AC Input Modules

FEATURES
• Transient Protection: Meets the
requirements of IEEE 472, “Surge
Withstanding Capability Test”
• UL, CSA, CE, TÜV Certified (TÜV
not available on OpenLine)
• Optical Isolation
• OpenLine® and G5 Modules have
Built-in Status LED
• Lifetime Warranty

70L-IAC 70G-IAC 70-IAC 70M-IAC

CIRCUITRY
Standard, Mini, G5 OpenLine®
I/O MODULE TYPICAL WIRING FOR MODULE 70
+ Rx PIN #
1
6 Vcc
VDC A
2 INPUT
DEVICE 1 1 FILTER
7 CH. A STATUS
OPTICAL HYSTERESIS
ISOLATION 5 GND
2 2
+VCC INPUT
3 VOLTAGE
HYST. CIRC. INPUT
DEVICE 3 3 FILTER
B
8 CH. B STATUS
CURRENT OPTICAL HYSTERESIS
OUTPUT REGULATING * ISOLATION
4
4 4
GROUND
5 TERMINAL BASE 9 MODULE ID
BLOCK # OR 0Ω
RACK MODULE
Status LED in G5 modules only. * Separate supplies may also be used.

SPECIFICATIONS: By Package Style


Package Style Std (70-) Mini (70M-) G5 (70G-) OL (70L-)
I/O Modules

Specifications Units
Output Current Range mA 1-50 1-50 1-50 1-50
Minimum Output Breakdown Voltage Vdc 50 50 50 50
Maximum Turn-On Time mS 20 20 20 20
Maximum Turn-Off Time mS 20 20 20 20
Isolation Voltage 1 Vrms 4000 4000 4000 2500
Vibration2 MIL-STD-202 MIL-STD-202 MIL-STD-202 IEC68-2-6
Mechanical Shock3 MIL-STD-202 MIL-STD-202 MIL-STD-202 IEC68-2-27
Storage Temp. Range °C -40 to +125 -40 to +125 -40 to +125 -40 to +100
Operating Temp. Range °C -40 to +100 -40 to +100 -40 to +100 -40 to +85
Warranty Lifetime Lifetime Lifetime Lifetime
1
Field to logic and channel-to-channel if Grayhill racks are used.
2
MIL-STD-202, Method 204, 20 G, 10-2000 Hz or IEC68-2-6, 0.15 mm/sec2, 10-150 Hz.
3
MIL-STD-202, Method 213, Condition F, 1500 G or IEC68-2-27, 11 mS, 15g.

I/O
14 Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois 60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com
Specifications are subject to change. Please refer to the current datasheet on www.grayhill.com for the most current published specifications for this product.

 02761&7.'5

SPECIFICATIONS: By Part Number


Standard and Miniature Modules
Type/Function Grayhill Part Number
Miniature 70M-IAC5 70M-IAC5A 70M-IAC15 70M-IAC15A 70M-IAC24 70M-IAC24A
Standard 70-IAC5 70-IAC5A 70-IAC15A 70-IAC24 70-IAC24A

Specifications Units
Nominal Input Voltage Vac 120 240 120 240 120 240
Input Voltage Range1 Vac/Vdc 90-140 180-280 90-140 180-280 90-140 180-280
Input Current @ Maximum Input Voltage mA, rms 8 6 8 6 8 6
Nominal Input Resistance (Rx) W 22K 60K 22K 60K 22K 60K
Maximum Pick-Up Voltage (Output Low) Vac 90 180 90 180 90 180
Minimum Drop-Out Voltage (Output High) Vac 25 50 25 50 25 50
Nominal Logic Voltage (Vcc) Vdc 5 5 15 15 24 24
Logic Voltage Range Vdc 3-6 3-6 8-18 8-18 15-30 15-30
Max. Logic Supply Current @ Nominal Vcc mA 10 10 10 10 10 10

G5 Modules
Type/Function Grayhill Part Number
G5, Status LED 70G-IAC5 70G-IAC5A 70G-IAC15 70G-IAC15A 70G-IAC24 70G-IAC24A

Specifications Units
Nominal Input Voltage Vac 120 240 120 240 120 240
Input Voltage Range1 Vac/Vdc 90-140 180-280 90-140 180-280 90-140 180-280
Input Current @ Maximum Input Voltage mA, rms 8 6 8 6 8 6
Nominal Input Resistance (Rx) W 22K 60K 22K 60K 22K 60K
Maximum Pick-Up Voltage (Output Low) Vac 90 180 90 180 90 180
Minimum Drop-Out Voltage (Output High) Vac 25 50 25 50 25 50
Nominal Logic Voltage (Vcc) Vdc 5 5 15 15 24 24
Logic Voltage Range Vdc 4.5-6 4.5-6 10-18 10-18 17-30 17-30
Max. Logic Supply Current @ Nominal Vcc mA 10 10 10 10 10 10

OpenLine® Modules
Available from your local Grayhill Distributor. For
Type/Function Grayhill Part Number prices and discounts, contact a local Sales Office,
Dual, Status LED 70L-IAC 70L-IACA an authorized local Distributor or Grayhill.

