You are on page 1of 16

Worldwide

www.tyco-fire.com
Contacts

DV-5 Deluge Valve, Diaphragm Style,


1-1/2 thru 8 Inch (DN40 thru DN200),
Deluge System — Wet Pilot Actuation
General
Description
The DV-5 Deluge Valve (described in
Technical Data Sheet TFP1305) is a
diaphragm style valve that depends
upon water pressure in the Diaphragm
Chamber to hold the Diaphragm
closed against the water supply pres-
sure. When the DV-5 Valve is set for
service, the Diaphragm Chamber is
pressurized through the trim connec-
tions from the inlet side of the sys-
tem’s main control valve, for example
an O.S.&Y. gate valve or butterfly valve
(Ref. Figures 1 and 4).
Opening of a wet pilot sprinkler re-
leases water from the Diaphragm
Chamber faster than it can be replen-
ished through the 1/8 inch (3,2 mm)
restriction provided by the Model NOTICE The owner is responsible for maintain-
ASV-1 Automatic Shut-Off Valve in the The DV-5 Deluge Valve with Wet Pilot ing their fire protection system and
diaphragm supply connections (Item Actuation Trim described herein must devices in proper operating condition.
5 - Fig. 3A and 5, also described in be installed and maintained in compli- Contact the installing contractor or
Technical Data Sheet TFP1384). This ance with this document, as well as manufacturer with any questions.
results in a rapid pressure drop in the with the applicable standards of the
Diaphragm Chamber and the force National Fire Protection Association,
differential applied through the Dia- in addition to the standards of any oth-
phragm that holds it in the set position er authorities having jurisdiction. Fail-
is reduced below the valve trip point. ure to do so may impair the perfor-
The water supply pressure then forces mance of these devices.
the Diaphragm open permitting water
to flow into the system piping, as well
as through the Alarm Port to actuate
the system alarms.
As water flows into the system, the pi-
lot chamber of the Model ASV-1 Au-
tomatic Shut-Off Valve (Item 5 - Fig.
3A and 5) becomes pressurized and
the ASV-1 automatically shuts off the
diaphragm chamber supply flow to
the DV-5 Diaphragm Chamber. Shut-
ting off the diaphragm chamber sup-
ply flow prevents the DV-5 Diaphragm
Chamber from becoming re-pressur-
ized, thereby preventing inadvertent
closing of the DV-5 during a fire (as
may be the case if an actuation de-
vice other than a pilot sprinkler were
to be closed after its initial operation,
for example a remote manual control
station).

Page 1 of 16 JULY 2014 TFP1310


TFP1310
Page 2 of 16

13

6
5

11 8

7 9

3 4

1 2

1 - DV-5 Deluge Valve 7 - Water Supply Pressure Gauge 12 - Waterflow Pressure Alarm Switch
2 - Main Control Valve (N.O.) 8 - Diaphragm Chamber Pressure (Shown at Rear of Valve)
3 - Diaphragm Chamber Supply Gauge 13 - Water Motor Alarm (Optional)
Control Valve (N.O.) 9 - System Drain Valve (N.C.)
4 - Local Manual Control Station 10 - Main Drain Valve (N.C.)
5 - Open Nozzles or Sprinklers (Shown at Rear of Valve)
6 - Wet Pilot Line Sprinklers 11 - Diaphragm Chamber Automatic
(Fire Detection) Shut-Off Valve

FIGURE 1 (1 OF 2)
SYSTEM SCHEMATIC (FRONT VIEW)
WET PILOT ACTUATION
TFP1310
Page 3 of 16

13

11

12

3
1

10
2

1 - DV-5 Deluge Valve 6 - Wet Pilot Line Sprinklers 10 - Main Drain Valve (N.C.)
2 - Main Control Valve (N.O.) (Fire Detection) 11 - Diaphragm Chamber Automatic
3 - Diaphragm Chamber Supply 7 - Water Supply Pressure Gauge Shut-Off Valve
Control Valve (N.O.) (Shown at Front of Valve) 12 - Waterflow Pressure Alarm Switch
4 - Local Manual Control Station 8 - Diaphragm Chamber Pressure 13 - Water Motor Alarm (Optional)
(Shown at Front of Valve) Gauge (Shown at Front of Valve)
5 - Open Nozzles or Sprinklers 9 - System Drain Valve (N.C.)

FIGURE 1 (2 OF 2)
SYSTEM SCHEMATIC (REAR VIEW)
WET PILOT ACTUATION
TFP1310
Page 4 of 16

WATERFLOW
the pilot line up to 500 feet to the most
PRESSURE DELUGE
remote pilot sprinkler.
ALARM WET PILOT
SWITCH
Provision must be made for install-
ACTUATION
TRIM
ing a 5.6 K-factor orifice, Inspector’s
Test Connection at the most hydrauli-
cally demanding location of a wet pi-
lot line (usually adjacent to the highest
NOTES:
and most remote wet pilot sprinkler or
1. SEE FIGURE 3, PER VALVE SIZE manual control station).
AS APPLICABLE, FOR TRIM
ARRANGEMENT WITH BILL OF NOTES:
MATERIALS AND COMPONENT
PART NUMBERS. Wet Pilot Lines must be maintained at
2. TRIM SHOWN FULLY ASSEMBLED;
a minimum temperature of 40°F (4°C).
COMPONENTS SUCH AS GAUGES At a minimum, it is recommended that
DV-5 AND SWITCHES MAY REQUIRE internally galvanized pipe and cast
DELUGE ASSEMBLY IN TRIM AT VALVE
VALVE INSTALLATION. iron fittings be used for wet pilot lines.

GROOVED
SYSTEM
SHUT-OFF
Materials Of
COUPLING VALVE
Construction
FIGURE 2 NOTES:
DV-5 PRE-TRIMMED DELUGE VALVE, The galvanized or brass nipples and
WET PILOT ACTUATION fittings for the Valve Trim provide cor-
rosion resistance and are intended to
Technical The trim arrangement is provided with
galvanized, black, or brass nipples
extend the life of the installation of the
DV-5 Valve when exposed to internal
Data and fittings. The galvanized and brass
trim are intended for non-corrosive
and external corrosive conditions. Al-
though these selections are intended
Approvals or corrosive conditions, whereas the to resist corrosion, it is recommend-
UL and C-UL Listed black trim is principally intended for ed that the end user or other techni-
FM Approved. use with AFFF systems. cal expert familiar with conditions at
NOTE: When the system pressure is the proposed installation be consulted
Valve Trim greater than 175 psi (12,1 bar), pro- with respect to these selections for a
The Vertical Wet Pilot Actuation Trim vision is to be made to replace the given corrosive condition.
(Fig. 3A/3B) and Horizontal Wet Pilot standard order 300 psi (20,7 bar) Wa-
Actuation Trim (Fig. 5) form a part of Systems using a seawater or brack-
ter Pressure Gauges, shown in Figure ish water supply require special con-
the laboratory listings and approvals 3A/3B and 5, with separately ordered
for the DV-5 Valve and is necessary siderations in order to extend the life
600 psi (41,4 bar) Water Pressure of the valve and trim. This type of sys-
for its proper operation. Gauges. tem ideally should be configured with
Each package of trim includes the fol- The Wet Pilot Actuation Trim provides a primary source of clean fresh water
lowing items: for connection of a detection system (e.g., a pressurized water tank) and
• Water Supply Pressure Gauge consisting of wet pilot line sprinklers only upon system operation is the
(heat detectors) and manual control secondary water supply (seawater or
• Diaphragm Chamber stations interconnected with minimum brackish water) allowed to enter the
Pressure Gauge 1/2 inch (DN15) Schedule 40 steel system. After the system operation,
• Diaphragm Chamber Connections pipe. The pilot line is connected to the the system should then be thoroughly
Wet Pilot Detection connection shown flushed with clean fresh water. Follow-
• Manual Control Station in Figure 3B. Nominal installation di- ing this recommendation will increase
• Main Drain Valve mensions for the Vertical Wet Pilot Ac- the service life of the DV-5 Valve and
tuation Trim are shown in Figure 4. Valve Trim.
• System Drain Valve
Pilot sprinklers are to be minimum 5.6 Pressure Gauges. Bronze bourdon
• Alarm Test Valve K-factor orifice listed or approved au- tube with brass socket.
• Automatic Drain Valve tomatic sprinklers. The Model FTR-1 Gauge Test Valve. Bronze body per
Fixed Temperature Release described ASTM B584.
The following items are included in the in Technical Data Sheet TFP1388 may
Pre-trimmed Valve Assembly and can be used as an alternative wet pilot line Manual Control Station. Corrosion
be ordered separately for the valve device. Manual Control Stations are to resistant copper alloys and glass filled
trim: be the Model MC-1 described in Tech- PTFE seals. Thermoplastic enclosure.
• Model BFV-N Butterfly Valve nical Data Sheet TFP1382. Automatic Drain Valve. Brass body
• Waterflow Pressure Alarm Switch The maximum height of a wet pilot line per ASTM B584, Type 440 stainless
(PS10-2) above the DV-5 Valve must not exceed steel or brass per ASTM B134 Ball,
the limitations shown in Graph A as a and galvanized steel inlet.
• Figure 577 Grooved Coupling
function of the minimum water sup- Automatic Shut-Off Valve. Brass
To ease field assembly of the trim ar- ply pressure to the DV-5 Valve for an body, cover, and center seat per UNS
rangement, the vertical trim compo- equivalent length (pipe plus fittings) of C36000, Type 316 stainless steel
nents are provided partially assem-
bled as shown in Figure 3B.
TFP1310
Page 5 of 16

NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N
1 300 psi/ 2000 kPa Water Pressure Gauge . . 2 92-343-1-005 19 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH 37 1/2" x 7" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002 20 3/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH 38 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
3 Model MC-1 Manual Control Station . . . . . . 1 52-289-2-001 21 1/2" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 5 CH 39 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
4 Model AD-1 Automatic Drain Valve . . . . . . . 1 52-793-2-004 22 3/4" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH 40 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
5 Model ASV-1 Automatic Shut-Off Valve . . . 1 92-343-1-021 23 1/4" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH 41 3/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
6 Item No. Not Used 24 1/2" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 8 CH 42 3/4" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 8 CH
7 1/2" Ball Valve . . . . . . . . . . . . . . . . . . . . . . . 2 46-050-1-004 25 3/4" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH 43 3/4" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
8 1/2" Spring Loaded Check Valve . . . . . . . . . 1 92-322-1-002 26 1/2" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 CH 44 3/4" x 4" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
9 1/2" Y-Strainer . . . . . . . . . . . . . . . . . . . . . . . 1 52-353-1-005 27 1/2" x 1/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 3 CH 45 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
10 3/4" Swing Check Valve . . . . . . . . . . . . . . . . 1 46-049-1-005 28 3/4" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH
11 3/4" Angle Valve . . . . . . . . . . . . . . . . . . . . . . 2 46-048-1-005 29 3/4" x 1/2" x 3/4" Tee . . . . . . . . . . . . . . . . . . 2 CH COMPONENTS INCLUDED ONLY IN
12 Drip Funnel Connector . . . . . . . . . . . . . . . . . 1 92-211-1-005 30 3/4" x 3/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 1 CH PRE-TRIMMED VALVE ASSEMBLIES:
13 Drip Funnel Bracket . . . . . . . . . . . . . . . . . . . 1 92-211-1-003 31 1/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH A1 Waterflow Pressure Alarm Switch,
14 Drip Funnel . . . . . . . . . . . . . . . . . . . . . . . . . . 1 92-343-1-007 32 1/2" x Close Nipple. . . . . . . . . . . . . . . . . . . . 3 CH Model PS10-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25710
15 3/32" Vent Fitting . . . . . . . . . . . . . . . . . . . . . 1 92-032-1-002 33 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 10 CH A2 Butterfly Valve, Power Ball 300:
16 1/4" x 18" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH 34 1/2" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH 1-1/2" (DN40) . . . . . . . . . . . . . . . . . . . . . . . . 1 51024A
17 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 1 CH 35 1/2" x 2-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 4 CH 2" (DN50) . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 51021A
18 1/2" x 12" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH 36 1/2" x 5" Nipple. . . . . . . . . . . . . . . . . . . . . . . 2 CH A3 Figure 577 Coupling:
1-1/2" (DN40) . . . . . . . . . . . . . . . . . . . . . . . . 1 57715ACP
2" (DN50) . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 57720ACP
16 41 11
A1 Select Appropriate Nipple Sizes
30 Nipple per DV-5 Deluge Valve Size
27 42 45 Number
1-1/2" (DN40) 2" (DN50)
15 38 1/2" x 1-1/2" 1/2" x 2"
29 (GREEN 39 1/2" x 2" 1/2" x 1-1/2"
LOCATION 24
20 TINT) 35 40 1/2" x 5" 1/2" x 5-1/2"
FOR OPTIONAL 4 45 3/4" x 1-1/2" 3/4" x 2-1/2"
ELECTRICALLY 35 28 42 33
SUPERVISED 42 22 21
N.O. ALARM 43 36 21 32
CONTROL 42 25 33
VALVE 42
22 26
33 10 26
42 42 24 40
24 42 35 24 24
29 12 1
14 26
38 28 33 32
11 44 33 27
7
13 37
35 1 5 33 3
A3
21 8
NOTES: 19 2 21
1. Wet Pilot Actuation Trim is A2
36 24 32
comprised of Items 1-45. 34
Items A1-A3 included only in 39 18
pre-trimmed valve assemblies 9
31 27 33 17
33 24 24
as applicable; otherwise
31 33
ordered separately. 23 2" (DN50)
2. All Fittings and Nipples are GROOVE x GROOVE
galvanized (Standard Order). DV-5 DELUGE VALVE 21
3. CH: Common Hardware. SHOWN
4. See Figure 2 of TFP1305 for 33
Valve Port identification.
5. Route all Tubing to Drip Funnel, 7
Item 14.
FIGURE 3A (1 OF 3)
1-1/2 AND 2 INCH (DN40 AND DN50) DV-5 DELUGE VALVES
EXPLODED VIEW OF VERTICAL WET PILOT ACTUATION TRIM

spring, and Nylon fabric reinforced, Tubing Connector. Brass per ASTM
natural rubber diaphragm per ASTM B16.
D2000. Tubing. Type L copper per ASTM B88.
Ball Valve. Corrosion resistant copper Pipe Fittings. Galvanized mallea-
alloys and glass filled PTFE seals. ble iron per ANSI B16.3 or cast iron
Spring Loaded Check Valve. Brass per ANSI B16.4; black malleable iron
body and buna-n seal. per ANSI B16.3 or cast iron per ANSI
B16.4; or, bronze per ANSI B16.15.
Y-Strainer. Bronze body per ASTM
B584 and Type 304 stainless steel Pipe Nipples. Schedule 40 galvanized
screen. steel per ASTM A53 or A135; Schedule
40 black steel per ASTM A53 or A135;
Swing Check Valve. Bronze body per
or, Schedule 40 red brass pipe per
ASTM B584 and BUNA-N seal.
ASTM B43.
Angle Valve. Bronze body per ASTM
B584 and nitrile disc (TEFLON disc for
2 inch size valve).
3/32” Vent Fitting. Brass per ASTM
B16.
TFP1310
Page 6 of 16

NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N
1 300 psi/ 2000 kPa Water Pressure Gauge . . 2 92-343-1-005 16 3/32" Vent Fitting . . . . . . . . . . . . . . . . . . . . . 1 92-032-1-002 31 3/4" x 3/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 1 CH
2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002 17 1/4" x 18" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH 32 1-1/4" x 3/4" x 1-1/4" Tee. . . . . . . . . . . . . . . 1 CH
3 Model MC-1 Manual Control Station . . . . . . 1 52-289-2-001 18 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 1 CH 33 1/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH
4 Model AD-1 Automatic Drain Valve . . . . . . . 1 52-793-2-004 19 1/2" x 12" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH 34 1/2" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH
5 Model ASV-1 Automatic Shut-Off Valve . . . 1 92-343-1-021 20 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH 35 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 13 CH
6 Item No. Not Used 21 3/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH 36 1/2" x 2-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 2 CH
7 1/2" Ball Valve . . . . . . . . . . . . . . . . . . . . . . . 2 46-050-1-004 22 1/2" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 5 CH 37 1/2" x 3-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
8 1/2" Spring Loaded Check Valve . . . . . . . . . 1 92-322-1-002 23 3/4" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH 38 1/2" x 4" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
9 1/2" Y-Strainer . . . . . . . . . . . . . . . . . . . . . . . 1 52-353-1-005 24 1/4" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH 39 1/2" x 4-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
10 3/4" Swing Check Valve . . . . . . . . . . . . . . . . 1 46-049-1-005 25 1/2" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 8 CH 40 1/2" x 5" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
11 3/4" Angle Valve . . . . . . . . . . . . . . . . . . . . . . 1 46-048-1-005 26 3/4" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH 41 1/2" x 5-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
12 1-1/4" Angle Valve . . . . . . . . . . . . . . . . . . . . 1 46-048-1-007 27 1/2" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 CH 42 1/2" x 7" Nipple. . . . . . . . . . . . . . . . . . . . . . . 2 CH
13 Drip Funnel Connector . . . . . . . . . . . . . . . . . 1 92-211-1-005 28 1/2" x 1/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 3 CH 43 3/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 3 CH
14 Drip Funnel Bracket . . . . . . . . . . . . . . . . . . . 1 92-211-1-003 29 3/4" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH 44 3/4" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 5 CH
15 Drip Funnel . . . . . . . . . . . . . . . . . . . . . . . . . . 1 92-343-1-007 30 3/4" x 1/2" x 3/4" Tee . . . . . . . . . . . . . . . . . . 2 CH 45 3/4" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
46 3/4" x 4-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
47 1-1/4" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . 1 CH
17 43 11
48 1-1/4" x 4" Nipple. . . . . . . . . . . . . . . . . . . . . 1 CH
A1 COMPONENTS INCLUDED ONLY IN
31 PRE-TRIMMED VALVE ASSEMBLIES:
28 44 46 A1 Waterflow Pressure Alarm Switch,
16 25 Model PS10-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25710
30 (GREEN A2 Model BFV-N Butterfly Valve, 3" (DN80) . . . 1 59300F030N
LOCATION 21 TINT)
A3 Figure 577 Coupling, 3" (DN80) . . . . . . . . . . 1 57730ACP
FOR OPTIONAL 36 26 35
ELECTRICALLY 36 29
SUPERVISED 44 22
23 27 4 41 22 35
N.O. ALARM 45 35
CONTROL 44 43
VALVE 44 27
23 38
35 10 25 42
43 13
44 25 25
25 15 1
30 27
35 35 34
32 35 28
7 47 48 14
42
12 5 35 3
40
1
8
NOTES: 22
1. Wet Pilot Actuation Trim is 22
20 2 A3
25 34
comprised of Items 1-48. 37
Items A1-A3 included only in 19
39 A2 9
pre-trimmed valve assemblies 35 18
35 25 25
as applicable; otherwise 35
33 28 35
ordered separately.
2. All Fittings and Nipples are 33
24
galvanized (Standard Order). 3" (DN80) 22
3. CH: Common Hardware. GROOVE x GROOVE
DV-5 DELUGE VALVE 35
4. See Figure 2 of TFP1305 for
SHOWN
Valve Port identification.
5. Route all Tubing to Drip Funnel, 7
Item 15.
FIGURE 3A (2 OF 3)
3 INCH (DN80) DV-5 DELUGE VALVE
EXPLODED VIEW OF VERTICAL WET PILOT ACTUATION TRIM
TFP1310
Page 7 of 16

NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N
1 300 psi/ 2000 kPa Water Pressure Gauge . . 2 92-343-1-005 25 1/2" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 8 CH 49 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002 26 1" 90° Elbow. . . . . . . . . . . . . . . . . . . . . . . . . 1 CH 50 2" x 3" Nipple . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
3 Model MC-1 Manual Control Station . . . . . . 1 52-289-2-001 27 1/2" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 CH 51 2" x 5" Nipple . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
4 Model AD-1 Automatic Drain Valve . . . . . . . 1 52-793-2-004 28 1/2" x 1/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 3 CH
5 Model ASV-1 Automatic Shut-Off Valve . . . 1 92-343-1-021 29 3/4" x 1/2" x 3/4" Tee . . . . . . . . . . . . . . . . . . 2 CH COMPONENTS INCLUDED ONLY IN
6 Item No. Not Used 30 1" x 1" x 1/2" Tee . . . . . . . . . . . . . . . . . . . . . 1 CH PRE-TRIMMED VALVE ASSEMBLIES:
7 1/2" Ball Valve . . . . . . . . . . . . . . . . . . . . . . . 2 46-050-1-004 31 1" x 3/4" x 1" Tee . . . . . . . . . . . . . . . . . . . . . 1 CH A1 Waterflow Pressure Alarm Switch,
8 1/2" Spring Loaded Check Valve . . . . . . . . . 1 92-322-1-002 32 2" x 1" x 2" Tee . . . . . . . . . . . . . . . . . . . . . . . 1 CH Model PS10-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25710
9 1/2" Y-Strainer . . . . . . . . . . . . . . . . . . . . . . . 1 52-353-1-005 33 1/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH A2 Model BFV-N Butterfly Valve:
10 3/4" Swing Check Valve . . . . . . . . . . . . . . . . 1 46-049-1-005 34 1/2" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH 4" (DN100) . . . . . . . . . . . . . . . . . . . . . . . . . . 1 59300F040N
11 1" Angle Valve . . . . . . . . . . . . . . . . . . . . . . . 1 46-048-1-006 35 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 10 CH 6" (DN150) . . . . . . . . . . . . . . . . . . . . . . . . . . 1 59300F060N
12 2" Angle Valve . . . . . . . . . . . . . . . . . . . . . . . 1 46-048-1-009 36 1/2" x 2-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 3 CH 8" (DN200) . . . . . . . . . . . . . . . . . . . . . . . . . . 1 59300F080N
13 Drip Funnel Connector . . . . . . . . . . . . . . . . . 1 92-211-1-005 37 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH A3 Figure 577 Coupling:
14 Drip Funnel Bracket . . . . . . . . . . . . . . . . . . . 1 92-211-1-003 38 1/2" x 5" Nipple. . . . . . . . . . . . . . . . . . . . . . . 2 CH 4" (DN100) . . . . . . . . . . . . . . . . . . . . . . . . . . 1 57740ACP
15 Drip Funnel . . . . . . . . . . . . . . . . . . . . . . . . . . 1 92-343-1-007 39 1/2" x 6" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH 6" (DN150) . . . . . . . . . . . . . . . . . . . . . . . . . . 1 57760ACP
16 3/32" Vent Fitting . . . . . . . . . . . . . . . . . . . . . 1 92-032-1-002 40 1/2" x 7" Nipple. . . . . . . . . . . . . . . . . . . . . . . 2 CH 8" (DN200) . . . . . . . . . . . . . . . . . . . . . . . . . . 1 57780ACP
17 Select Tubing per Table . . . . . . . . . . . . . . . . 1 CH 41 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
18 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 1 CH 42 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
19 1/2" x 24" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH 43 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
20 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH 44 3/4" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH Select Appropriate Tube Size
21 3/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH 45 3/4" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH Tube per DV-5 Deluge Valve Size
22 1/2" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 5 CH 46 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH No. 4" 6" 8"
23 1" Union . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH 47 1" x Close Nipple . . . . . . . . . . . . . . . . . . . . . 5 CH (DN100) (DN150) (DN200)
24 1/4" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH 48 1" x 3" Nipple . . . . . . . . . . . . . . . . . . . . . . . . 1 CH 17 1/4" x 24" 1/4" x 24" 1/4" x 32"

