You are on page 1of 6

BRF-DS -LR-0013

Technical Data Sheet

Automatic fire suppression system


Rack-mountable
RMDC-AFS-XX-XX-XX-X

Application

Rosenberger automatic fire suppression system is designed to protect electronic equipment stored in the rack
and cabinets if there is a fire. It is a rack mountable unit and charging FM200 (HFC-227ea) as extinguishing
agent, which provides two approaches to suppressor extinguish a fire scenario without human intervention.
 Fire detection tube
Dieses Dokument ist urheberrechtlich geschützt ● This document is protected by copyright ● Rosenberger (Shanghai) Technology Co.,Ltd.

Temperature reaches 160 ℃ +/-10 ℃, gas in the fire detection pipe will expand rapidly, a nozzle will be
blasted at the highest temperature point, fire extinguishing gas will be sprayed from the blasting port
through the fire detection pipe to realize cooling and fire extinguishing
 Fire detection glass ball
Temperature exceed 68 ℃, glass ball broken, fire extinguishing agent sprayed leaked out of the glass

The HFC-227ea/FM200 is a clean gas extinguishing agent with chemical and physical extinguishing effect.
It's colorless, tasteless, low toxicity, non-conductive, non-polluting protected objects, will not cause damage
to property and precision facilities, can be used in low fire extinguishing concentration, reliable extinguishing
fire category B, C and electrical fires.

Profile/Outline

System Architecture

1. Single unit system architecture

Rosenberger (Shanghai) Technology Co., Ltd.


BRF-TQ4SM-010/3.0

Rosenberger Hochfrequenztechnik GmbH & Co. KG


Room 1002-1003, Bldg#40, No.1888 Xinjinqiao Rd.,
P.O. Box 1260 D-84526 Tittmoning Germany Page
Pudong, Shanghai, China 201206
Tel: +49 (0) 8684 -18 0
Tel: +86 (21) 5899-5997
Fax: +49 (0) 8684 -18 1499
Fax: +86 (21) 5899-5594 1/6
Email: info@rosenberger.de
Email: info@rosenbergerap.com
Web: www.rosenberger.com
Web: www.rosenbergerap.com
BRF-DS -LR-0013
Technical Data Sheet

Automatic fire suppression system


Rack-mountable
RMDC-AFS-XX-XX-XX-X

① Nozzle (optional).
② Server rack.
③ Copper pipe connection interface.
④ Feedback signal.
⑤ Gas switch.
Dieses Dokument ist urheberrechtlich geschützt ● This document is protected by copyright ● Rosenberger (Shanghai) Technology Co.,Ltd.

⑥ Pressure gauge.
⑦ Fire detection pipe interface.
⑧ Server rack fire suppression unit.
⑨ Fire detecting tube.

2. Multi-unit system architecture

① Nozzle (optional).
② Server racks.
③ Copper pipe connection interface.
④ Feedback signal.
⑤ Gas switch.
⑥ Pressure gauge.
⑦ Fire detection tube interface.
⑧ Rack-mountable fire suppression unit.
⑨ Fire detection tube.
⑩ Connection hose.

Rosenberger (Shanghai) Technology Co., Ltd.


BRF-TQ4SM-010/3.0

Rosenberger Hochfrequenztechnik GmbH & Co. KG


Room 1002-1003, Bldg#40, No.1888 Xinjinqiao Rd.,
P.O. Box 1260 D-84526 Tittmoning Germany Page
Pudong, Shanghai, China 201206
Tel: +49 (0) 8684 -18 0
Tel: +86 (21) 5899-5997
Fax: +49 (0) 8684 -18 1499
Fax: +86 (21) 5899-5594 2/6
Email: info@rosenberger.de
Email: info@rosenbergerap.com
Web: www.rosenberger.com
Web: www.rosenbergerap.com
BRF-DS -LR-0013
Technical Data Sheet

Automatic fire suppression system


Rack-mountable
RMDC-AFS-XX-XX-XX-X

Note:

Above system architecture are used fire detecting tube solution, if clients want to use fire detection glass
ball solution, insert ball to the fire detection tube interface to replace fire detection tube.

Product Appearance
Dieses Dokument ist urheberrechtlich geschützt ● This document is protected by copyright ● Rosenberger (Shanghai) Technology Co.,Ltd.

A1
A2

A3
A4

A1: Pressure gauge

A2: Rack-mountable fire suppression unit

A3: Server rack

A4: Fire detection tube

Rosenberger (Shanghai) Technology Co., Ltd.


BRF-TQ4SM-010/3.0

Rosenberger Hochfrequenztechnik GmbH & Co. KG


Room 1002-1003, Bldg#40, No.1888 Xinjinqiao Rd.,
P.O. Box 1260 D-84526 Tittmoning Germany Page
Pudong, Shanghai, China 201206
Tel: +49 (0) 8684 -18 0
Tel: +86 (21) 5899-5997
Fax: +49 (0) 8684 -18 1499
Fax: +86 (21) 5899-5594 3/6
Email: info@rosenberger.de
Email: info@rosenbergerap.com
Web: www.rosenberger.com
Web: www.rosenbergerap.com
BRF-DS -LR-0013
Technical Data Sheet

Automatic fire suppression system


Rack-mountable
RMDC-AFS-XX-XX-XX-X

Front Side
Dieses Dokument ist urheberrechtlich geschützt ● This document is protected by copyright ● Rosenberger (Shanghai) Technology Co.,Ltd.

