Technical Data Sheet: Automatic Fire Suppression System Rack-Mountable
Technical Data Sheet: Automatic Fire Suppression System Rack-Mountable
Application
Rosenberger automatic fire suppression system is designed to protect electronic equipment stored in the rack
and cabinets if there is a fire. It is a rack mountable unit and charging FM200 (HFC-227ea) as extinguishing
agent, which provides two approaches to suppressor extinguish a fire scenario without human intervention.
Fire detection tube
Dieses Dokument ist urheberrechtlich geschützt ● This document is protected by copyright ● Rosenberger (Shanghai) Technology Co.,Ltd.
Temperature reaches 160 ℃ +/-10 ℃, gas in the fire detection pipe will expand rapidly, a nozzle will be
blasted at the highest temperature point, fire extinguishing gas will be sprayed from the blasting port
through the fire detection pipe to realize cooling and fire extinguishing
Fire detection glass ball
Temperature exceed 68 ℃, glass ball broken, fire extinguishing agent sprayed leaked out of the glass
The HFC-227ea/FM200 is a clean gas extinguishing agent with chemical and physical extinguishing effect.
It's colorless, tasteless, low toxicity, non-conductive, non-polluting protected objects, will not cause damage
to property and precision facilities, can be used in low fire extinguishing concentration, reliable extinguishing
fire category B, C and electrical fires.
Profile/Outline
System Architecture
① Nozzle (optional).
② Server rack.
③ Copper pipe connection interface.
④ Feedback signal.
⑤ Gas switch.
Dieses Dokument ist urheberrechtlich geschützt ● This document is protected by copyright ● Rosenberger (Shanghai) Technology Co.,Ltd.
⑥ Pressure gauge.
⑦ Fire detection pipe interface.
⑧ Server rack fire suppression unit.
⑨ Fire detecting tube.
① Nozzle (optional).
② Server racks.
③ Copper pipe connection interface.
④ Feedback signal.
⑤ Gas switch.
⑥ Pressure gauge.
⑦ Fire detection tube interface.
⑧ Rack-mountable fire suppression unit.
⑨ Fire detection tube.
⑩ Connection hose.
Note:
Above system architecture are used fire detecting tube solution, if clients want to use fire detection glass
ball solution, insert ball to the fire detection tube interface to replace fire detection tube.
Product Appearance
Dieses Dokument ist urheberrechtlich geschützt ● This document is protected by copyright ● Rosenberger (Shanghai) Technology Co.,Ltd.
A1
A2
A3
A4
Front Side
Dieses Dokument ist urheberrechtlich geschützt ● This document is protected by copyright ● Rosenberger (Shanghai) Technology Co.,Ltd.
B1 B2 B3 B4 B3 B1
B2: Nozzle(Optional)
B3: Handle
Rear Side
C1 C2 C3 C4 C5
1. Dimension:
W x D x H: 425×745×42 mm
2. Material:
Cabinet: Iron, metal spray paint process.
Front cover: Aluminum anodic oxidation treatment.
Extinguishing agent: FM200 (HFC-227ea)
Environmental Data
Technical Parameters
Product Parameters
1. Temperature sensitive glass ball: 68 ℃ (Temperature can also be selected according to customer
requirement).
2. Temperature of fire detection tube :160 ℃+/-10 ℃