Substation Civil Design and Construction Standard
11.4 Access
Buildings must be located adjacent to a roadway or loading bay and access doors located to facilitate ease of
installation, operation and maintenance of equipment.
11.7 Roofing
Roof structures must consist of Colorbond steel (or equivalent), installed over sisalation on a prefabricated
steel trussed or skillion roof, in accordance with the relevant Authority’s requirements and the BCA. Skillion
roofs are only to be used where height restrictions dictate.
The roofing system must be designed and installed so as to minimise maintenance over the design life of the
substation.
No penetrations are allowed in the roofing material.
Where environmental, industrial or agricultural pollution conditions are severe, alternative materials may be
required to comply with the requirements of this clause.
Page 31 of 47
Substation Civil Design and Construction Standard
11.1 Ceiling
A two-layer fire retardant plasterboard ceiling must be installed to comply with all relevant building
standards and comply with AS 1530.4 and the BCA for a 3 hours fire rating.
11.3 Insulation
The building must be insulated to AS 4859.1 as well as the provisions of the BCA to minimise fluctuating
temperatures within.
Page 32 of 47
Substation Civil Design and Construction Standard
11.6 Lighting
Page 33 of 47
Substation Civil Design and Construction Standard
relevant Local Authority, for approval prior to the commencement of the external lighting infrastructure.
Construction and installation of the outdoor lighting infrastructure must not commence until the design has
been approved in writing by TasNetworks .
All low voltage circuits must be installed in accordance with AS 3000.
11.4 Glazing
No glazing, skylights or windows will be permitted as part of the external facade of buildings.
Page 34 of 47
Substation Civil Design and Construction Standard
5 Transformers
Page 35 of 47
Substation Civil Design and Construction Standard
Where it is proposed to use existing transformer plinths, the design of the existing plinths must be checked
for the loadings of the new equipment. The size of the existing plinths must be suitable for the equipment to
be installed thereon, including jacking points, and must comply with this Standard.
Departure from design surfaces must not exceed 5 mm or 1 in 200 whichever is the lesser.
5.2 Firewalls
Page 36 of 47