Professional Documents
Culture Documents
Product Guide
REM 545
Machine Terminals REM 543 REM 545
1MRS751173-MBG
Issued: June 1999
Status: Updated
Version: H/25.10.2010
Data subject to change without notice
Features • Integrated machine terminals for the pro- • Control functions including local and
tection, control, measurement and supervi- remote control of switching objects with
sion of small and medium size generators, synchro-check, status indication of the
synchronous motors and large asynchro- switching objects and interlockings on bay
nous motors. and station level.
• Voltage and current measurement via con- • Measurement of phase currents, phase-to-
ventional measuring transformers or cur- phase and phase-to-neutral voltages, neu-
rent sensors and voltage dividers. tral current and residual voltage, frequency,
• Fixed man-machine interface including a power factor, active and reactive power
large graphic display, or an external display and energy.
module for flexible swichgear installation. • Optional RTD/mA I/O-module for stator
• Extended functionality including protec- winding, bearing and ambient temperature
tion, control, measurement, condition moni- monitoring. Analog mA outputs for interfac-
toring and communication. ing with process control system.
• Non-directional/directional overcur- • Condition monitoring including circuit-
rent/earth-fault protection functions, over- breaker condition monitoring, trip circuit
/undervoltage protection functions and spe- supervision and internal self-supervision of
cial functions for the protection of motors the machine terminal.
and generators, e.g. voltage controlled • Communication over three communication
overcurrent protection, differential protec- interfaces: one for local communication
tion with several principles, underexcitation with a PC and the others for remote com-
protection, underimpedance protection munication with a substation control sys-
(line back-up prot.), thermal overload pro- tem or with a substation monitoring system.
tection, protection against unbalanced • Part of the ABB’s Distribution Automation
load, abnormal frequency protection, system.
reverse or low-forward power protection
and start-up supervision for motors.
Application The REM 543 and REM 545 rotating ma- In addition to protection, measurement, con-
chine terminals are designed to be used as an trol and condition monitoring and general
integrated main protection system of genera- functions, the machine terminals are provided
tor and generator-transformer units in small with a large amount of PLC functions allow-
and medium-power diesel, hydroelectric and ing several automation and sequence logic
steam power plants, etc. The protection of functions needed for substation automation to
large and/or important MV synchronous and be integrated into one unit. The data commu-
asynchronous motors used e.g. in pumps, nication properties include SPA bus, LON
fans, mills and crushers during start-up and bus or MODBUS communication with
normal run forms another application area. higher-level equipment. Further, LON inter-
The REM 54_ machine terminals as inte- bay communication, together with PLC func-
grated packages make possible compact tions, minimizes the need for hardwiring
marine environment solutions for unit protec- between the machine terminals.
tion, too.
3
Machine Terminals REM 543 REM 545
1MRS751173-MBG
Design The machine terminals REM 543 and REM The user can set the length of a recording
545 differ from each other in the number of within a range determined by the number of
digital inputs and outputs available. Please analogue inputs used. The number of record-
refer to the section “Ordering” for more ings depends on the sampling frequency,
details. length of recordings and number of analogue
inputs.
The REM 54_ machine terminals incorporate
a wide range of functions: The recordings can be uploaded with a DR-
Collector Tool which converts the data to a
• Protection functions COMTRADE format. The DR-Collector Tool
• Measurement functions is supported in CAP501 and CAP505 relay
tools.
• Control functions
• Condition monitoring functions
Control functions
• General functions The control functions are used to indicate the
• Communication functions status of switching devices, i.e. circuit break-
• Standard functions ers and disconnectors, and to execute open
The function blocks are documented on the and close commands for controllable switch-
CD-ROM “Technical Descriptions of Func- ing devices of the switchgear. Furthermore,
tions” (1MRS 750889-MCD). control functions provide on/off switching
objects for control logic purposes and miscel-
laneous objects for data monitoring, etc.
Protection functions
Protection is one of the most important func- The control functions configured with the
tions of the REM 54_ machine terminal. The Relay Configuration Tool must be linked to
protection function blocks are independent of object status indicators included in the
each other and have their own setting groups, MIMIC configuration picture displayed on
data recording, etc. the HMI. The object status indicators are used
to indicate the status of switching devices via
Typical current-based protection functions the MIMIC picture and to control them
(e.g. overcurrent) can use either Rogowski locally.
coil or conventional current transformer mea-
surement. Correspondingly, voltage-based
functions (e.g. overvoltage) use either voltage Condition monitoring functions
dividers or voltage transformers. Condition monitoring function blocks such as
supervision of the energizing current and
For further information about functionality voltage input circuit, operation time counter,
levels and the protection functions included circuit-breaker electric wear, scheduled main-
in them, refer to the table “Functionality lev- tenance, trip circuit supervision and breaker
els, protection functions” in section “Order- travel time are available for the REM 54_
ing”. machine terminals.
