Professional Documents
Culture Documents
Index Page ➂ ➀ ➁
General Description –
Magnum DS . . . . . . . . . . . . . G1-1
General Description – ➃
DSII/DSLII. . . . . . . . . . . . . . . G1-7
Technical Data – Magnum DS . G1-11 ➄
Technical Data – DSII/DSLII . . G1-12
➅
Application Data – Magnum DS
and DSII/DSLII . . . . . . . . . . . G1-16 ➆
Typical Specifications . . . . . . . G1-20
Magnum DS Breakers are power ➇
circuit breakers designed and engi-
neered specifically for use in Mag- ➈
num DS Low Voltage Switchgear
assemblies applied at nominal volt- ➉
ages of 240, 480, and 600 Vac. Six
continuous ratings – 800 amperes k
through 5000 amperes – are covered
by only two physical breaker sizes. l
Controls and indicators are function-
ally grouped on the front of the
breakers and the through-the-door
design means they are easily viewed
and accessible.
➀ Trip Flag
G
➁ Three Accessory Windows
➂ Digitrip RMS Trip Unit
➃ Contact Status Indicator (Open or
Closed)
➄ Spring Status Indicator (Charged
or Discharged)
➅ “Push Off” to Open Breaker Button
➆ “Push On” to Close Breaker Button
➇ Manual Charging Handle The breaker can be conveniently racked
in or out, stopping at the various posi-
➈ Optional Operations Counter tions with the door closed.
Integrally designed breaker steel cassette for
➉ Optional “Off” Key Lock drawout breakers provides clear indication of
connect, test, and disconnect positions.
k Padlockable Levering Device
l Color-Coded Breaker Position
Indicators
Magnum DS Breakers are 100 per-
cent rated, UL listed, and are built
and tested in an ISO 9000 certified
facility to applicable standards
including:
■ ANSI C37.13 ■ NEMA SG3
■ ANSI C37.16 ■ UL 1066
■ ANSI C37.17 ■ CSA 22.2
■ ANSI C37.50 Faceplate controls facilitate operation of
Magnum DS is also suitable for use in: the breaker, and the three accessory
mounting windows provide for easy The breaker spring charging handle is de-
■ UL 1558 Low Voltage Switchgear identification. signed with sufficient space for operation
■ UL 891 Low Voltage Switchboards even with a gloved hand.
■ CSA 22.2.31 Low Voltage
Assemblies
CAT.71.01.T.E
G1-2 Circuit Breakers and Trip Units Cutler-Hammer
Low-Voltage Power Circuit Breakers – Magnum DS January 1999
General Description
CAT.71.01.T.E
Cutler-Hammer Circuit Breakers and Trip Units G1-3
January 1999 Low-Voltage Power Circuit Breakers – Magnum DS
General Description
Flexible Current Path As the circuit breaker is called upon Isolated View of Contact Opening
to open, the toe and heel simulta- Sequence
Increases Current Carrying neously touch. At that point, the cur-
Capability in Less Space rent changes its path from the main
■ Multi-finger contact structure contact to the arcing contact. As the
divides the current flow, increas- heel lifts off, any remaining current
ing the thermal carrying capability is driven to the toe. The result is
minimal arcing damage to the main
contact (heel) providing for longer
main contact life.
Upon closing, the toe absorbs most 1. Fully Closed Position
of the impact and deals with any arc- Only the main contact (heel) touches and
ing by touching down before the all current flow is through the main contact.
heel. Once again, the main contact
(heel) is protected resulting in longer
life.
Visual contact wear indicator shows
when contact replacement is necessary.
Arc Running System
■ Flexible braided current path to
the contact fingers reduces neces-
Provides Higher Interrupting
sary current carrying space and Capacity in Less Space
provides a smooth connection, ■ Heel-toe contact structure is a
eliminating bolted joints and con- 2. Simultaneous Touching of All
single contact finger design that Contacts
tact springs. This design helps performs both main and arcing The arcing contact (toe) touches down be-
increase breaker service life by
reducing localized heat buildup
contact functions by controlling fore the main contact (heel) lifts off with G
the arc direction. This design pro- current flow dividing between main (heel)
and mechanical stress inherent in
HH
ÈÈ
FÆF
GG
Æ
ÇÇ
and arcing (toe) contacts.
zzzz
,,,
yyy
vides for longer contact life.
conventional bolted joints.
■ Integral arc runner enhances the
Cross-Section of Magnum DS magnetic action of the arc chute
|{,y
{ |||
{{{
{
z
|
Heel-Toe Contact
by drawing the arc into the chute
with increased efficiency, reduc-
{,yz|,y{{ z
|
Arc
Chute ing arcing at the toe of the con-
Moving
Arcing
tacts. This exclusive design allows
Contact Integral for higher arcing in a smaller
z
y
,
|
(Toe) Arc Runner
Stationary space, resulting in increased inter-
Moving Main Contact
Contact rupting ratings. Alternating V Arc 3. Toe (Arcing) Contacts Touching
Fingers
{|z z,
y , |
Current Chute™ quickly divides and extin-
Moving Flow The main contact (heel) lifts off with the
Main guishes the arc. The V Arc Chute arcing contact (toe) still touching to deal
Contact Line
Conductor reaction speed protects contact with any arcing. Current flow is only
z,{
,,
zz
yy
|
,y{|
(Heel) XXXXXXX
X X
Moving
X X
XXXXXXX
Load material, extending contact life. through the arcing contact (toe).
