the industry for power circuit
■ Programmable trip units: Digitrip
spring-loaded core. The dropout breakers.
OPTIM 750, 1050
point is within 30 to 60 percent of Digitrip electronic trip units are ac
the nominal coil voltage and is For additional information on trip
devices that employ microproces-
not adjustable. Available as units see section G3
sor-based technology that provides
either instantaneous or time a true RMS current sensing means
delay type. The time delay is for proper correlation with thermal
within 2 to 7 seconds after zero characteristics of conductors and
voltage occurs, and is not adjust-
able. The device automatically Standard Control Diagram for Type DSII Electrically Operated Breaker,
resets when the breaker opens; for Ac or Dc Control Source.
approximately one minute is
Legend
required for resetting of the time LS — Limit Sw. for Closing Spring CS (or PB)
CS (or PB)
delay type. MOT — Motor for Spring Charging Close Ind. G Trip
R
SH TR — Shunt Trip Lts.
(e) Overcurrent trip switch (OTS). SR — Spring Release
Y — Anti-Pump Relay
A latching type switch with two
independent contacts either nor- Description of Operation
1 – Motor is energized through LS contact.
mally open or normally closed. 2 – Motor runs and charges Closing Spring. SR MOT SHTR
Operates only when the breaker 3 – When Closing Spring fully charged, LS
contacts reverse.
is tripped automatically on an 4 – CIosing CS-C contact energizes SR Coil Y
overload or fault condition. It through Y, LS & “b” contacts.
5 – When Breaker closes, “b” opens and Y Y LS LS
may be used for alarm and/or
Coil is energized in series with SR Coil.
interlocking circuits. Resetting is 6 – Y contact opens to open SR Coil circuit & b b a
done by a pushbutton on the prevent pumping should breaker open
breaker faceplate, or by a remote while CS-C is held closed. Y Coil has very
low drop-out voltage.
switch through an optional reset 7 – LS contacts reverse and motor recharges
coil. closing springs.

CAT.71.01.T.E
Cutler-Hammer Circuit Breakers and Trip Units G1-11
January 1999 Low-Voltage Power Circuit Breakers – Magnum DS
Technical Data

Magnum DS Ratings Maximum voltages at which the


interrupting ratings in Table 2 apply
Table 2 – Ratings of Magnum DS Breakers are:
Breaker Frame Ratings, RMS Symmetrical Amperes (000)
Type Amperes System Voltage Maximum Voltage
Interrupting Rating Short Time Rating➀
208-240V 480V 600V 208-240V 480V 600V 208 or 240 254
480 508
MDS-408 800 42 42 42 42 42 42 600 635
MDS-608 800 65 65 65 65 65 65
MDS-808 800 85 85 85 85 85 85 These interrupting ratings are based
MDS-C08 800 100 100 100 85 85 85
MDS-616 1600 65 65 65 65 65 65 on the standard duty cycle consist-
MDS-816 1600 85 85 85 85 85 85 ing of an opening operation, a
MDS-C16 1600 100 100 100 85 85 85 15-second interval and a close-open
MDS-620 2000 65 65 65 65 65 65
MDS-820 2000 85 85 85 85 85 85 operation, in succession, with
MDS-C20 2000 100 100 100 85 85 85 delayed tripping in case of short-
MDS-632 3200 65 65 65 65 65 65
MDS-832 3200 85 85 85 85 85 85
delay devices.
MDS-C32 3200 100 100 100 85 85 85
MDS-840 4000 130 85 85 85 85 85 The standard duty cycle for short-
MDS-C40 4000 130 100 100 100 100 100 time ratings consists of maintaining
MDS-850 4000 130 85 85 85 85 85 the rated current for two periods of
MDS-C50 5000 130 100 100 100 100 100
1/2 second each, with a 15-second
interval of zero current between the
two periods.

Table 3 – Available Sensor Ratings and Table 4 – Digitrip RMS Adjustable Trip Settings
Rating Plugs for Digitrip RMS➁ Time/Current Pickup Setting Pickup Point Time Band, Seconds
Breaker
Frame
Available Ratings
Characteristics (see note)
G
Long Delay 0.4, 0.5, 0.6, 0.7, 0.8 In Times 2, 4, 7, 10, 12, 15, 20, 24
800 200, 250, 300, 400, 600, 800 0.9, 0.95, 1.0 Long Delay Setting (at 6 times pickup value)

1600 200, 250, 300, 400, 600, 800, 1000, Instantaneous Off, 2, 3, 4, 6, 10 In Times
1200, 1600 M1 Instantaneous Setting

2000 200, 250, 300, 400, 600, 800, 1000, Short Delay 2, 2.5, 3, 4, 6, 8, 10 Ir Times 0.1, 0.2, 0.3, 0.4, 0.5
1200, 1600, 2000 M1 Short Delay Setting (Flat Response)
0.1*, 0.3*, 0.5*
3200 2500, 3000, 3200 *(I2t Response)
4000 3200, 4000 Ground Fault 0.25, 0.3, 0.35, 0.4, In Times 0.1, 0.2, 0.3, 0.4, 0.5
5000 3200, 4000, 5000 0.5, 0.6, 0.75, 1.00 Ground Fault Setting (Flat Response)
(1200A Maximum) 0.1*, 0.3*, 0.5*
*(I2t Response)
Note: In = Rating Plug Value
Ir = Long Delay Pickup Setting Times In

Table 5 – Magnum DS Breaker Control Voltages and Currents


Control Voltage 24 Dc 48 Dc 125 Dc 120 Ac 240 Ac

Close current (SR), ampere 2.70 1.30 0.67 0.59 0.34


Shunt trip current, ampere 2.70 1.30 0.67 0.59 0.34
Spring charge motor ampere 8.00 4.00 3.00 3.00 3.00
Control voltage range:
Close – 18-26 38-56 100-140 104-127 208-254
Trip – 18-26 28-56 70-140 60-127 208-254
Motor currents are running currents. Inrush is approximately 400%. Motor running time to charge spring
approximately 5 seconds.