Select Appropriate Nipple Sizes


Nipple per DV-5 Deluge Valve Size
17 47 11 No. 4" 6" 8"
A1 30 (DN100) (DN150) (DN200)
37 1/2" x 3" 1/2" x 3" 1/2" x 5"
47 49
28 41 1/2" x 2-1/2" 1/2" x 5-1/2" 1/2" x 8-1/2"
42 1/2" x 2" 1/2" x 3" 1/2" x 3-1/2"
29 16 25 43 1/2" x 6-1/2" 1/2" x 7-1/2" 1/2" x 9"
LOCATION 21 (GREEN 36 46 3/4" x 2-1/2" 3/4" x 3-1/2" 3/4" x 4-1/2"
FOR OPTIONAL TINT) 26 49 1" x 6" 1" x 9" 1" x 12"
37
ELECTRICALLY 36 47
SUPERVISED 44 4 39 22 42 22
23 23 27 35
N.O. ALARM 45
CONTROL 47
31 36 27
VALVE 25 43
10 47 13
35 25 25
25 46 15 1
48 27
29
35 34
41 35 28
14 40
7 32
50 51 5 35 3
12
8
NOTES: 1 22
40 9
1. Wet Pilot Actuation Trim is
22 25 34
comprised of Items 1-51. 2 38
20 19
Items A1-A3 included only in A3
pre-trimmed valve assemblies 38 35 18
as applicable; otherwise 25 25
35 A2 35
ordered separately. 35
33 28
2. All Fittings and Nipples are
galvanized (Standard Order). 33 22
24
3. CH: Common Hardware. 4" (DN100)
4. See Figure 2 of TFP1305 for GROOVE x GROOVE 35
Valve Port identification. DV-5 DELUGE VALVE
SHOWN 7
5. Route all Tubing to Drip Funnel,
Item 15.
FIGURE 3A (3 OF 3)
4, 6, AND 8 INCH (DN100, DN150, AND DN200) DV-5 DELUGE VALVES
EXPLODED VIEW OF VERTICAL WET PILOT ACTUATION TRIM
TFP1310
Page 8 of 16

Nipple Select Appropriate Nipple and Tube Sizes per DV-5 Deluge Valve Size
Number 1-1/2" (DN40) 2" (DN50) 3" (DN80) 4" (DN100) 6" (DN150) 8" (DN200)
1 1/2" x Close 1/2" x 2" 1/2" x 1-1/2" 1/2" x 2-1/2" 1/2" x 5-1/2" 1/2" x 8-1/2"
2 1/2" x Close 1/2" x Close 1/2" x 1-1/2" 1/2" x 2" 1/2" x 3" 1/2" x 3-1/2"
3 1/2" x 5" 1/2" x 5-1/2" 1/2" x 7" 1/2" x 6-1/2" 1/2" x 7-1/2" 1/2" x 9"
4 3/4" x 1-1/2" 3/4" x 1-1/2" 3/4" x 1-1/2" 3/4" x 2-1/2" 3/4" x 3-1/2" 3/4" x 4-1/2"
5 3/4" x 1-1/2" 3/4" x 2-1/2" 3/4" x 4-1/2" 1" x 6" 1" x 9" 1" x 12"
6 1/2" x 1-1/2" 1/2" x 1-1/2" 1/2" x 1-1/2" 1/2" x 3" 1/2" x 3" 1/2" x 5"
Main Drain
3/4" NPT 3/4" NPT 1-1/4" NPT 2" NPT 2" NPT 2" NPT
Size
Tube 1 1/4" x 18" 1/4" x 18" 1/4" x 18" 1/4" x 24" 1/4" x 24" 1/4" x 32"

VENT FITTING NOTES:


(GREEN TINT) 1. Install subassemblies in alphabetical order.
WATERFLOW
PRESSURE ALARM 2. See Figure 2 of TFP1305 for Valve Port
TUBE 1 identification.
SWITCH, ORDERED
SEPARATELY SYSTEM 3. Route all Tubing to Drip Funnel.
DRAIN VALVE 4. When DV-5 trips, Automatic Shut-Off Valve
(NORMALLY shuts off diaphragm chamber supply.
3/4 INCH NPT CLOSED)
CONNECTION FOR 5. Nipples 1-6 and Tube 1 vary in length relative
B
WATER MOTOR to DV-5 size. Select per table. All other nipples
ALARM NIPPLE and tubing packed unassembled shall be
4 installed per appropriate trim exploded view,
AUTOMATIC Figure 3A Part 1, 2, or 3.
LOCATION DRAIN VALVE
FOR OPTIONAL
ELECTRICALLY
SUPERVISED NIPPLE
N.O. ALARM NIPPLE 5
CONTROL 6
VALVE 1/2 INCH NPT
4" (DN100) CONNECTION
DRIP
FLANGE x FLANGE FOR "WET PILOT
FUNNEL
NIPPLE DV-5 DELUGE DETECTION" NIPPLE
1 VALVE SHOWN 2
1-1/4 INCH NPT
CONNECTION NIPPLE
TO DRAIN 3
MAIN A
DRAIN VALVE DIAPHRAGM
(NORMALLY D CHAMBER
CLOSED) PRESSURE
GAUGE
ALARM MAIN DRAIN
TEST VALVE CONNECTION
(NORMALLY (SIZED PER MANUAL
CLOSED) TABLE) CONTROL
STATION
SYSTEM
WATER C AUTOMATIC
SUPPLY DIAPHRAGM
CHAMBER SUPPLY SHUT-OFF VALVE
PRESSURE (NORMALLY
GAUGE CONTROL VALVE
(NORMALLY OPEN)
OPEN) 1/2 INCH NPT
CONNECTION FROM
WATER SUPPLY
FIGURE 3B
1-1/2 THRU 8 INCH (DN40 THRU DN200) DV-5 DELUGE VALVES
OPERATIONAL COMPONENTS OF VERTICAL WET PILOT ACTUATION TRIM
EXPLODED ARRANGEMENT OF SEMI-PREASSEMBLED TRIM
TFP1310
Page 9 of 16

Valve Nominal Installation Dimensions in Inches and (mm)


Size A B C D E F G H J K L M N
1-1/2" 7.00 8.88 13.19 10.50 15.25 1.25 5.81 1.81 3.00 7.00 3.88 8.00 4.02
DN40 (177,8) (225,4) (335,0) (266,7) (387,4) (31,8) (147,6) (46,0) (76,2) (177,8) (98,4) (204,0) (102,1)
2" 7.13 9.13 13.19 10.50 15.56 0.94 6.00 2.00 3.00 7.00 3.00 8.63 4.09
DN50 (181,0) (231,8) (335,0) (266,7) (395,3) (23,8) (152,4) (50,8) (76,2) (177,8) (76,2) (220,0) (103,9)
3" 7.81 10.44 13.19 10.50 19.13 1.63 6.69 2.69 4.25 7.00 0.88 12.75 3.85
DN80 (198,4) (265,1) (335,0) (266,7) (485,8) (41,3) (170,0) (68,3) (108,0) (177,8) (22,2) (324,0) (98,0)
4" 10.00 11.75 14.31 10.50 22.13 1.75 8.56 4.44 6.25 7.13 0.63 15.75 4.56
DN100 (254,0) (298,5) (363,5) (266,7) (562,0) (44,5) (217,5) (112,7) (158,8) (181,0) (15,9) (400,0) (116,0)
6" 11.38 14.31 15.31 10.50 23.31 3.50 9.94 5.81 6.25 7.13 1.81 18.13 5.86
DN150 (289,0) (363,5) (388,9) (266,7) (592,1) (88,9) (252,4) (147,6) (158,8) (181,0) (46,0) (460,4) (149,0)
8" 12.00 16.00 16.25 10.50 25.50 1.75 10.75 6.50 6.25 7.13 7.38 22.50 5.26
DN200 (304,8) (406,4) (412,8) (266,7) (647,7) (44,5) (273,1) (165,1) (158,8) (181,0) (187,3) (570,0) (134,0)