Contact Conductor
Carrier Current
Flow
Braided XXXXXXX
Flexible X
X
X
X
Contact
Shunts XXXXXXX Sensor
Breaker
Front
CAT.71.01.T.E
G1-4 Circuit Breakers and Trip Units Cutler-Hammer
Low-Voltage Power Circuit Breakers – Magnum DS January 1999
General Description
Rigid Frame Housing Built-in Safety Features ■ Connect. Both main and second-
ary contacts are connected and
The Magnum DS Breaker utilizes a Provide Optimum Operator the breaker is ready for normal
rigid frame housing – an ANSI Safety and System Security operation.
power breaker exclusive. This
■ Improved C-loop current path ■ Test. Main disconnects are disen-
housing provides the strength and
design provides dramatic gaged, secondary contacts are
stability required in the mounting of
improvements in both safety and engaged. All functions of the
the current path and operating
efficiency. Higher current ratings breaker and trip unit can be tested
mechanism.
increase the blow-on forces on in this position.
■ Increased Uptime. Because the the contact surfaces, allowing the ■ Disconnect. A storage position in
current path is isolated and insu- proper downstream protective the compartment but the breaker
lated inside a two-piece inter- device to open, isolating the fault is open and disconnected.
connected housing, any potential and increasing uptime.
damage that may occur during Positive on is indicated on the
arc interruption between the
■
Quality and Reliability
breaker faceplate. This unique
poles or outside of the breaker is interlocking feature prevents the Cutler-Hammer performs consistent
minimized. levering door from being opened endurance and reliability tests on
■ Increased Breaker Life. By provid- if the contacts are welded, pro- Magnum DS Breakers.
ing rigid support for the operating tecting personnel from exposure
■ Mini-Life Tests. A breaker is ran-
mechanism and the contact struc- to live primary contacts.
domly selected from the produc-
ture, mechanical stress is Making current release prevents
■ tion line daily, and tested for an
reduced, increasing reliability. the breaker from closing in on average of 50 mechanical opera-
■ Design Reliability. The housing a fault exceeding 15 times the tions to assure performance as
reduces the number of frame nominal current. required.
G parts in comparison with conven- ■ Keyed sensor plug insures error- ■ Maxi-Life Tests. MTBF testing
tional ANSI power breakers, pro- free installation of the sensor in continuously tests Magnum DS
viding increased reliability. the field. Breakers until they fail. This iden-
■ Rigid Frame. The engineered ther- ■ Deadfront faceplate isolates the tifies potential performance
moset composite resin provides operator from the primary voltage issues with the breaker and
excellent structural properties, when the breaker is energized. provides statistical analysis for
dielectric strength, and arc track further improvement.
resistance helping to provide the ■ Anti-pump prevents any attempts
higher interrupting and short time to reclose the breaker on a short
(withstand) ratings in a smaller circuit fault if the close signal
size. (mechanical or electrical) is
maintained.
■ Interlocked levering door cannot
be opened until the contacts are
in the open condition.
■ Three position indicators on the
faceplate for drawout mounting.
Specific colors identify the
breaker position.
CAT.71.01.T.E
Cutler-Hammer Circuit Breakers and Trip Units G1-5
January 1999 Low-Voltage Power Circuit Breakers – Magnum DS
Accessories
Internal Accessories
■ Auxiliary Switch – Provides the
capability to remotely indicate if
the breaker is open or closed. Up
to six normally open and six nor-
mally closed auxiliary contacts
are available for customer use.
The auxiliary switch is an internal acces-
■ Overcurrent Trip Switch (Bell sory that provides remote electrical indi-
Alarm) – A set of normally open cation if the breaker is open or closed.
CAT.71.01.T.E
G1-6 Circuit Breakers and Trip Units Cutler-Hammer
Low-Voltage Power Circuit Breakers – Magnum DS January 1999
Trip Units
CAT.71.01.T.E
Cutler-Hammer Circuit Breakers and Trip Units G1-7
January 1999 Low-Voltage Power Circuit Breakers – DSII
General Description
CAT.71.01.T.E
G1-8 Circuit Breakers and Trip Units Cutler-Hammer
Low-Voltage Power Circuit Breakers – DSII January 1999
General Decription
Molded Base
Moving
Arcing
Stationary Main Contact
Contact Fingers
Moving Contact
Assembly
Insulating
Link
Main Disconnecting
Insulating Link
Contacts
Lock Nut Sensors
CAT.71.01.T.E
Cutler-Hammer Circuit Breakers and Trip Units G1-9
January 1999 Low-Voltage Power Circuit Breakers – DSII
General Description
Type DSLII Limiter Type currents beyond the breaker rating, identifying the blown fuse and (2)
up to a maximum of 200,000 picks up a solenoid which raises the
Air Circuit Breakers amperes symmetrical. Thus, on breaker trip bar, holding the breaker
Application overloads and faults within the mechanically trip-free.
Type DSLII breakers are coordinated breaker interrupting rating, the
The DSLII-632 and DSLII-840 combi-
combinations of Type DSII breakers breaker protects the limiters; on
and series connected current limit- higher fault currents exceeding the
nations with separately mounted
limiters operate on the same princi-
G
ers. They are intended for applica- breaker rating, the limiters protect
ple except that the solenoid operates
tions requiring the overload the breaker.
a micro-switch which trips the
protection and switching functions Protection Against Single Phasing breaker electrically through a shunt
of air circuit breakers on systems trip coil.
