Professional Documents
Culture Documents
GAMMA's manufacturing facility is located in Colombia, South America, near the city of Medellín.
The Free Trade Agreement in force between Colombia and the United States provides
GAMMA’s fully stocked North American warehouse, located in Houston, TX, provides a
solution for all immediate supply needs.
We hope this brochure will become a tool for decision-making processes and facilitate the
purchasing activity, making GAMMA
Station post
Station posts in this catalog are available in standard strength, high strength, and extra high strength, in
ratings from 95 kV BIL through 350 kV BIL, and for applications ranging from 15 kV through 59 kV operating
voltages.
Each porcelain insulator body is molded from the highest quality raw materials produced in our
state-of-the-art mineral processing facilities, yielding a product of exceptional wet process workability,
purity, and uniformity. The entire surface of each station post receives a smooth, uniform glaze, in either
gray or brown, to provide maximum mechanical porcelain strength, to resist the accumulation of
contaminants on the surface, and to facilitate ease of cleaning via rain or routine maintenance. In addition,
the product line features uniform surface drying and voltage distribution to prevent flashover as well as
dry-band arc suppression for high performance and long-term reliability.
Our polymer station posts insulators core is made of a corrosion resistant epoxy resin fiberglass rod
constructed exclusively for electrical and mechanical applications. Housing and sheds consist of a
one-piece injection molded composite material that chemically bonds to the core rod. This creates a
water-tight seal between the polymer and the rod that is impervious to moisture penetration.
All hardware fittings are manufactured using hot dipped galvanized malleable cast iron or ductile cast iron
and are designed specifically for all mechanical and electrical applications to ensure optimum performance
and service longevity.
All GAMMA Polymer Station Post Insulators are designed, manufactured and tested according to ANSI
standard C29.9.
CERAMIC INSULATORS
CERAMIC INSULATORS
POST TYPE, 95 kV BIL
TR-202 TR-222
Standard Strength Unit Hig Strength Unit
ELECTRICAL VALUES
Typical application voltage, kV 7.5 7.5
, kV 105 105
Low frequency withstand, wet, kV 30 30
Impulse withstand, kV 95 95
PACKING DATA
Net weight, kg 6.80 14.9
Note 1: Dimensions in inches.
Note 2: ANSI 70 gray is standard. brown or white available by request.
Note 3: Insulators can be ordered with M12 thread.
CERAMIC INSULATORS
POST TYPE, 110 kV BIL
4Threads
Ø5/8"- 11
4 Threads
Ø1/2"- 13
12"
10"
3.0" 5.0"
Ø41/4" Ø6.25"
Ø7.0" Ø7.24"
TR-205 TR-225
Standard Strength Unit High Strength Unit
ELECTRICAL VALUES
Typical application voltage, kV 15 15
, kV 125 125
Low frequency withstand, wet, kV 45 45
Impulse withstand, kV 110 110
PACKING DATA
Net weight, kg 8.96 19.9
Note 1: Dimensions in inches.
Note 2: ANSI 70 gray is standard. brown or white available by request.
Note 3: Insulators can be ordered with M12 thread.
CERAMIC INSULATORS
POST TYPE, 150 kV BIL
4 Threads 4 Threads
Ø1/2"- 13 Ø5/8"- 11
14.0" 15.0"
3.0" 5.0"
Ø41/4" Ø6.31"
Ø61/2" Ø8.46"
TR-208 TR-227
Standard Strength Unit High Strength Unit
MECHANICAL VALUES
Cantilever strength, upright, pounds 2000 4000
Cantilever strength, underhung, pounds 2000 4000
Tensile strength, pounds 10000 20000
Torsion strength, inch.pounds 8000 16000
Compression strength, pounds 10000 16000
ELECTRICAL VALUES, kV
Typical application voltage 23 23
170 170
Low frequency withstand, wet 60 60
Impulse withstand 150 150
RADIO INFLUENCE VOLTAGE DATA
Low-frequency test voltage RMS to ground, kV 15 15
Maximum RIV at 1,000 kHz, μV 100 100
3.0" 5.0"
Ø41/4" Ø6.31"
Ø71/2" Ø8.58"
TR-210 TR-231
Standard Strength Unit High Strength Unit
ELECTRICAL VALUES
Typical application voltage, kV 34.5 34.5
, kV 225 225
Low frequency withstand, wet, kV 80 80
Impulse withstand, kV 200 200
PACKING DATA
Net weight, kg 20.25 33.56
Note 1: Dimensions in inches.