* MINIMUM CLEARANCE

A* B C* D*

E*
M
L

N
F
H K

G J

LEFT VIEW FRONT VIEW


FIGURE 4
1-1/2 THRU 8 INCH (DN40 THRU DN200) DV-5 DELUGE VALVES
VERTICAL WET PILOT ACTUATION / NOMINAL INSTALLATION DIMENSIONS
TFP1310
Page 10 of 16

NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N
1 300 psi/ 2000 kPa Water Pressure Gauge . . 2 92-343-1-005 8 1/2" Spring Loaded Check Valve . . . . . . . . . 1 92-322-1-002 15 3/32" Vent Fitting . . . . . . . . . . . . . . . . . . . . . 1 92-032-1-002
2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002 9 1/2" Y-Strainer . . . . . . . . . . . . . . . . . . . . . . . 1 52-353-1-005 16 1/4" x 18" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH
3 Model MC-1 Manual Control Station . . . . . . 1 52-289-2-001 10 3/4" Swing Check Valve . . . . . . . . . . . . . . . . 1 46-049-1-005 17 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 1 CH
4 Model AD-1 Automatic Drain Valve . . . . . . . 1 52-793-2-004 11 3/4" Angle Valve . . . . . . . . . . . . . . . . . . . . . . 2 46-048-1-005 18 1/2" x 12" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH
5 Model ASV-1 Automatic Shut-Off Valve . . . 1 92-343-1-021 12 Drip Funnel Connector . . . . . . . . . . . . . . . . . 1 92-211-1-005 19 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
6 Item No. Not Used 13 Drip Funnel Bracket . . . . . . . . . . . . . . . . . . . 1 92-211-1-003 20 3/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
7 1/2" Ball Valve . . . . . . . . . . . . . . . . . . . . . . . 2 46-050-1-004 14 Drip Funnel . . . . . . . . . . . . . . . . . . . . . . . . . . 1 92-343-1-007 21 1/2" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 5 CH
22 3/4" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH
23 1/4" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH
33 33 24 1/2" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 8 CH
33 24 25 3/4" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH
33
5 40 26 1/2" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 CH
1 7 24 27 1/2" x 1/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 3 CH
28 3/4" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH
21 9 29 3/4" x 1/2" x 3/4" Tee . . . . . . . . . . . . . . . . . . 2 CH
2 8 26 30 3/4" x 3/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 1 CH
19 31 1/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH
2" (DN50) 24 32 1/2" x Close Nipple. . . . . . . . . . . . . . . . . . . . 3 CH
GROOVE x GROOVE 32 33 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 10 CH
33 1 34 1/2" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
DV-5 DELUGE VALVE 34 35 1/2" x 2-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 4 CH
31 31 SHOWN 37 36 1/2" x 5" Nipple. . . . . . . . . . . . . . . . . . . . . . . 2 CH
24 33 37 1/2" x 7" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
39 21 38 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
23 21 32 39 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
26 40 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
36 33 41 3/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
27 33 27 42 3/4" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 8 CH
43 3/4" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
44 3/4" x 4" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
21 45 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
35 35 3
7 COMPONENTS ORDERED SEPARATELY:
36 A1 Waterflow Pressure Alarm Switch,
Model PS10-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25710
LOCATION 38
FOR OPTIONAL 24 32
ELECTRICALLY 33 Nipple
Select Appropriate Nipple Sizes
per DV-5 Deluge Valve Size
SUPERVISED Number
N.O. ALARM 29 24 1-1/2" (DN40) 2" (DN50)
38 1/2" x 1-1/2" 1/2" x 2"
CONTROL 24 17
22 39 1/2" x 2" 1/2" x 1-1/2"
43 42
VALVE 18 40 1/2" x 5" 1/2" x 5-1/2"
10 45 3/4" x 1-1/2" 3/4" x 2-1/2"
42 42 4
20 27 26 NOTES:
29 28 35 1. Wet Pilot Actuation Trim is comprised of
42 14 Items 1-45. Item A1 ordered separately.
30
35 15 2. All Fittings and Nipples are galvanized
(GREEN
44 (Standard Order).
A1 TINT) 16 12
(ORDERED 3. CH: Common Hardware.
SEPARATELY) 42 4. See Figure 2 of TFP1305 for Valve Port
41 identification.
11 22
5. Route all Tubing to Drip Funnel, Item 14.
42 42 45 13
11 6. Horizontal Arrangement uses only 7 out of
28 25
8 of Item 24, and 9 out of 10 of Item 33.
42 Discard unused material.

FIGURE 5 (1 OF 3)
1-1/2 AND 2 INCH (DN40 AND DN50) DV-5 DELUGE VALVES
EXPLODED VIEW OF HORIZONTAL WET PILOT ACTUATION TRIM
TFP1310
Page 11 of 16

NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N
1 300 psi/ 2000 kPa Water Pressure Gauge . . 2 92-343-1-005 5 Model ASV-1 Automatic Shut-Off Valve . . . 1 92-343-1-021 9 1/2" Y-Strainer . . . . . . . . . . . . . . . . . . . . . . . 1 52-353-1-005
2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002 6 Item No. Not Used 10 3/4" Swing Check Valve . . . . . . . . . . . . . . . . 1 46-049-1-005
3 Model MC-1 Manual Control Station . . . . . . 1 52-289-2-001 7 1/2" Ball Valve . . . . . . . . . . . . . . . . . . . . . . . 2 46-050-1-004 11 3/4" Angle Valve . . . . . . . . . . . . . . . . . . . . . . 1 46-048-1-005
4 Model AD-1 Automatic Drain Valve . . . . . . . 1 52-793-2-004 8 1/2" Spring Loaded Check Valve . . . . . . . . . 1 92-322-1-002 12 1-1/4" Angle Valve . . . . . . . . . . . . . . . . . . . . 1 46-048-1-007
13 Drip Funnel Connector . . . . . . . . . . . . . . . . . 1 92-211-1-005
35 35 25 14 Drip Funnel Bracket . . . . . . . . . . . . . . . . . . . 1 92-211-1-003
15 Drip Funnel . . . . . . . . . . . . . . . . . . . . . . . . . . 1 92-343-1-007
35 16 3/32" Vent Fitting . . . . . . . . . . . . . . . . . . . . . 1 92-032-1-002
17 1/4" x 18" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH
25 18 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 1 CH
22 9 19 1/2" x 12" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH
34 20 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
35 8 21 3/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
42 22 1/2" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 5 CH
1 5 23 3/4" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH
7 25 35
1 24 1/4" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH
20 37 25 1/2" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 8 CH
3" (DN80)
2 25 27
26 3/4" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH
GROOVE x GROOVE 27 1/2" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 CH
35 22
DV-5 DELUGE VALVE 42
28 1/2" x 1/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 3 CH
33 SHOWN 22 29 3/4" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
33 35 27
30 3/4" x 1/2" x 3/4" Tee . . . . . . . . . . . . . . . . . . 2 CH
35 31 3/4" x 3/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 1 CH
35 32 1-1/4" x 3/4" x 1-1/4" Tee. . . . . . . . . . . . . . . 1 CH
24 22 28 33 1/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH
35 34 1/2" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH
39 35 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 13 CH
28 36 1/2" x 2-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 2 CH
3
22 37 1/2" x 3-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
38 38 1/2" x 4" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
39 1/2" x 4-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
40 40 1/2" x 5" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
7 41 41 1/2" x 5-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
34 42 1/2" x 7" Nipple. . . . . . . . . . . . . . . . . . . . . . . 2 CH
LOCATION 43 3/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 3 CH
35 25 44 3/4" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 5 CH
FOR OPTIONAL 25 45 3/4" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
ELECTRICALLY 35
46 3/4" x 4-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
SUPERVISED 18 47 1-1/4" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . 1 CH
48 1-1/4" x 4" Nipple. . . . . . . . . . . . . . . . . . . . . 1 CH
N.O. ALARM 30 19
CONTROL 25 COMPONENTS ORDERED SEPARATELY:
23 44
VALVE 45 A1 Waterflow Pressure Alarm Switch,
10 Model PS10-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25710

