EIO0000002381 12/2018
Modicon Quantum
Update Procedure
User Guide
10/2019
EIO0000002381.01
www.schneider-electric.com
The information provided in this documentation contains general descriptions and/or technical
characteristics of the performance of the products contained herein. This documentation is not
intended as a substitute for and is not to be used for determining suitability or reliability of these
products for specific user applications. It is the duty of any such user or integrator to perform the
appropriate and complete risk analysis, evaluation and testing of the products with respect to the
relevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates or
subsidiaries shall be responsible or liable for misuse of the information contained herein. If you
have any suggestions for improvements or amendments or have found errors in this publication,
please notify us.
You agree not to reproduce, other than for your own personal, noncommercial use, all or part of
this document on any medium whatsoever without permission of Schneider Electric, given in
writing. You also agree not to establish any hypertext links to this document or its content.
Schneider Electric does not grant any right or license for the personal and noncommercial use of
the document or its content, except for a non-exclusive license to consult it on an "as is" basis, at
your own risk. All other rights are reserved.
All pertinent state, regional, and local safety regulations must be observed when installing and
using this product. For reasons of safety and to help ensure compliance with documented system
data, only the manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant
instructions must be followed.
Failure to use Schneider Electric software or approved software with our hardware products may
result in injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
© 2019 Schneider Electric. All rights reserved.
2 EIO0000002381 10/2019
Table of Contents
Safety Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Chapter 1 Preparing an Update. . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Prerequisites . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Quantum Modules Version, Firmware Files, and Connection . . . . . . . 14
Connecting the PC to a CPU. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Connecting the PC to an Ethernet Module or Coprocessor . . . . . . . . 22
Chapter 2 CPU Operating System Update . . . . . . . . . . . . . . . . . . . 23
Prerequisites . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
CPU OS Update . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Chapter 3 CPU with Ethernet Coprocessor Update . . . . . . . . . . . . 31
Prerequisites . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
CPU Ethernet Coprocessor Update . . . . . . . . . . . . . . . . . . . . . . . . . . 33
CPU OS Update . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Chapter 4 Hot Standby CPU Update. . . . . . . . . . . . . . . . . . . . . . . . 43
Prerequisites . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Preparing the Hot Standby System for CPU Update . . . . . . . . . . . . . . 47
Standby CPU Coprocessor Update . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Standby CPU OS Update . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
System Switchover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
New Standby CPU Update and System Setup . . . . . . . . . . . . . . . . . . 60
Chapter 5 Ethernet RIO System Head and Drop Module Update . . 61
140 CRP 312 00 Update Prerequisites . . . . . . . . . . . . . . . . . . . . . . . . 62
140 CRP 312 00 Firmware Update . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
140 CRA 312 00, BME CRA 312 10, and BMX CRA 312 x0 Update
Prerequisites . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
140 CRA 312 00, BME CRA 312 10, and BMX CRA 312 x0 Firmware
Update . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Chapter 6 S908 RIO System Head and Drop Module Update . . . . 75
140 CRP 93x 00 Update Prerequisites . . . . . . . . . . . . . . . . . . . . . . . . 76
140 CRP 93x 00 S908 RIO Head Update . . . . . . . . . . . . . . . . . . . . . . 77
140 CRA 93x 00 Update Prerequisites . . . . . . . . . . . . . . . . . . . . . . . . 82
140 CRA 93x 00 S908 RIO Drop Update . . . . . . . . . . . . . . . . . . . . . . 83
EIO0000002381 10/2019 3
Chapter 7 140 NOE 771 x1 Module Update . . . . . . . . . . . . . . . . . . . 89
Prerequisites . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
140 NOE 771 x1 Firmware Update . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Chapter 8 140 NOC 78x xx Module Update . . . . . . . . . . . . . . . . . . . 97
Prerequisites . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
140 NOC 78x xx Firmware Update . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
4 EIO0000002381 10/2019
Safety Information
Important Information
NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device
before trying to install, operate, service, or maintain it. The following special messages may appear
throughout this documentation or on the equipment to warn of potential hazards or to call attention
to information that clarifies or simplifies a procedure.
EIO0000002381 10/2019 5
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified
personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of
the use of this material.
A qualified person is one who has skills and knowledge related to the construction and operation
of electrical equipment and its installation, and has received safety training to recognize and avoid
the hazards involved.
WARNING
UNGUARDED EQUIPMENT
Do not use this software and related automation equipment on equipment which does not have
point-of-operation protection.
Do not reach into machinery during operation.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
This automation equipment and related software is used to control a variety of industrial processes.
The type or model of automation equipment suitable for each application will vary depending on
factors such as the control function required, degree of protection required, production methods,
unusual conditions, government regulations, etc. In some applications, more than one processor
may be required, as when backup redundancy is needed.
Only you, the user, machine builder or system integrator can be aware of all the conditions and
factors present during setup, operation, and maintenance of the machine and, therefore, can
determine the automation equipment and the related safeties and interlocks which can be properly
used. When selecting automation and control equipment and related software for a particular
application, you should refer to the applicable local and national standards and regulations. The
National Safety Council's Accident Prevention Manual (nationally recognized in the United States
of America) also provides much useful information.
In some applications, such as packaging machinery, additional operator protection such as point-
of-operation guarding must be provided. This is necessary if the operator's hands and other parts
of the body are free to enter the pinch points or other hazardous areas and serious injury can occur.
Software products alone cannot protect an operator from injury. For this reason the software
cannot be substituted for or take the place of point-of-operation protection.
6 EIO0000002381 10/2019
Ensure that appropriate safeties and mechanical/electrical interlocks related to point-of-operation
protection have been installed and are operational before placing the equipment into service. All
interlocks and safeties related to point-of-operation protection must be coordinated with the related
automation equipment and software programming.
NOTE: Coordination of safeties and mechanical/electrical interlocks for point-of-operation
protection is outside the scope of the Function Block Library, System User Guide, or other
implementation referenced in this documentation.
WARNING
EQUIPMENT OPERATION HAZARD
Verify that all installation and set up procedures have been completed.
Before operational tests are performed, remove all blocks or other temporary holding means
used for shipment from all component devices.
Remove tools, meters, and debris from equipment.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Follow all start-up tests recommended in the equipment documentation. Store all equipment
documentation for future references.
Software testing must be done in both simulated and real environments.
Verify that the completed system is free from all short circuits and temporary grounds that are not
installed according to local regulations (according to the National Electrical Code in the U.S.A, for
instance). If high-potential voltage testing is necessary, follow recommendations in equipment
documentation to prevent accidental equipment damage.
Before energizing equipment:
Remove tools, meters, and debris from equipment.
Close the equipment enclosure door.
Remove all temporary grounds from incoming power lines.
Perform all start-up tests recommended by the manufacturer.
EIO0000002381 10/2019 7
OPERATION AND ADJUSTMENTS
The following precautions are from the NEMA Standards Publication ICS 7.1-1995 (English
version prevails):
Regardless of the care exercised in the design and manufacture of equipment or in the selection
and ratings of components, there are hazards that can be encountered if such equipment is
improperly operated.
It is sometimes possible to misadjust the equipment and thus produce unsatisfactory or unsafe
operation. Always use the manufacturer’s instructions as a guide for functional adjustments.
Personnel who have access to these adjustments should be familiar with the equipment
manufacturer’s instructions and the machinery used with the electrical equipment.
Only those operational adjustments actually required by the operator should be accessible to
the operator. Access to other controls should be restricted to prevent unauthorized changes in
operating characteristics.
8 EIO0000002381 10/2019
About the Book
At a Glance
Document Scope
This user guide explains how to update a Modicon Quantum PAC operating system or a
communication module firmware.
Update Procedure
The update procedure is a maintenance operation that consists in changing a CPU or module
embedded software. It requires the CPU to be in STOP mode and disconnected from the systems
and applications it affects. When a module is addressed through the CPU, the CPU must be in
STOP mode and no functional communication traffic occur between the CPU and the module.
NOTICE
INOPERABLE EQUIPMENT
Stop the CPU before any firmware update or firmware check with OS Loader or Unity Loader
software.
Failure to follow these instructions can result in equipment damage.
Validity Note
This document is valid for EcoStruxure™ Control Expert 14.0 or later.
EIO0000002381 10/2019 9
Related Documents
You can download these technical publications and other technical information from our website
at www.schneider-electric.com/en/download.
WARNING
UNINTENDED EQUIPMENT OPERATION
The application of this product requires expertise in the design and programming of control
systems. Only persons with such expertise should be allowed to program, install, alter, and apply
this product.