Specifications Units
Nominal Input Voltage Vac 120 240
Input Voltage Range1 Vac/Vdc 0-140 0-280
Input Current @ Max. Input Voltage mA, rms 8 6

I/O Modules
Nominal Input Resistance (Rx) W 22K 64K
Max. Pick-Up Voltage (Output Low) Vac 90 180
Min. Drop-Out Voltage (Output High) Vac 25 50
Nominal Logic Voltage (Vcc) Vdc 5 5
Logic Voltage Range Vdc 4.5-28 4.5-28
Max. Logic Supply Current @ Nominal Vcc mA 6/CH 6/CH
Module ID Resistance to Logic Ground W 0 0
1
For input voltages in the range of 15-32 Vac, or 35-60 Vac, see DC input Modules with the NP
or G suffix.

I/O
4#;*+..X 0%T ˜ IJE +..)418' 8'07' ˜ # 4#0)'X ..+01+5  JNIFIgIMMK ˜  ˜ *10'U KNLgGIHgENHN ˜
#:U KNLgGIHgFLFN ˜ 999T)4#;*+..T%1/ 15
Specifications are subject to change. Please refer to the current datasheet on www.grayhill.com for the most current published specifications for this product.

Digital I/O Module Engineering Information

I/O MODULES
Our line of pluggable input and output modules transients, and have built-in RC snubber Standard 22.2 No. 14-95M and are documented
provide a low cost, versatile method for networks for increased capability with inductive in CSA file LR38763. Additionally, OpenLine®
interconnecting real world analog and digital loads. modules were tested and passed CSA 22.2
signals to data acquisition, monitoring, or control No. 213-M1987 Class I, Div. 2 Groups A, B, C
systems. All modules provide an optically DC output modules can operate DC loads over and D. Parts bearing the CE logo indicate
isolated barrier between sensitive a wide voltage range and have built-in voltage conformance with EN50082-2 and EN50081-2
microprocessor or digital logic circuits and spike protection. (89/336/EEC EMC directive) as well as EN60950
field power devices. (61010-1) for the low voltage directive. Contact
DIGITAL INPUT MODULES Grayhill for copies of our Declaration of
In the G5 and OpenLine® packages, analog Digital input modules are used to monitor the Conformity or visit out website. Parts bearing
and digital I/O modules are available with the status of a load or a sensor (such as a limit the TÜV logo indicate that they were the agency
same pin-out. This gives the flexibility of mixing switch, pressure switch, or temperature which performed the EN60950 evaluation.
and matching module types on the same switch). The output of these modules is a logic
mounting rack or base; making them perfect level signal which corresponds to the status of CONSTRUCTION AND LIFETIME
in applications which require interface to a the device being monitored. A high level output
variety of different sensors and loads. WARRANTY
signal indicates the load is off (the switch is All of our I/O modules are hard potted with
open). A low level output signal indicates the thermally conductive epoxy to withstand harsh
The case color of the single point modules load is on (the switch is closed). Input modules
identify their function. The industry standard industrial environments. The modules provide
are designed to give fast, clean switching by optical isolation, immunity to mechanical shock
for single point I/O module case colors is: providing filtering and hysteresis.
Digital AC Output Module = Black Case and vibration, and operate over a wide
Digital DC Output Module = Red Case temperature range. The module cases are a
Input and output modules are compatible in solvent resistant thermoplastic which meets
Digital AC Input Module = Yellow Case that the output of one can drive the input of the
Digital DC Input Module = White Case UL94-V-0 rating. The terminal pins are a tin-
other. plated copper wire. Component selection and
surface mount construction allow low operating
DIGITAL OUTPUT MODULES junction temperatures for long life. Superior
Digital output modules are used to switch AC UL, CSA AND CE APPROVALS design, rigorous testing, and field data give us
and DC loads such as solenoids, motors, or As one of the world's leading manufacturers of the confidence to back our I/O modules with
lamps from logic signal levels. Their inputs are I/O modules, we strive to assure that our the industry's first lifetime warranty.
directly compatible with TTL or CMOS interface products comply with all of the applicable
circuitry. international standards. In doing so, we believe
your products will also be readily accepted and I/O MODULE WIRING
AC output modules have zero voltage turn-on easily certified. All modules shown in this Analog and digital modules can be placed at
of the load to greatly reduce generated EMI section have been tested to UL Standard 508 any I/O location, however, to minimize the
and RFI. They are highly immune to electrical and are documented in UL file number E58632. possibility of crosstalk and noise pickup it is a
Similarly, they have been tested to CSA good practice to group similar module types
together. 14 or 16 gauge wire is typically used
to wire the field devices to the I/O rack terminal
block.

