ARYEN MÜHENDİSLİK RAFT FOUNDATION DESIGN

1 - GENERAL
Ultimate strength design method is used for reinforced concrete design.
For the stability check of foundation earth cone method is used.It is assumed that
sides of the cone make an angle (frustrum angle) with vertical.
Foundation design is checked according to overturning and compression.

2 - MATERIAL CHARACTERISTICS
Concrete : BS20 (C20)
Characteristic compressive strength of concrete 200 kg/cm2
Design compressive strength of concrete 130 kg/cm2
Design tensile strength of concrete 10,0 kg/cm2
Shear stregth of concrete 10 kg/cm2
Specific weigth of concrete 2400 kg/m3

Reinforcing steel bar :


St IIIa Yield strength of steel 4200 kg/cm2
Max.Allowable Design Stress 3.652 kg/cm2
St I Yield strength of steel 2200 kg/cm2
Max.Allowable Design Stress 1.913 kg/cm2

3 - LOADING
Loads are taken from Structural analysis/foundation loads sheets. Moments at base are
calculated according to these loads. (At both X and Y direction.)

4 - FOUNDATION TYPE
Raft type foundation are used for this antenna type of tower.

5 - SOIL PARAMETERS
Soil parameters are on the calculation sheets for each type of antenna tower.

REVISION Page No
ANTENNA TOWER a 08.04.
ANTENNA TOWER 30m 160-10 b 1
c
ARYEN MÜHENDİSLİK RAFT FOUNDATION DESIGN

SOIL PARAMETERS :

Unit Weight of Soil : 1800 kg/m3


Soil Bearing Capacity : 1 kg/cm2
Frustrum Angle : 30 °

Moments At Base

1)x-x Direction :

Mxx overturning == 445056 kgm


S.F. = 2
= 445056 kgm with safet factor

Hy horizontal = 120 kN Max H= 30 KN


= 12232 kg 3058,104 kg
= 24465 kg 6116,208 kg
V tension = 285 kN
= 29052 kg
= 58104 kg
Vcompres = 305 kN
= 31091 kg
= 62181 kg

2) y-y Direction :

Myy overturning = 0 kNm


= 0 kgm
S.F. = 1,5
= 0 kgm with safet factor

Hy horizontal = 0 kN
= 0 kg
= 0 kg

REVISION Page No
0 ANTENNA TOWER a 08.11.00
ANTENNA TOWER 30m 160-10 b 2
c
ARYEN MÜHENDİSLİK RAFT FOUNDATION DESIGN

A A tana= 0
0,60 0,60
3,300

0,20 HK

2,10 a H
0,55 3,300 0,55

0,50
T

Overturning Check = B= 5,000

Mtotal overturning = 445056 kgm

Vconcrete == B² * T + 4 * H* A²
= 16 m3

Vsoil = H / 3 ( B² + E² + B * E ) - Vchimney
= 79,8 m3
E = 7,425 m
W foundation == Vcon*2400+Vsoil*1800
= 181605 kg

SN = 185683 kg

e = 0,10 m ok
M resisting = SN*B/2
= 464207 kgm

F.S = M resisting / Mtotal overturning


= 1,04 overturning is not critical

Base Pressure Check =


s = SN / B2 (1+- 6e/B)
smax = 0,83 < 1,00 OK
smin = 0,65

Base Pressure Check(WHEN THERE IS TENSION ON THE BASE =


smax = 1,03

REVISION Page No
0 ANTENNA TOWER a 08.11.00
ANTENNA TOWER 30m 160-10 b 3
c
ARYEN MÜHENDİSLİK RAFT FOUNDATION DESIGN

Reinforcement Calculation =

a ) Raft Reinforcement =

M a-a = (( saa * L² ) / 2 + ( smax - saa ) * L² ) / 3 ) * B


M a-a = 626110 kgcm
saa = 0,81 kg/cm2

As = M a-a / fyd * j * d Use St IIIa(bottom) 21 f 16 Ast= 42


= 4 cm2 (top) 21 f 16 Ast= 42

Min. reinforcement Area = B * T * 0.0033 82,5 cm2

Use St IIIa 42 f 16 Ast= 84 Enough Reinf.


in both direction
b ) Chimney Reinforcement =

M = Hx,z * (H+HK)
= 1406728 kgcm

As = M / fyd * j * d
= 8,2 cm2 ( At one side )

Use St IIIa 6 f 16 Ast= 12 Enough Reinf.


Total Reinf: 20

10,0

10,0

10,0
5

c) Stirrups f 8/20 cm Use St I

REVISION Page No
0 ANTENNA TOWER a 08.11.00
ANTENNA TOWER 30m 160-10 b 4
c
ARYEN MÜHENDİSLİK RAFT FOUNDATION DESIGN

PUNCHING CHECK

Hn
T-5

Hn=A+2*((T-5)tan(45))/2 105,00 CM
Apunc=Hn*(T-5)*4 18900 CM2
Tp=Fcomp/Apunc = 3,3 kg/cm2 < 10 kg/cm2 OK

REVISION Page No
0 ANTENNA TOWER a 08.11.00
ANTENNA TOWER 30m 160-10 b 5
c