Loads are protected against single
whose available fault currents
phase operation by interlock arrange- Safety Features
exceed the interrupting rating of the
ments which trip the circuit breaker
breakers alone, and/or the withstand The integral fuses on Types DSLII-
whenever any one limiter blows. The
ratings of “downstream” circuit 308, DSLII-516, and DSLII-620 break-
breaker cannot be reclosed on a live
components. ers are inaccessible until the breaker
source until there are three unblown
is completely withdrawn from its
Sizes and Arrangements limiters in the circuit.
compartment, thereby assuring
Types DSLII-308 (800 ampere), On the Types DSLII-308, DSLII-516, complete isolation.
DSLII-516 (1600 ampere), and DSLII- and DSLII-620 breakers, the prima-
620 (2000 ampere) frame breakers Likewise, the Types DSLII-632 and
ries of small auxiliary transformers
include the limiters integrally DSLII-840 fuses are inaccessible
are connected in parallel with the
mounted on the drawout breaker until the separate fuse truck is
limiters. The voltage between the
elements in series with the upper completely withdrawn and the fuses
ends of an unblown limiter is zero,
terminals. isolated. The fuse truck is key inter-
but when any limiter blows, the
locked with the breaker to prevent
Current limiters used in Types DSLII- associated transformer is energized
withdrawal or insertion unless the
632 and DSLII-840 combinations are and (1) operates an indicator
breaker is locked open.
mounted on separate drawout
trucks in an additional equal size Table 1 – Interrupting Ratings of Type DSLII Breakers
compartment. Type DSLII-308 DSLII-516 DSLII-620 DSLII-632 DSLII-840
Scope of Fault Interruption Frame Size, Amperes 800 1600 2000 3200 4000
With properly selected and coordi- Maximum Interrupting Rating, 200,000 200,000 200,000 200,000 200,000
RMS Symmetrical Ampere,
nated limiters, it is expected that the System Voltage 600 or Below
breaker itself will clear overloads
and faults within its interrupting
rating, leaving the limiters intact
and undamaged. The limiters will
provide fast interruption of fault
CAT.71.01.T.E
G1-10 Circuit Breakers and Trip Units
Cutler-Hammer
Low-Voltage Power Circuit Breakers – DSII January 1999
Accessories/Trip Units
Optional Breaker (f) Electric Lockout (optional on equipment. The primary function of
manual breakers). In order to the Digitrip electronic trip unit is to
Attachments and Accessories close the breaker after manually provide circuit protection. This is
(a) Shunt trip on manually operated charging the closing mechanism, achieved by analyzing the secondary
breakers, for any standard con- it is necessary to operate an elec- current signals received from the
trol voltage. trical pushbutton on the breaker circuit breaker current sensors and
faceplate. This pushbutton is initiating trip signals to the circuit
(b) Auxiliary contacts on manually or wired-out to the secondary con- breaker trip unit when pre-set cur-
electrically operated breakers. tacts so it may be wired in series rent levels and time delay settings
Maximum of 5 normally open with any required external inter- are exceeded. By sampling the cur-
and 5 normally closed contacts locking. The mechanical “push- rent waveform at various points on
are available on any breaker, to-close” bar is made inoperative the wave and calculating true RMS
manually or electrically oper- when the breaker is in the con- current, the Digitrip is able to reduce
ated. The contact rating is 10 nected position. nuisance tripping events due to non-
amperes. sinusoidal wave shapes.
(g) Electric close release on manu-
(c) Compartment position switch, ally operated breakers, for any Electronic trip units are applied to
6 or 12 contact, actuated by standard control voltage. Breaker distribution systems when high
movement of drawout breaker can be closed by remote control standards of protection and coordi-
between the connected and test switch or pushbutton after the nation are called for. In addition,
positions. Most common uses closing spring is manually electronic trip units can provide fur-
are for disconnecting remote charged. ther enhanced features such as
control circuits of electrically alarming, diagnostics, system moni-
operated breaker, and for bypass- (h) Operation counter.
toring and communications.
ing “b” interlocking auxiliary
(i) Latch check switch.
contacts, when breaker is with- Cutler-Hammer RMS sensing trip
G drawn to test position. units for power breakers fall into two
Electronic Trip Units main categories:
(d) Undervoltage trip (ac and dc
available). Acts to trip the breaker Cutler-Hammer offers the most com- ■ Front adjustable trip units: Digitrip
when the voltage on its solenoid prehensive range of electronic trip RMS 510, 610, 810, 910
coil is insufficient to restrain a units in the industry for power circuit
■ Programmable trip units: Digitrip
spring-loaded core. The dropout breakers.
OPTIM 750, 1050
point is within 30 to 60 percent of Digitrip electronic trip units are ac
the nominal coil voltage and is For additional information on trip
devices that employ microproces-
not adjustable. Available as units see section G3
sor-based technology that provides
either instantaneous or time a true RMS current sensing means
delay type. The time delay is for proper correlation with thermal
within 2 to 7 seconds after zero characteristics of conductors and
voltage occurs, and is not adjust-
able. The device automatically Standard Control Diagram for Type DSII Electrically Operated Breaker,
resets when the breaker opens; for Ac or Dc Control Source.
approximately one minute is
Legend
required for resetting of the time LS — Limit Sw. for Closing Spring CS (or PB)
CS (or PB)
delay type. MOT — Motor for Spring Charging Close Ind. G Trip
R
SH TR — Shunt Trip Lts.