Follow all local and national safety codes and standards.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
10 EIO0000002381 10/2019
Modicon Quantum
Preparing an Update
EIO0000002381 12/2018
Chapter 1
Preparing an Update
Preparing an Update
Overview
This chapter describes how to prepare a CPU or module in order to update their firmware version.
EIO0000002381 10/2019 11
Preparing an Update
Prerequisites
Overview
This update requires a PC with Unity Pro/Control Expert, OS Loader, and Unity Loader (for
140 CRA 312 00, BMX CRA 312 •0, or BME CRA 312 10) installed and the binary file containing
the OS or firmware to download.
NOTE: The procedures described in this manual require Unity Pro/Control Expert and OS Loader
with a version greater than V2.2, and Unity Loader with a version greater than V2.3.
Unity Pro is the former name of Control Expert for version 13.1 or earlier.
Required Elements
To proceed with an update, you need the following elements:
Control Expert software installed on the PC.
NOTE: It is not necessary to launch Control Expert for a firmware or OS update.
The firmware or operating system. It can be downloaded from http://www.schneider-
electric.com.
OS Loader software (installed with Control Expert) to download the firmware or OS file in the
module.
Unity Loader software to download the firmware file in 140 CRA 312 00, BMX CRA 312 •0, or
BME CRA 312 10 module.
Step Action
1 Connect to www.schneider-electric.com global website.
2 Click Support → Documents & Software.
3 Hints to help you find the firmware file:
Filter future results by selecting Firmware - Released and Firmware - Updates in the
Document Type area.
Use the Search field.
Try different keywords to find the .bin or .ldx file.
For example, try to enter full module name (140CPU67160), part of the module name
(140CPU), functionality to update (copro), firmware version if it is know (v342).
NOTE: If no result is displayed, select Document Language → English to display results in
english.
4 Select the proper binary file for the module.
NOTE: Some modules may require more than one file for a complete update.
5 Download the binary file into the PC.
12 EIO0000002381 10/2019
Preparing an Update
OS Loader Software
OS Loader software is installed on the PC during Control Expert installation.
To launch OS Loader, click Start → Programs → EcoStruxure Control Expert → OS Loader.
Step Action
1 Connect to www.schneider-electric.com global website.
2 Enter Unity Loader in the Search input field.
Refine your search by selecting Documents and softwares in the Search in input field.
3 Select the Unity Loader version required.
4 Click Download. Usually a .zip file is proposed for download. This .zip file contains a dvd .iso file
and the installation instructions.
5 Run the Unity Loader setup file and follow the instructions (on the screen and in the downloaded
documentation) to install the software.
EIO0000002381 10/2019 13
Preparing an Update
NOTE: Refer to compatibility rules document in Unity Pro online help or in the release notes for
more information on versions compatibility.
NOTE: When Modbus and Modbus Plus connections are available, choosing Modbus Plus
connection reduces the update duration thanks to higher transfer rates.
14 EIO0000002381 10/2019
Preparing an Update
CPU reference
140 CPU 311 10
140 CPU 434 12U
140 CPU 534 14U
CPU reference
140 CPU 651 50
140 CPU 651 60
140 CPU 652 60
EIO0000002381 10/2019 15
Preparing an Update
CPU reference
140 CPU 671 60
140 CPU 672 60
140 CPU 672 61
140 CPU 678 61
NOTE: Hot Standby CPU have a
Hot Standby coprocessor.
Module reference
140 NOC 78• ••
140 NOE 771 01
140 NOE 771 11
16 EIO0000002381 10/2019
Preparing an Update
140 NOE 771 11 binary file is different for RoHS and non-RoHS modules.
Ethernet RIO Communication Head and Adapter Module List and Files
The following table shows the Ethernet RIO communication head and adapter module that can be
updated:
Module reference
140 CRP 312 00
140 CRA 312 00
BME CRA 312 10
BMX CRA 312 •0
EIO0000002381 10/2019 17
Preparing an Update
S908 RIO Communication Head and Adapter Module List and Files
The following table shows the S908 RIO communication head and adapter module that can be
updated:
Module reference
140 CRP 93• 00
140 CRA 93• 00
18 EIO0000002381 10/2019
Preparing an Update
Overview
You can download the Quantum CPU OS only by a direct connection between the PC and the CPU
using the Modbus or Modbus Plus protocol.
NOTE: The CPU USB port does not manage OS or firmware download.
NOTE: Modbus Plus communication is faster than Modbus communication and requires less time
to download a binary file. The Modbus Plus interface on the PC is provided by a TSXCUSBMBP
Modbus Plus USB adapter.
Prerequisite
Stop the CPU before launching a communication with OS Loader whether it is to read a firmware
version or update a firmware.
NOTE: The update procedure is a maintenance operation. It requires the CPU to be in STOP mode
and disconnected from the systems and applications it affects. When a module is addressed
through the CPU, the CPU must be in STOP mode and no functional communication traffic occur
between the CPU and the module.
EIO0000002381 10/2019 19
Preparing an Update
20 EIO0000002381 10/2019
Preparing an Update
Step Action
1 Install the CD labeled Modbus Plus Driver Suite into your CD drive.
2 The installation should begin automatically.
If not, follow the procedure below to start the installation manually.
From the Start menu (Start button on Windows task bar), select Run.
Type D:\Setup.exe (if your CD drive is not D:, substitute the drive letter of your CD drive) and
click OK.
3 Follow the on-screen instructions to complete the software installation.
4 The final step of the software installation displays a message window containing instructions to read
carefully.
To install the Modbus Plus communication adapter (TSXCUSBMBP) hardware, follow these steps:
Step Action
1 Connect the TSXCUSBMBP adapter to a USB port of your computer.
NOTE: Do not connect the Modbus Plus adapter cable between the TSXCUSBMBP and the CPU at
this step to avoid duplicate Modbus Plus node addresses on the Modbus Plus network. Connect it
only after setting the Modbus Plus address (step 4).
2 Follow the installation process until a message is displayed to indicate that the new hardware is
ready to use.
3 Restart your computer.
4 Set the TSXCUSBMBP adapter Modbus Plus address.
NOTE: The CPU default Modbus Plus address is 1. This means that a different address needs to be
assigned to the TSXCUSBMBP adapter.
To change the TSXCUSBMBP adapter Modbus Plus address:
Open Start → All Programs → Schneider Electric - MBX Driver Suite → Configuration → MBX
Device Drivers.
Select the TSXCUSBMBP adapter and click Edit.
When prompted, select Launch Device Manager.
In the Device Manager, select the USB adapter under MBX Devices for Modicon Network → USB
TSXCUSBMBP.
In the configuration window, select the Device Settings tab.
In the Node Address field, select an address value: 2 for example (TSXCUSBMBP adapter
address needs to be different than the CPU address).
The TSXCUSBMBP adapter Modbus Plus address is now set.
The TSXCUSBMBP adapter is ready to be used for updating a CPU module.
5 Connect the Modbus Plus adapter cable between the TSXCUSBMBP and the CPU.
EIO0000002381 10/2019 21
Preparing an Update
Prerequisites
For an Ethernet module or coprocessor update, follow these recommendations:
Make a minimal configuration with only the following equipment:
CPU with embedded Ethernet module, or CPU and Ethernet module (140 NOE 771 •1, or
140 CRP 312 00).
Power supply.
Rack.
Configure the PAC system with an empty program containing only the IP address configuration.
The Ethernet module or coprocessor has to be on the same Ethernet network as the PC running
OS Loader. The Ethernet module and PC need to have compatible IP address, subnet mask,
and default gateway.
The CPU is in Stop mode.
The Ethernet module to update has no TCP traffic.
NOTE: The update procedure is a maintenance operation. It requires the CPU to be in STOP mode,
disconnected from the systems and applications it affects, and no functional communication traffic
occur between the CPU and the module.
Connection Mode
To perform the physical connection between the PC running OS Loader and the CPU or Ethernet
communication module, you can use:
A crossover Ethernet cable directly between both equipment.
Two straight through Ethernet cables via a hub.
Communication Protocol
Communication for Ethernet module or coprocessor update is performed with FTP protocol.
22 EIO0000002381 10/2019
Modicon Quantum
CPU Update
EIO0000002381 12/2018
Chapter 2
CPU Operating System Update
Overview
This chapter describes how to connect a CPU and download the operating system using
OS Loader.
