SPA Series

Switching mode power supply with minimized noise and ripple


Features
● Built-in overcurrent protection, output short-circuit protection,
overheating and overvoltage protection circuits(SPA-075/100)
● Standard on safety IEC 60950, IEC 50178
● EMS(Electromagnetic susceptibility) EN61000-6-2
● EMI(Electromagnetic interference) EN61000-6-4
● Output voltage : 5VDC, 12VDC, 24VDC
● Output current : 30W, 50W, 75W, 100W
Please read “Caution for your safety” in operation
manual before using.

Ordering information
SPA 030 24
05 5VDC
Output voltage
12 12VDC
24 24VDC
030 30W
Output power 050 50W
075 75W
100 100W
Item
SPA Switching Mode Power Supply
Specifications
SPA- SPA- SPA- SPA- SPA- SPA- SPA- SPA- SPA- SPA- SPA- SPA-
Model
030-05 050-05 030-12 050-12 030-24 050-24 075-05 100-05 075-12 100-12 075-24 100-24
Capacity 30W 50W 30W 50W 30W 50W 75W 100W 75W 100W 75W 100W
Power supply※5 100-240VAC(85-264VAC) 100-120/200-240VAC(85-132/170-264VAC)
Frequency 50/60Hz
Input

Efficiency※1 Min. 60% Min. 67% Min. 74% Min. 80% Min. 70% Min. 78% Min. 72% Min. 78% Min. 80%
Current consumption※1 Max. 1.2A Max. 1.6A Max. 1.0A Max. 1.4A Max. 0.8A Max. 1.1A Max. 3.0A Max. 2.0A Max. 3.0A Max. 2.0A Max. 2.5A
Voltage 5VDC 12VDC 24VDC 5VDC 12VDC 24VDC
Current 6A 10A 2.5A 4.2A 1.5A 2 .1A 15A 20A 6.3A 8.5A 3.2A 4.2A
Votage fluctuation range※4 ±5%
Output

Input fluctuation ratio※2 Max. ±0.5%


Load fluctuation ratio※1 Max. ±2% Max. ±1% Max. ±2% Max. ±1%
Ripple※1 Max. ±1%
Starting time※1 Max. 200ms Max. 150ms Max. 250ms
Holding time※1 Min. 10ms Min. 5ms Min. 10ms Min. 5ms Min. 10ms
Max. 35A Max. 45A
Inrush current Max. 30A(100VAC) Max. 45A(100VAC) (100VAC) (100VAC) Max. 35A(100VAC)/
Max. 20A(100VAC)
protection Max. 40A(200VAC) /Max. 50A(240VAC) /Max. 40A /Max. 50A Max. 40A(240VAC)
(240VAC) (240VAC)
Protection

Output overcurrent Min.


Min. 110% Min. 110%
protection※3 105%
Output overvoltage
- 6.5V ±10% 16V ±10% 30V ±10%
protection
Output short-circuit
Max. 5ms Max. 10ms Max. 5ms Min. 10ms Max. 5ms
protection
Output indicator green LED
Insulation resistance Min. 100MΩ(Between all input and output terminals with 500VDC)
For 1 minute at 3.0kVAC 50/60Hz(Between all input and output terminals)
Dielectric strength
1 minute at 1.5kVAC 50/60Hz(Between all input terminals F.G)
Vibration 0.75mm amplitude at frequency of 10 to 55Hz(for 1 min.) in each of X, Y, Z directions for 2 hours
Shock 300m/s²in X, Y, Z directions for 3 times
Electromagnetic susceptibility EN61000-6-2 Appropriate
Electromagnetic interference EN61000-6-4 Appropriate
Protection IEC60950, IEC50178 Standard
Ambient -10 to 50℃ -10 to 40℃ -10 to 50℃
Environ temperature
Srorage: -25 to 65℃
-ment
Ambient humidity 25 to 85%RH, storage: 25 to 90%RH
Approval -
Unit weight Approx. 350g Approx. 400g
※1: 100% load for rated input voltage(100VAC).
※2: Rated input voltage •SPA-030/050 Series : 100-240VAC(85-264VAC)
under 100% of load.
•SPA-075/100 Series : 100-120/200-240(85-132/170-264VAC)
SPA-100-05 is under 100% of load for [100-120/200-240VAC(100-132/190-264VAC)].
※3: Rated input voltage(100VAC). ※4: Vary voltage by output voltage adjuster, it is changed over voltage variation range(±5%).
※5: The rated input volatge of SPA-100-05 is 100-120/200-240VAC(100-132/190-264VAC).
※Environment resistance is rated at no freezing or condensation.

P-8
Switching Power Supply

Output feature data for ambient temperature (A)


Photo
● SPA-030-05 ● SPA-075-05 ● SPA-100-05 ● SPA-100-12 electric
sensor
Load 120 Load 120
ratio (B)
100 ratio Fiber
(%) 100
Forced cooling (%) Forced cooling optic
80 sensor
80
Natural cooling Natural cooling
60 60 (C)
Door/Area
40 40 sensor

20 20
(D)
0 0 Proximity
-10 0 10 20 30 40 50 60 70 80 90 -10 0 10 20 30 40 50 60 70 80 90
sensor
Ambient temperature (℃) Ambient temperature (℃)
● SPA-030-12 ● SPA-050-12 ● SPA-075-12 (E)
Pressure
Load 120 Load 120 sensor
ratio Forced cooling
100 ratio
(%) 100 Forced cooling
(%) (F)
80 80
Rotary
Natural cooling Natural cooling encoder
60 60
40 (G)
40 Connector/
Socket
20 20
0 0 (H)
-10 0 10 20 30 40 50 60 70 80 90 -10 0 10 20 30 40 50 60 70 80 90 Temp.
Ambient temperature (℃) Ambient temperature (℃) controller