(e) Overcurrent trip switch (OTS). SR — Spring Release
Y — Anti-Pump Relay
A latching type switch with two
independent contacts either nor- Description of Operation
1 – Motor is energized through LS contact.
mally open or normally closed. 2 – Motor runs and charges Closing Spring. SR MOT SHTR
Operates only when the breaker 3 – When Closing Spring fully charged, LS
contacts reverse.
is tripped automatically on an 4 – CIosing CS-C contact energizes SR Coil Y
overload or fault condition. It through Y, LS & “b” contacts.
5 – When Breaker closes, “b” opens and Y Y LS LS
may be used for alarm and/or
Coil is energized in series with SR Coil.
interlocking circuits. Resetting is 6 – Y contact opens to open SR Coil circuit & b b a
done by a pushbutton on the prevent pumping should breaker open
breaker faceplate, or by a remote while CS-C is held closed. Y Coil has very
low drop-out voltage.
switch through an optional reset 7 – LS contacts reverse and motor recharges
coil. closing springs.
CAT.71.01.T.E
Cutler-Hammer Circuit Breakers and Trip Units G1-11
January 1999 Low-Voltage Power Circuit Breakers – Magnum DS
Technical Data
Table 3 – Available Sensor Ratings and Table 4 – Digitrip RMS Adjustable Trip Settings
Rating Plugs for Digitrip RMS➁ Time/Current Pickup Setting Pickup Point Time Band, Seconds
Breaker
Frame
Available Ratings
Characteristics (see note)
G
Long Delay 0.4, 0.5, 0.6, 0.7, 0.8 In Times 2, 4, 7, 10, 12, 15, 20, 24
800 200, 250, 300, 400, 600, 800 0.9, 0.95, 1.0 Long Delay Setting (at 6 times pickup value)
1600 200, 250, 300, 400, 600, 800, 1000, Instantaneous Off, 2, 3, 4, 6, 10 In Times
1200, 1600 M1 Instantaneous Setting
2000 200, 250, 300, 400, 600, 800, 1000, Short Delay 2, 2.5, 3, 4, 6, 8, 10 Ir Times 0.1, 0.2, 0.3, 0.4, 0.5
1200, 1600, 2000 M1 Short Delay Setting (Flat Response)
0.1*, 0.3*, 0.5*
3200 2500, 3000, 3200 *(I2t Response)
4000 3200, 4000 Ground Fault 0.25, 0.3, 0.35, 0.4, In Times 0.1, 0.2, 0.3, 0.4, 0.5
5000 3200, 4000, 5000 0.5, 0.6, 0.75, 1.00 Ground Fault Setting (Flat Response)
(1200A Maximum) 0.1*, 0.3*, 0.5*
*(I2t Response)
Note: In = Rating Plug Value
Ir = Long Delay Pickup Setting Times In
CAT.71.01.T.E
G1-12 Circuit Breakers and Trip Units
Cutler-Hammer
Low-Voltage Power Circuit Breakers – DSII January 1999
Technical Data
D (.4), E (.5), F (.6), Ground Fault (Flat Response) DSII-308, DSLII-308, 800 200, 300, 400,
H (.75), K (1.0) Setting 0.1*, 0.3*, 0.5 DSII-508 or 600, 800
(1200A Maximum) *(I2t Response) DSII-608
Note: In= Rating Plug Value DSII-516, DSLII-516 1600 200, 300, 400,
Ir = Long Delay Pickup Setting x In or DSII-616 600, 800, 1200,
1600
DSII-620 2000 200, 300, 400,
Table 8 – Control Voltages and Currents 600, 800, 1200,
Control Voltage 48 Dc 125 Dc 250 Dc 120 Ac 240 Ac 1600, 2000
DSLII-620 2000 2000
Close current (SR), ampere 5.0 2.0 1.0 3.0 2.0 DSII-632, DSLII-632 3200 2400, 3200
Shunt trip current, ampere 5.0 2.0 1.0 2.0 1.0 DSII-840, DSLII-840 4000 3200, 4000
Spring charge motor ampere 7.5 3.0 1.5 3.0 1.5 DSII-850 5000 5000
Control voltage range: 38-56 100-140 200-280 104-127 208-254
Close – 28-56 70-140 140-280 60-127 208-254 Table 11 – Available Digitrip RMS Rating
Trip –
Plugs Marked 50/60 Hertz➁
Note: Motor currents are running currents; inrush is approximately 400%. Motor running time to charge
spring approximately 5 seconds. Sensor Ratings, Plug Rating in Amperes (In)
Amperes
CAT.71.01.T.E
Cutler-Hammer Circuit Breakers and Trip Units G1-13
January 1999 Low-Voltage Power Circuit Breakers – DSII
Technical Data
The following curves illustrate the Limiter Selection Minimum, recommended, and maxi-
ratings, melting time-current charac- The selection of a suitable limiter mum limiter sizes for Types DSLII-
teristics and current limiting, or let- rating for a given application is gen- 308, DSLII-516, and DSLII-620 break-
through characteristics, of limiters erally governed by a choice of the ers are given in the following table.