EIO0000002381 10/2019 23
CPU Update
Prerequisites
CPU Version
The procedure below describes how to update a Quantum CPU.
This procedure can be adopted for all Quantum platforms (high end and legacy platforms).
Physical Connection
Connect your PC to the CPU for the update. For more information, refer to the topic on Connecting
the PC to a CPU (see page 19).
24 EIO0000002381 10/2019
CPU Update
CPU OS Update
Step Action
1 Verify that the CPU is in STOP mode.
2 Click Start → Programs → EcoStruxure Control Expert → OS Loader to launch OS Loader.
Result: The Welcome window is displayed.
3 Click Next.
Result: The Communication Protocol window is displayed.
4 Select the MODBUS01 or MBPLUS01 communication protocol in accordance with the chosen
physical connection and click Next.
Result: The Target window is displayed (the information displayed in the following example are for
illustration purpose only):
EIO0000002381 10/2019 25
CPU Update
Step Action
9 In the Devices dialog box, click Stop PLC if the CPU is not already stopped.
10 In the Devices dialog box, click Properties if you need to display information on the CPU status:
Processor state: started, stopped, or not configured
Processor type
Hardware identification
OS version
11 Click Next.
Result: The Operation window is displayed.
NOTICE
EQUIPMENT DAMAGE
During the download:
Do not power OFF the CPU.
Do not power OFF the PC.
Do not shut down OS Loader.
Do not disconnect the communication cable.
26 EIO0000002381 10/2019
CPU Update
After connecting the CPU, proceed as follows to select and download the firmware file:
Step Action
1 Select Download OS to device and click Browse.
2 Select the file to download into the CPU (see page 15).
EIO0000002381 10/2019 27
CPU Update
Step Action
3 Click Next.
Result: The File and Device Info window displays information on the OS file to download and the
device connected:
Check the PC binary file version. The compatibility with the CPU OS is indicated as follows:
PC file is compatible with the CPU: It is indicated by a green tick between the File and Device
dialog box. The transfer is allowed.
PC file version is lower than the CPU version: It is indicated by a yellow tick between the File and
Device dialog box. The transfer is allowed but it downgrades the CPU to an earlier version.
PC file is not compatible with the CPU: It is indicated by a red tick between the File and Device
dialog box and the Next button is grayed. The transfer is not allowed. Solve the incompatibility
before proceeding with the next step.
4 Click Next.
Result: The Summary window is displayed.
5 Click Download.
Result: A popup window is displayed.
6 Click Yes to validate the information displayed and launch the transfer.
Result: The Progress window is displayed with the remaining time. The duration depends on the
protocol used and the PC configuration.
7 In the Progress window, check if the download is completed.
Result: The SUCCESS message is displayed.
NOTE: If the SUCCESS message is not displayed, check each step and contact your local
Schneider Electric office for assistance.
28 EIO0000002381 10/2019
CPU Update
Step Action
8 Click Close and exit OS Loader.
9 Reset the CPU either by:
Pushing the Reset button located on the CPU if available.
Powering OFF and then powering ON the CPU.
Step Action
1 Verify that the CPU is in STOP mode.
2 Open OS Loader.
Result: The Welcome window is displayed.
3 Click Next.
Result: The Communication Protocol window is displayed.
4 Select the MODBUS01 or MBPLUS01 communication protocol in accordance with the chosen
physical connection and click Next.
Result: The Target window is displayed.
5 In the Device Type dialog box, select Processor.
6 In the Devices dialog box, click Scan to update the list of devices.
7 In the Devices dialog box, select the PLC node.
8 In the Target Address dialog box, click Connect to connect the PC to the CPU.
9 In the Devices dialog box, click Properties to check the OS version.
10 Click Close and exit OS Loader.
EIO0000002381 10/2019 29
CPU Update
30 EIO0000002381 10/2019
Modicon Quantum
CPU with Ethernet Coprocessor Update
EIO0000002381 12/2018
Chapter 3
CPU with Ethernet Coprocessor Update
Overview
The procedures describe how to connect a CPU with an Ethernet coprocessor and download the
firmware and operating system using OS Loader.
EIO0000002381 10/2019 31
CPU with Ethernet Coprocessor Update
Prerequisites
IP Address of the PC
Change the IP address of your PC to get it into the same subnetwork as the CPU.
The first three groups of digits have to be the same. For example, the CPU address is
85.16.133.13 and the PC address needs to be 85.16.133.xx.
Physical Connection
Connect your PC to the CPU Ethernet coprocessor for the update.
Make a minimal configuration with no TCP traffic as indicated in the section Connecting the PC to
an Ethernet Module or Coprocessor (see page 22).
32 EIO0000002381 10/2019
CPU with Ethernet Coprocessor Update
Step Action
1 Verify that the CPU is in STOP mode.
2 Disable the antivirus and firewall of your computer and enable them again once the module is
updated.
3 Click Start → Programs → EcoStruxure Control Expert → OS Loader to launch OS Loader.
Result: The Welcome window is displayed.
4 Click Next.
Result: The Communication Protocol window is displayed.
5 Select the FTP communication driver and click Next.
Result: The Target window is displayed (the information displayed in the following example are for
illustration purpose only):
EIO0000002381 10/2019 33
CPU with Ethernet Coprocessor Update
Step Action
9 If requested, type the MAC address of the coprocessor module that is written in front of the CPU.
NOTE:
If your module is located remotely, you can get the MAC address by
1. Pinging the module IP address.
2. Using the arp -a command to display the physical MAC address of the module.
10 In the Devices dialog box, select the Ethernet port node to update.
11 Click Properties if you need to display the firmware version.
12 Click Next.
Result: The Operation window is displayed.
NOTICE
EQUIPMENT DAMAGE
During the download:
Do not power OFF the CPU.
Do not power OFF the PC.
Do not shut down OS Loader.
Do not disconnect the communication cable.
34 EIO0000002381 10/2019
CPU with Ethernet Coprocessor Update
After connecting the CPU Ethernet coprocessor, proceed as follows to select and download the
firmware file:
Step Action
1 Select Download OS to device and click Browse.
2 Select the file to download into the CPU Ethernet coprocessor (see page 15).
EIO0000002381 10/2019 35
CPU with Ethernet Coprocessor Update
Step Action
3 Click Next.
Result: The File and Device Info window displays information on the firmware file to download and
the device connected:
Check the PC binary file version. The compatibility with the CPU Ethernet coprocessor firmware
is indicated as follows:
PC file is compatible with the CPU Ethernet firmware: It is indicated by a green tick between the
File and Device dialog box. The transfer is allowed.
PC file version is lower than the CPU Ethernet firmware version: It is indicated by a yellow tick
between the File and Device dialog box. The transfer is allowed but it downgrades the module
to an earlier version.
PC file is not compatible with the CPU Ethernet firmware: It is indicated by a red tick between the
File and Device dialog box and the Next button is grayed. The transfer is not allowed. Solve
the incompatibility before proceeding with the next step.
4 Click Next.
Result: The Summary window is displayed.
5 Click Download.
Result: A popup window is displayed.
6 Click Yes to validate the information displayed and launch the transfer.
Result: The Progress window is displayed with the remaining time. The duration depends on the
protocol used and the PC configuration.
36 EIO0000002381 10/2019
CPU with Ethernet Coprocessor Update
Step Action
7 In the Progress window, check if the download is completed.
Result: The SUCCESS message is displayed.
NOTE: If the SUCCESS message is not displayed, check each step and contact your local
Schneider Electric office for assistance.
8 Click Close and exit OS Loader.
9
Step Action
1 Verify that the CPU is in STOP mode.
2 Open OS Loader.
Result: The Welcome window is displayed.
3 Click Next.
Result: The Communication Protocol window is displayed.
4 Select the FTP communication driver and click Next.
Result: The Target window is displayed.
5 In the Device Type dialog box, select Direct device.
6 In the Target Address dialog box, type the device IP address.
7 Click Connect to connect the PC to the CPU Ethernet coprocessor.
8 If requested, type the MAC address of the coprocessor module that is written in front of the CPU.
NOTE: If your module is located remotely, you can get the MAC address by pinging the module
IP address, then using the arp -a command to display the physical MAC address of the module.
9 In the Devices dialog box, select the Ethernet port node updated.
10 In the Devices dialog box, click Properties to check the firmware version.
11 Click Close and exit OS Loader.
EIO0000002381 10/2019 37
CPU with Ethernet Coprocessor Update
CPU OS Update
OS Download
Once the CPU Ethernet coprocessor firmware is updated, proceed with the CPU OS update via
Modbus or Modbus Plus.
