You are on page 1of 6

Saybolt Global Inspection Manual

LIQUID LEVEL GAUGING

7.1. SAFETY CHECK BEFORE GAUGING liquid surface to a reference point on top of the tank).
They have the zero point at the lower inside of the clip
1. Examine gauge tapes and PETs and ensure that where it attaches to the bob. Outage (ullage) bobs are
grounding straps are properly attached to all gauging square on one end and have a hole to attach the outage
and temperature measurement equipment. tape at the other end. Outage tapes may be used only
2. Check to see that the clamp on the free end of the with outage bobs.
grounding strap works properly.
3. Before climbing any tank, determine whether there is Saybolt Inspectors should use Saybolt-issued gauge
any danger from toxic vapors, such as Hydrogen tapes and bobs.
Sulfide (H2S) or Benzene.
4. If you must go down onto a floating roof, be certain 7.2.2. Portable Measurement Units (PMUs)
you (1) have been trained in confined space entry and Portable Measurement Unit (PMU) is the term used by
(2) check for the presence of toxic vapors and oxygen API to describe measurement tapes equipped with
deficiency. If toxic vapors or oxygen deficiency is a permanent bobs that electronically sense the presence of
problem, have access to a self-contained breathing oil or water and temperature. PMUs are designed to fit
apparatus that has been checked for proper into vapor control valves, usually on board ships and
functioning. barges that minimize the escape of hazardous tank vapors
5. Be certain that terminal operations personnel are to the atmosphere.
notified when you are about to climb a tank, and
request that the terminal provide an attendant while Several companies manufacture the PMUs used in
you are working on a tank top. Saybolt. Those companies also manufacture the vapor
6. Visually check tank stairways, ladders and condition control valves designed to accommodate the tapes. Since
of the roof. Make sure that you do not climb or walk the several brands are not identical in design, each
on any stair, ladder or roof that appears unsafe or company also makes adapters available to permit one
damaged. brand of tape to fit the other brand of vapor control valve.
7. Do not carry anything onto a tank that requires the If the calibration tables have not been adjusted for the
use of both hands. One hand must always be free to relocated gauge point, it may be necessary to adjust the
hold on to the stair rail. If a tank has a ladder, both PMU gauge reading to correct for the new reference
hands must be free. height.
8. Do not enter firewalls (tank pit) that are filled with
water (or mud) that is deeper than the height of your PMUs measure the ullage (outage) of the tank contents.
boots. They function electronically. When petroleum contacts
the sensor at the tip of the bob, a continuous beeping tone
is emitted at the hub of the tape reel. When free water
7.2. GAUGING EQUIPMENT contacts the sensor at the tip of the bob, an intermittent
beeping tone is emitted at the hub of the tape reel.
7.2.1. Steel Tape and Bob Assembly
A steel tape, equipped with a reel, graduated in Ships and barges often carry their own PMUs to be used
meters/mm and/or ft/inches, or ft/hundredths. Tapes are by vessel personnel for their own purposes. Saybolt
typically 10 to 30 meters (25 to 100 feet) long. They are Inspectors should preferably use Saybolt PMUs to
available in chrome finish and stainless steel and other take measurements. In case ship's equipment is to be
finishes. used the inspector should check this equipment (e.g.
comparison with own tape, calibration log etc.)
Gauge tapes are designed to measure the depth of liquids
(from the liquid surface to the tank bottom) in a tank.
They have the zero point at the tip of the attached bob. 7.2.3. Automatic Gauging Equipment
Bobs are constructed of brass or stainless steel. Bobs are Mechanical gauging equipment (such as Whessoe, Varec,
pointed on one end (to help penetrate tank bottom solids) etc.) is affixed to the side of a shore tank. It is equipped
and have a hole to attach the tape at the other end. with a cable with a float attached to one end, and the other
NOTE: Outage (Ullage) tapes are designed to measure end of the cable is attached to the gauge read-out box on
the height of the space above the liquid in a tank (from the the side of the tank. As the oil level rises and falls, the
Issued: May 1, 2002 Saybolt Inspection Support & Development Group Chapter 7, Page 1 of 6
Saybolt Global Inspection Manual