B1 B2 B3 B4 B3 B1

B1: Mounting holes

B2: Nozzle(Optional)

B3: Handle

B4: Rack-mountable fire suppression unit

Rear Side

C1 C2 C3 C4 C5

Rosenberger (Shanghai) Technology Co., Ltd.


BRF-TQ4SM-010/3.0

Rosenberger Hochfrequenztechnik GmbH & Co. KG


Room 1002-1003, Bldg#40, No.1888 Xinjinqiao Rd.,
P.O. Box 1260 D-84526 Tittmoning Germany Page
Pudong, Shanghai, China 201206
Tel: +49 (0) 8684 -18 0
Tel: +86 (21) 5899-5997
Fax: +49 (0) 8684 -18 1499
Fax: +86 (21) 5899-5594 4/6
Email: info@rosenberger.de
Email: info@rosenbergerap.com
Web: www.rosenberger.com
Web: www.rosenbergerap.com
BRF-DS -LR-0013
Technical Data Sheet

Automatic fire suppression system


Rack-mountable
RMDC-AFS-XX-XX-XX-X

C1: Pressure gauge.


C2: Fire detection tube interface.
C3: Gas switch.
C4: Feedback signal.
C5: Copper pipe connection interface.
Dieses Dokument ist urheberrechtlich geschützt ● This document is protected by copyright ● Rosenberger (Shanghai) Technology Co.,Ltd.

Construction and Material

1. Dimension:
W x D x H: 425×745×42 mm
2. Material:
Cabinet: Iron, metal spray paint process.
Front cover: Aluminum anodic oxidation treatment.
Extinguishing agent: FM200 (HFC-227ea)

Environmental Data

1. Operation temperature: 0℃ to +50℃

2. Operation humidity: ≤97% RH

Technical Parameters

Product Parameters

No. Type of device Rack-mountable fire suppression unit


1 Storage of container 2L
2 Max filling rate 1.15kg/L
3 Storage pressure(20℃) 1.6MPa
4 Max. working pressure 2.5MPa
5 Action temperature of fire detecting tube 160 ℃ ±10 ℃
6 Max. length of fire detection tube 25m(according to rack no.)

Fire detection tube type specification

Outer Diameter Inner Diameter Wall thickness Melting point temperature


6mm 4mm 1.0 mm 160 ℃ +/-10 ℃

Rosenberger (Shanghai) Technology Co., Ltd.


BRF-TQ4SM-010/3.0

Rosenberger Hochfrequenztechnik GmbH & Co. KG


Room 1002-1003, Bldg#40, No.1888 Xinjinqiao Rd.,
P.O. Box 1260 D-84526 Tittmoning Germany Page
Pudong, Shanghai, China 201206
Tel: +49 (0) 8684 -18 0
Tel: +86 (21) 5899-5997
Fax: +49 (0) 8684 -18 1499
Fax: +86 (21) 5899-5594 5/6
Email: info@rosenberger.de
Email: info@rosenbergerap.com
Web: www.rosenberger.com
Web: www.rosenbergerap.com
BRF-DS -LR-0013
Technical Data Sheet

Automatic fire suppression system


Rack-mountable
RMDC-AFS-XX-XX-XX-X

Main spare parts with single or multiple linkage configurations:


Dieses Dokument ist urheberrechtlich geschützt ● This document is protected by copyright ● Rosenberger (Shanghai) Technology Co.,Ltd.

Nozzle Pressure Feedback Temp. sensitive Fire detection


Gas switch
(optional) gauge signal glass ball tube

1. Temperature sensitive glass ball: 68 ℃ (Temperature can also be selected according to customer

requirement).
2. Temperature of fire detection tube :160 ℃+/-10 ℃

3. Start power is no needed.


4. If temperature sensitive glass ball is needed, it can be inserted to the end of fire detection tube.

Ordering Information

Order Number Description


RMDC-AFS-DT-02-01-B Rack-mountable AFSS with 160℃ fire detection tube, 1U

While the information has been carefully compiled to the best of our knowledge, nothing is intended as representation or warranty on
our part and no statement herein shall be construed as recommendation to infringe existing patents. In the effort to improve our
products, we reserve the right to make changes judged to be necessary.

Draft Date Check Approve Date Rev. ECN Name Date


Ivan 2021-06-23 Laddie Jerry 2021-06-23 Draft Ivan 2021-06-23

Rosenberger (Shanghai) Technology Co., Ltd.


BRF-TQ4SM-010/3.0

Rosenberger Hochfrequenztechnik GmbH & Co. KG


Room 1002-1003, Bldg#40, No.1888 Xinjinqiao Rd.,
P.O. Box 1260 D-84526 Tittmoning Germany Page
Pudong, Shanghai, China 201206
Tel: +49 (0) 8684 -18 0
Tel: +86 (21) 5899-5997
Fax: +49 (0) 8684 -18 1499
Fax: +86 (21) 5899-5594 6/6
Email: info@rosenberger.de
Email: info@rosenbergerap.com
Web: www.rosenberger.com
Web: www.rosenbergerap.com