Step Action
1 Verify that the CPU is in STOP mode.
2 Click Start → Programs → EcoStruxure Control Expert → OS Loader to launch OS Loader.
Result: The Welcome window is displayed.
3 Click Next.
Result: The Communication Protocol window is displayed.
4 Select the MODBUS01 or MBPLUS01 communication protocol in accordance with the chosen
physical connection and click Next.
Result: The Target window is displayed (the information displayed in the following example are for
illustration purpose only):
38 EIO0000002381 10/2019
CPU with Ethernet Coprocessor Update
Step Action
6 In the Devices dialog box, click Scan to update the list of devices.
7 In the Devices dialog box, select the PLC node.
8 In the Target Address dialog box, click Connect to connect the PC to the CPU.
9 In the Devices dialog box, click Stop PLC if the CPU is not already stopped.
10 In the Devices dialog box, click Properties if you need to display information on the CPU status:
Processor state: started, stopped, or not configured
Processor type
Hardware identification
OS version
11 Click Next.
Result: The Operation window is displayed.
NOTICE
EQUIPMENT DAMAGE
During the download:
Do not power OFF the CPU.
Do not power OFF the PC.
Do not shut down OS Loader.
Do not disconnect the communication cable.
EIO0000002381 10/2019 39
CPU with Ethernet Coprocessor Update
After connecting the CPU, proceed as follows to select and download the OS file:
Step Action
1 Select Download OS to device and click Browse.
2 Select the file to download into the CPU (see page 15).
40 EIO0000002381 10/2019
CPU with Ethernet Coprocessor Update
Step Action
3 Click Next.
Result: The File and Device Info window displays information on the OS file to download and the
device connected:
Check the PC binary file version. The compatibility with the CPU OS is indicated as follows:
PC file is compatible with the CPU: It is indicated by a green tick between the File and Device
dialog box. The transfer is allowed.
PC file version is lower than the CPU version: It is indicated by a yellow tick between the File and
Device dialog box. The transfer is allowed but it downgrades the CPU to an earlier version.
PC file is not compatible with the CPU: It is indicated by a red tick between the File and Device
dialog box and the Next button is grayed. The transfer is not allowed. Solve the incompatibility
before proceeding with the next step.
4 Click Next.
Result: The Summary window is displayed.
5 Click Download.
Result: A popup window is displayed.
6 Click Yes to validate the information displayed and launch the transfer.
Result: The Progress window is displayed with the remaining time. The duration depends on the
protocol used and the PC configuration.
7 In the Progress window, check if the download is completed.
Result: The SUCCESS message is displayed.
NOTE: If the SUCCESS message is not displayed, check each step and contact your local
Schneider Electric office for assistance.
EIO0000002381 10/2019 41
CPU with Ethernet Coprocessor Update
Step Action
8 Click Close and exit OS Loader.
9 Reset the CPU either by:
Pushing the Reset button located on the CPU if available.
Powering OFF and then powering ON the CPU.
Step Action
1 Verify that the CPU is in STOP mode.
2 Open OS Loader.
Result: The Welcome window is displayed.
3 Click Next.
Result: The Communication Protocol window is displayed.
4 Select the MODBUS01 or MBPLUS01 communication protocol in accordance with the chosen
physical connection and click Next.
Result: The Target window is displayed.
5 In the Device Type dialog box, select Processor.
6 In the Devices dialog box, click Scan to update the list of devices.
7 In the Devices dialog box, select the PLC node.
8 In the Target Address dialog box, click Connect to connect the PC to the CPU.
9 In the Devices dialog box, click Properties to check the version displayed.
10 Click Close and exit OS Loader.
42 EIO0000002381 10/2019
Modicon Quantum
Hot Standby CPU Update
EIO0000002381 12/2018
Chapter 4
Hot Standby CPU Update
Overview
This chapter describes how to update a Standby CPU in a Hot Standby system while the process
is controlled by the Primary CPU.
NOTE: To update a Quantum Hot Standby operating system without shutting down the process,
the current application program has to be executable by the new operating system.
Observe this requirement when updating with minor revisions targeted for bug fixes or minor
enhancements.
When a major function enhancement needs to be made, maintaining this compatibility may not be
possible. In this case, an operating system update requires a system shutdown.
EIO0000002381 10/2019 43
Hot Standby CPU Update
Prerequisites
44 EIO0000002381 10/2019
Hot Standby CPU Update
Compatibility Issues
To update a Quantum Hot Standby operating system without shutting down the process, the
current application program has to be executable by the new operating system.
Observe this requirement when updating with minor revisions targeted for bug fixes or minor
enhancements.
When a major function enhancement needs to be made, maintaining this compatibility may not be
possible. In this case, an operating system update requires a system shutdown.
EIO0000002381 10/2019 45
Hot Standby CPU Update
IP Address of the PC
Change the IP address of your PC to get it into the same subnetwork as the CPU.
The first three groups of digits have to be the same. For example, the CPU address is
85.16.133.13 and the PC address needs to be 85.16.133.xx.
46 EIO0000002381 10/2019
Hot Standby CPU Update
WARNING
UNEXPECTED EQUIPMENT BEHAVIOR
Design your application in such a way that your process is not impacted by a cycle time variation
that might appear after a firmware update.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Preliminary steps required to update the Standby CPU in a Hot Standby system while the process
is controlled by the Primary CPU:
Step Action
1 Connect Unity Pro to the Primary CPU (through Modbus, Modbus Plus or USB).
2 Set the Command Register system bit %SW60.4 to 1.
3 Disconnect Unity Pro from the Primary CPU.
EIO0000002381 10/2019 47
Hot Standby CPU Update
Step Action
1 Note the Modbus or Modbus Plus address of the Standby CPU using the keypad functions:
Modbus: select Quantum PLC Communications → Communications Serial Port
Modbus Plus: select Quantum PLC Communications → Communications Modbus Plus
48 EIO0000002381 10/2019
Hot Standby CPU Update
Step Action
1 Disable the antivirus and firewall of your computer and enable them again once the module is
updated.
2 Click Start → Programs → EcoStruxure Control Expert → OS Loader to launch OS Loader.
Result: The Welcome window is displayed.
3 Click Next.
Result: The Communication Protocol window is displayed.
4 Select the FTP communication driver and click Next.
Result: The Target window is displayed (the information displayed in the following example are for
illustration purpose only):
EIO0000002381 10/2019 49
Hot Standby CPU Update
Step Action
8 If requested, type the MAC address of the Hot Standby coprocessor that is written in front of the
CPU.
9 In the Devices dialog box, select the Hot Standby coprocessor to update.
10 Click Properties if you need to display the firmware version.
11 Click Next.
Result: The Operation window is displayed.
NOTICE
EQUIPMENT DAMAGE
During the download:
Do not power OFF the CPU.
Do not power OFF the PC.
Do not shut down OS Loader.
Do not disconnect the communication cable.
50 EIO0000002381 10/2019
Hot Standby CPU Update
After connecting the Hot Standby coprocessor, proceed as follows to select and download the
firmware file:
Step Action
1 Select Download OS to device and click Browse.
2 Select the file to download into the CPU Hot Standby coprocessor (see page 16).
EIO0000002381 10/2019 51
Hot Standby CPU Update
Step Action
3 Click Next.
Result: The File and Device Info window displays information on the firmware file to download and
the device connected:
Check the PC binary file version. The compatibility with the Hot Standby coprocessor firmware is
indicated as follows:
PC file is compatible with the Hot Standby coprocessor firmware: It is indicated by a green tick
between the File and Device dialog box. The transfer is allowed.
PC file version is lower than the Hot Standby coprocessor firmware version: It is indicated by a
yellow tick between the File and Device dialog box. The transfer is allowed but it downgrades
the Hot Standby coprocessor to an earlier version.
PC file is not compatible with the Hot Standby coprocessor firmware: It is indicated by a red tick
between the File and Device dialog box and the Next button is grayed. The transfer is not
allowed. Solve the incompatibility before proceeding with the next step.
4 Click Next.
Result: The Summary window is displayed.
5 Click Download.
Result: A popup window is displayed.
6 Click Yes to validate the information displayed and launch the transfer.
Result: The Progress window is displayed with the remaining time. The duration depends on the
protocol used and the PC configuration.
52 EIO0000002381 10/2019
Hot Standby CPU Update
Step Action
7 In the Progress window, check if the download is completed.
Result: The SUCCESS message is displayed.