for Type DSLII breakers. following types of protection: Table 12
The let-through current for a given A. Maximum protection of “down- Breaker Sensor Limiter Rating, Amperes
limiter application is readily deter- Type Rating
stream” components. Type DSLII Amperes Minimum Recom- Maximum
mined by extending a vertical line ➀ mended ➂
breakers are often used for this ➁
from the applicable maximum avail- purpose even when the maximum
able symmetrical fault amperes at available fault currents are within DSLII-308 200 250 1200 2000
DSLII-308 300 400 1200 2000
the bottom margin to the character- the interrupting rating of the cor- DSLII-308 400 600 1200 2000
istic line for the particular limiter, responding Type DSII unfused DSLII-308 600 800 1200 2000
and from this intersection extending DSLII-308 800 1200 1600 2000
breakers. DSLII-516 600 800 2000 3000
a horizontal line to the left margin DSLII-516 800 1000 2000 3000
and reading the peak current. The B. Protection of the circuit breaker DSLII-516 1200 2000 2500 3000
withstand rating of any circuit ele- only. DSLII-516 1600 – 3000 –
DSLII-620 2000 – 3000 –
ments protected by the limiters Case A would tend to use the small-
should be at least equal to this peak est available limiter; Case B the larg- Table 13 – DSLII-632 and DSLII-840
current. est. When downstream protection is Available Limiters
It will be noted that the let-through required, the selection is usually a Breaker Type Available Limiters
current increases with the limiter compromise, since certain small lim-
DSLII-632 2500, 3000, 4000A
size or ampere rating; in other iters cannot be coordinated with the DSLII-840 2500, 3000, 4000, 5000A
words, the maximum current limit- breaker to avoid nuisance blowing
ing effect is obtained with the small- on overloads or small and moderate
est size. This effect is to be expected, short circuits. G
since the resistance decreases as the Table 14 – Sensor, Plug and Limiter Selection
rating increases. If the vertical line
DSII Sensor Plug Limiter Rating
from the bottom margin as Breakers Rating Rating (Applicable only to DSLII Breakers)
described in the previous paragraph
does not intersect the limiter charac- 308, 508, 608 200 100, 200 250, 300, 400, 600, 800, 1200, 1600, 2000
300 200, 250, 300 400, 600, 800, 1200, 1600, 2000
teristic line, it is indicated that the 400 200, 250, 300, 400 600, 800, 1200, 1600, 2000
available system fault current is 600 300, 400, 600 800, 1200, 1600, 2000
800 400, 600, 800 1200, 1600, 2000
below the “threshold” current of
that limiter, and it will offer no cur- 516, 616 200 100, 200 800, 1000, 1200, 1600, 2000, 2500, 3000
300 200, 250, 300 800, 1000, 1200, 1600, 2000, 2500, 3000
rent limiting effect. 400 200, 250, 300, 400 800, 1000, 1200, 1600, 2000, 2500, 3000
600 300, 400, 600 800, 1000, 1200, 1600, 2000, 2500, 3000
The current limiting principle is illus- 800 400, 600, 800 1000, 1200, 1600, 2000, 2500, 3000
trated below. 1200 600, 800, 1000, 1200 2000, 2500, 3000
1600 800, 1000, 1200, 1600 3000
la = The Available Peak Fault Current 620 200 100, 200 Not Applicable
tm=The Melting Time 300 200, 250, 300 Not Applicable
400 200, 250, 300, 400 Not Applicable
Ip = The Peak Let-Through Current 600 300, 400, 600 Not Applicable
800 400, 600, 800 Not Applicable
ta = The Arcing Time 1200 600, 800, 1000, 1200 Not Applicable
tc = The Total Interrupting (Clearing) 1600 800, 1000, 1200, 1600 Not Applicable
Time 2000➀ 1000, 1200, 1600, 2000➃. 3000➄
632 2400 1600, 2000, 2400 2500, 3000, 4000
3200 1600, 2000, 2400, 3000, 3200 2500, 3000, 4000
840 3200 1600, 2000, 2400, 3200 2500, 3000, 4000, 5000
4000 2000, 2400, 3200, 4000 2500, 3000, 4000, 5000
Ia 850 5000 3200, 4000, 5000 Not Applicable
Ip
tm ta
tc
➀ For use only when protection of downstream ➁ Lowest rating which can be coordinated with ➃ 2000 ampere is the only sensor available
equipment is required. Not completely breaker to minimize nuisance blowing. for DSLII-620.
coordinated with breaker to avoid nuisance ➂ Highest available ratings, for protection of ➄ 3000 ampere is the only limiter available
blowing. breaker only. for DSLII-620.