Design (cont´d) and the functions can be interconnected with Analogue channels of the machine terminal
protection, control, measurement, condition are configured with the CAP 505 Relay Prod-
monitoring and other standard functions. In uct Engineering Tool.
addition, digital inputs and outputs and LON
inputs and outputs can be connected to stan- A separate scaling factor can be set for each
dard functions by using the Relay Configura- analogue channel. The factors enable differ-
tion Tool. ences between the ratings of the protected
unit and those of the measuring device (CTs,
VTs etc.). The setting value 1.00 means that
Other functions the rated value of the protected unit is exactly
the same as that of the measuring device.
Low auxiliary voltage indication
The REM 54_ terminal is provided with a
low auxiliary voltage indication feature. The • Machine terminals with the hardware
power supply module issues an internal alarm number
signal when a drop in the power supply volt- REM54x_xxxAAAA/CAAA/AAAB are
age is detected (ACFail, active low). The configured for matching transformers
alarm signal is activated if the power supply • Machine terminals with the hardware
voltage is about 10% below the lowest rated number REM54x_xxx
DC input voltage of the power supply mod- AABA/CABA/AABB are configured for
ule. matching transformers and sensor inputs
5
Machine Terminals REM 543 REM 545
1MRS751173-MBG
Design (cont´d) Oscillation suppression Analogue outputs can be utilized for transfer-
The machine terminals have two global pa- ring any measured or calculated information
rameters for the suppression of digital input to panel meters or e.g. PLCs.
oscillation. The settings of these parameters
determine the oscillation level and hysteresis Alarm LED indicators
for all digital inputs. An event is generated if The machine terminal offers eight alarm LED
oscillation is detected. indicators to be configured with the Relay
Mimic Editor. The LED colours (green, yel-
Attributes of a digital input for machine ter- low, red), their use and the ON and OFF state
minal configuration texts can be freely defined. Three basic oper-
For each digital input the status of the input ation modes are supported: non-latched,
(value), the time tag for the status change latched-steady and latched blinking. Alarms
(time) and the validity of the digital input can be acknowledged remotely, locally and
(invalidity) can be issued by the attributes. by using logic.
These attributes are available in the machine
terminal configuration and can be used for The alarm channels include time tagging for
various purposes. detected alarms. The time tagging principle
used depends on the operation mode.
Digital outputs
The digital outputs of the machine terminal Interlocking LED indicator
are categorized as follows: The interlocking LED indicates that control
operation has been interlocked or that the
• HSPO: High-speed power output, double- interlocking is in bypass mode, e.g. when
pole contact, preferred for tripping pur- control is possible despite of interlocking.
poses and for circuit breaker and discon-
nector control Trip Circuit Supervision
• PO: Power output, either single-pole or The purpose of this function is to supervise
double-pole contact, preferred for circuit the tripping circuitry of the circuit breaker.
breaker and disconnector control An alarm will be generated in case a faulty
tripping circuit, e.g. a circuit is not able to
• SO: Signal output, either NO (Normally
Open) or NO/NC (Normally Open/Nor- perform a trip, is detected.
mally Closed) contact. The output contact
The supervision is based on the constant-cur-
is a normal duty contact and cannot be
rent injection through the tripping circuitry.
used for controlling a heavy load such as a
circuit breaker
Display panel
RTD/analogue inputs The machine terminal is provided with either
The REM 543 and REM 545 machine termi- a fixed display or an external display module.
nals equipped with an RTD/analogue module The external display module requires a sepa-
(RTD1) have eight general purpose analogue rate voltage supply from a common source
inputs for DC measurement. The RTD/ana- with the main unit. The display consists of 19
logue inputs are galvanically isolated from rows divided into two windows: a main win-
the machine terminal power supply and dow (17 rows) and an assisting window
enclosure. However, the inputs have a com- (2 rows).
mon ground. The general purpose RTD/ana-
logue inputs accept voltage-, current- or The graphic display presents detailed infor-
resistance-type signals. For each measuring mation on MIMIC, objects, events, measure-
mode, a separate parameter is provided for ments, control alarms, and parameters. The
choosing between the available measurement assisting window is used for terminal-depen-
ranges. dent indications/alarms and help messages.
