190--600 V Gas
Standard Features
D Kohler Co. provides one-source responsibility for the
generating system and accessories.
D The generator set and its components are prototype-tested,
Ratings Range factory-built, and production-tested.
60 Hz 50 Hz
Standby: kW 100--150 90--125 D The 60 Hz generator set offers a UL 2200 listing.
kVA 100--187.5 90--156 D The generator set accepts rated load in one step.
D The 60 Hz generator set meets NFPA 110, Level 1, when
equipped with the necessary accessories and installed per
NFPA standards.
D A one-year limited warranty covers all systems and
components. Two-, five-, and ten-year extended warranties
are also available.
D Alternator features:
d The unique Fast-Responset II excitation system delivers
excellent voltage response and short circuit capability
using a permanent magnet (PM)-excited alternator.
d The brushless, rotating-field alternator has broadrange
reconnectability.
Generator Set Ratings D Other features:
d Controllers are available for all applications. See
Natural Gas controller features inside.
130_C Rise
Standby Rating d The electronic, isochronous governor incorporates an
Alternator Voltage Ph Hz kW/kVA Amps integrated drive-by-wire throttle body actuator delivering
120/208 3 60 150/187.5 520
precise frequency regulation.
127/220 3 60 150/187.5 492
120/240 3 60 150/187.5 451
120/240 1 60 100/100 417
139/240 3 60 150/187.5 451
220/380 3 60 145/181.3 275
277/480 3 60 150/187.5 226
347/600 3 60 150/187.5 180
4S13 110/190 3 50 125/156 475
115/200 3 50 125/156 451
120/208 3 50 125/156 434
110/220 3 50 125/156 410
110/220 1 50 90/90 409
220/380 3 50 125/156 237
230/400 3 50 125/156 226
240/416 3 50 125/156 217
120/208 3 60 150/187.5 520
127/220 3 60 150/187.5 492
120/240 3 60 150/187.5 451
120/240 1 60 110/110 458
139/240 3 60 150/187.5 451
220/380 3 60 145/181.3 275
277/480 3 60 150/187.5 226
4S15 347/600 3 60 150/187.5 180
110/190 3 50 125/156 475
115/200 3 50 125/156 451
120/208 3 50 125/156 434
110/220 3 50 124/155 407
220/380 3 50 125/156 237
230/400 3 50 125/156 226
240/416 3 50 125/156 217
RATINGS: All three-phase units are rated at 0.8 power factor. All single-phase units are rated at 1.0 power factor. Standby Ratings: Standby ratings apply to installations served by a reliable utility source.
The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046/1, BS 5514, AS 2789, and DIN 6271.
Prime Power Ratings: Prime power ratings apply to installations where utility power is unavailable or unreliable. At varying load, the number of generator set operating hours is unlimited. A 10% overload
capacity is available for one hour in twelve. Ratings are in accordance with ISO-8528/1, overload power in accordance with ISO-3046/1, BS 5514, AS 2789, and DIN 6271. For limited running time and base
load ratings, consult the factory. Obtain the technical information bulletin (TIB-101) on ratings guidelines for the complete ratings definitions. The generator set manufacturer reserves the right to change the
design or specifications without notice and without any obligation or liability whatsoever. GENERAL GUIDELINES FOR DERATION: Altitude: Derate 1.3% per 100 m (328 ft.) elevation above 200 m (656 ft.)
up to a maximum elevation of 3000 m (9842 ft.). Temperature: Derate 2.0% per 10_C (18_F) temperature above 25_C (77_F) up to 50_C (122_F).
G4-118 (150RZGB) 10/08e
Alternator Specifications
Specifications Alternator D NEMA MG1, IEEE, and ANSI standards compliance for
temperature rise and motor starting.
Manufacturer Kohler
Type 4-Pole, Rotating-Field D Sustained short-circuit current of up to 300% of the rated
Exciter type Brushless, current for up to 10 seconds.
Permanent-Magnet
D Sustained short-circuit current enabling downstream circuit
Leads: quantity, type breakers to trip without collapsing the alternator field.
4S13 12, Reconnectable
4S15 4, 110--120/220--240 D Self-ventilated and dripproof construction.
Voltage regulator Solid State, Volts/Hz
D Vacuum-impregnated windings with fungus-resistant epoxy
Insulation: NEMA MG1 varnish for dependability and long life.
Material Class H
Temperature rise 130_C, Standby D Fast-Responset II brushless alternator with brushless
Bearing: quantity, type 1, Sealed exciter for excellent load response.