➀ Also ratings without instantaneous trip.


➁ The rating plug is for 50 and 60 Hz applica-
tions. Rating plugs are not interchangeable
with 60 Hz or 50 Hz only rating plugs.

CAT.71.01.T.E
G1-12 Circuit Breakers and Trip Units
Cutler-Hammer
Low-Voltage Power Circuit Breakers – DSII January 1999

Technical Data

DSII Ratings Maximum voltages at which the


interrupting ratings in Table 3 apply
Table 6 – Interrupting Ratings of Type DSII Breakers are:
Breaker Frame Ratings, RMS Symmetrical Amperes
Type Size, Amperes System Voltage Maximum Voltage
Interrupting Rating Short Time Rating ➀
208-240V 480V 600V 208-240V 480V 600V 208 or 240 254
480 508
DSII-308 800 42,000 30,000 30,000 30,000 30,000 30,000 600 635
DSII-508 800 65,000 50,000 42,000 50,000 50,000 42,000
DSII-608 800 65,000 65,000 50,000 65,000 65,000 50,000 These interrupting ratings are based
DSII-516 1600 65,000 50,000 42,000 50,000 50,000 42,000 on the standard duty cycle consist-
DSII-616 1600 65,000 65,000 50,000 65,000 65,000 50,000
DSII-620 2000 65,000 65,000 50,000 65,000 65,000 50,000 ing of an opening operation,a
DSII-632 3200 85,000 65,000 65,000 65,000 65,000 65,000 15-second interval and a close-open
DSII-840 4000 130,000 85,000 85,000 85,000 85,000 85,000 operation, in succession, with
DSII-850 5000 130,000 85,000 85,000 85,000 85,000 85,000
delayed tripping in case of short-
Table 7 – Digitrip RMS Adjustable Trip Settings delay devices.
Time/Current Pickup Setting Pickup Point Time Band, Seconds The standard duty cycle for short-
Characteristic (see note)
time ratings consists of maintaining
Long Delay 0.5, 0.6, 0.7, 0.8, In Times 2, 4, 7, 10, 12, 15, 20, 24 the rated current for two periods of
0.85, 0.9, 0.95, 1.0 Long Delay (at 6 times pickup value)
Setting 1⁄2 second each, with a 15-second
Instantaneous 2, 2.5, 3, 4, 5, 6 In Times
interval of zero current between the
M1=8, M2=12 Instantaneous two periods.
Setting
Short Delay 2, 2.5, 3, 4, 5, 6 Ir Times 0.1, 0.2, 0.3, 0.4, 0.5 Table 10 – Available Sensor Ratings for
S1=8, S2=10 Short Delay (Flat Response) Digitrip RMS
Setting 0.1*, 0.3*, 6.5*
G Ground Fault A (.25), B (.3), C (.35), In Times
*(I2t Response)
0.1, 0.2, 0.3, 0.4, 0.5
Breaker Frame Size,
Amperes
Sensor Ratings,
Amperes

D (.4), E (.5), F (.6), Ground Fault (Flat Response) DSII-308, DSLII-308, 800 200, 300, 400,
H (.75), K (1.0) Setting 0.1*, 0.3*, 0.5 DSII-508 or 600, 800
(1200A Maximum) *(I2t Response) DSII-608
Note: In= Rating Plug Value DSII-516, DSLII-516 1600 200, 300, 400,
Ir = Long Delay Pickup Setting x In or DSII-616 600, 800, 1200,
1600
DSII-620 2000 200, 300, 400,
Table 8 – Control Voltages and Currents 600, 800, 1200,
Control Voltage 48 Dc 125 Dc 250 Dc 120 Ac 240 Ac 1600, 2000
DSLII-620 2000 2000
Close current (SR), ampere 5.0 2.0 1.0 3.0 2.0 DSII-632, DSLII-632 3200 2400, 3200
Shunt trip current, ampere 5.0 2.0 1.0 2.0 1.0 DSII-840, DSLII-840 4000 3200, 4000
Spring charge motor ampere 7.5 3.0 1.5 3.0 1.5 DSII-850 5000 5000
Control voltage range: 38-56 100-140 200-280 104-127 208-254
Close – 28-56 70-140 140-280 60-127 208-254 Table 11 – Available Digitrip RMS Rating
Trip –
Plugs Marked 50/60 Hertz➁
Note: Motor currents are running currents; inrush is approximately 400%. Motor running time to charge
spring approximately 5 seconds. Sensor Ratings, Plug Rating in Amperes (In)
Amperes

Table 9 – Estimated Heat Loss Per Breaker 200 100, 200


300 200, 250, 300
Breaker Watts
400 200, 250, 300, 400
DSII-308 (DSLII-308) 400 (600) 600 300, 400, 600
DSII-516 (DSLII-516) 1000 (1500) 800 400, 600, 800
DSII-620 (DSLII-620) 1500 (2250) 1200 600, 800, 1000, 1200
DSII-632 2400 1600 800, 1000, 1200, 1600
DSII-840 3000 2000 1000, 1200, 1600, 2000
DSII-850 4700 2400 1600, 2000, 2400
DSII-FT32 3600
3200 1600, 2000, 2400, 3000, 3200
DSII-FT40 4500
4000 2000, 2400, 3200, 4000
5000 3200, 4000, 5000

➀ Short circuit ratings of non-automatic break-


ers except the DSII-840 and DSII-850 which
are 65,000.
➁ The rating plug is for 50 and 60 Hz applica-
tions. Rating plugs are not interchangeable
with 60 Hz or 50 Hz only rating plugs.

