CPU 66MHz 256MB Type: RMMX207

RIFLEX M1 CPU Order #: see below

The processor module is the heart of any M1 controller. It


executes the manufacturer or customer developed programs.
This software defines the reactions of the controller.
The module is equipped with a power supply and an integrat-
ed CAN master. There are one 100 Mbit Ethernet port witch
allows the easy integration of the controller in separated net-
works. The module is equipped with non-volatile ferroelectric
FRAMs. There is an USB interface. An USB memory device is
always needed for the programm memory of the RIFLEX M1
controller.

Features
Processor Module RMMX207
CPU x86 66 MHz (Pentium equivalent)
CF memory not available
SRAM data memory 512 kByte, with battery backup
FRAM data memory 64 kByte
DRAM operating memory 256 MB
PC-Card (program memory) not available
FLASH (program memory) 16 MB internal (8 MB for system software, 8 MB for application)
Interfaces Ethernet 1x RJ-45 socket: Ethernet 10/100BaseT (10/100 MBit/s, Twisted Pair)
COM 1 DSub9m: RS 232 (reduced signal set), RS 422 oder RS 485
COM 2 not available
USB Version 1.1 / 2.0 functionality
CAN 1x 10k … 1MBaud
Operating modes two 16 position rotary switches H/L for operating modes RUNning, TESTing
and PROGramming
State indicating LED’s RUNning green, INITialization yellow and ERRor red
Ethernet LED’s green und yellow
Synchronizing impulse yes
Watchdog yes
Real time clock with battery backup
Operating -30 bis +60 °C ambient temperatur (standard mounting position)
temperature -30 bis +55 °C ambient temperatur (other mounting positions)
Power consumption and inte-
grated power supply power supply own needs CPU available for I/O modules
+5V DC 3400 mA 1400 mA 2000 mA
+15V DC 280 mA 30 mA 250 mA
-15V DC 230 mA 30 mA 200 mA

Remark: The stated power consumption of the CPU does also apply if an external power
supply is used. The stated value is the maximum value und depends on the used interfaces (e.g.
USB, …).

Remark: FRAM, FLASH and CAN are not supported at the moment from the RIFLEX M1
controller.

2015/03 KUM/PFL/GA subject to change Page 1/4


DG DKap Stamm-Bez. Var Ind F Sp

hardware datasheet 43.210.0057515.001.04.4.4


 2015 by Rittmeyer AG, CH-6341 Baar
CPU 66MHz 256MB RMMX207

warning: Only one processor module is allowed in each controller system. If more than one
processor module is installed in one controller system the reactions of the digital and analog out-
puts are unpredictable, and serious damage may occur as a consequence.

attention: Commercially available USB memory devices must not be used with the RMMX207
CPU, because they are not specified for industrial use. Only the below listet USB memory device
may be used for the RMMX207 CPU.

remark: The backup battery of the NV-RAM prevents data from being lost for about 6 months
in the temperature range from 0°C to +60°C. Hence processor modules can be stored without
supplying power for a maximum of 6 months without losing data. Charging of a fully discharged
battery takes about 48 hours. The customer must assume that the battery is discharged on the
time of delivery.
If the battery is low, the NV-Ram will be formatted at the next booting process. Time of the RTC
will be lost. The red ERROR LED lights up and the error message SYS_MAIN: MSys-Software
booting aborted will be shown at the console and will be listed in the logbook.
On the next booting the CPU starts to work as usual, but with empty NV-RAM.

remark: App. 8 MByte of the USB memory device are occupied by operating system and driv-
ers.

remark: The typical lifetime of the battery is 10 years.

remark: Using the FRAM memory, data storage is ensured for more than 10 years without
battery.

Error messages
Error message Meaning
Breakdown of the battery On rebooting the NV-RAM will be deleted.
Processor over temperature Entry in the logbook
SW-Watchdog re-start of the controller (independent from any specific condition)

Integrated power supply


External power supply Description
Input voltage, nominal 24 V DC
Input voltage, allowed range 18 .. 34 V DC
Input voltage, peak value, if t < 1 s / min 40 V DC
Starting current < 5 A @ t < 0,5 ms
Power consumption with maximum charge on output typ. 1400 mA @ 24 V DC
Polarity reversal protection yes

The integrated power supply is galvanically isolated, and generates the voltages for the backplane.
It is automatically detected, if an RMNT25x module is installed on the backplane. Therefore an
RMNT25x can be added, if the modules on the backplane needs more power.
If a RMNT25x module is on the backplane, the integrated power supply will be deactivated, even if
the RMNT25x module is not in use.