NOTE: If the SUCCESS message is not displayed, check each step and contact your local
Schneider Electric office for assistance.
8 Click Close and exit OS Loader.
9 Reset the Standby CPU by performing a power cycle.
Step Action
1 Open OS Loader.
Result: The Welcome window is displayed.
2 Click Next.
Result: The Communication Protocol window is displayed.
3 Select the FTP communication driver and click Next.
Result: The Target window is displayed.
4 In the Device Type dialog box, select Direct device.
5 In the Target Address dialog box, type the device IP address.
6 Click Connect to connect the PC to the Hot Standby coprocessor.
7 If requested, type the MAC address of the Hot Standby coprocessor that is written in front of the
CPU.
8 In the Devices dialog box, select the Ethernet port node updated.
9 In the Devices dialog box, click Properties to check the firmware version.
10 Click Close and exit OS Loader.
EIO0000002381 10/2019 53
Hot Standby CPU Update
OS Download
Once the Hot Standby coprocessor firmware is updated, proceed with the CPU OS update via
Modbus or Modbus Plus.
Step Action
1 Click Start → Programs → EcoStruxure Control Expert → OS Loader to launch OS Loader.
Result: The Welcome window is displayed.
2 Click Next.
Result: The Communication Protocol window is displayed.
3 Select the MODBUS01 or MBPLUS01 communication protocol in accordance with the chosen
physical connection and click Next.
Result: The Target window is displayed (the information displayed in the following example are for
illustration purpose only):
54 EIO0000002381 10/2019
Hot Standby CPU Update
Step Action
6 In the Devices dialog box, select the PLC node.
7 In the Target Address dialog box, click Connect to connect the PC to the CPU.
8 In the Devices dialog box, click Stop PLC if the CPU is not already stopped.
9 In the Devices dialog box, click Properties if you need to display information on the CPU status:
Processor state: started, stopped, or not configured
Processor type
Hardware identification
OS version
10 Click Next.
Result: The Operation window is displayed.
NOTICE
EQUIPMENT DAMAGE
During the download:
Do not power OFF the CPU.
Do not power OFF the PC.
Do not shut down OS Loader.
Do not disconnect the communication cable.
EIO0000002381 10/2019 55
Hot Standby CPU Update
After connecting the CPU, proceed as follows to select and download the firmware file:
Step Action
1 Select Download OS to device and click Browse.
2 Select the file to download into the CPU (see page 16).
56 EIO0000002381 10/2019
Hot Standby CPU Update
Step Action
3 Click Next.
Result: The File and Device Info window displays information on the OS file to download and the
device connected:
Check the PC binary file version. The compatibility with the CPU OS is indicated as follows:
PC file is compatible with the CPU: It is indicated by a green tick between the File and Device
dialog box. The transfer is allowed.
PC file version is lower than the CPU version: It is indicated by a yellow tick between the File and
Device dialog box. The transfer is allowed but it downgrades the CPU to an earlier version.
PC file is not compatible with the CPU: It is indicated by a red tick between the File and Device
dialog box and the Next button is grayed. The transfer is not allowed. Solve the incompatibility
before proceeding with the next step.
4 Click Next.
Result: The Summary window is displayed.
5 Click Download.
Result: A popup window is displayed.
6 Click Yes to validate the information displayed and launch the transfer.
Result: The Progress window is displayed with the remaining time. The duration depends on the
protocol used and the PC configuration.
7 In the Progress window, check if the download is completed.
Result: The SUCCESS message is displayed.
NOTE: If the SUCCESS message is not displayed, check each step and contact your local
Schneider Electric office for assistance.
8 Click Close and exit OS Loader.
EIO0000002381 10/2019 57
Hot Standby CPU Update
Step Action
9 Disconnect the PC from the Standby CPU.
10 Switch off the power supply of the Standby CPU.
Step Action
1 Connect the PC to the Standby CPU.
2 Switch on the power supply of the Standby CPU
3 Open OS Loader.
Result: The Welcome window is displayed.
4 Click Next.
Result: The Communication Protocol window is displayed.
5 Select the MODBUS01 or MBPLUS01 communication protocol in accordance with the chosen
physical connection and click Next.
Result: The Target window is displayed.
6 In the Device Type dialog box, select Processor.
7 In the Devices dialog box, click Scan to update the list of devices.
8 In the Devices dialog box, select the PLC node.
9 In the Target Address dialog box, click Connect to connect the PC to the CPU.
10 In the Devices dialog box, click Properties to check the OS version.
11 Click Close and exit OS Loader.
12 Disconnect the PC from the Standby CPU.
13 Switch off the power supply of the Standby CPU.
Switch on the power supply of the Standby CPU to read information on the LCD display.
Check the version using the LCD display and keypad:
Select Quantum System Info → System Info Firmware Info
The following information is displayed
Rev. Ldr: Internal boot loader version.
Os: OS version (example of display: 03.20-00-11 for V3.20).
58 EIO0000002381 10/2019
Hot Standby CPU Update
System Switchover
Step Action
1 When using an application in the PCMCIA:
1. Insert the PCMCIA batteries.
2. Insert the PCMCIA card in the Standby CPU.
2 Power on the Standby CPU.
NOTE: The CPU must be in the No Conf state.
3 Reconnect all the communication cables (CRP module, Ethernet cables, …) except the
HSBY Link fiber optic cable.
4 At last, connect the HSBY Link fiber optic cable.
5 Check that the application program is automatically transferred to the Standby CPU. If not,
perform the transfer with the keyboard.
NOTE: Verify that the Modbus or Modbus Plus address is the same as the address noted when
preparing the Hot Standby system for update (see page 47).
6 Put the CPU in RUN mode.
Verify that the Primary CPU is in RUN Primary mode, and the Standby CPU is in RUN Standby
mode.
7 Perform a switchover by stopping the Primary CPU with the keyboard.
NOTE: Verify that the Standby CPU becomes the Primary CPU (check the LCD screen).
EIO0000002381 10/2019 59
Hot Standby CPU Update
Step Action
1 Connect Control Expert to the new Primary CPU (through Modbus, Modbus Plus or USB).
2 Set the Command Register system bit %SW60.4 to 0.
3 Disconnect the PC.
4 Verify that the Primary CPU is in Run Primary mode, and the Standby CPU is in Run Standby
mode.
60 EIO0000002381 10/2019
Modicon Quantum
Ethernet RIO System Head and Drop Module Update
EIO0000002381 12/2018
Chapter 5
Ethernet RIO System Head and Drop Module Update
Overview
This chapter describes how to update the Ethernet RIO system head and drop modules.
EIO0000002381 10/2019 61
Ethernet RIO System Head and Drop Module Update
IP Address of the PC
Change the IP address of your PC to get it into the same subnetwork as the 140 CRP 312 00
module.
The first three groups of digits have to be the same. For example, the 140 CRP 312 00 module
address is 10.10.1.102 and the PC address needs to be 10.10.1.xx.
Physical Connection
Connect the PC to one of the following Ethernet ports of the 140 CRP 312 00 module:
SERVICE port.
INTERLINK port.
Make a minimal configuration with no TCP traffic as indicated in the section Connecting the PC to
an Ethernet Module or Coprocessor (see page 22).
62 EIO0000002381 10/2019
Ethernet RIO System Head and Drop Module Update
Step Action
1 Verify that the CPU is in STOP mode.
2 Disable the antivirus and firewall of your computer and enable them again once the module is
updated.
3 Click Start → Programs → EcoStruxure Control Expert → OS Loader to launch OS Loader.
Result: The Welcome window is displayed.
4 Click Next.
Result: The Communication Protocol window is displayed.
5 Select the FTP communication driver and click Next.
Result: The Target window is displayed (the information displayed in the following example are for
illustration purpose only):
EIO0000002381 10/2019 63
Ethernet RIO System Head and Drop Module Update
Step Action
9 If requested, type the MAC address of the 140 CRP 312 00 module that is written in front of the
module.
NOTE:
If your module is located remotely, you can get the MAC address by
1. Pinging the module IP address.
2. Using the arp -a command to display the physical MAC address of the module.
10 In the Devices dialog box, select the module to update.
11 Click Properties if you need to display the firmware version.
12 Click Next.
Result: The Operation window is displayed.
NOTICE
EQUIPMENT DAMAGE
During the download:
Do not power OFF the module.
Do not power OFF the PC.
Do not shut down OS Loader.
Do not disconnect the communication cable.