CAT.71.01.T.E
Cutler-Hammer Circuit Breakers and Trip Units G1-13
January 1999 Low-Voltage Power Circuit Breakers – DSII
Technical Data

The following curves illustrate the Limiter Selection Minimum, recommended, and maxi-
ratings, melting time-current charac- The selection of a suitable limiter mum limiter sizes for Types DSLII-
teristics and current limiting, or let- rating for a given application is gen- 308, DSLII-516, and DSLII-620 break-
through characteristics, of limiters erally governed by a choice of the ers are given in the following table.
for Type DSLII breakers. following types of protection: Table 12
The let-through current for a given A. Maximum protection of “down- Breaker Sensor Limiter Rating, Amperes
limiter application is readily deter- Type Rating
stream” components. Type DSLII Amperes Minimum Recom- Maximum
mined by extending a vertical line ➀ mended ➂
breakers are often used for this ➁
from the applicable maximum avail- purpose even when the maximum
able symmetrical fault amperes at available fault currents are within DSLII-308 200 250 1200 2000
DSLII-308 300 400 1200 2000
the bottom margin to the character- the interrupting rating of the cor- DSLII-308 400 600 1200 2000
istic line for the particular limiter, responding Type DSII unfused DSLII-308 600 800 1200 2000
and from this intersection extending DSLII-308 800 1200 1600 2000
breakers. DSLII-516 600 800 2000 3000
a horizontal line to the left margin DSLII-516 800 1000 2000 3000
and reading the peak current. The B. Protection of the circuit breaker DSLII-516 1200 2000 2500 3000
withstand rating of any circuit ele- only. DSLII-516 1600 – 3000 –
DSLII-620 2000 – 3000 –
ments protected by the limiters Case A would tend to use the small-
should be at least equal to this peak est available limiter; Case B the larg- Table 13 – DSLII-632 and DSLII-840
current. est. When downstream protection is Available Limiters
It will be noted that the let-through required, the selection is usually a Breaker Type Available Limiters
current increases with the limiter compromise, since certain small lim-
DSLII-632 2500, 3000, 4000A
size or ampere rating; in other iters cannot be coordinated with the DSLII-840 2500, 3000, 4000, 5000A
words, the maximum current limit- breaker to avoid nuisance blowing
ing effect is obtained with the small- on overloads or small and moderate
est size. This effect is to be expected, short circuits. G
since the resistance decreases as the Table 14 – Sensor, Plug and Limiter Selection
rating increases. If the vertical line
DSII Sensor Plug Limiter Rating
from the bottom margin as Breakers Rating Rating (Applicable only to DSLII Breakers)
described in the previous paragraph
does not intersect the limiter charac- 308, 508, 608 200 100, 200 250, 300, 400, 600, 800, 1200, 1600, 2000
300 200, 250, 300 400, 600, 800, 1200, 1600, 2000
teristic line, it is indicated that the 400 200, 250, 300, 400 600, 800, 1200, 1600, 2000
available system fault current is 600 300, 400, 600 800, 1200, 1600, 2000
800 400, 600, 800 1200, 1600, 2000
below the “threshold” current of
that limiter, and it will offer no cur- 516, 616 200 100, 200 800, 1000, 1200, 1600, 2000, 2500, 3000
300 200, 250, 300 800, 1000, 1200, 1600, 2000, 2500, 3000
rent limiting effect. 400 200, 250, 300, 400 800, 1000, 1200, 1600, 2000, 2500, 3000
600 300, 400, 600 800, 1000, 1200, 1600, 2000, 2500, 3000
The current limiting principle is illus- 800 400, 600, 800 1000, 1200, 1600, 2000, 2500, 3000
trated below. 1200 600, 800, 1000, 1200 2000, 2500, 3000
1600 800, 1000, 1200, 1600 3000
la = The Available Peak Fault Current 620 200 100, 200 Not Applicable
tm=The Melting Time 300 200, 250, 300 Not Applicable
400 200, 250, 300, 400 Not Applicable
Ip = The Peak Let-Through Current 600 300, 400, 600 Not Applicable
800 400, 600, 800 Not Applicable
ta = The Arcing Time 1200 600, 800, 1000, 1200 Not Applicable
tc = The Total Interrupting (Clearing) 1600 800, 1000, 1200, 1600 Not Applicable
Time 2000➀ 1000, 1200, 1600, 2000➃. 3000➄
632 2400 1600, 2000, 2400 2500, 3000, 4000
3200 1600, 2000, 2400, 3000, 3200 2500, 3000, 4000
840 3200 1600, 2000, 2400, 3200 2500, 3000, 4000, 5000
4000 2000, 2400, 3200, 4000 2500, 3000, 4000, 5000
Ia 850 5000 3200, 4000, 5000 Not Applicable
Ip

tm ta
tc

➀ For use only when protection of downstream ➁ Lowest rating which can be coordinated with ➃ 2000 ampere is the only sensor available
equipment is required. Not completely breaker to minimize nuisance blowing. for DSLII-620.
coordinated with breaker to avoid nuisance ➂ Highest available ratings, for protection of ➄ 3000 ampere is the only limiter available
blowing. breaker only. for DSLII-620.

CAT.71.01.T.E
G1-14 Circuit Breakers and Trip Units
Cutler-Hammer
Low-Voltage Power Circuit Breakers – DSII January 1999

Technical Data

DSLII-308 Average Melting Time-Current Characteristics DSLII-308 Let-Through Characteristics

SCALE X 100 = CURRENT IN AMPERES

10,000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
70
80
90
1 2 3 4 5 6 7 8 9 10 20 30 40 50 60
1000 1000
900 900
800 800 400,000
700 700
600 600
500 500 300,000
400 400