PART NUMBER EXPLANATION: Digital I/O Modules

Module Type
70 = Digital Module, Standard Package
70G = Digital Module, G5 Package
70L = Digital Module, OpenLine® Package
70M = Digital Module, Mini Package
I/O Modules

Function
OAC = Digital Output AC
ODC = Digital Output DC
IAC = Digital Input AC
70M-ODC5A IDC = Digital Input DC
Suffix
AC Inputs: Blank = 120 Vac A = 220 Vac
DC Inputs: Blank = 3-32 Vdc B = Fast Switching NP = 15-32 Vac/10-32 Vdc
G = 35-60 Vac/Vdc D = 2.5–28 Vdc K = 2.5-16 Vdc
L = Inductive loads S = Dry Contacts
AC Outputs: Blank = 120 Vac A = 220 Vac A-11 = Non-Zero Cross
MA = 120 Vac, Manual Override A-5 = Normally Closed
AMA = 240 Vac, Manual Override
DC Outputs: Blank = 3-60 Vdc Fast A = 4-200 Vdc R = Dry Contact
MA = 3-60 Vdc, Manual Override B = 3-60 Vdc, Low Leakage
Logic Supply Voltage or Range
Digital Modules: Blank = 4.5-28 Vdc (OpenLine®)
5 Vdc, 15 Vdc, 24 Vdc = Logic Supply Voltage (Standard, Mini, G5)
Analog Modules: 4.75-5.25 Vdc

I/O
2 Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois 60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com
Specifications are subject to change. Please refer to the current datasheet on www.grayhill.com for the most current published specifications for this product.

Digital I/O Modules Engineering Information

DIMENSIONS: OpenLine® Digital Modules


Dimensions shown in inches (and millimeters).
Tolerances are ± .010 (0,25) unless indicated otherwise.

Module Type Output Input


I/O Module Pin # Function Function
1 Output A+ Input A+
2 Output A- Input A-
3 Output B+ Input B+ FUSE HOLDERS
4 Output B- Input B- (OUTPUTS ONLY) GREEN STATUS
5 Logic Gnd Logic Gnd LEDS
6 Vcc Vcc
7 Ch. A Input Ch. A Status
8 Ch. B Input Ch. B Status DATE
9 Module ID Module ID CODE

.025 2.49
(0,635) (63,25)
SQ. 2.23
.51 .34 (56,64)
2.09 (53,09) (8,64)
(12,95)
.19
(4,83) .22 .10 .03
(5,59) (2,54) (0,76) .38
(9,65)
PIN 1
PIN 2
PIN 3
PIN 4

PIN 5
PIN 6
PIN 7
PIN 8
PIN 9

.14 .24 (6,10)


(3,56)
2.70 (68,58)

Note: For PC board layout information, request Bulletin #745

DIMENSIONS: G5 Digital Modules


Dimensions shown in inches (and millimeters).
Tolerances are ± .010 (0,25) unless indicated otherwise.

Input Modules Ouput Modules

1.90 (48,3) 1.90 (48,3)

.46 .46
(11,7) (11,7)

GREEN STATUS LED

I/O Modules
GREEN FUSE HOLDER
STATUS LED

4-40 X 2-1/2" PHILLIPS HOLD-


DOWN SCREW INCLUDED
WITH EACH MODULE
MAXIMUM TORQUE = 5 FT-LB
2.55
(64,8)

2.20
O .040/.042 2.20
(55,9) O .040/.042
(1,02/1,07) (55,9)
(1,02/1,07)

5 4 3 2 1 .235 (5,97) 4 3 2 1 .235 (5,97)


.20 (5,1)
.20 (5,1)
.40 (10,2)
.40 (10,2)
.90 (22,9) .20 (5,1) .20 (5,1)
.90 (22,9)
1.15 (29,2) .15 (3,8) .15 (3,8)
1.15 (29,2)
1.35 (34,3)
1.35 (34,3)
1.55 (39,4)

I/O
Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois 60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com 3
Specifications are subject to change. Please refer to the current datasheet on www.grayhill.com for the most current published specifications for this product.

Digital I/O Modules Engineering Information

DIMENSIONS: Standard and Miniature Digital Modules


Dimensions shown in inches (and millimeters).
Tolerances are ± .010 (0,25) unless indicated otherwise.