Coupling Flexible Disc
Amortisseur windings Full
Voltage regulation, no-load to full-load
Permanent magnet (PM) alternator ±2% Average
550 controller (with 0.5% drift
due to temperature variation) 3-Phase Sensing, ±0.25%
Unbalanced load capability 100% of Rated Standby
Current
One-step load acceptance 100% of Rating
Peak motor starting kVA: (35% dip for voltages below)
480 V, 380 V 4S13 (12 lead) 515 (60Hz), 370 (50Hz)
480 V, 380 V 4S15 (12 lead) 620 (60Hz), 420 (50Hz)
Application Data
Engine Engine Electrical
Engine Specifications 60 Hz 50 Hz Engine Electrical System 60 Hz 50 Hz
Manufacturer General Motors Ignition system Individual Coil
Engine: model, type Industrial Powertrain, Near Plug Ignition
Vortec 8.1 L, 4-Cycle, Battery charging alternator:
Turbocharged and Ground (negative/positive) Negative
Charge Air-Cooled
Volts (DC) 12
Cylinder arrangement V-8
Ampere rating 70
Displacement, L (cu. in.) 8.1 (496)
Starter motor rated voltage (DC) 12
Bore and stroke, mm (in.) 108 x 111 (4.25 x 4.37)
Battery, recommended cold cranking
Compression ratio 9.1:1 amps (CCA):
Piston speed, m/min. (ft./min.) 399 (1311) 332 (1092) Qty., rating for --18_C (0°F) 1, 630
Main bearings: quantity, type Alum. Lead Silicon Alloy Battery voltage (DC) 12
Rated rpm 1800 1500
Max. power at rated rpm, kW (HP) 170 (228) 149 (200) Fuel
Cylinder head material Cast Iron Fuel System 60 Hz 50 Hz
Piston type and material Strutless Flat Top, Fuel type Natural Gas
Hypereutectic Cast Alum. Fuel supply line inlet 1.5 NPTF
Crankshaft material Cast Nodular Undercut Natural gas/LPG (vapor withdrawal) fuel
Rolled Fillet supply pressure, measured at the
Governor: type, make Electronic generator set fuel inlet after any fuel
Frequency regulation, no-load to full-load Isochronous system equipment accessories,
kPa (in. H2O) 1.74--2.74 (7.0--11.0)
Frequency regulation, steady state ±0.5%
Frequency Field-Convertible Fuel Composition Limits * Natural Gas
Air cleaner type, all models Dry Methane, % by volume 90 min.
Ethane, % by volume 4.0 max.
Exhaust
Propane, % by volume 1.0 max.
Exhaust System 60 Hz 50 Hz Propene, % by volume 0.1 max.
Exhaust manifold type Dry C4 and higher, % by volume 0.3 max.
Exhaust flow at rated kW, m3/min. (cfm) 30.1 (1063) 23.7 (837) Sulfur, ppm mass 25 max.
Exhaust temperature at rated kW, dry Lower heating value,
exhaust, _C (_F) 649 (1200) kJ/m3 (Btu/ft3), min. 26.6 (890)
Maximum allowable back pressure,
kPa (in. Hg) * Fuels with other compositions may be acceptable. If your fuel is
10.2 (3.0)
outside the listed specifications, contact your local distributor for
Exhaust outlet size at engine hookup, further analysis and advice.
mm (in.) 71 (2.8)
Operation Requirements
Air Requirements 60 Hz 50 Hz
Radiator-cooled cooling air,
m3/min. (scfm)[ 340 (12000) 258 (9100)
Cooling air required for generator set
when equipped with city water cooling or
remote radiator, based on 14_C (25_F)
rise, m3/min. (cfm) 359 (12670) 261 (9240)
Combustion air, m3/min. (cfm) 10.3 (365) 7.9 (278)
Heat rejected to ambient air:
Engine, kW (Btu/min.) 84.2 (4790) 60.6 (3450)
Alternator, kW (Btu/min.) 16.0 (912) 12.5 (709)
] Air density = 1.20 kg/m3 (0.075 lbm/ft3).
Fuel Consumption 60 Hz 50 Hz
Natural Gas, m3/hr. (cfh) at % loadw Standby Rating
100% 54.7(1930) 50.2(1770)
75% 42.9(1512) 38.0(1340)
50% 31.5 (1112) 27.4 (965)
25% 20.0 (707) 17.2 (607)
0% 10.4 (369) 8.8 (310)