300 300
200,000
200 Limiter Ampere Rating 200

AMPERE
250
300
400
600

800
1200
1600
2000

RATING
100 100 2000
90 90
80 80 100,000 1600
70 70 90,000
60 60 1200
80,000
50 50 800
70,000
40 40

MAXIMUM PEAK LET-THROUGH CURRENT, AMPS


60,000
30 30
50,000 600

ce
du
TIME IN SECONDS
20 20

o
TIME IN SECONDS

40,000

Pr
an
400

tc
ui
30,000

irc
10 10 300

C
9 9

nt
8 8 250

re
7 7

ur
C
6 6 20,000

ak
5 5

Pe
um
4 4

im
3 3

ax
M
2 2
10,000
9000
8000
1 1
.9 .9 7000
.8 .8
.7 .7 6000
.6 .6
5000
.5 .5

.4 .4 4000
.3 .3

3000
.2 .2

2000
.1 .1
.09 .09
.08 .08
.07 .07
.06 .06
.05 .05

.04 .04 1000


1000

2000

3000

4000

5000

6000
7000
8000
9000
10,000

20,000

30,000

40,000

50,000

60,000
70,000
80,000
90,000
100,000

200,000
.03 .03

.02 .02
AVAILABLE CURRENT, RMS SYMMETRICAL AMPERES

G .01 .01 Ref. Curve No. 639772


300
70
80
90
100

1000

2000

3000

4000
5000
6000
7000
8000
9000
200

400
500
600
700
800
900

10,000

1 2 3 4 5 6 7 8 9 10 20 30 40 50 60
Supersedes AD 36-783
dated April 1980
SCALE X 100 = CURRENT IN AMPERES
Ref. Curve No. 639771
Type DSL-206 Limiters – For DSL-206 and DSLII-308 Breakers
Supersedes AD 36-783 Let-Through Characteristics January 1997
dated April 1980
Type DSL-206 Limiters – For DSL-206 and DSLII-308 Breakers
Average Melting Time – Current Characteristics January 1997

DSLII-516 and DSLII-620 Average Melting Time-Current DSLII-516 and DSLII-620 Let-Through Characteristics
Characteristics
SCALE X 100 = CURRENT IN AMPERES
10,000
1000

2000

3000

4000
5000
6000
7000
8000
9000

400,000
100

200

300

400
500
600
700
800
900
70
80
90

1 2 3 4 5 6 7 8 9 10 20 30 40 50 60
1000 1000
900 900
800 800
700 700 300,000
600 600
500 500

400 400
AMPERE
200,000 RATING
300 300
3000

200 Limiter Ampere Rating 200 2500


2000
800
1000
1200
1600
2000
2500
3000

1600
100,000
100 100
90 90 90,000 1200
80 80
70 70
80,000 1000
60 60 70,000
800
50 50
MAXIMUM PEAK LET-THROUGH CURRENT, AMPS

60,000
40 40
50,000
e
uc

30 30
od

40,000
Pr
TIME IN SECONDS

20 20
TIME IN SECONDS

an
tc
ui

30,000
irc
C
nt

10 10
re

9 9
ur

8 8
C

7 7 20,000
ak

6 6
Pe

5 5
um
m

4 4
i
ax
M

3 3

2 2 10,000
9000
8000
7000
1 1
.9 .9 6000
.8 .8
.7 .7
5000
.6 .6
.5 .5
4000
.4 .4

.3 .3
3000
.2 .2

2000
.1 .1
.09 .09
.08 .08
.07 .07
.06 .06
.05 .05
1000
.04 .04
1000

2000

3000

4000

5000

6000
7000
8000
9000
10,000

20,000

30,000

40,000

50,000

60,000
70,000
80,000
90,000
100,000

200,000

.03 .03

.02 .02 AVAILABLE CURRENT, RMS SYMMETRICAL AMPERES

.01 .01
300
70
80
90
100

1000

2000

3000

4000
5000
6000
7000
8000
9000
200

400
500
600
700
800
900

10,000

1 2 3 4 5 6 7 8 9 10 20 30 40 50 60

Ref. Curve No. 639432


SCALE X 100 = CURRENT IN AMPERES
Type DSL-416 Limiters – For DSL-416, DSLII-516, DSL-420➀ Supersedes AD 36-783
and DSLII-620➀ Breakers dated April 1980
Ref. Curve No. 639431
Type DSL-416 Limiters – For DSL-416, DSLII-516, DSL-420➀ and DSLII-620➀ Breakers Supersedes AD 36-783
Average Melting Time – Current Characteristics dated April 1980 ➀ DSL 420 and DSLII-620 – use only the 3000 limiter. January 1997

➀ DSL-420 and DSLII-620 – use only 3000 limiter. January 1997

CAT.71.01.T.E
Cutler-Hammer Circuit Breakers and Trip Units G1-15
January 1999 Low-Voltage Power Circuit Breakers – DSII
Technical Data

DSLII-632 and DSLII-840 Average Melting Time-Current DSLII-632 and DSLII-840 Let-Through Characteristics
Characteristics
SCALE X 100 = CURRENT IN AMPERES

10,000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
70
80
90
1 2 3 4 5 6 7 8 9 10 20 30 40 50 60
1000 1000 400,000
900 Ampere Rating Limiter 900
800 800 AMPERE

2500

3000

4000
5000
700 700 RATING
600 600 300,000
500 500 5000
400 400 4000
300 300 200,000
3000
200 200 2500

100 100
90 90 100,000
80 80 90,000
70 70
80,000
60 60
50 50 70,000

MAXIMUM PEAK LET-THROUGH CURRENT, AMPS


40 40 60,000
50,000

ce
30 30

odu
40,000

Pr
TIME IN SECONDS
20 20
TIME IN SECONDS

an
tc
ui
30,000

irc
C
10 10

nt
9 9

re
8 8

ur
7 7

C
20,000

ak
6 6

Pe
5 5

um
4 4

im
ax
3 3

M
2 2 10,000
9000
8000
1 1 7000
.9 .9
.8 .8 6000
.7 .7
.6 .6 5000
.5 .5
4000
.4 .4

.3 .3
3000
.2 .2

2000
.1 .1
.09 .09
.08 .08
.07 .07
.06 .06
.05 .05
1000
.04 .04

1000

2000

3000

4000

5000

6000
7000
8000
9000
10,000

20,000

30,000

40,000

50,000

60,000
70,000
80,000
90,000
100,000

200,000
.03 .03

.02 .02
AVAILABLE CURRENT, RMS SYMMETRICAL AMPERES

.01 .01 G
300
70
80
90
100

1000

2000

3000

4000
5000
6000
7000
8000
9000
200

400
500
600
700
800
900

10,000

1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 Ref. Curve No. 705504


Supersedes AD 36-783
SCALE X 100 = CURRENT IN AMPERES Type DSL-632 Limiters – For DSL-632 and DSLII-632 Breakers dated April 1980
Type DSL-840 Limiters – For DSL-840 and DSLII-840 Breakers
Ref. Curve No. 705503
Supersedes AD 36-783 Let-Through Characteristics January 1997
Type DSL-632 Limiters – For DSL-632 and DSLII-632 Breakers dated April 1980
Type DSL-840 Limiters – For DSL-840 and DSLII-840 Breakers
Average Melting Time – Current Characteristics January 1997