● SPA-030-24 ● SPA-050-24 ● SPA-075-24 ●SPA-100-24 (I)


Load 120 Load 120 SSR/
ratio Forced cooling Power
100 ratio
(%) 100 controller
(%) Forced cooling
80 80
Natural cooling (J)
60 Natural cooling Counter
60
40 40
20 (K)
20 Timer
0 0
-10 0 10 20 30 40 50 60 70 80 90 -10 0 10 20 30 40 50 60 70 80 90
Ambient temperature (℃) Ambient temperature (℃) (L)
● SPA-050-05 Panel
meter
Load 120
ratio (M)
100
(%) Forced cooling Tacho/
Speed/ Pulse
80 meter
Natural cooling
60
(N)
40 Display
unit
20
0 (O)
Sensor
-10 0 10 20 30 40 50 60 70 80 90 controller
Ambient temperature (℃)

Feature data for output overvoltage protection


(P)
Switching
power
supply
● SPA-075-05 / SPA-100-05 ● SPA-075-12 / SPA-100-12 ● SPA-075-24 / SPA-100-24
(Q)
Output Output Output Stepping
Operation range of Operation range of Operation range of
voltage voltage motor&
overvoltage protection voltage overvoltage protection overvoltage protection
Driver&Controller
6.5V function[6.5V ±10%] function[16V ±10%] function[30V ±10%]
16V 30V
Output voltage range Output voltage range Output voltage range (R)
Graphic/
can not be covered can not be covered can not be covered Logic
within standard within standard within standard panel
5V Output voltage 12V Output voltage 24V Output voltage
fluctuation range fluctuation range fluctuation range (S)
Field
[5V ±5%] [12V ±5%] [12V ±5%]
network
device
0V 0V 0V

Feature data of overcurrent protection (T)


Software

Output
voltage ● It is when the rated input voltage is 100VAC, 100%. (U)
(V) ● It is able to protect overcurrent by load with built-in Other

overcurrent protection circuit.


When the over rated current is flowed, the circuit is
operated (Output voltage is fallen.) and it is cancelled
when the load current is under the rated current. (It is
returned to the rated output voltage.)
Output current (%)
Rated

P-9
SPA Series

Block diagram
Inrush current
protection Rectifier Rectifier
(L) circuit circuit circuit
Input power
Noise
85-264VAC
filter
50/60Hz
(N)

Control
circuit Voltage
detection
F·G
Overcurrent
protection
circuit

0V
DC OUT
+V

Dimensions (unit: mm)


● SPA-030/050 Series ● SPA-075/100 Series
55 33 100 30.4

LED LED

4
4

VR VR

2-M3

87
97
87
97

5-M3.5 2-M3
5-M3.5 (Bottom side)
(Bottom side)
45.5

38.5
3.5
3.5

6
6

4 154
4 114
9.5

3.5

3.5
7.5

20
40

42
3.5
28

3.5
28
17.5

22.5

29
29

83 25 138 10
114 154
120 160

Front part identification

1. Output display LED(green)


1 2. Output voltage adjuster
2 ※V.ADJ(voltage variable range: ±5% of the rated
output voltage)
3 3. Output power [+] terminal
4 4. Output power [-] terminal
5 5. [F.G] terminal
6. Input power [N] terminal
6
7. Input power [L] terminal
7

P-10
Switching Power Supply

Proper Usage (A)


Photo
electric
1. Technical information of operation 3. Caution for mounting sensor

For switch input voltage type, input voltage is 220V as ① Please mount the device on metal panel for the (B)
Fiber
factory default.To swich input voltage for 110V, remove the reliability. optic
cover then select proper jumper switch as below figures. ② Please mount the device in a ventilative place for high sensor

radiation of heat. (C)


Door/Area
sensor
4. Please use the power line as below specification.
(D)
Input power line Proximity
AWG19 to 21 AWG16 to 18
specification sensor

SPA-030-05 (E)
SPA-030-12 Pressure
sensor
SPA-050-12 SPA-050-05
110V 220V SPA-075-12 SPA-075-05
Model (F)
SPA-030-24 SPA-100-05 Rotary
encoder
SPA-050-24 SPA-100-12
2. Technical information of operation SPA-075-24
① This product is not available to operate of output voltage SPA-100-24 (G)
Connector/
as parallel and series. Socket

② The output current should be used within the rated


range. When it is operated in overcurrent status, the life (H)
Temp.
span of product can be shortened. controller

③ The output voltage should be used within the rated (I)


range. When the output overvoltage limit function SSR/
Power
is operated, the product operated normally with controller

cancellation of input power for few minutes.


④ The overvoltage limit function is operated when it is (J)
Counter
exceeded the rated output voltage range with an output
voltage adjuster.
(K)
⑤ This product has overheating protection function. It is Timer

operated normally when releasing the load connection


for few minutes. (L)
Panel
⑥ The power factor is within 0.5 to 0.7 using condenser meter

rectified method. Please use the below formula and


(M)
check the input power capacity when using a cabinet Tacho/
Speed/ Pulse
panel or transformer. meter

Apparent power[VA] = Active Power [W]


(N)
Power factor×Efficiency Display
⑦ This product does not have harmonics suppression and unit

power factor correction circuit.


(O)
Please mount the device for it. Sensor
controller
⑧ This product has a noise filter, it can be changed with
the mounting place and connection. (P)
Switching
⑨ Please change as a same rated fuse when the inner power
supply
fuse is broken.
(Q)
Stepping
motor&
Driver&Controller

(R)
Graphic/
Logic
panel

(S)
Field
network
device

(T)
Software

(U)
Other

P-11