44 44 4
21 28 27
NOTES:
30 29 36
44 15 1. Wet Pilot Actuation Trim is comprised of
31 Items 1-48. Item A1 ordered separately.
36 16
(GREEN 2. All Fittings and Nipples are galvanized
A1 48 TINT) 17 13 (Standard Order).
(ORDERED
44 3. CH: Common Hardware.
SEPARATELY)
43 4. See Figure 2 of TFP1305 for Valve Port
23 identification.
12
47 43 46 14 5. Route all Tubing to Drip Funnel, Item 15.
32 26 11 6. Horizontal Arrangement uses only 7 out of
43 8 of Item 25, and 12 out of 13 of Item 35.
Discard unused material.
FIGURE 5 (2 OF 3)
3 INCH (DN80) DV-5 DELUGE VALVE
EXPLODED VIEW OF HORIZONTAL WET PILOT ACTUATION TRIM
TFP1310
Page 12 of 16

NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N
1 300 psi/ 2000 kPa Water Pressure Gauge . . 2 92-343-1-005 12 2" Angle Valve . . . . . . . . . . . . . . . . . . . . . . . 1 46-048-1-009 23 1" Union . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH
2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002 13 Drip Funnel Connector . . . . . . . . . . . . . . . . . 1 92-211-1-005 24 1/4" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH
3 Model MC-1 Manual Control Station . . . . . . 1 52-289-2-001 14 Drip Funnel Bracket . . . . . . . . . . . . . . . . . . . 1 92-211-1-003 25 1/2" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 8 CH
4 Model AD-1 Automatic Drain Valve . . . . . . . 1 52-793-2-004 15 Drip Funnel . . . . . . . . . . . . . . . . . . . . . . . . . . 1 92-343-1-007 26 1" 90° Elbow. . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
5 Model ASV-1 Automatic Shut-Off Valve . . . 1 92-343-1-021 16 3/32" Vent Fitting . . . . . . . . . . . . . . . . . . . . . 1 92-032-1-002 27 1/2" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 CH
6 Item No. Not Used 17 Select Tubing per Table . . . . . . . . . . . . . . . . 1 CH 28 1/2" x 1/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 3 CH
7 1/2" Ball Valve . . . . . . . . . . . . . . . . . . . . . . . 2 46-050-1-004 18 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 1 CH 29 3/4" x 1/2" x 3/4" Tee . . . . . . . . . . . . . . . . . . 2 CH
8 1/2" Spring Loaded Check Valve . . . . . . . . . 1 92-322-1-002 19 1/2" x 24" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH 30 1" x 1" x 1/2" Tee . . . . . . . . . . . . . . . . . . . . . 1 CH
9 1/2" Y-Strainer . . . . . . . . . . . . . . . . . . . . . . . 1 52-353-1-005 20 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH 31 1" x 3/4" x 1" Tee . . . . . . . . . . . . . . . . . . . . . 1 CH
10 3/4" Swing Check Valve . . . . . . . . . . . . . . . . 1 46-049-1-005 21 3/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH 32 2" x 1" x 2" Tee . . . . . . . . . . . . . . . . . . . . . . . 1 CH
11 1" Angle Valve . . . . . . . . . . . . . . . . . . . . . . . 1 46-048-1-006 22 1/2" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 5 CH 33 1/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH
34 1/2" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH
35 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 10 CH
35 35 25 36 1/2" x 2-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 3 CH
37 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
35 38 1/2" x 5" Nipple. . . . . . . . . . . . . . . . . . . . . . . 2 CH
25 39 1/2" x 6" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
40 1/2" x 7" Nipple. . . . . . . . . . . . . . . . . . . . . . . 2 CH
22 9 41 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
34 42 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
35 8 43 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
43 44 3/4" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
5
7 25 35 45 3/4" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
1 1 46 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
38 47 1" x Close Nipple . . . . . . . . . . . . . . . . . . . . . 5 CH
20 4" (DN100) 27 48 1" x 3" Nipple . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
25 35
2 22
49 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
GROOVE x GROOVE 40 50 2" x 3" Nipple . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
DV-5 DELUGE VALVE 22 51 2" x 5" Nipple . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
33 SHOWN 35 27 COMPONENTS ORDERED SEPARATELY:
33
35 35 28 A1 Waterflow Pressure Alarm Switch,
24 22 42 Model PS10-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25710

38 3
28 22 Select Appropriate Tube Size
per DV-5 Deluge Valve Size
39 Tube
40 No. 4" 6" 8"
7 (DN100) (DN150) (DN200)
17 1/4" x 24" 1/4" x 24" 1/4" x 32"
34
LOCATION 36 Select Appropriate Nipple Sizes
FOR OPTIONAL 41 25 Nipple per DV-5 Deluge Valve Size
25
ELECTRICALLY 35 18 No. 4" 6" 8"
SUPERVISED (DN100) (DN150) (DN200)
29 19 37 1/2" x 3" 1/2" x 3" 1/2" x 5"
N.O. ALARM 41 1/2" x 2-1/2" 1/2" x 5-1/2" 1/2" x 8-1/2"
CONTROL 25
46 23 48 42 1/2" x 2" 1/2" x 3" 1/2" x 3-1/2"
VALVE 45 43 1/2" x 6-1/2" 1/2" x 7-1/2" 1/2" x 9"
10 46 3/4" x 2-1/2" 3/4" x 3-1/2" 3/4" x 4-1/2"
44 47 4 49 1" x 6" 1" x 9" 1" x 12"
21 28 27
29 31 37 NOTES:
51 30 15 1. Wet Pilot Actuation Trim is comprised of
36 16 Items 1-51. Item A1 ordered separately.
(GREEN
50 2. All Fittings and Nipples are galvanized
A1 TINT) 17 13
(ORDERED (Standard Order).
SEPARATELY) 47 3. CH: Common Hardware.
12
47 4. See Figure 2 of TFP1305 for Valve Port
23
identification.
47 49 11 14 5. Route all Tubing to Drip Funnel, Item 15.
32 26
6. Horizontal Arrangement uses only 7 out of
47 8 of Item 25, and 2 out of 3 of Item 36.
Discard unused material.
FIGURE 5 (3 OF 3)
4, 6, AND 8 INCH (DN100, DN150, AND DN200) DV-5 DELUGE VALVES
EXPLODED VIEW OF HORIZONTAL WET PILOT ACTUATION TRIM
TFP1310
Page 13 of 16

Supply Maximum Pilot Height, (2)


Pressure, (1) Ft.
psi (m)
(bar)
1-1/2” 2” 3” 4” 6” 8”
(DN40) (DN50) (DN80) (DN100) (DN150) (DN200)
20 7 3 7 17 18 9
(1,4) (1,4) (0,9) (1,4) (5,2) (5,5) (2,7)
40 24 19 30 39 38 38
(2,8) (7,3) (5,8) (9,1) (11,9) (11,6) (11,6)
60 49 38 52 54 56 44
(4,1) (14,0) (11,6) (15,8) (16,5) (17,1) (13,4)
80 58 54 70 60 70 58
(5,5) (17,8) (16,5) (21,3) (18,3) (21,3) (17,8)
100 78 78 93 78 99 65
(6,9) (23,8) (23,8) (28,3) (23,8) (30,2) (19,8)
120 87 87 117 115 130 96
(8,3) (26,5) (26,5) (35,7) (35,1) (39,6) (29,3)
140 105 107 139 142 154 141
(9,7) (32,0) (32,6) (42,4) (43,3) (46,9) (43,0)
160 127 123 161 176 161 170
(11,0) (38,7) (37,5) (49,1) (53,6) (49,1) (51,8)
175 134 138 172 171 194 194
(12,1) (40,8) (42,1) (52,4) (52,1) (59,1) (59,1)
200 160 160 206 223 216 206
(13,8) (48,8) (48,8) (62,8) (68,0) (65,8) (62,8)
225 185 166 237 233 246 250
(15,5) (56,4) (50,6) (72,2) (71,0) (75,0) (76,2)
250 201 199 251 247 275 257
(17,2) (61,3) (60,7) (76,5) (75,3) (83,8) (78,3)
NOTES:
(1) If supply pressure is variable, assume minimum expected value.
(2) Maximum pilot height for up to 500 feet (150 meters) of equivalent length of pilot line (pipe plus fittings).
(3) Interpolation between data points is permitted.