CAT.71.01.T.E
G1-14 Circuit Breakers and Trip Units
Cutler-Hammer
Low-Voltage Power Circuit Breakers – DSII January 1999
Technical Data
10,000
1000
2000
3000
4000
5000
6000
7000
8000
9000
100
200
300
400
500
600
700
800
900
70
80
90
1 2 3 4 5 6 7 8 9 10 20 30 40 50 60
1000 1000
900 900
800 800 400,000
700 700
600 600
500 500 300,000
400 400
300 300
200,000
200 Limiter Ampere Rating 200
AMPERE
250
300
400
600
800
1200
1600
2000
RATING
100 100 2000
90 90
80 80 100,000 1600
70 70 90,000
60 60 1200
80,000
50 50 800
70,000
40 40
ce
du
TIME IN SECONDS
20 20
o
TIME IN SECONDS
40,000
Pr
an
400
tc
ui
30,000
irc
10 10 300
C
9 9
nt
8 8 250
re
7 7
ur
C
6 6 20,000
ak
5 5
Pe
um
4 4
im
3 3
ax
M
2 2
10,000
9000
8000
1 1
.9 .9 7000
.8 .8
.7 .7 6000
.6 .6
5000
.5 .5
.4 .4 4000
.3 .3
3000
.2 .2
2000
.1 .1
.09 .09
.08 .08
.07 .07
.06 .06
.05 .05
2000
3000
4000
5000
6000
7000
8000
9000
10,000
20,000
30,000
40,000
50,000
60,000
70,000
80,000
90,000
100,000
200,000
.03 .03
.02 .02
AVAILABLE CURRENT, RMS SYMMETRICAL AMPERES
1000
2000
3000
4000
5000
6000
7000
8000
9000
200
400
500
600
700
800
900
10,000
1 2 3 4 5 6 7 8 9 10 20 30 40 50 60
Supersedes AD 36-783
dated April 1980
SCALE X 100 = CURRENT IN AMPERES
Ref. Curve No. 639771
Type DSL-206 Limiters – For DSL-206 and DSLII-308 Breakers
Supersedes AD 36-783 Let-Through Characteristics January 1997
dated April 1980
Type DSL-206 Limiters – For DSL-206 and DSLII-308 Breakers
Average Melting Time – Current Characteristics January 1997
DSLII-516 and DSLII-620 Average Melting Time-Current DSLII-516 and DSLII-620 Let-Through Characteristics
Characteristics
SCALE X 100 = CURRENT IN AMPERES
10,000
1000
2000
3000
4000
5000
6000
7000
8000
9000
400,000
100
200
300
400
500
600
700
800
900
70
80
90
1 2 3 4 5 6 7 8 9 10 20 30 40 50 60
1000 1000
900 900
800 800
700 700 300,000
600 600
500 500
400 400
AMPERE
200,000 RATING
300 300
3000
1600
100,000
100 100
90 90 90,000 1200
80 80
70 70
80,000 1000
60 60 70,000
800
50 50
MAXIMUM PEAK LET-THROUGH CURRENT, AMPS
60,000
40 40
50,000
e
uc
30 30
od
40,000
Pr
TIME IN SECONDS
20 20
TIME IN SECONDS
an
tc
ui
30,000
irc
C
nt
10 10
re
9 9
ur
8 8
C
7 7 20,000
ak
6 6
Pe
5 5
um
m
4 4
i
ax
M
3 3
2 2 10,000
9000
8000
7000
1 1
.9 .9 6000
.8 .8
.7 .7
5000
.6 .6
.5 .5
4000
.4 .4
.3 .3
3000
.2 .2
2000
.1 .1
.09 .09
.08 .08
.07 .07
.06 .06
.05 .05
1000
.04 .04
1000
2000
3000
4000
5000
6000
7000
8000
9000
10,000
20,000
30,000
40,000
50,000
60,000
70,000
80,000
90,000
100,000
200,000
.03 .03
.01 .01
300
70
80
90
100
1000
2000
3000
4000
5000
6000
7000
8000
9000
200
400
500
600
700
800
900
10,000
1 2 3 4 5 6 7 8 9 10 20 30 40 50 60
CAT.71.01.T.E
Cutler-Hammer Circuit Breakers and Trip Units G1-15
January 1999 Low-Voltage Power Circuit Breakers – DSII
Technical Data
DSLII-632 and DSLII-840 Average Melting Time-Current DSLII-632 and DSLII-840 Let-Through Characteristics
Characteristics
SCALE X 100 = CURRENT IN AMPERES
10,000
1000
2000
3000
4000
5000
6000
7000
8000
9000
100
200
300
400
500
600
700
800
900
70
80
90
1 2 3 4 5 6 7 8 9 10 20 30 40 50 60
1000 1000 400,000
900 Ampere Rating Limiter 900
800 800 AMPERE
2500
3000
4000
5000
700 700 RATING
600 600 300,000
500 500 5000
400 400 4000
300 300 200,000
3000
200 200 2500
100 100
90 90 100,000
80 80 90,000
70 70
80,000
60 60
50 50 70,000
ce
30 30
odu
40,000
Pr
TIME IN SECONDS
20 20
TIME IN SECONDS
an
tc
ui
30,000
irc
C
10 10
nt
9 9
re
8 8
ur
7 7
C
20,000
ak
6 6
Pe
5 5
um
4 4
im
ax
3 3
M
2 2 10,000
9000
8000
1 1 7000
.9 .9
.8 .8 6000
.7 .7
.6 .6 5000
.5 .5
4000
.4 .4
.3 .3
3000
.2 .2
2000
.1 .1
.09 .09
.08 .08
.07 .07
.06 .06
.05 .05
1000
.04 .04
1000
2000
3000
4000
5000
6000
7000
8000
9000
10,000
20,000
30,000
40,000
50,000
60,000
70,000
80,000
90,000
100,000
200,000
.03 .03
.02 .02
AVAILABLE CURRENT, RMS SYMMETRICAL AMPERES
.01 .01 G
300
70
80
90
100
1000
2000
3000
4000
5000
6000
7000
8000
9000
200
400
500
600
700
800
900
10,000
CAT.71.01.T.E
G1-16 Circuit Breakers and Trip Units
Cutler-Hammer
Low-Voltage Power Circuit Breakers – Magnum DS and DSII January 1999
Application Data
CAT.71.01.T.E
Cutler-Hammer Circuit Breakers and Trip Units G1-17
January 1999 Low-Voltage Power Circuit Breakers – Magnum DS
Application Data
CAT.71.01.T.E
G1-18 Circuit Breakers and Trip Units
Cutler-Hammer
Low-Voltage Power Circuit Breakers – Magnum DS January 1999
Application Data
CAT.71.01.T.E
Cutler-Hammer Circuit Breakers and Trip Units G1-19
January 1999 Low-Voltage Power Circuit Breakers – DSII
Application Data
Type DSII Breaker Sensor Selection Guide for Resistance Welding Applications These welding applications are
based on long delay and instanta-
neous trip devices with the following
Sensor Rating, settings. The long time delay setting
Amperes is based on the weld amperes and
15000 duty cycle. Instantaneous trip setting
40
00 is two times the average weld
32
10000 00 amperes (weld amperes times per-
24
cent duty cycle) or higher.