CAT.71.01.T.E
G1-16 Circuit Breakers and Trip Units
Cutler-Hammer
Low-Voltage Power Circuit Breakers – Magnum DS and DSII January 1999

Application Data

Application Altitude 3. Salt spray, excessive moisture,


The breakers are applicable at their dripping, etc.
Standards full voltage and current ratings up to Drip shields in equipment rooms
Magnum DS and DSII circuit break- a maximum altitude of 6600 feet and space heaters in indoor
ers meet or exceed all applicable (2000 meters) above sea level. When switchgear, or outdoor weather-
requirements of ANSI Standards installed at higher altitudes, the rat- proof enclosures, may be indi-
C37.13, C37.17, C37.50 and CSA. ings are subject to the following cor- cated, depending upon the
System Voltage and Frequency rection factors in accordance with severity of the conditions.
ANSI C37.20.1:
Magnum DS and DSII breakers are 4. Excessively high or low ambient
designed for operation on ac sys- Table 15 – Altitude Derating Factors temperatures.
tems only, 60 Hz or 50 Hz, 635 volts Altitude Voltage Current
maximum. Correction Correction For ambient temperatures exceed-
Feet Meters
ing 40°C, and based on a standard
Continuous Current Ratings 6,600 2,000 1.000 1.000 temperature rise of 65°C, the con-
Unlike transformers, generators and 7,000 2,150 0.989 0.998 tinuous current ratings of breaker
motors, circuit breakers are maxi- 7,500 2,300 0.976 0.995 frame sizes, and also buses, cur-
mum-rated devices and have no rent transformers, etc., will be
8,000 2,450 0.963 0.993
built-in temporary overload current subject to a derating factor calcu-
ratings. Consequently, it is vital that 8,500 2,600 0.950 0.990
lated from the following formula:
each application takes into consider- 9,000 2,750 0.933 0.987
ation the maximum anticipated cur- 9,500 2,900 0.917 0.983 105°C Total – Special Ambient, °C
rent demand, initial and future, 10,000 3,050 0.900 0.980 105°C Total – 40°C Standard
including temporary overloads. 10,500 3,200 0.883 0.977 Ambient
The continuous rating of any Mag- 11,000 3,350 0.867 0.973 Circuit breakers are not adversely
G num DS and DSII breaker is limited 11,500 3,500 0.850 0.970 affected by very low outdoor
ambient temperatures, particularly
to the sensor rating, or the frame size 12,000 3,650 0.833 0.967
current rating, whichever is the 12,500 3,800 0.817 0.963
when energized and carrying load
lesser. For instance, an MDS-616 currents. The standard space heat-
13,000 3,950 0.800 0.960
1600 ampere frame breaker with 800 ers in weatherproof switchgear
ampere sensors has a maximum will raise the temperature slightly
Unusual Environmental and
continuous rating of 800 amperes, and prevent condensation.
Operating Conditions
but the same breaker with 1600 Electrical components such as
Special attention should be given to
ampere sensors is limited to 1600 relays and instruments, however,
applications subject to the following
amperes maximum. must be applied within the manu-
conditions:
All current ratings are based on a facturer’s specified limits.
1. Damaging or hazardous fumes,
maximum ambient air temperature 5. Exposure to Seismic Shock.
vapors, etc.
of 40°C (104°F).
2. Excessive or abrasive dust. Magnum DS and DSII assemblies
Ambient Temperature and breakers have been certified
The temperature of the air surround- For such conditions, it is generally for applications through UBC Zone
ing the enclosure should be within recommended that the switch- 4 and for the California Building
the limits of: gear be installed in a clean, dry Code. Assembly modifications are
room, with filtered and/or pressur- required, so such conditions must
–30° (–22°F) to +40°C (104°F). ized clean air. This method per- be specified.
mits the use of standard indoor
switchgear and avoids the 6. Abnormally high frequency of
derating effect of non-ventilated operation.
enclosures.
In line with above, a lesser
number of operations between
servicing, and more frequent
replacement of parts, may be
indicated.

CAT.71.01.T.E
Cutler-Hammer Circuit Breakers and Trip Units G1-17
January 1999 Low-Voltage Power Circuit Breakers – Magnum DS
Application Data