Standard Module Miniature Module


1.00 (25,4)

.60 (15,2)

4–40 X 1-1/2" PHILLIPS HOLD- .40 (10,2)


DOWN SCREW INCLUDED
WITH EACH MODULE
MAXIMUM TORQUE = 5 FT-LB
1.70 (43,2)
1.70 (43,2)

1.25 Ø .040/.042
(31,8) 1.00
(1,02/1,07) Ø .040/.042
.235 ± .02 (25,4)
(1,02/1,07)
(6,0 ± 0,52)

5 4 3 2 1 5 4 3 2 1

.20 (5,1) .235 ±.020


(6,0 ± 0,52)
.30 (7,6)
.30 (7,6) .30 (7,6)
.10 (2,5)
.40 (10,2) .40 (10,2)
.90 (22,9) OUTPUT .90 (22,9) OUTPUT
MODULES MODULES
1.10 (27,9) HAVE ONLY 1.10 (27,9) HAVE ONLY
1.30 (33,0) TERMINALS TERMINALS
NUMBER 1-4 1.30 (33,0) NUMBER 1-4

WIRING DIAGRAM: Digital I/O Modules

LOAD HOT
DIGITAL 2 1 AC SUPPLY
AC OUTPUT
NEUTRAL

DIGITAL LOAD +
DC OUTPUT 2 1 DC SUPPLY

I/O Modules

HOT
DIGITAL 2 1 AC SUPPLY
AC INPUT
NEUTRAL

+
DIGITAL 2 1 DC SUPPLY
DC INPUT

DIGITAL
CONTACT 2 1
CLOSURE

I/O
4 Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois 60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com
Specifications are subject to change. Please refer to the current datasheet on www.grayhill.com for the most current published specifications for this product.

Digital I/O Module Selection Chart

I/O MODULE SIZE

Miniature Standard G5 OpenLine®


Saves 35% Space Compatible Industry Size Fused Outputs, Two Channel,
Integral LED Fused Outputs,
Integral LED

FUNCTION
(Check Specifications for Input and Output combinations, Feature or Option availability.)

Load Control Vcc Unique Options


Digital 120 Vac 5 Vdc Random Turn-on
220 Vac 15 Vdc Normally Closed
AC Output 24 Vdc Manual Override
4.5-28 Vdc Inductive Load

Load Control Vcc Unique Options


60 Vdc 5 Vdc Dry Contacts
Digital 200 Vdc 15 Vdc Manual Override
DC Output 24 Vdc
4.5-28 Vdc

Supply Vcc Input Voltage Unique Options


5 Vdc 120 Vac High DC
Digital 15 Vdc 220 Vac Voltage
AC Input 24 Vdc Input
4.5-28 Vdc

Supply Vcc Input Voltage Unique Options

I/O Modules
5 Vdc 3 to 32 Vdc 10 to 32 Vdc/
Digital 15 Vdc 15 to 32 Vac
DC Input 24 Vdc 8 KHz Switching
4.5-28 Vdc 35 to 60 Vac/Vdc
Contact Closure

I/O
Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois 60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com 5
Mouser Electronics

Authorized Distributor

Click to View Pricing, Inventory, Delivery & Lifecycle Information:

Grayhill:
70G-OAC24 70G-OAC24A 70G-OAC5 70G-OAC5A 70G-OAC5MA 70M-OAC5 70M-OAC5A 70-OAC15A 70-
OAC24 70-OAC24A 70-OAC5 70-OAC5A 70MRCK16-HL 70MRCK24-HL 70G-IDC15 70G-IDC24 70G-IDC5
70G-IDC5S 70-IDC24 70-IDC5 70-IDC5K 70M-IDC5 70G-IAC5 70G-ODC5 70G-ODC5A 70G-ODC5B 70L-IAC
70L-ODC5R 70L-ODCA 70M-IAC15 70M-IAC5A 70M-ODC5 70M-ODC5A 70M-ODC5B 70-ODC15 70-ODC24
70-ODC5 70M-ODC24 70-ODC5A 70M-IAC24A 70LRCK8-HL 70M-OAC15 70LRCK16-HL 70L-IDCB 70G-
ODC24A 70MRCK24-EC 70MRCQ24-HS 70-IDC15 70MRCK8-HL 70MRCK16-HS 70-OAC15 70G-IAC24
70MRCK16-EC 70G-ODC24B 70-ODC15B 70G-IDC5B 70G-IAC24A 70L-OACA-L 70-IAC24A 70M-OAC5-L
70MRCK24-HS 70G-ODC15B 70L-OACA 70MRCK8-EC 70-IDC5B 70M-OAC24 70G-ODC15 70LRCK24-HL 70-
OAC5-L 70-ODC24B 70L-ODCB 70L-IACA 70-OAC5A-L 70M-ODC15 70MRCQ24-EC 70G-ODC24 70L-IDC
70G-IAC15A 70L-OAC 70-IAC24 70G-OAC24-L 70M-IDC15 70G-IAC5A 70M-IAC15A 70G-OAC5A-L 70MRCQ24-
HL 70M-IDC24 70M-IAC24 70G-OAC15