Analogue outputs Additionally, the panel includes the following
The REM 543 and REM 545 feeder terminals HMI items:
equipped with an RTD/analogue module have
four general purpose 0...20 mA analogue cur- • three push-buttons for object control (I, O,
rent outputs. All outputs are galvanically iso- object selection)
lated from the supply and enclosure of the
machine terminal and from each other. • eight freely programmable alarm LEDs
with different colours and modes accord-
ing to the configuration
6
Machine Terminals REM 543 REM 545
1MRS751173-MBG
Design (cont´d) • LED indicator for control test and inter- machine terminal to the fibre-optic communi-
locking cation bus. The module RER 103 supports
• three protection LED indicators both SPA bus and LON bus communication.
• HMI push-button section with four arrow
buttons and buttons for clear and enter Self-supervision
• optically isolated serial communication The machine terminal REM 54_ is provided
port with an extensive self-supervision system.
The self-supervision system handles run-time
• backlight and contrast control fault situations and informs the user of faults
• freely programmable button (F) which can via the HMI and SPA/LON bus communica-
be used in the configuration of the tion.
machine terminal
• a button for remote/local control When a fault has been detected, the green
The HMI has two main levels, the user level Ready indicator starts blinking and a fault
and the technical level. The user level is for indication text appears on the HMI. At the
“everyday” measurements and monitoring same time, the machine terminal delivers a
whereas the technical level is intended for fault signal to the self-supervision output
advanced machine terminal programming. relay and blocks the protection trip outputs.
7
Machine Terminals REM 543 REM 545
1MRS751173-MBG
Design (cont´d) All of the eight alarm function blocks can be External parameterization
configured in the same alarm view of the The Relay Setting Tool is used for parameter-
mimic editor. ON and OFF state texts (only izing and setting the machine terminal exter-
one language version at the time can be sup- nally. The parameters can be set off-line on a
ported for the alarm) and LED colours can be PC and downloaded to the machine terminal
defined. Three different colours can be used over a communication port. The menu struc-
to define the ON and OFF state. Three basic ture of the setting tool, including views for
modes are available: parameterization and settings, is the same as
the menu structure of the machine terminal.
• non-latched
• latched-steady Terminal connections
• latched blinking All external circuits are connected to the ter-
Interlocking LED texts can also be defined in minal blocks on the rear panel. The terminal
the same alarm view but the colour of the block for the measuring transformers consists
interlocking LED cannot be changed. of fixed screw terminals.
