Professional Documents
Culture Documents
Protections Catalogue
December 2010
ComAp
Protections catalogue
Mains-decoupling protections are located at the point of connection of a device generating electrical
energy ("generator") and the mains, e.g. public grid operated by a local power utility, also referred to
as DNO (Distribution Network Operator). The main task of mains-decupling relay is to disconnect the
generator from the grid in case of unacceptable conditions, caused either by a failure in the grid or by
the generator itself. Thus, the mains is kept in a controllable state and the property of the DNO, his
customers connected to the public mains as well as the property of the generator owner is protected.
The protective functions described in this document are sometimes referred to as an "ANSI codes",
i.e. numerical indications of the protective functions and devices. These are based upon the ANSI
/IEEE Standard C37.2.
Any three-phase voltage system may be broken-down to those three components. By expressing
solely the phasor magnitude of positive, negative or zero sequence respectively, significant
phenomena on the measured voltage may be described:
- In a perfectly symmetrical system, the measured voltage is exactly the same magnitude as the
positive sequence voltage. Negative and zero sequence are not present
- With growing asymmetry, either in angle or amplitude of some of the phasors, the positive
sequence voltage magnitude decreases and the negative sequence voltage increases.
- With moving the zero point of the measured system away from the geometrical centre of the
system, the zero sequence increases, indicating shift in the zero point of the measured
system. This zero sequence voltage shift is however different from the Neutral Voltage
Displacement method, which is generally used for detecting the ground faults in isolated or
partially earthed systems.
Specific cases of the unintentional islanding are the automatic reclosing and situations where the imbalance
between power production and consumption in the islanded area is very big. Consequences of such
situations are usually very fast and could not be safely protected only by frequency and voltage protections.
For this purpose, a specific type of very fast "Loss of mains" protections, is applied.
Sometimes, it is possible to meet with requirements for different IDMT curve shapes, according to IEC
standards. The most common are "normal", "inverse" and "very inverse" curves.
Ink Inl
K L
L1
G k l L2 This arrangement necessary for restricted earth fault
k l L3 protection. The location of the neutral earthing point in
k l relation to the protection current transformers in the neutral
N conductor determines whether four or five current
k l
L K
Ink Inl
L1
G k l L2
k l This arrangement necessary for restricted earth fault
L3 protection. The location of the neutral earthing point in
k l relation to the protection current transformers in the neutral
N
k l conductor determines whether four or five current
transformers are employed.
Ink Inl
Directional overcurrent protection, applied in the point of generator connection to mains, is considered
a loss of mains protection, however it does not substitute the traditional loss of mains protections like
Vector shift or ROCOF. The typical application is a generator with its own load consumption (e.g. peak
shaving, soft transfer stand-by, or other applications). The generator is usually used to support the
local consumption with no export to the mains. In case of mains transition into an island mode, the
generator, running in parallel with the islanded area, starts to supply its consumption, generating
current in opposite direction. DOC protection relay is used to avoid this situation, and trip the
generator from the islanded mains, combining the overcurrent protection together with its directional
character. Compared to the "reverse power protection", DOC protection detects also reactive currents
within the given angle, what increases its sensitivity for tripping if reactive components are present in
the islanded area (transformers, capacitors, cables, compensators, ...).
90°
150°
0°
DOC threshold
Trip
Base angle area
-135°
-60°
-90°
Very common application of reverse power is protection of the generator mechanical drive from
motoric operation, which is an undesirable and often dangerous mode for some types of mechanical
drives.
NVD is not considered as mains-decupling protection, though it may be required on larger machines
or HV alternators connection to mains. In ComAp, it is offered in IP-C, D and E and in InteliPro with
possibility of setting whether the NVD it contributes to the common trip of the relay or uses its own
separate output for signalization of the NVD alarm.
The reclosing function is typical for feeder protection, where the fault can be expected at the feeder
and its disconnection from the mains may result in successful clearance of the fault, making the
reclosing cycle successful. It is also requested by some DNOs in mains-protection applications.
Breaker failure
Breaker failure is a supplementary protective function assuring that the circuit breaker, tripped by any
other protective function is securely open. This is evaluated based on the CB feedback. The function
issues a separate output, providing a backup trip which either triggers a backup mechanism of the
same circuit breaker, or trips another back-up breaker.