2015/03 KUM/PFL/GA subject to change Page 2/4


DG DKap Stamm-Bez. Var Ind F Sp

hardware datasheet 43.210.0057515.001.04.4.4


 2015 by Rittmeyer AG, CH-6341 Baar
CPU 66MHz 256MB RMMX207

State Indicating LEDs


RUN INIT ERR State
OFF OFF OFF Power off
OFF ON OFF Booting (takes about 10 .. 15 s)
OFF ON ON Debug mode (check rotary switches)
OFF OFF ON Booting terminated because of failure.
The standard software package (SSP) or dataset may be invalid. Download
SSP or dataset with the configuration program.
BLINK- BLINK- OFF Booting standard software package (SSP).
ING ING If this condition takes more than 30s, the dataset may be missing.
Download dataset with the configuration program.
ON OFF OFF Booting finished successfully and controller ready.

Operating modes
Rotary Rotary Operating mode
switch L switch H
0 RUN Normal mode
0 PROG Programming mode of the memory device. Only used for new controller.
Attention: First boot controller in RUN mode, then switch to PROG mode.
E TEST Booting with default settings
1 RUN Booting without dataset
2 RUN Booting without SSP
3 RUN Booting in debug mode

Pin Assignments
Connector Pin Signal Description
COM 1 (/TT00) DSub9m 1 +TX Transmit Data+ (RS 422)
2 RXD Receive Data (RS 232)
3 TXD Transmit Data (RS 232)
5 9 4 -TX Transmit Data- (RS 422)
5 GND Ground
6 +RX Receive Data+ (RS 422) / Data+ (RS 485)
6
1 7 RTS Request To Send (RS 232)
8 CTS Clear To Send (RS 232)
9 -RX Receive Data- (RS 422) / Data- (RS 485)

Connector power supply Pin Signal Description


1 + External power supply + 24 V DC
2 - External power supply ground
3 Functional earthing

Connector RJ45 Pin Signal Description


Ethernet ETH 1 1 TXD+ Transmit Data+
2 TXD- Transmit Data-
3 RXD+ Receive Data+
4 n.c. not connected
5 n.c. not connected
1
3
2
4
6 RXD- Receive Data-
7 n.c. not connected
5
6
7
8

8 n.c. not connected

2015/03 KUM/PFL/GA subject to change Page 3/4


DG DKap Stamm-Bez. Var Ind F Sp

hardware datasheet 43.210.0057515.001.04.4.4


 2015 by Rittmeyer AG, CH-6341 Baar
CPU 66MHz 256MB RMMX207

Ethernet-LED’s
LED color Description
green (LinkPuls) LED flashes if transfer on network
yellow (Speed) LED lights up, if the interface works with 100 Mbit/s

Connector USB Pin Signal Description


USB 1 +5 VDC Supply voltage
2 D+ Data Signal+
3 D- Data Signal -
4 GND Ground (reference ground)

CAN-Bus interface
Connector Pin Signal
CAN DSub9m 1
2 CAN_L
3 GND
5 9 4
5 (CAN_SHLD)
6 GND
6
1 7 CAN_H
8
9 (CAN_V+)

remark: The signals put in brackets are not used by the module and do not have any influ-
ence on the function of the module. These signal lines are only connected to guarantee compli-
ance with the standard.
The CAN-Bus must be provided with terminal resistors (121 Ω each) on both ends between the
CAN-H and CAN-L signals. This resistor is not built-in in the module.

remark: The RMMX207 CPU may be used from WinKP / SSP release 2.08.
Order Codes for Module and Accessories
Order Code Order # Description
RMMX207 0057515.001 CPU 66 MHz, 256MB incl. terminal
RMKZ51 0067503.001 Terminal set for CPU
RMUSB1G 0057530.001 USB memory 1GB, industrial, nano
2283890 Ethernet cable, RJ45 connector, 1m
2283891 Ethernet cable, RJ45 connector, 3m
2283892 Ethernet cable, RJ45 connector, 5m
2283893 Ethernet cable, RJ45 connector, 10m
2283894 Ethernet cable, RJ45 connector, 20m

remark: Suitable RS232 cables are described in document 43.270.0002444.001.

2015/03 KUM/PFL/GA subject to change Page 4/4


DG DKap Stamm-Bez. Var Ind F Sp

hardware datasheet 43.210.0057515.001.04.4.4


 2015 by Rittmeyer AG, CH-6341 Baar

You might also like