Local parameterization
When the parameters are set locally, the set-
ting parameters can be chosen from the hier-
archical menu structure. The desired
language for parameter description can be
selected.
8
Machine Terminals REM 543 REM 545
1MRS751173-MBG
+
L1 L3
Q1 A
0 -
+
Q0 N
n
X4.1
- I
+ *) a
da dn
+
Q9 PS1_4_ACFail Mains 1
- 2
X1.1
27 PS1_4_TempAlarm
100V Ch 10, VT4
25 X3.2
L1 L3 24
SERIAL BUS
P1 S1 100V Ch 9, VT3
22 X3.3
SERIAL BUS
21
100V Ch 8, VT2
S2 19 X4.1
3
P2 18
100V Ch 7, VT1 IRF 4
16
S1 15 0.2A
14 1A Ch 6, CT5 5
13
12 6
1A
S2 11 5A Ch 5, CT4
10
9 7
1A
8 PS1_4_HSPO3 9
5A Ch 4, CT3
8
7 +
M 6 1A 10 +
5
3~
5A Ch 3, CT2 External
4 0 open
3 1A PS1_4_HSPO1 11
2 5A Ch 2, CT1 13
1 PS1_4_TCS1 TCS1 12
+
15 +
X2.1 Ch 10, sensor External
DIFF
16
1 close
PS1_4_HSPO2
X2.2 Ch 9, sensor 18
DIFF
PS1_4_TCS2 TCS2 17
X2.3 Ch 8, sensor
DIFF
X2.4 Ch 7, sensor
DIFF
X4.2
X2.5 Ch 5, sensor
DIFF
8
X2.6 Ch 4, sensor
Disconnector Q1
DIFF 9 Close
PS1_4_HSPO4 11
X2.7 Ch 3, sensor 10
DIFF
12
X2.8
DIFF
Ch 2, sensor Disconnector Q1
PS1_4_HSPO5
13 Open
Ch 1, sensor 15
X2.9 DIFF 14
16
17
X4.2
1
2 PS1_4_BI1 PS1_4_SO1 18
4 PS1_4_BI2
5
6 PS1_4_BI3
7
X5.2
3
X5.1
1
BIO1_5_BI1 BIO1_5_SO1 4
- 2
3 5
BIO1_5_BI2
4 6
BIO1_5_SO2
BIO1_5_BI3
- 5 7
6 9
BIO1_5_BI4
7 8
BIO1_5_SO3
BIO1_5_BI5
- 8 10
9 12
BIO1_5_BI6
11
- 10
BIO1_5_BI7
BIO1_5_SO4
11 13
15
12
BIO1_5_BI8
14
13 BIO1_5_SO5
*) Power flow direction 14
BIO1_5_BI9 16
18
15
16 BIO1_5_BI10
17
17 BIO1_5_SO6
18 BIO1_5_BI11
X5.2
1
BIO1_5_BI12
2
REM 543
(1MRS 090212-AAB/CAB)
em543ext
9
Machine Terminals REM 543 REM 545
1MRS751173-MBG
Design (cont´d) +
L1 L3
Q1 A
0
+
Q0 N
n
X4.1
I
+ *) a
da dn
PS1_4_ACFail Mains + 1
Q9 -
2
X1.1 PS1_4_TempAlarm
27 100V Ch 10, VT4 X3.2
25 SERIAL BUS
L1 L3 24
P1 S1 100V Ch 9, VT3
X3.3
22 SERIAL BUS
21
100V Ch 8, VT2
S2 19 X4.1
3
P2 18
100V Ch 7, VT1 IRF 4
16
S1 15 0.2A
14 1A Ch 6, CT5 5
13
6
12 1A + -
S2 11 5A Ch 5, CT4
10
7 External
9
8
1A
5A Ch 4, CT3
PS1_4_HSPO3 9 0 open
7 8
M 6 1A 10 -
5 5A Ch 3, CT2
3~ 4
3 PS1_4_HSPO1 11
2
1A
5A Ch 2, CT1 13 + + -
1 PS1_4_TCS1 TCS1 12
- External
X2.1
15 1 close
Ch 10, sensor
DIFF
PS1_4_HSPO2 16
X2.2
DIFF
Ch 9, sensor
PS1_4_TCS2 TCS2
18 +
17
X2.3 Ch 8, sensor
DIFF
X2.4 Ch 7, sensor
DIFF
X4.2
X2.5 Ch 5, sensor
DIFF
8
4 PS1_4_BI2
5
6 PS1_4_BI3
7
X5.2
3
X5.1
1
BIO1_5_BI1 BIO1_5_SO1 4
- 2
3 5
BIO1_5_BI2
4 6
BIO1_5_SO2
BIO1_5_BI3
- 5 7
6 9
BIO1_5_BI4
7 8
BIO1_5_SO3
BIO1_5_BI5
- 8 10
9 12
BIO1_5_BI6
11
- 10
BIO1_5_BI7
BIO1_5_SO4
11 13
15
12
BIO1_5_BI8
14
13 BIO1_5_SO5
*) Power flow direction 14
BIO1_5_BI9 16
18
15
16 BIO1_5_BI10
17
17 BIO1_5_SO6
18 BIO1_5_BI11
X5.2 X7.1
1
BIO1_5_BI12
2
BIO2_7_PO1
17
18
X7.2
X7.1
1 BIO2_7_PO2 1
BIO2_7_BI1 2
2
3 3
BIO2_7_BI2
4 4
BIO2_7_BI3 BIO2_7_PO3
5 5
6
6
BIO2_7_BI4
7
7
BIO2_7_BI5
8 BIO2_7_PO4 8
9
9 10
BIO2_7_BI6
11
10 BIO2_7_BI7
11
BIO2_7_PO5 12
12 13
BIO2_7_BI8 14
15
13
14 BIO2_7_BI9
BIO2_7_PO6 16
15 17
16 BIO2_7_BI10 18
REM 545
(1MRS 090222-AAB/CAB)
em545ext
10