Note 2: ANSI 70 gray is standard. brown or white available by request.
Note 3: Insulators can be ordered with M12 thread.
CERAMIC INSULATORS
POST TYPE, 250 kV BIL
4 Threads
4 Threads Ø5/8”- 11
Ø1/2”- 13
3 .0” 5.0”
Ø41/4” Ø6.31”
Ø7.0”) Ø8.74”
TR-214 TR-267
Standard Strength Unit High Strength Unit
ELECTRICAL VALUES
Typical application voltage, kV 46 46
, kV 280 280
Low frequency withstand, wet, kV 100 100
Impulse withstand, kV 250 250
RADIO INFLUENCE VOLTAGE DATA
Low-frequency test voltage RMS to ground, kV 30 30
Maximum RIV at 1,000 kHz, μV 200 200
PACKING DATA
Net weight, kg 24.32 50.34
Note 1: Dimensions in inches.
Note 2: ANSI 70 gray is standard. brown or white available by request.
Note 3: insulators can be ordered with M12 thread.
CERAMIC INSULATORS
POST TYPE, 350 kV BIL
4 Threads 4 Threads
Ø1/2" Ø5/8"
30" 30"
3" 5"
Ø4 1/4" Ø6.3"
Ø8.1" Ø9.1"
TR-216 TR-278
Standard Strength Unit Hig Strength Unit
CRITICAL DISTANCE
Leakage distance, inches 72 72
MECHANICAL VALUES
Cantilever strength, upright, pounds 1500 3000
Cantilever strength, underhung, pounds 1500 3000
Tensile strength, pounds 16000 25000
Torsion strength, inch.pounds 15000 40000
Compression strength, pounds 25000 60000
ELECTRICAL VALUES, kV
Typical application voltage, kV 69 69
, kV 390 390
Low frequency withstand, wet, kV 145 145
Impulse withstand, kV 350 350
PACKING DATA
Net weight, kg 38.3 43.7
Note 1: Dimensions in inches.
Note 2: ANSI 70 gray is standard. brown or white available by request.
Note 3: insulators can be ordered with M12 thread.
CERAMIC INSULATORS
POST TYPE, 550 kV BIL
4 Threads 4 Threads
Ø5/8" Ø5/8"
45" 45"
Ø6.22" Ø6.3"
Ø8.46" Ø9.4"
TR-286 TR-287
Standard Strength Unit Hig Strength Unit
MECHANICAL VALUES
Cantilever strength, upright, pounds 1700 2600
Cantilever strength, underhung, pounds 1700 2600
Tensile strength, pounds 20000 25000
Torsion strength, inch.pounds 40000 90000
Compression strength, pounds 60000 75000
ELECTRICAL VALUES
Typical application voltage , kV 115 115
, kV 610 610
Low frequency withstand, wet, kV 230 230
Impulse withstand, kV 550 550
RADIO INFLUENCE VOLTAGE DATA
Low-frequency test voltage RMS to ground, kV 73 73
Maximum RIV at 1,000 kHz, μV 200 200
PACKING DATA
Net weight, kg 64.9 78.0
Note 1: Dimensions in mm (in).
Note 2: ANSI 70 gray is standard. brown or white available by request.
Note 3: insulators can be ordered with M12 thread.