00
20
00
10
5000 00
During-Weld Amperes (RMS)
12
00
80
0
60
2000 0
40
0
30
0
20
0
500 15
0 G
10
0
200
100
3 4 5 6 7 8 9 10 20 30 40 50 60
Percent Duty Cycle
CAT.71.01.T.E
G1-20 Circuit Breakers and Trip Units
Cutler-Hammer
Low-Voltage Power Circuit Breakers – Magnum DS January 1999
Typical Specifications
Power Circuit Breakers – G. Main power circuit breakers shall breaker shall consist of a set of
be provided with trip units as contacts extending to the rear
Magnum DS specified in pararaph [2.03 ____ through a glass polyester insulat-
A. [Main] [Tie] protective devices through ____]. ing support barrier; correspond-
shall be [fixed] [drawout] low- ing moving fringe contacts
H. Tie power circuit breakers shall
voltage power air-circuit break- suitably spaced shall be furnished
be provided with trip units as
ers, Cutler-Hammer type Mag- on the power circuit breaker studs
specified in paragraph [2.03 ____
num DS or approved equal. which engage in only the con-
through ____].
Frame ratings shall be 800, nected position. The assembly
1600, 2000, 3200, 4000, or 5000 I. [Main] [Tie] power circuit shall provide multiple silver-to-
amperes. All breakers shall be breakers, where indicated on the silver full floating high-pressure
UL listed for application in their drawings, shall include current point contacts with uniform pres-
intended enclosures for 100% of limiters. Limiters shall be inte- sure on each finger maintained by
their continuous ampere rating. grally mounted on 800-, 1600- springs.
and 2000-ampere breakers. For
B. Breakers shall be [manually 1. The secondary disconnecting
3200-ampere and 4000-ampere
operated (MO)] [electrically devices shall consist of floating
breakers, limiters shall be
operated (EO)] as indicated on fingers mounted on the remov-
mounted on a separate drawout
the drawings. able unit and engaging flat con-
limiter truck. Current limiters
tact segments at the rear of the
C. Electrically operated breakers shall be coordinated with the
compartment. The secondary
shall be complete with [120 Vac] breaker trip device, so as to avoid
disconnecting devices shall be
[48 Vdc] [125 Vdc] operators, unnecessary blowing of the
silver-plated and sliding contact
[close/open pushbuttons] [control current limiters. Breakers shall
engagement shall be main-
switch], plus red and green indi- include an anti-single-phase
tained in the “connected” and
cating lights to indicate breaker device that will trip the breaker
G contact position. [DC source shall in the event of a blown limiter,
“test” positions.
be supplied from a remote bat- indicate from the front of the 2. The removable power circuit
tery system] [AC source shall be breaker which limiter is blown, breaker element shall be
taken from a (remote source) and prevent the breaker from equipped with disconnecting
(control power transformer inter- being re-closed on a single-phase contacts and interlocks for
nal to the switchgear assembly)]. condition due to missing or drawout application. It shall
blown limiters. have four positions, CON-
D. All circuit breakers shall have a NECTED, TEST, DISCON-
minimum symmetrical interrupt- 1. Current limiters which are inte-
NECTED, and REMOVED. The
ing capacity of [42,000] [65,000] grally mounted with breaker
breaker drawout element shall
[85,000] [100,000] [200,000] shall be inaccessible until the
contain a worm gear levering
amperes. To assure a fully selec- breaker is completely with-
“in” and “out” mechanism with
tive system, all circuit breakers drawn from its compartment
removable lever crank. Lever-
shall have 30 cycle short-time assuring complete isolation.
ing shall be accomplished via
withstand ratings equal to their Current limiters mounted on a
the use of conventional tools.
symmetrical interrupting ratings separate fuse truck shall be key
Mechanical interlocking shall
through 85,000 amperes, regard- interlocked with the breaker to
be provided so that the breaker
less of whether equipped with prevent withdrawing or inser-
is in the tripped position before
instantaneous trip protection or tion unless the breaker is
levering “in” or “out” of the
not. locked open.