TABLE A
1-1/2 THRU 8 INCH (DN40 THRU DN200) DV-5 DELUGE VALVE
WET PILOT DESIGN CRITERIA FOR
UP TO 500 FEET OF EQUIVALENT LENGTH OF PILOT LINE (PIPE PLUS FITTINGS)

Installation The DV-5 Deluge Valve is to be in-


stalled in accordance with the follow-
Step 6. Suitable provision must be
made for disposal of drain water.
General Instructions ing criteria: Drainage water must be directed such
Proper operation of the DV-5 Deluge that it will not cause accidental dam-
Step 1. All nipples, fittings, and de-
Valves depends upon their trim being age to property or danger to persons.
vices must be clean and free of scale
installed in accordance with the in- and burrs before installation. Use pipe Step 7. Connect the Diaphragm
structions given in this Technical Data thread sealant sparingly on male pipe Chamber Supply Control Valve to the
Sheet. Failure to follow the appropri- threads only. inlet side of the system’s main control
ate trim diagram may prevent the DV-5 valve in order to facilitate setting of the
Step 2. The DV-5 Valve must be
Valve from functioning properly, as DV-5 Valve (Ref. Figure 4).
trimmed in accordance with Figure
well as void listings, approvals, and
3A/3B or 5. Step 8. An Inspector’s Test Connec-
the manufacturer’s warranties.
tion, as described in the Technical
Step 3. Care must be taken to ensure
The DV-5 Valve must be installed in a Data section, must be provided for
that check valves, strainers, globe
readily visible and accessible location. Wet Pilot Actuation systems.
valves, etc. are installed with the flow
The DV-5 Valve, associated trim, and arrows in the proper direction. Step 9. Unused pressure alarm switch
wet pilot lines must be maintained at connections must be plugged.
Step 4. Drain tubing to the drip funnel
a minimum temperature of 40°F (4°C).
must be installed with smooth bends Step 10. Conduit and electrical con-
Heat tracing of the DV-5 Valve or that will not restrict flow. nections are to be made in accor-
its associated trim is not permitted. dance with the requirements of the
Step 5. The main drain and drip funnel
Heat tracing can result in the forma- authority having jurisdiction and/or the
drain may be interconnected provid-
tion of hardened mineral deposits National Electric Code.
ed a check valve is located at least 12
that are capable of preventing proper
inches (300 mm) below the drip funnel.
operation.
TFP1310
Page 14 of 16

Step 11. Before a system hydrostatic were possibly exposed to a tempera- indicated on the Diaphragm Cham-
test is performed in accordance with ture greater than their maximum rated ber Pressure Gauge to drop below the
NFPA 13 system acceptance test re- ambient must be replaced. supply pressure shown on the Water
quirements, the DV-5 Diaphragm Supply Pressure Gauge, since this ac-
Step 7. Open the Diaphragm Cham-
Chamber is to be depressurized, the tion may result in tripping of the DV-5
ber Supply Control Valve and allow
Automatic Drain Valve (Item 4, Fig. 3A Valve.
time for full pressure to build up in the
and 5) is to be temporarily replaced Diaphragm Chamber. After setting a fire protection system,
with a 1/2 inch NPT plug, the 3/32 notify the proper authorities and ad-
inch Vent Fitting (16 - Fig. 3A and 5) Step 8. Operate (open) the Manu-
vise those responsible for monitor-
is to be temporarily replaced with a al Control Station to vent trapped air
ing proprietary and/or central station
1/4 inch NPT plug, and the Diaphragm from the Diaphragm Chamber. If nec-
alarms.
Cover Bolts must be uniformly and se- essary, first open the hinged cover,
curely tightened using a cross-draw and then fully pull down on the oper-
sequence. After tightening, double-
check to make certain that all of the
ating lever. Slowly close the operat-
ing lever, by pushing it up, after aer-
Care and
Diaphragm Cover Bolts are securely
tightened.
ated water ceases to discharge from
the Manual Control Station drain tub-
Maintenance
ing. Close the hinged cover and in- The following procedures and in-
spections must be performed as in-
Valve Setting sert a new break rod in the small hole
through the top of the enclosing box. dicated, in addition to any specific
requirements of the NFPA, and any
Procedure Crack open the Inspector’s Test Con-
nection and any other vent valves on
impairment must be immediately
corrected.
Steps 1 through 11 are to be per- the wet pilot line to relieve trapped air.
formed when initially setting the DV-5 After the discharge of air has stopped, Before closing a fire protection system
Deluge Valve; after an operational test close the vent valves and the Inspec- main control valve for maintenance
of the fire protection system; or, after tor’s Test Connection. work on the fire protection system that
system operation due to a fire. it controls, permission to shut down
Step 9. Inspect the drain connection the affected fire protection systems
NOTE: When the system is using ei- from the Manual Control Station. Any must first be obtained from the proper
ther a seawater or brackish water sup- leaks must be corrected before pro- authorities and all personnel who may
ply, it is recommended that the system ceeding to the next step. be affected by this action must be no-
be thoroughly flushed with clean fresh
Step 10. Verify the ability for the tified. Reset the DV-5 Deluge Valve
water. Following this recommenda-
DV-5 Diaphragm to hold pressure as in accordance with the Valve Setting
tion will increase the service life of the
follows: Procedure section.
DV-5 Valve and Trim.
• With the diaphragm chamber pres- The owner is responsible for the in-
Step 1. Close the Main Control Valve.
surized per Step 8, temporari- spection, testing, and maintenance of
Step 2. Close the Diaphragm Cham- ly close the Diaphragm Chamber their fire protection system and devic-
ber Supply Control Valve. Supply Control Valve, and monitor es in compliance with this document,
the Diaphragm Chamber Pressure as well as with the applicable stan-
Step 3. Open the Main Drain Valve,
Gauge for a drop in pressure. dards of the National Fire Protection
System Drain Valve, and all auxiliary
Association (e.g., NFPA 25), in addition
drains in the system. Close the System • If a drop in pressure is noted, the to the standards of any authority hav-
Drain Valve and auxiliary drain valves DV-5 Diaphragm is to be replaced ing jurisdiction. Contact the installing
after water ceases to discharge. Leave and/or any leaks must be corrected contractor or product manufacturer
the Main Drain Valve open. before proceeding to the next step. with any questions.
Step 4. Depress the plunger of the • If the Diaphragm Chamber Pressure It is recommended that automatic
Automatic Drain Valve to verify that Gauge does not indicate a drop in sprinkler systems be inspected, test-
it is open and that the DV-5 Valve is pressure, re-open the Diaphragm ed, and maintained by a qualified In-
completely drained. Chamber Supply Control Valve and spection Service in accordance with
Step 5. Clean the Strainer in the Dia- proceed to the next step. local requirements and/or national
phragm Chamber Supply connection Step 11. Slowly open the Main Con- codes.
by removing the clean-out plug and trol Valve. Close the Main Drain Valve NOTES: Some of the procedures out-
strainer basket. The Strainer may be as soon as water discharges from the lined in this section will result in oper-
flushed out by momentarily opening drain connection. Observe the Auto- ation of the associated alarms. Conse-
the Diaphragm Chamber Supply Con- matic Drain Valve for leaks. If there are quently, notification must first be given
trol Valve. leaks, determine/correct the cause of to the owner and the fire department,
Step 6. Reset the actuation system. the leakage problem. If there are no central station, or other signal station
leaks, the DV-5 Valve is ready to be to which the alarms are connected.
Manual Actuation — Push the operat- placed in service and the Main Control
ing lever up; however, do not close the Valve must then be fully opened. When the system is using either a sea-
hinged cover at this time. water or brackish water supply, in-
NOTE: When the Main Control Valve ternal and external inspection of the
Wet Pilot Actuation — Replace oper- is opened, the pressure on the Dia-
ated pilot sprinklers and/or reset the DV-5 Valve and Trim is essential. Parts
phragm Chamber may increase. This showing any signs of corrosion must
manual control stations. increase in pressure is normal, and if be replaced to ensure the integrity of
NOTE: In order to prevent the possi- the pressure is greater than 250 psi the system.
bility of a subsequent operation of an (17,2 bar), the pressure is to be re-
over-heated solder type pilot sprinkler, lieved by partially and temporarily
any solder type pilot sprinklers that opening the Manual Control Station;
however, do not allow the pressure as
TFP1310
Page 15 of 16