Application Maximum capabilities of transform- Generator Breakers


ers of various types, can be found in In most applications where genera-
Transformer Main Secondary section D2. It will be noted that the tors are connected through breakers
Breakers maximum ratings will often require to the secondary bus, they are used
Transformer secondary breakers are the substitution of larger frame main as emergency standby sources only,
required or recommended for one or breakers than those listed in the and are not synchronized or paral-
more of the following purposes: tables. Even if a self-cooled trans- leled with the unit substation trans-
former only is considered, it should formers. Under these conditions, the
1. To provide a one-step means
be remembered that with ratings of interrupting rating of the generator
of removing all load from the
750 kVA and higher, provision for the breaker will be based solely on the
transformer.
future addition of cooling fans is generator kVA and sub-transient
2. To provide transformer overload automatically included. It is recom- reactance. This reactance varies with
protection in the absence of an mended that the main breaker have the generator type and rpm, from a
individual primary breaker, and/or sufficient capacity for the future fan- minimum of approximately 9% for a
when primary fuses are used. cooled rating, plus an allowance for 2-pole 3600 rpm turbine driven gen-
overloads, if possible, particularly erator to 15% or 20% or more for a
3. To provide the fastest clearing of since load growth cannot always be medium or slow speed engine type
a short circuit in the secondary predicted. generator. Thus the feeder breakers
main bus.
The same considerations should be selected for the unit substation will
4. To provide a local disconnecting given to the main bus capacities and usually be adequate for a standby
means, in the absence of a local main current transformer ratios. generator of the same kVA as the
primary switch or breaker, for transformer.
maintenance purposes. Bus Sectionalizing (Tie) Breakers
Most generators have a 2-hour 25%
The minimum recommended contin-
5. For automatic or manual transfer overload rating, and the generator
uous current rating of bus sectional-
of loads to alternate sources, as in
double-ended secondary selective
izing or tie breakers, as used in
breaker must be adequate for this
overload current. Selective type long
G
double-ended secondary selective
unit substations. and short delay trip protection only
unit substations, or for connecting
is usually recommended for coordi-
6. For simplifying key interlocking two single-ended substations, is
nation with the feeder breakers,
with primary interrupter switches. one-half that of the associated main
with the long delay elements set
breakers. The interrupting rating
7. To satisfy NEC service entrance at 125% to 150% of the maximum
should be at least equal to that of the
requirements when more than six generator current rating for
feeder breakers. It is common prac-
feeder breakers are required. generator protection.
tice to select the tie breaker of the
Main secondary breakers, must have next frame size below that of the In the case of two or more paralleled
adequate interrupting ratings, but main breakers. However, many users generators, anti-motoring reverse
not necessarily adequate continu- and engineers prefer that the tie power relays (device 32) are recom-
ous current ratings. They should be breaker be identical to and inter- mended for protection of the prime
able to carry continuously not only changeable with the main breakers, movers, particularly piston type
the anticipated maximum continu- so that under normal conditions it engines. For larger generators
ous output of the transformer but will be available as a spare main requiring a Magnum MDS-632, DSII-
also any temporary overloads. breaker. 632 or larger, voltage-restraint type
overcurrent relays (device 51V) are
For a fully selective system, instanta- In general, the tie breaker, like the
recommended.
neous protection on main breakers main breaker, trip unit should have
should be defeated, as they typically its instantaneous tripping defeated.
cannot be coordinated with down-
stream devices.

CAT.71.01.T.E
G1-18 Circuit Breakers and Trip Units
Cutler-Hammer
Low-Voltage Power Circuit Breakers – Magnum DS January 1999

Application Data

Application conditions without requiring replace- Zone selective interlocking is a com-


ment of parts, for the various breaker munication signal between trip units
Feeder Breakers – General frame sizes. applied on upstream and down-
Circuit breakers for feeder circuit stream breakers. Each trip unit must
For motor starting duty, with closing
protection may be manually or elec- be applied as if zone selective inter-
starting currents up to 600% and
trically operated, with long and short locking were not employed, and set
opening running currents up to 100%
delay or long delay and instanta- for selective coordination.
of the breaker frame size, at 80%
neous type trip devices, and trip set-
power factor or higher, the endur- During fault conditions, each trip unit
tings, as required for the specific
ance or total operations (not requir- which senses the fault sends a
circuit and load requirements.
ing parts replacement) will be as restraining signal to all upstream trip
Feeder breakers as selected in Tables follows: units. This restraining signal results
A1 through A4 have adequate inter- in causing the upstream trip to con-
800A Frame: 1400
rupting ratings, and are assumed to tinue timing as it is set. In the
1600A Frame: 400
have adequate continuous current absence of a restraining signal, the
ratings for maximum load demands. The frequency of operation should trip unit trips the associated breaker
not exceed 20 starts in 10 minutes or with no intentional time delay, mini-
General purpose feeder breakers,
30 in one hour. mizing damage to the fault point.
such as for lighting circuits, are usu-
This restraining signal is a very low
ally equipped with long delay and Group Motor Feeder Breakers level. To minimize the potential for
instantaneous trip devices, with the Typical loads for such circuits are induced noise, and provide a low
long delay pickup set for the maxi- motor control centers. The feeder impedance interface between trip
mum load demand in the circuit. breakers may be either manually or units, a special secondary connector
Where arcing fault protection is electrically operated as preferred, is added to the DSII breaker, and
required, the instantaneous trip set- and are usually equipped with long twisted pair conductors are utilized
ting should be as low as practicable and short delay trip protection only
G consistent with inrush requirements. for coordination with the individual
for interconnection. For this reason,
zone selective interlocking must be
Motor Starting Feeder Breakers motor circuit devices. The minimum specified.
long delay pickup setting should be
These breakers are usually electri- Ground fault and short delay pickup
115% of the running current of the
cally operated, with long delay and on Digitrip Trip Units may be speci-
largest motor in the group, plus the
instantaneous tripping characteris- fied with zone selective interlocking.
sum of the running circuits of all
tics for motor running, locked rotor Since most system faults start as
other motors.
and fault protection. The breaker arcing ground faults, zone selective
sensor rating should be chosen so Zone Selective Interlocking interlocking on ground fault pickup
that the long delay pickup can be set By definition, a selectively coordi- only is usually adequate. Zone selec-
at 125% of motor full load current for nated system is one where by adjust- tive interlocking on short delay
motors with a 1.15 service factor, or ing trip unit pickup and time delay pickup may be utilized where no
at 115% for all other motors. Contac- settings, the circuit breaker closest to ground fault protection is provided.
tors are recommended for this appli- the fault trips first. The upstream
cation when there are a number of Zone selective interlocking may be
breaker serves two functions: (1)
daily operations involved. applied as a type of bus differential
back-up protection to the down-
protection. It must be recognized,
When system short circuits are less stream breaker and (2) protection
however, that one must accept the
than 40 times the motor full load cur- of the conductors between the
minimum pickup of the trip unit for
rent, the motor breaker tripping char- upstream and downstream break-
sensitivity.
acteristic should include a short ers. These elements are provided for
delay characteristic for greater fault on Digitrip trip units. It must also be recognized that not
protection. all systems may be equipped with
For faults which occur on the con-
zone selective interlocking. Systems
Repetitive Duty ductors between the upstream and
containing multiple sources, or
downstream breakers it is ideally
Repetitive breaker opening and clos- where the direction of power flow
desirable for the upstream breaker to
ing, such as in frequent motor start- varies, require special consider-
trip with no time delay. This is the
ing and stopping, are covered by ations, or may not be suitable for this
feature provided by zone selective
ANSI Standards C37.13 and C37.16. feature. Digitrip zone interlocking
interlocking. Digitrip trip units may
These Standards list the number of has been tested with up to three lev-
be specified to utilize this option.
operations between servicing els with up to 20 trip units per level.
(adjusting, cleaning, lubrication,
tightening, etc.) and the total num-
bers of operations under various