cell. The breaker shall include a
E. Where circuit breakers are 2. Power circuit breakers with provision for padlocking open
equipped with current limiters, current limiting fuses shall to prevent manual or electric
the combination shall have short- have a 200,000-ampere RMS closing. The padlocking shall
time ratings in accordance with symmetrical interrupting have a provision for securing
the characteristics of the limiter capacity at 600 volts and below. the breaker in the connected,
selected. test, or disconnected position
J. For drawout applications the by preventing levering.
F. All ratings shall be tested to the breaker cell shall be equipped
requirements of ANSI C37.20.1, with drawout rails and primary Insert applicable trip unit specifica-
C37.50 and C37.51 and UL wit- and secondary disconnecting tion from section G3.
nessed and approved. contacts. The stationary part of
the primary disconnecting
devices for each power circuit
CAT.71.01.T.E
Cutler-Hammer Circuit Breakers and Trip Units G1-21
January 1999 Low-Voltage Power Circuit Breakers – DSII
Typical Specifications
Power Circuit Breakers – G. Main power circuit breakers shall through a glass polyester insulat-
be provided with trip units as ing support barrier; correspond-
DS II specified in section G3. ing moving fringe contacts
A. [Main] [Tie] protective devices suitably spaced shall be furnished
H. Tie power circuit breakers shall
shall be [drawout] [fixed] insu- on the power circuit breaker studs
be provided with trip units as
lated case circuit breakers, Cutler- which engage in only the con-
specified in section G3.
Hammer type – DS II or approved nected position. The assembly
equal. Frame ratings shall be 800, I. [Main] [Tie] power circuit break- shall provide multiple silver-to-sil-
1200, 1600, 2000, 3000, or 4000 ers, where indicated on the draw- ver full floating high-pressure
amperes. All breakers shall be ings, shall include current point contacts with uniform pres-
UL listed for application in their limiters. Limiters shall be inte- sure on each finger maintained by
intended enclosures for 100% of grally mounted on 800-, 1600- springs.
their continuous ampere rating. and 2000-ampere breakers. For
1. The secondary disconnecting
3200-ampere and 4000-ampere
B. Breakers shall be [manually devices shall consist of floating
breakers, limiters shall be
operated (MO)] [electrically fingers mounted on the remov-
mounted on a separate drawout
operated (EO)] as indicated on able unit and engaging flat con-
limiter truck. Current limiters
the drawings. tact segments at the rear of the
shall be coordinated with the
compartment. The secondary
C. Electrically operated breakers breaker trip device, so as to avoid
disconnecting devices shall be
shall be complete with [120 Vac] unnecessary blowing of the cur-
silver-plated and sliding con-
[48 Vdc] [125 Vdc] operators, rent limiters. Breakers shall
tact engagement shall be main-
1[close/open pushbuttons] [con- include an anti-single-phase
tained in the “connected” and
trol switch], plus red and green device that will trip the breaker in
“test” positions.
indicating lights to indicate the event of a blown limiter, indi-
breaker contact position. [DC cate from the front of the breaker 2. The removable power circuit
source shall be supplied from a which limiter is blown, and breaker element shall be G
remote battery system] [AC prevent the breaker from being equipped with disconnecting
source shall be taken from a re-closed on a single-phase contacts, wheels and interlocks
(remote source) (control power condition due to missing or for drawout application. It shall
transformer internal to the blown limiters. have four (4) positions: CON-
switchgear assembly)]. NECTED, TEST, DISCON-
1. Current limiters which are inte-
NECTED, and REMOVED all of
D. All circuit breakers shall have a grally mounted with breaker
which permit closing the com-
minimum symmetrical interrupt- shall be inaccessible until the
partment door. The breaker dra-
ing capacity of [42,000] [65,000] breaker is completely with-
wout element shall contain a
[85,000] [100,000] [200,000] drawn from its compartment
worm gear levering “in” and
amperes. To assure a fully selec- assuring complete isolation.
“out” mechanism with remov-
tive system, all circuit breakers Current limiters mounted on a
able lever crank. Mechanical
shall have 30 cycle short-time separate fuse truck shall be key
interlocking shall be provided
withstand ratings equal to their interlocked with the breaker to
so that the breaker is in the
symmetrical interrupting ratings prevent withdrawing or inser-
tripped position before levering
through 85,000 amperes, regard- tion unless the breaker is
“in” or “out” of the cell. The
less of whether equipped with locked open.
breaker shall include a provi-
instantaneous trip protection or sion for padlocking open to pre-
2. Power circuit breakers with cur-
not. vent manual or electric
rent limiting fuses shall have a
E. Where circuit breakers are 200,000-ampere RMS symmet- closing. The padlocking shall
equipped with current limiters, rical interrupting capacity at also secure the breaker in the
the combination shall have short- 600 volts and below. connected, test or disconnected
time ratings in accordance with position by preventing levering.
J. For drawout applications the
the characteristics of the limiter
breaker cell shall be equipped Insert applicable trip unit specifica-
selected.
with drawout rails and primary tion from section G3.
F. All ratings shall be tested to the and secondary disconnecting
requirements of ANSI C37.20.1, contacts. The stationary part of
C37.50 and C37.51 and UL wit- the primary disconnecting
nessed and approved. devices for each power circuit For a complete product specifica-
breaker shall consist of a set of tion in CSI format, see Cutler-
contacts extending to the rear Hammer Products Specification
Guide, section 16475.
CAT.71.01.T.E
G1-22 Circuit Breakers and Trip Units
Cutler-Hammer
Low-Voltage Power Circuit Breakers – DSII January 1999
CAT.71.01.T.E