CERAMIC INSULATORS
POST TYPE, 650 kV BIL
4 hreads 4 hreads
Ø5/8" Ø5/8"
54" 54"
Ø6.22" Ø6.3"
Ø8.46" Ø9.1"
TR-288 TR-289
Standard Strength Unit Hig Strength Unit
CRITICAL DISTANCE
Leakage distance, inches 116 116
MECHANICAL VALUES, kN
Cantilever strength, upright, pounds 1400 2200
Cantilever strength, underhung, pounds 1400 2200
Tensile strength, pounds 20000 25000
Torsion strength, inch.pounds 40000 90000
Compression strength, pounds 60000 75000
ELECTRICAL VALUES
Typical application voltage, kV 138 138
, kV 710 710
Low frequency withstand, wet, kV 275 275
Impulse withstand, kV 650 650
RADIO INFLUENCE VOLTAGE DATA
Low-frequency test voltage RMS to ground, kV 88 88
Maximum RIV at 1,000 kHz, μV 200 200
PACKING DATA
Net weight, kg 71.9 90.9
54"
Ø8.66"
Ø9,84"
TR-289EU
Extra High Strenght
CATALOG NUMBER 289HU0650
ANSI CLASS C29.9 TR289EU
CRITICAL DISTANCE
Leakage distance, inches 120
MECHANICAL VALUES, kN
Cantilever strength, upright, pounds 4100
Cantilever strength, underhung, pounds 4100
Tensile strength, pounds 40000
Torsion strength, inch.pounds 120000
Compression strength, pounds 120000
ELECTRICAL VALUES
Typical application voltage, kV 138
, kV 710
Low frequency withstand, wet, kV 275
Impulse withstand, kV 650
RADIO INFLUENCE VOLTAGE DATA
Low-frequency test voltage RMS to ground, kV 88
Maximum RIV at 1,000 kHz, μV 200
PACKING DATA
Net weight, kg 90.9
Ø5.71"
1.0"
COLOMBIA
YEAR - DAY
7.0"
1.0"
THREAD
2.25" Ø3/8"-16 NC
Ø3.67"
MECHANICAL VALUES
Cantilever strength, pounds 1200
Tensile strength, pounds 5000
Torsion strength, inch.pounds 5000
Compression strength, pounds 5000
ELECTRICAL VALUES, kV
Low frequency withstand, wet 30
Impulse withstand 110
Note 1: Dimensions in inches.
Note 2: ANSI 70 gray is standard. brown available by request.
CERAMIC INSULATORS
SMALL STATION POST, 125 kV BIL
5.71"
1.0" COLOMBIA
YEAR - DAY
7.99"
1.0"
THREAD
2.25" Ø3/8"-16 NC
Ø3.67"
CRITICAL DISTANCE
Leakage distance, inches 17.52
Dry arcing distance, inches 7.0
MECHANICAL VALUES
Cantilever strength, pounds 1000
Tensile strength, pounds 5000
Torsion strength, inch.pounds 5000
Compression strength, pounds 5000
ELECTRICAL VALUES
Low frequency withstand, wet, kV 45
Impulse withstand, kV 125
Note 1: Dimensions in inches.
Note 2: ANSI 70 gray is standard. brown available by request.
CERAMIC INSULATORS
SMALL STATION POST, 125 kV BIL
Ø5.71"
1.0"
COLOMBIA
YEAR - DAY
9.0"
1.0"
THREAD
Ø3/8"-16 NC
2.25"
Ø3.67"
MECHANICAL VALUES
Cantilever strength, pounds 900
Tensile strength, pounds 5000
Torsion strength, inch.pounds 3000
Compression strength, pounds 5000
ELECTRICAL VALUES
Low frequency withstand, wet, kV 50
Impulse withstand, kV 125
Note 1: Dimensions in inches.
Note 2: ANSI 70 gray is standard. brown available by request.
CERAMIC INSULATORS
SMALL STATION POST, 150 kV BIL
Ø5.71"
1.0"
COLOMBIA
YEAR - DAY
10.0"
1.0" THREAD
Ø3/8"-16 NC
2.25”
Ø3.67”
MECHANICAL VALUES
Cantilever strength, pounds 1000
Tensile strength, pounds 5000
Torsion strength, inch.pounds 5000
Compression strength, pounds 5000
ELECTRICAL VALUES
Low frequency withstand, wet, kV 60
Impulse withstand, kV 150
Note 1: Dimensions in inches.
Note 2: ANSI 70 gray is standard. brown available by request.
POLYMER INSULATORS
POLYMER INSULATORS
POST TYPE, 95 kV BIL
4 tapped holes Ø1/2"-13 UNC
Pitch diameter Ø0.4715-Ø0.4650
Length of engagement 0.50 INCH.
Full thread on 3.0 (76) B.C.
Top fitting Both ends.