64 EIO0000002381 10/2019
Ethernet RIO System Head and Drop Module Update
After connecting the module, proceed as follows to select download the firmware file:
Step Action
1 Select Download OS to device and click Browse.
2 Select the file to download into the module (see page 17).
EIO0000002381 10/2019 65
Ethernet RIO System Head and Drop Module Update
Step Action
3 Click Next.
Result: The File and Device Info window displays information on the firmware file to download and
the device connected.
Check the PC binary file version. The compatibility with the 140 CRP 312 00 firmware is indicated
as follows:
PC file is compatible with the module firmware: It is indicated by a green tick between the File and
Device dialog box. The transfer is allowed.
PC file version is lower than the module firmware version: It is indicated by a yellow tick between
the File and Device dialog box. The transfer is allowed but it downgrades the module to an
earlier version.
PC file is not compatible with the module firmware: It is indicated by a red tick between the File
and Device dialog box and the Next button is grayed. The transfer is not allowed. Solve the
incompatibility before proceeding with the next step.
4 Click Next.
Result: The Summary window is displayed.
5 Click Download.
Result: A popup window is displayed.
6 Click Yes to validate the information displayed and launch the transfer.
Result: The Progress window is displayed with the remaining time.
The update process takes approximately 2 minutes:
1 minute for the firmware update.
1 minute to restart and re-establish I/O connections.
66 EIO0000002381 10/2019
Ethernet RIO System Head and Drop Module Update
Step Action
7 In the Progress window, check if the download is completed.
Result: The SUCCESS message is displayed.
NOTE: If the SUCCESS message is not displayed, check each step and contact your local
Schneider Electric office for assistance.
8 Click Close and exit OS Loader.
Step Action
1 Verify that the CPU is in STOP mode.
2 Open OS Loader.
Result: The Welcome window is displayed.
3 Click Next.
Result: The Communication Protocol window is displayed.
4 Select the FTP communication driver and click Next.
Result: The Target window is displayed.
5 In the Device Type dialog box, select Direct device.
6 In the Target Address dialog box, type the device IP address.
7 Click Connect to connect the PC to the module.
8 If requested, type the MAC address of the module that is written in front of the 140 CRP 312 00.
NOTE: If your module is located remotely, you can get the MAC address by pinging the module
IP address, then using the arp -a command to display the physical MAC address of the module.
9 In the Devices dialog box, select the Ethernet port node updated.
10 In the Devices dialog box, click Properties to check the firmware version.
11 Click Close and exit OS Loader.
EIO0000002381 10/2019 67
Ethernet RIO System Head and Drop Module Update
140 CRA 312 00, BME CRA 312 10, and BMX CRA 312 x0 Update Prerequisites
Overview
Adapter modules available in a Quantum Ethernet I/O system:
140CRA31200
BME CRA 312 10
BMXCRA312•0
NOTE: The adapter module firmware download is performed with Unity Loader software
(see page 13).
68 EIO0000002381 10/2019
Ethernet RIO System Head and Drop Module Update
IP Address of the PC
Change the IP address of your PC to get it into the same subnetwork as the adapter module.
The first three groups of digits have to be the same. For example, the adapter module address is
10.10.133.13 and the PC address needs to be 10.10.133.xx.
Physical Connection
Connect the PC to one of the following Ethernet ports of the module:
SERVICE port (140 CRA 312 00, BME CRA 312 10, BMX CRA 312 10).
DEVICE NETWORK port (BMX CRA 312 00).
Verify that communications are established between the PC and the adapter by issuing a Ping
command from the PC:
EIO0000002381 10/2019 69
Ethernet RIO System Head and Drop Module Update
140 CRA 312 00, BME CRA 312 10, and BMX CRA 312 x0 Firmware Update
Update Procedure
Do not interrupt the communication between the PC and the module while downloading a file
because it can cause irreparable damage to the module.
NOTICE
EQUIPMENT DAMAGE
During the download:
Do not power OFF the module.
Do not power OFF the PC.
Do not shut down Unity Loader.
Do not disconnect the communication cable.
70 EIO0000002381 10/2019
Ethernet RIO System Head and Drop Module Update
If the firmware download process is interrupted, the new firmware is not installed and the adapter
continues to use the old firmware. If an interruption occurs, restart the process.
Open Unity Loader on your PC and update the firmware for the remote I/O adapter:
Step Action
1 Disable the antivirus and firewall of your computer and enable them again once the module is updated.
2 Open Unity Loader on your PC. (Start → Programs → Schneider Electric → Unity Loader)
Unity Loader opens and displays the Project tab:
Click Connect.
4 When Unity Loader is connected to the module, select the Firmware tab.
EIO0000002381 10/2019 71
Ethernet RIO System Head and Drop Module Update
Step Action
5 In the PC area, click the ellipsis (...) button to open a dialog where you can navigate and select the
firmware file for the network connectivity module. The firmware is contained in a Unity Loader file (.ldx
extension).
When the firmware file is selected, the selected revision of this firmware is displayed in the list on the
left and the current version of the firmware is displayed in the list on the right.
6 When the arrow in the middle of the screen (above) is green, click Transfer.
NOTE: Only click Transfer if the arrow is green. A yellow arrow indicates that the firmware file on your
computer is different than the remote I/O adapter. A red arrow indicates that the firmware on the
computer is not compatible with the remote I/O adapter.
72 EIO0000002381 10/2019
Ethernet RIO System Head and Drop Module Update
Step Action
7 Click yes on the 2 dialogs that appear. A third dialog appears (below), which indicates the transfer status
with the blue bars at the bottom of the screen. When the transfer is completed, click Close.
EIO0000002381 10/2019 73
Ethernet RIO System Head and Drop Module Update
74 EIO0000002381 10/2019
Modicon Quantum
S908 RIO System Head and Drop Module Update
EIO0000002381 12/2018
Chapter 6
S908 RIO System Head and Drop Module Update
Overview
This chapter describes how to update an S908 RIO system head and drop module.
EIO0000002381 10/2019 75
S908 RIO System Head and Drop Module Update
Physical Connection
Connect your PC to the CPU located on the same rack as the 140 CRP 93• 00 module to update.
For more information, refer to the topic on Connecting the PC to a CPU (see page 19).
76 EIO0000002381 10/2019
S908 RIO System Head and Drop Module Update
NOTICE
INOPERABLE EQUIPMENT
Stop the CPU before updating the 140 CRP 93• 00 module.
Failure to follow these instructions can result in equipment damage.
To establish a connection between the PC and the module, and select the download function
proceed as follows:
Step Action
1 Verify that the CPU is in STOP mode.
2 Click Start → Programs → EcoStruxure Control Expert → OS Loader to launch OS Loader.
Result: The Welcome window is displayed.
3 Click Next.
Result: The Communication Protocol window is displayed.
EIO0000002381 10/2019 77
S908 RIO System Head and Drop Module Update
Step Action
4 Select the MODBUS01 or MBPLUS01 communication protocol in accordance with the chosen
physical connection and click Next.
Result: The Target window is displayed:
5 In the Device Type dialog box, select Local Head and type the Slot number.
6 If needed, click Scan to display all currently active devices.
7 In the Devices dialog box, select the PLC node (the PC is connected to the CPU via Modbus or
Modbus Plus, and we address the S908 Local Head).
8 In the Target Address dialog box, click Connect to connect the PC to the module.
9 In the Devices dialog box, click Properties if you need to display information on the module status.
10 Click Next.
Result: The Operation window is displayed.
78 EIO0000002381 10/2019
S908 RIO System Head and Drop Module Update
NOTICE
EQUIPMENT DAMAGE
During the download:
Do not power OFF the CPU and module.
Do not power OFF the PC.
Do not shut down the OS Loader.
Do not disconnect the communication cable.
After connecting the module, proceed as follows to select and download the firmware file:
Step Action
1 Select Download OS to device and click Browse.
2 Select the file to download into the module (see page 18).
EIO0000002381 10/2019 79
S908 RIO System Head and Drop Module Update
Step Action
3 Click Next.
Result: The File and Device Info window displays information on the firmware file to download and
the device connected:
Check the PC binary file version. The compatibility with the 140 CRP 93• 00 firmware is indicated
as follows:
PC file is compatible with the module: It is indicated by a green tick between the File and Device
dialog box. The transfer is allowed.
PC file version is lower than the module version: It is indicated by a yellow tick between the File
and Device dialog box. The transfer is allowed but it downgrades the module to an earlier
version.
PC file is not compatible with the module: It is indicated by a red tick between the File and Device
dialog box and the Next button is grayed. The transfer is not allowed. Solve the incompatibility
before proceeding with the next step.
