Professional Documents
Culture Documents
5
VIEW ON HV 7 VIEW ON TAP SWITCH END VIEW ON LV
6
PHASE ROTATION PHASE ROTATION
(A8 B8 C8) (c2 b2 a2 yN)
11 8
1U 1V 1W 9 2W 2V 2U 2N
10
15 12
D 114 114 114 D
105 105
1759 O/ALL
OF HV FLANGE
OF LV FLANGE
1049 LV GLAND PLATE
1320
1320
2 PLAN VIEW
A
800kVA ELECTRICAL RATINGS
No Load Full-Load Current at
Voltage Ratio HV Tappings Vector Group Frequency Normal Tap
at Normal Tap HV Side LV Side 15 2 DETACHABLE RADIATORS with AIR-RELEASE & DRAIN PLUG (520W x
+7.5 to -5.0% 1200C x 7S x 40P)
11000 / 415V in 2.5% Dyn11 50Hz 42A 1113A 14 1 DRAIN VALVE (25NB) with MALE PLUG
ESSENTIAL LABELS HV TERMINAL DETAILS (01)
0 - 250A A = M12 20 NM
INCREMENTS 13 4 JACKING PADS
524
RE-DRAWN IN INVENTOR CUSTOMER GENERAL ARRANGEMENT DRAWING FOR West Yorkshire LS11 5SS, United Kingdom
01 800kVA WILSON e1 ECOTRANS Tel:+44 (0) 113 271 7588
S.O. NUMBER 11000/415V, 50Hz, Dyn11, ONAN/KNAN Fax:+44 (0) 113 277 5124
DATE AL WOUND DISTRIBUTION TRANSFORMER web: www.wilsonpowersolutions.co.uk email: info@wilsonpowersolutions.co.uk
P.O. NUMBER
REV. BY: S. MALLETT 08-NOV-2016
00 ASHWINI H. MALEPATI H. MALEPATI ORIGINAL VERIFIED: F. MEHMOOD 10-MAR-2017 DRAWN
BASED ON: REV REV BY VERIFIED APPROVED DESCRIPTION APPROVED: J. DUCE 10-MAR-2017
W.O. NUMBER BY:
S. MALLETT DATE: 24/08/2016 DRG NO: WPS-800-AL-GA
6 5 4 3 2 1 WPDF02 REV 0 25-N0V-14