Professional Documents
Culture Documents
Building and Environment: Ting Yao, Zhang Lin
Building and Environment: Ting Yao, Zhang Lin
a r t i c l e i n f o a b s t r a c t
Article history: This study aims to the investigate effects of the air terminal layout on the performance of stratum
Received 23 May 2014 ventilation. Experimental and numerical approaches were both applied. Six indices were used to eval-
Received in revised form uate the air distribution performance. A total of three air terminal layouts were investigated. The
9 August 2014
experimental results indicate that the exhaust location and the supply airflow rate can affect the air
Accepted 11 August 2014
diffusion performance. In the simulated cases, the effects of the exhaust location on the thermal comfort
Available online 20 August 2014
and indoor air quality can be observed. It was found that having the exhausts located at the bottom of the
wall helped with air mixing in the occupied zone. Thermal comfort and good air quality can be achieved
Keywords:
Air terminal layouts
with exhausts located at a lower level along the same wall as the supplies. This arrangement also helps to
Air diffusion performance index (ADPI) save space for system installation. Therefore, it is a better choice for stratum ventilation design if the
Stratum ventilation performance requirements are met.
Thermal sensation © 2014 Elsevier Ltd. All rights reserved.
Mean age of air
CO2 concentration
http://dx.doi.org/10.1016/j.buildenv.2014.08.016
0360-1323/© 2014 Elsevier Ltd. All rights reserved.
76 T. Yao, Z. Lin / Building and Environment 82 (2014) 75e86
Table 1 Table 2
Cooling load. Supply and exhaust location.
Occupants Equipment Layout Supply location & opening Exhaust location & opening
Table 4
Anthropometric data of subjects.
Gender Number Age Height, H (cm) Weight, W (kg) BMIa (kg/dm2) BSAb (m)
Mean S.D. Mean S.D. Mean S.D. Mean S.D. Mean S.D.
Female 16 19.6 1.2 159.0 5.2 49.7 6.2 19.7 2.1 1.5 0.1
Male 16 20.0 0.9 170.8 3.0 63.8 6.4 21.9 2.6 1.7 0.1
Total 32 19.8 1.1 164.9 7.3 56.8 9.5 20.8 2.6 1.6 0.2
a
Body mass index (BMI) ¼ (W/H2) 104.
b
Body surface area (BSA) ¼ (W0.425 H0.725) 0.007184.
the mean age of air and carbon dioxide (CO2) concentration. In this
study, the performance of stratum ventilation is evaluated by the
following parameters:
where
qeds ¼ effective draft temperature for mixing ventilation, K
Tx ¼ local airstream dry-bulb temperature, C.
Fig. 6. Temperature of measured points: (a) 1.1 m level and (b) 0.1 m level.
Tc ¼ average room dry-bulb temperature, C.
vx ¼ local airstream centerline speed, m/s
For stratum ventilation, the thermal comfort condition is good
if 0.6 K < qeds < 0.6 K, and is satisfactory if 1.2 K < qeds < 1.2 K
when the velocity is less than 0.8 m/s. The ADPI is defined as the
percentage of locations where measurements were taken, that
Fig. 7. EDTS of measured points (1e6, 1.1 m level; 7e11, 0.1 m level and 12e13, 0.6 m
level).
Table 5
ADPI for all cases.
Case 1 2 3 4 5 6 7 8 9
ADPI 92.3% 92.3% 84.6% 100% 69.2% 92.3% 84.6% 92.3% 76.9%
Table 6
Thermal sensation.
Case 1 2 3
meet these specifications for effective draft temperature and ve- mark down his/her instantaneous thermal sensation, together with
locity [22]. If the ADPI is at the maximum (approaching 100%), the their opinions on the air temperature and speed. Based on the
most desirable conditions are achieved. Question 1 in questionnaire, the average thermal sensation of each
In Cases 1e3, tests of thermal sensations and comfort were case and standard deviation was calculated. The first two questions
conducted using human subjects under various experimental of the survey are as follow:
conditions. Thirty-two college-aged students in good health were Q1: Please choose one choice indicating your thermal sensation:
employed to participate in this work. This test was conducted , cold (3), , cool (2), , slightly cool (1), , neutral (0), ,
during the summer break of 2013. The clo-value was limited to 0.57 slightly warm (þ1), , warm (þ2) and , hot (þ3).