LIQUID LEVEL GAUGING

float rises and falls and the cable changes the reading on transferred to and from the tank. Often, but not always,
the gauge read-out box at the side of the tank. flexing will be indicated by a change in the measured
gauge height. Flexing may cause mis-measurement of the
Radar-type equipment (manufactured by Saab, Enraf and tank contents. (See Section 11 for a detailed description
others) is used on both ship and shore tanks. The radar of tank bottom problems.)
screen is mounted on top of the tank and the beam reflects
off the surface of the liquid. Gauge readings may be 7.3.4. Standpipes (Stilling wells, gauge pipe)
displayed either at the tank top or in a remote location, Tanks are often fitted with standpipes. The reference
such as the control room of a ship or terminal. gauge point is usually located on these standpipes. There
are certain industry standards that apply to standpipes
Other types of automatic gauging equipment rely on used for gauging. Standpipes should be slotted or
pressure or liquid-level detectors installed inside the tank. perforated over the entire length to permit tank liquid
These devices may also be read either on the top of the contents to flow freely inside the standpipe. Standpipes
tank or in a remote read-out location, such as the control should ideally be at least 25 cm (8”) in diameter.
room of the ship or terminal.
7.3.5. Changes in the Gauge Height
7.2.4. Water-finding Paste The measured gauge height of a tank may be different
Water finding paste is available in both jars and tubes. from the reference gauge height on the capacity table.
Jars permit re-mixing of pastes that have separated into That difference may be caused by various expansion
liquid/solid phases. problems of the tank, by flexing bottoms, by build-up of
solids on the tank bottom, or by debris that has fallen into
7.2.5. Product-finding Paste (Gasoline paste) the tank at the gauge point.
In very light products, the liquid level cannot be read
because the product evaporates while the tape is being 7.3.6. Incrustation / Clingage
raised from the liquid. Product-finding paste changes Tanks that contain products with high pour points or with
color when it contacts petroleum products. The liquid sediment may build up residues of these materials on the
level cut is indicated on the paste. walls and floor of the tank. Incrusted tanks have
decreased capacity and that, in turn, overstates the
quantity contained in the tank. Tank cleaning is the only
7.3. TANK MEASUREMENT UNCERTAINTIES remedy for incrustation.

The accuracy of measuring liquid levels may be affected 7.3.7. Leaks in the system
by several conditions. Some of the conditions you may Measurements may be inaccurate due to leaking in the
encounter are listed: pipeline system used by a terminal. Connecting valves
and transfer lines in a terminal may leak permitting
7.3.1. Capacity Table Accuracy product to be diverted into another tank.
Tanks may not have current capacity tables. Periodic
recalibration according to industry standards is 7.3.8. Condition of the Liquid in a Tank
recommended. When any liquid is measured, it must be still or calm,
with no motion. Ideally, it must also be free of entrained
7.3.2. Shell Expansion air or foam.
Tank shells expand and contract with temperature and
with the pressure of the materials placed into the tank. 7.3.9. Additional Gauge Hatches
Industry standards in some locations contain the formula A tank may have other openings in the roof or top where
for calculating shell expansion changes due to it is possible to access tank contents for measurement.
temperature and one method is outlined in section 11.2.4 These openings, if they can be safely reached, may be
of this Manual. very useful for determining flexing bottoms, innages in
cone-bottom tanks, and low levels of material. Only
7.3.3. Tank Bottom Movement official reference gauge points indicated on the capacity
Flexing tank bottoms are a condition created when the table should be used for all custody transfer
bottom of a tank moves up or down when liquids are measurements.
Issued: May 1, 2002 Saybolt Inspection Support & Development Group Chapter 7, Page 2 of 6
Saybolt Global Inspection Manual

