NO.:PSTR22071503
Name of Product Surge Protective Device (SPD)
Part No. DS120/320-(V+T)-S
Test date 2022/07/15~2022/07/16
Tested by Weijian He
Reviewed by Zhicheng Yi
Approved by Xudong Ding
Test place Hitech Surge Protection Testing Center
Standard IEC61643-11:2011
1
Prosurge Electronics
1. Identification and marking: (IEC61643-11, Section 7.1.1/7.1.2/8.2)
The following Identifications and markings are permanently attached to the body of the SPD,
b) Uc
c) Class II
g) Identification of terminals
Markings are not been placed or removable, indelible and legible by rubbing the makings by hand for 15s with a piece of cotton
soaked with water and again for 15s with a piece of cotton soaked with aliphatic solvent hexane.
Pass criteria
After test, the marking should be easily legible.
Conclusion: pass
Conclusion: Pass.
2
Prosurge Electronics
3.Residual current (IEC61643-11, Section 7.2.2/8.3.2)
The SPD was connected as for normal use, and voltage shall be adjusted to the reference test voltage of Uref.
To DS120/320-(V+T)-S, the Uref is 255 Vac
Measure the residual current flowing through the PE terminal.
Result:
Conclusion: Pass.
Then testing SPDs to class II, 8/20 current impulses with a sequence of crest values of approximately 0,1; 0,2; 0,5; 1,0 times In
shall be applied. If the SPD contains only voltage-limiting components, this test needs only to be performed at crest values of
Iimp for test class I or In for test class II.
To voltage switching SPD, The 1,2/50 voltage impulse is used. The generator voltage is set to an open circuit output voltage of 6
kV.
Pass criteria
The highest voltage value shall not exceed the value declared by the manufacturer
NOTE: The residual voltage is the highest crest value measured during surge current flow. Any high frequency disturbances
and spikes before and during current flow caused by specific generator design, like crowbar generators, are disregarded
Voltage and current records and visual inspection shall show no indication of puncture or flashover.
No visible damage shall occur during the test.
Result:
The maximum residual voltage measured is at In: 60kA 8/20μs.
Max measured limiting voltage @ In: 1488V(L-N)
Max measured limiting voltage @ 1.2/50: 1140V(N-PE)
3
Prosurge Electronics
4
Prosurge Electronics
Three group of five impulse of In 8/20 current impulse with positive polarity, and SPDs are energized at Uc.
Each impulse shall be synchronized to power frequency. Starting from 0o the synchronization angle shall be increased in steps of
(30+/-5) intervals. After the last group of impulses and the 1min period the SPD remains applied to Uc for another 15min to
check for stability.
The SPD is energized at Uc by means of a voltage source having a nominal current capability of at least 5A. This test is carried
out with current impulses in steps up to Ipeak for SPDs tested.
Pass criteria
Thermal stability shall be achieved.
Voltage and current records and visual inspection shall no indication of puncture or flashover.
No visible damage shall occur.
Values for measured limiting voltage after the test shall be low or equal to Up.
Internal and external disconnectors shall be in work order after test.
Result:
60 60 60 60 P
First group P
60 60 60 60
In=60kA 5 times (interval 1 min) with Uc applied
60 60 60 60 P
60 60 60 60 P
Interval between the impulses 50~60s, Interval between the groups 30~35 minutes
60 60 60 60 P
60 60 60 60 P
Second group P
60 60 60 60
In=60kA 5 times (interval 1 min) with Uc applied
60 60 60 60 P
60 60 60 60 P
Interval between the impulses 50~60s, Interval between the groups 30~35 minutes
60 60 60 60 P
60 60 60 60 P
Third group P
60 60 60 60
In=60kA 5 times (interval 1 min) with Uc applied
60 60 60 60 P
60 60 60 60 P
5
Prosurge Electronics
Interval 25~30 minutes, check thermal stability, cool down to ambient temperature.
Measured limiting voltage@In 60KA 1440 1460 1486 P
Measured limiting voltage@1.2/50 1220 P
Conclusion: Pass
The SPDs connect to a power frequency source. And the current is set to a constant value.
To first sample, the test is started at a value of 2mA rms or at Uc. This value of current is then increased in steps of either 2mA
or 5% of the previously adjusted test current, whichever is greater. Each step is maintained until thermal equilibrium is
reached( variation of temperature at the hottest spot less than 2K within 10min).
For the other samples the start point shall be changed from 2mA to a current corresponding to 5 steps below the current value at
which the first sample disconnected .
Pass criteria
The surface temperature rise of indoor SPDs shall not exceed 120K during and after test.
Five min after disconnection of all non-linear components under test the surface temperature rise shall not exceed 80K.
L-N Result:
Test value 4# 5# 6#
Environment temp.(C) 26
Hottest surface temp (K) 103 105 105
Disconnecting Current value 22 21 24
(mA)
Surface temp after 5 min(K) 57 54 58
Conclusion P P P
Conclusion: Pass
6
Prosurge Electronics
The SPD shall be connect to a power source for UT (0,-5%) for a duration tT (+5%,0).
And Immediately following the application of Uref (0,-5%) for a duration 15min.
Pass criterial
1. TOV failure mode
During the test, the tissue paper shall not catch fire.
SPDs with IP degree equal to, or greater than, IP20 shall not have live parts accessible with a standardize test finger applied
with a force of 5N.
If internal disconnection occurs during the test, there shall be clear evidence of effective disconnection of the corresponding
protective components.
N-PE:
Sample No. UT (V) tT (mS) Result/conclusion
7# 1200 200 withstand mode/P
8# 1200 200 withstand mode/P
9# 1200 200 withstand mode/P
Conclusion: Pass
7
Prosurge Electronics
Result:
After test, three samples show:
No abnormal was found, no sealing compound flow out. And IP is OK
Conclusion: Pass
Result:
After test, three samples show:
No abnormal was found, internal disconnectors did not operate.
Conclusion: Pass
Result:
During the test, three samples show no visible flame and sustained glowing.
Conclusion: Pass
Reference