(1 clo ¼ 0.155 m2 k/w). The activity level was 1.1 met because the Q2: Please choose one choice indicating your thermal comfort:
occupants in the classroom were sedentary. The anthropometric , comfortable (þ1), , slightly uncomfortable (þ2), , un-
data of the subjects are illustrated in Table 4. The questionnaire comfortable (þ3), and , very uncomfortable (þ4).
used for the test is based on the thermal sensation vote of the The mean local air age is defined as the average lifetime of the
ASHRAE 7-point scale, i.e 3, 2, 1, 0, 1, 2, and 3 representing cold, air at a particular location and gives an indication of the “freshness”
cool, slightly cool, neutral, slightly warm, warm, and hot, respec- of the air. It normally assumes that the age of the air at the inlet is
tively. The entire thermal sensation test with 16 subjects took about equal to zero, where it is the youngest [23]. Several researchers
2 h. During each 20-min session, each student was requested to have adopted the mean age of air as an indicator of the indoor air
T. Yao, Z. Lin / Building and Environment 82 (2014) 75e86 81
!
v v v vt
ðrtÞ þ ruj t ¼ Gt þr (2)
vt vxj vxj vxj
To fully study stratum ventilation performance with various air layout, fresh airflows reach the opposite wall and then recirculated.
terminal layouts, the velocity, temperature, local mean age of air This helps to improve the air quality in the lower upper zones,
and CO2 concentration at the X ¼ 1.9 m plane and Y ¼ 1.1 m plane though this is not a useful provision under normal circumstances.
were shown in Figs. 11e18. When the supply airflow rate is 15 ACH, the air diffusion perfor-
In Figs. 11 and 12, under Layouts (a), (b) and (c) airflow patterns mance under such a layout cannot meet the requirements. This
are similar in most areas of classroom. At the X ¼ 1.9 m plane, an arrangement also helps to save the space for system installation. It
uneven velocity pattern is found in the occupied zone (0.0e1.1 m). is therefore a better choice for stratum ventilation design if the
The occupants sitting in the vicinity of an air supply terminal are performance requirements are met.
exposed to a higher velocity. The obvious difference is that for
Layout (b) when the air jet reaches the occupants, more fresh air
Acknowledgment
tends to flow downwards because of the suction effect of the ex-
hausts, resulting in less fresh air flowing to the occupants sitting in
The work described in this paper is supported by a General
the second row. At the Y ¼ 1.1 plane, it is observed that air velocity
Research Grant from the Research Grants Council of the Hong Kong
distributes relatively uniform in the second row of the occupied
Special Administrative Region, China (Project No. CityU 124712).
zone and the velocity is generally around 0.3 m/s.
The authors thank all the students who participated in the exper-
Temperatures at these two planes are shown in Figs. 13 and 14.
iments. We would like to express our gratitude to Mr. Yong Cheng
At the X ¼ 1.9 m plane, significant temperature gradient can be
and Miss Weiqin Wu for their assistance.
observed. Temperature of the upper zone (>1.6 m) is obviously
higher because of lamps. Temperature distributions under three
layouts are similar at Y ¼ 1.1 m plane. References
In term of the age of air in Fig. 15, the mean local air age of the
[1] Tian L, Lin Z, Liu J, Wang QW. Numerical study of indoor air quality and
occupied zone is in the range of 250e400 s. In regions of the air jets, thermal comfort under stratum ventilation. Prog Comput Fluid Dyn 2008;8(7/
the mean age of air is significantly younger. Compared with the 8):541e8.
other two layouts, the mean age of air under Layout (b) is relatively [2] Tian L, Lin Z, Wang QW. Comparison of gaseous contaminant diffusion under
stratum ventilation and under displacement ventilation. Build Environ
younger, especially for the second row of the occupied zone and 2010;45(9):2035e46.
upper zone. In Fig. 15, older age of air are found in the upper left [3] Lin Z, Lee CK, Fong KF, Chow TT, Yao T, Chan ALS. Comparison of annual en-
corner, where a quasi-stagnant zone is formed, with Layouts (a) and ergy performances with different ventilation methods for cooling. Energy
Build 2011;43:130e6.
(c), especially for Layout (a). That is because under Layouts (a) and
[4] Tian L, Lin Z, Wang QW, Liu J. Numerical investigation of indoor aerosol
(c), more fresh air from the supplies is directly exhausted by dif- particle dispersion under stratum ventilation and under displacement venti-
fusers located at the opposite wall. Under Layout (b), because the lation. Indoor Built Environ 2009;18(4):360e75.
exhausts and supplies are located at the same wall, some fresh air [5] Lin Z, Wang JL, Yao T. Investigation into anti-airborne infection performance
of stratum ventilation. Build Environ 2012;54:29e38.
reaches the opposite wall and then recirculated. However, insig- [6] Lin Z, Wang JL, Yao T, Chow TT, Fong KF. Numerical comparison of dispersion
nificant differences in the age of air at the 1.1 m plane are found for of human exhaled droplets under different ventilation methods. World Rev
these three layouts. Sci Technol Sustain Dev 2013;10:142e61.
[7] Lin Z, Yao T, Chow TT, Fong KF, Chan LS. Performance evaluation and design
Figs. 17 and 18 show the CO2 concentration under the three guidelines for stratum ventilation. Build Environ 2011;46:2267e79.
layouts. In Fig. 17, the average CO2 concentration for the occupied [8] Lin Z, Chow TT, Tsang CF, Fong KF, Chan LS. CFD study on effect of the air
breathing zone is between 540 and 610 ppm, which is well below supply location on the performance of the displacement ventilation system.