LIQUID LEVEL GAUGING

Note: If the observed gauge height and the


7.3.10. Product Quantities at the Zero Gauge reference gauge height are not the same,
Level raise the bob slightly and carefully allow it
The capacity tables for tanks with datum plates above the to drop onto the bottom of the tank to
tank bottom, cone bottoms and sumps may indicate penetrate any sediment on the tank bottom.
product quantity below the zero-gauge level measured at Recheck the observed gauge height. If the
the reference gauge point. Inspectors should attempt to observed and reference gauge heights are
measure at the point where the tank bottom is lowest. still not the same, record the difference and
These measurements can be converted to accurate proceed with the gauging process.
quantities only when the capacity table provides for those • Lower the tape and bob carefully into the liquid at
measurements. If there is no capacity table for liquids least once again and read the liquid cut each time.
below the zero gauge point, the terminal should raise the (Three consecutive readings are required unless the
liquid level above the zero gauge point. first two measurements are within a 3 mm (1/8”)
span.)
7.3.11. Floating Roof Tanks • The two readings that are identical (within the same
When a tank has an floating roof, a correction for the 3mm (1/8" span)) are reported.
displacement of the roof on the product will need to be Note: It may be possible to gauge at more
made, except when the roof is firmly seated on its than one location. Additional innage gauges
supports. Measurements may not be taken in the roof should be measured, recorded and averaged
critical zone except when the capacity table specifically to obtain the reported innage gauge for that
states that this is permissible. The capacity table for most tank.
floating roof tanks is inaccurate in the critical zone.
7.4.2. Ullage (Outage) Gauging
• Note: Ullage gauges are reliable only when the
7.4. GAUGING THE LEVEL OF PETROLEUM measured reference height is the same both
before and after cargo transfer.
Read and record the automatic or other gauge on the side • Read the tank capacity table and record the reference
of the tank (or in the terminal control office) before gauge height of the tank in your gauging book.
climbing the tank. Verify that the floating roof is in the • Attach the bob to the gauge tape and apply water-
correct (low legs) position. Report the presence of water, finding paste to the surface of the bob
snow or ice on the roof. Note: An ullage tape and bob may also be used
to measure ullage gauge.
7.4.1. Innage Gauging • Ground the tape to the tank before gauging.
• Read the tank capacity table and record the reference • Lower the bob/tape carefully into the tank, moving
gauge height of the tank in your gauging book. very slowly as the bob nears the surface of the liquid.
• Attach the bob to the gauge tape and apply water- • After the bob has stopped swinging, continue to
finding paste to the surface of the bob (see FREE lower the tape slowly until a small portion of the bob
WATER GAUGING PROCEDURES below). or tape is immersed in the liquid and an even round
• Ground the tape to the tank before gauging. figure (or inch) graduation on the gauge tape is at the
• Gently lower the bob/tape carefully into the tank, reference gauge point.
moving it very slowly as you near the reference • Withdraw the tape and bob from the tank and read
gauge height at the reference gauge point. the liquid cut on the tape or bob.
• When you feel the tip of the bob touch the bottom of • (Three consecutive readings are required unless the
the tank (or the datum plate), read the observed first two measurements are within a 3 mm (1/8”)
gauge height at the reference gauge point marked on span.)
the tank gauge hatch. (Be careful not to lower the • The two readings that are identical (within the same
tape so far into the liquid that the bob may tilt.) If the 3mm (1/8" span)) are reported.
observed gauge height and the reference gauge height • Determine the ullage (outage) gauge using one of the
are the same, slowly reel in the tape until you can see following procedures:
and note the liquid cut on the tape.

Issued: May 1, 2002 Saybolt Inspection Support & Development Group Chapter 7, Page 3 of 6
Saybolt Global Inspection Manual

LIQUID LEVEL GAUGING

If you are using innage equipment to measure an are not recommended for use in petroleum)
ullage, the reading on the innage bob is subtracted • If water paste is supplied in jars, mix the paste before
from the reading at the reference gauge point to obtain using if it has developed a liquid phase.
the ullage gauge. • Apply the paste to the bob in an even layer that is just
Example 1: thick enough to hide the surface of the bob. Do not
Innage Tape reading at reference point: 03' 04" cover the graduations or numbers.
Innage Bob reading at liquid cut: -00' 02" • Lower the bob carefully into the oil until it just rests
Difference (ullage): 03' 02" on the tank bottom (or datum plate).
• Allow the bob to remain in place for at least 10
Innage Tape reading at reference point: 123 mm seconds (significantly longer periods may be required
Innage Bob reading at liquid cut: 12 mm for heavy or high-viscosity oils).
Difference (ullage): 111 mm • Coating the paste with light lubricating oil before
If you are using an outage tape and bob to measure immersion should help speed readability in heavy oil.
an ullage, the reading of the cut on the outage bob is • If heavy dark oil prevents reading the water cut when
added to the reading at the reference gauge point to the bob is withdrawn, pour or lightly spray a mild
obtain the outage gauge. solvent on the bob, well above the anticipated water
Example 2: cut, and allow the solvent to rinse the dark oil from
Outage Tape reading at reference point: 03' 04" the paste.
Outage Bob reading at liquid cut: 00' 02"
• Some water pastes do not adhere well to the bob in
Sum: 03' 06"
layered applications. It may be necessary to wipe the
bob dry and re-apply the paste under those
conditions.
7.5. SPECIAL PROCEDURES FOR GAUGING
• Always record the highest continuous clear cut as the
BITUMEN (including ASPHALT)
official water level measurement.
• The height of any spotting should be noted on the
Refer to chapter 19, Bitumen. report.