Annual Operation Test Procedure


Proper operation of the DV-5 Valve Ordering DV-5 Pre-trimmed Assembly Wet
Pilot Actuation Trim
(i.e., opening of the DV-5 Valve as dur-
ing a fire condition) must be verified at Procedure without Butterfly Valve
Specify: (specify size), (specify) End
least once a year as follows: NOTE: Part Numbers for factory pre- Connection, Pre-trimmed DV-5 As-
Step 1. If water must be prevented trimmed DV-5 Valves are provided in sembly without Butterfly Valve, P/N
from flowing beyond the riser, perform the Price Book. (specify):
the following steps: DV-5 Semi-Preassembled Vertical
1-1/2 Inch T x T . . . . . . . . . . . . P/N 52-911-3-1AP
2 Inch T x T . . . . . . . . . . . . . . . P/N 52-921-3-1AP
• Close the Main Control Valve. Wet Pilot Actuation Trim 3 Inch F x F . . . . . . . . . . . . . . . P/N 52-931-1-1AP
• Open the Main Drain Valve. Specify: (specify size and finish — gal- 3 Inch F x G . . . . . . . . . . . . . . . P/N 52-931-2-1AP
vanized is standard) Semi-Preassem- 4 Inch F x F . . . . . . . . . . . . . . . P/N 52-941-1-1AP
• Open the Main Control Valve one bled Vertical Wet Pilot Actuation Trim 4 Inch F x G . . . . . . . . . . . . . . . P/N 52-941-2-1AP
6 Inch F x F . . . . . . . . . . . . . . . P/N 52-961-1-1AP
turn beyond the position at which for DV-5 Deluge Valves, P/N (specify): 6 Inch F x G . . . . . . . . . . . . . . . P/N 52-961-2-1AP
water just begins to flow from the 1-1/2 & 2 Inch Galvanized . . . . P/N 52-477-2-307 8 Inch F x F . . . . . . . . . . . . . . . P/N 52-981-1-1AP
Main Drain Valve. 1-1/2 & 2 Inch Black . . . . . . . . P/N 52-477-1-307 8 Inch F x G . . . . . . . . . . . . . . . P/N 52-981-2-1AP
1-1/2 & 2 Inch Brass . . . . . . . . P/N 52-477-3-307
• Close the Main Drain Valve.
Accessories
Step 2. Open the Inspector’s Test 3 Inch Galvanized . . . . . . . . . . P/N 52-477-2-104 Refer to the Technical Data Sheets for
Connection. 3 Inch Black . . . . . . . . . . . . . . P/N 52-477-1-104 the following, as applicable, for details
NOTE: Be prepared to quickly per- 3 Inch Brass . . . . . . . . . . . . . . P/N 52-477-3-104 and additional accessories:
form Steps 3, 4, and 5 if water must 600 psi Water
be prevented from flowing beyond the 4, 6 & 8 Inch Galvanized . . . . . P/N 52-477-2-301 Pressure Gauge . . . . . . . . . . . P/N 92-343-1-004
riser. 4, 6 & 8 Inch Black . . . . . . . . . P/N 52-477-1-301 Model PS10-2
4, 6 & 8 Inch Brass . . . . . . . . . P/N 52-477-3-301 Potter Electric
Step 3. Verify that the DV-5 Valve has Waterflow
tripped, as indicated by the flow of DV-5 Unassembled Wet Pilot Pressure
water into the system. Alarm Switch . . . . . . . . . . . . . . . . . . . . P/N 25710
Actuation Trim for Vertical or Model WMA-1 Water
Step 4. Close the system’s Main Con- Horizontal Installation Motor Alarm . . . . . . . . . . . . . P/N 52-630-1-001P
trol Valve. Specify: (specify size and finish — gal- Model MC-1
vanized is standard) Unassembled Manual Control
Step 5. Close the Diaphragm Cham- Stations with
Wet Pilot Actuation Trim for vertical or
ber Supply Control Valve. Galvanized
horizontal installation of DV-5 Deluge Connections for
Step 6. Reset the DV-5 Deluge Valve Valves, P/N (specify): Remote Wet Pilot
in accordance with the Valve Setting 1-1/2 & 2 Inch Galvanized . . . . P/N 52-477-2-207
Actuation . . . . . . . . . . . . . . . . . P/N 52-289-2-001
Procedure. 1-1/2 & 2 Inch Black . . . . . . . . P/N 52-477-1-207
1-1/2 & 2 Inch Brass . . . . . . . . P/N 52-477-3-207 Replacement Trim Parts
Quarterly Waterflow Alarm Test Specify: (description) for use with
Procedure 3 Inch Galvanized . . . . . . . . . . P/N 52-477-2-204 DV-5 Deluge Valve, P/N (see Figure 3A
Testing of the system waterflow 3 Inch Black . . . . . . . . . . . . . . P/N 52-477-1-204
3 Inch Brass . . . . . . . . . . . . . . P/N 52-477-3-204
or 5)
alarms must be performed quarter-
ly. To test the waterflow alarm, open 4, 6 & 8 Inch Galvanized . . . . . P/N 52-477-2-201
the Alarm Test Valve, which will allow 4, 6 & 8 Inch Black . . . . . . . . . P/N 52-477-1-201
a flow of water to the Pressure Alarm 4, 6 & 8 Inch Brass . . . . . . . . . P/N 52-477-3-201
Switch and/or Water Motor Alarm.
Upon satisfactory completion of the DV-5 Pre-trimmed Assembly Wet
test, close the Alarm Test Valve. Pilot Actuation Trim
with Butterfly Valve
Limited Specify: (size), G x G End Connection,
Pre-trimmed DV-5 Assembly with But-
Warranty terfly Valve, P/N (specify):
1-1/2 Inch G x G . . . . . . . . . . . P/N 52-911-0-1AP
For warranty terms and conditions, 2 Inch G x G . . . . . . . . . . . . . . P/N 52-921-0-1AP
visit www.tyco-fire.com. 3 Inch G X G . . . . . . . . . . . . . . P/N 52-931-0-1AP
4 Inch G x G . . . . . . . . . . . . . . P/N 52-941-0-1AP
6 Inch G x G . . . . . . . . . . . . . . P/N 52-961-0-1AP
8 Inch G x G . . . . . . . . . . . . . . P/N 52-981-0-1AP
TFP1310
Page 16 of 16

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


Copyright © 2014 Tyco Fire Products, LP. All rights reserved.
TEFLON is trademark of the DuPont Corporation.

You might also like