4 Click Next.
Result: The Summary window is displayed.
5 Click Download.
Result: A popup window is displayed.
6 Click Yes to validate the information displayed and launch the transfer.
Result: The Progress window is displayed with the remaining time. The duration depends on the
protocol used and the PC configuration.
80 EIO0000002381 10/2019
S908 RIO System Head and Drop Module Update
Step Action
7 In the Progress window, check if the download is completed.
Result: The SUCCESS message is displayed.
NOTE: If the SUCCESS message is not displayed, check each step and contact your local
Schneider Electric office for assistance.
8 Click Close and exit OS Loader.
Step Action
1 Verify that the CPU is in STOP mode.
2 Open OS Loader.
Result: The Welcome window is displayed.
3 Click Next.
Result: The Communication Protocol window is displayed.
4 Select the MODBUS01 or MBPLUS01 communication protocol in accordance with the chosen
physical connection and click Next.
Result: The Target window is displayed.
5 In the Device Type dialog box, select Local Head and type the Slot number.
6 In the Devices dialog box, click Scan to update the list of devices.
7 In the Devices dialog box, select the PLC node.
8 In the Target Address dialog box, click Connect to connect the PC to the module.
9 In the Devices dialog box, click Properties to check the firmware version.
10 Click Close and exit OS Loader.
EIO0000002381 10/2019 81
S908 RIO System Head and Drop Module Update
Overview
The 140 CRA 93• 00 update is performed using OS Loader software via a Modbus or Modbus Plus
physical connection, and a 140 CRP 93• 00 head module.
Compatibility Rules
The update of a 140 CRA 93• 00 module via a 140 NRP 954 01C repeater may not be possible as
indicated in the following table:
CRA module reference Product version Remote OS update via 140 NRP 954 01C repeater
140 CRA 93• 00 ≤ 08 Yes
≥ 09 No
NOTE: For CRA modules with a product version 09, update the software version of the CRA
module from 2.0 to 2.01 before using a 140 NRP 954 01C repeater in the S908 RIO network.
Physical Connection
Connect your PC to the CPU located on the same rack as the 140 CRP 93• 00 head module. The
140 CRA 93• 00 drop module is connected to the head via an S908 network. For more information,
refer to the topic on Connecting the PC to a CPU (see page 19).
82 EIO0000002381 10/2019
S908 RIO System Head and Drop Module Update
NOTICE
INOPERABLE EQUIPMENT
Stop the CPU before updating the 140 CRA 93• 00 module.
Failure to follow these instructions can result in equipment damage.
To establish a connection between the PC and the module, and select the download function
proceed as follows:
Step Action
1 Verify that the CPU is in STOP mode.
2 Click Start → Programs → EcoStruxure Control Expert → OS Loader to launch OS Loader.
Result: The Welcome window is displayed.
3 Click Next.
Result: The Communication Protocol window is displayed.
EIO0000002381 10/2019 83
S908 RIO System Head and Drop Module Update
Step Action
4 Select the MODBUS01 or MBPLUS01 communication protocol in accordance with the chosen
physical connection and click Next.
Result: The Target window is displayed:
5 In the Device Type dialog box, select RemoteI/O Drop and type the Slot number and the Drop
number.
6 If needed, click Scan to display all currently active devices.
7 In the Devices dialog box, select the PLC node (the PC is connected to the CPU via Modbus or
Modbus Plus, and we address the S908 RemoteI/O Drop).
8 In the Target Address dialog box, click Connect to connect the PC to the module.
9 In the Devices dialog box, click Properties if you need to display information on the module status.
10 Click Next.
Result: The Operation window is displayed.
84 EIO0000002381 10/2019
S908 RIO System Head and Drop Module Update
NOTICE
EQUIPMENT DAMAGE
During the download:
Do not power OFF the CPU and module.
Do not power OFF the PC.
Do not shut down the OS Loader.
Do not disconnect the communication cable.
After connecting the module, proceed as follows to select and download the firmware file:
Step Action
1 Select Download OS to device and click Browse.
2 Select the file to download into the module (see page 18).
EIO0000002381 10/2019 85
S908 RIO System Head and Drop Module Update
Step Action
3 Click Next.
Result: The File and Device Info window displays information on the firmware file to download and
the device connected:
Check the PC binary file version. The compatibility with the 140 CRA 93• 00 firmware is indicated
as follows:
PC file is compatible with the module: It is indicated by a green tick between the File and Device
dialog box. The transfer is allowed.
PC file version is lower than the module version: It is indicated by a yellow tick between the File
and Device dialog box. The transfer is allowed but it downgrades the module to an earlier
version.
PC file is not compatible with the module: It is indicated by a red tick between the File and Device
dialog box and the Next button is grayed. The transfer is not allowed. Solve the incompatibility
before proceeding with the next step.
4 Click Next.
Result: The Summary window is displayed.
5 Click Download.
Result: A popup window is displayed.
6 Click Yes to validate the information displayed and launch the transfer.
Result: The Progress window is displayed with the remaining time. The duration depends on the
protocol used and the PC configuration.
86 EIO0000002381 10/2019
S908 RIO System Head and Drop Module Update
Step Action
7 In the Progress window, check if the download is completed.
Result: The SUCCESS message is displayed.
NOTE: If the SUCCESS message is not displayed, check each step and contact your local
Schneider Electric office for assistance.
8 Click Close and exit OS Loader.
Step Action
1 Verify that the CPU is in STOP mode.
2 Open OS Loader.
Result: The Welcome window is displayed.
3 Click Next.
Result: The Communication Protocol window is displayed.
4 Select the MODBUS01 or MBPLUS01 communication protocol in accordance with the chosen
physical connection and click Next.
Result: The Target window is displayed.
5 In the Device Type dialog box, select RemoteI/O Drop and type the Slot number and the Drop
number.
6 In the Devices dialog box, click Scan to update the list of devices.
7 In the Devices dialog box, select the PLC node.
8 In the Target Address dialog box, click Connect to connect the PC to the module.
9 In the Devices dialog box, click Properties to check the firmware version.
10 Click Close and exit OS Loader.
EIO0000002381 10/2019 87
S908 RIO System Head and Drop Module Update
88 EIO0000002381 10/2019
Modicon Quantum
140 NOE 771 x1 Module Update
EIO0000002381 12/2018
Chapter 7
140 NOE 771 x1 Module Update
Overview
This chapter describes how to update 140 NOE 771 01 and 140 NOE 771 11 modules.
EIO0000002381 10/2019 89
140 NOE 771 x1 Module Update
Prerequisites
Physical Connection
Connect your PC to the 140 NOE 771 •1 module Ethernet port.
Make a minimal configuration with no TCP traffic as indicated in the section Connecting the PC to
an Ethernet Module or Coprocessor (see page 22).
90 EIO0000002381 10/2019
140 NOE 771 x1 Module Update
NOTICE
INOPERABLE EQUIPMENT
Stop the CPU.
Verify that the 140 NOE 771 •1 module is free from TCP traffic.
Failure to follow these instructions can result in equipment damage.
To establish a connection between the PC and the module, and select the download function
proceed as follows:
Step Action
1 Disable the antivirus and firewall of your computer and enable them again once the module is
updated.
2 Stop the CPU manually or through Control Expert.
3 Click Start → Programs → EcoStruxure Control Expert → OS Loader to launch OS Loader.
Result: The Welcome window is displayed.
4 Click Next.
Result: The Communication Protocol window is displayed.
EIO0000002381 10/2019 91
140 NOE 771 x1 Module Update
Step Action
5 Select the FTP communication driver and click Next.
Result: The Target window is displayed (the information displayed in the following example are for
illustration purpose only):
92 EIO0000002381 10/2019
140 NOE 771 x1 Module Update
NOTICE
EQUIPMENT DAMAGE
During the download:
Do not power OFF the module.
Do not power OFF the PC.
Do not shut down OS Loader.
Do not disconnect the communication cable.
After connecting the module, proceed as follows to select and download the firmware file:
Step Action
1 Select Download OS to device and click Browse.
2 Select the file to download into the module (see page 16).
EIO0000002381 10/2019 93
140 NOE 771 x1 Module Update
Step Action
3 Click Next.
Result: The File and Device Info window displays information on the firmware file to download and
the device connected:
Check the PC binary file version. The compatibility with the 140 NOE 771 •1 module firmware is
indicated as follows:
PC file is compatible with the module firmware: It is indicated by a green tick between the File and
Device dialog box. The transfer is allowed.