7.5 kV
SML 2000 Lbs
MWL 800 Lbs
1.18"
7.5"
YY
2.36"
Bottom
Fiting
Ø3.0"
Ø4.0"
Ø4.45"
Ø5.63"
CRITICAL DISTANCE
Leakage distance, inches 11.6
Dry arcing distance, inches 5.7
MECHANICAL VALUES
Cantilever strength, pounds 2000
Cantilever maximum work, pounds 800
Tensile strength, pounds 16000
Torsion strength, inch.pounds 12000
Compression strength, pounds 10000
ELECTRICAL VALUES
Voltage class, kV 7.5
Critical impulse flashover, pos, kV 105
Low frequency withstand, wet, kV 30
Impulse withstand, kV 95
15 kV
SML 2000 Lbs
MWL 800 Lbs
1.18"
2.36"
10"
YY
Bottom
Fiting
Ø3.0"
Ø4.0"
Ø4.45"
5.63"
CRITICAL DISTANCE
Leakage distance, inches 19.3
Dry arcing distance, inches 8.1
MECHANICAL VALUES
Cantilever strength, pounds 2000
Cantilever maximum work, pounds 800
Tensile strength, pounds 16000
Torsion strength, inch.pounds 12000
Compression strength, pounds 10000
ELECTRICAL VALUES
Voltage class, kV 15
Critical impulse flashover, pos, kV 125
Low frequency withstand, wet, kV 45
Impulse withstand, kV 1110
1.18"
2.36"
14"
YY
Bottom
Fiting
Ø3.0"
Ø4.0"
Ø4.45"
5.63"
CRITICAL DISTANCE
Leakage distance, inches 28.4
Dry arcing distance, inches 11.3
MECHANICAL VALUES
Cantilever strength, pounds 2000
Cantilever maximum work, pounds 800
Tensile strength, pounds 16000
Torsion strength, inch.pounds 12000
Compression strength, pounds 10000
ELECTRICAL VALUES
Voltage class, kV 23
Critical impulse flashover, pos, kV 170
Low frequency withstand, wet, kV 60
Impulse withstand, kV 150
1.18"
2.36"
18"
YY
Bottom
Fiting
Ø3.0"
Ø4.0"
Ø4.45"
5.63"
CATALOG NUMBER APTTR210
ANSI CLASS C29.9 TR 210
CRITICAL DISTANCE
Leakage distance, inches 42
Dry arcing distance, inches 15.3
MECHANICAL VALUES
Cantilever strength, pounds 2000
Cantilever maximum work, pounds 800
Tensile strength, pounds 16000
Torsion strength, inch.pounds 12000
Compression strength, pounds 10000
ELECTRICAL VALUES
Voltage class, kV 35
Critical impulse flashover, pos, kV 225
Low frequency withstand, wet, kV 80
Impulse withstand, kV 200
1.18"
2.36"
22"
YY
Bottom
Fiting
Ø3.0"
Ø4.0"
Ø4.45"
5.63"
CATALOG NUMBER APTTR214
ANSI CLASS C29.9 TR 214
CRITICAL DISTANCE
Leakage distance, inches 51.1
Dry arcing distance, inches 18.6
MECHANICAL VALUES
Cantilever strength, pounds 2000
Cantilever maximum work, pounds 800
Tensile strength, pounds 16000
Torsion strength, inch.pounds 12000
Compression strength, pounds 10000
ELECTRICAL VALUES
Voltage class, kV 46
Critical impulse flashover, pos, kV 280
Low frequency withstand, wet, kV 100
Impulse withstand, kV 250
2.36"
30"
Bottom
YY
Fiting
Ø3.0"
Ø4.0"
Ø4.45"
5.63"
CATALOG NUMBER APTTR216
ANSI CLASS C29.9 TR 216
CRITICAL DISTANCE
Leakage distance, inches 51.1
Dry arcing distance, inches 18.6
MECHANICAL VALUES
Cantilever strength, pounds 2000
Cantilever maximum work, pounds 800
Tensile strength, pounds 16000
Torsion strength, inch.pounds 12000
Compression strength, pounds 10000
ELECTRICAL VALUES
Voltage class, kV 46
Critical impulse flashover, pos, kV 280
Low frequency withstand, wet, kV 100
Impulse withstand, kV 250