CAT.71.01.T.E
Cutler-Hammer Circuit Breakers and Trip Units G1-19
January 1999 Low-Voltage Power Circuit Breakers – DSII
Application Data

Type DSII Breaker Sensor Selection Guide for Resistance Welding Applications These welding applications are
based on long delay and instanta-
neous trip devices with the following
Sensor Rating, settings. The long time delay setting
Amperes is based on the weld amperes and
15000 duty cycle. Instantaneous trip setting
40
00 is two times the average weld
32
10000 00 amperes (weld amperes times per-
24
cent duty cycle) or higher.
00
20
00
10
5000 00
During-Weld Amperes (RMS)

12
00

80
0

60
2000 0

40
0
30
0

20
0

500 15
0 G
10
0
200

100
3 4 5 6 7 8 9 10 20 30 40 50 60
Percent Duty Cycle

Resistance Welding The size of the thermal memory is


The application of DSII circuit break- 30 T (In / In)2 unit Amperes2 seconds.
ers to resistance welding circuits is It fills at a rate of (iw / In)2 unit
shown on the Sensor Selection Amperes2 seconds/second, trips at
Guide above. Sensor ratings only 30T seconds, and empties at the rate
are given; the breaker frame must be of (In / In)2 unit Amperes2 seconds/
selected as required for interrupting second, where
ratings. T = Long Time Delay Setting in sec-
The DSII Digitrip microprocessor- onds (range is 2-24 seconds)
based true RMS sensing devices iw = RMS value of the welding
have a thermal memory and are well current in amperes
suited for this service. The thermal
memory functions to prevent In = Rating plug current value in
exceeding the breaker and cable amperes
maximum permissible thermal The memory is filled during the weld
energy level. The circuit also repli- and empties during the non-welding
cates time dissipation of thermal period of the duty cycle.
energy.

CAT.71.01.T.E
G1-20 Circuit Breakers and Trip Units
Cutler-Hammer
Low-Voltage Power Circuit Breakers – Magnum DS January 1999

Typical Specifications

Power Circuit Breakers – G. Main power circuit breakers shall breaker shall consist of a set of
be provided with trip units as contacts extending to the rear
Magnum DS specified in pararaph [2.03 ____ through a glass polyester insulat-
A. [Main] [Tie] protective devices through ____]. ing support barrier; correspond-
shall be [fixed] [drawout] low- ing moving fringe contacts
H. Tie power circuit breakers shall
voltage power air-circuit break- suitably spaced shall be furnished
be provided with trip units as
ers, Cutler-Hammer type Mag- on the power circuit breaker studs
specified in paragraph [2.03 ____
num DS or approved equal. which engage in only the con-
through ____].
Frame ratings shall be 800, nected position. The assembly
1600, 2000, 3200, 4000, or 5000 I. [Main] [Tie] power circuit shall provide multiple silver-to-
amperes. All breakers shall be breakers, where indicated on the silver full floating high-pressure
UL listed for application in their drawings, shall include current point contacts with uniform pres-
intended enclosures for 100% of limiters. Limiters shall be inte- sure on each finger maintained by
their continuous ampere rating. grally mounted on 800-, 1600- springs.
and 2000-ampere breakers. For
B. Breakers shall be [manually 1. The secondary disconnecting
3200-ampere and 4000-ampere
operated (MO)] [electrically devices shall consist of floating
breakers, limiters shall be
operated (EO)] as indicated on fingers mounted on the remov-
mounted on a separate drawout
the drawings. able unit and engaging flat con-
limiter truck. Current limiters
tact segments at the rear of the
C. Electrically operated breakers shall be coordinated with the
compartment. The secondary
shall be complete with [120 Vac] breaker trip device, so as to avoid
disconnecting devices shall be
[48 Vdc] [125 Vdc] operators, unnecessary blowing of the
silver-plated and sliding contact
[close/open pushbuttons] [control current limiters. Breakers shall
engagement shall be main-
switch], plus red and green indi- include an anti-single-phase
tained in the “connected” and
cating lights to indicate breaker device that will trip the breaker
G contact position. [DC source shall in the event of a blown limiter,
“test” positions.