7.6. FREE WATER GAUGING PROCEDURE 7.7. GAUGING WITH PORTABLE


MEASUREMENT UNITS (PMUs)
Free water beneath the oil in a tank may be measured by
the innage or outage method. The innage method is The following procedure is necessary for using PMUs and
preferred. vapor control valves:
NOTE: Free water that is on top of high-density • Examine the vapor control valves as soon as you
material in a tank cannot be accurately gauged. If board the vessel to be certain that the PMU is
water paste is used to measure under these conditions, equipped to fit the valve. It may be necessary to fit
report procedure used. an adapter to the PMU.
NOTE: When determining free water levels using a
• Examine the vessel’s tank capacity tables and verify
PMU (interface detector) always confirm this level with
whether tables have been modified for the new
water finding paste since interface detectors may give a
reference gauge location.
false reading due to suspended water in the product.
• Apply a thin but opaque coating of water finding
Immediately after a vessel has loaded, free water
paste on the bob of the PMU above the sensor.
measurements may not be accurate since some or all of
the free water may remain in suspension in the oil for • Fit the PMU into the vapor control valve and secure
some period of time. the locking collar on the PMU.
• Slowly open the vapor control valve, protecting
7.6.1. Procedure yourself from by-pass spray of petroleum if the valve
• Until you know which brand of paste gives the is not gas-tight.
best reading in a particular type of oil, select • Unwind the tape from the PMU until the sounding
the one that gives the highest clear water cut. device on the reel emits a continuous beeping tone.
(Extremely sensitive pastes, such as SarGel, • Raise and lower the tape & bob just above and below
Issued: May 1, 2002 Saybolt Inspection Support & Development Group Chapter 7, Page 4 of 6
Saybolt Global Inspection Manual

LIQUID LEVEL GAUGING

the liquid surface until you are satisfied that the may result from other factors such as foreign
sensor is exactly at the surface of the petroleum. objects dropped into the tank (e.g., a broken
• Read and record the ullage of the petroleum at the sample bottle or wiping rags) or flexing of
readout area specified by the PMUs manufacturer. the tank bottom.
• Continue to lower the tape & bob into the liquid until
the beeping tone becomes intermittent. There is no reasonable way to determine whether solids or
• Raise and lower the tape & bob just above and below sludge are spread evenly across the bottom of a tank.
the free water interface until you are satisfied that the Therefore only inferential steps can be taken to obtain the
sensor is exactly at the interface of the oil and water. best possible measurement:
• Read and record the ullage of the free water at the • Use the ullage method for cargo measurements;
readout area specified by the PMUs manufacturer. • The terminal should not drain the tank to a point below
(See note above regarding interface detection with the measured solids level;
PMUs) • The terminal should consider maintaining a layer of
• Continue to lower the tape & bob until you can feel free water on the tank bottom.
the bob just rest on the tank bottom.
• Allow the bob to remain in that position for as long
as necessary to obtain a confirming water 7.9. ROLLING GAUGES ON BOARD MARINE
measurement. VESSELS
• Reel in the tape & bob, reeling slowly as you
approach the vapor control valve, until the bob is Vessels subject to movement in the water from rolling
securely inside the upper housing of the valve but seas will usually have a problem with cargo in the tanks
also well above the valve itself. being in motion. Under those conditions, Inspectors may
NOTE: If you close the vapor control valve not be able to get two matching gauges out of three.
while the bob is below the valve, you will
either seriously damage the bob or cut the When cargo is in motion on ships or barges, take five (5)
tape. Take great care when using PMUs to ullage gauges as quickly as possible and record all five
avoid the need for expensive repairs. gauges. Average the five gauges to obtain the mean
• When the bob is secured inside the upper valve ullage to be used for liquid being measured in the tank.
housing, slowly close the valve.
• Unlock the locking collar on the PMU and withdraw
the PMU assembly. 7.10. MEASURING ICE BOTTOMS IN SHORE
TANKS