Build Environ 2005;40:1051e67.
the limits stipulated in the Hong Kong IAQ Certification Scheme for [9] Khan JA, Feigley CE, Lee E, Ahmed MR. Effects of inlet and exhaust locations
the Excellent Class (<800 ppm for an 8-h average) [30]. The CO2 and emitted gas density on indoor air contaminant concentrations. Build
levels are the same under all three layouts, but the distribution is Environ 2006;41:851e63.
[10] Lau J, Chen QY. Floor-supply displacement ventilation for workshops. Build
slightly different. The CO2 concentration of the occupied zone
Environ 2007;42:1718e30.
distributes relatively uniformly under Layout (a). For the occupants [11] Kuo JY, Chung KC. The effect of diffuser's location on thermal comfort analysis
sitting in the second row, there is a slightly higher concentration of with different air distribution strategies. J Build Phys 1999;22:208e29.
[12] McCarry B. Underfloor air distribution systems: benefits and when to use the
CO2 under Layout (b). As mentioned above, that is because of the
system in building design. ASHRAE Trans 1995;101(2):902e11.
presence of the occupants and the exhaust location, causing the [13] Kline SJ, McClintock FA. Describing uncertainties in single-sample experi-
fresh air to flow downwards. At the Y ¼ 1.1 m plane, CO2 concen- ments. Mech Eng 1953;75:3e9.
tration in the air jet regions is significantly lower than that out of [14] Fong ML, Lin Z, Fong KF, Chow TT, Yao T. Evaluation of thermal comfort
conditions in a classroom with three ventilation methods. Indoor Air 2011;21:
the air jet regions. 231e9.
[15] Fluent. Fluent 6.2 user's guide. Lebanon, NH: Fluent Inc; 2005.
4. Conclusion [16] Lin Z, Tian L, Yao T, Wang Q, Chow TT. Experimental and numerical study of
room airflow under stratum ventilation. Build Environ 2011;46:235e44.
[17] ASHRAE. Thermal environmental conditions for human occupancy. ANSI/
This study focused on the effect of air terminal layouts on ASHRAE standard 55e2010. ASHRAE, Inc; 2010.
stratum ventilation. Both experimental and numerical approaches [18] Koestel A, Tuve GL. Performance and evaluation of room air distribution
systems. ASHRAE Trans 1955;61:533.
were used. A total of three different air terminal layouts were [19] Reinmann JJ, Koestel A, Tuve GL. Evaluation of three room air distribution
studied. The experimental and numerical results indicate that the systems for summer cooling. ASHRAE Trans 1959;65:717.
exhausts location can affect the indoor thermal comfort and air [20] Rydberg J, Norback P. Air distribution and draft. ASHVE Trans 1949;55:225.
[21] Lin Z. Effective draft temperature for evaluating the performance of stratum
quality. Having exhausts located at the bottom of the wall helps ventilation. Build Environ 2011;46:1843e50.
with air mixing in the occupied zone. Similar performances in age [22] ASHRAE. ASHRAE handbook-fundamentals. Atlanta: American Society of
of and CO2 concentration are observed with Layouts (a) and (c). In Heating, Refrigerating and Air-Conditioning Engineers, Inc; 2009.
[23] Grieve PW. Measuring ventilation using trace-gases. Denmark: Brüel and
these cases, fresh air tends to flow from supplies directly to ex-
Kjær; 1989.
hausts. Quasi-stagnant zones are formed above and under this [24] Me ndez C, San Jose JF, Villafruela JM, Castro F. Optimization of a hospital room
supply air stratum. The ages of air of these quasi-stagnant zones are by means of CFD for more efficient ventilation. Energy Build 2008;40:849e54.
older. When the supply airflow rate is 10 ACH, a layout with the [25] Buratti C, Mariani R, Moretti E. Mean age of air in a naturally ventilated office:
experimental data and simulations. Energy Build 2011;43:2021e7.
exhausts located at the same wall as the supplies performs better, [26] Fiser J, Jicha M. Impact of air distribution system on quality of ventilation in
achieving good thermal comfort and indoor air quality. Under this small aircraft cabin. Build Environ 2013;69:171e82.
86 T. Yao, Z. Lin / Building and Environment 82 (2014) 75e86
[27] Li X, Jiang Y. Calculation of age-of-air with velocity field. Paper presented at [29] Stonier R. CO2: powerful IAQ diagnostic tool. Heat Pip Air Cond 1995;67(3).
Post-IAQ 96 Seminar; 1996. Beijing. [30] Indoor Air Quality Management Group. Government of HKSAR. A guide
[28] Persily A. Evaluating building IAQ and ventilation with indoor carbon dioxide. on indoor air quality certification scheme for offices and public places;
ASHARE Trans 1997;103(2):193e204. 2003.