be supplied from a remote bat- indicate from the front of the 2. The removable power circuit
tery system] [AC source shall be breaker which limiter is blown, breaker element shall be
taken from a (remote source) and prevent the breaker from equipped with disconnecting
(control power transformer inter- being re-closed on a single-phase contacts and interlocks for
nal to the switchgear assembly)]. condition due to missing or drawout application. It shall
blown limiters. have four positions, CON-
D. All circuit breakers shall have a NECTED, TEST, DISCON-
minimum symmetrical interrupt- 1. Current limiters which are inte-
NECTED, and REMOVED. The
ing capacity of [42,000] [65,000] grally mounted with breaker
breaker drawout element shall
[85,000] [100,000] [200,000] shall be inaccessible until the
contain a worm gear levering
amperes. To assure a fully selec- breaker is completely with-
“in” and “out” mechanism with
tive system, all circuit breakers drawn from its compartment
removable lever crank. Lever-
shall have 30 cycle short-time assuring complete isolation.
ing shall be accomplished via
withstand ratings equal to their Current limiters mounted on a
the use of conventional tools.
symmetrical interrupting ratings separate fuse truck shall be key
Mechanical interlocking shall
through 85,000 amperes, regard- interlocked with the breaker to
be provided so that the breaker
less of whether equipped with prevent withdrawing or inser-
is in the tripped position before
instantaneous trip protection or tion unless the breaker is
levering “in” or “out” of the
not. locked open.
cell. The breaker shall include a
E. Where circuit breakers are 2. Power circuit breakers with provision for padlocking open
equipped with current limiters, current limiting fuses shall to prevent manual or electric
the combination shall have short- have a 200,000-ampere RMS closing. The padlocking shall
time ratings in accordance with symmetrical interrupting have a provision for securing
the characteristics of the limiter capacity at 600 volts and below. the breaker in the connected,
selected. test, or disconnected position
J. For drawout applications the by preventing levering.
F. All ratings shall be tested to the breaker cell shall be equipped
requirements of ANSI C37.20.1, with drawout rails and primary Insert applicable trip unit specifica-
C37.50 and C37.51 and UL wit- and secondary disconnecting tion from section G3.
nessed and approved. contacts. The stationary part of
the primary disconnecting
devices for each power circuit

CAT.71.01.T.E
Cutler-Hammer Circuit Breakers and Trip Units G1-21
January 1999 Low-Voltage Power Circuit Breakers – DSII
Typical Specifications

Power Circuit Breakers – G. Main power circuit breakers shall through a glass polyester insulat-
be provided with trip units as ing support barrier; correspond-
DS II specified in section G3. ing moving fringe contacts
A. [Main] [Tie] protective devices suitably spaced shall be furnished
H. Tie power circuit breakers shall
shall be [drawout] [fixed] insu- on the power circuit breaker studs
be provided with trip units as
lated case circuit breakers, Cutler- which engage in only the con-
specified in section G3.
Hammer type – DS II or approved nected position. The assembly
equal. Frame ratings shall be 800, I. [Main] [Tie] power circuit break- shall provide multiple silver-to-sil-
1200, 1600, 2000, 3000, or 4000 ers, where indicated on the draw- ver full floating high-pressure
amperes. All breakers shall be ings, shall include current point contacts with uniform pres-
UL listed for application in their limiters. Limiters shall be inte- sure on each finger maintained by
intended enclosures for 100% of grally mounted on 800-, 1600- springs.
their continuous ampere rating. and 2000-ampere breakers. For
1. The secondary disconnecting
3200-ampere and 4000-ampere
B. Breakers shall be [manually devices shall consist of floating
breakers, limiters shall be
operated (MO)] [electrically fingers mounted on the remov-
mounted on a separate drawout
operated (EO)] as indicated on able unit and engaging flat con-
limiter truck. Current limiters
the drawings. tact segments at the rear of the
shall be coordinated with the
compartment. The secondary
C. Electrically operated breakers breaker trip device, so as to avoid
disconnecting devices shall be
shall be complete with [120 Vac] unnecessary blowing of the cur-
silver-plated and sliding con-
[48 Vdc] [125 Vdc] operators, rent limiters. Breakers shall
tact engagement shall be main-
1[close/open pushbuttons] [con- include an anti-single-phase
tained in the “connected” and
trol switch], plus red and green device that will trip the breaker in
“test” positions.
indicating lights to indicate the event of a blown limiter, indi-
breaker contact position. [DC cate from the front of the breaker 2. The removable power circuit
source shall be supplied from a which limiter is blown, and breaker element shall be G
remote battery system] [AC prevent the breaker from being equipped with disconnecting
source shall be taken from a re-closed on a single-phase contacts, wheels and interlocks
(remote source) (control power condition due to missing or for drawout application. It shall
transformer internal to the blown limiters. have four (4) positions: CON-
switchgear assembly)]. NECTED, TEST, DISCON-
1. Current limiters which are inte-
NECTED, and REMOVED all of
D. All circuit breakers shall have a grally mounted with breaker
which permit closing the com-
minimum symmetrical interrupt- shall be inaccessible until the
partment door. The breaker dra-
ing capacity of [42,000] [65,000] breaker is completely with-
wout element shall contain a
[85,000] [100,000] [200,000] drawn from its compartment
worm gear levering “in” and
amperes. To assure a fully selec- assuring complete isolation.
“out” mechanism with remov-
tive system, all circuit breakers Current limiters mounted on a
able lever crank. Mechanical
shall have 30 cycle short-time separate fuse truck shall be key
interlocking shall be provided
withstand ratings equal to their interlocked with the breaker to
so that the breaker is in the
symmetrical interrupting ratings prevent withdrawing or inser-
tripped position before levering
through 85,000 amperes, regard- tion unless the breaker is
“in” or “out” of the cell. The
less of whether equipped with locked open.
breaker shall include a provi-
instantaneous trip protection or sion for padlocking open to pre-
2. Power circuit breakers with cur-
not. vent manual or electric
rent limiting fuses shall have a
E. Where circuit breakers are 200,000-ampere RMS symmet- closing. The padlocking shall
equipped with current limiters, rical interrupting capacity at also secure the breaker in the
the combination shall have short- 600 volts and below. connected, test or disconnected
time ratings in accordance with position by preventing levering.
J. For drawout applications the
the characteristics of the limiter
breaker cell shall be equipped Insert applicable trip unit specifica-
selected.
with drawout rails and primary tion from section G3.
F. All ratings shall be tested to the and secondary disconnecting
requirements of ANSI C37.20.1, contacts. The stationary part of
C37.50 and C37.51 and UL wit- the primary disconnecting
nessed and approved. devices for each power circuit For a complete product specifica-
breaker shall consist of a set of tion in CSI format, see Cutler-
contacts extending to the rear Hammer Products Specification
Guide, section 16475.

CAT.71.01.T.E
G1-22 Circuit Breakers and Trip Units
Cutler-Hammer
Low-Voltage Power Circuit Breakers – DSII January 1999

This page intentionally left blank.


G

CAT.71.01.T.E

You might also like