PC file version is lower than the module firmware version: It is indicated by a yellow tick between
the File and Device dialog box. The transfer is allowed but it downgrades the module to an earlier
version.
PC file is not compatible with the module firmware: It is indicated by a red tick between the File and
Device dialog box and the Next button is grayed. The transfer is not allowed. Solve the
incompatibility before proceeding with the next step.
4 Click Next.
Result: The Summary window is displayed.
5 Click Download.
Result: A popup window is displayed.
6 Click Yes to validate the information displayed and launch the transfer.
Result: The Progress window is displayed with the remaining time. The duration depends on the
protocol used and the PC configuration.
94 EIO0000002381 10/2019
140 NOE 771 x1 Module Update
Step Action
7 In the Progress window, check if the download is completed.
Result: The SUCCESS message is displayed.
NOTE: If the SUCCESS message is not displayed, check each step and contact your local
Schneider Electric office for assistance.
8 Click Close and exit OS Loader.
Step Action
1 Open OS Loader.
Result: The Welcome window is displayed.
2 Click Next.
Result: The Communication Protocol window is displayed.
3 Select the FTP communication driver and click Next.
Result: The Target window is displayed.
4 In the Device Type dialog box, select Direct device.
5 In the Target Address dialog box, type the device IP address.
6 Click Connect to connect the PC to the module.
7 If requested, type the MAC address of the module that is written in front of the 140 NOE 771 •1.
NOTE: If your module is located remotely, you can get the MAC address by pinging the module
IP address, then using the arp -a command to display the physical MAC address of the module.
8 In the Devices dialog box, select the Ethernet port node updated.
9 In the Devices dialog box, click Properties to check the firmware version.
10 Click Close and exit OS Loader.
EIO0000002381 10/2019 95
140 NOE 771 x1 Module Update
96 EIO0000002381 10/2019
Modicon Quantum
140 NOC 78x 00 Module Update
EIO0000002381 12/2018
Chapter 8
140 NOC 78x xx Module Update
Overview
This chapter describes how to update a 140 NOC 78• •• module.
EIO0000002381 10/2019 97
140 NOC 78x 00 Module Update
Prerequisites
IP Address of the PC
Change the IP address of your PC to get it into the same subnetwork as the 140 NOC 78• ••
module.
The first three groups of digits have to be the same. For example, the 140 NOC 78• •• module
address is 10.10.133.13 and the PC address needs to be 10.10.133.xx.
Physical Connection
Connect the PC to one of the following Ethernet ports of the 140 NOC 78• •• module:
SERVICE port.
INTERLINK port.
Make a minimal configuration with no TCP traffic as indicated in the section Connecting the PC to
an Ethernet Module or Coprocessor (see page 22).
98 EIO0000002381 10/2019
140 NOC 78x 00 Module Update
NOTICE
INOPERABLE EQUIPMENT
Stop the CPU.
Verify that the 140 NOC 78• •• module is free from TCP traffic.
Failure to follow these instructions can result in equipment damage.
To establish a connection between the PC and the module, and select the download function
proceed as follows:
Step Action
1 Disable the antivirus and firewall of your computer and enable them again once the module is
updated.
2 Stop the CPU manually or through Control Expert.
3 Click Start → Programs → EcoStruxure Control Expert → OS Loader to launch OS Loader.
Result: The Welcome window is displayed.
4 Click Next.
Result: The Communication Protocol window is displayed.
EIO0000002381 10/2019 99
140 NOC 78x 00 Module Update
Step Action
5 Select the FTP communication driver and click Next.
Result: The Target window is displayed (the information displayed in the following example are for
illustration purpose only):
NOTICE
EQUIPMENT DAMAGE
During the download:
Do not power OFF the module.
Do not power OFF the PC.
Do not shut down OS Loader.
Do not disconnect the communication cable.
After connecting the module, proceed as follows to select and download the firmware file:
Step Action
1 Select Download OS to device and click Browse.
2 Select the file to download into the module (see page 16).
Step Action
3 Click Next.
Result: The File and Device Info window displays information on the firmware file to download and
the device connected:
Check the PC binary file version. The compatibility with the 140 NOC 78• •• firmware is indicated
as follows:
PC file is compatible with the module firmware: It is indicated by a green tick between the File and
Device dialog box. The transfer is allowed.
PC file version is lower than the module firmware version: It is indicated by a yellow tick between
the File and Device dialog box. The transfer is allowed but it downgrades the module to an
earlier version.
PC file is not compatible with the module firmware: It is indicated by a red tick between the File
and Device dialog box and the Next button is grayed. The transfer is not allowed. Solve the
incompatibility before proceeding with the next step.
4 Click Next.
Result: The Summary window is displayed.
5 Click Download.
Result: A popup window is displayed.
6 Click Yes to validate the information displayed and launch the transfer.
Result: The Progress window is displayed with the remaining time.
The update process takes approximately 2 minutes:
1 minute for the firmware update.
1 minute to restart and re-establish I/O connections.
Step Action
7 In the Progress window, check if the download is completed.
Result: The SUCCESS message is displayed.
NOTE: If the SUCCESS message is not displayed, check each step and contact your local
Schneider Electric office for assistance.
8 Click Close and exit OS Loader.
Step Action
1 Open OS Loader.
Result: The Welcome window is displayed.
2 Click Next.
Result: The Communication Protocol window is displayed.
3 Select the FTP communication driver and click Next.
Result: The Target window is displayed.
4 In the Device Type dialog box, select Direct device.
5 In the Target Address dialog box, type the device IP address.
6 Click Connect to connect the PC to the module.
7 If requested, type the MAC address of the module that is written in front of the 140 NOC 78• ••.
NOTE: If your module is located remotely, you can get the MAC address by pinging the module
IP address, then using the arp -a command to display the physical MAC address of the module.
8 In the Devices dialog box, select the Ethernet port node updated.
9 In the Devices dialog box, click Properties to check the firmware version.
10 Click Close and exit OS Loader.
Index
0-9 A
140CPU31110 adapter
update, 14 Modbus Plus, 21
140CPU43412
update, 14
140CPU53414 B
update, 14 BMECRA31210
140CPU65150 Unity Loader, 68
update, 14 update, 61
140CPU65160 BMXCRA31200
update, 14 Unity Loader, 68
140CPU65260 update, 61
update, 14 BMXCRA31210
140CPU67060 Unity Loader, 68
update, 14 update, 61
140CPU67160
update, 14
140CPU67260 C
update, 14 cable
140CPU67261 Ethernet, 22
update, 14 communication module
140CPU67861 update, 14
update, 14 connecting
140CRA31200 CPU, 23
Unity Loader, 68 Ethernet module, 22
update, 61 coprocessor
140CRA93x00 Ethernet, 31
update, 75 update, 31
140CRP31200 CPU
update, 61 connecting, 23
140CRP93x00 downloading, 23
update, 75 update, 14
140NOC78xxx
update, 97
140NOE77101 D
update, 89 download
140NOE77111 FactoryCast 140NOE77111, 89
update, 89 firmware, 12
downloading
CPU, 23
E S
embedded Ethernet S908
update, 14 update, 14
ERIO S908 RIO
update, 61 update, 75
Ethernet
cable, 22
coprocessor, 31 T
update, 31 TSXCUSBMBP, 21
Ethernet module
connecting, 22
update, 89 U
Unity Loader, 13, 68
140CRA31200, 68
F BMECRA31210, 68
FactoryCast 140NOE77111 BMXCRA31200, 68
download, 89 BMXCRA31210, 68
firmware
download, 12
H
Hot Standby
update, 43
M
Modbus Plus
adapter, 21
O
OS Loader, 13
P
preparing
update, 11
R
RIO module
update, 14
update
140CPU31110, 14
140CPU43412, 14
140CPU53414, 14
140CPU65150, 14
140CPU65160, 14
140CPU65260, 14
140CPU67060, 14
140CPU67160, 14
140CPU67260, 14
140CPU67261, 14
140CPU67861, 14
140CRA31200, 61
140CRA93x00, 75
140CRP31200, 61
140CRP93x00, 75
140NOC78xxx, 97
140NOE77101, 89
140NOE77111, 89
BMECRA31210, 61
BMXCRA31200, 61
BMXCRA31210, 61
communication module, 14
coprocessor, 31
CPU, 14
embedded Ethernet, 14
ERIO, 61
Ethernet, 31
Ethernet module, 89
Hot Standby, 43
preparing, 11
RIO module, 14
S908, 14
S908 RIO, 75