7.8. GAUGING SOLIDS OR SLUDGE ON TANK In very cold climates, free water on the bottom of shore
BOTTOMS tanks may become ice, particularly when a tank is not
very active. Some special considerations are needed
The presence of solids or semi-solid material on a tank when measuring custody transfers of cargoes involving
bottom is common in crude oil tanks and in tanks that these tanks.
contain high pour point material. These dense materials
may consist of sediment, sand, soil, or solidified For cargo loadings, the ice does not usually present a
hydrocarbons. problem because its level will remain the same before and
after loading a vessel.
The presence of solids or sludge is usually detected by
For cargo discharges, there may be a problem with
• The presence of sludge or heavy material on the gauge
quantifying free water discharged from the vessel. The
bob when it is withdrawn from the tank;
following procedure should be followed.
• The “feel” of the innage bob as it tries to penetrate
1. When gauging shore tank(s), apply water-finding
the material under the oil layer;
paste to the innage bob before measuring the
• The reference gauge height being greater than the
reference gauge height, being certain that the paste
measured gauge height.
extends all the way to the tip of the bob. Then
NOTE: Both of the above means of detection
measure the gauge height allowing the tip of the bob
Issued: May 1, 2002 Saybolt Inspection Support & Development Group Chapter 7, Page 5 of 6
Saybolt Global Inspection Manual

LIQUID LEVEL GAUGING

to sit on the tank or ice bottom for at least 15


seconds. Inspectors may also use the field notebook to record raw
2. Record the difference between the table gauge height data but the data must be transferred to an authorized
and the measured reference gauge height. form or computer program to ensure that all required data
3. Examine the water finding paste for color change. If has been recorded and to leave a copy of raw data with
only the paste at the tip has changed color, the approved parties.
difference between the measured reference gauge
height and the capacity table gauge height should be Minimum raw data information required is as follows:
assumed to be the ice ullage. If the water paste has • Terminal, Tank No., Product, Vessel Name
changed color higher up on the bob, the water cut • Automatic gauge reading
will represent the combined free water/ice ullage in • Measured Gauge Height and Reference Gauge
the tank. Height
4. After the vessel has finished unloading, repeat steps • Ullage or Innage product gauge
1, 2 and 3 above. • Free water innage gauge
5. The difference between the free water/ice (or ice • Temperatures at each level measured
only) ullage before discharge vs. the free water/ice
• Shore line capacity and condition as stated by the
(or ice only) ullage after discharge is the quantity of
terminal
free water discharged from the vessel.
• Date, time, Inspector’s name, Witness’s name (if
Free Water + Ice Before Discharge any)
- Free Water + Ice After Discharge
= Free Water Discharged from the Vessel

6. Free water coming from the ship may become ice by


the time measurements are taken, or it may remain
water, or it may be a combination of ice and water. If
ullage measurements are used for the free water or ice
layer, distinguishing between ice and water is not
necessary.

During inventories, if ice bottoms are measured, the level


of ice may be found to be somewhat greater than the level
of liquid water on the terminal's inventory records. If the
increase is minimal, it is the result of the tendency of
water to expand after freezing, and is not a gain in the
quantity of water.

Note: Some shore tanks have special center gauge


hatches for measuring water bottoms. These hatches
should be used for ice/water measurements following the
above procedure however care must be taken to reference
the capacity table that applies to the center gauge hatch.

7.11. REPORTING LIQUID LEVEL GAUGES

To avoid errors, each liquid level gauge shall be written


down immediately after the liquid level has been
measured. Saybolt Inspectors should use the appropriate
field form to make initial entries of all raw measurement
data.
Issued: May 1, 2002 Saybolt Inspection Support & Development Group Chapter 7, Page 6 of 6

You might also like